3500/72M Recip Rod Position Monitor: Operation and Maintenance Manual
3500/72M Recip Rod Position Monitor: Operation and Maintenance Manual
3500/72M Recip Rod Position Monitor: Operation and Maintenance Manual
The following are trademarks of General Electric Company in the United States and other
countries:
ACM, Actionable Information, Actionable Information to the Right People at the Right
Time, ADRE, Asset Condition Management, Asset Condition Monitoring, Bently ALIGN,
Bently BALANCE, Bently DOCUVIEW, Bently LUBE, Bently PERFORMANCE, Bently Nevada,
CableLoc, ClickLoc, Data Manager, Decision Support, DemoNet, Dynamic Data Manager,
Engineer Assist, FieldMonitor, flexiTIM, FluidLoc, Helping You Protect and Manage All Your
Machinery, HydroScan, HydroView, Key ∅, Keyphasor, Machine Condition Manager 2000,
MachineLibrary, Machine Manager, MicroPROX, Move Data, Not People, Move
Information, Not Data, NSv, Prime Spike, PROXPAC, Proximitor, REBAM, RuleDesk, SE,
Seismoprobe, Smart Monitor, Snapshot, System 1, System Extender, TDXnet, TDIXconnX,
TipLoc, TorXimitor, Transient Data Manager, Trendmaster, TrimLoc, Velomitor
Contact Information
The following ways of contacting Bently Nevada are provided for those times when you
cannot contact your local representative:
ii
Additional Information
Notice:
This manual does not contain all the information required to operate and maintain
the product. Refer to the following manuals for other required information.
iii
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
iv
Contents
2. General Information.................................................................... 8
2.1 Triple Modular Redundant Description............................................................ 10
2.2 Available Data ................................................................................................ 10
2.2.1 Statuses .......................................................................................... 10
2.2.2 Proportional Values ......................................................................... 12
2.3 LED Descriptions............................................................................................ 13
3. Configuration Information........................................................ 15
3.1 Software Configuration Options ...................................................................... 15
3.1.1 Recip Rod Position Monitor Configuration Options .......................... 16
3.1.2 Rod Position Single Channel Configuration ..................................... 18
3.1.3 Rod Position Pair Channel Configuration......................................... 26
3.1.4 Rod Drop Channel Configuration..................................................... 34
3.1.5 Hyper Channel Configuration .......................................................... 41
3.1.6 Rod Position Transducer Calibration ............................................... 47
3.2 Setpoints ........................................................................................................ 51
3.3 Software Switches .......................................................................................... 53
5. Maintenance .............................................................................. 67
5.1 Verifying a 3500 Rack – Recip Rod Position Monitor Module ......................... 67
5.1.1 Choosing a Maintenance Interval .................................................... 67
5.1.2 Required Test Equipment and Setup............................................... 68
v
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
5.1.3 Typical Verification test setup........................................................... 70
5.1.4 Using the Rack Configuration Software............................................ 71
5.1.5 Rod Position Single Channels.......................................................... 74
5.1.6 Rod Position Pair Channels ............................................................. 93
5.1.7 Rod Drop Channels ....................................................................... 114
5.1.8 Hyper Channels ............................................................................. 124
5.1.9 Verify Recorder Outputs................................................................. 137
5.1.10 If a Channel Fails a Verification Test .............................................. 138
6. Troubleshooting...................................................................... 139
6.1 Self-test......................................................................................................... 139
6.2 LED Fault Conditions .................................................................................... 140
6.3 System Event List Messages ........................................................................ 140
6.4 Alarm Event List Messages........................................................................... 150
vi
Section 1 - Receiving and Handling
1. Do not discharge static electricity onto the circuit board. Avoid tools
or procedures that would subject the circuit board to static damage. Some
possible causes include ungrounded soldering irons, nonconductive plastics,
and similar materials.
2. Personnel must be grounded with a suitable grounding strap (such as
3M Velostat No. 2060) before handling or maintaining a printed circuit board.
3. Transport and store circuit boards in electrically conductive bags or
foil.
4. Use extra caution during dry weather. Relative humidity less than 30
% tends to multiply the accumulation of static charges on any surface.
7
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
2. General Information
The 3500/72M Recip Rod Position Monitor is a four-channel monitor that accepts
input from Proximitor Transducers which measure the position of the
reciprocating rod on a rev-to-rev basis. The monitor uses this input to drive
alarms for protection and provide waveform data to System 1 for management
via 3500 TDI. The monitor can be programmed using the 3500 Rack
Configuration Software to perform any of the following functions: Rod Position-
Pair, Rod Position-Single, Rod Drop, and Hyper compressor Rod Movement.
The monitor can receive input from many types of transducers including the
following Bently Nevada transducers:
Proximitor Transducers
3300XL 8mm and 11mm
3300 8mm
7200 8mm, 11mm, and 14mm
8
Section 2 - General Information
9
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
The primary purpose of the 3500/72M monitor is to provide 1) machinery
protection by continuously comparing current machine wear against configured
alarm setpoints to drive alarms and, 2) essential machine wear information to
both operator and maintenance personnel. Alarm setpoints are configured using
the 3500 Rack Configuration Software. Alarm setpoints can be configured for
each active proportional value, and danger setpoints can be configured for two of
the active proportional values.
When shipped from the factory, the 3500/72M is delivered unconfigured. When
needed, the 3500/72M can be installed into a 3500 rack and configured to
perform the required monitoring function. This lets you stock a single monitor for
use as a spare for many different reciprocating compressor applications.
2.2.1 Statuses
The following statuses are provided by the Recip Rod Position Monitor. This
section describes the available statuses and where they can be found.
OK
This indicates if the monitor is functioning correctly. A NOT OK status is returned
under any of the following conditions:
- Module Hardware Failure
- Node Voltage Failure
- Configuration Failure
- Transducer Failure
- Slot ID Failure
- Channel not OK
10
Section 2 - General Information
If the Monitor OK status goes not OK, then the system OK Relay on the Rack
Interface I/O Module will be driven not OK.
Alert/Alarm 1
This indicates whether the monitor has entered Alert/Alarm 1. A monitor will enter
the Alert/Alarm 1 state when any proportional value provided by the monitor exceeds
its configured Alert/Alarm 1 setpoint.
Danger/Alarm 2
This indicates whether the monitor has entered Danger/Alarm 2. A monitor will enter
the Danger/Alarm 2 state when any proportional value provided by the monitor
exceeds its configured Danger/Alarm 2 setpoint.
Bypass
This indicates when the monitor has bypassed alarming for one or more proportional
values of a channel. When a channel bypass status is set, this monitor bypass
status will also be set.
Configuration Fault
This indicates if the monitor configuration is valid.
OK
This indicates that no fault has been detected by the associated Recip Rod Position
Monitor channel.
There are two types of channel OK checking: Transducer Input Voltage and
Transducer Supply Voltage A channel OK status will be deactivated if either of the
OK types goes not OK.
11
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Alert/Alarm 1
This indicates whether the associated monitor channel has entered Alert/Alarm 1. A
channel will enter the Alert/Alarm 1 state when any proportional value provided by
the channel exceeds its configured Alert/Alarm 1 setpoint.
Danger/Alarm 2
This indicates whether the associated monitor channel has entered Danger/Alarm 2.
A channel will enter the Danger/Alarm 2 state when any proportional value provided
by the channel exceeds its configured Danger/Alarm 2 setpoint.
Bypass
This indicates that the channel has bypassed alarming for one or more of its
proportional values. A channel bypass status may result from the following
conditions:
- The Keyphasor transducer associated with the channel has gone invalid
causing all proportional values associated with the Keyphasor to be
bypassed.
- The monitor has detected a serious internal fault.
- A software switch is bypassing any channel alarming function.
- The Special Alarm Inhibit is active and causing enabled alarms not to be
processed.
Off
This indicates whether the channel has been turned off. The monitor channels may
be turned off (inactivated) using the Rack Configuration Software.
(7) OK: Indicates that the Recip Rod Position Monitor and the Prox/Velom I/O module are operating
correctly.
(8) TX/RX: Flashes at the rate that messages are received and transmitted.
(9) BYPASS: Indicates that some of the monitor functions are temporarily suppressed.
13
Section 3 - Configuration Information
3. Configuration Information
This section describes how the 3500/72M Recip Rod Position Monitor is
configured using the Rack Configuration Software. It also describes any
configuration restrictions associated with this module. Refer to the 3500
Monitoring System Rack Configuration and Utilities Guide and the Rack
Configuration Software for the details on how to operate the software.
15
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
The type of Rack Interface Module installed in the rack (Standard or TMR). This field
is always set to standard since the Recip Rod Position Monitor can only be installed
in a standard rack.
Configuration ID
A unique six character identifier which is entered when a configuration is downloaded
to the 3500 rack.
16
Section 3 - Configuration Information
Prox/Velom Internal I/O
The transducer field wiring is connected directly to the I/O module.
Channel Type
The type of monitoring which is to be performed by the channel pair. The following
Channel types are available in the monitor:
- Rod Position Single
- Rod Position Pair
- Rod Drop
- Hyper
No Keyphasor
Can be used when a Keyphasor is not available. If this is marked, then it will restrict
data available for each channel type. Rod Position Single and Rod Position Pair
channel types will only have Position Magnitude, Position Angle, Pk-Pk, and Gap
measurements. Rod Drop will only allow Average measurements. Hyper channels
will only have Pk-Pk and Gap available.
Design Speed
When the No Keyphasor box is selected for Rod Position Single and Rod Position
Pair channel types, the configuration software creates a new box called Design
Speed. You are required to enter the designed operating RPM of the system.
Primary
The Keyphasor channel selected that is normally used for measurement. When this
Keyphasor transducer is marked invalid, the backup Keyphasor will provide the shaft
reference information.
Backup
The Keyphasor channel selected that will be used if the primary fails. If you do not
have a backup Keyphasor, select the same Keyphasor channel as the primary.
Piston Angle
17
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
When the piston hits top dead center, this is the angular measurement between the
centerline of the Keyphasor probe to the keyphasor leading edge. This is measured
to the left edge (for CCW rotating crankshaft) or to the right edge (for CW rotating
crankshaft) of the index notch on the crankshaft position wheel in the direction of
crank rotation when the piston is at Top Dead Center.
3.2.1.1.5 Channel
Active
Select whether the functions of the channel will be turned on () or off ().
Channel Selection
Use the pull down menu to determine which channel(s) are to be used with the
throw. Only one channel is used with Rod Position Single and Rod Drop channel
types. For Rod Position Pair and Hyper channel types, you must use dual channels,
either 1-2 or 3-4.
Configuration
A button used to display the configuration options for the selected channel type.
Barriers
Select the MTL 796(-) Zener External option, or Galvanic Isolators if external safety
barriers are connected between the monitor and the transducer. If the Prox/Accel
Internal Barrier I/O Module is selected for Slot Input/Output Module Type, the Internal
option is selected for you. These devices are used to restrict the amount of energy
that can flow into a hazardous area.
19
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Piston Material
The material from which the piston was made. The materials to choose from are
iron, steel, or aluminum.
Direction of Rotation:
The direction of the rotation of the crank shaft as viewed from the driver end of the
machine. This value will be Clockwise (CW) or Counter Clockwise (CCW).
Stroke
The length that the piston travels in one direction.
Probe Position
The distance from the crosshead pin pivot to the probe when the piston is at Top
Dead Center (TDC) at the head end of the cylinder.
Transducer Type
The following transducer types are available for the Rod Position Single NON-
BARRIER I/O modules:
- 3300 – 8mm
- 3300XL – 8mm
20
Section 3 - Configuration Information
- 3300XL – 11mm
- 7200 – 8mm
- 7200 – 11mm
- 7200 – 14mm
The following transducer types are available for the Rod Position Single BARRIER
I/O modules:
- 3300 – 8mm
- 3300XL – 8mm
- 3300XL – 11mm
- 7200 – 8mm
Transducer Orientation
The physical position of the transducer with respect to the rod. The orientation is
specified as 0 to 180 degrees left or right. Zero degrees is defined as follows:
For horizontal machines:
Stand at the driver end (crankshaft) and look towards the driven end (cylinder). Zero
degrees is located at the top (up) of the case; the 180 degree mark is located at the
bottom (down).
For vertical machines:
Stand at the top of the machine and look down. Zero degrees can be associated with
any recognizable physical reference point. Typically this might be set to the direction
“North”.
Note: Calibrate the selected transducer before continuing with the transducer
options.
Options Button
A button to display the configuration options for the selected transducer type.
CP Mod
Selecting the CP Mod button Channel Options Dialog Box, allows a Custom channel
configuration to be downloaded to the monitor. Custom configuration data is stored
in a Custom Products Modification File. Custom Products Modification files follow
the naming convention <modification #.mod>. These files must be located in the
\3500\Rackcfg\Mods\ directory. When a CP Mod file is selected, a window is
displayed which describes the function of the modification. CP Mod files are
available through Bently Nevada's Custom Products Division. Contact your local
Bently Nevada Sales Representative for details.
21
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Channel
The channel of the monitor being configured.
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
The type of Rack Interface Module installed in the rack (Standard or TMR). This field
is always set to standard since the Recip Rod Position Monitor can only be installed
in a standard rack.
22
Section 3 - Configuration Information
3.2.2.3.2 Enabled
An enabled proportional value specifies that the value will be provided by the
channel ( enabled, disabled).
Position Magnitude
The maximum value of the position vector magnitudes calculated every one degree
of crank rotation over one cycle. The position vector magnitudes are the rod center
position relative to a zero position representing the piston being concentric to the
cylinder bore.
Position Angle
The angle made by the vector representation of the maximum position magnitude.
Represents where the center of the rod is with respect to the zero position when the
position vector is at its maximum magnitude. 0 degrees is defined as vertical with
CW being positive rotation viewed from crank end. For Rod Position Single channel
types, Position Angle measurements can only be 0 or 180 degrees.
Crank Angle
The rotational angle of the crank corresponding to the axial position of the rod
(referenced from piston Top Dead Center) when the position vector is at its maximum
magnitude. Represents where the rod is located in its stroke when the position
vector is at its maximum magnitude. The crank angle is referenced from the piston
angle (TDC being 0 degrees) with positive rotation in the direction of crank rotation.
Pk Pk Displacement
Data which represents the overall peak to peak vibration. For the Recip Rod Position
Monitor the frequency response for Pk Pk displacement is always 1 to 600 Hz or 60
to 36,000 CPM.
Gap
A voltage representing the physical distance between the face of a proximity probe
tip and the observed surface. Standard polarity convention dictates that a
decreasing gap results in an increasing (less negative) output signal.
1X Amplitude
In a complex vibration signal, notation for the amplitude component that occurs at the
rotative speed frequency.
2X Amplitude
In a complex vibration signal, notation for the amplitude component having a
frequency equal to two times the shaft rotative speed.
Not 1X Amplitude
In a complex vibration signal, notation for the peak to peak amplitude of the wave
shape after the rotative speed component is removed.
Clamp Value
The value that a proportional value goes to when that channel or proportional value
is bypassed or defeated (For example when a problem occurs with the transducer).
23
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
The selected value can be between the minimum and maximum full-scale range
values. Only the values available from the Recorder Outputs, Communication
Gateway and Display Interface Module are clamped to the specified value when the
proportional value is invalid.
Recorder Output
The proportional value of a channel that is sent to the 4 to 20 mA recorder. The
recorder output is proportional to the measured value over the channel full scale
range. An increase in the proportional value that would be indicated as upscale on a
bar graph display results in an increase in the current at the recorder output.
If the channel is Bypassed, the output will be clamped to the selected clamp value or
to 2 mA (if the 2 mA clamp is selected).
Latching
Once an alarm is active it will remain active even after the proportional value enters
back into the configured non-alarm setpoint level. The channel will remain in alarm
until it is reset using one of the following methods:
- the reset switch on the front of the Rack Interface Module
- the contact on the Rack Interface I/O Module
- the Reset button in the Operator Display Software
- the reset command through the Communication Gateway Module
- the reset command through the Display Interface Module
- the reset command in the Rack Configuration Software
Nonlatching
When an alarm is active it will go inactive as soon as the proportional value enters
back into the configured non-alarm setpoint level.
Delay
The time which a proportional value must remain at or above an over alarm level or
below an under alarm level before an alarm is declared as active.
Alert
First level alarm that occurs when the transducer signal level exceeds the selected
Alert/Alarm 1 setpoint. This setpoint can be set on the Setpoint screen. The Alert
time delay is adjustable in one second intervals (from 1 to 60) for all available
proportional values.
Danger
Second level alarm that occurs when the transducer signal level exceeds the
selected Danger/Alarm 2 setpoint. This setpoint can be set on the Setpoint screen.
100 ms option
The 100 ms (typical) option applies to the Danger time delay only and has the
following results:
24
Section 3 - Configuration Information
If the 100 ms option is off ():
- The Danger time delay can be set at one second intervals (from 1 to 60).
- The Danger time delay can be set for up to two available proportional
values.
Setup Voltage
The voltage the channel’s transducer reads when the piston is at the setup crank
angle and is at rest in the cylinder on its initial rider band thickness (bottom
clearance).
Channel Offset
The distance aligned with the channel’s transducer that shows how far from ideal
center the rod is during setup when the piston is resting on its bottom rider band
thickness. A channel offset AWAY means that the rod is further away from the probe
face than when at ideal center. A channel offset TOWARD means that the rod is
closer to the probe face than when at ideal center.
26
Section 3 - Configuration Information
3.2.3.2 Rod Position Pair Channel Configuration Screen
This section describes the required inputs and options available on the Rod
Position Pair Channel Configuration screen.
Piston Material
The material from which the piston was made. The materials to choose from are
iron, steel, or aluminum.
27
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Piston Bottom Clearance
The measurement from the bottom of the piston to the cylinder internal diameter,
taken while the piston is at rest in the cylinder supported on its rider band(s).
Direction of Rotation:
The direction of the rotation of the crank shaft as viewed from the driver end of the
machine. This value will be Clockwise (CW) or Counter Clockwise (CCW).
Stroke
The length that the piston travels in one direction.
Probe Position
The distance from the crosshead pin pivot to the probe when the piston is at Top
Dead Center (TDC) at the head end of the cylinder.
Transducer Type
The following transducer types are available for the Rod Position Pair NON-
BARRIER I/O modules:
- 3300 – 8mm
- 3300XL – 8mm
- 3300XL – 11mm
- 7200 – 8mm
- 7200 – 11mm
- 7200 – 14mm
The following transducer types are available for the Rod Position Pair BARRIER I/O
modules:
- 3300 – 8mm
- 3300XL – 8mm
- 3300XL – 11mm
- 7200 – 8mm
28
Section 3 - Configuration Information
Transducer Orientation
The physical position of the transducer with respect to the rod. The orientation is
specified as 0 to 180 degrees left or right. Zero degrees is defined as follows:
For horizontal machines:
Stand at the driver end (crankshaft) and look towards the driven end (cylinder). Zero
degrees is located at the top (up) of the case; the 180 degree mark is located at the
bottom (down).
For vertical machines:
Stand at the top of the machine and look down. Zero degrees can be associated with
any recognizable physical reference point. Typically this might be set to the direction
“North”.
For Rod Position Pair channel type, transducer probes must be set at an angle apart
no less than 75 Degrees and no greater than 105 Degrees. For the best acuracy,
probes should be set as close to 90 Degrees apart as possible.
Note: Calibrate the selected transducer before continuing with the transducer
options.
Options Button
A button to display the configuration options for the selected transducer type.
CP Mod
Selecting the CP Mod button Channel Options Dialog Box, allows a Custom channel
configuration to be downloaded to the monitor. Custom configuration data is stored
in a Custom Products Modification File. Custom Products Modification files follow
the naming convention <modification #.mod>. These files must be located in the
\3500\Rackcfg\Mods\ directory. When a CP Mod file is selected, a window is
displayed which describes the function of the modification. CP Mod files are
available through Bently Nevada's Custom Products Division. Contact your local
Bently Nevada Sales Representative for details.
29
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
3.2.3.3 Rod Position Pair Channel Options Screen
This section describes the options available on the Rod Position Pair Channel
Transducer Options screen.
Channel
The channels of the monitor being configured.
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
The type of Rack Interface Module installed in the rack (Standard or TMR). This field
is always set to standard since the Recip Rod Position Monitor can only be installed
in a standard rack.
30
Section 3 - Configuration Information
3.2.3.3.2 Enabled
An enabled proportional value specifies that the value will be provided by the
channel ( enabled, disabled).
Position Magnitude
The maximum value of the position vector magnitudes calculated every one degree
of crank rotation over one cycle. The position vector magnitudes are the rod center
position relative to a zero position representing the piston being concentric to the
cylinder bore.
Position Angle
The angle made by the vector representation of the maximum position magnitude.
Represents where the center of the rod is with respect to the zero position when the
position vector is at its maximum magnitude. 0 degrees is defined as vertical with
CW being positive rotation viewed from crank end.
Crank Angle
The rotational angle of the crank corresponding to the axial position of the rod
(referenced from piston Top Dead Center) when the position vector is at its maximum
magnitude. Represents where the rod is located in its stroke when the position
vector is at its maximum magnitude. The crank angle is referenced from the piston
angle (TDC being 0 degrees) with positive rotation in the direction of crank rotation.
Pk Pk Displacement
Data which represents the overall peak to peak vibration. For the Recip Rod Position
Monitor the frequency response for Pk Pk displacement is always 1 to 600 Hz or 60
to 36,000 CPM.
Gap
A voltage representing the physical distance between the face of a proximity probe
tip and the observed surface. Standard polarity convention dictates that a
decreasing gap results in an increasing (less negative) output signal.
1X Amplitude
In a complex vibration signal, notation for the amplitude component that occurs at the
rotative speed frequency.
2X Amplitude
In a complex vibration signal, notation for the amplitude component having a
frequency equal to two times the shaft rotative speed.
Not 1X Amplitude
In a complex vibration signal, notation for the peak to peak amplitude of the wave
shape after the rotative speed component is removed.
Clamp Value
The value that a proportional value goes to when that channel or proportional value
is bypassed or defeated (For example when a problem occurs with the transducer).
31
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
The selected value can be between the minimum and maximum full-scale range
values. Only the values available from the Recorder Outputs, Communication
Gateway and Display Interface Module are clamped to the specified value when the
proportional value is invalid.
Recorder Output
The proportional value of a channel that is sent to the 4 to 20 mA recorder. The
recorder output is proportional to the measured value over the channel full scale
range. An increase in the proportional value that would be indicated as upscale on a
bar graph display results in an increase in the current at the recorder output
If the channel is Bypassed, the output will be clamped to the selected clamp value or
to 2 mA (if the 2 mA clamp is selected).
Latching
Once an alarm is active it will remain active even after the proportional value enters
back into the configured non-alarm setpoint level. The channel will remain in alarm
until it is reset using one of the following methods:
- the reset switch on the front of the Rack Interface Module
- the contact on the Rack Interface I/O Module
- the Reset button in the Operator Display Software
- the reset command through the Communication Gateway Module
- the reset command through the Display Interface Module
- the reset command in the Rack Configuration Software
Nonlatching
When an alarm is active it will go inactive as soon as the proportional value enters
back into the configured non-alarm setpoint level.
Delay
The time which a proportional value must remain at or above an over alarm level or
below an under alarm level before an alarm is declared as active.
Alert
First level alarm that occurs when the transducer signal level exceeds the selected
Alert/Alarm 1 setpoint. This setpoint can be set on the Setpoint screen. The Alert
time delay is adjustable in one second intervals (from 1 to 60) for all available
proportional values.
Danger
Second level alarm that occurs when the transducer signal level exceeds the
selected Danger/Alarm 2 setpoint. This setpoint can be set on the Setpoint screen.
100 ms option
The 100 ms (typical) option applies to the Danger time delay only and has the
following results:
32
Section 3 - Configuration Information
If the 100 ms option is off ():
- The Danger time delay can be set at one second intervals (from 1 to 60).
- The Danger time delay can be set for up to two available proportional
values.
If the 100 ms option is on ():
- The Danger time delay is set to 100 ms.
- The Danger time delay can only be set for the primary proportional value.
Setup Voltage
The voltage the channel’s transducer reads when the piston is at the setup crank
angle and is at rest in the cylinder on its initial rider band thickness (bottom
clearance).
Channel Offset
The distance aligned with the channel’s transducer that shows how far from ideal
center the rod is during setup when the piston is resting on its bottom rider band
thickness. A channel offset AWAY means that the rod is further away from the probe
face than when at ideal center. A channel offset TOWARD means that the rod is
closer to the probe face than when at ideal center.
33
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Rod Position Pair Channel Types—For the independent data values being
reported (those that only use the values from a single channel such as Pk-Pk
Displacement, Gap, 1X Amplitude, 2X Amplitude, Not 1X Amplitude): 1) the Not
OK will be reported in the channel status, 2) the proportional values will continue
to be calculated and reported, and 3) the channel will annunciate and maintain
an alarm if the data value in the Not OK condition exceeds the alarm setpoint.
For the composite data values (those that use the values from two channels such
as Position Magnitude, Position Angle, Crank Angle): if either channel goes Not
OK; 1) the appropriate channel status will be reported as Not OK, 2) the
composite data values will be reported as invalid, and.3) the channel pair will
defeat an alarm for the composite data values.
34
Section 3 - Configuration Information
3.2.4.2 Rod Drop Channel Configuration Screen
This section describes the required inputs and options available on the Rod Drop
Channel Configuration screen.
Stroke
The length that the piston travels in one direction.
Trigger Angle
The angular measurement of the crankshaft rotation in the direction of rotation from
the piston Top Dead Center (TDC) to the position at which the instantaneous
measurement will be taken. This is only applicable to Rod Drop channel type
configurations that have a Keyphasor.
35
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Probe Position
The distance from the crosshead pin pivot to the probe when the piston is at Top
Dead Center (TDC) at the head end of the cylinder.
Transducer Type
The following transducer types are available for the Rod Drop NON-BARRIER I/O
modules:
- 3300 – 8mm
- 3300XL – 8mm
- 3300XL – 11mm
- 7200 – 8mm
- 7200 – 11mm
- 7200 – 14mm
The following transducer types are available for the Rod Drop BARRIER I/O
modules:
- 3300 – 8mm
- 3300XL – 8mm
- 3300XL – 11mm
- 7200 – 8mm
Transducer Orientation
The physical position of the transducer with respect to the rod. The orientation is
specified as 0 to 180 degrees left or right. Zero degrees is defined as follows:
For horizontal machines:
36
Section 3 - Configuration Information
Stand at the driver end (crankshaft) and look towards the driven end (cylinder). Zero
degrees is located at the top (up) of the case; the 180 degree mark is located at the
bottom (down).
For vertical machines:
Stand at the top of the machine and look down. Zero degrees can be associated with
any recognizable physical reference point. Typically this might be set to the direction
“North”.
Note: Calibrate the selected transducer before continuing with the transducer
options.
Options Button
A button to display the configuration options for the selected transducer type.
CP Mod
Selecting the CP Mod button Channel Options Dialog Box, allows a Custom channel
configuration to be downloaded to the monitor. Custom configuration data is stored
in a Custom Products Modification File. Custom Products Modification files follow
the naming convention <modification #.mod>. These files must be located in the
\3500\Rackcfg\Mods\ directory. When a CP Mod file is selected, a window is
displayed which describes the function of the modification. CP Mod files are
available through Bently Nevada's Custom Products Division. Contact your local
Bently Nevada Sales Representative for details.
37
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
3.2.4.3 Rod Drop Channel Options Screen
This section describes the options available on the Rod Drop Channel
Transducer Options screen.
Channel
The channels of the monitor being configured.
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
The type of Rack Interface Module installed in the rack (Standard or TMR). This field
is always set to standard since the Recip Rod Position Monitor can only be installed
in a standard rack.
3.2.4.3.2 Enabled
An enabled proportional value specifies that the value will be provided by the
channel ( enabled, disabled).
38
Section 3 - Configuration Information
Average Piston Position
The time average (over the complete stroke) of the physical distance between the
face of the proximity probe tip and the observed rod with respect to the zero position
times the average correction factor.
Clamp Value
The value that a proportional value goes to when that channel or proportional value
is bypassed or defeated (For example when a problem occurs with the transducer).
The selected value can be between the minimum and maximum full-scale range
values. Only the values available from the Recorder Outputs, Communication
Gateway and Display Interface Module are clamped to the specified value when the
proportional value is invalid.
Recorder Output
The proportional value of a channel that is sent to the 4 to 20 mA recorder. The
recorder output is proportional to the measured value over the channel full scale
range. An increase in the proportional value that would be indicated as upscale on a
bar graph display results in an increase in the current at the recorder output.
If the channel is Bypassed, the output will be clamped to the selected clamp value or
to 2 mA (if the 2 mA clamp is selected).
Zero Position
The volts corresponding to the nominal DC shaft position. This voltage will be shown
on the user display.
Adjust Button
Adjust the Zero Position voltage. When this button is clicked, the current gap voltage
is automatically read into the Zero Position box. Since this utility provides active
feedback from the 3500 rack, a connection with the rack is required.
39
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Latching
Once an alarm is active it will remain active even after the proportional value enters
back into the configured non-alarm setpoint level. The channel will remain in alarm
until it is reset using one of the following methods:
- the reset switch on the front of the Rack Interface Module
- the contact on the Rack Interface I/O Module
- the Reset button in the Operator Display Software
- the reset command through the Communication Gateway Module
- the reset command through the Display Interface Module
- the reset command in the Rack Configuration Software
Nonlatching
When an alarm is active it will go inactive as soon as the proportional value enters
back into the configured non-alarm setpoint level.
Delay
The time which a proportional value must remain at or above an over alarm level or
below an under alarm level before an alarm is declared as active.
Alert
First level alarm that occurs when the transducer signal level exceeds the selected
Alert/Alarm 1 setpoint. This setpoint can be set on the Setpoint screen. The Alert
time delay is adjustable in one second intervals (from 1 to 60) for all available
proportional values.
Danger
Second level alarm that occurs when the transducer signal level exceeds the
selected Danger/Alarm 2 setpoint. This setpoint can be set on the Setpoint screen.
100 ms option
The 100 ms (typical) option applies to the Danger time delay only and has the
following results:
If the 100 ms option is off ():
- The Danger time delay can be set at one second intervals (from 1 to 60).
- The Danger time delay can be set for up to two available proportional
values.
If the 100 ms option is on ():
- The Danger time delay is set to 100 ms.
- The Danger time delay can only be set for the primary proportional value.
40
Section 3 - Configuration Information
41
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
3.2.5.2 Hyper Channel Configuration Screen
This section describes the options available on the Hyper Channel Configuration
screen.
Transducer Type
The following transducer types are available for the Hyper NON-BARRIER I/O
modules:
- 3300 – 8mm
- 3300XL – 8mm
- 3300XL – 11mm
- 7200 – 8mm
- 7200 – 11mm
- 7200 – 14mm
The following transducer types are available for the Hyper BARRIER I/O modules:
- 3300 – 8mm
- 3300XL – 8mm
42
Section 3 - Configuration Information
- 3300XL – 11mm
- 7200 – 8mm
Transducer Orientation
The physical position of the transducer with respect to the rod. The orientation is
specified as 0 to 180 degrees left or right. Zero degrees is defined as follows:
For horizontal machines:
Stand at the driver end (crankshaft) and look towards the driven end (cylinder). Zero
degrees is located at the top (up) of the case; the 180 degree mark is located at the
bottom (down).
For vertical machines:
Stand at the top of the machine and look down. Zero degrees can be associated with
any recognizable physical reference point. Typically this might be set to the direction
“North”.
Note: Calibrate the selected transducer before continuing with the transducer
options.
Options Button
A button to display the configuration options for the selected transducer type.
CP Mod
Selecting the CP Mod button Channel Options Dialog Box, allows a Custom channel
configuration to be downloaded to the monitor. Custom configuration data is stored
in a Custom Products Modification File. Custom Products Modification files follow
the naming convention <modification #.mod>. These files must be located in the
\3500\Rackcfg\Mods\ directory. When a CP Mod file is selected, a window is
displayed which describes the function of the modification. CP Mod files are
available through Bently Nevada's Custom Products Division. Contact your local
Bently Nevada Sales Representative for details.
43
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Channel
The channels of the monitor being configured.
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
The type of Rack Interface Module installed in the rack (Standard or TMR). This field
is always set to standard since the Recip Rod Position Monitor can only be installed
in a standard rack.
3.2.5.3.2 Enabled
An enabled proportional value specifies that the value will be provided by the
channel ( enabled, disabled).
Pk Pk Displacement
Data which represents the overall peak to peak vibration. For the Recip Rod Position
Monitor the frequency response for Pk Pk displacement is always 1 to 600 Hz or 60
to 36,000 CPM.
44
Section 3 - Configuration Information
Gap
A voltage representing the physical distance between the face of a proximity probe
tip and the observed surface. Standard polarity convention dictates that a
decreasing gap results in an increasing (less negative) output signal.
1X Amplitude
In a complex vibration signal, notation for the amplitude component that occurs at the
rotative speed frequency.
2X Amplitude
In a complex vibration signal, notation for the amplitude component having a
frequency equal to two times the shaft rotative speed.
Not 1X Amplitude
In a complex vibration signal, notation for the peak to peak amplitude of the wave
shape after the rotative speed component is removed.
Clamp Value
The value that a proportional value goes to when that channel or proportional value
is bypassed or defeated (For example when a problem occurs with the transducer).
The selected value can be between the minimum and maximum full-scale range
values. Only the values available from the Recorder Outputs, Communication
Gateway and Display Interface Module are clamped to the specified value when the
proportional value is invalid.
Recorder Output
The proportional value of a channel that is sent to the 4 to 20 mA recorder. The
recorder output is proportional to the measured value over the channel full scale
range. An increase in the proportional value that would be indicated as upscale on a
bar graph display results in an increase in the current at the recorder output.
If the channel is Bypassed, the output will be clamped to the selected clamp value or
to 2 mA (if the 2 mA clamp is selected).
Latching
Once an alarm is active it will remain active even after the proportional value enters
back into the configured non-alarm setpoint level. The channel will remain in alarm
until it is reset using one of the following methods:
- the reset switch on the front of the Rack Interface Module
- the contact on the Rack Interface I/O Module
45
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
- the Reset button in the Operator Display Software
- the reset command through the Communication Gateway Module
- the reset command through the Display Interface Module
- the reset command in the Rack Configuration Software
Nonlatching
When an alarm is active it will go inactive as soon as the proportional value enters
back into the configured non-alarm setpoint level.
Delay
The time which a proportional value must remain at or above an over alarm level or
below an under alarm level before an alarm is declared as active.
Alert
First level alarm that occurs when the transducer signal level exceeds the selected
Alert/Alarm 1 setpoint. This setpoint can be set on the Setpoint screen. The Alert
time delay is adjustable in one second intervals (from 1 to 60) for all available
proportional values.
Danger
Second level alarm that occurs when the transducer signal level exceeds the
selected Danger/Alarm 2 setpoint. This setpoint can be set on the Setpoint screen.
100 ms option
The 100 ms (typical) option applies to the Danger time delay only and has the
following results:
46
Section 3 - Configuration Information
The shaft calibrator kit, p/n 330186, is one tool used to temporarily mount a
spindle micrometer to the piston rod so that the transducer curve can be
generated. The kit includes a spindle micrometer, strap, 4140 target button for
system verification with a collet for alignment, eight probe adapters to
accommodate most Bently Nevada proximity probes, and an instruction card.
A proximity probe is mounted so that the probe face is flush with the piston rod
(mechanical zero). It is then backed out in small increments where the voltages
are recorded for each gap. The usable linear range can then be calculated using
the recorded voltages.
The default linear range and gap mil increments are determined by the
transducer selected in the previous screen.
47
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
The gap voltage values may be recorded with conventional methods and directly
entered into the calibration screen. Blue values are determined by the software
to be outside the useable linear range of the selected transducer.
Note: If internal or external barriers are being used, it is critical that the gap
voltage be measured on the safe side of the barrier or errors will result in the
monitor setup.
Adjust Button
The Adjust button next to each voltage may be used to read values directly from the
transducer into the calibration screen. This feature requires that the computer used
for configuring be connected to the 3500 rack and all wiring be correct within the
system. You must also have the configuration on the previous screen downloaded to
the rack and the Gap must have been enabled in the Options screen and
downloaded using the 3500 Config software. When connected to the 3500 rack a
current Gap measurement is shown in the lower right hand corner.
Note: The Adjust Button reads the current voltage value of the system. Proper
care must be taken to match up the correct physical gap of the probe with the
corresponding voltage.
After the probe has been backed out to a new gap, wait a period of 10 to 15
seconds before taking the Adjust Button reading from the Current Gap Voltage.
This accounts for the gap voltage filter setting time.
It is important to run the calibration with the probe viewing an area of the piston
rod actually viewed during normal operation of the compressor.
Lower Gap
The Lower Gap is determined by picking the least negative voltage within the linear
range. It is the lower value in the range to be used, defines one end of the bar
graph, and defines one setpoint limit.
Upper Gap
The Upper Gap is determined by picking the most negative voltage within the linear
range. It is the upper value in the range to be used, defines one end of the bar
graph, and defines one setpoint limit.
Note: The user must set the Upper and Lower Gaps after entering all the
transducer curve data. The upper and lower gaps must be within the linear
range of the transducer.
48
Section 3 - Configuration Information
Scale Factor
The calculated average scale factor within the chosen Upper and Lower Gaps. This
is the change in output per change in input (sensitivity) of a transducer.
OK Limits
The upper and lower OK limit voltages are displayed for reference.
Save Button
Calibration data will be saved for the channel as a text file that can be used for later
retrieval.
Load Button
Calibration data will be loaded for the channel from a saved calibration file.
To use data from a calibration file the transducer, barrier, and unit data must be
consistent with the current configured parameters.
49
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
3.2.6.2 Sample Transducer Calibration
The following calibration was made using a Tungsten Carbide target material.
The system included a 3300XL 8mm Proximitor and 5m probe combination. The
3500 rack was also connected to the software.
1. After the shaft calibrator kit was installed, the probe was backed out to 5 mils
of Gap. This value, -0.92 V, was input into the 5 mil voltage block using the
Adjust Button and reading from the Current Gap Voltage in the lower right
hand corner. Remember, the BLUE values are not used in linear range
calculations, but are only for reference.
2. The probe was then backed out to a 10 mil gap. Again, the Adjust Button
read the Current Gap Voltage and input the reading into the Voltage box.
3. The gap voltage was recorded in 5 mil increments until the voltage values
failed to change. This occurred at 85 mils of gap.
Note: Be sure to fill in all voltage spaces down to the bottom of the screen.
4. The ISF for every Gap Increment was calculated by the software along with
the percentage of deviation. The software automatically calculates the
useable linear range to be 55 mils. The useable linear range is defined as
50
Section 3 - Configuration Information
values with less than 10% deviation to its ISF and is within the OK limits of
the transducer. This is shown by the Black colored voltage values (10 to 65
mils).
5. The Lower Gap can be set to 10 mils (Least negative voltage inside the linear
range).
6. The Upper Gap can be set to 65 mils (Most negative voltage inside the linear
range).
3.3 Setpoints
This section specifies the available setpoints for each type of channel. A setpoint
is the level within the full-scale range that determines when an alarm occurs.
The 3500 Monitoring System allows Alert/Alarm 1 setpoints to be set for every
proportional value on each channel. The channel will drive an Alert/Alarm 1
indication if one or more of the channel proportional values exceeds its setpoints.
The 3500 Monitoring System also allows up to four Danger/Alarm 2 setpoints
(two over setpoints and two under setpoints) to be set for up to two of the
proportional values. You may select any two of the available proportional values
for the channel.
Note: The setpoint over and under limits can only be placed within the upper
and lower gap values of the specified transducer.
The following table lists the Alert/Alarm 1 and Danger/Alarm 2 setpoints available
for each channel pair type. The setpoint number is used in the Communication
Gateway and Display Interface Modules.
51
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Danger (Configurable)
All the Alert/Alarm 1 setpoints are provided first, followed by the configured
danger setpoints.
3.3.1.1.1 Example 1:
Rod Position Single with the Danger/Alarm 2 Over Gap setpoint and the
Danger/Alarm 2 Under Gap setpoint selected.
3.3.1.1.2 Example 2:
Rod Drop with the Danger/Alarm 2 Over Instantaneous Piston Position setpoint
selected.
Notes:
The alarming hysteresis for all channel configurations for a 72M Monitor is 1/64 of
Full Scale. When a channel exceeds an alarm setpoint, it must fall back below the
setpoint less the hysteresis before it can go out of alarm. For example, consider a
channel configuration with a 0–10 mils full scale and an alarm setpoint at 6 mils as
illustrated below:
52
Section 3 - Configuration Information
The hysteresis = 10 mils/64 = 0.16 mils. The channel input must fall below 6 mils -
0.16 mils (5.84 mils) before the channel is out of alarm.
53
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
3.4.1.1.1 Module Switches (Screen Not Shown)
Configuration Mode
A switch that allows the monitor to be configured. To configure the monitor, enable
(⌧)this switch and set the key switch on the front of the Rack Interface Module in the
PROGRAM position. When downloading a configuration from the Rack
Configuration Software, this switch will automatically be enabled and disabled by the
Rack Configuration Software. If the connection to the rack is lost during the
configuration process, use this switch to remove the module from Configuration
Mode.
Alert Bypass
When enabled, the channel does not perform Alert alarming functions.
Danger Bypass
When enabled, the channel does not perform Danger alarming functions.
Bypass
When enabled, the channel provides no alarming functions and supplies no
proportional values.
The channel switch number is used in the Communication Gateway and Display
Interface Modules.
4 Bypass
54
Section 4 - I/O Module Descriptions
55
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
(1) Connect the wire from the transducers associated with Channel 1 and 2.
(2) The jumper must be set to Prox/Accl transducer type for Channel 1 and 2.
(3) Connect the wire from the transducers associated with Channel 3 and 4.
(4) The jumper must be set to Prox/Accl transducer type for Channel 3 and 4.
(5) INHB/RET: Connect to an external switch. Used to inhibit all non-primary Alert/Alarm 1 functions
for all four channels.
(6) COM/REC: Connect each channel of the I/O module to a recorder.
56
Section 4 - I/O Module Descriptions
Refer to the 3500 Field Wiring Diagram Package for the recommended wiring.
Do not remove more than 6mm (0.25 in) of insulation from the wires.
57
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
(1) Connect the wire from the transducers associated with Channel 1 and 2.
(2) Connect the wire from the transducers associated with Channel 3 and 4.
(3) INHB/RET: Connect to an external switch. Used to inhibit all nonprimary Alert/Alarm 1 functions
for all four channels.
(4) COM/REC: Connect each channel of the I/O module to a recorder.
58
Section 4 - I/O Module Descriptions
(1) Connect the Prox/Velom I/O Module to the Proximitor External Termination Block using cable
129525-XXXX-XX.
(2) The jumper must be set to Prox/Accl transducer type for Channel 1 and 2.
(3) The jumper must be set to Prox/Accl transducer type for Channel 3 and 4.
(4) Connect the I/O module to the Recorder External Termination Block using Cable 129529-XXXX-
XX.
59
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
(1) Connect the wire from the transducers associated with Channel 1, 2, 3, and 4 to the External
Termination Block. INHB/RET: Connect to an external switch.
(2) Connect the I/O module to the External Termination Block using cable 129525-XXXX-XX
(3) Channel 1 and Channel 2
(4) Channel 3 and Channel 4
60
Section 4 - I/O Module Descriptions
4.4.1.2 Prox/Velom External Termination Block (Euro Style connectors)
(1) Connect the wire from the transducers associated with Channel 1, 2, 3, and 4 to the External
Termination Block. INHB/RET: Connect to an external switch.
(2) Connect the I/O module to the External Termination Block using cable 129525-XXXX-XX
(3) Channel 1 and Channel 2
(4) Channel 3 and Channel 4
61
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
4.4.1.3 Recorder External Termination Block (Terminal Strip connectors)
(1) Connect the recorders associated with Channel 1, 2, 3, and 4 to the Recorder External Termination
Block.
(2) Connect the I/O module to the Recorder External Termination Block using cable 129529-XXXX-
XX.
(3) Channel 1 and Channel 2
(4) Channel 3 and Channel 4
62
Section 4 - I/O Module Descriptions
4.4.1.4 Recorder External Termination Block (Euro Style connectors)
(1) Connect the recorders associated with Channel 1, 2, 3, and 4 to the Recorder External Termination
Block.
(2) Connect the I/O module to the Recorder External Termination Block using cable 129529-XXXX-
XX.
(3) Channel 1 and Channel 2
(4) Channel 3 and Channel 4
63
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
64
Section 4 - I/O Module Descriptions
Cable Number 129529-XXXX-XX
3500 Recorder Output to External Termination Block Cable
65
Section 5 -
5. Maintenance
The boards and components inside of 3500 modules cannot be repaired in the
field. Maintaining a 3500 rack consists of testing module channels to verify that
they are operating correctly. Modules that are not operating correctly should be
replaced with a spare.
This section shows how to verify the operation of channels in a Recip Rod
Position Monitor.
Section Topic
Number
5.1.1 Choosing a Maintenance Interval
5.1.2 Required Test Equipment
5.1.3 Typical Verification test setup
5.1.4 Using the Rack Configuration Software
5.1.5 Rod Position Single Channels
5.1.6 Rod Position Pair Channels
5.1.7 Rod Drop Channels
5.1.8 Hyper Channels
5.1.9 Verify Recorder Outputs
5.1.10 If a Channel Fails a Verification Test
67
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
5.1.2 Required Test Equipment and Setup
The verification procedures in this section require the following test equipment
and setup.
WARNING
High Voltage Present. Contact
could cause shock, burns, or
death.
Do not touch exposed wires or
terminals.
Application Alert: Tests will exceed alarm setpoint levels causing alarms to
activate. This could result in a relay contact state change.
68
Section 5 -
69
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
3. 40 KΩ Resistor
4. 100 µF Capacitor
5. Keyphasor Multiplier/Divider
6. Input Signal
7. Multimeter
8. Proximitor I/O Module
9. Function Generator
10. Power Supply
70
Section 5 -
Note: It is important to save the original rack configuration before doing any
Maintenance or Troubleshooting Procedures. It may be necessary during these
procedures to change setpoints, etc. which must be restored to their original
values at the conclusion of the procedures. At that time the original configuration
should be downloaded to the rack.
The Keyphasor module must not be configured for the Recip Multi-Event Wheel
to do the verification.
71
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
The following figures show how the Verification screen displays output from a
3500 rack:
(1) These fields display output for verifying channel alarms. Alert/Alarm 1 alarms are
displayed in yellow in the bar graph and with the word “Alarm” under the current value
box. Danger/Alarm 2 alarms are displayed in red in the bar graph and with the word
“Alarm” under the current value box.
(2) Current Value: The current proportional value is displayed in this box.
The Zero Position Voltage is the voltage input that will cause the reading on the
bar graph display and current value box to be zero. The Zero Position Volts
value is displayed in the Zero Position Volts box above each channel value bar
graph.
72
Section 5 -
73
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
WARNING
High Voltage Present. Contact
could cause shock, burns, or
death.
Do not touch exposed wires or
terminals.
Application Alert: Tests will exceed alarm setpoint levels causing alarms to
activate. This could result in a relay contact state change.
74
Section 5 -
Power Supply Function Generator Keyphasor Multiplier/Divider
Section Topic
Number
14. Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
15. Connect test equipment and run software as described in Section 5.1.2,
Required Test Equipment and Setup. Set the function generator to have
Sine wave output.
16. Set the Keyphasor multiplier/divider so that the multiply setting is one and the
divide setting is one. Turn down the Amplitude on the function generator to
have the minimum possible value and adjust the power supply DC voltage
level to produce a gap reading that results in a Position Magnitude that is
above (more negative than) the Calculated Center Voltage level and below
(less negative than) the Position Magnitude setpoint levels on the bar graph
display of the Verification screen.
17. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bar graph indicator for Position Magnitude is green, and
the Current Value field contains no alarm indication.
18. Increase (more negative) the power supply voltage such that the signal just
exceeds the Position Magnitude Over Alert/Alarm 1 setpoint level. Wait until
2 or 3 seconds after the alarm time delay expires and verify that the bar
graph indicator for Position Magnitude changes color from green to yellow
and that the Current Value Field indicates an Alarm.
19. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Position Magnitude remains yellow and that the Current Field still indicates
an Alarm.
20. Increase (more negative) the power supply such that the signal just exceeds
the Position Magnitude Over Danger/Alarm 2 setpoint level. Wait until 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for Position Magnitude changes color from yellow to red and that the
Current Value Field indicates an Alarm.
21. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Position Magnitude remains red and that the Current Value Field still
indicates an Alarm.
22. Decrease (less negative) the power supply voltage such that the gap signal
reads above the Calculated Center Voltage level and below the Over Alarm
setpoint levels. If the non-latching option is configured, observe that the bar
graph indicator for Position Magnitude changes color to green and that the
Current Value Box contains no indication of alarms. Press the RESET switch
on the RIM to reset latching alarms.
76
Section 5 -
23. Press the RESET switch on the RIM. Verify that the OK LED is on, the bar
graph indicator for Position Magnitude is green, and the Current Value field
contains no alarm indication.
24. Adjust the power supply level to produce a gap reading that is below (less
negative than) the Calculated Center Voltage level and results in a Position
Magnitude that is below (more negative than) the Position Magnitude setpoint
levels on the bar graph display of the Verification screen.
Note: The Position Magnitude value will always be positive. Notice when the
power supply voltage level crosses the Calculated Center Voltage level, the
Position Angle value changes by 180 degrees. This is the angle of the Position
Magnitude vector. This is always 0 or 180 only for Rod Position Single channel
types.
25. Press the RESET switch on the RIM. Verify that the OK LED is on, the bar
graph indicator for Position Magnitude is green, and the Current Value field
contains no alarm indication.
26. Decrease (less negative) the power supply voltage such that the signal just
exceeds the Position Magnitude Over Alert/Alarm 1 setpoint level. Wait until
2 or 3 seconds after the alarm time delay expires and verify that the bar
graph indicator for Position Magnitude changes color from green to yellow
and that the Current Value Field indicates an Alarm.
27. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Position Magnitude remains yellow and that the Current Field still indicates
an Alarm.
28. Decrease (less negative) the power supply such that the signal just exceeds
the Position Magnitude Over Danger/Alarm 2 setpoint level. Wait until 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for Position Magnitude changes color from yellow to red and that the
Current Value Field indicates an Alarm.
29. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Position Magnitude remains red and that the Current Value Field still
indicates an Alarm.
30. Increase (more negative) the power supply voltage such that the signal reads
below the Over Alarm setpoint levels. If the non-latching option is configured,
observe that the bar graph indicator for Position Magnitude changes color to
green and that the Current Value Box contains no indication of alarms. Press
the RESET switch on the RIM to reset latching alarms.
31. If you cannot verify any configured alarm, recheck the configured setpoints.
If the monitor still does not alarm properly or fails any other part of this test,
go to Section 5.1.10 (If a Channel Fails a Verification Test).
32. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET button on the RIM
to reset the OK LED.
33. Repeat steps 1 through 19 for all configured channels.
77
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
5.1.5.2.2 Pk Pk Displacement
34. Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
35. Connect test equipment and run software as described in Section 5.1.2,
Required Test Equipment and Setup. Set the function generator to have
Sine wave output.
36. Set the Keyphasor multiplier/divider so that the multiply setting is one and the
divide setting is one. Adjust the function generator amplitude to produce a
reading that is below the Pk-Pk Displacement setpoint level on the bar graph
display of the Verification screen.
37. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bargraph indicator for Pk-Pk Displacement is green, and
the Current Value field contains no alarm indication.
38. Adjust the function generator amplitude such that the signal just exceeds the
Pk-Pk Displacement Over Alert/Alarm 1 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for Pk-Pk Displacement changes color from green to yellow and that
the Current Value Field indicates an Alarm.
39. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Pk-Pk Displacement remains yellow and that the Current Value Field still
indicates an Alarm.
40. Adjust the function generator amplitude such that the signal just exceeds the
Pk-Pk Displacement Over Danger/Alarm 2 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for Pk-Pk Displacement changes color from yellow to red and that
the Current value Field indicates an Alarm.
41. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Pk-Pk Displacement remains red and that the Current Value Field still
indicates an Alarm.
42. Adjust the function generator amplitude such that the signal reads below the
Over Alarm setpoint levels. If the nonlatching option is configured, observe
that the bar graph indicator for Pk-Pk Displacement changes color to green
and that the Current Value Box contains no indication of Alarms. Press the
RESET switch on the RIM to reset latching alarms.
43. If you can not verify any configured alarm, recheck the configured setpoints.
If the monitor still does not alarm properly or fails any other part of this test,
go to Section 5.1.10 (If a Channel Fails a Verification Test).
44. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET button on the RIM
to reset the OK LED.
45. Repeat steps 1 through 11 for all configured channels.
78
Section 5 -
5.1.5.2.3 Gap
46. Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
47. Connect test equipment and run software as described in Section 5.1.2,
Required Test Equipment and Setup. Set the function generator to have
Sine wave output.
48. Set the Keyphasor multiplier/divider so that the multiply setting is one and the
divide setting is one. With minimal Amplitude level on the function generator,
adjust the power supply to produce a voltage that is within the Gap setpoint
levels on the Gap bar graph display of the Verification Screen.
49. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bargraph indicator for Gap is green and the Current Value
Field contains no alarm indication.
50. Adjust the power supply voltage such that the signal just exceeds the Gap
Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the alarm
time delay expires and verify that the bar graph indicator for Gap changes
color from green to yellow and that the Current Value Field indicates an
Alarm.
51. Press the RESET switch on the RIM. Verify that the OK LED is on, the
bargraph indicator for Gap is yellow and the Current Value Field indicates an
alarm.
52. Adjust the power supply voltage such that the signal just exceeds the Gap
Over Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the alarm
time delay expires and verify that the bar graph indicator for Gap changes
color from yellow to red and that the Current Value Field indicates an Alarm.
53. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Gap remains red and that the Current Value Field still indicates an Alarm.
54. Adjust the power supply voltage such that the signal reads below the Over
Alarm setpoint levels. If the nonlatching option is configured, observe that
the bar graph indicator for Gap changes color to green and that the Current
Value Box contains no idication of Alarms. Press the RESET switch on the
RIM to reset latching alarms.
55. Repeat steps 5 through 9 to test the Under Alert/Alarm 1 and Under
Danger/Alarm 2 setpoints by adjusting the power supply to exceed the Under
Alarm setpoint levels.
56. If you can’t verify any configured alarm, recheck the configured setpoints. If
the monitor still does not alarm properly or fails any other part of this test, go
to Section 5.1.10 (If a Channel Fails a Verification Test).
57. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET switch on the RIM
to reset the OK LED.
58. Repeat steps 1 through 12 for all configured channels.
79
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
5.1.5.2.4 1X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
59. Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
60. Connect test equipment and run software as described in Section 5.1.2,
Required Test Equipment and Setup. Set the function generator to have
Sine wave output.
61. Set the Keyphasor multiplier/divider so that the multiply setting is one and the
divide setting is one. Adjust the function generator amplitude to produce a
reading that is within the 1X Ampl setpoint levels on the 1X Ampl bar graph
display of the Verification screen.
62. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bargraph indicator for 1X Ampl is green and the Current
Value Field contains no alarm indication.
63. Adjust the function generator amplitude such that the signal just exceeds the
1X Ampl Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for 1X Ampl
changes color from green to yellow and that the Current Value Field indicates
an Alarm.
64. Press the RESET switch on the RIM. Verify that the bar graph indicator for
1X Ampl remains yellow and that the Current Value Field still indicates an
alarm.
65. Adjust the function generator amplitude such that the signal just exceeds the
1X Ampl Over Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after
the alarm time delay expires and verify that the bar graph indicator for 1X
Ampl changes color from yellow to red and that the Current Value Field
indicates an Alarm.
66. Press the RESET switch on the RIM. Verify that the bar graph indicator for
1X Ampl remains red and that the Current Value Field still indicates an Alarm.
67. Adjust the function generator amplitude such that the signal reads below the
Over Alarm setpoint levels. If the nonlatching option is configured, observe
that the bar graph indicator for 1X Ampl changes color to green and that the
Current Value Box contains no indication of Alarms. Press the RESET switch
on the RIM to reset latching alarms.
68. If you can’t verify any configured alarm, recheck the configured setpoints. If
the monitor still does not alarm properly or fails any other part of this test, go
to Section 5.1.10 (If a Channel Fails a Verification Test).
69. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET switch on the RIM
to reset the OK LED.
70. Repeat steps 1 through 11 for all configured channels.
80
Section 5 -
5.1.5.2.5 2X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
71. Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
72. Connect test equipment and run software as described in Section 5.1.2,
Required Test Equipment and Setup. Set the function generator to have
Sine wave output.
73. Set the Keyphasor multiplier/divider so that the multiply setting is one and the
divide setting is two. Adjust the function generator amplitude to produce a
reading that is within the 2X Ampl setpoint levels on the 2X Ampl bar graph
display of the Verification screen.
74. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bargraph indicator for 2X Ampl is green and the Current
Value Field contains no alarm indication.
75. Adjust the function generator amplitude such that the signal just exceeds the
2X Ampl Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for 2X Ampl
changes color from green to yellow and that the Current Value Field indicates
an Alarm.
76. Press the RESET switch on the RIM. Verify that the bar graph indicator for
2X Ampl remains yellow and that the Current Value Field still indicates an
alarm.
77. Adjust the function generator amplitude such that the signal just exceeds the
2X Ampl Over Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after
the alarm time delay expires and verify that the bar graph indicator for 2X
Ampl changes color from yellow to red and that the Current Value Field
indicates an Alarm.
78. Press the RESET switch on the RIM. Verify that the bar graph indicator for
2X Ampl remains red and that the Current Value Field still indicates an Alarm.
79. Adjust the function generator amplitude such that the signal reads below the
Over Alarm setpoint levels. If the nonlatching option is configured, observe
that the bar graph indicator for 2X Ampl changes color to green and that the
Current Value Box contains no indication of Alarms. Press the RESET switch
on the RIM to reset latching alarms.
80. If you can’t verify any configured alarm, recheck the configured setpoints. If
the monitor still does not alarm properly or fails any other part of this test, go
to Section 5.1.10 (If a Channel Fails a Verification Test).
81. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET switch on the RIM
to reset the OK LED.
82. Repeat steps 1 through 11 for all configured channels.
81
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
5.1.5.2.6 Not 1X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
83. Disconnect PWR, COM, and SIG field wiring from the channel terminals on
the I/O module.
84. Connect test equipment and run software as described in Section 5.1.2,
Required Test Equipment and Setup. Set the function generator to have
Sine wave output.
85. Set the Keyphasor multiplier/divider so that the multiply setting is one and the
divide setting is two. Adjust the function generator amplitude to produce a
reading that is within the Not 1X setpoint levels on the Not 1X bar graph
display of the Verification screen.
86. Press the RESET switch on the Rack Interface Module (RIM). Verify that the
OK LED is on, the bargraph indicator for Not 1X is green and the Current
Value Field contains no alarm indication.
87. Adjust the function generator amplitude such that the signal just exceeds the
Not 1X Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for Not 1X
changes color from green to yellow and that the Current Value Field indicates
an Alarm.
88. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Not 1X remains yellow and that the Current Value Field still indicates an
alarm.
89. Adjust the function generator amplitude such that the signal just exceeds the
Not 1X Over Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for Not 1X
changes color from yellow to red and that the Current Value Field indicates
an Alarm.
90. Press the RESET switch on the RIM. Verify that the bar graph indicator for
Not 1X remains red and that the Current Value Field still indicates an Alarm.
91. Adjust the function generator amplitude such that the signal reads below the
Over Alarm setpoint levels. If the nonlatching option is configured, observe
that the bar graph indicator for Not 1X changes color to green and that the
Current Value Box contains no indication of Alarms. Press the RESET switch
on the RIM to reset latching alarms.
92. If you can’t verify any configured alarm, recheck the configured setpoints. If
the monitor still does not alarm properly or fails any other part of this test, go
to Section 5.1.10 (If a Channel Fails a Verification Test).
93. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the I/O module. Verify that the OK LED
comes on and the OK relay energizes. Press the RESET switch on the RIM
to reset the OK LED.
Repeat steps 1 through 11 for all configured channels.
82
Section 5 -
5.1.5.3 Verify Channel Values – Rod Position Single
The general approach for testing channel values is to simulate the position and
Keyphasor input signals with a function generator and power supply. The output
values are verified by varying the input signal level and observing that the correct
results are reported in the Verification screen on the test computer.
Note: These parameters have an accuracy specification of ±1% of full scale for
amplitude.
Full Scale Voltage = Calculated Center Voltage - (Position Magnitude Top Scale
x Transducer Scale Factor)
Note: Use the Calculated Center Voltage and the Transducer Scale Factor
displayed on the Verification Screen.
Example 1:
Calculated Center Voltage = -10.250 Vdc
Position Magnitude Meter Top Scale = 40 mil
Transducer Scale Factor = 200mV/mil
Example 2:
Calculated Center Voltage = -10.25 Vdc
Position Magnitude Meter Top Scale = 800µm
Transducer Scale Factor = 7,874 mV/mm
= 7.874 mV/µm
98. Turn down the Amplitude on the function generator to have the minimum
possible value and adjust the power supply DC voltage level to the calculated
Full Scale voltage.
99. Verify that the Position Magnitude bar graph display and Current Value Box is
reading ±1% of full scale. If the recorder output is configured, refer to section
5.1.9 (Verify Recorder Outputs) for steps to verify the recorder output.
100. Verify the Position Angle bar graph display and Current Value Box is
reading correctly. If the Transducer Orientation is configured as 0°, the
Position Angle should read 180°. If the Transducer Orientation is configured
as 180°, the Position Angle should read 0°. If the recorder output is
83
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
configured, refer to section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
101. Set the power supply input voltage equal to the Calculated Center
Voltage. Verify that the Position Magnitude bar graph display and Current
Value Box is reading aproximately Zero. If the recorder output is configured,
refer to section 5.1.9 (Verify Recorder Outputs) for steps to verify the
recorder output.
102. Calculate the Opposite Full scale voltage according to the equation
and examples shown below.
Note: The Opposite Full scale voltage will result in a full scale reading on the
bar graph display and Current Value Box reading.
Example 1:
Calculated Center Voltage = -10.250 Vdc
Position Magnitude Meter Top Scale = 40 mil
Transducer Scale Factor = 200mV/mil
Example 2:
Calculated Center Voltage = -10.25 Vdc
Position Magnitude Meter Top Scale = 800µm
Transducer Scale Factor = 7,874 mV/mm
= 7.874 mV/µm
103. Turn down the Amplitude on the function generator to have the
minimum possible value and adjust the power supply DC voltage level to the
calculated Full Scale voltage.
104. Verify that the Position Magnitude bar graph display and Current
Value Box is reading ±1% of full scale. If the recorder output is configured,
refer to section 5.1.9 (Verify Recorder Outputs) for steps to verify the
recorder output.
105. Verify the Position Angle bar graph display and Current Value Box is
reading correctly. If the Transducer Orientation is at 0°, the Position Angle
should read 0°. If the Transducer Orientation is at 180°, the Position Angle
should read 180°. If the recorder output is configured, refer to section 5.1.9
(Verify Recorder Outputs) for steps to verify the recorder output.
106. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications of fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
107. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
84
Section 5 -
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
108. Repeat steps 1 through 13 for all configured channels.
109. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
110. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Triangle wave output.
111. Using a 2-Channel oscilloscope, look at the triangle wave at the input
to the monitor on one channel and look at the input to the keyphasor module
on the other channel. Be sure to look at the keyphasor signal on the I/O side
of the capacitor.
112. Set both channels of the oscilloscope to be DC coupled.
Note: Due to the low frequencies, making this measurement with the scope AC
coupled will introduce error in the Sync_Offset.
113. Measure and calculate the Crank Angle using the following
instructions and referencing the drawing below:
57. Turn down the DC offset to minimum level with out clipping the signal
on the triangle wave input channel so that it can be seen on the scope.
Adjust the vertical scale on the scope on the Keyphasor channel so that the
Keyphasor pulse can be seen.
Note: This may cause the channel to go Not OK and the proportional value to
go Invalid, but it will be reset after calculating the crank angle.
85
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
63. Adjust the DC offset of the triangle wave input such that the signal is
in the OK voltage range.
114. Verify that the Crank Angle bar graph display and Current Value Box
is reading approximately what was calculated above. If the recorder output is
configured, refer to section 5.1.9 (Verify Recorder Outputs) for steps to verify
recorder output.
115. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
116. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET button on
the Rack Interface Module (RIM) to reset the OK LED.
117. Repeat steps 1 through 8 for all configured channels.
5.1.5.3.3 Pk Pk Displacement
118. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
86
Section 5 -
119. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
120. Calculate the full scale voltage according to the equation and
examples shown below. Adjust the amplitude of the function generator to the
calculated Full Scale voltage.
Full Scale Voltage = Pk-Pk Displacement Meter Top Scale x Transducer Scale
Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
Direct Meter Top Scale = 40 mil
Transducer Scale Factor = 200mV/mil
Example 2:
Direct Meter Top Scale = 800µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
121. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Verify that the Pk-Pk Displacement bar graph
display and Current Value Box is reading ±1% of full scale. If the recorder
output is configured, refer to section 5.1.9 (Verify Recorder Outputs) for steps
to verify the recorder output.
122. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications of fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
123. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
124. Repeat steps 1 through 6 for all configured channels.
5.1.5.3.4 Gap
125. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
87
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
126. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
127. Adjust the power supply to produce a voltage equal to –18.00 Vdc on
the Volt Meter. Verify that the Gap bar graph display and Current Value Box
is reading –18.00 Vdc ±1% of Full Scale. If the recorder output is configured,
refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify recorder
output.
128. Adjust the power supply to produce a voltage equal to mid-scale on
the Volt Meter. Verify that the Gap bar graph display and Current Value Box
is reading the mid-scale value ±1% of Full Scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
129. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
130. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
131. Repeat steps 1 through 6 for all configured channels.
5.1.5.3.5 1X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
132. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
133. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
134. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated Full Scale voltage.
Full Scale Voltage = 1X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
1X Ampl Meter Top Scale = 40 mil
Transducer Scale Factor = 200 mV/mil
88
Section 5 -
Example 2:
1X Ampl Meter Top Scale = 800 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
135. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Verify that the 1X Ampl bar graph display and
Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
136. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
137. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
138. Repeat steps 1 through 6 for all configured channels.
5.1.5.3.6 2X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
139. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
140. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
141. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated Full Scale voltage.
Full Scale Voltage = 2X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
2X Ampl Meter Top Scale = 40 mil
Transducer Scale Factor = 200 mV/mil
89
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Example 2:
2X Ampl Meter Top Scale = 800 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
142. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Verify that the 2X Ampl bar graph display and
Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
143. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
144. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
145. Repeat steps 1 through 6 for all configured channels.
146. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
147. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
148. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated Full Scale voltage.
Full Scale Voltage = Not 1X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
Not 1X Ampl Meter Top Scale = 40 mil
Transducer Scale Factor = 200 mV/mil
90
Section 5 -
Vrms = 2.828 Vrms
Example 2:
Not 1X Ampl Meter Top Scale = 800 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
149. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Verify that the Not 1X Ampl bar graph display
and Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
150. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
151. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
152. Repeat steps 1 through 6 for all configured channels.
91
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Note: If the Danger Bypass has been activated, then the BYPASS LED will be
on. All other channels in the rack must be OK or bypassed for the relay to be
energized.
158. Verify that the OK relay on the Rack Interface I/O Module indicates
OK (energized). See 3500/20 Rack Interface Module Operation and
Maintenance Manual.
159. Increase the power supply voltage (more negative) until the OK LED
just goes off (upper limit). Verify that the Channel OK State line in the
Channel Status box reads not OK and that the OK Relay indicates not OK.
Verify that the Upper OK limit voltage displayed on the Verification screen is
equal to or more positive than the input voltage.
160. Decrease the power supply voltage (less negative) to -7.00 Vdc.
161. Press the RESET switch on the Rack Interface Module. Verify that
the OK LED comes back on and the OK relay energizes. Verify that the
Channel OK State line in the Channel Status box reads OK.
162. Gradually decrease the power supply voltage (less negative) until the
OK LED just goes off (lower limit). Verify that the Channel OK State line in
the Channel Status box reads not OK and that the OK Relay indicates not
OK. Verify that the Lower OK limit voltage displayed on the Verification
screen is equal to or more negative than the input voltage.
163. Increase the power supply voltage (more negative) to -7.00 Vdc.
164. Press the RESET switch on the Rack Interface Module. Verify that
the OK LED comes back on, the OK relay energizes, and that the Channel
OK State line in the Channel Status box reads OK.
165. If you cannot verify any configured OK limit, go to Section 5.1.10 (If a
Channel Fails a Verification Test).
166. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the Monitor I/O Module. Press
the RESET switch on the Rack Interface Module and verify that the OK LED
comes on and the OK relay energizes.
167. Repeat steps 1 through 14 for all configured channels.
168. Return the bypass switch for all configured channels to their original s
setting.
92
Section 5 -
93
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
WARNING
High Voltage Present. Contact
could cause shock, burns, or
death.
Do not touch exposed wires or
terminals.
Application Alert: Tests will exceed alarm setpoint levels causing alarms to
activate. This could result in a relay contact state change.
Connect the input from Channel 1 to the Channel 2 inputs at the I/O Module as
shown.
Note: Rod Position Pair Channel Types require input to two channels. This is
accomplished with one function generator by giving the same input to both
channels.
Note: When using the Software Verification screens for Rod Position Pair, the
screen for the first channel of the pair displays the Position Magnitude, Position
Angle, and Crank Angle proportional values. These are common/composite
proportional values, with all others being independent.
94
Section 5 -
5.1.6.1.2 Verification Screen Setup – Rod Position Pair
Run the Rack Configuration Software on the test computer. Choose Verification
from the Utilities menu and choose the proper Slot number and Channel number
then click on the Verify button.
The following table directs you to the starting page of each maintenance section
associated with the Rod Position Pair Channels:
Section Topic
Number
When varying the signal from an alarm condition to a non-alarm condition, alarm
hysteresis must be considered. Adjust the signal well below the alarm setpoint
for the alarm to clear.
95
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
5.1.6.2.1 Position Magnitude
Note: The Calculated Center Voltage value can be seen in the verification
screen.
172. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
173. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
Note: When using the Software Verification screens for Rod Position Pair, the
screen for the first channel of the pair displays the Position Magnitude, Position
Angle, and Crank Angle values. These are common/composite values between
the two channels, with all others being independent.
174. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Turn down the Amplitude on the function
generator to have the minimum possible value and adjust the power supply
DC voltage level to produce a gap reading that results in a Position
Magnitude that is above (more negative than) the Calculated Center Voltage
level and below (less negative than) the Position Magnitude setpoint levels
on the bar graph display of the Verification screen.
175. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bar graph indicator for Position Magnitude is
green, and the Current Value field contains no alarm indication.
176. Increase (more negative) the power supply voltage such that the
signal just exceeds the Position Magnitude Over Alert/Alarm 1 setpoint level.
Wait until 2 or 3 seconds after the alarm time delay expires and verify that the
bar graph indicator for Position Magnitude changes color from green to
yellow and that the Current Value Field indicates an Alarm.
177. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Position Magnitude remains yellow and that the Current Field still
indicates an Alarm.
178. Increase (more negative) the power supply such that the signal just
exceeds the Position Magnitude Over Danger/Alarm 2 setpoint level. Wait
until 2 or 3 seconds after the alarm time delay expires and verify that the bar
graph indicator for Position Magnitude changes color from yellow to red and
that the Current Value Field indicates an Alarm.
179. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Position Magnitude remains red and that the Current Value Field
still indicates an Alarm.
180. Decrease (less negative) the power supply voltage such that the gap
signal reads above (more negative) the Calculated Center Voltage level and
below (less negative) the Over Alarm setpoint levels. If the non-latching
option is configured, observe that the bar graph indicator for Position
Magnitude changes color to green and that the Current Value Box contains
no indication of alarms. Press the RESET switch on the RIM to reset latching
alarms.
96
Section 5 -
181. Press the RESET switch on the RIM. Verify that the OK LED is on,
the bar graph indicator for Position Magnitude is green, and the Current
Value field contains no alarm indication.
182. Adjust the power supply level to produce a gap reading that is below
(less negative) the Calculated Center Voltage level and results in a Position
Magnitude that is below (more negative than) the Position Magnitude setpoint
levels on the bar graph display of the Verification screen.
Note: The Position Magnitude value will always be positive.
183. Press the RESET switch on the RIM. Verify that the OK LED is on,
the bar graph indicator for Position Magnitude is green, and the Current
Value field contains no alarm indication.
184. Decrease (less negative) the power supply voltage such that the
signal just exceeds the Position Magnitude Over Alert/Alarm 1 setpoint level.
Wait until 2 or 3 seconds after the alarm time delay expires and verify that the
bar graph indicator for Position Magnitude changes color from green to
yellow and that the Current Value Field indicates an Alarm.
185. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Position Magnitude remains yellow and that the Current Field still
indicates an Alarm.
186. Decrease (less negative) the power supply such that the signal just
exceeds the Position Magnitude Over Danger/Alarm 2 setpoint level. Wait
until 2 or 3 seconds after the alarm time delay expires and verify that the bar
graph indicator for Position Magnitude changes color from yellow to red and
that the Current Value Field indicates an Alarm.
187. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Position Magnitude remains red and that the Current Value Field
still indicates an Alarm.
188. Increase (more negative) the power supply voltage such that the
signal reads below (more negative) the Over Alarm setpoint levels. If the
non-latching option is configured, observe that the bar graph indicator for
Position Magnitude changes color to green and that the Current Value Box
contains no indication of alarms. Press the RESET switch on the RIM to
reset latching alarms.
189. If you cannot verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
190. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
191. Repeat steps 1 through 20 for all configured channels.
5.1.6.2.2 Pk Pk Displacement
192. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
97
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
193. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
194. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Adjust the function generator amplitude to
produce a reading that is below the Pk-Pk Displacement setpoint level on the
bar graph display of the Verification screen.
195. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for Pk-Pk Displacement is
green, and the Current Value field contains no alarm indication.
196. Adjust the function generator amplitude such that the signal just
exceeds the Pk-Pk Displacement Over Alert/Alarm 1 setpoint level. Wait for
2 or 3 seconds after the alarm time delay expires and verify that the bar
graph indicator for Pk-Pk Displacement changes color from green to yellow
and that the Current Value Field indicates an Alarm.
197. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Pk-Pk Displacement remains yellow and that the Current Value
Field still indicates an Alarm.
198. Adjust the function generator amplitude such that the signal just
exceeds the Pk-Pk Displacement Over Danger/Alarm 2 setpoint level. Wait
for 2 or 3 seconds after the alarm time delay expires and verify that the bar
graph indicator for Pk-Pk Displacement changes color from yellow to red and
that the Current value Field indicates an Alarm.
199. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Pk-Pk Displacement remains red and that the Current Value
Field still indicates an Alarm.
200. Adjust the function generator amplitude such that the signal reads
below the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for Pk-Pk Displacement changes color to
green and that the Current Value Box contains no indication of Alarms.
Press the RESET switch on the RIM to reset latching alarms.
201. If you can not verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
202. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
203. Repeat steps 1 through 11 for all configured channels.
5.1.6.2.3 Gap
204. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
205. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
98
Section 5 -
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
206. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. With minimal Amplitude level on the function
generator, adjust the power supply to produce a voltage that is within the Gap
setpoint levels on the Gap bar graph display of the Verification Screen.
207. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for Gap is green and the
Current Value Field contains no alarm indication.
208. Adjust the power supply voltage such that the signal just exceeds the
Gap Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for Gap
changes color from green to yellow and that the Current Value Field indicates
an Alarm.
209. Press the RESET switch on the RIM. Verify that the OK LED is on,
the bargraph indicator for Gap is yellow and the Current Value Field indicates
an alarm.
210. Adjust the power supply voltage such that the signal just exceeds the
Gap Over Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for Gap
changes color from yellow to red and that the Current Value Field indicates
an Alarm.
211. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Gap remains red and that the Current Value Field still indicates
an Alarm.
212. Adjust the power supply voltage such that the signal reads below the
Over Alarm setpoint levels. If the nonlatching option is configured, observe
that the bar graph indicator for Gap changes color to green and that the
Current Value Box contains no idication of Alarms. Press the RESET switch
on the RIM to reset latching alarms.
213. Repeat steps 5 through 9 to test the Under Alert/Alarm 1 and Under
Danger/Alarm 2 setpoints by adjusting the power supply to exceed the Under
Alarm setpoint levels.
214. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
215. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
216. Repeat steps 1 through 12 for all configured channels.
5.1.6.2.4 1X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
99
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
217. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
218. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
219. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Adjust the function generator amplitude to
produce a reading that is within the 1X Ampl setpoint levels on the 1X Ampl
bar graph display of the Verification screen.
220. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for 1X Ampl is green and the
Current Value Field contains no alarm indication.
221. Adjust the function generator amplitude such that the signal just
exceeds the 1X Ampl Over Alert/Alarm 1 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for 1X Ampl changes color from green to yellow and that the Current
Value Field indicates an Alarm.
222. Press the RESET switch on the RIM. Verify that the bar graph
indicator for 1X Ampl remains yellow and that the Current Value Field still
indicates an alarm.
223. Adjust the function generator amplitude such that the signal just
exceeds the 1X Ampl Over Danger/Alarm 2 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for 1X Ampl changes color from yellow to red and that the Current
value Field indicates an Alarm.
224. Press the RESET switch on the RIM. Verify that the bar graph
indicator for 1X Ampl remains red and that the Current Value Field still
indicates an Alarm.
225. Adjust the function generator amplitude such that the signal reads
below the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for 1X Ampl changes color to green and
that the Current Value Box contains no indication of Alarms. Press the
RESET switch on the RIM to reset latching alarms.
226. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
227. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
228. Repeat steps 1 through 11 for all configured channels.
5.1.6.2.5 2X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
100
Section 5 -
229. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
230. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
231. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Adjust the function generator amplitude to
produce a reading that is within the 2X Ampl setpoint levels on the 2X Ampl
bar graph display of the Verification screen.
232. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for 2X Ampl is green and the
Current Value Field contains no alarm indication.
233. Adjust the function generator amplitude such that the signal just
exceeds the 2X Ampl Over Alert/Alarm 1 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for 2X Ampl changes color from green to yellow and that the Current
Value Field indicates an Alarm.
234. Press the RESET switch on the RIM. Verify that the bar graph
indicator for 2X Ampl remains yellow and that the Current Value Field still
indicates an alarm.
235. Adjust the function generator amplitude such that the signal just
exceeds the 2X Ampl Over Danger/Alarm 2 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for 2X Ampl changes color from yellow to red and that the Current
value Field indicates an Alarm.
236. Press the RESET switch on the RIM. Verify that the bar graph
indicator for 2X Ampl remains red and that the Current Value Field still
indicates an Alarm.
237. Adjust the function generator amplitude such that the signal reads
below the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for 2X Ampl changes color to green and
that the Current Value Box contains no indication of Alarms. Press the
RESET switch on the RIM to reset latching alarms.
238. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
239. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
240. Repeat steps 1 through 11 for all configured channels.
101
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
241. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
242. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
243. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Adjust the function generator amplitude to
produce a reading that is within the Not 1X setpoint levels on the Not 1X bar
graph display of the Verification screen.
244. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for Not 1X is green and the
Current Value Field contains no alarm indication.
245. Adjust the function generator amplitude such that the signal just
exceeds the Not 1X Over Alert/Alarm 1 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for Not 1X changes color from green to yellow and that the Current
Value Field indicates an Alarm.
246. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Not 1X remains yellow and that the Current Value Field still
indicates an alarm.
247. Adjust the function generator amplitude such that the signal just
exceeds the Not 1X Over Danger/Alarm 2 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for Not 1X changes color from yellow to red and that the Current
value Field indicates an Alarm.
248. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Not 1X remains red and that the Current Value Field still
indicates an Alarm.
249. Adjust the function generator amplitude such that the signal reads
below the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for Not 1X changes color to green and
that the Current Value Box contains no indication of Alarms. Press the
RESET switch on the RIM to reset latching alarms.
250. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
251. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
252. Repeat steps 1 through 11 for all configured channels.
102
Section 5 -
values are verified by varying the input signal level and observing that the correct
results are reported in the Verification screen on the test computer.
256. Record the transducer orientation angles from the monitor Options
screen. These angles are to be between 0° and 359° with 0° being vertical or
opposing gravity and going in the CW direction as viewed from the driver
end. These angles will be α1 and α2 for Channels 1 and 2 respectively.
Example:
α 1 = 10° Left (options screen) = 350°
α 2 = 85° Right (options screen) = 85°
257. Calculate β (the angle between the probes) with the following
equation:
β = α1 – α2
Example:
α1 = 350°
α2 = 85°
β = α1 – α2 = 350° - 85° = 265°
103
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
P1 and P2 are the DC offset Voltage value plus ½ of the Vpp Voltage value.
Note: Since the same input signal is going into Channel 1 and 2, the values of
P1 and P2 will be the same.
ZP1 and ZP2 are the Calculated Center Voltage levels given on the Software
Verification Screens. These values will most likely be different for each channel.
SF1 and SF2 are the probe Scale Factors for each channel given on the
Software Verification Screens.
259. Calculate the Position Magnitude vector value with the following
equation:
Position Magnitude (mils) = Sqrt(x’^2 + y’^2)
Example:
x’ = 30.0 mils
y’ = -32.7 mils
260. Verify that the Position Magnitude bar graph display and Current
Value Box is reading of the calculated value ±1% of Full Scale. If the
recorder output is configured, refer to section 5.1.9 (Verify Recorder Outputs)
for steps to verify the recorder output.
261. Transform the coordinates to the actual X and Y values of the position
vector with the following equations:
Φ = 90° - α1
x = x’CosΦ – y’SinΦ
y = x’SinΦ + y’CosΦ
Example:
Φ = 90° - 350°
Φ = -260°
x = 30.0*Cos(-260°) – (-32.7)*Sin(-260°)
x = -5.21 + 32.20
x = 26.99 mils
y = 30.0*Sin(-260°) + (-32.7)*Cos(-260°)
y = 29.54 + 5.68
y = 35.22 mils
262. Determine the Position Angle with the following rules and equations:
For y = 0
If x > 0 - Position Angle = 90°
104
Section 5 -
If x < 0 - Position Angle = 270°
If x = 0 - Position Angle = 0°
For y > 0
If x >= 0 - Position Angle = arctan (x/y)
If x < 0 - Position Angle = arctan (x/y) + 360°
Example:
x = 26.99 mils
y = 35.22 mils
y>0
x >= 0
Position Angle = arctan(26.99/35.22)
Position Angle = 37.5°
263. Verify that the Position Angle bar graph display and Current Value
Box is reading of the calculated value ±1% of Full Scale. If the recorder
output is configured, refer to section 5.1.9 (Verify Recorder Outputs) for steps
to verify the recorder output.
264. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications of fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
265. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
266. Repeat steps 1 through 13 for all configured channels.
267. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
268. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Triangle wave output.
269. Using a 2-Channel oscilloscope, look at the triangle wave at the input
to the monitor on one channel and look at the input to the keyphasor module
on the other channel. Be sure to look at the keyphasor signal on the I/O side
of the capacitor.
270. Set both channels of the oscilloscope to be DC coupled.
Note: Due to the low frequencies, making this measurement with the scope AC
coupled will introduce error in the Sync_Offset.
271. Measure and calculate the Crank Angle using the following
instructions and referencing the drawing below:
105
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
- Turn down the DC offset to minimum level with out clipping the signal on
the triangle wave input channel so that it can be seen on the scope.
Adjust the vertical scale on the scope on the keyphasor channel so that
the keyphasor pulse can be seen.
Note: This may cause the channel to go Not OK and the proportional value to
go Invalid, but it will be reset after calculating the crank angle.
- Adjust the DC offset of the triangle wave input such that the signal is in
the OK voltage range.
106
Section 5 -
272. Verify that the Crank Angle bar graph display and Current Value Box
is reading approximately what was calculated above. If the recorder output is
configured, refer to section 5.1.9 (Verify Recorder Outputs) for steps to verify
recorder output.
273. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
274. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET button on
the Rack Interface Module (RIM) to reset the OK LED.
275. Repeat steps 1 through 8 for all configured channels.
5.1.6.3.3 Pk Pk Displacement
276. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
107
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
277. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
278. Calculate the Full Scale voltage according to the equation and
examples shown below. Adjust the amplitude of the function generator to the
calculated voltage.
Full Scale Voltage = Pk-Pk Displacement Meter Top Scale x Transducer Scale
Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
Direct Meter Top Scale = 40 mil
Transducer Scale Factor = 200mV/mil
Example 2:
Direct Meter Top Scale = 800µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
279. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Verify that the Pk-Pk Displacement bar graph
display and Current Value Box is reading ±1% of full scale. If the recorder
output is configured, refer to section 5.1.9 (Verify Recorder Outputs) for steps
to verify the recorder output.
280. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications of fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
281. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
282. Repeat steps 1 through 6 for all configured channels.
5.1.6.3.4 Gap
283. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
108
Section 5 -
284. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
285. Adjust the power supply to produce a voltage equal to –18.00 Vdc on
the Volt Meter. Verify that the Gap bar graph display and Current Value Box
is reading –18.00 Vdc ±1% of Full Scale. If the recorder output is configured,
refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify recorder
output.
286. Adjust the power supply to produce a voltage equal to mid-scale on
the Volt Meter. Verify that the Gap bar graph display and Current Value Box
is reading the mid-scale value ±1% of Full Scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
287. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
288. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
289. Repeat steps 1 through 6 for all configured channels.
5.1.6.3.5 1X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
290. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
291. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
292. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated voltage with sinewave output.
Full Scale Voltage = 1X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
1X Ampl Meter Top Scale = 40 mil
Transducer Scale Factor = 200 mV/mil
109
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Example 2:
1X Ampl Meter Top Scale = 800 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
293. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Verify that the 1X Ampl bar graph display and
Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
294. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
295. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
296. Repeat steps 1 through 6 for all configured channels.
5.1.6.3.6 2X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
297. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
298. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
299. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated voltage with sinewave output.
Full Scale Voltage = 2X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
2X Ampl Meter Top Scale = 40 mil
Transducer Scale Factor = 200 mV/mil
110
Section 5 -
Vrms = (0.707/2) X (8)
Vrms = 2.828 Vrms
Example 2:
2X Ampl Meter Top Scale = 800 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
300. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Verify that the 2X Ampl bar graph display and
Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
301. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
302. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
303. Repeat steps 1 through 6 for all configured channels
304. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
305. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup and Section 5.1.6.1, Test
Equipment and Software Setup – Rod Position Pair. Set the function
generator to Sine wave output.
306. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated voltage with sinewave output.
Full Scale Voltage = Not 1X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
Not 1X Ampl Meter Top Scale = 40 mil
Transducer Scale Factor = 200 mV/mil
111
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
For Vrms input:
Vrms = (0.707/2) X (Vpp), for a sinewave input
Vrms = (0.707/2) X (8)
Vrms = 2.828 Vrms
Example 2:
Not 1X Ampl Meter Top Scale = 800 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
307. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Verify that the Not 1X Ampl bar graph display
and Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
308. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
309. Disconnect the test equipment and channel jumpers and reconnect
the PWR, COM, and SIG field wiring to the channel terminals on the I/O
module. Verify that the OK LED comes on and the OK relay energizes.
Press the RESET button on the RIM to reset the OK LED.
310. Repeat steps 1 through 6 for all configured channels.
112
Section 5 -
Note: If the Danger Bypass has been activated, then the BYPASS LED will be
on. All other channels in the rack must be OK or bypassed for the relay to be
energized.
316. Verify that the OK relay on the Rack Interface I/O Module indicates
OK (energized). See 3500/20 Rack Interface Module Operation and
Maintenance Manual.
317. Increase the power supply voltage (more negative) until the OK LED
just goes off (upper limit). Verify that the Channel OK State line in the
Channel Status box reads not OK and that the OK Relay indicates not OK.
Verify that the Upper OK limit voltage displayed on the Verification screen is
equal to or more positive than the input voltage.
318. Decrease the power supply voltage (less negative) to -7.00 Vdc.
319. Press the RESET switch on the Rack Interface Module. Verify that
the OK LED comes back on and the OK relay energizes. Verify that the
Channel OK State line in the Channel Status box reads OK.
320. Gradually decrease the power supply voltage (less negative) until the
OK LED just goes off (lower limit). Verify that the Channel OK State line in
the Channel Status box reads not OK and that the OK Relay indicates not
OK. Verify that the Lower OK limit voltage displayed on the Verification
screen is equal to or more negative than the input voltage.
321. Increase the power supply voltage (more negative) to -7.00 Vdc.
322. Press the RESET switch on the Rack Interface Module. Verify that
the OK LED comes back on, the OK relay energizes, and that the Channel
OK State line in the Channel Status box reads OK.
323. If you cannot verify any configured OK limit, go to Section 5.1.10 (If a
Channel Fails a Verification Test).
324. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the Monitor I/O Module. Press
the RESET switch on the Rack Interface Module and verify that the OK LED
comes on and the OK relay energizes.
325. Repeat steps 1 through 14 for all configured channels.
326. Return the bypass switch for all configured channels to their original
setting.
113
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
114
Section 5 -
WARNING
High Voltage Present. Contact
could cause shock, burns, or
death.
Do not touch exposed wires or
terminals.
Application Alert: Tests will exceed alarm setpoint levels causing alarms to
activate. This could result in a relay contact state change.
Section Topic
Number
115
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
5.1.7.2 Test Alarms – Rod Drop
The general approach for testing alarm setpoints is to simulate the position and
Keyphasor® input signals with a function generator and power supply. The
alarm levels are tested by varying the input signals and observing that the correct
results are reported in the Verification screen on the test computer. It is only
necessary to test those alarm parameters that are configured and being used.
The general test procedure to verify current alarm operation will include
simulating a transducer input signal and varying this signal:
327. to exceed over Alert/Alarm 1 and Danger/Alarm 2 Setpoints, and
328. to drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints
and
329. to produce a non-alarm condition.
When varying the signal from an alarm condition to a non-alarm condition, alarm
hysteresis must be considered. Adjust the signal well below the alarm setpoint
for the alarm to clear.
116
Section 5 -
337. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the bar graph indicator for Average Piston Position remains red and that
the Current Value Field still indicates an Alarm.
338. Adjust the power supply voltage such that the signal reads above the
Under Alarm setpoint levels. If the non-latching option is configured, observe
that the bar graph indicator for Average Piston Position changes color to
green and that the Current Value Box contains no indication of alarms. Press
the RESET switch on the Rack Interface Module (RIM) to reset latching
alarms.
339. If you can not verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
340. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET button on
the Rack Interface Module (RIM) to reset the OK LED.
341. Repeat steps 1 through 11 for all configured channels.
117
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
setpoint level. Wait until 2 or 3 seconds after the alarm time delay expires
and verify that the bar graph indicator for Instantaneous Piston Position
changes color from yellow to red and that the Current Value Field indicates
an Alarm.
349. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the bar graph indicator for Instantaneous Gap remains red and that the
Current Value Field still indicates an Alarm.
350. Adjust the power supply output such that the signal reads below the
Over Alarm setpoint levels. If the non-latching option is configured, observe
that the bar graph indicator for Instantaneous Piston Position changes color
to green and that the Current Value Box contains no indication of alarms.
Press the RESET switch on the Rack Interface Module (RIM) to reset
latching alarms.
351. If you can not verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Self Test).
352. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET button on
the Rack Interface Module (RIM) to reset the OK LED.
353. Repeat steps 1 through 11 for all configured channels.
Note: Use the Scale Factor (SF), Zero Position (ZP), and Average Correction
Factor (ACF) displayed on the Verification Screen.
358. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
359. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET button on
the Rack Interface Module (RIM) to reset the OK LED.
360. Repeat steps 1 through 6 for all configured channels.
361. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
362. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
363. Using a 2-Channel oscilloscope, look at the Sine wave at the input to
the monitor on one channel and look at the input to the keyphasor module on
the other channel. Be sure to look at the keyphasor signal on the I/O side of
the capacitor.
364. Set both channels of the oscilloscope to be DC coupled.
Note: Due to the low frequencies, making this measurement with the scope AC
coupled will introduce error in the Sync_Offset.
- Center the signal vertically about an axis on the scope. This makes it
easier to see the zero crossing.
- Measure the time of the full Keyphasor_Cycle_Time (6) as shown.
119
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
- Measure the time of the Sync_Offset_Time as shown (7). Calculate the
Sync_Offset_Angle:
120
Section 5 -
366. Verify that the Instantaneous Gap bar graph display, and Current
Value Box, is reading approximately what was calculated above. If the
recorder output is configured, refer to section 5.1.9 (Verify Recorder Outputs)
for steps to verify recorder output.
367. Using the equations shown below, calculate the Instantaneous Piston
Position. Verify that the Instantaneous Piston Position bar graph display, and
Current Value Box, is reading the calculated value ±1% of Full Scale. If the
recorder output is configured, refer to section 5.1.9 (Verify Recorder Outputs)
for steps to verify recorder output.
Note: Use the Scale Factor, Zero Position, and Instantaneous Correction Factor
displayed on the Verification Screen.
368. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
369. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET button on
the Rack Interface Module (RIM) to reset the OK LED.
370. Repeat steps 1 through 7 for all configured channels.
371. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the Rod Position I/O Module.
372. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup.
373. Bypass all other configured channels.
374. Adjust the power supply voltage to -7.00 Vdc.
375. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the monitor OK LED is on and that the Channel OK State line in the
Channel Status box of the Verification screen reads OK.
Note: If the Danger Bypass has been activated, then the BYPASS LED will be
on. All other channels in the rack must be OK or bypassed for the relay to be
energized.
376. Verify that the OK relay on the Rack Interface I/O Module indicates
OK (energized). See 3500/20 Rack Interface Module Operation and
Maintenance Manual.
122
Section 5 -
377. Increase the power supply voltage (more negative) until the OK LED
just goes off (upper limit). Verify that the Channel OK State line in the
Channel Status box reads Not OK and that the OK Relay indicates not OK.
Verify that the Upper OK limit voltage displayed on the Verification screen is
equal to or more positive than the input voltage.
378. Decrease the power supply voltage (less negative) to -7.00 Vdc.
379. Press the RESET switch on the Rack Interface Module. Verify that
the OK LED comes back on and the OK relay energizes. Verify that the
Channel OK State line in the Channel Status box reads OK.
380. Gradually decrease the power supply voltage (less negative) until the
OK LED just goes off (lower limit). Verify that the Channel OK State line in
the Channel Status box reads Not OK and that the OK Relay indicates not
OK. Verify that the Lower OK limit voltage displayed on the Verification
screen is equal to or more negative than the input voltage.
381. Increase the power supply voltage (more negative) to -7.00 Vdc.
382. Press the RESET switch on the Rack Interface Module. Verify that
the OK LED comes back on, the OK relay energizes, and that the Channel
OK State line in the Channel Status box reads OK.
383. If you cannot verify any configured OK limit, go to Section 5.1.10 (If a
Channel Fails a Verification Test).
384. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the Monitor I/O Module. Press
the RESET switch on the Rack Interface Module and verify that the OK LED
comes on and the OK relay energizes.
385. Repeat steps 1 through 14 for all configured channels.
386. Return the bypass switch for all configured channels to their original
setting.
Table 5-3 Rod Drop Default OK Limits Table
Transducer Lower OK Limit (Volts) Upper OK Limit (Volts)
3300 8 mm w/ Galvanic Isolation -1.1 -18.2
3300 8 mm w/ External barriers -1.1 -18.2
3300 8 mm w/ Internal barriers -1.28 -18.2
3300 8 mm w/o barriers -1.28 -19.04
3300XL 8 mm w/ Galvanic Isolation -1.1 -18.2
3300XL 8 mm w/ External barriers -1.1 -18.2
3300XL 8 mm w/ Internal barriers -1.28 -18.2
3300XL 8 mm w/o barriers -1.28 -19.04
3300XL 11 mm w/ Galvanic Isolation -1.1 -18.2
3300XL 11 mm w/ External barriers -1.1 -18.2
3300XL 11 mm w/ Internal barriers -1.28 -18.2
3300XL 11 mm w/o barriers -1.28 -19.04
7200 8 mm w/ Galvanic Isolation -1.1 -18.2
7200 8 mm w/ External barriers -1.1 -18.2
7200 8 mm w/ Internal barriers -1.28 -18.2
7200 8 mm w/o barriers -1.28 -19.04
7200 11 mm w/o barriers -3.55 -20.39
7200 14 mm w/o barriers -1.65 -18.05
Note: Assume ⍨ 50 mV accuracy for check tolerance.
123
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
WARNING
High Voltage Present. Contact
could cause shock, burns, or
death.
Do not touch exposed wires or
terminals.
Application Alert: Tests will exceed alarm setpoint levels causing alarms to
activate. This could result in a relay contact state change.
124
Section 5 -
5.1.8.1.2 Verification Screen Setup – Hyper
Run the Rack Configuration Software on the test computer. Choose Verification
from the Utilities menu and choose the proper Slot number and Channel number
then click on the Verify button.
The following table directs you to the starting page of each maintenance section
associated with the Hyper Channels:
Section Topic
Number
When varying the signal from an alarm condition to a non-alarm condition, alarm
hysteresis must be considered. Adjust the signal well below the alarm setpoint
for the alarm to clear.
5.1.8.2.1 Pk – Pk Displacement
390. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
125
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
391. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
392. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Adjust the function generator amplitude to
produce a reading that is below the Pk-Pk Displacement setpoint level on the
bar graph display of the Verification screen.
393. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for Pk-Pk Displacement is
green, and the Current Value field contains no alarm indication.
394. Adjust the function generator amplitude such that the signal just
exceeds the Pk-Pk Displacement Over Alert/Alarm 1 setpoint level. Wait for
2 or 3 seconds after the alarm time delay expires and verify that the bar
graph indicator for Pk-Pk Displacement changes color from green to yellow
and that the Current Value Field indicates an Alarm.
395. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Pk-Pk Displacement remains yellow and that the Current Value
Field still indicates an Alarm.
396. Adjust the function generator amplitude such that the signal just
exceeds the Pk-Pk Displacement Over Danger/Alarm 2 setpoint level. Wait
for 2 or 3 seconds after the alarm time delay expires and verify that the bar
graph indicator for Pk-Pk Displacement changes color from yellow to red and
that the Current value Field indicates an Alarm.
397. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Pk-Pk Displacement remains red and that the Current Value
Field still indicates an Alarm.
398. Adjust the function generator amplitude such that the signal reads
below the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for Pk-Pk Displacement changes color to
green and that the Current Value Box contains no indication of Alarms.
Press the RESET switch on the RIM to reset latching alarms.
399. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
400. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET switch on
the RIM to reset the OK LED.
401. Repeat steps 1 through 11 for all configured channels.
5.1.8.2.2 Gap
402. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
403. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
126
Section 5 -
404. Adjust the power supply to produce a voltage that is within the Gap
setpoint levels on the Gap bar graph display of the Verification Screen.
405. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for Gap is green and the
Current Value Field contains no alarm indication.
406. Adjust the power supply voltage such that the signal just exceeds the
Gap Over Alert/Alarm 1 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for Gap
changes color from green to yellow and that the Current Value Field indicates
an Alarm.
407. Press the RESET switch on the RIM. Verify that the OK LED is on,
the bargraph indicator for Gap is yellow and the Current Value Field indicates
an alarm.
408. Adjust the power supply voltage such that the signal just exceeds the
Gap Over Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the
alarm time delay expires and verify that the bar graph indicator for Gap
changes color from yellow to red and that the Current Value Field indicates
an Alarm.
409. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Gap remains red and that the Current Value Field still indicates
an Alarm.
410. Adjust the power supply voltage such that the signal reads below the
Over Alarm setpoint levels. If the nonlatching option is configured, observe
that the bar graph indicator for Gap changes color to green and that the
Current Value Box contains no idication of Alarms. Press the RESET switch
on the RIM to reset latching alarms.
411. Repeat steps 5 through 9 to test the Under Alert/Alarm 1 and Under
Danger/Alarm 2 setpoints by adjusting the power supply to exceed the Under
Alarm setpoint levels.
412. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
413. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET switch on
the RIM to reset the OK LED.
414. Repeat steps 1 through 12 for all configured channels.
5.1.8.2.3 1X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
415. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
416. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
127
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
417. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Adjust the function generator amplitude to
produce a reading that is within the 1X Ampl setpoint levels on the 1X Ampl
bar graph display of the Verification screen.
418. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for 1X Ampl is green and the
Current Value Field contains no alarm indication.
419. Adjust the function generator amplitude such that the signal just
exceeds the 1X Ampl Over Alert/Alarm 1 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for 1X Ampl changes color from green to yellow and that the Current
Value Field indicates an Alarm.
420. Press the RESET switch on the RIM. Verify that the bar graph
indicator for 1X Ampl remains yellow and that the Current Value Field still
indicates an alarm.
421. Adjust the function generator amplitude such that the signal just
exceeds the 1X Ampl Over Danger/Alarm 2 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for 1X Ampl changes color from yellow to red and that the Current
value Field indicates an Alarm.
422. Press the RESET switch on the RIM. Verify that the bar graph
indicator for 1X Ampl remains red and that the Current Value Field still
indicates an Alarm.
423. Adjust the function generator amplitude such that the signal reads
below the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for 1X Ampl changes color to green and
that the Current Value Box contains no indication of Alarms. Press the
RESET switch on the RIM to reset latching alarms.
424. Repeat steps 3 through 9 to test the Under Alert/Alarm 1 and Under
Danger/Alarm 2 setpoints by adjusting the function generator amplitude to
exceed the Under Alarm setpoint levels.
425. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
426. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET switch on
the RIM to reset the OK LED.
427. Repeat steps 1 through 12 for all configured channels.
5.1.8.2.4 2X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
428. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
128
Section 5 -
429. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
430. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Adjust the function generator amplitude to
produce a reading that is within the 2X Ampl setpoint levels on the 2X Ampl
bar graph display of the Verification screen.
431. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for 2X Ampl is green and the
Current Value Field contains no alarm indication.
432. Adjust the function generator amplitude such that the signal just
exceeds the 2X Ampl Over Alert/Alarm 1 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for 2X Ampl changes color from green to yellow and that the Current
Value Field indicates an Alarm.
433. Press the RESET switch on the RIM. Verify that the bar graph
indicator for 2X Ampl remains yellow and that the Current Value Field still
indicates an alarm.
434. Adjust the function generator amplitude such that the signal just
exceeds the 2X Ampl Over Danger/Alarm 2 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for 2X Ampl changes color from yellow to red and that the Current
value Field indicates an Alarm.
435. Press the RESET switch on the RIM. Verify that the bar graph
indicator for 2X Ampl remains red and that the Current Value Field still
indicates an Alarm.
436. Adjust the function generator amplitude such that the signal reads
below the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for 2X Ampl changes color to green and
that the Current Value Box contains no indication of Alarms. Press the
RESET switch on the RIM to reset latching alarms.
437. Repeat steps 3 through 9 to test the Under Alert/Alarm 1 and Under
Danger/Alarm 2 setpoints by adjusting the function generator amplitude to
exceed the Under Alarm setpoint levels.
438. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
439. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET switch on
the RIM to reset the OK LED.
440. Repeat steps 1 through 12 for all configured channels.
129
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
441. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
442. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
443. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Adjust the function generator amplitude to
produce a reading that is within the Not 1X setpoint levels on the Not 1X bar
graph display of the Verification screen.
444. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the OK LED is on, the bargraph indicator for Not 1X is green and the
Current Value Field contains no alarm indication.
445. Adjust the function generator amplitude such that the signal just
exceeds the Not 1X Over Alert/Alarm 1 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for Not 1X changes color from green to yellow and that the Current
Value Field indicates an Alarm.
446. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Not 1X remains yellow and that the Current Value Field still
indicates an alarm.
447. Adjust the function generator amplitude such that the signal just
exceeds the Not 1X Over Danger/Alarm 2 setpoint level. Wait for 2 or 3
seconds after the alarm time delay expires and verify that the bar graph
indicator for Not 1X changes color from yellow to red and that the Current
value Field indicates an Alarm.
448. Press the RESET switch on the RIM. Verify that the bar graph
indicator for Not 1X remains red and that the Current Value Field still
indicates an Alarm.
449. Adjust the function generator amplitude such that the signal reads
below the Over Alarm setpoint levels. If the nonlatching option is configured,
observe that the bar graph indicator for Not 1X changes color to green and
that the Current Value Box contains no indication of Alarms. Press the
RESET switch on the RIM to reset latching alarms.
450. If you can’t verify any configured alarm, recheck the configured
setpoints. If the monitor still does not alarm properly or fails any other part of
this test, go to Section 5.1.10 (If a Channel Fails a Verification Test).
451. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press the RESET switch on
the RIM to reset the OK LED.
452. Repeat steps 1 through 11 for all configured channels.
5.1.8.3.1 Pk – Pk Displacement
453. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
454. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
455. Calculate the full scale voltage according to the equation and
examples shown below. Adjust the amplitude of the function generator to the
calculated voltage.
Full Scale Voltage = Pk-Pk Displacement Meter Top Scale x Transducer Scale
Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
Direct Meter Top Scale = 10 mil
Transducer Scale Factor = 200mV/mil = .200 V/mil
Example 2:
Direct Meter Top Scale = 200µm
Transducer Scale Factor = 7,874 mV/mm
= 7.874 mV/µm
456. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Verify that the Pk-Pk Displacement bar graph
display and Current Value Box is reading ±1% of full scale. If the recorder
output is configured, refer to section 5.1.9 (Verify Recorder Outputs) for steps
to verify the recorder output.
457. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications of fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
458. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
131
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
459. Repeat steps 1 through 6 for all configured channels.
5.1.8.3.2 Gap
460. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
461. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
462. Adjust the power supply to produce a voltage equal to –18.00 Vdc on
the Volt Meter. Verify that the Gap bar graph display and Current Value Box
is reading –18.00 Vdc ±1% of Full Scale. If the recorder output is configured,
refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify recorder
output.
463. Adjust the power supply to produce a voltage equal to mid-scale on
the Volt Meter. Verify that the Gap bar graph display and Current Value Box
is reading the mid-scale value ±1% of Full Scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
464. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
465. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
466. Repeat steps 1 through 6 for all configured channels.
5.1.8.3.3 1X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
467. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
468. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
469. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated voltage.
Full Scale Voltage = 1X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
1X Ampl Meter Top Scale = 10 mil
Transducer Scale Factor = 200 mV/mil
132
Section 5 -
Example 2:
1X Ampl Meter Top Scale = 200 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
470. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is one. Verify that the 1X Ampl bar graph display and
Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
471. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
472. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
473. Repeat steps 1 through 6 for all configured channels.
5.1.8.3.4 2X Amplitude
Note: The Keyphasor must be triggering and have a valid rpm value to check
this parameter.
474. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
475. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
476. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated voltage.
Full Scale Voltage = 2X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
2X Ampl Meter Top Scale = 10 mil
133
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Transducer Scale Factor = 200 mV/mil
Example 2:
2X Ampl Meter Top Scale = 200 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
477. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Verify that the 2X Ampl bar graph display and
Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
478. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
479. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
480. Repeat steps 1 through 6 for all configured channels.
481. Disconnect the PWR, COM, and SIG field wiring from the channel
terminals on the I/O module.
482. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup. Set the function generator to
Sine wave output.
483. Calculate the full-scale voltage according to the equation and
examples shown below. Adjust the function generator amplitude to the
calculated voltage.
Full Scale Voltage = Not 1X Ampl Meter Top Scale X Transducer Scale Factor
Note: Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen.
Example 1:
134
Section 5 -
Not 1X Ampl Meter Top Scale = 10 mil
Transducer Scale Factor = 200 mV/mil
Example 2:
Not 1X Ampl Meter Top Scale = 200 µm
Transducer Scale Factor = 7,874 mV/mm = 7.874 mV/µm
484. Set the Keyphasor multiplier/divider so that the multiply setting is one
and the divide setting is two. Verify that the Not 1X Ampl bar graph display
and Current Value Box is reading ±1% of full scale. If the recorder output is
configured, refer to Section 5.1.9 (Verify Recorder Outputs) for steps to verify
the recorder output.
485. If the reading does not meet specifications, check that the input signal
is correct. If the monitor still does not meet specifications or fails any other
part of this test, go to section 5.1.10 (If a Channel Fails a Verification Test).
486. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the I/O module. Verify that the
OK LED comes on and the OK relay energizes. Press RESET switch on the
Rack Interface Module to reset the OK LED.
487. Repeat steps 1 through 6 for all configured channels.
488. Disconnect PWR, COM, and SIG field wiring from the channel
terminals on the Rod Position I/O Module.
489. Connect test equipment and run software as described in Section
5.1.2, Required Test Equipment and Setup.
490. Bypass all other configured channels.
135
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
491. Adjust the power supply voltage to -7.00 Vdc.
492. Press the RESET switch on the Rack Interface Module (RIM). Verify
that the monitor OK LED is on and that the Channel OK State line in the
Channel Status box of the Verification screen reads OK.
Note: If the Danger Bypass has been activated, then the BYPASS LED will be
on. All other channels in the rack must be OK or bypassed for the relay to be
energized.
493. Verify that the OK relay on the Rack Interface I/O Module indicates
OK (energized). See 3500 Rack Interface Module Operation and
Maintenance Manual.
494. Increase the power supply voltage (more negative) until the OK LED
just goes off (upper limit). Verify that the Channel OK State line in the
Channel Status box reads not OK and that the OK Relay indicates not OK.
Verify that the Upper OK limit voltage displayed on the Verification screen is
equal to or more positive than the input voltage.
495. Decrease the power supply voltage (less negative) to -7.00 Vdc.
496. Press the RESET switch on the RIM. Verify that the OK LED comes
back on and the OK relay energizes. Verify that the Channel OK State line in
the Channel Status box reads OK.
497. Gradually decrease the power supply voltage (less negative) until the
OK LED just goes off (lower limit). Verify that the Channel OK State line in
the Channel Status box reads not OK and that the OK Relay indicates not
OK. Verify that the Lower OK limit voltage displayed on the Verification
screen is equal to or more negative than the input voltage.
498. Increase the power supply voltage (more negative) to -7.00 Vdc.
499. Press the RESET switch on the RIM. Verify that the OK LED comes
back on, the OK relay energizes, and that the Channel OK State line in the
Channel Status box reads OK.
500. If you cannot verify any configured OK limit, go to Section 5.1.10 (If a
Channel Fails a Verification Test).
501. Disconnect the test equipment and reconnect the PWR, COM, and
SIG field wiring to the channel terminals on the Monitor I/O Module. Press
the RESET switch on the Rack Interface Module and verify that the OK LED
comes on and the OK relay energizes.
502. Repeat steps 1 through 14 for all configured channels.
503. Return the bypass switch for all configured channels to their original
setting.
136
Section 5 -
137
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
504. Disconnect the COM and REC field wiring from the channel terminals
on the I/O module.
505. Connect a multimeter to the COM and REC outputs of the I/O module.
The multimeter should have the capability to measure 4 to 20 mA.
506. If the proportional value is not Gap: Set the proportional value that
the recorder is configured for to full-scale (refer to the proportional value of
the channel pair type you are testing in the Verify Channel Values portion of
this manual). Verify that the recorder output is reading 20 mA ±1%. Go to
step 5.
507. If the proportional value is Gap: Set the Gap proportional value to –
18.00 Vdc (Refer to the proportional value of the channel pair type you are
testing in the Verify Channel Values portion of this manual). Verify that the
recorder output is reading 16 mA ±1%.
508. Set the proportional value that the recorder is configured for to mid-
scale. Verify that the recorder output is reading 12 mA ±1%.
509. Set the proportional value that the recorder is configured for to
bottom-scale. Verify that the recorder output is reading 4 mA ±1%.
510. Disconnect transducer input and verify that the recorder output
matches the set monitor clamp value ±1%.
511. If you can not verify the recorder output, the recorder configuration
and connections should be checked. If the monitor recorder output still does
not verify properly, go to Section 5.1.10 (If a Channel Fails a Verification
Test).
512. Disconnect the multimeter and reconnect the COM and REC field
wiring to the channel terminals on the I/O module.
513. Repeat steps 1 through 9 for all configured recorder channels.
138
Section 6 - Troubleshooting
6. Troubleshooting
This section describes how to troubleshoot a problem with the Recip Rod
Position Monitor or the I/O module by using the information provided by the self-
test, the LED’s, the System Event List, and the Alarm Event List.
6.1 Self-test
To perform the Recip Rod Position Monitor self-test:
519. Connect a computer running the Rack Configuration Software to the
3500 rack (if needed).
520. Select Utilities from the main screen of the Rack Configuration
Software.
521. Select System Events/Module Self-test from the Utilities menu.
522. Press the Module Self-test button on the System Events screen.
Application Alert: Machinery protection will be lost while the self-test is being
performed
523. Select the slot that contains the Recip Rod Position Monitor and press
the OK button. The Recip Rod Position Monitor will perform a full self-test
and the System Events screen will be displayed. The list will not contain the
results of the self-test.
524. Wait 30 seconds for the module to run a full self-test.
525. Press the Latest Events button. The System Events screen will be
updated to include the results of the Recip Rod Position Monitor self-test.
526. Verify if the Recip Rod Position Monitor passed the self-test. If the
monitor failed the self-test, refer to Section 7.3.
139
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Sequence Number:
The number of the event in the System Event List (for example 123).
Event Information:
The name of the event (for example Device Not Communicating).
Event Number:
Identifies a specific event.
140
Section 6 - Troubleshooting
Class:
Used to display the severity of the event. The following classes are available:
Event Date:
The date the event occurred.
Event Time:
The time the event occurred.
Event Specific:
It provides additional information for the events that use this field.
Slot:
Identifies the module that the event is associated with. If a half-height module is
installed in the upper slot or a full-height module is installed, the field will be 0 to 15.
If a half-height module is installed in the lower slot, then the field will be 0L to 15L.
For example, a module installed in the lower position in slot 5 would be 5L.
The following System Event List Messages may be placed in the list by the Recip
Rod Position Monitor and are listed in numerical order. If an event marked with a
star (*) occurs the Recip Rod Position Monitor will stop alarming. If you are
unable to solve any problems contact your nearest Bently Nevada Corporation
office.
Flash Memory Failure
Event Number: 11
Event Classification: Severe / Fatal Event
Action: Replace the Monitor Module as soon as possible.
EEPROM Memory Failure
Event Number: 13
Event Classification: Potential Problem or Severe / Fatal Event
Action: Replace the Monitor Module as soon as possible.
Device Not Communicating
Event Number: 32
Event Classification: Potential Problem
Action: Check to see if one of the following components is faulty:
- the Monitor Module
- the rack backplane
Device Is Communicating
Event Number: 33
Event Classification: Potential Problem
Action: Check to see if one of the following components is faulty:
- the Monitor Module
- the rack backplane
* Neuron Failure
Event Number: 34
Event Classification: Severe / Fatal Event
Action: Replace the Monitor Module immediately.
Monitor Module will stop alarming.
141
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
* I/O Module Mismatch
Event Number: 62
Event Classification: Severe / Fatal Event
Action: Verify that the type of I/O module installed matches what was selected in the
software. If the correct I/O module is installed, there may be a fault with the Monitor
Module or the Monitor I/O module.
Monitor Module will stop alarming.
I/O Module Compatible
Event Number: 63
Event Classification: Severe / Fatal Event
Action: Verify that the type of I/O module installed matches what was selected in the
software. If the correct I/O module is installed, there may be a fault with the Monitor
Module or the Monitor I/O module.
* Fail I/O Jumper Check
Event Number: 64
Event Classification: Severe / Fatal Event
Action: Verify that the type of I/O module installed matches what was selected in the
software. If the correct I/O module is installed, there may be a fault with the Monitor
Module or the Monitor I/O module.
Monitor Module will stop alarming.
Pass I/O Jumper Check
Event Number: 65
Event Classification: Severe / Fatal Event
Action: Verify that the type of I/O module installed matches what was selected in the
software. If the correct I/O module is installed, there may be a fault with the Monitor
Module or the Monitor I/O module.
Fail Main Board +5V-A
(Fail Main Board +5V - upper Power Supply)
Event Number: 100
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
Pass Main Board +5V-A
(Pass Main Board +5V - upper Power Supply)
Event Number: 101
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
Fail Main Board +5V-B
(Fail Main Board +5V - lower Power Supply)
Event Number: 102
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
142
Section 6 - Troubleshooting
- the Power Supply installed in the lower slot
Pass Main Board +5V-B
(Pass Main Board +5V - lower Power Supply)
Event Number: 103
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
Fail Main Board +5V-AB
(Fail Main Board +5V - upper and lower Power Supplies)
Event Number: 104
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Monitor Module will stop alarming.
Pass Main Board +5V-AB
(Pass Main Board +5V - upper and lower Power Supplies)
Event Number: 105
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Fail Main Board +15V-A
(Fail Main Board +15V - upper Power Supply)
Event Number: 106
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
Pass Main Board +15V-A
(Pass Main Board +15V - upper Power Supply)
Event Number: 107
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
143
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Fail Main Board +15V-B
(Fail Main Board +15V - lower Power Supply)
Event Number: 108
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
Pass Main Board +15V-B
(Pass Main Board +15V - lower Power Supply)
Event Number: 109
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
Fail Main Board +15V-AB
(Fail Main Board +15V - upper and lower Power Supplies)
Event Number: 110
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Monitor Module will stop alarming.
Pass Main Board +15V-AB
(Pass Main Board +15V - upper and lower Power Supplies)
Event Number: 111
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Fail Main Board -24V-A
(Fail Main Board -24V - upper Power Supply)
Event Number: 112
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
144
Section 6 - Troubleshooting
Pass Main Board -24V-A
(Pass Main Board -24V - upper Power Supply)
Event Number: 113
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
Fail Main Board -24V-B
(Fail Main Board -24V - lower Power Supply)
Event Number: 114
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
Pass Main Board -24V-B
(Pass Main Board -24V - lower Power Supply)
Event Number: 115
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the lower slot
Fail Main Board -24V-AB
(Fail Main Board -24V - upper and lower Power Supplies)
Event Number: 116
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
Monitor Module will stop alarming.
Pass Main Board -24V-AB
(Pass Main Board -24V - upper and lower Power Supplies)
Event Number: 117
Event Classification: Severe/Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the
problem is not caused by noise, check to see if one of the following components is
faulty:
- the Monitor Module
- the Power Supply installed in the upper slot
- the Power Supply installed in the lower slot
145
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
* Configuration Failure
Event Number: 301
Event Classification: Severe/Fatal Event
Action: Download a new configuration to the Monitor Module. If the problem still
exists replace the Monitor Module immediately.
Monitor Module will stop alarming.
Configuration Failure
Event Number: 301
Event Classification: Potential Problem
Action: Download a new configuration to the Monitor Module. If the problem still
exists replace the Monitor Module as soon as possible.
Module Entered Cfg Mode
(Module Entered Configuration Mode)
Event Number: 302
Event Classification: Typical Logged Event
Action: No action required.
Monitor Module will stop alarming.
Software Switches Reset
Event Number: 305
Event Classification: Potential Problem
Action: Download the software switches to the Monitor Module. If the software
switches are not correct, replace the Monitor Module as soon as possible.
Internal Cal Reset
(Internal Calibration Reset)
Event Number: 307
Event Classification: Severe/Fatal Event
Event Specific: Ch pair x
Action: Replace Monitor Module immediately.
Monitor TMR PPL Failed
(Monitor TMR Proportional value Failed)
Event Number: 310
Event Classification: Potential Problem
Action: Replace the Monitor Module.
Monitor TMR PPL Passed
(Monitor TMR Proportional value Passed)
Event Number: 311
Event Classification: Potential Problem
Action: Replace the Monitor Module.
Module Reboot
Event Number: 320
Event Classification: Typical Logged Event
Action: No action required.
* Module Removed from Rack
Event Number: 325
Event Classification: Typical Logged Event
Action: No action required.
Monitor Module will stop alarming.
Module Inserted in Rack
Event Number: 326
Event Classification: Typical Logged Event
Action: No action required.
146
Section 6 - Troubleshooting
Device Events Lost
Event Number: 355
Event Classification: Typical Logged Event
Action: No action required.
This may be due to the removal of the Rack Interface Module for an extended period
of time.
Module Alarms Lost
Event Number: 356
Event Classification: Typical Logged Event
Action: No action required.
This may be due to the removal of the Rack Interface Module for an extended period
of time.
Module Entered Calibr.
(Module Entered Calibration Mode)
Event Number: 365
Event Classification: Typical Logged Event
Action: No action required.
Monitor Module will stop alarming.
Module Exited Calibr.
(Module Exited Calibration Mode)
Event Number: 366
Event Classification: Typical Logged Event
Action: No action required.
Pass Module Self-test
Event Number: 410
Event Classification: Typical Logged Event
Action: No action required.
Enabled Ch Bypass
(Enabled Channel Bypass)
Event Number: 416
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
Alarming has been inhibited by this action.
Disabled Ch Bypass
(Disabled Channel Bypass)
Event Number: 417
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
* Enabled Alert Bypass
Event Number: 420
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
Alarming has been inhibited by this action.
Disabled Alert Bypass
Event Number: 421
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
* Enabled Danger Bypass
Event Number: 422
147
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
Alarming has been inhibited by this action.
Disabled Danger Bypass
Event Number: 423
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
Enabled Special Inh
(Enabled Special Inhibit)
Event Number: 424
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
Alarming has been inhibited by this action.
Disabled Special Inh
(Disabled Special Inhibit)
Event Number: 425
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
Enabled Mon Alarm Byp
(Enabled Monitor Alarm Bypass)
Event Number: 426
Event Classification: Typical logged event
Action: No action required.
Monitor Module will stop alarming.
Disabled Mon Alarm Byp
(Disabled Monitor Alarm Bypass)
Event Number: 427
Event Classification: Typical logged event
Action: No action required.
* Fail Slot Id Test
Event Number: 461
Event Classification: Severe/Fatal Event
Action: Verify that the Monitor Module is fully inserted in the rack. If the Monitor
Module is installed correctly, check to see if one of the following components is
faulty:
- the Monitor Module
- the rack backplane
Monitor Module will stop alarming.
Pass Slot Id Test
Event Number: 462
Event Classification: Severe/Fatal Event
Action: Verify that the Monitor Module is fully inserted in the rack. If the Monitor
Module is installed correctly, check to see if one of the following components is
faulty:
- the Monitor Module
- the rack backplane
148
Section 6 - Troubleshooting
* Enabled Test Signal
Event Number: 481
Event Classification: Typical logged event
Action: No action required.
Monitor Module will stop alarming.
Disabled Test Signal
Event Number: 482
Event Classification: Typical logged event
Action: No action required.
Switch To Primary Kph
Event Number: 491
Event Classification: Potential Problem
Event Specific: Ch pair x
Action: Check to see if one of the following is faulty:
- the secondary Keyphasor® transducer on the machine
- the Monitor Module
Switch To Backup Kph
Event Number: 492
Event Classification: Potential Problem
Event Specific: Ch pair x
Action: Check to see if one of the following is faulty:
- the primary Keyphasor transducer on the machine
- the Monitor Module
* Kph Lost
Event Number: 493
Event Classification: Potential Problem
Event Specific: Ch pair x
Action: Check to see if one of the following is faulty:
- both Keyphasor transducers on the machine
- the Monitor Module
- the Keyphasor Module
For vector and Keyphasor based, alarms the Monitor Module will stop alarming.
DSP Reset Attempted
Event Number: 501
Event Classification: Severe / Fatal Event
Event Specific: Ch pair x
Action: If the message is seen repeatedly in the System Event List, then replace the
Monitor Module immediately.
* DSP Self-test Failure
Event Number: 502
Event Classification: Severe / Fatal Event
Event Specific: Ch pair x
Action: Replace the Monitor Module immediately.
Monitor Module will stop alarming.
149
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
150
Section 7 - Ordering Information
7. Ordering Information
7.1 Ordering Considerations
When ordering I/O Modules with External Terminations the External Termination
Blocks and Cable must be ordered separately for each I/O Module.
The 3500 Internal Barrier Specification sheet should be consulted if the Internal
Barrier Option is selected.
Version 3.20 or higher of the 3500 Rack Configuration Software is required.
151
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
B: Assembly Instructions
01 Not Assembled
02 Assembled
7.2.5 Spares
140734-08
3500/72M Recip Rod Position Monitor
140471-01
I/O Module with Internal Terminations
140482-01
I/O Module with External Terminations
135489-01
I/O Module with Internal Barriers and Internal Terminations
146479-01
3500/72M Rod Position Manual
00580434
Internal I/O Module connector header, Euro Style, 8-pin,
green. Used on I/O modules 140471-01
00580441
Internal I/O Module connector header, Euro Style, 3-pin,
green. Used on I/O modules 135489-01 and 140471-01
00502133
Internal I/O Module connector header, Euro Style, 12-pin,
blue. Used on I/O modules 135489-01
152
Section 8 - Specifications
8. Specifications
8.1 Inputs
Signal:
Accepts from 1 to 4 proximity probe signals.
Input Impedance:
10 kΩ
Nominal Scale Factor:
Rod Position:
3.94 mV/µm (100 mV/mil) or
7.87 mV/µm (200 mV/mil)
Rod Drop:
3.94 mV/µm (100 mV/mil) or
7.87 mV/µm (200 mV/mil)
Hyper-Compressor:
3.94 mV/µm (100 mV/mil) or
7.87 mV/µm (200 mV/mil)
Note: Configuration allows a wide range of adjustment to accommodate
transducer sensitivity for different rod materials.
Power Consumption:
Nominal Consumption of 7.7 watts
8.2 Outputs
Front Panel LED’s:
OK LED:
Indicates when the 3500/72M is operating properly.
TX/RX LED:
Indicates when the 3500/72M is communicating with other
modules in the 3500 rack.
Bypass LED:
Indicates when the 3500/72M is in Bypass Mode.
Buffered Transducer Outputs
The front of each monitor has one coaxial connector for
each channel. Each connector is short-circuit protected.
Output Impedance:
550 Ω
Transducer Power Supply:
-24 Vdc
153
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Position Magnitude, Position Angle, Crank Angle, Pk-Pk
Amplitude, Gap, 1X Amplitude, Not 1X Amplitude, and 2X
Amplitude
Rod Position – Pair
Position Magnitude, Position Angle, Crank Angle, Pk-Pk
Amplitude, Gap, 1X Amplitude, Not 1X Amplitude, and 2X
Amplitude
Rod Drop
Average Piston Position, Average Probe Gap, Instantaneous
Piston Position, and Instantaneous Probe Gap
Hyper Channel
Pk-Pk Displacement, Gap, 1X Amplitude, Not 1X Amplitude,
and 2X Amplitude
Frequency Response:
Note: 1X and 2X vector and Not 1X parameters are valid for machine operation
of 60 cpm to 2000 cpm.
Peak-Peak Filter:
Fixed 1 Hz to 600 Hz
Gap Filter:
-3 dB at 0.09 Hz
Not 1X Filter:
Constant Q notch filter with minimum rejection in stop-band
of 34.9 dB over frequency range of 60 cpm to 15.8 times
running speed.
1X Vector Filter:
Constant Q filter with minimum rejection in stop-band of 57.7
dB
2X Vector Filter:
Constant Q filter with minimum rejection in stop-band of 57.7
dB
Accuracy
Position Magnitude
(direct):
Within ±0.33% of full scale typical, ±1.0% maximum
Gap:
Within ±0.33% of full scale typical, ±1.0% maximum
1X Amplitude:
Within ±0.33% of full scale typical, ±1.0% maximum
2X Amplitude:
Within ±0.33% of full scale typical, ±1.0% maximum
Pk-Pk Amplitude:
Within ±0.33% of full scale typical, ±1.0% maximum
Not 1X Amplitude:
Within ±3.0% of full scale typical
154
Section 8 - Specifications
Position Crank
Angle:
Within ±1° typical, ±3° maximum
Rod Position Angle
(paired only):
Within ±1° typical, ±3° maximum
Average Piston
Position (direct):
Fixed 1 Hz to 600 Hz
Average Gap:
-3 dB at 0.09 Hz
Accuracy
Average Piston
Position (direct):
Within ±0.33% of full scale typical, ±1.0% maximum
Average Gap:
Within ±0.33% of full scale typical, ±1.0% maximum
Instantaneous
Piston Position:
Within ±0.33% of full scale typical, ±1.0% maximum
Instantaneous
Probe Gap:
Within ±0.33% of full scale typical, ±1.0% maximum
8.6 Hyper-Channel:
Frequency Response:
Note: 1X and 2X vector and Not 1X parameters are valid for machine operation
of 60 cpm to 2,000 cpm.
Peak-Peak Filter:
Fixed 1 Hz to 600 Hz
Gap Filter:
-3 dB at 0.09 Hz
Not 1X Filter:
Constant Q notch filter with minimum rejection in stop-band
of 34.9 dB over frequency range of 60 cpm to 15.8 times
running speed.
1X Vector Filter:
Constant Q filter with minimum rejection in stop-band of 57.7
dB
2X Vector Filter:
Constant Q filter with minimum rejection in stop-band of 57.7
dB
Accuracy
Peak-Peak
Magnitude (direct):
155
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
Within ±0.33% of full scale typical, ±1.0% maximum
Gap:
Within ±0.33% of full scale typical, ±1.0% maximum
1X Amplitude:
Within ±0.33% of full scale typical, ±1.0% maximum
2X Amplitude:
Within ±0.33% of full scale typical, ±1.0% maximum
Not 1X Amplitude:
Within ±3.0% of full scale typical
8.7 Alarms
Alarm Setpoint Values:
Alert levels can be set for each value measured by the
monitor. In addition, Danger setpoint values can be set for
any two of the values measured by the monitor. All alarm
setpoint values are set using software configuration. Alarms
are adjustable and can be set from 0 to 100% of full-scale
for each measured value. Accuracy of an alarm setpoint is
to within 0.13% of the desired value.
Alarm Time Delays:
Alarm delays can be programmed using software, and can
be set as follows:
Alert:
From 1 to 60 seconds in 1 second intervals.
Danger:
From 1 to 60 seconds in 1 second intervals or 0.1 seconds
(nominal)
Timed OK Channel
Defeat:
Ok Channel defeat is disabled for all rod position
configurations. When used as a hyper-compressor monitor
the action of both transducers going not OK will cause the
immediate issue of a danger alarm.
156
Section 8 - Specifications
8.9 CE Mark Directives
EMC Directives
EN50081-2
Radiated Emissions
EN 55011, Class A
Conducted
Emissions
EN 55011, Class A
EN50082-2
Electrostatic
Discharge
EN 61000-4-2, Criteria B
Radiated
Susceptibility
ENV 50140, Criteria A
Conducted
Susceptibility
ENV 50141, Criteria A
Electrical Fast
Transient
EN 61000-4-4, Criteria B
Surge Capability
EN 61000-4-5, Criteria B
Magnetic Field
EN 61000-4-8, Criteria A
Power Supply Dip
EN 61000-4-11, Criteria B
Radio Telephone
ENV 50204, Criteria B
CE Mark Low Voltage Directives
EN 61010-1
Safety Requirements
157
3500/72M Recip Rod Position Monitor Operation and Maintenance Manual
8.11 Physical
Monitor Module
Dimensions (Height x
Width x Depth)
241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52
in)
Weight
0.91 kg (2.0 lbs.).
I/O Modules (non-barrier)
Dimensions (Height x
Width x Depth)
241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
Weight
0.20 kg (0.44 lb.).
I/O Modules (barrier)
Dimensions (Height x
Width x Depth)
241.3 mm x 24.4 mm x 163.1 mm (9.50 in x 0.96 in x 6.42
in)
Weight
0.46 kg (1.01 lbs.).
Rack Space Requirements
Monitor Module
1 full-height front slot
I/O Modules
1 full-height rear slot
158