Investigations in Electric Power Technology: Modularized Systems Volumes 1 To 4
Investigations in Electric Power Technology: Modularized Systems Volumes 1 To 4
Investigations in Electric Power Technology: Modularized Systems Volumes 1 To 4
25990-01
Instructor Guide
|3025990010000Q~
Electric Power / Controls
Investigations in
Electric Power Technology
Modularized Systems
Volumes 1 to 4
Instructor Guide
25990-01
AB
ELECTRIC POWER / CONTROLS
INVESTIGATIONS IN
ELECTRIC POWER TECHNOLOGY
MODULARIZED SYSTEMS
VOLUMES 1 TO 4
by
the Staff
of
Lab-Volt Ltd.
ISBN 2-89289-725-4
Printed in Canada
December 2005
To the Instructor
A major benefit derived from dynamic laboratory investigations is that students quickly realize
that actual circuit performance data will usually vary somewhat from calculated performance
data. As they learn to anticipate these disparities, they also learn to consider component
circuit and meter tolerances when calculating the maximum permissible deviation of actual
circuit results from the ideal or calculated values. The numerical results given in this guide
have been rounded off to the appropriate number of significant digits.
This instructor guide contains complete solutions to all procedure and review questions found
in the student manual. Each experiment begins with a discussion of the subject. The
discussion may include background or historical information to aid in introductory discussion
of the subject. It may also contain additional data which will open other possible avenues of
investigation or technical data to facilitate conduct of experiment and evaluation of results.
Each experiment has several performance objectives. You should insure that students
understand each of them.
III
IV
Table of contents
Power Circuits
V
Table of Contents (cont'd)
DC Machines
VI
Table of Contents (cont'd)
VII
Power Circuits
Experiment 1
Series and Parallel Equivalent Resistances
DISCUSSION
PROCEDURE
a) Requivalent = 600 S
b) Requivalent = 900 S
c) Requivalent = 2100 S
d) Requivalent = 1200 S
e) Requivalent = 2100 S
a) Requivalent = 300 S
b) Requivalent = 200 S
c) Requivalent = 240 S
d) Requivalent = 150 S
e) Requivalent = 171.4 S
1-1
Series and Parallel Equivalent Resistances
a) Requivalent = 200 S
b) Requivalent = 133.3 S
c) Requivalent = 92.3 S
d) Requivalent = 100 S
e) Requivalent = 120 S
REVIEW QUESTIONS
1. a. Infinitely high.
b. Very low or 0 S.
2. High.
3. 0 S
The decision as to which of the two methods is the easier depends upon which
two resistors are selected for the initial calculation in method b). If resistors R1
and R2, or R2 and R3 are used first, the calculation will involve fractions, in
which case method a) will be considered the easier method. Obviously, where
many resistors are involved, method b) can become cumbersome and time
consuming.
1-2
Series and Parallel Equivalent Resistances
Figure 1-8.
1-3
Series and Parallel Equivalent Resistances
S1
S2
S3
Requivalent = infinity S
S1
S3
S2
Requivalent = 39 S
S1
S3
S2
Requivalent = 37 S
S1
S2
S3
Requivalent = 47 S
Table 1-1.
1-4
Experiment 2
Resistances in Parallel
DISCUSSION
Electric current, like water, will flow through any path provided for it. If a single
resistor is connected across a power source, a certain amount of current will flow
through the resistor. If a second resistor is connected in parallel with the first, the
current will have two paths to flow through and more current will flow. If the second
resistor has the same resistance value as the first, the same amount of current will
flow through each resistor so that adding the second resistor to the circuit doubles
the current flow (or reduces resistance to current flow by one-half). If a third resistor,
having the same resistance as the first two, is added in parallel, a third current path
is formed and, obviously, three times as much current now flows as when only one
resistor was connected. If three times as much current flows, the effective
resistance must be one-third that of a single resistor. Current flow through the
various parallel resistance paths will always distribute in inverse proportion to the
resistance ratios.
Requivalent = 100/5 = 20 S
PROCEDURE
BLACK SECTION
RED SECTION BLUE SECTION
(WHITE FOR 240 V SYSTEM)
R
1200 S 600 S 300 S 1200 S 600 S 300 S 1200 S 600 S 300 S
(listed)
R
1200 S 600 S 300 S 1200 S 600 S 300 S 1200 S 600 S 300 S
(measured)
Table 2-1
1-5
Resistances in Parallel
G 14. Yes, the variations are well within the rated meter accuracy, plus zero
setting and human measurement errors.
REVIEW QUESTIONS
= (1 + 1 + 1 + 2 + 2 + 2 + 4 + 4 + 4)/1200 = 21/1200
R (equivalent) = 1200/21
= 57.1 S
a) The effective resistances of the three sets of equal values resistors are first
calculated as follows:
1-6
Resistances in Parallel
= 400/7
= 57.14 S
2. Yes.
R= 1200/7 = 171.4 S
R= 100 S
R= 85.7 S
R = 66.7 S
6. 1200 S
1-7
1-8
Experiment 3
Resistances in Series and in Series-Parallel
DISCUSSION
The series-parallel circuit usually presents no problems to the individual familiar with
series and parallel circuit calculations. It is only necessary to reduce the parallel
portions to their equivalent values then add them to the sum of the series
resistances. In this Laboratory Experiment, the student forms series and series-
parallel resistance combinations using the resistance module. He or she practices
translating circuit diagrams into actual circuits. He or she checks his work by
measuring the circuit resistance and comparing it with calculated resistance. Actual
measurements (experimental results) usually do not completely agree with
calculated values (theoretical values) so the student determines the error
percentage using the formula:
If the experimental result is higher than the theoretical value, the two numbers in the
numerator must be reversed.
PROCEDURE
Percent error = 0 %
1-9
Resistances in Series and in Series-Parallel
Percent error = 2 %
Percent error = 1 %
Requivalent (measured) = 99 S
Percent error = 1 %
1-10
Resistances in Series and in Series-Parallel
Requivalent (measured) = 0 S
Percent error = 0 %
Students should have no trouble detecting the short across terminals A-B.
REVIEW QUESTIONS
Figure 3-12.
2. Requivalent = 100 S
Figure 3-13.
4. Requivalent = 4.8 S
1-11
Resistances in Series and in Series-Parallel
Figure 3-14.
6. Requivalent = 26.32 S
7. R = 3600 S.
8. R = 3000 S.
Figure 3-15.
The diagrams shown represent only one method of obtaining the required
resistances.
1-12
Resistances in Series and in Series-Parallel
It might prove both challenging and rewarding to have the students work out
several other combinations such as the following:
1400 S
1) Connect the other two 600 S resistors in series instead of the 1200 S
resistor.
2) Connect three parallel 600 S instead of parallel 600 S and 300 S resistors.
2000 S
1) Connect the other two 300 S resistors in series instead of the 600 S
resistor.
2) Connect three 600 S resistors in parallel. Connect this parallel combination
in series with a series combination consisting of two 300 S resistors and
one 1200 S resistor.
1000 S
1) Connect two 300 S resistors in series with the parallel 1200 S and 600 S
resistors.
2) Connect two 300 S resistors in series with three parallel 1200 S resistors.
500 S
1) Connect three 1200 S resistors in parallel and three 300 S resistors in
parallel. Connect the two parallel combinations in series.
2) Connect two 600 S resistors in parallel and a 600 S resistor in parallel with
a 300 S resistor. Connect the two parallel combinations in series.
1-13
1-14
Experiment 4
Safety and the Power Supply
DISCUSSION
Safety is a vital factor in every activity. It cannot be scheduled for an hour or two of
discussion and then abandoned in favor of another subject. Whether or not an
accident occurs is usually dependant upon the degree to which basic, common
sense safety rules are followed and the extent to which application of these rules
overcomes the accident potential.
The modules used in this course are designed and constructed for maximum safety
commensurate with effective instruction. However, the students will be working near
potentially dangerous voltages and, if accident are to be avoided, the safety rules
on page 4, 0, 0, 0-3 of the student manual must be implemented and enforced
constantly. You should insist that all mishaps, whether they result in injury or not,
be reported to you. You can then investigate, determine the cause, and initiate any
indicated action to prevent recurrence. In many cases, electrical shock immobilizes
respiratory muscles and breathing stops. When this happens, artificial respiration
must be administered without delay.
Resistance (dry):
Resistance (wet):
Voltage:
1-15
Safety and the Power Supply
PROCEDURE
This dc voltage should measure high without a load because this dc source
is of the capacitor input type.
e. No.
1-16
Safety and the Power Supply
1-17
1-18
Experiment 5
Ohm’s Law
DISCUSSION
The ammeter measures current and is connected in series with the circuit under
test. Since there is only one current path in a series circuit, all of the circuit current
flows through the meter. However, the ammeter must not introduce any additional
resistance into the circuit. Current flow in a series circuit varies inversely with the
total resistance of the circuit so, if total resistance is increased, circuit current will
decrease and the ammeter will not indicate the true circuit current value.
Obviously, an ammeter will always add some resistance to a circuit (and a voltmeter
will always draw some current) but the object of good meter design is to disturb the
circuit being measured as little as possible.
PROCEDURE
G 1. R = 200 kS
G 2. R = 0.35 S
G 3. R = 0.65 S
G 4. Yes. The meters must not disturb appreciably the circuit being measured.
Table 5-1.
1-19
Ohm’s Law
Figure 5-4.
E 20 40 60 80 100 120
Table 5-2.
Yes.
Yes.
1-20
Ohm’s Law
b. Requivalent = 200 S
Yes.
The variation is well within the rated meter accuracies and component
tolerances.
REVIEW QUESTIONS
NO. 1 2 3 4 5 6 7 8 9 10
Table 5-3.
2. I = 1200 A dc
3. E = 0.3 V dc
4. I = 0.0008 A dc
5. I = 0.024 A dc
Yes.
6. Uninsulated bus-bars would produce current losses through the low resistance
paths created by the meter and electrolyte covered surroundings. However,
they would not offer much danger to workers. Their internal body resistances
would be many thousands of times greater than the water and electrolyte
covered surfaces. Even if internal body resistance dropped to an unlikely
1000 S, current through the body, with a 6 V potential, would be:
1-21
Ohm’s Law
Insulated bus-bars could eliminate these current losses; the electrical insulation
material would however impair the cooling of the bus-bars which would run
hotter and cause more voltage drop.
In practice, the bus-bars are never insulated. They are however guarded
against possible inadvertent short-circuiting with metal parts.
7. No. The birds are in contact with only one terminal (wire) of a power source;
therefore, there is no potential difference between their feet.
In order for current to flow through one of the birds there must be a potential
difference of voltage across it. As long as the bird’s feet are both at 2300 V,
there is no potential difference between them, and therefore, no current through
the bird. However, if one foot is on the 2300 V wire and the other on a ground
wire, there is a 2300 V potential across the bird and some high value of current,
determined by internal body resistance, will flow through the bird.
8. 0.3 A dc
1-22
Experiment 6
Circuit Solution – Part I
DISCUSSION
Series circuit – the current is the same in every component of a series circuit.
Parallel circuit – the voltage is the same across every component branch of a
parallel circuit.
This points up the fact that voltage and current distribution in a series circuit is
opposite to that in a parallel circuit. With that difference in mind, circuit computation
involves calculating first the value that is common to all components in a series
circuit (current) or all branches of a parallel circuit (voltage). After that, the unknown
values are calculated individually. A knowledge of the characteristics of series and
parallel circuits plus the use of Ohm’s Law enables the student to determine circuit
value with comparative ease.
PROCEDURE
G 2. V1 = 120 V
I1 = 0.4 A
IT = 0.4 A
G 3. V1 = 60 V
V2 = 60 V
I1 = 0.2 A
I2 = 0.1 A
IT = 0.3 A
1-23
Circuit Solution – Part I
G 4. V1 = 120 V
V2 = 120 V
V3 = 120 V
I1 = 0.4 A
I2 = 0.2 A
I3 = 0.1 A
IT = 0.7 A
G 5. V1 = 30 V
V2 = 60 V
IT = 0.1 A
I1 = 0.1 A
I2 = 0.1 A
Since this is a series circuit, the value that is constant throughout the circuit,
current, should be calculated first. Students who have difficulty with this
problem are allowing themselves to be influenced by the order in which the
answers are arranged. The voltage values in this problem can, of course,
be calculated first – even by observation, due to the association of the
number values of the resistors and power source voltage. This would not
be true of circuits with less obvious component values. However, it might
be worthwhile to point out at this time that voltage in a series circuit
distributes in accordance with the ratios of the series resistance in the
circuit. In this case, the voltage across the 600 S resistor must equal twice
the voltage across the 300 S resistor. The actual resistance values are
unimportant in this calculation. It is their ratio that matters. If one resistance
was 3 S and the other 6 S, the voltage distribution would be the same. The
circuit current would change but not the voltage division.
G 6. IT = 0.1 A
I1 = 0.1 A
I2 = 0.1 A
V1 = 40 V
V2 = 60 V
1-24
Circuit Solution – Part I
G 7. IT = 0.1 A
I1 = 0.1 A
I2 = 0.1 A
I3 = 0.1 A
V1 = 30 V
V2 = 60 V
V3 = 20 V
G 8. I2 = 0.133 A
I1 = 0.133 A
V1 = 40 V
VA = 120 V
IT = 0.133 A
G 9. V1 = 60 V
V2 = 60 V
V3 = 60 V
VA = 60 V
I2 = 0.1 A
I3 = 0.05 A
IT = 0.35 A
G 10. V3 = 60 V
V2 = 60 V
I2 = 0.1 A
I1 = 0.3 A
V1 = 60 V
VA = 120 V
1-25
Circuit Solution – Part I
REVIEW QUESTIONS
1. If the applied voltage is doubled, the voltage across each paralleled resistor
also doubles. Since voltage and current are directly related, the currents would
also double.
2. All voltages would reverse their polarity. All currents would reverse their
direction of flow.
Figure 6-10.
4. V1 = 18 V V3 = 40 V
V2 = 8 V V4 = 18 V
1-26
Experiment 7
Circuit Solution – Part II
DISCUSSION
During this Laboratory Experiment, the students check out the calculations
performed in the previous laboratory experiment (Circuit Solution – Part I). They
connect each circuit and measure the voltages and currents, then compare the
measured values with the calculated values. They have an opportunity to apply
Kirchhoff’s current law in calculating current flow in parallel circuits. The simple fact
that the current leaving a junction must be equal to the current entering the junction
is an extremely useful tool for parallel circuit calculations. Its counterpart for series
circuits is Kirchhoff’s voltage law which specifies that the sum of the voltage drops
around a series circuit must equal the applied voltage. In connecting the circuits and
meters the students acquire additional practical experience in translating schematic
diagrams into actual operating circuits. This experience will be a great help later in
the course when several modules and metering units must be connected in different
ways. The remarks column in each procedure problem should be used to indicate
significant variation between calculated and measured values. Variations of 10 %
or less are well within tolerance and need not be remarked. Note that the answer
columns are located below the figures.
PROCEDURE
G 2.
MEASURED CALCULATED
REMARKS
VALUES VALUES
G 3.
MEASURED CALCULATED
REMARKS
VALUES VALUES
V1 = 60 V V1 = 60 V agree
V2 = 60 V V2 = 60 V agree
1-27
Circuit Solution – Part II
G 4.
MEASURED CALCULATED
REMARKS
VALUES VALUES
G 5.
MEASURED CALCULATED
REMARKS
VALUES VALUES
V1 = 30 V V1 = 30 V agree
V2 = 60 V V2 = 60 V agree
G 6.
MEASURED CALCULATED
REMARKS
VALUES VALUES
V1 = 40 V V1 = 40 V agree
V2 = 60 V V2 = 60 V agree
1-28
Circuit Solution – Part II
G 7.
MEASURED CALCULATED
REMARKS
VALUES VALUES
V1 = 30 V V1 = 30 V agree
V2 = 60 V V2 = 60 V agree
V3 = 20 V V3 = 20 V agree
G 8.
MEASURED CALCULATED
REMARKS
VALUES VALUES
V1 = 40 V V1 = 40 V agree
G 9.
MEASURED CALCULATED
REMARKS
VALUES VALUES
V1 = 60 V V1 = 60 V agree
V2 = 60 V V2 = 60 V agree
V3 = 60 V V3 = 60 V agree
VA = 60 V VA = 60 V agree
1-29
Circuit Solution – Part II
G 10.
MEASURED CALCULATED
REMARKS
VALUES VALUES
V3 = 60 V V3 = 60 V agree
V2 = 60 V V2 = 60 V agree
V1 = 60 V V1 = 60 V agree
REVIEW QUESTIONS
Figure 7-12.
1-30
Circuit Solution – Part II
Figure 7-13.
3. No. The indicator may possibly bend but the meter movement will not be
damaged unless its rated overload capacity is exceeded.
4. The ammeter. Its low internal resistance would cause it to draw excessive
current.
5. Yes.
No. It could be measured but the reading would be very low on the scale and
impossible to read accurately.
1-31
Circuit Solution – Part II
Figure 7-14.
1-32
Experiment 8
Power in DC Circuits – Part I
DISCUSSION
Power is the rate at which work is done and, in electricity, is the combination of
voltage (pressure) and current (rate of electron flow). When a given voltage forces
a given amount of current through the resistance of a load, power is consumed by
the load in the form of heat or light or some form of work. In dc circuits, power is the
product of voltage and current. However, the resistance offered by the load, since
it controls current through the load, is a factor in power calculations. Where either
voltage or current is known and the load resistance is known, power can be
calculated by substituting the Ohm’s Law equivalent of the unknown value. For
example, in Procedure 2 (Figure 8-1) the applied voltage is 120 V and the
resistance is 300 S.
P=ExI
By Ohm’s Law:
I = E/R
Simplifying:
P = E²/R
P = 120²/300
= 14 400/300
= 48 W
PROCEDURE
G 2.
V1 = 120 V PR1 = 48 W
I1 = 0.4 A PT = 48 W PS = 48 W
1-33
Power in DC Circuits – Part I
G 3.
V1 = 60 V PR1 = 12 W
V2 = 60 V PR2 = 6 W PS = 18 W
I1 = 0.2 A PT = 18 W
I2 = 0.1 A
IT = 0.3 A
REMARKS satisfactory
G 4.
V1 = 120 V PR1 = 48 W
V2 = 120 V PR2 = 24 W PS = 84 W
V3 = 120 V PR3 = 12 W
I1 = 0.4 A PT = 84 W
I2 = 0.2 A
I3 = 0.1 A
G 5.
IT = 0.1 A
I1 = 0.1 A PR1 = 3 W
I2 = 0.1 A PR2 = 6 W PS = 9 W
V1 = 30 V PT = 9 W
V2 = 60 V
REMARKS satisfactory
1-34
Power in DC Circuits – Part I
G 6.
IT = 0.1 A
I1 = 0.1 A PR1 = 4 W
I2 = 0.1 A PR2 = 6 W PS = 10 W
V1 = 40 V PT = 10 W
V2 = 60 V
REMARKS satisfactory
G 7.
IT = 0.1 A
I1 = 0.1 A
I2 = 0.1 A PR1 = 3 W
I3 = 0.1 A PR2 = 6 W PS = 11 W
V1 = 30 V PR3 = 2 W
V2 = 60 V PT = 11 W
V3 = 20 V
REMARKS satisfactory
1-35
Power in DC Circuits – Part I
G 8.
CALCULATED POWER POWER SUPPLIED
VALUES DISSIPATED (IT x Ein)
I2 = 0.133 A
VA = 120 V PT = 15.96 W
IT = 0.133 A
REMARKS satisfactory
G 9.
CALCULATED POWER POWER SUPPLIED
VALUES DISSIPATED (IT x Ein)
V1 = 60 V
V2 = 60 V
V3 = 60 V PR1 = 12 W
VA = 60 V PR2 = 6 W PS = 21 W
I2 = 0.1 A PR3 = 3 W
I3 = 0.05 A PT = 21 W
IT = 0.35 A
REMARKS satisfactory
G 10.
CALCULATED POWER POWER SUPPLIED
VALUES DISSIPATED (IT x Ein)
V3 = 60 V
V2 = 60 V PR1 = 18 W
I2 = 0.1 A PR2 = 6 W PS = 36 W
I1 = 0.3 A PR3 = 12 W
V1 = 60 V PT = 36 W
VA = 120 V
REMARKS satisfactory
1-36
Power in DC Circuits – Part I
REVIEW QUESTIONS
J/s
1. Power (J/s) ' 600 W x 1 ' 600 J/s
W
Btu/hr
Power (Btu/hr) ' 600 W x 3.43 ' 2058 Btu/hr
W
2. The 300 S resistor has twice the current flowing through it, therefore, it
dissipates twice the power and is hotter.
3. The 600 S resistor has twice the voltage across it, therefore, it dissipates twice
the power and is hotter.
4. The resistor dissipating the most power (R2) must be the largest, while the one
dissipating the least power (R3) must be the smallest in order for all resistors
to attain the same temperature.
1 2 3 4 5 6 7 8
P (watts) 30 40 50 10 k 10 k 50 70 72
Table 8-1.
1 2 3 4 5 6 7 8
I (amps) 1 3 1 6 50 12 5 8
Table 8-2.
1-37
Power in DC Circuits – Part I
To solve the problem in column seven without getting ahead of the manual, use
the applicable equations R = E/I and P = E x I as follows:
(1) E/I = 10
(2) E x I = 250
E = 10 x I
(10 x I) x I = 250
Solve for I.
10 x I² ' 250
I² ' 250/10 ' 25
I ' 25 ' 5
= 1/12 x 144
= 144/12 = 12 S
= 120/12 = 10 A
d) P (instantaneous) = E x I (instantaneous)
= 120 x 10 = 1200 W
1-38
Experiment 9
Power in DC Circuits – Part II
DISCUSSION
In this Laboratory Experiment, the students learn that resistance is also a factor in
calculating power and that when any two of the Ohm’s Law factors (voltage, current
or resistance) are known, power can be calculated. The size, or total exposed area
of a resistor is a factor in determining the amount of power it can handle; it has no
bearing on the ohmic value.
PROCEDURE
b. The ohmic value, tolerance, and power rating are printed on the body
of resistors. The 300 S resistor can dissipate 50 W, the 600 S resistor,
25 W and the 1200 S resistor, 12 W.
G 3. IR1 = 0.4 A
G 7. 1) (P = E x I) = 120 x 0.2 = 24 W
2) (P = I² x R) = 0.04 x 600 = 24 W
3) (P = E²/R) = 14 400/600 = 24 W
G 9. a. I = 0.1 A
ER1 = 20 V
b. ER2 = 30 V
c. ER3 = 40 V
1-39
Power in DC Circuits – Part II
e. PS = ES x IS = 90 x 0.1 = 9 W
Yes.
G 12. I = 0.133 A
Yes.
PT = 27 + 13.5 = 40.5 W
Yes, since the difference between the calculated and measured values is
well within the accuracy of the measuring instrument.
REVIEW QUESTIONS
1. a) PR1 = 80 W
PR2 = 3 W
PR3 = 54 W
PTOTAL = 137 W
1-40
Power in DC Circuits – Part II
b) PR5 = 200 W
PR6 = 160 W
PTOTAL = 360 W
c) PR7 = 640 W
PR8 = 180 W
PR9 = 300 W
PTOTAL = 1120 W
S m
2. a) R ' 5.58 x 50 m/1000 ' 0.279 S
km km
b) E = I x R
E = 10 x 0.279 = 2.79 V
E ' I x R
' 10 x 0.32 ' 3.2 V
3. P = E²/R
= 120²/240 = 14 400/240 = 60 W
5. a) P = I²R = (2 x 104)² x 2
P = 4 x 108 x 2 = 8 x 108 W
= 800 000 000 W = 800 MW
b) E = IR
= 2 x 104 x 2 = 4 x 104 V = 40 000 V
= 40 kV
1-41
Power in DC Circuits – Part II
J/s
Power (J/s) = 1 x 1200 W = 1200 J/s
W
g J
Energy Required (J) = 50 kg x 1000 x 60E x 4.18 = 12.54 x 106J
kg deg x g
J s
time (hr) = 12.54 x 106J / (1200 x 3600 ) = 2.9 hours
s hr
The heating rate is 1200 J per second and the total heat required is 12.54 MJ;
therefore, the time required is:
1-42
Power in DC Circuits – Part II
1-43
1-44
Experiment 10
The Transmission Line
DISCUSSION
Electric power engineers probably think of Utopia as a place where power sources
deliver exactly what the loads required, with no power wasted in the intervening
transmission lines. However, in this imperfect world, it is a sad but unalterable fact
that even the best conducting material has some resistance and, if long lengths of
the material are used, the resistance becomes a factor to be reckoned with.
Consider a 3-meter length of copper wire with a resistance of 0.01 S
connecting a 10 V power source to a load having a resistance of 10 S. For all
practical purposes, all of the power source voltage appears across the load and the
power dissipated by the load is 10²/10 = 10 W. The line resistance can safely be
ignored. But if 3.2 kilometers of the same size wire is used to connect
power source and load, the resistance of the wire becomes approximately 10.6 S
and more power would be dissipated in the transmission line than in the load. The
object of the game is to keep the losses as low as possible. This demonstration
shows the students that, as the load current increases, the amount of power
dissipated in the line increases until, when a dead short is placed across the ends
of the line, the line overheats and is soon destroyed. It is advisable tu use wire with
enamel or varnish insulation rather than plastic, cloth or rubber. The insulation will
smoke and burn when the transmission line is shorted and enamel or varnish
insulation makes for less mess and odor. If 0.2 mm wire is not readily
available, any smaller wire down to 0.1 mm will be suitable.
PROCEDURE
V1 V2 V3 I
(VOLTS) (VOLTS) (VOLTS) (AMPS)
Table 10-1.
G 5. Yes.
V1 V2 V3 I
(VOLTS) (VOLTS) (VOLTS) (AMPS)
Table 10-2.
1-45
The Transmission Line
G 7. b. V1 ! V3 = 8 V
c. Yes.
V1 V2 V3 I
(VOLTS) (VOLTS) (VOLTS) (AMPS)
Table 10-3.
G 9. b. V1 ! V3 = 14 V
c. Yes.
d. Yes. The increase in current through the line caused a larger voltage
drop than in Procedure 7 (b).
e. Yes.
h. 22 W
G 10. e.
Note to the Instructor: Bear in mind the fact that, with a dead short as a
load, the transmission wire becomes extremely hot. Check the
transmission line before applying power and make sure it is not touching
anything that will melt, char or burn.
REVIEW QUESTIONS
2. If the line sags it may touch other nearby transmission lines causing further
shorts. The external heat may cause fires.
1-46
The Transmission Line
3. With a dead short, the line current was limited only by the low resistance of the
line. The high current caused the line to heat.
Figure 10-4.
d) P load = I² x R load
= 120² x 180 = 14 400 x 180
= 2.592 MW
e) P line = I² x R line
= 120² x 20 = 14 400 x 20
= 288 kW
f) E load = I x R load
= 120 x 80 = 21.6 kV
E load = P load/I
= 2.592 x 106/120 = 21.6 kV
1-47
The Transmission Line
Load voltage can also be calculated by multiplying the ratio of load resistance
to total resistance by the source voltage.
g) With the load disconnected, there will be no line current flowing; therefore,
there will be no line voltage drop and the full 24 kV will appear.
6. a) P = E²/R R = E²/P
c. P heater = I² x R heater
= (12.72)² x 7.2 = 161.8 x 7.2
= 1165 W
1-48
The Transmission Line
1-49
1-50
Experiment 11
AC Voltage and Current – Part I
DISCUSSION
Since both alternating and direct current are widely used, we must have some
convenient means of comparing them or evaluating alternating current in terms of
direct current. Because power is a function of the square of voltage (P = E²/R) or
current (P = I²/R), the heating effect or equivalent DC value must be calculated
using squared values of voltage or current. If the instantaneous voltage values of
Procedure 1 are taken at very small angular intervals, squared, added together and
then the average or mean value taken, the square root of the result will be the
effective, or root-mean-square, value – 70.7 V. If the same procedure is followed for
current, it will be found that the 50 A peak AC current is as effective as 35.35 A of
direct current. The frequency of the squared values will be double that of the original
sine wave since all squared values are positive and are now alternating about the
effective value. The power waveform has twice the frequency of the initial sine
wave.
PROCEDURE
1-51
AC Voltage and Current – Part I
Figure 11-2.
1-52
AC Voltage and Current – Part I
G 5. 0E P =0x0=0W
30E P = 50 x 25 = 1250 W
150E P = 50 x 25 = 1250 W
180E P =0x0=0W
360E P =0x0=0W
G 7. a. Pmax = 5000 W
b. Pmin = 0 W
c. PRL = 2500 W
1-53
AC Voltage and Current – Part I
REVIEW QUESTIONS
1. a) 1/60 or 0.0167 s
2.
Figure 11-4.
E peak = E rms/0.707
= 120/0.707 = 169.7 V
4. The amount of light would be the same. Unless otherwise specified, all AC
values are understood to be in rms which is as effective as DC values.
5. Zero to maximum occurs in one quarter of a cycle or 90E. Time for 90E is:
(1/4) (1/60) = 1/240 or 0.00417 s or 4.17 ms.
6. Since only half the cycle is positive, the time duration is: (1/2) (1/60) = 1/120 or
0.00833 s or 8.33 ms.
8. Effective current and voltage alternating values which have the same heating
effect on a resistive load as equivalent direct current values.
9. rms (root-mean-square)
1-54
AC Voltage and Current – Part I
10. a) Yes.
b) Yes.
1-55
1-56
Experiment 12
AC Voltage and Current – Part II
DISCUSSION
PROCEDURE
G 3. a. Edc = 120 V dc
1 2 3 4
Table 12-1.
c. Yes.
1-57
AC Voltage and Current – Part II
RL = 57 S 100 S 57 S 100 S
Table 12-2.
c. Yes.
d. Yes.
e. Yes.
REVIEW QUESTIONS
1. The meters cannot follow the AC alternations and indicate only the average
values, which are zero.
If the alternating frequency is low enough, the meter will oscillate between two
extreme values; the values being limited by the inertia of the meter movement
and its ability to follow the alternations. A zero center meter will move the same
distance in each direction and the average value (in this case, zero) will be
midway between the two extremes. If the AC voltage is alternating about some
DC level, the midpoint between the extremes will be the DC level.
2. The effective or rms values are of primary importance in most calculations. The
peak or peak-to-peak values can be calculated when needed.
3. Yes.
1-58
AC Voltage and Current – Part II
E peak = E rms/0.707
= 600/0.707 = 848.7 V
5. a) I rms = P/E
= 60/120 = 0.5 A ac
b) R = E/I
= 120/0.5 = 240 S
I peak = I rms/0.707
= 0.5/0.707 = 0.707 A
1-59
1-60
Experiment 13
The Wattmeter
DISCUSSION
Inductors and capacitors are called reactive devices. A perfect reactive device will
cause a phase shift of 90E between voltage and current so that, when a voltage is
maximum, current is zero and vice versa. Although voltage and current are present
in reactive circuits, their product, E x I, is “apparent” power – often called “wattless”
power, because it does no work. Most reactive circuits produce a phase shift angle
somewhere between zero and 90E. The precise phase shift and “actual” or “true”
power produced can be calculated using trigonometry. However, the wattmeter
indicates true power without the need for calculation. The wattmeter contains a
current coil and a voltage or potential coil, one of which is movable and is attached
to an indicator. The interaction of the magnetic fields resulting from current flow
through the two coils is additive and causes the indicator to move up the scale.
When voltage and current are in phase, the deflecting force is always in the same
direction. When a phase differential exists, current through one coil will reverse
before current reverses in the other, resulting in a reverse torque while the two
currents are flowing in opposite directions. The inertia of the indicating element
prevents it from following the torque reversals, however, and the resulting indication
is the resultant of the two torques. If the torques are equal, and opposite, as when
the phase angle is 90E, the wattmeter will indicate zero power.
PROCEDURE
G 3. a. IL = 2.1 A ac
b. Pin = 252 W
c. Pin = 252 W
d. Yes.
G 6. b.
E= 0V 40 V 80 V 120 V
W= 0W 28 W 112 W 252 W
Table 13-1.
1-61
The Wattmeter
G 7. Yes
G 9. a. IL = 2.1 A ac
b. Pin = 0 W
c. E x I = 252 VA
G 11. a. IL = 2.1 A ac
c. E x I = 252 VA
G 12. Note to the Instructor: Have the students use the next higher range of the
ammeter. The total capacitive reactance at 60 Hz is 57 S so current through the
capacitance is 120/57 = 2.1 A. The same value of current flows through the
resistance but the two currents are 90E out of phase. The actual line current as
measured by the ammeter flows at a 45E angle and can be calculated as follows:
However, the active power must be limited to the power in the resistance, which is
252 W.
I = 2.97 A
REVIEW QUESTIONS
1. No. Voltage and current are always in phase in a resistive load so the product
of voltage and current (VA) give the active power (W).
2. Apparent power (VA) is always greater than active power (W) in circuits that
contain inductance or capacitance.
b) Active power = W
4. Procedure 3) PF = 252/252 = 1
1-62
The Wattmeter
Procedure 9) PF = 0/252 = 0
2. Iron, heaters.
1-63
1-64
Experiment 14
Phase Angle, Active and Apparent Power
DISCUSSION
PROCEDURE
This power is both real and apparent and is indicated by the wattmeter.
Apparent power is the product of voltage and current and is expressed in
volt-amperes (VA). Active power is the product of voltage, current and
power factor and is expressed in watts (W). (Power factor will be covered
in a later Laboratory Experiment.) In a resistive circuit, apparent power (VA)
equals active power (W), and the voltage and current waveforms are in
phase.
G 2. a. No.
b. Yes.
d. 2500 W
1-65
Phase Angle, Active and Apparent Power
Table14-1.
Figure 14-7.
1-66
Phase Angle, Active and Apparent Power
c. Yes.
d. Yes.
e. Yes.
g. 0 W.
Table 14-2.
1-67
Phase Angle, Active and Apparent Power
Figure 14-9.
c. Yes.
d. Yes.
e. Yes.
f. 2500 VA
g. 0 W
1-68
Phase Angle, Active and Apparent Power
REVIEW QUESTIONS
1. A resistor. Current and voltage are in phase when all instantaneous power
values are positive. An inductor or capacitor cause “negative” power loops.
2. a)
Figure 14-10.
b)
Figure 14-11.
1-69
Phase Angle, Active and Apparent Power
c)
Figure 14-12.
3. A reactive device takes power from the source during half a cycle and returns
power during the other half cycle. The average power is zero.
When the reactive phase angle is 90E, the power sine wave alternates about a
zero value. When the phase angle is less than 90E, the power sine wave
alternates about some value greater than zero.
b) 0E= 0 cycle
1-70
Experiment 15
Capacitive Reactance
DISCUSSION
PROCEDURE
G 6. c. I = 2.1 A ac
P=0W
G 7. a. XC = 57.1 S
b. C = 46.5 µF
c. S = -252 VA
d. Q = -252 var
1-71
Capacitive Reactance
REVIEW QUESTIONS
1. 90E
2. 90E
3. a) S = -1800 VA
b) Q = -1800 var
d) XC = 200 S
e) C = 13.26 µF
4. a) XC = 50 S
b) XC = 200 S
d) C = 26.5 µF
e) C = 26.5 µF
XC = infinite
5. C = 8.84 µF
1-72
Experiment 16
Inductive Reactance
DISCUSSION
PROCEDURE
G 6. c. I = 2.1 A ac
P = 15 W
The power indicated is due to the resistance of the wire in the inductor.
G 7. a. XL = 57.1 S
b. L = 0.151 H
c. S = 252 VA
d. Q = 252 var
REVIEW QUESTIONS
1. a) S = 1800 VA
b) Q = 1800 var
c) P = 0 W.
d) XL = 200 S
e) L = 0.53 H
1-73
Inductive Reactance
3. L = 0.796 H
It should be noted that capacitor and inductor values used in the variable
capacitor and inductor modules have been selected to present reactances to
60 Hz AC that are comparable to the values of the resistors in the resistance
modules.
5. a) XL = 200 S
b) XL = 50 S
d) L = 0.265 H
e) L = 0.265 H
f) XL = 0 S
1-74
Experiment 17
Watt, Var, Volt-Ampere, and Power Factor
DISCUSSION
The last two Laboratory Experiments brought out the fact that, when an AC circuit
contains pure reactance, either capacitive or inductive, voltage and current are 90E
out of phase and no real or useful power is developed. Most practical AC circuits
have some reactance, and the apparent power (VA) is greater than the active power
(W). The difference between apparent power and active power is caused by
reactance and is called reactive power (var).
In this Laboratory Experiment, the students observe the effect of the inductance of
the R-L load on apparent power and line current. They then reduce the line current
and apparent power by adding capacitance. They learn that, although the added
capacitive reactance can reduce the reactive line current to a minimum value, it
does not change the active power consumed by the load.
PROCEDURE
G 3. a. IL = 1.79 A ac
b. P = 160 W
G 4. b. S = 215 VA
c. PF = 0.74
d. Q = 143.6 var
G 6. d. IL = 1.35 A ac
e. P = 160 W
G 7. b. S = 162 VA
c. PF = 0.99
d. Q = 25.4 var
G 8. a. Yes.
b. No. Since the voltage across the R-L load did not change, the current
drawn by the R-L remains the same.
1-75
Watt, Var, Volt-Ampere, and Power Factor
c. Yes, because the capacitance does not draw any active power; it draws
only reactive power.
G 9. a. IL = 1.63 A ac
b. XC = 100 S
REVIEW QUESTIONS
1. a) S = 5 kVA
b) PF = 0.6
2. a) S = 3 kVA
b) Q = 0 var
c) P = 3 kW
The two reactances cancel, and apparent power is equal to active power.
Therefore, the power factor is one.
d) PF = 1
3. a) S = 5 kVA
b) Q = !4 kvar
d) PF = 0.6
The new power factor is the same as that calculated in 1. b) because the
reactance is the same in both cases. However, the reactive power factor
was lagging while this one is leading.
e) Yes. The additional negative var increased the apparent power by 2 kVA.
4. No. The R-L load still draws inductive current plus in-phase resistive current.
5. No. The motor operation does not change and the active power needed to
overcome friction, windage, copper and iron losses remains the same.
1-76
Experiment 18
Vectors and Phasors – Series Circuit
DISCUSSION
This Laboratory Experiment introduces the student to the rotating vector or phasor,
a means of measuring the resultant of phase differentiated quantities and resultant
phase angles. The vector is assumed to rotate in a counterclockwise direction from
a starting line which coincides with %x line of the x-y coordinate plane. Rotation from
%x through %y to !x represents the positive half-cycle of a sine wave while rotation
from !x through !y back to the starting point represents the negative half-cycle. The
in-phase component (current in series circuits and voltage in parallel circuits) is
drawn along the starting or zero degree line. Leading quantities, such as voltage
across an inductance, are drawn in the %y direction from the in-phase component.
If all given values are drawn to scale, the resultant can be measured directly from
the diagram as can the angle between the resultant and the in-phase component.
PROCEDURE
Figure 18-5b.
G 2. b. ER = 80 V
EL = 60 V
ES = 100 V
1-77
Vectors and Phasors – Series Circuit
G 3. a. ER + EL = 80 + 60 = 140 V
Figure 18-6b.
Phasor ER = 60 V Measured ER = 60 V
Phasor EC = 60 V Measured EC = 60 V
The vector representing the resultant value, in this case, ES, must start at
the point where ER and EC originate. A line connecting the ends of vectors
ER and EC is not the vector ES. Remember that the ES vector rotates about
the same point as the ER and EC vectors.
1-78
Vectors and Phasors – Series Circuit
Figure 18-7b.
Phasor EC = 60 V Measured EC = 60 V
Phasor EL = 80 V Measured EL = 80 V
Phasor ES = 20 V Measured ES = 20 V
1-79
Vectors and Phasors – Series Circuit
Figure 18-8b.
Phasor ER = 80 V Measured ER = 80 V
Phasor EL = 80 V Measured EL = 80 V
Phasor EC = 60 V Measured EC = 60 V
1-80
Vectors and Phasors – Series Circuit
Figure 18-9b.
Phasor EC = 60 V Measured EC = 60 V
Phasor EL = 60 V Measured EL = 60 V
Phasor ES = 0 V Measured ES = 0V
The inductor wire has some DC resistance, therefore, there will be a small
amount of in-phase voltage and, consequently, the measured ES will have
some value.
REVIEW QUESTIONS
1. a) 37E leading.
The actual value of this phase angle is 36.9E. The cosine of the angle is
equal to the ratio of the adjacent side, ER to the hypotenuse, ES, or 0.8. The
arc cosine of 0.8 is approximately 36.9E.
b) 45E lagging.
c) 14E leading.
2. a) S = 100 VA, P = 80 W
b) S = 84.8 VA, P = 60 W
1-81
Vectors and Phasors – Series Circuit
c) S = 82.5 VA, P = 80 W
3. a) PF = 0.8
b) PF = 0.707
c) PF = 0.97
1-82
Experiment 19
Vectors and Phasors – Parallel Circuits
DISCUSSION
Vector analysis can be applied with equal facility to both series and parallel circuits.
In solving series circuits, current is the reference quantity because it is common to
all of the circuit components. In parallel circuits, voltage is the reference because
it is common to all of the circuit branches. The out of phase component in parallel
circuits is current so the direction of phasors representing reactive currents is
reversed from that representing reactive voltages in series circuits - that is, the
phasor for capacitive current is drawn upward since it is leading and the phasor for
inductive current is drawn downward since it is lagging.
PROCEDURE
Figure 19-1b.
1-83
Vectors and Phasors – Parallel Circuits
Figure 19-2b.
Phasor IR = 2 A Measured IR = 2A
Phasor IC = 1 A Measured IC = 1A
1-84
Vectors and Phasors – Parallel Circuits
Figure 19-3b.
1-85
Vectors and Phasors – Parallel Circuits
Figure 19-4b.
Phasor IR = 1 A Measured IR = 1A
1-86
Vectors and Phasors – Parallel Circuits
Figure 19-5b.
1-87
Vectors and Phasors – Parallel Circuits
Figure 19-6b.
Phasor IR = 2 A Measured IR = 2A
1-88
Vectors and Phasors – Parallel Circuits
Figure 19-7b.
Phasor IC = 2 A Measured IC = 2A
Phasor IL = 2 A Measured IL = 2A
Phasor IS = 0 A Measured IS = 0A
IS phase angle = 0E
REVIEW QUESTIONS
1. Yes. Minor variations are caused by meter and component tolerances and by
DC coil resistances.
2. a) Yes. Since current varies directly with voltage all current values would be
reduced by one-half.
b) No. The phase angle would change only if the reactance values or the
frequency changed.
3. Yes. The same voltage is applied across equal reactances. Since the var are
equal and opposite in sign, they cancel each other.
1-89
Vectors and Phasors – Parallel Circuits
c) IC = 4A
IL = 2A
IS = 3A
Capacitive reactance is reduced by one half so capacitive current, IC, will double
from 2 A to 4 A. Inductive reactance is doubled so inductive current will be halved
from 2 A to 1 A. The resultant current will be that portion of capacitive current not
cancelled by inductive current or 4 ! 2 = 3 A. Since the resultant current is
capacitive, the phase angle will be close to 90E and leading.
1-90
Experiment 20
Impedance
DISCUSSION
Impedance calculations for series circuits are fairly straightforward and involve
phasor addition or application of the Pythagorean Theorem i.e.
If the reactances are equal, the quantity (XL !XC)2 is zero and the impedance is
simply the circuit resistance with a phase angle of zero. Where the reactances are
unequal, determination as to whether the phase angle is leading or lagging can be
readily accomplished by comparing the magnitudes of the reactances.
PROCEDURE
G 2. Z = 100 S
Calculated EC = 80 V Measured EC = 80 V
Calculated ER = 60 V Measured ER = 60 V
G 3. Z = 100 S
Calculated ES = 50 V Measured ES = 50 V
Calculated EL = 30 V Measured EL = 30 V
Calculated ER = 40 V Measured ER = 40 V
1-91
Impedance
G 4. Z = 48 S
Calculated IR = 2 A Measured IR = 2A
G 5. Z = 100 S
Calculated ES = 50 V Measured ES = 50 V
Calculated ER = 40 V Measured ER = 40 V
G 6. Inductive and capacitive reactances are equal and cancel each other. The
circuit impedance is, therefore, equal to the resistance of 80 S.
Z = R = 80 S
Calculated IC = 2 A Measured IC = 2A
Calculated IL = 2 A Measured IL = 2A
REVIEW QUESTIONS
1. Z = 40 S
2. No. The phase angle can only be calculated if two of the three factors, R, Z or
X are known.
3. False. This equation indicates apparent power (VA) which may include reactive
and active powers.
1-92
Impedance
Note to the Instructor: It would be appropriate at this point to review apparent power,
active power, and reactive power.
Apparent power is the product of line voltage times line current, and does not take into
account their phase relationship. When voltage and current are in phase, apparent power
is equal to active power. S = E x I
Active power is the power actually consumed by the circuit. It is calculated as the phasor
difference between apparent power and reactive power.
P ' S2 & Q2
Reactive power or var is the product of the out-of-phase voltages and currents. It is
calculated as the phasor difference between apparent power and active power.
Q ' S2 & P2
4. Yes. Impedance includes resistance and reactance. If the circuit has only
resistance the reactive component is 0 S.
5. Yes. The reactive component of impedance varies with frequency. This causes
impedance to vary with frequency.
1-93
1-94
Experiment 21
Three-Phase Circuits
DISCUSSION
In a single-phase circuit, the power is of a pulsating nature. At unity power factor the
power is zero twice each cycle. When the power factor is less than unity, the power
is negative during parts of each cycle. Although the power supplied to each of the
three phases of a balanced three-phase load is pulsating, the total power is
constant. Because of this, the operating characteristics of three-phase machines in
general, are superior to those of similar single-phase machines.
PROCEDURE
G 1. c. E4 to 5 = 208 V ac
E5 to 6 = 210 V ac
E4 to 6 = 209 V ac
Note to the Instructor about three-phase measurements: The three line voltages
of a three-phase system are not always exactly equal in magnitude. This condition
can be caused by unbalanced loading somewhere between the power company
generators and the receptacle furnishing power to the Power Supply. Therefore,
when performing experiments that call for a specific three-phase input voltage
setting, it is possible to be metering a high or low line-to-line or line-to-neutral
voltage. Also, due to the multiplicity of meter and component tolerances plus human
errors, the measurements taken by the students may vary considerably from the
values listed in this manual. However, the desired trend, or changes indicated by
their results will be comparable to the answers given.
e. Eline-to-line = 209 V ac
G 2. c. E4 to N = 120 V ac
E5 to N = 120 V ac
E6 to N = 120 V ac
1-95
Three-Phase Circuits
e. Eline-to-line = 120 V ac
b. Yes.
G 4. a. E1 to 2 = 214 V ac E1 to N = 125 V ac
E2 to 3 = 217 V ac E2 to N = 123 V ac
E1 to 3 = 215 V ac E3 to N = 122 V ac
b. Yes.
c. Single-phase voltage.
G 5. d. E1 = 122 V ac I1 = 0.304 A ac
E2 = 121 V ac I2 = 0.302 A ac
E3 = 120 V ac I3 = 0.308 A ac
f. Yes.
g. Eload = 121 V ac
h. Eline-to-line = 209 V ac
j. Yes.
k. P1 = 37.1 W
P2 = 36.5 W
P3 = 37 W
l. PT = 110.6 W.
E2 = 119 V ac I2 = 0.299 A ac
E3 = 120V ac I3 = 0.305 A ac
1-96
Three-Phase Circuits
f. Yes.
g. Iload = 0.302 A ac
j. I4 = 0.52 A ac
I5 = 0.51 A ac
I6 = 0.52 A ac
If the currents exceed 500 mA, have the students change to the next
higher meter ranger.
l. Iline = 0.517 A ac
n. Yes.
o. P1 = 36.4W
P2 = 35.6W
P3 = 36.6 W
p. PT = 108.6W
REVIEW QUESTIONS
1. Eline-to-neutral = Eline-to-line / 3
= 200 V
3. In a wye connected circuit, the line current and the load current are equal.
Therefore, if the load current is 10 A, the line current is also 10 A.
Since P = E2 / R, E2 = P x R
E2 = 1 000 x 10 = 10 000
E= 10 000 = 100 V
1-97
Three-Phase Circuits
Iline = Iload x 3
= 69.2 A
b) Since it is a balanced three-phase load, the total power is three times the
power dissipated in each phase.
PT = 3 x Eline x Iload
or
PT = Eline x Iline x 3
= 52 800 W
1-98
Experiment 22
Three-Phase Watts, Vars, and Volt-Amperes
DISCUSSION
In a balanced wye (Y) connected three-phase load, the line-to-line (Eline) voltage is
equal to 3 , or approximately 1.73 times each line-to-neutral (Ephase) voltage. Each
line current (Iline) is the same as each load current (Iphase). However, in a balanced
delta ()) connected three-phase load, the voltage and current characteristics are
opposite to those of a wye connection. The line-to-line voltage (Eline) is the same as
each load voltage (Ephase) but the line current (Iline) is equal to 3 times each load
current (Iphase).
The formulas used for calculating active, apparent and reactive three-phase power
are essentially the same as used for single-phase power except for the additional 3
factor. From the formula for power in a single-phase circuit, the power developed
in each phase (P phase) of either a delta or wye connection is:
where 2 is the angle between the phase current and the phase voltage.
The total power in all three phases of a balanced three-phase load is then:
Ptotal = 3 x Pphase
In a delta connection:
1-99
Three-Phase Watts, Vars, and Volt-Amperes
Again the three-phase power in terms of line current and voltage is:
Thus, the expression for three-phase power in a balanced system either wye- or
delta - connected, is equal to:
If (Ephase x Iphase x cos 2) is the power per phase in watts, then (Ephase x Iphase)
represents the volt-amperes per phase. If follows, then, that the three-phase
apparent power in either a wye or delta system may be found by:
PF = P / S (5)
or is equal to the cosine of the angle between the phase current and phase voltage.
Three-phase reactive power is equal to the sum of the three reactive powers per
phase or:
Q2 = S2 ! P2
PROCEDURE
G 1. d. E1 = 117 V ac I1 = 0.402 A ac
E2 = 114 V ac I2 = 0.402 A ac
E3 = 114 V ac I3 = 0.408 A ac
f. Yes.
g. Iline = 0.404 A ac
h. Eline-to-line = 208 V ac
i. E1 x I1 = 47 var (L1)
E2 x I2 = 45.8 var (L2)
E3 x I3 = 46.5 var (L3)
1-100
Three-Phase Watts, Vars, and Volt-Amperes
G 2. d. E1 = 72 V ac I1 = 0.225 A ac
E2 = 69 V ac I2 = 0.225 A ac
E3 = 70 V ac I3 = 0.23 A ac
g. E4 = 90 V ac
E5 = 90 V ac
E6 = 90 V ac
i. 90 x 0.225 = 20.3 W
90 x 0.225 = 20.3 W
90 x 0.23 = 20.7 W
Total 3N active power = 61.3 W
l. Iline is the average of the three line currents (I1, I2, I3) listed in 2 (d)
= 0.226 A.
Eline-to-line x Iline x 1.73 = 81.3 VA
m. Yes.
REVIEW QUESTIONS
1. a) S = 7 612 VA
b) P = 6 090 W
c) Q = 4 567 var
2. I = 28.9 A
1-101
1-102
Experiment 23
Three-Phase Power Measurement
DISCUSSION
Power in an AC circuit depends on the power factor of the circuit as well as the
current and the voltage. At unity power factor, the current in both the current and
potential coils of a wattmeter reverses at the same time, resulting in a deflecting
force on the moving element which is always in the same direction. However, at
power factors less than unity, the current in one element reverses torque during the
time that the two currents are in opposite directions. The inertia of the moving
element prevents it following the torque reversals, so that the meter indication is the
resultant of the two torques. Thus, the wattmeter indicates the active or actual
power of an AC circuit.
PROCEDURE
G 2. c. I1 = 0.4 A ac
P1 = +70 W
P2 = +70 W
G 3. a. S = 144 VA
P = 140 W
PF = 0.972
b. Yes. Since the load is resistive the power factor should be unity.
Because of meter and load tolerances, the calculated power factor may
not be exactly unity.
G 4. c. I1 = 0.4 A ac
P1 = +10 W
P2 = !10 W
P1 + P2 = 0 W
1-103
Three-Phase Power Measurement
d. S = 144 VA
P=0W
PF = 0
Q= 144 var
G 5. c. I1 = 0.39 A ac
P1 = !36 W
P2 = +42 W
P1 + P2 = 6 W
d. S = 140 VA
P=6W
The inductors will dissipate some active power due to the winding
resistance and core losses.
PF = 0.043
Q = 140 var
REVIEW QUESTIONS
1. No. Each meter measures a portion of the total 3 N power, depending on the
power factor and how well the loads and line voltages are balanced.
2. That the load power factor is less than 50%. This occurs when the phase angle
between the voltage and current seen by the wattmeter is greater than 90E.
3. Yes. The total power would be three times the indicated power if the meter were
connected to measure one of the loads. See Figure 23-2.
4. Yes. Because of the missing neutral wire, two measurements must be made.
Single scale polyphase wattmeters are often used in heavier power circuits. Of
course, one single-phase wattmeter could be used to measure the total three-
phase power by switching it around to the various connections and positions,
and then taking the algebraic sum of the readings.
5. Yes. When the voltage and current are exactly 90E out of phase,
E x I x cos N = 0.
1-104
Experiment 24
Phase Sequence
DISCUSSION
A three-phase power line with unmarked wires can be tested with this phase
sequence indicator, and the wires then labeled accordingly. If the wires are already
labeled as A, B, and C, then the sequence indicator will show whether the actual
sequence is ABC or ACB, these two being opposite sequences.
PROCEDURE
G 2. d. Terminal 4 = Bright
Terminal 5 = Dim
Terminal 6 = Capacitor
The bright lamp will be connected to the leading phase of the three, the
dim lamp will be connected to the middle phase of the three, and the
capacitor will be connected to the most lagging phase of the three. If
the wall receptacle is wired correctly, terminal 4 of the power supply will
be the leading phase (bright lamp), terminal 5 of the power supply will
be the middle phase (dim lamp), and terminal 6 of the power supply will
be the most lagging phase (capacitor). This classification of the
terminal voltages as the leading, the middle, and the most lagging of
the three, means that the voltage on terminal 4 will lead the terminal 5
voltage by 120 electrical degrees, and the terminal 5 voltage will lead
the terminal 6 voltage by 120 electrical degrees. We can then say that
the phase sequence or the order in which the three voltages reach their
peak values, is 4 - 5 - 6. If this 4 - 5 - 6 sequence is repeated as 4 - 5 -
6 - 4 - 5 - 6 - 4 - 5 - 6..., it can be seen that sequence 4 - 5 - 6 is the
same as sequence 5 - 6 - 4, which is the same as sequence 6 - 4 - 5.
It just depends on which phase is used as the reference phase from
which to compare the others.
G 3. c. Terminal 4 = Bright
Terminal 5 = Dim
Terminal 6 = Capacitor
With two of the leads interchanged, the lamp that was dim in Procedure
2 will now be the bright one, and the bright-dim-capacitor sequence will
still determine the phase sequence which will be 5 - 6 - 4, 6 - 4 - 5 or 4 -
5 - 6, which are all identical.
e. Yes. The phase sequence did not change because the power company
does not change its phase sequence.
1-105
Phase Sequence
REVIEW QUESTIONS
1. Yes. By observing the direction of rotation and then comparing it when the
motor is connected across another three phase line.
2. No.
The three line-to-neutral voltages are not 120E out of phase with each other,
because the neutral point is not at zero potential when the phase loads are
unbalanced as they are in this circuit.
1-106
DC Machines
Experiment 0
Safety and the Power Supply
See Experiment 4 of the volume titled Power Circuits (page 1-15 of this manual).
2-1
2-2
Experiment 1
Prime Mover and Torque Measurement
DISCUSSION
During this Laboratory Experiment, the student becomes familiar with the basic
operation of the 3N synchronous motor, the Prony brake, and the electrodynamo-
meter. The synchronous motor must, by its nature and design, run at a constant,
unvarying speed. If it is loaded beyond where it can maintain constant speed, it will
come to a stop. As will be seen in later Laboratory Experiments, this capability is
unique in that it is the only motor that maintains constant speed despite variations
in load or applied power. Single phase synchronous motors are small and are
intended for steady but light loads. They are used extensively for quality
phonograph motors, magnetic tape drives, and electric clock movements.
The electrodynamometer indicates torque. The strength of the stator magnetic field
can be increased or decreased by a front panel control. The strength of the
magnetic field determines the degree to which the revolving rotor is able to cause
the stator to change position on its axis. The arc described by the shifted stator
represents torque and is indicated on a scale marked on the perimeter of the stator
housing.
The Prony brake also indicates torque. The difference between the forces applied
at the two ends of the friction belt is equal to the retarding force applied to the
friction pulley. This force, multiplied by the radius of the friction pulley, constitutes
the motor loading torque. The built-in spring balance converts the retarding force
into an accurately calibrated torque indication.
PROCEDURE
G 5. b. I1 = I2 = I3 = 0.13 A ac.
d. I1 = I2 = I3 = 0.55 A ac
2-3
Prime Mover and Torque Measurement
G 7 a. The speed remains constant at 1800 r/min for all levels of excitation.
b. Rotation = Clockwise.
G 8. b. Rotation = Counterclockwise.
G 11. b. Yes.
Yes.
G 12. b. Yes.
d. No.
G 16. a. I1 = I2 = I3 = 0.8 A ac
b. 1800 r/min
c. No.
G 20. e. I1 = I2 = I3 = 0.13 A ac
h. I1 = I2 = I3 = 0.8 A ac
2-4
Prime Mover and Torque Measurement
REVIEW QUESTIONS
2. Excitation above or below the optimum, or unity power factor setting, causes the
current through the stator windings to increase.
= 2B x 1800 x 1 / 60
= 188.5 W
= 2B x 1800 x 2.4 / 60
= 452 W
The Prony brake requires turning one wheel to vary the torque and another
wheel to bring the balance in equilibrium and read the torque.
2-5
2-6
Experiment 2
The Direct Current Motor – Part I
DISCUSSION
PROCEDURE
G 2. c. 4 poles.
G 3. b. 75 commutator bars.
c. 2 brushes.
G 4. a. 5 and 6.
b. 3 and 4.
d. 1 and 2.
G 5. a. 7 and 8.
2-7
The Direct Current Motor – Part I
G 9. c. E(armature) = 25 V dc
This value may be a little above or below 20 V dc. If above, use the
200 V dc range.
REVIEW QUESTIONS
1. I = 0.45 A dc
2. E = 5.1 V dc
4. It is a good conductor.
Copper is an excellent conductor and offers very low resistance to current flow.
Resistance is a factor in power dissipation (I2R) and should be as low as
possible to prevent losses due to coil heating. With lower power losses,
efficiency is increased and, with less heat to dissipate, the frame and motor size
and bulk can be made smaller.
The carbon brushes are inexpensive and easy to replace. Use of carbon
brushes insures minimum wear on the commutator which is relatively expensive
and difficult to replace.
6. a) I = 70.6 A
b) P = 8 472 W
c) Yes.
2-8
The Direct Current Motor – Part I
8. I = 12 A dc
2-9
2-10
Experiment 3
The Direct Current Motor – Part II
DISCUSSION
In this Laboratory Experiment, the student further investigates the basic properties
of DC motors. An important aspect of DC motor operation is counter, or back, EMF;
the voltage induced in the armature windings due to their cutting through the stator
magnetic fields. Counter EMF (CEMF) opposes the source EMF; therefore, current
through the armature windings is a function of the difference between applied EMF
and CEMF. If the applied voltage or source EMF is increased, current through the
armature will increase and so will the motor speed. CEMF is caused by the current
carrying armature coils cutting through the magnetic field between the stator poles.
If this magnetic field is made weaker, less CEMF is induced and more current will
flow through the armature coils. The armature will rotate faster in an attempt to
induce more CEMF to limit armature current. Speed then is affected by two factors:
the applied voltage and the strength of the stator magnetic field.
PROCEDURE
G 7. a. Yes.
b. Rotation = Clockwise.
Rotation = Counterclockwise.
2-11
The Direct Current Motor – Part II
e. Rotation = Clockwise.
G 15. a. No.
b. No.
G 18. b. CEMF drops due to loss of magnetic field, causing armature current to
increase, causing speedup.
When the shunt coil is opened, the magnetic field strength in the stator
fields is limited to the residual flux in the stator. The armature coils are
cutting through extremely weak magnetic flux lines and very little CEMF
is induced in the armature. Without CEMF to limit it, armature current
and rotational speed increase greatly. The Lab-Volt motors have been
designed to withstand this mistreatment. However, a great majority of
motors would increase in speed until destruction.
c. No. Removing the field power also removes the armature power
stopping the motor.
E
0 30 60 90 120
(volts)
SPEED
0 285 590 840 1 200
(r/min)
Table 3-1.
2-12
The Direct Current Motor – Part II
Figure 3-6.
e. Yes.
REVIEW QUESTIONS
1. With AC applied to the armature, adjust brushes for zero induced AC in shunt
winding.
2. No. Assuming no residual stator flux, a large armature current would flow, but
the motor would not start. If sufficient residual flux is present, the motor would
start and rapidly accelerate to excessive speed due to high armature current
and a weak stator field.
The series motor of Procedures 5 through 11 did not run away because it has
been designed to have its power losses limit maximum speed to a practical
value.
2-13
The Direct Current Motor – Part II
b) Yes. With the exception of the losses mentioned in (a) motor speed varies
directly with armature voltage.
Figure 3-7.
Figure 3-8.
2-14
The Direct Current Motor – Part II
Figure 3-9.
9. a) Method (b).
b) Method (a).
2-15
2-16
Experiment 4
The DC Shunt Motor
DISCUSSION
During this Laboratory Experiment, the student encounters the DC shunt motor. As
its name implies, the field coil and armature windings are connected in shunt or
parallel across the power source. The armature winding consists of relatively few
turns of heavy gauge wire. The voltage across the two windings is the same, but the
armature draws considerably more current than the field coil. Torque or rotation is
caused by the interaction of the current carrying armature winding with the magnetic
field produced by the field coil. Although speed regulation is quite good, the speed
is not precisely constant as is that of the synchronous motor. As the armature
rotates within the magnetic field an EMF is induced in its winding. This EMF is in a
direction to oppose the source EMF and is, therefore, called counter EMF or CEMF.
CEMF varies directly with rotational speed. Current flow through the armature
winding is a result of the difference between source EMF and CEMF, and of course,
speed is a function of armature current. If the load increases, the motor tends to
slow down and less CEMF is induced. The decrease in CEMF permits increased
armature current flow, thus providing more torque for the increased load. Motor
speed is increased by inserting resistance into the field coil circuit which weakens
the magnetic field. Thus, the speed can be increased from “basic” or full-load, full-
field speed to some maximum speed set by the electrical and mechanical limitations
of the motor. Since speed is increased by weakening the field flux, care must be
taken never to open the field circuit of a shunt motor that is running unloaded.
PROCEDURE
E I SPEED TORQUE
(volts) (amps) (r/min) (N·m)
Table 4-1.
2-17
The DC Shunt Motor
E I SPEED TORQUE
(volts) (amps) (r/min) (lbf·in)
Table 4-1.
Figure 4-2.
2-18
The DC Shunt Motor
REVIEW QUESTIONS
1. Pout = 201 W
3. Efficiency = 62.2 %
4. Losses = 122 W
5. Armature and field winding resistances, windage, bearing and brush friction,
rheostat and brush resistance.
6. No. The fan would only help to dissipate the heat generated by the losses.
2-19
The DC Shunt Motor
7. 1- Power is wasted.
8. 5.4 times
2-20
Experiment 5
The DC Series Motor
DISCUSSION
The DC series motor has the field coil and armature windings connected in series
across the power source. Since armature current flows through it, the field coil is
wound with a few turns of heavy gauge wire. Unlike the shunt motor, the field flux
of a series motor varies as the armature current varies. When the series motor is
lightly loaded and very little armature current flows, the field flux is weak, very little
CEMF is induced in the armature winding so the motor speed is quite fast. As the
load increases, armature current and field flux strength increase so the motor speed
is slower. If the load is removed completely, the motor could speed up to the extent
that it would fly apart. Small series motors usually have enough windage and
bearing friction to limit maximum unloaded speed to a safe value. The series DC
motor, in comparison with the shunt DC motor, has high starting torque and poor
speed regulation.
PROCEDURE
E I SPEED TORQUE
(volts) (amps) (r/min) (N·m)
Table 5-1.
2-21
The DC Series Motor
E I SPEED TORQUE
(volts) (amps) (r/min) (lbf·in)
Table 5-1.
Speed and current for 0 N·m torque were measured with the
electrodynamometer disconnected from the series DC motor. Although
Table 5-1, when completed, shows quite plainly how load changes affect
motor speed, another simple demonstration will emphasize the difference
in motor speed between “no-load” and “almost no-load”. With the
electrodynamometer disconnected from the motor, the speed is 5 270 r/min
, limited by windage, bearing friction and brush friction. With
the electrodynamometer connected but adjusted for zero load the speed
drops to about 3 600 r/min . The decrease of 1 670 r/min
is caused by the coupling belt losses and the loading effect of
the electrodynamometer rotor with its windage and bearing friction. This
points up the fact that, as the series DC motor approaches no-load
conditions, the speed increases in very large increments.
2-22
The DC Series Motor
Figure 5-2.
2-23
The DC Series Motor
G 8. b. E = 38 V Torque = 1.56N·m
R = E/I = 38 / 3 = 12.7 S
REVIEW QUESTIONS
1. Pout = 196 W
3. Efficiency = 60 %
4. Losses = 130 W
5. 3.5 times.
2-24
Experiment 6
The DC Compound Motor
DISCUSSION
PROCEDURE
E I SPEED TORQUE
(volts) (amps) (r/min) (N·m)
Table 6-1.
E I SPEED TORQUE
(volts) (amps) (r/min) (lbf·in)
Table 6-1.
2-25
The DC Compound Motor
Figure 6-3.
2-26
The DC Compound Motor
REVIEW QUESTIONS
1. Pout = 159 W
3. Efficiency = 66.3%
4. Losses = 81 W
5. 4.75 times.
6. The shunt winding provides a fairly constant flux field for speed regulation
limiting the no-load speed. The series winding improves the starting
characteristics by increasing torque.
7. a) Starting torque is low for the shunt wound DC motor, and is high for the
series and compound wound motors.
It should be noted that the same physical series winding is used for the
series and compound motors, hence, the compound motor starting torque
is greater than that of the series motor due to the additional torque
contributed by the shunt winding (assuming the two windings are aiding).
Ordinarily, the starting torque of a series motor is greater than that of an
equally rated compound motor.
b) Starting current is approximately 50% greater for the shunt wound motor
than for the series and compound wound motors.
c) Efficiency is about equal for each of the motor types at a full load torque.
d) Speed regulation is relatively good for the shunt motor, poor for the
compound motor and very poor for the series motor.
2-27
2-28
Experiment 7
The DC Separately Excited Shunt Generator
DISCUSSION
PROCEDURE
IF EA
(milliamperes) (volts)
0 13
50 30
100 53
150 78
200 100
250 117
300 129
350 140
400 150
Table 7-1.
2-29
The DC Separately Excited Shunt Generator
f. A weak magnetic field, caused by residual stator flux, exists even when
no excitation voltage is applied. Armature rotation within this field
generates a small voltage.
G 5. c. Yes.
G 6. c. EA = 129 V dc
d. Yes.
G 7. c. Yes.
G 8. c. EA = 129 V dc
d. Yes.
G 10. c. IF = 320 mA
RL IA EA POWER
(ohms) (amps) (volts) (watts)
4 0 132 0
Table 7-2.
G 12. b. Yes.
2-30
The DC Separately Excited Shunt Generator
The motor should start slowing down at about 200 mA and continue to
slow down as excitation current is increased to 600 mA.
REVIEW QUESTIONS
2. Pmin. = 225 W
3. The “bending over” is due to magnetic saturation of the stator core, whereby an
increase in magnetizing current produces a smaller increase in magnetic field
strength. See Figure 7-4.
Figure 7-4
2-31
The DC Separately Excited Shunt Generator
Figure 7-5.
5. Regulation = 10%
2-32
Experiment 8
The DC Self-Excited Shunt Generator
DISCUSSION
The self-excited DC shunt generator provides its own field excitation. The shunt field
is connected to the armature through the commutator so that direct current flows
through the shunt field. This arrangement leaves the self-excited generator
independent of any separate source of DC excitation. However, regulation is poorer
than that of the separately-excited generator because the field current is dependent
on armature voltage. If the generator load increases, output voltage decreases due
to armature reaction and the IR drop across the armature winding resistance. Since
excitation voltage comes from the generator output, a decrease in output voltage
causes a decrease in field current and field flux which, in turn, causes a further
decrease in output voltage. Output voltage can be varied to compensate for load
changes by manually adjusting the field rheostat. However, automatic adjustment
is more convenient and more rapidly responsive to load changes. Such devices as
the Terril regulator, the diactor, and the saturable reactor or magnetic amplifier
provide automatic means of varying field flux inversely with changes in output
voltage.
PROCEDURE
G 4. c. Yes.
e. EA = 160 V dc
G 5. Yes. Varying the rheostat varies the strength of the magnetic field through
which the armature is rotating, thus, varying the voltage induced in the
armature winding.
2-33
The DC Self-Excited Shunt Generator
RL IA EA POWER
(ohms) (amps) (volts) (watts)
4 0 160 0
Table 8-1.
REVIEW QUESTIONS
1. No.
2-34
The DC Self-Excited Shunt Generator
3. Yes.
Figure 8-3.
5. Regulation = 33.3%
The self-excited generator provides its own field flux from the generated output
voltage. If the output voltage varies, the field flux also varies, so a change in
output voltage is magnified by a reduction in field flux, which causes less
voltage to be induced in the armature winding and a further reduction in
generated output voltage.
2-35
2-36
Experiment 9
The DC Compound Generator
DISCUSSION
The compound motor can be connected with the series field flux either aiding or
opposing the shunt field flux. When flux created by the two coils is in the same
direction, the generator is said to be cumulative-compounded. If the series field flux
opposes the shunt field flux, the generator is said to be differential-compounded.
Differential compounding is rarely used, and then only to meet certain special
requirements. Since most compound generators are cumulative-compounded, they
are simply called compound generators. The shunt coil can be connected directly
across the armature (short-shunt) or across the series connected armature and
series coil (long-shunt). There is no appreciable operational difference between the
two methods of connection. The number of turns comprising the series winding
determines the ratio of full-load to no-load output voltage. If the series winding has
many turns, the generator is overcompounded and full-load voltage is greater than
no-load voltage. If, on the other hand, the series winding has few turns, the
generator is undercompounded and full-load voltage is less than no-load voltage.
If the series winding is such that full-load voltage equals no-load voltage, the
generator is said to be flat compounded. The compound generator is used more
than other types because it can be designed to have a wide variety of
characteristics.
PROCEDURE
G 4. c. Yes.
e. EA = 165 V dc
G 5. Yes. The field rheostat controls current through the shunt coil thus
controlling the magnetic field flux which in turn varies the output voltage.
2-37
The DC Compound Generator
RL IA EA POWER
(ohms) (amps) (volts) (watts)
4 0 120 0
Table 9-1.
Figure 9-3.
2-38
The DC Compound Generator
RL IA EA POWER
(ohms) (amps) (volts) (watts)
4 0 120 0
600 0.2 110 22
300 0.3 96 28.8
200 0.38 80 30.4
150 0.4 60 24
120 0.36 45 16.2
100 0.32 35 11.2
80 0.3 25 7.5
75 0.3 23 6.9
Table 9-2.
REVIEW QUESTIONS
1. a) Procedure 10.
b) Procedure 7.
Figure 9-4.
2-39
The DC Compound Generator
3. From 45 V dc to 90 V dc
Figure 9-5.
5. Regulation = 0%
6. The compound generator has the best regulation (0%) and the self-excited
shunt generator has the poorest regulation (33.3%) while the regulation of the
separately excited shunt generator (10%) is about midway between the other
two types.
It should be remembered that the ampere-turns of the series coil is one of the
things that determines the full-load to no-load voltage ratio of a compound
generator. A flat-compounded generator will have zero regulation while over
and under-compounded generators can have varying degrees of regulation.
7. The series field creates more flux so as to maintain a constant output voltage.
2-40
Experiment 10
DC Motor Starter
DISCUSSION
If a DC motor were connected directly to a power line, the armature inrush current
would be 20 to 30 times the normal full-load motor current. Since torque is directly
proportional to armature current, the starting torque could be 30 times normal and
the initial heating of the motor would be 900 times normal. Except for small
machines, neither motor, driven machine, nor power lines would stand this
punishment. The voltage across the motor must therefore be reduced in some way,
and the simplest and most usual method is to connect a resistor in series with the
armature. The resistor should allow more than full-load current to flow, so that the
torque will be sufficient to accelerate the rated load. A usual starting resistor will
allow 150 to 300% of normal full-load current to flow.
Industry often requires that DC motors be started automatically. The same simple
principle used in the manual face-plate starter, of progressively short-circuiting
accelerating (or starting) resistors as the motor comes up to speed, is used. These
automatic starters for DC motors can be classified under two general methods of
acceleration, namely, current-limit acceleration and definite-time acceleration. In the
current-limit starter, sensing relays operate for changing values of armature current
or voltage as the motor accelerates. The relays successively cut-out (short-circuit)
the accelerating resistors.
More modern DC motor starters are the SCR controllers which operate directly off
the AC supply. These controllers accomplish the functions of rectifying the AC
power and of limiting the DC voltage or current available to the load (the DC motor).
The SCR speed control will be studied in a later Laboratory Experiment.
PROCEDURE
G 4. a. IA = 3.4 A dc
b. Time = 0.5 s
d. Yes.
Yes.
e. Time = 1.2 s
2-41
DC Motor Starter
G 5. b. Yes.
Yes.
REVIEW QUESTIONS
1. To provide a maximum starting torque and to reduce the starting period during
which the armature current limiting resistor is in the circuit.
2. Because a 3-point starter protects the motor from overspeeding if the shunt-field
circuit is opened.
3. The circuit breaker in series with the high-wattage resistor would open the
circuit to the motor. If a breaker were not used, the resistor would overheat and
burn.
5. It provides a fixed current through the electromagnet to hold the starter handle
at its maximum CW position.
2-42
Experiment 11
Thyristor Speed Controllers
PROCEDURE
EA IA IF SPEED
(V) (A) (mA) (r/min)
0 0 385 0
10 0.1 385 95
Table 11-1.
G 7. Yes.
G 8. Yes.
2-43
Thyristor Speed Controllers
Table 11-2.
2-44
Thyristor Speed Controllers
1100
1000
900
800
700
Motor Speed (r/min)
600
500
400
300
200
100
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Load (N-m)
Open Loop
Closed Loop without IR Compensation
Closed Loop with IR Compensation
Figure 11-3.
2-45
Thyristor Speed Controllers
1100
1000
900
800
700
Motor Speed (r/min)
600
500
400
300
200
100
0
0 1 2 3 4 5 6 7 8 9 10
Load (lbf-in)
Open Loop
Closed Loop without IR Compensation
Closed Loop with IR Compensation
G 15. Yes.
2-46
Thyristor Speed Controllers
Table 11-3.
G 19. Yes.
2-47
Thyristor Speed Controllers
REVIEW QUESTIONS
4. The armature voltage decreases because the average value of the pulsated
voltage produced by thyristor rectifiers decreases when the current increases.
2-48
Experiment 12
Thyristor Speed Controllers with Regulation
PROCEDURE
Table 12-1.
2-49
Thyristor Speed Controllers with Regulation
G 13. Yes.
G 14. The results are similar. It shows that the closed-loop mode of control
automatically maintains the armature voltage constant.
G 18. Yes.
G 21. Yes.
G 23. Yes.
G 24. Yes.
2-50
Thyristor Speed Controllers with Regulation
LOAD SETTING EA IA IF
SPEED (r/min)
(N@m) (V) (A) (mA)
Table 12-2.
LOAD SETTING EA IA IF
SPEED (r/min)
(lbf@in) (V) (A) (mA)
Table 12-2.
G 28. No.
G 29. Yes.
2-51
Thyristor Speed Controllers with Regulation
REVIEW QUESTIONS
1. The closed-loop system is provided with circuitry that senses the voltage and
current of the motor. It adjusts its output voltage to keep the motor speed
constant.
2-52
Appendix D
SCR Speed Control – Part I
DISCUSSION
PROCEDURE
EA IA I1 SPEED
(volts) (amps) (amps) (r/min)
Table D-1.
e. Late.
Have the students disconnect the DC voltmeter from the circuit prior to
making the high speed test. Although the rated armature voltage is
being exceeded, no harm will be done, if the operating time is kept to
a minimum.
D-1
SCR Speed Control – Part I
f. Yes.
g. Yes.
h. 60 Hz
d. Yes.
d. No.
e. No.
REVIEW QUESTIONS
1. With filtered DC power, the form factor is closer to unity, there is less sparking
at the brushes, less noise and vibration, and less heat generated.
2. With no feedback (open-loop operation) the input DC voltage varies with loading
causing an even greater speed variation than normal.
3. A phase shift of 90E occurs only when a circuit looks like a pure capacitance.
Therefore, there can be no resistance in the circuit and R1 must equal 0 S.
D-2
Appendix E
SCR Speed Control – Part II
DISCUSSION
The triggering or firing angle of the SCR is determined by the DC bias voltage
between its gate and cathode. Since the gate is tied to a fixed DC reference voltage,
the firing angle is determined by the DC cathode voltage level. This DC voltage level
is also the armature voltage, and as its values varies with motor loading, it causes
the SCR to trigger either early (small angle) or late (large angle) thereby causing the
output power of the speed controller to increase or decrease as required.
PROCEDURE
G 2. If time permits, have the students repeat Procedures 3 and 4 with rheostat
R1 set at approximately 3/4 of its full clockwise position. The speed
regulation will improve.
e. Yes.
REVIEW QUESTIONS
E-1
SCR Speed Control – Part II
2. The generated CEMF depends on motor speed. The difference between EA and
CEMF determines IA. If the speed changes, CEMF changes causing IA to
change which, it turn, causes E A to change.
3. The armature tends to slow down, CEMF decreases and armature current
increases causing a drop in the armature supply voltage. This voltage drop is
also between the gate and cathode of the SCR and allows it to fire early in the
AC cycle, thus decreasing the triggering angle and increasing the output power.
4. By lowering the reference voltage, the gate of the SCR is made more negative
with respect to the cathode. It then fires later in the AC cycle increasing the
triggering angle, and decreasing output power, causing the motor to slow down.
E-2
Single-Phase Transformers
and AC Machines
Experiment 0
Safety and the Power Supply
See Experiment 4 of the volume titled Power Circuits (page 1-15 of this manual).
3-1
3-2
Experiment 1
The Single-Phase Transformer
DISCUSSION
All devices which transfer or transform energy lose some power during the process.
The transformer although relatively efficient, consumes power while transferring AC
energy between windings. With no load connected to the secondary, the current
input to the primary winding is about two to five percent of full load current. This no-
load primary current is the exciting current. Most of the exciting current is reactive
and provides the magnetizing flux for transformer operation. However, a small part
of it is in-phase current which supplies the winding and core losses, consisting of
eddy current and hysteresis losses. These losses are undesirable and are kept to
a minimum by good transformer design.
PROCEDURE
G 2. a. terminals 1 to 2 = 120 V ac
terminals 3 to 4 = 208 V ac
terminals 5 to 6 = 120 V ac
b. terminals 3 to 7 = 104 V ac
terminals 7 to 8 = 76 V ac
terminals 8 to 4 = 28 V ac
terminals 3 to 8 = 180 V ac
terminals 7 to 4 = 104 V ac
terminals 5 to 9 = 60 V ac
terminals 9 to 6 = 60 V ac
c. terminals 1 to 2 = 0.5 A ac
terminals 3 to 4 = 0.3 A ac
terminals 5 to 6 = 0.5 A ac
terminals 3 to 7 = 0.3 A ac
terminals 8 to 4 = 0.3 A ac
3-3
The Single-Phase Transformer
G 3. terminals 1 to 2 = 8.2 S
terminals 3 to 4 = 29 S
terminals 3 to 7 = 14 S
terminals 7 to 8 = 10.8 S
terminals 8 to 4 = 4 S
terminals 5 to 6 = 8.5 S
terminals 5 to 9 = 4.2 S
terminals 9 to 6 = 4.5 S
G 4. f. winding 1 to 2 = 120 V ac
winding 3 to 4 = 208 V ac
winding 5 to 6 = 120 V ac
winding 3 to 7 = 104 V ac
winding 7 to 8 = 76 V ac
winding 8 to 4 = 28 V ac
winding 5 to 9 = 60 V ac
winding 9 to 6 = 60 V ac
b. No. The exciting current is relatively small (typically 20 mA) and cannot
be measured using the 500 mA meter.
winding 1 to 2
G 6. a. ' 1
winding 5 to 6
winding 1 to 2
b. = 0.578
winding 3 to 4
G 7. c. I1 = 0.4 A ac
E1 = 10 V ac
I2 = 0.4 A ac
3-4
The Single-Phase Transformer
e. I1 / I2 = 1
G 8. c. I3 = 0.23 A ac
E1 = 7.5 V ac
e. I1 / I3 = 1.74
f. Yes. The inverse of the turns ratio is 1 / 0.578 = 1.74 which equals the
current ratio.
E1 I1 E2
V ac mA ac V ac
25 6 25
50 9.5 50
75 12.5 75
100 16 100
125 21 125
200 81 200
Table 0-1.
3-5
The Single-Phase Transformer
Figure 0-5.
c. No. The voltage ratio depends on the turns ratio, which is fixed and
equal to unity in this case.
REVIEW QUESTIONS
1. I1-2 = 0.5 A ac
2. a) Current ratio is inversely proportional to the voltage ratio and turns ratio.
I7-8 = 0.79 A ac
3. a) winding 1 to 2 = 69.2 V ac
b) winding 5 to 9 = 34.6 V ac
c) winding 7 to 8 = 43.8 V ac
d) winding 5 to 6 = 69.2 V ac
4. Primary winding 1 - 2 draws out of phase exciting current as well as load current
so its I2R losses will be slightly higher than the I2R losses in the secondary
winding 5 - 6.
3-6
The Single-Phase Transformer
I1 = I2 x E1 / E2
= 0.4 x 120 / 10 = 4.8 A ac
the normal value is 0.5 A ac. The short circuit current is 4.8 A ac or
9.6 times greater than normal.
3-7
3-8
Experiment 2
Transformer Polarity
DISCUSSION
Transformers are alternating current devices and their polarity would appear to be
of minor importance. However, when two or more windings are connected together,
the relative instantaneous polarities have a profound effect on the resultant voltage.
If the voltage in one winding is at its positive peak when the voltage in another
winding is at its negative peak, they are opposing and the voltage measured across
the two windings will be the difference between the voltages across the individual
windings. In the United States, the American Standards Association (ASA) and in
Canada, the Canadian Standards Association (CSA) have developed a standard
system of marking transformer leads. High voltage leads are marked H1 and H2 and
low voltage leads are marked X1 and X2. When H1 is instantaneously positive, X1
is also instantaneously positive. Tests similar to that performed in Procedure 3 of
this Laboratory Experiment enable you to determine whether a transformer is
subtractive or additive where the leads are not marked. The H1 lead is always
assumed to be to the left when facing the transformer from the low-voltage side. The
leads of other windings are then marked in relation to the H1 lead.
PROCEDURE
G 1. f. 1 and 3.
h. 1 and 5.
G 2. c. E1 to 2 = 60 V ac
E5 to 6 = 60 V ac
E2 to 6 = 0 V ac
g. E1 to 2 = 60 V ac
E5 to 6 = 60 V ac
E2 to 6 = 120 V ac
i. In Figure 2-3, the windings are connected series opposing (the voltage
in one winding is 180E out of phase with the voltage in the other
winding). Since the two voltages are equal and opposite in phase, they
3-9
Transformer Polarity
cancel each other. In Figure 2-4, the two voltages are in phase with
each other and the output is equal to their sum.
j. 1 and 5, 2 and 6.
G 3. b. E1 to 2 = 60 V ac
e. E2 to 4 = 44 V ac
h. E2 to 3 = 164 V ac E1 to 2 = 60 V ac
j. Yes. With the windings connected series opposing, the net output
voltage is 104 ! 60 = 44 V ac. With the windings connected series
aiding, the output voltage is 104 + 60 = 164 V ac.
k. 1 and 3, 2 and 4.
REVIEW QUESTIONS
Figure 2-1.
b) 208 ! 120 = 88 V ac
3-10
Transformer Polarity
Figure 2-2
c) 120 + 60 = 180 V ac
Figure 2-3.
3-11
Transformer Polarity
d) 120 ! 28 = 92 V ac
Figure 2-4.
3-12
Experiment 3
Transformer Regulation
DISCUSSION
The type of load placed on the secondary winding has a significant effect on
transformer regulation. If the load is resistive, the load current and voltage are in
phase. This reduces the inductive phase angle of the secondary winding voltage
and current, tending to bring them more nearly into phase. The greater the load, the
greater the resistive current and the smaller the phase angle between the secondary
voltage and current. As the resistive load increases, voltage decreases and current
increases.
An inductive load increases the inductive reactance of the secondary circuit. The
voltage and current variations with an inductive load are greater than for a
comparable resistive load.
A capacitive load adds capacitive reactance in series with the inductive reactance
of the secondary winding. The combination forms a series LC circuit. The voltage
induced into the secondary is in series with the inductive reactance of the secondary
winding and the capacitive reactance of the load. The voltages across the reactive
components vary with frequency and component value. Capacitive reactance varies
1
inversely with frequency and capacitance ( XC ' ) so, when the circuit is below
2BfC
resonance, the capacitive reactance is high and the voltage across the capacitive
load is greater than the voltage across the inductive reactance of the secondary
winding. As the capacitive reactance is decreased, the circuit moves toward a
resonant condition and the voltages across the reactances increase until, at
resonance, the two reactances are equal and the reactive voltages are equal and
at maximum.
3-13
Transformer Regulation
PROCEDURE
ZL I2 E2 I1
(ohms) (mA ac) (V ac) (mA ac)
4 0 120 20
Table 3-1.
G 3. a. 9.1 %
ZL I2 E2 I1
(ohms) (mA ac) (V ac) (mA ac)
4 0 120 20
Table 3-2.
3-14
Transformer Regulation
ZL I2 E2 I1
(ohms) (mA ac) (V ac) (mA ac)
4 0 120 20
Table 3-3.
Figure 3-3.
REVIEW QUESTIONS
3-15
Transformer Regulation
2. a) With low internal impedance there will be a low internal voltage drop, so
transformer regulation will be very good.
b) With very little impedance to limit current flow, the short circuit current will
be very high.
4. No. For the same VA load, the capacitor will have more voltage and less current
thus causing the least transformer heating, inductive loading causes greatest
heating.
This can be verified by comparing Tables 3-1 and 3-3. From Table 3-1, when
the resistive load, ZL, is 600 S, the VA load is 0.190 x 117 = 22.23 VA. From
Table 3-3, when the capacitive load, ZL, is 600 S, the voltage is 125 V ac. For
a VA load of 22.23 VA the current through the windings would be only 22.23 /
125 = 178 mA.
3-16
Experiment 4
The Autotransformer
DISCUSSION
PROCEDURE
G 2. d. I1 = 0.25 A ac
I2 = 0.49 A ac
E2 = 58 V ac
b. Yes. The primary and secondary powers are equal when allowance is
made for exciting current losses.
c. Step-down.
G 5. d. I1 = 0.41 A ac
I2 = 0.195 A ac
E2 = 119 V ac
b. Yes. If the transformer efficiency was 100%, the two power values
would be exactly equal.
3-17
The Autotransformer
c. Step-up.
REVIEW QUESTIONS
1. a) IP = VA / EP
= 60 000 / 600 = 100 A
IS = VA / ES
= 60 000 / 120 = 500 A
IS = (EP / ES) x IP
= (600 / 120) x 100 = 500 A
It must be understood that the same value of current does not flow through
the two winding sections. With 720 V output, the load is across the
complete winding but input power is to one section only. Therefore, when
the windings are connected series aiding, part of the power to the load is
due to transformer action and the rest is due to direct conductance from the
source. Figure 4-1a shows the current paths for the 360 kVA load (series
aiding) at the instant when point A is negative. The 360 kVA load, at
720 V ac, draws 360 000 / 720 = 500 A ac of current. The input power is
also 360 kVA but at 600 V ac so the input current is 360 000 / 600 =
600 A ac. At the instant when point A is negative, the 600 A input current
divides at point A with 500 A flowing upward through the 120 V winding to
the load and 100 A flowing downward through the 600 V winding. At point
B the 500 A load current and the 100 A primary current combine and flow
back through the source. The 100 A through the 600 V winding represents
60 kVA which is transferred to the core for transformer action. Therefore,
this section of the winding is the primary with a power input of 60 kVA. The
500 A that flows upward from point A has an increase of potential of 120 V.
The product of 500 A and 120 V is 60 kVA. This section of the winding is
the seconcary with a power output of 60 kVA. This 60 kVA is that portion of
the total load power (360 kVA) which has been transferred by transformer
action. The remainder of the output power is conducted directly from the
3-18
The Autotransformer
source through the upper winding to the load and can be calculated as
P = E x I =600 x 500 = 300 kVA. Total power consumed by the load is the
sum of conducted and transformed power: P total = conducted power +
transformed power = 300 + 60 = 360 kVA.
Figure 4-1a.
When the windings are connected series opposing the transformer action
is subtractive and total power consumed by the load can be calculated as
the difference between conducted power and transformed power:
The load voltage is 600 ! 120 = 480 V (See Figure 4-1 b). Load current is
240 000 / 480 = 500 A. Input power is 240 kVA and, with a 600 V source,
input current is 240 000 / 600 = 400 A. With 400 A as input and 500 A
drawn by the load it must follow that the 100 A through the primary section
adds to the 400 A from the power source to flow upward through the
secondary section to the load. At point B the 500 A from the load separates,
with 100 A flowing up through the primary section and 400 A flowing back
through the source.
3-19
The Autotransformer
Figure 4-1b.
3. a) Primary = 1 to 2
Secondary = 1 to 4
3-20
The Autotransformer
b) Primary = 1 to 2
Secondary = 1 to 4
c) Primary 1 to 2
Secondary 1 to 7
d) Primary = 1 to 2
Secondary = 1 to 8
3-21
3-22
Experiment 5
Transformers in Parallel
DISCUSSION
In an ideal transformer, the power in the secondary is exactly equal to the primary
power. This is true for a transformer with a coefficient of coupling of 1.0 (complete
coupling) and no internal losses. In practice, such a transformer cannot be made.
The degree to which any transformer approaches these ideal conditions is called
the efficiency of the transformer. Mathematically, the efficiency is equal to the output
power divided by the input power. Or,
Since losses reduce the efficiency of a transformer, and therefore represent wasted
power, these losses are usually kept to a minimum. This is especially true in the
design of iron core transformers that must deliver large amounts of power.
b) Stray Losses - Not all of the flux lines produced by the windings travel through
the iron core. Some of the lines stray (leak) from the windings out into space,
and therefore do not link the primary and secondary. This leakage of flux lines
represents wasted energy.
d) Eddy Current Loss - Since the iron core is a conducting material, the
magnetic field of the transformer induces a voltage in the core. This voltage
3-23
Transformers in Parallel
causes currents to flow within the core. These currents are called eddy
currents. Eddy currents can be considered as short circuit currents, in as
much as the only resistance they encounter is the small resistance of the core
material. Like hysteresis losses, eddy currents remove energy from the
transformer windings, and so represent wasted power. Eddy currents can be
reduced by dividing the core into thin laminations, with the laminations
insulated from each other by means of an insulating coating applied to both
sides of each lamination. The eddy currents can then only flow in the
individual laminations, and, since the laminations are thin, the resistance
offered to the eddy currents is greatly increased.
e) Saturation Loss - When the current in the primary winding increases, the
number of flux lines increases. When an additional increase in current
produces only a few additional flux lines in the core, the core is then said to
be saturated. Any further increase in primary current results in wasted power,
since the magnetic field cannot couple the additional power to the secondary.
PROCEDURE
G 5. b. EL = 195 V ac
IL = 0.48 A ac
I1 = 0.24 A ac
I2 = 0.24 A ac
Pin = 100 W
G 7. Yes. The load should be distributed reasonably evenly between the two
transformers because they have identical windings, and thus, they should
share the load equally.
3-24
Transformers in Parallel
REVIEW QUESTIONS
Figure 5-2.
2. A pure capacitive load is reactive, and thus, draws no active power. Efficiency,
(Pout / Pin) has a zero in the numerator so efficiency is zero.
3. Copper (I2R) losses caused by the winding resistances. Core losses caused by
hysteresis and eddy currents in the iron. Dielectric losses in the insulating
materials. Stray losses produced by stray flux.
4. The efficiency of the transformer is better than that of the motors because it is
a static piece of equipment, and therefore does not exhibit the rotational losses
of motors such as windage and bearing friction losses.
3-25
3-26
Experiment 6
The Distribution Transformer
DISCUSSION
When the 120 V loads are balanced on each side of the neutral, the neutral carries
no current. If a heavier load is connected between one of the outside wires and
neutral, the neutral carries the unbalanced current from the transformer to the load.
The current flowing in the neutral wire is always the difference between the currents
in the two outside wires. It is desirable to keep the loads as nearly balanced as
possible to keep the flow of current in the neutral to a minimum.
If the load is connected to only one side of a three-wire system, the neutral carries
the full-load current. For this reason, the neutral is usually of the same size wire as
the two outside lines. An accidental opening of the neutral wire when an unbalanced
load is being supplied results in badly unbalanced voltages across the loads. For
this reason, the neutral is connected solidly from the transformer to the load and no
fuses or other overcurrent devices are installed in the neutral. For further protection
against an open neutral and for protection against damage by lightning, the neutral
wire is connected to ground.
PROCEDURE
3-27
The Distribution Transformer
PROCEDURE R1 R2 I1 I2 IN E1 E2 ET
NUMBER S S mA mA mA V V V
Table 6-1
d. Yes.
h. No. Because these two currents are 90E out of phase with each other,
the neutral line current must be their phasor sum.
2 2
IN ' I1 % I2
' 0.084 % 0.078 ' 0.402 A
The calculated neutral current may differ slightly from the measured
value because the inductive current is not exactly 90E out of phase
(due to its internal winding resistance) plus meter and measurement
errors.
REVIEW QUESTIONS
1. a) Line 1 = 21.83 A ac
Line 2 = 25.5 A ac
The neutral line current is equal to the difference between the two line
currents: = 3.67 A ac
3-28
The Distribution Transformer
b) Line 1 and line 2 would be in series across 240 V. Since line 1 has the
higher resistance, its lamps would see a higher voltage drop and therefore
be brighter.
2. a) I secondary = VA / V secondary
= 60 000 / 240 = 250 A ac
3-29
3-30
Experiment 7
Prime Mover and Torque Measurement
DISCUSSION
The object of this Laboratory Experiment is to familiarize the student with torque
measuring devices. He or she will learn how they operate and how to use them. For
this, the student will be using the split-phase induction motor as a prime mover. He
or she will simply learn how to connect it; the complete study of its characteristics
will be studied in later Laboratory Experiments.
The student will study two types of torque measuring device, the
electrodynamometer and the Prony brake. In the electrodynamometer, the strength
of the stator magnetic field can be increased or decreased by a front panel control.
The strength of the magnetic field determines the degree to which the revolving
rotor is able to cause the stator to change position on its axis. The arc described by
the shifted stator represents torque and is indicated on a scale marked on the
perimeter of the stator housing.
The Prony brake also measures torque. It is essentially a balance which measures
the retarding force caused by a belt running over a friction wheel attached to the
shaft of the machine under test. The measuring scale is calibrated in torque units.
PROCEDURE
G 2. c. I = 3.25 A ac
G 5. b. Yes.
Yes.
G 6. b. Yes.
d. No.
G 10 a. I = 4.4 A ac
3-31
Prime Mover and Torque Measurement
G 13. d. I = 3.25 A ac
REVIEW QUESTIONS
1. By interchanging the lead connections to either the main winding or the auxiliary
winding.
2. P = 181.1 W
The Prony brake requires turning one wheel to vary the torque and another
wheel to bring the balance in equilibrium and to read the torque.
3-32
Experiment 8
The Split-Phase Inductor Motor – Part I
DISCUSSION
PROCEDURE
G 2. c. No. It is physically displaced 45E (90 electrical degrees) from the main
winding. This is a 4-pole motor, so the mid-point between two stator
poles is 45 mechanical degrees.
d. 4 main poles.
e. 4 auxiliary poles.
There are four main stator windings and four auxiliary windings,
therefore, there are four main stator poles and four auxiliary poles.
f. 4-pole motor.
l. 0.4 mm [ ]
3-33
The Split-Phase Inductor Motor – Part I
G 3. d. Higher.
G 4. a. 1 and 2.
b. 3 and 4.
c. 6 and 7.
d. 4 and 5.
c. The larger diameter of the wire used for the main winding offers much
less resistance to current flow than the small diameter wire used for the
auxiliary winding.
REVIEW QUESTIONS
1. 2 poles.
3. The auxiliary winding in conjunction with the main winding, provides a rotating
magnetic field for starting the motor.
3-34
The Split-Phase Inductor Motor – Part I
4. With different values of resistance and inductive reactance, the current phase
angles will be different. The magnetic field strengths will reach maximum at
different times, seeming to rotate. This induces currents in the rotor, causing it
to turn.
5. There would be no phase difference between the two windings, therefore, the
single pulsating magnetic field cannot cause the rotor to start turning.
3-35
3-36
Experiment 9
The Split-Phase Inductor Motor – Part II
DISCUSSION
The induction motor is the most popular motor in use today. This is due to the
comparative simplicity of its construction and operation. Rotor current is induced by
the rotating magnetic field and thus no external rotor connections, such as slip rings
or brushes, are necessary. As the stator magnetic field revolves, its lines of force
cut through the rotor bars, which are low-resistance metallic conductors. Eddy
currents are induced into the rotor bars. These currents flow in a direction to oppose
the motion of the magnetic field (Lenz’s Law: induced current is in such a direction
as to oppose the motion which generates it). However, the force exerted by the rotor
currents against the magnetic field movement is also exerted on the rotor, (Newton’s
third law of motion: for every action there is an equal and opposite reaction). The
rotor shaft is mounted on bearings, so it turns readily and follows the rotating
magnetic field. However, its rotational speed must be less than that of the rotating
magnetic field because there must be relative motion between the rotor and the
magnetic field in order to induce current into the rotor bars and keep the rotor
turning.
PROCEDURE
G 2. c. Yes.
d. No.
G 3. c. Yes.
The rotor will rotate in either direction in the absence of a rotating stator
magnetic field. The motor continues to run because the rotor creates
a magnetic field called a “cross-field” which contributes to an effective
rotating magnetic field.
G 4. d. Yes.
e. No.
G 5. d. Yes.
e. Yes.
f. Clockwise.
3-37
The Split-Phase Inductor Motor – Part II
G 6. c. Counterclockwise.
G 8. b. Yes.
c. Yes.
d. T = 1.0 s
G 10. a. Yes.
b. Yes.
c. Yes.
d. The motor will start, the centrifugal switch will open, the motor will slow
down until the switch closes, then it will speed up again and open the
switch, etc.
The centrifugal switch is in series with the two field windings so, every
time it opens, it interrupts current flow to the windings and the rotor,
with no current being induced in it, starts coasting to a stop. When it
has slowed down to where the centrifugal force can no longer
overcome the tension of the centrifugal switch springs, the switch
closes and restores power to the windings. The rotor then picks up
speed and the switch opens again. This cycle repeats as long as the
power source is on.
REVIEW QUESTIONS
1. No.
2. Yes. The motor will and does run on the main winding after it has come up to
speed. It could run on the auxiliary winding but high current flow through the
comparatively fine wire of the auxiliary winding would soon burn it out.
3-38
The Split-Phase Inductor Motor – Part II
3. By reversing the connecting leads to either the main winding or the auxiliary
winding.
4. The speed necessary for opening the switch contacts would be doubled. Since
the motor cannot reach this speed, the switch would remain closed and the
motor would run on both windings and overheat.
5. The motor started, the centrifugal switch opened and de-energized the
windings. The motor coasted until the switch closed and restored power to the
windings. The motor speeded up and the switch opened again.
6. No. The same current would flow through both windings. There would be no
phase shift and consequently no rotating magnetic field to cause the rotor to
turn.
7. No.
3-39
3-40
Experiment 10
The Split-Phase Inductor Motor – Part III
DISCUSSION
Once the split-phase induction motor is started and running, it develops torque
because of the action of the crossfield set up by the rotor. As the rotor revolves,
voltages are induced in the rotor bars because they are conductors cutting through
magnetic lines of force. These voltages are in phase with the stator magnetizing
current (this can be verified by applying Fleming’s Right Hand Rule). The induced
rotor voltages cause rotor current to flow. The impedance to rotor current flow is
almost entirely reactive, so the current will lag the voltage by nearly 90E. These rotor
currents set up a magnetic field, known as a crossfield which is displaced 90E from
the field set up by the stator winding. Thus, the effect of the magnetizing current set
up in the rotor is to produce a revolving magnetic field. The strength of the crossfield
is almost equal to that of the stator field at synchronous speed and becomes weaker
as speed is reduced.
PROCEDURE
G 2. Imain winding = 15 A ac
G 3. b. Iauxiliary winding = 12 A ac
G 4. e. Istarting = 25 A ac
E I P SPEED
VIBRATION
(volts) (amps) (watts) (r/min)
Table 10-1
3-41
The Split-Phase Inductor Motor – Part III
Table 10-2
REVIEW QUESTIONS
3-42
The Split-Phase Inductor Motor – Part III
3. I = 4.75 A ac
4. 5.3 times
5. Since it has less reactance XL (fewer turns) it carries almost as much current,
therefore, its I2R losses (finer wire) are greater.
6. No.
7. 1.25 times
3-43
3-44
Experiment 11
The Capacitor-Start Motor
DISCUSSION
PROCEDURE
G 2. Imain winding = 15 A ac
G 3. b. Iauxiliary winding = 8 A ac
G 4. e. Istarting = 16 A ac
It should be noted that the initial current surge is less for the capacitor-
start motor than for the split-phase motor. The capacitor acts to limit it
to a lower value.
G 5. a. The main winding is the same for both motors, so the main winding
current values are the same.
c. With less auxiliary winding current and a much greater current phase
shift, the starting current of the capacitor-start motor is lower.
3-45
The Capacitor-Start Motor
Table 11-1.
REVIEW QUESTIONS
3-46
The Capacitor-Start Motor
3. I = 4.75 A ac
4. 3.4 times .
5. The starting current of the capacitor-start motor is smaller but the starting torque
is greater. This is due to the greater phase angle between the winding currents.
The running characteristics are the same because the main windings are the
same.
3-47
3-48
Experiment 12
The Capacitor-Run Motor
DISCUSSION
The capacitor-run motor provides a number of advantages over the regular split-
phase and capacitor-start types of induction motors. The presence of the capacitor
in series with the second stator winding, thus, sets up a part or all of the crossfield,
which, without the second winding, is set up by the rotor currents. This reduces or
eliminates the magnetizing currents in the rotor and the accompanying copper
losses, thus increasing the efficiency of the motor. At full load the torque is relatively
constant instead of pulsating at 120 Hz, therefore, the capacitor-run motor operates
with less vibration and noise, and a higher power factor than the other two motor
types.
PROCEDURE
G 2. b. Yes.
c. No. One winding is displaced from the other by an angle of 45E (90
electrical degrees).
e. 4-pole.
G 4. b. 1 and 2.
c. 3 and 4.
e. 5 and 6.
3-49
The Capacitor-Run Motor
Table 12-1.
d. Yes.
Starting Current = 8 A ac
REVIEW QUESTIONS
3-50
The Capacitor-Run Motor
3. I = 3.1 A ac
4. 2.6 times .
5. The capacitor-run motor has a higher power factor, less starting torque. It is
more efficient and runs more smoothly at full-load than the other types.
6. By interchanging the connection leads on either one of the two identical stator
field windings.
7. Electrolytic capacitors have a high leakage factor and are unreliable for
continuous duty in high current applications. Oil-filled capacitors are much more
reliable and are less “lossy”.
3-51
3-52
Experiment 13
The Universal Motor – Part I
DISCUSSION
If the series DC motor were connected to a source of 120 V ac it would start and
run, but not as well as with a DC voltage source. The reason for this is that factors
which have no effect on DC operation become significant during AC operation. The
inductive reactance of the series field coil limits motor current to a comparatively low
value. Consequently, the power developed is small. The solid iron field poles
produce hysteresis and eddy current losses due to stator flux alternations.
Commutation is poorer and brush life is reduced because of transformer action
between the main field windings and the short-circuited coils undergoing
commutation. The universal motor is a modification of the series DC motor. It
reduces the limiting factors and operates well on AC or DC.
PROCEDURE
G 4. a. 3 and 4.
b. 5 and 6.
c. 1 and 2.
G 8. b. Note to the Instructor: If any of the universal motors have adjusted neutral
positions which do not coincide with the mark on the housing, have the students
mark the new neutral positions.
G 10 c. I = 3.5 A ac
Table 13-1.
3-53
The Universal Motor – Part I
Table 13-2.
3-54
The Universal Motor – Part I
REVIEW QUESTIONS
3. a) power = 204 W
4. a) power = 384 W
5. When operated on DC: the efficiency is higher, the delivered power is higher,
the speed is higher but the input current is lower.
3-55
3-56
Experiment 14
The Universal Motor – Part II
DISCUSSION
To reduce losses due to hysteresis and eddy currents, the field structure (the stator
in the Lab-Volt universal motor), instead of being solid, is laminated. Few universal
motors operate at the same speed on AC as on DC. Whether it runs faster on AC
or DC is a matter of design. As noted in the previous Laboratory Experiment, this
particular universal motor runs faster when operated from a DC power source.
PROCEDURE
G 3. b. I = 3.7 A dc
G 5. b. I = 1.4 A ac
G 6. The inductive reactance of the armature and field windings limits field
current during AC operation. This reduces the AC starting torque
considerably below the DC starting torque.
3-57
The Universal Motor – Part II
G 8. d. I = 2.3 A ac
G 9. a. The current is about the same but the speed is much slower. Without
the compensating winding the motor produces less power and there is
more sparking at the brushes.
b. Yes.
G 11. I = 2.4 A dc
b. Yes.
G 13. e. I = 3.25 A ac
f. Yes.
h. As soon as the short was removed the motor stalled, since it cannot
develop full power when it is uncompensated.
G 14. b. I = 3.9 A dc
c. No.
G 15. No. Inductive compensation is effective only when the current is alternating.
The DC performance is the same with the compensating winding shorted
as when it is open. On DC, the motor draws more current and there is
severe sparking at the brushes.
3-58
The Universal Motor – Part II
REVIEW QUESTIONS
5. Small fans and blowers, hair dryers, electric shavers, electric hair clippers, can
openers, sewing machines, vibrators, coffee grinders, power screwdrivers,
nutdrivers, sabre saws, hedge clippers.
3-59
Three-Phase Transformers
and AC Machines
Experiment 0
Safety and the Power Supply
See Experiment 4 of the volume titled Power Circuits (page 1-15 of this manual).
4-1
4-2
Experiment 1
Three-Phase Transformer Connections
DISCUSSION
In the wye-wye connection only 57.7 % of the line voltage is impressed upon each
winding, but full line current flows in each transformer winding. The wye-wye
connection is seldom used.
The delta-wye connection is well adapted for stepping up voltages since the voltage
is increased by the transformer ratio multiplied by the factor 3 . The wye-delta
connection can be used for stepping down voltages. The high-voltage windings of
most transformers are wye-connected.
PROCEDURE
G 1. a. Wye-wye.
Table 1-1-A.
4-3
Three-Phase Transformer Connections
G 2. a. Delta-wye.
E1 = 90 V, E2 = 90 V, E3 = 90 V E1 = 89 V, E2 = 90 V, E3 = 90 V
E7 = 90 V, E8 = 90 V, E9 = 90 V E7 = 89 V, E8 = 90 V, E9 = 90 V
Table 1-1-B.
G 3. a. Wye-delta.
Table 1-1-C.
G 4. a. Delta-delta.
Table 1-1-D.
4-4
Three-Phase Transformer Connections
Table 1-1-E.
REVIEW QUESTIONS
1. a) No.
Open-Delta: VA maximum = 3 x E x I.
Delta-Delta: VA maximum = 3 x E x I
c) No. In practice, even with a balanced load, the secondary voltages become
unbalanced under load due to the voltage drop across the two secondary
windings.
2. a) Wye-wye: The total capacity would be the sum of each of the three
transformer capacities.
b) Wye-delta: The total capacity would be the sum of each of the three
transformer capacities.
4-5
Three-Phase Transformer Connections
c) Delta-wye: The total capacity would be the sum of each of the three
transformer capacities.
3. a) No.
b) No.
c) No.
d) Yes. The secondary voltages and also the phase angles would become
unbalanced.
4. a) Yes.
b) Yes.
c) No.
d) No. The secondary voltages would not become unbalanced, but they would
probably drop in value due to the heavy load on the power source.
4-6
Experiment 2
Prime Mover and Torque Measurement
DISCUSSION
The object of this Laboratory Experiment is to familiarize the student with torque
measuring devices. He or she will learn how they operate and how to use them. For
this, the student will be using the shunt-wound DC motor as a prime mover. He or
she will simply learn how to connect it; the DC shunt motor will be used as a driver
in later Laboratory Experiments.
The student will study two types of torque measuring device, the
electrodynamometer and the Prony brake. In the electrodynamometer, the strength
of the stator magnetic field can be increased or decreased by a front panel control.
The strength of the magnetic field determines the degree to which the revolving
rotor is able to cause the stator to change position on its axis. The arc described by
the shifted stator represents torque and is indicated on a scale marked on the
perimeter of the stator housing.
The Prony brake also measures torque. It is essentially a balance which measures
the retarding force caused by a belt running over a friction wheel attached to the
shaft of the machine under test. The measuring scale is calibrated in torque units.
PROCEDURE
d. I = 0.5 A dc
G 6. b. Yes.
Yes.
G 7. b. Yes.
d. No.
4-7
Prime Mover and Torque Measurement
REVIEW QUESTIONS
1. By interchanging the lead connections to either the shunt field winding or the
armature winding.
2. P = 173 W
The Prony brake requires turning one wheel to vary the torque and another
wheel to bring the scale in equilibrium and to read the torque.
4-8
Experiment 3
The Wound-Rotor Induction Motor – Part I
DISCUSSION
The squirrel-cage rotor is a self-contained unit with a series of straight bars around
the periphery that are permanently short-circuited at both ends by rings. It has no
electrical or mechanical connection with the electrical supply source or the control
circuit. Its resistance is fixed, thus providing fixed full-load operating speed, starting
torque, and rate of acceleration characteristics.
The wound-rotor construction differs from that of the squirrel-cage in that it is wound
with insulated windings similar to the stator winding. This three-phase winding is
wye-connected with the open ends of each phase winding being connected via
three slip rings, and brushes, to three external variable resistors. Varying the
resistance produces variation in speed and torque.
In this Laboratory Experiment, the students will measure the voltages induced in the
rotor windings by the revolving stator magnetic field.
PROCEDURE
G 2. b. No.
b. 1.5 A ac
c. 120 V ac
d. Wye.
e. 7, 8 and 9.
f. 60 V ac
g. 2 A ac
Power = 175 W
4-9
The Wound-Rotor Induction Motor – Part I
E2 = 100 V ac
b. Active power = 60 W
E2 = 154 V ac
c. Yes.
E2 = 208 V ac
d. Against. The induced rotor voltage increases as the rotor spins faster.
This occurs because the rate at which the magnetic flux of the rotating
stator field cuts the rotor windings increases.
E2 = 52 V ac
E2 = 0 V ac
4-10
The Wound-Rotor Induction Motor – Part I
d. With. The induced rotor voltage decreases as the rotor spins faster.
This occurs because the rate at which the magnetic flux of the rotating
stator field cuts the rotor windings decreases.
REVIEW QUESTIONS
2. 4 poles
Rotor rotation in the same direction as that of the rotating stator field is called
positive (+), and rotor rotation in the opposite direction to that of the rotating
stator field is called negative (!). Therefore, the rotor speeds in 8 and 9 are
negative values.
slip (11) = 0 %
5. No.
6. The power needed to produce the magnetic field is reactive. (See Procedure
7. d)
Q = 225 var
P = 60 W
4-11
The Wound-Rotor Induction Motor – Part I
8. Yes (within the meter and measurement tolerances). See Figure 3-2.
Figure 3-2.
4-12
Experiment 4
The Wound-Rotor Induction Motor – Part II
DISCUSSION
If the rotor windings are short-circuited, by reducing their external series resistance
to zero, the wound-rotor then behaves like the squirrel-cage rotor with its
permanently shorted conducting bars. As shown in the previous Laboratory
Experiment, three-phase voltages are induced in the rotor windings by the rotating
magnetic field produced by the three-phase stator current. These induced voltages
cause high currents to circulate in the rotor windings (or rotor bars in the squirrel-
cage rotor). The circulating rotor currents then produce their own strong magnetic
fields. These local rotor flux fields produce their own magnetic poles, which are
attracted to the rotating stator field. Thus, the rotor revolves with the rotating stator
field. In this Laboratory Experiment, the students will measure these circulating rotor
currents and their relationship to the stator current and developed motor torque.
PROCEDURE
c. Yes.
G 4. b. Yes.
G 6. a. I1 = 3.4 A ac I2 = 6 A ac
REVIEW QUESTIONS
4-13
The Wound-Rotor Induction Motor – Part II
4. If time permits, have the students verify their answers by performing Procedure
6 using the variable 3 phase output of the power supply, terminals 4, 5 and 6,
adjusted for an E1 of 100 V.
The students can compare their answers with the results of Procedure 3.
Reduction = 75 %
c) Torque is proportional to both stator and rotor magnetic field strengths. With
1/2 of the currents the field strength is reduced to 1/4 of the original.
Reduction = 75 %
4-14
Experiment 5
The Wound-Rotor Induction Motor – Part III
DISCUSSION
Varying the resistance in the rotor circuit produces variations in operating speed as
much as 75 %; the greater the resistance inserted in the rotor circuit, the lower the
speed below synchronous speed. When the resistance is adjusted to its lowest
value, the speed is less than that obtained with squirrel-cage motors. This is due to
the internal resistance of the rotor windings, which is appreciably higher than that
of the shorted rotor bars in the squirrel-cage.
PROCEDURE
TORQUE I1 I2 I3 W1 W2 SPEED
(N·m) (amps) (amps) (amps) (watts) (watts) (r/min)
Table 5-1.
TORQUE I1 I2 I3 W1 W2 SPEED
(lbf·in) (amps) (amps) (amps) (watts) (watts) (r/min)
4-15
The Wound-Rotor Induction Motor – Part III
TORQUE I1 I2 I3 W1 W2 SPEED
(N·m) (amps) (amps) (amps) (watts) (watts) (r/min)
Table 5-2.
TORQUE I1 I2 I3 W1 W2 SPEED
(lbf·in) (amps) (amps) (amps) (watts) (watts) (r/min)
12 Motor stalls
Note to the Instructor: Due to the winding and rheostat resistance tolerances,
some of the wound-rotor motors may stall while operating in an overload
condition at low speed.
e. Yes.
f. Yes.
G 8. c. Note to the Instructor: The stator and rotor currents may be measured with
greater accuracy by changing both meters to the 2.5 A ac range.
4-16
The Wound-Rotor Induction Motor – Part III
REVIEW QUESTIONS
c) active power = 72 W
g) efficiency = 56.3%
g) efficiency = 33.6%
4-17
The Wound-Rotor Induction Motor – Part III
5. The input power supplies not only the actual output power plus the iron, copper,
windage, and friction losses, but also the power dissipated by the external
resistances.
6. As loading increases, the motor delivers more power, so the active input power
increases proportionately. However, the reactive power required for the
magnetic field remains relatively constant.
4-18
Experiment 6
The Squirrel-Cage Induction Motor
DISCUSSION
Unlike the wound-rotor motor with its poor speed regulation under load, the low
impedance rotor of the squirrel-cage motor provides good speed regulation. Since
the squirrel-cage rotor impedance is low, a small decrease in speed (increase in
slip) produces a large increase in rotor current. For this reason the speed regulation
of the squirrel-cage motor is good, the full-load slip being approximately 7 %. The
starting torque of the squirrel-cage motor is lower than that of the wound-rotor motor
because at rest the low impedance rotor with its relatively large inductance to
resistance ratio, has high induced currents that lag the induced voltage by 90E. As
the rotor begins to turn and pick up speed, the slip decreases, the frequency of the
induced voltage decreases, the rotor reactance decreases, the power factor
increases, and the motor efficiency increases. When the slip drops to some value
between 2 and 10 percent, depending on the load, the speed stabilizes and remains
relatively constant.
PROCEDURE
G 2. e. No.
b. 1.5 A ac
c. 120 V ac
Power = 175 W,
4-19
The Squirrel-Cage Induction Motor
TORQUE I1 I2 I3 W1 W2 SPEED
(N·m) (amps) (amps) (amps) (watts) (watts) (r/min)
Table 6-1.
TORQUE I1 I2 I3 W1 W2 SPEED
(lbf·in) (amps) (amps) (amps) (watts) (watts) (r/min)
REVIEW QUESTIONS
c) active power = 60 W
4-20
The Squirrel-Cage Induction Motor
g) efficiency = 59%
4. The squirrel-cage motor: is more efficient, has higher full-load speed and has
better speed regulation. The wound-rotor motor: has higher starting torque,
lower starting current, and its speed can be varied.
5. Its rotor construction is simple and very rugged, and cannot be burned out. The
absence of commutator, brushes, and slip rings eliminates any possible
troubles or need for maintenance of these items.
4-21
4-22
Experiment 7
The Synchronous Motor – Part I
DISCUSSION
PROCEDURE
G 2. b. No.
b. 120 V ac
c. 1 A ac
d. 7 and 8.
e. 120 V dc
Power = 175 W
4-23
The Synchronous Motor – Part I
G 8. b. The motor will not start under load. It vibrates, growls, and chatters
heavily.
d. No.
G 9. c. The motor starts smoothly under load. The starting current is 4.5 A. The
running current fluctuates at approximately 1 A.
d. Yes.
g. Yes.
G 12. The rate at which the rotating magnetic field cuts the rotor windings
decreases.
REVIEW QUESTIONS
2. No.
3. a. The resistance partially shorts the rotor windings, preventing excessive high
voltage build-up.
b. The AC rotor current that flows, aids the rotating stator field producing extra
torque.
4. With approximately the same starting current, the synchronous motor has
greater torque due to its higher rotor winding resistance.
4-24
Experiment 8
The Synchronous Motor – Part II
DISCUSSION
Where many transformers and induction motors are used, for example, in large
industrial plants, the currents drawn tend to lag the impressed voltage, as is
common with inductive circuits. The greater the lag, the poorer the power factor. We
can improve the power factor by adding capacitance to the load circuits. It thus
becomes practical to replace the induction motors in some of the plant machinery
with synchronous motors, which help improve the power factor while furnishing
useful mechanical power. A synchronous motor used in this way is often said to be
operating as a synchronous capacitor.
PROCEDURE
W1 = 25 W W2 = 25 W
4-25
The Synchronous Motor – Part II
I2 E1 I1 POWER POWER
W1 W2 PF
(amps) (volts) (amps) (VA) (watts)
Table 8-1.
Note to the Instructor: Due to line voltage, power supply and motor winding
tolerances, many students may not be able to increase the DC excitation current to
the 0.9 A level. This is of no consequence, as the Table contains more than enough
information to allow the characteristic “V” motor curves to be plotted as shown in
Figure 8-2.
Also if the line voltage is higher or lower than 208 V ac at the fixed output of the
power supply, the characteristic “V” motor curves should shift respectively right or
left in Figure 8-2. This is due to the fact that at a higher line voltage the rotor has to
supply more var to induce the line voltage and then a higher current must flow into
the rotor windings. The opposite is true for a lower line voltage.
(Remember that at PF = 100%, all the reactive power is supplied by the rotor.)
4-26
The Synchronous Motor – Part II
Figure 8-2
G 5. a. Q = 280 var
b. Lagging.
G 6. a. Q = 236 var
b. Leading.
G 7. Q = 6.34 var
REVIEW QUESTIONS
2. By over-exciting the rotor, it will have a leading power factor just like a
capacitor, and can be used to correct a lagging power factor line condition.
4-27
The Synchronous Motor – Part II
3. Yes.
4. This power supplies only the copper, iron, friction, and windage losses. Since
the speed is constant only the copper losses will vary because of the
changing stator currents.
4-28
Experiment 9
The Synchronous Motor – Part III
DISCUSSION
The most important advantage of the synchronous motor is its constant speed under
varying load conditions. Another important advantage is its ability to operate, even
under full-load conditions, at a lagging or leading power factor that can be readily
adjusted simply by changing the DC excitation supplied to the rotor. As the DC
excitation is increased, the motor tends to draw a more leading current, while the
current lags more as the excitation is reduced.
Usually the synchronous motor is used for the dual purpose of delivering a
mechanical load and correcting an otherwise low lagging power factor. This is true
in systems that must supply power to a considerable number of induction motors.
In such plants, it is frequently advantageous to install a synchronous motor to raise
the power factor to a suitable value and at the same time to have it drive some
constant speed continuous-duty load.
PROCEDURE
G 3. c. I1 = 0.84 A ac , I2 = 0.5 A dc ,
E1 = 208 V ac E2 = 140 V dc
E2 = 125 V dc W1 = 151 W ,
W2 = 151 W
b. I1 = 1.12 A ac , I2 = 0.8 A dc
E1 = 208 V ac E2 = 140 V dc
W1 = 221 W W2 = 103 W
4-29
The Synchronous Motor – Part III
c. With an overexcited rotor creating more magnetic field than the motor
needs, the power line supplies negative reactive power to the stator to
keep the total magnetic flux constant.
d. Leading.
REVIEW QUESTIONS
e) DC power = 62.5 W
g) efficiency = 57%
e) DC power = 112 W
4-30
The Synchronous Motor – Part III
4-31
4-32
Experiment 10
The Three-Phase Alternator
DISCUSSION
DC and AC generators are similar in one important aspect – they both generate
alternating EMF. In the DC generator, the alternating voltage is rectified through the
medium of a commutator and brushes, where the AC generator has no rectifier and
delivers AC electricity energy to its loads.
AC generators are usually called alternators. But unlike DC generators, they must
be driven at a constant speed because the frequency of the generated EMF is
determined by that speed. The latter is usually referred to as the synchronous
speed, for which reason these machines are frequently called synchronous
alternators or synchronous generators. Remembering that generator action
depends upon the relative motion of conductors with respect to lines of force, it
should be clear that it is possible to construct an alternator with a stationary field
and a moving armature or with a stationary armature and a moving field. In practice,
the latter arrangement is the preferable one.
PROCEDURE
c. There is some residual magnetism in the rotor, so some flux cuts the
stator windings, generating a small voltage.
I1 E1 E2 E3 Eac
(amps) (volts) (volts) (volts) (avg.)
0 9 7.5 8 8.2
0.1 58 52 55 55
0.2 105 100 103 103
0.3 142 138 140 140
0.4 175 170 175 173
0.5 198 192 195 195
0.6 212 208 210 210
0.7 225 220 220 222
0.8 235 230 230 232
0.9 245 238 240 241
4-33
The Three-Phase Alternator
Table 10-1
E3 to 6 = 120 V ac
f. Yes.
G 8. c. I1 = 0.48 A dc
e. I2 = 1.8 A ac
REVIEW QUESTIONS
c) E = 200 V ac
d) E = 200 V ac
e) As the DC rotor current increases to 0.6 A, the iron in the rotor begins to
saturate. Therefore, as excitation current increases above this value, there
will be a smaller increase in the magnetic flux and the generated voltage.
4-34
The Three-Phase Alternator
Figure 10-3
4-35
4-36
Experiment 11
The Alternator Under Load
DISCUSSION
PROCEDURE
f. Regulation = 7.2 %
f. Regulation = 16.8 %
g. Opposes.
f. Regulation = -32.7 %
g. Aid.
4-37
The Alternator Under Load
G 6. c. The output voltage increased to 234 V while the load current increased
from 0.1 A to 0.32 A.
d. The output voltage increased to over 250 V while the output current
increases to 0.9 A.
f. Due to capacitive loading, the stator winding currents lead the output
voltage by 90E and create an increase in the MMF, increasing the
magnetic flux which in turn increases the output voltage.
f. E1 to 4 = 118 V ac
E2 to 5 = 110 V ac
E3 to 6 = 123 V ac
h. Yes. The effect of this unbalance would cause: large return currents in
neutral wires, unbalanced three-phase currents in motors, floating
neutral points in WYE connected loads, and large circulating currents
in DELTA connected transformers.
REVIEW QUESTIONS
1. In addition to the explanation given in Procedure 6. f), the voltage drop across
the winding reactances is such that it adds vectorially to the generated voltage
so that the output voltage rises with a capacitive load.
2. Yes. The output voltage could raise to a dangerous level, sufficient to break
down the winding insulation and damage the alternator. Associated switches
and breakers could also be damaged.
3. With a high power factor, DC rotor excitation is minimum. A lagging power factor
load tends to reduce the stator magnetic field, thus the DC excitation has to be
increased to maintain the rated output voltage.
4-38
Experiment 12
Alternator Synchronization
PROCEDURE
G 3. b. E2 = 208 V ac
G 4. b. Note to the Instructor: If the lights flash in sequence instead of all together,
it indicates that the phase sequence of the three power supply terminals and
that of the alternator are different.
G 5. a. The stator current jumps quickly to 0.3 A and then returns to zero.
Note to the Instructor: The line current I1 will probably jump quickly and then
return to almost zero. The jump or current surge occurs because the two line
voltages are usually not completely equal and in phase with each other.
b. The stator current jumps quickly to 1.2 A and then returns to zero.
Note to the Instructor: When the lights are dim, there is a small phase
difference between the two voltages, which creates a greater voltage difference
than when the lights are dark. Therefore, the current I1 will surge to a higher
value than in part (a).
If the lights are partially bright when the switch is closed, there is a
relatively large phase difference between the two voltages. This
produces a large voltage difference, which creates a larger surge
current than in part (b). The alternator will also jerk, as the rotor is
forced into the correct position by the large stator surge currents. After
the surge, the current will again drop back to almost zero.
d. The phase sequence of the power company and that of the alternator
are different.
f. By interchanging any two of the leads coming from the stator of the
alternator.
4-39
Alternator Synchronization
REVIEW QUESTIONS
1. The frequency, phase, and phase sequence, as well as the voltage amplitudes
must be equal to each other.
When the phase sequence is wrong, and the alternator is joined to the
existing supply, it immediately tries to reverse its direction and run as a
motor in the opposite direction, against the rotation of the driving motor.
This occurs because the power line sets up a rotating magnetic field in the
alternator which tries to make the alternator run as a synchronous motor in
the reverse direction. This cause very large currents in the stator, overloads
and tries to stall the driving motor, and generates very large voltages in the
rotor of the alternator. The resulting electrical overloads and mechanical
shocks can damage both the alternator and the driving motor.
3. Both frequencies must be the same in order for the alternator to deliver power.
4-40
Experiment 13
Alternator Power
PROCEDURE
G 4. a. W1 = -25 W, W2 = 25 W
Note to the Instructor: If the DC excitation current exceeds 0.5 A dc, have the
students change to the 2.5 A dc meter range.
d. Reactive.
With the rotor overexcited, the alternator draws leading reactive power
from the infinite bus.
G 6. a. W1 = -25 W, W2 = 25 W
Active power = 0 W
d. Reactive.
With the rotor underexcited, the alternator draws lagging reactive power
from the infinite bus.
4-41
Alternator Power
G 8. a. W1 = 55 W, W2 = 30 W
Active power = 85 W
d. Active.
G 10. a. W1 = 0 W, W2 = 60 W
E1 = 208 V ac
b. W1 = 60 W, W2 = 0 W
E1 = 208 V ac
G 11. W1 = -25 W, W2 = 25 W
E1 = 210 V ac
G 12. W1 = 25 W, W2 = -25 W
E1 = 212 V ac
REVIEW QUESTIONS
1. a) Decrease.
b) Increase.
2. Alternator output = 94 kW
4-42
Alternator Power
4. The existing infinite bus voltage sets up a rotating magnetic field in the stator of
the alternator, and the speed of this rotating field is fixed by the system
frequency. This field forces the rotor to turn at the infinite bus synchronous
speed.
4-43
4-44
Experiment 14
Three-Phase Motor Starter
DISCUSSION
In industry, motor starters very often use an overload relay on only two of the phase
conductors but recent tendency is towards using three separate overload relays,
each with a normally-closed contact, or a single overload relay with three sensing
elements as supplied with the starters used in this Laboratory Experiment.
Some types of overload relays are also available with the manual reset or automatic
reset characteristic. The automatic reset type returns to its normal position a period
of time after the relay has tripped. In the manual reset type, the reset button must
be pressed to reset the starter to its normal position.
PROCEDURE
G 1. I = 1 A ac
G 5. a. E = 208 V ac
b. No.
c. No.
e. Yes.
Yes.
f. I = 0.73 A ac
g. The stop button opens the circuits to the contactor coil which opens
contacts M and disconnects the motor from the power source.
h. t = 108 s
j. Note to the Instructor: If the overload relay is of the automatic reset type,
there is no necessity for pressing the reset button.
n. I = 4.5 A ac t = 15 s
G 6. b. I = 1 A ac
c. E = 120 V dc I = 0.4 A dc
4-45
Three-Phase Motor Starter
G 7. a. Yes.
G 9. a. E = 208 V ac
b. No.
c. No.
e. The “Motor Synchronized” lamp will come on very briefly and will stay
off.
f. The lamp comes on very briefly and stays off thereafter until the motor
is locked into synchronism by the starter. Then it comes back on.
g. I = 0.3 A ac
h. The stop button opens the circuit to the contactor coil which opens
contacts M and disconnects the motor from the power source.
j. t = 138 s
G 10. a. Note to the Instructor: If the overload relay is of the automatic reset type,
there is no necessity for pressing the reset button.
e. I = 3.9 A ac t = 11 s
When the motor falls out of synchronism, it rapidly comes to a halt and
the line current increases. The current sensing relay opens the circuit
to the contactor coil and disconnect the motor from the source.
REVIEW QUESTION
2. The motor did not reach the speed at which the current sensing device
energizes the excitation field and completes the self-holding circuit of the
contactor coil.
3. The inverse-time curve of the overload relay makes it trip faster on higher
current.
4-46
Three-Phase Motor Starter
4. This would have represented a heavier overload and the overload relay would
have tripped faster.
4-47
4-48
Experiment 15
Frequency Conversion
PROCEDURE
W1 = -57 W, W2 = 105 W
W1 = 50 W, W2 = 200 W
Note to the Instructor: Have the students re-adjust the DC excitation of the
synchronous motor so that I3 is at its minimum value. This procedure should be
followed whenever the synchronous motor is operated or has its loading
changed.
The active power delivered to the stator (250 W) includes the active
power lost in the motor due to its iron and copper losses, windage and
friction. This power (48 W) is essentially the no-load power found in
Procedure 3. e.
Note to the Instructor: The fact that mechanical power is being supplied by
the synchronous motor can be verified by noting that its input stator current
increases as the power output of the wound rotor increases.
4-49
Frequency Conversion
REVIEW QUESTIONS
1. The squirrel cage motor speed is slightly less than twice the 60 Hz synchronous
speed of 1800 r/min, because it receives 120 Hz power from the rotor of the
frequency converter.
2. If the wound rotor were turning at 900 r/min in the same direction as the rotating
stator magnetic field, a frequency of 30 Hz would be generated. If it were
revolving at 900 r/min opposite to the direction of the rotating field, a frequency
of 90 Hz would be generated.
b) If the squirrel cage motor turns the rotor at 3600 r/min in the same direction
as the rotating stator magnetic field, the field will then cut the rotor windings
at 2400 r/min, and a frequency of 120 Hz will be generated.
Actually there will be some slip due to the squirrel-cage motor and both
frequencies will be slightly lower.
4-50
Experiment 16
Reactance and Frequency
PROCEDURE
G 3. a. R = E1 / IR = 302 S
XC = E1 / IC = 306 S
XL = E1 / IL = 310 S
b. Yes. The calculated values and the listed values should agree within
component and meter tolerances.
G 9. a. R = E1 / IR = 300 S
XC = E1 / IC = 153 S
XL = E1 / IL = 625 S
b. The 120 Hz value of the resistance load should be the same as the
60 Hz value (within measurement error) but the 120 Hz reactance value
of the inductance load will be about twice the 60 Hz value, and the
120 Hz reactance value of the capacitance load will be about one-half
of the 60 Hz value.
Note to the Instructor: Remember, that the current values found in Procedure
8. e) are dependent on the exact setting of the power supply voltage. Any error
in the voltage setting or in the voltmeter itself will cause the current values to be
in error. The current meter accuracy and component value tolerances plus
measuring errors will introduce further errors in the calculations. Therefore,
when comparing two sets of calculated values which are subject to possible
cumulative errors one should expect some variation.
4-51
Reactance and Frequency
G 10. c. 600 S. The 120 Hz reactance of the capacitance load will be one-half
the 60 Hz value or 600 S.
d. 600 S. The 120 Hz reactance of the inductance load will be twice the
60 Hz value or 600 S.
REVIEW QUESTIONS
1. a) No.
b) No.
c) No.
d) Yes.
e) Yes.
2. Yes.
4. IL = 0.1 A ac
IC = 0.4 A ac
The total current IT is equal to the algebraic sum of the two currents IC and IL,
and since capacitive current is considered as having a negative value, in this
case IT = -0.3 A ac.
The negative sign indicates that the total current IT is considered to be entirely
capacitive and will lead the line voltage by 90E.
4-52
Experiment 17
Selsyn Control
DISCUSSION
Selsyns (or synchros) are electromagnetic devices which are used primarily for the
transfer of angular position data. They are normally used to provide a means of
transmitting the position of a remotely located device to one or more indicators
located away from the transmitting area. In appearance they resemble small electric
motors. However, when appreciable power is to be transferred, they may be larger
in size.
PROCEDURE
G 2. e. E1 = 90 V ac, E2 = 45 V ac, E3 = 45 V ac
f. E1 = 45 V ac, E2 = 90 V ac, E3 = 45 V ac
g. E1 = 45 V ac, E2 = 45 V ac, E3 = 90 V ac
G 6. d. Yes.
g. Yes.
h. As the rotor is turned each stator current will, in turn, momentarily peak
to some maximum value depending upon the braking torque and then
fall to zero.
4-53
Selsyn Control
REVIEW QUESTIONS
1. Yes. As long as the three connecting stator leads are of heavy enough gauge
to keep losses to a minimum, they will work at any distance.
Figure 17-a
3. Wind direction indicator, antenna direction indicator, gun position indicator, and
remote position controller.
4-54
.
.