Earth Leakage Relay

www.itmikro.com

NX300A
300EA
Features for NX 300A / 300EA
•• Numerical earth leakage relay

•• Programmable current sensitivity and time delay


NX 300A •• Detection of no connection to ZCT

•• Relay trip indicator

•• Relay alarm indicator

•• Real-time leakage current display

•• 50% pre-fault indicator

•• Leakage fault current recording

•• Standard DIN 96x96mm panel mounting

•• Protected against nuisance tripping

Features for NX 300EA only


NX 300EA •• Positive safety output contact
•• Pre-fault alarm contact
•• Remote reset function

Technical Data
AUXILIARY SUPPLY INPUT INDICATORS
Model NX300A / 300EA -230A : 184 ~ 276 V AC Remote Reset : N.O. dry contact * Pre-fault alarm : Red indicator
Model NX300A / 300EA -110A : 94 ~ 127 V AC (Normal blink)
Rated frequency : 50 Hz Time delay : Red indicator
VA rating : 3 VA typical OUTPUTS (Fast blink)
Trip contact : Activated during leakage Leakage trip : 7-segment display
trip, manual test trip or and red indicator
SETTING ZCT connection error ZCT connection error : 7-segment display
Sensitivity adjustment : 30mA, 50mA, Positive safety contact*: Activated when powerup and red indicator
0.10~1.00A(Step=50mA) and relay function Real-time leakage current : 7-segment display
1.00~10.0A (Step=1.00A) correctly
Time delay adjustment : Instantaneous, Alarm contact* : Activated when
0.1~3.0sec (Step=0.1s) measured leakage ZERO - PHASE CURRENT TRANSFORMER
NX 300A / 300EA

current exceeded 50% To operate with Mikro’s ZCT series of current


of IΔn. transformer
PERFORMANCE
Setting accuracy : -15% to +0% OUTPUT CONTACTS ENVIRONMENTAL CONDITIONS
Timing accuracy : ±5% Rated voltage : 240 V AC Temperature : -10°C to 55°C
Contact rating : 5 A Humidity : 5% to 95%,
Expected electrical life : 100,000 operations non-condensing
RECORD at rated current MECHANICAL
Fault record : 3 latest tripped fault Expected mechanical life : 5 x 106 operations Mounting : Panel mounting
currents or “tSt” for Dimension (mm) : 96(w) x 96(h) x 90(d)
manual test trip Enclosure protection : IP54 at the panel
Storage : Non-volatile memory Approximate weight : 0.4 kg (excluding ZCT)

*Applicable to NX300EA series only


Earth Leakage Relay

www.itmikro.com

Typical Application Diagram For NX 300A Case Dimensions


96 mm

NX300A

96 mm
Front

90 mm
70 mm

Side
Typical Application Diagram For NX 300EA

91.0 ± 0.5 mm
NX300EA

91.0 ± 0.5 mm
Panel Cutout

Ordering Information
MODEL DESCRIPTION
NX300A - 240AD For 50Hz system, auxiliary voltage 85~265 V AC or 110~340 V DC
NX300EA - 240AD For 50Hz system, auxiliary voltage 85~265 V AC or 110~340 V DC
NX300A - 230A For 50Hz system, auxiliary voltage 184~276 V AC
NX300EA - 230A For 50Hz system, auxiliary voltage 184~276 V AC
NX300A - 110A For 50Hz system, auxiliary voltage 94~127 V AC
NX300EA - 110A For 50Hz system, auxiliary voltage 94~127 V AC
NX300A - 240AD6 For 60Hz system, auxiliary voltage 85~265 V AC or 110~340 V DC
NX300EA - 240AD6 For 60Hz system, auxiliary voltage 85~265 V AC or 110~340 V DC
NX300A - 230A6 For 60Hz system, auxiliary voltage 184~276 V AC
NX300EA - 230A6 For 60Hz system, auxiliary voltage 184~276 V AC
NX 300A / 300EA

NX300A - 110A6 For 60Hz system, auxiliary voltage 94~127 V AC


NX300EA - 110A6 For 60Hz system, auxiliary voltage 94~127 V AC