www.Jameco.com ✦ 1-800-831-4242
The content and copyrights of the attached
material are the property of its owner.

Jameco Part Number 479373


Series HA, HD
12-90Amp • 480 Vac - AC OUTPUT
• Zero Voltage and Random Featuring state-of-the-art Surface
Mount Technology, these SPST-NO
Turn-On Switching relays deliver proven reliability in the
• Panel Mount most demanding applications.
Output consists of an SCR AC switch
• 1200V Transient Capability
and is available in zero-cross, random
• Integrated Overvoltage turn-on (phase controllable) and ver-
Protection by Automatic sions with either AC or DC input (coil)
Self Turn-On (Suffix P) control.
Manufactured in Crydom’s ISO 9001
• 110 & 125A Models Certified facility for optimum product
Available performance and reliability.
AC CONTROL HA4812 HA4825 HA4850 HA4875 HA4890
MODEL NUMBERS
D C CONTROL HD4812 HD4825 HD4850 HD4875 HD4890

OUTPUT SPECIFICATIONS ➀
Operating Voltage (47-63 Hz) [Vrms] 48-530 48-530 48-530 48-530 48-530
Max. Load Current ➂ [Arms] 12 25 50 75 90
Min. Load Current, [mArms] 40 40 40 40 40
Transient Overvoltage [Vpk] 1200 1200 1200 1200 1200
Max. Surge Current, (16.6ms) [Apk] 140 250 625 1000 1200
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.7 1.7 1.7 1.7 1.7
Thermal Resistance Junction to Case (R θJC) [˚C/W] 1.48 1.02 0.63 0.31 0.28
Maximum I 2 t for Fusing, (8.3 msec.) [A 2sec] 81 260 1620 4150 6000
Max. Off-State Leakage Current @ Rated Voltage [mArms] 10 10 10 10 10
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] ➁ 500 500 500 500 500
Max. Turn-On Time ➄ 1/2 Cycle (DC Input), 10.0 msec (AC Input)
Max. Turn-Off Time 1/2 Cycle (DC Input), 40.0 msec (AC Input)
Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5 0.5

INPUT SPECIFICATIONS ➀ DC CONTROL AC CONTROL AC CONTROL


(D PREFIX) ( A P R E F I X )➃ (E SUFFIX)
Control Voltage Range 3-32 Vdc 90-280 Vrms (60Hz) 18-36 Vrms
Max. Reverse Voltage -32 Vdc --- ---
Max. Turn-On Voltage 3.0 Vdc 90 Vrms 18 Vrms
Min. Turn-Off Voltage 1.0 Vdc 10 Vrms 4.0 Vrms
Nominal Input Impedance See Note ➅ 60K Ohms 9.0K Ohms
Typical Input Current 2.0 mA ➅ 2mA @ 120 Vrms, 4mA @ 240 Vrms 3mA @ 24 Vrms
GENERAL NOTES © 2003 CRYDOM CORP, Specifications subject to change without notice.
➀ All parameters at 25˚C unless otherwise specified.
➁ Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
➂ Heat sinking required, for derating curves see page 2.
➃ 24 Vac Input option, E suffix.
➄ Turn-on time for random turn-on versions
is 0.02 msec (DC Control Models).
➅ Input circuitry incorporates active current limiter. For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
FastFax Document No. 158 Email: sales@crydom.com WEB SITE: http://www.crydom.com
SERIES HA/HD. UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
REV. 111303 Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
PAGE 1 OF 3 GERMANY: +49 (0)180 3000 506
Series HA, HD
12-90Amp • 480 Vac - AC OUTPUT
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base 4000 Vrms
Insulation Resistance (Min.) @ 500 Vdc 109 Ohm
Max. Capacitance Input/Output 8 pF
Ambient Operating Temperature Range -40 to 80˚C
Ambient Storage Temperature Range -40 to 125˚C
MECHANICAL SPECIFICATIONS
Weight: (typical) 3.0 oz. (86.5g)
Encapsulation: Thermally Conductive Epoxy
Terminals: Screws and Saddle Clamps Furnished, Unmounted

AVAILABLE OPTIONS 1.10


MOUNTING (27.9)
E 24 VAC Input (18-36 Vac) HOLE/SLOT .45 8-32 TERMINAL
0.17 (4.3) DIA. (11.4) (2 PLACES )
Example: HA4825E

F Faston Terminals (Up to 50 Amp Models)


Example: HD4850F 1 OUTPUT
2 2.30
(58.4)
1.87
(47.5) 1.70
G Input Status LED. (43.2)
-- +
Agencies Approval Pending 4 INPUT 3
Example: HD4850G
Note: Control Voltage Range 4.5-32 Vdc
for DC Control Models. 1.00 .78
BASE PLATE
.125 (3.2) (25.4) 6-32 TERMINAL (19.8)
P Internal Overvoltage Protection. 1.80 (2 PLACES) .90
(45.7) (22.9)
Relay Will Self Trigger Between
900-1200 Vpk. Not Suitable For
Capacitive Loads.
Agencies Approval Pending. Screw Torque Requirements:
Example: HD4825P 6-32 Screws - 10 in. lbs.,
8-32 and 10-32 Screws - 20in. lbs. 1.10 FASTON TERMINAL
-10 Random Turn-On (AC & DC Control) (Screws dry without grease.) MOUNTING (27.9) .250 X .032 (2 PLCS.)
Phase Controllable (DC Control) HOLE/SLOT .45 .87 REF.
Fastons: 0.17 (4.3) DIA. (11.4) (22.2)
Example: HD4890-10 Single pair (up to 25A)
Double pair* (up to 50A).
H Heat Transfer Pad (Attached) *Caution: User must connect to both pairs
1 OUTPUT 2 2.30
Example: HD4890H (58.4)
1.87
(47.5) 1.70
(43.2)
Ordering System: Combination of the -- +
4 INPUT 3
suffixes should be made in the following order:
EFPG-10.
Example: HA4850EFPG-10 .78
BASE PLATE 1.00 FASTON
.125 (3.2) (25.4) TERMINAL (19.8)
1.80 .187 X .032 .90
(22.9)
Crydom Heat Sinks offer excellent (45.7) (2 PLCS.)

thermal management and are per-


fectly matched to the load current
ratings of Crydom panel mount
relays. Request Crydom’s Heat Sink
specification sheet for all the details. All dimensions are in inches (millimeters)

© 2003 CRYDOM CORP, Specifications subject to change without notice.


APPROVALS
UL E116949
For recommended applications and more information contact:
CSA LR81689 USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
VDE 10143 UG Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
FastFax Document No. 158
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
SERIES HA/HD.
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
REV. 111303
GERMANY: +49 (0)180 3000 506
PAGE 2 OF 3
Series HA, HD
12-90Amp • 480 Vac - AC OUTPUT

CURRENT DERATING CURVES


12A
14
25A
12 30 95
7˚C/W 3˚C/W 1˚C/W
10 110 25 100

Base Plate Temp [˚C]

Base Plate Temp [˚C]


9˚C/W 5˚C/W 3˚C/W 2˚C/W
Power Dissipation

Power Dissipation
8 20
NO HEATSINK 115
6 15 110
4 10
120 NO HEATSINK
2 5 120

0 0
0 2 4 6 8 10 12 20 40 60 80 5 10 15 20 25 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C] Load Current [Arms] Max Ambient Temp. [˚C]

50A 75A 90A


60 120 120 90
1˚C/W .5˚C/W 90 .5˚C/W .2˚C/W
95
Base Plate Temp [˚C]

Base Plate Temp [˚C]

Base Plate Temp [˚C]


1.5˚C/W .5˚C/W .3˚C/W .4˚C/W
100
Power Dissipation

Power Dissipation

Power Dissipation
40 80 100 80
100
2˚C/W 1˚C/W
1ºC/W

110 110
110
20 40 40

NO HEATSINK 120 120 120


0 0 0
10 20 30 40 50 20 40 60 80 15 30 45 60 75 20 40 60 80 20 40 60 80 0 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C] Load Current [Arms] Max Ambient Temp. [˚C] Load Current [Arms] Max Ambient Temp. [˚C]

© 2003 CRYDOM CORP, Specifications subject to change without notice.

For recommended applications and more information contact:


USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
FastFax Document No. 158 Email: sales@crydom.com WEB SITE: http://www.crydom.com
SERIES HA/HD. UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
REV. 111303 Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
PAGE 3 OF 3 GERMANY: +49 (0)180 3000 506

You might also like