MMX-2017-12N Intelligent Network Fire Alarm Control Panel (Secutron)
MMX-2017-12N Intelligent Network Fire Alarm Control Panel (Secutron)
MMX-2017-12N Intelligent Network Fire Alarm Control Panel (Secutron)
MMX-2017-12N
Intelligent Network Fire Alarm Control Panel Features
Fire Alarm Control
• One expandable to seventeen Intelligent Signaling
Line Circuits (SLC)
• Modular design
• Each SLC Loop is capable of supporting 99 Analog
Sensors and 99 Addressable Modules which can be
wired in Style 6 or 7 (Class A) or Style 4 (Class B)
• Four Style Z/Y (Class A/B) Notification Appliance
Circuits rated at 1.7 Amps each
• Large 4 by 20 character Back-lit LCD Display with user
friendly menu
• Panel Security to protect site configurations
• Correlatable Switch Inputs which allows for multi-
functional outputs
• Four Status Queues with selector switches and LEDs
for Alarm, Supervisory, Trouble and Monitor
• Auxiliary relay contacts for Common Alarm, Common
Supervisory and Common Trouble
• Group bypass with built-in false alarm prevention
technology
• RS-232 output for remote system printer or CRT
• Two Event History Logs comprised of a 6000 Alarm
History Log for alarm related events and a 6000 Event
Description Log for all events
• Supports three configuration files (current, previous and
Secutron’s MMX-2017-12N Network Fire Alarm next configuration) with “hot swap” support
Control Panel offers modular components to meet a • Supports Conventional Hardwire Adder Modules
wide variety of applications. Designed for peer-to-peer • Built-in One Man Walk Test operation
network communications, the MMX-2017-12N allows • Configurable for Canadian Two Stage operation
for a maximum of 63 nodes, while providing reliability, • Built-in 16 zone configurable LED annunciator complete
flexibility and expandability. with individual slide-in labels for zone definition
• Configurable for Coded Operation
The MMX-2017-12N base panel consists of one • Real time 3D graphical monitoring and control using
intelligent signaling line circuit (SLC) capable of Open Graphic Navigator™
supporting 99 analog sensors and 99 addressable • BACnet support
modules. In addition the base panel also consists • Supports Boolean logic functions
of Four Style Z/Y (Class A/B) Notification Appliance • Built-in Ethernet port
Circuits rated at 1.7 Amps each and a large 4 x 20 • Remote diagnostics via a built-in web server
back-lit alphanumeric LCD display. • UL listed for Smoke Control
Network Features
The MMX-2017-12N network configuration allows the
• Up to 63 nodes
control panel to be connected to a Secutron network
• Peer-to-peer network communications
to provide additional input circuits, visual zones,
• Style 4 (Class B) or Style 6 or 7 (Class A) wiring
programmable notification appliance circuits, and relays.
configuration
The network interface module allows the panels to • Proprietary Arcnet Network Communications
communicate on a peer-to-peer network. protocol
The network capabilities allow site specific • Supports copper and/or fiber optic network cable
customization and the ability to meet local and national
requirements.
S6619 S6619
ALCN-792M Quad Loop Controller Module FNC-2000 Fire Network Controller Module
The ALCN-792M Quad Loop Controller Module provides The FNC-2000 provides network capability to the MMX-
two Signaling Line Circuits (SLC) to the MMX system 2017-12N. One Fire Network Controller Module is
consisting of 99 Analog Sensors and 99 Addressable required per network node panel. In addition the FNC-
Modules per loop. The ALCN-792M can be expanded 2000 provides an interface for adding an optional FOM-
with the use of the ALCN-792D Daughter Board 2000-SP Fiber Optic Network Adder Module. The FNC-
Module. The ALCN-792M occupies one module slot. 2000 mounts in the MMX-2017-12N main chassis.
MMX-BB-1002 18”H x 12.75”W x 1.2”D Power Supply Ratings 12 Amps. max. (secondary)
MMX-BB-1003 26.4”H x 12.75”W x 1.2”D For NAC Circuits 24VDC unfiltered, 10 Amps. max.
DM-1008A Eight Initiating Circuit Module UDACT-300A Digital Alarm Communicator Module
The DM-1008A provides 8 Style B (Class B) or 4 Style The UDACT-300A Digital Alarm Communicator Module
D (Class A) Initiating Circuits configurable for Alarm, allows the MMX-2017-12N to transmit addressable point
Supervisory or Trouble zones. The DM-1008A occupies information to a central station. The UDACT-300A occupies
one module slot in the MMX-2017-12N main chassis. one module slot in the MMX-2017-12N main chassis.
RAM-1032TZ Main Remote LED Annunciator RAX-1048TZ Programmable LED Annunciator Module
The RAM-1032TZ Main Remote LED Annunciator The RAX-1048TZ Programmable LED Annunciator
provides common annunciator functions and 32 points Module provides 48 programmable bi-colored LEDs. The
of LED annunciation. The RAM-1032TZ has indicators RAX-1048TZ connects to the main panel or either the
for A.C. On, Common Trouble and Signal Silence and RAXN-LCD or RAM-1032TZ when mounted remotely.
controls for System Reset, Lamp Test, Fire Drill, Buzzer The RAX-1048TZ occupies one display position in the
Silence and Signal Silence. The RAM-1032TZ occupies MMX-BB-1000 or BB-5000 Series enclosure.
one display position in the MMX-BB-1000 or BB-5000
Series enclosure.
Graphic Annunciator Driver Modules
MGD-32 Master Graphic Driver Module AGD-048 Adder Graphic Driver Module
The MGD-32 Master Graphic Driver Module provides The AGD-048 Adder Graphic Driver Module can be
common control inputs for the common control switches used with the MGD-32 to support an additional 48
such as System Reset, Signal Silence, Auxiliary supervised outputs. The AGD-048 mounts in a graphic
Disconnect, Fire Drill, Lamp Test, Acknowledge and annunciator wallbox or in the BB-5000 Series enclosure.
General Alarm. The MGD-32 can also drive up to 32
supervised outputs. These output points are capable
of driving LEDs or incandescent lamps. The MGD-32
mounts in a graphic annunciator wallbox or in the BB-
5000 enclosures. An external power supply is required
for incandescent lamps and lamp test.
RS-485
RAXN-LCD and
two RAX-1048TZ in an
MMX-BB-1003R enclosure
Node 1
MMX-2017-12N in an
MMX-BBX-1072AR enclosure
RS-485
RAXN-LCD in an
MMX-BB-1001R enclosure
Node 5 Node 2
MMX-2003-12N in an MMX-2003-12N in an
MMX-BBX-1024R enclosure MMX-BBX-1024R enclosure
RS-485
Class ‘B’ (Style 4) wiring
Ethernet
RAXN-LCD in an
MMX-BB-1001R enclosure
Node 4 Node 3
MMX-2017-12N in an MMX-2017-12N in an
MMX-BBX-1072AR enclosure MMX-BBX-1072AR enclosure
Current Consumption
Model Number Description Standby Alarm
MMX-2017-12N Main Chassis (12 Amp) 0.310 0.733
ALCN-792M Dual Analog Loops 0.130 0.145
ALCN-792M with ALCN-792D Quad Analog Loops 0.130 0.145
FNC-2000 Fire Network Controller Module 0.190 0.0190
FOM-2000-SP Fiber Optics Module 0.015 0.015
DM-1008A 8 Initiating Circuit Module 0.080 1 zone active: 0.125
2 zone active: 0.170
4 zone active: 0.275
6 zone active: 0.370
8 zone active: 0.465
SGM-1004A 4 Notification Appliance Circuit Module 0.060 0.258
RM-1008A 8 Relay Circuit Module 0.025 0.150
FDX-008 Fan Damper Control Module 0.015 0.035
UDACT-300A Dialer Module 0.045 0.120
PR-300 City Tie Module 0.035 0.300
RAX-1048TZ Adder Annunciator Chassis 0.022 1 zone active: 0.026
2 zone active: 0.030
3 zone active: 0.035
4 zone active: 0.039
48 zone active: 0.262
RAM-1032TZ Adder Annunciator Chassis 0.050 32 zone active: 0.300
AGD-048 Adder Graphic Driver Board 0.035 # of LEDs x 4mA
IPS-2424 Programmable Input Switches Module 0.010 0.015