Project: 272.8 KWp Rooftop Solar Power Plant for RFL Group at RFL-11, Bike
Variant: South
No 3D scene defined, no shadings
System power: 273 kWp
Sylhet - Bangladesh
Page 1/9
Project: 272.8 KWp Rooftop Solar Power Plant for RFL Group
at RFL-11, Bike, Habiganj, Sylhet, Bangaldesh
PVsyst V7.2.3
Variant: South
VC0, Simulation date:
21/11/22 15:40
with v7.2.3
Project summary
Geographical Site Situation Project settings
Sylhet Latitude 24.28 °N Albedo 0.20
Bangladesh Longitude 91.38 °E
Altitude 15 m
Time zone UTC+6
Meteo data
Olipur
Meteonorm 8.0 (1996-2015), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 496 units Nb. of units 2 units
Pnom total 273 kWp Pnom total 220 kWac
Pnom ratio 1.240
Results summary
Produced Energy 375.7 MWh/year Specific production 1377 kWh/kWp/year Perf. Ratio PR 84.74 %
Table of contents
Cover page 1
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
Special graphs 7
Aging Tool 8
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 20 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Astronergy Manufacturer Huawei Technologies
Model CHSM72M-HC-550 Model SUN2000-110KTL-M0
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 550 Wp Unit Nom. Power 110 kWac
Number of PV modules 496 units Number of inverters 2 unit
Nominal (STC) 273 kWp Total power 220 kWac
Modules 31 Strings x 16 In series Operating voltage 200-1000 V
At operating cond. (50°C) Max. power (=>30°C) 121 kWac
Pmpp 249 kWp Pnom ratio (DC:AC) 1.24
U mpp 605 V
I mpp 412 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 2.0 % Module temperature according to irradiance Global array res. 32 mΩ
Uc (const) 29.0 W/m²K Loss Fraction 2.0 % at STC
Uv (wind) 0.0 W/m²K/m/s
Serie Diode Loss LID - Light Induced Degradation Module Quality Loss
Voltage drop 0.7 V Loss Fraction 2.0 % Loss Fraction -0.8 %
Loss Fraction 0.1 % at STC
System losses
Auxiliaries loss
Proportionnal to Power 5.0 W/kW
0.0 kW from Power thresh.
AC wiring losses
Inv. output line up to injection point
Inverter voltage 400 Vac tri
Loss Fraction 1.00 % at STC
Inverter: SUN2000-110KTL-M0
Wire section (2 Inv.) Copper 2 x 3 x 95 mm²
Average wires length 61 m
Main results
System Production
Produced Energy 375.7 MWh/year Specific production 1377 kWh/kWp/year
Performance Ratio PR 84.74 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
Loss diagram
1528 kWh/m² Global horizontal irradiation
+6.4% Global incident in coll. plane
Special graphs
Daily Input/Output diagram
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.55 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Olipur MN80 SYN
Years 1990 (reference year)
Years simulated 1-25
Performance Ratio
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.55 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Olipur MN80 SYN
Years 1990 (reference year)
Years simulated 1-25