Touch Screen Room Thermostat About your thermostat Model definition of your thermostat

User Guide Model:BAC-1000MLN BAC-1000MLN Modern Touch Screen A1: Two pipe; Control Fan Coil Unit and Two
Room Thermostats are designed to control wired Motorized valve.(when room temperature
the fans and valves in air conditioner applications reaches the setpoint, both will turn off)
via comparison of the room temperature and A2: Two pipe; Control Fan Coil Unit and Two
setting temperature as reaching the aim of wired Motorized valve.(when room temperature
comfort and saving energy. BAC-1000 are reaches the setpoint, valve will turn off but fan will
microprocessor based thermostat with LCD turn to low speed)
display. B: Two pipe; Control on/off Motorized Damper
C: Two Pipe; Control Fan Coil Unit and Three
Features of your thermostat wired Motorized valve
M: Two pipe; Control 0-10V Motorized Valve
Modern desgin similar as a cell phone.
E: Four pipe; Control Fan Coil Unit and Two wired
Beautiful Frame CHROME creates elegant life.
Heat and Cool Motorized valve.
Acrylic lenses to avoid the finger scrath.
Welcome T: Clock
Touch Button makes simple operation.
L: Backlight
Your new thermostat will provide year of reliable Large screen display with backlight is easy to
P: Weekly Programmable
service. Using this digital thermostat will provide read—even in the dark.
Precise comfort control keeps temperature within N: RS485/MODBUS RTU communication
more uniform comfort in your home through the K: Keycard
1°C of the level you set.
seasons. Thank you for buying the product! E: External sensor
Please read this manual for complete instructions Easy installation.
For example:BAC-1000MLN
on installing and operating your thermostat. If you 86mm hidden box and european 60mm round
require further assistance, please feel free to box is selectable. Operation
contact us.
1. Setting the temperature
In the box you will find Press to set temperature.
Screws 2pc
Home screen quick reference will display in the left corner of screen.
Thermostat 1pc
User Guide 1pc Wall plate 1pc Set 2. Setting Lock (optional function)
Room Temp. Valve Fan
Service Temp. On/off Speed Press and hold for 3 sec. to lock the screen.
We offer the warranty of 24 months from the sales day. The icon will display on the screen.
If it is not the problem of quality or beyond the warranty Energysaving Press and hold again for 3 sec. to unlock the
time, we will charge for the after-sale service. Network screen.
Manual Auto Fan 3. Setting the fan
Technical Data of your thermostat Lock
Cooling
Timing On/Off Press to select the fan speed AUTO, HIGH,
Clock
Sensor:NTC Accuracy:±1℃ MED, LOW.
Temp. Range:5 -35℃ Power Consumption:<1.5W 4. Setting the system mode
Sleeping
Timing error:<1% Power Supply:110~240V, 50 ~60Hz
Current Load:1A(Inductive), 2A(Resistance)
Press M to change the system mode HEATING,
Mode Fan Power Up Down
Shell Material:PC (Fireproof) On/off
COOLING and VENTILATION. In the mode of
Dimension:86x86x13.3mm VENTILATION, the valve is off but the fan runs.
Installation box:86*86mm or European 60mm
Ambient Temp.:0 ~ 45℃,5 ~ 95%RH(Non condensing)
Storage Temp:-5~ 55℃
5.Setting the Clock ambient temperature and setpoint is 5 ℃, the valve will open 20%.
Installing your thermostat
Press and hold M to set Clock;Press M to set the Heat mode (P-band: 2 )
minutes of the time,press to adjust the relative When the ambient temperature is below the set point the output Your thermostat is suitable for installation within
a standard 86mm pattress box or European 60mm
values.Same setting for hour and week of the time. is somewhere between 0~100%.
round pattress box.
After that, all will be confirmed automatically. % of Output 100%
0-10V P=2 Step 1. Keep power off. See Fig 1.

...
6. Setting functions and options 30%

20%
During power off, press and hold M at the same
10%
time for 5 sec. to system functions. Then press M 0%
to change the different items.
-20 -15 -10 -5 Set point
+5 +10 +15 +20
Press or to set the relative values. Fig 1
All the settings will confirm automatically when Cool mode(P-band: 2 ) Step 2. Remove the mounting Plate. See Fig 2.
power is on. When the ambient temperature is above the set point the output
is somewhere between 0~100%.
No Func on Se ng & Op ons Default
Temp. % of Output 100%
1 -9℃ to 9℃ -2 0-10V P=2

...
Calibra on 30%
00: When room temp. reaches 20%
the setpoint, the fan will turn Fig 2
10%
Fan Control off.
2 00
01: When room temp. reaches 0% Step 3. Connect power supply, load and external (floor) sensor
the setpoint, the fan will keep -20 -15 -10 -5 Set point
+5 +10 +15 +20 into the appropriate terminals if there is external sensor.
the same speed. (see “Wiring your thermostat” for details and Fig 3).
00:All the bu ons are locked
3 Lock except POWER 01
01 :All the bu ons are locked
00:Cool only
4 Heat/Cool 01
01: Heat/Cool
5 Min. Set Temp. 5-15℃ 5 Fig 3
6 Max. Set Temp. 15-35℃ 35 loop will become sluggish. It can be adjust from 1S-60S. Factory Default
00:12 hours is 40S. Step 4. Fix the mounting plate into the wall with screws in
7 Time Display 01
01:24 hours Wiring your thermostat the box. See Fig 4
00:display both set temp. and
8 Display mode room temp. 00
01:display set temp. only AC 95~220V , 50~60Hz
0-10 Valve
9 INVLID - + N L
10 P value 1-10 2
11 I value 1S-60S 40 Fan
12 INVLID Fig 4
13 IP Address 0X00-0XFF(1-255) 1 Step 5. Fasten body of thermostat and the mounting plate
14 Baud Rate Setting
1: 9600, 2: 14400, 3: 19200, 4:38400,
1 through the groove. See Fig 5.
5: 56000
Low
Med
High

15 Modbus version 801

temperature for the output to go from 0 to 100%. It can be adjust from


1~10. Factory default is 2. Fig 5 Fig 6
The P value is bigger, the change of valve output will be bigger; (white)B A (red) Step 6. Installation complete. See Fig 6.
The P value is smaller, the change of valve output will be smaller.
Modbus RISK OF ELECTRICAL SHOCK. Disconnect/isolate
For example, when P=2, the temperature difference between
power supply prior to making electrical connections.
ambient temperature and setpoint is 5 ℃,the valve will open
Contact with high voltage components can cause electrical
about 10%; when P=4, the temperature difference between Two Pipe System shock, severe injury or death.