Hot Water Demand per Fixture for Various Type of Buildings

(Litres of water per hour per fixture, calculated at a final temperature of 60°C)
Apartment Industrial Office Private
House Club Gymnasium Hospital Hotel Plant Building Residence School YMCA
1.Basin,private Lavatory 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6
2.Basin,public lavatory 15 23 30 23 30 45.5 23 - 57 30
3.Bathtub 76 76 114 76 76 - 76 - 114
4.Dishwasher 57 190-570 - 190-570 190-760 76-380 - 57 76-380 76-380
5.Foot Basin 11 11 46 11 11 46 - 11 11 46
6.Kitchen Sink 38 76 - 76 114 76 76 38 76 76
7.Laundry,Staionary tub 76 106 - 106 106 - - 76 - 106
8.Pantry Sink 19 38 - 38 38 - 38 19 38 38
9.Shower 114 568 850 284 284 850 114 114 850 850
10.Service Sink 76 76 - 76 114 76 76 57 76 76
11.Hydrotherapeutic - - - 1520 - - - - - -
shower -
12.Hubbard bath - - - 2270 - - - - - -
13.Leg bath - - - 380 - - - - - -
14.Arm bath - - - 130 - - - - - -
15.Sitz bath - - - 114 - - - - - -
16.Continuous-flow - - - 625 - - - - - -
bath -
17.Circular wash sink - - - 76 76 114 76 - 57 -
18.Semicircular wash - - - 38 38 57 38 - 114 -
sink
19.Demand Factor 0.3 0.3 0.4 0.25 0.25 0.4 0.3 0.3 0.4 0.4
20.Storage Capacity 1.25 0.9 1 0.6 0.8 1 2 0.7 1 1
Factor