Calculation for Fire Pump Room Ventilation

Ventilation Fans will work at same ACH in case of fire @ 10 ACH & normal mode
with 6 ACH

Area = 34 m²
Hight = 3.15 m²
Volume = 107.1 m³

One Air Change 62.5 CFM

Ventilation Air Required @ Noraml Case 6 ACH 375 CFM


Ventilation Air Required @ Fire Case 10 ACH 625 CFM

assume 10% more for frsh air fan fire pump room should be +ve all the time

Ventilation Air Required @ Noraml Case 6 ACH 413 CFM


Ventilation Air Required @ Fire Case 10 ACH 688 CFM

Get Required Fresh Air Fan


Normal Mode 413 CFM
Fire Mode 688 CFM

Get Required Exhaust Air Fan


Normal Mode 375 CFM
Fire Mode 625 CFM