MVI69 AFC Datasheet
MVI69 AFC Datasheet
MVI69 AFC Datasheet
The Liquid & Gas Flow Computer Module is designed as an Integrated component
®
for CompactLogix systems to measure hydrocarbon gasses or liquids with accuracy
and precision.
The flow computer calculates flow rates and accumulated totals of volume, mass,
and energy (heating value) for specified liquids and gases. Selected calculated
results are transferred to processor memory for use in the application ladder
programs. A SCADA host may retrieve the same values through any of three front-
panel Modbus serial ports.
Features Benefits
8 Meter runs ♦ The module can calculate up to 8 meter runs with four streams per runs simultaneously,
making it cost effective, since more meters can be connected to a single flow computer.
♦ Monitor gas and liquid meters for (flow rates, accumulator values and other calculation
results). All alarm data is displayed on the AFC Manager screen
♦ The AFC Manager software provides ability to download and view the archives and events
Three Configurable Modbus ♦ Change Configuration Online with no downtime
Ports ♦ All Data including configuration, calculated results, and historical records available using
Modbus through any of the three ports.
♦ All ports can operate as Modbus slaves and one port can be configured as a Modbus Master
Customized Modbus Data ♦ Remapping to a virtual slave enables data concentration
Mapping ♦ Data concentration reduces bandwidth load on the communication system
Auditability ♦ Audit Scan captures process inputs and calculated results as "snapshots", allowing
verification of calculations.
♦ Event Log records significant events and alarms.
♦ Hourly and daily archives are configurable historical records of user-selected data.
♦ Using Modbus, Audit Scan, Event Log, and Archives, can be viewed online, printed, or
saved to a file in .txt or .csv format.
Security ♦ Data download is secure with no data loss.
♦ Password protection schemes are available to control user access.
Configuration
The AFC Manager is a Windows 98/NT/2000/XP/Vista/7-based configuration, reporting, and monitoring tool provided with all
AFC modules. Project configurations may be uploaded, downloaded and saved to the PC under user-selectable file names.
General Specifications
♦ Single-slot, 1769 backplane-compatible
♦ The module is recognized by the processor as an Input/Output module.
♦ The included sample ladder logic file is used for data transfer between module and
processor.
♦ Configuration data can be downloaded over Modbus or delivered by user-defined
ladder.
♦ Supports CompactLogix and MicroLogix 1500 LRP Controllers except
1769-L23E-QBFC1B, 1769-L16x, and 1769-L18x Additional Products
®
ProSoft Technology offers a full
Functional Specifications complement of hardware and
software solutions for a wide variety
The AFC module operates as a powerful flow computer module, augmenting the
® of industrial communication
operation of the CompactLogix processor by providing a dedicated and accurate set of
platforms. For a complete list of
flow calculations.
products, visit our web site at:
♦ Calculates flow rates, accumulated volumes, accumulated mass, and accumulated www.prosoft-technology.com
energy
♦ Calculation results are transferred to processor memory and may also be
transferred to a SCADA host using Modbus.
♦ User configurable, allowing each of the meter runs to be individually set up to meet Ordering Information
the specific requirements of an application
To order this product, please use the
Archiving following:
♦ Supports data archiving and event logging
♦ Data archiving is available for each meter run, hourly for two days (48 records) and
daily for one month (35 records) under default configuration, with optional extended
archives up to 1,440 hourly (60 days) and 1,440 daily. The actual number of Liquid and Gas Flow
archives is dependent upon the size set by the user for each archive type.
♦ Event logging feature provides storage of up to 1,999 station events.
Computer for
CompactLogix®
Configurable Options
♦ User-selectable units for totalizers and flow rates on a per channel basis
♦ Roll-over value for resettable and non-resettable totalizers for every meter channel MVI69-AFC
♦ Process analog input units and ranges (pressure, temperature, differential
pressure, density) from analog input modules and pulse inputs from
pulse/frequency input modules in a CompactLogix chassis To place an order, please contact
♦ Fluid selection provides a choice of several liquid groups or gas measurement, your local ProSoft
using AGA or ISO calculations. Technology distributor. For a list
♦ Event log reports for all security-sensitive configuration data (for example, orifice of ProSoft Technology
diameter) are date and time stamped. This data can be saved to disk for importing distributors near you, go to:
into any spreadsheet or printed as a hard copy www.prosoft-technology.com
and select Where to Buy from the
Modbus Interface menu.
♦ All three Modbus slave ports allow for SCADA communication and can be
configured for RTU or ASCII mode.
♦ Modbus table may be re-mapped as a virtual Modbus slave for user-assigned
contiguous register polling by a SCADA master (up to 20,000 registers).
♦ One of the three ports can be configured as a Modbus Master port to poll data from
remote devices.