The document is a maintenance checklist for fire systems at a cocoa plantation. It details 23 locations where fire equipment was inspected, including security posts, offices, and storage areas. Most locations were found to have functioning smoke detectors, alarms, and panels. However, a few areas had trouble alarms due to recent construction or non-functioning SIM cards. Replacement parts were installed at two locations to restore those systems to normal working condition.
The document is a maintenance checklist for fire systems at a cocoa plantation. It details 23 locations where fire equipment was inspected, including security posts, offices, and storage areas. Most locations were found to have functioning smoke detectors, alarms, and panels. However, a few areas had trouble alarms due to recent construction or non-functioning SIM cards. Replacement parts were installed at two locations to restore those systems to normal working condition.
The document is a maintenance checklist for fire systems at a cocoa plantation. It details 23 locations where fire equipment was inspected, including security posts, offices, and storage areas. Most locations were found to have functioning smoke detectors, alarms, and panels. However, a few areas had trouble alarms due to recent construction or non-functioning SIM cards. Replacement parts were installed at two locations to restore those systems to normal working condition.
The document is a maintenance checklist for fire systems at a cocoa plantation. It details 23 locations where fire equipment was inspected, including security posts, offices, and storage areas. Most locations were found to have functioning smoke detectors, alarms, and panels. However, a few areas had trouble alarms due to recent construction or non-functioning SIM cards. Replacement parts were installed at two locations to restore those systems to normal working condition.
Project : PT BUMITANGERANG MESINDOTAMA ( COCOA ) Mulai Pekerjaan : 28 Juli 2022
Jenis : SERVICE MAINTENANCE FIRE SYSTEM Hari/Tanggal : 7/28/2022 Plant : TANGGERANG Nama Kontraktor : PT WIRA SUKSES SEJATI Kunjungan : 1 ( pertama ) LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN No KETERANGAN TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9 Panel kondisinya masih trouble di karna kan ada 1 Pos security BT 3 MCFA Simpleks 4100 Simpleks 1 N/A N/A N/A N/A N/A N/A ✓ N/A ✓ Fisik atau sistem pembongkaran di area Onxy Simpleks 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ N/A ✓ Sulawesi dan simcard tidak terkoneksi Panel kondisinya masih trouble di karna kan ada 2 Pos security BT 2 MCFA Simpleks 4100 Simpleks 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ N/A ✓ pembongkaran di area 3 Pos security BT 1 Annunciator Simpleks 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ N/A ✓ Sulawesi dan simcard tidak terkoneksi Area di bongkar tampilan di panel trouble no 4 Sulawesi room BT 1 lantai 1 Smoke detector addressable Simpleks 3 Smoke check 12,7,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ answer smoke detector, hornstrobe,mcp 5 Area lobby lantai 1 Smoke detector addressable Simpleks 4 Smoke check 4,5,52,53 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 6 Ruang office HSE Smoke detector addressable Simpleks 1 Smoke check 10 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 7 Bali room lantai 1 Smoke detector addressable Simpleks 1 Smoke check 9 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 8 HRGA Dept lantai 1 Smoke detector addressable Simpleks 1 Smoke check 55 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 9 Office lantai 2 Smoke detector addressable Simpleks 6 Smoke check 13,14,15,18,19,20 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 10 Area pantry Smoke detector addressable Simpleks 1 Smoke check 12 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 11 Papua room lantai 2 Smoke detector addressable Simpleks 1 Smoke check 16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 12 Office lantai 2 Smoke detector addressable Simpleks 13 Smoke check 21,25,26,169,170,171,172 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 173.174.175.176 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 13 Lampung room Smoke detector addressable Simpleks 2 Smoke check 27,28 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 14 Ruang projects Office lantai 2 BT 1 Smoke detector addressable Simpleks 16 Smoke check 2,3,18,21,22,24,25,26,27,28,29 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 30,31,32,33,34 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Smoke detector rusak 1 unit sudah di ganti baru 15 Area ruang ganti BT 1 lantai 1 Smoke detector addressable Simpleks 7 Smoke check 1,2,3,5,7,11,17 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ sistem kembali normal 16 Ruang instrumen BT 1 lantai 1 Smoke detector addressable Simpleks 2 Smoke check 16,14 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 17 Ruang analisa BT 1 lantai 1 Smoke detector addressable Simpleks 2 Smoke check 10,13 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 18 Office room BT 1 lantai 1 Smoke detector addressable Simpleks 1 Smoke check 15 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 19 Area sensory room BT 1 lantai 1 Smoke detector addressable Simpleks 1 Smoke check 8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 20 Prepation Room BT 1 lantai 1 Smoke detector addressable Simpleks 1 Smoke check 9 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 21 ARC Hives room BT 1 lantai 1 Smoke detector addressable Simpleks 2 Smoke check 3,6 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Smoke detector rusak 1 unit sudah di ganti baru 22 Control room miling BT 1 lantai 1 Smoke detector addressable Simpleks 2 Smoke check 44,45 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ sistem kembali normal 23 Area sempling BT 1 lantai 1 Manual call points Simpleks 4 Trigger Input 46,47,48,49 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal Hornstrobe Simpleks 4 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal Beacon sounder Simpleks 4 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 24 SPL SILO BT 1 lantai 1 Smoke detector addressable Simpleks 4 Smoke check 89,90,91,92 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 25 Ruang produksi silo BT 1 lantai 1 Smoke detector addressable Simpleks 11 Smoke check 110.111.112.113.114 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 115,116,117,118,119, ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 120 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 26 Area powder plant control room BT 1 lantai 2 Smoke detector addressable Simpleks 4 Smoke check 38,39,40,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 27 Area control room press Bt 1 lantai 2 Smoke detector addressable Simpleks 6 Smoke check 32,33,34,35,36,37 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Smoke detector rusak 1 unit dan sudah di ganti baru 28 Area boiler Pos BT 1 Smoke detector addressable Simpleks 1 Smoke check 41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ sistem kembali normal 29 Area DEGBC area'bos Bt 1 lantai 2 Smoke detector addressable Simpleks 2 Smoke check 50,52 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 30 at 3 LVDP lantai 3 Smoke detector addressable Simpleks 7 Smoke check 35,36,37,38,39,40,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 31 Area winowing Bt 3 Smoke detector addressable Simpleks 5 Smoke check 44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 32 Ruang Opex BT 3 Smoke detector addressable Simpleks 3 Smoke check 49,50,51 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 33 Ruang Leporas 2v BT 3 Smoke detector addressable Simpleks 2 Smoke check 52,53 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Smoke detector rusak 1 unit dan sudah di ganti baru 34 BT 3 area plant at RM office Smoke detector addressable Simpleks 9 Smoke check 114.115.116.117.118 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ sistem kembali normal 119.120.121.122 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 35 Area office timbangan BT 2 Smoke detector addressable Simpleks 2 Smoke check 63.128 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 36 Area office warehouse BT 3 Smoke detector addressable Simpleks 1 Smoke check 6 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 37 Area locker Bt 3 Smoke detector addressable Simpleks 1 Smoke check 4 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 38 BT 3 area Gh 1 line 1 GHIU Smoke detector addressable Simpleks 9 Smoke check 1,2,3,4,5,6,7,8,9 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 39 BT 3 area Gh 1 line 1 GH1A Smoke detector addressable Simpleks 5 Smoke check 1,2,3,4,5 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 40 BT 3 area Gh 1 line 2 GHIW Smoke detector addressable Simpleks 10 Smoke check 10,11,12,13,14,15,16,17,18,19 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 41 BT 3 area Gh 1 line 2 GH1C Smoke detector addressable Simpleks 5 Smoke check 6,7,8,9,10 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 42 BT 3 area Gh 1 line 3 GHIY Smoke detector addressable Simpleks 11 Smoke check 20,21,22,23,24,25,26,27,28,29,30 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 43 BT 3 area Gh 1 line 3 GH1E Smoke detector addressable Simpleks 6 Smoke check 11,12,13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 44 BT 3 area Gh 1 line 4 GHIA Smoke detector addressable Simpleks 11 Smoke check 31,32,33,34,35,36,37,38,39,40,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 45 BT 3 area Gh 1 line 4 GH1G Smoke detector addressable Simpleks 6 Smoke check 17,18,19,20,21,22 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN No KETERANGAN TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9 46 BT 3 area Gh 1 line 5 GH1Z Smoke detector addressable Simpleks 11 Smoke check 42,43,44,45,46,47,48,49,50,51,52 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 47 BT 3 area Gh 1 line 5 GH1I Smoke detector addressable Simpleks 6 Smoke check 23,24,25,26,27,28 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 48 BT 3 area Gh 1 line 6 GH1Z Smoke detector addressable Simpleks 11 Smoke check 53,54,55,56,57,58,59,60,61,62,63 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 49 BT 3 area Gh 1 line 6 GH1K Smoke detector addressable Simpleks 6 Smoke check 29,30,31,32,33,34 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Smoke detector rusak 1 unit dan sudah di ganti baru 50 BT 3 area Gh 1 line 7 GH1ZG Smoke detector addressable Simpleks Smoke check 17,18,19,20,21,22,23,24,45 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ 9 sistem kembali normal 51 BT 3 area Gh 1 line 7 GH1M Smoke detector addressable Simpleks 6 Smoke check 35,36,37,38,39,40 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 52 BT 3 area Gh 1 line 8 GH1Z1 Smoke detector addressable Simpleks 11 Smoke check 75,76,77,78,79,80,81,82,83,84,82 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 53 BT 3 area Gh 1 line 8 GH10 Smoke detector addressable Simpleks 6 Smoke check 41,42,43,44,45,46 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 54 BT 3 area Gh 1 line 9 GH1K Smoke detector addressable Simpleks 11 Smoke check 86,87,88,89,90,91,92,93,94,95,96 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 55 BT 3 area Gh 1 line 9 GH1Q Smoke detector addressable Simpleks 6 Smoke check 47,48,49,50,51,52 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 56 BT 3 area Gh 1 line 10 GH1ZL Smoke detector addressable Simpleks 9 Smoke check 97,98,99,100,101,102,103,104,105 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 57 BT 3 area Gh 1 line 10 GH1R Smoke detector addressable Simpleks 5 Smoke check 53,54,55,56,57 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 58 BT 3 area Gh 1 line 10 GH1T Smoke detector addressable Simpleks 5 Smoke check 58,59,60,61,62 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 59 BT 3 area Gh 1 line 11 HU Smoke detector addressable Simpleks 4 Smoke check 1,2,3,4 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 60 BT 3 area Gh 1 line 11 HA Smoke detector addressable Simpleks 4 Smoke check 5,6,7,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 61 BT 3 area Gh 1 line 12 HW Smoke detector addressable Simpleks 4 Smoke check 13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 62 BT 3 area Gh 1 line 12 HC Smoke detector addressable Simpleks 4 Smoke check 17,18,19,20 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 63 BT 3 area Gh 1 line 13 HY Smoke detector addressable Simpleks 4 Smoke check 17,18,19,20 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 64 BT 3 area Gh 1 line 13 HE Smoke detector addressable Simpleks 5 Smoke check 21,22,23,24,45 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 65 BT 3 area Gh 1 line 14 HG Smoke detector addressable Simpleks 5 Smoke check 26,27,28,29,30 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 66 BT 3 area Gh 1 line 14 HZA Smoke detector addressable Simpleks 4 Smoke check 31,32,33,34 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 67 BT 3 area Gh 1 line 15 HZC Smoke detector addressable Simpleks 4 Smoke check 35,36,37,338 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 68 BT 3 area Gh 1 line 15 HI Smoke detector addressable Simpleks 5 Smoke check 39,40,41,42,43 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 69 BT 3 area Gh 1 line 16 HJ Smoke detector addressable Simpleks 5 Smoke check 44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 70 BT 3 area Gh 1 line 16 HZD Smoke detector addressable Simpleks 4 Smoke check 49,50,51,52 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 71 BT 3 area Gh 1 line 17 HZZG Smoke detector addressable Simpleks 4 Smoke check 58,59,60,61 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 72 BT 3 area Gh 1 line 17 HM Smoke detector addressable Simpleks 5 Smoke check 53,54,55,56,57 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 73 BT 3 area Gh 1 line 18 HZI Smoke detector addressable Simpleks 4 Smoke check 62,63,64,65 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 74 BT 3 area Gh 1 line 18 HO Smoke detector addressable Simpleks 5 Smoke check 66,67,68,69,70 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 75 BT 3 area Gh 1 line 19 HZK Smoke detector addressable Simpleks 4 76,77,78,79 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 76 BT 3 area Gh 1 line 19 HQS Smoke detector addressable Simpleks 5 Smoke check 71,72,73,74,75 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 77 BT 3 area Gh 1 line 20 HZM Smoke detector addressable Simpleks 4 Smoke check 81,82,83,89 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 78 BT 3 area Gh 1 line 20 HS Smoke detector addressable Simpleks 4 Smoke check 84,85,86,87 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 79 BT 3 area Gh 1 line 21 HZN Smoke detector addressable Simpleks 4 Smoke check 92,93,94,95 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 80 BT 3 area Gh 1 line 21 HT Smoke detector addressable Simpleks 4 Smoke check 88,89,90,91 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 81 Pos BT2 Ruang Traning Smoke detector addressable Simpleks 3 Smoke check 6,7,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 82 Pos BT2 Ruang FCU / AHU Smoke detector addressable Simpleks 2 Smoke check 9,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 83 Pos BT2 area Lab mikro Smoke detector addressable Simpleks 10 Smoke check 11,12,13,14,15,16,17,18,19,20,21 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Heat detector addressable Simpleks 2 Hyer dryer 12,23 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 84 Pos BT2 Gudang WH kantor office Smoke detector addressable Simpleks 3 Smoke check 20,21,22 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 85 Pos BT1 Gudang Silo Smoke detector addressable Simpleks 4 Smoke check 27,28,29,30 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 86 Pos BT1 Lantai 2 Ruang Panel Smoke detector addressable Simpleks 2 Smoke check 50,51 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 87 Pos BT1 Lantai 2 kantor office ruang dekumen Smoke detector addressable Simpleks 1 Smoke check 40 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 88 Pos BT2 area panel dekat ruang traning Smoke detector addressable Simpleks 2 Smoke check 28,29 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 89 Area gudang sperpart BT 2 Smoke detector addressable Simpleks 29 Smoke check 24,25,26,27,28,29,30,31,32,33,34 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Smoke check 35,36,37,38,39,40,41,42,43,44,45 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Smoke check 46,47,48,49,50,51,52,53,54,55 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Manual call points Simpleks 1 Trigger Input 23 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal Beacon sounder Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 90 Office gudang sperpart Smoke detector addressable Simpleks 2 Smoke check 34,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 91 Ruangan Chimical Smoke detector addressable Simpleks 1 Smoke check 27 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 92 Area BT 2 Gedung putih lantai 1 Smoke detector addressable Simpleks 6 Smoke check 84,85,86,87,88,89 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal Manual call points Simpleks 2 Trigger Input 82,83 N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal Horstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal TBFA Local 1 Fisik atau sistem N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 93 Area BT 2 Gedung putih lantai 2 Smoke detector addressable Simpleks 7 Smoke check 90,91,92,93,94,95,96 N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal Manual call points Simpleks 1 Trigger Input 97 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal Horstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 94 Area BT 2 Gedung putih lantai 3 Smoke detector addressable Simpleks 5 Smoke check 98,99,100,101,102 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Manual call points Simpleks 1 Trigger Input 103 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal Horstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 95 Area BT 2 gudang WH 1 ( E ) Line 1 E1A Smoke detector addressable Simpleks 16 Smoke check 81,82,83,84,85,86,87,88,89,90 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN No KETERANGAN TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9 91,92,93,94,95,96 ✓ ✓ N/A N/A N/A N/A Sistem normal N/A N/A ✓ Line 2 E2C Smoke detector addressable Simpleks 16 Smoke check 65,66,67,68,69,70,71,72,73,74 ✓ ✓ N/A N/A N/A N/A Sistem normal N/A N/A ✓ 75,76,77,78,79,80 ✓ ✓ N/A N/A N/A N/A Sistem normal N/A N/A ✓ Line 3 E1H Smoke detector addressable Simpleks 15 Smoke check 49,50,51,52,53,54,55,56,57,58 ✓ ✓ N/A N/A N/A N/A Sistem normal N/A N/A ✓ ,59,60,61,62,63 ✓ ✓ N/A N/A N/A N/A Sistem normal N/A N/A ✓ Smoke detector rusak 1 unit dan sudah di ganti baru Line 4 E1G Smoke detector addressable Simpleks Smoke check 34,35,36,37,38,39,40,41,42,43 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ 15 sistem kembali normal 44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 5 E1E Smoke detector addressable Simpleks 15 Smoke check 17,18,19,20,21,22,23,24,25,26 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
96 Area BT 2 gudang WH1( E )
Line 6 E1C Smoke detector addressable Simpleks 15 Smoke check 2,3,4,5,6,7,8,9,10,11,12,13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Smoke detector rusak 1 unit dan sudah di ganti baru Line 7 EIA Smoke detector addressable Simpleks 10 Smoke check 97,98,99,101,102,103,14,105,106 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ sistem kembali normal 97 Gudang E2 Horstrobe Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal Manual call points Simpleks 3 Trigger Input 19,20,21 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal TBFA Local 1 Fisik N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 98 Gudang E1 Horstrobe Simpleks 5 Trigger Input 22,23,24,25,26 N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal Manual call points Simpleks 5 Trigger Input 1,2,3,4,5 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal Beacon sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal TBFA Local 1 Fisik N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 99 Area BT 2 gudang GH1 ( D ) Line 8 DJ Smoke detector addressable Simpleks 14 Smoke check 121.122.123.124.125 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 126.127.128.129.130 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 131.132.133.134 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 9 DH Smoke detector addressable Simpleks 14 Smoke check 107.108.109.110 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 111.112.113.114.115 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 116.117.118.119.120 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 10 DF Smoke detector addressable Simpleks 14 Smoke check 93,94,95,96,97,98,99,101 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 102.103.104.105.106 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 11 Smoke detector addressable Simpleks 14 Smoke check 79,80,81,82,83,84,85,86,87,88 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 89,90,91,92 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 12 DB Smoke detector addressable Simpleks 19 Smoke check 65,66,67,68,69,70,71,72,73,74,75 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 77,78,145,146,147,148,149 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 100 Area BT 2 Gudang GH 1 ( D ) Horstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal Manual call points Simpleks 6 Trigger Input 59,60,61,62,63,64 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal Beacon Sounder Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal TBFA Local 1 Fisik N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 101 Area BT 2 WH1 ( C ) Line 13 CL Smoke detector addressable Simpleks 8 Smoke check 57,58,59,60,62,62,63,64 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 13 CI Smoke detector addressable Simpleks 8 Smoke check 49,50,51,52,53,54,55,56 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 14 CN Smoke detector addressable Simpleks 8 Smoke check 33,34,35,36,37,38,39,40 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 14 CG Smoke detector addressable Simpleks 8 Smoke check 41,42,43,44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 15 CE Smoke detector addressable Simpleks 8 Smoke check 25,26,27,28,29,30,31,32 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 15 CP Smoke detector addressable Simpleks 8 Smoke check 17,18,19,20,21,22,23,24 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 16 CR Smoke detector addressable Simpleks 8 Smoke check 1,2,3,4,5,6,7,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 16 CC Smoke detector addressable Simpleks 8 Smoke check 9,10,11,12,13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 17 CT Smoke detector addressable Simpleks 5 Smoke check 140.141.142.143.144 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 17 CA Smoke detector addressable Simpleks 5 Smoke check 135.136.137.138.139 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 102 Area BT 2 WH1 ( C ) Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal Manual call points Simpleks 5 Trigger Input 65,66,67,68,69 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal Horstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 103 Area BT 2 Gudang WH 1 ( B ) Line 18 BL Smoke detector addressable Simpleks 9 Smoke check 1,2,3,4,5,6,7,8,9 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 18 BI Smoke detector addressable Simpleks 7 Smoke check 10,11,12,13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 19 BN Smoke detector addressable Simpleks 9 Smoke check 24,25,26,27,28,29,30,31,32 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 19 BG Smoke detector addressable Simpleks 7 Smoke check 17,18,19,20,21,22,23 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 20 BP Smoke detector addressable Simpleks 9 Smoke check 33,32,33,34,35,36,37,38,39,40,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 20 BE Smoke detector addressable Simpleks 7 Smoke check 42,43,44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 21 BR Smoke detector addressable Simpleks 9 Smoke check 56,57,58,59,60,61,62,63,64 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 21 BC Smoke detector addressable Simpleks 7 Smoke check 49,50,51,52,53,54,55 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 22 BA Smoke detector addressable Simpleks 5 Smoke check 65,66,67,68,69 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal Line 22 BB Smoke detector addressable Simpleks 5 Smoke check 70,71,72,73,74 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal 104 WH - 1 Gudang Arsip Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 105 WH - 1 Arsip market Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 106 WH - 1 Gudang E - 2 Manual call points Simpleks 3 Trigger Input 97,98,99 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 107 WH - 1 Gudang E - 2 Horstrobe Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN No KETERANGAN TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9 108 WH - 1 Gudang E - 1 Manual call points Simpleks 5 Trigger Input 101.102.103.104.105 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 109 WH - 1 Gudang E - 1 Horstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 110 WH - 1 Gudang E - 1 Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 111 WH - 1 Gudang E - 1 TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 112 WH - 1 Gudang E - 1 Modul output Simpleks 4 Trigger Input 106.107.108.109.110 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 113 WH - 1 Gudang D - 1 Manual call points Simpleks 5 Trigger Input 67,66,65,64,63 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 114 WH - 1 Gudang D - 1 Hornstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 115 WH - 1 Gudang D - 1 Beacon Sounder Simpleks 8 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 116 WH - 1 Gudang D - 1 TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 117 WH - 1 Gudang D - 1 Modul output Simpleks 4 Trigger Input 62,61,60,59, N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 118 WH - 1 Gudang C - 1 Manual call points Simpleks 4 Trigger Input 145.146.147.148 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 119 WH - 1 Gudang C - 1 Hornstrobe Simpleks 4 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 120 WH - 1 Gudang C - 1 Beacon Sounder Local 1 Fisik atau sistem N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 121 WH - 1 Gudang C - 1 TBFA Local 1 Trigger Input N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 122 WH - 1 gudang C - 1 Modul output Simpleks 2 Trigger Input 149.150 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 123 WH - 1 Gudang B - 1 Manual call points Simpleks 5 Trigger Input 71,72,73,74,75 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 124 WH - 1 Gudang B - 1 Hornstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 125 WH - 1 Gudang B - 1 Beacon Sounder Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 126 WH - 1 Gudang B - 1 TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 127 WH - 1 Gudang B - 1 Modul output Simpleks 2 Trigger Input 76,77 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 128 WH - 1 Ruang cas baterai Manual call points Simpleks 1 Trigger Input 49 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 129 WH - 1 Ruang cas baterai Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 130 WH - 1 Ruang cas baterai Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 131 WH - 1 Ruang Traning Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 132 WH - 1 Ruang FCU - AHU Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 133 WH - 1 Ruang Ganti Manual call points Simpleks 1 Trigger Input 4 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 134 WH - 1 Ruang Ganti Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 135 WH - 1 Ruang Ganti Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 136 WH - 1 Ruang Ganti TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 137 WH - 1 Ruang Ganti Modul output Simpleks 9 Trigger Input 12,13,14,15,16,18,19,20,21,23 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 138 WH - 1 Gudang Karton Manual call points Simpleks 1 Trigger Input 61 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 139 WH - 1 Gudang Karton Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 140 WH - 1 Ruang Lab Chemical Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 141 WH - 2 Ruang Binowing Manual call points Simpleks 5 Trigger Input 49,50,51,52,53 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 142 WH - 2 Ruang Binowing Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 143 WH - 2 Ruang Binowing Beacon Sounder Simpleks 7 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 144 WH - 2 Ruang panel Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 145 WH - 2 Ruang sample Manual call points Simpleks 1 Smoke check 40 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 146 WH - 2 Ruang sample Horstrobe Simpleks 1 Smoke check N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 147 WH - 2 Ruang Timbangan Manual call points Simpleks 1 Smoke check 39 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 148 WH - 2 Ruang Timbangan Beacon Sounder Simpleks 2 Smoke check N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 149 WH - 2 Ruang Office Beacon Sounder Simpleks 2 Smoke check N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 150 WH - 2 Ruang locker Beacon Sounder Simpleks 1 Smoke check N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 151 WH - 2 Gedung H - 1 Manual call points Simpleks 7 Trigger Input 75,76,77,78,79,80,81 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 152 WH - 2 Gedung H - 1 Hornstrobe Simpleks 7 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 153 WH - 2 Gedung H - 1 Beacon Sounder Simpleks 17 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 154 WH - 2 Gedung H - 1 TBFA Local 4 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 155 WH - 2 Gedung H - 1 Modul output Simpleks 24 Trigger Input 82,83,84,85,86,87,88,89,90,91,92 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 93,94,95,96,97,98,99,101,102 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 103.104.105.106 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 156 WH - 2 Gedung H - 2 Manual call points Simpleks 2 Trigger Input 107.108 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 157 WH - 2 Gedung H - 2 Hornstrobe Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 158 WH - 2 Gedung H - 2 Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 159 WH - 2 Gedung H - 2 TBFA Local 1 Fisik dan sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 160 WH - 2 Gedung H - 2 Modul output Simpleks 5 Trigger Input 109.110.111.112.113 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 161 WH - 2 Gedung LEMN Manual call points Simpleks 1 Trigger Input 63 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 162 Gedung putih lantai 1 Manual call points Simpleks 2 Trigger Input 82,83 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 163 Gedung putih lantai 1 Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 164 Gedung putih lantai 1 TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal 165 Gedung putih lantai 1 Modul output Simpleks 1 Trigger Input 81 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 166 Gedung putih lantai 2 Manual call points Simpleks 1 Trigger Input 97 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 167 Gedung putih lantai 2 Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 168 Gedung putih lantai 3 Manual call points Simpleks 1 Trigger Input 103 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal 169 Gedung putih lantai 3 Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 170 BT 1 Office lantai 1 Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal 171 BT 1 Office lantai 1 Modul output Simpleks 11 Trigger Input N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal 172 BT 1 Office lantai 2 Manual call points Simpleks 6 Trigger Input 16,19,21,22,23,24 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN No KETERANGAN TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9 173 BT 1 Office lantai 2 Hornstrobe Simpleks 6 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 174 BT 1 Office lantai 2 Beacon Sounder Simpleks 6 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 175 BT 1 Area Karton Manual call points Simpleks 5 Trigger Input 57,58,59,60,61 N/A N/A ✓ N/A N/A Sistem normal N/A N/A N/A ✓ 176 BT 1 Area Karton Hornstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 177 BT 1 Area Karton Beacon sounder Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 178 Area miling Manual call points Simpleks 1 Trigger Input 46 N/A N/A ✓ N/A N/A Sistem normal N/A N/A N/A ✓ 179 Area miling Beacon sounder Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 180 Area BT 1 Silo Manual call points Simpleks 4 Trigger Input 93,94,95,96 N/A N/A ✓ N/A N/A Sistem normal N/A N/A N/A ✓ 181 Area BT 1 Silo Hornstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 182 Area BT 1 Silo Beacon sounder Simpleks 16 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 183 Area BT 1 Silo TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A Sistem normal N/A ✓ ✓ ✓ 184 Area BT 1 Silo Modul output Simpleks 10 Trigger Input 97,98,99,100,101,102, N/A N/A N/A N/A N/A ✓Sistem normal N/A N/A ✓ 103.104.105.106 N/A N/A N/A N/A N/A ✓Sistem normal N/A N/A ✓ 185 Area BT 1 Ruang panel mixing Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 186 Area BT 1 Ruang panel mixing Beacon sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 187 Area BT 1 Ruang panel powder Hornstrobe Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 188 Area BT 1 Ruang panel powder Manual call points Simpleks 2 Trigger Input 54,55 N/A N/A ✓ N/A N/A Sistem normal N/A N/A N/A ✓ 189 Area BT 1 Ruang panel powder Beacon sounder Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal N/A N/A N/A ✓ 200 Area dekat powder plant control room lantai 2 Smoke detector Simpleks 8 Smoke check 20,21,22,23,24,25,26,27,28 ✓ ✓ N/A N/A N/A Sistem normal N/A N/A N/A ✓ Heat detector Simpleks 8 Hyer dryer 29,30,31,32,33,34,35,36 ✓ ✓ N/A N/A N/A Sistem normal N/A N/A N/A ✓ 201 GH0 Electro magnetic door Simpleks 1 Trigger Input N/A N/A ✓ N/A N/A Sistem normal N/A N/A N/A ✓ 202 GH1 Electro magnetic door Simpleks 3 Trigger Input N/A N/A ✓ N/A N/A Sistem normal N/A N/A N/A ✓ 203 GH2 Electro magnetic door Simpleks 2 Trigger Input N/A N/A ✓ N/A N/A Sistem normal N/A N/A N/A ✓ 204 GH3 Electro magnetic door Simpleks 5 Trigger Input N/A N/A ✓ N/A N/A Sistem normal N/A N/A N/A ✓ Sistem masih trouble di karna kan MCFA masih 205 Office GH 3 Annunciator Simpleks 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ N/A ✓ trouble
NB. PARAMETER PEMERIKSAAN EQUIPMENT FIRE ALARM
PT. WIRA SUKSES SEJATI PT. BUMITANGERANG MESINDOTAMA ( COCOA )
NO PARAMETER PEMERIKSAAN STANDAR SIMBOL 1 Lampu Led indikator Hidup / Berkedip ✓: Ok / Bagus 2 Pengetesan detector Aktip < 30 detik X : Tidak Ok / rusak 3 MPS Aktip / Mudah ditarik /Ditekan N/A : Not available 4 Horstrobe atau Alarm bell Sesuai / Suara seragam semua 5 Lampu Blitz horstrobe Hidup / Nyala 6 Modul Input / Modul output / Modul Relay Bagus / Led kedip 7 TBFA atau MCFA Bagus 8 Kondisi kabel dalam TBFA Terminasi bagus / Di rapihkan 9 Bersih Bersih / Telah di bersihkan ( MUHAMMAD HARIANTO ) ( OOM MUKAROMAH )