Checklist Maintenance

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

CHECKLIST TEST - MAINTENANCE SERVICE

Project : PT BUMITANGERANG MESINDOTAMA ( COCOA ) Mulai Pekerjaan : 28 Juli 2022


Jenis : SERVICE MAINTENANCE FIRE SYSTEM Hari/Tanggal : 7/28/2022
Plant : TANGGERANG Nama Kontraktor : PT WIRA SUKSES SEJATI
Kunjungan : 1 ( pertama )
LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN
No KETERANGAN
TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9
Panel kondisinya masih trouble di karna kan ada
1 Pos security BT 3 MCFA Simpleks 4100 Simpleks 1 N/A N/A N/A N/A N/A N/A ✓ N/A ✓
Fisik atau sistem pembongkaran di area
Onxy Simpleks 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ N/A ✓ Sulawesi dan simcard tidak terkoneksi
Panel kondisinya masih trouble di karna kan ada
2 Pos security BT 2 MCFA Simpleks 4100 Simpleks 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ N/A ✓
pembongkaran di area
3 Pos security BT 1 Annunciator Simpleks 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ N/A ✓ Sulawesi dan simcard tidak terkoneksi
Area di bongkar tampilan di panel trouble no
4 Sulawesi room BT 1 lantai 1 Smoke detector addressable Simpleks 3 Smoke check 12,7,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓
answer smoke detector, hornstrobe,mcp
5 Area lobby lantai 1 Smoke detector addressable Simpleks 4 Smoke check 4,5,52,53 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
6 Ruang office HSE Smoke detector addressable Simpleks 1 Smoke check 10 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
7 Bali room lantai 1 Smoke detector addressable Simpleks 1 Smoke check 9 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
8 HRGA Dept lantai 1 Smoke detector addressable Simpleks 1 Smoke check 55 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
9 Office lantai 2 Smoke detector addressable Simpleks 6 Smoke check 13,14,15,18,19,20 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
10 Area pantry Smoke detector addressable Simpleks 1 Smoke check 12 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
11 Papua room lantai 2 Smoke detector addressable Simpleks 1 Smoke check 16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
12 Office lantai 2 Smoke detector addressable Simpleks 13 Smoke check 21,25,26,169,170,171,172 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
173.174.175.176 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
13 Lampung room Smoke detector addressable Simpleks 2 Smoke check 27,28 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
14 Ruang projects Office lantai 2 BT 1 Smoke detector addressable Simpleks 16 Smoke check 2,3,18,21,22,24,25,26,27,28,29 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
30,31,32,33,34 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Smoke detector rusak 1 unit sudah di ganti baru
15 Area ruang ganti BT 1 lantai 1 Smoke detector addressable Simpleks 7 Smoke check 1,2,3,5,7,11,17 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓
sistem kembali normal
16 Ruang instrumen BT 1 lantai 1 Smoke detector addressable Simpleks 2 Smoke check 16,14 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
17 Ruang analisa BT 1 lantai 1 Smoke detector addressable Simpleks 2 Smoke check 10,13 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
18 Office room BT 1 lantai 1 Smoke detector addressable Simpleks 1 Smoke check 15 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
19 Area sensory room BT 1 lantai 1 Smoke detector addressable Simpleks 1 Smoke check 8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
20 Prepation Room BT 1 lantai 1 Smoke detector addressable Simpleks 1 Smoke check 9 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
21 ARC Hives room BT 1 lantai 1 Smoke detector addressable Simpleks 2 Smoke check 3,6 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Smoke detector rusak 1 unit sudah di ganti baru
22 Control room miling BT 1 lantai 1 Smoke detector addressable Simpleks 2 Smoke check 44,45 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓
sistem kembali normal
23 Area sempling BT 1 lantai 1 Manual call points Simpleks 4 Trigger Input 46,47,48,49 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
Hornstrobe Simpleks 4 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
Beacon sounder Simpleks 4 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
24 SPL SILO BT 1 lantai 1 Smoke detector addressable Simpleks 4 Smoke check 89,90,91,92 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
25 Ruang produksi silo BT 1 lantai 1 Smoke detector addressable Simpleks 11 Smoke check 110.111.112.113.114 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
115,116,117,118,119, ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
120 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
26 Area powder plant control room BT 1 lantai 2 Smoke detector addressable Simpleks 4 Smoke check 38,39,40,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
27 Area control room press Bt 1 lantai 2 Smoke detector addressable Simpleks 6 Smoke check 32,33,34,35,36,37 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Smoke detector rusak 1 unit dan sudah di ganti baru
28 Area boiler Pos BT 1 Smoke detector addressable Simpleks 1 Smoke check 41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓
sistem kembali normal
29 Area DEGBC area'bos Bt 1 lantai 2 Smoke detector addressable Simpleks 2 Smoke check 50,52 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
30 at 3 LVDP lantai 3 Smoke detector addressable Simpleks 7 Smoke check 35,36,37,38,39,40,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
31 Area winowing Bt 3 Smoke detector addressable Simpleks 5 Smoke check 44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
32 Ruang Opex BT 3 Smoke detector addressable Simpleks 3 Smoke check 49,50,51 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
33 Ruang Leporas 2v BT 3 Smoke detector addressable Simpleks 2 Smoke check 52,53 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Smoke detector rusak 1 unit dan sudah di ganti baru
34 BT 3 area plant at RM office Smoke detector addressable Simpleks 9 Smoke check 114.115.116.117.118 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓
sistem kembali normal
119.120.121.122 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
35 Area office timbangan BT 2 Smoke detector addressable Simpleks 2 Smoke check 63.128 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
36 Area office warehouse BT 3 Smoke detector addressable Simpleks 1 Smoke check 6 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
37 Area locker Bt 3 Smoke detector addressable Simpleks 1 Smoke check 4 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
38 BT 3 area Gh 1 line 1 GHIU Smoke detector addressable Simpleks 9 Smoke check 1,2,3,4,5,6,7,8,9 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
39 BT 3 area Gh 1 line 1 GH1A Smoke detector addressable Simpleks 5 Smoke check 1,2,3,4,5 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
40 BT 3 area Gh 1 line 2 GHIW Smoke detector addressable Simpleks 10 Smoke check 10,11,12,13,14,15,16,17,18,19 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
41 BT 3 area Gh 1 line 2 GH1C Smoke detector addressable Simpleks 5 Smoke check 6,7,8,9,10 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
42 BT 3 area Gh 1 line 3 GHIY Smoke detector addressable Simpleks 11 Smoke check 20,21,22,23,24,25,26,27,28,29,30 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
43 BT 3 area Gh 1 line 3 GH1E Smoke detector addressable Simpleks 6 Smoke check 11,12,13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
44 BT 3 area Gh 1 line 4 GHIA Smoke detector addressable Simpleks 11 Smoke check 31,32,33,34,35,36,37,38,39,40,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
45 BT 3 area Gh 1 line 4 GH1G Smoke detector addressable Simpleks 6 Smoke check 17,18,19,20,21,22 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN
No KETERANGAN
TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9
46 BT 3 area Gh 1 line 5 GH1Z Smoke detector addressable Simpleks 11 Smoke check 42,43,44,45,46,47,48,49,50,51,52 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
47 BT 3 area Gh 1 line 5 GH1I Smoke detector addressable Simpleks 6 Smoke check 23,24,25,26,27,28 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
48 BT 3 area Gh 1 line 6 GH1Z Smoke detector addressable Simpleks 11 Smoke check 53,54,55,56,57,58,59,60,61,62,63 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
49 BT 3 area Gh 1 line 6 GH1K Smoke detector addressable Simpleks 6 Smoke check 29,30,31,32,33,34 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Smoke detector rusak 1 unit dan sudah di ganti baru
50 BT 3 area Gh 1 line 7 GH1ZG Smoke detector addressable Simpleks Smoke check 17,18,19,20,21,22,23,24,45 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓
9 sistem kembali normal
51 BT 3 area Gh 1 line 7 GH1M Smoke detector addressable Simpleks 6 Smoke check 35,36,37,38,39,40 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
52 BT 3 area Gh 1 line 8 GH1Z1 Smoke detector addressable Simpleks 11 Smoke check 75,76,77,78,79,80,81,82,83,84,82 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
53 BT 3 area Gh 1 line 8 GH10 Smoke detector addressable Simpleks 6 Smoke check 41,42,43,44,45,46 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
54 BT 3 area Gh 1 line 9 GH1K Smoke detector addressable Simpleks 11 Smoke check 86,87,88,89,90,91,92,93,94,95,96 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
55 BT 3 area Gh 1 line 9 GH1Q Smoke detector addressable Simpleks 6 Smoke check 47,48,49,50,51,52 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
56 BT 3 area Gh 1 line 10 GH1ZL Smoke detector addressable Simpleks 9 Smoke check 97,98,99,100,101,102,103,104,105 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
57 BT 3 area Gh 1 line 10 GH1R Smoke detector addressable Simpleks 5 Smoke check 53,54,55,56,57 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
58 BT 3 area Gh 1 line 10 GH1T Smoke detector addressable Simpleks 5 Smoke check 58,59,60,61,62 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
59 BT 3 area Gh 1 line 11 HU Smoke detector addressable Simpleks 4 Smoke check 1,2,3,4 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
60 BT 3 area Gh 1 line 11 HA Smoke detector addressable Simpleks 4 Smoke check 5,6,7,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
61 BT 3 area Gh 1 line 12 HW Smoke detector addressable Simpleks 4 Smoke check 13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
62 BT 3 area Gh 1 line 12 HC Smoke detector addressable Simpleks 4 Smoke check 17,18,19,20 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
63 BT 3 area Gh 1 line 13 HY Smoke detector addressable Simpleks 4 Smoke check 17,18,19,20 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
64 BT 3 area Gh 1 line 13 HE Smoke detector addressable Simpleks 5 Smoke check 21,22,23,24,45 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
65 BT 3 area Gh 1 line 14 HG Smoke detector addressable Simpleks 5 Smoke check 26,27,28,29,30 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
66 BT 3 area Gh 1 line 14 HZA Smoke detector addressable Simpleks 4 Smoke check 31,32,33,34 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
67 BT 3 area Gh 1 line 15 HZC Smoke detector addressable Simpleks 4 Smoke check 35,36,37,338 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
68 BT 3 area Gh 1 line 15 HI Smoke detector addressable Simpleks 5 Smoke check 39,40,41,42,43 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
69 BT 3 area Gh 1 line 16 HJ Smoke detector addressable Simpleks 5 Smoke check 44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
70 BT 3 area Gh 1 line 16 HZD Smoke detector addressable Simpleks 4 Smoke check 49,50,51,52 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
71 BT 3 area Gh 1 line 17 HZZG Smoke detector addressable Simpleks 4 Smoke check 58,59,60,61 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
72 BT 3 area Gh 1 line 17 HM Smoke detector addressable Simpleks 5 Smoke check 53,54,55,56,57 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
73 BT 3 area Gh 1 line 18 HZI Smoke detector addressable Simpleks 4 Smoke check 62,63,64,65 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
74 BT 3 area Gh 1 line 18 HO Smoke detector addressable Simpleks 5 Smoke check 66,67,68,69,70 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
75 BT 3 area Gh 1 line 19 HZK Smoke detector addressable Simpleks 4 76,77,78,79 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
76 BT 3 area Gh 1 line 19 HQS Smoke detector addressable Simpleks 5 Smoke check 71,72,73,74,75 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
77 BT 3 area Gh 1 line 20 HZM Smoke detector addressable Simpleks 4 Smoke check 81,82,83,89 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
78 BT 3 area Gh 1 line 20 HS Smoke detector addressable Simpleks 4 Smoke check 84,85,86,87 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
79 BT 3 area Gh 1 line 21 HZN Smoke detector addressable Simpleks 4 Smoke check 92,93,94,95 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
80 BT 3 area Gh 1 line 21 HT Smoke detector addressable Simpleks 4 Smoke check 88,89,90,91 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
81 Pos BT2 Ruang Traning Smoke detector addressable Simpleks 3 Smoke check 6,7,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
82 Pos BT2 Ruang FCU / AHU Smoke detector addressable Simpleks 2 Smoke check 9,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
83 Pos BT2 area Lab mikro Smoke detector addressable Simpleks 10 Smoke check 11,12,13,14,15,16,17,18,19,20,21 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Heat detector addressable Simpleks 2 Hyer dryer 12,23 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
84 Pos BT2 Gudang WH kantor office Smoke detector addressable Simpleks 3 Smoke check 20,21,22 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
85 Pos BT1 Gudang Silo Smoke detector addressable Simpleks 4 Smoke check 27,28,29,30 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
86 Pos BT1 Lantai 2 Ruang Panel Smoke detector addressable Simpleks 2 Smoke check 50,51 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
87 Pos BT1 Lantai 2 kantor office ruang dekumen Smoke detector addressable Simpleks 1 Smoke check 40 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
88 Pos BT2 area panel dekat ruang traning Smoke detector addressable Simpleks 2 Smoke check 28,29 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
89 Area gudang sperpart BT 2 Smoke detector addressable Simpleks 29 Smoke check 24,25,26,27,28,29,30,31,32,33,34 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Smoke check 35,36,37,38,39,40,41,42,43,44,45 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Smoke check 46,47,48,49,50,51,52,53,54,55 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Manual call points Simpleks 1 Trigger Input 23 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
Beacon sounder Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
90 Office gudang sperpart Smoke detector addressable Simpleks 2 Smoke check 34,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
91 Ruangan Chimical Smoke detector addressable Simpleks 1 Smoke check 27 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
92 Area BT 2 Gedung putih lantai 1 Smoke detector addressable Simpleks 6 Smoke check 84,85,86,87,88,89 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
Manual call points Simpleks 2 Trigger Input 82,83 N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
Horstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
TBFA Local 1 Fisik atau sistem N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
93 Area BT 2 Gedung putih lantai 2 Smoke detector addressable Simpleks 7 Smoke check 90,91,92,93,94,95,96 N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
Manual call points Simpleks 1 Trigger Input 97 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
Horstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
94 Area BT 2 Gedung putih lantai 3 Smoke detector addressable Simpleks 5 Smoke check 98,99,100,101,102 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Manual call points Simpleks 1 Trigger Input 103 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
Horstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
95 Area BT 2 gudang WH 1 ( E )
Line 1 E1A Smoke detector addressable Simpleks 16 Smoke check 81,82,83,84,85,86,87,88,89,90 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN
No KETERANGAN
TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9
91,92,93,94,95,96 ✓ ✓ N/A N/A N/A N/A Sistem normal
N/A N/A ✓
Line 2 E2C Smoke detector addressable Simpleks 16 Smoke check 65,66,67,68,69,70,71,72,73,74 ✓ ✓ N/A N/A N/A N/A Sistem normal
N/A N/A ✓
75,76,77,78,79,80 ✓ ✓ N/A N/A N/A N/A Sistem normal
N/A N/A ✓
Line 3 E1H Smoke detector addressable Simpleks 15 Smoke check 49,50,51,52,53,54,55,56,57,58 ✓ ✓ N/A N/A N/A N/A Sistem normal
N/A N/A ✓
,59,60,61,62,63 ✓ ✓ N/A N/A N/A N/A Sistem normal
N/A N/A ✓
Smoke detector rusak 1 unit dan sudah di ganti baru
Line 4 E1G Smoke detector addressable Simpleks Smoke check 34,35,36,37,38,39,40,41,42,43 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓
15 sistem kembali normal
44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 5 E1E Smoke detector addressable Simpleks 15 Smoke check 17,18,19,20,21,22,23,24,25,26 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal

96 Area BT 2 gudang WH1( E )


Line 6 E1C Smoke detector addressable Simpleks 15 Smoke check 2,3,4,5,6,7,8,9,10,11,12,13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Smoke detector rusak 1 unit dan sudah di ganti baru
Line 7 EIA Smoke detector addressable Simpleks 10 Smoke check 97,98,99,101,102,103,14,105,106 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓
sistem kembali normal
97 Gudang E2 Horstrobe Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
Manual call points Simpleks 3 Trigger Input 19,20,21 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
TBFA Local 1 Fisik N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
98 Gudang E1 Horstrobe Simpleks 5 Trigger Input 22,23,24,25,26 N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
Manual call points Simpleks 5 Trigger Input 1,2,3,4,5 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
Beacon sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
TBFA Local 1 Fisik N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
99 Area BT 2 gudang GH1 ( D )
Line 8 DJ Smoke detector addressable Simpleks 14 Smoke check 121.122.123.124.125 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
126.127.128.129.130 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
131.132.133.134 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 9 DH Smoke detector addressable Simpleks 14 Smoke check 107.108.109.110 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
111.112.113.114.115 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
116.117.118.119.120 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 10 DF Smoke detector addressable Simpleks 14 Smoke check 93,94,95,96,97,98,99,101 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
102.103.104.105.106 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 11 Smoke detector addressable Simpleks 14 Smoke check 79,80,81,82,83,84,85,86,87,88 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
89,90,91,92 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 12 DB Smoke detector addressable Simpleks 19 Smoke check 65,66,67,68,69,70,71,72,73,74,75 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
77,78,145,146,147,148,149 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
100 Area BT 2 Gudang GH 1 ( D ) Horstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
Manual call points Simpleks 6 Trigger Input 59,60,61,62,63,64 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
Beacon Sounder Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
TBFA Local 1 Fisik N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
101 Area BT 2 WH1 ( C )
Line 13 CL Smoke detector addressable Simpleks 8 Smoke check 57,58,59,60,62,62,63,64 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 13 CI Smoke detector addressable Simpleks 8 Smoke check 49,50,51,52,53,54,55,56 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 14 CN Smoke detector addressable Simpleks 8 Smoke check 33,34,35,36,37,38,39,40 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 14 CG Smoke detector addressable Simpleks 8 Smoke check 41,42,43,44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 15 CE Smoke detector addressable Simpleks 8 Smoke check 25,26,27,28,29,30,31,32 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 15 CP Smoke detector addressable Simpleks 8 Smoke check 17,18,19,20,21,22,23,24 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 16 CR Smoke detector addressable Simpleks 8 Smoke check 1,2,3,4,5,6,7,8 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 16 CC Smoke detector addressable Simpleks 8 Smoke check 9,10,11,12,13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 17 CT Smoke detector addressable Simpleks 5 Smoke check 140.141.142.143.144 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 17 CA Smoke detector addressable Simpleks 5 Smoke check 135.136.137.138.139 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
102 Area BT 2 WH1 ( C ) Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
Manual call points Simpleks 5 Trigger Input 65,66,67,68,69 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
Horstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
103 Area BT 2 Gudang WH 1 ( B )
Line 18 BL Smoke detector addressable Simpleks 9 Smoke check 1,2,3,4,5,6,7,8,9 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 18 BI Smoke detector addressable Simpleks 7 Smoke check 10,11,12,13,14,15,16 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 19 BN Smoke detector addressable Simpleks 9 Smoke check 24,25,26,27,28,29,30,31,32 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 19 BG Smoke detector addressable Simpleks 7 Smoke check 17,18,19,20,21,22,23 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 20 BP Smoke detector addressable Simpleks 9 Smoke check 33,32,33,34,35,36,37,38,39,40,41 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 20 BE Smoke detector addressable Simpleks 7 Smoke check 42,43,44,45,46,47,48 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 21 BR Smoke detector addressable Simpleks 9 Smoke check 56,57,58,59,60,61,62,63,64 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 21 BC Smoke detector addressable Simpleks 7 Smoke check 49,50,51,52,53,54,55 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 22 BA Smoke detector addressable Simpleks 5 Smoke check 65,66,67,68,69 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
Line 22 BB Smoke detector addressable Simpleks 5 Smoke check 70,71,72,73,74 ✓ ✓ N/A N/A N/A N/A N/A N/A ✓ Sistem normal
104 WH - 1 Gudang Arsip Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
105 WH - 1 Arsip market Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
106 WH - 1 Gudang E - 2 Manual call points Simpleks 3 Trigger Input 97,98,99 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
107 WH - 1 Gudang E - 2 Horstrobe Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN
No KETERANGAN
TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9
108 WH - 1 Gudang E - 1 Manual call points Simpleks 5 Trigger Input 101.102.103.104.105 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
109 WH - 1 Gudang E - 1 Horstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
110 WH - 1 Gudang E - 1 Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
111 WH - 1 Gudang E - 1 TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
112 WH - 1 Gudang E - 1 Modul output Simpleks 4 Trigger Input 106.107.108.109.110 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
113 WH - 1 Gudang D - 1 Manual call points Simpleks 5 Trigger Input 67,66,65,64,63 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
114 WH - 1 Gudang D - 1 Hornstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
115 WH - 1 Gudang D - 1 Beacon Sounder Simpleks 8 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
116 WH - 1 Gudang D - 1 TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
117 WH - 1 Gudang D - 1 Modul output Simpleks 4 Trigger Input 62,61,60,59, N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
118 WH - 1 Gudang C - 1 Manual call points Simpleks 4 Trigger Input 145.146.147.148 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
119 WH - 1 Gudang C - 1 Hornstrobe Simpleks 4 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
120 WH - 1 Gudang C - 1 Beacon Sounder Local 1 Fisik atau sistem N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
121 WH - 1 Gudang C - 1 TBFA Local 1 Trigger Input N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
122 WH - 1 gudang C - 1 Modul output Simpleks 2 Trigger Input 149.150 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
123 WH - 1 Gudang B - 1 Manual call points Simpleks 5 Trigger Input 71,72,73,74,75 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
124 WH - 1 Gudang B - 1 Hornstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
125 WH - 1 Gudang B - 1 Beacon Sounder Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
126 WH - 1 Gudang B - 1 TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
127 WH - 1 Gudang B - 1 Modul output Simpleks 2 Trigger Input 76,77 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
128 WH - 1 Ruang cas baterai Manual call points Simpleks 1 Trigger Input 49 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
129 WH - 1 Ruang cas baterai Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
130 WH - 1 Ruang cas baterai Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
131 WH - 1 Ruang Traning Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
132 WH - 1 Ruang FCU - AHU Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
133 WH - 1 Ruang Ganti Manual call points Simpleks 1 Trigger Input 4 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
134 WH - 1 Ruang Ganti Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
135 WH - 1 Ruang Ganti Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
136 WH - 1 Ruang Ganti TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
137 WH - 1 Ruang Ganti Modul output Simpleks 9 Trigger Input 12,13,14,15,16,18,19,20,21,23 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
138 WH - 1 Gudang Karton Manual call points Simpleks 1 Trigger Input 61 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
139 WH - 1 Gudang Karton Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
140 WH - 1 Ruang Lab Chemical Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
141 WH - 2 Ruang Binowing Manual call points Simpleks 5 Trigger Input 49,50,51,52,53 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
142 WH - 2 Ruang Binowing Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
143 WH - 2 Ruang Binowing Beacon Sounder Simpleks 7 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
144 WH - 2 Ruang panel Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
145 WH - 2 Ruang sample Manual call points Simpleks 1 Smoke check 40 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
146 WH - 2 Ruang sample Horstrobe Simpleks 1 Smoke check N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
147 WH - 2 Ruang Timbangan Manual call points Simpleks 1 Smoke check 39 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
148 WH - 2 Ruang Timbangan Beacon Sounder Simpleks 2 Smoke check N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
149 WH - 2 Ruang Office Beacon Sounder Simpleks 2 Smoke check N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
150 WH - 2 Ruang locker Beacon Sounder Simpleks 1 Smoke check N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
151 WH - 2 Gedung H - 1 Manual call points Simpleks 7 Trigger Input 75,76,77,78,79,80,81 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
152 WH - 2 Gedung H - 1 Hornstrobe Simpleks 7 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
153 WH - 2 Gedung H - 1 Beacon Sounder Simpleks 17 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
154 WH - 2 Gedung H - 1 TBFA Local 4 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
155 WH - 2 Gedung H - 1 Modul output Simpleks 24 Trigger Input 82,83,84,85,86,87,88,89,90,91,92 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
93,94,95,96,97,98,99,101,102 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
103.104.105.106 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
156 WH - 2 Gedung H - 2 Manual call points Simpleks 2 Trigger Input 107.108 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
157 WH - 2 Gedung H - 2 Hornstrobe Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
158 WH - 2 Gedung H - 2 Beacon Sounder Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
159 WH - 2 Gedung H - 2 TBFA Local 1 Fisik dan sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
160 WH - 2 Gedung H - 2 Modul output Simpleks 5 Trigger Input 109.110.111.112.113 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
161 WH - 2 Gedung LEMN Manual call points Simpleks 1 Trigger Input 63 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
162 Gedung putih lantai 1 Manual call points Simpleks 2 Trigger Input 82,83 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
163 Gedung putih lantai 1 Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
164 Gedung putih lantai 1 TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ ✓ ✓ Sistem normal
165 Gedung putih lantai 1 Modul output Simpleks 1 Trigger Input 81 N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
166 Gedung putih lantai 2 Manual call points Simpleks 1 Trigger Input 97 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
167 Gedung putih lantai 2 Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
168 Gedung putih lantai 3 Manual call points Simpleks 1 Trigger Input 103 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
169 Gedung putih lantai 3 Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
170 BT 1 Office lantai 1 Beacon Sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ N/A N/A N/A ✓ Sistem normal
171 BT 1 Office lantai 1 Modul output Simpleks 11 Trigger Input N/A N/A N/A N/A N/A ✓ N/A ✓ ✓ Sistem normal
172 BT 1 Office lantai 2 Manual call points Simpleks 6 Trigger Input 16,19,21,22,23,24 N/A N/A ✓ N/A N/A N/A N/A N/A ✓ Sistem normal
LOKASI AREA MERK JUMLAH METODE NO PARAMETER PEMERIKSAAN
No KETERANGAN
TERPASANG NAMA ALAT ALARM TYPE EQUIPMENT PENGETESAN ADDRESS 1 2 3 4 5 6 7 8 9
173 BT 1 Office lantai 2 Hornstrobe Simpleks 6 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
174 BT 1 Office lantai 2 Beacon Sounder Simpleks 6 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
175 BT 1 Area Karton Manual call points Simpleks 5 Trigger Input 57,58,59,60,61 N/A N/A ✓ N/A N/A Sistem normal
N/A N/A N/A ✓
176 BT 1 Area Karton Hornstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
177 BT 1 Area Karton Beacon sounder Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
178 Area miling Manual call points Simpleks 1 Trigger Input 46 N/A N/A ✓ N/A N/A Sistem normal
N/A N/A N/A ✓
179 Area miling Beacon sounder Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
180 Area BT 1 Silo Manual call points Simpleks 4 Trigger Input 93,94,95,96 N/A N/A ✓ N/A N/A Sistem normal
N/A N/A N/A ✓
181 Area BT 1 Silo Hornstrobe Simpleks 5 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
182 Area BT 1 Silo Beacon sounder Simpleks 16 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
183 Area BT 1 Silo TBFA Local 1 Fisik atau sistem N/A N/A N/A N/A N/A Sistem normal
N/A ✓ ✓ ✓
184 Area BT 1 Silo Modul output Simpleks 10 Trigger Input 97,98,99,100,101,102, N/A N/A N/A N/A N/A ✓Sistem normal
N/A N/A ✓
103.104.105.106 N/A N/A N/A N/A N/A ✓Sistem normal
N/A N/A ✓
185 Area BT 1 Ruang panel mixing Hornstrobe Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
186 Area BT 1 Ruang panel mixing Beacon sounder Simpleks 1 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
187 Area BT 1 Ruang panel powder Hornstrobe Simpleks 2 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
188 Area BT 1 Ruang panel powder Manual call points Simpleks 2 Trigger Input 54,55 N/A N/A ✓ N/A N/A Sistem normal
N/A N/A N/A ✓
189 Area BT 1 Ruang panel powder Beacon sounder Simpleks 3 Trigger Input N/A N/A N/A ✓ ✓ Sistem normal
N/A N/A N/A ✓
200 Area dekat powder plant control room lantai 2 Smoke detector Simpleks 8 Smoke check 20,21,22,23,24,25,26,27,28 ✓ ✓ N/A N/A N/A Sistem normal
N/A N/A N/A ✓
Heat detector Simpleks 8 Hyer dryer 29,30,31,32,33,34,35,36 ✓ ✓ N/A N/A N/A Sistem normal
N/A N/A N/A ✓
201 GH0 Electro magnetic door Simpleks 1 Trigger Input N/A N/A ✓ N/A N/A Sistem normal
N/A N/A N/A ✓
202 GH1 Electro magnetic door Simpleks 3 Trigger Input N/A N/A ✓ N/A N/A Sistem normal
N/A N/A N/A ✓
203 GH2 Electro magnetic door Simpleks 2 Trigger Input N/A N/A ✓ N/A N/A Sistem normal
N/A N/A N/A ✓
204 GH3 Electro magnetic door Simpleks 5 Trigger Input N/A N/A ✓ N/A N/A Sistem normal
N/A N/A N/A ✓
Sistem masih trouble di karna kan MCFA masih
205 Office GH 3 Annunciator Simpleks 1 Fisik atau sistem N/A N/A N/A N/A N/A N/A ✓ N/A ✓
trouble

NB. PARAMETER PEMERIKSAAN EQUIPMENT FIRE ALARM

PT. WIRA SUKSES SEJATI PT. BUMITANGERANG MESINDOTAMA ( COCOA )


NO PARAMETER PEMERIKSAAN STANDAR SIMBOL
1 Lampu Led indikator Hidup / Berkedip ✓: Ok / Bagus
2 Pengetesan detector Aktip < 30 detik X : Tidak Ok / rusak
3 MPS Aktip / Mudah ditarik /Ditekan N/A : Not available
4 Horstrobe atau Alarm bell Sesuai / Suara seragam semua
5 Lampu Blitz horstrobe Hidup / Nyala
6 Modul Input / Modul output / Modul Relay Bagus / Led kedip
7 TBFA atau MCFA Bagus
8 Kondisi kabel dalam TBFA Terminasi bagus / Di rapihkan
9 Bersih Bersih / Telah di bersihkan ( MUHAMMAD HARIANTO ) ( OOM MUKAROMAH )