M O D U L A R T H R E E - P H A S E U P S S YS T E M S
—
Technological innovation
and energy saving in action
The DPA 250 S4 online double conversion modular uninterruptible
power supply (UPS) represents the latest technological innovation.
The DPA 250 S4 has a high-efficiency, modular This modular UPS is based on decentralized
architecture that offers best reliability for envi- parallel architecture (DPA™), where every UPS
ronmentally conscious organizations that also module is practically its own UPS, having all the
need zero downtime and low cost of ownership. essential functional units needed for indepen-
The DPA 250 S4 is specially designed for critical, dent operation. DPA increases system reliability
high-density computing environments such as and availability compared to other modular UPS
small- to medium-sized data centers. solutions in the market, as there is inherent re-
dundancy between the UPS modules on all func-
The DPA 250 S4 sets the standard for the next tional levels.
decade of UPS progress with advanced features
such as its transformer-free IGBT converters that The DPA 250 S4 is specially designed for critical,
feature three-level topology with interleaving high-density computing environments such as:
controls to enable market-leading efficiency of • Small- to medium-sized data centers
97.6 percent for the UPS module. This high effi- • Commercial buildings and general IT
ciency reduces operational costs and minimizes applications
environmental impact. • Healthcare facilities
• Railway signaling applications and airports
—
High efficiency reduces total cost
of ownership (TCO)
— Selecting a UPS with high efficiency saves opera- Featuring superior 97.6 percent UPS module ef-
01
The DPA 250 S4 sig- tional expenditures over the service lifetime and ficiency and 97.4 percent system efficiency, the
nificantly reduce your minimizes the impact it has on the environment. DPA 250 S4 reduces energy losses that create
energy costs over time.
For example, with a 250 Power losses are pure overhead costs and the pure costs as direct electricity spend and costs
kW load, you can have DPA 250 S4 can reduce those losses by more than for cooling. Thanks to three-level interleaved
direct losses reduced by
more than 500 MWh over 30 percent compared to similar products in the technology, the DPA 250 S4 achieves an efficiency
10 years, which at cur- market. of over 97 percent in a wide operating range,
rent price of electricity
(0.1 EUR/kWh) results in when the load is between 25 and 75 percent of
savings of 50,000 EUR. nominal capacity.
With a reduced need for
cooling and optimized
electrical infrastructure,
savings are even greater.
1,200,000
Direct
energy savings
> 500 MWh
over 10 years
1,000,000
Direct
energy savings
> 280 MWh
over 10 years
800,000
600,000
400,000
Energy losses (kWh)
200,000
0
Year 1 Year 3 Year 5 Year 10
ABB’s DPA 250 S4 (97.4% efficiency) Alternative 1 (96,0% efficiency) Alternative 2 (95,0% efficiency)
—
01
4 D PA 2 5 0 S 4 ( 5 0 K W – 1 , 5 0 0 K W ) T H E M O S T E N E R G Y- L E A N U P S O N T H E M A R K E T
—
Xtra VFI – double conversion mode maximizes DPA 250 S4 can step up the system efficiency by
01
Superior double conver- efficiency under low-load conditions optimizing the number of modules used in double
sion efficiency helps to
Under operating conditions where the load is low conversion mode to feed the load. In case of a
decrease costs of opera-
tion. The Xtra VFI feature compared to UPS total capacity, efficiency typi- load step, more modules are switched automati-
boosts efficiency when
cally suffers and relative power losses are in- cally in milliseconds to online mode to secure the
the UPS operates with
low load compared to creased. Under these conditions, by using ABB’s critical load.
nominal capacity.
intelligent Xtra VFI – double conversion mode, the
98.0
97.5
97.0
97% efficiency reached
through wide operating range,
typical for majority of applications
96.5
96.0
Xtra VFI function
increases
efficiency when
load is low
95.5
Efficiency (%)
95.0
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
—
01
5
—
Uninterruptable power
– scalable from 50 kW up to 1.5 MW
—
01 A benefit of a modular UPS is that capacity can be 250 kW N+1 redundant power in one UPS cabinet
50 kW power in easily scaled up or down. UPS system power can The DPA 250 S4 250 kW cabinet can host up to six
one UPS module
— be optimized to match the load and upgraded 50 kW modules for 250 kW N+1 redundant power.
02 easily if power demand increases. The same Modules are easy to slide in and slide out. Featur-
1,500 kW power in
one UPS system power protection concept can be used by loads ing smart and secure power connectors, the DPA
— with different power demand characteristics. 250 modules can be removed, or added, while
03
DPA – delivering almost This makes things easy for operations personnel other UPS modules in the system support the
infinite reliability and equipment maintenance. load in double conversion mode.
and availability
DPA 250 S4
50 kW UPS module
Up to (5+1) x 50 kW
~ =
= ~
= Control logic
= Display
Up to 6 x 250 kW frames in parallel
— —
01 02
—
03
6 D PA 2 5 0 S 4 ( 5 0 K W – 1 , 5 0 0 K W ) T H E M O S T E N E R G Y- L E A N U P S O N T H E M A R K E T
—
Full flexibility to meet a variety
of installation schemes
Up to 6 x 50 kW
UPS module
Integrated UPS module with
all UPS essential functions:
rectifier, inverter, static
DC (battery) breakers bypass, control logic and
DC breakers for energy display.
storage connection on
each module separately.
Output isolation switch
Included in the standard
Maintenance bypass configuration to allow
(optional) disconnection of complete
Integrated MBS is available UPS cabinet from load
as option for enhanced supply line.
service ability with single
frame installations.
Connectivity section
Two slots for connectivity
I/O section and DC wiring cards, eg. SNMP web card
Wiring area has good space and relay board. USB and
for service. Single and dual RS-232 comm. ports.
input feed supported as well Building alarm inputs / relay
as common or separate outputs. Connection point
battery. Top or bottom for parallel system
cable entry supported. communication cable.
7
—
Maximized availability with
decentralized parallel architecture DPA™
24
7
— With DPA, the UPS is modularized, and each mod- Online swappable module for continuous uptime
01 Fail-safe
operation for high ule has all the hardware and software needed for DPA architecture enables UPS modules to operate
power applications autonomous operation: rectifier, inverter, battery completely independently of each other. This
converter, static bypass switch, back-feed protec- means that in case one UPS module needs to be
tion, control logic, display, and mimic diagram for removed or added to the system, this can be man-
monitoring and control. A module’s output is not aged fast and seamlessly.
affected by failures elsewhere in the modular UPS
system. If one module is lost, the others take up The DPA 250 S4 has a very robust design and fea-
its load. In other words, a multimodule system is tures strong and practical handles. It is only pos-
fault tolerant and there are no single points of sible to insert modules into the rack in the correct
failure. Uptime is guaranteed, and availability is orientation and the slide rails have mechanical
maximized. stoppers to stop the module from sliding out too
—
01
8 D PA 2 5 0 S 4 ( 5 0 K W – 1 , 5 0 0 K W ) T H E M O S T E N E R G Y- L E A N U P S O N T H E M A R K E T
—
Easy to operate
– fast and secure to maintain
—
ABB – best quality for products
and services
11
—
—
Technical specification
Technical specification
GENERAL DATA
System power range 50 - 1,500 kW
Nominal power per module 50 kW
Nominal power / frame 250 kW (N+1)
Number of UPS modules 5+1
Topology Online double conversion
Parallel configuration Up to 30 modules
Cable entry Top or bottom
Output power factor 1.0
Serviceability Only frontal access needed
Back-feed protection Built-in as standard
INPUT
Nominal input voltage 380 / 400 / 415 VAC
Voltage tolerance (referred to 400 V) - 40% at partial loads
Current distortion THDi <2.8%
Frequency range 35 – 70 Hz
Power factor 0.99
Walk in / soft start Yes
OUTPUT
Rated output voltage 380 / 400 / 415 VAC
Voltage tolerance (referred to 400 V) ± 2.0%
Voltage distortion THDU <2.0%
Frequency 50 or 60 Hz (selectable)
Rater power factor 1.0
EFFICIENCY
Module efficiency Up to 97.6%
Overall system efficiency Up to 97.4%
In eco-mode Up to 99%
ENVIRONMENT
Protection rating IP 20 (IP 21 optional)
Storage temperature -25 °C to +70 °C
Operating temperature 0°C to +40°C
Altitude (above sea level) 1,000 m w/o derating
BATTERIES
Types VRLA, open cells, NiCd and Li-Ion
Battery charger Decentralized charger per module
COMMUNICATIONS
User interface Graphical touch screen (one per frame as standard)
Decentralized LCD and mimic diagram (one per module as standard)
Communication ports Communication ports USB, RS-232, potential-free contacts, SNMP (optional)
Customer interface Remote shutdown, gen-set interface, external bypass contact
COMPLIANCY
Safety IEC / EN 62040-1
EMC IEC / EN 62040-2
Performance IEC / EN 62040-3
Manufacturing ISO 9001:2015, ISO 14001:2015, OHSAS18001
DIMENSIONS
Weight (without modules / without batteries) 270 kg
Weight module 68 kg
Dimensions w x h x d 791 x 1975 x 923 mm
—
abb.com/ups