Problem Example of Pneumatic Conveying System
Problem Example of Pneumatic Conveying System
Case studies
Part II: Coarse material
17.1 Introduction
For this case study a material has been chosen that has no natural dense phase convey-
ing capability and so can only be conveyed in dilute phase suspension flow in a conven-
tional pneumatic conveying system. The magnesium sulphate had a mean particle size of
about 225 m and so de-aerated very rapidly. The bulk density of the material was about
1010 kg/m3 and the particle density 2350 kg/m3. As with dense phase conveying, the min-
imum conveying air velocity for a material is a critical design parameter, but unlike dense
phase conveying there is no significant change in its value with solids loading ratio.
Data on the pneumatic conveying of magnesium sulphate was presented in Chapter 12.
The material was conveyed through pipeline no. 6 (Figure 12.24) and the conveying
characteristics were presented in Figure 12.23d. It was reported (Section 12.2.6.4) that
the minimum conveying air velocity for the material was about 14 m/s. Tests were car-
ried out with conveying line pressure drop values up to 1.8 bar and the maximum value
of solids loading ratio that could be achieved was about 10.
Pipeline details
Length 95 m
Bore 105 mm
Bends 9 90°
D/d 12
8
6
Material mass flow rate (tonne/h)
1.0 5
7
No go area
6 0.8 a 4
5.65 b
5
3
0.6
4
3 2
0.4
2
1
1 0.2
0.33
0
0.15 0.20 0.25 0.30 0.35 0.40
Air mass flow rate (kg/s)
Figure 17.2 Conveying characteristics for magnesium sulphate in pipeline no. 15.
24
16
12
0
0 4 8 12 16 20
Conveying line inlet air velocity (m/s)
17.2.3 Summary
Design duty
Material Magnesium sulphate
Mean particle size 225 m
Bulk density b 1010 kg/m3
Particle density p 2350 kg/m3
Pipeline
Horizontal h 300 m
Vertical v 25 m
Bends b 7 90°
Capability
.
Material flow rate mp 40 tonne/h
Minimum air velocity Cmin 14 m/s
Air supply Blower
Delivery pressure p 1.0 bar gauge
Pipeline inlet pressure p1 0.85 bar gauge
Pipeline pressure drop p 0.85 bar
Pipeline inlet velocity C1 1.2 Cmin 17 m/s
398 PNEUMATIC CONVEYING DESIGN GUIDE
Determine
Pipeline bore d.
Free air delivered V0
Power required P
17.3 Procedure
The location of the equivalent operating point on the conveying characteristics for the
test pipeline needs to be established first, taking account of the pressure and air flow
rate requirements. Scaling is conveniently carried out in two stages. In the first stage
scaling is with respect to conveying distance, and this includes both pipeline orientation
and bends. In the second stage the scaling is with respect to pipeline bore. Air only
pressure drop values need to be established and so this procedure is also included.
.
where ma is the air mass flow rate (kg/s); p1, the conveying line inlet air pressure
(185 kN/m2 abs); d, the pipeline bore (0.105 m); C1, the conveying line inlet air velocity
(17 m/s) and T1, the conveying line inlet air temperature (288 K (15°C)).
Substituting these values in Equation (17.1) gives
.
ma 0.330 kg/s
This operating point is located on Figure 17.2 as point (a) and it will be seen that it is
approximately 20 per cent in-board from the conveying limit.
0.5
1.34m˙ a2 bar
pa 1.0 4 1.0 (17.2)
d 105
4 0.0045 95
(9 0.2) 18.1
0.105
Substituting this value, the air flow rate of 0.330 kg/s and the pipeline bore of 0.105 m
into Equation (17.2) gives:
From this it will be seen that the air only pressure drop is quite significant for dilute
phase flow. This value of pressure drop is automatically included in the conveying
characteristics in Figure 17.2. A constant pressure drop line of 0.103 bar, if included
on the plot, would strike the horizontal axis at an air flow rate of 0.330 kg/s. It also
means that at the operating point only 0.8500.103 0.747 bar is used for conveying
material. This value will decrease with increase in pipeline length.
4 0.0045 325
(7 0.2) 57.1
0.105
Substituting this value, the air flow rate of 0.330 kg/s and the pipeline bore of 0.105 m
into Equation (17.2) gives:
This represents an increase in air only pressure drop of 0.298 0.103 0.195 bar. This
means that instead of having 0.747 bar for conveying material, it is now reduced to
0.747 0.195 0.552 bar. This represents a 26 per cent reduction in available pressure
drop and so this will have a very significant effect on the material flow rate that can be
achieved. This is in addition to the reduction as a consequence of scaling to a longer
pipeline.
To achieve the 15 tonne/h in the plant pipeline, however, a much larger bore pipeline
will be required and this will improve the situation considerably. When the conveying
characteristics are scaled in total these features can be seen, as with Figures 14.1, 14.4
400 PNEUMATIC CONVEYING DESIGN GUIDE
and 14.5. When only a single point is used the intermediate stage of the data scaled to
the plant pipeline, of the test pipeline bore, is not available. This means that a value for
the plant pipeline bore needs to be selected at this point. If the value chosen does not
meet the required duty the calculation will have to return to this point with an updated
value. For 15 tonne/h a bore of 250 mm will be selected.
4 0.0045 325
(7 0.2) 24.8
0.25
For the larger bore of pipeline a new air flow rate will be required. This can either be
determined by using Equation (17.1), as for the test pipeline, or scaling the 0.330 kg/s
for the test pipeline in proportion to the larger pipe section area. Either way the new air
flow rate will come to 1.87 kg/s.
Substituting the new value for , the new air flow rate of 1.87 kg/s and the pipeline
bore of 0.250 m into Equation (17.2) gives:
The original operating point on the material conveying characteristics on Figure 17.2
was set at a pressure drop of 0.85 bar (point a). For the plant pipeline the air only pres-
sure drop is 0.139 bar whereas for the test pipeline it is 0.103 bar, which represents an
increase of 0.036 bar. The operating point on Figure 17.2 therefore needs to be reduced
by this amount for scaling purposes, to take account of the difference in air only pressure
drop values. The new operating point (b) is therefore at a pressure drop of 0.814 bar.
Le h 2v Nb m (17.3)
where h is the total length of horizontal sections of pipeline; v, the total length of verti-
cally up sections of pipeline; N, the total number of bends in pipeline and b, the equiva-
lent length of each bend.
CASE STUDIES 401
There is no significant vertical lift and there are nine bends in the test pipeline. With a
conveying line inlet air velocity of 17 m/s the equivalent length of the bends, from
Figure 17.3, is about 20 m each. It will be seen from this that the bends can have a dom-
inating effect in dilute phase conveying systems.
17.3.4 Scaling
The data for the test pipeline can now be scaled to that for the plant pipeline. The first
stage is in terms of equivalent length and the second in terms of pipeline bore.
The two equivalent lengths were determined immediately above, and the material flow
rate for the test pipeline of 5.65 tonne/h was obtained from the revised operating point
on Figure 17.2; 3.17 tonne/h is the material flow rate that would be expected, for the
same conveying line pressure drop and air flow rate, if the pipeline had the same bore as
the test pipeline.
It is the 3.17 tonne/h that needs to be scaled here and substituting data into this equa-
tion gives:
2
250
3.17 18.0 tonne/h
105
This is greater than the 15 tonne/h required, but significantly less than 15 tonne/h would
be achieved with a smaller 200 mm bore pipeline. A pressure greater than 1.0 bar would
be needed if it was required to use a 200 mm bore pipeline, but then it would not be pos-
sible to use a positive displacement blower.
With a conveying line inlet air pressure of 0.85 bar gauge the case for stepping the
pipeline to a larger bore is marginal. Little improvement in conveying performance
would be achieved, but it would certainly help if there was a need to reduce erosive wear
of particle degradation.
This is the volumetric flow rate of the air at free air conditions, which are the reference
conditions required for the specification of a compressor.
p 185
P 203V˙0 ln 4 kW 203 1.522 ln 190 kW (17.7)
p3 100
selecting a conveying system. With an estimated value for power required it is possible to
evaluate conveying costs.
If the unit cost of electricity is taken as €0.10/kW h the specific cost can be
evaluated as follows:
h 10c
Specific cost 190 kW € 1.06 per tonne conveyed
18 tonne kW.h
18
2.7
3.6 1.87
As can be seen this is very dilute phase conveying, as expected, but is typical of low
pressure long distance conveying systems handling this type of material.