004 - Power Fuse (LS)
004 - Power Fuse (LS)
004 - Power Fuse (LS)
Prime-MEC
LS HRC Power Fuses
Electric Equipment
Current without
Power Fuse
(40kA ms)
Ipeak
Let through current
e
Cycl
0.5
low
Be
1
•••Contents•••
Introduction 4
Conditions of selection 6
Characteristics curves 8
Ordering information 14
2
LS HRC Power Fuses
Introduction
Features
•The LS HRC Power Fuses belong to the PRIME MEC series. It interrupts high currents before the first loop of fault
current has reached its natural peak value and therefore cuts down the required withstand capacity of the associated
equipment on the electric system.
•Though small in size, it has a high breaking capacity and its enclosed type is suitable for use inside of the panel board.
•PRIME MEC fuses are equipped with striker pins for trip indicators as well as for operating the related load break
switches.
•Link type fuse holder enables easy maintenance and high stability when replacing the fuses.
•With Fuse Checker, checking the conditions of a fuse in the panel board or by telecommunication is possible.(Optional)
Applied standards
•IEC 282-1, DIN 43625, BS 2692, KSC 4612
Applications
•Transformer protection
- To protect against short circuit current in the secondary part of
a transformer and fault current in the transformer circuit.
•Condenser protection
- To protect against fault current in the condenser circuit.
•Motor protection
- To protect against fault current in the motor circuit
•Cable protection
- Fault current protection secures the cable
3
Ratings
LFL-6G-5B 5
LFL-6G-10B 10
LFL-6G-20B 20
LFL-6G-30B 55 1.0
30
LFL-6G-40B 40 192 LFL-6G-D1HB 100
LFL-6G-50B 50 3~4In
7.2 40 In: Rated 7.2 60
LFL-6G-60B 63 current
LFL-6G-75B 75
LFL-6G-100B 100 2.0
LFL-6G-125B 125 77
LFL-6G-160B 160
292 2.8 LFL-6G-D2HB 200
LFL-6G-200B 200
LFL-12G-5B 5
LFL-12G-10B 10
LFL-12G-20B 20
LFL-12G-30B 30 55 1.3
LFL-12G-40B 40 292 LFL-12G- 100
LFL-12G-50B 50 D1HB
12 50 3~6In 12 75
LFL-12G-60B 63
LFL-12G-75B 75
2.8
LFL-12G-100B 100
LFL-12G-125B 125 77 LFL-12G-
LFL-12G-160B 160 442 4.2 200
D2HB
LFL-12G-200B 200
LFL-15G-5B 5
LFL-15G-10B 10 55 1.3
LFL-15G-20B 20
LFL-15G-30B 30 LFL-15G- 63
LFL-15G-40B 15.5 40 40 3~4In 292 2.8 D60B 15 110
LFL-15G-50B 50 77
LFL-15G-60B 63
LFL-15G-75B 75 LFL-15G-
442 4.2 100
LFL-15G-100B 100 D1HB
LFL-20G-5B 5
LFL-20G-10B 10 55 2.0
LFL-20G-20B 20
LFL-20G-30B 30 442 LFL-20G- 200
LFL-20G-40B 40 D2HB
77 4.2
LFL-20G-50B 50
LFL-20G-60B 63 40 24 125
24 3~4In
LFL-20G-75B 75 LFL-20G-
537 77 5.1 100
LFL-02G-100B 100 D1HB
LFL-20G-75B 75
LFL-02G-100B 100
5.1 LFL-20G-
LFL-20G-125B 125 442 87 200
D2HB
LFL-20G-160B 160
LFL-20G-200B 200
LFL-30G-5B 5
LFL-30G-10B 10
55 2.4
LFL-30G-20B 20
LFL-30G-30B 30 LFL-30G- 36 63 170
36 25 3~4In 537
LFL-30G-40B 40 D1HB
LFL-30G-50B 50 77 5.1
LFL-30G-60B 63
•Application site : Indoor use
•For fuse link & fuse holder type, refer to page 15.
4
LS HRC Power Fuses
Conditions of selection
When ordering 15.5, 36kV Power Fuse, Refer to page 9.10. For further information contact the manufacturer.
Selecting •The inrush current of a transformer is selected assuming that the current is 10 time that of the full-load transformer current in 0.1sec.
conditions •The rated current of the Power Fuses is selected to continuously flow at 1.5time of the transformer rated current.
•Power Fuses for proteting against short-circuit in the secondary part of a transformer are selected assuming that the current is 25times that of
the transformer rated current in 2seconds.
5
For condenser protection
Circuit Transformer Circuit Condenser Circuit Condenser Circuit Condenser
Phase voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses
(kV) (kVA) (kV) (kVA) (kV) (kVA) (kV) (kVA)
ф
3ф 3.3 64~81 LFL-3G-50B 6.6 128~163 LFL-6G-50B 11 204~270 LFL-12G-50B 22.9 425~564 LFL-20G-50B
81~105 LFL-3G-60B 163~210 LFL-6G-60B 270~341 LFL-12G-60B 564~710 LFL-20G-60B
105~150 LFL-3G-75B 210~300 LFL-6G-75B 341~490 LFL-12G-75B 710~1021 LFL-20G-75B
150~222 LFL-3G-100B 300~445 LFL-6G-100B 490~795 LFL-12G-100B 1021~1655 LFL-20G-100B
222~275 LFL-3G-125B 445~550 LFL-6G-125B 795~1138 LFL-12G-125B 1655~2370 LFL-20G-125B
275~370 LFL-3G-160B 550~742 LFL-6G-160B 1138~1522 LFL-12G-160B 2370~3170 LFL-20G-160B
370~500 LFL-3G-200B 742~1000 LFL-6G-200B 1522~1921 LFL-12G-200B 3170~4000 LFL-20G-200B
•The inrush current of a condenser is selected to withstand 71time of the condenser rated current in 0.002sec.
Selecting •The rated current of the Power Fuses is selected to continuously flow at 1.43 times of the condenser rated current.
conditions
ф
3ф 3.3 115~142 LFL-3G-50B 6.6 230~284 LFL-6G-50B
3.5 100
138~191 LFL-3G-60B 276~382 LFL-6G-60B
181~252 LFL-3G-75B 362~503 LFL-6G-75B 5.5 150
235~369 LFL-3G-100B 469~739 LFL-6G-100B
293~435 LFL-3G-125B 586~870 LFL-6G-125B 8 200
343~572 LFL-3G-160B 751~1223 LFL-6G-160B
22 200
375~630 LFL-3G-200B 1154~1760 LFL-6G-200B
•The starting current of a motor is selected to withstand 5 times of •Under the short-circuit condition, the power fuse
Selecting the full-loads current in 10sec. breaks the circuit in high speed. Therefore, with
conditions relatively high rated current, the Power Fuse
protects small size cables.
•Selected to protect from above 10 times of the
short-circuit current.
6
LS HRC Power Fuses
Characteristics curves
40 40
125A 50A
20 100A 20
10A
1 1
0.8 5A 0.8
0.6 0.6
0.4 0.4
0.2 0.2
0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04
0.02 0.02
0.01 0.01
2
10
20
40
60
80
0.02
0.04
0.06
0.08
800
200
600
0.1
100
0.2
1000
100
400
0.4
20
40
2000
0.6
0.8
10
4000
1
8
4
6
1000 1000
800 800
600 600
200A
400 400
160A
200 200
100 100
80 80
60 60
Cut-off current (peak value:kA) →
40 40
200A
Operating time (sec) →
20 20
160A
10 10
8 8
6 6
4 4
2 2
1 1
0.8 0.8
0.6 0.6
0.4 0.4
0.2 0.2
0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04
0.02 0.02
0.01 0.01
0.02
0.04
0.06
0.08
0.1
2
0.2
10
20
40
60
80
100
800
0.4
200
600
20
40
0.6
0.8
100
4
8
2
10
1000
1
400
4
6
2000
4000
7
7.2kV Cut-off characteristics 7.2kV Pre-arcing time-
current characteristics
1000 1000
800 800
600 600 200A
400 400
160A
200 200
100 100
80 80
60 60
40 40
Cut-off current (peak value:kA) →
200A
20 160A 20
2 2
1 1
0.8 0.8
0.6 0.6
0.4 0.4
0.2 0.2
0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04
0.02 0.02
0.01 0.01
1
2
0.02
0.04
0.06
0.08
0.2
0.4
10
40
0.1
100
20
0.6
0.8
4
6
8
10
20
40
60
80
6
800
200
600
4
100
1000
400
2000
4000
6000
8000
10000
Prospective breaking current(rms : kA) → Prospective rated current(rms : A) →
1000
800
600
400
30A 100A
200 75A
20A 63A
100 50A
80 10A
60 40A
Cut-off current (peak value:kA) →
40 40 5A
20
Operating time (sec) →
100A 20
75A
10 63A 10
8 50A 8
6 40A 6
30A
4 20A 4
10A
5A
2 2
1
1
0.8
0.8
0.6 0.6
0.4 0.4
0.2 0.2
0.1
0.08 0.1
0.06 0.08
0.06
0.04
0.04
0.02
0.02
0.01
0.01
0.02
0.04
0.06
0.1
0.2
0.4
0.6
0.8
10
20
40
1
4
6
8
1000
2000
4000
6000
8000
100
200
400
600
800
10
20
40
60
80
2
4
6
8
8
LS HRC Power Fuses
Characteristics curves
40 40
125A 50A 63A
100A 20
20
0.2 0.2
0.1 0.1
0.08
0.08
0.06
0.06
0.04 0.04
0.02
0.02
0.01 0.01
20
40
60
80
400
800
200
600
4000
100
2000
4
6000
8000
2
1000
10000
10
6
0.1
0.2
2
0.02
0.04
0.06
0.08
0.4
0.6
0.8
6
8
10
100
40
4
20
63A
200
50A
40A
100
80 30A
60
20A
Cut-off current (peak value:kA) →
40 40
10A
5A
20 20
Operating time (sec) →
10 63A 10
8 50A 8
6 6
40A
4 30A 4
20A
2 10A 2
5A
1 1
0.8 0.8
0.6 0.6
0.4 0.4
0.2 0.2
0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04
0.02 0.02
0.01 0.01
0.02
0.04
0.06
0.08
0.1
0.2
0.4
0.6
0.8
1000
2000
4000
6000
8000
10
20
25
100
200
400
600
800
1
4
6
8
10
20
40
60
80
2
4
6
8
9
Striker operating characterstics
Operating weight (kgf) →
Operating distance(mm) →
10
LS HRC Power Fuses
Fuse holder dimensions
Earth hole
Mounting hold
15
176
421
323
55
35
Below1
6 Fuse checker
35
14
123.7 76.2
155.2
253.3
250
ф12.5(Hold) 70
Fuse size(A) B C D Applied Holder
200.5
ф 55 294.6 492.9 156 LFH-12G-D1HB
ф 77 285.6 488.8 156 LFH-15G-D60B
Mounting hole
Below1
6 Fuse checker 35
14
123.7 76.2
155.5
Mounting hold
Fuse size(A) B C D E Applied Holder
Earth hole 15 ф 55 362.3 687.5 243.7 671 LFH-12G-D2HB
ф 77 373.3 691.6 243.7 671 LFH-15G-D1HB
300
671
616
296
ф 87 378.3 695 243.7 671 LFH-20G-D2HB
243.7 100
184
11
Power Fuse holder
E F E F
3.3 45 421 250 376 477 97 130 LFL-3G-5B, 10B, 20B, 30B, 40B, 50B
6.6 60 421 254 380 503 123 158 LFL-6G-60B, 75B, 100B
LFH-20G-D2HB 24 200 22.9 125 671 374 692 957 - 260 LFL-20G-30B, 40B, 50B, 60B
22.9 125 671 379 695 957 - 260 LFL-20G-75C, 100C 125B, 160B, 200B
12
LS HRC Power Fuses
Ordering information
P/F Link
LFH
P/F Holder
LFH
13
Basic conditions for selecting the Power Fuse
Ratings
Operating Voltage (____V) Frequency (____Hz) Ampere (____A) Breaking capacity (____kV)
Applications
•Transformers
Set to allow continuous flow at 1.5 times of the rated current of a transformer and to break at 25 times of the rated current of a
transformer within 2 seconds when a short circuit condition occurs in the secondary part.
•Condenser
- Inrush current : set to allow flows at 71 times of the rated current of a condenser for 0.002 seconds.
- Rated current : set to allow continuous flows at 1.43 times of the rated current of a condenser.
•Motor
•Cable
Example of ordering
Rated voltage : 24kV, Hz : 60Hz, Rated current : 200A, Breaking capacity : 40kA
14
Leader in Electrics & Automation
• For your safety, please read user's manual thoroughly before operating.
• Contact the nearest authorized service facility for examination, repair, or adjustment.
• Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions • Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lsis.biz
2006. 04 LS HRC Power Fuses (E) 2003. 08/(02) 2006. 04 Printed in Korea STAFF