Percentage differential relays are used for differential protection as they are more sensitive at low currents and can tolerate larger mismatches at high currents compared to simple differential relays. The percentage differential relay consists of a restraining coil tapped in the center to form two sections for the operating coil. It operates based on a percentage difference between the currents in the two sections, with the percentage setpoint able to be fixed or variable. This design allows the relay to adapt its pickup value to the fault and provide stability even with large percentage mismatches during high through faults.
Percentage differential relays are used for differential protection as they are more sensitive at low currents and can tolerate larger mismatches at high currents compared to simple differential relays. The percentage differential relay consists of a restraining coil tapped in the center to form two sections for the operating coil. It operates based on a percentage difference between the currents in the two sections, with the percentage setpoint able to be fixed or variable. This design allows the relay to adapt its pickup value to the fault and provide stability even with large percentage mismatches during high through faults.
Simple Differential relays are not often used due to the susceptibility to false operation because it will not be having any restraining coil for example overcurrent relay used for differential protection. The maloperation of the relay are causes due to the saturation errors, accuracy errors and mismatch errors in CT’s, magnetising inrush current due to energisation. To overcome the drawbacks of simple differential relay, percentage differential relays are used which offers high sensitivity at low currents and tolerate larger mismatches at high currents. Assume both CTs of a protected equipment path. The relay trips if the operating torque have the same nominal ratio of is greater than the restraining torque. The transformation n. The magnetizing currents Percentage difference can be fixed or of the two CTs will not be same it varies variable it depends on the manufacturer. widely. So, there will be substantial spill There is also a minimum differential current current will flow through the operating coil pickup before tripping without considering the restraint current. The minimum pickup, differential operation, restraint current characteristics and slope will vary among relay manufactures. Slope of a percentage relay may be a straight line, it may be a curve up depending on the application and design of percentage restraint. The slope during a through fault condition. This will curve allows even larger percentage result in maloperation or loss of stability on mismatches during heavy through fault a simple differential protection. In practical current. The percentage differential relay scenarios on a transformer protection CTs will not have any fixed operate value. The on the two sides must work at different Relay automatically adapts its pickup value voltage levels so the current on two sides to the fault occurs. The restraining winding will be different. This shows why the spill is also known as the biasing winding current goes on increasing as the through because we bias the relay towards the fault current increases. In the Case of restraint. During internal fault the spill busbar protection, the CTs ratio are same at current will be two time the circulating both ends. Busbars are subjects to very high current, which giving a slope of 2. through fault current which tends to magnify the differences between the characteristics of the two CTs. The percentage differential relay consists of a restraining coil which is tapped at the center of the coil thus forming two sections in the operating coil of the differential relay. It is represented as Nr/2. The restraining coil is connected in the current circulating
For power system studies consulting, individual training and corporate training requirements, contact us. www.powerprojectsindia.com