Final Control
Final Control
FINAL CONTROL
Prepared by: Prof M N Bhusavalwala
mnb@eed.svnit.ac.in
1.INTRODUCTION
In a typical process-control application, the measurement and evaluation of some process variable are carried out by a low-energy analog or digital representation of the variable. The control signal that carries feedback information back to the process for necessary corrective action is expressed by the same low level of representation. In general, the controlled process itself may involve a high-energy condition, such as the flow of thousands of cubic meters of liquid or several hundred thousand Newton hydraulic forces, as in a steel rolling mill. The function of the final control element is to translate low-energy control signals into a level of action commensurate with the process under control. This can be considered an amplification of the control signal, although in many cases the signal is also converted into an entirely different form.
mnb@eed.svnit.ac.in
INTRODUCTIONCONTD
In this chapter, the general concepts to implement the final control element function are presented together with specific examples in several areas of process control. A sensor used to measure some variable in a process-control application should have negligible effect on the process itself. It follows that sensor selection is based mainly on required measurement specifications and necessary protections (of the sensor) from harmful effects of the process environment. In sensor selection, the process-control technologist need not have intimate knowledge of the mechanisms of the process itself. The process-control technologist should have sufficient background on the final control element and its associated signal conditioning to know how such devices interface with preceding process controllers and transducers.
mnb@eed.svnit.ac.in
mnb@eed.svnit.ac.in
mnb@eed.svnit.ac.in
mnb@eed.svnit.ac.in
mnb@eed.svnit.ac.in
3. SIGNAL CONVERSIONS
The principal objective of signal conversion is to convert the low-energy control signal to a high-energy signal to drive the actuator. Controller output signals are typically in one of three forms: (1) electrical current, usually 4-20 mA, (2) pneumatic pressure, usually 3-15 psi, (3) digital signals, usually TTL level voltages in serial or parallel format. There are many different schemes for conversion of these signals to other forms depending on the desired final form and evolving technology. You should always be receptive to the advances of technology and the new subsequent methods of signal conditioning and conversion.
mnb@eed.svnit.ac.in 10
mnb@eed.svnit.ac.in
12
EXAMPLE:1
mnb@eed.svnit.ac.in
13
EXAMPLE:1
mnb@eed.svnit.ac.in
15
EXAMPLE :2
mnb@eed.svnit.ac.in
16
mnb@eed.svnit.ac.in
17
mnb@eed.svnit.ac.in
19
mnb@eed.svnit.ac.in
20
Fig.4 A pneumatic amplifier or booster converts the signal pressure to a higher pressure or the same pressure but with greater gas volume. 21
mnb@eed.svnit.ac.in
23
P CONVERTER
mnb@eed.svnit.ac.in
P CONVERTER
Fig.6 illustrates a simple way to construct such a converter. Notice that the current through a coil produces a force that will tend to pull the flapper down and close off the gap. A high current produces a high pressure so that the device is direct acting. Adjustment of the springs and perhaps the position relative to the pivot to which they are attached allows the unit to be calibrated so that 4 mA corresponds to 3 psig and 20 mA corresponds to 15 psig. Fig.6 Principles of a current-to-pressure
converter.
mnb@eed.svnit.ac.in
25
4. ACTUATORS
If a valve is used to control fluid flow, some mechanism must physically open or close the valve. If a heater is to warm a system, some device must turn the heater ON or OFF or vary its excitation. These are examples of the requirement of an actuator in the process-control loop. Notice the distinction of this device from both the input control signal and the control element itself (valve, heater, and so on, as shown in Fig.1). Actuators take on many diverse forms to suit the particular requirements of process-control loops. We will consider several types of electrical and pneumatic actuators.
mnb@eed.svnit.ac.in
26
mnb@eed.svnit.ac.in
27
mnb@eed.svnit.ac.in
28
Fig.8
A solenoid used to change gears. A solenoid is used to change the gears of a twoposition transmission. An SCR is used to activate the solenoid coil.
mnb@eed.svnit.ac.in 29
mnb@eed.svnit.ac.in
30
32
33
34
35
36
Fig.12 The induction motor depends on a rotor field induced by the ac field coils (not shown).
mnb@eed.svnit.ac.in
37
mnb@eed.svnit.ac.in
mnb@eed.svnit.ac.in
mnb@eed.svnit.ac.in
41
Fig.15 Cross section of a stepper with 8 rotor teeth and 12 stator poles. Note that the rotor lines up with the A poles. With the next step, the rotor will line up with the B poles.
42
EXAMPLE :3
mnb@eed.svnit.ac.in
43
mnb@eed.svnit.ac.in
45
Fig.16 A direct pneumatic actuator for converting pressure signals into mechanical shaft motion.
mnb@eed.svnit.ac.in
46
mnb@eed.svnit.ac.in
47
mnb@eed.svnit.ac.in
48
EXAMPLE :4
mnb@eed.svnit.ac.in
49
50
51
EXAMPLE :5
mnb@eed.svnit.ac.in
52
Fig.19 A hydraulic servo system. The process-control system provides the set-point of the servo system.
mnb@eed.svnit.ac.in
53
Fig.19 A hydraulic servo system. The process-control system provides the set-point of the servo system.
mnb@eed.svnit.ac.in
54
5. FLUID VALVES
The chemical and petroleum industries have many applications requiring control of fluid processes. Many other industries also depend in part on operations that involve fluids and the regulation of fluid parameters. The word fluid here represents either gases, liquids, or vapors. Many principles of control can be equally applied to any of these states of matter with only slight corrections. Many fluid operations require regulation of such quantities as density and composition, but by far the most important control parameter is flow rate. A regulation of flow rate emerges as the regulatory parameter for reaction rate, temperature, composition, or a host of other fluid properties. We will consider in some detail that process control element specifically associated with flow - the control valve.
mnb@eed.svnit.ac.in
56
Flow rate through a restriction in a line is a function of the pressure drop across the restriction.
mnb@eed.svnit.ac.in 58
mnb@eed.svnit.ac.in
61
mnb@eed.svnit.ac.in
62
mnb@eed.svnit.ac.in
63
mnb@eed.svnit.ac.in
66
mnb@eed.svnit.ac.in
67
EXAMPLE :6
mnb@eed.svnit.ac.in
68
EXAMPLE :7
mnb@eed.svnit.ac.in
69
EXAMPLE :8
mnb@eed.svnit.ac.in
70
EXAMPLE :9
mnb@eed.svnit.ac.in
71
mnb@eed.svnit.ac.in
72