ASHP Sizing and Selection Guide (EN)
ASHP Sizing and Selection Guide (EN)
ASHP Sizing and Selection Guide (EN)
ii
TABLE OF CONTENTS
Table of Contents
GLOSSARY ............................................................................................................................... vi
INTRODUCTION ....................................................................................................................... 1
STEP 1: DEFINE ASHP CONFIGURATION .................................................................................. 5
STEP 2: Choose Indoor Unit Type(s) for use with Ductless Mini-split ASHP .............................. 8
STEP 3: DETERMINE DESIGN HEATING AND COOLING LOAD ESTIMATES .......................11
STEP 4: DETERMINE SIZING APPROACH AND CAPACITY REQUIREMENTS OF ASHP .......................20
STEP 5: IDENTIFY AND SELECT ASHP MATCHING KEY REQUIREMENTS ........................25
STEP 6: DEFINE THE ASHP CONTROL STRAGEGY ............................................................34
STEP 7: DEFINE BACKUP HEATING REQUIREMENTS ........................................................42
Appendix A: Determining the “Economic Switch-over Temperature” to Switch from ASHP Heating to
Full Backup Heating ...................................................................................................................45
Appendix B: ASHP Key Specifications Summary Worksheet ....................................................52
List of Tables
Table 1: Typical Air-Source Heat Pump Options for Different Applications and Heating System
Configurations ............................................................................................................................ 5
Table 2: Different Types of ASHP Applications and Corresponding Load Estimating Options ...11
Table 3: Mapping Primary Client Objectives / ASHP Applications to the Sizing Options ............20
Table 4: Sizing Options 4A and 4B and Sizing Criteria for Selecting ASHP Equipment .............22
Table 5: Sizing Options 4C and 4D and Sizing Criteria for Selecting ASHP Equipment ............23
Table 6: Examples of Possible Centrally-ducted ASHP Equipment Choices Using Different
Sizing Options ...........................................................................................................................32
Table 7: Examples of Possible Mini-split ASHP Equipment Choices Using Different Sizing
Options .....................................................................................................................................33
Table 8: Common Backup Fuels with Conversion Factors for use in the COPmin Equation ........47
Table 9: Example of Extended Performance Data for an ASHP Showing COP versus Outdoor
Temperature .............................................................................................................................50
Table 10: Example of Extended Performance Data for a Variable-Capacity ASHP Showing COP
versus Outdoor Temperature .....................................................................................................51
List of Figures
Figure 1: Overview of the ASHP Selection and Sizing Process .................................................. 2
Figure 2: Air-Source Heat Pump Selection and Sizing Guide ..................................................... 3
Figure 3: The "ASHP Key Specifications Summary Worksheet" ................................................. 3
Figure 4: ASHP Selection and Sizing Spreadsheet Tool ............................................................ 4
Figure 5: "Worked Example" – Mini-split, Multi-zone, Add-on ASHP .......................................... 4
Figure 6: Centrally ducted ASHP ............................................................................................... 6
Figure 7: Ductless mini-split ASHP............................................................................................. 6
Figure 8: Ductless mini-split, multi-zone ASHP .......................................................................... 7
Figure 9: Wall Mounted Indoor Unit ............................................................................................ 8
Figure 10: Floor Mounted Indoor Unit ......................................................................................... 9
Figure 11: Ceiling-mounted Indoor unit ...................................................................................... 9
Figure 12: Ducted Indoor Unit ...................................................................................................10
Figure 13: CSA F280 Load Analysis determines design loads based on building envelope
characteristics ...........................................................................................................................12
Figure 14: Energy Efficiency Evaluation (Audit) Report (circa 2012) used to estimate design
loads .........................................................................................................................................12
Figure 15: HOT2000 Energy Modelling software can estimate design loads for both new and
existing houses .........................................................................................................................13
Figure 16: Using existing equipment to estimate Design Loads ................................................14
Figure 17: Two-storey house floor plans with Second-Floor Targeted Areas circled .................18
Figure 18: Example of a Plotting a Heating Load Line and Design Cooling Load for a House ...19
Figure 19: An Example of defining Target Capacities for different ASHP Sizing Options ...........21
Figure 20: Comparing CC-ASHP Turn-down Ratios ..................................................................27
Figure 21: Performance Curves and Balance Point Temperatures for 3 Possible ASHP Choices
.................................................................................................................................................28
Figure 22: Fraction of Total Annual Heating Curves for Five Climate Zones in Canada ............29
Figure 23: Climate Zone Assignments for Heat Pump Applications ...........................................30
Figure 24: Decision Tree to determine the most appropriate ASHP Control Strategy Option.....34
Figure 25: Example of Heating Modes with Control Strategy 6A1 .............................................35
Figure 26: Example of Heating Modes with Control Strategy 6A2 .............................................37
Figure 27: Example of Heating Modes with Control Strategy 6B1 .............................................38
Figure 28: Example of Heating Modes with Control Strategy 6B2 .............................................39
Figure 29: Example of Heating Modes with Control Strategy 6C ...............................................39
Natural Resources Canada Version 1.0, 2020-12-21
Air-Source Heat Pump Sizing and Selection Guide iv
TABLE OF CONTENTS
GLOSSARY
Add-on system: Adding HVAC equipment to a pre-existing system.
AFUE: Annual Fuel Utilization Efficiency. Dimensionless ratio used to indicate the fuel
conversion efficiency of a furnace as a percentage. A 96% AFUE furnace will output 96 Btu of
useful heat for 100 Btu of fuel consumption. A 96% AFUE, 50,000 Bth/h gas furnace will have a
heat output of 48,000 Btu/h (i.e., 50,000 x 0.96 = 48,000).
AHRI: Air-Conditioning, Heating & Refrigeration Institute
ANSI: American National Standards Institute
ASHP: Air source heat pump
ASHRAE: American Society of Heating, Refrigerating and Air Conditioning Engineers.
Auxiliary back-up heating system: A backup heating system needed if/when the heat pump
cannot provide enough heat for the building (i.e., furnace, electric baseboard, etc.)
Balance point temperature (BPT): See “Thermal balance point”.
Btu: British Thermal Unit equivalent to 0.293 watt-hours, or 1,055 Joules of energy content.
Btu/h: British Thermal Unit per hour (sometimes written as Btuh), used to rate the output or
capacity of heating or cooling equipment. One Btu/h is equivalent to 0.293 watts of capacity.
CC-ASHP: See “Cold-Climate” ASHP
Centrally Ducted ASHP: A system that uses an outdoor and indoor evaporator/condenser unit
to transfer heat from outside to the inside of a building, and vice-versa, via a forced air
distribution system.
CEE: Consortium for Energy Efficiency
Climate Zones: Regions that have a similar number of heating degree days (HDD) in the
heating season. Canada is subdivided into six climate zones (i.e., Zones 4, 5, 6, 7A, 7B and 8)
with HDD values range from < 3000 HDD (Zone 4) to ≥ 7,000 HDD (Zone 8). These climate
zones are developed and managed by ANSI/ASHRAE Standard 169 and are widely referenced
in energy performance ratings procedures and standards.
Climate Zones for ASHPs: Climate zones developed specifically for the CSA EXP-07 “Load-
based climate-specific testing and rating procedures for heat pumps and air conditioners”.
Canada is subdivided into five ASHP climate zones described as: Marine, Cold/dry, Cold/humid,
Very cold, and Subarctic. These climate zones are referenced throughout this Guide.
Cold-climate ASHP: An alternative to traditional air source heat pump heating/cooling systems
that is effective (i.e., maintains capacity and COP) even at cold ambient temperatures. (For
further details, refer to NEEP’s Cold Climate Air-Source Heat Pump Specification
https://neep.org/ASHP-Specification). Note that the ability of the system to maintain capacity at
cold outdoor temperature should also be considered when determining if a system is a suitable
“cold-climate ASHP”. See NEEP’s Cold Climate Air-Source Product List to assist in this regard
available at the link above.
capable of meeting the buildings heating requirements and a backup heating system will be
required.
Total Cooling Load: The total cooling load is the sum of the sensible and latent cooling loads
for the building or target area under consideration.
Turn-down Ratio: In a two stage, multi-stage or variable capacity ASHP, this is the ratio of
maximum capacity to minimum capacity (e.g., 3:1). ASHPs with higher turn-down ratios will
operate without cycling for a greater proportion of the heating season, increasing their seasonal
efficiency.
Two-staged ASHP: An ASHP that has a two-stage compressor, which can operate at two
different levels, low-stage or high-stage, depending on the capacity needed.
Variable-capacity ASHP: An ASHP that has a compressor which can operate at different
levels, depending on the capacity needed. CC-ASHPs are often equipped with variable
capacity driven compressors.
Watt or W: One W is equivalent to 3.413 Btu/h.
Wet-bulb Temperature (WBT): WBT is the temperature read by a thermometer covered in
water-soaked cloth (wet-bulb thermometer) over which air is passed, and is used to measure
the relative humidity or moisture content of the air. At 100% relative humidity (RH), the WBT is
equal to the dry-bulb temperature (DBT). At lower RH values the WBT is lower than the DBT of
the air.
INTRODUCTION
Purpose
The Air Source Heat Pump Sizing and Selection Guide is intended for use by mechanical
system designers / renovation contractors to assist them in selecting and sizing air source heat
pumps (ASHP) for Canadian climates in both new and existing residential (i.e., retrofit)
applications.
Scope
The focus of this Guide is on air source heat pumps (ASHP) for space heating and/or cooling
applications.
This guide covers the following applications of ASHPs:
New home (or major new addition) installations.
Full heating system replacement where existing HVAC equipment is removed.
Add-on ASHP applications to displace heating energy or provide supplemental heating
where existing heating equipment remains functional.
Exclusions:
Installation best practices and requirements are outside the scope of this Guide.
Users can complete the guide process by using one or more of these components. Short
descriptions of each are provided on the following pages.
The following pages provide brief descriptions of the three ASHP options, while Table 1
provides an overview of typical uses for the different options.
Table 1: Typical Air-Source Heat Pump Options for Different Applications and Heating System Configurations
Option 1A: Option 1B: Option 1C:
Application Heating System Centrally Ductless Ductless
Description Configuration Ducted Single-zone Multi-zone
In all applications, this type of ASHP delivers heating / cooling to the conditioned space via a
forced-air distribution system.
Multi-zone ASHPs may require the installation of a separate distribution box as per
manufacturer instructions. Extra consideration on installation may be required when
designing these systems to accommodate the location of the distribution box.
Record the type of installation by checking the appropriate box in the “notes column” on the
“ASHP Key Specifications Summary Worksheet”.
Once you have decided on the most appropriate configuration of ASHP, circle the chosen option,
and indicate the type of installation (i.e., new install / full HVAC replacement / Add-on ASHP) on
the “ASHP Key Specifications Summary Worksheet”.
If you have chosen: Option 1A – Centrally Ducted ASHP, skip ahead to STEP 3.
In STEP 2 you will choose the indoor unit type(s) to be used with the ductless single-zone or
multi-zone ASHP(s) chosen in STEP 1.
Common types of indoor units for ductless ASHPs include:
Option 2A: Wall mounted,
Option 2B: Floor mounted,
Option 2C: Ceiling mounted, and
Option 2D: Ducted (concealed).
The following sections provide brief descriptions of these different indoor unit options.
Once you have decided on the most appropriate indoor unit option(s) for the application, record
the option(s) chosen and number of indoor units required on the “ASHP Key Specifications
Summary Sheet”.
Ceiling mounted units are most often installed as part of a multi-zone system where a wall or
floor mounted unit is used in the main living area and the ceiling mounted unit is installed
upstairs for conditioning hallways and central locations in open floorplans.
Ducted indoor units are most often installed as part of a multi-zone system where a wall or floor
mounted unit is used in the main living area and a ducted indoor unit is installed upstairs for
conditioning separate bedrooms and hallways.
Table 2 matches different ASHP applications to the most likely load estimating options
available. Brief descriptions and examples of using these four load estimating options are
provided on the following pages.
Table 2: Different Types of ASHP Applications and Corresponding Load Estimating Options
If all building envelope retrofits were implemented, design loads for the house are as reported:
Post-Retrofit Design Heating Load (DHL): 43,641 Btu/h at a design temperature of -4°F (-20°C);
Post-Retrofit Design Cooling Load (DCL): 23,519 Btu/h at a design temperature of 88°F (31°C).
If building envelope retrofits were NOT implemented, the design cooling load would still be a reasonable
estimate, but the design heating load will need to be adjusted.
Based on the audit report, this particular example house has pre-retrofit design loads of:
Pre-Retrofit DHL: 49,592 Btu/h at a design temperature of -4°F (-20°C);
Pre-Retrofit DCL: 23,519 Btu/h at a design temperature of 88°F (31°C).
EXAMPLE – Option 3D: Estimating Design Loads from Existing Equipment Capacities
For example, a 1987 vintage, tract-built house has the original heating and cooling equipment installed
with the following nameplate information:
Heating: Natural gas furnace, Input = 90,000 Btu/h, Output = 68,400 Btu/h
Cooling: Central A/C Condenser, Model number: HS18-311
NOTE: When using model numbers to determine existing capacities, use the manufacturer’s
model number nomenclature to determine the corresponding capacity value.
A web search of the manufacturer’s coding of model numbers indicates that -31 in the model
number designates a cooling capacity of 31,000 Btu/h (2.6 tons). Rated capacity in cooling is
commonly reported at 95°F (35°C).
The design temperature conditions are: -4°F (-20°C) for heating and 88°F (31°C) for cooling.
Applying the Bracketing statements to this example installation:
Existing heating output = 68,400 Btu/h
If sized: at 140% of DHL, then DHL = 48,860 Btu/h; If sized at 125% of DHL, then DHL = 54,720 Btu/h
Existing cooling output = 31,000 Btu/h at 95°F (35°C)
NOTE: To obtain the cooling capacity at the design temperature of 88°F (31°C), designers should consult
the manufacturers expanded performance tables (then select the output at the temperature closest to the
design cooling temperature). If these are not available, approximate with the nominal rated capacity.
If sized at: 125% of DCL, then DCL ~ 24,800 Btu/h; at 100% of DCL, then DCL ~ 31,000 Btu/h (these are
approximate because the capacity of the system at the design cooling temperature of 88°F (31°C) would
be slightly higher than the nominal rated capacity at 95°F (35°C).
Based on the existing equipment capacities, design loads are estimated to be:
DHL: 48,860 to 54,720 Btu/h at a design temperature of -4°F (-20°C),
DCL: 24,800 to 31,000 Btu/h at a design temperature of 88°F (31°C).
The equation for rectangular ducts, with dimensions measured in inches is:
Maximum Airflow Capacity (CFM) = (Trunk1depth x Trunk1width + Trunk2depth x Trunk2width + etc.) x 0.00694 x 900,
or simplifying,
Maximum Airflow Capacity (CFM) = (Trunk1depth x Trunk1width + Trunk2depth x Trunk2width + etc.) x 6.25
(Equation 1a)
The equation for rectangular ducts, with dimensions measured in centimetres is:
Maximum Airflow Capacity (m3/s) = (Trunk1depth x Trunk1width + Trunk2depth x Trunk2width + etc.) x 0.0001 x 4.57,
or simplifying,
Maximum Airflow Capacity (m3/s) = (Trunk1depth x Trunk1width + Trunk2depth x Trunk2width + etc.) x 0.000457
(Equation 1b)
The equation for round ducts, with dimensions measured in inches is:
Maximum Airflow Capacity (CFM) = (Trunk1diameter2 + Trunk2diameter2 + etc.) x π / 4 x 0.00694 x 900,
or simplifying,
Maximum Airflow Capacity (CFM) = (Trunk1diameter2 + Trunk2diameter2 + etc.) x 4.91 (Equation 2a)
The equation for round ducts, with dimensions measured in centimetres is:
Maximum Airflow Capacity (m3/s) = (Trunk1diameter2 + Trunk2diameter2 + etc.) x π / 4 x 0.0001 x 4.57,
or simplifying,
Maximum Airflow Capacity (m3/s) = (Trunk1diameter2 + Trunk2diameter2 + etc.) x 0.000359 (Equation 2b)
Where: 0.00694 is the conversion factor between square-inches and square-feet.
0.0001 is the conversion factor between square-centimetres and square-meters
900 feet/minute (4.57 metres/second) is the maximum recommended velocity by HRAI for low velocity, residential ducts.
π (pi) is a constant, with a value of approximately 3.14.
Heating and cooling loads for the whole house have been estimated from a previous energy audit as:
Heating: 49,600 Btu/h at a design temperature of -4°F (-20°C); and
Cooling: 23,500 Btu/h at a design temperature of 88°F (31°C).
Other information:
Finished floor areas on all three levels total about 3,310 square-feet.
Target area size is about 1,130 square-feet.
Figure 17: Two-storey house floor plans with Second-Floor Targeted Areas circled
Figure 18: Example of a Plotting a Heating Load Line and Design Cooling Load for a House
These thermal load characteristics will be used in STEP 4 to establish target capacity values for
the ASHP.
The “best-fit” sizing approach will depend on the client’s expectations for the ASHP
installation.
A productive conversation with the client should determine their expectations, and will
help ensure that you meet their objectives for the ASHP installation.
Use the descriptions in Table 3 to help gauge client expectations and link their
expectation to a specific sizing option (i.e., 4A, 4B, 4C or 4D).
Document the choice made by the client by recording the sizing option on the “ASHP
Key Specifications Summary Sheet”.
Calculate the target output capacity of the ASHP needed for the application using the
specific instructions for the sizing option chosen, and record the value(s) on the “ASHP
Key Specifications Summary Sheet”.
Table 3: Mapping Primary Client Objectives / ASHP Applications to the Sizing Options
Option 4A: Option 4B: Option 4C: Option 4D:
Main Client Objectives / Goals Emphasis Balanced Emphasis Sized on
for the ASHP Installation on Heating and on Design Heating
Cooling Cooling Heating Load
Client is primarily interested in cooling. The ASHP is
seen as an alternative for a new or existing A/C unit;
The backup / existing heating system is seen as the
primary heating source for most of the heating season.
Client is interested in both cooling and ASHP heating.
The backup/existing heating system is used primarily
during colder weather.
Client sees the ASHP primarily as a heating source. The
backup / existing heating system is used during the
coldest periods. Cooling performance is of secondary
interest to the client. A CC-ASHP is suggested.
Client is interested in an ASHP that is sized to provide
all or nearly all of the heating at design conditions with
little or no use of backup heating. Cooling performance
of secondary interest to the client. A CC-ASHP is
suggested.
Figure 19: An Example of defining Target Capacities for different ASHP Sizing Options
Table 4: Sizing Options 4A and 4B and Sizing Criteria for Selecting ASHP Equipment
For the specific sizing option selected for the application under consideration, use the Target
Heating Capacity to identify “best fit” ASHP equipment in STEP 5.
Natural Resources Canada Version 1.0, 2020-12-21
Air-Source Heat Pump Sizing and Selection Guide 23
STEP 4: SIZING APPROACH AND CAPACITY REQUIREMENTS
Where: Design heating load is heating requirement of the house or target area at the design temperature.
Design temperature is the outdoor temperature (°F) specified for the location for design heating calculations.
When using Option 4C, calculate and record the Target Heating Capacity value for the
application under consideration on the “ASHP Key Specifications Summary Sheet”.
When using Option 4D, record the Target Heating Capacity value for the application under
consideration on the “ASHP Key Specifications Summary Sheet”.
In order select a best-fit ASHP system which will satisfy client’s expectations:
3) Compare performance of the candidate ASHP models to one another and to client
requirements. Possible factors to consider and compare could include:
i) Stage or modulating capabilities,
ii) Turn-down ratio (maximum to minimum capacity),
iii) Low-temperature performance capabilities and low-temperature operating limits,
iv) Thermal balance point temperature (t-BPT) for the application and Fraction of Total
Annual Heating provided above the t-BPT for the climate zone under consideration
(see details on how to estimate the “Fraction of Total Annual Heating” value later in STEP 5),
v) Efficiency ratings (e.g., COP, EER, etc.) and how they vary over the operating range,
vi) Noise ratings of outdoor units,
vii) Cost of the equipment.
4) Make any final adjustments to ASHP sizing and staging-modulation, if necessary, to
match client requirements.
5) Record the “best fit” ASHP on the “ASHP Key Specifications Summary Sheet”.
Air-Conditioning, Heating & Refrigeration Institute (AHRI) and Consortium for Energy
Efficiency (CEE)
The AHRI directory of certified products is located here:
https://www.ahridirectory.org/Search/SearchHome?ReturnUrl=%2f#
The CEE provides a useful front-end user interface for the AHRI directory. It is located here:
http://www.ceedirectory.org/site/1/Home
The CEE/AHRI database has test data with:
Cooling capacity data is available at 95°F (35°C). This will be suitable for screening Target
Cooling Capacity for Sizing Options 4A and 4B, from STEP 4.
o Only maximum or high-stage cooling values are provided for two-stage and variable
capacity equipment, which may limit the use with Sizing Option 4B in STEP 4 when
considering minimum or low-stage cooling capacities. (See “Note to Designers and
Contractors” for details on how to estimate minimum cooling output when using Sizing
Option 4B” with multi-stage ASHPs).
Heating capacity and efficiency measurements down to 17°F (-8.3°C), which will be
sufficient when Target Heating Capacity values are referencing outputs at 17°F (-8.3°C)
(e.g., Sizing Option 4C from STEP 4).
o Only maximum or high-stage heating values are provided for two-stage and variable
capacity equipment.
Northeast Energy Efficiency Partnerships
An Excel spreadsheet list of cold-climate ASHP products is maintained by the Northeast Energy
Efficiency Partnerships (NEEP), a non-profit organization in the United States. It is located
here: http://www.neep.org/ASHPInstallerResources
The NEEP List shows both high-stage and low-stage heating and high-stage cooling output
values for two-stage and variable capacity equipment, and has manufacturer-reported data with
heating capacity and efficiency values down to 5°F (-15°C).
The NEEP list is useful when ASHP sizing is being based on minimum or low-stage
cooling capacity (See “Note to Designers and Contractors” for details on how to estimate
minimum cooling output when using Sizing Option 4B with multi-stage ASHPs).
The NEEP list is useful for screening and initial selection of ASHPs based on heating
performance when performance data below 17°F (-8.3°C) is relevant (e.g., Sizing
Option 4D from STEP 4).
Figure 21: Performance Curves and Balance Point Temperatures for 3 Possible ASHP Choices
Use this information with other data (e.g. capacity, equipment cost, efficiency rating, etc.)
to help make the final decision on the ASHP model for the particular application.
Figure 22: Fraction of Total Annual Heating Curves for Five Climate Zones in Canada
By plotting the t-BPT of an ASHP installation as a vertical line on the outdoor temperature axis,
these curves will estimate the fraction of total annual heating that the ASHP will deliver without
the use of backup heating.
The fraction of total annual heating provided is indicated by the intersection of the t-BPT
line with the climate-zone curve for the house location. Red circles indicate the heating
fractions for the three ASHPs shown in Figure 22 in “Cold-Humid” climate zone
locations.
You can determine the climate zone for house locations in Canada by examining the
map of Climate Zone Assignments shown in Figure 23.
Note that there are a number of factors that will affect the actual heating fraction compared to
the value estimated using Figure 22:
Defrost and oil pan heater operation (that is typically not accounted for in the AHRI or
manufacturer extended performance tables) will reduce the available capacity somewhat
and decrease the actual heating fraction slightly.
Controls such as a standard 2-stage heat pump thermostat that allows the heat pump to
operate below the t-BPT will increase the actual heating fraction.
Heat pumps with higher capacities at low temperatures and allow lower temperature
operation, will have a higher actual heating fraction than heat pumps with steeper
capacity curves that drop off quickly or simply don’t operate in cold temperatures, even
when they have similar t-BPT values.
The first three examples are retrofits of centrally ducted ASHPs to the same detached
house using an existing supply duct system, but selecting different sizing options,
chosen in STEP 4. This existing duct system does not have the airflow capacity needed
for the 4D sizing option.
The fourth example (i.e., 4D sizing) is an installation of a ducted ASHP in a new-build,
energy-efficient, semi-detached house. In this example, the duct system would be sized
and designed to accommodate the airflow requirements of the ASHP system chosen.
Table 6: Examples of Possible Centrally-ducted ASHP Equipment Choices Using Different Sizing Options
Details on the sizing and selection process for these four centrally-ducted ASHP cases are
provided in a “ASHP Sizing and Selection Worked Examples” addendum to the Guide which
is available as a separate PDF download.
Details on the sizing and selection process for these four ductless mini-split ASHP cases are
provided in a “ASHP Sizing and Selection Worked Examples” addendum to the Guide which
is available as a separate PDF download.
Figure 24: Decision Tree to determine the most appropriate ASHP Control Strategy Option
Once you have determined the most appropriate Control Strategy, circle the chosen option, and
indicate a switch-over temperature to full backup heating if required on the “ASHP Key
Specifications Summary Worksheet”.
The five different control strategy options are described in the following sections.
Factors to consider when implementing the different options are listed at the end of
STEP 6.
Types of ASHP installations covered by these control strategy options include:
o Integrated ASHP / backup systems (e.g., “hybrid” or “dual-fuel” systems);
o Add-on ASHP systems; and,
o Ductless ASHP systems.
At outdoor temperatures below the cut-off temperature, ASHP operation will be disabled
and all heating will be provided by the backup heating system.
At outdoor temperatures above the thermal balance point temperature, all heating will be
provided by the ASHP.
At outdoor temperatures below the thermal balance point temperature, heating will be
provided by both the ASHP and backup system (i.e., in sequence of operation, the details
of which will depend on the thermostat or equipment control logic). Refer to
Implementation of Controls at the end of this STEP for additional details on control
sequencing.
o This type of control is most applicable to installations where a low-cost fuel is used for
backup heating, whether integrated into a single system or with an add-on heat pump
using an independent backup heating system.
An example of the various heating modes with Control Strategy 6B2 are shown in Figure 28. In
this instance, the e-BPT is below the t-BPT.
At outdoor temperatures above the t-
BPT, all heating will be provided by
the ASHP.
At outdoor temperatures between the
t-BPT and the switch-over
temperature, heating will be provided
by both the ASHP and backup
system (i.e., in sequence of
operation, the details of which will
depend on the thermostat or
equipment control logic). Refer to
Implementation of Controls at the
end of this STEP for additional details
on control sequencing.
At outdoor temperatures below the e-
BPT, ASHP operation will be disabled Figure 28: Example of Heating Modes with Control Strategy 6B2
and all heating will be provided by the
backup heating system.
For regions with time-of-use electricity rates, the e-BPT may have two or more values
based on time-of-day and day-of-week settings.
Factors when Implementation Control Strategies 6A1, 6A2, 6B1 and 6B2
Integrated ASHP and backup heating system:
A single, multi-stage indoor thermostat sequences the operation of both the ASHP and
back-up heating system above the outdoor temperature cut-off set-point (Note: Control
Strategy 6B1 does not have an outdoor temperature cut-off control).
o For system using fuel-based furnaces (e.g., “hybrid” or “dual-fuel” systems), the
thermostat will first bring on the ASHP to satisfy a “heating call”, and only turn off the
ASHP and bring on backup heating if the “heating call” cannot be satisfied by the
ASHP.
o For ducted systems using backup heating that can operate simultaneously with the
ASHP (e.g., downstream electric resistance heating elements) the ASHP may
continue to operate simultaneously with the backup heating in order to satisfy the
“heating call”.
o For ductless systems with controls that can be integrated with backup heating
(e.g., mini-split / multi-split systems with auxiliary heat relay to electric baseboard
backup), the thermostat will first bring on the ASHP to satisfy a “heating call”, and only
bring on the backup heating if the “heating call” cannot be satisfied by the ASHP.
Additional Factors when Implementing Control Strategies 6A1, 6A2 and 6B2 only
An outdoor temperature cut-off control disables ASHP operation at outdoor temperatures
below the cut-off set-point, and all heating is provided by the backup system.
o For control strategy 6A1, the ASHP low-temperature cut-off specification determines the
cut-off temperature; For control strategies 6A2 and 6B2 the cost of heat analysis
determines the switch-over point (see APPENDIX A: “Determining the Economic Cut-off
Temperature (e-BPT)”, for additional details).
o The outdoor cut-off temperature will likely be set on the thermostat directly, or on the
equipment via dip-switches or setup menus, depending on the manufacturer.
o When using control strategies 6A2 or 6B2 in regions with time-of-use electricity rates,
choosing a control offering multiple cut-off temperatures that are based on time-of-
day and day-of-week is preferable.
Once you have determined the most appropriate backup option, circle the chosen option, and if
new backup is required, indicate the minimum capacity and type of new backup heating needed
(i.e., fuel or electric) on the “ASHP Key Specifications Summary Worksheet”.
Restricted or unrestricted ASHPs sized to less than the design load, for example,
o Ductless or mini-ducted add-on ASHP installations using one or more indoor units.
o Centrally ducted ASHP replacing an air conditioner with fossil-fuel furnace backup
(e.g., “hybrid” or “dual-fuel” systems)
From the Utility Website, fixed costs are: Delivery - Customer Charge ($40.56 per month); and
Regulatory - Standard Supply Service Rate ($0.25 per month).
Over the 2-month billing period, the consumption-based delivery and regulatory costs are:
= ($67.75 – $40.56) + ($5.09 – ($0.25 x 2)) = $31.78
The Consumption-based Delivery and Regulatory rate is: $31.78 / 1,137 kWh used = $0.028 / kWh
Consumption-based time of use (TOU) Electricity Rates, including delivery & regulatory charges are:
On-Peak: ($0.132 + $0.028) plus 13% HST, minus 8% Provincial Rebate = $0.160 x 1.05 = $0.168 / kWh
Mid-Peak: ($0.095 + $0.028) plus 13% HST, minus 8% Provincial Rebate = $0.123 x 1.05 = $0.129 / kWh
Off-Peak: ($0.065 +$ 0.028) plus 13% HST, minus 8% Provincial Rebate = $0.093 x 1.05 = $0.098 / kWh
= ($119.94 - $20.00) plus 13% HST divided by 339 m 3 = $99.94 x 1.13 / 339 = $0.333 / m3
Cost of fuel units, energy content and associated conversion factors are provided in Table 8.
The conversion factor is needed to convert the fuel units into kWhs, and is numerically the
higher heating value of the fuel in kWh per unit of fuel (e.g., Natural Gas: 10.36 kWh/m3)
Table 8: Common Backup Fuels with Conversion Factors for use in the COPmin Equation
Backup Fuel Higher Heating Value Cost of Fuel Units Conversion Factors for Equation 6
(kWh per unit of fuel)
Natural Gas 37.3 MJ / m3 $ / m3 10.36
Natural Gas 37.3 MJ / m3 $ / GJ 277.8
LPG / Propane 25.3 MJ / litre $ / litre 7.03
Heating Oil 38.2 MJ / litre $ / litre 10.61
EXAMPLE: Calculating COPmin for an installation using natural gas for backup heating.
Consumption-based Cost of Electricity is $0.10 / kWh
Consumption-based Cost of Natural Gas is $0.333 / m3 (equivalent to $8.93 / GJ);
(NOTE: Both the electricity and fuel prices include energy and delivery costs and taxes, but exclude
fixed monthly charges that do not vary with the amount of electricity or natural gas consumed).
A graphic alternative to determining COPmin in provided in Figure 31 for natural gas. To use this
chart, project the consumption-based cost of electricity, shown on the vertical axis, as a
horizontal line, and the consumption-based cost of natural gas divided by the furnace efficiency
(i.e., AFUE), shown on the horizontal axis, as a vertical line. Where the two lines cross will
indicate the COPmin value shown by the sloped lines on the chart.
Figure 31: Chart for determining Minimum COP for ASHP Heating Cost to Equal Natural Gas Heating Cost
The example shown in Figure 31 estimates a COPmin value of 3.0 which is the same as the
value calculated using equation 6.
NOTE TO DESIGNERS AND CONTRACTORS: Use of LPG/propane or Fuel Oil for Backup
In most instances, the cost of LPG/propane or fuel oil is high enough to result in backup heating costs
that are higher than ASHP heating costs even at relatively low outdoor temperatures.
Switching to LPG / propane or fuel oil heating will typically be based on the need for additional heating
capacity rather than the cost of heat from the ASHP.
As a result, no economic cut-off control is normally required when using LPG/propane or fuel oil for
backup heating. Switching from ASHP heating to backup heating will be handled by the normal
staging controls of the heating system.
Example: Electricity cost of $0.17 / kWh; LPG / propane cost of $0.90 / L; Furnace AFUE of 95%.
Conversion Factor for LPG/ Propane is 7.03 kWh / L (from Table 8)
Using Equation 6:
COPmin = $0.17 x 0.95 / $0.90 x 7.03 = 1.3
An ASHP will provide lower cost heating than the propane furnace down to a COP of 1.3
Figure 32: Example of determining Minimum COP for ASHP Heating Cost to Equal Natural Gas Heating Cost
with Time-of-Use (TOU) Electricity Rates
In this example the electricity rates vary with the time-of-day and day of week with on-peak,
mid-peak and off-peak electricity cost so $0.17, $0.13 and $0.10 per kWh respectively. These
prices include energy and delivery costs and taxes, but exclude fixed monthly charges that do
not vary with the amount of electricity consumed. The cost of natural gas is $0.333 per cubic
metre which includes energy and delivery costs and taxes, but excludes fixed monthly charges
that do not vary with the amount of fuel consumed. The natural gas furnace has an AFUE
(efficiency) of 95%.
The minimum ASHP COP values needed to product heating at a cost equal to that of the natural
gas backup furnace are:
Table 9: Example of Extended Performance Data for an ASHP Showing COP versus Outdoor Temperature
The cut-off control installed in this system would be set to restrict ASHP operation to these
outdoor temperatures and times-of-day and days-of-week corresponding to the different rate
periods.
Table 10: Example of Extended Performance Data for a Variable-Capacity ASHP Showing COP versus Outdoor Temperature
Since economic cut-off points will commonly occur at warmer temperatures, when the ASHP is
primarily operating on the lowest capacity, it is suggested that the “low-stage” performance table
be used to determine the e-BPT when using 2-stage or variable capacity ASHPs.
Using the example of a COPmin value equal to 3.0, the e-BPT is about 25°F (-4°C) for this
particular variable capacity ASHP model.
The cut-off control installed in the system would be set to restrict ASHP operation to
outdoor temperatures above 25°F (-4°C).
Identify & Select ASHP Candidate #1 Candidate #2 Candidate #3 Candidate #4 Final Choice: ____________
5 Identify candidate Model #: ___________________ Model #: ___________________ Model #: ___________________ Model #: ___________________ Heat-output: __________ Btu/h
ASHP models
matching Stages: ________; Cut-off: _____°F Stages: ________; Cut-off: _____°F Stages: ________; Cut-off: _____°F Stages: ________; Cut-off: _____°F at 17°F , or at ________°F
Key Requirements
Nominal Cap: _______________ Nominal Cap: _______________ Nominal Cap: _______________ Nominal Cap: _______________ Low Temp. Cut-off: ________°F
Cooling at design: ________Btu/h
Heat-output: ______________ Btu/h Heat-output: ______________ Btu/h Heat-output: ______________ Btu/h Heat-output: ______________ Btu/h
BP Temperature: _________°F
at 17°F , or at ________°F at 17°F , or at ________°F at 17°F , or at ________°F at 17°F , or at ________°F %Total Heating above BPT:
Cool-output at 95°F: ________ Btu/h Cool-output at 95°F: ________ Btu/h Cool-output at 95°F: ________ Btu/h Cool-output at 95°F: ________ Btu/h _________ % of total