Dry Room in Battery Plant
Dry Room in Battery Plant
Dry Room in Battery Plant
Paul A. Nelson
Chemical Sciences and Engineering Division, Argonne National Laboratory, Bldg. 200,
9700 S. Cass Avenue, Argonne IL 60439 USA
nelsonp@anl.gov
Dennis W. Dees
Chemical Sciences and Engineering Division, Argonne National Laboratory, Bldg. 200,
9700 S. Cass Avenue, Argonne IL 60439 USA
dees@anl.gov
© 2016. This manuscript version is made available under the Elsevier user license
http://www.elsevier.com/open-access/userlicense/1.0/
Abstract
The manufacture of lithium ion batteries requires some processing steps to be carried
out in a dry room, where the moisture content should remain below 100 parts per
million. The design and operation of such a dry room adds to the cost of the battery.
This paper studies the humidity management of the air to and from the dry room to
understand the impact of design and operating parameters on the energy demand and
the cost contribution towards the battery manufacturing cost. The study is conducted
with the help of a process model for a dry room with a volume of 16000 cubic meters.
For a defined base case scenario it is found that the dry room operation has an energy
demand of approximately 400 kW. The paper explores some tradeoffs in design and
operating parameters by looking at the humidity reduction by quenching the make-up
air vs. at the desiccant wheel, and the impact of the heat recovery from the desiccant
regeneration cycle.
Keywords
Dry room, lithium ion battery, battery manufacturing, humidity control
Page 1 of 35
Table of Contents
1. Introduction ..................................................................................................................... 3
4. Conclusions ......................................................................................................................... 21
5. Abbreviations ...................................................................................................................... 23
Acknowledgments................................................................................................................... 23
Bibliography ............................................................................................................................ 25
Page 2 of 35
1. Introduction
Increasing demand for lithium ion batteries (LIB) [1] and the resultant demand for
reliable dry rooms [2] have spurred numerous suppliers offering dry room technologies.
The trend is toward larger manufacturing plants to benefit from economies of scale [3].
These plants seek to squeeze out inefficiencies and cost factors. The dry room
represents a step in the manufacturing process where the energy demand is very high
because of the large volume of air that needs to be temperature controlled and dried.
A dry room is an essential part of the manufacturing plant for lithium ion batteries
[4] [5] [6]. Here the cells are filled with the electrolyte which is very sensitive to
moisture (e.g., lithium hexafluoride reacts with water) and sealed in an environment
with moisture concentrations below 100 parts per million by volume (ppmv). Small
variations in the moisture content can affect the capacity and/or the cycle life of the
volume, where the incoming air contains very low moisture content (say 15 ppm or
0.066 grains per pound (gpp)), such that the exit gas does not exceed the specified
upper limit (say 100 parts per million volume (ppmv) or 0.44 gpp). The air flow rate
through the dry room is controlled with sensors to maintain the exit gas at a moisture
placement and air flows ensures rapid resolution of any occasional spikes in moisture at
key spots in the room [8]. The room enclosure is kept leak-proof which includes use of a
Page 3 of 35
vapor barrier seal on the concrete floor followed by an epoxy finish coat. Some key
parameters in the design of the dry room include the volume of the room, the allowable
moisture concentration, and the amount of moisture released from the materials
The objective of this paper is to estimate the energy consumption and the cost
contribution to the battery manufacturing plant from operating a dry room. A generic
system diagram has been proposed to enable a reasonable estimate of the cost and
produce 100,000 packs of automotive lithium ion batteries (LIB). The plant equipment is
amortized over 6 years. The dry room is assumed to have a volume of 16,000 m3.
Page 4 of 35
Make-Up Air
9°C, 50 gr/lb H2O 24°C, 3.0 gr/lb 426 kW
33°C, 50% RH A6
152 kW
Cool
Pre-Cool Blend Filter A5
A1 A2 A3 A4
57 kW 10°C, 3.0 gr/lb
25°C A11
8 kW
100 ppmv, 0.44 gr/lb 41,000 scfm
14°C
A10 5% B7 A7 95%
0.066 gr/lb
63 kW Post-Heat 12°C Desiccant
0.066 gr/lb Wheel
A9 10°C
A8
Post-Cool
0 kW
10°C B8 16°C
Discharged Air
146°C B11 3.2% H2O
Regen 122°C B12 B14
Heat B10 142°C 36°C
30 kW
B13
B9 122°C 8 kW
Ht
.E
xc
h.
Figure 1. Schematic of the air management for the Dry Room
Figure 1 is a schematic of the management of the air supply for the dry room,
including some assumptions, input parameters, and calculated results for a base case
system. The make-up air at 33°C, 50% relative humidity (RH) or 2.5 vol.% moisture, is
pre-cooled to 9°C to drop out some of the moisture and then blended with the return
air from the dry room. The combined stream emerges at a temperature of 24°C and a
moisture content of 0.07 vol.% (3 gpp). This stream is filtered and cooled down to 10°C,
and then split with 95% going towards the dry room (A7-A10), the balance (purge
stream) to be eventually discharged (B7-B14) from the system. A low purge rate (5%) is
advantageous in that it lowers the heating and cooling loads in the system, and is
Page 5 of 35
discussed in Section 3.5. The dry-room stream is passed through a desiccant wheel
where the moisture content is reduced to 15 ppmv (0.066 gpp). This gas is then heated
or cooled as needed such that the dry room exit air is at 25°C. For this base case
scenario, the dry room inlet temperature is 14°C. Within the dry room the air picks up
moisture from the personnel, from the negative electrodes that come in with moisture
content, and the opening of the airlock doors. The air flow rate and its inlet temperature
are calculated such that the return air is at 25°C and with a moisture content of 100
ppmv (0.44 gpp), or less. For the base case set of conditions, the inlet air is at 14°C and
the air flow rate is 20 m3 s-1 (41,000 ft3 min-1). This air flow rate corresponds to a
The desiccant wheel is regenerated by passing the discharge air stream heated to
146°C. The discharge air stream flows multiple times through the desiccant wheel to
heat and cool the desiccant wheel and to allow for recovery of some of the sensible
heat, as shown in the figure. Table 1 lists the assumptions and input parameters used in
Table 1. Assumed / Input Parameters in Dry Room Process Model (Base Case)
gpp) and 100 ppm (0.44 gpp) of moisture, respectively, the air flow needed through the
Page 6 of 35
dry room is calculated to be 19.6 m3 s-1 (41,600 ft3 min-1). This flow represents a
residence time or volumetric air turnover every 13.6 minutes. With the heat generated
in the dry room assumed to be 250 kW, the inlet air temperature needs to be at 14°C to
ensure that the air leaving the dry room is at the specified 25°C.
Table 2. Moisture Content and Energy Demands in the Process (Base Case)
Table 2 shows the heating and cooling loads for the steps in the process. The largest
cooling load of 426 kW is at the Cool station (A5-A6). The combined cooling load at
three stations (Pre-Cool, Cool, and Post-Cool) is 483 kW. Assuming a coefficient of
performance of 3.5, the electric power needed for the heat removal is 138 kW. A
needed for the blowers (167 kW) and refrigeration (138 kW), adding up to 305 kW. The
thermal energy requirements are at Post-Heat (63 kW) and for the discharge air heating
for zeolite wheel regeneration (30 kW). The total energy requirement for the operation
(the sum of the thermal and electrical) is 398 kW. If we consider that the electric power
from the grid is generated from natural gas (NG) with an efficiency of 40%, then the
energy required for the system becomes ((138+167)/0.4 + 93 =) 856 kW. Using the EPA
greenhouse gas equivalencies calculator [10], the greenhouse gas emissions from the
generation of the thermal and energy usage for the dry room air management converts
to 5.4 MT of CO2 Equivalent. These estimates do not include the inefficiencies of heat
Page 7 of 35
The modeling results were used to estimate the cost of the capital equipment and
raw materials, while the labor requirement for the baseline plant was estimated from
The cost of the dry room operations was based on an algorithm defined by Peters and
Timmerhaus [11], which also provides a range of percentages. Table 4 lists the
estimated percentages for the cost assessment in column 2. The annual cost of
operations was then calculated by adding the Total Operating Cost to the annualized
The cost of the dry room operations was estimated to be $3.5 M per year, or $35 per
pack, or $1270 per m3 of the dry room, for the plant producing 100,000 battery packs
per year. For reference, Argonne’s BatPaC model [12] [13] estimates the cost of a 10
kWh battery for a Plug-in Hybrid Electric Vehicle (PHEV) producing 100K packs per year
preparing the estimate, an alternative estimate was obtained by using a range of the
percentages for the parameters in Table 4, which are shown in column 4. A random
Page 8 of 35
number generator was used to generate a percentage value within the range for each
cost item to calculate the cost of dry room operations. This was repeated over 1000
times, to yield an average value of $38 per pack, with a standard deviation of $2. The
results were spread between a maximum and minimum of $46 and $31, respectively,
Figure 2. Frequency distribution of cost calculations using randomized percentages from Table 4, column 4.
Page 9 of 35
The moisture mainly comes into the system with the make-up air. At 33°C and
50% RH, water vapor enters the system at a rate of 19.4 g s-1 (1.08 mol s-1, 2.5 vol.%).
The Pre-Cool station cools the gas to 9°C and condenses out 10.6 g s-1 of moisture. The
second source of moisture into the system is with the materials and personnel entering
the dry room, adding 1.23 g s-1. Blending the make-up air with the return air from the
dry room (containing 100 ppmv H2O or 0.066 gpp), results in the mixture with a
moisture content of 682 ppm (3 gpp). The Cool station reduces the mixture temperature
to 10°C (saturated vapor pressure is 1.2 vol.%) but because of the already low moisture
content, no further condensation occurs at this station. The main air stream (A7)
undergoes the final moisture removal at the desiccant wheel, where 9.5 g s-1 (0.53
mol s-1) H2O is adsorbed, dropping the moisture level in the air to 15 ppmv (0.066 gpp).
The air emerging from the desiccant wheel is warmed up to ~12°C because of the
heat of adsorption that is generated when the moisture is adsorbed onto the desiccant.
This air stream is then heated to 14°C before entering the dry room.
Within the dry room, moisture is released by the personnel and negative electrodes,
while some moisture enters during the opening of the air lock doors. This breakdown is
shown in Table 5.
Page 10 of 35
The discharge stream from the splitter carries 0.51 g s-1 (0.028 mols s-1) of moisture
and extracts the 9.5 g s-1 of moisture that was adsorbed on the desiccant wheel. The
discharge stream exits the system at ~36°C with 10.0 g s-1 of moisture (1.3 vol.%). The
saturated vapor pressure at 36°C is approximately 6%. The material balance for the
regenerate the desiccant wheel. With an approach temperature of 20°C, the heat
exchanger requires a heat transfer area of 2200 m2. Eliminating the heat exchanger
would simplify the process but it would increase the heat load on the air heater by a
factor of more than 5, from 30 to 168 kW. The feasibility of a smaller heat exchanger
was explored by studying the effect of the approach temperature by varying it from
20°C to 132°C (no heat exchanger needed). Figure 3 shows that with increasing
approach temperature, the heat load needed to raise the discharge air temperature to
146°C (for desiccant regeneration) increases linearly. The larger approach temperature
allows for a smaller heat exchanger, as shown by the non-linear decrease in the heat
transfer area requirement. The cost of the dry room operations ($ per pack) decreases,
Page 11 of 35
Figure 3. The heat exchanger size and cost of natural gas determines the cost of the dry room operations.
-1
Natural gas = 2 cents kWh .
portion of the moisture in the make-up air. For the base case scenario, the heat removal
load for cooling to 9°C in this step is 57 kW. The extent of cooling at this station has
the Pre-Cool station was conducted by varying the temperature from 1° to 33°C. The
Lowering the Pre-Cool temperature from 33°C (no precooling) changes the cooling
load at the Pre-Cool station from zero to 76 kW at 1°C, and at the Cool station from 457
to 416 kW. The combined cooling load increases by 8%, from 457 kW at 33°C to 492 kW
at 1°C.
Page 12 of 35
As the Pre-Cool setting is lowered, the amount of heat needed at the Post-Heat
increases from 20 to 78 kW. The total thermal energy load increases by 96% (54 to 106
kW) when the Pre-Cool temperature is reduced from 33°C to 1°C. The Total Energy
Need represents the sum of the thermal energy load and the power needed for
increases 18%, from 351 to 414 kW as the Pre-Cool setting is reduced from 33 to 1°C.
temperature is lowered. However, the lower Pre-Cool temperature settings reduces the
burden of removing moisture at the zeolite wheel, which can then turn slower and also
benefit from a smaller temperature differential as a result of the heat effects of less
Figure 4. Effect of the Pre-Cool Temperature Setting on the Heating and Cooling Needs
Page 13 of 35
Table 7. Effect of the Pre-Cool Temperature on Heating and Cooling
The distribution of water removal from the system as a function of the Pre-Cool
temperature is shown in Table 8. At 9°C, 55% of the water entering with the make-up air
(51.5% of the total water entering the system) is removed at the Pre-Cool station. The
balance is removed with the purge stream (2.5%) and via the desiccant wheel (46.0%),
ultimately leaving with the discharge stream (B14). With a setting of 33°C, there is no
water removal at the Pre-Cool station. Thus all the water is removed via the desiccant
wheel (94.9%) and the purge stream (5.1%). The trends of the water distribution at the
Figure 5. Distribution of Water into and out of the process as a function of the Pre-Cool temperature.
Page 14 of 35
3.4. Ambient Air Conditions
The main function of the operations supporting the dry room is to ensure that the
moisture content brought in with the ambient make-up air and the moisture that is
introduced / generated within the dry room is reduced to very low levels. For the Base
Case conditions, the moisture coming in with the make-up air is overwhelmingly higher
(by 2 orders of magnitude) than from inside the dry room. Furthermore, the
temperature of the ambient air also varies with the plant location and season.
The effect of the ambient air conditions was studied by varying the temperature
from 40°C to -17.8°C (104°F to 0°F). The RH was held constant at 50% for all
temperatures. With lower temperatures and lower moisture content, the cooling load at
the Pre-Cool station diminishes and becomes zero at 9°C (the Pre-Cool set temperature).
At temperatures below 9°C, the load at the Cool station is also reduced. The drier air
entering the desiccant wheel generates less heat of adsorption and so the gas exits (A8)
at a lower temperature. The effect of the ambient air temperature on the heating and
cooling demands, as well as the overall energy demand for the dry room operation are
shown in Figure 6 and Table 9. Over the range of temperature studied, the Total Energy
Need is found to pass through a minimum value of 385 kW when the ambient air is at
20°C; at still lower temperatures more energy is needed at Post-Heat to meet the dry
The effect on cost is also shown in Figure 6, where the cost of electricity decreases,
while the cost of natural gas increases with decreasing ambient temperatures. The total
Page 15 of 35
cost of operations ($ per pack) is seen to decrease sharply from 40°C to 20°C, and then
more gradually, reflecting the slopes of the other energy and cost curves.
Figure 6. Effect of the Ambient Air Temperature on the Energy Demands and Costs (RH=50%).
Table 9. Effect of Ambient Air Temperature Heating and Cooling Needs, and Costs (RH=50%).
the case of the dry room, moisture and carbon dioxide are generated. Both these
species are removed effectively by the molecular sieve used in the desiccant wheel, as
these molecular sieves are also used for drying and CO2 removal from natural gas [14].
The purge flow ensures that the concentrations of any other chemical species that are
not removed via condensation or the molecular sieve do not build up too much.
The purge rate determines the amount of make-up air needed and, therefore, is a
significant determinant in the energy needs and the cost of operations. The effect of the
Page 16 of 35
purge rate was studied by varying it from the base case of 5% to 20%. A higher flow
associated with increasing the purge / make-up air increases the heat removal loads.
The larger moisture content entering the system increases the heat effects of the zeolite
wheel, and the heat required for regeneration. Thus, increasing the purge rate increases
the energy demand (cooling and heating) and equipment sizes, all of which lead to
higher costs of operation. Raising the purge rate from the base case of 5% to 20% purge,
increases the energy demand by 62% to 645 kW and increases the cost per pack for the
dry room operations by 10% to $38.37. These results are summarized in Figure 7 and
Table 10.
Figure 7. Effect of the purge rate on the heating and cooling needs, and the cost of operations.
Table 10. The heating and cooling needs, and the cost of operating the dry room at different purge rates.
Page 17 of 35
3.6. Other Parametric Sensitivities
The model includes a large number of assumed input values and the sensitivity of
the output values to some of these parameters has been studied. The effects of plant
life, the volume of the dry room, the prices of natural gas and electricity, and the
coefficient of performance are shown in Figure 8. Changing the amortization rate from
the base case of 6 years to 4 or 8 years changes the cost of the dry room operation from
$34.85 per pack to $43.45 or $30.55, respectively. Changing the size of the dry room by
10% changes the per pack cost by a dollar or approximately 3%. Changing the price of
electricity from the base case 0.5 cents per kWh to 0.3 or 0.7, changes the cost from
$34.85 to $34.11 or $35.59, respectively. A 40% (100 kW) change in the amount of heat
generated in the dry room changes the temperature setting of the dry room inlet air and
therefore the heat load, thereby changing the cost by ~60 cents per pack. Changing the
COP from 3.5 to 3 or 4, changes the cost by approximately 10 cents per pack, while a 1
cent per kWh change in the price of natural gas changes the operations cost by about 11
Page 18 of 35
Figure 8. Effect of plant life (amortization period), dry room volume, price of electricity, heat generated in the
dry room, the Coefficient of Performance, and the price of Natural Gas on the operating cost of the dry room in
dollars per pack. The numbers in the plot represent the differential from the base case cost of $34.85 per pack.
favorable set can be selected such that it lowers both the energy consumption and cost
Lowering the purge rate will reduce both the cost and energy demand (Figure 7).
The savings has to be balanced against the risk of potential for impurity buildup
Page 19 of 35
Sizing the heat exchanger in the desiccant regeneration loop showed a reduction
in operating costs, where the differential savings diminish at the larger approach
temperatures (Figure 2). However, a smaller heat exchanger will increase the
total energy demand of the plant and therefore the greenhouse emissions
footprint.
total energy demand and the cost. However, this also transfers the burden of
moisture removal to the zeolite wheel, which is likely to increase the cost of
calculations. Removing the moisture from the small volume of make-up air is
perhaps more effective than removing it from the large volume of air going to
removal load should have a marked effect on the cost of the dry room operation.
The cumulative effects of the combination of eliminating the Pre-Cool station and
the heat exchanger are shown in Table 11. The former reduces the energy demand by
12% (relative to the base case), and then the elimination of the heat exchanger
increases the energy demand up to 487 kW, or 22% above the base case. The cost of
operations for the combination of changes is reduced to $32 from the base case of $35
per pack.
Page 20 of 35
Table 11. Cumulative effects of progressive changes in the design and operating conditions on energy demand
and costs.
The scenarios simulated for this study are based on steady state conditions. Real
systems are dynamic and are therefore typically sensor driven, where the air quality
(humidity, temperature, concentrations of key components e.g., CO2, etc.) in the dry
room and at various points within the system are monitored continuously. When the
ambient air has low humidity or the moisture released/introduced into the dry room is
lower than the rated capacity, the automated controller with an appropriate algorithm
can reduce the energy demand and cost by a combination of one or more of the
following: (i) lowering the purge / fresh feed rate, (ii) raising the temperature set points
at Pre-Cool and Cool stations, (iii) slowing the revolution rate of the desiccant wheel.
The combination of sensors and a smart controller enable the detection of or prediction
of off-design conditions and are beneficial in that the system will not need to be
designed for excessive large air flow rates to recover from upset conditions, such as
frequent or prolonged opening of the air lock door, introduction of a batch of materials
with higher moisture content, number of workers present in the room being more than
failures. The development of the algorithm for these controllers would be helped with a
4. Conclusions
Page 21 of 35
The results from the process model provide an understanding of the interactions of
the design and operating parameters. Such a model (or its results) can be incorporated
in the process control algorithm of a dry room so that the operation is optimized for a
Sensitivities of the various input parameters indicate that the amount of air needed
has the biggest impact on the energy need and the cost of operations.
The mass of air that flows through the dry room affects the energy needs and
the size of the equipment, and directly affects the cost of operations. Thus,
smaller rooms operating with low turnovers can reduce the energy demand
and cost.
The heat exchanger plays a very important role in recycling heat. The cases
studied suggest that eliminating the heat exchanger would reduce the dollar
cost. However, that would sharply increase the total energy demand of
Even though low purge rates reduce the cost of operations, certain minimum
the zeolite wheel, but increases the overall cooling load and the energy
demand.
Page 22 of 35
Ultimately, the energy demand and cost of operations is dependent on the quantity
of air that has to be managed, which is directly dependent on the volume of the dry
room, the air turnover rate in the dry room, and the amount of purge necessary.
5. Abbreviations
COP Coefficient of Performance
kW kilowatt
NG Natural gas
RH Relative Humidity
Acknowledgments
The authors wish to acknowledge Kevin G. Gallagher and Gary Henriksen for their help in
preparing this manuscript. Support from David Howell and Peter Faguy at the Vehicle
Technologies Office, Office of Energy Efficiency and Renewable Energy, U.S. Department of
Energy, , is gratefully acknowledged. The submitted manuscript has been created by UChicago
Page 23 of 35
Argonne, LLC, Operator of Argonne National Laboratory (“Argonne”). Argonne, a U.S.
Department of Energy Office of Science laboratory, is operated under contract no. DE-AC02-
06CH11357. The U.S. Government retains for itself, and others acting on its behalf, a paid-up
works, distribute copies to the public, and perform publicly and display publicly, by or on behalf
of the Government.
Page 24 of 35
Bibliography
[ J. Pinho, "Dry Rooms: Why they are needed and a Review of the complex issues
2] associated with building them - particularly the large ones required to mass produce lithium
3]
[ M. Koltypin, D. Aurbach, L. Nazar and B. Ellis, "On the Stability of LiFePO4 Olivine
Page 25 of 35
7] Advanced Secondary Batteries, Seoul, Korea, 1996.
[ K.-S. Lee and S.-H. Choi, "Effect of geometric parameters on ventilation performance in
9] Relationship between the dry room parameters and the moisture control unit.," Journal of
November 2015].
[ M. Peters, K. Timmerhaus and R. West, Plant Design and Economics for Chemical
http://www.cse.anl.gov/BatPaC/.
[ P. Nelson, K. Gallagher, I. Bloom and D. Dees, "Modeling the Performance and Cost of
14] http://www.hermescatalyst.com/images/stories/pdf/Hermes_application_brochure.pdf.
Page 26 of 35
Page 27 of 35
Table 1. Assumed / Input Parameters in Dry Room Process Model (Base Case)
Assumption / Input Parameter Value
Ratio of Dry-Room-Air to Make-Up-Air 19
Make-Up Air Temperature 33 °C
Make-Up Air Relative Humidity 50 %
Temperature after Pre-Cool (A2) 9 °C
Temperature rise through Filter and Blower (A5) 3 °C
Temperature after Cooler (A5-A6) 10 °C
Moisture Level in Dry Room Inlet Air 15 ppmv (0.066 gpp)
Desiccant Capacity (MS-4A) 0.15 gH2O/gsolid
Desiccant in Solid Support 1 wt.%
Heat of Adsorption (MS-4A) 4,200 kJ/kgH2O
No. of Persons in Dry Room (30 workers x 24 hours) 720 man-hours/day
Moisture Contribution from Personnel 1500 gr/man-hour [7] [9]
Moisture Content in Negative Electrodes 0.05 wt.%
Door Opening / Closing 120 per day
Moisture Level of Dry Room Exit Air 100 ppmv (0.44 gpp)
Heat Generated in Dry Room (Equipment+Personnel) 250 kW
Page 28 of 35
Table 2. Moisture Content and Energy Demands in the Process (Base Case)
Calculated Results
Moisture Content at A2 1.14%
(50 gpp)
Moisture Removed at Pre-Cool (A1-A2) 10.6 g/s
Cooling Load at Pre-Cool (A1-A2) 57 kW
Temperature of Blended Air Stream at A3 24 °C
Moisture Content at A3 659 ppm
2.9 gpp
Moisture Removed at Cool (A5-A6) -
Cooling Load at Cool (A5-A6) 426 kW
Moisture Removed at Desiccant Wheel (A7-A8) 9.5 g/s
Cooling Load at Post Cool (A9-A10) -
Heating Load at Post-Heat (A9-A10) 63 kW
Dry Room Inlet Temperature (A10) 14 °C
Air Flow through Dry Room 19.6 m3/s
Desiccant Regeneration Heat Load (B10-B11) 30 kW
Total Cooling Load 483 kW
Electric Power for Refrigeration 138 kW
Electric Power for Blowers 167 kW
Total Thermal + Electric Load 398 kW
Page 29 of 35
Table 3. Costs for the Base Case System
Cost of Delivered Capital Equipment $741,000
Cost of Electricity ($0.05/kWh, $367/day) $134,000 per year
Cost of Natural Gas ($0.02/kWh, $44/day) $16,000 per year
Cost of Labor (14 man-hours/day) $78,000 per year
Cost of Utilities $180,000 per year
Page 30 of 35
Table 4. Assumed Input Parameters in Cost Estimate
Assumption / Input Parameter Estimated % Of Range %
1. Direct Costs
A. Purchased Equipment Model Model
Installation Model Purchased Equipment 25-55%
B. Buildings, process and auxiliary 30% Purchased Equipment 20-60
C. Service facilities and yard improvements 40% Purchased Equipment 40-60
D. Land 0% Purchased Equipment 0
2. Indirect Costs
A. Engineering and supervision 5% Direct Costs 5-10
B. Construction expense and contractor's fee 10% Direct Costs 5-15
C. Contingency 5% Fixed Cap. Investment 5-10
3. Fixed Capital Investment = I + II
4. Working Capital 5% Fixed Cap. Investment 5-10
5. Total Capital Investment = III + IV
Page 31 of 35
Table 5. Moisture Source in Dry Room
Moisture Source in Dry Room g/s %
Personnel 0.81 66
Door 1.3x10-4
Negative Electrodes 0.42 34
Total 1.23 100
Page 32 of 35
Table 7. Effect of the Pre-Cool Temperature on Heating and Cooling
Pre-Cool Temperature 33°C 25°C 15°C 9°C 1°C
Page 33 of 35
Table 10. The heating and cooling needs, and the cost of operating the dry room at different
purge rates.
Purge Rate, % 5 10 15 20
Pre-Cool, kW 57 119 190 269
Cool, kW 426 429 432 435
Post-Cool, kW - - 6.3 40.5
Total Cooling, kW 483 548 628 745
Post-Heat, kW 63 28 - -
Regen Heat, kW 30 70 120 178
Total Heating, kW 93 99 120 178
Total Energy Need, kW 398 448 521 645
Cost per Pack, $/pack $34.85 $35.76 $36.85 $38.37
Table 11. Cumulative effects of progressive changes in the design and operating conditions on
energy demand and costs.
Total
Energy Cost per
Demand Pack
Base Case 398 kW $34.85
1. Eliminate Pre-Cool 351 kW $34.36
2. Eliminate Heat Exchanger from Regeneration Loop 487 kW $32.01
Page 34 of 35
Table 12. Effect of Ambient Air Temperature Heating and Cooling Needs, and Costs (RH=50%).
Ambient T, °C 40 33 20 10 0 -17.8
Ambient T, °F 104 91.4 68 50 32 0
Pre-Cool Load, kW 89 57 14 1 0 0
Cool Load, kW 426 426 426 426 415 393
Post-Cool Load, kW - - - - - -
Post-Heat Load, kW 63 63 63 79 89 96
Total Energy Need, kW 407 398 385 396 401 400
Cost of Electricity, K$ 138 134 128 127 125 122
Cost of Natural Gas, K$ 16.2 16.2 16.2 18.8 20.2 21.3
Cost per Pack, $/pack 35.11 34.85 34.51 34.53 34.50 34.38
Page 35 of 35