Sigineer Power M3048BP M5000H 48BP Solar Inverter Manual 202112122
Sigineer Power M3048BP M5000H 48BP Solar Inverter Manual 202112122
Sigineer Power M3048BP M5000H 48BP Solar Inverter Manual 202112122
com
Manufacturer Information
Sigineer Power Limited
Email: info@sigineer.com
TEL: +86 769 82817616
US Warehouse: 4415 S 32nd St, Phoenix, AZ 85040
1
www.sigineer.com
Table of Content
1 Important Safety Information ......................................................................................................................... 1
1.1 General Safety Precautions .......................................................................................................................... 1
1.2 Precautions When Working with Batteries .................................................................................................. 2
1.3 Target Group ................................................................................................................................................ 2
2 Introduction ..................................................................................................................................................... 2
2.1 General Information ..................................................................................................................................... 2
2.2 Mechanical Design....................................................................................................................................... 3
2.3 Features ........................................................................................................................................................ 4
2.4 Electrical Performance ................................................................................................................................. 4
2.4.1 DC to AC Invert ................................................................................................................................. 4
2.4.2 AC & MPPT Charger ......................................................................................................................... 4
2.4.3 DC&AC Transfer ............................................................................................................................... 7
2.4.4 Power Saver ....................................................................................................................................... 7
2.4.5 Protections.......................................................................................................................................... 8
2.4.6 Remote Monitoring ............................................................................................................................ 9
2.4.7 LCD & Specification Setup ............................................................................................................... 9
2.4.8 Audible Alarm .................................................................................................................................. 24
2.4.9 FAN Operation ................................................................................................................................. 24
2.4.10 Auto Generator Start Dry Contact.................................................................................................. 25
2.4.11 Automatic Recovery Operation ...................................................................................................... 25
2.4.12 Batteryless Operation ..................................................................................................................... 25
2.4.13 Advanced Utility Charging & Bypass Control With Timer ........................................................... 26
2.4.14 Automatic Neutral-to-Ground Bonding ......................................................................................... 26
2.4.15 Lithium Battery Wakeup ................................................................................................................ 26
2.4.16 Other Features ................................................................................................................................ 27
3 Installation..................................................................................................................................................... 27
3.1 Location .............................................................................................................................................. 27
3.2 Unpacking and Inspection................................................................................................................... 27
3.3 Battery Wiring ..................................................................................................................................... 28
3.4 PV Wiring ........................................................................................................................................... 31
3.5 AC Wiring ........................................................................................................................................... 31
3.6 Communication With Lithium Batteries ............................................................................................. 33
3.7 Inverter Parallel Operation ......................................................................................................................... 35
3.7.1 Parallel in Single Phase to Expand Power ....................................................................................... 35
3.7.2 Parallel To Form Three Phase .......................................................................................................... 38
3.7.2 Parallel To Form Split Phase ............................................................................................................ 42
3.7.4 LCD Setting For Parallel Operation ................................................................................................ 43
3.8 Communication with Computer .......................................................................................................... 45
3.9 Grounding ........................................................................................................................................... 46
4 Maintenance & Troubleshooting .................................................................................................................. 47
5 Warranty ....................................................................................................................................................... 51
Appendix 1 : M3048BP M5000H-48BP Solar Inverter Spec Sheet ................................................................ 51
Please record the Sigineer Power unit’s model and serial number in case you need to provide this
information in the future. It is much easier to record this information now than try to gather it after
the unit has been installed.
Order Number:
Model Number: / Serial Number:
2
www.sigineer.com
1
www.sigineer.com
FOR SUCH USES. USING THE INVERTER/CHARGER WITH THESE PARTICULAR EQUIPMENTS
IS AT YOUR OWN RISK.
2 Introduction
The M3048BP & M5000H-48BP transformerless Off Grid Solar Inverter/Charger is a combination of 4
products:
1. Transformerless DC to AC power inverter
2. AC to DC utility battery charger
3. 80A(M3048BP) and 100A(M5000H-48BP) MPPT Solar Charger Controller
4. High Speed DC/AC Transfer Switch.
It is a very technically advanced off grid solar inverter on the market.
Some solar inverter on the market physically includes a solar charger which has no communication with the
2
www.sigineer.com
circuit of the inverter.
Our MPPT charger is electrically integrated into the inverter design and is able to harness the PV production
to charge batteries when the inverter is powered off.
Its powerful DSP (digital signal processor) makes them very versatile and almost all of its specifications can
be adjusted via its top cover LCD or remote LCD panel, such as AC output voltage, frequency, power
priority, low/high battery cutoff, charging profiles & amperage, DC/AC transfer conditions, etc.
The M3048BP & M5000H-48BP model with 48V DC input and output pure sine wave single phase output.
You can get split phase or three phase power by stacking them up to 6 pcs.
The single unit can operate without batteries connected.
The timer built in the inverter enables the inverter to use utility power for the loads and battery charging at
preset time.
It supports different types of remote monitoring with Remote LCD Panel (Sold separately), Wi-Fi or GPRS
module or computer.
The BMS port communicates with lithium battery for optimal operation of batteries.
It also has a programmable “US2” setting which works with lithium batteries without BMS communication
with the inverter.
The 200% surge capacity of 5 seconds makes it possible to support demanding inductive loads.
Thus the M Series Solar Inverter/Charger is suitable for a myriad of applications including renewable energy
systems, utility, truck, RV and emergency vehicles etc.
To get the most out of the power inverter, it must be installed, used and maintained properly. Please read the
instructions in this manual before installing and operating.
3
www.sigineer.com
2.3 Features
*Automatic Solar Charging When the Inverter is Powered Off
*Auto Generator Start
*Batteryless Operation
*Advanced Utility Charging & Bypass Control with Timer
*Overload Bypass
*Battery Polarity Reverse Protection
*Smart remote monitor with WIFI or GPRS Module
*Remote LCD Panel with Adjustable Parameters
*80A/100A MPPT Solar Charger
*Maximum THD: 3% at nominal battery voltage
*Powerful 4-stage power factor corrected battery charger
*High surge output capability, 200% peak load for 5 seconds
*Low quiescent current, low power ‘Power Saver Mode’ to conserve energy
*Equalization Charging
*20ms transfer time from AC to battery for the continuous load operation
*Thermally controlled variable speed fan for more efficient cooling
*Extensive protections against various harsh situations
*Solar Priority or SBU developed for renewable energy systems
*Parallel operation up to 6 units, capable of forming three phase or split phase output
2.4.1 DC to AC Invert
Overload Capacity
The M3048BP & M5000H-48BP inverter/charger has different overload capacities, making it ideal to
handle demanding loads.
1 For 110%<Load<150%, Fault (Power off) after 10 seconds.
2 For 150%<Load≤200%, Fault (Power off) after the 5 seconds.
Caution:
After the inverter is switched on, it takes a finite time for it to self diagnose and get ready to deliver full
power. Hence, the user should always switch on the load(s) after a few seconds of switching on the inverter
to avoid switching on the load before the inverter is powered on. This may prematurely trigger the overload
protection. When a load is switched on, it may require a higher initial power surge to start. If multiple loads
are being powered, they should be switched on one by one so that the inverter is not overloaded by the
higher starting surge.
4
www.sigineer.com
helpful if this powerful charger applies charging on a small capacity battery bank.
The max charging current decreases according to the input AC voltage.
There are three main charging stages:
Bulk Charging: This is the initial stage of charging. While Bulk Charging, the charger supplies the battery
with controlled constant current. The charger will remain in Bulk charge until the Absorption charge voltage
(determined by the Battery Type selection) is achieved.
Software timer will measure the time from charger start until the battery charger reaches 0.3V below the
boost voltage, then take this time as T0 and T0×10 = T1.
Absorb Charging: This is the second charging stage and begins after the absorb voltage has been reached.
Absorb Charging provides the batteries with a constant voltage and reduces the DC charging current in order
to maintain the absorb voltage setting.
In this period, the inverter will start a T1 timer; the charger will keep the boost voltage in Boost CV mode
until the T1 timer has run out. Then drop the voltage down to the float voltage. The timer has a minimum
time of 1 hour and a maximum time of 12 hours. When charging current reduces to below 0.01C, the charger
will go to the float charge.
Float Charging: The third charging stage occurs at the end of the Absorb Charging time. While Float
charging, the charge voltage is reduced to the float charge voltage (determined by the Battery Type
selection*). In this stage, the batteries are kept fully charged and ready if needed by the inverter.
If the battery type is selected as “lithium battery”, our charger will drastically reduce the charging current to
zero once float voltage is reached.
The charging capacity will go to peak in around 3 seconds, this may probably cause a generator to drop
frequency, making inverter transfer to battery mode.
It is suggested to gradually put charging load on the generator by switching the charging switch from min to
max, together with the 15s switch delay, our inverter gives the generator enough time to spin up.
Battery Equalization
5
www.sigineer.com
Equalization function is added into the M series inverter charge controller. It reverses the buildup of
negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of
the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the
plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery.
Therefore, it’s recommended to equalize battery periodically.
How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 43 first. Then, you may
apply this function in device by either one of following methods:
1. Setting equalization interval in program 47.
2. Active equalization immediately in program 48.
When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is
active immediately, the controller will start to enter Equalize stage.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to
battery equalization voltage point, the charge controller will extend the battery equalized time until battery
voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization
voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return
to float stage.
The M Series pure sine wave inverter/charger is built with MPPT solar charging modules up to 100A.
Model # AC Charging Current MPPT Solar Charger Max Charging Current
M3048BP 40A 80A 80A
M5000H-48BP 80A 100A 100A
The MPPT Solar Charger will automatically work when the inverter is powered off.
Even when the power switch is in unit off position, the built-in solar charger will automatically work when
6
www.sigineer.com
PV input voltage and battery voltage is qualified, this is to optimize solar production for battery charging.
But the inverter will not convert battery power to AC output.
When the battery is fully charged, the inverter will keep the battery capacity at 100%, and convert the extra
PV power directly from DC to AC to power loads.
When the battery is fully charged, the voltage has to drop by 2 volts (or below 95% of SOC when BMS
communication is established) to activate the charger.
7
www.sigineer.com
In “Power saver” mode, the inverter will draw power mainly in sensing moments, thus the idle consumption
is reduced from 60 watts to 30 watts.
Note: The minimum power of a load to take inverter out of sleep mode (Power Saver On) is 100
Watts.
When the inverter is in idle, even there is AC input power, the inverter will discharge the battery as
the LCD, relay, fans are powered by DC.
In the “search sense” mode, the LED will blink and the inverter will make a ticking sound. At full output
voltage, the inverter will make a steady humming sound. When the inverter is used as an “uninterruptible”
power supply the search sense mode function should be defeated.
Exceptions
Some devices, when scanned by the load sensor, cannot be detected. Small fluorescent lights are the most
common example. (Try altering the plug polarity by turning the plug over.) Some computers and
sophisticated electronics have power supplies that do not present a load until line voltage is available. When
this occurs, each unit waits for the other to begin. To drive these loads, either a small companion load must
be used to bring the inverter out of its search mode, or the inverter may be programmed to remain operating
at full output voltage.
2.4.5 Protections
The M Series inverter/charger is equipped with extensive protections against various harsh situations/faults.
These protections include:
⚫ AC Input over voltage protection/AC Input low voltage protection
⚫ Low battery alarm/High battery alarm
⚫ Over temperature protection/Over load protection
⚫ Short Circuit protection (1s after fault)
⚫ Battery Polarity Reverse Protection
Users can customize whether the inverter should automatically restart or not after some of these protections.
Warning !
The below mistakes will damage the inverter permanently and must be avoided:
*Reverse the PV input polarity.
*Use any third-party accessories, communication cables on the inverter.
8
www.sigineer.com
*Wire the AC input power to the AC output terminals.
To monitor the inverter on a computer, please download the software (SG Solar Power Monitor) from our
website in the Support>Software Download section.
The M series inverters can be remotely monitored by a Wi-Fi or GPRS module plugged into its USB port.
The Wi-Fi / GPRS module is a plug-and-play monitoring device which allows users to monitor the status of
the PV system from a mobile phone APP or from the website anytime anywhere.
The inverter’s AC output power can be powered on and off via APP.
The Sigineer Monitor APP will automatically refresh the data in every 5 minutes. To access real date, please
roll down the screen to refresh.
To monitor the inverter via both WiFi and USB port, the RMT-WiFi module can be connected via a short
extension cable.
The operation and display panel area includes three LED indicators, four function keys and a LCD display.
It shows very rich operating info.
1 LCD display 2 Status indicator 3 Charging indicator 4 Fault indicator 5 Function buttons
9
www.sigineer.com
Green Solid On Battery is fully charged.
Flashing Battery is being charged.
Red Solid On Fault occurs in the inverter.
Flashing Warning condition occurs in the inverter.
Button Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting
mode or to enter setting mode
Icon Description
AC Input Information
AC input icon
Indicate AC input power, AC input voltage, AC input frequency, AC input
current
Indicate AC power loads in bypass
PV Input Information
PV input icon
Output Information
Inverter icon
Load Information
Load icon
10
www.sigineer.com
Other Information
Indicate output source priority: solar first, utility first, SBU mode or SUB
mode
Indicate warning code or fault code
CC&CV Charge Mode Battery Voltage @ Battery Voltage @50%> Battery Voltage @ Icon
Load >50% Load > 20% Load < 20%
<48V < 41.2V < 43.6V <44.8V
Load Information
Indicates overload.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
0%~24% 25%~49% 50%~74% 75%~100%
11
www.sigineer.com
Indicates unit connects to the mains.
These three signs indicate the output priority. SOL.FIRST indicates solar first.
BAT.FIRST indicates battery first. UTI.FIRST indicates utility first.
Mute Operation
Indicates unit audible alarm is disabled.
LCD SETTING
The M 5KW inverter LCD allows users to virtually change all of its specs. It will enter setting mode if the
ENTER button is held for 3 seconds. Press “UP” or “DOWN” button to select setting programs, and then
press “ENTER” button to confirm the selection or ESC button to exit.
12
www.sigineer.com
When solar is gone in SBU mode, the power priority becomes battery>utility, battery priority is higher than
utility priority.
In this mode, the inverter will transfer between DC and AC as per the settings of program 12 and 13. Users
can set it to utility priority to stop the cycling.
01 SUB Priority
Solar energy provides power to the loads as the first priority.
If solar energy is not sufficient to power all connected loads, solar and utility will power loads at the same
time.
Battery provides power to the loads only when solar energy is not sufficient and there is no utility.
03:UPS
In UPS Mode, the acceptable AC input voltage range:
M3048BP 95-140Vac±7V
M5000H-48BP 170~280VAC±7V.
03: GEN
In Generator Mode, the acceptable AC input voltage range:
M3048BP 65-140Vac±7V
M5000H-48BP 90~280VAC±7V
Note: When the inverter is connected to a generator, the generator should be more than twice the inverter
nominal power.
04: SdS
When the power saver mode is disabled, the inverter will output full voltage, and the idle power is about
50-60 watts.
04: SEN
13
www.sigineer.com
If the power saver mode is enabled, the output of inverter will be off when connected load is low or not
detected.
The threshold for load detection is 100W. The idle power in power saver mode is about 30 watts.
05: FLd
Flood Battery: CV :58.4V, Float 56V.
05: USE
User-Defined
If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program
19, 20 and 21. This setting works for GEL batteries etc.
05: US2
User-Defined 2
This US2 setting is designed for the inverter to work with lithium battery without communication via BMS.
As floating charging is not required for lithium batteries, in US2 mode, the program 19&20 will be
interlocked and set to the same value whenever one of them is changed.
Compared with USE, the charger in US2 will immediately reduce charging current when the preset voltage
in 19 is reached.
NOTE: The US2 will not optimally charge the lithium battery due to the lack of BMS communication. The
battery capacity icon bar doesn’t reflect the actual battery capacity; it is converted from battery voltage. For
more details, please refer to page 13.
When the inverter is in US2, it could not correctly display the accurate SOC of the lithium batteries.
The displayed SOC is converted from battery voltage. The SOC will change only when the battery voltage
changes big enough.
Due to the ripple current from the utility charger, when “US2” is set for charging lithium batteries, it is
recommended to set the max utility charging current at 30% of the nominal charge current.
05: LI
Lithium
This setting only works when inverter communicates with lithium battery BMS built with the same protocol.
The program is set to “LI”, the LCD will show a hidden program of 36 about BMS protocol types.
There are many lithium battery BMS communication protocols, L01, L02 to L99.
For Sigineer Power LFP power walls, the protocol is L01.
When the battery type set as “LI”, the maximum charge current can be modified by the user.
Note: When the communication fails, the inverter will cut off output.
RS485 communication protocol is L01 to L50.
The CAN communication protocol is L51 to L99.
06: LFE
14
www.sigineer.com
When this feature is enabled, the inverter will attempt to restart 3 times after overloads, if it still fails to start
the load after 3 attempts, it will show warning code 07.
The solar charger has higher priority than the utility charger, if the max charging current and utility charger
is set to the same value, the solar charger will still work.
If setting value in Program 02 is smaller than that in Program 11, the final charging current is set according
to Program 02 for utility charger.
14:CSO
Solar Priority
Solar energy will charge battery as the first priority.
Utility will charge battery only when solar energy is not available (lost).
14:SNU
Solar and Utility (Default)
Solar energy and utility will both charge battery.
15
www.sigineer.com
14:OSO
Solar Only
Solar energy will be the only charger source no matter utility is available or not.
But when the battery voltage drops below the setting of 21(Low DC Cut-off Voltage) , the utility power will
be used to force a charging cycle to avoid battery over discharging.
If this off grid solar inverter is working in DC to AC invert mode, only solar energy can charge the battery.
Solar energy will charge battery if it's available and sufficient.
If user-defined setting (USE/US2) is selected in program 5, this program can be set up.
When the battery is charged to CV setting, the voltage has to drop by 2 volts to activate the charger.
After User-defined (USE/US2) setting is selected in program 5, this program can be set up
Low DC cut-off voltage will be fixed to setting value regardless of load percentage.
When low DC Cut-Off voltage is reached:
1. If battery is the only power source, inverter will shut down.
2. If PV energy and battery power are available, inverter will charge battery without AC output.
3. If PV energy, battery power and utility are all available, inverter will transfer to line mode and provide
output power to loads and charge the battery at the same time.
16
www.sigineer.com
When low battery voltage protection occurs and qualified PV or AC power inputs, the inverter will
automatically charge and invert DC to AC when the battery voltage reach 54V Or 10% more SOC than low
battery cut off in Lithium mode).
To make it work, the power switch must remain in the original “ON” position.
23:SIG
Single Unit Operation.
When unit operates separately and is not in parallel operation.
23:PAL
Parallel in Single Phase
When the units are used in parallel with single phase
23: 3P1/3P2/3P3
Parallel in Three Phase: 3P1, 3P2, 3P2
It requires at least 3 inverters to support three-phase equipment, 1 inverter in each phase.
Please select “3P1” for the inverters connected to L1 phase, “3P2” for the inverters connected to L2 phase
and “3P3” for the inverters connected to L3 phase.
17
www.sigineer.com
18
www.sigineer.com
19
www.sigineer.com
11 Maximum Utility Charging 10A to Max(default 30A)
Current
12 DC to AC Transfer Voltage Default 46.0V,
44.0V~51.2V resettable,
12 DC to AC Transfer Voltage Lithium mode: default
40%, 5%~50% resettable
13 AC to DC Transfer Voltage Default 54.0V,
48.0V~58.0V resettable,
13 AC to DC Transfer Voltage Li mode: default 80%,
60%~100% resettable
14 Charger Power Source Solar Priority
Priority
14 Charger Power Source Solar and Utility
Priority (Default)
14 Charger Power Source Solar Only
Priority
20
www.sigineer.com
23 AC Output Mode Split phase
46 Battery Equalization
Setting range is from
Timeout
5min to 900min.
Increment of each click
is 1 min.
47 Equalization Interval Setting range is from 1 to
90 days. Increment of
each click is 1 day.
21
www.sigineer.com
49 Utility charging time
50 AC output time
① AC Input current
② Output current
③ Load percentage
④ PV input current
⑤ Battery charging current
⑥Warning or Fault code
① AC input power in Watts
② Inverter temperature
③ Load power in Watts
④ PV energy sum in KWH
⑤ Battery percentage
⑥Warning or Fault code
22
www.sigineer.com
Time
(15:20:10, December 15, 2018)
The LCD will display different inverter status when the up or down button is pressed.
The last page of LCD shows the software version of the inverter PCB. There are 8 digits.
23
www.sigineer.com
at line mode. Charging by utility
No battery connected
The inverter is built with automatic PV and utility power wakeup feature.
When the power switch is in power off, and qualified PV input, the PV charger will be activated, and the
rest part of the inverter will remain powered off.
In this mode, the utility power can only illuminate the LCD, it can’t charge batteries.
When the inverter shuts off due to low battery voltage, and the switch is kept on “on” position, the inverter
will use qualified utility power or PV power to charge batteries and wake up at “cold start voltage” to
discharge the battery to provide AC output.
If the inverter is set in SOL or SUB, the automatic wake up feature will charge battery close to “Utility to
Battery switch” voltage, and then cut off utility charger, switch to DC to AC model.
24
www.sigineer.com
For low battery alarm, when battery setting is not in “LI” mode, it is 2 volts higher than Low DC Cut-off
Voltage for 48Vdc model and 1 volt higher than Low DC Cut-off Voltage for 24Vdc model.
When the battery setting is in “LI” mode, low battery alarm is 5% higher than Low DC Cut-off Soc.
25
www.sigineer.com
different power supply levels.
Users can also use utility power as to supplement the load consumption to save power.
This design avoids two neutral-to-ground connections from existing at the same time, thereby preventing an
electrical shock hazard between the vehicle/boat’s neutral and the external AC source’s neutral.
26
www.sigineer.com
The M3048BP and M5000H-48BP inverters will use solar or AC input power to wake up overdischarged
lithium battery by a boost circuitry.
When they detect a 0V battery, the charger will output a small current of 48Vdc voltage to awaken the
lithium batteries.
Once the lithium battery voltage is charged back to normal (over 48Vdc), the charger will proceed with the
charging settings of program 19 and 20.
3 Installation
3.1 Location
Follow all the local regulations to install the inverter.
Please install the equipment in a location of Dry, Clean, Cool with good ventilation.
Working temperature: ‐10℃ to 55℃(14℉ to 131℉)
Storage temperature: ‐15℃ to 60℃(5℉to 140℉)
Relative Humidity: 5% to 95%,non-condensing
Cooling: Forced air
Warning! Operation in a condensing environment will invalid warranty.
27
www.sigineer.com
Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat
dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY
Install the unit by screwing the six sets of screws.
Install the unit by screwing three screws. It’s recommended to use M4 or M5 screws.
Note: For proper air circulation to dissipate heat, allow a clearance of approx. 20cm to the side and approx.
50 cm above and below the unit. Be sure to install each unit in the same level.
Ring terminal:
28
www.sigineer.com
Battery cables must have crimped (or preferably, soldered and crimped) copper compression lugs unless
aluminum mechanical lugs are used. Soldered connections alone are not acceptable. High quality, UL-listed
battery cables are available .These cables are color-coded with pressure crimped, sealed ring terminals.
Battery terminal must be clean to reduce the resistance between the DC terminal and cable connection. A
buildup of dirt or oxidation may eventually lead to the cable terminal overheating during periods of high
current draw. Use a stiff wire brush and remove all dirt and corrosion from the battery terminals and cables.
Note: for lead acid battery, the recommended charge current is 0.2C(C-battery capacity)
29
www.sigineer.com
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected
tightly.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative
(-).
Reducing RF interference
To reduce the effect of radiated interference, twist the DC cables. To further reduce RF interference, shield
the cables with sheathing /copper foil / braiding.
Taping battery cables together to reduce inductance
Do not keep the battery cables far apart. In case it is not convenient to twist the cables, keep them taped
together to reduce their inductance. Reduced inductance of the battery cables helps to reduce induced
voltages. This reduces ripple in the battery cables and improves performance and efficiency.
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC
over-current protector or disconnect device between battery and inverter. It may not be requested to have a
disconnect device in some applications, however, it’s still requested to have over-current protection installed.
Please refer to typical amperage in below table as required fuse or breaker size.
30
www.sigineer.com
WARNING input connections will cause permanent damage to the inverter which is not covered under
warranty. Always check polarity before making connections to the inverter.
The inverter contains capacitors that may produce a spark when first connected to battery.
Do not mount in a confined a battery or gas compartment.
Ensure the inverter is off before disconnecting the battery cables, and that AC power is
disconnected from the inverter input.
3.4 PV Wiring
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between
the inverter and PV modules.
The PV terminal pins can accept cable size up to 8AWG, and the torque for the screws is 1.6Nm.
Max. PV Array Open Circuit Voltage is 450Vdc, pls make sure Open circuit Voltage (Voc) of PV modules
does not exceed 450V.
3.5 AC Wiring
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
31
www.sigineer.com
maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is
50A for 5KVA.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect
input and output connectors.
N→Neutral (Blue)
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
*Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal
L N
Ground (yellow-green) LINE (brown or black) Neutral (blue)
Wiring Instruction for M5000H 230V Single Phase inverter in 120/240 split phase system
Sigineer Power’s M5000H-48BP 230V single phase inverter is an international model which can be used in
120/240V Split phase systems in America and also 230Vac single phase systems.
Users from 120/240Vac 60Hz split phase phase electricity system( 120VL+120V L+ N+G) must strictly
follow our wiring instructions, or damage to inverter will occur.
32
www.sigineer.com
NOTE: The M5000H-48BP can work with Sigineer Power transformer to split the 240Vac into 120/240Vac
voltages.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are reverseed, it may cause utility
short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s
required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and
recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage,
please check with manufacturer of air conditioner that if it’s equipped with time-delay function before
installation. Otherwise, this off grid solar inverter will trigger overload fault and cut off output to protect
your appliance but sometimes it still causes internal damage to the air conditioner.
Connect one end of RJ45 of battery to BMS communication port of inverter. Connect the other end of RJ45
cable to battery communication port.
33
www.sigineer.com
Note: if you choose lithium battery, make sure to connect the BMS communication cable between the
battery and the inverter. You need to choose battery type as “lithium battery”
34
www.sigineer.com
05.
Please refer to “05: LI” for details.
Note:
When multiple inverters are paralleled with multiple lithium batteries, please follow the below setup.
1 Out of the lithium batteries, set one unit as the master and the rest as slave as per the lithium DIP/ADS
switches.
2 Connect the master battery to the inverter which shows “Host”.
If the user connects the master battery to one of the rest the slave inverters in the group, the inverter can
automatically work as the master unit, but the communication will be slower.
TheM5000H-48BP inverters can be stacked up to 6 pcs to expand output power in 230Vac or create
230/400Vac three phase.
The M3048BP can be stacked up to 6 pcs to expand output power in 120Vac or create 120/208Vac three
phase.
When they are stacked, all the inverters will share the loads evenly. Each will be ready output full power
even the load is under nominal power, none of them will go into power saver mode.
This is designed to handle sudden loads fluctuations.
Note:
When there is more than one inverter paralleled in one phase, if the slave unit shut off, the rest inverters in
the system will continue operate.
If the master unit shuts off, all the rest inverters will shut off.
35
www.sigineer.com
36
www.sigineer.com
37
www.sigineer.com
Two inverters in one phase and only one inverter for the remaining phases:
Power Wire Connection
38
www.sigineer.com
Two inverters in two phases and only one inverter for the remaining phase:
Power Wire Connection
39
www.sigineer.com
Three inverters in one phase and only one inverter for the remaining two phases:
Power Wire Connection
Three inverters in one phase, two inverters in second phase and one inverter for the third phase:
40
www.sigineer.com
Power Wire Connection
Four inverters in one phase and one inverter for the other two phases:
Power Wire Connection
WARNING: Do not connect the current sharing cable between the inverters which are in different phases.
41
www.sigineer.com
Communication Connection
Communication Connection
42
www.sigineer.com
Power Connection
Communication Connection
43
www.sigineer.com
Step 5: If there is no more fault alarm, the parallel system is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to
the load.
Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases
are matched with unit setting, they will work normally. Otherwise, they will display warning 15/16 and will
not work in the line mode.
LCD display in L1-phase unit LCD display in L2-phase unit LCD display in L3-phase unit
Step 5: If there is no more fault alarm, the system to support 3-phase equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to
the load.
Note 1: If there’s only one inverter in L1-phase, the LCD will show as “HS”. If there is more than one
inverter in L1-phase, the LCD of the HOST inverter will show as “HS”, the rest of L1-phase inverters will
show as “3P1”.
Note 2: To avoid overload occurring, before turning on breakers in load side, it’s better to have whole
system in operation first.
Note 3: Transfer time for this operation exists. Power interruption may happen to critical devices, which
cannot bear transfer time.
44
www.sigineer.com
Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and split phases
are matched with unit setting, they will work normally. Otherwise, they will display warning 15/16 and will
work in the line mode. (Split phase 120V/240V)
LCD display in L1-phase unit LCD display in L2-phase unit
Step 5: If there is no more fault alarm, the system with split phase output is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to
the load.
Note 1: If there’s only one inverter in L1-phase, the LCD will show as “HST”. If there is more than one
inverter in L1-phase, the LCD of the HOST inverter will show as “HST”, the rest of L1-phase inverters will
show as “2P0”.
Note 2: To avoid overload occurring, before turning on breakers in load side, it’s better to have whole
system in operation first.
Note 3: Transfer time for this operation exists. Power interruption may happen to critical devices, which
cannot bear transfer time.
45
www.sigineer.com
3.9 Grounding
Connect an AWG 8 gauge or greater copper wire between the grounding terminal on the inverter and the
earth grounding system or the vehicle chassis.
46
www.sigineer.com
01 Fan is locked
02 Over temperature
47
www.sigineer.com
80 CAN fault
81 Host loss
Warning Indicator
12 Solar charger stops due to low battery Beep once every second
No beep
19 Battery disconnect
48
www.sigineer.com
TroubleShooting
Buzzer beeps Fault code 01 Fan fault. 1.Check whether all fans are working properly.
49
www.sigineer.com
continuously and red 2.Replace the fan.
LED is on.(Fault code) 1.Check whether the air flow of the unit is blocked or
Internal temperature of component
Fault code 02 whether the ambient temperature is too high.
is over 100℃.
2.Check whether the thermistor plug is loose.
Buzzer beeps once
Restart the unit, if the error happens again, please
Battery is over-charged.
every second, and red return to repair center.
Fault code 03
LED is flashing. Check if spec and quantity of batteries are meet
The battery voltage is too high.
requirements.
(Warning code)
1.Measure battery voltage in DC input.
Warning code 04 The battery voltage/SOC is too low. 2.Check battery SOC in LCD when use Li battery.
3.Recharge the battery.
Check if wiring is connected well and remove
Fault code 05 Output short circuited.
abnormal load.
1.Reduce the connected load.
Output abnormal (Inverter voltage
Fault code 06/58 2. Restart the unit, if the error happens again, please
is over 150Vac or below 40Vac).
return to repair center.
The inverter is overload 110% and Reduce the connected load by switching off some
Fault code 07
time is up. equipment.
1.If you connect to a lithum battery without
communication, check whether the voltage points of
the program 19 and 21 are too high for the lithum
Fault code 08 Bus voltage is too high.
battery.
2. Restart the unit, if the error happens again, please
return to repair center.
Restart the unit, if the error happens again, please
Fault code 09/53/57 Internal components failed.
return to repair center.
The input status is different in Check if AC input wires of all inverters are
Warning code 15
parallel system. connected well.
Warning code 16 Input phase is not correct. Change the input phase S and T wiring.
1.Make sure the parallel setting are the same
The output phase not correct in
Warning code 17 system(sigle or paralle; 3P1,3P2,3P3).
parallel.
2.Make sure all phases inverters are power on.
1.Check whether communication line is correct
Li battery can't communicate to the
Warning code 20 connection between inverter and battery.
inverter.
2.Check whether BMS protocol type is correct setting.
Fault code 51 Over current or surge.
Restart the unit, if the error happens again, please
Fault code 52 Bus voltage is too low.
return to repair center.
Fault code 55 Output voltage is unbalanced
Battery is not connected well If the battery is connected well, please return to
Fault code 56
or fuse is burnt. repair center.
1. Check whether the AC output connected to the grid
input.
2. Check whether Program 8 settings are the same for
all parallel inverters
Fault code 60 Negative power fault 3. Check whether the current sharing cables are
connected well in the same parallel phases.
4. Check whether all neutral wires of all parallel units
are connected together.
5. If problem still exists, contact repair center.
1. Check whether the parallel communication cables
Fault code 80 CAN fault
are connected well.
2. Check whether Program 23 settings are right for the
Fault code 81 parallel system.
Host loss
3. If problem still exists, contact repair center
Note: To restart the inverter, all power sources need to be disconnected. After the LCD screen light is off, only use the battery to
restart the inverter.
50
www.sigineer.com
5 Warranty
We warrant this product against defects in materials and workmanship for a period of one year from the date
of purchase and will repair or replace any defective M Series Inverter when directly returned, postage
prepaid, to manufacturer. This warranty will be considered void if the unit has suffered any obvious physical
damage or alteration either internally or externally and does not cover damage arising from improper use
such as plugging the unit into an unsuitable power sources, attempting to operate products with excessive
power consumption requirements, reverse polarity, or use in unsuitable climates.
WARRANTY DOES NOT INCLUDE LABOR, TRAVEL CHARGES, OR ANY OTHER COSTS
INCURRED FOR REPAIR, REMOVAL, INSTALLATION, SERVICING, DIAGNOSING OR
HANDLING OF EITHER DEFECTIVE PARTS OR REPLACEMENT PARTS. THE WARRANTOR
ASSUMES NO LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND.
LOSS OR DAMAGE: Loss or damage in transit is the responsibility of the carrier. Any claim should be
filed with the delivering transport company. Invoice, Bill of Lading and Delivery receipt with damage noted
therein must accompany any claims for freight damage. Claims for shortage and lost shipments must be
made in writing to the shipper within 3 days of the receipt of shipment. Claims not reported within this time
frame will not be honored.
This warranty does not apply to and we will not be responsible for any defect in or damage to:
a) the product if it has been misused, neglected, improperly installed, physically damaged or altered, either
internally or externally, or damaged from improper use or use in an unsuitable environment; violations of
the warnings in the manual will invalid the warranty.
b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or input
voltage that creates operating conditions beyond the maximum or minimum limits listed in the product
specifications including high input voltage from generators and lightning strikes;
c) the product if repairs have been done to it other than by us or its authorized service centers;
Low AC Voltage Trip 95Vac±7V (UPS); 65Vac±7V (Appliances) 170Vac±7V (UPS); 90Vac±7V (Appliances)
Low AC Voltage Return 100Vac±7V (UPS); 70Vac±7V (Appliances) 180Vac±7V (UPS); 100Vac±7V (Appliances)
Nominal AC Input Frequency 50Hz / 60Hz (Auto Detection) 50Hz / 60Hz (Auto Detection)
51
www.sigineer.com
10 ms(Typical) ; 20 ms Max; <30ms 10 ms(Typical) ; 20 ms Max; <30ms
Transfer Time
Parallel Parallel
AC Voltage Regulation (Batt. Mode) 120 VAC ±5% 230 VAC ±5%
Surge AC Output Power 6000W (5 secs) 10000W (5 secs)
Output Frequency 50Hz/60Hz(default) 50Hz/60Hz(default)
Cold Start Battery Voltage* (Without 46.0Vdc/Li Mode(Default 30%, Low DC 46.0Vdc/Li Mode(Default 30%, Low DC
PV or AC) Cut-off SOC +10%) Cut-off SOC +10%)
52
www.sigineer.com
PV Voltage Accuracy +/-2V +/-2V
*Cold start voltage is the minimal battery voltage for the inverter to power on without PV or AC input.
※Errors and omissions reserved. Specifications in this manual are subject to change without prior
notice.
53