Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Sigineer Power M3048BP M5000H 48BP Solar Inverter Manual 202112122

Download as pdf or txt
Download as pdf or txt
You are on page 1of 55

www.sigineer.

com

Transformerless Off Grid


Solar Inverter Charger
User’s Manual
For Model:
M3048BP
M5000H-48BP

Version 2.1 (PN:M35202111222)

Manufacturer Information
Sigineer Power Limited
Email: info@sigineer.com
TEL: +86 769 82817616
US Warehouse: 4415 S 32nd St, Phoenix, AZ 85040

1
www.sigineer.com

Table of Content
1 Important Safety Information ......................................................................................................................... 1
1.1 General Safety Precautions .......................................................................................................................... 1
1.2 Precautions When Working with Batteries .................................................................................................. 2
1.3 Target Group ................................................................................................................................................ 2
2 Introduction ..................................................................................................................................................... 2
2.1 General Information ..................................................................................................................................... 2
2.2 Mechanical Design....................................................................................................................................... 3
2.3 Features ........................................................................................................................................................ 4
2.4 Electrical Performance ................................................................................................................................. 4
2.4.1 DC to AC Invert ................................................................................................................................. 4
2.4.2 AC & MPPT Charger ......................................................................................................................... 4
2.4.3 DC&AC Transfer ............................................................................................................................... 7
2.4.4 Power Saver ....................................................................................................................................... 7
2.4.5 Protections.......................................................................................................................................... 8
2.4.6 Remote Monitoring ............................................................................................................................ 9
2.4.7 LCD & Specification Setup ............................................................................................................... 9
2.4.8 Audible Alarm .................................................................................................................................. 24
2.4.9 FAN Operation ................................................................................................................................. 24
2.4.10 Auto Generator Start Dry Contact.................................................................................................. 25
2.4.11 Automatic Recovery Operation ...................................................................................................... 25
2.4.12 Batteryless Operation ..................................................................................................................... 25
2.4.13 Advanced Utility Charging & Bypass Control With Timer ........................................................... 26
2.4.14 Automatic Neutral-to-Ground Bonding ......................................................................................... 26
2.4.15 Lithium Battery Wakeup ................................................................................................................ 26
2.4.16 Other Features ................................................................................................................................ 27
3 Installation..................................................................................................................................................... 27
3.1 Location .............................................................................................................................................. 27
3.2 Unpacking and Inspection................................................................................................................... 27
3.3 Battery Wiring ..................................................................................................................................... 28
3.4 PV Wiring ........................................................................................................................................... 31
3.5 AC Wiring ........................................................................................................................................... 31
3.6 Communication With Lithium Batteries ............................................................................................. 33
3.7 Inverter Parallel Operation ......................................................................................................................... 35
3.7.1 Parallel in Single Phase to Expand Power ....................................................................................... 35
3.7.2 Parallel To Form Three Phase .......................................................................................................... 38
3.7.2 Parallel To Form Split Phase ............................................................................................................ 42
3.7.4 LCD Setting For Parallel Operation ................................................................................................ 43
3.8 Communication with Computer .......................................................................................................... 45
3.9 Grounding ........................................................................................................................................... 46
4 Maintenance & Troubleshooting .................................................................................................................. 47
5 Warranty ....................................................................................................................................................... 51
Appendix 1 : M3048BP M5000H-48BP Solar Inverter Spec Sheet ................................................................ 51
Please record the Sigineer Power unit’s model and serial number in case you need to provide this
information in the future. It is much easier to record this information now than try to gather it after
the unit has been installed.
Order Number:
Model Number: / Serial Number:

2
www.sigineer.com

1 Important Safety Information


Save This Manual! Read this manual before installation, it contains important safety, installation
and operating instructions. Keep it in a safe place for future reference.
All wiring must follow the National Electric Code, Provincial or other codes in effect at the time
of installation, regardless of suggestions in this manual. This off grid solar inverter should be
connected to a grounded wiring system. If the system ground is floating, please follow the codes
in effect.
MISTAKES TO AVOID
1 Don’t reverse the PV input polarity.
2 Don’t use any third-party accessories, communication cables on the inverter.
3 Don’t wire the AC input power to the AC output terminals.
4 Don’t install the inverter without AC input surge protection device (SPD)or lightning
protection.

1.1 General Safety Precautions


1.1.1 Before installing and using the M Series Off Grid Solar Inverter Charger, read the manual and
cautionary markings on the Inverter/Charger enclosure. Be sure to read all instructions and cautionary
markings for any equipment attached to this unit. Installers must be certified technicians or electricians.
1.1.2 This product is designed for indoor/compartment installation. Do not expose the inverter/charger to
rain, snow, spray, bilge or dust. To reduce the risk of hazard, do not cover or obstruct the ventilation
openings. Do not install the inverter/charger in a zero-clearance compartment. Overheating may result.
Allow at least 30CM (11.81 inches) of clearance around the inverter for air flow. Make sure that the air can
circulate freely around the unit. A minimum air flow of 145CFM is required.
1.1.3 To avoid a risk of fire and electronic shock. Make sure that existing wiring is in good electrical
condition; and that wire size is not undersized. Do not operate the Inverter with damaged or substandard
wiring.
1.1.4 This equipment contains components which can produce arcs or sparks. To prevent fire or explosion
do not install in compartments containing batteries or flammable materials or in locations which require
ignition protected equipment. This includes any space containing gasoline-powered machinery, fuel tanks,
or joints, fittings, or other connection between components of the fuel system. See Warranty for instructions
on obtaining service.
1.1.5 Do not dis-assemble the Inverter/Charger. It contains no user serviceable parts. Attempting to service
the Inverter/Charger yourself may result in a risk of electrical shock or fire. Internal capacitors remain
charged after all power is disconnected.
1.1.6 To reduce the risk of electrical shock, disconnect both AC and DC power from the Inverter/Charger
before attempting any maintenance or cleaning. Turning off controls will not reduce this risk
CAUTION: Equipment damage
The output side of the inverter’s AC wiring should at no time be connected to public power or a generator.
This condition is far worse than a short circuit. If the unit survives this condition, it will shut down until
corrections are made.
Installation should ensure that the inverter’s AC output is, at no time, connected to its AC input.

WARNING: LIMITATIONS ON USE


SPECIFICALLY, PLEASE NOTE THAT THE INVERTER/CHARGER SHOULD NOT BE USED IN
CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES.
WE MAKE NO WARRANTY OR REPRESENTATION IN CONNECTION WITH THEIR PRODUCTS

1
www.sigineer.com
FOR SUCH USES. USING THE INVERTER/CHARGER WITH THESE PARTICULAR EQUIPMENTS
IS AT YOUR OWN RISK.

1.2 Precautions When Working with Batteries


1.2.1 If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye,
immediately flood eye with running cold water for at least 20 minutes and get medical attention
immediately.
1.2.2 Never smoke or allow a spark or flame in the vicinity of battery or engine.
1.2.3 Do not drop a metal tool on the battery. The resulting spark or short-circuit on the battery of other
electrical part may cause an explosion.
1.2.4. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a
lead-acid battery. A lead-acid battery produces a short-circuit current high enough to weld a ring or the like
to metal, causing a severe burn.
1.2.5 To reduce the risk of injury, charge only rechargeable batteries accepted by our inverter such as
deep-cycle lead acid, lead antimony, lead calcium gel cell, absorbed mat, NiCad/NiFe or Lithium battery.
Other types of batteries may burst, causing personal injury and damage. NEVER charge a frozen battery.
1.2.6 Don’t install the inverter near batteries, the inverter may heat battery electrolyte and cause corrosive
fumes to vent and damage/corrode nearby electronics or metals.

1.3 Target Group


This document is intended for qualified persons and end users. Tasks that do not require any particular
qualification can also be performed by end users. Qualified persons must have the following skills:
Knowledge of how an inverter works and is operated
Training in how to deal with the dangers and risks associated with installing and using electrical devices and
installations
Training in the installation and commissioning of electrical devices and installations
Knowledge of the applicable standards and directives
Knowledge of and compliance with this document and all safety information

2 Introduction

2.1 General Information


Thank you for purchasing the M3048BP & M5000H-48BP Off Grid Solar Inverter/Chargers.

The M3048BP & M5000H-48BP transformerless Off Grid Solar Inverter/Charger is a combination of 4
products:
1. Transformerless DC to AC power inverter
2. AC to DC utility battery charger
3. 80A(M3048BP) and 100A(M5000H-48BP) MPPT Solar Charger Controller
4. High Speed DC/AC Transfer Switch.
It is a very technically advanced off grid solar inverter on the market.
Some solar inverter on the market physically includes a solar charger which has no communication with the

2
www.sigineer.com
circuit of the inverter.
Our MPPT charger is electrically integrated into the inverter design and is able to harness the PV production
to charge batteries when the inverter is powered off.
Its powerful DSP (digital signal processor) makes them very versatile and almost all of its specifications can
be adjusted via its top cover LCD or remote LCD panel, such as AC output voltage, frequency, power
priority, low/high battery cutoff, charging profiles & amperage, DC/AC transfer conditions, etc.
The M3048BP & M5000H-48BP model with 48V DC input and output pure sine wave single phase output.
You can get split phase or three phase power by stacking them up to 6 pcs.
The single unit can operate without batteries connected.
The timer built in the inverter enables the inverter to use utility power for the loads and battery charging at
preset time.

It supports different types of remote monitoring with Remote LCD Panel (Sold separately), Wi-Fi or GPRS
module or computer.

The BMS port communicates with lithium battery for optimal operation of batteries.
It also has a programmable “US2” setting which works with lithium batteries without BMS communication
with the inverter.
The 200% surge capacity of 5 seconds makes it possible to support demanding inductive loads.
Thus the M Series Solar Inverter/Charger is suitable for a myriad of applications including renewable energy
systems, utility, truck, RV and emergency vehicles etc.
To get the most out of the power inverter, it must be installed, used and maintained properly. Please read the
instructions in this manual before installing and operating.

2.2 Mechanical Design

1.LCD Display 2.Status Indicator 3.Charging Indicator


4.Fault Indicator 5. Function Buttons 6. AC Input Terminal
7. Wi-Fi/GPRS Port 8. USB Port(connects to 9. Dry Contact
computer)
10. PV Input Terminal 11. ON/OFF Power Switch 12. Battery Terminals
13 Parallel Communication Ports 14 Current Sharing Ports 15 AC Output Terminal
16 AC Breaker 17 BMS Communication Port(For 18 RS485 Communication Port
RS485/CAN Protocol) (For Expansion)

3
www.sigineer.com

2.3 Features
*Automatic Solar Charging When the Inverter is Powered Off
*Auto Generator Start
*Batteryless Operation
*Advanced Utility Charging & Bypass Control with Timer
*Overload Bypass
*Battery Polarity Reverse Protection
*Smart remote monitor with WIFI or GPRS Module
*Remote LCD Panel with Adjustable Parameters
*80A/100A MPPT Solar Charger
*Maximum THD: 3% at nominal battery voltage
*Powerful 4-stage power factor corrected battery charger
*High surge output capability, 200% peak load for 5 seconds
*Low quiescent current, low power ‘Power Saver Mode’ to conserve energy
*Equalization Charging
*20ms transfer time from AC to battery for the continuous load operation
*Thermally controlled variable speed fan for more efficient cooling
*Extensive protections against various harsh situations
*Solar Priority or SBU developed for renewable energy systems
*Parallel operation up to 6 units, capable of forming three phase or split phase output

2.4 Electrical Performance

2.4.1 DC to AC Invert

Overload Capacity
The M3048BP & M5000H-48BP inverter/charger has different overload capacities, making it ideal to
handle demanding loads.
1 For 110%<Load<150%, Fault (Power off) after 10 seconds.
2 For 150%<Load≤200%, Fault (Power off) after the 5 seconds.

Caution:
After the inverter is switched on, it takes a finite time for it to self diagnose and get ready to deliver full
power. Hence, the user should always switch on the load(s) after a few seconds of switching on the inverter
to avoid switching on the load before the inverter is powered on. This may prematurely trigger the overload
protection. When a load is switched on, it may require a higher initial power surge to start. If multiple loads
are being powered, they should be switched on one by one so that the inverter is not overloaded by the
higher starting surge.

2.4.2 AC & MPPT Charger


The M Series pure sine wave inverter/charger is equipped with an active PFC (Power Factor Corrected)
multistage battery charger. The PFC feature is used to control the amount of power used to charge the
batteries in order to obtain a power factor as close as possible to 1.
The M Series pure sine wave inverter/charger has a very rapid charge current available, and the max charge
current can be adjusted from 10% to 100% in small increments on the LCD of the inverter. This will be

4
www.sigineer.com
helpful if this powerful charger applies charging on a small capacity battery bank.
The max charging current decreases according to the input AC voltage.
There are three main charging stages:
Bulk Charging: This is the initial stage of charging. While Bulk Charging, the charger supplies the battery
with controlled constant current. The charger will remain in Bulk charge until the Absorption charge voltage
(determined by the Battery Type selection) is achieved.
Software timer will measure the time from charger start until the battery charger reaches 0.3V below the
boost voltage, then take this time as T0 and T0×10 = T1.
Absorb Charging: This is the second charging stage and begins after the absorb voltage has been reached.
Absorb Charging provides the batteries with a constant voltage and reduces the DC charging current in order
to maintain the absorb voltage setting.
In this period, the inverter will start a T1 timer; the charger will keep the boost voltage in Boost CV mode
until the T1 timer has run out. Then drop the voltage down to the float voltage. The timer has a minimum
time of 1 hour and a maximum time of 12 hours. When charging current reduces to below 0.01C, the charger
will go to the float charge.

Float Charging: The third charging stage occurs at the end of the Absorb Charging time. While Float
charging, the charge voltage is reduced to the float charge voltage (determined by the Battery Type
selection*). In this stage, the batteries are kept fully charged and ready if needed by the inverter.
If the battery type is selected as “lithium battery”, our charger will drastically reduce the charging current to
zero once float voltage is reached.

The charging capacity will go to peak in around 3 seconds, this may probably cause a generator to drop
frequency, making inverter transfer to battery mode.
It is suggested to gradually put charging load on the generator by switching the charging switch from min to
max, together with the 15s switch delay, our inverter gives the generator enough time to spin up.

To guarantee the best performance of AC charger when the AC input is from a


generator, the standby generator should be of at least 150% higher capacity than the
inverter.
Warning! Operation with an under-rated generator or generator with unqualified
Caution: wave form may cause premature failure which is not under warranty.

Battery Equalization

5
www.sigineer.com
Equalization function is added into the M series inverter charge controller. It reverses the buildup of
negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of
the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the
plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery.
Therefore, it’s recommended to equalize battery periodically.
How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 43 first. Then, you may
apply this function in device by either one of following methods:
1. Setting equalization interval in program 47.
2. Active equalization immediately in program 48.
When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is
active immediately, the controller will start to enter Equalize stage.

Equalize charging time and timeout


In Equalize stage, the controller will supply power to charge battery as much as possible until battery
voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain
battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting
battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to
battery equalization voltage point, the charge controller will extend the battery equalized time until battery
voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization
voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return
to float stage.

The M Series pure sine wave inverter/charger is built with MPPT solar charging modules up to 100A.
Model # AC Charging Current MPPT Solar Charger Max Charging Current
M3048BP 40A 80A 80A
M5000H-48BP 80A 100A 100A

The MPPT Solar Charger will automatically work when the inverter is powered off.
Even when the power switch is in unit off position, the built-in solar charger will automatically work when

6
www.sigineer.com
PV input voltage and battery voltage is qualified, this is to optimize solar production for battery charging.
But the inverter will not convert battery power to AC output.
When the battery is fully charged, the inverter will keep the battery capacity at 100%, and convert the extra
PV power directly from DC to AC to power loads.

When the battery is fully charged, the voltage has to drop by 2 volts (or below 95% of SOC when BMS
communication is established) to activate the charger.

2.4.3 DC&AC Transfer


While in the Standby Mode, the AC input of the inverter is continually monitored. Whenever AC power falls
out of the trip voltages, the inverter automatically transfers back to the Invert Mode with minimum
interruption to your appliances.
The transfer from AC mode to Inverter mode occurs in approximately 10 milliseconds, with the worst case
of 20 milliseconds. And it is the same time from Inverter mode to Standby mode.
Though it is not designed as a computer UPS system, this transfer time is usually fast enough to hold them
up as devices like computers can generally tolerate a max power loss of 20ms.
When the inverters are paralleled, the transfer time is <30ms.

Bypass output power derating:


When AC input voltage drops below 170Vac, the output power will be de-rated linearly to as long as 20% at 90Vac.

M5000H-48BP Output Power


Rated Power
20% Power

90V 170V 280V Input Voltage

M3048BP Output Power


Rated Power
20% Power

65V 95V 140V Input Voltage

2.4.4 Power Saver


There are two working statuses for the inverters: “Power On” and “Power Off”.
When power switch is in the “Unit Off” position, the inverter is powered off.
When power switch is turned to “Power ON”, the inverter is powered on.
When the inverter is powered on, users can activate “power saver” in the program 04 of the software.
The “Power Saver” function is dedicated to conserve battery power when AC power demand is either
minimal or not required at all by the loads.
In this mode, the inverter pulses the AC output in every 30 seconds looking for an AC load (i.e., electrical
appliance). Whenever an AC load (greater than 100 watts) is turned on, the inverter recognizes the need for
power and automatically starts inverting and output goes to full voltage. When there is a small load (less
than 100 watts) detected, the inverter automatically goes back into search mode to minimize energy
consumption from the battery bank.

7
www.sigineer.com
In “Power saver” mode, the inverter will draw power mainly in sensing moments, thus the idle consumption
is reduced from 60 watts to 30 watts.

Power Saver On Power Saver Off Power Saver On (Load detected)

Note: The minimum power of a load to take inverter out of sleep mode (Power Saver On) is 100
Watts.
When the inverter is in idle, even there is AC input power, the inverter will discharge the battery as
the LCD, relay, fans are powered by DC.

For more detailed technical information, please contact us.

In the “search sense” mode, the LED will blink and the inverter will make a ticking sound. At full output
voltage, the inverter will make a steady humming sound. When the inverter is used as an “uninterruptible”
power supply the search sense mode function should be defeated.

Exceptions
Some devices, when scanned by the load sensor, cannot be detected. Small fluorescent lights are the most
common example. (Try altering the plug polarity by turning the plug over.) Some computers and
sophisticated electronics have power supplies that do not present a load until line voltage is available. When
this occurs, each unit waits for the other to begin. To drive these loads, either a small companion load must
be used to bring the inverter out of its search mode, or the inverter may be programmed to remain operating
at full output voltage.

2.4.5 Protections
The M Series inverter/charger is equipped with extensive protections against various harsh situations/faults.
These protections include:
⚫ AC Input over voltage protection/AC Input low voltage protection
⚫ Low battery alarm/High battery alarm
⚫ Over temperature protection/Over load protection
⚫ Short Circuit protection (1s after fault)
⚫ Battery Polarity Reverse Protection

Users can customize whether the inverter should automatically restart or not after some of these protections.

Warning !
The below mistakes will damage the inverter permanently and must be avoided:
*Reverse the PV input polarity.
*Use any third-party accessories, communication cables on the inverter.

8
www.sigineer.com
*Wire the AC input power to the AC output terminals.

2.4.6 Remote Monitoring


The M series inverter (produced after 2021 Nov) can be remotely monitored and controlled.
It supports 4 different types of remote monitoring
1. Plug in the remote LCD panel to the RS485 port.
2. Connects it to a computer via the USB port and monitor the inverter on the software.
3. Plugs a Wi-Fi or GPRS module into Wi-Fi port, monitor it on a computer or cellphone APP.
4. Connect to the RS485 port, it allows customer to monitor on their own software programmed with the
same protocol.

To monitor the inverter on a computer, please download the software (SG Solar Power Monitor) from our
website in the Support>Software Download section.

The M series inverters can be remotely monitored by a Wi-Fi or GPRS module plugged into its USB port.
The Wi-Fi / GPRS module is a plug-and-play monitoring device which allows users to monitor the status of
the PV system from a mobile phone APP or from the website anytime anywhere.
The inverter’s AC output power can be powered on and off via APP.

The Sigineer Monitor APP will automatically refresh the data in every 5 minutes. To access real date, please
roll down the screen to refresh.
To monitor the inverter via both WiFi and USB port, the RMT-WiFi module can be connected via a short
extension cable.

2.4.7 LCD & Specification Setup

Press the On/Off switch to turn on the unit.

The operation and display panel area includes three LED indicators, four function keys and a LCD display.
It shows very rich operating info.
1 LCD display 2 Status indicator 3 Charging indicator 4 Fault indicator 5 Function buttons

LED Indicator Operation Status


Green Solid On Output is powered by utility in AC mode.
Flashing Output is powered by battery or PV in battery
mode.

9
www.sigineer.com
Green Solid On Battery is fully charged.
Flashing Battery is being charged.
Red Solid On Fault occurs in the inverter.
Flashing Warning condition occurs in the inverter.

Button Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting
mode or to enter setting mode

Icon Description
AC Input Information

AC input icon
Indicate AC input power, AC input voltage, AC input frequency, AC input
current
Indicate AC power loads in bypass
PV Input Information
PV input icon

Indicate PV power, PV voltage, PV current, etc

Output Information

Inverter icon

Indicate output voltage, output current, output frequency, inverter temperature

Load Information

Load icon

Indicate power of load, power percentage of load


Indicate overload happened
Indicate short circuit happened
Battery Information
Indicate battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery
mode and charging status in line mode.
Indicate battery voltage, battery percentage, battery current

Indicate SLA battery


Indicate lithium battery
Indicate charging source priority: solar first, solar and utility, or only solar

10
www.sigineer.com
Other Information
Indicate output source priority: solar first, utility first, SBU mode or SUB
mode
Indicate warning code or fault code

Indicate a warning or a fault is happening

Indicate it’s during setting values

Indicate the alarm is disabled

In AC mode, battery icon will present Battery Charging Status


Status Battery voltage LCD Display
<48V 4 bars will flash in turns.
Constant Current mode / 48 ~ 50V Bottom bar will be on and the other three bars will
Constant Voltage mode flash in turns.
50 ~ 52V Bottom two bars will be on and the other two bars
will flash in turns.
> 52V Bottom three bars will be on and the top
bar will flash.
Floating mode. Batteries are fully charged. 4 bars will be on.

CC&CV Charge Mode Battery Voltage @ Battery Voltage @50%> Battery Voltage @ Icon
Load >50% Load > 20% Load < 20%
<48V < 41.2V < 43.6V <44.8V

48-50V 41.2-43.2V 43.6-45.6V 44.8-46.8V

50-52V 43.2-45.2V 45.6-47.6V 46.8-48.8V

>52V > 45.2V > 47.6V >48.8V

Load Information
Indicates overload.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
0%~24% 25%~49% 50%~74% 75%~100%

Mode Operation Information

11
www.sigineer.com
Indicates unit connects to the mains.

Indicates unit connects to the PV panel.

Indicates load is supplied by utility power.


Indicates the utility charger circuit is working.

Indicates the DC/AC inverter circuit is working.

These three signs indicate the output priority. SOL.FIRST indicates solar first.
BAT.FIRST indicates battery first. UTI.FIRST indicates utility first.
Mute Operation
Indicates unit audible alarm is disabled.

LCD SETTING
The M 5KW inverter LCD allows users to virtually change all of its specs. It will enter setting mode if the
ENTER button is held for 3 seconds. Press “UP” or “DOWN” button to select setting programs, and then
press “ENTER” button to confirm the selection or ESC button to exit.

Program 01: Power Priority for AC Loads

01 UEI: Utility Priority (Default)


In this mode, the utility will provide power to the AC loads as the first power source.
Solar and battery energy will provide power to the loads only when utility power is not available.
This mode works for applications with cheap utility power or using battery in power outages.

01 SOL: Solar Priority


In this mode, the solar energy provides power to the loads as the first power source.
If solar energy is insufficient, battery energy will be consumed.
Utility power will engage when one of below conditions happens:
1 Solar energy is not available (No PV production).
2 Battery voltage drops to either low-level warning voltage or the setting point in program 12 (DC to AC
Transfer Voltage in “SOL Priority”).
Once the solar power is lost, the utility will have higher priority than battery. This mode can be regarded as
“SUB”(Solar>Utility>Battery).
In this mode, the inverter will transfer between DC and AC as per the settings of program 12 and 13. Users
can set it to utility priority to stop the cycling.

01 SbU: SBU Priority


As indicated by the abbreviation, the power priority comes as solar>battery>utility.
Solar energy provides power as the first priority.
If solar energy is insufficient, battery energy will be consumed.
Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or
the setting point in program 12(DC to AC Transfer Voltage in “SBU Priority”).

12
www.sigineer.com
When solar is gone in SBU mode, the power priority becomes battery>utility, battery priority is higher than
utility priority.
In this mode, the inverter will transfer between DC and AC as per the settings of program 12 and 13. Users
can set it to utility priority to stop the cycling.

01 SUB Priority
Solar energy provides power to the loads as the first priority.
If solar energy is not sufficient to power all connected loads, solar and utility will power loads at the same
time.
Battery provides power to the loads only when solar energy is not sufficient and there is no utility.

Program 02: Maximum Charging Current


M3048BP model: default 40A, 10A~80A Settable
M5000H-48BP model: default 60A, 10A~100A Settable
(If Li is selected in program 5, this program can’t be set up)
The MPPT charger will stop when charging is completed. To activate the charger, the battery voltage must
drop at least 2 voltages below the lower value in program 19 and 20.

Program 03: AC Input Voltage Range

03 APL: Appliance Mode


In Appliance Mode, the acceptable AC input voltage range is
M3048BP 65-140Vac±7V
M5000H-48BP 90~280VAC±7V.

03:UPS
In UPS Mode, the acceptable AC input voltage range:
M3048BP 95-140Vac±7V
M5000H-48BP 170~280VAC±7V.

03: GEN
In Generator Mode, the acceptable AC input voltage range:
M3048BP 65-140Vac±7V
M5000H-48BP 90~280VAC±7V

Note: When the inverter is connected to a generator, the generator should be more than twice the inverter
nominal power.

Program 04: Power Saving Mode Enable/Disable

04: SdS
When the power saver mode is disabled, the inverter will output full voltage, and the idle power is about
50-60 watts.

04: SEN

13
www.sigineer.com
If the power saver mode is enabled, the output of inverter will be off when connected load is low or not
detected.
The threshold for load detection is 100W. The idle power in power saver mode is about 30 watts.

Program 05: Battery Type


05: AGN
AGM Battery (Default) : CV :56.4V, Float 54V.

05: FLd
Flood Battery: CV :58.4V, Float 56V.

05: USE
User-Defined
If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program
19, 20 and 21. This setting works for GEL batteries etc.

05: US2
User-Defined 2
This US2 setting is designed for the inverter to work with lithium battery without communication via BMS.
As floating charging is not required for lithium batteries, in US2 mode, the program 19&20 will be
interlocked and set to the same value whenever one of them is changed.
Compared with USE, the charger in US2 will immediately reduce charging current when the preset voltage
in 19 is reached.
NOTE: The US2 will not optimally charge the lithium battery due to the lack of BMS communication. The
battery capacity icon bar doesn’t reflect the actual battery capacity; it is converted from battery voltage. For
more details, please refer to page 13.
When the inverter is in US2, it could not correctly display the accurate SOC of the lithium batteries.
The displayed SOC is converted from battery voltage. The SOC will change only when the battery voltage
changes big enough.
Due to the ripple current from the utility charger, when “US2” is set for charging lithium batteries, it is
recommended to set the max utility charging current at 30% of the nominal charge current.

05: LI
Lithium
This setting only works when inverter communicates with lithium battery BMS built with the same protocol.
The program is set to “LI”, the LCD will show a hidden program of 36 about BMS protocol types.
There are many lithium battery BMS communication protocols, L01, L02 to L99.
For Sigineer Power LFP power walls, the protocol is L01.
When the battery type set as “LI”, the maximum charge current can be modified by the user.
Note: When the communication fails, the inverter will cut off output.
RS485 communication protocol is L01 to L50.
The CAN communication protocol is L51 to L99.

Program 06: Automatic Overload Restart


06: LFd
Disabled.

06: LFE

14
www.sigineer.com
When this feature is enabled, the inverter will attempt to restart 3 times after overloads, if it still fails to start
the load after 3 attempts, it will show warning code 07.

Program 07: Automatic OverTemp Restart

Program 08: AC Output Voltage


The AC output voltage between hot and neutral can be set to 208V, 220V, 230V and 240V for
M5000H-48BP and 100/110/120Vac for M3048BP.

Program 09: AC Output Frequency


The AC Output Frequency can be set to 50Hz or 60Hz.

Program 10: Number of 12V Batteries Connected In Series


The default value is 4. This program is only a reminder about the 12V battery quantity.

Program 11: Maximum Utility Charging Current


Model # Default Value Resettable Range
M3048BP 30A 0-40A
M5000H-48BP 30A 0-80A

The solar charger has higher priority than the utility charger, if the max charging current and utility charger
is set to the same value, the solar charger will still work.
If setting value in Program 02 is smaller than that in Program 11, the final charging current is set according
to Program 02 for utility charger.

Program 12 DC to AC Transfer Voltage


The setting works when program 01 is in “SBU Priority” or “Solar Priority” Mode.
Model # Default Value Resettable Range
M3048BP 46V/50% 44V~51.2V/6%-95%
M5000H-48BP
The battery SOC will be displayed when BMS communication is established.

Program 13 AC to DC Transfer Voltage


The setting works when program 01 is in “SBU Priority” or “Solar Priority” Mode.
Model # Default Value Resettable Range
M3048BP 54V/95% 48V~58V/10%-100%
M5000H-48BP
The battery SOC will be displayed when BMS communication is established.

Program 14 Charge Power Source Priority

14:CSO
Solar Priority
Solar energy will charge battery as the first priority.
Utility will charge battery only when solar energy is not available (lost).

14:SNU
Solar and Utility (Default)
Solar energy and utility will both charge battery.

15
www.sigineer.com

14:OSO
Solar Only
Solar energy will be the only charger source no matter utility is available or not.
But when the battery voltage drops below the setting of 21(Low DC Cut-off Voltage) , the utility power will
be used to force a charging cycle to avoid battery over discharging.

If this off grid solar inverter is working in DC to AC invert mode, only solar energy can charge the battery.
Solar energy will charge battery if it's available and sufficient.

Program 15 Alarm On/Off Control

Program 16 Backlight On/Off Control


When off is set, the LCD will go dim after 60 seconds left unattended.

Program 17 Beeps once between AC and DC Transfer

Program 18 Overload Bypass


When enabled, the unit will transfer to line mode if overload occurs in battery mode.

Program 19 C.V. Charging Voltage


Model # Default Value Resettable Range
M3048BP 56.4V 48V~58.4V
M5000H-48BP

If user-defined setting (USE/US2) is selected in program 5, this program can be set up.
When the battery is charged to CV setting, the voltage has to drop by 2 volts to activate the charger.

Program 20 Float Charging Voltage


Model # Default Value Resettable Range
M3048BP 54V 48V~58.4V
M5000H-48BP
If user-defined setting (USE/US2) is selected in program 5, this program can be set up

Program 21 Low DC Cut-Off Voltage

Model # Default Value Resettable Range


M3048BP 42V/20% 40V~48V/5%-50%
M5000H-48BP
The battery SOC will be displayed when BMS communication is established.

After User-defined (USE/US2) setting is selected in program 5, this program can be set up
Low DC cut-off voltage will be fixed to setting value regardless of load percentage.
When low DC Cut-Off voltage is reached:
1. If battery is the only power source, inverter will shut down.
2. If PV energy and battery power are available, inverter will charge battery without AC output.
3. If PV energy, battery power and utility are all available, inverter will transfer to line mode and provide
output power to loads and charge the battery at the same time.

16
www.sigineer.com
When low battery voltage protection occurs and qualified PV or AC power inputs, the inverter will
automatically charge and invert DC to AC when the battery voltage reach 54V Or 10% more SOC than low
battery cut off in Lithium mode).
To make it work, the power switch must remain in the original “ON” position.

Program 23 AC Output Mode


This setting is only available when the inverter is in standby mode (Switch off).
Power saving function will be automatically disabled when in parallel operation.

23:SIG
Single Unit Operation.
When unit operates separately and is not in parallel operation.

23:PAL
Parallel in Single Phase
When the units are used in parallel with single phase

23: 3P1/3P2/3P3
Parallel in Three Phase: 3P1, 3P2, 3P2
It requires at least 3 inverters to support three-phase equipment, 1 inverter in each phase.
Please select “3P1” for the inverters connected to L1 phase, “3P2” for the inverters connected to L2 phase
and “3P3” for the inverters connected to L3 phase.

23: 2P0+2P1: split phase 120V/208V; 2P0+2P2: split phase 120V/240V


Parallel in Split Phase(only for M3048BP)

Do NOT connect current sharing cable between units on different phases.

Program 28 Address setting


Default 001. 001-255. Settable. It is for external solar charger expansion.

Program 36 Lithium BMS Protocol


For Sigineer Power LFP power walls, the protocol is L01.
Please refer to “05: LI” for details.

Program 37 Real time setting---Year


Default 2018, range 2018~2099

Program 38 Real time setting---Month


Default 01, range 01~12

Program 39 Real time setting---Date


Default 01, range 01~31

Program 40 Real time setting---Hour


Default 00, range 00~23

Program 41 Real time setting---Minute


Default 00, range 00~59

17
www.sigineer.com

Program 42 Real time setting---Second


Default 00, range 00~59

Program 43 Battery Equalization


If “Flooded” or “User-Defined” is selected in program 05, this program can be set up. The Equalization is
banned for AGM batteries.

Program 44 Battery Equalization Voltage


Model # Default Value Resettable Range
M3048BP 58.4V 48-58.4V
M5000H-48BP

Program 45 Battery Equalized Time


Default 60min, 5min~900min Settable

Program 46 Battery Equalized Timeout


Default 120min, 5min~900min Settable

Program 47 Equalization Interval


Default 30days, 1 day~90 days Settable

Program 48 Equalization Activated Immediately


If equalization function is enabled in program 43, this program can be set up. If “Enable” is selected in this
program, it’s to activate battery equalization immediately and LCD main page will shows “Eq”.If “Disable”
is selected, it will cancel equalization function until next activated equalization time arrives based on
program 47 setting. At this time, “Eq” will not be shown in LCD main page

Program 49 Utility charging time


Allow utility to charge the battery all day run.
0000(default)
The timer allows utility to charge the battery at preset time.
Use 4 digits to represent the time period, the upper two digits represent the time when utility start to charge
the battery, setting range from 00 to 23, and the lower two digits represent the time when utility end to
charge the battery, setting range from 00 to 23.
(eg: 2320 represents the time allows utility to charge the battery is from 23:00 to the next day 20:59, and the
utility charging is prohibited outside of this period)

Program 50 AC output time


Allow inverter to power the load all day run.
0000(default)
The timer allows inverter to power the load at preset time.
Use 4 digits to represent the time period, the upper two digits represent the time when inverter start to power
the load, setting range from 00 to 23, and the lower two digits represent the time when inverter end to power
the load, setting range from 00 to 23.
(eg: 2320 represents the time allows inverter to power the load is from 23:00 to the next day 20:59, and the
inverter AC output power is prohibited outside of this period)

18
www.sigineer.com

Program # Description ICON


01 Power Priority for AC Utility Priority
Loads
01 Power Priority for AC Solar Priority
Loads
01 Power Priority for AC SBU Priority
Loads
01 Power Priority for AC SUB Priority
Loads
02 Maximum Charging Max PV+Utility
Current Charging Current
03 AC Input Voltage Range Appliance Mode
(Default)
03 AC Input Voltage Range UPS Mode

03 AC Input Voltage Range Generator mode

04: Power Saving Mode Saving mode disable


(Default)
04: Power Saving Mode Saving mode enable

05 Battery Type AGM Battery (Default)

05 Battery Type Flood Battery

05 Battery Type User-Defined

05 Battery Type User-Defined 2

05 Battery Type Lithium

06 Automatic Overload Restart Restart Disable (Default)

06 Automatic Overload Restart Restart Enable

07 Automatic OverTemp Restart Disable (Default)


Restart
07 Automatic OverTemp Restart Enable
Restart
08 AC Output Voltage 230V (Default)

09 AC Output Frequency 50Hz (Default)

10 Number of 12V Batteries The default value is 4 for


Connected In Series 48V model, and 2 for
24Vdc model.

19
www.sigineer.com
11 Maximum Utility Charging 10A to Max(default 30A)
Current
12 DC to AC Transfer Voltage Default 46.0V,
44.0V~51.2V resettable,
12 DC to AC Transfer Voltage Lithium mode: default
40%, 5%~50% resettable
13 AC to DC Transfer Voltage Default 54.0V,
48.0V~58.0V resettable,
13 AC to DC Transfer Voltage Li mode: default 80%,
60%~100% resettable
14 Charger Power Source Solar Priority
Priority
14 Charger Power Source Solar and Utility
Priority (Default)
14 Charger Power Source Solar Only
Priority

15 Alarm On/Off Control Audible Alarm on


(default)
15 Alarm On/Off Control Audible Alarm off(Mute)

16 Backlight On/Off Control Backlight on (default)

16 Backlight On/Off Control Backlight off

17 Beeps once between AC Alarm on (default)


and DC Transfer
17 Beeps once between AC Alarm off
and DC Transfer
18 Overload Bypass Bypass Disable
(default)
18 Overload Bypass Bypass enable

19 C.V. Charging Voltage 48V model: default


56.4V, 48.0V~58.4V
Settable
20 Float Charging Voltage

21 Low DC Cut-Off Voltage Without BMS


communication
21 Low DC Cut-Off Voltage With BMS
communication
23 AC Output Mode Single Unit Operation

23 AC Output Mode Parallel in Single Phase

23 AC Output Mode Three phase: 3P1, 3P2,


3P2

20
www.sigineer.com
23 AC Output Mode Split phase

28 RS485 Default 001. 001-255


Communication Address Settable. For external
solar charger expansion.
36 Lithium BMS Protocol Default L01

37 Real time setting---Year

38 Real time setting---Month

39 Real time setting---Date

40 Real time setting---Hour

41 Real time setting---Minute

42 Real time setting---Second


43 Battery Equalization Disabled (Default)

43 Battery Equalization Enable

44 Battery Equalization Default 58.4V, 48~60V


Voltage settable
45 Battery Equalization Time Setting range is from
5min to 900min.
Increment of each click
is 1min.

46 Battery Equalization
Setting range is from
Timeout
5min to 900min.
Increment of each click
is 1 min.
47 Equalization Interval Setting range is from 1 to
90 days. Increment of
each click is 1 day.

48 Equalization Activated Disabled (Default)


Immediately
48 Equalization Activated Enable
Immediately

21
www.sigineer.com
49 Utility charging time

50 AC output time

LCD Display Setting


The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable
information is switched in below order: input voltage, input frequency, PV voltage, MPPT charging current,
MPPT charging power, battery voltage, output voltage, output frequency, load percentage, load in VA, load
in Watt, DC discharging current, main CPU Version and second MCU Version.

Setting Information LCD display


① AC Input voltage
② Output voltage
③ Load percentage
④ PV input voltage
⑤ Battery voltage
⑥Warning or Fault code
(Default Display Screen)
① AC Input frequency
② Output frequency
③ Load power in VA
④ PV energy sum in KWH
⑤ Battery percentage
⑥Warning or Fault code

① AC Input current
② Output current
③ Load percentage
④ PV input current
⑤ Battery charging current
⑥Warning or Fault code
① AC input power in Watts
② Inverter temperature
③ Load power in Watts
④ PV energy sum in KWH
⑤ Battery percentage
⑥Warning or Fault code

22
www.sigineer.com

Firmware Version of Inverter PCB and MPPT


PCB
(CPU1: 040-00-b21; CPU2:041-00-b21)

Time
(15:20:10, December 15, 2018)

The LCD will display different inverter status when the up or down button is pressed.
The last page of LCD shows the software version of the inverter PCB. There are 8 digits.

Operating Mode Description

Operation mode Description LCD display


Standby mode / Power saving Charging by utility and PV Charging by utility
mode energy.
Note: *Standby mode: The
inverter is not turned on yet
but at this time, the inverter No output is
can charge battery without supplied by the
AC output. unit but it still can Charging by PV energy No charging
*Power saving mode: If charge batteries.
enabled, the output of inverter
will be off when connected
load is two low or not
detected.
Charging by utility and PV Charging by utility
energy
Fault mode
Note:
*Fault mode: Errors are PV energy and
caused by inside circuit error utility can charge
or external reasons such as batteries. Charging by PV energy No charging
over temperature, output short
circuited and so on.

The unit will Charging by PV energy


provide output
Line Mode power from the
mains. It can also
charge the battery

23
www.sigineer.com
at line mode. Charging by utility

No battery connected

Power from battery and PV energy

The unit will


provide output
Battery Mode power from
Power from battery only
battery and PV
power.

The inverter is built with automatic PV and utility power wakeup feature.
When the power switch is in power off, and qualified PV input, the PV charger will be activated, and the
rest part of the inverter will remain powered off.
In this mode, the utility power can only illuminate the LCD, it can’t charge batteries.

When the inverter shuts off due to low battery voltage, and the switch is kept on “on” position, the inverter
will use qualified utility power or PV power to charge batteries and wake up at “cold start voltage” to
discharge the battery to provide AC output.
If the inverter is set in SOL or SUB, the automatic wake up feature will charge battery close to “Utility to
Battery switch” voltage, and then cut off utility charger, switch to DC to AC model.

2.4.8 Audible Alarm


The inverter also gives audible alarms when the following situations occur.
Warning Buzzer beeps 0.5s every second.
Error Long Beep. Beeps 0.5s every 1s for 10s, shut off, then long beep for 60 seconds.

2.4.9 FAN Operation


For M Series 5KW models, there are two DC fans.
The DC fans will just the fan speed in a linear proportion according to load and charger wattage.
It will slow down after 1 minute when the triggering condition disappears.
Allow at least 30CM of clearance around the inverter for air flow. Make sure that the air can circulate freely
around the unit.
Fan noise level <60db at a distance of 1 meter.

24
www.sigineer.com

2.4.10 Auto Generator Start Dry Contact


The solar inverter is built with a very versatile 3-pin dry contact rated at 3A/250VAC on the rear
panel.
The internal relays of the dry contact will give out either “close” or “open” signals.
These signals can be used to indicate the low battery voltage alarm or control a generator.
The NC & C pins are constantly close, they will open when battery voltage reaches low alarm or the setting
in Program 12 (DC to AC Transfer).
The NO & C pins are constantly open, they will close when battery voltage reaches low alarm or the setting
in Program 12 (DC to AC Transfer) to start the generator. Once the generator is started and battery voltage
increases with charging, the dry contact pins will open at the setting of Program 13 (AC to DC Transfer) to
avoid overcharging.

Unit Status Operation NC & C NO & C


Power Off Inverter off ( no AC output) Close Open
Power On Inverter in AC Bypass Mode Close Open
Inverter in DC to Program 01 set Battery Level < Low Battery Open Close
AC Mode to Utility Alarm
Priority Battery Level > Program 13 Close Open
(AC to DC Transfer)
Program 01 set Battery Level < Program 12 Open Close
to SBU or (DC to AC Transfer)
Solar Priority Battery Level > Program 13 Close Open
(AC to DC Transfer)

For low battery alarm, when battery setting is not in “LI” mode, it is 2 volts higher than Low DC Cut-off
Voltage for 48Vdc model and 1 volt higher than Low DC Cut-off Voltage for 24Vdc model.
When the battery setting is in “LI” mode, low battery alarm is 5% higher than Low DC Cut-off Soc.

2.4.11 Automatic Recovery Operation


For the M3048BP & M5000H-48BP, it is designed with automatic recovery from:
⚫ Overloads shutoff
⚫ Over temperature shutoff
⚫ Low battery voltage cutoff.
Pls to “Program 06 Automatic Overload Restart ” “Program 07: Automatic OverTemp Restart
”and “Program 21 Low DC Cut-Off Voltage” for more details.

2.4.12 Batteryless Operation


The M5000H-48BP inverter can operate without batteries.
It can convert DC solar power to AC and/or bypass AC input power to power loads.
This function is designed to save battery investment.
In DC to AC mode, the AC output voltage and power will fluctuate with the PV input power.
If the AC input power supply is unstable, the AC output of the inverter will be unstable as well.
The batteryless operation mode only works with loads that can tolerate voltage fluctuations and can work at

25
www.sigineer.com
different power supply levels.
Users can also use utility power as to supplement the load consumption to save power.

2.4.13 Advanced Utility Charging & Bypass Control With Timer


The M3048BP and M5000H-48BP inverters are designed with a timer to control its AC output power and
AC charger at preset time frame.
This will enable the inverter to use utility power at off peak hours to save the electricity bills.

2.4.14 Automatic Neutral-to-Ground Bonding


The automatic neutral-to-ground bonding feature uses an internal relay that automatically connects the AC
neutral output to the vehicle/boat’s safety ground (“bonding” it) in Inverter Mode and disconnects it
(“un-bonding” it) when they have connected to a qualified external AC source.

This design avoids two neutral-to-ground connections from existing at the same time, thereby preventing an
electrical shock hazard between the vehicle/boat’s neutral and the external AC source’s neutral.

Note: This feature is standard for M3048BP.


Our regular M5000H-48BP doesn’t have this feature, it is optional for volume order at the time of
production.

2.4.15 Lithium Battery Wakeup


Lithium-ion battery will enter sleep mode when it is overdischarged. When the protection circuit is triggered,
the voltage could drop to 0Vdc.
Such batteries are assumed to be useless for most inverters which require a minimal DC voltage to be
powered on.
It makes it possible for a charger to charge ordinarily.

26
www.sigineer.com
The M3048BP and M5000H-48BP inverters will use solar or AC input power to wake up overdischarged
lithium battery by a boost circuitry.
When they detect a 0V battery, the charger will output a small current of 48Vdc voltage to awaken the
lithium batteries.
Once the lithium battery voltage is charged back to normal (over 48Vdc), the charger will proceed with the
charging settings of program 19 and 20.

2.4.16 Other Features


Conformal Coating
The entire line of M series inverters have been processed with a conformal coating on the PCB, making it
water, rust, and dust resistant.
While these units are designed to withstand corrosion from the salty air, they are not splash proof.

3 Installation

3.1 Location
Follow all the local regulations to install the inverter.
Please install the equipment in a location of Dry, Clean, Cool with good ventilation.
Working temperature: ‐10℃ to 55℃(14℉ to 131℉)
Storage temperature: ‐15℃ to 60℃(5℉to 140℉)
Relative Humidity: 5% to 95%,non-condensing
Cooling: Forced air
Warning! Operation in a condensing environment will invalid warranty.

3.2 Unpacking and Inspection


Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should
have received the following items in the package:
*The inverter x 1
*User manual x 1
*Communication cable x 1
*Current sharing cable x 1
*Parallel communication cable x 1

Mounting the Unit


Before connecting all wiring, please take off bottom cover by removing two screws as shown below.
Consider the following points before selecting where to install:
Do not mount the inverter on flammable construction materials.
Mount on a solid surface
Install this inverter at eye level in order to allow the LCD display to be read at all times.
The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
The recommended installation position is to be adhered to the wall vertically.

27
www.sigineer.com
Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat
dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY
Install the unit by screwing the six sets of screws.

Install the unit by screwing three screws. It’s recommended to use M4 or M5 screws.

Note: For proper air circulation to dissipate heat, allow a clearance of approx. 20cm to the side and approx.
50 cm above and below the unit. Be sure to install each unit in the same level.

3.3 Battery Wiring


Before connecting all wiring, please take off the DC and AC terminal cover by removing their screws.
The DC terminal bolt size is M6 and the diameter of the DC cable holes on the box is 18mm.
It is suggested the battery bank be kept as close as possible to the inverter. The following table is a suggested
wiring option for DC cable with length from 1 meter to 5 meters.

Ring terminal:

Maximum Battery Ring Terminal Torque


Model# Amperage capacity Wire Size Cable Dimensions value
mm2 D (mm) L (mm)

M3048BP 71A 100AH 1*4 AWG 35 6.4 39.2 2-3Nm

M5000H-48BP 117A 200AH 1 x 2AWG 35 6.4 39.2 2-3Nm

28
www.sigineer.com

Recommended breaker specification of battery for each inverter:


Model 1 unit
M3048BP 100A/60VDC
M5000H-48BP 150A / 60VDC
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker
should be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase:

Model 2 units 3 units 4 units 5 units 6 units


M3048BP 100A/120VAC 150A/120VAC 200A/120VAC 250A/120VAC 300A/120VAC
M5000H-48BP 100A/230VAC 150A/230VAC 200A/230VAC 250A/230VAC 300A/230VAC
Note1: Also, you can use 50A breaker for only 1 unit, and each inverter has a breaker at its AC input.
Note2: Regarding three phase system, you can use 4 poles breaker, the rating is up to the current of the
phase which has the maximum units. Or you can follow the suggestion of note 1.
Recommended battery capacity

Inverter Parallel Quantity 2 3 4 5 6


Battery Capacity 200AH 300AH 400AH 500AH 600AH
(M3048BP)
Battery Capacity 400AH 600AH 800AH 1000AH 1200AH
(M5000H-48BP)
WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will
transfer to fault mode.

Please follow the above minimum wire size requirement.


One cable is always best, but if there is a problem obtaining for example 100mm²cable, use 2*50mm²or
3*35mm²instead, as long as the square area adds up. Performance of any product can be improved by
thicker cable and shorter runs, so if in doubt round up and keep the length as short as possible.

Battery cables must have crimped (or preferably, soldered and crimped) copper compression lugs unless
aluminum mechanical lugs are used. Soldered connections alone are not acceptable. High quality, UL-listed
battery cables are available .These cables are color-coded with pressure crimped, sealed ring terminals.

Battery terminal must be clean to reduce the resistance between the DC terminal and cable connection. A
buildup of dirt or oxidation may eventually lead to the cable terminal overheating during periods of high
current draw. Use a stiff wire brush and remove all dirt and corrosion from the battery terminals and cables.

Note: for lead acid battery, the recommended charge current is 0.2C(C-battery capacity)

29
www.sigineer.com

Please follow below steps to implement battery connection:


Assemble battery ring terminal based on recommended battery cable and terminal size.
Connect all battery packs as units requires. It is suggested to connect at least 200AH capacity battery for
5kva inverter.
Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are
tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly
connected and ring terminals are tightly screwed to the battery terminals.

WARNING: Shock Hazard


Installation must be performed with care due to high battery voltage in series.

CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected
tightly.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative
(-).

Reducing RF interference
To reduce the effect of radiated interference, twist the DC cables. To further reduce RF interference, shield
the cables with sheathing /copper foil / braiding.
Taping battery cables together to reduce inductance
Do not keep the battery cables far apart. In case it is not convenient to twist the cables, keep them taped
together to reduce their inductance. Reduced inductance of the battery cables helps to reduce induced
voltages. This reduces ripple in the battery cables and improves performance and efficiency.

CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC
over-current protector or disconnect device between battery and inverter. It may not be requested to have a
disconnect device in some applications, however, it’s still requested to have over-current protection installed.
Please refer to typical amperage in below table as required fuse or breaker size.

Over torqueing may cause the bolt to break.


Equipment Damage
The inverter is not reverse polarity protected. Reversing the battery polarity on the DC

30
www.sigineer.com
WARNING input connections will cause permanent damage to the inverter which is not covered under
warranty. Always check polarity before making connections to the inverter.
The inverter contains capacitors that may produce a spark when first connected to battery.
Do not mount in a confined a battery or gas compartment.
Ensure the inverter is off before disconnecting the battery cables, and that AC power is
disconnected from the inverter input.

3.4 PV Wiring

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between
the inverter and PV modules.
The PV terminal pins can accept cable size up to 8AWG, and the torque for the screws is 1.6Nm.

Max. PV Array Open Circuit Voltage is 450Vdc, pls make sure Open circuit Voltage (Voc) of PV modules
does not exceed 450V.

INVERTER MODEL M3048BP M5000H-48BP


Max. PV Array Open Circuit Voltage 250VDC 450Vdc
PV Array MPPT Voltage Range 120-250Vdc 120~430Vdc
Start-up Voltage 150Vdc 150Vdc

Please follow below steps to implement PV module connection:


1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Check correct polarity of connection cable from PV modules and
PV input connectors. Then, connect positive pole (+) of
connection cable to positive pole (+) of PV input connector.
Connect negative pole (-) of connection cable to negative pole (-)
of PV input connector.

3. Make sure the wires are securely connected.

Don’t reverse the PV input polarity or damage will occur.

3.5 AC Wiring

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during

31
www.sigineer.com
maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is
50A for 5KVA.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect
input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.


WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC
input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model Gauge Torque Value
M3048BP 8 AWG 1.2~ 1.6Nm
M5000H-48BP 8 AWG 1.2~ 1.6Nm

Please follow below steps to implement AC input/output connection:


*Before making AC input/output connection, be sure to open DC protector or disconnector first.
*Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
*Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws.
Be sure to connect PE protective conductor first.
→Ground (yellow-green)
L→LINE (brown or black)

N→Neutral (Blue)
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
*Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal

screws. Be sure to connect PE protective conductor first.

L N
Ground (yellow-green) LINE (brown or black) Neutral (blue)

*Make sure the wires are securely connected.

Wiring Instruction for M5000H 230V Single Phase inverter in 120/240 split phase system
Sigineer Power’s M5000H-48BP 230V single phase inverter is an international model which can be used in
120/240V Split phase systems in America and also 230Vac single phase systems.
Users from 120/240Vac 60Hz split phase phase electricity system( 120VL+120V L+ N+G) must strictly
follow our wiring instructions, or damage to inverter will occur.

32
www.sigineer.com

1 Connect Ground wire to Ground terminal.


2 Connect AC input Hot1 to Input Hot.
3 Connect AC input Hot2 to Input Neutral.
4 Connect Output Hot to AC output Hot1.
5 Connect output Neutral to AC output Hot2.
6 DON’T CONNECT AC INPUT NEUTRAL or load neutral to the inverter.

NOTE: The M5000H-48BP can work with Sigineer Power transformer to split the 240Vac into 120/240Vac
voltages.

CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are reverseed, it may cause utility
short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s
required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and
recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage,
please check with manufacturer of air conditioner that if it’s equipped with time-delay function before
installation. Otherwise, this off grid solar inverter will trigger overload fault and cut off output to protect
your appliance but sometimes it still causes internal damage to the air conditioner.

Preventing Paralleling of the AC Output


The AC output of the unit should never be connected to the utility power / generator.
Such a connection may result in parallel operation of the different power sources and AC power from the
utility / generator will be fed back into the unit which will instantly damage the inverter and may also pose a
fire and safety hazard.

3.6 Communication With Lithium Batteries


The BMS port allows the M series inverters to communicate with lithium batteries BMS with the same
protocol. Our M series inverters support a growing number of lithium batteries from the big brands.
To get more details of our BMS protocol and the compatible lithium battery models, pls email us at
info@sigineer.com.

Please follow below steps to implement lithium battery connection:

Connect one end of RJ45 of battery to BMS communication port of inverter. Connect the other end of RJ45
cable to battery communication port.

33
www.sigineer.com

Lithium Battery Connection (optional)


If choose lithium battery for the inverter, you are allowed to use the lithium battery which has been
configured. There're two connectors on the lithium battery, RJ45 port of BMS and power cable.
Please follow below steps to implement lithium battery connection:
Assemble battery ring terminal based on recommended battery cable and terminal size (same as Lead acid,
see section Lead-acid Battery connection for details) .
Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are
tightened with torque of 2-3Nm. Make sure polarity at both the battery and the inverter/charge is correctly
connected and ring terminals are tightly screwed to the battery terminals.
Connect the end of RJ45 of battery to BMS communication port of inverter.
The other end of RJ45 insert to battery communication port.

Note: if you choose lithium battery, make sure to connect the BMS communication cable between the
battery and the inverter. You need to choose battery type as “lithium battery”

Lithium battery communication and setting


In order to communicate with battery BMS, you should set the battery type to “LI” in Program 5. Then the
LCD will switch to Program 36, which is to set the protocol type. There are several RS485 protocols in the
inverter which can match some customized battery, Please consult with supplier first before you choosing
the battery model.
Connect the end of RJ45 of battery to BMS communication port of inverter
Make sure the lithium battery BMS port connects to the inverter is Pin to Pin, the inverter BMS port and
RS485 port pin assignment shown as below:

PCB Type CAN PROTOCOL


Pinout BMS port RS485 port
Pin#1 RS485B RS485B
Pin#2 RS485A RS485A
Pin#3 -- --
Pin#4 CANH --
Pin#5 CANL --
Pin#6 -- --
Pin#7 -- --
Pin#8 -- --

LCD setting For Lithium Batteries


To make the inverter communicate with the battery BMS, the battery type should be set to “LI” in Program

34
www.sigineer.com
05.
Please refer to “05: LI” for details.

Note:
When multiple inverters are paralleled with multiple lithium batteries, please follow the below setup.
1 Out of the lithium batteries, set one unit as the master and the rest as slave as per the lithium DIP/ADS
switches.
2 Connect the master battery to the inverter which shows “Host”.
If the user connects the master battery to one of the rest the slave inverters in the group, the inverter can
automatically work as the master unit, but the communication will be slower.

3.7 Inverter Parallel Operation

TheM5000H-48BP inverters can be stacked up to 6 pcs to expand output power in 230Vac or create
230/400Vac three phase.
The M3048BP can be stacked up to 6 pcs to expand output power in 120Vac or create 120/208Vac three
phase.

When they are stacked, all the inverters will share the loads evenly. Each will be ready output full power
even the load is under nominal power, none of them will go into power saver mode.
This is designed to handle sudden loads fluctuations.

Note:
When there is more than one inverter paralleled in one phase, if the slave unit shut off, the rest inverters in
the system will continue operate.
If the master unit shuts off, all the rest inverters will shut off.

3.7.1 Parallel in Single Phase to Expand Power


Two inverters in parallel:
Power Wire Connection

Communication Wire Connection

35
www.sigineer.com

Three inverters in parallel:


Power Wire Connection

Communication Wire Connection

Four inverters in parallel:


Power Wire Connection

36
www.sigineer.com

Communication Wire Connection

Five inverters in parallel:


Power Wire Connection

Communication Wire Connection

Six inverters in parallel:


Power Wire Connection

37
www.sigineer.com

Communication Wire Connection

3.7.2 Parallel To Form Three Phase


One inverter in each phase:
Power Wire Connection

Communication Wire Connection

Two inverters in one phase and only one inverter for the remaining phases:
Power Wire Connection

38
www.sigineer.com

Communication Wire Connection

Two inverters in two phases and only one inverter for the remaining phase:
Power Wire Connection

Communication Wire Connection

39
www.sigineer.com
Three inverters in one phase and only one inverter for the remaining two phases:
Power Wire Connection

Communication Wire Connection

Two inverters in each phase:


Power Wire Connection

Communication Wire Connection

Three inverters in one phase, two inverters in second phase and one inverter for the third phase:

40
www.sigineer.com
Power Wire Connection

Communication Wire Connection

Four inverters in one phase and one inverter for the other two phases:
Power Wire Connection

Communication Wire Connection

WARNING: Do not connect the current sharing cable between the inverters which are in different phases.

41
www.sigineer.com

3.7.2 Parallel To Form Split Phase


One inverter in each phase:
Power Connection

Communication Connection

Two inverters in each phase:


Power Connection

Communication Connection

Three inverters in each phase:

42
www.sigineer.com
Power Connection

Communication Connection

3.7.4 LCD Setting For Parallel Operation

Setting Program: Please refer to program 23


Commissioning
Parallel in single phase
Step 1: Check the following requirements before commissioning:
Correct wire connection
Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are connected
together.
Step 2: Turn on each unit and set “PAL” in LCD setting program 23 of each unit. And then shut down all
units.
Note: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be
programmed.
Step 3: Turn on each unit.

LCD display in Master unit LCD display in Slave unit

Note: Master and slave units are randomly defined.


Step 4: Switch on all AC breakers of Line wires in AC input. It’s better to have all inverters connect to utility
at the same time. If not, it will display warning 15.
LCD display in Master unit LCD display in Slave unit

43
www.sigineer.com

Step 5: If there is no more fault alarm, the parallel system is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to
the load.

Parallel in three phase


Step 1: Check the following requirements before commissioning:
Correct wire connection
Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are connected
together.
Step 2: Turn on all units and configure LCD program 23 as 3P1, 3P2 and 3P3 sequentially. Then shut down
all units.
Note: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be
programmed.
Step 3: Turn on all units sequentially. Please turn on HOST inverter first, then turn on the rest one by one.
LCD display in L3-phase
LCD display in L1-phase unit LCD display in L2-phase unit
unit

Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases
are matched with unit setting, they will work normally. Otherwise, they will display warning 15/16 and will
not work in the line mode.
LCD display in L1-phase unit LCD display in L2-phase unit LCD display in L3-phase unit

Step 5: If there is no more fault alarm, the system to support 3-phase equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to
the load.

Note 1: If there’s only one inverter in L1-phase, the LCD will show as “HS”. If there is more than one
inverter in L1-phase, the LCD of the HOST inverter will show as “HS”, the rest of L1-phase inverters will
show as “3P1”.
Note 2: To avoid overload occurring, before turning on breakers in load side, it’s better to have whole
system in operation first.
Note 3: Transfer time for this operation exists. Power interruption may happen to critical devices, which
cannot bear transfer time.

44
www.sigineer.com

Parallel in Split Phase


Step 1: Check the following requirements before commissioning:
Correct wire connection
Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are connected
together.
Step 2: Turn on all units and configure LCD program 23 as 2P0 on phase1 units, then set as 2P2(or 2P1) on
phase2 units:
2P0+2P1: split phase 120V/208V
2P0+2P2: split phase 120V/240V
Note: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be
programmed.
Step 3: Turn on all units sequentially. Please turn on HOST inverter first, then turn on the rest one by one.
(The below pictures show as split phase 120V/240V)
LCD display in L1-phase unit LCD display in L2-phase unit

Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and split phases
are matched with unit setting, they will work normally. Otherwise, they will display warning 15/16 and will
work in the line mode. (Split phase 120V/240V)
LCD display in L1-phase unit LCD display in L2-phase unit

Step 5: If there is no more fault alarm, the system with split phase output is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to
the load.
Note 1: If there’s only one inverter in L1-phase, the LCD will show as “HST”. If there is more than one
inverter in L1-phase, the LCD of the HOST inverter will show as “HST”, the rest of L1-phase inverters will
show as “2P0”.
Note 2: To avoid overload occurring, before turning on breakers in load side, it’s better to have whole
system in operation first.
Note 3: Transfer time for this operation exists. Power interruption may happen to critical devices, which
cannot bear transfer time.

3.8 Communication with Computer


The inverter can be monitored on the computer.
Please use the communication cable to connect to inverter and PC. Install the “SG Solar Power Monitor” on
a computer and follow on-screen instruction to install the monitoring software. For the detailed software
operation, please check user manual of software.

45
www.sigineer.com

3.9 Grounding
Connect an AWG 8 gauge or greater copper wire between the grounding terminal on the inverter and the
earth grounding system or the vehicle chassis.

46
www.sigineer.com

4 Maintenance & Troubleshooting


This troubleshooting guide contains information about how to troubleshoot possible error conditions while
using the M3048BP and M5000H-48BP Solar Power Inverter/Chargers.
The following chart is designed to help you quickly pinpoint the most common inverter failures.
Indicator and Buzzer

Fault Code Fault Event Icon on

01 Fan is locked

02 Over temperature

03 Battery voltage is too high

04 Battery voltage is too low

05 Output short circuited

06 Output voltage is too high.

07 Overload time out

08 Bus voltage is too high

09 Bus soft start failed

51 Over current or surge

52 Bus voltage is too low

53 Inverter soft start failed

55 Over DC voltage in AC output

56 Battery connection is open

57 Current sensor failed

58 Output voltage is too low

60 Negative power fault


61 PV voltage is too high

62 Internal communication error

47
www.sigineer.com

80 CAN fault

81 Host loss

Warning Indicator

Warning Code Warning Event Audible Alarm Icon flashing

01 Fan is locked Beep 3 times every second

02 Over temperature Beep once every second

03 Battery is over-charged Beep once every second

04 Low battery Beep once every second

07 Overload Beep once every 0.5 second

10 Output power derating Beep twice every 3 seconds

12 Solar charger stops due to low battery Beep once every second

Solar charger stops due to high PV


13 Beep once every second
voltage
14 Solar charger stops due to overload Beep once every second

15 Parallel input utility grid different Beep once every second

16 Parallel input phase error Beep once every second

17 Parallel output phase loss Beep once every second


Beep once every second
18 Buck over current

No beep
19 Battery disconnect

20 BMS communication error Beep once every second


Beep once every second
21 PV power insufficient
Beep once every second
22 Parallel forbidden without battery
Beep once every second
25 Parallel inverters’ capacity different

33 BMS communication loss Beep once every second

48
www.sigineer.com

34 Cell over voltage Beep once every second

35 Cell under voltage Beep once every second

36 Total over voltage Beep once every second

37 Total under voltage Beep once every second

38 Discharge over current Beep once every second

39 Charge over current Beep once every second

40 Discharge over temperature Beep once every second

41 Charge over temperature Beep once every second

42 Mosfet over temperature Beep once every second

43 Battery over temperature Beep once every second

44 Battery under temperature Beep once every second

45 System shut down Beep once every second

TroubleShooting

Problem LCD/LED/Buzzer Explanation What to do

Unit shuts down LCD/LEDs and buzzer will


The battery voltage is too low . 1.Re-charge battery.
Automatically during be active for 3 seconds
(<1.91V/Cell) 2.Replace battery.
startup process. and then complete off.
1.The battery voltage is far too
No response after 1. Check if batteries and the wiring are connected well.
low. (<1.4V/Cell)
No indication. 2.Re-charge battery.
power on. 2.Battery polarity is connected
3.Replace battery.
reversed.
Input voltage is 0 on the
Check if AC breaker is tripped and AC wiring is
LCD and green LED is Input protector is tripped.
connected well.
flashing.
Mains exist but the
1. Check if AC wires are too thin and/or too long.
unit works in battery
Insufficient quality of AC power. 2. Check if generator (if applied) is working well or if
Green LED is flashing.
mode. (Shore or Generator) input voltage range setting is correct.
(UPS→Appliance)

Set “Battery First” or “Solar First”


Green LED is flashing. Change output source priority to Utility first.
as the priority of output source.
When it’s turned on,
internal relay is LCD display and LEDs are
Battery is disconnected. Check if battery wires are connected well.
switching on and off flashing
repeatedly.

Buzzer beeps Fault code 01 Fan fault. 1.Check whether all fans are working properly.

49
www.sigineer.com
continuously and red 2.Replace the fan.

LED is on.(Fault code) 1.Check whether the air flow of the unit is blocked or
Internal temperature of component
Fault code 02 whether the ambient temperature is too high.
is over 100℃.
2.Check whether the thermistor plug is loose.
Buzzer beeps once
Restart the unit, if the error happens again, please
Battery is over-charged.
every second, and red return to repair center.
Fault code 03
LED is flashing. Check if spec and quantity of batteries are meet
The battery voltage is too high.
requirements.
(Warning code)
1.Measure battery voltage in DC input.
Warning code 04 The battery voltage/SOC is too low. 2.Check battery SOC in LCD when use Li battery.
3.Recharge the battery.
Check if wiring is connected well and remove
Fault code 05 Output short circuited.
abnormal load.
1.Reduce the connected load.
Output abnormal (Inverter voltage
Fault code 06/58 2. Restart the unit, if the error happens again, please
is over 150Vac or below 40Vac).
return to repair center.
The inverter is overload 110% and Reduce the connected load by switching off some
Fault code 07
time is up. equipment.
1.If you connect to a lithum battery without
communication, check whether the voltage points of
the program 19 and 21 are too high for the lithum
Fault code 08 Bus voltage is too high.
battery.
2. Restart the unit, if the error happens again, please
return to repair center.
Restart the unit, if the error happens again, please
Fault code 09/53/57 Internal components failed.
return to repair center.
The input status is different in Check if AC input wires of all inverters are
Warning code 15
parallel system. connected well.
Warning code 16 Input phase is not correct. Change the input phase S and T wiring.
1.Make sure the parallel setting are the same
The output phase not correct in
Warning code 17 system(sigle or paralle; 3P1,3P2,3P3).
parallel.
2.Make sure all phases inverters are power on.
1.Check whether communication line is correct
Li battery can't communicate to the
Warning code 20 connection between inverter and battery.
inverter.
2.Check whether BMS protocol type is correct setting.
Fault code 51 Over current or surge.
Restart the unit, if the error happens again, please
Fault code 52 Bus voltage is too low.
return to repair center.
Fault code 55 Output voltage is unbalanced

Battery is not connected well If the battery is connected well, please return to
Fault code 56
or fuse is burnt. repair center.
1. Check whether the AC output connected to the grid
input.
2. Check whether Program 8 settings are the same for
all parallel inverters
Fault code 60 Negative power fault 3. Check whether the current sharing cables are
connected well in the same parallel phases.
4. Check whether all neutral wires of all parallel units
are connected together.
5. If problem still exists, contact repair center.
1. Check whether the parallel communication cables
Fault code 80 CAN fault
are connected well.
2. Check whether Program 23 settings are right for the
Fault code 81 parallel system.
Host loss
3. If problem still exists, contact repair center

Note: To restart the inverter, all power sources need to be disconnected. After the LCD screen light is off, only use the battery to
restart the inverter.

50
www.sigineer.com

5 Warranty
We warrant this product against defects in materials and workmanship for a period of one year from the date
of purchase and will repair or replace any defective M Series Inverter when directly returned, postage
prepaid, to manufacturer. This warranty will be considered void if the unit has suffered any obvious physical
damage or alteration either internally or externally and does not cover damage arising from improper use
such as plugging the unit into an unsuitable power sources, attempting to operate products with excessive
power consumption requirements, reverse polarity, or use in unsuitable climates.
WARRANTY DOES NOT INCLUDE LABOR, TRAVEL CHARGES, OR ANY OTHER COSTS
INCURRED FOR REPAIR, REMOVAL, INSTALLATION, SERVICING, DIAGNOSING OR
HANDLING OF EITHER DEFECTIVE PARTS OR REPLACEMENT PARTS. THE WARRANTOR
ASSUMES NO LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND.
LOSS OR DAMAGE: Loss or damage in transit is the responsibility of the carrier. Any claim should be
filed with the delivering transport company. Invoice, Bill of Lading and Delivery receipt with damage noted
therein must accompany any claims for freight damage. Claims for shortage and lost shipments must be
made in writing to the shipper within 3 days of the receipt of shipment. Claims not reported within this time
frame will not be honored.

This warranty does not apply to and we will not be responsible for any defect in or damage to:
a) the product if it has been misused, neglected, improperly installed, physically damaged or altered, either
internally or externally, or damaged from improper use or use in an unsuitable environment; violations of
the warnings in the manual will invalid the warranty.
b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or input
voltage that creates operating conditions beyond the maximum or minimum limits listed in the product
specifications including high input voltage from generators and lightning strikes;
c) the product if repairs have been done to it other than by us or its authorized service centers;

Appendix 1 : M3048BP M5000H-48BP Solar Inverter


Spec Sheet
MODEL # M3048BP M5000H-48BP

Nominal AC Output Power 3000VA/3000W 5000VA/5000W

AC Input Waveform Sinusoidal (Utility or Generator) Sinusoidal (Utility or Generator)

Max AC Input Voltage 150Vac 300Vac

Low AC Voltage Trip 95Vac±7V (UPS); 65Vac±7V (Appliances) 170Vac±7V (UPS); 90Vac±7V (Appliances)
Low AC Voltage Return 100Vac±7V (UPS); 70Vac±7V (Appliances) 180Vac±7V (UPS); 100Vac±7V (Appliances)

High AC Voltage Trip 140Vac±7V 280Vac±7V


AC Mode

High AC Voltage Return 135Vac±7V 270Vac±7V

Nominal AC Input Frequency 50Hz / 60Hz (Auto Detection) 50Hz / 60Hz (Auto Detection)

Low Frequency Trip 40±1Hz 40±1Hz


Low Frequency Return 42±1Hz 42±1Hz

High Frequency Trip 65±1Hz 65±1Hz

High Frequency Return 63±1Hz 63±1Hz


Efficiency (Line Mode) >95% ( Under full Linear Loads) >95% ( Under full Linear Loads)

51
www.sigineer.com
10 ms(Typical) ; 20 ms Max; <30ms 10 ms(Typical) ; 20 ms Max; <30ms
Transfer Time
Parallel Parallel

AC Input Breaker 40A 40A

Battery Voltage 48 VDC 48 VDC

Output Waveform Pure Sine Wave Pure Sine Wave

AC Voltage Regulation (Batt. Mode) 120 VAC ±5% 230 VAC ±5%
Surge AC Output Power 6000W (5 secs) 10000W (5 secs)
Output Frequency 50Hz/60Hz(default) 50Hz/60Hz(default)

Max. Output Fault Current/ Duration 80A/ 300μs 80A/ 300μs

Max. Output Overcurrent Protection 76A 65A

DC To AC Efficiency (Peak) 90% 93%


Overload Protection 5s@≥150% load; 10s@110%~150% load 5s@≥150% load; 10s@110%~150% load

Cold Start Battery Voltage* (Without 46.0Vdc/Li Mode(Default 30%, Low DC 46.0Vdc/Li Mode(Default 30%, Low DC
PV or AC) Cut-off SOC +10%) Cut-off SOC +10%)

Minimal Battery Voltage To Activate


40.8Vdc 40.8Vdc
AC Charger(Without PV)

44.0Vdc @ load < 20% 44.0Vdc @ load < 20%


Low DC Warning Voltage (Lead-Acid
Mode) 42.8Vdc @ 20% ≤ load < 50% 42.8Vdc @ 20% ≤ load < 50%
40.4Vdc @ load ≥ 50% 40.4Vdc @ load ≥ 50%
Inverter Mode

46.0Vdc @ load < 20% 46.0Vdc @ load < 20%


Low DC Warning Return
Voltage(Lead-Acid Mode) 44.8Vdc @ 20% ≤ load < 50% 44.8Vdc @ 20% ≤ load < 50%

42.4Vdc @ load ≥ 50% 42.4Vdc @ load ≥ 50%

42.0Vdc @ load < 20% 42.0Vdc @ load < 20%


Low DC Cut-off Voltage (Lead-Acid
Mode) 40.8Vdc @ 20% ≤ load < 50% 40.8Vdc @ 20% ≤ load < 50%

38.4Vdc @ load ≥ 50% 38.4Vdc @ load ≥ 50%

Low DC Cut-off Voltage (Li Mode) 42.0Vdc 42.0Vdc


Low DC Warning SOC (Li Mode) Low DC Cut-off SOC +5% Low DC Cut-off SOC +5%
Low DC Warning Return SOC (Li
Low DC Cut-off SOC +10% Low DC Cut-off SOC +10%
Mode)
Low DC Cut-off SOC (Li Mode) Default 20%, 5%~50% settable Default 20%, 5%~50% settable

High DC Recovery Voltage 56.4Vdc(C.V. charging voltage) 56.4Vdc(C.V. charging voltage)


High DC Cut-off Voltage 60.8Vdc 60.8Vdc

Idle Power <60W <60W

CV & Float Charge voltage 48.0V~58.4V Settable 48.0V~58.4V Settable


Maximum PV Array Power 4000W 6000W

Max PV Input Current 22A 22A

MPPT Efficiency 98.0% max. 98.0% max.

PV Open Circuit Voltage 250Vdc 450Vdc


Charge Mode

PV Charger Start-up Voltage 150Vdc±10Vdc 150Vdc±10Vdc


MPPT Range @ Operating Voltage 120-250VDC 120-430VDC

Overcharge Protection 60Vdc 60Vdc

Maximum Solar Charge Current 80 A 100 A

Maximum AC Charge Current 40 A 80 A

Maximum Charge Current(PV+AC) 80A 100 A

Battery Voltage Accuracy +/-0.3% +/-0.3%

52
www.sigineer.com
PV Voltage Accuracy +/-2V +/-2V

Inverter Dimension DxWxH 455*295*130mm/17.9*11.6*5.1" 455*295*130mm/17.9*11.6*5.1"

Pack Dimension DxWxH 580*380*220mm/23*15*9" 580*380*220mm/23*15*9"


General Specifications

Net Weight 12KG/25.3lbs 12KG/25.3lbs


Gross Weight 13.5KG/29.8lbs 13.5KG/29.8lbs

5% to 95% Relative Humidity 5% to 95% Relative Humidity


Humidity
(Non-condensing) (Non-condensing)

Operating Temperature ‐10℃ to 55℃(-14℉to 131℉) ‐10℃ to 55℃(-14℉to 131℉)

Storage Temperature ‐15℃ to 60℃(5℉to 140℉) ‐15℃ to 60℃(5℉to 140℉)

Altitude <2000m <2000m

*Cold start voltage is the minimal battery voltage for the inverter to power on without PV or AC input.

※Errors and omissions reserved. Specifications in this manual are subject to change without prior
notice.

SAVE THIS MANUAL!


READ THIS MANUAL BEFORE INSTALLATION, IT
CONTAINS IMPORTANT SAFETY, INSTALLATION AND
OPERATING INSTRUCTIONS. KEEP IT IN A SAFE PLACE
FOR FUTURE REFERENCE.

Sigineer Power Limited


Email: info@sigineer.com
TEL: +86 769 82817616
US Warehouse: 4415 S 32nd St, Phoenix, AZ 85040

53

You might also like