United Caravan Trading & Contracting Oil & Gas Division: On-Site Inspection & Service Report

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

UNITED CARAVAN TRADING & CONTRACTING

OIL & GAS DIVISION


ON-SITE INSPECTION & SERVICE REPORT
SERVICE REF:
CUSTOMER : KCA DEUTAG
CUSTOMER ORDER NO :
EQUIPMENT INSPECTED : ACCUMULATOR UNIT
RIG NO : T902
ACTIVITY : NDT / PRESSURE TEST / OTHER SERVICE
PROCEDURE :
TYPE OF SERVICE : FREE SERVICE / INVOICEABLE
SPARES BY :
CLIENT / UCTC
(IF REQUIRED)
CREW DETAILS
SUPERVISOR NAME : MR.ARUN KUMAR
TECHNICIAN NAME : MR.AMIT KUMAR
DATE OF REQUEST : 02/08/2022
DATE OF ARRIVAL : 02/08/2022
DATE OF DEPARTURE : 03/08/2022
INSPECTION DETAILS

CLIENT REQUEST 1.ACCUMULATOR UNIT GAUGE PRESSURE SHOW VARIATION BETWEEN UNIT &
REMOTE PANELS DRILLER & TOOL PUSHER

UCTC OBSERVATION: AS PER ASSESMENT FOUND PRESSURE TRANSMITTER IS NOT WORKING PROPERLY
OF ACCUMULATOR TRANSMITTER.

UCTC CORRECTIVE ACTION: 1. RECOMMENDED TO REPLACE WITH NEW TRANSMITTER OF ACCUMULATOR.


2.RECOMMENDED TO REPLACE REMOTE PANELS ACC. GAUGES RANGE 0-6000PSI
RECIVER GAUGE.
Part no- 1. Transmitter--2100-1100---01nos
2. Gauge 0-6kpsi receiver gauge--- 4060-2100 or 816199--02nos

COMMENTS (IF ANY):


RECOMMENDED : Replace All three transmitter for correct result of pressure part no as
1.2100-0100---0-3k psi---01nos Annular
2.2100-1100---0-6k psi---01nos Accumulator
3.2100-2100---0-10k psi---01nos Manifold

UCTC REPRESENTATIVE CUSTOMER REPRESENTATIVE


Doc. No.: UCTC/FM/OP/03 , Rev. : 03 , Dt. : 01/2021