Type-K Thermocouple Temperature Probe


Instruction Sheet
Introduction
The 80PK-11 is a Type-K Thermocouple Temperature Probe
designed for HVAC temperature measuring applications. The 20
inch PVC cable terminates with a Type-K thermocouple inside a
19.5 inch nylon cuff. The 80PK-11 can be used with any
temperature measuring instrument that is designed to accept
Type-K thermocouples and has a miniature connector input. The
80PK-11 is not suitable for liquid immersion but can work in
humid to wet environments.
XWWarning
To avoid electrical shock, do not use this probe
when voltages exceeding 24 V rms or 60 V dc are
present. The probe tip is electrically connected to
the output terminals.
Specifications
Type: K Special Grade (Chromel vs Alumel)
Measurement Range: -30 ºC to 150 ºC (-19.3 ºF to 302 ºF)
Accuracy:  1.5 ºC (2.7 ºF)
Measurement Time (Time Constant): 2 seconds
Maximum Voltage: 24 V ac rms or 60 V dc maximum for proper
safe operation.
Maximum Temperature of Bead: 150 ºC (302 ºF)
Operating Temperature: 0 °C to 50 °C
Storage Temperature: -20 °C to 65 °C
Cable: Total Length: 1 m (40 in), 20 in cable, 19.5 in cuff
Insulation Material: Hytrel
Connector: Type: Yellow mini-thermocouple with 0.500 in pin
Material: Hytrel 4774
Maximum Temperature: 200 ºC (392 ºF)
Measurement Considerations
Instrument Compatibility
The 80PK-11 is designed to be compatible with any temperature
measuring instrument that accepts Type-K thermocouples, has a
miniature thermocouple connector, and has cold reference
junction compensation. Accuracy of the temperature measuring
instrument must be considered along with the 80PK-11 accuracy
specification in order to determine the overall accuracy of the
combination.

PN 2724595
August 2006, Rev.1, 12/2018
© 2006-2018 Fluke Corporation, All rights reserved.
All product names are trademarks of their respective
companies.
80PK-11 English Instruction Sheet
Page 2

Temperature Limitations
The 200 ºC (392 ºF) continuous temperature rating of the
80PK-11 is primarily determined by the Hytrel insulation. The
bead alone may be momentarily subjected to higher
temperatures without damage.
Media Limitations
Type-K Chromel-Alumel thermocouple wires are compatible with
clean oxidizing atmospheres.
Operation
W Caution
Repeated sharp bending can break the 80PK-11
lead. To protect the lead, avoid sharp bends,
especially near the connector.
Use the 80PK-11 as follows:
1. Connect the probe to a compatible Type-K measuring
instrument using the miniature thermocouple connector
(0.500 in pin spacing).
2. Turn on the measuring instrument and select the
appropriate range and scale.
3. Check the readout on the measuring instrument. With
no heat or cold source applied to the sensor, it should
display the ambient (room) temperature.
4. Wrap the probe firmly around the object you wish to
measure. The readout will give you the source
temperature.
LIMITED WARRANTY AND LIMITATION OF LIABILITY
This Fluke product will be free from defects in material and workmanship
for one year from the date of purchase. This warranty does not cover
fuses, disposable batteries, or damage from accident, neglect, misuse,
alteration, contamination, or abnormal conditions of operation or
handling. Resellers are not authorized to extend any other warranty on
Fluke’s behalf. To obtain service during the warranty period, contact your
nearest Fluke authorized service center to obtain return authorization
information, then send the product to that Service Center with a
description of the problem.
THIS WARRANTY IS YOUR ONLY REMEDY. NO OTHER
WARRANTIES, SUCH AS FITNESS FOR A PARTICULAR PURPOSE,
ARE EXPRESSED OR IMPLIED. FLUKE IS NOT LIABLE FOR ANY
SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES
OR LOSSES, ARISING FROM ANY CAUSE OR THEORY. Since some
states or countries do not allow the exclusion or limitation of an implied