Saic A 1001
Saic A 1001
Saic A 1001
00 31-May-18
Soil Sampling, Testing and Review of Test Reports SAIC-A-1001 15-Jul-18 CIVIL-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A Laboratory Testing
Gradation, density and moisture content control test are performed at the
following frequencies: one standard sieve analysis (ASTM C 136, ASTM
SAES-A-114
A4 D 422 or ASTM D 1140) and one Modified Proctor Test per ASTM D 1557
Sec. 6.4.1.1
with corresponding Proctor curve for each type of fill material or where
there is a change in the type or source of the material.
B Fill Materials
SAES-A-114
B1 Fill materials shall consist of gravel, sand and/or marl.
Sec. 6.1.1.1
The maximum size of fill materials shall be one-half (½ ) the lift thickness SAES-A-114
B2
or 75mm (3 inches), whichever is less. Sec. 6.1.1.1
SAES-A-114
C1 The amount of material passing the 50mm sieve shall be 100%.
Sec. 6.1.2.1
The amount of material passing the No. 200 sieve shall be between 0- SAES-A-114
C2
20%. Sec. 6.1.2.1
Soil Sampling, Testing and Review of Test Reports SAIC-A-1001 15-Jul-18 CIVIL-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
The maximum size of fill materials shall be one-half (½ ) the lift thickness SAES-A-114
D1
or 75mm, whichever is less. Sec. 6.1.1.1
REMARKS:
REFERENCE DOCUMENTS:
1- SAES-A-114 -- Excavation and Backfill, 30 September 2014
2- Schedule Q - March 2013