Ground Floor Lighting Layout Second Floor Lighting Layout: Kitchen Lanai Master Bedroom

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

2 3

PANEL BOARD DESIGNATION : PB1 SYSTEM : 2P 230V 2W+G 60HZ LOCATION : GROUND FLOOR

CONNECTED LOADS BREAKER RATING WIRING SCHEDULE SIZE OF CONDUIT


CIRCUIT
LOAD DESCRIPTION
NUMBER
Volt- Amper Current in Phase
Quantity AT POLE KAIC
VA Amperes System

2-3.5mm² Cu. Wire THHN +


1 LIGHTING OUTLET 10 1000 4.35 1 20 2 10 1-2.0mm² Cu. Wire Grounding 20mmØ PNS

2-3.5mm² Cu. Wire THHN +


2 LIGHTING OUTLET 6 600 2.61 1 20 2 10 1-2.0mm² Cu. Wire Grounding 20mmØ PNS

DS DS 2-3.5mm² Cu. Wire THHN +


3 CONVENIENCE OUTLET 8 1440 6.26 1 20 2 10 1-2.0mm² Cu. Wire Grounding 20mmØ PNS

CABINET
CABINET
QUARTER'S SHO. 4

QUARTER'S AREA 2 LAUNDRY 3040 13.22

WALK IN

CABINET
AREA 1 LINEN AREA AREA BATH W.C.
W6
TAB CLOSET
D5 D2
T&B
WM D6
D5
SIZE OF THE CONDUCTOR: I= 129.97 + 25%@22.5 = 135.60@80%DF= 108.48Amperes
D6 USE: 2- 60mm² ²
DN

TERRACE
KITCHEN
MASTER

COUNTER
BEDROOM

DIRTY
KITCHEN

CABINET
BAR
LANAI DINING AREA
D4 D4

D2
BEDROOM 2
C2
D5

PANTRY D3
CABINET
C4 D3
UP

STO. 6 5 4 3 2 1 STAIR STAIR


3 2 1 9 10 11 12 13 14 15 16 FEEDER SCHEDULE
HALLWAY

DN
DN

D5 D6
FEEDER WIRE / CABLE CONDUIT
F1
POSSIBLE FAULT
CABINET CABINET LOCATION

HALLWAY
DS
L3.5 2-3.5mm² THW + 1-2.0mm² TW 20mmØ

D3
C1 D3
L5.5 2-5.5mm² THW + 1-3.5mm² TW 20mmØ
GUEST BEDROOM 1
BEDROOM LIVING AREA L8.0 2-8.0mm² THW + 1-3.5mm² TW 32mmØ

CANOPY
CARPORT
L14 2- 14mm² THW + 1-8.0mm² TW 32mmØ
ALL

ALL

DN
PB1 PB2
FIREW

FIREW
W7 L50 2-50mm² THW + 1-22mm² TW 50mmØ
D7 C3
L60 2-60mm² THW + 1-30mm² TW 50mmØ

PB TERRACE L125 2-125mm² THW + 1-30mm² TW 65mmØ

DS

CANOPY
UP

1 4

E SECOND FLOOR LIGHTING LAYOUT


E GROUND FLOOR LIGHTING LAYOUT 1 1 SCALE : 1 :100 MTS
1 1 SCALE : 1 :100 MTS

ARCHITECTURAL FIRM PROJECT TITLE PROJECT OWNER SHEET CONTENT REVISIONS RA 9266 ARTICLE 4 SECTION 33 SHEET NO.

GROUND FLOOR PLAN Drawings and specifications and other contract documents duly signed,
PROPOSED 2 - STOREY RESIDENTIAL BUILDING SECOND FLOOR PLAN stamped or sealed, as instruments of service, are the intellectual property
and documents of the architect, whether thE object for which they are made
is executed or not. It shall be unlawful for any person to duplicate or to make
copies of said documents for use in the repetition of and for other projects or
E-1
buildings, whether executed partly or in whole, without the written consent of
architect or author of said documents.