E PKS: Control Builder Parameter Reference

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3341

EXPERION PKS

RELEASE 516

Control Builder Parameter Reference


EPDOC-XX18-en-516A
August 2020
Disclaimer
This document contains Honeywell proprietary information. Information contained herein is to
be used solely for the purpose submitted, and no part of this document or its contents shall be
reproduced, published, or disclosed to a third party without the express permission of
Honeywell International Sàrl.
While this information is presented in good faith and believed to be accurate, Honeywell
disclaims the implied warranties of merchantability and fitness for a purpose and makes no
express warranties except as may be stated in its written agreement with and for its customer.
In no event is Honeywell liable to anyone for any direct, special, or consequential damages.
The information and specifications in this document are subject to change without notice.
Copyright 2020 - Honeywell International Sàrl

2
Contents 3
Chapter 1 - About This Document 206
1.1 Revision History 206
Chapter 2 - 3xxxx Parameters 207
2.1 3TIMESFLOW[1..24] 207
2.2 3TIMESFLOW[1..200] 207
2.3 24VPSSTS 208
Chapter 3 - Axxxx Parameters 209
3.1 ABBREV 215
3.2 ABORTALM.FL 215
3.3 ABORTALM.PR 216
3.4 ABORTALM.SV 216
3.5 ABORTLOCK 216
3.6 ACCDEV.FL[1..4] 217
3.7 ACCDEV.TP[1..4] 217
3.8 ACCEPTDEV 218
3.9 ACCEPTRNG 218
3.10 ACCEPTSIMPEERDATA 219
3.11 ACCESSLEVEL 219
3.12 ACCTV 220
3.13 ACCTVFL 220
3.14 ACEMACADDR 221
3.15 ACEMEMINMB 221
3.16 ACERDNROLE 222
3.17 ACERMCONNSTS 223
3.18 ACK 223

3
3.19 ACQUIREOPT 224
3.20 ACQRESTYPE 224
3.21 ACTARRWRITES 225
3.22 ACTAVAIL 225
3.23 ACTCOMMAND 226
3.24 ACTCREATETIME 226
3.25 ACTCREATETYPE 227
3.26 ACTCRMIGOPT 227
3.27 ACTENTITY 228
3.28 ACTENTITYIOC 228
3.29 ACTEXECENDTTIME 229
3.30 ACTEXECSTARTTIME 229
3.31 ACTID 230
3.32 ACTIVESCOPE 230
3.33 ACTNONARRWRITES 231
3.34 ACTOPT 231
3.35 ACTPARENT 232
3.36 ACTREMOVETYPE 232
3.37 ACTSTATE 233
3.38 ACQONBEHALF 234
3.39 ACQSTATE 235
3.40 ACTIVEDATE 236
3.41 ACTIVEFL 236
3.42 ACTIVEHANDLR[1..8] 236
3.43 ACTIVELOC.HANDLER 237
3.44 ACTIVELOC.HANDLERN 237
3.45 ACTIVELOC.HNDTYPE 238

4
3.46 ACTIVELOC.STEP[1..15] 238
3.47 ACTIVELOC.STEPN[1..15] 239
3.48 ACTIVELOC.STEPICOMP[1..15] 239
3.49 ACTIVELOC.STEPIPEND[1..15] 240
3.50 ACTIVELOC.TIME[1..15] 240
3.51 ACTIVELOCOCD 241
3.52 ACTIVEARRPARAMWRITES 241
3.53 ACTIVENONARRPARAMWRITES 242
3.54 ACTPARENTLOOKUP 242
3.55 ACTPRIM[1..40] 243
3.56 ACTRAMPRATE[1..NUMPROFILES]
[1..NUMRAMPSOAK] 243
3.57 ACTSOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK]244
3.58 ACTSOAKVAL[1..NUMPROFILES][1..NUMRAMPSOAK] 244
3.59 ACTSTARTOP[1..NUMPROFILES] 245
3.60 ACTSTARTSEG[1..NUMPROFILES] 245
3.61 ACTTYPE 246
3.62 ACTUALPROVERSIGNAL 246
3.63 ACTUALSCANTIME 247
3.64 ACTVTNTIME 247
3.65 ACTWRITEALLOCFAIL 247
3.66 ADDRCOUNT 248
3.67 ADVALARM_ACTIVE_ALARMS 248
3.68 ADVALARM_ACTUAL_VALUE [0...4] [0...31] 249
3.69 ADVALARM_COND_ASSOCALARM [0...31] 249
3.70 ADVALARM_COND_NAME [0...31] 249
3.71 ADVALARM_ENABLE [0...31] 250

5
3.72 ADVALARM_NUM_CONFCOND 250
3.73 ADVALARM_PARREF_BITS [0...4] [0...31] 251
3.74 ADVALARM_PARREF_BLOCK [0...4] [0...31] 251
3.75 ADVALARM_PARREF_PARAM [0...4] [0...31] 252
3.76 ADVALARM_PARREF_SUBINDEX [0...4] [0...31] 252
3.77 ADVALARM_PRIORITY [0...31] 253
3.78 ADVALARM_REFERED_BLOCK_ID [0...4] [0...31] 253
3.79 ADVALARM_REFERED_PARAM_ID [0...4] [0...31] 253
3.80 ADVALARM_STALE_DATA 254
3.81 ADVALARM_UPDATED_OD_IDX 254
3.82 ADVDEVALM.DB 255
3.83 ADVDEVALM.DBU 255
3.84 ADVDEVALM.FL 256
3.85 ADVDEVALM.PR 256
3.86 ADVDEVALM.SV 256
3.87 ADVDEVALM.TM 257
3.88 ADVDEVALM.TMO 257
3.89 ADVDEVALM.TP 258
3.90 ADVDEVOPT 258
3.91 ADVSP 259
3.92 ADVSPP 259
3.93 AICHNLNAME 260
3.94 AIHASENAME 260
3.95 AIPTEXECST 261
3.96 AIREGISTERED[ ] 261
3.97 ALERTTIMEOUT 262
3.98 ALFMT 262

6
3.99 ALGOPROCSTATE 263
3.100 ALGOREGSTATE 263
3.101 ALGOTYPE 264
3.102 ALIAS[ ].ALL 264
3.103 ALIAS[ ].STATUS 265
3.104 ALIAS[ ].VALUE 265
3.105 ALIASBLKTYP[ ] 265
3.106 ALIASDATATYP[ ] 266
3.107 ALIASOPT 266
3.108 ALIASPRMTYP[ ] 267
3.109 ALIASREF[ ][ ] 267
3.110 ALIASSRC[ ][ ] 267
3.111 ALLEVTJRNLD 268
3.112 ALLOWNAN 268
3.113 ALMACTIVE [0..NUMALARMS-1] 269
3.114 ALMDB 269
3.115 ALMDBU 270
3.116 ALMDESC [0..NUMALARMS-1] 271
3.117 ALMENBSTATE 271
3.118 ALMIN[1..16] 272
3.119 ALMOPT 273
3.120 ALMOUT 273
3.121 ALMPRI [0.. NUMALARMS-1] 274
3.122 ALMSELOPT 274
3.123 ALMSEQ 275
3.124 ALMSEV [0..NUMALARMS-1] 275
3.125 ALMSTR[0..NUMALARMS-1] 276

7
3.126 ALMTM 276
3.127 ALMWINTXT[1..32] 277
3.128 ALONEAV 278
3.129 ALTENBOPT 278
3.130 ALTSYNCCMD 279
3.131 AMCOMMAND 279
3.132 AMHI 280
3.133 AMLO 281
3.134 AMODULES 281
3.135 AMMODE 282
3.136 AMRESPTIME 282
3.137 AMSTATUS 283
3.138 ANYRESTARTFL 284
3.139 AOCHNLNAME 284
3.140 AOPTEXECST 285
3.141 APPIMAGETYPE 285
3.142 APPROVALS 286
3.143 AREVISION 286
3.144 ACTIVEARRPARAMWRITES 286
3.145 ACTIVENONARRPARAMWRITES 287
3.146 ArraySize 287
3.147 ARRINDEX 288
3.148 ARIBITRATIONSTATUS 288
3.149 ARWMULTOP[1..8] 289
3.150 ARWNET[1..8] 289
3.151 ARWNETIN 290
3.152 ARWNETIN[1..8] 291

8
3.153 ARWOP 291
3.154 ARWOPIN 292
3.155 ARWRATIO 292
3.156 ASACONNSTS 293
3.157 ASACONNSTS[0..7] 293
3.158 ASAERRCODE 294
3.159 ASAERRCODE[0..7] 294
3.160 ASAERRINFO 295
3.161 ASAERRINFO[0..7] 295
3.162 ASICVERA[1..8] 295
3.163 ASICVERB[1..8] 296
3.164 ASSIGNABLE 296
3.165 ASSOCASSET 297
3.166 ASSOCCHANNEL 297
3.167 ASSOCIOP 298
3.168 ASSOCIOPTYP 298
3.169 ASSOCGANGEDCHANNELS 299
3.170 ASSOCIATEDTREND 299
3.171 ASTEPID 300
3.172 ATLOADSTATE 300
3.173 AUTHOR 301
3.174 AUTHSERVERIPADDR 301
3.175 AUTHSTATE 302
3.176 AUTOBAUDDISABLE 302
3.177 AUTOCLOSE 303
3.178 AUTOMAN 303
3.179 AUTOMAN2 303

9
3.180 AUTOMATICPOINTIMPORT 304
3.181 AUTONOCMD 304
3.182 AUTOOPEN 305
3.183 AUTOPERIOD 305
3.184 AUTOPHASE 306
3.185 AUTOPUBLICNAME 306
3.186 AUTOSTART 307
3.187 AUTOSTOP 307
3.188 AUTOSTOPACTED 308
3.189 AUTOSYNCCMD 308
3.190 AUTOSYNCOPT 309
3.191 AUTOSYNCSTAT 309
3.192 AUTOTRIGGER 310
3.193 AUTOTRIGGERPERIOD 310
3.194 AUXCMD 311
3.195 AUXDATA[0..7] 311
3.196 AUXDESC 312
3.197 AUXDESC[0..10] 312
3.198 AUXMEM 313
3.199 AUXOPT 313
3.200 AUXREQ 314
3.201 AUXREQDATA[1..5] 314
3.202 AUXSTS 314
3.203 AUXUNIT 315
3.204 AV 315
3.205 AV[0..7] 316
3.206 AVAILFL 316

10
3.207 AVCONV 317
3.208 AVERSION 317
3.209 AVGDEPTH 318
3.210 AVGFLOWRATE[1..200] 318
3.211 AVGICPNAKS 319
3.212 AVGICPSENDS 319
3.213 AVGPKTRXRATE 320
3.214 AVGRCVBYTESPERSEC 320
3.215 AVGRCVMSGPERSEC 321
3.216 AVGRDRRESPONSETIMEUS 321
3.217 AVGSPILL[1..200] 321
3.218 AVGWRTIME 322
3.219 AVGXMITBYTESPERSEC 322
3.220 AVGXMITMSGPERSEC 323
3.221 AVRAW 323
3.222 AVRAW[0..7] 324
3.223 AVRAWSTS 324
3.224 AVSTS 325
3.225 AWAITINGACK[1..24] 326
3.226 AWAITINGACK[1..200] 326
Chapter 4 - Bxxxx Parameters 327
4.1 B[1..6] 331
4.2 BACKCALCCONN 331
4.3 BACKCALCIN 332
4.4 BACKCALCIN[1..3] 332
4.5 BACKCALCIN[1..8] 333
4.6 BACKCALCOUT 334

11
4.7 BACKCALCOUT[1..4] 334
4.8 BACKCALCOUT[1..8] 335
4.9 BACKLASHL 335
4.10 BACKLASHR 336
4.11 BACKUPRAMSCRUBERRS 336
4.12 BACKUPRAMSWEEPERR 337
4.13 BADAVRAW 337
4.14 BADCAL 338
4.15 BADCAL[0..numChans-1] 338
4.16 BADCAL[0..7] 339
4.17 BADCODE 339
4.18 BADCOMPTERM.FL 340
4.19 BADCOMPTERM.PR 340
4.20 BADCOMPTERM.SV 341
4.21 BADCTL.FL 341
4.22 BADCTLALM.FL 341
4.23 BADCTLALM.PR 342
4.24 BADCTLALM.SV 342
4.25 BADCTLALM.TM 343
4.26 BADCTLALM.TMO 343
4.27 BADCTLFL 344
4.28 BADCTLOPT 344
4.29 BADINACT[1..8] 345
4.30 BADINACTMINTM[1..8] 346
4.31 BADINDETTM[1..8] 346
4.32 BADINPTOPT[1..4] 347
4.33 BADINPTOPT[1..8] 347

12
4.34 BADIPCSUM 348
4.35 BADOCOPT 348
4.36 BADOCOPTENB 349
4.37 BADOPTFLDSETTING 350
4.38 BADREPORTINSTANCE 350
4.39 BADUDPCSUM 350
4.40 BADPV 351
4.41 BADPV_DI_S 352
4.42 BADPVALLA, BADPVALLB 352
4.43 BADPVALM.FL 352
4.44 BADPVALM.PR 353
4.45 BADPVALM.SV 353
4.46 BADPVALM.TM 354
4.47 BADPVALM.TMO 354
4.48 BADPVALM.TP 355
4.49 BADPVFL 355
4.50 BADPVFL[0..numChans-1] 356
4.51 BADPVFL[1..NUMCHAN] 357
4.52 BADSO 357
4.53 BADSO[6..7] 358
4.54 BADUDPCSUM 359
4.55 BASENAME 359
4.56 BASEPERIOD 360
4.57 Base Template 361
4.58 BATCHEUDESC 362
4.59 BATCHEVTMRY 362
4.60 BATCHID 362

13
4.61 BATCHSIZECURR 363
4.62 BATCHSIZEDEF 364
4.63 BATTERYNOTOK 364
4.64 BATTERYNOTOKSFTAB 365
4.65 BCDSWSTS 365
4.66 BCOUT.ARWSTS 367
4.67 BCOUT.EUHI 367
4.68 BCOUT.EULO 368
4.69 BCOUT.HISELECT 368
4.70 BCOUT.INITREQ 369
4.71 BCOUT.INITVAL 369
4.72 BCOUT.LOCALMAN 370
4.73 BCOUT.ONESHOT 370
4.74 BCOUT.ORFBSTS 371
4.75 BCOUT.ORFBVAL 371
4.76 BCOUT.OROFFSET 372
4.77 BCOUT.PROPOVRD 372
4.78 BECMPRICMD 373
4.79 BFF 373
4.80 BIAS 374
4.81 BINITIALIZE 374
4.82 BKGCOLOR 375
4.83 BKR 375
4.84 BKS 376
4.85 BKT 376
4.86 BKTBYPASS 376
4.87 BLCKCOMMENT1 377

14
4.88 BLCKCOMMENT2 377
4.89 BLCKCOMMENT3 378
4.90 BLCKCOMMENT4 378
4.91 BLDSVRPNT 379
4.92 BLKDSDSIZE 379
4.93 BLKTYPCOUNT 380
4.94 BLKTYPDESC 380
4.95 BLKTYPHELPTXT 380
4.96 BLKTYPLIB 381
4.97 BLKTYPSIZE 381
4.98 BLOCKINITCOUNTER 382
4.99 BLOCKLOGO 382
4.100 BLOCKREFERENCENAME.BREF 382
4.101 BLOCKREFERENCENAME.DESC 383
4.102 BLOCKREFERENCENAME.TYPE 383
4.103 BLOCKTYPEID 384
4.104 BLOCKTYPNAME 384
4.105 BLOCKTYPENAME 385
4.106 BLOCKMAPPING 386
4.107 BMODULES 386
4.108 BOOLMUX 387
4.109 BOOLPARAM 387
4.110 BOOLVAL[0…200] 387
4.111 BOOL_VALUE 388
4.112 BOOLVALUEOFF 388
4.113 BOOLVALUEON 389
4.114 BOOTIMAGEVER 389

15
4.115 BOOTROMIMGCHKSMFAIL 390
4.116 BOXCON 390
4.117 BOXCONNSTATE [5..63] 391
4.118 BOXNUM 391
4.119 BOXREADSPPSAVG [5..63] 392
4.120 BOXREADSPPSMAX [5..63] 392
4.121 BOXTYPE 393
4.122 BOXWRITESPPSAVG [5..63] 393
4.123 BOXWRITESPPSMAX [5..63] 394
4.124 BPS 394
4.125 BPSDELAY 395
4.126 BPSDELAYREM 395
4.127 BRDGBCASTARR 396
4.128 BRDGLCLTYARR 396
4.129 BRDGPHYARR 397
4.130 BRDGLOGARR 397
4.131 BRDGRXPKTSARR 398
4.132 BRDNINCONGRUENTVIEWS 398
4.133 BREVISION 399
4.134 BRNGTEMPTRIP 399
4.135 BRNGTEMPTRIPACTED 399
4.136 BRNGTEMPALM.FL 400
4.137 BRNGTEMPALM.OPT 400
4.138 BRNGTEMPALM.PR 401
4.139 BRNGTEMPALM.SV 401
4.140 BSHILM 401
4.141 BSLOLM 402

16
4.142 BUFFERTIME 402
4.143 BUFTM_SET 403
4.144 BUFXMAX[0..5] 403
4.145 BUFXTOTAL[0..5] 403
4.146 BUFXUSED[0..5] 404
4.147 BURNOUTMODE 404
4.148 BVERSION 406
4.149 BYPCANCELOPT 406
4.150 BYPASS 407
4.151 BYPPERM 407
Chapter 5 - Cxxxx Parameters 408
5.1 C[1..8] 422
5.2 C[1..10] 422
5.3 C[1..10].BYPPERM 423
5.4 C[1..10].BYPREQ 423
5.5 C[1..10].CONFIGCODE 424
5.6 C[1..10].CONFIGDESC 424
5.7 C[1..10].CONFIGSTS 425
5.8 C[1..10].DESC 425
5.9 C[1..10].EXECCODE 425
5.10 C[1..10].EXECDESC 426
5.11 C[1..10].EXECSTS 426
5.12 C[1..10].EXPR 427
5.13 C[1..10].EXPRPCODE 427
5.14 C[1..10].FL 428
5.15 C[1..10].GATEASGN 428
5.16 C[1..10].INVOKFL 428

17
5.17 C1 429
5.18 C1[0..7] 430
5.19 C2 431
5.20 C2[0..7] 433
5.21 C3 433
5.22 C3[0..5] 434
5.23 C300COMMAND 435
5.24 C300IP 435
5.25 C300MAXTEMP [1...3] 435
5.26 C300MINTEMP [1...3] 436
5.27 C300STATE 436
5.28 C300MODTYPE 437
5.29 C300TEMP [1...3] 437
5.30 CABCOMMAND 438
5.31 CABEXECTIMER 438
5.32 CABINETNAME 439
5.33 CABINETPOSITION 440
5.34 CABINSTCOUNT 440
5.35 CABPREFRDTIM 441
5.36 CABPREFWRTIM 442
5.37 CABSOFTVER 442
5.38 CABSTATE 443
5.39 CABTYPNAME 443
5.40 CALBIAS 444
5.41 CALBIAS[0..numChans-1] 444
5.42 CALBIAS[0..7] 445
5.43 CALIBALLA 445

18
5.44 CALIBALLB 446
5.45 CALIBFTA1STS 446
5.46 CALIBFTA2STS 447
5.47 CALIBRATION 447
5.48 CALIBRJSTS 448
5.49 CALIBSTS 448
5.50 CAPABILITY 449
5.51 CAPVALOPT 450
5.52 CAPSAFEVAL 450
5.53 CARDTYPE 451
5.54 CASREQFL 451
5.55 CASSTS 452
5.56 CATNUMBER 452
5.57 CBADREADS 453
5.58 CBBLOCKPROP 453
5.59 CBBLOCKPROPI 454
5.60 CARRYDNFL 454
5.61 CARRYUPFL 454
5.62 CC3SUPRTDV 455
5.63 CCBFMTAV 456
5.64 CCLCNT 456
5.65 CCFTOL 456
5.66 CCLINFO[0..49] 457
5.67 CCLLOADSTAT 457
5.68 CCLNAME[0..49] 458
5.69 CCLPACKET 458
5.70 CCLSIZE[0..49] 458

19
5.71 CCRRUNCOUNT 459
5.72 CDDMTYPINSTCNT 459
5.73 CDDMTYPNAME 460
5.74 CDISPAVGCHPPS 460
5.75 CDISPAVGLPS [1...RDISPCONNMAX] 460
5.76 CDISPAVGLPSCONN [1...RDISPCONNMAX] 461
5.77 CDISPAVGPPS [1...RDISPCONNMAX] 461
5.78 CDISPAVGPPSCONN [1...RDISPCONNMAX] 462
5.79 CDISPAVGSPS [1...RDISPCONNMAX] 462
5.80 CDISPAVGSPSCONN [1...RDISPCONNMAX] 463
5.81 CDISPEXCHAVGPPSCONN 463
5.82 CDISPEXCHAVGSPSCONN 463
5.83 CDISPEXCHMAXPPSCONN 464
5.84 CDISPEXCHMAXSPSCONN 464
5.85 CDISPMAXCHPPS 465
5.86 CDISPMAXLPS [1...RDISPCONNMAX] 465
5.87 CDISPMAXLPSCONN [1...RDISPCONNMAX] 466
5.88 CDISPMAXPPS [1...RDISPCONNMAX] 466
5.89 CDISPMAXPPSCONN [1...RDISPCONNMAX] 467
5.90 CDISPMAXSPS [1...RDISPCONNMAX] 467
5.91 CDISPMAXSPSCONN [1...RDISPCONNMAX] 468
5.92 CEECMDENUMMASK 468
5.93 CEECOLDFL 469
5.94 CEECOMMAND 469
5.95 CEEIOID 470
5.96 CEEIP 470
5.97 CEENUM 470

20
5.98 CEERESADDR[1..15] 471
5.99 CEERESADDRN[1..15] 471
5.100 CEESTARTOPT 472
5.101 CEESTATE 474
5.102 CEESWITCHFL 475
5.103 CEETAG 475
5.104 CEETOPSTART 476
5.105 CEEWARMFL 477
5.106 CF1 477
5.107 CF2 478
5.108 CFIFORATEA 478
5.109 CFIFORATEM 479
5.110 CHANFBNAME[0..63] 479
5.111 CHANINUSE[0..31] 479
5.112 CHANLASTMBERR[0..63] 481
5.113 CHANLASTMBERRTIME[0..63] 487
5.114 CHANMBERRCNT[0..63] 487
5.115 CHANMBERRFL[0..63] 488
5.116 CHANNAME 488
5.117 CHANNAME[1..NUMCHAN] 488
5.118 CHANNEL [0..NUMCHANNELS-1] 489
5.119 CHANNUM 489
5.120 CHANREQRSPRCVD[0..63] 490
5.121 CHANREQSENT[0..63] 491
5.122 CHANRSTSTATS 491
5.123 CHANSTS 492
5.124 CHANSTS[0..63] 492

21
5.125 CHANSTS[0..31] 493
5.126 CHANTEXT 493
5.127 CHANTYPE 494
5.128 CHASSISSIZE 494
5.129 CHGINDEX 495
5.130 CHIGHREADAVGPPS 495
5.131 CHIGHREADMAXPPS 496
5.132 CHGOFSTALM.PR 496
5.133 CHGOFSTALM.SV 497
5.134 CHGOFSTALM.TM 497
5.135 CHILDUCMACQ 497
5.136 CHNFLTSTS[0..numChans-1] 498
5.137 CHNLNAME 498
5.138 CHNLNAME_AI_C 499
5.139 CHNLNAME_AI_S 500
5.140 CHNLNAME_AO_C 501
5.141 CHNLNAME_AO_S 502
5.142 CHNLNAME_DI_C 503
5.143 CHNLNAME_DI_S 504
5.144 CHNLNAME_DO_C 505
5.145 CHNLNAME_DO_S 506
5.146 CHNLNAME[1..NUMCHAN] 507
5.147 CHNLSF1A 507
5.148 CHNLSF2A 508
5.149 CHNLSF1B 508
5.150 CHNLSF2B 509
5.151 CHNSTS[0..numChans-1] 509

22
5.152 CIDLOADMORE 510
5.153 CIDLOADSTATUS 510
5.154 CINCONNHNDL[1..10][1..6] 510
5.155 CINCONNNAV[1..10][1..6] 511
5.156 CINCONNPRM[1..10][1..6] 511
5.157 CINCONNSTRVAL[1..10][1..6] 512
5.158 CINCONNVAL[1..10][1..6] 512
5.159 CJDISABLE 512
5.160 CJENABLE [0..NUMCHANNELS-1] 513
5.161 CJMODE 513
5.162 CJNOTCHFLT 514
5.163 CJOFFSET 514
5.164 CJOFFSET[0..numChans-1] 515
5.165 CJOFFSET [0..NUMCHANNELS-1] 515
5.166 CJOVERRANGE 516
5.167 CJSTATUS [0..NUMCHANNELS-1] 516
5.168 CJTACT 517
5.169 CJTEMP 517
5.170 CJ_BOTTOM 518
5.171 CJ_TOP 518
5.172 CJUNDERRANGE 519
5.173 CLEARGAINDELAY 519
5.174 CLIENTCONNSTS[0..4] 519
5.175 CLIENTIP[0..4] 520
5.176 CLIENTNAME 520
5.177 CLKADJUST 521
5.178 CLKTIME 521

23
5.179 CLKZONE 522
5.180 CLOSEDLOOPRESP 522
5.181 CLOSEFEEDBKTIME 523
5.182 CLOSEIBV 523
5.183 CLOSEMAIN 524
5.184 CLOSEPULSEWIDTH 524
5.185 CLOSESEQ 524
5.186 CLOSESEQALM.FL 525
5.187 CLOSESEQALM.PR 525
5.188 CLOSESEQALM.SV 526
5.189 CLOWREADAVGPPS 526
5.190 CLOWREADMAXPPS 527
5.191 CLR_GD_C 527
5.192 CLROPREQFL 527
5.193 CLRQUEUEOPT 528
5.194 CLUSTERID 528
5.195 CLXCONNSTS 529
5.196 CLXCONNSTS[0-3] 529
5.197 CLX_GATEWAY 530
5.198 CLX_TAG 531
5.199 CMACTIVEFL 531
5.200 CMAXTEMP 532
5.201 CMDATTR 532
5.202 CMDCLOSE 533
5.203 CMDDISALM.FL 533
5.204 CMDDISALM.PR 533
5.205 CMDDISALM.SV 534

24
5.206 CMDDISALM.TM[0..2] 534
5.207 CMDEXEC 535
5.208 CMDFALALM.FL 535
5.209 CMDFALALM.PR 536
5.210 CMDFALALM.SV 536
5.211 CMDFALALM.TM[0..2] 537
5.212 CMDFPVALUE 537
5.213 CMDOPEN 538
5.214 CMDREADY 538
5.215 CMDREQIN 538
5.216 CMDRUN 539
5.217 CMDSTOP 539
5.218 CMINTEMP 540
5.219 CMLOADFL 540
5.220 CMODULES 541
5.221 CNETCONNECT 541
5.222 CNTDNFL 542
5.223 CNTEQN 542
5.224 CNTLVLFL 543
5.225 CNTUPFL 543
5.226 CNUMSRCCONN[1..10] 544
5.227 COLLCOUNT 544
5.228 COMBOPOINT 545
5.229 COMMAND 545
5.230 COMMAND[1..200] 549
5.231 COMMANDACK[1..4] 550
5.232 COMMANDSTATS[1..200] 551

25
5.233 COMMERROR[1..24] 551
5.234 COMMERROR[1..200] 552
5.235 COMMFAILFL 552
5.236 COMMFAULT 553
5.237 COMMOK 553
5.238 COMMSTATUS 553
5.239 COMMTHRESHOLD 554
5.240 COMPARBITRATIONSTS 554
5.241 COMPHILM 555
5.242 COMPELETED 555
5.243 COMPLOLM 556
5.244 COMPNVSCMD 556
5.245 COMPOSITEKEYSW 557
5.246 COMPOSITEPHASESTS 558
5.247 COMPTERM 559
5.248 COMPUTEARW 559
5.249 CONFIGCODE 560
5.250 CONFIGCODE[1..8] 567
5.251 CONFIGDESC 567
5.252 CONFIGDESC[1..8] 576
5.253 CONFIGPROVERSIGNAL 577
5.254 CONFIGSTS 578
5.255 CONFIGSTS[1..8] 578
5.256 CONFIGURATIONFILE 579
5.257 CONFIGURED 579
5.258 CONFIGVERSION 580
5.259 CONFIRM[0..15] 580

26
5.260 CONFIRMED[0..15] 580
5.261 CONFLICTFL 581
5.262 CONINUSE 582
5.263 CONINUSEMON 582
5.264 CONNCLOSEFAIL 583
5.265 CONNECTIONERROR 583
5.266 CONNECTIONEVTTIME 584
5.267 CONNERR 584
5.268 CONFIGINFO 585
5.269 CONFIGVER 586
5.270 CONFREVMISMATCH 586
5.271 CONNLISTSIZE 587
5.272 CONNOPENFAIL 587
5.273 CONNOPENREJECT 588
5.274 CONNSENDERR 588
5.275 CONNSTAT 588
5.276 CONNSTATUS 589
5.277 CONNSTS[0..1] 590
5.278 CONNTMOMULT 590
5.279 CONSOPENRDY 591
5.280 CONSOLIDATECONN 591
5.281 CONSSTARTRDY 592
5.282 CONST[1...8] 592
5.283 CONSTACCLOCK 593
5.284 CONSTENABLE 594
5.285 CONTAINEDIN 595
5.286 CONTAINMEM 595

27
5.287 CONTCUTOUT 596
5.288 CONTOUSE 596
5.289 CONTROLLOCK 597
5.290 CONTROLPREDICTION 597
5.291 CONTROLPRIORITY 598
5.292 CONTROLREQ 598
5.293 CONVTOASCII 599
5.294 CONVTOLONG 599
5.295 COS 600
5.296 COS[0..NumChans-1] 600
5.297 COUNTERTYPE 600
5.298 CHGOFSTALMENB 601
5.299 CP[1..10] 601
5.300 CPCOMPATIBLE 602
5.301 CPCODESIZE[1..10] 602
5.302 CPEERAVGLPS [1..RPEERCONNMAX] 603
5.303 CPEERAVGLPSCONN [1...RPEERCONNMAX] 603
5.304 CPEERAVGPPS [1...RPEERCONNMAX] 604
5.305 CPEERAVGPPSCONN [1...RPEERCONNMAX] 604
5.306 CPEERAVGSPS [1...RPEERCONNMAX] 605
5.307 CPEERAVGSPSCONN [1...RPEERCONNMAX] 605
5.308 CPEEREXCHAVGPPSCONN 605
5.309 CPEEREXCHAVGSPSCONN 606
5.310 CPEEREXCHMAXPPSCONN 606
5.311 CPEEREXCHMAXSPSCONN 607
5.312 CPEERMAXLPS [1...RPEERCONNMAX] 607
5.313 CPEERMAXLPSCONN [1...RPEERCONNMAX] 607

28
5.314 CPEERMAXPPS [1...RPEERCONNMAX] 608
5.315 CPEERMAXPPSCONN [1...RPEERCONNMAX] 608
5.316 CPEERMAXSPS [1...RPEERCONNMAX] 609
5.317 CPEERMAXSPSCONN [1...RPEERCONNMAX] 609
5.318 CPEERWAAVGPPS 610
5.319 CPEERWAAVGPPSCONN 610
5.320 CPEERWAMAXPPS 611
5.321 CPEERWAMAXPPSCONN 611
5.322 CPLASTSAVE 612
5.323 CPMCOMMAND[0..numChans-1] 612
5.324 CPMCOMMAND 613
5.325 CPMSTATE 613
5.326 CPNODESTATEPARM 614
5.327 CPPARPERFRAG 614
5.328 CPRESTORESCOPE 615
5.329 CPSAVCOMPPERC 615
5.330 CPSLEEPTIME 616
5.331 CPSTATUS 616
5.332 CPTIMEOFSAVE 617
5.333 CPUCYCLEAVG[0..39] 617
5.334 CPUCYCLEMAX[0..39] 618
5.335 CPU0FREEAVG 619
5.336 CPU0FREEMIN 619
5.337 CPU1FREEAVG 620
5.338 CPU1FREEMIN 620
5.339 CPUFREEAVG 621
5.340 CPUFREEAVGA 622

29
5.341 CPUFREEAVGB 622
5.342 CPUFREECRITLM 623
5.343 CPUFREEMIN 623
5.344 CPUFREEMIN1 624
5.345 CPUFREELOWLM 625
5.346 CPUFREEMINA 625
5.347 CPUFREEMINB 626
5.348 CPUFREERESET 626
5.349 CPULOLM 627
5.350 CPULOLOLM 627
5.351 CPUMAXFLOAT 628
5.352 CPV 628
5.353 CPVALIDSAVESTATES 629
5.354 CPVALIDSAVESTATESSZ 629
5.355 CPVALIDRESTSTATES 630
5.356 CPVALIDRESTSTATESSZ 630
5.357 CRCYCLEOVRN[0..40] 631
5.358 CRCYCLESKIP 631
5.359 CRCYCLESKIP[0..40] 632
5.360 CREATEDBY 632
5.361 CROSSOVERCABLEFAILED 633
5.362 CRSKIPPERIOD 634
5.363 CRSKIPPERIOD[0..40] 634
5.364 CSRC[1..10][1..6] 635
5.365 CSTS[1..8] 635
5.366 CTEMP 636
5.367 CTLACTN 637

30
5.368 CTLEQN 637
5.369 CTLINIT 637
5.370 CTRLIPADDR 638
5.371 CTLSTATE 638
5.372 CTRLCAPABILITY 639
5.373 CTRLCONFIRM 639
5.374 CTRLDESC 640
5.375 CTRLMODE 640
5.376 CTRLNAME 641
5.377 CTRLRESTART 642
5.378 CTRLSTATE 642
5.379 CTRLSTATUS 642
5.380 CTRLSTEPPEDFLAG 643
5.381 CURDEVICEIDX 643
5.382 CUROBJVALUE 644
5.383 CURHOSTNAME 644
5.384 CURHRERRFIFOENTRY 644
5.385 CURHRRCVFIFOENTRY 645
5.386 CURHRRPTFIFOENTRY 645
5.387 CURPINPT 646
5.388 CURPROFILEID 646
5.389 CURRDESCREF 647
5.390 CURRELINIDLY 647
5.391 CURRENTBATCHSIZE 648
5.392 CURRENTREL 648
5.393 CURRENTVERSION 649
5.394 CURREUDESCREF 649

31
5.395 CURRNUMACT 650
5.396 CURRVALREF 650
5.397 CURRVALTREND 651
5.398 CURSEGID 651
5.399 CURSEGTYP 652
5.400 CURTIME 652
5.401 CUSTPCRANGE 654
5.402 CUSTYPHELPTXT 654
5.403 CUTOFF.LM 655
5.404 CV 655
5.405 CV.ABSDEVIATION 656
5.406 CV.ACTIVEHL 656
5.407 CV.ACTIVELL 656
5.408 CV.ACTIVEVAL 657
5.409 CV.BADCOUNT 657
5.410 CV.BadPV 658
5.411 CV.BadPVShedTime 658
5.412 CV.BADPVSHEDTIMEFL 658
5.413 CV.BADREADSALLOWED 659
5.414 CV.BALANCEFACTOR 659
5.415 CV.BALANCETARGET 660
5.416 CV.BIAS 660
5.417 CV.CALCBLKINTERVALS 660
5.418 CV.CLLOOPRESPTIME 661
5.419 CV.CONSTRAINTTYPE 661
5.420 CV.CONTROLPRIORITY 662
5.421 CV.CONTROLTHISCV 662

32
5.422 CV.CRITICAL 662
5.423 CV.CVBIAS 663
5.424 CV.CVINDEX 663
5.425 CV.DCSVALUE 664
5.426 CV.DECOUPLERATIO 664
5.427 CV.DELTAACTSOFTHILIM 664
5.428 CV.DELTAACTSOFTLOLIM 665
5.429 CV.DELTASOFTHL 665
5.430 CV.DELTASOFTLL 666
5.431 CV.DESC 666
5.432 CV.DESIREDVALUE 666
5.433 CV.DEVIATION 667
5.434 CV.DISTURBANCE 667
5.435 CV.DISTURBANCEFLAG 668
5.436 CV.DISTURESTTUNING 668
5.437 CV.ENGGHIGHLIMIT 668
5.438 CV.ENGGLOWLIMIT 669
5.439 CV.ENGGUNITS 669
5.440 CV.ER_C 670
5.441 CV.ERRORTOLERANCE 670
5.442 CV.EXECUTIONSTATUS 670
5.443 CV.FF2FBPERFRAT_C 671
5.444 CV.FF2FBPERFRATIO 671
5.445 CV.FILTEREDBIAS 672
5.446 CV.FILTEREDRAMP 672
5.447 CV.FUNNELTYPE 672
5.448 CV.FUTUREVAL 673

33
5.449 CV.FUTUREVAL_C 673
5.450 CV.HIGHLIMIT 674
5.451 CV.HIGHLIMIT_C 674
5.452 CV.HLERRORWEIGHT 674
5.453 CV.HLRAMP 675
5.454 CV.HLRAMPRATE 675
5.455 CV.HOLDINTEGRATOR 676
5.456 CV.HOLDINTEGRATORENUM 676
5.457 CV.INITMODE 676
5.458 CV.INTEGRATINGCV 677
5.459 CV.LASTBAD 677
5.460 CV.LASTGOOD 678
5.461 CV.LINEARCOEFF 678
5.462 CV.LINEARCOEFF_C 678
5.463 CV.LLERRORWEIGHT 679
5.464 CV.LLRAMP 679
5.465 CV.LLRAMPRATE 680
5.466 CV.LOWLIMIT 680
5.467 CV.LOWLIMIT_C 680
5.468 CV.MINFUNNEL 681
5.469 CV.MODELINDEX1 681
5.470 CV.MODELINDEX2 682
5.471 CV.MODELTYPE 682
5.472 CV.MOVECAUSE 682
5.473 CV.MOVECAUSEDESC 683
5.474 CV.MOVEINDEPMOVEDESC1 683
5.475 CV.MOVEINDEPMOVEDESC2 684

34
5.476 CV.NAME 684
5.477 CV.NEWVALUEFLAG 684
5.478 CV.NEWVALUEPINCONN 685
5.479 CV.NOISEVARIANCE 685
5.480 CV.NUMBEROFBLOCKS 686
5.481 CV.PERFRATIO 686
5.482 CV.PERFRATIO_C 686
5.483 CV.PREDSSVALUE 687
5.484 CV.PREDVALUE 687
5.485 CV.PREDVALUE_C 688
5.486 CV.PRIORITY 688
5.487 CV.PROCESSHL 688
5.488 CV.PROCESSHLPINCONN 689
5.489 CV.PROCESSLL 689
5.490 CV.PROCESSLLPINCONN 690
5.491 CV.PVTRACK 690
5.492 CV.PVTRACKENUM 690
5.493 CV.PVVALRESET 691
5.494 CV.PVVALSTATUS 691
5.495 CV.PVVALSTATUS_C 692
5.496 CV.QUADRATICCOEFF 692
5.497 CV.RAMPRATE 692
5.498 CV.RAMPVALUE 693
5.499 CV.RATEBALANCE 693
5.500 CV.READVALUE 694
5.501 CV.READVALUEPINCONN 694
5.502 CV.SCALINGFACTOR 694

35
5.503 CV.SE_C 695
5.504 CV.SETPOINT 695
5.505 CV.SETPOINTRAMP 696
5.506 CV.SETPOINTVAL 696
5.507 CV.SHADOWPRICE 696
5.508 CV.SHADOWPRICEDISPLAY 697
5.509 CV.SSFILTEREDRAMP 697
5.510 CV.SSSTATEESTFILTER 698
5.511 CV.SSVALUE 698
5.512 CV.SSVALUE_C 698
5.513 CV.STATEEST 699
5.514 CV.STATEESTDISPLAY 699
5.515 CV.STATUS 700
5.516 CV.STATUSDISP_C 700
5.517 CV.STATUSDISPLAY 701
5.518 CV.TREATASBAD 701
5.519 CV.UNBIASEDMODELVAL 701
5.520 CV.UPDATEFREQUENCY 702
5.521 CV.VALUE 702
5.522 CV.VALUE_C 703
5.523 CV.WINDUPSTATUS 703
5.524 CV[1..8] 703
5.525 CVEUHI 704
5.526 CVEUHI[1..8] 705
5.527 CVEULO 705
5.528 CVEULO[1..8] 706
5.529 CVGAIN 706

36
5.530 CVINIT 707
5.531 CVINITSRC 707
5.532 CVORFB 708
5.533 CVORFBSRC 708
5.534 CVSRC 708
5.535 CVTYPE 709
5.536 CWRITEAVGPPS 709
5.537 CWRITEMAXPPS 710
5.538 CX[1..10] 710
5.539 CYCLEACTIVE[1..24] 711
5.540 CYCLEACTIVE[1..200] 711
5.541 CYCLEOPT[1..NUMPROFILES] 712
5.542 CYCLESKIPMAX 713
5.543 CYCLETIME 714
5.544 CYCLETIME[0..63] 714
Chapter 6 - Dxxxx Parameters 715
6.1 D[1..5] 722
6.2 D[1..10] 723
6.3 D1 723
6.4 D2 724
6.5 DABLOCKSINCM 724
6.6 DAMPING 725
6.7 DAREF 725
6.8 DATA[1..32] 726
6.9 DATAACQ1 726
6.10 DATAACQ2 727
6.11 DATAACQ3 727

37
6.12 DATAACQBLOCKID1 728
6.13 DATABLOCK 728
6.14 DATAOK[1..4] 729
6.15 DATAOK[1..24] 729
6.16 DATAOK[1..200] 730
6.17 DATAQUEUESZ 730
6.18 DATATYPE 730
6.19 DATECREATED 731
6.20 DATELOADED 732
6.21 DATEMODIFIED 732
6.22 DATEPTIMPORT 733
6.23 DAY 733
6.24 DAYLIGHTTIME 734
6.25 DBLOADCLIENT 734
6.26 DBTRACEENABLE 735
6.27 DBTRACEFLAGS1..6 736
6.28 DBVALID 736
6.29 DBVALID [1..40] 737
6.30 DBVALIDCMD 737
6.31 DBVALID[1..45] 738
6.32 DCPREAD 738
6.33 DCPSCAN 739
6.34 DCPSETFACTORYRESET 739
6.35 DCPSETIPADDR 740
6.36 DCPSETNAME 740
6.37 DCPSETSIGNAL 741
6.38 DEADBAND 741

38
6.39 DEADBAND1 742
6.40 DEADBAND2 742
6.41 DEADTIME 743
6.42 DEADTIMEBIAS 743
6.43 DEBOUNCE 744
6.44 DEBOUNCETIME_DI_C 744
6.45 DEBUG 745
6.46 DEBUGFLAGSET 746
6.47 DECONF 746
6.48 DEFAULTBATCHSIZE 747
6.49 DEFLTREFWARNING 747
6.50 DEFLTREFWARNRPRT 748
6.51 DEFTIMOUT 748
6.52 DELAY 749
6.53 DELAYPRIMARY[1..200] 749
6.54 DELAYPRIMARY[1..24] 750
6.55 DELAYTABLE[1..60] 750
6.56 DELAYTIME 750
6.57 DELAYTYPE 751
6.58 DELCV 752
6.59 DELIVEREDWGT[1..200] 752
6.60 DELTATIME 753
6.61 DENSTEAM 753
6.62 DENWATER 753
6.63 DENWATERREF 754
6.64 DEPLOYMENTINCOMPLETESF 754
6.65 DESC 755

39
6.66 DESIGNEXEC 756
6.67 DEV 756
6.68 DEVADDR 757
6.69 DEVALM.ALL 757
6.70 DEVALM.DB 758
6.71 DEVALM.DBU 758
6.72 DEVALM.FL 759
6.73 DEVALM.PR 759
6.74 DEVALM.SV 759
6.75 DEVALM.TM 760
6.76 DEVALM.TMO 760
6.77 DEVALM.TP 761
6.78 DEVCTL 761
6.79 DEVFLAG[0..N] 761
6.80 DEVFLAG 762
6.81 DEVGENUINE 762
6.82 DEVHIALM.DB 763
6.83 DEVHIALM.DBU 763
6.84 DEVHIALM.FL 764
6.85 DEVHIALM.PR 764
6.86 DEVHIALM.SV 765
6.87 DEVHIALM.TM 765
6.88 DEVHIALM.TMO 766
6.89 DEVHIALM.TP 766
6.90 DevHigh.DeadBandUnits 767
6.91 DevHigh.DeadBandValue 767
6.92 DEVHIGH.FL 768

40
6.93 DevHigh.OffDelayTimeSec 768
6.94 DevHigh.OnDelayTimeSec 768
6.95 DevHigh.Priority 769
6.96 DevHigh.Severity 769
6.97 DevHigh.TripPoint 770
6.98 DEVICE 770
6.99 DEVICEID[0..7] 771
6.100 DEVICEIDX 771
6.101 DEVICELOCATION 773
6.102 DEVICEREVNO[0..7] 773
6.103 DEVICETYPE 774
6.104 DEVLM 774
6.105 DEVLOALM.DB 775
6.106 DEVLOALM.DBU 775
6.107 DEVLOALM.FL 776
6.108 DEVLOALM.PR 776
6.109 DEVLOALM.SV 776
6.110 DEVLOALM.TM 777
6.111 DEVLOALM.TMO 777
6.112 DEVLOALM.TP 778
6.113 DevLow.DeadBandUnits 778
6.114 DevLow.DeadBandValue 779
6.115 DEVLOW.FL 779
6.116 DevLow.OffDelayTimeSec 780
6.117 DevLow.OnDelayTimeSec 780
6.118 DevLow.Priority 781
6.119 DevLow.Severity 781

41
6.120 DevLow.TripPoint 782
6.121 DEVSPCBIT[0..135] 782
6.122 DEVSTS[0..15] 783
6.123 DEVSUPCMDS[0 - 15][0 - 39] 783
6.124 DEVTM 784
6.125 DEVTYPE 784
6.126 DFNPHWYEM 785
6.127 DHCPENABLE 786
6.128 DHCPENDADDR 786
6.129 DHCPSTARTADDR 787
6.130 DI[1..4] 787
6.131 DI[1..10] 788
6.132 DIAGREQSENT[0..15] 788
6.133 DIAGREQRSPRCVD[0..15] 788
6.134 DICHNLNAME 789
6.135 DIGFILTER[0..numChans-1] 789
6.136 DIGFILTER [0..NUMCHANNELS-1] 790
6.137 DIHASENAME 790
6.138 DIMODE 791
6.139 DIPTEXECST 791
6.140 DIPVMAP[0..15] 792
6.141 DIRECTSYNC 792
6.142 DIREGISTERD[ ] 793
6.143 DISABLEBATTERYALARM 793
6.144 DISCONNDEVNAME 794
6.145 DISCREP 794
6.146 DISCRTINPUT1[1..4] 795

42
6.147 DISCRTINPUT2[1..4] 795
6.148 DISCRTINPUT3[1..4] 796
6.149 DISP_C 796
6.150 DISPADJPARAM 796
6.151 DISPLAYEDSTATUS 797
6.152 DISPLAYSTATE 797
6.153 DISPLAYSUBSCRMAXPPS 798
6.154 DISPOVRLOAD 798
6.155 DISPPOS 799
6.156 DISPRATEAVG 799
6.157 DISPRATEMAX 800
6.158 DISPSUBCACHEFRFCTR 800
6.159 DISQSECCMD 801
6.160 DISRC [1..10] 801
6.161 DISTS[1..10] 802
6.162 DITYPE 802
6.163 DLCNBSLOT 803
6.164 DL_RPI 803
6.165 DLINKDLRROLE 804
6.166 DLINK1FAILED 804
6.167 DLINK1FRAMECRCERR 805
6.168 DLINK1LANIDERR 806
6.169 DLINK1MACADDR 807
6.170 DLINK1LASTACTIVE 807
6.171 DLINK2LASTACTIVE 808
6.172 DLINK2MACADDR 808
6.173 DLINK1RXRATE 809

43
6.174 DLINK1RXRATELIMIT 810
6.175 DLINK1RXRATEMAX 810
6.176 DLINK1SILENT 811
6.177 DLINK1TXRATE 812
6.178 DLINK1TXRATEMAX 813
6.179 DLINK2FAILED 815
6.180 DLINK2FRAMECRCERR 816
6.181 DLINK2LANIDERR 816
6.182 DLINK2SILENT 817
6.183 DLINK2RXRATE 818
6.184 DLINK2RXRATELIMIT 819
6.185 DLINK2RXRATEMAX 820
6.186 DLINK2TXRATE 821
6.187 DLINK2TXRATEMAX 822
6.188 DLINKDUPEADDR 823
6.189 DLINKENABLE 824
6.190 DLINKHELP2 825
6.191 DLINKHELP 825
6.192 DLINKNETWORKERR 826
6.193 DLINKIPADDR 826
6.194 DLINKIPADDRMASK 827
6.195 DLINKIPADDRMASKSTR 827
6.196 DLINKIPADDRSTR 828
6.197 DLINKPARTNERNOTVISIBLE 828
6.198 DLINKNETWORKERR 829
6.199 DLINKRDNPROTO 830
6.200 DLINKRXERR 830

44
6.201 DLINKRXRATE 831
6.202 DLINKRXRATEMAX 832
6.203 DLINKTXERR 833
6.204 DLINKTXRATEMAX 834
6.205 DLINKVLANID 835
6.206 DLRACTIVESUP 835
6.207 DLRACTIVESUPPRI 836
6.208 DLRCURRENTROLE 836
6.209 DLRFAULTCNT 837
6.210 DLRINTERVAL 837
6.211 DLRNODECOUNT 838
6.212 DLRPRECEDENCE 838
6.213 DLRRESETFAULT 838
6.214 DLRRINGFAULT 839
6.215 DLRRINGMODE 839
6.216 DLRRINGSTATE 840
6.217 DLRTIMEOUT 840
6.218 DLRVERIFYFAULTLOC 841
6.219 DLYTIME 841
6.220 DO[1..3] 842
6.221 DOMSO 842
6.222 DOMSO[0..numChans-1] 843
6.223 DONEFL 843
6.224 DOOP 843
6.225 DOPTEXECST 844
6.226 DOSTYPE 844
6.227 DOTNETVER[0..1] 845

45
6.228 DOTYPE 846
6.229 DOVALSTS[1..2] 847
6.230 DOWNLINKFAIL 847
6.231 DP 848
6.232 DPBIAS 848
6.233 DPENGUNIT 848
6.234 DPSLOPE 849
6.235 DPV 849
6.236 DRAWINGINFO 850
6.237 DRIVERNAME 850
6.238 DRIVERNAME 850
6.239 DRVMEMFREE 851
6.240 DRVMEMRESERVED 851
6.241 DRVMEMUSED 852
6.242 DS_SET 852
6.243 DSBLSYNCCMD 852
6.244 DSMAPBLKID 853
6.245 DSMAPCONNVAL 854
6.246 DSPARAMALIAS 854
6.247 DSPARAMCOUNT 854
6.248 DSPARAMRCBBLOB 855
6.249 DSPARAMRCBBLOBCRC 855
6.250 DSPARAMRCBBLOBSIZE 856
6.251 DSPARAMRCBBLOBARRCOUNT 856
6.252 DSSOURCE 856
6.253 DTANORM 857
6.254 DTAOFFSET 857

46
6.255 DTASCALE 858
6.256 DTIME 858
6.257 DTIMEAVG 859
6.258 DTIMEAVGCOMP 859
6.259 DTIMEMAX 860
6.260 DTIMEMIN 860
6.261 DTIMESTD 860
6.262 DTIMESTDPRC 861
6.263 DUPIOLADDR 861
6.264 DUPIPIECNETWORK 862
6.265 DV.ACTIVEPROCESSVALUE 862
6.266 DV.ACTIVEVALUE 863
6.267 DV.BIAS 863
6.268 DV.CRITICAL 863
6.269 DV.DESC 864
6.270 DV.DVINDEX 864
6.271 DV.ENGGUNITS 865
6.272 DV.EXECSTATUS 865
6.273 DV.ISBAD 865
6.274 DV.NAME 866
6.275 DV.PREVIOUSVAL 866
6.276 DV.PVVALRESET 867
6.277 DV.PVVALSTATUS 867
6.278 DV.PVVALSTATUS_C 867
6.279 DV.READPROCESSVAL 868
6.280 DV.READVALUE 868
6.281 DV.READVALUEPINCONN 869

47
6.282 DV.SCALINGFACTOR 869
6.283 DV.STARTVALUE 869
6.284 DV.STATUS 870
6.285 DV.STATUSDISP 870
6.286 DV.STATUSDISP_C 871
6.287 DV.TYPICALMOVESIZE 871
6.288 DV.USETHISDV 871
6.289 DV.VALUE 872
6.290 DV.WINDUPSTATUS 872
6.291 DVRNGEXT 873
6.292 DYNPEERALLOC 873
6.293 DYNSTATE[1.255] 874
Chapter 7 - Exxxx Parameters 876
7.1 EAGN 883
7.2 EAMRDATAPKTSPERSEC 883
7.3 EAMRMSGSPERSEC 884
7.4 EAMRPERCENTOPTAVG 884
7.5 EAMRRDNXFERMBPERSEC 885
7.6 EAMRSIGPKTSPERSEC 885
7.7 EAPPCONNTONSTATUS 886
7.8 EAPPNODEIP 886
7.9 EAPPNODENAME 887
7.10 ECHSWDESC[0...63] 887
7.11 EDGEDETECT 888
7.12 EDGEDETECT[0..7] 889
7.13 EDITLOCK 889
7.14 EEGSTATE 890

48
7.15 EFFECOPTSPEED 891
7.16 EHBADDED 891
7.17 EHBADDEDIP 892
7.18 EHBHWYNUM 892
7.19 EHBLC1 893
7.20 EHBLC2 893
7.21 EHBLCIP1 894
7.22 EHBLCIP2 894
7.23 EHBRMIP1 895
7.24 EHBRMIP2 896
7.25 EHBROLEFORBOX [5..63] 897
7.26 EHBTHIS 897
7.27 EHBTHISIP 898
7.28 EHPMDATAACCESS 898
7.29 EHPM_ERRCODE 899
7.30 EHPM_SELFTEST 900
7.31 EHPMSTATE 900
7.32 EICONNERRCODE[0..8] 901
7.33 EICONNERRINFO[0..8] 901
7.34 EICONNSTS[0..8] 902
7.35 EIOMTYPE 902
7.36 EIM_IPADDRESS 903
7.37 EIMNAME 903
7.38 EIMTYPE 904
7.39 EIMDISCONNECTDEVNAME 904
7.40 EIPATH[0..8] 904
7.41 EIPMODE 905

49
7.42 EIPSUPPORTED 905
7.43 EIPIOIPADDR 906
7.44 EIPIOCONNSTS 906
7.45 EIPIOSLOTNUM 907
7.46 ELCNBCOMMAND 908
7.47 ELCNBNUM 909
7.48 ELCNBSTATE 909
7.49 ELCNCOMMINV 910
7.50 ELCNLNGTHINV 910
7.51 ELCNMULTIIPADDRSTR 911
7.52 ELCNNODECOMMAND 912
7.53 ELCNNODENUM 912
7.54 ELCNNODENUMPARTNER 913
7.55 ELCNNODESTAT1 913
7.56 ELCNNODESTAT2 914
7.57 ELCNNODESTAT3 914
7.58 ELCNNODESTAT4 915
7.59 ELCNNODESTAT5 915
7.60 ELCNNODESTAT6 916
7.61 ELCNNODESTAT7 916
7.62 ELCNNODESTAT8 917
7.63 ELCNNODESTAT9 917
7.64 ELCNNODESTAT10 918
7.65 ELCNNODESTAT11 918
7.66 ELCNNODESTAT12 919
7.67 ELCNNODESTAT13 919
7.68 ELCNNODESTAT14 920

50
7.69 ELCNNODESTAT15 920
7.70 ELCNNODESTAT16 921
7.71 ELCNNODESTAT17 921
7.72 ELCNNODESTAT18 922
7.73 ELCNNODESTAT19 922
7.74 ELCNNODESTAT20 923
7.75 ELCNNODESTAT21 923
7.76 ELCNNODESTAT22 924
7.77 ELCNNODESTAT23 924
7.78 ELCNNODESTAT24 925
7.79 ELCNNODESTAT25 925
7.80 ELCNNODESTAT26 926
7.81 ELCNNODESTAT27 926
7.82 ELCNNODESTAT28 927
7.83 ELCNNODESTAT29 927
7.84 ELCNNODESTAT30 928
7.85 ELCNNODETYPE 928
7.86 ELCNPACKETINV 929
7.87 ELCNRXRATE 929
7.88 ELCNRXRATEMAX 930
7.89 ELCNSEQINV 930
7.90 ELCNSRCINV 931
7.91 ELCNSTATSRST 931
7.92 ELCNTOLCNRATE 932
7.93 ELCNTOLCNRATEMAX 932
7.94 ELCNTXRATE 933
7.95 ELCNTXRATEMAX 933

51
7.96 ELEMSUBVAL 933
7.97 ELEMSUBVALTYPE 934
7.98 ELOF[0..numChans-1] 935
7.99 ENABLE[1..10] 935
7.100 ENABLE 935
7.101 ENABLECAB 936
7.102 ENABLEDEVICE[0..15] 937
7.103 ENABLELOGICALENIM 937
7.104 ENABLEMVDROPIFINIT 937
7.105 ENABLEMVREADVALIDATION 938
7.106 ENABLENAMUR 938
7.107 ENABLEOPMTOELCN 939
7.108 ENABLEOPMTOLCN 940
7.109 ENABLESCDETECT 940
7.110 ENABLESOE 941
7.111 ENBEXTPATH 941
7.112 ENBHANDLER[1..8] 942
7.113 ENBLATALM[0..numChans-1] 943
7.114 ENBLGANGEDOUTPUTS 943
7.115 ENBLLOGICALENIM 944
7.116 ENBLSTBYCMD 944
7.117 ENBLSYNCCMD 945
7.118 ENBMEMALMFL 945
7.119 ENBNOLOAD[0..numChans-1] 946
7.120 ENBSCHDTRAF 946
7.121 ENBSHUTDOWN 947
7.122 ENCMDS 947

52
7.123 ENDOFFSET 948
7.124 ENDPHASE 948
7.125 ENDTIME 949
7.126 ENETIPADDR[0-3] 950
7.127 ENETIPADDR 950
7.128 ENGUNITSYSTEM 951
7.129 ENHGENLIN1 951
7.130 ENHGENLIN2 952
7.131 ENHREGCALC 952
7.132 ENIMIPADDR 953
7.133 ENIMIPADDRESS 953
7.134 ENIMUCNNUM 954
7.135 ENOLOAD[0..numChans-1] 954
7.136 ENPULSEWIDTHREJ 955
7.137 ENSPAREDETECT 955
7.138 ENTERSBYCMD 956
7.139 ENTHALPY 956
7.140 ENTHALPYENGUNIT 957
7.141 ENTHALPYIO 957
7.142 ENTITYNAME 957
7.143 ENTROPY 958
7.144 ENTROPYENGUNIT 958
7.145 ENTROPYIO 959
7.146 ENUMBOOLMAP[0..63] 959
7.147 EPKSACCESS 960
7.148 EPKSMIGRATIONMODE 960
7.149 EPKSNAME 961

53
7.150 EPKSSTATUS 962
7.151 EPLCGCH1BAUDRATE 962
7.152 EPLCGCH1PARITY 963
7.153 EPLCGCH2BAUDRATE 963
7.154 EPLCGCH2PARITY 963
7.155 EPLCGMULTIBUFPIPELINE 964
7.156 EPLCGREDUNDCOMMSOPTION 964
7.157 EPLCGUSEROUTPUTSUPPRESS 965
7.158 EPMSTATE 965
7.159 EQMTORECMAP 966
7.160 EQNEUNITSOPT 966
7.161 EQUIPEXECSTS 967
7.162 EQUIPNAME 967
7.163 EQUIPMODE 968
7.164 EQUIPMODEATTR 968
7.165 EQUIPREQ.STS 969
7.166 EQUIPSTATE 969
7.167 EQUIPSTATUS.STS 969
7.168 ERRATICFLOW[1..24] 970
7.169 ERRATICFLOW[1..200] 970
7.170 ERRCNT[0..1] 971
7.171 ERRCODE 972
7.172 ERRCODE[0..1] 983
7.173 ERRCODE[0..31] 984
7.174 ERRFL 984
7.175 ERRFL[0..1] 985
7.176 ERRFL[0..31] 985

54
7.177 ERRIN1AV 986
7.178 ERRIN2AV 986
7.179 ERRINFO[0..1] 987
7.180 ERRORCODE 987
7.181 ERRORDBL 987
7.182 ERRORDBR 988
7.183 ERRORINDICATOR 988
7.184 ERRORMSGIDX 988
7.185 ERROSPRESENT 989
7.186 ERROUTAV 989
7.187 ESCKEYSTROKE[1..4] 990
7.188 ESIG 990
7.189 ESTDURATION 990
7.190 ESTWEIGHT 991
7.191 ESWENB 992
7.192 ESWFL.AUTO 992
7.193 ESWFL.BCAS 993
7.194 ESWFL.CAS 993
7.195 ESWFL.MAN 994
7.196 ESWPERM 994
7.197 ETH1IPADDRSTR 995
7.198 ETH1SOFTFAIL 995
7.199 ETH2IPADDRSTR 996
7.200 ETH2SOFTFAIL 996
7.201 ETRANS 996
7.202 EUCNAUTHGROUP 997
7.203 EUDESC 997

55
7.204 EUDESC[0..120] 998
7.205 EURNGEXT 998
7.206 EVALTRANS[1..15][1..10] 999
7.207 EVALTRANSN[1..15][1..10] 999
7.208 EVENTDESC 1000
7.209 EVENTFL[1..NUMEVENTS] 1000
7.210 EVENTBGNTIME[1..NUMPROFILES]
[1..NUMEVENTS] 1001
7.211 EVENTENDTIME[1..NUMPROFILES]
[1..NUMEVENTS] 1001
7.212 EVENTMSGRETRIED 1002
7.213 EVENTMSGSENT 1002
7.214 EVENTNAKRECEIVED 1003
7.215 EVENTQUEUESZ 1003
7.216 EVENTRECEIVERDROPPED 1004
7.217 EVENTSEGID[1..NUMPROFILES][1..NUMEVENTS] 1004
7.218 EVENTSRC 1004
7.219 EVENTTHROTTLEREQ 1005
7.220 EVERIFY[0..numChans-1] 1005
7.221 EVTOPT 1006
7.222 EVTOPTEXEDTL 1008
7.223 EVTOPTFORMULAPARAM 1009
7.224 EVTOPTHIST 1009
7.225 EVTOPTMODEATR 1010
7.226 EVTOPTRCMEXE 1010
7.227 EVTOPTRCMINFO 1011
7.228 EVTOPTRECIPE 1011
7.229 EVTOPTREPORTPARAM 1012

56
7.230 EVTOPTRESALLOC 1012
7.231 EVTOPTSCMS 1013
7.232 EVTOPTSCMTS 1013
7.233 EVTOPTSTATECHG 1014
7.234 EVTOPTSTEPC 1014
7.235 EVTOPTSTEPS 1014
7.236 EWIREOFF[0..numChans-1] 1015
7.237 EXCMODEOPT 1015
7.238 EXCPTALM.PR 1016
7.239 EXCPTALM.SV 1016
7.240 EXCPTNLINENM 1017
7.241 EXCPTNMODULE 1017
7.242 EXCPTNMSG 1018
7.243 EXCPTNTYPE 1018
7.244 EXECCODE 1020
7.245 EXECCODE[1..8] 1036
7.246 EXECDESC 1037
7.247 EXECDESC[1..8] 1038
7.248 EXECIDOPT 1038
7.249 EXECSTATE 1039
7.250 EXECSTS 1040
7.251 EXECSTS[1..8] 1042
7.252 EXECSTSFAILTM 1042
7.253 EXECTIME 1043
7.254 EXECUTEOPT 1044
7.255 EXECUTIONMODE 1044
7.256 EXITOPT 1045

57
7.257 EXPIRATIONDATE 1045
7.258 EXPR[1..8] 1046
7.259 EXPRDESC[1...8] 1046
7.260 EXPRPCODE[1..8] 1047
7.261 External 1047
7.262 EXTERRORSTATUS 1048
7.263 EXTERRORSTATUSN 1048
7.264 EXTGETRQUAVG 1049
7.265 EXTGETRQUMAX 1050
7.266 EXTPATH 1050
7.267 EXTPOWERFAIL 1051
7.268 EXTRAPULSE 1051
7.269 EXTRAPULSETM 1052
7.270 EXTREF 1052
7.271 EXTREFSTRUCT 1053
7.272 EXTSTRRQUAVG 1053
7.273 EXTSTRRQUMAX 1054
7.274 EZCROSS[0..numChans-1] 1054
Chapter 8 - Fxxxx Parameters 1056
8.1 F 1060
8.2 FACTDATAERR 1060
8.3 FAILALM.FL 1061
8.4 FAILALM.PR 1062
8.5 FAILALM.SV 1062
8.6 FAILOPT 1062
8.7 FAILSTATE[0..numChans-1] 1063
8.8 FANFAULTSF 1064

58
8.9 FANOUT 1064
8.10 FANSTS 1065
8.11 FAULTACT[0..numChans-1] 1065
8.12 FAULTDELAY 1066
8.13 FAULTENB[ ] 1066
8.14 FAULTENB[0..7] 1067
8.15 FAULTMODE[0..numChans-1] 1067
8.16 FAULTOPT 1068
8.17 FAULTOPT_AO_C 1070
8.18 FAULTOPT_DO_C 1071
8.19 FAULTRESET 1072
8.20 FAULTST 1073
8.21 FAULTSTATE[0..numChans-1] 1073
8.22 FAULTVALUE 1074
8.23 FAULTVALUE[0..numChans-1] 1075
8.24 FAULTVALUE[0..numChans-1] 1076
8.25 FAULTVALUE[0..numChans-1] 1076
8.26 FAULTVALUE[0..numChans-1] 1077
8.27 FAULTVALUE[0..7] 1077
8.28 FAULTVALUE_AO_C 1078
8.29 FBCONN1 1079
8.30 FBCONN2 1079
8.31 FBCONN3 1080
8.32 FBCONN4 1080
8.33 FBCONN5 1081
8.34 FBCONN6 1081
8.35 FBCONN7 1082

59
8.36 FBCONN8 1082
8.37 FBCONN9 1083
8.38 FBCONN10 1083
8.39 FBORSTS 1084
8.40 FBTYPE 1084
8.41 FCE_OUTPUT[1..24] 1085
8.42 FCE_OUTPUT[1..200] 1085
8.43 FEEDFAILED[1..24] 1086
8.44 FEEDFAILED[1..200] 1086
8.45 FEEDOVERRIDE[1..24] 1087
8.46 FEEDOVERRIDE[1..200] 1087
8.47 FEEDTYPE[1..24] 1088
8.48 FEEDTYPE[1..200] 1088
8.49 FEEDWEIGHT[1..24] 1089
8.50 FEEDWEIGHT[1..200] 1089
8.51 FETCHMODE 1090
8.52 FF 1090
8.53 FFCONN 1091
8.54 FFOPT 1091
8.55 FFPERIOD 1092
8.56 FFSTS 1092
8.57 FILEPOSITION 1093
8.58 FILTERHDR[0..numChans-1] 1093
8.59 FILTEROFF[0..numChans / 8] 1093
8.60 FILTEROFF [0..NUMCHANNELS-1] 1094
8.61 FILTERON [0..NUMCHANNELS-1] 1095
8.62 FILTERON[0..numChans / 8] 1096

60
8.63 FILTERTIME 1096
8.64 FINALCMDPARAM 1096
8.65 FINALCMDPC 1097
8.66 FINALCMDVAL 1098
8.67 FIRSTOUTACTED 1099
8.68 FIRSTOUTALM.FL 1099
8.69 FIRSTOUTALM.PR 1099
8.70 FIRSTOUTALM.SV 1100
8.71 FIRSTOUTINPUT 1100
8.72 FIRSTUPACTED 1101
8.73 FLAG 1101
8.74 FLOAT_VALUE 1102
8.75 FLOAT64PARAM 1102
8.76 FLOAT64VAL[0…40] 1102
8.77 FLSHSTAT 1103
8.78 FLSHSTAT[1..32] 1103
8.79 FLTIP 1104
8.80 FMWREV1 [1...15] through FMWREV8 [1...15] 1104
8.81 FONTSTYLE 1105
8.82 FORCEMODEATTR 1105
8.83 FORCEREADREQ 1106
8.84 FORCERESTART 1106
8.85 FORCETOINACTIVE 1107
8.86 FPGAFAIL 1107
8.87 FPINDICATOR[1..4] 1108
8.88 FPINDRAW[1..4] 1109
8.89 FPVALUE[1..4] 1109

61
8.90 FPVALUERAW[1..4] 1109
8.91 FRC 1110
8.92 FRCPERM 1110
8.93 FRCREQ 1111
8.94 FRCSEL 1111
8.95 FREEARRPARAMWRITES 1112
8.96 FREEARRWRITES 1112
8.97 FREEFL 1112
8.98 FREEMEM 1113
8.99 FREEMEMINK 1113
8.100 FREENONARRPARAMWRITES 1114
8.101 FREESCALARTAGREADS 1114
8.102 FREENONARRWRITES 1115
8.103 FREEUDTTAGREADS 1115
8.104 FREEUDTTAGREAD 1116
8.105 FREESCATAGREAD 1116
8.106 FREEZETIME 1117
8.107 FREQ5060 1117
8.108 FREQ6050 1117
8.109 FREQPERIOD 1118
8.110 FREQPERIOD[0..7] 1119
8.111 FSTFLSHSPD 1119
8.112 FSTS 1120
8.113 FTA1TYPE 1120
8.114 FTA2TYPE 1121
8.115 FTAAOVRNFL 1121
8.116 FTAASTS 1122

62
8.117 FTABOVRNFL 1122
8.118 FTABSTS 1123
8.119 FTACONNA 1123
8.120 FTACONNB 1124
8.121 FTAPRESA 1124
8.122 FTAPRESB 1125
8.123 FTAREVERSEDA 1125
8.124 FTAREVERSEDB 1126
8.125 FTEABLOCKRATE 1126
8.126 FTEARXRATE 1126
8.127 FTEATXRATE 1127
8.128 FTEBBLOCKRATE 1127
8.129 FTEBRXRATE 1128
8.130 FTEBTXRATE 1128
8.131 FTEBBLOCK 1129
8.132 FTEIECSUBNETCONF 1129
8.133 FTEMARTADDRCOUNT 1130
8.134 FTEMARTAVGDEPTH 1130
8.135 FTEMARTCOLLCOUNT 1131
8.136 FTEMARTMAXDEPTH 1131
8.137 FTENETWORKERR 1132
8.138 FTEPARTNERNOTVISIBLE 1132
8.139 FTERECEIVEERRORS 1133
8.140 FTETRANSMITERRORS 1133
8.141 FULLFL 1134
8.142 FULLITEMNAME 1134
8.143 FUNCTIONNAME.DESC 1135

63
8.144 FUNCTIONNAME.TYPE 1135
8.145 FUNCTIONNAME.FCN 1136
8.146 FWINVALIDA 1136
8.147 FWINVALIDB 1137
8.148 FWREVISION 1137
Chapter 9 - Gxxxx Parameters 1138
9.1 G 1140
9.2 G[1..4].ALGID 1140
9.3 G[1..4].FIRSTCOND 1141
9.4 G[1..4].NUMINPTS 1141
9.5 G[1..4].SO 1142
9.6 GAIN 1142
9.7 GAINDELAYCHANGED 1142
9.8 GAINDELAYLOCK 1143
9.9 GAINHILM 1143
9.10 GAINIMPACT 1144
9.11 GAINLOLM 1144
9.12 GAINMULTIPLIER 1144
9.13 GAINOPT 1145
9.14 GAPHILM 1145
9.15 GAPLOLM 1146
9.16 GENERATEALERTS 1146
9.17 GENERRORSTATUS 1146
9.18 GENERRORSTATUSN 1147
9.19 GCBLOCKSINCM 1148
9.20 GENSTATE 1149
9.21 GENSTATEA 1149

64
9.22 GENTESTACTIVE 1150
9.23 GI 1150
9.24 GLOBSCMMON 1150
9.25 GOBACKREL 1151
9.26 GOODPVHHFL 1151
9.27 GOODPVHIFL 1152
9.28 GOODPVLLFL 1152
9.29 GOODPVLOFL 1153
9.30 GOP 1153
9.31 GOPFINAL 1154
9.32 GOPREQ 1154
9.33 GOPSCADA 1155
9.34 GPV 1155
9.35 GPVAUTO 1156
9.36 GROSSWEIGHT[1..24] 1156
9.37 GROSSWEIGHT[1..200] 1157
9.38 GROSSWGTFEED[1..24] 1157
9.39 GROSSWGTFEED[1..200] 1158
9.40 GROUP 1158
9.41 GROUP.NUMBER 1159
9.42 GROUP.NUMPARAMS 1159
9.43 GROUP.PARAM 1160
9.44 GROUP.POSITION 1161
9.45 GSTS 1161
9.46 GWCOMMAND 1162
9.47 GWCURSUBPERIOD 1162
9.48 GwEEC 1163

65
9.49 GWHCIFLAG 1163
9.50 GWHOSTIPPRI 1164
9.51 GWHOSTNAMEPRI 1164
9.52 GWOPCCONNSTATUS 1165
9.53 GWOPCCONNSTR 1165
9.54 GWOPCDCPS 1165
9.55 GWOPCGETERR 1166
9.56 GWOPCGSTATE 1166
9.57 GWOPCPARAMCNT 1167
9.58 GWOPCPMONERR 1167
9.59 GWOPCPMONNAME 1167
9.60 GWOPCPMONQUAL 1168
9.61 GWOPCPMONSTR 1168
9.62 GWOPCSRVSTATE 1169
9.63 GWOPCSTERRAVG 1169
9.64 GWOPCSTERRMAX 1169
9.65 GWOPCPFERRAVG 1170
9.66 GWOPCPFERRMAX 1170
9.67 GWOPCPARAMCNT 1171
9.68 GWOPCSTOREERR 1171
9.69 GWOPCSTOREPS 1172
9.70 GWOPCVERSION 1172
9.71 GWPID 1172
9.72 GWRDNROLE 1173
9.73 GWSTATSRESET 1173
9.74 GWSUBPERIOD 1174
9.75 GWUTCCONVERT 1174

66
Chapter 10 - Hxxxx Parameters 1176
10.1 HALMENABLE 1181
10.2 HANDLER 1182
10.3 HANDLERREF 1182
10.4 HANDLETIMEOUT 1182
10.5 HARDFAIL 1183
10.6 HARDWAREREV[0..7] 1183
10.7 HART[0..7] 1184
10.8 HARTENABLE 1184
10.9 HARTIPENABLE 1185
10.10 HARTSUPPORT 1185
10.11 HARTVERSION 1185
10.12 HAUTODET[1..16] 1186
10.13 HCFGDEV 1187
10.14 HCFGDEVTMPL 1188
10.15 HCMD00 1188
10.16 HCMD12 1189
10.17 HCMD13 1189
10.18 HCMD14 1190
10.19 HCMD16 1190
10.20 HCMD48BT[1..200] 1191
10.21 HCMD48NOTIFY[1..200] 1191
10.22 HCMD48STRNGS[1..200] 1192
10.23 HCMDFAIL 1192
10.24 HCMDFAILFL 1193
10.25 HCMDRESPRDYFL_AI_S 1194
10.26 HCMDRESPRDYFL_AO_S 1194

67
10.27 HCOMERFL 1195
10.28 HCOMFAIL 1195
10.29 HCOMHYS 1196
10.30 HCOMSTS 1197
10.31 HCOMTHRS 1197
10.32 HCUAVAIL 1198
10.33 HCUAVAIL2 1198
10.34 HDAY 1199
10.35 HDESC 1200
10.36 HDEVID 1200
10.37 HDEVIDCD[1..16] 1201
10.38 HDEVIDFL 1201
10.39 HDEVMFG 1202
10.40 HDEVMISM 1202
10.41 HDEVMSG 1203
10.42 HDEVPROFILE 1203
10.43 HDEVREV 1204
10.44 HDEVST 1204
10.45 HDEVSTSTATUS 1205
10.46 HDEVSTS_AI_S 1206
10.47 HDEVSTS_AO_S 1207
10.48 HDEVTYPE 1207
10.49 HDEVTYPE7 1208
10.50 HDEVTYPENAME 1208
10.51 HDVMFGCD 1209
10.52 HDVMFGCD7 1209
10.53 HDVREVCD 1210

68
10.54 HDVTYPCD 1210
10.55 HDVTYPCD7 1211
10.56 HDVTYPCDNAME 1211
10.57 HDWREV[1..8] 1212
10.58 HDWREV1 [1...15] through HDWREV8 [1...15] 1212
10.59 HDYNCC[1..4] 1213
10.60 HDYNDESC[1..4] 1213
10.61 HDYNDSC 1214
10.62 HDYNDVC[1..4] 1215
10.63 HDYNEU[1..4] 1215
10.64 HDYNNAME[1..4] 1216
10.65 HDYNST[1..4] 1216
10.66 HDYNVAL[1..4] 1218
10.67 HEADERID 1218
10.68 HEADERREVISION 1218
10.69 HEADERVERSION 1219
10.70 HEAPMEM 1219
10.71 HelpTxt1 1220
10.72 HENABLE 1220
10.73 HENABLE_AI_C 1221
10.74 HENABLE_AO_C 1221
10.75 HEU 1222
10.76 HEXCOMERRSFL 1222
10.77 HEXTDEVST 1223
10.78 HFASSYNO 1223
10.79 HFLAGS 1224
10.80 HHWREV 1225

69
10.81 HIST.TYPE 1225
10.82 HIALM 1225
10.83 HIALM.PR 1226
10.84 HIALM.SV 1227
10.85 HIALM.TYPE 1227
10.86 HIGHAL 1230
10.87 HIGHENG[0..numChans-1] 1230
10.88 HIGHENG[0..7] 1231
10.89 HIGHSIGNAL[0..numChans-1] 1231
10.90 HIGHSIGNAL[0..7] 1232
10.91 HILMRAMPRATE 1233
10.92 HIOPLHFSTA 1234
10.93 HIOPLHFSTB 1235
10.94 HISHART5 1235
10.95 HIST.STDPHDCOLLRATE 1236
10.96 HIST.EXCPHDCOLLRATE 1236
10.97 HIST.EXTDPHDCOLLRATE 1237
10.98 HIST.FASTPHDCOLLRATE 1238
10.99 HIST 1239
10.100 HISTDESC 1239
10.101 HISTEUDESC[1..50] 1240
10.102 HIST.EXC 1240
10.103 HIST.EXCCOLLRATE 1241
10.104 HIST.EXCOFFSET 1242
10.105 HIST.EXTD 1243
10.106 HIST.FAST 1243
10.107 HIST.FASTCOLLRATE 1244

70
10.108 HIST.GATEPARAM 1245
10.109 HIST.GATESTRING 1245
10.110 HIST.GATEVALUE 1246
10.111 HIST.NUMPARAMS 1247
10.112 HIST.PARAM 1248
10.113 HIST.STD 1248
10.114 HIST.STDCOLLRATE 1249
10.115 HIST.STDOFFSET 1250
10.116 HISTTYPE[1..50] 1251
10.117 HISTVALUE[1..50] 1251
10.118 HISTVALUEMAX[1..50] 1252
10.119 HISTVALUEMIN[1..50] 1252
10.120 HLOCKBYPRIMARYMASTER (HART Revision 6.0
and later) 1253
10.121 HLOCKPERMANENT (HART Revision 6.0 and later) 1253
10.122 HLOCKSTATUS (HART Revision 6.0 and later) 1254
10.123 HLONGTAG 1254
10.124 HMAINTREQ (HART Revision 6.0 and later) 1255
10.125 HMAXDEVVARS (HART Revision 6.0 and later) 1255
10.126 HMONTH 1256
10.127 HMPORTACTIVE 1256
10.128 HMW 1256
10.129 HNCFGCHG (HART Revision 6.0 and later) 1257
10.130 HNCOMERR 1257
10.131 HNMSMINPRE 1258
10.132 HNSMMINPRE (HART Revision 6.0 and later) 1258
10.133 HOLDALM.FL 1259

71
10.134 HOLDALM.PR 1259
10.135 HOLDALM.SV 1260
10.136 HOLDBRTHTM 1260
10.137 HOLDBRTHTP 1261
10.138 HOLDCMD 1261
10.139 HOLDOPT 1262
10.140 HOLDSTEPPER 1263
10.141 HOLDVAL 1263
10.142 HOSTIPPRI 1264
10.143 HOSTNAME 1265
10.144 HOSTNAMEPRI 1265
10.145 HOSTSOESTS 1267
10.146 HOUR 1267
10.147 HPHYSIG 1268
10.148 HPM_CNTRLPERSREV 1268
10.149 HPM_CNTRLPERSVER 1269
10.150 HPM_COMMPERSREV 1269
10.151 HPM_COMMPERSVER 1269
10.152 HPM_FWREV 1270
10.153 HPM_HWREV 1270
10.154 HPM_IOL_HWREV 1271
10.155 HPMNODENO 1271
10.156 HPMSOFTFAIL 1272
10.157 HPVALMCODE 1272
10.158 HPVCHAR 1273
10.159 HPVCHNFLAGS 1273
10.160 HPVDAMP 1274

72
10.161 HPVLRV 1274
10.162 HPVMISM 1275
10.163 HPVTLDST 1275
10.164 HPVURV 1276
10.165 HPVXFRCODE 1277
10.166 HREVMISM 1277
10.167 HSCANCFG 1278
10.168 HSCANOVR 1281
10.169 HSCANTIME 1281
10.170 HSLOT0TS 1282
10.171 HSLOTCC [1..HSLOTVARIDX] (HART Revision 6.0
and later) 1282
10.172 HSLOTDSC[1..HSLOTVARIDX] 1283
10.173 HSLOTDVC[1..HSLOTVARIDX] 1283
10.174 HSLOTEU[1..8] 1284
10.175 HSLOTNAME[1..HSLOTVARIDX] 1284
10.176 HSLOTST [1..HSLOTVARIDX] (HART Revision 6.0
and later) 1285
10.177 HSLOTVAL [1..HSLOTVARIDX] 1286
10.178 HSMSTRFL 1286
10.179 HSTLANIDERRS 1287
10.180 HSLOTVARIDX 1287
10.181 HSWDESC [0..63] 1288
10.182 HSWREV 1288
10.183 HWREVMAJ 1288
10.184 HWREVMIN 1289
10.185 HSWVALUE [0..63] 1289

73
10.186 HWTYPE 1290
10.187 HWYNUM 1290
10.188 HWYNUM1 1291
10.189 HWYNUM2 1291
10.190 HWYNUMADDED 1292
10.191 HWYNUMPRT 1292
10.192 HWYNUMTHIS 1293
10.193 HTAG 1293
10.194 HTDEU 1294
10.195 HTDLRL 1294
10.196 HTDMINSPAN 1295
10.197 HTDSN 1295
10.198 HTDURL 1295
10.199 HUCMDREV 1296
10.200 HVARALERT (HART Revision 6.0 and later) 1296
10.201 HWFAULT 1297
10.202 HWFAULT[0..numChans-1] 1297
10.203 HWREVMAJ 1298
10.204 HWREVMIN 1299
10.205 HWRTPRCTCODE 1300
10.206 HWTEMP 1301
10.207 HYEAR 1301
10.208 HelpTxt1 1301
Chapter 11 - Ixxxx Parameters 1303
11.1 IACYCCONNIMRS[1..IPEERCONNMAX] 1314
11.2 IACYCCONNLRQS[1..IPEERCONNMAX] 1314
11.3 IACYCCONNSRQS[1..IPEERCONNMAX] 1315

74
11.4 IACYCIMRAVAIL 1315
11.5 IACYCIMRMAX 1316
11.6 IACYCIMRUSED 1316
11.7 IACYCIMRUSEDCONN [0...29] 1317
11.8 IACYCLGREQAVAIL 1317
11.9 IACYCLGREQMAX 1318
11.10 IACYCLGREQUSED 1318
11.11 IACYCLGREQUSEDCONN [0...29] 1319
11.12 IACYCSMREQAVAIL 1319
11.13 IACYCSMREQMAX 1319
11.14 IACYCSMREQUSED 1320
11.15 IACYCSMREQUSEDCONN [0...29] 1320
11.16 IBVOPNFDBK 1321
11.17 IBVOPNFDBKSTS 1321
11.18 IBVVLVFDBKTO 1321
11.19 IC.BYPPERM 1322
11.20 IC.BYPREQ 1322
11.21 IC.CONFIGCODE 1323
11.22 IC.CONFIGDESC 1324
11.23 IC.CONFIGSTS 1324
11.24 IC.DESC 1324
11.25 IC.EXECCODE 1325
11.26 IC.EXECDESC 1325
11.27 IC.EXECSTS 1326
11.28 IC.EXPR 1326
11.29 IC.EXPRPCODE 1326
11.30 IC.FL 1327

75
11.31 IC.INVOKFL 1327
11.32 ICINCONNHNDL[1..6] 1328
11.33 ICINCONNNAV[1..6] 1328
11.34 ICINCONNPRM[1..6] 1328
11.35 ICINCONNSTRVAL[1..6] 1329
11.36 ICINCONNVAL[1..6] 1329
11.37 ICMPINADDRMASKREPS 1330
11.38 ICMPINADDRMASKS 1330
11.39 ICMPINCSUMERRORS 1330
11.40 ICMPINDESTUNREACHS 1331
11.41 ICMPINECHOREPS 1331
11.42 ICMPINECHOS 1332
11.43 ICMPINERRORS 1332
11.44 ICMPINMSGS 1333
11.45 ICMPINPARAMPROBS 1333
11.46 ICMPINREDIRECTS 1333
11.47 ICMPINSRCQUENCHS 1334
11.48 ICMPINTIMEEXCDS 1334
11.49 ICMPINTIMESTAMPREPS 1335
11.50 ICMPINTIMESTAMPS 1335
11.51 ICMPOUTADDRMASKREPS 1335
11.52 ICMPOUTADDRMASKS 1336
11.53 ICMPOUTDESTUNREACHS 1336
11.54 ICMPOUTECHOREPS 1337
11.55 ICMPOUTECHOS 1337
11.56 ICMPOUTERRORS 1338
11.57 ICMPOUTMSGS 1338

76
11.58 ICMPOUTPARAMPROBS 1339
11.59 ICMPOUTREDIRECTS 1339
11.60 ICMPOUTSRCQUENCHS 1339
11.61 ICMPOUTTIMEEXCDS 1340
11.62 ICMPOUTTIMESTAMPREPS 1340
11.63 ICMPOUTTIMESTAMPS 1341
11.64 ICNUMSRCCONN 1341
11.65 IC.OPT 1341
11.66 ICONSTATE 1342
11.67 ICPCODESIZE 1347
11.68 ICPMBUFALLOC 1347
11.69 ICPMBUFALLOC[0..3] 1348
11.70 ICPMBUFINUSE 1348
11.71 ICPMBUFINUSE[0..3] 1349
11.72 ICPMBUFMAX[0..3] 1349
11.73 ICPMBUFMIN 1350
11.74 ICPMBUFMIN[0..3] 1350
11.75 ICPMBUFSIZE 1350
11.76 ICPMBUFSIZE[0..3] 1351
11.77 ICPNAKS[1..RPEERCONNMAX] 1351
11.78 ICPNAKSPERCONN 1352
11.79 ICPNOBUFSPERCONN 1352
11.80 ICPPENDLMTPERCONN 1353
11.81 ICPSBUFALLOC 1353
11.82 ICPSBUFALLOC[0..3] 1354
11.83 ICPSBUFINUSE[0..3] 1354
11.84 ICPSBUFMIN 1355

77
11.85 ICPSBUFMIN[0..3] 1355
11.86 ICPSBUFSIZE 1356
11.87 ICPSBUFSIZE[0..3] 1356
11.88 ICPSENDFAIL 1357
11.89 ICPSENDFAIL[1..RPEERCONNMAX] 1357
11.90 ICPSENDFAILPERCONN 1358
11.91 ICPSENDNOBUFS 1358
11.92 ICPSENDPENDLIMIT[1..RPEERCONNMAX] 1359
11.93 ICPSENDXMTTO[1..RPEERCONNMAX] 1359
11.94 ICPTIMEOUTPERCONN 1360
11.95 ICPSTATRESET 1360
11.96 ICSRC[1..6] 1361
11.97 ICYCCONNIMRS[1..IPEERCONNMAX] 1361
11.98 ICYCCONNLRQS[1..IPEERCONNMAX] 1362
11.99 ICYCCONNSRQS[1..IPEERCONNMAX] 1362
11.100 ICYCIMRAVAIL 1363
11.101 ICYCIMRMAX 1363
11.102 ICYCIMRUSED 1364
11.103 ICYCIMRUSEDCONN [0...29] 1364
11.104 ICYCLGREQAVAIL 1365
11.105 ICYCLGREQMAX 1365
11.106 ICYCLGREQUSED 1366
11.107 ICYCLGREQUSEDCONN [0...29] 1366
11.108 ICYCSMIOREQUSEDCONN 1366
11.109 ICYCSMREQAVAIL 1367
11.110 ICYCSMREQMAX 1367
11.111 ICYCSMREQUSED 1368

78
11.112 ICYCSMREQUSEDCONN [0...29] 1368
11.113 ID 1369
11.114 IDENTIFY 1369
11.115 IDLEMODE[0..7] 1370
11.116 IECDATATYPE 1370
11.117 IEDCONNECTIONSTATUS 1371
11.118 IEDNAME 1371
11.119 IEDOMAINNAME 1372
11.120 IEDSTATRESET 1372
11.121 IEDTAGNAME 1372
11.122 IECLINKINACTIVE 1373
11.123 IELDEVICENAME 1373
11.124 IFINDISCARDS 1374
11.125 IFINERRORS 1374
11.126 IFINNONUCASTPKTS 1375
11.127 IFINOCTETS 1375
11.128 IFINUCASTPKTS 1375
11.129 IFINUNKNOWNPROTOS 1376
11.130 IFOUTDISCARDS 1376
11.131 IFOUTERRORS 1377
11.132 IFOUTNONUCASTPKTS 1377
11.133 IFOUTOCTETS 1377
11.134 IFOUTQLEN 1378
11.135 IFOUTUCASTPKTS 1378
11.136 IFTRANS 1379
11.137 IGNORD 1379
11.138 IGNORDFL[1..6] 1379

79
11.139 IGNORHI 1380
11.140 IGNORLM 1380
11.141 IGNORLO 1381
11.142 IGNORTM 1381
11.143 IIMCOMMAND 1381
11.144 IIMLINKIOID 1382
11.145 IIMSTATE 1382
11.146 IIMTYPE 1383
11.147 IIOCS 1383
11.148 IIOPS 1384
11.149 IMAGEVER 1384
11.150 IMAGEVER_D 1385
11.151 IMPORTSTATUS # 1386
11.152 IMPORTSTS 1387
11.153 IMRAVGRESPTIMEDISPREAD 1387
11.154 IMRAVGSTDDISPREAD 1388
11.155 IMRAVGRESPTIMEP2PREAD 1388
11.156 IMRAVGRESPTIMEP2PWRITE 1389
11.157 IMRMAXRESPTIMEDISPREAD 1389
11.158 IMRMAXSTDDISPREAD 1390
11.159 IMRMAXRESPTIMEP2PREAD 1390
11.160 IMRMAXRESPTIMEP2PWRITE 1391
11.161 IMTYPE 1391
11.162 IN 1392
11.163 IN[*] 1393
11.164 IN[0..2] 1394
11.165 IN[0..12] 1395

80
11.166 IN[1] 1395
11.167 IN[1,2] 1396
11.168 IN[1..2] 1396
11.169 IN[1..3] 1397
11.170 IN[1..8] 1397
11.171 IN[1..20] 1398
11.172 IN.Boolean 1399
11.173 IN.ENUM 1399
11.174 IN.FLOAT32 1399
11.175 INFLOAT64 1400
11.176 IN.INT8 1400
11.177 INT8_VALUE 1401
11.178 IN.INT16 1401
11.179 INT16_VALUE 1402
11.180 ININT32 1402
11.181 INT32_VALUE 1403
11.182 IN.SDENUM 1403
11.183 IN.UINT8 1404
11.184 IN.UINT16 1404
11.185 IN.UINT32 1405
11.186 INACTINDETTM[1..8] 1405
11.187 INALM 1406
11.188 INALT 1408
11.189 INBADOPT 1408
11.190 INBADOPT 1409
11.191 INBETFL 1410
11.192 INCLAMPOPT 1410

81
11.193 INCLUDEINTEGRATORCLRI 1411
11.194 INCOMPLETE 1411
11.195 INDESC[*] 1412
11.196 INDPTOUTINIT 1412
11.197 INDRCTSYNC 1413
11.198 INDSYNCCMD 1414
11.199 INFLOAT64 1414
11.200 ININT32 1415
11.201 INITCOMPLETE 1415
11.202 INITCONNECTD[0..1] 1416
11.203 INITCONNECTD[1..3] 1416
11.204 INITCOUNTER 1416
11.205 INITMAN 1417
11.206 INITOPAFTLD 1418
11.207 INITOPOPT 1419
11.208 INITPENDING 1419
11.209 INITREQ 1420
11.210 INITREQ[0..2] 1422
11.211 INITREQ[1..8] 1423
11.212 INITREQLATCH 1423
11.213 INITREQSRC 1423
11.214 INITVAL 1424
11.215 INITVAL_AO_S 1425
11.216 INITVAL_DO_S 1425
11.217 INITVAL[0..numChans-1] 1425
11.218 INITVAL[1..8] 1426
11.219 INITVAL[1..NUMCHAN] 1426

82
11.220 INITVALSRC 1426
11.221 INPIN 1427
11.222 INPTDIR 1427
11.223 INPTDIR_AI_C 1429
11.224 INPTDIR_DI_C 1430
11.225 INPTDIR_DO_C 1431
11.226 INPTINVSTS[1..2] 1431
11.227 INPTINVSTS[1..8] 1431
11.228 INPTWIRETYP 1432
11.229 INPUTACTED[*] 1432
11.230 INPUTCHGDB 1433
11.231 INPUTERROR 1433
11.232 INPTDIR 1434
11.233 INPUTRANGE[0..numChans-1] 1434
11.234 INPUTRANGE[0..7] 1435
11.235 INPUTROC 1435
11.236 INPUTSTREAM 1436
11.237 INPUTTYPE 1436
11.238 INSBLOCK[1..10] 1437
11.239 INSERTINDEX 1437
11.240 INSERTSTS[1..10] 1437
11.241 INSFAILFL 1438
11.242 INSFAIL.PR 1438
11.243 INSFAIL.SV 1439
11.244 INSFAILALM.FL 1439
11.245 INSFAILALM.PR 1440
11.246 INSFAILALM.SV 1440

83
11.247 INSFAILFL 1441
11.248 INSMASTER 1441
11.249 INSRC[1..8] 1442
11.250 INTERLANCOMMFAILED 1442
11.251 INTGPD_SET 1442
11.252 INSTRUCTCNFM 1443
11.253 INSTRUCTCOMP 1443
11.254 INSTRUCTNOTIFOPT 1444
11.255 INSTRUCTPEND 1444
11.256 INSTRUCTSEQ 1445
11.257 INSTS[1..8] 1445
11.258 INSTSELECT 1446
11.259 INSTYPE[1..10] 1446
11.260 INT32PARAM 1447
11.261 INT32VAL[0..80] 1447
11.262 INT64PARAM 1447
11.263 INT64VAL[40] 1448
11.264 INTEGRITY1[1..4] 1448
11.265 INTEGRITY2[1..4] 1449
11.266 INTEGRITYPERIOD 1449
11.267 INTERLANFAILED 1450
11.268 INTERVALCOUNTER 1450
11.269 INTERVALS 1451
11.270 INTISWCMD 1452
11.271 INITVAL_AO_S 1452
11.272 INITVAL_DO_S 1452
11.273 INVCOND[1..8] 1453

84
11.274 INVFRMHNDLER[1..8] 1453
11.275 INVFRMHNDLRN[1..8] 1454
11.276 INVFRMHNDTYP[1..8] 1454
11.277 INVFROMSTEP[1..8][1..15] 1455
11.278 INVFROMSTEPN[1..8][1..15] 1455
11.279 INVPVFL 1456
11.280 INVOKE[1..8] 1456
11.281 INVOKT.HANDLE 1457
11.282 INVOKT.NEXTCOMP 1457
11.283 INVOLTTHRESH 1457
11.284 INVPWRGOOD1 1458
11.285 INVPWRGOOD2 1458
11.286 INVREASON[1..8] 1459
11.287 INVTHREAD[1..8] 1459
11.288 INVTIME[1..8] 1460
11.289 IOCBFMTAV 1460
11.290 IOLINKCOLOR 1461
11.291 IOCCONN 1461
11.292 IOCNUMBER 1462
11.293 IOCONNEXTSTS 1462
11.294 IOCONNSTATUS 1463
11.295 IOCSTATE 1465
11.296 IOCTYPE 1465
11.297 IOL1SOFTFAIL 1466
11.298 IOL2SOFTFAIL 1466
11.299 IOLCHNFAILA 1467
11.300 IOLCHNFAILB 1467

85
11.301 IOLCHNHISTA [1...10] 1468
11.302 IOLCHNHISTB[1...10] 1468
11.303 1.25 IOLCHNSTSA 1469
11.304 IOLCHNSTSB 1469
11.305 IOLDAUGHSF 1470
11.306 IOLFREE 1470
11.307 IOLIFNUM 1471
11.308 IOLINK1IOID 1471
11.309 IOLINK2IOID 1472
11.310 IOLIMSTATE 1472
11.311 IOLINK 1473
11.312 IOLINKCONN 1473
11.313 IOLINKTYPE 1474
11.314 IOLINKTYPEENUMMASK 1475
11.315 IOLMAXERR 1475
11.316 IOLOVRRUN 1476
11.317 IOLSOFTFAIL 1476
11.318 IOMASAPH 1477
11.319 IOMBTREV 1477
11.320 IOMBTREV(UOC) 1478
11.321 IOMBTREVA 1478
11.322 IOMBTREVB 1479
11.323 IOMCARDA 1479
11.324 IOMCARDB 1480
11.325 IOMCMD[1..40] 1480
11.326 IOMCOMMAND 1481
11.327 IOMCOMMAND[1..40] 1482

86
11.328 IOMCONN 1483
11.329 IOMDESCA 1483
11.330 IOMDESCB 1483
11.331 IOMEXECSTATE 1484
11.332 IOMFILEA 1485
11.333 IOMFILEB 1485
11.334 IOMFWREV 1486
11.335 IOMFWREVA 1486
11.336 IOMFWREVB 1487
11.337 IOMGRCLI 1487
11.338 IOMGRMAPFREE 1488
11.339 IOMGRMAPRUNNING 1488
11.340 IOMGRMEMFREE 1489
11.341 IOMGRMEMTOTAL 1489
11.342 IOMHWREV 1490
11.343 IOMHWREVA 1490
11.344 IOMHWREVB 1491
11.345 IOMLHFSTA 1492
11.346 IOMLHFSTB 1494
11.347 IOMLOCATION 1495
11.348 IOMNAME 1495
11.349 IOMNUM 1496
11.350 IOMOPERA 1497
11.351 IOMOPERB 1497
11.352 IOMPLREVA 1498
11.353 IOMPLREVB 1498
11.354 IOMSLOT 1498

87
11.355 IOMSLOTNUMBER 1499
11.356 IOMSTATE 1500
11.357 IOMSTS[1..40] 1502
11.358 IOMSTSA 1502
11.359 IOMSTSB 1503
11.360 IOMSTS(UOC) 1504
11.361 IOMTYPE 1504
11.362 IOMTYPE(UOC) 1506
11.363 IOMTYPE[1..40] 1507
11.364 IOMSTS 1514
11.365 IOMTYPE 1515
11.366 IOMFWREV(UOC) 1516
11.367 IOP 1517
11.368 IOPBLOCKNAME [1...40] 1517
11.369 IOPDESCA 1518
11.370 IOPDESCB 1518
11.371 IOPHARTLHFSTA 1519
11.372 IOPHARTLHFSTB 1520
11.373 IOPLOADSTATE 1520
11.374 IOPLOCATION 1521
11.375 IOPORCUR[1..40] 1521
11.376 IOPORPREV[1..40] 1522
11.377 IOPTYPE 1522
11.378 IORACKNUMBER 1523
11.379 IORACKNUM(UOC) 1524
11.380 IOREDOPT 1524
11.381 IOSCHEDOPT 1525

88
11.382 IOSSTALLTIME 1525
11.383 IOSTKNDROP 1526
11.384 IOTANETTYPE 1526
11.385 IOTATYPE 1527
11.386 IOTATOPOLOGY 1528
11.387 IPADDRESS 1528
11.388 IPEERAVGLPS [1...IPEERCONNMAX] 1530
11.389 IPEERAVGPPS [1...IPEERCONNMAX] 1531
11.390 IPEERCONN 1531
11.391 IPEERCONNERRCODE [1...N] 1532
11.392 IPEERCONNERRINFO [1...N] 1532
11.393 IPEERCONNMAX 1532
11.394 IPEERCONNSTS [1...N] 1533
11.395 IPEERMAXLPS [1...IPEERCONNMAX] 1533
11.396 IPEERMAXPPS [1...IPEERCONNMAX] 1534
11.397 IPEERNAME [1...IPEERCONNMAX] 1534
11.398 IPEERNAMELOOKUP 1535
11.399 IPEERPATH [1...IPEERCONNMAX] 1535
11.400 IPFRAGCREATES 1536
11.401 IPFRAGFAILS 1536
11.402 IPFRAGOKS 1537
11.403 IPINADDRERRORS 1537
11.404 IPINDELIVERS 1538
11.405 IPINDISCARDS 1538
11.406 IPINHDRERRORS 1539
11.407 IPINRECEIVES 1539
11.408 IPINUNKNOWNPORTS 1540

89
11.409 IPOUTDISCARDS 1540
11.410 IPOUTNOROUTES 1541
11.411 IPOUTREQUESTS 1541
11.412 IPREASSMFAILS 1542
11.413 IPREASSEMFAILS 1542
11.414 IPREASSEMOKS 1543
11.415 IPREASSEMREQS 1543
11.416 IPREASSEMTIMEOUT 1544
11.417 IPROUTINGDISCARDS 1544
11.418 ISBIGENDIAN 1545
11.419 ISROCKWELLIO 1545
11.420 ISSUEDATE 1546
11.421 ISVIRTUALPLATFORM 1546
11.422 ITEMCNT 1546
11.423 ITEMNAME 1547
11.424 ITEMS 1548
Chapter 12 - Jxxxx Parameters 1549
12.1 JAGBASIC1[1..4] 1549
12.2 JAGBASIC2[1..4] 1550
12.3 JOURNALONLY 1550
12.4 JUMPGROUP 1551
12.5 JUMPGROUPNAME 1551
12.6 JUMPGROUPNUM 1552
12.7 JUMPPATHNUM 1552
12.8 JUMPSAFEENB 1553
12.9 JUMPTARGETNUM 1554
12.10 JUMPZONE 1554

90
12.11 JUMPZONEENB 1555
12.12 JUMPZONENAME 1555
12.13 JUMPZONENUM 1556
Chapter 13 - Kxxxx Parameters 1557
13.1 K 1557
13.2 K[1..4] 1558
13.3 K[1..8] 1559
13.4 K1 1559
13.5 K2 1560
13.6 KEYWORD 1560
13.7 KFF 1561
13.8 KL 1561
13.9 KLIN 1561
13.10 KMODIFEXT 1562
13.11 KMODIFGAP 1562
13.12 KMODIFNL 1563
13.13 KR 1563
Chapter 14 - Lxxxx Parameters 1564
14.1 LAG1TIME 1569
14.2 LAG2TIME 1569
14.3 LAMPTEST 1570
14.4 LAMPOUT[1..32] 1570
14.5 LANABLOCKEDRATE 1570
14.6 LANABLOCKEDRATEMAX 1571
14.7 LANAFAILED 1571
14.8 LANAMACADDR 1572
14.9 LANARXRATE 1573

91
14.10 LANARXRATEMAX 1574
14.11 LANASILENT 1575
14.12 LANATXRATE 1575
14.13 LANATXRATEMAX 1576
14.14 LANBBLOCKEDRATE 1577
14.15 LANBBLOCKEDRATEMAX 1578
14.16 LANBFAILED 1578
14.17 LANBMACADDR 1579
14.18 LANBRXRATE 1580
14.19 LANBRXRATEMAX 1581
14.20 LANBSILENT 1582
14.21 LANBTXRATE 1582
14.22 LANBTXRATEMAX 1583
14.23 LANRXERR 1584
14.24 LANRXRATE 1585
14.25 LANRXRATEMAX 1585
14.26 LANTXERR 1586
14.27 LANTXRATE 1587
14.28 LANTXRATEMAX 1588
14.29 LASTCONNTIME[0..1] 1588
14.30 LASTDATA[1..32] 1589
14.31 LASTDISCONNTIME[0..1] 1589
14.32 LASTERRTIME[0..1] 1590
14.33 LASTERRTIME 1590
14.34 LASTEXECDURATIONDISP 1590
14.35 LASTEXTSTAT 1591
14.36 LASTGOOD 1591

92
14.37 LASTGOODPV 1592
14.38 LASTGOPREQ 1592
14.39 LASTIN[1..8] 1592
14.40 LASTINSTS[1..8] 1593
14.41 LASTIOLCMD 1593
14.42 LASTMBERR[0..15] 1595
14.43 LASTMBERRTIME[0..15] 1601
14.44 LASTMODELUPDATE 1601
14.45 LASTMODEREQ 1602
14.46 LASTOPMNAME 1602
14.47 LASTOPREQ 1603
14.48 LASTOPTYPE 1604
14.49 LASTPCUSED 1604
14.50 LASTPV 1605
14.51 LASTRATEREQ 1605
14.52 LASTREQFL 1605
14.53 LASTRESETTIME 1606
14.54 LASTSERIAL 1606
14.55 LASTSPREQ 1607
14.56 LASTSPTVREQ 1607
14.57 LASTSTAT 1607
14.58 LASTSTEP 1608
14.59 LASTSTORESTS 1609
14.60 LASTSTORESTSN 1609
14.61 LASTSYNCABRT 1609
14.62 LASTSYNCARES 1610
14.63 LASTTUNINGUPDATE 1610

93
14.64 LATCHENB 1611
14.65 LCDDISPLAYSF 1611
14.66 LCDDSPSTS 1612
14.67 LCNALONEA 1612
14.68 LCNALONEB 1613
14.69 LCNCBLSTSA 1613
14.70 LCNCBLSTSB 1614
14.71 LCNDMAUNDERERR 1614
14.72 LC BATTERYFAIL 1615
14.73 LCNMSGBUFPCT 1615
14.74 LCNMSGBUFPEAKPCT 1616
14.75 LCNRX1DECODEERR 1616
14.76 LCNRX1FCSERR 1617
14.77 LCNRX1FRAMEERR 1617
14.78 LCNRX1IOCPCHERR 1618
14.79 LCNRX1LCNIOVERERR 1618
14.80 LCNRX1OVERSZERR 1619
14.81 LCNRX1RATE 1619
14.82 LCNRX1RATEMAX 1620
14.83 LCNRX2DECODEERR 1620
14.84 LCNRX2FCSERR 1621
14.85 LCNRX2FRAMEERR 1621
14.86 LCNRX2IOCPCHERR 1622
14.87 LCNRX2LCNIOVERERR 1622
14.88 LCNRX2OVERSZERR 1623
14.89 LCNRX2RATE 1623
14.90 LCNRX2RATEMAX 1624

94
14.91 LCNTOELCNRATE 1624
14.92 LCNTOELCNRATEMAX 1625
14.93 LCNTXRATE 1625
14.94 LCNTXRATEMAX 1626
14.95 LCTIMESYNCFAIL 1626
14.96 LDTACYCIMRUSED 1626
14.97 LDTACYCLGREQUSED 1627
14.98 LDTACYCSMREQUSED 1627
14.99 LDTCYCIMRUSED 1628
14.100 LDTCYCLGREQUSED 1628
14.101 LDTCYCSMREQUSED 1628
14.102 LDTIMRAVAIL 1629
14.103 LDTIMRMAX 1629
14.104 LDTLGREQAVAIL 1630
14.105 LDTLGREQMAX 1630
14.106 LDTSMREQAVAIL 1630
14.107 LDTSMREQMAX 1631
14.108 LEADLAG 1631
14.109 LEADTIME 1632
14.110 LEADWIRERES 1632
14.111 LEGACYGAP 1633
14.112 LEGACYINITOPT 1633
14.113 LINEPERD 1634
14.114 LINEARTYPE 1634
14.115 LINKNUM 1635
14.116 LIVEDEVICEINDEX 1635
14.117 LNNAME 1636

95
14.118 LOADFL 1636
14.119 LOADID 1637
14.120 LOADSP 1637
14.121 LOADSPCONN 1638
14.122 LOADSPSTS 1638
14.123 LOADSTATE 1639
14.124 LOCALCLOSE 1640
14.125 LOCALMAN 1640
14.126 LOCALOPEN 1640
14.127 LOCALSTART 1641
14.128 LOCALSTOP 1641
14.129 LOCALSTOPACTED 1642
14.130 LOCALSWITCH 1642
14.131 LOCATION 1642
14.132 LOCUTOFF 1643
14.133 LOGICALENIM 1644
14.134 LOGICALENIMIPADDRESS 1644
14.135 LOGICALUCNNW 1644
14.136 LOGICINITOPT 1645
14.137 LOGICGATE1 1646
14.138 LOGICGATE2 1646
14.139 LOGICGATE3 1647
14.140 LOGICGATE4 1647
14.141 LOGIENIMDATEPTIMPORT 1648
14.142 LOGIENIMIMPORTSTATUS 1648
14.143 LOLMRAMPRATE 1649
14.144 LOOKAHEAD 1649

96
14.145 LOOPADDR 1650
14.146 LOOPCOUNT 1650
14.147 LOOPDATA 1651
14.148 LOOPDATACHG 1651
14.149 LOOPMODE 1652
14.150 LOOPRATE 1653
14.151 LOOPTYPE 1653
14.152 LOSTKNDROP 1654
14.153 LOWENG[0..numChans-1] 1655
14.154 LOWENG[0..7] 1655
14.155 LOWERDEADTM 1655
14.156 LOWERDESC 1656
14.157 LOWERLMFL 1656
14.158 LOWERRATE 1657
14.159 LOWERTIME 1657
14.160 LOWSIGNAL[0..numChans-1] 1657
14.161 LOWSIGNAL[0..7] 1658
14.162 LRL 1659
14.163 LRL HART 1659
14.164 LRR 1659
14.165 LRRACTED 1660
14.166 LRRALM.FL 1660
14.167 LRRALM.OPT 1661
14.168 LRRALM.PR 1661
14.169 LRRALM.SV 1661
14.170 LRV 1662
14.171 LRV HART 1662

97
14.172 LSCYCLEOVRN[0...40] 1663
14.173 LSCYCLESKIP[0..40] 1664
14.174 LSCYCLESKIP 1664
14.175 LSSKIPERIOD 1665
14.176 LSSKIPPERIOD[0..40] 1665
14.177 LSTHRERRFIFOENTRY 1666
14.178 LSTHRRCVFIFOENTRY 1666
14.179 LSTHRRPTFIFOENTRY 1666
14.180 LTC 1667
14.181 LTO 1667
Chapter 15 - Mxxxx Parameters 1668
15.1 MACADDRA 1677
15.2 MACADDRB 1678
15.3 MACADDRR 1678
15.4 MAINCLOSEFDBK 1678
15.5 MAINCLOSEFDBKSTS 1679
15.6 MAINTAINONFAULT 1679
15.7 MAINTOPT 1680
15.8 MAINVLVFDBKTO 1680
15.9 MAJ 1681
15.10 MAJORREV 1681
15.11 MAJRECFAULT 1682
15.12 MAJURECFAULT 1682
15.13 MANPULSECMD 1683
15.14 MANPULSETIME 1683
15.15 MANUALMODE[1..24] 1684
15.16 MANUALMODE[1..200] 1684

98
15.17 MANUFACTURER 1685
15.18 MASTERID 1685
15.19 MASTERSTATE 1686
15.20 MATERIALPATH[1..200] 1689
15.21 MATRIKON_OPC_ABPLUGIN 1689
15.22 MATRIKON_OPC_HOST 1690
15.23 MATRIKON_OPC_PLC 1690
15.24 MATRIKON_OPC_PROGID 1691
15.25 MAX 1691
15.26 MAX_D 1692
15.27 MAX_N_S 1692
15.28 MAX_N_SJL 1692
15.29 MAX_N_SS 1693
15.30 MAXACTPERIOD 1693
15.31 MAXBLKTYPES 1694
15.32 MAXBROWSEP 1694
15.33 MAXBROWSER 1695
15.34 MAXCABTYPES 1695
15.35 MAXCACHEVAR 1696
15.36 MAXCDDMTYPES 1696
15.37 MaxConfigSize 1697
15.38 MAXCYCLE 1697
15.39 MAXDEADTIME 1698
15.40 MAXDEPTH 1698
15.41 MAXDEVICEINDEX 1698
15.42 MAXFREEBLKSZ 1699
15.43 MAXFREEINK 1699

99
15.44 MAXFTENODES 1700
15.45 MAXGPSSKEW 1701
15.46 MAXHISOAKDEV[1..NUMPROFILES] 1701
15.47 MAXICPNAKS 1702
15.48 MAXICPSENDS 1702
15.49 MAXIMR 1703
15.50 MaxIntervalsInInit 1703
15.51 MAXLOSOAKDEV[1..NUMPROFILES] 1704
15.52 MAXMINRATIO 1704
15.53 MAXMONITOR 1705
15.54 MAXMONPERSUBSCR 1705
15.55 MAXMONPERSESS 1705
15.56 MAXNODEID 1706
15.57 MAXNOOFBLOCKS 1707
15.58 MAXNOOFFTENODES 1708
15.59 MAXNUMACT 1708
15.60 MAXOWNERS 1708
15.61 MAXPCOVERRUN 1709
15.62 MAXPENDREQ 1709
15.63 MAXPTPFASTSKEW 1710
15.64 MAXPTPSLOWSKEW 1710
15.65 MAXPUBLISH 1711
15.66 MAXPULSEL 1711
15.67 MAXPULSER 1712
15.68 MAXRCMSUSED 1712
15.69 MAXREQUEST 1712
15.70 MAXRESOURCES 1713

100
15.71 MAXRFBDEV 1713
15.72 MAXRAMPDEV[1..NUMPROFILES] 1714
15.73 MAXSESSION 1714
15.74 MAXSESSIONSPC 1714
15.75 MAXSESSIONTO 1715
15.76 MAXSNTPSKEW 1715
15.77 MAXSNODESBROWSE 1716
15.78 MAXSUBSCRC 1716
15.79 MAXSUBSCRLT 1716
15.80 MAXSUBSCRPERSESS 1717
15.81 MAXRCVBYTESPERSEC 1717
15.82 MAXRCVMSGPERSEC 1718
15.83 MAXRXPKTRATE 1718
15.84 MAXSOAKVAL[1..NUMPROFILES] 1718
15.85 MAXSTACK 1719
15.86 MAXTIME 1719
15.87 MAXTIME[0..2] 1720
15.88 MAXTIMEFL 1720
15.89 MAXTRANS[0..2] 1721
15.90 MAXUIDREQ 1721
15.91 MAXXMITBYTESPERSEC 1721
15.92 MAXXMITMSGPERSEC 1722
15.93 MBERRCNT[0..15] 1722
15.94 MBERRFL[0..15] 1723
15.95 MBTCPFREEBUFCOUNT 1723
15.96 MBTCPINVALIDRCVMSGCOUNT 1723
15.97 MEANINGPRI[0..15] 1724

101
15.98 MEANINGSEC[0..15] 1724
15.99 MEDIADEADA 1725
15.100 MEDIADEADB 1725
15.101 MEDIADEADAV 1726
15.102 MEDOPT 1726
15.103 MEM1CR 1726
15.104 MEMALLCR 1727
15.105 MEMFREEAVG 1727
15.106 MEMFREECRIT 1728
15.107 MEMFREECRITLM 1728
15.108 MEMFREELOWLM 1729
15.109 MEMFREEMIN 1729
15.110 MESSAGE[0..15] 1729
15.111 MIN 1730
15.112 MINALIVE 1730
15.113 MINHWREVSF 1731
15.114 MINLVLSECSIG[0..15] 1731
15.115 MINORREV 1732
15.116 MINPUBLISH 1732
15.117 MINPULSEL 1732
15.118 MINPULSER 1733
15.119 MINRECFAULT 1733
15.120 MINSOAKVAL[1..NUMPROFILES] 1734
15.121 MINSESSIONTO 1734
15.122 MINSUBSCRIPTION 1735
15.123 MINTIME 1735
15.124 MINURECFAULT 1735

102
15.125 MINUTE 1736
15.126 MMSRPS 1736
15.127 MMSSTORERPS 1737
15.128 MODCOMPATA 1737
15.129 MODDIF 1738
15.130 MODE 1738
15.131 MODE 1739
15.132 MODE 1740
15.133 MODE 1740
15.134 MODEAPPL[1..4] 1741
15.135 MODEATTR 1742
15.136 MODEATTR 1742
15.137 MODEATTR 1743
15.138 MODEATTR 1745
15.139 MODEATTR 1745
15.140 MODEATTRCHGFL 1746
15.141 MODEATTRFL.NORM 1747
15.142 MODEATTRFL.OPER 1747
15.143 MODEATTRFL.PROG 1748
15.144 MODEATTRREF 1749
15.145 MODECHANGE 1749
15.146 MODEFL.AUTO 1750
15.147 MODEEM 1750
15.148 MODEFL.BCAS 1751
15.149 MODEFL.CAS 1751
15.150 MODEFL.MAN 1752
15.151 MODEFL.NORM 1752

103
15.152 MODELINDEX 1753
15.153 MODELISVALID 1753
15.154 MODELNAME 1753
15.155 MODELNUM 1754
15.156 MODELPV 1755
15.157 MODELUPDATED 1755
15.158 MODELXM_BLOB 1756
15.159 MODELXM_BLOB_NUMBER_OF_BYTES 1756
15.160 MODELXM_BLOB_SIZE 1756
15.161 MODELXS_BLOB 1757
15.162 MODELXS_BLOB_NUMBER_OF_BYTES 1757
15.163 MODELXS_BLOB_SIZE 1758
15.164 MODEOUT 1758
15.165 MODEPERM 1759
15.166 MODEPERM 1759
15.167 MODE POLICING 1760
15.168 MODEREQ 1760
15.169 MODESEL.AUTO 1761
15.170 MODESEL.BCAS 1761
15.171 MODESEL.CAS 1762
15.172 MODESEL.MAN 1762
15.173 MODESEL.PROGRAM 1763
15.174 MODETRACK 1763
15.175 MODETRACK 1764
15.176 MODHASBKUP 1765
15.177 MODIFIEDBY 1766
15.178 MODISREDUN 1766

104
15.179 MODSTATE 1767
15.180 MODTYPE 1767
15.181 MODTYPEA 1769
15.182 MOMSTATE 1769
15.183 MONACTCMD 1770
15.184 MONCMDPARAM 1771
15.185 MONINACTCMD 1772
15.186 MONLDCMD 1773
15.187 MONREADLDUI 1773
15.188 MONREADPARAM 1773
15.189 MONRQDLD 1774
15.190 MONSTATES 1775
15.191 MONTASKREF 1775
15.192 MONTH 1776
15.193 MOTIONBIT[1..4] 1776
15.194 MOTORTRIPALM.FL 1777
15.195 MOTORTRIPALM.OPT 1777
15.196 MOTORTRIPALM.PR 1777
15.197 MOTORTRIPALM.SV 1778
15.198 MPCFREEMEM 1778
15.199 MPCFREEMEMINK 1779
15.200 MPCMAXFREEBLKSZ 1779
15.201 MPCMAXFREEINK 1780
15.202 MPCNTOTMEMDESC 1780
15.203 MPCNUMFREEBLKS 1781
15.204 MPCNUMFREEDESC 1781
15.205 MPCNUMREGDESC 1782

105
15.206 MPCNUMUSEDBLKS 1782
15.207 MPCNUMUSEDDESC 1783
15.208 MPCTOTALMEM 1783
15.209 MPCTOTALMEMINK 1784
15.210 MPCUSEDMEM 1784
15.211 MPCUSEDMEMINK 1785
15.212 MPVEM 1785
15.213 MSGBUFPEAKPCT 1786
15.214 MSGDATAFMT [0…15] 1786
15.215 MSGDATASRC [0…15] 1787
15.216 MSGDELAY 1787
15.217 MSGSEQNUMBER[1..200] 1788
15.218 MSGTYPE[0..15] 1788
15.219 MTR 1789
15.220 MTRSRC 1789
15.221 MTS 1789
15.222 MTT 1790
15.223 MTTACTED 1790
15.224 MULREDUNSTAT 1791
15.225 MULTIINPTDESC 1791
15.226 MUXSEL 1792
15.227 MV.ACHIEVABLEHL 1792
15.228 MV.ACHIEVABLELL 1792
15.229 MV.ACTHL 1793
15.230 MV.ACTIVEMAXMOVEDOWN 1793
15.231 MV.ACTIVEMAXMOVEUP 1794
15.232 MV.ACTIVEVAL 1794

106
15.233 MV.ACTLL 1794
15.234 MV.ADDITIONALANTIWINDUPMOVE 1795
15.235 MV.BIAS 1795
15.236 MV.CALCBLKINTERVALS 1796
15.237 MV.CALCRESOLUTION 1796
15.238 MV.CASSTATUS 1796
15.239 MV.CONSTRAINTTYPEENUM 1797
15.240 MV.CONTROLHORIZON 1797
15.241 MV.CONTROLMOVE 1798
15.242 MV.CRITICAL 1798
15.243 MV.CTLCVINDEX1 1798
15.244 MV.CTLCVINDEX2 1799
15.245 MV.CURRENTMOVE 1799
15.246 MV.CURRENTMOVEIFON 1800
15.247 MV.DELTAACTSOFTHL 1800
15.248 MV.DELTAACTSOFTLL 1800
15.249 MV.DELTASOFTHL 1801
15.250 MV.DELTASOFTLL 1801
15.251 MV.DESC 1802
15.252 MV.DESIREDVAL 1802
15.253 MV.ENGGHL 1802
15.254 MV.ENGGLL 1803
15.255 MV.ENGGUNITS 1803
15.256 MV.EXCITESIGNAL 1804
15.257 MV.EXECSTATUS 1804
15.258 MV.FUTUREVAL_C 1804
15.259 MV.FUTUREVALUE 1805

107
15.260 MV.HELDINJECTEDSIGNALVAL 1805
15.261 MV.HIGHLIMIT 1806
15.262 MV.HLRAMP 1806
15.263 MV.HLRAMPRATE 1806
15.264 MV.INITCOUNT 1807
15.265 MV.INITINTERVALS 1807
15.266 MV.INJECTEDSIGNAL 1808
15.267 MV.INTERACTIONMOVE 1808
15.268 MV.INTERNALWINDUPRATIO 1808
15.269 MV.ISCONTROLLABLE 1809
15.270 MV.ITRCVINDEX1 1809
15.271 MV.ITRCVINDEX2 1810
15.272 MV.LASTSTATUS 1810
15.273 MV.LINEARCOEFF 1810
15.274 MV.LINEARCOEFF_C 1811
15.275 MV.LLRAMP 1811
15.276 MV.LLRAMPRATE 1812
15.277 MV.LOWLIMIT 1812
15.278 MV.MANACTION 1812
15.279 MV.MAXMOVEDOWN 1813
15.280 MV.MAXMOVEUP 1813
15.281 MV.MOVE_CTLCVINDEX1 1814
15.282 MV.MOVE_CTLCVINDEX2 1814
15.283 MV.MOVE_ITRCVINDEX1 1814
15.284 MV.MOVE_ITRCVINDEX2 1815
15.285 MV.MVINDEX 1815
15.286 MV.MVINDEX_C 1816

108
15.287 MV.NAME 1816
15.288 MV.NOOFBLKS 1816
15.289 MV.OP_MAX_X 1817
15.290 MV.OP_MIN_X 1817
15.291 MV.OPHIGHTRANSITION 1818
15.292 MV.OPHIGHWINDUP 1818
15.293 MV.OPLOWTRANSITION 1818
15.294 MV.OPLOWWINDUP 1819
15.295 MV.OPPROCESSHL 1819
15.296 MV.OPPROCESSLL 1820
15.297 MV.OPPVFILTERCOEF 1820
15.298 MV.OPTCVINDEX 1820
15.299 MV.OPTIMIZATIONMOVE 1821
15.300 MV.OPTOPVGAIN 1821
15.301 MV.OPTPRIORITY 1822
15.302 MV.OPVAL 1822
15.303 MV.OPVALUE 1822
15.304 MV.PERCENT_CTLMOVE 1823
15.305 MV.PERCENT_ITRMOVE 1823
15.306 MV.PERCENT_OPTMOVE 1824
15.307 MV.PERCENTMOVE_CTLCVINDEX1 1824
15.308 MV.PERCENTMOVE_CTLCVINDEX2 1824
15.309 MV.PERCENTMOVE_ITRCVINDEX1 1825
15.310 MV.PERCENTMOVE_ITRCVINDEX2 1825
15.311 MV.PIDMODE 1826
15.312 MV.PREDICTEDPV 1826
15.313 MV.PREVIOUSVAL 1826

109
15.314 MV.PROCESSHL 1827
15.315 MV.PROCESSLL 1827
15.316 MV.PV_MAX_Y 1828
15.317 MV.PV_MIN_Y 1828
15.318 MV.PVNOISEGAP 1828
15.319 MV.PVTRACK 1829
15.320 MV.PVTRACKENUM 1829
15.321 MV.PVVAL 1830
15.322 MV.QUADRATICCOEFF 1830
15.323 MV.READPROCESSVAL 1830
15.324 MV.READVAL 1831
15.325 MV.RESOLUTION 1831
15.326 MV.RESOLUTIONMISMATCH 1832
15.327 MV.RESOLUTIONRESIDUAL 1832
15.328 MV.SCALINGFACTOR 1832
15.329 MV.SENTVALUE 1833
15.330 MV.SENTVALUEIFON 1833
15.331 MV.SHADOWPRICE 1834
15.332 MV.SSMOVEMAINCAUSE 1834
15.333 MV.SSMOVEMAINCV 1834
15.334 MV.SSVALUE 1835
15.335 MV.SSVALUE_C 1835
15.336 MV.STARTVALUE 1836
15.337 MV.STATUS 1836
15.338 MV.STATUSDISP_C 1836
15.339 MV.STATUSDISPLAY 1837
15.340 MV.STEPINPROGRESS 1837

110
15.341 MV.TOTALSSMOVE 1838
15.342 MV.TRACKPVWITHGAP 1838
15.343 MV.TYPICALMOVESIZE 1838
15.344 MV.U_SOLVE 1839
15.345 MV.USEACHLIM 1839
15.346 MV.USEPOLYMODEL 1840
15.347 MV.USETHISMV 1840
15.348 MV.USETHISMV_C 1840
15.349 MV.VALIDATIONFAILCOUNT 1841
15.350 MV.VALUE 1841
15.351 MV.VALUE_C 1842
15.352 MV.WEIGHT 1842
15.353 MV.WINDUPSTATUS 1842
15.354 MW 1843
15.355 MWSTS 1843
15.356 MXCOMMAND[1..200] 1844
15.357 MXFERSTATQ[1..200] 1845
15.358 MXFERSTATUS[1..200] 1845
15.359 MXGROUPNUM[1..200] 1846
15.360 MXMATPATH[1..200] 1846
15.361 MXNEGTOLER[1..200] 1847
15.362 MXOVRLAPNUM[1..200] 1847
15.363 MXPOSTOLER[1..200] 1848
15.364 MXTARGETWGT[1..200] 1848
15.365 MXTRANID[1..200] 1849
Chapter 16 - Nxxxx Parameters 1850
16.1 N 1857

111
16.2 N[1..5] 1858
16.3 N_EXIST_SPR 1858
16.4 NAME 1859
16.5 NAMEREF 1860
16.6 NAMURENBL_DI_C 1862
16.7 NAMURPVRAW 1862
16.8 NAMURPVRAW_DI_S 1863
16.9 NETBCDSW 1863
16.10 NETELAPSEDTM 1864
16.11 NETMODE[1..4] 1864
16.12 NETTIMEPASTTHISSEG 1865
16.13 NETWORKTYPE 1865
16.14 NETWRKTYP 1866
16.15 NEWSAMPLE 1866
16.16 NEXTCOMP 1867
16.17 NEXTCOMP[1..15] 1867
16.18 NEXTCOMP[1..15] 1868
16.19 NEXTHANDLE 1868
16.20 NEXTHANDLE[1..10] 1869
16.21 NEXTNUMBER 1869
16.22 NEXTPHASE 1870
16.23 NFLAG 1870
16.24 NLFORM 1871
16.25 NLGAIN 1871
16.26 NMIN 1872
16.27 NMODE 1872
16.28 NMODATTR 1873

112
16.29 NNUMERIC 1873
16.30 NOCACHE_PARAM_ID [0...3] 1874
16.31 NOCACHE_PARAM_NAME [0...3] 1875
16.32 NODELCNELCN 1875
16.33 NODENAME 1876
16.34 NODESTATESTR 1877
16.35 NOFIELDPWR 1877
16.36 NOFIELDPWR[0..numChans-1] 1878
16.37 NOLOAD 1878
16.38 NOLOAD[0..numChans-1] 1879
16.39 NONCRITICALMVLOSS 1879
16.40 NONFTEMARTADDRCOUNT 1879
16.41 NONFTEMARTAVGDEPTH 1880
16.42 NONFTEMARTCOLLCOUNT 1880
16.43 NONFTEMARTMAXDEPTH 1881
16.44 NONPUBLISHABLE 1881
16.45 NONREDFTABA 1882
16.46 NONREDFTABB 1882
16.47 NOOFFTENODES 1883
16.48 NOOFUPDATES 1883
16.49 NOPERDB # 1884
16.50 NOREQUESTPREAMBLES 1884
16.51 NORMAL 1884
16.52 NORMAL[1..24] 1885
16.53 NORMMODE 1885
16.54 NORMMODEATTR 1887
16.55 NOTACTSUPV 1887

113
16.56 NOTCHFILTER[0..numChans-1] 1888
16.57 NOTCHFILTER[0..7] 1888
16.58 NOTCHFILTER 1889
16.59 NOTE 1890
16.60 NOTIFINHIBIT 1890
16.61 NOTIFPUBLISH 1891
16.62 NOTRATEAVG 1891
16.63 NOTRATEMAX 1892
16.64 NOTREDCNFGA 1892
16.65 NOTREDCNFGB 1893
16.66 NOTSAMEFTAA 1893
16.67 NOTSAMEFTAB 1894
16.68 NOWAITINGFL 1894
16.69 NOWALARM 1895
16.70 NSTRING 1895
16.71 NTOTMEMDESC 1896
16.72 NTPADDRESS 1897
16.73 NTPDELAY 1897
16.74 NTPDELAYMAX 1897
16.75 NTPLASTSTRATUM 1898
16.76 NTPOFFSET 1898
16.77 NTPOFFSETMAX 1899
16.78 NTPSTAT 1899
16.79 NULLPVFL 1900
16.80 NUM 1900
16.81 NUMACCRQUAVG 1901
16.82 NUMACCRQUMAX 1902

114
16.83 NUMACEINCON 1902
16.84 NUMACEOUTCON 1903
16.85 NUMACT 1903
16.86 NUMACTCR 1904
16.87 NUMACTCRFAIL 1905
16.88 NUMACTIVEPOINTS 1905
16.89 NUMACTWRT 1905
16.90 NUMADJPARAMS 1906
16.91 NUMALIASES 1906
16.92 NUMALLTRANS 1907
16.93 NUMANNWIN 1907
16.94 NUMASSIGNFBS 1907
16.95 NUMBEROFCVS 1908
16.96 NUMBEROFDVS 1908
16.97 NUMBEROFEQP 1909
16.98 NUMBEROFMVS 1909
16.99 NUMBEVENTSAVG 1910
16.100 NUMBEVENTSMAX 1910
16.101 NUMBLKINST 1911
16.102 NUMBLKREF 1911
16.103 NUMBLKTYPES 1911
16.104 NUMBLOBS 1912
16.105 NUMBLOCK 1912
16.106 NUMBLOCKS 1913
16.107 NUMBLOCKUSED 1913
16.108 NUMBOOL 1914
16.109 NUMC3INCON 1914

115
16.110 NUMC3OUTCON 1915
16.111 NUMCABCOL (Custom cabinet) 1915
16.112 NUMCABROWS 1916
16.113 NUMCABTYPES 1916
16.114 NUMCACHE[1..40] 1917
16.115 NUMCACHEVAR 1917
16.116 NUMCCLRQU 1918
16.117 NUMCCLRQUAVG 1918
16.118 NUMCCLRQUMAX 1919
16.119 NUMCDDMTYPES 1919
16.120 NUMCHANS 1920
16.121 NUMCLIENTCONN 1921
16.122 NUMCLXPROC 1921
16.123 NUMCLXUDT 1922
16.124 NUMCMPCONTFB 1922
16.125 NUMCN100INCON 1923
16.126 NUMCN100OUTCON 1923
16.127 NUMCOEFDEN 1924
16.128 NUMCOEFNUM 1924
16.129 NUMCOMPFB 1925
16.130 NUMCONDS 1925
16.131 NUMCONN 1926
16.132 NUMCONN[0..1] 1926
16.133 NUMCONN[0..7] 1927
16.134 NUMCPMINCON 1927
16.135 NUMCPMOUTCON 1928
16.136 NUMCUSTOMRANGE 1929

116
16.137 NUMCVSEXCEEDLIM 1929
16.138 NUMCVSNEARINGLIM 1930
16.139 NUMCVSWITHINLIM 1930
16.140 NUMCYCLE 1930
16.141 NUMDATA 1931
16.142 NUMDINPUTS 1931
16.143 NUMDISCONN 1932
16.144 NUMDISCONN[0..1] 1933
16.145 NUMDISCONN[0..7] 1933
16.146 NUMDOUTS 1933
16.147 NUMUDTTAGREAD 1934
16.148 NUMEHPMINCON 1934
16.149 NUMEIPDEVICE 1935
16.150 NUMEIPDEVICE 1935
16.151 NUMERIC1 1936
16.152 NUMERIC2 1936
16.153 NUMEIMEIPIOS 1937
16.154 NUMEVENTS[1..NUMPROFILES] 1937
16.155 NUMEXCIMRAVAIL 1937
16.156 NUMEXCRSPAVAIL 1938
16.157 NUMEXCRQUAVAIL 1938
16.158 NUMEXCRQUAVG 1939
16.159 NUMEXCRQUMAX 1939
16.160 NUMEXCRSPAVG 1940
16.161 NUMEXCRSPMAX 1940
16.162 NUMEXTBLKS 1940
16.163 NUMFAILEDGETITEM 1941

117
16.164 NUMFIMINCON 1941
16.165 NUMFIMOUTCON 1942
16.166 NUMFLOAT64 1942
16.167 NUMFREEBLKS 1943
16.168 NUMFREEDESC 1943
16.169 NUMFTENODES 1944
16.170 NUMFUNREF 1944
16.171 NUMGPSSKEWEX 1945
16.172 NUMHANDLERS 1945
16.173 NUMHISTPARMS 1945
16.174 NUMIEDS 1946
16.175 NUMIMR 1946
16.176 NUMIN 1947
16.177 NUMINPUTS 1947
16.178 NUMINSERT 1947
16.179 NUMINSTANCES 1948
16.180 NUMINT32 1948
16.181 NUMINT64 1949
16.182 NUMINTERVALSININIT 1949
16.183 NUMIOLMINCON 1949
16.184 NUMIOLMOUTCON 1950
16.185 NUMIOM 1950
16.186 NUMIPADDR 1951
16.187 NUMLIOMINCON 1951
16.188 NUMLIOMOUTCON 1952
16.189 NUMLOC 1952
16.190 NUMMBTCPRCVBYTEAVG 1952

118
16.191 NUMMBTCPRCVBYTEMAX 1953
16.192 NUMMBTCPRCVMSGAVG 1953
16.193 NUMMBTCPRCVMSGMAX 1954
16.194 NUMMBTCPXMITBYTEAVG 1954
16.195 NUMMBTCPXMITBYTEMAX 1954
16.196 NUMMBTCPXMITMSGAVG 1955
16.197 NUMMBTCPXMITMSGMAX 1955
16.198 NUMMVSEXCEEDLIM 1956
16.199 NUMMVSNEARINGLIM 1956
16.200 NUMMVSWITHINLIM 1956
16.201 NUMNTFRQUAVG 1957
16.202 NUMNTFRQUMAX 1957
16.203 NUMOFCHNLSGANGED 1958
16.204 NUMOFEVENTRECVRS 1959
16.205 NUMOFINPUTS 1959
16.206 NUMOFSCANTABLEEVENTS 1960
16.207 NUMOUTPUTS 1960
16.208 NUMOWNERS 1960
16.209 NUMPARALLEL 1961
16.210 NUMPARAMS 1961
16.211 NUMPARAMS 1962
16.212 NUMPARRSPAVG 1962
16.213 NUMPARRSPMAX 1963
16.214 NUMPEERENV[ ] 1963
16.215 NUMPHASES 1964
16.216 NUMPINPT 1964
16.217 NUMPMDINCON 1965

119
16.218 NUMPMDOUTCON 1965
16.219 NUMPOINTSREADS 1966
16.220 NUMPOINTSWRITES 1966
16.221 NUMPRI 1967
16.222 NUMPRMREF 1967
16.223 NUMPRIORITYIOM 1968
16.224 NUMPROFILES 1968
16.225 NUMPTPSKEWEX 1968
16.226 NUMQCSINCON 1969
16.227 NUMQCSOUTCON 1969
16.228 NUMQUALITY 1970
16.229 NUMRAMPSOAK[1..NUMPROFILES] 1970
16.230 NUMRECPARMS 1971
16.231 NUMREGDESC 1971
16.232 NUMREQUESTR 1972
16.233 NUMRUNRCMS 1972
16.234 NUMSCADAINCON 1973
16.235 NUMSCATAGREAD 1973
16.236 NUMSCEINCON 1973
16.237 NUMSCEOUTCON 1974
16.238 NUMSCFIMINCON 1974
16.239 NUMSCFIMOUTCON 1975
16.240 NUMSEC 1975
16.241 NUMSEGS 1976
16.242 NUMSESSIONS 1976
16.243 NUMSHUTDOWN 1976
16.244 NUMSHUTDOWN[0..7] 1977

120
16.245 NUMSIGS 1977
16.246 NUMSIOLMINCN 1978
16.247 NUMSIOLMOUCN 1978
16.248 NUMSIOVRD 1979
16.249 NUMSLOTS 1979
16.250 NUMSMINCON 1980
16.251 NUMSMOUTCON 1980
16.252 NUMSNTPSKEWEX 1981
16.253 NUMSRCCONN[1..8] 1981
16.254 NUMSTATES 1982
16.255 NUMSTEPS 1982
16.256 NUMSYNCS 1983
16.257 NUMTBR 1983
16.258 NUMTHREADS 1984
16.259 NUMTRANS 1984
16.260 NUMTRANS [0,1] 1985
16.261 NUMTRANS[0..2] 1985
16.262 NUMUIDS 1986
16.263 NUMUINT32 1986
16.264 NUMUNITS 1986
16.265 NUMUOCINCON 1987
16.266 NUMUOCOUTCON 1987
16.267 NUMUSEDBLKS 1988
16.268 NUMUSEDDESC 1988
16.269 NUMWAITING 1988
16.270 NUMWSGINCON 1989
16.271 NUMWSGOUTCON 1990

121
16.272 NUMXFERINST 1990
16.273 NUMXINPT 1990
16.274 NVSCOMINPROG 1991
16.275 NVSFREEAVG 1991
16.276 NVSFREECRIT 1992
16.277 NVSFREECRITLM 1992
16.278 NVSFREELOWLM 1992
16.279 NVSFREEMIN 1993
16.280 NVSMEDIAERR 1993
16.281 NVSUSED 1994
Chapter 17 - Oxxxx Parameters 1995
17.1 OFFCAP[1..10] 2003
17.2 OFFNRMALM.FL 2003
17.3 OFFNRMALM.OPT 2004
17.4 OFFNRMALM.PR 2005
17.5 OFFNRMALM.SV 2006
17.6 OFFNRMALM.TM 2006
17.7 OFFNRMALM.TMO 2007
17.8 OFFNRMFL 2007
17.9 OFFPULSE 2008
17.10 OHMOFFSET 2008
17.11 OHMOFFSET[0..numChans-1] 2009
17.12 OI[0..2] 2009
17.13 OIACTED 2010
17.14 OIALM.FL[0..1] 2010
17.15 OIALM.FL[0..2] 2011
17.16 OIALM.OPT[0..1] 2011

122
17.17 OIALM.OPT[0..2] 2012
17.18 OIALM.PR[0..1] 2012
17.19 OIALM.PR[0..2] 2012
17.20 OIALM.SV[0..1] 2013
17.21 OIALM.SV[0..2] 2013
17.22 OIOCS 2014
17.23 OIOPS 2014
17.24 OKINCH1AV 2015
17.25 OKINCH2AV 2015
17.26 OKOUTAV 2016
17.27 OLDAV 2016
17.28 ONCAP[1..10] 2016
17.29 ONPROCESS 2017
17.30 ONPULSE 2017
17.31 OP 2018
17.32 OP 2021
17.33 OP[0..7] 2022
17.34 OP[0..numChans-1] 2022
17.35 OP[1..8] 2022
17.36 OP[1..NUMCHAN] 2023
17.37 OP[1..16]. INSTRUCTDISABLE 2023
17.38 OP[1..16].ACQSTATE 2024
17.39 OP[1..16].BYPREQ 2024
17.40 OP[1..16].CMDREQSTS 2025
17.41 OP[1..16].CONFIGASSOCPARAM 2025
17.42 OP[1..16].CONFIGCODE 2026
17.43 OP[1..16].CONFIGDESC 2026

123
17.44 OP[1..16].CONFIGSTS 2027
17.45 OP[1..16].CURRDESCREF 2027
17.46 OP[1..16].CURREUDESCREF 2028
17.47 OP[1..16].CURRVALREF 2028
17.48 OP[1..16].CURRVALTREND 2029
17.49 OP[1..16].DELAYTIME 2029
17.50 OP[1..16].DELAYTIMEREM 2030
17.51 OP[1..16].DESC 2030
17.52 OP[ ].DSTN 2031
17.53 OP[1..16].ENTRYDESCREF 2031
17.54 OP[1..16].ENTRYEUDESCREF 2031
17.55 OP[1..16].ENTRYLABEL 2032
17.56 OP[1..16].ENTRYMAXREF 2032
17.57 OP[1..16].ENTRYMINREF 2033
17.58 OP[1..16].ENTRYVALREF 2033
17.59 OP[1..16].EQUIPNAME 2034
17.60 OP[1..16].EXECCODE 2034
17.61 OP[1..16].EXECDESC 2035
17.62 OP[1..16].EXECSTS 2035
17.63 OP[1..16].EXPRPCODE 2036
17.64 OP[1..16].FILTERABLE 2036
17.65 OP[1..16].INSTRUCTCNFM 2036
17.66 OP[1..16].INSTRUCTCOMP 2037
17.67 OP[1..16].INSTRUCTION 2037
17.68 OP[1..16].INSTRUCTPEND 2038
17.69 OP[1..16].INSTRUCTTYPE 2038
17.70 OP[1..16].MONTASKREF 2039

124
17.71 OP[1..16].NOTE 2039
17.72 OP[1..16].OWNERSSTS 2040
17.73 OP[1..16].OWNFL 2040
17.74 OP[1..16].RELFL 2041
17.75 OP[1..16].REQFL 2041
17.76 OP[1..16].ROLE 2042
17.77 OP[1..16].SRCEXPR 2042
17.78 OP[1..16].STATE 2043
17.79 OP[1..16].TARGETCHANGE 2043
17.80 OP[1..16].TARGETDESCREF 2044
17.81 OP[1..16].TARGETEUDESCREF 2044
17.82 OP[1..16].TARGETLABEL 2045
17.83 OP[1..16].TARGETMAXREF 2045
17.84 OP[1..16].TARGETMINREF 2045
17.85 OP[1..16].TARGETVALREF 2046
17.86 OP[1..16].TYPE 2046
17.87 OP[1..16].WARNING 2048
17.88 OP_AO_S 2048
17.89 OP_DO_S 2049
17.90 OP2PVPOLYMODEL 2050
17.91 OPBIAS 2050
17.92 OPBIAS[1..8] 2051
17.93 OPBIAS.FIX 2051
17.94 OPBIAS[1..8].FIX 2052
17.95 OPBIAS.FLOAT 2052
17.96 OPBIAS[1..8].FLOAT 2053
17.97 OPBIAS.RATE 2053

125
17.98 OPBIAS[1..8].RATE 2054
17.99 OPCHAR 2054
17.100 OPCMD[0..2] 2055
17.101 OPCNAME 2056
17.102 OPCTYPE 2056
17.103 OPCUASRVCONFIG 2056
17.104 OPDOMAP[0..3][1..3] 2057
17.105 OPENFEEDBKTIME 2057
17.106 OPEM 2058
17.107 OPENIBV 2058
17.108 OPENLOOPRESP 2059
17.109 OPENMAIN 2059
17.110 OPENPULSEWIDTH 2060
17.111 OPENSEQ 2060
17.112 OPENSEQALM.FL 2060
17.113 OPENSEQALM.PR 2061
17.114 OPENSEQALM.SV 2061
17.115 OPENWIRE [0..Number of status in assembly] 2062
17.116 OPERTAG 2062
17.117 OPERTAGDESC 2063
17.118 OPEU 2063
17.119 OPEU 2064
17.120 OPEU[1..8] 2064
17.121 OPEUMOVE 2065
17.122 OPEUX 2065
17.123 OPEUX[1..8] 2066
17.124 OPEXHIFL 2066

126
17.125 OPEXHIFL[1..8] 2067
17.126 OPEXHILM 2067
17.127 OPEXLOFL 2068
17.128 OPEXLOFL[1..8] 2068
17.129 OPEXLOLM 2069
17.130 OPFINAL 2069
17.131 OPFINAL_AO_S 2071
17.132 OPFINAL[0..numChans-1] 2072
17.133 OPFINAL[0..numChans-1] 2072
17.134 OPFINALHIRANGE [0..numChans-1] 2073
17.135 OPFINALLORANGE [0..numChans-1] 2073
17.136 OPFL[0..numChans-1] 2074
17.137 OPHIACTIVE 2074
17.138 OPHIALM.DB 2075
17.139 OPHIALM.DBU 2075
17.140 OPHIALM.FL 2076
17.141 OPHIALM.PR 2076
17.142 OPHIALM.SV 2077
17.143 OPHIALM.TM 2077
17.144 OPHIALM.TMO 2078
17.145 OPHIALM.TP 2078
17.146 OPHIFL 2079
17.147 OPHIFL[1..8] 2079
17.148 OPHIGH.FL 2080
17.149 OPHILM 2080
17.150 OPHILMOPT 2081
17.151 OPHIOPTOFFSET 2081

127
17.152 OPIN 2082
17.153 OPIN0 2082
17.154 OPIN1 2083
17.155 OPIN2 2083
17.156 OPIN3 2084
17.157 OPIN4 2084
17.158 OPIN5 2085
17.159 OPINCONNHNDL[1..16][1..6] 2085
17.160 OPINCONNNAV[1..16][1..6] 2085
17.161 OPINCONNPRM[1..16][1..6] 2086
17.162 OPINCONNSTRVAL[1..16][1..6] 2086
17.163 OPINCONNVAL[1..16][1..6] 2087
17.164 OPINITVAL 2087
17.165 OPINITVAL[0..numChans-1] 2088
17.166 OPLOACTIVE 2088
17.167 OPLOALM.DB 2089
17.168 OPLOALM.DBU 2089
17.169 OPLOALM.FL 2090
17.170 OPLOALM.PR 2090
17.171 OPLOALM.SV 2091
17.172 OPLOALM.TM 2091
17.173 OPLOALM.TMO 2092
17.174 OPLOALM.TP 2092
17.175 OPLOFL 2093
17.176 OPLOFL[1..8] 2093
17.177 OPLOLM 2094
17.178 OPLOLMOPT 2094

128
17.179 OPLOOPTOFFSET 2095
17.180 OPLOW.FL 2095
17.181 OPMINCHG 2096
17.182 OPNUMSRCCONN[1..16] 2096
17.183 OPOUT0 2097
17.184 OPOUT1 2097
17.185 OPOUT2 2098
17.186 OPOUT3 2098
17.187 OPOUT4 2099
17.188 OPOUT5 2099
17.189 OPOUT 2100
17.190 OPPCODESIZE[1..16] 2100
17.191 OPREQ 2101
17.192 OPROCLM 2102
17.193 OPROCNEGFL 2102
17.194 OPROCNEGFL[1..8] 2103
17.195 OPROCPOSFL 2103
17.196 OPROCPOSFL[1..8] 2104
17.197 OPSECDATA 2104
17.198 OPSECDATA[1..8] 2105
17.199 OPSECDATA.ARWSTS 2105
17.200 OPSECDATA.EUHI 2105
17.201 OPSECDATA.EULO 2106
17.202 OPSECDATA.INITREQ 2106
17.203 OPSECDATA.INITVAL 2107
17.204 OPSECDATA.ONESHOT 2107
17.205 OPSECDATA.ORFBVA 2108

129
17.206 OPSECDATA.OROFFS 2108
17.207 OPSOURCE 2108
17.208 OPSRC[1..16][1..6] 2109
17.209 OPSTOREHNDL[1..16] 2109
17.210 OPSTORENAV[1..16] 2110
17.211 OPSTOREPRM[1..16] 2110
17.212 OPSTORESTRVAL[1..16] 2110
17.213 OPSTOREVAL[1..16] 2111
17.214 OPTACCELTOL 2111
17.215 OPTDIR 2112
17.216 INPTDIR_AO_C 2113
17.217 OPTFIELDS 2114
17.218 OPTFLD_SET 2115
17.219 OPTMODE 2116
17.220 OPTOAOCONN 2116
17.221 OPTOL 2117
17.222 OTRPI 2117
17.223 OPTSPEED 2118
17.224 OPTSPEEDFACTOR 2119
17.225 OPTYPE 2119
17.226 OPTYPEENUMMASK 2120
17.227 OPX 2120
17.228 OPX[1..8] 2121
17.229 ORBYPASSFL[1..4] 2121
17.230 ORBYPPERM 2121
17.231 ORDER 2122
17.232 ORDERINCEE 2122

130
17.233 ORDERINCM 2123
17.234 ORDERINLINK 2124
17.235 ORED 2125
17.236 OREDOUT 2125
17.237 ORFBSTSSRC 2125
17.238 ORFBVALSRC 2126
17.239 ORIAPPCONNID[1..48] 2126
17.240 ORICONNSTATE[1..48] 2127
17.241 ORIGINALGAIN 2127
17.242 ORIPATH[1..48] 2127
17.243 ORITCLASS[1..48] 2128
17.244 ORMUXED[1..48] 2128
17.245 OROFFSET 2129
17.246 OROPT 2129
17.247 ORPHANRESPCNT 2130
17.248 OSVER 2130
17.249 OTCONNPRIORITY 2131
17.250 OTCONNTYPE 2131
17.251 OTDENBL 2132
17.252 OTRPI 2132
17.253 OUT 2133
17.254 OUT[0..12] 2135
17.255 OUT[1..8] 2135
17.256 OUT.Boolean 2135
17.257 OUT.ENUM 2136
17.258 OUT.FLOAT32 2136
17.259 OUTFLOAT64 2137

131
17.260 OUT.INT8 2137
17.261 OUT.INT16 2137
17.262 OUTINT32 2138
17.263 OUT.SDENUM 2138
17.264 OUT.UINT 8 2139
17.265 OUT.UINT16 2139
17.266 OUT.UINT32 2139
17.267 OUT1 2140
17.268 OUT2 2140
17.269 OUTCAP 2141
17.270 OUTDIR 2141
17.271 OUTFLOAT64 2141
17.272 OUTHORN1 2142
17.273 OUTHORN2 2142
17.274 OUTIND 2143
17.275 OUTINT32 2143
17.276 OUTPIN 2144
17.277 OUTPUTTYPE 2144
17.278 OUTSENSE 2145
17.279 OUTSENSE[6..7] 2145
17.280 OUTTYPE 2146
17.281 OUTSTS[1..8] 2146
17.282 OVERALLRESPONSETIME 2147
17.283 OVERCAPACITY[1..24] 2147
17.284 OVERCAPACITY[1..200] 2147
17.285 OVRDSEL 2148
17.286 OVRDSEL2 2148

132
17.287 OVERRANGE 2149
17.288 OVERRANGE[0..numChans-1] 2149
17.289 OVERRANGE [0..NUMCHANNELS-1] 2150
17.290 OVERRUNSCUR 2150
17.291 OVERRUNSPREV 2151
17.292 OVERTEMP 2151
17.293 OVERTEMPTHLD 2152
17.294 OVERTOLRNCE[1..200] 2152
17.295 OVERUNDERVOLTAGE 2153
17.296 OVRRUNCURHR[1..40] 2153
17.297 OVRRUNPREVHR[1..40] 2154
17.298 OVRSIGNA 2154
17.299 OWDENBL 2155
17.300 OWDENBL [0..NUMCHANNELS - 1] 2156
17.301 OWDENBL_AI_C 2157
17.302 OWDENBL_DI_C 2157
17.303 OWDENBL_DO_C 2158
17.304 OWNCMNDSTS[1..5] 2158
17.305 OWNCMPPHASESTS[1..5] 2159
17.306 OWNCOMMAND[1..5] 2160
17.307 OWNERID[1..MAXOWNERS] 2161
17.308 OWNERIDN[1..5] 2161
17.309 OWNERIDN[1..MAXOWNERS] 2162
17.310 OWNERLOOKUP 2162
17.311 OWNERS 2163
17.312 OWNINGENIM 2163
17.313 OWNMODE[1..5] 2164

133
17.314 OWNMODEATTR[1..5] 2164
17.315 OWNSTATE[1..5] 2165
Chapter 18 - Pxxxx Parameters 2167
18.1 P 2178
18.2 P[1..6] 2179
18.3 P[1..10] 2179
18.4 P0 2179
18.5 P1 2180
18.6 P1CLAMPOPT 2181
18.7 P1EU 2182
18.8 P1FILTINIT 2182
18.9 P1FILTTIME 2182
18.10 P1STS 2183
18.11 P2 2183
18.12 P2PEfficiency 2184
18.13 P2PSCANPERIOD 2184
18.14 P2STS 2184
18.15 PARAMETERREFERENCENAME.DESC 2185
18.16 PARAMETERREFENCENAME.PREF 2185
18.17 PARAMETERREFENCENAME.TYPE 2186
18.18 PARAMINIT 2186
18.19 PARAMNAME[0..500] 2187
18.20 PARENTASSET 2187
18.21
PARTNERINCOMPATIBLEA/PARTNERINCOMPATIBLEB 2188
18.22 PARTMISMATCH 2189
18.23 PARTNOTVIS 2190

134
18.24 PATH 2190
18.25 PATHBRKSTS 2191
18.26 PAUSEFL 2192
18.27 PCENGINEVER 2193
18.28 PCMCOMMAND 2193
18.29 PCMSTATE 2193
18.30 PCMNUMPRI 2194
18.31 PCMNUMSEC 2195
18.32 PCODESIZE[1..8] 2195
18.33 PCONN[1..10] 2195
18.34 PCOVERRUN 2196
18.35 PDELAYDIRCHG 2196
18.36 PDESC[1..10] 2197
18.37 PDFIFORATEA 2197
18.38 PDFIFORATEM 2198
18.39 PDTEIMIP 2198
18.40 PDTCONNSTS 2199
18.41 PDTEIMCONNSTS 2199
18.42 PDTEIMAVGRXPKTS 2199
18.43 PDTEIMMAXRXPKTS 2200
18.44 PDTTGTIPADDR 2200
18.45 PEAKFTEABLOCKRATE 2201
18.46 PEAKFTEBBLOCKRATE 2201
18.47 PEAKFTEARXRATE 2202
18.48 PEAKFTEBRXRATE 2202
18.49 PEAKFTEATXRATE 2203
18.50 PEAKFTEBTXRATE 2203

135
18.51 PEERAGETIME 2204
18.52 PEERALGOPT 2204
18.53 PEERALIASENB 2206
18.54 PEERALIASNUM 2207
18.55 PEERENV[ ] 2207
18.56 PEERGETAVG [1..30] 2208
18.57 PEERINPUTENB 2208
18.58 PEERINPUTNUM 2209
18.59 PEERRATEAVG 2209
18.60 PEERRATEMAX 2209
18.61 PEERREADOPT 2210
18.62 PEERSTRAVG [1..30] 2211
18.63 PEERSTRRESP [ ] 2211
18.64 PEERSUBSCPER [ ] 2212
18.65 PENABLE[1..10] 2212
18.66 PERFRATIOBACKOFFTOL 2212
18.67 PERIOD 2213
18.68 PERIODENUMMASK 2215
18.69 PERIODSEC 2215
18.70 PERSONALITYDAY 2216
18.71 PERSONALITYMONTH 2216
18.72 PERSONALITYNAME 2217
18.73 PERSONALITYREV 2217
18.74 PERSONALITYVER 2218
18.75 PERSONALITYYEAR 2218
18.76 PERSWAPENB 2218
18.77 PERSWAPTHRES 2219

136
18.78 PFANTICTIME 2219
18.79 PFREQ 2220
18.80 PFREQAVG 2221
18.81 PFREQMAX 2221
18.82 PHASE 2221
18.83 PHASEHOUR 2222
18.84 PHASEMIN 2223
18.85 PHASENAME[0..500] 2223
18.86 PHWYPRTLC 2224
18.87 PHWYPRTLCIP 2224
18.88 PHWYPRTLCIPISRED 2225
18.89 PHWYPRTRMIP1 2225
18.90 PHWYPRTRMIP2 2226
18.91 PHYCHNERRA1 [1...15] through PHYCHNERRA8
[1...15] 2226
18.92 PHYCHNERRB1 [1...15] through PHYCHNERRB8
[1...15] 2227
18.93 PHYCHNMNA1 [1...15] through PHYCHNMNA8
[1...15] 2227
18.94 PHYCHNMNB1 [1...15] through PHYCHNMNB8
[1...15] 2228
18.95 PHYCHNPLA1 [1...15] through PHYCHNPLA8
[1...15] 2228
18.96 PHYCHNPLB1 [1...15] through PHYCHNPLB8
[1...15] 2229
18.97 PHYCHNMNASC1 [1...20] through
PHYCHNMNASC4 [1...20] 2229
18.98 PHYCHNMNBSC1 [1...20] through
PHYCHNMNBSC4 [1...20] 2230

137
18.99 PHYCHNPLASC1 [1...20] through PHYCHNPLASC4
[1...20] 2230
18.100 PHYCHNPLBSC1 [1...20] through
PHYCHNPLBSC4 [1...20] 2231
18.101 PHYCHNSILA1 [1...15] through PHYCHNSILA8
[1...15] 2231
18.102 PHYCHNSILB1 [1...15] through PHYCHNSILB8
[1...15] 2232
18.103 PHYCOMMERR1 [1...15] through PHYCOMMERR8
[1...15] 2233
18.104 PHYLHFSTA [1..8] 2234
18.105 PHYRCVCHN1 [1...15] through PHYRCVCHN8
[1...15] 2235
18.106 PHYSDSA1 [1...15] through PHYSDSA8 [1...15] 2235
18.107 PHYSIOPSTS1 [1...15] through PHYSIOPSTS8
[1...15] 2236
18.108 PHYSMODTYPE1 [1...15] through
PHYSMODTYPE8 [1...15] 2237
18.109 PI[0..2] 2237
18.110 PID 2238
18.111 PIDSTATUS 2238
18.112 PIUCARDOP(1..32) 2238
18.113 PIUOTDCF 2239
18.114 PIUSMOTH 2239
18.115 PL 2240
18.116 PL[0..5] 2241
18.117 PLSTS 2241
18.118 PLVERSION 2242
18.119 PNETCONFIGCHNG 2243
18.120 PNETCONFIGPATH 2244

138
18.121 PNTALGOTYPE[ ] 2244
18.122 PNTFORM 2244
18.123 PNTTYPE 2245
18.124 PO 2246
18.125 PO[1..3] 2247
18.126 POCLOSE 2247
18.127 POCLOSECONNECTED 2248
18.128 POCONNECTED[1..3] 2248
18.129 PODIR 2249
18.130 POLOWER 2249
18.131 POLLTIME 2250
18.132 POOPEN 2250
18.133 POOPENCONNECTED 2250
18.134 POPERIOD 2251
18.135 PORAISE 2251
18.136 PORT 2252
18.137 PORUN 2252
18.138 PORUNCONNECTED 2253
18.139 POSTOP 2253
18.140 POSTOPCONNECTED 2254
18.141 POSTTRANSEXECSTS 2254
18.142 POWERCONNOPT 2255
18.143 POWERFAIL[1..200] 2256
18.144 PP[1..10] 2256
18.145 PPREDUNLINKFAIL 2257
18.146 PRBIAS 2257
18.147 PREDPVHIALM.FL 2258

139
18.148 PREDPVHIALM.PR 2258
18.149 PREDPVHIALM.SV 2259
18.150 PREDPVHIALM.TP 2259
18.151 PREDPVHIALM.TM 2260
18.152 PREDPVHIALM.TMO 2260
18.153 PREDPVLOALM.FL 2261
18.154 PREDPVLOALM.PR 2261
18.155 PREDPVLOALM.SV 2262
18.156 PREDPVLOALM.TM 2262
18.157 PREDPVLOALM.TMO 2263
18.158 PREDPVLOALM.TP 2263
18.159 PREFERREDCONN 2264
18.160 PREFSP 2264
18.161 PREFSPCLEAR 2265
18.162 PREFSPSET 2265
18.163 PRENGUNIT 2266
18.164 PRESSURE 2266
18.165 PRESSUREENGUNIT 2267
18.166 PRESSUREIO 2268
18.167 PREVALARM 2268
18.168 PREVISION 2268
18.169 PREVLOADSTAT 2269
18.170 PREVTRANSEXECSTS 2269
18.171 PRFRATIO 2270
18.172 PRIBLOCKNAME[1...40] 2270
18.173 PRICANTTALKTOSECONUCN 2271
18.174 PRICHNERRA [1...40] 2271

140
18.175 PRICHNERRB [1...40] 2272
18.176 PRICHNMNA [1...40] 2272
18.177 PRICHNMNB [1...40] 2273
18.178 PRICHNPLA [1...40] 2273
18.179 PRICHNPLB [1...40] 2274
18.180 PRICHNSILA [1...40] 2274
18.181 PRICHNSILB [1...40] 2275
18.182 PRICOMMERR [1...40] 2276
18.183 PRIIFCARD 2277
18.184 PRIIFCHNERRA 2277
18.185 PRIIFCHNERRB 2278
18.186 PRIIFCHNMNA 2278
18.187 PRIIFCHNMNB 2279
18.188 PRIIFCHNPLA 2279
18.189 PRIIFCHNPLB 2280
18.190 PRIIFCHNSILA 2280
18.191 PRIIFCHNSILB 2281
18.192 PRIIFCOMMERR 2282
18.193 PRIIFFILE 2283
18.194 PRIIFRCVCHN 2283
18.195 PRIIFSTS 2284
18.196 PRIM.[1..8].INITIALIZABLE 2284
18.197 PRIMARYACE 2285
18.198 PRIMARYSIG 2285
18.199 PRIMCONNSTS 2286
18.200 PRIMDATA.[1..8].ARWSTS 2286
18.201 PRIMDATA.[1..8]. EUHI 2287

141
18.202 PRIMDATA.[1..8]. EULO 2287
18.203 PRIMDATA.[1..8].HISELECT 2288
18.204 PRIMDATA.[1..8].INITSTS 2288
18.205 PRIMDATA.[1..8].INITVAL 2289
18.206 PRIMDATA.[1..8].LOCALMAN 2289
18.207 PRIMDATA.[1..8].ORFBSTS 2290
18.208 PRIMDATA.[1..8].ORFBVAL 2290
18.209 PRIMDATA.[1..8].OROFFSET 2291
18.210 PRIMDATA.[1..8].PROPOVRD 2291
18.211 PRIMERRCNT 2292
18.212 PRIMERRCODE 2292
18.213 PRIMERRFL 2293
18.214 PRIMERRINFO 2293
18.215 PRIMIP 2294
18.216 PRIMIPMON 2294
18.217 PRIMLASTCONNTIME 2294
18.218 PRIMLASTDISCONNTIME 2295
18.219 PRIMLASTERRTIME 2295
18.220 PRIMLOOPDATA 2296
18.221 PRIMNUMCONN 2296
18.222 PRIMNUMCONNATMPT 2297
18.223 PRIMNUMDISCONN 2297
18.224 PRIMOVERLAP[1..24] 2297
18.225 PRIMOVERLAP[1..200] 2298
18.226 PRIMTCP 2298
18.227 PRIMTCPMON 2299
18.228 PRIORITYIOM 2299

142
18.229 PRIRCVCHN [1..40] 2300
18.230 PRISECKEYSWMISMATCH 2301
18.231 PROCDEADTIME 2301
18.232 PROCDEADTIMEACT 2302
18.233 PROCDEADTIMEBIAS 2302
18.234 PROCEDURALLEVEL 2303
18.235 PROCESS_ID 2304
18.236 PROCESSED 2304
18.237 PROCGAIN 2305
18.238 PROCGAINACT 2305
18.239 PROCGAINEU 2306
18.240 PROCGAINMULT 2306
18.241 PROCGAINPCT 2307
18.242 PROCGAINUNITS 2308
18.243 PRODCODE 2308
18.244 PRODCODEA 2309
18.245 PRODTYPE 2309
18.246 PRODTYPEA 2310
18.247 PROFILEDESC[1..NUMPROFILES] 2310
18.248 PROFILEID 2311
18.249 PROFINETENABLE 2311
18.250 PROFRESET 2312
18.251 PROGCMD 2312
18.252 PROGCMDRECOG 2313
18.253 PROGID[0..40] 2313
18.254 PROGLCKTOIDLE 2314
18.255 PROGLCKTORUN 2314

143
18.256 PROGLOCKED 2314
18.257 PROGPACKET[0..2] 2315
18.258 PROGSTSDESC 2315
18.259 PROTOSTSTYPE 2316
18.260 PRPVHIGH.FL 2316
18.261 PrPVHigh.OffDelayTimeSec 2317
18.262 PrPVHigh.OnDelayTimeSec 2317
18.263 PrPVHigh.Priority 2317
18.264 PrPVHigh.Severity 2318
18.265 PrPVHigh.TripPoint 2318
18.266 PRPVLOW.FL 2319
18.267 PrPVLow.OffDelayTimeSec 2319
18.268 PrPVLow.OnDelayTimeSec 2320
18.269 PrPVLow.Priority 2320
18.270 PrPVLow.Severity 2320
18.271 PrPVLow.TripPoint 2321
18.272 PRSLOPE 2321
18.273 PSTS 2322
18.274 PSTS[1..6] 2322
18.275 PSTS[1..10] 2323
18.276 PSUB[1..10] 2323
18.277 PTEXECST 2324
18.278 PTEXECST[1..NUMCHAN] 2324
18.279 PTNRFLTIP 2325
18.280 PTPDELAY 2325
18.281 PTPDELAYMAX 2326
18.282 PTPENABLE 2326

144
18.283 PTPMASTERIP 2327
18.284 PTPNUMNODELAYRESP 2327
18.285 PTPNUMNOFOLLOWUP 2327
18.286 PTPNUMNOSYNC 2328
18.287 PTPOFFSET 2328
18.288 PTPOFFSETMAX 2329
18.289 PTPROCESSOROVERRUN 2329
18.290 PTPSKEWTHLD 2329
18.291 PTPSTAT 2330
18.292 PUBLICNAME 2331
18.293 PUBMETHOD 2332
18.294 PULSECMD 2332
18.295 PULSECMDTEXT[0..2] 2333
18.296 PULSEINTYPE 2333
18.297 PULSEMODE 2334
18.298 PULSEMODE[0..5] 2335
18.299 PULSETIME 2336
18.300 PULSEWIDTH 2336
18.301 PULSEWIDTH[1..3] 2337
18.302 PURGEDBCMD 2337
18.303 PURGEBUF 2338
18.304 PUSHSP 2339
18.305 PV 2339
18.306 PV[0..numChans-1] 2346
18.307 PV[0..7] 2346
18.308 PV[0..63] 2347
18.309 PV[0..120] 2347

145
18.310 PV[1..64] 2348
18.311 PV[1..200] 2348
18.312 PV[1..NUMCHAN] 2349
18.313 PV_AI_S 2349
18.314 PVASYNCOPT 2350
18.315 PVAUTO 2351
18.316 PVAUTOFL 2352
18.317 PVAUTOSTS 2353
18.318 PVBIAS 2353
18.319 PVCALC 2354
18.320 PVCHAR 2354
18.321 PVCHGDLY 2366
18.322 PVCLAMP 2367
18.323 PVCONN 2368
18.324 PVEM 2368
18.325 PVENGUNIT 2369
18.326 PVEQN 2369
18.327 PVERSION 2370
18.328 PVEUHI 2370
18.329 PVEUHI[0..120] 2372
18.330 PVEUHI_AI_C 2372
18.331 PVEULO 2373
18.332 PVEULO[0..120] 2374
18.333 PVEULO_AI_C 2375
18.334 PVEXEUHI 2375
18.335 PVEXEUHI_AI_C 2376
18.336 PVEXEULO 2377

146
18.337 PVEXEULO_AI_C 2378
18.338 PVEXHIFL 2379
18.339 PVEXHILM 2380
18.340 PVEXLOFL 2380
18.341 PVEXLOLM 2381
18.342 PVFL 2381
18.343 PVFL[0..numChans-1] 2382
18.344 PVFL[0..2] 2382
18.345 PVFL[0..511] 2383
18.346 PVFL[1..512] 2384
18.347 PVFL[1..1000] 2384
18.348 PVFL[1..1968] 2385
18.349 PVFL_DI_S 2385
18.350 PVFORMAT 2386
18.351 PVHHALM.DB 2387
18.352 PVHHALM.DBU 2387
18.353 PVHHALM.FL 2388
18.354 PVHHALM.PR 2388
18.355 PVHHALM.SV 2389
18.356 PVHHALM.TM 2389
18.357 PVHHALM.TMO 2390
18.358 PVHHALM.TP 2390
18.359 PVHIALM.DB 2391
18.360 PVHIALM.DBU 2391
18.361 PVHIALM.FL 2392
18.362 PVHIALM.PR 2392
18.363 PVHIALM.SV 2393

147
18.364 PVHIALM.TM 2393
18.365 PVHIALM.TMO 2394
18.366 PVHIALM.TP 2394
18.367 PVHILM 2395
18.368 PVHISIGCHG.CT 2395
18.369 PVHISIGCHG.TP 2396
18.370 PVHISIGNAL [0..NUMCHANNELS-1] 2396
18.371 PVLLALM.DB 2398
18.372 PVLLALM.DBU 2399
18.373 PVLLALM.FL 2399
18.374 PVLLALM.PR 2400
18.375 PVLLALM.SV 2400
18.376 PVLLALM.TM 2401
18.377 PVLLALM.TMO 2401
18.378 PVLLALM.TP 2402
18.379 PVLOALM.DB 2402
18.380 PVLOALM.DBU 2403
18.381 PVLOALM.FL 2403
18.382 PVLOALM.PR 2404
18.383 PVLOALM.SV 2404
18.384 PVLOALM.TM 2405
18.385 PVLOALM.TMO 2405
18.386 PVLOALM.TP 2406
18.387 PVLOLM 2406
18.388 PVLOSIGCHG.CT 2407
18.389 PVLOSIGCHG.TP 2407
18.390 PVLOSIGNAL [0..NUMCHANNELS-1] 2408

148
18.391 PVMANOPT 2409
18.392 PVNORMAL 2410
18.393 PVP 2411
18.394 PVRATE 2412
18.395 PVRAW 2412
18.396 PVRAW_AI_S 2414
18.397 PVRAW[0..numChans-1] 2414
18.398 PVRAW[0..120] 2415
18.399 PVRAW[0..numChans-1] 2415
18.400 PVRAWHI 2416
18.401 PVRAWHI[0..numChans-1] 2416
18.402 PVRAWHI[0..120] 2417
18.403 PVRAWLO 2417
18.404 PVRAWLO[0..numChans-1] 2418
18.405 PVRAWLO[0..120] 2418
18.406 PVRAWREF 2419
18.407 PVROCBYPASSFL 2419
18.408 PVROCNEGFL 2420
18.409 PVROCNEGLM 2420
18.410 PVROCPOSFL 2420
18.411 PVROCPOSLM 2421
18.412 PVSCALEFACTOR [0..NUMCHANNELS-1] 2421
18.413 PVSOURCE 2422
18.414 PVSRC 2424
18.415 PVSRCOPT 2424
18.416 PVSTS 2427
18.417 PVSTS[1..NUMCHAN] 2430

149
18.418 PVSTS[0..63] 2430
18.419 PVSTS[0..120] 2431
18.420 PVSTS[0..1968] 2431
18.421 PVSTS[0..numChans-1] 2432
18.422 PVSTS[0..numChans-1] 2432
18.423 PVSTS[1..64] 2433
18.424 PVSTSFL.ALL 2433
18.425 PVSTSFL.BAD 2434
18.426 PVSTSFL.MAN 2434
18.427 PVSTSFL.NORM 2435
18.428 PVSTSFL.UNCERTN 2436
18.429 PVSTS_AI_S 2437
18.430 PVSTSSRC 2438
18.431 PVTEMP 2438
18.432 PVTRAKOPT 2439
18.433 PVTRAKOPTAI 2440
18.434 PVVAL 2440
18.435 PVVAL[0..numChans-1] 2441
18.436 PVVALSTS 2441
18.437 PVVALSTS[0..63] 2443
18.438 PVVALSTS[1..64] 2443
18.439 PVVALSTS[0..511] 2444
18.440 PWMPERIOD 2444
18.441 PWMPERIOD[0..numChans-1] 2445
18.442 PWRGOOD1 2445
18.443 PWRGOOD2 2446
18.444 PWRSUPPLYSF 2446

150
18.445 PX[1..10] 2446
Chapter 19 - Qxxxx Parameters 2448
19.1 Q 2448
19.2 QDFL 2449
19.3 QUFL 2449
19.4 QIMPACTMAC 2450
19.5 QUALITYPARAM 2450
19.6 QUALITYVAL[0…80] 2451
19.7 QUALITYVALBIT[0…80][0…32] 2451
19.8 QUALPROGA 2451
19.9 QUALSTATE 2452
19.10 QUEUEDREQCNT[0..15] 2452
19.11 QUEUEFULLFL 2453
19.12 QUEUEID[1..n] 2453
19.13 QUEUEIDN[1..n] 2454
19.14 QUEUELOOKUP 2454
19.15 QUEUESIZE 2454
19.16 QSTS 2455
Chapter 20 - Rxxxx Parameters 2456
20.1 RACK_NUMBER 2465
20.2 R 2466
20.3 RACK_TYPE 2467
20.4 RACYCIMRAVAIL 2468
20.5 RACYCIMRAVAILDISP 2468
20.6 RACYCIMRAVAILPEER 2469
20.7 RACYCIMRMAX 2469
20.8 RACYCIMRUSED 2470

151
20.9 RACYCIMRUSEDDISP 2470
20.10 RACYCIMRUSEDPEER 2471
20.11 RACYCLGREQAVAIL 2471
20.12 RACYCLRQAVAILDISP 2472
20.13 RACYCLRQAVAILPEER 2472
20.14 RACYCLGREQMAX 2473
20.15 RACYCLGREQUSED 2473
20.16 RACYCLRQUSED 2474
20.17 RACYCLRQUSEDDISP 2474
20.18 RACYCLRQUSEDPEER 2475
20.19 RACYCSMREQAVAIL 2475
20.20 RACYCSRQAVAILDISP 2476
20.21 RACYCSRQAVAILPEER 2476
20.22 RACYCSMREQMAX 2477
20.23 RACYCSMREQUSED 2477
20.24 RACYCSMRQUSED 2478
20.25 RACYCSRQUSEDDISP 2478
20.26 RACYCSRQUSEDPEER 2479
20.27 RAISEDEADTM 2479
20.28 RAISEDESC 2479
20.29 RAISELMFL 2480
20.30 RAISERATE 2480
20.31 RAISETIME 2481
20.32 RAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK] 2481
20.33 RAMPSOAK 2482
20.34 RAMSCRUBERRS 2482
20.35 RAMSWEEPERR 2484

152
20.36 RANGE[0..numChans-1] 2485
20.37 RATE 2486
20.38 RATEALARM[1..24] 2486
20.39 RATEALARM[1..200] 2487
20.40 RATE[1..24] 2487
20.41 RATE[1..200] 2488
20.42 RATIOBIAS 2488
20.43 RATIOCTL 2489
20.44 RATIOEM 2489
20.45 RBOPTION 2489
20.46 RBROCLM 2490
20.47 RCCONFREV 2491
20.48 RCDATASET 2491
20.49 RCDESC 2492
20.50 RCINSTNUM 2492
20.51 RCMAXINSTNUM 2492
20.52 RCMCOMPLETED 2493
20.53 RCNAME 2493
20.54 RCNAMEREF 2494
20.55 RCRPTID 2494
20.56 RCRPTTYPE 2494
20.57 RCVCNTA 2495
20.58 RCVCNTB 2495
20.59 RCVERRA 2496
20.60 RCVERRB 2496
20.61 RCVNONRDRFRAMECOUNT 2497
20.62 RCVRDRREQUESTCOUNT 2497

153
20.63 RCVRDRRESPONSECOUNT 2498
20.64 RCYCIMRAVAIL 2498
20.65 RCYCIMRAVAILDISP 2499
20.66 RCYCIMRAVAILPEER 2499
20.67 RCYCIMRMAX 2500
20.68 RCYCIMRUSED 2500
20.69 RCYCIMRUSEDDISP 2501
20.70 RCYCIMRUSEDPEER 2501
20.71 RCYCLGREQAVAIL 2502
20.72 RCYCLGREQMAX 2502
20.73 RCYCLGRQUSED 2502
20.74 RCYCLGREQUSEDCONN 2503
20.75 RCYCLRQAVAILDISP 2503
20.76 RCYCLRQAVAILPEER 2504
20.77 RCYCLRQUSED 2504
20.78 RCYCLRQUSEDDISP 2505
20.79 RCYCLRQUSEDPEER 2505
20.80 RCYCSMIOREQUSEDCONN 2506
20.81 RCYCSMREQAVAIL 2506
20.82 RCYCSMREQMAX 2506
20.83 RCYCSMRQUSED 2507
20.84 RCYCSMREQUSEDCONN 2507
20.85 RCYCSRQAVAILDISP 2508
20.86 RCYCSRQAVAILPEER 2508
20.87 RCYCSRQUSEDDISP 2509
20.88 RCYCSRQUSEDPEER 2509
20.89 RDEGRADALM 2510

154
20.90 RDERRALM.PR 2510
20.91 RDERRALM.SV 2511
20.92 RDISPAVGLPS [1...RDISPCONNMAX] 2511
20.93 RDISPAVGLPSCONN [1...RDISPCONNMAX] 2512
20.94 RDISPAVGPPS [1...RDISPCONNMAX] 2512
20.95 RDISPAVGPPSCONN [1...RDISPCONNMAX] 2513
20.96 RDISPCONN 2513
20.97 RDISPCONNMAX 2514
20.98 RDISPDEGIMRCONN [1...RDISPCONNMAX] 2514
20.99 RDISPDEGRADIMR [1...RPEERCONNMAX] 2515
20.100 RDISPMAXLPS [1...RDISPCONNMAX] 2515
20.101 RDISPMAXLPSCONN [1...RDISPCONNMAX] 2516
20.102 RDISPMAXPPS [1...RDISPCONNMAX] 2516
20.103 RDISPMAXPPSCONN [1...RDISPCONNMAX] 2517
20.104 RDISPHOST [1...RPEERCONNMAX] 2517
20.105 RDNAUTOSYNC 2517
20.106 RDNCAPABILITY 2518
20.107 RDNCHASSISID 2519
20.108 RDNCMPT 2520
20.109 RDNCNTCYCMAX 2522
20.110 RDNCNTCYCMAX[0…40] 2522
20.111 RDNCNTCYCTP 2523
20.112 RDNCOMMFAILFTE 2524
20.113 RDNCOMMFAILRDN 2524
20.114 RDNCTLABILITY 2524
20.115 RDNDELAYAVG 2525
20.116 RDNDELAYMAX 2526

155
20.117 RDNDEVICEIDX 2527
20.118 RDNHISTREASON [1...15] 2528
20.119 RDNHISTSTATE [1...15] 2568
20.120 RDNHISTTIME[1...15] 2578
20.121 RDNHISTREASON 2579
20.122 RDNHISTSTATE 2579
20.123 RDNINHIBITSYNC 2579
20.124 RDNISTIMEMAX 2585
20.125 RDNLINKACTIVE 2586
20.126 RDNLINKFAILED 2586
20.127 RDNLOS 2588
20.128 RDNMACADDR 2595
20.129 RDNNONTRKMAX 2596
20.130 RDNOPMFRZTIME 2597
20.131 RDNOPMSTATUS 2599
20.132 RDNPKTRCVAVG 2604
20.133 RDNPKTRCVMAX 2605
20.134 RDNPKTXMITAVG 2605
20.135 RDNPKTXMITMAX 2606
20.136 RDNROLESTATE 2606
20.137 RDNRCVAVG 2608
20.138 RDNRCVMAX 2608
20.139 RDNRXRATE 2609
20.140 RDNRXRATEMAX 2609
20.141 RDNSOTIMEMAX 2609
20.142 RDNSYNCPROG 2610
20.143 RDNSYNCSTATE 2611

156
20.144 RDNTXRATE 2613
20.145 RDNTXRATEMAX 2613
20.146 RDNXFERAVG 2613
20.147 RDNXFERMAX 2614
20.148 RDNXMITAVG 2615
20.149 RDNXMITMAX 2615
20.150 RDRRETRYCOUNT 2616
20.151 RDYFL 2616
20.152 READERROPT 2617
20.153 READERRORS 2617
20.154 READERRORSMAX 2617
20.155 READINESS 2618
20.156 READINESSA 2618
20.157 READPPS 2618
20.158 READPPSMAX 2619
20.159 READSPECFLAG 2619
20.160 READSTATUS 2619
20.161 READSTATUS 2620
20.162 REASONSET 2620
20.163 RECPDESC[1..50] 2621
20.164 RECLIMITOPT 2622
20.165 RECMATCODE[1..50] 2622
20.166 RECOVMSGIDX 2623
20.167 RECSCALE[1..50] 2623
20.168 RDNHISTTIME 2624
20.169 RECTARGET[1..50] 2624
20.170 RECTARGETMAX[1..50] 2625

157
20.171 RECTARGETMIN[1..50] 2625
20.172 RECTOEQMENB 2625
20.173 RECTOEQMMAP 2626
20.174 RECVCLOSEREQ 2626
20.175 RECVCLOSERSP 2627
20.176 RECVNAKS 2627
20.177 RECVOPENREQ 2628
20.178 RECVOPENRSP 2628
20.179 REDDATAA 2629
20.180 REDDATAB 2630
20.181 REDSWITCHPERIOD 2631
20.182 REDTAG 2631
20.183 REDUNDANCY_WARNING 2633
20.184 REDUNDANT 2633
20.185 REDUNSTATE 2634
20.186 REDUNSTATEA 2634
20.187 REEXECOPT 2635
20.188 REEXECOPTOG 2636
20.189 REEXECOPTOH 2637
20.190 REEXECOPTOS 2639
20.191 REEXECPOLICY 2640
20.192 REFCOUNT 2640
20.193 REFRESHMS 2641
20.194 REJFACTOR 2641
20.195 REF 2642
20.196 REFTYPE 2642
20.197 REGCALC 2643

158
20.198 REGCTLOFFMODE 2643
20.199 REGCTLOFFMODEATTR 2644
20.200 REGCTLONMODE 2644
20.201 REGCTLONMODEATTR 2644
20.202 RegCtlStrategy 2645
20.203 REGCTLTARGETPARAM 2645
20.204 REGHASENAME 2646
20.205 REGREGISTERED 2646
20.206 REGTARGETBLK 2646
20.207 REGTARGETOPTMASK 2647
20.208 RELAYPRESENT 2647
20.209 RELOADINIDLY 2648
20.210 RELEASEOPT 2648
20.211 REMCAS 2649
20.212 REMCASTYPE 2649
20.213 REMOTESWITCH 2650
20.214 REMSOAKTIME 2650
20.215 REQ.ACQSTATE[1..100] 2651
20.216 REQ.CMDREQ.OUT[1..100] 2651
20.217 REQ.CMDREQSTS[1..100] 2652
20.218 REQ.EQUIPNAME[1..100] 2652
20.219 REQ.OUTDEST[1..100] 2652
20.220 REQ.OWNERSSRC[1..100] 2653
20.221 REQ.OWNERSSTS[1..100] 2653
20.222 REQ.OWNFL[1..100] 2654
20.223 REQ.REQFL[1..100] 2654
20.224 REQ.RELFL[1..100] 2654

159
20.225 REQEXECID[1..15] 2655
20.226 REQORDER 2655
20.227 REQRSPRCVD 2656
20.228 REQRTRY 2656
20.229 REQRTRYCNT[0..15] 2656
20.230 REQSTATE 2657
20.231 REQUSTEDSCANTIME 2658
20.232 RESADDR[1..15] 2658
20.233 RESAVEPERIOD 2659
20.234 RESADDRFUTUR[1..15] 2659
20.235 RESADDRFUTRN[1..15] 2660
20.236 RESADDRN[1..15] 2660
20.237 RESET 2661
20.238 RESETDEVDROPOFF 2663
20.239 RESETEIMNAME 2663
20.240 RESETERRORSCMD 2663
20.241 RESETFIRSTUP 2664
20.242 RESETFL 2664
20.243 RESETFL[0..7] 2667
20.244 RESETHCOMERR 2667
20.245 RESETMODE[0..numChans-1] 2668
20.246 RESETMODEL 2668
20.247 RESETSTAT 2669
20.248 RESETTIMER 2670
20.249 RESETVAL 2670
20.250 RESPTIMEAVG 2671
20.251 RESPTIMEMAX 2671

160
20.252 RESPTIMEMIN 2671
20.253 RESTART 2672
20.254 RESTARTFL 2673
20.255 RESTARTOPT 2674
20.256 RETAINISTS 2674
20.257 RETENDATAATTND 2675
20.258 RETENSAVEENABLED 2676
20.259 RETENSAVETIME 2676
20.260 RETENTIONSAVEFREEZE 2677
20.261 RETENVETOREASON 2677
20.262 RETRANSMISSIONSZ 2680
20.263 RETRYOPT 2680
20.264 RETRYSCURR 2681
20.265 RETRYSTOTAL 2681
20.266 RFB 2682
20.267 RG 2682
20.268 RHPWEIGHTS 2682
20.269 RJRAW 2683
20.270 RJTEMP 2683
20.271 RLSRESABNORM 2684
20.272 RLSRESNORM 2684
20.273 RMW 2685
20.274 ROCLM 2685
20.275 ROCLMOPT 2686
20.276 ROCNEGALM.FL 2686
20.277 ROCNEGALM.PR 2687
20.278 ROCNEGALM.SV 2687

161
20.279 ROCNEGALM.TM 2688
20.280 ROCNEGALM.TMO 2688
20.281 ROCNEGALM.TP 2689
20.282 ROCPOSALM.FL 2689
20.283 ROCPOSALM.PR 2690
20.284 ROCPOSALM.SV 2690
20.285 ROCPOSALM.TM 2691
20.286 ROCPOSALM.TMO 2691
20.287 ROCPOSALM.TP 2692
20.288 ROCSAFELM 2692
20.289 ROLE 2692
20.290 ROLLAVGBAD 2693
20.291 ROLLAVGOK 2693
20.292 ROLLAVGRST 2694
20.293 ROLLAVGSZ 2694
20.294 ROLLBFBASE 2695
20.295 ROLLBUF 2695
20.296 ROLLFRBASE 2696
20.297 ROLLFREQ 2697
20.298 ROLLMULTIPLE 2697
20.299 ROMAPPIMGCHKSMFAIL 2698
20.300 ROMBOOTIMGCHKSMFAIL 2698
20.301 RP 2699
20.302 RPEERAVGLPS [1...RPEERCONNMAX] 2699
20.303 RPEERAVGLPSCONN [1...RPEERCONNMAX] 2700
20.304 RPEERAVGPPS [1...RPEERCONNMAX] 2700
20.305 RPEERAVGPPSCONN [1...RPEERCONNMAX] 2701

162
20.306 RPEERCONN 2701
20.307 RPEERCONNMAX 2702
20.308 RPEERDEGIMRCONN [1...RPEERCONNMAX] 2702
20.309 RPEERDEGRADIMR[1..RPEERCONNMAX] 2703
20.310 RPEERMAXLPS [1..RPEERCONNMAX] 2703
20.311 RPEERMAXLPSCONN [1...RPEERCONNMAX] 2704
20.312 RPEERMAXPPS [1...RPEERCONNMAX] 2704
20.313 RPEERMAXPPSCONN [1...RPEERCONNMAX] 2705
20.314 RPEERNAME[1...RPEERCONNMAX] 2705
20.315 RPEERNAMELOOKUP 2706
20.316 RPEERSUBPER[1...RPEERCONNMAX] 2706
20.317 RPHYCONNID 2707
20.318 RPTCONNECTIONSTATE 2707
20.319 RPTENABLEFAILURE 2707
20.320 RQ 2708
20.321 RRRCEESTATE 2708
20.322 RSPPIN 2709
20.323 RSTERRCNT 2709
20.324 RSTPROCESSED 2710
20.325 RSTRTINIDLY 2710
20.326 RSTSTATS 2711
20.327 RT 2712
20.328 RTABLE.DIAG[1..5000] 2712
20.329 RTABLE.PART[1..5000] 2713
20.330 RTABLE.PARTN[1..5000] 2713
20.331 RTABLE.PEER[1..5000] 2714
20.332 RTABLE.STATE[1..5000] 2714

163
20.333 RTABLE.STATE[1..5000] 2715
20.334 RTABLENROWS 2715
20.335 RTABLEUROWS 2715
20.336 RTABLEIDX 2716
20.337 RTBACKCALOUT 2716
20.338 RTCONN 2717
20.339 RTDTYPE 2717
20.340 RTHIFL 2718
20.341 RTHILM 2719
20.342 RTLOFL 2719
20.343 RTLOLM 2719
20.344 RTOTACYCIMR 2720
20.345 RTOTACYCLGREQ 2720
20.346 RTOTACYCSMREQ 2721
20.347 RTOTCYCIMR 2721
20.348 RTOTCYCLGREQ 2722
20.349 RTOTCYCSMREQ 2722
20.350 RTPPRESENT 2722
20.351 RUNBKACTALM.FL 2723
20.352 RUNBKACTALM.PR 2723
20.353 RUNBKACTALM.SV 2724
20.354 RUNBKACTFL 2724
20.355 RUNPULSEWIDTH 2724
20.356 RUNTIME 2725
20.357 RV 2725
20.358 RX 2726
Chapter 21 - Sxxxx Parameters 2727

164
21.1 S 2738
21.2 S1 2739
21.3 SAFEOP 2740
21.4 SAFEOPALM.FL 2741
21.5 SAFEOPALM.PR 2741
21.6 SAFEOPALM.SV 2742
21.7 SAFEOPCMD 2742
21.8 SAFEOPTRIGFL 2742
21.9 SAFEOUTPUT 2743
21.10 SAFEOUTPUT[6..7] 2744
21.11 SAFEREDTAG 2744
21.12 SAFESTATE[0..numChans-1] 2745
21.13 SAFINTER.FL 2745
21.14 SAMPLERATE 2746
21.15 SAMPLESKEW 2746
21.16 SAVEDELAY1 2747
21.17 SAVEDELAY2 2747
21.18 SCAADVCODE1 2748
21.19 SCAADVCODE2 2749
21.20 SCACOMCOUNT 2750
21.21 SCACOMSTS 2751
21.22 SCADEVID 2751
21.23 SCADEVMFG 2752
21.24 SCADEVREV 2753
21.25 SCADEVTYPE 2753
21.26 SCADEVTYPENAME 2754
21.27 SCAHWREV 2754

165
21.28 SCALASTCOMCODE 2755
21.29 SCAREQCODE 2756
21.30 SCARESPCODE 2757
21.31 SCASWREV 2757
21.32 SC.BYPPERM 2758
21.33 SC.BYPREQ 2758
21.34 SC.CONFIGCODE 2758
21.35 SC.CONFIGDESC 2759
21.36 SC.CONFIGSTS 2759
21.37 SC.DESC 2760
21.38 SC.EXECCODE 2760
21.39 SC.EXECDESC 2761
21.40 SC.EXECSTS 2761
21.41 SC.EXPR 2761
21.42 SC.EXPRPCODE 2762
21.43 SC.FL 2762
21.44 SC.INVOKFL 2763
21.45 SC.OPT 2763
21.46 SCALARTAGREADS 2763
21.47 SCALEMOTION[1..24] 2764
21.48 SCALEMOTION[1..200] 2764
21.49 SCALEPERIOD 2765
21.50 SCALESELECTD[1..4] 2766
21.51 SCANAREA 2766
21.52 SCANASSOCDSP 2767
21.53 SCANCTRLLVL 2768
21.54 SCANEUHI 2768

166
21.55 SCANEULO 2769
21.56 SCANFREQ 2770
21.57 SCANGRPDTL 2770
21.58 SCANOVERRUN 2771
21.59 SCANPNTDTL 2771
21.60 SCANRATE 2772
21.61 SCANRATE(UOC) 2775
21.62 SCANRATE [1...40] 2776
21.63 SCHDOPTIMIZE 2776
21.64 SCHEDCYCLE[0..120] 2777
21.65 SCINCONNHNDL[1..6] 2777
21.66 SCINCONNNAV[1..6] 2778
21.67 SCINCONNPRM[1..6] 2778
21.68 SCINCONNSTRVAL[1..6] 2778
21.69 SCINCONNVAL[1..6] 2779
21.70 SCMASTEP[1..15] 2779
21.71 SCMID 2780
21.72 SCMMODE 2780
21.73 SCMMONITOR 2780
21.74 SCMMONSRC 2781
21.75 SCMNAME 2781
21.76 SCMOPT 2782
21.77 SCMSTATE 2783
21.78 SCNUMSRCCONN 2783
21.79 SCRIPTOR 2784
21.80 SCSRC[1..6] 2784
21.81 SDENUMTEXT 2784

167
21.82 SEALOPT 2785
21.83 SECCANTTALKTOPRIONUCN 2785
21.84 SECBLOCKNAME [1...40] 2786
21.85 SECCHNERRA [1...40] 2786
21.86 SECCHNERRB [1...40] 2787
21.87 SECCHNMNA [1...40] 2787
21.88 SECCHNMNB [1...40] 2788
21.89 SECCHNPLA [1...40] 2788
21.90 SECCHNPLB [1...40] 2789
21.91 SECCHNSILA [1...40] 2789
21.92 SECCHNSILB [1...40] 2790
21.93 SECCOMMERR [1..40] 2791
21.94 SECCONNSTS 2792
21.95 SECDATAIN 2792
21.96 SECDATAIN.ARWSTS 2793
21.97 SECDATAIN.CASREQ 2794
21.98 SECDATAIN.CASSHED 2795
21.99 SECDATAIN.EUHI 2795
21.100 SECDATAIN.EULO 2796
21.101 SECDATAIN.EUSPAN100 2797
21.102 SECDATAIN.HISELECT 2798
21.103 SECDATAIN.INITREQ 2798
21.104 SECDATAIN.INITSTS 2799
21.105 SECDATAIN.INITVAL 2800
21.106 SECDATAIN.LOCALMAN 2801
21.107 SECDATAIN.ONESHOT 2802
21.108 SECDATAIN.ORFBSTS 2802

168
21.109 SECDATAIN.ORFBVAL 2803
21.110 SECDATAIN.OROFFSET 2804
21.111 SECDATAIN.PROPOVRD 2804
21.112 SECDATAIN.SECTYPE 2805
21.113 SECERRCNT 2806
21.114 SECERRCODE 2806
21.115 SECERRFL 2807
21.116 SECERRINFO 2807
21.117 SECIFCHNERRA 2808
21.118 SECIFCHNERRB 2808
21.119 SECIFCHNMNA 2809
21.120 SECIFCHNMNB 2809
21.121 SECIFCHNPLA 2810
21.122 SECIFCHNPLB 2810
21.123 SECIFCHNSILA 2811
21.124 SECIFCHNSILB 2811
21.125 SECIFCOMMERR 2812
21.126 SECIFRCVCHN 2813
21.127 SECINITOPT[1..8] 2813
21.128 SECINITOPT1 2814
21.129 SECIP 2814
21.130 SECIPMON 2815
21.131 SECLASTCONNTIME 2815
21.132 SECLASTDISCONNTIME 2815
21.133 SECLASTERRTIME 2816
21.134 SECLOOPDATA 2816
21.135 SECMODNAME 2817

169
21.136 SECNAMESTRG 2817
21.137 SECNAMESTRING 2818
21.138 SECNOTSYNED 2819
21.139 SECNUMCONN 2819
21.140 SECNUMCONNATMPT 2819
21.141 SECNUMDISCONN 2820
21.142 SECOND 2820
21.143 SECONDARYSIG 2821
21.144 SECOVERLAP[1..24] 2821
21.145 SECOVERLAP[1..200] 2822
21.146 SECRCVCHN [1..40] 2822
21.147 SECRPTCONNECTIONSTATE 2823
21.148 SECSIGSECLVL 2823
21.149 SECTCP 2824
21.150 SECTCPMON 2824
21.151 SECTMPNAME 2825
21.152 SECVAR 2825
21.153 SELDESC 2826
21.154 SELECTCABLEACMD 2826
21.155 SELECTCABLEBCMD 2827
21.156 SELHANDLER[1..8] 2828
21.157 SELHANDLERN[1..8] 2828
21.158 SELIN 2829
21.159 SELINT32FL 2829
21.160 SELMETHOD 2830
21.161 SELXDESC 2830
21.162 SELXFL[1..4] 2831

170
21.163 SELXFL[1..6] 2831
21.164 SELXFL[1..8] 2832
21.165 SELXINP 2832
21.166 SENDCLOSEREQ 2833
21.167 SENDCLOSERESP 2833
21.168 SENDFL[0..15] 2834
21.169 SENDOPENREQ 2834
21.170 SENDOPENRSP 2834
21.171 SENSORTYPE[0..numChans-1] 2835
21.172 SENSORTYPE [0..NUMCHANNELS-1] 2835
21.173 SENSRTYP 2836
21.174 SENSRTYP_AI_C 2840
21.175 SEQCLOSE 2842
21.176 SEQNOCMD 2843
21.177 SEQOPEN 2843
21.178 SEQSTART 2844
21.179 SEQSTATUS 2844
21.180 SEQSTOP 2844
21.181 SEQSTOPACTED 2845
21.182 SERIALNO 2845
21.183 SERIALNUM 2846
21.184 SERVERIP 2847
21.185 SHAREDMEM 2847
21.186 SHEDHOLD 2848
21.187 SHEDMODE[0..7] 2848
21.188 SHEDHOLD 2849
21.189 SHORT 2849

171
21.190 SHORT_DI_C 2850
21.191 SHORT[0..numChans-1] 2850
21.192 SHORTCIRCUIT[0..Number of status in assembly] 2851
21.193 Show UCM On Unit Timeline 2851
21.194 SHUTDOWNCMD 2851
21.195 SI 2852
21.196 SIACTED 2852
21.197 SIALM.FL 2853
21.198 SIALM.OPT 2853
21.199 SIALM.PR 2854
21.200 SIALM.SV 2855
21.201 SIFL 2855
21.202 SIMC200MACID 2856
21.203 SIMC200EMACID 2857
21.204 SIMCOMMAND 2857
21.205 SIMVALUE[1..1968] 2858
21.206 SIMDEVICEIDX 2858
21.207 SIMENABLE 2859
21.208 SIMIPADDRESS 2859
21.209 SIMMODE 2860
21.210 SIMSTATE 2862
21.211 SIMTARGET 2863
21.212 SIMULATEDIO 2863
21.213 SIMVALUE 2864
21.214 SIMVALUE[1..16] 2865
21.215 SIMVALUE[1..120] 2865
21.216 SIMVALUEREAL 2866

172
21.217 SIOPT 2866
21.218 SIPTYPE[0..7] 2867
21.219 SIPTYPE[0..numChans-1] 2867
21.220 SLOT0[0..7] 2868
21.221 SLOT1[0..7] 2868
21.222 SLOT2[0..7] 2869
21.223 SLOT3[0..7] 2869
21.224 SLOT 2870
21.225 SLOTNUM 2871
21.226 SLOTNUMBER 2872
21.227 SLOTNUM[0-3] 2873
21.228 SLOTSFBT 2873
21.229 SLOT0BOARDSTATUS 2874
21.230 SLOT0SELFTEST 2875
21.231 SLOT0STATUS 2875
21.232 SLOT0TS 2876
21.233 SLOT0TYPE 2876
21.234 SLOT2BOARDSTATUS 2877
21.235 SLOT2SELFTEST 2877
21.236 SLOT2STATUS 2878
21.237 SLOT2TYPE 2878
21.238 SLOT3BOARDSTATUS 2879
21.239 SLOT3SELFTEST 2879
21.240 SLOT3STATUS 2880
21.241 SLOT3TYPE 2880
21.242 SLOT4BOARDSTATUS 2881
21.243 SLOT4SELFTEST 2881

173
21.244 SLOT4STATUS 2882
21.245 SLOT4TYPE 2882
21.246 SLOT5BOARDSTATUS 2883
21.247 SLOT5SELFTEST 2883
21.248 SLOT5STATUS 2884
21.249 SLOT5TYPE 2884
21.250 SLOTTYPE 2885
21.251 SLOTNUM 2885
21.252 SLOWSTEPTIMR[1..24] 2886
21.253 SLOWSTEPTIMR[1..200] 2886
21.254 SLWFLSHSPD 2886
21.255 SNTPADDRESS 2887
21.256 SNTP1ADDR 2887
21.257 SNTP2ADDR 2888
21.258 SNTPSKEWTHLD 2888
21.259 SNTPSTAT 2889
21.260 SO 2889
21.261 SO[1..NUMCHAN] 2891
21.262 SO[6..7] 2892
21.263 SOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK]2892
21.264 SOAKVAL[1..NUMPROFILES][1..NUMRAMPSOAK] 2893
21.265 SOCMDOFF 2893
21.266 SOCMDON 2894
21.267 SOESDENUM 2895
21.268 SOESTDESC 2895
21.269 SOFTFAIL 2896
21.270 SOFTFAIL1A 2897

174
21.271 SOFTFAIL2A 2897
21.272 SOFTFAIL1B 2898
21.273 SOFTFAIL2B 2898
21.274 SOFTWAREREV[0..7] 2899
21.275 SOINITVAL 2899
21.276 SOINITVAL[1..NUMCHAN] 2900
21.277 SOREADFAIL 2900
21.278 SOSOURCE 2901
21.279 SOSTS 2901
21.280 SLWSRCID 2901
21.281 SP 2902
21.282 SP1FASTFEED[1..4] 2904
21.283 SP2FASTFEED[1..4] 2904
21.284 SP1FEEDING[1..4] 2905
21.285 SP2FEEDING[1..4] 2905
21.286 SP1TOLERANCE[1..4] 2906
21.287 SPCODESIZE 2906
21.288 SPCONN 2907
21.289 SPECIALTYPE 2907
21.290 SPECIFICVOLUME 2908
21.291 SPECIFICVOLUMEENGUNIT 2908
21.292 SPECIFICVOLUMEIO 2909
21.293 SPEM 2909
21.294 SPEUHI 2909
21.295 SPEULO 2910
21.296 SPFORMAT 2911
21.297 SPHI 2911

175
21.298 SPHIACTIVE 2912
21.299 SPHIFL 2912
21.300 SPHILM 2913
21.301 SPHILMOPT 2913
21.302 SPHIOPTOFFSET 2914
21.303 SPHIRAMPRATE 2915
21.304 SPLO 2915
21.305 SPLOACTIVE 2916
21.306 SPLOFL 2916
21.307 SPLOLM 2917
21.308 SPLOLMOPT 2917
21.309 SPLOOPTOFFSET 2918
21.310 SPLORAMPRATE 2918
21.311 SPOUT 2919
21.312 SPP 2919
21.313 SPPIN 2920
21.314 SPRATEREQ 2920
21.315 SPREQ 2921
21.316 SPTOL 2921
21.317 SPTV 2922
21.318 SPTVARWOPT 2922
21.319 SPTVDEVFL 2923
21.320 SPTVDEVMAX 2924
21.321 SPTVNORMRATE 2924
21.322 SPTVOPT 2925
21.323 SPTVP 2925
21.324 SPTVRATE 2926

176
21.325 SPTVREQ 2926
21.326 SPTVSTATE 2927
21.327 SPTVTIME 2927
21.328 SRC 2928
21.329 SRCDATA[0] 2928
21.330 SRVACEHASBKP 2929
21.331 SRVHASBKP 2929
21.332 SSERROR 2930
21.333 SSOBJECTIVEVALUE 2930
21.334 SSRECTOEQM 2930
21.335 SSSINGULARVALUE 2931
21.336 SSTEPLOCK 2931
21.337 STALECOUNT 2932
21.338 STARTFL 2932
21.339 STARTINDEX 2933
21.340 STARTOFFSET 2935
21.341 STARTOP[1..NUMPROFILES] 2935
21.342 STARTOPSEL 2936
21.343 STARTOPT 2936
21.344 STARTPHASE 2937
21.345 STARTRATE 2938
21.346 STARTSEG[1..NUMPROFILES] 2938
21.347 STARTTIME 2939
21.348 STARTVAL 2939
21.349 STATE 2940
21.350 STATE0 2943
21.351 STATE1 2944

177
21.352 STATETEXT[*] 2944
21.353 STATETEXT[0..1] 2945
21.354 STATETEXT[0..3] 2945
21.355 STATETEXT[0..6] 2946
21.356 STATETIME[0..2] 2946
21.357 STATRESET 2947
21.358 STATSRESET 2948
21.359 STATRESETA 2949
21.360 STATRESETB 2950
21.361 STATUS_1[1..24] 2950
21.362 STATUS_2[1..24] 2951
21.363 STATUS 2951
21.364 STATUSRAW[1..4] 2952
21.365 STDBYMAN 2952
21.366 STDBYSTS 2953
21.367 STDBYSTSA 2953
21.368 STDBYSTSB 2954
21.369 STDTIME 2954
21.370 STEADYSTATEOP 2955
21.371 STEADYSTATEOPEU 2955
21.372 STEADYSTATEPV 2956
21.373 STEAM_WATER 2956
21.374 STEAMQUALITY 2957
21.375 STEAMQUALITYIO 2957
21.376 STEAMTYPE 2958
21.377 STEP 2958
21.378 STEPALM.FL 2958

178
21.379 STEPALM.PR 2959
21.380 STEPALM.SV 2959
21.381 STEPPERSTATUS 2960
21.382 STEPTOPHASE 2960
21.383 STICTIONL 2961
21.384 STICTIONR 2961
21.385 STIDBDISCRE 2961
21.386 STI_EU 2962
21.387 STIPVNUMBER 2964
21.388 STISCRATCHPAD 2964
21.389 STISTATUS 2965
21.390 STISWVER 2965
21.391 STITAG 2965
21.392 STMCHOVRRUNSA 2966
21.393 STMCHOVRRUNSB 2966
21.394 STMCHMAXOVRRUNTIMEA 2967
21.395 STMCHMAXOVRRUNTIMEB 2967
21.396 STMCHLASTOVERRUNTIMEA 2968
21.397 STMCHLASTOVERRUNTIMEB 2968
21.398 STNDPIPELEN 2968
21.399 STOPALM.FL 2969
21.400 STOPALM.PR 2969
21.401 STOPALM.SV 2970
21.402 STOPFL 2970
21.403 STOPOPT 2971
21.404 STOPPULSEWIDTH 2972
21.405 STOPRATE 2973

179
21.406 STOPSTATEOPT 2973
21.407 STOPTIME 2974
21.408 STOPVAL 2974
21.409 STOREENB 2975
21.410 STORESTS 2975
21.411 STORONCHGENB 2976
21.412 STR[0..7] 2976
21.413 STR[1..8] 2977
21.414 STR[1..16] 2977
21.415 STR[1..120] 2978
21.416 STRLEN 2978
21.417 STRRESP[ ] 2979
21.418 STTEXT 2980
21.419 STTEXTA 2980
21.420 STTEXTB 2981
21.421 STUBIOM 2981
21.422 SUBMODTYPE 2982
21.423 SUBSCRIBEFAIL 2982
21.424 SUBSCPERIOD 2983
21.425 SUBSLOTNUM 2984
21.426 SUBVAL 2985
21.427 SUBVALTYPE 2986
21.428 SUM_MAXD 2986
21.429 SUM_N_A 2986
21.430 SUM_N_B 2987
21.431 SUM_N_F 2987
21.432 SUM_N_S 2988

180
21.433 SUM_N_SJL 2988
21.434 SUM_N_SS 2988
21.435 SUPVFIFORATEA 2989
21.436 SUPVFIFORATEM 2989
21.437 SURPLUSSCNTIME 2990
21.438 SWAPCTRLCMD 2990
21.439 SWAPPOSCMD 2990
21.440 SWAPPRIMARYCMD 2991
21.441 SWAPSBYCMD 2991
21.442 SWITCH 2992
21.443 SWITCHCMD 2992
21.444 SWTCHACT 2993
21.445 SYNCHSTS [1...40] 2994
21.446 SYNCPINSTONUMINPUTS 2994
21.447 SYNCSECCMD 2995
21.448 SYNCTIME 2995
21.449 SYNCTIMEBEG 2996
21.450 SYNCTIMEEND 2996
21.451 System Template 2997
Chapter 22 - Txxxx Parameters 2998
22.1 T 3006
22.2 T0 3007
22.3 T1 3007
22.4 T1HILM 3008
22.5 T1LOLM 3008
22.6 T2 3008
22.7 T2HILM 3009

181
22.8 T2LOLM 3009
22.9 TAGEXECSTATUS 3010
22.10 Tag Name 3010
22.11 TAGPARENT 3011
22.12 TAGTYPE 3011
22.13 TAGRDEXTSTATUS 3012
22.14 TAGRDGENSTATUS 3013
22.15 TARGETERROR[1..200] 3014
22.16 TARGETNAME 3015
22.17 TARGETPLATFORM 3015
22.18 TARGETSTEP[1..15] 3016
22.19 TARGETSTEPN[1..15] 3016
22.20 TASKHLTHMON 3017
22.21 TASKSTACKHILM 3017
22.22 TASKSTACKSIZE [0...N] 3018
22.23 TASKSTACKUSED [0...N] 3018
22.24 TAU 3019
22.25 TBADREADS 3019
22.26 TBREF[0..2] 3020
22.27 TCDISPAVGPPS 3020
22.28 TCDISPMAXPPS 3021
22.29 TCMICURRENTSTATE 3021
22.30 TCMIANDTCMKEYSWPOSMISMATCH 3022
22.31 TCMIAUTHSERVERIP 3022
22.32 TCMIAUTHSTS 3023
22.33 TCMICOMMAND 3023
22.34 TCMIDOWNLINKIP 3024

182
22.35 TCMIDOWNLINKRXERROR 3024
22.36 TCMIDOWNLINKRXRATE 3025
22.37 TCMIDOWNLINKTXERROR 3025
22.38 TCMIDOWNLINKTXRATE 3026
22.39 TCMIDRIFTVALUE 3026
22.40 TCMIIPADDRLEFT 3027
22.41 TCMIIPADDRRIGHT 3027
22.42 TCMIMULTIIPADDRSTR 3028
22.43 TCMINODETYPE 3028
22.44 TCMINUM 3029
22.45 TCMIPRIMARYKEYSWITCH 3029
22.46 TCMIPRIVATEPATHIP 3030
22.47 TCMIPRIVATEPATHRXERROR 3030
22.48 TCMIPRIVATEPATHTXERROR 3031
22.49 TCMIPRIVATEPATHRXRATE 3031
22.50 TCMIPRIVATEPATHTXRATE 3032
22.51 TCMINODEDATE 3032
22.52 TCMINODETIME 3033
22.53 TCMISECKEYSWITCH 3033
22.54 TCMISTATE 3034
22.55 TCMISYNCHERNODE 3034
22.56 TCMITIMESYNCFAIL 3035
22.57 TCMKEYSWITCH 3035
22.58 TCMVERSION 3036
22.59 TCMPROGRAM 3036
22.60 TCPACTIVEOPENS 3036
22.61 TCPATTEMPTFAILS 3037

183
22.62 TCPCONNNUM 3038
22.63 TCPCONNTABLE 3038
22.64 TCPCURRESTAB 3038
22.65 TCPEERAVGPPS 3039
22.66 TCPEERMAXPPS 3039
22.67 TCPESTABRESETS 3040
22.68 TCPINCSUMERRS 3040
22.69 TCPINERRS 3041
22.70 TCPINSEGS 3041
22.71 TCPMAXCONN 3042
22.72 TCPOUTRESETS 3042
22.73 TCPOUTSEGS 3042
22.74 TCPPASSIVEOPENS 3043
22.75 TCPRETRANSSEGS 3044
22.76 TCPRTOALGO 3044
22.77 TCPRTOMAX 3044
22.78 TCPRTOMIN 3045
22.79 TCRNGOPT 3045
22.80 TEMPAVG 3046
22.81 TEMPCRIT 3046
22.82 TEMPCRITLM 3047
22.83 TEMPCURA 3047
22.84 TEMPCURB 3048
22.85 TEMPERATURE 3048
22.86 TEMPERATUREENGUNIT 3049
22.87 TEMPERATUREIO 3049
22.88 TEMPHILM 3050

184
22.89 TEMPLOLM 3051
22.90 TEMPMAX 3052
22.91 TEMPMAXA 3052
22.92 TEMPMAXB 3053
22.93 TEMPMIN 3053
22.94 TEMPMINA 3054
22.95 TEMPMINB 3054
22.96 TEMPMODE 3055
22.97 TEMPUNITS [0..NUMCHANNELS-1] 3055
22.98 TERMSTATEOPT 3056
22.99 TESTDATASAVE 3056
22.100 TESTOPT 3057
22.101 TESTPAR_Boolean [6] 3057
22.102 TESTPAR_CONTEXT 3058
22.103 TESTPAR_FLOAT64 [6] 3058
22.104 TESTPAR_UINT32 [6] 3059
22.105 TEXTCOLOR 3059
22.106 TEXTCOMMENT 3060
22.107 TEXTSIZE 3060
22.108 TF 3061
22.109 TGTAPPCONNID[1..24] 3061
22.110 TGTCONNSTATE [1..20] 3062
22.111 TGTCONNSTATE[1..24] 3062
22.112 TGTIP 3063
22.113 TGTRECVMSGRATE [1..20] 3063
22.114 TGTRESENTMSGCNT [1..20] 3063
22.115 TGTRNDTRIPAVG [1..20] 3064

185
22.116 TGTRNDTRIPMAX [1..20] 3064
22.117 TGTRNGDEF 3065
22.118 TGTRNGDEFOPT 3065
22.119 TGTSENTMSGRATE [1..20] 3065
22.120 TGTTCLASS[1..24] 3066
22.121 THERMERR 3066
22.122 THERMOCOUPLETYPE 3067
22.123 THREAD[1..10] 3069
22.124 THRESHOLD 3069
22.125 TIME 3070
22.126 TIME[1..8] 3070
22.127 TIMEBASE 3071
22.128 TIMEBASE[0..7] 3072
22.129 TIMEIN 3073
22.130 TIMEOUT 3073
22.131 TIMELASTSKEW 3074
22.132 TIMELASTSYNC 3074
22.133 TIMEPASTTHISSEG 3075
22.134 TIMER1 3076
22.135 TIMER2 3076
22.136 TIMER3 3077
22.137 TIMER4 3077
22.138 TIMER5 3078
22.139 TIMER6 3078
22.140 TIMESOURCE 3079
22.141 TIMESYNCSTAT 3080
22.142 TIMETOFINISH[1..24] 3080

186
22.143 TIMETOFINISH[1..200] 3081
22.144 TIMETORESAVE 3081
22.145 TIMETOSAVE1 3082
22.146 TIMETOSAVE2 3083
22.147 TIMOUT[0..15] 3083
22.148 TIMOUTCNT[0..15] 3084
22.149 TIMEZONE 3084
22.150 TINUMINMSGAVGPS 3085
22.151 TINUMOUTMSGMAXPS 3085
22.152 TINUMOUTMSGAVGPS 3086
22.153 TINUMINMSGMAXPS 3086
22.154 TIPEERAVGLPS [1...TIPEERCONNMAX] 3086
22.155 TIPEERAVGPPS [1...TIPEERCONNMAX] 3087
22.156 TIPEERCONN 3087
22.157 TIPEERCONNERRCODE [1...N] 3088
22.158 TIPEERCONNERRINFO [1...N] 3088
22.159 TIPEERCONNMAX 3089
22.160 TIPEERCONNSTS [1...N] 3090
22.161 TIPEERMAXLPS [1...TIPEERCONNMAX] 3090
22.162 TIPEERMAXPPS [1...TIPEERCONNMAX] 3091
22.163 TIPEERNAME [1...TIPEERCONNMAX] 3091
22.164 TIPEERPATH [1...TIPEERCONNMAX] 3092
22.165 TKNCNTA 3092
22.166 TKNCNTB 3093
22.167 TMBTCPAVGRCVMSGPS 3093
22.168 TMBTCPAVGXMITMSGPS 3093
22.169 TMBTCPMAXRCVMSGPS 3094

187
22.170 TMBTCPMAXXMITMSGPS 3094
22.171 TMOUTFL 3095
22.172 TMOUTMODE 3095
22.173 TMOUTTIME 3096
22.174 TMPENGUNIT 3096
22.175 TNUMACEINCON 3097
22.176 TNUMACEOUTCON 3097
22.177 TNUMC3INCON 3098
22.178 TNUMC3OUTCON 3099
22.179 TNUMCN100INCON 3100
22.180 TNUMCN100OUTCON 3100
22.181 TNUMCPMINCON 3100
22.182 TNUMCPMOUTCON 3101
22.183 TNUMEHPMINCON 3101
22.184 TNUMFIMINCON 3102
22.185 TNUMFIMOUTCON 3103
22.186 TNUMIOLMINCON 3104
22.187 TNUMIOLMOUTCON 3104
22.188 TNUMLIOMINCON 3105
22.189 TNUMLIOMOUTCON 3106
22.190 TNUMNTFRQUAVG 3107
22.191 TNUMNTFRQUMAX 3107
22.192 TNUMPLCOUTCON 3108
22.193 TNUMPMDINCON 3109
22.194 TNUMPMDOUTCON 3109
22.195 TNUMQCSINCON 3110
22.196 TNUMQCSOUTCON 3111

188
22.197 TNUMSCADAINCON 3111
22.198 TNUMSCEINCON 3112
22.199 TNUMSCEOUTCON 3113
22.200 TNUMSCFIMINCON 3114
22.201 TNUMSCFIMOUTCON 3114
22.202 TNUMSIOLMINCON 3115
22.203 TNUMSIOLMOUTCON 3116
22.204 TNUMSMINCON 3116
22.205 TOCONNPRIORITY 3117
22.206 TOCONNTYPE 3118
22.207 TOGDESC 3118
22.208 TOGINTERVALS 3118
22.209 TOGINTSEL 3119
22.210 TOPOLOGY 3119
22.211 TORPI 3120
22.212 TORPI 3120
22.213 TOTALACTCAP 3121
22.214 TOTALARRAYSIZE 3121
22.215 TOTALCONFIGSIZE 3121
22.216 TOTALDSDSIZE 3122
22.217 TOTALMEM 3123
22.218 TOTALMEMINK 3123
22.219 TOTALNUMGETITEM 3124
22.220 TOTALNUMPOINTSREADS 3124
22.221 TOTALREQRESPCOUNT 3125
22.222 TOTALREQSENT 3125
22.223 TOTALTIME 3125

189
22.224 TOTALTIME[1..50] 3126
22.225 TOTALRXRATE 3126
22.226 TOTALRXRATEMAX 3127
22.227 TOTALTXRATE 3127
22.228 TOTALTXRATEMAX 3128
22.229 TOTCHNERRA 3128
22.230 TOTCHNERRB 3129
22.231 TOTCHNMNA 3129
22.232 TOTCHNMNB 3130
22.233 TOTCHNPLA 3130
22.234 TOTCHNPLB 3131
22.235 TOTCHNSILA 3131
22.236 TOTCHNSILB 3132
22.237 TOTELAPSEDTM 3132
22.238 TOTICPNAKS 3133
22.239 TOTICPSENDFAIL 3133
22.240 TP 3134
22.241 TPNCLKSRCMASTER 3134
22.242 TPNTIMESTR 3135
22.243 TRACKING 3135
22.244 TRANCYCLE[1..24] 3136
22.245 TRANMONITR 3136
22.246 TRANSPERSEC 3136
22.247 TRANSTERM 3137
22.248 TRDISPAVGLPS [1...TRDISPCONNMAX] 3138
22.249 TRDISPAVGLPSCONN [1...TRDISPCONNMAX] 3139
22.250 TRDISPAVGPPS [1...TRDISPCONNMAX] 3139

190
22.251 TRDISPAVGPPSCONN [1...TRDISPCONNMAX] 3140
22.252 TRDISPCONN 3140
22.253 TRDISPCONNMAX 3141
22.254 TRDISPDEGIMRCONN [1...TRDISPCONNMAX] 3141
22.255 TRDISPMAXLPS [1...TRDISPCONNMAX] 3142
22.256 TRDISPMAXLPSCONN [1...TRDISPCONNMAX] 3142
22.257 TRDISPMAXPPS [1...TRDISPCONNMAX] 3143
22.258 TRDISPMAXPPSCONN [1...TRDISPCONNMAX] 3143
22.259 TREEBITMAP 3144
22.260 TREND 3144
22.261 TRENDINTRVAL 3145
22.262 TREND.NUMBER 3146
22.263 TREND.NUMPARAMS 3146
22.264 TREND.PARAM 3147
22.265 TREND.POSITION 3148
22.266 TRENDSETNUMBER 3149
22.267 TRFB 3149
22.268 TRGOPTS_SET 3149
22.269 TRICONDATE 3150
22.270 TRICONEXMAINTREQ 3150
22.271 TRICONTIME 3151
22.272 TRIGGER 3151
22.273 TRIGGEROPTS 3151
22.274 TRINODENUM 3152
22.275 TRIPRIMIP1 3152
22.276 TRIPTIME 3153
22.277 TRISECIP1 3153

191
22.278 TRKCLOSEFEEDBKTIME 3153
22.279 TRKNUMTRANS 3154
22.280 TRKOPENFEEDBKTIME 3154
22.281 TRKSIOVRD 3155
22.282 TRKSTATETIME 3155
22.283 TRMNTALM.PR 3155
22.284 TRMNTALM.SV 3156
22.285 TRNUMINMSGAVGPS 3156
22.286 TRNUMINMSGMAXPS 3157
22.287 TRNUMOUTMSGMAXPS 3157
22.288 TRNUMOUTMSGAVGPS 3158
22.289 TRPEERAVGLPS [1...TRPEERCONNMAX] 3158
22.290 TRPEERAVGLPSCONN [1...TRPEERCONNMAX] 3159
22.291 TRPEERAVGPPS [1...TRPEERCONNMAX] 3159
22.292 TRPEERAVGPPSCONN [1...TRPEERCONNMAX] 3160
22.293 TRPEERCONN 3160
22.294 TRPEERCONNMAX 3161
22.295 TRPEERDEGIMRCONN [1...TRPEERCONNMAX] 3161
22.296 TRPEERMAXLPS [1...TRPEERCONNMAX] 3162
22.297 TRPEERMAXLPSCONN [1...TRPEERCONNMAX] 3162
22.298 TRPEERMAXPPS [1...TRPEERCONNMAX] 3163
22.299 TRPEERMAXPPSCONN [1...TRPEERCONNMAX] 3163
22.300 TRPEERNAME [1...TRPEERCONNMAX] 3164
22.301 TRPLOPT 3164
22.302 TRUNCATEOPT 3164
22.303 TSAADATREADWRITEFAIL 3165
22.304 TSC 3165

192
22.305 TSCALM.FL 3166
22.306 TSCALM.OPT 3166
22.307 TSCALM.PR 3166
22.308 TSCALM.SV 3167
22.309 TSENABLED 3167
22.310 TSFORPROT 3168
22.311 TSO 3168
22.312 TSOALM.FL 3168
22.313 TSOALM.OPT 3169
22.314 TSOALM.PR 3169
22.315 TSOALM.SV 3170
22.316 TSTS 3170
22.317 TURNONOFF 3171
22.318 TV 3171
22.319 TV[6..7] 3172
22.320 TVFL 3173
22.321 TVPROC 3173
22.322 TVPROC[6..7] 3175
22.323 TVRAW 3175
22.324 TVRAW[6..7] 3176
22.325 TYPE 3176
22.326 TYPECONVERT1 3177
22.327 TYPECONVERT2 3177
22.328 TYPECONVERT3 3178
22.329 TYPECONVERT4 3178
22.330 TYPECONVERT5 3179
22.331 TYPECONVERT6 3179

193
22.332 TYPEIDENTIFIER 3180
22.333 TYPEINVALIDA 3180
22.334 TYPEINVALIDB 3181
Chapter 23 - Uxxxx Parameters 3182
23.1 UCMNAME 3184
23.2 UCNADDRESS 3185
23.3 UCNLIVESTR 3186
23.4 UCNOVERRUN 3186
23.5 UCNNW 3186
23.6 UCPCLOSE 3187
23.7 UCPOPEN 3187
23.8 UCPREL 3188
23.9 UCPSTART 3188
23.10 UCPSTOP 3188
23.11 UCPSTOPACTED 3189
23.12 UDPINDGRAMS 3189
23.13 UDPINERRORS 3190
23.14 UDPINCSUMERRORS 3191
23.15 UDPLISTENERS 3191
23.16 UDPNOPORTS 3192
23.17 UDPNUMLISTENERS 3193
23.18 UDPOUTGRAMS 3193
23.19 UDTTAGREADS 3194
23.20 UEAKEY 3194
23.21 UEAKEYCONFSF 3195
23.22 UEALED 3196
23.23 UEALEDSTS 3196

194
23.24 UEALOCATE 3197
23.25 UIDDEVTYPE[0..15] 3197
23.26 UIDDEVTYPEMON[0..15] 3198
23.27 UIDLOOPADDR[0..15] 3198
23.28 UIDLOOPDATA[0..15] 3199
23.29 UIDLOOPDATACHG[0..15] 3199
23.30 UIDLOOPMODE[0..15] 3200
23.31 UIDLOOPRATE[0..15] 3200
23.32 UIDLOOPTYPE[0..15 3201
23.33 UIDORPHANRESPCNT[0..15] 3202
23.34 UIDREQSENT[0..15] 3202
23.35 UIDREQRSPRCVD[0..15] 3202
23.36 UIDSUPCMDS[0..15] [0..50] 3203
23.37 UINT32PARAM 3203
23.38 UINT32VAL[0…80] 3204
23.39 ULCNBMAC 3204
23.40 UNCMDALM.FL 3205
23.41 UNCMDALM.PR 3206
23.42 UNCMDALM.SV 3206
23.43 UNCMDCHGALM.FL 3207
23.44 UNCMDCHGALM.OPT 3207
23.45 UNCMDCHGALM.PR 3208
23.46 UNCMDCHGALM.SV 3208
23.47 UNCONNSENDERR 3209
23.48 UNDERRANGE 3209
23.49 UNDERRANGE[0..numChans-1] 3210
23.50 UNDERRANGE [0..NUMCHANNELS-1] 3210

195
23.51 UNDERTOLRNCE[1..200] 3211
23.52 UNDERZERO[1..24] 3211
23.53 UNDERZERO[1..200] 3212
23.54 UNEXPECTEDRDRRESPONSECOUNT 3212
23.55 UNFORCEDPREDICTION 3213
23.56 UNIT[1...50] 3213
23.57 UNITACQ[1...50] 3213
23.58 UNITACQFL[1...50] 3214
23.59 UNITACQSTATE[1...50] 3214
23.60 UNITCLASS[1...50] 3215
23.61 UNITCLSID[1...50] 3215
23.62 UNITID[0..15] 3216
23.63 UNITIDMON[0..15] 3216
23.64 UNITNAME[1...50] 3217
23.65 UNITNUM[1..50] 3217
23.66 UNITRELFL[1...50] 3218
23.67 UNITS 3218
23.68 UNITTEXT 3219
23.69 UOCPSFAILRIGHT 3219
23.70 UOCPSFAILLEFT 3219
23.71 UPDATEMODEL 3220
23.72 UPDATERATE 3220
23.73 UPDATOPT 3221
23.74 UPDRESOPT 3221
23.75 UPTIME 3222
23.76 URL 3223
23.77 URL (HART) 3225

196
23.78 URVTOLERANCE 3225
23.79 URV 3226
23.80 URV (HART) 3226
23.81 USEDFL 3227
23.82 USEDMEM 3227
23.83 USEDMEMINK 3228
23.84 USEDXLREQSINIT 3228
23.85 USEDXLREQSRESP 3229
23.86 USEKEEPALIVE 3229
23.87 USENAMEREF 3229
23.88 USEPVIFWOUNDUP 3230
23.89 USERCFGVAL 3231
23.90 USERDEFRANGE[0..7] 3231
23.91 USERLCKTOIDLE 3232
23.92 USERLCKTORUN 3232
23.93 USESIM 3232
23.94 USERSYMNAME 3233
23.95 USESIMULATION 3233
Chapter 24 - Vxxxx Parameters 3234
24.1 V3TIMESFLOW 3236
24.2 VALVETRAVELRDCT 3236
24.3 VAVGFLOWRATE 3237
24.4 VAVGSPILL 3237
24.5 VAWAITINGACK 3237
24.6 VCOMINTEGRTY 3238
24.7 VCOMMAND 3238
24.8 VCOMMANDSTAT 3239

197
24.9 VCOMMERROR 3239
24.10 VCYCLEACTIVE 3239
24.11 VDATAOK 3240
24.12 VDELAYPRIMRY 3240
24.13 VDELIVEREDWT 3241
24.14 VENDOR 3241
24.15 VENDOR[0..15] 3241
24.16 VENDORID 3242
24.17 VERIFYLOST 3242
24.18 VERIFYLOST[0..numChans-1] 3243
24.19 VERRATICFLOW 3243
24.20 VERSION 3243
24.21 VERSIONDATE 3244
24.22 VERSIONNUM 3245
24.23 VERYUNSTABLE[1..24] 3246
24.24 VERYUNSTABLE[1..200] 3247
24.25 VFCE_OUTPUT 3247
24.26 VFEEDFAILED 3247
24.27 VFEEDOVERRDE 3248
24.28 VFEEDTYPE 3248
24.29 VFEEDWEIGHT 3249
24.30 VGROSSWEIGHT 3249
24.31 VGROSSWGTFED 3249
24.32 VIBRALM.FL 3250
24.33 VIBRALM.OPT 3250
24.34 VIBRALM.PR 3251
24.35 VIBRALM.SV 3251

198
24.36 VIBRTRIP 3251
24.37 VIBRTRIPACTED 3252
24.38 VMANUALMODE 3252
24.39 VMATERIALPTH 3253
24.40 VMSGSEQNUMBR 3253
24.41 VMXCHANNEL 3253
24.42 VMXCOMMAND 3254
24.43 VMXFERSTATQ 3254
24.44 VMXFERSTATUS 3255
24.45 VMXGROUPNUM 3255
24.46 VMXMATPATH 3256
24.47 VMXNEGTOLER 3256
24.48 VMXOVRLAPNUM 3256
24.49 VMXPOSTOLER 3257
24.50 VMXTARGETWGT 3257
24.51 VMXTRANID 3258
24.52 VOLTAGE 3258
24.53 VOLTAGE[0..7] 3259
24.54 VOLTAGETYPE 3260
24.55 VOTED 3260
24.56 VOVERCAPACTY 3260
24.57 VOVERTOLRNCE 3261
24.58 VPOWERFAIL 3261
24.59 VPRIMOVERLAP 3262
24.60 VRATE 3262
24.61 VRATEALARM 3262
24.62 VSCALEMOTION 3263

199
24.63 VSECOVERLAP 3263
24.64 VSEL_CHANNEL 3264
24.65 VSLOWSTEPTMR 3264
24.66 VTARGETERROR 3264
24.67 VTIMETOFINSH 3265
24.68 VUNDERTOLRNC 3265
24.69 VUNDERZERO 3266
24.70 VVERYUNSTBLE 3266
24.71 VWAITOVLPREQ 3266
24.72 VWGTUNSTABLE 3267
Chapter 25 - Wxxxx Parameters 3268
25.1 WAITINGFL 3269
25.2 WAITOVLPREQ[1..24] 3270
25.3 WAITOVLPREQ[1..200] 3270
25.4 WAITSTABLE[1..200] 3271
25.5 WARMSTRTA 3271
25.6 WARMSTRTB 3272
25.7 WARMTIMEOUT 3272
25.8 WARNING 3273
25.9 WCTCLKTIME 3273
25.10 WDGTEMPALM.FL 3274
25.11 WDGTEMPALM.OPT 3274
25.12 WDGTEMPALM.PR 3274
25.13 WDGTEMPALM.SV 3275
25.14 WDGTEMPTRIP 3275
25.15 WDGTEMPTRIPACTED 3276
25.16 WDTHWFAIL 3276

200
25.17 WDTSWFAIL 3277
25.18 WDTREFRESHMAX 3278
25.19 WDTREFRESHMIN 3278
25.20 WEEKDAY 3279
25.21 WEEKDAYFMT 3279
25.22 WETLEGTEMP 3280
25.23 WGTUNSTABLE[1..24] 3280
25.24 WIREOFF 3280
25.25 WIREOFF[0..numChans-1] 3281
25.26 WIREOFF[0..7] 3281
25.27 WIREOFFALARM[0..7] 3282
25.28 WITHBIAS[1..40] 3282
25.29 WITHBIASENM[1..40] 3283
25.30 WRFIFORATEA 3283
25.31 WRFIFORATEM 3284
25.32 WRITEERROPT 3284
25.33 WRITEERRORS 3285
25.34 WRITEERRORSMAX 3285
25.35 WRITEOPT 3285
25.36 WRITEPPS 3287
25.37 WRITEPPSMAX 3287
25.38 WRITESTATUS 3287
25.39 WRTERRALM.PR 3288
25.40 WRTERRALM.SV 3288
25.41 WTS 3289
25.42 WTSALM.FL 3289
25.43 WTSALM.OPT 3290

201
25.44 WTSALM.PR 3290
25.45 WTSALM.SV 3290
Chapter 26 - Xxxxx Parameters 3292
26.1 X 3294
26.2 X[1..4] 3294
26.3 X[1..6] 3295
26.4 X[1..8] 3295
26.5 X[1..10] 3296
26.6 X1 3296
26.7 X1BACKCALOUT 3297
26.8 X1BIAS 3297
26.9 X1CONN 3298
26.10 X1P 3298
26.11 X1KB 3298
26.12 X1SECDATA 3299
26.13 X1STS 3299
26.14 X2 3300
26.15 X2BACKCALOUT 3300
26.16 X2BIAS 3301
26.17 X2CONN 3301
26.18 X2KB 3301
26.19 X2SECDATA 3302
26.20 X2STS 3302
26.21 XB[1..6] 3303
26.22 XB[1..10] 3303
26.23 XCONN[1..4] 3303
26.24 XCONN[1..8] 3304

202
26.25 XCONN[1..10] 3304
26.26 XDESC[1..2] 3305
26.27 XDESC[1..4] 3305
26.28 XDESC[1..8] 3305
26.29 XDESC[1..10] 3306
26.30 XENABLE[1..10] 3306
26.31 XEUHI 3307
26.32 XEULO 3307
26.33 XK[1..4] 3307
26.34 XK[1..6] 3308
26.35 XK[1..10] 3308
26.36 XKB[1..6] 3309
26.37 XKB[1..10] 3309
26.38 XOVERFAILED 3310
26.39 XSTS 3310
26.40 XSTS[0..5] 3311
26.41 XSTS[1..4] 3311
26.42 XSTS[1..6] 3311
26.43 XSTS[1..10] 3312
26.44 XSUB[1..10] 3312
26.45 XWHIFL 3313
26.46 XWLOFL 3313
26.47 X_AUTORESTART 3313
26.48 X_BLOCKMEM 3314
26.49 X_BLOCKMEMCR 3315
26.50 X_BLOCKMEMMR 3315
26.51 X_BRANCHLIM 3316

203
26.52 X_CC3MINREQV 3316
26.53 X_CHILDUCMACQ 3317
26.54 X_CNFGEQUIPNAME 3317
26.55 X_DEFLTFRMPARAMREF 3318
26.56 X_DEFLTRPRTPARAMREF 3318
26.57 X_DEFLTVALREF 3319
26.58 X_DISPADJPARAM 3319
26.59 X_DISPEQUIPNAME 3320
26.60 X_EQUIPLSTATE 3320
26.61 X_EVTOPTFORMULAPARAM 3321
26.62 X_EVTOPTREPORTPARAM 3322
26.63 X_EXECMODE 3322
26.64 X_MASTERCLUSTERID 3323
26.65 X_NAMEREF 3323
26.66 X_NAMEREFSTS 3324
26.67 X_NUMUNITS 3324
26.68 X_PLATOPT 3325
26.69 X_REFCOMMIT 3325
26.70 X_REFMODE 3326
26.71 X_REFSTATE 3327
26.72 X_SSRECTOEQM 3327
26.73 X_TRANSTERM 3328
26.74 X_UNITNAMEREF 3329
26.75 X_UNITNAMEREFSTS 3330
26.76 X_UNITTARGREF 3330
26.77 X_UNITTARGREFSTS 3331
26.78 X_USENAMEREF 3331

204
Chapter 27 - Yxxxx Parameters 3333
27.1 YEAR 3333
27.2 YEARFMT 3333
Chapter 28 - Common labels 3335
28.1 Add 3335
28.2 Array indices (i) 3336
28.3 Array indices (j) 3336
28.4 Assign 3336
28.5 Assign channel block 3336
28.6 Block Faceplate Color 3336
28.7 Block Symbol Name 3337
28.8 Default 3337
28.9 Derivation hierarchy 3337
28.10 List of parameters 3337
28.11 Module name 3337
28.12 Module type 3338
28.13 Remove 3338
28.14 Selected parameters grid 3338
28.15 Unassign channel block 3338
28.16 View block name 3338
28.17 View parameter labels and values 3338
28.18 View pin labels 3339
28.19 View pin values 3339
28.20 View type name 3339

205
CHAPTER

1 ABOUT THIS DOCUMENT

Provides information about parameters associated with configuration forms for function blocks in
Control Builder.

1.1 Revision History

Revision Date Description

A August 2020 Initial release of the document.

- 206 -
CHAPTER

2 3XXXX PARAMETERS

2.1 3TIMESFLOW[1..24] 207


2.2 3TIMESFLOW[1..200] 207
2.3 24VPSSTS 208

2.1 3TIMESFLOW[1..24]

Specific to QIPACTERM
Block
Description Three Times Average Flow
Data Type Boolean
Range Off(0) OK
On(1) Three Times Average Flow
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 10 of the Status 2 word in the input assembly for the
designated position [1-24].

2.2 3TIMESFLOW[1..200]

Specific to QIPACCHAN
Block
Description Three Times Average Flow
Data Type Boolean
Range Off(0) OK
On(1) Three Times Average Flow
Default 0
Config Load No

- 207 -
Chapter 2 - 3xxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 10 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

2.3 24VPSSTS

Specific to Block(s) TCMI


Description 24 Volts Power Supply
Data Type ENUM
Range N/A
Default OK
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 208 -
CHAPTER

3 AXXXX PARAMETERS

3.1 ABBREV 215


3.2 ABORTALM.FL 215
3.3 ABORTALM.PR 216
3.4 ABORTALM.SV 216
3.5 ABORTLOCK 216
3.6 ACCDEV.FL[1..4] 217
3.7 ACCDEV.TP[1..4] 217

3.8 ACCEPTDEV 218


3.9 ACCEPTRNG 218
3.10 ACCEPTSIMPEERDATA 219
3.11 ACCESSLEVEL 219
3.12 ACCTV 220
3.13 ACCTVFL 220
3.14 ACEMACADDR 221
3.15 ACEMEMINMB 221
3.16 ACERDNROLE 222
3.17 ACERMCONNSTS 223
3.18 ACK 223
3.19 ACQUIREOPT 224
3.20 ACQRESTYPE 224
3.21 ACTARRWRITES 225
3.22 ACTAVAIL 225
3.23 ACTCOMMAND 226
3.24 ACTCREATETIME 226
3.25 ACTCREATETYPE 227
3.26 ACTCRMIGOPT 227
3.27 ACTENTITY 228
3.28 ACTENTITYIOC 228
3.29 ACTEXECENDTTIME 229
3.30 ACTEXECSTARTTIME 229
3.31 ACTID 230
3.32 ACTIVESCOPE 230

- 209 -
Chapter 3 - Axxxx Parameters

3.33 ACTNONARRWRITES 231


3.34 ACTOPT 231
3.35 ACTPARENT 232
3.36 ACTREMOVETYPE 232
3.37 ACTSTATE 233
3.38 ACQONBEHALF 234
3.39 ACQSTATE 235
3.40 ACTIVEDATE 236
3.41 ACTIVEFL 236
3.42 ACTIVEHANDLR[1..8] 236
3.43 ACTIVELOC.HANDLER 237
3.44 ACTIVELOC.HANDLERN 237
3.45 ACTIVELOC.HNDTYPE 238
3.46 ACTIVELOC.STEP[1..15] 238

3.47 ACTIVELOC.STEPN[1..15] 239


3.48 ACTIVELOC.STEPICOMP[1..15] 239
3.49 ACTIVELOC.STEPIPEND[1..15] 240
3.50 ACTIVELOC.TIME[1..15] 240
3.51 ACTIVELOCOCD 241
3.52 ACTIVEARRPARAMWRITES 241
3.53 ACTIVENONARRPARAMWRITES 242
3.54 ACTPARENTLOOKUP 242
3.55 ACTPRIM[1..40] 243
3.56 ACTRAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK] 243
3.57 ACTSOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK] 244
3.58 ACTSOAKVAL[1..NUMPROFILES][1..NUMRAMPSOAK] 244
3.59 ACTSTARTOP[1..NUMPROFILES] 245
3.60 ACTSTARTSEG[1..NUMPROFILES] 245
3.61 ACTTYPE 246
3.62 ACTUALPROVERSIGNAL 246
3.63 ACTUALSCANTIME 247
3.64 ACTVTNTIME 247
3.65 ACTWRITEALLOCFAIL 247
3.66 ADDRCOUNT 248
3.67 ADVALARM_ACTIVE_ALARMS 248
3.68 ADVALARM_ACTUAL_VALUE [0...4] [0...31] 249
3.69 ADVALARM_COND_ASSOCALARM [0...31] 249
3.70 ADVALARM_COND_NAME [0...31] 249
3.71 ADVALARM_ENABLE [0...31] 250

- 210 -
Chapter 3 - Axxxx Parameters

3.72 ADVALARM_NUM_CONFCOND 250


3.73 ADVALARM_PARREF_BITS [0...4] [0...31] 251
3.74 ADVALARM_PARREF_BLOCK [0...4] [0...31] 251
3.75 ADVALARM_PARREF_PARAM [0...4] [0...31] 252
3.76 ADVALARM_PARREF_SUBINDEX [0...4] [0...31] 252
3.77 ADVALARM_PRIORITY [0...31] 253
3.78 ADVALARM_REFERED_BLOCK_ID [0...4] [0...31] 253
3.79 ADVALARM_REFERED_PARAM_ID [0...4] [0...31] 253
3.80 ADVALARM_STALE_DATA 254
3.81 ADVALARM_UPDATED_OD_IDX 254
3.82 ADVDEVALM.DB 255
3.83 ADVDEVALM.DBU 255
3.84 ADVDEVALM.FL 256
3.85 ADVDEVALM.PR 256

3.86 ADVDEVALM.SV 256


3.87 ADVDEVALM.TM 257
3.88 ADVDEVALM.TMO 257
3.89 ADVDEVALM.TP 258
3.90 ADVDEVOPT 258
3.91 ADVSP 259
3.92 ADVSPP 259
3.93 AICHNLNAME 260
3.94 AIHASENAME 260
3.95 AIPTEXECST 261
3.96 AIREGISTERED[ ] 261
3.97 ALERTTIMEOUT 262
3.98 ALFMT 262
3.99 ALGOPROCSTATE 263
3.100 ALGOREGSTATE 263
3.101 ALGOTYPE 264
3.102 ALIAS[ ].ALL 264
3.103 ALIAS[ ].STATUS 265
3.104 ALIAS[ ].VALUE 265
3.105 ALIASBLKTYP[ ] 265
3.106 ALIASDATATYP[ ] 266
3.107 ALIASOPT 266
3.108 ALIASPRMTYP[ ] 267
3.109 ALIASREF[ ][ ] 267
3.110 ALIASSRC[ ][ ] 267

- 211 -
Chapter 3 - Axxxx Parameters

3.111 ALLEVTJRNLD 268


3.112 ALLOWNAN 268
3.113 ALMACTIVE [0..NUMALARMS-1] 269
3.114 ALMDB 269
3.115 ALMDBU 270
3.116 ALMDESC [0..NUMALARMS-1] 271
3.117 ALMENBSTATE 271
3.118 ALMIN[1..16] 272
3.119 ALMOPT 273
3.120 ALMOUT 273
3.121 ALMPRI [0.. NUMALARMS-1] 274
3.122 ALMSELOPT 274
3.123 ALMSEQ 275
3.124 ALMSEV [0..NUMALARMS-1] 275

3.125 ALMSTR[0..NUMALARMS-1] 276


3.126 ALMTM 276
3.127 ALMWINTXT[1..32] 277
3.128 ALONEAV 278
3.129 ALTENBOPT 278
3.130 ALTSYNCCMD 279
3.131 AMCOMMAND 279
3.132 AMHI 280
3.133 AMLO 281
3.134 AMODULES 281
3.135 AMMODE 282
3.136 AMRESPTIME 282
3.137 AMSTATUS 283
3.138 ANYRESTARTFL 284
3.139 AOCHNLNAME 284
3.140 AOPTEXECST 285
3.141 APPIMAGETYPE 285
3.142 APPROVALS 286
3.143 AREVISION 286
3.144 ACTIVEARRPARAMWRITES 286
3.145 ACTIVENONARRPARAMWRITES 287
3.146 ArraySize 287
3.147 ARRINDEX 288
3.148 ARIBITRATIONSTATUS 288
3.149 ARWMULTOP[1..8] 289

- 212 -
Chapter 3 - Axxxx Parameters

3.150 ARWNET[1..8] 289


3.151 ARWNETIN 290
3.152 ARWNETIN[1..8] 291
3.153 ARWOP 291
3.154 ARWOPIN 292
3.155 ARWRATIO 292
3.156 ASACONNSTS 293
3.157 ASACONNSTS[0..7] 293
3.158 ASAERRCODE 294
3.159 ASAERRCODE[0..7] 294
3.160 ASAERRINFO 295
3.161 ASAERRINFO[0..7] 295
3.162 ASICVERA[1..8] 295
3.163 ASICVERB[1..8] 296

3.164 ASSIGNABLE 296


3.165 ASSOCASSET 297
3.166 ASSOCCHANNEL 297
3.167 ASSOCIOP 298
3.168 ASSOCIOPTYP 298
3.169 ASSOCGANGEDCHANNELS 299
3.170 ASSOCIATEDTREND 299
3.171 ASTEPID 300
3.172 ATLOADSTATE 300
3.173 AUTHOR 301
3.174 AUTHSERVERIPADDR 301
3.175 AUTHSTATE 302
3.176 AUTOBAUDDISABLE 302
3.177 AUTOCLOSE 303
3.178 AUTOMAN 303
3.179 AUTOMAN2 303
3.180 AUTOMATICPOINTIMPORT 304
3.181 AUTONOCMD 304
3.182 AUTOOPEN 305
3.183 AUTOPERIOD 305
3.184 AUTOPHASE 306
3.185 AUTOPUBLICNAME 306
3.186 AUTOSTART 307
3.187 AUTOSTOP 307
3.188 AUTOSTOPACTED 308

- 213 -
Chapter 3 - Axxxx Parameters

3.189 AUTOSYNCCMD 308


3.190 AUTOSYNCOPT 309
3.191 AUTOSYNCSTAT 309
3.192 AUTOTRIGGER 310
3.193 AUTOTRIGGERPERIOD 310
3.194 AUXCMD 311
3.195 AUXDATA[0..7] 311
3.196 AUXDESC 312
3.197 AUXDESC[0..10] 312
3.198 AUXMEM 313
3.199 AUXOPT 313
3.200 AUXREQ 314
3.201 AUXREQDATA[1..5] 314
3.202 AUXSTS 314

3.203 AUXUNIT 315


3.204 AV 315
3.205 AV[0..7] 316
3.206 AVAILFL 316
3.207 AVCONV 317
3.208 AVERSION 317
3.209 AVGDEPTH 318
3.210 AVGFLOWRATE[1..200] 318
3.211 AVGICPNAKS 319
3.212 AVGICPSENDS 319
3.213 AVGPKTRXRATE 320
3.214 AVGRCVBYTESPERSEC 320
3.215 AVGRCVMSGPERSEC 321
3.216 AVGRDRRESPONSETIMEUS 321
3.217 AVGSPILL[1..200] 321
3.218 AVGWRTIME 322
3.219 AVGXMITBYTESPERSEC 322
3.220 AVGXMITMSGPERSEC 323
3.221 AVRAW 323
3.222 AVRAW[0..7] 324
3.223 AVRAWSTS 324
3.224 AVSTS 325
3.225 AWAITINGACK[1..24] 326
3.226 AWAITINGACK[1..200] 326

- 214 -
Chapter 3 - Axxxx Parameters

3.1 ABBREV

Specific to Server
Block(s)
Description Abbreviation of server name - Used for operator change events
Data Type String
Range N/A
Default Null
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence SCAN
Related
Parameters
Remarks Abbreviation name is used when alarms are published to remote servers via DSA.
This allows a short name to be used in the alarm summary to represent the source
server for the alarm.

3.2 ABORTALM.FL

Specific to Block SCM


(s)
Description Abort Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related ABORTALM.PR, STATE
Parameters
Remarks When On, indicates that the Abort Alarm condition (SCM's STATE has
transitioned to Abort) exists.

- 215 -
Chapter 3 - Axxxx Parameters

3.3 ABORTALM.PR

Specific to Block(s) SCM


Description Abort State Alarm Priority - Specifies the alarm priority for the Abort alarm
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer/Application Developer
Residence CEE
Related Parameters ABORTALM.FL, ABORTALM.SV.
Remarks

3.4 ABORTALM.SV

Specific to Block(s) SCM


Description Abort State Alarm Severity - Specifies the alarm severity for the Abort
alarm.
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters ABORTALM.FL, ABORTALM.PR.
Remarks

3.5 ABORTLOCK

Specific to Block(s) SCM


Description Abort Command Access Lock
Data Type Enumeration CSCOACCLOCK
Range Engineer (0) Operator (1) OtherFB (2) ViewOnly (3) Supervisor (4)
Default Engineer (0)
Config Load Yes
Active Loadable No

- 216 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters COMMAND
Remarks Value of ABORTLOCK restricts who can issue the Abort command.

3.6 ACCDEV.FL[1..4]

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Accumulator Deviation Flag - Indicates when an accumulator deviation trip point
(ACCDEV.TP[1..4]) has been reached. There is one flag per trip point.
Data Type Boolean
`Range Off (0): ACCDEV.TP[n] is less than or equal to
ACCTV - PV
On (1): ACCDEV.TP[n] is greater than or equal to
ACCTV - PV
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACCDEV.TP[1..4], ACCTVFL, PV.
Parameters
Remarks The function block compares the actual deviation (ACCTV - PV) with each deviation
trip point (ACCDEV.TP[1..4]; It sets a flag (ACCDEV.FL[1..4]) when it is less than a
single trip point.

3.7 ACCDEV.TP[1..4]

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Accumulator Deviation Trip Point - Used to determine when the accumulated value
(PV) is getting “near” the target value (ACCTV). Trip point values are expressed as
deviations from the target value.
Data Type 64-Bit Real Number
Range NaN, or greater than or equal to 0.0.
Default NaN
Config Yes
Load
Active No
Loadable

- 217 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer


Residence CEE
Related ACCDEV.FL[1..4]ACCTVFLPV
Parameters
Remarks The function block compares the actual deviation (ACCTV - PV) with each deviation
trip point (ACCDEV.FL[1..4]), when it is less than a single trip point. ACCDEV.FL[n] is
set to On when ACCDEV.TP[n] is greater-than or equal to ACCTV-PV.

3.8 ACCEPTDEV

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) AICHANNEL and AOCHANNEL (Series
Block C I/O)
Description Accept Device ID
Data Type Boolean Push button
Range
Default Off
Config Load No
Active No
Loadable
Access Lock Operator
Residence IOLINK
Related HDEVIDFLHDEVIDHDEVIDCD[1..16]
Parameters
Remarks When ACCEPTDEV is pressed:
l HDEVID is copied to HDEVIDCD
l HDEVIDFL should also clear momentarily.
l Any pending notifications relating to HDEVIDFL are returned to normal.
To make the changes permanent, the user should update from the Monitoring
side to the Project side of Control Builder.

3.9 ACCEPTRNG

Specific to HAICHANNEL (PM I/O); AICHANNEL (Series C I/O)


Block
Description Accept Device Ranges. PV ranges are copied from the HART device to update the PV
ranges in the control system.
Data Type Boolean Push button
Range
Default Off
Config No
Load
Active No
Loadable

- 218 -
Chapter 3 - Axxxx Parameters

Access Lock Operator


Residence IOLINK
Related HPVCHAR
Parameters
Remarks When ACCEPTRNG is pressed:
l HTDURL is copied to PVEXEUHI
l HPVURV is copied to PVEUHI
l HTDLRL is copied to PVEXEULO
l HPVLRV is copied to PVEULO
These changes cause the PV ranges of the control system to match the PV ranges
of the attached HART device. To make the changes permanent, the user should
upload from the Monitoring side and update to Project in Control Builder.

3.10 ACCEPTSIMPEERDATA

Specific to Block(s) C300, UOC, CN100


Description Accept control data and enables use of peer from simulation platform
Data Type Boolean
Range On/Off
Default Off
Config Load Yes
Active Loadable Yes
Access Lock Engineer
Residence CEE
Related Parameters

Remarks

3.11 ACCESSLEVEL

Specific to CAB types


Block(s)
Description Access Level. CEs assign the instance default of parameter ACCESSLEVEL at the
time of creation of a CAB type. When a CAB program stores through a parameter
reference, the access level used for the store is the one specified by
ACCESSLEVEL. ACCESSLEVEL can be assigned to CAB types but cannot be
changed on CAB instances.
Modification The Attribute Instance Default can be modified at type creation time.
of Definition
Data Type Enumeration CABACCLEVEL
Range PROGRAM, CONTCONTROL
Default Assigned by CE on the type definition. See Note 1.
Config Load Yes

- 219 -
Chapter 3 - Axxxx Parameters

Active No
Loadable
Access Lock Type Definition Only
Residence CEE See Note 2.
Related None
Parameters
Remarks 1. When a CAB type is first created, the value “PROGRAM” is assigned as the
instance default of ACCESSLEVEL. CEs can change instance default to
“CONTCONTROL” if desired. The value of ACCESSLEVEL cannot be changed
on CAB instances.
2. In terms of normal parameter access, ACCESSLEVEL is resident in the CEE.
However, by the time a CAB instance is created in the CEE, the value of
ACCESSLEVEL is available to the code of the associated CAB program.

3.12 ACCTV

Specific to Block(s) Totalizer, Pulse Input Totalizer


Description Accumulator Target Value - Specifies the target value of the accumulator.
Data Type 64-Bit Real Number, 0
Range NaN, or greater-than or equal-to zero, Yes
Default 0, Operator
Config Load Yes, CEE
Active Loadable No
Access Lock Operator
Residence CEE, ACCTV is displayed as the set point of an Auxiliary function block.
Related Parameters ACCDEV.FL[1..4]ACCDEV.TP[1..4]ACCTVFLPV
Remarks ACCTV is displayed as the set point of an Auxiliary function block.

3.13 ACCTVFL

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Accumulated-Target-Value Reached Flag - The “target reached”flag for the
Totalizer function block. It indicates if the present variable (PV) has reached the
target value [ACCTV].
Data Type Boolean
Range Off (PV is less than ACCTV) On (PV is greater than or equal to ACCTV)
Default N/A
Config Load No
Active No
Loadable

- 220 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ACCDEV.TP[1..4]ACCTVPV
Parameters
Remarks

3.14 ACEMACADDR

Specific to ACE
Block(s)
Description ACE Media Access Control Address - Specifies the ControlNet address for the PCIC
card in the ACE node that will be used for peer-to-peer communication with Hybrid
Controllers.
Data Type 32-Bit Integer
Range 0 to 99
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence SR
Related CMLOADFLCNETCONNECT
Parameters
Remarks

3.15 ACEMEMINMB

Specific to Block(s) ACE


Description ACE Memory in Megabytes (MB)
Data Type Enumeration
Range 0 32MB
1 64MB
2 96MB
3 128MB
Default 32MB
Config Load Yes
Active Loadable No

- 221 -
Chapter 3 - Axxxx Parameters

Access Lock Application Developer Only


Residence SR
Related Parameters
Remarks

3.16 ACERDNROLE

Specific to
Block ACE
Description ACE Cut Over Role
Data Type ENUMERATION
(0) Undefined
(1) NonRedundant
(2) Primary
Range (3) Secondary
Default (2) Primary
Config Load No
Active
Loadable No
Access Lock AppDevOnly
Residence ACE
Related
Parameters

BlockExtn sets this parameter as "Primary" when you create ACE and as
"Secondary" when the migration tool creates backup ACE. During the switch-over,
the ACE role is changed and the parameter state is changed by RRM.

ATTENTION This parameter is ViewOnly for users.


Remarks

- 222 -
Chapter 3 - Axxxx Parameters

3.17 ACERMCONNSTS

Specific to
Block ACE
Description ACERM Connection Status
Data Type ENUMERATION
(0) NONREDUN
(1) NOTCONNECTED
(2) REGINPROG
(3) CONNINPROG
Range (4) CONNECTED
Default (1) NOTCONNECTED
Config
Load No
Active
Loadable Yes
Access Lock ViewOnly
Residence CEE
Related
Parameters

This parameter indicates the connection status between ACE and the ACERM.
When ACE is loaded the status is NONREDUN. When the cut-over is started the
registration is initiated from ACE to ACERM and stay connected till the end of the
Remarks cut-over.

3.18 ACK

Specific to Block ANNPANNEL


(s)
Description Operator Acknowledge
Data Type Boolean
Range ON/OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Operator
Residence CEE
Related FLSHSTAT
Parameters
Remarks On a raising edge transition, the Ack issued by the operator passes to the
Alarm Window.

- 223 -
Chapter 3 - Axxxx Parameters

3.19 ACQUIREOPT

Specific to Phase
Block(s)
Description Acquire Resource before Execution
Data Type Boolean
Range OFF (0) no resource acquisition will be initiated by this phase block ON (1) Resource
specified by EQUIPNAME will be acquired immediately after phase activation
Default ON (1)
Config Yes
Load
Access Lock AppDevOnly
Residence CEE
Related EQUIPNAME or EQUIPNAMEREF, TERMSTATEOPT
Parameters
Remarks Will be ignored (assumed to be OFF) if EQUIPNAME and EQUIPNAMEREF is NULL
Caution: If EQUIPNAME is not NULL and ACQUIREOPT=OFF the recipe may get
blocked, if the resource has not been acquired by another step or phase before or
will be acquired by another step or phase while this phase block is active.

3.20 ACQRESTYPE

Specific to Block(s) RCM


Description Acquired Resource block Type
Data Type Enumeration
Range 0 STEP
1 PHASE
2 UCM
3 SCM
4 RCM
Default UCM
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks

- 224 -
Chapter 3 - Axxxx Parameters

3.21 ACTARRWRITES

Specific to Block C300 CEE


(s)
Description Active arrayed writes
Data Type UINT16
Range 0-65
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related -
Parameters
Remarks Number of active arrayed writes in the EIM, initiated from one or more C300’s
through this EIM.

3.22 ACTAVAIL

Specific to All Blocks


Block(s)
Description Activity available
Data Type Boolean
Range ON/OFF
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUMACT, CURRNUMACT, MAXNUMACT, NUMACTCRFAIL, ACTAVAIL, NUMACTCR
Parameters
Remarks This parameter is a flag and allows a block to check if an Activity is available. This
parameter returns 0 if TOTALACTCAP equals CURRNUMACT, else it returns 1.

- 225 -
Chapter 3 - Axxxx Parameters

3.23 ACTCOMMAND

Specific to ACT
Block(s)
Description Activity command
Data Type Enumeration ACTCOMMAND
Range None (0) - No command is specified for the Activity Start (1) - Command the Activity
to the Executing stage Hold (2) - Hold the execution of the Activity Stop (3) - Stop
the execution of the Activity Abort (4) - Abort the execution of the Activity Remove (5)
- Remove the Activity
Default -
Config No
Load
Active No
Loadable
Access Operator
Lock
Residence CEE
Related ACTSTATE, EXECSTATE, MODEATTR
Parameters
Remarks Used by an operator to control the state of the activity. Commands will only be
processed when the CEE is running. Access to this parameter is controlled by the
activity mode attribute (MODEATTR) parameter. Remove - Remove this activity. A
valid command when the activity is in the initializing, pre-execution, post-execution,
or failed state. Start - Commands the activity or controlled object to the executing
state. A valid command when the activity is in the pre-execution or executing state.
Hold - Commands the controlled object to temporarily suspend execution. A valid
command when the activity is in the executing state. Abort - Commands the
controlled object into the abort state. A valid command when the activity is in the
executing state. Stop - Commands the controlled object to into the stop state. A valid
command when the activity is in the executing state.

3.24 ACTCREATETIME

Specific to ACT
Block(s)
Description Activity creation time
Data Type Time
Range -
Default 0
Config Load No
Active No
Loadable

- 226 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ACTEXECSTARTTIME, ACTEXECENDTTIME
Parameters
Remarks This parameter stores the Activity creation date and time in the controller in UTC
format. However, you can see the date and time in your local time format.

3.25 ACTCREATETYPE

Specific to ACT
Block(s)
Description Activity creation method
Data Type Enumeration ACTCREATE
Range None (0) - Activity is available AutoRun (1) - Associated with an auto-created Activity
AutoInitAndRun (2) - Initialize the Data block to the last loaded version Manual (3) -
Associated with a user-created Activity Child (4) - Associated with a child SCM/RCM
Default None
Config No
Load
Active -
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is an internal parameter.

3.26 ACTCRMIGOPT

Specific to CEE
Block(s)
Description Migration Options
Data Type Enumeration
Range Disabled
FORCEREMOVE
Default DISABLED
Config Yes
Load
Active No
Loadable

- 227 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer


Residence CEE
Related NUMACTCR
Parameters
Remarks This parameter specifies the controller migration options while Control Recipes
exist in the CEE. DISABLED: Controller migration is not allowed when executing
Control Recipes in the CEE (NUMACTCR>0). FORCEREMOVE: Allows you to proceed
with Controller On-Process Migration (OPM) when executing Control Recipes in the
CEE (NUMACTCR>0). However, all Control Recipes are removed after the OPM.

NOTE After the migration of the controller, ACTCRMIGOPT is in


DISABLED state even if the value prior to migration was FORCEREMOVE.
It is intended that the value of FORCEREMOVE may not be carried over
through a migration.

3.27 ACTENTITY

Specific to ACT
Block(s)
Description The loaded blocks from which the Activities are created.
Data Type BlockID
Range -
Default -
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Activities are created from the Activity Entities. Every single Activity is associated
with an Activity Entity. RCMs, SCMs, and Master Recipes can be Activity Entities.

3.28 ACTENTITYIOC

Specific to ACT
Block(s)
Description IOC of Activity entity
Data Type INT32
Range -
Default NULLIOC
Config Load No
Active No

- 228 -
Chapter 3 - Axxxx Parameters

Loadable
Access Lock ReadOnly
Residence CEE
Related
Parameters
Remarks This parameter is an internal parameter. It is used by the ERDB Controller
inconsistency checker. It returns the Activity entity's IOC. If there is no entity
associated with the Activity, the parameter returns a Null IOC.

3.29 ACTEXECENDTTIME

Specific to ACT
Block(s)
Description Activity end time
Data Type Time
Range -
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTCREATETIME, ACTEXECSTARTTIME
Parameters
Remarks This parameter stores the date and time when the Activity exits from the execution
state. The date and time is stored in the controller in UTC format. However, you can
see the date and time in your local time format.

3.30 ACTEXECSTARTTIME

Specific to ACT
Block(s)
Description Activity execution start time
Data Type Time
Range -
Default 0
Config Load No
Active No
Loadable

- 229 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ACTCREATETIME, ACTEXECENDTTIME
Parameters
Remarks This parameter stores the date and time when the Activity enters into the execution
state. The date and time is stored in the controller in UTC format. However, you can
see the date and time in your local time format.

3.31 ACTID

Specific to ACT
Block(s)
Description Activity Identification
Data Type UINT 64
Range -
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is an internal parameter. This ID is unique within the server (mainly all DSA
servers) and cannot be reused for a long period. The ID is independent of an
SCM/RCM execution ID.

3.32 ACTIVESCOPE

Specific to CEEC300, CEEUOC


Block(s)
Description Active Step Parameter Options
Data Type ENUM – ActiveFlBehaviour
Range CurrentOnly (0) - Pre-R310 behavior of the parameters
FullStack (1) - Post-R310 behavior of the parameters

Default CurrentOnly
Config Load Yes
Active No
Loadable

- 230 -
Chapter 3 - Axxxx Parameters

Access Application Developer


Lock
Residence CEE
Related ACTIVEFL, STATE, TIME, INSTRUCTCNFM
Parameters
Remarks With R310, an introduction of a new behavior modified the expected values of some
step parameters like ACTIVEFL, STATE, TIME, and INSTRUCTCNFM. This resulted in
change in behavior of strategies in which these parameters were used. To avoid this,
the ACTIVESCOPE parameter is introduced. This parameter enables you to select if
the affected parameters must behave as in pre-R310 or post-R310.

3.33 ACTNONARRWRITES

Specific to Block C300 CEE


(s)
Description Active non-array writes
Data Type UINT16
Range 0-135
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related -
Parameters
Remarks Number of active non-array writes in the EIM, initiated from one or more
C300’s through this EIM.

3.34 ACTOPT

Specific to RCM, SCM, MR


Block(s)
Description Activity creation option
Data Type Enumeration
Range OFF ON
Default OFF
Config Yes
Load
Active No
Loadable

- 231 -
Chapter 3 - Axxxx Parameters

Access Lock APPDEVONLY


Residence CEE
Related
Parameters
Remarks This parameter provides you the following options for Activity creation:
l None - When this option is selected, no Activity is created.
l Auto - When this option is selected, an Activity is automatically created when
you provide the START command to an RCM or an SCM. The Activity retains
the current formula/report parameter values of the RCM or the SCM. This
option is unavailable for an MR block.
l User or App - When this option is selected, an Activity can be created by you or
an external application. The RCM or SCM appears in the Activity Entity list.
lAll - When this option is selected, an Activity can be created automatically or
on-demand by any external application. This option is unavailable for an MR
block.
In a layered recipe configuration, creation of an Activity for a child RCM, SCM, or
MR is determined by the configuration option specified for a parent RCM, SCM, or
MR. Note: For migrated SCM or RCM, the default value is None.

3.35 ACTPARENT

Specific to ACT
Block(s)
Description Activity's parent
Data Type BlockID
Range -
Default Nil
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter is an internal parameter and is only available for child Activities.
This parameter displays the name of the parent Activity.

3.36 ACTREMOVETYPE

Specific to ACT
Block(s)
Description Activity removal method
Data Type Enumeration ACTREMOVE
Range l Automatic (1) - The Activity is automatically deleted when the execution of the

- 232 -
Chapter 3 - Axxxx Parameters

underlying entity (RCM/SCM/CR) reaches a terminal state and is reset.


l User or App (2) - You need to issue REMOVE command to the Activity to
remove it.
Default For auto-created and child activities, the default remove type is automatic. For
user-created activities, the default remove type is pulled from the Batch
Preferences tab.
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related ACTCREATETYPE
Parameters
Remarks This parameter can be adjusted for each manually created Activity through the
Activity Data UI after an Activity is created.

3.37 ACTSTATE

Specific to ACT
Block(s)
Description Current stage of the Activity
Data Type Enumeration ActivityState
Range Available (0) - Activity is not in use Init (1) - Activity is initializing Pre-Exec (8) - Pre
execution Executing (16) - The acquired object is allowed to execute Post-Exec (24)
- Post execution Failed (5) - Failed
Default Available
Config No
Load
Active
Loadable

- 233 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ACTSTATE, EXECSTATE STATE
Parameters
Remarks Different stages of the Activity:
l Available - In this state, Activity is not in use and can be assigned.
l When a CEE is configured, a number of activities are allocated. This
number is configurable on the CEE form. An Activity in the available
state is ready to respond to a request for creating a new Activity.

l Initializing - This is a transient state. In this stage, the Activity responds to a


request to be created. During this state, an Activity attempts to acquire
memory in the controller for the associated Data block and initialize the Data
block to the loaded values for the associated SCM/RCM (when
PARAMINIT=ON). This stage is not applicable for auto-created Activities.
l Pre-Exec - In this stage, the formula/report parameters in the Data block can
be viewed. The values of the adjustable parameters can be changed. The new
values can be used when the activity runs. You can issue a START command
to a pre-exec activity to start the execution. This stage is not applicable to auto-
created Activities.
l Executing - In this stage, the Activity represents the execution of its underlying
entity (RCM, SCM, or Control recipe). The STATE parameter of the Activity
reflects the state of the underlying RCM, SCM, or Control recipe, which can be
one of the following states:
l Transient : Running, Restarting, Interrupting, Stopping, Holding,
Starting, and Aborting
l Quiescent : Held and Stopped
l Terminal : Complete, Stopped, and Aborted

l Post-Exec - In this stage, the Activity is detached from the underlying entity
(SCM/RCM/Control recipe). The formula/report parameter values are
captured by the Data block of the Activity. You can enter or review the report
parameter values. For auto-created and auto-removal Activities, this stage is
transient and is not visible.
l Failed - This state indicates that an error has occurred and you cannot recover
the Activity automatically.
l Refer to the SCM STATE transition diagram in the SCM STATE and COMMAND
interaction in the Sequential Control Module User's Guide for additional
information.

3.38 ACQONBEHALF

Specific to MR and SCM


Block(s)
Description Acquire on behalf option
Data Type ENUM
Range Self Parent
Default Self
Config Yes
Load

- 234 -
Chapter 3 - Axxxx Parameters

Active No
Loadable
Access Lock APPDEVONLY
Residence NOLOAD
Related
Parameters
Remarks If you configure this parameter for SCM/MR, it allows a Control recipe or an SCM to
acquire resources (Units, UCMs, SCMs, or common devices) on behalf of a running
object (Self) or on behalf of a Parent that is passed in at run time.

3.39 ACQSTATE

Specific to PHASE
Block(s)
Description Acquisition State
Data Type Enumeration (ACQSTATE)
Range 0 NONE
1 ACQUIRING Requester is
attempting to
acquire the
resource
2 ACQUIRED Requester
owns the
resource
3 RELEASING Requester is
attempting to
release the
resource
4 ERROR An error
occurred; for
example,
resource was
deleted and
reloaded.
Default NONE (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related
Parameters
Remarks Note that even in the ACQUIRED state other
requesters may own the same resource, if
Resource.MAXOWNERS is greater than 1. If ACQSTATE
equals ERROR: The resource needs to be re-acquired
or released to recover from the error.

- 235 -
Chapter 3 - Axxxx Parameters

3.40 ACTIVEDATE

Specific to Block(s) RCM


Description Active Date
Data Type Time
Range
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

3.41 ACTIVEFL

Specific to Block(s) Step


Description Step Active Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks Indicates if Step is currently active (On) or not (Off).

3.42 ACTIVEHANDLR[1..8]

Specific to SCM
Block(s)
Description Active Handler Type Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No

- 236 -
Chapter 3 - Axxxx Parameters

Loadable
Access Lock ViewOnly
Residence CEE
Related ACTIVELOC.HANDLER, ACTIVELOC.HANDLERN, ACTIVELOC.HNDTYPE,
Parameters ACTIVELOC.STEP[1..15], ACTIVELOC.STEPN[1..15], ACTIVELOC.TIME[1..15], TYPE.
Remarks There are eight different handler types, corresponding to the following numeric
values: 1 = EDIT (not user definable) 2 = MAIN 3 = CHECK 4 = INTERRUPT 5 =
RESTART 6 = HOLD 7 = STOP 8 = ABORT For example, if ACTIVEHANDLR[5] = On,
then the currently active handler is of type RESTART. ACTIVEHANDLR[I] flag is On
when the currently active handler is TYPE i.

3.43 ACTIVELOC.HANDLER

Specific to SCM
Block(s)
Description Active Handler Name
Data Type BlockId
Range N/A
Default Null String
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTIVELOC.HANDLERN
Parameters
Remarks Contains the name (for example, SCMName.HandlerName) of the currently active
handler. ACTIVELOC.HANDLER is a BlockId parameter and not supported in
expressions. Its Integer-32 Partner Parameter ACTIVELOC.HANDLERN can be used
in Transition Condition expressions and Step Output expressions.

3.44 ACTIVELOC.HANDLERN

Specific to SCM
Block(s)
Description Active Handler Name
Data Type 32-Bit Integer
Range N/A
Default Null String
Config No
Load
Active No
Loadable

- 237 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ACTIVELOC.HANDLER
Parameters
Remarks Contains the name (for example, SCMName.HandlerName) of the currently active
handler. ACTIVELOC.HANDLERN may be used in Transition Condition expressions
and Step Output expressions, whereas ACTIVELOC.HANDLER (a BlockId
parameter) is not supported in expressions.

3.45 ACTIVELOC.HNDTYPE

Specific to Block(s) SCM


Description Active Handler Type
Data Type 32-Bit Integer
Range 0 to 8
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters TYPE
Remarks

3.46 ACTIVELOC.STEP[1..15]

Specific to SCM
Block(s)
Description Active Step Name
Data Type BlockId
Range N/A
Default Null String
Config No
Load
Active No
Loadable

- 238 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ACTIVELOC.STEPN[1..15]
Parameters
Remarks ACTIVELOC.STEP[i] contains the currently active step's name (for example,
SCMName.StepName). In release R110, i must be 1. ACTIVELOC.STEP[1..15] is a
BlockId parameter and not supported in expressions. Its Integer-32 Partner
Parameter ACTIVELOC.STEPN[1..15] can be used in Transition Condition
expressions and Step Output expressions.

3.47 ACTIVELOC.STEPN[1..15]

Specific to SCM
Block(s)
Description Active Step Name
Data Type 32-Bit Integer
Range N/A
Default Null String
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTIVELOC.STEP[1..15]
Parameters
Remarks ACTIVELOC.STEP[i] contains the currently active step's name (for example,
SCMName.StepName). In release R110, i must be 1. ACTIVELOC.STEPN[1..15] may
be used in Transition Condition expressions and Step Output expressions, whereas
ACTIVELOC.STEP[1..15] (a BlockId parameter) is not supported in expressions.

3.48 ACTIVELOC.STEPICOMP[1..15]

Specific to SCM
Block(s)
Description Active Step Instructions Complete
Data Type Boolean
Range Off - Instruction(s) are not complete On - Instruction(s) are complete
Default Off
Config No
Load
Active No
Loadable

- 239 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ACTIVELOC.STEPIPEND[1..15]ACTIVELOC.STEP[1..15] and other ACTIVELOC.XXX
Parameters parameters
Remarks ACTIVELOC.STEPICOMP[1] Indicates the Instruction completion status of the Active
Step identified by ACTIVELOC.STEP[1]. For a Step without Instructions, this value
will be One. Array size of 10 anticipates support of parallel Step execution (planned
for the Mercury release). Currently only element 1 is valid.

3.49 ACTIVELOC.STEPIPEND[1..15]

Specific to SCM
Block(s)
Description Active Step Instruction Pending
Data Type Boolean
Range Off - Instruction(s) are not pending On - Instruction(s) are pending
Default Off
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTIVELOC.STEPICOMP[1..15]ACTIVELOC.STEP[1..15] and other ACTIVELOC.XXX
Parameters parameters
Remarks When On, ACTIVELOC.STEPIPEND[1] indicates that the Active Step identified by
ACTIVELOC.STEP[1] currently has an Instruction pending that requires operator
interaction. For a Step without Instructions, this value will be Off. Array size of 10
anticipates support of parallel Step execution (planned for the Mercury release).
Currently only element 1 is valid.

3.50 ACTIVELOC.TIME[1..15]

Specific to Block SCM


(s)
Description Active Step Time
Data Type 32-Bit Integer
Range 0 to 2147483647
Default 0
Config Load No
Active Loadable No

- 240 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ACTIVELOC.STEP[1..15], PENABLE[1..10], PERIOD
Parameters
Remarks ACTIVELOC.TIME[i] contains the number of execution cycles that the current
step has been active.

3.51 ACTIVELOCOCD

Specific to Block(s) SCM


Description Active Location Checkpoint Data
Data Type STRUCTDATA
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

3.52 ACTIVEARRPARAMWRITES

Specific to Block PB_EIP, CEEC300, CEEUOC


(s)
Description Active Arrayed Param Writes
Data Type UINT16
Range 0-325
Default 0

Config Load No

Active Loadable No
Access Lock ViewOnly
Residence No Load

Related -
Parameters
Remarks Number of arrayed tag/parameter writes currently active in this EIM, initiated from
one or more C300’s.

- 241 -
Chapter 3 - Axxxx Parameters

3.53 ACTIVENONARRPARAMWRITES

Specific to PB_EIP, CEEC300, CEEUOC


Block(s)
Description Active Non-Arrayed Param Writes
Data Type UINT16
Range 0-675
Default 0

Config Load No

Active No
Loadable
Access Lock ViewOnly
Residence No Load

Related -
Parameters
Remarks Number of non-arrayed tag/parameter writes currently active in this EIM, initiated
from one or more C300’s.

3.54 ACTPARENTLOOKUP

Specific to ACT
Block(s)
Description Displays the ClusterID, EEC, and IOC of the parent Activities.
Data Type String
Range 20 characters
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTPARENT
Parameters
Remarks It is a parameter which is used in custom graphic to display the Cluster ID, EEC,
and IOC of the parent Activities in the following format: ClusterID, EEC, IOC.

- 242 -
Chapter 3 - Axxxx Parameters

3.55 ACTPRIM[1..40]

Specific to IOLINK, C300 IOLINK


Block(s)
Description Acting Primary I/O Module. Defines the acting primary Input/Output Processor
(IOP), where the index of this array corresponds to the number of the IOP.
Data Type Enumeration
Range IOP_B (0): IOP B is the acting primary.
IOP_A (1): IOP A is the acting primary.
--- (2): IOP is not configured.
Default IOP_A (1)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks Applies to primary IOP only. Note that this is the same as the ACTPRIM parameter
in a TPS system.

3.56 ACTRAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK]

Specific to RampSoak
Block(s)
Description Actual Ramp Rate (in EUs per min) - There is one ramp rate per Ramp/Soak pair of
each profile.
Data Type Real
Range N/A
Default NaN
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTSOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK], ACTSOAKVAL
Parameters [1..NUMPROFILES][1..NUMRAMPSOAK], ACTSTARTOP[1..NUMPROFILES],
ACTSTARTSEG[1..NUMPROFILES], NUMPROFILES, NUMRAMPSOAK
[1..NUMPROFILES]
Remarks The actual rate is calculated after a ramp segment completes. There is one ramp
rate per Ramp/Soak pair.

- 243 -
Chapter 3 - Axxxx Parameters

3.57 ACTSOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK]

Specific to RampSoak
Block(s)
Description Actual Soak Time (in Minutes) - There is one soak time per Ramp/Soak pair.
Data Type Real
Range 0.0 to 7200.0
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTRAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK]ACTSOAKVAL
Parameters [1..NUMPROFILES][1..NUMRAMPSOAK], ACTSTARTOP[1..NUMPROFILES],
ACTSTARTSEG[1..NUMPROFILES], NUMPROFILES, NUMRAMPSOAK
[1..NUMPROFILES]
Remarks The actual time is recorded after a soak segment completes. There is one soak time
per Ramp/Soak pair of each profile.

3.58 ACTSOAKVAL[1..NUMPROFILES][1..NUMRAMPSOAK]

Specific to RampSoak
Block(s)
Description Actual Soak Value - There is one soak value per Ramp/Soak pair.
Data Type Real
Range N/A
Default NaN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTRAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK]ACTSOAKTIME
Parameters [1..NUMPROFILES][1..NUMRAMPSOAK]ACTSTARTOP
[1..NUMPROFILES]ACTSTARTSEG[1..NUMPROFILES]NUMRAMPSOAK
[1..NUMPROFILES]
Remarks The actual value is recorded after a ramp segment completes (and the soak
segment begins). There is one soak value per Ramp/Soak pair of each profile.

- 244 -
Chapter 3 - Axxxx Parameters

3.59 ACTSTARTOP[1..NUMPROFILES]

Specific to RampSoak
Block(s)
Description Actual Starting Output Value
Data Type Real
Range N/A
Default 0
Config ViewOnly
Load
Active No
Loadable
Access Lock No
Residence CEE
Related ACTRAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK]ACTSOAKTIME
Parameters [1..NUMPROFILES][1..NUMRAMPSOAK]ACTSOAKVAL[1..NUMPROFILES]
[1..NUMRAMPSOAK]ACTSTARTSEG
[1..NUMPROFILES]NUMPROFILESNUMRAMPSOAK[1..NUMPROFILES]
Remarks

3.60 ACTSTARTSEG[1..NUMPROFILES]

Specific to RampSoak
Block(s)
Description Actual Starting Segment ID
Data Type Real
Range N/A
Default 0
Config ViewOnly
Load
Active No
Loadable
Access Lock No
Residence CEE
Related ACTRAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK]ACTSOAKTIME
Parameters [1..NUMPROFILES][1..NUMRAMPSOAK]ACTSOAKVAL[1..NUMPROFILES]
[1..NUMRAMPSOAK]ACTSTARTOP
[1..NUMPROFILES]NUMPROFILESNUMRAMPSOAK[1..NUMPROFILES]
Remarks

- 245 -
Chapter 3 - Axxxx Parameters

3.61 ACTTYPE

Specific to ACT, SCM, RCM, and MR


Block(s)
Description Type of Activity
Data Type Enumeration Activity
Range Batch Procedure
Default Batch - For RCMs and MRs Procedure - For SCM
Config Load No - For ACT block Yes - For SCM, RCM, and MR blocks
Active No - For SCM, RCM, and MR blocks N/A - For ACT block
Loadable
Access Lock ViewOnly - For ACT AppDevOnly - For SCM, RCM, and MR
Residence CEE, SR
Related ACTCREATETYPE
Parameters
Remarks This parameter is configured with the Activity Entities (RCMs, SCMs, and MRs). It
determines the type of Activities created from the Activity Entity.

3.62 ACTUALPROVERSIGNAL

Specific to Series C PI
Block(s)
Description Actual Prover Signal
Data Type UINT8
Range 0, 1, 3, 5, 7
Default 0
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence IOM
Related CONFIGPROVERSIGNALMAINTAINONFAULT
Parameters
Remarks This parameter provides the user or a program the actual signal stream being
output to the prover signal screw pair. The only valid values returned are: 0 - No
stream is selected 1 - Good pulses from the dual stream present on channel 1 and
channel 2 are being output to the prover signal screw pair. 3 - Good pulses from the
dual stream present on channel 3 and channel 4 are being output to the prover
signal screw pair. 5 - Good pulses from the dual stream present on channel 5 and
channel 6 are being output to the prover signal screw pair. 7 - Good pulses from the
dual stream present on channel 7 and channel 8 are being output to the prover
signal screw pair.

- 246 -
Chapter 3 - Axxxx Parameters

3.63 ACTUALSCANTIME

Specific to Block(s) TCMI


Description Actual Scan Time (ms)
Data Type FLOAT64
Range N/A
Default 0.0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

3.64 ACTVTNTIME

Specific to Block(s) Step


Description Activation Time
Data Type Integer
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

3.65 ACTWRITEALLOCFAIL

Specific to Block(s) PB_EIP, CEEC300, CEEUOC

Description Active Write Alloc Failures


Data Type UINT16
Range >=0
Default 0

Config Load No

Active Loadable No

- 247 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence No Load

Related -
Parameters
Remarks Number of write allocation failures in the EIM due to unavailability of write tag
resources.

3.66 ADDRCOUNT

Specific to Block(s) TCMI


Description Address Count
Data Type UINT32
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

3.67 ADVALARM_ACTIVE_ALARMS

Specific to Block(s) FF Device


Description Advanced Alarm Active Conditions
Data Type BITSTRING
Range 32 bits
Default 0
Config Load NOLOAD
Active Loadable No
Access Lock ViewOnly
Residence ERDB
Related Parameters No
Remarks

- 248 -
Chapter 3 - Axxxx Parameters

3.68 ADVALARM_ACTUAL_VALUE [0...4] [0...31]

Specific to Block(s) FF Device


Description Advanced Alarm Actual Value
Data Type UINT32
Range 0x0 to 0xFFFFFFFF [Hex value]
Default 0
Config Load NONE
Active Loadable No
Access Lock ViewOnly
Residence ERDB
Related Parameters
Remarks

3.69 ADVALARM_COND_ASSOCALARM [0...31]

Specific to Block(s) FF Device


Description Alarm(s) associated with the alarm condition
Data Type BITSTRING
Range 8 Bits
Default 0x0000
Config Load PCM
Active Loadable No
Access Lock Engineer
Residence FIM, ERDB
Related Parameters
Remarks

3.70 ADVALARM_COND_NAME [0...31]

Specific to Block(s) FF Device


Description Alarm Condition Name
Data Type STRING
Range 40 characters string
Default NULL
Config Load SR
Active Loadable No

- 249 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer


Residence SR, ERDB
Related Parameters
Remarks

3.71 ADVALARM_ENABLE [0...31]

Specific to Block(s) FF Device


Description Advanced Alarm Detection Enable
Data Type BOOLEAN
Range TRUE or FALSE
Default TRUE
Config Load PCM
Active Loadable No
Access Lock Engineer
Residence FIM, ERDB
Related Parameters
Remarks

3.72 ADVALARM_NUM_CONFCOND

Specific to Block(s) FF Device


Description Number of Alarm Conditions configured for the FF device
Data Type INT16
Range 0 to (+/-) 32767
Default 0
Config Load ERDBONLY
Active Loadable No
Access Lock Engineer
Residence ERDB
Related Parameters
Remarks

- 250 -
Chapter 3 - Axxxx Parameters

3.73 ADVALARM_PARREF_BITS [0...4] [0...31]

Specific to FF Device
Block(s)
Description A bitmap that indicates which bits in the device parameter will be used to
generate the corresponding alarm.
Data Type UINT32
Range 0x0 to 0xFFFFFFFF [Hex value]
Default 0
Config Load PCM
Active No
Loadable
Access Lock Engineer
Residence FIM, ERDB
Related
Parameters
Remarks

3.74 ADVALARM_PARREF_BLOCK [0...4] [0...31]

Specific to
Block(s)
Description This is the ID of the block that contains the parameter to be monitored. This will
be the OD index of the block.
Data Type UINT16
Range 0x0 to 0xFFFF [Hex value]
Default 0
Config Load SR
Active No
Loadable
Access Lock Engineer
Residence SR, ERDB
Related
Parameters
Remarks

- 251 -
Chapter 3 - Axxxx Parameters

3.75 ADVALARM_PARREF_PARAM [0...4] [0...31]

Specific to FF Device
Block(s)
Description This value identifies the parameter within the device. The value will be the
absolute OD index of the parameter.
Data Type UINT16
Range 0x0 to 0xFFFF [Hex value]
Default 0
Config Load PCM
Active No
Loadable
Access Lock Engineer
Residence FIM, ERDB
Related
Parameters
Remarks

3.76 ADVALARM_PARREF_SUBINDEX [0...4] [0...31]

Specific to FF Device
Block(s)
Description If the parameter is a structure or array, this value specifies the sub-index of the
field or array element to be monitored
Data Type UINT8
Range 0x0 to 0xFF [Hex value]
Default 0
Config Load PCM
Active No
Loadable
Access Lock Engineer
Residence FIM, ERDB
Related
Parameters
Remarks

- 252 -
Chapter 3 - Axxxx Parameters

3.77 ADVALARM_PRIORITY [0...31]

Specific to Block(s) FF Device


Description Enum value for each Alarm priority
Data Type ENUM
Range 0 to 3
Default NONE
Config Load PCM
Active Loadable No
Access Lock Engineer
Residence FIM, ERDB
Related Parameters
Remarks Enum value for each Alarm-criticality and priority

3.78 ADVALARM_REFERED_BLOCK_ID [0...4] [0...31]

Specific to Block(s) FF Device


Description Block ID referred in condition configuration
Data Type String
Range
Default NULL
Config Load ERDBONLY
Active Loadable No
Access Lock Engineer
Residence ERDB
Related Parameters
Remarks

3.79 ADVALARM_REFERED_PARAM_ID [0...4] [0...31]

Specific to Block(s) FF Device


Description Param ID referred to configure condition
Data Type String
Range
Default NULL
Config Load ERDBONLY
Active Loadable No

- 253 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer


Residence ERDB
Related Parameters
Remarks

3.80 ADVALARM_STALE_DATA

Specific to Block(s) FF Device


Description Advanced Alarm Stale Data Exist
Data Type BOOLEAN
Range TRUE or FALSE
Default FALSE
Config Load NONE
Active Loadable No
Access Lock ViewOnly
Residence ERDB
Related Parameters
Remarks

3.81 ADVALARM_UPDATED_OD_IDX

Specific to Block(s) FF Device


Description Flag to identify the block od index updation during condition configuration
Data Type BOOLEAN
Range TRUE or FALSE
Default FALSE
Config Load ERDBONLY
Active Loadable No
Access Lock Engineer
Residence ERDB
Related Parameters
Remarks

- 254 -
Chapter 3 - Axxxx Parameters

3.82 ADVDEVALM.DB

Specific to PID, PIDFF, PID-PL, PosProp


Block(s)
Description Advisory Deviation Alarm Deadband
Data Type 64-Bit Real Number
Range 0.0 to 100.0 if alarm deadband units (ADVDEVALM.DBU) are Percent Greater-than
or equal-to 0.0 if alarm deadband units (ADVDEVALM.DBU) are Engineering Units
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related ADVDEVALM.DBU
Parameters
Remarks For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

3.83 ADVDEVALM.DBU

Specific to PID, PIDFF, PID-PL, PosProp


Block(s)
Description Advisory Deviation Alarm Deadband Units - Indicates if ADVDEVALM.DB is in
Percent or Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU(1)
Default Percent (0)
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related ADVDEVALM.DB
Parameters
Remarks For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 255 -
Chapter 3 - Axxxx Parameters

3.84 ADVDEVALM.FL

Specific to Block(s) PID, PIDFF, PID-PL, PosProp


Description Advisory Deviation Alarm Flag - Indicates if an advisory alarm has been
detected
Data Type Boolean
Range Off (0) (not in Advisory Deviation alarm) On (1) (in Advisory Deviation alarm
condition)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

3.85 ADVDEVALM.PR

Specific to Block(s) PID, PIDFF, PID-PL, PosProp


Description Advisory Deviation Alarm Priority - Defines the priority of an advisory
deviation alarm.
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

3.86 ADVDEVALM.SV

Specific to Block(s) PID, PIDFF, PID-PL, PosProp


Description Advisory Deviation Alarm Severity
Data Type 16-Bit Integer
Range 0 to 255
Default 0

- 256 -
Chapter 3 - Axxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

3.87 ADVDEVALM.TM

Specific to PID, PIDFF, PID-PL, PosProp


Block(s)
Description Advisory Deviation Alarm Filter Time (in seconds) - The purpose of this variable is to
prevent input spikes from causing alarms.
Data Type DeltaTime
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related ADVDEVALM.TP
Parameters
Remarks If ADVDEVALM.TM equals zero, an alarm will be generated as soon as the advisory
deviation exceeds the trip point. For more information about alarm configuration,
refer to Control Builder Components Theory Guide.

3.88 ADVDEVALM.TMO

Specific to Block PID, PIDER, PIDFF, PID-PL, PosProp, RATIOCTL


(s)
Description Advisory Deviation Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable

- 257 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for Advisory
Deviation Alarm.

3.89 ADVDEVALM.TP

Specific to PID, PIDFF, PID-PL, PosProp


Block(s)
Description Advisory Deviation Alarm Trip Point (in Engineering Units) - An alarm will be
generated when the difference between the process variable (PV) and Advisory
Setpoint value (ADVSP) exceeds the value in this variable.
Data Type 64-Bit Real Number
Range NaN, or greater-than or equal-to zero.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related ADVSP, PV,
Parameters
Remarks Alarm generation requires [PV - ADVSP] > ADVDEVALM.TP

3.90 ADVDEVOPT

Specific to PID, PIDFF, PID-PL, PosProp


Block(s)
Description Advisory Deviation Option - Indicates if advisory deviation alarming is requested.
Data Type Enumeration ENBSTATE
Range Enable (0): Advisory deviation alarming is requested Disable (1): Advisory
deviation alarming is not requested
Default Enable (0)
Config Load Yes
Active No
Loadable

- 258 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks

3.91 ADVSP

Specific to Block(s) PID, PIDFF, PID-PL, PosProp


Description Advisory Setpoint Value (in Engineering Units)
Data Type 64-Bit Real Number
Range SPLOLM to SPHILM
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters ADVSPP
Remarks

3.92 ADVSPP

Specific to Block(s) PID, PIDFF, PID-PL, PosProp


Description Advisory Setpoint Value (in Percent)
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters ADVSP
Remarks

- 259 -
Chapter 3 - Axxxx Parameters

3.93 AICHNLNAME

Specific to Universal IO module


Block(s)
Description Channel Name ??? Displays the channel names in the AI Status tab of the UIO
module.
Data Type String
Range Length: 16 characters
Default
Config No
Load
Access Lock ViewOnly
Active No
Loadable
Residence SR
Related CHNLNAMEAOCHNLNAMEDICHNLNAMEDOCHNLNAME
Parameters
Remarks This parameter identifies the configured name of the channels associated with this
IOM block. It is used to display the channel names on AI Status Data tab. This
parameter displays only the channel names configured with the PNTTYPE of AI.

3.94 AIHASENAME

Specific to CB and EC
Blocks
Description AI HASE Name
Data Type BLOCKID
Range
Default
Config. No
Load
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter displays the algorithm HRB name along with the HASE name
configured for the slot represented by the index. The format is
HASENAME.ALGOHRBNAME.

- 260 -
Chapter 3 - Axxxx Parameters

3.95 AIPTEXECST

Specific to Universal IO module


Block(s)
Description Point Execution State - Displays the point execution state in the AI Status tab of the
UIO module.
Data Type Enumeration
Range 0 Inactive Point is not scanned or
processed.
1 Active Point is scanned and
processed.
Default Inactive
Config Load No
Access Lock ViewOnly
Active No
Loadable
Residence IOM
Related PTEXECSTAOPTEXECSTDIPTEXECSTDOPTEXECST
Parameters
Remarks This parameter displays the point execution state of UIO module in the AI Status
Data tab. When PTEXECST is Inactive, the point processing does not occur for the
channel.

3.96 AIREGISTERED[ ]

Specific to CB
Blocks
Description AI Registered
Data Type BOOLEAN
Range TRUE or FALSE
Default FALSE
Config. Load No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter will be checked if the RVAI algorithm HRB configured in slot is
registered with the Box HRB

- 261 -
Chapter 3 - Axxxx Parameters

3.97 ALERTTIMEOUT

Specific to Step
Block(s)
Description Alert Timeout in minutes
Data Type 64-Bit Real Number
Range 0.0 to 1092.25
Default 1.0
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks The minimum value that can be entered is one (1). The value gets rounded up to
the nearest integer value. For example, if you enter 0.12 as the value, it gets
rounded up to 1. If the alert timeout duration is exceeded for conformational
instruction of STEP block in a SCM/RCM, an alarm is generated which can be seen
in the Alarm Summary display on Station.

3.98 ALFMT

Specific to Block(s) HRBALG_PIUAI


Description Alarm Format
Data Type ENUM
Range ALFMT00 ALFMT01
Default PV
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters -
Remarks This parameter represents the enumerations defined in the HRB Algo box.

- 262 -
Chapter 3 - Axxxx Parameters

3.99 ALGOPROCSTATE

Specific to All Algorithm Hiway Responder blocks


Blocks
Description Algorithm Processing State
Data Type Enumeration
Range 0 Full – Hiway Gateway (HG) read write is allowed. Hiway Responder Block (HRB)
is fully functional.

NOTE For more information about HRB, refer to Hiway Responder


Block (HRB) in the Control Builder Components Reference guide.

1 –Partial– HG read write does not happen in this state. This state has been
reserved for future use.
2 – Dormant – In this state HRB does not execute and is not functional at all. This
state has been reserved for future use.
Default 0 — Full
Config. Load No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks This parameter is always Full in R431.1. Partial and Dormant states are not
implemented and are reserved for future use.

3.100 ALGOREGSTATE

Specific to HRBALG_REG block HRBALG_PIUAI, HRBALG_HLPIUAO, HRBALG_HLPIUDI,


Blocks HRBALG_HLPIUDO, HRBALG_HLPIUCO, HRBALG_HLPIUAC, HRBALG_HLPIUDC
Description Algorithm Registration State
Data Type Enumeration
Range 0 Created 3 RegistrationFail
1 UnRegistered 4 RegistrationOk
2 ConfigLoadFail 5 LoadFail
Default 0 Created
Config. No
Load
Active No
Loadable

- 263 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related BOXCON
Parameters
Remarks This parameter displays the registration stateof the algorithm.

3.101 ALGOTYPE

Specific to HRBALG_REG block


Blocks
Description Algorithm type
Data Type Enumeration

Default 1 PIDNORM
Config. Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter is updated after the load of Hiway Algorithm Slot Emulation
(HASE) and contains the type of the algorithm.

3.102 ALIAS[ ].ALL

Specific to Block(s) SCM, RCM


Description The base nested parameter for alias.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters NUMACTNUMADJPARAMSNUMALIASES
Remarks Internal parameter sized by NUMALIASES.

- 264 -
Chapter 3 - Axxxx Parameters

3.103 ALIAS[ ].STATUS

Specific to Block(s) SCM, RCM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

3.104 ALIAS[ ].VALUE

Specific to Block(s) SCM, RCM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

3.105 ALIASBLKTYP[ ]

Specific to Block(s) SCM, RCM


Description Block type of the aliases defined in the Alias Table.
Data Type 16-Bit Integer (Template ID)
Range
Default N/A
Config Load Yes
Active Loadable No

- 265 -
Chapter 3 - Axxxx Parameters

Access Lock Application Developer


Residence ERDB
Related Parameters NUMACTNUMADJPARAMSNUMALIASES
Remarks Sized by NUMALIASES.

3.106 ALIASDATATYP[ ]

Specific to Block(s) SCM, RCM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

3.107 ALIASOPT

Specific to SCM, RCM


Block(s)
Description Alias Table Option - Defines whether or not an Alias Table will be configured in
the SCM.
Data Type Boolean
Range False (0) True (1)
Default False (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence ERDB
Related
Parameters
Remarks If ALIASOPT is configured to False, all the alias parameters will not be exposed in
the SCM/RCM configuration form.

- 266 -
Chapter 3 - Axxxx Parameters

3.108 ALIASPRMTYP[ ]

Specific to Block(s) SCM, RCM


Description Parameter type of the aliases defined in the Alias Table.
Data Type 16-Bit Integer (Param ID)
Range
Default N/A
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence ERDB
Related Parameters NUMACTNUMADJPARAMSNUMALIASES
Remarks Sized by NUMALIASES.

3.109 ALIASREF[ ][ ]

Specific to Block(s) SCM, RCM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

3.110 ALIASSRC[ ][ ]

Specific to Block(s) SCM, RCM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No

- 267 -
Chapter 3 - Axxxx Parameters

Access Lock
Residence
Related Parameters
Remarks

3.111 ALLEVTJRNLD

Specific to Block(s) RCM


Description All Events have been Journaled
Data Type Boolean
Range True False
Default Default (0)
Config Load True
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

3.112 ALLOWNAN

Specific to RCM
Block(s)
Description Allow NaN despite strong range check
Data Type enum
Range Default (0) reserved for future use to follow some global default , currently
equivalent to OFF Off (1) override global default with OFF On (2) override global
default with ON
Default Default (0)
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related Phase block#39;s formula and report parameters (user defined)
Parameters
Remarks If ON NaN will pass a range check for formula or report parameter. If OFF NaN
processing is according IEEE 754 (NaN is not smaller than any number , NaN is not
greater than any number).

- 268 -
Chapter 3 - Axxxx Parameters

3.113 ALMACTIVE [0..NUMALARMS-1]

Specific to All EtherNet/IP (EIP) IOM blocks that support alarms. EIP IOMs: 1732E-IB16M12DR,
Block(s) 1732E-IF4M12R, 1732E-IR4IM12R, 1732E-IT4IM12R, 1738-IB4DM12, 1738-
IE2CM12, 1738-IE4CM12, 1738-IR2M12, 1738-IT2IM12
Description Alarm State flag
Data Type Boolean
Range l Off
l On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related ALMSTR, ALMSUB, ALMPARAM, ALMCOND, ALMCONDVAL, ALMPRI, ALMSEV,
Parameters ALMDESC
Remarks This parameter indicates if the alarm is active. Each index of these related
parameters contain information about a particular alarm. EIP IOMs support only
system alarms.

3.114 ALMDB

Specific to DataAcq, All RegCtl Blocks except: Fanout, PulseCount, and PulseLength.
Block(s)
Description Overall Deadband for all analog alarms
Data Type 64-Bit Real Number
Range N/A
Default 0.00
Config Yes
Load
Active No
Loadable

- 269 -
Chapter 3 - Axxxx Parameters

Access Engineer/Application Developer


Lock
Residence CEE
Related ADVDEVALM.DBDEVFLAG[0..N], DEVHIALM.DB, DEVLOALM.DB, OPHIALM.DB,
Parameters OPLOALM.DB, PVHHALM.DB, PVHIALM.DB, PVLLALM.DB, PVLOALM.DB,
Remarks Individual alarm deadbands are not individually configurable. The configured
ALMDB is loaded to the block, then the block copies the ALMDB value to all the
xxALM.DB of all analog alarms on the block. ALMDB and ALMTM are handled in the
same way. Thus, all analog alarms get the same three values through a one-time
configuration entering of the three values. If desired, the individual alarm
parameters (xxALM.DB, xxALM.DBU, and xxALM.TM) may be modified after the
block is loaded. The block load will always set all individual alarm parameters to the
three configured values.

3.115 ALMDBU

Specific to DataAcq, All RegCtl Blocks except Fanout, PulseCount, and PulseLength.
Block(s)
Description Overall Deadband unit for all analog alarms
Data Type Enumeration ALMDBU
Range Percent (0) Engineering Units (1)
Default Percent (0)
Config Yes
Load
Active No
Loadable
Access Application Developer Only (DataAcq) Engineer (RegCtl Blocks)
Lock
Residence CEE
Related ADVDEVALM.DBU, DEVHIALM.DBU, DEVLOALM.DBU, OPHIALM.DBU,
Parameters OPLOALM.DBU, PVHHALM.DBU, PVHIALM.DBU, PVLLALM.DBU, PVLOALM.DBU
Remarks Individual alarm deadbands are not individually configurable. The configured
ALMDBU is loaded to the block, then the block copies the ALMDBU value to all the
xxALM.DBU of all analog alarms on the block. ALMDB and ALMTM are handled in
the same way. Thus, all analog alarms get the same three values through a one-
time configuration entering of the three values. If desired, the individual alarm
parameters (xxALM.DB, xxALM.DBU, and xxALM.TM) may be modified after the
block is loaded. The block load will always set all individual alarm parameters to the
three configured values.

- 270 -
Chapter 3 - Axxxx Parameters

3.116 ALMDESC [0..NUMALARMS-1]

Specific to All EtherNet/IP (EIP) IOM blocks that support alarms. EIP IOMs: 1732E-IB16M12DR,
Block(s) 1732E-IF4M12R, 1732E-IR4IM12R, 1732E-IT4IM12R, 1738-IB4DM12, 1738-
IE2CM12, 1738-IE4CM12, 1738-IR2M12, 1738-IT2IM12
Description Alarm Description
Data Type String
Range
Default
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related ALMSTR, ALMSUB, ALMPARAM, ALMCOND, ALMCONDVAL, ALMPRI, ALMSEV,
Parameters ALMACTIVE
Remarks This value is configurable by the user on the project view. Each index of these
related parameters contain information about a particular alarm. EIP IOMs support
only system alarms.

3.117 ALMENBSTATE

Specific to CEE, CEEC300, CEEACE, CPM, C300, ACE, RM, CM, SCM, IOM, CEEUOC, UOC,
Block(s) CN100, CEECN100, most tagged blocks, TCMI
Description Alarm Enable State
Exposure INANDOUT
Data Type Boolean
Range Off (0) On (1)
Default On (1)
Config Yes
Load
Active No
Loadable
Access Lock Operator RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence C300(CEEC300, C300, CM, SCM, IOM), C200(CEE, CPM, CM, SCM, IOM), ACE
(CEEACE, ACE, CM, SCM), RM(RM), UOC(CEEUOC, UOC, CM, SCM, IOM), For most
tagged blocks residency will the platform it is configured and loaded to.
Related INALM
Parameters
Remarks For CM, when On, ALMENBSTATE allows alarms detected by component blocks
within the CM to propagate out of the CEE to alarm displays and journals. When Off,
alarms reports do not propagate out of the CEE, but alarm flags reflect current
alarm state. When ALMENBSTATE changes from Off to On, all active alarms are
regenerated.

- 271 -
Chapter 3 - Axxxx Parameters

Specific to PM I/O HART Channels, Series C I/O HART Channels


Block(s)
Description Alarm Enable State
Data Type Boolean
Range 0 Off HART alarms and events
are not generated for this
channel.
1 On HART alarms and events
are generated for this
channel.
Default On
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related HENABLEJOURNALONLY
Parameters
Remarks The HENABLE parameter must be On to access this parameter. If the
JOURNALONLY parameter is On, the HART alarms are reported to the Event
Summary Journal only in Station.

Specific to Block(s) EIM Platform Block


Description Alarming Enabled
Data Type Boolean
Range NA
Default T
Config Load
Active Loadable No
Access Lock Operator
Residence PCM
Related Parameters
Remarks Enable or disable EIM platform block alarms.

3.118 ALMIN[1..16]

Specific to ALMWINDOW
Block(s)
Description Alarm inputs for Window group
Data Type Boolean
Range ON/OFF
Default OFF
Config Load NO
Active No

- 272 -
Chapter 3 - Axxxx Parameters

Loadable
Access Lock Engineer
Residence CEE
Related ALMOUT
Parameters
Remarks Alarm inputs for which alarms need to be raised are connected here. All these
inputs are Ored sent to ALMOUT

3.119 ALMOPT

Specific to DICHANNEL (PM I/O); DICHANNEL (Series C I/O)


Block(s)
Description Alarming Option. Defines the alarm option to be used for this point.
Data Type Enumeration
Range NONE (0): No alarms are to be detected.
OFFNORML (1): Off Normal; alarm if current PV state is not the PVNORMAL state.
PVNORMAL is defined by the STATETXT(0) or STATETXT(1)
descriptor, as configured by the user.
CHNSOFST (2): Change of State; alarm is generated when the digital input
changes state in either direction. Note that I/O Processor (IOP)
firmware must support Change of State Reporting.
Default NONE (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence IOP
Related
Parameters
Remarks This parameter is only exposed when the DITYPE is STATUS and the PNTFORM is
Full.

3.120 ALMOUT

Specific to Block(s) ALMWINDOW


Description Alarm output of the window group
Data Type Boolean
Range ON/OFF
Default OFF
Config Load NO
Active Loadable No

- 273 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters ALMIN[1..16]
Remarks This is Ored value of all the ALMIN[*]

3.121 ALMPRI [0.. NUMALARMS-1]

Specific to All EtherNet/IP (EIP) IOM blocks that support alarms. EIP IOMs: 1732E-
Block(s) IB16M12DR, 1732E-IF4M12R, 1732E-IR4IM12R, 1732E-IT4IM12R, 1738-IB4DM12,
1738-IE2CM12, 1738-IE4CM12, 1738-IR2M12, 1738-IT2IM12
Description Alarm Priority
Data Type Enumeration ALPRIOR
Range l None (0)
l Journal (1)
l Low (2)
l High (3)
l Urgent (4)
Default
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related ALMSTR, ALMSUB, ALMPARAM, ALMCOND, ALMCONDVAL, ALMSEV, ALMDESC,
Parameters ALMACTIVE
Remarks This value is configurable by the user on the project view. Each index of these
related parameters contain information about a particular alarm. EIP IOMs only
support system alarms.

3.122 ALMSELOPT

Specific to FLAG and DIGACQ


Block(s)
Description Alarm Selection Option – Selection between Off Normal and Change of State alarm
options.
Data Type ENUM
Range Off Normal, Change of state
Default Off Normal
Config Yes
Load
Active No
Loadable

- 274 -
Chapter 3 - Axxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related ALTENBOPT
Parameters
Remarks This parameter is mutually exclusive with ALTENBOPT parameter. You can
configure either Alert option or Alarm option (Off Normal or COS). The default
option is Off Normal. You have the choice whether to choose Off Normal or COS
alarm and then configure accordingly. If you select the Alert Enable option, then
the Alarm selection option is disabled with default value as Off Normal. In addition,
the parameter - NORMAL is also disabled.

NOTE
1. DEVCTL block does not have Off Normal alarm so COS is directly
available to configure using CHGOFSTALMENB parameter.
2. Alert Enable option is applicable only to Flag block.

3.123 ALMSEQ

Specific to Block(s) ALMWINDOW


Description Alarm sequence
Data Type Enumeration: ALMSEQ
Range Ringbackseq, Manualresetseq, Autoresetseq
Default Ringback
Config Load YES
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This indicates the selected alarm sequence for this block.

3.124 ALMSEV [0..NUMALARMS-1]

Specific to All EtherNet/IP (EIP) IOM blocks that support alarms. EIP IOMs: 1732E-IB16M12DR,
Block(s) 1732E-IF4M12R, 1732E-IR4IM12R, 1732E-IT4IM12R, 1738-IB4DM12, 1738-
IE2CM12, 1738-IE4CM12, 1738-IR2M12, 1738-IT2IM12
Description Alarm Severity
Data Type 16-Bit Unsigned Integer
Range 0 to 15
Default 0
Config Load Yes
Active No

- 275 -
Chapter 3 - Axxxx Parameters

Loadable
Access Lock AppDevOnly
Residence CEE
Related ALMSTR, ALMSUB, ALMPARAM, ALMCOND, ALMCONDVAL, ALMSEV, ALMPRI,
Parameters ALMDESC, ALMACTIVE.
Remarks This value is configurable by the user on the project view. Each index of these
related parameters contain information about a particular alarm. EIP IOMs support
only system alarms.

3.125 ALMSTR[0..NUMALARMS-1]

Specific to All EIP IOM blocks that support alarms. EIP IOMs: 1732E-IB16M12DR, 1732E-
Block(s) IF4M12R, 1732E-IR4IM12R, 1732E-IT4IM12R, 1738-IB4DM12, 1738-IE2CM12,
1738-IE4CM12, 1738-IR2M12, 1738-IT2IM12
Description Alarm description string that identifies a particular alarm.
Data Type STRING
Range
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related ALMSUB, ALMPARAM, ALMCOND, ALMCONDVAL, ALMPRI, ALMSEV, ALMDESC,
Parameters ALMACTIVE.
Remarks User visible alarm description string that identifies a particular alarm. This
information is present for EtherNet/IP modules that exist as System templates. For
module templates that are created by the user, this information has to be entered
when creating the block template through PDE. Each index of these related
parameters contain information about a particular alarm. EIP IOMs only support
system alarms.

3.126 ALMTM

Specific to DataAcq, All RegCtl Blocks except PulseCount and PulseLength.


Block(s)
Description Filter Time for all alarms
Data Type 32-Bit Unsigned Integer
Range 0 to 60
Default 0
Config Yes
Load
Active No

- 276 -
Chapter 3 - Axxxx Parameters

Loadable
Access Engineer/Application Developer
Lock
Residence CEE
Related ADVDEVALM.TM, CMDDISALM.TM[0..2], CMDFALALM.TM[0..2], DEVHIALM.TM,
Parameters DEVLOALM.TM, OPHIALM.TM, OPLOALM.TM, PVHHALM.TM, PVHIALM.TM,
PVLLALM.TM, PVLOALM.TM.
Remarks Individual alarm deadbands are not individually configurable. The configured
ALMTM is loaded to the block, then the block copies the ALMTM value to all the
xxALM.TM of all analog alarms on the block. ALMDB and ALMDBU are handled in
the same way. Thus, all analog alarms get the same three values through a one-
time configuration entering of the three values. If desired, the individual alarm
parameters (xxALM.DB, xxALM.DBU, and xxALM.TM) may be modified after the
block is loaded. The block load will always set all individual alarm parameters to the
three configured values.

3.127 ALMWINTXT[1..32]

Specific to Block(s) ANNPANEL


Description Annunciator window text
Data Type String
Range 32 Characters.
Default Annunciator window [x]
Config Load
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks This description appears on the detail display pages for the Alarm panel.

- 277 -
Chapter 3 - Axxxx Parameters

3.128 ALONEAV

Specific to Block(s) TCMI

Description Alone In Ring Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

3.129 ALTENBOPT

Specific to FLAG block


Block(s)
Description Alert Enable Option - This parameter enables the FLAG block to be configured for
generating alerts.
Data Type Boolean
Range OFF (Alerts are disabled)
ON (Alerts are enabled)
Default OFF (Alerts are disabled)
Config Load Yes
Active No
Loadable
Access Lock Application Developer only
Residence CEE
Related INALT HIALM.TYPE
Parameters
Remarks l When ALTENBOPT is set to ON, the FLAG block can be configured to generate
an alert on an off-normal condition.
l When ALTENBOPT is set to OFF, the FLAG block can be configured to
generate an alarm on an off-normal condition.
l A FLAG block cannot be configured to generate an alarm and an alert
simultaneously. The selection between an alarm and an alert is based on the
ALTENBOPT parameter.
l The ALTENBOPT parameter cannot be modified after the FLAG block is
loaded.
l The ALTENBOPT parameter can be exposed as an output pin.

- 278 -
Chapter 3 - Axxxx Parameters

3.130 ALTSYNCCMD

Specific to C300 FBs, PGM, UOC


Block(s)
Description Alternate Sync Over FTE
Data Type Boolean
Range Off (0) On (1) NA
Default Off
Config Load No, Yes
Active No
Loadable
Access Lock Operator
Residence C300, PGM, NOLOAD
Related
Parameters
Remarks Used to command a one-time initial Sync across the alternate FTE communication
path followed by immediate switchover. This parameter has edge trigger semantics
and always returns OFF when read.

3.131 AMCOMMAND

Specific to PID-PL
Block(s)
Description Auto-modeler Commanded State - Defines the command state last sent to auto-
modeling software.
Data Type 16-Bit Integer
Range 0 Command auto-modeler to stop running.

1 Command auto-modeler to start or


resume.
2 Command auto-modeler to pause.
Other Transient state corresponding to ordinal
value of the AMSTATUS parameter
Default 0
Config Yes
Load
Active No
Loadable

- 279 -
Chapter 3 - Axxxx Parameters

Access Lock Operator


Residence CEE
Related AMSTATUS
Parameters
Remarks When activated, the auto-modeler will step either the SP or the OP of the function
block between two user-specified bounds. As each step is made, the auto-modeler
examines the response of PV and generates a model to represent this response.
When the proposed model predicts the PV response well, the auto-model stores the
model and turns off. The auto-modeler requires installation of the Profit Loop PKS
Assistant on the local node (server or station).

3.132 AMHI

Specific to PID-PL
Block(s)
Description Auto-modeler Upper Limit for Excitation - Upper bound for the AMMODE parameter
during bump testing.
Data Type Float64
Range Depends on AMMODE
OP AMLO to 100
SP AMLO to SPHILM
Default
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related AMLO, AMMODE, AMRESPTIME
Parameters
Remarks When activated, the auto-modeler will step either the SP or the OP of the function
block between two user-specified bounds. As each step is made, the auto-modeler
examines the response of PV and generates a model to represent this response.
When the proposed model predicts the PV response well, the auto-model stores the
model and turns off. The auto-modeler requires installation of Profit Loop PKS
Assistant on the local node (server or station).

- 280 -
Chapter 3 - Axxxx Parameters

3.133 AMLO

Specific to PID-PL
Block(s)
Description Auto-modeler Lower Limit for Excitation - Lower bound for the AMMODE
parameter during bump testing.
Data Type Float64
Range Depends on AMMODE:
OP 0 to AMHI
SP SPLOLM to AMHI
Default
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related AMHI, AMLO, AMRESPTIME.
Parameters
Remarks When activated, the auto-modeler will step either the SP or the OP of the function
block between two user-specified bounds. As each step is made, the auto-modeler
examines the response of PV and generates a model to represent this response.
When the proposed model predicts the PV response well, the auto-model stores the
model and turns off. The auto-modeler requires installation of Profit Loop PKS
Assistant on the local node (server or station).

3.134 AMODULES

Specific to Block(s) Cabinets


Description It defines the first column of the cabinet to configure the IO modules to the
cabinet.
Data Type BLOCKID
Range —
Default —
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks

- 281 -
Chapter 3 - Axxxx Parameters

3.135 AMMODE

Specific to PID-PL
Block(s)
Description Auto-modeler Mode - Defines which parameter the auto-modeler will change to
identify process dynamics.
Data Type Enumeration PLAMMODE
Range OP(0): Auto-modeler will alter the value of the
OP parameter.
SP(1): Auto-modeler will alter the value of the
SP parameter.
Default OP
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related AMHI, AMLO, AMRESPTIME.
Parameters
Remarks When activated, the auto-modeler will step either the SP or the OP of the function
block between two user-specified bounds. As each step is made, the auto-modeler
examines the response of PV and generates a model to represent this response.
When the proposed model predicts the PV response well, the auto-model stores the
model and turns off. The auto-modeler requires installation of Profit Loop PKS
Assistant on the local node (server or station).

3.136 AMRESPTIME

Specific to PID-PL
Block(s)
Description Auto-modeler Response Time - Starting estimate for the process open loop
response time.
Data Type Float64
Range >0
Default 1.0
Config Yes
Load
Active No
Loadable

- 282 -
Chapter 3 - Axxxx Parameters

Access Operator
Lock
Residence CEE
Related AMHI, AMLO, AMMODE.
Parameters
Remarks When activated, the auto-modeler will step either the SP or the OP of the function
block between two user-specified bounds. As each step is made, the auto-modeler
examines the response of PV and generates a model to represent this response.
When the proposed model predicts the PV response well, the auto-model stores the
model and turns off. A good starting estimate for the open loop response time can
dramatically reduce the amount of time required to identify the process dynamics.
The auto-modeler requires installation of Profit Loop PKS Assistant on the local
node (server or station).

3.137 AMSTATUS

Specific to PID-PL
Block(s)
Description Auto-modeler Status - Updates the active model in the function block with values
stored in model buffer.
Data Type Enumeration PLAMSTATUS
Range Not_Running(0): Auto-modeler is not yet started.
In_Progress(1): Auto-modeler is running.
Paused(2): Auto-modeler has been paused.
Unable_to_Model(3): Auto-modeler cannot find an adequate
process model.
Done(4): Auto-modeler has identified a process
model.
Wizard_Failure(5): Failure in Profit Loop PKS Assistant -
contact Honeywell.
Profit_Stepper_Failure(6): Failure in auto-modeler software -
contact Honeywell.
Default Not_Running
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related AMCOMMAND,
Parameters
Remarks When activated, the auto-modeler will step either the SP or the OP of the function
block between two user-specified bounds. As each step is made, the auto-modeler
examines the response of PV and generates a model to represent this response.
When the proposed model predicts the PV response well, the auto-model stores the
model and turns off. The auto-modeler requires installation of the Profit Loop PKS
Assistant on the local node (server or station).

- 283 -
Chapter 3 - Axxxx Parameters

3.138 ANYRESTARTFL

Specific to STARTSIGNAL
Block(s)
Description Any Restart Flag - Holds True for the first execution cycle, if any of the preceding
flag parameters are True. This is the same as saying that the parameter holds True
whenever parameter RESTART is not equal to NONE.
Data Type Boolean
Range True False
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RESTART
Parameters
Remarks

3.139 AOCHNLNAME

Specific to Universal IO module


Block(s)
Description Channel Name - Displays the channel names in the AO Status tab of the UIO
module.
Data Type String
Range Length: 40 characters
Default
Config No
Load
Access Lock ViewOnly
Active No
Loadable
Residence SR
Related CHNLNAMEAICHNLNAMEDICHNLNAMEDOCHNLNAME
Parameters
Remarks This parameter identifies the configured name of the channels associated with this
IOM block. . It is used to display the channel names in AO Status Data tab. This
parameter displays only the channel names configured with the PNTTYPE of AO.

- 284 -
Chapter 3 - Axxxx Parameters

3.140 AOPTEXECST

Specific to Universal IO module


Block(s)
Description Point Execution State - Displays the point execution state in the AO Status tab of
the UIO module.
Data Type Enumeration
Range 0 Inactive Point is not scanned or
processed.
1 Active Point is scanned and
processed.
Default Inactive
Config Load No
Access Lock ViewOnly
Active No
Loadable
Residence IOM
Related PTEXECSTAIPTEXECSTDIPTEXECSTDOPTEXECST
Parameters
Remarks This parameter displays the point execution state of UIO module in the AO Status
Data tab. When PTEXECST is Inactive, the point processing does not occur for the
channel.

3.141 APPIMAGETYPE

Specific to All Blocks


Blocks
Description Application Image Type
Data Type ENUM
Range 0 – C300_NoHwyEmul 1 – C300_HwyEmul
Default C300_NoHwyEmul
Config. Yes
Load
Access AppDevOnly
Lock
Residence CEE
Related BASEPERIOD
Parameters
Remarks C300_NoHwyEmul – If this enumeration is selected, then C300 is loadable on the
C300 hardware with personality not containing the EHB enabler. If C300 hardware
contains C300 personality with EHB enabler, then load will fail with error. C300_
HwyEmul – If this enumeration is selected, then C300 is loadable on the C300
hardware with personality containing the EHB enabler. Also, the BASEPERIOD of
CEE must be 50ms. If C300 hardware contains a personality other than the one
having the EHB enabler, then load will fail with error.

- 285 -
Chapter 3 - Axxxx Parameters

3.142 APPROVALS

Specific to Block(s) RCM


Description Approvals
Data Type String
Range
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameter
Remarks

3.143 AREVISION

Specific to RM
Block(s)
Description Application Revision. Identifies the minor revision of the RM application code.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

3.144 ACTIVEARRPARAMWRITES

Specific to EIM EIP Protocol Block


Block(s)
Description Arrayed tag/parameter writes
Data Type UINT16
Range 1-325
Default 0

- 286 -
Chapter 3 - Axxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related -
Parameters
Remarks Number of arrayed tag/parameter writes currently active in this EIM, initiated
from one or more C300’s.

3.145 ACTIVENONARRPARAMWRITES

Specific to EIM EIP Protocol Block


Block(s)
Description Non-arrayed tag/parameter writes
Data Type UINT16
Range 0-675
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NoLoad
Related -
Parameters
Remarks Number of non-arrayed tag/parameter writes currently active in this EIM,
initiated from one or more C300’s.

3.146 ArraySize

Specific to BOOLEAN_TAG, Scalar UDT Block


Block(s)
Description Tag Array Size: When trying to Access an Arrayed Boolean Parameter or Tag from
CLX, this Parameter needs to be configured to the array Size equivalent to the
Array Size of that Parameter or Tag.
Data Type UINT16
Range 1-256
Default 1
Config Load Yes
Active No
Loadable

- 287 -
Chapter 3 - Axxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related -
Parameters
Remarks -

3.147 ARRINDEX

Specific to Block(s) EIM


Description Attribute Index
Data Type BOOLEAN
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence ERDBONLY
Related Parameters
Remarks

3.148 ARIBITRATIONSTATUS

Specific to RCM, UCM, MR


Block(s)
Description UCM Arbitration Status
Data Type Enumeration
Range 0 NONE
1 ACQUIRING
2 ACQUIRED
3 RELEASING
4 ERROR
5 WARNING
Default NONE
Config Load No
Active No
Loadable

- 288 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks Displays the status of the connection between the recipe and the current Unit
Control Module. Note: This parmeter is disabled for MR block.

3.149 ARWMULTOP[1..8]

Specific to FANOUT
Block(s)
Description Anti-Reset Windup Multiple Output (OP) Status - Applies to function blocks with
multiple output (OP) connections. Contains the windup status for each output
variable.
Data Type Enumeration ARWNET
Range 0 NORMAL Free to move in any
direction.
1 HI Free to move in the lower
direction.
2 LO Free to move in the higher
direction.
3 HILO Cannot move in any
direction.
Default NORMAL
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ARWNET[1..8]
Parameters
Remarks

3.150 ARWNET[1..8]

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PID-PL PosProp,
Block(s) RampSoak, RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Network Anti-Reset Windup Status for the primary - Applies to function blocks with
multiple initializable inputs. Contains the windup status of each initializable input.
Data Type Enumeration ARWNET
Range Normal (0): The input is free to move in any
direction.

- 289 -
Chapter 3 - Axxxx Parameters

Hi (1): The input cannot move higher, but is


free to move lower.
Lo (2): The input cannot move lower, but is free
to move higher.
HiLo (3): The input cannot move in any direction.
Default Normal (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ARWOP
Parameters
Remarks ARWNET(1) computation is independent of whether gain (K) is positive or negative.

3.151 ARWNETIN

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDER, PIDFF, PID-PL PosProp,
Block(s) RampSoak, RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Anti-Reset Windup Network Status Input - Added in the standard ARWNET
computation logic to allow stores from Sequential Control Modules (SCMs) and
Custom Algorithm Block (CAB) programs.
Data Type Enumeration ARWNET
Range 0 NORMAL Input is free to move in
any direction.
1 HI Input cannot move higher,
but is free to move lower.
2 LO Input cannot move lower,
but is free to move higher.
3 HILO Input cannot move in any
direction.
Default Normal (0)
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related ARWOP
Parameters
Remarks ARWNET(1) computation is independent of whether gain (K) is positive or negative.

- 290 -
Chapter 3 - Axxxx Parameters

3.152 ARWNETIN[1..8]

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDER, PIDFF, PID-PL PosProp,
Block(s) RampSoak, RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Network Anti-Reset Windup Status Input - Added in the standard ARWNET
computation logic to allow stores from Sequential Control Modules (SCMs) and
Custom Algorithm Block (CAB) programs.
Data Type Enumeration ARWNET
Range Normal (0): The input is free to move in any
direction.
Hi (1): The input cannot move higher, but is
free to move lower.
Lo (2): The input cannot move lower, but is free
to move higher.
HiLo (3): The input cannot move in any direction.
Default Normal (0)
Config Load No
Active No
Loadable
Access Lock Engineer
Residence Not Loaded
Related ARWOP
Parameters
Remarks ARWNET(1) computation is independent of whether gain (K) is positive or negative.

3.153 ARWOP

Specific to All RegCtl Blocks: AutoMan, OvrdSel, PID, PID-PL, PIDFF, PosProp, RampSoak,
Block(s) RegSummer, RemCas, RatioBias, RegCalc, and Switch, FANOUT
Description Output Anti-Reset Windup Status - Applies to function blocks with, at most, one
output ( PV) connection. Contains the windup status of the OP variable.
Data Type Enumeration ARWNET
Range Normal (0): OP is free to move in either direction.
Hi (1): OP is free to move in the lower direction.
Lo (2): OP is free to move in the higher
direction.
HiLo (3): OP cannot move in any direction.
Default Normal (0)
Config Load No
Active No
Loadable

- 291 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ARWNET[1..8]ARWMULTOP[1..8]
Parameters
Remarks

3.154 ARWOPIN

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDER, PIDFF, PID-PL PosProp,
Block(s) RampSoak, RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Output Anti-Reset Windup Output (OP) Input - Added in the standard ARWOP
computation logic to allow stores from Sequential Control Modules (SCMs) and
Custom Algorithm Block (CAB) programs.
Data Type Enumeration ARWOP
Range Normal (0): Free to move in either direction.
Hi (1): Free to move in the lower direction.
Lo (2): Free to move in the higher direction.
HiLo (3): Cannot move in any direction.
Default Normal
Config Load No
Active No
Loadable
Access Lock Engineer
Residence Not Loaded
Related ARWNET[1..8]
Parameters
Remarks

3.155 ARWRATIO

Specific to PID-PL
Block(s)
Description Anti-Windup Ratio - Controls the speed the OP is moved out of a windup condition.
Data Type Float64
Range 0-1
0= No tracking; ignore secondary
measurement (no unwinding)
1= Full tracking; immediately reset OP limits
to secondary measurement
Values between 0 and 1 balance OP readback noise filtering with unwinding speed.
Default 0.1
Config

- 292 -
Chapter 3 - Axxxx Parameters

Load
Active No
Loadable
Access Lock Engineer
Residence
Related CTLACTN, PV
Parameters
Remarks When function block windup is detected, one or both of the OP operating limits is
temporarily reset to the current OP. If the PID-PL function block cascades to
another function block and a secondary measurement is available, PID-PL ramps
the OP limits toward the secondary measurement. This occurs most often when
l the PID-PL function block is writing to the setpoint of a secondary function
block, and
l the PV of the secondary is available for measurement.
The anti-windup ratio determines how quickly the OP limits track the secondary
measurement.

3.156 ASACONNSTS

Specific to All IOM Function Blocks except Serial Interface IOM - To be used for
Block(s) Troubleshooting only. Refer to ASACONNSTS[0..7] for Serial Interface IOM.
Description ASA Connection Status
Data Type 32-Bit Integer
Range 0x0 to 0x8000
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks 0x4000 indicates running/connected (good status).

3.157 ASACONNSTS[0..7]

Specific to Block(s) Serial Interface IOM


Description ASA Connection Status
Data Type 32-Bit Integer
Range 0x0 to 0x8000
Default
Config Load No

- 293 -
Chapter 3 - Axxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks 0x4000 indicates running/connected (good status).

3.158 ASAERRCODE

Specific to All IOM Function Blocks except Serial Interface IOM - To be used for
Block(s) Troubleshooting only. Refer to ASAERRCODE[0..7] for Serial Interface IOM.
Description ASA Error Code
Data Type 32-Bit Integer
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ASAERRINFO
Parameters
Remarks General status code for ASA/ControlNet messaging.

3.159 ASAERRCODE[0..7]

Specific to Block(s) Serial Interface IOM


Description ASA Error Code
Data Type 32-Bit Integer
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters ASAERRINFO[0..7]
Remarks General status code for ASA/ControlNet messaging.

- 294 -
Chapter 3 - Axxxx Parameters

3.160 ASAERRINFO

Specific to All IOM Function Blocks except Serial Interface IOM - To be used for
Block(s) Troubleshooting only. Refer to ASAERRINFO[0..7] for Serial Interface IOM.
Description ASA Error Information
Data Type 32-Bit Integer
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ASAERRCODE
Parameters
Remarks Extended status information for ASA/ControlNet messaging.

3.161 ASAERRINFO[0..7]

Specific to Block(s) Serial Interface IOM


Description ASA Error Information
Data Type 32-Bit Integer
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters ASAERRCODE[0..7]
Remarks Extended status information for ASA/ControlNet messaging.

3.162 ASICVERA[1..8]

Specific to Block(s) UIO-2 IOM


Description ASIC Version
Data Type STRING
Range Not Applicable
Default 0
Config Load No

- 295 -
Chapter 3 - Axxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related Parameters
Remarks This parameter displays version of ASICs (1-8).

3.163 ASICVERB[1..8]

Specific to Block(s) UIO-2 IOM


Description ASIC Version
Data Type STRING
Range Not Applicable
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related Parameters
Remarks This parameter displays version of ASICs (1-8).

3.164 ASSIGNABLE

Specific to Asset
Block(s)
Description Directly Assignable (for scope of responsibility and alarm enable/disable)
Data Type Boolean
Range 0 Asset cannot be directly assigned to an
operator or station.
1 Asset can be directly assigned to an
operator or station.
Default 0 Not assignable
Config No
Load
Active No
Loadable

- 296 -
Chapter 3 - Axxxx Parameters

Access Lock Application Developer Only


Residence SCAN
Related
Parameters
Remarks Assets that can be assigned to an operator or station are called “assignable assets”.
The scope of an assignable asset includes all asset children of the assignable asset
including any points associated with those assets or any alarm groups that have
been designated that asset for scope of responsibility purposes.

3.165 ASSOCASSET

Specific to Alarm Groups, ACE; C200/C200E; SIMC200E; CPM; CPM200; C300; Series C I/O
Block(s) modules; FIM4; FIM 8; PGM; FTEB; SIMIOLIM; IOLIM; LIOM; SLINK; WDM; Series C
I/O: AI-HART, AI-HL, AI-LLMUX, AI-LLAI, AO, AO-HART, DI-24, DI-HV, DI-SOE, DO-
24B, PI, SP, SVP, FDM created: All HART devices; Fieldbus: All devices; EHG devices;
DeviceNet devices; Profibus devices; DSB, PBHIOMB, PBHCHANNEL; UOC, TCMI,
EIM
Description Associated Asset name: The name of the asset to which the alarm group is
associated.
Data Type String
Range Length: 132 Characters maximum, N/A
Default Null
Config Alarm Groups -No, Yes
Load
Active Yes, EIM -No
Loadable
Access Lock Application Developer Only
Residence SCAN, Server/SR, SRSCANAL
Related
Parameters
Remarks An alarm group must be associated with an asset which is declared as assignable.
Additionally, the asset must be assigned to an operator before the operator can
view the activity. Specifies the Asset Group to be used to define a point's scope of
responsibility. If left blank or an invalid asset is specified, the default behavior will be
to use the server point. This parameters flows down from IED Blocks Associated
Asset

3.166 ASSOCCHANNEL

Specific to Series C PICHANNEL


Block(s)
Description Associated Input Channel
Data Type UINT8
Range 0, 2, 4, 6, 8
Default -

- 297 -
Chapter 3 - Axxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock ViewOnly
Residence SR
Related INPUTSTREAM
Parameters
Remarks This parameter contains the channel number of the channel's associated channel
when dual-stream integrity is being used

3.167 ASSOCIOP

Specific to PMIO Channel Blocks


Block(s)
Description Associated I/O Processor (IOP). Defines the associated IOP block to which the
I/O Channel (IOC) is assigned.
Data Type String
Range
Default
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence SR
Related
Parameters
Remarks

3.168 ASSOCIOPTYP

Specific to PMIO Channel Blocks


Block(s)
Description Associate I/O Processor Type. Defines the type of I/O Processor associated with the
I/O Channel (IOC).
Data Type Enumeration
Range --- (0): Not Configured LLAI (1): Low-Level Analog Input HLAI (2): High-Level
Analog Input DI (3): Digital Input DO (4): Digital Output AO (5): Analog Output
LLMUX (7): Low Level Analog Multiplexer STI-MV (14): Smart Transmitter Interface
- Multivariable DISOE (16): Digital Input Sequence of Events AO16 (24): Analog
Output 16 DO32 (25): Digital Output 32 RHMUX (28): Remote Hardened Multiplexer
Default --- (0)
Config No
Load

- 298 -
Chapter 3 - Axxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks

3.169 ASSOCGANGEDCHANNELS

Specific to UIO - Series C DOCHANNEL


Block(s)
Description Associated ganged channels
Data Type String
Range Not applicable
Default Blank
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related ENBLGANGEDOUTPUTSNUMOFCHNLSGANGED
Parameters
Remarks This parameter displays the channel numbers that are ganged when channel
ganging is enabled. For more information about channel ganging, refer to Series C
I/O User's Guide.

3.170 ASSOCIATEDTREND

Specific to PID-PL
Block(s)
Description Associated Trend - This parameter is used for specifying a Trend number for new
plots.
Data Type 32-bit integer
Range 1 - 3000
Default 0
Config Yes
Load
Active No
Loadable

- 299 -
Chapter 3 - Axxxx Parameters

Access Lock Operator


Residence Server
Related
Parameters
Remarks This parameter is supported only in Profit Loop blocks. You can save trend
information by clicking “Save” on the title tool bar of the trend. If you modify or
configure a new plot, you can save it by specifying a number for AssociatedTrend.
The default configuration (first four plots in loop tune trend) of trend plots can be
changed at runtime but are not saved. The AssociatedTrend number is indicated
only on the displays sysdtlpidplb.htm and sysdtlpidplaltb.htm.

3.171 ASTEPID

Specific to DevCtl, All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PID-PL, PIDFF, PosProp,
Block(s) RampSoak, RegSummer, RemCas, RatioBias, RegCalc, and Switch. All Drive Control
Blocks: HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER
Description Active step handle in Sequential Control Module (SCM) Control Request
(CONTROLREQ).
Data Type 32-Bit Integer
Range 1 to 1023
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CONTROLREQ, SCHDOPTIMIZE SCHEDCYCLE[0..120] SCMASTEP[1..15]
Parameters
Remarks

3.172 ATLOADSTATE

Specific to Block(s) RCM, SCM


Description Alias Table Load State
Data Type Enumeration
Range 0 FAILED
1 LOADINGMOD
2 LOADINGTABLE
3 WAITINGEND
4 COMPLETE
Default COMPLETE
Config Load No

- 300 -
Chapter 3 - Axxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

3.173 AUTHOR

Specific to Block(s) RCM


Description Author
Data Type String
Range ON-OFF
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

3.174 AUTHSERVERIPADDR

Specific to Block EHPM


(s)
Description Authentication Server IP is the address of ENIM which is authenticating the
EHPM controller.
Data Type String
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related EAGN
Parameters
Remarks This is the IP address of ENIM which is authenticating the EHPM controller.

- 301 -
Chapter 3 - Axxxx Parameters

3.175 AUTHSTATE

Specific to EHPM
Block(s)
Description Authentication State shows the actual state while authentication is in progress.
Data Type ENUM
Range None (0) Init (1) ReqFail (2) ReqPass (3) FailLocalAuth (4) RespSent (5) RespFail (6)
RespPass (7) SessionPending (8) Operate (9) Serve (10) Master (11)
NumAuthStates (12)
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence EHPM
Related AuthServerIPAddr
Parameters
Remarks This state is set while ENIM is authenticating the EHPM controller.

3.176 AUTOBAUDDISABLE

Specific to EtherNet/IP [EIP] IOM: 1738-IB4DM12


Block(s)
Description Autobaud disable — Autobaud allows the module to match the baud rate of the
existing devices on a network.
Data Type Boolean
Range l Off
l On
Default Off
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related
Parameters
Remarks When the value of this parameter is ON, it disables the Autobaud attribute.

- 302 -
Chapter 3 - Axxxx Parameters

3.177 AUTOCLOSE

Specific to Block(s) VALVEDAMPER, SOLENOID


Description Auto Close
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters OP, GOP, OPFINAL, OPREQ, REMOTESWITCH
Remarks Command to close the valve.

3.178 AUTOMAN

Specific to HRBALG_REG block


Blocks
Description AUTOMAN function block reference
Data Type BLOCKID
Range Not applicable
Default Null
Config. Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter contains a reference to the AUTOMAN block in the emulation CM
which holds the HRBALG_REG instance.

3.179 AUTOMAN2

Specific to HRBALG_REG block


Blocks
Description AUTOMAN FB Reference 2
Data Type BLOCKID
Default NULL
Config. Load Yes

- 303 -
Chapter 3 - Axxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the AUTOMAN2 block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

3.180 AUTOMATICPOINTIMPORT

Specific to EHPM
Block(s)
Description Automatic point import is used to optionally enable/disable the automatic import of
EHPM points using the auto-import service. If this option is disabled/unchecked,
then the EHPM points cannot be imported automatically and you have to import
them using the EHPM Point Import Utility.
Data Type BOOLEAN
Range ON-OFF
Default OFF
Config Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly
Residence ERDBOnly
Related -
Parameters
Remarks Automatic point import is unchecked by default and you have to check this option to
enable the auto-import service to initiate automatic import of the EHPM points.
Automatic import of EHPM points into ERDB and then into Experion server can be
initiated after the following events:
1. Checkpoint EHPM from Native Window
2. ENIM failover to the secondary
3. ENIM startup
4. Restore connection between Experion server and ENIM

3.181 AUTONOCMD

Specific to Block(s) VALVEDAMPER


Description Auto No Command
Data Type Boolean
Range ON, OFF

- 304 -
Chapter 3 - Axxxx Parameters

Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters AUTOOPENAUTOCLOSE
Remarks

3.182 AUTOOPEN

Specific to Block(s) VALVEDAMPER, SOLENOID


Description Auto Open
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters OP, GOP, OPFINAL, OPREQ, REMOTESWITCH
Remarks Command to open the valve.

3.183 AUTOPERIOD

Specific to CHGEXEC
Block(s)
Description Automatic Period - Configuration parameter which determines period of
CHGEXEC auto-trigger processing.
Data Type Enumeration
Range 0 500 ms
5 1 sec
10 2 sec
Default 1 sec
Config Load Yes
Active No
Loadable

- 305 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer


Residence CEE
Related AUTOPHASE
Parameters
Remarks

3.184 AUTOPHASE

Specific to CHGEXEC
Block(s)
Description Automatic Phase - Automatically assigned configuration parameter which controls
phase of CHGEXEC auto-trigger processing.
Data Type 32-Bit Integer
Range
Default -1
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related AUTOPERIOD
Parameters
Remarks

3.185 AUTOPUBLICNAME

Specific to SCM, RCM, and MR


Block(s)
Description Specifies if the public name track is the name.
Data Type BOOLEAN
Range -
Default True
Config No
Load
Active No
Loadable

- 306 -
Chapter 3 - Axxxx Parameters

Access AppDevOnly
Lock
Residence SR
Related
Parameters
Remarks This parameter provides a name to identify a group of recipes created from multiple
instances, multiple versions, multiple Master Recipes, or multiple recipes making
the same product. It compares different batches across multiple instances of the
same product. If AUTOPUBLICNAME is selected, the PUBLICNAME parameter is not
available. Changing to a Public Name needs reloading of the recipe to reflect the
change. Activity Summary Display contains Public Name field, which displays Public
Name of the associated Activity Entity. Activities displayed on Activity Summary
Display can be filtered by Public Name.

3.186 AUTOSTART

Specific to Block(s) HTMOTOR, LTMOTOR


Description Auto Start
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters OP, GOP, OPFINAL, OPREQ, REMOTESWITCH
Remarks Command to start the motor.

3.187 AUTOSTOP

Specific to Block(s) HTMOTOR, LTMOTOR


Description Auto Stop
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters OP, GOP, OPFINAL, OPREQ, REMOTESWITCH
Remarks Command to stop the motor.

- 307 -
Chapter 3 - Axxxx Parameters

3.188 AUTOSTOPACTED

Specific to Block HTMOTOR


(s)
Description Auto Stop Acted
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related AUTOSTOP RESETFIRSTUP
Parameters
Remarks Indicates that the corresponding command has been issued and changed the
output state to STOP.

3.189 AUTOSYNCCMD

Specific to RM
Block(s)
Description Auto Synchronization Command
Data Type Enumeration
Range Never (0) Always (1) Conditional (2)
Default Never (0)
Config Load No
Active No
Loadable
Access Lock Operator Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 308 -
Chapter 3 - Axxxx Parameters

3.190 AUTOSYNCOPT

Specific to RM
Block(s)
Description Auto Synchronization Option.
Data Type Enumeration
Range Never (0) Always (1) Conditional (2)
Default Never (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

3.191 AUTOSYNCSTAT

Specific to RM
Block(s)
Description Auto Synchronization State - Present State of Redundancy Module Auto-
Synchronization
Data Type Enumeration
Range Disabled (0) Enabled (1)
Default Disabled (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 309 -
Chapter 3 - Axxxx Parameters

3.192 AUTOTRIGGER

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Auto Trigger Mode - Enable or disable mode
Data Type Boolean
Range True: Enable mode False: Disable mode
Default True
Config Yes
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related
Parameters
Remarks Request Blocks execute in either the triggered mode or in an auto triggered mode.
In the triggered mode, the block will execute on the positive transition of the
SENDFL parameter, if the READYFL parameter is true. In the auto triggered mode,
when the check box is selected, the block will execute when the DONEFL parameter
is true (the previous request has completed).

ATTENTION The DONEFL parameter must not be used with PCDI blocks
when the AUTOTRIGGER parameter is enabled.

3.193 AUTOTRIGGERPERIOD

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Auto Trigger Period in milliseconds
Data Type 32-Bit Unsigned Integer
Range 0 to 4294967295
Default 0
Config Yes
Load
Active No
Loadable

- 310 -
Chapter 3 - Axxxx Parameters

Access Lock Engineer/Application Developer


Residence CEE
Related
Parameters
Remarks This parameter is used to delay the beginning of the following auto triggered block
execution. Auto triggered execution will resume in the Control Module cycle
following expiration of the auto trigger period. If the auto trigger period has expired
before the DONEFL parameter transitions to true, the block will be auto triggered
immediately. The default AUTOTRIGGERPERIOD value is 0 milliseconds, which
results in the block being triggered as quickly as possible.

3.194 AUXCMD

Specific to Block(s) SCM, RCM


Description Auxiliary Sequential Control Module (SCM) Command
Data Type 32-Bit Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters AUXSTS, AUXREQDATA[1..5]
Remarks Parameter for use with Batch Level 3. AUXCMD reset value is zero.

3.195 AUXDATA[0..7]

Specific to SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


Block(s)
Description Auxiliary Configuration Data - Used for specifying additional configuration
parameters for the FTA application; a generic array is provided because each value
can mean different things for different FTA applications. AUXDATA is writable while
online.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Yes
Load
Active No
Loadable

- 311 -
Chapter 3 - Axxxx Parameters

Access Lock Application Developer


Residence CEE
Related
Parameters
Remarks Refer to the Allen-Bradley Interface Appendix the MODBUS Interface Appendix in
the Serial Interface Module Implementation Guide for additional configuration data.

3.196 AUXDESC

Specific to Block(s) All Blocks


Description Auxiliary Descriptor
Data Type STRING
Range Array of strings
Default N/A

Config Load No

Active Loadable No
Access Lock View Only
Residence SR

Related Parameters N/A


Remarks Descriptors for alarms and events (fixed)

3.197 AUXDESC[0..10]

Specific to Block(s) CEE, CPM, SIMIOLIM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

- 312 -
Chapter 3 - Axxxx Parameters

3.198 AUXMEM

Specific to Block(s) ProfitCtl


Description Aux Memory()KB)
Data Type FLOAT64
Range ±1.7E+308
Default False
Config Load
Active Loadable No
Access Lock VIEWONLY
Residence
Related Parameters
Remarks

3.199 AUXOPT

Specific to SCM, RCM


Block(s)
Description Auxiliary Sequential Control Module (SCM) Request.
Data Type 32-Bit Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related AUXCMD, AUXREQAUXREQDATA[1..5]AUXSTSAUXUNIT
Parameters
Remarks Parameter for use with Batch Level 3. SCM AUXxx parameters are used for
interfacing to TotalPlant Batch. The SCM execution does not do anything special
based on the AUXxx parameter values. AUXOPT is reset to 0 on a successfully
processed Reset command to the SCM.

- 313 -
Chapter 3 - Axxxx Parameters

3.200 AUXREQ

Specific to Block(s) SCM, RCM


Description Auxiliary Sequential Control Module (SCM) Request.
Data Type 32-Bit Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters AUXCMD, AUXREQDATA[1..5], AUXSTS.
Remarks Parameter for use with Batch Level 3. The AUXREQ reset value is zero.

3.201 AUXREQDATA[1..5]

Specific to Block(s) SCM


Description Auxiliary SCM Request Data
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related AUXCMD, AUXUNITAUXREQDATA[1..5]
Parameters
Remarks Parameter for use with Batch Level 3. The AUXREQDATA[1..5] reset value is
NaN.

3.202 AUXSTS

Specific to Block(s) SCM


Description Auxiliary Sequential Control Module (SCM) Status.
Data Type 32-Bit Integer
Range N/A
Default 0
Config Load No
Active Loadable No

- 314 -
Chapter 3 - Axxxx Parameters

Access Lock Operator


Residence CEE
Related Parameters AUXCMD, AUXREQ, AUXSTS
Remarks Parameter for use with Batch Level 3. The AUXSTS reset value is zero.

3.203 AUXUNIT

Specific to SCM
Block(s)
Description Auxiliary Unit.
Data Type 32-Bit Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related AUXCMD, AUXREQ, AUXREQDATA[1..5], AUXOPT, AUXSTS.
Parameters
Remarks Parameter for use with Batch Level 3. SCM AUXxx parameters are used for
interfacing to TotalPlant Batch. The SCM execution does not do anything special
based on the AUXxx parameter values. AUXUNIT is reset to 0 on a successfully
processed Reset command to the SCM.

3.204 AV

Specific to Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC, Series C PICHANNEL, UIO - Series
Block(s) C DICHANNEL, HRBALG_HLPIUCO
Description Accumulated Value - Engineering Units value corresponding to the raw pulse
count.
Data Type 64-Bit Real Number, FLOAT64
Range N/A
Default NaN
Config No
Load
Active No
Loadable

- 315 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly, AppDevOnly


Residence CEE, IOM
Related AVSTSAVRAWSTSAVSTSC1C2
Parameters
Remarks AV represents the raw pulse count in engineering units based on the following
equation. AV = (C1/C2) * AVRAW This parameter value maps to AV (OP) of the
COUNTER16. The value displayed is the scaled value based on the scaling factor
(AVCONV) configuration.

NOTE This value is not displayed for a 32-bit counter as the detailed
display for a 32-bit counter does not display the accumulated value.

3.205 AV[0..7]

Specific to Block(s) Pulse Input IOM


Description Accumulated Value - Engineering Units value corresponding to the raw pulse
count.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

3.206 AVAILFL

Specific to SCM, RCM, UCM, CM


Block(s)
Description Resource is available
Data Type BOOLEAN
Range Off Resource is not available
On Resource is available
Default Off
Config Load No
Active No
Loadable

- 316 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related NUMOWNERSMAXOWNERS
Parameters
Remarks This flag indicates, whether the resource is available for (additional) requests.
AVAILFL is ON, if NUMOWNERS < (less than) MAXOWNERS AVAILFL is OFF, if
NUMOWNERS = MAXOWNERS

3.207 AVCONV

Specific to Block(s) HRBALG_HLPIUCO


Description Scaling Factor
Data Type FLOAT64
Range N/A
Default 0.0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks This parameter maps to the AVCONV of the COUNTER16.

NOTE This value is not displayed for a 32-bit counter as


this parameter is not applicable for a 32-bit counter.

3.208 AVERSION

Specific to RM
Block(s)
Description Application Version. Identifies the major revision of the RM application code.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active No
Loadable

- 317 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence Not Loaded Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Related
Parameters
Remarks

3.209 AVGDEPTH

Specific to Block(s) TCMI


Description Average Depth
Data Type UINT32
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

3.210 AVGFLOWRATE[1..200]

Specific to QIPACCHAN
Block
Description Average Flow Rate
Data Type Float64
Range N/A
Default NAN
Config No
Load
Active No
Loadable

- 318 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence CEE
Related MATERIALPATH[1..200], COMMAND, COMMANDSTATS[1..200], MXFERSTATUS
Parameters [1..200], MXFERSTATQ[1..200], OVERTOLRNCE[1..200],UNDERTOLRNCE[1..200],
POWERFAIL[1..200], DELIVEREDWGT[1..200], TARGETERROR[1..200], AVGSPILL
[1..200]
Remarks This is the resultant average flow rate value for the material transfer. This value
provides material transfer results and is valid after the material transfer for the
designated channel [1..200] in the QiMPACT cluster completes.

3.211 AVGICPNAKS

Specific to CEEFB, CEEACEFB, CEESIMC200FB, FIM, FIMS, OPC, ICG, IOLIM, IOLIMS,
Block(s) CEEC300, GEEFB, CEEUOC
Description Average ICP NAK Count
Data Type Float64
Enumeration OUTPUT
Range Greater than or equal to 0
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300,C200,ACE,SIMC200,FIM
Related
Parameters
Remarks Average Integrated Control Protocol (ICP) No Acknowledgements - The average
number of ICP not acknowledgements per second for all responder connections.

3.212 AVGICPSENDS

Specific to CEEFB, CEEACEFB, CEESIMC200FB, FIM, FIMS, OPC, ICG, IOLIM, IOLIMS,
Block(s) CEEC300, GEEFB, CEEUOC
Description Average Integrated Control Protocol (ICP) Sends.
Data Type Float64
Range Greater than or equal to 0
Default Off
Config Load No
Active No
Loadable

- 319 -
Chapter 3 - Axxxx Parameters

Access Lock ViewOnly


Residence C300, C200, ACE, SIMC200, FIM, UOC
Related N/A
Parameters
Remarks Average Integrated Control Protocol (ICP) Sends - The average number of Control
Data Access (CDA) and ICP retries per second for all responder connections.

3.213 AVGPKTRXRATE

Specific to Block(s) EIM EIP Protocol Block


Description Average Rx Pkt Rate
Data Type FLOAT32
Range -
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Average Receive PDT Packet Rate from C300 to EIM in Packets/Second.

3.214 AVGRCVBYTESPERSEC

Specific to Block(s) PCDI_MASTER


Description Average Bytes Received per Second
Data Type Float 32
Range
Default 0
Config Load No
Active Loadable No
Access Lock VeiwOnly
Residence CEE
Related Parameters
Remarks

- 320 -
Chapter 3 - Axxxx Parameters

3.215 AVGRCVMSGPERSEC

Specific to Block(s) PCDI_MASTER


Description Average Messages Received per Second
Data Type Float 32
Range
Default 0
Config Load No
Active Loadable No
Access Lock VeiwOnly
Residence CEE
Related Parameters
Remarks

3.216 AVGRDRRESPONSETIMEUS

Specific to Block EHPM


(s)
Description Amount of time (in seconds) it takes for a request to receive the
corresponding response.
Data Type UINT32, unit of time (seconds)
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related N/A
Parameters
Remarks

3.217 AVGSPILL[1..200]

Specific to QIPACCHAN
Block
Description Average Spill
Data Type Float64
Range N/A
Default NAN
Config No

- 321 -
Chapter 3 - Axxxx Parameters

Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MATERIALPATH[1..200], COMMAND, COMMANDSTATS[1..200], MXFERSTATUS
Parameters [1..200], MXFERSTATQ[1..200], OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200],
POWERFAIL[1..200], DELIVEREDWGT[1..200], TARGETERROR[1..200],
AVGFLOWRATE[1..200]
Remarks This is the resultant average spill value for the material transfer. This value
provides material transfer results and is valid after the material transfer for the
designated channel [1..200] in the QiMPACT cluster completes.

3.218 AVGWRTIME

Specific to Block C200 IOLINK, C300 IOLINK


(s)
Description Average Write Process Time. The average time it takes for an IOLINK Write to
complete.
Data Type Float32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related N/A
Parameters
Remarks Used only during development and debug.

3.219 AVGXMITBYTESPERSEC

Specific to Block(s) PCDI_MASTER


Description Average Bytes Transmitted per Second
Data Type Float 32
Range
Default 0
Config Load No
Active Loadable No

- 322 -
Chapter 3 - Axxxx Parameters

Access Lock VeiwOnly


Residence CEE
Related Parameters
Remarks

3.220 AVGXMITMSGPERSEC

Specific to Block(s) PCDI_MASTER


Description Average Messages Transmitted per Second
Data Type Float 32
Range
Default 0
Config Load No
Active Loadable No
Access Lock VeiwOnly
Residence CEE
Related Parameters
Remarks

3.221 AVRAW

Specific to Block(s) Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC
Description Raw Accumulated Value - Raw pulse count.
Data Type 32-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters AVRAWSTS
Remarks

Specific to Block(s) Series C PICHANNEL, UIO - Series C DICHANNEL


Description Raw Accumulated Value
Data Type UINT32
Range 0 to 4,294,967,295
Default 0
Config Load No

- 323 -
Chapter 3 - Axxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters AV
Remarks AVRAW represents the raw pulse count, where AV = (C1/C2) * AVRAW

3.222 AVRAW[0..7]

Specific to Block(s) Pulse Input IOM


Description Raw Accumulated Value - Raw pulse count.
Data Type 32-Bit Unsigned Integer
Range Greater-than or equal-to zero.
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

3.223 AVRAWSTS

Specific to Block(s) Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC
Description Bad Raw Accumulated Value Status.
Data Type Enumeration
Range Bad (0) Uncertn (1) Normal (2) Manual (3)
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters AVGICPNAKSAVGICPSENDSAVRAW
Remarks

Specific to Block(s) Series C PICHANNEL, UIO - Series C DICHANNEL


Description Raw Accumulated Value Status
Data Type ENUM
Range BAD(0) UNCERTAIN(1) NORMAL(2) MANUAL(3)
Default BAD(0)

- 324 -
Chapter 3 - Axxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters AVRAWAVSTS
Remarks AVRAWSTS represents the status of the raw accumulated value (AVRAW).

3.224 AVSTS

Specific to Block(s) Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC
Description Bad Accumulated Value Status
Data Type Enumeration
Range Bad (0) Uncertn (1) Normal (2) Manual (3)
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters AV
Remarks

Specific to Block(s) Series C PICHANNEL, UIO - Series C DICHANNEL


Description Accumulated Value Status
Data Type ENUM
Range BAD(0) UNCERTAIN(1) NORMAL(2) MANUAL(3)
Default BAD(0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters AVAVRAWSTS
Remarks AVSTS represents the status of the accumulated value (AV).

- 325 -
Chapter 3 - Axxxx Parameters

3.225 AWAITINGACK[1..24]

Specific to QIPACTERM
Block
Description Waiting for Controller to Acknowledge Last Material Transfer/Hand Add Complete
Data Type Boolean
Range Off(0) Not Waiting
On(1) Waiting
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 7 of the Status 1 byte in the input
assembly for the designated position [1-24].

3.226 AWAITINGACK[1..200]

Specific to QIPACCHAN
Block
Description Waiting for Controller to Acknowledge Last Material Transfer/Hand Add Complete
Data Type Boolean
Range Off(0) Not Waiting
On(1) Waiting
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 7 of the Status 1 byte in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

- 326 -
CHAPTER

4 BXXXX PARAMETERS

4.1 B[1..6] 331


4.2 BACKCALCCONN 331
4.3 BACKCALCIN 332
4.4 BACKCALCIN[1..3] 332
4.5 BACKCALCIN[1..8] 333
4.6 BACKCALCOUT 334
4.7 BACKCALCOUT[1..4] 334

4.8 BACKCALCOUT[1..8] 335


4.9 BACKLASHL 335
4.10 BACKLASHR 336
4.11 BACKUPRAMSCRUBERRS 336
4.12 BACKUPRAMSWEEPERR 337
4.13 BADAVRAW 337
4.14 BADCAL 338
4.15 BADCAL[0..numChans-1] 338
4.16 BADCAL[0..7] 339
4.17 BADCODE 339
4.18 BADCOMPTERM.FL 340
4.19 BADCOMPTERM.PR 340
4.20 BADCOMPTERM.SV 341
4.21 BADCTL.FL 341
4.22 BADCTLALM.FL 341
4.23 BADCTLALM.PR 342
4.24 BADCTLALM.SV 342
4.25 BADCTLALM.TM 343
4.26 BADCTLALM.TMO 343
4.27 BADCTLFL 344
4.28 BADCTLOPT 344
4.29 BADINACT[1..8] 345
4.30 BADINACTMINTM[1..8] 346
4.31 BADINDETTM[1..8] 346
4.32 BADINPTOPT[1..4] 347

- 327 -
Chapter 4 - Bxxxx Parameters

4.33 BADINPTOPT[1..8] 347


4.34 BADIPCSUM 348
4.35 BADOCOPT 348
4.36 BADOCOPTENB 349
4.37 BADOPTFLDSETTING 350
4.38 BADREPORTINSTANCE 350
4.39 BADUDPCSUM 350
4.40 BADPV 351
4.41 BADPV_DI_S 352
4.42 BADPVALLA, BADPVALLB 352
4.43 BADPVALM.FL 352
4.44 BADPVALM.PR 353
4.45 BADPVALM.SV 353
4.46 BADPVALM.TM 354

4.47 BADPVALM.TMO 354


4.48 BADPVALM.TP 355
4.49 BADPVFL 355
4.50 BADPVFL[0..numChans-1] 356
4.51 BADPVFL[1..NUMCHAN] 357
4.52 BADSO 357
4.53 BADSO[6..7] 358
4.54 BADUDPCSUM 359
4.55 BASENAME 359
4.56 BASEPERIOD 360
4.57 Base Template 361
4.58 BATCHEUDESC 362
4.59 BATCHEVTMRY 362
4.60 BATCHID 362
4.61 BATCHSIZECURR 363
4.62 BATCHSIZEDEF 364
4.63 BATTERYNOTOK 364
4.64 BATTERYNOTOKSFTAB 365
4.65 BCDSWSTS 365
4.66 BCOUT.ARWSTS 367
4.67 BCOUT.EUHI 367
4.68 BCOUT.EULO 368
4.69 BCOUT.HISELECT 368
4.70 BCOUT.INITREQ 369
4.71 BCOUT.INITVAL 369

- 328 -
Chapter 4 - Bxxxx Parameters

4.72 BCOUT.LOCALMAN 370


4.73 BCOUT.ONESHOT 370
4.74 BCOUT.ORFBSTS 371
4.75 BCOUT.ORFBVAL 371
4.76 BCOUT.OROFFSET 372
4.77 BCOUT.PROPOVRD 372
4.78 BECMPRICMD 373
4.79 BFF 373
4.80 BIAS 374
4.81 BINITIALIZE 374
4.82 BKGCOLOR 375
4.83 BKR 375
4.84 BKS 376
4.85 BKT 376

4.86 BKTBYPASS 376


4.87 BLCKCOMMENT1 377
4.88 BLCKCOMMENT2 377
4.89 BLCKCOMMENT3 378
4.90 BLCKCOMMENT4 378
4.91 BLDSVRPNT 379
4.92 BLKDSDSIZE 379
4.93 BLKTYPCOUNT 380
4.94 BLKTYPDESC 380
4.95 BLKTYPHELPTXT 380
4.96 BLKTYPLIB 381
4.97 BLKTYPSIZE 381
4.98 BLOCKINITCOUNTER 382
4.99 BLOCKLOGO 382
4.100 BLOCKREFERENCENAME.BREF 382
4.101 BLOCKREFERENCENAME.DESC 383
4.102 BLOCKREFERENCENAME.TYPE 383
4.103 BLOCKTYPEID 384
4.104 BLOCKTYPNAME 384
4.105 BLOCKTYPENAME 385
4.106 BLOCKMAPPING 386
4.107 BMODULES 386
4.108 BOOLMUX 387
4.109 BOOLPARAM 387
4.110 BOOLVAL[0…200] 387

- 329 -
Chapter 4 - Bxxxx Parameters

4.111 BOOL_VALUE 388


4.112 BOOLVALUEOFF 388
4.113 BOOLVALUEON 389
4.114 BOOTIMAGEVER 389
4.115 BOOTROMIMGCHKSMFAIL 390
4.116 BOXCON 390
4.117 BOXCONNSTATE [5..63] 391
4.118 BOXNUM 391
4.119 BOXREADSPPSAVG [5..63] 392
4.120 BOXREADSPPSMAX [5..63] 392
4.121 BOXTYPE 393
4.122 BOXWRITESPPSAVG [5..63] 393
4.123 BOXWRITESPPSMAX [5..63] 394
4.124 BPS 394

4.125 BPSDELAY 395


4.126 BPSDELAYREM 395
4.127 BRDGBCASTARR 396
4.128 BRDGLCLTYARR 396
4.129 BRDGPHYARR 397
4.130 BRDGLOGARR 397
4.131 BRDGRXPKTSARR 398
4.132 BRDNINCONGRUENTVIEWS 398
4.133 BREVISION 399
4.134 BRNGTEMPTRIP 399
4.135 BRNGTEMPTRIPACTED 399
4.136 BRNGTEMPALM.FL 400
4.137 BRNGTEMPALM.OPT 400
4.138 BRNGTEMPALM.PR 401
4.139 BRNGTEMPALM.SV 401
4.140 BSHILM 401
4.141 BSLOLM 402
4.142 BUFFERTIME 402
4.143 BUFTM_SET 403
4.144 BUFXMAX[0..5] 403
4.145 BUFXTOTAL[0..5] 403
4.146 BUFXUSED[0..5] 404
4.147 BURNOUTMODE 404
4.148 BVERSION 406
4.149 BYPCANCELOPT 406

- 330 -
Chapter 4 - Bxxxx Parameters

4.150 BYPASS 407


4.151 BYPPERM 407

4.1 B[1..6]

Specific to RegCalc
Block(s)
Description Individual bias for each input X[1] through X[6].
Data Type Real
Range N/A
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related X[1..6]
Parameters
Remarks BACKCALCIN establishes the initialization, override, and windup propagation
between connected Regulatory Control (RegCtl) and Analog Output (AO) Blocks.
This is one half of the BACKCALCIN/BACKCALCOUT connection.

4.2 BACKCALCCONN

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PID-PL PIDFF, PosProp,
Block(s) RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description Secondary Data structure associated with Regulatory Control Block output(s).
Contains Calculated Value CV) limits, initialization, and data windup status, and so
on. BACKCALCIN is associated with the secondary block, and therefore is related to
the number of outputs used on the primary block. Connecting BACKCALCIN to its
BACKCALCOUT “partner” is required in order to establish the initialization path
between the two blocks.
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable

- 331 -
Chapter 4 - Bxxxx Parameters

Access Lock Application Developer


Residence CEE
Related BACKCALCOUT, BACKCALCOUT[1..4], BACKCALCOUT[1..8].
Parameters
Remarks BACKCALCIN establishes the initialization, override, and windup propagation
between connected Regulatory Control (RegCtl) and Analog Output (AO) Blocks.
This is one half of the BACKCALCIN/BACKCALCOUT connection.

4.3 BACKCALCIN

Specific to All RegCtl Blocks except PulseCount and PulseLength.


Block(s)
Description Secondary Data structure associated with Regulatory Control Block output(s).
Contains Calculated Value ( CV) limits, initialization, and data windup status, and so
on. BACKCALCIN is associated with the secondary block, and therefore is related to
the number of outputs used on the primary block. Connecting BACKCALCIN to its
BACKCALCOUT ὔpartnerὕ is required in order to establish the initialization path
between the two blocks.
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BACKCALCOUT, BACKCALCOUT[1..4], BACKCALCOUT[1..8].
Parameters
Remarks BACKCALCIN establishes the initialization, override, and windup propagation
between connected Regulatory Control (RegCtl) and Analog Output (AO) Blocks.
This is one half of the BACKCALCIN/BACKCALCOUT connection.

4.4 BACKCALCIN[1..3]

Specific to DevCtl
Block(s)
Description BackCalc Record - Secondary Data structure associated with Device Control Block
output(s). This structure contains status information from the Digital Output
Channel (DOC) block. BACKCALCIN is associated with the secondary block, and
therefore is related to the number of outputs used on the primary block.
Connecting BACKCALCIN to its BACKCALCOUT ὔpartnerὕ is required in order to
establish the initialization path between the two blocks.
Data Type Structure
Range N/A

- 332 -
Chapter 4 - Bxxxx Parameters

Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BACKCALCOUT
Parameters
Remarks BACKCALCIN establishes the initialization propagation between connected Device
Control and Digital Output Channel Blocks. This is one half of the
BACKCALCIN/BACKCALCOUT connection.

4.5 BACKCALCIN[1..8]

Specific to Fanout
Block(s)
Description Secondary Data structure associated with the Fanout block output(s). Contains
Calculated Value ( CV) limits, initialization, and data windup status, and so on.
BACKCALCIN is associated with the secondary block, and therefore is related to the
number of outputs used on the primary block. Connecting BACKCALCIN to its
BACKCALCOUT ὔpartnerὕ is required in order to establish the initialization path
between the two blocks.
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BACKCALCOUT, X1BACKCALOUT, X2BACKCALOUT.
Parameters
Remarks BACKCALCIN establishes the initialization, override, and windup propagation
between connected Regulatory Control (RegCtl) and Analog Output (AO) blocks. This
is one half of the BACKCALCIN/BACKCALCOUT connection.

- 333 -
Chapter 4 - Bxxxx Parameters

4.6 BACKCALCOUT

Specific to AOC, DOC, PWM Channel, AutoMan, Fanout, PID, PIDFF, PID-PL, PosProp,
Block(s) REEOUT, UCNOUT, HIWAYOUT, HAOCHANNEL
Description BackCalc Record - Secondary Data structure associated with Regulatory Control
Block input(s). Contains Calculated Value ( CV) limits, initialization, and data windup
status, and so on. BACKCALCOUT is associated with the primary block, and
therefore is related to the number of inputs used on the secondary block
Connecting BACKCALCIN to its BACKCALCOUT ὔpartnerὕ is required in order to
establish the initialization path between the two blocks.
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE (ACE for UCNOUT and HIWAYOUT)
Related BACKCALCIN, BACKCALCIN[1..8].
Parameters
Remarks BACKCALCOUT establishes the initialization, override, and windup propagation
between connected Regulatory Control (RegCtl) and Analog Output (AO) blocks.
This is one half of the BACKCALCIN/BACKCALCOUT connection.

4.7 BACKCALCOUT[1..4]

Specific to OvrdSel
Block(s)
Description Secondary Data structure associated with Regulatory Control block input(s).
Contains Calculated Value ( CV) limits, initialization, and data windup status, and so
on. BACKCALCOUT is associated with the primary block, and therefore is related to
the number of inputs used on the secondary block. Connecting BACKCALCIN to its
BACKCALCOUT “partner” is required in order to establish the initialization path
between the two blocks.
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable

- 334 -
Chapter 4 - Bxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related BACKCALCIN
Parameters
Remarks BACKCALCOUT establishes the initialization, override, and windup propagation
between connected Regulatory Control (RegCtl) and Analog Output (AO) blocks.
This is one half of the BACKCALCIN/BACKCALCOUT connection.

4.8 BACKCALCOUT[1..8]

Specific to Switch
Block(s)
Description Secondary Data structure associated with Regulatory Control block input(s).
Contains Calculated Value ( CV) limits, initialization, and data windup status, and so
on. BACKCALCOUT is associated with the primary block, and therefore is related to
the number of inputs used on the secondary block. Connecting BACKCALCIN to its
BACKCALCOUT “partner” is required in order to establish the initialization path
between the two blocks.
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BACKCALCIN
Parameters
Remarks BACKCALCOUT establishes the initialization, override, and windup propagation
between connected Regulatory Control (RegCtl) and Analog Output (AO) blocks. This
is one half of the BACKCALCIN/BACKCALCOUT connection.

4.9 BACKLASHL

Specific to Block(s) PosProp


Description Backlash Lower compensation of actuator (in seconds).
Data Type Real
Range 0.0 to 60.0 seconds
Default 0.0 seconds
Config Load Yes
Active Loadable No

- 335 -
Chapter 4 - Bxxxx Parameters

Access Lock Supervisor


Residence CEE
Related Parameters
Remarks

4.10 BACKLASHR

Specific to Block(s) PosProp


Description Backlash Raise Compensation of actuator (in seconds).
Data Type Real
Range 0.0 to 60.0 seconds
Default 0.0 seconds
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

4.11 BACKUPRAMSCRUBERRS

Specific to C300, FIM4, PGM, EHPM


Block(s)
Description Corrected Backup RAM Sweep
Data Type Boolean
Range Off (0) - No backup RAM errors detected On (1) - Backup RAM errors detected and
corrected
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300, PGM, FIM4, EHPM
Related BACKUPRAMSWEEPERR,SOFTFAIL
Parameters
Remarks Errors detected within Backup DRAM are corrected through a scrub operation.
Detected error count should remain low. However, if it gets above a certain
threshold, this parameter is set to On to indicate the softfail condition. When
BCAKUPRAMSCRUBERRS is On, the EHPM function block issues a diagnostic
alarm.

- 336 -
Chapter 4 - Bxxxx Parameters

4.12 BACKUPRAMSWEEPERR

Specific to C300, PGM, FIM4 , EHPM


Block(s)
Description Uncorrectable Backup RAM Sweep - Indicates status of detected errors in Backup
RAM.
Data Type Boolean
Range Off (0) - No Errors detected in Backup RAM On (1) - Errors detected in Backup RAM
but unable to correct
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related BACKUPRAMSCRUBERRS, SOFTFAIL
Parameters
Remarks When On, indicates the presence of one or more single bit memory faults which
could not be corrected by the DRAM scrub process. When BACKUPRAMSWEEPERR
is on, the C300 and EHPM function block issues a diagnostic alarm.

4.13 BADAVRAW

Specific to Series C PICHANNEL


Block(s)
Description Bad Pulse AVRAW
Data Type UINT32
Range 0 to 4,294,967,295
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence IOM
Related INPUTSTREAM
Parameters
Remarks BADAVRAW represents the raw bad pulse count. This parameter is applicable only
when a channel is configured for dual stream input configuration where “Good”
and “Bad” pulses are accumulated.

- 337 -
Chapter 4 - Bxxxx Parameters

4.14 BADCAL

Specific to AIC, AOC


Block(s)
Description Bad Calibration Indicator - On a per channel basis, this parameter indicates if
calibration is bad or missing.
Data Type Boolean
Range Ok (0) BadCalibration (1)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CABTYPNAMECALBIAS
Parameters
Remarks The BADCAL indicator may also indicate that calibration was aborted after inputs
were sampled or outputs were referenced. This condition is cleared by a successful
calibration.

4.15 BADCAL[0..numChans-1]

Specific to AIM, AOM


Block(s)
Description Bad Calibration Indicator - On a per channel basis, this parameter indicates if
calibration is bad or missing.
Data Type Boolean
Range Ok (0) BadCalibration (1)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CABTYPNAMECALBIAS
Parameters
Remarks The BADCAL indicator may also indicate that calibration was aborted after inputs
were sampled or outputs were referenced. This condition is cleared by a successful
calibration.

- 338 -
Chapter 4 - Bxxxx Parameters

4.16 BADCAL[0..7]

Specific to Chassis HART AI IOM, HART AO IOM


Block(s)
Description Bad Calibration Indicator - On a per channel basis, this parameter indicates if
calibration is bad or missing.
Data Type Boolean
Range OK (0) BadCalibration (1)
Default OK (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CALBIAS
Parameters
Remarks The BADCAL indicator may also indicate that calibration was aborted after inputs
were sampled or outputs were referenced. This condition is cleared by a successful
calibration. The calibration status for each channel is supplied in the channel
status bytes of the assembly published by the IO module.

4.17 BADCODE

Specific to Block(s) All IO Channels, SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


Description Reason for Bad States
Data Type Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 339 -
Chapter 4 - Bxxxx Parameters

4.18 BADCOMPTERM.FL

Specific to Block FLOWCOMP


(s)
Description Bad Compensation Term Flag - Shows when compensation term is bad.
Data Type Boolean
Range False - Compensation term alarm does not exist True - Compensation term
alarm exists
Default False
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200, C300, ACE
Related
Parameters
Remarks

4.19 BADCOMPTERM.PR

Specific to FLOWCOMP
Block(s)
Description Bad Compensation Term Priority - Defines the priority of a Bad Compensation term
alarm.
Data Type Enumeration ALPRIOR
Range None (0) Alarm is not reported to the system and is not annunciated
Journal Alarm is written to the event file, where it can be accessed for alarm
(1) and event reports, or event display on a Station. JOURNAL priority
alarms do not appear in the alarm summary display.
Low (2), Alarm is displayed in the alarm zone at the bottom of a Station display
High (3), to bring new alarms to the attention of operators and/or directed to an
Urgent (4) alarm/event printer. It also appears in the alarm summary display in
low intensity yellow (for LOW), in yellow (for HIGH), and in red (for
URGENT).
Default None
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks

- 340 -
Chapter 4 - Bxxxx Parameters

4.20 BADCOMPTERM.SV

Specific to FLOWCOMP
Block(s)
Description Bad Compensation Term Severity - Assigns a relative severity to alarm by specifying
a weight in the range of 0 to 15. The specified weight determines when the
specified alarm is processed relative to the other alarms.
Data Type 16-Bit Integer
Range 0 to 255
Default 0 - Lowest severity
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks

4.21 BADCTL.FL

Specific to Block(s) PROFCONOUT


Description BADCTL FL
Data Type BOOL
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters
Remarks BADCTL FL

4.22 BADCTLALM.FL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PID-PL, PIDFF, PosProp,
Block(s) RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Bad Control Alarm Flag
Data Type Boolean
Range Off (0) On (1)

- 341 -
Chapter 4 - Bxxxx Parameters

Default Off (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BADCTLFL, BADCTLALM.PR, BADCTLALM.SV.
Parameters
Remarks

4.23 BADCTLALM.PR

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PID-PL, PIDFF, PosProp,
Block(s) RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Bad Control Alarm Priority - Defines the priority of a Bad Control alarm.
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related BADCTLFL, BADCTLALM.FL, BADCTLALM.SV.
Parameters
Remarks

4.24 BADCTLALM.SV

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PID-PL, PIDFF, PosProp,
Block(s) RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Bad Control Alarm Severity
Data Type 16-Bit Integer
Range 0 to 255
Default 0
Config Load Yes
Active No
Loadable

- 342 -
Chapter 4 - Bxxxx Parameters

Access Lock Engineer


Residence CEE
Related BADCTLFL, BADCTLALM.FL, BADCTLALM.PR.
Parameters
Remarks

4.25 BADCTLALM.TM

Specific to AUTOMAN, ENHREGCALC, FANOUT, OVRDSEL, PID, PID-PL, PIDER, PIDFF,


Block(s) POSPROP, RATIOBIAS, RATIOCTL, REGCALC, REMCAS, REGSUMMER, and SWITCH

Description Bad Control Alarm Time in seconds.


Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual on-delay time for bad control
alarmsonly when the BADCTLOPT is configured as NOSHED.However, the
BADCTLALM.TM and BADCTLOPT parameters are validated only when the block is
loaded and the subsequent changes made from the Monitoring view. For more
information about on-delay time configuration for BADCTLALM, refer to Control
Builder Components Theory Guide.

4.26 BADCTLALM.TMO

Specific to AUTOMAN, ENHREGCALC, FANOUT, OVRDSEL, PID, PID-PL, PIDER, PIDFF,


Block(s) POSPROP, RATIOBIAS, RATIOCTL, REGCALC, REMCAS, REGSUMMER, and SWITCH

Description Bad Control Alarm Off Delay Time


Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable

- 343 -
Chapter 4 - Bxxxx Parameters

Access Lock EngineerAppDev


Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for bad control
alarms.

4.27 BADCTLFL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PID-PL, PIDFF, PosProp,
Block(s) RampSoak, RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Bad Control Flag - Indicates if a Bad Control condition exists.
Data Type Boolean
Range Off (0): Bad Control condition does not exist. On (1): Bad Control condition exists.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BADCTLALM.FL, BADCTLALM.PR, BADCTLALM.SV.
Parameters
Remarks

4.28 BADCTLOPT

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PID-PL, PIDFF, PosProp,
Block(s) RegSummer, RemCas, RatioBias, RegCalc, and Switch.
Description Bad Control Option - Indicates what to do when Calculated Variable (CV) is NaN
(that is, BADCTLFL = On).
Data Type Enumeration BADCTLOPT
Range No_Shed (0): MODE remains unchanged; Output (OP) is
held at the last good value.
ShedHold (1): MODE is shed to Manual, and MODEATTR
goes to Operator. External mode switching is
disabled, and Output (OP) is held at the
current value.
ShedLow (2): MODE is shed to Manual, and MODEATTR
goes to Operator. External mode switching is
disabled, and Output (OP) goes to
OPEXLOLM.
ShedHigh (3): MODE is shed to Manual, and MODEATTR
goes to Operator. External mode switching is
disabled, and Output (OP) goes to

- 344 -
Chapter 4 - Bxxxx Parameters

OPEXHILM.
ShedSafe (4): MODE is shed to Manual, and MODEATTR
goes to Operator. External mode switching is
disabled, and Output (OP) goes to SAFEOP.
If SAFEOP = NaN, OP is held at the last good
value.
Default No_Shed (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related BADCTLFLESWENB, MODE, MODEATTR, OP, BADOCOPT
Parameters
Remarks The mode shed option configured in the BADCTLOPT comes into effect whenever
there is an IO communication loss and a bad control occurs within the time delay
specified in the BADOCOPT parameter. However, if the BADCTLOPT is configured
as No_Shed, the mode shed occurs after the specified time delay.

4.29 BADINACT[1..8]

Specific to CheckBool Logic Block


Block(s)
Description Bad Input Action
Data Type Enumeration
Range (0) OFF (1) ON (2) HoldLast
Default OFF
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related BADINDETTM[1..8], BADINACTMINTM[1..8]
Parameters
Remarks Specifies the action to be taken in the event of an invalid input. If the value of INSTS
[1..8] is kBadValSts, the value passed through the block, from IN[1..8] to OUT[1..8],
will be modified based on the configuration of this parameter. If BADINACT is
configured as OFF then OUT[1..8] is set equal to OFF If BADINACT is configured as
ON then OUT[1..8] is set equal to ON If BADINACT is configured as HoldLast then
OUT[1..8] is set equal to LASTIN[1..8] However, the duration which OUT[1..8] will be
held at this configured value is determined by BADINDETTM[1..8] and
BADINACTMINTM[1..8]

- 345 -
Chapter 4 - Bxxxx Parameters

4.30 BADINACTMINTM[1..8]

Specific to CheckBool Logic Block


Block(s)
Description Bad Input Action Minimum Time
Data Type Float64
Range 0- 8000 sec
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related BADINDETTM[1..8], BADINACT[1..8]
Parameters
Remarks Specifies the minimum length of time (in seconds) that OUT[1..8] will be held at its
BADINACT[1..8] configuration value.

4.31 BADINDETTM[1..8]

Specific to CheckBool Logic Block


Block(s)
Description Bad Input Detection Threshold Time
Data Type Float64
Range 0- 8000 sec
Default 0
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related BADINACT[1..8], BADINACTMINTM[1..8]
Parameters
Remarks Specifies the delay time (in seconds) required before OUT[1..8] will be changed to
the value configured in BADINACT[1..8]. The input status must remain “BAD” for
the entire detection threshold time before the configured action is taken.

- 346 -
Chapter 4 - Bxxxx Parameters

4.32 BADINPTOPT[1..4]

Specific to Block OvrdSel


(s)
Description Bad Input Option - Indicates if bad inputs (NaN) should be included in the input
selection process.
Data Type Enumeration BADINPTOPT
Range IgnoreBad (0): Ignore bad inputs. IncludeBad (1): Include bad inputs.
Default IncludeBad (1)
Config Load Yes
Active Loadable No
Access Lock Engineer / Application Developer
Residence CEE
Related
Parameters
Remarks

4.33 BADINPTOPT[1..8]

Specific to Block Switch


(s)
Description Bad Input Option - Indicates if bad inputs (NaN) should be included in the input
selection process.
Data Type Enumeration BADINPTOPT
Range IgnoreBad (0): Ignore bad inputs. IncludeBad (1): Include bad inputs.
Default IncludeBad (1)
Config Load Yes
Active Loadable No
Access Lock Engineer / Application Developer
Residence CEE
Related
Parameters
Remarks

- 347 -
Chapter 4 - Bxxxx Parameters

4.34 BADIPCSUM

Specific to FTEB, FIM4, PGM, C300 , EHPM, TCMI


Block(s)
Description Bad Internet Protocol (IP) Checksum - Identifies the number of FTE IP messages
which were received but determined as having bad IP checksums.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FTEB, FIM4, PGM, EHPM
Related
Parameters
Remarks

Specific to Block(s) EIM, UOC


Description IP Checksum Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (TCP statistics, see C300 definition)

4.35 BADOCOPT

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PID-PL, PIDFF,
Block(s) RampSoak, RatioBias, RatioCtl, RegCalc, RegSummer, RemCas, and Switch.
Description Bad Output Conn Option
Data Type FLOAT32
Range 0 - Changes the mode to MANual and mode attribute to Operator after an IO
communication loss. 1 to 60 sec - Changes the mode to MANual and mode attribute
to Operator, if the IO communication is not restored within the specified time delay,
after an IO communication loss. However, if the IO communication is restored
within the specified time delay, the block does not shed its mode or change the
mode attribute. Nan - Initializes the upstream blocks but does not change the mode
of the block or mode attribute after an IO communication loss.

- 348 -
Chapter 4 - Bxxxx Parameters

Default 0
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related MODEATTR
Parameters
Remarks This parameter is configurable only when the BADOCOPTENB parameter is
enabled. This parameter is applicable only when the output of the regulatory
control block is connected to the analog and digital outputs. However, the users are
allowed to access or store values to this parameter. This parameter value is
retained through RAM Retention Startup. For a Fanout block, a single parameter is
sufficient to determine the behavior of the Fanout block in the event of a
communication loss with IO.

4.36 BADOCOPTENB

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PID-PL, PIDFF,
Block(s) RampSoak, RatioBias, RatioCtl, RegCalc, RegSummer, RemCas, and Switch.
Description Enable Bad Output Connection Option
Data Type Enumeration
Range Enable - You can specify a time delay for the Regulatory Control blocks to shed the
mode. Disable - The mode sheds to MANual immediately after an IO communication
loss.
Default Disable
Config Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related BADOCOPT UNCMDCHGALM.FL UNCMDCHGALM.SV UNCMDCHGALM.PR
Parameters
Remarks The BADOCOPT, UNCMDCHGALM.FL, UNCMDCHGALM.SV, and
UNCMDCHGALM.PR parameters are enabled in the configuration form only if the
BADOCOPTENB parameter is enabled. The value of the BADOCOPTENB parameter
can be changed on the Project view before loading the Control Module. This
parameter value is retained through the RAM Retention Startup. This parameter is
not a part of Checkpoint data and is not restored on Checkpoint Restore operation.

- 349 -
Chapter 4 - Bxxxx Parameters

4.37 BADOPTFLDSETTING

Specific to Block(s) EIM


Description Invalid optFlds Settings
Data Type BOOL
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

4.38 BADREPORTINSTANCE

Specific to Block(s) EIM


Description Invalid Report Instance
Data Type BOOL
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

4.39 BADUDPCSUM

Specific to FTEB, C300, FIM4, PGM, EHPM, TCMI


Block(s)
Description Bad User Datagram Protocol (UDP) Checksum - Identifies the number of FTE UDP
messages which were received but determined as having bad UDP checksums.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No

- 350 -
Chapter 4 - Bxxxx Parameters

Loadable
Access Lock ViewOnly
Residence C300, FTEB, FIM4, PGM, EHPM
Related BADIPCSUM
Parameters
Remarks

Specific to Block(s) EIM, UOC


Description UDP Checksum Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (UDP statistics, see C300 definition)

4.40 BADPV

Specific to Block(s) DIC


Description Indicates the Digital Input process variable (PV)status.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 351 -
Chapter 4 - Bxxxx Parameters

4.41 BADPV_DI_S

Specific to Block(s) UIO, DI32-24VDC, DI16-VAC, DI16-DRYCT, DI16-VACDC


Description Bad Process Value Flag
Data Type BOOLEAN
Range Off PV is not bad

On PV is bad
Default ON
Config Load No
Active Loadable

Access Lock ViewOnly


Residence IOM Block
Related
Parameters

Remarks This parameter indicates that a bad PV value has been detected at this data
point.

4.42 BADPVALLA, BADPVALLB

Specific to Block(s) DI-24, DI-HV, DI-SOE, UIO


Description Bad Process Value All
Data Type BLIND
Range 4 bytes
Default Not applicable
Config Load No
Access Lock ViewOnly
Active Loadable No
Residence IOM
Related Parameters Not applicable
Remarks

4.43 BADPVALM.FL

Specific to DataAcq, DevCtl, PID-PL, DIGACQ, ROC, MAINIBV, LEVELCOMP, HTMOTOR,


Block(s) LTMOTOR, SOLENOID, VALVEDAMPER
Description Bad Process Variable (PV) Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)

- 352 -
Chapter 4 - Bxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BADPVALM.PRBADPVALM.SVDEVHIALM.PRHIALM.SVHIALM.TYPE DevCtl Only:
Parameters GPVNUMDATANUMDINPUTS
Remarks DevCtl Only: Illegal if NUMDINPUTS = 0.

4.44 BADPVALM.PR

Specific to DataAcq, DevCtl, PID-PL, DIGACQ, ROC, MAINIBV, LEVELCOMP, HTMOTOR,


Block(s) LTMOTOR, SOLENOID, VALVEDAMPER
Description Bad PV Alarm Priority
Data Type Enumeration ALMPR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DataAcq only: BADPVFL, BADPVALM.FL, BADPVALM.SV, PVSTSFL.BAD DevCtl only:
Parameters BADPVFL, BADPVALM.FL, BADPVALM.SV, NUMDATA, NUMDINPUTS. Others:
BADPVFL, BADPVALM.FL, BADPVALM.SV
Remarks DevCtl only: Illegal if NUMDINPUTS = 0.

4.45 BADPVALM.SV

Specific to DataAcq, DevCtl, PID-PL, DIGACQ, ROC, MAINIBV, LEVELCOMP, HTMOTOR,


Block(s) LTMOTOR, SOLENOID, VALVEDAMPER
Description Bad PV Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable

- 353 -
Chapter 4 - Bxxxx Parameters

Access Lock Engineer


Residence CEE
Related DevCtl Only: BADPVFL, BADPVALM.FL, BADPVALM.PRNUMDATA, NUMDINPUTS.
Parameters DataAcq Only: BADPVFL, BADPVALM.FL, BADPVALM.PR, PVSTSFL.BAD. Others:
BADPVFL, BADPVALM.FL, BADPVALM.PR.
Remarks DevCtl only: Illegal if NUMDINPUTS = 0.

4.46 BADPVALM.TM

Specific to DIGACQ, PID-PL, ROC, DATAACQ


Block(s)
Description Bad PV Alarm in seconds.
Data Type UNIT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure the individual on-delay time for bad PV
alarms. For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

4.47 BADPVALM.TMO

Specific to Block(s) DIGACQ, PID-PL, ROC, DATAACQ


Description Bad PV Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for bad PV
alarms.

- 354 -
Chapter 4 - Bxxxx Parameters

4.48 BADPVALM.TP

Specific to PID-PL
Block(s)
Description Bad PV Alarm Shed Time - Number of seconds that the PV can be bad (NaN) before
the block generates a BADCTL alarm.
Data Type Float64
Range >0, NaN
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related BADPVFL, BADPVALM.FL, BADPVALM.PR, BADPVALM.SV, CTLEQN.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations. NaN disables this shed.

4.49 BADPVFL

Specific to SIFLAGARRCH, SINUMARRCH, SITEXTARRCH, REQFLAGARRAY, REQNUMARRAY,


Block(s) REQTEXTARRAY, AIC, PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH
Description Bad PV Flag - Flag that indicates that an error response was received for the last
request sent by this request block. Note that this flag is set to TRUE for both local
errors (communication errors that prevented the request from being sent out on
the network, for example) and remote errors (the target device could not process
the request and so sent an explicit failure status). For alarming on errors, connect
the ERRFL to a Flag Block and configure the Flag Block to send an Alarm when
ERRFL is TRUE.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related ERRFL
Parameters

- 355 -
Chapter 4 - Bxxxx Parameters

Specific to Block PM I/O: AICHANNEL, DICHANNEL, DI, DI24V, DISOE Series C: DICHANNEL,
(s) PICHANNEL, UIO
Description Bad Process Variable (PV) Flag. Shows that a bad PV has been detected for this
data point.
Data Type Boolean
Range Off: PV is okay. On: PV is bad.
Default On
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter indicates that a bad PV value has been detected at this data
point.

Specific to Block(s) ROC


Description Bad PV Flag - Invalid PV
Data Type Boolean
Range TRUE,FALSE
Default ON
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks Indicates that a bad PV has been detected for this data point.

4.50 BADPVFL[0..numChans-1]

Specific to EIP Digital Input modules


Block(s)
Description Bad Process Variable (PV) Flag - Shows that a bad PV has been detected for this
channel of IO module.
Data Type BOOLEAN
Range l Off: PV is okay
l On: PV is bad
Default Off
Config Load No
Active Loadable No

- 356 -
Chapter 4 - Bxxxx Parameters

Access Lock ViewOnly


Residence NoLoad
Related None
Parameters
Remarks It is indexed by channel number.

4.51 BADPVFL[1..NUMCHAN]

Specific to Block DI, DI24, DISOE, HAICHANNEL (PM I/O); DI-HV, DI-24 (Series C I/O)
(s)
Description Bad Process Variable (PV) Flag. Shows that a bad PV has been detected for
this data point.
Data Type Boolean
Range Off: PV is okay. On: PV is bad.
Default On
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks

4.52 BADSO

Specific to Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Bad Input State Flag - When On, this parameter indicates the current value of
Output State (SO) is does not necessarily reflect the value of the module's terminal
screws.
Data Type Boolean
Range Off (0): Current value of Output State (SO) is valid. On (1): Current value of Output
State (SO) is invalid.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Affects Channels 6-7 only.

- 357 -
Chapter 4 - Bxxxx Parameters

Specific to Block(s) Series C PICHANNEL


Description Bad Output State Flag
Data Type BOOLEAN
Range OFF(0) ON(1)
Default OFF (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related SO
Parameters
Remarks BADSO indicates whether the current value of the output state is valid or
invalid.
l OFF indicates the current value of the output state is VALID.
l ON indicates the current value of the output state is INVALID.

4.53 BADSO[6..7]

Specific to Pulse Input IOM


Block(s)
Description Bad Input State Flag - When On, this parameter indicates the current value of
Output State (SO) is does not necessarily reflect the value of the module's terminal
screws..
Data Type Boolean
Range Off (0): Current value of Output State (SO) is valid. On (1): Current value of Output
State (SO) is invalid
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Affects channels 6-7 only.

- 358 -
Chapter 4 - Bxxxx Parameters

4.54 BADUDPCSUM

Specific to FTEB, C300, FIM4, PGM, EHPM, TCMI


Block(s)
Description Bad User Datagram Protocol (UDP) Checksum - Identifies the number of FTE UDP
messages which were received but determined as having bad UDP checksums.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FTEB, FIM4, PGM, EHPM
Related BADIPCSUM
Parameters
Remarks

Specific to Block(s) EIM, UOC


Description UDP Checksum Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (UDP statistics, see C300 definition)

4.55 BASENAME

Specific to Block(s) MASTER RECIPE


Description Base Name of the Master Recipe
Data Type STRING
Range NA
Default Empty
Config Load
Active Loadable Yes

- 359 -
Chapter 4 - Bxxxx Parameters

Access Lock APPDEVONLY


Residence SR, SCAN
Related Parameters
Remarks

4.56 BASEPERIOD

Specific to CEE, DNET_IM, CEEACE, CEESIMC200, CEEC300


Block(s)
Description Base Execution Period

Data Type ENUM


Range 5ms (0) 25ms (1) 50ms (2)
Default 50ms

Config Yes
Load

Active No
Loadable
Access Application Developer
Lock

Residence All platforms which host CEE

Related PERIOD
Parameters

Remarks The base period must be set in accordance with the software personality image that is
loaded to the CPM controller. The CEEREX2 personality image is used with a 50 ms base
cycle. The FEEREX2 personality is used with the 5 ms base cycle. If the configured value
is not supported by the personality image, an error will be returned upon load of the
CPM/CEE block. The 50 ms base period (or 50 ms CEE) supports block execution periods
from 50 ms to 2000 ms. The 5 ms base period (or 5 ms CEE) supports block execution
periods from 5 ms to 200 ms. The Base Period for C300CEE (In Saturn) is fixed at 50ms.

Specific to CEEUOC
Block(s)
Description Base Execution Period

Data Type ENUM


Range 50ms (0) 500ms (1)
Default 50ms

Config Yes
Load

- 360 -
Chapter 4 - Bxxxx Parameters

Access Application Developer


Lock

Residence UOC Platform which hosts CEE

Related PERIOD
Parameters

Remarks The base period must be set in accordance with the software personality image that is
loaded to the UOC controller. If the configured value is not supported by the personality
image, an error will be returned upon load of the CPM/CEE block. The 50 ms base period
(or 50 ms CEE) supports block execution periods from 50 ms to 1000 ms. The 500 ms
base period (or 500 ms CEE) supports block execution periods from 500 ms to 10000 ms.

Specific to CEECN100
Block(s)
Description Base Execution Period

Data Type ENUM

Exposure NONE
Range 20 ms (0)
Default 20 ms

Config Yes
Load
Access Application Developer
Lock

Residence CN100 Platform which hosts CEE

Related PERIOD
Parameters

Remarks CEECN100 as of today supports only 20ms Base Period. The 20 ms base period (or 20 ms
CEE) supports block execution periods from 20 ms to 1000 ms.

4.57 Base Template

Specific to Block(s) Server, Asset, Alarm Group


Description Base Template name - Indicates the Base Template that is used for this
block.
Data Type String
Range Limit: 5 characters
Default Null
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

- 361 -
Chapter 4 - Bxxxx Parameters

4.58 BATCHEUDESC

Specific to Block(s) RCM


Description Batch Size Engineering Units
Data Type String
Range
Default %
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

4.59 BATCHEVTMRY

Specific to CEEC300, CEEUOC


Block(s)
Description Batch Events Memory - Indicates the relative size of the buffer size allocated for
batch events.
Data Type Enumeration of EventBufferSize
Range None (0) Small (1) Medium (2) Large (3)
Default Small
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks It’s a configuration parameter for batch events. It can be configured for below
values : Small : 120 events Medium : 240 events Large : 720 events

4.60 BATCHID

Specific to Block(s) RCM, ACT


Description Control Recipe ID
Data Type String
Range 23 characters
Default

- 362 -
Chapter 4 - Bxxxx Parameters

Config Load RCM - Yes ACT - No


Active Loadable No
Access Lock RCM - Engineer ACT - ViewOnly
Residence CEE
Related Parameters BATCHSIZEDEF, BATCHSIZECURR
Remarks A string associated with the current batch.

Specific to MR
Block(s)
Description Control Recipe ID
Data Type String
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks MR does not contain any batch ID. However, the batch ID is automatically
created when an activitiy is created.

4.61 BATCHSIZECURR

Specific to ACT
Block(s)
Description Current batch size
Data Type FLOAT64
Range 0 - Maximum Float 64
Default 100
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related BATCHSIZEDEF, BATCHEUDESC
Parameters
Remarks The size of the current batch units are defined by the BATCHEUDESC parameter.
This parameter can only be changed when the activity is in the initializing or Pre-
Exec states. The initial value for this parameter is the Default Batch Size
(BATCHSIZEDEF) of the Associated Entity.

- 363 -
Chapter 4 - Bxxxx Parameters

4.62 BATCHSIZEDEF

Specific to ACT
Block(s)
Description Default batch size
Data Type FLOAT64
Range 0 - Maximum Float 64
Default 100
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related BATCHSIZECURR, BATCHEUDESC
Parameters
Remarks This parameter defines the default size of the batch. Units are defined by the
BATCHEUDESC parameter. This parameter can only be changed when the activity
is in the initializing or Pre-Exec states.

4.63 BATTERYNOTOK

Specific to CPM, FIM4, PGM, C300 , EHPM


Block(s)
Description Battery Not Okay - Indicates status of CPM battery.
Data Type Enumeration of BATTERYNOTOK
Range OK (0) Sufficiently charged battery is present.
UNDERVOLTAGE (1) Battery is either in a low voltage
condition, not connected, or not present.

OVERVOLTAGE (2) Battery is over voltage


UNKNOWN (3) Unknown
Default OK (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, C300, FIM4, PGM, EHPM
Related BATTERYNOTOKSFTAB, SOFTFAIL
Parameters
Remarks A diagnostic alarm is issued from the function block whenever BATTERYNOTOK
status is not OK. Since the PGM and the FIM4 do not use a battery, the status of
the battery will always be OK.

- 364 -
Chapter 4 - Bxxxx Parameters

4.64 BATTERYNOTOKSFTAB

Specific to C300, PGM, FIM4 , EHPM


Block(s)
Description Battery Not Okay - Indicates status of CPM battery. Used to display battery state on
Soft failure tab.
Data Type Enumeration of BATTERYNOTOK
Range OK (0) Sufficiently charged battery is present.
UNDERVOLTAGE (1) Battery is either in a low voltage
condition, not connected, or not present.

OVERVOLTAGE (2) Battery is over voltage


UNKNOWN (3) Unknown
Default OK (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related BATTERYNOTOK, SOFTFAIL
Parameters
Remarks This Parameter used to Display the Battery Status on Soft Failures Tab. Since the
PGM and the FIM4 do not use a battery, the status of the battery will always be OK.

4.65 BCDSWSTS

Specific to C300, FIM4, PGM, EHPM


Block(s)
Description Device Index Switches Changed
Data Type Boolean
Range On, Off
Default Off
Config No
Load
Active No
Loadable

- 365 -
Chapter 4 - Bxxxx Parameters

Access Lock ViewOnly


Residence C300, FIM4, PGM, EHPM
Related SOFTFAIL
Parameters
Remarks Flag is set to On indicating a Softfail condition whenever the Device Index switch
value is changed after the controller has completed startup. Also a diagnostic alarm
is issued from the function block when this flag is set. Restoring the original Device
Index switch value resets this flag to Off and causes the diagnostic alarm to return
to normal.

Specific to EIM
Block(s)
Description Device Index Switches Changed
Data Type Boolean
Range NA
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks True if the FTE device index switches have been changed since the device was
powered on. If the FTE device index switches are changed and the device is
restarted, the FTE IP address may change.

Specific to UOC
Block(s)
Description FTE Device Index Switches Changed
Data Type Boolean
Range N/A
Default Off
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Soft failure condition. FTE device index switches have been changed since initial
startup. The device may use a different IP address if power cycled.

- 366 -
Chapter 4 - Bxxxx Parameters

4.66 BCOUT.ARWSTS

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Back Calculation Output Anti-Reset Windup Status - Indicates the anti-reset
windup status that is provided to the primary.
Data Type Enumeration
Range Normal Hi Lo HiLo
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks

4.67 BCOUT.EUHI

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Back Calculation Output Engineering Units High - Defines the Engineering Units
high limit that corresponds to 100 percent of the scale.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks

- 367 -
Chapter 4 - Bxxxx Parameters

4.68 BCOUT.EULO

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Back Calculation Output Engineering Units Low - Defines the Engineering Units
low limit that corresponds to 0 percent of the scale.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks

4.69 BCOUT.HISELECT

Specific to REEOUT
Block(s)
Description Back Calculation Output High Select- Shows the override feedback type (high or
low selector) that is provided to the primary.
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

- 368 -
Chapter 4 - Bxxxx Parameters

4.70 BCOUT.INITREQ

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Back Calculation Output Initialization Request - Indicates if the primary is being
requested to initialize.
Data Type Boolean
Range Off - Initialization is not requested On - Initialization is requested
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks

4.71 BCOUT.INITVAL

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Back Calculation Output Initialization Value - Indicates the initialization value
that is provided to the primary.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks

- 369 -
Chapter 4 - Bxxxx Parameters

4.72 BCOUT.LOCALMAN

Specific to REEOUT
Block(s)
Description Back Calculation Output Local Manual - Reads the local manual status that is
provided to the primary.
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

4.73 BCOUT.ONESHOT

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Back Calculation Output One Shot - Indicates the one-shot initialization value that
is provided to the primary requesting one-shot initialization.
Data Type 32-Bit Integer
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks

- 370 -
Chapter 4 - Bxxxx Parameters

4.74 BCOUT.ORFBSTS

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Back Calculation Output Override Feedback Status - Indicates the override
feedback status that is provided to the primary.
Data Type Enumeration
Range NotCon Sel NotSel
Default (0) NotCon
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks This value will not change, because override strategies are not supported between
the ACE supervisory controller and the Universal Control Network (UCN) Process
Manager controllers.

4.75 BCOUT.ORFBVAL

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Back Calculation Output Override Feedback Value - Indicates the value that is
provided to the primary for override feedback initialization.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks This value will not change, because override strategies are not supported between
the ACE supervisory controller and the Universal Control Network (UCN) Process
Manager controllers.

- 371 -
Chapter 4 - Bxxxx Parameters

4.76 BCOUT.OROFFSET

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Back Calculation Output Override Offset - Indicates the override offset option
that is provided to the primary.
Data Type Boolean
Range Off, On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related BACKCALCOUT
Parameters
Remarks

4.77 BCOUT.PROPOVRD

Specific to REEOUT
Block(s)
Description Back Calculation Propagation Override - Reads propagation override value that
is provided to the primary.
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

- 372 -
Chapter 4 - Bxxxx Parameters

4.78 BECMPRICMD

Specific to RM, C300, PGM and FIM4 FBs, TCMI


Block(s)
Description Become Primary Command
Data Type Boolean
Range True (0) False (1)
Default True (0)
Config Load No
Active No
Loadable
Access Lock Operator Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence C300, FIM4, PGM
Related
Parameters
Remarks Used to command an unsynchronized secondary module to transition into the
primary role in the absence of a partner module. This parameter has edge trigger
semantics and always returns OFF when read.

Specific to Block(s) UOC


Description Become Primary
Data Type Boolean
Range N/A
Default

Config Load Yes


Active Loadable

Access Lock Operator


Residence NOLOAD
Related Parameters

Remarks (redundancy parameters, see C300 definition)

4.79 BFF

Specific to Block(s) PIDFF


Description Feedforward Input Bias
Data Type Real
Range N/A
Default 0
Config Load
Active Loadable No

- 373 -
Chapter 4 - Bxxxx Parameters

Access Lock Operator


Residence CEE
Related Parameters FF, PV, SIFL, SP.
Remarks

4.80 BIAS

Specific to UAI, AI16-100MS


Block(s)

Description Bias
Data Type FLOAT32
Range Minimum: -99999.0
Maximum: +99999.0
Default 0.0
Config Load Yes
Active
Loadable

Access Lock EngineerAppDev


Residence IOM Block
Related
Parameters

Remarks This parameter contains the value for the Bias. (Please refer to the UAI module spec
and tech data sheet for more details)

4.81 BINITIALIZE

Specific to HARTDEVICE (Chassis I/O)


Block(s)
Description Initialization Status - Indicates the initialization status for the device block. (See
remarks below for usage of this parameter.)
Data Type Boolean
Range
Default FALSE (0)
Config No
Load
Active No
Loadable

- 374 -
Chapter 4 - Bxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks The device block is considered initialized only when the block has successfully
received Device Information from the connected device. This parameter is used by
the Software Multiplexer to check that the device FB is fully initialized and that it
has received essential parameters like ManufacterID, Device Type, Serial no, and
so on.

4.82 BKGCOLOR

Specific to Text Comment block


Block(s)
Description Use this parameter to specify the background color of the Text Comment block.
Data Type UINT32
Range 1-72
Default 12
Config Load No
Active Yes
Loadable
Access Lock APPDEVONLY
Residence ERDB only
Related
Parameters
Remarks For more information on active loadable parameter, refer to the About
Editing/Loading parameters while active section in the Control Building User's
Guide.

4.83 BKR

Specific to Block(s) HTMOTOR


Description Breaker in Remote
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters BKS
Remarks Used as permissive interlock.

- 375 -
Chapter 4 - Bxxxx Parameters

4.84 BKS

Specific to Block(s) HTMOTOR


Description Breaker in Service
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters
Remarks Used as permissive interlock.

4.85 BKT

Specific to Block(s) HTMOTOR


Description Breaker in Test
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters
Remarks Used as permissive interlock.

4.86 BKTBYPASS

Specific to Block(s) HTMOTOR


Description BYPASS when BKT
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No

- 376 -
Chapter 4 - Bxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters BYPASSBKT
Remarks Bypasses all permissive and protective interlocks when BKT is ON.

4.87 BLCKCOMMENT1

Specific to All Blocks


Block(s)
Description Block Comment 1
Data Type String
Range Length : 40 characters
Default N/A
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence SR
Related BLCKCOMMENT2, BLCKCOMMENT3, BLCKCOMMENT4
Parameters
Remarks Lets you enter pertinent comment to be associated with this block. Must have
template license for identification tab to apply.

4.88 BLCKCOMMENT2

Specific to All Blocks


Block(s)
Description Block Comment 2.
Data Type String
Range Length : 40 characters
Default N/A
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence SR
Related BLCKCOMMENT1, BLCKCOMMENT3, BLCKCOMMENT4
Parameters
Remarks Lets you enter pertinent comment to be associated with this block .Must have
template license for identification tab to apply.

- 377 -
Chapter 4 - Bxxxx Parameters

4.89 BLCKCOMMENT3

Specific to All Blocks


Block(s)
Description Block Comment 3
Data Type String
Range Length : 40 characters
Default N/A
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence SR
Related BLCKCOMMENT1, BLCKCOMMENT2, BLCKCOMMENT4
Parameters
Remarks Lets you enter pertinent comment to be associated with this block . Must have
template license for identification tab to apply.

4.90 BLCKCOMMENT4

Specific to All Blocks


Block(s)
Description Block Comment 4
Data Type String
Range Length : 40 characters
Default N/A
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence SR
Related BLCKCOMMENT1, BLCKCOMMENT2, BLCKCOMMENT3
Parameters
Remarks Lets you enter pertinent comment to be associated with this block . Must have
template license for identification tab to apply.

- 378 -
Chapter 4 - Bxxxx Parameters

4.91 BLDSVRPNT

Specific to All Series C I/O channel blocks and PM I/O channel blocks
Block(s)
Description Enable Server Point Build
Data Type BOOLEAN
Range FALSE TRUE
Default FALSE
Config Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence IOLINK, IOLIM
Related
Parameters
Remarks When this parameter is enabled, the non-HART channels are built as Server points.
When this parameter is disabled, the non-HART channels are not built as Server
points. However, this parameter is enabled for the HART channels, by default.

ATTENTION The “Enable Server Point Build” parameter cannot be


disabled when a channel is loaded.This parameter is not applicable for
the SPM and SVPM channel blocks.

4.92 BLKDSDSIZE

Specific to Block All blocks


Description Dynamic State Data (DSD) size of this block
Data Type INT32
Range Greater than or equal to zero
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter represents the DSD size of a particular block.

- 379 -
Chapter 4 - Bxxxx Parameters

4.93 BLKTYPCOUNT

Specific to Block(s) CEE, CEEC300, CEEUOC, CEECN100


Description Block Type Count - The number of instances currently loaded to the
controller.
Data Type 32-Bit Integer
Range 0 to 4, 258,848 (instances)
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related
Parameters
Remarks

4.94 BLKTYPDESC

Specific to Block(s) CEE, CEEC300, CEEUOC, CEECN100


Description Block Type Description
Data Type String (one dimensional array)
Range 0 to 400 (maximum string size is 32 characters)
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related Parameters
Remarks The description string used for the block type name.

4.95 BLKTYPHELPTXT

Specific to CEE, CEEC300, CEEUOC, CEECN100


Block(s)
Description Block Type Help Text
Data Type String
Range Length: 256 characters maximum
Default 0
Config Load No
Active No
Loadable

- 380 -
Chapter 4 - Bxxxx Parameters

Access Lock View Only


Residence SR
Related
Parameters
Remarks The statement is: “Regarding block sizes, some blocks utilize additional memory for
configuration specifc data, which is not included below. Please refer to the
documentation for the list of blocks.”

4.96 BLKTYPLIB

Specific to CEE, CEEC300, CEEUOC, CEECN100


Block(s)
Description CCL Library
Data Type String (one dimensional array)
Range maximum string size is 20 characters
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related
Parameters
Remarks This string will be null for CEE static block types. Will show respective CCL library
for CCL block types, such as "FTW_PULSEIN_000".

4.97 BLKTYPSIZE

Specific to CEE, CEEC300, CEEUOC, CEECN100


Block(s)
Description Block Type Size
Data Type 32-Bit Integer
Range 0 to 4,258,848
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related BLKTYPHELPTXT
Parameters
Remarks This value does not include any memory required for the block specific
configuration and run-time data.

- 381 -
Chapter 4 - Bxxxx Parameters

4.98 BLOCKINITCOUNTER

Specific to Block(s) ProfitCtl


Description Block Init Counter
Data Type INT16
Range ±32767
Default 0
Config Load
Active Loadable No
Access Lock VIEWONLY
Residence
Related Parameters
Remarks

4.99 BLOCKLOGO

Specific to Block(s) SCM


Description Logo for Contained CMs
Data Type BLOB
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

4.100 BLOCKREFERENCENAME.BREF

Specific to MAP
Block(s)
Description Block reference
Data Type BLOCKID
Default None
Config Yes
Load
Active No
Loadable

- 382 -
Chapter 4 - Bxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related BLOCKREFERENCENAME.TYPE
Parameters
Remarks A block reference is a Tag or a Tag.basic block which is referred for a Unit indirectly
during execution. The block reference must have a derivation parent (or
grandparent - in the lineage) that matches the associated block reference type.
Example: If CM01 has a Numeric block configured inside, CM01 can be configured
as the function reference only if type is configured as numeric.

4.101 BLOCKREFERENCENAME.DESC

Specific to Block MAP


(s)
Description Block reference description
Data Type String
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks It is the descriptive text for the block reference. It is configured in the PDE of
the Map Block.

4.102 BLOCKREFERENCENAME.TYPE

Specific to MAP
Block(s)
Description Block reference type
Data Type BLOCKID
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related BLOCKREFERENCENAME.DESC
Parameters
Remarks A block reference type is Experion PKS resident block type or UDT associated with a
block reference. It defines the type used when referring to the reference. It is
configured in PDE of the Map block.

- 383 -
Chapter 4 - Bxxxx Parameters

4.103 BLOCKTYPEID

Specific to CAB and CDB Types, MAP


Block(s)
Description Block type identification - Holds an identifier value unique to each CAB or CDB type.
The identifier value is used for ensuring that block types and instances are
correctly matched across import changes even if there are any name changes.
Data Type String
Range 40 characters
Default Assigned by build-time services at the conclusion of a type edit session.
Config Yes
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

4.104 BLOCKTYPNAME

Specific to All CAB types


Block(s)
Description Block Type Name - A name for the CAB type. This includes both library name and
block type name.
Data Type String
Range l For CAB types that run only on ACE, a maximum of 101 characters are
supported.
l For CAB types that run on both C300 and ACE, a maximum of 82 characters
are supported.
Default Not Applicable
Config Yes
Load
Active No
Loadable
Access Lock View Only
Residence CEE
Related CABTYPNAME
Parameters
Remarks BLOCKTYPNAME is displayed in the following format: “<block library name>.<block
type name>”. It is displayed near the top left corner of the CAB development
environment window. It is also displayed in the column “CAB Friendly Name” on the
CAB Types Info tab of both the CEE-ACE block and the CEE-C300 block.

- 384 -
Chapter 4 - Bxxxx Parameters

Specific to DEVCTL,PROFCONIN,PROFCONOUT, PROFITCONTROLLER, AUTOMAN,


Block(s) ENHREGCALC, FANOUT, INCRSUMMER, OVRDSEL, PID, PIDER, PIDFFD,
PROFITLOOP, PODPROP, PULSECOUNT, PULSELENGTH, RAMPSOAK, RATIOBIAS,
RATIOCTL, REEOUT, REGCALC, REGSUMMER, REMCAS, SWITCH, TIMER.
Description This parameter is used for describing the name of the alternative block type.
Data Type String
Range
Default CTUD
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter is used for representing the alternative block type.

4.105 BLOCKTYPENAME

Specific to DEVCTL,PROFCONIN,PROFCONOUT, PROFITCONTROLLER, AUTOMAN,


Block(s) ENHREGCALC, FANOUT, INCRSUMMER, OVRDSEL, PID, PIDER, PIDFFD,
PROFITLOOP, PODPROP, PULSECOUNT, PULSELENGTH, RAMPSOAK, RATIOBIAS,
RATIOCTL, REEOUT, REGCALC, REGSUMMER, REMCAS, SWITCH, TIMER.
Description This parameter is used for describing the name of the block type.
Data Type String
Range
Default CTUD
Config No
Load
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related
Parameters
Remarks This parameter is used for representing the block type.

Specific to Block(s) PROFCONIN, PROFCONOUT, PROFCON


Description PROFITCONTROLLER IN Block Type
Data Type STRING
Range NA
Default PROFITCTLIN
Config Load

- 385 -
Chapter 4 - Bxxxx Parameters

Active Loadable No
Access Lock APPDEVONLY
Residence
Related Parameters
Remarks

4.106 BLOCKMAPPING

Specific to Block Master Recipe, Step, Transition, Sync, Handler, Recipe Step, Text Comment
(s)

Description This parameter is used to identify the Block type origin (used in Multi Versions
Comparison).
Data Type String
Range

Default

Config Load ERDB only


Active Loadable

Access Lock Operator


Residence ERDB only
Related
Parameters

Remarks

4.107 BMODULES

Specific to Block Cabinets


(s)
Description It defines the second column of the cabinet to configure the IO modules to
the cabinet.
Data Type BLOCKID
Range —
Default —
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks

- 386 -
Chapter 4 - Bxxxx Parameters

4.108 BOOLMUX

Specific to SignalSel
Block(s)
Description Flag for Boolean Mux Selection.
Data Type Boolean
Range OFF (0) Boolean MUX selection
ON (1) Integer MUX selection
Default OFF
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related SELMETHOD, SELXFL[1..6]
Parameters
Remarks This parameter represents the flag to choose between Integer MUX selection and
Boolean Mux selection. If the flag is set to On, Boolean selection will be
performed,otherwise Integer selection will performed.

4.109 BOOLPARAM

Specific to Block(s) EIM


Description Data Attribute Boolean
Data Type BOOL
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence NOLOAD
Related Parameters
Remarks

4.110 BOOLVAL[0…200]

Specific to Block(s) EIM


Description Boolean Value
Data Type BOOLEAN
Range NA

- 387 -
Chapter 4 - Bxxxx Parameters

Default Off
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters NUMBOOL
Remarks Accessed as an array. Mapped to custom Boolean parameters.

4.111 BOOL_VALUE

Specific to BOOLEAN_TAG, Scalar UDT Block


Block(s)
Description BOOLEAN Value: This is the Parameter where the value read from control Logix
PLC is Displayed or the Value to be written to the PLC needs to be entered.
Data Type BOOLEAN
Range 0 or 1
Default 0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related Access Lock
Parameters
Remarks Configuration of Access Lock Parameter present on this block determines whether
it has been configured as a Parameter to be read or a Parameter to be written.

4.112 BOOLVALUEOFF

Specific to TypeConvert, Push


Block(s)
Description Used to convert Boolean values to Enumeration.
Data Type Enumeration TCGENERICENUM
Range Enum0 to Enum63
Default Enum0
Config Load Yes
Active No
Loadable

- 388 -
Chapter 4 - Bxxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks This is applicable for conversion between Boolean and Enumeration values. The
output Enumeration value will be whatever the BOOLVALUEOFF is set to.

4.113 BOOLVALUEON

Specific to TypeConvert, Push


Block(s)
Description Used to convert Boolean values to Enumeration.
Data Type Enumeration TCGENERICENUM
Range Enum0 to Enum63
Default Enum1
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks This is applicable for conversion between Boolean and Enumeration values. The
output Enumeration value will be whatever the BOOLVALUEON is set to.

4.114 BOOTIMAGEVER

Specific to Block(s) C300, PGM, FIM4, EHPM, EIM, UOC, IO RACK, TCIM
Description Boot Image Version
Data Type String
Range Length : 32 Characters
Default Null, TCMI_100.2-05.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related N/A
Parameters
Remarks Release version of Experion PKS module boot firmware currently in the
controller.

- 389 -
Chapter 4 - Bxxxx Parameters

4.115 BOOTROMIMGCHKSMFAIL

Specific to Block(s) C300, FIM4, FIM8, PGM


Description ROM Boot image is corrupt soft failure
Data Type BOOLEAN

Range On, Off

Default Off

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence C300, FIM4, FIM8, PGM

Related Parameters ROMAPPIMGCHKSMFAIL

Remarks After restart the module will likely be unusable.

4.116 BOXCON

Specific to HRBALG_REG, HRBALG_PIUAI block


Blocks
Description Box Connector
Data Type BLOCKID
Range Not Applicable
Default Not Applicable
Config. Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter holds a reference to the box emulation with which the algorithm
emulation is registered.

- 390 -
Chapter 4 - Bxxxx Parameters

4.117 BOXCONNSTATE [5..63]

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Box connection state
Data Type Enumeration
Range 0–Inactive
1–Active
Default 0–Inactive
Config. Load No
Active Loadable
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter displays the state of the box connection.

4.118 BOXNUM

Specific to Box Hiway Responder Block (HRB) (HRBBOX_CB) , (HRBBOX_EC), HRBBOX_HLPIU,


Blocks and HRBBOX_LXPIU
Description Box Number
Data Type UINT8
Range 5 to 63
Default 5
Config. Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter specifies the number of the box on the TDC2000 Hiway that the
emulation associated with this Box HRB is replacing. This address is used during
communication between the Box HRB and its associated EHBs.

Specific to HRBALG_REG, HRBALG_AI, HRBALG_DIHRBALG_PIUAI, HRBALG_HLPIUAO,


Blocks HRBALG_HLPIUDI, HRBALG_HLPIUDO HRBALG_HLPIUCO, HRBALG_HLPIUAC,
HRBALG_HLPIUDC
Description BoxNumber
Data Type UINT8
Range 5 to 63
Default 5
Config. No

- 391 -
Chapter 4 - Bxxxx Parameters

Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The parameter receives the updated value from box HRB when algorithm
registration is successful.

4.119 BOXREADSPPSAVG [5..63]

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Cumulative reads average
Data Type FLOAT64
Range
Default 0
Config. Load No
Active Loadable
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter displays the average cumulative read of the box.

4.120 BOXREADSPPSMAX [5..63]

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Cumulative reads maximum
Data Type FLOAT64
Range
Default 0
Config. Load No
Active Loadable
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter displays the maximum cumulative read of the box.

- 392 -
Chapter 4 - Bxxxx Parameters

4.121 BOXTYPE

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Hiway Box Type
Data Type Array of Enumeration
Range HLPIU, LLPIU, LEPIU, ELEPIU, CB, and EC
Default
Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter displays the emulating box type.

Specific to HRBBOX_CB and HRBBOX_ECHRBALG_PIUAI, HRBALG_HLPIUAO, HRBALG_


Blocks HLPIUDI, HRBALG_HLPIUDO, HRBALG_HLPIUCO, HRBALG_HLPIUAC, HRBALG_
HLPIUDC
Description Hiway Box Type
Data Type Enumeration
Range 0 (None)
1 CB 7 EC
Default 1 CB
Config. Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter displays the emulating box type.

4.122 BOXWRITESPPSAVG [5..63]

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Cumulative writes average
Data Type FLOAT64
Range
Default 0
Config. Load No
Active Loadable

- 393 -
Chapter 4 - Bxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks This parameter displays the average cumulative write of the box.

4.123 BOXWRITESPPSMAX [5..63]

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Cumulative writes maximum
Data Type FLOAT64
Range
Default 0
Config. Load No
Active Loadable
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter displays the maximum cumulative write of the box.

4.124 BPS

Specific to CONTROLMODULE
Block(s)
Description Block Process Special - Specify if Control Module is to support Process Special
Trigger.
Data Type Boolean
Range 0 OFF Does not support process
special trigger
1 ON Supports process special
trigger
Default OFF
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks The BPS parameter is only available with an execution period selection of NONE for
an ACE controller. The Control Module only executes when an operator, program,
or another function block does a store to a process special trigger.

- 394 -
Chapter 4 - Bxxxx Parameters

4.125 BPSDELAY

Specific to CONTROLMODULE
Block(s)
Description Block Process Special Delay - Specify the integer value that represents the number
of seconds before a Sequential Control Module or another function block, such as a
CAB, is to trigger the Block Process Special execution.
Data Type Float64
Range 0 to 86400
Default 0
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks Subsequent stores to this parameter are ignored until the block executes. Storing a
value of zero to this parameter causes the BPS to execute immediately.

4.126 BPSDELAYREM

Specific to CONTROLMODULE
Block(s)
Description Block Process Special Delay Remaining - Shows the integer value that represents
the number of seconds remaining before the BPS is to be triggered.
Data Type Float64
Range 0 to 86400
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 395 -
Chapter 4 - Bxxxx Parameters

4.127 BRDGBCASTARR

Specific to Block(s) ELCN_BRG


Description Locality identifier array for LCN/ELCN nodes
Data Type Enumeration
Range none    (0)  - indexed node does not exist on the LCN or ELCN
LCN    (1) - indexed node exists on the LCN
ELCN (2) - indexed node exists on the ELCN
BOTH (3) - indexed node exists on the LCN and ELCN
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge View
Remarks

4.128 BRDGLCLTYARR

Specific to Block(s) ELCN_BRG


Description Locality identifier array for LCN/ELCN nodes
Data Type Enumeration
Range none    (0)  - indexed node does not exist on the LCN or ELCN

LCN    (1) - indexed node exists on the LCN


ELCN (2) - indexed node exists on the ELCN
BOTH (3) - indexed node exists on the LCN and ELCN
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge View
Remarks

- 396 -
Chapter 4 - Bxxxx Parameters

4.129 BRDGPHYARR

Specific to Block(s) ELCN_BRG


Description Phys packets [pkts] count

Data Type 32-Bit Integer


Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge View
Remarks

4.130 BRDGLOGARR

Specific to Block(s) ELCN_BRG


Description Logical packets [pkts] count

Data Type 32-Bit Integer


Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge View
Remarks

- 397 -
Chapter 4 - Bxxxx Parameters

4.131 BRDGRXPKTSARR

Specific to Block(s) ELCN_BRG


Description Total Rx packets [pkts] count

Data Type 32-Bit Integer


Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge View
Remarks

4.132 BRDNINCONGRUENTVIEWS

Specific to Block(s) ELCN_BRG


Description ELCN Bridge Partner has Different Network View
Data Type Boolean
Range ON, OFF
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related SOFTFAIL
Parameters

Remarks The redundant partner does not see the same LCN nodes. Check LCN cable
status.

- 398 -
Chapter 4 - Bxxxx Parameters

4.133 BREVISION

Specific to RM
Block(s)
Description Boot Revision. Identifies the minor revision of the RM boot code.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Not Loaded
Related
Parameters
Remarks Requests to read or store to any RM parameter must come from the Supervisory
platform (through Control Builder or Server).

4.134 BRNGTEMPTRIP

Specific to Block(s) HTMOTOR


Description Bearing Temperature Trip
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters BRNGTEMPTRIPACTED RESETFIRSTUP
Remarks Used as protection interlock.

4.135 BRNGTEMPTRIPACTED

Specific to HTMOTOR
Block(s)
Description Bearing Temperature Tripped
Data Type Boolean
Range ON-OFF
Default OFF

- 399 -
Chapter 4 - Bxxxx Parameters

Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BRNGTEMPTRIP RESETFIRSTUP
Parameters
Remarks Indicates that the corresponding permissive interlock has occurred and
changed the output state to STOP.

4.136 BRNGTEMPALM.FL

Specific to Block(s) HTMOTOR


Description Bearing temperature Trip Alarm flag
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters BRNGTEMPALM.OPTBRNGTEMPALM.PRBRNGTEMPALM.SV
Remarks

4.137 BRNGTEMPALM.OPT

Specific to Block(s) HTMOTOR


Description Bearing temperature Trip Alarm option
Data Type Enumeration
Range ENABLE DISABLE
Default ENABLE
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters BRNGTEMPALM.FLBRNGTEMPALM.PRBRNGTEMPALM.SV
Remarks

- 400 -
Chapter 4 - Bxxxx Parameters

4.138 BRNGTEMPALM.PR

Specific to Block(s) HTMOTOR


Description Bearing temperature Trip Alarm priority
Data Type Enumeration
Range NONE JOURNAL LOW HIGH URGENT
Default LOW
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters BRNGTEMPALM.FLBRNGTEMPALM.OPTBRNGTEMPALM.SV
Remarks

4.139 BRNGTEMPALM.SV

Specific to Block(s) HTMOTOR


Description Bearing temperature Trip Alarm severity
Data Type 16-Bit Integer
Range 0-15
Default 0
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters BRNGTEMPALM.FLBRNGTEMPALM.OPTBRNGTEMPALM.PR
Remarks

4.140 BSHILM

Specific to Block(s) RATIOBIAS


Description Bias High Limit - Defines bias high limit value in Engineering Units.
Data Type Real
Range
Default 50
Config Load Yes
Active Loadable No

- 401 -
Chapter 4 - Bxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters BSLOLM
Remarks

4.141 BSLOLM

Specific to Block(s) RATIOBIAS


Description Bias Low Limit - Defines bias low limit value in Engineering Units.
Data Type Real
Range
Default -50
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters BSHILM
Remarks

4.142 BUFFERTIME

Specific to EIM
Block(s)
Description Buffer Time
Data Type UINT32
Range 4294967295
Default 0
Config
Load
Active No
Loadable
Access Lock AppDevOnly
Residence EIM
Related
Parameters
Remarks The attribute BufTm (see Figure 26) shall specify the time interval in milliseconds
for the buffering of internal notifications caused by data-change (dchg), quality-
change (qchg), dataupdate (dupd) by the BRCB for inclusion into a single report.
Default values is read from the CID/ICD file.

- 402 -
Chapter 4 - Bxxxx Parameters

4.143 BUFTM_SET

Specific to Block(s) EIM


Description bufTime Setting
Data Type ENUM
Range NA
Default Dynamic
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

4.144 BUFXMAX[0..5]

Specific to IOLIM, Secondary IOLIM, C300 IOLINK, FIM


Block(s)
Description Maximum Number of Memory Buffers. Shows the maximum number of memory
buffers used, where the array index (0 to 5) corresponds to the buffer size.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

4.145 BUFXTOTAL[0..5]

Specific to IOLIM, Secondary IOLIM, C300 IOLINK, FIM


Block(s)
Description Total Number of Memory Buffers. Shows the total static allocation of memory
buffers, where the array index (0 to 5) corresponds to the buffer size.
Data Type 16-Bit Unsigned Integer
Range N/A

- 403 -
Chapter 4 - Bxxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

4.146 BUFXUSED[0..5]

Specific to IOLIM, Secondary IOLIM, C300 IOLINK, FIM


Block(s)
Description Number of Memory Buffers Used. Shows the current number of memory buffers
used in the Monitoring mode, where the array index (0 to 5) corresponds to the
buffer size.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

4.147 BURNOUTMODE

Specific to UAI
Block(s)

Description Burn Out Mode


Data Type ENUM
Range
0 DownScale

1 UpScale

2 UserValue

3 None

Default 0 None

- 404 -
Chapter 4 - Bxxxx Parameters

Config Yes
Load

Active No
Loadable

Access Application Developer


Lock

Residence IOM Block


Related SENSRTYP_AI_C
Parameters
USERCFGVAL
PVEULO_AI_C
PVEUHI_AI_C
Remarks This parameter provides the user the ability to define specific behavior when a Burnout
condition is detected.
This parameter is applicable to most Sensor types (Please refer to the UAI module spec
and tech data sheet for more details).
l If this parameter is set to DownScale, the controller will set the PV to the
corresponding PVEULO_AI_C whenever the Burnout condition is reported by the
module
l If this parameter is set to UpScale, the controller will set the PV to the corresponding
PVEUHI_AI_C whenever the Burnout condition is reported by the module
l If this parameter is set to UserValue, the controller will set the PV to the
corresponding USERCFGVAL whenever the Burnout condition is reported by the
module
l If this parameter is set to None, the controller will take no action on the PV
whenever the Burnout condition is reported by the module

The burnout configuration option is disabled for the following sensor types:

l Linear
l 4_20_mA
l 0_20_mA
l 0_1_V
l 0_2_V
l 0_5_V
l 0_10_V
l 1_5_V
l -1_1_V
l -2_2_V
l -5_5_V
l -10_10_V

- 405 -
Chapter 4 - Bxxxx Parameters

4.148 BVERSION

Specific to RM
Block(s)
Description Boot Version. Identifies the major revision of the RM boot code.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

4.149 BYPCANCELOPT

Specific to SCM
Block(s)
Description Bypass Cancel Option
Data Type Enumeration
Range (0) None - Bypassed/forced Transition Conditions are not canceled/cleared (1)
OnScmReset - Bypassed/forced Transition Conditions are canceled/cleared on
SCM Reset command (2) OnTransEnd - Bypassed/forced Transition Conditions are
canceled/cleared when the Transition evaluation finishes (Transition changes
from Enabled to Disabled state)
Default None
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks Selects SCM behavior on when to cancel/clear Transition Condition Bypass/Force
requests. Selection applies to all Transitions of all Handlers in the SCM, but can be
changed while the SCM is executing.

- 406 -
Chapter 4 - Bxxxx Parameters

4.150 BYPASS

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Permissive and interlock bypass
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related BYPPERM, OI[0..2], OP, PI[0..2]. DEVCTL Only: NUMDOUTS
Parameters
Remarks Can be changed only when BYPPERM = On. When On, override and permissive
interlocks are bypassed. Default to Off, when BYPPERM is set to Off. DEVCTL Only:
Illegal if NUMDOUTS = 0

4.151 BYPPERM

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Override and Permissive Bypass Permit
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related BYPASS, OI[0..2], PI[0..2]. DEVCTL Only: NUMDOUTS
Parameters
Remarks When On, allows BYPASS to be set to bypass the Permissive and Override
Interlocks - OI[0..2] and PI[0..2]. DEVCTL Only:Illegal if NUMDOUTS = 0.

- 407 -
CHAPTER

5 CXXXX PARAMETERS

5.1 C[1..8] 422


5.2 C[1..10] 422
5.3 C[1..10].BYPPERM 423
5.4 C[1..10].BYPREQ 423
5.5 C[1..10].CONFIGCODE 424
5.6 C[1..10].CONFIGDESC 424
5.7 C[1..10].CONFIGSTS 425

5.8 C[1..10].DESC 425


5.9 C[1..10].EXECCODE 425
5.10 C[1..10].EXECDESC 426
5.11 C[1..10].EXECSTS 426
5.12 C[1..10].EXPR 427
5.13 C[1..10].EXPRPCODE 427
5.14 C[1..10].FL 428
5.15 C[1..10].GATEASGN 428
5.16 C[1..10].INVOKFL 428
5.17 C1 429
5.18 C1[0..7] 430
5.19 C2 431
5.20 C2[0..7] 433
5.21 C3 433
5.22 C3[0..5] 434
5.23 C300COMMAND 435
5.24 C300IP 435
5.25 C300MAXTEMP [1...3] 435
5.26 C300MINTEMP [1...3] 436
5.27 C300STATE 436
5.28 C300MODTYPE 437
5.29 C300TEMP [1...3] 437
5.30 CABCOMMAND 438
5.31 CABEXECTIMER 438
5.32 CABINETNAME 439

- 408 -
Chapter 5 - Cxxxx Parameters

5.33 CABINETPOSITION 440


5.34 CABINSTCOUNT 440
5.35 CABPREFRDTIM 441
5.36 CABPREFWRTIM 442
5.37 CABSOFTVER 442
5.38 CABSTATE 443
5.39 CABTYPNAME 443
5.40 CALBIAS 444
5.41 CALBIAS[0..numChans-1] 444
5.42 CALBIAS[0..7] 445
5.43 CALIBALLA 445
5.44 CALIBALLB 446
5.45 CALIBFTA1STS 446
5.46 CALIBFTA2STS 447

5.47 CALIBRATION 447


5.48 CALIBRJSTS 448
5.49 CALIBSTS 448
5.50 CAPABILITY 449
5.51 CAPVALOPT 450
5.52 CAPSAFEVAL 450
5.53 CARDTYPE 451
5.54 CASREQFL 451
5.55 CASSTS 452
5.56 CATNUMBER 452
5.57 CBADREADS 453
5.58 CBBLOCKPROP 453
5.59 CBBLOCKPROPI 454
5.60 CARRYDNFL 454
5.61 CARRYUPFL 454
5.62 CC3SUPRTDV 455
5.63 CCBFMTAV 456
5.64 CCLCNT 456
5.65 CCFTOL 456
5.66 CCLINFO[0..49] 457
5.67 CCLLOADSTAT 457
5.68 CCLNAME[0..49] 458
5.69 CCLPACKET 458
5.70 CCLSIZE[0..49] 458
5.71 CCRRUNCOUNT 459

- 409 -
Chapter 5 - Cxxxx Parameters

5.72 CDDMTYPINSTCNT 459


5.73 CDDMTYPNAME 460
5.74 CDISPAVGCHPPS 460
5.75 CDISPAVGLPS [1...RDISPCONNMAX] 460
5.76 CDISPAVGLPSCONN [1...RDISPCONNMAX] 461
5.77 CDISPAVGPPS [1...RDISPCONNMAX] 461
5.78 CDISPAVGPPSCONN [1...RDISPCONNMAX] 462
5.79 CDISPAVGSPS [1...RDISPCONNMAX] 462
5.80 CDISPAVGSPSCONN [1...RDISPCONNMAX] 463
5.81 CDISPEXCHAVGPPSCONN 463
5.82 CDISPEXCHAVGSPSCONN 463
5.83 CDISPEXCHMAXPPSCONN 464
5.84 CDISPEXCHMAXSPSCONN 464
5.85 CDISPMAXCHPPS 465

5.86 CDISPMAXLPS [1...RDISPCONNMAX] 465


5.87 CDISPMAXLPSCONN [1...RDISPCONNMAX] 466
5.88 CDISPMAXPPS [1...RDISPCONNMAX] 466
5.89 CDISPMAXPPSCONN [1...RDISPCONNMAX] 467
5.90 CDISPMAXSPS [1...RDISPCONNMAX] 467
5.91 CDISPMAXSPSCONN [1...RDISPCONNMAX] 468
5.92 CEECMDENUMMASK 468
5.93 CEECOLDFL 469
5.94 CEECOMMAND 469
5.95 CEEIOID 470
5.96 CEEIP 470
5.97 CEENUM 470
5.98 CEERESADDR[1..15] 471
5.99 CEERESADDRN[1..15] 471
5.100 CEESTARTOPT 472
5.101 CEESTATE 474
5.102 CEESWITCHFL 475
5.103 CEETAG 475
5.104 CEETOPSTART 476
5.105 CEEWARMFL 477
5.106 CF1 477
5.107 CF2 478
5.108 CFIFORATEA 478
5.109 CFIFORATEM 479
5.110 CHANFBNAME[0..63] 479

- 410 -
Chapter 5 - Cxxxx Parameters

5.111 CHANINUSE[0..31] 479


5.112 CHANLASTMBERR[0..63] 481
5.113 CHANLASTMBERRTIME[0..63] 487
5.114 CHANMBERRCNT[0..63] 487
5.115 CHANMBERRFL[0..63] 488
5.116 CHANNAME 488
5.117 CHANNAME[1..NUMCHAN] 488
5.118 CHANNEL [0..NUMCHANNELS-1] 489
5.119 CHANNUM 489
5.120 CHANREQRSPRCVD[0..63] 490
5.121 CHANREQSENT[0..63] 491
5.122 CHANRSTSTATS 491
5.123 CHANSTS 492
5.124 CHANSTS[0..63] 492

5.125 CHANSTS[0..31] 493


5.126 CHANTEXT 493
5.127 CHANTYPE 494
5.128 CHASSISSIZE 494
5.129 CHGINDEX 495
5.130 CHIGHREADAVGPPS 495
5.131 CHIGHREADMAXPPS 496
5.132 CHGOFSTALM.PR 496
5.133 CHGOFSTALM.SV 497
5.134 CHGOFSTALM.TM 497
5.135 CHILDUCMACQ 497
5.136 CHNFLTSTS[0..numChans-1] 498
5.137 CHNLNAME 498
5.138 CHNLNAME_AI_C 499
5.139 CHNLNAME_AI_S 500
5.140 CHNLNAME_AO_C 501
5.141 CHNLNAME_AO_S 502
5.142 CHNLNAME_DI_C 503
5.143 CHNLNAME_DI_S 504
5.144 CHNLNAME_DO_C 505
5.145 CHNLNAME_DO_S 506
5.146 CHNLNAME[1..NUMCHAN] 507
5.147 CHNLSF1A 507
5.148 CHNLSF2A 508
5.149 CHNLSF1B 508

- 411 -
Chapter 5 - Cxxxx Parameters

5.150 CHNLSF2B 509


5.151 CHNSTS[0..numChans-1] 509
5.152 CIDLOADMORE 510
5.153 CIDLOADSTATUS 510
5.154 CINCONNHNDL[1..10][1..6] 510
5.155 CINCONNNAV[1..10][1..6] 511
5.156 CINCONNPRM[1..10][1..6] 511
5.157 CINCONNSTRVAL[1..10][1..6] 512
5.158 CINCONNVAL[1..10][1..6] 512
5.159 CJDISABLE 512
5.160 CJENABLE [0..NUMCHANNELS-1] 513
5.161 CJMODE 513
5.162 CJNOTCHFLT 514
5.163 CJOFFSET 514

5.164 CJOFFSET[0..numChans-1] 515


5.165 CJOFFSET [0..NUMCHANNELS-1] 515
5.166 CJOVERRANGE 516
5.167 CJSTATUS [0..NUMCHANNELS-1] 516
5.168 CJTACT 517
5.169 CJTEMP 517
5.170 CJ_BOTTOM 518
5.171 CJ_TOP 518
5.172 CJUNDERRANGE 519
5.173 CLEARGAINDELAY 519
5.174 CLIENTCONNSTS[0..4] 519
5.175 CLIENTIP[0..4] 520
5.176 CLIENTNAME 520
5.177 CLKADJUST 521
5.178 CLKTIME 521
5.179 CLKZONE 522
5.180 CLOSEDLOOPRESP 522
5.181 CLOSEFEEDBKTIME 523
5.182 CLOSEIBV 523
5.183 CLOSEMAIN 524
5.184 CLOSEPULSEWIDTH 524
5.185 CLOSESEQ 524
5.186 CLOSESEQALM.FL 525
5.187 CLOSESEQALM.PR 525
5.188 CLOSESEQALM.SV 526

- 412 -
Chapter 5 - Cxxxx Parameters

5.189 CLOWREADAVGPPS 526


5.190 CLOWREADMAXPPS 527
5.191 CLR_GD_C 527
5.192 CLROPREQFL 527
5.193 CLRQUEUEOPT 528
5.194 CLUSTERID 528
5.195 CLXCONNSTS 529
5.196 CLXCONNSTS[0-3] 529
5.197 CLX_GATEWAY 530
5.198 CLX_TAG 531
5.199 CMACTIVEFL 531
5.200 CMAXTEMP 532
5.201 CMDATTR 532
5.202 CMDCLOSE 533

5.203 CMDDISALM.FL 533


5.204 CMDDISALM.PR 533
5.205 CMDDISALM.SV 534
5.206 CMDDISALM.TM[0..2] 534
5.207 CMDEXEC 535
5.208 CMDFALALM.FL 535
5.209 CMDFALALM.PR 536
5.210 CMDFALALM.SV 536
5.211 CMDFALALM.TM[0..2] 537
5.212 CMDFPVALUE 537
5.213 CMDOPEN 538
5.214 CMDREADY 538
5.215 CMDREQIN 538
5.216 CMDRUN 539
5.217 CMDSTOP 539
5.218 CMINTEMP 540
5.219 CMLOADFL 540
5.220 CMODULES 541
5.221 CNETCONNECT 541
5.222 CNTDNFL 542
5.223 CNTEQN 542
5.224 CNTLVLFL 543
5.225 CNTUPFL 543
5.226 CNUMSRCCONN[1..10] 544
5.227 COLLCOUNT 544

- 413 -
Chapter 5 - Cxxxx Parameters

5.228 COMBOPOINT 545


5.229 COMMAND 545
5.230 COMMAND[1..200] 549
5.231 COMMANDACK[1..4] 550
5.232 COMMANDSTATS[1..200] 551
5.233 COMMERROR[1..24] 551
5.234 COMMERROR[1..200] 552
5.235 COMMFAILFL 552
5.236 COMMFAULT 553
5.237 COMMOK 553
5.238 COMMSTATUS 553
5.239 COMMTHRESHOLD 554
5.240 COMPARBITRATIONSTS 554
5.241 COMPHILM 555

5.242 COMPELETED 555


5.243 COMPLOLM 556
5.244 COMPNVSCMD 556
5.245 COMPOSITEKEYSW 557
5.246 COMPOSITEPHASESTS 558
5.247 COMPTERM 559
5.248 COMPUTEARW 559
5.249 CONFIGCODE 560
5.250 CONFIGCODE[1..8] 567
5.251 CONFIGDESC 567
5.252 CONFIGDESC[1..8] 576
5.253 CONFIGPROVERSIGNAL 577
5.254 CONFIGSTS 578
5.255 CONFIGSTS[1..8] 578
5.256 CONFIGURATIONFILE 579
5.257 CONFIGURED 579
5.258 CONFIGVERSION 580
5.259 CONFIRM[0..15] 580
5.260 CONFIRMED[0..15] 580
5.261 CONFLICTFL 581
5.262 CONINUSE 582
5.263 CONINUSEMON 582
5.264 CONNCLOSEFAIL 583
5.265 CONNECTIONERROR 583
5.266 CONNECTIONEVTTIME 584

- 414 -
Chapter 5 - Cxxxx Parameters

5.267 CONNERR 584


5.268 CONFIGINFO 585
5.269 CONFIGVER 586
5.270 CONFREVMISMATCH 586
5.271 CONNLISTSIZE 587
5.272 CONNOPENFAIL 587
5.273 CONNOPENREJECT 588
5.274 CONNSENDERR 588
5.275 CONNSTAT 588
5.276 CONNSTATUS 589
5.277 CONNSTS[0..1] 590
5.278 CONNTMOMULT 590
5.279 CONSOPENRDY 591
5.280 CONSOLIDATECONN 591

5.281 CONSSTARTRDY 592


5.282 CONST[1...8] 592
5.283 CONSTACCLOCK 593
5.284 CONSTENABLE 594
5.285 CONTAINEDIN 595
5.286 CONTAINMEM 595
5.287 CONTCUTOUT 596
5.288 CONTOUSE 596
5.289 CONTROLLOCK 597
5.290 CONTROLPREDICTION 597
5.291 CONTROLPRIORITY 598
5.292 CONTROLREQ 598
5.293 CONVTOASCII 599
5.294 CONVTOLONG 599
5.295 COS 600
5.296 COS[0..NumChans-1] 600
5.297 COUNTERTYPE 600
5.298 CHGOFSTALMENB 601
5.299 CP[1..10] 601
5.300 CPCOMPATIBLE 602
5.301 CPCODESIZE[1..10] 602
5.302 CPEERAVGLPS [1..RPEERCONNMAX] 603
5.303 CPEERAVGLPSCONN [1...RPEERCONNMAX] 603
5.304 CPEERAVGPPS [1...RPEERCONNMAX] 604
5.305 CPEERAVGPPSCONN [1...RPEERCONNMAX] 604

- 415 -
Chapter 5 - Cxxxx Parameters

5.306 CPEERAVGSPS [1...RPEERCONNMAX] 605


5.307 CPEERAVGSPSCONN [1...RPEERCONNMAX] 605
5.308 CPEEREXCHAVGPPSCONN 605
5.309 CPEEREXCHAVGSPSCONN 606
5.310 CPEEREXCHMAXPPSCONN 606
5.311 CPEEREXCHMAXSPSCONN 607
5.312 CPEERMAXLPS [1...RPEERCONNMAX] 607
5.313 CPEERMAXLPSCONN [1...RPEERCONNMAX] 607
5.314 CPEERMAXPPS [1...RPEERCONNMAX] 608
5.315 CPEERMAXPPSCONN [1...RPEERCONNMAX] 608
5.316 CPEERMAXSPS [1...RPEERCONNMAX] 609
5.317 CPEERMAXSPSCONN [1...RPEERCONNMAX] 609
5.318 CPEERWAAVGPPS 610
5.319 CPEERWAAVGPPSCONN 610

5.320 CPEERWAMAXPPS 611


5.321 CPEERWAMAXPPSCONN 611
5.322 CPLASTSAVE 612
5.323 CPMCOMMAND[0..numChans-1] 612
5.324 CPMCOMMAND 613
5.325 CPMSTATE 613
5.326 CPNODESTATEPARM 614
5.327 CPPARPERFRAG 614
5.328 CPRESTORESCOPE 615
5.329 CPSAVCOMPPERC 615
5.330 CPSLEEPTIME 616
5.331 CPSTATUS 616
5.332 CPTIMEOFSAVE 617
5.333 CPUCYCLEAVG[0..39] 617
5.334 CPUCYCLEMAX[0..39] 618
5.335 CPU0FREEAVG 619
5.336 CPU0FREEMIN 619
5.337 CPU1FREEAVG 620
5.338 CPU1FREEMIN 620
5.339 CPUFREEAVG 621
5.340 CPUFREEAVGA 622
5.341 CPUFREEAVGB 622
5.342 CPUFREECRITLM 623
5.343 CPUFREEMIN 623
5.344 CPUFREEMIN1 624

- 416 -
Chapter 5 - Cxxxx Parameters

5.345 CPUFREELOWLM 625


5.346 CPUFREEMINA 625
5.347 CPUFREEMINB 626
5.348 CPUFREERESET 626
5.349 CPULOLM 627
5.350 CPULOLOLM 627
5.351 CPUMAXFLOAT 628
5.352 CPV 628
5.353 CPVALIDSAVESTATES 629
5.354 CPVALIDSAVESTATESSZ 629
5.355 CPVALIDRESTSTATES 630
5.356 CPVALIDRESTSTATESSZ 630
5.357 CRCYCLEOVRN[0..40] 631
5.358 CRCYCLESKIP 631

5.359 CRCYCLESKIP[0..40] 632


5.360 CREATEDBY 632
5.361 CROSSOVERCABLEFAILED 633
5.362 CRSKIPPERIOD 634
5.363 CRSKIPPERIOD[0..40] 634
5.364 CSRC[1..10][1..6] 635
5.365 CSTS[1..8] 635
5.366 CTEMP 636
5.367 CTLACTN 637
5.368 CTLEQN 637
5.369 CTLINIT 637
5.370 CTRLIPADDR 638
5.371 CTLSTATE 638
5.372 CTRLCAPABILITY 639
5.373 CTRLCONFIRM 639
5.374 CTRLDESC 640
5.375 CTRLMODE 640
5.376 CTRLNAME 641
5.377 CTRLRESTART 642
5.378 CTRLSTATE 642
5.379 CTRLSTATUS 642
5.380 CTRLSTEPPEDFLAG 643
5.381 CURDEVICEIDX 643
5.382 CUROBJVALUE 644
5.383 CURHOSTNAME 644

- 417 -
Chapter 5 - Cxxxx Parameters

5.384 CURHRERRFIFOENTRY 644


5.385 CURHRRCVFIFOENTRY 645
5.386 CURHRRPTFIFOENTRY 645
5.387 CURPINPT 646
5.388 CURPROFILEID 646
5.389 CURRDESCREF 647
5.390 CURRELINIDLY 647
5.391 CURRENTBATCHSIZE 648
5.392 CURRENTREL 648
5.393 CURRENTVERSION 649
5.394 CURREUDESCREF 649
5.395 CURRNUMACT 650
5.396 CURRVALREF 650
5.397 CURRVALTREND 651

5.398 CURSEGID 651


5.399 CURSEGTYP 652
5.400 CURTIME 652
5.401 CUSTPCRANGE 654
5.402 CUSTYPHELPTXT 654
5.403 CUTOFF.LM 655
5.404 CV 655
5.405 CV.ABSDEVIATION 656
5.406 CV.ACTIVEHL 656
5.407 CV.ACTIVELL 656
5.408 CV.ACTIVEVAL 657
5.409 CV.BADCOUNT 657
5.410 CV.BadPV 658
5.411 CV.BadPVShedTime 658
5.412 CV.BADPVSHEDTIMEFL 658
5.413 CV.BADREADSALLOWED 659
5.414 CV.BALANCEFACTOR 659
5.415 CV.BALANCETARGET 660
5.416 CV.BIAS 660
5.417 CV.CALCBLKINTERVALS 660
5.418 CV.CLLOOPRESPTIME 661
5.419 CV.CONSTRAINTTYPE 661
5.420 CV.CONTROLPRIORITY 662
5.421 CV.CONTROLTHISCV 662
5.422 CV.CRITICAL 662

- 418 -
Chapter 5 - Cxxxx Parameters

5.423 CV.CVBIAS 663


5.424 CV.CVINDEX 663
5.425 CV.DCSVALUE 664
5.426 CV.DECOUPLERATIO 664
5.427 CV.DELTAACTSOFTHILIM 664
5.428 CV.DELTAACTSOFTLOLIM 665
5.429 CV.DELTASOFTHL 665
5.430 CV.DELTASOFTLL 666
5.431 CV.DESC 666
5.432 CV.DESIREDVALUE 666
5.433 CV.DEVIATION 667
5.434 CV.DISTURBANCE 667
5.435 CV.DISTURBANCEFLAG 668
5.436 CV.DISTURESTTUNING 668

5.437 CV.ENGGHIGHLIMIT 668


5.438 CV.ENGGLOWLIMIT 669
5.439 CV.ENGGUNITS 669
5.440 CV.ER_C 670
5.441 CV.ERRORTOLERANCE 670
5.442 CV.EXECUTIONSTATUS 670
5.443 CV.FF2FBPERFRAT_C 671
5.444 CV.FF2FBPERFRATIO 671
5.445 CV.FILTEREDBIAS 672
5.446 CV.FILTEREDRAMP 672
5.447 CV.FUNNELTYPE 672
5.448 CV.FUTUREVAL 673
5.449 CV.FUTUREVAL_C 673
5.450 CV.HIGHLIMIT 674
5.451 CV.HIGHLIMIT_C 674
5.452 CV.HLERRORWEIGHT 674
5.453 CV.HLRAMP 675
5.454 CV.HLRAMPRATE 675
5.455 CV.HOLDINTEGRATOR 676
5.456 CV.HOLDINTEGRATORENUM 676
5.457 CV.INITMODE 676
5.458 CV.INTEGRATINGCV 677
5.459 CV.LASTBAD 677
5.460 CV.LASTGOOD 678
5.461 CV.LINEARCOEFF 678

- 419 -
Chapter 5 - Cxxxx Parameters

5.462 CV.LINEARCOEFF_C 678


5.463 CV.LLERRORWEIGHT 679
5.464 CV.LLRAMP 679
5.465 CV.LLRAMPRATE 680
5.466 CV.LOWLIMIT 680
5.467 CV.LOWLIMIT_C 680
5.468 CV.MINFUNNEL 681
5.469 CV.MODELINDEX1 681
5.470 CV.MODELINDEX2 682
5.471 CV.MODELTYPE 682
5.472 CV.MOVECAUSE 682
5.473 CV.MOVECAUSEDESC 683
5.474 CV.MOVEINDEPMOVEDESC1 683
5.475 CV.MOVEINDEPMOVEDESC2 684

5.476 CV.NAME 684


5.477 CV.NEWVALUEFLAG 684
5.478 CV.NEWVALUEPINCONN 685
5.479 CV.NOISEVARIANCE 685
5.480 CV.NUMBEROFBLOCKS 686
5.481 CV.PERFRATIO 686
5.482 CV.PERFRATIO_C 686
5.483 CV.PREDSSVALUE 687
5.484 CV.PREDVALUE 687
5.485 CV.PREDVALUE_C 688
5.486 CV.PRIORITY 688
5.487 CV.PROCESSHL 688
5.488 CV.PROCESSHLPINCONN 689
5.489 CV.PROCESSLL 689
5.490 CV.PROCESSLLPINCONN 690
5.491 CV.PVTRACK 690
5.492 CV.PVTRACKENUM 690
5.493 CV.PVVALRESET 691
5.494 CV.PVVALSTATUS 691
5.495 CV.PVVALSTATUS_C 692
5.496 CV.QUADRATICCOEFF 692
5.497 CV.RAMPRATE 692
5.498 CV.RAMPVALUE 693
5.499 CV.RATEBALANCE 693
5.500 CV.READVALUE 694

- 420 -
Chapter 5 - Cxxxx Parameters

5.501 CV.READVALUEPINCONN 694


5.502 CV.SCALINGFACTOR 694
5.503 CV.SE_C 695
5.504 CV.SETPOINT 695
5.505 CV.SETPOINTRAMP 696
5.506 CV.SETPOINTVAL 696
5.507 CV.SHADOWPRICE 696
5.508 CV.SHADOWPRICEDISPLAY 697
5.509 CV.SSFILTEREDRAMP 697
5.510 CV.SSSTATEESTFILTER 698
5.511 CV.SSVALUE 698
5.512 CV.SSVALUE_C 698
5.513 CV.STATEEST 699
5.514 CV.STATEESTDISPLAY 699

5.515 CV.STATUS 700


5.516 CV.STATUSDISP_C 700
5.517 CV.STATUSDISPLAY 701
5.518 CV.TREATASBAD 701
5.519 CV.UNBIASEDMODELVAL 701
5.520 CV.UPDATEFREQUENCY 702
5.521 CV.VALUE 702
5.522 CV.VALUE_C 703
5.523 CV.WINDUPSTATUS 703
5.524 CV[1..8] 703
5.525 CVEUHI 704
5.526 CVEUHI[1..8] 705
5.527 CVEULO 705
5.528 CVEULO[1..8] 706
5.529 CVGAIN 706
5.530 CVINIT 707
5.531 CVINITSRC 707
5.532 CVORFB 708
5.533 CVORFBSRC 708
5.534 CVSRC 708
5.535 CVTYPE 709
5.536 CWRITEAVGPPS 709
5.537 CWRITEMAXPPS 710
5.538 CX[1..10] 710
5.539 CYCLEACTIVE[1..24] 711

- 421 -
Chapter 5 - Cxxxx Parameters

5.540 CYCLEACTIVE[1..200] 711


5.541 CYCLEOPT[1..NUMPROFILES] 712
5.542 CYCLESKIPMAX 713
5.543 CYCLETIME 714
5.544 CYCLETIME[0..63] 714

5.1 C[1..8]

Specific to Block(s) Auxcalc, EnhAuxCalc


Description Results of up to eight calculator expressions.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CSTS[1..8]
Remarks

Specific to Block(s) RegCalc, EnhRegCalc


Description Expression result for each user input expression EXPR[1..8]
Data Type Real
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CSTS[1..8]
Remarks

5.2 C[1..10]

Specific to Block(s) AUXSUMMER


Description Scaling factor for associated block input P[1..10].
Data Type 64-Bit Real Number
Range Any real number, NaN is not allowed
Default 1.0

- 422 -
Chapter 5 - Cxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters P[1..10]
Remarks

5.3 C[1..10].BYPPERM

Specific to Block(s) Transition


Description Conditional Force Permit
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters C[1..10].BYPREQ, C[1..10].FL.
Remarks If C[i].BYPPERM is On, C[i].FL will be set according to C[i].BYPREQ.

5.4 C[1..10].BYPREQ

Specific to Block(s) Transition


Description Conditional Force Request
Data Type Enumeration CSCOBYPREQ
Range ToOff (0) ToOn (1) None (2)
Default None (2)
Config Load No
Active Loadable No
Access Lock Controlled by CONTROLLOCK
Residence CEE
Related Parameters C[1..10].BYPPERM, C[1..10].FL.
Remarks

- 423 -
Chapter 5 - Cxxxx Parameters

5.5 C[1..10].CONFIGCODE

Specific to Transition
Block(s)
Description Condition Configuration Code
Data Type Enumeration CSCOCONFIGCODECOND
Range None (0) Ok (1) UnknownError (2) ImplictConv (3) LossOfPrecsn (4) UnexpctEnd (5)
UnexpctComma (6) ColonWoQMark (7) FctNotMltArg (8) ClosParenExp (9)
OperandExp (10) MissingArg (11) OperatorExp (12) ColonExp (13) TypeMismatch
(14) TypeNotSupp (15) SyntaxError (16) ExprTooCmplx (17) NotEPcodeMe (18)
NotEDataStak (19) UnsuppFeatur (20) ExprTooLong (21) DivideByZero (22)
UnknownToken (23) UnexpTokenOS (24) UnknownFunc (25) UnexpOCExpr2 (26)
UnexpOCExpr3 (27) ZeroArgument (28) UnexpToken (29) InvalResult (30)
InvalTokenTb (31) IntegerExp (32) DoubleExp (33) MissedImpl (34) UnicodeConv
(35) ConstExprRem (36) DuplExprRem (37) ExtUse38 (38) ExtUse39 (39) ExtUse40
(40) ExtUse41 (41) ExtUse42 (42) ExtUse43 (43) ExtUse44 (44) ExtUse45 (45)
ExtUse46 (46) ExtUse47 (47) ExtUse48 (48) ExtUse49 (49) ExtUse50 (50)
UnSupConType (51) UnExpClsParn (52) CantAssRVal (53) UnExpArrOpen (54)
ArrClsExpect (55) ArrOpnExpect (56) ArrIndxError (57) StringExpect (58)
InvalidRefer (59) TooManyConns (60) CantConvInpt (61)
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related
Parameters
Remarks See for additional information.

5.6 C[1..10].CONFIGDESC

Specific to Block(s) Transition


Description Conditional Configuration Descriptor
Data Type String
Range N/A
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See C[1..10].CONFIGSTSfor additional information.

- 424 -
Chapter 5 - Cxxxx Parameters

5.7 C[1..10].CONFIGSTS

Specific to Transition
Block(s)
Description Condition Configuration Status
Data Type Enumeration CSCOCONFIG
Range Ok (0) Information (1) Warning (2) SevereWarn (3) Fail (4) Error (5) SevereError (6)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related C[1..10].CONFIGCODEC[1..10].CONFIGDESC
Parameters
Remarks Transition input condition configuration status parameters C[1..10].CONFIGSTS, C
[1..10].CONFIGCODE, and C[1..10].CONFIGDESC are set on SCMSTATE transition
from Inactive to Validated.

5.8 C[1..10].DESC

Specific to Block(s) Transition


Description Condition Description
Data Type String
Range Maximum string length is 23 characters.
Default Null String
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

5.9 C[1..10].EXECCODE

Specific to Transition
Block(s)
Description Condition Execution Code
Data Type Enumeration CSCOEXECCODE
Range None (0) ConfigError (1) ExprEvalFail (2) StoreFailed (3) CommError (4)
StoreWarning (5) InternalErr (6) CtrlReqErr (7) DataTypeErr (8) StorePending (9)

- 425 -
Chapter 5 - Cxxxx Parameters

Default None (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks See C[1..10].EXECSTSfor additional information.

5.10 C[1..10].EXECDESC

Specific to Block(s) Transition


Description Condition Execution Code Descriptor
Data Type String
Range N/A
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See C[1..10].EXECSTSC[1..10].EXECSTS for additional information.

5.11 C[1..10].EXECSTS

Specific to Transition
Block(s)
Description Condition Execution Status
Data Type Enumeration SCSCOEXECSTS
Range Ok (0) Bypass (1) Info (2) Warning (3) Fail (4) Error (5) OkPaused (6) BypassPaused
(7) InfoPaused (8) WarnPaused (9) FailPaused (10) ErrorPaused (11)
Default Ok (0)
Config Load No
Active No
Loadable

- 426 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related C[1..10].EXECCODEC[1..10].EXECDESC
Parameters
Remarks Transition input condition execution status parameters C[1..10].EXECSTS, C
[1..10].EXECCODE, and C[1..10].EXECDESC are update when the transition is in the
Sequential Control Module's (SCM) current scope of execution.

5.12 C[1..10].EXPR

Specific to Block(s) Transition


Description Condition Expression
Data Type String
Range Length: 255 characters.
Default Null String
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

5.13 C[1..10].EXPRPCODE

Specific to Block(s) Transition


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

- 427 -
Chapter 5 - Cxxxx Parameters

5.14 C[1..10].FL

Specific to Block(s) Transition


Description Condition Status Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.15 C[1..10].GATEASGN

Specific to Block(s) Transition


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

5.16 C[1..10].INVOKFL

Specific to Block Transition


(s)
Description Invoke Transition Condition Invoke Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No

- 428 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related C[1..10].FL
Parameters
Remarks C[i].INVOKFL on invoke transition is updated from C[i].FL at the time of
handler invocation.

5.17 C1

Specific to Block Totalizer, Pulse Input Totalizer, Deadtime


(s)
Description Engineering Units scaling factor for the calculation of DELAYTIME or Totalizer
Process Variable.(PV)
Data Type 64-Bit Real Number
Range Any Real Number, NaN or Zero is not allowed.
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Deadtime: Engineer Totalizer, Pulse Input Totalizer: Operator
Residence CEE
Related D1, DELAYTIME
Parameters
Remarks

Specific to Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Engineering Units scale factor (dimensionless) - For example, a factor to convert
gallons to barrels.
Data Type 64-Bit Real Number
Range Any Real Number, NaN is not allowed.
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related AVC2PV
Parameters
Remarks For Pulse Input, C1 is used to calculate AV and PL in EU as follows: AV in EU =
(C1/C2)*Counter Value Frequency value in EU - (C1/C2)* TIMEBASE * Counter
Value.

- 429 -
Chapter 5 - Cxxxx Parameters

Specific to Series C PICHANNEL


Block(s)
Description C1 Scale Factor
Data Type FLOAT64
Range OUTPUT
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence IOM
Related AVAVRAWBADAVRAWBADPVC2PVPVRAW
Parameters
Remarks C1 represents the dimensionless engineering units scale factor used to scale the
RAW counts and pulse frequencies to engineering units based on the equations for
Process Value (PV) and Accumulated Value (AV).

Specific to UIO - Series C DICHANNEL


Block(s)
Description C1 Scale Factor
Data Type FLOAT64
Range OUTPUT
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence IOM
Related AVAVRAWC2
Parameters
Remarks C1 represents the dimensionless engineering units scale factor used to scale the
RAW counts to engineering units based on the equations for Accumulated Value
(AV).

5.18 C1[0..7]

Specific to Pulse Input IOM


Block(s)
Description Engineering Units scale factor (dimensionless) - for example, a factor to convert
gallons to barrels.
Data Type 64-Bit Real Number
Range 3.4 e -38 to 3.4 e 38
Default 1.0
Config Load Yes

- 430 -
Chapter 5 - Cxxxx Parameters

Active No
Loadable
Access Lock Application Developer
Residence CEE
Related AVC2PLTV
Parameters
Remarks For Pulse Input IOM, C1 is used to calculate AV and PL in EU as follows: AV in EU =
(C1/C2)* AVRAW PV in EU = (C1/C2) * TIMEBASE * pulses/(Frequency Integration
Period) TV in EU = (C1/C2) * TVRAW

5.19 C2

Specific to Block(s) Pulse Input Totalizer


Description Scaling factor for consistency with Pulse Input channels
Data Type 64-Bit Real Number (Not NaN)
Range Any Real number, NaN or Zero not allowed.
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks

Specific to Series C PICHANNEL


Block(s)
Description C2 Scale Factor
Data Type FLOAT64
Range OUTPUT
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence IOM
Related AVAVRAWBADAVRAWBADPVC1PVPVRAW
Parameters
Remarks C2 represents the meter factor in pulses per engineering units used to scale the
RAW counts and pulse frequencies to engineering units based on the equations for
Process Value (PV) and Accumulated Value (AV).

- 431 -
Chapter 5 - Cxxxx Parameters

Specific to UIO - Series C DICHANNEL


Block(s)
Description C2 Scale Factor
Data Type FLOAT64
Range OUTPUT
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence IOM
Related AVAVRAWC1
Parameters
Remarks C2 represents the meter factor in pulses per engineering units used to scale the
RAW counts to engineering units based on the equations for Accumulated Value
(AV).

Specific to Block(s) Deadtime


Description Scaling factor for the P2 input.
Data Type Real Number
Range Any Real Number, NaN not allowed.
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

Specific to Pulse Input IOC, Pulse Input w/Fast Cutoff IOC


Block(s)
Description Meter factor in pulses per Engineering Units. For example, the number of pulses
per gallon.
Data Type 64-Bit Real Number
Range
Default 1.0
Config Load Yes
Active No
Loadable

- 432 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related AVPV
Parameters
Remarks For Pulse Input IOM, this is used to calculate AV and PV in EU as follows: AV in EU =
(C1/C2) * Counter Value Frequency value in EU = (C1/C2) * TIMEBASE * Counter
Value

5.20 C2[0..7]

Specific to Pulse Input IOM


Block(s)
Description Meter factor in pulses per Engineering Unitls - for example, number of pulses per
gallon.
Data Type 64-Bit Real Number
Range 3.4 e -38 to 3.4 e 38
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related AVC2PLTV
Parameters
Remarks For Pulse Input IOM, C2 is used to calculate AV, PV, and TV in EU as follows: AV in
EU = (C1/C2) * AVRAW PV in EU = (C1/C2) * Integration Period) TV in EU = (C1/C2) *
TVRAW

5.21 C3

Specific to Pulse Input IOC


Block(s)
Description Pulse Length scale factor used to scale the Pulse Period, Pulse High and Pulse
Low values to Engineering Units.
Data Type 64-Bit Real Number
Range N/A
Default 1.0
Config Load Yes
Active No
Loadable

- 433 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks

Specific to Series C PICHANNEL


Block(s)
Description Pulse Length Scale Factor
Data Type FLOAT64
Range OUTPUT
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence IOM
Related FREQPERIODPL
Parameters
Remarks C3 represents the pulse length measurement engineering unit's conversion factor
used to scale the pulse period, pulse high values, and pulse low values to
engineering units.

5.22 C3[0..5]

Specific to Pulse Input IOM


Block(s)
Description Pulse Length measurement Engineering Units conversion factor (in Engineering
Units per unit of time).
Data Type 64-Bit Real Number
Range 3.4 e -38 to 3.4 e 38
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks For Pulse Input IOM (Channels 0-5 only), this is used to calculate Pulse Length in
Engineering Units: PL in EU = (C3)*Timer Latch Value in microseconds.

- 434 -
Chapter 5 - Cxxxx Parameters

5.23 C300COMMAND

Specific to C300 FBs


Block(s)
Description Controller command
Data Type Enumeration
Range None (0) - No command Shutdown (1) - Controller will be shutdown
Default None (0)
Config Load No
Active No
Loadable
Access Lock Engineer
Residence C300
Related N/A
Parameters
Remarks Shutdown command can be issued when the C300STATE is IDLE, which
transitions the controller to the RDY state. No other value of C300STATE can be
commanded.

5.24 C300IP

Specific to Block(s) EIM EIP Protocol Block


Description C300 IP Address
Data Type String
Range -
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks IP Address of the C300 in which this IO is configured.

5.25 C300MAXTEMP [1...3]

Specific to Block(s) C300 FBs, Series C FIM


Description Maximum Controller Temperature °C indicated by three different
thermometers.
Data Type Float64
Range -55.00 °C to +120.00 °C

- 435 -
Chapter 5 - Cxxxx Parameters

Default 0.00 °C
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, Series C FIM
Related C300MINTEMP [1...3]C300TEMP [1...3]
Parameters
Remarks Displays maximum temperature the module has reached till now.

5.26 C300MINTEMP [1...3]

Specific to Block(s) C300 FBs, Series C FIM4


Description Minimum Controller Temperature °C indicated by three different
thermometers.
Data Type Float64
Range -55.00 °C to +120.00 °C
Default 0.00 °C
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, Series C FIM4
Related C300MAXTEMP [1...3]C300TEMP [1...3]
Parameters
Remarks Displays minimum temperature the module has reached till present time.

5.27 C300STATE

Specific to C300 FBs


Block(s)
Description C300 Controller state
Data Type Enumeration
Range OFFNET (0) TESTING (1) BOOTING (2) ALIVE (3) LOADING (4) OK (5) FAILED (6)
PIREADY (7) BACKUP (8) NOTLOADED (9) NOCEE (10) CEEIDLE (11) CEERUN (12)
CEEMIX (13) TIMESOURCE (14)
Default NOTLOADED (9)
Config No
Load
Active No
Loadable

- 436 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence C300
Related C300COMMAND
Parameters
Remarks C300STATE is derived from CEESTATE and the platform state. Note: SOFTFAIL,
C300STATE and CEESTATE are independent of one another. A change in the state
of SOFTFAIL does not cause a change in either C300STATE or CEESTATE.

5.28 C300MODTYPE

Specific to Block(s) C300 FBs


Description C300 Module type.
Data Type Enumeration
Range UNKNOWN (0) - Unknown CEEWITH2IOLS (3) - CEE with two IOLs
Default UNKNOWN (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300
Related Parameters N/A
Remarks

5.29 C300TEMP [1...3]

Specific to Block(s) C300 FBs, Series C FIM


Description Controller Temperature °C indicated by three different thermometers.
Data Type Float64
Range -55.00 °C to +120.00 °C
Default 0.00 °C
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, Series C FIM
Related C300COMMANDC300MAXTEMP [1...3]C300MINTEMP [1...3]
Parameters
Remarks Displays temperature measured by three different thermometers on the
board.

- 437 -
Chapter 5 - Cxxxx Parameters

5.30 CABCOMMAND

Specific to CAB types


Block(s)
Description CAB Command. Operator writes to CABCOMMAND to affect certain transitions in
the value of CABSTATE. Storing “Quit” can trigger transition from Terminated to
Dormant. Storing “Run” can trigger transition from Terminated to Normal or from
Dormant to Normal. CABCOMMAND always returns the value “None” when read.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Enumeration CABCOMMAND
Range None = 0, Quit = 1, Run = 2
Default None
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related CABSTATE
Parameters
Remarks

5.31 CABEXECTIMER

Specific to CAB types


Block(s)
Description CAB Execution Timer - The value that is displayed depends on whether the CAB
type is “Atomic” or “Distributed”. For more information, refer to the Remarks
section.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Float64
Range For Atomic CABs the Range is 0.0 - ~250,000.0 (limited by watchdog) For Distributed
CABs the Range is 0.0 - Max Float64 value after done running (-0.1 through
Negative Max Float64 while Distributed CAB is running)
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly

- 438 -
Chapter 5 - Cxxxx Parameters

Residence CEE

Related CABPREFRDTIMCABPREFWRTIM
Parameters
Remarks l For Atomic CAB type: This parameter contains the time in microseconds
required during the last execution cycle to run the user's CAB code. This timer
starts when the user's code is invoked and ends after the user's code is
finished and all associated CAB error handlers and watchdog code is
complete.
l For Distributed CAB type: This parameter value has a dual purpose.
l To determine how long a distributed program has been running -
There will be a negative number in SECONDS showing how long
the distributed CAB had been in the Execute() subroutine. Once the
Execute() subroutine has exited, the CABEXECTIMER will be
updated to a positive number. This number reflects the amount of
time in microseconds that the Execute() subroutine actually ran (as
it does in an atomic block).
To determine if a distributed CAB is “runaway” The engineer or
l

operator can give the “QUIT” command on a runaway distributed


CAB and it will terminate.
CAB/C300 does not support the parameter CABEXECTIMER. Attempts to read it
from a loaded CAB/C300 instance always return NaN. To measure execution timing
for CAB/C300 instances, use the utility block, EXECTIMER.

5.32 CABINETNAME

Specific to Block Series C I/O channel blocks


(s)
Description This parameter displays the cabinet name in the Main tab of the Series C I/O
channel blocks.
Data Type BLOCKID
Range 64
Default —
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SRAL
Related
Parameters
Remarks

- 439 -
Chapter 5 - Cxxxx Parameters

5.33 CABINETPOSITION

Specific to Block Series C I/O channel blocks


(s)
Description This parameter displays the cabinet position in the Main tab of the Series C I/O
channel blocks.
Data Type STRING
Range 64
Default —
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SRAL
Related
Parameters
Remarks

5.34 CABINSTCOUNT

Specific to CEE-ACE block, CEE-C300 block


Block(s)
Description CAB Instance Count - Array parameter which indicates the number of instances in
the CEE for each CAB type.
Data Type Integer
Range Varies with platform. For more information, refer to the remarks.
Index Index range is platform specific. For more information, refer to the remarks.
Range
Default 0
Config No
Load
Active No
Loadable

- 440 -
Chapter 5 - Cxxxx Parameters

Access View Only


Lock
Residence CEE
Related CABTYPNAME
Parameters
Remarks CABINSTCOUNT is an array parameter whose indices have a one-to-one
correspondence to the indices of parameter CABTYPNAME. CABTYPNAME[I]
displays the name of a CAB type in the CEE while CABINSTCOUNT[I] displays how
many instances of that type exist within the CEE. There is no enforced upper limit
on how many instances a CAB type can have. The limit comes only from CEE
memory. For CEE-ACE, CABINSTCOUNT never displays a value less than 1. For CEE-
C300, CABINSTCOUNT can display the value 0. This indicates that the last instance
of the type has been deleted but the type itself is being held within CEE-C300 for up
to 1 minute in case a new instance is created. For CAB/C300, the index range is 1
to100. For CAB/ACE, the index range is 1 to 400. CABINSTCOUNT is displayed on the
CAB Types Info form of the CEE block form.

5.35 CABPREFRDTIM

Specific to CAB types


Block(s)
Description CAB PRef Read Timer. Contains the total time in microseconds spent outside of
CAB user code processing parameter reference read requests during the current
execute cycle.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Float64
Range 0.0 - ~250,000.0 (limited by watchdog)
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CABEXECTIMER, CABPREFWRTIM
Parameters
Remarks CAB/C300 does not the support parameter CABPREFRDTIM. Attempts to read it
from a loaded CAB/C300 instance always return NaN.

- 441 -
Chapter 5 - Cxxxx Parameters

5.36 CABPREFWRTIM

Specific to CAB types


Block(s)
Description CAB PRef Write Timer. Contains the total time in microseconds spent outside of
CAB user code processing parameter reference write requests during the current
execute cycle.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Float64
Range 0.0 - ~250,000.0 (limited by watchdog)
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CABEXECTIMERCABPREFRDTIM
Parameters
Remarks CAB/C300 does not support the parameter CABPREFWRTIM. Attempts to read it
from a loaded CAB/C300 instance always return NaN.

5.37 CABSOFTVER

Specific to CAB types


Block(s)
Description CAB Software Version. Contains the version of CAB software that was used to build
the user's CAB program. It is set by the CAB Build environment when a CAB type is
created or edited.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type String
Range 32 characters
Default The default value is set by the CAB build-time on save.
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence System Repository
Related DOTNETVER[0..1]OSVER
Parameters
Remarks CAB/C300 does not support the parameter CABSOFTVER. Attempts to read it from
a loaded CAB/C300 instance always return blank.

- 442 -
Chapter 5 - Cxxxx Parameters

5.38 CABSTATE

Specific to CAB types


Block(s)
Description CAB State. CABTSTATE summarizes the operating condition of the CAB instance.
Meaning of the possible values is given below.
l Unloaded-Abnormal transient condition. Shows only if there has been a
communication error during program load.
l Normal-Normal condition. Access to FDPs and CDPs is supported. Block
Execute() subroutine is processing.
l Exception-Abnormal condition with an associated event report. Access to
FDPs and CDPs is supported. Block Execute() subroutine is processing but is
throwing an exception every cycle.
l Terminated-Abnormal condition with alarm. Access to FDPs and CDPs is
supported. Block Execute() subroutine is not processing.
Dormant-Abnormal condition with no alarm. Access to FDPs and CDPs is
l

supported. Block Execute() subroutine is not processing.


Stores to parameter CABCOMMAND can trigger a limited number of transitions in
CABSTATE.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Enumeration CABSTATE
Range Unloaded = 0, Normal = 1, Exception = 2, Terminated = 3, Dormant = 4
Default Unloaded
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CABCOMMAND, PROGSTSDESC, EXCPTNTYPE
Parameters
Remarks

5.39 CABTYPNAME

Specific to CEE-ACE block, CEE-C300 block


Block(s)
Description CAB Type Name - Array parameter listing names of CAB types in the CEE.
Data Type String
Range Not Applicable
Index Index range is platform-specific. For more information, refer to the remarks.
Range
Default Not applicable.
Config No
Load

- 443 -
Chapter 5 - Cxxxx Parameters

Active No
Loadable
Access View Only
Lock
Residence CEE
Related BLOCKTYPNAME
Parameters
Remarks This parameter displays the names of all CAB types currently loaded and in use
within the CEE. Format of name displayed is identical to the format for parameter
BLOCKTYPNAME of CAB blocks: “<block library name>.<block type name>”. All
elements of CABTYPNAME are displayed on the CAB Types Info tab of the CEE block
form. For CAB/C300, CABTYPNAME displays the names of all CAB types which are
currently loaded. The index range is 1 to 100. For CAB/ACE, CABTYPNAME displays
the names of all CAB types which are currently loaded and in use. The index range
is 1 to 400.

5.40 CALBIAS

Specific to Block AIC, AOC


(s)
Description Calibration Bias - Specifies a bias value which is applied to the raw analog
data.
Data Type 64-Bit Real Number
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related BADCAL
Parameters
Remarks CALBIAS[0..5] is accessible by the Application Developer on the Configuration
Form only.

5.41 CALBIAS[0..numChans-1]

Specific to Block(s) AIM, AOM


Description Calibration Bias - Specifies a bias value which is applied to the raw analog
data.
Data Type 64-Bit Real Number
Range
Default 0
Config Load Yes

- 444 -
Chapter 5 - Cxxxx Parameters

Active Loadable No
Access Lock Application Developer
Residence CEE
Related BADCAL
Parameters
Remarks CALBIAS is accessible by the Application Developer on the Configuration
Form only.

5.42 CALBIAS[0..7]

Specific to Block(s) Chassis HART AI IOM, HART AO IOM


Description Calibration Bias - Specifies a bias value that is applied to the raw analog
data.
Data Type Float64
Range
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters BADCAL
Remarks

5.43 CALIBALLA

Specific to Block(s) AI-HART, AI-LLMUX, AO-HART


Description Calibration Status
Data Type Boolean
Range 0 OFF
1 ON
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks

- 445 -
Chapter 5 - Cxxxx Parameters

5.44 CALIBALLB

Specific to Block(s) AI-HART, AI-LLMUX, AO-HART


Description Calibration Status
Data Type Boolean
Range 0 OFF
1 ON
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks

5.45 CALIBFTA1STS

Specific to LLMUX, RHMUX


Block(s)
Description Field Termination Assembly (FTA) 1 Calibration Status. Defines the current
calibration status of the FTA1 connected to the associated I/O Processor (IOP) type
LLMUX or RHMUX.
Data Type Enumeration
Range Disabled (0): FTA1 Calibration is disabled.
Enabled (1): FTA1 Calibration is enabled.
Not_Permitted (2): Calibration is not permitted because IOP
is in RUN.
Default Not_Permitted (2)
Config Load No
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOM
Related
Parameters
Remarks The IOP must be in its IDLE state before calibration can be enabled.

- 446 -
Chapter 5 - Cxxxx Parameters

5.46 CALIBFTA2STS

Specific to LLMUX, RHMUX


Block(s)
Description Field Termination Assembly (FTA) 2 Calibration Status. Defines the current
calibration status of the FTA2 connected to the associated module type LLMUX or
RHMUX.
Data Type Enumeration
Range Disabled (0): FTA1 Calibration is disabled.
Enabled (1): FTA1 Calibration is enabled.

Not_Permitted (2): Calibration is not permitted because IOM


is in RUN.
Default Not_Permitted (2)
Config Load No
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOM
Related
Parameters
Remarks The IOP must be in its IDLE state before
calibration can be enabled.

5.47 CALIBRATION

Specific to PID-PL
Block(s)
Description Calibration - When on, indicates that the PV is invalid because the analyzer
generating it is being calibrated or is out of commission.
Data Type Boolean
Range Off (0): Analyzer is not in calibration.
On (1): Analyzer is in calibration.
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related CTLEQN
Parameters
Remarks When this parameter is set on, Profit Loop PKS control algorithm ignores the PV
and freezes the current model bias. This parameter is applicable only when
CTLEQN is set to Profit Loop PKS, and is ignored in PID control equations.

- 447 -
Chapter 5 - Cxxxx Parameters

5.48 CALIBRJSTS

Specific to LLAI
Block(s)
Description Reference Junction Calibration Status. Enables the calibration of the channel 1
Reference Junction (RJ) input for the associated I/O Processor (IOP) type LLAI.
Data Type Enumeration
Range Disabled (0): Reference Junction calibration is
disabled.
Enabled (1): Reference Junction calibration is
enabled.
Not_Permitted (2): Calibration is not permitted because IOP
is in RUN.
Default Not_Permitted (2)
Config No
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOLIM
Related
Parameters
Remarks The IOP must be in its IDLE state before calibration can be enabled. The proper
calibration sequence is to set the slot 1 calibration_slot Boolean and provide the
correct slot configuration word for RJ calibration. Reset when the calibration of RJ is
completed or aborted.

5.49 CALIBSTS

Specific to Block Analog Module Blocks (PM I/O)


(s)
Description Calibration Status. Defines the calibration status for the associated analog I/O
Processor (IOP).
Data Type Enumeration
Range Disabled (0): Calibration is disabled.
Enabled (1): Calibration is enabled.
Not_Permitted (2): Calibration is not permitted because IOP
is in RUN.
Default Not_Permitted (2)
Config Load No
Active Loadable No

- 448 -
Chapter 5 - Cxxxx Parameters

Access Lock Engineer/Application Developer


Residence IOLIM
Related
Parameters
Remarks The IOP must be in its IDLE state before calibration can be enabled.

Specific to Analog Module Blocks (Series C I/O)


Block(s)
Description FTA Calibration Status
Data Type Enumeration
Range Disabled (0): Calibration is disabled.
Enabled (1): Calibration is enabled.
Not_Permitted (2): Calibration is not permitted because IOM
is in RUN.
Default Not_Permitted (2)
Config No
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOLINK
Related
Parameters
Remarks The IOM must be in the IDLE state prior to enabling calibration. For the AI-LLMUX,
CALIBSTS is an arrayed parameter that has four elements. Each array element
controls and reads the calibration status for one attached FTA. Note:Series C AO-
HART (CC-PAOH51) module does not support calibration. If CALIBSTS is enabled
and AO-HART module is loaded to CC-PAOH51 module, the configuration mismatch
error appears.

5.50 CAPABILITY

Specific to C300
Block(s)
Description Feature Configuration
Data Type Bit string
Range 0 – Enable Extended Feature Configuration
Default Enable Extended Feature Configuration. Default value for “Enable Extended
Feature Configuration” is OFF
Config ERDBONLY
Load
Active Yes
Loadable

- 449 -
Chapter 5 - Cxxxx Parameters

Access Lock AppDevOnly


Residence ERDB
Related CTRLCAPABILITY
Parameters
Remarks Setting this parameter value to Enable Extended Feature Configuration indicates
that the downloaded controller image supports extended features, such as
Experion PKS Profit Control and Ethernet Interface Module. If the user has PCNT
02 version hardware and is using it or planning on using it with the extended
features, then they should set this value. This parameter controls the assignment
to the controller of blocks requiring the extended feature capability.

5.51 CAPVALOPT

Specific to Block(s) GRPCAPRBK


Description Capability FailSafe Option
Data Type Enumeration
Range SAFEVAL, LASTVAL
Default SAFEVAL
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters CAPSAFEVAL
Remarks User sets the safe value option using this param.

5.52 CAPSAFEVAL

Specific to Block GRPCAPBRK


(s)
Description Capability Safe Value
Data Type IEEEFloat64
Range
Default NaN
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related CAPVALOPT
Parameters
Remarks Can be configured only when the CAPVALOPT=SAFEVAL and it stores Safe
Value of OUTCAP.

- 450 -
Chapter 5 - Cxxxx Parameters

5.53 CARDTYPE

Specific to HRBBOX_CB block, HRBBOX_EC block, HRBBOX_HLPIU, and HRBBOX_LxPIU block


Blocks
Description Card type
Data Type Enumeration
Range CB/EC : REGCTL PIU : None
Default For EC/CB : REGCTL For PIU : NONE
Config. Yes
Load
Active No
Loadable
Access Lock ViewOnly for HLPIU and LXPIU
Residence CEE
Related
Parameters
Remarks This parameter displays the card type of the HRBBOX_CB block and HRBBOX_EC
block. This parameter is can only be viewed for CB/EC box as the box contains only
one type of card (that is, Regulatory type).

5.54 CASREQFL

Specific to PID, PIDER, PIDFF, PosProp RemCas, RatioBias, RegSummer


Block(s)
Description Cascade Request Flag - If set, means the function block was in cascade, then shed
mode due to input timeout, and will return to cascade as soon as it fetches a good
input.
Data Type Boolean
Range Off (0) On (1): Mode was shed due to timeout; waiting to return to cascade mode.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

- 451 -
Chapter 5 - Cxxxx Parameters

5.55 CASSTS

Specific to HIWAYOUT, UCNOUT


Block(s)
Description Cascade Status - Indicates the remote cascade match between the ACE controller
and UCN or HIWAY requlatory control point.
Data Type Enumeration
Range 0 SECDATANOTREAD Secondary data is not
being read
1 CASMISMATCH There is a cascade
mismatch
2 CASOK Cascade is okay
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

5.56 CATNUMBER

Specific to Block(s) All IOM Function Blocks


Description Catalog Number
Data Type 32-Bit Integer
Range
Default TC-IAH061(1756-IF6I): 1 TC- MUX021: 0
TC-IAH161(1756-IF16): 6 TC-OAH061(1756-OF6CI): 4
TC-IDA161(1756-IA16): 5 TC-OAV061(1756-OF6VI): 3
TC-IDD321(1756-IB32/B): 12 TC-OAV081(1756-OF8): 9
TC-IDJ161(1756-IB16I): 6 TC-ODA161(1756-OB16I): 7
TC-IDK161(1756-IA16I): 5 TC-ODD321(1756-OB32): 17
TC-IDW161(1756-IM16I): 6 TC-ODJ161(1756-OB16I): 7
TC-IDX081(1756-IA8D): 1 TC-ODK161(1756-OA16I): 7
TC-IDX161(1756-IB16D): 2 TC-ODX081(1756-OA8D): 4
TC-IXL061(1756-IT6I): 2 TC-ODX161(1756-OB16D): 4
TC-IXR061(1756-IR6I): 5 TC-MDP081 (Pulse Input IOM): 8
Config Load Yes
Active Loadable No

- 452 -
Chapter 5 - Cxxxx Parameters

Access Lock Application Developer


Residence CEE
Related Parameters
Remarks Although loaded, this parameter is not exposed on any configuration form.

5.57 CBADREADS

Specific to QIPACTERM
Block(s)
Description Consecutive Bad Reads.
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Provides the number of consecutive bad data blocks received from the QiMPact
device, as determined by checksum validation of this block.

5.58 CBBLOCKPROP

Specific to Block All blocks


(s)
Description This parameter defines the property of the block.
Data Type Integer 32
Range - (2,147,483,647 -1 ) to 2,147,483,647
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related
Parameters
Remarks This parameter increments the counter value only when the CBBLOCKPROP
is set to TRUE.

- 453 -
Chapter 5 - Cxxxx Parameters

5.59 CBBLOCKPROPI

Specific to Block(s) All blocks


Description This parameter defines the property of the indexed block.
Data Type Integer 32
Range - (2,147,483,647 -1 ) to 2,147,483,647
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence No Load
Related Parameters
Remarks

5.60 CARRYDNFL

Specific to Up / Down Counter Block


Block(s)
Description Down Carry Flag
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related QDFL, QUFL
Parameters
Remarks This parameter is set to “TRUE” when a block execution occurs followed by a
counter underflow. . This parameter provides a pulse indication to allow counter
chaining.

5.61 CARRYUPFL

Specific to Up / Down Counter Block


Block(s)
Description Up Carry Flag
Data Type Boolean
Range FALSE,TRUE

- 454 -
Chapter 5 - Cxxxx Parameters

Default FALSE
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related QDFL, QUFL
Parameters
Remarks This parameter is set to “TRUE” when a block execution occurs followed by a
counter overflow. This parameter provides a pulse indication to allow counter
chaining.

5.62 CC3SUPRTDV

Specific to CEE-C300 block.


Block(s)
Description CAB/C300 Supported Version - Maximum version of CAB type features which can
run within this C300.
Data Type Integer
Range >= 1
Default Based on version of CAB/C300 run-time in the platform.
Config No
Load
Active No
Loadable
Access Lock View Only
Residence CEE
Related X_CC3MINREQV of CAB types
Parameters
Remarks Whenever a CAB type is loaded to a C300, its X_CC3MINREQV is compared to the
CC3SUPRTDV of the CEE block. Load will be successful if X_CC3MINREQV >=
CC3SUPRTDV. CC3SUPRTDV is visible on the CAB Types Info tab of the CEE block
form.

- 455 -
Chapter 5 - Cxxxx Parameters

5.63 CCBFMTAV

Specific to Block(s) TCMI

Description CCB Format Error Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

5.64 CCLCNT

Specific to Block CPM, CEEC300


(s)
Description Number of Loaded Control Component Libraries (CCLs) in the Control
Processor Module (CPM).
Data Type 16-Bit Integer
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200(CPM), C300(CEEC300)
Related CCLINFO, CCLNAME.
Parameters
Remarks Gives a count of the number of CCLs loaded to the CPM at any given time.

5.65 CCFTOL

Specific to Block(s) ProfitCtl


Description CCF tolerance
Data Type FLOAT64
Range NA
Default 0
Config Load Yes

- 456 -
Chapter 5 - Cxxxx Parameters

Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

5.66 CCLINFO[0..49]

Specific to CPM, CEEC300


Block(s)
Description Control Component Library (CCL) Management Information - Contains Internal
CCL Management information.
Data Type String (One Dimensional Array)
Range 0 to 49
Default Null String
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200(CPM), C300(CEEC300)
Related CCLCNT, CCLNAME
Parameters
Remarks

5.67 CCLLOADSTAT

Specific to Block CPM, CEEC300


(s)
Description Control Component Library (CCL) Load Status - Shows load status of CCL last
loaded to the CPM.
Data Type 16-Bit Integer
Range None
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200(CPM), C300(CEEC300)
Related
Parameters
Remarks

- 457 -
Chapter 5 - Cxxxx Parameters

5.68 CCLNAME[0..49]

Specific to Block CPM, CEEC300


(s)
Description Control Component Library (CCL) Name - Lists the names of all the loaded
libraries in the CPM.
Data Type String (One Dimensional Array)
Range Length : 40 Characters
Default Null String
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200(CPM), C300(CEEC300)
Related CCLCNT, CCLINFO
Parameters
Remarks

5.69 CCLPACKET

Specific to Block(s) CPM, CEEC300


Description Library Load Parameter
Data Type BLOB
Range
Default
Config Load No
Active Loadable No
Access Lock Engineer
Residence C200(CPM), C300(CEEC300)
Related Parameters
Remarks

5.70 CCLSIZE[0..49]

Specific to Block(s) CPM, CEEC300


Description Control Component Library (CCL) Size - Lists sizes of loaded libraries.
Data Type 32-Bit Integer
Range N/A
Default 0
Config Load No
Active Loadable No

- 458 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence C200(CPM), C300(CEEC300)
Related CCLCNT, CCLINFO, CCLNAME
Parameters
Remarks Contains the sizes of all the loaded libraries in the CPM (DataSize +
CodeSize).

5.71 CCRRUNCOUNT

Specific to Block(s) RCM


Description CR Run Count
Data Type 32-Bit Integer
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

5.72 CDDMTYPINSTCNT

Specific to Block(s) CEEC300, CEE(C200), CEE(ACE), CEE(SIMC200), CEEUOC


Description Block Type Instance Count
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEE),C200(CEE),ACE(CEE),SIM200(CEE) , UOC(CEE)
Related Parameters
Remarks

- 459 -
Chapter 5 - Cxxxx Parameters

5.73 CDDMTYPNAME

Specific to Block(s) CEEFB,CEEACEFB,CEESIMC200FB,CEEC300, CEEUOC


Description Block Type Name
Data Type String
Range Length: max. 83 characters
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ER DB and SR DB
Related Parameters
Remarks

5.74 CDISPAVGCHPPS

Specific to EHPM
Block(s)
Description This parameter shows the average cache hit rate for display data access, that is,
average of number of requests serviced by cache for display data access.
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

5.75 CDISPAVGLPS [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Execution Environment Display Average IMRs Per Seconds - The average number
of display messages per second processed by the execution environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0

- 460 -
Chapter 5 - Cxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related STATSRESET
Parameters
Remarks

5.76 CDISPAVGLPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Execution Environment Display Average IMRs Per Connection - The average
number of display messages per connection processed by the execution
environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, CEEUOC
Related STATSRESET, CDISPMAXLPSCONN
Parameters
Remarks

5.77 CDISPAVGPPS [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Execution Environment Display Average Parameters Per Seconds - The average
number of display peer parameters per second processed by the execution
environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable

- 461 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related STATSRESET
Parameters
Remarks

5.78 CDISPAVGPPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Average Display Parameters Per Second - Indicates the average number of peer
parameters/sec processed by the Execution Environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related STATSRESET
Parameters
Remarks

5.79 CDISPAVGSPS [1...RDISPCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Control Execution Environment Display Average Stores Per Seconds - The average
number of display acyclic stores per second processed by the execution
environment.
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 462 -
Chapter 5 - Cxxxx Parameters

5.80 CDISPAVGSPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Average Display Acyclic Stores Per Second - Indicates the average number of
display acyclic stores/sec processed by the Execution Environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related STATSRESET
Parameters
Remarks

5.81 CDISPEXCHAVGPPSCONN

Specific to Block(s) CEEFB, CEEC300


Description Average Exchange Display Parameter Per Second get rate per connection.
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.82 CDISPEXCHAVGSPSCONN

Specific to Block(s) CEEFB, CEEC300


Description Average Exchange Display Parameter Store Per Second store rate per
connection.
Data Type Float64
Range
Default 0.0

- 463 -
Chapter 5 - Cxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

5.83 CDISPEXCHMAXPPSCONN

Specific to Block(s) CEEFB, CEEC300


Description Maximum Exchange Display Parameter Per Second get rate per
connection.
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.84 CDISPEXCHMAXSPSCONN

Specific to Block(s) CEEFB, CEEC300


Description Maximum Exchange Display Parameter Store Per Second store rate per
connection.
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 464 -
Chapter 5 - Cxxxx Parameters

5.85 CDISPMAXCHPPS

Specific to EHPM
Block(s)
Description This parameter shows the maximum cache hit rate for display data access, that is,
maximum of number of requests serviced by cache for display data access.
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

5.86 CDISPMAXLPS [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Execution Environment Display Maximum IMRs Per Seconds - The maximum
number of display messages per second processed by the execution environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related STATSRESET
Parameters
Remarks

- 465 -
Chapter 5 - Cxxxx Parameters

5.87 CDISPMAXLPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Execution Environment Display Maximum IMRs Per Connection - The maximum
number of display messages per connection processed by the execution
environment.
Data Type FLOAT64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related STATSRESET
Parameters
Remarks

5.88 CDISPMAXPPS [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Execution Environment Maximum Display Parameters Per Seconds - The
maximum number of display peer parameters per second processed by the
execution environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related STATSRESET
Parameters
Remarks

- 466 -
Chapter 5 - Cxxxx Parameters

5.89 CDISPMAXPPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Maximum Display Parameters Per Second - Indicates the maximum number of
peer parameters/sec processed by the Execution Environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related STATSRESET
Parameters
Remarks

5.90 CDISPMAXSPS [1...RDISPCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Control Execution Environment Maximum Display Stores Per Seconds - The
maximum number of display acyclic stores per second processed by the execution
environment.
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 467 -
Chapter 5 - Cxxxx Parameters

5.91 CDISPMAXSPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC


Block(s)
Description Maximum Display Acyclic Stores Per Second - Indicates the maximum number of
display acyclic stores/sec processed by the Execution Environment.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC)
Related STATSRESET
Parameters
Remarks

5.92 CEECMDENUMMASK

Specific to CEEC300, CEE, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description CEE Command Enumeration Mask
Data Type String
Range
Default None
Config Load No
Active No
Loadable
Access Lock Supervisor or Engineer - when an Idle command is stored to CEECOMMAND and
the CEE is in the Run state. Supervisor, Engineer or Operator - when a
CEECOMMAND of Run is stored and the CEE is in Idle.
Residence SR
Related CEECOMMAND
Parameters
Remarks

- 468 -
Chapter 5 - Cxxxx Parameters

5.93 CEECOLDFL

Specific to STARTSIGNAL
Block(s)
Description Control Execution Environment (CEE) Cold Flag - Holds True for the first
execution cycle following cold start of the CEE.
Data Type Boolean
Range True False
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RESTART
Parameters
Remarks

5.94 CEECOMMAND

Specific to CEEC300, CEE, CPM, CEEUOC, CEECN100


Block(s)
Description Control Execution Environment (CEE) Command - Stores to this parameter toggle
CEESTATE parameter between Idle and Run states.
Data Type Enumeration
Range IDLE (0) RUN (1) NONE (2) COLDSTART(3) WARMSTART(4)
Default IDLE (0)
Config No
Load
Active No
Loadable
Access Lock Supervisor or Engineer - when an Idle command is stored to CEECOMMAND and
the CEE is in the cold start/warm start state. Supervisor, Engineer or Operator -
when a CEECOMMAND of cold start/warm start is stored and the CEE is in Idle.
Residence C200(CEE, CPM), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related CEESTATE
Parameters
Remarks If the controller is loaded with strategies and power is lost / rebooted user can
command cold start or warm start. In case of warm start all the strategies will retain
the old values (Values just before controller lost power/re-started).This is also
called as RRR (RAM Retention Restart). For Warm start, Battery should be in good
condition. When Cold start is commanded all the strategies will be initiated with
default values.

- 469 -
Chapter 5 - Cxxxx Parameters

5.95 CEEIOID

Specific to Block(s) C300 FB, CN100 and C300


Description CEE Block IOID
Data Type BlockID
Range --
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, CEE
Related Parameters IOLINK1IOID, IOLINK2IOID
Remarks Displays the C300CEE FB name

5.96 CEEIP

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Specifies the IP address of the C300 Controller, which is emulating the box
Data Type String
Range NA
Default 0.0.0.0
Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related TGTIP
Parameters
Remarks This parameter displays the IP address of C300 Controller which is emulating
the box.

5.97 CEENUM

Specific to Block(s) N/A (this parameter is directly on the point)


Description Experion PKS server parameter that contains an identifier for the CDA
controller
Data Type INT2
Range 0-65536
Default 0 (point has never been accessed on server)
Config Load N/A

- 470 -
Chapter 5 - Cxxxx Parameters

Active Loadable N/A


Access Lock N/A
Residence N/A
Related N/A
Parameters
Remarks This parameter is generally used within Experion PKS server only.

5.98 CEERESADDR[1..15]

Specific to Block(s) SCM


Description SCM Start Address on CEE Restart
Data Type BlockID
Range
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

5.99 CEERESADDRN[1..15]

Specific to Block(s) SCM


Description Numeric SCM Start Address on CEE Restart
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 471 -
Chapter 5 - Cxxxx Parameters

5.100 CEESTARTOPT

Specific to CM
Block(s)
Description Control Execution Environment Start Option - Allows the application designer to
override the warm or cold selection made by an operator at runtime
Data Type Enumeration CEERESTARTOPT
Range FOLLOWCEE (0) Follow the restart commanded for CEE. For this
configuration, parent control modules instruct their
component blocks to initialize according to whichever type of
restart the operator has selected for the CEE as a whole:
cold or warm.
ALWAYSCOLD (1) Execute cold start behavior. For this configuration, parent
control modules instruct their component blocks to do a cold
restart regardless of which restart option has been selected
for the CEE as a whole.
ALWAYSWARM (2) Execute warm start behavior. For this configuration, parent
control modules instruct their component blocks to do a
warm restart regardless of which restart option has been
selected for the CEE as a whole.
Default ALWAYSCOLD (1)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CEECOLDFL, CEECOMMAND, EXECSTATE, PCMSTATE.
Parameters
Remarks Control modules do not have functionality modified by selection of warm or cold
restart, but the behavior of blocks contained within the control module can be
impacted.

Specific to SCM, RCM


Block(s)
Description Control Execution Environment Start Option - Select SCM/RCM behavior on CEE
Restart
Data Type Enumeration CEERESTARTOPT
Range FOLLOWCEE (0) Follow the restart commanded for CEE
ALWAYSCOLD (1) Execute cold start behavior
ALWAYSWARM (2) Execute warm start behavior
Default FOLLOWCEE (0)
Config Yes
Load
Active No
Loadable

- 472 -
Chapter 5 - Cxxxx Parameters

Access Engineer
Lock
Residence CEE
Related CEECOLDFL, CEECOMMAND, EXECSTATE, PCMSTATE.
Parameters
Remarks On cold start, the SCM/RCM will be activated if it was not inactive before and Mode
set to MANUAL. Normally the SCM/RCM will be in IDLE. If a check handler exists,
further execution will depend on Check Handler Invoke Transition and parameter
EXCMODEOPT. Therefore, the effect of the cold start mode MANUAL may be
cancelled out by a true check handler invoke transition and EXCMODEOPT=AUTO. It
is the responsibility of the engineer to consider the interactions of those
parameters On warm start, the SCM/RCM will be activated if it was not inactive
before. Normally the SCM/RCM will be in IDLE. If a check handler exists, further
execution will be depend on Check Handler Invoke Transition. This parameter has
no effect on inactive SCMs/RCMs. Inactive SCMs/RCMs always remain inactive on
CEE Restart.

Specific to UCM
Block(s)
Description Control Execution Environment Start Option -Select UCM behavior on CEE
Restart
Data Type Enumeration CEERESTARTOPT
Range FOLLOWCEE (0) Follow the restart commanded for CEE.
ALWAYSCOLD (1) Execute cold start behavior.
ALWAYSWARM (2) Execute warm start behavior.
Default FOLLOWCEE (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CEECOLDFL, CEECOMMAND, EXECSTATE, PCMSTATE.
Parameters
Remarks Note that UCMs have no restart type dependent behavior, so the value of this
parameter has no impact at this time.

Specific to Block(s) MR
Description Control Execution Environment Start Option - Select MR behavior on CEE
Restart
Data Type Enumeration CEERESTARTOPT
Range ALWAYSCOLD (1) - Execute cold start behavior
Default ALWAYSCOLD (1)
Config Load No
Active Loadable No

- 473 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related CEECOLDFL, CEECOMMAND, EXECSTATE, PCMSTATE.
Parameters
Remarks

5.101 CEESTATE

Specific to CEEC300, CEE, CEEACE, CEESIMC200, CM, SCM, IOM, CPM, ACE, CEEUOC,
Block(s) CEECN100
Description Control Execution Environment State - Gives current state of CEE.
Data Type Enumeration
Range Idle (0) Run (1) Failed (2) NotLoaded (3)
Default Idle (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, CM, SCM, IOM), C200(CEE, CPM, CM, SCM, IOM), ACE(CEEACE,
ACE, CM, SCM), SIMC200(CEESIMC200, CM, SCM), UOC(CEEUOC, CM, SCM, IOM),
CN100(CEECN100, CM, IOM)
Related CEECOMMAND, EXECSTATE, PCMSTATE
Parameters
Remarks Although this parameter is most logically associated with the CEE and CEEC300,
CEEACE and CEESIMC200 function blocks, it is exposed as a parameter on CM,
SCM, and IOM as well. It is exposed on C200 and ACE FBs in C200 and ACE
platforms.
l Note that CEESTATE can be changed only by writing to the CEECOMMAND
parameter.
l When CEESTATE is Run, all active blocks within the CEE execute.
l When CEESTATE is Idle, only CEE and IOM FBs execute.
l CEE FB issues a change of state notification whenever CEESTATE is changed.
l CEESTATE holds the value NOTLOADED until the first load of the CEE.
l For CEE state in RRR refer RRRCEESTATE.

- 474 -
Chapter 5 - Cxxxx Parameters

5.102 CEESWITCHFL

Specific to STARTSIGNAL
Block(s)
Description Control Execution Environment (CEE) Switch Flag - Holds True for the first
execution cycle following redundant switchover of the CEE on a C200/C200E
Controller or C300 Controller. Value of CEESWITCHFL is true during an OPM. The
RESTART value will equal CEESWITCH (6) during the indirect synchronization of
redundant controllers during On Process Migration.
Data Type Boolean
Range True False
Default False
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RESTART
Parameters
Remarks

5.103 CEETAG

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description C300 Controller tag name
Data Type String
Range 0-128
Default 0
Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter displays the tag name of C300 Controller which is emulating
the box.

- 475 -
Chapter 5 - Cxxxx Parameters

5.104 CEETOPSTART

Specific to SCM
Block(s)
Description SCM Start on CEE Restart
Data Type Boolean
Range On/Off
Default On
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related
Parameters
Remarks If the CEETOPSTART parameter is set as "ON," then the CEE restarts and the SCM
starts executing at the top of the CHECK handler unless the operator commands
execution to start at a different handler. The values of CEERESADDR[ ] and the
various SET.UPDCEERESOPT parameters have no impact on where the SCM
resumes execution. If the CEETOPSTART parameter is set as "OFF," then the CEE
restarts and the SCM starts executing a STEP within the MAIN handler that is
indicated by the value of CEERESADDR[ ].

Specific to Block(s) MR
Description MR Start on CEE Restart
Data Type Boolean
Range On
Default On
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 476 -
Chapter 5 - Cxxxx Parameters

5.105 CEEWARMFL

Specific to STARTSIGNAL
Block(s)
Description Control Execution Environment (CEE) Warm Flag - Holds True for the first
execution cycle following warm start of the CEE.
Data Type Boolean
Range True False
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RESTART
Parameters
Remarks

5.106 CF1

Specific to FLOWCOMP
Block(s)
Description Conversion Factor - Used to convert the uncompensated flow to the same units as
the compensated flow (for example, mass-flow to volumetric-flow), or correct for
assumed design conditions.
Data Type 32-Bit Real Number
Range CF1 greater than 0.0
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks

- 477 -
Chapter 5 - Cxxxx Parameters

5.107 CF2

Specific to FLOWCOMP
Block(s)
Description Conversion Factor - Used to convert the uncompensated flow to the same units as
the compensated flow (for example, mass-flow to volumetric-flow), or correct for
assumed design conditions.
Data Type 32-Bit Real Number
Range CF2 greater than 0.0
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks

5.108 CFIFORATEA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Average Cache FIFO Access Rate. Shows the average number of parameters
accessed through cache FIFO per second.
Data Type 32-Bit Real Number
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

- 478 -
Chapter 5 - Cxxxx Parameters

5.109 CFIFORATEM

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Maximum Cache FIFO Access Rate. Shows the maximum number of parameters
accessed through cache FIFO per second.
Data Type 32-Bit Real Number
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

5.110 CHANFBNAME[0..63]

Specific to Block(s) PCDI_MASTER


Description Name of assigned Channel Function Block
Data Type String
Range
Default (Unassigned)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Cee
Related Parameters
Remarks

5.111 CHANINUSE[0..31]

Specific to RM, Serial Interface IOM


Block(s)
Description Channel In Use - Indicates whether the Channel is currently being used (a value of
On) or not (a value of Off).
Data Type Boolean
Range Off (0) On (1)

- 479 -
Chapter 5 - Cxxxx Parameters

Default Off (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence CEE
Related CHANSTS[0..31]
Parameters
Remarks

- 480 -
Chapter 5 - Cxxxx Parameters

5.112 CHANLASTMBERR[0..63]

- 481 -
Chapter 5 - Cxxxx Parameters

Specific to Block(s) PCDI_MASTER


Description Last Modbus Channel Error
Data Type Enumeration

- 482 -
Chapter 5 - Cxxxx Parameters

Range 0 OK

- 483 -
Chapter 5 - Cxxxx Parameters

1 No More Data

- 484 -
Chapter 5 - Cxxxx Parameters

2 Already Added

- 485 -
Chapter 5 - Cxxxx Parameters

3 Send Limit
4 Orphan Resp
5 Diag Testing
6 Already Added with Send Limit
256 Generic Fail
257 Not Init
258 Invalid Param
259 Unsupported Cmd
260 Resources
261 Invalid UID
262 No Device
263 Add Fail
264 Send Fail
265 Send Err
266 No Conn
267 Sock Err
268 Bad Buffer
269 Internal Err
270 Timed Out
271 Not Found
272 Wait Failed
273 Dev Disabled
274 Rcv Msg Len
275 Bad Resp
276 Bad Xact
277 Unexpected Diag Val
278 Master Inactive
279 Device Init
280 Device Fail
281 SM Idle
512 Illegal Func
513 Illegal Addr
514 Illegal Data
515 Slave Fail
516 Ack Fail
517 Slave Busy
518 Parity Err
519 Bad Path
520 No Target Resp

- 486 -
Chapter 5 - Cxxxx Parameters

Default Not Init


Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.113 CHANLASTMBERRTIME[0..63]

Specific to Block(s) PCDI_MASTER


Description Last Modbus Channel Error Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.114 CHANMBERRCNT[0..63]

Specific to Block(s) PCDI_MASTER


Description Modbus Channel Error Count
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 487 -
Chapter 5 - Cxxxx Parameters

5.115 CHANMBERRFL[0..63]

Specific to Block(s) PCDI_MASTER


Description Modbus Channel Error Flag
Data Type Boolean
Range On/Off
Default On
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.116 CHANNAME

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Channel Name
Data Type String
Range 40 Characters
Default (unassigned)
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

5.117 CHANNAME[1..NUMCHAN]

Specific to HLAI, HLAI_100, STI_MV, AO8, AO16, DI, DI24, DISOE, DO16, DO32
Block(s)
Description Channel Block Name
Data Type String
Range Length : 16 characters
Default N/A
Config Yes
Load
Active No

- 488 -
Chapter 5 - Cxxxx Parameters

Loadable
Access Lock Application Developer
Residence IOP
Related
Parameters
Remarks A unique name up to identify the block in the system. The module name should
reflect the type of module being used and its location. This will make tracking easier
in the future when you add more modules to your system. For example, the module
name PI_IOM_01 might stand for Pulse Input - Input Output Module - Primary
chassis. This name appears on all related system displays and any generated
reports.

5.118 CHANNEL [0..NUMCHANNELS-1]

Specific to EIP IOM: 1732E-IT4IM12R


Block(s)
Description Select Channel for Cold Junction Compensation.
Data Type BOOLEAN
Range l 1: ON
l 0: OFF
Default OFF
Config No
Load
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related CJMODE, CJENABLE
Parameters
Remarks This option is available only if the Cold Junction Compensation Mode is Average
Selected. It allows you to select all the channels that have a thermistor attached.
When a single channel is selected, the thermistor attached to that channel
provides the compensation temperature for all channels. When more than one
channel is selected, the temperature used by the selected channels is averaged
across all the selected channels that have a valid thermistor detected.

5.119 CHANNUM

Specific to PMIO Channel Blocks; Series C I/O Channel Blocks


Block(s)
Description Channel Number. Defines the channel number or slot number of the associated
I/O Processor (IOP)/ I/O Module IOMpoint.
Data Type 16-Bit Unsigned Integer
Range 1 to number of points on associated IOP/IOM

- 489 -
Chapter 5 - Cxxxx Parameters

Default 1
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks The term Channel has the same meaning as the TPS term Slot.

Specific to Block PCDI_MASTER


(s)
Description Channel Number - Defines the channel number of the associated Array
Request Channel block.
Data Type 16-Bit Unsigned Integer
Range 0 to number of associated channels
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related
Parameters
Remarks

5.120 CHANREQRSPRCVD[0..63]

Specific to Block(s) PCDI_MASTER


Description Channel Request Responses Received
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 490 -
Chapter 5 - Cxxxx Parameters

5.121 CHANREQSENT[0..63]

Specific to Block(s) PCDI_MASTER


Description Channel Request Sent
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.122 CHANRSTSTATS

Specific to Block(s) PCDI_MASTER


Description Channel Reset Statistics
Data Type Boolean
Range True/False
Default False
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks Click button to reset channel statistics to zero in Monitoring mode.

- 491 -
Chapter 5 - Cxxxx Parameters

5.123 CHANSTS

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Channel Status
Data Type Enumeration
Range 0 Not Used
1 No Data
2 Idle
3 CEE Idle
4 Simulate
5 Fail
6 Run
Default Not Used
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.124 CHANSTS[0..63]

Specific to Block(s) PCDI_MASTER


Description Channel Status
Data Type Enumeration
Range 0 Not Used
1 No Data
2 Idle
3 CEE Idle
4 Simulate
5 Fail
6 Run
Default Not Used
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 492 -
Chapter 5 - Cxxxx Parameters

5.125 CHANSTS[0..31]

Specific to RM, Serial Interface IOM


Block(s)
Description Channel Status - Provides a status for each channel of the module.
Data Type Enumeration
Range NotUsed(0) Ok(1) Bad(2)
Default NotUsed(0)
Config Load No
Active No
Loadable
Access Lock ViewOnly RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence CEE
Related CHANINUSE[0..31], ERRFL[0..31].
Parameters
Remarks

5.126 CHANTEXT

Specific to IOM
Block(s)
Description Channel In Use - Indicates whether the Channel is currently being used (a value
of On) or not (a value of Off).
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 493 -
Chapter 5 - Cxxxx Parameters

5.127 CHANTYPE

Specific to AIREF, AOREF, DIREF, and DOREF


Block(s)
Description Channel Type
Data Type BLOCKID
Range Not Applicable
Default Not Applicable
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence ERDBONLY
Related REFTYPE
Parameters
Remarks This parameter is used for setting to a specific type that can be referenced when
REFTYPE is configured as "SERIES_C_IO" or "PMIO." This parameter is disabled
when the REFTYPE is set "PARAMETER" or "NONE."

5.128 CHASSISSIZE

Specific to 1738-AENT
Block(s)
Description Chassis size — Number of modules in this chassis. The chassis size is the number
of Input modules + number of output modules + 1 for the adapter.
Data Type UINT32
Range 1-64
Default 1
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks

- 494 -
Chapter 5 - Cxxxx Parameters

5.129 CHGINDEX

Specific to CHGEXEC
Block(s)
Description Output which gives index of input which changed, causing the CHGEXEC to allow
its parent CM to run to completion.
Data Type 32-Bit Integer
Range 0 to 32
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence CEE
Related DATA[1..32]LASTDATA[1..32]
Parameters
Remarks Changed input INDEX

5.130 CHIGHREADAVGPPS

Specific to EHPM
Block(s)
Description This parameter shows the average parameters per second load during display read
operation. This is a high-priority read load (for example, standard history read,
display startup load and so on).
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

- 495 -
Chapter 5 - Cxxxx Parameters

5.131 CHIGHREADMAXPPS

Specific to EHPM
Block(s)
Description This parameter shows the maximum parameters per second load during display
read operation. This is a high-priority read load (for example, standard history read,
display startup load and so on).
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

5.132 CHGOFSTALM.PR

Specific to FLAG, DEVCTL, and DIGACQ


Block(s)
Description Change of state Alm Priority
Data Type ENUM
Range NONE, JOURNAL, LOW, HIGH and URGENT
Default NONE
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CHGOFSTALM.SVCHGOFSTALM.TMCHGOFSTALMENBALMSELOPT
Parameters
Remarks The COS alarm is reported in the station with the given priority mentioned under
priority column. The Possible priorities are None, Journal, Low, High and Urgent.

- 496 -
Chapter 5 - Cxxxx Parameters

5.133 CHGOFSTALM.SV

Specific to Block(s) FLAG, DEVCTL, and DIGACQ


Description Change of state alarm Severity
Data Type INT16
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters CHGOFSTALM.TMCHGOFSTALMENBALMSELOPTCHGOFSTALM.PR
Remarks The COS alarm is reported in the station with the configured Severity.

5.134 CHGOFSTALM.TM

Specific to FLAG, DEVCTL, and DIGACQ


Block(s)
Description Change of state alarm Delay. Delay configured for COS alarm.
Data Type UINT32
Range 0 to 9999
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CHGOFSTALMENBALMSELOPTCHGOFSTALM.PRCHGOFSTALM.SV
Parameters
Remarks The COS alarm is reported in the station after a configured delay time whenever
there is a state change in FLAG, DEVCTL or DIGACQ blocks.

5.135 CHILDUCMACQ

Specific to PHASE
Block(s)
Description UCM acquisition instruction to child
Data Type Enumeration
Range 0 AcquireUCM
1 Don'tAcquireUCM

- 497 -
Chapter 5 - Cxxxx Parameters

Default AcquireUCM
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks This parameter is used by the parent RCM (through PHASE block) to instruct the
child if UCM should be acquired by the child or not.The “AcquireUCM” allows the
child to acquire the UCM if it has one configured. If the child has no UCM
configured, the instruction will be ignored. The “Don'tAcquireUCM” does not allow
the child to acquire the UCM it configured.

5.136 CHNFLTSTS[0..numChans-1]

Specific to l 1738–OE2CM12
Block(s)
l 1738–OE4CM12
l 1732E-OF4M12R
Description Channel Fault Status — It indicates the health of the channel.
Data Type Boolean
Range l 0 : Off
l 1 : On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks If the value is ON, then it indicates that the state of the channel is faulty. If the
value is OFF, the it indicates that the channel is in a good state.

5.137 CHNLNAME

Specific to Block All Series C I/O Modules


(s)
Description Channel Name
Data Type STRING
Range Length: 40 characters

- 498 -
Chapter 5 - Cxxxx Parameters

Default
Config Load No
Access Lock ViewOnly
Active Loadable No
Residence IOM
Related AICHNLNAMEAOCHNLNAMEDICHNLNAMEDOCHNLNAME
Parameters
Remarks This parameter identifies the configured name of the channels associated with
this IOM block.

5.138 CHNLNAME_AI_C

Specific to Block UIO


(s)

Description Channel Name


Data Type String
Range

Default

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters

Remarks Used to display the channel names on the channel specific Configuration tabs of
the UIO module.

Displays the channel names in the AI configuration tab of the UIO module.
This parameter displays only the channel names configured with the PNTTYPE of
AI.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description Channel Name
Data Type String
Range

Default

Config No
Load

Active
Loadable

- 499 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock

Residence SR
Related
Parameters

Remarks Used to display the channel name on the channel specific Configuration tab of the UIO
module.
For the single purpose modules some of these parameters may not apply. For example in
case of UAI, CHNLNAME_AO_C, CHNLNAME_DI_C and CHNLNAME_DO_C will not apply.

5.139 CHNLNAME_AI_S

Specific to Block(s) UIO


Description Channel Name
Data Type String
Range

Default

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters

Remarks Displays the channel names in the AI Status tab of the UIO module.
This parameter displays only the channel names configured with the PNTTYPE of
AI.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description Channel Name
Data Type String
Range

Default

Config No
Load

Active
Loadable

- 500 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock

Residence SR
Related
Parameters

Remarks Used to display the channel name on the channel specific Status tab of the UIO module.
For the single purpose modules some of these parameters may not apply. For example in
case of UAI, CHNLNAME_AO_S, CHNLNAME_DI_S and CHNLNAME_DO_S will not apply.

5.140 CHNLNAME_AO_C

Specific to Block UIO


(s)

Description Channel Name


Data Type String
Range

Default

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters

Remarks Used to display the channel names on the channel specific Configuration tabs of
the UIO module.
Displays the channel names in the AO Configuration tab of the UIO module.
This parameter displays only the channel names configured with the PNTTYPE of
AO.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description Channel Name
Data Type String
Range

Default

Config No
Load

Active
Loadable

- 501 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock

Residence SR
Related
Parameters

Remarks Used to display the channel name on the channel specific Configuration tab of the UIO
module.
For the single purpose modules some of these parameters may not apply. For example in
case of UAI, CHNLNAME_AO_C, CHNLNAME_DI_C and CHNLNAME_DO_C will not apply.

5.141 CHNLNAME_AO_S

Specific to Block(s) UIO


Description Channel Name
Data Type String
Range

Default

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters

Remarks Displays the channel names in the AO Status tab of the UIO module.
This parameter displays only the channel names configured with the PNTTYPE of
AO.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description Channel Name
Data Type String
Range

Default

Config No
Load

Active
Loadable

- 502 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock

Residence SR
Related
Parameters

Remarks Used to display the channel name on the channel specific Status tab of the UIO module.
For the single purpose modules some of these parameters may not apply. For example in
case of UAI, CHNLNAME_AO_S, CHNLNAME_DI_S and CHNLNAME_DO_S will not apply.

5.142 CHNLNAME_DI_C

Specific to Block UIO


(s)

Description Channel Name


Data Type String
Range

Default

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters

Remarks Used to display the channel names on the channel specific Configuration tabs of
the UIO module.
Displays the channel names in the DI configuration tab of the UIO module.
This parameter displays only the channel names configured with the PNTTYPE of
DI.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description Channel Name
Data Type String
Range

Default

Config No
Load

Active
Loadable

- 503 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock

Residence SR
Related
Parameters

Remarks Used to display the channel name on the channel specific Configuration tab of the UIO
module.
For the single purpose modules some of these parameters may not apply. For example in
case of UAI, CHNLNAME_AO_C, CHNLNAME_DI_C and CHNLNAME_DO_C will not apply.

5.143 CHNLNAME_DI_S

Specific to Block(s) UIO


Description Channel Name
Data Type String
Range

Default

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters

Remarks Displays the channel names in the DI Status tab of the UIO module.
This parameter displays only the channel names configured with the PNTTYPE of
DI.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description Channel Name
Data Type String
Range

Default

Config No
Load

Active
Loadable

- 504 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock

Residence SR
Related
Parameters

Remarks Used to display the channel name on the channel specific Status tab of the UIO module.
For the single purpose modules some of these parameters may not apply. For example in
case of UAI, CHNLNAME_AO_S, CHNLNAME_DI_S and CHNLNAME_DO_S will not apply.

5.144 CHNLNAME_DO_C

Specific to Block UIO


(s)

Description Channel Name


Data Type String
Range

Default

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters

Remarks Used to display the channel names on the channel specific Configuration tabs of
the UIO module.
Displays the channel names in the DO Configuration tab of the UIO module.
This parameter displays only the channel names configured with the PNTTYPE of
DO.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description Channel Name
Data Type String
Range

Default

Config No
Load

Active
Loadable

- 505 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock

Residence SR
Related
Parameters

Remarks Used to display the channel name on the channel specific Configuration tab of the UIO
module.
For the single purpose modules some of these parameters may not apply. For example in
case of UAI, CHNLNAME_AO_C, CHNLNAME_DI_C and CHNLNAME_DO_C will not apply.

5.145 CHNLNAME_DO_S

Specific to Block(s) UIO


Description Channel Name
Data Type String
Range

Default

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters

Remarks Displays the channel names in the DO Status tab of the UIO module.
This parameter displays only the channel names configured with the PNTTYPE of
DO.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description Channel Name
Data Type String
Range

Default

Config No
Load

Active
Loadable

- 506 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock

Residence SR
Related
Parameters

Remarks Used to display the channel name on the channel specific Status tab of the UIO module.
For the single purpose modules some of these parameters may not apply. For example in
case of UAI, CHNLNAME_AO_S, CHNLNAME_DI_S and CHNLNAME_DO_S will not apply.

5.146 CHNLNAME[1..NUMCHAN]

Specific to Block AI-HART, AI-HL, AI-LLMUX, AI-LLAI, AO-HART, AO, DI-HV, DI-24, DI-SOE, DO-
(s) 24B
Description Channel Block Name
Data Type String
Range
Default
Config Load Yes
Active Loadable No
Active Loadable No
Access Lock View Only
Residence SR
Related
Parameters
Remarks If a channel is put in the Red Tag condition, the output is frozen at the last
value or state.

5.147 CHNLSF1A

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description Primary IOM Channel Failures
Data Type Bit String
Range N/A
Default 0
Config Load No
Active No
Loadable

- 507 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related N/A
Parameters
Remarks Primary IOM. Each bit represents one of the Soft Failures listed in the PM IO and
Series C IO Soft Failure codes spreadsheet.

5.148 CHNLSF2A

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description Primary IOM Channel Failures
Data Type Bit String
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks Primary IOM. Each bit represents one of the Soft Failures listed in the PM IO and
Series C IO Soft Failure codes spreadsheet.

5.149 CHNLSF1B

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description Secondary IOM Channel Failures
Data Type Bit String
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks Secondary IOM. Each bit represents one of the Soft Failures listed in the PM IO
and Series C IO Soft Failure codes spreadsheet.

- 508 -
Chapter 5 - Cxxxx Parameters

5.150 CHNLSF2B

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description Secondary IOM Channel Failures
Data Type Bit String
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks Secondary IOM. Each bit represents one of the Soft Failures listed in the PM IO
and Series C IO Soft Failure codes spreadsheet.

5.151 CHNSTS[0..numChans-1]

Specific to 1738-OB2EPM12 and 1738-OB8EM12


Block(s)
Description Channel status — It indicates the health of the channel. If ON = Channel is in a
faulted state. If OFF = Channel is in good state. This is the information that is
obtained from the module.
Data Type Boolean
Range l 0 : OFF
l 1 : ON
Default OFF
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related None
Parameters
Remarks

- 509 -
Chapter 5 - Cxxxx Parameters

5.152 CIDLOADMORE

Specific to Block(s) 850M


Description CID Load More Info
Data Type UINT32
Range 0
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

5.153 CIDLOADSTATUS

Specific to Block(s) 850M


Description CID Load Status
Data Type ENUM
Range l 0 - FILENOTLOADED
l 1 - STACKPROCESSING
l 2 - SUCCESS
l 3 - FAILURE
l 4 - OUTOFMEMORY
Default FILENOTLOADED
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

5.154 CINCONNHNDL[1..10][1..6]

Specific to Block(s) Transition


Description This is an Internal Parameter for system use only.
Data Type
Range

- 510 -
Chapter 5 - Cxxxx Parameters

Default
Config Load No
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

5.155 CINCONNNAV[1..10][1..6]

Specific to Block(s) Transition


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load No
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

5.156 CINCONNPRM[1..10][1..6]

Specific to Block(s) Transition


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

- 511 -
Chapter 5 - Cxxxx Parameters

5.157 CINCONNSTRVAL[1..10][1..6]

Specific to Block(s) Transition


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

5.158 CINCONNVAL[1..10][1..6]

Specific to Block(s) Transition


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load No
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

5.159 CJDISABLE

Specific to AIM, RM
Block(s)
Description Cold Junction Disable - Appears as a configuration checkbox that when enabled
allows CJOFFSET to be configured.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer RM only: Requests to read or store to any RM parameter

- 512 -
Chapter 5 - Cxxxx Parameters

must come from the Supervisory platform (through Control Builder or Server).
Residence CEE
Related CJOFFSET CJOFFSET
Parameters
Remarks For AIM, CJDISABLE is only configurable on the Thermocouple Module.

5.160 CJENABLE [0..NUMCHANNELS-1]

Specific to Block(s) EtherNet/IP [EIP] IOMs: 1738-IT2IM12, 1732E-IT4IM12R


Description Cold Junction Compensation: Used to enable or disable the Cold Junction
sensor.
Data Type BOOLEAN
Range l 1: ON
l 0: OFF
Default
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related CJOFFSET, CJMODE, CJNOTCHFLT
Parameters
Remarks

5.161 CJMODE

Specific to EtherNet/IP [EIP] IOMs: 1738-IT2IM12, 1732E-IT4IM12R


Block(s)
Description Cold Junction Compensation Mode: Determines where the cold junction
temperature measurement source is located.
Data Type Enumeration
Range 1738-IT2IM12:
l None
l Channel-01 (default)
l Channel -02
l Average Both
1732E-IT4IM12R:
l Average selected (default)
l Channel Independent
Default 1738-IT2IM12 — Channel-01 1732E-IT4IM12R — Average selected
Config Load No
Active No

- 513 -
Chapter 5 - Cxxxx Parameters

Loadable
Access Lock AppDevOnly
Residence SR
Related CJOFFSET, CJENABLE, CHANNEL[0-3]
Parameters
Remarks

5.162 CJNOTCHFLT

Specific to Block(s) EtherNet/IP [EIP] IOMs: 1738-IT2IM12


Description Notch Filter for Cold Junction Compensation.
Data Type Enumeration
Range 1738-IT2IM12:
l 60 Hz
l 50 Hz
Default 60 Hz
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

5.163 CJOFFSET

Specific to Block AIC


(s)
Description Cold Junction Offset - Offset to be added to cold junction temperature as a
correction factor.
Data Type 64-Bit Real Number
Range -5 to +5 degrees (C or F)
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Not Loaded
Related CALBIASCJDISABLE.
Parameters
Remarks Configurable only when CJDISABLE is set.

- 514 -
Chapter 5 - Cxxxx Parameters

5.164 CJOFFSET[0..numChans-1]

Specific to AIM
Block(s)
Description Cold Junction Offset - Offset to be added to cold junction temperature as a
correction factor.
Data Type 64-Bit Real Number
Range -5 to +5 degrees (C or F)
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE (TC-IAH161(1756-IF16) not loaded)
Related CALBIAS[0..numChans-1], CJDISABLE (AIM only).
Parameters
Remarks CJOFFSET is accessible by the Application Developer on the Thermocouple AIM
Configuration Form only. Configurable only when CJDISABLE is set.

5.165 CJOFFSET [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1738-IT2IM12, 1732E-IT4IM12R


Block(s)
Description Cold Junction Offset — Cold Junction Offset compensates for the inaccuracies of
the Cold Junction sensor.
Data Type INT 16
Range 0 – 7000 (0 to 70° C)
Default 0
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related CJENABLE, CJMODE
Parameters
Remarks CJOFFSET accepts the raw count in ° C with precision of 2 decimal places in the
range of 0.00 C to 70.00 °C. Raw Count = °C x 100. [Example: For 28.00°C (82.40°F),
its value will be 2800 (28.00x100)

- 515 -
Chapter 5 - Cxxxx Parameters

5.166 CJOVERRANGE

Specific to EtherNet/IP [EIP] IOMs: 1738-IT2IM12


Block(s)
Description Cold Junction Over Range Flag
Data Type BOOLEAN
Range l 1: ON
l 0: OFF
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter turns to ON when the Thermocouple module reports an over
range condition for the Cold Junction Temperature.

5.167 CJSTATUS [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1732E-IT4IM12R


Block(s)
Description Cold Junction temperature status
Data Type Enumeration
Range l 0. No Fault
l 1. Underrange
l 2. Overrange
l 3. No Thermistor Detected
Default No Fault
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related CJTEMP
Parameters
Remarks Based on the Cold Junction temperature value the Cold Junction Status will be set
appropriately. Cold Junction status with No Fault indicates a valid Cold Junction
temperature source.

- 516 -
Chapter 5 - Cxxxx Parameters

5.168 CJTACT

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Cold Junction Temperature Compensation. Specifies whether the Smart
Temperature Transmitter' s internal cold-junction temperature reference or an
externally provided cold-junction temperature reference is to be used.
Data Type Boolean
Range Off: External cold-junction temperature is active. On: Transmitter's internal cold-
junction temperature is active.
Default On
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related N/A
Parameters
Remarks This parameter is only exposed if ASSOCIOPTYP is STI-MV. We recommend that
you select the Internal Cold-Junction Temperature Compensation, since there is
no need to enter the reference temperature. If you choose the External Cold-
Junction Temperature Compensation, you must use the Smart Field
Communicator (SFC) to enter the cold junction temperature value in the
transmitter. Refer to the SFC User's Manual for configuration instructions.

5.169 CJTEMP

Specific to EtherNet/IP [EIP] IOMs: 1738-IT2IM12,1732E-IT4IM12R


Block(s)
Description Cold Junction Compensation Temperature ( °C)
Data Type INT 16
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Displays the cold junction temperature value from the device or attached
thermistors. CJTEMP = 10 x Cold Junction temperature (°C)

- 517 -
Chapter 5 - Cxxxx Parameters

5.170 CJ_BOTTOM

Specific to UAI
Block(s)

Description Bottom (DegC)


Data Type FLOAT64
Range

Default NaN
Config Load No
Active
Loadable

Access Lock View Only


Residence IOM Block
Related N/A
Parameters

Remarks This displays the Cold Junction temperature from the On Board Thermometer at the
Bottom of the Module..

5.171 CJ_TOP

Specific to Block UAI


(s)

Description Top (DegC)


Data Type FLOAT64
Range

Default NaN
Config Load No
Active Loadable

Access Lock View Only


Residence IOM Block
Related N/A
Parameters

Remarks This displays the Cold Junction temperature from the On Board Thermometer at the
Top of the Module.

- 518 -
Chapter 5 - Cxxxx Parameters

5.172 CJUNDERRANGE

Specific to EtherNet/IP [EIP] IOMs: 1738-IT2IM12


Block(s)
Description Cold Junction Under Range Flag
Data Type BOOLEAN
Range l 1: ON
l 0: OFF
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter turns to ON when the Thermocouple module reports an under
range condition for the Cold Junction Temperature.

5.173 CLEARGAINDELAY

Specific to Block(s) ProfitCtl


Description Clear Gain Delay
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

5.174 CLIENTCONNSTS[0..4]

Specific to Block(s) CEEC300


Description Client Connection Status
Data Type ENUM
Range None, Open, Timeout, Closed

- 519 -
Chapter 5 - Cxxxx Parameters

Default None
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related CLIENTIP[0..4], CLIENTNAME[0..4], RMSGRATEAVG[0..4], RMSGRATEMAX
Parameters [0..4]
Remarks Indicates the connection status of the EIM Client.

5.175 CLIENTIP[0..4]

Specific to Block CEEC300


(s)
Description Client IP
Data Type STRING
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related CLIENTNAME[0..4], CLIENTCONNSTS[0..4], RMSGRATEAVG[0..4],
Parameters RMSGRATEMAX[0..4]
Remarks Indicates the ip addr of the EIM Client

5.176 CLIENTNAME

Specific to Block CEEC300


(s)
Description Client Name
Data Type BLOCKID
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related CLIENTIP[0..4], CLIENTCONNSTATUS[0..4], RMSGRATEAVG[0..4],
Parameters RMSGRATEMAX[0..4]
Remarks Indicates the name of the EIM Client

- 520 -
Chapter 5 - Cxxxx Parameters

5.177 CLKADJUST

Specific to RM
Block(s)
Description Local clock adjustment
Data Type Enumeration
Range Standard (0) Daylight (1)
Default Standard (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks This parameter is not supported in this release.

5.178 CLKTIME

Specific to RM
Block(s)
Description Clock time, as reported by the Redundancy Module.
Data Type TIME
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 521 -
Chapter 5 - Cxxxx Parameters

5.179 CLKZONE

Specific to RM
Block(s)
Description Time zone
Data Type 16-Bit Unsigned Integer
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

5.180 CLOSEDLOOPRESP
For non-integrating processes (D[1] <> 0), this parameter is read only. Use the performance ratio,
PRFRATIO, to alter the speed of response.

Specific to PID-PL
Block(s)
Description Closed-Loop Response Time - The expected settling time (in minutes) for the
control loop. The settling time is the amount of time required to line out the
controller after a setpoint change or large disturbance. This is a user-entered value
for integrating processes, and a calculated value for non-integrating processes.
Data Type Float64
Range >0.1
Default 10
Config Yes
Load
Active No
Loadable

- 522 -
Chapter 5 - Cxxxx Parameters

Access Lock Supervisor


Residence CEE
Related CTLEQND[1..5]PRFRATIO
Parameters
Remarks CLOSEDLOOPRESP does not include process deadtime or the effective delay due
to inverse response dynamics. Add these to the CLOSEDLOOPRESP to obtain a
more accurate estimate of the closed-loop settling time. For non-integrating
processes, CLOSEDLOOPRESP is the product of the open loop response time,
OPENLOOPRESP, and the performance ratio, PRFRATIO. This parameter is
applicable only when CTLEQN is set to Profit Loop PKS, and is ignored in PID
control equations.

5.181 CLOSEFEEDBKTIME

Specific to Block VALVEDAMPER


(s)
Description Close Feedback Time
Data Type Float64
Range 0 - Max of Real Number
Default 0.0
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related TRKOPENFEEDBKTIME
Parameters
Remarks Time taken to receive CLOSE feedback (LTC) after CLOSE command
(CMDCLOSE) is issued

5.182 CLOSEIBV

Specific to Block(s) MAINIBV


Description Close command to IBV
Data Type Boolean
Range ON, OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CLOSEMAIN
Remarks This out put will be connected to Drive control of IBV.

- 523 -
Chapter 5 - Cxxxx Parameters

5.183 CLOSEMAIN

Specific to Block(s) MAINIBV


Description Close command to MAIN
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CLOSEIBV
Remarks This output will be connected to Drive control of MAIN valve.

5.184 CLOSEPULSEWIDTH

Specific to Block(s) VALVEDAMPER


Description Close Output Pulsewidth
Data Type Double
Range 0 to 60 seconds
Default 1
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters OPENPULSEWIDTH
Remarks Duration for which output should go high as signal for close comes.

5.185 CLOSESEQ

Specific to Block(s) MAINIBV


Description Close Sequence Command
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No

- 524 -
Chapter 5 - Cxxxx Parameters

Access Lock Program


Residence CEE
Related Parameters
Remarks

5.186 CLOSESEQALM.FL

Specific to Block(s) MAINIBV


Description Close SEQ Fail Alarm Flag
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CLOSESEQALM.PRCLOSESEQALM.SV
Remarks

5.187 CLOSESEQALM.PR

Specific to Block(s) MAINIBV


Description Close SEQ Fail Alarm Priority
Data Type Enumeration
Range NONE JOURNAL LOW HIGH URGENT
Default Low
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters CLOSESEQALM.FLCLOSESEQALM.SV
Remarks

- 525 -
Chapter 5 - Cxxxx Parameters

5.188 CLOSESEQALM.SV

Specific to Block(s) MAINIBV


Description Close SEQ Fail Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters CLOSESEQALM.FLCLOSESEQALM.PR
Remarks

5.189 CLOWREADAVGPPS

Specific to EHPM
Block(s)
Description This parameter shows the average parameters per second load during subscribed
display read operation. This is a low-priority read load (for example, HMIWeb
display).
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

- 526 -
Chapter 5 - Cxxxx Parameters

5.190 CLOWREADMAXPPS

Specific to EHPM
Block(s)
Description This parameter shows the maximum parameters per second load during
subscribed display read operation. This is a low-priority read load (for example,
HMIWeb display).
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

5.191 CLR_GD_C

Specific to Block(s) ProfitCtl


Description Color of CLR GD
Data Type ENUM
Range NA
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

5.192 CLROPREQFL

Specific to Block(s) DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Clear Requested Output Value (OPREQ) Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)

- 527 -
Chapter 5 - Cxxxx Parameters

Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters GOPREQ, OPREQ, OPTYPE.
Remarks

5.193 CLRQUEUEOPT

Specific to Block(s) UCM


Description Clear Arbitration Queue on Inactivation
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks
ATTENTION Though this parameter is specific to
UCM, this parameter can be exposed on the
faceplate of the CM and can be modified during
runtime. The default value of this parameter in CM
is ON (differs from UCM) but the behavior of this
parameter in CM is identical to UCM.

5.194 CLUSTERID

Specific to CEEFB, CEEC300, CEEACE, CEESIMC200E, CEEUOC


Block(s)
Description Unique Cluster ID for inter cluster peer-to-peer.
Data Type INT32
Range 0 - 255
Default 1
Config Load Yes
Active -
Loadable

- 528 -
Chapter 5 - Cxxxx Parameters

Access Lock Application Developer


Residence CEE
Related ACTID
Parameters
Remarks This number is used in the generation of Activity IDs. The Cluster ID is populated
in the Batch Preference configuration form.

Specific to Block(s) UOC


Description Cluster ID
Data Type INT32
Range ±2147483647
Default 1
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

5.195 CLXCONNSTS

Specific to Block(s) PB_EIP, CEEC300, CEEUOC


Description Connection Status
Data Type ENUM
Range NoState Initialized OpenPending Open ClosedPending
Default NoState

Config Load No

Active Loadable No
Access Lock ViewOnly
Residence No Load

Related Parameters -
Remarks Class 3 EIP Connection status from EIM to Control Logix.

5.196 CLXCONNSTS[0-3]

Specific to CEEFB
Block(s)
Description Connection Status — Displays the status of the connection between the C300
and the ControlLogix PLC.
Data Type ENUM
Range l 0 : NoState

- 529 -
Chapter 5 - Cxxxx Parameters

l 1 : Initialized
l 2 : OpenPending
l 3: Open
l 4 : ClosePending
Default NoState
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks

5.197 CLX_GATEWAY

Specific to UDT Block


Block(s)
Description Control Logix Gateway — This parameter contains the name of the ControlLogix
gateway that has been created. It represents an equivalent ControlLogix PLC.
Data Type BlockID
Range 32 characters

Default
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related None
Parameters
Remarks After you configure this parameter, the IPADDRESS and SLOT information flows
down to the individual User Defined Tags that are assigned in a gateway block.

- 530 -
Chapter 5 - Cxxxx Parameters

5.198 CLX_TAG

Specific to UDT Block


Block(s)
Description Control Logix Tag — Represents the name of the tag created in the PLC , which this
particular block is attempting to read from/write to.
Data Type String
Range

Default
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks

5.199 CMACTIVEFL

Specific to STARTSIGNAL
Block(s)
Description Control Module (CM) Active Flag - Holds True for the first execution cycle following
inactivation and then activation of the parent CM.
Data Type Boolean
Range True False
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RESTART
Parameters
Remarks

- 531 -
Chapter 5 - Cxxxx Parameters

5.200 CMAXTEMP

Specific to Block(s) C300, PGM and FIM4 FBs


Description Maximum module temperature °C measured by three different
thermometers.
Data Type Float64
Range -55.00 °C to +120.00 °C
Default 0.00 °C
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM
Related CMINTEMPCTEMP
Parameters
Remarks Displays maximum temperature the module has reached till the present
time.

5.201 CMDATTR

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Totalizer Command Attribute - Specifies who may store to the COMMAND
parameter, (that is, the operator, another function block, or user program).
Data Type Enumeration CMDATTR
Range Operator (0) OtherFB (1)
Default Operator (0)
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related COMMAND
Parameters
Remarks CMDATTR regulates the COMMAND parameter only. Using STARTFL, STOPFL, or
RESETFL, other Function Blocks or Store may independently Start, Stop or Reset
Totalizer even if CMDATTR is Operator.

- 532 -
Chapter 5 - Cxxxx Parameters

5.202 CMDCLOSE

Specific to Block(s) VALVEDAMPER


Description Issue Close Command
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters OPGOPOPFINALOPREQMTT WTS ERRCODEOI[0..2]PI[0..2]
Remarks Command to close the valve.

5.203 CMDDISALM.FL

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Command Disagree Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CMDDISALM.PR, CMDDISALM.SV, CMDDISALM.TM[0..2], GOP, GPV,
Parameters HIALMHENABLEOP, OPFINAL, PV DEVCTL Only: NUMDINPUTS, NUMDOUTS
Remarks DEVCTL Only: Illegal if NUMDINPUTS = 0 or NUMDOUTS = 0. Illegal if all
CMDDISALM.TM[0..2] = 0.

5.204 CMDDISALM.PR

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Command Disagree Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None

- 533 -
Chapter 5 - Cxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related CMDDISALM.FL, CMDDISALM.SV, CMDDISALM.TM[0..2], DEVCTL Only:
Parameters NUMDINPUTS, NUMDOUTS.
Remarks DEVCTL Only: Illegal if NUMDINPUTS = 0 or NUMDOUTS = 0. Illegal if
CMDDISALM.TM[0..2]= 0.

5.205 CMDDISALM.SV

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Command Disagree Alarm Severity
Data Type 16-Bit Integer
Range 0 to 255
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related CMDDISALM.FL, CMDDISALM.PR, CMDDISALM.TM[0..2], DEVCTL Only:
Parameters NUMDINPUTS, NUMDOUTS.
Remarks DEVCTL Only: Illegal if NUMDINPUTS = 0 or NUMDOUTS = 0. Illegal if all
CMDDISALM.TM[0..2] = 0.

5.206 CMDDISALM.TM[0..2]

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Command Disagree Feedback Times - The wait time for each state, before
Command Disagree Alarm becomes active.
Data Type 32-Bit Integer
Range 0 to 1000 seconds
Default 0 seconds
Config Load Yes
Active No
Loadable

- 534 -
Chapter 5 - Cxxxx Parameters

Access Lock Engineer


Residence CEE
Related CMDDISALM.FL, CMDDISALM.PR, CMDDISALM.SV, CMDDISALM.TM[0..2],
Parameters DEVCTL Only: NUMDINPUTS, NUMDOUTS, NUMSTATES.

Remarks Function block must be inactive to change to or from 0. DEVCTL Only: Illegal if
NUMDINPUTS = 0 or NUMDOUTS = 0. DEVCTL Only: CMDDISALM.TM[2] is illegal if
NUMSTATES = 2.

5.207 CMDEXEC

Specific to SCM
Block(s)
Description Sequential Control Module (SCM) Execution Command
Data Type Enumeration CSCOEXECC
Range None (0) Resume (1) CheckConfig (2)
Default None (0)
Config Load No

Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related COMMAND
Parameters
Remarks Used internally by the SCM for execution stop and restart related commands. The
COMMAND parameter is the primary user interface to the SCM.

5.208 CMDFALALM.FL

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Command Fail Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No

Active No
Loadable

- 535 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related CMDFALALM.PR, CMDFALALM.SV, CMDFALALM.TM[0..2], GOP, GPV, HIALM, OP,
Parameters OPFINAL, PV. DEVCTL Only: NUMDINPUTS, NUMDOUTS
Remarks DEVCTL Only: Illegal if NUMDINPUTS = 0 or NUMDOUTS = 0. Illegal if all
CMDFALALM.TM[0..2] = 0.

5.209 CMDFALALM.PR

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Command Fail Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related CMDFALALM.FL, CMDFALALM.SV, CMDFALALM.TM[0..2], DEVCTL Only:
Parameters NUMDINPUTS, NUMDOUTS.
Remarks DEVCTL Only: Illegal if NUMDINPUTS = 0 or NUMDOUTS = 0. Illegal if all
CMDFALALM.TM[0..2] = 0.

5.210 CMDFALALM.SV

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Command Fail Alarm Severity
Data Type 16-Bit Integer
Range 0 to 255
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related CMDFALALM.FL, CMDFALALM.PR, CMDFALALM.TM[0..2], DEVCTL Only:
Parameters NUMDINPUTS, NUMDOUTS.
Remarks DEVCTL Only: Illegal if NUMDINPUTS = 0 or NUMDOUTS = 0. Illegal if all
CMDFALALM.TM[0..2] = 0.

- 536 -
Chapter 5 - Cxxxx Parameters

5.211 CMDFALALM.TM[0..2]

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Command Fail Alarm Time-outs - The wait time for each state before Command Fail
Alarm becomes active.
Data Type 32-Bit Integer
Range 0 to 1000 seconds
Default 0 seconds
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CMDDISALM.TM[0..2], CMDFALALM.FL, CMDFALALM.PR, CMDFALALM.SV,
Parameters DEVCTL Only: NUMDINPUTS, NUMDOUTS, NUMSTATES.
Remarks Function block must be inactive to change to or from 0. Must be less-than
respective CMDDISALM.TM[0..2]. DEVCTL Only: Illegal if NUMDINPUTS = 0 or
NUMDOUTS = 0. DEVCTL Only: CMDFALALM.TM[2] is illegal if NUMSTATES =2.

5.212 CMDFPVALUE

Specific to Block JAGXCHAN


(s)
Description Floating Point Value
Data Type FLOAT32
Range N/A
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related COMMAND, CMDREADY
Parameters
Remarks This value is written by the control strategy or user for commands requiring a
floating point value.

- 537 -
Chapter 5 - Cxxxx Parameters

5.213 CMDOPEN

Specific to Block(s) VALVEDAMPER


Description Command Open
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters GOPOPOPFINALOI[0..2]OPREQPI[0..2]MTTERRCODE WTS
Remarks Command to open the valve.

5.214 CMDREADY

Specific to JAGXCHAN
Block(s)
Description Command Interface Ready Flag
Data Type Boolean
Range Off(0) Command Interface Not Ready
On(1) Command Interface Ready
Default On
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related COMMAND, CMDFPVALUE
Parameters
Remarks Indicates to control strategies or the user the state of the command interface. If the
flag is on the interface is idle and a command can be issued.

5.215 CMDREQIN

Specific to Block(s) SCM, RCM, UCM, CM


Description Command input
Data Type STRUCT
Range

- 538 -
Chapter 5 - Cxxxx Parameters

Default
Config Load No
Active Loadable No
Access Lock OtherFb
Residence
Related Parameters
Remarks For internal use only.

5.216 CMDRUN

Specific to Block(s) HTMOTOR, LTMOTOR


Description Issue Run Command
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CMDSTOP
Remarks Digital Output of the block to start the motor.

5.217 CMDSTOP

Specific to Block(s) HTMOTOR, LTMOTOR


Description Issue Stop Command
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CMDRUN
Remarks Digital Output of the block to stop the motor.

- 539 -
Chapter 5 - Cxxxx Parameters

5.218 CMINTEMP

Specific to Block C300, PGM and FIM4 FB


(s)
Description Minimum module temperature in degrees C measured by three different
thermometers.
Data Type Float64
Range -55.00 °C to +120.00 °C
Default 0.00 °C
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, Series C FIM, PGM
Related CMAXTEMPCTEMP
Parameters
Remarks Displays minimum temperature the module has reached till the present time.

5.219 CMLOADFL

Specific to STARTSIGNAL
Block(s)
Description Control Module (CM) Load Flag - Holds True for the first execution cycle
following a load of the parent CM.
Data Type Boolean
Range True False
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RESTART
Parameters
Remarks

- 540 -
Chapter 5 - Cxxxx Parameters

5.220 CMODULES

Specific to Block(s) Cabinets


Description It defines the third column of the cabinet to configure the IO modules to the
cabinet.
Data Type String
Range —
Default —
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks

5.221 CNETCONNECT

Specific to ACE, SIM_C200


Block(s)
Description ControlNet Connection - Indicates if the ACE or SIM_C200 (for C200 simulation)
node is directly connected to ControlNet network.
Data Type Boolean
Range Off - Not Connected On - Connected
Default Off - Not Connected
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence SR
Related ACEMACADDR SIMC200MACID
Parameters
Remarks

- 541 -
Chapter 5 - Cxxxx Parameters

5.222 CNTDNFL

Specific to Block Up / Down Counter Block


(s)
Description Count Down Flag
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related CNTLVLFL, PAUSEFL, RESETFL, LOADFL, INCLAMPOPT
Parameters
Remarks This parameter decrements the counter value only when the CNTDNFL is set
to “TRUE”.

5.223 CNTEQN

Specific to Up / Down Counter Block


Block(s)
Description This parameter is used to display the counter equation.
Data Type Enumeration
Range 0 = Eq. A 1 = Eq. B 2 = Eq. C 3 = Eq. D 4 = Eq. E 5 = Eq. F 6 = Eq. G 7 = Eq. H
Default Eq. A
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related QDFL, QUFL, CARRYDNFL, CARRYUPFL
Parameters
Remarks This parameter specifies the counting algorithm to use. For detailed information
about the counter algorithm refer to Control Builder Components Theory Guide.

- 542 -
Chapter 5 - Cxxxx Parameters

5.224 CNTLVLFL

Specific to Up / Down Counter Block


Block(s)
Description Count on Level Flag
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related CNTUPFL, CNTDNFL
Parameters
Remarks This parameter displays the type of algorithm that must be used for evaluating the
count flags. Edge triggered algorithm is used by default.

5.225 CNTUPFL

Specific to Block Up / Down Counter Block


(s)
Description Count Up Flag
Data Type Boolean
Range FALSE TRUE
Default FALSE
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related CNTLVLFL, PAUSEFL, RESETFL, LOADFL, INCLAMPOPT
Parameters
Remarks This parameter increments the counter value only when the CNTUPFL is set
to “TRUE”.

- 543 -
Chapter 5 - Cxxxx Parameters

5.226 CNUMSRCCONN[1..10]

Specific to Tranistion Block


Block(s)
Description Number of Source Connections for Condition expression. Represents number of
source references in the expression of Condition i, where i is the parameter index
from 1..10.
Data Type Integer32
Range 0 to 6
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence ACE, C200, SIM_C200
Related CPCODESIZE[1..10]
Parameters
Remarks

5.227 COLLCOUNT

Specific to Block(s) TCMI


Description Collisions Count
Data Type UINT32
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 544 -
Chapter 5 - Cxxxx Parameters

5.228 COMBOPOINT

Specific to CEE Control Module


Blocks
Description Extend TPS Point
Data Type Enumeration
Range No
Yes
Default No
Config. Yes
Load
Active Yes
Loadable
Access AppDevOnly
Lock
Residence SR
Related
Parameters
Remarks COMBOPOINT is used on Control Modules which hold basic blocks deployed to
emulate TDC2000 Hiway algorithms. Control Modules that are used for ordinary
CEE configurations have COMBOPOINT configured as NO. Control Modules that is
used for emulation under an EHB have COMBOPOINT configured as YES. This
configuration notifies the ESV-T or ES-T above the CEE to resolve names of
requested parameters by communicating to the HG point in the EHB first, and
then, if not found, to the CM in the CEE. Therefore, the parameters of the HG point
and the emulation CM can be viewed from the Server under the same tag name.
For further information on Combo Points and EHB, refer to Guidelines for Replacing
Hiway boxes with LCN-connected C300 emulations Guide.

5.229 COMMAND

Specific to SCM, UCM, RCM


Block(s)
Description Sequential Control Module (SCM) Command - The SCM, UCM, or RCM is
commanded by stores to this parameter.
Data Type Enumeration CSCOCOMMAND
Range None (0) Inactive (1) Start (2) Reset (3) Interrupt (4) Restart (5) Hold (6) Stop (7)
Abort (8) Resume (9) Active (10) Cancel (11) - Only available in Experion R400 or
later.
Default None (0)
Config No
Load
Active No
Loadable

- 545 -
Chapter 5 - Cxxxx Parameters

Access Lock Range Access lock

INACTIVE/ACTIVE Supervisor
HOLD Refer CONTROLLOCK
ABORT Refer ABORTLOCK
Other values Operator
Residence CEE
Related ABORTLOCK, CONTCUTOUT, MODE, MODEATTR, SSTEPLOCK, STATE.
Parameters
Remarks Ability to change COMMAND depends on the current value of related variables
(listed above). See the SCM/RCM State/Command Interaction diagram in the
Sequential Control User's Guide for more details. Note: If the MODE is “SingleStep” or
“SafeStep” when the STATE is “Inactive” then the MODE will be automatically set to
“Auto” when activation is initiated by setting the COMMAND as “Active”. This is
applicable only for SCM and RCM.

Double commanding of SCMs/RCMs by different actors at the same time, should be avoided, as it
may result in side effects, that are difficult to diagnose.

Specific to Master Recipe


Block(s)
Description Master Recipe Command - The Master Recipe is commanded by stores to this
parameter.
Data Type Enumeration CSCOCOMMAND
Range None (0) Inactive (1) Active (10)
Default None (0)
Config Load No
Active No
Loadable
Access Lock Range Access lock

INACTIVE/ACTIVE Supervisor
Residence CEE
Related ABORTLOCK, CONTCUTOUT, CONTROLLOCK, MODE, MODEATTR, SSTEPLOCK,
Parameters STATE.
Remarks Ability to change COMMAND depends on the current value of related variables
(listed in the previous row).

Specific to Timer
Block(s)
Description Timer Command - Used by the operator to control the operation of the Timer
function block.
Data Type Enumeration TIMERCOMMAND
Range None (0) Reset (1) Stop (2) Restart (3) Start (4)
Default None (0)
Config Load No
Active No
Loadable

- 546 -
Chapter 5 - Cxxxx Parameters

Access Lock Operator


Residence CEE
Related STARTFL, STATE, STOPFL.
Parameters
Remarks Start: Timer is started; PV starts incrementing. Stop: Timer is stopped; PV freezes.
Reset: Timer is reset; PV is set to 0, and RV is set to SP. Restart: Timer continues
from the point it last stopped.

Specific to Block(s) Totalizer, Pulse Input Totalizer


Description Totalizer Command - Allows the operator to control the operation of a
Totalizer.
Data Type Enumeration COMMAND
Range None (0) No effect on Totalizer.
Start (1): Starts the Totalizer.
Stop (2): Stops the Totalizer
Reset (3): Resets the Totalizer to RESETVAL.
Default None (0)
Config Load No
Active Loadable No
Residence CEE
Related CLRQUEUEOPTCMACTIVEFLCMAXTEMP, CMDATTR
Parameters
Remarks

Specific to HAICHANNEL (PM I/O); AICHANNEL


Block(s) (Series C I/O)
Description Command. Lets the user initiate a database transfer between the STI point and the
Smart Transmitter, and calibrate the transmitter.
Data Type Enumeration
Range None (0): The STI point has not issued a
command.
DnLoadDb (1): Loads the transmitter parameters from
the STI point database into the
transmitter.
UpLoadDb (2): Loads the transmitter database from the
transmitter into the STI point.
Set_LRV (3): Sets the Lower Range Value.
Set_URV (4): Sets the Upper Range Value.

Cor_LRV (5): Corrects the Lower Range Value.


Cor_URV (6): Corrects the Upper Range Value.
Cor_Inpt (7): Corrects the zero point for the Process
Variable (PV).
RstCor (8): Sets all input calibration parameters to
the default values.
Calibrate (9):. Refer to the Field Instrument's
documentation.

- 547 -
Chapter 5 - Cxxxx Parameters

ResetErr (10): Refer to the Field Instrument's


documentation.
Restart (11): Refer to the Field Instrument's
documentation.
Shutdown (12): Refer to the Field Instrument's
documentation.
Default None (0)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOM
Related
Parameters
Remarks This parameter is only exposed, if ASSOCIOPTYP is STI-MV. IF DECONF is PV or PV_
SV, the only COMMAND supported is DnLoadDB. During an upload operation,
previously unseen data is read from the transmitter database and stored in the STI
database. If this data is not desired, using the checkpoint restore or load IDF
functions can restore the data.

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description I/O Link Command. Lets users initiate selected commands for the associated I/O
link.
Data Type Enumeration
Range NONE (0): No command.
SELECT_CH_A (1): Selects Channel A.
SELECT_CH_B (2): Selects Channel B.
RESET_ERRORS (3): Reset I/O Link errors.
ENB_PERSWAP (4): Enable Periodic Channel Swap.
DIS_PERSWAP (5): Disable Periodic Channel Swap.
Default NONE (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence IOLINK
Related
Parameters
Remarks These commands affect the entire associated I/O link, since they are broadcast to
all the input/output processors (IOPs). Note that this differs from the IOMCMD
parameter, which affects only one particular IOP.

- 548 -
Chapter 5 - Cxxxx Parameters

Specific to JAGXCHAN
Block(s)
Description Scale Command
Data Type Enumeration
Range 0-163 Refer to the Mettler Toledo QiMPACT Controller
Messaging Specification, section 10.2.2.1.
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CMDFPVALUE, CMDREADY
Parameters
Remarks This value is written by the control strategy or user to issue a scale command.

5.230 COMMAND[1..200]

Specific to QIPACCHAN
Block
Description Command Number
Data Type Enumeration
Range 0 None
1 Start Material Transfer
2 Start Material Transfer with Gross
Weight Target. Only valid for a scale.
3 Start Hand Add
4 Acknowledge Material Transfer or Hand
Add Complete
5 Abort Material Transfer
6 Reset Slow Step Timer
7 Start Manual Mode
8 Turn on FCE in Manual Mode
9 Turn on FCE in Manual Mode
10 Restart Auto Mode
11 Complete Feed in Manual Mode
12 Master Reset - Instrument Channel
13 Report Last Status
14 Master Reset - Cluster
15 Validate Aggregate Secondary Feeds
99 Validate Data Integrity

- 549 -
Chapter 5 - Cxxxx Parameters

Default 0 - None
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MATERIALPATH[1..200], COMMANDSTATS[1..200], MXFERSTATUS[1..200],
Parameters MXFERSTATQ[1..200], OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200],
POWERFAIL[1..200], DELIVEREDWGT[1..200], TARGETERROR[1..200],
AVGFLOWRATE[1..200], AVGSPILL[1..200]
Remarks This is the value entered when the material transfer was initiated for the
designated channel [1-200] in the QiMPACT cluster.

5.231 COMMANDACK[1..4]

Specific to JAGXCHAN
Block(s)
Description Command Acknowledge
Data Type INT
Range 0 Default

1 Values Rotate 1, 2 ,3 to acknowledge that


the JX has recognized
2 And processed a new non-Null
command.
3
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bits 6 and 7 of the FPIndicator byte in the floating point input
assembly for the designated scale slot [1..4].

- 550 -
Chapter 5 - Cxxxx Parameters

5.232 COMMANDSTATS[1..200]

Specific to QIPACCHAN
Block
Description Command Status from Q.iMPACT
Data Type Enumeration
Range 0-5 SUCCESS
6 NOT COMPLETE
7 - 27, 30, 33 - 34 ERROR
28 - 29, 33 - 34 WARNING
* See Mettler Toledo QiMPACT Controller Messaging document for details.
Default 0 - Success
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MATERIALPATH[1..200], COMMAND, MXFERSTATUS[1..200], MXFERSTATQ[1..200],
Parameters OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200], POWERFAIL[1..200],
DELIVEREDWGT[1..200], AVGFLOWRATE[1..200], AVGSPILL[1..200]
Remarks Status of the last command initiated for the designated channel [1-200] in the
QiMPACT cluster.

5.233 COMMERROR[1..24]

Specific to Block QIPACTERM


Description Communication Error (within QiMPACT Cluster)
Data Type Boolean
Range Off(0) OK
On(1) Error
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 6 of the Status 2 word in the input assembly for the
designated position [1-24].

- 551 -
Chapter 5 - Cxxxx Parameters

5.234 COMMERROR[1..200]

Specific to QIPACCHAN
Block
Description Communication Error (within QiMPACT Cluster)
Data Type Boolean
Range Off(0) OK
On(1) Error
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 6 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

5.235 COMMFAILFL

Specific to AOCHANNEL, HAOCHANNEL, DOCHANNEL (PM I/O); AOCHANNEL, DOCHANNEL


Block(s) (Series C I/O)
Description Communications Failure. Notification whether or not an error occurred while
reading OP data from the channel - PWM channel for DOCHANNEL.
Data Type Boolean
Range Off (0) The OP data for the channel was successfully
read.
On (1) Error occurred upon reading the OP data from
the channel - PWM channel for DOCHANNEL.

Default Off (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks DOCHANNEL: This parameter is only valid for PWM types.

- 552 -
Chapter 5 - Cxxxx Parameters

5.236 COMMFAULT

Specific to Block(s) Chassis HART AI IOM, HART AO IOM


Description Communication Fault - Indicates a communication failure to the IO block
Data Type Boolean
Range Normal (0) Failure (1)
Default Normal (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.237 COMMOK

Specific to Block(s) EIM


Description Communication Ok
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Shows communication status between DSIN and DSMAP

5.238 COMMSTATUS

Specific to Block(s) QIPACCHAN


Description Communications Status
Data Type Enumeration
Range 0 - OK 1 - ERROR
Default OK
Config Load No
Active Loadable No

- 553 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters None
Remarks

5.239 COMMTHRESHOLD

Specific to Chassis HART AI IOM, HART AO IOM


Block(s)
Description Communication Failure Threshold - A threshold value that can be set to trigger
an alarm for a HART device.
Data Type 32-Bit Integer
Range 100 to 65535
Default 100
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks An alarm is generated when the number of communication failures exceeds the
threshold value.

5.240 COMPARBITRATIONSTS

Specific to RCM
Block(s)
Description Composite Arbitration Status
Data Type Enumeration
Range 0 NONE
1 ACQUIRING
2 ACQUIRED
3 RELEASING
4 ERROR
5 WARNING
Default NONE
Config Load No
Active No
Loadable

- 554 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks Displays the composite status derived from all the active threads that have PHASE
blocks. This status is an aggregation of the individual statuses of the connection
between a PHASE block and its resource.

5.241 COMPHILM

Specific to Block FLOWCOMP


(s)
Description Compensation Term High Limit - Defines the upper limit of the Compensation
Term (COMPTERM).
Data Type 32-Bit Real Number
Range COMPLOLM to 10.0
Default 1.25
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks

5.242 COMPELETED

Specific to Phase
Block(s)
Description Phase fully completed
Data Type Boolean
Range True, False
Default N/A
Config Load NO
Active No
Loadable

- 555 -
Chapter 5 - Cxxxx Parameters

Access ViewOnly
Lock
Residence CEE
Related MODE,
Parameters
Command,
STATE.
Remarks During normal execution in MODE=AUTO it will be ON only if the block has reached
STATE=Active or ActiveComplt respectively. That means this parameter indicates if all
block processing has been finished. This is regardless, whether the block controls a
child or not and regardless through what terminal state the child has allowed the
completion. COMPLETED will not become ON , if the processing of the block was
cancelled during mode SINGLESTEP by a CANCEL command.

5.243 COMPLOLM

Specific to Block FLOWCOMP


(s)
Description Compensation Term Low Limit - Defines the low limit of the Compensation
Term (COMPTERM).
Data Type 32-Bit Real Number
Range 0.0 to COMPHILM
Default 0.80
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks

5.244 COMPNVSCMD

Specific to IOLIM, Secondary IOLIM, C300 IOLINK


Block(s)
Description Compact Non-Volatile Storage.
Data Type Boolean
Range Off (0): The command is not active. On (1): The command is active
Default Off
Config No
Load
Active No
Loadable

- 556 -
Chapter 5 - Cxxxx Parameters

Access Lock Engineer


Residence IOLIM, C300 IOLINK
Related ENCMDS
Parameters
Remarks Pressing the button will compact the IOLIM's configuration. The ‘Compact Non-
Volatile Storage’ button is located on the Main tab of the IOLIM configuration form
and the Memory Statistics tab of the IOLINK and C300 IOLINK configuration form.
The button is enabled only when Enable IOLIM Commands (ENCMDS) is set to ON.

5.245 COMPOSITEKEYSW

Specific to Block(s) TCMI


Description Composite Keyswitch
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 557 -
Chapter 5 - Cxxxx Parameters

5.246 COMPOSITEPHASESTS

Specific to RCM, UCM, MR


Block(s)
Description Composite Phase State
Data Type Enumeration
Range 0 Loading
1 Loaded
2 Inactive
3 Validated
4 Running
5 Complete
6 Checking
7 Idle
8 interrupting
9 Interrupted
10 Restarting
11 Restarted
12 Holding
13 Held
14 Stopping
15 Stopped
16 Aborting
17 Aborted
18 CommErr
Default NONE
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Displays the composite state of children. The most serious state of the active
phases and steps. Note: This parameter is disabled for MR block.

- 558 -
Chapter 5 - Cxxxx Parameters

5.247 COMPTERM

Specific to FLOWCOMP
Block(s)
Description Compensation Term - This term is calculated differently for each of five flow
compensation equations, A through E.
Data Type 32-Bit Real Number
Range NaN or COMPLOLM to COMPHILM
Default 1.00
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, C300, ACE
Related COMPHILMCOMPLOLMPVCHAR
Parameters
Remarks

5.248 COMPUTEARW

Specific to All Regulatory Control Blocks


Block(s)
Description Compute Anti-Rest Windup (ARW) - Indicates that the windup status has to be
recomputed.
Data Type Boolean
Range (0) False (1) True
Default False
Config No
Load
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks CAB programs need to set this flag to TRUE, to initiate recomputation of windup
state. The flag is reset during windup computation. In ENHREGCALC block the flag
is not reset and remains set to TRUE. The flag cannot be set OFF by insertion
programs.

- 559 -
Chapter 5 - Cxxxx Parameters

5.249 CONFIGCODE

Specific to SCM, RCM


Block(s)
Description Configuration Code
Data Type Enumeration CSCOCONFIGCODE
Range None (0) UnknownError (1) - Unknown error - Call Honeywell InternalErr (2) -
Internal error - Call Honeywell. ILLOwnHandle (3) -
Handler,Step,Transition,Sync,Phase ILLHndlrHndl (4) - Handler NextHNotNull (5) -
Handler,Step,Transition,Sync,Phase ILLNNextTrns (6) - Step,Sync,Phase
ConnInvObjs (7) - Step,Transition,Sync,Phase InvNextType (8) -
Handler,Step,Transition,Sync,Phase NotImplNxTyp (9) - not used ILLExcConds (10)
- Step ILLConds (11) - Transition ILLOutputs (12) - Step IncObjects (13) - Handler,
SCM, RCM: Not all contained objects are okay ILLNOutputs (14) - Step ILLNConds
(15) - Transition ILLGateLogic (16) - Transition IncGateLogic (17) - Transition.
NullGateUsed (18) - Transition. OvlpGateInps (19) - Transition. SkipGateInps (20) -
Transition. ILLInvkTObj (21) - Handler ILLInvkTCnfg (22) - Handler ILLHndlrType
(23) - Handler. ILLHndlrSel (24) - Wrong Handler selected - Forced Disable. An
invalid selection or download occurred. The invalid handler is disabled. The
SCM/RCM is operational except for the invalid handler(s). HndlrInstMis (25) -
Handler,Step,Transition,Sync,Phase ILLExcCProp (26) - Step. IncOpProp (27) - Step
IncCondProp (28) - Transition. IncInvkTProp (29) - Handler IncPropagtn (30) -
Handler , Some objects not set to Edit. LostObjects (31) - Found lost objects (blocks
not belonging to any handler). This may hint to a database or Control Builder
problem. ActIgnored (32) - Step EditIgnored (33) -
Handler,Step,Transition,Sync,Phase TooFewCond (34) - Transition MaxTmLtMinT
(35) - Step NegativeTime (36) - Step EnbHdUnavail (37) - unused DisHdUnavail (38)
- unused EditNotPermt (39) - unused IntGateError (40) - transition. UserNullHnd
(41) - Handler UserEditHnd (42) - Handler. ILLObjAsHnd (43) - Invalid object
selected as Handler. Reported by SCM/RCM: The SCM/RCM is not operational. An
invalid selection or download occurred. NonEditLostO (44) - Found non-editable lost
objects. NonOptGatLog (45) - Transition RefusedConn (46) -
Handler,Step,Transition,Sync,Phase. ILLMultRef (47) - Sync. ConfHndErr (48) -
Failure in handler(s). Reported by SCM/RCM. One or more selected handlers have
an error or fatal error. Check the parameters CONFIGSTS, CONFIGDESC on all
handlers for more detailed information. The SCM/RCM is not operational. A START
command shall not be attempted. CnfHndSurWrn (49) - One or more Handler(s)
with Errors. One or more selected handlers have an error. One or more not selected
handlers have a fatal error. Check the parameters CONFIGSTS, CONFIGDESC on
all handlers for more detailed information. The SCM/RCM may be operational. The
SCM/RCM will fail, if a selected handler with error is executed. Handlers with fatal
errors shall not be selected. ConfHndWarn (50) - One or more Handler(s) with
Problems. Reported by SCM/RCM. One or more selected handlers have a severe
warning. One or more not selected handlers have an error. Check the parameters
CONFIGSTS, CONFIGDESC on all handlers for more detailed information. The
SCM/RCM is operational. If handlers with severe warnings are executed problems
may occur. Handlers with errors shall not be selected. ConfHndInfo (51) - Not All
Handlers Fully Operational. Reported by SCM/RCM. One or more selected handlers
have a warning. One or more not selected handlers have a severe warning. Check
the parameters CONFIGSTS, CONFIGDESC on all handlers for more detailed
information. The SCM/RCM is operational. If handlers with warnings are executed
problems may occur. ConfUnknCnfSt (52) - Unknown Handler Configuration
Status. Reported by SCM/RCM or handler: The SCM/RCM encountered an internal
problem and was unable to assess the status of all handlers. The SCM/RCM is not
functioning. Call Honeywell. ResrcMissing (53) - There is a problem with the
connections to the UCM IllegalConvErr (54) - Phase ImpConvInfo (55) - Phase
ATLoadInProg (56) - Alias Table load in progress, do not activate SCM/RCM while
Alias Table load is in progress ATLoadFailed (57) - Alias Table load failed Spare58

- 560 -
Chapter 5 - Cxxxx Parameters

(58) - unused Spare59 (59) - unused Spare60 (60) - unused Spare61 (61) - unused
PeerAlgOptConfigError(70) - RTable is full , change PEERALGOPT IllegalNullPhase
(74) - Phase. ExecOptWoScmRcm(75) - Phase UnsupportedFeature(76) - Phase
TermStateOptWoScmRcm(77) - Phase ScmRcmWoAcqOpt(78) - Phase
ScmRcmWoExecOpt(79) - Phase MissingCmdReqOutConn(80) - Phase
MissingValueRefConn(81) - Phase ConnNotEstablished(82) - Phase
EquipConnNotEstablished(83) - Phase RsrcConnNotEstablished(84) - Phase.
LonelyTermState(85) - Phase EquipmentIgnored(86) - Phase
EquipmentNotSupported(88) - Phase ResourceNotSupported(89) - Phase.
BlankNameRef(90) - USENAMEREF = USENAMEREF but connection for NAMEREF
could not be established. Likely a configuration error or not everything was loaded,
also reported by Phase
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CONFIGDESC, CONFIGSTS
Parameters
Remarks For the severity of the problem see CONFIGSTS. The individual enum values
indicate which blocks can generate this value. For more information see below for
the respective block types.

Specific to Phase
Block(s)
Description Configuration Code
Data Type Enumeration CSCOCONFIGCODE
Range None (0) - OK , no problems detected InternalErr (2) - Internal error - Call
Honeywell. ILLOwnHandle (3) - Created without valid own handle. Should not
happen. Check integrity of erdb. Reload. If persists call Honeywell. NextHNotNull (5)
- Next Type = None requires Null Handle. Should not happen. ILLNNextTrns (6) -
Number of next transitions out of range. Controller has configuration data not
supported by the firmware. Could hint to a software version mismatch between
erdb and CEE or database corruption. Should not happen. ConnInvObjs (7) -
Connected to objects of wrong type. User has made a configuration mistake. Phase
block cannot be connected to Phase or Step directly, if it is connected to more than
one block ( branch selection ). InvNextType (8) - Invalid specified Type of target
object. Control Builder should not allow this to happen. Somehow the phase block
was connected to an unsupported block. Reconfigure the connections at
NEXTCOMP. HndlrInstMis (25) - Connected to object of other Handler. Control
Builder should not permitt this to occur. An invalid selection or download occurred.
The block is not operational. Reconfigure and reload the SCM/RCM. EditIgnored
(33) - Info only , Edit attempt ignored , should not happen , if persists call
Honeywell. RefusedConn (46) - Next Object refused connection. Result of a
configuration error. Check sequence topology. IllegalConvErr(54) - One or more
problems exist with data types used in formula or report parameters. Check
consistency of data types between phase block parameters and external
references. Correct configuration and reload. ImpConvInfo(55) - Info only , one or
more formula or report parameter references will cause an implicit type conversion
from one data type to another type. Although this is a supported configuration ,

- 561 -
Chapter 5 - Cxxxx Parameters

undesired effects may occur with some values due to the different characteristics of
the data types. It is the responsibility of the engineer to ensure, that all possible
runtime values will be processed as intended. IllegalNullPhase(74) - All resource
and execution options must be OFF for Null-Phases. ExecOptWoScmRcm(75) -
EXECUTEOPT = ON is not supported for the configured/selected equipment.
UnsupportedFeature(76) - The phase is not supported in this handler type for
RCMs UnsupportedFeature(76) - Data block does not support Value References.
TermStateOptWoScmRcm(77) - Info only , TERMSTATEOPT = ON will be ignored for
non-executable equipment like CMs/UCMs or if no equipment is specified. Can be
avoided by changing TERMSTATEOPT = OFF. ScmRcmWoAcqOpt(78) - Warning only
, ACQUIREOPT = OFF and EXECUTEOPT = ON. The phase block shall execute the
equipment without acquiring it first. The recipe will only work, if the RCM acquires
the equipment by other means. If not an intended advanced configuration
indicates an engineering error leading to a runtime deadlock. ScmRcmWoExecOpt
(79) - Warning only , Phase shall acquire and release the equipment without
executing it. Although a supported configuration, very likely an engineering error.
MissingCmdReqOutConn(80) - should not happen , could indicate that system
resources are exhausted , if persists call Honeywell MissingValueRefConn(81) -
There is a problem with one or more value or parameter references in formula or
report parameters. Check configuration and make sure that everything is loaded
properly. ConnNotEstablished(82) - One or more connections could not be
established. Check alias, peer and OPC references. EquipConnNotEstablished(83) -
Connection to equipment is broken. Check configuration , firmware revisions and
the availability of all components involved in communication.
RsrcConnNotEstablished(84) - Connection to resource is broken. Check
configuration , firmware revisions and the availability of all components involved in
communication. LonelyTermState(85) - Information only , TERMSTATEOPT=ON and
EXECUTEOPT=OFF. The recipe may get blocked at this phase block , if the engineer
does not make sure, that all possible execution scenarios always bring the
SCM/RCM into a terminal state. EquipmentIgnored(86) - Information only , All
options are OFF , therefore the configured equipment configuration will be ignored.
Could be intentional. Could be a hint to engineering errors.
EquipmentNotSupported(88) - The configured resource does not have an internal
equipment interface required if EXECUTEOPT=ON or TERMSTATEOPT=ON. Only
SCMs and RCMs support that interface. Should not happen, if SCM or RCM is
specified. ResourceNotSupported(89) - The container specified as resource does
not provide the required internal resource interface. Check the configuration and
consistency of Control Builder and controller software versions. BlankNameRef(90)
- X_USENAMEREF = USENAMEREF but connection for X_NAMEREF could not be
established. Likely a configuration error or not everything was loaded.
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CONFIGDESC, CONFIGSTS
Parameters
Remarks For the severity of the problem see CONFIGSTS. If an undocumented code is shown
contact your Honeywell support channel.

- 562 -
Chapter 5 - Cxxxx Parameters

Specific to Sync
Block(s)
Description Configuration Code
Data Type Enumeration CSCOCONFIGCODE
Range None (0) - OK , no problems detected InternalErr (2) - Internal error - Call
Honeywell. ILLOwnHandle (3) - Created without valid own handle. Should not
happen. Check integrity of erdb. Reload. If persists call Honeywell. NextHNotNull (5)
- Next Type = None requires Null Handle. Should not happen. ILLNNextTrns (6) -
Number of next transitions out of range. Controller has configuration data not
supported by the firmware. Could hint to a software version mismatch between
erdb and CEE or database corruption. Should not happen. ConnInvObjs (7) -
Connected to objects of wrong type. User has made a configuration mistake. Refer
Sequential Control Users Guide for toplogy rules. InvNextType (8) - Invalid specified
Type of target object. Control Builder should not allow this to happen. Somehow the
phase block was connected to an unsupported block. Reconfigure the connections
at NEXTCOMP. HndlrInstMis (25) - Connected to object of other Handler. Control
Builder should not permitt this to occur. An invalid selection or download occurred.
The block is not operational. Reconfigure and reload the SCM/RCM. EditIgnored
(33) - Info only , Edit attempt ignored , should not happen , if persists call
Honeywell. RefusedConn (46) - Next Object refused connection. Should not
happen. Indicates a controller connection binding or communication problem.
ILLMultRef (47) - Same Target specified more than one time. User has made a
configuration mistake. 2 blocks shall not be connected to each user twice.
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CONFIGDESC, CONFIGSTS
Parameters
Remarks For the severity of the problem see CONFIGSTS.

Specific to Handler
Block(s)
Description Configuration Code
Data Type Enumeration CSCOCONFIGCODE
Range None (0) - OK , no problems detected UnknownError (1) - Unknown error - Call
Honeywell InternalErr (2) - Internal error - Call Honeywell. ILLOwnHandle (3) -
Created without valid own handle. Should not happen. Check integrity of erdb.
Reload. If persists call Honeywell. ILLHndlrHndl (4) - Handler should belong to
itself. Reported by Handler: Internal problem encountered by handler. Reload the
SCM/RCM, if the problem continues call Honeywell. NextHNotNull (5) - Next Type =
None requires Null Handle. Should not happen. InvNextType (8) - Invalid specified
Type of invoke object. Control Builder should not allow this to happen. Somehow
the handler was connected to an unsupported block. Use Chart->Set Invoke
Transition to attempt recovery. IncObjects (13) - Not all contained objects are okay.
One or more objects in this handler encountered an error. It is strongly
recommended to review and correct the configuration within this handler. Check
the parameters CONFIGSTS, CONFIGDESC on all objects in the handler for more

- 563 -
Chapter 5 - Cxxxx Parameters

detailed information. The handler may be operational or partially operational (for


example, some branches only). ILLInvkTObj (21) - Step and Phase is not supported
as Invoke Object for Handler. Control Builder should not permitt this to occur. Use
Chart->Set Invoke Transition to attempt recovery. ILLHndlrType (23) - Unexpected
Handler type. Internal problem encountered by handler. This handler is not
operational. Reload the SCM/RCM , if the problem persists call Honeywell.
HndlrInstMis (25) - Connected to Invoke Block of another Handler. Control Builder
should not permitt this to occur. An invalid selection or download occurred. The
block is not operational. Reconfigure and reload the SCM/RCM. IncInvkTProp (29) -
Invoke Trans not set to Edit. The handler does not know, which block is the first
block. Therefore nothing will happen if this handler is invoked. IncPropagtn (30) -
Some objects not set to Edit. Should not happen. EditIgnored (33) - Info only , Edit
attempt ignored , should not happen , if persists call Honeywell. UserNullHnd (41) -
User defined Null Handler. The SCM/RCM encountered an unsupported
configuration. The SCM/RCM may be operational, depending on the status of all
handlers. Reload the SCM/RCM. UserEditHnd (42) - User defined Edit Handler. The
SCM/RCM encountered an unsupported configuration. The SCM/RCM may be
operational, depending on the status of all handlers. Reload the SCM/RCM.
RefusedConn (46) - Next Object refused connection. Result of a configuration error.
Check sequence topology. ConfHndErr (48) - One or more objects in the handler
encountered a fatal error. Check the parameters CONFIGSTS, CONFIGDESC on all
objects in the handler for more detailed information. The handler is not operational.
CnfHndSurWrn (49) - One or more objects in the handler encountered an error.
Check the parameters CONFIGSTS, CONFIGDESC on all objects in the handler for
more detailed information. The handler may be operational. It is strongly
recommended to check and correct the configuration within this handler.
ConfHndWarn (50) - One or more objects in the handler encountered a severe
warning. Check the parameters CONFIGSTS, CONFIGDESC on all objects in the
handler for more detailed information. The handler is operational with limitations. It
is recommended to check and correct the configuration within this handler.
ConfHndInfo (51) One or more objects in the handler encountered a warning.
Check the parameters CONFIGSTS, CONFIGDESC on all objects in the handler for
more detailed information. The handler is operational .It may be advisable to review
the configuration within this handler. ConfUnknCnfSt (52) - Unknown Handler
Configuration Status. The SCM/RCM encountered an internal problem and was
unable to assess the configuration status. The SCM/RCM is not functioning. Call
Honeywell. UnsupportedFeature(76) - Interrupt Handler is not supported for RCMs
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CONFIGDESC, CONFIGSTS
Parameters
Remarks For the severity of the problem see CONFIGSTS.

Specific to Step
Block(s)
Description Configuration Code
Data Type Enumeration CSCOCONFIGCODE
Range None (0) - OK , no problems detected InternalErr (2) - Internal error - Call

- 564 -
Chapter 5 - Cxxxx Parameters

Honeywell. ILLOwnHandle (3) - Created without valid own handle. Should not
happen. Check integrity of erdb. Reload. If persists call Honeywell. NextHNotNull (5)
- Next Type = None requires Null Handle. Should not happen. ILLNNextTrns (6) -
Number of next transitions out of range. Controller has configuration data not
supported by the firmware. Could hint to a software version mismatch between erdb
and CEE or database corruption. Should not happen. ConnInvObjs (7) - Connected
to objects of wrong type. User has made a configuration mistake. Phase block
cannot be connected to Phase or Step directly, if it is connected to more than one
block ( branch selection ). InvNextType (8) - Invalid specified Type of target object.
Control Builder should not allow this to happen. Somehow the phase block was
connected to an unsupported block. Reconfigure the connections at NEXTCOMP.
ILLExcConds (10) - Not all exception conditions okay. Check the parameters
CONFIGSTS, CONFIGDESC on the conditions of this step for more detailed
information. ILLOutputs (12) - Not all outputs okay. Reported by Step: Check the
parameters CONFIGSTS, CONFIGDESC on the outputs of this step for more detailed
information. ILLNOutputs (14) - Number of outputs out of range. Control Builder
should not allow this to occur. HndlrInstMis (25) - Connected to object of other
Handler. Control Builder should not permitt this to occur. An invalid selection or
download occurred. The block is not operational. Reconfigure and reload the
SCM/RCM. ILLExcCProp (26) - Some Exception conditions not set to Edit. Should
not happen. IncOpProp (27) - Some outputs not set to Edit. Should not happen.
EditIgnored (33) - Info only , Edit attempt ignored , should not happen , if persists
call Honeywell. MaxTmLtMinT (35) - Max Time less than Min Time. The step is
operational, but the time configuration of the step is very likely not desired. If Step
time out alarming is configured, the step will always generate an alarm, when
executed. NegativeTime (36) - Negative time is not allowed. Correct the times
configured. The step is not operational RefusedConn (46) - Next Object refused
connection. Result of a configuration error. Check sequence topology.
UnsupportedFeature(76) - The step is not supported in this handler type for RCMs
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CONFIGDESC, CONFIGSTS
Parameters
Remarks For the severity of the problem see CONFIGSTS.

Specific to Transition
Block(s)
Description Configuration Code
Data Type Enumeration CSCOCONFIGCODE
Range None (0) - OK , no problems detected InternalErr (2) - Internal error - Call
Honeywell. ILLOwnHandle (3) - Created without valid own handle. Should not
happen. Check integrity of erdb. Reload. If persists call Honeywell. NextHNotNull (5)
- Next Type = None requires Null Handle. Should not happen. ConnInvObjs (7) -
Connected to objects of wrong type. User has made a configuration mistake.
Transition block cannot be connected to Transition directly. InvNextType (8) -
Invalid specified Type of target object. Control Builder should not allow this to
happen. Somehow the phase block was connected to an unsupported block.
Reconfigure the connections at NEXTCOMP. ILLConds (11) - Not all continuation
conditions okay. Check the parameters CONFIGSTS, CONFIGDESC on the

- 565 -
Chapter 5 - Cxxxx Parameters

conditions of this transition for more detailed information. ILLNConds (15) -


Number of conditions out of range. Control Builder should not allow this to happen.
ILLGateLogic (16) - Invalid Gate Logic configuration. Reported by transition: The
gate logic configuration does not allow the transition to function. IncGateLogic (17)
- Unused Gates should not be configured. The transition is operational. The
information reported may hint to some configuration issues. NullGateUsed (18) -
Gates without inputs are used. The transition is operational. The information
reported may hint to some configuration issues. OvlpGateInps (19) - Info only ,
Gates use overlapping inputs. SkipGateInps (20) - Info only, Some gate inputs are
skipped. HndlrInstMis (25) - Connected to object of other Handler. Control Builder
should not permitt this to occur. An invalid selection or download occurred. The
block is not operational. Reconfigure and reload the SCM/RCM. IncCondProp (28) -
Some Conditions not set to Edit. Should not happen. EditIgnored (33) - Info only ,
Edit attempt ignored , should not happen , if persists call Honeywell. TooFewCond
(34) - More inputs than allocated Conditions. Control Builder should not permitt this
to occur. IntGateError (40) - Internal Gate Logic Error - Call Honeywell. The
transition is not functioning. NonOptGatLog (45) - Non-Optimal Gate Logic. The
transition is operational. No action required by the user. Some users may desire to
optimize such configurations RefusedConn (46) - This Object refused connection.
Result of a configuration error. Check sequence topology.
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CONFIGDESC, CONFIGSTS
Parameters
Remarks For the severity of the problem see CONFIGSTS.

Specific to RegCalc, EnhRegCalc


Block(s)
Description Configuration Code
Data Type Enumeration RegCalcConfigCode
Range None Ok UnknownError ImplicitConv LossOfPrecsn UnexpctEnd UnexpctComma
ColonWoQMark FctNotMltArg ClosParenExp OperandExp MissingArg OperatorExp
ColonExp TypeMismatch TypeNotSupp SyntaxError ExprTooCmplx NotEPcodeMem
NotEDataStak UnsuppFeatur ExprTooLong DivideByZero UnknownToken
UnexpTokenOS UnknownFunc UnexpOCExpr2 UnexpOCExpr3 ZeroArgument
UnexpToken InvalResult InvalTokenTb IntegerExp DoubleExp MissedImpl
UnicodeConv ConstExprRem DuplExprRem ExtUse38 ExtUse39 ExtUse40 ExtUse41
ExtUse42 ExtUse43 ExtUse44 ExtUse45 ExtUse46 ExtUse47 ExtUse48 ExtUse49
ExtUse50 UnSupConType UnExpClsParn CantAssRVal UnExpArrOpen ArrClsExpect
ArrOpnExpect ArrIndxError StringExpect InvalidRefer TooManyConns
CantConvInpt FctExpParen AsgnOpLimExc AsgnOperMiss NullExprErr
StrRefNotSup CantFtchConn ComplexLHS NullExprWarn
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly

- 566 -
Chapter 5 - Cxxxx Parameters

Lock
Residence CEE
Related CONFIGDESC, CONFIGSTS
Parameters
Remarks For the severity of the problem see CONFIGSTS.

5.250 CONFIGCODE[1..8]

Specific to Auxcalc,Enhauxcalc
Block(s)
Description Configuration Code
Data Type Enumeration AUXCALCCONFIGCODE
Range None (0) Ok (1) UnknownError (2) ImplicitConv (3) LossOfPrecsn (4) UnexpctEnd (5)
UnexpctComm (6) ColonWoQMar (7) FctNotMltArg (8) ClosParenExp (9)
OperandExp (10) MissingArg (11) OperatorExp (12) ColonExp (13) TypeMismatch
(14) TypeNotSupp (15) SyntaxError (16) ExprTooCmplx (17) NotEPcodeMe (18)
NotEDataStak (19) UnsuppFeatur (20) ExprTooLong (21) DivideByZero (22)
UnknownToken (23) UnexpTokenO (24) UnknownFunc (25) UnexpOCExpr2 (26)
UnexpOCExpr3 (27) ZeroArgument (28) UnexpToken (29) InvalResult (30)
InvalTokenTb (31) IntegerExp (32) DoubleExp (33) MissedImpl (34) UnicodeConv
(35) ConstExprRem (36) DuplExprRem (37) ExtUse38 (38) ExtUse39 (39) ExtUse40
(40) ExtUse41 (41) ExtUse42 (42) ExtUse43 (43) ExtUse44 (44) ExtUse45 (45)
ExtUse46 (46) ExtUse47 (47) ExtUse48 (48) ExtUse49 (49) ExtUse50 (50)
UnSupConTyp (51) UnExpClsParn (52) CantAssRVal (53) UnExpArrOpen (54)
ArrClsExpect (55) ArrOpnExpect (56) ArrIndxError (57) StringExpect (58)
InvalidRefer (59) TooManyConn (60) CantConvInpt (61)
Default None (0)
Config No
Load
Active No
Loadable
Access Engineer/Application Developer
Lock
Residence CEE
Related
Parameters
Remarks

5.251 CONFIGDESC

Specific to Handler, RegCalc, SCM, RCM, Step, Transition, Phase


Block(s)
Description Configuration Descriptor
Data Type String
Range Maximum of 39 characters. See Remarks.

- 567 -
Chapter 5 - Cxxxx Parameters

Default None
Config No
Load
Access ViewOnly
Lock
Residence CEE
Related CONFIGCODE, CONFIGSTS
Parameters
Remarks For the severity of the problem see CONFIGSTS. For detailed information see
CONFIGCODE of respective block.

(0)NoError OK
(1)UnknownError Unknown error. Call Honeywell.
(2)ConfigInternalError Internal error. Call Honeywell.
(3)ConfigInvalidOwnHandle Created without valid own handle.
(4)ConfigInvalidHandlerHandle Handler should belong to itself.
Reported by Handler: Internal problem
encountered by handler. Reload the
SCM , if the problem persists call
Honeywell.
5)NextHandleNotNull Next Type = None requires Null
Handle.
(6)InvalidNumberOfNextTransitions Number of next transitions out of
range.
(7)ConnectedToInvalidObjects Connected to objects of wrong type.
(8)InvalidNextType Invalid specified Type of target object.
(9)NotImplementedNextType Sync Objects are not implemented yet.
(10)IncompleteExcConditions Not all exception conditions okay.
Reported by Step: Check the
parameters CONFIGSTS,
CONFIGDESC on the exception
conditions of this step for more
detailed information.
(11)IncompleteConditions Not all continuation conditions okay.
Reported by Transition: Check the
parameters CONFIGSTS,
CONFIGDESC on the conditions of this
transition for more detailed
information.
(12)IncompleteOutputs Not all outputs okay. Reported by Step:
Check the parameters CONFIGSTS,
CONFIGDESC on the outputs of this
step for more detailed information.
(13)IncompleteObjects Not all contained objects out okay.
Reported by handler: One or more
objects in this handler encountered an
error. It is strongly recommended to
review and correct the configuration
within this handler. Check the
parameters CONFIGSTS,
CONFIGDESC on all objects in the
handler for more detailed information.
The handler may be operational.

- 568 -
Chapter 5 - Cxxxx Parameters

(14)InvalidNumberOfOutputs Number of outputs out of range.

- 569 -
Chapter 5 - Cxxxx Parameters

(15)InvalidNumberOfConditions Number of conditions out of range.

- 570 -
Chapter 5 - Cxxxx Parameters

(16)InvalidGateLogic Invalid Gate Logic configuration.


Reported by transition: The gate logic
configuration does not allow the
transition to function.
(17)InconsistentGateLogic Unused Gates should not be
configured. Reported by transition: The
transition is operational. The
information reported may hint to some
configuration issues.
(18)ConfigNullGateUsed Gates without inputs are used.
Reported by transition: The transition
is operational. The information
reported may hint to some
configuration issues.
(19)OverlappingGateInputs Gates use overlapping inputs.
(20)SkippedGateInputs Some gate inputs are skipped.
(21)InvalidInvokeTransObject Could not access invoke Transition.
(22)InvalidInvokeTransConfiguration Foreign invoke Transition configured.
(23)InvalidHandlerType Unexpected Handler type. Reported by
Handler: Internal problem
encountered by handler. Reload the
SCM , if the problem persists call
Honeywell.
(24)InvalidHandlerSelected Wrong Handler selected - Forced
Disable. Reported by SCM: An invalid
selection or download occured. The
invalid handler is disabled. The SCM is
operational except for the invalid
handler(s).
(25)HandlerInstanceMismatch Connected to object of other Handler.
Reported by handler. An invalid
selection or download occured. The
handler is not operational.
Reconfigure and reload the SCM.
(26)IncompleteExcConditionPropagation Some Exc Conditions not set to Edit.
(27)IncompleteOutputPropagation Some outputs not set to Edit.
(28)IncompleteConditionPropagation Some Conditions not set to Edit.
(29)EditIncompleteInvokeTransPropagation Invoke Trans not set to Edit.

(30)IncompletePropagation Some objects not set to Edit.


(31)FoundLostObjects Found lost objects.
(32)ActivateAttemptIgnored Activate attempts ignored.
(33)EditAttemptIgnored Edit attempt ignored.
(34)ToFewConditionsAllocated More inputs than allocated Conditions.

(35)MaxTimeLessThanMinTime Max Time less than Min Time.


Reported by step: The step is
operational, but the time configuration
of the step is very likely not desired.
(36)NegativeTime Negative time is not allowed. Reported
by step: Correct the times configured.
The step is not operational.

- 571 -
Chapter 5 - Cxxxx Parameters

(37)EnabledHandlerBecameUnavailable Enabled Handler became unavailable.

- 572 -
Chapter 5 - Cxxxx Parameters

(38)DisabledHandlerBecameUnavailable Selected Handler became unavailable.

- 573 -
Chapter 5 - Cxxxx Parameters

(39)CurrentStateDoesNotPermitEdit Handler cannot be edited right now.

- 574 -
Chapter 5 - Cxxxx Parameters

(40)InternalErrorGateLogic Internal Gate Logic Error - Call


Honeywell. Reported by transition: The
transition is not functioning.
(41)UserDefinedNullHandler User defined Null Handler. Reported
by SCM: The SCM encountered an
unsupported configuration. The SCM
may be operational, depending on the
status of all handlers. Reload the SCM.
(42)UserDefinedEditHandler User defined Edit Handler. Reported by
SCM: The SCM encountered an
unsupported configuration. The SCM
may be operational, depending on the
status of all handlers. Reload the SCM.
(43)InvalidObjectSelectedAsHandler Invalid object selected as Handler.
Reported by SCM: The SCM is not
operational. An invalid selection or
download occured.
(44)FoundNonEditableLostObjects Found non-editable lost objects.
(45)ConfigNonoptimalGateLogic Non-Optimal Gate Logic. Reported by
transition: The transition is
operational. No action required by the
user. Some users may desire to
optimze such configurations.
(46)ConfigReferencedObjectRefusedConn Next Object refused connection.
(47)ConfigIllegalMultipleReference Same Target specified more than one
time.
(48)ConfigHandlerFail Failure in handler(s). Reported by
SCM. One or more selected handlers
have an error or fatal error. Check the
parameters CONFIGSTS,
CONFIGDESC on all handlers for more
detailed information. The SCM is not
operational. A START command shall
not be attempted. Reported by handler:
One or more objects in the handler
encountered a fatal error. Check the
parameters CONFIGSTS,
CONFIGDESC on all objects in the
handler for more detailed information.
The handler is not operational.
(49)ConfigHandlerSevereWarning One or more Handler(s) with Errors.
Reported by SCM. One or more
selected handlers have an error. One
or more not selected handlers have a
fatal error. Check the parameters
CONFIGSTS, CONFIGDESC on all
handlers for more detailed
information. The SCM may be
operational. The SCM will fail, if a
selected handler with error is
executed. Handlers with fatal errors
shall not be selected. Reported by
handler: One or more objects in the
handler encountered an error. Check
the parameters CONFIGSTS,
CONFIGDESC on all objects in the
handler for more detailed information.
The handler may be operational. It is

- 575 -
Chapter 5 - Cxxxx Parameters

strongly recommended to check and


correct the configuration within this
handler.
(50)ConfigHandlerWarning One or more Handler(s) with
Problems. Reported by SCM. One or
more selected handlers have a severe
warning. One or more not selected
handlers have an error. Check the
parameters CONFIGSTS,
CONFIGDESC on all handlers for more
detailed information. The SCM is
operational. If handlers with severe
warnings are executed problems may
occur. Handlers with errors shall not
be selected. Reported by handler: One
or more objects in the handler
encountered a severe warning. Check
the parameters CONFIGSTS,
CONFIGDESC on all objects in the
handler for more detailed information.
The handler is operational with
limitations. It is recommended to check
and correct the configuration within
this handler.
(51)ConfigHandlerInfo Not All Handlers Fully Operational.
Reported by SCM. One or more
selected handlers have a warning. One
or more not selected handlers have a
severe warning. Check the parameters
CONFIGSTS, CONFIGDESC on all
handlers for more detailed
information. The SCM is operational. If
handlers with warnings are executed
problems may occur. Reported by
handler: One or more objects in the
handler encountered a warning.
Check the parameters CONFIGSTS,
CONFIGDESC on all objects in the
handler for more detailed information.
The handler is operational .It may be
advisable to review the configuration
within this handler.
(52)ConfigUnknownConfigStatus Unknown Handler Config Status.
Reported by SCM or handler: The SCM
encountered an internal problem and
was unable to assess the status of all
handlers. The SCM is not functioning.
Call Honeywell.

5.252 CONFIGDESC[1..8]

Specific to Block(s) Auxcalc, Enhauxcalc


Description Configuration Descriptor
Data Type String
Range Maximum of 39 characters.

- 576 -
Chapter 5 - Cxxxx Parameters

Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.253 CONFIGPROVERSIGNAL

Specific to Series C PI
Block(s)
Description Configured Prover Signal
Data Type UINT8
Range 0, 1, 3, 5, 7
Default 0
Config Load No
Active No
Loadable
Access Lock Operator
Residence IOM
Related ACTUALPROVERSIGNALMAINTAINONFAULT
Parameters
Remarks This parameter provides the user the ability to specify on any given Pulse Input
Module the signal stream to output to the Prover signal screw pair. Only dual
streams are valid to be selected. The options available are:
l 0 - No stream is selected
l 1 - Good pulses from the dual stream present on channel 1 and channel 2 are
being output to the prover signal screw pair.
l 3 - Good pulses from the dual stream present on channel 3 and channel 4 are
being output to the prover signal screw pair.
l 5 - Good pulses from the dual stream present on channel 5 and channel 6 are
being output to the prover signal screw pair.
l 7 - Good pulses from the dual stream present on channel 7 and channel 8 are
being output to the prover signal screw pair.

- 577 -
Chapter 5 - Cxxxx Parameters

5.254 CONFIGSTS

Specific to Handler, RegCalc, SCM, RCM, Step, Transition, Phase


Block(s)
Description: Configuration Status
Data Type Enumeration AUXCALCCONFIGSTS, CSCOCONFIG
Range Ok (0) - The configuration is fully functional. No problems or issues detected
Information (1) - The configuration is operational. No action required, review
advised. However there are things, which may need further consideration. In some
cases the configuration may be optimized. Warning (2) ) - The configuration may be
operational. Review required. Configuration may contain engineering errors.
SevereWarning (3) - The configuration is unlikely to be operational or useful.
Review required. Corrections strongly advised. Fail (4) - The configuration is not
operational and needs corrections. The block reporting this or a higher value will
not participate in any processing. Error (5) - The configuration is not operational
and needs corrections. One or more problems are likely not correctable by the user.
SevereError (6) - not used by SCM , RCM and their contained blocks
Default Ok (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CONFIGSTS, CONFIGDESC
Parameters
Remarks CONFIGSTS , CONFIGCODE and CONFIGDESC are updated only during activation
of RCM/SCM and maintain their values as long as RCM/SCM are active. Perform
drill down in Control Builder Monitoring tree view to identify root causes and/or
multiple configuration problems.

5.255 CONFIGSTS[1..8]

Specific to Block Auxcalc, Enhauxcalc


(s)
Description: Configuration Status
Data Type Enumeration AUXCALCCONFIGSTS, CSCOCONFIG
Range Ok (0) Information (1) Warning (2) SevereWarning (3) Fail (4) Error (5)
SevereError (6)
Default Ok (0)
Config Load No
Active Loadable No

- 578 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks

5.256 CONFIGURATIONFILE

Specific to Block(s) 850M


Description File name.
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence ERDBONLY
Related Parameters
Remarks Name of associated .icd or .cif file

5.257 CONFIGURED

Specific to RM
Block(s)
Description RM Configuration Status. Value of USER indicates the module has been configured
to do something different than the “out-of-the-box”default.
Data Type Enumeration
Range Factory (0) User (1)
Default Factory (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 579 -
Chapter 5 - Cxxxx Parameters

5.258 CONFIGVERSION

Specific to Block(s) 850M


Description Configuration Version
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

5.259 CONFIRM[0..15]

Specific to Block(s) Message


Description Confirmation
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks

5.260 CONFIRMED[0..15]

Specific to Block(s) Message


Description Confirmed
Data Type Boolean
Range Off (0) On (1)
Default
Config Load
Active Loadable No

- 580 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

5.261 CONFLICTFL

Specific to SCM. RCM, UCM, CM


Block(s)
Description Conflict Flag - Unmanaged conflicts.
Data Type Boolean
Range Off No unmanaged conflicts
On Unmanaged conflicts
Default Off
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related QUEUESIZE
Parameters
Remarks This is a diagnostic parameter and shall not be used for control. Depending on the
application, the value may flicker/fluctuate. This is normal and not a defect. This
flag indicates, whether requests were rejected, which could not be granted directly
nor placed into queue (because queue does not exist or it is full). This flag will
always be reset, whenever a requester is released or otherwise removed from the
resource or its queue. It will be set on the first request which cannot be handled by
the resource and cannot be placed into the queue. A value of ON indicates, that
conflict resolution will occur in seemingly random fashion. If this is not desired, the
value of QUEUESIZE shall be increased. A value of ON indicates also, that the
queue information displayed is incomplete. This is not a problem per-se. For more
information see Components Theory. Is always OFF, if NUMWAITING < (less than)
QUEUESIZE. Is always OFF, if NUMOWNERS < (less than) MAXOWNERS.

- 581 -
Chapter 5 - Cxxxx Parameters

5.262 CONINUSE

Specific to PCDI_MASTER
Block(s)
Description Current connection in use
Data Type Enumeration
Range 0 Primary
1 Secondary
2 None
Default Primary
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Static text that describes the connection currently in use, which is either Primary or
Secondary. This parameter is only available for configured redundant peer devices.
This parameter changes dynamically during monitoring.

5.263 CONINUSEMON

Specific to PCDI_MASTER
Block(s)
Description Current connection in use monitor
Data Type Enumeration
Range 0 Primary
1 Secondary
2 None
Default Primary
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Static text that describes the connection currently in use, which is either Primary or
Secondary. This parameter is only available for configured redundant peer devices.
This parameter changes dynamically during monitoring.

- 582 -
Chapter 5 - Cxxxx Parameters

5.264 CONNCLOSEFAIL

Specific to Block(s) FTEB


Description Connection Close Failure - Identifies the connection close failures.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

5.265 CONNECTIONERROR

Specific to SIMEHPM
Block(s)
Description Connection Error provides connection error information that occurs between
Experion PKS SCE node and UniSim E-APP node.
Data Type STRING
Range NA
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence No Load
Related EAPPCONNTONSTATUS
Parameters
Remarks Connection error provides information about why the connection between two
nodes failed or what is the possible error in connection.

- 583 -
Chapter 5 - Cxxxx Parameters

5.266 CONNECTIONEVTTIME

Specific to SIMEHPM
Block(s)
Description Time Of Last Connection Event shows the time of the most recent connection
event established between Experion PKS SCE node and UniSim E-APP node.
Data Type STRING
Range NA
Default None
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence SRAL
Related EAPPCONNTONSTATUS
Parameters
Remarks

5.267 CONNERR

Specific to FTEB
Block(s)
Description This specifies the last open connection error of Series A IOM's configured to this
FTEB.
Data Type Enumeration
Range NA
Default Unknown
Config No
Load
Active No
Loadable
Access Lock ViewOnly

- 584 -
Chapter 5 - Cxxxx Parameters

Residence FTEB
Active No
Connector
Related
Parameters
Remarks This will show the last open connection error status of all the (Up to 16) Series A & H
IOM's configured to this FTEB. This parameter shows the last open error status of
all the configured IOM's. This is a view only FTEB IO manager statistics parameter.
This represents the IO manager error status codes and the possible enums are,
l NoMapError = 0:
l InvalidMapInstance:
l InvalidAssemblyInstance:
l InsufficientMapMemory:
l InsufficientConfigMemory,
l InsufficientSharedRam,
l InvalidCommPath,
l InvalidConfig,
l IcpDriverFail,
l BuffSizeBad,
l BadConnType,
l DeleteConnBusy,
l PriorReconfigurationPending,
l AsaReconfigurationFail,
l InvalidUpdateRate,
l ConnModeBad,
l ConnRoleBad,
l ConnTriggerBad,
l ConnTransportBad,
l ConnPriorityBad,
l BuffTypeBad
All the above enums are self explanatory and need no further explanation.

5.268 CONFIGINFO

Specific to 1738-AENT
Block(s)
Description Configuration Information
Data Type ENUM
Range l 0– OK
l 1 — IOMNotLoaded
l 2 — ConfigError
l 3 — Internal Error

- 585 -
Chapter 5 - Cxxxx Parameters

Default 0 — OK
Config Load No
Active No
Loadable
Access Lock ReadOnly
Residence CEE
Related IOCONNSTATUS
Parameters
Remarks This parameter provides additional information when consolidated connections are
used.
l 1 – An I/O module that is supposed to participate in the assembly connection
is not loaded.
l 2 – There is problem with the configuration and we could not attempt to
establish a connection. The configuration needs to be changed. (Example:
Configuration data for this setup exceeds the max amount.)
l 3 – An internal error occurred that is preventing us from attempting to
establish a connection. (Example: Max IOMs Exceeded, Insufficient Memory,
etc)

5.269 CONFIGVER

Specific to
Block EIM
Description Config Version of DSMAP
Data Type UINT8
Range 0 to 255
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related
Parameters VERSION of DSIN block
Indicates the version of the DSMAP block. Used to validate DSMAP and DSIN
Remarks are on the same version.

5.270 CONFREVMISMATCH

Specific to Block(s) EIM


Description ConfigRev Mismatch
Data Type BOOL
Range NA

- 586 -
Chapter 5 - Cxxxx Parameters

Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

5.271 CONNLISTSIZE

Specific to Block(s) CM
Description
Data Type Integer
Range
Default 0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

5.272 CONNOPENFAIL

Specific to Block(s) FTEB


Description Connection Open Failure - identifies the connection open failures.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

- 587 -
Chapter 5 - Cxxxx Parameters

5.273 CONNOPENREJECT

Specific to Block(s) FTEB


Description Connection Open Reject - Identifies the connection open rejuects.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

5.274 CONNSENDERR

Specific to Block(s) FTEB, Secondary FTEB


Description Connected send errors
Data Type 32-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

5.275 CONNSTAT

Specific to FTEB
Block(s)
Description This specifies the connection status of Series A &H IOM's configured to this FTEB.
Data Type Enumeration
Range NA
Default Unknown
Config No
Load
Active No

- 588 -
Chapter 5 - Cxxxx Parameters

Loadable
Access Lock ViewOnly
Residence FTEB
Active No
Connector
Related
Parameters
Remarks This will show the connection status of all the (up to 16) Series A & H IOM's
configured to this FTEB. This parameter will show the status of all the configured
IOM'. The user can use this parameter to know the connection status of each IOM
configured to this FTEB. This is view only FTEB IO manager statistics parameter.
The IO manager possible connections status enums are,
l BadSchedule = 0:
l CommError:
l ConfigError:
l Connected:
l ConnInUse:
l IomNotFound:
l NoConfig:
l NoKeeper:
l NoSchedule:
l NotConnected:
l WrongModule:
The above enums are same as the ones that are displayed in the module
configuration tab of IO modules forms. All the enums are self explanatory.

5.276 CONNSTATUS

Specific to Block EIM


Description DSIN Connection Status
Data Type ENUM
Range Disconnected (0) Connected (1)
Default Disconnected
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters LASTCONNERROR
Remarks This parameter is for Internal use only

- 589 -
Chapter 5 - Cxxxx Parameters

5.277 CONNSTS[0..1]

Specific to Block(s) PCDI_MASTER


Description Connection Status
Data Type Enumeration
Range 0 Invalid
1 Initial
2 Connecting
3 Connected
4 Failed
Default Initial
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Device
Related Parameters
Remarks

5.278 CONNTMOMULT

Specific to All EIP IOM/Devices/Drives and EIP Generic adapter


Block(s)
Description Connection Timeout Multiplier
Data Type ENUM
Range 0 - *4

1 - *8
2 - *16
3 - *32
4 - *64
5 - *128
6 - *256
7 - *512
255 - Computed
Default 255 - Computed
Config Load Yes
Active No
Loadable

- 590 -
Chapter 5 - Cxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related OTCONNPRIORITY, TOCONNPRIORITY
Parameters
Remarks When the value is “Computed”, the value in internally determined by the block to
match with a minimum connection timeout time.

5.279 CONSOPENRDY

Specific to Block(s) VALVEDAMPER, SOLENOID


Description Ready for Console Open
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.280 CONSOLIDATECONN

Specific to 1738-AENT adapter block


Block(s)
Description Consolidate IOM Connections
Data Type BOOLEAN
Range l 0 – Off – Each IOM associated with this adapter will have a separate
connection.
l 1 – On – Each IOM associated with this adapter will share one connection
which will be maintained by the adapter. All Input/Output from modules will be
consolidated and sent/received by the adapter.
Default 0 – Off
Config Yes
Load
Active No
Loadable

- 591 -
Chapter 5 - Cxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related None
Parameters
Remarks For the Rockwell 1734 and 1738 family of I/O, this is also known as assembly
connections. When enabled, parameters TORPI and OTRPI on the adapter become
configurable and must be configured accordingly. The TORPI and OTRPI in the
individual I/O modules associated with this adapter will not be configurable.

5.281 CONSSTARTRDY

Specific to Block(s) LTMOTOR


Description Ready to Start from Console
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related BRNGTEMPTRIPBYPASSBYPPERMOI[0..2]MTTERRCODE VIBRTRIP
Parameters WDGTEMPTRIP
Remarks Indicates when motor is ready to start based on the interlocks.

5.282 CONST[1...8]

Specific to AuxCalc, EnhAuxCalc, RegCalc, EnhRegCalc


Block(s)
Description An array eight parameters that could be used as constants in expressions of
calculator blocks.
Data Type Float 64
Range N/A
Default NaN
Config YES
Load
Active No
Loadable

- 592 -
Chapter 5 - Cxxxx Parameters

Access Lock Configurable by CONSTACCLOCK


Residence CEE
Related CONSTACCLOCK, CONSTENABLE, EXPRDESC[1...8]
Parameters
Remarks The constants can be used as output pins to write values to other blocks or used as
input pins to fetch values from other blocks. The parameter can be configured only
when the CONSTENABLE is set to TRUE and the access lock specified by the
CONSTACCLOCK parameter is “Engineer” or “EngineerAppDev”. Example: This
parameter can be used in expressions as follows: CM1.CALC1.CONST[1] *
CM1.CALC1.X[2] + CM2.REGCALCA.CV Note:
l This parameter can be modified by Standard block or CAB block (present within
the same or in another Control Module) based on the configured access lock
(CONSTACCLOCK).
l The values of CONST[1...8] are retained on a Checkpoint Save-Restore, On
Process Migration and RAM Retention Restart.
l If a constant value is used in an expression when CONSTENABLE is set to
“FALSE”, the expression result is NAN.
l If the CONSTACCLOCK is set to “Operator”, the values of CONST[1...8] can be
stored with any access level. SCMs, programs and other function blocks can
also change the values of CONST[1..8] parameter.
l If CONSTACCLOCK is set to “Engineer”, the values can be stored to the CONST
[1..8] parameter only if you have logged in as Engineer, Program, OtherFB,
and AppDevOnly. If you have logged in as other user, an “Invalid Access Level”
error is displayed.
l If CONSTACCLOCK is set to “EngineerAppDev”, the values of CONST[1...8] can
be stored only if you have logged in as EngineerAppDev. If you have logged in
as other user, an “Invalid Access Level” error is displayed.
l If CONSTACCLOCK is set to “Program”, the values of CONST[1...8] can be
stored only if you logged in as SCMs and other user programs or other
function blocks. If you have logged in as any other user, an “Invalid Access
Level” error is displayed.
l Memory is allocated to this parameter, only if the CONSTENABLE is set to
TRUE.

5.283 CONSTACCLOCK

Specific to AuxCalc, EnhAuxCalc, RegCalc, EnhRegCalc


Block(s)
Description This parameter defines the access lock for configuring the array of block expression
constants (CONST[1..8]).
Data Type ENUMERATION
Range Engineer - Values can be stored to the CONST [1...8] parameters only when the
access level is set to Engineer, Program, OtherFB, and AppDevOnly. Operator -
Values are stored to the CONST [1...8] parameter with any access level.
Engineer/AppDev - Values can be written to the CONST [1...8] parameters only
when the access level is Engineer or AppDevOnly. Program - Only SCM's and other
user programs or other function blocks can write the values to the CONST [1...8]
parameters.
Default Engineer
Config YES

- 593 -
Chapter 5 - Cxxxx Parameters

Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related CONSTENABLE, CONST[1...8], EXPRDESC[1...8]
Parameters
Remarks This parameter is enabled for use when the CONSTENABLE is set to TRUE. Note:
The value of CONSTACCLOCK parameter is retained on a Checkpoint Save-Restore,
On Process Migration and RAM Retention Restart.

5.284 CONSTENABLE

Specific to AuxCalc, EnhAuxCalc, RegCalc, EnhRegCalc


Block(s)
Description This parameter is used for enabling/disabling the use of expression constants in
calculator blocks.
Data Type Boolean
Range FALSE/TRUE
Default FALSE
Config YES
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related CONST[1...8], CONSTACCLOCK, EXPRDESC[1...8]
Parameters
Remarks When this parameter is set to “TRUE”, the parameters CONST[1..8], and
CONSTACCLOCK are enabled for use. If the value of this parameter is set to
“FALSE”,
l No memory is allocated for the CONST [1..8] and the CONSTACCLOCK
parameters. They remain disabled.
l “Parameter Blank” error is displayed when the constants are read.
l “CONSTENABLE not enabled” error is displayed when the constant values are
stored.
Note:
l If CONSTENABLE is set to “FALSE” after configuring the values of
CONSTACCLOCK and CONST[1..8], the CONSTACCLOCK and CONST[1..8]
parameters are reset to their default values. Subsequently, if the
CONSTENABLE is set to “TRUE”, the CONSTACCLOCK and CONST[1..8]
parameters are enabled with default values. The previously configured values
are not retained.
l If CONSTENABLE is set to “TRUE “and the Calculator blocks are loaded to an
old version controller then the CONSTENABLE displays “Parameter Blank”
error and all new parameters are unavailable.
l The value of CONSTENABLE parameter is retained on a Checkpoint Save-
Restore, On Process Migration and RAM Retention Restart.

- 594 -
Chapter 5 - Cxxxx Parameters

5.285 CONTAINEDIN

Specific to Block All PM I/O channel blocks (AI, AO, DI, DO, HAI, and HAO Channels); All Series C
I/O channel blocks
Description Contained in.
Data Type String
Range N/A
Default Null
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence SR
Related N/A
Parameters
Remarks The name of CM block to which the IOC is assigned. It appears on the Main tab.

5.286 CONTAINMEM

Specific to Containers
Block(s)
Description All memory allocated by this block and all contained component blocks (not
counting the contained containers).
Data Type INT32
Range 0 to 4294967296
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related None
Parameters
Remarks This parameter is implemented for SCM/RCM/Master recipe /Control recipe, but
the infrastructure is for all containers.

- 595 -
Chapter 5 - Cxxxx Parameters

5.287 CONTCUTOUT

Specific to Block(s) Most Function Blocks


Description Alarming Contact Cutout
Data Type BOOLEAN
Range Off On
Default Off

Config Load No

Active Loadable No
Access Lock Program
Residence Respective device/controller, platform

Related Parameters N/A


Remarks

5.288 CONTOUSE

Specific to PCDI_MASTER
Block(s)
Description Current connection to use
Data Type Enumeration
Range 0 Primary
1 Secondary
2 AUTO
3 NONE
4 UNDEFINED
Default Primary
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks This parameter is only available for configured redundant peer devices. It lets users
change the primary or secondary connection. A setting of AUTO lets the peer
software automatically choose either the primary or secondary connection when a
device fails over. The AUTO and NONE selections are the only ones available for a
non-redundant bridge device.

- 596 -
Chapter 5 - Cxxxx Parameters

5.289 CONTROLLOCK

Specific to SCM
Block(s)
Description Control Access Lock
Data Type Enumeration CSCOACCLOCK
Range Operator (0) Engineer (1) ViewOnly (2) OtherFB (3) Supervisor (4)
Default Operator (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related COMMANDMODE
Parameters
Remarks CONTROLLOCK defines what access lock is used for the following changes: MODE
change to SemiAuto or Manual Issue a Hold COMMAND

5.290 CONTROLPREDICTION

Specific to Block(s) PROFITCTLIN


Description CV Prediction Array
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Array for CV Prediction values of size number of CVS x Prediction size (20)

Specific to Block(s) PROFCONOUT


Description MV Future Moves
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No

- 597 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.VALUE
Remarks Predicted future MV values

5.291 CONTROLPRIORITY

Specific to Block(s) ProfitCtl


Description Control Priority
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load
Active Loadable No
Access Lock ENGINEER
Residence
Related Parameters
Remarks

5.292 CONTROLREQ

Specific to DevCtl All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description Sequential Control Module (SCM) Control Request
Data Type Structure
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related GOPREQ, MODEATTR, OPREQ, OPTYPE, SCHEDCYCLE[0..120] SCMASTEP[1..15],
Parameters SCMID, SCMOPT.
Remarks Invalid if Control Module SCMOPT ≠ Fixed.

- 598 -
Chapter 5 - Cxxxx Parameters

5.293 CONVTOASCII

Specific to PCDITEXTARRCH
Block(s)
Description Convert to ASCII - Character length of string values.
Data Type Boolean
Range True/False
Default True
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks CONVTOASCII, STRLEN, and NSTRING combine to determine total text block size.
Their load order is important. CONVTOASCII must be first followed by STRLEN. Size
Validation will be performed by text block during load of NSTRING.

5.294 CONVTOLONG

Specific to PCDINUMARRCH
Block(s)
Description Convert to Long - Determines if numeric values will be represented as floating
point numbers, when not checked, or longs.
Data Type Boolean
Range True/False
Default False
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks

- 599 -
Chapter 5 - Cxxxx Parameters

5.295 COS

Specific to Block(s) DIC


Description Change of State.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.296 COS[0..NumChans-1]

Specific to Block(s) DIM


Description Change of State.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.297 COUNTERTYPE

Specific to HRBALG_HLPIUCO
Block(s)
Description
Data Type ENUM
Range COUNTER16 COUNTER32
Default COUNTER16
Config Load No
Active No
Loadable

- 600 -
Chapter 5 - Cxxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks This parameter enables to select either the 16–bit counter or the 32–bit counter
depending on the point type.

5.298 CHGOFSTALMENB

Specific to DEVCTL
Block(s)
Description COS Alarm Enable option is used to enable/disable COS alarm priority, severity,
time delay.
Data Type BOOLEAN
Values OFF, ON
Default OFF
Config Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related CHGOFSTALM.PRCHGOFSTALM.SVCHGOFSTALM.TM
Parameters
Remarks for this parameter indicates that Change of state alarm priority, severity, time delay
are disabled and cannot be configured until this parameter is enabled. Only project
side changes are allowed. No online modification support is available for this
parameter.

5.299 CP[1..10]

Specific to Block(s) ENHAUXCALC


Description Input Scalig Factor - Defines the scaling factor for each input parameter.
Data Type Float64
Range 0 to 10
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence ACE, C200
Related Parameters P[1..10], PP[1..10]
Remarks

- 601 -
Chapter 5 - Cxxxx Parameters

5.300 CPCOMPATIBLE

Specific to C200, C300, FIM4, EHG, LIOM , EHPM, ACE, SIM_C200, CEE, CEEACE,
Block(s) CEESIMC200, OPC, ICG, IOLINK, SIMIOLIM, SIMIOLINK, CEEC300, GEE, EE,
SLINKB, SLINKA, CEEUOC, UOC, CEECN100
Description Checkpoint Compatibility
Data Type Integer32
Range ±2147483647
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This is an identification number for the checkpoint file which is unique across the
enterprise. It indicates the logical integrity of the checkpoint file data.

5.301 CPCODESIZE[1..10]

Specific to Transition Block


Block(s)
Description Number of Pcode Bytes for Condition expression. Represents number of bytes
required for the Psuedo code for the expression of Condition i, where i is the
parameter index from 1..10.
Data Type Integer32
Range 0 to 200
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence ACE, C200, SIM_C200
Related CNUMSRCCONN[1..10]
Parameters
Remarks

- 602 -
Chapter 5 - Cxxxx Parameters

5.302 CPEERAVGLPS [1..RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Peer Responder Rate
Data Type Float64
Range Greater than or equal to 0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100 IOLINKCN100)
Related STATRESET, CPEERMAXLPS
Parameters
Remarks

5.303 CPEERAVGLPSCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Control Execution Environment Peer Average IMRs Per Connection
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100 IOLINKCN100)
Related STATRESET, CPEERMAXLPSCONN
Parameters
Remarks

- 603 -
Chapter 5 - Cxxxx Parameters

5.304 CPEERAVGPPS [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Control Execution Environment Peer Average Parameters Per Second
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100 IOLINKCN100)
Related STATRESET, CPEERMAXPPS
Parameters
Remarks

5.305 CPEERAVGPPSCONN [1...RPEERCONNMAX]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Average Peer Parameters Per Second Per Connection
Data Type Float64
Exposure OUTPUT
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, CN100(CEECN100
IOLINKCN100)
Related STATRESET, CPEERMAXPPSCONN
Parameters
Remarks

- 604 -
Chapter 5 - Cxxxx Parameters

5.306 CPEERAVGSPS [1...RPEERCONNMAX]

Specific to Block(s) CEE, IOLIM, FIM


Description Control Execution Environment Peer Average Stores Per Second
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related Parameters
Remarks

5.307 CPEERAVGSPSCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Average Peer Acyclic Stores Per Second
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC),
CN100(CEECN100 IOLINKCN100)
Related STATRESET, CPEERMAXSPSCONN
Parameters
Remarks

5.308 CPEEREXCHAVGPPSCONN

Specific to Block(s) CEEFB, CEEC300


Description Average Exchange Peer Parameter Per Second get rate per connection.
Data Type Float64
Range
Default 0.0

- 605 -
Chapter 5 - Cxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.309 CPEEREXCHAVGSPSCONN

Specific to Block(s) CEEFB, CEEC300


Description Average Exchange Peer Parameter Store Per Second store rate per
connection.
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

5.310 CPEEREXCHMAXPPSCONN

Specific to Block(s) CEEFB, CEEC300


Description Maximum Exchange Peer Parameter Per Second get rate per connection.
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 606 -
Chapter 5 - Cxxxx Parameters

5.311 CPEEREXCHMAXSPSCONN

Specific to Block(s) CEEFB, CEEC300


Description Maximum Peer Exchange Store Per Second store rate per connection.
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.312 CPEERMAXLPS [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Control Execution Environment Peer Maximum IMRs Per Second
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100 IOLINKCN100)
Related STATRESET, CPEERAVGLPS
Parameters
Remarks

5.313 CPEERMAXLPSCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Control Execution Environment Peer Maximum IMRs Per Connection
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0

- 607 -
Chapter 5 - Cxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100 IOLINKCN100)
Related STATRESET, CPEERAVGLPSCONN
Parameters
Remarks

5.314 CPEERMAXPPS [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Max Peer Responder Rate
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100 IOLINKCN100)
Related STATRESET, CPEERAVGPPS
Parameters
Remarks

5.315 CPEERMAXPPSCONN [1...RPEERCONNMAX]

Specific to C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC),


Block(s) CEECN100
Description Maximum Get Rate
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active Loadable No

- 608 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100 IOLINKCN100)
Related STATRESET, CPEERAVGPPSCONN
Parameters
Remarks

5.316 CPEERMAXSPS [1...RPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Control Execution Environment Peer Maximum Stores Per Second - The maximum
number of peer acyclic stores per second processed by the execution environment.

Data Type Float64


Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

5.317 CPEERMAXSPSCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Maximum Peer Acyclic Stores Per Second
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable

- 609 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100 IOLINKCN100)
Related STATRESET, CPEERAVGSPSCONN
Parameters
Remarks

5.318 CPEERWAAVGPPS

Specific to Block(s) CEEC300, CEE(ACE), CEEUOC, CEECN100


Description WA Peer Average Responder Rate
Data Type Float64
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(CEE) , UOC(CEEUOC), CN100 (CEECN100)
Related Parameters CPEERWAMAXPPS
Remarks

5.319 CPEERWAAVGPPSCONN

Specific to Block(s) CEEC300, CEE(ACE), CEEUOC, CEECN100


Description WA Average Get Rate
Data Type Float64
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(CEE), UOC(CEEUOC), CN100 (CEECN100)
Related Parameters CPEERWAMAXPPSCONN
Remarks

- 610 -
Chapter 5 - Cxxxx Parameters

5.320 CPEERWAMAXPPS

Specific to Block(s) CEEC300, CEEACEFB, CEEUOC, CEECN100


Description WA Peer Maximum Responder Rate
Data Type Float64
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(CEE) , UOC(CEEUOC), CN100 (CEECN100)
Related Parameters CPEERWAAVGPPS
Remarks

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300


Block(s)
Description Control Execution Environment Peer Maximum Parameters Per Second
Data Type Float64
Range >= 0.0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM
Related STATSRESET
Parameters
Remarks The maximum number of peer parameters per second processed by the execution
environment, including both cyclic and acyclic requests.

5.321 CPEERWAMAXPPSCONN

Specific to Block(s) CEEC300, CEEACEFB, CEEUOC, CN100


Description WA Maximum Get Rate
Data Type Float64
Range
Default 0
Config Load No
Active Loadable No

- 611 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300), ACE(CEE) , UOC(CEEUOC), CN100 (CEECN100)
Related Parameters CPEERWAAVGPPSCONN
Remarks

5.322 CPLASTSAVE

Specific to Block C200, C300, FIM4, EHG and LIOM. ACE, SIM_C200, SIMACE, OPC, ICG,
(s) SIMIOLIM, EHPM, UOC
Description Time of Last Checkpoint Save
Data Type TIME
Range Integer64
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related CPSTATUS, CPTIMEOFSAVE
Parameters
Remarks Provides wall clock time of when most recent checkpoint save was completed
on this platform.

5.323 CPMCOMMAND[0..numChans-1]

Specific to Block(s) CPM


Description This block will replace PCMCOMMAND in a later release.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

- 612 -
Chapter 5 - Cxxxx Parameters

5.324 CPMCOMMAND

Specific to Block(s) UOC


Description Module Command
Data Type ENUM
Range N/A
Default None
Config Load Yes
Active Loadable
Access Lock Engineer
Residence NOLOAD
Related Parameters
Remarks UOC platform block command.

5.325 CPMSTATE

Specific to Primiray/Secondary C300, C200, EHG & LIOM. ACE, SIM_C200


Block(s)
Description Controller State
Data Type Enumeration
Range OFFNET (0) TESTING (1) BOOTING (2) ALIVE (3) LOADING (4) OK (5) FAILED (6)
PIREADY (7) BACKUP (8) NOTLOADED (9) NOCEE (10) CEEIDLE (11) CEERUN (12)
CEEMIX (13) TIMESOURCE (14)
Default NOTLOADED (9)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, ACE, SIM_C200, C300, EHG
Related C300STATE, C300COMMAND
Parameters
Remarks This is same as C300STATE. Parameter was added for backward compatibility and is
an invisible parameter.

Specific to Block(s) UOC


Description Module State
Data Type ENUM
Range N/A
Default NOTLOADED
Config Load No
Active Loadable

- 613 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks UOC platform block state.

5.326 CPNODESTATEPARM

Specific to Block(s) C200, C300, LIOM, FIM4, EHG ACE, SIM_C200, OPC, ICG, SIMIOLIM, EHPM,
UOC
Description Name of Pltform Blk Parm that Checkpoint accesses for node's Exec State.
Data Type String
Range Length 64 characters, N/A
Default CPMSTATE
Config Load No, Yes
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks

5.327 CPPARPERFRAG

Specific to Block(s) CEEFB,CEEACEFB,CEESIMC200FB,SIMIOLINK,GEEFB, CEEUOC


Description Number of Parameters per CDA Request
Data Type 32-bit unsigned integer
Range None
Default 100
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks

- 614 -
Chapter 5 - Cxxxx Parameters

5.328 CPRESTORESCOPE

Specific to C200, C300, FIM4, EHG, LIOM, EHPM, UOC ACE, SIM_C200, OPC, ICG, SIMIOLIM,
Block(s) HLAI, STIMV, LLMUX, LLAI, RHMUX, AO8, AO16, DO16, DO32, DI, DI24V, DISOE,
AO16HART, HLAIHART, AI-HART, AI-LLMUX, AI-LLAI, AO-HART, DI-HV, DI-24, DO-
24B, CB, AMC, HLPIU, LEPIU, LLPIU, DHP, AMCRCD, CBRCD
Description Checkpoint Restore Scope
Data Type Enumeration
Range ExposedNotChecked (0) ExposedChecked (1) UnExposedChecked (2)
UnExposedNotChecked (3) N/A
Default UnExposedChecked (2), UnExposedNotChecked
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter indicates the Restore Scope of the block. It is present on blocks
which have an associated SS attribute.

5.329 CPSAVCOMPPERC

Specific to Block(s) C200, C300, FIM, LIOM, EHG, EHPM, UOC ACE, SIM_C200, OPC, ICG,
SIMIOLIM
Description Percentage SAVE complete
Data Type Unsigned integer8
Range N/A, 0 to 255
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related CPSTATUS
Parameters
Remarks This parameter indicates the percentage completion of Checkpoint Save.

- 615 -
Chapter 5 - Cxxxx Parameters

5.330 CPSLEEPTIME

Specific to Block(s) CEEFB,CEEACEFB,CEESIMC200FB,SIMIOLINK,GEEFB, CEEUOC


Description Time between CDA requests (in milliseconds).
Data Type UINT32
Range None
Default 1000
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks

5.331 CPSTATUS

Specific to Block C200, C300, FIM4, EHG, LIOM, , EHPM, UOC ACE, SIM_C200, OPC, ICG,
(s) SIMIOLIM
Description Checkpoint Status
Data Type Enumeration
Range 0 (Blank)
1 Running
2 Complete
3 Complete with Stale Data
4 Complete with Dangling Data
5 Complete with Mismatched Data
6 Failed - Corruption, no checkpoint file
produced
7 Failed - Other, See error logs on server
N/A
Default 0 (which is “ ” enumerated value)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related CPTIMEOFSAVE, CPLASTSAVE, CPSAVCOMPPERC
Parameters
Remarks Provides status of most recent checkpoint save on this platform.

- 616 -
Chapter 5 - Cxxxx Parameters

5.332 CPTIMEOFSAVE

Specific to Block C200, C300, FIM4, EHG, LIOM, EHPM ACE, SIM_C200, OPC, ICG, SIMIOLIM
(s)
Description Elapsed Time of Last Checkpoint Save
Data Type DELTATIME
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related CPSTATUS, CPLASTSAVE
Parameters
Remarks Provides the time that was required to complete the most recent checkpoint
save on this platform.

5.333 CPUCYCLEAVG[0..39]

Specific to CEEC300, CEE, CEEUOC


Block(s)
Description Average percentage of Central Processing Unit (CPU) Processing Power Used Per
Cycle.
Data Type FLOAT64
Range Greater than or equal to 0
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC)
Related CPUCYCLEMAX[0..39], STATSRESET.
Parameters
Remarks Each element gives a rolling average of the CPU used by each execution cycle.
Units are percent of 50 ms cycle. Index corresponds to the cycle (phase) number.
Averaging can be restarted by storing to the STATSRESET parameter.
Characteristic time constant of the average is 1 minute. Wait 2-3 minutes to be sure
averaging has fully settled. The CPUCYCLEAVG[40] contains the average value
across all 40 phases.

- 617 -
Chapter 5 - Cxxxx Parameters

Specific to CEEACE, CEESIMC200


Block(s)
Description CPU Cycle Average - Defines a rolling average of the central processing unit (CPU)
used for point processing on given execution cycle.
Data Type Float64
Range N/A
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence ACE, SIM_C200
Related
Parameters
Remarks Units are in percent of the 500 milliseconds cycle. The index corresponds to the
cycle (phase) number. Characteristic time constant of the average is 1 minute. Wait
2 to 3 minutes to be sure averaging has completed. You can reset the calculation by
clicking the Initialize Timing Stats (STATRESET) button on the Statistics tab of the
CEE configuration form in Monitor mode. The CPUCYCLEAVG[40] contains the
average value across all 40 phases.

5.334 CPUCYCLEMAX[0..39]

Specific to CEEC300, CEE, CEEUOC


Block(s)
Description Max CPU Used per Cycle
Data Type FLOAT64
Range Greater than or equal to 0.
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300) , UOC(CEEUOC)
Related CPUCYCLEAVG[0..39], STATSRESET
Parameters
Remarks Each element gives the historical maximum of the CPU used by each execution
cycle. Units are percent of 50 ms cycle. Index corresponds to the cycle (phase)
number. Historical maximum can be reset to current instantaneous value by
storing to the STATSRESET parameter. The CPUCYCLEMAX[40] contains the
maximum value across all 40 phases.

- 618 -
Chapter 5 - Cxxxx Parameters

Specific to CEEACE, CEESIMC200


Block(s)
Description CPU Cycle Maximum
Data Type FLOATA64
Range N/A
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence ACE, SIM_C200
Related CPUCYCLEAVG[0..39]
Parameters
Remarks Units are in percent of the 500 milliseconds cycle. The index corresponds to the
cycle (phase) number. You can reset the calculation by clicking the Initialize Timing
Stats (STATRESET) button on the Statistics tab of the CEE configuration form in
Monitor mode. The CPUCYCLEMAX[40] contains the maximum value across all 40
phases.

5.335 CPU0FREEAVG

Specific to Block(s) UOC and CN100, C300, EIM, ELCNB, ELCNNODE


Description CPU Free, core 0 (%)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks CPU free running average (for core 0 only).

5.336 CPU0FREEMIN

Specific to UOC, C300, CN100, EIM, ELCNB, ELCNNODE


Block(s)
Description Minimum CPU Free, core 0 (%)
Data Type FLOAT64
Range ±1.7E+308
Default

- 619 -
Chapter 5 - Cxxxx Parameters

Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks CPU free running average low water mark (for core 0 only). Note that the low
water mark is reset using the "reset statistics" command.

5.337 CPU1FREEAVG

Specific to Block(s) UOC, C300


Description CPU Free, core 1 (%)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks CPU free running average (for core 1 only).

5.338 CPU1FREEMIN

Specific to UOC, C300


Block(s)
Description Minimum CPU Free, core 1 (%)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks CPU free running average low water mark (for core 1 only). Note that the low water
mark is reset using the "reset statistics" command.

- 620 -
Chapter 5 - Cxxxx Parameters

5.339 CPUFREEAVG

Specific to C200, C300, ACE, FIM, IOLIM, FTEB, FIM4, EHG, LIOM, PGM, CEE, CEESIMC200,
Block(s) EE, EHPM,TCMI
Description Average free Central Processing Unit (CPU) Processing Power.
Data Type Float64
Range 0.0 to 100.0
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE, CPM), C300, ACE, FTEB, FIM, FIM4, EHG, LIOM, SIM_C200, IOLIM, PGM,
EHPM
Related CPUFREEMIN, STATSRESET, CPUFREERESET
Parameters
Remarks Gives rolling average of free CPU not currently used for processing by the CPM.
Units are percent. Averaging can be restarted by storing to the STATSRESET
parameter. Characteristic time constant of the average is 1 minute. Wait 2-3
minutes to be sure averaging has fully settled.

Specific to Block(s) EIM


Description CPU Free (%)
Data Type Float64
Range 0.0 to 100.0
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

Specific to Block(s) UOC


Description CPU Free, all cores (%)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable

- 621 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks CPU free running average (all cores).

5.340 CPUFREEAVGA

Specific to Block All Series C I/O Modules


(s)
Description CPU Free Average
Data Type Float64
Range 0.0 Minimum
100.00 Maximum
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related CPUFREEMINA, CPUFREEAVGA.
Parameters
Remarks This parameter displays the average percentage of CPU free time for the A IOM
in the last 2 minutes.

5.341 CPUFREEAVGB

Specific to Block All Series C I/O Modules


(s)
Description CPU Free Average
Data Type Float64
Range 0.0 Minimum
100.00 Maximum
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related CPUFREEMINB, CPUFREEAVGB.
Parameters
Remarks This parameter displays the average percentage of CPU free time for the B IOM
in the last 2 minutes.

- 622 -
Chapter 5 - Cxxxx Parameters

5.342 CPUFREECRITLM

Specific to Block(s) EIM, UOC, ELCN, ELCNB


Description CPU Free Critical Alarm (%)
Data Type 64-Bit Real Number
Range 10-100 %
Default 20
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence ELCN_BRG
Related Parameters ELCN_BRG Main tab – Advanced Configuration
Remarks

5.343 CPUFREEMIN

Specific to C200, C300, ACE, FIM, IOLIM, FTEB, FIM4, EHG, LIOM, PGM, CEE, CEESIMC200,
Block(s) EE, EHPM
Description Historical Minimum of Free CPU Processing Power.
Data Type Float64
Range 0.0 to 100.0
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE, CPM), C300, ACE, FTEB, FIM, FIM4, EHG, LIOM, IOLIM, SIM_C200, PGM,
EHPM
Related CPUCYCLEMAX[0..39], CPUFREEAVG, STATSRESET, CPUFREERESET
Parameters
Remarks Gives the historic minimum of the unused CPU available. Units are percent.
Historical minimum can be reset to current instantaneous value by storing to the
STATSRESET parameter.

Specific to Block(s) EIM


Description Minimum CPU Free (%)
Data Type FLOAT64
Range 0.0 to 100.0
Default

- 623 -
Chapter 5 - Cxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

Specific to UOC
Block(s)
Description Minimum CPU Free, all cores (%)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks CPU free running average low water mark (all cores). Note that the low water mark
is reset using the "reset statistics" command.

5.344 CPUFREEMIN1

Specific to Block(s) TCMI


Description CPU Free Minimum (%)
Data Type STRING
Range N/A
Default 90.30
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 624 -
Chapter 5 - Cxxxx Parameters

5.345 CPUFREELOWLM

Specific to Block(s) ELCN_BRG, CN100


Description CPU Free Low Alarm (%)
Data Type 64-Bit Real Number
Range 10-100 %
Default 20
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence ELCN_BRG
Related Parameters ELCN_BRG Main tab – Advanced Configuration
Remarks

5.346 CPUFREEMINA

Specific to Block All Series C I/O Modules


(s)
Description CPU Free Minimum
Data Type FLOAT32
Range 0.0 Minimum
100.00 Maximum
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related CPUFREEAVGA, CPUFREEAVGA.
Parameters
Remarks This parameter displays the minimum percentage of CPU free for all cycles of
the A IOM

- 625 -
Chapter 5 - Cxxxx Parameters

5.347 CPUFREEMINB

Specific to Block All Series C I/O Modules


(s)
Description CPU Free Minimum
Data Type FLOAT32
Range 0.0 Minimum
100.00 Maximum
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related CPUFREEAVGB, CPUFREEAVGB.
Parameters
Remarks This parameter displays the minimum percentage of CPU free for all cycles of
the B IOM

5.348 CPUFREERESET

Specific to Block(s) C200, C300, FIM4, FTEB and EHG ACE, SIM_C200, PGM
Description Init CPU Free Stats
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load No
Active Loadable No
Access Lock Operator
Residence C200(CEE, CPM), C300, FIM4, EHG, ACE, SIM_C200, FTEB, PGM
Related CPUFREEAVG, CPUFREEMIN, STATSRESET
Parameters
Remarks This parameter has edge trigger semantics and always returns OFF when
read.

- 626 -
Chapter 5 - Cxxxx Parameters

5.349 CPULOLM

Specific to C300 and FIM4, PGM


Block(s)
Description CPU Free Low Alarm (%)
Data Type Float64
Range 10 to 100
Default 20
Config CEE
Load
Active No
Loadable
Access Lock Engineer
Residence C300, FIM4, PGM
Related CPULOLOLM
Parameters
Remarks This parameter is configurable in contrast to CPULOLOLM. When the CPU
resource available falls less than this limit a diagnostic alarm is generated. By
default the value is set to 20 so that the Honeywell recommended spec of CPUFree
of 20% matches the default CPU low alarm.

5.350 CPULOLOLM

Specific to C300 and FIM4, PGM


Block(s)
Description CPU Free Low Low Alarm (%)
Data Type Float64
Range N/A
Default 10
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM
Related CPULOLM
Parameters
Remarks This parameter is set to a fixed, minimal value and is intended to help the engineer
or operator ensure that enough CPU remains free to handle bursts in
communication or other unexpected and/or anomalous loads.

- 627 -
Chapter 5 - Cxxxx Parameters

5.351 CPUMAXFLOAT

Specific to SCM, RCM, CM , UCM, CR, and MR


Block(s)
Description For SCM, RCM, CM, UCM, and Control recipe - The floating maximum value of the
CfExecute duration. For Master recipe - All time maximum value of the
CR.CPUMAXFLOAT.
Data Type INT32
Range 0 to 4294967296
Default 0
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related None
Parameters
Remarks For SCM, RCM, CM, UCM, and Control recipe - Spikes are recorded and no damping
increases. Progressive damping decreases which is optimized for system de-
bottlenecking (hot spot identification), and not for PU measurement . (Total of all
values of all containers exceed CEE average CPU capacity unless all containers
have max=avg , that is no fluctuations in CPU usage). In addition, it can be used for
direct PU measurement only under certain conditions. It may not provide useful
information on Windows nodes as it is suitable for trending (except Control recipe).
For Master recipe - Reset during activation, suitable for trending.

5.352 CPV

Specific to Block(s) LEADLAG, DEADTIME, AUXSUMMER, FLOWCOMP


Description Overall scaling factor for PV
Data Type Real Number
Range Any Real Number, NaN not allowed.
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE C200, C300, ACE for FLOWCOMP block
Related Parameters PV
Remarks

- 628 -
Chapter 5 - Cxxxx Parameters

5.353 CPVALIDSAVESTATES

Specific to EHPM, UOC


Block(s)
Description Array having permitted node's Exec States for Chkpt saves
Data Type Enumeration
Range OFFNET (0) TESTING (1) BOOTING (2) ALIVE (3) LOADING (4) OK (5) FAILED (6)
PIREADY (7) BACKUP (8) NOTLOADED (9) NOCEE (10) CEEIDLE (11) CEERUN (12)
CEEMIX (13) TIMESOURCE (14) PCMSTATEMAX (15) N/A
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related CPVALIDSAVESTATESSZ
Parameters
Remarks CPVALIDSAVESTATES array contains those states in the node's exec state that
permit a checkpoint save. In addition, if the node's in a failed condition where the
node's exec state parm (as given in CPNODESTATEPARM) cannot be obtained via
CDA, then a save is not permitted.

5.354 CPVALIDSAVESTATESSZ

Specific to Block(s) EHPM, UOC


Description Array size of CPVALIDSAVESTATES
Data Type 32-Bit Integer (INT32)
Range N/A, ±2147483647
Default 4
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters CPVALIDSAVESTATES
Remarks

- 629 -
Chapter 5 - Cxxxx Parameters

5.355 CPVALIDRESTSTATES

Specific to C200, C300, EHG, FIM4, LIOM, UOC. ACE, SIM_C200, OPC, ICG, SIMIOLIM, EHPM.
Block(s)
Description Array having permitted node's Exec States for Checkpoint restores
Data Type Enumeration
Range OFFNET (0) TESTING (1) BOOTING (2) ALIVE (3) LOADING (4) OK (5) FAILED (6)
PIREADY (7) BACKUP (8) NOTLOADED (9) NOCEE (10) CEEIDLE (11) CEERUN (12)
CEEMIX (13) TIMESOURCE (14) PCMSTATEMAX (15) N/A
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related CPVALIDRESTSTATESSZ
Parameters
Remarks This parameter contains states in the node's exec state that permit a checkpoint
restore. A valid restore state includes the node's failed condition, where the node's
exec state parameter (as given in CPNODESTATEPARM) can't be read through CDA.

5.356 CPVALIDRESTSTATESSZ

Specific to Block C200, C300, EHG, FIM4, LIOM, UOC. ACE, SIM_C200, OPC, ICG, SIMIOLIM,
(s) PGM, EHPM
Description Array size of CPVALIDRESTSTATES
Data Type 32-Bit Integer (INT32)
Range N/A, ±2147483647
Default 4
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related CPVALIDRESTSTATES
Parameters
Remarks

- 630 -
Chapter 5 - Cxxxx Parameters

5.357 CRCYCLEOVRN[0..40]

Specific to CEE, CEEC300, CEEUOC


Block(s)
Description Current Hour Cycle Overruns.
Data Type 16-Bit Real Number
Range 0 to 32767
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC)
Related LSCYCLEOVRN[0...40]
Parameters
Remarks Each element gives a count of cycle overruns that have occurred during the
current hour. Elements 0..39 give the count for the corresponding cycle. Element
40 gives the total count over all cycles. All elements are reset to 0 once an hour.
Reset time is not synchronized with wall clock time.

5.358 CRCYCLESKIP

Specific to CEEFB, CEEC300, CEEACE, CEESIMC200E, CEEUOC, CEECN100


Block(s)
Description The number of cancelled cycles for Control recipe (CR) executions in the present hour.
Data Type INT32
Range 0 to 32767
Default 0
Config Load No
Active No
Loadable
Access ViewOnly
Lock
Residence C300(CEEC300), C200E(CEEC200EFB), UOC(CEEUOC), CN100(CEECN100)
Related LSCYCLESKIP
Parameters
Remarks Each element gives a count of Control recipe executions skipped in the present hour.
Elements 0 to 39 give the count for the corresponding cycle. Element 40 gives the
total count over all cycles. All elements are reset to 0 once in an hour. The time is not
synchronized with the current time.

- 631 -
Chapter 5 - Cxxxx Parameters

5.359 CRCYCLESKIP[0..40]

Specific to CEEC300, CEEC200EFB


Block(s)
Description The number of cancelled cycles for Control recipe (CR) executions in the present
hour.
Data Type INT32
Range 0 to 32767
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200E(CEEC200EFB)
Related LSCYCLESKIP[0..40]
Parameters
Remarks Each element gives a count of Control recipe executions skipped in the present
hour. Elements 0 to 39 give the count for the corresponding cycle. Element 40 gives
the total count over all cycles. All elements are reset to 0 once in an hour. The time
is not synchronized with the current time.

5.360 CREATEDBY

Specific to All Blocks


Block(s)
Description Created By – Name of block creator
Data Type String
Range Length: 40 characters
Default Null
Config Load Yes
Active No Yes (CM, SCM, RCM)
Loadable
Access Lock Application Developer
Residence Server
Related DATECREATED, MODIFIEDBY, QUALSTATE, VERSION, VERSIONDATE,
Parameters VERSIONNUM
Remarks Identifies user who created block, if operator security is implemented. Otherwise,
may just show Default login.

Specific to Block(s) UOC


Description Created By
Data Type String
Range N/A

- 632 -
Chapter 5 - Cxxxx Parameters

Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

5.361 CROSSOVERCABLEFAILED

Specific to Block(s) TCMI


Description Crossover Cable Failed
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 633 -
Chapter 5 - Cxxxx Parameters

5.362 CRSKIPPERIOD

Specific to CEEFB, CEEC300, CEEACE, CEESIMC200E, CEEUOC, CEECN100


Block(s)

Description The highest execution period affected by the Control recipe limited for the current hour.
Data Type Enumeration-Period
Exposure Output
Range Enum values of Period enumeration (0 – 31)
Default None
Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence C300(CEEC300), C200E(CEEC200EFB), UOC(CEEUOC), CN100(CEECN100)


Related LSSKIPPERIOD[0..40]
Parameters

Remarks Each element gives the value of the period for which the Control recipe execution skipped
in the current hour. Elements 0 to 39 give the value of the period for which Control recipe
execution skipped. Element 40 gives the maximum value of the period for which Control
recipe execution skipped over all cycles. All elements are reset to 0 once in an hour. Time
is not synchronized with the current time.

5.363 CRSKIPPERIOD[0..40]

Specific to CEEC300, CEEC200EFB


Block(s)
Description The highest execution period affected by the Control recipe limited for the current
hour.
Data Type Enumeration
Range Range of supported values of the PERIOD
Default None
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200E(CEEC200EFB)
Related LSSKIPPERIOD[0..40]
Parameters
Remarks Each element gives the value of the period for which the Control recipe execution
skipped in the current hour. Elements 0 to 39 give the value of the period for which
Control recipe execution skipped. Element 40 gives the maximum value of the
period for which Control recipe execution skipped over all cycles. All elements are
reset to 0 once in an hour. Time is not synchronized with the current time.

- 634 -
Chapter 5 - Cxxxx Parameters

5.364 CSRC[1..10][1..6]

Specific to Block(s) Transition


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

5.365 CSTS[1..8]

Specific to AuxCalc, EnhAuxCalc


Block(s)
Description Expression Statuses
Data Type Enumeration PVSTS
Range 0 BAD
1 UNCERTN
2 NORMAL
3 MANUAL
4 INITACK
5 INITREQ
6 INITBAD
Default BAD (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related C[1..8]
Parameters
Remarks On a Warm restart, Cold restart or when the block is inactivated or when ACE is
repowered, all expression results C[1..8] are set to NaN and its Status CSTS[1...8]
are set to BAD.

- 635 -
Chapter 5 - Cxxxx Parameters

Specific to RegCalc, EnhRegCalc


Block(s)
Description Expression result status for each result C[1] through C[8].
Data Type Enumeration PVSTS
Range 0 BAD
1 UNCERTN
2 NORMAL
3 MANUAL
4 INITACK
5 INITREQ
6 INITBAD
Default Bad (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related C[1..8]
Parameters
Remarks On a Warm restart, Cold restart or when the block is inactivated or when ACE is
repowered, all expression results C[1..8] are set to NaN and its Status CSTS[1...8]
are set to BAD.

5.366 CTEMP

Specific to Block(s) C300, PGM, FIM4, EHPM


Description Controller Temperature °C measured by three different thermometers.
Data Type Float64
Range -55.00 °C to +120.00 °C
Default 0.00 °C
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, Series C FIM, PGM, EHPM
Related Parameters CMAXTEMPCMINTEMP
Remarks

- 636 -
Chapter 5 - Cxxxx Parameters

5.367 CTLACTN

Specific to Block(s) PID, PIDFF


Description Control Action - The output direction of a PID function block (direct or
reverse).
Data Type Enumeration CTLACTN
Range Direct (0) Reverse (1)
Default Reverse (1)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

5.368 CTLEQN

Specific to Block(s) PID-PL, PID, PIDER, PIDFF, OVRDSEL, RATIOCTL, SWITCH.


Description Control Equation Type
Data Type Enumeration CTLEQN
Range EqA (0) EqB (1) EqC (2) EqD (3) EqE (4) EqF (5) EqG (6) ProfitLoop
Default EqA (0)
Config Load Yes
Active Loadable No
Access Lock Engineer / Application Developer
Residence CEE
Related Parameters
Remarks

5.369 CTLINIT

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Control Initialization Request Flag - Used to request one-shot initialization of a
Regulatory Control block. May be written to by a user program or another function.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)

- 637 -
Chapter 5 - Cxxxx Parameters

Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

5.370 CTRLIPADDR

Specific to
Block EIM
Description Controller IP Address
Data Type STRING
Range n/a
Default 0.0.0.0
Config Load Yes
Active
Loadable No
Access Lock AppDevOnly
Residence CEE
Related
Parameters TARGETNAME
This parameter indicates the IP address of the Controller to which the
Remarks destination DSIN block is assigned.

5.371 CTLSTATE

Specific to All Regulatory Control Blocks


Block(s)
Description Control State - Shows the control state of the block.
Data Type Enumeration
Range (0) FWD (1) Hold (2) INIT (3) MAN
Default INIT
Config No
Load
Active No
Loadable

- 638 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This parameter is equivalent to the PATHIND parameter in the TPS-Application
Manager. In the FWD state, the algorithm performs normal forward calculation. If
the point is in INIT state, the algorithm must perform initialization. If the point is in
MAN, the operator controls the output but CV should still be computed for proper
handling of bad control. The Hold state is not supported at this time. .

5.372 CTRLCAPABILITY

Specific to C300
Block(s)
Description Controller Capability
Data Type ENUM
Range 0 - Not determined 1 - 50ms 2 - 20ms 3 - 50ms_EHB 4 - 50ms_Extended
Default 0 - Not determined
Config Load NOLOAD
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CAPABILITY
Parameters
Remarks l PCNT 01 version C300s will have a value of “50ms”.
l PCNT 02 version C300s set up to support the new extended features in
R500 will have a value of "50ms_Extended"

5.373 CTRLCONFIRM

Specific to Most Function Blocks


Block(s)
Description Control Confirmation - Lets you select whether or not the electronic signature
function is to be turned ON or OFF for this object.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Yes
Loadable

- 639 -
Chapter 5 - Cxxxx Parameters

Access Lock Application Developer


Residence SR
Related
Parameters
Remarks Requires an electronic signature license.

Specific to Block(s) UOC


Description Control Confirmation
Data Type Boolean
Range N/A
Default F
Config Load Yes
Active Loadable Yes
Access Lock AppDevOnly
Residence SRSCANAL
Related Parameters
Remarks

5.374 CTRLDESC

Specific to Block(s) ProfitCtl


Description Controller Desc
Data Type STRING
Range NA
Default Profit Controller
Config Load
Active Loadable No
Access Lock ENGINEER
Residence
Related Parameters
Remarks

5.375 CTRLMODE

Specific to PID-PL
Block(s)
Description PV Control Mode - PV operating mode for the Profit Loop PKS control algorithm.
Data Type Enumeration
Range SETPOINT The function block attempts to have the PV track
the SP.
Range The function block attempts to maintain the PV

- 640 -
Chapter 5 - Cxxxx Parameters

between the limits of SPHI and SPLO.


Default SETPOINT
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related CTLEQN, SP,SPHI,SPLO.
Parameters
Remarks 6.284.1 This parameter is applicable only when CTLEQN is set to Profit Loop PKS,
and is ignored in PID control equations.

Specific to Block(s) ProfitCtl


Description Controller Mode
Data Type ENUM
Range NA
Default OFF
Config Load
Active Loadable No
Access Lock VIEWONLY
Residence
Related Parameters
Remarks

5.376 CTRLNAME

Specific to Block(s) ProfitCtl


Description Controller Master Name
Data Type STRING
Range NA
Default PC
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

- 641 -
Chapter 5 - Cxxxx Parameters

5.377 CTRLRESTART

Specific to Block(s) ProfitCtl


Description Control Restart
Data Type BOOL
Range NA
Default False
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

5.378 CTRLSTATE

Specific to Block(s) ProfitCtl


Description Controller BLC State
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

5.379 CTRLSTATUS

Specific to Block(s) ProfitCtl


Description Controller STATUS
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No

- 642 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters
Remarks

5.380 CTRLSTEPPEDFLAG

Specific to Block(s) ProfitCtl


Description Ctrl Stepped Flag
Data Type INT32
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

5.381 CURDEVICEIDX

Specific to C300 FBs


Block(s)
Description Current Device Index
Data Type 16-Bit Unsigned Integer
Range 0-255
Default 1
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300
Related DEVICEIDX
Parameters
Remarks User (hardware) configured FTE Device Index of module (via rotary switches).
Unlike the IP address, this does not change with redundancy role change.

- 643 -
Chapter 5 - Cxxxx Parameters

5.382 CUROBJVALUE

Specific to Block(s) ProfitCtl


Description Obj func. Value
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

5.383 CURHOSTNAME

Specific to
Block ACE
Description Current Host Name
Data Type STRING
Range NA
Default NA
Config Load No
Active
Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters HOSTNAMEPRI, MODHASBKUP

This parameter displays the host name of the node in the Monitoring view. This
parameter is required when the MODHASBKUP parameter is selected and the
Remarks HOSTNAMEPRI parameter is not available for configuration.

5.384 CURHRERRFIFOENTRY

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Current Hour Error FIFO Entries
Data Type UINT32
Range
Default 0

- 644 -
Chapter 5 - Cxxxx Parameters

Config. Load No
Active Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter displays the number of error entries reported by EHBI in the
current hour.

5.385 CURHRRCVFIFOENTRY

Specific to Experion Hiway Bridge (EHB) platform block


Blocks
Description Current Hour Receive FIFO Entries
Data Type UINT32
Range
Default 0
Config. Load No
Active
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The parameter displays the number of receive FIFO (unsolicited writes) entries
reported by EHBI in the current hour.

5.386 CURHRRPTFIFOENTRY

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Current Hour Report FIFO Entries
Data Type UINT32
Range
Default 0
Config. Load No
Active Loadable

- 645 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This parameter displays the number of report entries generated by EHBI in
the current hour.

5.387 CURPINPT

Specific to Block SignalSel


(s)
Description Current number of inputs
Data Type 32-Bit Integer
Range 0 to 6
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related NUMPINPT, PCONN[1..10]
Parameters
Remarks This parameter represents the number of inputs to be considered after
ignoring invalid inputs

5.388 CURPROFILEID

Specific to Block(s) RampSoak


Description Current Profile ID
Data Type Integer
Range 1 to 10
Default 1
Config Load Operator
Active Loadable No
Access Lock No
Residence CEE
Related Parameters
Remarks

- 646 -
Chapter 5 - Cxxxx Parameters

5.389 CURRDESCREF

Specific to Block(s) Step


Description Current Value Reference Descriptor
Data Type Parameter ID
Range
Default
Config Load
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

5.390 CURRELINIDLY

Specific to Control Module in CEE. Not supported in FIM or LIOM.


Block(s)
Description Current Reload Initialization Delay - Counts down executions while the CM
initializes after reload or CEE restart.
Data Type INT32
Range Not applicable (view-only parameter)
Default 0
Config No
Load
Active No
Loadable

- 647 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related RELOADINIDLY INITPENDING RSTRTINIDLY
Parameters
Remarks CURRELINIDLY is normally zero. When nonzero, the CM responds to requests to
read block parameters with a status which instructs the client to hold last fetched
input. Once CURRELINIDLY reaches zero, the CM has performed enough
executions to initialize component block data and starts responding to read
requests with normal status. CURRELINIDLY becomes nonzero in two types of
scenarios.
l The first is a reload scenario in which a CM is loaded to a CEE to which it has
already been loaded. In this scenario, CURRELINIDLY is set equal to
RELOADINIDLY.
l The second scenario is that of a CEE restart, either by RAM Retention Startup,
or by Idle to Run transition following checkpoint restore. In this scenario,
CURRELINIDLY is set equal to the sum of RELOADINIDLY and the scaled
value of CEE.RSTRTINIDLY.
CURRELINIDLY does not start to count down until the CM starts to execute. Thus,
if a CM is left Inactive after reload, or if a CEE is left Idle after restart, the CM will
hold off read clients until the state is changed. Before a CM starts to execute after a
reload or restart the following holds. CM.CURRELINIDLY = CM.RELOADINIDLY + (
CEE.RSTRTINIDLY / CM.PERIOD ) (where the minimum CM.PERIOD is the base
period of the particular controller)

5.391 CURRENTBATCHSIZE

Specific to Block(s) RCM


Description Current Batch Size
Data Type 16-Bit Integer
Range
Default 100
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks

5.392 CURRENTREL

Specific to Block(s) UOC


Description Database Release
Data Type String
Range N/A

- 648 -
Chapter 5 - Cxxxx Parameters

Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks

5.393 CURRENTVERSION

Specific to Block(s) MASTER RECIPE


Description Current Version
Data Type BOOLEAN
Range
Default TRUE
Config Load
Active Loadable Yes
Access Lock APPDEVONLY
Residence CEE, SCAN
Related Parameters
Remarks

5.394 CURREUDESCREF

Specific to Block(s) Step


Description Current Value Reference Engineering Units Descriptor
Data Type Parameter ID
Range
Default
Config Load
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

- 649 -
Chapter 5 - Cxxxx Parameters

5.395 CURRNUMACT

Specific to CEE
Block(s)
Description Number of Activities
Data Type INT32
Range 0-1000
Default 0
Config YES
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related MAXNUMACT, NUMACTCRFAIL, NUMACTCR, ACTAVAIL, CURRNUMACT
Parameters
Remarks This parameter determines the maximum number of Activities that can be
associated with RCMs/SCMs/CRs in the CEE. The maximum value of NUMACT is
1000. If NUMACT is configured as a value greater than 0, then the CEE Activity
Manager (CAM) consumes 1K of the function block memory for Activities and one
Tag name for every Activity. The activity count needs to be large enough to account
for all activities created at the same time in the controller. The following should be
included: • All top level SCMs, RCMs, and Control recipes that are configured with
Activities enabled and currently have an Activity in the Activity Summary (in pre-
execution, execution or post-execution). • Executing child RCMs with Activity
Parents and executing child Control recipes(child SCMs are not included). Note: It is
recommended to set NUMACT to a value that exceeds the number of activities
needed.

5.396 CURRVALREF

Specific to Step
Block(s)
Description Step Current Value Reference
Data Type Parameter Id
Range Any Tag.[Block].Parameter reference
Default “”
Config Load Yes
Active No
Loadable

- 650 -
Chapter 5 - Cxxxx Parameters

Access Lock AppDeveloper Only


Residence SR
Related CURRVALTREND, TRENDINTRVAL
Parameters
Remarks Identifies a parameter as the Current Value for the Step. The identified parameter
is monitored and shown on the SCM Table view associated with the Step. Example
values are CMName.Pid.PV and SCMName.INALM.

5.397 CURRVALTREND

Specific to Step
Block(s)
Description Step Current Value add to Trend
Data Type Boolean
Range Off - CURRVALREF not added to Trend On - CURRVALREF is added to Trend
Default Off
Config Load Yes
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related CURREUDESCREF, CURRVALREF, TRENDINTRVAL
Parameters
Remarks Specifies whether the parameter identified by CURRVALREF is added to the built-in
Trend display that is part of the SCM Table view. Note that the built-in Trend display
is not supported in the pilot release.

5.398 CURSEGID

Specific to Block(s) RampSoak


Description Current Segment ID.
Data Type Integer
Range 1 to 60
Default N/A
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters CURPROFILEID
Remarks

- 651 -
Chapter 5 - Cxxxx Parameters

5.399 CURSEGTYP

Specific to Block(s) RampSoak


Description Current Segment Type (Ramp or Soak).
Data Type Enumeration
Range Ramp (0) Soak (1)
Default Ramp (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

5.400 CURTIME

Specific to C300, C200, FTEB, FIM4, EHG, EHPM, TCMI ACE, SIM_C200, IOLINK, SIMIOLIM,
Block(s) CEEC300, FFLINK, PGM
Description Current Time - Indicates current system time, as communicated to the ACE
supervisory controller, Control Processor Module in the C200 Controller, C300
Controller and Simulation Control Environment controller from the Server. The
format is MM/DD/YY HH:MM:SS.
Data Type Time
Range 01/01/1972 and later
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300, C200, ACE, SIM_C200, FTEB, IOLINK, SIMIOLIM, CEEC300, FIM4, PGM,
EHPM
Related DAYDAYLIGHTTIMEHOURMINUTEMONTHADVDEVALM.TM, TIMEZONE, YEAR
Parameters
Remarks If the controller resides in a different time zone than the Server, the value provided
in CURTIME might be different than those provided by YEAR, MONTH, DAY, HOUR,
MINUTE, and SECOND. The controller's time zone residency is specified by the
TIMEZONE AND DAYLIGHTTIME parameters.

Specific to Block(s) IOLIM, Secondary IOLIM, FIM


Description Current Time
Data Type TIME
Range N/A

- 652 -
Chapter 5 - Cxxxx Parameters

Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM, FIM
Related Parameters
Remarks Shows the current wall clock time for the associated module.

Specific to Block(s) EIM


Description Current System Time.
Data Type TIME
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Current System Time for the associated module.

Specific to CPM200,CPM, CPM200S, ACE, SIM-C200, C300, C300SEC, FIM, FIMS, IOLINK,
Block(s) IOLIM, IOLIMS, SIMIOLIM, FTEB, FTEBS, CEEC300, FIM4, FIM4SEC, FFLINK, EHG,
EHGS, CEEUOC, CEECN100
Description Current System Time
Data Type Time
Range -
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, C200, ACE, SIM-C200, C300, C300SEC, FIM, FIMS, UOC, UOCSEC, CN100,
CN100SEC
Related
Parameters
Remarks Current Time. Shows the current wall clock time for the associated module.

Specific to UOC
Block(s)
Description Current System Time
Data Type TIME
Range
Default 0
Config Load No

- 653 -
Chapter 5 - Cxxxx Parameters

Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Current system time. Note that the displayed time is adjusted based on the
user's time zone configuration.

5.401 CUSTPCRANGE

Specific to Block(s) MAP


Description Map block custom param code range
Data Type INT32
Range 19968 - 29968
Default 19968
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters NUMFUNREF, NUMBLKREF, NUMPRMREF, LASTPCUSED
Remarks

5.402 CUSTYPHELPTXT

Specific to Block(s) CEEC300,CEEFB,CEEACEFB,CEESIMC200FB


Description Custom Type Help Text
Data Type String
Range 1 - 256
Default Custom Data Blocks (CDBs) and Phase Blocks
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks

- 654 -
Chapter 5 - Cxxxx Parameters

5.403 CUTOFF.LM

Specific to Totalizer, Pulse Input Totalizer, Deadtime


Block(s)
Description Zero-Flow Cutoff Limit in Engineering Units - Allows the user to specify a cutoff
limit such that, when the value of the RATE falls below this limit, PV remains
constant (no accumulation).
Data Type 64-Bit Real Number
Range NaN, or greater-than or equal-to 0.0.
Default Deadtime: NaN Totalizer, Pulse Input Totalizer: 0.0
Config Load Yes
Active No
Loadable
Access Lock Totalizer, Pulse Input Totalizer: Engineer Deadtime: Supervisor
Residence CEE
Related
Parameters
Remarks

5.404 CV

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDER PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RegSummer, RemCas, RatioBias, RatioCtl,
RegCalc, and Switch.
Description Calculated Value - The result (calculated value) of the function blocks. The value
may be in Percent or Engineering Units, depending on the function block.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config No
Load
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related RATIOCTL Block: SP X1 X2
Parameters
Remarks For RATIOCTL block, CV is the traget value for controlled flow (X1). Note:
Occasionally runtime OP and CV values exceed the set CVEUHI. For the digital
algorithm to approximate the ideal analog form, the CV must be allowed to cover a
wide range without clipping. Otherwise, in some instances the response times may
be altered. However, the CVEUHI and CVEULO values will be used to scale the
output to a percentage.

- 655 -
Chapter 5 - Cxxxx Parameters

5.405 CV.ABSDEVIATION

Specific to Block(s) PROFITCTLIN


Description CV ABSDEVIATION
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS, CV.DEVIATION, CV.VALUE CVHIHGLIMIT, CV.LOWLIMIT
Remarks Arrayed parameters of size NUMBEROFCVS

5.406 CV.ACTIVEHL

Specific to Block(s) PROFITCTLIN


Description CV HighLimit(Active)
Data Type FLOAT64
Range NA
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS , CV.ACTIVELL
Remarks For each CV, this is an active high limit. It is an array of size NUMBEROFCVS
.

5.407 CV.ACTIVELL

Specific to Block(s) PROFITCTLIN


Description CV LowLimit(Active)
Data Type FLOAT64
Range NA
Default
Config Load No
Active Loadable No

- 656 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related Parameters NUMBEROFCVS , CV.ACTIVEHL
Remarks For each CV, this is an active low limit. It is an array of size NUMBEROFCVS .

5.408 CV.ACTIVEVAL

Specific to Block(s) PROFITCTLIN


Description Active source value
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Active value of CV. This is an array of size NUMBEROFCVS.

5.409 CV.BADCOUNT

Specific to Block PROFITCTLIN


(s)
Description No.of Bad counts
Data Type INT32
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Count-down of y_badok This is an array of size NUMBEROFCVS . Each CV has
its own value.

- 657 -
Chapter 5 - Cxxxx Parameters

5.410 CV.BadPV

Specific to Block(s) PROFITCTLIN


Description CV BadPV
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.411 CV.BadPVShedTime

Specific to Block(s) PROFITCTLIN


Description Bad PV Shed Time(sec) Alarm
Data Type UINT32
Range 0 to 65535
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

5.412 CV.BADPVSHEDTIMEFL

Specific to Block(s) PROFITCTLIN


Description CV BADPVSHEDTIMEFL
Data Type BOOL
Range FALSE, TRUE
Default FALSE
Config Load No
Active Loadable No

- 658 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.413 CV.BADREADSALLOWED

Specific to PROFITCTLIN
Block(s)
Description No.Bad reads allowed
Data Type INT32
Range NA
Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Number of bad reads allowed. This is an array of size NUMBEROFCVS i.e. per CV
you can configure this parameter.

5.414 CV.BALANCEFACTOR

Specific to Block(s) PROFITCTLIN


Description Balance Factor for integrating CV
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Balance Factor for integrating CV's >0. This is an array of size
NUMBEROFCVS .

- 659 -
Chapter 5 - Cxxxx Parameters

5.415 CV.BALANCETARGET

Specific to Block(s) PROFITCTLIN


Description Position in intervals where SS value is computed
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.416 CV.BIAS

Specific to Block(s) PROFITCTLIN


Description Bias for Simulation
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.417 CV.CALCBLKINTERVALS

Specific to Block PROFITCTLIN


(s)
Description Calc. blk intervals
Data Type INT16
Range ±32767
Default 0
Config Load No
Active Loadable No

- 660 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related NUMBEROFCVS
Parameters
Remarks CV Blocking interval in the prediction horizon. Arrayed parameters of size
NUMBEROFCVS

5.418 CV.CLLOOPRESPTIME

Specific to Block(s) PROFITCTLIN


Description Closed Loop Resp Time
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Specified by users for integrators. Arrayed parameter of size
NUMBEROFCVS.

5.419 CV.CONSTRAINTTYPE

Specific to Block(s) PROFITCTLIN


Description Constraint Type
Data Type ENUM
Range 0: free, +/-1: fixed hi/lo (hard), +/-2: fixed hi/lo (soft), 3: setpoint
Default FREE
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS.

- 661 -
Chapter 5 - Cxxxx Parameters

5.420 CV.CONTROLPRIORITY

Specific to Block(s) PROFITCTLIN


Description Submodel priority for each CV
Data Type ENUM
Range High (0) Normal (1) Low (2)
Default Normal
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS.

5.421 CV.CONTROLTHISCV

Specific to PROFITCTLIN
Block(s)
Description Control This CV
Data Type ENUM
Range Yes (0) No (1)
Default YES
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Control this CV value, YES: control it, NO: DO NOT control it. Arrayed parameters
of size NUMBEROFCVS.

5.422 CV.CRITICAL

Specific to Block(s) PROFITCTLIN


Description Critical
Data Type BOOL
Range False, True
Default F
Config Load Yes

- 662 -
Chapter 5 - Cxxxx Parameters

Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.423 CV.CVBIAS

Specific to Block(s) PROFITCTLIN


Description CV Bias
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.424 CV.CVINDEX

Specific to Block(s) PROFITCTLIN


Description CV Index
Data Type INT16
Range ±32767
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 663 -
Chapter 5 - Cxxxx Parameters

5.425 CV.DCSVALUE

Specific to Block(s) PROFITCTLIN


Description DCS Value
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.426 CV.DECOUPLERATIO

Specific to Block(s) PROFITCTLIN


Description Decouple Ratio
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.427 CV.DELTAACTSOFTHILIM

Specific to Block(s) PROFITCTLIN


Description CV Active DeltaHighSoftLimit
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No

- 664 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Active high soft limit as a delta from y_H(Real World)

5.428 CV.DELTAACTSOFTLOLIM

Specific to Block(s) PROFITCTLIN


Description CV Active DeltaLowSoftLimit
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Active soft limit as a delta from y_L(Real World)

5.429 CV.DELTASOFTHL

Specific to Block(s) PROFITCTLIN


Description Delta Soft HILIM
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 665 -
Chapter 5 - Cxxxx Parameters

5.430 CV.DELTASOFTLL

Specific to Block(s) PROFITCTLIN


Description Delta Soft LOLIM
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.431 CV.DESC

Specific to Block(s) PROFITCTLIN


Description Description
Data Type STRING
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.432 CV.DESIREDVALUE

Specific to Block(s) PROFITCTLIN


Description Desired value
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No

- 666 -
Chapter 5 - Cxxxx Parameters

Access Lock OPERATOR


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.433 CV.DEVIATION

Specific to Block(s) PROFITCTLIN


Description CV DEVIATION
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS, CV.ABSDEVIATION, CV.VALUE CVHIHGLIMIT,
CV.LOWLIMIT
Remarks Arrayed parameters of size NUMBEROFCVS

5.434 CV.DISTURBANCE

Specific to Block(s) PROFITCTLIN


Description DISTURBANCE for Simulation
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 667 -
Chapter 5 - Cxxxx Parameters

5.435 CV.DISTURBANCEFLAG

Specific to Block(s) PROFITCTLIN


Description Disturbance Est.
Data Type BOOL
Range NA
Default F
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.436 CV.DISTURESTTUNING

Specific to Block(s) PROFITCTLIN


Description Distur Est Tuning
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.437 CV.ENGGHIGHLIMIT

Specific to Block(s) PROFITCTLIN


Description Engg High limit
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No

- 668 -
Chapter 5 - Cxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.438 CV.ENGGLOWLIMIT

Specific to Block(s) PROFITCTLIN


Description Engg Low limit
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.439 CV.ENGGUNITS

Specific to Block(s) PROFITCTLIN


Description Engineering units
Data Type STRING
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 669 -
Chapter 5 - Cxxxx Parameters

5.440 CV.ER_C

Specific to Block PROFITCTLIN


(s)
Description Color for ERR Tol
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.441 CV.ERRORTOLERANCE

Specific to Block(s) PROFITCTLIN


Description Opt error tol
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.442 CV.EXECUTIONSTATUS

Specific to Block(s) PROFITCTLIN


Description Execution status
Data Type ENUM
Range Inactive (0) Active (1)
Default INACTIVE
Config Load Yes

- 670 -
Chapter 5 - Cxxxx Parameters

Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.443 CV.FF2FBPERFRAT_C

Specific to Block PROFITCTLIN


(s)
Description Color for FF2FB PERF RAT
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.444 CV.FF2FBPERFRATIO

Specific to Block(s) PROFITCTLIN


Description FF/FB perf ratio
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 671 -
Chapter 5 - Cxxxx Parameters

5.445 CV.FILTEREDBIAS

Specific to Block(s) PROFITCTLIN


Description Filtered bias
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.446 CV.FILTEREDRAMP

Specific to Block(s) PROFITCTLIN


Description Filtered ramp
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.447 CV.FUNNELTYPE

Specific to Block PROFITCTLIN


(s)
Description FUNNEL TYPE
Data Type ENUM
Range STD-FUNNEL (0) NARROW-OPENING (1) USE-DECOUPLE-RATIO (2) RAMP-
FUNNEL (3)
Default STD-FUNNEL
Config Load Yes
Active Loadable No

- 672 -
Chapter 5 - Cxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.448 CV.FUTUREVAL

Specific to Block(s) PROFITCTLIN


Description Predicted value at 4 tau
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.449 CV.FUTUREVAL_C

Specific to Block PROFITCTLIN


(s)
Description Color for Fut.Val
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

- 673 -
Chapter 5 - Cxxxx Parameters

5.450 CV.HIGHLIMIT

Specific to Block(s) PROFITCTLIN


Description Entered CV high limit
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.451 CV.HIGHLIMIT_C

Specific to Block PROFITCTLIN


(s)
Description Color for HL
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.452 CV.HLERRORWEIGHT

Specific to Block(s) PROFITCTLIN


Description HILIM error weight
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes

- 674 -
Chapter 5 - Cxxxx Parameters

Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.453 CV.HLRAMP

Specific to Block(s) PROFITCTLIN


Description HighLimit Ramp
Data Type ENUM
Range NO-RAMP (0) UP-RAMP (1) DIAMONDY (2) DIAMONDYH (3) DOWN-RAMP
(4)
Default NO-RAMP
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.454 CV.HLRAMPRATE

Specific to Block(s) PROFITCTLIN


Description CV high limit ramp rate change
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 675 -
Chapter 5 - Cxxxx Parameters

5.455 CV.HOLDINTEGRATOR

Specific to Block(s) PROFITCTLIN


Description Hold Integrator
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.456 CV.HOLDINTEGRATORENUM

Specific to Block(s) PROFITCTLIN


Description Enum for Hold Integrator
Data Type ENUM
Range Yes (0) No (1)
Default YES
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.457 CV.INITMODE

Specific to Block(s) PROFITCTLIN


Description Initialization mode
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No

- 676 -
Chapter 5 - Cxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.458 CV.INTEGRATINGCV

Specific to Block(s) PROFITCTLIN


Description INTEGRATING CV
Data Type BOOL
Range F, T
Default F
Config Load Yes
Active Loadable No
Access Lock APPDEVONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.459 CV.LASTBAD

Specific to Block(s) PROFITCTLIN


Description Last CV Bad?
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 677 -
Chapter 5 - Cxxxx Parameters

5.460 CV.LASTGOOD

Specific to Block(s) PROFITCTLIN


Description Last good value
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.461 CV.LINEARCOEFF

Specific to Block(s) PROFITCTLIN


Description Eco. obj. linear coeff
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.462 CV.LINEARCOEFF_C

Specific to Block PROFITCTLIN


(s)
Description Color for Linear Coeff
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No

- 678 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.463 CV.LLERRORWEIGHT

Specific to Block(s) PROFITCTLIN


Description LOLIM error weight
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.464 CV.LLRAMP

Specific to Block(s) PROFITCTLIN


Description LowLimit Ramp
Data Type ENUM
Range NO-RAMP (0) UP-RAMP (1) DIAMONDY (2) DIAMONDYH (3) DOWN-RAMP
(4)
Default NO-RAMP
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 679 -
Chapter 5 - Cxxxx Parameters

5.465 CV.LLRAMPRATE

Specific to Block(s) PROFITCTLIN


Description CV low limit ramp rate change
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.466 CV.LOWLIMIT

Specific to Block(s) PROFITCTLIN


Description Entered CV low limit
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters NUMBEROFCVS, CV.HIGHLIMIT
Remarks Arrayed parameters of size NUMBEROFCVS

5.467 CV.LOWLIMIT_C

Specific to Block PROFITCTLIN


(s)
Description Color for LL
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No

- 680 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.468 CV.MINFUNNEL

Specific to Block(s) PROFITCTLIN


Description Min funnel opening
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.469 CV.MODELINDEX1

Specific to Block(s) PROFITCTLIN


Description Model Index Information
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 681 -
Chapter 5 - Cxxxx Parameters

5.470 CV.MODELINDEX2

Specific to Block(s) PROFITCTLIN


Description Model Index Information
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.471 CV.MODELTYPE

Specific to Block(s) PROFITCTLIN


Description Model Type
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.472 CV.MOVECAUSE

Specific to Block(s) PROFITCTLIN


Description Move Explanation
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No

- 682 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.473 CV.MOVECAUSEDESC

Specific to Block(s) PROFITCTLIN


Description Move Description
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.474 CV.MOVEINDEPMOVEDESC1

Specific to Block(s) PROFITCTLIN


Description CVMove cause variables description
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 683 -
Chapter 5 - Cxxxx Parameters

5.475 CV.MOVEINDEPMOVEDESC2

Specific to Block(s) PROFITCTLIN


Description CVMove cause variables description
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.476 CV.NAME

Specific to Block(s) PROFITCTLIN


Description Name
Data Type STRING
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock APPDEVONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.477 CV.NEWVALUEFLAG

Specific to Block(s) PROFITCTLIN


Description Async CV New Value Flag
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No

- 684 -
Chapter 5 - Cxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.478 CV.NEWVALUEPINCONN

Specific to Block(s) PROFITCTLIN


Description CV New Value IN Connector
Data Type INCONN
Range NA
Default
Config Load
Active Loadable
Access Lock ViewOnly
Residence
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS. This is an internal parameter.

5.479 CV.NOISEVARIANCE

Specific to Block(s) PROFITCTLIN


Description NOISEVARIANCE for Simulation
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 685 -
Chapter 5 - Cxxxx Parameters

5.480 CV.NUMBEROFBLOCKS

Specific to Block(s) PROFITCTLIN


Description No. of blocks
Data Type INT32
Range ±2147483647
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.481 CV.PERFRATIO

Specific to Block(s) PROFITCTLIN


Description Performance ratio
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.482 CV.PERFRATIO_C

Specific to Block PROFITCTLIN


(s)
Description Color for Value
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No

- 686 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.483 CV.PREDSSVALUE

Specific to Block(s) PROFITCTLIN


Description SS Value
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.484 CV.PREDVALUE

Specific to Block(s) PROFITCTLIN


Description Pred Value
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 687 -
Chapter 5 - Cxxxx Parameters

5.485 CV.PREDVALUE_C

Specific to Block PROFITCTLIN


(s)
Description Color for Pred. Val
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.486 CV.PRIORITY

Specific to Block(s) PROFITCTLIN


Description Priority
Data Type ENUM
Range High (0) Normal (1) Low (2)
Default NORMAL
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.487 CV.PROCESSHL

Specific to Block(s) PROFITCTLIN


Description Process high limit
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes

- 688 -
Chapter 5 - Cxxxx Parameters

Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.488 CV.PROCESSHLPINCONN

Specific to Block(s) PROFITCTLIN


Description CV PROCESS HL input Connector
Data Type INCONN
Range NA
Default
Config Load
Active Loadable
Access Lock ViewOnly
Residence
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS. This is an internal parameter.

5.489 CV.PROCESSLL

Specific to Block(s) PROFITCTLIN


Description Process low limit
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 689 -
Chapter 5 - Cxxxx Parameters

5.490 CV.PROCESSLLPINCONN

Specific to Block(s) PROFITCTLIN


Description CV EULL input Connector
Data Type INCONN
Range
Default
Config Load
Active Loadable
Access Lock ViewOnly
Residence
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS. This is an Internal parameter.

5.491 CV.PVTRACK

Specific to Block(s) PROFITCTLIN


Description Track PV
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.492 CV.PVTRACKENUM

Specific to Block(s) PROFITCTLIN


Description Status of PV Val
Data Type ENUM
Range Yes (0) No (1)
Default Yes
Config Load No
Active Loadable No

- 690 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.493 CV.PVVALRESET

Specific to Block(s) PROFITCTLIN


Description Reset PV Val
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.494 CV.PVVALSTATUS

Specific to PROFITCTLIN
Block(s)
Description Status of PV Val
Data Type ENUM
Range VALID (0) HOLD (1) BAD (2) EXT (3) CLAMP_HI (4) CLAMP_LO (5) HI (6) LO (7) ROC
(8) FREEZE (9) OBSOLETE (10) REF (11) NA (12) INITIALIZING (13)
Default VALID
Config Load No
Active No
Loadable
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

- 691 -
Chapter 5 - Cxxxx Parameters

5.495 CV.PVVALSTATUS_C

Specific to Block PROFITCTLIN


(s)
Description Color for PV Val Status
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.496 CV.QUADRATICCOEFF

Specific to Block(s) PROFITCTLIN


Description Econ obj. quad coeff
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.497 CV.RAMPRATE

Specific to Block(s) PROFITCTLIN


Description Ramp rate
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes

- 692 -
Chapter 5 - Cxxxx Parameters

Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.498 CV.RAMPVALUE

Specific to Block(s) PROFITCTLIN


Description Ramp value
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.499 CV.RATEBALANCE

Specific to Block(s) PROFITCTLIN


Description INTEGRATOR RATE BALANCE
Data Type BOOL
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 693 -
Chapter 5 - Cxxxx Parameters

5.500 CV.READVALUE

Specific to Block(s) PROFITCTLIN


Description Read value (PV)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.501 CV.READVALUEPINCONN

Specific to Block(s) PROFITCTLIN


Description CV input Connector
Data Type INCONN
Range
Default
Config Load
Active Loadable
Access Lock ViewOnly
Residence
Related Parameters
Remarks This is an Internal parameter

5.502 CV.SCALINGFACTOR

Specific to Block(s) PROFITCTLIN


Description Scaling value
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No

- 694 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.503 CV.SE_C

Specific to Block PROFITCTLIN


(s)
Description Color for SE
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.504 CV.SETPOINT

Specific to Block(s) PROFITCTLIN


Description Setpoint
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 695 -
Chapter 5 - Cxxxx Parameters

5.505 CV.SETPOINTRAMP

Specific to Block(s) PROFITCTLIN


Description SetPoint Ramp
Data Type ENUM
Range NO-RAMP (0) UP-RAMP (1) DIAMONDY (2) DIAMONDYH (3) DOWN-RAMP
(4)
Default NO-RAMP
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.506 CV.SETPOINTVAL

Specific to Block(s) PROFITCTLIN


Description Setpoint
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.507 CV.SHADOWPRICE

Specific to Block(s) PROFITCTLIN


Description Shadow Price
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No

- 696 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.508 CV.SHADOWPRICEDISPLAY

Specific to Block(s) PROFITCTLIN


Description Shadow/Error Price of SS CV constraint
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.509 CV.SSFILTEREDRAMP

Specific to Block(s) PROFITCTLIN


Description SS Filter Ramp Val
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 697 -
Chapter 5 - Cxxxx Parameters

5.510 CV.SSSTATEESTFILTER

Specific to Block(s) PROFITCTLIN


Description Filter for SS State Est
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.511 CV.SSVALUE

Specific to Block(s) PROFITCTLIN


Description Optimal SS Val
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.512 CV.SSVALUE_C

Specific to Block PROFITCTLIN


(s)
Description Color for SSValue
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No

- 698 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.513 CV.STATEEST

Specific to Block(s) PROFITCTLIN


Description State Estimation Flag
Data Type ENUM
Range DEFAULT (0) ON (1) ON_MAN (2) OFF (3)
Default Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence NUMBEROFCVS
Related Parameters Arrayed parameters of size NUMBEROFCVS
Remarks

5.514 CV.STATEESTDISPLAY

Specific to Block(s) PROFITCTLIN


Description State Estimation On/Off Display
Data Type ENUM
Range ON (0) D-OFF (1) D-ON (2) OFF (3)
Default ON
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 699 -
Chapter 5 - Cxxxx Parameters

5.515 CV.STATUS

Specific to PROFITCTLIN
Block(s)
Description Status
Data Type ENUM
Range NA (0) GOOD (1) PREDICTED (2) DROPPED (3) BAD (4) CRITICAL (5) INIT (6)
ERROR7 (7) ERROR8 (8) ERROR9 (9) ERROR10 (10) INIT_GOOD (11) INIT_
PREDICTED (12) INIT_DROPPED (13) INIT_BAD (14) INIT_CRITICAL (15) INIT_INIT
(16)
Default NA
Config No
Load
Active No
Loadable
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.516 CV.STATUSDISP_C

Specific to Block PROFITCTLIN


(s)
Description Color for Status Disp
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

- 700 -
Chapter 5 - Cxxxx Parameters

5.517 CV.STATUSDISPLAY

Specific to PROFITCTLIN
Block(s)
Description CV Status Display
Data Type ENUM
Range DROP (0) CRIT (1) PRED (2) INIT (3) INIT-C (4) WOUND_UP (5) WOUND_UP-C (6)
GOOD (7) GOOD-C (8) BAD (9) EXT (10) EXT-C (11) CLAMP_HI (12) CLAMP_HI-C
(13) CLAMP_LO (14) CLAMP_LO-C (15) HIGH (16) HIGH-C (17) LOW (18) LOW-C
(19) ROC (20) ROC-C (21) FREEZE (22) FREEZE-C (23) DROP-SC (24) CRIT-SC (25)
Default DROP
Config No
Load
Active No
Loadable
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.518 CV.TREATASBAD

Specific to Block(s) PROFITCTLIN


Description Unbiased pred val
Data Type BOOL
Range NA
Default
Config Load No
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.519 CV.UNBIASEDMODELVAL

Specific to Block(s) PROFITCTLIN


Description Unbiased pred val
Data Type FLOAT64
Range ±1.7E+308

- 701 -
Chapter 5 - Cxxxx Parameters

Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.520 CV.UPDATEFREQUENCY

Specific to Block(s) PROFITCTLIN


Description UPDATE FREQUENCY
Data Type ENUM
Range >= (0) < (1)
Default >=
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.521 CV.VALUE

Specific to Block(s) PROFITCTLIN


Description Value
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 702 -
Chapter 5 - Cxxxx Parameters

5.522 CV.VALUE_C

Specific to Block PROFITCTLIN


(s)
Description Color for Value
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFCVS
Parameters
Remarks Arrayed parameters of size NUMBEROFCVS

5.523 CV.WINDUPSTATUS

Specific to Block(s) PROFITCTLIN


Description Windup status
Data Type ENUM
Range ERROR0 (0) NORMAL (1) HI (2) LO (3) HILO (4)
Default NORMAL
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

5.524 CV[1..8]

Specific to Fanout
Block(s)
Description Calculated Variable for function blocks with Multiple Outputs - The result
(calculated value) of the function block. There is one CV for each output.
Data Type 64-Bit Real Number
Range N/A
Default NaN

- 703 -
Chapter 5 - Cxxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

5.525 CVEUHI

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RegSummer, RemCas, RatioBias, RegCalc,
and Switch.
Description Calculated Variable (CV) High Range (in Engineering Units) - This value
corresponds to 100% of full-scale value.
Data Type 64-Bit Real Number
Range Greater-than or equal-to CVEULO
Default 100.0
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related CVEULO
Parameters
Remarks If NUMSEC >0, CV high and low ranges are configured for PID or for other blocks
they track the ranges of the secondary's input (that is, the other end of the control
output connection). CV high and low ranges track the secondary’s XEUHI and
XEULO in the blocks which have X input. If NUMSEC =0, CVEUHI & CVEULO can be
configured by the engineer. Note: Occasionally runtime OP and CV values exceed
the set CVEUHI. For the digital algorithm to approximate the ideal analog form, the
CV must be allowed to cover a wide range without clipping. Otherwise, in some
instances the response times may be altered. However, the CVEUHI and CVEULO
values will be used to scale the output to a percentage.

- 704 -
Chapter 5 - Cxxxx Parameters

5.526 CVEUHI[1..8]

Specific to Fanout
Block(s)
Description Calculated Variable (CV) High Range (in Engineering Units) - This value
corresponds to 100% of full-scale value.
Data Type 64-Bit Real Number
Range Greater-than or equal-to CVEULO[1..8]
Default 100.0
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related CVEULO[1..8]
Parameters
Remarks If NUMSEC = 0, CV high and low ranges are configured for PID; otherwise, they
track the ranges of the secondary's input (that is, the other end of the control
output connection). If NUMSEC = 0, CV high and low ranges track the XEUHI and
XEULO in the blocks which have X input Note: Occasionally runtime OP and CV
values exceed the set CVEUHI. For the digital algorithm to approximate the ideal
analog form, the CV must be allowed to cover a wide range without clipping.
Otherwise, in some instances the response times may be altered. However, the
CVEUHI and CVEULO values will be used to scale the output to a percentage.

5.527 CVEULO

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RegSummer, RemCas, RatioBias, RegCalc,
and Switch.
Description Calculated Variable (CV) Low Range (in Engineering Units) - This value corresponds
to 0% of full scale.
Data Type Real
Range Less-than or equal-to CVEUHI
Default 0.0
Config Yes
Load
Active No
Loadable

- 705 -
Chapter 5 - Cxxxx Parameters

Access Lock Engineer


Residence CEE
Related CVEUHI
Parameters
Remarks If NUMSEC >0, CV high and low ranges are configured for PID or for other blocks
they track the ranges of the secondary's input (that is, the other end of the control
output connection). CV high and low ranges track the secondary’s XEUHI and
XEULO in the blocks which have X input. If NUMSEC =0, CVEUHI & CVEULO can be
configured by the engineer.

5.528 CVEULO[1..8]

Specific to Fanout
Block(s)
Description Calculated Variable (CV) Low Range (in Engineering Units) - This value corresponds
to 0% of full scale.
Data Type Real
Range Less-than or equal-to CVEUHI[1..8]
Default 0.0
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CVEUHI
Parameters
Remarks If NUMSEC = 0, CV high and low ranges are configured; otherwise, they track the
ranges of the secondary's input (that is, the other end of the control output
connection). If NUMSEC = 0, CV high and low ranges track the XEUHI and XEULO
in the blocks which have X input.

5.529 CVGAIN

Specific to Block(s) ProfitCtl


Description CV Gain
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No

- 706 -
Chapter 5 - Cxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters
Remarks

5.530 CVINIT

Specific to Block(s) RegCalc


Description Calculated Variable (CV) under initialization conditions.
Data Type Real
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters
Remarks

5.531 CVINITSRC

Specific to Block(s) RegCalc


Description CVINIT (Calculated Variable under initialization conditions) source selector.
Data Type Enumeration REGCALCSELECTOR
Range CVINIT to C8STS (0 - 27)
Default X1 (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 707 -
Chapter 5 - Cxxxx Parameters

5.532 CVORFB

Specific to Block RegCalc


(s)
Description Calculated Variable (CV) under override feedback conditions (that is, in the
non-selected path)
Data Type Real
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

5.533 CVORFBSRC

Specific to Block(s) RegCalc


Description Calculated Variable under override feedback conditions (CVORFB) source
selector.
Data Type Enumeration REGCALCSELECTOR
Range X1 to C8STS (0 - 27)
Default X1 (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

5.534 CVSRC

Specific to Block(s) RegCalc


Description Calculated Variable (CV) output source selector.
Data Type Enumeration REGCALCSELECTOR
Range X1 C8STS (0 - 27)
Default X1 (0)

- 708 -
Chapter 5 - Cxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

5.535 CVTYPE

Specific to All Regulatory Control Blocks


Block(s)
Description Calculated Variable (CV) Type - Defines whether CV value is in Percent or
Engineering Units.
Data Type Enumeration
Range (0) Engineering Units (1) Percent
Default Engineering Units
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The CV is in Percent for PID type blocks with equations A to D. For PID equation E
and all other regulatory control blocks, the CV is in Engineering Units

5.536 CWRITEAVGPPS

Specific to Block EHPM


(s)
Description This parameter shows the average parameters per second load during peer-to-
peer write operation.
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Loadable Yes

- 709 -
Chapter 5 - Cxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related -
Parameters
Remarks -

5.537 CWRITEMAXPPS

Specific to EHPM
Block(s)
Description This parameter shows the maximum parameters per second load during peer-
to-peer write operation.
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Loadable Yes
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

5.538 CX[1..10]

Specific to Block(s) ENHREGCALC


Description Calculated Input - Defines the scaling factor for each input.
Data Type Float64
Range 0 to 10
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 710 -
Chapter 5 - Cxxxx Parameters

5.539 CYCLEACTIVE[1..24]

Specific to Block QIPACTERM


Description Material Transfer Cycle Active
Data Type Boolean
Range Off(0) Inactive
On(1) Active
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 5 of the Status 1 byte in the input assembly for the
designated position [1-24].

5.540 CYCLEACTIVE[1..200]

Specific to Block QIPACCHAN


Description Material Transfer Cycle Active
Data Type Boolean
Range Off(0) Inactive
On(1) Active
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
RelatedParameters:
Remarks This is the value of bit 5 of the Status 1 byte in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

- 711 -
Chapter 5 - Cxxxx Parameters

5.541 CYCLEOPT[1..NUMPROFILES]

Specific to RampSoak
Block(s)
Description Cycle Option: Allows automatic switch over to next profile, or run the same profile in
a cyclic manner
Data Type Integer
Range 0 Single Currently selected
(or running) profile
will stop after
executing the last
ramp soak pair
1 Cyclic Currently selected
(or running) profile
will keep running in
a cyclic manner. For
example, after
executing the last
ramp soak segment,
the block will start
again from the
beginning of the
start segment
configured for the
profile.
2 RoundRobin After executing the
last ramp soak
segment, the block
will start execution of
the next profile in
the order.
Default Cyclic (1)
Config Yes
Load
Active No
Loadable

- 712 -
Chapter 5 - Cxxxx Parameters

Access Engineer
Lock
Residence CEE
Related
Parameters
Remarks When the RAMPSOAK block is restarted by
changing the mode to AUTO, the block restarts
and the starting point is based on the setting of
CYCLEOPT.
l If CYCLEOPT = SINGLE or CYCLIC, the
block restarts from the beginning of the
current profile.
l If CYCLEOPT = ROUNDROBIN, the blocks
restarts from the beginning of the first
profile. Every consecutive profile
configured for ROUNDROBIN is executed
in order. The execution will never stop
until the next profile is configured for
SINGLE or CYCLIC action. This means
that after the last ramp/soak pair in the
last profile is executed, the execution of
the first profile begins and so on until the
next profile is configured for SINGLE or
CYCLIC action.

5.542 CYCLESKIPMAX

Specific to MR
Block(s)
Description Number of added cycles for Control recipe creation; maximum across all the past
Control recipes (not including the currently running Control recipes).
Data Type INT32
Range 0 to 4294967296
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related None
Parameters
Remarks Shows the worst case Control recipe creation impact for this Master recipe
(number of cycles missed and the execution delayed). This parameter resets on
activation and is updated only at the Control recipe removal.

- 713 -
Chapter 5 - Cxxxx Parameters

5.543 CYCLETIME

Specific to Block(s) PosProp, PidPosProp


Description Cycle time for commanding raise or lower pulses (in seconds).
Data Type Real
Range 0.020 to 1000.0
Default 10.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

5.544 CYCLETIME[0..63]

Specific to Block(s) PCDI_MASTER


Description Cycle Time in milliseconds
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 714 -
CHAPTER

6 DXXXX PARAMETERS

6.1 D[1..5] 722


6.2 D[1..10] 723
6.3 D1 723
6.4 D2 724
6.5 DABLOCKSINCM 724
6.6 DAMPING 725
6.7 DAREF 725

6.8 DATA[1..32] 726


6.9 DATAACQ1 726
6.10 DATAACQ2 727
6.11 DATAACQ3 727
6.12 DATAACQBLOCKID1 728
6.13 DATABLOCK 728
6.14 DATAOK[1..4] 729
6.15 DATAOK[1..24] 729
6.16 DATAOK[1..200] 730
6.17 DATAQUEUESZ 730
6.18 DATATYPE 730
6.19 DATECREATED 731
6.20 DATELOADED 732
6.21 DATEMODIFIED 732
6.22 DATEPTIMPORT 733
6.23 DAY 733
6.24 DAYLIGHTTIME 734
6.25 DBLOADCLIENT 734
6.26 DBTRACEENABLE 735
6.27 DBTRACEFLAGS1..6 736
6.28 DBVALID 736
6.29 DBVALID [1..40] 737
6.30 DBVALIDCMD 737
6.31 DBVALID[1..45] 738
6.32 DCPREAD 738

- 715 -
Chapter 6 - Dxxxx Parameters

6.33 DCPSCAN 739


6.34 DCPSETFACTORYRESET 739
6.35 DCPSETIPADDR 740
6.36 DCPSETNAME 740
6.37 DCPSETSIGNAL 741
6.38 DEADBAND 741
6.39 DEADBAND1 742
6.40 DEADBAND2 742
6.41 DEADTIME 743
6.42 DEADTIMEBIAS 743
6.43 DEBOUNCE 744
6.44 DEBOUNCETIME_DI_C 744
6.45 DEBUG 745
6.46 DEBUGFLAGSET 746

6.47 DECONF 746


6.48 DEFAULTBATCHSIZE 747
6.49 DEFLTREFWARNING 747
6.50 DEFLTREFWARNRPRT 748
6.51 DEFTIMOUT 748
6.52 DELAY 749
6.53 DELAYPRIMARY[1..200] 749
6.54 DELAYPRIMARY[1..24] 750
6.55 DELAYTABLE[1..60] 750
6.56 DELAYTIME 750
6.57 DELAYTYPE 751
6.58 DELCV 752
6.59 DELIVEREDWGT[1..200] 752
6.60 DELTATIME 753
6.61 DENSTEAM 753
6.62 DENWATER 753
6.63 DENWATERREF 754
6.64 DEPLOYMENTINCOMPLETESF 754
6.65 DESC 755
6.66 DESIGNEXEC 756
6.67 DEV 756
6.68 DEVADDR 757
6.69 DEVALM.ALL 757
6.70 DEVALM.DB 758
6.71 DEVALM.DBU 758

- 716 -
Chapter 6 - Dxxxx Parameters

6.72 DEVALM.FL 759


6.73 DEVALM.PR 759
6.74 DEVALM.SV 759
6.75 DEVALM.TM 760
6.76 DEVALM.TMO 760
6.77 DEVALM.TP 761
6.78 DEVCTL 761
6.79 DEVFLAG[0..N] 761
6.80 DEVFLAG 762
6.81 DEVGENUINE 762
6.82 DEVHIALM.DB 763
6.83 DEVHIALM.DBU 763
6.84 DEVHIALM.FL 764
6.85 DEVHIALM.PR 764

6.86 DEVHIALM.SV 765


6.87 DEVHIALM.TM 765
6.88 DEVHIALM.TMO 766
6.89 DEVHIALM.TP 766
6.90 DevHigh.DeadBandUnits 767
6.91 DevHigh.DeadBandValue 767
6.92 DEVHIGH.FL 768
6.93 DevHigh.OffDelayTimeSec 768
6.94 DevHigh.OnDelayTimeSec 768
6.95 DevHigh.Priority 769
6.96 DevHigh.Severity 769
6.97 DevHigh.TripPoint 770
6.98 DEVICE 770
6.99 DEVICEID[0..7] 771
6.100 DEVICEIDX 771
6.101 DEVICELOCATION 773
6.102 DEVICEREVNO[0..7] 773
6.103 DEVICETYPE 774
6.104 DEVLM 774
6.105 DEVLOALM.DB 775
6.106 DEVLOALM.DBU 775
6.107 DEVLOALM.FL 776
6.108 DEVLOALM.PR 776
6.109 DEVLOALM.SV 776
6.110 DEVLOALM.TM 777

- 717 -
Chapter 6 - Dxxxx Parameters

6.111 DEVLOALM.TMO 777


6.112 DEVLOALM.TP 778
6.113 DevLow.DeadBandUnits 778
6.114 DevLow.DeadBandValue 779
6.115 DEVLOW.FL 779
6.116 DevLow.OffDelayTimeSec 780
6.117 DevLow.OnDelayTimeSec 780
6.118 DevLow.Priority 781
6.119 DevLow.Severity 781
6.120 DevLow.TripPoint 782
6.121 DEVSPCBIT[0..135] 782
6.122 DEVSTS[0..15] 783
6.123 DEVSUPCMDS[0 - 15][0 - 39] 783
6.124 DEVTM 784

6.125 DEVTYPE 784


6.126 DFNPHWYEM 785
6.127 DHCPENABLE 786
6.128 DHCPENDADDR 786
6.129 DHCPSTARTADDR 787
6.130 DI[1..4] 787
6.131 DI[1..10] 788
6.132 DIAGREQSENT[0..15] 788
6.133 DIAGREQRSPRCVD[0..15] 788
6.134 DICHNLNAME 789
6.135 DIGFILTER[0..numChans-1] 789
6.136 DIGFILTER [0..NUMCHANNELS-1] 790
6.137 DIHASENAME 790
6.138 DIMODE 791
6.139 DIPTEXECST 791
6.140 DIPVMAP[0..15] 792
6.141 DIRECTSYNC 792
6.142 DIREGISTERD[ ] 793
6.143 DISABLEBATTERYALARM 793
6.144 DISCONNDEVNAME 794
6.145 DISCREP 794
6.146 DISCRTINPUT1[1..4] 795
6.147 DISCRTINPUT2[1..4] 795
6.148 DISCRTINPUT3[1..4] 796
6.149 DISP_C 796

- 718 -
Chapter 6 - Dxxxx Parameters

6.150 DISPADJPARAM 796


6.151 DISPLAYEDSTATUS 797
6.152 DISPLAYSTATE 797
6.153 DISPLAYSUBSCRMAXPPS 798
6.154 DISPOVRLOAD 798
6.155 DISPPOS 799
6.156 DISPRATEAVG 799
6.157 DISPRATEMAX 800
6.158 DISPSUBCACHEFRFCTR 800
6.159 DISQSECCMD 801
6.160 DISRC [1..10] 801
6.161 DISTS[1..10] 802
6.162 DITYPE 802
6.163 DLCNBSLOT 803

6.164 DL_RPI 803


6.165 DLINKDLRROLE 804
6.166 DLINK1FAILED 804
6.167 DLINK1FRAMECRCERR 805
6.168 DLINK1LANIDERR 806
6.169 DLINK1MACADDR 807
6.170 DLINK1LASTACTIVE 807
6.171 DLINK2LASTACTIVE 808
6.172 DLINK2MACADDR 808
6.173 DLINK1RXRATE 809
6.174 DLINK1RXRATELIMIT 810
6.175 DLINK1RXRATEMAX 810
6.176 DLINK1SILENT 811
6.177 DLINK1TXRATE 812
6.178 DLINK1TXRATEMAX 813
6.179 DLINK2FAILED 815
6.180 DLINK2FRAMECRCERR 816
6.181 DLINK2LANIDERR 816
6.182 DLINK2SILENT 817
6.183 DLINK2RXRATE 818
6.184 DLINK2RXRATELIMIT 819
6.185 DLINK2RXRATEMAX 820
6.186 DLINK2TXRATE 821
6.187 DLINK2TXRATEMAX 822
6.188 DLINKDUPEADDR 823

- 719 -
Chapter 6 - Dxxxx Parameters

6.189 DLINKENABLE 824


6.190 DLINKHELP2 825
6.191 DLINKHELP 825
6.192 DLINKNETWORKERR 826
6.193 DLINKIPADDR 826
6.194 DLINKIPADDRMASK 827
6.195 DLINKIPADDRMASKSTR 827
6.196 DLINKIPADDRSTR 828
6.197 DLINKPARTNERNOTVISIBLE 828
6.198 DLINKNETWORKERR 829
6.199 DLINKRDNPROTO 830
6.200 DLINKRXERR 830
6.201 DLINKRXRATE 831
6.202 DLINKRXRATEMAX 832

6.203 DLINKTXERR 833


6.204 DLINKTXRATEMAX 834
6.205 DLINKVLANID 835
6.206 DLRACTIVESUP 835
6.207 DLRACTIVESUPPRI 836
6.208 DLRCURRENTROLE 836
6.209 DLRFAULTCNT 837
6.210 DLRINTERVAL 837
6.211 DLRNODECOUNT 838
6.212 DLRPRECEDENCE 838
6.213 DLRRESETFAULT 838
6.214 DLRRINGFAULT 839
6.215 DLRRINGMODE 839
6.216 DLRRINGSTATE 840
6.217 DLRTIMEOUT 840
6.218 DLRVERIFYFAULTLOC 841
6.219 DLYTIME 841
6.220 DO[1..3] 842
6.221 DOMSO 842
6.222 DOMSO[0..numChans-1] 843
6.223 DONEFL 843
6.224 DOOP 843
6.225 DOPTEXECST 844
6.226 DOSTYPE 844
6.227 DOTNETVER[0..1] 845

- 720 -
Chapter 6 - Dxxxx Parameters

6.228 DOTYPE 846


6.229 DOVALSTS[1..2] 847
6.230 DOWNLINKFAIL 847
6.231 DP 848
6.232 DPBIAS 848
6.233 DPENGUNIT 848
6.234 DPSLOPE 849
6.235 DPV 849
6.236 DRAWINGINFO 850
6.237 DRIVERNAME 850
6.238 DRIVERNAME 850
6.239 DRVMEMFREE 851
6.240 DRVMEMRESERVED 851
6.241 DRVMEMUSED 852

6.242 DS_SET 852


6.243 DSBLSYNCCMD 852
6.244 DSMAPBLKID 853
6.245 DSMAPCONNVAL 854
6.246 DSPARAMALIAS 854
6.247 DSPARAMCOUNT 854
6.248 DSPARAMRCBBLOB 855
6.249 DSPARAMRCBBLOBCRC 855
6.250 DSPARAMRCBBLOBSIZE 856
6.251 DSPARAMRCBBLOBARRCOUNT 856
6.252 DSSOURCE 856
6.253 DTANORM 857
6.254 DTAOFFSET 857
6.255 DTASCALE 858
6.256 DTIME 858
6.257 DTIMEAVG 859
6.258 DTIMEAVGCOMP 859
6.259 DTIMEMAX 860
6.260 DTIMEMIN 860
6.261 DTIMESTD 860
6.262 DTIMESTDPRC 861
6.263 DUPIOLADDR 861
6.264 DUPIPIECNETWORK 862
6.265 DV.ACTIVEPROCESSVALUE 862
6.266 DV.ACTIVEVALUE 863

- 721 -
Chapter 6 - Dxxxx Parameters

6.267 DV.BIAS 863


6.268 DV.CRITICAL 863
6.269 DV.DESC 864
6.270 DV.DVINDEX 864
6.271 DV.ENGGUNITS 865
6.272 DV.EXECSTATUS 865
6.273 DV.ISBAD 865
6.274 DV.NAME 866
6.275 DV.PREVIOUSVAL 866
6.276 DV.PVVALRESET 867
6.277 DV.PVVALSTATUS 867
6.278 DV.PVVALSTATUS_C 867
6.279 DV.READPROCESSVAL 868
6.280 DV.READVALUE 868

6.281 DV.READVALUEPINCONN 869


6.282 DV.SCALINGFACTOR 869
6.283 DV.STARTVALUE 869
6.284 DV.STATUS 870
6.285 DV.STATUSDISP 870
6.286 DV.STATUSDISP_C 871
6.287 DV.TYPICALMOVESIZE 871
6.288 DV.USETHISDV 871
6.289 DV.VALUE 872
6.290 DV.WINDUPSTATUS 872
6.291 DVRNGEXT 873
6.292 DYNPEERALLOC 873
6.293 DYNSTATE[1.255] 874

6.1 D[1..5]

Specific to PID-PL
Block(s)
Description Denominator Coefficients - Array of coefficients defining the denominator
polynomial in the Laplace transfer function model of the process.
Data Type Float64
Range
Default 1
Config Yes
Load

- 722 -
Chapter 6 - Dxxxx Parameters

Active No
Loadable
Access Engineer
Lock
Residence CEE
Related N[1..5], NUMCOEFDEN, NUMCOEFNUM, PROCGAINEU, PROCGAINPCT,
Parameters PROCDEADTIME, RESETMODEL, UPDATEMODEL.
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. D[1] is the coefficient preceeding the s^0 (constant) term while D[5] is the
coefficient preceeding the s^4 term. After the function block is loaded, this
parameter must be updated (see UPDATEMODEL) before any change in its value is
implemented. This parameter is applicable only when CTLEQN is set to Profit Loop
PKS, and is ignored in PID control equations.

6.2 D[1..10]

Specific to Block(s) DEADTIME, AUXSUMMER


Description Bias for associated block input (P[1..10]). There is one bias for each input.
Data Type Real Number
Range
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters DEADTIME: C1, DELAYTIME, AUXSUMMER: P[1..10]
Remarks

6.3 D1

Specific to Block(s) Deadtime


Description Bias for the calculation of DELAYTIME.
Data Type Real Number
Range
Default 0.0
Config Load Yes
Active Loadable No

- 723 -
Chapter 6 - Dxxxx Parameters

Access Lock Supervisor


Residence CEE
Related Parameters C1DELAYTIME
Remarks

6.4 D2

Specific to Block(s) Deadtime


Description Bias for the P2 input.
Data Type Real Number
Range
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

6.5 DABLOCKSINCM

Specific to DIGACQ
Block(s)
Description Number Of blocks in CM for System Detail Display.
Data Type 8-Bit Integer
Range 1 and above
Default 1
Config Load YES
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks This parameter is used in system detail display to display only the selected number
of blocks and hide the not required blocks.

- 724 -
Chapter 6 - Dxxxx Parameters

6.6 DAMPING

Specific to AICHANNEL (PM I/O); AICHANNEL (Series C I/O)


Block(s)
Description Damping. Specifies the first-order Process Variable (PV) filtering option for the
Smart Transmitter.
Data Type 32-Bit Real Number
Range For Pressure Transmitter (SPT_DP, SPT_GP, SPT_AP): 0.0, 0.16, 0.32, 0.48, 1.00, 2.0,
4.0, 8.00, 16.0, 32.0, NaN For Temperature Transmitter (STT): 0.0, 0.30, 0.70, 1.5,
3.10, 6.3, 12.7, 25.5, 51.1, 102.3, NaN For Magnetic Flowmeter Transmitter (SFM):
0.0, 0.5,1.0, 2.0, 3.0, 4.0, 5.0, 10.0, 50.0, 100, NaN
Default 0.0
Config No
Load
Active No
Loadable
Access Engineer
Lock
Residence IOM
Related
Parameters
Remarks This parameter is only exposed if ASSOCIOPTYP is STI-MV. It is a view-only
parameter when the STI point execution state PTEXECST is Active. Users can also
implement PV filtering by using the TF parameter. However, DAMPING is the
preferred parameter for PV filtering. Any real number in the range of damping
specified in the transmitter's User Manual can be used. If DAMPING has been
configured at the transmitter, the STI IOP adjusts the entered value to one of the
values in the Range shown above for the appropriate transmitter type. However,
the IOP will not adjust the damping value for Magnetic Flowmeter Transmitters
(SFM).

6.7 DAREF

Specific to Block(s) EIM


Description DA Reference
Data Type
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ERDBSR
Related Parameters
Remarks

- 725 -
Chapter 6 - Dxxxx Parameters

6.8 DATA[1..32]

Specific to CHGEXEC
Block(s)
Description Connects to change monitored input data and publishes a consistent copy of
inputs for use by downstream logic.
Data Type Boolean
Range 0 Off
1 On
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other function block
Residence CEE
Related LASTDATA[1..32]ALTSYNCCMD
Parameters
Remarks

6.9 DATAACQ1

Specific to HRBALG_REG block


Blocks
Description DATAACQ FB Reference 1
Data Type BLOCKID
Range Not applicable
Default Null
Config. Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter holds a reference to the DATAACQ1 block in the emulation CM
which holds the HRBALG_REG instance. This parameter connector is used in
algorithm emulations DAS/PIDNORM/PIDSPC/PIDCM/PIDCMA for PV handling.

- 726 -
Chapter 6 - Dxxxx Parameters

6.10 DATAACQ2

Specific to HRBALG_REG block


Blocks
Description DATAACQ FB Reference 2
Data Type BLOCKID
Range Not applicable
Default Null
Config. Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter holds a reference to the DATAACQ2 block in the emulation CM
which holds the HRBALG_REG instance. This parameter connector is used in DAS
algorithm emulation for SP handling.

6.11 DATAACQ3

Specific to HRBALG_REG block


Blocks
Description DATAACQ3 FB Reference 3
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the DATAACQ block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

- 727 -
Chapter 6 - Dxxxx Parameters

6.12 DATAACQBLOCKID1

Specific to CB AI Algorithm HRB


Blocks
Description DATACQFBConnector
Data Type BLOCKID
Range Not applicable

Default DATAACQ block


Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter is a Function Block connector to DATAACQ block, which is
residing in the same CM

6.13 DATABLOCK

Specific to SCM, RCM


Block(s)
Description Data Block Type
Data Type BLOCKID
Range
Default Null
Config Yes
Load
Active No
Loadable
Access Application Developer Only
Lock
Residence CEE
Related DISPADJPARAMEVTOPTFORMULAPARAMEVTOPTREPORTPARAM
Parameters
Remarks Represents the DATA Block which has been added to the SCM/RCM to provide a
shared parameter definition between an RCM, contained PHASE Blocks, and the
lower level RCM/SCMs. The parameter represents the DATA Block itself, such as
myRCM.DATA; however, the Configuration form will display the Phase Block Type of
the selected block. The description intentionally does not match the parameter. The
‘Data Block Type’ is used rather than ‘DATA Block’ to be consistent with what is
shown to the user - Type Name.

- 728 -
Chapter 6 - Dxxxx Parameters

6.14 DATAOK[1..4]

Specific to JAGXCHAN
Block(s)
Description Data OK/Error Indication
Data Type Boolean
Range Off(0) Data
not OK
On(1) Data OK

Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 15 of the status word in the floating point input
assembly for the designated scale [1..4].

6.15 DATAOK[1..24]

Specific to QIPACTERM
Block
Description Instrument Data Integrity OK
Data Type Boolean
Range Off(0) Integrity
Bad
On(1) Integrity
OK
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 1 of the Status 1 byte in the input assembly for
the designated position [1-24].

- 729 -
Chapter 6 - Dxxxx Parameters

6.16 DATAOK[1..200]

Specific to QIPACCHAN
Block
Description Instrument Data Integrity OK
Data Type Boolean
Range Off(0) Integrity Bad
On(1) Integrity OK
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 1 of the Status 1 byte in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

6.17 DATAQUEUESZ

Specific to Block(s) OPCUASRVUOC


Description Maximum Data Queue Sizes
Data Type UINT32
Range 0 to 4294967295
Default 100
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

6.18 DATATYPE

Specific to Block(s) EIM


Description Data Type
Data Type ENUM
Range NA
Default UNDEFINED

- 730 -
Chapter 6 - Dxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR, ERDBSR
Related Parameters
Remarks

6.19 DATECREATED

Specific to All Blocks


Block(s)
Description Created On – Date FB Created on.
Data Type TIME
Range N/A
Default 0
Config Load Yes
Active No Yes (CM, SCM, RCM)
Loadable
Access Lock Application Developer
Residence Server
Related CREATEDBY, MODIFIEDBY, QUALSTATE, VERSION, VERSIONDATE, VERSIONNUM
Parameters
Remarks Shows date and time template was created. If this block is in Version Control
System, shows date and time initial version of template was created.

Specific to Block All Blocks


(s)
Description Creation Date - Shows date and time template was created.
Data Type String
Range Mm/dd/yyyy hh:mm:ss
Default Null
Config Load Yes
Active Loadable No Yes (CM, SCM, RCM)
Access Lock Application Developer Only
Residence Server
Related CRCYCLESKIP[0..40]MODIFIEDBY, QUALSTATEACTCREATETYPE, CREATEDBY,
Parameters CREATEDBY
Remarks If this block is in Version Control System, shows date and time initial version of
template was created.

- 731 -
Chapter 6 - Dxxxx Parameters

Specific to Block(s) UOC


Description Created On
Data Type TIME
Range
Default 0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

6.20 DATELOADED

Specific to Server
Block(s)
Description Date Model Last loaded - Specifies the last date that the model was loaded to the
server.
Data Type String
Range Mm/dd/yyyy hh:mm:ss
Default Null
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence SCAN
Related
Parameters
Remarks Array of the date and time the model was last loaded to this server for each model.
Displayed on the Load dialog as Date Loaded To Server.

6.21 DATEMODIFIED

Specific to Block(s) Generic Comp


Description Date Last Changed - Specifies the last date that the model was changed.
Data Type String
Range Mm/dd/yyyy hh:mm:ss
Default Null
Config Load No
Active Loadable No

- 732 -
Chapter 6 - Dxxxx Parameters

Access Lock Application Developer Only


Residence SCAN
Related Parameters
Remarks Displayed on the Load dialog as the Date Last Changed.

6.22 DATEPTIMPORT

Specific to EHPM, TCMI


Block(s)
Description Date of last point imported into ERDB for the EHPM Controller.
Data Type STRING
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SRAL
Related N/A
Parameters
Remarks The parameter value is set by the EHPM Point Import Utility and it shows the last
time points were imported into ERDB for the EHPM Controller.

6.23 DAY

Specific to Block(s) CEEC300, ACE, CPM, SIM_C200, CEEUOC, CEECN100


Description Defines the current day component of the Controller's local time.
Data Type 32-Bit Integer
Range 1 to 31
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE, C200, SIM_C200, UOC(CEEUOC), CN100(CEECN100)
Related Parameters DAYLIGHTTIME, TIMEZONE
Remarks

- 733 -
Chapter 6 - Dxxxx Parameters

6.24 DAYLIGHTTIME

Specific to CEEC300, ACE, CPM, SIM_C200, CEEUOC, CEECN100


Block(s)
Description Daylight Time - Specifies whether the Controller's local time is currently in Daylight
Savings Time or not.
Data Type Boolean
Exposure Output
Range Off (0) - Daylight Savings Time is inactive On (1) - Daylight Savings Time is active
Default Off
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300(CEEC300), ACE, C200, SIM_C200, UOC(CEEUOC), CN100(CEECN100)
Related DAY, HOUR, MINUTE, MONTH, SECOND, TIMEZONE, YEAR
Parameters
Remarks This parameter affects the determination of the Controller's local time, as
represented by the YEAR, MONTH, DAY, HOUR, MINUTE, and SECOND parameters.

6.25 DBLOADCLIENT

Specific to C200, C300, FIM4, EHG, LIOM, EHPM, UOC ACE, SIM_C200, OPC, ICG, SIMIOLIM,
Block(s) PGM
Description Id. of Load Client
Data Type String
Range Length: 80 characters, N/A
Default 0
Config Load No, Yes
Active No
Loadable
Access Lock Application Developer Only
Residence C300, C200, ACE, SIM_C200, SIMIOLIM, FIM,4 EHG, LIOM, OPC, ICG, PGM, EHPM,
NOLOAD
Related
Parameters
Remarks This is used as a transaction management mechanism to makesure that load vs.
checkpoint (or other similar operations) do not corrupt each other.

- 734 -
Chapter 6 - Dxxxx Parameters

6.26 DBTRACEENABLE

Specific to ELCN_NODE
Block(s)

Description This parameter indicates whether GTAC-directed diagnostic tracing is enabled.


Data Type Boolean
Range True/False
Default False
Config Load No
Active No
Loadable

Access Lock Engineer


Residence Platform Block
Related DBTRACEFLAGS1..DBTRACEFLAGS6
Parameters

Remarks If this value is true, it will trigger a SoftFail on the node, so that operators/engineers are
aware that diagnostic tracing is enabled.

- 735 -
Chapter 6 - Dxxxx Parameters

6.27 DBTRACEFLAGS1..6

Specific to ELCN_NODE
Block(s)

Description A numeric unsigned 32-bit value indicating 32 flags each of which can govern
diagnostic tracing of a specific area of interest.
Data Type UINT32
Range 0.. 4294967295
Default 0
Config Load False
Active False
Loadable

Access Lock Engineer


Residence Platform Block
Related DBTRACEFLAGS1..DBTRACEFLAGS6
Parameters

Remarks DBTRACEFLAGS1 governs tracing for platform application.


DBTRACEFLAGS2 governs tracing for UEA display application.
DBTRACEFLAGS3 governs tracing for lcnp4emu application.
DBTRACEFLAGS4 governs tracing for ELCNNODE type dependent application as
follows:
ENIM- epni2emu, NG- engiAemu, EHB- ehbemu, ENB- enbemu
DBTRACEFLAGS5 governs tracing for ELCNNODE types as follows:

NG- engiBemu, else- ftesysapp application


DBTRACEFLAG6 governs tracing for platform_block application

6.28 DBVALID

Specific to All PM I/O Modules and All Series C I/O Modules


Block(s)
Description Database Valid. Shows whether or not the user has validated the Input/Output
Module (IOM) database.
Data Type Enumeration
Range On (0): Database is valid.
Off (1): Database is invalid.
Default Off (1)
Config Load No
Active Loadable No

- 736 -
Chapter 6 - Dxxxx Parameters

Access Lock Engineer


Residence IOP
Related N/A
Parameters
Remarks The IOM must have a valid database before it can be set to RUN.

6.29 DBVALID [1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Database Valid
Data Type Enumeration
Range Valid (0): Database is valid
Invalid (1): Database is not valid
--- (2): The IOP is not configured
Default Invalid (1)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks This parameter indicates whether or not the user has validated the IOP/IOM
database configuration. The IOP/IOM cannot be set to RUN unless the database is
valid. The index of this array (1 to 40) corresponds to the IOP/IOM Number.

6.30 DBVALIDCMD

Specific to Block(s) All PM I/O Modules and All Series C I/O Modules
Description Validate I/O Processor Database.
Data Type Boolean
Range On (0) Validate IOP database has been initiated.
Off (1) No command.
Default Off (1)
Config Load No
Active Loadable No

- 737 -
Chapter 6 - Dxxxx Parameters

Access Lock Engineer


Residence IOLIM
Related Parameters N/A
Remarks Command to validate the IOM's database.

6.31 DBVALID[1..45]

Specific to IOLINK
Block(s)
Description Database Valid. Shows whether or not the user has validated the Input/Output
Processor (IOP) database, where the index of this array corresponds to the number
of the IOP.
Data Type Enumeration
Range VALID (0): Database is valid.
INVALID (1): Database is invalid.
--- (2): The IOP is not configured.
Default INVALID (1)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks The IOP must have a valid database before it can be set to RUN.

6.32 DCPREAD

Specific to Block(s) UOC


Description Read PROFINET DCP
Data Type BLOB
Range

Default

Config Load No
Active Loadable

Access Lock Engineer


Residence UOC
Related Parameters PROFINETENABLE
Remarks

- 738 -
Chapter 6 - Dxxxx Parameters

6.33 DCPSCAN

Specific to Block(s) UOC


Description Scan PROFINET Devices
Data Type Boolean
Range On/Off
Default Off
Config Load No
Active Loadable

Access Lock Engineer


Residence UOC
Related Parameters PROFINETENABLE
Remarks

6.34 DCPSETFACTORYRESET

Specific to Block(s) UOC


Description Factory Reset PROFINET Device
Data Type BLOB
Range

Default

Config Load No
Active Loadable

Access Lock Engineer


Residence UOC
Related Parameters PROFINETENABLE
Remarks

- 739 -
Chapter 6 - Dxxxx Parameters

6.35 DCPSETIPADDR

Specific to Block(s) UOC


Description Set PROFINET Device IP Address
Data Type BLOB
Range

Default

Config Load No
Active Loadable

Access Lock Engineer


Residence UOC
Related Parameters PROFINETENABLE
Remarks

6.36 DCPSETNAME

Specific to Block(s) UOC


Description Set PROFINET Device Name
Data Type BLOB
Range

Default

Config Load No
Active Loadable

Access Lock Engineer


Residence UOC
Related Parameters PROFINETENABLE
Remarks

- 740 -
Chapter 6 - Dxxxx Parameters

6.37 DCPSETSIGNAL

Specific to Block(s) UOC


Description Signal PROFINET Device
Data Type BLOB
Range

Default

Config Load No
Active Loadable

Access Lock Engineer


Residence UOC
Related Parameters PROFINETENABLE
Remarks

6.38 DEADBAND

Specific to Block(s) GE, GT, LE, LT


Description Deadband Value-Defines the value of the deadband for Comparison
Functions.
Data Type 64-Bit Real
Range Greater-than or equal-to 0.
Default 0.005
Config Load Yes
Active Loadable Yes
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

Specific to Block(s) CEEFB, CEEACEFB, CEESIMC200FB, CEEC300, CEEUOC, CEECN100


Description Memory limit Deadband
Data Type INT32
Exposure Output
Range Greater-than or equal-to 0.
Default 0
Config Load Yes
Active Loadable Yes

- 741 -
Chapter 6 - Dxxxx Parameters

Access Lock Application Developer


Residence CEE
Related
Parameters
Remarks Deadband Value-Defines the value of the deadband for Comparison
Functions.

6.39 DEADBAND1

Specific to Block(s) EQ, NE


Description Deadband Value #1 - Defines the value of the (inner) deadband.
Data Type 64-Bit Real
Range Greater-than or equal-to 0. Less-than or equal-to DEADBAND
Default 0.005
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

6.40 DEADBAND2

Specific to Block(s) EQ, NE


Description Deadband Value #2 - Defines the value of the (outer) deadband.
Data Type 64-Bit Real
Range Greater-than or equal-to DEADBAND1
Default 0.01
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 742 -
Chapter 6 - Dxxxx Parameters

6.41 DEADTIME

Specific to HRBALG_REG block


Blocks
Description DEADTIME FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the DEADTIME block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

Specific to Block(s) ProfitCtl


Description Dead time
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

6.42 DEADTIMEBIAS

Specific to Block(s) ProfitCtl


Description Dead time bias
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No

- 743 -
Chapter 6 - Dxxxx Parameters

Access Lock ENGINEER


Residence NOLOAD
Related Parameters
Remarks

6.43 DEBOUNCE

Specific to DICHANNEL (PM I/O) ; DICHANNEL (Series C I/O)


Block(s)
Description Contact Debounce Time. Defines the length of time in milliseconds that an input
must remain in a new state for it to be declared as a valid event by the DISOE IOM
Data Type 8-Bit Unsigned Integer
Range 0 to 50ms
Default 10ms
Config Yes
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOM
Related N/A
Parameters
Remarks This parameter is only exposed if the PM I/O channel block is associated with a
DISOE IOM and PNTFORM = FULL. This parameter is only exposed if the DIMODE =
SOE and DI channel block is associated with a Series C DI-SOE IOM and EVTOPT =
SOE.

ATTENTION For UIO-2 DI channel, this parameter is only exposed when


the EVTOPT parameter is configured as "SOE."

6.44 DEBOUNCETIME_DI_C

Specific to UIO
Block(s)

Description Debounce Time


Data Type UINT32
Range This parameter is the length of time an input must remain in a new state for it to be
declared in the new state. This value is currently not user configurable.
Default 10 ms
Config Yes
Load

- 744 -
Chapter 6 - Dxxxx Parameters

Active No
Loadable

Access AppDevOnly
Lock

Residence CEE
Related
Parameters

Remarks This parameter is the length of time an input must remain in a new state for it to be
declared as a valid event by the UIO IOM.

Specific to UIO
Block(s)

Description Debounce Time


Data Type UINT32
Range 0 to 50 ms
Default 10 ms
Config Load Yes
Active
Loadable

Access Lock AppDevOnly


Residence IOM Block
Related
Parameters

Remarks The length of time an input must remain in a new state before it is declared in the new
state. This value is currently not user configurable

6.45 DEBUG

Specific to Block(s) All IO Channels


Description Spare for debug information
Data Type Integer
Range N/A
Default 0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 745 -
Chapter 6 - Dxxxx Parameters

6.46 DEBUGFLAGSET

Specific to C300, PGM, FIM4, EHPM


Block(s)
Description Debug Flag Enabled. See Remarks.
Data Type Boolean
Range On, Off
Default Off
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related SOFTFAIL
Parameters
Remarks This parameter indicates a Soft Fail condition, which indicates that the image
loaded to the module was built with one or more debug flags asserted. When debug
flags are asserted, the image is not a standard release image. Such an image
should never be running on a module that is on process (unless both customer
and Honeywell representativies understand the ramifications and risks of doing
so.)

6.47 DECONF

Specific to AICHANNEL, HAICHANNEL (PM I/O) ; AICHANNEL (Series C I/O)


Block(s)
Description Digitally Enhanced (DE) Configuration Mode. Specifies the mode of the DE
communication protocol that the transmitter will use to send data to this point.
Data Type Enumeration
Range ANALOG (0): Not supported.
PV (1): Transmits only the Process Variable (PV)
- 4-byte format.
PV_SV (2): Transmits the PV and Secondary
Variable (SV) - 4-byte format.
PV_DB (3): Transmits the PV and the transmitter
database (DB) - 6-byte format.
PV_SV_DB (4): Transmits the PV, SV, and DB - 6-byte
format.
Default PV_SV_DB (4)
Config Load Yes
Active No
Loadable

- 746 -
Chapter 6 - Dxxxx Parameters

Access Lock Engineer


Residence IOM
Related
Parameters
Remarks This parameter is only exposed if the ASSOCIOPTYP is STI-MV. We recommend
using the DECONF selection PV_DB or PV_SV_DB because both offer database
mismatch detection and on process mismatch recovery.

6.48 DEFAULTBATCHSIZE

Specific to Block(s) RCM


Description Default Batch Size
Data Type 16-Bit Integer
Range
Default 100
Config Load Yes
Active Loadable No
Access Lock EngineerApplication Developer
Residence CEE
Related Parameters
Remarks

6.49 DEFLTREFWARNING

Specific to PHASE
Block(s)
Description Warning message for Formula Parameter Populate Default Parameters
Data Type Static String
Range
Default “Warning: Setting Default Value/Parameter References will overwrite all current
values”
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence
Related X_DEFLTFRMPARAMREF X_DEFLTVALREF
Parameters
Remarks This parameter is not visible on PHASE Blocks designated as the DATA Block.
Excluded from Copy, Propagation, Import/Export and Bulk Build.

- 747 -
Chapter 6 - Dxxxx Parameters

6.50 DEFLTREFWARNRPRT

Specific to PHASE
Block(s)
Description Warning message for Report Parameter Populate Default Parameters
Data Type Static String
Range
Default “Warning: Setting Default References will overwrite all current values”
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence
Related X_DEFLTRPRTPARAMREF
Parameters
Remarks This parameter is not visible on PHASE Blocks designated as the DATA Block.
Excluded from Copy, Propagation, Import/Export and Bulk Build.

6.51 DEFTIMOUT

Specific to PCDI_MASTER
Block(s)
Description Time Out
Data Type 32-Bit Unsigned Integer
Range 50 to 60,000
Default 1000
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related
Parameters
Remarks Sets the Modbus request timeout period in milliseconds. This value is used for all
serial devices, unless overridden by a serial device. The valid range for this setting
is 50 to 60, 000 milliseconds.

- 748 -
Chapter 6 - Dxxxx Parameters

6.52 DELAY

Specific to Block(s) MAINIBV


Description Main valve open cmd delay
Data Type 16-Bit Unsigned Integer
Range >0
Default 0
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

6.53 DELAYPRIMARY[1..200]

Specific to QIPACCHAN
Block
Description Waiting to Start Primary Overlapped Feed
Data Type Boolean
Range Off(0) Not Waiting
On(1) Waiting
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 13 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

- 749 -
Chapter 6 - Dxxxx Parameters

6.54 DELAYPRIMARY[1..24]

Specific to QIPACTERM
Block
Description Waiting to Start Primary Overlapped Feed
Data Type Boolean
Range Off(0) Not Waiting
On(1) Waiting
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 13 of the Status 2 word in the input assembly for the
designated position [1-24].

6.55 DELAYTABLE[1..60]

Specific to Block(s) Deadtime


Description Delay Table.
Data Type Real Number
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMIOMNUMLOC
Remarks

6.56 DELAYTIME

Specific to Block(s) 2oo3, Delay, MVote, Ondelay, Offdelay, Watchdog


Description Delay in seconds
Data Type Integer
Range 0-8000 seconds

- 750 -
Chapter 6 - Dxxxx Parameters

Default Delay, Ondelay, Offdelay, Watchdog: 2 seconds


2oo3, MVote: 5 seconds
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

Specific to Deadtime
Block(s)
Description Delay Time (in Minutes) - If fixed delay is configured, it is a fixed time, specified by
the user; for variable delay, it is a Parameter time, calculated by the function block.
Data Type Real Number
Range Greater-than or equal-to 0.0 minutes.
Default 0.0
Config Load Fixed Delay: Yes Variable Delay: No
Active No
Loadable
Access Lock Fixed Delay: Engineer Variable Delay: ViewOnly
Residence CEE
Related DELAYTYPE
Parameters
Remarks

6.57 DELAYTYPE

Specific to Block(s) Deadtime


Description Delay Type
Data Type Enumeration of DELAYTYPE
Range Fixed (0) Variable (1)
Default Fixed (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 751 -
Chapter 6 - Dxxxx Parameters

6.58 DELCV

Specific to Block PID, PIDFF


(s)
Description Incremental Change in Calculated Variable (Error: Reference source not
found), in Percent.
Data Type 64-Bit Real
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

6.59 DELIVEREDWGT[1..200]

Specific to QIPACCHAN
Block
Description Delivered Weight
Data Type Float64
Range N/A
Default NAN
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MATERIALPATH[1..200], COMMAND, COMMANDSTATS[1..200], MXFERSTATUS
Parameters [1..200], MXFERSTATQ[1..200] , OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200],
POWERFAIL[1..200], TARGETERROR[1..200], AVGFLOWRATE[1..200], AVGSPILL
[1..200]
Remarks This is the resultant delivered weight value for the material transfer. This value
provides material transfer results and is valid after the material transfer for the
designated channel [1..200] in the QiMPACT cluster completes.

- 752 -
Chapter 6 - Dxxxx Parameters

6.60 DELTATIME

Specific to Block(s) Totalizer


Description Delta Time
Data Type Real
Range N/A
Default 0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

6.61 DENSTEAM

Specific to Block(s) LEVELCOMP


Description Density of steam
Data Type Float64
Range Computed from Pressure in Kg/m3
Default NaN
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PRESSUREPRENGUNIT
Remarks This is computed value from PRESSURE.

6.62 DENWATER

Specific to Block(s) LEVELCOMP


Description Density of water
Data Type Float64
Range Computed from Pressure in Kg/m3
Default NaN
Config Load NO
Active Loadable No

- 753 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters PRESSUREPRENGUNIT
Remarks This is computed value from PRESSURE.

6.63 DENWATERREF

Specific to Block(s) LEVELCOMP


Description Density of water in Reference Leg
Data Type Float64
Range Computed form the temperature (range of 0-70DEGC.) in Kg/m3.
Default NaN
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters WETLEGTEMP
Remarks This temperature is calculated based on the WETLEGTEMP parameter.

6.64 DEPLOYMENTINCOMPLETESF

Specific to ELCN_NODE
Block(s)

Description Deployment Incomplete Error - Indicates a softfail condition when


upgrading/migrating/installing Experion R501.6.
Data Type Boolean
Range N/A
Default OFF
Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence ELCN_NODE
Related When installing this, it is important for completion that the user fails the secondary back
Parameters over to the primary so both have the same processes running.

- 754 -
Chapter 6 - Dxxxx Parameters

6.65 DESC

Specific to Applies to all blocks with alarming capability except Timer. Also includes Flag,
Block(s) Message and Push blocks.
Description Block Descriptor - Used to specify descriptive text for the function block. Appears
on both detail and group displays.
Data Type String
Range Length: 132 characters
Default Null string
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence SR
Related EUDESC, KEYWORD.
Parameters
Remarks This is a configurable parameter which may be set by the user prior to loading
the block to the controller (or server).

Specific to Applies to all blocks with alarming capability except Timer. Also includes Flag,
Block(s) Message and Push blocks.
Description Block Descriptor - Used to specify descriptive text for the function block. Appears
on both detail and group displays.
Data Type String
Range Length : 24 Characters
Default Null string
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence SR
Related EUDESC, KEYWORD.
Parameters
Remarks This is a configurable parameter which may be set by the user prior to loading
the block to the controller (or server).

Specific to Block(s) UOC


Description Description
Data Type String
Range N/A
Default Control Edge Unit Operations Controller
Config Load Yes
Active Loadable

- 755 -
Chapter 6 - Dxxxx Parameters

Access Lock AppDevOnly


Residence SRAL
Related Parameters
Remarks

6.66 DESIGNEXEC

Specific to Block(s) ProfitCtl


Description Design exec in mins
Data Type FLOAT64
Range NA
Default 1
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

6.67 DEV

Specific to Block(s) PID, PIDFF, PosProp


Description Deviation - The difference between the Process Variable (PV) and Set Point
(SP).
Data Type 64-Bit Real
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PV, SP.
Parameters
Remarks

- 756 -
Chapter 6 - Dxxxx Parameters

6.68 DEVADDR

Specific to SIFLAGARRCH, SINUMARRCH, SITEXTARRCH.


Block(s)
Description Serial Link Device Address - Identifies a device on the serial link connected to the
FTA.
Data Type 32-Bit Integer
Range 0 - 2,147,483,647
Default 0
Config Load Yes
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Refer to the Allen-Bradley Interface Appendix the MODBUS Interface Appendix in
the Serial Interface Module Implementation Guide for additional configuration data.

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Peer Device Address
Data Type 8-Bit Unsigned Integer
Range 1 to 234 255
Default 1
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Modbus serial device address, 1 to 247 or 255, if the assigned PCDI_Master Block is
a Modbus TCP Bridge device. If the assigned Master Block is a Modbus TCP Device,
this should be 255.

6.69 DEVALM.ALL

Specific to Block SignalSel


(s)
Description Deviation Alarm
Data Type Structure
Range N/A
Default N/A
Config Load No

- 757 -
Chapter 6 - Dxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related DEVALM.TP, DEVALM.TM, DEVALM.DB, DEVALM.PR, DEVALM.SV,
Parameters DEVALM.FL, DEVALM.DBU
Remarks The collection of Deviation Alarm Parameters

6.70 DEVALM.DB

Specific to Block SignalSel


(s)
Description Deviation Alarm Deadband
Data Type Float64
Range N/A
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related DEVALM.TP, DEVALM.TM, DEVALM.PR, DEVALM.SV, DEVALM.FL,
Parameters DEVALM.DBU, DEVALM.ALL
Remarks For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

6.71 DEVALM.DBU

Specific to Block SignalSel


(s)
Description Deviation dead units in EUs or in percent of alarm trip point.
Data Type Enumeration:ALMDBU
Range 0: PERCENT 1: EU
Default PERCENT
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related DEVALM.TPDEVALM.TMDEVALM.DBDEVALM.FLDEVALM.ALL
Parameters
Remarks For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 758 -
Chapter 6 - Dxxxx Parameters

6.72 DEVALM.FL

Specific to Block(s) SignalSel


Description Deviation Alarm Flag
Data Type Boolean
Range OFF (0) No deviation alarm exists
ON (1) A deviation alarm exists
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related Parameters DEVALM.TPDEVALM.TMDEVALM.DBDEVALM.ALLDEVALM.DBU
Remarks The flag that is set when deviation alarm is triggered

6.73 DEVALM.PR

Specific to Block(s) SignalSel


Description Deviation Alarm Priority
Data Type Enumeration: ALPRIOR
Range 0: NONE 1: JOURNAL 2: LOW 3: HIGH 4: URGENT
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related Parameters DEVALM.SVDEVALM.FL
Remarks This parameter represents the priority of the deviation alarm

6.74 DEVALM.SV

Specific to Block(s) SignalSel


Description Deviation Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No

- 759 -
Chapter 6 - Dxxxx Parameters

Access Lock Engineer


Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related Parameters DEVALM.PR, DEVALM.FL
Remarks This parameter represents the severity of the deviation alarm

6.75 DEVALM.TM

Specific to SignalSel
Block(s)
Description Deviation Alarm Time in seconds
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related DEVALM.TP, DEVALM.DB, DEVALM.FL, DEVALM.ALL, DEVALM.DBU
Parameters
Remarks The time in seconds after which a deviation alarm will be initiated if the inputs
remain outside the deviation trippoint. For more information about alarm
configuration, refer to Control Builder Components Theory Guide.

6.76 DEVALM.TMO

Specific to Block SignalSel


(s)
Description Deviation Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for
deviation alarms.

- 760 -
Chapter 6 - Dxxxx Parameters

6.77 DEVALM.TP

Specific to Block(s) SignalSel


Description Deviation Alarm Trippoint
Data Type Float64
Range N/A
Default NaN
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related Parameters DEVALM.TM, DEVALM.DB, DEVALM.FL, DEVALM.ALL, DEVALM.DBU
Remarks The trippoint for the deviation alarm

6.78 DEVCTL

Specific to HRBALG_DI — HRB Algorithm DI


Blocks
Description DEVCTL FB Reference
Data Type BLOCKID
Range Not applicable

Default
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the DEVCTL block in the emulation CM, which
holds the HRBALG_DI instance. This parameter connector is used in EC DI
algorithm emulation.

6.79 DEVFLAG[0..N]

Specific to C300, CPM, IOLIM, FIM4, LIOM, PGM, EHPM


Block(s)
Description Developer Flag - Indicates status of embedded developer instrumentation.
Data Type Boolean
Range Off (0) Developer instrumentation disabled.

- 761 -
Chapter 6 - Dxxxx Parameters

On (1) Developer instrumentation enabled.


Default Off (0)
Config Load No
Active No
Loadable
Access Lock Intimate User
Residence C300, C200, IOLIM, FIM4, LIOM, PGM, EHPM
Related
Parameters
Remarks Used to conditionally enable embedded instrumentation to better diagnose
abnormal conditions and is not user visible. The value of array index N is 32 in C200
and 64 in C300.

6.80 DEVFLAG

Specific to Block(s) UOC


Description Developer Flags
Data Type Boolean
Range N/A

Default FALSE
Config Load Yes
Active Loadable
Access Lock Operator
Residence NOLOAD
Related Parameters
Remarks

6.81 DEVGENUINE

Specific to UOC
Block(s)
Description Non-Genuine Hardware Detected
Data Type Boolean
Range N/A

Default Off
Config Load No
Active
Loadable

- 762 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Soft failure condition. Runtime diagnostics has detected non-genuine, possibly
counterfeit hardware. Users should contact Honeywell to arrange for replacement
hardware.

6.82 DEVHIALM.DB

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation High Alarm Deadband
Data Type 64-Bit Real
Range 0.0 to 100.0, if alarm deadband units (DEVHIALM.DBU) are in Percent. Greater-
than or equal to 0.0, if alarm deadband units (DEVHIALM.DBU) are Engineering
Units (EUs).
Default 0.0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related DEVHIALM.DBUDEVHIALM.FL, DEVHIALM.PR, DEVHIALM.SV, DEVHIALM.TM,
Parameters DEVHIALM.TP, PV, SP.
Remarks The following rule is applied to DEVHIALM.DB to prevent DEVHI and DEVLO alarm
that are both active at the same time: DEVHIALM.DB <= (DEVHIALM.TP -
DEVLOALM.TP)/2 (or DEVLOALM.TP <= DEVHIALM.TP - (2*DEVLOALM.DB)) For
more information about alarm configuration, refer to Control Builder Components
Theory Guide.

6.83 DEVHIALM.DBU

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation High Alarm Deadband Units - Indicates if DEVHIALM.DB is in Percent
or Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU (1)
Default Percent (0)
Config Load Yes
Active No
Loadable

- 763 -
Chapter 6 - Dxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related DEVFLAG[0..N]DEVHIALM.DBU, DEVHIALM.FL, DEVHIALM.PR, DEVHIALM.SV,
Parameters DEVHIALM.TM, DEVHIALM.TP, PV SP.
Remarks For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

6.84 DEVHIALM.FL

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation High Alarm Flag - Indicates if DEVHIALM.TP has been exceeded.
Data Type Boolean
Range Off (0): DEVHIALM.TP has not been exceeded (that is, no Deviation High alarm).
On (1): DEVHIALM.TP has been exceeded.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related DEVFLAG[0..N]DEVHIALM.DBU, DEVHIALM.FL, DEVHIALM.PR, DEVHIALM.SV,
Parameters DEVHIALM.TMDEVHIALM.TP, PV, SP.
Remarks

6.85 DEVHIALM.PR

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation High Alarm Priority - Defines the priority of a Deviation High alarm.
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DEVFLAG[0..N]DEVHIALM.DBU, DEVHIALM.FL, DEVHIALM.PR, DEVHIALM.SV,
Parameters DEVHIALM.TM, DEVHIALM.TP, PV, SP.
Remarks

- 764 -
Chapter 6 - Dxxxx Parameters

6.86 DEVHIALM.SV

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation High Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DEVFLAG[0..N], DEVHIALM.DBU, DEVHIALM.FL, DEVHIALM.PR, DEVHIALM.SV,
Parameters DEVHIALM.TMDEVHIALM.TP, PV, SP.
Remarks

6.87 DEVHIALM.TM

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation High Alarm Filter Time (in seconds) - The purpose of this variable is to
prevent input spikes from causing alarms. An alarm will only be generated if the
deviation consistently exceeds the high deviation trip point for more than
DEVHIALM.TM seconds.
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DEVFLAG[0..N], DEVHIALM.DBU, DEVHIALM.FL, DEVHIALM.PR, DEVHIALM.SV,
Parameters DEVHIALM.TM, DEVHIALM.TP, PV, SP.
Remarks If DEVHIALM.TM = 0, an alarm will be generated as soon as the deviation exceeds
the high deviation trip point. For more information about alarm configuration, refer
to Control Builder Components Theory Guide.

- 765 -
Chapter 6 - Dxxxx Parameters

6.88 DEVHIALM.TMO

Specific to Block PID, PIDER, PIDFF, PosProp, RATIOCTL


(s)
Description Deviation High Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for
Deviation High Alarms.

6.89 DEVHIALM.TP

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation High Alarm Trip Point (in Engineering Units) - Defines the upper limit for
the deviation.
Data Type 64-Bit Real Number
Range NaN, or 0.0 to [PVEUHI - PVEULO]
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DEVFLAG[0..N], DEVHIALM.DBU, DEVHIALM.FL, DEVHIALM.PR, DEVHIALM.SV,
Parameters DEVHIALM.TM, DEVHIALM.TP, PV, SP.
Remarks PID and PosProp only: Alarm occurs when PV is higher than (SP + DEVHIALM.TP).
RampSoak only: Alarm occurs when PV - CV > DEVHIALM.TP. The following rule is
applied to DEVHIALM.DB to prevent DEVHI and DEVLO alarm that are both active
at the same time. DEVLOALM.TP <= DEVHIALM.TP – (2 DEVLOALM.DB) (or
DEVHIALM.DB <= (DEVHIALM.TP - DEVLOALM.TP)/2 )

- 766 -
Chapter 6 - Dxxxx Parameters

6.90 DevHigh.DeadBandUnits

Specific to PROFITCTLIN
Block(s)
Description DeviationHigh:DeadBand Units
Data Type ENUM
Range Percent (0) EU (1)
Default Percent
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.HIGHLIMIT, DevHigh.TripPoint, DevHigh.Priority,
Parameters DevHigh.Severity, DevHigh.OnDelayTimeSec, DevHigh.OffDelayTimeSec,
DevHigh.DeadBandValue
Remarks Arrayed parameter of size NUMBEROFCVS

6.91 DevHigh.DeadBandValue

Specific to PROFITCTLIN
Block(s)
Description DeviationHigh:DeadBand Value
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.HIGHLIMIT, DevHigh.TripPoint, DevHigh.Priority,
Parameters DevHigh.Severity, DevHigh.OnDelayTimeSec, DevHigh.OffDelayTimeSec,
DevHigh.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

- 767 -
Chapter 6 - Dxxxx Parameters

6.92 DEVHIGH.FL

Specific to Block(s) PROFITCTLIN


Description DEVHIGH FL
Data Type BOOL
Range OFF, ON
Default OFF
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

6.93 DevHigh.OffDelayTimeSec

Specific to PROFITCTLIN
Block(s)
Description DeviationHigh:Off-Delay Time(sec)
Data Type UINT32
Range 0 to 65535
Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.HIGHLIMIT, DevHigh.TripPoint, DevHigh.Priority,
Parameters DevHigh.Severity, DevHigh.OnDelayTimeSec, DevHigh.DeadBandValue,
DevHigh.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

6.94 DevHigh.OnDelayTimeSec

Specific to PROFITCTLIN
Block(s)
Description DeviationHigh:On-Delay Time(sec)
Data Type UINT32
Range 0 to 65535
Default 0

- 768 -
Chapter 6 - Dxxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.HIGHLIMIT, DevHigh.TripPoint, DevHigh.Priority,
Parameters DevHigh.Severity, DevHigh.OffDelayTimeSec, DevHigh.DeadBandValue,
DevHigh.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

6.95 DevHigh.Priority

Specific to PROFITCTLIN
Block(s)
Description DeviationHigh:Priority
Data Type ENUM
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.HIGHLIMIT, DevHigh.TripPoint, DevHigh.Severity,
Parameters DevHigh.OnDelayTimeSec, DevHigh.OffDelayTimeSec, DevHigh.DeadBandValue,
DevHigh.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

6.96 DevHigh.Severity

Specific to PROFITCTLIN
Block(s)
Description DeviationHigh:Severity
Data Type INT16
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable

- 769 -
Chapter 6 - Dxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related NUMBEROFCVS , CV.Value, CV.HIGHLIMIT, DevHigh.TripPoint, DevHigh.Severity,
Parameters DevHigh.OnDelayTimeSec, DevHigh.OffDelayTimeSec, DevHigh.DeadBandValue,
DevHigh.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

6.97 DevHigh.TripPoint

Specific to PROFITCTLIN
Block(s)
Description DeviationHigh:Trip Point
Data Type FLOAT64
Range ±1.7E+308
Default NaN
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.HIGHLIMIT, DevHigh.TripPoint, DevHigh.Severity,
Parameters DevHigh.OnDelayTimeSec, DevHigh.OffDelayTimeSec, DevHigh.DeadBandValue,
DevHigh.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

6.98 DEVICE

Specific to Block(s) PM I/O Channel Blocks


Description Associated I/O Processor. The name of the IOP block instance the IOC is
assigned to.
Data Type String
Range N/A
Default Null
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related
Parameters
Remarks

- 770 -
Chapter 6 - Dxxxx Parameters

6.99 DEVICEID[0..7]

Specific to Chassis HART AI IOM, HART AO IOM


Block(s)
Description Device Identification - Indicates the serial number read from the HART device
connected to the channel. The device serial number is 3 bytes.
Data Type 32-Bit Unsigned Integer
Range 0 to 16777215 (only a 3 byte device serial number is possible).
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

6.100 DEVICEIDX

Specific to C300, FIM4, PGM, FTEB, EHPM, TCMI.


Block(s)
Description Device Index - Identifies the unique FTE Device Index number configured on
switches in the module.
Data Type 32-Bit Integer
Range 0 to 511
Default 0
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence C300, FTEB, FIM4, PGM, EHPM
Related CURDEVICEIDX
Parameters
Remarks User (software) configured FTE Device Index of module (through C300 , EHPM FB).
Reserves a consecutive pair of device indices regardless of whether module is
configured redundant or non-redundant. This must match the Device Index
specified on the hardware's rotary switches.

- 771 -
Chapter 6 - Dxxxx Parameters

Specific to EIM Platform Block


Block(s)
Description Device Index — Identifies the unique FTE Device Index number configured on
switches in the module.
Data Type INT32
Range 1-512
Default 0
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks FTE device index.

Specific to Block(s) UOC


Description Device Index
Data Type INT32
Exposer NONE
Range ±2147483647
Default 0
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks FTE device index.

Specific to RETENTIONTRIG
Block(s)
Description Device Index
Data Type UINT16
Exposer Output
Range None
Default 0
Config Load No
Active No
Loadable

- 772 -
Chapter 6 - Dxxxx Parameters

Access Lock View Only


Residence CEE
Related POWERCONNOPT
Parameters
Remarks Device Index of the UOC controller which is currently acting as primary. The
controller’s Device Index plays an important role when POWERCONNOPT =
Dual1PerModule.

6.101 DEVICELOCATION

Specific to All PM I/O Channels; All Series C I/O Channels


Block
Description Associated Device Location. A description of the physical location (within the
plant) where the connected device is found.
Data Type String
Range 64 Characters
Default Null
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence SR
Related N/A
Parameters
Remarks This parameter is user-entered.

6.102 DEVICEREVNO[0..7]

Specific to Chassis HART AI IOM, HART AO IOM


Block(s)
Description Device Revision Number - Indicates the revision number of the transmitter
command set on the HART device connected to the channel.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active No
Loadable

- 773 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks

6.103 DEVICETYPE

Specific to Block(s) 850M


Description Device Type
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

6.104 DEVLM

Specific to Block(s) SignalSel


Description Deviation Limit
Data Type Float64
Range >0 including NaN
Default NaN
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related DEVTM, IGNORD, IGNORDFL[1..6]
Parameters
Remarks If any P inputs go beyond the deviation limit for a specific time they shall be
ignored

- 774 -
Chapter 6 - Dxxxx Parameters

6.105 DEVLOALM.DB

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation Low Alarm Deadband
Data Type 64-Bit Real Number
Range to 100.0 if alarm deadband units (DEVLOALM.DBU) are Percent Greater-than or
equal to 0.0 if alarm deadband units (DEVLOALM.DBU) are Engineering Units
(EUs).
Default 0.0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related DEVLOALM.DBU
Parameters
Remarks The following rule is applied to DEVLOALM.DB to prevent DEVHI and DEVLO alarm
that are both active at the same time: DEVLOALM.DB <= (DEVHIALM.TP -
DEVLOALM.TP)/2 (or DEVHIALM.TP >= DEVLOALM.TP + (2*DEVHIALM.DB)) For
more information about alarm configuration, refer to Control Builder Components
Theory Guide.

6.106 DEVLOALM.DBU

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation Low Alarm Deadband Units - p - Indicates if DEVLOALM.DB is in
Percent or Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU (1)
Default Percent (0)
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related DEVLOALM.DB
Parameters
Remarks For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 775 -
Chapter 6 - Dxxxx Parameters

6.107 DEVLOALM.FL

Specific to PID, PIDFF, PosProp, RampSoak


Block(s)
Description Deviation Low Alarm Flag - Indicates DEVLOALM.TP has been exceeded.
Data Type Boolean
Range Off (0): DEVLOALM.TP has not been exceeded; that is, no Deviation Low alarm.
On (1): DEVLOALM.TP has been exceeded.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

6.108 DEVLOALM.PR

Specific to Block(s) PID, PIDFF, PosProp and RampSoak


Description Deviation Low Alarm Priority - Defines the priority of a Deviation Low
alarm.
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

6.109 DEVLOALM.SV

Specific to Block(s) PID, PIDFF, PosProp and RampSoak


Description Deviation Low Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0

- 776 -
Chapter 6 - Dxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters DEVLOALM.FL, DEVLOALM.PR.
Remarks

6.110 DEVLOALM.TM

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation Low Alarm Filter Time (in Seconds) - The purpose of this variable is to
prevent input spikes from causing alarms. An alarm will only be generated if the
deviation is consistently below the low deviation trip point for more than
DEVLOALM.TM seconds.
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CURDEVICEIDX
Parameters
Remarks If DEVLOALM.TM = 0, an alarm will be generated as soon as the deviation falls
below the low deviation trip point. For more information about alarm configuration,
refer to Control Builder Components Theory Guide.

6.111 DEVLOALM.TMO

Specific to Block PID, PIDER, PIDFF, POSPROP, RATIOCTL


(s)
Description Deviation Low Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No

- 777 -
Chapter 6 - Dxxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for
Deviation Low Alarm.

6.112 DEVLOALM.TP

Specific to PID, PIDFF, PosProp and RampSoak


Block(s)
Description Deviation Low Alarm Trip Point (in Engineering Units) - Defines the lower limit for
the deviation.
Data Type 64-Bit Real Number
Range NaN, or 0.0 to [PVEUHI - PVEULO]
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PV, PVEUHI, PVEULO, SP.
Parameters
Remarks The following rule is applied to DEVLOALM.DB to prevent DEVHI and DEVLO alarm
that are both active at the same time. DEVLOALM.TP <= DEVHIALM.TP – (2
DEVLOALM.DB) (or DEVLOALM.DB <= (DEVHIALM.TP - DEVLOALM.TP)/2 )

6.113 DevLow.DeadBandUnits

Specific to PROFITCTLIN
Block(s)
Description DeviationLow:DeadBand Units
Data Type ENUM
Range Percent (0) EU (1)
Default Percent
Config Load Yes
Active No
Loadable

- 778 -
Chapter 6 - Dxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related NUMBEROFCVS , CV.Value, CV.LOWLIMIT, DevLow.TripPoint, DevLow.Priority,
Parameters DevLow.Severity, DevLow.OnDelayTimeSec, DevLow.OffDelayTimeSec,
DevLow.DeadBandValue
Remarks Arrayed parameter of size NUMBEROFCVS

6.114 DevLow.DeadBandValue

Specific to PROFITCTLIN
Block(s)
Description DeviationLow:DeadBand Value
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.LOWLIMIT, DevLow.TripPoint, DevLow.Priority,
Parameters DevLow.Severity, DevLow.OnDelayTimeSec, DevLow.OffDelayTimeSec,
DevLow.DeadBandUnits
Remarks

6.115 DEVLOW.FL

Specific to Block(s) PROFITCTLIN


Description DEVLOW FL
Data Type BOOL
Range OFF, ON
Default OFF
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 779 -
Chapter 6 - Dxxxx Parameters

6.116 DevLow.OffDelayTimeSec

Specific to PROFITCTLIN
Block(s)
Description DeviationLow:Off-Delay Time(sec)
Data Type UINT32
Range 0 to 65535
Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.LOWLIMIT, DevLow.TripPoint, DevLow.Priority,
Parameters DevLow.Severity, DevLow.OnDelayTimeSec, DevLow.DeadBandValue,
DevLow.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

6.117 DevLow.OnDelayTimeSec

Specific to PROFITCTLIN
Block(s)
Description DeviationLow:On-Delay Time(sec)
Data Type UINT32
Range 0 to 65535
Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.LOWLIMIT, DevLow.TripPoint, DevLow.Priority,
Parameters DevLow.Severity, DevLow.OffDelayTimeSec, DevLow.DeadBandValue,
DevLow.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

- 780 -
Chapter 6 - Dxxxx Parameters

6.118 DevLow.Priority

Specific to PROFITCTLIN
Block(s)
Description DeviationLow:Priority
Data Type ENUM
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.LOWLIMIT, DevLow.TripPoint, DevLow.Severity,
Parameters DevLow.OnDelayTimeSec, DevLow.OffDelayTimeSec, DevLow.DeadBandValue,
DevLow.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

6.119 DevLow.Severity

Specific to PROFITCTLIN
Block(s)
Description DeviationLow:Severity
Data Type INT16
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.LOWLIMIT, DevLow.TripPoint, DevLow.Priority,
Parameters DevLow.OnDelayTimeSec, DevLow.OffDelayTimeSec,
DevLow.DeadBandValue,DevLow.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

- 781 -
Chapter 6 - Dxxxx Parameters

6.120 DevLow.TripPoint

Specific to PROFITCTLIN
Block(s)
Description DeviationLow:Trip Point
Data Type FLOAT64
Range ±1.7E+308
Default NaN
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , CV.Value, CV.LOWLIMIT, DevLow.Priority, DevLow.Severity,
Parameters DevLow.OnDelayTimeSec, DevLow.OffDelayTimeSec, DevLow.DeadBandValue,
DevLow.DeadBandUnits
Remarks Arrayed parameter of size NUMBEROFCVS

6.121 DEVSPCBIT[0..135]

Specific to Block(s) HARTDEVICE (Chassis I/O)


Description Device Specific Status Bits - Indicates the status read from a HART device.
Data Type Boolean
Range
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks The device status is 136 bits of data and is in response to Command 48.

- 782 -
Chapter 6 - Dxxxx Parameters

6.122 DEVSTS[0..15]

Specific to Block(s) PCDI_MASTER


Description Device Status - Displays the current device status.
Data Type Enumeration
Range 0 INVALID
1 INITIAL
2 DIAG
3 OPERATIONAL
4 FAIL
5 IDLE
Default INVALID (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Device
Related Parameters
Remarks

6.123 DEVSUPCMDS[0 - 15][0 - 39]

Specific to PCDI_MASTER
Block(s)
Description Device Supported Commands
Data Type 32-Bit Integer
Range
Default Array Zeroed: No configured UNITID/commands Safety Manager: Auto
configured Safety Manager commands
Config Load
Active No
Loadable
Access Lock Application Developer Only
Residence Device
Related
Parameters
Remarks

- 783 -
Chapter 6 - Dxxxx Parameters

6.124 DEVTM

Specific to Block(s) SignalSel


Description Deviation Time in seconds
Data Type Float64
Range N/A
Default 0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related DEVLM
Parameters
Remarks If any P inputs go beyond the deviation limit for the deviation time they are
ignored

6.125 DEVTYPE

Specific to PCDI_MASTER
Block(s)
Description Device Type - Define the type of peer device represented by the block.
Data Type Enumeration
Range 0 Single MODBUS TCP Bridge
1 Redundant MODBUS TCP Bridge
2 Single MODBUS TCP Device
3 Redundant MODBUS TCP Device
4 Single Safety Manager
5 Redundant Safety Manager
Default Single MODBUS TCP Bridge (0)
Config Yes
Load
Active No
Loadable

- 784 -
Chapter 6 - Dxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related DEVADDR, UNITIDMON[0..15, UNITID[0..15],
Parameters
Remarks MODBUS TCP Device Types:
l Bridges are used to connect multiple Modbus devices to a single master block,
with each block acting on behalf of the Modbus device. In other words, each
request block represents a particular device through its UNITIDMON
parameter. in this case, the UNITIDMON must match the request blocks
DEVADDR parameter.
l Devices are used to represent the Master block as a native Modbus device.
Each request block represents a single request type on the same block. When
a device type is selected, the UNITID parameter represents the Modbus device
ID. In this case, the UNITID must match the request blocks DEVADDR
parameter.
Safety Manager Device Types:
l Safety Managers are used to connect to Honeywell's Safety Manager R130 or
greater devices. The parameters for UNITID, UNITIDMON, and DEVADDR
follow the same rules for Modbus devices described above.

6.126 DFNPHWYEM

Specific to Experion Hiway Bridge (EHB) platform block, ELCN_NODE (EHB)


Blocks
Description Define physical gateway emulation
Data Type Boolean
Range OFF
ON
Default OFF
Config. No
Load
Active No
Loadable
Access Lock Configurable on form
Residence SR
Related
Parameters
Remarks Determines whether the physical Hiway to which the EHB belongs is configured on
this EHB’s form or on the local partner EHB’s form. When this parameter is set to
OFF, the following parameters cannot be configured in the form.
l HWYNUM
l HWYNUMPRT
l PHWYPRTLC
l PHWYPRTRMIP1
l PHWYPRTRMIP2
Instead, they are auto-populated while loading the EHB platform block.

- 785 -
Chapter 6 - Dxxxx Parameters

6.127 DHCPENABLE

Specific to UOC
Blocks
Description Enable DHCP Server
Data Type Boolean
Range N/A
Default TRUE
Config. Yes
Load
Active
Loadable
Access Lock Engineer
Residence CEE
Related DHCPSTARTADDR, DHCPENDADDR
Parameters
Remarks Downlink DHCP configuration. Enable or disable the downlink DHCP server. This
option is only available if the downlink network interface is enabled.

6.128 DHCPENDADDR

Specific to UOC
Blocks
Description End of DHCP IP Lease Block
Data Type STRING
Range N/A
Default 0.0.0.0
Config. Load Yes
Active
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks Downlink DHCP configuration. End of DHCP IP lease block. This option is only
available when the downlink DHCP server is enabled.

- 786 -
Chapter 6 - Dxxxx Parameters

6.129 DHCPSTARTADDR

Specific to UOC
Blocks
Description Start of DHCP IP Lease Block
Data Type STRING
Range N/A
Default 0.0.0.0
Config. Load Yes
Active
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks Downlink DHCP configuration. Start of DHCP IP lease block. This option is only
available when the downlink DHCP server is enabled.

6.130 DI[1..4]

Specific to DevCtl
Block(s)
Description Digital Input Value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related DIMODEDIPVMAP[0..15], GPVAUTO, NUMDINPUTS, NUMSTATES, PVAUTO.
Parameters
Remarks The number of Elements allowed is restricted by the value of NUMDINPUTS. For
example, if NUMDINPUTS = 2, then only DIPVMAP[0..3] are legal.

- 787 -
Chapter 6 - Dxxxx Parameters

6.131 DI[1..10]

Specific to Block(s) GRPCAPRBK


Description ON/OFF state of equipments
Data Type Boolean
Range
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Equipment ON/OFF state. Using this parameter the Group capability is
calculated.

6.132 DIAGREQSENT[0..15]

Specific to Block(s) PCDI_MASTER


Description Diagnositc Requests
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

6.133 DIAGREQRSPRCVD[0..15]

Specific to Block(s) PCDI_MASTER


Description Diagnositc Requests: Responses Received
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No

- 788 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

6.134 DICHNLNAME

Specific to Universal IO module


Block(s)
Description Channel Name - Displays the channel names in the DI Status tab of the UIO
module.
Data Type STRING
Range Length: 40 characters
Default
Config No
Load
Access Lock ViewOnly
Active No
Loadable
Residence SR
Related CHNLNAMEAICHNLNAMEAOCHNLNAMEDOCHNLNAME
Parameters
Remarks This parameter identifies the configured name of the channels associated with this
IOM block. It is used to display the channel names in DI Status Data tab. This
parameter displays only the channel names configured with the PNTTYPE of DI.

6.135 DIGFILTER[0..numChans-1]

Specific to All Analog Input Module Function Blocks


Block(s)
Description Digital Filter (msec) - This parameter is a configurable time constant used in a first
order lag filter which is used to remove noise from inputs.
Data Type 32-Bit Integer
Range 0 (disables the filter), or (2 x RTS) + 1 to 20100 milliseconds (See Remarks)
Default 0 (filter is disabled)
Config Yes
Load
Active No
Loadable

- 789 -
Chapter 6 - Dxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related
Parameters
Remarks The Digital Filter time must be greater than 2 times the RTS (Real Time Sample)
value, not to exceed 20100 milliseconds. The RTS is the execution period of the
analog to digital conversion loop in the AI device. In most cases, the RTS is equal to
the SAMPLERATE parameter

6.136 DIGFILTER [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1732E-IF4M12R, 1732E-IR4IM12R, 1732E-IT4IM12R,


Block(s) 1738-IE2CM12, 1738-IE4CM12, 1738-IR2M12, 1738-IT2IM12
Description Digital Filter time in milliseconds
Data Type 16-Bit Unsigned Integer
Range 0 — 10000
Default 0
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related
Parameters
Remarks This parameter sets the digital filter time constant, in milliseconds.

6.137 DIHASENAME

Specific to EC
Blocks
Description ECDI HASE name
Data Type BLOCKID
Range ViewOnly
Default HGRW
Config. No
Load
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter shows algorithm HRB name along with HASE name configured for
the slot represented by index. The format is HASENAME.ALGOHRBNAME.

- 790 -
Chapter 6 - Dxxxx Parameters

6.138 DIMODE

Specific to Series C DI-24, DI-SOE IOM Block


Block(s)
Description Digital Input Module Mode configuration
Data Type Enumeration
Range 0 Normal For DI-SOE IOM FB, the input channel will sample and
process inputs every 20 milliseconds. This mode does not
support SOE event generation.
1 Soe For DI-SOE IOM FB, the input channel will sample the input
every millisecond, process PV every 20 milliseconds, and
support SOE functionality.
2 LowLatency For DI-SOE IOM FB, the input channel will sample and
process inputs every 5 milliseconds. This mode does not
support SOE event generation.
Default For DI-SOE IOM: Soe For DI-24 IOM: Normal
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related
Parameters
Remarks This parameter is only available in Project mode.

6.139 DIPTEXECST

Specific to Universal IO module


Block(s)
Description Point Execution State - Displays the point execution state in the DI Status tab of the
UIO module.
Data Type Enumeration
Range 0 Inactive Point is not scanned or
processed.
1 Active Point is scanned and
processed.
Default Inactive
Config Load No
Access Lock ViewOnly

- 791 -
Chapter 6 - Dxxxx Parameters

Active No
Loadable
Residence IOM
Related PTEXECSTAIPTEXECSTAOPTEXECSTDOPTEXECST
Parameters
Remarks This parameter displays the point execution state of UIO module in the DI Status
Data tab. When PTEXECST is Inactive, the point processing does not occur for the
channel.

6.140 DIPVMAP[0..15]

Specific to DevCtl
Block(s)
Description Actual State Definitions.
Data Type String
Range Bad (0) InBet (1) State0 (4) State1 (5) State2 (6)
Default Bad (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DI[1..4], GPVAUTO, NUMDINPUTS,. NUMSTATES, PVAUTO.
Parameters
Remarks The number of elements allowed is restricted by the value of NUMDINPUTS. For
example, if NUMDINPUTS = 2, then only DIPVMAP[0..3] are legal. No member of
DIPVMAP may be assigned State2, if NUMSTATES = 2.

6.141 DIRECTSYNC

Specific to C200, C300, PGM and FIM4


Block(s)
Description Direct Synchronization State - When enabled, indicates the redundant controller
(or module) pair supports direct synchronization or the normal controller
redundancy synchronization.
Data Type Enumeration
Range DISABLED (0) - Does not support direct
synchronization or partner is absent.
ENABLED (1) - Direct synchronization allowed.
Default DISABLED (0)
Config Load No
Active No
Loadable

- 792 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence C200, C300, FIM4, PGM
Related INDRCTSYNC
Parameters
Remarks Matching firmware versions is a requirement for direct synchronization. Primary
and secondary modules always show the same value of DIRECTSYNC, if they are
communicating.

6.142 DIREGISTERD[ ]

Specific to EC
Blocks
Description DI Registered
Data Type Boolean
Range TRUE or FALSE
Default FALSE
Config. Load No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter will be selected if the EC DI algorithm HRB configured in the slot
is registered with the Box HRB

6.143 DISABLEBATTERYALARM

Specific to C300
Block(s)
Description Disable Battery Alarm and Soft Fail
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence C300
Related
Parameters
Remarks When this parameter is enabled, the C300 Controller does not report any battery-
related soft fails and events irrespective of whether a battery backup is provided to
the C300 Controller or not.

- 793 -
Chapter 6 - Dxxxx Parameters

6.144 DISCONNDEVNAME

Specific to Secondary 850M


Block(s)
Description Disconnected Device
Data Type BLOCKID
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access View Only
Lock
Residence 850M
Related RDNHISTREASON
Parameters
Remarks This parameter only exists on the Secondary 850M function block and it is updated
with the name of the primary block that is the catalyst for redundancy behavior as
follows. The 850M redundancy solution drops synchronization with
RDNHISTREASON DeviceConnectionStatus when the secondary is unable to open
a connection with the IED (when the primary 850M has successfully established a
connection with the IED). This parameter is updated with the name of the first IED
with which the secondary 850M has loss communication or is unable to establish
communication. The 850M redundancy solution drops synchronization with
RDNHISTREASON SyncDataReceiveError when a block synchronized to the
secondary encounters an error while processing redundancy data received from
the primary. This parameter is updated with the name of the first block that
encounters a synchronization data receive error. This parameter is reset to blank
when the 850M commences initial-sync.

6.145 DISCREP

Specific to Block(s) 2oo3, MVote


Description Discrepancy output value.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 794 -
Chapter 6 - Dxxxx Parameters

6.146 DISCRTINPUT1[1..4]

Specific to JAGXCHAN
Block(s)
Description Discrete Input 1
Data Type Boolean
Range Off(0) Input Off
On(1) Input On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 9 of the status word in the floating point input assembly for
the designated scale slot [1..4].

6.147 DISCRTINPUT2[1..4]

Specific to JAGXCHAN
Block(s)
Description Discrete Input 2
Data Type Boolean
Range Off(0) Input Off
On(1) Input On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 10 of the status word in the floating point input assembly
for the designated scale slot [1..4].

- 795 -
Chapter 6 - Dxxxx Parameters

6.148 DISCRTINPUT3[1..4]

Specific to Block(s) JAGXCHAN


Description Discrete Input 3
Data Type Boolean
Range Off(0) Input Off
On(1) Input On
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
RelatedParameters:
Remarks This is the value of bit 11 of the status word in the floating point input
assembly for the designated scale slot [1..4].

6.149 DISP_C

Specific to Block(s) ProfitCtl


Description Color for Disp
Data Type ENUM
Range NA
Default BLACK
Config Load Yes
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

6.150 DISPADJPARAM

Specific to PHASE
Block(s)
Description Display adjustable parameter option
Data Type Boolean
Range OFF, ON
Default OFF
Config Yes

- 796 -
Chapter 6 - Dxxxx Parameters

Load
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks This parameter is used by PHASE block to specify if its adjustable formula
parameters and report parameters should be displayed in the Formula and Report
tab of the parent RCM when the parent RCM has a Data block. The parameters will
be displayed if DISPADJPARAM is configured to ON, and not displayed if
DISPADJPARAM is configured to OFF. The parameter will be ignored and
formula/report parameters are always displayed, if the RCM does not have a DATA
block.

6.151 DISPLAYEDSTATUS

Specific to Block(s) ProfitCtl


Description Ctrl Disp. status
Data Type ENUM
Range NA
Default INACTIVE
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

6.152 DISPLAYSTATE

Specific to ACT, RCM, SCM


Block(s)
Description Display State (Summary Information for User Interface)
Data Type 64-Bit Integer
Range NA
Default 0
Config No
Load
Active No
Loadable

- 797 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence Not Loaded
Related
Parameters
Remarks For an RCM/SCM - It combines the COLORSTATE, STATE, EXECSTS, CONFIGSTS,
INALM, INSTRUCTPEND, MODE, and MODEATTR parameters into a single bit
packed field. For an ACT - It combines the EXECSTS and MODEATTR parameters
into a single bit packed field when its state is not executing. When its state is
executing, it returns the DISPLAYSTATE of its execution object (SCM/RCM/CR).

6.153 DISPLAYSUBSCRMAXPPS

Specific to EHPM
Block(s)
Description This parameter defines the PPS limit after which the EHPM begins to throttle
subscribed CDA display clients load on HPM processors. When total sum of PPS
from subscribed CDA display clients exceeds the configured
DISPLAYSUBSCRMAXPPS value, the EHPM slows down internal polling rates by a
factor of two. For example, a CDA display client subscribed at a 2 second rate
effectively executes at 4 second subscription rate.
Data Type UNIT16
Range 100–1000
Default 500
Config Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly
Residence CEE
Related -
Parameters
Remarks -

6.154 DISPOVRLOAD

Specific to EHPM
Block(s)
Description This parameter shows the load on the subscribed display path (throttling active
to fit allowed PPS limit).
Data Type BOOLEAN
Range OFF-ON
Default OFF
Config Load No
Active Loadable Yes

- 798 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related DISPLAYSUBSCRMAXPPS
Parameters
Remarks -

6.155 DISPPOS

Specific to RM
Block(s)
Description Display position. Identifies the Chassis A vs. Chassis B workstation display field
groups to which the remainder of this object's data should be applied.
Data Type Enumeration
Range Undefined (0) Chassis_A (1) Chassis_B (2)
Default Undefined (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

6.156 DISPRATEAVG

Specific to Block IOLIM, Secondary IOLIM, FIM, CPM


(s)
Description Display Rate Average. Shows the average display update rate in parameters
per second.
Data Type 32-Bit Real Number
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks

- 799 -
Chapter 6 - Dxxxx Parameters

6.157 DISPRATEMAX

Specific to Block IOLIM, Secondary IOLIM, FIM, CPM


(s)
Description Display Rate Maximum. Shows the maximum display update rate in
parameters per second.
Data Type 32-Bit Real Number
Range N/A
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks

6.158 DISPSUBCACHEFRFCTR

Specific to EHPM
Block(s)
Description This parameter controls internal caching of parameters requested by subscribed
CDA display clients such as HMIWeb displays and so on. When cache is enabled
(DISPSUBCACHEFRFCTR = 50), then multiple CDA display clients requesting the
same parameter value retrieve the values from cache. When cache is disabled
(DISPSUBCACHEFRFCTR = 0), then all clients retrieve values independently of each
other.
Data Type ENUM
Range 0 and 50
Default 50
Config Yes
Load
Active Yes
Loadable
Access Lock Engineer
Residence CEE
Related CDISPAVGCHPPS, CDISPMAXCHPPS
Parameters
Remarks Parameter value in cache is updated at the rate of the fastest subscribed CDA
display client.

- 800 -
Chapter 6 - Dxxxx Parameters

6.159 DISQSECCMD

Specific to RM
Block(s)
Description Disqualify Secondary Command
Data Type Boolean
Range True (0) False (1)
Default True (0)
Config Load No
Active No
Loadable
Access Lock Operator Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

6.160 DISRC [1..10]

Specific to Block(s) GRPCAPRBK


Description Connection for DI input
Data Type INCONN
Range
Default
Config Load NO
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related DI[1..10]
Parameters
Remarks Connections for DI[1..10] parameter to accept an input with both value and
status.

- 801 -
Chapter 6 - Dxxxx Parameters

6.161 DISTS[1..10]

Specific to Block GRPCAPRBK


(s)
Description Indicates DI[1..10] input Status
Data Type Enumeration: PVSTS
Range NORMAL, BAD, MANUAL, UNCERTN
Default BAD
Config Load NO
Active Loadable No
Access Lock View only
Residence CEE
Related DI[1..10]
Parameters
Remarks If this input is Bad, then corresponding DI[*] will not be considered for
computation of capability.

6.162 DITYPE

Specific to DICHANNEL; DICHANNEL (Series C I/O)


Block(s)
Description Digital Input Type. Defines the type of digital input point.
Data Type Enumeration
Range STATUS (0): For this Digital Input type, the PVAUTO value represents the
state of raw input(PVRAW) signal after direct/reverse
(INPTDIR) conversion is performed.
LATCHED (1): When configured as a latched input channel, an input pulse
that is ON for a minimum of 40 milliseconds is latched ON for
1.5 seconds.
ACCUM (2) Pulses are accumulated.
Default STATUS (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related N/A
Parameters
Remarks Accumulator type is not supported. Accumulator type is supported only for UIO - DI
CHANNEL 15 to 18.

- 802 -
Chapter 6 - Dxxxx Parameters

6.163 DLCNBSLOT

Specific to IOM
Block(s)
Description Downlink ControlNet Module Slot Number in Chassis.
Data Type 32-Bit Integer
Range 0 to (chassis size - 1)
Default 0
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence SR
Related IOMSLOT ULCNBMAC
Parameters
Remarks DLCNBSLOT refers to the physical slot number of the controller rack's CNI module.
That CNI module acts as the downlink to the remote I/O chassis of interest. Note
that the slot numbers start at zero, on the left side of the rack. If configuring an IOM
located in the same chassis as the controller, leave this parameter set to the default
value of zero.

6.164 DL_RPI

Specific to EIP Relay: 193DNEN_E3, 193DNEN_E3P


Block(s)
Description Update rate for Data Link
Data Type UINT16
Range 0 - 65535
Default 500
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related None
Parameters
Remarks Specifies the rate at which the Advance Data Status parameter will be updated
from the E3/E3-plus Relay hardware.

- 803 -
Chapter 6 - Dxxxx Parameters

6.165 DLINKDLRROLE

Specific to Block UOC


(s)
Description Configured Role of UOC in DLR Ring.
Data Type
Range Disabled
Member
Supervisor
Default
Config Load
Active Loadable
Access Lock
Residence
Related
Parameters
Remarks The default is Supervisor. When the UOC is the Active Supervisor, additional DLR
ring status is available.

6.166 DLINK1FAILED

Specific to Block(s) EIM


Description ETH 1 Failed
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks True if ETH 1 network interface is disconnected.

Specific to Block(s) UOC


Description ETH 3 Failed
Data Type BOOLEAN
Range N/A
Default 0
Config Load No
Active Loadable

- 804 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Downlink error condition. The ETH3 network interface is disconnected or
failed.

Specific to Block ELCN_NODE


(s)
Description ETH 1 Failed
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This is applicable only for ELCN NG node. True if ETH 1 network interface is
disconnected.

6.167 DLINK1FRAMECRCERR

Specific to Block(s) EIM


Description ETH 1 Frame CRC Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Frame CRC errors detected on the ETH 1 interface.

Specific to Block(s) UOC


Description ETH 3 Frame CRC Errors
Data Type UINT32
Range 0 to 4294967295
Default 0

- 805 -
Chapter 6 - Dxxxx Parameters

Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Downlink ETH3 frame CRC errors.

6.168 DLINK1LANIDERR

Specific to Block(s) EIM


Description ETH 1 LAN ID Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks LAN ID errors detected on ETH 1 interface.

Specific to UOC
Block(s)
Description ETH 3 LAN ID Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink ETH3 HSR LAN ID errors. This parameter increments when the HSR ring
is incorrectly connected. All nodes on the HSR ring should be connected ETH3-to-
ETH4 only, never ETH3-to-ETH3 or ETH4-to-ETH4.

- 806 -
Chapter 6 - Dxxxx Parameters

6.169 DLINK1MACADDR

Specific to EIM
Block(s)
Description Downlink MAC Address
Data Type STRING
Range NA
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks MAC address for ETH/downlink network interface. Note that HSR/PRP uses a
single MAC address for both ETH 1 and ETH 2 interfaces.

Specific to UOC
Block(s)
Description Downlink MAC Address
Data Type STRING
Range NA
Default
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink ETH3 MAC address. Note that the same MAC address applies to both
ETH3 and ETH4 on systems using the Star-PRP or Ring-HSR connection type.

6.170 DLINK1LASTACTIVE

Specific to Block(s) UOC


Description The IP Address or MAC Address of the last active node detected on Port 3 of
the UOC.
Data Type String
Range
Default
Config Load

- 807 -
Chapter 6 - Dxxxx Parameters

Active Loadable
Access Lock
Residence
Related
Parameters
Remarks If this module is not the Active Supervisor, Not Available is shown.

6.171 DLINK2LASTACTIVE

Specific to Block(s) UOC


Description The IP Address or MAC Address of the last active node detected on Port 2 of
the UOC.
Data Type String
Range
Default
Config Load
Active Loadable
Access Lock
Residence
Related
Parameters
Remarks If this module is not the Active Supervisor, Not Available is shown.

6.172 DLINK2MACADDR

Specific to Block(s) UOC


Description Downlink MAC Address
Data Type STRING
Range N/A
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

- 808 -
Chapter 6 - Dxxxx Parameters

6.173 DLINK1RXRATE

Specific to Block(s) EIM


Description ETH 1 Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Packets per second received over ETH 1 interface.

Specific to Block(s) UOC


Description ETH 3 Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Downlink ETH3 receive rate, measured in packets per second.

Specific to Block ELCN_NODE


(s)
Description ETH 1 Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. Packets per second received over
ETH 1 interface

- 809 -
Chapter 6 - Dxxxx Parameters

6.174 DLINK1RXRATELIMIT

Specific to Block UOC, EIM, CN100


Description Downlink port 1 (EIM) or 3 (UOC, CN100) Rate limit exceeded
Data Type Boolean
Range True, False
Default False
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters DLINK1RXRATELIMIT
Remarks Soft Failure alarm

6.175 DLINK1RXRATEMAX

Specific to Block(s) EIM


Description ETH 1 Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks High water mark of packets per second received over ETH 1 interface.

Specific to UOC
Block(s)
Description ETH 3 Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active
Loadable

- 810 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Downlink ETH3 receive rate high water mark, measured in packets per second.
Note that the high water mark is reset using the "reset statistics" command.

Specific to ELCN_NODE
Block(s)
Description ETH 1 Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. High water mark of packets per second
received over ETH 1 interface.

6.176 DLINK1SILENT

Specific to Block(s) EIM


Description ETH 1 Silent
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks True if ETH 1 network interface is silent (connected but receiving no
packets).

- 811 -
Chapter 6 - Dxxxx Parameters

Specific to Block UOC


(s)
Description ETH 3 Silent
Data Type BOOLEAN
Range N/A
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink error condition. The ETH3 network interface is connected but no
traffic is detected.

Specific to ELCN_NODE
Block(s)
Description ETH 1 Silent
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. True if ETH 1 network interface is silent
(connected but receiving no packets).This is analogous to ETH1SILENT.

6.177 DLINK1TXRATE

Specific to Block(s) EIM


Description ETH 1 Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No

- 812 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks Packets per second transmitted over ETH 1 interface.

Specific to Block(s) UOC


Description ETH 3 Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Downlink ETH3 transmit rate, measured in packets per second.

Specific to Block ELCN_NODE


(s)
Description ETH 1 Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. Packets per second transmitted over
ETH 1 interface.

6.178 DLINK1TXRATEMAX

Specific to Block(s) EIM


Description ETH 1 Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No

- 813 -
Chapter 6 - Dxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks High water mark of packets per second transmitted over ETH 1 interface.

Specific to UOC
Block(s)
Description ETH 3 Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink ETH3 transmit rate high water mark, measured in packets per second.
Note that the high water mark is reset using the "reset statistics" command.

Specific to ELCN_NODE
Block(s)
Description ETH 1 Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. High water mark of packets per second
transmitted over ETH 1 interface.

- 814 -
Chapter 6 - Dxxxx Parameters

6.179 DLINK2FAILED

Specific to Block(s) EIM


Description ETH 2 Failed
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks True if ETH 2 network interface is disconnected.

Specific to Block(s) UOC


Description ETH 4 Failed
Data Type BOOLEAN
Range N/A
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink error condition. The ETH4 network interface is disconnected or
failed.

Specific to Block ELCN_NODE


(s)
Description ETH 2 Failed
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. True if ETH 2 network interface is
disconnected.

- 815 -
Chapter 6 - Dxxxx Parameters

6.180 DLINK2FRAMECRCERR

Specific to Block(s) EIM


Description ETH 2 Frame CRC Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Frame CRC errors detected on the ETH 2 interface.

Specific to Block(s) UOC


Description ETH 4 Frame CRC Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Downlink ETH4 frame CRC errors.

6.181 DLINK2LANIDERR

Specific to Block(s) EIM


Description ETH 2 LAN ID Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks LAN ID errors detected on ETH 2 interface.

- 816 -
Chapter 6 - Dxxxx Parameters

Specific to UOC
Block(s)
Description ETH 4 LAN ID Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink ETH4 HSR LAN ID errors. This parameter increments when the HSR ring
is incorrectly connected. All nodes on the HSR ring should be connected ETH3-to-
ETH4 only, never ETH3-to-ETH3 or ETH4-to-ETH4.

6.182 DLINK2SILENT

Specific to Block(s) EIM


Description ETH 2 Silent
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters
Remarks True if ETH s network interface is silent (connected but receiving no
packets).

Specific to Block UOC


(s)
Description ETH 4 Silent
Data Type BOOLEAN
Range N/A
Default 0
Config Load No
Active Loadable

- 817 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Downlink error condition. The ETH4 network interface is connected but no
traffic is detected.

Specific to ELCN_NODE
Block(s)
Description ETH 2 Silent
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NoLoad
Related
Parameters
Remarks This is applicable only for ELCN NG node. This is analogous to ETH1SILENT.True if
ETH s network interface is silent (connected but receiving no packets).

6.183 DLINK2RXRATE

Specific to Block(s) EIM


Description ETH 2 Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Packets per second received over ETH 2 interface.

Specific to Block(s) UOC


Description ETH 4 Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0

- 818 -
Chapter 6 - Dxxxx Parameters

Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Downlink ETH4 receive rate, measured in packets per second.

Specific to Block ELCN_NODE


(s)
Description ETH 2 Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. Packets per second received over
ETH 2 interface.

6.184 DLINK2RXRATELIMIT

Specific to Block UOC, EIM, CN100


Description Downlink port 1 (EIM) or 3 (UOC, CN100) Rate limit exceeded
Data Type Boolean
Range True, False
Default False
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters DLINK2RXRATELIMIT
Remarks Soft Failure alarm.

- 819 -
Chapter 6 - Dxxxx Parameters

6.185 DLINK2RXRATEMAX

Specific to Block(s) EIM


Description ETH 2 Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks High water mark of packets per second received over ETH 2 interface.

Specific to UOC
Block(s)
Description ETH 4 Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink ETH4 receive rate high water mark, measured in packets per second.
Note that the high water mark is reset using the "reset statistics" command.

Specific to ELCN_NODE
Block(s)
Description ETH 2 Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable

- 820 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. High water mark of packets per second
received over ETH 2 interface.

6.186 DLINK2TXRATE

Specific to Block(s) EIM


Description ETH 2 Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Packets per second transmitted over ETH 2 interface.

Specific to Block(s) UOC


Description ETH 4 Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Downlink ETH4 transmit rate, measured in packets per second.

Specific to Block ELCN_NODE


(s)
Description ETH 2 Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No

- 821 -
Chapter 6 - Dxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. Packets per second transmitted over
ETH 2 interface.

6.187 DLINK2TXRATEMAX

Specific to EIM
Block(s)
Description ETH 2 Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Abbreviation name is used when alarms are published to remote servers via DSA.
This allows a short name to be used in the alarm summary to represent the source
server for the alarm.

Specific to UOC
Block(s)
Description ETH 4 Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink ETH4 transmit rate high water mark, measured in packets per second.
Note that the high water mark is reset using the "reset statistics" command.

- 822 -
Chapter 6 - Dxxxx Parameters

Specific to ELCN_NODE
Block(s)
Description ETH 2 Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. Abbreviation name is used when alarms
are published to remote servers via DSA. This allows a short name to be used in the
alarm summary to represent the source server for the alarm.

6.188 DLINKDUPEADDR

Specific to Block(s) EIM


Description Duplicate IP Address Detected
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks True if a duplicate IP address is detected on the ETH/downlink network.

Specific to UOC
Block(s)
Description Duplicate IP Address Detected
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active
Loadable

- 823 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Downlink error condition. A duplicate IP address is detected on the downlink
network. User must either change the downlink IP address or remove the duplicate
IP address from the downlink network.

Specific to ELCN_NODE
Block(s)
Description Duplicate IP Address Detected
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. True if a duplicate IP address is
detected on the ETH/downlink network.

6.189 DLINKENABLE

Specific to Block(s) UOC


Description Enable Downlink Network Interface
Data Type BOOLEAN
Exposure NONE

Range N/A
Default TRUE
Config Load Yes
Active Loadable
Access Lock Engineer
Residence CEE
Related Parameters All other DLINK parameters on tab.

Remarks Downlink configuration. Enable or disable the downlink network interface.

- 824 -
Chapter 6 - Dxxxx Parameters

6.190 DLINKHELP2

Specific to UOC
Block(s)
Description Downlink Network Configuration Help Text
Data Type STRING
Range N/A
Default Choose "Ring-HSR" when connecting to an HSR network using the ETH 3 and ETH 4
ports. EPMs must be configured with their x100 switch at position 3.
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks

6.191 DLINKHELP

Specific to UOC
Block(s)
Description Downlink Network Configuration Help Text
Data Type STRING
Range N/A
Default Choose "Non-redundant" when connecting to a DLR network using the ETH 3 port and
an external DLR switch. EPMs must be configured with their x100 switch at position 4.
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks

- 825 -
Chapter 6 - Dxxxx Parameters

6.192 DLINKNETWORKERR

Specific to EIM Platform Block


Block(s)
Description Downlink Network Error
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks True if a diagnostic error is detected on the downlink network. See the “downlink”
tab for additional diagnostic parameters.

Specific to Block(s) UOC


Description Downlink Network Error
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Soft failure condition. One or more downlink network errors are detected.

6.193 DLINKIPADDR

Specific to Block(s) UOC


Description IP Address
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable

- 826 -
Chapter 6 - Dxxxx Parameters

Access Lock APPDEVONLY


Residence CEE
Related Parameters
Remarks This UOC's IP Address on the downlink network.

6.194 DLINKIPADDRMASK

Specific to Block(s) UOC


Description Subnet Mask
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence CEE
Related Parameters
Remarks The IP Address mask for the downlink subnet.
Downlink ETH3 receive rate, measured in packets per second.

6.195 DLINKIPADDRMASKSTR

Specific to Block(s) UOC


Description Subnet Mask
Data Type STRING
Range N/A
Default 0.0.0.0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SR
Related
Parameters
Remarks Downlink network IP Address String. An alternative representation of the IP
Address.
Note that the downlink network should be on a different subnet than the FTE
network.

- 827 -
Chapter 6 - Dxxxx Parameters

6.196 DLINKIPADDRSTR

Specific to Block(s) UOC


Description IP Address
Data Type STRING
Range N/A
Default 0.0.0.0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SR
Related Parameters
Remarks Downlink network subnet mask string.

6.197 DLINKPARTNERNOTVISIBLE

Specific to Block(s) EIM


Description Partner Not Visible On Downlink Network
Data Type BOOLEAN
Range N/A
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks True if the redundant partner device is not visible on the downlink network.

Specific to Block(s) UOC


Description Partner Not Visible On Downlink Network
Data Type BOOLEAN
Range N/A
Default Off
Config Load No
Active Loadable

- 828 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Soft failure condition. Redundant partner device is not visible on downlink
network.

6.198 DLINKNETWORKERR

Specific to EIM Platform Block


Block(s)
Description Downlink Network Error
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks True if a diagnostic error is detected on the downlink network. See the “downlink”
tab for additional diagnostic parameters.

Specific to Block(s) UOC


Description Downlink Network Error
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Soft failure condition. One or more downlink network errors are detected.

- 829 -
Chapter 6 - Dxxxx Parameters

6.199 DLINKRDNPROTO

Specific to UOC
Block(s)
Description Connection Type
Data Type ENUM
Range N/A
Default Non-redundant
Config Load Yes
Active
Loadable
Access APPDEVONLY
Lock
Residence CEE
Related
Parameters
Remarks Downlink connection type. Specifies the connection type of the downlink network,
typically non-redundant (when used to connect to a DLR network using external DLR-
based switches) or Ring-HSR (when used to natively connect to an HSR network).

6.200 DLINKRXERR

Specific to Block EIM


(s)
Description Downlink Receive Errors or Star-PRP (when used to connect to a parallel
switch tree).
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Receive errors on ETH/downlink network.

Specific to Block UOC


(s)
Description Downlink Receive Errors or Star-PRP (when used to connect to a parallel
switch tree).
Data Type UINT32
Range 0 to 4294967295
Default 0

- 830 -
Chapter 6 - Dxxxx Parameters

Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink receive error counter.

6.201 DLINKRXRATE

Specific to Block EIM


(s)
Description Total Rx Rate (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Kilobits per second received over ETH/downlink network (both ETH 1 and ETH
2 interfaces).

Specific to Block(s) UOC


Description Total Rx Rate (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Downlink receive rate, measured in kilobits per second.

Specific to Block(s) ELCN_NODE


Description Total Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0

- 831 -
Chapter 6 - Dxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks This is applicable only for ELCN NG node. This is NG-to-NG traffic.

6.202 DLINKRXRATEMAX

Specific to EIM
Block(s)
Description Total Rx Rate Max (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of kilobits per second received over ETH/downlink network
(both ETH 1 and ETH 2 interfaces).

Specific to UOC
Block(s)
Description Total Rx Rate Max (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink receive rate high water mark, measured in kilobits per second. Note that
the high water mark is reset using the "reset statistics" command.

- 832 -
Chapter 6 - Dxxxx Parameters

Specific to ELCN_NODE
Block(s)
Description Total Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. High water mark of packets per second
received over ETH interface.

6.203 DLINKTXERR

Specific to Block(s) EIM


Description Downlink Transmit Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Transmit errors on ETH/downlink network.

Specific to Block(s) UOC


Description Downlink Transmit Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Downlink transmit error counter.

- 833 -
Chapter 6 - Dxxxx Parameters

6.204 DLINKTXRATEMAX

Specific to EIM
Block(s)
Description Total Tx Rate Max (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of kilobits per second transmitted over ETH/downlink network
(both ETH 1 and ETH 2 interfaces).

Specific to UOC
Block(s)
Description Total Tx Rate Max (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Downlink transmit rate high water mark, measured in kilobits per second. Note that
the high water mark is reset using the "reset statistics" command.

Specific to ELCN_NODE
Block(s)
Description Total Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load NO
Active No
Loadable

- 834 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks This is applicable only for ELCN NG node. High water mark of packets per second
transmitted over ETH interface.

6.205 DLINKVLANID

Specific to Block(s) UOC


Description VLAN ID
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence CEE
Related Parameters
Remarks Downlink VLAN ID. Note that this setting is currently disabled.

6.206 DLRACTIVESUP

Specific to Block(s) UOC


Description The IP Address or MAC Address of the current Active Supervisor.
Data Type String
Range
Default
Config Load
Active Loadable
Access Lock
Residence
Related Parameters
Remarks

- 835 -
Chapter 6 - Dxxxx Parameters

6.207 DLRACTIVESUPPRI

Specific to Block(s) UOC


Description The Precedence value of the current Active Supervisor (highest configured
precedence)
Data Type
Range 0-255
Default
Config Load
Active Loadable
Access Lock
Residence
Related
Parameters
Remarks

6.208 DLRCURRENTROLE

Specific to Block UOC


(s)
Description The last two are error conditions.
Data Type
Range Backup Supervisor

Active Supervisor
Member
No Supervisor

Incompatible
Default
Config Load
Active Loadable
Access Lock
Residence
Related
Parameters
Remarks Incompatible refers to out of range Beacon Interval and Timeout. That condition
should not be seen.

- 836 -
Chapter 6 - Dxxxx Parameters

6.209 DLRFAULTCNT

Specific to UOC
Block(s)
Description A running count of the number of ring faults detected.
Data Type UINT32
Range
Default
Config Load
Active
Loadable
Access Lock
Residence
Related
Parameters
Remarks It increments once when the ring is broken. A UOC switchover will cause this count to
increment. Reset by Reset Statistics command and also reset by Recover from Rapid
Fault command.

6.210 DLRINTERVAL

Specific to UOC
Block(s)
Description Configured DLR Beacon transmit interval when Active Supervisor. Only
configurable when Supervisor is selected.
Data Type
Range 400-100000 usec
Default
Config Load
Active
Loadable
Access Lock
Residence
Related
Parameters
Remarks If this supervisor is not the current Active Supervisor, it will reflect the values of the
current Active Supervisor.

- 837 -
Chapter 6 - Dxxxx Parameters

6.211 DLRNODECOUNT

Specific to Block(s) UOC


Description The number of nodes participating in the DLR Ring.
Data Type UINT32
Range
Default
Config Load
Active Loadable
Access Lock
Residence
Related Parameters
Remarks It is possible that non-DLR-aware nodes are present that would not be
counted.

6.212 DLRPRECEDENCE

Specific to UOC
Block(s)
Description Active Supervisor precedence.
Data Type
Range 0-255
Default
Config Load
Active
Loadable
Access Lock
Residence
Related
Parameters
Remarks An Active Supervisor will yield to another with a higher precedence. Only configurable
when Supervisor is selected. Secondary is primary value -1; therefore, the minimum
configured value is 1.

6.213 DLRRESETFAULT

Specific to Block(s) UOC


Description Used to reset the Rapid Fault condition that removed the module from the
ring.
Data Type
Range Recover from Rapid Fault
Command

- 838 -
Chapter 6 - Dxxxx Parameters

Default
Config Load
Active Loadable
Access Lock
Residence
Related Parameters
Remarks It also resets the DLR Fault Count.

6.214 DLRRINGFAULT

Specific to Block UOC


(s)
Description Indicates that the DLR is in Rapid Fault or a non-Ring condition.
Data Type
Range Soft Failure
Default
Config Load
Active Loadable
Access Lock
Residence
Related
Parameters
Remarks All of the Soft Failures on the Downlink TAB drive the Downlink Network Error on
the Soft Failures Tab.

6.215 DLRRINGMODE

Specific to Block(s) UOC


Description The current operating mode of the DLR system.
Data Type Linear
Ring
Range
Default
Config Load
Active Loadable
Access Lock
Residence
Related Parameters
Remarks Linear is shown if the ring was never closed.

- 839 -
Chapter 6 - Dxxxx Parameters

6.216 DLRRINGSTATE

Specific to UOC
Block(s)
Description The current state of the DLR system.
Data Type
Range Normal
Fault
UnexpectedLoop
PartialFault
RapidFault
Default
Config Load
Active
Loadable
Access
Lock
Residence
Related
Parameters
Remarks The current state of the DLR system.
Fault means the ring is not operating normally from this nodes point-of-view. It is
likely that only one or two nodes may report a ring fault.
PartialFault meaning is not specified.

RapidFault is a condition that arises when there are five cable disconnects within 30
seconds, and the ring is broken in only one direction. At that point, the DLR system is
disabled to allow the remainder of the ring to recover. RapidFault requires the user to
resolve the condition and then issue the Recover from Rapid Fault command. This
only applies to the Active Supervisor.
UnexpectedLoop is a condition where there appears to be an extra connection
between ring switches that causes duplicate traffic to be seen. Locate and remove
the loop.

6.217 DLRTIMEOUT

Specific to UOC
Block(s)
Description DLR Beacon Timeout Interval.
Data Type
Range 800-500000 usec
Default
Config Load
Active
Loadable

- 840 -
Chapter 6 - Dxxxx Parameters

Access Lock
Residence
Related
Parameters
Remarks The Timeout Interval must be 2-3x the Beacon Interval.
Only configurable when Supervisor is selected.
If this Supervisor is not the current Active Supervisor, it will reflect the values of the
current Active Supervisor

6.218 DLRVERIFYFAULTLOC

Specific to Block(s) UOC


Description Used in Active Supervisor when there is a ring fault.
Data Type
Range Update Fault Location
Command
Default
Config Load
Active Loadable
Access Lock
Residence
Related
Parameters
Remarks It will update the Last Active Node addresses to help in troubleshooting a ring
break.

6.219 DLYTIME

Specific to DICHANNEL (PM I/O) ; DICHANNEL (Series C I/O)


Block(s)
Description Delay Time. Specifies the time in seconds that a point in alarm is to be held in the
alarm state even if the condition clears.
Data Type 8-Bit Unsigned Integer
Range 0 to 60 seconds
Default 5 seconds
Config Yes
Load
Active No
Loadable

- 841 -
Chapter 6 - Dxxxx Parameters

Access Lock Engineer


Residence IOM
Related N/A
Parameters
Remarks This parameter is only exposed when the ASSOCIOPTYP is DISOE and the ALMOPT
configuration is not NONE. For an off-normal alarm: If an alarm condition exists
when the delay timer expires, the point is held alarm. For a change of state (COS)
alarm: If the PV is in the same state when the delay timer expires, future state
changes are immediately alarmed. If the PV is in the opposite state, a second COS
alarm is produced and the delay timer is restarted.

6.220 DO[1..3]

Specific to DevCtl
Block(s)
Description Digital Output Values
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related GOPFINAL, NUMDOUTSOPDOMAP[0..3][1..3]OPFINAL
Parameters
Remarks Only valid if NUMDOUTS allows the respective output. DO[i] and PO[i] cannot be
connected simultaneously.

6.221 DOMSO

Specific to Block(s) DOC


Description Output value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 842 -
Chapter 6 - Dxxxx Parameters

6.222 DOMSO[0..numChans-1]

Specific to Block(s) DOM


Description Output value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

6.223 DONEFL

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Done Flag - Triggered request has completed.
Data Type Boolean
Range True/False
Default False
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks
ATTENTION The DONEFL parameter must not be used
with PCDI blocks when the AUTOTRIGGER parameter is
enabled.

6.224 DOOP

Specific to Block Universal IO module


(s)
Description PWM Percent Output - Displays OP in the DO Status Tab of the UIO module.
Data Type FLOAT64
Range 0.0 to 100.0 %
Default 0.0 %

- 843 -
Chapter 6 - Dxxxx Parameters

Config Load No
Access Lock ViewOnly
Active Loadable No
Residence IOM
Related Series C DOCHANNEL: OP
Parameters
Remarks The OP is the percent on time for the pulsed output when the DO Channel is
configured for PWM.

6.225 DOPTEXECST

Specific to Universal IO module


Block(s)
Description Point Execution State - Displays the point execution state in the DO Status tab of
the UIO module.
Data Type Enumeration
Range 0 Inactive Point is not scanned or
processed.
1 Active Point is scanned and
processed.
Default Inactive
Config Load No
Access Lock ViewOnly
Active No
Loadable
Residence IOM
Related PTEXECSTAIPTEXECSTAOPTEXECSTDIPTEXECST
Parameters
Remarks This parameter displays the point execution state of UIO module in the DO Status
Data tab. When PTEXECST is Inactive, the point processing does not occur for the
channel.

6.226 DOSTYPE

Specific to DOCHANNEL (PM I/O) ; DOCHANNEL (Series C I/O)


Block(s)
Description Digital Output (DO) Slot Type. Determines the type of digital output slot.
Data Type Enumeration
Range 0 NONE STATUS and No
Connection, or Not
Configured.
1 UNKNOWN Unknown
2 SONOTCONF Status Output Not

- 844 -
Chapter 6 - Dxxxx Parameters

Configured
3 SOPOINT Status Output Configured
as Point
4 SOCOMPONENT Status Output Configured
as Component
5 ONPULSE ONPULSE Connected
6 OFFPULSE OFFPULSE Connected
7 OPNOTCONF OP Not Configured
8 OPPOINT
9 OPCOMPONENT
Default NONE
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks This parameter is set at configuration time based on DOPTYPE and the
Connections. This parameter does not appear on the Configuration form, but can
be monitored on the block faceplate.

6.227 DOTNETVER[0..1]

Specific to CAB types


Block(s)
Description Dot Net Version. A one or two element array that contains the version of .NET
framework that was used to build the user's CAB program. It is set by the CAB Build
environment when a CAB type is created or edited.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type String
Range 32 characters
Default Blank
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence System Repository
Related CABSOFTVER, OSVER
Parameters
Remarks CAB/C300 does not support the parameter DOTNETVER. Attempts to read it from a
loaded CAB/C300 instance always return blank.

- 845 -
Chapter 6 - Dxxxx Parameters

6.228 DOTYPE

Specific to Block(s) DOCHANNEL (PM I/O)


Description Digital Output (DO) Type. Determines the type of digital output point.
Data Type Enumeration
Range STATUS (0): Status output type.
PWM (1): Pulse Width Modulated output type.
Default STATUS (0)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence IOM
Related Parameters N/A
Remarks Determines the type of digital output point.

Specific to Block DOCHANNEL (Series C I/O)


(s)
Description Digital Output (DO) Type. Determines the type of digital output point.
Data Type Enumeration
Range 0 Status Status output type.
1 PWM Pulse Width Modulated output type.
2 OnPulse Used to drive an on pulse to a field
device
3 OffPulse Used to drive an off pulse to a field
device
Default STATUS (0)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence IOM
Related
Parameters
Remarks Determines the type of digital output point.

Specific to Block(s) PBDOCHANNEL


Description Digital Output (DO) Type. Determines the type of digital output point.
Data Type Enumeration
Range 0 NULL
1 SO
2 ONPULSE
3 OFFPULSE
Default (1) SO

- 846 -
Chapter 6 - Dxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Determines the type of digital output point. The PGM supports only the SO
type.

6.229 DOVALSTS[1..2]

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description DO Value Status
Data Type Structure
Range
Default
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CMDRUN (Open) CMDSTOP (Close)
Remarks

6.230 DOWNLINKFAIL

Specific to Block(s) TCMI


Description Downlink Fail (Socket Communication Error)
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 847 -
Chapter 6 - Dxxxx Parameters

6.231 DP

Specific to Block(s) LEVELCOMP


Description Differential Pressure
Data Type Float64
Range N/A
Default NaN
Config Load NO
Active Loadable No
Access Lock Program
Residence CEE
Related Parameters DPBIASDPSLOPE
Remarks The Differential pressure input from the DP transmitter is connected here.

6.232 DPBIAS

Specific to LEVELCOMP
Block(s)
Description DP bias
Data Type Float64
Range
Default 0
Config Load YES
Active No
Loadable
Access Lock Engineer when CM is INACTIVE
Residence CEE
Related DPDPSLOPE
Parameters
Remarks This parameter participates in ranging required for the DP using the formula of a
straight line y = mx +c where m is the slope and c is bias constant. X is the incoming
quantity and y is the revised input.

6.233 DPENGUNIT

Specific to Block(s) LEVELCOMP


Description DP Engineering Unit Selection
Data Type Enumeration
Range mmwc, Pascal, INWC, mbar
Default mmwc

- 848 -
Chapter 6 - Dxxxx Parameters

Config Load YES


Active Loadable No
Access Lock APPDEV Only
Residence CEE
Related Parameters DPDPBIASDPSLOPE
Remarks This parameter indicates the engineering unit of the value fed to DP.

6.234 DPSLOPE

Specific to LEVELCOMP
Block(s)
Description DP slope
Data Type Float64
Range
Default 1
Config Load YES
Active No
Loadable
Access Lock Engineer when CM is INACTIVE
Residence CEE
Related DPDPBIAS
Parameters
Remarks This parameter participates in ranging required for the DP using the formula of a
straight line y = mx +c where m is the slope and c is bias constant. X is the incoming
quantity and y is the revised DP.

6.235 DPV

Specific to Block(s) AUXSUMMER, DEADTIME, LEADLAG


Description Overall bias for PV - A bias that is applied to the calculation of PV.
Data Type Real Number
Range
Default 0.0
Config Load Yes
Active Loadable No
Access Lock DEADTIME: Supervisor AUXSUMMER and LEADLAG: Engineer
Residence CEE
Related Parameters PV
Remarks

- 849 -
Chapter 6 - Dxxxx Parameters

6.236 DRAWINGINFO

Specific to Block(s) Cabinets


Description It provides the file path of the cabinet.
Data Type String
Range 0 – 255
Default —
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SRAL
Related Parameters
Remarks

6.237 DRIVERNAME

Specific to Block(s) CPM, RM


Description Network Driver Name
Data Type String
Range Length: 255 characters
Default Null String
Config Load No
Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters ABORTALM.PR
Remarks

6.238 DRIVERNAME

Specific to Block All EtherNet/IP ArmorPoint I/O modules


(s)
Description Adapter name — This parameter represents the Adapter that the I/O module is
associated with.
Data Type BLOCKID
Range
Default
Config Load Yes
Active Loadable No

- 850 -
Chapter 6 - Dxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related
Parameters
Remarks

6.239 DRVMEMFREE

Specific to IEC61850LINK–memory driver


Block(s)
Description Memory in kilobytes available for stack allocations. The value is calculated by
Memory pools free + DRVMEMRESERVED – Pools ram used.
Data Type Unsigned Integer
Range 0 - 4294967295
Default 0
Config Load Yes
Active No
Loadable
Access Lock View Only
Residence CEE
Related DRVMEMRESERVED, DRVMEMUSED
Parameters
Remarks This value should never be zero due to the required 2 MB minimum before loading
an SCL file.

6.240 DRVMEMRESERVED

Specific to Block(s) IEC61850LINK–memory driver


Description Memory in kilobytes reserved for IEC 61850 stack.
Data Type Unsigned Integer
Range 0 - 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock View Only
Residence CEE
Related Parameters DRVMEMUSED, DRVMEMFREE
Remarks The amount of reserved memory for 850M hardware is a constant 27 MB.

- 851 -
Chapter 6 - Dxxxx Parameters

6.241 DRVMEMUSED

Specific to Block(s) IEC61850LINK–memory driver


Description Memory in kilobytes used by the IEC 61850 stack.
Data Type Unsigned Integer
Range 0 - 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock View Only
Residence CEE
Related DRVMEMRESERVED, DRVMEMFREE
Parameters
Remarks This value will never be zero while the application is running on the
controller.

6.242 DS_SET

Specific to Block(s) EIM


Description DataSet Setting
Data Type ENUM
Range NA
Default Dynamic
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

6.243 DSBLSYNCCMD

Specific to C300 and FIM4, EHG, PGM, TCMI


Block(s)
Description Disable Synchronization
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load No

- 852 -
Chapter 6 - Dxxxx Parameters

Active No
Loadable
Access Lock Operator
Residence C300, FIM4, EHG, PGM
Related ENBLSYNCCMD
Parameters
Remarks Used to disable synchronization (and/or disable auto-synchronization). This
parameter has edge trigger semantics and always returns OFF when read.

Specific to Block(s) UOC


Description Disable Synchronization
Data Type Boolean
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock Operator
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

6.244 DSMAPBLKID

Specific to Block(s) EIM


Description Dataset Map Block
Data Type BLOCKID
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks Shows DSMAP block reference

- 853 -
Chapter 6 - Dxxxx Parameters

6.245 DSMAPCONNVAL

Specific to Block(s) EIM


Description DSMAP Reference
Data Type Any
Range
Default
Config Load
Active Loadable No
Access Lock OtherFb
Residence NOLOAD
Related Parameters
Remarks

6.246 DSPARAMALIAS

Specific to Block(s) EIM


Description Alias Name
Data Type STRING
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

6.247 DSPARAMCOUNT

Specific to Block(s) EIM


Description DataSet Param Count
Data Type UINT16
Range 65535
Default 0
Config Load
Active Loadable No

- 854 -
Chapter 6 - Dxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related Parameters
Remarks

6.248 DSPARAMRCBBLOB

Specific to Block(s) EIM


Description MMS blob
Data Type BLOB
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

6.249 DSPARAMRCBBLOBCRC

Specific to Block(s) EIM


Description MMS blob crc
Data Type UINT32
Range 4294967295
Default 0
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

- 855 -
Chapter 6 - Dxxxx Parameters

6.250 DSPARAMRCBBLOBSIZE

Specific to Block(s) EIM


Description MMS blob size in bytes
Data Type UINT32
Range 4294967295
Default 0
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

6.251 DSPARAMRCBBLOBARRCOUNT

Specific to Block(s) EIM


Description MMS blob Array Count
Data Type UINT16
Range 65535
Default 0
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

6.252 DSSOURCE

Specific to Block(s) EIM


Description Dataset Source Block
Data Type BLOCKID
Range NA
Default
Config Load Yes
Active Loadable No

- 856 -
Chapter 6 - Dxxxx Parameters

Access Lock AppDevOnly


Residence SR
Related Parameters
Remarks Shows SUBSCRIBER block reference

6.253 DTANORM

Specific to EXECTIMER
Block(s)
Description Delta Time Average NORMalization factor
Data Type FLOAT64
Range
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related DTIMEAVGCOMP, DTIMEAVG, DTAOFFSET, DTASCALE
Parameters
Remarks DTANORM is the denominator applied to DTIMEAVG in computing
DTIMEAVGCOMP. For details refer to DTIMEAVGCOMP.

6.254 DTAOFFSET

Specific to EXECTIMER
Block(s)
Description Delta Time Average OFFSET
Data Type FLOAT64
Range
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related DTIMEAVGCOMP, DTIMEAVG, DTANORM, DTASCALE
Parameters
Remarks DTAOFFSET is the subtractive offset applied to DTIMEAVG in computing
DTIMEAVGCOMP. For details refer to DTIMEAVGCOMP.

- 857 -
Chapter 6 - Dxxxx Parameters

6.255 DTASCALE

Specific to EXECTIMER
Block(s)
Description Delta Time Average SCALE factor
Data Type FLOAT64
Range
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related DTIMEAVGCOMP, DTIMEAVG, DTANORM, DTAOFFSET
Parameters
Remarks DTASCALE is the numerator applied to DTIMAVG in computing DTIMEAVGCOMP.
For details refer to DTIMEAVGCOMP.

6.256 DTIME

Specific to EXECTIMER
Block(s)
Description Delta TIME
Data Type FLOAT64
Range
Default NaN
Config No
Load
Active No
Loadable
Access Lock View Only
Residence CEE
Related DTIMEAVG, DTIMEMIN, DTIMEMAX, DTIMESTD
Parameters
Remarks Instantaneous measurement of delta time in units of microseconds.Always shows
NaN on the EXECTIMER instance used to establish the beginning of the time
interval. Shows non-NaN on the EXECTIMER instance used to establish the end of
the time interval if the following holds true:
l TIMEIN parameter of block instance is connected.
l TIMEIN parameter of block instance is receiving a good value.
l Block instance is enabled.
l Block instance is executing.
>DTIME captures the difference between the current time read by the end
instance and the time value received through parameter TIMEIN.

- 858 -
Chapter 6 - Dxxxx Parameters

6.257 DTIMEAVG

Specific to EXECTIMER
Block(s)
Description Delta TIME AVeraGe
Data Type FLOAT64
Range
Default NaN
Config Load No
Active No
Loadable
Access Lock View only
Residence CEE
Related DTIME, DTIMESTD, DTIMEAVGCOMP, DTIMEAVG, ACTREMOVETYPE
Parameters
Remarks DTIMEAVG is the rolling time average of instantaneous DTIME values. The time
interval of the rolling average is established by parameter TAU. The averaging is
reset by writing On to parameter RESET.

6.258 DTIMEAVGCOMP

Specific to EXECTIMER
Block(s)
Description Delta TIME AVeraGe COMPensated
Data Type FLOAT64
Range
Default NaN
Config No
Load
Active No
Loadable
Access Lock View only
Residence CEE
Related DTIMEAVG, DTAOFFSET, DTANORM, DTASCALE
Parameters
Remarks Value of DTIMEAVG after application of negative offset and scale factors. Value is
computed as follows. DTIMEAVGCOMP = (DTIMEAVG - DTAOFFSET) * DTASCALE /
DTANORM. DTIMEAVGCOMP and its associated configuration parameters can
optionally be used for tasks such as the following:
l Subtract out the small timing overhead not associated with the block or
module under measurement.
l Attempt to compensate for other factors by scaling up or down a
measurement.

- 859 -
Chapter 6 - Dxxxx Parameters

6.259 DTIMEMAX

Specific to Block(s) EXECTIMER


Description Delta Time MAXimum
Data Type FLOAT64
Range
Default NaN
Config Load No
Active Loadable No
Access Lock View only
Residence CEE
Related Parameters DTIME, ACTREMOVETYPE
Remarks Maximum value of DTIME since RESET was last set to On.

6.260 DTIMEMIN

Specific to Block(s) EXECTIMER


Description Delta Time MINimum
Data Type FLOAT64
Range
Default NaN
Config Load No
Active Loadable No
Access Lock View only
Residence CEE
Related Parameters DTIME, ACTREMOVETYPE
Remarks Minimum value of DTIME since RESET was last set to On.

6.261 DTIMESTD

Specific to EXECTIMER
Block(s)
Description Delta TIME STandard Deviation
Data Type FLOAT64
Range
Default NaN
Config No
Load
Active No

- 860 -
Chapter 6 - Dxxxx Parameters

Loadable
Access Lock View only
Residence CEE
Related DTIME, DTIMEAVG, DTIMESTDPRC
Parameters
Remarks DTIMESTD is the square root of the time variance in the DTIME values. It presents
a rolling estimate of the standard deviation of the DTIME values in the same way
that DTIMEAVG presents the rolling average of the DTIME values. The time interval
over which the estimate is constructed is established by parameter TAU. The
averaging is reinitialized whenever parameter RESET is set to On.

6.262 DTIMESTDPRC

Specific to Block EXECTIMER


(s)
Description Delta TIME STandard Deviation in PeRCent
Data Type FLOAT64
Range
Default NaN
Config Load No
Active Loadable No
Access Lock View only
Residence CEE
Related DTIME, DTIMEAVG, DTIMESTD
Parameters
Remarks DTIMESTDPRC is computed as follows. DTIMESTDPRC = 100.0 * DTIMESTD /
DTIMEAVG

6.263 DUPIOLADDR

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Duplicate I/O Link Address Detected
Data Type Boolean
Range Off (0): Duplicate address not detected.
On (1): Duplicate address detected.
Default Off (0)
Config Load No
Active No
Loadable

- 861 -
Chapter 6 - Dxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related
Parameters
Remarks When this parameter is On, there is more than one IOLIINK interface connected
to the I/O link with the same physical address.

6.264 DUPIPIECNETWORK

Specific to Block(s) IEC61850M, IEC61850MSEC


Description Duplicate IP-IEC61850 Network
Data Type Boolean
Range 0 – Off – 1 – On –
Default 0 – Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence 850M
Related Parameters
Remarks

6.265 DV.ACTIVEPROCESSVALUE

Specific to Block(s) PROFITCTLIN


Description PV of downstream PID
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

- 862 -
Chapter 6 - Dxxxx Parameters

6.266 DV.ACTIVEVALUE

Specific to Block(s) PROFITCTLIN


Description ACTIVE actual value
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.267 DV.BIAS

Specific to Block(s) PROFITCTLIN


Description Bias for Simulation
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.268 DV.CRITICAL

Specific to Block(s) PROFITCTLIN


Description CRITICAL
Data Type ENUM
Range Yes (0), No (1)
Default YES
Config Load Yes
Active Loadable No

- 863 -
Chapter 6 - Dxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.269 DV.DESC

Specific to Block(s) PROFITCTLIN


Description Description
Data Type STRING
Range NA
Default DV DESC
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.270 DV.DVINDEX

Specific to Block(s) PROFITCTLIN


Description DV Index
Data Type INT16
Range ±32767
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

- 864 -
Chapter 6 - Dxxxx Parameters

6.271 DV.ENGGUNITS

Specific to Block(s) PROFITCTLIN


Description Engg. Units
Data Type STRING
Range NA
Default CELCIUS
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.272 DV.EXECSTATUS

Specific to Block(s) PROFITCTLIN


Description PID Status
Data Type ENUM
Range Inactive (0), Active (1)
Default INACTIVE
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.273 DV.ISBAD

Specific to Block(s) PROFITCTLIN


Description Indicates that DV is BAD
Data Type BOOL
Range FALSE, TRUE
Default False
Config Load Yes
Active Loadable No

- 865 -
Chapter 6 - Dxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.274 DV.NAME

Specific to Block(s) PROFITCTLIN


Description Name
Data Type STRING
Range NA
Default DV NAME
Config Load Yes
Active Loadable No
Access Lock APPDEVONLY
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.275 DV.PREVIOUSVAL

Specific to Block(s) PROFITCTLIN


Description Previous Value
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

- 866 -
Chapter 6 - Dxxxx Parameters

6.276 DV.PVVALRESET

Specific to Block(s) PROFITCTLIN


Description Reset Validation
Data Type BOOL
Range NA
Default False
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.277 DV.PVVALSTATUS

Specific to PROFITCTLIN
Block(s)
Description Status of PV Val
Data Type ENUM
Range VALID (0) HOLD (1) BAD (2 EXT (3) CLAMP_HI (4) CLAMP_LO (5) HI (6) LO (7) ROC
(8) FREEZE (9) OBSOLETE (10) REF (11) NA (12) INITIALIZING (13)
Default VALID
Config Load No
Active No
Loadable
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFDVS
Parameters
Remarks Arrayed parameter of size NUMBEROFDVS

6.278 DV.PVVALSTATUS_C

Specific to Block PROFITCTLIN


(s)
Description Color for PV Val
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)

- 867 -
Chapter 6 - Dxxxx Parameters

Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFDVS
Parameters
Remarks Arrayed parameter of size NUMBEROFDVS

6.279 DV.READPROCESSVAL

Specific to Block(s) PROFITCTLIN


Description PV value
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.280 DV.READVALUE

Specific to Block(s) PROFITCTLIN


Description SP OP) value
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

- 868 -
Chapter 6 - Dxxxx Parameters

6.281 DV.READVALUEPINCONN

Specific to Block(s) PROFITCTLIN


Description DV input Connector
Data Type INCONN
Range NA
Default NA
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks This is an Internal parameter

6.282 DV.SCALINGFACTOR

Specific to Block(s) PROFITCTLIN


Description Scaling factor
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.283 DV.STARTVALUE

Specific to Block(s) PROFITCTLIN


Description Start Value for Simulation
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load Yes
Active Loadable No

- 869 -
Chapter 6 - Dxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.284 DV.STATUS

Specific to Block(s) PROFITCTLIN


Description DV status (solver)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.285 DV.STATUSDISP

Specific to Block(s) PROFITCTLIN


Description DV Status
Data Type ENUM
Range DROP (0) CRIT (1) GOOD-C (2) GOOD (3) DROP-SC (4) CRIT-SC (5)
Default DROP
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

- 870 -
Chapter 6 - Dxxxx Parameters

6.286 DV.STATUSDISP_C

Specific to Block PROFITCTLIN


(s)
Description Color for Status Disp
Data Type ENUM
Range RED (0) BLUE (1) GREEN (2) YELLOW (3) MAGENTA (4) PURPLE (5) CYAN (6)
WHITE (7) BLACK (8)
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related NUMBEROFDVS
Parameters
Remarks Arrayed parameter of size NUMBEROFDVS

6.287 DV.TYPICALMOVESIZE

Specific to Block(s) PROFITCTLIN


Description Typical Move Size of this DV
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.288 DV.USETHISDV

Specific to Block(s) PROFITCTLIN


Description Use this DV
Data Type ENUM
Range No (0) Yes (1)
Default YES
Config Load Yes

- 871 -
Chapter 6 - Dxxxx Parameters

Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.289 DV.VALUE

Specific to Block(s) PROFITCTLIN


Description DV Value
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

6.290 DV.WINDUPSTATUS

Specific to Block(s) PROFITCTLIN


Description Windup status
Data Type ENUM
Range ERROR0 (0) NORMAL (1) HI (2) LO (3) HILO (4)
Default NORMAL
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters NUMBEROFDVS
Remarks Arrayed parameter of size NUMBEROFDVS

- 872 -
Chapter 6 - Dxxxx Parameters

6.291 DVRNGEXT

Specific to AICHANNEL, HAICHANNEL (PM I/O), AICHANNEL, (Series C)


Block(s)
Description Device PV Range
Data Type Structure, 16 bytes long
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks A parameter used within Experion PKS for obtaining the 4 parameters (HTDURL,
HPVURV, HPVLRV and HTDLRL) that form the basis of the Device PV range
settings.

6.292 DYNPEERALLOC

Specific to SCM, RCM


Block(s)
Description Flag to select whether peer memory for dynamic fetch is allocated either during
block load or dynamically prior to need for peer data.
Data Type Enumeration
Range 0 Load
1 Dynamic
Default Dynamic
Config CEE
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related PEERALGOPT
Parameters
Remarks This parameter is not available when the Dynamic Fetch Option (PEERALGOPT)
equals NONE. The non-default value Load (OFF) is provided only for strict backward
compability with Releases prior to R310. The recommended value for all applications
is Dynamic (ON).

- 873 -
Chapter 6 - Dxxxx Parameters

Specific to MR
Block(s)
Description Flag to select whether peer memory for dynamic fetch is allocated either during
block load or dynamically prior to need for peer data.
Data Type Enumeration
Range 0 Load
1 Dynamic
Default Dynamic
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PEERALGOPT
Parameters
Remarks This parameter is not available when the Dynamic Fetch Option (PEERALGOPT)
equals NONE.

6.293 DYNSTATE[1.255]

Specific to Block All


(s)
Description Dynamic State - Gives dynamic state of the block.
Data Type BLOB
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter is only used to support the save/restore dynamic snapshot
functions.

Specific to MR
Block(s)
Description Flag to select whether peer memory for dynamic fetch is allocated during block
load or dynamically prior to need for peer data.
Data Type Enumeration
Range 0 Load
1 Dynamic
Default Dynamic

- 874 -
Chapter 6 - Dxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PEERALGOPT
Parameters
Remarks This parameter is not available when the Dynamic Fetch Option (PEERALGOPT)
equals NONE.

- 875 -
CHAPTER

7 EXXXX PARAMETERS

7.1 EAGN 883


7.2 EAMRDATAPKTSPERSEC 883
7.3 EAMRMSGSPERSEC 884
7.4 EAMRPERCENTOPTAVG 884
7.5 EAMRRDNXFERMBPERSEC 885
7.6 EAMRSIGPKTSPERSEC 885
7.7 EAPPCONNTONSTATUS 886

7.8 EAPPNODEIP 886


7.9 EAPPNODENAME 887
7.10 ECHSWDESC[0...63] 887
7.11 EDGEDETECT 888
7.12 EDGEDETECT[0..7] 889
7.13 EDITLOCK 889
7.14 EEGSTATE 890
7.15 EFFECOPTSPEED 891
7.16 EHBADDED 891
7.17 EHBADDEDIP 892
7.18 EHBHWYNUM 892
7.19 EHBLC1 893
7.20 EHBLC2 893
7.21 EHBLCIP1 894
7.22 EHBLCIP2 894
7.23 EHBRMIP1 895
7.24 EHBRMIP2 896
7.25 EHBROLEFORBOX [5..63] 897
7.26 EHBTHIS 897
7.27 EHBTHISIP 898
7.28 EHPMDATAACCESS 898
7.29 EHPM_ERRCODE 899
7.30 EHPM_SELFTEST 900
7.31 EHPMSTATE 900
7.32 EICONNERRCODE[0..8] 901

- 876 -
Chapter 7 - Exxxx Parameters

7.33 EICONNERRINFO[0..8] 901


7.34 EICONNSTS[0..8] 902
7.35 EIOMTYPE 902
7.36 EIM_IPADDRESS 903
7.37 EIMNAME 903
7.38 EIMTYPE 904
7.39 EIMDISCONNECTDEVNAME 904
7.40 EIPATH[0..8] 904
7.41 EIPMODE 905
7.42 EIPSUPPORTED 905
7.43 EIPIOIPADDR 906
7.44 EIPIOCONNSTS 906
7.45 EIPIOSLOTNUM 907
7.46 ELCNBCOMMAND 908

7.47 ELCNBNUM 909


7.48 ELCNBSTATE 909
7.49 ELCNCOMMINV 910
7.50 ELCNLNGTHINV 910
7.51 ELCNMULTIIPADDRSTR 911
7.52 ELCNNODECOMMAND 912
7.53 ELCNNODENUM 912
7.54 ELCNNODENUMPARTNER 913
7.55 ELCNNODESTAT1 913
7.56 ELCNNODESTAT2 914
7.57 ELCNNODESTAT3 914
7.58 ELCNNODESTAT4 915
7.59 ELCNNODESTAT5 915
7.60 ELCNNODESTAT6 916
7.61 ELCNNODESTAT7 916
7.62 ELCNNODESTAT8 917
7.63 ELCNNODESTAT9 917
7.64 ELCNNODESTAT10 918
7.65 ELCNNODESTAT11 918
7.66 ELCNNODESTAT12 919
7.67 ELCNNODESTAT13 919
7.68 ELCNNODESTAT14 920
7.69 ELCNNODESTAT15 920
7.70 ELCNNODESTAT16 921
7.71 ELCNNODESTAT17 921

- 877 -
Chapter 7 - Exxxx Parameters

7.72 ELCNNODESTAT18 922


7.73 ELCNNODESTAT19 922
7.74 ELCNNODESTAT20 923
7.75 ELCNNODESTAT21 923
7.76 ELCNNODESTAT22 924
7.77 ELCNNODESTAT23 924
7.78 ELCNNODESTAT24 925
7.79 ELCNNODESTAT25 925
7.80 ELCNNODESTAT26 926
7.81 ELCNNODESTAT27 926
7.82 ELCNNODESTAT28 927
7.83 ELCNNODESTAT29 927
7.84 ELCNNODESTAT30 928
7.85 ELCNNODETYPE 928

7.86 ELCNPACKETINV 929


7.87 ELCNRXRATE 929
7.88 ELCNRXRATEMAX 930
7.89 ELCNSEQINV 930
7.90 ELCNSRCINV 931
7.91 ELCNSTATSRST 931
7.92 ELCNTOLCNRATE 932
7.93 ELCNTOLCNRATEMAX 932
7.94 ELCNTXRATE 933
7.95 ELCNTXRATEMAX 933
7.96 ELEMSUBVAL 933
7.97 ELEMSUBVALTYPE 934
7.98 ELOF[0..numChans-1] 935
7.99 ENABLE[1..10] 935
7.100 ENABLE 935
7.101 ENABLECAB 936
7.102 ENABLEDEVICE[0..15] 937
7.103 ENABLELOGICALENIM 937
7.104 ENABLEMVDROPIFINIT 937
7.105 ENABLEMVREADVALIDATION 938
7.106 ENABLENAMUR 938
7.107 ENABLEOPMTOELCN 939
7.108 ENABLEOPMTOLCN 940
7.109 ENABLESCDETECT 940
7.110 ENABLESOE 941

- 878 -
Chapter 7 - Exxxx Parameters

7.111 ENBEXTPATH 941


7.112 ENBHANDLER[1..8] 942
7.113 ENBLATALM[0..numChans-1] 943
7.114 ENBLGANGEDOUTPUTS 943
7.115 ENBLLOGICALENIM 944
7.116 ENBLSTBYCMD 944
7.117 ENBLSYNCCMD 945
7.118 ENBMEMALMFL 945
7.119 ENBNOLOAD[0..numChans-1] 946
7.120 ENBSCHDTRAF 946
7.121 ENBSHUTDOWN 947
7.122 ENCMDS 947
7.123 ENDOFFSET 948
7.124 ENDPHASE 948

7.125 ENDTIME 949


7.126 ENETIPADDR[0-3] 950
7.127 ENETIPADDR 950
7.128 ENGUNITSYSTEM 951
7.129 ENHGENLIN1 951
7.130 ENHGENLIN2 952
7.131 ENHREGCALC 952
7.132 ENIMIPADDR 953
7.133 ENIMIPADDRESS 953
7.134 ENIMUCNNUM 954
7.135 ENOLOAD[0..numChans-1] 954
7.136 ENPULSEWIDTHREJ 955
7.137 ENSPAREDETECT 955
7.138 ENTERSBYCMD 956
7.139 ENTHALPY 956
7.140 ENTHALPYENGUNIT 957
7.141 ENTHALPYIO 957
7.142 ENTITYNAME 957
7.143 ENTROPY 958
7.144 ENTROPYENGUNIT 958
7.145 ENTROPYIO 959
7.146 ENUMBOOLMAP[0..63] 959
7.147 EPKSACCESS 960
7.148 EPKSMIGRATIONMODE 960
7.149 EPKSNAME 961

- 879 -
Chapter 7 - Exxxx Parameters

7.150 EPKSSTATUS 962


7.151 EPLCGCH1BAUDRATE 962
7.152 EPLCGCH1PARITY 963
7.153 EPLCGCH2BAUDRATE 963
7.154 EPLCGCH2PARITY 963
7.155 EPLCGMULTIBUFPIPELINE 964
7.156 EPLCGREDUNDCOMMSOPTION 964
7.157 EPLCGUSEROUTPUTSUPPRESS 965
7.158 EPMSTATE 965
7.159 EQMTORECMAP 966
7.160 EQNEUNITSOPT 966
7.161 EQUIPEXECSTS 967
7.162 EQUIPNAME 967
7.163 EQUIPMODE 968

7.164 EQUIPMODEATTR 968


7.165 EQUIPREQ.STS 969
7.166 EQUIPSTATE 969
7.167 EQUIPSTATUS.STS 969
7.168 ERRATICFLOW[1..24] 970
7.169 ERRATICFLOW[1..200] 970
7.170 ERRCNT[0..1] 971
7.171 ERRCODE 972
7.172 ERRCODE[0..1] 983
7.173 ERRCODE[0..31] 984
7.174 ERRFL 984
7.175 ERRFL[0..1] 985
7.176 ERRFL[0..31] 985
7.177 ERRIN1AV 986
7.178 ERRIN2AV 986
7.179 ERRINFO[0..1] 987
7.180 ERRORCODE 987
7.181 ERRORDBL 987
7.182 ERRORDBR 988
7.183 ERRORINDICATOR 988
7.184 ERRORMSGIDX 988
7.185 ERROSPRESENT 989
7.186 ERROUTAV 989
7.187 ESCKEYSTROKE[1..4] 990
7.188 ESIG 990

- 880 -
Chapter 7 - Exxxx Parameters

7.189 ESTDURATION 990


7.190 ESTWEIGHT 991
7.191 ESWENB 992
7.192 ESWFL.AUTO 992
7.193 ESWFL.BCAS 993
7.194 ESWFL.CAS 993
7.195 ESWFL.MAN 994
7.196 ESWPERM 994
7.197 ETH1IPADDRSTR 995
7.198 ETH1SOFTFAIL 995
7.199 ETH2IPADDRSTR 996
7.200 ETH2SOFTFAIL 996
7.201 ETRANS 996
7.202 EUCNAUTHGROUP 997

7.203 EUDESC 997


7.204 EUDESC[0..120] 998
7.205 EURNGEXT 998
7.206 EVALTRANS[1..15][1..10] 999
7.207 EVALTRANSN[1..15][1..10] 999
7.208 EVENTDESC 1000
7.209 EVENTFL[1..NUMEVENTS] 1000
7.210 EVENTBGNTIME[1..NUMPROFILES][1..NUMEVENTS] 1001
7.211 EVENTENDTIME[1..NUMPROFILES][1..NUMEVENTS] 1001
7.212 EVENTMSGRETRIED 1002
7.213 EVENTMSGSENT 1002
7.214 EVENTNAKRECEIVED 1003
7.215 EVENTQUEUESZ 1003
7.216 EVENTRECEIVERDROPPED 1004
7.217 EVENTSEGID[1..NUMPROFILES][1..NUMEVENTS] 1004
7.218 EVENTSRC 1004
7.219 EVENTTHROTTLEREQ 1005
7.220 EVERIFY[0..numChans-1] 1005
7.221 EVTOPT 1006
7.222 EVTOPTEXEDTL 1008
7.223 EVTOPTFORMULAPARAM 1009
7.224 EVTOPTHIST 1009
7.225 EVTOPTMODEATR 1010
7.226 EVTOPTRCMEXE 1010
7.227 EVTOPTRCMINFO 1011

- 881 -
Chapter 7 - Exxxx Parameters

7.228 EVTOPTRECIPE 1011


7.229 EVTOPTREPORTPARAM 1012
7.230 EVTOPTRESALLOC 1012
7.231 EVTOPTSCMS 1013
7.232 EVTOPTSCMTS 1013
7.233 EVTOPTSTATECHG 1014
7.234 EVTOPTSTEPC 1014
7.235 EVTOPTSTEPS 1014
7.236 EWIREOFF[0..numChans-1] 1015
7.237 EXCMODEOPT 1015
7.238 EXCPTALM.PR 1016
7.239 EXCPTALM.SV 1016
7.240 EXCPTNLINENM 1017
7.241 EXCPTNMODULE 1017

7.242 EXCPTNMSG 1018


7.243 EXCPTNTYPE 1018
7.244 EXECCODE 1020
7.245 EXECCODE[1..8] 1036
7.246 EXECDESC 1037
7.247 EXECDESC[1..8] 1038
7.248 EXECIDOPT 1038
7.249 EXECSTATE 1039
7.250 EXECSTS 1040
7.251 EXECSTS[1..8] 1042
7.252 EXECSTSFAILTM 1042
7.253 EXECTIME 1043
7.254 EXECUTEOPT 1044
7.255 EXECUTIONMODE 1044
7.256 EXITOPT 1045
7.257 EXPIRATIONDATE 1045
7.258 EXPR[1..8] 1046
7.259 EXPRDESC[1...8] 1046
7.260 EXPRPCODE[1..8] 1047
7.261 External 1047
7.262 EXTERRORSTATUS 1048
7.263 EXTERRORSTATUSN 1048
7.264 EXTGETRQUAVG 1049
7.265 EXTGETRQUMAX 1050
7.266 EXTPATH 1050

- 882 -
Chapter 7 - Exxxx Parameters

7.267 EXTPOWERFAIL 1051


7.268 EXTRAPULSE 1051
7.269 EXTRAPULSETM 1052
7.270 EXTREF 1052
7.271 EXTREFSTRUCT 1053
7.272 EXTSTRRQUAVG 1053
7.273 EXTSTRRQUMAX 1054
7.274 EZCROSS[0..numChans-1] 1054

7.1 EAGN

Specific to EHPM
Block(s)
Description EUCN authentication group number defines the EUCN group on that physical wire
and only those nodes which belong to this group and communicating with each
other.
Data Type INT32
Range 1 to 511
Default NOTLOADED
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence EHPM
Related N/A
Parameters
Remarks

7.2 EAMRDATAPKTSPERSEC

Specific to ELCN_NODE
Block(s)
Description Number of redundancy data packets sent from a redundant AM to its paired node.
Data Type INT
Range 0 – 65,535

Default 0
Config Load Initial load
Active Not Applicable
Loadable

- 883 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence ELCN parameter block
Related EAMRDATAPKTSPERSRC, EAMRSIGPKTSPERSRC, EMARPERCENTOPTAVG,
Parameters EAMRRDNXFERMBPERSEC
Remarks Data packets are only issued from the primary AM to the secondary AM

7.3 EAMRMSGSPERSEC

Specific to ELCN_NODE
Block(s)
Description Number of redundancy messages sent from a redundant AM to its paired node.
Data Type INT
Range 0 – 65,535

Default 0
Config Load Initial load
Active Not Applicable
Loadable
Access Lock ViewOnly
Residence ELCN parameter block
Related EAMRDATAPKTSPERSRC, EAMRSIGPKTSPERSRC, EMARPERCENTOPTAVG,
Parameters EAMRRDNXFERMBPERSEC
Remarks Averaged over 5 seconds. These can be sent in either direction, primary or
secondary.

7.4 EAMRPERCENTOPTAVG

Specific to ELCN_NODE
Block(s)
Description Average optimization of AMR traffic across redundancy link.
Data Type INT
Range 0 – 100

Default 0
Config Initial load
Load
Active Not Applicable
Loadable
Access ViewOnly
Lock
Residence ELCN parameter block
Related EAMRDATAPKTSPERSRC, EAMRSIGPKTSPERSRC, EAMRMSGSPERSRC,
Parameters EAMRRDNXFERMBPERSEC
Remarks Averaged over 5 seconds. Optimization value is the reduction in traffic as % of overall
traffic. For example, if traffic would normally be 1000 data packets, but the
optimization reduced this traffic to 900 data packets, then this value would be 10 (%).

- 884 -
Chapter 7 - Exxxx Parameters

7.5 EAMRRDNXFERMBPERSEC

Specific to ELCN_NODE
Block(s)
Description Number of bits per second transferred from a redundant AM node to its partner.
Data Type INT
Range 0 – 65,535

Default 0
Config Initial load
Load
Active Not Applicable
Loadable
Access ViewOnly
Lock
Residence ELCN parameter block
Related EAMRDATAPKTSPERSRC, EAMRSIGPKTSPERSRC, EMARPERCENTOPTAVG,
Parameters EAMRMSGSPERSRC
Remarks Averaged over 5 seconds. This can be measured in either direction, primary <>
secondary.This value can be used to characterize the load that EAMR RDN link may
be expected to place on a virtual production communication link which, as opposed to
the dedicated UEA RDN wire, may be shared with other virtual communications
across the same virtual data transport.

7.6 EAMRSIGPKTSPERSEC

Specific to ELCN_NODE
Block(s)
Description Number of redundancy signals sent from a redundant AM to its paired node.
Data Type INT
Range 0 – 65,535

Default 0
Config Load Initial load
Active Not Applicable
Loadable
Access Lock ViewOnly
Residence ELCN parameter block
Related EAMRMSGSPERSRC, EAMRDATAPKTSPERSRC, EAMRPERCENTOPTAVG,
Parameters EAMRRDNXFERMBPERSEC
Remarks Signal packets can be sent in either direction, primary or secondary.

- 885 -
Chapter 7 - Exxxx Parameters

7.7 EAPPCONNTONSTATUS

Specific to SIMEHPM
Block(s)
Description E-APP Connection Status shows the result of connection establishment between
Experion SCE node and UniSim E-APP node.
Data Type ENUM
Range NA
Default NotConnected
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence No Load
Related CONNECTIONERROR
Parameters
Remarks E-APP Connection Status shows whether the connection between Experion SCE
node and UniSim E-APP node is established successfully or not (Connected or
NotConnected).

7.8 EAPPNODEIP

Specific to SIMEHPM
Block(s)
Description E-APP Node IP Address shows the IP address of the E-APP Node in the UniSim
system with which the Simulation Control Environment (SCE) node communicates.
One E-APP node represents one UCN network number type.
Data Type STRING
Range NA
Default 0.0.0.0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related EAPPNODENAME
Parameters
Remarks This parameter represents the path to connect to an E-APP node. An unsuccessful
connection between SCE node/SIMEHPM.exe and E-APP node results in an error.

- 886 -
Chapter 7 - Exxxx Parameters

7.9 EAPPNODENAME

Specific to SIMEHPM
Block(s)
Description E-APP Node Name shows the node name of the E-APP node in the UniSim system
with which the SCE node communicates.
Data Type STRING
Range NA
Default None
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related EAPPNODEIP
Parameters
Remarks

7.10 ECHSWDESC[0...63]

Specific to Blocks HRBALG_REG block


Description HSW description-EC
Data Type Array of Strings
Range Not applicable

Default Values are specified in ECRegparams.arr.xml


Config. Load No
Access Lock ViewOnly
Residence SR
Related HSWValue
Parameters
Remarks This parameter contains text, which describes each word of the Hiway slot
emulation.

- 887 -
Chapter 7 - Exxxx Parameters

7.11 EDGEDETECT

Specific to Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Input Edge Detection specifies which edge of pulse to be detected for counting. All
timing, counting and frequency functions in the hardware begin with the transition
of the signal (applied to the screw terminals) from Low to High, or High to Low.
Data Type Enumeration
Range Rising Edge (0): Signal transitions from low voltage to
high voltage will cause an Off-to-On
transition in the ASIC functions of the
module.
Falling Edge (1): Signal transitions from high voltage to
low voltage will cause an Off-to-On
transition in the ASIC functions of the
module.
Default Rising Edge (0)
Config Yes
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to Series C PICHANNEL


Block(s)
Description Edge Detection
Data Type ENUM
Range FallingEdge(0) Signal transmissions from high voltage
to low voltage cause an Off-to On
transition in the ASIC function of the IO
module.
RisingEdge(1) Signal transmissions from low voltage to
high voltage cause an Off-to-On
transition in the ASIC functions of the IO
module.
Default Rising Edge (1)
Config Yes
Load
Active No
Loadable

- 888 -
Chapter 7 - Exxxx Parameters

Access Lock AppDevOnly


Residence IOM
Related N/A
Parameters
Remarks EDGEDETECT determines whether the signal transmissions rising or falling edge
will cause an Off-to-On transition in the ASIC functions of the IO module. All timing,
counting, and frequency functions in the hardware begin with the transition of the
signal (applied to the screw terminals) from low-to-high or high-to-low as
determined by the Edge Detection (EDGEDETECT) selection.

7.12 EDGEDETECT[0..7]

Specific to Pulse Input IOM


Block(s)
Description Input Edge Detection specifies which edge of pulse to be detected for counting.
Data Type Enumeration
Range Rising Edge (0) Falling Edge (1)
Default Rising Edge (0)
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks RisingEdge mode refers to screw-terminal-input transitions from low voltages to
high voltage will cause an Off-to-On transition in the ASIC functions of the module.
FallingEdge mode refers to screw-terminal-input transitions from high voltages to-
low voltage will cause an Off-to-On transition in the ASIC functions of the module.

7.13 EDITLOCK

Specific to CAB and CDB Types


Block(s)
Description Edit Lock - Identifies the computer name and the user name of the Control
Engineer who has opened the block for edit. It is automatically set when an edit
session starts and automatically cleared when an edit session ends.
Data Type String
Range 64 Characters
Default Blank
Config Yes
Load
Active No

- 889 -
Chapter 7 - Exxxx Parameters

Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks Attempts by another Control Engineer to open a CAB/CDB type, when EDITLOCK is
not blank; will be rejected unless the type is opened as ViewOnly. In the event that a
computer crashes during an edit session and cannot be restarted, the DBAdmin
utility can be used to clear the EDITLOCK condition. Refer to the Control Hardware
Troubleshooting and Maintenance Guide for more information.

7.14 EEGSTATE

Specific to Block(s) OPC


Description EEGateway State - Displays current state of EEGateway
Data Type Enumeration
Range 1 HCI_STATUS_RUNNING
2 HCI_STATUS_FAILED
3 HCI_STATUS_NOCONFIG
4 HCI_STATUS_SUSPENDED
5 HCI_STATUS_TEST
6 HCI_STATUS_IDLE
7 HCI_STATUS_WARNING
8 HCI_STATUS_INITIALIZING
9 HCI_STATUS_SHUTTINGDOWN
10 HCI_STATUS_SHUTDOWNCOMPLETE
11 HCI_STATUS_BACKUP
Default HCI_STATUS_NOCONFIG
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 890 -
Chapter 7 - Exxxx Parameters

7.15 EFFECOPTSPEED

Specific to Block(s) ProfitCtl


Description Integrator opt speed
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

7.16 EHBADDED

Specific to Box Hiway Responder Block (HRB)


Blocks
Description Tag name of EHB configured as "Added EHB"
Data Type String
Range
Default Blank
Config. No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the tagname of the EHB which has the "Added EHB"
relationship with the Hiway box emulation. This parameter is assigned
automatically when the Box HRB is loaded based on the value of HWYNUMTHIS.
This parameter can be NULL or non-NULL. When this parameter is non-NULL, it
matches value of parameter EHB.PHWYPRTLC of the EHB whose EHB.HWYNUM
matches HWYNUMTHIS.

- 891 -
Chapter 7 - Exxxx Parameters

7.17 EHBADDEDIP

Specific to Box Hiway Responder Block (HRB)


Blocks
Description IP address of EHB configured as "Added EHB"
Data Type IP Address String
Range
Default Blank
Config. Yes
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the IP address of the EHB whose tagname is indicated by
the value of EHBADDED. This parameter is assigned automatically when the Box
HRB is loaded based on the value of HWYNUMTHIS.

7.18 EHBHWYNUM

Specific to Blocks ELCN_NODE (EHB)


Description EHB Node Number
Data Type INT32
Range Min Value: 2
Max Value: 62
Default 0
Config. Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks This is the EHB address on data Hiway.

- 892 -
Chapter 7 - Exxxx Parameters

7.19 EHBLC1

Specific to CEE platform block


Blocks
Description Experion Hiway Bridge Local Tagname 1
Data Type Block Id.
Range
Default Blank
Config. No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the tagname of one of the EHBs with which box
emulations assigned to the CEE communicate. This parameter always specifies an
EHB which is in the same Experion Server cluster as the CEE. When the CEE
platform block is loaded, EHBLC1 is populated automatically based on the EHB
indicated by HWYNUM1.

7.20 EHBLC2

Specific to CEE platform block


Blocks
Description Experion Hiway Bridge Local Tagname 2
Data Type Block Id.
Range
Default Blank
Config. No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the tagname of one of the EHBs with which box
emulations assigned to the CEE communicate. This parameter always specifies an
EHB which is in the same Experion Server cluster as the CEE. When the CEE
platform block is loaded, EHBLC2 is populated automatically based on the EHB
indicated by HWYNUM1.

- 893 -
Chapter 7 - Exxxx Parameters

7.21 EHBLCIP1

Specific to CEE platform block


Blocks
Description Experion Hiway Bridge Local IP Address 1
Data Type IP Address String
Range
Default Blank
Config. Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly, ViewOnly on form
Residence CEE
Related
Parameters
Remarks This parameter specifies the IP address of the EHB whose tagname is indicated by
the value of EHBLC1. When the CEE platform block is loaded, EHBLCIP1 is
populated automatically based on the EHB indicated by HWYNUM1.

7.22 EHBLCIP2

Specific to CEE platform block


Blocks
Description Experion Hiway Bridge Local IP Address 2
Data Type IP Address String
Range
Default Blank
Config. Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly, ViewOnly on form
Residence CEE
Related
Parameters
Remarks This parameter specifies the IP address of the EHB whose tagname is indicated by
the value of EHBLC2. When the CEE platform block is loaded, EHBLCIP2 is
populated automatically based on the EHB indicated by HWYNUM1.

- 894 -
Chapter 7 - Exxxx Parameters

7.23 EHBRMIP1

Specific to CEE platform block


Blocks
Description Remote EHB 1 Address
Data Type IP Address String
Range
Default Blank
Config. Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly, ViewOnly on form
Residence CEE
Related
Parameters
Remarks This parameter specifies the IP address of an EHB with which box emulations
assigned to the CEE communicate. This parameter always specifies an EHB which
is in a different Experion Server cluster from the CEE. When the CEE platform block
is loaded, EHBRMIP1 is populated automatically based on the EHB indicated by
HWYNUM1.

Specific to Box Hiway Responder Block (HRB)


Blocks
Description IP address of Remote EHB1
Data Type IP Address String
Range
Default Blank
Config. Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter specifies the IP address of an EHB which communicates with this
Hiway box emulation. This parameter is assigned automatically when the Box HRB
is loaded based on the value of HWYNUMTHIS. This parameter can be NULL or
non-NULL. When this parameter is non-NULL, it matches either the value of
EHB.PHWYPRTRMIP1 or EHB.PHWYPRTRMIP2 of the EHB whose EHB.HWYNUM
matches HWYNUMTHIS.

- 895 -
Chapter 7 - Exxxx Parameters

7.24 EHBRMIP2

Specific to CEE platform block


Blocks
Description Experion Hiway Bridge Remote 2
Data Type IP Address String
Range
Default Blank
Config. Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly, ViewOnly on form
Residence CEE
Related
Parameters
Remarks This parameter specifies the IP address of an EHB with which box emulations
assigned to the CEE communicate. This parameter always specifies an EHB which
is in a different Experion Server cluster from the CEE. When the CEE platform block
is loaded, EHBRMIP2 is populated automatically based on the EHB indicated by
HWYNUM1.

Specific to Box Hiway Responder Block (HRB)


Blocks
Description IP address of Remote EHB2
Data Type IP Address String
Range
Default Blank
Config. Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter specifies the IP address of an EHB which communicates with this
Hiway box emulation. This parameter is assigned automatically when the Box HRB
is loaded based on the value of HWYNUMTHIS. This parameter can be NULL or
non-NULL. When this parameter is non-NULL, it matches either the value of
EHB.PHWYPRTRMIP1 or EHB.PHWYPRTRMIP2 of the EHB whose EHB.HWYNUM
matches HWYNUMTHIS.

- 896 -
Chapter 7 - Exxxx Parameters

7.25 EHBROLEFORBOX [5..63]

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description EHB role
Data Type Enumeration
Range 0 - None 2 – AddedHG
1 – ThisHG 3 - RemoteHG
Default 0 -None
Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter displays the role of the EHB for the box.

7.26 EHBTHIS

Specific to Box Hiway Responder Block (HRB)


Blocks
Description Tag name of EHB configured as "This EHB"
Data Type String
Range
Default Blank
Config. No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the tagname of the EHB which has the "This EHB"
relationship with the Hiway box emulation. This parameter is assigned
automatically when the Box HRB is loaded based on the value of HWYNUMTHIS.
This parameter always matches the tagname of the EHB whose EHB.HWYNUM
matches HWYNUMTHIS.

- 897 -
Chapter 7 - Exxxx Parameters

7.27 EHBTHISIP

Specific to Box Hiway Responder Block (HRB)


Blocks
Description IP address of EHB configured as "This EHB"
Data Type IP Address String
Range
Default Blank
Config. Yes
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the IP address of the EHB whose tagname is indicated by
the value of EHBTHIS. This parameter is assigned automatically when the Box HRB
is loaded based on the value of HWYNUMTHIS.

7.28 EHPMDATAACCESS

Specific to EHPM
Block(s)
Description EHPM Data Access
Data Type ENUM
Range Peer to Peer Only Peer to Peer and ExpServer
Default Peer to Peer Only
Config Load Yes
Active Yes
Loadable

- 898 -
Chapter 7 - Exxxx Parameters

Access Lock AppDevOnly


Residence SR
Related
Parameters
Remarks This parameter is used to optionally download the EHPM points to the Experion
server so that Experion applications and HMIWeb displays can collect data through
CDA.
l Selecting the configuration parameter value as “Peer to Peer Only” enables
peer data access between the Experion controllers and the EHPM points
through CDA.
l Selecting the configuration parameter value as “Peer to Peer and ExpServer”
enables read access to the EHPM points through CDA from Experion
applications and HMIWeb displays in addition to enabling peer data access.

NOTE The EHPM block must be loaded to the monitoring side in Control
Builder to reflect the change in parameter value.

NOTE If you select Peer to peer and ExpServer option, it flags the EHPM
points as combo points in the Experion server.The EHPM Combo Point
configuration directs the ESV-T or ES-T to resolve names of requested
EHPM point parameters through the SR first, and then, if not found in
the SR, through the TPN Server.Once a parameter name is resolved
through the SR, all read requests issued by Experion applications and
HMIWeb displays to this parameter are redirected over CDA.

7.29 EHPM_ERRCODE

Specific to Block EHPM


(s)
Description EHPM error code shows the error code during the run time if any.
Data Type UINT8
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related N/A
Parameters
Remarks This parameter shows the error code if there is any error during normal
operation of the EHPM.

- 899 -
Chapter 7 - Exxxx Parameters

7.30 EHPM_SELFTEST

Specific to Block(s) EHPM


Description EHPM self test message is displayed while controller is booting.
Data Type UINT8
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related Parameters N/A
Remarks This parameter shows the self test message while controller is booting.

7.31 EHPMSTATE

Specific to Primary / Secondary EHPM


Block(s)
Description EHPM controller state
Data Type ENUM
Range OFFNET (0) CONFGMIS (1) IDLE (2) LOADING (15) STANDBY (16) STANDBYSF (17)
IDLESF (3) RUN (4) RUNSF (5) FAIL UPGRADE (18) UPGRADESF (19) S_IDLE (20)
(6) FAILSF (7) PWRON (8) S_IDLESF (21) S_RUN (22) S_RUNSF (23) S_
PWRONSF (9) ALIVE (10) ALIVESF PAUSE (24) S_PAUSSF (25) BACKUP (26)
(11) TEST (12) TESTSF (13) BACKUP (27) S_BACKUP (28) S_BACKUP (29)
UNKNOWN (14)
Default UNKNOWN
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence EHPM
Related N/A
Parameters
Remarks

- 900 -
Chapter 7 - Exxxx Parameters

7.32 EICONNERRCODE[0..8]

Specific to CEEFB, CEEC300, CEEUOC


Block(s)
Description Exchange Initiator Connection Error Code - Indicates the ICP/ASA error returned
on an open connection attempt.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related EICONNSTS, EICONNERRINFO, EIPPATH
Parameters
Remarks Shows error code of the connection between the controller and the target
controller or programmable logic controller.

7.33 EICONNERRINFO[0..8]

Specific to CEEFB, CEEC300, CEEUOC


Block(s)
Description Exchange Connection Error Description
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related EICONNSTS, EIPPATH, EICONNERRCODE.
Parameters
Remarks Shows error code of the connection between the controller and the target
controller or programmable logic controller.

- 901 -
Chapter 7 - Exxxx Parameters

7.34 EICONNSTS[0..8]

Specific to Block(s) CEEFB, CEEC300, CEEUOC


Description Exchange Connection Status
Data Type Enumeration
Range NoState
Initialized(1)
Not Used(2)
Open(3)
Not Used(2)
Default NoState
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EIPPATH, EICONNERRINFO, EICONNERRCODE.
Remarks This parameter gives the Exchange connection status.

7.35 EIOMTYPE

Specific to All ArmorPoint modules, ArmorBlock modules, PowerFlex Drive, E3, and E3 plus
Block(s) Devices
Description EIP Device Description — It provides the details of the EtherNet/IP device in use.
Data Type String
Range 64-Characters

Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks The format followed is: Family Name followed by the device/IO module name, and
the number of channels it supports.

- 902 -
Chapter 7 - Exxxx Parameters

7.36 EIM_IPADDRESS

Specific to EIP IO, E3, E3+, PF755 Drive, Aggregate UDT and Scalar UDT Blocks
Block(s)
Description IP address of EIM
Data Type STRING
Range 16
Default 0.0.0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related -
Parameters
Remarks This is a view only parameter that can be seen on the main tab of the block. The
IPADDRESS of the EIM that it is associated with gets populated in this parameter.

7.37 EIMNAME

Specific to EIP IO, E3, E3+, PF755 Drive, Aggregate UDT and Scalar UDT Blocks
Block(s)
Description EIM Name
Data Type BLOCKID
Range -
Default -
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related -
Parameters
Remarks This is a configuration parameter made available at the instance level and needs to
be configured with the EIM that needs to be used. Once configured, the
IPADDRESS information flows down to the individual blocks.

- 903 -
Chapter 7 - Exxxx Parameters

7.38 EIMTYPE

Specific to Block(s) 1738-AENT


Description EIP Adapter Descriptor
Data Type String
Range 0 — 64 characters
Default
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks Static Description of the block and it cannot be changed.

7.39 EIMDISCONNECTDEVNAME

Specific to Block(s) EIM


Description EIP Communication Mode
Data Type ENUM

Range Direct Connection, Through EIM

Default Direct Connection

Config Load Yes

Active Loadable Yes

Access Lock AppDevOnly

Residence SR

Related Parameters EIPSUPPORTED

Remarks Sets how C300 accesses EIP data.

7.40 EIPATH[0..8]

Specific to Block CEEFB, CEEC300, CEEUOC


(s)
Description Exchange Initiator Peer Path - The exchange initiator's Automation System
Architecture (ASA) path.
Data Type String
Range 64 Characters
Default NULL
Config Load No

- 904 -
Chapter 7 - Exxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related EICONNSTS, EICONNERRINFO, EICONNERRCODE.
Parameters
Remarks Shows the path to the target node in comma separated string format.

7.41 EIPMODE

Specific to Block(s) C300


Description Disconnect Device
Data Type Disconnect Device

Range
Default None

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence SR

Related Parameters EIPSUPPORTED

Remarks

7.42 EIPSUPPORTED

Specific to Block(s) C300


Description Enable Support for Ethernet/IP
Data Type BOOLEAN

Range On, Off

Default Off

Config Load Yes

Active Loadable
Access Lock AppDevOnly

Residence SR

Related Parameters EIPMODE


EIMDISCONNECTDEVNAME
RESETEIMNAME
Remarks

- 905 -
Chapter 7 - Exxxx Parameters

7.43 EIPIOIPADDR

Specific to Block(s) PB_EIP, CEEC300, CEEUOC


Description EIP IO IP Address
Data Type STRING
Range -
Default 0

Config Load No

Active Loadable No
Access Lock ViewOnly
Residence No Load

Related Parameters -
Remarks IP address of the EIP IO Module or Adapter or Device

7.44 EIPIOCONNSTS

Specific to EIM EIP Protocol Block


Block(s)
Description Connection Status
Data Type ENUM
Range NoState Faulted Validating Connecting Running Shutting_Down Waiting
Reconfiguring
Default NoState
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence NoLoad
Related -
Parameters
Remarks Class 1 EIP IO Connection Status to the EIP IO Module or Adapter or Device.
NoState – Not configured. Faulted – Failure in the EIP IO Connection. Validating –
Intermediate state before attempting the connection to the EIP IO. Connecting -
Intermediate state before going to Faulted or Running state. Running – Successful
connected to the EIP IO. Shutting_Down – In process to close the EIP IO
connection. Waiting – Waiting to connect either first connection attempt or after a
failure. Reconfiguring – Reconnecting attempt to the EIP IO.

- 906 -
Chapter 7 - Exxxx Parameters

7.45 EIPIOSLOTNUM

Specific to Block(s) EIM EIP Protocol Block


Description EIP IO Slot Number
Data Type UINT8
Range 0-64
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Slot Number of the EIP IO – valid only in case it is a Modular IO

Specific to Block(s) PB_EIP, CEEC300, CEEUOC Block


Description EIP IO Slot Number
Data Type UINT8
Range 0-64
Default 0

Config Load No

Active Loadable No
Access Lock ViewOnly
Residence No Load

Related Parameters -
Remarks Slot Number of the EIP IO – valid only in case it is a Modular IO

- 907 -
Chapter 7 - Exxxx Parameters

7.46 ELCNBCOMMAND

Specific to ELCN_BRG
Block(s)

Description ELCN_BRG device Module Command


Data Type Enumeration
Range None (0) – No command Shutdown
(1) –ELCN_BRG will be shutdown
Default None (0)
Config No
Load

Active No
Loadable

Access Engineer
Lock

Residence ELCN_BRG
Related ELCN_BRG Main tab - ELCNBSTATE
Parameters

Remarks The Shutdown command causes the related UEA box to Reboot into the “Ready” state.
This “Ready” state makes the UEA capable of a firmware load. In the “Ready” state, only
the Firmware Manager tool can “talk” to the UEA.
If you do not perform a firmware load following a Shutdown, then you will have to Reboot
the UEA from the front panel display at the physical box. The Reboot returns the ELCN
Bridge UEA to a fully operational state – typically this would be BACKUP as the primary
would be running.

You can perform the Shutdown command from the following Experion displays:
l Detail Display (Cmd on the faceplate or Module Command on the Main tab)
l Monitoring side of Control Builder (Module Command on the Main tab)

- 908 -
Chapter 7 - Exxxx Parameters

7.47 ELCNBNUM

Specific to ELCN_BRG
Block(s)

Description LCN node number of ELCN Bridge. Its range ensures that it does not interfere with any
existing LCN node numbers.
Data Type 32-Bit Integer
Range 97 or 98
Default 0
Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence ELCN_BRG
Related ELCN_BRG Main tab
Parameters

Remarks By default, Control Builder assigns LCN addresses 97 and 98 to the ELCN Bridge
redundant pair – these addresses cannot be changed.  Control Builder assigns LCN
address 97 to the ELCN Bridge that has an odd Device Index, and assigns LCN Address
98 to its redundant partner.

7.48 ELCNBSTATE

Specific to Block(s) ELCN_BRG


Description ELCN_BRG Module State
Data Type Enumeration of PCMSTATE
Range OK (5)
BACKUP (8)
NOTLOADED (9)
Default NOTLOADED (9)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN_BRG Main tab
Remarks

- 909 -
Chapter 7 - Exxxx Parameters

7.49 ELCNCOMMINV

Specific to Block(s) ELCN_BRG


Description ELCN Communication Error count
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks Transmit or Receive socket error. Detail in the eventlog.

7.50 ELCNLNGTHINV

Specific to Block(s) ELCN_BRG


Description ELCN Invalid Length count
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks Received ELCN packet data length does not match.

- 910 -
Chapter 7 - Exxxx Parameters

7.51 ELCNMULTIIPADDRSTR

Specific to ELCN_BRG, ELCN_NODE


Block(s)
Description Address for ELCN node multicast communication
Data Type String

NOTE
String is converted unsigned integer 32 for load to ELCN_BRG at
Application Developer level. The multicast unsigned integer 32 value is
maintained in the ELCN_BRG.

Range Greater than 0 ... 234.255.255.255


Default 234.129.239.100
Config Load Yes
Active No
Loadable
Access Engineer/Application Developer
Lock
Residence SR
Related ELCN_BRG, ELCN_BRG Main tab
Parameters
Remarks Secondary ELCN_BRG contains the same value as that configured for the Primary
ELCN_BRG.

CAUTION
Honeywell strongly recommends that you use the default ELCN Multicast
IP Address and not change it unless you are familiar with the use of the IP
Multicast Protocol.

The ELCN Multicast IP Address must match on the ELCN Bridge and all ELCN Nodes
on this network, including Control Builder block configuration of ELCN Appliance
Nodes (such as NIM and AM) and the Board0 configuration of Microsoft Windows-
based TPS Nodes (ES-T, ESVT, ACE-T, and E-APP) in order for them to communicate.
If you decide to change this value from the default, then you will need to change the
value on the ELCN Bridge and every ELCN Node as well.
After the ELCN Bridges and ELCN Nodes are running, any changes to the ELCN
Multicast IP Address should not be done on-process.
Consult Honeywell or your personnel familiar with the use of the IP Multicast Protocol
and Honeywell Fault Tolerant Ethernet to determine the repercussions of changing
the ELCN Multicast IP Address.

- 911 -
Chapter 7 - Exxxx Parameters

7.52 ELCNNODECOMMAND

Specific to ELCN_NODE
Block(s)

Description ELCN_NODE device Module Command


Data Type Enumeration
Range None (0) – No command Shutdown
1. ELCN_NODE type application will be reset
2. ELCN_NODE will be shutdown
Default None (0)
Config No
Load

Active No
Loadable

Access Engineer
Lock

Residence ELCN_NODE
Related ELCN_NODE Main tab - ELCNNODESTATE
Parameters

Remarks Shutdown command puts ELCN_NODE into a not running state (offnet) and makes it
capable of firmware load (which will reboot the node). A manual reboot of the ELCN_
NODE is required when firmware load is not performed.

Reset command reboots the node and does not require reloading of firmware.

7.53 ELCNNODENUM

Specific to Block(s) ELCN_NODE


Description LCN node number of the primary ELCN_NODE.
Data Type 32-Bit Integer
Range 1 to 96
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence ELCN_NODE
Related Parameters ELCN_NODE Main tab
Remarks

- 912 -
Chapter 7 - Exxxx Parameters

7.54 ELCNNODENUMPARTNER

Specific to Block(s) ELCN_NODE


Description LCN node number of the partner ELCN_NODE.
Data Type 32-Bit Integer
Range 1 to 96
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence ELCN_NODE
Related Parameters ELCN_NODE Main tab
Remarks

7.55 ELCNNODESTAT1

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 913 -
Chapter 7 - Exxxx Parameters

7.56 ELCNNODESTAT2

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.57 ELCNNODESTAT3

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 914 -
Chapter 7 - Exxxx Parameters

7.58 ELCNNODESTAT4

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.59 ELCNNODESTAT5

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 915 -
Chapter 7 - Exxxx Parameters

7.60 ELCNNODESTAT6

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.61 ELCNNODESTAT7

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 916 -
Chapter 7 - Exxxx Parameters

7.62 ELCNNODESTAT8

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.63 ELCNNODESTAT9

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 917 -
Chapter 7 - Exxxx Parameters

7.64 ELCNNODESTAT10

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.65 ELCNNODESTAT11

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 918 -
Chapter 7 - Exxxx Parameters

7.66 ELCNNODESTAT12

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.67 ELCNNODESTAT13

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 919 -
Chapter 7 - Exxxx Parameters

7.68 ELCNNODESTAT14

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.69 ELCNNODESTAT15

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 920 -
Chapter 7 - Exxxx Parameters

7.70 ELCNNODESTAT16

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.71 ELCNNODESTAT17

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 921 -
Chapter 7 - Exxxx Parameters

7.72 ELCNNODESTAT18

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.73 ELCNNODESTAT19

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 922 -
Chapter 7 - Exxxx Parameters

7.74 ELCNNODESTAT20

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.75 ELCNNODESTAT21

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 923 -
Chapter 7 - Exxxx Parameters

7.76 ELCNNODESTAT22

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.77 ELCNNODESTAT23

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 924 -
Chapter 7 - Exxxx Parameters

7.78 ELCNNODESTAT24

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.79 ELCNNODESTAT25

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 925 -
Chapter 7 - Exxxx Parameters

7.80 ELCNNODESTAT26

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.81 ELCNNODESTAT27

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 926 -
Chapter 7 - Exxxx Parameters

7.82 ELCNNODESTAT28

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.83 ELCNNODESTAT29

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

- 927 -
Chapter 7 - Exxxx Parameters

7.84 ELCNNODESTAT30

Specific to Block(s) ELCN_NODE


Description ELCNNODE Statistics
Data Type INT32
Range 0-100000
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Currently not used

7.85 ELCNNODETYPE

Specific to Block(s) ELCN_NODE


Description The type of node this ELCN node is
0: ENIM, 1:AM, 2: ELPCG
Data Type INT
Range

Default

Config Load

Active Loadable

Access Lock

Residence

Related Parameters

Remarks

- 928 -
Chapter 7 - Exxxx Parameters

7.86 ELCNPACKETINV

Specific to Block(s) ELCN_BRG


Description ELCN Invalid Packet count
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks ELCN packet indicator missing in the received ELCN packet header.

7.87 ELCNRXRATE

Specific to Block(s) ELCN_BRG


Description ELCN Rx Rate [pkts/sec]
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks Data packets received from ELCN

- 929 -
Chapter 7 - Exxxx Parameters

7.88 ELCNRXRATEMAX

Specific to Block(s) ELCN_BRG


Description ELCN Rx Rate Max [pkts/sec]
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks Data packets received from ELCN

7.89 ELCNSEQINV

Specific to Block(s) ELCN_BRG


Description ELCN Out of Sequence count
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks Sequence number in the received ELCN packet not expected

- 930 -
Chapter 7 - Exxxx Parameters

7.90 ELCNSRCINV

Specific to Block(s) ELCN_BRG


Description ELCN Invalid Source count
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks Source node > 127 in the received ELCN packet

7.91 ELCNSTATSRST

Specific to ELCN_BRG, ELCN_NODE


Block(s)

Description Used to initiate reset of ELCN statistics.


Data Type Boolean
Range NA
Default Off
Config No
Load

Active No
Loadable

Access Operator
Lock

Residence ELCN_BRG, ELCN_NODE


Related ELCN Bridge Statistics tab, ELCN Node Statistics tab
Parameters

Remarks Store to this parameter causes initialization of all statistics parameters maintained within
the ELCN Bridge Statistics tab or ELCN Node Statistics tab.

- 931 -
Chapter 7 - Exxxx Parameters

7.92 ELCNTOLCNRATE

Specific to Block(s) ELCN_BRG


Description ELCN to LCN Rate [msgs/sec]
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks Message transfer from ELCN to LCN

7.93 ELCNTOLCNRATEMAX

Specific to Block(s) ELCN_BRG


Description ELCN to LCN Rate Max [msgs/sec]
Data Type 32-Bit Integer
Range

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ELCN_BRG
Related Parameters ELCN Bridge Statistics
Remarks Message transfer from ELCN to LCN

- 932 -
Chapter 7 - Exxxx Parameters

7.94 ELCNTXRATE

Specific to Block(s) ELCN_BRG


Description ELCN Tx Rate [pkts/sec]
Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics

Remarks Data packets transmitted to ELCN

7.95 ELCNTXRATEMAX

Specific to Block(s) ELCN_BRG

Description ELCN Tx Rate Max [pkts/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics

Remarks Data packets transmitted to ELCN

7.96 ELEMSUBVAL

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Substitution Value per Element
Data Type Boolean
Range True/False
Default False
Config Yes

- 933 -
Chapter 7 - Exxxx Parameters

Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Substitution on error is supported with SUBVALTYPE and SUBVAL parameters that
may be overridden with parameters ELEMSUBVALTYPE and ELEMSUBVAL, which
can be defined per element and Default to using the common settings when
ELEMSUBVALTYPE is Use Default.

7.97 ELEMSUBVALTYPE

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Substitution Value Type per Element
Data Type Enumeration
Range 0 Last known good
1 SUBVAL
2 NaN
3 Use Default
Default Use Default
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Substitution on error is supported with SUBVALTYPE and SUBVAL parameters that
may be overridden with parameters ELEMSUBVALTYPE and ELEMSUBVAL, which
can be defined per element and Default to using the common settings when
ELEMSUBVALTYPE is Use Default. The NaN is only available for PCDINUMARRCH
blocks.

- 934 -
Chapter 7 - Exxxx Parameters

7.98 ELOF[0..numChans-1]

Specific to Block(s) DIM (only configurable on the 8-channel, 120 VAC, Diagnostic module)
Description Enable Loss of Power
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters NOFIELDPWR[0..numChans-1]
Remarks

7.99 ENABLE[1..10]

Specific to AUXSUMMER, ENHAUXCALC


Block(s)
Description Process Input Enable - Determines if block will use corresponding input (P[1..10]
or substitute value (PSUB[1..10]).
Data Type Boolean
Range (0) Off (Disabled - Use substitute value) (1) On (Enabled - Use process input)
Default On
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related P[1..10]PSUB[1..10]
Parameters
Remarks

7.100 ENABLE

Specific to EXECTIMER
Block(s)
Description ENABLE allows EXECTIMER instance to execute when On. Causes EXECTIMER to
exit immediately with no computation when Off.
Data Type BOOLEAN
Range

- 935 -
Chapter 7 - Exxxx Parameters

Default On
Config Yes
Load
Active No
Loadable
Access Operator
Lock
Residence CEE
Related
Parameters
Remarks In most cases where EXECTIMER is applied, parameter ENABLE is not used. On
rare occasions, an application engineer may find it convenient to leave instances of
EXECTIMER in place permanently as part of the configuration. When this is done,
ENABLE maybe set to On to minimize CPU consumed when measurements are not
actually being taken. When EXECTIMER configurations are disabled, ENABLE
should be set to Off, at both the “begin time interval” instance and the “end time
interval” instance.

7.101 ENABLECAB

Specific to CEE-C300
Block(s)
Description Enable CAB Runtime - Enables or disables the CAB run-time in CEE-C300.
Data Type Boolean
Range On Off
Default Off
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related
Parameters
Remarks By Default, this parameter is disabled. When disabled, any attempt to load a CAB
type to the C300 is rejected. If CAB is to be used within the C300, ENABLECAB must
be enabled. If ENABLECAB is already enabled, it cannot be disabled until all CAB
instances and types are deleted from the C300. If ENABLECAB is enabled within a
loaded CEE, the CEE block must be uploaded and updated into CB Project view to
ensure that it is enabled on any subsequent load of the CEE configuration.
ENABLECAB is displayed on the CAB Types Info form of the CEE block form.

- 936 -
Chapter 7 - Exxxx Parameters

7.102 ENABLEDEVICE[0..15]

Specific to Block PCDI_MASTER


(s)
Description Enable Device - Allows device to be enabled or disabled during Monitoring.
Data Type Boolean
Range True/False
Default True
Config Load Yes
Active Loadable No
Access Lock Engineer/Application Developer
Residence CEE
Related
Parameters
Remarks Disabling the device does not clear the device. To clear a device, set its UNIT
ID to zero.

7.103 ENABLELOGICALENIM

Specific to Block(s) TCMI


Description Enable Logical ENIM
Data Type BOOLEAN
Range N/A
Default F
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

7.104 ENABLEMVDROPIFINIT

Specific to Block(s) ProfitCtl


Description Enable MV Drop in INIT
Data Type ENUM
Range NA
Default NO

- 937 -
Chapter 7 - Exxxx Parameters

Config Load Yes


Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

7.105 ENABLEMVREADVALIDATION

Specific to Block(s) ProfitCtl


Description Validate MV Read Value
Data Type ENUM
Range NA
Default Validate with MV ROC
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

7.106 ENABLENAMUR

Specific to Series C DI channel


Block(s)
Description Enable NAMUR support
Data Type BOOLEAN
Range OFF(0) Disable NAMUR support
ON(1) Enable NAMUR support
Default OFF(0)
Config Yes
Load
Active No
Loadable

- 938 -
Chapter 7 - Exxxx Parameters

Access Lock Application Developer Only


Residence IOM
Related
Parameters
Remarks This parameter specifies that the input signal adheres to the NAMUR Standard (IEC
60947-5-6:1999 specification). When NAMUR support is active, Open circuit and
short circuit detection are also supported as specified in the standard.
ENABLENAMUR can be configured only when:
l Module Type is UIO-2
l DITYPE is NOT set as “Accum”
l EVTOPT is NOT set as “SOE”
When NAMUR is enabled (ENABLENAMUR = ON), the:
l EVTOPT is NOT configurable (NOT exposed)
lDITYPE is limited to only “Status” and “Latched,” and “Accum” option is not
exposed for configuration.
After loading the UIO-DI channel, ENABLENAMUR can only be changed (from OFF
to ON), when the channel PTEXECST is “INACTIVE”.

7.107 ENABLEOPMTOELCN

Specific to Experion Hiway Bridge (EHB) platform block


Block(s)
Description Enable OPM to ELCN EHB
Data Type BOOLEAN
Range TRUE(1) ,FALSE (0)

Default FALSE
Config NO
Load
Active NO
Loadable
Access AppDevOnly
Lock
Residence SR
Related
Parameters
Remarks This parameter enables the OPM from Classic EHB to ELCN EHB. The Control Builder
does not allow the deconfiguration or deletion of a platform block when the device is
running. This parameter enables the deconfiguration of the classic EHB platform
block from Control Builder.

- 939 -
Chapter 7 - Exxxx Parameters

7.108 ENABLEOPMTOLCN

Specific to ELCN_NODE (EHB)


Block(s)
Description Enable OPM backward to LCN (classic EHB)
Data Type BOOLEAN
Range TRUE(1) ,FALSE (0)

Default FALSE
Config NO
Load
Active NO
Loadable
Access AppDevOnly
Lock
Residence SR
Related
Parameters
Remarks This parameter enables the backward migration from ELCN EHB to Classic EHB.
Control Builder does not allow the deconfiguration or deletion of a platform block
when the device is running. This parameter enables the deconfiguration of the ELCN_
NODE (EHB) platform block from Control Builder.

7.109 ENABLESCDETECT

Specific to Series C DI channel


Block(s)
Description Enable Short Circuit Detection
Data Type BOOLEAN
Range OFF(0) Disable Short Circuit Detection
ON(1) Enable Short Circuit Detection
Default OFF(0)
Config Yes
Load
Active No
Loadable

- 940 -
Chapter 7 - Exxxx Parameters

Access Lock Engineer


Residence IOM
Related
Parameters
Remarks This parameter allows you to enable/disable short circuit detection. When this
parameter is enabled, the condition is annunciated as an alarm in the “System
Alarm Summary”. When a short circuit is detected, the PVSTS is set as “BAD” and
the “Short Circuit Detected” soft failure is generated. This parameter
(ENABLESCDETECT) is only configurable (Enabled and exposed) when the:
l Module Type is UIO-2
l ENABLENAMUR is set as “ON”
ENABLESCDETECT is not configurable (disabled and NOT exposed) when the:
l Module Type is NOT UIO-2
l ENABLENAMUR is set as “OFF”
l DITYPE is set as “Accum”
l EVTOPT is set as “SOE”
After loading the UIO-DI channel, the ENABLESCDETECT parameter can be
changed (from OFF to ON) irrespective of the channel PTEXECST configuration.

7.110 ENABLESOE

Specific to Block(s) EIM


Description Enable SOE
Data Type BOOLEAN
Range NA
Default
Config Load
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

7.111 ENBEXTPATH

Specific to All EIP IOM/Devices/Drives/CNet IOs and EIP Generic adapter


Block(s)
Description Enable Extended Path support
Data Type BOOLEAN
Range Off (0): Extended Path support is disabled
On (1): Extended Path support is enabled
Default Off

- 941 -
Chapter 7 - Exxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related EXTPATH
Parameters
Remarks The parameter on the EIP IOMs/Devices that reside under the adapter is hidden and
is used internally by the block. In this case the parameter is available on the EIP
Generic adapter to be configured by the user.

7.112 ENBHANDLER[1..8]

Specific to SCM, RCM


Block(s)
Description Enable Handler Type
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access Engineer for Index 2..8 ViewOnly for Index 1
Lock
Residence CEE
Related TYPE
Parameters
Remarks ENBHANDLER[i] determines whether any of the following can invoke the TYPE i
handler from the current STATE. - Local step exception conditions - Invoke
Transition (if user defined handler exists for this type and has been selected) -
Phase state projection (RCM only) ENBHANDLER[i] can only be changed to On if
the TYPE i handler is accessible from the current SCM/RCM STATE. The SCM/RCM
changes ENBHANDLER[1..8] to the Defaults for a given STATE when that STATE is
entered. For that reason writing to this parameter from within a handler has only
effect for the duration of this handler (for example, turn off a hold handler during
some section of the main handler ). If this value needs to be changed while the
SCM/RCM is in a final state , logic outside this SCM/RCM needs to be employed.

- 942 -
Chapter 7 - Exxxx Parameters

7.113 ENBLATALM[0..numChans-1]

Specific to Block(s) 1738-OB2EPM12 and 1738-OB8EM12


Description Enable Latched Alarms
Data Type Boolean
Range l 0 : OFF
l 1 : ON
Default OFF
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters None
Remarks

7.114 ENBLGANGEDOUTPUTS

Specific to UIO - Series C DOCHANNEL


Block(s)
Description Enable Ganged Outputs
Data Type Boolean
Range Off (0)
On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related NUMOFCHNLSGANGED
Parameters
Remarks This parameter allows you to enable DO channel ganging.

NOTE This parameter is disabled for the 32nd channel of the UIO
module.

To gang the DO channels, ensure the following:


l The adjacent channels must be configured as DO channel in the Channel
Configuration tab of the UIO module at the IOM level.
l The adjacent DO channel must not be configured in any Control Module.
For more information about channel ganging, refer to Series C I/O User's Guide.

- 943 -
Chapter 7 - Exxxx Parameters

7.115 ENBLLOGICALENIM

Specific to EHPM, TCMI


Block(s)
Description Enable Import from Logical ENIM option allows import of EHPM points from the
Remote ENIM to Experion ERDB for the specific EHPM.
Data Type BOOLEAN
Range OFF (0) ON (1)
Default OFF (0)
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence ERDBONLY
Related LOGICALUCNNW
Parameters LOGICALENIM
LOGICALENIMIPADDRESSLOGIENIMDATEPTIMPORTLOGIENIMIMPORTSTATUS
Remarks When Enable import from Logical ENIM option is set as ON, then all the remaining
related parameters for Remote ENIM and import will be enabled.

7.116 ENBLSTBYCMD

Specific to C300, PGM and FIM4, UOC.


Block(s)
Description Enable Standby
Data Type Boolean
Range Off (0) On (1) N/A
Default Off
Config Load No, Yes
Active No
Loadable
Access Lock Operator, Supervisor
Residence C300, FIM4, PGM, NOLOAD
Related N/A
Parameters
Remarks Used to command synchronized secondary to reboot into the Standby state. This
parameter has edge trigger semantics and always returns OFF when read.

- 944 -
Chapter 7 - Exxxx Parameters

7.117 ENBLSYNCCMD

Specific to C300 and FIM4,EHG, PGM, TCMI


Block(s)
Description Enable Synchronization
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load No
Active No
Loadable
Access Lock Operator
Residence C300, FIM4, EHG, PGM
Related DSBLSYNCCMD
Parameters
Remarks Used to command initial synchronization (and enable auto-synchronization). This
parameter has edge trigger semantics and always returns OFF when read.

Specific to Block(s) UOC


Description Enable Synchronization
Data Type Boolean
Range Off (0) On (1) N/A
Default
Config Load Yes
Active Loadable
Access Lock Operator
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

7.118 ENBMEMALMFL

Specific to CEEC300, ACE, CPM, SIM_C200, CEEUOC, CEECN100


Block(s)
Description Enable Memory Limit Exceeded Alarm
Data Type Boolean
Exposure None
Range Off (0) Memory Limit Exceeded alarm disabled.
On (1) Memory Limit Exceeded alarm enabled.
Default On (1)
Config Yes
Load

- 945 -
Chapter 7 - Exxxx Parameters

Active No
Loadable
Access Lock Operator
Residence C300, ACE, C200, SIMC200, UOC, CN100
Related FREEMEM, MAXFREEBLKSZ, USEDMEM
Parameters
Remarks A “Memory Limit Exceeded” alarm is generated by the CPM block when the user
visible pool of memory has been exhausted. The alarm returns-to-normal, if either
this flag is disabled or sufficient control strategy is deleted from the user pool such
that FREEMEM is a positive number.

7.119 ENBNOLOAD[0..numChans-1]

Specific to 1738-OB2EPM12 and 1738-OB8EM12


Block(s)
Description Enable No Load — This parameter is part of configuration assembly for this module
and is used to turn on and turn off No Load Detection.
Data Type Boolean
Range l 0 : OFF
l 1 : ON
Default ON
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related None
Parameters
Remarks

7.120 ENBSCHDTRAF

Specific to Block CPM


(s)
Description Enabled Scheduled Traffic - Indicates status of scheduled traffic function.
Data Type Boolean
Range OFF (0) Scheduled traffic disabled.
ON (1) Controller is configured for scheduled
traffic use.
Default OFF (0)
Config Load Yes
Active Loadable No

- 946 -
Chapter 7 - Exxxx Parameters

Access Lock Application Developer Only


Residence C200
Related
Parameters
Remarks

7.121 ENBSHUTDOWN

Specific to IOLIM, Secondary IOLIM


Block(s)
Description Enable Shutdown. Lets user enable or disable the shutdown command function
for the associated IOLIM.
Data Type Boolean
Range Off (0): IOLIM cannot be commanded to shutdown. On (1): IOLIM can be
commanded to shutdown.
Default None
Config Load No
Active No
Loadable
Access Lock Engineer
Residence IOLIM
Related
Parameters
Remarks This parameter inhibits a user from accidentally issuing a shutdown command
to an IOLIM .

7.122 ENCMDS

Specific to IOLIM, Secondary IOLIM, C300 IOLINK


Block(s)
Description Enable IOLIM/IOLINK Commands.
Data Type Boolean
Range Off (0): IOLIM commands cannot be executed. On (1): IOLIM commands can be
executed.
Default Off (0)
Config No
Load
Active No
Loadable

- 947 -
Chapter 7 - Exxxx Parameters

Access Lock Engineer


Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks This parameter is a lock to prevent users from accidentally executing the shutdown
or purge database commands for the IOLIM. The “Shutdown IOLIM,” “Purge IOLIM
Database,” and “Compact NVS” commands can only be executed if ENCMDS is ON.

7.123 ENDOFFSET

Specific to Step
Block(s)
Description End Offset in seconds
Data Type 32-Bit Integer
Range
Default 0
Config Yes
Load
Active No
Loadable
Access Application Developer Only
Lock
Residence SR
Related
Parameters
Remarks Minitrend frozen values use two parameters defined for the step to allow visibility
for phenomena occurring before the step started and after the step completed.
Both times are in seconds with a Default of 0. ENDOFFSET defines how much
history is shown after the step completed. The end time is calculated as: End time =
Step end + ENDOFFSET When the step is repeated as part of an execution loop in
SCM/RCM, the step start time is larger that the recorded step end time when the
step is reactivated. In this case, the minitrend display resumes the realtime method
for the current values for the duration of the repeated step execution.

7.124 ENDPHASE

Specific to ProfitCtl
Block(s)
Description Algo End Processing Phase
Data Type INT32
Range NA
Default 0
Config No
Load

- 948 -
Chapter 7 - Exxxx Parameters

Active No
Loadable
Access Lock VIEWONLY
Residence NOLOAD
Related STARTPHASE
Parameters
Remarks This parameter represents the CEE phase in which profit controller execution
finishes. Since the execution of this block happens in background processing, this
block may not finish execution in the same phase where it started executing

7.125 ENDTIME

Specific to Step,Phase
Block(s)
Description Completion Time
Data Type TimeOfDay
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related STARTTIME
Parameters
Remarks A step is “complete” , when the next transition is true and when the transition to
the next step has been processed. Time when step/phase has been deactivated
and has been removed from ACTIVELOC.STEP[1..15]

Specific to Block(s) ProfitCtl


Description Exec End Time
Data Type INT32
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters STARTTIME
Remarks

- 949 -
Chapter 7 - Exxxx Parameters

7.126 ENETIPADDR[0-3]

Specific to Block CEEFB


(s)
Description ENET Module IP Address — Indicates the IP Address of the ENET Adapter in
the chassis.
Data Type String
Range 15 characters
Default 0.0.0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks

7.127 ENETIPADDR

Specific to EIM EIP Protocol Block


Block(s)
Description ENET Module IP Address — Indicates the IP Address of the ENET Adapter in
chassis.
Data Type STRING
Range 15 Characters
Default 0.0.0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NoLoad
Related -
Parameters
Remarks IP Address of the ENET interface module used to connect to the Control Logix
module mounted on a 1756 chassis.

- 950 -
Chapter 7 - Exxxx Parameters

Specific to Block(s) CEE


Description ENET Module IP Address — Indicates the IP Address of the ENET Adapter in
chassis.
Data Type STRING
Range 15 Characters
Default 0.0.0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related -
Parameters

Remarks -

7.128 ENGUNITSYSTEM

Specific to Block(s) Steam Property Block


Description Engineering Unit System
Data Type ENUM
Range SI
METRIC
ENGLISH
Default SI
Config Load Yes
Access Lock Application Developer Only
Active Loadable No
Residence CEE
Related Parameters
Remarks

7.129 ENHGENLIN1

Specific to HRBALG_REG block


Blocks
Description ENHGENLIN1 FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Yes

- 951 -
Chapter 7 - Exxxx Parameters

Load
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the ENHGENLIN1 block in the emulation CM,
which holds the HRBALG_REG instance. This parameter connector is used in an EC
algorithm emulation to read or write segment co-ordinates for the Characterizer
algorithm.
Checkpoint Yes

7.130 ENHGENLIN2

Specific to HRBALG_REG block


Blocks
Description ENHGENLIN2 FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the ENHGENLIN2 block in the emulation CM,
which holds the HRBALG_REG instance. This parameter connector is used in an EC
algorithm emulation to read or write segment co-ordinates for the Characterizer
algorithm.
Checkpoint Yes

7.131 ENHREGCALC

Specific to HRBALG_REG block


Blocks
Description ENHREGCALC FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Load Yes

- 952 -
Chapter 7 - Exxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the ENHREGCALC block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

7.132 ENIMIPADDR

Specific to Block(s) TCMI


Description ENIM IP Address
Data Type STRING
Range N/A
Default 10.10.1.121
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

7.133 ENIMIPADDRESS

Specific to EHPM
Block(s)
Description ENIM IP address is the FTE IP address of owner ENIM for the current EHPM. This
ENIM IP address is calculated based on the owning ENIM device index entered.
Data Type STRING
Range -
Default 0.0.0.0
Config Yes
Load
Active Yes
Loadable

- 953 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence ERDB
Related OWNINGENIM
Parameters
Remarks Automatic Import service uses this ENIM IP address to establish communication
with the ENIM (assigned with this IP address). Primary and secondary ENIMs are
connected using provided IP address and provided IP address +1 respectively.

7.134 ENIMUCNNUM

Specific to Block(s) ELCN_NODE (ENIM)

Description EUCN Network Number

Data Type 32-Bit Integer

Range 1 to 20

Default 0

Config Load No

Active Loadable No

Access Lock AppDevOnly

Residence ELCN_NODE

Related Parameters ELCN_NODE Main tab

Remarks

7.135 ENOLOAD[0..numChans-1]

Specific to Block(s) DOM


Description Enable No Load
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters NOLOAD
Remarks ENOLOAD is only configurable on diagnostic modules.

- 954 -
Chapter 7 - Exxxx Parameters

7.136 ENPULSEWIDTHREJ

Specific to Series C PICHANNEL


Block(s)
Description Enable Pulse Width Rejection
Data Type BOOLEAN
Range OFF(0) ON(1)
Default OFF
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence IOM
Related
Parameters
Remarks l When enabled, only pulse widths greater than the (*) “Minimum Pulse Width”
will be counted.
l When disabled, the module will attempt to count any pulse width.
This parameter may odified only if the channel is INACTIVE. Note: Refer to the
Series C Spec and Tech data for the specific duration.

7.137 ENSPAREDETECT

Specific to UIO-2 IOM


Block(s)
Description Detect Connections to Spare Channels
Data Type BOOLEAN
Range 0 OFF Disable Connections to
Spare Channels Detection
1 ON Enable Connections to
Spare Channels Detection
Default OFF
Config Yes
Load
Access Lock Engineer
Residence IOM
Related -
Parameters
Remarks This parameter allows the user to enable/disable detection of connections to spare
channels. When enabled, if a load is detected on a channel configured as SPARE
an alarm is annunciated to the System Alarm Summary indicating “Device Found
on Spare Channel”.

- 955 -
Chapter 7 - Exxxx Parameters

7.138 ENTERSBYCMD

Specific to RM
Block(s)
Description Enter Standby Command
Data Type Boolean
Range True (0) False (1)
Default True (0)
Config Load No
Active No
Loadable
Access Lock Operator Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

7.139 ENTHALPY

Specific to Block(s) Steam Property Block


Description Enthalpy (H) Value
Data Type IEEE_FLOAT64
Range Any Real Number
Default IEEENaN
Config Load No
Access Lock Engineer
Active Loadable No
Residence CEE
Related Parameters
Remarks

- 956 -
Chapter 7 - Exxxx Parameters

7.140 ENTHALPYENGUNIT

Specific to Block(s) Steam Property Block


Description Enthalpy (H) Engineering Unit
Data Type ENUM
Range kJ/kg degree K SI Unit
kcal/kg degree C Metric Unit
Btu/lb degree F Eng Unit
Default kJ/kg degree K
Config Load Yes
Access Lock Application Developer Only
Active Loadable No
Residence SR
Related Parameters
Remarks

7.141 ENTHALPYIO

Specific to Block(s) Steam Property Block


Description Enthalpy (H) IO Configuration
Data Type ENUM
Range Input Parameter configured as Input
Output Parameter configured as Output
Not Configured Parameter configured as None
Default Not Configured
Config Load Yes
Access Lock Application Developer Only
Active Loadable No
Residence CEE
Related Parameters
Remarks

7.142 ENTITYNAME

Specific to Block(s) Most Standalone Blocks


Description Item Name - Specify name that acts as an alias to the peer device name.
Data Type String
Range 40 Characters

- 957 -
Chapter 7 - Exxxx Parameters

Default
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

7.143 ENTROPY

Specific to Block(s) Steam Property Block


Description Entropy (S) Value
Data Type IEEE_FLOAT64
Range SI 0 to 10 KJ/Kg-K
Metric 0 to 2.4 Kcal/Kg degree C
English 0 to 2.4 Btu/lb degree F
Default IEEENaN
Config Load No
Access Lock Engineer
Active Loadable No
Residence CEE
Related Parameters
Remarks

7.144 ENTROPYENGUNIT

Specific to Block(s) Steam Property Block


Description Entropy (S) Engineering Unit
Data Type ENUM
Range kJ/kg degree K SI Unit
kcal/kg degree C Metric Unit
Btu/lb degree F Eng Unit
Default kJ/kg degree K
Config Load Yes
Access Lock Application Developer Only

- 958 -
Chapter 7 - Exxxx Parameters

Active Loadable No
Residence SR
Related Parameters
Remarks

7.145 ENTROPYIO

Specific to Block(s) Steam Property Block


Description Entropy (S) IO Configuration
Data Type ENUM
Range Input Parameter configured as Input
Output Parameter configured as Output
Not Configured Parameter configured as None
Default Not Configured
Config Load Yes
Access Lock Application Developer Only
Active Loadable No
Residence CEE
Related Parameters
Remarks

7.146 ENUMBOOLMAP[0..63]

Specific to TypeConvert, Push


Block(s)
Description An array used when converting Enumerations to Boolean values.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks This is applicable for conversioin between Enumerations and Boolean values. The
output Boolean value will be whatever the corresponding ENUMBOOLMAP value is
set to.

- 959 -
Chapter 7 - Exxxx Parameters

7.147 EPKSACCESS

Specific to Block(s) OPCUASRVUOC


Description Experion Access
Data Type ENUM
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEESRAL
Related Parameters None
Remarks

7.148 EPKSMIGRATIONMODE

Specific to ELCN_BRG
Block(s)
Description Experion Migration Mode Enabled
Data Type Boolean
Range FALSE (default) - The ELCN Bridges are not in the Experion Migration Mode.

TRUE - The ELCN Bridges are in the Experion Migration Mode.


Default FALSE (Checkbox is unchecked).
Config
Load
Active
Loadable

- 960 -
Chapter 7 - Exxxx Parameters

Access Writable only during ELCN Bridge Control Builder block initial load.  Read Only
Lock thereafter.
Residence The value (or state) of this parameter is retained and remembered if the ELCN Bridges
are rebooted. The parameter is synchronized to the secondary ELCN Bridge platform
block, but not shown on the secondaryELCN Bridge Control Builder block or Experion
Detail Display for either the primary or secondary ELCN Bridge.
Related
Parameters
Remarks This parameter is used only during an Experion On-Process Migration when migrating
from an Experion Release prior to R510 to an Experion Release of R510 (or greater). 
This parameter is necessary for the initial installation of the ELCN Bridge and only
during an Experion On-Process Migration.
As long as the checkbox remains checked, you can delete the ELCN Bridge Control
Builder blocks from the “ELCN Bridge Commissioning Server” without affecting the
running state functionality of the ELCN Bridge(s).
Only writeable at ELCN Bridge Control Builder block build time. Read Only after
loading to Monitoring side. Visible only on the primary ELCN Bridge Control Builder
block. Not visible on the Experion Detail Display of either the primary or secondary
ELCN Bridge.
NOTE:  The Control Builder block for the secondary ELCN Bridge does not show this
parameter. It is automatically synchronized and configured from the value in the
primary block.
The EPKSMIGRATIONMODE parameter should be set TRUE (the checkbox checked
for Experion Migration Mode Enabled) when “commissioning” new ELCN Bridges
during an Experion On-Process Migration from a release prior to Experion R510.1 (for
example, R431.5) to Experion R510.1 or to any later Experion Server release that
supports ELCN Bridge.
The summary of this “commissioning” process is as follows:
l In the Project Side of Control Builder, after setting the parameter TRUE,load
the ELCN Bridge Control Builder blocks to the temporary R510.1 or later ELCN
Bridge Commissioning Server.
l After the full Experion On-Process Migration is complete (that is, out of dual
primary mode), and this parameter value is TRUE, you can delete the ELCN
Bridge Control Builder blocks from the ELCN Bridge Commissioning Server’s
Monitoring tab, without affecting the ELCN Bridge operation.
l Configure new ELCN Bridge Control Builder blocks on the fully migrated
Experion System’s Experion Server (the blocks could be pre-built to the Project
tab. Set the EPKSMIGRATIONMODE parameter to FALSE (default) – checkbox
is unchecked for Experion Migration Mode Enabled. Load the new platform
blocks.

REFERENCE: The entire process to use this parameter along with the ELCN Bridge
Commissioning Server is documented in the ELCN Overview and Implementation
Guide.

7.149 EPKSNAME

Specific to Block(s) OPCUASRVUOC


Description Experion Name
Data Type INOUTCONN
Range

- 961 -
Chapter 7 - Exxxx Parameters

Default
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

7.150 EPKSSTATUS

Specific to Block(s) OPCUASRVUOC


Description Experion Status
Data Type UINT32
Range 0 to 4294967295
Default
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence CEEAL
Related Parameters None
Remarks

7.151 EPLCGCH1BAUDRATE

Specific to Block(s) ELCN_NODE (EPLCG)


Description Port 1 baud rate
Data Type ENUM
Range 19200/9600/4800/2400/300/150/50

Default 9600
Config Load Initial load
Active Loadable Not Applicable
Access Lock Control Builder
Residence CEE
Related EPLCGCH1PARITY
Parameters
Remarks Baud rate used in communication with PLCs attached to the EPLCG Field
Port 1.

- 962 -
Chapter 7 - Exxxx Parameters

7.152 EPLCGCH1PARITY

Specific to Block(s) ELCN_NODE (EPLCG)


Description Port 1 Parity
Data Type ENUM
Range EVEN, ODD

Default ODD
Config Load Initial load
Active Loadable Not Applicable
Access Lock Control Builder
Residence CEE
Related Parameters EPLCGCH1BAUDRATE
Remarks Serial parity in communication with PLCs attached to the EPLCG Field Port
1.

7.153 EPLCGCH2BAUDRATE

Specific to Block(s) ELCN_NODE (EPLCG)


Description Port 2 baud rate
Data Type ENUM
Range 19200/9600/4800/2400/300/150/50

Default 9600
Config Load Initial load
Active Loadable Not Applicable
Access Lock Control Builder
Residence CEE
Related EPLCGCH2PARITY
Parameters
Remarks Baud rate used in communication with PLCs attached to the EPLCG Field
Port 2.

7.154 EPLCGCH2PARITY

Specific to Block(s) ELCN_NODE (EPLCG)


Description Port 2 Parity
Data Type ENUM
Range EVEN, ODD

Default ODD
Config Load Initial load
Active Loadable Not Applicable

- 963 -
Chapter 7 - Exxxx Parameters

Access Lock Control Builder


Residence CEE
Related Parameters EPLCGCH2BAUDRATE
Remarks Serial parity in communication with PLCs attached to the EPLCG Field Port
2.

7.155 EPLCGMULTIBUFPIPELINE

Specific to ELCN_NODE (EPLCG)


Block(s)
Description Multi-Buffer Pipelining
Data Type BOOLEAN
Range TRUE, FALSE

Default TRUE
Config Initial load
Load
Active Not Applicable
Loadable
Access Control Builder
Lock
Residence ELCN Parameter Block
Related
Parameters
Remarks Perform data acquisition using multiple 'pipelined' buffers. Use this option to obtain
maximum data acquisition performance at the expense of increased PLC network
bandwidth consumption. By default, data acquisition uses a single non-pipelined
buffer to reduce PLC network bandwidth consumption at the expense of decreased
data acquisition performance.

7.156 EPLCGREDUNDCOMMSOPTION

Specific to ELCN_NODE (EPLCG)


Block(s)
Description Redundant Communications
Data Type BOOLEAN
Range TRUE, FALSE

Default FALSE
Config Load Initial load
Active Not Applicable
Loadable

- 964 -
Chapter 7 - Exxxx Parameters

Access Lock Control Builder


Residence CEE
Related
Parameters
Remarks When set to FALSE Ports 1 and 2 provide two independent paths each
communicating with a set of unique PLCs.
When set to TRUE Ports 1 and 2 provide redundant communication path to a single
set of PLCs.

7.157 EPLCGUSEROUTPUTSUPPRESS

Specific to ELCN_NODE (EPLCG)


Block(s)
Description User Output Suppression
Data Type Boolean
Range TRUE, FALSE

Default FALSE
Config Load Initial load
Active Not Applicable
Loadable
Access Lock Control Builder
Residence CEE
Related
Parameters
Remarks A value of FALSE permits user outputs to PLC via Analog outputs, Digital Outputs
and Timer/Counters.
A value of TRUE suppresses user outputs to PLC via Analog outputs, Digital
Outputs and Timer/Counters.

Keepalives are not affected.

7.158 EPMSTATE

Specific to Block(s) Controller Rack, IO RACK


Description Module State
Data Type Enumeration
Range 0 Offline
1 Online

Default Offline
Config Load Yes
Active Loadable No

- 965 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence Controller Rack, IO RACK
Related Parameters
Remarks Current state of the Controller Rack or IO RACK.

7.159 EQMTORECMAP

Specific to Block(s) SCM


Description Recipe Response to Equipment State Mapping
Data Type Enumeration
Range 0 None
1 Default

2 Start
3 Reset
4 Interrupt
5 Restart
6 Hold
7 Stop
8 Abort
9 Resume
Default Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

7.160 EQNEUNITSOPT

Specific to Block(s) PID


Description Proportional-Only (Equation E) Units Option
Data Type Enumeration
Range 0 EUs Use Engineering Units
1 Percent Use percent
Default EUs (0)
Config Load Yes
Active Loadable No

- 966 -
Chapter 7 - Exxxx Parameters

Access Lock Engineer/Application Developer


Residence CEE
Related Parameters
Remarks

7.161 EQUIPEXECSTS

Specific to Block Phase


(s)
Description last processed value of parameter EXECSTS of block defined by EQUIPNAME
Data Type Enum
Range Like EXECSTS (SCM, RCM)
Default n/a
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related ACQUIREOPT, RELEASEOPT, EQUIPNAME, CONFIGCODE, EXECSTS,
Parameters EXECUTEOPT
Remarks will not be updated, if Phase block is inactive will not have a useful value, if
EXECUTEOPT=OFF

7.162 EQUIPNAME

Specific to Block(s) Phase


Description Name of the resource to be acquired
Data Type BlockId
Range Tagged Container Block in same cluster ( must be RCM, SCM, CM or UCM)
Default Null
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters ACQUIREOPT, RELEASEOPT, CONFIGCODE
Remarks

- 967 -
Chapter 7 - Exxxx Parameters

7.163 EQUIPMODE

Specific to Block Phase


(s)
Description last processed value of parameter MODE of block defined by EQUIPNAME
Data Type Enum
Range Like MODE (SCM,RCM)
Default n/a
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related ACQUIREOPT, RELEASEOPT, EQUIPNAME, CONFIGCODE, MODE,
Parameters EXECUTEOPT
Remarks will not be updated, if Phase block is inactive will not have a useful value, if
EXECUTEOPT=OFF

7.164 EQUIPMODEATTR

Specific to Block Phase


(s)
Description last processed value of parameter MODEATTR of block defined by EQUIPNAME

Data Type Enum


Range Like MODEATTR (SCM, RCM)
Default n/a
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related ACQUIREOPT, RELEASEOPT, EQUIPNAME, CONFIGCODE,
Parameters MODEATTREXECUTEOPT
Remarks will not be updated, if Phase block is inactive will not have a useful value, if
EXECUTEOPT=OFF

- 968 -
Chapter 7 - Exxxx Parameters

7.165 EQUIPREQ.STS

Specific to Block(s) Phase


Description Phase Blocks Requester Store Connection to Equipment
Data Type INT32
Range 0 – MAX int 32
Default n/a
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EQUIPNAME
Remarks

7.166 EQUIPSTATE

Specific to Phase
Block(s)
Description last processed value of parameter STATE of block defined by EQUIPNAME
Data Type Enum
Range Like STATE (SCM,RCM)
Default n/a
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACQUIREOPT, RELEASEOPT, EQUIPNAME, CONFIGCODE, STATE, EXECUTEOPT
Parameters
Remarks EQUIPSTATE will not be updated, if Phase block is inactive EQUIPSTATE will not
have a useful value, if EXECUTEOPT=OFF

7.167 EQUIPSTATUS.STS

Specific to Block(s) Phase


Description Phase Blocks Store Connection to Equipment
Data Type INT32
Range 0 – MAX int 32
Default n/a

- 969 -
Chapter 7 - Exxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EQUIPNAME
Remarks

7.168 ERRATICFLOW[1..24]

Specific to Block QIPACTERM


Description Too High or Too Low Flow
Data Type Boolean
Range Off(0) OK
On(1) Too High or Too Low Flow
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 9 of the Status 2 word in the input assembly for the
designated position [1-24].

7.169 ERRATICFLOW[1..200]

Specific to QIPACCHAN
Block
Description Too High or Too Low Flow
Data Type Boolean
Range Off(0) OK
On(1) Too High or Too Low Flow
Default Off
Config Load No
Active No
Loadable

- 970 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This is the value of bit 9 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

7.170 ERRCNT[0..1]

Specific to Block(s) PCDI_MASTER


Description Error Count: Reset Statistics
Data Type Boolean
Range True/False
Default False
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks

- 971 -
Chapter 7 - Exxxx Parameters

7.171 ERRCODE

- 972 -
Chapter 7 - Exxxx Parameters

Specific to SIFLAGARRCH, SINUMARRCH, SITEXTARRCH.


Block(s)
Description Detailed Error Code - Provides an indication of the status of the array data for each
channel. Holds and returns the last reported status from a series.
Data Type String

- 973 -
Chapter 7 - Exxxx Parameters

Range Length: 8 characters Possible String values:

- 974 -
Chapter 7 - Exxxx Parameters

Codes set by Serial Interface Array Channel block

- 975 -
Chapter 7 - Exxxx Parameters

Ch_Inctv: The Channel block is inactive.

- 976 -
Chapter 7 - Exxxx Parameters

Md_Inctv: The SIM block is inactive, so the Channel block cannot obtain new
array data.
CEE_Idle: The CEE is Idle, so the Channel block is not executing.
ChCfgErr: A Channel block configuration error exists. Check that the Number of
Elements configured is appropriate for the Starting Index of the device.
Or for the Serial Interface Text Array Channel block, that the
configured NSTRING and STRLEN do not exceed 64 characters.
No_SIMFB: The Channel block cannot locate its assigned SIM block. Check that the
SIM block is loaded to the CEE.
No_Data: ERRCODE is set “No_Data” when the Channel block is activated or the
CEE is set to RUN. If the Channel block is still not executing because
either the Channel block is Inactive or the CEE is Idle, ERRCODE will
continue to report “No_Data” until the next transition of the CEE or
Channel block. If the Channel block is executing, “No_Data” should
only be seen for a short period of time before ERRCODE is set to either
a good or bad value
No_Conn: The Channel block cannot obtain array data because a proper
connection does not exist between the CPM (Controller) and SIM.
IO_Comm: There is an I/O Communications problem between the CPM
(Controller) and SIM.
DataCond: The Channel block has received a Data Conditioner it does not
understand. A Data Conditioner is an internal value sent by the FTA
that indicates how the 64 bytes of data should be interpreted.
Codes set by SIM

NO_CONF Initial value set by the SIM


CFG_LOAD Set by SIM when it is attempting to load configuration to the FTA.
MOD_IDLE SIM is idle.
CFG_WAIT The SIM is waiting for valid communications from the FTA before
attempting to send the slot configuration.
ARR_INIT Set by the FTA after receiving configuration.
CONFIG The SIM cannot load a configuration.
FTA_COMM The SIM cannot communicate with the FTA.

#_ELEMNT The number of elements does not match Data Type.

Codes set by Serial Inteface FTA (common)

Dev_Addr The device address has a configuration error.


DataType The Data Type has a configuration error.
Startidx The start index has a configuration error
#_Elemnt A number of elements configuration
Config An application specific configuration error has occurred
Inv_Resp An invalid field device response has occurred.
Parity A field device communication error has occurred
Checksum
MsgTmout
ChrTmout
Ex or xx An exception or other field bus device error has occurred. The “xx”error
code is specific to the field device.

- 977 -
Chapter 7 - Exxxx Parameters

OK No errors exist.
Default
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related ERRFL
Parameters
Remarks

- 978 -
Chapter 7 - Exxxx Parameters

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Error Status on the last request operation.
Data Type Enumeration

- 979 -
Chapter 7 - Exxxx Parameters

Range 0 OK Successful return value

- 980 -
Chapter 7 - Exxxx Parameters

1 No More Ok status - No more data to process


Data
2 Already Ok status - the buffer has already been added to the send
Added queue
3 Send Limit Ok status - no more requests may be sent because the
configured limit has been reached
4 Orphan Resp Ok status - received message does not have a waiting
request. Request either timed out or was already answered.
5 Diag Testing No error - diagnostic testing in process
6 Already No error - request is already on the queue and send limit is
Added with in affect
Send Limit
256 Generic Fail Unexpected internal failure
257 Not Init The block has not correctly registered for access to shared
memory and has an invalid pointer to shared memory
objects.
258 Invalid An invalid parameter has been specified
Param
259 Unsupported An unsupported MODBUS function code was specified in a
Cmd request. Supported MODBUS function codes must be
configured in the corresponding MBTCP_MASTER block.
260 Resources Failure to allocate a buffer for a request.
261 Invalid UID Request was issued for an unconfigured MODBUS Unit
Index (UID). All devices must be configured in the
corresponding MBTCP_MASTER block.
262 No Device
263 Add Fail
264 Send Fail Failed to send the request
265 Send Err
266 No Conn No connection is available on which to send the request
267 Sock Err A socket error occurred - socket error code is available in the
connection ERRINFO parameter.
268 Bad Buffer An invalid buffer index was specified
269 Internal Err Internal error indicating that an object pointer was not valid
(Null)
270 Timed Out The request timed out
271 Not Found The specified object was not found
272 Wait Failed A system synchronization object wait failed
273 Dev Disabled The specified MODBUS device is disabled in the MBTCP_
MASTER block
274 Rcv Msg Len The specified buffer length is invalid based on expected
content - usually applies to a receive buffer validation.
275 Bad Resp Request response was not formatted as expected (other
than length)
276 Bad Xact The MODBUS TCP transaction id was malformatted.
277 Unexpected The response to a diagnostic request contained an

- 981 -
Chapter 7 - Exxxx Parameters

Diag Val unexpected data value based on diagnostic configured


value.
278 Master The diagnostic test failed - expected value was not received
Inactive
279 Device Init Request could not be sent, associated device is still in
INITIAL state
280 Device Fail Request could not be sent, associated device is in FAILED
state
281 SM Idle Request could not be sent, Safety Manager is in IDLE state
512 Illegal Func
513 Illegal Addr
514 Illegal Data
515 Slave Fail
516 Ack Fail
517 Slave Busy
518 Parity Err
519 Bad Path
520 No Target
Resp
Default Not Init
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 982 -
Chapter 7 - Exxxx Parameters

7.172 ERRCODE[0..1]

Specific to PCDI_MASTER
Block(s)
Description Last Error
Data Type Enumeration
Range 0 OK Successful
256 Conn The connection in use has been forced
Forced
257 Socket Socket related error, non-catastrophic, was returned from the
Warn stack. Extended error code contains the system error
258 Conn Fail A single connection has failed, the alternate connection is in use
259 Count A parameter with a predefined threshold has exceeded that
Exceeded threshold

260 Send A send operation blocked


Blocking
512 Not Init Block has not been mapped into shared memory yet
513 Socket Socket related error returned from the stack. Extended error code
Err contains the system error
514 Timedout The request has timed out. This is only set after retries have
timed-out
515 No Conn Failed to connect to either primary or secondary device or both
connections have failed
516 Send Fail Generic send failed err
517 Msg Size Sent size did not match buffersize to send
518 Invalid Failed to get a receive buffer
Buffer
519 Invalid Invalid parameter passed
Param
520 Devs All serial devices have failed
Failed
Default Not Init
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Device
Related
Parameters
Remarks

- 983 -
Chapter 7 - Exxxx Parameters

7.173 ERRCODE[0..31]

Specific to Serial Interface IOM


Block(s)
Description Detailed Error Code - Provides an indication of the status of the array data for each
Channel.
Data Type String
Range Length: 8 characters. Possible String values:
NO_CONF: Inital value set by SIM
CFG_LOAD: Set by SIM when loading configuration to FTA
ARR_INIT: Set by FTA after receiving configuration
CONFIG: Set by SIM if it cannot load a configuration
FTA COMM: Set by SIM if it cannot communicate with the FTA
#ELEMNT: Set by SIM if number of elements does not match
data type (possibly also set by FTA)
OK_POLL No errors exist against the Array channel block
whose poll rate is within 0 to255.
Default Null String
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ERRFL
Parameters
Remarks

7.174 ERRFL

Specific to SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


Block(s)
Description Flag that indicates that an error response was received for the last request sent by
this request block. Note that this flag is set to TRUE for both local errors
(communication errors that prevented the request from being sent out on the
network, for example) and remote errors (the target device could not process the
request and so sent an explicit failure status). For alarming on errors, connect the
ERRFL to a Flag Block and configure the Flag Block to send an Alarm when ERRFL
is TRUE.
Data Type Boolean
Range Off (0): data is okay On (1): data is invalid
Default Off (0)
Config No
Load
Active No
Loadable

- 984 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly (When FECTCHMODE is 0) Engineer (When FETCHMODE is 1)


Residence CEE
Related BADPVFLERRCODEINITREQFETCHMODE.
Parameters
Remarks

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Overall Error Flag
Data Type Boolean
Range True/False
Default True
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

7.175 ERRFL[0..1]

Specific to Block(s) PCDI_MASTER


Description Error Flag
Data Type Boolean
Range True/False
Default True
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

7.176 ERRFL[0..31]

Specific to Serial Interface IOM


Block(s)
Description Overall Error Flag - Indicates the validity of the array data for each Channel; when
Off - the data is Ok, and when On the data is invalid.
Data Type Boolean
Range Off (0) On (1)

- 985 -
Chapter 7 - Exxxx Parameters

Default Off (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ERRCODE[0..31]
Parameters
Remarks

7.177 ERRIN1AV

Specific to Block(s) TCMI

Description Errors in CH1 Avg Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

7.178 ERRIN2AV

Specific to Block(s) TCMI

Description Errors in CH2 Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

- 986 -
Chapter 7 - Exxxx Parameters

7.179 ERRINFO[0..1]

Specific to Block(s) PCDI_MASTER


Description Additional Error information
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

7.180 ERRORCODE

Specific to RM
Block(s)
Description Redundancy Module Status Code, as it appears on the front panel of the
Redundancy Module.
Data Type String
Range Maximum of 6 characters
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

7.181 ERRORDBL

Specific to Block(s) PosProp, PidPosProp (when PV > SP)


Description Error Deadband for the lower direction (in percent).
Data Type Real
Range 0.0 to 100.0%
Default 5.0%

- 987 -
Chapter 7 - Exxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

7.182 ERRORDBR

Specific to Block(s) PosProp, PidPosProp (when PV < SP)


Description Error Deadband for the lower direction (in percent).
Data Type Real
Range 0.0 to 100.0%
Default 5.0%
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

7.183 ERRORINDICATOR
Delete this text and replace it with your own content.

7.184 ERRORMSGIDX

Specific to RM
Block(s)
Description Redundancy Module Error Message Index. Full error code, which references a
matching test string.
Data Type 16-Bit Unsigned Integer
Range 0 to 65535
Default N/A
Config Load No
Active No
Loadable

- 988 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

7.185 ERROSPRESENT

Specific to Block(s) EIM


Description Errors Present
Data Type BOOL
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

7.186 ERROUTAV

Specific to Block(s) TCMI

Description Errors Output Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

- 989 -
Chapter 7 - Exxxx Parameters

7.187 ESCKEYSTROKE[1..4]

Specific to JAGXCHAN
Block(s)
Description Escape KeyStroke
Data Type Boolean
Range Off(0) Off
On(1) Escape Key
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 8 of the status word in the floating point input assembly for
the designated scale slot [1..4].

7.188 ESIG

Specific to Block(s) All Blocks, UOC


Description Electronic Signature License
Data Type String
Range N/A
Default “Electronic Signature is a Licensed Option”
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence Server
Related Parameters PRIMARYSIG, SECONDARYSIG
Remarks

7.189 ESTDURATION

Specific to Step
Block(s)
Description Estimated Trend Duration in seconds
Data Type 32-Bit Integer
Range

- 990 -
Chapter 7 - Exxxx Parameters

Default 0
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks Minitrend realtime trend is used for current values and uses a parameter defined
for the step and phase to define the default range for the time scale. The value of
this parameter is the estimated duration (ESTDURATION) of the step/phase
execution. The time is in seconds. If no value or the value is zero, the estimated
duration time is calculated from the trend update interval of the step. The start and
end times are calculated as: Start time = Current time - ESTDURATION

7.190 ESTWEIGHT

Specific to CM, SCM, IOM, PIOMB


Block(s)
Description Holds estimate of block execution time that CEE uses for cycle load distribution.
Data Type 64-Bit Real Number
Range NaN, 0.0, non-zero values
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related PHASE
Parameters
Remarks This parameter is not supported until a future release. It specifies an estimate for
execution time (in units of PU) of a CM function block or SCM function block. CEE
uses the ESTWEIGHT values it receives to track block execution loading for each
cycle. If PHASE is set to -1 at the time of load, CEE assigns a value to PHASE so that
the block executes on the least loaded cycle. If ESTWEIGHT is loaded with the value
of NAN or 0.0, CEE assigns a low precision default value to ESTWEIGHT.

- 991 -
Chapter 7 - Exxxx Parameters

7.191 ESWENB

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RatioBias, RegCalc, RegSummer, RemCas, Switch.
Description External Mode Switch Enable State - Indicates if external mode switching is
enabled.
Data Type Enumeration ENABLE
Range Disable (0): External mode switching is disabled. Enable (1): External mode
switching is enabled.
Default Disable (0)
Config Yes, this parameter is loadable.
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related ESWFL.AUTO, ESWFL.BCAS, ESWFL.CAS, ESWFL.MAN, ESWPERM.
Parameters
Remarks When external mode switching is enabled, REDTAG can not be turned ON. To red
tag a point in which external mode switching is enabled, you must first disable the
external mode switching and then set the REDTAG parameter to “On.”

7.192 ESWFL.AUTO

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RatioBias, RegCalc, RegSummer, RemCas, Switch.
Description External Switch Flag for Auto Mode - “On” means an external source has requested
a change to Auto mode.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related ESWENB, ESWPERM.
Parameters
Remarks

- 992 -
Chapter 7 - Exxxx Parameters

7.193 ESWFL.BCAS

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RatioBias, RegCalc, RegSummer, RemCas, Switch.
Description External Switch Flag for BackupCascade Mode - “On” means an external source
has requested a change to Backup Cascade mode.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Other Function Block
Active No
Loadable
Access Lock No
Residence CEE
Related ESWENB, ESWPERM.
Parameters
Remarks

7.194 ESWFL.CAS

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RatioBias, RegCalc, RegSummer, RemCas, Switch.
Description External Switch Flag for Cascade Mode - “On” means an external source has
requested a change to Cascade mode.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related ESWENB, ESWPERM.
Parameters
Remarks

- 993 -
Chapter 7 - Exxxx Parameters

7.195 ESWFL.MAN

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RatioBias, RegCalc, RegSummer, RemCas, Switch.
Description External Switch Flag for Manual Mode - “On” means an external source has
requested a change to Manual mode.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related ESWENB, ESWPERM.
Parameters
Remarks

7.196 ESWPERM

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description External Mode Switch Permissive - Indicates if external mode switching is
permitted.
Data Type Enumeration MODEPERM
Range NOTPERM (0): External mode switching is not permitted. PERMIT (1): External
mode switching is permitted.
Default NOTPERM (0)
Config Load Yes, this parameter is loadable.
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related ESWENB, ESWFL.AUTO, ESWFL.BCAS, ESWFL.CAS, ESWFL.MAN.
Parameters
Remarks

- 994 -
Chapter 7 - Exxxx Parameters

7.197 ETH1IPADDRSTR

Specific to ELCN_NODE
Block(s)

Description Indicates the IP address for the Network Gateway “ETH1” interface. This interface
provides the NG’s “PIN A” network communications.
Data Type String
Range 169.254.1.1 to 169.254.1.255
Default NA
Config Load Yes
Active No
Loadable

Access Lock Engineer/Application Developer


Residence ELCN_NODE
Related "ETH2IPADDRSTR" on the facing page
Parameters

Remarks This is applicable only for ELCN NG node.

7.198 ETH1SOFTFAIL

Specific to Block(s) ELCN_NODE


Description Indicates whether ETH1 interface is receiving traffic (or not)
Data Type Boolean
Range True/False
Default False
Config Load False
Active Loadable No
Access Lock Read Only
Residence Platform block
Related Parameters ETH2SOFTFAIL and ETH1SILENT

- 995 -
Chapter 7 - Exxxx Parameters

7.199 ETH2IPADDRSTR

Specific to ELCN_NODE
Block(s)

Description Indicates the IP address for the Network Gateway “ETH2” interface. This interface
provides the NG’s “PIN B” network communications.
Data Type String
Range 169.254.2.1 to 169.254.2.255
Default NA
Config Load Yes
Active No
Loadable

Access Lock Engineer/Application Developer


Residence ELCN_NODE
Related ETH1IPPADDRSTR
Parameters

Remarks This is applicable only for ELCN NG node.

7.200 ETH2SOFTFAIL

Specific to Block(s) ELCN_NODE


Description Indicates whether ETH2 interface is receiving traffic (or not)
Data Type Boolean
Range True/False
Default False
Config Load False
Active Loadable No
Access Lock Read Only
Residence Platform block
Related Parameters ETH1SOFTFAIL and ETH2SILENT

7.201 ETRANS

Specific to Block(s) DOM


Description Enable Idle to Fault
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes

- 996 -
Chapter 7 - Exxxx Parameters

Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks Although loaded, this parameter is not exposed on any configuration form.

7.202 EUCNAUTHGROUP

Specific to Block(s) TCMI


Description TCMI Auth node
Data Type UINT16
Range N/A
Default 1
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

7.203 EUDESC

Specific to All Function Blocks except IOChannels and 2oo3


Block(s)
Description Block Engineering Units Descriptor - Used to describe an important aspect of the
block, for example, Engineering Units.
Data Type String
Range Length: 16 characters (See Remarks)
Default Null String
Config Load Yes
Active Yes
Loadable

- 997 -
Chapter 7 - Exxxx Parameters

Access Lock Application Developer


Residence SR
Related DESC, KEYWORD.
Parameters
Remarks The 16 characters is only a suggested limit for display purposes. Most blocks
accept up to 24 characters.

ATTENTION
l For the Data Acquisition (DATAACQ) block (if a projected
parameter pointing to a Data Acquisition block parameter), the
units configured in the DATAACQ block are displayed in Trends.
l For the Device Control (DEVCTL) block and the Flag block, empty
unit is displayed in Trends.
l For the Proportional-Integral-Derivative (PID) block (if a projected
parameter pointing to a PID block parameter), the units
configured in the PID block are displayed in Trends.
For more information about the EUDESC parameter display in Trends,
see Server and Client Configuration Guide.

7.204 EUDESC[0..120]

Specific to Block(s) PCDINUMARRCH


Description Engineering Units Description
Data Type String
Range Length: 15 characters
Default Null String
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

7.205 EURNGEXT

Specific to AICHANNEL, HAICHANNEL (PM I/O); AICHANNEL (Series C I/O)


Block(s)
Description Channel PV Range
Data Type STRUCTURE, 16 bytes long
Range N/A
Default N/A

- 998 -
Chapter 7 - Exxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks A parameter used within Experion PKS for obtaining the 4 parameters (HTDURL,
HPVURV, HPVLRV and HTDLRL) that form the basis of the Device PV range
settings.

7.206 EVALTRANS[1..15][1..10]

Specific to SCM
Block(s)
Description Currently Evaluated Transition Name
Data Type BlockId
Range N/A
Default Null String
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTIVELOC.STEP[1..15], EVALTRANSN[1..15][1..10]
Parameters
Remarks EVALTRANS[i][j] contains the name (for example, SCMName.TransitionName) of
the currently evaluated transition of branch j of thread i. EVALTRANS[1..15][1..10] is
a BlockId parameter and not supported in expressions. Its Integer-32 Partner
Parameter EVALTRANSN[1..15][1..10] can be used in Transition Condition
expressions and Step Output expressions.

7.207 EVALTRANSN[1..15][1..10]

Specific to SCM
Block(s)
Description Currently Evaluated Transition Name
Data Type 32-Bit Integer
Range N/A
Default Null String
Config No
Load

- 999 -
Chapter 7 - Exxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTIVELOC.STEP[1..15]EVALTRANS[1..15][1..10]ERRFL
Parameters
Remarks EVALTRANS[i][j] contains the name (for example, SCMName.TransitionName) of
the currently evaluated transition of branch j of thread i. EVALTRANSN[1..15][1..10]
may be used in Transition Condition expressions and Step Output expressions,
whereas EVALTRANS[1..15][1..10] (a BlockId parameter) is not supported in
expressions.

7.208 EVENTDESC

Specific to Block(s) EIM


Description Event Description
Data Type String
Range
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

7.209 EVENTFL[1..NUMEVENTS]

Specific to Block(s) RampSoak


Description RampSoak Event Flags
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 1000 -
Chapter 7 - Exxxx Parameters

7.210 EVENTBGNTIME[1..NUMPROFILES][1..NUMEVENTS]

Specific to Block(s) RampSoak


Description Event Start Time
Data Type Real
Range NaN, or Greater-than or equal-to 0.0
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

7.211 EVENTENDTIME[1..NUMPROFILES][1..NUMEVENTS]

Specific to Block(s) RampSoak


Description Event End Time
Data Type Real
Range NaN, or Greater-than or equal-to 0.0
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

- 1001 -
Chapter 7 - Exxxx Parameters

7.212 EVENTMSGRETRIED

Specific to Block(s) TCMI


Description Event Message Retried
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

7.213 EVENTMSGSENT

Specific to Block(s) TCMI


Description Event Message Sent
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 1002 -
Chapter 7 - Exxxx Parameters

7.214 EVENTNAKRECEIVED

Specific to Block(s) TCMI


Description Event negative acknowledgment received
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

7.215 EVENTQUEUESZ

Specific to Block(s) OPCUASRVUOC


Description Maximum Event Queue Sizes
Data Type UINT32
Range 0 to 4294967295
Default 10000
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

- 1003 -
Chapter 7 - Exxxx Parameters

7.216 EVENTRECEIVERDROPPED

Specific to Block(s) TCMI


Description Event receiver dropped
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

7.217 EVENTSEGID[1..NUMPROFILES][1..NUMEVENTS]

Specific to Block(s) RampSoak


Description Event Segment ID
Data Type Integer
Range 0 to 100
Default 1
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

7.218 EVENTSRC

Specific to Block(s) EIM


Description Event Source
Data Type String
Range
Default
Config Load
Active Loadable No

- 1004 -
Chapter 7 - Exxxx Parameters

Access Lock AppDevOnly


Residence SR
Related Parameters
Remarks

7.219 EVENTTHROTTLEREQ

Specific to Block(s) TCMI


Description Event throttling requested
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

7.220 EVERIFY[0..numChans-1]

Specific to Block(s) DOM (see Remarks)


Description Enable Output Verify
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks EVERIFY may be configured only on diagnostic modules.

- 1005 -
Chapter 7 - Exxxx Parameters

7.221 EVTOPT

Specific to SCM/RCM, Master Recipe (MR)


Block(s)
Description SCM/RCM Overall Event Option. Defines if event reporting to be supported for this
data point.
Data Type BOOLEAN
Range TRUE Overall SCM/RCM event journal option is
enabled.
FALSE Overall SCM/RCM event journal option is
disabled.
Default FALSE
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related EVTOPTSCMS
Parameters EVTOPTSCMTS
EVTOPTRECIPE
EVTOPTHIST
EVTOPTSTATECHG
EVTOPTMODEATR
EVTOPTRCMEXE
EVTOPTRESALLOC
EVTOPTEXEDTL
EVTOPTFORMULAPARAM
EVTOPTREPORTPARAMEVTOPTRCMINFOEVTOPTSTEPSEVTOPTSTEPC
Remarks This parameter enables SCM event reporting.

Specific to PMIO DICHANNEL


Block(s)
Description Reporting Option
Data Type ENUM
Range 0 NONE SOE is allowed
3 SOE Point notifies Sequence of
Events (SOE) Processing.
Default NONE
Config Yes
Load
Active No
Loadable

- 1006 -
Chapter 7 - Exxxx Parameters

Access Application Developer


Lock
Residence IOM
Related N/A
Parameters
Remarks If [EVTOPT] = EIP and the PV changes, higher-level control points are notified and a
“process special” on that data takes place. If [EVTOPT] = SOE and a PV change
occurs, Sequence Of Events Processing is notified. If [EVTOPT] = EIP_SOE, the
actions in both apply. [EVTOPT] configuration requires [DITYPE] = Status or
Latched. If [DITYPE] = Latched, [EVTOPT] cannot = EIPSOE or SOE. This parameter
is only displayed if the channel block is associated with a DISOE IOM and
[PNTFORM] = FULL.

Specific to Series C IO DICHANNEL


Block(s)
Description Reporting Option
Data Type ENUM
Range 0 NONE SOE is allowed
3 SOE Point notifies Sequence of
Events (SOE) Processing.
Default NONE
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence IOM
Related N/A
Parameters
Remarks If [EVTOPT] = SOE and a PV change occurs, Sequence Of Events Processing is
notified. If [EVTOPT] = NONE, the events will not be reported but still PV processing
is done. [EVTOPT] configuration requires [DITYPE] = Status or Latched. If [DITYPE]
= Latched, [EVTOPT] cannot = SOE. This parameter is displayed if the channel block
is associated with a DISOE IOM. When the EVTOPT = None (Default Value), DI
channels of DI-SOE IOM operating in SOE mode will not report SOE events and vice
versa. When the DI-SOE IOM is Normal (DI-24V mode) or the LowLatency mode,
this parameter value will be “None.” When you try to change he EVTOPT value to
SOE if the DIMODE parameter has either Normal/LowLatency, the following error
message is displayed. “EVTOPT incompatible with module's DIMODE”

Specific to UIO DICHANNEL


Block(s)
Description Reporting Option
Data Type ENUM
Range 0 NONE SOE is allowed
1 SOE Point notifies Sequence of
Events (SOE).
3 SOE Point notifies Sequence of
Events (SOE) Processing.
Default NONE

- 1007 -
Chapter 7 - Exxxx Parameters

Config No
Load
Active No
Loadable
Access Application Developer
Lock
Residence IOM
Related DEBOUNCE
Parameters
Remarks If EVTOPT is set as SOE and a PV change occurs, Sequence Of Events Processing is
notified. If [EVTOPT] = NONE, the events are not be reported but still PV processing
is done. EVTOPT configuration requires that the DITYPE is set as "Status "or
"Latched". If DITYPE is set as Latched, EVTOPT cannot be set as "SOE." This
parameter is displayed if the channel block is associated with a DISOE IOM. When
the EVTOPT is set as "None (Default Value)," DI channels of DI-SOE IOM operating
in SOE mode does not report SOE events and vice versa. When the DI-SOE IOM is
set as "Normal (DI-24V mode)" or "LowLatency mode," this parameter value is set as
"None." When you try to change the EVTOPT value to SOE if the DIMODE
parameter has either Normal/LowLatency, an error message is displayed. When
the EVTOPT = None (Default Value), DI channels of DI-SOE IOM operating in SOE
mode will not report SOE events and vice versa. When the DI-SOE IOM is Normal
(DI-24V mode) or the LowLatency mode, this parameter value will be “None”. When
the user tries to change the EvtOpt value to SOE when the DIMODE parameter has
either Normal/LowLatency, the following error shall be reported:

7.222 EVTOPTEXEDTL

Specific to RCM
Block(s)
Description Execution Details Event Option
Data Type Boolean
Range True Recipe Command, Active Phase Change, Mode Command, Mode Change,
Phase/Step Start, Phase/Step Complete, and Recipe Removal events
journal option are enabled.
False Recipe Command, Active Phase Change, Mode Command, Mode Change,
Phase/Step Start, Phase/Step Complete, and Recipe Removal events
journal option are disabled.
Default False
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related EVTOPT
Parameters
Remarks

- 1008 -
Chapter 7 - Exxxx Parameters

7.223 EVTOPTFORMULAPARAM

Specific to PHASE
Block(s)
Description Phase level formula parameter journaling option
Data Type Enumeration
Range 0 Off No events
1 On Always generate events
2 FollowContainer Follow the SCM/RCM
configuration
3 ONforTopLevel Report only when the
PHASE/DATA block is
contained by a top-level
recipe
4 ONforLowestLevel Report only when the
PHASE/DATA block is
contained by the RCM at
lowest level
Default FollowContainer
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks This parameter specifies if the events for formula parameters in a PHASE or DATA
block should be generated or not. Note: Off, On, FollowContainer, and
ONforTopLevel are supported in R310 and later releases. ONforLowestLevel will be
supported post R410.

7.224 EVTOPTHIST

Specific to Block(s) SCM


Description SCM History Parameter Event Option
Data Type Boolean
Range True SCM History Parameter event journal option is enabled.

False SCM History Parameter event journal option is


disabled.
Default False
Config Load Yes
Active Loadable No

- 1009 -
Chapter 7 - Exxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related Parameters EVTOPT
Remarks

7.225 EVTOPTMODEATR

Specific to Block(s) SCM, RCM


Description SCM History Parameter Event Option
Data Type Boolean
Range True Mode Attribute Change event journal option is enabled
False Mode Attribute Change event journal option is disabled.

Default True
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

7.226 EVTOPTRCMEXE

Specific to RCM
Block(s)
Description Recipe Execution Event Option
Data Type Boolean
Range True Batch Creation, Batch End, Execution Start, Execution Termination, and
State Change events journal option are enabled.
False Batch Creation, Batch End, Execution Start, Execution Termination, and
State Change events journal option are disabled.
Default True
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related EVTOPT
Parameters
Remarks

- 1010 -
Chapter 7 - Exxxx Parameters

7.227 EVTOPTRCMINFO

Specific to RCM
Block(s)
Description Recipe Information Event Option
Data Type Boolean
Range True Recipe identification information events of Version, Date Modified, and
Scale Factor events journal option are enabled.
False Recipe identification information events of Version, Date Modified, and
Scale Factor events journal option are disabled.
Default False
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related EVTOPT
Parameters
Remarks

7.228 EVTOPTRECIPE

Specific to Block(s) SCM


Description SCM Recipe Parameter Event Option
Data Type Boolean
Range True SCM Recipe Parameter event journal option is enabled.

False SCM Recipe Parameter event journal option is disabled.

Default False
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters EVTOPT
Remarks

- 1011 -
Chapter 7 - Exxxx Parameters

7.229 EVTOPTREPORTPARAM

Specific to PHASE
Block(s)
Description Phase level report parameter journaling option
Data Type Enumeration
Range 0 Off No events
1 On Always generate events
2 FollowContainer Follow the SCM/RCM
configuration
3 ONforTopLevel Report only when the
PHASE/DATA block is
contained by a top-level
recipe
4 ONforLowestLevel Report only when the
PHASE/DATA block is
contained by the RCM at
lowest level
Default FollowContainer
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks This parameter specifies if the events for report parameters in a PHASE or DATA
block should be generated or not. Note: Off, On, FollowContainer, and
ONforTopLevel are supported in R310 and later releases. ONforLowestLevel will be
supported post R410.

7.230 EVTOPTRESALLOC

Specific to RCM
Block(s)
Description Resource Allocation Event Option
Data Type Boolean
Range True Resource Allocation and Resource Release for the equipment modules
and UCM events journal option are enabled.
False Resource Allocation and Resource Release for the equipment modules
and UCM events journal option are disabled.
Default True
Config Load Yes
Active No

- 1012 -
Chapter 7 - Exxxx Parameters

Loadable
Access Lock Application Developer Only
Residence CEE
Related EVTOPT
Parameters
Remarks

7.231 EVTOPTSCMS

Specific to Block(s) SCM


Description SCM Start Event Option
Data Type Boolean
Range True SCM Start event journal option is enabled
False SCM Start event journal option is disabled
Default False
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters EVTOPT
Remarks

7.232 EVTOPTSCMTS

Specific to Block(s) SCM


Description SCM Terminal State Event Option
Data Type Boolean
Range True SCM Terminal State event journal option is enabled.
False SCM Terminal State event journal option is disabled.
Default False
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters EVTOPT
Remarks

- 1013 -
Chapter 7 - Exxxx Parameters

7.233 EVTOPTSTATECHG

Specific to Block(s) SCM, RCM


Description Event Option State Change
Data Type Boolean
Range True State Change event journal option is enabled
False State Change event journal option is disabled
Default True
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

7.234 EVTOPTSTEPC

Specific to Block(s) SCM, RCM


Description Step Complete Event Option
Data Type Boolean
Range True Step's Complete event journal option is enabled.
False Step's Complete event journal option is disabled.
Default False
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters EVTOPT
Remarks

7.235 EVTOPTSTEPS

Specific to Block(s) SCM, RCM


Description Step Start Event Option
Data Type Boolean
Range True Step's Start event journal option is enabled.
False Step's Start event journal option is disabled.
Default False

- 1014 -
Chapter 7 - Exxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters EVTOPT
Remarks

7.236 EWIREOFF[0..numChans-1]

Specific to Block(s) DIM (configurable only on Diagnostic modules)


Description Enable Wire-Off Diagnostic
Data Type Boolean
Range Wire-Off Diagnostic disabled (0) Wire-Off Diagnostic enabled (1)
Default Wire-Off Diagnostic disabled (0)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters WIREOFF[0..numChans-1]
Remarks

7.237 EXCMODEOPT

Specific to SCM
Block(s)
Description Execution Mode Option
Data Type Enumeration CSCOEXCMODEOPTION
Range None (0) Auto (1)
Default Auto (1)
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODE
Parameters
Remarks When EXCMODEOPT is Auto, the SCMMODE is automatically set to Auto
whenever the active handler changes.

- 1015 -
Chapter 7 - Exxxx Parameters

7.238 EXCPTALM.PR

Specific to CAB types


Block(s)
Description Exception Alarm.Priority. Sets the priority of the alarm notification if a CAB alarm
event is reported. Engineer can change this value at run time.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Enumeration ALPRIOR
Range NONE, JOURNAL, LOW, HIGH, URGENT
Default JOURNAL
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CABSTATE
Parameters
Remarks

7.239 EXCPTALM.SV

Specific to CAB types


Block(s)
Description Exception Alarm.Severity. Sets the severity of the alarm notification if a CAB alarm
event is reported. Engineer can change this value at run time.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type 16-Bit Integer
Range 0-15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CABSTATE
Parameters
Remarks

- 1016 -
Chapter 7 - Exxxx Parameters

7.240 EXCPTNLINENM

Specific to CAB types


Block(s)
Description Exception Line Number. When CABSTATE = Exception, AND the CAB block is built
using the Debug Configuration in Visual Studio - EXCPTNLINENM shows a string
with the name of the function that was executing when the exception occurred
and the source line number within that function.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type String
Range 255 characters
Default Blank
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CABSTATE, EXCPTNTYPE, EXCPTNMODULE
Parameters
Remarks If multiple functions have been called, they are shown in the order of the current
function, followed by the function that called the current function, then the next
function, and so on. The function names and the source file name are abbreviated
to only show the last 32 characters to allow for more call tree entries in the
EXCEPTNLINENM parameter. When CABSTATE = Exception, AND the CAB block is
built using the Release Configuration in Visual Studio - EXCPTNLINENM shows a
string with the name of the function that was executing when the exception
occurred. EXCPTNLINENM shows blank when CABSTATE <> Exception. CAB/C300
does not support the parameter EXCPTNLINENM. Attempts to read it from a loaded
CAB/C300 instance always return blank.

7.241 EXCPTNMODULE

Specific to CAB types


Block(s)
Description Exception Module. When CABSTATE = Exception, EXCPTNMODULE shows a string
with the name of the function that was executing when the exception occurred.
EXCPTNMODULE shows blank when CABSTATE <>Exception.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type String
Range 64 characters
Default Blank
Config Load No
Active No
Loadable

- 1017 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence CEE
Related CABSTATE, EXCPTNTYPE, EXCPTNMODULE
Parameters
Remarks CAB/C300 does not support the parameter EXCPTNMODULE. Attempts to read it
from a loaded CAB/C300 instance always return blank.

7.242 EXCPTNMSG

Specific to CAB types


Block(s)
Description Exception Message. When CABSTATE = Exception, EXCPTNMSG shows a string
with descriptive information. EXCPTNMSG shows blank when CABSTATE <>
Exception. For some exceptions, such as exceptions defined and thrown explicitly
within user code, EXCPTNMSG might be blank.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type String
Range 255 characters
Default Blank
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CABSTATE, EXCPTNTYPE
Parameters
Remarks

7.243 EXCPTNTYPE

Specific to CAB types


Block(s)
Description Exception Type. When CABSTATE = Exception, EXCPTNTYPE shows a string
indicating the type of exception that has been thrown. Shows blank when
CABSTATE <> Exception. The EXCPTNTYPE string has the following format:
“<namespace>.<exception type name>”
Modification Definition of this parameter cannot be modified.
of Definition
Data Type String
Range 64 characters
Default Blank
Config Load No

- 1018 -
Chapter 7 - Exxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CABSTATE, EXCPTNMSG
Parameters
Remarks For exceptions thrown by the CAB infrastructure, the namespace
is“Honeywell.CAB.” For exceptions explicitly thrown by user code, the namespace
is“CAB.” For exceptions thrown by the VB.NET language run-time, the namespace
starts with“System.” The exception type name itself varies. Some examples of
EXCPTNTYPE strings are shown below. User program has an integer-divide-by-
zero defect: “System.OverflowException”. User program has a stack overflow defect:
“System.StackOverflowException” User program has an array index out of Range
defect: “System.IndexOutOfRangeException” User program calls Abort():
“Honeywell.CAB.AbortException” User program defines an application exception
and throws it: “CAB.<user exception type name>”

- 1019 -
Chapter 7 - Exxxx Parameters

7.244 EXECCODE

- 1020 -
Chapter 7 - Exxxx Parameters

Specific to Handler, SCM, Step, Transition, ACT


Block(s)
Description Execution Code
Data Type Enumeration CSCOEXECCODE

- 1021 -
Chapter 7 - Exxxx Parameters

Range 0 None 116 SyntaxError

- 1022 -
Chapter 7 - Exxxx Parameters

1 ConfigError 117 ExprTooCmplx

- 1023 -
Chapter 7 - Exxxx Parameters

2 ExprEvalFail 118 NotEPcodeMem

- 1024 -
Chapter 7 - Exxxx Parameters

3 StoreFailed 119 NotEDataStak

- 1025 -
Chapter 7 - Exxxx Parameters

4 CommError 120 UnsuppFeatur

- 1026 -
Chapter 7 - Exxxx Parameters

5 StoreWarning 121 ExprTooLong

- 1027 -
Chapter 7 - Exxxx Parameters

6 InternalErr 122 DivideByZero

- 1028 -
Chapter 7 - Exxxx Parameters

7 CtrlReqErr 123 UnknownToken

- 1029 -
Chapter 7 - Exxxx Parameters

8 DataTypeErr 124 UnexpTokenOS

- 1030 -
Chapter 7 - Exxxx Parameters

9 StorePending 125 UnknownFunc

- 1031 -
Chapter 7 - Exxxx Parameters

10 ResourcLimit 126 UnexpOCExpr2

- 1032 -
Chapter 7 - Exxxx Parameters

11 EqmNotInProgram 127 UnexpOCExpr3

- 1033 -
Chapter 7 - Exxxx Parameters

12 EqmAcqError 128 ZeroArgument

- 1034 -
Chapter 7 - Exxxx Parameters

13 FormulaRangeError 129 UnexpToken


14 FormulaFetchNotComplete 130 InvalResult

15 ReportRangeError 131 InvalTokenTb


16 ReportFetchNotComplete 132 IntegerExp
17 EqmAcqRlsError 133 DoubleExp
18 RTableFull 134 MissedImpl
19 AcquiringResource 135 UnicodeConv
20 InvalidCommandvalue 136 ImplicitConv
21 ReleasingResource 137 DuplExprRem
22 DestIsNotADevice 138 ExtUse38
23 RemoteFetchPending 139 ExtUse39
24 EqmNotAvailable 140 ExtUse40
25 InstSelectChange 141 ExtUse41
26 EmptyAliasTableCell 142 ExtUse42
27 PendingHold 143 ExtUse43
28 PendingStop 144 ExtUse44
29 PendingAbort 145 ExtUse45
30 RequesterBusy 146 ExtUse46
31 PendingInterrupt 147 ExtUse47
32 UnsuitableEqmState 148 ExtUse48
33 ActNotAssociated 149 ExtUse49
34 HoldForReload 150 ExtUse50
35 OutOfMemory 151 UnSupConType
36 RCMACTOutOfSync 152 UnExpClsParn
37 ChildActCreateWarn 153 CantAssRVal
38 ChildActIsInvalid 154 UnExpArrOpen
39 ChildActCreateFail 155 ArrClsExpect
40 ChildActNotAvailable 156 ArrOpnExpect
41 ChildActCloning 157 ArrIndxError
42 Delayed 158 StringExpect
43 ConfMrAndNoAct 159 InvalidRefer
44 ChildHasActivity 160 TooManyConns
45 UnitInvalid 161 CantConvInpt
46 IntegrityError 162 FctExpParen
47 DelayBySystem 163 AsgnOpLimExc
101 Ok 164 AsgnOperMiss
102 UknownError 165 NullExprErr
103 ConstExprRem 166 StrRefNotSup

- 1035 -
Chapter 7 - Exxxx Parameters

104 LossOfPrecsn 167 CantFtchConn


105 UnexpctEnd 168 ComplexLHS
106 UnexpctComma 169 NullExprWarn
107 ColonWoQMark 170 ExtUse70
108 FctNotMltArg 171 RemoteFetchPending

109 ClosParenExp 172 RemoteFetchDisabled

110 OperandExp 173 DataNotEnabled


111 MissingArg 174 WCTUnknown
112 OperatorExp 175 DynPeerMemError
113 ColonExp
114 TypeMismatch
115 TypeNotSupp
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related EXECDESC, EXECSTS.
Parameters
Remarks This parameter works in conjunction with the EXECSTS and EXECDESC parameter
to provide information related to current errors in the system. When the activity is
executing, it reflects the execution code of the associated execution object
(SCM/RCM).

7.245 EXECCODE[1..8]

Specific to AuxCalc, Enhauxcalc, RegCalc


Block(s)
Description Execution Code
Data Type Enumeration AUXCALCEXECCODE
Range None (0) ConfigError (1) ExprEvalFail (2) StoreFailed (3) CommError (4)
StoreWarning (5) InternalErr (6) CtrlReqErr (7) DataTypeErr (8) StorePending (9)
ResourcLimit (10)
Default None (0)
Config Load No
Active No
Loadable

- 1036 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence CEE
Related EXECDESC[1..8], AVGICPNAKS.
Parameters
Remarks

7.246 EXECDESC

Specific to Handler, SCM, Step, Transition, AuxCalc, RegCalc


Block(s)
Description Execution Code Descriptor
Data Type String
Range Maximum of 39 characters
Default None
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related EXECCODE, EXECSTS.
Parameters
Remarks Possible error code values are as follows: 0 = OK 1 = Configuration Error 2 =
Expression Evaluation Failed 3 = Store Failed 4 = Communication Error 5 = Store
Warning 6 = Internal Error 7 = Control Request Error 8 = Data Type Error* 9 = Store
Pending 10 = Resource Limit 11 = Equipment not in Program 12 = Equipment
Acquisition Error 13 = Formula Value: Range exceeded 14 = Formula Value: Read
not complete 15 = Report Value: Range exceeded 16 = Report Value: Read not
complete 17 = Incomplete Resource Release 18 = Recipe Table Full 19 = Acquiring
Resource 20 = Invalid Command Value 21 = Releasing Resource 22 = Destination Is
Not a Device 23 = Remote Fetch Pending 24 = Actively Polling For Resource** 25 =
Instance Select Change 26 = Empty Alias Table Cell 27 = Pending Hold 28 = Pending
Stop 29 = Pending Abort 30 = Requester Busy 31 = Pending Interrupt 32 =
Unsuitable Equipment State 33 = Activity Not Associated 34 = Hold For Data Ready
35 = Controller Out Of Memory 36 = Activity Out Of Sync 37 = Child Activity Create
Warning 38 = Child Activity Is Invalid 39 = Child Activity Create Fail 40 = Wait Child
Activity Not Available 41 = Wait Control Recipe Creation 42 = Delayed 43 = Conf With
MR and No Activity 44 = Child Has Activity Already Hold for Data Ready *If Data Type
Error occurs on a step output where the type is not NULL ( OP[1..16].TYPE ), then
the most likely cause is an incorrectly configured output. Either change the output
type to NULL or change the expression. ** One potential cause of this could be that
a path is not open to the peer controller this block is trying to communicate with. On
the CEEFB Peer Communications Tab, verify the status to the controller you are
trying to connect to is healthy.

- 1037 -
Chapter 7 - Exxxx Parameters

Specific to ACT
Block(s)
Description The Descriptions of the current Execution Code.
Data Type String
Range Maximum of 39 characters
Default None
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related EXECSTS, EXECCODE
Parameters
Remarks This parameter works in conjunction with the ExecSts and ExecCode parameter. It
provides a brief Description of the enumeration stored in ExecCode. When the
activity is executing, it reflects the execution Description of the associated execution
object (SCM/RCM).

7.247 EXECDESC[1..8]

Specific to Block(s) Auxcalc, Enhauxcalc


Description Execution Code Descriptor
Data Type String
Range Maximum of 39 characters.
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EXECCODE[1..8], AVGICPNAKS.
Remarks

7.248 EXECIDOPT

Specific to Block(s) Auxcalc


Description Enable Execution ID Processing
Data Type Boolean
Range ON/OFF
Default OFF

- 1038 -
Chapter 7 - Exxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters MAXOWNERS
Remarks Must be loaded before MAXOWNERS

7.249 EXECSTATE

Specific to CM, IOM, SCM, UCM, RCM, MR, CR, PIOMB


Block(s)
Description Execution state of the block and its components.
Data Type Enumeration of EXECSTATE
Range Inactive (0) Active (1)
Default Inactive (0)
Config No
Load
Active No
Loadable
Access Lock l Supervisor
l ViewOnly (for SCM, RCM, MR, and CR)
Residence CEE
Related CEESTATE STATE (for SCM, RCM, MR, and CR)
Parameters
Remarks l For CMs: Only when EXECSTATE is Active and the CEESTATE is Run, are the
block and its component blocks executing.
l For IOMs: When EXECSTATE is Active, the IOM is executing regardless of
CEESTATE.
l For both CMs and IOMs: Block reload is only allowed when the block is NOT
executing. Note that EXECSTATE is always initialized to INACTIVE after load,
reload or snapshot restore, regardless of its previous state.
l For SCM, RCM, MR, and CR: EXECSTATE is computed as a result of STATE.
When the STATE parameter Range is 0 to 3, the EXECSTATE is set to Inactive.
For other STATE parameter Ranges, EXECSTATE is set to Active. Note: For CR,
only a value of ACTIVE is observable. This is not a defect. The parameter is
provided for compatibility with other block types only.

Specific to Block(s) UIO


Description Execution State
Data Type Enumeration
Range
Inactive 0

Active 1

- 1039 -
Chapter 7 - Exxxx Parameters

Default Idle
Config Load Yes
Active Loadable No
Access Lock Operator
Residence UIO
Related Parameters

Remarks Current state of the module.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Execution State
Data Type Enumeration
Range
0 INACTIVE

1 ACTIVE

Default Idle
Config Load Yes
Active
Loadable

Access Lock Operator


Residence IOM Block
Related
Parameters

Remarks Current state of the module.

7.250 EXECSTS

Specific to SCM, Handler, Step, Transition, RCM, AuxCalc, RegCalc, ACT


Block(s)
Description Execution Status-Provides the overall operation status of the TypeConvert function
block.
Data Type Enumeration CSCOEXECSTS
Range Ok (0) Bypass (1) Info (2) Warning (3) Fail (4) Error (5) OkPaused (6) BypassPaused
(7) InfoPaused (8) WarnPaused (9) FailPaused (10) ErrorPaused (11) Disabled(12)
NotTransition(13)
Default Ok (0)
Config No
Load
Active No
Loadable

- 1040 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence CEE
Related ExecCode, ExecDesc
Parameters
Remarks SCM component (Handler, Step, Transition) status parameters EXECSTS,
EXECCODE, EXECDESC are updated when they are in the SCM's current scope of
execution. The SCM's status parameters are representative of the status of the
components in the current scope. This parameter displays the current activity
status. When the activity is executing, it reflects the execution status of the
associated execution object (SCM/RCM/CR).

Specific to TypeConvert
Block(s)
Description Execution Status - Provides the overall operation status of the TypeConvert
function block.
Data Type Enumeration TCEXECSTS
Range OK (0) ClampWarning (1) BadInput (2) InBlkMissing (3)
Default Ok (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related
Parameters
Remarks l When EXECSTS is OK, it means that the fetching of inputs as well as the
conversion was completed without any error or clamping. When EXECSTS
value is other than OK, it means that either:
l the input could not be fetched, or
l the connection to the input is lost, or
l it is bad data, or
l the input is clamped during type conversion or
l there is no input connection made to any of the inputs of the PUSH
block.

l When EXECSTS is ClampWarning, it means that the function completed, but


with some limitation. This provides information on how successful the block
was in type conversion. After fetching good data, if the block had to clamp the
input during type conversion due to larger input provided than the output
chosen for conversion, EXECSTS will be CLAMPWARNING. The ClampWarning
is issued only when the input needs to be clamped to match the output type
configured for conversion. For example, if the input is configured as UINT16
and is configured to convert into UINT8 (output), then the value will be
clamped to UINT8 ranges.
l When EXECSTS is BadInput, it means that the input connection exists but the
data fetched is NaN (bad value). This is applicable only for float input types.
l When EXECSTS is InBlkMissing, it means that the block has detected an input
connection that does not exist.

- 1041 -
Chapter 7 - Exxxx Parameters

Specific to Block(s) PUSH


Description Execution Status - Provides the overall operation status of the PUSH
function block.
Data Type Enumeration
Range OK (0) CLAMPWARNING (1) BADINPUT (2) INBLKMISSING (3)
Default OK (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

7.251 EXECSTS[1..8]

Specific to Block(s) Auxcalc, Enhauxcalc


Description Execution Status
Data Type Enumeration AUXCALCEXECSTS
Range Ok (0) Bypass (1) Info (2) Warning (3) Fail (4) Error (5)
Default Ok (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

7.252 EXECSTSFAILTM

Specific to SCM, RCM


Block(s)
Description Execution Status Fail Filter Time - Specify a fail filter time that will suppress all
failures and errors for the amount of time entered in seconds.
Data Type Float64
Range 0.0 to 1000.0
Default 0
Config Yes
Load
Active No

- 1042 -
Chapter 7 - Exxxx Parameters

Loadable
Access Engineer
Lock
Residence CEE
Related
Parameters
Remarks The suppression will cause EXECSTS to be WARNING instead of FAIL or ERROR.
Also, the generation of FAIL alarms will be delayed for the configured time. If the
condition causing EXECSTS to be FAIL or ERROR goes away before expiration of the
filter time, the FAIL or ERROR value will be suppressed completely; otherwise, it will
be delayed. The purpose of the parameter is to avoid fake alarms or the premature
invocation of recipe and sequence exception handling by TotalPlantBatch or
RCM/SCM invoke transitions due to temporary communication problems. A non-
zero value may be required to integrate thrid-party systems (for example,.through
OPC ). Since the system cannot differentiate between“wrong errors” and legitimate
errors, responses to legimate errors are delayed as well. The underlying
assumption is that legimate errors will be present until resolved, whereas wrong
errors, will go away after a short time by themselves.

7.253 EXECTIME

Specific to ProfitCtl
Block(s)
Description Execution Time
Data Type INT32
Range NA
Default 0
Config No
Load
Active No
Loadable
Access Lock VIEWONLY
Residence NOLOAD
Related SYNCTIME, TOTALTIME
Parameters
Remarks This parameter represents time taken by profit controller algorithm to finish
execution. On ACE, there is no interruption when block start executing. On C300,
since the block runs in background processing it may happen that EXECTIME may
be more than what it took on ACE and it will include the time for which background
task was pre-empted.

- 1043 -
Chapter 7 - Exxxx Parameters

7.254 EXECUTEOPT

Specific to Phase
Block(s)
Description Execute Resource
Data Type Boolean
Range OFF (0) no execution control ON (1) Block specified by EQUIPNAME or
EQUIPNAMEREF will be started. This is the Default value and implies that the Phase
block executes and takes control over the equipment (that is, SCM/RCM) ONLY
when the SCM is in Idle/Terminal state. However, if the SCM is not in Idle/Terminal
state, then the phase block will wait until the SCM terminates. During this waiting
period, RCM will not influence the SCM's execution and vice versa. After the SCM
reaches the terminal state, the Phase will command the SCM to make it running.
Default ON (1)
Config Yes
Load
Active No
Loadable
Access AppDevOnly
Lock
Residence CEE
Related EQUIPNAME or EQUIPNAMEREF ,TERMSTATEOPT
Parameters
Remarks will be ignored (assumed to be OFF) if EQUIPNAME and EQUIPNAMEREF is NULL
Can only be ON if EQUIPNAME or EQUIPNAMEREF is not NULL and references an
SCM or RCM In any case phase block will give commands only to resources which
are currently acquired by the RCM.

7.255 EXECUTIONMODE

Specific to Block(s) SCM, RCM


Description Execution Mode
Data Type Enumeration
Range 0 ProcedureExecution
1 DeviceExecution
Default DeviceExecution
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks

- 1044 -
Chapter 7 - Exxxx Parameters

7.256 EXITOPT

Specific to CHGEXEC
Block(s)
Description Exit Option - Controls whether CHGEXEC causes parent CM to exit early under
conditions of no input change.
Data Type Enumeration
Range 0 EXITONEQU
5 CONTONEQU
Default EXITONEQU (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related DATA[1..32]ALTSYNCCMDALTSYNCCMD
Parameters
Remarks

7.257 EXPIRATIONDATE

Specific to Block(s) RCM


Description Expiration Date
Data Type Time
Range
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

- 1045 -
Chapter 7 - Exxxx Parameters

7.258 EXPR[1..8]

Specific to AuxCalc, Enhauxcalc, RegCalc


Block(s)
Description Calculator Expressions - Each may contain a user-specified logical, arithmetic or
conditional expression of up to eighty characters.
Data Type String
Range Length: up to 255 characters. (This will be unlimited in a future release.)
Default Null string
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

7.259 EXPRDESC[1...8]

Specific to AuxCalc, EnhAuxCalc, RegCalc, EnhRegCalc


Block(s)
Description This parameter is used for specifying a short Description for expressions in
Calculator blocks.
Data Type STRING (maximum length 64)
Range N/A
Default Blank
Config YES
Load
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related CONSTACCLOCK
Parameters
Remarks This parameter is used with the expression constant parameters (CONST[1..8]) for
providing a short Description for the expressions. This parameter must be set prior
to loading the Calculator blocks into the controller/server. This parameter is
available even when the CONSTENABLE is FALSE.

- 1046 -
Chapter 7 - Exxxx Parameters

7.260 EXPRPCODE[1..8]

Specific to Block(s) Auxcalc, RegCalc


Description Expression Pseudo-code
Data Type String
Range Maximum of 220 characters.
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks

7.261 External

Specific to Server
Block(s)
Description External Server - Indicates whether the server is external to the system.
Data Type Boolean
Range (0) Not an external
server
(1) Server is external to
system
Default 0
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence SCAN
Related
Parameters
Remarks Indicates if the server is DSA connected, and not part of the
system but may share segments of the model.

- 1047 -
Chapter 7 - Exxxx Parameters

7.262 EXTERRORSTATUS

Specific to EIP IO, E3, E3+, PF755 Drive.


Block(s)
Description Extended Error Status: When the connection between an EIP device and c300 fails,
this Parameter provides an Extended error code to identify the reason for failure.
Data Type STRING
Range -
Default 0x0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related GENERRORSTATUS
Parameters
Remarks l General Error Status: This will be one of the below:
1. EIMEIP_TAG_GEN_STS_GOOD (0x00)
2. EIMEIP_TAG_GEN_STS_BAD (0xFF) – Internal Error
3. General CIP Error Code returned by the CLx – this will found in the CIP Spec
Document
#define EIMEIP_TAG_GENSTS_BAD 0xFF #define EIMEIP_TAG_GENSTS_GOOD 0
l Extended Error Status: This will be one of the below:
1. EIMEIP_TAG_EXT_STS_GOOD (0x00)
2. 0x01 to 0xFF : Internal Error codes (see below list)
3. Extended CIP Error Code returned by the CLx – this will found in the CIP
Spec Document
kEIMSwitchoverExtSt = 1, kTagReadDataSizeZeroExtSt,
kTagReadTooLargeDataSizeExtSt, kEIMConnectionLostExtSt,
kTagReadSendFailedExtSt, kTagReadInvalidCfgStateExtSt, kTagReadStaleData

7.263 EXTERRORSTATUSN

Specific to Block(s) All EIP IOM/Devices/Drives and EIP Generic adapter.


Description Extended Error Status Number
Data Type INT32
Range N/A
Default 0.0
Config Load No
Active Loadable No

- 1048 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters GENERRORSTATUS, GENERRORSTATUS, EXTERRORSTATUS
Remarks

Specific to Block All EIP IOM/Devices/Drives and EIP Generic adapter 1738-AENT
(s)
Description Extended Error Status Number
Data Type INT32
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related GENERRORSTATUSN, GENERRORSTATUS, EXTERRORSTATUS,
Parameters IOCONNSTATUS, IOCONNEXTSTS
Remarks Extended Error Status: This will be one of the below:
1. 0(Good Status)
2. 1- 255 (Internal Error codes)
3. Extended CIP Error Code returned by the CLx – this will found in the CIP
Spec Document.

7.264 EXTGETRQUAVG

Specific to CEEC300, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description OPC Pull/Get Rate
Data Type Float64
Exposure Output
Range N/A
Default 0.0
Config No
Load
Active No
Loadable

- 1049 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence C300, ACE, SIM_C200, UOC, CN100
Related EXTSTRRQUMAX, STATSRESET.
Parameters
Remarks Since the characteristic time constant of the average is 1 minute, wait 2 to 3
minutes to be sure the averaging has completed. Click the Intialize Timing Stats
button on the Statistics tab of the CEE configuration form, to restart the calculation
from present in the Monitoring mode.

7.265 EXTGETRQUMAX

Specific to CEEC300, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description Max OPC Pull/Get Rate
Data Type Float64
Exposure Output
Range N/A
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, ACE, SIM_C200, UOC, CN100
Related EXTGETRQUAVG, STATSRESET.
Parameters
Remarks Click the Intialize Timing Stats button on the Statistics tab of the CEE configuration
form, to restart the calculation from present in the Monitoring mode.

7.266 EXTPATH

Specific to All EIP IOM/Devices/Drives/CNet IOs and EIP Generic adapter


Block(s)
Description Extended Path to Device (for EIP IOM/Devices/Drives)

Extended Path Prefix to Device (for EIP Generic adapter)


Data Type STRING
Range Limit: 64 characters
Default
Config Yes
Load
Active No
Loadable

- 1050 -
Chapter 7 - Exxxx Parameters

Access AppDevOnly
Lock
Residence CEE
Related ENBEXTPATH
Parameters
Remarks The parameter on the EIP IOMs/Devices that reside under the adapter is read only its
value is automatically updated. In this case EIP Generic adapter would present the
parameters ENBEXTPATH and EXTPATH. The user would configure ENBEXTPATH =
TRUE. EXTPATH parameter would encode the Extended path prefix (Extended path
without the final slot number for the target IOM). The EXTPATH parameter of the
Generic adapter would automatically be copied to corresponding parameter of the
IOMs underneath and the slot number would be automatically appended in the IOM
based on the slot number entered by the user in the IOM. Similarly, ENBEXTPATH
parameter of the Generic adapter would automatically be copied to the corresponding
parameter of the IOM.

7.267 EXTPOWERFAIL

Specific to UOC
Block(s)
Description External Power Failure
Data Type BOOLEAN
Range OFF, ON
Default OFF
Config Load No
Active No
Loadable
Access View Only
Lock
Residence CEE
Related PWRGOOD1, PWRGOOD2
Parameters
Remarks When all external power feeding the UOC’s power supply(s) is lost (as detected
through signals PWRGOOD1 and / or PWRGOOD2), this parameter is ON and the
“External Power Failure” soft failure is reported by the non-redundant or primary UOC.
Once external power is recovered, this parameter is OFF and the soft failure returns to
normal.

7.268 EXTRAPULSE

Specific to Block(s) PosProp, PidPosProp


Description Extra Pulse Time Option
Data Type Boolean
Range Off (0) On (1)

- 1051 -
Chapter 7 - Exxxx Parameters

Default Off (0)


Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

7.269 EXTRAPULSETM

Specific to Block PosProp, PidPosProp


(s)
Description Extra Pulse Time left over (in seconds)
Data Type Real
Range N/A
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the difference between unclamped value and clamped value of
RAISETIME or LOWERTIME.

7.270 EXTREF

Specific to OPC
Block(s)
Description External Reference - Specifies the Model Parameter in a SCM Alias table as
reference to either an external (OPC server block) or Float64 Data Types.
Data Type Unknown
Range N/A
Default N/A
Config Load No
Active No
Loadable

- 1052 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence ER
Related EXTREFSTRUCT
Parameters
Remarks

7.271 EXTREFSTRUCT

Specific to OPC
Block(s)
Description External Reference Structure - Specifies the Model Parameter in a SCM Alias table
as reference to either an external (OPC server block) or external reference
structure (ExtRefStruct) type.
Data Type ExtRefStruct
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ER
Related EXTREF
Parameters
Remarks

7.272 EXTSTRRQUAVG

Specific to CEEC300, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description External Store Requests Average - Indicates the average number of completed
Store requests to all external servers, such as an OPC server, from this CEE per
second.
Data Type Float64
Exposure Output
Range N/A
Default 0.0
Config No
Load
Active No
Loadable

- 1053 -
Chapter 7 - Exxxx Parameters

Access Lock ViewOnly


Residence C300, ACE, SIM_C200, UOC, CN100
Related EXTSTRRQUMAX, STATSRESET.
Parameters
Remarks Since the charateristic time constant of the average is 1 minute, wait 2 to 3 minutes
to be sure the averaging has completed. Click the Intialize Timing Stats button on
the Statistics tab of the CEE configuration form, to restart the calculation from
present in the Monitoring mode.

7.273 EXTSTRRQUMAX

Specific to CEEC300, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description Max OPC Store Rate
Data Type Float64
Exposure Output
Range N/A
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, ACE, SIM_C200, UOC, CN100
Related EXTSTRRQUAVG, STATSRESET
Parameters
Remarks Click the Intialize Timing Stats button on the Statistics tab of the CEE configuration
form, to restart the calculation from present in the Monitoring mode.

7.274 EZCROSS[0..numChans-1]

Specific to Block DOM


(s)
Description Enable Loss of Power
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No

- 1054 -
Chapter 7 - Exxxx Parameters

Access Lock Application Developer


Residence CEE
Related NOFIELDPWR[0..numChans-1]
Parameters
Remarks EZCROSS is only visible, configured, and loaded on the 8-channel 120V AC
diagnostic module.

- 1055 -
CHAPTER

8 FXXXX PARAMETERS

8.1 F 1060
8.2 FACTDATAERR 1060
8.3 FAILALM.FL 1061
8.4 FAILALM.PR 1062
8.5 FAILALM.SV 1062
8.6 FAILOPT 1062
8.7 FAILSTATE[0..numChans-1] 1063

8.8 FANFAULTSF 1064


8.9 FANOUT 1064
8.10 FANSTS 1065
8.11 FAULTACT[0..numChans-1] 1065
8.12 FAULTDELAY 1066
8.13 FAULTENB[ ] 1066
8.14 FAULTENB[0..7] 1067
8.15 FAULTMODE[0..numChans-1] 1067
8.16 FAULTOPT 1068
8.17 FAULTOPT_AO_C 1070
8.18 FAULTOPT_DO_C 1071
8.19 FAULTRESET 1072
8.20 FAULTST 1073
8.21 FAULTSTATE[0..numChans-1] 1073
8.22 FAULTVALUE 1074
8.23 FAULTVALUE[0..numChans-1] 1075
8.24 FAULTVALUE[0..numChans-1] 1076
8.25 FAULTVALUE[0..numChans-1] 1076
8.26 FAULTVALUE[0..numChans-1] 1077
8.27 FAULTVALUE[0..7] 1077
8.28 FAULTVALUE_AO_C 1078
8.29 FBCONN1 1079
8.30 FBCONN2 1079
8.31 FBCONN3 1080
8.32 FBCONN4 1080

- 1056 -
Chapter 8 - Fxxxx Parameters

8.33 FBCONN5 1081


8.34 FBCONN6 1081
8.35 FBCONN7 1082
8.36 FBCONN8 1082
8.37 FBCONN9 1083
8.38 FBCONN10 1083
8.39 FBORSTS 1084
8.40 FBTYPE 1084
8.41 FCE_OUTPUT[1..24] 1085
8.42 FCE_OUTPUT[1..200] 1085
8.43 FEEDFAILED[1..24] 1086
8.44 FEEDFAILED[1..200] 1086
8.45 FEEDOVERRIDE[1..24] 1087
8.46 FEEDOVERRIDE[1..200] 1087

8.47 FEEDTYPE[1..24] 1088


8.48 FEEDTYPE[1..200] 1088
8.49 FEEDWEIGHT[1..24] 1089
8.50 FEEDWEIGHT[1..200] 1089
8.51 FETCHMODE 1090
8.52 FF 1090
8.53 FFCONN 1091
8.54 FFOPT 1091
8.55 FFPERIOD 1092
8.56 FFSTS 1092
8.57 FILEPOSITION 1093
8.58 FILTERHDR[0..numChans-1] 1093
8.59 FILTEROFF[0..numChans / 8] 1093
8.60 FILTEROFF [0..NUMCHANNELS-1] 1094
8.61 FILTERON [0..NUMCHANNELS-1] 1095
8.62 FILTERON[0..numChans / 8] 1096
8.63 FILTERTIME 1096
8.64 FINALCMDPARAM 1096
8.65 FINALCMDPC 1097
8.66 FINALCMDVAL 1098
8.67 FIRSTOUTACTED 1099
8.68 FIRSTOUTALM.FL 1099
8.69 FIRSTOUTALM.PR 1099
8.70 FIRSTOUTALM.SV 1100
8.71 FIRSTOUTINPUT 1100

- 1057 -
Chapter 8 - Fxxxx Parameters

8.72 FIRSTUPACTED 1101


8.73 FLAG 1101
8.74 FLOAT_VALUE 1102
8.75 FLOAT64PARAM 1102
8.76 FLOAT64VAL[0…40] 1102
8.77 FLSHSTAT 1103
8.78 FLSHSTAT[1..32] 1103
8.79 FLTIP 1104
8.80 FMWREV1 [1...15] through FMWREV8 [1...15] 1104
8.81 FONTSTYLE 1105
8.82 FORCEMODEATTR 1105
8.83 FORCEREADREQ 1106
8.84 FORCERESTART 1106
8.85 FORCETOINACTIVE 1107

8.86 FPGAFAIL 1107


8.87 FPINDICATOR[1..4] 1108
8.88 FPINDRAW[1..4] 1109
8.89 FPVALUE[1..4] 1109
8.90 FPVALUERAW[1..4] 1109
8.91 FRC 1110
8.92 FRCPERM 1110
8.93 FRCREQ 1111
8.94 FRCSEL 1111
8.95 FREEARRPARAMWRITES 1112
8.96 FREEARRWRITES 1112
8.97 FREEFL 1112
8.98 FREEMEM 1113
8.99 FREEMEMINK 1113
8.100 FREENONARRPARAMWRITES 1114
8.101 FREESCALARTAGREADS 1114
8.102 FREENONARRWRITES 1115
8.103 FREEUDTTAGREADS 1115
8.104 FREEUDTTAGREAD 1116
8.105 FREESCATAGREAD 1116
8.106 FREEZETIME 1117
8.107 FREQ5060 1117
8.108 FREQ6050 1117
8.109 FREQPERIOD 1118
8.110 FREQPERIOD[0..7] 1119

- 1058 -
Chapter 8 - Fxxxx Parameters

8.111 FSTFLSHSPD 1119


8.112 FSTS 1120
8.113 FTA1TYPE 1120
8.114 FTA2TYPE 1121
8.115 FTAAOVRNFL 1121
8.116 FTAASTS 1122
8.117 FTABOVRNFL 1122
8.118 FTABSTS 1123
8.119 FTACONNA 1123
8.120 FTACONNB 1124
8.121 FTAPRESA 1124
8.122 FTAPRESB 1125
8.123 FTAREVERSEDA 1125
8.124 FTAREVERSEDB 1126

8.125 FTEABLOCKRATE 1126


8.126 FTEARXRATE 1126
8.127 FTEATXRATE 1127
8.128 FTEBBLOCKRATE 1127
8.129 FTEBRXRATE 1128
8.130 FTEBTXRATE 1128
8.131 FTEBBLOCK 1129
8.132 FTEIECSUBNETCONF 1129
8.133 FTEMARTADDRCOUNT 1130
8.134 FTEMARTAVGDEPTH 1130
8.135 FTEMARTCOLLCOUNT 1131
8.136 FTEMARTMAXDEPTH 1131
8.137 FTENETWORKERR 1132
8.138 FTEPARTNERNOTVISIBLE 1132
8.139 FTERECEIVEERRORS 1133
8.140 FTETRANSMITERRORS 1133
8.141 FULLFL 1134
8.142 FULLITEMNAME 1134
8.143 FUNCTIONNAME.DESC 1135
8.144 FUNCTIONNAME.TYPE 1135
8.145 FUNCTIONNAME.FCN 1136
8.146 FWINVALIDA 1136
8.147 FWINVALIDB 1137
8.148 FWREVISION 1137

- 1059 -
Chapter 8 - Fxxxx Parameters

8.1 F

Specific to FLOWCOMP
Block(s)
Description Flow Input - The value of the uncompensated flow input. This is a square-rooted,
differential pressure input.
Data Type Real
Range
Default NaN
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence C200, C300, ACE
Related
Parameters
Remarks

8.2 FACTDATAERR

Specific to C300, PGM, FIM4, EHPM.


Block(s)
Description Factory Data Checksum Error
Data Type Boolean
Range N/A
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, C200, ACE, SIM_C200, FIM, PGM, EHPM
Related
Parameters
Remarks Factory data checksum must be zero. If Checksum of Factory data is not zero, then
this flag is set to indicate the Softfail condition and a diagnostic alarm is issued.

Specific to Block EIM


(s)
Description Factory Data Checksum Error
Data Type Boolean
Range N/A
Default Off
Config Load No

- 1060 -
Chapter 8 - Fxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks True if the factory data in the device EEPROM is missing or invalid for the
currently loaded firmware.

Specific to Block UOC


(s)
Description Factory Data Error
Data Type Boolean
Range N/A
Default Off
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Soft failure condition. Factory data is invalid or corrupted. Hardware should
be replaced.

8.3 FAILALM.FL

Specific to Block(s) SCM


Description Sequential Control Module (SCM) Fail Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EXECSTS
Remarks FAILALM.FL is On when SCM EXECSTS is Fail

- 1061 -
Chapter 8 - Fxxxx Parameters

8.4 FAILALM.PR

Specific to Block(s) SCM


Description Sequential Control Module (SCM) Fail Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters FAILALM.FL, FAILALM.PR
Remarks

8.5 FAILALM.SV

Specific to Block(s) SCM


Description Sequential Control Module (SCM) Fail Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters FAILALM.FL, FAILALM.PR
Remarks

8.6 FAILOPT

Specific to AO8, AO16, AO16HART, DO16, D032


Block(s)
Description Failure Option. defines the state which an AO or DO IOM goes into if the IOM,
IOLINK, or C300 fails.
Data Type Enumeration
Range HOLD (0): Hold output at last good value.
UNPOWER Output goes to unpowered value.
(1):
Default UNPOWER (1)

- 1062 -
Chapter 8 - Fxxxx Parameters

Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related N/A
Parameters
Remarks If the IOM failure is due to power loss, the outputs go to the unpowered value
regardless of the FAILOPT value. When power is restored to the IOM, outputs are
reset regardless of the FAILOPT value. For the HART Analog Output IOM, the
unpowered value is approximately 0.5mA.

Specific to AOCHANNEL, HAOCHANNEL, DOCHANNEL


Block(s)
Description Failure Option. defines the state which an AO or DO IOM goes into if the IOM,
IOLINK, or C300 fails.
Data Type Enumeration
Range HOLD (0): Hold output at last good value.
UNPOWER (1): Output goes to unpowered value.
Default UNPOWER (1)
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related N/A
Parameters
Remarks If the IOM failure is due to power loss, the outputs go to the unpowered value
regardless of the FAILOPT value. When power is restored to the IOM, outputs are
reset regardless of the FAILOPT value. For the HART Analog Output IOM, the
unpowered value is approximately 0.5mA.

8.7 FAILSTATE[0..numChans-1]

Specific to DOM
Block(s)
Description Shed Mode - Shed to Hold enabler.
Data Type Boolean
Range Use Safe State (0) Hold Last Output State (1)
Default Use Safe State (0)
Config Yes
Load
Active No
Loadable

- 1063 -
Chapter 8 - Fxxxx Parameters

Access Lock Application Developer


Residence CEE
Related SAFESTATE[0..numChans-1]
Parameters
Remarks In the event of controller failure or loss of communication between the controller
and the IOM, if enabled, the output will hold the last state processed. If disabled, the
output will assume the Safe State. Note that if the IOM device itself fails, the output
value is not deterministic.

8.8 FANFAULTSF

Specific to Block(s) ELCN_BRG, ELCN_NODE

Description Fan Fault Condition

Data Type Boolean

Range ON, OFF

Default OFF

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG, ELCN_NODE

Related Parameters SOFTFAIL

Remarks UEA cooling fan is not operational

8.9 FANOUT

Specific to HRBALG_REG block


Blocks
Description FANOUT FB reference
Data Type BLOCKID
Range Not applicable

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the FANOUT block in the emulation CM, if the
emulation CM contains a FANOUT block.

- 1064 -
Chapter 8 - Fxxxx Parameters

8.10 FANSTS

Specific to Block(s) TCMI


Description Fan Status
Data Type ENUM
Range N/A
Default OK
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

8.11 FAULTACT[0..numChans-1]

Specific to EIP Analog Output Modules


Block(s)
Description Fault Action — Represents the action that the module should take in case the
communication between the controller and the IOM is broken for some reason.
Data Type ENUM
Range l 0 : Hold Last State
l 1 : Clamp Low
l 2 : Clamp High
l 3 : Fault Value
Default Hold Last State
Config Load Yes
Active No
Loadable

- 1065 -
Chapter 8 - Fxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related None
Parameters
Remarks l Hold Last State : OP is held at the last known value before communication
loss.
l Clamp Low : OP is set to the configured OPFINALLORANGE
l Clamp High : OP is set to the configured OPFINALHIRANGE
l Fault Value : OP is set to configured Fault Value

ATTENTION For all analog output channels of the 1738_OE2CM12 and


1738_OE4CM12 Armor point output modules, when the channel range is
configured as 4-20 mA and the value of FAULTACT= Clamp Low, then if
the communication breaks between C300 and the Armor point IO
module, the channel value changes to 0.

8.12 FAULTDELAY

Specific to TC-POB041
Block(s)
Description Fault Detection Delay Time
Data Type Enumeration
Range 11 ms 12 ms 14 ms 18 ms 26 ms 42 ms
Default 11 ms
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related FAULTENB[ ], LATCHENB.
Parameters
Remarks Determines the length of time over which a fault must be continuously present
before the device will recognize the fault and signal it. Applies globally to all
channels on the device.

8.13 FAULTENB[ ]

Specific to TC-POB041
Block(s)
Description Enable Fault Detection
Data Type Boolean
Range Off(0) On(1)

- 1066 -
Chapter 8 - Fxxxx Parameters

Default Off(0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related FAULTRESETLATCHENB
Parameters
Remarks Enables detection of wire-off and short-circuit conditions. Applies to individual
channel. There are four channels associated with this device.

8.14 FAULTENB[0..7]

Specific to
AOM - TC-OAV081(1756-OF8)
Block(s)
Description Enable Wire Off Alarm Reporting
Data Type Boolean
Range OFF (0) ON (1)
Default OFF (0)
Config
Yes
Load
Access Lock Operator
Active
No
Loadable
Residence CEE
Related
WIREOFF[0..7]WIREOFF[0..7]
Parameters
This parameter enables open-wire detection reporting for a particular output
channel, which is configured for 4-20 mA current operation, and experiences an
Remarks
open-wire while the output is sourcing more than 0.1 mA current. This parameter
can be changed online.

8.15 FAULTMODE[0..numChans-1]

Specific to 1738-OA2M12AC3, 1738-OB2EPM12, and 1738-OB8EM12


Block(s)
Description Fault Mode — It is a configuration parameter, which determines the behavior of
each output when communication with the controller fails. The available values for
each channel are Off , On, or Hold.
Data Type ENUM
Range l 0 : Off
l 1 : On
l 2 : Hold

- 1067 -
Chapter 8 - Fxxxx Parameters

Default Off
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks l OFF —The output value takes the value, OFF, when communication with the
controller fails, irrespective of the value being driven prior to communication
loss.
l ON —The output value takes the value, ON, when communication with the
controller fails, irrespective of the value being driven prior to communication
loss.
l HOLD — The output value is held at a value that was being driven prior to
communication loss.

8.16 FAULTOPT

Specific to AOCHANNEL (Series C I/O)


Block(s)
Description Fault Option
Data Type Enumeration
Range 0 Hold Hold output at last good
value.
1 Unpower Output goes to un-powered
value.
3 UseFaultValue Output goes to the value
specified by the
FAULTVALUE parameter.
4 UseFaultValueAll Output goes to the value
specified by the
FAULTVALUE parameter.
Default Unpower
Config Load Yes
Active No
Loadable

- 1068 -
Chapter 8 - Fxxxx Parameters

Access Lock EngineerAppDev


Residence IOM
Related FAULTVALUE
Parameters
Remarks This parameter provides the ability to define the state which an AO channel goes
into, in the case of:
l A timeout of the upstream connection or
l An Output Path Diagnostic fault detection

NOTE If the IOM failure is due to power loss, outputs go un-powered


regardless of the FAULTOPT value.

Special behavior: When the option “UseFaultValueAll” is configured, the module will
apply the value specified in FAULTVALUE as follows:
l In case of Upstream Timeout
The range applied remains: -6.9 to 106.9 (0.0 mA, 2.9 mA through 106.9 mA)
l In case of Output Path Fault
The range is limited to -6.8 to 106.9 (2.9 mA to 21.1 mA) The rationale is since -6.9
represents 0.0 mA, it is avoided, as this will cause the diagnostic to RTN even when
the fault is still present.

Specific to DOCHANNEL (Series C I/O)


Block(s)
Description Fault Option
Data Type Enumeration
Range 0 Hold Hold output at last good value.
1 Unpower Output goes to un-powered
value.
2 Power Output goes to the powered value

3 UseFaultValue Output goes to the value


specified by the FAULTVALUE
parameter.
Default Unpower
Config Yes
Load
Active No
Loadable
Access EnginnerAppDev
Lock
Residence IOM
Related FAULTOPT, FAULTVALUE
Parameters
Remarks This parameter determines the behavior of an individual output value when a fault
condition exists. When DOTYPE is SO, the allowed values for FAULTOPT are: Hold,
Unpower and Power. When DOTYPE is ONPULSE or OFFPULSE, the allowed values
for FAULTOPT are: Hold and Unpower. When DOTYPE is PWM, the allowed values
for FAULTOPT are: Hold, Unpower and UseFaultValue. While the FAULTOPT
settings Power and Unpower always set the output to 1 or 0 regardless of the
DOTYPE, the FAULTOPT settings Hold and UseFaultValue produce different results
depending upon the DOTYPE. The table below provides the different results.

- 1069 -
Chapter 8 - Fxxxx Parameters

DOTYPE FAULTOPT
Hold UseFaultValue

SO Hold at the current value Not permitted


ONPULSE Finish pulse and hold output at Not permitted
a 0.
OFFPULSE Finish pulse and hold output at Not permitted
a 1.
PWM Continue PWM cycle at current Finish current
OP value. PWM cycle at
current OP
value. Future
PWM cycles are
at the
FAULTVALUE
OP.
If the IOM failure is due to power loss, outputs go un-powered regardless of the
FAULTOPT value.

8.17 FAULTOPT_AO_C

Specific to UIO
Block(s)

Description Fault Option


Data Type ENUM
Range
0 Unpower Output goes to un-powered value.

1 UseFaultvalue Output goes to value specificed by FAULTVALUE parameter.

3 Hold Hold output at last good value.

Default Unpower
Config Yes
Load

Active No
Loadable

Access EngineerAppDev
Lock

Residence UIO
Related FAULTVALUE
Parameters

Remarks This parameter defines the state which an AO channel goes into when the IOM stops
communicating with the device that is responsible for sending updates to it.
If the IOM failure is due to power loss, outputs go un-powered regardless of the
FAULTOPT value.

- 1070 -
Chapter 8 - Fxxxx Parameters

Specific to UIO, AO04, AO08


Block(s)

Description Fault Option


Data Type ENUM
Range
0 Unpower Output goes to un-powered value.

1 UseFaultvalue Output goes to value specificed by FAULTVALUE parameter.

2 Hold Hold output at last good value.

Default Unpower
Config Yes
Load

Active
Loadable

Access EngineerAppDev
Lock

Residence IOM Block


Related
Parameters

Remarks This parameter defines the state which an AO channel goes into when the IOM stops
communicating with the device that is responsible for sending updates to it.
If the IOM failure is due to power loss, outputs go un-powered regardless of the
FAULTOPT value.
This parameter is not available for AO04 and AO08. The existing behavior of these 2
modules does not make it possible for the controller to collect the echo back values prior
to writing the outputs. The only available option is the default value of Unpowered.

8.18 FAULTOPT_DO_C

Specific to UIO
Block(s)

Description Fault Option


Data Type ENUM
Range
0 Un-power Output goes to un-powered value.

1 Power Output goes to the powered value.

2 Hold Hold output at last good value.

Default Unpowered
Config Yes
Load

Active No
Loadable

- 1071 -
Chapter 8 - Fxxxx Parameters

Access EngineerAppDev
Lock

Residence UIO
Related None
Parameters

Remarks This parameter determines the behavior of an individual output value when a fault
condition exists. If the IOM failure is due to power loss, outputs go un-powered regardless
of the FAULTOPT value.

Specific to UIO, DO32-24VDC, DO08-VAC, DO08-RELAY


Block(s)

Description Fault Option


Data Type ENUM
Range
0 Un-power Output goes to un-powered value.

1 Power Output goes to the powered value.

2 Hold Hold output at last good value.

Default Unpowered
Config Yes
Load

Active
Loadable

Access EngineerAppDev
Lock

Residence IOM Block


Related
Parameters

Remarks This parameter determines the behavior of an individual output value when a fault
condition exists. If the IOM failure is due to power loss, outputs go un-powered regardless
of the FAULTOPT value.
This parameter is not available for DO32-24VDC and DO08-VAC. The existing behavior of
these 2 modules does not make it possible for the controller to collect the echo back
values prior to writing the outputs. The only available option is the default value of
Unpowered.

8.19 FAULTRESET

Specific to TC-POB041
Block(s)
Description Fault Reset
Data Type Boolean
Range Off(0) On(1)
Default Off(0)
Config Yes
Load

- 1072 -
Chapter 8 - Fxxxx Parameters

Active No
Loadable
Access Lock Engineer
Residence CEE
Related FAULTENB[ ]LATCHENB
Parameters
Remarks If LATCHENB has been asserted so that detected faults are latched, this parameter
is used to allow generation of a Latched Fault reset pulse to the device. The
engineer clicks on a check box. The function block generates the appropriate pulse
and clears the checkbox when the reset operation is complete. Applies globally to all
channels on the device.

8.20 FAULTST

Specific to Series CSeries C AOCHANNEL and Series C DOCHANNEL


Block(s)
Description Fault State
Data Type Enumeration
Range 0 Normal The channel is in its
normal state.
1 Faulted The channel is in a
faulted state.
Default Normal
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter indicates the overall state
(faulted or normal) of this channel.

8.21 FAULTSTATE[0..numChans-1]

Specific to 1738-OA2M12AC3, 1738-OB2EPM12, and 1738-OB8EM12


Block(s)
Description Fault State — Based on the configuration of FAULTMODE, FAULTSTATE and
FAULTVALUE parameters should be appropriately configured to indicate the same,
as these parameters are a part of the configuration assembly that will be sent to
the module.
Data Type Boolean
Range l 0 : OFF
l 1 : ON

- 1073 -
Chapter 8 - Fxxxx Parameters

Default OFF
Config No
Load
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related FAULTMODE[0..numChans-1]
Parameters
Remarks l FAULTMODE = OFF , FAULTSTATE = 0 FAULTVALUE = 0
l FAULTMODE = ON , FAULTSTATE = 0 FAULTVALUE = 1
l FAULTMODE = HOLD , FAULTSTATE = 1 FAULTVALUE = 0
l FAULTMODE = HOLD , FAULTSTATE = 1 FAULTVALUE = 1

8.22 FAULTVALUE

Specific to AOCHANNEL (Series C I/O)


Block(s)
Description Fault Value
Data Type FLOAT32
Range -6.9 to 106.9
Default -6.9
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence IOM
Related FAULTOPT
Parameters
Remarks This parameter defines the value which a channel is set to when the user has
selected UseFaultValue or UseFaultValueAll for the FAULTOPT and the IOM stops
communicating withthe device that is responsible for sending updates to it. For
additional details, see the Special Behavior Note for FAULTOPT parameter (for
Series C AOCHANNEL). The default setting for FAULTVALUE will result in the
channel behaving exactly as if Unpower was selected for FAULTOPT.

Specific to DOCHANNEL (Series C I/O)


Block(s)
Description Fault Value
Data Type FLOAT32
Range 0.0 to 100.0
Default 0.0
Config Yes
Load

- 1074 -
Chapter 8 - Fxxxx Parameters

Active No
Loadable
Access Lock EngineerAppDev
Residence IOM
Related FAULTOPT, DOTYPE
Parameters
Remarks This parameter defines the value which a channel is set to when the user has
selected UseFaultValue for the FAULTOPT and the IOM stops communicating with
the device that is responsible for sending updates to it. The default setting for
FAULTVALUE will result in the channel behaving exactly as if Unpower was selected
for FAULTOPT. This parameter is only valid when its DOTYPE is set to PWM.

8.23 FAULTVALUE[0..numChans-1]

Specific to AOM
Block(s)
Description Safe Value (in percent) - Specifies a safe output value to be assumed in the event
of a controller failure or loss of communication between the controller and IOM.
Note that SHEDMODE must be enabled in order to configure and use the
FAULTVALUE. Note that if the IOM device itself fails, the output value is not
deterministic.
Data Type 64-Bit Real Number
Range N/A
Default 50 for modules operating in voltage mode only. -25 for modules operating in
current mode (or current and voltage modes).
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related SAFESTATE[0..numChans-1] (for DOM)
Parameters
Remarks -25 is the recommended Safe Value for current mode. 50 is the recommended Safe
Value for voltage mode. Note that the non-isolated (high-density) AOM allows
channels to be configured for use in either voltage or current mode. Since only one
default value can be specified (-25), it is recommended that the user change the
value to 50 (or other safe value) if using voltage mode.

- 1075 -
Chapter 8 - Fxxxx Parameters

8.24 FAULTVALUE[0..numChans-1]

Specific to EtherNet/IP Analog Output Modules


Block(s)
Description Fault value (count)— This parameter is allowed to be configured, only when the
Fault Action parameter is configured to Fault Value. This value must be entered as
a count and not as a percentage.
Data Type INT32
Range

Default 0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related FAULTACT[0..numChans-1]
Parameters
Remarks It is indexed by channel number.

8.25 FAULTVALUE[0..numChans-1]

Specific to 1738-OA2M12AC3, 1738-OB2EPM12, and 1738-OB8EM12


Block(s)
Description Fault Value — Based on the configuration of FAULTMODE, FAULTSTATE and
FAULTVALUE parameters should be appropriately configured to indicate the same,
as these parameters are a part of the configuration assembly that will be sent to the
module.
Data Type Boolean
Range l 0 : OFF
l 1 : ON
Default OFF
Config No
Load
Active No
Loadable

- 1076 -
Chapter 8 - Fxxxx Parameters

Access Lock AppDevOnly


Residence SR
Related FAULTMODE[0..numChans-1]
Parameters
Remarks l FAULTMODE = OFF , FAULTSTATE = 0 FAULTVALUE = 0
l FAULTMODE = ON , FAULTSTATE = 0 FAULTVALUE = 1
l FAULTMODE = HOLD , FAULTSTATE = 1 FAULTVALUE = 0
l FAULTMODE = HOLD , FAULTSTATE = 1 FAULTVALUE = 1

8.26 FAULTVALUE[0..numChans-1]

Specific to EtherNet/IP Analog Output Modules


Block(s)
Description Fault value (count)— This parameter is allowed to be configured, only when the
Fault Action parameter is configured to Fault Value. This value must be entered as
a count and not as a percentage.
Data Type INT32
Range

Default 0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related FAULTACT[0..numChans-1]
Parameters
Remarks It is indexed by channel number.

8.27 FAULTVALUE[0..7]

Specific to Chassis HART AO IOM


Block(s)
Description Safe Value - Specifies a safe output value (in %) to be assumed in the event of a
controller failure or loss of communication between the controller and IOM.
FAULTVALUE can be configured and used only when SHEDMODE is enabled.
Data Type Float64
Range
Default 50 for devices operating in voltage mode -25 for devices operating in current mode
(or current and voltage modes).
Config Yes
Load

- 1077 -
Chapter 8 - Fxxxx Parameters

Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related SHEDMODE[0..7]
Parameters
Remarks Note that SHEDMODE must be enabled in order to configure and use the
FAULTVALUE. The default value is NaN. If no value is specified for the
FAULTVALUE, then NaN is replaced by following value while downloading the
configuration to the IOM. -25 is the recommended Safe Value for current mode. 50
is the recommended Safe Value for voltage mode. Note that if the IOM device fails,
the output value is not deterministic.

8.28 FAULTVALUE_AO_C

Specific to UIO
Block(s)

Description Fault Value


Data Type FLOAT32
Range -6.9 to 106.9
Default -6.9
Config Yes
Load

Active No
Loadable

Access EngineerAppDev
Lock

Residence UIO
Related FAULTOPT_AO_C
Parameters

Remarks If FAULTOPT_AO_C is UseFaultValue, FAULTVALUE_AO_C defines the value to which the


output is set if communication between the controller and the IOM is lost.
If the IOM hard fails or loses power, outputs go to unpowered regardless of FAULTVALUE.

Specific to UIO, AO04, AO08


Block(s)

Description Fault Value


Data Type FLOAT32
Range -6.9 to 106.9
Default -6.9
Config Yes
Load

Active
Loadable

- 1078 -
Chapter 8 - Fxxxx Parameters

Access EngineerAppDev
Lock

Residence IOM Block


Related FAULTOPT_AO_C
Parameters

Remarks If FAULTOPT_AO_C is UseFaultValue, FAULTVALUE_AO_C defines the value to which the


output is set if communication between the controller and the IOM is lost.
If the IOM hard fails or loses power, outputs go to unpowered regardless of FAULTVALUE.

8.29 FBCONN1

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains
function block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.30 FBCONN2

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load

- 1079 -
Chapter 8 - Fxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains
function block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.31 FBCONN3

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains function
block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.32 FBCONN4

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load

- 1080 -
Chapter 8 - Fxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains function
block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.33 FBCONN5

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains
function block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.34 FBCONN6

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load

- 1081 -
Chapter 8 - Fxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains
function block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.35 FBCONN7

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains function
block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.36 FBCONN8

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load

- 1082 -
Chapter 8 - Fxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains function
block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.37 FBCONN9

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains
function block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.38 FBCONN10

Specific to Regulatory HRB


Blocks
Description Function block connector
Data Type BLOCKID
Range
Default Blank
Config. Yes
Load

- 1083 -
Chapter 8 - Fxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related
Parameters
Remarks This parameter is not used in the current release. This parameter contains
function block connectors to be used for connecting native blocks with HRB. These
parameters will appear along with all the existing connectors in the Native Block
Reference tab.

8.39 FBORSTS

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegSummer, RegCalc, and Switch.
Description Function Block Override Status
Data Type Enumeration PTORST
Range NotCon (0) Sel (1) NotSel (2)
Default NotCon (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks Indicates if the primary is selected or not.

NOTE
Fanout has 8 secondaries, but it shows the FBORSTS status from its first secondary only.

8.40 FBTYPE

Specific to Block PID


(s)
Description Function Block Type - Indicates type of base template from which the function
block was derived.
Data Type Enumeration FBTYPES
Range l Null,
l PID and all Regulatory Control function blocks,
l DataAcq and all Auxiliary function blocks,
l DigComp,
l DisDev,

- 1084 -
Chapter 8 - Fxxxx Parameters

l All Logic function blocks,


l All Utility function blocks,
l Sco.
Default Null
Config Load No, automatically determined when the function block is assigned to the
Execution Environment.
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

8.41 FCE_OUTPUT[1..24]

Specific to Block QIPACTERM


Description Final Control Element Output
Data Type Boolean
Range Off(0) Off
On(1) On
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 6 of the Status 1 byte in the input assembly for the
designated position [1-24].

8.42 FCE_OUTPUT[1..200]

Specific to QIPACCHAN
Block
Description Final Control Element Output
Data Type Boolean
Range Off(0) Off
On(1) On
Default Off
Config Load No

- 1085 -
Chapter 8 - Fxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 6 of the Status 1 byte in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

8.43 FEEDFAILED[1..24]

Specific to QIPACTERM
Block
Description Feed Failed
Data Type Boolean
Range Off(0) OK
On(1) Failed

Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 5 of the Status 2 word in the input assembly for the
designated position [1-24].

8.44 FEEDFAILED[1..200]

Specific to QIPACTERM
Block
Description Feed Failed
Data Type Boolean
Range Off(0) OK
On(1) Failed
Default Off
Config Load No
Active No
Loadable

- 1086 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This is the value of bit 5 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

8.45 FEEDOVERRIDE[1..24]

Specific to QIPACTERM
Block
Description Feed Override Active
Data Type Boolean
Range Off(0) Inactive
On(1) Active - external logic inhibited from
removing feed permissive
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 4 of the Status 2 word in the input assembly for the
designated position [1-24].

8.46 FEEDOVERRIDE[1..200]

Specific to QIPACCHAN
Block
Description Feed Override Active
Data Type Boolean
Range Off(0) Inactive
On(1) Active - external logic inhibited from
removing feed permissive
Default Off
Config Load No
Active No
Loadable

- 1087 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This is the value of bit 4 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

8.47 FEEDTYPE[1..24]

Specific to QIPACTERM
Block
Description Feed Type
Data Type Enumeration
Range 0 Gain In Weight
1 Loss In Weight
2 Flow Meter
3 Hand Add
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bits 0 and 1 of the Status 2 word in the input assembly for the
designated position [1-24].

8.48 FEEDTYPE[1..200]

Specific to QIPACCHAN
Block
Description Feed Type
Data Type Enumeration
Range 0 Gain In Weight
1 Loss In Weight
2 Flow Meter
3 Hand Add
Default 0
Config Load No
Active No

- 1088 -
Chapter 8 - Fxxxx Parameters

Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bits 0 and 1 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

8.49 FEEDWEIGHT[1..24]

Specific to QIPACTERM
Block
Description Feed Weight
Data Type Float64
Range N/A
Default NAN
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks During most feeds this is the net accumulated weight for the single feed. During
primary overlapped feeds this is the combined feed weight of all feeds. At the
completion of the feed, it contains the delivered weight for the feed. This value is
reset to 0 at the beginning of a feed. This is the value in the input assembly for the
designated position [1-24].

8.50 FEEDWEIGHT[1..200]

Specific to QIPACCHAN
Block
Description Feed Weight
Data Type Float64
Range N/A
Default NAN
Config No
Load
Active No
Loadable

- 1089 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks During most feeds this is the net accumulated weight for the single feed. During
primary overlapped feeds this is the combined feed weight of all feeds. At the
completion of the feed, it contains the delivered weight for the feed. This value is
reset to 0 at the beginning of a feed. This is the value in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

8.51 FETCHMODE

Specific to Block All IO Channels, PWM Channel, SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


(s)
Description Fetch Mode - When this mode is set, the IO Channel works without the IOM
function block.
Data Type Integer
Range N/A
Default Off (0)
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks Direct Get, Direct Store

8.52 FF

Specific to Block(s) PIDFF


Description Feed Forward Input in Engineering Units.
Data Type Real
Range N/A
Default NaN
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters PV, SP, SIFL.
Remarks

- 1090 -
Chapter 8 - Fxxxx Parameters

8.53 FFCONN

Specific to Block(s) PIDFF


Description Feed Forward Input Connect.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock Application Developer
Residence
Related Parameters
Remarks

8.54 FFOPT

Specific to PIDFF
Block(s)
Description Feedforward Option. FFOPT indicates if feedforward is to be added to or
multiplied by the incremental PID output.
Data Type Integer
Range
Default 0
Config Load
Active No
Loadable
Access Lock Engineer
Residence
Related FF, PV. SIFL, SP.
Parameters
Remarks

- 1091 -
Chapter 8 - Fxxxx Parameters

8.55 FFPERIOD

Specific to CONTROLMODULE
Block(s)
Description Foundation Fieldbus (FF) Execution period - Specify an execution
period/processing period (or scan rate) for fieldbus blocks contained in the CM in
milliseconds and seconds. It determines how the fieldbus blocks contained in the
CM participate in the Link schedule.
Data Type Enumeration FFPERIOD
Range 0 250ms
1 500ms
2 1s
3 2s
4 4s
5 8s
6 16s
7 32s
Default 1s
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

8.56 FFSTS

Specific to Block(s) PIDFF


Description Feed Forward Input Status
Data Type Integer
Range
Default 0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 1092 -
Chapter 8 - Fxxxx Parameters

8.57 FILEPOSITION

Specific to Block(s) TCMI


Description Right or Left File Position
Data Type STRING
Range N/A
Default --
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

8.58 FILTERHDR[0..numChans-1]

Specific to Block(s) DIM


Description Filter Grid Header
Data Type String
Range Maximum of 20 characters
Default Null String
Config Load
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks

8.59 FILTEROFF[0..numChans / 8]

Specific to DIM
Block(s)
Description Filter times for On to Off transition in milliseconds. Configurable on each DIM in
groups of 8 consecutive channels.
Data Type DC Modules: Enumeration of FILTERONOFF AC Modules: Enumeration of
ACFILTERONOFF
Range FILTEROFFON: No Delay (0) 1 ms Delay (1) 2 ms Delay (2) 9 ms Delay (9) 18 ms
Delay (18) ACFILTEROFFON: 9 ms Delay (9) 18 ms Delay (18)
Default DC Modules: No Delay (0) AC Modules: 9 ms Delay (9)

- 1093 -
Chapter 8 - Fxxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock Application Developer
Residence CEE
Related FILTERON[0..numChans / 8]
Parameters
Remarks

8.60 FILTEROFF [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1738-IB4DM12, 1738-IB8M12


Block(s)
Description Input Delay Time ON to OFF (micro second)
Data Type 16-Bit Unsigned Integer
Range 0-65535
Default 1000
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related FILTERON
Parameters
Remarks Input ON to OFF delay is the time from a valid input signal to recognition by the
module hardware. This is useful for filtering out transient noise.

8.60.1 FILTEROFF

Specific to Block EtherNet/IP [EIP] IOMs: 1732E-IB16M12DR


(s)
Description Input Delay Time ON to OFF (micro second)
Data Type Enumeration
Range 0, 1, 2, 4, 8, 16
Default 1
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related FILTERON
Parameters
Remarks Input ON to OFF delay is the time from a valid input signal to recognition by the
module hardware.

- 1094 -
Chapter 8 - Fxxxx Parameters

8.61 FILTERON [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1738-IB4DM12, 1738-IB8M12


Block(s)
Description Input Delay Time OFF to ON (micro second)
Data Type 16-Bit Unsigned Integer
Range 0-65535
Default 1000
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related FILTEROFF
Parameters
Remarks Input OFF to ON delay is the time from a valid input signal to recognition by the
module hardware. This is useful for filtering out transient noise.

8.61.1 FILTERON

Specific to Block EtherNet/IP [EIP] IOMs: 1732E-IB16M12DR


(s)
Description Input Delay Time OFF to ON (milli second)
Data Type Enumeration
Range 0, 1, 2, 4, 8, 16
Default 1
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related FILTEROFF
Parameters
Remarks Input OFF to ON delay is the time from a valid input signal to recognition by the
module hardware.

- 1095 -
Chapter 8 - Fxxxx Parameters

8.62 FILTERON[0..numChans / 8]

Specific to DIM
Block(s)
Description Filter times for Off to On transition in milliseconds. Configurable on each DIM in
groups of 8 consecutive channels.
Data Type DC Modules: Enumeration of FILTEROFFON AC Modules: Enumeration of
ACFILTEROFFON
Range FILTEROFFON: No Delay (0) 1ms Delay (1) 2 ms Delay (2) ACFILTEROFFON: 1 ms
Delay (1) 2 ms Delay (2)
Default DC Modules: No Delay (0) AC Modules: 1 ms Delay (1)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related FILTEROFF[0..numChans / 8]
Parameters
Remarks

8.63 FILTERTIME

Specific to Block(s) UAI, AI16-100MS


Description Filter Time
Data Type UINT32
Range 0 to 120
Default 0
Config Load Yes
Active Loadable

Access Lock AppDevOnly


Residence IOM Block
Related Parameters

Remarks The filter time to be applied by the module to the analog signal

8.64 FINALCMDPARAM

Specific to EIP Generic device, EIP Generic drive and other EIP Drive/Device modules in Control
Block(s) builder library.
Description Final Command Parameter
Data Type STRING
Range Maximum character supported is 64

- 1096 -
Chapter 8 - Fxxxx Parameters

Config Load No
Active No
Loadable
Access AppDevOnly
Lock
Residence ERDB
Related FINALCMDVAL, FINALCMDPC
Parameters
Remarks EIP Generic Device/Drives and other EIP Drives/Devices support a feature to set the
device to a failsafe state on deletion of Control Module containing EIP Drive/Device
output channel/AO reference block from monitoring.
FINALCMDPARAM is the parameter that the user configures on PDE (Parameter
definition editor) while creating an EIP device/drive type. The value of this parameter
is another parameter on the type that the user wishes to configure for failsafe action
for the device.
FINALCMDVAL is the value that the user wants the parameter configured for failsafe
action (as the value of FINALCMDPARAM) to assume and be written to device on
deletion of Control Module containing EIP Drive/Device output channel/AO reference
block from monitoring. This value should be provided by the user in PDE while
creating an EIP device/drive type.
FINALCMDPC is an internal parameter used by PDE and the EIP Generic IOM block in
CEE to support this feature.

8.65 FINALCMDPC

Specific to EIP Generic device, EIP Generic drive and other EIP Drive/Device modules in Control
Block(s) builder library.
Description Final Command Param Code.
Data Type UINT16
Range N/A

Default 0
Config Load Yes
Active No
Loadable

- 1097 -
Chapter 8 - Fxxxx Parameters

Access AppDevOnly
Lock
Residence CEE
Related FFINALCMDPARAM, FINALCMDVAL
Parameters
Remarks EIP Generic Device/Drives and other EIP Drives/Devices support a feature to set the
device to a failsafe state on deletion of Control Module containing EIP Drive/Device
output channel/AO reference block from monitoring.
FINALCMDPARAM is the parameter that the user configures on PDE (Parameter
definition editor) while creating an EIP device/drive type. The value of this parameter
is another parameter on the type that the user wishes to configure for failsafe action
for the device.
FINALCMDVAL is the value that the user wants the parameter configured for failsafe
action (as the value of FINALCMDPARAM) to assume and be written to device on
deletion of Control Module containing EIP Drive/Device output channel/AO reference
block from monitoring. This value should be provided by the user in PDE while
creating an EIP device/drive type.
FINALCMDPC is an internal parameter used by PDE and the EIP Generic IOM block in
CEE to support this feature.

8.66 FINALCMDVAL

Specific to Final OP Value Upon Unpower.


Block(s)
Description Refresh Connections on Switchover.
Data Type INT32
Default 0
Config Load Yes
Active No
Loadable
Access AppDevOnly
Lock
Residence CEE
Related FINALCMDPARAM, FINALCMDPC
Parameters
Remarks EIP Generic Device/Drives and other EIP Drives/Devices support a feature to set the
device to a failsafe state on deletion of Control Module containing EIP Drive/Device
output channel/AO reference block from monitoring.
FINALCMDPARAM is the parameter that the user configures on PDE (Parameter
definition editor) while creating an EIP device/drive type. The value of this parameter
is another parameter on the type that the user wishes to configure for failsafe action
for the device.
FINALCMDVAL is the value that the user wants the parameter configured for failsafe
action (as the value of FINALCMDPARAM) to assume and be written to device on
deletion of Control Module containing EIP Drive/Device output channel/AO reference
block from monitoring. This value should be provided by the user in PDE while
creating an EIP device/drive type.
FINALCMDPC is an internal parameter used by PDE and the EIP Generic IOM block in
CEE to support this feature.

- 1098 -
Chapter 8 - Fxxxx Parameters

8.67 FIRSTOUTACTED

Specific to Block FIRSTOUT


(s)
Description The status flag of first out acted.
Data Type Boolean
Range OFF, ON
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This flag is set to ON state if any valid input transition from normal state to
abnormal state.

8.68 FIRSTOUTALM.FL

Specific to Block(s) FIRSTOUT


Description First out alarm Flag
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related FIRSTOUTALM.PRFIRSTOUTALM.SV
Parameters
Remarks When ON, it indicates that the function block is not currently in the normal
state

8.69 FIRSTOUTALM.PR

Specific to Block(s) FIRSTOUT


Description First out alarm priority
Data Type Enumeration ALMPR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None

- 1099 -
Chapter 8 - Fxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related FIRSTOUTALM.FLFIRSTOUTALM.SV
Parameters
Remarks When ON, it indicates that the function block is not currently in the normal
state

8.70 FIRSTOUTALM.SV

Specific to Block(s) FIRSTOUT


Description First out alarm severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related FIRSTOUTALM.FLFIRSTOUTALM.PR
Parameters
Remarks When ON, it indicates that the function block is not currently in the normal
state

8.71 FIRSTOUTINPUT

Specific to FIRSTOUT
Block(s)
Description The Input Index that underwent transition or “MULTIPLE”in case of a multiple
input transition.
Data Type Enumeration
Range Input #1, Input# 2 ...Input #24, Multiple
Default NONE
Config Load NO
Active No
Loadable

- 1100 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This would indicate first input that transitioned to cause Firstout. In the case of
multiple inputs, it will display as multiple.

8.72 FIRSTUPACTED

Specific to Block(s) HTMOTOR


Description The status flag of first out acted
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This flag is set to ON state if the firstout logic detects a valid input
transition.

8.73 FLAG

Specific to HRBALG_REG block


Blocks
Description FLAG FB reference
Data Type BLOCKID
Range Not applicable

Default NULL
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the FLAG block in the emulation CM of EC. The
emulation CM of EC holds the HRBALG_REG instance. This parameter connector is
used in EC- Algorithm emulation for storing Mode Shed condition.

- 1101 -
Chapter 8 - Fxxxx Parameters

8.74 FLOAT_VALUE

Specific to FLOAT32_TAG, Scalar UDT Block


Block(s)
Description FLOAT32 Value: This is the Parameter where the value read from control Logix PLC
is Displayed or the Value to be written to the PLC needs to be entered.
Data Type -
Range 0 or 1
Default 0
Config Load Yes

Active No
Loadable
Access Lock Operator
Residence CEE
Related Access Lock
Parameters
Remarks Configuration of Access Lock Parameter present on this block determines whether
it has been configured as a Parameter to be read or a Parameter to be written.

8.75 FLOAT64PARAM

Specific to Block(s) EIM


Description Data Attribute Float64
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence NOLOAD
Related Parameters
Remarks

8.76 FLOAT64VAL[0…40]

Specific to Block(s) EIM


Description Float64 Value
Data Type FLOAT64
Range ±1.7E+308
Default 0.0

- 1102 -
Chapter 8 - Fxxxx Parameters

Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters NUMFLOAT64
Remarks Accessed as an array. Mapped to custom Float64 parameters

8.77 FLSHSTAT

Specific to Block(s) ALMWINDOW


Description Flash status output of Window group
Data Type Enumeration: FLASHSTATE
Range FASTFLASH SLOWFLASH LAMPSTEADY LAMPOFF
Default LAMPOFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters ALMIN[1..16]
Remarks Indicates the flashing state of the alarm window.

8.78 FLSHSTAT[1..32]

Specific to Block(s) ANNPANEL


Description Input to the Annunciator Panel
Data Type Enumeration: FLASHSTATE
Range FASTFLASH SLOWFLASH LAMPSTEADY LAMPOFF
Default LAMPOFF
Config Load NO
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters LAMPOUT[1..32]
Remarks Connect input from Flash state of alarm window function block.

- 1103 -
Chapter 8 - Fxxxx Parameters

8.79 FLTIP

Specific to Block ACE


Description Floating IP Address
Data Type STRING
Range 15
Default 0.0.0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters

This parameter displays the floating IP configured on the ACE when the ACE
Remarks is loaded.

8.80 FMWREV1 [1...15] through FMWREV8 [1...15]

Specific to IOLINK
Block(s)
Description IOP Firmware Revision
Data Type String
Range
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related IOMFWREVA, IOMFWREVB
Parameters
Remarks These parameters are arrays (that correspond to PMIO chassis numbered 1
through 8) with up to 15 entries each indicating the associated IOP's firmware
revision. The index of each array corresponds to the physical slot in the PMIO
chassis number. IOP firmware revision is expressed in the form X.Y, where X is the
version and Y is the revision level.

- 1104 -
Chapter 8 - Fxxxx Parameters

8.81 FONTSTYLE

Specific to Text Comment block


Block(s)
Description Use this parameter to specify the comments' text font.
Data Type STRING
Range N/A
Default Microsoft Sans serif
Config Load No
Active Yes
Loadable
Access Lock APPDEVONLY
Residence ERDB only
Related
Parameters
Remarks For more information on active loadable parameter, refer to the About
Editing/Loading parameters while active section in the Control Building User's
Guide.

8.82 FORCEMODEATTR

Specific to AUTOMAN,FANOUT,ENHREGCALC,SWITCH,OVRDSEL,REGCALC,RATIOBIAS,PIDFF,
Block(s) POSPROP, PIDER, RATIOCTL, PID-PL, PID, REGSUMMER, RAMPSOAK, REMCAS.
Description Force Mode Attribute decides whether Human stores to Mode parameter is allowed
or not when Mode Attribute is PROGRAM.
Data Type BOOLEAN
Range ON OFF
Default OFF
Config Yes
Load
Active No
Loadable
Access ENGINEER
Lock
Residence CEE
Related MODEATTR MODE
Parameters
Remarks OFF (Disabled): Human stores (from an Operator, Supervisor or Engineer) to MODE
are allowed, even when the ModeAttribute is PROGRAM. ON (Enabled): Human
stores (from an Operator, Supervisor or Engineer) to MODE are restricted, when
the ModeAttribute is PROGRAM.

- 1105 -
Chapter 8 - Fxxxx Parameters

8.83 FORCEREADREQ

Specific to TRANSITION
Block(s)
Description Force Read Request - Force cyclic get requests for all Transition input
connections
Data Type Boolean
Range OFF (0): No special handling required.
ON (1) All cyclic get requests of the Transition have to be
enabled permanently.
Default OFF (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameter
Remarks Can only be adjusted in INACTIVE

8.84 FORCERESTART

Specific to RETENTIONTRIG
Block(s)
Description Force Restart
Data Type Boolean
Range OFF, ON
Default OFF
Config Yes
Load
Active No
Loadable
Access AppDevOnly
Lock
Residence CEE
Related PWRGOOD1, PWRGOOD2
Parameter
Remarks When FORCERESTART = ON, a retention-data-save triggered by loss of external
power to the UOC is followed by a shutdown and automatic restart of the UOC. In the
event that not all actuators associated with this controller are affected by the external
power loss, restarting the controller ensures that any powered actuators transition to
their configured fail-safe state.

- 1106 -
Chapter 8 - Fxxxx Parameters

8.85 FORCETOINACTIVE

Specific to RCM
Block(s)
Description Force RCM to Inactive from IDLE
Data Type Boolean
Range True (0n) Allows RCM to be inactivated even if
some post execution processing is not
complete
False (Off) Allows RCM inactivation only after all post
execution processing is complete
Default False
Config Yes
Load
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related
Parameters
Remarks The default value of OFF will ensure delivery of batch events to the server event
database before the RCM can be inactivated and deleted. A value of ON allows
inactivation and deletion of the RCM regardless of event processing. This value may
be required to recover from system failures or to operate the system in some
degraded condition (for example, event database does not operate, communication
to server interrupted).

8.86 FPGAFAIL

Specific to EIM, C300, CN100, ELCN, ELCNNODE, UOC,


Block(s)
Description FPGA Hardware Failure
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks True if the device detects a failure with the FPGA functionality. UOC - Soft failure
condition. FPGA diagnostic failure. Hardware should be replaced.

- 1107 -
Chapter 8 - Fxxxx Parameters

8.87 FPINDICATOR[1..4]

Specific to Block(s) JAGXCHAN


Description Floating Point Input Indicator
Data Type Enumeration
Range 0 Gross Weight
1 Net Weight
2 Tare Weight
3 Fine Gross Weight
4 Fine Net Weight

5 Fine Tare Weight


6 Rate
7 JagBasic Custom Variable 1

8 JagBasic Custom Variable 2


9 JagBasic Custom Variable 3
10 JagBasic Custom Variable 4
11 Low-Pass Filter Corner Frequency
12 Notch Filter Frequency
13 Setpoint 1 Coincidence
14 Setpoint 2 Coincidence
15 Setpoint 1 Dribble
16 Setpoint 2 Dribble
17 Setpoint 1 Tolerance
18 Primary Units-Low Increment Size
19-28 Reserved
29 Last JAGXTREME Error Code
30 No Data Response - Command
Success
31 No Data Response - Command Failed

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
RelatedParameters: FPVALUE[1..4]
Remarks This is the value of bits 0 through 4 of the FPIndicator byte in the floating
point input assembly for the designated scale slot [1..4].

- 1108 -
Chapter 8 - Fxxxx Parameters

8.88 FPINDRAW[1..4]

Specific to Block(s) JAGXTERM


Description Floating Point Indicator
Data Type BYTE
Range 0-255
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks The floating point indicator byte presented as an integer.

8.89 FPVALUE[1..4]

Specific to Block JAGXCHAN


(s)
Description Floating Point Value
Data Type FLOAT32
Range N/A
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related FPINDICATOR[1..4]
Parameters
Remarks This is the floating point value in the floating point input assembly for the
designated scale slot [1..4].

8.90 FPVALUERAW[1..4]

Specific to Block(s) JAGXTERM


Description Floating Point Value
Data Type FLOAT32
Range N/A
Default Null
Config Load No

- 1109 -
Chapter 8 - Fxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters FPINDICATOR[1..4]
Remarks This is the floating point value in the floating point input assembly.

8.91 FRC

Specific to Block CEE, CEEC300, IOLINK, IOLINKC300, CEEUOC, CEECN100


(s)
Description Free Running Counter
Data Type 32-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300, IOLINKC300), IOLIM(IOLINK), UOC(CEEUOC),
CN100(CEECN100)
Related
Parameters
Remarks

8.92 FRCPERM

Specific to Block(s) SignalSel


Description Forced Select Permissive
Data Type Boolean
Range OFF (0) Operator not permitted to force select an input

ON (1) Operator may force select previously defined


inputs
Default OFF
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related FRCREQ, FRCSEL
Parameters
Remarks Setting this parameter allows the operator to force select an input

- 1110 -
Chapter 8 - Fxxxx Parameters

8.93 FRCREQ

Specific to Block SignalSel


(s)
Description Forced Select Request Flag
Data Type Boolean
Range OFF (0) No Input forced
ON (1) Force the previously selected input
Default OFF
Config Load Yes
Active Loadable No
Access Lock Operator
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related ACTREMOVETYPE, FRCSEL
Parameters
Remarks The operator can force select an input by setting this flag. Also, the FRCPERM
flag must be set.

8.94 FRCSEL

Specific to Block SignalSel


(s)
Description Forced Select Input
Data Type Enumeration: PINP:0x7E
Range 0: None 1: SelectP1 2: SelectP2 3: SelectP3 4: SelectP4 5: SelectP5 6: SelectP6
Default SelectP1
Config Load Yes
Active Loadable No
Access Lock Operator
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related FRCREQ, ACTREMOVETYPE
Parameters
Remarks This parameter denotes the input to be force selected if the FRCPERM and
FRCREQ flags are set.

- 1111 -
Chapter 8 - Fxxxx Parameters

8.95 FREEARRPARAMWRITES

Specific to Block(s) PB_EIP, CEEC300, CEEUOC


Description Free Arrayed Param Writes
Data Type UINT16
Range 0-325
Default 0

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence No Load

Related Parameters -
Remarks Number of arrayed tag/parameter writes currently free in this EIM.

8.96 FREEARRWRITES

Specific to Block(s) C300 CEE


Description Free arrayed writes
Data Type UINT16
Range 0-65
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Number of free arrayed writes available in the EIM

8.97 FREEFL

Specific to SCM, RCM, UCM, CM


Block(s)
Description Free Flag - Resource is unused.
Data Type BOOLEAN
Range Off Resource is
not free
On Resource is
free
(completely
unused)

- 1112 -
Chapter 8 - Fxxxx Parameters

Default Off (If SCMOPT in CM equals None or Fixed) On (If SCMOPT in CM


equals COMMON)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related SCMOPT
Parameters
Remarks This flag indicates, whether the resource is completely unused.
FREEFL is ON, if NUMOWNERS = 0 FREEFL is OFF, if NUMOWNERS
(greater than)#62; 0 FREEFL always has the opposite value of
USEDFL If and only if MAXOWNERS = 1, FREEFL is equal to AVAILFL.

8.98 FREEMEM

Specific to CEEC300, CPM, CEEUOC, CEECN100


Block(s)
Description Currently Free Memory
Data Type 32-Bit Integer
Exposure Output
Range 0 to 4194304 Bytes
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CPM), UOC(CEEUOC), CN100(CEECN100)
Related MAXFREEBLKSZ, TOTALMEM, USEDMEM.
Parameters
Remarks The free memory decreases as blocks are loaded and increases as blocks are
unloaded. The difference between TOTALMEM and FREEMEM is equal to
USEDMEM.

8.99 FREEMEMINK

Specific to CEEC300, CPM, CEEUOC, CEECN100


Block(s)
Description Currently Free Memory
Data Type 32-Bit Integer
Range 0 to 4194304 Kbytes

- 1113 -
Chapter 8 - Fxxxx Parameters

Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CPM), UOC(CEEUOC), CN100(CEECN100)
Related MAXFREEINK, TOTALMEMINK, USEDMEMINK.
Parameters
Remarks This parameter publishes total amount of unused memory in the user memory
pool. Free memory decreases as blocks are loaded and increases as blocks are
unloaded. The difference between TOTALMEMINK and FREEMEMINK is equal to
USEDMEMINK.

8.100 FREENONARRPARAMWRITES

Specific to Block(s) PB_EIP, CEEC300, CEEUOC


Description Free Non-Arrayed Param Writes
Data Type UINT16
Range 0-675
Default 0

Config Load No

Active Loadable No
Access Lock ViewOnly
Residence No Load

Related Parameters -
Remarks Number of non-arrayed tag/parameter writes currently free in this EIM.

8.101 FREESCALARTAGREADS

Specific to Block(s) EIM EIP Protocol Block


Description Free Scalar Tag Reads
Data Type UINT16
Range 0-2325
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Number of Free Scalar Tag Reads available to be configured in this EIM.

- 1114 -
Chapter 8 - Fxxxx Parameters

Specific to Block(s) PB_EIP, CEEC300, CEEUOC


Description Free Scalar Tag Reads
Data Type UINT16
Range 0-2325
Default 0

Config Load No

Active Loadable No
Access Lock ViewOnly
Residence No Load

Related Parameters -
Remarks Number of Free Scalar Tag Reads available to be configured in this EIM.

8.102 FREENONARRWRITES

Specific to Block(s) C300 CEE


Description Free non-array writes
Data Type UINT16
Range 0-135
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Number of free non-array writes available in the EIM.

8.103 FREEUDTTAGREADS

Specific to Block(s) PB_EIP, CEEC300, CEEUOC


Description Free UDT Tag Reads
Data Type UINT16
Range 0-325
Default 0

Config Load No

Active Loadable No

- 1115 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence No Load

Related Parameters -
Remarks Number of Free UDT Tag Reads available to be configured in this EIM..

8.104 FREEUDTTAGREAD

Specific to Block(s) C300 CEE


Description Free UDT Tag Reads
Data Type UINT16
Range 0-65
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Number of Free UDT Tag Reads available in the EIM.

8.105 FREESCATAGREAD

Specific to Block(s) C300 CEE


Description Free Scalar Tag Reads
Data Type UINT16
Range 0-400
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Number of Free Scalar Tag Reads available in the EIM.

- 1116 -
Chapter 8 - Fxxxx Parameters

8.106 FREEZETIME

Specific to Block(s) All IO Channels, PWM Channel


Description Maximum Freeze Time
Data Type Real
Range N/A
Default 4
Config Load

Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

8.107 FREQ5060

Specific to Block(s) UAI, AI16-100MS, DI16-VACDC


Description Frequency
Data Type ENUM
Range
0 50Hz

1 60Hz

Default
1 60Hz

Config Load Yes


Active Loadable

Access Lock Application Developer


Residence IOM Block
Related Parameters BURNOUTMODE
Remarks This parameter defines the frequency of the AC power source.

8.108 FREQ6050

Specific to LLAI, LLMUX, RHMUX, STI; AI-LLMUX, AI-LLAI, DI-HV


Block(s)
Description Frequency 60/50 Hz.
Data Type Enumeration
Range 60 Hz (0) 50 Hz (1)
Default 60 Hz (0)
Config Yes

- 1117 -
Chapter 8 - Fxxxx Parameters

Load

Active No
Loadable
Access Lock Engineer
Residence IOM
Related N/A
Parameters
Remarks For the LLMUX, RHMUX, and STI blocks, this parameter defines the power
frequency configuration needed. For the LLAI IOM, this parameter displays the
frequency used in case of missing/invalid AC signal. For the AI-LLMUM and DI-HV
IOMs, this parameter defines the frequency of the AC power source.

8.109 FREQPERIOD

Specific to Block(s) Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC
Description Frequency Integration Period - Period at which Module calculates
frequency.
Data Type Enumeration
Range 25ms (0) 50ms (1) 100ms (2) 200ms (3) 500ms (4) 1000ms (5) 2000ms (6)
Default 1000ms (5)
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

Specific to Block Series C PICHANNEL


(s)
Description Frequency Integration Period
Data Type ENUM
Range 25ms(0) 50ms(1) 100ms(2) 200ms(3) 500msS(4) 1000ms(5) 2000ms(6)
Default 1000ms
Config Load Yes
Active Loadable No

- 1118 -
Chapter 8 - Fxxxx Parameters

Access Lock AppDevOnly


Residence IOM
Related PV
Parameters
Remarks FREQPERIOD represents the interval of time in which frequency calculation is
performed.
l 25ms - 25 milliseconds
l 50ms - 50 milliseconds
l 100ms - 100 milliseconds
l 200ms - 200 milliseconds
l 500ms - 0.5 seconds
l 1000ms - 1 seconds
l 2000ms - 2 seconds

8.110 FREQPERIOD[0..7]

Specific to Block(s) Pulse Input IOM


Description Frequency Integration Period - Period at which Module calculates
frequency.
Data Type Enumeration
Range 25ms (0) 50ms (1) 100ms (2) 200ms (3) 500ms (4) 1000ms (5) 2000ms (6)
Default 1000ms (5)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks PV in EU = (C1/C2) * TIMEBASE * pulses/(Frequency Integration Period)

8.111 FSTFLSHSPD

Specific to Block ANNPANEL


(s)
Description Fast flash factor. It is dependant on Slow flash speed
Data Type Enumeration: FLASHFACTOR
Range 2xSlowFlash, 4xSlowFlash
Default 4xSlowFlash
Config Load YES
Active Loadable No

- 1119 -
Chapter 8 - Fxxxx Parameters

Access Lock Engineer


Residence CEE
Related SLWFLSHSPD
Parameters
Remarks Determines the fast flash speed of the alarm window as a multiple of slow
flash speed.

8.112 FSTS

Specific to Block(s) FLOWCOMP


Description Flow Input Value Status - Indicates the current status of flow input F.
Data Type Enumeration PVVALSTS
Range Bad (0): The value is bad and has been replaced with
NaN.
Uncertn (1): The status of the value is uncertain.
Normal (2): The value is good.
Manual (3): The value was manually stored.
Default Bad
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE/C200
Related F, COMPOSITEPHASESTSCOMPTERM
Parameters
Remarks

8.113 FTA1TYPE

Specific to LLMUX, RHMUX


Block(s)
Description Field Termination Assembly (FTA) 1 Type Position 1,2. Shows the type of FTA1
connected to the associated I/O Processor (IOP).
Data Type Enumeration
Range None (0) TC (1) RTD (2)
Default None (0)
Config Load No
Active No
Loadable

- 1120 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence IOP
Related
Parameters
Remarks Each FTA supports 16 points for a total of 32 points.

8.114 FTA2TYPE

Specific to LLMUX, RHMUX


Block(s)
Description Field Termination Assembly (FTA) 2 Type Position 1,2. Shows the type of FTA2
connected to the associated I/O Processor (IOP).
Data Type Enumeration
Range None (0) TC (1) RTD (2)
Default None (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks Each FTA supports 16 points for a total of 32 points.

8.115 FTAAOVRNFL

Specific to Serial Interface IOM


Block(s)
Description FTA A Overrun Flag - Indicates whether the FTA currently has too many writes to
process and is in an overrun condition (value is On) or not (value is Off).
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable

- 1121 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related FTABOVRNFL
Parameters
Remarks When an Overrun is indicated, some requested writes are not being completed.
Check the application to see if the quantity or rate of writes can be reduced, or if
possible, split the load between two FTAs, so that no overruns occur.

8.116 FTAASTS

Specific to Block(s) Serial Interface IOM


Description FTA A Status - Provides the current status of the FTA.
Data Type Enumeration
Range FtaNotPresnt (0) TfaOk (1) FtaConfig (2) FtaSoftFail (3)
Default FtaNotPresnt (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters FTABSTS
Remarks

8.117 FTABOVRNFL

Specific to Serial Interface IOM


Block(s)
Description FTA B Overrun Flag - Indicates whether the FTA currently has too many writes to
process and is in an overrun condition (value is On) or not (value is Off).
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related FTAAOVRNFL
Parameters
Remarks When an Overrun is indicated, some requested writes are not being completed.
Check the application to see if the quantity or rate of writes can be reduced, or if
possible, split the load between two FTAs, so that no overruns occur.

- 1122 -
Chapter 8 - Fxxxx Parameters

8.118 FTABSTS

Specific to Block(s) Serial Interface IOM


Description FTA B Status - Provides the current status of the FTA.
Data Type Enumeration
Range FtaNotPresnt (0) TfaOk (1) FtaConfig (2) FtaSoftFail (3)
Default FtaNotPresnt (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters FTAASTS
Remarks

8.119 FTACONNA

Specific to All IOP Blocks


Block(s)
Description Field Termination Assembly (FTA) Connection to I/O File. Shows the FTA connector
that is connected to the associated I/O Processor (IOP).
Data Type Enumeration
Range CONN_A (0): IOP is connected to FTA connector A.
CONN_B (1): IOP is connected to FTA connector B.

Default CONN_A (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks

- 1123 -
Chapter 8 - Fxxxx Parameters

8.120 FTACONNB

Specific to All IOP Blocks


Block(s)
Description Field Termination Assembly (FTA) Connection to I/O File. Shows the FTA connector
that is connected to the associated I/O Processor (IOP).
Data Type Enumeration
Range CONN_A (0): IOP is connected to FTA connector A.
CONN_B (1): IOP is connected to FTA connector B.
Default CONN_A (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks

8.121 FTAPRESA

Specific to All PM I/O Modules


Block(s)
Description Field Termination Assembly (FTA) Present Channel A . Shows whether the module
on Channel A is connected to a FTA or not.
Data Type Boolean
Range Off (0): FTA absent.
On (1): FTA present.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

- 1124 -
Chapter 8 - Fxxxx Parameters

8.122 FTAPRESB

Specific to All PM I/O Modules


Block(s)
Description Field Termination Assembly Present Channel B. Shows whether the module on
Channel B is connected to a FTA or not.
Data Type Boolean
Range Off (0): FTA absent.
On (1): FTA present.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks This parameter does not apply to non-redundant IOM configurations.

8.123 FTAREVERSEDA

Specific to Block(s) All PM I/O Modules


Description Field Termination Assembly (FTA) Connections Reversed. Shows that
the actual connection to the channel A FTA does not match the
configured connection.
Data Type Boolean
Range Off (0): Ok On
(1): FTA connections
reversed.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks Shows that the actual connection to the channel A FTA does not match
the configured connection.

- 1125 -
Chapter 8 - Fxxxx Parameters

8.124 FTAREVERSEDB

Specific to Block(s) All PM I/O Modules


Description Field Termination Assembly (FTA) Connections Reversed. Shows that
the actual connection to the channel B FTA does not match the
configured connection.
Data Type Boolean
Range Off (0): Ok On
(1): FTA connections
reversed.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks

8.125 FTEABLOCKRATE

Specific to Block(s) TCMI


Description FTE A Block Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Packets per second blocked (by CF9 firewall) on FTE A cable.

8.126 FTEARXRATE

Specific to TCMI
Block(s)
Description Local Area Network (LAN) A Receive Rate- Identifies communication receive rate in
kilobits per second (kbps) for port A (Yellow Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range

- 1126 -
Chapter 8 - Fxxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANAFAILED
Parameters
Remarks

8.127 FTEATXRATE

Specific to TCMI
Block(s)
Description Local Area Network (LAN) A Transmit Rate- Identifies communication transmission
rate in kilobits per second (kbps) for port A (Yellow Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANAFAILED
Parameters
Remarks

8.128 FTEBBLOCKRATE

Specific to Block(s) TCMI


Description FTE B Block Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No

- 1127 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks Packets per second blocked (by CF9 firewall) on FTE B cable.

8.129 FTEBRXRATE

Specific to TCMI
Block(s)
Description Local Area Network (LAN) B Receive Rate- Identifies communication receive rate in
kilobits per second (kbps) for port B (Green Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

8.130 FTEBTXRATE

Specific to TCMI
Block(s)
Description Local Area Network (LAN) B Transmit Rate- Identifies communication transmission
rate in kilobits per second (kbps) for port B (Green Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

- 1128 -
Chapter 8 - Fxxxx Parameters

8.131 FTEBBLOCK

Specific to Series A IO module function blocks


Block(s)
Description This specifies the FTE Bridge block to which the IO module is attached/assigned.
Data Type BlockId
Range NA
Default NA
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Active No
Connector
Related DRIVERNAME
Parameters
Remarks This will store the FTEB name to which the specific IOM is attached. By using this
parameter the path to the IOM can be built. All the defined FTEB blocks in the
Control Builder can be selected for the IO module block. The selection will be
through a combo box.

8.132 FTEIECSUBNETCONF

Specific to Block IEC61850M, IEC61850MSEC


(s)
Description FIEC61850-FTE Network Subnet Conflict
Data Type Boolean
Range 0 – Off – 1 – On –
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence 850M
Related
Parameters
Remarks A conflict exists between the IP addresses defined for the FTE and IEC61850
networks.

- 1129 -
Chapter 8 - Fxxxx Parameters

8.133 FTEMARTADDRCOUNT

Specific to C300, FIM4, FTEB, PGM, EHPM, EIM, TCMI, UOC


Block(s)
Description Fault Tolerant Ethernet (FTE) MAC Address Resolution Table (MART) Address Count
- Identifies the number of IP addresses contained in the FTE MART.
Data Type 16-Bit Integer, UINT16 (UOC)
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, FTEB, PGM, EHPM, EIM
Related
Parameters
Remarks (FTE parameters, see C300 definition)

8.134 FTEMARTAVGDEPTH

Specific to C300, FIM4, PGM, FTEB, EHPM., EIM, UOC


Block(s)
Description Fault Tolerant Ethernet (FTE) MAC Address Resolution Table (MART) Average Depth
- Identifies the average depth of the FTE MART or the average number of entries in
the table.
Data Type 16-Bit Integer, UINT16 (UOC)
Range 0 to 65535
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, FTEB, PGM, EHPM, NOLOAD
Related
Parameters
Remarks (FTE parameters, see C300 definition)

- 1130 -
Chapter 8 - Fxxxx Parameters

8.135 FTEMARTCOLLCOUNT

Specific to C300, FIM4, PGM, FTEB, EHPM., EIM, TCMI


Block(s)
Description Fault Tolerant Ethernet (FTE) MAC Address Resolution Table (MART) Collision
Count - Identifies the number of collisions that have occurred when hashing the
FTE MART.
Data Type 16-Bit Integer, UINT16
Range 0 to 65535
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, FTEB, PGM, EHPM, NOLOAD
Related
Parameters
Remarks (FTE parameters, see C300 definition)

8.136 FTEMARTMAXDEPTH

Specific to C300, FIM4, PGM, FTEB, EHPM, TCMI, UOC EIM


Block(s)
Description Fault Tolerant Ethernet (FTE) MAC Address Resolution Table (MART) Maximum
Depth - Identifies the maximum depth that the FTE MART has reached or the
largest number of entries in the table.
Data Type 16-Bit Integer, 0 to 65535, UINT16
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, FTEB, PGM, EHPM, NOLOAD
Related
Parameters
Remarks (FTE parameters, see C300 definition)

Specific to Block(s) UOC


Description Max Depth
Data Type UINT16
Range 0 to 65535
Default 0

- 1131 -
Chapter 8 - Fxxxx Parameters

Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

8.137 FTENETWORKERR

Specific to EIM, C300, UOC, CN100, ELCNB, ELCNNODE, EHPM


Block(s)
Description FTE Network Error
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks True if a diagnostic error is detected on the FTE network. See the “FTE” tab for
additional diagnostic parameters. Soft failure condition. One or more FTE network
errors are detected. See the FTE tab for more information.

8.138 FTEPARTNERNOTVISIBLE

Specific to C300, EIM, UOC , CN100, ELCNB, ELCNNODE, EHPM


Block(s)
Description Partner Not Visible on FTE Network
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active No
Loadable

- 1132 -
Chapter 8 - Fxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks True if the redundant partner is not visible on the FTE network. Soft failure
condition. Redundant partner device is not visible on FTE network. See the FTE tab
for more information.

8.139 FTERECEIVEERRORS

Specific to Block(s) TCMI


Description FTE Receive Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Receive errors on FTE A cable.

8.140 FTETRANSMITERRORS

Specific to Block(s) TCMI


Description FTE Transmit Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Receive errors on FTE B cable.

- 1133 -
Chapter 8 - Fxxxx Parameters

8.141 FULLFL

Specific to SCM, RCM, UCM, CM


Block(s)
Description Resource Is Not Available
Data Type BOOLEAN
Range Off Resource is not or only partially used
On Resource is completely used, not
available for more requests
Default Off (If SCMOPT in CM equals COMMON) On (If SCMOPT in CM equals None or
Fixed)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SCMOPT
Parameters
Remarks This flag indicates whether the resource is completely used and will not accept any
more requests. FULLFL is ON, if NUMOWNERS = MAXOWNERS FULLFL is OFF, if
NUMOWNERS < (less than) MAXOWNERS FULLFL always has the opposite value of
AVAILFL If and only if MAXOWNERS = 1, FULLFL is equal to USEDFL.

8.142 FULLITEMNAME

Specific to Assets, Alarm Groups


Block(s)
Description Full Item Name - An alternate naming method based on the entity's position in the
model structure.
Data Type String
Range Up to 200 characters
Default Null
Config No
Load
Active No
Loadable
Access Lock Application Developer Only
Residence SCAN
Related
Parameters
Remarks Also referred to the Enterprise Model Namespace. The Full Item Name of an asset
or alarm group consists of the item name of the entity together with the item name
of its parent and so forth up to a root node. A Full Item Name uniquely identifies an
entity within the system. For example, “\Plant\Filtration\Tank\FlowMeter”.

- 1134 -
Chapter 8 - Fxxxx Parameters

8.143 FUNCTIONNAME.DESC

Specific to Block MAP


(s)
Description Function description
Data Type String
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks It is the descriptive text for the function reference. It is configured in the PDE
of the Map block.

8.144 FUNCTIONNAME.TYPE

Specific to MAP
Block(s)
Description Function type
Data Type BLOCKID
Default None
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related FUNCTIONNAME.DESC
Parameters
Remarks A function type is the Phase type associated with a function. It defines the phase
type used to invoke the function from a parent recipe and the phase type of the
Data block for the child recipe to be invoked. It is configured in PDE of the Map
block.

- 1135 -
Chapter 8 - Fxxxx Parameters

8.145 FUNCTIONNAME.FCN

Specific to MAP
Block(s)
Description Function reference
Data Type BLOCKID
Default None
Config Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related FUNCTIONNAME.TYPE
Parameters
Remarks A function reference is the name of an SCM, RCM, MR, Proxy SCM or Proxy RCM
that is executed for the function for a unit during execution. The function reference
must have a Data block that matches the associated function type. Example: If
RCM01 has a Data block Phase:Phase1, RCM01 can be configured as the function
reference only if Phase type is configured as Phase:Phase1.

8.146 FWINVALIDA

Specific to All PM I/O Modules


Block(s)
Description Module Firmware Not IOLIM Compatible. Shows that the firmware in the
associated channel A IOM is not compatible with I/O Link Interface Module
(IOLIM).
Data Type Boolean
Range Off (0): Ok On (1): IOM firmware is not IOLIM compatible.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM
Related N/A
Parameters
Remarks The incompatible IOM cannot be commanded to RUN through the Monitoring
mode in Control Builder.

- 1136 -
Chapter 8 - Fxxxx Parameters

8.147 FWINVALIDB

Specific to All PM I/O Modules


Block(s)
Description Module Firmware Not IOLIM Compatible. Shows that the firmware in the
associated channel B IOM is not compatible with I/O Link Interface Module
(IOLIM).
Data Type Boolean
Range Off (0): Ok On (1): IOM firmware is not IOLIM compatible.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks The incompatible IOM cannot be commanded to RUN through the Monitoring
mode in Control Builder.

8.148 FWREVISION

Specific to FTEB and C300 FBs.


Block(s)
Description Firmware Revision
Data Type String
Range Length : 2 Characters
Default NULL
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300
Related N/A
Parameters
Remarks Factory embedded firmware revision. This differs from the boot/application image
version (which changes with firmware load) in that it reflects the revision of factory
programmed devices (for example, PLD).

- 1137 -
CHAPTER

9 GXXXX PARAMETERS

9.1 G 1140
9.2 G[1..4].ALGID 1140
9.3 G[1..4].FIRSTCOND 1141
9.4 G[1..4].NUMINPTS 1141
9.5 G[1..4].SO 1142
9.6 GAIN 1142
9.7 GAINDELAYCHANGED 1142

9.8 GAINDELAYLOCK 1143


9.9 GAINHILM 1143
9.10 GAINIMPACT 1144
9.11 GAINLOLM 1144
9.12 GAINMULTIPLIER 1144
9.13 GAINOPT 1145
9.14 GAPHILM 1145
9.15 GAPLOLM 1146
9.16 GENERATEALERTS 1146
9.17 GENERRORSTATUS 1146
9.18 GENERRORSTATUSN 1147
9.19 GCBLOCKSINCM 1148
9.20 GENSTATE 1149
9.21 GENSTATEA 1149
9.22 GENTESTACTIVE 1150
9.23 GI 1150
9.24 GLOBSCMMON 1150
9.25 GOBACKREL 1151
9.26 GOODPVHHFL 1151
9.27 GOODPVHIFL 1152
9.28 GOODPVLLFL 1152
9.29 GOODPVLOFL 1153
9.30 GOP 1153
9.31 GOPFINAL 1154
9.32 GOPREQ 1154

- 1138 -
Chapter 9 - Gxxxx Parameters

9.33 GOPSCADA 1155


9.34 GPV 1155
9.35 GPVAUTO 1156
9.36 GROSSWEIGHT[1..24] 1156
9.37 GROSSWEIGHT[1..200] 1157
9.38 GROSSWGTFEED[1..24] 1157
9.39 GROSSWGTFEED[1..200] 1158
9.40 GROUP 1158
9.41 GROUP.NUMBER 1159
9.42 GROUP.NUMPARAMS 1159
9.43 GROUP.PARAM 1160
9.44 GROUP.POSITION 1161
9.45 GSTS 1161
9.46 GWCOMMAND 1162

9.47 GWCURSUBPERIOD 1162


9.48 GwEEC 1163
9.49 GWHCIFLAG 1163
9.50 GWHOSTIPPRI 1164
9.51 GWHOSTNAMEPRI 1164
9.52 GWOPCCONNSTATUS 1165
9.53 GWOPCCONNSTR 1165
9.54 GWOPCDCPS 1165
9.55 GWOPCGETERR 1166
9.56 GWOPCGSTATE 1166
9.57 GWOPCPARAMCNT 1167
9.58 GWOPCPMONERR 1167
9.59 GWOPCPMONNAME 1167
9.60 GWOPCPMONQUAL 1168
9.61 GWOPCPMONSTR 1168
9.62 GWOPCSRVSTATE 1169
9.63 GWOPCSTERRAVG 1169
9.64 GWOPCSTERRMAX 1169
9.65 GWOPCPFERRAVG 1170
9.66 GWOPCPFERRMAX 1170
9.67 GWOPCPARAMCNT 1171
9.68 GWOPCSTOREERR 1171
9.69 GWOPCSTOREPS 1172
9.70 GWOPCVERSION 1172
9.71 GWPID 1172

- 1139 -
Chapter 9 - Gxxxx Parameters

9.72 GWRDNROLE 1173


9.73 GWSTATSRESET 1173
9.74 GWSUBPERIOD 1174
9.75 GWUTCCONVERT 1174

9.1 G

Specific to Block(s) Sel, Selreal


Description G Selector input value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

Specific to Block(s) FLOWCOMP


Description Specific Gravity Input - Shows value of the specific gravity.
Data Type Real
Range
Default 1.0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence C200, C300, ACE
Related Parameters
Remarks

9.2 G[1..4].ALGID

Specific to Block Transition


(s)
Description Gate Algorithm ID G[1].ALGID: Secondary Gate (S) Type G[2..4].ALGID: Primary
Gate (Px) Type
Data Type Enumeration CSCOALGID
Range None (0) On (1) Off (2) Connect (3) Not (4) Or (5) Nor (6) And (7) Nand (8) Xor
(9)

- 1140 -
Chapter 9 - Gxxxx Parameters

Default None (0)


Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks G[1].ALGID defines the secondary gate, G[2].ALGID through G[4] define the
primary gates.

9.3 G[1..4].FIRSTCOND

Specific to Block(s) Transition


Description Gate First Condition Handle
Data Type 32-Bit Integer
Range 0 to 10
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See G[1..4].NUMINPTS for additional information.

9.4 G[1..4].NUMINPTS

Specific to Block(s) Transition


Description Gate Number of Inputs
Data Type 32-Bit Integer
Range 0 to 10
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks See G[1..4].NUMINPTS for additional information.

- 1141 -
Chapter 9 - Gxxxx Parameters

9.5 G[1..4].SO

Specific to Block(s) Transition


Description Gate Status Output
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

9.6 GAIN

Specific to Block(s) ProfitCtl


Description Model Gain
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

9.7 GAINDELAYCHANGED

Specific to Block(s) ProfitCtl


Description Gain Delay Changed
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No

- 1142 -
Chapter 9 - Gxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters
Remarks

9.8 GAINDELAYLOCK

Specific to Block(s) ProfitCtl


Description Lock Gain Delay
Data Type INT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

9.9 GAINHILM

Specific to AutoMan, Fanout, PID, PIDER, PIDFF, PosProp, RatioCtl, RegCalc, RegSummer
Block(s)
Description Gain High Limit - Specifies upper limit for gain value. If K, K1, K2, KLIN, or
KMODIFEXT exceed this limit, they will be clamped to this limit, as applicable.
Data Type 64-Bit Real Number
Range Any value greater than GAINLOLM.
Default 240.00
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related GAINLOLM, K, K1KLIN, KMODIFEXT
Parameters
Remarks

- 1143 -
Chapter 9 - Gxxxx Parameters

9.10 GAINIMPACT

Specific to Block(s) ProfitCtl


Description Gain Impact
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

9.11 GAINLOLM

Specific to AutoMan, Fanout, PID, PIDER, PIDFF, PosProp, RatioCtl, RegCalc, RegSummer
Block(s)
Description Gain Low Limit - Specifies the lower limit for the gain value. If K, K1, K2, KLIN, or
KMODIFEXT go below this limit, they will be clamped to this limit
Data Type 64-Bit Real Number
Range Any value less than GAINHILM.
Default 0.00
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related GAINHILM, K, KLIN, KMODIFEXT
Parameters
Remarks

9.12 GAINMULTIPLIER

Specific to Block(s) ProfitCtl


Description Gain Multiplier
Data Type FLOAT64
Range NA
Default 1
Config Load Yes

- 1144 -
Chapter 9 - Gxxxx Parameters

Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

9.13 GAINOPT

Specific to Block PID, PIDFF


(s)
Description Gain Option. Specifies how the PID gain should be calculated.
Data Type Enumeration GAINOPT
Range Lin (0): Linear Gain Gap (1): Gap Gain Nonlin (2): Nonlinear Gain Ext (3):
External Gain
Default Lin (0)
Config Load Yes
Active Loadable No
Access Lock Engineer/Application Developer
Residence CEE
Related
Parameters
Remarks

9.14 GAPHILM

Specific to Block(s) PID, PIDFF


Description Gap High Limit. Used if GAINOPT = Gap (configured).
Data Type 64-Bit Real Number
Range N/A
Default 0.00
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 1145 -
Chapter 9 - Gxxxx Parameters

9.15 GAPLOLM

Specific to Block(s) PID, PIDFF


Description Gap Low Limit. Used if GAINOPT = Gap (configured).
Data Type 64-Bit Real Number
Range N/A
Default 0.00
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

9.16 GENERATEALERTS

Specific to Block(s) SCM/RCM


Description Generate Alerts Flag
Data Type Boolean
Range 0 Off Does not generate alerts
1 On Generates alerts
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

9.17 GENERRORSTATUS

Specific to EIP IO, E3, E3+, PF755 Drive.


Block(s)
Description General Error Status: When the connection between a EIP device and c300 fails,
this Parameter provides an error code to identify the reason for failure.
Data Type STRING
Range -
Default 0x0
Config Load No

- 1146 -
Chapter 9 - Gxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related EXTERRORSTATUS
Parameters
Remarks l General Error Status: This will be one of the below:
1. EIMEIP_TAG_GEN_STS_GOOD (0x00)
2. EIMEIP_TAG_GEN_STS_BAD (0xFF) – Internal Error
3. General CIP Error Code returned by the CLx – this will found in the CIP Spec
Document
#define EIMEIP_TAG_GENSTS_BAD 0xFF #define EIMEIP_TAG_GENSTS_GOOD 0
l Extended Error Status: This will be one of the below:
1. EIMEIP_TAG_EXT_STS_GOOD (0x00)
2. 0x01 to 0xFF : Internal Error codes (see below list)
3. Extended CIP Error Code returned by the CLx – this will found in the CIP
Spec Document
kEIMSwitchoverExtSt = 1, kTagReadDataSizeZeroExtSt,
kTagReadTooLargeDataSizeExtSt, kEIMConnectionLostExtSt,
kTagReadSendFailedExtSt, kTagReadInvalidCfgStateExtSt, kTagReadStaleData

9.18 GENERRORSTATUSN

Specific to Block(s) All EIP IOM/Devices/Drives and EIP Generic adapter.


Description General Error Status Number
Data Type INT32
Range N/A
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EXTERRORSTATUSN, GENERRORSTATUS, EXTERRORSTATUS
Remarks

- 1147 -
Chapter 9 - Gxxxx Parameters

Specific to Block All EIP IOM/Devices/Drives and EIP Generic adapter and 1738-AENT.
(s)
Description General Error Status Number
Data Type INT32
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related EXTERRORSTATUSN, GENERRORSTATUS, EXTERRORSTATUS,
Parameters IOCONNSTATUS, IOCONNEXTSTS
Remarks General Error Status: This will be one of the below:
1. 0 (Good Status)
2. 255 (Internal Error Condition)
3. General CIP Error Code returned by the CLx – this will found in the CIP
Spec Document.

9.19 GCBLOCKSINCM

Specific to GRPCAPRBK
Block(s)
Description Number of blocks in CM for System Detail Display.
Data Type INT8
Range 1 and above.
Default 1
Config Load YES
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks This parameter is used in system detail display to display only this number of
blocks and hide the not required blocks.

- 1148 -
Chapter 9 - Gxxxx Parameters

9.20 GENSTATE

Specific to RM
Block(s)
Description General State of the Redundancy Module
Data Type Enumeration
Range Undefined (0) Startup (1) Reload (2) Fault (3) Ok (4)
Default Undefined (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

9.21 GENSTATEA

Specific to RM
Block(s)
Description RM Module General State. For each module in the host chassis, general state of
module
Data Type Enumeration [20]
Range Undefined (0) Startup (1) Reload (2) Fault (3) Ok (4)
Default Undefined (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 1149 -
Chapter 9 - Gxxxx Parameters

9.22 GENTESTACTIVE

Specific to C300, PGM, EHPM


Block(s)
Description Traffic Generation Test Status
Data Type Boolean
Range On (1) Off (0)
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, PGM, EHPM
Related
Parameters
Remarks This parameter Indicates whether the traffic generation test is active. When ‘On’
the detailed status can be viewed through module tool.

9.23 GI

Specific to Block(s) EIM


Description Initiate GI
Data Type BOOL
Range NA
Default 0
Config Load
Active Loadable No
Access Lock Engineer
Residence NOLOAD
Related Parameters
Remarks

9.24 GLOBSCMMON

Specific to Block(s) All blocks


Description This parameter is used to monitor the global SCM.
Data Type Structure
Range
Default

- 1150 -
Chapter 9 - Gxxxx Parameters

Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence No Load
Related Parameters
Remarks

9.25 GOBACKREL

Specific to C200,,C300, PGM, EHG, LIOM, FIM, FIM4, IOLIM, FTEB, EHPM, UOC. ACE, SIM-
Block(s) C200, RM, 1757-SRM, SIMIOLIM, TC-IAH061(1756-IF6I), TC-IAH161(1756-IF16),
TC-IDJ161(1756-IB16I), TC-IDK161(1756-IB16I), TC-IDW161(1756-IM16I), TC-
IXL061(1756-IT6I), TC-IXL062(1756-IT6I2), TC-IXR061(1756-IR6I), TC-OAH061
(1756-OF6CI), TC-OAV061(1756-OF6VI), TC-OAV081(1756-OF8), TC-ODJ161(1756-
OB16I), TC-ODK161(1756-OA16I), TC-ORC081(1756-OX8I), TC-ORC161(1756-
OW16I), TC-IDD321(1756-IB32/B), TC-ODD321(1756-OB32), TC-IDA161(1756-IA16),
TC-ODA161(1756-OB16I), TC-MUX021, TC_MUX021, TC-ODX081(1756-OA8D), TC-
ODX161(1756-OB16D), TC-IDX081(1756-IA8D), TC-IDX161(1756-IB16D), TC-
PIL081, TC-POB041, 1797-IE8NF, 1797-IBN16, 1797-IRT8, 1797-OE8, 1797-OB4D,
TC-MDP081, 1757-PIM, 1794-IA8, 1794-IB16, 1794-IE8, 1794-IR8, 1794-IT8, 1794-
OA8, 1794-OB16P, 1794-OE4, 1794-OW8, JAGXTERM, QIPACTERM
Description Previous DB Release
Data Type String
Range Na
Default Na
Config NOLOAD, No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence SR, NOLOAD
Related Na
Parameters
Remarks This parameter is not used in Saturn Release

9.26 GOODPVHHFL

Specific to Block(s) Analog input and DACA


Description Good PV and High High Condition Flag
Data Type Boolean
Range OFF, ON
Default OFF

- 1151 -
Chapter 9 - Gxxxx Parameters

Config Load YES


Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters BADPVPVHHALM.FL
Remarks This will be AND of the NOT of BADPV alarm Flag and the PVHH alarm Flag

9.27 GOODPVHIFL

Specific to Block(s) Analog Input and DACA


Description Good PV and High Condition Flag
Data Type Boolean
Range OFF, ON
Default OFF
Config Load YES
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters BADPVPVHIALM.FL
Remarks This will be AND of the NOT of BADPV alarm Flag and the PVHI alarm Flag

9.28 GOODPVLLFL

Specific to Block(s) Analog Input and DACA FB


Description Good PV and Low Low Condition Flag
Data Type Boolean
Range OFF, ON
Default OFF
Config Load YES
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters BADPVPVLLALM.FL
Remarks This will be AND of the NOT of BADPV alarm Flag and the PVLL alarm Flag

- 1152 -
Chapter 9 - Gxxxx Parameters

9.29 GOODPVLOFL

Specific to Block(s) Analog Input and DACA


Description Good PV and Low Condition Flag
Data Type Boolean
Range OFF, ON
Default OFF
Config Load YES
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters BADPVPVLOALM.FL
Remarks This will be AND of the NOT of BADPV alarm Flag and the PVLO alarm Flag

9.30 GOP

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Generic Output (OP)
Data Type Enumeration GENSTATE
Range Active (2): Not configured SafeOP for two state device (that is, if
SafeOp = State 0, Active will set OP to state 1).
Safe (3): The state nominated as the SafeOP state on the
State Assignment form.
S0 (4): State zero as defined on the State Assignment form.

S1 (5): State one as defined on the State Assignment form.


S2 (6): State two as defined on the State Assignment form.
Only applicable for DEVCTL and VALVEDAMPER
blocks.
Default S0 (4)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related GOPFINAL, GOPREQ, MODEATTR, OP, OPFINAL, OPREQ, SAFEOP, SAFEREDTAG.
Parameters DEVCTL Only: NUMDOUTS, NUMSTATES.
Remarks Once SAFEOP is configured, GOP always defaults to SAFEOP. DEVCTL Only:
l Access is illegal if NUMDOUTS = 0.
l S2 is illegal if NUMSTATES = 2.
l Active is illegal if NUMSTATES = 3.

- 1153 -
Chapter 9 - Gxxxx Parameters

9.31 GOPFINAL

Specific to Block DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


(s)
Description Generic Field Output State (OPFINAL)
Data Type Enumeration GENSTATE
Range S0 (4) S1 (5) S2 (6) Only applicable for DEVCTL and VALVEDAMPER blocks.
Default S0 (4)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related GOP, MODEATTROP, OPFINAL. DEVCTL Only: NUMDOUTS, NUMSTATES,
Parameters OPDOMAP[0..3][1..3] .
Remarks DEVCTL Only: Access is illegal, if NUMDOUTS = 0.

9.32 GOPREQ

Specific to Block(s) DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Generic Requested Output Value (OPREQ)
Data Type Enumeration GENSTATE
Range Null (0) Active (2) Safe (3) S0 (4) S1 (5) S2 (6)
Default Null (0)
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related CONTROLREQ, GOP, OP, OPREQ, OPTYPE, SCMOPT. DEVCTL Only: 0
Parameters NUMSTATES,
Remarks DEVCTL Only: S2 is illegal if NUMSTATES = 2.

- 1154 -
Chapter 9 - Gxxxx Parameters

9.33 GOPSCADA

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Generic Output for Experion PKS server detail displays - This parameter represents
the three user-defined states so that they may be represented clearly in the detail
displays.
Data Type Enumeration GENSTATESC
Range State_0 (0) State_1 (1) State_2 (2)
Default State_0 (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related GOP, OP.
Parameters
Remarks

9.34 GPV

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Generic Process Variable (PV)
Data Type Enumeration GENSTATE
Range Null (0) Inbet (1) S0 (4) For DEVCTL Only S1 (5) S2 (6)
Default Null (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly, Other Function Block (see Remarks)
Residence CEE
Related GPVAUTO, PV, PVAUTO, PVSOURCE, PVSRCOPT. DEVCTL Only: DIMODEDIPVMAP
Parameters [0..15], NUMDINPUTS, NUMSTATES.
Remarks Access Lock is ViewOnly if PVSOURCE = AUTO, MAN or TRACK; or if PVSRCOPT is
ONLYAUTO.
DEVCTL Only:
l Access is illegal, if NUMDINPUTS = 0.
l S2 is illegal, if NUMSTATES = 2.
l InBet is illegal, if DIPVMAP is not assigned to InBet.
l Access Lock is Other Function Block if PVSOURCE = SUB.

- 1155 -
Chapter 9 - Gxxxx Parameters

9.35 GPVAUTO

Specific to Block DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


(s)
Description Generic PVAUTO
Data Type Enumeration GENSTATE
Range Null (0) Inbet (1) S0 (4) For DEVCTL Only S1 (5) S2 (6)
Default Null (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related GPV, PV, PVAUTO, PVSOURCE. DEVCTL Only: DIMODEDIPVMAP[0..15],
Parameters NUMDINPUTS, NUMSTATES.
Remarks DEVCTL Only:
l Access is illegal, if NUMDINPUTS = 0.
l S2 is illegal, if NUMSTATES = 2.
l InBet is illegal, if DIPVMAP is not assigned to InBet.

9.36 GROSSWEIGHT[1..24]

Specific to QIPACTERM
Block
Description Gross Weight
Data Type Float64
Range N/A
Default NAN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks For scales, this is the gross weight. For flow meters, this is the same as feed weight.
This is the value in the input assembly for the designated position [1-24].

- 1156 -
Chapter 9 - Gxxxx Parameters

9.37 GROSSWEIGHT[1..200]

Specific to QIPACCHAN
Block
Description Gross Weight
Data Type Float64
Range N/A
Default NAN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks For scales, this is the gross weight. For flow meters, this is the same as feed weight.
This is the value in the input assembly for the designated channel [1-200] in the
QiMPACT cluster.

9.38 GROSSWGTFEED[1..24]

Specific to Block QIPACTERM


Description Gross Weight Feed
Data Type Boolean
Range Off(0) Not Gross Weight Feed
On(1) Gross Weight Feed
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 3 of the Status 2 word in the input assembly for the
designated position [1-24].

- 1157 -
Chapter 9 - Gxxxx Parameters

9.39 GROSSWGTFEED[1..200]

Specific to QIPACCHAN
Block
Description Gross Weight Feed
Data Type Boolean
Range Off(0) Not Gross Weight Feed
On(1) Gross Weight Feed
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 3 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

9.40 GROUP

Specific to Block(s) Common to most blocks


Description Group Configuration
Data Type Structure
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The collection of group configuration information associated with a
parameter.

Specific to Block Common to most blocks, UOC


(s)
Description Group Configuration
Data Type STRUCTDATA
Range N/A
Default N/A
Config Load No, Yes

- 1158 -
Chapter 9 - Gxxxx Parameters

Active Loadable No
Access Lock Application Developer, APPDEVONLY
Residence Server, SCAN
Related
Parameters
Remarks The collection of group configuration information associated with a
parameter.

9.41 GROUP.NUMBER

Specific to Block(s) Common to most blocks, UOC


Description Group Number
Data Type 32-Bit Integer
Range 0 to 3000, ±2147483647
Default 0
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server, SCAN
Related Parameters
Remarks The desired Group # to be associated with this group parameter.

9.42 GROUP.NUMPARAMS

Specific to Block Common to most blocks


(s)
Description Number of Group Parameters
Data Type 16-Bit Integer
Range 1 to 25
Default 5
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The number (1 to 25) of group parameters to be included in the Groups
Configuration table.

- 1159 -
Chapter 9 - Gxxxx Parameters

Specific to Block(s) UOC


Description Number of Group parameters
Data Type INT16
Range ±32767
Default 5
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

9.43 GROUP.PARAM

Specific to Common to most blocks


Block(s)
Description Group Parameter
Data Type PARAMID
Range N/A
Default N/A
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks A valid parameter name for a parameter associated with the given point that is
configured in the system.

Specific to Block(s) UOC


Description Group Parameter
Data Type PARAMID
Range
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

- 1160 -
Chapter 9 - Gxxxx Parameters

9.44 GROUP.POSITION

Specific to Block Common to most blocks


(s)
Description Group Position
Data Type INT8
Range 1 to 8
Default 1
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The number of the position the configured parameter will occupy in the
Station Group display.

Specific to Block(s) UOC


Description Group Position
Data Type INT8
Range ±127
Default 1
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

9.45 GSTS

Specific to Block FLOWCOMP


(s)
Description Specific Gravity Input Value Status - Indicates the current status of G (Gravity)

Data Type Enumeration PVVALSTS


Range Bad (0): The value is bad and has been replaced
with NaN.
Uncertn (1): The status of the value is uncertain.
Normal (2): The value is good.
Manual (3): The value was manually stored.
Default Normal

- 1161 -
Chapter 9 - Gxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE/CPM
Related G, COMPTERM
Parameters
Remarks

9.46 GWCOMMAND

Specific to OPC, ICG


Block(s)
Description Gateway Command - Initiate a command to OPC Gateway or Inter Cluster
Gateway in Monitoring mode.
Data Type Enumeration opcgcommand
Range None (0)
Shutdown (1)
Idle (2)
Run (3)
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence ACE
Related
Parameters
Remarks

9.47 GWCURSUBPERIOD

Specific to Block(s) OPC, ICG


Description Current OPC Subscription Rate
Data Type Enumeration
Range 1 to 30 seconds DEFAULT (0) 10 sec (10)
1 sec (7) 15 sec (11)
2 sec (8) 30 sec (12)
5 sec (9)
Default DEFAULT (0)
Config Load No

- 1162 -
Chapter 9 - Gxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

9.48 GwEEC

Specific to Block OPC Gateway (OPCG) block, Intercluster Gateway (ICG) block
Description Gateway EEC
Data Type UINT16
Range
Default 0
Config Load No
Active Loadable No
Access Lock Engineer
Residence OPC Gateway
Related Parameters
Remarks The value of this parameter updated while loading the OPCG/ICG.

9.49 GWHCIFLAG

Specific to Block OPC, ICG


(s)
Description Gateway Honeywell Communications Infrastructure (HCI) Flag - Indicates
condition of HCI function.
Data Type Boolean
Range Off On
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

- 1163 -
Chapter 9 - Gxxxx Parameters

9.50 GWHOSTIPPRI

Specific to OPC, ICG


Block(s)
Description Gatewayt Host IP for Primary - Specifies the Internet Protocol (IP) address for the
node hosting the gateway.
Data Type String
Range
Default
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence SR
Related GWHOSTNAMEPRI
Parameters
Remarks Using an IP address instead of the host name results in a more robust and least
error prone communication path configuration between the Server and the given
node.

9.51 GWHOSTNAMEPRI

Specific to Block OPC, ICG


(s)
Description Gateway Host Name for Primary - Specifies the network name for the node
hosting the gateway.
Data Type String
Range
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related GWHOSTIPPRI
Parameters
Remarks

- 1164 -
Chapter 9 - Gxxxx Parameters

9.52 GWOPCCONNSTATUS

Specific to Block(s) OPC, ICG


Description Gateway OPC Connection Status - Indicates current status of OPC
connection.
Data Type Enumeration connstatus
Range
Default NoState
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

9.53 GWOPCCONNSTR

Specific to Block(s) OPC, ICG


Description Gateway OPC Connection String - Indicates applicable string for OPC
connection.
Data Type String
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

9.54 GWOPCDCPS

Specific to Block(s) OPC, ICG


Description Gateway OPC Data Change Rate
Data Type Float64
Range
Default 0

- 1165 -
Chapter 9 - Gxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

9.55 GWOPCGETERR

Specific to Block(s) OPC, ICG


Description Gateway OPC Get (Read) Error
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

9.56 GWOPCGSTATE

Specific to OPC, ICG


Block(s)
Description Gateway OPC Gateway State - The current state of the OPC Gateway (Idle,
Active, and so on)
Data Type Enumeration
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence OPC Gateway
Related GWCOMMAND
Parameter
Remarks The state parameter is set based on the issued command (GWCommand) and is
similar to that of an ACE.

- 1166 -
Chapter 9 - Gxxxx Parameters

9.57 GWOPCPARAMCNT

Description Gateway OPC Parameter Count


Data Type 32-Bit Integer
Range
Default 0
Configuration/Load No
Active Loadable No
Access Lock View Only
Residence
Related Parameters
Remarks This parameter displays the number of parameters that are subscribing to
the OPC server. This count returns only the number of parameters that
have an active subscription using PUBSUB. It does not consider the
number of stores or the number of PREFETCH parameters. The number of
PREFETCH parameters can be monitored using the PFREQAVG and
PFREQMAX parameters.

9.58 GWOPCPMONERR

Specific to Block(s) OPC, ICG


Description Gateway OPC Parameter Monitor Error
Data Type String
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

9.59 GWOPCPMONNAME

Specific to Block(s) OPC, ICG


Description Gateway OPC Parameter Monitor Name
Data Type String
Range
Default
Config Load Yes

- 1167 -
Chapter 9 - Gxxxx Parameters

Active Loadable No
Access Lock Application Developer Only
Residence
Related Parameters
Remarks

9.60 GWOPCPMONQUAL

Specific to Block(s) OPC, ICG


Description Gateway OPC Parameter Monitor Quality
Data Type Enumeration OPCQuality
Range
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence
Related Parameters
Remarks

9.61 GWOPCPMONSTR

Specific to Block(s) OPC, ICG


Description Gateway OPC Parameter Monitor String
Data Type String
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 1168 -
Chapter 9 - Gxxxx Parameters

9.62 GWOPCSRVSTATE

Specific to Block(s) OPC, ICG


Description Gateway OPC Server State - Indicates current state of server.
Data Type Enumeration opcserverstate
Range
Default NoConfig
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

9.63 GWOPCSTERRAVG

Description Gateway OPC Store (write) Error Average


Data Type FLOAT32
Range
Default 0
Configuration/Load No
Active Loadable No
Access Lock View Only
Residence
Related Parameters GWOPCSTOREERR
Remarks This parameter displays a running time average of store errors per second.
The parameter is set to zero when the any one of the following condition
occurs.
l STATSRESET is stored.
l The OPC Gateway state transitions changes from “IDLE”to “RUN”.

9.64 GWOPCSTERRMAX

Description Gateway OPC Store (write) Error Maximum


Data Type 32-Bit Integer
Range
Default 0
Configuration/Load No
Active Loadable No

- 1169 -
Chapter 9 - Gxxxx Parameters

Access Lock View Only


Residence
Related Parameters GWOPCSTOREERR
Remarks This parameter displays a historical maximum of store/write errors per
second. The parameter is set to zero when the any one of the following
condition occurs.
l STATSRESET is stored.
l The OPC Gateway state transitions changes from “IDLE”to “RUN”.

9.65 GWOPCPFERRAVG

Description Gateway OPC Prefetch Errors Average


Data Type FLOAT32
Range
Default 0
Configuration/Load No
Active Loadable No
Access Lock View Only
Residence
Related Parameters
Remarks This parameter displays a running time average of Prefetch errors per
second. The parameter is set to zero when the any one of the following
condition occurs.
l STATSRESET is stored.
l The OPC Gateway state transitions changes from “IDLE”to “RUN”.

9.66 GWOPCPFERRMAX

Description Gateway OPC Prefetch Errors Maximum


Data Type 32-bit integer
Range
Default 0
Configuration/Load No
Active Loadable No

- 1170 -
Chapter 9 - Gxxxx Parameters

Access Lock
Residence View Only
Related Parameters
Remarks This parameter displays historical maximum of Prefetch read errors per
second. The parameter is set to zero when the any one of the following
condition occurs.
l STATSRESET is stored.
l The OPC Gateway state transitions changes from “IDLE”to “RUN”.

9.67 GWOPCPARAMCNT

Description Gateway OPC Parameter Count


Data Type 32-Bit Integer
Range
Default 0
Configuration/Load No
Active Loadable No
Access Lock View Only
Residence
Related Parameters
Remarks This parameter displays the number of parameters that are subscribing to
the OPC server. This count returns only the number of parameters that
have an active subscription using PUBSUB. It does not consider the
number of stores or the number of PREFETCH parameters. The number of
PREFETCH parameters can be monitored using the PFREQAVG and
PFREQMAX parameters.

9.68 GWOPCSTOREERR

Specific to Block(s) OPC, ICG


Description Gateway OPC Store (write) Error
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 1171 -
Chapter 9 - Gxxxx Parameters

9.69 GWOPCSTOREPS

Specific to Block(s) OPC, ICG


Description Gateway OPC Store Rate
Data Type Float64
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

9.70 GWOPCVERSION

Specific to Block(s) OPC, ICG


Description Gateway OPC Version - Indicates version of OPC in use.
Data Type Float64
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

9.71 GWPID

Specific to Block(s) OPC


Description Gateway Process ID
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No

- 1172 -
Chapter 9 - Gxxxx Parameters

Access Lock ViewOnly


Residence
Related Parameters
Remarks

9.72 GWRDNROLE

Specific to
Block OPC Gateway (OPCG) block, Intercluster Gateway (ICG) block
Description Gateway Cut Over Role
Data Type ENUMERATION
(1) Undefined
(4) NonRedundant
(5) Primary
Range (6) Secondary
Default (5) Primary
Config
Load No
Active
Loadable No
Access Lock AppDevOnly
Residence OPC Gateway
Related
Parameters

BlockExtn sets this parameter as "Primary" when you create OPCG/ICG and as
"Secondary" when the migration tool creates backup OPCG/ICG. During the switch-
over, the OPCG/ICG role is changed and the parameter state is changed by RRM.

ATTENTION This parameter is ViewOnly for users.


Remarks

9.73 GWSTATSRESET

Specific to Block(s) OPC, ICG


Description Gateway Statistics Reset - Resets alI Gateway statistics.
Data Type Boolean
Range 0 = Off
1 = On
Default Off (0)
Config Load No

- 1173 -
Chapter 9 - Gxxxx Parameters

Active Loadable No
Access Lock Operator
Residence ACE
Related Parameters
Remarks

9.74 GWSUBPERIOD

Specific to OPC, ICG


Block(s)
Description OPC Subscription Rate for Peer-to-Peer communications between nodes.
Data Type Enumeration
Range 1 to 30 seconds DEFAULT (0) 10 sec (10)
1 sec (7) 15 sec (11)
2 sec (8) 30 sec (12)
5 sec (9)
Default DEFAULT (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks GWSUBPERIOD alone determines the OPC subscription period of OPC items and is
not influence at all by the Control Module PERIOD setting.

9.75 GWUTCCONVERT

Specific to OPC , ICG


Block(s)
Description Gateway Universal Time (UTC) Convert - Select if Gateway is to convert all VT_
DATE variable types to UTC.
Data Type Boolean
Range Off On
Default Off
Config Load Yes
Active No
Loadable

- 1174 -
Chapter 9 - Gxxxx Parameters

Access Lock Application Developer Only


Residence ACE
Related
Parameters
Remarks

- 1175 -
CHAPTER

10 HXXXX PARAMETERS

10.1 HALMENABLE 1181


10.2 HANDLER 1182
10.3 HANDLERREF 1182
10.4 HANDLETIMEOUT 1182
10.5 HARDFAIL 1183
10.6 HARDWAREREV[0..7] 1183
10.7 HART[0..7] 1184

10.8 HARTENABLE 1184


10.9 HARTIPENABLE 1185
10.10 HARTSUPPORT 1185
10.11 HARTVERSION 1185
10.12 HAUTODET[1..16] 1186
10.13 HCFGDEV 1187
10.14 HCFGDEVTMPL 1188
10.15 HCMD00 1188
10.16 HCMD12 1189
10.17 HCMD13 1189
10.18 HCMD14 1190
10.19 HCMD16 1190
10.20 HCMD48BT[1..200] 1191
10.21 HCMD48NOTIFY[1..200] 1191
10.22 HCMD48STRNGS[1..200] 1192
10.23 HCMDFAIL 1192
10.24 HCMDFAILFL 1193
10.25 HCMDRESPRDYFL_AI_S 1194
10.26 HCMDRESPRDYFL_AO_S 1194
10.27 HCOMERFL 1195
10.28 HCOMFAIL 1195
10.29 HCOMHYS 1196
10.30 HCOMSTS 1197
10.31 HCOMTHRS 1197
10.32 HCUAVAIL 1198

- 1176 -
Chapter 10 - Hxxxx Parameters

10.33 HCUAVAIL2 1198


10.34 HDAY 1199
10.35 HDESC 1200
10.36 HDEVID 1200
10.37 HDEVIDCD[1..16] 1201
10.38 HDEVIDFL 1201
10.39 HDEVMFG 1202
10.40 HDEVMISM 1202
10.41 HDEVMSG 1203
10.42 HDEVPROFILE 1203
10.43 HDEVREV 1204
10.44 HDEVST 1204
10.45 HDEVSTSTATUS 1205
10.46 HDEVSTS_AI_S 1206

10.47 HDEVSTS_AO_S 1207


10.48 HDEVTYPE 1207
10.49 HDEVTYPE7 1208
10.50 HDEVTYPENAME 1208
10.51 HDVMFGCD 1209
10.52 HDVMFGCD7 1209
10.53 HDVREVCD 1210
10.54 HDVTYPCD 1210
10.55 HDVTYPCD7 1211
10.56 HDVTYPCDNAME 1211
10.57 HDWREV[1..8] 1212
10.58 HDWREV1 [1...15] through HDWREV8 [1...15] 1212
10.59 HDYNCC[1..4] 1213
10.60 HDYNDESC[1..4] 1213
10.61 HDYNDSC 1214
10.62 HDYNDVC[1..4] 1215
10.63 HDYNEU[1..4] 1215
10.64 HDYNNAME[1..4] 1216
10.65 HDYNST[1..4] 1216
10.66 HDYNVAL[1..4] 1218
10.67 HEADERID 1218
10.68 HEADERREVISION 1218
10.69 HEADERVERSION 1219
10.70 HEAPMEM 1219
10.71 HelpTxt1 1220

- 1177 -
Chapter 10 - Hxxxx Parameters

10.72 HENABLE 1220


10.73 HENABLE_AI_C 1221
10.74 HENABLE_AO_C 1221
10.75 HEU 1222
10.76 HEXCOMERRSFL 1222
10.77 HEXTDEVST 1223
10.78 HFASSYNO 1223
10.79 HFLAGS 1224
10.80 HHWREV 1225
10.81 HIST.TYPE 1225
10.82 HIALM 1225
10.83 HIALM.PR 1226
10.84 HIALM.SV 1227
10.85 HIALM.TYPE 1227

10.86 HIGHAL 1230


10.87 HIGHENG[0..numChans-1] 1230
10.88 HIGHENG[0..7] 1231
10.89 HIGHSIGNAL[0..numChans-1] 1231
10.90 HIGHSIGNAL[0..7] 1232
10.91 HILMRAMPRATE 1233
10.92 HIOPLHFSTA 1234
10.93 HIOPLHFSTB 1235
10.94 HISHART5 1235
10.95 HIST.STDPHDCOLLRATE 1236
10.96 HIST.EXCPHDCOLLRATE 1236
10.97 HIST.EXTDPHDCOLLRATE 1237
10.98 HIST.FASTPHDCOLLRATE 1238
10.99 HIST 1239
10.100 HISTDESC 1239
10.101 HISTEUDESC[1..50] 1240
10.102 HIST.EXC 1240
10.103 HIST.EXCCOLLRATE 1241
10.104 HIST.EXCOFFSET 1242
10.105 HIST.EXTD 1243
10.106 HIST.FAST 1243
10.107 HIST.FASTCOLLRATE 1244
10.108 HIST.GATEPARAM 1245
10.109 HIST.GATESTRING 1245
10.110 HIST.GATEVALUE 1246

- 1178 -
Chapter 10 - Hxxxx Parameters

10.111 HIST.NUMPARAMS 1247


10.112 HIST.PARAM 1248
10.113 HIST.STD 1248
10.114 HIST.STDCOLLRATE 1249
10.115 HIST.STDOFFSET 1250
10.116 HISTTYPE[1..50] 1251
10.117 HISTVALUE[1..50] 1251
10.118 HISTVALUEMAX[1..50] 1252
10.119 HISTVALUEMIN[1..50] 1252
10.120 HLOCKBYPRIMARYMASTER (HART Revision 6.0 and later) 1253
10.121 HLOCKPERMANENT (HART Revision 6.0 and later) 1253
10.122 HLOCKSTATUS (HART Revision 6.0 and later) 1254
10.123 HLONGTAG 1254
10.124 HMAINTREQ (HART Revision 6.0 and later) 1255

10.125 HMAXDEVVARS (HART Revision 6.0 and later) 1255


10.126 HMONTH 1256
10.127 HMPORTACTIVE 1256
10.128 HMW 1256
10.129 HNCFGCHG (HART Revision 6.0 and later) 1257
10.130 HNCOMERR 1257
10.131 HNMSMINPRE 1258
10.132 HNSMMINPRE (HART Revision 6.0 and later) 1258
10.133 HOLDALM.FL 1259
10.134 HOLDALM.PR 1259
10.135 HOLDALM.SV 1260
10.136 HOLDBRTHTM 1260
10.137 HOLDBRTHTP 1261
10.138 HOLDCMD 1261
10.139 HOLDOPT 1262
10.140 HOLDSTEPPER 1263
10.141 HOLDVAL 1263
10.142 HOSTIPPRI 1264
10.143 HOSTNAME 1265
10.144 HOSTNAMEPRI 1265
10.145 HOSTSOESTS 1267
10.146 HOUR 1267
10.147 HPHYSIG 1268
10.148 HPM_CNTRLPERSREV 1268
10.149 HPM_CNTRLPERSVER 1269

- 1179 -
Chapter 10 - Hxxxx Parameters

10.150 HPM_COMMPERSREV 1269


10.151 HPM_COMMPERSVER 1269
10.152 HPM_FWREV 1270
10.153 HPM_HWREV 1270
10.154 HPM_IOL_HWREV 1271
10.155 HPMNODENO 1271
10.156 HPMSOFTFAIL 1272
10.157 HPVALMCODE 1272
10.158 HPVCHAR 1273
10.159 HPVCHNFLAGS 1273
10.160 HPVDAMP 1274
10.161 HPVLRV 1274
10.162 HPVMISM 1275
10.163 HPVTLDST 1275

10.164 HPVURV 1276


10.165 HPVXFRCODE 1277
10.166 HREVMISM 1277
10.167 HSCANCFG 1278
10.168 HSCANOVR 1281
10.169 HSCANTIME 1281
10.170 HSLOT0TS 1282
10.171 HSLOTCC [1..HSLOTVARIDX] (HART Revision 6.0 and later) 1282
10.172 HSLOTDSC[1..HSLOTVARIDX] 1283
10.173 HSLOTDVC[1..HSLOTVARIDX] 1283
10.174 HSLOTEU[1..8] 1284
10.175 HSLOTNAME[1..HSLOTVARIDX] 1284
10.176 HSLOTST [1..HSLOTVARIDX] (HART Revision 6.0 and later) 1285
10.177 HSLOTVAL [1..HSLOTVARIDX] 1286
10.178 HSMSTRFL 1286
10.179 HSTLANIDERRS 1287
10.180 HSLOTVARIDX 1287
10.181 HSWDESC [0..63] 1288
10.182 HSWREV 1288
10.183 HWREVMAJ 1288
10.184 HWREVMIN 1289
10.185 HSWVALUE [0..63] 1289
10.186 HWTYPE 1290
10.187 HWYNUM 1290
10.188 HWYNUM1 1291

- 1180 -
Chapter 10 - Hxxxx Parameters

10.189 HWYNUM2 1291


10.190 HWYNUMADDED 1292
10.191 HWYNUMPRT 1292
10.192 HWYNUMTHIS 1293
10.193 HTAG 1293
10.194 HTDEU 1294
10.195 HTDLRL 1294
10.196 HTDMINSPAN 1295
10.197 HTDSN 1295
10.198 HTDURL 1295
10.199 HUCMDREV 1296
10.200 HVARALERT (HART Revision 6.0 and later) 1296
10.201 HWFAULT 1297
10.202 HWFAULT[0..numChans-1] 1297

10.203 HWREVMAJ 1298


10.204 HWREVMIN 1299
10.205 HWRTPRCTCODE 1300
10.206 HWTEMP 1301
10.207 HYEAR 1301
10.208 HelpTxt1 1301

10.1 HALMENABLE

Specific to Block(s) EIP IOPOINT AI or AO, it is not applicable for DI or DO

Description Alarm Enable

Data Type BOOLEAN

Range True or False

Default True

Config Load Yes

Active Loadable Yes

Access Lock Operator

Residence CEEAL

Related Parameters N/A

Remarks User can enable or disable alarms for HART notifications

- 1181 -
Chapter 10 - Hxxxx Parameters

10.2 HANDLER

Specific to Block(s) Step, Transition, Handler


Description Contains the name of the Handler that Transition or Step belongs to.
Data Type BlockId
Range N/A
Default Null String
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUM
Remarks

10.3 HANDLERREF

Specific to Block(s) Handler, Step, Transition


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

10.4 HANDLETIMEOUT

Specific to Chassis HART AI IOM


Block(s)
Description Handle Timeout - Specifies the time (in seconds) that the IO card will hold the
response message for a handle. The handle is a token given out when the gateway
cannot service an unconnected message.
Data Type 32-Bit Integer
Range 1 to 255
Default 4 seconds
Config Yes
Load

- 1182 -
Chapter 10 - Hxxxx Parameters

Active No
Loadable
Access Application Developer Only
Lock
Residence CEE
Related
Parameters
Remarks When an unconnected message is sent to the IO module, the IO module may not
respond immediately. In this case, the IO module gives out a handle (token) that is
used later to collect the response from the IO module. HANDLETIMEOUT specifies
the amount of time the IO module will hold the response for a particular message
handle. If the controller does not reference the handle within this time, the
response is flushed out from the IO module. This action allows for optimal use of
the IO module resources.

10.5 HARDFAIL

Specific to Block(s) EIM


Description Hard Failure Description
Data Type ENUM
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

10.6 HARDWAREREV[0..7]

Specific to Chassis HART AI IOM, HART AO IOM


Block(s)
Description Hardware Revision - Indicates the hardware revision number of the HART
device connected to the channel.
Data Type 8-Bit Unsigned Integer
Range 0 to 32
Default 0
Config Load No
Active No
Loadable

- 1183 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks

10.7 HART[0..7]

Specific to Chassis HART AI IOM, HART AO IOM, EHPM


Block(s)
Description IOM Channel Device Type - Specifies whether the channel is connected to a
HART I/O or non-HART I/O device.
Data Type Boolean
Range Non-HART (0) HART (1)
Default Non-HART (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related Analog Input: INPUTRANGE[0..7] Analog Output: SIPTYPE[0..7]
Parameters
Remarks

10.8 HARTENABLE

Specific to Block EIP IOPOINT AI or AO, it is not applicable for DI or DO, EHPM
(s)
Description Enable HART

Data Type BOOLEAN

Range True or False

Default False

Config Load Yes

Active Loadable Yes


Access Lock AppDevOnly

Residence CEEAL

Related HARTSUPPORT
Parameters
Remarks User can enable or disable HART diagnostics, provided the IO module is
supporting HART protocol.

- 1184 -
Chapter 10 - Hxxxx Parameters

10.9 HARTIPENABLE

Specific to Block(s) UOC, EHPM


Description Allows external access to HART parameters from IO that support it.
Data Type BOOLEAN

Range On, Off

Default Off

Config Load Yes

Active Loadable Yes

Access Lock Engineer

Residence UOC

Related Parameters
Remarks Opens port in firewall for external access to HART data.

10.10 HARTSUPPORT

Specific to Block(s) EIP IOPOINT AI or AO, it is not applicable for DI or DO, EHPM
Description HART Supported
Data Type BOOLEAN

Range True or False

Default True

Config Load Yes

Active Loadable No

Access Lock AppDevOnly

Residence CEE

Related Parameters N/A

Remarks This indicates that the EIP IO module supports HART protocol

10.11 HARTVERSION

Specific to Series C I/O HART channels , AO16HART (PM I/O), PM I/O HART Channels
Block(s)
Description Supported HART Version
Data Type Enumeration
Range 0 Unknown
5 HART5
6 HART6
7 HART7
8 HART8

- 1185 -
Chapter 10 - Hxxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks The attached HART device supports HART 5 to HART 8 or an unknown command
set. This parameter is only exposed when HENABLE= TRUE.

10.12 HAUTODET[1..16]

Specific to AO16HART (PM I/O) : AO-HART (Series C I/O) , PM I/O HART Channels
Block(s)
Description Enable Auto Detection. See Remarks.
Data Type Boolean
Range OFF (0) ON (1) Automatic Detection is disabled.
Automatic Detection is enabled.
Default OFF
Config No
Load
Active No
Loadable
Access Engineer only
Lock
Residence IOM
Related HDEVMFGHDEVTYPEHDEVREVHDEVID
Parameters
Remarks The Auto Detection function provides users with detailed information about HART
field devices before the channel blocks are configured and loaded. For input
devices, automatic detection is always enabled because the input channel always
has power available. Output devices rely on current from the HART AO IOM. Since
the default current from the AO channel is 0 mA, the user must explicitly enable
automatic detection by setting HAUTODET to ON. When Automatic Detection is
enabled, the IOM will set the channel current to 3.2 mA and begin polling for HART
field devices. If a HART device is connected, the device information is displayed on
the IOM's HART Status tab. This includes Manufacturer, Device Type, Revision, and
Serial Number. When Automatic Detection is disabled, the IOM will reset the
channel current to 0 mA and the device information in the HART Status tab will be
reset. Automatic Detection can only be enabled for AO channel blocks that are not
loaded (that is, reside in the Control Builder Monitoring Tree). A channel block load,
regardless of HART enabled or disabled, will disable Automatic Detection.

- 1186 -
Chapter 10 - Hxxxx Parameters

10.13 HCFGDEV

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O); AO16HART (PM I/O) , PM I/O HART Channels
Description Configured HART Device. Parameter used to help interpret the device's command
48 data.
Data Type Enumeration
Range 251 Generic HART Device HART communication and
functions are enabled, but
specific command 48 details
are missing.
12288 Flowserve Logix 12xx R01 AO only
DD04
5888 Honeywell STT25H R01 AI only
DD03
5889 Honeywell ST3000 R01 AI only
DD03
5890 Honeywell ST3000 R02 AI only
DD02
Others as added with
HART DD DD Manager
Default Generic HART Device
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence SR
Related HDEVMISMHDVMFGCDHDVTYPCDHDVREVCD
Parameters
Remarks l HCFGDEV is used to help interpret the device's command 48 data.
l HCFGDEV thus provides an enumeration that links to a list of HART devices
whose DD files have been added to or otherwise included with Experion PKS.
Each unique device in the list is represented by a unique combination of
Manufacturer, Device Type and Device Revision.
l Only input devices are listed for HAICHANNELS and only output devices are
listed for HAOCHANNELS

- 1187 -
Chapter 10 - Hxxxx Parameters

10.14 HCFGDEVTMPL

Specific to Series C I/O channel blocks; AO16HART (PM I/O)


Block(s)
Description This parameter is used to make a reference between the channel block and the
HART device template
Data Type String
Range NA
Default —
Config Load CEE
Active Loadable No
Access Lock No
Residence
Related
Parameters
Remarks

10.15 HCMD00

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O); AO16HART (PM I/O), PM I/O HART Channels
Description None
Data Type Structure, 22 bytes long
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART Command 0 data as retrieved by HART Command 0 and as defined in HCF_
Spec-127 Section7.1 (Revision 7.0). For HART 5.0 devices, HART 6.0/7.0 only data
fields are set to default values. Similarly, for HART 6.0 devices, HART 7.0 only data
fields are set to default values.

- 1188 -
Chapter 10 - Hxxxx Parameters

10.16 HCMD12

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O) ; AO16HART (PM I/O), PM I/O HART Channels
Description None
Data Type Structure, 24 bytes long
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART Command 12 data as retrieved by HART Command 12 and as defined in
HCF_Spec-127 Section 6.12 (Revision 6.0).

10.17 HCMD13

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O); AO16HART (PM I/O), PM I/O HART Channels
Description None
Data Type Structure, 21 bytes long
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART Command 13 data as retrieved by HART Command 13 and as defined in
HCF_Spec-127 Section 6.13 (Revision 6.0).

- 1189 -
Chapter 10 - Hxxxx Parameters

10.18 HCMD14

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O); AO16HART (PM I/O), PM I/O HART Channels
Description None
Data Type Structure, 16 bytes long
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART Command 14 data as retrieved by HART Command 14 and as defined in
HCF_Spec-127 Section 6.14 (Revision 6.0).

10.19 HCMD16

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O); AO16HART (PM I/O), PM I/O HART Channels
Description None
Data Type Structure, 3 bytes long
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART Command 16 data as retrieved by HART Command 16 and as defined in
HCF_Spec-127 Section 6.16 (Revision 6.0).

- 1190 -
Chapter 10 - Hxxxx Parameters

10.20 HCMD48BT[1..200]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description HART Additional Device Status as retrieved by HART command 48. Useful as an
output from an HAI or HAO channel block in control strategies.
Data Type Boolean, An array of 200 independent bit flags.
Range OFF/ON
Default OFF (If no bits are set, then NONE is displayed.)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks When bit value is 1, the indicated condition exists and is displayed with an icon and
associated text description for that particular bit. When bit value is 0, the indicated
condition does not exist. Notifications are raised on transitions from 0 to 1, when
configured by user.

10.21 HCMD48NOTIFY[1..200]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description Notification Option
Data Type Enumeration
Range Alarm (03) Record in the alarm log.
Event (01) Record in the event summary.
ViewOnly (00) Do not record, but provide status
indications in Control Builder.
Default Event (01)
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related N/A
Parameters
Remarks The “command 48” notification options are provided by the configured HART device
(HCFGDEV) and cannot be changed in Control Builder. The user may change the
“command 48” notification options with DD Manager.

- 1191 -
Chapter 10 - Hxxxx Parameters

10.22 HCMD48STRNGS[1..200]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description Command 48 String
Data Type String
Range 136 characters
Default N/A, Device dependent
Config YES
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related N/A
Parameters
Remarks The “command 48 strings” are options are provided by the configured HART device
(HCFGDEV) and cannot be changed in Control Builder. The “command 48 strings”
are embedded within the DD file and while these strings are added to the database
with DD Manager, the user is not permitted to change them so that the strings
remain as they were defined by the manufacturer in the corresponding DD file.

10.23 HCMDFAIL

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description Failed Command.
Data Type Enumeration
Range User Visible Text Values

None 122 through 126


Extended Command 31
Command xxx Where xxx is always 3 digits and is any value
between 0 and 255, except 31, and 122 through 126.

Default None
Config Load No
Active No
Loadable

- 1192 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOP
Related HCMDRESP RESETHCOMERR
Parameters
Remarks l HCMDFAIL provides the HART command number that generated an error
response code from the HART device.
l The error reponse code is in HCMDRESP.
l The RESETHCOMERR button resets HCMDFAIL.

10.24 HCMDFAILFL

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description HART Command Failed Flag
Data Type Boolean
Range Off All HART commands successfully
completed.
On One or more HART commands were
unsuccessfully attempted.
Default Off
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related HDEVSTHCOMTHRSHNCOMERRHCOMSTSHCMDFAIL
Parameters
Remarks HCMDFAILFL is not set and the alarm is not posted if the device responds to a
common practice command (that is, any command number greater than 32) with a
response code 64, (Command not Implemented). However in this case, HCMDFAIL
and HCMDRESP parameters are updated to show that the command is not
implemented.

- 1193 -
Chapter 10 - Hxxxx Parameters

10.25 HCMDRESPRDYFL_AI_S

Specific to UIO
Block(s)

Description Hart command response ready status


Data Type BOOLEAN
Range
0 FALSE HART command response is not available

1 TRUE HART command response is available

Default -6.9
Config Load False
Active No
Loadable

Access Lock ViewOnly


Residence CEE
Related
Parameters

Remarks This parameter indicate that the response to a previously sent HART command is
available to be read by controller.

10.26 HCMDRESPRDYFL_AO_S

Specific to UIO
Block(s)

Description Hart command response ready status


Data Type BOOLEAN
Range
0 FALSE HART command response is not available

1 TRUE HART command response is available

Default -6.9
Config Load False
Active No
Loadable

Access Lock ViewOnly


Residence CEE
Related
Parameters

Remarks This parameter indicate that the response to a previously sent HART command is
available to be read by controller.

- 1194 -
Chapter 10 - Hxxxx Parameters

10.27 HCOMERFL

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O); AO16HART
Block (PM I/O), PM I/O HART Channels
Description HART Communications Error flag.
Data Type Boolean
Range OFF The IOM is communicating with the
HART device.
ON The IOM is not communicationg with
the HART device.
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related HDEVSTHCOMTHRSHNCOMERRHCOMSTSHCOMFAIL
Parameters
Remarks

10.28 HCOMFAIL

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O); AO16HART (PM
Block I/O), PM I/O HART Channels
Description Last Communication Failure.
Data Type Enumeration
Range 0 None No communication failures detected.
1 No Response No response received from the device (Possible
causes: Faulty wiring, non-HART device on the wire,
noise on the wires).
2 IOM The IOM detects communication errors. (Possible
Detected causes: Faulty wiring wire, noise on the wires,
Errors problems with the device).
3 Device The connected HART device detects communication
Detected errors. (Possible causes: Faulty wiring or wire, noise
Errors on the wires, problems with the IOM).
4 Device and Both devices detect errors. (Possible causes: Faulty
IOM wiring or wire, noise on the wires, problems with the
Detected device).
Errors
Default None (0)
Config Load No
Active No
Loadable

- 1195 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOP
Related HCOMSTSRESETHCOMERR
Parameters
Remarks l Whenever HCOMSTS returns to its default state, the previous value for
HCOMSTS is written to HCOMFAIL.
l The RESETHCOMERR button resets HCOMFAIL to its default value.

10.29 HCOMHYS

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description Communication Error Hysteresis.
Data Type 16-Bit Unsigned Integer
Range 1 to 65535, but never greater than HCOMTHRS.
Default 10
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence IOP
Related HNCOMERRHCOMERFLHCOMTHRS
Parameters
Remarks l When HART communication errors (HNCOMERR) accummulate and exceed
the threshold value of HCOMTHRS, the parameter HEXCOMERRSFL is set.
The IOP also generates a corresponding alarm or return to normal whenever
the error count threshold is crossed.
l When HCOMTHRS is set to 65535, HEXCOMERRSFL is disabled and will never
be set. The alarm also is effectively disabled when HCOMTHRS is set to 65535

- 1196 -
Chapter 10 - Hxxxx Parameters

10.30 HCOMSTS

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description HART Communication Status.Shows the current communication status with the
HART device. The value of HCOMSTS changes when a change in status occurs.
Data Type Enumeration
Range 0 OK Status good.
1 No Response No response received from the device.
(Possible causes: Faulty wiring, non-HART
device on the wire, noise on the wires).
2 IOM Detected The IOM detects communication errors.
Errors (Possible causes: Faulty wiring or wire, noise
on the wires, problems with the device).
3 Device Detected The connected HART device detects
Errors communication errors. (Possible causes: faulty
wiring or wire, noise on the wires, problems
with the IOM).
4 Device and IOM Both devices detect errors. (Possible causes:
Detected Errors Faulty wiring or wire, noise on the wires,
problems with the device).
Default OK (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HCOMFAILHCOMERFL RESETHCOMERR
Parameters
Remarks l HCOMERFL is set whenever HCOMSTS isother than “0”
l Whenever HCOMSTS returns to its default state, the previous value of
HCOMSTS is written to HCOMFAIL.
l The RESETHCOMERR button resets HCOMSTS to its default value.

10.31 HCOMTHRS

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description HART Communication Error Threshold.
Data Type 16-Bit Unsigned Integer
Range 1 to 65535
Default 100
Config Yes
Load

- 1197 -
Chapter 10 - Hxxxx Parameters

Active No
Loadable
Access Lock Engineer
Residence IOM
Related HNCOMERRHEXCOMERRSFL
Parameters
Remarks l When HART communication errors (HNCOMERR) accummulate and exceed
the threshold value of HCOMTHRS, the parameter HEXCOMERRSFL is set.
The IOP also generates a corresponding alarm or return to normal whenever
the error count threshold is crossed.
l When HCOMTHRS is set to 65535, HEXCOMERRSFL is disabled and will never
be set. The alarm also is effectively disabled when HCOMTHRS is set to 65535.

10.32 HCUAVAIL

Specific to AO16HART and HLAIHART (PM I/O); AI-HART, AO-HART (Series C I/O); AO16HART
Block(s) (PM I/O), PM I/O HART Channels
Description HART communication units available.
Data Type FLOAT32
Range -380% to 100%
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HSCANCFG
Parameters
Remarks Parameter changes as the user configures scanning rates for each HART channel
of the IOM and then loads these channels. A negative percentage indicates that
overruns (HSCANOVR) are occurring on one or more channels and HART
information is not being collected within the configured Scanning HART Variables
interval.

10.33 HCUAVAIL2

Specific to Universal IO Module


Block(s)
Description HCU available from the channel 17 to the channel 32
Data Type FLOAT32
Range -380% to 100%
Default Not applicable

- 1198 -
Chapter 10 - Hxxxx Parameters

Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence
Related HCUAVAIL, HSCANCFG
Parameters
Remarks When the scanning rates are configured for each HART channel and the channels
are loaded, this parameter value varies based on the configured scanning rates. A
negative percentage indicates that overruns (HSCANOVR) occur on one or more
channels and HART information is not retrieved in the configured “HSCANCFG”
interval. For UIO channels, this value presents the HART communication units
available to channels 17 to 32. For HART communication units on channels 1 to 16,
see HCUAVAIL.

ATTENTION This parameter is not applicable for UIO-2 module.

10.34 HDAY

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O
HART Channels
Description Day
Data Type 8-Bit Unsigned Integer
Range 1-31
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM/IOLINK
Related HMONTHHYEAR
Parameters
Remarks

- 1199 -
Chapter 10 - Hxxxx Parameters

10.35 HDESC

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O
HART Channels
Description Descriptor
Data Type String
Range 16-character string
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks

10.36 HDEVID

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL (Series C I/O); AO16HART
Block (PM I/O), PM I/O HART Channels
Description ID (Serial Number) -HART Device ID (Identification) as defined in Command 0 of
HCF_Spec-183 Section 6.1. It is unique for every device manufacturered with a
given HDEVMFG and HDEVTYP.
Data Type 32-Bit Unsigned Integer
Range 0 to 16,777,215
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly.
Residence IOM
Related ACCEPTDEVHDEVIDCD[1..16]
Parameters
Remarks

- 1200 -
Chapter 10 - Hxxxx Parameters

10.37 HDEVIDCD[1..16]

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O
HART Channels
Description Id (Serial Number) - as defined in Command 0 of HCF_Spec-183 Section 6.1
Data Type 32-Bit Unsigned Integer
Range 0 to 16,777,215
Default 0
Config Load YES
Active Loadable No
Access Lock Application Developer
Residence IOM
Related ACCEPTDEVHDEVID
Parameters
Remarks HDEVIDCD is compared with HDEVID to determine if HDEVIDFL should be
set.

10.38 HDEVIDFL

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AO16HART (PM I/O), PM I/O HART
Block Channels
Description Device Changed flag.
Data Type Boolean
Range OFF The HART device previously connected to a HART
channel remains the same.
ON The HART device previously connected to a HART
channel has been replaced with different HART device.
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related HDEVSTACCEPTDEVHDEVIDCD[1..16]HDEVID
Parameters
Remarks

- 1201 -
Chapter 10 - Hxxxx Parameters

10.39 HDEVMFG

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL (Series C I/O), PM I/O
Block HART Channels
Description Manufacturer ID-HART Manufacturer as retrieved in HART command 0 and as
defined in HCF_Spec-183 Section 5.8 Table 8 (Revision 13)
Data Type Enumeration
Range 1 to 65535: Values 249 through 24576 are reserved for HART.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks Reference HCF_Spec-183 Section 5.8 Table 8 (Revision 20) for more details. Values
between 0 and 255 that are not defined in the table are displayed as “UNKNOWN
XXX” where XXX is the undefined number.

10.40 HDEVMISM

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Device Type Mismatch
Data Type Boolean
Range ON The HART device that is currently connected to the
channel does not match the configured HART device
type in the control strategy. A device type mismatch
occurs when:
l HDVMFGCD does not equal HDEVMFG or,
l HDVTYPCD does not equal HDEVTYP

OFF There is a match between the user-configured HART


device and the connected device.
Default OFF
Config No
Load
Active No
Loadable

- 1202 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related HDEVSTHDEVMFGHDVMFGCDHDEVTYPEHDVTYPCDHDEVREVHDVREVCD
Parameters
Remarks Using a Generic HART Device type matches every HART device and will not cause a
mismatch. HDEVMISM and HREVMISM are mutually exclusive in that only one can
be set at any given time.

10.41 HDEVMSG

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description Message
Data Type String
Range 32 characters
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

10.42 HDEVPROFILE

Specific to PMIO: HAICHANNEL, HAOCHANNEL Series C I/O: AICHANNEL, AOCHANNEL,


Block PM I/O HART Channels
Description Device Profile Code
Data Type ENUM
Range 1 None
2 HART Process Automation Device
3 HART Discrete Device
4 Hybrid : Process Automation + Discrete
5 I/O System
Default None
Config Load No
Active Loadable No

- 1203 -
Chapter 10 - Hxxxx Parameters

Access Lock View Only


Residence IOM
Related
Parameters
Remarks HART device profile as defined in HCF_Spec-183 section 5.57 table 57 (Revision
20)

10.43 HDEVREV

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL (Series C I/O), PM I/O
Block HART Channels
Description Revision - Refer to HART Command 0 and as defined in HCF_Spec-127 Section
6.1 (Revision 6) for more details.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks For more information, refer to HART Command 0 and as defined in HCF_Spec-
127 Section 6.1 (Revision 7)

10.44 HDEVST

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O), PM I/O HART Channels
Description HART Device Status (HDEVST) is not a user visible parameter, except as output pin.
However, when the condition exists, the individual bit definitions appear on the
HART Device Status tab in Control Builder.
Data Type BLOB
Range 32 bit structure bit mapped to HDEVSTSTATUS
Default No Errors
Config Load ViewOnly
Active No
Loadable

- 1204 -
Chapter 10 - Hxxxx Parameters

Access Lock IOM


Residence
Related HDEVSTSTATUS
Parameters
Remarks The HCFGCH, HDEVMISM, HREVMISM AND HDEVIDFL bits are visible on the
HART Identification tab.

10.45 HDEVSTSTATUS

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description HART Device Status Status (HDEVSTSTATUS) is a helper parameter for HDEVST.
Data Type 32 bit BITSTRING; some bits are reserved for future use
Range User Visible Text Bit Boolean Parameter

Primary Variable Out Of 0 HPVOUTLM


Limits
Non-Primary Variable 1 HVOUTLM
Out Of Limits
Loop Current Saturated 2 HCURRSAT
Loop Current Fixed 3 HCURRFIX
More Status Available 4 HMOREAVL
Cold Start 5 HDEVCOLD
Configuration Changed 6 HCFGCH
Device Malfunction 7 HDEVMALF
Device Type Mismatch 8 HDEVMISM
Device Revision 9 HREVMISM
Mismatch
Devcie ID Mismatch 10 HDEVIDFL
Secondary Master 11 HSMSTRFL
Present
HART Communication 12 HCOMERFL
Failure
Excessive 13 HEXCOMERRSFL
Communication Errors
HART Command Failed 14 HCMDFAILFL
HART Scan Overrun 15 HSCANOVR
Device PV Range 16 HPVMISM
Mismatch
Maintenance Required 17 HMAINTREQ
Device Variable Alert 18 HVARALERT
Device Locked 19 HLOCKSTATUS
Lock Permanent 20 HLOCKPERMANENT

- 1205 -
Chapter 10 - Hxxxx Parameters

Primary 21 HLOCKBYPRIMARYMASTER
Master
Lock
Default No Errors
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDEVSTHMAINTREQ (HART Revision 6.0 and later), HVARALERT (HART Revision
Parameters 6.0 and later), HLOCKSTATUS (HART Revision 6.0 and later), HLOCKPERMANENT
(HART Revision 6.0 and later)and HLOCKBYPRIMARYMASTER (HART Revision 6.0
and later).
Remarks 1. Bits 0 through 7 are from the HART Field Device Status as retrieved by most
HART commands and as described in HCF_SPEC-99 Section 7.4.3 Table 12.
2. Refer to parameters HMAINTREQ, HVARALERT, HLOCKSTATUS,
HLOCKPERMANENT, and HLOCKBYPRIMARYMASTER for HART Device
Status Parameter for details on the remaining bits.
3. When a value is a 1, the indicated condition exists. When a value is a 0, the
indicated condition does not exist and the User Visible Text and a red icon are
displayed.
4. Where appropriate, notifications are raised on transitions from 0 to 1.
5. The HCFGCH parameter is a different parameter than the HCFGCHFL.
HCFGCHFL is reserved for use with TPS. Also note the similarly named
HNCFGCHG is the number of times that HCFGCH has been set.
Bits 17 through 21 are for HART 6.0 and later version devices and are new
parameters for Experion. While Experion will support these parameters for Series C
I/O, these same parameters are not supported for PM I/O. The HDEVSTSTATUS
parameter is used for assigning output pins.

10.46 HDEVSTS_AI_S

Specific to Block(s) UIO


Description Hart Device Status
Data Type BOOLEAN
Range
0 FALSE Hart Device is offline

1 TRUE Hart Device is online

Default False
Config Load No
Active Loadable No

- 1206 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters

Remarks This parameter indicate the HART device is communicating or not.

10.47 HDEVSTS_AO_S

Specific to Block(s) UIO


Description Hart Device Status
Data Type BOOLEAN
Range
0 FALSE Hart Device is offline

1 TRUE Hart Device is online

Default False
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters

Remarks This parameter indicate the HART device is communicating or not.

10.48 HDEVTYPE

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL (Series C I/O), PM I/O
Block HART Channels
Description Type -HART Device Type as defined in HCF_Spec-183 Section 5.1 Table 1 (Revision
13).Note that each OEM has their own sub-table within section 5.1.
Data Type 8-Bit Unsigned Integer
Range 1 to 255: Values 250 through 255 are reserved for HART.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HDEVTYPE displays the LSB of the expanded device type for HART7 devices.

- 1207 -
Chapter 10 - Hxxxx Parameters

10.49 HDEVTYPE7

Specific to HAICHANNEL,HAOCHANNEL, Series C AOCHANNEL, Series C AICHANNEL,


Block HLAIHART, AO16HART, Series C AI-HART and Series C AO-HART , PM I/O HART
Channels
Description Type
Data Type UINT16
Range 1 to 65535
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence IOM
Related HDVTYPCDHDVTYPCD7HDEVTYPE
Parameters
Remarks HART device type as defined in HCF_Spec-183 Section 5.1 Table 1 (Revision 20)
Note that each OEM has their own sub-table within section 5.1.

10.50 HDEVTYPENAME

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL (Series C I/O), PM I/O
Block HART Channels
Description HART Device Type Name - Is the enumeration that corresponds to the combination
of HDEVMFG and HDEVTYPE.
Data Type Enumeration
Range 251 Any Device
12289 Logix 12xx
5889 ST3000
5892 STT25H
Default Any Device (251)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related HDVTYPCD
Parameters
Remarks The ranges listed above are as Experion PKS is shipped. With every device added to
the particular server's database, an additional device may also be added to the
above range. DD Manager is used to add HART Devices to a server.

- 1208 -
Chapter 10 - Hxxxx Parameters

10.51 HDVMFGCD

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Manufacturer - Reference HCF_Spec-183 Section 5.8 Table 8 (Revision 13) for
more details.
Data Type Enumeration
Range 1 to 255: Values 251 through 255 are reserved for HART. Values between 1 ND 255
that are not defined in the table are shown as “UNKNOWNxxx,”where xxx is the
undefined number.
Default 250 (Generic HART device)
Config Yes
Load
Active No
Loadable
Access ViewOnly
Lock
Residence IOM
Related HDEVMFGHDEVMISMHDEVIDFLHCFGDEV
Parameters
Remarks HDVMFGCD is compared with HDEVMFG to determine if HDEVIDFL should be set.
HDVMFGCD is compared with HDEVMFG to determine if HDEVMISM should be set.
Users do not set this parameter directly. This parameter is embedded in the
enumeration for HCFGDEV so that when a user changes HCFGDEV, this parameter
may also change. This parameter returns the configured manufacturing ID for
device types up to 255 as the enumeration size in IOM is limited to 1 byte.
HDVMFGCD displays the MSB of the HDVTYPCD7 for HART7 devices.

10.52 HDVMFGCD7

Specific to HAICHANNEL, HAOCHANNEL, Series C AOCHANNEL, Series C AICHANNEL, PM


Block I/O HART Channels
Description Manufacturer
Data Type ENUM
Range 1 to 65535. -> Reference HCF_Spec-183 Section 5.8 Table 8 (Revision 20) for more
details. Values 251 through 24576 are reserved for HART. Values that are not
defined in the table in the range 1- 255 are displayed as “UNKNOWN XXX” where
XXX is the undefined number.
Default Generic HART Device (250)
Config Yes
Load
Active No
Loadable

- 1209 -
Chapter 10 - Hxxxx Parameters

Access Lock View Only


Residence IOM
Related HDVTYPCDHDEVTYPEHDEVTYPE7
Parameters
Remarks HDEVMISM is set when MDVMFGCD7 is not equal to HDEVMFG7. You cannot
directly set this parameter. However, since this parameter is embedded in the
enumeration for HCFGDEV, when you change HCFGDEV, this parameter may also
change.

10.53 HDVREVCD

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Revision - HART Device Revision as defined in HCF_Spec-127 Section 6.1 (Revision 6)
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default N/A
Config Yes
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDEVREVHDEVMISMHCFGDEV
Parameters
Remarks HDVREVCD is compared with HDEVREV to determine if HDEVIDFL should be set.
HDVREVCD is compared with HDEVREV to determine if HDEVMISM should be set.
Users do not directly set this parameter. This parameter is embedded in the
enumeration for HCFGDEV so that when a user changes HCFGDEV, this parameter
may also change.

10.54 HDVTYPCD

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description HART Device Type - Reference HCF_Spec-183 Section 5.1 Table 1 (Revision 13) for
more details. Note that each OEM has their own sub-table within section 5.1.
Data Type 8-Bit Unsigned Integer
Range 1 to 255: Values 250, and 252 through 255 are reserved for HART.
Default 251
Config Yes
Load
Active No
Loadable

- 1210 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related HDEVTYPEHDEVMISMHCFGDEV
Parameters
Remarks HDVTYPCD is compared with HDEVTYP to determine if HDEVIDFL should be set.
HDVTYPCD is compared with HDEVTYP to determine if HDEVMISM should be set.
Users do not set this parameter directly. This parameter is embedded in the
enumeration for HCFGDEV so that when a user changes HCFGDEV, this parameter
may also change. HDVTYPCD displays the LSB of HDVTYPCD7.

10.55 HDVTYPCD7

Specific to HAICHANNEL, HAOCHANNEL, Series C AOCHANNEL, Series C AICHANNEL, PM


Block(s) I/O HART Channels
Description Type
Data Type UINT16
Range Reference HCF_Spec-183 Section 5.1 Table 1 (Revision 20) Note that each OEM
has its own sub-table within section 5.1.
Default 251
Config Yes
Load
Active No
Loadable
Access Lock View Only
Residence IOM
Related HDVTYPCDHDEVTYPEHDEVTYPE7HDEVMISMHCFGDEV
Parameters
Remarks HDEVMISM is set when HDVTYPCD7 is not equal to HDEVTYP You cannot directly
set this parameter. However, since this parameter is embedded in the enumeration
for HCFGDEV, when you change HCFGDEV, this parameter may also change.

10.56 HDVTYPCDNAME

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description HART Device Type (name)
Data Type Enumeration
Range 251 Any device
12289 Logix 12xx
5889 ST3000
5893 STT25H
Default 251 - Any device
Config Yes

- 1211 -
Chapter 10 - Hxxxx Parameters

Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related HDVTYPCD
Parameters
Remarks HDVTYPCDNAME is the enumeration that corresponds to both HDVMFGCD with
HDEVTYPCD. Users do not set this parameter directly. This parameter is embedded
in the enumeration for HCFGDEV so that when a user changes HCFGDEV, this
parameter may also change. The ranges shown above are as shipped with
Experion PKS system. Device types can be added to this parameter by using DD
Manager utility.

10.57 HDWREV[1..8]

Specific to Block(s) IOLINK


Description Hardware Revision
Data Type String
Range 12 characters maximum
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOP
Related Parameters
Remarks

10.58 HDWREV1 [1...15] through HDWREV8 [1...15]

Specific to IOLINK
Block(s)
Description IOP Hardware Revision
Data Type String
Range
Default 0
Config No
Load
Active No
Loadable

- 1212 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related IOMHWREVAIOMHWREVB
Parameters
Remarks These parameters are arrays (that correspond to PMIO chassis numbered 1
through 8) with up to 15 entries each indicating the associated IOP's hardware
revision. The index of each array corresponds to the physical slot in the PMIO
chassis number.

10.59 HDYNCC[1..4]

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Classification
Data Type Enumeration
Range See HCF_Spec-183 Section 5.21 Table 21 (Revision 13.0) for more details
Default Not Classified
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HSLOTST [1..HSLOTVARIDX] (HART Revision 6.0 and later), HDYNEU[1..4],
Parameters HSLOTCC [1..HSLOTVARIDX] (HART Revision 6.0 and later), HNSMMINPRE (HART
Revision 6.0 and later), HMAXDEVVARS (HART Revision 6.0 and later), HNCFGCHG
(HART Revision 6.0 and later), HEXTDEVST, HPVCHNFLAGS, HDYNST[1..4],
HDEVSTSTATUS
Remarks Only valid for HART 6 and later version devices. HART Classification code for PV, SV,
TV and QV. HDYNCC array indices are 1 for PV, 2 for SV, 3 for TV and 4 for QV. This
parameter is only exposed when HENABLE = TRUE.

10.60 HDYNDESC[1..4]

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description Descriptor -HART Digital PV, SV, TV and QV Description
Data Type String
Range Maximum of 48 Characters

- 1213 -
Chapter 10 - Hxxxx Parameters

Default Array Index Default Value

1 Primary Variable
2 Secondary Variable
3 Tertiary Variable
4 Quaternary Variable
Config Load No
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters HDYNNAME[1..4]HDYNDVC[1..4]HDYNST[1..4]HDYNEU[1..4]
Remarks

10.61 HDYNDSC

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description Descriptor - HART Digital PV, SV, TV and QV Description
Data Type String
Range Maximum of 48 Characters
Default Array Index Default Value

1 Primary Variable
2 Secondary Variable
3 Tertiary Variable
4 Quaternary Variable
Config Load No
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters HDYNNAME[1..4]HDYNDVC[1..4]HDYNST[1..4]HDYNEU[1..4]
Remarks HART Digital PV, SV, TV and QV Description.

- 1214 -
Chapter 10 - Hxxxx Parameters

10.62 HDYNDVC[1..4]

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description HART Digital PV, SV, TV and QV Dynamic Variable Codes
Data Type Enumeration
Range None (250) No Dynamic variable assigned.
Variable 000 (0) Device specific variable 0 is mapped to PV, SV,
TV, or QV
Variable 001 (1) Device specific variable 0 is mapped to PV, SV,
TV, or QV
Through excluding 250
Variable 255 (255) Device specific variable 255 is mapped to PV, SV,
TV, or QV
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related HDYNNAME[1..4]HDYNDESC[1..4]HDYNST[1..4]HDYNEU[1..4]
Parameters
Remarks

10.63 HDYNEU[1..4]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O), PM I/O HART Channels
Description Units - HART Engineering Units for PV, SV, TV and QV.
Data Type Enumeration
Range See HCF_Spec-183 Section 5.2 Table 2 (Revision 13) for more details.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDYNNAME[1..4]HDYNDVC[1..4]HDYNDESC[1..4]HDYNST[1..4]
Parameters
Remarks HDYNEU array indices are 1 for PV, 2 for SV, 3 for TV and 4 for QV. This parameter
is only exposed when HENABLE = TRUE.

- 1215 -
Chapter 10 - Hxxxx Parameters

10.64 HDYNNAME[1..4]

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description Name - HART Digital PV, SV, TV and QV Names.
Data Type String
Range Maximum of 24 Characters
Default Array Index Default Value

1 PV
2 SV
3 TV
4 QV
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters HDYNDVC[1..4]HDYNDESC[1..4]HDYNST[1..4]HDYNEU[1..4]
Remarks These names are for user identification and are not loaded to the device

10.65 HDYNST[1..4]

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Status
Data Type BITS, mapped as per HCF_Spec-99 section 8.4 Device Variable Status
Range See HCF_Spec-99 Section 8.4 (Revision 8) for more details.
0 Unknown
1-7 Bad, Not Limited
8-15 Bad, Not Limited, More
16-23 Bad, Low Limited
24-31 Bad, Low Limited, More
32-39 Bad, High Limited
40-47 Bad, High Limited, More
48-55 Bad, Constant
56-63 Bad, Constant, More
64-71 Poor, Not Limited
72-79 Poor, Not Limited, More
80-87 Poor, Low Limited
88-95 Poor, Low Limited, More
96-103 Poor, High Limited

- 1216 -
Chapter 10 - Hxxxx Parameters

104-111 Poor, High Limited, More


112-119 Poor, Constant
120-127 Poor, Constant, More
128-135 Manual, Not Limited
136-143 Manual, Not Limited, More
144-149 Manual, Low Limited
152-159 Manual, Low Limited, More
160-167 Manual, High Limited
168-175 Manual, High Limited, More
176-183 Manual, Constant
184-191 Manual, Constant, More
192-199 Good, Not Limited
200-207 Good, Not Limited, More
208-215 Good, Low Limited
216-223 Good, Low Limited, More
224-231 Good, High Limited
232-239 Good, High Limited, More
240-247 Good, Constant
248-255 Good, Constant, More
Default N/A
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence IOM
Related HDYNCC[1..4], HSLOTST [1..HSLOTVARIDX] (HART Revision 6.0 and later),
Parameters HSLOTCC [1..HSLOTVARIDX] (HART Revision 6.0 and later), HNMSMINPRE,
HMAXDEVVARS (HART Revision 6.0 and later), HNCFGCHG (HART Revision 6.0 and
later), HEXTDEVST, HPVCHNFLAGS, HDYNEU[1..4], HDEVSTSTATUS.
Remarks Only valid for HART 6 and later version devices. HART Variable status for PV, SV, TV
and QV. Always undefined for HART 5 devices. For some HART 6 and later version
devices HDYNST[1..4] may also be undefined. HDYNST array indices are 1 for PV, 2
for SV, 3 for TV and 4 for QV. Only the 5 highest order bits are mapped into the
range. Thus, 8 different values from the device will provide the same enumeration
value to the user. This parameter is only exposed when HENABLE = TRUE.

- 1217 -
Chapter 10 - Hxxxx Parameters

10.66 HDYNVAL[1..4]

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description Value -HART digital PV, SV, TV and QV values
Data Type FLOAT32
Range Device Specific
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters HDYNNAME[1..4]HDYNDVC[1..4]HDYNDESC[1..4]HDYNEU[1..4]
Remarks HDYNVAL array indices are 1 for PV, 2 for SV, 3 for TV and 4 for QV.

10.67 HEADERID

Specific to Block(s) 850M


Description Revision
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters
Remarks

10.68 HEADERREVISION

Specific to Block(s) 850M


Description Revision
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No

- 1218 -
Chapter 10 - Hxxxx Parameters

Access Lock Engineer


Residence SR
Related Parameters
Remarks

10.69 HEADERVERSION

Specific to Block(s) 850M


Description Version
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters
Remarks

10.70 HEAPMEM

Specific to Block(s) ProfitCtl


Description Heap Memory(KB)
Data Type FLOAT64
Range NA
Default False
Config Load Yes
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

- 1219 -
Chapter 10 - Hxxxx Parameters

10.71 HelpTxt1

Specific to EIM
Block(s)
Description HelpTxt1
Data Type STRING
Range NA
Default Note: Renaming of Alias Name here in source MMSSUBS block may need
renaming of Alias Name in associated destination DSIN block(s).
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ERDBONLY
Related
Parameters
Remarks

10.72 HENABLE

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) AICHANNEL, AOCHANNEL (Series C


Block I/O)
Description Enable HART channel.
Data Type Boolean
Range 0 False HART functions are disabled.
1 True HART functions are enabled.
Default FALSE
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence IOM
Related
Parameters
Remarks HART parameters are not exposed in Control Builder when HENABLE is FALSE. The
CM containing the channel must be loaded or reloaded to change this parameter.
For HAI channels -
l When HENABLE is TRUE, PVCHAR is not exposed.
l On HAI channels, HENABLE affects the processing of PVRAW according to the
following settings for PTEXECST and HENABLE.
PTEXECST HENABLE Result

- 1220 -
Chapter 10 - Hxxxx Parameters

ACTIVE FALSE No Change - Point processing executes.


INACTIVE FALSE No Change - Point processing does not
execute. PV and all its ancestors go to NaN
and BAD.
ACTIVE TRUE Point processing executes. HART data is
scanned periodically. Pass-through traffic
gets secondary access to the device's HART
data path.
INACTIVE TRUE Point processing does not execute. PV and
all its ancestors, except PVRAW, go to NaN
and BAD. PVRAW is updated with the
converted value. Periodic HART data scan
ceases. Pass-through traffic gets exclusive
access to the device's HART data path.

10.73 HENABLE_AI_C

Specific to Block(s) UIO


Description Enable HART
Data Type BOOLEAN
Range
0 FALSE HART functions are disabled.

1 TRUE HART functions are enabled.

Default False
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE, IOM Block
Related Parameters N/A
Remarks None

10.74 HENABLE_AO_C

Specific to Block(s) UIO


Description Enable HART
Data Type BOOLEAN
Range
0 FALSE HART functions are disabled.

1 TRUE HART functions are enabled.

Default False
Config Load Yes

- 1221 -
Chapter 10 - Hxxxx Parameters

Active Loadable No
Access Lock Application Developer
Residence CEE, IOM Block
Related Parameters N/A
Remarks None

10.75 HEU

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Engineering Units
Data Type Enumeration
Range Reference HCF_Spec-183 Section 5.2, Table 2 (Revision 13). Values between 0 and
255 that are not defined in the table are shown as “UNKNOWNxxx,” where xxx is
the undefined number.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART PV Upper and Lower Range Value Engineering Units as defined in HCF_Spec-
127 Section 6.13 (Revision 6.0).

10.76 HEXCOMERRSFL

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Excessive Communication Errors
Data Type Boolean
Range Off The accumulated count of HART communication errors
(HNCOMERR) is less than the error threshold value
(HCOMTHRS).
On The accumulated count of HART communication errors
(HNCOMERR) is greater than or equal to the error threshold
value (HCOMTHRS).
Default Off
Config Load No
Active No
Loadable

- 1222 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related HDEVSTHCOMTHRSHNCOMERRHCOMSTSHCMDFAIL
Parameters
Remarks Setting HCOMTHRS to 65535 disables HEXCOMERRSFL from being set.

10.77 HEXTDEVST

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Extended Device Status
Data Type 8-Bit Unsigned Integer
Range
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks HART Revision 6.0 and later only For more information refer to byte 16 of HART
Command 0 as defined in HCF_Spec-127 Section 6.1 (Revision 6). Also refer to HCF_
SPEC-183, Revision 13.0 Section 5.17 Table 17 for more information. This parameter,
while not shown on any tab, can be face plated and made an output from the block.

10.78 HFASSYNO

Specific to HAICHANNEL, HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Final Assembly Number
Data Type 32-Bit Unsigned Integer
Range 0 to 16,777,215
Default N/A
Config Load No
Active No
Loadable

- 1223 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related N/A
Parameters
Remarks HFASSYNO is often used for identifying the materials and electronics used in the
field device. In some plants this number references a drawing number indicating
the installation and application of the device.

10.79 HFLAGS

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description None
Data Type 8-bit Unsigned Integer, 8 independent bit fields
Range 0x01, Multi-Sensor Field Device
0x02, EEPROM Control
0x04, Protocol Bridge Device
0x08, Reserved
0x10, Reserved
0x20, Reserved
0x40, C8PSK Capable Field Device
0x80, C8PSK Capable in Multi-Drop only
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART Device Flags as retrieved by HART Command 0 and as defined in HCF_Spec-
183, Section 5.11 Table 11 (Revision 13.0). Multiple flags can be set at the same time.

- 1224 -
Chapter 10 - Hxxxx Parameters

10.80 HHWREV

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Hardware Revision - Refer to HART Command 0 and as defined in HCF_Spec-127
Section 6.1 (Revision 6) for more details.
Data Type 8-Bit Unsigned Integer
Range 0 to 30, 31 is reserved.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

10.81 HIST.TYPE

Specific to Block(s) UOC


Description History Type
Data Type STRING
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.82 HIALM

Specific to All blocks except Timer, Flag, Pulse Input IOM, IOChannels, DevCtl, and 2oo3
Block(s)
Description Highest Alarm Detected - This variable is used by the system to ensure that when
alarm conditions exist for a function block at the same time, the most important or
highest-level alarm condition will appear on both detail and group displays.
Data Type Enumeration REGALMTYPE
Range NoAlarm: (0) No alarm exists; this is the lowest-level
alarm condition.

- 1225 -
Chapter 10 - Hxxxx Parameters

Config: (1) Configuration alarm


OPHi (2) OP High alarm
OPLo (3) OP Low alarm
AdvDev (4) Advisory Deviation alarm
DevHi (5) Deviation High alarm
DevLo (6) Deviation Low alarm
SafetyIlock (7) Safety Interlock alarm
BadCtl (8) Bad Control alarm
BadCompTerm (9) Bad CompTerm alarm
Default NoAlarm (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related EXTREFSTRUCT, BADCTLFL, CMDDISALM.FL, CMDFALALM.FL, DEVHIALM.FL,
Parameters EXECSTS[1..8], EXECDESC[1..8], HIALM.SV, OFFNRMALM.FL, OPHIALM.FL,
OPLOALM.FL, SIALM.FL, UNCMDALM.FL.
Remarks The value of FBHIALM first takes into account the configured Priorities
(xxxxALM.PR) for the function block alarms. When the function block has multiple
alarms, and the priorities are equal, the following default priority order is used
(highest-to-lowest):
1. BadCtl
2. SafetyILock
3. DevHi or DevLo: (DevHi and DevLo alarms cannot exist concurrently.)
4. AdvDev
5. OpHi or OpLo: (OpHi and OpLo alarms cannot exist concurrently.)
6. BadCompTerm

10.83 HIALM.PR

Specific to RegCtl, RegSummer, DevCtl, DataAcq, SCM, Flag, Push, MainIBV, LevelComp,
Block(s) ContactMon, FirstOut, DigAcq, AlmWindow, Grpcaprbk, Htmotor, Ltmotor, Solenoid,
ValveDamper
Description Highest Alarm Priority - Indicates the priority of the highest-level alarm that
currently exists for the function block.
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None (0)
Config Load No
Active No
Loadable

- 1226 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related HIALM.SV, HIALM.TYPE.
Parameters
Remarks

10.84 HIALM.SV

Specific to RegCtl, RegSummer, DevCtl, DataAcq, SCM, Flag, Push, MainIBV, LevelComp,
Block(s) ContactMon, FirstOut, DigAcq, AlmWindow, Grpcaprbk, Htmotor, Ltmotor, Solenoid,
ValveDamper
Description Highest Alarm Severity - Indicates the severity of the highest-level alarm that
currently exists for the function block.
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly Flag Only: Engineer
Residence CEE
Related DEVLOALM.FL, HIALM.TYPE.
Parameters
Remarks

10.85 HIALM.TYPE

Specific to DataAcq, SCM, Push, RegSummer, MainIBV, LevelComp, ContactMon, FirstOut,


Block(s) DigAcq, AlmWindow, Grpcaprbk, Htmotor, Ltmotor, Solenoid, ValveDamper
Description Highest Alarm Detected - This variable is used by the system to ensure that, when
alarm conditions exist for a function block at the same time, the most important or
highest-level alarm condition will appear on both detail and group displays.
Data Type Enumeration DACALMTYPE
Range None (0): No alarm exists (Lowest-level alarm
condition)
BadPV (1): Bad PV alarm
PvHiHi (2): PV High High alarm
PvLoLo (3): PV Low Low alarm
PvHi (4): PV High alarm
PvLo (5): PV Low alarm
PosROC (6): Positive Rate-of-Change alarm

- 1227 -
Chapter 10 - Hxxxx Parameters

NegROC (7): Negative Rate-of-Change alarm


Default None (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related DEVLOALM.FL, HIALM.SV.
Parameters
Remarks

Specific to RegCtl
Block(s)
Description Highest Alarm Detected - This variable is used by the system to ensure that when
alarm conditions exist for a function block at the same time, the most important or
highest-level alarm condition will appear on both detail and group displays.
Data Type Enumeration
Range NONE No alarm exists; this is the lowest-level
alarm condition.
PredLo Predicted Low alarm
PredHi Predicted High alarm
OPHi OP High alarm
OPLo OP Low alarm
AdvDev Advisory Deviation alarm
DevHi Deviation High alarm
DevLo Deviation Low alarm
SafetyIlock Safety Interlock alarm
BadCtl Bad Control alarm
Default NONE (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related DEVLOALM.FL, HIALM.SV.
Parameters
Remarks

- 1228 -
Chapter 10 - Hxxxx Parameters

Specific to DevCtl
Block(s)
Description Highest Alarm Detected - This variable is used by the system to ensure that, when
alarm conditions exist for a function block at the same time, the most important or
highest-level alarm condition will appear on both detail and group displays.
Data Type Enumeration DEVHIALM
Range None (0) No alarm
BadPv (1) Bad PV alarm
OffNormal (2) Off Normal alarm
CmdDisagree (3) Command Disagree alarm
CommandFail (4) Command Fail alarm
UnCommanded (5) Uncommanded alarm
SafetyIlock (6) Safety Interlock alarm
Oride0Ilock (7) State0 Override Interlock alarm
Oride1Ilock (8) State1 Override Interlock alarm
Oride2Ilock (9) State2 Override Interlock alarm
Default None (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence No
Related DEVLOALM.FL, HIALM.SV.
Parameters
Remarks

Specific to FLAG block


Block(s)
Description Highest Alarm Detected - This variable is used by the system to ensure that, when
alarm conditions exist for a function block at the same time, the most important or
highest-level alarm condition will appear on both detail and group displays.
Data Type Enumeration HIALMFlag
Range None (0) OffNormal (1)
Default None (0)
Config No
Load
Active No
Loadable
Access Lock Engineer
Residence No
Related ALTENBOPTALTENBOPTINALTOFFNRMALM.FL, OFFNRMALM.PR,
Parameters OFFNRMALM.SV.
Remarks This parameter is set to OFFNRMALT when there is an active alert in the block. The
HIALM.TYPE will be set to OFFNRMALT when INALT is set to ON.

- 1229 -
Chapter 10 - Hxxxx Parameters

10.86 HIGHAL

Specific to DICHANNEL (PM I/O)


Block(s)
Description Highest Alarm. Shows the highest alarm currently detected at this point.
Data Type Enumeration
Range NoAlarm (0): No alarm exists.
OffNorm (1): Current PV state is not the configured
PVNORMAL state. For a flag point, the
off-normal state (STATE1) is the alarmed
state.
BadPV (4): PV is bad.
Default NoAlarm (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks This parameter is only exposed when the ASSOCIOPTYP is DISOE and the
PNTFORM is Full. The system uses this parameter to ensure that when two or more
different types of alarms occur on a point at the same time, the most important or
highest level alarm appears on the point's Group, Detail, and Alarm Summary
displays.

10.87 HIGHENG[0..numChans-1]

Specific to AIM, AOM This parameter is configurable only on the AIM.


Block(s)
Description High Engineering: Specify the value that represents the maximum limit for the
output.
Data Type 64-Bit Real Number
Range NaN, greater-than LOWENG
Default 100.0
Config Load AIM: Yes AOM: No
Active No
Loadable

- 1230 -
Chapter 10 - Hxxxx Parameters

Access Lock AIM: Application Developer AOM: ViewOnly


Residence CEE
Related LOWENG[0..numChans-1]
Parameters
Remarks If the user program tries to set an output value outside the specified limit, the
output will be clipped at the limit and an alarm bit is set. Clamp value is specified in
Engineering Units.

10.88 HIGHENG[0..7]

Specific to Block(s) Chassis HART AI IOM, HART AO IOM


Description High Engineering Value
Data Type Float64
Range NaN, greater than LOWENG
Default 100.0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters LOWENG[0..7]
Remarks

10.89 HIGHSIGNAL[0..numChans-1]

Specific to AIM, AOM


Block(s)
Description High Signal
Data Type 64-Bit Real Number
Range N/A
Default See Remarks below.
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related INPUTRANGE[0..numChans-1]LOWSIGNAL[0..numChans-1]SIPTYPE
Parameters [0..numChans-1].
Remarks For AIMs, this parameter is set within the controller, based on the store of
INPUTRANGE. For AOMs, this parameter is set within the controller, based on the
store of SIPTYPE.

- 1231 -
Chapter 10 - Hxxxx Parameters

10.90 HIGHSIGNAL[0..7]

Specific to Chassis HART AI IOM


Block(s)
Description High Signal Value
Data Type Float64
Range
Default See Remarks below.
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related INPUTRANGE[0..7]LOWSIGNAL[0..7]
Parameters
Remarks This parameter is set within the controller and is based on the store of
INPUTRANGE (voltage or current mode). HIGHSIGNAL is not configured if the
HART parameter is selected for the channel.

Specific to Chassis HART AO IOM


Block(s)
Description High Signal Value
Data Type Float64
Range
Default See Remarks below.
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related LOWSIGNAL[0..7]SIPTYPE[0..7]
Parameters
Remarks This parameter is set within the controller and is based on the value of SIPTYPE
(voltage or current mode). HIGHSIGNAL is not configured if the HART parameter is
selected for the channel.

- 1232 -
Chapter 10 - Hxxxx Parameters

10.91 HILMRAMPRATE

Specific to PID-PL
Block(s)
Description High Limit Ramp Rate, in Engineering Units/Minute - Sets the rate at which the
Active high limit ramps toward a new HI LIMIT.
Data Type Float64
Range 0
Because a zero ramp rate would prevent convergence to the operator-set limit, it is
re-interpreted as an infinite rate.
Default NaN
Config Load
Active No
Loadable
Access Lock Engineer
Residence
Related LOGICINITOPTLOLMRAMPRATE
Parameters
Remarks Whenever the Active high limit is above the operator-set limit, the Active limit ramps
toward the new limit at this specified rate. The operator-set high limit is:
l SPHILM for range control
l SP for setpoint control

- 1233 -
Chapter 10 - Hxxxx Parameters

10.92 HIOPLHFSTA

Specific to Block(s) HLAIHART, AO16HART


Description HART I/O Module Last Hard Fail Status Primary
Data Type Enumeration
Range 0 ---
1 Watchdog Timeout
2 Internal RAM Diagnostic Error
3 External RAM Diagnostic Error
4 Stack OverflowError
5 RAM Address Error
6 Startup Diagnostic Error
11 Invalid Execution Error 11
12 Invalid Execution Error 12
13 Invalid Execution Error 13
14 Invalid Execution Error 14
15 Invalid Execution Error 15
16 Invalid Execution Error 16
17 Invalid Execution Error 17
Default Invalid Execution Error 17
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

- 1234 -
Chapter 10 - Hxxxx Parameters

10.93 HIOPLHFSTB

Specific to Block(s) HLAIHART, AO16HART


Description HART I/O Module Last Hard Fail Status Secondary
Data Type Enumeration
Range 0 ---
1 Watchdog Timeout
2 Internal RAM Diagnostic Error
3 External RAM Diagnostic Error
4 Stack OverflowError
5 RAM Address Error
6 Startup Diagnostic Error
11 Invalid Execution Error 11
12 Invalid Execution Error 12
13 Invalid Execution Error 13
14 Invalid Execution Error 14
15 Invalid Execution Error 15
16 Invalid Execution Error 16
17 Invalid Execution Error 17
Default Invalid Execution Error 17
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

10.94 HISHART5

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description HART protocol Version 5 or older device flag.
Data Type Boolean
Range OFF The connected device is newer than HART
version 5.
ON The connected device is HART version 5 or older
(4, 3, 2, 1).
Default OFF
Config Load No
Active Loadable No

- 1235 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOP
Related HDEVST
Parameters
Remarks

10.95 HIST.STDPHDCOLLRATE

Specific to Block(s) All tagged blocks


Description PHD Collection rate for Standard History collection type.
Data Type ENUM
Range Default, Override, Disable
Default Default
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The PHD Collection rate at which the Standard History type values are
collected.

Specific to Block(s) UOC


Description PHD Collection Rate for STD History Collection Type
Data Type ENUM
Range N/A
Default Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.96 HIST.EXCPHDCOLLRATE

Specific to Block All tagged blocks


(s)
Description PHD Collection rate for exception History collection type.
Data Type ENUM
Range Default, Override, Disable

- 1236 -
Chapter 10 - Hxxxx Parameters

Default Default
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The PHD collection rate specified at which the frequency for exception History
are collected.

Specific to Block(s) UOC


Description PHD Collection Rate for EXC History Collection Type
Data Type ENUM
Range N/A
Default Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.97 HIST.EXTDPHDCOLLRATE

Specific to All tagged blocks


Block(s)
Description
Data Type ENUM
Range Default, Override, Disable
Default Default
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The collection rate specifies the frequency at which the PHD Collection rate for
Extended History collection type are collected.

- 1237 -
Chapter 10 - Hxxxx Parameters

Specific to Block(s) UOC


Description PHD Collection Rate for EXTD History Collection Type
Data Type ENUM
Range N/A
Default Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.98 HIST.FASTPHDCOLLRATE

Specific to Block All tagged blocks


(s)
Description PHD Collection rate for Fast History collection type
Data Type ENUM
Range Default, Override, Disable
Default Default
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The PHD collection rate specifies the frequency at which the fast history
values are collected.

Specific to Block(s) UOC


Description PHD Collection Rate for Fast History Collection Type
Data Type ENUM
Range N/A
Default Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

- 1238 -
Chapter 10 - Hxxxx Parameters

10.99 HIST

Specific to Block(s) Common to most blocks


Description History Configuration
Data Type STRUCTDATA
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock Application Developer
Residence Server
Related Parameters
Remarks The collection of history collection information associated with a
parameter.

Specific to Block(s) UOC


Description History Configuration
Data Type STRUCTDATA
Range
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.100 HISTDESC

Specific to Block(s) SCM


Description History Parameter Descriptor
Data Type String
Range Maximum of 63 characters.
Default Null String
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters NUMHISTPARMS
Remarks

- 1239 -
Chapter 10 - Hxxxx Parameters

10.101 HISTEUDESC[1..50]

Specific to Block(s) SCM


Description History Parameter Engineering Units Description
Data Type String
Range 24 Characters
Default Blank
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

10.102 HIST.EXC

Specific to All tagged blocks


Block(s)
Description Exception Collection Type - Exception type of history collection. The “Exception
History” type is created at the server-side to collect history values for string
parameters. This parameter is configurable from Station only.
Data Type Boolean
Range Off(0) On(1)
Default Off
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks You cannot select exception history and periodic history (fast, standard, and/or
extended) simultaneously for a single point parameter.

Specific to Block(s) UOC


Description Exception Collection Type
Data Type BOOLEAN
Range N/A
Default F
Config Load Yes
Active Loadable

- 1240 -
Chapter 10 - Hxxxx Parameters

Access Lock APPDEVONLY


Residence SCAN
Related Parameters
Remarks

10.103 HIST.EXCCOLLRATE

Specific to All tagged blocks


Block(s)
Description Exception Collection Rate - Collection rate for Exception History collection.
Data Type INT16
Range 0 to 255
Default 0
Config Yes
Load
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks When a number of parameters are configured to be collected at the same rate, the
server may become overloaded, In such scenarios, you can offset the collection of
the parameters by providing different offset.
l The offset group that the parameters are assigned to specify the time at which
the history values are collected.
l The collection rate specifies the frequency at which the history values are
collected.
For example, if a point parameter is configured with a 6-second collection rate and
assigned to a 0-second collection offset group, the history values are collected on
the 0th, 6th, 12th, ..., 54th second. The 0-second offset means there is no collection
offset. If the same point parameter is assigned to a 2-second collection offset
group, the history values are collected on the 2nd, 8th, 14th, ..., 56th second.

Specific to Block(s) UOC


Description Collection Rate for Exception History Collection Type
Data Type INT16
Range ±32767
Default 0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

- 1241 -
Chapter 10 - Hxxxx Parameters

10.104 HIST.EXCOFFSET

Specific to All tagged blocks


Block(s)
Description Exception Offset - Offset for Exception History collection.
Data Type INT16
Range 0 to 255
Default 0
Config Yes
Load
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks When a number of parameters are configured to be collected at the same rate, the
server may become overloaded, In such scenarios, you can offset the collection of
the parameters by providing different offset.
l The offset group that the parameters are assigned to specify the time at which
the history values are collected.
l The collection rate specifies the frequency at which the history values are
collected.
For example, if a point parameter is configured with a 6-second collection rate and
assigned to a 0-second collection offset group, the history values are collected on
the 0th, 6th, 12th, ..., 54th second. The 0-second offset means there is no collection
offset. If the same point parameter is assigned to a 2-second collection offset group,
the history values are collected on the 2nd, 8th, 14th, ..., 56th second.

Specific to Block(s) UOC


Description Collection Rate Offset for Exception History Collection Type
Data Type INT16
Range ±32767
Default 0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

- 1242 -
Chapter 10 - Hxxxx Parameters

10.105 HIST.EXTD

Specific to Block(s) Common to most blocks


Description Extended Collection Type.
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related Parameters
Remarks Selects the Extended type of history collection.

Specific to Block(s) UOC


Description Extended Collection Type
Data Type BOOLEAN
Range N/A
Default F
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.106 HIST.FAST

Specific to Block(s) Common to most blocks


Description Fast Collection Type
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related Parameters
Remarks Selects the Fast type of history collection.

- 1243 -
Chapter 10 - Hxxxx Parameters

Specific to Block(s) UOC


Description Fast Collection Type
Data Type BOOLEAN
Range N/A
Default F
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.107 HIST.FASTCOLLRATE

Specific to Block(s) All tagged blocks


Description Fast Collection Rate - Collection rate for Fast History collection.
Data Type INT16
Range 0 to 255
Default 0
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The collection rate specifies the frequency at which the history values are
collected.

Specific to Block(s) UOC


Description Collection Rate for Fast History Collection Type
Data Type INT16
Range ±32767
Default 0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

- 1244 -
Chapter 10 - Hxxxx Parameters

10.108 HIST.GATEPARAM

Specific to Common to most blocks


Block(s)
Description Gating Parameter
Data Type PARAMID
Range N/A
Default N/A
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks An optional gating parameter in the system, which is configured by the Control
Builder, that defines the conditions under which data for this parameter should be
collected.

Specific to Block(s) UOC


Description Gating Parameter
Data Type PARAMID
Range
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.109 HIST.GATESTRING

Specific to Common to most blocks


Block(s)
Description Gating Parameter String
Data Type String
Range Length : 255 characters
Default Null
Config Load Yes
Active Yes
Loadable

- 1245 -
Chapter 10 - Hxxxx Parameters

Access Lock Application Developer


Residence Server
Related
Parameters
Remarks An optional gating parameter in the system, which is not configured by the Control
Builder, that defines the conditions under which data for this parameter should be
collected.

Specific to Block(s) UOC


Description Gating Parameter String
Data Type STRING
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.110 HIST.GATEVALUE

Specific to Block(s) Common to most blocks


Description Gating Parameter Value - The gate state for the configured gating
parameter.
Data Type String
Range Length : 255 characters
Default Null
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related Parameters
Remarks The gate state for the configured gating parameter.

Specific to Block(s) UOC


Description Gating Parameter value
Data Type STRING
Range N/A
Default
Config Load Yes
Active Loadable

- 1246 -
Chapter 10 - Hxxxx Parameters

Access Lock APPDEVONLY


Residence SCAN
Related Parameters
Remarks

10.111 HIST.NUMPARAMS

Specific to Block Common to most blocks


(s)
Description Number of History Parameters
Data Type 16-Bit integer
Range 1 to 25
Default 10
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks The number of history parameters (1 to 25) to be included in the History
Configuration table.

Specific to Block(s) UOC


Description Number of History parameters
Data Type INT16
Range ±32767
Default 10
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

- 1247 -
Chapter 10 - Hxxxx Parameters

10.112 HIST.PARAM

Specific to Common to most blocks


Block(s)
Description History Parameter.
Data Type PARAMID
Range N/A
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks A valid parameter name for a parameter associated with the given point that is to
be collected and stored as historical data at predetermined intervals.

Specific to Block(s) UOC


Description History Parameter
Data Type PARAMID
Range
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.113 HIST.STD

Specific to Block(s) Common to most blocks


Description Standard Collection Type
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load Yes
Active Loadable Yes

- 1248 -
Chapter 10 - Hxxxx Parameters

Access Lock Application Developer


Residence Server
Related Parameters
Remarks Selects the Standard type of history collection.

Specific to Block(s) UOC


Description Standard Collection Type
Data Type BOOLEAN
Range N/A
Default F
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.114 HIST.STDCOLLRATE

Specific to All tagged blocks


Block(s)
Description Standard Collection Rate - Collection rate for Standard History collection.
Data Type INT16
Range 0 to 255
Default 0
Config Yes
Load
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks When a number of parameters are configured to be collected at the same rate, the
server may become overloaded, In such scenarios, you can offset the collection of
the parameters by providing different offset.
l The offset group that the parameters are assigned to specify the time at which
the history values are collected.
l The collection rate specifies the frequency at which the history values are
collected.
For example, if a point parameter is configured with a 6-second collection rate and
assigned to a 0-second collection offset group, the history values are collected on
the 0th, 6th, 12th, ..., 54th second. The 0-second offset means there is no collection
offset. If the same point parameter is assigned to a 2-second collection offset
group, the history values are collected on the 2nd, 8th, 14th, ..., 56th second.

- 1249 -
Chapter 10 - Hxxxx Parameters

Specific to Block(s) UOC


Description Collection Rate for Standard History Collection Type
Data Type INT16
Range ±32767
Default 0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.115 HIST.STDOFFSET

Specific to All tagged blocks


Block(s)
Description Standard Offset - Offset for Standard History collection.
Data Type INT16
Range 0 to 255
Default 0
Config Yes
Load
Active Yes
Loadable
Access Lock Application Developer
Residence Server
Related
Parameters
Remarks When a number of parameters are configured to be collected at the same rate, the
server may become overloaded, In such scenarios, you can offset the collection of
the parameters by providing different offset.
l The offset group that the parameters are assigned to specify the time at which
the history values are collected.
l The collection rate specifies the frequency at which the history values are
collected.
For example, if a point parameter is configured with a 6-second collection rate and
assigned to a 0-second collection offset group, the history values are collected on
the 0th, 6th, 12th, ..., 54th second. The 0-second offset means there is no collection
offset. If the same point parameter is assigned to a 2-second collection offset group,
the history values are collected on the 2nd, 8th, 14th, ..., 56th second.

- 1250 -
Chapter 10 - Hxxxx Parameters

Specific to Block(s) UOC


Description Collection Rate Offset for Standard History Collection Type
Data Type INT16
Range ±32767
Default 0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

10.116 HISTTYPE[1..50]

Specific to Block(s) SCM, RCM, Master Recipe


Description History Parameter Type
Data Type String
Range Maximum of 11 characters
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters HISTVALUE
Remarks Parameter type of the History parameter.

10.117 HISTVALUE[1..50]

Specific to SCM
Block(s)
Description History Parameter Value
Data Type 64-Bit Real Number
Range Double precision according IEEE 754
Default NaN
Config Yes
Load
Active No
Loadable

- 1251 -
Chapter 10 - Hxxxx Parameters

Access Lock Operator


Residence CEE
Related RECTARGET[1..50],DATABLOCK
Parameters
Remarks HISTVALUE allows the specification of formula values for SCMs. This is the legacy
mechanism which will not be developed any further. It is not recommended to use
HISTVALUE and DATABLOCK at the same time, since this may lead to confusion.
For more information on DATA block, refer to the Sequential Control Module User
Guide.

10.118 HISTVALUEMAX[1..50]

Specific to Block(s) SCM


Description History Parameter Maximum Value
Data Type 64-Bit Real Number
Range
Default NaN
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

10.119 HISTVALUEMIN[1..50]

Specific to Block(s) SCM


Description History Parameter Minimum Value
Data Type 64-Bit Real Number
Range
Default NaN
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

- 1252 -
Chapter 10 - Hxxxx Parameters

10.120 HLOCKBYPRIMARYMASTER (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Primary Master Lock
Data Type Boolean
Range 0 OFF The primary HART master DID
NOT place the device lock.
1 ON The primary HART master
placed the device lock.
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDEVSTSTATUS, HARTVERSION, HLOCKSTATUS (HART Revision 6.0 and later),
Parameters HLOCKPERMANENT (HART Revision 6.0 and later)
Remarks Details of the lock on the HART Device. Reference HCF_Spec-183 Section 5.25, Table
25 (Revision 13). Only valid on HART 6 and later devices.

10.121 HLOCKPERMANENT (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Lock Permanent
Data Type Boolean
Range 0 OFF Device lock is not permanent and
will be removed on a device power
cycle.
1 ON Device lock is permanent. (It will be
maintained on a power cycle.)
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDEVSTSTATUS, HARTVERSION, HLOCKSTATUS (HART Revision 6.0 and later),
Parameters HLOCKBYPRIMARYMASTER (HART Revision 6.0 and later)
Remarks Details of the lock on the HART Device. Reference HCF_Spec-183 Section 5.25, Table
25 (Revision 13). Only valid on HART 6 and later devices.

- 1253 -
Chapter 10 - Hxxxx Parameters

10.122 HLOCKSTATUS (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Device Locked
Data Type Boolean
Range 0 OFF Device is NOT locked.
1 ON Device is locked.
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDEVSTSTATUSHARTVERSIONHLOCKPERMANENT (HART Revision 6.0 and
Parameters later)HLOCKBYPRIMARYMASTER (HART Revision 6.0 and later)
Remarks Refer to HCF_Spec-183 Section 5.25, Table 25 (Revision 13) for more details. Only
valid on HART 6 and later devices.

10.123 HLONGTAG

Specific to All Series C I/O channel blocks and PM I/O channel blocks, PM I/O HART Channels
Block(s)
Description Long Tag
Data Type STRING
Range 64 characters
Default Not Applicable
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK, IOLIM
Related
Parameters
Remarks This parameter is used for displaying 40–character HART long tag name. In
addition, this parameter is displayed in the detail displays of the channel block.

ATTENTION This parameter is not applicable for the SPM and SVPM
channel blocks.

- 1254 -
Chapter 10 - Hxxxx Parameters

10.124 HMAINTREQ (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Maintenance Required
Data Type Boolean
Range 0 OFF The device does not require
maintenance.
1 ON The device has not malfunctioned, but
it does require maintenance.
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDEVSTSTATUS, HARTVERSION
Parameters
Remarks Refer to HCF_Spec-183 Section 5.25, Table 17 (Revision 13) for more details. Only
valid on HART 6 and later devices.

10.125 HMAXDEVVARS (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Maximum Number of Variables
Data Type 8-Bit Unsigned Integer
Range 0 t0 255
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks HART Revision 6.0 and later only For more information refer to byte 13 of HART
Command 0 as defined in HCF_Spec-127 Section 6.1 (Revision 6). This parameter is
only exposed when HENABLE = TRUE.

- 1255 -
Chapter 10 - Hxxxx Parameters

10.126 HMONTH

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O)


Description Month
Data Type 8-Bit Unsigned Integer
Range 1-12
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related Parameters HDAYHYEAR
Remarks

10.127 HMPORTACTIVE

Specific to Block(s) EIP IOPOINT AI or AO, it is not applicable for DI or DO

Description Master Port Active

Data Type BOOLEAN

Range True or False

Default N/A

Config Load Yes

Active Loadable NOLOAD

Access Lock ViewOnly

Residence NOLOAD

Related Parameters N/A

Remarks LED indicating the connectivity of IO module with the HART device

10.128 HMW

Specific to HRBBOX_CB, HRBBOX_EC, HRBBOX_LxPIU, and HRBBOX_HLPIU block


Blocks
Description Hiway Memory Words
Data Type Array of UINT16
Range 0–63
Default 0
Config. No
Load
Active No
Loadable

- 1256 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related SLOTNUM
Parameters
Remarks This parameter reflects Hiway box memory on the box configuration form. Each row
represents one word in the Hiway Box memory. The first index displays the first
word, the second index displays the second word, and so on. Slot number
parameter can be used to visualize certain portion of box memory at a time. For
instance, if the slot number parameter is 1, the first 64 words will be visible, if it is 2,
then the next 64 words will be visible, and so on.

10.129 HNCFGCHG (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Configuration Change Counter
Data Type 16-Bit Unsigned Integer
Range 0 to 65535
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HCFGCH
Parameters
Remarks HART Revision 6.0 and later only HNCFGCHG is the number of times that HCFGCH
has been set. This parameter is only exposed when HENABLE = TRUE.

10.130 HNCOMERR

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Communication Errors.
Data Type 16-Bit Unsigned Integer
Range 0 to 65535
Default 0
Config No
Load
Active No
Loadable

- 1257 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOP
Related HCOMTHRSHCOMERFL RESETHCOMERR
Parameters
Remarks The value of HNCOMERR is increased when a communications retry is necessary;
HNCOMERR is decreased when a retry is not necessary. Excessively high values for
HNCOMERR indicate that the communication link has significant electrical noise.
HNCOMERR is always less than HCOMTHRS. The RESETHCOMERR button resets
HNCOMERR to zero.

10.131 HNMSMINPRE

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Minimum M to S Preambles -Minimum number of preambles required for the
request message from the Master to the Slave. Refer to byte 3 of HART Command 0
as defined in HCF_Spec-127 Section 6.1 (Revision 6) for more details.
Data Type 8-Bit Unsigned Integer
Range 2 to 255
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART Revision 6.0 and later only.

10.132 HNSMMINPRE (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Minimum slave to master Preambles
Data Type 8-Bit Unsigned Integer
Range 2 to 255
Default N/A
Config No
Load
Active No
Loadable

- 1258 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks HART Revision 6.0 and later only Minimum number of preambles required for the
request message from the Slave to the Master. For more information refer to byte
12 of HART Command 0 as defined in HCF_Spec-127 Section 6.1 (Revision 6). This
parameter is only exposed when HENABLE = TRUE.

10.133 HOLDALM.FL

Specific to SCM
Block(s)
Description Hold Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related HOLDALM.PR, HOLDALM.SV STATE.
Parameters
Remarks When this is On, it indicates that the Hold Alarm condition (SCMSTATE has
transitioned to Hold or Holding) exists.

10.134 HOLDALM.PR

Specific to Block(s) SCM


Description Hold Alarm Priority - Specifies the alarm priority for the Hold alarm.
Data Type Enumeration ALMPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters HOLDALM.FL, HOLDALM.SV, STATE.
Remarks

- 1259 -
Chapter 10 - Hxxxx Parameters

10.135 HOLDALM.SV

Specific to Block(s) SCM


Description Hold Alarm Severity - Specifies the alarm severity for the Hold alarm.
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters HOLDALM.FL, HOLDALM.PR, STATE
Remarks

10.136 HOLDBRTHTM

Specific to ACE
Block(s)
Description Hold Breath Time(sec)
Data Type FLOAT64
Range 0 to 7 (Granularity 0.5)
Default 0 (7 for ACE migrated from a pre-R311 release)
Config Yes
Load
Active No
Loadable
Access Application Developer Only
Lock
Residence CEE
Related
Parameters
Remarks Hold Breath Timeout time in seconds. This value indicates the time the CEE waits
for prefetch data and holds execution of blocks before executing with fail safe
values. The default value of HOLDBRTHTM is 0 for new ACE. For an ACE that has
been migrated from a pre-R311 release, the HOLDBRTHTM is set to 7.
HOLDBRTHTM = 0 switches off this functionality. This means if peer data is not
available within the prefetch anticipation time, the CEE doesn't hold execution of
blocks and executes immediately with fail safe values. The HOLDBRTHTM value can
be configured in the granularity of 0.5. For example, the possible values can be 0,
0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, and 7. HOLDBRTHTM will be
clamped/rounded as follows:
l Out of range, which is less than minimum (1) and greater than maximum (7),
will be rejected.
l For values within range:

- 1260 -
Chapter 10 - Hxxxx Parameters

Entered Value Rounded/Clamped value

>=X+0 and <=X+0.25 X


>X+0.25 and <=X+0.75 X+0.5
>X+0.75 and <=X+1 X+1
Where X is an integer between 1 and 7 (both inclusive) For Example:
l If the entered value is 1.20 (>=1 and <=1.25), it will be clamped to 1.
l If the entered value is 1.3 or 1.7 (>1.25 and <=1.75), it will be clamped to 1.5.
l If the entered value is 1.8 (>1.75 and <=2), it will be rounded to 2.
Note: This timeout time is common for the entire ACE and the execution of all blocks
will be suspended until a timeout occurs or data/error is received.

10.137 HOLDBRTHTP

Specific to CEEACE
Block(s)
Description Hold Breath Trippoint
Data Type 16-Bit Integer
Range
Default 0
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks -1 (minus one) - There are no reports for CEE hold breath events. 0 (zero) - CEE
reports hold-breath event on every occurrence. Greater than 0 (zero) - Specifies
the number of ACE phases that should be delayed before a hold breath alarm is
generated.

10.138 HOLDCMD

Specific to Block(s) RampSoak


Description RampSoak Hold Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No

- 1261 -
Chapter 10 - Hxxxx Parameters

Access Lock Other Function Block


Residence CEE
Related Parameters
Remarks

10.139 HOLDOPT

Specific to DevCtl, All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: GRPCAPRBK, HTMOTOR, LTMOTOR,
SOLENOID, VALVEDAMPER
Description The Hold State Option is a configurable parameter that specifies the action the
control device takes, when SCMSTATE is Holding or Held. This option should be
disabled, when sequencing actions are required as part of the SCM. In this case,
the SCM should execute its HOLD Handler. The SCM can also disable this option.
Data Type Enumeration REGEXOPT
Range None (0): no changes Man (1): set MODEREQ = Manual Auto (2): set MODEREQ =
Auto Cas (3): set MODEREQ = Cas FixedOP (4): set OPREQ = HOLDVAL HoldPv (5):
set SPREQ = PV FixedSP (6): set SPTVREQ = HOLDVAL, and SPRATEREQ = NaN
RampedSP (7): set SPTVREQ = HOLDVAL, and SPRATEREQ = HOLDRATE
Default None (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DevCtl and Drive Control only: OPTYPE, RESTARTOPT, SAFEOP, SCMOPT,
Parameters STARTOPT, STOPOPT.
Remarks Defines values for SPREQ, SPTVREQ, SPRATEREQ, OPREQ, and MODEREQ, when
the Control Module.SCMSTATE transitions to Held or Holding. DevCtl and Drive
Control only: Illegal if ControlModule.SCMOPT ≠ Fixed. Note: If the Man and Cas
modes are not supported, then corresponding error should be displayed while
configuring or loading. Also, the value box should be disabled.
Description Hold State Set Point (SP) Ramp Rate - The value used for setting SPRATEREQ when
HOLDOPT is RampedSP.
Data Type 64-Bit Real Number
Range NaN, 0, and Real Numbers
Default NaN
Config Yes
Load
Access Lock Engineer
Residence CEE
Related HOLDOPT
Parameters
Remarks Defines value for SPRATEREQ, when HOLDOPT = Ramped Set Point (SP)

- 1262 -
Chapter 10 - Hxxxx Parameters

10.140 HOLDSTEPPER

Specific to Block(s) ProfitCtl


Description Hold Stepper
Data Type BOOL
Range NA
Default False
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters
Remarks

10.141 HOLDVAL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Hold State Value - The value used for setting OPREQ, when HOLDOPT is FixedOP;
or for setting SPREQ or SPTVREQ, when HOLDOPT is FixedSP or RampedSP.
Data Type 64-Bit Real Number
Range OPEXLOLM to OPEXHILM, when HOLDOPT = Fixed Output (OP) SPLOLM to
SPHILM, when HOLDOPT = Fixed Set Point (SP) or Ramped Set Point (SP) (NaN,
0.0, or positive and negative real numbers)
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related HOLDOPT
Parameters
Remarks Defines a value for OP when HOLDOPT = FixedOP, or a value for SP when
HOLDOPT = FixedSP, or a value for SPTV when HOLDOPT = RampedSP. Note: If the
Man and Cas modes are not supported, then corresponding error should be
displayed while configuring or loading. Also, the value box should be disabled.

- 1263 -
Chapter 10 - Hxxxx Parameters

10.142 HOSTIPPRI

Specific to ACE, OPC, SIM_C200, SIMIOLIM, SIMEHPM


Block(s)
Description Host IP for Primary - Specifies the Internet Protocol (IP) address for the node
hosting the program.
Data Type String
Range N/A
Default N/A
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence SR
Related HOSTNAMEPRI
Parameters
Remarks Using an IP address instead of the host name results in a more robust and least
error prone communication path configuration between the Server and the given
node.

Specific to Inter Cluster Gateway


Block(s)
Description Host IP Address - Identifies the machine that the Inter Cluster Gateway will
communicate with as a client. This field should be filled in with the same value as
GWHOSTIPPRI when using the Inter Cluster Gateway in conjunction with an OPC
Gateway block, or it should be filled in with the value of the other cluster's Inter
Cluster Gateway when using two Inter Cluster Gateway blocks
Data Type String
Range N/A
Default N/A
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence SR
Related HOSTNAMEPRI
Parameters
Remarks Using an IP address instead of the host name results in a more robust and least
error prone communication path configuration between the Server and the given
node.

Specific to Block(s) UOC, CN100


Description Host IP Address
Data Type STRING
Range N/A
Default 0.0.0.0

- 1264 -
Chapter 10 - Hxxxx Parameters

Config Load Yes


Active Loadable
Access Lock APPDEVONLY
Residence SR
Related Parameters
Remarks

10.143 HOSTNAME

Specific to Block ACE


Description Host name monitor
Data Type STRING
Range
Default Not Applicable
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters HOSTIPPRI
Remarks

10.144 HOSTNAMEPRI

Specific to Block ACE, OPC, SIM_C200, SIMIOLIM, SIMEHPM


(s)
Description Host Name for Primary - Specifies the network name for the node hosting
the program.
Data Type String
Range N/A
Default N/A
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related HOSTIPPRI
Parameters
Remarks

- 1265 -
Chapter 10 - Hxxxx Parameters

Specific to Inter Cluster Gateway


Block(s)
Description Host Name - Identifies the machine that the Inter Cluster Gateway will
communicate with as a client. This field should be filled in with the same value as
GWHOSTNAMEPRI when using the Inter Cluster Gateway in conjunction with an
OPC Gateway block, or it should be filled in with the name of the other cluster's
Inter Cluster Gateway when using two Inter Cluster Gateway blocks
Data Type String
Range N/A
Default N/A
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence SR
Related HOSTNAMEPRI
Parameters
Remarks Using an IP address instead of the host name results in a more robust and least
error prone communication path configuration between the Server and the given
node.

Specific to Block(s) UOC, CN100


Description Host Name
Data Type STRING
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SR
Related Parameters
Remarks

- 1266 -
Chapter 10 - Hxxxx Parameters

10.145 HOSTSOESTS

Specific to Block(s) TCMI


Description Host SOE
Data Type STRING
Range N/A
Default --
Config Load No
Active Loadable N/A
Access Lock ViewONLY
Residence NOLOAD
Related Parameters

Remarks

10.146 HOUR

Specific to CEEC300, ACE, CPM, SIM_C200, CEEUOC, CEECN100


Block(s)
Description Current Hour
Data Type 32-Bit integer
Range 0 to 23
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE, C200, SIM_C200, UOC(CEEUOC), CN100(CEECN100)
Related DAYLIGHTTIME, TIMEZONE.
Parameters
Remarks Defines the hour component of the Controller's local time. Wall Clock Time (WCT) is
being lost during loss of power (that is, the controller has no built-in clock) and
cannot be restored in RAM retention restart scenario. Hence, the controllers may
be operating without a time source and this parameter returns a permanent zero
value.

- 1267 -
Chapter 10 - Hxxxx Parameters

10.147 HPHYSIG

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description HART Physical Signaling Code -Refer to byte 7 of HART Command 0 as defined in
HCF_Spec-127 Section 6.1 (Revision 6.0) for more details. Also refer to HCF_SPEC-
183 Section 5.10 Table 10 (Revision 13.0).
Data Type Enumeration
Range 0 Bell 202 Current
1 Bell 202 Voltage
2 RS-485
3 RS-232
6 Special
7 Reserved
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

10.148 HPM_CNTRLPERSREV

Specific to Block(s) EHPM


Description Control Processor Revision of EHPM Personality
Data Type UINT16
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related Parameters HPM_CNTRLPERSVER
Remarks This shows the revision of EHPM Controller processor personality.

- 1268 -
Chapter 10 - Hxxxx Parameters

10.149 HPM_CNTRLPERSVER

Specific to Block(s) EHPM


Description Control Processor Version of EHPM Personality
Data Type UINT16
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related Parameters HPM_CNTRLPERSREV
Remarks This shows the version of EHPM controller processor personality.

10.150 HPM_COMMPERSREV

Specific to Block(s) EHPM


Description Communication Processor Revision of EHPM Personality
Data Type UINT16
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related Parameters HPM_COMMPERSVER
Remarks This shows the revision of EHPM communication processor personality.

10.151 HPM_COMMPERSVER

Specific to Block(s) EHPM


Description Communication Processor Version of EHPM Personality
Data Type UINT16
Range N/A
Default N/A
Config Load No
Active Loadable No

- 1269 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence EHPM
Related Parameters HPM_COMMPERSREV
Remarks This shows the version of EHPM communication processor personality.

10.152 HPM_FWREV

Specific to Block(s) EHPM


Description EHPM Firmware Revision number
Data Type UINT16
Range N/A
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related Parameters N/A
Remarks EHPM Firmware Revision number

10.153 HPM_HWREV

Specific to Block(s) EHPM


Description EHPM Hardware Revision number
Data Type UINT16
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related Parameters N/A
Remarks EHPM Hardware Revision number

- 1270 -
Chapter 10 - Hxxxx Parameters

10.154 HPM_IOL_HWREV

Specific to Block(s) EHPM


Description EHPM IO Link Hardware Revision
Data Type UINT16
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related Parameters N/A
Remarks This is the hardware revision number of IO link connected to the EHPM.

10.155 HPMNODENO

Specific to EHPM
Block(s)
Description EHPM node number in EUCN network. This number must be unique to an EUCN
network.
Data Type INT32
Range 3 to 64 (1 is always assigned to ENIM)
Default 0
Config Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related UCNNW
Parameters
Remarks This value must be entered between the range of 3 to 64. In this range the odd
numbers are configurable and even numbers are not configurable (redundant
nodes are automatically assigned with an even number). For an EUCN network,
there must be a unique number for EHPM node number and the same EHPM
node number can be used across different EUCN networks.

- 1271 -
Chapter 10 - Hxxxx Parameters

10.156 HPMSOFTFAIL

Specific to EHPM
Block(s)
Description HPM Soft Failures (See TPS Native Window for details), shows the soft failures
that have occurred from TPS side.
Data Type BOOLEAN
Range NA
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence No Load
Related
Parameters
Remarks This is just an indicator and more detailed information about the soft failure is
available on the TPS Native Window.

10.157 HPVALMCODE

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description PV Alarm Selection Code -HART PV Alarm Selection Code as defined in HCF_Spec-
183 Section 5.6 Table 6 (Revision 13).
Data Type Enumeration
Range 0 High
1 Low
239 Hold Last Value
240-249 Device Specific
250 Not Used
251 None
252 Unknown
253 Special
Default N/A
Config Load No
Active No
Loadable

- 1272 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related N/A
Parameters
Remarks

10.158 HPVCHAR

Specific to HAICHANNEL (PM I/O), PM I/O HART Channels


Block(s)
Description HART PV Characterization. Characterizes PV when the channel is HART enabled.
Range 26 “Device Range” selection provides same function as
PVCHAR set to Linear. Selection also generates and clears
Device PV Revision mismatch flag and associated alarm.
27 “SystemRange”, same function as PVCHAR set to Linear.
28 “SystemRangeAndSQRT”, same function as PVCHAR set to
SQRROOT.
Default Device Range
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence IOLIM
Related N/A
Parameters
Remarks HPVCHAR is shown on the Configuration tab. The CM or IOM containing the
channel must be re-loaded to affect a change.

10.159 HPVCHNFLAGS

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Pv Analog Channel Flags
Data Type 8-Bit Unsigned Integer, 8 independent bit fields
Range 0x00 Associated Field device does not have an
ADC attached to it.
0x01 Associated Field device does have an
ADC attached to it.
Default N/A
Config No
Load
Active No

- 1273 -
Chapter 10 - Hxxxx Parameters

Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks HART Revision 6.0 and later only HART Analog Channel Flags as retrieved by HART
command 15 and as defined in HCF_Spec 183 Section 5.26 Table 26 (Revision 13).
Multiple bits can be set at the same time. This parameter, while not shown on any
tab, can be face-plated and made an output from the block.

10.160 HPVDAMP

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description HART PV Damping range value (Units in seconds)
Data Type FLOAT32
Range Device specific
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

10.161 HPVLRV

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description PV Lower Range Value
Data Type FLOAT32
Range Device specific
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

- 1274 -
Chapter 10 - Hxxxx Parameters

10.162 HPVMISM

Specific to HAICHANNEL (PM I/O) AICHANNEL (Series C I/O), PM I/O HART Channels
Block
Description Device PV Range Mismatch
Data Type Boolean
Range 1 ON The HART device that is currently connected to the channel
does not match the configured HART device type in the
control strategy. One or more of the following conditions is
true:
l PVEXEUHI = HTDURL
l PVEUHI = HPVURV
l PVEULO = HPVLRV
l PVEXEULO = HTDLRL

0 OFF The device PV characterization values match: PVEXEUHI,


PVEUHI, PVEXEULO, and PVEULO
Default OFF
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDEVSTPVEXEUHIPVEUHIPVEXEULOPVEULO
Parameters
Remarks The channel cannot be activated when HPVMISM is set. A configuration mismatch
will occur.

10.163 HPVTLDST

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), AICHANNEL and AOCHANNEL (Series
Block C I/O), PM I/O HART Channels
Description Private Label Distributor
Data Type Enumeration
Range 1 to 625535 → Values 250 through 24576 are reserved for HART. Reference HCF_
Spec-183 Section 5.8 Table 8 (Revision 20) for more details.
Default
Config Load No
Active No
Loadable

- 1275 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks HART Private Label Distributor as received in HART command 0 and as defined in
HCF_Spec-183 Section 5.8 Table 8 (Revision 20)

10.164 HPVURV

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description PV Upper Range Value
Data Type FLOAT32
Range Device specific
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

- 1276 -
Chapter 10 - Hxxxx Parameters

10.165 HPVXFRCODE

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description PV Transfer Function Code -HART PV Transfer Function Code as defined in HCF_
Spec-183 Section 5.3 Table 3 (Revision 13).
Data Type Enumeration
Range 0 Linear
1 Square Root
2 Square Root Third Power
3 Square Root Fifth Power
4 Special Curve
5 Square
230 Discrete (Switch)
231- 233 Do not use
240- 249 Device Specific
250 Not Used
251 None
252 Unknown
253 Special
Default N/A
Config Load No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

10.166 HREVMISM

Specific to HAICHANNEL and HAOCHANNEL


Block(s)
Description Device Revision Mismatch
Data Type Boolean
Range 1 ON The HART device that currently exists at the end of the wire is different
from the device that the user thought would exist at the end of the
wire. A device revision occurs whenever HDVMFGCD is the same as
HDEVMFG and HDVTYPCD is the same as HDEVTYP and HDVREVCD
is different from HDEVREV. HDEVMISM and HREVMISM are mutually
exclusive in that only one can be set at any given time. Note that the
Generic HART Device matches EVERY HART device.
0 OFF There is a match between the user-configured HART device and the
actual device.

- 1277 -
Chapter 10 - Hxxxx Parameters

Default OFF
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence IOM
Related HDEVST, HTMPLATE, HDEVMFG, HDVMFGCD, HDEVTYPE, HDVTYPCD, HDEVREV,
Parameters HDVREVCD
Remarks

10.167 HSCANCFG

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL (Series C


Block I/O), PM I/O HART Channels
Descriptio Scan HART Variables - Sets the frequency for the scanning of HART device and/or
n dynamic variable data for HART devices connected to IOP channels.
Data Type Enumeration
Range User Scan HCU Note
Enu Selectio Scanne Interval Percent HDEVRAT HDYNRAT
m n d In Sec. Used E E
Value Variable Capacit
(s) y
4 1
Modem Mode
m
1 1S Device 1 30% NA 2 16 0
Device
2 1S 1 30% NA 2 0 16
Dynamic Dynami
c
3 2S Device 2 12.5% 50% 2 8 0
Device
4 2S 2 12.5% 50% 2 0 8
Dynamic Dynami
c
5 2S Dev Device 2 30% NA 2 8 8
& Dyn and
Dynami
c
6 4S Device 4 6.25% 25% 1 4 0
Device
7 4S 4 6.25% 25% 1 0 4
Dynamic Dynami
c
8 4S Dev Device 4 12.5% 50% 2 4 4
& Dyn and

- 1278 -
Chapter 10 - Hxxxx Parameters

Dynami
c
9 8S Device 8 3.13% 12.5% 3 2 0
Device
10 8S 8 3.13% 12.5% 3 0 2
Dynamic Dynami
c
11 8S Dev Device 8 6.25% 25% 1 2 2
& Dyn and
Dynami
c

12 16S Device 16 1.6% 6.25% N/A 1 0


Device
13 16S 16 1.6% 6.25% N/A 0 1
Dynamic Dynami
c
14 16S Dev Device 16 3.13% 12.5% 3 1 1
& Dyn and
Dynami
c
15 Status N/A N/A 1.12.1 1.12.2 1.12.3 N/A 1.12.4 0 1.12.
Only 1.6% 6.25% 50
Default 16S Dynamic 1.6% (13)
Config Yes
Load
Active No
Loadable

- 1279 -
Chapter 10 - Hxxxx Parameters

Access Application Developer


Lock
Residence IOM
Related HDYNNAME[1..4]HDYNDVC HSLOTNAME[1..HSLOTVARIDX]HSLOTDVC
Parameter [1..4]HDYNDESC[1..4]HDYNST [1..HSLOTVARIDX]HSLOTDSC
s [1..4]HDYNEU[1..4] [1..HSLOTVARIDX]HSLOTVAL
[1..HSLOTVARIDX]HSLOTEU[1..8]
Remarks 1. Maximum number of HART communication units (HCU) available in an IOM is
mapped to 100%. You can determine how to share these units by setting
HSCANCFG for each channel in the IOM. The particular number of HCU's is a
technical detail that does not concern you. However, you need to know what
percentage of HCU's are being consumed by each configuration setting.
2. The range settings can be explained as follows: The “User Selection” in the
second column will provide for the variables in the third column to be
scanned at the interval in the fourth column. Doing so will consume the
percentage of the IOM's HCUs given in the fifth/sixth column. The seventh
column (Notes) are explained below and the final two columns are technical
information for the IOM team if these IOMs are made available in TDC.
3. To achieve the maximum scanning rate while sharing HCU's evenly, you
must select a note 1 choice for each channel in the IOM. This is driven from
the fact that if the 16 channels in an IOM equally use 100% of the available
HART communication units then (100/16 = 6.25) each channel will be
allocated 6.25% of the total bandwidth.
4. However, it is possible that you will require a faster polling rate on one device
than another device. In that case, you can select a note 2 choice to allocate
additional HCU's to one channel. In turn to avoid HART scanning overruns,
you must then lessen the number of HCU's for another channel.
Refer to Section 4.7.2.5 Scanning HART Device Variables in the PMIO Integration
DFS for a Description of scenarios on HART communication units.

10.167.1 AICHANNEL and AOCHANNEL for UIO-2 Blocks:

Specific to AICHANNEL and AOCHANNEL for UIO-2


Block(s)
Description Scan HART Variables
Data Type ENUM
Range Enum Value User Selection Scanned Variable(s)
15 Status Only N/A
16 Device Only Device
17 Dynamic Only Dynamic
18 Dev & Dyn Device and Dynamic
Default Dynamic Only (17)
Config Load Yes

- 1280 -
Chapter 10 - Hxxxx Parameters

Access Lock Application Developer


Residence IOM
Related HSCANTIME
Parameters
Remarks l The requested variables are scanned continuously.
l The actual update rate is provided in seconds by HSCANTIME.
l Update rate if affected by the number of configured Device Variables.
l Update rate is affected by FDM pass-through traffic and device indications
such as More Status Available or Configuration Changed.

10.168 HSCANOVR

Specific to HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL , AOCHANNEL (Series C


Block I/O), PM I/O HART Channels
Description HART Scan overrun.
Data Type Boolean
Range ON Dynamic and/or device variables on this channel
have not been scanned at the configured scan
rate (HSCANCFG) within the last minute. See
Remarks below.
OFF No scan overruns have been detected within the
last minute.
Default OFF
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related HDEVSTHSCANCFG
Parameters
Remarks When scan overruns occur, steps should be taken to ensure that HART digital data
is being collected at the rate required by the process. Re-configure channel and/or
other channels of the associated IOM.

10.169 HSCANTIME

Specific to AICHANNEL and AOCHANNEL for UIO-2


Block
Description Scan HART Variables
Data Type FLOAT64
Range N/A

- 1281 -
Chapter 10 - Hxxxx Parameters

Default N/A
Config Load No
Access Lock ViewOnly
Residence IOM
Related HSCANCFG
Parameters
Remarks Displays the update rate for the HART variables requested by HSCANCFG.
Displayed value is in Seconds.

10.170 HSLOT0TS

Specific to
Block(s) HAICHANNEL, SERIES C AOCHANNEL, SERIES C AICHANNEL
Description Slot0 Data Time Stamp
Data Type TIME
Range 00:00:00 to 23:59:59
Default 00:00:00
Config Load No
Active
Loadable No
Access Lock View Only
Residence PGM
Related
Parameters

Time Stamp is monotonic and rollover. Time stamp of HART Device/Dynamic


Remarks variable is read for every 24 hours.

10.171 HSLOTCC [1..HSLOTVARIDX] (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Classification
Data Type Enumeration
Range See HCF_Spec-183 Section 5.21 Table 21 (Revision 13.0) for more details.
Default Not Classified
Config Load No
Active No
Loadable

- 1282 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks HART Classification codes for slot 0 variable, slot 1variable, slot 2 variable and up to
slot 7 variable. Only valid for HART 6 and later version devices. This parameter is
only exposed when HENABLE = TRUE.

10.172 HSLOTDSC[1..HSLOTVARIDX]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Descriptor -Description for slot 0 variable, slot 1variable, slot 2 variable, and up to
slot 7 variable.
Data Type String
Range Maximum of 32 Characters
Default None (The 4 array values are blank.)
Config Load No
Active No
Loadable
Access Lock Application Developer
Residence SR
Related HSLOTNAME[1..HSLOTVARIDX]HSLOTDVC[1..HSLOTVARIDX]HSLOTVAL
Parameters [1..HSLOTVARIDX]HSLOTEU[1..8]
Remarks

10.173 HSLOTDVC[1..HSLOTVARIDX]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Variable Code -Slot 0, Slot 1, Slot 2 and Slot 3 Device Variable Codes.
Data Type Enumeration
Range 250 None There is no Slot n variable

0 Variable 000 Read device specific


variable 0.
1 Variable 001 Read device specific
variable 1
through Excluding 25
255 Variable 255 Read device specific
variable 255.
Default None
Config Load Yes

- 1283 -
Chapter 10 - Hxxxx Parameters

Active No
Loadable
Access Lock Application Developer
Residence IOM
Related HSLOTNAME[1..HSLOTVARIDX]HSLOTDSC[1..HSLOTVARIDX]HSLOTVAL
Parameters [1..HSLOTVARIDX]HSLOTEU[1..8]
Remarks

10.174 HSLOTEU[1..8]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Units -HART Engineering Units for slot0 variable, slot1variable, slot2 variable and
slot3 variable.
Data Type Enumeration
Range See HCF_Spec-183 Section 5.2 Table 2 (Revision 20) for more details.
Default UNKNOWN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HSLOTNAME[1..HSLOTVARIDX]HSLOTDVC[1..HSLOTVARIDX]HSLOTDSC
Parameters [1..HSLOTVARIDX]HSLOTVAL [1..HSLOTVARIDX]
Remarks HART Engineering Units for slot 0 variable, slot 1variable, slot 2 variable and up to
slot 7 variable.

10.175 HSLOTNAME[1..HSLOTVARIDX]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Name - Slot0, Slot1, Slot2 and Slot3 Name.
Data Type String
Range Maximum 24 Characters

- 1284 -
Chapter 10 - Hxxxx Parameters

Default Array Index Default Value

1 Slot 0 Variable
2 Slot 1 Variable
3 Slot 2 Variable
4 Slot 3 Variable
5 Slot 4 Variable
6 Slot 5 Variable
7 Slot 6 Variable
8 Slot 7 Variable
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related HSLOTDVC[1..HSLOTVARIDX]HSLOTDSC[1..HSLOTVARIDX]HSLOTVAL
Parameters [1..HSLOTVARIDX]HSLOTEU[1..8]
Remarks

10.176 HSLOTST [1..HSLOTVARIDX] (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Status
Data Type BITS, mapped as per HCF_Spec-99 Section 8.4 Device Variable Status
Range See HCF_Spec-99 Section 8.4 (Revision 8) and HDYNST[1..4] for more details.
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDYNCC[1..4], HDYNEU[1..4], HSLOTCC [1..HSLOTVARIDX] (HART Revision 6.0 and
Parameters later), HNSMMINPRE (HART Revision 6.0 and later), HMAXDEVVARS (HART
Revision 6.0 and later), HNCFGCHG (HART Revision 6.0 and later), HEXTDEVST,
HPVCHNFLAGS, HDYNST[1..4], HARTVERSION, HDEVSTSTATUS
Remarks HART Variable status for slot 0 variable, slot 1 variable, slot 2 variable and up to slot
7 variable. Only valid for HART 6 and later version devices. Only the 5 highest order
bits are mapped into the range. Thus, 8 different values from the device will provide
the same enumeration value to the user. This parameter is only exposed when
HENABLE = TRUE.

- 1285 -
Chapter 10 - Hxxxx Parameters

10.177 HSLOTVAL [1..HSLOTVARIDX]

Specific to HAICHANNEL and HAOCHANNEL (PM I/O); AICHANNEL (Series C I/O), PM I/O
Block HART Channels
Description Value
Data Type FLOAT32
Range Device Specific
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HSLOTNAME[1..HSLOTVARIDX]HSLOTDVC[1..HSLOTVARIDX]HSLOTDSC
Parameters [1..HSLOTVARIDX]HSLOTEU[1..8]
Remarks HART slot 0 value, slot 1 value, slot 2 value and up to slot 7 value.

10.178 HSMSTRFL

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Secondary Master present flag.
Data Type Boolean
Range 0 OFF A secondary master was not detected on the wire
between the IOM and the HART device within the
past three minutes.
1 ON A secondary master has been detected on the wire
between the IOM and the HART device within the
past three minutes.
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks A secondary master is said to be present if a transaction from a secondary master
was detected by the IOM.

- 1286 -
Chapter 10 - Hxxxx Parameters

10.179 HSTLANIDERRS

Specific to Block(s) UOC


Description HSR or PRP have non-zero LAN ID Errors on either or both cables.
Data Type Soft Failure
Range
Default
Config Load
Active Loadable
Access Lock
Residence
Related Parameters
Remarks This indicates a cabling issue:
HSR: incorrect top-to-bottom connections
PRP: a connection between the two independent network trees.

10.180 HSLOTVARIDX

Specific to PM I/O: HAICHANNEL, HAOCHANNEL Series C I/O: AICHANNEL, AOCHANNEL, PM


Block I/O HART Channels
Description Number of Slot Variables
Data Type UINT8
Range N/A
Default 8
Config Yes
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related HSLOTEU[1..8]HSLOTVAL [1..HSLOTVARIDX]HSLOTDSC
Parameters [1..HSLOTVARIDX]HSLOTDVC[1..HSLOTVARIDX]HSLOTNAME
[1..HSLOTVARIDX]HSLOTST [1..HSLOTVARIDX] (HART Revision 6.0 and
later)HSLOTCC [1..HSLOTVARIDX] (HART Revision 6.0 and later)
Remarks The related parameters use HSLOTVARIDX as their array dimension. The value of
HSLOTVARIDX is set to 4 or 8 based on the controller firmware version
automatically. If the controller firmware is of an older version, then HSLOTVARIDX
value will be set to 8 or else set to 4.

- 1287 -
Chapter 10 - Hxxxx Parameters

10.181 HSWDESC [0..63]

Specific to Blocks HRBALG_REG block


Description HSW Description
Data Type Array of strings
Range Not applicable
Default Values are specified in Regparams.arr.xml
Config. Load No
Active Loadable
Access Lock ViewOnly
Residence SR
Related HSWVALUE [0..63]
Parameters
Remarks This parameter contains the text that describes each word of the Hiway slot
emulation.

10.182 HSWREV

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Software Revision -Refer to HART Command 0 and as defined in HCF_Spec-127
Section 6.1 (Revision 6) for more details.
Data Type 8-Bit Unsigned Integer
Range 0 to 253 only, 254 and 255 are reserved.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

10.183 HWREVMAJ

Specific to Block(s) IO RACK


Description Hardware Version
Data Type UINT16
Range

- 1288 -
Chapter 10 - Hxxxx Parameters

Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence IO RACK
Related Parameters
Remarks

10.184 HWREVMIN

Specific to Block(s) IO RACK


Description Hardware Version
Data Type STRING
Range
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence IO RACK
Related Parameters
Remarks

10.185 HSWVALUE [0..63]

Specific to HRBALG_REG block


Blocks
Description HSW Values
Data Type UINT16
Range 0-65535
Default 0
Config. Load Yes
Active
Loadable
Access Lock AppDevOnly
Residence CEE
Related HSWDESC [0..63]
Parameters
Remarks This parameter contains the value for each word of the Hiway slot emulation.
AIHSW/AIHSWVALUE/AOHSWDESC/AOHSWVALUE

- 1289 -
Chapter 10 - Hxxxx Parameters

10.186 HWTYPE

Specific to Block(s) UOC, C300


Description Hardware Type
Data Type STRING
Range N/A
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (hardware statistics, see C300 definition)

10.187 HWYNUM

Specific to Experion Hiway Bridge (EHB) platform block, ELCN_NODE (EHB)


Blocks
Description Logical Hiway number
Data Type Integer
Range 0 to 20
Default 0
Config. No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the number by which the Hiway box (TDC2000 Hiway) was
known on the LCN when the Hiway’s HG was migrated to EHB. This is an LCN-local
number which is not globally unique. In addition, this parameter is used to indicate
EHBs, CEEs, and Box HRBs which are associated with the same Hiway emulation
under the same Experion Server cluster.

NOTE This parameter is always configured regardless of whether


DFNPHWYEM is ON or OFF. When DFNPHWYEM is OFF, HWYNUM
allows the partner EHB with DFNPHWYEM is ON to be located.

- 1290 -
Chapter 10 - Hxxxx Parameters

10.188 HWYNUM1

Specific to CEE platform block


Blocks
Description Logical Hiway Num 1
Data Type Integer
Range 0-20
Default 0
Config. No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the logical Hiway number of one of up to two EHBs which
have “This EHB” relationships with box emulations assigned to this CEE. The CEE
and the designated EHB always belong to the same Experion Server cluster.

NOTE HWYNUM1 is the only parameter on the CEE platform


configuration form related to attributes of Hiway emulation which is
configured. It allows the EHB to which defines the Hiway emulation to be
identified so that remaining Hiway configuration of the CEE can be
populated at time of load. HWYNUM1 must indicate the HWYNUM value
of an EHB which has DFNPHWYEM set to ON.

10.189 HWYNUM2

Specific to CEE platform block


Blocks
Description Logical Hiway Num 2
Data Type Integer
Range 0-20
Default 0
Config. No
Load
Active No
Loadable

- 1291 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence SR
Related
Parameters
Remarks This parameter specifies the logical Hiway number of one of up to two EHBs which
have “This EHB” relationships with box emulations assigned to this CEE. The CEE
and the designated EHB always belong to the same Experion Server cluster. When
the CEE platform block is loaded, HWYNUM2 is populated automatically based on
the EHB indicated by HWYNUM1.

10.190 HWYNUMADDED

Specific to Box Hiway Responder Block (HRB)


Blocks
Description Logical Hiway Number of the EHB configures as "Added EHB"
Data Type UINT32
Range 0 to 20
Default 0
Config. No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the Logical Hiway Number of the EHB in the same ESV-T
cluster which does not own the box emulation, if any. This parameter can be NULL
or non-NULL. This parameter is assigned automatically when the Box HRB is
loaded based on the value of HWYNUMTHIS. This parameter always matches
EHB.HWYNUMPART of the EHB whose EHB.HWYNUM matches HWYNUMTHIS.

10.191 HWYNUMPRT

Specific to Experion Hiway Bridge (EHB) platform block, ELCN_NODE (EHB)


Blocks
Description Logical Hiway number partner
Data Type Integer
Range 0 to 4
Default 0
Config. No
Load
Active
Loadable

- 1292 -
Chapter 10 - Hxxxx Parameters

Access ViewOnly
Lock
Residence SR
Related
Parameters
Remarks This parameter specifies the logical Hiway number of the EHB, if any, which is
connected to the same LCN under the same Experion Server cluster and which had
been connected to the same physical Hiway through a partner HG. This is an LCN-
local number which is not globally unique. When DFNPHWYEM is set to OFF,
HWYNUMPRT remains unconfigured in the form. Instead, when the EHB platform
block is loaded it is populated automatically based on the partner EHB indicated by
the HWYNUM parameter.

10.192 HWYNUMTHIS

Specific to Box Hiway Responder Block (HRB)


Blocks
Description Logical Hiway Number of the EHB configured as "ThisEHB"
Data Type UNIT32
Range 0 to 20
Default 0
Config. No
Load
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the Logical Hiway Number of the EHB which owns the box
emulation. When HWYNUMTHIS is specified, related parameters are configured
automatically.

10.193 HTAG

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O) ; AICHANNEL, AOCHANNEL


(Series C I/O)
Description Tag
Data Type String
Range 8-character string
Default N/A
Config Load No
Active Loadable No

- 1293 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related N/A
Parameters
Remarks

10.194 HTDEU

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Engineering Units
Data Type Enumeration
Range Reference HCF_Spec-183 Section 5.2, Table 2 (Revision 13). Values between 0 and
255 that are not defined in the table are shown as “UNKNOWNxxx,” where xxx is
the undefined number.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART Transducer Limits and Minimum Span Engineering Units as defined in HCF_
Spec-127 Section 6.13 (Revision 6.0).

10.195 HTDLRL

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels
Description Lower Transducer Limit
Data Type FLOAT32
Range N/A, Device specific
Default N/A, Device specific
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

- 1294 -
Chapter 10 - Hxxxx Parameters

10.196 HTDMINSPAN

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O)


Description Minimum Span
Data Type FLOAT32
Range N/A, Device specific
Default N/A, Device specific
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks HART Transducer Minimum Span as defined in HCF_Spec-127 Section 6.13
(Revision 6.0)

10.197 HTDSN

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O)


Description Transducer Serial Number
Data Type 32-Bit Unsigned Integer
Range 0 to 16,777,215
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

10.198 HTDURL

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O)


Description Upper Transducer Limit
Data Type FLOAT32
Range N/A, Device specific
Default N/A, Device specific
Config Load No
Active Loadable No

- 1295 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related Parameters N/A
Remarks

10.199 HUCMDREV

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Universal Command Revision -Refer to HART Command 0 and as defined in HCF_
Spec-127 Section 6.1 (Revision 6) for more details.
Data Type Enumeration
Range 0-3, 7-255 UNKNOWN ###, where ### is 0
through 3 or 7 through 255
4 HART Revision 4
5 HART Revision 5
6 HART Revision 6
7 HART Revision 7
8 HART Revision 8
Default UNKNOWN 000
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks HART IOMs and IOLIMs have been designed and tested to work only with HART
revision 5, 6, and 7 devices. For more information refer to HART Command 0 and as
defined in HCF_Spec-127 Section 6.1 (Revision 7).

10.200 HVARALERT (HART Revision 6.0 and later)

Specific to AICHANNEL, AOCHANNEL (Series C I/O)


Block(s)
Description Device Variable Alert
Data Type Boolean
Range 0 OFF No device variables are in an
alarm or warning state.
1 ON One or more device variables are
in an alarm or warning state.

- 1296 -
Chapter 10 - Hxxxx Parameters

Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related HDEVSTSTATUS, HARTVERSION
Parameters
Remarks Refer to HCF_Spec-183 Section 5.25, Table 17 (Revision 13) for more details. Only
valid on HART revision 6 and later version devices.

10.201 HWFAULT

Specific to Block(s) DIC


Description Hardware fault detected.
Data Type Boolean
Range No Fault Detected (0) Fault Detected (1)
Default No Fault Detected (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

10.202 HWFAULT[0..numChans-1]

Specific to Block(s) DIM


Description Hardware fault detected.
Data Type Boolean
Range No Fault Detected (0) Fault Detected (1)
Default No Fault Detected (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 1297 -
Chapter 10 - Hxxxx Parameters

10.203 HWREVMAJ

Specific to Block(s) C300, PGM, FIM4, EHPM, TCMI


Description Hardware Major Revision.
Data Type 16-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, PGM, EHPM
Related Parameters HWREVMIN
Remarks

Specific to Block(s) EIM


Description Hardware Version
Data Type UINT16
Range 0 to 65535
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters HWREVMIN
Remarks

Specific to Block(s) UOC


Description Hardware Version
Data Type UINT16
Range 0 to 65535
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (hardware statistics, see C300 definition)

Specific to Block(s) IO RACK


Description Hardware Version
Data Type UINT16
Range

- 1298 -
Chapter 10 - Hxxxx Parameters

Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IO RACK
Related Parameters
Remarks

10.204 HWREVMIN

Specific to Block(s) C300, PGM, FIM4, EHPM, TCMI


Description Hardware Minor Revision.
Data Type 16-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, PGM, EHPM
Related Parameters HWREVMAJ
Remarks

Specific to Block(s) EIM Platform Block


Description Hardware Revision
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

Specific to Block(s) UOC


Description Hardware Revision
Data Type STRING
Range N/A
Default
Config Load No
Active Loadable

- 1299 -
Chapter 10 - Hxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks (hardware statistics, see C300 definition)

Specific to Block(s) IO RACK


Description Hardware Version
Data Type String
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IO RACK
Related Parameters
Remarks

10.205 HWRTPRCTCODE

Specific to HAICHANNEL and HAOCHANNEL (PM I/O), PM I/O HART Channels


Block
Description Write Protect Code -HART Write Protect Code as defined in HCF_Spec-183
Section 5.7 Table 7 (Revision 13)
Data Type Enumeration
Range 0 No Not Write Protected
1 Yes Write Protected
240-249 Device Specific
250 Not Used
251 None
252 Unknown
253 Special
Default Unknown (252)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks

- 1300 -
Chapter 10 - Hxxxx Parameters

10.206 HWTEMP

Specific to Block(s) TCMI


Description Hardware Temperature DEG C
Data Type FLOAT64
Range N/A
Default 30
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

10.207 HYEAR

Specific to Block HAICHANNEL and HAOCHANNEL (PM I/O)


Description Year
Data Type 16-Bit Unsigned Integer
Range 1900 to 2155
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related Parameters HMONTHHDAY
Remarks N/A

10.208 HelpTxt1

Specific to EIM
Block(s)
Description HelpTxt1
Data Type STRING
Range NA
Default Note: Renaming of Alias Name here in source MMSSUBS block may need
renaming of Alias Name in associated destination DSIN block(s).
Config Load No

- 1301 -
Chapter 10 - Hxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence ERDBONLY
Related
Parameters
Remarks

- 1302 -
CHAPTER

11 IXXXX PARAMETERS

11.1 IACYCCONNIMRS[1..IPEERCONNMAX] 1314


11.2 IACYCCONNLRQS[1..IPEERCONNMAX] 1314
11.3 IACYCCONNSRQS[1..IPEERCONNMAX] 1315
11.4 IACYCIMRAVAIL 1315
11.5 IACYCIMRMAX 1316
11.6 IACYCIMRUSED 1316
11.7 IACYCIMRUSEDCONN [0...29] 1317

11.8 IACYCLGREQAVAIL 1317


11.9 IACYCLGREQMAX 1318
11.10 IACYCLGREQUSED 1318
11.11 IACYCLGREQUSEDCONN [0...29] 1319
11.12 IACYCSMREQAVAIL 1319
11.13 IACYCSMREQMAX 1319
11.14 IACYCSMREQUSED 1320
11.15 IACYCSMREQUSEDCONN [0...29] 1320
11.16 IBVOPNFDBK 1321
11.17 IBVOPNFDBKSTS 1321
11.18 IBVVLVFDBKTO 1321
11.19 IC.BYPPERM 1322
11.20 IC.BYPREQ 1322
11.21 IC.CONFIGCODE 1323
11.22 IC.CONFIGDESC 1324
11.23 IC.CONFIGSTS 1324
11.24 IC.DESC 1324
11.25 IC.EXECCODE 1325
11.26 IC.EXECDESC 1325
11.27 IC.EXECSTS 1326
11.28 IC.EXPR 1326
11.29 IC.EXPRPCODE 1326
11.30 IC.FL 1327
11.31 IC.INVOKFL 1327
11.32 ICINCONNHNDL[1..6] 1328

- 1303 -
Chapter 11 - Ixxxx Parameters

11.33 ICINCONNNAV[1..6] 1328


11.34 ICINCONNPRM[1..6] 1328
11.35 ICINCONNSTRVAL[1..6] 1329
11.36 ICINCONNVAL[1..6] 1329
11.37 ICMPINADDRMASKREPS 1330
11.38 ICMPINADDRMASKS 1330
11.39 ICMPINCSUMERRORS 1330
11.40 ICMPINDESTUNREACHS 1331
11.41 ICMPINECHOREPS 1331
11.42 ICMPINECHOS 1332
11.43 ICMPINERRORS 1332
11.44 ICMPINMSGS 1333
11.45 ICMPINPARAMPROBS 1333
11.46 ICMPINREDIRECTS 1333

11.47 ICMPINSRCQUENCHS 1334


11.48 ICMPINTIMEEXCDS 1334
11.49 ICMPINTIMESTAMPREPS 1335
11.50 ICMPINTIMESTAMPS 1335
11.51 ICMPOUTADDRMASKREPS 1335
11.52 ICMPOUTADDRMASKS 1336
11.53 ICMPOUTDESTUNREACHS 1336
11.54 ICMPOUTECHOREPS 1337
11.55 ICMPOUTECHOS 1337
11.56 ICMPOUTERRORS 1338
11.57 ICMPOUTMSGS 1338
11.58 ICMPOUTPARAMPROBS 1339
11.59 ICMPOUTREDIRECTS 1339
11.60 ICMPOUTSRCQUENCHS 1339
11.61 ICMPOUTTIMEEXCDS 1340
11.62 ICMPOUTTIMESTAMPREPS 1340
11.63 ICMPOUTTIMESTAMPS 1341
11.64 ICNUMSRCCONN 1341
11.65 IC.OPT 1341
11.66 ICONSTATE 1342
11.67 ICPCODESIZE 1347
11.68 ICPMBUFALLOC 1347
11.69 ICPMBUFALLOC[0..3] 1348
11.70 ICPMBUFINUSE 1348
11.71 ICPMBUFINUSE[0..3] 1349

- 1304 -
Chapter 11 - Ixxxx Parameters

11.72 ICPMBUFMAX[0..3] 1349


11.73 ICPMBUFMIN 1350
11.74 ICPMBUFMIN[0..3] 1350
11.75 ICPMBUFSIZE 1350
11.76 ICPMBUFSIZE[0..3] 1351
11.77 ICPNAKS[1..RPEERCONNMAX] 1351
11.78 ICPNAKSPERCONN 1352
11.79 ICPNOBUFSPERCONN 1352
11.80 ICPPENDLMTPERCONN 1353
11.81 ICPSBUFALLOC 1353
11.82 ICPSBUFALLOC[0..3] 1354
11.83 ICPSBUFINUSE[0..3] 1354
11.84 ICPSBUFMIN 1355
11.85 ICPSBUFMIN[0..3] 1355

11.86 ICPSBUFSIZE 1356


11.87 ICPSBUFSIZE[0..3] 1356
11.88 ICPSENDFAIL 1357
11.89 ICPSENDFAIL[1..RPEERCONNMAX] 1357
11.90 ICPSENDFAILPERCONN 1358
11.91 ICPSENDNOBUFS 1358
11.92 ICPSENDPENDLIMIT[1..RPEERCONNMAX] 1359
11.93 ICPSENDXMTTO[1..RPEERCONNMAX] 1359
11.94 ICPTIMEOUTPERCONN 1360
11.95 ICPSTATRESET 1360
11.96 ICSRC[1..6] 1361
11.97 ICYCCONNIMRS[1..IPEERCONNMAX] 1361
11.98 ICYCCONNLRQS[1..IPEERCONNMAX] 1362
11.99 ICYCCONNSRQS[1..IPEERCONNMAX] 1362
11.100 ICYCIMRAVAIL 1363
11.101 ICYCIMRMAX 1363
11.102 ICYCIMRUSED 1364
11.103 ICYCIMRUSEDCONN [0...29] 1364
11.104 ICYCLGREQAVAIL 1365
11.105 ICYCLGREQMAX 1365
11.106 ICYCLGREQUSED 1366
11.107 ICYCLGREQUSEDCONN [0...29] 1366
11.108 ICYCSMIOREQUSEDCONN 1366
11.109 ICYCSMREQAVAIL 1367
11.110 ICYCSMREQMAX 1367

- 1305 -
Chapter 11 - Ixxxx Parameters

11.111 ICYCSMREQUSED 1368


11.112 ICYCSMREQUSEDCONN [0...29] 1368
11.113 ID 1369
11.114 IDENTIFY 1369
11.115 IDLEMODE[0..7] 1370
11.116 IECDATATYPE 1370
11.117 IEDCONNECTIONSTATUS 1371
11.118 IEDNAME 1371
11.119 IEDOMAINNAME 1372
11.120 IEDSTATRESET 1372
11.121 IEDTAGNAME 1372
11.122 IECLINKINACTIVE 1373
11.123 IELDEVICENAME 1373
11.124 IFINDISCARDS 1374

11.125 IFINERRORS 1374


11.126 IFINNONUCASTPKTS 1375
11.127 IFINOCTETS 1375
11.128 IFINUCASTPKTS 1375
11.129 IFINUNKNOWNPROTOS 1376
11.130 IFOUTDISCARDS 1376
11.131 IFOUTERRORS 1377
11.132 IFOUTNONUCASTPKTS 1377
11.133 IFOUTOCTETS 1377
11.134 IFOUTQLEN 1378
11.135 IFOUTUCASTPKTS 1378
11.136 IFTRANS 1379
11.137 IGNORD 1379
11.138 IGNORDFL[1..6] 1379
11.139 IGNORHI 1380
11.140 IGNORLM 1380
11.141 IGNORLO 1381
11.142 IGNORTM 1381
11.143 IIMCOMMAND 1381
11.144 IIMLINKIOID 1382
11.145 IIMSTATE 1382
11.146 IIMTYPE 1383
11.147 IIOCS 1383
11.148 IIOPS 1384
11.149 IMAGEVER 1384

- 1306 -
Chapter 11 - Ixxxx Parameters

11.150 IMAGEVER_D 1385


11.151 IMPORTSTATUS # 1386
11.152 IMPORTSTS 1387
11.153 IMRAVGRESPTIMEDISPREAD 1387
11.154 IMRAVGSTDDISPREAD 1388
11.155 IMRAVGRESPTIMEP2PREAD 1388
11.156 IMRAVGRESPTIMEP2PWRITE 1389
11.157 IMRMAXRESPTIMEDISPREAD 1389
11.158 IMRMAXSTDDISPREAD 1390
11.159 IMRMAXRESPTIMEP2PREAD 1390
11.160 IMRMAXRESPTIMEP2PWRITE 1391
11.161 IMTYPE 1391
11.162 IN 1392
11.163 IN[*] 1393

11.164 IN[0..2] 1394


11.165 IN[0..12] 1395
11.166 IN[1] 1395
11.167 IN[1,2] 1396
11.168 IN[1..2] 1396
11.169 IN[1..3] 1397
11.170 IN[1..8] 1397
11.171 IN[1..20] 1398
11.172 IN.Boolean 1399
11.173 IN.ENUM 1399
11.174 IN.FLOAT32 1399
11.175 INFLOAT64 1400
11.176 IN.INT8 1400
11.177 INT8_VALUE 1401
11.178 IN.INT16 1401
11.179 INT16_VALUE 1402
11.180 ININT32 1402
11.181 INT32_VALUE 1403
11.182 IN.SDENUM 1403
11.183 IN.UINT8 1404
11.184 IN.UINT16 1404
11.185 IN.UINT32 1405
11.186 INACTINDETTM[1..8] 1405
11.187 INALM 1406
11.188 INALT 1408

- 1307 -
Chapter 11 - Ixxxx Parameters

11.189 INBADOPT 1408


11.190 INBADOPT 1409
11.191 INBETFL 1410
11.192 INCLAMPOPT 1410
11.193 INCLUDEINTEGRATORCLRI 1411
11.194 INCOMPLETE 1411
11.195 INDESC[*] 1412
11.196 INDPTOUTINIT 1412
11.197 INDRCTSYNC 1413
11.198 INDSYNCCMD 1414
11.199 INFLOAT64 1414
11.200 ININT32 1415
11.201 INITCOMPLETE 1415
11.202 INITCONNECTD[0..1] 1416

11.203 INITCONNECTD[1..3] 1416


11.204 INITCOUNTER 1416
11.205 INITMAN 1417
11.206 INITOPAFTLD 1418
11.207 INITOPOPT 1419
11.208 INITPENDING 1419
11.209 INITREQ 1420
11.210 INITREQ[0..2] 1422
11.211 INITREQ[1..8] 1423
11.212 INITREQLATCH 1423
11.213 INITREQSRC 1423
11.214 INITVAL 1424
11.215 INITVAL_AO_S 1425
11.216 INITVAL_DO_S 1425
11.217 INITVAL[0..numChans-1] 1425
11.218 INITVAL[1..8] 1426
11.219 INITVAL[1..NUMCHAN] 1426
11.220 INITVALSRC 1426
11.221 INPIN 1427
11.222 INPTDIR 1427
11.223 INPTDIR_AI_C 1429
11.224 INPTDIR_DI_C 1430
11.225 INPTDIR_DO_C 1431
11.226 INPTINVSTS[1..2] 1431
11.227 INPTINVSTS[1..8] 1431

- 1308 -
Chapter 11 - Ixxxx Parameters

11.228 INPTWIRETYP 1432


11.229 INPUTACTED[*] 1432
11.230 INPUTCHGDB 1433
11.231 INPUTERROR 1433
11.232 INPTDIR 1434
11.233 INPUTRANGE[0..numChans-1] 1434
11.234 INPUTRANGE[0..7] 1435
11.235 INPUTROC 1435
11.236 INPUTSTREAM 1436
11.237 INPUTTYPE 1436
11.238 INSBLOCK[1..10] 1437
11.239 INSERTINDEX 1437
11.240 INSERTSTS[1..10] 1437
11.241 INSFAILFL 1438

11.242 INSFAIL.PR 1438


11.243 INSFAIL.SV 1439
11.244 INSFAILALM.FL 1439
11.245 INSFAILALM.PR 1440
11.246 INSFAILALM.SV 1440
11.247 INSFAILFL 1441
11.248 INSMASTER 1441
11.249 INSRC[1..8] 1442
11.250 INTERLANCOMMFAILED 1442
11.251 INTGPD_SET 1442
11.252 INSTRUCTCNFM 1443
11.253 INSTRUCTCOMP 1443
11.254 INSTRUCTNOTIFOPT 1444
11.255 INSTRUCTPEND 1444
11.256 INSTRUCTSEQ 1445
11.257 INSTS[1..8] 1445
11.258 INSTSELECT 1446
11.259 INSTYPE[1..10] 1446
11.260 INT32PARAM 1447
11.261 INT32VAL[0..80] 1447
11.262 INT64PARAM 1447
11.263 INT64VAL[40] 1448
11.264 INTEGRITY1[1..4] 1448
11.265 INTEGRITY2[1..4] 1449
11.266 INTEGRITYPERIOD 1449

- 1309 -
Chapter 11 - Ixxxx Parameters

11.267 INTERLANFAILED 1450


11.268 INTERVALCOUNTER 1450
11.269 INTERVALS 1451
11.270 INTISWCMD 1452
11.271 INITVAL_AO_S 1452
11.272 INITVAL_DO_S 1452
11.273 INVCOND[1..8] 1453
11.274 INVFRMHNDLER[1..8] 1453
11.275 INVFRMHNDLRN[1..8] 1454
11.276 INVFRMHNDTYP[1..8] 1454
11.277 INVFROMSTEP[1..8][1..15] 1455
11.278 INVFROMSTEPN[1..8][1..15] 1455
11.279 INVPVFL 1456
11.280 INVOKE[1..8] 1456

11.281 INVOKT.HANDLE 1457


11.282 INVOKT.NEXTCOMP 1457
11.283 INVOLTTHRESH 1457
11.284 INVPWRGOOD1 1458
11.285 INVPWRGOOD2 1458
11.286 INVREASON[1..8] 1459
11.287 INVTHREAD[1..8] 1459
11.288 INVTIME[1..8] 1460
11.289 IOCBFMTAV 1460
11.290 IOLINKCOLOR 1461
11.291 IOCCONN 1461
11.292 IOCNUMBER 1462
11.293 IOCONNEXTSTS 1462
11.294 IOCONNSTATUS 1463
11.295 IOCSTATE 1465
11.296 IOCTYPE 1465
11.297 IOL1SOFTFAIL 1466
11.298 IOL2SOFTFAIL 1466
11.299 IOLCHNFAILA 1467
11.300 IOLCHNFAILB 1467
11.301 IOLCHNHISTA [1...10] 1468
11.302 IOLCHNHISTB[1...10] 1468
11.303 1.25 IOLCHNSTSA 1469
11.304 IOLCHNSTSB 1469
11.305 IOLDAUGHSF 1470

- 1310 -
Chapter 11 - Ixxxx Parameters

11.306 IOLFREE 1470


11.307 IOLIFNUM 1471
11.308 IOLINK1IOID 1471
11.309 IOLINK2IOID 1472
11.310 IOLIMSTATE 1472
11.311 IOLINK 1473
11.312 IOLINKCONN 1473
11.313 IOLINKTYPE 1474
11.314 IOLINKTYPEENUMMASK 1475
11.315 IOLMAXERR 1475
11.316 IOLOVRRUN 1476
11.317 IOLSOFTFAIL 1476
11.318 IOMASAPH 1477
11.319 IOMBTREV 1477

11.320 IOMBTREV(UOC) 1478


11.321 IOMBTREVA 1478
11.322 IOMBTREVB 1479
11.323 IOMCARDA 1479
11.324 IOMCARDB 1480
11.325 IOMCMD[1..40] 1480
11.326 IOMCOMMAND 1481
11.327 IOMCOMMAND[1..40] 1482
11.328 IOMCONN 1483
11.329 IOMDESCA 1483
11.330 IOMDESCB 1483
11.331 IOMEXECSTATE 1484
11.332 IOMFILEA 1485
11.333 IOMFILEB 1485
11.334 IOMFWREV 1486
11.335 IOMFWREVA 1486
11.336 IOMFWREVB 1487
11.337 IOMGRCLI 1487
11.338 IOMGRMAPFREE 1488
11.339 IOMGRMAPRUNNING 1488
11.340 IOMGRMEMFREE 1489
11.341 IOMGRMEMTOTAL 1489
11.342 IOMHWREV 1490
11.343 IOMHWREVA 1490
11.344 IOMHWREVB 1491

- 1311 -
Chapter 11 - Ixxxx Parameters

11.345 IOMLHFSTA 1492


11.346 IOMLHFSTB 1494
11.347 IOMLOCATION 1495
11.348 IOMNAME 1495
11.349 IOMNUM 1496
11.350 IOMOPERA 1497
11.351 IOMOPERB 1497
11.352 IOMPLREVA 1498
11.353 IOMPLREVB 1498
11.354 IOMSLOT 1498
11.355 IOMSLOTNUMBER 1499
11.356 IOMSTATE 1500
11.357 IOMSTS[1..40] 1502
11.358 IOMSTSA 1502

11.359 IOMSTSB 1503


11.360 IOMSTS(UOC) 1504
11.361 IOMTYPE 1504
11.362 IOMTYPE(UOC) 1506
11.363 IOMTYPE[1..40] 1507
11.364 IOMSTS 1514
11.365 IOMTYPE 1515
11.366 IOMFWREV(UOC) 1516
11.367 IOP 1517
11.368 IOPBLOCKNAME [1...40] 1517
11.369 IOPDESCA 1518
11.370 IOPDESCB 1518
11.371 IOPHARTLHFSTA 1519
11.372 IOPHARTLHFSTB 1520
11.373 IOPLOADSTATE 1520
11.374 IOPLOCATION 1521
11.375 IOPORCUR[1..40] 1521
11.376 IOPORPREV[1..40] 1522
11.377 IOPTYPE 1522
11.378 IORACKNUMBER 1523
11.379 IORACKNUM(UOC) 1524
11.380 IOREDOPT 1524
11.381 IOSCHEDOPT 1525
11.382 IOSSTALLTIME 1525
11.383 IOSTKNDROP 1526

- 1312 -
Chapter 11 - Ixxxx Parameters

11.384 IOTANETTYPE 1526


11.385 IOTATYPE 1527
11.386 IOTATOPOLOGY 1528
11.387 IPADDRESS 1528
11.388 IPEERAVGLPS [1...IPEERCONNMAX] 1530
11.389 IPEERAVGPPS [1...IPEERCONNMAX] 1531
11.390 IPEERCONN 1531
11.391 IPEERCONNERRCODE [1...N] 1532
11.392 IPEERCONNERRINFO [1...N] 1532
11.393 IPEERCONNMAX 1532
11.394 IPEERCONNSTS [1...N] 1533
11.395 IPEERMAXLPS [1...IPEERCONNMAX] 1533
11.396 IPEERMAXPPS [1...IPEERCONNMAX] 1534
11.397 IPEERNAME [1...IPEERCONNMAX] 1534

11.398 IPEERNAMELOOKUP 1535


11.399 IPEERPATH [1...IPEERCONNMAX] 1535
11.400 IPFRAGCREATES 1536
11.401 IPFRAGFAILS 1536
11.402 IPFRAGOKS 1537
11.403 IPINADDRERRORS 1537
11.404 IPINDELIVERS 1538
11.405 IPINDISCARDS 1538
11.406 IPINHDRERRORS 1539
11.407 IPINRECEIVES 1539
11.408 IPINUNKNOWNPORTS 1540
11.409 IPOUTDISCARDS 1540
11.410 IPOUTNOROUTES 1541
11.411 IPOUTREQUESTS 1541
11.412 IPREASSMFAILS 1542
11.413 IPREASSEMFAILS 1542
11.414 IPREASSEMOKS 1543
11.415 IPREASSEMREQS 1543
11.416 IPREASSEMTIMEOUT 1544
11.417 IPROUTINGDISCARDS 1544
11.418 ISBIGENDIAN 1545
11.419 ISROCKWELLIO 1545
11.420 ISSUEDATE 1546
11.421 ISVIRTUALPLATFORM 1546
11.422 ITEMCNT 1546

- 1313 -
Chapter 11 - Ixxxx Parameters

11.423 ITEMNAME 1547


11.424 ITEMS 1548

11.1 IACYCCONNIMRS[1..IPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Initiator Acyclic Connection IMRs - The current number of acyclic IMRs in use per
connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

11.2 IACYCCONNLRQS[1..IPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Initiator Acyclic Connections Large Requests - The current number of acyclic
large requests in use per connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 1314 -
Chapter 11 - Ixxxx Parameters

11.3 IACYCCONNSRQS[1..IPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Initiator Acyclic Connections Small Requests - The current number of acyclic
small requests in use per connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

11.4 IACYCIMRAVAIL

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Acyclic IMRs Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

- 1315 -
Chapter 11 - Ixxxx Parameters

11.5 IACYCIMRMAX

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Maximum Acyclic IMRs
Data Type 32-Bit Integer
Exposure Output
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Inter-process Message Structure (IMR) is used to pass information between
the control object adapter and the control kernel object manager for
communications across the network.

11.6 IACYCIMRUSED

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Acyclic IMRs Used
Data Type 32-Bit Integer
Exposure Output
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

- 1316 -
Chapter 11 - Ixxxx Parameters

11.7 IACYCIMRUSEDCONN [0...29]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Acyclic IMRs Used Per Conn
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks The Inter-process Message Structure (IMR) is used to pass information between
the control object adapter and the control kernel object manager for
communications across the network

11.8 IACYCLGREQAVAIL

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Acyclic Large Requests Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks

- 1317 -
Chapter 11 - Ixxxx Parameters

11.9 IACYCLGREQMAX

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Maximum Acyclic Large Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks

11.10 IACYCLGREQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Acyclic Large Requests Used
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks

- 1318 -
Chapter 11 - Ixxxx Parameters

11.11 IACYCLGREQUSEDCONN [0...29]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Acyclic Large Requests Per Connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks

11.12 IACYCSMREQAVAIL

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, , CEEUOC, CEECN100


(s)
Description Acyclic Small Requests Available
Data Type OUTPUT
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

11.13 IACYCSMREQMAX

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Description Maximum Acyclic Small Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0

- 1319 -
Chapter 11 - Ixxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, CEEUOC, CN100
(CEECN100)
Related
Parameters
Remarks

11.14 IACYCSMREQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)

Description Acyclic Small Requests Used


Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters

Remarks

11.15 IACYCSMREQUSEDCONN [0...29]

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Description Acyclic Small Requests Per Connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related Parameters
Remarks

- 1320 -
Chapter 11 - Ixxxx Parameters

11.16 IBVOPNFDBK

Specific to Block(s) MAINIBV


Description Integral Bypass Valve (IBV) Open Feed back
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters MAINCLOSEFDBK
Remarks This input will be connected to IBV valves open limit switch.

11.17 IBVOPNFDBKSTS

Specific to Block MAINIBV


(s)
Description integral Bypass Valve (IBV) Open Feed back input Status
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related MAINCLOSEFDBKSTS
Parameters
Remarks This parameter will get the status from PVVALSTS of DI channel connected to
this block.

11.18 IBVVLVFDBKTO

Specific to MAINIBV
Block(s)
Description Integral Bypass Valve (IBV) Valve Feedback Timeout
Data Type I6-Bit Unsigned Integer
Range >0
Default 0
Config YES

- 1321 -
Chapter 11 - Ixxxx Parameters

Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MAINVLVFDBKTO
Parameters
Remarks Expiry of this timer (in seconds) indicates that desired feedback has not come and
the open command operations will be aborted.,If IBVVLVFDBKTO is 0, During
download it will give warning.,This parameter will allow changes from Montiotring to
be done only when CM is Inactive.

11.19 IC.BYPPERM

Specific to Block(s) Step


Description Step Interrupt Condition Bypass Permit.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters IC.BYPREQ, IC.FL.
Remarks When On, IC.FL is set according to IC.BYPREQ.

11.20 IC.BYPREQ

Specific to Step
Block(s)
Description Step Interrupt Condition Bypass Request.
Data Type Enumeration CSCOBYPREQ
Range ToOff (0) ToOn (1) None (2)
Default None (2)
Config No
Load
Active No
Loadable

- 1322 -
Chapter 11 - Ixxxx Parameters

Access Lock Operator


Residence CEE
Related IACYCCONNIMRS[1..IPEERCONNMAX]IACYCCONNLRQS
Parameters [1..IPEERCONNMAX]IACYCCONNSRQS
[1..IPEERCONNMAX]
IACYCIMRAVAIL
IACYCIMRMAX
IACYCIMRUSED
IACYCLGREQAVAIL
IACYCLGREQMAX
IACYCLGREQUSED
IACYCSMREQAVAILIACYCSMREQMAXIACYCSMREQUSEDIC.BYPPERMIC.FL
Remarks See IC.BYPPERM for additional information.

11.21 IC.CONFIGCODE

Specific to Step
Block(s)
Description Common Interrupt Condition Configuration Code
Data Type Enumeration CSCOCONFIGCODECOND
Range None (0) Ok (1) UnknownErr (2) ImplicitConv (3) LossOfPrecsn (4) UnexpctEnd (5)
UnexpctComma (6) ColonWoQMark (7) FctNotMltArg (8) ClosParenExp (9)
OperandExp (10) MissingArg (11) OperatorExp (12) ColonExp (13) TypeMismatch
(14) TypeNotSupp (15) SyntaxError (16) ExprTooCmplx (17) NotEPcodeMe (18)
NotEDataStak (19) UnsuppFeatur (20) ExprTooLong (21) DivideByZero (22)
UnknownToken (23) UnexpTokenOS (24) UnknownFunc (25) UnexpOCExpr2 (26)
UnexpOCExpr3 (27) ZeroArgument (28) UnexpToken (29) InvalResult (30)
InvalTokenTb (31) IntegerExp (32) DoubleExp (33) MissedImpl (34) UnicodeConv
(35) ConstExprRem (36) DuplExprRem (37) ExtUse38 (38) ExtUse39 (39) ExtUse40
(40) ExtUse41 (41) ExtUse42 (42) ExtUse43 (43) ExtUse44 (44) ExtUse45 (45)
ExtUse46 (46) ExtUse47 (47) ExtUse48 (48) ExtUse49 (49) ExtUse50 (50)
UnSupConType (51) UnExpClsParn (52) CantAssRVal (53) UnExpArrOpen (54)
ArrClsExpect (55) ArrOpnExpect (56) ArrIndxError (57) StringExpect (58)
InvalidRefer (59) TooManyConnS (60) CantConvInpt (61)
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related
Parameters
Remarks See IC.CONFIGSTSfor additional information.

- 1323 -
Chapter 11 - Ixxxx Parameters

11.22 IC.CONFIGDESC

Specific to Block(s) Step


Description Common Interrupt Condition Configuration Descriptor
Data Type String
Range Maximum of 39 characters
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See IC.CONFIGSTSfor additional information.

11.23 IC.CONFIGSTS

Specific to Step
Block(s)
Description Common Interrupt Condition Configuration Status
Data Type Enumeration CSCOCONFIGSTS
Range Ok (0) Information (1) Warning (2) SevereWarn (3) Error (4) SevereError (5)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related IC.CONFIGCODEIC.CONFIGDESC
Parameters
Remarks Interrupt input condition configuration status parameters IC.CONFIGSTS,
IC.CONFIGCODE, and IC.CONFIGDESC are set on SCMSTATE transition from
Inactive to Validated.

11.24 IC.DESC

Specific to Block(s) Step/Transition


Description Step Interrupt Condition Descriptor
Data Type String
Range Length: 64 characters
Default Null String

- 1324 -
Chapter 11 - Ixxxx Parameters

Config Load Yes


Active Loadable Yes
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

11.25 IC.EXECCODE

Specific to Step
Block(s)
Description Step Interrupt Condition Execution Code
Data Type Enumeration CSCOEXECCODE
Range None (0) ConfigError (1) ExprEvalFail (2) StoreFailed (3) CommError (4)
StoreWarning (5) InternalErr (6) CtrlReqErr (7) DataTypeErr (8) StorePending (9)
Default None (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks See IC.EXECSTSfor additional information.

11.26 IC.EXECDESC

Specific to Block(s) Step


Description Step Interrupt Condition Execution Code Descriptor
Data Type String
Range Maximum of 39 characters.
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See IC.EXECSTSfor additional information.

- 1325 -
Chapter 11 - Ixxxx Parameters

11.27 IC.EXECSTS

Specific to Step
Block(s)
Description Step Interrupt Condition Execution Status
Data Type Enumeration CSCOEXECSTS
Range Ok (0) Bypass (1) Info (2) Warning (3) Fail (4) Error (5) OkPaused (6) BypassPaused
(7) InfoPaused (8) WarnPaused (9) FailPaused (10) ErrorPaused (11)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related IC.CONFIGCODEIC.CONFIGDESC
Parameters
Remarks Step Interrupt Condition execution status parameter IC.EXECSTS, IC.EXECCODE,
and IC.EXECDESC are updated when the step is in the Sequential Control Module's
(SCM) current scope of execution.

11.28 IC.EXPR

Specific to Block(s) Step


Description Step Interrupt Condition Expression
Data Type String
Range String has a maximum length of 255 characters.
Default Null String
Config Load Yes
Active Loadable No
Access Lock Application Developer.
Residence SR
Related Parameters
Remarks

11.29 IC.EXPRPCODE

Specific to Block(s) Step


Description This is an internal parameter for system use only.
Data Type
Range

- 1326 -
Chapter 11 - Ixxxx Parameters

Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

11.30 IC.FL

Specific to Block(s) Step


Description Step Interrupt Condition Status Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

11.31 IC.INVOKFL

Specific to Block(s) Step


Description Step Interrupt Condition Invoke Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters IC.FL
Remarks

- 1327 -
Chapter 11 - Ixxxx Parameters

11.32 ICINCONNHNDL[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

11.33 ICINCONNNAV[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

11.34 ICINCONNPRM[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable NO

- 1328 -
Chapter 11 - Ixxxx Parameters

Access Lock
Residence
Related Parameters
Remarks

11.35 ICINCONNSTRVAL[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

11.36 ICINCONNVAL[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 1329 -
Chapter 11 - Ixxxx Parameters

11.37 ICMPINADDRMASKREPS

Specific to Block(s) C300, FIM4 and FTEB FBs


Description Internet Control Message Protocol (ICMP) Address Masks Reply Messages
Received
Data Type 32-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4
Related N/A
Parameters
Remarks

11.38 ICMPINADDRMASKS

Specific to Block(s) C300, FIM4, FTEB, PGM, EHPM


Description Internet Control Message Protocol (ICMP) Address Masks Messages
Received
Data Type 32-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters N/A
Remarks

11.39 ICMPINCSUMERRORS

Specific to Block(s) EIM, UOC, TCMI, C300


Description Messages with Checksum Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No

- 1330 -
Chapter 11 - Ixxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (ICMP statistics, see C300 definition)

11.40 ICMPINDESTUNREACHS

Specific to C300, FIM4, FTEB, PGM, EHPM, EIM,UOC, TCMI


Block(s)
Description Dest. Unreachable Msgs Recvd
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, 0 to 4294967295
Related
Parameters
Remarks Identifies The number of ICMP destination unreachable messages received
(ICMP statistics, see C300 definition)

11.41 ICMPINECHOREPS

Specific to Block C300, FIM4, FTEB, PGM, EHPM, EIM,UOC, TCMI


(s)
Description Echo Reply Messages Recvd
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks Identifies the number of ICMP Echo Reply messages received. (ICMP statistics,
see C300 definition)

- 1331 -
Chapter 11 - Ixxxx Parameters

11.42 ICMPINECHOS

Specific to C300, FIM4, FTEB, PGM, EHPM, EIM, TCMI


Block(s)
Description Echo Messages Recvd
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks Identifies the number of ICMP Echo (request) messages received. (ICMP
statistics, see C300 definition)

11.43 ICMPINERRORS

Specific to C300, FIM4, FTEB, PGM, EHPM, EIM, UOC


Block(s)
Description Messages with Format Errors
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks Identifies the number of ICMP messages which the entity received but determined
as having ICMP-specific errors, such as bad ICMP checksums, bad length, and so
on. (ICMP statistics, see C300 definition)

- 1332 -
Chapter 11 - Ixxxx Parameters

11.44 ICMPINMSGS

Specific to C300, FIM4, FTEB, PGM, EHPM,EIM, UOC


Block(s)
Description Messages Received
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related N/A
Parameters
Remarks Identifies the total number of ICMP messages which the entity received. Note that
this counter includes all messages counted by the parameter ICMPINERRORS.

11.45 ICMPINPARAMPROBS

Specific to Block(s) C300, FIM4, FTEB , EHPM.


Description Internet Control Message Protocol (ICMP) Parameter Problems Messages
Received
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, EHPM
Related N/A
Parameters
Remarks

11.46 ICMPINREDIRECTS

Specific to Block(s) C300, FIM4, FTEB , EHPM.


Description Internet Control Message Protocol (ICMP) Source Quenches Received
Data Type 32-Bit Integer
Range

- 1333 -
Chapter 11 - Ixxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, EHPM
Related Parameters N/A
Remarks

11.47 ICMPINSRCQUENCHS

Specific to Block(s) C300, FIM4, FTEB, PGM, EHPM


Description Internet Control Message Protocol (ICMP) Source Quench Messages
Received
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related N/A
Parameters
Remarks

11.48 ICMPINTIMEEXCDS

Specific to Block(s) C300, FIM4, FTEB, PGM, EHPM


Description Internet Control Message Protocol (ICMP) Time Exceeds Messages
Received
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters N/A
Remarks

- 1334 -
Chapter 11 - Ixxxx Parameters

11.49 ICMPINTIMESTAMPREPS

Specific to Block(s) C300, FIM4, FTEB, PGM, EHPM


Description Internet Control Message Protocol (ICMP) Timestamp Messages Received
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters N/A
Remarks

11.50 ICMPINTIMESTAMPS

Specific to Block(s) C300, FIM4, FTEB, PGM, EHPM


Description Internet Control Message Protocol (ICMP) Timestamp Reply Messages
Received
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related N/A
Parameters
Remarks

11.51 ICMPOUTADDRMASKREPS

Specific to Block(s) C300, FIM4, FTEB, PGM, EHPM


Description Internet Control Message Protocol (ICMP) Address Mask Reply Messages
Sent
Data Type 32-Bit Integer
Range
Default 0
Config Load No

- 1335 -
Chapter 11 - Ixxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related N/A
Parameters
Remarks

11.52 ICMPOUTADDRMASKS

Specific to Block(s) C300, FIM4, FTEB, PGM, EHPM


Description Internet Control Message Protocol (ICMP) Address Mask Messages Sent
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters N/A
Remarks

11.53 ICMPOUTDESTUNREACHS

Specific to C300, FIM4, FTEB, PGM, EHPM, EIM, UOC, TCMI


Block(s)
Description Dest. Unreachable Msgs Sent
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks Identifies the number of ICMP Destination Unreachable messages sent. (ICMP
statistics, see C300 definition)

- 1336 -
Chapter 11 - Ixxxx Parameters

11.54 ICMPOUTECHOREPS

Specific to Block C300, FIM4, FTEB, PGM, EHPM, EIM, UOC, TCMI
(s)
Description Echo Reply Messages Sent
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks Identifies the number of ICMP Echo Reply messages sent. (ICMP statistics, see
C300 definition)

11.55 ICMPOUTECHOS

Specific to Block C300, FIM4, PGM, FTEB, EHPM, EIM, UOC, TCMI
(s)
Description Echo Messages Sent
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks Identifies the number of ICMP Echo (request) messages sent. (ICMP statistics,
see C300 definition)

- 1337 -
Chapter 11 - Ixxxx Parameters

11.56 ICMPOUTERRORS

Specific to C300, FIM4, PGM, FTEB, EHPM, EIM, UOC, TCMI


Block(s)
Description Out Error Messages
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks This parameter should not include errors discovered outside the ICMP layer such
as the inability of IP to route the resultant datagram. In some implementations,
there may be no types of errors which contribute to this counter's value. Identifies
the number of ICMP messages which this entity did not send due to problems
discovered within ICMP such as a lack of buffers. (ICMP statistics, see C300
definition)

11.57 ICMPOUTMSGS

Specific to C300, FIM4, PGM, FTEB, EHPM,.EIM, UOC, TCMI


Block(s)
Description Messages Sent
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks Identifies the total number of ICMP messages which this entity attempted to send.
Note that this counter includes all those counted by the parameter
ICMPOUTERRORS. (ICMP statistics, see C300 definition)

- 1338 -
Chapter 11 - Ixxxx Parameters

11.58 ICMPOUTPARAMPROBS

Specific to Block(s) C300, FIM4, PGM, FTEB, EHPM.


Description Internet Control Message Protocol (ICMP) Parameter Problem Messages
Sent
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

11.59 ICMPOUTREDIRECTS

Specific to Block(s) C300, FIM4, PGM, FTEB, EHPM.


Description Internet Control Message Protocol (ICMP) Redirect Messages Sent
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.60 ICMPOUTSRCQUENCHS

Specific to Block(s) C300, FIM4, PGM, FTEB, EHPM.


Description Internet Control Message Protocol (ICMP) Source Quench Messages Sent
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No

- 1339 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.61 ICMPOUTTIMEEXCDS

Specific to Block(s) C300, FIM4, PGM, FTEB, EHPM.


Description Internet Control Message Protocol (ICMP) Time Exceed Messages Sent
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.62 ICMPOUTTIMESTAMPREPS

Specific to Block(s) C300, FIM4, PGM, FTEB, EHPM.


Description Internet Control Message Protocol (ICMP) Timestamp Reply Messages
Sent
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

- 1340 -
Chapter 11 - Ixxxx Parameters

11.63 ICMPOUTTIMESTAMPS

Specific to Block(s) C300, FIM4, PGM, FTEB, EHPM.


Description Internet Control Message Protocol (ICMP) Timestamp Messages Sent
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.64 ICNUMSRCCONN

Specific to Step Block


Block(s)
Description Number of Source Connections for Interrupt Condition expression. Represents
number of source references in the Step-specific Interrupt Condition expression.
Data Type Integer32
Range 0 to 6
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence ACE, C200, SIM_C200
Related ICPCODESIZE
Parameters
Remarks

11.65 IC.OPT

Specific to Block(s) Step


Description Step Interrupt Condition Option
Data Type Boolean
Range Off (0) On (1)
Default Off (0)

- 1341 -
Chapter 11 - Ixxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks Must be set to On, to enable the Step Interrupt Condition.

11.66 ICONSTATE

Specific to C300, FIM4, PGM, EHPM


Block(s)
Description Icon State
Data Type Enumeration
Range 1 NonRdnIdle Non-Redundant, Idle execution
state.
2 NonRdnIdleSim Non-Redundant, Idle execution state
in Simulation mode.
3 PriIdleNoSec Primary, Idle, partner absent (or
incompatible).
4 PriIdleNotSync Primary, Idle, partner visible but not
synchronized.
5 PriIdleSyncd Primary, Idle, Synchronized.
6 PriIdleStandby Primary, Idle, Standby.
7 NonRdnIdleSoftFail Non-Redundant, Idle, Soft Failure
condition exists.
8 NonRdnIdleSimSoftFail Non-Redundant, Idle execution state
in Simulation mode with Soft Failure
condition exists.
9 PriIdleNoSecSoftFail Primary, Idle, No Secondary, Soft
Failure condition exists.
10 PriIdleNotSyncSoftFail Primary, Idle, Not Synchronized, Soft
Failure condition exists.
11 PriIdleStandbySoftFail Primary, Idle, Standby, Soft Failure
condition exists.
12 NonRdnRunOk Non-Redundant, Run or Ok
execution state.
13 NonRdnRunOkSim Non-Redundant, Run or Ok
execution state in Simulation mode.
14 PriRunOkNoSec Primary, Run or Ok, partner absent
(or incompatible).
15 PriRunOkNotSync Primary, Run or Ok, partner visible
but Not Synchronized.
16 PriRunOkSyncd Primary, Run or Ok, Synchronized.
17 PriRunOkStandby Primary, Run or Ok, Standby.

- 1342 -
Chapter 11 - Ixxxx Parameters

18 NonRdnRunOkSoftFail Non-Redundant, Run or Ok, Soft


Failure condition exists.
19 NonRdnRunOkSimSoftFail Non-Redundant, Run or Ok
execution state in Simulation mode
with Soft Failure condition.
20 PriRunOkNoSecSoftFail Primary, Run or Ok execution state
with Soft Failure condition and
Secondary not visible.
21 PriRunOkNotSyncSoftFail Primary, Run or Ok execution state,
Not Synchronized with secondary.
Soft Failure condition exists.
22 PriRunOkSyncdSoftFail Primary, Run or Ok execution state,
Synchronized with secondary, Soft
Failure condition exists.
23 PriRunOkStandbySoftFail Primary, Run or Ok execution state,
Standby and Soft Failure condition
exists.
24 NonRdnNoDb Non-Redundant, No Database.
25 NonRdnNoDbSim Non-Redundant, No Database in
Simulation mode.
26 PriNoDbNoSec Primary, No Database, partner
absent (or incompatible).
27 PriNoDbNotSync Primary, No Database, partner visible
but Not Synchronized.
28 PriNoDbSyncd Primary, No Database,
Synchronized.
29 PriNoDbStandby Primary in Standby with NoDb
execution state.
30 NonRdnNoDbSoftFail Non-Redundant, NoDb execution
state, Soft Failure condition exists.
31 NonRdnNoDbSimSoftFail Non-Redundnat, NoDb execution
state in Simulation mode with Soft
Failure condition.
32 PriNoDbNoSecSoftFail Primary, NoDb execution state,
Secondary not visible, Soft Failure
condition exists.
33 PriNoDbNotSyncSoftFail Primary, NoDb execution state. Not
Synchronized with secondary, Soft
Failure condition exists.
34 PriNoDbSyncdSoftFail Primary, NoDb, Synchronized, Soft
Failure condition exists.
35 PriNoDbStandbySoftFail Primary NoDb, Standby, SoftFailure
exists.
36 SecNoPri Secondary, partner absent (or
incompatible).
37 SecNotSync Secondary, partner visible but Not
Synchronized.
38 SecSyncd Secondary, Synchronized.
39 SecStandby Secondary Standby.

- 1343 -
Chapter 11 - Ixxxx Parameters

40 SecNoPriSoftFail Secondary, Primary not visible, Soft


Failure exists.
41 SecNotSyncSoftFail Secondary, Not Synchronized with
primary, Soft Failure condition exists.

42 SecSyncdSoftFail Secondary Synchronized with


primary, Soft Failure condition exists.

43 SecStandbySoftFail Secondary in Standby, Soft Failure


condition exists.
Default NonRdnIdle
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence EE
Related PCMSTATERDNSYNCSTATE
Parameters
Remarks The icon's appearance is derived from the module's execution state, redundancy
configuration, and redundancy status.
* ICONSTATE is applicable to several other blocks, but its range and values differ for each block.
Refer respective block description.

Specific to IOLINK
Block(s)
Description Icon State. Shows the current state of the associated input/output link through
the IOLINK block icon.
Data Type Enumeration
Range NOEE (0): IOLINK block has not been loaded. ONLINE (1): IOLINK block is
loaded and online.
Default NOEE (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks The IOLINK does not have an INACTIVE state.

- 1344 -
Chapter 11 - Ixxxx Parameters

Specific to All PM I/O and Series C I/O Modules


Block(s)
Description Icon State. Defines the state of the icon for the I/O modules.
Data Type Enumeration
Range 0 IDLE IOM is non-redundant, IDLE
1 PriIdleNoSec Primary is Idle, Secondary has comm
error.
2 PriIdleNotSync Primary is Idle, Secondary is Not
Synchronized
3 PriIdleSync Primary is Idle, secondary is
Synchronized
4 RUN IOM is non-redundant, RUN
5 PriRunNoSec Primary is Run, Secondary has comm
error
6 PriRunNotSync Primary is Run, Secondary is Not
Synchronized
7 PriRunSync Primary is Run, Secondary is
Synchronized
8 FAILED IOM is non-redundant, comm error from
IOLIM to IOM
9 PriCommErrNoSec Primary and Secondary have comm error
10 PriCommErrNoSync Primary has comm error, secondary is Not
Synchronized
11 NODB IOM is non-redundant, (DBVALID =
Invalid)
12 PriNoDbNoSec Primary is NoDb, Secondary has comm
error
13 PriNoDbNotSync Primary is NoDb, Secondary is Not
Synchronized

14 PriNoDbSync Primary is NoDb, Secondary is not in


comm error
Default IDLE for PM I/O
FAILED for Series C I/O
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM/C300
Related
Parameters
Remarks

- 1345 -
Chapter 11 - Ixxxx Parameters

Specific to PM I/O Channels and Series C I/O Channels


Block(s)
Description Icon State. Shows the current state of the associated input/output channel (IOC)
through the IOC block icon.
Data Type Enumeration
Range 0 Inactive PTEXECST = Inactive.

1 Active PTEXECST = Active.

2 CommError IOM or IOLIM is off net.


3 Inactive PTEXECST = Inactive
and is HART enabled.
4 Active PTEXECST = Active and
is HART enabled.
5 CommError 12.60.1 IOM or IOLIM is
off net and is HART
enabled.
Default Inactive
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks When PTEXECST is Inactive, the point
processing does not occur for the
channel.

Specific to Block(s) Controller Rack, IO RACK, UOC


Description Icon State.
Data Type Enumeration
Range N/A
Default NonRdnIdle
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Controller Rack, IO RACK, NOLOAD
Related Parameters
Remarks Current icon displayed in control builder

Specific to Controller Rack, IO RACK, UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-
Block(s) VAC, DI16-DRYCT, DO08-RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Icon States
Data Type Enumeration
Range N/A

- 1346 -
Chapter 11 - Ixxxx Parameters

Default NonRdnIdle
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Controller Rack, IO RACK, IO modules
Related
Parameters
Remarks Current icon displayed in control builder

11.67 ICPCODESIZE

Specific to Step Block


Block(s)
Description Number of Pcode Bytes for Interrupt Condition expression. Represents number of
bytes required for the Psuedo code of the Step-specific Interrupt Condition
expression.
Data Type Integer32
Range 0 to 200
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence ACE, C200, SIM_C200
Related ICNUMSRCCONN
Parameters
Remarks

11.68 ICPMBUFALLOC

Specific to Block CEEFB, CEEACEFB, CEESIMC200FB, FIM, FIMS, OPC, ICG, IOLIM, IOLIMS,
(s) CEEC300, GEEFB
Description ICP Shared RAM Buffers Allocated
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No

- 1347 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters
Remarks

11.69 ICPMBUFALLOC[0..3]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG,
(s) GEE FBs
Description Integrated Control Protocol Main RAM Buffers Allocated - The current main
buffer allocation.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

11.70 ICPMBUFINUSE

Specific to Block CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,


(s) CEEC300,GEEFB
Description ICP Main Buffers In Use
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters
Remarks

- 1348 -
Chapter 11 - Ixxxx Parameters

11.71 ICPMBUFINUSE[0..3]

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG,
GEE FBs
Description Integrated Control Protocol Main RAM Buffer In Use - The main RAM buffers
in use.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

11.72 ICPMBUFMAX[0..3]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG, GEE
Block(s) FBs
Description Integrated Control Protocol Main RAM Buffer Maximum - The maximum number of
main RAM buffers that are in use at any given time.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

- 1349 -
Chapter 11 - Ixxxx Parameters

11.73 ICPMBUFMIN

Specific to Block CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,


(s) CEEC300,GEEFB
Description ICP Main Buffer Minimum
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters
Remarks

11.74 ICPMBUFMIN[0..3]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG, GEE
Block(s) FBs
Description Integrated Control Protocol Main RAM Buffer Maximum - The maximum number of
main RAM buffers that are in use at any given time.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

11.75 ICPMBUFSIZE

Specific to Block CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,


(s) CEEC300,GEEFB
Description ICP Main Buffer Size
Data Type 32-Bit Integer
Range Greater than or equal to 0

- 1350 -
Chapter 11 - Ixxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters
Remarks As of PlantScape R500, the current buffer sizes are:
512 Byte
2K Byte

11.76 ICPMBUFSIZE[0..3]

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG,
GEE FBs
Description Integrated Control Protocol Main RAM Buffer Size - The current buffer size.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks The current main buffer sizes are: 512 Byte 2K Byte

11.77 ICPNAKS[1..RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG, GEE
Block(s) FBs
Description Integrated Control Protocol (ICP) Not Acknowledgements - The total number of ICP
not acknowledgements per responder connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable

- 1351 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks The current main buffer sizes are: 512 Byte 2K Byte

11.78 ICPNAKSPERCONN

Specific to
Block(s) CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,CEEC300,GE
EFB
Description ICP NAK Count Per Connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameter
s
Remarks

11.79 ICPNOBUFSPERCONN

Specific to Block CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,


(s) CEEC300,GEEFB
Description Number of Buffer Per Connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters
Remarks

- 1352 -
Chapter 11 - Ixxxx Parameters

11.80 ICPPENDLMTPERCONN

Specific to
Block(s) CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,CEEC300,GEE
FB,CEEUOC
Descriptio Pending Limit Errors Per Connection
n
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200, UOC(CEEUOC)

Related
Paramete
rs
Remarks

11.81 ICPSBUFALLOC

Specific to CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,CEEC300,GEEF
Block(s) B
Description ICP Shared RAM Buffers Allocated
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameter
s
Remarks

- 1353 -
Chapter 11 - Ixxxx Parameters

11.82 ICPSBUFALLOC[0..3]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG,
(s) GEE FBs
Description Integrated Control Protocol (ICP) Shared Buffers Allocated - The current
buffer allocation.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

11.83 ICPSBUFINUSE[0..3]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG,
(s) GEE FBs
Description Integrated Control Protocol (ICP) Shared Buffer In Use - The shared RAM
buffers in use.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

- 1354 -
Chapter 11 - Ixxxx Parameters

11.84 ICPSBUFMIN

Specific to CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,CEEC300,GEEFB
Block(s)

Description Minimum ICP Shared RAM Buffers Available


Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters

Remarks This is the minimum number of ICP shared RAM buffers that were available at any
given time.

11.85 ICPSBUFMIN[0..3]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG, GEE
Block(s) FBs
Description Integrated Control Protocol (ICP) Shared Buffer Minimum - The minimum number
of RAM buffers that are available at any given time.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

- 1355 -
Chapter 11 - Ixxxx Parameters

11.86 ICPSBUFSIZE

Specific to CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,CEEC300,GEEF
Block(s) B
Description ICP Shared RAM Buffer Size
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameter
s
Remarks As of PlantScape R500, the current buffer sizes are:
256 Byte
400 Byte
512 Byte
4K Byte

11.87 ICPSBUFSIZE[0..3]

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG,
GEE FBs
Description Integrated Control Protocol (ICP) Shared RAM Buffer Size - The current
buffer size.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks The current shared buffer sizes are: 256 Byte 400 Byte 512 Byte 4K Byte

- 1356 -
Chapter 11 - Ixxxx Parameters

11.88 ICPSENDFAIL

Specific to Block CEEFB, CEEACEFB, CEESIMC200FB, FIM, FIMS, OPC, ICG, IOLIM, IOLIMS,
(s) CEEC300, GEEFB
Description ICP Send Failures
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters
Remarks This parameter shows the number of CDA to ICP retries for all Responder
connections.

11.89 ICPSENDFAIL[1..RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG, GEE
Block(s) FBs
Description Integrated Control Protocol (ICP) Send Failures Per Connection- The number of
Control Data Access (CDA) to ICP retries per responder connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

- 1357 -
Chapter 11 - Ixxxx Parameters

11.90 ICPSENDFAILPERCONN

Specific to Block CEEFB, CEEACEFB, CEESIMC200FB, FIM, FIMS, OPC, ICG, IOLIM, IOLIMS,
(s) CEEC300, GEEFB
Description ICP Send Fails Per Connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters

Remarks

11.91 ICPSENDNOBUFS

Specific to CEE, IOLIM, FIM


Block(s)
Description Integrated Control Protocol (ICP) Send No Buffers - The number of Control Data
Access (CDA) to ICP retries due to no buffers available for all responder
connections.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 1358 -
Chapter 11 - Ixxxx Parameters

11.92 ICPSENDPENDLIMIT[1..RPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Integrated Control Protocol (ICP) Send Pending Limits - The number of Control
Data Access (CDA) to ICP retries per responder connection due to the maximum
number of pending transmits already queued.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

11.93 ICPSENDXMTTO[1..RPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Integrated Control Protocol (ICP) Send Transmit Timeout - The number of Control
Data Access (CDA) to ICP retries per responder connection due to the time out
exceeded for a connection to become ready for transmit.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 1359 -
Chapter 11 - Ixxxx Parameters

11.94 ICPTIMEOUTPERCONN

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG,
GEE FBs
Description Timeout Errors Per Connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200
Related
Parameters
Remarks

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEACE, CEESIMC200, OPC,ICG,
GEE FB
Description Timeout Errors Per Connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM C200
Related
Parameters
Remarks

11.95 ICPSTATRESET

Specific to Block(s) FTEB


Description Integrated Control Protocol (ICP) Statistics Reset - Resets alI ICP statistics.
Data Type Boolean
Range 0 = Off
1 = On
Default Off (0)
Config Load No
Active Loadable No

- 1360 -
Chapter 11 - Ixxxx Parameters

Access Lock Operator


Residence FTEB
Related Parameters
Remarks

11.96 ICSRC[1..6]

Specific to Block(s) Step


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

11.97 ICYCCONNIMRS[1..IPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Initiator Cyclic Connection IMRs - The current number of cyclic IMRs in use per
connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

- 1361 -
Chapter 11 - Ixxxx Parameters

11.98 ICYCCONNLRQS[1..IPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Initiator Cyclic Connections Large Requests - The current number of cyclic large
requests in use per connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

11.99 ICYCCONNSRQS[1..IPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Initiator Cyclic Connections Small Requests - The current number of cyclic small
requests in use per connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 1362 -
Chapter 11 - Ixxxx Parameters

11.100 ICYCIMRAVAIL

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Cyclic IMRs Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

11.101 ICYCIMRMAX

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Maximum Cyclic IMRs
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

- 1363 -
Chapter 11 - Ixxxx Parameters

11.102 ICYCIMRUSED

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Cyclic IMRs Used
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

11.103 ICYCIMRUSEDCONN [0...29]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Cyclic IMRs Used Per Connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks

- 1364 -
Chapter 11 - Ixxxx Parameters

11.104 ICYCLGREQAVAIL

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Cyclic Large Requests Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, C300(CEEC300,
IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100(CEECN100)
Related
Parameters
Remarks

11.105 ICYCLGREQMAX

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Maximum Cyclic Large Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

- 1365 -
Chapter 11 - Ixxxx Parameters

11.106 ICYCLGREQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Cyclic Large Requests Used
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

11.107 ICYCLGREQUSEDCONN [0...29]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Cyclic Large Requests Per Connection
Data Type 32-Bit Integer
Exposure Output
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

11.108 ICYCSMIOREQUSEDCONN

Specific to Block(s) CEE, IOLINK


Description Cyclic Small IO Requests Per connection
Data Type 32-Bit Integer
Range Greater than or equal to 0

- 1366 -
Chapter 11 - Ixxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), CN100(IOLINK)
Related Parameters N/A
Remarks

11.109 ICYCSMREQAVAIL

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Cyclic Small Requests Available
Data Type 32-Bit Integer
Exposure Output
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

11.110 ICYCSMREQMAX

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Maximum Cyclic Small Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No

- 1367 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks

11.111 ICYCSMREQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Cyclic Small Requests Used
Data Type 32-Bit Integer
Exposure Output
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

11.112 ICYCSMREQUSEDCONN [0...29]

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC


Description Cyclic Small Requests Per Connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC)
Related Parameters N/A
Remarks

- 1368 -
Chapter 11 - Ixxxx Parameters

11.113 ID

Specific to Step
Block(s)
Description Step ID (User Defined)
Data Type 32-Bit Integer
Range -2^31 to (2^31)-1
Default 0
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks General purpose parameter provided for whatever the user chooses. The SCM or
Step does not use this for anything.

11.114 IDENTIFY

Specific to UOC, C300, CN100


Block(s)
Description Identify Device
Data Type BOOLEAN
Range N/A
Default Off
Config Load Yes
Active
Loadable
Access Operator
Lock
Residence NOLOAD
Related
Parameters
Remarks Identify command. The identify command causes the front panel display of the
physical device to blink through a rainbow sequence for 30 seconds. LEDs will cycle
through green, orange, red, and off. This command is intended to assist users with
identifying a physical device.

- 1369 -
Chapter 11 - Ixxxx Parameters

11.115 IDLEMODE[0..7]

Specific to Chassis HART AO IOM


Block(s)
Description Idle Mode - Shed to IDLE Value enabler If enabled, the output will assume the Idle
Value (IDLEVALUE) in the event of controller failure or a loss of communication
between the controller and IOM. If disabled, the output will hold the last good value
processed. The module is forced to go to IDLEMODE when there is a switchover in
a controller-redundant system.
Data Type Boolean
Range Hold Last Output Value (0), Use IDLEVALUE (1)
Default Use last output Value (0)
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks IDLEMODE must be set to “Use IDLE Value” in order to configure IDLEVALUE.

11.116 IECDATATYPE

Specific to Block(s) EIM


Description IEC Data Type
Data Type ENUM
Range NA
Default NOT DEFINED
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ERDBONLY
Related Parameters
Remarks

- 1370 -
Chapter 11 - Ixxxx Parameters

11.117 IEDCONNECTIONSTATUS

Specific to Block(s) 850M


Description IED Connection Status
Data Type ENUM
Range l 0 - Disconnected
l 1 - Connected
l 2 - StackNotReady
l 3 - NotLoaded
l 4 - Connecting
l 5 - NotEnabled
Default NotLoaded
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

11.118 IEDNAME

Specific to Block(s) 850M, EIM


Description IED Name
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD , ERDBSR
Related Parameters
Remarks

- 1371 -
Chapter 11 - Ixxxx Parameters

11.119 IEDOMAINNAME

Specific to Block(s) 850M, EIM


Description Domain Name
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock AppDevOnly, ViewOnly
Residence CEE
Related Parameters
Remarks

11.120 IEDSTATRESET

Specific to Block(s) 850M


Description Reset Statistics
Data Type BOOLEAN
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters
Remarks

11.121 IEDTAGNAME

Specific to Block(s) 850M


Description Physical device name
Data Type BLOCKID
Range N/A
Default N/A
Config Load No
Active Loadable No

- 1372 -
Chapter 11 - Ixxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related Parameters
Remarks

11.122 IECLINKINACTIVE

Specific to Block(s) IEC61850M, IEC61850MSEC


Description IEC61850 Link Inactive
Data Type Boolean
Range 0 – Off 1 – On
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence 850M
Related Parameters IIMSTATE
Remarks Indicates if the IEC61850 link is active or inactive.

11.123 IELDEVICENAME

Specific to Block(s) 850M


Description Logical Device Instance
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

- 1373 -
Chapter 11 - Ixxxx Parameters

11.124 IFINDISCARDS

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description In Packets Discarded, resource limit - Indicates the number of FTE input packets
discarded due to resource limit.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

11.125 IFINERRORS

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description In Packets Discarded, format errors - Indicates the number of FTE input packets
discarded due to format errors.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

- 1374 -
Chapter 11 - Ixxxx Parameters

11.126 IFINNONUCASTPKTS

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Broadcast Packets Delivered Above
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.127 IFINOCTETS

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Total Octets Received from Media
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.128 IFINUCASTPKTS

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Unicast Packets Delivered Above
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No

- 1375 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.129 IFINUNKNOWNPROTOS

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Packets for Unknown Protocols
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.130 IFOUTDISCARDS

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Out Packets Discarded Due to Resource Limit
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

- 1376 -
Chapter 11 - Ixxxx Parameters

11.131 IFOUTERRORS

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Out Packets Discarded Due to Errors
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.132 IFOUTNONUCASTPKTS

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Broadcast Packets from Above
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.133 IFOUTOCTETS

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Total Octets Sent on the Media
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No

- 1377 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.134 IFOUTQLEN

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Size of Output Queue
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.135 IFOUTUCASTPKTS

Specific to Block(s) FTEB, C300, PGM, FIM4 , EHPM


Description Unicast Packets from Above
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

- 1378 -
Chapter 11 - Ixxxx Parameters

11.136 IFTRANS

Specific to Block(s) AIM, excluding non-isolated (high-density) modules


Description Idle/Fault Transition Enable
Data Type Boolean
Range Off (0) On (1)
Default On (1)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks Although loaded, this parameter is not exposed on any configuration form.

11.137 IGNORD

Specific to Block(s) SignalSel


Description Inputs Ignored
Data Type Boolean
Range OFF (0) No inputs have been ignored
Default ON (1) At least one input has been ignored
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related Parameters IGNORDFL[1..6]
Remarks This parameter is set if any of the inputs has been ignored

11.138 IGNORDFL[1..6]

Specific to SignalSel
Block(s)
Description Inputs Ignored Flags
Data Type Boolean
Range Each array element takes values OFF, ON
OFF (0) The input associated with the array element has
not been ignored
ON (1) The input associated with the array element has
been ignored

- 1379 -
Chapter 11 - Ixxxx Parameters

Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related IGNORD
Parameters
Remarks Each array element denotes if the respective input has been ignored or not

11.139 IGNORHI

Specific to Block(s) SignalSel


Description Ignore Highest Inputs
Data Type 32-Bit Integer
Range 0-6
Default 0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related Parameters IGNORLO
Remarks This parameter denotes the number of highest inputs to be ignored

11.140 IGNORLM

Specific to Block(s) SignalSel


Description Ignore limit
Data Type Float64
Range Greater than 0 including NaN
Default NaN
Config Load Yes
Active Loadable No
Access Lock Operator
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related IGNORTM, IGNORD, IGNORDFL[1..6]
Parameters
Remarks If any P inputs go beyond the Ignore limit for a specific time they shall be
ignored.

- 1380 -
Chapter 11 - Ixxxx Parameters

11.141 IGNORLO

Specific to Block(s) SignalSel


Description Ignore Lowest Inputs
Data Type 32-Bit Integer
Range 0-6
Default 0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related Parameters IGNORHI
Remarks This parameter denotes the number of lowest inputs to be ignored

11.142 IGNORTM

Specific to Block(s) SignalSel


Description Ignore Time in seconds
Data Type Float64
Range N/A
Default 0
Config Load Yes
Active Loadable No
Access Lock Operator
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related IGNORLM
Parameters
Remarks If any P inputs go beyond the ignore limit for the Ignore time they shall be
ignored.

11.143 IIMCOMMAND

Specific to IEC61850M, IEC61850MSEC


Block(s)
Description Interface Module Command
Data Type Enumeration
Range None (0) – No command Shutdown (1) – Controller will be shutdown IDLE RUN
Default None (0)
Config Load No

- 1381 -
Chapter 11 - Ixxxx Parameters

Active No
Loadable
Access Lock Engineer
Residence 850M
Related IIMSTATE
Parameters
Remarks Shutdown command can be issued when the IIMSTATE is IDLE, which transitions
the controller to the RDY state. No other value of IIMSTATE can be commanded.

11.144 IIMLINKIOID

Specific to IEC61850M, IEC61850MSEC


Block(s)
Description IIM Link Block IOID
Data Type BLOCKID
Range N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence 850M
Remarks This parameter displays the name of the IEC61850LINK block associated with
the platform block.

11.145 IIMSTATE

Specific to IEC61850M, IEC61850MSEC


Block(s)
Description 850M Module State
Data Type Enumeration
BACKUP (8): Application mode with database loaded, all EEs good, module is
secondary.
NOTLOADED (9): Application mode with no database.
CEEIDLE (11): Application mode with database loaded, all EEs good with controller
in IDLE.
CEERUN (12): Application mode with database loaded, all EEs good with controller
in RUN.
Default N/A
Config No
Load
Active No
Loadable

- 1382 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence 850M
Related IIMCOMMAND
Parameters
Remarks IIMSTATE is derived from CEESTATE and platform state. NOTE: SOFTFAIL,
IIMSTATE and CEESTATE are independent of one another. A change in the state of
SOFTFAIL does not cause a change in either IIMSTATE or CEESTATE.

11.146 IIMTYPE

Specific to Block IEC61850M, IEC61850MSEC


(s)
Description
Data Type STRING
Range 64
Default IEC 61850 Interface Module
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence 850M
Related
Parameters
Remarks This parameter displays the name of the IEC61850LINK block associated with
the platform block.

11.147 IIOCS

Specific to All I/O Module Function Blocks


Block(s)
Description Input Consumer Status
Data Type ENUM
Range 0 – BadBySubslot
32 – BadBySlot
64 – BadByDevice
96 – BadByController
128 - Good
Default
Config Load No
Active No
Loadable

- 1383 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence CEE
Related IIOPS, OIOPS, OIOCS
Parameters
Remarks This is consumer status. This status is given by controller’s submodule indicating
whether it is ready for consumption of input data.

11.148 IIOPS

Specific to Block(s) All I/O Module Function Blocks


Description Input Provider Status
Data Type ENUM
Range 0 – BadBySubslot
32 – BadBySlot
64 – BadByDevice
96 – BadByController
128 - Good
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters IIOCS, OIOPS, OIOCS
Remarks This is provider status. This status is given by device for input data.

11.149 IMAGEVER

Specific to C200, EHG, FIM, FIM4, FTEB, IOLIM, LIOM, C300, PGM, EHPMACE, SIM_C200,
Block(s) OPC, ICG, SIMIOLIM
Description Application Image Version - Identifies current personality image version loaded
in the module.
Data Type String
Range Length: 32 Characters Maximum
Default Null
Config Load No
Active No
Loadable

- 1384 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence FTEB, C300, EHG, IOLIM, LIOM, FIM4, FIM, C200, ACE, SIM_C200, OPC, ICG and
SIMIOLIM, PGM, EHPM
Related BOOTIMAGEVER
Parameters
Remarks Current release version of Experion PKS module application firmware.

Specific to Block(s) EIM, UOC


Description Application Image Version.
Data Type String
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (hardware statistics, see C300 definition)

Specific to Block(s) IO RACK


Description Application Image Version
Data Type String
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IO RACK
Related Parameters
Remarks Set by the controller

11.150 IMAGEVER_D

Specific to C300, PGM, FIM4, EHPM, TCMI


Block(s)
Description Application Image Version - Identifies current personality image version loaded
in the module. See Remarks.
Data Type String
Range Length: 32 Characters Maximum
Default Null
Config Load No
Active No

- 1385 -
Chapter 11 - Ixxxx Parameters

Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related IMAGEVER, BOOTIMAGEVER
Parameters
Remarks Dummy duplicate parameter for displaying on Maintenance tab along with Main
tab

Specific to Block(s) UOC


Description Application Image Version
Data Type STRING
Range N/A
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (hardware statistics, see C300 definition)

11.151 IMPORTSTATUS #

Specific to EHPM
Block(s)
Description Import status shows the status of current import (automatic or manual) of the
EHPM points. It shows the status string for the current stage of the EHPM point
import. It shows status for both manual import and automatic import.
Data Type STRING
Range -
Default -
Config Load Yes
Active Yes
Loadable
Access Lock ViewOnly
Residence SRAL
Related AUTOMATICPOINTIMPORT
Parameters
Remarks If the automatic point import option is selected, during the auto import process,
automatic import status shows the current status. The status string messages
shown are Importing, Complete, Information is identical to ERDB and so on.

- 1386 -
Chapter 11 - Ixxxx Parameters

11.152 IMPORTSTS

Specific to Block(s) TCMI


Description Import Status
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

11.153 IMRAVGRESPTIMEDISPREAD

Specific to EHPM
Block(s)
Description This parameter shows the average response time from the HPM Comm Processor
during display read operation. This is the average time taken to service display cyclic
read (for example, HMIWeb display and standard history read).
Data Type FLOAT64
Range -
Default 0
Config No
Load
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

- 1387 -
Chapter 11 - Ixxxx Parameters

11.154 IMRAVGSTDDISPREAD

Specific to EHPM
Block(s)
Description This parameter shows the average response time from the HPM Comm Processor
during display read operation. This is the average time taken to service display
acyclic read (for example, standard history read).
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

11.155 IMRAVGRESPTIMEP2PREAD

Specific to EHPM
Block(s)
Description This parameter shows the average response time from the HPM Comm Processor
during peer-to-peer read operation. This is the average time taken to service peer
cyclic read.
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

- 1388 -
Chapter 11 - Ixxxx Parameters

11.156 IMRAVGRESPTIMEP2PWRITE

Specific to EHPM
Block(s)
Description This parameter shows the average response time from the HPM Comm Processor
during peer-to-peer write operation. This is the average time taken to service peer
acyclic write.
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

11.157 IMRMAXRESPTIMEDISPREAD

Specific to EHPM
Block(s)
Description This parameter shows the maximum response time from the HPM Comm
Processor during display read operation. This is the maximum time taken to service
display cyclic read (for example, HMIWeb display and standard history read).
Data Type FLOAT64
Range -
Default 0
Config No
Load
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

- 1389 -
Chapter 11 - Ixxxx Parameters

11.158 IMRMAXSTDDISPREAD

Specific to EHPM
Block(s)
Description This parameter shows the maximum response time from the HPM Comm
Processor during display read operation. This is the maximum time taken to service
display acyclic read (for example, standard history read).
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

11.159 IMRMAXRESPTIMEP2PREAD

Specific to EHPM
Block(s)
Description This parameter shows the maximum response time from the HPM Comm
Processor during peer-to-peer read operation. This is the maximum time taken to
service peer cyclic read.
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

- 1390 -
Chapter 11 - Ixxxx Parameters

11.160 IMRMAXRESPTIMEP2PWRITE

Specific to EHPM
Block(s)
Description This parameter shows the maximum response time from the HPM Comm
Processor during peer-to-peer write operation. This is the maximum time taken to
service peer acyclic write.
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Yes
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks -

11.161 IMTYPE

Specific to IO RACK
Block(s)
Description ControlEdge 900 Expansion Module
Data Type STRING
Range
Default ControlEdge 900 Expansion Module
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks String used to describe the module that is displayed in the file new menu as well as
on the device properties main tab.

- 1391 -
Chapter 11 - Ixxxx Parameters

11.162 IN

Specific to Block(s) Limit, Checkbad


Description Input value for the IN connection.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

Specific to Block Delay, FTrig, Maxpulse, Minpulse, Not, Offdelay, Ondelay, Pulse, RTrig, Trig,
(s) Watchdog
Description Input value for the IN connection.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

Specific to Block(s) SHL, SHR, ROR, ROL


Description Input value for the IN connection.
Data Type 16-Bit Integer
Range
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 1392 -
Chapter 11 - Ixxxx Parameters

Specific to Block(s) DIGACQ


Description Input Value usually from Channel Block.
Data Type Boolean
Range OFF, ON
Default OFF(0)
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters
Remarks Usually, this parameter exposed as pin connects to a Channels block.

Specific to Block(s) None


Description Input value to rolling average for the IN connection.
Data Type FLOAT64
Range N/A
Default NaN
Config Load Yes
Active Loadable No
Access Lock OtherFbLock
Residence CEE
Related Parameters
Remarks None

11.163 IN[*]

Specific to Block(s) FIRSTOUT


Description Status of Inputs
Data Type Boolean
Range OFF, ON
Default OFF
Config Load YES
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related NUMDINPUTS
Parameters
Remarks Input whose transition needs to be monitored here is connected to this
parameter.

- 1393 -
Chapter 11 - Ixxxx Parameters

Specific to Block(s)
Description PV
Data Type STRUCT
Range
Default
Config Load
Active Loadable No
Access Lock ENGINEER
Residence
Related Parameters
Remarks

Specific to Block(s) PROFCONOUT


Description In Connector
Data Type STRUCT
Range
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence
Related Parameters
Remarks In Connector

11.164 IN[0..2]

Specific to Block(s) EQ, GE, GT, LE, LT, NE, SelReal


Description Input value for the IN connection.
Data Type Real
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 1394 -
Chapter 11 - Ixxxx Parameters

Specific to Block(s) Sel


Description Input value for the IN connection
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

11.165 IN[0..12]

Specific to Genlin
Block(s)
Description Input Coordinates 0 to 12 - These Parameters define the input value at the
respective coordinate for the General Linearization function block.
Data Type 64-Bit Real Number
Range Each coordinate must be greater-than the previous coordinate, and less-than the
next coordinate.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related NUMSEGS, OUT[0..12].
Parameters
Remarks

11.166 IN[1]

Specific to ABS, EXP, LN, LOG, NEG, ROUND, SQRT, TRUNC


Block(s)
Description Input value for the IN connection
Data Type Real
Range
Default 0.0
Config Load No

- 1395 -
Chapter 11 - Ixxxx Parameters

Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks The IN parameters are not loadable and are not intended to be checkpointable or
preset through a configuration dialog. Operators should not expect to access and
use unconnected Math block pins from Control Builder.

11.167 IN[1,2]

Specific to Block CONTACTMON


(s)
Description Input
Data Type Boolean
Range OFF, ON
Default OFF
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks The Normally open and Normally close contact of a single switch will be
connected here.

11.168 IN[1..2]

Specific to DIV, MOD, POW, SUB


Block(s)
Description Input value for the IN connection
Data Type Real
Range
Default 0.0
Config Load No
Active No
Loadable

- 1396 -
Chapter 11 - Ixxxx Parameters

Access Lock Other Function Block


Residence CEE
Related
Parameters
Remarks The IN parameters are not loadable and are not intended to be checkpointable or
preset through a configuration dialog. Operators should not expect to access and
use unconnected Math block pins from Control Builder.

11.169 IN[1..3]

Specific to Block(s) 2oo3


Description Input values for the IN connection
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

11.170 IN[1..8]

Specific to Block(s) And, Mux, MVote, Nand, Nor, Or, Qor, Xor, CheckBool
Description Input value for the IN connection
Data Type Boolean
Range Off (0) On (1)
Default Off (For OR, XOR, QOR, CHECKBOOL, MVOTE) On (For AND, NAND)
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters INSTS[1..8] for CheckBool block
Remarks

Specific to Block(s) Muxreal, Max, Min


Description Input value for the IN connection
Data Type 64-Bit Real Number
Range N/A

- 1397 -
Chapter 11 - Ixxxx Parameters

Default NaN
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

Specific to ADD, MUL


Block(s)
Description Input value for the IN connection
Data Type Real
Range
Default ADD: 0.0 MUL: 1.0
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks The IN parameters are not loadable and are not intended to be checkpointable or
preset through a configuration dialog. Operators should not expect to access and
use unconnected Math block pins from Control Builder.

11.171 IN[1..20]

Specific to Block(s) NooN


Description Input values for the IN connection
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 1398 -
Chapter 11 - Ixxxx Parameters

11.172 IN.Boolean

Specific to Block TypeConvert, Push.


(s)
Description Boolean Input Value - Provides the value fetched from the TypeConvert
function block source.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related EXECSTS
Parameters
Remarks

11.173 IN.ENUM

Specific to Block(s) TypeConvert, Push.


Description Enumerated Input Value
Data Type Enumeration
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EXECSTS
Remarks

11.174 IN.FLOAT32

Specific to TypeConvert, Push.


Block(s)
Description 32-Bit Floating Point Input Value - Provides value fetched from the TypeConvert
function block's source.
Data Type Real
Range N/A
Default NaN

- 1399 -
Chapter 11 - Ixxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related EXECSTS
Parameters
Remarks

11.175 INFLOAT64

Specific to Block Up / Down Counter Block


(s)
Description Input, 64 bit Floating Point Format
Data Type Float 64
Range Floating point equivalent of - (2,147,483,647 -1 ) to 2,147,483,647, must handle
NaN and + /- Infinity
Default 0.0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks This value is used for presetting (load operation) the counter or as a limit for
comparison.

11.176 IN.INT8

Specific to Block(s) TypeConvert, Push.


Description Signed 8-Bit Input Value
Data Type 8-Bit Integer
Range -32768 to 32767
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EXECSTS
Remarks

- 1400 -
Chapter 11 - Ixxxx Parameters

11.177 INT8_VALUE

Specific to INT8_TAG, Scalar UDT Block


Block(s)
Description INT8 Value: This is the Parameter where the value read from control Logix PLC is
Displayed or the Value to be written to the PLC needs to be entered.
Data Type INT8
Range -
Default 0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related Access Lock
Parameters
Remarks Configuration of Access Lock Parameter present on this block determines whether
it has been configured as a Parameter to be read or a Parameter to be written.

11.178 IN.INT16

Specific to Block(s) TypeConvert, Push.


Description Signed 16-Bit Input Value
Data Type 16-Bit Integer
Range -32768 to 32767
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EXECSTS
Remarks

- 1401 -
Chapter 11 - Ixxxx Parameters

11.179 INT16_VALUE

Specific to INT16_TAG, Scalar UDT Block


Block(s)
Description INT16 Value: This is the Parameter where the value read from control Logix PLC is
Displayed or the Value to be written to the PLC needs to be entered.
Data Type INT16
Range -
Default 0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related Access Lock
Parameters
Remarks Configuration of Access Lock Parameter present on this block determines whether
it has been configured as a Parameter to be read or a Parameter to be written.

11.180 ININT32

Specific to Block Up / Down Counter Block


(s)
Description Input, Integer Format
Data Type Integer 32
Range - (2,147,483,647 -1 ) to 2,147,483,647
Default 0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks This value is used for presetting (load operation) the counter or as a limit for
comparison.

- 1402 -
Chapter 11 - Ixxxx Parameters

11.181 INT32_VALUE

Specific to INT32_TAG, Scalar UDT Block


Block(s)
Description INT32 Value: This is the Parameter where the value read from control Logix PLC is
Displayed or the Value to be written to the PLC needs to be entered.
Data Type INT32
Range -
Default 0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related Access Lock
Parameters
Remarks Configuration of Access Lock Parameter present on this block determines whether
it has been configured as a Parameter to be read or a Parameter to be written.

11.182 IN.SDENUM

Specific to Block(s) TypeConvert, Push.


Description Self Defining Enumeration Input.
Data Type Integer
Range Positive Integers
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters EXECSTS
Remarks

- 1403 -
Chapter 11 - Ixxxx Parameters

11.183 IN.UINT8

Specific to TypeConvert, Push.


Block(s)
Description Unsigned 8-Bit Input Value - Provides the value fetched from the
TYPECONVERT function block's source.
Data Type Unsigned 8-Bit Integer
Range 0 to 255
Default 0
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related EXECSTS, INSRC[1..8]
Parameters
Remarks

11.184 IN.UINT16

Specific to TypeConvert, Push.


Block(s)
Description Unsigned 16-Bit Input Value - Provides the value fetched from the TypeConvert
function block's source.
Data Type Unsigned 16-Bit Integer
Range 0 to 65535
Default 0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related EXECSTS
Parameters
Remarks

- 1404 -
Chapter 11 - Ixxxx Parameters

11.185 IN.UINT32

Specific to Block(s) TypeConvert, Push.


Description Unsigned 32-Bit Input Value
Data Type Unsigned 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters EXECSTS
Remarks

11.186 INACTINDETTM[1..8]

Specific to CheckBool Logic Block


Block(s)
Description Inactive Input Detection Threshold Time.
Data Type Float64
Range 0-8000 sec
Default 60
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related BADINACT[1..8], BADINACTMINTM[1..8]
Parameters
Remarks Specifies the delay time (in seconds) required before OUT[1..8] will be changed to
the value configured in BADINACT[1..8]. The input status must remain “INACTIVE”
for the entire detection threshold time before the configured action is taken.

- 1405 -
Chapter 11 - Ixxxx Parameters

11.187 INALM

Specific to All alarming basic blocks and all independent blocks (FlowComp, RegCtl, CEE,
Block(s) CEEC300, CM, CPM, C300, PCDI_MASTER, DataAcq, DevCtl, ICG, IOM, Flag, SCM,
Push)
Description Function Block In Alarm Flag - Indicates if an alarm condition has been detected
with this function block.
Data Type Boolean
Range Off (0): Function block is not in alarm On (1): Function block is in alarm
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Respective Device, Controller or Platform
Related DevCtl only: CMDDISALM.FL, CMDFALALM.FL, SIALM.FL, UNCMDALM.FL.
Parameters
Remarks Flag block only:
l When INALM is On (1), HIALM.TYPE will always be OFFNRMLALM.
l When INALM is Off (0), HIALM.TYPE will always be NONE.
CEE, CPM blocks: Indicates if one or more diagnostic alarms are presently active
within the block.

Specific to DICHANNEL (PM I/O)


Block(s)
Description In Alarm Flag. Shows whether an alarm condition exits or not.
Data Type Boolean
Range 0 Off No alarm.
1 On Alarm exists.
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM/IOLINK
Related N/A
Parameters
Remarks This parameter is only exposed when the PNTFORM is Full. When the INALM
parameter is On, a red border appears around the block when viewing the control
strategy in the Monitoring mode through Control Builder.

Specific to MAINIBV, DIGACQ, CONTACTMON, FIRSTOUT, LEVELCOMP, GRPCAPRBK, ROC,


Block(s) ALMWINDOW, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER
Description FB In-Alarm Flag
Data Type Boolean
Range OFF (0): Function block is not in alarm ON (1): Function block is in alarm

- 1406 -
Chapter 11 - Ixxxx Parameters

Default OFF
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CLOSESEQALM.FLBADPVALM.FL
Parameters
Remarks

Specific to Block(s) EIM Platform Block


Description In-Alarm
Data Type Boolean
Range NA
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

Specific to All alarming basic blocks and all independent blocks (RegCtl, CEE, CEEC300, CM, CPM,
Block(s) C300, CEEUOC, CEECN100, DataAcq, DevCtl, IOM, Flag, SCM, Push)
Description In-Alarm Flag

Data Type BOOLEAN

Exposure Output
Range Off (0) – Function block is not in alarm On (1) – Function block is in alarm
Default Off

Config No
Load
Access View Only
Lock

Residence Respective Device/Controller/Platform

Related N/A
Parameters

Remarks Indicates if one or more diagnostic alarms are presently active within the block.

- 1407 -
Chapter 11 - Ixxxx Parameters

11.188 INALT

Specific to FLAG block


Block(s)
Description In Alert Flag - This parameter indicates that an alert condition is detected.
Data Type Boolean
Range OFF (Alert is not detected)
ON (Alert is detected)
Default OFF
Config Yes
Load
Active No
Loadable
Access Lock View Only
Residence CEE
Related INALMALTENBOPTHIALM.TYPE
Parameters
Remarks This parameter is set to “ON“ only when an alert is generated. When INALT is set to
OFF, the alert returns to normal in the Alert Summary Display. Note: INALT cannot
be ON when and INALM is ON and INALM cannot be ON when INALT is ON.

11.189 INBADOPT

Specific to DIC
Block(s)
Description Input Bad Option - Configurable Value from the following range is substituted when
input is determined to be bad.
Data Type Enumeration INBADOPT
Range Off (0) On (1) Hold (2)
Default Off (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks INBADOPT is meant for use when the DICHANNEL's PV is connected to a block that
only uses value and not status. For blocks that take value and status, the
configured INBADOPT value is sent with a Bad status when Input is determined to
be bad.

- 1408 -
Chapter 11 - Ixxxx Parameters

Specific to EQ, GE, GT, LE, LT, NE


Block(s)
Description Input Bad Option - Defines the output fail-safe value when any input is Not a
Number (NaN). This is required since it is not specified whether the comparison is
ordered or unordered.
Data Type Boolean
Range Off, On
Default Off
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks If IN[1] and/or IN[2] are NaN, OUT and INBADOPT is set to ON.

11.190 INBADOPT

Specific to UDT Block


Block(s)
Description Input Bad Option — This is an enumerated type that indicates what the UDT
members would be set to if the UDT block fails to receive valid data from the PLC for
some reason.
Data Type ENUM
Range l 0 : DEFAULT
l 1 : HOLD
Default HOLD
Config Yes
Load
Active No
Loadable

- 1409 -
Chapter 11 - Ixxxx Parameters

Access Lock Engineer


Residence CEE
Related None
Parameters
Remarks The options for this parameter include:
l DEFAULT — All the parameters are set to the default value based on their
datatype
l HOLD — Holds the last known value
The values based on the datatype, when DEFAULT has been chosen are as follows:
l INT8/INT16/INT32 = 0
l FLOAT32 = NAN
l BOOLEAN = OFF
l STRING = Blank
This configuration will apply to all kinds of UDTs ( a UDT with only read parameters,
only write parameters, or a combination of both). During communication failures,
the write parameters do not take the value that you enter (user-specified value), if
the INBADOPT value is Default. It takes the user-specified value if the INBADOPT
value is Hold.

11.191 INBETFL

Specific to Block(s) DEVCTL, SOLENOID, VALVEDAMPER


Description Process Variable (PV) In Between State Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters GPV, PV, DEVCTL Only: DIMODEDIPVMAP[0..15], NUMDINPUTS.
Remarks Illegal if DIPVMAP is not selected for InBet. Illegal if NUMDINPUTS = 0.

11.192 INCLAMPOPT

Specific to Up / Down Counter Block


Block(s)
Description Input Clamping Option
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Load Yes

- 1410 -
Chapter 11 - Ixxxx Parameters

Active No
Loadable
Access Lock Application Developer
Residence CEE
Related INFLOAT64
Parameters
Remarks This parameter is referred to determine whether special handling is required for
out of range values or invalid INFLOAT64 values.

11.193 INCLUDEINTEGRATORCLRI

Specific to Block(s) ProfitCtl


Description Include Integrator for CLR
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

11.194 INCOMPLETE

Specific to CAB types


Block(s)
Description Flag parameter that automatically gets set whenever the parameter definitions of a
CAB type have been modified. INCOMPLETE is automatically cleared when the CAB
type is successfully built in Microsoft .Net Framework 4.0. CAB types can be saved to
ERDB when INCOMPLETE is True. Also, CAB instances can be used when
INCOMPLETE is True. However, instances cannot be loaded to the CEE unless
INCOMPLETE is False.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Boolean
Range False, True
Default False
Config Load No
Active No
Loadable

- 1411 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence System Repository
Related None
Parameters
Remarks

11.195 INDESC[*]

Specific to FIRSTOUT
Block(s)
Description Description of Inputs
Data Type String
Range 32 Characters
Default INPUT #
Config Load YES
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks This is a configurable parameter which may be set by the user prior to loading the
block to the controller. This description will be shown in the alarms description.

11.196 INDPTOUTINIT

Specific to FANOUT
Blocks
Description Independent Output Initialization
Data Type BOOLEAN
Range
Default FALSE
Config. Load Yes
Active No
Loadable
Access Lock APPDEVONLY
Residence CEE
Related
Parameters
Remarks Setting the parameter to TRUE removes the requirement of adding an AUTOMAN
on each output of the FANOUT.

- 1412 -
Chapter 11 - Ixxxx Parameters

11.197 INDRCTSYNC

Specific to C200, C300, FIM4, PGM and LIOM FBs


Block(s)
Description Indirect Synchronization State - Indirect synchronization is a multistage process,
which requires several steps of interaction with the Controller Migration Wizard.
Data Type Enumeration
Range DISABLED (0) Indicates that an On-Process Migration session
is not in progress.
WAITSYNC1 (1) Module is waiting for snapshot restore of the
secondary to complete.
WAITSYNC2 (2) Module is waiting for the command to
synchronize and switchover.
WAITSYNC3 (3) Module is waiting to commence initial
synchronization.
WAITSYNC4 (4) Module is waiting for the opening of secondary
I/O connections to complete.
TRANSFERDSD (5) Control processing in the primary is frozen and
Dynamic State Data (DSD) is being transferred
from primary to secondary.
SWITCHOVER (6) Controller initiates redundancy switchover.
MATCHPEERREFS (7) Matching peer references.
Default DISABLED (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, C300, FIM4, PGM and LIOM
Related DIRECTSYNC, INDSYNCCMD.
Parameters
Remarks A transition in INDRCTSYNC results in the generation of a system event
notification.

- 1413 -
Chapter 11 - Ixxxx Parameters

11.198 INDSYNCCMD

Specific to C200, FIM4, LIOM, PGM and C300 FBs


Block(s)
Description Indirect Synchronization Command - Command is written by the Controller
Migration Wizard to control specific phases of the indirect synchronization process.
Data Type Enumeration
Range NONE (0) No Command
ENABLE (1) Begin a new On Process Migration session. Results in the transition
of INDRCTSYNC out of the initial state of DISABLED, and causes
the primary module to disable configuration and snapshot restore
but to keep processing control.
SYNCSWITCH Following secondary snapshot restore, this starts the final
(2) sequencing of indirect synchronization and leads to redundant
controller switchover.
ABORT (3) Terminate current On Process Migration session. The stages of
indirect synchronization are covered by time-out monitoring so that
if the Controller Migration Wizard dies or if communication is
interrupted, the Controller can terminate activity on its own and
revert to a safe quiescent state. ABORT is provided so that the
Controller Migration Wizard can terminate indirect synchronization
without waiting for timeout.
Default NONE (0)
Config No
Load
Active No
Loadable
Access Intimate User
Lock
Residence C200, C300, FIM4 and LIOM, PGM
Related DIRECTSYNC, INDRCTSYNC.
Parameters
Remarks This parameter has edge trigger semantics and always returns NONE when read.

11.199 INFLOAT64

Specific to Block Up / Down Counter Block


(s)
Description Input, 64 bit Floating Point Format
Data Type Float 64
Range Floating point equivalent of - (2,147,483,647 -1 ) to 2,147,483,647, must handle
NaN and + /- Infinity
Default 0.0
Config Load No
Active Loadable No

- 1414 -
Chapter 11 - Ixxxx Parameters

Access Lock Other Function Block


Residence CEE
Related
Parameters
Remarks This value is used for presetting (load operation) the counter or as a limit for
comparison.

11.200 ININT32

Specific to Block Up / Down Counter Block


(s)
Description Input, Integer Format
Data Type Integer 32
Range - (2,147,483,647 -1 ) to 2,147,483,647
Default 0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks This value is used for presetting (load operation) the counter or as a limit for
comparison.

11.201 INITCOMPLETE

Specific to CPM200, CPM, CPM200S, ACE, SIM -C200, C300, C300SEC, SIMIOLIM, CEEC300,
Block(s) FIM4, FIM4SEC, EHG, EHGS, UOC, UOCSEC, CEEUOC, CEECN100
Description Initialization Complete
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200,C300,ACE,SIM-C200, UOC, CN100
Related
Parameters
Remarks -

- 1415 -
Chapter 11 - Ixxxx Parameters

11.202 INITCONNECTD[0..1]

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Init Connection Flag
Data Type Boolean
Range ON OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters BACKCALCIN
Remarks

11.203 INITCONNECTD[1..3]

Specific to DevCtl
Block(s)
Description Initialization Connection Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BACKCALCIN[1..3]
Parameters
Remarks INITCONNECTD[i] is automatically set to On (1) by the function block (on the
Control Module's EXECSTATE transition to Active) if the BACKCALCIN[i] is
connected to a k structure.

11.204 INITCOUNTER

Specific to Block(s) ProfitCtl


Description Init counter
Data Type INT16
Range NA
Default 0

- 1416 -
Chapter 11 - Ixxxx Parameters

Config Load Yes


Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

11.205 INITMAN

Specific to DevCtl, Pulse Count Control, Pulse Length Control, HTmotor, LTmotor, Solenoid,
Block(s) ValveDamper
Description Initialization Manual Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related GOP, GPV, INITOPAFTLD, INITOPOPTOP, PV, SI. DevCtl: NUMDOUTS, Pulse Length
Parameters Control: BACKCALCOUT
Remarks DEVCTL Only: Illegal if NUMDOUTS = 0. Pulse Length only: When the Pulse Length
function block goes into initialization mode, either because it's Secondary (DOC)
requested it or because the LOCALMAN is On, INITMAN goes On. It is reset to Off
only when it's Primary (usually PosProp) receives the initialization request and it's
Secondary is out of initialization.

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Initialization Manual Flag - When On, it indicates that the function block is in
Initialization Manual. INITMAN goes On when either a cascade is broken (that is, a
block's mode is not Cascade), or initialization is requested by a secondary.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable

- 1417 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence CEE
Related BACKCALCIN, BACKCALCIN[1..3], BACKCALCIN[1..8].
Parameters
Remarks

11.206 INITOPAFTLD

Specific to DevCtl
Block(s)
Description OP and DO Initialization after Load
Data Type Enumeration INITSTATE
Range DEFAULT, STATE0, STATE1, STATE2
Default Default
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related DO[1..3], GOP, OP, OPDOMAP[0..3][1..3], NUMDOUTS.
Parameters
Remarks Illegal if NUMDOUTS = 0. When the default option for parameter INITOPAFTLD is
selected, there may be a mismatch between the OP value and the DO states until a
back-initialization or state change occurs. State0 may not correspond to all DOs of 0
(OFF).

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description OP, CmdRun(Open) and CmdStop(Close) Initialization after Load
Data Type Enumeration
Range Default, Run, stop for LT/HT and default,open, close, nocommand for
VLVDAMPER, default, open, close for SOLND
Default Default
Config Load YES
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related CMDRUNCMDSTOPGOP, OP
Parameters
Remarks

- 1418 -
Chapter 11 - Ixxxx Parameters

11.207 INITOPOPT

Specific to Block(s) DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Output (OP) Initialization Option
Data Type Enumeration INITOPOPT
Range NORMALOPOPT, HOLDOPOPT, SAFEOPT
Default NORMALOPOPT
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters OP, GOP, INITMAN, DEVCTL Only: NUMDOUTS.
Remarks DEVCTL Only: Illegal if NUMDOUTS = 0.

11.208 INITPENDING

Specific to Control Module in CEE. Not supported in FIM or LIOM.


Block(s)
Description Initialization Pending - Indicates when the CM is holding off read requests in order
to initialize.
Data Type BOOLEAN
Range Off On
Default Off
Config No
Load
Active No
Loadable
Access Lock ReadOnly
Residence CEE
Related RELOADINIDLY CURRELINIDLY RSTRTINIDLY
Parameters
Remarks For any particular CM, INITPENDING is On whenever CURRELINIDLY is nonzero.
INITPENDING does not convey any information that is not already shown by the
value of CURRELINIDLY. However, it may be used in logic strategies or schematic
displays if appropriate.

- 1419 -
Chapter 11 - Ixxxx Parameters

11.209 INITREQ

Specific to Pulse Length Control, Pulse Count Control


Block(s)
Description Initialization request for Primary.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BACKCALCOUT
Parameters
Remarks When the Pulse Length Control function block goes into an Initialization mode,
either because it's Secondary (DOC) requested it or because the LOCALMAN is on,
INITREQ goes ON. It is reset to OFF only when it's Primary (usually POSPROP)
receives the initialization request and it's Secondary is out of initialization.

Specific to Deadtime, Leadlag


Block(s)
Description Initialization Request Flag - Indicates if the function block has been requested to
initialize. If the flag is On, those function blocks will reset their calculated and/or
accumulated values.
Data Type Boolean
Range Off (0) - Initialization is not requested. On (1) - Initialization is requested.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks If the flag is set, those function blocks will reset their calculated and/or
accumulated values. The function block sets INITREQ to On whenever it becomes
active. INITREQ may also be set by other function blocks.

Specific to SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


Block(s)
Description Initialization Request Flag - Indicates the validity of the array data.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)

- 1420 -
Chapter 11 - Ixxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BADPVFL, ERRFL.
Parameters
Remarks INITREQ is always equal to ERRFL; this parameter is provided to be consistent with
other function blocks that provide an INITREQ that indicates whether the block can
be stored to at the current time.

Specific to AOC, DOC, PWM Channel


Block(s)
Description Initialization Request Flags - Used by a function block; it requests a primary to
initialize. There is one flag for each primary.
Data Type Boolean
Range Off (0): Full output path is normal.
On (1): Output path has been broken and needs
to be back initialized.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related INITVAL
Parameters
Remarks

Specific to AOCHANNEL, HAOCHANNEL, DOCHANNEL (PM I/O), AOCHANNEL, DOCHANNEL


Block(s) (Series C I/O)
Description Initialization Request. Shows the state of the back initialization request for the
associated output channel block.
Data Type Boolean
Range 0 Off Full output path is normal.
1 On Output path has been broken and
needs to be back initialized.
Default On (1)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks

- 1421 -
Chapter 11 - Ixxxx Parameters

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Initialization request for Primary
Data Type Boolean
Range OFF (0) ON (1)
Default OFF
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related GOP, OP
Parameters
Remarks OFF indicates that the block will be able to act on a command to that state (index 0
corresponds to state 0, index 1 to state 1, and index 2 to state 2).

11.210 INITREQ[0..2]

Specific to DevCtl
Block(s)
Description Initialization Request Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related GOP, OP.
Parameters
Remarks Off indicates that the block will be able to act on a command to that state (index 0
corresponds to state 0, index 1 to state 1, and index 2 to state 2).

- 1422 -
Chapter 11 - Ixxxx Parameters

11.211 INITREQ[1..8]

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Initialization Request Flags - Used by a function block to request a primary to
initialize. There is one flag for each primary.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related INITVAL[1..8]
Parameters
Remarks

11.212 INITREQLATCH

Specific to Block(s) AOC, DOC, PWM Channel, AOCHANNEL, DOCHANNEL


Description Initialize Request Latched
Data Type Boolean
Range 0 Off (False)
1 On (True)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

11.213 INITREQSRC

Specific to Block(s) RegCalc


Description INITREQ (Initialization Request Flag) source selector
Data Type Enumeration REGCALCSELECTOR
Range X1 to C8STS

- 1423 -
Chapter 11 - Ixxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

11.214 INITVAL

Specific to AOC, DOC, PWM Channel


Block(s)
Description Initialization Value - The value to which a primary should initialize. There is one
value for each primary.
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related INITREQ
Parameters
Remarks

Specific to AOCHANNEL, HAOCHANNEL (PM I/O); AOCHANNEL (Series C I/O)


Block(s)
Description Initialization Value - The value to which a primary should initialize. There is one
value for each primary.
Data Type 64-Bit Real Number
Range -6.9 % to 106.9 %
Default 0.0 %
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related OP
Parameters
Remarks This is the back initialization value read from the IOP.

- 1424 -
Chapter 11 - Ixxxx Parameters

11.215 INITVAL_AO_S

Specific to UIO, AO04, AO08


Block(s)

Description Echo Back Value


Data Type FLOAT64
Range -6.9% to 106.9%
Default 0.0%
Config Load No
Active
Loadable

Access Lock ViewOnly


Residence IOM Block
Related OUTPUTVALUE_AO_S, OUTPUTFINAL_AO_S
Parameters

Remarks Indicates the value to which the primary point is to be initialized. This is the back
initialization value read from the IOM.

11.216 INITVAL_DO_S
Delete this text and replace it with your own content.

11.217 INITVAL[0..numChans-1]

Specific to Block EIP Analog Output Modules


(s)
Description Echo back value, initialization value - The value to which a primary value
should initialize.
Data Type FLOAT32
Range

Default 0.0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related None
Parameters
Remarks It is indexed by the channel number.

- 1425 -
Chapter 11 - Ixxxx Parameters

11.218 INITVAL[1..8]

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Initialization Value - The value to which a primary should initialize. There is one
value for each primary.
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

11.219 INITVAL[1..NUMCHAN]

Specific to Block(s) AO8, AO16


Description Echoback Value
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOP
Related Parameters
Remarks

11.220 INITVALSRC

Specific to Block(s) RegCalc


Description Initialization Value (INITVAL[1..8]) source selector.
Data Type Enumeration REGCALCSELECTOR
Range X1 to C8STS (0 - 27)
Default X1 (0)

- 1426 -
Chapter 11 - Ixxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

11.221 INPIN

Specific to Block(s) ProfitCtl


Description In Connector
Data Type INCONN
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence
Related Parameters
Remarks

11.222 INPTDIR

Specific to AICHANNEL, HAICHANNEL (PM I/O) ; AICHANNEL (Series C I/O)


Block(s)
Description Input Direction. Specifies response to analog PV input as direct or reverse. Direct
action means that PVCALC increases as PVRAW input increases. Reverse action
means that PVCALC decreases as PVRAW input increases.
Data Type Enumeration
Range 0 DIRECT PVCALC increases as
PVRAW increases
1 REVERSE PVCALC decreases as
PVRAW increases
Default Direct (0)
Config Load Yes
Active No
Loadable

- 1427 -
Chapter 11 - Ixxxx Parameters

Access Lock Engineer/Application Developer


Residence IOM
Related N/A
Parameters
Remarks Input Direction applies to Linear and Square Root PV characterizations.

Specific to DICHANNEL (PM I/O)


Block(s)
Description Input Direction. Specifies response to digital PV input as direct or reverse. Direct
action means that the PV condition tracks the PVRAW condition, when PVRAW is Off
the PV is Off and when it is On the PV is On. Reverse action means that the PV
condition is the opposite of the PVRAW condition, when PVRAW is Off the PV is ON
and when it is On the PV is Off.
Data Type Enumeration
Range 0 DIRECT If PVRAW = Off, PV = Off If
PVRAW = On, PV = On
1 REVERSE If PVRAW = Off, PV = On If
PVRAW = On, PV = Off
Default DIRECT (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOM
Related N/A
Parameters
Remarks This parameter is only exposed when the PNTFORM is Full.

Specific to Blocks HRBALG_HLPIUDI, HRBALG_HLPIUDC


Description Input Direction
Data Type ENUM
Range DIRECT REVERSE
Default DIRECT
Config. Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This parameter represents the direction of the HLPIU digital input’s
direction.

- 1428 -
Chapter 11 - Ixxxx Parameters

11.223 INPTDIR_AI_C

Specific to Block(s) UIO


Description Input Direction
Data Type ENUM
Range
0 DIRECT PV increases as the raw value increases

1 REVERSE PVCALC decreases as the raw value


increases" with "PV decreases as the raw
value increases

Default Direct
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks Remove all

Specific to UAI, AI16-100MS


Block(s)

Description Input Direction


Data Type ENUM
Range
0 DIRECT PV increases as the raw value increases

1 REVERSE PV decreases as the raw value increases

Default Direct
Config Yes
Load

Active
Loadable

Access AppDevOnly
Lock

Residence IOM Block


Related
Parameters

Remarks This parameter provides the user the ability to specify a way to normalize the analog
input form the sensor to be used by control. The processing is as follows:
l For DIRECT: PV increases as the raw value increases
l For REVERSE: PV decreases as the raw value increases

- 1429 -
Chapter 11 - Ixxxx Parameters

11.224 INPTDIR_DI_C

Specific to Block(s) UIO


Description Input Direction
Data Type ENUM
Range
0 DIRECT If Raw value = Off, PV = Off

If Raw value = On, PV = On

1 REVERSE If Raw value = Off, PV = On

If Raw value = On, PV = Off

Default Direct
Config Load Yes
Active Loadable No
Access Lock Engineer / Application Developer
Residence CEE
Related Parameters N/A
Remarks Remove all

Specific to UIO, DI32-24VDC, DI16-VAC, DI16-DRYCT, DI16-VACDC


Block(s)

Description Input Direction


Data Type ENUM
Range
0 DIRECT If Raw value = Off, PV = Off

If Raw value = On, PV = On

1 REVERSE If Raw value = Off, PV = On

If Raw value = On, PV = Off

Default Direct
Config Load Yes
Active No
Loadable

- 1430 -
Chapter 11 - Ixxxx Parameters

Access Lock Engineer / Application Developer


Residence IOM Block
Related N/A
Parameters

Remarks This parameter provides the user the ability to specify a way to normalize the digital
input form the sensor to be used by control.
The processing is as follows:
For DIRECT: When Raw Field Value is OFF -> PV will be OFF
When Raw Field Value is ON -> PV will be ON
For REVERSE: When Raw Field Value is OFF -> PV will be ON
When Raw Field Value is ON -> PV will be OFF

11.225 INPTDIR_DO_C
Delete this text and replace it with your own content.

11.226 INPTINVSTS[1..2]

Specific to Block(s) Sel


Description Input Inversion Status
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

11.227 INPTINVSTS[1..8]

Specific to Block(s) And, Nand, Nor, Or, Qor, Xor, Mux


Description Input Inversion Status
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No

- 1431 -
Chapter 11 - Ixxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters NUMOFINPUTS
Remarks

11.228 INPTWIRETYP

Specific to Block(s) Series C AICHANNEL Block Only

Description Input Wire Connection Type

Data Type ENUM

Exposure OUTPUT

Range 0 2-Wire TC or RTD with 2 wire


connection

1 3-Wire RTD with 3 wire connection

2 4-Wire RTD with 4 wire connection

Default 2 Wire

Config Load Yes

Engineer / Application Developer

Residence IOM

Related N/A
Parameters

Remarks Applicable for only channels where SENSRTYP is: either THERMCPL or RTD.

Internal Only No

11.229 INPUTACTED[*]

Specific to Block FIRSTOUT


(s)
Description Input acted flag of Input 1 to 24
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No

- 1432 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This flag is set to on when the corresponding INPUT[*] transition caused First
Out detection.

11.230 INPUTCHGDB

Specific to Push
Block(s)
Description Input change deadband
Data Type Real
Range Non-zero positive number
Default 0.001
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks Change in the input value has to be more than the INPUTCHGDB for that value
to be stored to destination.

11.231 INPUTERROR

Specific to Block(s) Steam Property Block


Description Input Error
Data Type BOOLEAN
Range OFF
ON
Default OFF
Access Lock View Only
Residence CEE
Related PRESSURE
Parameters TEMPERATUREENTHALPYENTROPYSPECIFICVOLUMESTEAMQUALITY
Remarks This parameter value is set to "ON" when the input is out of range.

- 1433 -
Chapter 11 - Ixxxx Parameters

11.232 INPTDIR

Specific to Blocks HRBALG_HLPIUDI


Description Input Direction
Data Type ENUM
Range DIRECT REVERSE
Default DIRECT
Config. Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This parameter represents the direction of the HLPIU digital input’s
direction.

11.233 INPUTRANGE[0..numChans-1]

Specific to AIM
Block(s)
Description Input Range
Data Type Enumeration of INPUTRANGE Enumeration of INPUTRANGE_TC for Thermocouple
modules Enumeration of INPUTRANGE_RTD for RTD modules
Range INPUTRANGE -10V_to_10V (0) 0V_to_5V (1) 0V_to_10V (2) 4mA_to_20mA (3)
INPUTRANGE_TC -12_to_78mV (4) -12_to_30mV (5) INPUTRANGE_RTD 1-487_
ohms (6) 2-1000_ohms (7) 4-2000_ohms (8) 8-4020_ohms (9)
Default INPUTRANGE: 4mA_to_20mA (3) INPUTRANGE_TC: -12_to_78mV (4) INPUTRANGE_
RTD: 1-487_ohms (6)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks

- 1434 -
Chapter 11 - Ixxxx Parameters

11.234 INPUTRANGE[0..7]

Specific to Block Chassis HART AI IOM


(s)
Description Input Range
Data Type Enumeration of INPUTRANGE
Range -10V_TO_10V (0) 0V_TO_5 V (1) 0V_TO_10 V (2) 4MA_TO_20 MA (3) 1V_TO_5V (4)

Default 4MA_TO_20 MA (3)


Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Active Connector Yes
Related HART[0..7]
Parameters
Remarks Input range is fixed at 4MA_TO_20 MA range when HART parameter is selected
for the channel.

11.235 INPUTROC

Specific to ROC
Block(s)
Description This parameter displays the rate of change of the input parameter P1. The unit for
rate of change is EU/Min. The change in the parameter P1 from one CM scan to
the next scan is used to compute rate of change. There is no filtering done on this
parameter.
Data Type FLOAT
Range
Default NaN
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related P1
Parameters
Remarks

- 1435 -
Chapter 11 - Ixxxx Parameters

11.236 INPUTSTREAM

Specific to Series C PICHANNEL


Block(s)
Description Input Stream Type
Data Type ENUM
Range Single(0) Dual(1)
Default Single
Config Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence IOM
Related N/A
Parameters
Remarks Enables selection between single and dual pulse-stream operation. To select dual
pulse-stream, the channel must be odd-numbered and the channel's pulse stream
partner channel must not have been configured. Channels {1,2}, {3,4}, {5,6} and
{7,8} are partnered together.

11.237 INPUTTYPE

Specific to Blocks HRBALG_HLPIUDI, HRBALG_HLPIUDC


Description Point Input Type
Data Type ENUM
Range NOTIFYSTATE CHANGEDETECT SOE
Default NOTIFYSTATE
Config. Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This parameter represents the type of DI point.

- 1436 -
Chapter 11 - Ixxxx Parameters

11.238 INSBLOCK[1..10]

Specific to DATAACQ, All Regulatory Control Blocks except PROSPROP, PULSECOUNT,


Block(s) PULSELENGHT, REGCALC
Description Insert Block - Identifies name of CAB instance associated with insertion type.
Data Type BlockId
Range
Default Null
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related INSTYPE[1..10]
Parameters
Remarks

11.239 INSERTINDEX

Specific to Block(s) CM, SCM


Description The number of blocks ever inserted.
Data Type Integer
Range N/A
Default 1
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

11.240 INSERTSTS[1..10]

Specific to DATAACQ, All Regulatory Control Blocks except PROSPROP, PULSECOUNT,


Block(s) PULSELENGHT, REGCALC
Description Insertion Status - Shows execution status for given insertion point.
Data Type Enumeration INSERTSTS
Range (0) Unloaded, (1) Normal, (2) Exception, (3) Termination, (4) Dormant (5)
Notsupported
Default Normal

- 1437 -
Chapter 11 - Ixxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The status should be NORMAL, if the insertion program executes until completion
with no failures. The status is set to the value returned by the inserted CAB
program

11.241 INSFAILFL

Specific to DATAACQ, All Regulatory Control Blocks except PROSPROP, PULSECOUNT,


Block(s) PULSELENGHT, REGCALC.
Description Insertion Fail Flag - Indicates if an alarm condition has been detected for an
insertion failure.
Data Type Boolean
Range Off (False), On (True)
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Insertion fail alarm is generated by the calling block, if the insertion program
returns a non-normal state, except termination.

11.242 INSFAIL.PR

Specific to DATAACQ, All Regulatory Control Blocks except PROSPROP, PULSECOUNT,


Block(s) PULSELENGHT, REGCALC
Description Insertion Fail Priority - Shows the priority associated with the insertion failure
alarm.
Data Type Enumeration
Range (0) None, (1) Journal, (2) Low, (3) High (4) Urgent
Default None
Config Load Yes
Active Loadable No

- 1438 -
Chapter 11 - Ixxxx Parameters

Access Lock Engineer


Residence CEE
Related INSFAILFL
Parameters
Remarks

11.243 INSFAIL.SV

Specific to DATAACQ, All Regulatory Control Blocks except PROSPROP, PULSECOUNT,


Block(s) PULSELENGHT, REGCALC
Description Insertion Fail Severity - Shows the severity associated with the insertion failure
alarm.
Data Type Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related INSFAILFLINSFAIL.PR
Parameters
Remarks

11.244 INSFAILALM.FL

Specific to Block All Regulatory Control Blocks


(s)
Description Insertion Fail Flag - Indicates if an alarm condition has been detected for an
insertion failure.
Data Type Boolean
Range Off, On
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related INSFAILFL
Parameters
Remarks

- 1439 -
Chapter 11 - Ixxxx Parameters

11.245 INSFAILALM.PR

Specific to Block(s) All Regulatory Control Blocks


Description Insertion Fail Priority - Shows the priority associated with the insertion
failure alarm.
Data Type Enumeration
Range (0) None, (1) Journal, (2) Low, (3) High (4) Urgent
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related INSFAILFL
Parameters
Remarks

11.246 INSFAILALM.SV

Specific to Block All Regulatory Control Blocks


(s)
Description Insertion Fail Severity - Shows the severity associated with the insertion
failure alarm.
Data Type Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related INSFAILFLINSFAILALM.PR
Parameters
Remarks

- 1440 -
Chapter 11 - Ixxxx Parameters

11.247 INSFAILFL

Specific to DATAACQ, All Regulatory Control Blocks except PROSPROP, PULSECOUNT,


Block(s) PULSELENGHT, REGCALC.
Description Insertion Fail Flag - Indicates if an alarm condition has been detected for an
insertion failure.
Data Type Boolean
Range Off (False), On (True)
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Insertion fail alarm is generated by the calling block, if the insertion program
returns a non-normal state, except termination.

11.248 INSMASTER

Specific to CAB types


Block(s)
Description Insertion Master. Parameter that automatically gets set whenever the CAB
instance is configured to be an insertion point algorithm. Contains the name
(BlockId) of the block that uses the CAB instance as an insertion point algorithm.
INSMASTER is cleared when the CAB instance is configured for normal execution
processing.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type BlockId
Range
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence System Repository
Related None
Parameters
Remarks

- 1441 -
Chapter 11 - Ixxxx Parameters

11.249 INSRC[1..8]

Specific to Block(s) CheckBool Logic Block


Description Input Structured Source - Provides information for the input connection.
Data Type STRUCT strCfDiscreteValueStatus
Range (0) TC_Boolean (1) (8) TC_STRUCT
Default TC_Boolean
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters IN[1..8], INSTS[1..8]
Remarks

11.250 INTERLANCOMMFAILED

Specific to Block(s) TCMI


Description Internal LAN Comm Failed
Data Type BOOLEAN
Range N/A
Default --
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

11.251 INTGPD_SET

Specific to Block(s) EIM


Description intgPd Setting
Data Type ENUM
Range NA
Default Dynamic
Config Load
Active Loadable No

- 1442 -
Chapter 11 - Ixxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related Parameters
Remarks

11.252 INSTRUCTCNFM

Specific to Step
Block(s)
Description Step Instructions Confirmation
Data Type Boolean
Range Off - Confirmation not requested On - Confirmation requested for all confirmable
Instructions of the Step
Default Off
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related INSTRUCTCOMP, INSTRUCTPEND
Parameters
Remarks Used for a Step level confirmation of all confirmable Instructions of the Step.
Should not be accessed by the user directly. This parameter is used by the SCM
Table View to verify that a Step level confirmation is possible, and then the display
will individually confirm all Outputs as needed, so that journal entries will exist for
each Output.

11.253 INSTRUCTCOMP

Specific to Step
Block(s)
Description Step Instructions Complete
Data Type Boolean
Range OFF – When Step Instructions are Active or SCM/RCM is in IDLE. ON – When Step
Instructions are Complete or No Instructions are configured.
Default Off
Config Load No
Active No
Loadable

- 1443 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence CEE
Related INSMASTER, INSTRUCTPEND
Parameters
Remarks Provides a summary indication of whether the Step Instruction(s) have been
completed.

11.254 INSTRUCTNOTIFOPT

Specific to Block(s) SCM, RCM, MR


Description Instruction Notification Option
Data Type Enumeration
Default None
Config Load No
Active Loadable Yes
Access Lock AppDevOnly
Residence CEE
Related Parameters INSTRUCTYPE, GENERATEALERTS
Remarks

11.255 INSTRUCTPEND

Specific to SCM
Block(s)
Description SCM Instruction Pending
Data Type Boolean
Range Off - Instruction(s) are not pending On - Instruction(s) are pending
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTIVELOC.STEPICOMP[1..15], ACTIVELOC.STEPIPEND[1..15]
Parameters
Remarks Provides a summary indication of whether the SCM currently has an Active Step
with an Instruction pending that requires operator interaction.

- 1444 -
Chapter 11 - Ixxxx Parameters

11.256 INSTRUCTSEQ

Specific to Step
Block(s)
Description Step Instructions Enforce Sequential Order
Data Type Boolean
Range Off - Sequential Order not enforced On - Sequential Order is enforced
Default Off
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OP[1..16].INSTRUCTCNFM, OP[1..16].INSTRUCTPEND, OP[1..16].INSTRUCTCOMP
Parameters
Remarks Selects whether the confirmable Instructions of the Step must be confirmed in
order from Output #1, #2, ... up to Output #N. Step level confirmation is not
supported when INSTRUCTSEQ is On.

11.257 INSTS[1..8]

Specific to CheckBool Logic Block


Block(s)
Description Input Status
Data Type Enumeration
Range 0 - 6 (0) kBadValSts (1) kUncertainValSts (2) kNormalValSts (3) kManualValSts (4)
kInitAckValSts (5) kInitRegValStst (6) kInitBadValSts
Default kNormalValSts
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Provides the current status of the connected input.

- 1445 -
Chapter 11 - Ixxxx Parameters

11.258 INSTSELECT

Specific to SCM,RCM
Block(s)
Description Alias instance selection. Represents selected instance column.
Data Type 16-Bit Integer
Range 1 - NUMINSTANCES, if ALIASOPT = True 0, if ALIASOPT = False
Default 1
Config Load Yes
Active No
Loadable
Access Lock Engineer and Operator
Residence CEE
Related NUMINSTANCES, CONFIGCODE, CONFIGCODE, ALIASOPT
Parameters
Remarks Can be configured at configuration time, and modified at run-time. Since
ALIASOPT cannot be read within a CEE, the parameter INSTSELECT can be used
to determine if an alias table is present at the SCM or RCM.

11.259 INSTYPE[1..10]

Specific to DATAACQ, All Regulatory Control Blocks except PROSPROP, PULSECOUNT,


Block(s) PULSELENGHT, REGCALC
Description Insertion Type - Specifies type of insertion to be inserted from CAB instance.
Data Type Enumeration DACINSERT or REGINSERT
Range For DATAACQ Block (0) PV_Alg, (1) Post_PVchar, (2) Post_Clampfilt, (3)
Post_PVsrc, (4) Post_Alarmproc
For Regulatory Control Block (0) Post_input (1) Pre_Alg (2) Ctl_Alg (3) Post_Alg
(4) Post_Ctlout
Default
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related INSBLOCK[1..10]
Parameters
Remarks

- 1446 -
Chapter 11 - Ixxxx Parameters

11.260 INT32PARAM

Specific to Block(s) EIM


Description Data Attribute INT32
Data Type INT32
Range ±2147483647
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence NOLOAD
Related Parameters
Remarks

11.261 INT32VAL[0..80]

Specific to Block(s) EIM


Description Integer32 Value
Data Type Integer32 Value
Range ±2147483647
Default 0
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters NUMINT32
Remarks Accessed as an array. Mapped to custom INT32 parameters

11.262 INT64PARAM

Specific to Block(s) EIM


Description Data Attribute INT64
Data Type INT64
Range ±9223372036854775807
Default
Config Load
Active Loadable No

- 1447 -
Chapter 11 - Ixxxx Parameters

Access Lock AppDevOnly


Residence NOLOAD
Related Parameters
Remarks

11.263 INT64VAL[40]

Specific to Block(s) EIM


Description Integer64 Value
Data Type INT64
Range ±9223372036854775807
Default 0
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters NUMINT64
Remarks Accessed as an array. Mapped to custom INT64 parameters

11.264 INTEGRITY1[1..4]

Specific to JAGXCHAN
Block(s)
Description Data Integrity Bit 1
Data Type Boolean
Range Off(0) Integrity Not OK
On(1) Integrity OK
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 5 of the FPIndicator byte in the floating point input
assembly for the designated scale slot [1..4].

- 1448 -
Chapter 11 - Ixxxx Parameters

11.265 INTEGRITY2[1..4]

Specific to Block JAGXCHAN


(s)
Description Data Integrity Bit 2
Data Type Boolean
Range Off(0) Integrity Not OK
On(1) Integrity OK
Default 0
Config Load: No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 14 in the floating point input assembly for the
designated scale slot [1..4].

11.266 INTEGRITYPERIOD

Specific to EIM
Block(s)
Description Integrity Period
Data Type UINT32
Range 4294967295
Default 0
Config Load
Active No
Loadable
Access Lock AppDevOnly
Residence EIM
Related
Parameters
Remarks Indicates the period in milliseconds used for generating an integrity report. An
integrity report shall report the values of all members of the related data-set.

- 1449 -
Chapter 11 - Ixxxx Parameters

11.267 INTERLANFAILED

Specific to FTEB, C300, PGM, FIM4 , EHPM , EIM, UOC, TCMI


Block(s)
Description Inter-Local Area Network (LAN) Failed -
Data Type Boolean
Range 0 = Not Failed
1= Failed
Default Not Failed (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks Provides status indicator for Inter-LAN communications. If ON for all nodes, it
means that the crossover cable has failed. (FTE parameters, see C300 definition)

Specific to Block(s) UOC


Description InterLAN Comm Failed
Data Type BOOLEAN
Range N/A
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

11.268 INTERVALCOUNTER

Specific to Block(s) ProfitCtl


Description Interval counter
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No

- 1450 -
Chapter 11 - Ixxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters
Remarks

11.269 INTERVALS

Specific to Block(s) PROFITCTLIN


Description CV Blocking Interval
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

Specific to PROFCONOUT
Block(s)
Description MV blocking intervals
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config No
Load
Active No
Loadable
Access Lock VIEWONLY
Residence NOLOAD
Related MV.NOOFBLKS
Parameters
Remarks MV blocking intervals. In principle, the controller should consider a constraint on
each CV at each control interval in the future out to the correction horizon (where
steady state is achieved). In practice, however, this can result in too large a problem
to be solved efficiently. So, the controller places constraints only at selected
intervals. This is blocking

- 1451 -
Chapter 11 - Ixxxx Parameters

11.270 INTISWCMD

Specific to RM
Block(s)
Description Initiate Switch-over Command
Data Type Boolean
Range True (0) False (1)
Default True (0)
Config Load No
Active No
Loadable
Access Lock Operator Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

11.271 INITVAL_AO_S

Specific to UIO, AO04, AO08


Block(s)

Description Echo Back Value


Data Type FLOAT64
Range -6.9% to 106.9%
Default 0.0%
Config Load No
Active
Loadable

Access Lock ViewOnly


Residence IOM Block
Related OUTPUTVALUE_AO_S, OUTPUTFINAL_AO_S
Parameters

Remarks Indicates the value to which the primary point is to be initialized. This is the back
initialization value read from the IOM.

11.272 INITVAL_DO_S
Delete this text and replace it with your own content.

- 1452 -
Chapter 11 - Ixxxx Parameters

11.273 INVCOND[1..8]

Specific to SCM, RCM, CR


Block(s)
Description Invoke Condition Number
Data Type 32-Bit Integer
Range 0 to 10
Default 0
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related
Parameters
Remarks INVCOND[i] contains the number of the last condition to change when TYPE i
handler was invoked through the invoke transition. If handler i invokes through
command or step condition, INVCOND[i] = 0. If multiple conditions have changed
since the last evaluation of the Invoke Transition, the parameter value returns the
lowest index of those conditions which had changed. Note that this detection works
purely on edge detection regardless of the direction of the change (0->1 versus 1-
>0) and independent of the direction of the logic. Therefore if multiple conditions
have changed in the same execution cycle, the returned value may not always
match intuition especially if the invoke transition never returned to false between 2
consecutive handler invocations of the same handler type. This constraint should
be considered if making automatic responses dependent on this parameter. If the
invoke transition always returns to false after handler invocation and before next
handler invocation, the parameter value will match the intuitively expected value.
However, the constraint remains that the lowest index will be shown if multiple
conditions caused the invoke transition to become true in the same execution cycle.

11.274 INVFRMHNDLER[1..8]

Specific to SCM
Block(s)
Description Invoked From Handler Name
Data Type BlockId
Range N/A
Default Null String
Config No
Load
Active No
Loadable

- 1453 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence CEE
Related INVFRMHNDLRN[1..8], TYPE..
Parameters
Remarks INVFRMHNDLER[i] contains the name (for example, SCMName.HandlerName) of
the handler from which the TYPE i handler was last invoked. INVFRMHNDLER[1..8]
is a BlockId parameter and not supported in expressions. Its Integer-32 Partner
Parameter INVFRMHNDLRN[1..8] can be used in Transition Condition expressions
and Step Output expressions.

11.275 INVFRMHNDLRN[1..8]

Specific to SCM
Block(s)
Description Invoked From Handler Name
Data Type 32-Bit Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related INVFRMHNDLRN[1..8], TYPE.
Parameters
Remarks INVFRMHNDLER[i] contains the name (for example, SCMName.HandlerName) of
the handler from which the TYPE i handler was last invoked. INVFRMHNDLRN[1..8]
may be used in Transition Condition expressions and Step Output expressions,
whereas INVFRMHNDLER[1..8] (a BlockId parameter) is not supported in
expressions.

11.276 INVFRMHNDTYP[1..8]

Specific to Block SCM, RCM, Control Recipe


(s)
Description Invoked From Handler Type
Data Type 32-Bit Integer
Range 0 to 8
Default 0
Config Load No
Active Loadable No

- 1454 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence CEE
Related TYPE.
Parameters
Remarks INVFRMHNDTYP[i] contains the TYPE of handler from which the TYPE i
handler was last invoked.

11.277 INVFROMSTEP[1..8][1..15]

Specific to SCM
Block(s)
Description Invoked From Step Name
Data Type BlockId
Range N/A
Default Null String
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related INVFROMSTEPN[1..8][1..15], TYPE.
Parameters
Remarks INVFROMSTEP[i][j] contains the name (for example, SCMName.StepName) of the
step in thread j that was active at the time of the TYPE i handler's last invocation.
INVFROMSTEP[1..8] is a BlockId parameter and not supported in expressions. Its
Integer-32 Partner Parameter INVFROMSTEPN[1..8] can be used in Transition
Condition expressions and Step Output expressions.

11.278 INVFROMSTEPN[1..8][1..15]

Specific to SCM
Block(s)
Description Invoked From Step Name
Data Type 32-Bit Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable

- 1455 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence CEE
Related INVFROMSTEP[1..8][1..15], TYPE.
Parameters
Remarks INVFROMSTEP[i][j] contains the name (for example, SCMName.StepName) of the
step in thread j that was active at the time of the TYPE i handler's last invocation.
INVFRMHNDLRN[1..8] may be used in Transition Condition expressions and Step
Output expressions, whereas INVFRMHNDLER[1..8] (a BlockId parameter) is not
supported in expressions.

11.279 INVPVFL

Specific to Block(s) DIGACQ


Description Inverted State Flag
Data Type Boolean
Range OFF (0) ON (1)
Default ON
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PV, STATE0, STATE1 STATETEXT[0..1]
Remarks The INVPVFL reflects the negated value of PVFL

11.280 INVOKE[1..8]

Specific to Block(s) SCM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

- 1456 -
Chapter 11 - Ixxxx Parameters

11.281 INVOKT.HANDLE

Specific to Block(s) Handler


Description Invoke Transition Handle
Data Type 32-Bit Integer
Range 0 to 1023
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUM
Remarks Contains the number (NUM) of the handler's invoke transition.

11.282 INVOKT.NEXTCOMP

Specific to Block(s) Handler


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

11.283 INVOLTTHRESH

Specific to Block Pulse Input IOM


(s)
Description Input Voltage Threshold - Specifies level of input.
Data Type Enumeration
Range 2V 8V
Default 2V
Config Load Yes
Active Loadable No

- 1457 -
Chapter 11 - Ixxxx Parameters

Access Lock Application Developer


Residence CEE
Related
Parameters
Remarks This value determines whether the actual screw-terminal-input is “high
voltage” or “low voltage”.

11.284 INVPWRGOOD1

Specific to Block(s) RETENTIONTRIG


Description Invert Power Good 1
Data Type BOOLEAN
Range OFF, ON
Default OFF
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related PWRGOOD1
Parameters
Remarks If ON, the inverse of the PWRGOOD1 signal is interpreted to mean “Power
Good”.

11.285 INVPWRGOOD2

Specific to Block(s) RETENTIONTRIG


Description Invert Power Good 2
Data Type BOOLEAN
Range OFF, ON
Default OFF
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related PWRGOOD2
Parameters
Remarks If ON, the inverse of the PWRGOOD2 signal is interpreted to mean “Power
Good”.

- 1458 -
Chapter 11 - Ixxxx Parameters

11.286 INVREASON[1..8]

Specific to SCM, RCM, CR


Block(s)
Description Handler Invoke Reason
Data Type Enumeration CSCOEVENTREASON
Range Unknown (0) Command (1): caused by write to parameter COMMAND LocalCond
(2): Step's Interrupt or Stop Condition GlobalCond (3): Handler's Invoke Transition
EqmToRecProjection (4): caused by projection from SCM(s) or RCM(s) or CR(s)
controlled by phase block(s) CommandByPhase (5) : caused by command from
phase block in upper layer RCM or CR
Default Unknown (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks INVREASON[i] contains the reason that the TYPE[i] handler was last invoked.

11.287 INVTHREAD[1..8]

Specific to SCM
Block(s)
Description Invoke Thread Number
Data Type 32-Bit Integer
Range 0 to 10
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related INVREASON[1..8], TYPE.
Parameters
Remarks INVTHREAD[i] contains the thread number of the step whose local condition
caused the TYPE i handler to be invoked. INVTHREAD[i] = 0 if INVREASON[i] is not
equal to LocalCond.

- 1459 -
Chapter 11 - Ixxxx Parameters

11.288 INVTIME[1..8]

Specific to SCM
Block(s)
Description Invoke Time of Handler
Data Type 32-Bit Integer
Range 0 to 2147483647
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Provides the time that the handler of type i was last invoked. the time value is an
integer that can be compared to other handler invoke times; it has no correlation to
the time of day.

11.289 IOCBFMTAV

Specific to Block(s) TCMI

Description IOCB Format Error Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

- 1460 -
Chapter 11 - Ixxxx Parameters

11.290 IOLINKCOLOR

Specific to All PM I/O Modules and All Series C I/O Modules


Block(s)
Description I/O Link Cable Color
Data Type Enumeration
Range 0 Unknown
1 Gray
2 Violet
Default Gray
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The I/O Link cable color corresponds to the I/O Link number. Link 1 is always Gray
and Link 2 is always Violet. For Series C I/O, the color of the physical I/O Link
address jumper must match this parameter.

11.291 IOCCONN

Specific to PCDI_MASTER, IOM blocks, PIOMB


Block(s)
Decription Currently Assigned Channels
Data Type Enumeration
Range 0 INCONN
1 OUTCONN
2 PCONN
Default INCONN (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks List of the channel names currently assigned to the block. Each request block uses
one channel. Channel numbers are assigned through the request blocks. The
maximum number of channels is based on the device type.

- 1461 -
Chapter 11 - Ixxxx Parameters

11.292 IOCNUMBER

Specific to Block(s) All IO Channels, SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


Description This is an internal parameter for system use only.
Data Type
Range Range is zero based. This parameter's range was 1 based in previous
releases.
Default
Config Load
Active Loadable No
Access Lock
Residence
Related
Parameters
Remarks

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Channel Number
Data Type 32-Bit Integer
Range
Default -1
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

11.293 IOCONNEXTSTS

Specific to All the Armor Point, Armor Block Modules, PowerFlex Drives, E3, and E3+ devices.
Block(s)
Description IO Connection Extended Status — This parameter provides extended status
information related to the connection between the controller and the IO. If a
connection is not established, this parameter displays the reason for the
connection failure.
Data Type Enum
Range l 0 : Standby
l 1 : WrongModule
l 4096 : Faulted
l 4352 : Faulted_WaitingToConnect
l 4608 : Faulted_Connecting

- 1462 -
Chapter 11 - Ixxxx Parameters

l 4864 : Faulted_BadIpAddr
l 5120 : Faulted_SrvAllocFailed
l 5376 : Faulted_IOAllocFailed
l 5632 : Faulted_BadT2ODataPtr
l 5888 : Faulted_BadO2TDataPtr
l 6144 : Faulted_BadT2ORpi
l 6400 : Faulted_BadO2TRpi
l 6656 : Faulted_BadConfigPtr
l 8192 : Validating
l 12288 : Connecting
l 16384 : Running
l 20480 : ShuttingDown
l 24576 : Inhibited
l 28762 : Waiting
l 28928 : WaitingToConnect
l 29184 : WaitingToShutdown
l 32768 : Reconfiguring
Default 0 : Standby
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related IOCONNSTATUS
Parameters
Remarks

11.294 IOCONNSTATUS

Specific to All I/O Module Function Blocks


Block(s)
Description I/O Connection Status - Displays the status of the connection between the Hybrid
Controller and the I/O Module. If the connection could not be established, this will
display the reason for the connection failure.
Data Type Enumeration
Range (0) Bad Schedule (6) No Configuration
(1) Communications Error (7) No Keeper
(2) Configuration Error (8) No Schedule
(3) Connected (9) Not Connected
(4) Connection in Use (10) Wrong Module
(5) I/O Module Not Found

- 1463 -
Chapter 11 - Ixxxx Parameters

Default (9) Not Connected


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Configured No
on
DeviceNet
Remarks

Specific to All Armor Point, Armor Block Modules, Powerflex Drives, E3 and E3+ devices.
Block(s)
Description I/O Connection Status - Displays the status of the connection between the
controller and the I/O Module. If the connection could not be established, this will
display the reason for the connection failure.
Data Type Enumeration
Range (0) BadSchedule (6) NoConfig
(1) CommError (7) NoKeeper
(2) ConfigError (8) NoSchedule
(3) Connected (9) NotConnected
(4) ConninUse (10) WrongModule
(5) IomNotFound (255) : unknown
Default (9) Not Connected
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Configured No
on
DeviceNet
Remarks

- 1464 -
Chapter 11 - Ixxxx Parameters

11.295 IOCSTATE

Specific to Block(s) All IO Channels, SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


Description IOC State
Data Type Integer
Range
Default 0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description PCDI Channel State
Data Type Enumeration
Range 0 INACTIVE
1 OK
2 UNAVAIL
3 INITREQLATCH
4 NOSOURCE
5 BADSOURCE
Default INACTIVE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

11.296 IOCTYPE

Specific to Block All IO Channels except Pulse Input IOM, SIFLAGARRCH, SINUMARRCH,
(s) SITEXTARRCH.
Description Channel Type
Data Type Integer
Range N/A
Default Varies
Config Load

- 1465 -
Chapter 11 - Ixxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks

11.297 IOL1SOFTFAIL

Specific to Block(s) C300 and FIM4.


Description IOLink(1) Soft Fail Error - Indicates a soft failure on IOLINK1
Data Type Boolean
Range On, Off
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4
Related Parameters IOL2SOFTFAIL, SOFTFAIL
Remarks

11.298 IOL2SOFTFAIL

Specific to Block(s) C300 and FIM4.


Description IOLink(2) Soft Fail Error - Indicates a soft failure on IOLINK2
Data Type Boolean
Range On, Off
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4
Related Parameters IOL1SOFTFAIL, SOFTFAIL
Remarks

- 1466 -
Chapter 11 - Ixxxx Parameters

11.299 IOLCHNFAILA

Specific to Block C200 IOLINK, C300 IOLINK


(s)
Description I/O Link Channel A Fail. Shows that the associated I/O link's channel A has
failed.
Data Type Boolean
Range Off (0): I/O Link Channel A is okay. On (1): I/O Link Channel A has failed.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related 1.25 IOLCHNSTSA
Parameters
Remarks When this parameter is On, the corresponding IOLCHNSTSA parameter is in
its ERROR state.

11.300 IOLCHNFAILB

Specific to Block C200 IOLINK, C300 IOLINK


(s)
Description I/O Link Channel B Fail. Shows that the associated I/O link's channel B has
failed.
Data Type Boolean
Range Off (0): I/O Link Channel B is okay.
On (1): I/O Link Channel B has failed.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related IOLCHNSTSB
Parameters
Remarks When this parameter is On, the corresponding IOLCHNSTSB parameter is in
its ERROR state.

- 1467 -
Chapter 11 - Ixxxx Parameters

11.301 IOLCHNHISTA [1...10]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOLINK Channel A error history. Keeps error history of IOLINK Cable A for the
last 10 “one minute” periods.
Data Type 16-Bit Unsigned Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related IOL1SOFTFAIL
Parameters
Remarks

11.302 IOLCHNHISTB[1...10]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOLINK Channel B error history. Keeps error history of IOLINK Cable B for the
last 10 “one minute” periods.
Data Type 16-Bit Unsigned Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related IOLCHNSTSB
Parameters
Remarks

- 1468 -
Chapter 11 - Ixxxx Parameters

11.303 1.25 IOLCHNSTSA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description I/O Link Cable A Status. Shows the overall status of cable A based on the rate of
errors detected.
Data Type Enumeration
Range Unknown (0): No status.
Ok (1): Cable is good. No errors detected during last pass of Periodic Cable
Swap.
Warning (2): Cable is questionable. Some cable errors detected during last pass
of Periodic Cable Swap. However, the errors detected did not
exceed the PERSWAPTHRES parameter.
Error (3): Cable is bad. Either the cable errors detected during the last pass of
Periodic Cable Swap or the sum of errors detected for the last 10
passes of Periodic Cable Swap on this cable exceeds the
PERSWAPTHRES parameter.
Default Unknown (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related IOLCHNFAILA, PERSWAPTHRES.
Parameters
Remarks Note that this is the same as the IOLASTS parameter in a TPS system.

11.304 IOLCHNSTSB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description I/O Link Cable B Status. Shows the overall status of cable B based on the rate of
errors detected.
Data Type Enumeration
Range Unknown (0): No status.
Ok (1): Cable is good. No errors detected during last pass of Periodic Cable
Swap.
Warning (2): Cable is questionable. Some cable errors detected during last pass
of Periodic Cable Swap. However, the errors detected did not
exceed the PERSWAPTHRES parameter.
Error (3): Cable is bad. Either the cable errors detected during the last pass of
Periodic Cable Swap or the sum of errors detected for the last 10
passes of Periodic Cable Swap on this cable exceeds the
PERSWAPTHRES parameter.

- 1469 -
Chapter 11 - Ixxxx Parameters

Default Unknown (0)


Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related IOLCHNFAILB, PERSWAPTHRES.
Parameters
Remarks Note that this is the same as the IOLBSTS parameter in a TPS system.

11.305 IOLDAUGHSF

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description I/O Link Daughter Card Soft Failure. Shows whether or not a soft failure exists in
the associated IOLIM's daughter card.
Data Type Boolean
Range Off (0): No soft failures exist.
On (1): One or more soft failures exist.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related
Parameters
Remarks When this parameter is On, users should view the Server Alarm Summary display
for more information.

11.306 IOLFREE

Specific to Block C200 IOLINK, C300 IOLINK


(s)
Description I/O Link Bandwidth Free. Shows the percentage of I/O link bandwidth that is
available.
Data Type 32-Bit Real Number
Range 0.0 to 100.0
Default 100.0
Config Load No

- 1470 -
Chapter 11 - Ixxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related
Parameters
Remarks

11.307 IOLIFNUM

Specific to IOLINK, C300 IOLINK


Block(s)
Description Physical IOL I/F Number. The Physical IOLINK Interface number written to the
IOLIM/C300 block.
Data Type 16-Bit Unsigned Integer
Range 1, 2
Default 1
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence IOLINK, C300 IOLINK
Related LINKNUM
Parameters
Remarks IOLIFNUM for the C200 IOLIM block can only be 1 since the hardware only
supports one I/O Link. IOLIFNUM for the C300 block can be either 1 or 2
representing the physical IOLINK Interface for either IOLINK 1 or 2.

11.308 IOLINK1IOID

Specific to Block(s) C300


Description IOLINK1 Block IOID - Provides the corresponding IOLINK1 function block
name
Data Type BlockId
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No

- 1471 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence C300
Related IOLINK2IOID, CEEIOID
Parameters
Remarks

Specific to Block(s) CN100 and C300


Description BlockID
Data Type BlockID
Exposure Output
Config Load No
Access Lock ViewOnly
Residence CEE
Related Parameters None
Remarks

11.309 IOLINK2IOID

Specific to Block(s) C300


Description IOLINK2 Block IOID - Provides the corresponding IOLINK2 function block
name
Data Type BlockId
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300
Related IOLINK1IOID, CEEIOID
Parameters
Remarks

11.310 IOLIMSTATE

Specific to IOLIM, Secondary IOLIM.


Block(s)
Description IOLIM State. Shows the current state of the associated IOLIM.
Data Type Enumeration
Range UNKNOWN: The IOLIM state is unknown. TESTING, BOOTING, ALIVE,
LOADING, PROGRAMMING, PIREADY, FAILED.

- 1472 -
Chapter 11 - Ixxxx Parameters

NODB: The IOLIM does not have a valid database.


OK: The IOLIM is the current Primary and is functioning
properly.
FAILED: The IOLIM has failed.
BACKUP: The IOLIM is the current secondary.
Default UNKNOWN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks The Secondary IOLIM block's IOLIMSTATE can only be UNKNOWN or BACKUP.

11.311 IOLINK

Specific to Block(s) All PM I/O Modules and All Series C I/O Modules
Description Associated IOLINK
Data Type BlockId
Range Maximum of 64 characters
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters N/A
Remarks This is the name of the IOLINK block instance to which the IOM is assigned

11.312 IOLINKCONN

Specific to All PM I/O Modules and All Series C I/O Modules


Block(s)
Description Connects to IOLINK
Data Type Enumeration
Range 1 Blue Blue link
2 Gray Gray link
0 Unknown Link connection undefined

- 1473 -
Chapter 11 - Ixxxx Parameters

Default Blue link (1)


Config Yes
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related IOMNUM
Parameters
Remarks The C300's two IOLINKs are commonly referred to as the blue link and the gray link.
I/O modules can be assigned to either of these two links. This parameter helps the
user determine if the I/O module is assigned to the blue link or to the gray link. For
Series C I/O modules, the IOLINKCONN color must match the color of the IOLINK
address tile that is installed on the IOTA. Otherwise, the I/O module will not be able
to communicate with the Experion PKS system. For PM I/O modules on an IOLIM,
IOLINKCONN is always Blue (1).

11.313 IOLINKTYPE

Specific to Block(s) C200 IOLINK, C300 IOLINK


Description IOLINK EE Type. Allows you to select the I/O Family Type for the associated
IOLINK.
Data Type Enumeration
Range 0 NONE
1 PM_IO_TYPE
2 Series C_IO_TYPE
Default NONE
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence IOLINK
Related N/A
Parameters
Remarks Parameter is to NONE for IOLIM block

- 1474 -
Chapter 11 - Ixxxx Parameters

11.314 IOLINKTYPEENUMMASK

Specific to Block(s) C200 IOLINK, C300 IOLINK


Description IOLINKTYPE Enumeration Mask.
Data Type String
Range 0 NONE
1 PM_IO_TYPE
2 SERIES_C_IO_TYPE
Default NONE
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence IOLINK
Related Parameters
Remarks

11.315 IOLMAXERR

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description I/O Link Maximum Errors Exceeded. Shows the I/O link has exceeded the
maximum error limit.
Data Type Boolean
Range Off (0): Maximum errors not exceeded.
On (1): Maximum errors exceeded.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related TOTCHNERRA, TOTCHNERRB, TOTCHNSILA, TOTCHNSILB.
Parameters
Remarks When this parameter is On, the sum of the total communication errors and the
total silences for either or both I/O link channels exceeds 20000.

- 1475 -
Chapter 11 - Ixxxx Parameters

11.316 IOLOVRRUN

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOL Process Data Cycle Overruns. Indicates whether or not PV scanning from the
IOP or IOPs completed in the IOP scan rate timeframe.
Data Type Boolean
Range OFF (0) No Overruns
ON (1) IOL Process Data Cycle Overruns
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related
Parameters
Remarks An alarm is generated when IOLOVRUN is set to 1.

11.317 IOLSOFTFAIL

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOLINK Soft Failure.
Data Type BITSTRING
Range See IO Soft Failure list for detail
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200 IOLINK, C300 IOLINK
Related
Parameters
Remarks When IOLSOFTFAIL is set to 1, indicates that the UM51 detected a Soft failure.
An alarm is generated as a result.

- 1476 -
Chapter 11 - Ixxxx Parameters

11.318 IOMASAPH

Specific to FTEB
Block(s)
Description This specifies the ASA Path of Series A & H IOM's configured to this FTEB
Data Type String
Range NA
Default Unknown
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB
Active No
Connector
Related
Parameters
Remarks This will show the ASAPATHs of the IOM's configured. This will help the user to
know at which location the IOM is present.

11.319 IOMBTREV

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Boot Revision
Data Type STRING
Range
Default ControlEdge 900 Expansion Module
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence IOM Block
Related
Parameters
Remarks This is the IOM card Boot Code revision status in the form V.R.B, where V = Version
and R = Revision and B is Build ID.

- 1477 -
Chapter 11 - Ixxxx Parameters

11.320 IOMBTREV(UOC)

Specific to UIO
Block(s)
Description BootRevision
Data Type String
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence UIO
Related
Parameters
Remarks This is the IOM card Boot Code revision status in the form V.R.B, where V = Version
and R = Revision and B is Build ID.

11.321 IOMBTREVA

Specific to All Series C I/O Modules


Block(s)
Description IOM Boot Revision
Data Type String
Range 12 characters maximum
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks This is the IOM card Boot Code revision status in the form V.R.B, where V =
Version and R = Revision and B is Build ID.

- 1478 -
Chapter 11 - Ixxxx Parameters

11.322 IOMBTREVB

Specific to All Series C I/O Modules


Block(s)
Description IOM Boot Revision
Data Type String
Range 12 characters maximum
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks This is the IOM card Boot Code revision status in the form V.R.B, where V =
Version and R = Revision and B is Build ID.

11.323 IOMCARDA

Specific to All PM I/O Modules


Block(s)
Description I/O Module Card A. Defines the card or slot number of the I/O Module connected
to the Field Termination Assembly (FTA) connector A.
Data Type 16-Bit Unsigned Integer
Range 1 to 15
Default 1
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOLIM
Related N/A
Parameters
Remarks For an IOM type AO8, IOM A will be the preferred primary.

- 1479 -
Chapter 11 - Ixxxx Parameters

11.324 IOMCARDB

Specific to All PM I/O Modules


Block(s)
Description I/O Module Card B. Defines the card or slot number of the I/O Module connected
to the Field Termination Assembly (FTA) connector B.
Data Type 16-Bit Unsigned Integer
Range 1 to 15
Default 1
Config Load Yes, except for PM nonredundant I/O Modules
Active No
Loadable
Access Lock Application Developer
Residence IOLIM
Related N/A
Parameters
Remarks For an IOM type AO8, IOM A will be the preferred primary.

11.325 IOMCMD[1..40]

Specific to IOLINK
Block(s)
Description I/O Module Command. Lets users initiate selected commands for the associated
redundant I/O Processor (IOP) pair or single IOP, if nonredundant, where the index
of this array corresponds to the number of the IOP.
Data Type Enumeration
Range NONE (0): No command.
SELECT_CH_A (1): Selects Channel A.
SELECT_CH_B (2): Selects Channel B.
RESET_ERRORS (3): Reset I/O Link errors.
SWAP_PRIMARY (4): Swap primary and secondary.
Default NONE (0)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOP
Related
Parameters
Remarks If the PERSWAPENB parameter is On, the active receive channel toggles between A
and B once a minute. The SWAP_PRIMARY command is only allowed when the IOP
partners are synchronized, the Primary is connected to a Field Termination
Assembly (FTA), and the Secondary is connected to a FTA.

- 1480 -
Chapter 11 - Ixxxx Parameters

11.326 IOMCOMMAND

Specific to All Series C I/O Modules


Block(s)
Description Command
Data Type Enumeration
Range 0 None No Command.
3 Reset_ Instructs IOMA and IOMB to reset their error and silence
Errors counts.
1 Select_ Instructs IOMA and IOMB to use the “A” IOLINK cable for
Cable_A communication to the C300.
2 Select_ Instructs IOMA and IOMB to use the “B” IOLINK cable for
Cable_B communication to the C300
4 Swap_ Instructs the Secondary IOM to become the Primary IOM.
Primary However, this operation is only allowed when: {1} the
Secondary is synchronized and {2} if the Primary and
Secondary are both connected to the IOTA.
6 Disable_ Experion PKS will no longer try to synchronize this
Sync redundant IOM pair.
7 Enable_ On a periodic basis, Experion PKS will try to synchronize
Sync this redundant IOM pair.
8 Shutdown_ Ready the IOM A for firmware download
IOM_A
9 Restart_ Release the IOM A from firmware download ready
IOM_A
10 Shutdown_ Ready the IOM B for firmware download
IOM_B
11 Restart_ Release the IOM B from firmware download ready
IOM_B
5 --- Displayed only on the project side
Default NONE (0)
Config No
Load
Active No
Loadable
Access Lock Engineer for Shutdown_IOM_A, Shutdown_IOM_B, and Disable_Sync. Operator for
all other commands.
Residence IOLINK
Related
Parameters
Remarks

- 1481 -
Chapter 11 - Ixxxx Parameters

11.327 IOMCOMMAND[1..40]

Specific to C200 IOLINK, SIMIOLIM, C300 IOLINK


Block(s)
Description I/O Module Command. Allows you to initiate selected commands for the associated
redundant PMIO or Series C IOM pair or single IOM, if nonredundant. The index of
this array corresponds to the number of the IOM.
Data Type Enumeration
Range PMIO Modules

NONE (0): No command.


SELECT_CH_A (1): Selects Channel A.
SELECT_CH_B (2): Selects Channel B.
RESET_ERRORS (3): Reset I/O Link errors.
SWAP_PRIMARY (4): Swap primary and secondary.
Series C IO Modules

NONE (0): No command.


RESETERRORSCMD Reset I/O Link errors
SELECTCABLEACMD Selects Channel A
SELECTCABLEBCMD Selects Channel B
SWAPPRIMARYCMD Swap Primary and secondary.
DSBLSYNCCMD Disable Synchronization
ENBLSYNCCMD Enable Synchronization
SHUTDOWN Ready the IOM for firmware download
RESTART Release the IOM from firmware
download ready
Default NONE (0)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOLINK
Related
Parameters
Remarks If the PERSWAPENB parameter is On, the active receive channel toggles between A
and B once a minute. The SWAP_PRIMARY command is only allowed when the IOM
partners are synchronized. Also, redundant PMIO IOPs must be connected to Field
Termination Assemblies(FTAs). This parameter replaces the IOMCMD parameter.

- 1482 -
Chapter 11 - Ixxxx Parameters

11.328 IOMCONN

Specific to Block(s) All IO Channels, SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


Description IO Module Connector
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock Application Developer
Residence
Related Parameters
Remarks

11.329 IOMDESCA

Specific to All IOP Blocks


Block(s)
Description I/O Module Description Channel A. Shows descriptive text for the associated
channel A redundant I/O Processor (IOP) partner or single nonredundant IOP.
Data Type String
Range 8 characters maximum
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks

11.330 IOMDESCB

Specific to All IOP Blocks


Block(s)
Description I/O Module Description Channel B. Shows descriptive text for the associated
channel B redundant I/O Processor (IOP) partner.
Data Type String
Range 8 characters maximum

- 1483 -
Chapter 11 - Ixxxx Parameters

Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks

11.331 IOMEXECSTATE

Specific to Block(s) Controller Rack, IO RACK


Description IOM execution state
Data Type Enumeration
Range 0 Inactive

1 Active
Default INACTIVE (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Controller Rack, IO RACK
Related Parameters

Remarks Table column listing the state of all loaded IOMs.

Specific to Controller Rack, IO RACK, UIO, UAI, DI32-24VDC, DO32-24VDC, DO32-24VDC, DI16-VAC,
Block(s) DO08-VAC, DI16-DRYCT, DO08-RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description IOM execution state
Data Type Enumeration
Range 0 Inactive

1 Active
Default INACTIVE (0)
Config No
Load

Active No
Loadable

- 1484 -
Chapter 11 - Ixxxx Parameters

Access ViewOnly
Lock

Residence Controller Rack, IO Rack, IO modules


Related
Parameters

Remarks Table column listing the state of all loaded IOMs.

11.332 IOMFILEA

Specific to All IOM Blocks


Block(s)
Description I/O Module File A. Defines the file number of the I/O Module connected to the
Field Termination Assembly connector A.
Data Type 16-Bit Unsigned Integer
Range 1 to 8
Default 1
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOLIM/IOLINK
Related N/A
Parameters
Remarks For an IOM type AO8, IOM A will be the preferred primary.

11.333 IOMFILEB

Specific to All IOM Blocks


Block(s)
Description I/O Module File B. Defines the file number of the I/O Module connected to the
Field Termination Assembly connector B.
Data Type 16-Bit Unsigned Integer
Range 1 to 8
Default 1
Config Load Yes
Active No
Loadable

- 1485 -
Chapter 11 - Ixxxx Parameters

Access Lock Application Developer


Residence IOLIM/IOLINK
Related
Parameters
Remarks For an IOM type AO8, IOM A will be the preferred secondary.

11.334 IOMFWREV

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Firmware Revision
Data Type STRING
Range 12 characters maximum
Default NA.
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence IOM Block
Related
Parameters
Remarks This is the IOM card firmware revision status in the form X.Y, where X = Version and
Y = Revision.

11.335 IOMFWREVA

Specific to All PM I/O Modules and All Series C I/O Modules


Block(s)
Description I/O Module Firmware Revision Channel A. Shows the current firmware revision of
the associated channel A redundant I/O Module partner or single nonredundant
IOM.
Data Type String
Range 12 characters maximum
Default N/A
Config No
Load
Active No
Loadable

- 1486 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence IOM
Related N/A
Parameters
Remarks For PM I/O Modules, the IOM firmware revision is expressed in the form X.Y, where
X is the version and Y is the revision level. For Series C I/O Modules, the IOM
firmware revision is expressed in the form V.R.B. Where V = Version, R = Revision
and B = Build ID.

11.336 IOMFWREVB

Specific to All PM I/O Modules


Block(s)
Description I/O Module Firmware Revision Channel B. Shows the current firmware revision of
the associated channel B redundant I/O Module partner or single nonredundant
IOM.
Data Type String
Range 12 characters maximum
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks The IOM firmware revision is expressed in the form X.Y, where X is the version and
Y is the revision level.

11.337 IOMGRCLI

Specific to FTEB
Block(s)
Description This specifies the C300 block IP to which the FTEB IO manager is Connected.
Data Type String
Range NA
Default 0.0.0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly

- 1487 -
Chapter 11 - Ixxxx Parameters

Residence FTEB
Active No
Connector
Related IPADDRESS
Parameters
Remarks This will show the C300 IP address to which this FTEB IO manager is connected.
This will help the user to know that to which C300 this FTEB is connected

11.338 IOMGRMAPFREE

Specific to Block C200E


(s)
Description IOMGR Free Map Entries - Displays the number of IO units that can be loaded
to the C200E.
Data Type UINT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200E
Active Connector
Related
Parameters
Remarks This parameter value is always 0 when using SIM-C200E.

11.339 IOMGRMAPRUNNING

Specific to Block C200E


(s)
Description IOMGR Map Entries Connected - Displays the number of IO units loaded to
the C200E.
Data Type UINT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly

- 1488 -
Chapter 11 - Ixxxx Parameters

Residence C200E
Active Connector
Related
Parameters
Remarks This parameter value is always 0 when using SIM-C200E.

11.340 IOMGRMEMFREE

Specific to Block(s) C200E


Description IOMGR Buffer Free Memory - Displays the total amount of free memory.
Data Type UINT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence C200E
Active Connector
Related Parameters
Remarks This parameter value is always 0 when using SIM-C200E.

11.341 IOMGRMEMTOTAL

Specific to Block C200E


(s)
Description IOMGR Buffer Total Memory - Displays the total amount of memory used by
the loaded IO units.
Data Type UINT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence C200E
Active Connector
Related
Parameters
Remarks This parameter value is always 0 when using SIM-C200E.

- 1489 -
Chapter 11 - Ixxxx Parameters

11.342 IOMHWREV

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Hardware Revision
Data Type STRING
Range 12 characters maximum
Default N/A
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence IOM Block
Related
Parameters
Remarks This is the IOM card hardware revision status.

11.343 IOMHWREVA

Specific to All PM I/O Modules


Block(s)
Description I/O Module Hardware Revision Channel A. Shows the status of the hardware
revision for the associated channel A redundant I/O Module partner or single
nonredundant IOM.
Data Type String
Range 12 characters maximum
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks

- 1490 -
Chapter 11 - Ixxxx Parameters

11.344 IOMHWREVB

Specific to All PM I/O Modules


Block(s)
Description I/O Module Hardware Revision Channel B. Shows the status of the hardware
revision for the associated channel B redundant I/O Module partner.
Data Type String
Range 12 characters maximum
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks

- 1491 -
Chapter 11 - Ixxxx Parameters

11.345 IOMLHFSTA

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Last Hard Fail Status Channel A. Shows the last hard failure status
experienced by the associated channel A redundant I/O Module partner or single
nonredundant IOM.
Data Type Enumeration
Range 0 Unknown Unknown Status.
1 PowerDown This IOM Powered Down.
2 InvPrgExec Invalid Program Execution.

3 EpromErr EPROM Checksum Error.


4 RamCntErr RAM Contents Error.
5 RamAdrErr RAM Addressing Error.
6 DpaError Device Physical Address
Error.
7 DsaError Device Soft Address Error.
8 RxBufOvFl I/O Link Receive Buffer
Overflow.
9 IolJabber I/O Link Jabber Circuit
Failure.
11 BadPgJmp Illegal Value Case Control.
12 AdConvInmcp A-D Conversion
Incomplete.
13 AdOutOvfl A-D Output Value
Overflow.
14 AdOutUndef A-D Output is Undefined.
15 AdCalibErr A-D Calibration is
Incorrect.
16 BadLcLtc Bad DC LTC.
17 Dmt_Tmot Dead Man Timer Timeout.
18 MltOutFail Multiple Output Failures.
20 BadDaRange Bad D-A Range.
21 MstrTmot Master 68K Timeout.
22 Um51WDog Um51 Watchdog Timer
Timed Out
23 CntrCrtFail IOM Counter Circuit
Failure
24 SOECntFail SOE Counter Failure
25 OpCntrlHwFail Output Control HW Failure

26 BadIOMType Wrong Module Type


Default

- 1492 -
Chapter 11 - Ixxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence PCM
Related
Parameters
Remarks Refer to the Troubleshooting and Maintenance Guide for more information.

- 1493 -
Chapter 11 - Ixxxx Parameters

11.346 IOMLHFSTB

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Last Hard Fail Status Channel B. Shows the last hard failure status
experienced by the associated channel B redundant I/O Module partner or single
nonredundant IOM.
Data Type Enumeration
Range 0 Unknown Unknown Status.
1 PowerDown This IOM Powered Down.
2 InvPrgExec Invalid Program Execution.

3 EpromErr EPROM Checksum Error.


4 RamCntErr RAM Contents Error.
5 RamAdrErr RAM Addressing Error.
6 DpaError Device Physical Address
Error.
7 DsaError Device Soft Address Error.
8 RxBufOvFl I/O Link Receive Buffer
Overflow.
9 IolJabber I/O Link Jabber Circuit
Failure.
11 BadPgJmp Illegal Value Case Control.
12 AdConvInmcp A-D Conversion
Incomplete.
13 AdOutOvfl A-D Output Value
Overflow.
14 AdOutUndef A-D Output is Undefined.
15 AdCalibErr A-D Calibration is
Incorrect.
16 BadLcLtc Bad DC LTC.
17 Dmt_Tmot Dead Man Timer Timeout.
18 MltOutFail Multiple Output Failures.
20 BadDaRange Bad D-A Range.
21 MstrTmot Master 68K Timeout.
22 Um51WDog Um51 Watchdog Timer
Timed Out
23 CntrCrtFail IOM Counter Circuit
Failure
24 SOECntFail SOE Counter Failure
25 OpCntrlHwFail Output Control HW Failure

26 BadIOMType Wrong Module Type


Default

- 1494 -
Chapter 11 - Ixxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence PCM
Related
Parameters
Remarks Refer to the Troubleshooting and Maintenance Guide for more information.

11.347 IOMLOCATION

Specific to Block(s) Chassis HART AI IOM, HART AO IOM


Description IOM Location - Describes the location of the IOM.
Data Type String
Range Length: 32 characters
Default
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

11.348 IOMNAME

Specific to Block FTEB


(s)
Description This specifies the name of Series A & H IOM's configured to this FTEB
Data Type BlockId
Range NA
Default Unknown
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Active Connector No
Related
Parameters
Remarks This will show the names of the IOM's configured. This will help the user to
identify the IOM

- 1495 -
Chapter 11 - Ixxxx Parameters

Specific to Block(s) Controller Rack, IO RACK


Description IOM Block Name
Data Type STRING
Range NA
Default Unknown
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Controller Rack, IO RACK
Active Connector No
Related Parameters
Remarks Table column listing all loaded IOMs.

11.349 IOMNUM

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Number. Defines the logical address of the associated I/O Module on
the given I/O Link.
Data Type 16-Bit Unsigned Integer
Range 0 to 40
Default 0
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence IOLIM/C300
Related N/A
Parameters
Remarks For PM I/O, this parameter value must be unique on a specific I/O Link, and its
Range must be between 1 and 40. If IOMNUM=0 and the IOM block is assigned to
an I/O Link block, Control Builder automatically Defaults the IOMNUM to the next
available value on the I/O Link. For Series C I/O, this parameter value must be
unique on a specific I/O Link, and its user-entered value must be between 1 and
40. The value must also match the IOLINK address tile setting on the IOTA related
to this IOM. Note that the Default value of 0 is assigned when the IOM is created.
However, valid values for IOMs that communicate on the IOLINK are from 1 to 40.

- 1496 -
Chapter 11 - Ixxxx Parameters

11.350 IOMOPERA

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Operation Channel A. Shows whether the I/O Module is currently
operating as the primary or secondary in redundant IOP configurations.
Data Type Enumeration
Range 0 PRIMARY IOM is currently operating
as a Primary.
1 SECONDARY IOM is currently operating
as a Secondary.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks

11.351 IOMOPERB

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Operation Channel B. Shows whether the I/O Module is currently
operating as the primary or secondary in redundant IOM configurations.
Data Type Enumeration
Range 0 PRIMARY IOM is currently operating
as a Primary.
1 SECONDARY IOM is currently operating
as a Secondary.
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks This Parameter does not apply to nonredundant IOM configurations.

- 1497 -
Chapter 11 - Ixxxx Parameters

11.352 IOMPLREVA

Specific to Block HLAIHART and AO16HART (PM I/O); AI-HART, AO-HART (Series C I/O)
Description IOM card Programmable Logic Revision.
Data Type String
Range 12 Characters maximum
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related N/A
Parameters
Remarks This parameter is displayed between the IOM's hardware revision and
firmware revision.

11.353 IOMPLREVB

Specific to Block HLAIHART and AO16HART (PM I/O) ; AI-HART, AO-HART (Series C I/O)
Description IOM card Programmable Logic Revision.
Data Type String
Range 12 Characters maximum
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is displayed between the IOM's hardware revision and
firmware revision.

11.354 IOMSLOT

Specific to All IOM function blocks


Block(s)
Description IO Module Slot Number in Chassis
Data Type 32-Bit Integer
Range 0 to (chassis size - 1)
Default 0

- 1498 -
Chapter 11 - Ixxxx Parameters

Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence SR
Related DLCNBSLOT, ULCNBMAC.
Parameters
Remarks IOMSLOT refers to the physical chassis slot number of the IOM under
configuration. Note that the slot numbers start at zero, which is on the left side of
the rack. If configuring an IOM co-located in the same chassis as the controller, 0 is
not a valid slot for an IOM. This location is reserved for the CNI to the supervisory
network.

11.355 IOMSLOTNUMBER

Specific to Block(s) UOC


Description IOM Slot Number
Data Type 16-Bit Integer
Exposure Output

Range 0 to 12
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description IOM Slot Number
Data Type UINT16
Exposure Output

Range 1-12
Default 1
Config Load Yes
Active -
Loadable

- 1499 -
Chapter 11 - Ixxxx Parameters

Access Lock AppDevOnly


Residence IOM Block
Related
Parameters
Remarks Physical module slot position in the IO rack.

11.356 IOMSTATE

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Execution State. Defines the current execution state of the associated
I/O Module.
Data Type Enumeration
Range 1 IDLE
2 RUN
Default IDLE (1)
Config Load No
Active No
Loadable
Access Lock Operator for Idle to Run command Engineer for Run to Idle command
Residence IOM
Related N/A
Parameters
Remarks The IOM must be in its RUN state for I/O data to be used by a loaded control
strategy. We recommend that you activate the IOM block before activating its
associated I/O Channel (IOC) blocks.

Specific to All Series-A I/O and PIOMB


Block(s)
Description I/O Module Execution State. Defines the current execution state of the associated
I/O Module.
Data Type Enumeration
Range 0 INACTIVE
1 OK
2 FAIL
3 STBY
4 START
5 STUB
Default INACTIVE (0)
Config Load No
Active No
Loadable

- 1500 -
Chapter 11 - Ixxxx Parameters

Access Lock Operator for Idle to Run command Engineer for Run to Idle command
Residence CEE
Related
Parameters
Remarks The IOM must be in its RUN state for I/O data to be used by a loaded control
strategy. We recommend that you activate the IOM block before activating its
associated I/O Channel (IOC) blocks.

Specific to Block PCDI_MASTER


(s)
Description Module State - Defines the current execution state of the associated peer
device module.
Data Type Enumeration
Range 0 INACTIVE
1 OK
2 FAIL
3 STBY
4 START
5 STUB
Default INACTIVE (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Device
Related
Parameters
Remarks

- 1501 -
Chapter 11 - Ixxxx Parameters

11.357 IOMSTS[1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description I/O Module Status. Shows the status of the primary IOM The index of this array
corresponds to the number of the IOM.
Data Type Enumeration
Range ALIVE (0): IOM is ready for firmware download
IDLE (1): IOM is Idle state.
OK (2): IOM is in RUN.
NO_RESP (3): IOM is configured but not responding.
IDLE_SF (4): IOM is in IDLE state and has a Soft
Failure.
SOFT_FAIL (5): IOM is in RUN state and has a Soft
Failure.
COMM_ERR (6): Communication with IOM has errors.
CONFIG_MIS (7): Installed IOM is different than
configured IOM.
NO_CONFIG (8): IOM is not configured.
--- (9): IOM does not exist.
Default ALIVE
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks Note: PMIO blocks do not support the Alive status.

11.358 IOMSTSA

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Status Channel A. Shows the status of the specific physical I/O
Module.
Data Type Enumeration
Range 0 POWER_ON Transient state when power is
turned on.
1 IDLE In the Idle state.
2 OK Running.
3 NO_RESP No response.

- 1502 -
Chapter 11 - Ixxxx Parameters

4 IDLE_SF In the Idle state and has a Soft


Failure.
5 SOFT_FAIL In the Running state and has a
Soft Failure.
6 COMM_ERR Communication Error.
7 CONFIG_MIS Configuration Mismatch.
8 NO_CONFIG This IOP is Not Configured.
9 --- This IOP does not exist.
10 ALIVE IOM is ready for firmware
download.
11 FAILED IOM has failed.
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

11.359 IOMSTSB

Specific to All PM I/O Modules and Series C I/O Module


Block(s)
Description I/O Module Status Channel B. Shows the status of the specific physical I/O
Module.
Data Type Enumeration
Range 0 POWER_ON Transient state when power is
turned on.
1 IDLE In the Idle state.
2 OK Running.
3 NO_RESP No response.
4 IDLE_SF In the Idle state and has a Soft
Failure.
5 SOFT_FAIL In the Running state and has a
Soft Failure.
6 COMM_ERR Communication Error.
7 CONFIG_MIS Configuration Mismatch.
8 NO_CONFIG This IOP is Not Configured.
9 --- This IOP does not exist.
10 ALIVE IOM is ready for firmware
download.

- 1503 -
Chapter 11 - Ixxxx Parameters

11 FAILED IOM has failed.


Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related N/A
Parameters
Remarks Does not apply to non-redundant IOM configurations.

11.360 IOMSTS(UOC)

Specific to Block(s) Controller Rack, IO RACK


Description IOM Status
Range 0 Not_Config
1 Pending
2 Offline
3 Online
4 Configuring
5 Reading
6 Upgrading
7 Error

8 ---
Default Offline
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Controller Rack, IO RACK
Related Parameters N/A
Remarks Table column listing the status of all loaded IOMs.

11.361 IOMTYPE

Specific to All IOM function blocks and PIOMB


Block(s)
Description This non-configurable parameter is a Description of the respective IO module type.
Data Type String
Range Length: 64 characters
Default Defined appropriately on each I/O module type. See Note below.

- 1504 -
Chapter 11 - Ixxxx Parameters

Config Not configurable, but loaded to SR


Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks Note that there is a standard format for IOMTYPE descriptor strings: Module type,
number of channels, electrical characteristics, auxiliary descriptor. For example:
Analog Output, 6 ch, 4-20 mA, Isolated For PIOMB: “Profibus I/O Module Block”

Specific to Block(s) Controller Rack, IO RACK


Description IConfigured IOM Type
Data Type Enumeration
Range 0 ---

1 UIO
Default ---
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Controller Rack, IO RACK
Related Parameters N/A
Remarks Table column listing the module type of all loaded IOMs.

Specific to Block(s) UIO


Description Module Type
Data Type String
Range N/A
Default Universal I/O, 16 channels
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence UIO
Related Parameters SR
Remarks Static string displayed on the Main tab under the configuration group.

- 1505 -
Chapter 11 - Ixxxx Parameters

11.362 IOMTYPE(UOC)

Specific to Block(s) Controller Rack, IO RACK


Description Configured IOM Type
Data Type Enumeration
Range 0 ---
1 UIO
Default ---
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Controller Rack, IO RACK
Related Parameters N/A
Remarks Table column listing the module type of all loaded IOMs.

Specific to Block(s) UIO


Description Module Type
Data Type String
Range N/A
Default Universal I/O, 16 channels
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence UIO
Related Parameters SR
Remarks Static string displayed on the Main tab under the configuration group.

- 1506 -
Chapter 11 - Ixxxx Parameters

11.363 IOMTYPE[1..40]

- 1507 -
Chapter 11 - Ixxxx Parameters

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description I/O Module Type. Defines the configured Input/Output Module (IOM) type, where
the index of the array corresponds to the number of the IOM.
Data Type Enumeration

- 1508 -
Chapter 11 - Ixxxx Parameters

Range PMIO Module Type Description

- 1509 -
Chapter 11 - Ixxxx Parameters

--- (0): Not Configured

- 1510 -
Chapter 11 - Ixxxx Parameters

LLAI (1): Low-Level Analog Input

- 1511 -
Chapter 11 - Ixxxx Parameters

HLAI (2): High-Level Analog Input

- 1512 -
Chapter 11 - Ixxxx Parameters

DI (3): Digital Input/Digital Input 24V


DO (4): Digital Output
AO (5): Analog Output
LLMUX (7): Low Level Analog Multiplexer
STI-MV (14): Smart Transmitter Interface - Multivariable

DISOE (16): Digital Input Sequence of Events


AO16 (24): Analog Output 16
DO32 (25): Digital Output 32
RHMUX (28): Remote Hardened Multiplexer
HLAIHART (29): HART-capable High-Level Analog Input
with 16 channels and 100 ms sampling
DI24V (30) Digital Input 24V
AO16 HART (31) HART-capable Analog Output with 16
channels
Series C I/O Module Type Description

---- (0) Not Configured


AI_HART (51) High Level Analog Input, HART Capable, 16
channels
AI_HL (52) Not available
AI_LL (53) Not available
AI_MUX (54) Low Level Analog Input Mux, 64 channels
AI_PI (55) Not available
AI_ST (56) Not available
AO (57) Not available
AO_HART (58) Analog Output, HART Capable, 16 channels

DI_120 (59) High Voltage Digital Input, 32 channels


DI_24 (60) Low Voltage (24DC) Digital Input, 32
channels
DI_240 (61) High Voltage Digital Input, 32 channels
DI_SOE (62) Not available
DO_120 (63) Not available
DO_24 (64) Not available
DO_240 (65) Not available
DO_24B (66) Bussed Low Voltage Digital Output, 32
channels
PBI (67) Not available
AI_SIL (68) Not available
DI_SIL (69) Not available
DO_SIL (70) Not available

- 1513 -
Chapter 11 - Ixxxx Parameters

Default --- (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related N/A
Parameters
Remarks

11.364 IOMSTS

Specific to Block(s) Controller Rack, IO RACK


Description IOM Status
Data Type Enumeration
Range 0 Not_Config

1 Pending

2 Offline

3 Online

4 Configuring

5 Reading

6 Upgrading

7 Error

8 -
Default Offline
Config Load No
Active Loadable -
Access Lock ViewOnly
Residence Controller Rack, IO RACK
Related Parameters

Remarks Table column listing the status of all loaded IOMs

- 1514 -
Chapter 11 - Ixxxx Parameters

11.365 IOMTYPE

Specific to Block(s) Controller Rack, IO RACK


Description Configured IOM Type
Data Type Enumeration
Range 0 - -
1 UIO 900UO1-xxxx

3 UAI 900A01-xxxxx

4 DI16-VAC 900G03-xxxx

5 DI32-24VDC 900G32-0102

6 DO08-VAC 900H03-xxxx

7 DO32-24VDC 900H32-0102

8 PFQ04 900K01-xxxx

9 DO08-RELAY 900H01-0102

10 AO04 900B01-xxxx

11 AI16-100MS 900A16-0301

12 DI16-DRYCT 900G01-0102

13 AO08 900B08-xxxx

14 DI16-VACDC 900G04-xxxx
Default -
Config Load No
Active Loadable -
Access Lock ViewOnly
Residence Controller Rack, IO RACK
Related Parameters

Remarks Table column listing the module type of all loaded IOMs.

- 1515 -
Chapter 11 - Ixxxx Parameters

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Module Type
Data Type STRING

NA
Range UIO Universal I/O, 16 channels

UAI Universal AI Module, 8 Channels

DI32-24VDC DI - 24VDC-32Ch(sinking) -16Ch ISO

DO32-24VDC Digital Output 24 VDC, 32 Channels

DI16-VAC DI – 16ch AC

DO08-VAC Digital Output AC Voltage Type, 8


Channels

DI16-DRYCT DI – 16ch dry Contact Type

DO08-RELAY DO08-RELAY Digital Output Relays, 8


Channels

AO04 Analog Output, 4 Channels

AI16-100MS High Level Analog Input, 16 Channels

AO08 Analog Output, 8 Channels

DI16-VACDC DI - 120/240 VAC, 125 VDC (16ch-Iso)


Default N/A
Config Load No
Active -
Loadable

Access Lock ViewOnly


Residence SR
Related
Parameters

Remarks Static string displayed on the Main tab under the configuration group.

11.366 IOMFWREV(UOC)

Specific to Block UIO


(s)
Description Firmware Revision
Data Type String
Range 12 characters minimum
Default N/A
Config Load No
Active Loadable No

- 1516 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence UIO
Related N/A
Parameters
Remarks This is the IOM card firmware revision status in the form X.Y, where X = Version
and Y = Revision.

11.367 IOP

Specific to PM I/O Channel Blocks; Series C I/O Channel Blocks


Block(s)
Description Associated I/O Processor also known as I/O Module. The name of the IOP/IOM
block instance the IOC is assigned to.
Data Type BLOCK ID, (String)
Range N/A
Default Null
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related N/A
Parameters
Remarks

11.368 IOPBLOCKNAME [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOP Block Name. Indicates the corresponding configured IOP/IOM Tag Name. The
index of this array corresponds to the IOP/IOM Number.
Data Type BlockId
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

- 1517 -
Chapter 11 - Ixxxx Parameters

11.369 IOPDESCA

Specific to Block(s) PM I/O Channel Blocks; Series C I/O Channel Blocks


Description IOM Descriptor
Data Type String
Range 8 characters maximum.
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks This parameter is an 8-character string describing the IOM device.

11.370 IOPDESCB

Specific to Block(s) PM I/O Channel Blocks; Series C I/O Channel Blocks


Description IOM Descriptor
Data Type String
Range 8 characters maximum.
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks This parameter is an 8-character string describing the IOM device.

- 1518 -
Chapter 11 - Ixxxx Parameters

11.371 IOPHARTLHFSTA

Specific to Block(s) HLAIHART, AO16HART


Description HART Last Hard Fail Status
Data Type Enumeration
Range 0 ---
1 Watchdog timeout
2 Internal RAM diagnostic error
3 External RAM diagnostic error
4 Stack overflow error
5 RAM Address error
6 Startup diagnostic error
11 Invalid execution error 11
12 Invalid execution error 12
13 Invalid execution error 13
14 Invalid execution error 14
15 Invalid execution error 15
16 Invalid execution error 16
17 Invalid execution error 17
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks

- 1519 -
Chapter 11 - Ixxxx Parameters

11.372 IOPHARTLHFSTB

Specific to Block(s) HLAIHART, AO16HART


Description HART Last Hard Fail Status
Data Type Enumeration
Range 0 ---
1 Watchdog timeout
2 Internal RAM diagnostic error
3 External RAM diagnostic error
4 Stack overflow error
5 RAM Address error
6 Startup diagnostic error
11 Invalid execution error 11
12 Invalid execution error 12
13 Invalid execution error 13
14 Invalid execution error 14
15 Invalid execution error 15
16 Invalid execution error 16
17 Invalid execution error 17
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks

11.373 IOPLOADSTATE

Specific to Block(s) EIP Input Output Module AI or AO, it is not applicable for DI or DO

Description IO point status

Data Type ENUM

Range 0- UnLoaded
1 - Loading
2 - Loaded
3 - LoadError
Default Loaded

Config Load Yes

- 1520 -
Chapter 11 - Ixxxx Parameters

Active Loadable No

Access Lock AppDevOnly

Residence CEE

Related Parameters N/A

Remarks This parameter indicates the load state of IO point on IOM

11.374 IOPLOCATION

Specific to All PM I/O Modules and Series C I/O Modules, HLAI, STIMV, LLMUX, LLAI, RHMUX,
Block AO8, AO16, DO16, DO32, DI, DI24V, DISOE, AO16HART, HLAIHART, AI-HART, AI-
LLMUX, AI-LLAI, AO-HART, DI-HV, DI-24, DO-24B
Description IOM Location. A Description of the physical location (within the plant) where the
IOM can be found.
Data Type String
Range 64 Characters
Default Null
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer
Residence SR
Related N/A
Parameters
Remarks A user-entered parameter.

11.375 IOPORCUR[1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Overruns in the Current Hour
Data Type 16-bit Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks This parameter indicates the number of overruns that have occurred during the
current hour. The index of this array corresponds to the IOP/IOM number.

- 1521 -
Chapter 11 - Ixxxx Parameters

11.376 IOPORPREV[1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Overruns in the Previous Hour
Data Type 16-bit Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks This parameter indicates the number of overruns that have occurred during the
previous hour. The index of this array corresponds to the IOP/IOM number.

11.377 IOPTYPE

Specific to Block(s) PM I/O Channel Blocks; Series C I/O Channel Blocks


Description Associated I/O Processor Type also known as I/O Module Type.
Data Type Enumeration
Range Refer to IOPTYPE parameter of the IOP/IOM block
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks Enumerations between 1 and 50 are reserved for PM I/O IOPs/IOMs

- 1522 -
Chapter 11 - Ixxxx Parameters

Specific to All Series C I/O Modules


Block(s)
Description IOM Type
Data Type Enumeration
Range Value IOM Description

0 ---- None
51 AI_HART High Level Analog Input
with HART
52 AI_LLMUX Low Level Mux Input
53 AO_HART Analog Output with HART
54 DI_HV High Voltage Digital Input
55 DI_24 Low Voltage Digital Input
56 DO_24B Bussed Low Voltage Digital
Output
Default Varies with every IOM. Always matches the IOM block name.
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks Enumerations between 1 and 50 are reserved for PM I/O IOPs/IOMs This is the
configured IOM type that is compared with the actual IOM type.

11.378 IORACKNUMBER

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Associated Rack Number
Data Type UINT32
Exposure Output

Range 1-12
Default 1
Config Load Yes
Active
Loadable
Access Lock AppDevOnly
Residence IOM Block
Related
Parameters
Remarks The rack number the module resides in.

- 1523 -
Chapter 11 - Ixxxx Parameters

11.379 IORACKNUM(UOC)

Specific to Block(s) UIO


Description Associated Rack Number
Data Type UINT32
Range 1-12
Default 1
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters

Remarks The unique ID of the rack the module resides in.

11.380 IOREDOPT

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Redundant Option. Defines whether or not this I/O Module as part of a
redundant pair.
Data Type Boolean
Range 0 Off The IOM is not redundant.

1 On The IOM is redundant


Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOLIM
Related N/A
Parameters
Remarks If IOREDOPT parameter is On, user must configure the I/O Link physical address
for the redundant IOP B partner.

- 1524 -
Chapter 11 - Ixxxx Parameters

11.381 IOSCHEDOPT

Specific to Block(s) CM, IOM, PCDI_MASTER, and PIOMB


Description This is an internal parameter for system use only.
Data Type Enumeration
Range 1. NotIOMk
2. OutputModule
3. MixedModule
4. InputModule
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks In PGM, this parameter obtains its value through the PDC-PIOMB
association.

11.382 IOSSTALLTIME

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Token Pass Stall Time. Defines the period of time (currently 200us / 10ms worst
case) that is allocated to handle critical activities other than I/O link traffic.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks Token Stall time is time allotted to the UM51 and other I/O link (IOL) residents to
perform duties other than I/O link traffic. IOL-resident IOPs/IOMs and the UM51
can become so busy handling IOL traffic during high IOL load situations that other
critical activities may be disregard.

- 1525 -
Chapter 11 - Ixxxx Parameters

11.383 IOSTKNDROP

Specific to IOLINK
Block(s)
Description Input/Output Processor (IOP) Token Drop Count. Shows the number of token
pass drops on the I/O link.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks

11.384 IOTANETTYPE

Specific to Block(s) CN100


Description Selected network type/protocol
Data Type ENUM
Exposure Output
Range FTE, Ring-HSR, Star-PRP, Ring-DLR
Default FTE
Config Load Yes
Access Lock ViewOnly
Residence CEE
Related Parameters NETBCDSW
Remarks Network type/protocol in use

- 1526 -
Chapter 11 - Ixxxx Parameters

11.385 IOTATYPE

Specific to Block Series CSeries C Digital Input Modules and Series C DICHANNELS
(s)
Description Input/Output Termination Assembly Type
Data Type Enumeration
Range Value IOTA Description

0 24V 24 Volt Digital Input IOTA,


nonRedundant
1 24V_Rdn 24 Volt Digital Input IOTA, Redundant
2 120V 120 Volt Digital Input IOTA,
nonRedundant
3 120V_Rdn 120 Volt Digital Input IOTA,
Redundant
4 240V 240 Volt Digital Input IOTA,
nonRedundant
5 240V_Rdn 240 Volt Digital Input IOTA,
Redundant
6 --- Unknown
Default ---
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks The IOTATYPE parameter is read from the IOTA.

Specific to Block Series CSeries C Digital Output Modules and Series C DOCHANNELS
(s)
Description IOTA Type
Data Type Enumeration
Range Value IOTA Description

0 24V 24 Volt Digital Output IOTA,


nonRedundant
1 24V_Rdn 24 Volt Digital Output IOTA, Redundant
2 HV High Voltage Digital Output IOTA,
nonRedundant
3 HV_Rdn High Voltage Digital Output IOTA,
Redundant
6 --- Unknown
Default ---
Config Load No
Active Loadable No

- 1527 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence IOM
Related N/A
Parameters
Remarks The IOTATYPE parameter is read from the IOTA.

11.386 IOTATOPOLOGY

Specific to Block(s) CN100


Description Type of IOTA
Data Type ENUM
Exposure Output
Range STAR, RING
Default STAR
Config Load Yes
Access Lock ViewOnly
Residence CEE
Related Parameters NETBCDSW
Remarks Type of CN100 IOTA

11.387 IPADDRESS

Specific to Block(s) CPM, RM, PGM, FTEB, FIM4, EHG, C300, EHPM, TCMI
Description Ethernet IP Address
Data Type String
Range Length: 15 characters
Default Null String
Config Load No
Active Loadable No
Access Lock Engineer
Residence SR
Related DEVICEIDX
Parameters
Remarks IP Address assigned to Module based upon base IP address and module
device index

Specific to Block(s) EIM


Description Ethernet IP Address
Data Type String
Range NA

- 1528 -
Chapter 11 - Ixxxx Parameters

Default 0.0.0.0
Config Load
Active Loadable No
Access Lock APPDEVONLY
Residence SR
Related Parameters DEVICEIDX
Remarks FTE IP address, calculated from FTE base IP address and FTE device index.

Specific to All ArmorPoint modules, ArmorBlock modules, PowerFlex Drive, E3, and E3 plus
Block(s) Devices
Description IP address of the device— It provides the details of the EtherNet/IP device in use.
Data Type String
Range 15-Characters

Default 0.0.0.0
Config Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks For Armor Point modules ( that are assigned under the Adapter), this parameter
identifies the IP Address of the Armor Point Adapter (1738-AENT). For Armor Block
IO, PowerFlex drives and E3 devices, this parameter holds the IP address of the
device itself.

Specific to CONTROLLOGIXMODULE
Block(s)
Description IP address of the device— This parameter represents the IPAddress of the ENET
module through which the communication to the PLC from C300 is achieved.
Data Type String
Range 15-Characters

Default 0.0.0.0
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks

- 1529 -
Chapter 11 - Ixxxx Parameters

Specific to Block(s) 850M


Description Device IP Address
Data Type STRING
Range N/A
Default 0.0.0.0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

Specific to UOC
Block(s)
Description Ethernet IP Address
Data Type STRING
Range N/A
Default 0.0.0.0
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SR
Related
Parameters
Remarks FTE IP address. Note that the FTE IP address is automatically calculated, based
on the FTE device index.

11.388 IPEERAVGLPS [1...IPEERCONNMAX]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Average IMR/Sec
Data Type Float64
Range Greater than or equal to 0.0
Default 0.00
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related IPEERMAXLPS
Parameters
Remarks

- 1530 -
Chapter 11 - Ixxxx Parameters

11.389 IPEERAVGPPS [1...IPEERCONNMAX]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Average Parameters/Sec
Data Type Float64
Range Greater than or equal to 0.0
Default 0.00
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related IPEERMAXPPS
Parameters
Remarks

11.390 IPEERCONN

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Current Peer Connections
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related N/A
Parameters
Remarks

- 1531 -
Chapter 11 - Ixxxx Parameters

11.391 IPEERCONNERRCODE [1...N]

Specific to Block(s) CEEC300, CEE, IOLIM, FIM, CEEUOC, CEECN100


Description Connection Error Code
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related Parameters
Remarks

11.392 IPEERCONNERRINFO [1...N]

Specific to CEEC300, CEE, IOLIM, FIM, CEEUOC, CEECN100


Block(s)
Description Extended Error Info
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100(CEECN100)
Related
Parameters
Remarks Peer Initiator Connection Extended Error Information - Indicates the ICP/ASA
extended error information returned on an open connection attempt.

11.393 IPEERCONNMAX

Specific to CEEC300, CEE, IOLIM, FIM, IOLINKC300, CEEUOC


Block(s)
Description Maximum Initiator Connections.
Data Type 32-Bit Integer
Range Greater than or equal to 0

- 1532 -
Chapter 11 - Ixxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC)
Related Initiator Peer Connections Maximum - The maximum number of peer
Parameters connections supported in this version of firmware
Remarks

11.394 IPEERCONNSTS [1...N]

Specific to Block(s) CEEC300, CEE, IOLIM, FIM, CEEUOC, CEECN100


Description Connection Status
Data Type Enumeration
Range NoState (0) Initialized (1) OpenPending (2) Open (3) ClosePending (4)
Default No State (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100(CEECN100)
Related
Parameters
Remarks Peer Initiator Connection Status - Indicates the current ICOA connection
status

11.395 IPEERMAXLPS [1...IPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Initiator Peer Maximum IMRs Per Second - The maximum number of peer
messages per second received on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0.00
Config Load No
Active No
Loadable

- 1533 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Initiator Peer Maximum IMRs Per Second - The maximum number of peer
messages per second received on the wire.

11.396 IPEERMAXPPS [1...IPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Average Parameters/Sec.
Data Type Float64
Range Greater than or equal to 0
Default 0.00
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related IPEERAVGPPS
Parameters
Remarks Initiator Peer Maximum Parameters Per Second - The maximum number of peer
parameters per second received on the wire

11.397 IPEERNAME [1...IPEERCONNMAX]

Specific to Block CEE, CEEC300, ICG, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100
(s)
Description Target Name
Data Type BLOCKID
Range
Default Null
Config Load No
Active Loadable No

- 1534 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Initiator Peer Name - The name of the target CPM, ACE, FIM or IOLIM block

11.398 IPEERNAMELOOKUP

Specific to CEE
Block(s)
Description Displays the ClusterID, EEC, and IOC of the target name.
Data Type String
Range 20 characters
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related IPEERNAME [1...IPEERCONNMAX]
Parameters
Remarks It is a parameter which is used in custom graphic to display the Cluster ID, EEC,
and IOC of the target name in the following format: ClusterID, EEC, IOC.

11.399 IPEERPATH [1...IPEERCONNMAX]

Specific to Block(s) CEEC300, CEE, IOLIM, FIM, CEEUOC, CEECN100


Description Target Path.
Data Type String
Range Length : 32 Characters
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100(CEECN100)
Related Initiator Peer Path - The peer initiator's Automation System Architecture
Parameters (ASA) path
Remarks

- 1535 -
Chapter 11 - Ixxxx Parameters

11.400 IPFRAGCREATES

Specific to FTEB, C300, FIM4 EHPM , PGM


Block(s)
Description Internet Protocol (IP) Fragments Created - Identifies the number of IP datagram
fragments that have been generated as a result of fragmentation at this entity.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks The number of IP datagram fragments that have been generated as a result of
fragmentation at this entity

11.401 IPFRAGFAILS

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description Internet Protocol (IP) Fragmented Failures - Identifies the number of IP datagrams
that have been discarded because they needed to be fragmented at this entity but
could not be. For example, they could not be fragmented because their Don't
Fragment flag was set.
Data Type 32-Bit Integer
Range
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks The number of IP datagrams that have been discarded because they needed to be
fragmented at this entity but could not be.

- 1536 -
Chapter 11 - Ixxxx Parameters

11.402 IPFRAGOKS

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description Internet Protocol (IP) Fragmented Okays - Identifies the number of IP datagrams
that have been successfully fragmented at this entity.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks The number of IP datagrams that have been successfully fragmented at this entity.

11.403 IPINADDRERRORS

Specific to FTEB, C300, PGM, FIM4 , EHPM , EIM, UOC, TCMI


Block(s)
Description Datagrams Misdelivery Drops
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM , NOLOAD
Related
Parameters
Remarks Identifies the number of input datagrams discarded because the IP address in their
IP header's destination field was not a valid address to be received at this entity.
This count includes invalid addresses, such as 0.0.0.0, and addresses of
unsupported Classes, such as Class E. For entities which are not IP Gateways and
therefore do not forward datagrams, this counter includes datagrams discarded
because the destination address was not a local address. (IP statistics, see C300
definition)

- 1537 -
Chapter 11 - Ixxxx Parameters

11.404 IPINDELIVERS

Specific to FTEB, C300, PGM, FIM4, EHPM , EIM, UOC, TCMI


Block(s)
Description Datagrams Delivered Above
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM , NOLOAD
Related
Parameters
Remarks Identifies the total number of input datagrams successfully delivered to IP user-
protocols, including Internet Control Message Protocol (ICMP). (IP statistics, see
C300 definition)

11.405 IPINDISCARDS

Specific to FTEB, C300, PGM, FIM4, EHPM , EIM, UOC, TCMI


Block(s)
Description Datagrams Discarded for Resrcs
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM , NOLOAD
Related
Parameters
Remarks Identifies the number of input IP datagrams for which no problems were
encountered to prevent their continued processing, but which were discarded for
another reason. For example, discarded for lack of buffer space. Note that this
counter does not include any datagrams discarded while awaiting re-assembly. (IP
statistics, see C300 definition)

- 1538 -
Chapter 11 - Ixxxx Parameters

11.406 IPINHDRERRORS

Specific to FTEB, C300, FIM4, EHPM , EIM, UOC, TCMI


Block(s)
Description Datagrams Format Errors Drops
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, EHPM , NOLOAD
Related
Parameters
Remarks Identifies the number of input datagrams discarded due to errors in their IP
headers, including bad checksums, version number mismatch, other format errors,
time-to-live exceeded, errors discovered in processing their IP options, and so on.
(IP statistics, see C300 definition)

11.407 IPINRECEIVES

Specific to FTEB, C300, PGM, FIM4, EHPM , EIM, UOC, TCMI


Block(s)
Description Datagrams Received from Below
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM , NOLOAD
Related
Parameters
Remarks Identifies The total number of input datagrams received from connected nodes,
including those received in error. (IP statistics, see C300 definition)

- 1539 -
Chapter 11 - Ixxxx Parameters

11.408 IPINUNKNOWNPORTS

Specific to FTEB, C300, PGM, FIM4, EHPM , EIM, UOC, TCMI


Block(s)
Description Unknown Protocol Datagrams
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM ,NOLOAD
Related
Parameters
Remarks Identifies the number of locally-addressed datagrams received successfully but
discarded because of an unknown or unsupported protocol. (IP statistics, see C300
definition)

11.409 IPOUTDISCARDS

Specific to FTEB, C300, PGM, FIM4 , EHPM , EIM, UOC, TCMI


Block(s)
Description Out Datagrams Discarded
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM , NOLOAD
Related
Parameters
Remarks Identifies the number of output IP datagrams for which no problem was
encountered to prevent their transmission to their destination, but which were
discarded for another reason. For example, discarded for lack of buffer space. Note
that this counter would include datagrams counted in IP forwarded datagrams, if
any such packets met this (discretionary) discard criterion. (IP statistics, see C300
definition)

- 1540 -
Chapter 11 - Ixxxx Parameters

11.410 IPOUTNOROUTES

Specific to FTEB, C300, PGM, FIM4, EHPM EIM, UOC, TCMI


Block(s)
Description Datagrams Drops for No Routes
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM NOLOAD
Related
Parameters
Remarks Identifies The number of IP datagrams discarded because no route could be found
to transmit them to their destination. Note that this counter includes any packets
counted in IP forwarded datagrams which meet this ‘no-route’ criterion. It also
includes any datagrams which a host cannot route because all of its default
gateways are down. (IP statistics, see C300 definition)

11.411 IPOUTREQUESTS

Specific to FTEB, C300, PGM, FIM4, EHPM , EIM, UOC, TCMI


Block(s)
Description Datagrams Sent Out
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM , NOLOAD
Related
Parameters
Remarks Identifies the total number of IP datagrams which local IP user-protocols, including
Internet Control Message Protocol (ICMP), supplied to IP in requests for
transmission. Note that this counter does not include any datagrams counted in
the IP forwarded datagrams. (IP statistics, see C300 definition)

- 1541 -
Chapter 11 - Ixxxx Parameters

11.412 IPREASSMFAILS

Specific to Block(s) UOC, TCMI


Description Fragments Reassembly Fails
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (IP statistics, see C300 definition)

11.413 IPREASSEMFAILS

Specific to FTEB, C300, PGM, FIM4, EHPM, EIM


Block(s)
Description Internet Protocol (IP) Re-assembly Failures - Identifies the number of failures
detected by the IP re-assembly algorithm for any reason, such as timed out, errors,
and so on.
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, NOLOAD
Related IPREASSEMOKS, IPREASSEMREQS
Parameters
Remarks Note that this is not necessarily a count of discarded IP fragments, since some
algorithms can lose track of the number of fragments by combining them as they
are received.

- 1542 -
Chapter 11 - Ixxxx Parameters

11.414 IPREASSEMOKS

Specific to FTEB, C300, PGM, FIM4 , EHPM, EIM, TCMI


Block(s)
Description Internet Protocol (IP) Re-assembly Okays - Identifies The number of IP
datagrams successfully re-assembled.
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM, VIEWONLY
Related
Parameters
Remarks

Specific to Block(s) UOC


Description Fragments Reassembled
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (IP statistics, see C300 definition)

11.415 IPREASSEMREQS

Specific to FTEB, C300, PGM, FIM4, EHPM, EIM, TCMI


Block(s)
Description Internet Protocol Reassembly Requirements - Identifies the number of IP
fragments received which needed to be reassembled at this entity.
Data Type 32-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable

- 1543 -
Chapter 11 - Ixxxx Parameters

Access Lock ViewOnly


Residence FTEB, C300, FIM4, PGM, EHPM NOLOAD
Related
Parameters
Remarks

Specific to Block(s) UOC


Description Fragments Needing Reassembly
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (IP statistics, see C300 definition)

11.416 IPREASSEMTIMEOUT

Specific to Block(s) FTEB, C300, PGM, FIM4, EHPM


Description Retransmission Queue Timeout
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related Parameters
Remarks

11.417 IPROUTINGDISCARDS

Specific to FTEB, C300, PGM and FIM4, EHPM


Block(s)
Description Internet Protocol (IP) Routing Discards - Identifies The number of routing entries
which were chosen to be discarded even though they are valid.
Data Type 32-Bit Integer
Range

- 1544 -
Chapter 11 - Ixxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks One possible reason for discarding such an entry could be to free-up buffer space
for other routing entries.

11.418 ISBIGENDIAN

Specific to Block C300


Description Endianness of C300 platforms
Data Type Boolean
Range True, False
Default True
Config Load No
Active Loadable No
Access Lock Read Only
Residence CEE
Related Parameters
Remarks Used by tools (all C300 platforms are treated as big-endian).

11.419 ISROCKWELLIO

Specific to Block TC-HAIO081, TC-HAO081


Description Is Rockwell IO
Data Type Boolean
Range OFF, ON
Default OFF
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence
Related Parameters

This must be set to ON if the configured I/O module is a Rockwell I/O


Remarks module.

- 1545 -
Chapter 11 - Ixxxx Parameters

11.420 ISSUEDATE

Specific to Block(s) RCM


Description Issue Date
Data Type Time
Range
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

11.421 ISVIRTUALPLATFORM

Specific to Block(s) ELCN_NODE

Description Selects whether this node is running on a UEA platform or a virtual platform

Data Type Boolean

Range True (Virtual) or False (UEA)

Default F

Config Load Yes

Active Loadable No

Access Lock AppDevOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related Parameters ELCN_NODEMaintab

Remarks

11.422 ITEMCNT

Specific to Block Alarm Groups


(s)
Description Alarm Group Item count - The number of assets or data points associated with
the alarm group.
Data Type Int32
Range 1 - 500
Default 1

- 1546 -
Chapter 11 - Ixxxx Parameters

Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SCAN
Related ITEMS
Parameters
Remarks

11.423 ITEMNAME

Specific to All Tagged Blocks


Block(s)
Description Item name - A non-unique name by which an entity is known within the context of
the enterprise model.
Data Type String
Range Limit: 40 characters
Default For system names - SYSTEM_xxx For assets - ASSET_xxx For alarm groups -
ALARMGROUP_xxx Where xxx = an auto-generated Id number.
Config No
Load
Active No
Loadable
Access Lock Application Developer Only
Residence SCAN
Related
Parameters
Remarks Name must not conflict with any top-level system names, and should conform to
the standard convention for names within the system. The Item name must be
unique among children of the same containment parent in the Enterprise Model
Builder hierarchy The following restrictions apply:
l The following characters are restricted and may not be used: “.,/\\<>'\“*?|:;[]{}
()\”
l Dots are allowed in parameter naming only.
l An embedded space or leading space is not allowed.
l Spaces are allowed in area naming only.
l Tabs may not be used.
l The name may not be null (no characters).
lOne of these characters must be present in a valid name:
ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz
Note that this is not an actual parameter and it does not appear in parameter point
selection lists.

- 1547 -
Chapter 11 - Ixxxx Parameters

11.424 ITEMS

Specific to Alarm Group


Block(s)
Description Group Items - The Tag Name or Full Item Name of the assets and/or points that
are part of the alarm group.
Data Type String
Range
Default 1
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence SCAN
Related ITEMCNT
Parameters
Remarks

- 1548 -
CHAPTER

12 JXXXX PARAMETERS

12.1 JAGBASIC1[1..4] 1549


12.2 JAGBASIC2[1..4] 1550
12.3 JOURNALONLY 1550
12.4 JUMPGROUP 1551
12.5 JUMPGROUPNAME 1551
12.6 JUMPGROUPNUM 1552
12.7 JUMPPATHNUM 1552

12.8 JUMPSAFEENB 1553


12.9 JUMPTARGETNUM 1554
12.10 JUMPZONE 1554
12.11 JUMPZONEENB 1555
12.12 JUMPZONENAME 1555
12.13 JUMPZONENUM 1556

12.1 JAGBASIC1[1..4]

Specific to JAGXCHAN
Block(s)
Description JagBasic Custom Bit 1
Data Type Boolean
Range Off(0) Off
On(1) On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 6 of the status word in the floating point input assembly
for the designated scale slot [1..4].

- 1549 -
Chapter 12 - Jxxxx Parameters

12.2 JAGBASIC2[1..4]

Specific to JAGXCHAN
Block(s)
Description JagBasic Custom Bit 2
Data Type Boolean
Range Off(0) Off
On(1) On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 7 of the status word in the floating point input assembly for
the designated scale slot [1..4].

12.3 JOURNALONLY

Specific to Block(s) All Tagged Blocks


Description Alarming JOURNAL ONLY
Data Type Boolean
Range Off (0)
On (1)
Default Off
Config Load Yes
Active Loadable No
Access Lock Operator
Residence Respective Device, Controller or Platform
Related Parameters
Remarks When Set On, all alarms are reported to Journal Only

Specific to PM I/O HART Channels, Series C I/O HART Channels


Block(s)
Description Journal Only option
Data Type Boolean
Range 0 Off HART alarms are reported to Alarm
Summary and Event Summary Journal
in Station
1 On HART alarms and events are reported to
Event Summary Journal only in Station

- 1550 -
Chapter 12 - Jxxxx Parameters

Default Off
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related HENABLEALMENBSTATE
Parameters
Remarks The HENABLE parameter must be On to access this parameter. The
ALMENBSTATE parameter must be On for HART alarm journaling.

12.4 JUMPGROUP

Specific to Handler
Block(s)
Description Used to specify which Phases or Steps belong to which jump group. By default,
there are no jump groups defined. This parameter must be set by the engineer at
configuration time only.
Data Type BLOCKID
Range 0-9999
Default 0
Active No
Loadable
Access Lock Application Developer
Residence CEE
Pin None
Exposure
Related JUMPGROUPNUM, JUMPTARGETNUM, JUMPSAFEENB
Parameters
Checkpoint No

12.5 JUMPGROUPNAME

Specific to Handler
Block(s)
Description Parameter value specifies the name to be used for the Jump Zone when presented
to the user for selection in the enhanced GoTo dialog. This parameter must be set
by the engineer at configuration time only.
Data Type STRING
Range 50 characters
Default 0
Active No
Loadable

- 1551 -
Chapter 12 - Jxxxx Parameters

Access Lock Application Developer


Residence SR
Pin None
Exposure
Related JUMPSAFEENB
Parameters
Checkpoint No

12.6 JUMPGROUPNUM

Specific to Block Handler


(s)
Description Parameter value specifies the number of jump zones defined for the
particular handler.
Data Type INTEGER
Range 0-50
Default 0
Active Loadable No
Access Lock Application Developer
Residence CEE
Pin Exposure None
Related JUMPSAFEENB
Parameters
Checkpoint No

12.7 JUMPPATHNUM

Specific to Block(s) Handler


Description Parameter value specifies the number of paths defined for a particular
zone.
Data Type INTEGER
Range 0-15
Default 0
Active Loadable No
Access Lock Application Developer
Residence CEE
Pin Exposure None
Related Parameters JUMPZONENUM, JUMPSAFEENB
Checkpoint No

- 1552 -
Chapter 12 - Jxxxx Parameters

12.8 JUMPSAFEENB

Specific to SCM, RCM


Block(s)
Description Parameter value specifies whether or not jumps are allowed. If set to OFF, no zones
are displayed and selectable in the GoTo dialog and no jumps are allowed by the
CEE. This parameter can only be set dynamically to disable all jumps or enable only
the jumps defined as safe in the Jump Zone list. Setting this parameter does not
change the individual zones' ENABLED parameter setting. When JUMPSAFEENB is
OFF, all safe jumps are prevented and individual jump zone enables are
unchanged; when JUMPSAFEENB is ON, then individual jump zone enables
determine valid jumps.
Data Type BOOLEAN
Range 0/1
Default OFF
Active No
Loadable
Access Engineer
Lock
Residence CEE
Pin FACEPLATONLY
Exposure
Related JUMPGROUPNUM, JUMPGROUPNAME, JUMPGROUP, JUMPTARGETNUM,
Parameters JUMPZONENUM, JUMPZONENAME, JUMPZONEENB, JUMPZONE, JUMPPATHNUM
Checkpoint Yes

Specific to MR
Block(s)
Description Parameter value specifies whether jumps are allowed. If set to OFF, no zones are
displayed and selectable in the GoTo dialog and no jumps are allowed by the CEE.
This parameter can only be set dynamically to disable all jumps or enable only the
jumps defined as safe in the Jump Zone list. Setting this parameter does not
change the individual zones' ENABLED parameter setting. When JUMPSAFEENB is
OFF, all safe jumps are prevented, and individual jump zone enables are
unchanged; when JUMPSAFEENB is ON, then individual jump zone enables
determine valid jumps.
Data Type BOOLEAN
Range ON OFF
Default OFF
Config No
Load
Active No
Loadable

- 1553 -
Chapter 12 - Jxxxx Parameters

Access ViewOnly
Lock
Residence CEE
Related JUMPGROUPNUM, JUMPGROUPNAME, JUMPGROUP, JUMPTARGETNUM,
Parameters JUMPZONENUM, JUMPZONENAME, JUMPZONEENB, JUMPZONE, JUMPPATHNUM
Remarks This parameter is disabled for MR block since MR does not support the enhanced
jump functionality.

12.9 JUMPTARGETNUM

Specific to Block(s) Handler


Description Parameter value specifies the number of targets defined for a particular
group.
Data Type INTEGER
Range 0-25
Default 0
Active Loadable No
Access Lock Application Developer
Residence CEE
Pin Exposure None
Related JUMPGROUPNUM, JUMPSAFEENB
Parameters
Checkpoint No

12.10 JUMPZONE

Specific to Handler
Block(s)
Description Parameter value specifies the valid Jump Group number for each of the paths of
the parallel section for which a zone is being defined. In single threaded zones,
only the first path is required. This parameter must be set by the engineer at
configuration time only.
Data Type INTEGER
Range 50
Default 0
Active No
Loadable
Access Lock Application Developer

- 1554 -
Chapter 12 - Jxxxx Parameters

Residence CEE
Pin None
Exposure
Related JUMPZONENUM, JUMPPATHNUM, JUMPSAFEENB
Parameters
Checkpoint No

12.11 JUMPZONEENB

Specific to Handler
Block(s)
Description Parameter value specifies whether the zone is selectable or not. If not, it will not be
presented to the user in the enhanced GoTo dialog and any jump targets in that
zone will not be allowed by the CEE. This parameter can be set dynamically to
enable/disable the zone to either include or exclude potential jump targets.
Data Type BOOLEAN
Range 0/1
Default 0
Active No
Loadable
Access Lock Program
Residence CEE
Pin FACEPLATONLY
Exposure
Related JUMPZONENUM, JUMPZONEENB
Parameters
Checkpoint Yes

12.12 JUMPZONENAME

Specific to Handler
Block(s)
Description Parameter value specifies the name to be used for the Jump Zone when presented
to the user for selection in the enhanced GoTo dialog. This parameter must be set
by the engineer at configuration time only.
Data Type STRING
Range 50 char
Default 0
Active No
Loadable
Access Lock Application Developer

- 1555 -
Chapter 12 - Jxxxx Parameters

Residence SR
Pin None
Exposure
Related JUMPZONENUM, JUMPZONEENB
Parameters
Checkpoint Yes

12.13 JUMPZONENUM

Specific to Block Handler


(s)
Description Parameter value specifies the number of jump zones defined for the
particular handler.
Data Type INTEGER
Range 0-50
Default 0
Active Loadable No
Access Lock Application Developer
Residence CEE
Pin Exposure None
Related JUMPSAFEENB
Parameters
Checkpoint No

- 1556 -
CHAPTER

13 KXXXX PARAMETERS

13.1 K 1557
13.2 K[1..4] 1558
13.3 K[1..8] 1559
13.4 K1 1559
13.5 K2 1560
13.6 KEYWORD 1560
13.7 KFF 1561

13.8 KL 1561
13.9 KLIN 1561
13.10 KMODIFEXT 1562
13.11 KMODIFGAP 1562
13.12 KMODIFNL 1563
13.13 KR 1563

13.1 K

Specific to Block(s) Mux, Muxreal


Description K Selector - Number of the input to be outputted
Data Type Unsigned Integer
Range 0 to 7
Default 0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

- 1557 -
Chapter 13 - Kxxxx Parameters

Specific to Block Automan, Fanout, RegCalc, PID, PIDFF, RegSummer


(s)
Description Total Gain for Calculated Variable (CV). The PID gain. Used if GAINOPT = Lin
(configured).
Data Type 64-Bit Real Number
Range GAINLOLM to GAINHILM
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Automan, Fanout, RegCalc, RegSummer, QOR: Engineer PID, PIDFF:
Supervisor
Residence CEE
Related GAINHILM, GAINLOLM.
Parameters
Remarks

Specific to Block(s) Qor


Description K Selector
Data Type Integer
Range 1 to 8
Default 1
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

13.2 K[1..4]

Specific to Block(s) OvrdSel


Description Individual Gain for Inputs X(1) through X(4).
Data Type Real
Range GAINLOLM to GAINHILM
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters GAINHILM, GAINLOLM.
Remarks

- 1558 -
Chapter 13 - Kxxxx Parameters

13.3 K[1..8]

Specific to Block(s) Fanout


Description Total Gain for each output
Data Type 64-Bit Real Number
Range GAINLOLM to GAINHILM
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters GAINHILM, GAINLOLM.
Remarks The block applies individual user-specified gains (K[1..8]) to its outputs.

13.4 K1

Specific to Block(s) Fanout, RatioCtl, RatioBias, GenCas


Description Individual Gain for the X1 Input.
Data Type Real
Range GAINLOLM to GAINHILM
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Operator Supervisor for RATIOCTL block
Residence CEE
Related Parameters GAINHILM, GAINLOLM.
Remarks For RATIOCTL block, this parameter represents the scaling factor for X1
input.

Specific to Block(s) PIDER


Description Scaling factor for external reset feedback sgnal.
Data Type Float64
Range 0.0 to 1.0
Default 1
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters RFB
Remarks

- 1559 -
Chapter 13 - Kxxxx Parameters

13.5 K2

Specific to Block(s) Fanout, RatioCtl, RatioBias, GenCas


Description Individual Gain for the X2 Input.
Data Type Real
Range GAINLOLM to GAINHILM
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Operator Supervisor for RATIOCTL block
Residence CEE
Related GAINHILM, GAINLOLM.
Parameters
Remarks For RATIOCTL block, this parameter represents the scaling factor for X2
input.

13.6 KEYWORD

Specific to All blocks


Block(s)
Description Used to provide summary description of the block.
Data Type String
Range Length: 16 characters
Default Null String
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence SR
Related DESC, EUDESC.
Parameters
Remarks KEYWORD can be used to provide a brief block description on schematic displays
where DESC is too long.

- 1560 -
Chapter 13 - Kxxxx Parameters

13.7 KFF

Specific to PIDFF
Block(s)
Description Gain for the feedforward input.
Data Type Real
Range GAINLOLM to GAINHILM
Default 1
Config Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related FF, PV, SIFL, SP, GAINLOLM, GAINHILM.
Parameters
Remarks KFF converts the feedforward input from units of input change to percent output
change. It has units of %OP/FF input unit.

13.8 KL

Specific to Block(s) PosProp, PidPosProp


Description Overall gain for Lower Pulse Generation.
Data Type Real
Range 0.0 to 10.0
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

13.9 KLIN

Specific to Block(s) PID, PIDFF


Description Linear Gain factor. Used if GAINOPT = Gap, Nonlin, or Ext (configured).
Data Type 64-Bit Real Number
Range GAINLOLM to GAINHILM
Default 1.0

- 1561 -
Chapter 13 - Kxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters GAINHILM, GAINLOLM.
Remarks

13.10 KMODIFEXT

Specific to Block(s) PID, PIDFF


Description External Gain Modifier. Used if GAINOPT = Ext (configured).
Data Type 64-Bit Real Number
Range GAINLOLM to GAINHILM
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Program
Residence CEE
Related Parameters GAINHILM, GAINLOLM.
Remarks

13.11 KMODIFGAP

Specific to Block(s) PID, PIDFF


Description Gap Gain factor. Used if GAINOPT = Gap (configured)
Data Type 64-Bit Real Number
Range 0.0 to 1.0
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 1562 -
Chapter 13 - Kxxxx Parameters

13.12 KMODIFNL

Specific to Block(s) PID, PIDFF


Description Nonlinear Gain Modifier (calculated)
Data Type 64-Bit Real Number
Range N/A
Default 1.#QNAN0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NLFORM, NLGAIN.
Remarks

13.13 KR

Specific to Block(s) PosProp, PidPosProp


Description Overall gain for Raise Pulse Generation.
Data Type Real
Range 0.0 to 10.0
Default 1.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

- 1563 -
CHAPTER

14 LXXXX PARAMETERS

14.1 LAG1TIME 1569


14.2 LAG2TIME 1569
14.3 LAMPTEST 1570
14.4 LAMPOUT[1..32] 1570
14.5 LANABLOCKEDRATE 1570
14.6 LANABLOCKEDRATEMAX 1571
14.7 LANAFAILED 1571

14.8 LANAMACADDR 1572


14.9 LANARXRATE 1573
14.10 LANARXRATEMAX 1574
14.11 LANASILENT 1575
14.12 LANATXRATE 1575
14.13 LANATXRATEMAX 1576
14.14 LANBBLOCKEDRATE 1577
14.15 LANBBLOCKEDRATEMAX 1578
14.16 LANBFAILED 1578
14.17 LANBMACADDR 1579
14.18 LANBRXRATE 1580
14.19 LANBRXRATEMAX 1581
14.20 LANBSILENT 1582
14.21 LANBTXRATE 1582
14.22 LANBTXRATEMAX 1583
14.23 LANRXERR 1584
14.24 LANRXRATE 1585
14.25 LANRXRATEMAX 1585
14.26 LANTXERR 1586
14.27 LANTXRATE 1587
14.28 LANTXRATEMAX 1588
14.29 LASTCONNTIME[0..1] 1588
14.30 LASTDATA[1..32] 1589
14.31 LASTDISCONNTIME[0..1] 1589
14.32 LASTERRTIME[0..1] 1590

- 1564 -
Chapter 14 - Lxxxx Parameters

14.33 LASTERRTIME 1590


14.34 LASTEXECDURATIONDISP 1590
14.35 LASTEXTSTAT 1591
14.36 LASTGOOD 1591
14.37 LASTGOODPV 1592
14.38 LASTGOPREQ 1592
14.39 LASTIN[1..8] 1592
14.40 LASTINSTS[1..8] 1593
14.41 LASTIOLCMD 1593
14.42 LASTMBERR[0..15] 1595
14.43 LASTMBERRTIME[0..15] 1601
14.44 LASTMODELUPDATE 1601
14.45 LASTMODEREQ 1602
14.46 LASTOPMNAME 1602

14.47 LASTOPREQ 1603


14.48 LASTOPTYPE 1604
14.49 LASTPCUSED 1604
14.50 LASTPV 1605
14.51 LASTRATEREQ 1605
14.52 LASTREQFL 1605
14.53 LASTRESETTIME 1606
14.54 LASTSERIAL 1606
14.55 LASTSPREQ 1607
14.56 LASTSPTVREQ 1607
14.57 LASTSTAT 1607
14.58 LASTSTEP 1608
14.59 LASTSTORESTS 1609
14.60 LASTSTORESTSN 1609
14.61 LASTSYNCABRT 1609
14.62 LASTSYNCARES 1610
14.63 LASTTUNINGUPDATE 1610
14.64 LATCHENB 1611
14.65 LCDDISPLAYSF 1611
14.66 LCDDSPSTS 1612
14.67 LCNALONEA 1612
14.68 LCNALONEB 1613
14.69 LCNCBLSTSA 1613
14.70 LCNCBLSTSB 1614
14.71 LCNDMAUNDERERR 1614

- 1565 -
Chapter 14 - Lxxxx Parameters

14.72 LC BATTERYFAIL 1615


14.73 LCNMSGBUFPCT 1615
14.74 LCNMSGBUFPEAKPCT 1616
14.75 LCNRX1DECODEERR 1616
14.76 LCNRX1FCSERR 1617
14.77 LCNRX1FRAMEERR 1617
14.78 LCNRX1IOCPCHERR 1618
14.79 LCNRX1LCNIOVERERR 1618
14.80 LCNRX1OVERSZERR 1619
14.81 LCNRX1RATE 1619
14.82 LCNRX1RATEMAX 1620
14.83 LCNRX2DECODEERR 1620
14.84 LCNRX2FCSERR 1621
14.85 LCNRX2FRAMEERR 1621

14.86 LCNRX2IOCPCHERR 1622


14.87 LCNRX2LCNIOVERERR 1622
14.88 LCNRX2OVERSZERR 1623
14.89 LCNRX2RATE 1623
14.90 LCNRX2RATEMAX 1624
14.91 LCNTOELCNRATE 1624
14.92 LCNTOELCNRATEMAX 1625
14.93 LCNTXRATE 1625
14.94 LCNTXRATEMAX 1626
14.95 LCTIMESYNCFAIL 1626
14.96 LDTACYCIMRUSED 1626
14.97 LDTACYCLGREQUSED 1627
14.98 LDTACYCSMREQUSED 1627
14.99 LDTCYCIMRUSED 1628
14.100 LDTCYCLGREQUSED 1628
14.101 LDTCYCSMREQUSED 1628
14.102 LDTIMRAVAIL 1629
14.103 LDTIMRMAX 1629
14.104 LDTLGREQAVAIL 1630
14.105 LDTLGREQMAX 1630
14.106 LDTSMREQAVAIL 1630
14.107 LDTSMREQMAX 1631
14.108 LEADLAG 1631
14.109 LEADTIME 1632
14.110 LEADWIRERES 1632

- 1566 -
Chapter 14 - Lxxxx Parameters

14.111 LEGACYGAP 1633


14.112 LEGACYINITOPT 1633
14.113 LINEPERD 1634
14.114 LINEARTYPE 1634
14.115 LINKNUM 1635
14.116 LIVEDEVICEINDEX 1635
14.117 LNNAME 1636
14.118 LOADFL 1636
14.119 LOADID 1637
14.120 LOADSP 1637
14.121 LOADSPCONN 1638
14.122 LOADSPSTS 1638
14.123 LOADSTATE 1639
14.124 LOCALCLOSE 1640

14.125 LOCALMAN 1640


14.126 LOCALOPEN 1640
14.127 LOCALSTART 1641
14.128 LOCALSTOP 1641
14.129 LOCALSTOPACTED 1642
14.130 LOCALSWITCH 1642
14.131 LOCATION 1642
14.132 LOCUTOFF 1643
14.133 LOGICALENIM 1644
14.134 LOGICALENIMIPADDRESS 1644
14.135 LOGICALUCNNW 1644
14.136 LOGICINITOPT 1645
14.137 LOGICGATE1 1646
14.138 LOGICGATE2 1646
14.139 LOGICGATE3 1647
14.140 LOGICGATE4 1647
14.141 LOGIENIMDATEPTIMPORT 1648
14.142 LOGIENIMIMPORTSTATUS 1648
14.143 LOLMRAMPRATE 1649
14.144 LOOKAHEAD 1649
14.145 LOOPADDR 1650
14.146 LOOPCOUNT 1650
14.147 LOOPDATA 1651
14.148 LOOPDATACHG 1651
14.149 LOOPMODE 1652

- 1567 -
Chapter 14 - Lxxxx Parameters

14.150 LOOPRATE 1653


14.151 LOOPTYPE 1653
14.152 LOSTKNDROP 1654
14.153 LOWENG[0..numChans-1] 1655
14.154 LOWENG[0..7] 1655
14.155 LOWERDEADTM 1655
14.156 LOWERDESC 1656
14.157 LOWERLMFL 1656
14.158 LOWERRATE 1657
14.159 LOWERTIME 1657
14.160 LOWSIGNAL[0..numChans-1] 1657
14.161 LOWSIGNAL[0..7] 1658
14.162 LRL 1659
14.163 LRL HART 1659

14.164 LRR 1659


14.165 LRRACTED 1660
14.166 LRRALM.FL 1660
14.167 LRRALM.OPT 1661
14.168 LRRALM.PR 1661
14.169 LRRALM.SV 1661
14.170 LRV 1662
14.171 LRV HART 1662
14.172 LSCYCLEOVRN[0...40] 1663
14.173 LSCYCLESKIP[0..40] 1664
14.174 LSCYCLESKIP 1664
14.175 LSSKIPERIOD 1665
14.176 LSSKIPPERIOD[0..40] 1665
14.177 LSTHRERRFIFOENTRY 1666
14.178 LSTHRRCVFIFOENTRY 1666
14.179 LSTHRRPTFIFOENTRY 1666
14.180 LTC 1667
14.181 LTO 1667

- 1568 -
Chapter 14 - Lxxxx Parameters

14.1 LAG1TIME

Specific to LeadLag
Block(s)
Description First Order Lag Time (in Minutes) - A time constant used as a first-order lag
compensation factor by the LeadLag function block.
Data Type Real Number
Range 0.0 to 1440.0 minutes
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related LAG2TIME
Parameters
Remarks If LAG2TIME = 0.0, there is no second-order lag compensation.

14.2 LAG2TIME

Specific to LeadLag
Block(s)
Description Second Order Lag Time (in Minutes) - A time constant used as a first-order lag
compensation factor by the LeadLag function block.
Data Type Real Number
Range 0.0 to 1440.0 minutes
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related LAG1TIME
Parameters
Remarks If LAG2TIME = 0.0, there is no second-order lag compensation.

- 1569 -
Chapter 14 - Lxxxx Parameters

14.3 LAMPTEST

Specific to Block(s) ANNPANEL


Description Lamp test
Data Type Boolean
Range ON/OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters LAMPOUT[1..32]
Remarks This is to test the healthiness of lamps of annunciator panel FB

14.4 LAMPOUT[1..32]

Specific to Block(s) ANNPANEL


Description Output value of the Annunciator Panel
Data Type Boolean
Range ON/OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters FLSHSTAT
Remarks This feeds the DO Channel block.

14.5 LANABLOCKEDRATE

Specific to Block EIM Platform Block, TCMI, UOC, C300


(s)
Description FTE A Block Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No

- 1570 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Packets per second blocked (by CF9 firewall) on FTE A cable. (FTE parameters,
see C300 definition)

14.6 LANABLOCKEDRATEMAX

Specific to EIM, TCMI, UOC, C300


Block(s)
Description FTE A Block Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of packets per second blocked (by CF9 firewall) on FTE A
interface. (FTE parameters, see C300 definition)

14.7 LANAFAILED

Specific to FTEB, C300, PGM, FIM4, EHPM , TCMI


Block(s)
Description Local Area Network (LAN) A Failed - Provides status indicator for port A (Yellow
Tree Port) on the FTE interface.
Data Type Boolean
Range 0 = Not Failed 1 = Failed
Default Not Failed (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED, INTERLANFAILED
Parameters
Remarks If this indicator is ON, it means that communications have failed on Port A.

- 1571 -
Chapter 14 - Lxxxx Parameters

Specific to Block(s) EIM, UOC


Description FTE A (Yellow) Failed
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.8 LANAMACADDR

Specific to Block(s) EIM


Description FTE A (Yellow) MAC
Data Type STRING
Range NA
Default Ringbac
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks MAC address for FTE A network interface

Specific to Block(s) UOC


Description FTE A (Yellow) MAC Address
Data Type STRING
Range N/A
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

- 1572 -
Chapter 14 - Lxxxx Parameters

Specific to Block(s) TCMI


Description FTE A (Yellow) MAC Address
Data Type STRING
Range N/A
Default 00-40-84-14-91-4F
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.9 LANARXRATE

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description Local Area Network (LAN) A Receive Rate- Identifies communication receive rate in
kilobits per second (kbps) for port A (Yellow Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANAFAILED
Parameters
Remarks

Specific to Block(s) EIM


Description FTE A Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Packets per second received on FTE A cable.

- 1573 -
Chapter 14 - Lxxxx Parameters

Specific to Block(s) UOC


Description FTE A Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.10 LANARXRATEMAX

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description Local Area Network (LAN) A Receive Rate Maximum- Identifies maximum
communication receive rate in kilobits per second (kbps) for port A (Yellow Tree
Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANAFAILED
Parameters
Remarks

Specific to Block(s) EIM


Description FTE B Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks High water mark of packets per second transmitted over FTE B cable.

- 1574 -
Chapter 14 - Lxxxx Parameters

Specific to Block(s) UOC


Description FTE A Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.11 LANASILENT

Specific to Block(s) EIM, UOC, TCMI


Description FTE A (Yellow) Silent
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.12 LANATXRATE

Specific to FTEB, C300, PGM, FIM4, EHPM , TCMI


Block(s)
Description Local Area Network (LAN) A Transmit Rate- Identifies communication transmission
rate in kilobits per second (kbps) for port A (Yellow Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable

- 1575 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence FTEB, C300, FIM4, PGM, EHPM
Related LANAFAILED
Parameters
Remarks

Specific to Block(s) EIM


Description FTE A Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Packets per second transmitted on FTE A cable.

Specific to Block(s) UOC


Description FTE A Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.13 LANATXRATEMAX

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description Local Area Network (LAN) A Transmit Rate Maximum- Identifies maximum
communication transmission rate in kilobits per second (kbps) for port A (Yellow
Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No

- 1576 -
Chapter 14 - Lxxxx Parameters

Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANAFAILED
Parameters
Remarks

Specific to Block(s) EIM


Description FTE A Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks High water mark of packets per second transmitted over FTE A cable.

Specific to Block(s) UOC


Description FTE A Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.14 LANBBLOCKEDRATE

Specific to Block EIM, TCMI, UOC, C300


(s)
Description FTE B Block Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No

- 1577 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Packets per second blocked (by CF9 firewall) on FTE B cable. (FTE parameters,
see C300 definition)

14.15 LANBBLOCKEDRATEMAX

Specific to EIM, TCMI, UOC, C300


Block(s)
Description FTE B Block Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of packets per second blocked (by CF9 firewall) on FTE B
interface. (FTE parameters, see C300 definition)

14.16 LANBFAILED

Specific to FTEB, C300, PGM, FIM4 , EHPM , TCMI


Block(s)
Description Local Area Network (LAN) B Failed - Provides status indicator for port B (Green
Tree Port) on the FTE interface.
Data Type Boolean
Range 0 = Not Failed 1 = Failed
Default Not Failed (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANAFAILED, INTERLANFAILED
Parameters
Remarks If this indicator is ON, it means that communications have failed on Port B.

- 1578 -
Chapter 14 - Lxxxx Parameters

Specific to Block(s) EIM, UOC


Description FTE B (Green) Failed
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.17 LANBMACADDR

Specific to Block(s) EIM


Description FTE B (Green) MAC
Data Type String
Range N/A
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks MAC address for FTE B network interface

Specific to Block(s) UOC


Description FTE B (Green) MAC Address
Data Type STRING
Range N/A
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

- 1579 -
Chapter 14 - Lxxxx Parameters

Specific to Block(s) TCMI


Description FTE B (Green) MAC Address
Data Type STRING
Range N/A
Default 00-40-84-14-91-50
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.18 LANBRXRATE

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description Local Area Network (LAN) B Receive Rate- Identifies communication receive rate in
kilobits per second (kbps) for port B (Green Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

Specific to Block(s) UOC


Description FTE B Rx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

- 1580 -
Chapter 14 - Lxxxx Parameters

14.19 LANBRXRATEMAX

Specific to FTEB, C300, PGM, FIM4 , EHPM


Block(s)
Description Local Area Network (LAN) B Receive Rate Maximum- Identifies maximum
communication receive rate in kilobits per second (kbps) for port B (Green Tree
Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

Specific to Block(s) EIM


Description FTE B Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks High water mark of packets per second received over FTE B cable.

Specific to Block(s) UOC


Description FTE B Rx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

- 1581 -
Chapter 14 - Lxxxx Parameters

14.20 LANBSILENT

Specific to Block(s) EIM,UOC, TCMI


Description FTE B (Green) Silent
Data Type BOOLEAN
Exposure OUTPUT
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.21 LANBTXRATE

Specific to FTEB, C300, PGM, FIM4, EHPM , TCMI


Block(s)
Description Local Area Network (LAN) B Transmit Rate- Identifies communication transmission
rate in kilobits per second (kbps) for port B (Green Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

Specific to Block(s) EIM


Description FTE B Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No

- 1582 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters LANBFAILED
Remarks Packets per second transmitted on FTE B cable.

Specific to Block(s) UOC


Description FTE B Tx Rate (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.22 LANBTXRATEMAX

Specific to FTEB, C300, PGM, FIM4, EHPM


Block(s)
Description Local Area Network (LAN) B Transmit Rate Maximum- Identifies maximum
communication transmission rate in kilobits per second (kbps) for port B (Green
Tree Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

Specific to Block(s) EIM


Description FTE B Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No

- 1583 -
Chapter 14 - Lxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks High water mark of packets per second transmitted over FTE B cable.

Specific to Block(s) UOC


Description FTE B Tx Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.23 LANRXERR

Specific to Block(s) EIM, TCMI


Description FTE Receive Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Receive errors on FTE A cable.

Specific to Block(s) UOC, C300


Description FTE Receive Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable

- 1584 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.24 LANRXRATE

Specific to Block(s) EIM, TCMI


Description Total Rx Rate (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Kilobits per second recevied through FTE network (bothj FTE A and FTE B
cables).

Specific to Block(s) UOC


Description Total Rx Rate (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.25 LANRXRATEMAX

Specific to Block EIM, TCMI


(s)
Description Total Rx Rate Max (kBit/sec)
Data Type UINT32
Range 0 to 4294967295

- 1585 -
Chapter 14 - Lxxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of kilobits per second received through FTE network (bothj
FTE A and FTE B cables).

Specific to Block(s) UOC


Description Total Rx Rate Max (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.26 LANTXERR

Specific to Block(s) EIM Platform Block, TCMI


Description FTE Transmit Errors
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Receive errors on FTE B cable.

Specific to Block(s) UOC, C300


Description FTE Transmit Errors
Data Type UINT32
Range 0 to 4294967295
Default 0

- 1586 -
Chapter 14 - Lxxxx Parameters

Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.27 LANTXRATE

Specific to Block(s) EIM, TCMI


Description Total Tx Rate (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Kilobits per second transmitted through FTE network (bothj FTE A and FTE B
cables).

Specific to Block(s) UOC


Description Total Tx Rate (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

- 1587 -
Chapter 14 - Lxxxx Parameters

14.28 LANTXRATEMAX

Specific to EIM, TCMI


Block(s)
Description Total Tx Rate Max (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of kilobits per second transmitted through FTE network (bothj
FTE A and FTE B cables).

Specific to Block(s) UOC


Description Total Tx Rate Max (kBit/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

14.29 LASTCONNTIME[0..1]

Specific to Block(s) PCDI_MASTER


Description Last Connect Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No

- 1588 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence Device
Related Parameters
Remarks

14.30 LASTDATA[1..32]

Specific to Block(s) CHGEXEC


Description Last Data - Holds value of DATA[ ] array from last execution cycle of
CHGEXEC.
Data Type Boolean
Range 0 Off
1 On
Default Off (0)
Config Load No
Active Loadable No
Access Lock View Only
Residence CEE
Related DATA[1..32]ALTSYNCCMD
Parameters
Remarks

14.31 LASTDISCONNTIME[0..1]

Specific to Block(s) PCDI_MASTER


Description Last Disconnect Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Device
Related Parameters
Remarks

- 1589 -
Chapter 14 - Lxxxx Parameters

14.32 LASTERRTIME[0..1]

Specific to Block(s) PCDI_MASTER


Description Time of Last Error
Data Type Time
Range
Default 0 (12/31/1971 9:00:00 PM)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.33 LASTERRTIME

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Time of Last Error
Data Type Time
Range
Default 0 (12/31/1971 9:00:00 PM)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.34 LASTEXECDURATIONDISP

Specific to Block(s) ProfitCtl


Description Actual Exec (in mins)
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No

- 1590 -
Chapter 14 - Lxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters
Remarks

14.35 LASTEXTSTAT

Specific to Block(s) QIPACCHAN


Description Ext. Status Last Transaction
Data Type 32-Bit Unsigned Integer
Range n/a
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters None
Remarks

14.36 LASTGOOD

Specific to Block Totalizer, Pulse Input Totalizer


(s)
Description Last Good Value - This is the last good accumulated value, before the input
went bad.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PV
Parameters
Remarks

- 1591 -
Chapter 14 - Lxxxx Parameters

14.37 LASTGOODPV

Specific to Block(s) DataAcq, PID,PIDFF, PosProp.


Description Last good Process Variable (PV) value
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PV, PVSTS.
Remarks

14.38 LASTGOPREQ

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Last Generic Requested Output Value (GOPREQ) while ControlModule.SMCSTATE
is Running
Data Type Enumeration GENSTATE
Range Null (0) S0 (1) S1 (2) S2 (3)
Default Null (0)
Config Load No
Access Lock Other Function Block
Residence CEE
Related GOPREQ, LASTOPMNAME, LASTOPREQ, LASTREQFL, OPREQ, RESTARTOPT,
Parameters SCMOPT, SCMSTATE DEVCTL Only: NUMSTATES, STATETEXT[0..6]
Remarks S2 is illegal if NUMSTATES = 2. Illegal if ControlModule.SCMOPT ≠ Fixed.

14.39 LASTIN[1..8]

Specific to Block(s) CheckBool Logic Block


Description Last Valid Input Value
Data Type Boolean
Range (0) OFF (1) ON
Default OFF
Config Load No
Active Loadable No

- 1592 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters LASTINSTS[1..8]
Remarks Provides the last value of IN[1..8]

14.40 LASTINSTS[1..8]

Specific to CheckBool Logic Block


Block(s)
Description Last Valid Input Status
Data Type Enumeration
Range 0 - 6 (0) kBadValSts (1) kUncertainValSts (2) kNormalValSts (3) kManualValSts (4)
kInitAckValSts (5) kInitRegValStst (6) kInitBadValSts
Default kNormalValSts
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related LASTIN[1..8]
Parameters
Remarks Provides the last value of INSTS[1..8]

14.41 LASTIOLCMD

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Last I/O Link Command. Shows the last I/O link command requested through the
COMMAND parameter, or the last SELECT_CH_A / SELECT_CH_B command
automatically issued when periodic channel swap is enabled.
Data Type Enumeration
Range NONE (0): No effect.
SELECT_CH_A (1): Select I/O Link Channel A.
SELECT_CH_B (2): Select I/O Link Channel B.
RESET_ERRORS (3): Reset IOL communication error count to
zero.
ENB_PERSWAP (4): Enable periodic swapping of IOL cables.
DIS_PERSWAP (5): Disable periodic swapping of IOL cables.
Default NONE (0)
Config No
Load

- 1593 -
Chapter 14 - Lxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related COMMAND
Parameters
Remarks Note that this is the same as the IOLCMD parameter in a TPS system.

- 1594 -
Chapter 14 - Lxxxx Parameters

14.42 LASTMBERR[0..15]

- 1595 -
Chapter 14 - Lxxxx Parameters

Specific to Block(s) PCDI_MASTER


Description Last Modbus Error
Data Type Enumeration

- 1596 -
Chapter 14 - Lxxxx Parameters

Range 0 OK

- 1597 -
Chapter 14 - Lxxxx Parameters

1 No More Data

- 1598 -
Chapter 14 - Lxxxx Parameters

2 Already Added

- 1599 -
Chapter 14 - Lxxxx Parameters

3 Send Limit
4 Orphan Resp
5 Diag Testing
6 Already Added with Send Limit
256 Generic Fail
257 Not Init
258 Invalid Param
259 Unsupported Cmd
260 Resources
261 Invalid UID
262 No Device
263 Add Fail
264 Send Fail
265 Send Err
266 No Conn
267 Sock Err
268 Bad Buffer
269 Internal Err
270 Timed Out
271 Not Found
272 Wait Failed
273 Dev Disabled
274 Rcv Msg Len
275 Bad Resp
276 Bad Xact
277 Unexpected Diag Val
278 Master Inactive
279 Device Init
280 Device Fail
281 SM Idle
512 Illegal Func
513 Illegal Addr
514 Illegal Data
515 Slave Fail
516 Ack Fail
517 Slave Busy
518 Parity Err
519 Bad Path
520 No Target Resp

- 1600 -
Chapter 14 - Lxxxx Parameters

Default Not Init


Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.43 LASTMBERRTIME[0..15]

Specific to Block(s) PCDI_MASTER


Description Last Modbus Error Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.44 LASTMODELUPDATE

Specific to Block(s) ProfitCtl


Description Last Model Update
Data Type STRING
Range NA
Default Example
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

- 1601 -
Chapter 14 - Lxxxx Parameters

14.45 LASTMODEREQ

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Last value of MODEREQ (Mode Request), when is Running.
Data Type Enumeration REGMODE
Range Man (0) Auto (1) Cas (2) None (3)
Default None (3)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RESTARTOPT, SCMOPT, SCMSTATE.
Parameters
Remarks

14.46 LASTOPMNAME

Specific to Secondary C200 C300, PGM, FIM4 FB, ACE FB, and EHPM
Block(s)
Description Last OPM Name - Name of last block to be on-process migrated.
Data Type BlockId
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, C300, FIM4, LIOM, PGM, and ACE
Related ALTSYNCCMD, DSBLSYNCCMD, ENBLSYNCCMD
Parameters
Remarks Used to isolate the name of the first CEE suboridinate block encountered that has
detected a controller On-Process Migration error. Parameter appears only on
configuraton form for secondary module.

- 1602 -
Chapter 14 - Lxxxx Parameters

14.47 LASTOPREQ

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Last value of OPREQ (Output Request), when SCMMODE is Running.
Data Type 64-Bit Real Number
Range OPEXLOLMOPEXHILM
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RESTARTOPT SCMOPT SCMSTATE
Parameters
Remarks

Specific to DevCtl
Block(s)
Description Last OPREQ (Output Request) while SCM was running.
Data Type String
Range Length: 12 characters
Default STATETEXT[0]
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related GOPREQ, LASTGOPREQ, LASTREQFL, NUMSTATES, OPREQ, RESTARTOPT,
Parameters SCMOPT, SCMSTATE, STATETEXT[0..6].
Remarks LASTOPREQ is a String set equal to STATETEXT (GOPREQ value while Running).
STATETEXT[6] [‘State2’] is illegal if NUMSTATES = 2. Illegal if
ControlModule.SCMOPT ≠ Fixed.

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Last OPREQ (Output Request) while SCM was running.
Data Type Self-Defining Enumeration
Range BAD, RUN, STOP for HT/LT, BAD, OPEN, CLOSE for SOLND and BAD, OPEN,
CLOSE, NOCOMMAND for VLVDAMPR
Default BAD
Config Load NO
Active No
Loadable

- 1603 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related GOPREQ, LASTGOPREQ, LASTREQFL, OPREQ, RESTARTOPT, SCMOPT,
Parameters SCMSTATE
Remarks LASTOPREQ is a String set equal to STATETEXT (GOPREQ value while Running).
Illegal if ControlModule.SCMOPT ≠ Fixed.

14.48 LASTOPTYPE

Specific to DevCtl, All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: HTmotor, LTmotor, Solenoid, ValveDamper
Description Last OPTYPE (Output Type) stored when SCM was Running.
Data Type Enumeration OPTYPE
Range Null (0) Set (1) NotStored (2) Default (3)
Default Null (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODEATTRREFLASTOPMNAMELASTOPREQLASTREQFLOPTYPE RESTARTOPT,
Parameters SCMOPT, SCMSTATE.
Remarks Illegal if ControlModule.SCMOPT ≠ Fixed.

14.49 LASTPCUSED

Specific to Block(s) MAP


Description Last param code used
Data Type INT32
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters NUMFUNREF, NUMBLKREF, NUMPRMREF, CUSTPCRANGE
Remarks

- 1604 -
Chapter 14 - Lxxxx Parameters

14.50 LASTPV

Specific to Block(s) AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Description Last Process Variable (PV). Shows the value of the PV before the value
became BAD.
Data Type 32-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks Useful reference when PV has gone BAD.

14.51 LASTRATEREQ

Specific to Block(s) PID, PIDFF, PosProp


Description Last value of (Set Point Rate Request), when is Running
Data Type 64-Bit Real Number
Range NaN, 0.0, Real numbers.
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters RESTARTOPT, SCMOPT, SCMSTATE.
Remarks

14.52 LASTREQFL

Specific to DevCtl All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: HTmotor, LTmotor, Solenoid, ValveDamper
Description Last Requested Parameters Flag
Data Type Boolean
Range Off (0): Don't show Last Requested Variables. On (1): Display Last Requested
Variables.
Default Off (0)

- 1605 -
Chapter 14 - Lxxxx Parameters

Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related LASTOPREQLASTOPMNAMELASTOPTYPE RESTARTOPT SCHEDCYCLE[0..120]
Parameters SCMASTEP[1..15] SCMMODE SCMOPT SCMSTATE
Remarks Illegal if ControlModule.SCMOPT ≠ Fixed.

14.53 LASTRESETTIME

Specific to Block(s) ELCN_BRG, ELCN_NODE


Description Timestamp of the last time the LCN Statistics Reset Button was pressed.
Data Type Time
Range N/A
Default 1/1/1972
Config Load No
Active Loadable No
Access Lock Operator
Residence Residency is the platform to which the tagged block is configured and loaded.
Related Parameters ELCNSTATSRST
Remarks

14.54 LASTSERIAL

Specific to Block(s) DOC


Description Last Serial Number
Data Type Integer
Range N/A
Default 0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 1606 -
Chapter 14 - Lxxxx Parameters

14.55 LASTSPREQ

Specific to Block(s) PID, PIDFF, PosProp


Description Last value of SPREQ (Set Point Request), when SCMMODE is Running.
Data Type 64-Bit Real Number
Range to .
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters RESTARTOPT, SCMOPT, SCMSTATE.
Remarks

14.56 LASTSPTVREQ

Specific to Block PID, PIDFF, PosProp


(s)
Description Last Requested Set Point Target Value (SPTVREQ) when
ControlModule.SCMSTATE = Running.
Data Type 64-Bit Real Number
Range to .
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related RESTARTOPT, SCMOPT, SCMSTATE.
Parameters
Remarks

14.57 LASTSTAT

Specific to Block(s) QIPACCHAN


Description Status Last Transaction
Data Type 32-Bit Unsigned Integer
Range n/a
Default 0
Config Load No

- 1607 -
Chapter 14 - Lxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters None
Remarks

14.58 LASTSTEP

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Last ASTEPID while SCM was Running the Last Active Step when themonitored
SCM was in Running State.
Data Type Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related LASTOPMNAME LASTOPREQ, LASTOPTYPENUM RESTARTOPT, SCHEDCYCLE
Parameters [0..120] SCMASTEP[1..15], SCMMODE, SCMOPT, SCMSTATE.
Remarks Illegal if ControlModule.SCMOPT ≠ Fixed.

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Last value of (SCM Active STEP), when is Running.
Data Type String
Range Length: 8 characters
Default Null String
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 1608 -
Chapter 14 - Lxxxx Parameters

14.59 LASTSTORESTS

Specific to Block(s) PUSH


Description Last Store Status
Data Type Enumeration
Range 0 STOREOK
1 STOREPENDING
2 STOREFAIL
3 DATATYPERR
Default STOREOK
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters STORESTS
Remarks

14.60 LASTSTORESTSN

Specific to Block(s) PUSH


Description Last Store Status Error Number
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.61 LASTSYNCABRT

Specific to RM
Block(s)
Description Last Synchronization Abort Cause
Data Type Enumeration [4]
Range NoAbort (0) ModInsert (1) ModRemoval (2) ModMismatch (3) Editing (4) StalledSync
(5) SecFault (6)

- 1609 -
Chapter 14 - Lxxxx Parameters

Default NoAbort (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

14.62 LASTSYNCARES

Specific to RM
Block(s)
Description Last Synchronization Attempt Result
Data Type Enumeration [4]
Range NoAttempt (0) Abort (1) Success (2)
Default NoAttempt (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

14.63 LASTTUNINGUPDATE

Specific to Block(s) ProfitCtl


Description Last Tuning Update
Data Type STRING
Range NA
Default Example
Config Load Yes
Active Loadable No

- 1610 -
Chapter 14 - Lxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters
Remarks

14.64 LATCHENB

Specific to TC-POB041
Block(s)
Description Latch Mode Enable
Data Type Boolean
Range Off(0) On(1)
Default Off(0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related FAULTENB[ ]FAULTRESET
Parameters
Remarks Enables latching of detected faults. Only applicable if fault detection is enabled.
Applies globally to all channels on the device.

14.65 LCDDISPLAYSF

Specific to Block(s) ELCN_BRG, ELCN_NODE

Description LCD Display Panel Errors

Data Type Boolean

Range ON, OFF

Default OFF

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG, ELCN_NODE

Related Parameters SOFTFAIL

Remarks LCD (on the front panel at the physical UEA box) is not operational.

- 1611 -
Chapter 14 - Lxxxx Parameters

14.66 LCDDSPSTS

Specific to Block(s) TCMI


Description LCD Display Status
Data Type ENUM
Range N/A
Default OK
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

14.67 LCNALONEA

Specific to Block(s) ELCN_BRG

Description Total Cable A Alone in Ring

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

- 1612 -
Chapter 14 - Lxxxx Parameters

14.68 LCNALONEB

Specific to Block(s) ELCN_BRG

Description Total Cable B Alone in Ring

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

14.69 LCNCBLSTSA

Specific to Block(s) TCMI


Description LCN Cable A Failed
Data Type BOOLEAN
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 1613 -
Chapter 14 - Lxxxx Parameters

14.70 LCNCBLSTSB

Specific to Block(s) TCMI


Description LCN Cable B Failed
Data Type BOOLEAN
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

14.71 LCNDMAUNDERERR

Specific to ELCN_BRG
Block(s)

Description LCN Tx DMA Underrun Error count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active No
Loadable

Access Lock ViewOnly

Residence ELCN_BRG

Related ELCN Bridge Statistics tab


Parameters

Remarks DMA under-run while the LCNI is transmitting. The LCNI stops transmission such that
the frame sent will have a framing error.

- 1614 -
Chapter 14 - Lxxxx Parameters

14.72 LC BATTERYFAIL

Specific to Block(s) TCMI


Description LC battery failure
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

14.73 LCNMSGBUFPCT

Specific to Block(s) ELCN_BRG

Description LCN Tx [%]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks Allocated buffers for transmission to LCN

- 1615 -
Chapter 14 - Lxxxx Parameters

14.74 LCNMSGBUFPEAKPCT

Specific to Block(s) ELCN_BRG

Description LCN Tx Peak [%]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statisticstab

Remarks Highest amount of buffers allocated for transmission to LCN

14.75 LCNRX1DECODEERR

Specific to ELCN_BRG
Block(s)

Description LCN Rx1 Manchester Decoder Error count

Data Type 32-Bit Integer

Range

Default 0

Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence ELCN_BRG

Related ELCN Bridge Statistics tab


Parameters

Remarks Manchester Decoder Error- The LCNI hardware detected an error in the Manchester
decoder operation. This can be due to a hardware failure or poor quality of received signal.

- 1616 -
Chapter 14 - Lxxxx Parameters

14.76 LCNRX1FCSERR

Specific to Block(s) ELCN_BRG

Description LCN Rx1 Frame Check Seq Error count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks FCS Error - Locally computed FCS did not compare with the FCS received.

14.77 LCNRX1FRAMEERR

Specific to ELCN_BRG
Block(s)

Description LCN Rx1 Framing Errorcount

Data Type 32-Bit Integer

Range

Default 0

Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence ELCN_BRG

Related ELCN Bridge Statistics tab


Parameters

Remarks Framing Error- The total number of bits received between the start of frame delimiter and
end of frame delimiter was not exactly divisible by 16.

- 1617 -
Chapter 14 - Lxxxx Parameters

14.78 LCNRX1IOCPCHERR

Specific to Block ELCN_BRG


(s)

Description LCN Rx1 IOCB Chain Full Error count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related ELCN Bridge Statistics tab


Parameters

Remarks Receiver Overrun Error – Overload issue.  Indicates slow receive from LCN and
possible loss of packets.

14.79 LCNRX1LCNIOVERERR

Specific to Block(s) ELCN_BRG

Description LCN Rx1 LCNI Overrun Error count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

- 1618 -
Chapter 14 - Lxxxx Parameters

14.80 LCNRX1OVERSZERR

Specific to Block(s) ELCN_BRG

Description LCN Rx1 Oversize Error count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks Oversize Frame Error - The frame was longer than the allowed length.

14.81 LCNRX1RATE

Specific to Block(s) ELCN_BRG

Description LCN Rx1 Rate [pkts/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks Data packets received from LCN on channel 1

- 1619 -
Chapter 14 - Lxxxx Parameters

14.82 LCNRX1RATEMAX

Specific to Block(s) ELCN_BRG

Description LCN Rx1 Rate Max [pkts/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab


Remarks Data packets received from LCN on channel 1

14.83 LCNRX2DECODEERR

Specific to Block(s) ELCN_BRG

Description LCN Rx2 Manchester Decoder error count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

- 1620 -
Chapter 14 - Lxxxx Parameters

14.84 LCNRX2FCSERR

Specific to Block(s) ELCN_BRG

Description LCN Rx2 Frame Check Sequenceerror count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

14.85 LCNRX2FRAMEERR

Specific to ELCN_BRG
Block(s)

Description LCN Rx2 Framing errorcount

Data Type 32-Bit Integer

Range

Default 0

Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence ELCN_BRG

Related ELCN Bridge Statistics tab


Parameters

Remarks Framing Error. The total number of bits received between the start of frame delimiter and
end of frame delimiter was not exactly divisible by 16.

- 1621 -
Chapter 14 - Lxxxx Parameters

14.86 LCNRX2IOCPCHERR

Specific to Block ELCN_BRG


(s)

Description LCN Rx2 IOCB Chain Full error count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related ELCN Bridge Statistics tab


Parameters

Remarks Receiver Overrun Error – Overload issue.  Indicates slow receive from LCN and
possible loss of packets.

14.87 LCNRX2LCNIOVERERR

Specific to Block(s) ELCN_BRG

Description LCN Rx2 LCNI Overrun errorcount

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

- 1622 -
Chapter 14 - Lxxxx Parameters

14.88 LCNRX2OVERSZERR

Specific to Block(s) ELCN_BRG

Description LCN Rx2 Oversize error count

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks Oversize Frame Error - The frame was longer than the allowed length.

14.89 LCNRX2RATE

Specific to Block(s) ELCN_BRG

Description LCN Rx2 Rate [pkts/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics

Remarks Data packets received from LCN on channel 2

- 1623 -
Chapter 14 - Lxxxx Parameters

14.90 LCNRX2RATEMAX

Specific to Block(s) ELCN_BRG

Description LCN Rx2 Rate Max [pkts/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks Data packets received from LCN on channel 2

14.91 LCNTOELCNRATE

Specific to Block(s) ELCN_BRG

Description LCN to ELCN Rate [msgs/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks Message transfer from LCN to ELCN

- 1624 -
Chapter 14 - Lxxxx Parameters

14.92 LCNTOELCNRATEMAX

Specific to Block(s) ELCN_BRG

Description LCN to ELCN Rate Max [msgs/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks Message transfer from LCN to ELCN

14.93 LCNTXRATE

Specific to Block(s) ELCN_BRG

Description Data packets transmitted to ELCN [pkts/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

- 1625 -
Chapter 14 - Lxxxx Parameters

14.94 LCNTXRATEMAX

Specific to Block(s) ELCN_BRG

Description LCN Tx Rate Max [pkts/sec]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks Data packets transmitted to ELCN

14.95 LCTIMESYNCFAIL

Specific to Block(s) TCMI


Description LC time synch failure
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

14.96 LDTACYCIMRUSED

Specific to Block(s) CEEC300


Description LDT Acyclic IMRs Used.
Data Type 32-bit integer
Range
Default 0
Config Load No
Active Loadable No

- 1626 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks This parameter represents the current number of LDT Acyclic IMRs used.

14.97 LDTACYCLGREQUSED

Specific to Block(s) CEEC300


Description LDT Acyclic Large Requests Used
Data Type 32-bit integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300)
Related
Parameters
Remarks This parameter represents the current number of LDT acyclic large requests
used.

14.98 LDTACYCSMREQUSED

Specific to Block(s) CEEC300


Description LDT Acyclic Large Requests Used
Data Type 32-bit integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300)
Related
Parameters
Remarks This parameter represents the current number of LDT acyclic small requests
used.

- 1627 -
Chapter 14 - Lxxxx Parameters

14.99 LDTCYCIMRUSED

Specific to Block(s) CEEC300


Description LDT Cyclic IMRs Used
Data Type 32-bit integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300)
Related Parameters
Remarks This parameter represents the current number of LDT cyclic IMRs in use.

14.100 LDTCYCLGREQUSED

Specific to Block(s) CEEC300


Description LDT Cyclic Large Requests Used
Data Type 32-bit integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300)
Related
Parameters
Remarks This parameter represents the current number of LDT cyclic large requests
used.

14.101 LDTCYCSMREQUSED

Specific to Block(s) CEEC300


Description LDT Cyclic Small Requests Used
Data Type 32-bit integer
Range N/A
Default 0
Config Load No
Active Loadable No

- 1628 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300)
Related
Parameters
Remarks This parameter represents the current number of LDT cyclic small requests
used.

14.102 LDTIMRAVAIL

Specific to Block(s) CEEC300


Description LDT IMRs Available
Data Type 32-bit integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300)
Related Parameters
Remarks

14.103 LDTIMRMAX

Specific to Block(s) CEEC300


Description LDT Total IMRs
Data Type 32-bit integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300)
Related Parameters
Remarks

- 1629 -
Chapter 14 - Lxxxx Parameters

14.104 LDTLGREQAVAIL

Specific to Block(s) CEEC300


Description LDT Large Requests Available
Data Type 32-bit integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.105 LDTLGREQMAX

Specific to Block(s) CEEC300


Description LDT Total Large Requests
Data Type 32-bit integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.106 LDTSMREQAVAIL

Specific to Block(s) CEEC300


Description LDT Small Requests Available
Data Type 32-bit integer
Range N/A
Default 0
Config Load No
Active Loadable No

- 1630 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters N/A
Remarks

14.107 LDTSMREQMAX

Specific to Block(s) CEEC300


Description LDT Total Small Requests
Data Type 32-bit integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.108 LEADLAG

Specific to HRBALG_REG block


Blocks
Description LEADLAG FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the LEADLAG block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

- 1631 -
Chapter 14 - Lxxxx Parameters

14.109 LEADTIME

Specific to LeadLag
Block(s)
Description Lead Time (in Minutes) - A time constant used as a lead compensation factor by
the LeadLag function block.
Data Type Real Number
Range -1440.0 to 1440.0 minutes
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks If LEADTIME = 0.0, there is no lead compensation.

14.110 LEADWIRERES

Specific to Block(s) Series C AICHANNEL Block Only

Description Lead Wire Resistance (Ohms)

Data Type FLOAT32

Exposure OUTPUT

Range 0 to 50

Default 0

Config Load No

Engineer

Residence IOM

Related Parameters N/A

Remarks Applicable for only channels where:


SENSRTYP is: RTD and INPTWIRETYP is: 2-Wire or
SENSRTYP is: 0_500_Ohms or 0_2000_Ohms

Internal Only No

- 1632 -
Chapter 14 - Lxxxx Parameters

14.111 LEGACYGAP

Specific to PID, PIDER, PIDFF, PID-PL


Block(s)
Description Legacy gap option
Data Type Boolean
Range OFF (Option disabled) ON (Option enabled)
Default OFF
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related
Parameters
Remarks Applies to the following FBs; PID, PIDFF, PIDER and PID-PL. When the parameter is
ON, the PID Gap algorithm calculation is same as the xPM. Users migrating from
xPM controllers to EKPS may choose to enable this option to maintain the same
PID gap behavior as the xPM controller.

14.112 LEGACYINITOPT

Specific to DEVCTL
Block(s)
Description Legacy OP Initialization Option
Data Type Enumeration
Range ENABLE DISABLE
Default DISABLE
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks This option enables the selection between Experion PKS and HPM like behavior for
return from Initialization.
l When LEGACYINITOPT=DISABLE, then the current Experion PKS behavior
will be retained for return from initialization.
l When LEGACYINITOPT=ENABLE, then the HPM like behavior will be used for
return from initialization.
Note: You can modify the LEGACYINITOPT value after loading the strategy. This
enables users to move to the new behavior after migration, where LEGACYINITOPT
is available.

- 1633 -
Chapter 14 - Lxxxx Parameters

14.113 LINEPERD

Specific to Block(s) LLAI


Description Line Period in Microseconds.
Data Type 32-Bit Real Number
Range 15616.0 to 21759.0
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters N/A
Remarks

14.114 LINEARTYPE

Specific to UAI
Block(s)

Description Linear Type


Data Type ENUM
Range
0 4_20_mA

1 0_20_mA

2 0_10_mV

3 0_50_mV

4 0_100_mV

5 -10_10_mV

6 -50_50_mV

7 -100_100_mV

8 -500_500_mV

9 0_1_V

10 0_2_V

11 0_5_V

12 0_10_V

13 1_5_V

14 -1_1_V

15 -2_2_V

16 -5_5_V

17 -10_10_V

- 1634 -
Chapter 14 - Lxxxx Parameters

Default 0 4_20_mA
Config Yes
Load

Active No
Loadable

Access Application Developer


Lock

Residence IOM Block


Related SENSRTYP_AI_C
Parameters

Remarks This parameter defines the type of Linear Signal connected. This parameter is exposed
when SENSRTYP_AI_C is set to LINEAR.
The user is always provided with the list of valid values for the particular AI sensor type.
The user is NEVER shown or given the opportunity to select an invalid value.

14.115 LINKNUM

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Link Number. Shows the link number within the I/O Link Interface Module
(IOLIM).
Data Type 16-Bit Unsigned Integer
Range 1 or 2 See Remarks.
Default 1
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related IOLIFNUM
Parameters
Remarks For the IOLIM platform, this can only be 1 since the hardware only supports one
I/O Link. For the C300 platform, this parameter can be either 1 or 2 representing
the physical IOLINK Interface for either IOLINK1 or IOLINK2.

14.116 LIVEDEVICEINDEX

Specific to C300, PGM and FIM4


Block(s)
Description Live Device index - Indicates the current setting of the Device Index rotary
switches located on the IOTA
Data Type 32-Bit Integer
Range N/A
Default 0

- 1635 -
Chapter 14 - Lxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM
Related IPADDRESS
Parameters
Remarks

14.117 LNNAME

Specific to Block(s) 850 EIM


Description Logical Node Name
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

14.118 LOADFL

Specific to Up / Down Counter Block


Block(s)
Description Load Flag
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related RESETFL, PAUSEFL
Parameters
Remarks If the parameter is set to “TRUE”, output value assumes the input value. For
example, if the input value is 64, the output value also becomes 64.

- 1636 -
Chapter 14 - Lxxxx Parameters

14.119 LOADID

Specific to CPM200, CPM, CPM200S, ACE, SIM-C200, CEEFB, CEEACEFB, CEESIMC200FB,


Block(s) C300, C300SEC, UOC, UOCSEC,CONTROLMODULE, UCM, CEEC300,CEEUOC,
CEECN100, FIM4, FIM4SEC, TC-IAH061, 1756-IF6I, TC-IAH161, 1756-IF16, TC-
IDJ161, 1756-IB16I, TC-IDK161, 1756-IA16I, TC-IDW161, 1756-IM16I, TC-IXL061,
1756-IT6I, TC-IXL062, 1756-IT6I_B, TC-IXR061, 1756-IR6I, TC-OAH061, 1756-
OF6CI, TC-OAV061, 1756-OF6VI, TC-OAV081, 1756-OF8, TC-ODJ161, 1756-OB16I,
TC-ODK161, 1756-OA16I, TC-ORC081, TC-ORC161, TC-IDD321, 1756-IB32, TC-
ODD321, 1756-OB32, TC-IDA161, 1756-IA16, TC-ODA161, 1756-OA16, TC-MUX021,
TC_MUX021, TC-ODX081, 1756-OA8D, TC-ODX161, 1756-OB16D, TC-IDX081, 1756-
IA8D, TC-IDX161, 1756-IB16D, SCM, RCM, TC-PIA082, TC-PIB161, TC-PIL081, TC-
POA081, TC-POB041, 1797-IE8NF, 1797-IBN16, 1797-IRT8, 1797-OE8, 1797-OB4D,
TC-MDP081, 1757-PIM, 1757-CN2FF, TC-FIAH81, TC-FID161, TC-FOA041, TC-
FOD161, TC-FIDA81, TC-FIL081, TC-FIR081, TC-FODA81, TC-FOR081 1794-IA8,
1794-IB16, 1794-IE8, 1794-IR8, 1794-IT8, 1794-OA8, 1794-OB16P, 1794-OE4, 1794-
OW8, PBIM_SST, BIZERBASTDEV, ENCODERDEV, PBI_DEVICE, PROFIDRIVEDEV,
SIMATIC_AI, SIMATIC_AO, SIMATIC_DI, SIMATIC_DO, SIMOCODE3UF5DEV, 1305,
1336-PLUS-II, GENERIC_DRIVE, DNET_IM, DNET_DEVICE, JAGXTERM,
QIPACTERM, TC-HAI081, TC-HAO081, HARTDEVICE, LOGIX1200_0104, ST3000_
0103, ST3000_0202, STT25H_0103.
Description ERDB / Controller load consistency ID
Data Type 32-Bit Integer
Range N/A
Default 0
Config Yes
Load
Active No
Loadable
Access Application Developer Only
Lock
Residence CPM200, CPM200S, ACE, SIM-C200, CEEFB, CEEACEFB, CEESIMC200FB, C300,
C300SEC, UOC, UOCSEC
Related
Parameters
Remarks Used to track consistency between FB configuration in the controller and
monitoring side of DB

14.120 LOADSP

Specific to GRPCAPRBK
Block(s)
Description Load set point Input
Data Type DOUBLE
Range
Default NaN
Config Load NO
Active No
Loadable

- 1637 -
Chapter 14 - Lxxxx Parameters

Access Lock VIEW ONLY


Residence CEE
Related LOADSPSTS
Parameters
Remarks This indicates the desired load set point. This input is compared with Group
capability to decide RUNBACK condition.

14.121 LOADSPCONN

Specific to Block(s) GRPCAPRBK


Description Connection for Load Set point input
Data Type INCONN
Range
Default
Config Load NO
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related LOADSP
Parameters
Remarks Connections for LOADSP parameter to accept an input with both value and
status.

14.122 LOADSPSTS

Specific to Block GRPCAPRBK


(s)
Description Load set point Input status
Data Type Enumeration:PVSTS
Range NORMAL, BAD, MANUAL, UNCERTN
Default BAD
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related LOADSP
Parameters
Remarks Depending on this parameter the LOADSP is considered in the calculation of
rate limit output.

- 1638 -
Chapter 14 - Lxxxx Parameters

14.123 LOADSTATE

Specific to CM, SCM


Block(s)
Description Container block load state.
Data Type Enumeration LOADSTATE
Range LOADFAILED (0) UNLOADED (1) LOADINGPROG (2) LDNGCMPTYPES (3)
CMLOADINGTBR (4) LOADINGCONFIG (5) LOADINGCONN (6) READY (7)
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter is used by container blocks to track the state of load. During normal
operation it progresses to READY by the time of load completion. If an error is
detected during load it stops at LOADFAILED. The only way to get an SCM FB or CM
FB out of the LOADFAILED state is to reload. EXECSTATE cannot be set to Active
until LOADSTATE reaches READY.

Specific to CAB and CDB Types


Block(s)
Description Load State - Identifies the load state of a CAB or CDB instance during load of
program (CAB) or definition (CDB).
Data Type Enumeration
Range Unloaded (0) Loading (1) Loaded (2)
Default Assigned by CAB build-time services at the conclusion of a type edit session.
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Values of this parameter are used for handshaking by the loading agent in Control
Builder or Control Library during the load process. The existence of this parameter
prevents the need to use CABSTATE for handshaking during load of CAB programs.

- 1639 -
Chapter 14 - Lxxxx Parameters

14.124 LOCALCLOSE

Specific to Block(s) VALVEDAMPER


Description Local Close
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters GOP, OP, OPFINAL, OPREQ, LOCALSWITCH.
Remarks Command to CLOSE the valve.

14.125 LOCALMAN

Specific to DevCtl, Pulse Count Control, Pulse Length Control All Drive Control Blocks:
Block(s) HTmotor, LTmotor, Solenoid, ValveDamper
Description Local Manual Input.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock DevCtl: Other Function Block Pulse Count, Pulse Length: Program
Residence CEE
Related GOP, GPV, OP, PV, DevCtl : NUMDINPUTS, NUMDOUTS,
Parameters
Remarks DevCtl: Illegal if NUMDOUTS = 0 or NUMDINPUTS = 0. LOCALMAN can be used to
indicate to the Pulse Length Control function block that the connected device is
being controlled locally and not by the CEE.

14.126 LOCALOPEN

Specific to Block(s) VALVEDAMPER, SOLENOID


Description Local Open
Data Type Boolean
Range ON-OFF
Default OFF

- 1640 -
Chapter 14 - Lxxxx Parameters

Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters GOP, OPOPFINALOPREQLOCALSWITCH
Remarks Command to open the valve.

14.127 LOCALSTART

Specific to Block(s) HTMOTOR, LTMOTOR


Description Local Start
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters GOPOPOPFINALOPREQLOCALSWITCH
Remarks Command to start the motor.

14.128 LOCALSTOP

Specific to Block(s) HTMOTOR, LTMOTOR


Description Local Stop
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters GOPOPOPFINALOPREQLOCALSWITCH
Remarks Command to stop the motor.

- 1641 -
Chapter 14 - Lxxxx Parameters

14.129 LOCALSTOPACTED

Specific to HTMOTOR
Block(s)
Description Local Stop Acted
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related LOCALSTOP RESETFIRSTUP
Parameters
Remarks Indicates that the corresponding command has been issued that has changed
the output state to STOP.

14.130 LOCALSWITCH

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Switch in Local Position
Data Type Boolean
Range OFF ON
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters REMOTESWITCH
Remarks ‘Local’ commands allowed only when LocalSwitch is ON

14.131 LOCATION

Specific to Block(s) Cabinets


Description It provides the physical location (within the plant) where the cabinets are
located.
Data Type String
Range 0 – 255
Default —

- 1642 -
Chapter 14 - Lxxxx Parameters

Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SRAL
Related
Parameters
Remarks

14.132 LOCUTOFF

Specific to DataAcq
Block(s)
Description Low Signal Cutoff - EvaluatesPVAUTO
Data Type 64-Bit Real Number
Range PVEULO to PVEUHI, NaN, Greater-than or equal-to 0. See Remarks
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related PVEUHI, PVEULO, PVCHAR.
Parameters
Remarks When LOCUTOFF is: NaN: no action Non-Nan: when PVAUTO < LOCUTOFF,
PVAUTO is set to PVEULO. Store to this parameter requires CM to be inactive or
CEE in Idle. LOCUTOFF is not applicable if PVCHAR is None.

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Low Cutoff Signal. Specifies the low signal cutoff point for flow inputs.
Data Type 32-Bit Real Number
Range PVEULO to PVEUHI; Greater Than 0
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOM
Related
Parameters
Remarks In PM I/O Channels, LOCUTOFF configuration applies only if PVChar = Linear or
Sqrroot. In Series C I/O AICHANNELs, LOCUTOFF configuration applies if PVChar =
Linear, Sqrroot, DeviceRange, SystemRange, or SystemRangeAndSQRT.

- 1643 -
Chapter 14 - Lxxxx Parameters

14.133 LOGICALENIM

Specific to Block EHPM, TCMI


(s)
Description Device Index of Remote ENIM shows the device index of Remote ENIM.
Data Type INT32
Range 1 to 511
Default None
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related LOGICALENIMIPADDRESS
Parameters
Remarks Device Index of Remote ENIM entered, derives the IP address of Remote ENIM
and sets the path.

14.134 LOGICALENIMIPADDRESS

Specific to Block(s) EHPM, TCMI


Description Remote ENIM IP Address shows the IP address of the Remote ENIM.
Data Type INT32
Range NA
Default None
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence ERDBONLY
Related Parameters LOGICALENIM
Remarks

14.135 LOGICALUCNNW

Specific to Block EHPM, TCMI


(s)
Description UCN Network Number shows the UCN network number of the Remote ENIM.
Data Type INT32
Range 1 to 20
Default None

- 1644 -
Chapter 14 - Lxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock AppDevOnly
Residence ERDBONLY
Related LOGICALENIM
Parameters LOGICALENIMIPADDRESS
LOGIENIMDATEPTIMPORTLOGIENIMIMPORTSTATUS
Remarks

14.136 LOGICINITOPT

Specific to CONTROLMODULE
Block(s)
Description Logic Block Initialization Option
Data Type Enumeration
Range 0 PULSEEXPIRED Logic outputs may turn ON
or pulse as a result of a
state transition, even
though inputs have not
changed.
1 PULSEREADY Supports pre-existing
Control Module
configuration behavior to
remain unchanged across
migration to new releases.
Default PULSEEXPIRED (0)
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related
Parameters
Remarks This parameter affects the behavior of Logic blocks FTRIG, MAXPULSE, MINPULSE,
MVOTE, nooN, OFFDELAY, ONDELAY, PULSE, RTRIG, TRIG, and 2oo3, when they go
through state transitions of activate cold start, warm start, or RAM Retention Restart
(RRR). When LOGICINITOPT is set to PULSEEXPIRED (the default), logic outputs
may turn ON or pulse as a result of a state transition, even though inputs have not
changed. We recommend that the LOGICINITOPT remain at its default value of
PULSEEXPIRED for all new Control Module configurations. The PULSEREADY
value supports pre-existing Control Module configuration behavior to remain
unchanged across migration to new releases. Refer to the given Logic block
description in the Control Builder Components Theory document for more
information.

- 1645 -
Chapter 14 - Lxxxx Parameters

14.137 LOGICGATE1

Specific to HRBALG_REG block


Blocks
Description LOGICGATE1 FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the LOGICGATE1 block in the emulation CM,
which holds the HRBALG_REG instance. This parameter connector is used in an EC
algorithm emulation to read GATE4 value for the Logic algorithm.
Checkpoint Yes

14.138 LOGICGATE2

Specific to HRBALG_REG block


Blocks
Description LOGICGATE2 FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the LOGICGATE2 block in the emulation CM,
which holds the HRBALG_REG instance. This parameter connector is used in an EC
algorithm emulation to read GATE4 value for the Logic algorithm.
Checkpoint Yes

- 1646 -
Chapter 14 - Lxxxx Parameters

14.139 LOGICGATE3

Specific to HRBALG_REG block


Blocks
Description LOGICGATE3 FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the LOGICGATE3 block in the emulation CM,
which holds the HRBALG_REG instance. This parameter connector is used in an EC
algorithm emulation to read GATE4 value for the Logic algorithm.
Checkpoint Yes

14.140 LOGICGATE4

Specific to HRBALG_REG block


Blocks
Description LOGICGATE4 FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Yes
Load
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the LOGICGATE4 block in the emulation CM,
which holds the HRBALG_REG instance. This parameter connector is used in an EC
algorithm emulation to read GATE4 value for the Logic algorithm.
Checkpoint Yes

- 1647 -
Chapter 14 - Lxxxx Parameters

14.141 LOGIENIMDATEPTIMPORT

Specific to EHPM, TCMI


Block(s)
Description Date Of Last Import shows the date of last import of points from the Remote
ENIM to the configured EHPM.
Data Type STRING
Range NA
Default None
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence SRAL
Related
Parameters
Remarks

14.142 LOGIENIMIMPORTSTATUS

Specific to EHPM, TCMI


Block(s)
Description Import Status shows the import status for the EHPM point import from remote
login to the EHPM. Once the EHPM point import is complete, it shows import status
as “Completed”.
Data Type STRING
Range NA
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SRAL
Related
Parameters
Remarks

- 1648 -
Chapter 14 - Lxxxx Parameters

14.143 LOLMRAMPRATE

Specific to PID-PL
Block(s)
Description Low Limit Ramp Rate, in Engineering Units/Minute - Sets the rate at which the
Active low limit ramps toward a new LO LIMIT.
Data Type Float64
Range 0
Because a zero ramp rate would prevent convergence to the operator-set limit, it is
re-interpreted as an infinite rate.
Default NaN
Config Load
Active No
Loadable
Access Lock Engineer
Residence
Related HILMRAMPRATE
Parameters
Remarks Whenever the Active high limit is above the operator-set limit, the Active limit ramps
toward the new limit at this specified rate. The operator-set high limit is:
l SPLOLM for range control
l SP for setpoint control

14.144 LOOKAHEAD

Specific to SCM, RCM


Block(s)
Description Look Ahead Algorithm for Dynamic Fetch
Data Type Enumeration
Range 0 None No Look ahead , backward
compatible with R310 and
before

1 Simple Straight forward look


ahead only (non-
branching ).
2 Full Complex look ahead for
lowest latency
Default None (0)
Config Yes
Load
Active No
Loadable

- 1649 -
Chapter 14 - Lxxxx Parameters

Access Application Developer Only


Lock
Residence CEE
Related PEERALGOPT, DYNPEERALLOC, PERIOD, PEERAGETIME
Parameters
Remarks This parameter shall only be adjusted by advanced engineers understanding the
impact at system level and with respect to the user defined functionality of the
SCM/RCM. LOOKAHEAD can only be configured if PEERALGOPT<>NONE and
DYNPEERALLOC=YES. This parameter allows to trade system resource
consumption (CEE memory, peer communication load) against latency times. Any
change of this parameter - especially if applied to multiple or all SCMs/RCMs - will
most likely have significant impact on: CEE memory consumption , Peer
communication load (including OPC if used) and observed latency times in
SCMs/RCMs using peer or OPC data. If the SCM/RCM uses local CEE data only
(including I/O connected directly to this controller) , this parameter has no impact
whatsoever, because Dynamic Fetch is not applicable to local communication. More
detailed information can be found in the Sequential Control User Guide in the
Section “Dynamic Fetch”

14.145 LOOPADDR

Specific to PCDI_MASTER
Block(s)
Description Loop Address
Data Type 32-Bit Unsigned Integer
Range 1 to 999999
Default 1
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related UIDLOOPADDR[0..15]
Parameters
Remarks This parameter represents the default address used to read or write a diagnostic
request to a slave device. This parameter value can be overridden by the
UIDLOOPADDR parameter for an individual device.

14.146 LOOPCOUNT

Specific to PHASE, STEP


Block(s)
Description Loop Counter
Data Type 32-Bit Integer
Range 0..32000

- 1650 -
Chapter 14 - Lxxxx Parameters

Default 0
Config No
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Will be incremented on any activation of the block. If the maximum value (32,000) is
reached, the block will stop counting without any warning or error. This means any
more increments will not be visible to the user. Will be reset on SCM/RCM reset.

14.147 LOOPDATA

Specific to PCDI_MASTER
Block(s)
Description Loop Data
Data Type String
Range 8 Characters
Default 0xA5A5
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related UIDLOOPDATA[0..15]
Parameters
Remarks This parameter represents the data value written to diagnostic request to slave
devices LOOPADDR. This parameter value can be overridden by the UIDLOOPDATA
parameter for an individual device.

14.148 LOOPDATACHG

Specific to PCDI_MASTER
Block(s)
Description Loop Data Change
Data Type Enumeration
Range 0 Use Use default is only an option for override
Default values in an individual device.
1 No The value is not modified from the read
Change result. The original value supplied to
LOOPDATA is re-used for the next diagnostic
request.

- 1651 -
Chapter 14 - Lxxxx Parameters

2 Invert Inverts the data value read from a diagnostic


request for numeric arrays (integer values
are decremented). Flag arrays are toggled.
Text arrays have each printable character
inverted.
3 Increment Increments the data value read from a
diagnostic request for numeric arrays. Flag
values are toggled. Text arrays have each
printable character incremented.
4 Any Value The value is not modified from the read
result.
Default No Change
Config Yes
Load
Active No
Loadable
Access Engineer/Application Developer
Lock
Residence CEE
Related UIDLOOPDATACHG[0..15]
Parameters
Remarks This parameter value
can be overridden by the
UIDLOOPDATACHG for
an individual device.

14.149 LOOPMODE

Specific to PCDI_MASTER
Block(s)
Description Loop Test Mode
Data Type Enumeration
Range 0 Use Use default is only an option for override values in an
Default individual device
1 Read Only The diagnostic request only reads values. Writes are not
performed.
2 Write/Read The diagnostic loop first writes then reads to/from the
individual device. If a prior request completed or failed, a
diagnostic write request will be sent to the slave device.
Otherwise, a diagnostic read request will be sent out.
Default Read Only
Config Yes
Load
Active No
Loadable

- 1652 -
Chapter 14 - Lxxxx Parameters

Access Lock Engineer/Application Developer


Residence CEE
Related UIDLOOPMODE[0..15]
Parameters
Remarks This parameter value can be overridden by the UIDLOOPMODE for an individual
device.

14.150 LOOPRATE

Specific to PCDI_MASTER
Block(s)
Description Loop Rate in milliseconds
Data Type 32-Bit Unsigned Integer
Range 50 to 900000
Default Native MODBUS TCP Device: 1000 Safety Manager: 1500
Config Yes
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related UIDLOOPRATE[0..15]
Parameters
Remarks The time between testing each end device in milliseconds. The PCDI Master will
check the diagnostics between the master and slave devices every LOOPRATE
period. This parameter value can be overridden by the UIDLOOPRATE for an
individual device.

14.151 LOOPTYPE

Specific to PCDI_MASTER
Block(s)
Description Loop Type
Data Type Enumeration
Range 0 Use Default Used to set the value for
UIDLOOPTYPE parameters
to use the LOOPTYPE
setting. This value is not
visible for LOOPTYPE.
1 Diag Loopback The diagnostic commands
are used. The output value
will have the same value as
the input.
2 Exception Status The exception status is
being read.

- 1653 -
Chapter 14 - Lxxxx Parameters

3 Comm Event Log Reads from the Comm


Event Log
4 Coil A coil is being used for the
diagnostics.
5 Discrete Input A discrete input is being
used
6 Holding Reg A holding register is being
used for the diagnostic
loopback.
7 Input Reg An input register is being
used for the diagnostic
loopback.
8 Diag Register
Default Diag Loopback
Config Yes
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related UIDLOOPTYPE[0..15]
Parameters
Remarks This parameter describes what type of read/write operation will be done. The
supported commands for a device must support the loop type selected. For
example, a loop type of Coil must have 0x01 (read coil) selected. Use Default setting
is only an option for override values in an individual device. This parameter value
can be overridden by the UIDLOOPTYPE for an individual device.

14.152 LOSTKNDROP

Specific to Block(s) C200 IOLINK, C300 IOLINK


Description Token Drop Count. Displays the number of Token Pass drops on the I/O
Link.
Data Type 16-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related Parameters
Remarks

- 1654 -
Chapter 14 - Lxxxx Parameters

14.153 LOWENG[0..numChans-1]

Specific to AIM, AOM LOWENG is configurable only on the AIM.


Block(s)
Description Low Engineering - Specifies the value that represents the minimum limit for the
output.
Data Type 64-Bit Real Number
Range NaN, less-than HIGHENG
Default 0.0
Config Load AIM: Yes AOM: No
Active No
Loadable
Access Lock AIM: Application Developer AOM: ViewOnly
Residence CEE
Related HIGHENG[0..numChans-1]
Parameters
Remarks If the user program tries to set an output value outside the specified limit, the
output will be clipped at the limit and an alarm bit is set. Clamp value is specified in
Engineering Units.

14.154 LOWENG[0..7]

Specific to Block(s) Chassis HART AI IOM, HART AO IOM


Description Low Engineering Value
Data Type Float64
Range NaN, less than HIGHENG
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters HIGHENG[0..7]
Remarks

14.155 LOWERDEADTM

Specific to Block(s) PosProp, PidPosProp


Description Lower Dead Time (in seconds).
Data Type Real
Range N/A

- 1655 -
Chapter 14 - Lxxxx Parameters

Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

14.156 LOWERDESC

Specific to Block(s) PosProp, PidPosProp


Description Lower Output Descriptor.
Data Type String
Range N/A
Default “Lower”
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters
Remarks

14.157 LOWERLMFL

Specific to PosProp, PidPosProp


Block(s)
Description Lower Pulse Limit Flag - Used to inhibit lower pulses by the PosProp function
block and is pulled from another function block.
Data Type Boolean
Range Off (0) - Allow lower pulse output. On (1) - Inhibit lower pulse output.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

- 1656 -
Chapter 14 - Lxxxx Parameters

14.158 LOWERRATE

Specific to Block(s) PosProp, PidPosProp


Description Lower Output Stroke Rate (in percent per second).
Data Type Real
Range 0.0 to 100.0
Default 100.0% per second
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

14.159 LOWERTIME

Specific to Block(s) PosProp, PidPosProp


Description Lower Output Pulse Time (in seconds).
Data Type Real
Range MINPULSEL, lesser of MAXPULSEL, and CYCLETIME.
Default N/A
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks If LOWERTIME < MINPULSEL, no pulse is issued.

14.160 LOWSIGNAL[0..numChans-1]

Specific to AIM, AOM


Block(s)
Description Low Signal
Data Type 64-Bit Real Number
Range
Default See Remarks below.
Config Load No
Active No
Loadable

- 1657 -
Chapter 14 - Lxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related HIGHSIGNAL[0..numChans-1]INPUTRANGE[0..numChans-1], SIPTYPE
Parameters [0..numChans-1]
Remarks For AIMs, this parameter is set within the controller based on the store of
INPUTRANGE. For AOMs, this parameter is set within the controller based on the
store of SIPTYPE.

14.161 LOWSIGNAL[0..7]

Specific to Chassis HART AI IOM


Block(s)
Description Low Signal Value
Data Type Float64
Range
Default See Remarks below.
Config Load Yes.
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related INPUTRANGE[0..7]HIGHSIGNAL[0..7]
Parameters
Remarks This parameter is set within the controller and is based on the store of
INPUTRANGE (voltage or current mode). LOWSIGNAL is not configured if the HART
parameter is selected for the channel.

Specific to Chassis HART AO IOM


Block(s)
Description Low Signal Value
Data Type Float64
Range
Default See Remarks below.
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related HIGHSIGNAL[0..7], SIPTYPE[0..7]
Parameters
Remarks This parameter is set within the controller and is based on the value of SIPTYPE
(Voltage or Current mode). LOWSIGNAL is not configured if the HART is selected for
the channel.

- 1658 -
Chapter 14 - Lxxxx Parameters

14.162 LRL

Specific to AICHANNEL, HAICHANNEL (PM I/O), AICHANNEL (Series C I/O), PM I/O HART
Block(s) Channels
Description For AICHANNEL: Lower Range Limit. Specifies the lower range limit of the Process
Variable (PV) measurement at the Smart Transmitter. The Engineering Units are
defined by the STI_EU parameter. For HAICHANNEL: PV Extended Low Range.
Indicates the lower range limit of the PV at the HART device.
Data Type 32-Bit Real Number
Range N/A
Default NaN
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related STI_EU, for AICHANNEL HTDLRL for HAICHANNEL (PM I/O)
Parameters
Remarks For AICHANNEL: This parameter is only exposed if ASSOCIOPTYP is STI-MV. It is set
at the factory, according to transmitter type, and cannot be changed. For
HAICHANNEL: This parameter is exposed only if HENABLE is TRUE. The same
value as HTDLRL. Two parameters are used in order to show the limits on two
different tabs of the same configuration form.

14.163 LRL HART

Description Lower Range Limit. Indicates the lower range limit of the PV at the HART device.
This limit is fixed and cannot be changed.
Data Type Real
Range N/A
Access Read Only
Lock
Default NaN
Residence EHPM

14.164 LRR

Specific to Block(s) HTMOTOR


Description Lockout Relay Reset
Data Type Boolean
Range ON-OFF
Default ON

- 1659 -
Chapter 14 - Lxxxx Parameters

Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters LRRACTED
Remarks Used as permissive and protective interlock.

14.165 LRRACTED

Specific to Block(s) HTMOTOR


Description LRR acted
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock View only
Residence CEE
Related Parameters LRR RESETFIRSTUP
Remarks Used as permissive and protective interlock.

14.166 LRRALM.FL

Specific to Block(s) HTMOTOR


Description Lockout Relay Reset alarm flag
Data Type Boolean
Range ON-OFF
Default ON
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters LRRALM.OPTLRRALM.PRLRRALM.SV
Remarks

- 1660 -
Chapter 14 - Lxxxx Parameters

14.167 LRRALM.OPT

Specific to Block(s) HTMOTOR


Description Lockout Relay Reset alarm option
Data Type Enumeration
Range ENABLE DISABLE
Default ENABLE
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters LRRALM.FLLRRALM.PRLRRALM.SV
Remarks

14.168 LRRALM.PR

Specific to Block(s) HTMOTOR


Description Lockout Relay Reset alarm priority
Data Type Boolean
Range NONE JOURNAL LOW HIGH URGENT
Default LOW
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters LRRALM.FLLRRALM.OPTLRRALM.SV
Remarks

14.169 LRRALM.SV

Specific to Block(s) HTMOTOR


Description Lockout Relay Reset alarm severity
Data Type 16-Bit Integer
Range 0-15
Default 0
Config Load YES
Active Loadable No

- 1661 -
Chapter 14 - Lxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters LRRALM.FLLRRALM.OPTLRRALM.PR
Remarks

14.170 LRV

Specific to AICHANNEL, HAICHANNEL (PM I/O) ; AICHANNEL (Series C I/O)


Block(s)
Description For AICHANNEL: Lower Range Value. Defines the lower end of the operating range
for the PVRAW input value. The Engineering Units are defined by the STI_EU
parameter. For HAICHANNEL: PV Low Range (4mA). Indicates the lower range limit
of the operating range for PVRAW.
Data Type 32-Bit Real Number
Range N/A
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence IOM
Related STIDBDISCRE, STI_EU, for AICHANNEL
Parameters
Remarks For AICHANNEL: This parameter is exposed only if ASSOCIOPTYP is STI-MV. It is a
view-only parameter when the STI point execution state PTEXECST is Active. For
HAICHANNEL: This parameter is exposed only if HENABLE is TRUE. The same
value as HPVLRV. Two parameters are used in order to show the limits on two
different tabs of the same configuration form.

14.171 LRV HART

Description Lower Range Value. Defines the lower end of the operating range for the PVRAW
value. User entry for PVEULO is the user - entered engineering - unit value that
corresponds to LRV.
Data Type Real
Range N/A
Access Read Only
Lock
Default NaN
Residence EHPM

- 1662 -
Chapter 14 - Lxxxx Parameters

14.172 LSCYCLEOVRN[0...40]

Specific to CEE, CEEC300, IOLINK, CEEUOC


Block(s)
Description Count of Cycle Overruns in Last Hour
Data Type 16-Bit Integer
Range 0 to 32,767
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC)
Related CPVALIDSAVESTATESSZ
Parameters CPVALIDRESTSTATESCPVALIDRESTSTATESSZCRCYCLEOVRN[0..40]
Remarks Each element gives a count of cycle overruns that have occurred during the
previous hour. Elements 0…39 give the count for the corresponding cycle. Element
40 gives the total count over all cycles. Ass elements are copied from
CRCYCLEOVRN [0...39] once an hour. Copy occurs at the same time that
CRCYCLEOVRN [0...39] is reset. It is not synchronized with wall clock time.

Specific to CEECN100
Block(s)
Description Previous Hr Cycle Overruns
Data Type 16-Bit Integer
Range 0 to 32,767
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CN100(CEECN100)
Related CRCYCLEOVRN[0..50]
Parameters
Remarks Each element gives a count of cycle overruns that have occurred during the
previous hour. Elements 0…49 give the count for the corresponding cycle. Element
50 gives the total count over all cycles. Ass elements are copied from
CRCYCLEOVRN [0...49] once an hour. Copy occurs at the same time that
CRCYCLEOVRN [0...49] is reset. It is not synchronized with wall clock time.

- 1663 -
Chapter 14 - Lxxxx Parameters

14.173 LSCYCLESKIP[0..40]

Specific to CEEC300, CEEC200EFB


Block(s)
Description The number of cancelled cycles for Control recipe executions at the last hour.
Data Type INT32
Range 0 to 32767
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200E(CEEC200EFB)
Related CRCYCLESKIP[0..40]
Parameters
Remarks Each element gives a count of Control recipe executions skipped in the last hour.
Elements 0 to 39 give the count for the corresponding cycle. Element 40 gives the
total count over all cycles. All elements are updated with CRCYCLESKIP[0..40] once
in an hour. The time is not synchronized with the current time.

14.174 LSCYCLESKIP

Specific to CEEFB, CEEC300, CEEACE, CEESIMC200E, CEEUOC, CEECN100


Block(s)
Description The number of canceled cycles for Control recipe executions at the last hour.
Data Type INT32
Range 0 to 32767
Default 0
Config Load No
Active No
Loadable
Access ViewOnly
Lock
Residence C300(CEEC300), C200E(CEEC200EFB), UOC(CEEUOC), CN100(CEECN100)
Related CRCYCLESKIP[0..40]
Parameters
Remarks Each element gives a count of Control recipe executions skipped in the last hour.
Elements 0 to 39 give the count for the corresponding cycle. Element 40 gives the
total count over all cycles. All elements are updated with CRCYCLESKIP[0..40] once in
an hour. The time is not synchronized with the current time.

- 1664 -
Chapter 14 - Lxxxx Parameters

14.175 LSSKIPERIOD

Specific to CEEFB, CEEC300, CEEACE, CEESIMC200E, CEEUOC


Block(s)
Description The highest execution period affected by the Control recipe limited for the last hour.
Data Type ENUM -PERIOD
Range Enum values of Period enumeration (0 – 31)
Default Default
Config Load No
Active No
Loadable
Access ViewOnly
Lock
Residence C300(CEEC300), C200E(CEEC200EFB), UOC(CEEUOC)
Related CRSKIPPERIOD[0..40]
Parameters
Remarks EEach element gives the value of the period for which Control recipe execution
skipped in the current hour. Elements 0 to 39 give the value of the period for which
Control recipe execution skipped. Element 40 gives the maximum value of the period
for which the Control recipe execution skipped over all cycles. All elements are
updated from CRSKIPPERIOD[0..40] once in an hour. Time is not synchronized with
the current time.

14.176 LSSKIPPERIOD[0..40]

Specific to CEE, CEEC300, CEEUOC


Block(s)

Description Count of Cycle Overruns in Last Hour


Data Type 16-Bit Integer
Range 0 to 32,767
Default 0
Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence C200(CEE), C300(CEEC300), UOC(CEEUOC)


Related CRCYCLEOVRN [0…40]
Parameters

Remarks Each element gives a count of cycle overruns that have occurred during the previous
hour. Elements 0…39 give the count for the corresponding cycle. Element 40 gives the
total count over all cycles. Ass elements are copied from CRCYCLEOVRN [0...40] once an
hour. Copy occurs at the same time that CRCYCLEOVRN [0...40] is reset. It is not
synchronized with wall clock time.

- 1665 -
Chapter 14 - Lxxxx Parameters

14.177 LSTHRERRFIFOENTRY

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Last Hour Error FIFO Entries
Data Type UINT32
Range
Default 0
Config. Load No
Active Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter displays the number of error entries reported by EHBI in the
last hour.

14.178 LSTHRRCVFIFOENTRY

Specific to Experion Hiway Bridge (EHB) platform block


Blocks
Description Last Hour Receive FIFO Entries
Data Type UINT32
Range
Default 0
Config. Load No
Active
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter displays the number of receive FIFO (unsolicited writes) entries
reported by EHBI in the current hour.

14.179 LSTHRRPTFIFOENTRY

Specific to Blocks Experion Hiway Bridge (EHB) platform block


Description Last Hour Report FIFO Entries
Data Type UINT32
Range

- 1666 -
Chapter 14 - Lxxxx Parameters

Default 0
Config. Load No
Active Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter displays the number of report entries generated by EHBI in
the last hour.

14.180 LTC

Specific to Block(s) VALVEDAMPER, SOLENOID


Description Limit Close
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters LTO
Remarks Used as feedback to find the current status of valve is open or not

14.181 LTO

Specific to Block(s) VALVEDAMPER, SOLENOID


Description Limit Open
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters LSCYCLESKIP[0..40]
Remarks Used as feedback to find the current status of valve is open or not

- 1667 -
CHAPTER

15 MXXXX PARAMETERS

15.1 MACADDRA 1677


15.2 MACADDRB 1678
15.3 MACADDRR 1678
15.4 MAINCLOSEFDBK 1678
15.5 MAINCLOSEFDBKSTS 1679
15.6 MAINTAINONFAULT 1679
15.7 MAINTOPT 1680

15.8 MAINVLVFDBKTO 1680


15.9 MAJ 1681
15.10 MAJORREV 1681
15.11 MAJRECFAULT 1682
15.12 MAJURECFAULT 1682
15.13 MANPULSECMD 1683
15.14 MANPULSETIME 1683
15.15 MANUALMODE[1..24] 1684
15.16 MANUALMODE[1..200] 1684
15.17 MANUFACTURER 1685
15.18 MASTERID 1685
15.19 MASTERSTATE 1686
15.20 MATERIALPATH[1..200] 1689
15.21 MATRIKON_OPC_ABPLUGIN 1689
15.22 MATRIKON_OPC_HOST 1690
15.23 MATRIKON_OPC_PLC 1690
15.24 MATRIKON_OPC_PROGID 1691
15.25 MAX 1691
15.26 MAX_D 1692
15.27 MAX_N_S 1692
15.28 MAX_N_SJL 1692
15.29 MAX_N_SS 1693
15.30 MAXACTPERIOD 1693
15.31 MAXBLKTYPES 1694
15.32 MAXBROWSEP 1694

- 1668 -
Chapter 15 - Mxxxx Parameters

15.33 MAXBROWSER 1695


15.34 MAXCABTYPES 1695
15.35 MAXCACHEVAR 1696
15.36 MAXCDDMTYPES 1696
15.37 MaxConfigSize 1697
15.38 MAXCYCLE 1697
15.39 MAXDEADTIME 1698
15.40 MAXDEPTH 1698
15.41 MAXDEVICEINDEX 1698
15.42 MAXFREEBLKSZ 1699
15.43 MAXFREEINK 1699
15.44 MAXFTENODES 1700
15.45 MAXGPSSKEW 1701
15.46 MAXHISOAKDEV[1..NUMPROFILES] 1701

15.47 MAXICPNAKS 1702


15.48 MAXICPSENDS 1702
15.49 MAXIMR 1703
15.50 MaxIntervalsInInit 1703
15.51 MAXLOSOAKDEV[1..NUMPROFILES] 1704
15.52 MAXMINRATIO 1704
15.53 MAXMONITOR 1705
15.54 MAXMONPERSUBSCR 1705
15.55 MAXMONPERSESS 1705
15.56 MAXNODEID 1706
15.57 MAXNOOFBLOCKS 1707
15.58 MAXNOOFFTENODES 1708
15.59 MAXNUMACT 1708
15.60 MAXOWNERS 1708
15.61 MAXPCOVERRUN 1709
15.62 MAXPENDREQ 1709
15.63 MAXPTPFASTSKEW 1710
15.64 MAXPTPSLOWSKEW 1710
15.65 MAXPUBLISH 1711
15.66 MAXPULSEL 1711
15.67 MAXPULSER 1712
15.68 MAXRCMSUSED 1712
15.69 MAXREQUEST 1712
15.70 MAXRESOURCES 1713
15.71 MAXRFBDEV 1713

- 1669 -
Chapter 15 - Mxxxx Parameters

15.72 MAXRAMPDEV[1..NUMPROFILES] 1714


15.73 MAXSESSION 1714
15.74 MAXSESSIONSPC 1714
15.75 MAXSESSIONTO 1715
15.76 MAXSNTPSKEW 1715
15.77 MAXSNODESBROWSE 1716
15.78 MAXSUBSCRC 1716
15.79 MAXSUBSCRLT 1716
15.80 MAXSUBSCRPERSESS 1717
15.81 MAXRCVBYTESPERSEC 1717
15.82 MAXRCVMSGPERSEC 1718
15.83 MAXRXPKTRATE 1718
15.84 MAXSOAKVAL[1..NUMPROFILES] 1718
15.85 MAXSTACK 1719

15.86 MAXTIME 1719


15.87 MAXTIME[0..2] 1720
15.88 MAXTIMEFL 1720
15.89 MAXTRANS[0..2] 1721
15.90 MAXUIDREQ 1721
15.91 MAXXMITBYTESPERSEC 1721
15.92 MAXXMITMSGPERSEC 1722
15.93 MBERRCNT[0..15] 1722
15.94 MBERRFL[0..15] 1723
15.95 MBTCPFREEBUFCOUNT 1723
15.96 MBTCPINVALIDRCVMSGCOUNT 1723
15.97 MEANINGPRI[0..15] 1724
15.98 MEANINGSEC[0..15] 1724
15.99 MEDIADEADA 1725
15.100 MEDIADEADB 1725
15.101 MEDIADEADAV 1726
15.102 MEDOPT 1726
15.103 MEM1CR 1726
15.104 MEMALLCR 1727
15.105 MEMFREEAVG 1727
15.106 MEMFREECRIT 1728
15.107 MEMFREECRITLM 1728
15.108 MEMFREELOWLM 1729
15.109 MEMFREEMIN 1729
15.110 MESSAGE[0..15] 1729

- 1670 -
Chapter 15 - Mxxxx Parameters

15.111 MIN 1730


15.112 MINALIVE 1730
15.113 MINHWREVSF 1731
15.114 MINLVLSECSIG[0..15] 1731
15.115 MINORREV 1732
15.116 MINPUBLISH 1732
15.117 MINPULSEL 1732
15.118 MINPULSER 1733
15.119 MINRECFAULT 1733
15.120 MINSOAKVAL[1..NUMPROFILES] 1734
15.121 MINSESSIONTO 1734
15.122 MINSUBSCRIPTION 1735
15.123 MINTIME 1735
15.124 MINURECFAULT 1735

15.125 MINUTE 1736


15.126 MMSRPS 1736
15.127 MMSSTORERPS 1737
15.128 MODCOMPATA 1737
15.129 MODDIF 1738
15.130 MODE 1738
15.131 MODE 1739
15.132 MODE 1740
15.133 MODE 1740
15.134 MODEAPPL[1..4] 1741
15.135 MODEATTR 1742
15.136 MODEATTR 1742
15.137 MODEATTR 1743
15.138 MODEATTR 1745
15.139 MODEATTR 1745
15.140 MODEATTRCHGFL 1746
15.141 MODEATTRFL.NORM 1747
15.142 MODEATTRFL.OPER 1747
15.143 MODEATTRFL.PROG 1748
15.144 MODEATTRREF 1749
15.145 MODECHANGE 1749
15.146 MODEFL.AUTO 1750
15.147 MODEEM 1750
15.148 MODEFL.BCAS 1751
15.149 MODEFL.CAS 1751

- 1671 -
Chapter 15 - Mxxxx Parameters

15.150 MODEFL.MAN 1752


15.151 MODEFL.NORM 1752
15.152 MODELINDEX 1753
15.153 MODELISVALID 1753
15.154 MODELNAME 1753
15.155 MODELNUM 1754
15.156 MODELPV 1755
15.157 MODELUPDATED 1755
15.158 MODELXM_BLOB 1756
15.159 MODELXM_BLOB_NUMBER_OF_BYTES 1756
15.160 MODELXM_BLOB_SIZE 1756
15.161 MODELXS_BLOB 1757
15.162 MODELXS_BLOB_NUMBER_OF_BYTES 1757
15.163 MODELXS_BLOB_SIZE 1758

15.164 MODEOUT 1758


15.165 MODEPERM 1759
15.166 MODEPERM 1759
15.167 MODE POLICING 1760
15.168 MODEREQ 1760
15.169 MODESEL.AUTO 1761
15.170 MODESEL.BCAS 1761
15.171 MODESEL.CAS 1762
15.172 MODESEL.MAN 1762
15.173 MODESEL.PROGRAM 1763
15.174 MODETRACK 1763
15.175 MODETRACK 1764
15.176 MODHASBKUP 1765
15.177 MODIFIEDBY 1766
15.178 MODISREDUN 1766
15.179 MODSTATE 1767
15.180 MODTYPE 1767
15.181 MODTYPEA 1769
15.182 MOMSTATE 1769
15.183 MONACTCMD 1770
15.184 MONCMDPARAM 1771
15.185 MONINACTCMD 1772
15.186 MONLDCMD 1773
15.187 MONREADLDUI 1773
15.188 MONREADPARAM 1773

- 1672 -
Chapter 15 - Mxxxx Parameters

15.189 MONRQDLD 1774


15.190 MONSTATES 1775
15.191 MONTASKREF 1775
15.192 MONTH 1776
15.193 MOTIONBIT[1..4] 1776
15.194 MOTORTRIPALM.FL 1777
15.195 MOTORTRIPALM.OPT 1777
15.196 MOTORTRIPALM.PR 1777
15.197 MOTORTRIPALM.SV 1778
15.198 MPCFREEMEM 1778
15.199 MPCFREEMEMINK 1779
15.200 MPCMAXFREEBLKSZ 1779
15.201 MPCMAXFREEINK 1780
15.202 MPCNTOTMEMDESC 1780

15.203 MPCNUMFREEBLKS 1781


15.204 MPCNUMFREEDESC 1781
15.205 MPCNUMREGDESC 1782
15.206 MPCNUMUSEDBLKS 1782
15.207 MPCNUMUSEDDESC 1783
15.208 MPCTOTALMEM 1783
15.209 MPCTOTALMEMINK 1784
15.210 MPCUSEDMEM 1784
15.211 MPCUSEDMEMINK 1785
15.212 MPVEM 1785
15.213 MSGBUFPEAKPCT 1786
15.214 MSGDATAFMT [0…15] 1786
15.215 MSGDATASRC [0…15] 1787
15.216 MSGDELAY 1787
15.217 MSGSEQNUMBER[1..200] 1788
15.218 MSGTYPE[0..15] 1788
15.219 MTR 1789
15.220 MTRSRC 1789
15.221 MTS 1789
15.222 MTT 1790
15.223 MTTACTED 1790
15.224 MULREDUNSTAT 1791
15.225 MULTIINPTDESC 1791
15.226 MUXSEL 1792
15.227 MV.ACHIEVABLEHL 1792

- 1673 -
Chapter 15 - Mxxxx Parameters

15.228 MV.ACHIEVABLELL 1792


15.229 MV.ACTHL 1793
15.230 MV.ACTIVEMAXMOVEDOWN 1793
15.231 MV.ACTIVEMAXMOVEUP 1794
15.232 MV.ACTIVEVAL 1794
15.233 MV.ACTLL 1794
15.234 MV.ADDITIONALANTIWINDUPMOVE 1795
15.235 MV.BIAS 1795
15.236 MV.CALCBLKINTERVALS 1796
15.237 MV.CALCRESOLUTION 1796
15.238 MV.CASSTATUS 1796
15.239 MV.CONSTRAINTTYPEENUM 1797
15.240 MV.CONTROLHORIZON 1797
15.241 MV.CONTROLMOVE 1798

15.242 MV.CRITICAL 1798


15.243 MV.CTLCVINDEX1 1798
15.244 MV.CTLCVINDEX2 1799
15.245 MV.CURRENTMOVE 1799
15.246 MV.CURRENTMOVEIFON 1800
15.247 MV.DELTAACTSOFTHL 1800
15.248 MV.DELTAACTSOFTLL 1800
15.249 MV.DELTASOFTHL 1801
15.250 MV.DELTASOFTLL 1801
15.251 MV.DESC 1802
15.252 MV.DESIREDVAL 1802
15.253 MV.ENGGHL 1802
15.254 MV.ENGGLL 1803
15.255 MV.ENGGUNITS 1803
15.256 MV.EXCITESIGNAL 1804
15.257 MV.EXECSTATUS 1804
15.258 MV.FUTUREVAL_C 1804
15.259 MV.FUTUREVALUE 1805
15.260 MV.HELDINJECTEDSIGNALVAL 1805
15.261 MV.HIGHLIMIT 1806
15.262 MV.HLRAMP 1806
15.263 MV.HLRAMPRATE 1806
15.264 MV.INITCOUNT 1807
15.265 MV.INITINTERVALS 1807
15.266 MV.INJECTEDSIGNAL 1808

- 1674 -
Chapter 15 - Mxxxx Parameters

15.267 MV.INTERACTIONMOVE 1808


15.268 MV.INTERNALWINDUPRATIO 1808
15.269 MV.ISCONTROLLABLE 1809
15.270 MV.ITRCVINDEX1 1809
15.271 MV.ITRCVINDEX2 1810
15.272 MV.LASTSTATUS 1810
15.273 MV.LINEARCOEFF 1810
15.274 MV.LINEARCOEFF_C 1811
15.275 MV.LLRAMP 1811
15.276 MV.LLRAMPRATE 1812
15.277 MV.LOWLIMIT 1812
15.278 MV.MANACTION 1812
15.279 MV.MAXMOVEDOWN 1813
15.280 MV.MAXMOVEUP 1813

15.281 MV.MOVE_CTLCVINDEX1 1814


15.282 MV.MOVE_CTLCVINDEX2 1814
15.283 MV.MOVE_ITRCVINDEX1 1814
15.284 MV.MOVE_ITRCVINDEX2 1815
15.285 MV.MVINDEX 1815
15.286 MV.MVINDEX_C 1816
15.287 MV.NAME 1816
15.288 MV.NOOFBLKS 1816
15.289 MV.OP_MAX_X 1817
15.290 MV.OP_MIN_X 1817
15.291 MV.OPHIGHTRANSITION 1818
15.292 MV.OPHIGHWINDUP 1818
15.293 MV.OPLOWTRANSITION 1818
15.294 MV.OPLOWWINDUP 1819
15.295 MV.OPPROCESSHL 1819
15.296 MV.OPPROCESSLL 1820
15.297 MV.OPPVFILTERCOEF 1820
15.298 MV.OPTCVINDEX 1820
15.299 MV.OPTIMIZATIONMOVE 1821
15.300 MV.OPTOPVGAIN 1821
15.301 MV.OPTPRIORITY 1822
15.302 MV.OPVAL 1822
15.303 MV.OPVALUE 1822
15.304 MV.PERCENT_CTLMOVE 1823
15.305 MV.PERCENT_ITRMOVE 1823

- 1675 -
Chapter 15 - Mxxxx Parameters

15.306 MV.PERCENT_OPTMOVE 1824


15.307 MV.PERCENTMOVE_CTLCVINDEX1 1824
15.308 MV.PERCENTMOVE_CTLCVINDEX2 1824
15.309 MV.PERCENTMOVE_ITRCVINDEX1 1825
15.310 MV.PERCENTMOVE_ITRCVINDEX2 1825
15.311 MV.PIDMODE 1826
15.312 MV.PREDICTEDPV 1826
15.313 MV.PREVIOUSVAL 1826
15.314 MV.PROCESSHL 1827
15.315 MV.PROCESSLL 1827
15.316 MV.PV_MAX_Y 1828
15.317 MV.PV_MIN_Y 1828
15.318 MV.PVNOISEGAP 1828
15.319 MV.PVTRACK 1829

15.320 MV.PVTRACKENUM 1829


15.321 MV.PVVAL 1830
15.322 MV.QUADRATICCOEFF 1830
15.323 MV.READPROCESSVAL 1830
15.324 MV.READVAL 1831
15.325 MV.RESOLUTION 1831
15.326 MV.RESOLUTIONMISMATCH 1832
15.327 MV.RESOLUTIONRESIDUAL 1832
15.328 MV.SCALINGFACTOR 1832
15.329 MV.SENTVALUE 1833
15.330 MV.SENTVALUEIFON 1833
15.331 MV.SHADOWPRICE 1834
15.332 MV.SSMOVEMAINCAUSE 1834
15.333 MV.SSMOVEMAINCV 1834
15.334 MV.SSVALUE 1835
15.335 MV.SSVALUE_C 1835
15.336 MV.STARTVALUE 1836
15.337 MV.STATUS 1836
15.338 MV.STATUSDISP_C 1836
15.339 MV.STATUSDISPLAY 1837
15.340 MV.STEPINPROGRESS 1837
15.341 MV.TOTALSSMOVE 1838
15.342 MV.TRACKPVWITHGAP 1838
15.343 MV.TYPICALMOVESIZE 1838
15.344 MV.U_SOLVE 1839

- 1676 -
Chapter 15 - Mxxxx Parameters

15.345 MV.USEACHLIM 1839


15.346 MV.USEPOLYMODEL 1840
15.347 MV.USETHISMV 1840
15.348 MV.USETHISMV_C 1840
15.349 MV.VALIDATIONFAILCOUNT 1841
15.350 MV.VALUE 1841
15.351 MV.VALUE_C 1842
15.352 MV.WEIGHT 1842
15.353 MV.WINDUPSTATUS 1842
15.354 MW 1843
15.355 MWSTS 1843
15.356 MXCOMMAND[1..200] 1844
15.357 MXFERSTATQ[1..200] 1845
15.358 MXFERSTATUS[1..200] 1845

15.359 MXGROUPNUM[1..200] 1846


15.360 MXMATPATH[1..200] 1846
15.361 MXNEGTOLER[1..200] 1847
15.362 MXOVRLAPNUM[1..200] 1847
15.363 MXPOSTOLER[1..200] 1848
15.364 MXTARGETWGT[1..200] 1848
15.365 MXTRANID[1..200] 1849

15.1 MACADDRA

Specific to Block(s) C300, PGM, FIM4, EHPM


Description MAC Address A - Media Access Control Address of port A (Yellow Tree Port).
Data Type String
Range Length : 12 Characters
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related Parameters MACADDRBMACADDRR
Remarks Unlike the IP address, this does not change with redundancy role change.

- 1677 -
Chapter 15 - Mxxxx Parameters

15.2 MACADDRB

Specific to Block(s) C300, PGM, FIM4 , EHPM


Description MAC Address B - Media Access Control Address of port B (Green Tree Port).
Data Type String
Range Length : 12 Characters
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related Parameters MACADDRAMACADDRR
Remarks Unlike the IP address, this does not change with redundancy role change.

15.3 MACADDRR

Specific to Block C300, PGM, FIM4, EHPM


(s)
Description MAC Address Redundancy - Media Access Control Address of port used for
redundancy link.
Data Type String
Range Length : 12 Characters
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related MACADDRAMACADDRB
Parameters
Remarks

15.4 MAINCLOSEFDBK

Specific to Block(s) MAINIBV


Description Main Valve close Feed back
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO

- 1678 -
Chapter 15 - Mxxxx Parameters

Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters IBVOPNFDBK
Remarks Main valve's close feedback from field is connected here

15.5 MAINCLOSEFDBKSTS

Specific to Block(s) MAINIBV


Description Main Valve close Feed back input Status
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters IBVOPNFDBKSTS
Remarks This parameter will get the status from DI channel connected to this block.

15.6 MAINTAINONFAULT

Specific to Series C PI
Block(s)
Description Maintain Selection on Fault
Data Type BOOLEAN
Range OFF(0) Do not Maintain On Fault (the selection
is reset such that no signal is output).
ON(1) Maintain On Fault.
Default OFF
Config Yes
Load
Active No
Loadable

- 1679 -
Chapter 15 - Mxxxx Parameters

Access Lock AppDevOnly


Residence IOM
Related ACTUALPROVERSIGNALCONFIGPROVERSIGNAL
Parameters
Remarks This parameter provides the user the ability to specify the action to be taken by the
system in case of a special condition or faults in the module or its ability to output
the selected stream to the pover signal. The possible conditions and faults are as
follows:
l Module state is changed to IDLE.
l Module loses communications with the controller.
l Module diagnostics failure detected in an unsynchronized primary module.
l Module diagnostics failure detected in a non-redundant module.
The only valid configuration values are:
l OFF - Do not Maintain On Fault (The selection is reset such that no signal is
output to the Prover).
l ON - Maintain on Fault.

15.7 MAINTOPT

Specific to Block(s) DevCtl


Description Maintenance Statistics Option
Data Type Boolean
Range Off (0): Maintenance Statistics not enabled. On (1) : Maintenance Statistics
enabled.
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related MAXTIME[0..2]MAXTRANS[0..2]NUMSIOVRDNUMTRANS RESETFL,
Parameters STATETIME[0..2].
Remarks

15.8 MAINVLVFDBKTO

Specific to MAINIBV
Block(s)
Description Main Valve Feedback Timeout
Data Type 16-Bit Unsigned Integer
Range <0
Default 0
Config YES

- 1680 -
Chapter 15 - Mxxxx Parameters

Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks Expiry of this timer (in seconds) indicates that desired feedback has not come and
the open command operations will be aborted.If MAINVLVFDBKTO is 0, During
download it will be give warning.This parameter will allow changes from Monitoring
to be done only when CM is Inactive.

15.9 MAJ

Specific to Block(s) 2oo3, MVote


Description Majority output value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

15.10 MAJORREV

Specific to All IOM Function Blocks


Block(s)
Description Major revision code - Intended to contain a matching or compatible firmware major
version indicator. Currently, this functionality is unused, thus all values are
defaulted to zero.
Data Type 32-Bit Integer
Range N/A
Default 0
Config Load Yes
Active No
Loadable

- 1681 -
Chapter 15 - Mxxxx Parameters

Access Lock Application Developer


Residence CEE
Related MINLVLSECSIG[0..15], MINORREV.
Parameters
Remarks Although loaded, this parameter is not exposed on any configuration form.

15.11 MAJRECFAULT

Specific to RM
Block(s)
Description Indication of a major recoverable fault in the Redundancy Module.
Data Type Enumeration
Range Ok (0) Fault (1)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

15.12 MAJURECFAULT

Specific to RM
Block(s)
Description Indication of a major unrecoverable fault in the Redundancy Module.
Data Type Enumeration
Range Ok (0) Fault (1)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 1682 -
Chapter 15 - Mxxxx Parameters

15.13 MANPULSECMD

Specific to Block PosProp, PidPosProp


(s)
Description Manual Pulse Command - Defines the type of pulse command the operator
wants to issue.
Data Type Enumeration
Range None (0): No change.
Raise1 (1): Raise output by MANPULSETIME each
keystroke.
Lower1 (2): Lower output by MANPULSETIME each
keystroke.
Raise10 (3): Raise output by 10 * MANPULSETIME each
keystroke.
Lower10 (4): Lower output by 10 * MANPULSETIME
each keystroke.
Default None (0)
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related
Parameters
Remarks

15.14 MANPULSETIME

Specific to PosProp, PidPosProp


Block(s)
Description Manual Pulse Time (in seconds) - Defines the duration of a raise/lower pulse
that is issued by operator command.
Data Type Real
Range 0.0 to 60.0 seconds
Default 1.0 seconds
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

- 1683 -
Chapter 15 - Mxxxx Parameters

15.15 MANUALMODE[1..24]

Specific to Block QIPACTERM


Description Manual-Not Auto-Mode
Data Type Boolean
Range Off(0) Auto Mode
On(1) Manual Mode
Default 1
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 2 of the Status 2 word in the input assembly for the
designated position [1-24].

15.16 MANUALMODE[1..200]

Specific to QIPACCHAN
Block
Description Manual-Not Auto-Mode
Data Type Boolean
Range Off(0) Auto Mode
On(1) Manual Mode
Default 1
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 2 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

- 1684 -
Chapter 15 - Mxxxx Parameters

15.17 MANUFACTURER

Specific to Block(s) 850M


Description Manufacturer Name
Data Type STRING
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

15.18 MASTERID

Specific to Block(s) PCDI_MASTER, PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Connected Master Block Key
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 1685 -
Chapter 15 - Mxxxx Parameters

15.19 MASTERSTATE

- 1686 -
Chapter 15 - Mxxxx Parameters

Specific to Block(s) PCDI_MASTER


Description Master State
Data Type Enumeration

- 1687 -
Chapter 15 - Mxxxx Parameters

Range 0 Inactive
1 Initializing
2 Cnx OK DV Init
3 Cnx OK DV OK
4 Cnx OK DV PF
5 Cnx OK DV POK
6 Cnx OK DV Fail
7 Cnx OK SM Init
8 Cnx OK SM OK
9 Cnx OK SM PF
10 Cnx OK SM POK
11 Cnx OK SM Fail
12 Cnx Fail
13 Cnx OK DV Init
14 Cnx OK DV OK
15 Cnx OK DV PF
16 Cnx OK DV POK
17 Cnx OK DV Fail
18 Cnx Marg DV Init
19 Cnx Marg DV OK
20 Cnx Marg DV PF
21 Cnx Marg DV POK
22 Cnx Marg DV Fail
23 Cnx OK SM Init
24 Cnx OK SM OK
25 Cnx OK SM PF
26 Cnx OK SM POK
27 Cnx OK SM Fail
28 Cnx Marg SM Init
29 Cnx Marg SM OK
30 Cnx Marg SM PF
31 Cnx Marg SM POK
32 Cnx Marg SM Fail
33 Cnx Fail
34 Cnx Offline
35 Cnx OK SM Idle
36 Cnx OK SM Idle
37 Cnx Marg SM Idle
Default Initializing

- 1688 -
Chapter 15 - Mxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Device
Related Parameters
Remarks

15.20 MATERIALPATH[1..200]

Specific to QIPACCHAN
Block
Description Material Path Index
Data Type 16-Bit Unsigned Integer
Range 0-65535
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related COMMAND, COMMANDSTATS[1..200], MXFERSTATUS[1..200], MXFERSTATQ
Parameters [1..200], OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200], POWERFAIL[1..200],
DELIVEREDWGT[1..200], TARGETERROR[1..200], AVGSPILL[1..200], AVGFLOWRATE
[1..200]
Remarks This is the value entered when the material transfer was initiated for the
designated channel [1-200] in the QiMPACT cluster.

15.21 MATRIKON_OPC_ABPLUGIN

Specific to ControlLogixModule
Block(s)
Description Allen Bradely Plugin name — Represents the Allen Bradely Plugin name as
configured in MatrikonOPC Server for Allen Bradely PLCs.
Data Type String
Range

Default
Config Load No
Active No
Loadable

- 1689 -
Chapter 15 - Mxxxx Parameters

Access Lock AppDevOnly


Residence ERDBONLY
Related
Parameters
Remarks

15.22 MATRIKON_OPC_HOST

Specific to ControlLogixModule
Block(s)
Description Matrikon OPC Host Name — The name of the computer on which the preferred
OPC server software resides.
Data Type String
Range

Default
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence ERDBONLY
Related
Parameters
Remarks

15.23 MATRIKON_OPC_PLC

Specific to ControlLogixModule
Block(s)
Description PLC Object Name — Object name of PLC as configured in the MatrikonOPC
Server for Allen Bradely PLCs.
Data Type String
Range

Default
Config Load No
Active No
Loadable

- 1690 -
Chapter 15 - Mxxxx Parameters

Access Lock AppDevOnly


Residence ERDBONLY
Related
Parameters
Remarks

15.24 MATRIKON_OPC_PROGID

Specific to Block(s) ControlLogixModule


Description Matrikon OPC Prog ID — Represents the Matrkon OPC Server Name
Data Type String
Range

Default
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence ERDBONLY
Related Parameters
Remarks

15.25 MAX

Specific to Block(s) Limit


Description Maximum Limit.
Data Type 64-Bit Real Number
Range Any real number, not NaN.
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 1691 -
Chapter 15 - Mxxxx Parameters

15.26 MAX_D

Specific to Block(s) ProfitCtl


Description MAX_D
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

15.27 MAX_N_S

Specific to Block(s) ProfitCtl


Description MAX_N_S
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

15.28 MAX_N_SJL

Specific to Block(s) ProfitCtl


Description MAX_N_SJL
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No

- 1692 -
Chapter 15 - Mxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related Parameters
Remarks

15.29 MAX_N_SS

Specific to Block(s) ProfitCtl


Description MAX_N_SS
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

15.30 MAXACTPERIOD

Specific to CEE
Block(s)
Description Maximum period taken by an Activity during initialization.
Data Type Enumeration
Range 500 ms, 1 sec, 2 sec
Default 1sec
Config Yes
Load
Active Yes
Loadable

- 1693 -
Chapter 15 - Mxxxx Parameters

Access AppDevOnly
Lock
Residence CEE
Related PERIOD
Parameters
Remarks The purpose of this parameter is to speed up the initializing state of Activities that
are associated with SCM/RCMs for long periods. This parameter is used for making
an Activity execute faster than its associated RCM. For example, if the
MAXACTPERIOD is 500 ms and the PERIOD of the associated entity (SCM/RCM) is 2
sec, then the activity runs with a period of 500 ms during the initializing state. If the
MAXACTPERIOD is set to 500 ms and the PERIOD of the associated entity
(SCM/RCM) is 50 ms, then the Activity runs with a period of 50ms during the
initializing state. Also, MAXACTPERIOD has no impact for blocks with PERIOD <= to
the MAXACTPERIOD. Once the initialization is complete, the Activity aligns its
execution period with its associated entity. The value of this parameter applies to all
the manual Activities in the associated CEE. This parameter is a part of the “Load
while Active” functionality.

15.31 MAXBLKTYPES

Specific to CEEC300, CEE, CEEUOC, CEECN100


Block(s)
Description Max Number of Block Types

Data Type INT32


Range 0 to 4,258,848 (block types)
Default 0

Config No
Load

Active Load No
Access View Only
Lock

Residence C200(CEE), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)

Related
Parameters

Remarks Maximum Number of Block Types that can be supported in the Control Execution
Environment, including those that are part of Control Component Libraries.

15.32 MAXBROWSEP

Specific to Block(s) OPCUASRVUOC


Description Maximum Browse Continuation Points
Data Type UINT32
Range 0 to 4294967295
Default 0

- 1694 -
Chapter 15 - Mxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.33 MAXBROWSER

Specific to Block(s) OPCUASRVUOC


Description Maximum Browse Results
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.34 MAXCABTYPES

Specific to CEE-ACE block, CEE-C300 block


Block(s)
Description Maximum CAB Types - Maximum number of CAB types that can be loaded and used
within the controller.
Data Type Integer
Range Range is platform specific. For more information, refer to the remarks.
Default Not applicable.
Config Load No
Active No
Loadable
Access Lock View Only.
Residence CEE
Related NUMCABTYPES
Parameters
Remarks For CEE-ACE, the maximum number of in-use CAB types is 400. For CEE-C300, the
maximum number of loaded CAB types is 100. MAXCABTYPES is visible on the CAB
Types Info tab of the CEE block form.

- 1695 -
Chapter 15 - Mxxxx Parameters

15.35 MAXCACHEVAR

Specific to Block IOLIM, Secondary IOLIM, FIM


(s)
Description Maximum Number of Cached Variables. Shows the maximum number of
cached parameter values.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks

15.36 MAXCDDMTYPES

Specific to CEEC300, CEEFB, CEEACE, CEESIMC200, CEEUOC,CEEvUOC, CEECN100


Block(s)
Description Maximum Instantiated Block Types
Data Type 32-Bit Integer
Range 0-400 for C300, 0-600 for ACE and 0-1000 for UOC/vUOC
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEE), C200(CEE), ACE(CEE), SIMC200(CEE), UOC(CEEUOC), vUOC
(CEEvUOC), CN100(CEECN100)
Related
Parameters
Remarks

- 1696 -
Chapter 15 - Mxxxx Parameters

15.37 MaxConfigSize

Specific to 1738-AENT
Block(s)
Description Maximum Size of Configuration Data — It represents the maximum configuration
size supported by 1738-AENT Adapter.
Data Type UINT32
Range
Default 510
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks It is a static value and it cannot be changed.

15.38 MAXCYCLE

Specific to FLOWCOMP
Block(s)
Description Maximum Cycle - Defines the maximum number of alarm filter cycles during which
the last good value for the COMPTERM parameter is to be held before becoming
NaN.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks An alarm is generated only if the calculated COMPTERM is consistently BAD for
more than the configured alarm filter cycles.

- 1697 -
Chapter 15 - Mxxxx Parameters

15.39 MAXDEADTIME

Specific to Block(s) ProfitCtl


Description Max dead time
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

15.40 MAXDEPTH

Specific to Block(s) TCMI


Description Maximum Depth
Data Type UINT32
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

15.41 MAXDEVICEINDEX

Specific to Block TCMI


(s)
Description Maximum Node ID - Identifies the highest Device Index supported within the
FTE community.
Data Type 16-Bit Integer
Range
Default 0
Config Load No

- 1698 -
Chapter 15 - Mxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

15.42 MAXFREEBLKSZ

Specific to CEEC300, CPM, CEEUOC, CEECN100


Block(s)
Description Largest Free Memory Block Size(b)
Data Type 32-Bit Integer
Range 0 to 4194304 Bytes
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200(CPM), C300(CEEC300) , UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM, TOTALMEM, USEDMEM.
Parameters
Remarks Block configurations such as Sequential Control Module (SCM) function blocks can
require large blocks of contiguous memory. MAXFREEBLKSZ gives the largest
amount of memory currently available to a contiguous block configuration.
MAXFREEBLKSZ is always less than or equal to FREEMEM.

15.43 MAXFREEINK

Specific to CEEC300, CPM, CEEUOC, CEECN100


Block(s)
Description Largest Free Memory Block Size(kb)
Data Type 32-Bit Integer
Range 0 to 4194304 Bytes
Default 0
Config No
Load
Active No
Loadable

- 1699 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence C200(CPM), C300(CEEC300) , UOC(CEEUOC), CN100(CEECN100)
Related FREEMEMINK, TOTALMEMINK, USEDMEMINK.
Parameters
Remarks Block configurations such as Sequential Control Module (SCM) function blocks can
require large blocks of contiguous memory. MAXFREEINK gives the largest amount
of memory currently available to a contiguous block configuration. MAXFREEINK is
always less than or equal to FREEMEMINK.

15.44 MAXFTENODES

Specific to FTEB, C300, PGM, FIM4, EHPM , TCMI


Block(s)
Description Maximum Fault Tolerant Ethernet (FTE) Nodes - Identifies the maximum number
of FTE nodes that have been detected within the FTE community.
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

Specific to EIM, UOC


Block(s)
Description Max Number of FTE Nodes
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Identifies the maximum number of FTE nodes that have been detected within the
FTE community. (FTE parameters, see C300 definition)

- 1700 -
Chapter 15 - Mxxxx Parameters

15.45 MAXGPSSKEW

Specific to Block C300 FBs


(s)
Description Maximum GPS Skew - Maximum skew recorded till present while
synchronizing time from GPS.
Data Type TIME
Range
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300
Related
Parameters
Remarks This parameter is not actively used.

15.46 MAXHISOAKDEV[1..NUMPROFILES]

Specific to RampSoak
Block(s)
Description Maximum High Soak Deviation - that is, maximum deviation between PV and
SOAKVAL(I)(j) during soak segments when PV < SOAKVAL(I)(j). Applies to all ramp
segments in a profile.
Data Type Real
Range NaN, or greater-than or equal-to 0.0
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MAXLOSOAKDEV[1..NUMPROFILES]
Parameters
Remarks

- 1701 -
Chapter 15 - Mxxxx Parameters

15.47 MAXICPNAKS

Specific to CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,
Block(s) CEEC300,GEEFB, CEEUOC, CEECN100
Description Total ICP NAK Count
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, C200, ACE, SIMC200, FIM, UOC, CN100
Related N/A
Parameters
Remarks Maximum Integrated Control Protocol (ICP) Not Acknowledgements - The maximum
number of ICP messages not acknowledged per second for all responder
connections

15.48 MAXICPSENDS

Specific to CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,
Block(s) CEEC300,GEEFB, CEEUOC, CEECN100
Description Maximum Integrated Control Protocol (ICP) Sends failures
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, C200, ACE, SIMC200, FIM, UOC, CN100
Related N/A
Parameters
Remarks Maximum Integrated Control Protocol (ICP) Sends - The maximum number of
Control Data Access (CDA) and ICP retries per second for all responder connections.

- 1702 -
Chapter 15 - Mxxxx Parameters

15.49 MAXIMR

Specific to IOLIM, C300 IOLINK, FIM


Block(s)
Description Maximum Number of Pending Requests. Shows the maximum number of pending
Control Data Access (CDA) server requests.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

15.50 MaxIntervalsInInit

Specific to Block(s) ProfitCtl


Description Max Intervals in INIT
Data Type FLOAT64
Range NA
Default 3
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

- 1703 -
Chapter 15 - Mxxxx Parameters

15.51 MAXLOSOAKDEV[1..NUMPROFILES]

Specific to RampSoak
Block(s)
Description Maximum Low Soak Deviation - that is, maximum deviation between PV, and
SOAKVAL(I)(j) during soak segments when PV < SOAKVAL(I)(j). Applies to all ramp
segments in a profile.
Data Type Real
Range NaN, or greater-than or equal-to 0.0
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MAXHISOAKDEV[1..NUMPROFILES]
Parameters
Remarks

15.52 MAXMINRATIO

Specific to EXECTIMER
Block(s)
Description MAXimum to MINimum RATIO
Data Type FLOAT64
Range
Default NaN
Config No
Load
Active No
Loadable
Access Lock View only
Residence CEE
Related DTIMEMAX, DTIMEMIN, MAXMINRATIO
Parameters
Remarks In cases where an application engineer wants to set the parameter REJFACTOR to a
value other than NaN, MAXMINRATIO can be used to judge what would be an
appropriate value. If MAXMINRATIO is large, it typically means the measurement is
capturing interrupt execution or higher priority task execution unrelated to the
block or blocks under test.

- 1704 -
Chapter 15 - Mxxxx Parameters

15.53 MAXMONITOR

Specific to Block(s) OPCUASRVUOC


Description Maximum Monitor Item Counts
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.54 MAXMONPERSUBSCR

Specific to Block(s) OPCUASRVUOC


Description Maximum Monitor Item Per Subscription
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.55 MAXMONPERSESS

Specific to Block(s) OPCUASRVUOC


Description Maximum Monitor Item Per Session
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No

- 1705 -
Chapter 15 - Mxxxx Parameters

Access Lock AppDevOnly


Residence CEEAL
Related Parameters None
Remarks

15.56 MAXNODEID

Specific to Block FTEB, C300, PGM, FIM4, EHPM , TCMI


(s)
Description Maximum Node ID - Identifies the highest Device Index supported within the
FTE community.
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

Specific to Block EIM


(s)
Description Maximum Node ID - Identifies the highest Device Index supported within the
FTE community.
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks

Specific to Block(s) UOC


Description Max Device Index
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No

- 1706 -
Chapter 15 - Mxxxx Parameters

Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (FTE parameters, see C300 definition)

15.57 MAXNOOFBLOCKS

Specific to Block(s) PROFITCTLIN


Description Max Blocking in CV and MV
Data Type INT32
Range ±2147483647
Default 20
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters
Remarks

Specific to Block(s) PROFCONOUT


Description Max Blocking in CV and MV
Data Type INT32
Range ±2147483647
Default 20
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.NOOFBLKS
Remarks Max Blocking in CV and MV

- 1707 -
Chapter 15 - Mxxxx Parameters

15.58 MAXNOOFFTENODES

Specific to TCMI
Block(s)
Description Maximum Fault Tolerant Ethernet (FTE) Nodes - Identifies the maximum number of
FTE nodes that have been detected within the FTE community.
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

15.59 MAXNUMACT

Specific to Block(s) CEE


Description Maximum number of simultaneous Activities.
Data Type INT32
Range 0-1000
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related NUMACT, CURRNUMACT, NUMACTCRFAIL, ACTAVAIL, NUMACTCR,
Parameters STATSRESET
Remarks This parameter is reset to 0 when STATSRESET=ON.

15.60 MAXOWNERS

Specific to SCM, RCM, UCM, CM, MR


Block(s)
Description Maximum Granted Requesters
Data Type 32-Bit Integer
Range l 0 to 5 for SCM, RCM, UCM

- 1708 -
Chapter 15 - Mxxxx Parameters

l 0 to 10 for CM
l 0 to 20 for MR
Default 1
Config Load PCM
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related NUMOWNERSOWNERID[1..MAXOWNERS]OWNERIDN[1..MAXOWNERS]
Parameters
Remarks A value of 1 defines an exclusively used resource , a value <1 defines a non-
exclusively used resource. A value of 0 disables all resource functionality.

15.61 MAXPCOVERRUN

Specific to ProfitCtl
Block(s)
Description Max PC Overrun Allowed
Data Type INT16
Range NA
Default 3
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related PCOVERRUN
Parameters
Remarks If PCOVERUN > MAXPCOVERRUN, block goes into OFF state. This situation can
occur when for consecutive execution periods, block does not finish its execution.

15.62 MAXPENDREQ

Specific to PCDI_MASTER
Block(s)
Description Maximum Pending Requests (transactions)
Data Type 32-Bit Unsigned Integer
Range 1 to 64
Default 1
Config Yes
Load

- 1709 -
Chapter 15 - Mxxxx Parameters

Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related
Parameters
Remarks This parameter represents the maximum number of transactions for a PCDI_
MASTER device block. Once the maximum amount of transactions has been
exceeded, the next transaction results in an alarm. Transactions that exceed the
maximum number of transactions will be ignored.

15.63 MAXPTPFASTSKEW

Specific to C300, PGM2, FIM4, FIM8, EHPM


Block(s)
Description Max PTP Negative Skew (msec)
Data Type UINT32
Range -
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, EHPM
Related
Parameters
Remarks This parameter displays t the maximum skew (in milliseconds) of the local clock for
which the local clock was faster than the master clock.

15.64 MAXPTPSLOWSKEW

Specific to C300, PGM2, FIM4, FIM8, EHPM


Block(s)
Description Max PTP Positive Skew (msec)
Data Type UINT32
Range -
Default 0
Config Load No
Active No
Loadable

- 1710 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence CEE, EHPM
Related
Parameters
Remarks This parameter the maximum skew (in milliseconds) of the local clock for which the
local clock was slower than the master clock.

15.65 MAXPUBLISH

Specific to Block(s) OPCUASRVUOC


Description Maximum Publishing Intervals
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.66 MAXPULSEL

Specific to Block(s) PosProp, PidPosProp


Description Maximum Output Pulse Time for Lower Pulses (in seconds).
Data Type Real
Range NaN, MINPULSEL to 60.0 seconds.
Default 60.0 seconds
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

- 1711 -
Chapter 15 - Mxxxx Parameters

15.67 MAXPULSER

Specific to Block(s) PosProp, PidPosProp


Description Maximum Output Pulse Time for Raise Pulses (in seconds).
Data Type Real
Range NaN, MINPULSER to 60.0 seconds.
Default 60.0 seconds
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

15.68 MAXRCMSUSED

Specific to Block(s) CEE


Description Maximum RCMs used.
Data Type INT32
Range -
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMRUNRCMS, STATSRESET
Remarks This parameter is reset to 0 when STATSRESET=ON.

15.69 MAXREQUEST

Specific to Block(s) OPCUASRVUOC


Description Maximum Request Age
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No

- 1712 -
Chapter 15 - Mxxxx Parameters

Access Lock AppDevOnly


Residence CEEAL
Related Parameters None
Remarks

15.70 MAXRESOURCES

Specific to Block(s) SCM


Description Maximum Number of Allocatable Resources
Data Type 32-Bit Integer
Range 0 to 4
Default 1
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

15.71 MAXRFBDEV

Specific to PIDER
Block(s)
Description Maximum Reset Feedback (RFB) Deviation - Specifies maximum deviation allowed
between calculated value (CV) and RFB in percent.
Data Type Float64
Range 0.0 to 100 percent
Default 100.0 percent
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CV, RETRYSTOTAL, RFB
Parameters
Remarks

- 1713 -
Chapter 15 - Mxxxx Parameters

15.72 MAXRAMPDEV[1..NUMPROFILES]

Specific to RampSoak
Block(s)
Description Maximum Ramp Deviation - that is, maximum deviation between PV and CV during
ramp segments. Applies to all ramp segments in a profile.
Data Type Real
Range NaN, or greater-than or equal-to 0.0
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

15.73 MAXSESSION

Specific to Block(s) OPCUASRVUOC


Description Maximum Session Counts

Data Type UINT32


Range 0 to 4294967295
Default 10
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.74 MAXSESSIONSPC

Specific to Block(s) OPCUASRVUOC


Description Maximum Sessions Per Client

Data Type UINT32


Range 0 to 4294967295

- 1714 -
Chapter 15 - Mxxxx Parameters

Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.75 MAXSESSIONTO

Specific to Block(s) OPCUASRVUOC


Description Maximum Session Timeout

Data Type UINT32


Range 0 to 4294967295
Default 3600000
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.76 MAXSNTPSKEW

Specific to C300, PGM, FIM4, EHPM


Block(s)
Description Maximum SNTP Skew - Maximum skew recorded till present while
synchronizing time from SNTP server.
Data Type TIME
Range
Default Null
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

- 1715 -
Chapter 15 - Mxxxx Parameters

15.77 MAXSNODESBROWSE

Specific to Block(s) OPCUASRVUOC


Description Maximum Nodes to Browse

Data Type UINT32


Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.78 MAXSUBSCRC

Specific to Block(s) OPCUASRVUOC


Description Max Subscription Counts
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.79 MAXSUBSCRLT

Specific to Block(s) OPCUASRVUOC


Description Max Subscription Lifetime
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No

- 1716 -
Chapter 15 - Mxxxx Parameters

Access Lock AppDevOnly


Residence CEEAL
Related Parameters None
Remarks

15.80 MAXSUBSCRPERSESS

Specific to Block(s) OPCUASRVUOC


Description Max Subscription Per Session
Data Type UINT32
Range 0 to 4294967295
Default 10
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.81 MAXRCVBYTESPERSEC

Specific to Block(s) PCDI_MASTER


Description Maximum Bytes Received per Second
Data Type Float32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 1717 -
Chapter 15 - Mxxxx Parameters

15.82 MAXRCVMSGPERSEC

Specific to Block(s) PCDI_MASTER


Description Maximum Messages Received per Second
Data Type Float32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

15.83 MAXRXPKTRATE

Specific to Block(s) EIM EIP Protocol Block


Description Maximum Rx Pkt Rate
Data Type FLOAT32
Range -
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Maximum Receive PDT Packet Rate from C300 to EIM in Packets/Second.

15.84 MAXSOAKVAL[1..NUMPROFILES]

Specific to Block(s) RampSoak


Description Maximum Soak Target Value in a profile.
Data Type Real
Range N/A
Default NaN
Config Load Yes
Active Loadable No

- 1718 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

15.85 MAXSTACK

Specific to Block(s) CEEC300


Description Maximum CEE Budgeted Stack %
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300
Related Parameters
Remarks

Specific to Block(s) CEEUOC, CEECN100


Description Maximum CEE Budgeted Stack %
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence UOC, CN100
Related Parameters
Remarks

15.86 MAXTIME

Specific to Step
Block(s)
Description Maximum Active Time
Data Type 32-Bit Integer
Range 0 or greater-than MINTIME

- 1719 -
Chapter 15 - Mxxxx Parameters

Default 0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related MINTIMETIME.
Parameters
Remarks MAXTIME is the maximum number of execution cycles that the step can be active
before an SCM STEPALM is generated. Setting MAXTIME = 0 disables STEPALM.

15.87 MAXTIME[0..2]

Specific to Block(s) DevCtl


Description Maximum Duration per State
Data Type 64-Bit Real Number
Range 0.0 to 96000.0 hours (4000.0 days)
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters MAINTOPT, NUMSTATES.
Remarks MAXTIME[2] is illegal if NUMSTATES = 2.

15.88 MAXTIMEFL

Specific to Block(s) Step


Description Maximum Step Expired Flag.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters MAXTIME TIME.
Remarks MAXTIMEFL is On when Step TIME is greater-than MAXTIME.

- 1720 -
Chapter 15 - Mxxxx Parameters

15.89 MAXTRANS[0..2]

Specific to Block(s) DevCtl


Description Maximum Transitions per State.
Data Type 64-Bit Real Number
Range 0.0 to Maximum Real Number
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters MAINTOPT, NUMSTATES.
Remarks MAXTRANS[2] is illegal if NUMSTATES = 2.

15.90 MAXUIDREQ

Specific to PCDI_MASTER
Block(s)
Description Maximum per Slave (Unit ID) Requests
Data Type 32-Bit Unsigned Integer
Range 1 to 64
Default 1
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related
Parameters
Remarks This parameter shows the maximum number of active requests to a serial device.
An alarm is generated when a device exceeds the active request per serial device
maximum.

15.91 MAXXMITBYTESPERSEC

Specific to Block(s) PCDI_MASTER


Description Maximum Bytes Transmitted per Second
Data Type Float32
Range
Default 0

- 1721 -
Chapter 15 - Mxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

15.92 MAXXMITMSGPERSEC

Specific to Block(s) PCDI_MASTER


Description Maximum Messages Transmitted per Second
Data Type Float32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

15.93 MBERRCNT[0..15]

Specific to Block(s) PCDI_MASTER


Description Modbus Error Count
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 1722 -
Chapter 15 - Mxxxx Parameters

15.94 MBERRFL[0..15]

Specific to Block(s) PCDI_MASTER


Description Modbus Error Flag
Data Type Boolean
Range True/False
Default True
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

15.95 MBTCPFREEBUFCOUNT

Specific to Block(s) CEEC300


Description Modbus TCP Free Buffer Count
Data Type 32-Bit Integer
Range 0 to 2147483647
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

15.96 MBTCPINVALIDRCVMSGCOUNT

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Modbus TCP Invalid Receive Message Count
Data Type 32-Bit Integer
Range 0 to 2147483647
Default 0
Config Load No
Active Loadable No

- 1723 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

15.97 MEANINGPRI[0..15]

Specific to Message
Block(s)
Description Meaning Primary - Description of what the primary signature means. For example,
review, approval, responsiblility, or authority.
Data Type String
Range 24 Characters Maximum
Default
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related MSGSEQNUMBER[1..200], MSGTYPE[0..15]
Parameters
Remarks Used with message types of SINGLESIGNATURE and DOUBLESIGNATURE.

15.98 MEANINGSEC[0..15]

Specific to Message
Block(s)
Description Meaning Secondary - Description of what the secondary signature means. For
example, review, approval, responsiblility, or authority.
Data Type String
Range 24 Characters Maximum
Default
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related MSGSEQNUMBER[1..200], MSGTYPE[0..15]
Parameters
Remarks Used with message type of DOUBLESIGNATURE.

- 1724 -
Chapter 15 - Mxxxx Parameters

15.99 MEDIADEADA

Specific to Block(s) ELCN_BRG

Description Total Cable A Media Dead

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

15.100 MEDIADEADB

Specific to Block(s) ELCN_BRG

Description Total Cable B Media Dead

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics tab

Remarks

- 1725 -
Chapter 15 - Mxxxx Parameters

15.101 MEDIADEADAV

Specific to Block(s) TCMI

Description Media Dead Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

15.102 MEDOPT

Specific to SignalSel
Block(s)
Description Median option for even number of valid inputs
Data Type Enumeration: SELMETHOD
Range 0: MIN 1: MAX 2: AVG
Default MIN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE)
Related BOOLMUX
Parameters
Remarks This parameter is enabled only when SELMETHOD is MED and represents the
operation to perform with the middle two inputs when even number of inputs is
valid.

15.103 MEM1CR

Specific to Block(s) MR
Description Maximum memory demand of one Control recipe.
Data Type INT32
Range 0 to 4294967296

- 1726 -
Chapter 15 - Mxxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters None
Remarks

15.104 MEMALLCR

Specific to MR
Block(s)
Description Memory currently used by all Control recipe's for this Master recipe.
Data Type INT32
Range 0 to 4294967296
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related None
Parameters
Remarks The value of this parameter is 0 if no Control recipes exist. It may also reach n times
of MEM1CR, where n is the number of Control recipes. Value is suitable for
trending and alarming.

15.105 MEMFREEAVG

Specific to Block(s) CN100, EIM, ELCNB, ELCNNODE, UOC, C300


Description Main RAM Free (%)
Data Type FLOAT64
Range ±1.7E+308, ±1.7E+308
Default
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Main RAM free.

- 1727 -
Chapter 15 - Mxxxx Parameters

15.106 MEMFREECRIT

Specific to Block CN100, EIM, ELCNB, ELCNNODE, UOC, C300


Description Free system memory is below the fixed critical limit
Data Type BOOLEAN
Range On/Off
Default Off
Config Load No
Active Loadable No
Access Lock
Residence CEE
Related Parameters MEMFREECRITLM
Remarks Soft Failure

15.107 MEMFREECRITLM

Specific to CN100, EIM, ELCNB, ELCNNODE, UOC, C300


Block(s)
Description Main RAM Free Critical Alarm (%)
Data Type FLOAT64
Range 0.0 to 100.0, ±1.7E+308
Default 10
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Main RAM free critical alarm set point. A "Main RAM free critical" alarm is generated
if the main RAM free statistic drops below this value. This set point is not user
configurable.

- 1728 -
Chapter 15 - Mxxxx Parameters

15.108 MEMFREELOWLM

Specific to Block(s) CN100, EIM, ELCNB, ELCNNODE, UOC, C300

Description Main Ram Free Low Alarm (%)

Data Type FLOAT64

Range 10.0 to 100.0

Default 20

Config Load Yes

Active Loadable No

Access Lock Engineer

Residence ELCN_BRG

Related Parameters Main tab – Advanced Configuration

Remarks

15.109 MEMFREEMIN

Specific to CN100, EIM, ELCNB, ELCNNODE, UOC, C300


Block(s)
Description Main RAM Free Minimum (%)
Data Type FLOAT64
Range ±1.7E+308, ±1.7E+308
Default
Config Load NO
Active NO
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Main RAM free low water mark. Note that the low water mark is reset using the
"reset statistics" command.

15.110 MESSAGE[0..15]

Specific to Block(s) Message


Description Message Text
Data Type String
Range Maximum of 132 characters
Default Null String

- 1729 -
Chapter 15 - Mxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Operator
Residence SR
Related Parameters
Remarks

15.111 MIN

Specific to Block(s) Limit


Description Mode Attribute Reference
Data Type 64-Bit Real Number
Range Any real number, not NaN.
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

15.112 MINALIVE

Specific to Block(s)
Description Min Keep Alive Intervals
Data Type UINT32
Range 0 to 4294967295
Default 5000
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters
Remarks

- 1730 -
Chapter 15 - Mxxxx Parameters

15.113 MINHWREVSF

Specific to EIM, UOC, CN100


Block(s)
Description Minimum Recommended HW Revision
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks True if device hardware fails to meet the minimum recommended hardware
revision for the currently loaded firmware.

15.114 MINLVLSECSIG[0..15]

Specific to Message
Block(s)
Description Minimum Level Secondary Signature - Defines the minimum security level
required for secondary signature.
Data Type Enumeration
Range Operator (0) Supervisor (1) Engineer (2) Manager (3)
Default 0 - Operator
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MSGSEQNUMBER[1..200], MSGTYPE[0..15]
Parameters
Remarks Only required for message type of DOUBLESIGNATURE.

- 1731 -
Chapter 15 - Mxxxx Parameters

15.115 MINORREV

Specific to All IOM Function Blocks


Block(s)
Description Minor revision code - Intended to contain a matching or compatible firmware minor
version indicator. Currently, this functionality is unused, thus all values are
defaulted to zero.
Data Type 32-Bit Integer
Range N/A
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related MAJORREV
Parameters
Remarks Although loaded, this parameter is not exposed on any configuration form.

15.116 MINPUBLISH

Specific to Block(s) OPCUASRVUOC


Description Minimum Publishing Intervals

Data Type UINT32


Range 0 to 4294967295
Default 250
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

15.117 MINPULSEL

Specific to PosProp, PidPosProp


Block(s)
Description Minimum Output Pulse Time for Lower Pulses (in seconds).
Data Type Real
Range NaN, 0.0 to MAXPULSEL

- 1732 -
Chapter 15 - Mxxxx Parameters

Default 0.0 seconds


Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related
Parameters
Remarks MINPULSEL reflects the physical properties of a device, for example a valve. It is
the pulse duration required to move that device.

15.118 MINPULSER

Specific to PosProp, PidPosProp


Block(s)
Description Minimum Output Pulse Time for Raise Pulses (in seconds).
Data Type Real
Range NaN, 0.0 to MAXPULSER
Default 0.0 seconds
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related
Parameters
Remarks MINPULSER reflects the physical properties of a device, for example a valve. It is
the pulse duration required to move that device.

15.119 MINRECFAULT

Specific to RM
Block(s)
Description Indication of a minor recoverable fault in the Redundancy Module.
Data Type Enumeration
Range Ok (0) Fault (1)
Default Ok (0)
Config Load No
Active No
Loadable

- 1733 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

15.120 MINSOAKVAL[1..NUMPROFILES]

Specific to Block(s) RampSoak


Description Minimum Soak Value in a profile.
Data Type Real
Range N/A
Default NaN
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

15.121 MINSESSIONTO

Specific to Block(s) OPCUASRVUOC


Description Minimum Session Timeout

Data Type UINT32


Range 0 to 4294967295
Default 10000
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters
Remarks

- 1734 -
Chapter 15 - Mxxxx Parameters

15.122 MINSUBSCRIPTION

Specific to Block(s) OPCUASRVUOC


Description Minimum Subscription
Lifetime
Data Type UINT32
Range 0 to 4294967295
Default 10000
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters
Remarks

15.123 MINTIME

Specific to Step
Block(s)
Description Step Minimum Active Time
Data Type 32-Bit Integer
Range 0 to (2^31)-1
Default 0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related MAXTIME, TIME.
Parameters
Remarks MINTIME is the minimum number of execution cycles that the step is active. When
Step TIME is less-than-or-equal to MINTIME it prevents the transition(s) out of the
step from being evaluated.

15.124 MINURECFAULT

Specific to RM
Block(s)
Description Indication of a minor unrecoverable fault in the Redundancy Module.
Data Type Enumeration
Range Ok (0) Fault (1)

- 1735 -
Chapter 15 - Mxxxx Parameters

Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

15.125 MINUTE

Specific to ACE, CPM, SIM_C200, CEEC300, CEEUOC, CEECN100


Block(s)
Description Defines the current minute component of the Controller's local time.
Data Type 32-Bit Integer
Range 0 to 59
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence ACE, C200(CPM), C300(CEEC300), SIM_C200, UOC(CEEUOC), CN100(CEECN100)
Related DAYLIGHTTIME, TIMEZONE.
Parameters
Remarks Wall Clock Time (WCT) is being lost during loss of power (that is, the controller has
no built-in clock) and cannot be restored in RAM retention restart scenario. Hence,
the controllers may be operating without a time source and this parameter returns
a permanent zero value.

15.126 MMSRPS

Specific to Block IEC61850LINK


(s)
Description MMS Request Rate
Data Type FLOAT64
Range >= 0.0
Default 0.0
Config Load No
Active Loadable N/A

- 1736 -
Chapter 15 - Mxxxx Parameters

Access Lock View Only


Residence CEE
Related
Parameters
Remarks This value represents the rate at which MMS requests are made on the
IEC61850Link.

15.127 MMSSTORERPS

Specific to Block IEC61850LINK


(s)
Description MMS Store Rate
Data Type FLOAT64
Range >= 0.0
Default 0.0
Config Load No
Active Loadable N/A
Access Lock View Only
Residence CEE
Related
Parameters
Remarks This value represents the rate of MMS store messages sent out on the
IEC61850LINK

15.128 MODCOMPATA

Specific to RM
Block(s)
Description Indication of the module pair's assessment of their compatibility
Data Type Enumeration [20]
Range Undefined (0) Incompatible (1) Fully (2) Standby (3)
Default Undefined (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Not Loaded
Related
Parameters
Remarks Requests to read or store to any RM parameter must come from the Supervisory
platform (through Control Builder or Server).

- 1737 -
Chapter 15 - Mxxxx Parameters

15.129 MODDIF

Specific to All I/O Module Function Blocks


Block(s)
Description Module Diff State
Data Type ENUM
Range 0 – NO DIFF
1 – SUBSTITUTED
2 – MISMATCH
3 – MISSING
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related IIOPS, IIOCS, OIOPS, OIOCS
Parameters
Remarks This is consumer status for output data. This status is given by device for output data
indicating whether it is ready to consume data or not.

15.130 MODE

Specific to SCM, RCM


Block(s)
Description Sequential Control Module (SCM) Mode - Defines the SCM execution mode.
Data Type Enumeration enmScmMode
Range None (0) Auto (1) SemiAuto (2) SingleStep (3) Manual (4) Normal (5)
Default None (0)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related CONTCUTOUTCONTROLLOCK, GWCOMMAND, EXCMODEOPT, MODEATTR,
Parameters SSTEPLOCK JUMPSAFEENB
Remarks Note: If the MODE is “SingleStep” or “SafeStep” when the STATE is “Inactive”, then
the MODE will be automatically set to “Auto” when activation is initiated by setting
the COMMAND as “Active”. This is applicable only for SCM and RCM. The ability to
change MODE to a certain value depends on the following current values:
MODEATTR, SSTEPLOCK, and CONTROLLOCK. For more information on MODE's
ranges, refer to the Sequential Control Module User Guide, SCM Modes.

- 1738 -
Chapter 15 - Mxxxx Parameters

15.131 MODE

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Mode - Defines the mode of a Regulatory Control function block.
Data Type Enumeration REGMODE
Range Manual (0): OP is stored by either the operator or a
user program. The function block doesn't
derive OP, so the input (SP, X1, and so
on) is ignored.
Automatic (1): The function block derives OP. The input
(SP, X1, and so on) may be stored by
either the operator or a user program.
Cascade (2): The function block derives OP. The input
is pulled from another function block
(the primary).
Backup Cascade (3): The function block derives OP. The input
is pulled from a backup cascade. (Note:
Bcas only applies to the Remote Cascade
FB.)
None (4)
Normal (5)
Default Manual (Man)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related MODEATTRBADOCOPT
Parameters
Remarks MODE change by a program requires MODEATTR = Program and REDDATAA,
REDDATAB, REDTAG = Off; MODE change by an operator requires MODEATTR =
Operator, MODEPERM= Permit, and REDTAG = Off. When a regulatory control block
experiences an IO communication loss, you can change the value of MODE
irrespective of the value set in BADOCOPT parameter. Note: This is not applicable to
the PIDER block

NOTE When the Operator modifies the MODE to "Manual," the


MODEATTR is automatically transitioned from "Program" to "Operator."
Changing the MODEATTR to "Operator" locks out program access and
ensures that the Operator is not engaged in a struggle with a program
for control of the plant in a critical situation. The program can regain
access to the process when the MODEATTR is returned to "Program."

- 1739 -
Chapter 15 - Mxxxx Parameters

15.132 MODE

Specific to DEVCTL, MAINIBV, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Mode
Data Type Enumeration MODE
Range Manual
Default Manual
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks DEVCTL Only: Access is illegal if NUMDOUTS = 0. The value of this parameter is
fixed Manual to be compatible with other function blocks.

NOTE When the Operator modifies the MODE to "Manual," the


MODEATTR is automatically transitioned from "Program" to "Operator."
Changing the MODEATTR to "Operator" locks out program access and
ensures that the Operator is not engaged in a struggle with a program
for control of the plant in a critical situation. The program can regain
access to the process when the MODEATTR is returned to "Program."

15.133 MODE

Specific to Series CSeries C AOCHANNEL and Series C DOCHANNEL


Block(s)
Description Operating mode for channel block
Data Type Enumeration
Range 1 Man Manual mode, a user or a program provides
this channel's output value.
2 Cas Cascade mode, a control (ex. RegCtl) block
provides the output value.
5 Normal Parameter NMODE determines this point's
mode and parameter determines this point's
MODEATTR.
Default Cascade
Config Load Yes
Active No
Loadable

- 1740 -
Chapter 15 - Mxxxx Parameters

Access Lock Operator


Residence IOM
Related MODEATTR, MODEATTR, NMODE, NMODATTR, REDTAG
Parameters
Remarks This parameter defines the current mode for this channel.
l For a user to change MODE, MODEATTR must equal Operator, MODEPERM
must equal Permit, and REDTAG must be OFF.
l For a program to change MODE, MODEATTR must equal Program and
REDTAG must be OFF.

NOTE When the Operator modifies the MODE to "Manual," the


MODEATTR is automatically transitioned from "Program" to "Operator."
Changing the MODEATTR to "Operator" locks out program access and
ensures that the Operator is not engaged in a struggle with a program
for control of the plant in a critical situation. The program can regain
access to the process when the MODEATTR is returned to "Program."

15.134 MODEAPPL[1..4]

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Mode Applicability - Defines changes for Regulatory Control function blocks.
Data Type Boolean
Range Off (0): Mode is not supported On (1): Mode is supported
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODE
Parameters
Remarks MODEAPPL[1] is On, if Manual (Man) mode is valid; otherwise, it is Off. MODEAPPL
[2] is On, if Automatic (Auto) mode is valid; otherwise, it is Off. MODEAPPL[3] is On,
if Cascade (Cas) mode is valid; otherwise, it is Off.

- 1741 -
Chapter 15 - Mxxxx Parameters

15.135 MODEATTR

Specific to SCM, RCM


Block(s)
Description Mode Attribute
Data Type Enumeration MODEATTR
Range Operator (1) Program (2) Normal (3)
Default Operator (1)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related COMMAND, CONTCUTOUT, CONTROLLOCK, MODE, SSTEPLOCK.
Parameters
Remarks MODE and COMMAND can only be accessed by an Operator, when MODEATTR is
Operator. When MODEATTR is Program, only programs can store to MODE and
COMMAND. Phase block will not issue commands while MODEATTR=OPERATOR.

15.136 MODEATTR

Specific to ACT
Block(s)
Description Activity Mode Attribute
Data Type ENUM ModeAttr
Range Operator (1): ActCOMMAND can only be accessed by an Operator Program (2): Only
programs can store to ActCOMMAND Normal (3): Parameter NORMMODEATTR of
the associated execution object determines MODEATTR
Default OPERATOR
Config No
Load
Active No
Loadable

- 1742 -
Chapter 15 - Mxxxx Parameters

Access Lock Operator


Residence CEE
Related COMMAND, ACTCOMMAND
Parameters
Remarks This parameter controls the access to the ActCommand parameter and is applied to
the activity when it is in the pre-exec and post-exec state. When the activity is
executing, this parameter is copied over to the SCM/RCM. When the value is
Normal (3), the activity goes to the RCM/SCM and retrieves the value for the
NormModeAttr.

NOTE When the Operator modifies the MODE to "Manual," the


MODEATTR is automatically transitioned from "Program" to "Operator."
Changing the MODEATTR to "Operator" locks out program access and
ensures that the Operator is not engaged in a struggle with a program
for control of the plant in a critical situation. The program can regain
access to the process when the MODEATTR is returned to "Program."

15.137 MODEATTR

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Mode Attribute determines where state commands to the Device Control Function
Blocks may originate, that is, who may set OP.
Data Type Enumeration MODEATTR
Range None (0) Operator (1): Only the operator may command the output state. Program
(2): Only ottagher Function Blocks (for example, Logic FBs, SCM programs) may
command the output state by setting OP or OPCMD[i]. Normal (3): When Normal is
stored to MODEATTR, the parameter is set to the present value of
NORMMODEATTR
Default Operator (0)
Config Yes
Load
Active No
Loadable

- 1743 -
Chapter 15 - Mxxxx Parameters

Access Lock Operator


Residence CEE
Related GOP, OPREQ, MODETRACK, OP, REDTAG. DEVCTL Only: CONTROLREQ,
Parameters NUMDOUTS, REDDATAA, REDDATAB.
Remarks DEVCTL Only: Access is illegal, if NUMDOUTS = 0. MODEATTR may not be changed
if REDTAG is on.

NOTE When the Operator modifies the MODE to "Manual," the


MODEATTR is automatically transitioned from "Program" to "Operator."
Changing the MODEATTR to "Operator" locks out program access and
ensures that the Operator is not engaged in a struggle with a program
for control of the plant in a critical situation. The program can regain
access to the process when the MODEATTR is returned to "Program."

Specific to MAINIBV
Block(s)
Description Mode Attribute
Data Type Enumeration
Range None (0) Operator (1): Only the operator may command OP. Program (2): Only other
Function Blocks (for example, Logic FBs, SCM programs) may command the output
state by setting OPENCMD or CLOSECMD. Normal (3): When Normal is stored to
MODEATTR, the parameter is set to the present value of NORMMODEATTR
Default OPERATOR
Config YES
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related OP
Parameters
Remarks
NOTE When the Operator modifies the MODE to "Manual," the
MODEATTR is automatically transitioned from "Program" to "Operator."
Changing the MODEATTR to "Operator" locks out program access and
ensures that the Operator is not engaged in a struggle with a program
for control of the plant in a critical situation. The program can regain
access to the process when the MODEATTR is returned to "Program."

- 1744 -
Chapter 15 - Mxxxx Parameters

15.138 MODEATTR

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Mode Attribute - Defines whether the operator or a user program has the authority
to change certain variables within this function block.
Data Type Enumeration MODEATTR
Range Operator (1): The operator can set MODE, OP, SP, RATIO and BIAS. Program (2):
The program (SCM) can set MODE, OP, SP, RATIO and BIAS.
Default Operator (1)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related MODE, OP, SP, X1.
Parameters
Remarks MODEATTR change requires the Safety Interlock Flag () and REDDATAA,
REDDATAB, REDTAG to be Off. MODEATTR is displayed near MODE on detail and
group displays. If MODEATTR is Program, a “-P” appears to the left of MODE; if it is
Operator, blanks are displayed next to MODE.

NOTE When the Operator modifies the MODE to "Manual," the


MODEATTR is automatically transitioned from "Program" to "Operator."
Changing the MODEATTR to "Operator" locks out program access and
ensures that the Operator is not engaged in a struggle with a program
for control of the plant in a critical situation. The program can regain
access to the process when the MODEATTR is returned to "Program."

15.139 MODEATTR

Specific to Series CSeries C AOCHANNEL and Series C DOCHANNEL


Block(s)
Description Mode Attribute
Data Type Enumeration
Range 1 Operator Operator provides the
channel's output value
2 Program Program can change the
channel's output value.
3 Normal Parameter NMODATTR
determines this point's
MODEATTR.
Default Operator

- 1745 -
Chapter 15 - Mxxxx Parameters

Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence IOM
Related MODE, MODEPERM, REDTAG
Parameters
Remarks This parameter determines whether the operator or the sequence program has
authority to change certain parameters of the associated channel block. For an
operator to change MODEATTR, MODEPERM must equal Permit and REDTAG must
be OFF. The setting for MODEATTR only affects the channel's output if MODE is set
to Man (Manual).

NOTE When the Operator modifies the MODE to "Manual," the


MODEATTR is automatically transitioned from "Program" to "Operator."
Changing the MODEATTR to "Operator" locks out program access and
ensures that the Operator is not engaged in a struggle with a program
for control of the plant in a critical situation. The program can regain
access to the process when the MODEATTR is returned to "Program."

15.140 MODEATTRCHGFL

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Mode attribute change flag
Data Type Boolean
Range ON OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters
Remarks

- 1746 -
Chapter 15 - Mxxxx Parameters

15.141 MODEATTRFL.NORM

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Normal Mode Attribute Flag - Indicates if mode attribute is normal; that is,
MODEATTR = NORMMODEATTR
Data Type Boolean
Range Off (0): Mode attribute is not normal On (1): Mode attribute is normal
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODEATTR, NORMMODEATTR.
Parameters
Remarks

Specific to Block(s) DEVCTL, MAINIBV, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Normal Mode Attribute Indicator Flag
Data Type Boolean
Range Off (0): Mode attribute is not normal On (1): Mode attribute is normal
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters MODEATTR, MODEATTRFL.OPER, MODEATTRFL.PROG.
Remarks Value is On if MODEATTR = NORMMODEATTR

15.142 MODEATTRFL.OPER

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Operator Mode Attribute Flag - Indicates if the mode attribute is Operator
Data Type Boolean
Range Off (0): Mode attribute is not Operator On (1): Mode attribute is Operator
Default Off (0)
Config Load No
Active No
Loadable

- 1747 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related MODEATTR
Parameters
Remarks

Specific to Block(s) DEVCTL, MAINIBV, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Operator Mode Attribute Indicator Flag
Data Type Boolean
Range Off (0): Mode attribute is not Operator On (1): Mode attribute is Operator
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters MODEATTR, MODEATTRFL.NORM.
Remarks Value is On if MODEATTR = Operator.

15.143 MODEATTRFL.PROG

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Program Mode Attribute Flag - Indicates if the mode attribute is Program.
Data Type Boolean
Range Off (0): MODEATTR is not currently Program. On (1): MODEATTR is currently
Program.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODEATTR
Parameters
Remarks

Specific to Block DEVCTL, MAINIBV, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


(s)
Description Program Mode Attribute Flag
Data Type Boolean
Range Off (0): MODEATTR is not currently Program. On (1): MODEATTR is currently
Program.

- 1748 -
Chapter 15 - Mxxxx Parameters

Default Off (0)


Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related MODEATTR, MODEATTRFL.NORM, MODEATTRFL.OPER.
Parameters
Remarks Value is On if MODEATTR = Program.

15.144 MODEATTRREF

Specific to CM
Block(s)
Description Mode Attribute Reference
Range Must be a parameter reference to a parameter of the CM or one of its contained
blocks. Must be of type enumertion or integer. Must accept input values of 1-
OPERATOR and 2-PROGRAM.
Default NULL
Config yes
Load
Active No
Loadable
Access Lock AppDev-Only
Residence CEE
Related MODETRACK SCMOPT
Parameters
Remarks This reference parameter specifies, which block parameter is the “master”
MODEATTR of the Control Module , since the CM itself does not have a MODEATTR
and may contain muttiple blocks with MODEATTR. The reference can be left empty.
In this case the MODETRACK parameter of SCM has no effect on this CM. This
parameter has no effect if SCMOPT <(less than or greater than)> COMMON.

15.145 MODECHANGE

Specific to All Regulatory Control Blocks


Block(s)
Description Mode Change - Indicates the first time mode changes to Auto or Cascade.
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active No
Loadable

- 1749 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks CAB programs may need to read this parameter to detect a mode change from
manual to auto or cascade. The flag will stay on for less than one cycle and so the
user will not be able to visibly see the state change.

15.146 MODEFL.AUTO

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Auto Mode Flag - Indicates if the mode is Auto.
Data Type Boolean
Range Off (0): Mode is not Auto. On (0): Mode is Auto.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODE
Parameters
Remarks

15.147 MODEEM

Specific to HRBALG_REG, HRBALG_HLPIUAO, HRBALG_HLPIUAC, HRBALG_HLPIUDO,


Blocks HRBALG_HLPIUDC
Description Emulation mode
Data Type Enumeration
Range MAN AUTO CAS BCAS
Default MAN
Config. Load No
Access Lock Operator
Residence NO LOAD
Related
Parameters
Remarks This parameter represents HG mode on HRB.

- 1750 -
Chapter 15 - Mxxxx Parameters

15.148 MODEFL.BCAS

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Backup Cascade Mode Flag - Indicates if the mode is Backup Cascade.
Data Type Boolean
Range Off (0): Mode is not Backup Cascade. On (1): Mode is Backup Cascade.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODE
Parameters
Remarks

15.149 MODEFL.CAS

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Cascade Mode Flag - Indicates if the mode is Cascade
Data Type Boolean
Range Off (0): Mode is not Cascade. On (1): Mode is Cascade.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODE
Parameters
Remarks

- 1751 -
Chapter 15 - Mxxxx Parameters

15.150 MODEFL.MAN

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Manual Mode Flag - Indicates if the mode is Manual.
Data Type Boolean
Range Off (0): Mode is not Manual. On (1): Mode is Manual.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODE
Parameters
Remarks

15.151 MODEFL.NORM

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Mode Flag Normal - Indicates if mode is normal; that is, MODE = NORMMODE.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODE, NORMMODE.
Parameters
Remarks Although MODE and NORMMODE share the same enumeration, MODE cannot be
set to NONE and NORMMODE cannot be set to NORMAL. Control Builder checks
status at load time and triggers an error flag, if it detects any problems.

- 1752 -
Chapter 15 - Mxxxx Parameters

15.152 MODELINDEX

Specific to Block(s) ProfitCtl


Description Model Index
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

15.153 MODELISVALID

Specific to Block(s) PROFITCTLIN, PROFCON, PROFCONOUT


Description Model Is Valid
Data Type ENUM
Range No (0) Yes (1)
Default NO
Config Load Yes
Active Loadable No
Access Lock APPDEVONLY
Residence ERDB
Related Parameters
Remarks

15.154 MODELNAME

Specific to Block(s) Server


Description Model Name
Data Type BlockId
Range
Default Null
Config Load No
Active Loadable No

- 1753 -
Chapter 15 - Mxxxx Parameters

Access Lock Application Developer Only


Residence SCAN
Related Parameters
Remarks Array of BlockIds for the root of each model loaded.

15.155 MODELNUM

Specific to Block(s) UIO


Description Model Number
Data Type String
Range N/A
Default N/A
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence UIO
Related
Parameters

Remarks Number displayed on the maintenance tab indicating the module’s model
number.

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Model Number
Data Type String
Range N/A
Default N/A
Config Load NO
Active No
Loadable

Access Lock ViewOnly


Residence IOM Block
Related
Parameters

Remarks Number displayed on the maintenance tab indicating the module’s model number.

- 1754 -
Chapter 15 - Mxxxx Parameters

15.156 MODELPV

Specific to PID-PL
Block(s)
Description Raw predicted PV - The unbiased predicted value for the process variable, PV.
Data Type Float64
Range
Default 0
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related PV, model parameters.
Parameters
Remarks The user cannot fix the value of MODELPV. Writing to this parameter forces a reset
of its value to the current PV. To get an idea of the accuracy of process model, trend
the MODELPV against the actual PV. This parameter is applicable only when
CTLEQN is set to Profit Loop PKS, and is ignored in PID control equations.

15.157 MODELUPDATED

Specific to PID-PL
Block(s)
Description Model Updated with Displayed Values - Indicates whether model in function
block matches displayed values.
Data Type Boolean
Range True (1) Model in function block matches
displayed values.
False (0) Model in function block does not match
displayed values.
Default True (1)
Config Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related NUMCOEFNUM, NUMCOEFDEN, N, PROCGAIN, PROCDEADTIME,
Parameters UPDATEMODEL, RESETMODEL
Remarks

- 1755 -
Chapter 15 - Mxxxx Parameters

15.158 MODELXM_BLOB

Specific to Block(s) ProfitCtl


Description Array of Compressed XM Data
Data Type STRING
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

15.159 MODELXM_BLOB_NUMBER_OF_BYTES

Specific to Block(s) ProfitCtl


Description Compressed XM Data Size in number of bytes
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

15.160 MODELXM_BLOB_SIZE

Specific to Block(s) ProfitCtl


Description Array size required for MODELXM_BLOB
Data Type INT32
Range NA
Default 0
Config Load Yes
Active Loadable No

- 1756 -
Chapter 15 - Mxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related Parameters
Remarks

15.161 MODELXS_BLOB

Specific to Block(s) ProfitCtl


Description Array of Compressed XS Data
Data Type STRING
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

15.162 MODELXS_BLOB_NUMBER_OF_BYTES

Specific to Block(s) ProfitCtl


Description Compressed XS Data Size in number of bytes
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

- 1757 -
Chapter 15 - Mxxxx Parameters

15.163 MODELXS_BLOB_SIZE

Specific to Block(s) ProfitCtl


Description Array size required for MODELXS_BLOB
Data Type INT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

15.164 MODEOUT

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Mode Output - Indicates the Last MODE value stroed to the Universal Control
Network (UCN) Process Manager MODE parameter. It does not monitor the current
MODE of the UNC point.
Data Type Enumeration
Range (2) Cascade (4) None
Default (4) None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related MAXMINRATIO RELAYPRESENT, RELEASEOPT MODEOUT
Parameters
Remarks After block activation, a value of None is provided. Once the first cascade request is
responded to with a store to Cascade to the UCN point MODE, this parameter will
provide a value of Cascade.

- 1758 -
Chapter 15 - Mxxxx Parameters

15.165 MODEPERM

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description Mode Permissive - Indicates if the operator can change the mode of a function
block.
Data Type Enumeration MODEPERM
Range NOTPERM (0) - Operator is not permitted to change the mode. PERMIT (1) -
Operator is permitted to change the mode.
Default PERMIT (1)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODE
Parameters
Remarks

15.166 MODEPERM

Specific to Series CSeries C AOCHANNEL and Series C DOCHANNEL


Block(s)
Description Mode Permissive
Data Type Enumeration
Range 0 NOTPERM Users cannot change this
channel's mode.
1 PERMIT Users can change this channel's
mode.
Default Permit
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOM
Related MODE, MODEATTR
Parameters
Remarks This parameter determines if the operator is permitted to change the mode of
this channel.

- 1759 -
Chapter 15 - Mxxxx Parameters

15.167 MODE POLICING

Specific to HRBALG_REG block


Blocks
Description HRB Mode Policing
Data Type BOOLEAN
Range ON/OFF

Default ON
Config. Yes
Load
Access Lock Engineer
Residence CEE
Related None
Parameters
Remarks This parameter enables or disables the mode policing done by the HRB block. When
the parameter is set to ON, the HRB block drives the mode and ModeAttr. When the
parameter is set to OFF, the HRB block will not do mode policing and will not update
the mode to the HG point.

15.168 MODEREQ

Specific to RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL, PIDER,
Block(s) PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer, and
Switch.
Description The requested MODE. The SCM CONTROLREQ (Control Request) wants to change
the Regulatory Block's MODE.
Data Type Enumeration REGMODE
Range Man (0) Auto (1) Cas (2) None (3)
Default None (3)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related CONTROLREQ, LASTMODEREQ, SCMOPT.
Parameters
Remarks

- 1760 -
Chapter 15 - Mxxxx Parameters

15.169 MODESEL.AUTO

Specific to ENHREGCALC,RATIOBIAS,PIDFF,POSPROP, PIDER, RATIOCTL, PID-PL, PID


Block(s)
Description MODESEL.AUTO determines if AUTO mode will be available in the MODE list or not.

Data Type BOOLEAN


Range 0 – 1 (0 – OFF, 1 – ON)
Default On (Checked)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODE
Parameters
Remarks ON indicates that AUTO Mode will be a part of the MODE list displayed. OFF
indicates, that AUTO Mode will not be a part of the MODE list displayed.

15.170 MODESEL.BCAS

Specific to REMCAS
Block(s)
Description MODESEL.BCAS determines if BCAS mode will be available in the MODE list or not.
Data Type Boolean
Range 0 – 1 (0 – OFF, 1 – ON)
Default ON (Checked)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODE
Parameters
Remarks ON indicates that BCAS mode will be a part of the MODE list displayed. OFF
indicates, that BCAS mode will not be a part of the MODE list displayed.

- 1761 -
Chapter 15 - Mxxxx Parameters

15.171 MODESEL.CAS

Specific to AUTOMAN,FANOUT,ENHREGCALC,SWITCH,OVRDSEL,REGCALC,RATIOBIAS,PIDFF,
Block(s) POSPROP, PIDER, RATIOCTL, PID-PL, PID, REGSUMMER
Description MODESEL.CAS determines if CAS mode will be available in the MODE list or not.
Data Type Boolean
Range 0 – 1 (0 – OFF, 1 – ON)
Default ON (Checked)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODE
Parameters
Remarks ON indicates that CAS mode will be a part of the MODE list displayed. OFF indicates,
that CAS mode will not be a part of the MODE list displayed.

15.172 MODESEL.MAN

Specific to AUTOMAN,FANOUT,ENHREGCALC,SWITCH,OVRDSEL,REGCALC,RATIOBIAS,PIDFF,
Block(s) POSPROP, PIDER, RATIOCTL, PID-PL, PID, REGSUMMER, REMCAS, RAMPSOAK
Description MODESEL.MAN determines if MAN mode will be available in the MODE list or not.
Data Type Boolean
Range 0 – 1 (0 – OFF, 1 – ON)
Default ON (Checked)
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related MODE
Parameters
Remarks ON indicates that MAN mode will be a part of the MODE list displayed. OFF indicates,
that MAN mode will not be a part of the MODE list displayed.

- 1762 -
Chapter 15 - Mxxxx Parameters

15.173 MODESEL.PROGRAM

Specific to AUTOMAN,FANOUT,ENHREGCALC,SWITCH,OVRDSEL,REGCALC,RATIOBIAS,PIDFF,
Block(s) POSPROP, PIDER, RATIOCTL, PID-PL, PID, REGSUMMER, REMCAS, RAMPSOAK,
DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER, MAINIBV.
Description MODESEL.PROGRAM determines if PROGRAM mode attribute will be available in
the MODEATTR list or not.
Data Type Boolean
Range 0 – 1 (0 – OFF, 1 – ON)
Default ON (Checked)
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related MODEATTR
Parameters
Remarks ON indicates that PROGRAM Mode Attribute will be a part of the MODEATTR list
displayed. OFF indicates, that PROGRAM Mode Attribute will not be a part of the
MODEATTR list displayed.

15.174 MODETRACK

Specific to DevCtl RegCtl Blocks: AutoMan, EnhRegCalc, Fanout, OvrdSel, PID, PIDFF, PID-PL,
Block(s) PIDER, PosProp, RampSoak, RatioCtl, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: HTmotor, LTmotor, Solenoid, ValveDamper
Description Sequential Control Module (SCM) Mode Tracking Option - A configurable
parameter that defines how the regulatory control or device control FB will set the
state of the MODEATTR based upon the MODE of the SCM.
Data Type Enumeration MODETRACK
Range None (0) OneShot (1) ContRtn (2) SemiCont (3) Cont (4)
Default OneShot (1)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODEATTR SCMMODE, SCMOPT, SCMSTATE.
Parameters
Remarks Is invalid if ControlModule.SCMOPT ≠ Fixed.

- 1763 -
Chapter 15 - Mxxxx Parameters

15.175 MODETRACK

Specific to SCM, RCM


Block(s)
Description Mode Tracking Option - A configurable parameter that defines how the regulatory
control or device control FB will set the state of the MODEATTR based upon the
MODE of the SCM.
Data Type Enumeration
Range 0 None When no tracking is enabled, the MODEATTR does not
change from the default OPERATOR.
1 OneShot One shot tracking changes the value of the MODEATTR to
PROGRAM when the MODE changes to any of the auto
values or the STATE changes to running. (MODEATTR
changeable by operator)
2 ContRtn Continuous tracking with return changes the MODEATTR
state to PROGRAM, if MODE or STATE change (MODEATTR
cannot be changed by the operator). If MODE is changed
to MANUAL when MODEATTR is in the Program state,
MODEATTR is changed to OPERATOR.

3 SemiCont Semi-continuous tracking changes the value of


MODEATTR to PROGRAM, if the MODE, STATE, or any SCM
or any SCM Step Output want's to control the device. If the
MODE is changed back to MANUAL when MODEATTR is
set to PROGRAM, change MODEATTR back to OPERATOR
4 Cont Continuous tracking changes the MODEATTR to
PROGRAM, if the MODE is set to any of the auto modes.
(MODEATTR cannot be changed by the operator). If
MODEATTR is set to PROGRAM and the MODE changes to
MANUAL than the MODEATTR does not change, but can
be changed by the operator.
Default OneShot
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks See Modetrack processing in the Sequential Control User's Guide for more
information.

- 1764 -
Chapter 15 - Mxxxx Parameters

15.176 MODHASBKUP

Specific to
Block ACE
Description ACE has backup
Data Type BOOLEAN
Range OFF ON
Default OFF
Config
Load Yes
Active
Loadable Yes
Access
Lock AppDevOnly
Residence CEE
Related
Parameters HOSTIPPRI

This parameter indicates that this ACE has Backup and can be used for cut-over.
When this parameter is set as "TRUE," the HOSTNAMEPRI is not available for
configuration and the floating IP must be provided in HOSTIPPRI. If this parameter
is set to "FALSE," ACE node does not have Backup and cannot perform the cut-over.
While loading ACE, if the MODHASBKUP parameter is set as "TRUE," the validation
occurs and verifies whether the configured HOSTIPPRI matches the floating IP
Remarks configured on the ACE.

Specific to
Block OPC Gateway, Inter Cluster Gateway
Description ACE has backup
Data Type BOOLEAN
Range OFF ON
Default OFF
Config
Load Yes
Active
Loadable Yes
Access
Lock AppDevOnly
Residence CEE
Related
Parameters GWHOSTIPPRI

This parameter indicates that this ACE in which the OPCG/ICG is loaded has
Backup and can be used for cut-over. When this parameter is set as "TRUE," the
GWHOSTNAMEPRI is not available for configuration and the floating IP must be
provided in GWHOSTIPPRI. If this parameter is set to "FALSE," ACE node does not
have Backup and cannot perform the cut-over. While loading ACE, if the
MODHASBKUP parameter is set as "TRUE," the validation occurs and verifies
whether the configured GWHOSTIPPRI matches the floating IP configured on the
Remarks ACE.

- 1765 -
Chapter 15 - Mxxxx Parameters

15.177 MODIFIEDBY

Specific to All Blocks


Block(s)
Description Last modified by.
Data Type String
Range Length : 40 characters
Default Null
Config Load Yes
Active No Yes (CM, SCM, RCM)
Loadable
Access Lock Application Developer Only
Residence Server
Related DATECREATED, CREATEDBY, VERSIONNUM, QUALSTATE, VERSION,
Parameters VERSIONDATE
Remarks Identifies user who made last modifications to block, if operator security is
implemented. Otherwise, may just show default login. If this block is in Version
Control System, modifications apply to last version of block.

Specific to Block(s) UOC


Description Last Modified By
Data Type STRING
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SCAN
Related Parameters
Remarks

15.178 MODISREDUN

Specific to C300, CN100, FIM, CPM, IOLIM, LIOM, FTEB, EHG FIM4, RM, PGM, EHPM , TCMI,
Block(s) UOC, EIM 1757-SRM
Description Module is redundant - Defines whether this module is redundant or not.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable

- 1766 -
Chapter 15 - Mxxxx Parameters

Access Lock Engineer


Residence Primary C300, PGM, EHPM For the Secondary C300 FB and both primary and
secondary C200(CPM), IOLIM, FTEB parameter is SR resident.
Related ABORTALM.PR
Parameters
Remarks A check in the check box means the module is redundant and the function is On.

15.179 MODSTATE

Specific to IOLIM, Secondary IOLIM, SIMIOLIM


Block(s)
Description IOLIM State. Shows the current state of the associated IOLIM.
Data Type Enumeration
Range UNKNOWN: The IOLIM state is unknown. TESTING, BOOTING,
ALIVE, LOADING, PROGRAMMING, PIREADY,
FAILED.
NODB: The IOLIM does not have a valid database.
OK: The IOLIM is the current Primary and is functioning
properly.
FAILED: The IOLIM has failed.
BACKUP: The IOLIM is the current secondary.
Default UNKNOWN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks The Secondary IOLIM block's MODSTATE can only be UNKNOWN or BACKUP. This
block replaces the MODSTATE block.

15.180 MODTYPE

Specific to Block C300, PGM, FIM4, EHPM


(s)
Description Module Type - Indicates the hardware type and details like model number,
number of IOLINKS.
Data Type String
Range Length: 64 characters
Default
Config Load No

- 1767 -
Chapter 15 - Mxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

Specific to Block(s) EIM


Description Module Type
Data Type String
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

Specific to Block(s) UOC


Description Module Type
Data Type STRING
Range N/A
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (hardware statistics, see C300 definition)

Specific to Block TCMI


(s)
Description Module Type - Indicates the hardware type and details like model number,
number of IOLINKS.
Data Type String
Range Length: 64 characters
Default UEA
Config Load No
Active Loadable No

- 1768 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

15.181 MODTYPEA

Specific to RM
Block(s)
Description Module Type - For each module in the host chassis, text description of module type
based on module's Product Type and Product Code values.
Data Type Enumeration [20]
Range UNK (0) --- (1) CPM (2) CNB (3) RM (4) AC (5) IOM (6) SP1 (7) SP2 (8) SP3 (9) SP4
(10) SP5 (11)
Default --- (1)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related PRODCODEAPRODTYPEA
Parameters
Remarks

15.182 MOMSTATE

Specific to DevCtl
Block(s)
Description Momentary Output States
Data Type Enumeration MOMSTATE
Range None (0) Mom_1 (1) Mom_0 (2) Mom_2 (3) Mom_1_2 (4) Mom_0_2 (5) Mom_0_1 (6)
Default None (0)
Config Yes
Load
Active No
Loadable

- 1769 -
Chapter 15 - Mxxxx Parameters

Access Engineer
Lock
Residence CEE
Related GOP, NUMSTATES, OP, OPDOMAP[0..3][1..3], SAFEOP.
Parameters
Remarks Access is illegal, if NUMDOUTS = 0. The function block must be inactive to change
MOMSTATE. MOMSTATE is inaccessible if REDDATAA, REDDATAB, REDTAG is set.
MOMSTATE may not be set if SEALOPT is Enabled. Mom_1: State1 is momentary; it
can only be selected if SAFEOP does not = State1. Mom_0: State0 is momentary; it
can only be selected if SAFEOP does not = State0. Mom_2: State2 is momentary; it
can only be selected if NUMSTATES = 3 and SAFEOP does not = State2. Mom_1_2:
Both State1 and State2 are momentary; they can only be selected if NUMSTATES =
3, and SAFEOP = State0. Mom_0_2: Both State0 and State2 are momentary; they
can only be selected if NUMSTATES = 3, and SAFEOP = State1. Mom_0_1: Both
State0 and State1 are momentary; they can only be selected if NUMSTATES = 3,
and SAFEOP = State2.

15.183 MONACTCMD

Specific to Block(s) C300, IOLIM, FTEB, SIMIOLIM, FIM4, PGM, EHPM


Description Enumeration for Activate
Data Type Enumeration
Range Refer to PCMSTATE, EHPMSTATE
Default RUN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, IOLIM, FTEB, SIMIOLIM, FIM4, PGM, EHPM
Related Parameters
Remarks

Specific to Block(s) EIM


Description Enum for activate
Data Type ENUM
Range NA
Default ACTIVE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

- 1770 -
Chapter 15 - Mxxxx Parameters

Specific to Block(s) UOC


Description Enum for activate
Data Type ENUM
Range N/A
Default CEERUN
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

15.184 MONCMDPARAM

Specific to Block(s) C300, IOLIM, FTEB, SIMIOLIM


Description Parameter Stores Activation
Data Type String
Range Length: 64 Characters
Default PCMSTATE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, IOLIM, FTEB, SIMIOLIM
Related Parameters
Remarks

Specific to Block(s) EIM


Description Parameter Stores Activation
Data Type String
Range NA
Default EXECSTATE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

- 1771 -
Chapter 15 - Mxxxx Parameters

15.185 MONINACTCMD

Specific to Block(s) C300, IOLIM, FTEB, SIMIOLIM, FIM4, PGM, EHPM


Description Enumeration for Inactivate
Data Type Enumeration
Range Refer to PCMSTATE, EHPMSTATE
Default Refer to PCMSTATE, EHPMSTATE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, IOLIM, FTEB, SIMIOLIM, FIM4, PGM, EHPM
Related Parameters
Remarks

Specific to Block(s) EIM


Description Enum for inactivate
Data Type ENUM
Range NA
Default INACTIVE
Config Load No
Active Loadable No
Access Lock INACTIVE
Residence NOLOAD
Related Parameters
Remarks

Specific to Block(s) UOC


Description Enum for inactivate
Data Type ENUM
Range N/A
Default CEEIDLE
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

- 1772 -
Chapter 15 - Mxxxx Parameters

15.186 MONLDCMD

Specific to Block(s) C300, IOLIM, FTEB, SIMIOLIM, EIM


Data Type Enumeration
Range Refer PCMSTATE
Default IDLE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, IOLIM, FTEB, SIMIOLIM, NOLOAD
Related Parameters
Remarks

15.187 MONREADLDUI

Specific to Block(s) C300, IOLIM, FTEB, SIMIOLIM, FIM4, PGM, EHPM


Description Parameter read for LoadUI
Data Type String
Range Length: 32 Characters
Default Refer to PCMSTATE, EHPMSTATE, cpmstate
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, IOLIM, FTEB, SIMIOLIM, FIM4, PGM, EHPM
Related Parameters
Remarks

15.188 MONREADPARAM

Specific to Block(s) C300, IOLIM, IOLINK, Secondary IOLINK, FTEB, SIMIOLIM, FIM4, PGM,
EHPM, EIM
Description Parameter to be monitored
Data Type String
Range Length: 32 Characters
Default ICONSTATE
Config Load No
Active Loadable No

- 1773 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence C300, IOLIM, IOLINK, FTEB, SIMIOLIM, FIM4, PGM, EHPM, NOLOAD
Related
Parameters
Remarks

Specific to C300, FIM4, BCM and FTEB OPC, ICG, IOLINK, SIMIOLINK, HLAI, STIMV, LLMUX,
Block(s) LLAI, RHMUX, AO8, AO16, DO16, DO32, DI, DI24V, DISOE, AO16HART, HLAIHART,
AOCHANNEL, AICHANNEL, DOCHANNEL, DICHANNEL, HAICHANNEL,
HAOCHANNEL, AI-HART, AI-LLMUX, AO-HART, DI-HV, DI-24, DO-24B,
HARTDEVICE, LOGIX1200_0104, ST3000_0103, ST3000_0202, STT25H_0103, CB,
AMC, HLPIU, LEPIU, LLPIU, DHP, AMCRCD. CBRCD. SLINKB. SLINKA. UOC
Description Parameter to be monitored
Data Type String
Range Length: 32 Characters
Default ICONSTATE
Config No
Load
Access Lock ViewOnly
Residence C300, BCM, IOLIM, FTEB, SIMIOLIM, FIM4, NOLOAD
Related -
Parameters
Remarks -

15.189 MONRQDLD

Specific to Block(s) C300, IOLIM, FTEB, SIMIOLIM, EIM


Description Required Load State
Data Type Enumeration
Range Refer to PCMSTATE
Default NonRdnIdle, INACTIVE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, IOLIM, FTEB, SIMIOLIM
Related Parameters
Remarks

- 1774 -
Chapter 15 - Mxxxx Parameters

15.190 MONSTATES

Specific to Block(s) C300, IOLIM, FTEB, SIMIOLIM, FIM4, PGM, EHPM, EIM, UOC
Description Enumeration values for each state
Data Type Enumeration
Range Refer to ICONSTATE
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, IOLIM, FTEB, SIMIOLIM, FIM4, PGM, EHPM, NOLOAD
Related Parameters
Remarks

15.191 MONTASKREF

Specific to Step
Block(s)
Description Step Monitoring Task Reference
Data Type Parameter Id
Range Any Tag.[Block].Parameter reference
Default “”
Config Yes
Load
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related
Parameters
Remarks Identifies a parameter as the Monitoring Task result associated with the Step. The
identified parameter is interpreted as a Boolean value (0 is Off; non-0 is On) even if
the parameter data type is not Boolean. The parameter is monitored and an
indication shown on the SCM Table view associated with the Step. A “Monitoring
Task” is a control strategy that evaluates a process condition for which the result is
normally True/On or False/Off.

- 1775 -
Chapter 15 - Mxxxx Parameters

15.192 MONTH

Specific to ACE, CPM, SIM_C200, CEEC300, EHG, CPM200,CPM,CPM200S,ACE,SIM-


Block(s) C200,CEEC300,EHG,EHGS, CEEUOC, CEECN100
Description Defines the month component of the Controller's local time. Current Month
Data Type 32-Bit Integer
Range 1 to 12 (January to December)
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE, C200(CPM), SIM_C200, C300(CEEC300, UOC(CEEUOC), CN100(CEECN100)
Related DAYLIGHTTIME, TIMEZONE.
Parameters
Remarks Defines the current minute component of the Controller's local time.

15.193 MOTIONBIT[1..4]

Specific to JAGXCHAN
Block(s)
Description Motion Bit
Data Type Boolean
Range Off(0) No Motion
On(1) Motion
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 12 of the status word in the floating point input assembly
for the designated scale slot [1..4].

- 1776 -
Chapter 15 - Mxxxx Parameters

15.194 MOTORTRIPALM.FL

Specific to Block(s) HTMOTOR, LTMOTOR, VALVEDAMPER


Description Motor Trip Alarm Flag
Data Type Boolean
Range OFF ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters MOTORTRIPALM.OPT, MOTORTRIPALM.SV, MOTORTRIPALM.PR.
Remarks

15.195 MOTORTRIPALM.OPT

Specific to Block(s) HTMOTOR, LTMOTOR, VALVEDAMPER


Description Motor Trip Alarm Option
Data Type Enumeration
Range ENABLE DISABLE
Default ENABLE
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MOTORTRIPALM.FL, MOTORTRIPALM.SV, MOTORTRIPALM.PR
Remarks

15.196 MOTORTRIPALM.PR

Specific to Block(s) HTMOTOR, LTMOTOR, VALVEDAMPER


Description Motor Trip Alarm Priority
Data Type Enumeration
Range NONE JOURNAL LOW HIGH URGENT
Default LOW
Config Load YES
Active Loadable No

- 1777 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MOTORTRIPALM.FL, MOTORTRIPALM.SV, MOTORTRIPALM.OPT
Remarks

15.197 MOTORTRIPALM.SV

Specific to Block(s) HTMOTOR, LTMOTOR, VALVEDAMPER


Description Motor Trip Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MOTORTRIPALM.FL, MOTORTRIPALM.OPTMOTORTRIPALM.PR
Remarks

15.198 MPCFREEMEM

Specific to CEEC300
Block(s)
Description MIMO MPC Free Memory - Shows amount of currently free memory in MIMO MPC
memory pool.
Data Type INT32
Range 0 to 17403904 Bytes
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCMAXFREEBLKSZ, MPCTOTALMEM, MPCUSEDMEM
Parameters
Remarks The free memory decreases as blocks are loaded and increases as blocks are
unloaded. The difference between MPCTOTALMEM and MPCFREEMEM is equal to
MPCUSEDMEM

- 1778 -
Chapter 15 - Mxxxx Parameters

15.199 MPCFREEMEMINK

Specific to CEEC300
Block(s)
Description Amount of free memory in MIMO MPC memory pool in units of kilo bytes
Data Type INT32
Range 0 to 17403904 Bytes
Default N/A
Config No
Load
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCMAXFREEINK, MPCTOTALMEMINK, MPCUSEDMEMINK
Parameters
Remarks This parameter indicates total amount of unused memory in the MIMO MPC
memory pool. MIMO MPC Free memory decreases as CMs with Profit Controller FBs
are loaded and activated and increases as CMs with Profit Controller FBs are
inactivated and deleted. The difference between MPCTOTALMEMINK and
MPCFREEMEMINK is equal to MPCUSEDMEMINK.

15.200 MPCMAXFREEBLKSZ

Specific to CEEC300
Block(s)
Description Size of largest contiguous memory block in MIMO MPC memory pool
Data Type INT32
Range 0 to 17403904 Bytes
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCFREEMEM, MPCTOTALMEM, MPCUSEDMEM
Parameters
Remarks MPCMAXFREEBLKSZ gives the largest amount of memory currently available to a
contiguous block for MIMO MPC configuration. MPCMAXFREEBLKSZ is always less
than or equal to MPCFREEMEM.

- 1779 -
Chapter 15 - Mxxxx Parameters

15.201 MPCMAXFREEINK

Specific to CEEC300
Block(s)
Description Size of largest contiguous memory block in MIMO MPC memory poo in units of kilo
bytes
Data Type INT32
Range 0 to 17403904 Bytes
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCFREEMEMINK, MPCTOTALMEMINK, MPCUSEDMEMINK
Parameters
Remarks MPCMAXFREEINK gives the largest amount of memory currently available to a
contiguous block configuration. MPCMAXFREEINK is always less than or equal to
MPCFREEMEMINK.

15.202 MPCNTOTMEMDESC

Specific to CEEC300
Block(s)
Description Total Number of MIMO MPC Memory Descriptors available
Data Type INT32
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300
Related MPCFREEMEM, MPCMAXFREEBLKSZ, MPCNTOTMEMDESC, MPCNUMEXTBLKS,
Parameters MPCNUMFREEBLKS, MPCNUMFREEDESC, MPCNUMREGDESC,
MPCNUMUSEDBLKS, MPCTOTALMEM, MPCNUMFREEBLKS,MPCUSEDMEM
Remarks This is a static number. Units are number of descriptors

- 1780 -
Chapter 15 - Mxxxx Parameters

15.203 MPCNUMFREEBLKS

Specific to CEEC300,
Block(s)
Description Number of Free MIMO MPC Memory Blocks
Data Type INT32
Range 0 to 17403904
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCFREEMEM, MPCMAXFREEBLKSZ, MPCNTOTMEMDESC, MPCNUMEXTBLKS,
Parameters MPCNUMFREEBLKS, MPCNUMFREEDESC, MPCNUMREGDESC,
MPCNUMUSEDBLKS, MPCTOTALMEM, MPCNUMFREEBLKS,MPCUSEDMEM
Remarks Memory is not sectioned into blocks until it is used. It is common to have only one
free memory block. Use MPCMAXFREEBLKSZ to the size of the largest free block.
Units are number of blocks - Blocks vary in size.

15.204 MPCNUMFREEDESC

Specific to CEEC300
Block(s)
Description Number of Free (available) MIMO MPC Memory Descriptors
Data Type INT32
Range 0 to MPCNTOTMEMDESC
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCFREEMEM, MPCMAXFREEBLKSZ, MPCNTOTMEMDESC, MPCNUMEXTBLKS,
Parameters MPCNUMFREEBLKS, MPCNUMFREEDESC, MPCNUMREGDESC,
MPCNUMUSEDBLKS, MPCTOTALMEM, MPCNUMFREEBLKS,MPCUSEDMEM
Remarks Units are number of descriptors.

- 1781 -
Chapter 15 - Mxxxx Parameters

15.205 MPCNUMREGDESC

Specific to CEEC300
Block(s)
Description Number of Registered MIMO MPC Memory Descriptors
Data Type INT32
Range 0 to MPCNTOTMEMDESC
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCFREEMEM, MPCMAXFREEBLKSZ, MPCNTOTMEMDESC, MPCNUMEXTBLKS,
Parameters MPCNUMFREEBLKS, MPCNUMFREEDESC, MPCNUMREGDESC,
MPCNUMUSEDBLKS, MPCTOTALMEM, MPCNUMFREEBLKS,MPCUSEDMEM
Remarks It is common for this number to be close to zero, since descriptors are registered
when connections are lost. Units are number of descriptors.

15.206 MPCNUMUSEDBLKS

Specific to CEEC300
Block(s)
Description Number of Used MIMO MPC Memory Blocks
Data Type INT32
Range 0 to 17403904
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCFREEMEM, MPCMAXFREEBLKSZ, MPCNTOTMEMDESC, MPCNUMFREEBLKS,
Parameters MPCNUMFREEDESC, MPCNUMREGDESC, MPCNUMUSEDDESC, MPCTOTALMEM,
MPCUSEDMEM
Remarks Units are number of blocks – Blocks vary in size.

- 1782 -
Chapter 15 - Mxxxx Parameters

15.207 MPCNUMUSEDDESC

Specific to CEEC30000
Block(s)
Description Number of MIMO MPC Used Memory Descriptors – Equal to MPCNTOTMEMDESC
– MPCNUMFREEDESC
Data Type INT32
Range 0 to MPCNTOTMEMDESC
Default 0
Config Load No
Active No
Loadable
Access Lock View Only
Residence C300(CEEC300)
Related MPCFREEMEM, MPCMAXFREEBLKSZ, MPCNTOTMEMDESC, MPCNUMEXTBLKS,
Parameters MPCNUMFREEBLKS, MPCNUMFREEDESC, MPCNUMREGDESC,
MPCNUMUSEDBLKS, MPCTOTALMEM, MPCNUMFREEBLKS
Remarks Units are number of descriptors

15.208 MPCTOTALMEM

Specific to Block CEEC300


(s)
Description Total size of MIMO MPC memory pool
Data Type INT32
Range 0 to 17403904 Bytes
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence C300
Related MPCFREEMEMINK, MPCMAXFREEINK, MPCUSEDMEMINK
Parameters
Remarks The difference between MPCTOTALMEMINK and MPCFREEMEMINK is equal to
MPCUSEDMEMINK.

- 1783 -
Chapter 15 - Mxxxx Parameters

15.209 MPCTOTALMEMINK

Specific to Block CEEC300


(s)
Description Total Memory - Lists total size of MIMO MPC memory pool in kilo bytes.
Data Type INT32
Range 0 to 16996 Bytes
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence C300
Related MPCFREEMEM, MPCMAXFREEBLKSZ, MPCUSEDMEM
Parameters
Remarks The difference between MPCTOTALMEM and MPCFREEMEM is equal to
MPCUSEDMEM.

15.210 MPCUSEDMEM

Specific to CEEC300
Block(s)
Description MIMO MPC Used Memory – Shows total amount of used memory in MIMO MPC
memory pool
Data Type INT32
Range 0 to 17403904 Bytes
Default N/A
Config No
Load
Active No
Loadable
Access Lock View Only
Residence C300
Related MPCFREEMEM, MPCTOTALMEM, MPCMAXFREEBLKSZ
Parameters
Remarks The MIMO MPC used memory increases as CM with Profit Controller FBs are loaded
and activated. The MIMI MPC used memory decreases as CMs with Profit Controller
FBs blocks are inactivated and deleted. The difference between MPCTOTALMEM
and MPCUSEDMEM is equal to MPCFREEMEM.

- 1784 -
Chapter 15 - Mxxxx Parameters

15.211 MPCUSEDMEMINK

Specific to CEEC300
Block(s)
Description Total amount of used memory in CEE user memory pool
Data Type INT32
Range 0 to 16996 Bytes
Default 0
Config No
Load
Active No
Loadable
Access Lock View Only
Residence C200, C300
Related MPCMAXFREEINK, MPCTOTALMEMINK, MPCFREEMEMINK
Parameters
Remarks The MIMO MPC used memory increases as CM with Profit Controller FBs are
loaded and activated. The MIMI MPC used memory decreases as CMs with Profit
Controller FBs blocks are inactivated and deleted. The difference between
MPCTOTALMEMINK and MPCUSEDMEMINK is equal to MPCFREEMEMINK.

15.212 MPVEM

Specific to Regulatory HRB


Blocks
Description Manual PV in LEADLAG algorithm
Data Type FLOAT 64
Range
Default NaN
Config. Load No
Access Lock Operator
Residence NO LOAD
Related
Parameters
Remarks This parameter represents Manual PV in LEADLAG algorithm. This is not
applicable for any algorithm other than LEADLAG.

- 1785 -
Chapter 15 - Mxxxx Parameters

15.213 MSGBUFPEAKPCT

Specific to Block ELCN_BRG


(s)

Description Message Peak [%]

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related ELCN Bridge Statistics tab


Parameters

Remarks Highest amount of buffers allocated for re-assembling packets into messages
between LCN and ELCN

15.214 MSGDATAFMT [0…15]

Specific to MESSAGE
Block(s)
Description Message Data Format
Data Type Enumeration PVFORMAT
Range D0 (0)
D1 (1)
D2 (2)

D3 (3)
Default D1 (1)
Config Load Yes
Active No
Loadable

- 1786 -
Chapter 15 - Mxxxx Parameters

Access Lock Application Developer Only


Residence SRAL
Related MESSAGE [0…15]
Parameters
MSGDATASRC [0…15]
Remarks The MSGDATAFMT is used to set the decimal format of the configured MSGDATASRC
of type float. It is not applicable for the non-float data type values.
The MSGDATAFMT is set to PVFORMAT by default, which is configured in the data
source block. This is applicable for the following conditions:
1. The configured data source point is PV.
2. Data source block should have PVFORMAT parameter.

The MSGDATAFMT is set to D1 by default, when the above conditions are not
applicable.

15.215 MSGDATASRC [0…15]

Specific to MESSAGE
Block(s)
Description Message Data Source
Data Type INOUTCONN
Range Not Applicable
Default Not Applicable
Config Load Yes
Active No
Loadable
Access Application Developer Only
Lock
Residence CEE
Related MESSAGE [0…15]
Parameters
Remarks The configured message data source value will be fetched and replaced wherever {V}
is present in the text message (MESSAGE [0...15]). If specifier {V} is not present in the
MESSAGE[0...15], then by default the formatted data source value will be attached at
the end of the MESSAGE[0...15].
Supported data types: Unsigned Integer, Integer, Floating Point, and Boolean.

15.216 MSGDELAY

Specific to Block(s) PCDI_MASTER


Description Message Delay in milliseconds
Data Type 32-Bit Unsigned Integer
Range 0 to 60000
Default 0

- 1787 -
Chapter 15 - Mxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer/Application Developer
Residence CEE
Related Parameters
Remarks

15.217 MSGSEQNUMBER[1..200]

Specific to Block(s) QIPACCHAN


Description Message Sequence Number
Data Type 32-Bit Integer
Range n/a
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters None
Remarks

15.218 MSGTYPE[0..15]

Specific to Block(s) Message


Description Message Type - Defines what type of message is configured.
Data Type Enumeration
Range INFO (0) CONFIRM (1) SINGLESIGNATURE (2) DOUBLSIGNATURE (3)
Default INFO (0)
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks

- 1788 -
Chapter 15 - Mxxxx Parameters

15.219 MTR

Specific to Block(s) HTMOTOR, LTMOTOR


Description Motor Run State
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters MTS
Remarks Parameter used as RUN feedback of the state of the device.

15.220 MTRSRC

Specific to Block HTMOTOR, LTMOTOR


(s)
Description MTR Structure Source
Data Type INCONN
Range
Default
Config Load NO
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related MTR
Parameters
Remarks Connection parameter to get both value and status for MTR from the
preceding block.

15.221 MTS

Specific to Block(s) HTMOTOR, LTMOTOR


Description Motor Stop State
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO

- 1789 -
Chapter 15 - Mxxxx Parameters

Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters MTR
Remarks Parameter used as STOP feedback of the state of the device.

15.222 MTT

Specific to Block(s) HTMOTOR, LTMOTOR


Description Motor Trip State
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters
Remarks Used as protection interlock.

15.223 MTTACTED

Specific to HTMOTOR
Block(s)
Description Motor Tripped
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MTT RESETFIRSTUP
Parameters
Remarks Indicates that the corresponding protection interlock has occurred and changed
the output state to STOP.

- 1790 -
Chapter 15 - Mxxxx Parameters

15.224 MULREDUNSTAT

Specific to Block(s) CPM, RM


Description The state of the module's redundancy
Data Type Enumeration
Range CONFIGREDUN (0) FORCEDREDUN (1) NONREDUN (2)
Default CONFIGREDUN (0)
Config Load No
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters ABORTALM.PR
Remarks This parameter is set differently for CPM and RM:
l CPM: CONFIGREDUN
l RM: FORCEDREDUN

15.225 MULTIINPTDESC

Specific to FIRSTOUT
Block(s)
Description Multiple input description
Data Type String
Range 32 characters
Default Multiple inputs
Config Load YES
Active No
Loadable
Access Lock AppDev Only
Residence SR
Related
Parameters
Remarks This is a configurable parameter. This description will be shown in the alarms
description in case of multiple inputs transitioning from NORMAL state in a single
cycle.

- 1791 -
Chapter 15 - Mxxxx Parameters

15.226 MUXSEL

Specific to SignalSel
Block(s)
Description Multiplex Selected Input
Data Type 32-Bit Integer
Range 1-6
Default 1
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related BOOLMUX
Parameters
Remarks This parameter represents the control signal value to select an input when the
selection method is MUX.

15.227 MV.ACHIEVABLEHL

Specific to Block(s) PROFCONOUT


Description Achievable HL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.ACHIEVABLELL
Remarks The calculated achievable MV high limit

15.228 MV.ACHIEVABLELL

Specific to Block(s) PROFCONOUT


Description Achievable LL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No

- 1792 -
Chapter 15 - Mxxxx Parameters

Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.ACHIEVABLEHL
Remarks The calculated achievable MV low limit

15.229 MV.ACTHL

Specific to Block(s) PROFCONOUT


Description Active High limit
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.ACTLL
Remarks MV high limit

15.230 MV.ACTIVEMAXMOVEDOWN

Specific to Block(s) PROFCONOUT


Description Max Move Down
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.ACTIVEMAXMOVEUP
Remarks MV low change limit

- 1793 -
Chapter 15 - Mxxxx Parameters

15.231 MV.ACTIVEMAXMOVEUP

Specific to Block(s) PROFCONOUT


Description Max Move Up
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.ACTIVEMAXMOVEDOWN
Remarks MV high change limit

15.232 MV.ACTIVEVAL

Specific to Block(s) PROFCONOUT


Description Current value
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.VALUE
Remarks Current value

15.233 MV.ACTLL

Specific to Block(s) PROFCONOUT


Description Active Low limit
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1794 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.ACTHL
Remarks MV low limit

15.234 MV.ADDITIONALANTIWINDUPMOVE

Specific to Block(s) PROFCONOUT


Description Additional antiwindup move for SP
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks Additional antiwindup move applied to SP

15.235 MV.BIAS

Specific to Block(s) PROFCONOUT


Description Bias for Simulation
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.VALUE
Remarks Bias for Simulation

- 1795 -
Chapter 15 - Mxxxx Parameters

15.236 MV.CALCBLKINTERVALS

Specific to Block(s) PROFCONOUT


Description Calc. blk intervals
Data Type INT16
Range ±32767
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.NOOFBLKS
Remarks Calculated block intervals

15.237 MV.CALCRESOLUTION

Specific to Block(s) PROFCONOUT


Description CALC resolution
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.RESOLUTION, MV.RESOLUTIONMISMATCH
Remarks Estimated resolution if auto, else max output mismatch

15.238 MV.CASSTATUS

Specific to Block(s) PROFCONOUT


Description Cascade status
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1796 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters
Remarks Cascade status, 0: off, 1: init, 2: on. Use for mode switching at DSS.

15.239 MV.CONSTRAINTTYPEENUM

Specific to Block(s) PROFCONOUT


Description Enum for Constraint Type
Data Type ENUM
Range NA
Default FREE
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.CONSTRAINTTYPE
Remarks 0: free, +/-1: fixed hi/lo (hard), +/-2: fixed hi/lo (soft)

15.240 MV.CONTROLHORIZON

Specific to Block(s) PROFCONOUT


Description Control Horizon
Data Type FLOAT64
Range ±1.7E+308
Default 2
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.CONTROLPREDICTION, MV.SSVALUE, MV.VALUE
Remarks Control Horizon

- 1797 -
Chapter 15 - Mxxxx Parameters

15.241 MV.CONTROLMOVE

Specific to Block(s) PROFCONOUT


Description CONTROLMOVE
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks SS Move Due to Control

15.242 MV.CRITICAL

Specific to Block(s) PROFCONOUT


Description Critical MV
Data Type ENUM
Range NA
Default YES
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence NOLOAD
Related Parameters MV.USETHISMV
Remarks IsCritical- Yes or No

15.243 MV.CTLCVINDEX1

Specific to Block(s) PROFCONOUT


Description CTLCVINDEX1
Data Type INT16
Range ±32767
Default NA
Config Load No
Active Loadable No

- 1798 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.CTLCVINDEX2
Remarks Dominant Control CV that caused MV move

15.244 MV.CTLCVINDEX2

Specific to Block(s) PROFCONOUT


Description CTLCVINDEX2
Data Type INT16
Range ±32767
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.CTLCVINDEX1
Remarks Second Dominant Control CV that caused MV move

15.245 MV.CURRENTMOVE

Specific to Block(s) PROFCONOUT


Description MV move to be implemented
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.VALUE
Remarks MV move to be implemented

- 1799 -
Chapter 15 - Mxxxx Parameters

15.246 MV.CURRENTMOVEIFON

Specific to Block(s) PROFCONOUT


Description MV move if mode is ON
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.CURRENTMOVE
Remarks MV move if mode is ON

15.247 MV.DELTAACTSOFTHL

Specific to Block(s) PROFCONOUT


Description Delta Active soft HL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.DELTAACTSOFTLL
Remarks Active soft limit as a delta from active high limit

15.248 MV.DELTAACTSOFTLL

Specific to Block(s) PROFCONOUT


Description Delta Active soft LL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1800 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.DELTAACTSOFTHL
Remarks Active soft limit as a delta from active low limit

15.249 MV.DELTASOFTHL

Specific to Block(s) PROFCONOUT


Description Delta Soft HL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.DELTASOFTLL
Remarks Soft limit as delta from active high limit

15.250 MV.DELTASOFTLL

Specific to Block(s) PROFCONOUT


Description Delta Soft LL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.DELTASOFTHL
Remarks Soft limit as delta from active low limit

- 1801 -
Chapter 15 - Mxxxx Parameters

15.251 MV.DESC

Specific to Block(s) PROFCONOUT


Description MV Description
Data Type STRING
Range NA
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.NAME
Remarks MV Description

15.252 MV.DESIREDVAL

Specific to Block(s) PROFCONOUT


Description Economic obj. desired value
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters
Remarks Economic objective desired value

15.253 MV.ENGGHL

Specific to Block(s) PROFCONOUT


Description Engg. HL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No

- 1802 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MV.ENGGLL
Remarks Entered Engineering MV high limit

15.254 MV.ENGGLL

Specific to Block(s) PROFCONOUT


Description Engg. LL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.ENGGHL
Remarks Entered Engineering MV low limit

15.255 MV.ENGGUNITS

Specific to Block(s) PROFCONOUT


Description Engg. unit
Data Type STRING
Range NA
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.DESC
Remarks Engineering units displayed

- 1803 -
Chapter 15 - Mxxxx Parameters

15.256 MV.EXCITESIGNAL

Specific to Block(s) PROFCONOUT


Description Excitation signal from Stepper
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.INJECTEDSIGNAL, MV.VALUE
Remarks Excitation signal from Stepper

15.257 MV.EXECSTATUS

Specific to Block(s) PROFCONOUT


Description Exec Status
Data Type ENUM
Range NA
Default INACTIVE
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.WINDUPSTATUS
Remarks Execution status for this MV, 0: INACTIVE, 1: ACTIVE.

15.258 MV.FUTUREVAL_C

Specific to Block(s) PROFCONOUT


Description Color for Fut Val
Data Type ENUM
Range NA
Default BLACK
Config Load No
Active Loadable No

- 1804 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV>FUTUREVAL
Remarks UI Color for Predicted value at 4 tau

15.259 MV.FUTUREVALUE

Specific to Block(s) PROFCONOUT


Description Future Value
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.CURRENTMOVE, MV.READVALUE
Remarks Predicted value at 4 tau

15.260 MV.HELDINJECTEDSIGNALVAL

Specific to Block(s) PROFCONOUT


Description Held Injected Signal Val
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.INJECTEDSIGNAL, MV.EXCITESIGNAL
Remarks Accumulated injected signal from stepper

- 1805 -
Chapter 15 - Mxxxx Parameters

15.261 MV.HIGHLIMIT

Specific to Block(s) PROFCONOUT


Description Entered MV high limit
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters MV.LOWLIMIT, MV.VALUE
Remarks Entered MV high limit

15.262 MV.HLRAMP

Specific to Block(s) PROFCONOUT


Description High Limit Ramp
Data Type ENUM
Range NA
Default NO-RAMP
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.HLRAMPRATE, MV.HIGHLIMIT
Remarks High Limit Ramp

15.263 MV.HLRAMPRATE

Specific to Block(s) PROFCONOUT


Description HL Ramp rate
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No

- 1806 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MV.HLRAMP, MV.HIGHLIMIT
Remarks MV high limit ramp rate change

15.264 MV.INITCOUNT

Specific to Block(s) PROFCONOUT


Description INIT count
Data Type INT32
Range ±2147483647
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.INITINTERVALS
Remarks Count the intervals that MV is in INIT status

15.265 MV.INITINTERVALS

Specific to Block(s) PROFCONOUT


Description Init Intervals
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.INITCOUNT, MV.BLOCKINITCOUNTER
Remarks No. of intervals in init space

- 1807 -
Chapter 15 - Mxxxx Parameters

15.266 MV.INJECTEDSIGNAL

Specific to Block(s) PROFCONOUT


Description Stepper injected Signal
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.EXCITESIGNAL, MV.VALUE
Remarks MV real injected signal from Profit Stepper

15.267 MV.INTERACTIONMOVE

Specific to Block(s) PROFCONOUT


Description INTERACTIONMOVE
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks SS Move Due to Interaction

15.268 MV.INTERNALWINDUPRATIO

Specific to Block(s) PROFCONOUT


Description Internal Windup Ratio
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1808 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters
Remarks Internal Windup Ratio calculated based

15.269 MV.ISCONTROLLABLE

Specific to Block PROFCONOUT


(s)
Description Is RegCtl block Writeable
Data Type BOOL
Range NA
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence NOLOAD
Related MV.USETHISMV
Parameters
Remarks If this MV and all its downstream regctl’s are controllable, this is true.
Otherwise, it's false

15.270 MV.ITRCVINDEX1

Specific to Block(s) PROFCONOUT


Description ITRCVINDEX1
Data Type INT16
Range ±32767
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.ITRCVINDEX2
Remarks Dominant Interaction CV that caused MV move

- 1809 -
Chapter 15 - Mxxxx Parameters

15.271 MV.ITRCVINDEX2

Specific to Block(s) PROFCONOUT


Description ITRCVINDEX2
Data Type INT16
Range ±32767
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.ITRCVINDEX1
Remarks Second Dominant Interaction CV that caused MV move

15.272 MV.LASTSTATUS

Specific to Block(s) PROFCONOUT


Description MV Value from prev interval
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.STATUS
Remarks u_solve (MV status engine) from previous interval

15.273 MV.LINEARCOEFF

Specific to Block(s) PROFCONOUT


Description Economic objective linear coefficient
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load 1
Active Loadable No

- 1810 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MV.QUADRATICCOEFF
Remarks Economic objective linear coefficient

15.274 MV.LINEARCOEFF_C

Specific to Block(s) PROFCONOUT


Description Color for Lin. Coeff
Data Type ENUM
Range NA
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.LINEARCOEFF
Remarks Economic objective linear coefficient color (for UI)

15.275 MV.LLRAMP

Specific to Block(s) PROFCONOUT


Description Low Limit Ramp
Data Type ENUM
Range NA
Default NO-RAMP
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.LLRAMPRATE, MV.LOWLIMIT
Remarks Low Limit Ramp

- 1811 -
Chapter 15 - Mxxxx Parameters

15.276 MV.LLRAMPRATE

Specific to Block(s) PROFCONOUT


Description LL ramp rate
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.LLRAMP, MV.LOWLIMIT
Remarks MV low limit ramp rate change

15.277 MV.LOWLIMIT

Specific to Block(s) PROFCONOUT


Description Low Limit
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters MV.HIGHLIMIT, MV.VALUE
Remarks Entered MV low limit

15.278 MV.MANACTION

Specific to Block(s) PROFCONOUT


Description Action When in MAN Mode
Data Type ENUM
Range NA
Default FFWD
Config Load Yes
Active Loadable No

- 1812 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MV.STATUS, MV.USETHISMV
Remarks 1=drop from model prediction calculations; 0=FFWD

15.279 MV.MAXMOVEDOWN

Specific to Block(s) PROFCONOUT


Description Max move Down
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.MAXMOVEUP, MV.CURRENTMOVE
Remarks MV max move Down

15.280 MV.MAXMOVEUP

Specific to Block(s) PROFCONOUT


Description Max move up
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.MAXMOVEDOWN, MV.CURRENTMOVE
Remarks MV max move Up

- 1813 -
Chapter 15 - Mxxxx Parameters

15.281 MV.MOVE_CTLCVINDEX1

Specific to Block(s) PROFCONOUT


Description MOVE-CTLCVINDEX1
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.MOVE_CTLCVINDEX2
Remarks MV Move Due to Dominant CV

15.282 MV.MOVE_CTLCVINDEX2

Specific to Block(s) PROFCONOUT


Description MOVE-CTLCVINDEX2
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.MOVE_CTLCVINDEX1
Remarks MV Move Due to 2nd Dominant CV

15.283 MV.MOVE_ITRCVINDEX1

Specific to Block(s) PROFCONOUT


Description MOVE-ITRCVINDEX1
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1814 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.MOVE_ITRCVINDEX2
Remarks MV Move Due to Dominant Interaction CV

15.284 MV.MOVE_ITRCVINDEX2

Specific to Block(s) PROFCONOUT


Description MOVE-ITRCVINDEX2
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.MOVE_ITRCVINDEX1
Remarks MV Move Due to 2nd Dominant Interaction CV

15.285 MV.MVINDEX

Specific to Block(s) PROFCONOUT


Description MV Index
Data Type INT16
Range ±32767
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.NAME
Remarks Index of this MV in this application

- 1815 -
Chapter 15 - Mxxxx Parameters

15.286 MV.MVINDEX_C

Specific to Block(s) PROFCONOUT


Description Color for Index
Data Type ENUM
Range NA
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.MVINDEX
Remarks Index of this MV in this application color (for UI)

15.287 MV.NAME

Specific to Block(s) PROFCONOUT


Description MV Name
Data Type STRING
Range NA
Default NA
Config Load No
Active Loadable No
Access Lock APPDEVONLY
Residence CEE
Related Parameters MV.DESC
Remarks MV Name

15.288 MV.NOOFBLKS

Specific to Block(s) PROFCONOUT


Description No.of blocking intervals
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load
Active Loadable No

- 1816 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence
Related Parameters
Remarks No.of blocking intervals

15.289 MV.OP_MAX_X

Specific to Block(s) PROFCONOUT


Description max_x for OP scaling
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV. OP_MIN_X
Remarks max_x for OP scaling

15.290 MV.OP_MIN_X

Specific to Block(s) PROFCONOUT


Description min_x for OP scaling
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.OP_MAX_X
Remarks min_x for OP scaling

- 1817 -
Chapter 15 - Mxxxx Parameters

15.291 MV.OPHIGHTRANSITION

Specific to Block(s) PROFCONOUT


Description OP High Transition
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.OPVAL, MV.VALUE
Remarks If OP is greater than this value, the PV will respond slowly

15.292 MV.OPHIGHWINDUP

Specific to Block(s) PROFCONOUT


Description OP High Windup
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.OPVAL, MV.PVVAL
Remarks If OP is greater than this value, the PV will not respond

15.293 MV.OPLOWTRANSITION

Specific to Block(s) PROFCONOUT


Description OP Low Transition
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No

- 1818 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MV.OPVAL, MV.VALUE
Remarks If OP is smaller than this value, the PV will respond slowly

15.294 MV.OPLOWWINDUP

Specific to Block(s) PROFCONOUT


Description OP Low windup
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.OPVAL, MV.PVVAL
Remarks If OP is smaller than this value, the PV will not respond

15.295 MV.OPPROCESSHL

Specific to Block(s) PROFCONOUT


Description OP Process High Limit from DCS
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.OPVAL
Remarks OP Process High Limit from DCS

- 1819 -
Chapter 15 - Mxxxx Parameters

15.296 MV.OPPROCESSLL

Specific to Block(s) PROFCONOUT


Description Read OP Process Low Limit from DCS
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.OPVAL, MV.OPPROCESSHL
Remarks OP Process Low Limit from DCS

15.297 MV.OPPVFILTERCOEF

Specific to Block(s) PROFCONOUT


Description OP-PV Filter Coeff
Data Type FLOAT64
Range ±1.7E+308
Default 0.2
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.OP2PVPOLYMODEL
Remarks 0-1, 1: No filtering, Default: 0.2, Stronger filtering with smaller value

15.298 MV.OPTCVINDEX

Specific to Block(s) PROFCONOUT


Description OPTCVINDEX
Data Type INT16
Range ±32767
Default NA
Config Load No
Active Loadable No

- 1820 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters
Remarks CV that Limits the MV Optimization

15.299 MV.OPTIMIZATIONMOVE

Specific to Block(s) PROFCONOUT


Description OPTIMIZATIONMOVE
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks SS Move Due to Optimization

15.300 MV.OPTOPVGAIN

Specific to Block(s) PROFCONOUT


Description OP to PV Gain
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.OPPVFILTERCOEF
Remarks OP to PV Gain in Engineering/% unit

- 1821 -
Chapter 15 - Mxxxx Parameters

15.301 MV.OPTPRIORITY

Specific to Block(s) PROFCONOUT


Description Optimization priority
Data Type ENUM
Range NA
Default NORMAL
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks MV optimization priority

15.302 MV.OPVAL

Specific to Block(s) PROFCONOUT


Description RegCtl block OP
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.OPVALUE
Remarks RegCtl block OP

15.303 MV.OPVALUE

Specific to Block PROFCONOUT


(s)
Description PID.OP
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1822 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related MV.OPVAL
Parameters
Remarks The OP value of the downstream PID read into the controller, used to predict
the achievable MV limit

15.304 MV.PERCENT_CTLMOVE

Specific to Block(s) PROFCONOUT


Description PERCENT-CTLMOVE
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks Percent - SS Move Due to Control

15.305 MV.PERCENT_ITRMOVE

Specific to Block(s) PROFCONOUT


Description PERCENT-ITRMOVE
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks Percent - SS Move Due to Interaction

- 1823 -
Chapter 15 - Mxxxx Parameters

15.306 MV.PERCENT_OPTMOVE

Specific to Block(s) PROFCONOUT


Description PERCENT-OPTMOVE
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks Percent - SS Move Due to Optimization

15.307 MV.PERCENTMOVE_CTLCVINDEX1

Specific to Block(s) PROFCONOUT


Description PERCENTMOVE-CTLCVINDEX1
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.PERCENTMOVE_CTLCVINDEX2
Remarks Percent- MV Move Due to Dominant CV

15.308 MV.PERCENTMOVE_CTLCVINDEX2

Specific to Block(s) PROFCONOUT


Description PERCENTMOVE-CTLCVINDEX2
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1824 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.PERCENTMOVE_CTLCVINDEX1
Remarks Percent- MV Move Due to 2nd Dominant CV

15.309 MV.PERCENTMOVE_ITRCVINDEX1

Specific to Block(s) PROFCONOUT


Description PERCENTMOVE-ITRCVINDEX1
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.PERCENTMOVE_ITRCVINDEX2
Remarks Percent- MV Move Due to Dominant Interaction CV

15.310 MV.PERCENTMOVE_ITRCVINDEX2

Specific to Block(s) PROFCONOUT


Description PERCENTMOVE-ITRCVINDEX2
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.PERCENTMOVE_ITRCVINDEX1
Remarks Percent- MV Move Due to 2nd Dominant CV

- 1825 -
Chapter 15 - Mxxxx Parameters

15.311 MV.PIDMODE

Specific to Block(s) PROFCONOUT


Description PID DSC MODE
Data Type STRING
Range NA
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.USETHISMV, MV.EXECSTATUS
Remarks PID DSC MODE

15.312 MV.PREDICTEDPV

Specific to Block(s) PROFCONOUT


Description Predicted PID.PV
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.PVVAL, MV.VALUE
Remarks Predicted value of PV of downstream regctl

15.313 MV.PREVIOUSVAL

Specific to Block(s) PROFCONOUT


Description Previous Value
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1826 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.VALUE
Remarks MV at previous interval

15.314 MV.PROCESSHL

Specific to Block(s) PROFCONOUT


Description Process HL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.PROCESSLL
Remarks Process setpoint high limit

15.315 MV.PROCESSLL

Specific to Block(s) PROFCONOUT


Description Process LL
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.PROCESSHL
Remarks Process setpoint low limit

- 1827 -
Chapter 15 - Mxxxx Parameters

15.316 MV.PV_MAX_Y

Specific to Block(s) PROFCONOUT


Description Max_y for PV scaling
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.PVVAL, MV.PV_MIN_Y
Remarks Max_y for PV scaling

15.317 MV.PV_MIN_Y

Specific to Block(s) PROFCONOUT


Description min_y for PV scaling
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.PVVAL, MV.PV_MAX_Y
Remarks min_y for PV scaling

15.318 MV.PVNOISEGAP

Specific to Block(s) PROFCONOUT


Description PV Noise Gap for wind-up
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1828 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.PVVAL
Remarks The calculated SP to PV tracking Gap in windup

15.319 MV.PVTRACK

Specific to Block(s) PROFCONOUT


Description Track PV
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.PVVAL
Remarks 1:limit tracks value, 0: no tracking

15.320 MV.PVTRACKENUM

Specific to Block(s) PROFCONOUT


Description Enum for PV Track
Data Type ENUM
Range NA
Default NO
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.PVTRACK
Remarks Enum for PV track parameter

- 1829 -
Chapter 15 - Mxxxx Parameters

15.321 MV.PVVAL

Specific to Block(s) PROFCONOUT


Description RegCtl block PV
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks RegCtl block PV

15.322 MV.QUADRATICCOEFF

Specific to Block(s) PROFCONOUT


Description Economic objective quadratic coefficient
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.LINEARCOEFF
Remarks Economic objective quadratic coefficient

15.323 MV.READPROCESSVAL

Specific to Block(s) PROFCONOUT


Description The sp/op value read into the controller
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1830 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MV.PVVAL
Remarks The pv value read into the controller.

15.324 MV.READVAL

Specific to Block(s) PROFCONOUT


Description MV[ SP/OP] read value
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.READPROCESSVALUE, MV.OPVALUE
Remarks MV[ SP/OP] read value

15.325 MV.RESOLUTION

Specific to Block(s) PROFCONOUT


Description MV Resolution
Data Type FLOAT64
Range ±1.7E+308
Default -1
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.CALCRESOLUTION
Remarks -1: no resolution calc, 0: auto resolution, > 0: entered resolution

- 1831 -
Chapter 15 - Mxxxx Parameters

15.326 MV.RESOLUTIONMISMATCH

Specific to Block(s) PROFCONOUT


Description Resolution mismatch
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.RESOLUTION
Remarks Output mismatch at this interval

15.327 MV.RESOLUTIONRESIDUAL

Specific to Block(s) PROFCONOUT


Description Resolution residual
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.RESOLUTION
Remarks Accumulated residual output less than DCS resolution

15.328 MV.SCALINGFACTOR

Specific to Block(s) PROFCONOUT


Description Scaling factor
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No

- 1832 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters
Remarks MV scaling factor

15.329 MV.SENTVALUE

Specific to Block(s) PROFCONOUT


Description Sent Value
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.VALUE, MV.CURRENTMOVE
Remarks Output from controller (sp or op), WARM/ON update

15.330 MV.SENTVALUEIFON

Specific to Block(s) PROFCONOUT


Description Sent Value when ON
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.VALUE, MV.CURRENTMOVE
Remarks Output from controller if mode is ON

- 1833 -
Chapter 15 - Mxxxx Parameters

15.331 MV.SHADOWPRICE

Specific to Block(s) PROFCONOUT


Description Shadow price
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks Shadow/Error Price of SS MV constraint

15.332 MV.SSMOVEMAINCAUSE

Specific to Block PROFCONOUT


(s)
Description MV Move cause
Data Type ENUM
Range NA
Default Not Determined
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related MV.SSMOVEMAINCV
Parameters
Remarks 0: not determined, 1: Optimization, 2: Control, 3: Interaction-Opt, 4:
Interaction-Control

15.333 MV.SSMOVEMAINCV

Specific to Block(s) PROFCONOUT


Description Main CV Cause
Data Type INT32
Range ±2147483647
Default NA
Config Load No

- 1834 -
Chapter 15 - Mxxxx Parameters

Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSMOVEMAINCAUSE
Remarks Main CV Cause(Limit) MV to Move(Opt)

15.334 MV.SSVALUE

Specific to Block(s) PROFCONOUT


Description Pred SS value
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.VALUE
Remarks Predicted optimal value

15.335 MV.SSVALUE_C

Specific to Block(s) PROFCONOUT


Description Color for SSValue
Data Type ENUM
Range NA
Default BLACK
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks Predicted optimal value color (for UI)

- 1835 -
Chapter 15 - Mxxxx Parameters

15.336 MV.STARTVALUE

Specific to Block(s) PROFCONOUT


Description Start Value for Simulation
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.BIAS
Remarks Start Value for Simulation

15.337 MV.STATUS

Specific to Block(s) PROFCONOUT


Description MV status
Data Type ENUM
Range NA
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related MV.USETHISMV
Parameters
Remarks MV status (display), 1: on, 2: wound up hi, 3: would up lo, 4: ffwd, 5: service, 6:
init

15.338 MV.STATUSDISP_C

Specific to Block(s) PROFCONOUT


Description Color for Status Disp
Data Type ENUM
Range NA
Default BLACK
Config Load No
Active Loadable No

- 1836 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.STATUSDISP
Remarks Status Display color (for UI)

15.339 MV.STATUSDISPLAY

Specific to Block(s) PROFCONOUT


Description Status Display of the Status Item
Data Type ENUM
Range NA
Default ON
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.STATUS
Remarks Status Display of the Status Item

15.340 MV.STEPINPROGRESS

Specific to Block(s) PROFCONOUT


Description Stepper Status
Data Type BOOL
Range NA
Default NA
Config Load No
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters MV.EXCITESIGNAL
Remarks When true, ProfitStepper is in the process of manipulating this variable.

- 1837 -
Chapter 15 - Mxxxx Parameters

15.341 MV.TOTALSSMOVE

Specific to Block(s) PROFCONOUT


Description TOTALSSMOVE
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SSVALUE
Remarks MV Steady State Move

15.342 MV.TRACKPVWITHGAP

Specific to Block(s) PROFCONOUT


Description Track PV with a Gap
Data Type ENUM
Range NA
Default NO
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.TRACKPV
Remarks SP Tracks PV with a Gap in Windup

15.343 MV.TYPICALMOVESIZE

Specific to Block(s) PROFCONOUT


Description Typical Move Size
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load No
Active Loadable No

- 1838 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MV.SCALINGFACTOR
Remarks Typical Move Size of this MV, default must be 1.0

15.344 MV.U_SOLVE

Specific to Block(s) PROFCONOUT


Description Calc MV Move
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.STATUS
Remarks MV status (solver). Internal use.

15.345 MV.USEACHLIM

Specific to PROFCONOUT
Block(s)
Description Use Achievable Limit
Data Type ENUM
Range NA
Default OFF
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related MV.LOWLIMIT, MV.HIGHLIMIT
Parameters
Remarks 0: Off, 1: Use achievable high limit, 2: Use achievable low limit, 3: Use both
achievable high and low limits

- 1839 -
Chapter 15 - Mxxxx Parameters

15.346 MV.USEPOLYMODEL

Specific to Block(s) PROFCONOUT


Description Use Polynomial Model
Data Type ENUM
Range NA
Default NO
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks Use the User entered polynomial coefficients to do MV Limit Prediction

15.347 MV.USETHISMV

Specific to Block(s) PROFCONOUT


Description Use this MV
Data Type ENUM
Range NA
Default RMPC
Config Load Yes
Active Loadable No
Access Lock OPERATOR
Residence CEE
Related Parameters MV.PIDMODE
Remarks !=0: use this MV for control, 0: do not use this MV for control.

15.348 MV.USETHISMV_C

Specific to Block(s) PROFCONOUT


Description Color for Use This MV
Data Type ENUM
Range NA
Default BLACK
Config Load No
Active Loadable No

- 1840 -
Chapter 15 - Mxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters MV.USETHISMV
Remarks Use this MV color (for UI)

15.349 MV.VALIDATIONFAILCOUNT

Specific to Block(s) PROFCONOUT


Description MV Validation Fail count
Data Type INT32
Range ±2147483647
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.VALUE, MV.STATUS
Remarks Count the intervals that MV read value validation failed

15.350 MV.VALUE

Specific to Block(s) PROFCONOUT


Description ReadValue or SentValue
Data Type FLOAT64
Range ±1.7E+308
Default NA
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters MV.SENTVALUE
Remarks ReadValue or SentValue whose quality is good

- 1841 -
Chapter 15 - Mxxxx Parameters

15.351 MV.VALUE_C

Specific to Block(s) PROFCONOUT


Description Color for Value
Data Type ENUM
Range NA
Default BLACK
Config Load
Active Loadable No
Access Lock VIEWONLY
Residence
Related Parameters
Remarks MV Value color (for UI)

15.352 MV.WEIGHT

Specific to Block(s) PROFCONOUT


Description MV weight
Data Type FLOAT64
Range ±1.7E+308
Default 1
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters MV.SCALINGFACTOR
Remarks MV weight, default must be 1.0

15.353 MV.WINDUPSTATUS

Specific to Block(s) PROFCONOUT


Description Windup status
Data Type ENUM
Range NA
Default NORMAL
Config Load No
Active Loadable No

- 1842 -
Chapter 15 - Mxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters MV.EXECSTATUS
Remarks Windup status for this MV, 1: normal, 2: hi, 3: lo, 4: hilo.

15.354 MW

Specific to Block(s) FLOWCOMP


Description Molecular Weight Input
Data Type Real
Range NaN or Greater than or equal to 0.0
Default 1.0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence No Load
Related Parameter MWSTS
Remarks

15.355 MWSTS

Specific to Block FLOWCOMP


(s)
Description Molecular Weight Status - Indicates the current status of Molecular Weight
input MW
Data Type Enumeration PVVALSTS
Range Bad (0) The value is bad and has been replaced
with NaN.
Uncertain (1) The status of the value is uncertain.
Normal (2) The value is good.
Manual The value was manually stored.
Default Normal
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200, C300, ACE
Related
Parameter
Remarks

- 1843 -
Chapter 15 - Mxxxx Parameters

15.356 MXCOMMAND[1..200]

Specific to QIPACCHAN
Block
Description Command Number
Data Type Enumeration
Range 0 None
1 Start Material Transfer
2 Start Material Transfer with Gross
Weight Target. Only valid for a scale.
3 Start Hand Add
4 Acknowledge material transfer or Hand
Add Complete
5 Abort Material Transfer
6 Reset Slow Step Timer
7 Start Manual Mode
8 Turn on FCE in Manual Mode
9 Turn on FCE in Manual Mode
10 Restart Auto Mode
11 Complete Feed in Manual Mode
12 Master Reset - Instrument Channel
13 Reserved
14 Master Reset - Cluster
15 Validate Aggregate Secondary Feeds
99 Validate Data Integrity
Default Off
Config No
Load
Active No
Loadable
Access Lock Read/Write
Residence CEE
Related MXMATPATH[1..200], MXGROUPNUM[1..200], MXOVRLAPNUM[1..200],
Parameters MXTARGETWGT[1..200], MXPOSTOLER[1..200], MXNEGTOLER[1..200], MXTRANID
[1..200]
Remarks This value is written by the user's application for the designated channel [1..200] in
the QiMPACT for which a material transfer is to be initiated. All other parameters
required for the particular material transfer type, must be written before this
parameter. Writing to this parameter triggers the process to issue the material
transfer command to the QiMPACT.

- 1844 -
Chapter 15 - Mxxxx Parameters

15.357 MXFERSTATQ[1..200]

Specific to QIPACCHAN
Block
Description Material Transfer Status Qualifiers Integer Representation
Data Type 32-Bit Integer
Range 0-7
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MATERIALPATH[1..200], COMMAND, COMMANDSTATS[1..200], MXFERSTATUS
Parameters [1..200], MXFERSTATQ[1..200], OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200],
POWERFAIL[1..200], DELIVEREDWGT[1..200], TARGETERROR[1..200], AVGSPILL
[1..200], AVGFLOWRATE[1..200]
Remarks This value provides material transfer results and is valid after the material transfer
for the designated channel [1..200] in the QiMPACT cluster completes.

15.358 MXFERSTATUS[1..200]

Specific to QIPACCHAN
Block
Description Material Transfer Status from Q.iMPACT
Data Type Enumeration (BYTE)
Range 0-3 SUCCESS
4-6 MATERIAL TRANSFER COMPLETE
7 - 25 FAILED
26 RUNNING
** See Mettler Toledo QiMPACT Controller Messaging document for details.
Default 0 - SUCCESS
Config No
Load
Active No
Loadable

- 1845 -
Chapter 15 - Mxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related MATERIALPATH[1..200], COMMAND, COMMANDSTATS[1..200], MXFERSTATQ
Parameters [1..200], OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200], POWERFAIL[1..200],
DELIVEREDWGT[1..200],TARGETERROR[1..200], AVGSPILL[1..200], AVGFLOWRATE
[1..200]
Remarks Current status of the material transfer in progress for the designated channel [1-
200] in the QiMPACT cluster.

15.359 MXGROUPNUM[1..200]

Specific to QIPACCHAN
Block
Description Group Number for Start Material Transfer Command
Data Type BYTE
Range 0-255
Default 0
Config No
Load
Active No
Loadable
Access Lock Read/Write
Residence CEE
Related MXMATPATH[1..200], MXOVRLAPNUM[1..200], MXTARGETWGT[1..200],
Parameters MXPOSTOLER[1..200], MXNEGTOLER[1..200], MXTRANID[1..200]MXCOMMAND
[1..200]
Remarks This value is written by the user's application for the designated channel [1..200] in
the QiMPACT for which a material transfer is to be initiated. If this parameter is
required for the particular material transfer type to be initiated, it must be written
before the COMMAND parameter is written.

15.360 MXMATPATH[1..200]

Specific to QIPACCHAN
Block
Description Material Path Index
Data Type 16-Bit Unsigned Integer
Range 0-65535
Default 0
Config No
Load
Active No
Loadable

- 1846 -
Chapter 15 - Mxxxx Parameters

Access Lock Read/Write


Residence CEE
Related MXCOMMAND[1..200], MXGROUPNUM[1..200], MXOVRLAPNUM[1..200],
Parameters MXTARGETWGT[1..200], MXPOSTOLER[1..200], MXNEGTOLER[1..200], MXTRANID
[1..200]
Remarks This value is written by the user's application for the designated channel [1..200] in
the QiMPACT for which a material transfer is to be initiated. If this parameter is
required for the particular material transfer type to be initiated, it must be written
before the COMMAND parameter is written.

15.361 MXNEGTOLER[1..200]

Specific to QIPACCHAN
Block
Description Tolerance -
Data Type Float64
Range N/A
0
Config No
Load
Active No
Loadable
Access Lock Read/Write
Residence CEE
Related MXCOMMAND[1..200], MXGROUPNUM[1..200], MXOVRLAPNUM[1..200],
Parameters MXTARGETWGT[1..200], MXPOSTOLER[1..200], MXTRANID[1..200], MXMATPATH
[1..200]
Remarks This value is written by the user's application for the designated channel [1..200] in
the QiMPACT for which a material transfer is to be initiated. If this parameter is
required for the particular material transfer type to be initiated, it must be written
before the COMMAND parameter is written.

15.362 MXOVRLAPNUM[1..200]

Specific to QIPACCHAN
Block
Description Number of Overlapping Secondary Feeds
Data Type 16-Bit Unsigned Integer
Range 0-65535
Default 0
Config No
Load
Active No
Loadable

- 1847 -
Chapter 15 - Mxxxx Parameters

Access Lock Read/Write


Residence CEE
Related MXCOMMAND[1..200], MXGROUPNUM[1..200], MXTARGETWGT[1..200],
Parameters MXPOSTOLER[1..200], MXTRANID[1..200], MXMATPATH[1..200], MXNEGTOLER
[1..200]
Remarks This value is written by the user's application for the designated channel [1..200] in
the QiMPACT for which a material transfer is to be initiated. If this parameter is
required for the particular material transfer type to be initiated, it must be written
before the COMMAND parameter is written.

15.363 MXPOSTOLER[1..200]

Specific to QIPACCHAN
Block
Description Tolerance +
Data Type Float64
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock Read/Write
Residence CEE
Related MXCOMMAND[1..200], MXGROUPNUM[1..200], MXTARGETWGT[1..200], MXTRANID
Parameters [1..200], MXMATPATH[1..200], MXNEGTOLER[1..200], MXOVRLAPNUM[1..200]
Remarks This value is written by the user's application for the designated channel [1..200] in
the QiMPACT for which a material transfer is to be initiated. If this parameter is
required for the particular material transfer type to be initiated, it must be written
before the COMMAND parameter is written.

15.364 MXTARGETWGT[1..200]

Specific to QIPACCHAN
Block
Description Target Weight
Data Type Float64
Range N/A
Default 0
Config No
Load
Active No
Loadable

- 1848 -
Chapter 15 - Mxxxx Parameters

Access Lock Read/Write


Residence CEE
Related MXCOMMAND[1..200], MXGROUPNUM[1..200], MXTRANID[1..200], MXMATPATH
Parameters [1..200], MXNEGTOLER[1..200], MXOVRLAPNUM[1..200], MXPOSTOLER[1..200]
Remarks This value is written by the user's application for the designated channel [1..200] in
the QiMPACT for which a material transfer is to be initiated. If this parameter is
required for the particular material transfer type to be initiated, it must be written
before the COMMAND parameter is written.

15.365 MXTRANID[1..200]

Specific to QIPACCHAN
Block
Description Material Transfer ID
Data Type String
Range 40 Characters
Default 0
Config No
Load
Active No
Loadable
Access Lock Read/Write
Residence CEE
Related MXCOMMAND[1..200], MXGROUPNUM[1..200], MXMATPATH[1..200],
Parameters MXNEGTOLER[1..200], MXOVRLAPNUM[1..200], MXPOSTOLER[1..200],
MXTARGETWGT[1..200]
Remarks This value is written by the user's application for the designated channel [1..200] in
the QiMPACT for which a material transfer is to be initiated. If this parameter is
required for the particular material transfer type to be initiated, it must be written
before the COMMAND parameter is written.

- 1849 -
CHAPTER

16 NXXXX PARAMETERS

16.1 N 1857
16.2 N[1..5] 1858
16.3 N_EXIST_SPR 1858
16.4 NAME 1859
16.5 NAMEREF 1860
16.6 NAMURENBL_DI_C 1862
16.7 NAMURPVRAW 1862

16.8 NAMURPVRAW_DI_S 1863


16.9 NETBCDSW 1863
16.10 NETELAPSEDTM 1864
16.11 NETMODE[1..4] 1864
16.12 NETTIMEPASTTHISSEG 1865
16.13 NETWORKTYPE 1865
16.14 NETWRKTYP 1866
16.15 NEWSAMPLE 1866
16.16 NEXTCOMP 1867
16.17 NEXTCOMP[1..15] 1867
16.18 NEXTCOMP[1..15] 1868
16.19 NEXTHANDLE 1868
16.20 NEXTHANDLE[1..10] 1869
16.21 NEXTNUMBER 1869
16.22 NEXTPHASE 1870
16.23 NFLAG 1870
16.24 NLFORM 1871
16.25 NLGAIN 1871
16.26 NMIN 1872
16.27 NMODE 1872
16.28 NMODATTR 1873
16.29 NNUMERIC 1873
16.30 NOCACHE_PARAM_ID [0...3] 1874
16.31 NOCACHE_PARAM_NAME [0...3] 1875
16.32 NODELCNELCN 1875

- 1850 -
Chapter 16 - Nxxxx Parameters

16.33 NODENAME 1876


16.34 NODESTATESTR 1877
16.35 NOFIELDPWR 1877
16.36 NOFIELDPWR[0..numChans-1] 1878
16.37 NOLOAD 1878
16.38 NOLOAD[0..numChans-1] 1879
16.39 NONCRITICALMVLOSS 1879
16.40 NONFTEMARTADDRCOUNT 1879
16.41 NONFTEMARTAVGDEPTH 1880
16.42 NONFTEMARTCOLLCOUNT 1880
16.43 NONFTEMARTMAXDEPTH 1881
16.44 NONPUBLISHABLE 1881
16.45 NONREDFTABA 1882
16.46 NONREDFTABB 1882

16.47 NOOFFTENODES 1883


16.48 NOOFUPDATES 1883
16.49 NOPERDB # 1884
16.50 NOREQUESTPREAMBLES 1884
16.51 NORMAL 1884
16.52 NORMAL[1..24] 1885
16.53 NORMMODE 1885
16.54 NORMMODEATTR 1887
16.55 NOTACTSUPV 1887
16.56 NOTCHFILTER[0..numChans-1] 1888
16.57 NOTCHFILTER[0..7] 1888
16.58 NOTCHFILTER 1889
16.59 NOTE 1890
16.60 NOTIFINHIBIT 1890
16.61 NOTIFPUBLISH 1891
16.62 NOTRATEAVG 1891
16.63 NOTRATEMAX 1892
16.64 NOTREDCNFGA 1892
16.65 NOTREDCNFGB 1893
16.66 NOTSAMEFTAA 1893
16.67 NOTSAMEFTAB 1894
16.68 NOWAITINGFL 1894
16.69 NOWALARM 1895
16.70 NSTRING 1895
16.71 NTOTMEMDESC 1896

- 1851 -
Chapter 16 - Nxxxx Parameters

16.72 NTPADDRESS 1897


16.73 NTPDELAY 1897
16.74 NTPDELAYMAX 1897
16.75 NTPLASTSTRATUM 1898
16.76 NTPOFFSET 1898
16.77 NTPOFFSETMAX 1899
16.78 NTPSTAT 1899
16.79 NULLPVFL 1900
16.80 NUM 1900
16.81 NUMACCRQUAVG 1901
16.82 NUMACCRQUMAX 1902
16.83 NUMACEINCON 1902
16.84 NUMACEOUTCON 1903
16.85 NUMACT 1903

16.86 NUMACTCR 1904


16.87 NUMACTCRFAIL 1905
16.88 NUMACTIVEPOINTS 1905
16.89 NUMACTWRT 1905
16.90 NUMADJPARAMS 1906
16.91 NUMALIASES 1906
16.92 NUMALLTRANS 1907
16.93 NUMANNWIN 1907
16.94 NUMASSIGNFBS 1907
16.95 NUMBEROFCVS 1908
16.96 NUMBEROFDVS 1908
16.97 NUMBEROFEQP 1909
16.98 NUMBEROFMVS 1909
16.99 NUMBEVENTSAVG 1910
16.100 NUMBEVENTSMAX 1910
16.101 NUMBLKINST 1911
16.102 NUMBLKREF 1911
16.103 NUMBLKTYPES 1911
16.104 NUMBLOBS 1912
16.105 NUMBLOCK 1912
16.106 NUMBLOCKS 1913
16.107 NUMBLOCKUSED 1913
16.108 NUMBOOL 1914
16.109 NUMC3INCON 1914
16.110 NUMC3OUTCON 1915

- 1852 -
Chapter 16 - Nxxxx Parameters

16.111 NUMCABCOL (Custom cabinet) 1915


16.112 NUMCABROWS 1916
16.113 NUMCABTYPES 1916
16.114 NUMCACHE[1..40] 1917
16.115 NUMCACHEVAR 1917
16.116 NUMCCLRQU 1918
16.117 NUMCCLRQUAVG 1918
16.118 NUMCCLRQUMAX 1919
16.119 NUMCDDMTYPES 1919
16.120 NUMCHANS 1920
16.121 NUMCLIENTCONN 1921
16.122 NUMCLXPROC 1921
16.123 NUMCLXUDT 1922
16.124 NUMCMPCONTFB 1922

16.125 NUMCN100INCON 1923


16.126 NUMCN100OUTCON 1923
16.127 NUMCOEFDEN 1924
16.128 NUMCOEFNUM 1924
16.129 NUMCOMPFB 1925
16.130 NUMCONDS 1925
16.131 NUMCONN 1926
16.132 NUMCONN[0..1] 1926
16.133 NUMCONN[0..7] 1927
16.134 NUMCPMINCON 1927
16.135 NUMCPMOUTCON 1928
16.136 NUMCUSTOMRANGE 1929
16.137 NUMCVSEXCEEDLIM 1929
16.138 NUMCVSNEARINGLIM 1930
16.139 NUMCVSWITHINLIM 1930
16.140 NUMCYCLE 1930
16.141 NUMDATA 1931
16.142 NUMDINPUTS 1931
16.143 NUMDISCONN 1932
16.144 NUMDISCONN[0..1] 1933
16.145 NUMDISCONN[0..7] 1933
16.146 NUMDOUTS 1933
16.147 NUMUDTTAGREAD 1934
16.148 NUMEHPMINCON 1934
16.149 NUMEIPDEVICE 1935

- 1853 -
Chapter 16 - Nxxxx Parameters

16.150 NUMEIPDEVICE 1935


16.151 NUMERIC1 1936
16.152 NUMERIC2 1936
16.153 NUMEIMEIPIOS 1937
16.154 NUMEVENTS[1..NUMPROFILES] 1937
16.155 NUMEXCIMRAVAIL 1937
16.156 NUMEXCRSPAVAIL 1938
16.157 NUMEXCRQUAVAIL 1938
16.158 NUMEXCRQUAVG 1939
16.159 NUMEXCRQUMAX 1939
16.160 NUMEXCRSPAVG 1940
16.161 NUMEXCRSPMAX 1940
16.162 NUMEXTBLKS 1940
16.163 NUMFAILEDGETITEM 1941

16.164 NUMFIMINCON 1941


16.165 NUMFIMOUTCON 1942
16.166 NUMFLOAT64 1942
16.167 NUMFREEBLKS 1943
16.168 NUMFREEDESC 1943
16.169 NUMFTENODES 1944
16.170 NUMFUNREF 1944
16.171 NUMGPSSKEWEX 1945
16.172 NUMHANDLERS 1945
16.173 NUMHISTPARMS 1945
16.174 NUMIEDS 1946
16.175 NUMIMR 1946
16.176 NUMIN 1947
16.177 NUMINPUTS 1947
16.178 NUMINSERT 1947
16.179 NUMINSTANCES 1948
16.180 NUMINT32 1948
16.181 NUMINT64 1949
16.182 NUMINTERVALSININIT 1949
16.183 NUMIOLMINCON 1949
16.184 NUMIOLMOUTCON 1950
16.185 NUMIOM 1950
16.186 NUMIPADDR 1951
16.187 NUMLIOMINCON 1951
16.188 NUMLIOMOUTCON 1952

- 1854 -
Chapter 16 - Nxxxx Parameters

16.189 NUMLOC 1952


16.190 NUMMBTCPRCVBYTEAVG 1952
16.191 NUMMBTCPRCVBYTEMAX 1953
16.192 NUMMBTCPRCVMSGAVG 1953
16.193 NUMMBTCPRCVMSGMAX 1954
16.194 NUMMBTCPXMITBYTEAVG 1954
16.195 NUMMBTCPXMITBYTEMAX 1954
16.196 NUMMBTCPXMITMSGAVG 1955
16.197 NUMMBTCPXMITMSGMAX 1955
16.198 NUMMVSEXCEEDLIM 1956
16.199 NUMMVSNEARINGLIM 1956
16.200 NUMMVSWITHINLIM 1956
16.201 NUMNTFRQUAVG 1957
16.202 NUMNTFRQUMAX 1957

16.203 NUMOFCHNLSGANGED 1958


16.204 NUMOFEVENTRECVRS 1959
16.205 NUMOFINPUTS 1959
16.206 NUMOFSCANTABLEEVENTS 1960
16.207 NUMOUTPUTS 1960
16.208 NUMOWNERS 1960
16.209 NUMPARALLEL 1961
16.210 NUMPARAMS 1961
16.211 NUMPARAMS 1962
16.212 NUMPARRSPAVG 1962
16.213 NUMPARRSPMAX 1963
16.214 NUMPEERENV[ ] 1963
16.215 NUMPHASES 1964
16.216 NUMPINPT 1964
16.217 NUMPMDINCON 1965
16.218 NUMPMDOUTCON 1965
16.219 NUMPOINTSREADS 1966
16.220 NUMPOINTSWRITES 1966
16.221 NUMPRI 1967
16.222 NUMPRMREF 1967
16.223 NUMPRIORITYIOM 1968
16.224 NUMPROFILES 1968
16.225 NUMPTPSKEWEX 1968
16.226 NUMQCSINCON 1969
16.227 NUMQCSOUTCON 1969

- 1855 -
Chapter 16 - Nxxxx Parameters

16.228 NUMQUALITY 1970


16.229 NUMRAMPSOAK[1..NUMPROFILES] 1970
16.230 NUMRECPARMS 1971
16.231 NUMREGDESC 1971
16.232 NUMREQUESTR 1972
16.233 NUMRUNRCMS 1972
16.234 NUMSCADAINCON 1973
16.235 NUMSCATAGREAD 1973
16.236 NUMSCEINCON 1973
16.237 NUMSCEOUTCON 1974
16.238 NUMSCFIMINCON 1974
16.239 NUMSCFIMOUTCON 1975
16.240 NUMSEC 1975
16.241 NUMSEGS 1976

16.242 NUMSESSIONS 1976


16.243 NUMSHUTDOWN 1976
16.244 NUMSHUTDOWN[0..7] 1977
16.245 NUMSIGS 1977
16.246 NUMSIOLMINCN 1978
16.247 NUMSIOLMOUCN 1978
16.248 NUMSIOVRD 1979
16.249 NUMSLOTS 1979
16.250 NUMSMINCON 1980
16.251 NUMSMOUTCON 1980
16.252 NUMSNTPSKEWEX 1981
16.253 NUMSRCCONN[1..8] 1981
16.254 NUMSTATES 1982
16.255 NUMSTEPS 1982
16.256 NUMSYNCS 1983
16.257 NUMTBR 1983
16.258 NUMTHREADS 1984
16.259 NUMTRANS 1984
16.260 NUMTRANS [0,1] 1985
16.261 NUMTRANS[0..2] 1985
16.262 NUMUIDS 1986
16.263 NUMUINT32 1986
16.264 NUMUNITS 1986
16.265 NUMUOCINCON 1987
16.266 NUMUOCOUTCON 1987

- 1856 -
Chapter 16 - Nxxxx Parameters

16.267 NUMUSEDBLKS 1988


16.268 NUMUSEDDESC 1988
16.269 NUMWAITING 1988
16.270 NUMWSGINCON 1989
16.271 NUMWSGOUTCON 1990
16.272 NUMXFERINST 1990
16.273 NUMXINPT 1990
16.274 NVSCOMINPROG 1991
16.275 NVSFREEAVG 1991
16.276 NVSFREECRIT 1992
16.277 NVSFREECRITLM 1992
16.278 NVSFREELOWLM 1992
16.279 NVSFREEMIN 1993
16.280 NVSMEDIAERR 1993

16.281 NVSUSED 1994

16.1 N

Specific to Block(s) ROL, ROR, SHL, SHR


Description Number of bits to be shifted
Data Type 16-Bit Integer
Range 0 to 16
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

Specific to Block(s) nooN


Description Number of inputs that must be TRUE to trigger an output change.
Data Type 16-Bit Integer
Range 1 to 5
Default 1
Config Load Yes
Active Loadable No

- 1857 -
Chapter 16 - Nxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters
Remarks

16.2 N[1..5]

Specific to PID-PL
Block(s)
Description Numerator Coefficients - Array of coefficients defining the numerator polynomial in
the Laplace transfer function model of the process.
Data Type Float64
Range
Default 1
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related D[1..5], NUMCOEFDEN, NUMCOEFNUM, PROCDEADTIME, PROCGAIN,
Parameters RESETMODEL UPDATEMODEL.
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. N[1] is the coefficient preceeding the s^0 (constant) term while N[5] is the
coefficient preceding the s^4 term. After the function block is loaded, this parameter
must be updated (see UPDATEMODEL) before any change in its value is
implemented. This parameter is applicable only when CTLEQN is set to Profit Loop
PKS, and is ignored in PID control equations.

16.3 N_EXIST_SPR

Specific to Block(s) ProfitCtl


Description N_EXIST_SPR
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No

- 1858 -
Chapter 16 - Nxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related Parameters
Remarks

16.4 NAME

Specific to All Function Blocks


Block(s)
Description Module Name
Data Type String
Range Length : 16 characters
Default Null
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence SR
Related
Parameters
Remarks A unique name to identify the block in the system. The module name should reflect
the type of module being used and its location. This will make tracking easier in the
future when you add more modules to your system. For example, the module name
PI_IOM_01 might stand for Pulse Input - Input Output Module - Primary chassis.
This name appears on all related system displays and any generated reports. The
following restrictions apply:
l The following characters are restricted and may not be used: ` ~ ! @ # $ % ^ &
* + - = ( ) { } [ ] | \ \ : ; ' < >, . ? / \ “
l Dots are allowed in parameter naming only.

l An embedded space or leading space is not allowed.


l Spaces are allowed in area naming only.

l Tabs may not be used.


l The name may not be null (no characters).
l One of these characters must be present in a valid name:
ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz
l The name must be less than the maximum size allowed for a tagname:
l 16 for composites.
l 15 for basic blocks.
l 100 for parameter names.

l The name must be unique.


Note that this is not an actual parameter and it does not appear in parameter point
selection lists.

- 1859 -
Chapter 16 - Nxxxx Parameters

Specific to Block(s) RCM, SCM, UCM


Description Provide the name for tagged objects
Data Type BLOCKID
Range
Default Null
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks Holds connection information so an alias reference can refer to it.

Specific to MAP
Block(s)
Description Reference name
Data Type String
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related FUNCTIONNAME.DESCFUNCTIONNAME.TYPE
Parameters
Remarks User-defined name of a function reference, block reference and parameter
reference configured for a Map block.

16.5 NAMEREF

Specific to RCM
Block(s)
Description Unit Control Module Name Reference
Data Type InOutCon
Range
Default Null
Config Yes
Load
Active No
Loadable

- 1860 -
Chapter 16 - Nxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related CONFIGCODE
Parameters
Remarks The parameter is available when USENAMEREF check box is configured as ON. You
can only use aliases configured in the Alias Table of the same RCM as names in this
field. The data type of the aliases has to be BLOCKID. Setting an RCM and PHASE to
use an Alias reference instead of a specific UCM or SCM/RCM gives you the ability
to switch between UCMs or SCMs/RCMs without having to reload the client
RCM/PHASE.

Specific to PHASE
Block(s)
Description SCM or RCM Name Reference
Data Type InOutCon
Range
Default Null
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related CONFIGCODE
Parameters
Remarks The parameter is available when USENAMEREF check box is configured as ON. You
can only use aliases configured in the Alias Table of the same RCM as names in this
field. The data type of the aliases has to be BLOCKID. Setting an RCM and PHASE
to use an Alias reference instead of a specific UCM or SCM/RCM gives you the
ability to switch between UCMs or SCMs/RCMs without having to reload the client
RCM/PHASE.

Specific to MR
Block(s)
Description Name Reference
Data Type InOutCon
Range
Default Null
Config Load No
Active No
Loadable

- 1861 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related CONFIGCODE
Parameters
Remarks Holds connection information to refer to an Alias. Not available when
USENAMEREF = NAME. This parameter is used to configure the UCM for RCM.

NOTE This parameter is disabled for MR as the units are associated to


the MR using the Unit Selection tab.

16.6 NAMURENBL_DI_C

Specific to UIO
Block(s)

Description Enable NAMUR support


Data Type BOOLEAN
Range
0 OFF Disable NAMUR Support

1 ON Enable NAMUR Support

Default OFF
Config Load Yes
Active No
Loadable

Access Lock AppDevOnly


Residence IOM Block
Related
Parameters

Remarks This parameter specifies that the input signal adheres to the NAMUR Standard (IEC
60947-5-6:1999 specification).
When NAMUR support is active, open circuit and short circuit detection are also
supported as specified in the standard.

16.7 NAMURPVRAW

Specific to UIO-2 – Series C DICHANNEL


Block(s)
Description NAMUR PV Raw Value(mA)
Data Type FLOAT32
Range N/A
Default 0
Config No

- 1862 -
Chapter 16 - Nxxxx Parameters

Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related ENABLENAMUR
Parameters
Remarks This parameter holds the NAMUR raw input value of the signal (in milli amps) from
the device connected to the IO terminal Assembly (IOTA) and is used to compute
Digital PV. This parameter is exposed only when the Module type is UIO-2 and
ENABLENAMUR is ON.

16.8 NAMURPVRAW_DI_S

Specific to UIO
Block(s)

Description NAMUR PV Raw Value(mA)


Data Type FLOAT32
Range N/A
Default 0
Config No
Load

Active
Loadable

Access View Only


Lock

Residence IOM Block


Related NAMURENBL
Parameters

Remarks This parameter holds the NAMUR raw input value of the signal (in milli amps) from the
device connected to the IO terminal block and used to compute Digital PV.
This parameter exposed only when the NAMURENBL is ON.

16.9 NETBCDSW

Specific to Block(s) CN100


Description Rotary Switch on IOTA to select network type and protocol
Data Type UINT16
Exposure Output
Range 0-9
Default Off
Config Load No

- 1863 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters IOTATOPOLOGY
Remarks 2 = FTE; 3 = HSR; 4 = PRP; 5 = DLR; 6 = transparent

16.10 NETELAPSEDTM

Specific to RampSoak
Block(s)
Description Net Elapsed Time for current RampSoak Profile (in Minutes)
Data Type Real
Range Greater-than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related TOTELAPSEDTM
Parameters
Remarks Does not include time for stopped timers due to deviation. This parameter is reset
to zero during the following conditions:
l When CEE state is changed to IDLE
l On block inactivation
l When a new profile is started during the block execution
l When the profile reset request is recognized during block execution (on
observing PROFRESET).
l When current profile identifier is changed by changing the value of
parameter CURPROFILEID

16.11 NETMODE[1..4]

Specific to JAGXCHAN
Block(s)
Description Net Weight Mode
Data Type Boolean
Range Off(0) Not Net weight Mode
On(1) Net Weight Mode
Default Off
Config Load No
Active No
Loadable

- 1864 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This is the value of bit 13 of the status word in the floating point input assembly
for the designated scale slot [1..4].

16.12 NETTIMEPASTTHISSEG

Specific to Block RAMPSOAK


(s)
Description Net Time Past in This Segment
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related
Parameters
Remarks This parameter is reset to zero during the following conditions:
l When a profile is started
l When the profile reset request is recognized during block execution (on
observing PROFRESET)
l When current segment identifier is changed by parameter store
CURSEGID.
l When the profile is restarted after a pause during block execution, with
RESETTIMER=ON

16.13 NETWORKTYPE

Specific to Block(s) CPM, RM, IOLIM


Description Network Type
Data Type Enumeration
Range ControlNet (0) Ethernet (1)
Default ControlNet (0)
Config Load No
Active Loadable No

- 1865 -
Chapter 16 - Nxxxx Parameters

Access Lock Engineer


Residence SR
Related Parameters ABORTALM.PR
Remarks

16.14 NETWRKTYP

Specific to Server
Block(s)
Description Network type - The type of network communication that the system uses
Data Type Enumeration
Range (0) DUAL - Server uses two separate subnets for communication.
(1) SINGLE/FTE - Server uses single subnet for communication. The
server may or may not be participating in an FTE community
using two NICs.
Default (1) Ethernet
Config Load No
Active No
Loadable
Access Lock Application Developer Only
Residence SCAN
Related
Parameters
Remarks

16.15 NEWSAMPLE

Specific to PID-PL
Block(s)
Description New PV Received - Indicates that a new PV measurement has been received.
Data Type Boolean
Range Off A new sample is not available
On A new sample is available. The PV has
been updated to reflect the latest
measurement.
Default On
Config No
Load
Active No
Loadable

- 1866 -
Chapter 16 - Nxxxx Parameters

Access Other Function Block


Lock
Residence CEE
Related PVASYNCOPT
Parameters
Remarks External synchronization allows an external device, such as a gas chromatograph,
to indicate when a new PV measurement is available. When PVASYNCOPT is
EXTERNALSYNC, the NEWSAMPLE flag must be set to indicate that a new PV value
is available. This block does not alter the value of the NEWSAMPLE parameter; an
external block, such as FTRIG, should be used for this purpose. This parameter is
applicable only when CTLEQN is set to Profit Loop PKS, and is ignored in PID
control equations.

16.16 NEXTCOMP

Specific to Transition
Block(s)
Description Next Component Reference
Data Type Output Connection
Range N/A
Default N/A
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks NEXTCOMP specifies the SCM component that follows the transition. The
transition.NEXTCOMP block pin is exposed by default. It may be connected to a
single step (through the step's DESC parameter), or left open (causing the handler
to end when the transition is true).

16.17 NEXTCOMP[1..15]

Specific to Step
Block(s)
Description Next Component Reference
Data Type Output Connection
Range N/A
Default N/A
Config Yes
Load

- 1867 -
Chapter 16 - Nxxxx Parameters

Active No
Loadable
Access Application Developer
Lock
Residence CEE
Related
Parameters
Remarks NEXTCOMP specifies the SCM component that follows the step. The step's
NEXTCOMP[1] block pin is exposed by default. It may be connected to a single
transition through the transition's DESC parameter (which may have additional
corrections from other steps' NEXTCOMP[i]). If left open, the handler will end when
the step completes. The block pins NEXTCOMP[2] through NEXTCOMP[i] can be
exposed for i transitions out of a step (with a maximum of 10). The transitions are
evaluated in order of the NEXTCOMP index. In the case of multiple true transitions,
the branch taken is the branch connected to the NEXTCOMP with the lowest index.

16.18 NEXTCOMP[1..15]

Specific to SYNC
Block(s)
Description Next Component Reference
Data Type Output Connection
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks NEXTCOMP specifies the SCM component that follows the SYNC. The SYNC's
NEXTCOMP[1] block pin is exposed by default. . This parameter supoorts up to 10
array indices, but it displays up to 15. If configured for more than 10, Control Builder
displays an error.

16.19 NEXTHANDLE

Specific to Block(s) Transition


Description Next Component Handle
Data Type 32-Bit Integer
Range 0 to 1023
Default 0

- 1868 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related NEXTCOMP, NUM.
Parameters
Remarks Contains the number (NUM) of the next SCM component following the
transition.

16.20 NEXTHANDLE[1..10]

Specific to Step
Block(s)
Description Next Component Handle
Data Type 32-Bit Integer
Range 0 to 1023
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NEXTCOMP[1..15], NUM.
Parameters
Remarks NEXTHANDLE[i] contains the number of the next Sequential Control Module
(SCM) component connected to NEXTCOMP[i].

16.21 NEXTNUMBER

Specific to Block(s) Step


Description Step Next Component Handle Count.
Data Type 32-Bit Integer
Range 0 to 10
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NEXTCOMP[1..15]
Remarks Contains the number of components (transitions) following the step.

- 1869 -
Chapter 16 - Nxxxx Parameters

16.22 NEXTPHASE

Specific to Block(s) CEEC300, CEESIMC200


Description Next PHASE of controller
Data Type 32-Bit Integer
Range 0 to 39
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), SIM_C200(CEESIMC200)
Related Parameters SIMENABLE
Remarks Parameter will be exposed and used only when SIMENABLE = TRUE

16.23 NFLAG

Specific to FLAGARRAY, SIFLAGARRCH


Block(s)
Description Number of Flag Values - Specifies the number of boolean values in the array of
data from the serial device.
Data Type 32-Bit Integer
Range SIFLAGARRCH: 1 to 512 FLAGARRAY: 1 to 1000
Default 1
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related SIFLAGARRCH only: FLAGARRAY only:
Parameters
Remarks

Specific to Block(s) PCDIFLAGARRCH


Description The number of Boolean values that must be read or written by this block.
Data Type 16-Bit Integer
Range 1 to 1968
Default 1
Config Load Yes
Active Loadable No

- 1870 -
Chapter 16 - Nxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related
Parameters
Remarks The number of flags to read. If this is a write request block, the number
should be 1.

16.24 NLFORM

Specific to Block(s) PID, PIDFF


Description Non-linear Gain form. Used if GAINOPT = Nonlin (configured)
Data Type Integer
Range 0 or 1
Default 1
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

16.25 NLGAIN

Specific to Block(s) PID, PIDFF


Description Non-linear Gain factor. Used if GAINOPT = Nonlin (configured).
Data Type 64-Bit Real Number
Range GAINLOLM to GAINHILM
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 1871 -
Chapter 16 - Nxxxx Parameters

16.26 NMIN

Specific to SignalSel
Block(s)
Description Number of Minimum Valid Inputs
Data Type 32-Bit Integer
Range 1-6
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related NUMPINPT, CURPINPT
Parameters
Remarks This parameter represents the number of minimum valid inputs for the algorithm
to execute and is enabled only when the SELMETHOD is other than MUX.

16.27 NMODE

Specific to Series CSeries C AOCHANNEL and Series C DOCHANNEL


Block(s)
Description Normal Mode
Data Type Enumeration
Range 0 None No configured “normal”
operating mode.
1 Man Manual is the configured
“normal” mode.
2 Cas Cascade is the configured
“normal” mode.
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence IOM
Related NMODATTR
Parameters
Remarks This parameter defines the normal operating mode for the channel block.
l NMODE (Normal Mode) is the MODE that is activated by pressing the Normal
button on the operator panel.
l If NMODE is None and the user presses the Normal button, the user is
informed that MODE was not set because MODE is None.

- 1872 -
Chapter 16 - Nxxxx Parameters

16.28 NMODATTR

Specific to Series CSeries C AOCHANNEL and Series C DOCHANNEL


Block(s)
Description Normal Mode Attribute
Data Type Enumeration
Range 1 Operator Users have the ability to
change certain parameters.
2 Program The program has ability to
change certain parameters.
0 None MODEATTR is not affected by
this parameter.
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence IOM
Related NMODE
Parameters
Remarks l NMODATTR (Normal Mode Attribute) is the MODEATTR (Mode Attribute) that is
activated by pressing the Normal button on the operator panel.
l If NMODATTR is None and the user presses the Normal button, the user is
informed that MODEATTR was not set because NMODATTR is None.

16.29 NNUMERIC

Specific to NUMERICARRAY, SINUMARRCH


Block(s)
Description Number of Numeric Values - Specifies the number of numeric values in the array
of data from the serial device.
Data Type 32-Bit Integer
Range SINUMARRCH: 1 to 64 NUMERICARRAY: 1 to 200
Default 1
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related SINUMARRCH only: PV[1..64] NUMERICARRAY only:
Parameters
Remarks SINUMARRCH: The interface to the serial device has a maximum size of 64 bytes.
The table below shows how the 64-bytes are interpreted, based on register type.

- 1873 -
Chapter 16 - Nxxxx Parameters

Register Type NNUMERIC Range

Real (4-byte) 0..16


Integer (2-byte) 0..32
Byte (1-byte) 0..64

Specific to PCDINUMARRCH
Block(s)
Description Number of Numeric Values
Data Type 16-Bit Unsigned Integer
Range 1 to 120, 1 to 60
Default 1
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks The number of numeric values to read. This number may not exceed 60 or 120
depending on the starting index. Valid values are actually dependent upon the start
index value. For example, with 300000 (signed integer) start index range, the valid
values would be 1 to 120 or 1 to 60 contiguous Signed integer numbers. Error
messages will be generated for invalid number entries.

16.30 NOCACHE_PARAM_ID [0...3]

Specific to FF Device
Block(s)
Description A FF device-level parameter to hold the identification of parameters which will be
treated as no-cache by the FIM.
Data Type UINT16
Range 0x0 to 0xFFFF [Hex value]
Default 0
Config Load PCM
Active No
Loadable
Access Lock Engineer
Residence FIM, ERDB
Related
Parameters
Remarks

- 1874 -
Chapter 16 - Nxxxx Parameters

16.31 NOCACHE_PARAM_NAME [0...3]

Specific to FF Device
Block(s)
Description A FF device-level parameter to hold the name of parameters which will be
treated as no-cache by the FIM.
Data Type PARAMID
Range
Default NONE
Config Load ERDBOnly
Active No
Loadable
Access Lock Engineer
Residence ERDB
Related
Parameters
Remarks

16.32 NODELCNELCN

Specific to ELCN_BRG, ELCN_NODE


Block(s)

Description Duplicate LCN Node Addresses Detected

Data Type Boolean

Range ON, OFF

Default OFF

Config Load No

Active No
Loadable

Access Lock ViewOnly

Residence ELCN_BRG, ELCN_NODE

Related SOFTFAIL
Parameters

Remarks The second node with the same LCN node number will not start up properly. This node
will need to be shutdown, reconfigured then reloaded.

- 1875 -
Chapter 16 - Nxxxx Parameters

16.33 NODENAME

Specific to Block(s) Server


Description Server Node Name - Host name or IP Address of the server.
Data Type String
Range N/A
Default Null
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SCAN
Related Parameters
Remarks

- 1876 -
Chapter 16 - Nxxxx Parameters

16.34 NODESTATESTR

Specific to Block(s) ELCN_NODE or ELCN_BRG, TCMI

Description Node State

Data Type String: 20 Characters Maximum

Range

ELCN_BRD OK, BACKUP, NOTLOADED


FAIL has failed

LOC LOAD is loading from a local source

NET LOAD is loading over the LCN network

NOT CONFIG is not configured

OFF is powered off

OK is running normally

PWR_ON is powered on and awaiting load

QUALIF has passed self test

READY has completed loading and is in initialization

TERM is terminating

TEST is under test

Default NULL

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_NODE or ELCN_BRG

Related Parameters Main tab

Remarks

16.35 NOFIELDPWR

Specific to Block(s) DIC, DOC


Description No Field Power - Indicates that a loss of field power has occurred.
Data Type Boolean
Range No loss of power detected (0) Loss of power detected (1)
Default No loss of power detected (0)
Config Load No
Active Loadable No

- 1877 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters ELOF[0..numChans-1](DIC only), EZCROSS[0..numChans-1] (DOC only)
Remarks Previously the LOF and ZCROSS parameters.

16.36 NOFIELDPWR[0..numChans-1]

Specific to Block(s) DIM, DOM


Description No Field Power - Indicates that a loss of field power has occurred.
Data Type Boolean
Range No loss of power detected (0) Loss of power detected (1)
Default No loss of power detected (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters ELOF[0..numChans-1] (DIM only), EZCROSS[0..numChans-1] (DOM only)
Remarks Previously the LOF and ZCROSS parameters.

16.37 NOLOAD

Specific to Block(s) DOC


Description Indicates when output current draw is below the threshold.
Data Type Boolean
Range Current draw is not below threshold (0) Current draw is below threshold (1)

Default Current draw is not below threshold (0)


Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters ENDOFFSETENDTIMEENOLOAD[0..numChans-1]
Remarks

- 1878 -
Chapter 16 - Nxxxx Parameters

16.38 NOLOAD[0..numChans-1]

Specific to Block(s) DOM


Description Indicates when output current draw is below the threshold.
Data Type Boolean
Range Current draw is not below threshold (0) Current draw is below threshold (1)

Default Current draw is not below threshold (0)


Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters ENDOFFSET, ENDTIMEENOLOAD[0..numChans-1]
Remarks

16.39 NONCRITICALMVLOSS

Specific to Block(s) ProfitCtl


Description Non Critical MV Loss
Data Type ENUM
Range NA
Default STOP
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

16.40 NONFTEMARTADDRCOUNT

Specific to FTEB C300, PGM, FIM4, EHPM


Block(s)
Description Non-Fault Tolerant Ethernet (FTE) MAC Address Resolution Table (MART) Address
Count - Identifies the number of IP addresses contained in the non-FTE MART.
Data Type 16-Bit Integer
Range
Default 0
Config Load No

- 1879 -
Chapter 16 - Nxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

16.41 NONFTEMARTAVGDEPTH

Specific to FTEB C300, PGM, FIM4 , EHPM


Block(s)
Description Non-Fault Tolerant Ethernet (FTE) MAC Address Resolution Table (MART) Average
Depth - Identifies the average depth of the non-FTE MART or the average number
of entries in the table.
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

16.42 NONFTEMARTCOLLCOUNT

Specific to FTEB C300, PGM, FIM4, EHPM


Block(s)
Description Non-Fault Tolerant Ethernet (FTE) MAC Address Resolution Table (MART) Collision
Count - Identifies the Number of collisions that have occurred when hashing the
non-FTE MART.
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable

- 1880 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

16.43 NONFTEMARTMAXDEPTH

Specific to FTEB C300, PGM, FIM4, EHPM


Block(s)
Description Non-Fault Tolerant Ethernet (FTE) MAC Address Resolution Table (MART)
Maximum Depth - Identifies the maximum depth that the non-FTE MART has
reached or the largest number of entries in the table.
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

16.44 NONPUBLISHABLE

Specific to Server
Block(s)
Description Non-publishing server
Data Type Boolean
Range (0) Publishing server
(1) Non-publishing server.
Default 0
Config Load No
Active No
Loadable

- 1881 -
Chapter 16 - Nxxxx Parameters

Access Lock Application Developer Only


Residence SCAN
Related
Parameters
Remarks Designates the node as a non-publishable server. Connections to this server are
not be included in the list of connections for other servers. E-servers are an
example of non-publishing servers.

16.45 NONREDFTABA

Specific to All IOM Blocks


Block(s)
Description Nonredundant Field Termination Assembly (FTA) BA. Shows that a nonredundant
I/O Module is connected to the cable B connector on the Channel A FTA.
Data Type Boolean
Range 0 Off Ok
1 On Nonredundant IOM on FTA
connector B.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

16.46 NONREDFTABB

Specific to All IOM Blocks


Block(s)
Description Nonredundant Field Termination Assembly (FTA) BB. Shows that a nonredundant
I/O Module is connected to the cable B connector on the Channel B FTA.
Data Type Boolean
Range 0 Off Ok
1 On Nonredundant IOM on FTA
connector B.
Default Off (0)
Config Load No
Active No
Loadable

- 1882 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks

16.47 NOOFFTENODES

Specific to TCMI
Block(s)
Description Number Fault Tolerant Ethernet (FTE) nodes - Identifies the current number of FTE
node within the FTE community.
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks

16.48 NOOFUPDATES

Specific to Block(s) EIM


Description Report Update Count
Data Type UINT32
Range 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

- 1883 -
Chapter 16 - Nxxxx Parameters

16.49 NOPERDB #

Specific to Block(s) EHPM


Description Number of points in ERDB after import
Data Type INT32
Range 0 to 6000 (points created in TPS side)
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SRAL
Related Parameters
Remarks Number of EHPM points imported to the EHPM in ERDB.

16.50 NOREQUESTPREAMBLES

Specific to HARTDEVICE (Chassis I/O)


Block(s)
Description Number of Request Preambles - Indicates the number of request preambles
needed for the HART device to receive a message.
Data Type 8-Bit Unsigned Integer
Range 0 to 20
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

16.51 NORMAL

Specific to Block(s) Flag, Push.


Description Normal State - Defines the normal state of the Flag function block.
Data Type Enumeration STATETEXT, None
Range StateText (0) StateText (1) None
Default None

- 1884 -
Chapter 16 - Nxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Supervisor Engineer is limited to change to/from None.
Residence CEE
Related Parameters OFFNRMALM.FL, PV, STATETEXT[0..1].
Remarks Setting NORMAL to None disables the Off-Normal alarm.

16.52 NORMAL[1..24]

Specific to FIRSTOUT
Block(s)
Description Normal state of an INPUT[*]
Data Type Boolean
Range OFF, ON
Default OFF
Config Load YES
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks First Out logic takes this state as reference and reports an INPUT transition when
input changes from the NORMAL State.

16.53 NORMMODE

Specific to DevCtl All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Normal Mode - Defines the normal mode of a Regulatory Control function block.
Data Type Enumeration REGMODE
Range Manual (Man) Automatic (Auto) Cascade (Cas) Backup Cascade (Bcas) None
Default DevCtl: Manual (Man) RegCtl: None
Config Yes
Load
Active No
Loadable

- 1885 -
Chapter 16 - Nxxxx Parameters

Access Engineer
Lock
Residence CEE
Related
Parameters
Remarks The mode of a RegCtl block is derived at runtime, based on current conditions.
However, the user may configure a normal mode (NORMMODE) and normal
attribute MODE), and go to that mode by pressing the NORM button on the
operator pane. When the button is pressed, the contents of NORMMODE is copied
to MODE, and NORMMODEATTR is copied to MODEATTR. Possible values for
NORMMODE are None, Man, Auto, and Cas. Possible values for NORMMODEATTR
are Operator, Program, and None. Although MODE and NORMMODE share the
same enumeration, MODE cannot be set to NONE and NORMMODE cannot be set
to NORMAL. Control Builder checks status at load time and triggers an error flag, if
it detects any problems. Note: Storing to MODE will not cause NORMMODE to
change. Likewise, storing to MODEATTR will not cause NORMMODEATTR to
change.

Specific to Block(s) DEVCTL, MAINIBV, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Normal Mode
Data Type Enumeration MODE
Range Manual (Man)
Default Manual (Man)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters MODE
Remarks

Specific to SCM, RCM


Block(s)
Description Normal Mode - Defines the normal mode of the SCM.
Data Type Enumeration MODE
Range None (0) Auto (1) SemiAuto (2) SingleStep (3) Manual (4) Normal (5)
Default SCM: None (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODE
Parameters
Remarks When Normal (5) is stored to MODE, the SCM MODE is set to the configured
NORMMODE. Only None (0) and Auto (1) are valid for SCM NORMMODE.

- 1886 -
Chapter 16 - Nxxxx Parameters

16.54 NORMMODEATTR

Specific to SCM, RCM, DevCtl, All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF,
Block(s) PosProp, PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc,
RegSummer, and Switch.
Description Normal Mode Attribute - Defines the Normal Mode Attribute of a Regulatory Control
function block.
Data Type Enumeration MODEATTR
Range None (0) Oper (1) Program (2)
Default None (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODEATTR DevCtl only: MODEATTR, MODETRACK, NUMDOUTS.
Parameters
Remarks Access Illegal if NUMDOUTS = 0.

Specific to Block MAINIBV, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


(s)
Description Normal Mode Attribute - Defines the Normal Mode Attribute of a Drive Control
function block
Data Type Enumeration
Range NONE (0) OPER (1) PROGRAM (2)
Default NONE
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related MODEATTR, MODETRACK
Parameters
Remarks

16.55 NOTACTSUPV

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Not the Active Supervisor.
Data Type Boolean
Range Off (0): Card is the Active Supervisor.
On (1): Card is not the Active Supervisor.
Default Off (0)

- 1887 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks When On (1), indicates that the IOL interface daughter card could not transition
into the active supervisor role.

16.56 NOTCHFILTER[0..numChans-1]

Specific to AIM
Block(s)
Description Isolated Modules: Notch Filter Non_Isolated Modules: 3 dB Filter
Data Type Non-Isolated Modules: Enumeration of THREEDBFILTR Isolated Modules:
Enumeration of NOTCHFILTER
Range Non-Isolated Modules: 20 Hz (0) Isolated Modules: 50Hz (1) 60Hz (2)
Default Non-Isolated Modules: 20Hz (0) Isolated Modules: 60Hz (2)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Note that for the non-isolated Analog Input modules, NOTCHFILTER is
configurable on a per-module basis, rather than on a per channel basis.

16.57 NOTCHFILTER[0..7]

Specific to Block(s) Chassis HART AI IOM


Description Notch Filter Setting
Data Type Enumeration of NOTCHFILTER
Range 20Hz (6)
Default 20 Hz (6)
Config Load Yes
Active Loadable No

- 1888 -
Chapter 16 - Nxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related Parameters
Remarks

16.58 NOTCHFILTER

Specific to EtherNet/IP [EIP] IOMs: 1732E-IR4IM12R, 1732E-IT4IM12R, 1738-IE2CM12, 1738-


Block(s) IE4CM12, 1738-IR2M12, 1738-IT2IM12
Description Notch Filter — This parameter selects the desired filter frequency for the module.
Data Type Enumeration
Range Module 1732E-IR4IM12R, 1732E-IT4IM12R:
l 50Hz (1)
l 60Hz (2)
l 250Hz (4)
l 500Hz (8)
Module 1738-IR2M12, 1738-IT2IM12:
l 50Hz (0)
l 60Hz (1)
l 100Hz (2)
l 120Hz (3)
l 200Hz (4)
l 240Hz (5)
l 300Hz (6)
l 400Hz (7)
l 480Hz (8)
Module 1738-IE2CM12:
l 50Hz (1)
l 60Hz (2)
l 250Hz (4)
l 500Hz (6)
Module 1738-IE4CM12:
l 60Hz (0)
l 50Hz (1)
l 100Hz (2)
l 120Hz (3)
l 200Hz (4)
l 240Hz (5)
l 300Hz (6)
l 400Hz (7)
l 480Hz (8)
Default 60Hz (0)

- 1889 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related UPDATERATE
Parameters
Remarks The UPDATERATE changes for each filter setting. For modules 1738-IT2IM12,
1732E-IT4IM12R this option is present for each channel.

16.59 NOTE

Specific to Step
Block(s)
Description Step Note
Data Type BigString
Range Maximum length of 20,000 characters
Default “”
Config Load Yes
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related ARIBITRATIONSTATUS
Parameters
Remarks Contains raw HTML for configured Step Note. User does not have to be aware of
or do anything with this parameter.

16.60 NOTIFINHIBIT

Specific to CEEC300, CEESIMC200, CEEUOC


Block(s)
Description Notification Inhibit
Data Type Boolean
Range True - Inhibit False - Do Not Inhibit
Default False
Config Yes
Load
Active No
Loadable

- 1890 -
Chapter 16 - Nxxxx Parameters

Access Lock Engineer


Residence C300(CEEC300), SIM_C200(CEESIMC200), UOC(CEEUOC)
Related SIMENABLE
Parameters
Remarks Notification Inhibit - Lets you inhibit display of notifications associated with the
CEESIMC200 and its contents on the Station's Alarm Summary during simulation.
Parameter will be exposed and used only when SIMENABLE = TRUE

16.61 NOTIFPUBLISH

Specific to Block(s) OPCUASRVUOC


Description Max Notifications Per Publish
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

16.62 NOTRATEAVG

Specific to Block IOLIM, Secondary IOLIM, C300 IOLINK, FIM, CPM


(s)
Description Notification Rate Average. Shows the average notifications transfer rate in
notifications per second.
Data Type 32-Bit Real Number
Range N/A
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

- 1891 -
Chapter 16 - Nxxxx Parameters

16.63 NOTRATEMAX

Specific to IOLIM, Secondary IOLIM, C300 IOLINK, FIM, CPM


Block(s)
Description Notification Rate Maximum. Shows the maximum notification transfer rate in
notifications per second.
Data Type 32-Bit Real Number
Range N/A
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

16.64 NOTREDCNFGA

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Not Redundantly Configurable. Shows that associated IOM on
Channel A is not redundantly configurable.
Data Type Boolean
Range 0 Off Ok
1 On IOM not redundantly
configurable
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks When asserted, indicates that the IOM is not Redundantly configurable.

- 1892 -
Chapter 16 - Nxxxx Parameters

16.65 NOTREDCNFGB

Specific to All PM I/O Modules and Series C I/O Modules


Block(s)
Description I/O Module Not Redundantly Configurable. Shows that associated IOM on
Channel B is not redundantly configurable.
Data Type Boolean
Range 0 Off Ok
1 On IOM not redundantly
configurable
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks When asserted, indicates that the IOM is not Redundantly configurable.

16.66 NOTSAMEFTAA

Specific to All IOM Blocks


Block(s)
Description Not Same FTA Channel A. Shows that a redundancy hardware diagnostic failure
exists or that redundant I/O Module partners are connected to different channel A
FTAs.
Data Type Boolean
Range 0 OFF Ok.
1 ON Redundant IOM pair not
on same FTA.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

- 1893 -
Chapter 16 - Nxxxx Parameters

16.67 NOTSAMEFTAB

Specific to All IOM Blocks


Block(s)
Description Not Same FTA Channel B. Shows that a redundancy hardware diagnostic failure
exists or that redundant I/O Module partners are connected to different channel B
FTAs.
Data Type Boolean
Range 0 OFF Ok.
1 ON Redundant IOM pair not
on same FTA.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

16.68 NOWAITINGFL

Specific to SCM. RCM, UCM, CM


Block(s)
Description No Waiting Flag - No request are waiting.
Data Type Boolean
Range Off 1 or more requests are waiting
On No requests are waiting
Default On
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related QUEUESIZENUMWAITINGCONFLICTFL
Parameters
Remarks This flag indicates, that no unsatisfied requests for the resource exist. This
indication is independent of QUEUESIZE. OFF, if NUMWAITING >(greater than) 0
OFF, if CONFLICTFL = ON ON, otherwise If QUEUESIZE = 0, NOWAITINGFL will
always be the opposite of CONFLICTFL. If QUEUESIZE >(greater than) 0,
NOWAITINGFL will always be the opposite of WAITINGFL.

- 1894 -
Chapter 16 - Nxxxx Parameters

16.69 NOWALARM

Specific to Block(s) ProfitCtl


Description Current alarms
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

16.70 NSTRING

Specific to TEXTARRAY, SITEXTARRCH


Block(s)
Description Number of String Values - Specifies the number of string values in the array of data
from the serial device.
Data Type 32-Bit Integer
Range SITEXTARRCH only: 0 to 8 TEXTARRAY only: 0 to 120
Default 1
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence CEE
Related SITEXTARRCH only: STRLEN, STR[1..8]. TEXTARRAY only: STRLEN, STR[1..120].
Parameters
Remarks The Text Array block supports a maximum size of 960 two-byte characters. This
number is chosen based on the amount of data that can fit in one ControlNet
message. This is important when full array access is supported. SITEXTARRCH only:
With the interface to the serial device having a maximum size of 64-bytes, the table
below shows how the 64-bytes are interpreted, based on the NSTRING and STRLEN
configured, and the resulting STR[ ] range. Illegal combinations of NSTRING and
STRLEN (those requiring more than 64-bytes of data) will be rejected.
NSTRING STRLEN STR[ ] Range

- 1895 -
Chapter 16 - Nxxxx Parameters

1 64 1..1
2 32 1..2
4 16 1..4
8 8 1..8

Specific to PCDITEXTARRCH
Block(s)
Description Number of text Strings in the array
Data Type 16-Bit Unsigned Integer
Range 1 to 16
Default 1
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks The number of text strings (NSTRING) to read. Valid values from 1 to 16. The
number of strings (NSTRING) times the number of characters per string (STRLEN)
may not exceed 120 unicode characters or 240 ASCII characters, if CONVTOASCII is
enabled/on.

16.71 NTOTMEMDESC

Specific to ACE, CPM, SIM_C200, CEEC300, CEEUOC, CEECN100


Block(s)
Description Total Mem Descriptors
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE, C200(CPM), SIM_C200, C300, UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM, MAXFREEBLKSZ, NUMFREEBLKS, NUMFREEDESC, NUMREGDESC,
Parameters NUMUSEDBLKS, NUMUSEDDESC, TOTALMEM, USEDMEM.
Remarks Total Number of Memory Descriptors available. This is a static number. Units are
number of descriptors

- 1896 -
Chapter 16 - Nxxxx Parameters

16.72 NTPADDRESS

Specific to Block(s) EIM, UOC, TCIM


Description NTP Server Address
Data Type STRING
Range NA
Default 0.0.0.0, 10.10.1.55
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks NTP server IP address.

16.73 NTPDELAY

Specific to Block(s) EIM, UOC, CN100


Description NTP Delay (msec)
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Network travel time between NTP server and device, in milliseconds.

16.74 NTPDELAYMAX

Specific to Block EIM, UOC, CN100


(s)
Description NTP Maximum Delay (msec)
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No

- 1897 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks High water mark of network travel time between NTP server and device, in
milliseconds.

16.75 NTPLASTSTRATUM

Specific to Block(s) UOC, TCMI, CN100


Description NTP Last Stratum Value
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Last NTP stratum value.

16.76 NTPOFFSET

Specific to Block(s) EIM, UOC, CN100, C300


Description NTP Offset (msec)
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Clock offset between NTP server and device, in milliseconds.

Specific to Block(s) TCMI


Description NTP Offset (msec)
Data Type FLOAT64
Range ±1.7E+308

- 1898 -
Chapter 16 - Nxxxx Parameters

Default 1
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks Offset between system time and NTP server time.

16.77 NTPOFFSETMAX

Specific to Block(s) EIM, TCMI, UOC, CN100, C300


Description NTP Maximum Offset (msec)
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of clock offset between NTP server and device, in
milliseconds.

16.78 NTPSTAT

Specific to Block(s) EIM, UOC, TCMI, CN100


Description NTP Status
Data Type ENUM
Range NA
Default SNTP1
Config Load No

Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks NTP time synchronization status.

- 1899 -
Chapter 16 - Nxxxx Parameters

16.79 NULLPVFL

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description PV Bad Value Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related GPV, PV. DEVCTL Only: DIMODEDIPVMAP[0..15]NUMDINPUTS,
Parameters
Remarks This is not necessarily the same as the BADPVALM.FL alarm flag. DEVCTL Only:
Access is illegal, if NUMDINPUTS = 0.

16.80 NUM

Specific to Handler, Step, Transition, Phase


Block(s)
Description Sequential Control Module (SCM) Component Number.
Data Type 32-Bit Integer
Range 0 to 1023
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ACTIVELOC.STEPN[1..15], ACTIVELOC.HANDLERN, RESADDR[1..15]
Parameters
Remarks NUM is the number assigned to each component when the SCM/RCM is loaded.
The absolute number of a component is not guaranteed to remain the same if the
SCM/RCM is reloaded. This parameter shall only be used for comparisons with or
assignments of one of the related parameters. Hardcoding component numbers in
SCM/RCM expressions or other control strategies is not a supported configuration.

- 1900 -
Chapter 16 - Nxxxx Parameters

Specific to CM, UCM, SCM, RCM, CR, MR (all container blocks)


Block(s)
Description Internal Handle
Data Type INT32
Range Not applicable
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related UNITNUM[1..50]
Parameters
Remarks This parameter holds the IOID of container block in INT32 format. The absolute
number of a container is not guaranteed to remain the same under all engineering
scenarios involving load operations. This parameter shall only be used for
comparisons with or assignments of one of the related parameters. Hardcoding
container numbers in expressions or other control strategies is not a supported
configuration.

16.81 NUMACCRQUAVG

Specific to CEE, CEEC300, CEEUOC, CEECN100


Block(s)
Description Push/Store Response Rate
Data Type FLOAT 64
Range Greater than or equal to 0.00
Default 0.00
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), UOC(CEEUOC), CN100(CEECN100)
Related NUMACCRQUMAX, STATSRESET.
Parameters
Remarks Rolling average of acyclic parameter request throughput. Blocks such as PUSH,
CAB and STEP outputs cause acyclic peer to peer communication traffic.

- 1901 -
Chapter 16 - Nxxxx Parameters

16.82 NUMACCRQUMAX

Specific to CEE, CEEC300, CEEUOC, CEECN100


Block(s)
Description Max Push/Store Rate
Data Type FLOAT 64
Range Greater than or equal-to 0.00
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE) , UOC(CEEUOC), CN100(CEECN100)
Related NUMACCRQUAVG, STATSRESET.
Parameters
Remarks Historical maximum of acyclic parameter request throughput since last store to
STATSRESET. SCM step outputs are the only block mechanisms to cause acyclic
peer to peer communication traffic.

16.83 NUMACEINCON

Specific to Block CEEC300, ACE, CPM, CEEACE, CEE, ICG, CEEUOC, CEECN100
(s)
Description Number of ACE Input Connections
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE),UOC(CEEUOC), CN100(CEECN100)
Related NUMACEOUTCON
Parameters
Remarks This parameter does apply for SIM_C200, since it cannot open connections to
an ACE.

- 1902 -
Chapter 16 - Nxxxx Parameters

16.84 NUMACEOUTCON

Specific to CEEC300, ACE, CPM, CEEACE, CEE, ICG, CEEUOC, CEECN100


Block(s)
Description Responding to ACEs
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), UOC(CEEUOC), CN100(CEECN100)
Related NUMACEINCON
Parameters
Remarks Number of ACE Output Connections - Defines number of Application Control
Environments (ACEs) for peer targets. This parameter does not apply for SIM_C200,
since it cannot open connections to an ACE.

16.85 NUMACT

Specific to CEE
Block(s)
Description Number of Activities
Data Type INT32
Range 0-1000
Default 0
Config Yes
Load
Active Yes
Loadable

- 1903 -
Chapter 16 - Nxxxx Parameters

Access AppDevOnly
Lock
Residence CEE
Related MAXNUMACT, NUMACTCRFAIL, NUMACTCR, ACTAVAIL, CURRNUMACT
Parameters
Remarks This parameter determines the maximum number of Activities that can be
associated with RCMs/SCMs/CRs in the CEE. The maximum value of NUMACT is
1000. If NUMACT is configured as a value greater than 0, then the CEE Activity
Manager (CAM) consumes 1K of the function block memory for Activities and one
Tag name for every Activity. The activity count needs to be large enough to account
for all activities created at the same time in the controller. The following should be
included:
l All top level SCMs, RCMs, and Control recipes that are configured with
Activities enabled and currently have an Activity in the Activity Summary (in
pre-execution, execution or post-execution).
l Executing child RCMs with Activity Parents and executing child Control recipes
(child SCMs are not included).

NOTE It is recommended to set NUMACT to a value that exceeds the


number of activities needed.

16.86 NUMACTCR

Specific to CEE
Block(s)
Description Control recipe count
Data Type Integer
Range 0-5000
Default 0
Config Load No
Active Loadable -
Access Lock ViewOnly
Residence CEE
Related -
Parameters
Remarks This parameter provides the count of executing Activities created from the Class
Based Master recipes.

- 1904 -
Chapter 16 - Nxxxx Parameters

16.87 NUMACTCRFAIL

Specific to Block(s) CEE


Description Number of creation fail attempts since the last success.
Data Type INT32
Range INT32
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMACT, CURRNUMACT, MAXNUMACT, ACTAVAIL, NUMACTCR
Remarks

16.88 NUMACTIVEPOINTS

Specific to Block OPC


(s)
Description Number of Active Items - The number of active items currently in this server's
Active List.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

16.89 NUMACTWRT

Specific to Block(s) CEEFB


Description Number of Active Write — Number of writes currently being processed on
this CEE.
Data Type INT16
Range
Default 0

- 1905 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks

16.90 NUMADJPARAMS

Specific to Block(s) SCM, RCM


Description Number of Adjustable Formula Parameters
Data Type 32-Bit Integer
Range
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

16.91 NUMALIASES

Specific to Block(s) SCM, RCM


Description Number of aliases configured in the Alias Table.
Data Type 16-Bit Integer
Range 0 to 500
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks

- 1906 -
Chapter 16 - Nxxxx Parameters

16.92 NUMALLTRANS

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Number of all PV transitions
Data Type Float64
Range 0.0 to Maximum Real Number
Default 0
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMTRANS[0..2] TRKNUMTRANS
Remarks

16.93 NUMANNWIN

Specific to Block ANNPANEL


(s)
Description Number of Annunciator Panels
Data Type 8-Bit Unsigned Integer
Range 1-32
Default 16
Config Load YES
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related FLSHSTAT
Parameters
Remarks Determines the number of alarm window function blocks that can be
connected to this block.

16.94 NUMASSIGNFBS

Specific to CEEC300, CEESIMC200, CEEUOC


Block(s)
Description Max Assigned Blocks
Data Type 32-Bit Integer
Range
Default 1024

- 1907 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related SIMENABLE
Parameters
Remarks Number of Assigned Function Blocks – Defines maximum assigned blocks to given
environment. Parameter will be exposed and used only when SIMENABLE = TRUE

16.95 NUMBEROFCVS

Specific to PROFITCTLIN, PROFITCTL


Block(s)
Description Number of CVs
Data Type INT16
Range ±32767
Default 1
Config Load Yes
Active No
Loadable
Access Lock APPDEVONLY
Residence CEE
Related MODELISVALID
Parameters
Remarks This parameter represents the number of control variables in the model. In ACE,
maximum number of control variables can be 40 and in C300 they can be 10.

16.96 NUMBEROFDVS

Specific to PROFITCTLIN, ProfitCtl


Block(s)
Description Number of DVs
Data Type INT16
Range NA
Default 0
Config Load Yes
Active No
Loadable

- 1908 -
Chapter 16 - Nxxxx Parameters

Access Lock APPDEVONLY


Residence CEE
Related MODELISVALID
Parameters
Remarks This parameter represents the number of disturbance variables in the model. In
ACE, maximum number of disturbance variables can be 20 and in C300 they can be
5.

16.97 NUMBEROFEQP

Specific to Block(s) GRPCAPRBK


Description Number of equipment in the group.
Data Type 8-Bit Unsigned Integer
Range 1-10
Default 2
Config Load YES
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks This indicates the number of equipments for which the OUTCAP is
calculated.

16.98 NUMBEROFMVS

Specific to Block ProfitCtl


(s)
Description Number of MVs
Data Type INT16
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related
Parameters
Remarks For ACE, you can have maximum 20 MVs and for C300 you can have
maximum 5 MVs

- 1909 -
Chapter 16 - Nxxxx Parameters

Specific to Block(s) PROFCONOUT


Description Number of MVs
Data Type INT16
Range ±32767
Default 1
Config Load
Active Loadable No
Access Lock APPDEVONLY
Residence
Related Parameters NA
Remarks Number of manipulated variables

16.99 NUMBEVENTSAVG

Specific to Block(s) CEEFB, CEEC300,CEEACE, CEEC200E, CEEUOC


Description NumBatch Events Rateber of MVs
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters
Remarks

16.100 NUMBEVENTSMAX

Specific to Block(s) CEEFB, CEEC300,CEEACE, CEEC200E, CEEUOC


Description Maximum of Batch Events Rate
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters
Remarks

- 1910 -
Chapter 16 - Nxxxx Parameters

16.101 NUMBLKINST

Specific to Block(s) CEE, CEEC300, CEEUOC, CEECN100


Description Number of Block Instances Loaded
Data Type INT32
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE, C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related Parameters
Remarks This Parameter give the number of instances of block is loaded

16.102 NUMBLKREF

Specific to Block(s) MAP


Description Block references number
Data Type INT32
Range 0 - 250
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Number of block references configured in the PDE of the respective Map
block.

16.103 NUMBLKTYPES

Specific to Block(s) CEEC300, CEE, CEEUOC, CEECN100


Description Number of Block Types
Data Type 32-Bit Integer
Range 0 to 4,258,848 (block types)
Default 0
Config Load No
Active Loadable No

- 1911 -
Chapter 16 - Nxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), UOC(CEEUOC), CN100(CEECN100)
Related
Parameters
Remarks It includes the block types for all the loaded Control Component Libraries
(CCLs).

16.104 NUMBLOBS

Specific to Block(s) Applies to all blocks that are supported in simulation.


Description Number of Dynamic State Blobs.
Data Type 32-BIT INTEGER
Range 1-256
Default 1
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks Number of BLOBs needed to save dynamic state data.

16.105 NUMBLOCK

Specific to All Fieldbus Devices


Block(s)
Description Number of Blocks - Shows the total number of blocks that exist in the given Fieldbus
device.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable

- 1912 -
Chapter 16 - Nxxxx Parameters

Access ViewOnly
Lock
Residence Controller
Related NUMBLOCKS
Parameters
Remarks The total number of blocks in a device includes all permanent and instantiated
blocks. Blocks may or may not be loaded to the Monitoring side. For example, a
device with 1 resource block, 5 permanent transducer blocks and 5 permanent
function blocks will have 11 blocks total regardless of whether the blocks are in use
or not. Instantiated blocks will be added to and removed from the device's block
count as needed. If instantiated blocks are removed, the block count for that device
will decrease. Likewise, the block count will increase when blocks are instantiated.

16.106 NUMBLOCKS

Specific to SCM, RCM, CR, and MR


Block(s)
Description For SCM, RCM, Control recipe - Number of component blocks. For Master recipe -
All time maximum of CR.NUMBLOCKS
Data Type INT32
Range 0
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUMCOMPFB
Parameters
Remarks For SCM, RCM - True count in contrast to NUMCOMPFB, fixed after download,
always = NUMCOMPFB For Control recipe - True count of Control recipe creation
blocks, which can only increase during execution, always = NUMCOMPFB For
Master recipe - Reset during activation, updated during Control recipe destruction,
always = NUMCOMPFB, can be used as test coverage indicator during FAT.

16.107 NUMBLOCKUSED

Specific to FIM, FIM4


Block(s)
Description Number of Blocks Used - Shows the total number of blocks that exist in all the
devices connected to the given Fieldbus Interface Module.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0

- 1913 -
Chapter 16 - Nxxxx Parameters

Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence Controller
Related NUMBLOCK
Parameters
Remarks Total number of blocks used for all devices connected to all links on a FIM/FIM4.
This value includes both commissioned and uncommissioned devices. The total
number of blocks in a device includes all permanent and instantiated blocks. Blocks
may or may not be loaded to the Monitoring side. For example, a device with 1
resource block, 5 permanent transducer blocks and 5 permanent function blocks
will have 11 blocks total regardless of whether the blocks are in use or not.
Instantiated blocks will be added to and removed from the device's block count as
needed. If instantiated blocks are removed, the block count for that device will
decrease. Likewise, the block count will increase when blocks are instantiated.

16.108 NUMBOOL

Specific to Block EIM


Description Number of configured Bool parameters
Data Type INT16
Range 0 to 200
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related NUMBOOL of DSIN block, DSBOOLPARAM, MMSBOOLPARAMCONN,
Parameters DSBOOLSTATE
This parameter indicates the no. of BOOL parameters configured in the
Remarks Dataset.

16.109 NUMC3INCON

Specific to CEEC300, ACE, CPM, SIM_C200, CEEACE, CEE, CEESIMC200, CEEUOC, CEECN100
Block(s)
Description Number of C300 input Connections - Defines number of C300s for peer targets.
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0

- 1914 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), UOC(CEEUOC), CN100(CEECN100)
Related NUMC3OUTCON
Parameters
Remarks Number of C300 input Connections - Defines number of C300s for peer targets.

16.110 NUMC3OUTCON

Specific to CEEC300, ACE, CPM, SIM_C200, CEEACE, CEE, CEESIMC200, CEEUOC, CEECN100
Block(s)
Description Number of C300 Output Connections - Defines number of originator C300s.
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), UOC(CEEUOC), CN100(CEECN100)
Related NUMC3INCON
Parameters
Remarks Number of C300 Output Connections - Defines number of originator C300s.

16.111 NUMCABCOL (Custom cabinet)

Specific to Block(s) Cabinets


Description It defines the number of columns to configure the IO modules to the
cabinet.
Data Type INT16
Range 1–3
Default 3
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SRAL
Related Parameters
Remarks

- 1915 -
Chapter 16 - Nxxxx Parameters

16.112 NUMCABROWS

Specific to Block(s) Cabinets


Description It defines the number of rows to configure the IO modules to the cabinet.
Data Type INT16
Range 1 – 12
Default 12
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SRAL
Related Parameters
Remarks

16.113 NUMCABTYPES

Specific to CEE-ACE block, CEE-C300 block


Block(s)
Description Number of CAB types - Number of CAB types currently in use within the CEE.
Data Type Integer
Range <= MAXCABTYPES
Default 0
Config No
Load
Active No
Loadable
Access View Only
Lock
Residence CEE
Related MAXCABTYPES
Parameters
Remarks NUMCABTYPES starts at 0 before any CAB types and instances have been loaded. It
increments by one with the load of every new CAB type and decrements by one
every time a CAB type is no longer in use within the CEE. For C300, NUMCABTYPES
indicates the total number of types currently loaded and resident in memory within
the C300. For ACE, NUMCABTYPES indicates the total number of CAB types loaded
and in use. With CAB/ACE, types which are no longer in use remain memory
resident until ACE shutdown and restart but are not counted in NUMCABTYPES.
NUMCABTYPES is visible on the CAB Types Info tab of the CEE block form.

- 1916 -
Chapter 16 - Nxxxx Parameters

16.114 NUMCACHE[1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Cached Parameters
Data Type 16-bit Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks This parameter indicates the number of cached parameters residing in the IOLINK.
The index of this array corresponds to the IOP number.

16.115 NUMCACHEVAR

Specific to Block(s) IOLIM, Secondary IOLIM, FIM


Description Number of Cached Variables. Shows the number of cached parameter
values.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks

- 1917 -
Chapter 16 - Nxxxx Parameters

16.116 NUMCCLRQU

Specific to CEE, CEEC300, CEEUOC, CEECN100


Block(s)
Description Total Initiator Pull Requests
Data Type FLOAT 64
Range Greater than or equal to 0.0
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related SUBSCPERIOD
Parameters
Remarks Value of NUMCCLRQU is associated with the currently loaded block configuration
and SUBSCPERIOD. Note that this statistical parameter is not affected by.

Specific to Block(s) IOLIM, Secondary IOLIM, CPM, C300 IOLINK


Description AO/DO Channel Connections.
Data Type 32-bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM, C200, C300 IOLINK
Related Parameters
Remarks This parameter displays the total number of connected AO and DO
channels.

16.117 NUMCCLRQUAVG

Specific to Block(s) CEEFB, CEEC300, CEEUOC, CEECN100


Description Avg Initiator Pull Requests.
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No

- 1918 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence C200(CEE), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related Parameters NUMCCLRQUNUMCCLRQUMAX
Remarks Rolling average of peer pull requests in the last second.

16.118 NUMCCLRQUMAX

Specific to Block(s) CEE, CEEC300, CEEUOC, CEECN100


Description Maximum Initiator Pull Requests since last Statistics reset
Data Type Float64
Range
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related Parameters NUMCCLRQUNUMCCLRQUAVG
Remarks

16.119 NUMCDDMTYPES

Specific to Block(s) CEEFB, CEEACEFB, CEESIMC200FB, CEEC300, CEEUOC, CEECN100


Description Instantiated Block Types
Data Type INT32
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200(CEE), C300(CEEC300) , SIM_C200(CEE), UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

- 1919 -
Chapter 16 - Nxxxx Parameters

16.120 NUMCHANS

Specific to Block(s) All PM I/O Modules and Series C I/O Modules


Description Number of Channels. Defines the number of channels for the I/O Module
(IOM).
Data Type 16-Bit Unsigned Integer
Range 1 to 32
Default Based on IOM type.
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM/IOLINK
Related
Parameters
Remarks

Specific to Block(s) PCDI_MASTER


Description Number of Channels
Data Type 16-Bit Unsigned Integer
Range
Default 64
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

Specific to Block(s) UIO


Description Number of Channels
Data Type UINT16
Range N/A
Default 16
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence UIO
Related Parameters N/A
Remarks This parameter specifies the number of channels for the IOM.

- 1920 -
Chapter 16 - Nxxxx Parameters

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-


Block(s) RELAY, AO04, AI16-100MS, AO08, DI16-VACDC
Description Number of Channels
Data Type UINT16
Range N/A
Default 16
Config Load No
Active
Loadable

Access Lock ViewOnly


Residence IOM Block
Related N/A
Parameters

Remarks This parameter specifies the number of channels for the IOM.

16.121 NUMCLIENTCONN

Specific to Block OPC


(s)
Description Number of Client Connections - Current number of clients connected to the
Gateway.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

16.122 NUMCLXPROC

Specific to Block CEEFB


(s)
Description Number of Control Logix PLCs — It Indicates the number of Control Logix
PLCs configured.
Data Type UINT32
Range
Default 0

- 1921 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks

16.123 NUMCLXUDT

Specific to Block CEEFB


(s)
Description Number of Control Logix UDTs — It Indicates the number of Control Logix
UDTs configured.
Data Type UINT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks

16.124 NUMCMPCONTFB

Specific to Block(s) CM
Description Internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

- 1922 -
Chapter 16 - Nxxxx Parameters

16.125 NUMCN100INCON

Specific to Block C300, ACE, CPM, SIM_C200, CEEACE, CEE, CEESIMC200, CN100
(s)
Description Number of CN100 input Connections - Defines number of CN100s for peer
targets.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), CN100
Related NUMCN100OUTCON
Parameters
Remarks

16.126 NUMCN100OUTCON

Specific to Block C300, ACE, CPM, SIM_C200, CEEACE, CEE, CEESIMC200, CN100
(s)
Description Number of CN100 Output Connections - Defines number of CN100s for peer
targets.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), CN100
Related NUMCN100INCON
Parameters
Remarks

- 1923 -
Chapter 16 - Nxxxx Parameters

16.127 NUMCOEFDEN

Specific to PID-PL
Block(s)
Description Number of Denominator Coefficients - The number of denominator coefficients in
the Laplace transfer function model of the process.
Data Type 32-Bit Integer
Range 1-5
Default 2
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related D[1..5], MODELUPDATED, N[1..5], NUMCOEFNUMPROCDEADTIME, PROCGAIN,
Parameters RESETMODEL, UPDATEMODEL.
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. NUMCOEFDEN should be at least one greater than NUMCOEFNUM. After
the function block is loaded, this parameter must be updated (see UPDATEMODEL.)
before any change in its value is implemented. This parameter is applicable only
when CTLEQN is set to Profit Loop PKS, and is ignored in PID control equations.

16.128 NUMCOEFNUM

Specific to PID-PL
Block(s)
Description Number of Numerator Coefficients - The number of numerator coefficients in the
Laplace transfer function model of the process.
Data Type 32-Bit Integer
Range 1-5
Default 1
Config Yes
Load
Active No
Loadable

- 1924 -
Chapter 16 - Nxxxx Parameters

Access Engineer
Lock
Residence CEE
Related D[1..5]MODELUPDATEDN
Parameters [1..5]NUMCOEFDENPROCDEADTIMEPROCGAINRESETMODELUPDATEMODEL
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. NUMCOEFDEN should be at least one greater than NUMCOEFNUM. After
the function block has been loaded, this parameter must be updated (see
UPDATEMODEL.) before any change in its value is implemented. This parameter is
applicable only when CTLEQN is set to Profit Loop PKS, and is ignored in PID
control equations.

16.129 NUMCOMPFB

Specific to CM, SCM, RCM, UCM, MR


Block(s)
Description Highest index used for function blocks: The highest index used for the component
function blocks in the Control Module (CM), Recipe Control Module (RCM), or
Sequential Control Module (SCM) plus one. A value of zero denotes LOADSTATE of
CM/SCM is NOT ready.
Data Type 16-Bit Integer
Range Greater than or equal to 0
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUM
Parameters
Remarks To determine the count of component blocks within SCM, RCM, or Master Recipe,
use NUMBLOCKS.

16.130 NUMCONDS

Specific to Transition
Block(s)
Description Number of Input Conditions
Data Type 32-Bit Integer
Range 0 to 10
Default 0
Config Load Yes

- 1925 -
Chapter 16 - Nxxxx Parameters

Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks The primary use is for sizing the internal storage of SCM FB. The user does not
have to explicitly configure NUMCONDS; This value is determined by the system
when the SCM is edited.

16.131 NUMCONN

Specific to All IOM Function Blocks except Serial Interface IOM - To be used for
Block(s) Troubleshooting only. Refer to NUMCONN[0..7] for Serial Interface IOM.
Description Number of Connections - Indicates a running count of the number of times that a
connection has been formed to the associated device.
Data Type 32-Bit Integer
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUMDISCONN, NUMSHUTDOWN.
Parameters
Remarks

16.132 NUMCONN[0..1]

Specific to Block(s) PCDI_MASTER


Description Number of successful Connects
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Device
Related Parameters
Remarks

- 1926 -
Chapter 16 - Nxxxx Parameters

16.133 NUMCONN[0..7]

Specific to Serial Interface IOM.


Block(s)
Description Number of Connections - Indicates a running count of the number of times that a
connection has been formed to the associated device.
Data Type 32-Bit Integer
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUMDISCONN[0..7], NUMSHUTDOWN.
Parameters
Remarks

16.134 NUMCPMINCON

Specific to CEEC300, ACE, SIM_C200, CEEACE, CEE, CEESIMC200, ICG, CEEUOC


Block(s)
Description Initiating to C200s/C200Es
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CEE), SIM_C200(SIM_C200,
CEESIMC200)
Related NUMCPMINCON
Parameters
Remarks Number of CPM Input Connections - Defines number of Control Processor
Modules (CPMs) for peer targets. For SIM_C200, this parameter defines number of
Simulation Control Environments (SCEs) for peer targets.

Specific to IOLIM, Secondary IOLIM, CPM


Block(s)
Description Peer Initiator Connections
Data Type 32-bit Integer
Range 0 to 1

- 1927 -
Chapter 16 - Nxxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, CPM
Related NUMCPMINCON
Parameters
Remarks This parameter displays the number of IOLIM initiated connections to CPMs. Since
only one CPM can control all output channels within a given IOLIM, the maximum
value of this parameter is one.

16.135 NUMCPMOUTCON

Specific to CEEC300, ACE, SIM_C200, CEEACE, CEE, CEESIMC200, ICG, CEEUOC


Block(s)
Description Responding to C200s/C200Es
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CEE), SIM_C200(SIM_
C200,CEESIMC200), UOC(CEEUOC)
Related NUMCPMINCON
Parameters
Remarks Number of CPM Output Connections - Defines number of peer originator Control
Processor Modules (CPMs). For SIM_C200, this parameter defines the number of
peer originator Simulation Control Environments (SCEs).

Specific to Block(s) IOLIM, Secondary IOLIM, CPM


Description Peer Responder Connections
Data Type 32-bit Integer
Range 0 to 1
Default 0
Config Load No
Active Loadable No

- 1928 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence IOLIM, C200
Related NUMCPMINCON
Parameters
Remarks This parameter displays the number of CPM initiated connections to an
IOLIM.

16.136 NUMCUSTOMRANGE

Specific to Block Recipe Step Block


(s)
Description Number of Custom Range Parameters
Data Type Integer
Range N/A
Default 0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related None
Parameters
Remarks This parameter gives the number of Custom Range Parameters defined by the
User on the block.

16.137 NUMCVSEXCEEDLIM

Specific to Block(s) ProfitCtl


Description NUM CVS EXCEED LIM
Data Type INT16
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

- 1929 -
Chapter 16 - Nxxxx Parameters

16.138 NUMCVSNEARINGLIM

Specific to Block(s) ProfitCtl


Description NUM CVS NEARING LIM
Data Type INT16
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

16.139 NUMCVSWITHINLIM

Specific to Block(s) ProfitCtl


Description NUM CVS WITHIN LIM
Data Type INT16
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

16.140 NUMCYCLE

Specific to Block(s) CEEC300, CEESIMC200, CEEUOC


Description Number of Cycles
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 42
Config Load No
Active Loadable No

- 1930 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300), SIMC200(CEESIMC200) , UOC(CEEUOC)
Related Parameters SIMENABLE
Remarks Parameter will be exposed and used only when SIMENABLE = TRUE

16.141 NUMDATA

Specific to Block CHGEXEC


(s)
Description Number of elements of DATA[ ] array scanned for change with each execution
of CHGEXEC.
Data Type 32-Bit Integer
Range 1 to 32
Default 8
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related DATA[1..32]LASTDATA[1..32]
Parameters
Remarks

16.142 NUMDINPUTS

Specific to DevCtl
Block(s)
Description Number of Digital Inputs
Data Type Integer
Range 0 to 4
Default 0
Config No
Load
Active No
Loadable

- 1931 -
Chapter 16 - Nxxxx Parameters

Access Lock Engineer


Residence CEE
Related BADPVALM.FL, BADPVALM.PR, GPVAUTO, INBETFL, LOCALMAN,
Parameters BADPVALM.SV, CMDDISALM.FL, NTOTMEMDESC, NULLPVFL, PV,
CMDDISALM.PR, CMDDISALM.SV, PVAUTO, PVFL[0..2], PVSOURCE,
CMDDISALM.TM[0..2], CMDFALALM.FL, PVSRCOPT, SEALOPT, STATETEXT
CMDFALALM.PR, CMDFALALM.SV, [0..6, UNCMDALM.FL, UNCMDALM.PR,
CMDFALALM.TM[0..2], DI[1..4], GPV, UNCMDALM.SV.
Remarks To change, the function block must be InActive.

Specific to FIRSTOUT, ANNPANEL


Block(s)
Description Number of Inputs
Data Type 8-Bit Unsigned Integer
Range 0-24
Default 8
Config Load YES
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related IN[*]
Parameters
Remarks This parameter specifies how many inputs need to be monitored. To change this
parameter, the FB must be inactive.

16.143 NUMDISCONN

Specific to All IOM Function Blocks except Serial Interface IOM - To be used for
Block(s) Troubleshooting only. Refer to NUMDISCONN[0..7] for Serial Interface IOM.
Description Number of Disconnects - Indicates a running count of the number of times that a
connection has been closed due to fault (rather than due to a commanded
operation).
Data Type 32-Bit Integer
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MODEATTRFL.OPER, NUMSHUTDOWN.
Parameters
Remarks

- 1932 -
Chapter 16 - Nxxxx Parameters

16.144 NUMDISCONN[0..1]

Specific to Block(s) PCDI_MASTER


Description Number of Disconnects
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence Device
Related Parameters
Remarks

16.145 NUMDISCONN[0..7]

Specific to Serial Interface IOM.


Block(s)
Description Number of Disconnects - Indicates a running count of the number of times that a
connection has been closed due to fault (rather than due to a commanded
operation).
Data Type 32-Bit Integer
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUMCONN[0..7]
Parameters
Remarks

16.146 NUMDOUTS

Specific to DevCtl
Block(s)
Description Number of Digital Outputs
Data Type Integer
Range 0 to 3

- 1933 -
Chapter 16 - Nxxxx Parameters

Default 0
Config No
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related BYPASS, CMDDISALM.FL, CMDDISALM.PR, OIALM.SV[0..2], OP, OPDOMAP[0..3]
Parameters CMDDISALM.SV, CMDDISALM.TM[0..2], [1..3], OPFINAL, OROPT, PI[0..2], PO
CMDFALALM.FL, CMDFALALM.PR, [1..3], PULSEWIDTH[1..3],
CMDFALALM.SV, CMDFALALM.TM[0..2], DO PVSOURCE, REDTAG, SAFEOP,
[1..3], GOP, GOPFINAL, INITMAN, SEALOPT, SI, SIALM.FL, SIALM.OPT,
INITOPAFTLD, INITOPOPT, LOCALMAN, SIALM.PR, SIALM.SV, STATETEXT
MODEATTR, OI[0..2], OIALM.FL[0..2], [0..6], UNCMDALM.FL,
OIALM.OPT[0..2], OIALM.PR[0..2]. UNCMDALM.PR, UNCMDALM.SV.
Remarks To change, the function block must be InActive.

16.147 NUMUDTTAGREAD

Specific to Blocks C300 CEE


Description UDT Tag Reads
Data Type UINT16
Range 0-65

Default 0
Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Number of UDT Tag Reads configured through this EIM.

16.148 NUMEHPMINCON

Specific to Block(s) CEEACE


Description Number of EHPM input Connections - Defines number of EHPMs for peer
targets.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No

- 1934 -
Chapter 16 - Nxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence ACE (CEEACE)
Related None
Parameters
Remarks This parameter represents aggregate value for CEEACE.

16.149 NUMEIPDEVICE

Specific to Block(s) CEEFB, CEE


Description Number of EIP devices
Data Type UINT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks It Indicates the number of EtherNet/IP devices configured.

16.150 NUMEIPDEVICE

Specific to Blocks EIM EIP Protocol Block


Description Num of EIP IO Devices
Data Type UINT32
Range 0-255

Default 0
Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related -
Parameters
Remarks Number of EIP IO Devices configured through this EIM from one or more
C300’s.

- 1935 -
Chapter 16 - Nxxxx Parameters

16.151 NUMERIC1

Specific to HRBALG_REG block


Blocks
Description NUMERIC FB Reference 1
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the NUMERIC block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

16.152 NUMERIC2

Specific to HRBALG_REG block


Blocks
Description NUMERIC FB Reference 2
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the NUMERIC block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

- 1936 -
Chapter 16 - Nxxxx Parameters

16.153 NUMEIMEIPIOS

Specific to Blocks C300 CEE


Description Number of EIM EIP IO’s
Data Type UINT16
Range 0-80

Default 0
Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Number of EIM EIP IO’s configured through this EIM.

16.154 NUMEVENTS[1..NUMPROFILES]

Specific to Block(s) RampSoak


Description Number of Events in a Profile
Data Type Integer
Range 1 to 16
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters NUMRAMPSOAK[1..NUMPROFILES]
Remarks

16.155 NUMEXCIMRAVAIL

Specific to Block CEEFB, CEEC300


(s)
Description Number of Exchange IMRs Available - Total number of exchange IMRs
available in the controller.
Data Type 32-Bit Integer
Range
Default 0
Config Load No

- 1937 -
Chapter 16 - Nxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

16.156 NUMEXCRSPAVAIL

Specific to CEEFB, CEEC300


Block(s)
Description Number of Exchange Responses Available - Total number of exchange
responses available in the controller
Data Type 32-Bit Integer
Range 0 to 40
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

16.157 NUMEXCRQUAVAIL

Specific to CEEFB, CEEC300


Block(s)
Description Number of Exchange Requests Available - Total number of exchange requests
available in the controller
Data Type 32-Bit Integer
Range 0 to 40
Default 0
Config Load No
Active No
Loadable

- 1938 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks

16.158 NUMEXCRQUAVG

Specific to Block CEEC300, CEEACE, CEESIMC200, CEEUOC


(s)
Description Exchange Request Rate
Data Type Float64
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(CEEACE), SIM_C200(CEESIMC200), UOC(CEEUOC)
Related NUMEXCRQUMAX
Parameters
Remarks Number of Exchange Requests Average – Defines the average exchange
request throughput

16.159 NUMEXCRQUMAX

Specific to Block CEEC300, CEEACE, CEESIMC200, CEEUOC


(s)
Description Max Exchange Request Rate
Data Type FLOAT 64
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(CEEACE), SIM_C200(CEESIMC200), UOC(CEEUOC)
Related NUMEXCRQUAVG
Parameters
Remarks Number of Exchange Requests Maximum - Defines the maximum exchange
request throughput.

- 1939 -
Chapter 16 - Nxxxx Parameters

16.160 NUMEXCRSPAVG

Specific to Block CEEC300, CEEACE, CEESIMC200, CEEUOC


(s)
Description Number of Exchange Response Average - Defines the average exchange
response throughput.
Data Type Float64
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(CEEACE), SIMC200(CEESIMC200) , UOC(CEEUOC)
Related NUMEXCRSPMAX
Parameters
Remarks

16.161 NUMEXCRSPMAX

Specific to Block CEEC300, CEEACE, CEESIMC200, CEEUOC


(s)
Description Maximum Exchange Response Rate
Data Type Float64
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(CEEACE), SIM_C200(CEESIMC200), UOC(CEEUOC)
Related NUMEXCRSPAVG
Parameters
Remarks Number of Exchange Response Maximum - Defines maximum exchange
response throughput.

16.162 NUMEXTBLKS

Specific to ACE, CPM, SIMC200, CEEC300, CEEUOC, CEECN100


Block(s)
Description Number of External Blocks
Data Type 32-Bit Integer
Range 0 to 4,258,848 (Bytes)

- 1940 -
Chapter 16 - Nxxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200(CPM), C300(CEEC300), ACE, SIM_C200, UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM, MAXFREEBLKSZ, NTOTMEMDESC, NUMFREEBLKS, NUMFREEDESC,
Parameters NUMREGDESC, NUMUSEDBLKS, NUMUSEDDESC, TOTALMEM, USEDMEM.
Remarks External memory blocks refer to blocks located within different CPM, ACE, or
SIMC200. For example, blocks used in peer-to-peer. Units are number of blocks -
Blocks vary in size.

16.163 NUMFAILEDGETITEM

Specific to Block OPC


(s)
Description Number of Failed to Get Item -Number of failed GetItemDefinition, since this
server started.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

16.164 NUMFIMINCON

Specific to CEEC300, ACE, CEE, CEEACE, ICG, CEEUOC


Block(s)
Description Initiating to FIMs
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable

- 1941 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300), ACE(ACE, CEEACE),UOC(CEEUOC)
Related NUMFIMOUTCON
Parameters
Remarks Number of FIM Input Connections - Defines number of Fieldbus Interface Modules
(FIMs) for peer targets. This parameter does apply for SIM_C200, since it cannot
open connections to a FIM.

16.165 NUMFIMOUTCON

Specific to CEEC300, ACE, CEEACE, CEE, ICG, CEEUOC


Block(s)
Description Responding to FIMs.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), UOC(CEEUOC)
Related NUMFIMINCON
Parameters
Remarks Number of FIM Output Connections - Defines number of originator Fieldbus
Interface Modules (FIMs). This parameter does apply for SIM_C200, since it cannot
open connections to a FIM.

16.166 NUMFLOAT64

Specific to Block EIM


Description Number of configured Float64 parameters
Data Type INT16
Range 0 to 40
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related NUMFLOAT64 of DSIN block, DSFLOAT64PARAM, MMSFLOAT64CONN,
Parameters DSFLOAT64STATE
This parameter indicates the no. of FLOAT64 parameters configured in the
Remarks Dataset.

- 1942 -
Chapter 16 - Nxxxx Parameters

16.167 NUMFREEBLKS

Specific to CEEC300, ACE, CPM, SIMC200, CEEUOC, CEECN100


Block(s)
Description Number of Free Memory Blocks
Data Type 32-Bit Integer
Range 0 to 4,258,848
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200(CPM), C300(CEEC300), ACE, SIM_C200, , UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM, MAXFREEBLKSZ, NTOTMEMDESC, NUMEXTBLKS, NUMFREEDESC,
Parameters NUMREGDESC, NUMUSEDBLKS, NUMUSEDDESC, TOTALMEM, USEDMEM.
Remarks Memory is not sectioned into blocks until it is used. It is common to have only one
free memory block. Use MAXFREEBLKSZ to the size of the largest free block. Units
are number of blocks - Blocks vary in size.

16.168 NUMFREEDESC

Specific to CEEC300, CPM, SIM_C200, ACE, , CEEUOC, CEECN100


Block(s)
Description Free Memory Descriptors
Data Type 32-Bit Integer
Range 0 to NTOTMEMDESC
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CPM), SIM_C200, ACE, UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM, MAXFREEBLKSZ, NTOTMEMDESC, NUMEXTBLKS, NUMFREEDESC,
Parameters NUMEXTBLKS, NUMUSEDBLKS, NUMUSEDDESC, TOTALMEM, USEDMEM.
Remarks Number of Free (available) Memory Descriptors. Units are number of descriptors.

- 1943 -
Chapter 16 - Nxxxx Parameters

16.169 NUMFTENODES

Specific to FTEB C300, PGM, FIM4, EHPM , EIM, UOC, TCMI, CN100
Block(s)
Description Number Fault Tolerant Ethernet (FTE) nodes - Identifies the current number of
FTE node within the FTE community.
Data Type 16-Bit Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related
Parameters
Remarks Identifies the current number of FTE node within the FTE community. (FTE
parameters, see C300 definition)

16.170 NUMFUNREF

Specific to Block(s) MAP


Description Function references number
Data Type INT32
Range 0 - 250
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Number of function references configured in the PDE of the respective Map
block.

- 1944 -
Chapter 16 - Nxxxx Parameters

16.171 NUMGPSSKEWEX

Specific to Block(s) C300 FBs


Description Number of times GPS skew threshold exceeded
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300
Related Parameters
Remarks This parameter is not actively used.

16.172 NUMHANDLERS

Specific to Block(s) SCM, RCM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

16.173 NUMHISTPARMS

Specific to SCM
Block(s)
Description Number of History Parameters
Data Type 32-Bit Integer
Range 0 to 50
Default 0
Config Load Yes
Active No
Loadable

- 1945 -
Chapter 16 - Nxxxx Parameters

Access Lock Application Developer


Residence CEE
Related HISTDESC
Parameters
Remarks The user does not explicitly configure NUMHISTPARMS. It is determined by the
system when History values are added or deleted.

16.174 NUMIEDS

Specific to Block(s) IEC61850LINK


Description Total IEDs
Data Type UINT16
Range >= 0
Default 0
Config Load N/A
Active Loadable No
Access Lock View Only
Residence CEE
Related Parameters
Remarks This is the total number of IEDs currently loaded to the IEC61850 Link.

16.175 NUMIMR

Specific to IOLIM, Secondary IOLIM, C300 IOLINK, FIM


Block(s)
Description Number of Pending Requests. Shows the number of pending Control Data
Access (CDA) server requests.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

- 1946 -
Chapter 16 - Nxxxx Parameters

16.176 NUMIN

Specific to Block(s) ALMWINDOW


Description Number of Inputs for Window groups
Data Type 8-Bit Unsigned Integer
Range 1 to 16
Default 4
Config Load YES
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters ALMIN[1..16]
Remarks Specifies the number of alarm inputs that can be connected to the block.

16.177 NUMINPUTS

Specific to Blocks HRBALG_HLPIUDI, HRBALG_HLPIUDC


Description Number of Inputs
Data Type UINT8
Range 12
Default 1
Config. Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This parameter represents the number of DI inputs.

16.178 NUMINSERT

Specific to DATAACQ, All Regulatory Control Blocks except PROSPROP, PULSECOUNT,


Block(s) PULSELENGHT, REGCALC
Description Number of insertion points
Data Type 16-Bit Integer
Range 0 to 10
Default 0
Config Load Yes
Active Loadable No

- 1947 -
Chapter 16 - Nxxxx Parameters

Access Lock Application Developer


Residence CEE
Related INSBLOCK[1..10], INSTYPE[1..10]
Parameters
Remarks

16.179 NUMINSTANCES

Specific to Block(s) SCM, RCM


Description Number of instances configured in the Alias Table.
Data Type 16-Bit Integer
Range 0 to 100
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks Defines the number of instances or columns in the Alias Table.

16.180 NUMINT32

Specific to Block EIM


Description Number of configured Integer32 parameters
Data Type INT16
Range 0 to 80
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related NUMINT32 of DSIN block, DSINT32PARAM, MMSINT32CONN,
Parameters DSINT32STATE
This parameter indicates the no. of INT32 parameters configured in the
Remarks Dataset.

- 1948 -
Chapter 16 - Nxxxx Parameters

16.181 NUMINT64

Specific to Block EIM


Description Number of configured Integer64 parameters
Data Type INT16
Range 0 to 40
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related NUMINT64 of DSIN block, DSINT64PARAM, MMSINT64CONN,
Parameters DSINT64STATE
This parameter indicates the no. of INT64 parameters configured in the
Remarks Dataset.

16.182 NUMINTERVALSININIT

Specific to Block(s) ProfitCtl


Description Num Intervals in init
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

16.183 NUMIOLMINCON

Specific to CEEC300, ACE, SIM_C200, CEEACE, CEESIMC200, ICG, , CEEUOC


Block(s)
Description Initiating to IOLIMs
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No

- 1949 -
Chapter 16 - Nxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), UOC(CEEUOC)
Related NUMIOLMOUTCN
Parameters
Remarks Number of IOLIM Input Connections - Defines number of I/O Link Interface
Modules (IOLIMs) for peer targets.

16.184 NUMIOLMOUTCON

Specific to CEEC300, ACE, SIM_C200, CEEACE, CEESIMC200, CEEUOC


Block(s)
Description Responding to IOLIMs
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), UOC(CEEUOC)
Related NUMIOLMINCON
Parameters
Remarks Number of IOLIM Output Connections - Defines the number of originator I/O
Link Interface Modules (IOLIMs).

16.185 NUMIOM

Specific to FTEB
Block(s)
Description This specifies the Number of Series A IOM's configured to this FTEB block
Data Type 8-Bit Unsigned Integer
Range 16
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly

- 1950 -
Chapter 16 - Nxxxx Parameters

Residence FTEB
Active No
Connector
Related
Parameters
Remarks This specifies the number of Series A IOM's configured to this FTEB block. Note that
only 16 IOM's can be configured per FTEB block. The user can get an indication on
how many IOM's are connected to this FTEB and how many more he can configure.

16.186 NUMIPADDR

Specific to Block CEEFB


(s)
Description Number of IP Addresses — It Indicates the number of EtherNet/IP IP Address
configured.
Data Type UINT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks

16.187 NUMLIOMINCON

Specific to Block CEEC300, ACE, SIM_C200, CEEACE, CEESIMC200, ICG


(s)

Description Initiating to LIOMs


Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200)
Related NUMIOLMINCON
Parameters

Remarks Number of LIOM Input Connections - Defines number of originator LIOMs

- 1951 -
Chapter 16 - Nxxxx Parameters

16.188 NUMLIOMOUTCON

Specific to Block CEEC300, ACE, SIM_C200, CEEACE, CEESIMC200, ICG


(s)
Description Responding to LIOMs
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200)
Related NUMLIOMINCON
Parameters
Remarks Number of LIOM Output Connections - Defines number of originator LIOMs.

16.189 NUMLOC

Specific to Block(s) Deadtime


Description Number of Locations in Delay Table.
Data Type Integer
Range 2 to 60
Default 60
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters DELAYTABLE[1..60], DELAYTIME.
Remarks

16.190 NUMMBTCPRCVBYTEAVG

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Receive Bytes/sec
Data Type Float64
Range 0 to 34E38
Default 0
Config Load No
Active Loadable No

- 1952 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters NUMMBTCPRCVBYTEMAX
Remarks Number of Modbus TCP Receive Bytes on Average per second

16.191 NUMMBTCPRCVBYTEMAX

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Maximum Receive Bytes/sec
Data Type Float64
Range 0 to 34E38
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMMBTCPRCVBYTEAVG
Remarks Maximum Number of Modbus TCP Receive Bytes per second

16.192 NUMMBTCPRCVMSGAVG

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Receive Messages/sec
Data Type Float64
Range 0 to 34E38
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMMBTCPRCVMSGMAX
Remarks Number of Modbus TCP Receive Messages on Average per second

- 1953 -
Chapter 16 - Nxxxx Parameters

16.193 NUMMBTCPRCVMSGMAX

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Max Receive Messages/sec
Data Type Float64
Range 0 to 34E38
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMMBTCPRCVMSGAVG
Remarks Maximum Number of Modbus TCP Receive Messages per second

16.194 NUMMBTCPXMITBYTEAVG

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Transmit Bytes/sec
Data Type Float64
Range 0 to 34E38
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMMBTCPXMITBYTEMAX
Remarks Number of Modbus TCP Transmit Bytes on Average per second

16.195 NUMMBTCPXMITBYTEMAX

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Max Transmit Bytes/sec
Data Type Float64
Range 0 to 34E38
Default 0
Config Load No
Active Loadable No

- 1954 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters NUMMBTCPXMITBYTEAVG
Remarks Maximum Number of Modbus TCP TranSsmit Bytes per second

16.196 NUMMBTCPXMITMSGAVG

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Transmit Messages/sec
Data Type Float64
Range 0 to 34E38
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters NUMMBTCPXMITMSGMAX
Remarks Number of Modbus TCP Transmit Messages on Average per second

16.197 NUMMBTCPXMITMSGMAX

Specific to Block(s) CEEC300,CEEACE, CEEUOC, CEECN100


Description Max Transmit Messages/second
Data Type Float64
Range 0 to 34E38
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related NUMMBTCPXMITMSGAVG
Parameters
Remarks Maximum Number of Modbus TCP Transmit Messages on Average per
second

- 1955 -
Chapter 16 - Nxxxx Parameters

16.198 NUMMVSEXCEEDLIM

Specific to Block(s) ProfitCtl


Description NUM MVS EXCEED LIM
Data Type INT16
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

16.199 NUMMVSNEARINGLIM

Specific to Block(s) ProfitCtl


Description NUM MVS NEARING LIM
Data Type INT16
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

16.200 NUMMVSWITHINLIM

Specific to Block(s) ProfitCtl


Description NUM MVS WITHIN LIM
Data Type INT16
Range NA
Default 0
Config Load No
Active Loadable No

- 1956 -
Chapter 16 - Nxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters
Remarks

16.201 NUMNTFRQUAVG

Specific to Block(s) CEEC300, CEE, CEEUOC, CEECN100


Description Notifications Rate
Data Type 64-Bit Real Number
Range Greater than or equal to 0.0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE) , UOC(CEEUOC), CN100(CEECN100)
Related Parameters NUMNTFRQUMAX, STATSRESET.
Remarks Rolling average of notification request throughput.

16.202 NUMNTFRQUMAX

Specific to Block CEEC300, CEE, CEEUOC, CEECN100


(s)
Description Max Notifications Rate
Data Type FLOAT 64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE) , UOC(CEEUOC), CN100(CEECN100)
Related NUMNTFRQUAVG, STATSRESET.
Parameters
Remarks Historical maximum of notification request throughput since last store of
STATSRESET.

- 1957 -
Chapter 16 - Nxxxx Parameters

16.203 NUMOFCHNLSGANGED

Specific to UIO - Series C DOCHANNEL


Block(s)
Description Number of Channels Ganged
Data Type ENUM
Range 2 (2) 3 (3) 4 (4)
Default 2 (2)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related ENBLGANGEDOUTPUTSASSOCGANGEDCHANNELS
Parameters
Remarks This parameter allows to specify the number of DO channels to be ganged. This
parameter is configurable only when ENBLGANGEDOUTPUTS parameter is
enabled.

NOTE
l For the 30th DO channel, this parameter can only be configured as
2 and 3.
l For the 31st DO channel, this parameter can only be configured as
2.

To successfully configure the NUMOFCHNLSGANGED parameter, ensure the


following:
l The adjacent channels must be configured as DO channel in the Channel
Configuration tab of the UIO module at the IOM level.
l The adjacent DO channel must not be configured in any Control Module.
The following modification is made to the DO channels that are ganged using this
parameter.
l Adjacent channels that are ganged are hidden in the Project view.
l Adjacent channels that are ganged are not allowed for assignment.
lAdjacent channels that are ganged are not displayed in the DO Status Data
tab at IOM level.
For more information about channel ganging, refer to Series C I/O User's Guide.

- 1958 -
Chapter 16 - Nxxxx Parameters

16.204 NUMOFEVENTRECVRS

Specific to Block(s) TCMI


Description Number Of Event Receivers
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

16.205 NUMOFINPUTS

Specific to Block(s) MVote, Min, Max, ADD, MUL


Description Number of configured inputs
Data Type Integer
Range 1 to 8
Default MVote: 3 Min, Max, ADD, MUL: 2
Active Loadable No
Config Load Yes
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

Specific to Block(s) EQ, GE, GT, LE, LT, NE


Description Number of configured inputs
Data Type Integer
Range 1 to 2
Default 2
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 1959 -
Chapter 16 - Nxxxx Parameters

16.206 NUMOFSCANTABLEEVENTS

Specific to Block(s) TCMI


Description Number Of Scan Table items
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

16.207 NUMOUTPUTS

Specific to Blocks HRBALG_HLPIUDO, HRBALG_HLPIUDC


Description Number of Outputs
Data Type UINT8
Range 12
Default 1
Config. Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This parameter represents the number of DO outputs.

16.208 NUMOWNERS

Specific to SCM, RCM, UCM, CM


Block(s)
Description Number of granted requesters
Data Type 32-Bit Integer
Range 0..MAXOWNERS
Default 0
Config Load No
Active No
Loadable

- 1960 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related MAXOWNERSAVAILFLFREEFL USEDFL
Parameters
Remarks A value of 1 defines an exclusively used resource, a value >(greater than) 1
defines a non-exclusively used resource.

16.209 NUMPARALLEL

Specific to Block(s) SCM, RCM, UCM, CM


Description Number of Parallel Threads
Data Type 32-Bit Integer
Range
Default 15
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

16.210 NUMPARAMS

Specific to Block(s) EIM


Description Number of Parameters
Data Type UINT32
Range 4294967295
Default 0
Config Load
Active Loadable No
Access Lock 4294967295
Residence SR
Related Parameters
Remarks

- 1961 -
Chapter 16 - Nxxxx Parameters

16.211 NUMPARAMS

Specific to Block(s) OPCUASRVUOC


Description Number of Parameters
Data Type UINT32
Range 0 to 4294967295
Default 10
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEESRAL
Related Parameters None
Remarks

16.212 NUMPARRSPAVG

Specific to CEEC300, CEE, CEEUOC, CEECN100


Block(s)
Description Total Responder Rate
Data Type 64-Bit Real Number
Range Greater than or equal to 0.0
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE) , UOC(CEEUOC), CN100(CEECN100)
Related NUMPARRSPMAX, STATSRESET.
Parameters
Remarks Gives a running time average of parameter response throughput being serviced by
the CEE. Units are parameter responses per second. Averaging restarts from the
current moment when parameter STATSRESET is stored. Characteristic time
constant of the average is 1 minute. Wait 2 - 3 minutes to be sure averaging has
fully settled.

- 1962 -
Chapter 16 - Nxxxx Parameters

16.213 NUMPARRSPMAX

Specific to CEEC300, CEE, CEEUOC, CEECN100


Block(s)
Description Maximum Total Responder Rate
Data Type FLOAT 64
Range Greater than or equal to 0.0
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), UOC(CEEUOC), CN100(CEECN100)
Related NUMPARRSPAVG, STATSRESET.
Parameters
Remarks Gives a historical maximum of parameter response throughput being serviced by
the CEE. Units are parameter responses per second. Search for maximum restarts
from the current moment when parameter STATSRESET is stored.

16.214 NUMPEERENV[ ]

Specific to CEEC300, CEE, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description Number of Peer Environments - Specifies the number of peer environments that
are to have specific subscription periods and store expiration times configured for
them.
Data Type 32-Bit integer
Range >= 0
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300(CEEC300), C200(CEE), ACE(CEEACE), SIM_C200(CEESIMC200), UOC
(CEEUOC), CN100(CEECN100)
Related PEERALIASENBPEERENV[ ], PEERSUBSCPER [ ], PEERSTRRESP [ ], STRRESP[ ],
Parameters SUBSCPERIOD.
Remarks Specifies the number of peer environments that are to have specific subscription
periods and store expiration times configured for them.

- 1963 -
Chapter 16 - Nxxxx Parameters

16.215 NUMPHASES

Specific to Block(s) SCM


Description Number of Phases
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

16.216 NUMPINPT

Specific to SignalSel, AuxSummer, FlowComp


Block(s)
Description Number of Process Input Connections - Represents the number of process input
connections that are configured for the block.
Data Type 32-Bit Integer
Range 0 to 10 (dependent on the function block)
Default 0
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to FLOWCOMP
Block(s)
Description Number of Process Input Connections - Represents the number of process input
connections that are configured for the block.
Data Type 32-Bit Integer
Range Greater than or equal to 2 and Less than or equal to 5
Default 0
Config Load No
Active No
Loadable

- 1964 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence C200, C300, ACE
Related
Parameters
Remarks

16.217 NUMPMDINCON

Specific to Block CEEACE, CEEC200E


(s)
Description Initiating to PMDs
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE(CEEACE), C200E(CEEC200E)
Related NUMPMDOUTCON
Parameters
Remarks Number of PMD Input Connections - This parameter defines the number of
PMDs for peer targets.

16.218 NUMPMDOUTCON

Specific to Block CEEACE, CEEC200E, CEEUOC, CEECN100


(s)
Description Responding to PMDs
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE(CEEACE), C200E(CEEC200E), UOC(CEEUOC), CN100(CEECN100)
Related NUMPMDINCON
Parameters
Remarks Number of PMD Output Connections - This parameter defines the number of
peer originator PMDs.

- 1965 -
Chapter 16 - Nxxxx Parameters

16.219 NUMPOINTSREADS

Specific to Block OPC


(s)
Description Number of Points Reads - Number of points that has been successfully read
since this server started.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

16.220 NUMPOINTSWRITES

Specific to OPC
Block(s)
Description Number of Points Writes - Number of points that has been successfully written
since this server started.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 1966 -
Chapter 16 - Nxxxx Parameters

16.221 NUMPRI

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Number of Primaries
Data Type 32-Bit Integer
Range 0 to 8 (dependent on the function block)
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

16.222 NUMPRMREF

Specific to Block(s) MAP


Description Parameter references number
Data Type INT32
Range 0 - 250
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Number of parameter references configured in the PDE of the respective
Map block.

- 1967 -
Chapter 16 - Nxxxx Parameters

16.223 NUMPRIORITYIOM

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Configured Priority IOMs. Indicates the current number of configured Priority IO
Modules on the IOLINK.
Data Type 16-Bit Unsigned Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks This parameter is found on the IOLINK configuration form Main tab and
displays.

16.224 NUMPROFILES

Specific to Block(s) RampSoak


Description Number of Profiles
Data Type Integer
Range 1 to 99
Default 1
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks

16.225 NUMPTPSKEWEX

Specific to Block C300, PGM2, FIM4, FIM8, EHPM


(s)
Description PTP Skew Limit Exceeded
Data Type UINT32
Range -

- 1968 -
Chapter 16 - Nxxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, EHPM
Related
Parameters
Remarks This parameter displays the number of times the PTP skew threshold has
been exceeded.

16.226 NUMQCSINCON

Specific to Block CEEACE, CEEC200E, CEEUOC, CEECN100


(s)
Description Initiating to QCSs
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE(CEEACE), C200E(CEEC200E), UOC(CEEUOC), CN100(CEECN100)
Related NUMQCSOUTCON
Parameters
Remarks Number of QCS Input Connections - This parameter defines the number of
QCSs for peer targets.

16.227 NUMQCSOUTCON

Specific to Block CEEACE, CEEC200E, CEEUOC, CEECN100


(s)
Description Responding to QCSs
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No

- 1969 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence ACE(CEEACE), C200E(CEEC200E), UOC(CEEUOC), CN100(CEECN100)
Related NUMQCSINCON
Parameters
Remarks Number of QCS Output Connections - This parameter defines the number of
peer originator QCSs.

16.228 NUMQUALITY

Specific to Block EIM


Description Number of configured Quality parameters
Data Type INT16
Range 0 to 80
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related NUMQUALITY of DSIN block, DSQUALPARAM, MMSQUALCONN,
Parameters DSQUALSTATE
This parameter indicates the no. of Quality parameters configured in the
Remarks Dataset.

16.229 NUMRAMPSOAK[1..NUMPROFILES]

Specific to Block(s) RampSoak


Description Number of Ramp/Soak Pairs in a Profile
Data Type Integer
Range 1 to 50
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters NUMEVENTS[1..NUMPROFILES]
Remarks

- 1970 -
Chapter 16 - Nxxxx Parameters

16.230 NUMRECPARMS

Specific to SCM
Block(s)
Description Number of Recipe Parameters
Data Type 32-Bit Integer
Range 0 to 50
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related RECPDESC[1..50], RECSCALE[1..50], RECMATCODE[1..50], RECTARGET[1..50],
Parameters RECTARGETMAX[1..50], RECTARGETMIN[1..50].
Remarks The user does not explicitly configure NUMRECPARS. it is determined by the
system when Recipe values are added or deleted

16.231 NUMREGDESC

Specific to CEEC300, CPM, SIM_C200, ACE, CEEUOC, CEECN100


Block(s)
Description Registered Memory Descriptors
Data Type 32-Bit Integer
Range 0 to NTOTMEMDESC
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CPM), ACE, SIM_C200, UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM, MAXFREEBLKSZ, NTOTMEMDESC, NUMEXTBLKS, NUMFREEBLKS,
Parameters NUMFREEDESC, NUMUSEDBLKS, NUMUSEDDESC, TOTALMEM, USEDMEM.
Remarks It is common for this number to be close to zero, since descriptors are registered
when connections are lost. Units are number of descriptors.

- 1971 -
Chapter 16 - Nxxxx Parameters

16.232 NUMREQUESTR

Specific to Block(s) SCM


Description Number of Internal requesters used
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

16.233 NUMRUNRCMS

Specific to CEE
Block(s)
Description Number of Running RCMs
Data Type INT32
Range INT32
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MAXRCMSUSED
Parameters
Remarks The value of this parameter may not be the same as that of CURRNUMACT since
some of the running RCMs are not associated with the Activity.

NOTE RCMs in the starting state are not counted.

- 1972 -
Chapter 16 - Nxxxx Parameters

16.234 NUMSCADAINCON

Specific to CEEACE, CEEC200E, CEEUOC, CEECN100


Block(s)
Description Initiating to SCADAs
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE(CEEACE), C200E(CEEC200E), UOC(CEEUOC), CN100(CEECN100)
Related
Parameters
Remarks Number of SCADA Input Connections - This parameter defines the number of
SCADAs for peer targets.

16.235 NUMSCATAGREAD

Specific to Blocks C300 CEE


Description Scalar Tag Reads
Data Type UINT16
Range 0-400

Default 0
Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks Number of Scalar Tag Reads configured through this EIM.

16.236 NUMSCEINCON

Specific to CEEC300, ACE, CPM, CEEACE, CEE, CEESIMC200, ICG, CEEUOC, CEECN100
Block(s)
Description Initiating to SIM-C200E/C200s
Data Type 32-Bit integer
Range Greater than or equal to 0
Default 0

- 1973 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), UOC(CEEUOC), CN100(CEECN100)
Related NUMSCEOUTCON
Parameters
Remarks Number of SIM_C200 Input Connections - Defines number of Simulation Control
Environments (SCEs) for peer targets.

16.237 NUMSCEOUTCON

Specific to CEEC300, ACE, CPM, CEEACE, CEE, CEESIMC200, CEECN100


Block(s)
Description Responding to SIM-C200E/C200s
Data Type 32-Bit integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), CN100(CEECN100)
Related NUMSCEINCON
Parameters
Remarks Number of SIM_C200 Output Connections - Defines number of originator
Simulation Control Environments (SCEs).

16.238 NUMSCFIMINCON

Specific to Block CEEC300, ACE, CPM, SIM_C200, CEEACE, CEE, CEESIMC200


(s)
Description Number of Series C FIM input Connections - Defines number of Series C FIM
for peer targets.
Data Type 32-Bit integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No

- 1974 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200)
Related NUMSCFIMOUTCON
Parameters
Remarks

16.239 NUMSCFIMOUTCON

Specific to Block CEEC300, ACE, CPM, SIM_C200, CEEACE, CEE, CEESIMC200


(s)
Description Number of Series C FIM Output Connections - Defines number of originator
Series C FIM.
Data Type 32-Bit integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200)
Related NUMSCFIMINCON
Parameters
Remarks

16.240 NUMSEC

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Number of Secondaries
Data Type 32-Bit Integer
Range 0 to 8 (dependent on the function block)
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 1975 -
Chapter 16 - Nxxxx Parameters

16.241 NUMSEGS

Specific to Genlin
Block(s)
Description Number of Segments - Total number of segments defined to the General
Linearization function block.
Data Type Integer
Range 1 to 12
Default 1
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related IN, OUT.
Parameters
Remarks

16.242 NUMSESSIONS
Delete this text and replace it with your own content.

16.243 NUMSHUTDOWN

Specific to All IOM Function Blocks except Serial Interface IOM - To be used for
Block(s) Troubleshooting only. Refer to NUMSHUTDOWN[0..7] for Serial Interface IOM.
Description Number of Shutdowns - Indicates a running count of the number of times that a
connection to the associated device has been closed due to either a fault or
commanded shutdown.
Data Type 32-Bit Integer
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUMCONN
Parameters
Remarks

- 1976 -
Chapter 16 - Nxxxx Parameters

16.244 NUMSHUTDOWN[0..7]

Specific to Serial Interface IOM.


Block(s)
Description Number of Shutdowns - Indicates a running count of the number of times that a
connection to the associated device has been closed due to either a fault or
commanded shutdown.
Data Type 32-Bit Integer
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUMCONN[0..7]
Parameters
Remarks

16.245 NUMSIGS

Specific to Block(s) Most Function Blocks


Description Electronic Signature Type
Data Type Enumeration
Range None (0) Single (1) Double (2)
Default None (0)
Config Load Yes
Active Loadable No
Access Lock Engineer / Application Developer
Residence SR
Related CTRLCONFIRM
Parameters
Remarks Number of Signatures - Lets you select number of electronic signatures to
be used.

Specific to Block(s) UOC


Description Electronic Signature Type
Data Type ENUM
Range N/A
Default NONE
Config Load Yes
Active Loadable

- 1977 -
Chapter 16 - Nxxxx Parameters

Access Lock AppDevOnly


Residence SCAN
Related Parameters
Remarks

16.246 NUMSIOLMINCN

Specific to CEEC300, ACE, CPM, SIM_C200, CEEACE, CEE, CEESIMC200, ICG


Block(s)
Description Number of SIM IOLIM Input Connections - Defines number of Simulation I/O Link
Interface Modules (IOLIMs) for peer targets.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200)
Related NUMSIOLMOUCN
Parameters
Remarks

16.247 NUMSIOLMOUCN

Specific to ACE, CPM, SIM_C200, CEEACE, CEE, CEESIMC200


Block(s)
Description Number of SIMIOLIM Output Connections - Defines the number of originator I/O
Link Interface Modules (IOLIMs).
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200)
Related NUMSIOLMINCN
Parameters
Remarks

- 1978 -
Chapter 16 - Nxxxx Parameters

16.248 NUMSIOVRD

Specific to DevCtl
Block(s)
Description Number of Safety Interlock Trips - The accumulated number of Safety Override
Interlocks since the last reset of maintenance Statistics.
Data Type 64-Bit Real Number
Range 0.0 to Maximum Real Number
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MAINTOPT, RESETFL, SI.
Parameters
Remarks Default to 0.0 if MAINTOPT is set to Off. Reset to 0.0 whenever RESETFL is changed
from Off to On.

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Number of Safety Interlock Trips - The accumulated number of Safety Override
Interlocks since the last reset of maintenance Statistics.
Data Type Float64
Range 0.0 to Maximum Real Number
Default 0
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related TRKSIOVRD, RESETFL, SI.
Parameters
Remarks Default to 0.0 if TrkNumSIOvrd is set to OFF. Reset to 0.0 whenever RESETFL is
changed from OFF to ON.

16.249 NUMSLOTS

Specific to RM
Block(s)
Description Number of slots in the host chassis
Data Type 32-Bit Unsigned Integer
Range 1 to 20

- 1979 -
Chapter 16 - Nxxxx Parameters

Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

16.250 NUMSMINCON

Specific to Block CEEACE, CEEC200E


(s)
Description Initiating to SMs
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE(CEEACE), C200E(CEEC200E)
Related NUMSMOUTCON
Parameters
Remarks Number of SM Input Connections - This parameter defines the number of SMs
for peer targets.

16.251 NUMSMOUTCON

Specific to Block CEEACE, CEEC200E, CEEUOC, CEECN100


(s)
Description Responding to SMs
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No

- 1980 -
Chapter 16 - Nxxxx Parameters

Access Lock ViewOnly


Residence ACE(CEEACE), C200E(CEEC200E), CN100(CEECN100)
Related NUMSMINCON
Parameters
Remarks Number of SM Output Connections - This parameter defines the number of SMs
for peer targets

16.252 NUMSNTPSKEWEX

Specific to Block(s) C300, PGM, FIM4, EHPM


Description Number of times SNTP skew threshold is exceeded
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related Parameters
Remarks

16.253 NUMSRCCONN[1..8]

Specific to Block AUXCALC, ENHAUXCALC, ENHREGCALC, REGCALC


(s)
Description Number of Source Connections - Defines the number of references present in
each expression.
Data Type 32-Bit Integer
Range 0 to 6
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks

- 1981 -
Chapter 16 - Nxxxx Parameters

16.254 NUMSTATES

Specific to DevCtl
Block(s)
Description Number of Settable States
Data Type Integer
Range 2 to 3
Default 2
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related CMDDISALM.FL, CMDDISALM.PR, MAXTIME, MAXTRANS[0..2],
Parameters CMDDISALM.SV, CMDDISALM.TM[0..2], MOMSTATE, NUMTRANS[0..2],
CMDFALALM.FL, CMDFALALM.PR, OP, OPDOMAP[0..3][1..3],
CMDFALALM.SV, CMDFALALM.TM[0..2], OPFINAL, OPREQ, PI[0..2], PV,
DIMODEDIPVMAP[0..15], GOP, GOPFINAL, GPV, PVAUTO, PVFL[0..2], SAFEOP,
GPVAUTO, LASTOPMNAME, LASTOPREQ, STATETIME[0..2].
Remarks The function block must be inactive to change this parameter. Any member of
DIPVMAP[] that may have been assigned to state S2 will be changed to Null, upon
NUMSTATES being set to = 2.

Specific to Block(s) EIM


Description No of states
Data Type INT32
Range ±2147483647
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence ERDBONLY
Related Parameters
Remarks

16.255 NUMSTEPS

Specific to Block(s) SCM, RCM


Description This is an internal parameter for system use only.
Data Type
Range
Default

- 1982 -
Chapter 16 - Nxxxx Parameters

Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

16.256 NUMSYNCS

Specific to Block(s) SCM, RCM


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

16.257 NUMTBR

Specific to Block(s) CM
Description Internal parameter for system use only
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

- 1983 -
Chapter 16 - Nxxxx Parameters

16.258 NUMTHREADS

Specific to Block(s) SCM, RCM


Description SCM Current Number of Active Threads
Data Type 32-Bit Integer
Range 0 to 10
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Provides the current number of active threads in the execution of the
SCM/RCM.

16.259 NUMTRANS

Specific to SCM. RCM


Block(s)
Description Sequential Control Module (SCM) Total Number of Transitions
Data Type 32-Bit Integer
Range N/A
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The primary use is for sizing the internal storage of the SCM function block. The
user does not have to explicitly configure NUMTRANS. This value is determined by
the system when the SCM is loaded.

- 1984 -
Chapter 16 - Nxxxx Parameters

16.260 NUMTRANS [0,1]

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Total Number of State Transitions - The accumulated number of transitions to the
reference state since the last reset of Maintenance Statistics.
Data Type Float64
Range 0.0 to Maximum Real Number
Default 0
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related NUMALLTRANS, TRKNUMTRANS, PV, RESETFL.
Parameters
Remarks

16.261 NUMTRANS[0..2]

Specific to DevCtl
Block(s)
Description Total Number of State Transitions - The accumulated number of transitions to the
reference state since the last reset of Maintenance Statistics.
Data Type 64-Bit Real Number
Range 0.0 to Maximum Real Number
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related GPV, MAINTOPT, NUMSTATES, PV, RESETFL.
Parameters
Remarks Defaulted to 0.0 if MAINTOPT is not set On. Reset to 0.0 whenever RESETFL is set
from Off to On. NUMTRANS[2] is illegal if NUMSTATES = 2.

- 1985 -
Chapter 16 - Nxxxx Parameters

16.262 NUMUIDS

Specific to Block(s) PCDI_MASTER


Description Number of UIDs
Data Type 16-Bit Unsigned Integer
Range
Default 16
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

16.263 NUMUINT32

Specific to Block EIM


Description Number of configured UInteger32 parameters
Data Type INT16
Range 0 to 80
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related NUMUINT32 of DSIN block, DSUINT32PARAM, MMSUINT32CONN,
Parameters DSUINT32STATE
This parameter indicates the no. of UINT32 parameters configured in the
Remarks Dataset.

16.264 NUMUNITS

Specific to Block(s) MR
Description Number of Units
Data Type INT16
Range 1 - 50
Default 1
Config Load Yes
Active Loadable No

- 1986 -
Chapter 16 - Nxxxx Parameters

Access Lock APPDEVONLY


Residence CEESR
Related Parameters ACQONBEHALF, NUMUNITS, UNITNAME, UNITACQ
Remarks This parameter represents the number of Units configured for an MR.

16.265 NUMUOCINCON

Specific to Block CEEACE, CEEC200E, CEEUOC, CEECN100


(s)
Description Initiating to UOCs
Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE(CEEACE), C200E(CEEC200E), UOC(CEEUOC), CN100(CEECN100)
Related NUMUOCOUTCON
Parameters
Remarks Number of UOC Input Connections - This parameter defines the number of
UOCs for peer targets.

16.266 NUMUOCOUTCON

Specific to Block CEEACE, CEEC200E, CEECN100


(s)

Description Responding to UOCs


Data Type 32-bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE(CEEACE), C200E(CEEC200E), CN100(CEECN100)
Related NUMUOCINCON
Parameters

Remarks Number of UOC Output Connections - This parameter defines the number of UOCs
for peer targets.

- 1987 -
Chapter 16 - Nxxxx Parameters

16.267 NUMUSEDBLKS

Specific to CEEC300, CPM, SIM_C200, ACE, CEEUOC, CEECN100


Block(s)
Description Number of User Memory Blocks
Data Type 32-Bit Integer
Range 0 to 4,258, 848
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CPM), ACE, SIM_C200, , UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM, MAXFREEBLKSZ, NTOTMEMDESC,, NUMEXTBLKS, NUMFREEBLKS,
Parameters NUMFREEDESC, NUMREGDESC, NUMUSEDDESC, TOTALMEM, USEDMEM.
Remarks Units are number of blocks - Blocks vary in size.

16.268 NUMUSEDDESC

Specific to CEEC300, CPM, SIM_C200, ACE, CEEUOC, CN100(CEECN100)


Block(s)
Description Number of Used Memory Descriptors
Data Type 32-Bit Integer
Range 0 to NTOTMEMDESC
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CPM), ACE, SIM_C200, UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM, MAXFREEBLKSZ, NTOTMEMDESC, NUMEXTBLKS, NUMFREEBLKS,
Parameters NUMFREEDESC, NUMREGDESC, NUMUSEDBLKS, TOTALMEM, USEDMEM.
Remarks Units are number of descriptors – Equal to NTOTMEMDESC – NUMFREEDESC

16.269 NUMWAITING

Specific to Block(s) SCM, RCM, UCM, CM


Description Number of Waiting requesters
Data Type 32-Bit Integer
Range 0..QUEUESIZE

- 1988 -
Chapter 16 - Nxxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters QUEUESIZE, WAITINGFL
Remarks

16.270 NUMWSGINCON

Specific to CEEC300, ACE, SIM_C200, CEEACE, CEESIMC200, ICG, CEEUOC, CEECN100


Block(s)
Description Initiating to WDMs
Data Type 32-Bit Integer
Range >=0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), UOC(CEEUOC), CN100(CEECN100)
Related FREEMEM,
Parameters
MAXFREEBLKSZ,
NTOTMEMDESC,

NUMEXTBLKS,
NUMFREEBLKS,
NUMFREEDESC,
NUMREGDESC,
NUMUSEDBLKS,
TOTALMEM,
USEDMEM.
Remarks Number of WDM Input Connections - Defines number of originator WDMs.

- 1989 -
Chapter 16 - Nxxxx Parameters

16.271 NUMWSGOUTCON

Specific to CEEC300, ACE, SIM_C200, CEEACE, CEESIMC200, ICG, CEEUOC, CEECN100


Block(s)
Description Responding to WDMs
Data Type >=0
Range 0 to NTOTMEMDESC
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), ACE(ACE, CEEACE), C200(CPM, CEE), SIM_C200(SIM_C200,
CEESIMC200), UOC(CEEUOC), CN100(CEECN100)
Related NUMWSGINCON
Parameters
Remarks Number of WDM Output Connections - Defines number of originator WDMs

16.272 NUMXFERINST

Specific to Block(s) CM
Description Internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

16.273 NUMXINPT

Specific to RegSummer
Block(s)
Description Number of Process Input Connections - Represents the number of process input
connections that are configured for the RegSummer block.
Data Type 32-Bit Integer
Range 1-4
Default N/A

- 1990 -
Chapter 16 - Nxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), ACE(CEEACE).
Related
Parameters
Remarks

16.274 NVSCOMINPROG

Specific to Block IOLIM, Secondary IOLIM, C300 IOLINK


(s)
Description Non-Volatile Storage Compaction in Progress.
Data Type Boolean
Range Off (0): NVS compaction is not in progress.
On (1): NVS compaction is in progress.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks No configuration loads or deletes can be performed while NVS compation is in
progress.

16.275 NVSFREEAVG

Specific to Block(s) EIM, TCMI, UOC, CN100, C300


Description NVS Free (%)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks NVS free running average, in percent.

- 1991 -
Chapter 16 - Nxxxx Parameters

16.276 NVSFREECRIT

Specific to Block EIM, TCMI, UOC, CN100, C300


Description Free non-volatile storage is below the fixed critical limit
Data Type BOOLEAN
Range On/Off
Default Off
Config Load No
Active Loadable No
Access Lock
Residence CEE
Related Parameters >NVSFREECRITLM
Remarks Soft Failure

16.277 NVSFREECRITLM

Specific to EIM, TCMI, UOC, CN100, C300


Block(s)
Description NVS Free Critical Alarm (%)
Data Type FLOAT64
Range ±1.7E+308
Default 10
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks NVS free critical alarm set point. An "NVS free critical" alarm is generated if the NVS
free statistic drops below this value. This set point is not user configurable.

16.278 NVSFREELOWLM

Specific to EIM, TCMI, UOC, CN100, C300


Block(s)
Description NVS Free Low Alarm (%)
Data Type FLOAT64
Range ±1.7E+308
Default 20

- 1992 -
Chapter 16 - Nxxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks NVS free low alarm set point. An "NVS free low" alarm is generated if the NVS free
statistic drops below this value.

16.279 NVSFREEMIN

Specific to Block(s) EIM, TCMI, UOC, CN100, C300


Description NVS Free Minimum (%)
Data Type FLOAT64
Range ±1.7E+308
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Low water mark for NVS free running average, in percent.

16.280 NVSMEDIAERR

Specific to UOC, CN100, C300


Block(s)
Description NVS/Retention Restart Media Error
Data Type BOOLEAN
Range OFF, ON
Default OFF
Config No
Load
Active No
Loadable

- 1993 -
Chapter 16 - Nxxxx Parameters

Access View Only


Lock
Residence CEE
Related None
Parameters
Remarks The UOC Retention Restart function requires an SD card for the saving and restoring
of retention data. When a RETENTIONTRIG Block is loaded to the UOC and no valid
SD card is detected, this parameter is ON and the “NVS/Retention Restart Media
Error” soft failure is reported by the non-redundant or primary UOC. Once a valid SD
card is inserted in the UOC or the RETENTIONTRIG Block is deleted from the UOC,
this parameter is OFF and the soft failure returns to normal. The virtual UOC does not
generate this soft failure.

16.281 NVSUSED

Specific to IOLIM, Secondary IOLIM, C300 IOLINK, FIM


Block(s)
Description Non-Volatile Storage Usage. Shows the percentage of non-volatile storage
memory used in the associated module.
Data Type 32-Bit Real Number
Range 0.0 to 100.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

- 1994 -
CHAPTER

17 OXXXX PARAMETERS

17.1 OFFCAP[1..10] 2003


17.2 OFFNRMALM.FL 2003
17.3 OFFNRMALM.OPT 2004
17.4 OFFNRMALM.PR 2005
17.5 OFFNRMALM.SV 2006
17.6 OFFNRMALM.TM 2006
17.7 OFFNRMALM.TMO 2007

17.8 OFFNRMFL 2007


17.9 OFFPULSE 2008
17.10 OHMOFFSET 2008
17.11 OHMOFFSET[0..numChans-1] 2009
17.12 OI[0..2] 2009
17.13 OIACTED 2010
17.14 OIALM.FL[0..1] 2010
17.15 OIALM.FL[0..2] 2011
17.16 OIALM.OPT[0..1] 2011
17.17 OIALM.OPT[0..2] 2012
17.18 OIALM.PR[0..1] 2012
17.19 OIALM.PR[0..2] 2012
17.20 OIALM.SV[0..1] 2013
17.21 OIALM.SV[0..2] 2013
17.22 OIOCS 2014
17.23 OIOPS 2014
17.24 OKINCH1AV 2015
17.25 OKINCH2AV 2015
17.26 OKOUTAV 2016
17.27 OLDAV 2016
17.28 ONCAP[1..10] 2016
17.29 ONPROCESS 2017
17.30 ONPULSE 2017
17.31 OP 2018
17.32 OP 2021

- 1995 -
Chapter 17 - Oxxxx Parameters

17.33 OP[0..7] 2022


17.34 OP[0..numChans-1] 2022
17.35 OP[1..8] 2022
17.36 OP[1..NUMCHAN] 2023
17.37 OP[1..16]. INSTRUCTDISABLE 2023
17.38 OP[1..16].ACQSTATE 2024
17.39 OP[1..16].BYPREQ 2024
17.40 OP[1..16].CMDREQSTS 2025
17.41 OP[1..16].CONFIGASSOCPARAM 2025
17.42 OP[1..16].CONFIGCODE 2026
17.43 OP[1..16].CONFIGDESC 2026
17.44 OP[1..16].CONFIGSTS 2027
17.45 OP[1..16].CURRDESCREF 2027
17.46 OP[1..16].CURREUDESCREF 2028

17.47 OP[1..16].CURRVALREF 2028


17.48 OP[1..16].CURRVALTREND 2029
17.49 OP[1..16].DELAYTIME 2029
17.50 OP[1..16].DELAYTIMEREM 2030
17.51 OP[1..16].DESC 2030
17.52 OP[ ].DSTN 2031
17.53 OP[1..16].ENTRYDESCREF 2031
17.54 OP[1..16].ENTRYEUDESCREF 2031
17.55 OP[1..16].ENTRYLABEL 2032
17.56 OP[1..16].ENTRYMAXREF 2032
17.57 OP[1..16].ENTRYMINREF 2033
17.58 OP[1..16].ENTRYVALREF 2033
17.59 OP[1..16].EQUIPNAME 2034
17.60 OP[1..16].EXECCODE 2034
17.61 OP[1..16].EXECDESC 2035
17.62 OP[1..16].EXECSTS 2035
17.63 OP[1..16].EXPRPCODE 2036
17.64 OP[1..16].FILTERABLE 2036
17.65 OP[1..16].INSTRUCTCNFM 2036
17.66 OP[1..16].INSTRUCTCOMP 2037
17.67 OP[1..16].INSTRUCTION 2037
17.68 OP[1..16].INSTRUCTPEND 2038
17.69 OP[1..16].INSTRUCTTYPE 2038
17.70 OP[1..16].MONTASKREF 2039
17.71 OP[1..16].NOTE 2039

- 1996 -
Chapter 17 - Oxxxx Parameters

17.72 OP[1..16].OWNERSSTS 2040


17.73 OP[1..16].OWNFL 2040
17.74 OP[1..16].RELFL 2041
17.75 OP[1..16].REQFL 2041
17.76 OP[1..16].ROLE 2042
17.77 OP[1..16].SRCEXPR 2042
17.78 OP[1..16].STATE 2043
17.79 OP[1..16].TARGETCHANGE 2043
17.80 OP[1..16].TARGETDESCREF 2044
17.81 OP[1..16].TARGETEUDESCREF 2044
17.82 OP[1..16].TARGETLABEL 2045
17.83 OP[1..16].TARGETMAXREF 2045
17.84 OP[1..16].TARGETMINREF 2045
17.85 OP[1..16].TARGETVALREF 2046

17.86 OP[1..16].TYPE 2046


17.87 OP[1..16].WARNING 2048
17.88 OP_AO_S 2048
17.89 OP_DO_S 2049
17.90 OP2PVPOLYMODEL 2050
17.91 OPBIAS 2050
17.92 OPBIAS[1..8] 2051
17.93 OPBIAS.FIX 2051
17.94 OPBIAS[1..8].FIX 2052
17.95 OPBIAS.FLOAT 2052
17.96 OPBIAS[1..8].FLOAT 2053
17.97 OPBIAS.RATE 2053
17.98 OPBIAS[1..8].RATE 2054
17.99 OPCHAR 2054
17.100 OPCMD[0..2] 2055
17.101 OPCNAME 2056
17.102 OPCTYPE 2056
17.103 OPCUASRVCONFIG 2056
17.104 OPDOMAP[0..3][1..3] 2057
17.105 OPENFEEDBKTIME 2057
17.106 OPEM 2058
17.107 OPENIBV 2058
17.108 OPENLOOPRESP 2059
17.109 OPENMAIN 2059
17.110 OPENPULSEWIDTH 2060

- 1997 -
Chapter 17 - Oxxxx Parameters

17.111 OPENSEQ 2060


17.112 OPENSEQALM.FL 2060
17.113 OPENSEQALM.PR 2061
17.114 OPENSEQALM.SV 2061
17.115 OPENWIRE [0..Number of status in assembly] 2062
17.116 OPERTAG 2062
17.117 OPERTAGDESC 2063
17.118 OPEU 2063
17.119 OPEU 2064
17.120 OPEU[1..8] 2064
17.121 OPEUMOVE 2065
17.122 OPEUX 2065
17.123 OPEUX[1..8] 2066
17.124 OPEXHIFL 2066

17.125 OPEXHIFL[1..8] 2067


17.126 OPEXHILM 2067
17.127 OPEXLOFL 2068
17.128 OPEXLOFL[1..8] 2068
17.129 OPEXLOLM 2069
17.130 OPFINAL 2069
17.131 OPFINAL_AO_S 2071
17.132 OPFINAL[0..numChans-1] 2072
17.133 OPFINAL[0..numChans-1] 2072
17.134 OPFINALHIRANGE [0..numChans-1] 2073
17.135 OPFINALLORANGE [0..numChans-1] 2073
17.136 OPFL[0..numChans-1] 2074
17.137 OPHIACTIVE 2074
17.138 OPHIALM.DB 2075
17.139 OPHIALM.DBU 2075
17.140 OPHIALM.FL 2076
17.141 OPHIALM.PR 2076
17.142 OPHIALM.SV 2077
17.143 OPHIALM.TM 2077
17.144 OPHIALM.TMO 2078
17.145 OPHIALM.TP 2078
17.146 OPHIFL 2079
17.147 OPHIFL[1..8] 2079
17.148 OPHIGH.FL 2080
17.149 OPHILM 2080

- 1998 -
Chapter 17 - Oxxxx Parameters

17.150 OPHILMOPT 2081


17.151 OPHIOPTOFFSET 2081
17.152 OPIN 2082
17.153 OPIN0 2082
17.154 OPIN1 2083
17.155 OPIN2 2083
17.156 OPIN3 2084
17.157 OPIN4 2084
17.158 OPIN5 2085
17.159 OPINCONNHNDL[1..16][1..6] 2085
17.160 OPINCONNNAV[1..16][1..6] 2085
17.161 OPINCONNPRM[1..16][1..6] 2086
17.162 OPINCONNSTRVAL[1..16][1..6] 2086
17.163 OPINCONNVAL[1..16][1..6] 2087

17.164 OPINITVAL 2087


17.165 OPINITVAL[0..numChans-1] 2088
17.166 OPLOACTIVE 2088
17.167 OPLOALM.DB 2089
17.168 OPLOALM.DBU 2089
17.169 OPLOALM.FL 2090
17.170 OPLOALM.PR 2090
17.171 OPLOALM.SV 2091
17.172 OPLOALM.TM 2091
17.173 OPLOALM.TMO 2092
17.174 OPLOALM.TP 2092
17.175 OPLOFL 2093
17.176 OPLOFL[1..8] 2093
17.177 OPLOLM 2094
17.178 OPLOLMOPT 2094
17.179 OPLOOPTOFFSET 2095
17.180 OPLOW.FL 2095
17.181 OPMINCHG 2096
17.182 OPNUMSRCCONN[1..16] 2096
17.183 OPOUT0 2097
17.184 OPOUT1 2097
17.185 OPOUT2 2098
17.186 OPOUT3 2098
17.187 OPOUT4 2099
17.188 OPOUT5 2099

- 1999 -
Chapter 17 - Oxxxx Parameters

17.189 OPOUT 2100


17.190 OPPCODESIZE[1..16] 2100
17.191 OPREQ 2101
17.192 OPROCLM 2102
17.193 OPROCNEGFL 2102
17.194 OPROCNEGFL[1..8] 2103
17.195 OPROCPOSFL 2103
17.196 OPROCPOSFL[1..8] 2104
17.197 OPSECDATA 2104
17.198 OPSECDATA[1..8] 2105
17.199 OPSECDATA.ARWSTS 2105
17.200 OPSECDATA.EUHI 2105
17.201 OPSECDATA.EULO 2106
17.202 OPSECDATA.INITREQ 2106

17.203 OPSECDATA.INITVAL 2107


17.204 OPSECDATA.ONESHOT 2107
17.205 OPSECDATA.ORFBVA 2108
17.206 OPSECDATA.OROFFS 2108
17.207 OPSOURCE 2108
17.208 OPSRC[1..16][1..6] 2109
17.209 OPSTOREHNDL[1..16] 2109
17.210 OPSTORENAV[1..16] 2110
17.211 OPSTOREPRM[1..16] 2110
17.212 OPSTORESTRVAL[1..16] 2110
17.213 OPSTOREVAL[1..16] 2111
17.214 OPTACCELTOL 2111
17.215 OPTDIR 2112
17.216 INPTDIR_AO_C 2113
17.217 OPTFIELDS 2114
17.218 OPTFLD_SET 2115
17.219 OPTMODE 2116
17.220 OPTOAOCONN 2116
17.221 OPTOL 2117
17.222 OTRPI 2117
17.223 OPTSPEED 2118
17.224 OPTSPEEDFACTOR 2119
17.225 OPTYPE 2119
17.226 OPTYPEENUMMASK 2120
17.227 OPX 2120

- 2000 -
Chapter 17 - Oxxxx Parameters

17.228 OPX[1..8] 2121


17.229 ORBYPASSFL[1..4] 2121
17.230 ORBYPPERM 2121
17.231 ORDER 2122
17.232 ORDERINCEE 2122
17.233 ORDERINCM 2123
17.234 ORDERINLINK 2124
17.235 ORED 2125
17.236 OREDOUT 2125
17.237 ORFBSTSSRC 2125
17.238 ORFBVALSRC 2126
17.239 ORIAPPCONNID[1..48] 2126
17.240 ORICONNSTATE[1..48] 2127
17.241 ORIGINALGAIN 2127

17.242 ORIPATH[1..48] 2127


17.243 ORITCLASS[1..48] 2128
17.244 ORMUXED[1..48] 2128
17.245 OROFFSET 2129
17.246 OROPT 2129
17.247 ORPHANRESPCNT 2130
17.248 OSVER 2130
17.249 OTCONNPRIORITY 2131
17.250 OTCONNTYPE 2131
17.251 OTDENBL 2132
17.252 OTRPI 2132
17.253 OUT 2133
17.254 OUT[0..12] 2135
17.255 OUT[1..8] 2135
17.256 OUT.Boolean 2135
17.257 OUT.ENUM 2136
17.258 OUT.FLOAT32 2136
17.259 OUTFLOAT64 2137
17.260 OUT.INT8 2137
17.261 OUT.INT16 2137
17.262 OUTINT32 2138
17.263 OUT.SDENUM 2138
17.264 OUT.UINT 8 2139
17.265 OUT.UINT16 2139
17.266 OUT.UINT32 2139

- 2001 -
Chapter 17 - Oxxxx Parameters

17.267 OUT1 2140


17.268 OUT2 2140
17.269 OUTCAP 2141
17.270 OUTDIR 2141
17.271 OUTFLOAT64 2141
17.272 OUTHORN1 2142
17.273 OUTHORN2 2142
17.274 OUTIND 2143
17.275 OUTINT32 2143
17.276 OUTPIN 2144
17.277 OUTPUTTYPE 2144
17.278 OUTSENSE 2145
17.279 OUTSENSE[6..7] 2145
17.280 OUTTYPE 2146

17.281 OUTSTS[1..8] 2146


17.282 OVERALLRESPONSETIME 2147
17.283 OVERCAPACITY[1..24] 2147
17.284 OVERCAPACITY[1..200] 2147
17.285 OVRDSEL 2148
17.286 OVRDSEL2 2148
17.287 OVERRANGE 2149
17.288 OVERRANGE[0..numChans-1] 2149
17.289 OVERRANGE [0..NUMCHANNELS-1] 2150
17.290 OVERRUNSCUR 2150
17.291 OVERRUNSPREV 2151
17.292 OVERTEMP 2151
17.293 OVERTEMPTHLD 2152
17.294 OVERTOLRNCE[1..200] 2152
17.295 OVERUNDERVOLTAGE 2153
17.296 OVRRUNCURHR[1..40] 2153
17.297 OVRRUNPREVHR[1..40] 2154
17.298 OVRSIGNA 2154
17.299 OWDENBL 2155
17.300 OWDENBL [0..NUMCHANNELS - 1] 2156
17.301 OWDENBL_AI_C 2157
17.302 OWDENBL_DI_C 2157
17.303 OWDENBL_DO_C 2158
17.304 OWNCMNDSTS[1..5] 2158
17.305 OWNCMPPHASESTS[1..5] 2159

- 2002 -
Chapter 17 - Oxxxx Parameters

17.306 OWNCOMMAND[1..5] 2160


17.307 OWNERID[1..MAXOWNERS] 2161
17.308 OWNERIDN[1..5] 2161
17.309 OWNERIDN[1..MAXOWNERS] 2162
17.310 OWNERLOOKUP 2162
17.311 OWNERS 2163
17.312 OWNINGENIM 2163
17.313 OWNMODE[1..5] 2164
17.314 OWNMODEATTR[1..5] 2164
17.315 OWNSTATE[1..5] 2165

17.1 OFFCAP[1..10]

Specific to Block(s) GRPCAPRBK


Description OFF state Capability Value of equipment
Data Type IEEEFloat64
Range
Default 0
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This represents OFF state Capability Value of corresponding Equipment.

17.2 OFFNRMALM.FL

Specific to Block(s) Flag, Push.


Description Off Normal Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No

- 2003 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related NORMAL, OFFNRMALM.PR, OFFNRMALM.SV, PV,
Parameters
Remarks When On, it indicates that the Flag function block is not currently in the
normal state.

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Off Normal Alarm Flag - Indicates the ‘OFF-Normal’condition. The Device is ‘OFF-
Normal’wherever the Process Variable (PV) does not equal OPREQ.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related BYPASS, CMDDISALM.FL, CMDDISALM.PR, CMDDISALM.SV, CMDDISALM.TM
Parameters [0..2], GOPREQ, GPV, HIALM, OPREQ, PV.
Remarks InActive when GOPREQ is Null.

Specific to Block(s) CONTACTMON, DIGACQ, ALMWINDOW


Description Off Normal Alarm Flag
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related NORMALOFFNRMALM.PROFFNRMALM.SVPV,
Parameters
Remarks When ON, it indicates that the function block is not currently in the normal
state

17.3 OFFNRMALM.OPT

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Off Normal Alarm Option
Data Type Enumeration
Range Disable Enable

- 2004 -
Chapter 17 - Oxxxx Parameters

Default ENABLE
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters OFFNRMALM.FLOFFNRMALM.PR
Remarks

17.4 OFFNRMALM.PR

Specific to Block(s) Flag, Push.


Description Off Normal Alarm Priority
Data Type Enumeration ALMPR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters OFFNRMALM.FLOFFNRMALM.SV.
Remarks

Specific to Block(s) DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Off Normal Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters GOPREQ, OPREQ.
Remarks InActive when GOPREQ is Null.

Specific to Block(s) CONTACTMON, DIGACQ, ALMWINDOW


Description Off Normal Alm Priority
Data Type Enumeration
Range NONE (0) Journal (1) Low (2) High (3) Urgent (4)
Default NONE
Config Load YES
Active Loadable No

- 2005 -
Chapter 17 - Oxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters OFFNRMALM.FLOFFNRMALM.SV
Remarks

17.5 OFFNRMALM.SV

Specific to DEVCTL, FLAG, PUSH, FIRSTOUT, DIGACQ, ALMWINDOW, HTMOTOR,


Block(s) LTMOTOR, SOLENOID, VALVEDAMPER
Description Off Normal Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OFFNRMALM.FLOFFNRMALM.PR. DevCtl Only: GOPREQ, OPREQ.
Parameters
Remarks DevCtl only: InActive when GOPREQ is Null.

17.6 OFFNRMALM.TM

Specific to FLAG, DIGACQ


Block(s)
Description Off normal Alarm time in seconds.
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual on-delay time for off normal
alarms. For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 2006 -
Chapter 17 - Oxxxx Parameters

17.7 OFFNRMALM.TMO

Specific to Block FLAG, DIGACQ


(s)
Description Off normal Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for off
normal alarms.

17.8 OFFNRMFL

Specific to Block DICHANNEL (PM I/O)


(s)
Description Off-Normal Alarm Flag. Shows whether an off-normal alarm has been detected
at this point or not.
Data Type Boolean
Range Off: No alarm exists. On: Current PV state is not the same as the configured
PVNORMAL state.
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is only exposed if ALMOPT is OFFNORML.

- 2007 -
Chapter 17 - Oxxxx Parameters

17.9 OFFPULSE

Specific to DOCHANNEL (PM I/O and Series C I/O)


Block(s)
Description Off Pulse Command
Data Type 64-Bit Real Number
Range 0.0 TO 60.0 seconds
Default
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOM
Related
Parameters
Remarks l This command sets the output to OFF for the specified number of seconds. At
the end of the pulse time, the output is set to ON. If 0.0 is entered for
OFFPULSE, the output is immediately set to ON.
l For PM I/O, DOTYPE must be set to STATUS to use OFFPULSE functionality.
l For Series C I/O, DOTYPE must be set to OFFPULSE to use OFFPULSE
functionality.
l When the OFFPULSE pin is connected to a Device Control's PO pin, the
operator must change the OP of the Device Control to start an OFFPULSE.
The operator cannot set a value to the OFFPULSE parameter of the DO
Channel directly. Writes to SO and ONPULSE will also be rejected.
l When the SO, ONPULSE, and OFFPULSE pins are not connected to a
Function Block, the operator can store a value to the OFFPULSE parameter
and start an OFF Pulse with the entered pulse width.
l The value read indicates the last commanded pulse width.

17.10 OHMOFFSET

Specific to AIC
Block(s)
Description 10-Ohm Offset - Corrective value for use only with 10-ohm copper RTD.
Data Type 32-Bit Integer
Range -99 to 99
Default 0
Config Load No
Active No
Loadable

- 2008 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related CALBIAS[0..numChans-1], SENSORTYPE[0..numChans-1].
Parameters
Remarks OHMOFFSET can only be configured on the RTD input module, and is only
configurable when SENSORTYPE is set equal to 10_Cop_427.

17.11 OHMOFFSET[0..numChans-1]

Specific to Block(s) AIM


Description 10-Ohm Offset - Corrective value for use only with 10-ohm copper RTD.
Data Type 32-Bit Integer
Range -99 to 99
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters CALBIAS[0..numChans-1], SENSORTYPE[0..numChans-1].
Remarks OHMOFFSET can only be configured on the RTD input module.

17.12 OI[0..2]

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Override Interlock
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable

- 2009 -
Chapter 17 - Oxxxx Parameters

Access Lock Engineer/ Other Function Block (see Remarks)


Residence CEE
Related BYPASS, BYPPERM, GOP, NUMDOUTS, OIALM.SV[0..2], OP, SAFEOP, SI,
Parameters OIALM.FL[0..2], OIALM.OPT[0..2], SIALM.FL, SIALM.OPT, SIALM.PR,
OIALM.PR[0..2], SIALM.SV.
Remarks Engineer can change only if function block is inactive. These interlocks are not
active is BYPASS is set On. The priority of the OI interlocks is determined by
SAFEOP.
l If SAFEOP = S0, then priority is SI, 0, 1, 2.
l If SAFEOP = S1, then priority is SI, 1, 0, 2.
l If SAFEOP = S2, then priority is SI, 2, 0, 1.
DEVCTL Only: OI(x) is illegal if NUMDOUTS is less-than x.

17.13 OIACTED

Specific to HTMOTOR
Block(s)
Description Ovride interlock acted
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OI[0..2] RESETFIRSTUP
Parameters
Remarks Indicates that the override interlock has been corresponding issued that has
changed the output state to STOP.

17.14 OIALM.FL[0..1]

Specific to Block HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


(s)
Description Override Interlock Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No

- 2010 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related BYPASS, BYPPERM, HIALM, INALM, NUMDOUTS, OIALM.OPT[0..1], OIALM.PR
Parameters [0..1], OIALM.SV[0..1].
Remarks Always Off, if BYPASS is set On.

17.15 OIALM.FL[0..2]

Specific to Block DevCtl


(s)
Description Override Interlock Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related BYPASS, BYPPERM, HIALM, INALM, NUMDOUTS, OIALM.FL[0..2], OIALM.OPT
Parameters [0..2], OIALM.SV[0..2].
Remarks Always Off, if BYPASS is set On.

17.16 OIALM.OPT[0..1]

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Override Interlock Alarm Option.
Data Type Enumeration
Range Enable Disable
Default Enable
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 2011 -
Chapter 17 - Oxxxx Parameters

17.17 OIALM.OPT[0..2]

Specific to Block(s) DevCtl


Description Override Interlock Alarm Option.
Data Type Enumeration OVRDALOP
Range No (0) Yes (1)
Default
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters NUMDOUTS
Remarks Illegal if NUMDOUTS = 0.

17.18 OIALM.PR[0..1]

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Override Interlock Alarm Priority
Data Type Enumeration
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default Low (2)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters NUMDOUTS, OI[0..2], OIALM.FL[0..1], OIALM.OPT[0..1], OIALM.SV[0..1].
Remarks

17.19 OIALM.PR[0..2]

Specific to Block(s) DevCtl


Description Override Interlock Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active Loadable No

- 2012 -
Chapter 17 - Oxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters NUMDOUTS, OI[0..2], OIALM.FL[0..2], OIALM.OPT[0..2], OIALM.SV[0..2].
Remarks Illegal if NUMDOUTS = 0.

17.20 OIALM.SV[0..1]

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Override Interlock Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters OI[0..2], OIALM.FL[0..1], OIALM.OPT[0..1], OIALM.PR[0..1].
Remarks

17.21 OIALM.SV[0..2]

Specific to Block(s) DevCtl


Description Override Interlock Alarm Severity
Data Type 16-Bit Integer
Range 0 to 255
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters NUMDOUTS, OI[0..2], OIALM.FL[0..2], OIALM.OPT[0..2], OIALM.PR[0..2].
Remarks Illegal if NUMDOUTS = 0.

- 2013 -
Chapter 17 - Oxxxx Parameters

17.22 OIOCS

Specific to All I/O Module Function Blocks


Block(s)
Description Output Consumer Status
Data Type ENUM
Range 0 – BadBySubslot
32 – BadBySlot
64 – BadByDevice
96 – BadByController
128 - Good
Default
Config Load No
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related IIOPS, IIOCS, OIOPS
Parameters
Remarks This is consumer status for output data. This status is given by device for output data
indicating whether it is ready to consume data or not.

17.23 OIOPS

Specific to All I/O Module Function Blocks


Block(s)
Description Output Provider Status
Data Type ENUM
Range 0 – BadBySubslot
32 – BadBySlot
64 – BadByDevice
96 – BadByController
128 - Good
Default
Config Load No
Active No
Loadable

- 2014 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related IIOPS, IIOCS, OIOCS
Parameters
Remarks This is provider status for output data. This status is given by controller for output
data whether data is good or not.

17.24 OKINCH1AV

Specific to Block(s) TCMI

Description Success CH1 Input Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

17.25 OKINCH2AV

Specific to Block(s) TCMI

Description Success CH2 Input Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

- 2015 -
Chapter 17 - Oxxxx Parameters

17.26 OKOUTAV

Specific to Block(s) TCMI

Description Success Output Average Messages

Data Type UINT32

Range N/A

Default --

Config Load No

Active Loadable N/A

Access Lock ViewOnly

Residence NOLOAD

Related Parameters

Remarks

17.27 OLDAV

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Old Accumulated Value - The value of the Process Variable (PV), just before it was
reset. This parameter makes the old value available to those functions that need it.
Data Type 64-Bit Real Number
Range Greater-than or equal-to 0.0
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV,
Parameters
Remarks

17.28 ONCAP[1..10]

Specific to Block(s) GRPCAPRBK


Description ON state Capability Value of equipment
Data Type IEEEFloat64
Range

- 2016 -
Chapter 17 - Oxxxx Parameters

Default 0
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This represents ON state Capability Value of corresponding Equipment.

17.29 ONPROCESS

Specific to Block(s) UOC


Description On Process
Data Type BOOLEAN
Range NA
Default OFF
Config Load No

Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

17.30 ONPULSE

Specific to DOCHANNEL (PM I/O and Series C I/O)


Block(s)
Description On Pulse Command
Data Type 64-Bit Real Number
Range 0.0 TO 60.0 seconds
Default N/A
Config No
Load
Active No
Loadable

- 2017 -
Chapter 17 - Oxxxx Parameters

Access Lock Operator


Residence IOP
Related
Parameters
Remarks l This command sets the output to ON for the specified number of seconds. At
the end of the pulse time, the output is set to OFF. If 0.0 is entered for
ONPULSE, the output is immediately set to OFF.
l For PM I/O, DOTYPE must be set to STATUS to use ONPULSE functionality.
l For Series C I/O, DOTYPE must be set to ONPULSE to use ONPULSE
functionality.
l When the ONPULSE pin is connected to a Device Control's PO pin, the
operator must change the OP of the Device Control to start an ONPULSE. The
operator cannot set a value to the ONPULSE parameter of the DO Channel
directly. Writes to SO and OFFPULSE will also be rejected.
l When the SO, ONPULSE, and OFFPULSE pins are not connected to a
Function Block, the operator can store a value to the ONPULSE parameter
and start an ON Pulse with the entered pulse width.
l The value read indicates the last commanded pulse width.

17.31 OP

Specific to All RegCtl Blocks except Fanout: PID, PIDER, PIDFF, PID_PL, RatioCtl, RemCas,
Block(s) RatioBias, RegCalc, Switch, AutoMan, OvrdSel, RegSummer, and RampSoak.
Description Output Value (in Percent)
Data Type 64-Bit Real Number
Range OPEXLOLM to OPEXHILM
Default 0.0
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related OPEU
Parameters
Remarks Output Value ( OP) is represented in percentage of the Calculated Value ( CV) range
( CVEULO and CVEUHI).

Specific to DevCtl
Block(s)
Description Commanded Output State
Data Type String
Range Length: 12 characters
Default STATETEXT[4]
Config No
Load

- 2018 -
Chapter 17 - Oxxxx Parameters

Active No
Loadable
Access Lock Operator
Residence CEE
Related BYPASS, CMDDISALM.FL, CMDDISALM.PR, NUMDOUTS, NUMSTATES, OI[0..2].
Parameters CMDDISALM.SV, CMDDISALM.TM[0..2], OPDOMAP[0..3][1..3], OPFINAL,
CMDFALALM.FL, CMDFALALM.PR, OPREQ, SAFEOP, SAFEREDTAG, SI,
CMDFALALM.SV, CMDFALALM.TM[0..2], STATETEXT[0..6], UNCMDALM.FL,
GOP, GOPFINAL, GOPREQ, MOMSTATE, UNCMDALM.PR, UNCMDALM.SV.
Remarks OP is a String set equal to STATETEXT[GOP]. Access is illegal, if NUMDOUTS = 0.
STATETEXT[6] [‘State2’] is illegal if NUMSTATES = 2. STATETEXT[2] [‘Active’] is
illegal if SAFEOP = S2.

Specific to Block(s) AOCHANNEL, HAOCHANNEL (PM I/O); AOCHANNEL, (Series C I/O)


Description Output. Defines the output value from this point in percent.
Data Type 64-Bit Real Number
Range -6.9 to 106.9 percent
Default -6.9 percent of Full Scale
Config Load No
Active Loadable No
Access Lock Operator
Residence IOM
Related
Parameters
Remarks The control mode must be Manual before an operator can adjust the OP
manually.

Specific to DOCHANNEL (PM I/O)/(Series C I/O)


Block(s)
Description PWM Output. Specifies the percent on-time for a DOTYPE PWM output. (For
DOTYPE STATUS output, use SO.)
Data Type 64-Bit Real Number
Range 0.0 to 100.0 percent
Default 0.0 percent
Config Load No
Active No
Loadable
Access Lock Operator
Residence IOP
Related PERIOD
Parameters
Remarks Pulse on-time is calculated as follows. For DIRECT action: Pulse On-Time = (OP
percent x PERIOD) / 100 For REVERSE action: Pulse On-Time = (100 percent - OP
percent x PERIOD) / 100

- 2019 -
Chapter 17 - Oxxxx Parameters

Specific to DOCHANNEL, Series C DOCHANNEL


Block(s)
Description PWM Output
Data Type Float64
Range 0.0 to 100.0 %
Default 0.0 %
Config No
Load
Active No
Loadable
Access Operator
Lock
Residence IOM
Related Refer to PERIOD parameter for length of period.
Parameters
Remarks The OP is the percent on time for the pulsed output. When the channel is
configured as PWM and is connected to a Function Block, the value indicates the
fetched value from the upstream Function Block. The value can be changed by
changing the value in the upstream Function Block. When the channel is
configured as PWM and the OP pin is not connected to a Function Block, the
operator can store a value to this parameter and control the PWM. When the
channel is configured as STATUS, the value indicates NaN, and user cannot control
the value. For direct action, pulse-on time is calculated as follows: Pulse On-Time =
(OP% * PERIOD) / 100 For reverse action: Pulse On-Time = (100% - OP% *
PERIOD) / 100

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Commanded Output State
Data Type Self-Defining Enumeration
Range HTMOTOR, LTMOTOR: SAFE RUN STOP SOLENOID: SAFE OPEN CLOSE
VALVEDAMPER: SAFE OPEN CLOSE NOCOMMAND
Default HTMOTOR, LTMOTOR: STOP SOLENOID: CLOSE VALVEDAMPER: NOCOMMAND
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OI[0..2]. OPFINAL, OPREQ, CMDDISALM.PR, CMDDISALM.SV,
Parameters SAFEOP, SAFEREDTAG, SI, CMDDISALM.TM[0..2], CMDFALALM.FL,
UNCMDALM.FL UNCMDALM.PR, CMDFALALM.PR, CMDFALALM.SV,
UNCMDALM.SV. CMDDISALM.FL, CMDFALALM.TM[0..2], GOP, GOPFINAL,
GOPREQ,
Remarks

- 2020 -
Chapter 17 - Oxxxx Parameters

Specific to HRBALG_REG block


Blocks
Description Output value in percentage
Data Type FLOAT64
Range 0-100
Default 0
Config. No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks This parameter is applicable for the algorithms such as PIDSPC, PIDCM, and
PIDCMA which supports Supervisory (AM) Cascade connection. The OP parameter
is connected to the REMCAS block's X1 input. This parameter receives the data from
Computer Set Point (CSP) (from AM) for PIDSPC or CO (from AM) for PIDCM/CMA
when the Mode is "CAS."

17.32 OP

Specific to HRBALG_REG block


Blocks
Description Output value in percentage
Data Type FLOAT64
Range 0-100
Default 0
Config. No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks This parameter is applicable for the algorithms such as PIDSPC, PIDCM, and
PIDCMA which supports Supervisory (AM) Cascade connection. The OP parameter
is connected to the REMCAS block's X1 input. This parameter receives the data from
Computer Set Point (CSP) (from AM) for PIDSPC or CO (from AM) for PIDCM/CMA
when the Mode is "CAS."

- 2021 -
Chapter 17 - Oxxxx Parameters

17.33 OP[0..7]

Specific to Block Chassis HART AO IOM


(s)
Description Output Value - Provides the output value of the 8 IOM channels which are
updated by channel block
Data Type Float64
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

17.34 OP[0..numChans-1]

Specific to Block(s) EIP Analog Output Modules


Description Output value (%)— Output value represented in percentage.
Data Type Float32
Range

Default 0.0
Config Load
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters None
Remarks It is indexed by the channel number.

17.35 OP[1..8]

Specific to Fanout
Block(s)
Description Output ( OP) Values (in percent) for function blocks with Multiple Outputs -
There is one value per output.
Data Type 64-Bit Real Number
Range OPEXLOLM to OPEXHILM

- 2022 -
Chapter 17 - Oxxxx Parameters

Default OPEXLOLM
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related OPEU[1..8]
Parameters
Remarks OP is represented in percentage of the Calculated Variable ( CV) range (
CVEULOand CVEUHI ).

17.36 OP[1..NUMCHAN]

Specific to Block(s) AO8, AO16


Description Target Output Value
Data Type 64-Bit Real Number
Range -6.9 to 106.9 percent
Default -6.9 percent of Full Scale
Config Load No
Active Loadable No
Access Lock Operator
Residence IOP
Related
Parameters
Remarks The control mode must be Manual before an operator can adjust the OP
manually.

17.37 OP[1..16]. INSTRUCTDISABLE

Specific to Block(s) STEP


Description Instruction Disable
Data Type Boolean
Range ON
OFF
Default OFF
Active Loadable N/A
Access Lock Engineeer
Residence CEE
Related Parameters
Remarks

- 2023 -
Chapter 17 - Oxxxx Parameters

17.38 OP[1..16].ACQSTATE

Specific to Step
Block(s)
Description Acquisition State
Data Type Enumeration
Range 0 NONE
1 ACQUIRING Requester is attempting to
acquire the resource.
2 ACQUIRED Requester owns the
resource.
3 RELEASING Requester is attempting to
release the resource.
4 ERROR An error occurred (for
example, Resource was
deleted and reloaded).
Default NONE
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OP[1..16].OWNFLOP[1..16].RELFLOP[1..16].REQFL
Parameters
Remarks Accessible, if OP[1..16].TYPE > (greater than) or = N_IEC, otherwise the parameter is
undefined Note that even in state ACQUIRED other requesters may own the same
resource, if Resource.MAXOWNERS > (greater than) 1 If ACQSTATE=ERROR: To
recover from the error, the resource needs to be re-acquired or released.

17.39 OP[1..16].BYPREQ

Specific to Step
Block(s)
Description Bypass Request - Output bypass.
Data Type Enumeration
Range 0 None Normal output processing
1 Skip Skip/bypass output
processing
Default None (0)
Config No
Load
Active No
Loadable

- 2024 -
Chapter 17 - Oxxxx Parameters

Access Lock Controlled by CONTROLLOCK


Residence CEE
Related
Parameters
Remarks If the output processing has not started yet, it will let the step proceed as if the
output would not exist. If the output processing has started but did not complete, it
will let the step proceed, as if the output completed immediately and successfully.
This is most useful for allowing steps with failed outputs to proceed. If the output
processing is already complete, it has no effect.

17.40 OP[1..16].CMDREQSTS

Specific to Block(s) Step


Description Command Request Status
Data Type 32-Bit Integer
Range See Control Builder Error Codes Reference
Default -1
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks Diagnostic parameter, store status of connection to resource.

17.41 OP[1..16].CONFIGASSOCPARAM

Specific to Block Step


(s)
Description Configure Associate Key Parameter Option
Data Type Boolean
Range 0 Off Cannot configure associate
parameter
1 On Can configure associate
parameter
Default Off (0)
Config Load Yes
Active Loadable Yes

- 2025 -
Chapter 17 - Oxxxx Parameters

Access Lock Application Developer Only


Residence SR
Related
Parameters
Remarks This parameter enables or disables associated parameters for respective Step
Outputs.

17.42 OP[1..16].CONFIGCODE

Specific to Step
Block(s)
Description Output Configuration Code
Data Type Enumeration CSCOCONFIGCODEOUTPUT
Range None (0) Ok (1) UnknownError (2) ImplicitConv (3) LossOfPrecsn (4) UnexpctEnd (5)
UnexpctComma (6) ColonWoQMark (7) FctNotMltArg (8) ClosParenExp (9)
OperandExp (10) MissingArg (11) OperatorExp (12) ColonExp (13) TypeMismatch
(14) TypeNotSupp (15) SyntaxError (16) ExprTooCmplx (17) NotEPcodeMe (18)
NotEDataStak (19) UnsuppFeatur (20) ExprTooLong (21) DivideByZero (22)
UnknownToken (23) UnexpTokenOS (24) UnknownFunc (25) UnexpOCExpr2 (26)
UnexpOCExpr3 (27) ZeroArgument (28) UnexpToken (29) InvalResult (30)
InvalTokenTb (31) IntegerExp (32) DoubleExp (33) MissedImpl (34) UnicodeConv
(35) ConsstExprRem (36) DuplExprRem (37) DstnInvalid (38) DstnCRqInval (39)
ExtUse40 (40) ExtUse41 (41) ExtUse42 (42) ExtUse43 (43) ExtUse44 (44) ExtUse45
(45) ExtUse46 (46) ExtUse47 (47) ExtUse48 (48) ExtUse49 (49) ExtUse50 (50)
UnsupConTyp (51) UnExpClsParn (52) CantAssRVal (53) UnExpArrOpen (54)
ArrClsExpect (55) ArrOpnExpect (56) ArrIndxError (57) StringExpect (58)
InvalidRefer (59) TooManyConnS (60) CantConvInpt (61)
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related
Parameters
Remarks See OP[1..16].CONFIGSTS for additional information.

17.43 OP[1..16].CONFIGDESC

Specific to Block(s) Step


Description Output Configuration Descriptor
Data Type String
Range Maximum of 39 characters.

- 2026 -
Chapter 17 - Oxxxx Parameters

Default Null String


Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See OP[1..16].CONFIGSTS for additional information.

17.44 OP[1..16].CONFIGSTS

Specific to Step
Block(s)
Description Output Configuration Status
Data Type Enumeration CSCOCONFIGSTS
Range Ok (0) Information (1) Warning (2) SevereWarn (3) Fail (4) Error (5) SevereError (6)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OP[1..16].CONFIGASSOCPARAM, OP[1..16].CONFIGCODE, OP[1..16].CONFIGDESC.
Parameters
Remarks Step output configuration status parameters OP[1..16].CONFIGSTS, OP
[1..16].CONFIGCODE, OP[1..16].CONFIGDESC are set on SCM STATE transition
from Inactive to Validated.

17.45 OP[1..16].CURRDESCREF

Specific to Step
Block(s)
Description Reference to the Current value descriptor
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference
Default Null string
Config Load Yes
Active Yes
Loadable

- 2027 -
Chapter 17 - Oxxxx Parameters

Access Lock Application Developer Only


Residence SR
Related OP[1..16].CURREUDESCREF OP[1..16]CURRVALREF
Parameters
Remarks Identifies the parameter as the Current Value Reference Descriptor for Step
Output. The identified parameter is shown on the SCM Table view associated with
the Step Output. Example name is CMNAME.DESC.

17.46 OP[1..16].CURREUDESCREF

Specific to Step
Block(s)
Description Reference to the Current value engineering units descriptor
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference
Default Null string
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer Only
Residence SR
Related OP[1..16].CURRDESCREF OP[1..16]CURRVALREF
Parameters
Remarks Identifies the parameter as the Current Value Reference Engineering Units
Descriptor for Step Output. The identified parameter is shown on the SCM Table
view associated with the Step Output. Example name is CMNAME.EUDESC.

17.47 OP[1..16].CURRVALREF

Specific to Step
Block(s)
Description Step Output Current Value Reference
Data Type Parameter Id
Range Any Tag.[Block].Parameter reference
Default ""
Config Yes
Load
Active No
Loadable

- 2028 -
Chapter 17 - Oxxxx Parameters

Access Lock AppDeveloper Only


Residence SR
Related OP[1..16].CURRVALTREND
Parameters
Remarks Identifies a parameter as the Current Value for the Step Output. The identified
parameter is monitored and shown on the SCM Table view associated with the Step
Output. Example values are CMName.Pid.PV and SCMName.INALM.

17.48 OP[1..16].CURRVALTREND

Specific to Step
Block(s)
Description Step Output Current Value add to Trend
Data Type Boolean
Range Off - OP[].CURRVALREF not added to Trend On - OP[].CURRVALREF is added to
Trend
Default Off
Config Load Yes
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related OP[1..16].CURRDESCREF, OP[1..16].CURREUDESCREF, OP[1..16].CURRVALREF
Parameters
Remarks Specifies whether the parameter identified by OP[].CURRVALREF is added to the
built-in Trend display that is part of the SCM Table view. Note that the built-in Trend
display is not supported in the pilot release.

17.49 OP[1..16].DELAYTIME

Specific to Step
Block(s)
Description Step Output Delay Time (in seconds)
Data Type Integer32
Range 0 to 25000000
Default 0
Config Load Yes
Active No
Loadable

- 2029 -
Chapter 17 - Oxxxx Parameters

Access Lock Engineer


Residence CEE
Related OP[1..16].DELAYTIMEREM
Parameters
Remarks The delay time is the time the STEP block waits before executing the current output
only. If the next output has a lower delay time, then it gets executed first.

17.50 OP[1..16].DELAYTIMEREM

Specific to Step
Block(s)
Description Step Output Delay Time Remaining (in seconds)
Data Type Integer32
Range 0 to 25000000
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OP[1..16].DELAYTIME
Parameters
Remarks Provides the number of seconds remaining for the current Output delay/pause in
progress. Value will be 0 unless the Output delay/pause is in progress.

17.51 OP[1..16].DESC

Specific to Block(s) Step block, Transition block


Description Output Description
Data Type String
Range Maximum Length: 64 characters
Default Null String
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

- 2030 -
Chapter 17 - Oxxxx Parameters

17.52 OP[ ].DSTN

Specific to Block(s) Step


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

17.53 OP[1..16].ENTRYDESCREF

Specific to Step
Block(s)
Description Reference to the Entry value descriptor
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference
Default Null string
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer Only
Residence SR
Related OP[1..16].ENTRYEUDESCREF OP[1..16].ENTRYMAXREF OP[1..16].ENTRYMINREF
Parameters OP[1..16].ENTRYVALREF
Remarks Identifies the parameter as the Entry Value Reference Descriptor for Step Output.
The identified parameter is shown on the SCM Table view associated with the Step
Output. Example value is SCMName.DESC.

17.54 OP[1..16].ENTRYEUDESCREF

Specific to Step
Block(s)
Description Reference to the Entry value engineering units descriptor
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference

- 2031 -
Chapter 17 - Oxxxx Parameters

Default Null string


Config Yes
Load
Active Yes
Loadable
Access Lock Application Developer Only
Residence SR
Related OP[1..16].ENTRYDESCREF OP[1..16].ENTRYMAXREF OP[1..16].ENTRYMINREF OP
Parameters [1..16].ENTRYVALREF
Remarks Identifies the parameter as the Entry Value Reference Engineering Units
Descriptor for Step Output. The identified parameter is shown on the SCM Table
view associated with the Step Output. Example value is SCMName.EUDESC.

17.55 OP[1..16].ENTRYLABEL

Specific to Block(s) Step


Description Entry Parameter Label
Data Type String
Range 0 to 2000 characters
Default Null string
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters OP[1..16].ENTRY
Remarks

17.56 OP[1..16].ENTRYMAXREF

Specific to Step
Block(s)
Description Reference to the Entry value maximum
Data Type Parameter ID
Range Any Tag [Block] Parameter reference
Default Null string
Config Yes
Load
Active Yes
Loadable

- 2032 -
Chapter 17 - Oxxxx Parameters

Access Lock Application Developer Only


Residence SR
Related OP[1..16].ENTRYDESCREF OP[1..16].ENTRYMINREF OP[1..16].ENTRYVALREF OP
Parameters [1..16].ENTRYEUDESCREF
Remarks Identifies the parameter as the Entry Value Reference Maximum for Step Output.
The identified parameter is shown on the SCM Table view associated with the Step
Output, and the Operator cannot store a value to this parameter. Example value is
CM.NUMERIC.PVHILM.

17.57 OP[1..16].ENTRYMINREF

Specific to Step
Block(s)
Description Reference to the Entry value minimum
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference
Default Null string
Config Yes
Load
Active Yes
Loadable
Access Lock Application Developer Only
Residence SR
Related OP[1..16].ENTRYVALREF OP[1..16].ENTRYDESCREF OP[1..16].ENTRYMAXREF OP
Parameters [1..16].ENTRYEUDESCREF
Remarks Identifies the parameter as the Entry Value Reference Minumum for Step Output.
The identified parameter is shown on the SCM Table view associated with the Step
Output, and the Operator cannot store a value to this parameter. Example value is
CM.NUMERIC.PVLOLM.

17.58 OP[1..16].ENTRYVALREF

Specific to Step
Block(s)
Description Reference to the Step output entry value
Data Type Parameter Id
Range Any Tag.[Block].Parameter reference
Default Null string
Config Yes
Load
Active No
Loadable

- 2033 -
Chapter 17 - Oxxxx Parameters

Access Lock AppDeveloper Only


Residence SR
Related OP[1..16].ENTRYDESCREF OP[1..16].ENTRYMAXREF OP[1..16].ENTRYEUDESCREF
Parameters OP[1..16].ENTRYMINREF
Remarks Identifies a parameter as the Entry Value for the Step Output. The identified
parameter is shown on the SCM Table view associated with the Step Output, and
the Operator can store a value to this parameter as the result of the Step Output's
Instruction. Example values are CMName.Pid.PV.

17.59 OP[1..16].EQUIPNAME

Specific to Step
Block(s)
Description Equipment Name - Name of the resource to be acquired.
Data Type BLOCKID
Range
Default NULL
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks Accessible, if OP[1..16].TYPE > (greater than) or = N_IEC, otherwise the parameter is
undefined The value will always be equal to the Tagname used in the output
destination, if the destination is not using an alias. The value will show the
currently used resource, if the output destination is an alias.

17.60 OP[1..16].EXECCODE

Specific to Step
Block(s)
Description Output Execution Code
Data Type Enumeration CSCOEXECCODE
Range None (0) ConfigError (1) ExprEvalFail (2) StoreFailed (3) CommError (4)
StoreWarning (5) InternalErr (6) CtrlReqErr (7) DataTypeErr (8) StorePending (9)
Default None (0)
Config Load No
Active No
Loadable

- 2034 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks See OP[1..16].EXECSTS for additional information.

17.61 OP[1..16].EXECDESC

Specific to Block(s) Step


Description Output Execution Code Descriptor
Data Type String
Range Maximum of 39 characters.
Default Null String
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See OP[1..16].EXECSTS for additional information.

17.62 OP[1..16].EXECSTS

Specific to Step
Block(s)
Description Output Execution Status
Data Type Enumeration CSCOEXECST
Range Ok (0) Bypass (1) Info (2) Warning (3) Fail (4) Error (5) OkPaused (6) BypassPaused
(7) InfoPaused (8) WarnPaused (9) FailPaused (10) ErrorPaused (11)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OP[1..16].EXECCODE, OP[1..16].EXECDESC.
Parameters
Remarks Step output execution status parameters OP[1..16].EXECSTS, OP
[1..16].EXECCODE, and OP[1..16].EXECDESC are updated when the step is in the
SCM's current scope of execution.

- 2035 -
Chapter 17 - Oxxxx Parameters

17.63 OP[1..16].EXPRPCODE

Specific to Block(s) Step


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

17.64 OP[1..16].FILTERABLE

Specific to Block(s) Step


Description Step Output is Filterable
Data Type Boolean
Range 0 Off Filter is not used
1 On Filter can be used
Default On (1)
Config Load
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

17.65 OP[1..16].INSTRUCTCNFM

Specific to Step
Block(s)
Description Step Output Instruction Confirmation
Data Type Boolean
Range Off - Confirmation not requested On - Confirmation requested for Instruction of
the Step Output
Default Off
Config Load No

- 2036 -
Chapter 17 - Oxxxx Parameters

Active No
Loadable
Access Lock Operator
Residence CEE
Related OP[1..16].INSTRUCTCOMP, OP[1..16].INSTRUCTPEND
Parameters
Remarks Used to confirm the Instruction of the Step Output. Provided to the user via a
checkbox on the SCM Table view.

17.66 OP[1..16].INSTRUCTCOMP

Specific to Step
Block(s)
Description Step Output Instruction Complete
Data Type Boolean
Range OFF – When Step Instructions are Active or SCM/RCM is in IDLE. ON – When Step
Instructions are Complete or No Instructions are configured.
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OP[1..16].FILTERABLE, OP[1..16].INSTRUCTCNFM, OP[1..16].INSTRUCTPEND
Parameters
Remarks Provides an indication of whether the Step Output Instruction has been completed.

17.67 OP[1..16].INSTRUCTION

Specific to Step
Block(s)
Description Step Output Instruction
Data Type BigString
Range Maximum length of 20,000 characters
Default
Config Load Yes
Active No
Loadable

- 2037 -
Chapter 17 - Oxxxx Parameters

Access Lock AppDeveloper Only


Residence SR
Related OP[1..16].NOTE, OP[1..16].WARNING
Parameters
Remarks Contains raw HTML for configured Step Output Instruction. User does not have to
be aware of or do anything with this parameter.

17.68 OP[1..16].INSTRUCTPEND

Specific to Step
Block(s)
Description Step Output Instruction Pending
Data Type Boolean
Range Off - Instruction is not pending On - Instruction is pending
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OP[1..16].FILTERABLEOP[1..16].INSTRUCTCNFMOP[1..16].INSTRUCTCOMP
Parameters
Remarks Provides an indication of whether the Step Output currently has an Instruction
pending that requires operator interaction.

17.69 OP[1..16].INSTRUCTTYPE

Specific to Step
Block(s)
Description Step Output Instruction Type
Data Type Enumeration
Range (0) None (1) Info (2) Confirm
Default None
Config Yes
Load
Active No
Loadable

- 2038 -
Chapter 17 - Oxxxx Parameters

Access Lock AppDeveloper Only


Residence CEE
Related OP[1..16].INSTRUCTION
Parameters
Remarks Selects the Instruction Type for the Step Output: None - no Instruction is
configured Info - an Informational Instruction is configured that does not require
operator confirmation Confirm - a Confirmable Instruction is configured that does
require operator confirmation

NOTE Users should only set the OP[X].INSTRUCTTYPE parameter in a


step block as template defining if they’ve already set the
INSTRUCTNOTIFOPT as template defining on the container.

17.70 OP[1..16].MONTASKREF

Specific to Step
Block(s)
Description Step Output Monitoring Task Reference
Data Type Parameter Id
Range Any Tag.[Block].Parameter reference
Default ""
Config Yes
Load
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related
Parameters
Remarks Identifies a parameter as the Monitoring Task result associated with the Step
Output. The identified parameter is interpreted as a Boolean value (0 is Off; non-0 is
On) even if the parameter data type is not Boolean. The parameter is monitored
and an indication shown on the SCM Table view associated with the Step Output. A
"Monitoring Task" is a control strategy that evaluates a process condition for which
the result is normally True/On or False/Off.

17.71 OP[1..16].NOTE

Specific to Step
Block(s)
Description Step Output Note
Data Type BigString
Range Maximum length of 20,000 characters

- 2039 -
Chapter 17 - Oxxxx Parameters

Default ""
Config Load Yes
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related OP[1..16].INSTRUCTIONOP[1..16].WARNING
Parameters
Remarks Contains raw HTML for configured Step Output Note. User does not have to be
aware of or do anything with this parameter.

17.72 OP[1..16].OWNERSSTS

Specific to Block Step


(s)
Description Resource Owners Get Status
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Accessible, if OP[1..16].TYPE > (greater than) or = N_IEC, otherwise the
parameter is undefined.

17.73 OP[1..16].OWNFL

Specific to Block Step


(s)
Description Ownership Flag
Data Type Boolean
Range 0 Off Resource is not owned
1 On Resource is owned
Default Off
Config Load No
Active Loadable No

- 2040 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related OP[1..16].ACQSTATE
Parameters
Remarks Accessible, if OP[1..16].TYPE > (greater than) or = N_IEC, otherwise the
parameter is undefined

17.74 OP[1..16].RELFL

Specific to Step
Block(s)
Description Release Flag - Release resource input.
Data Type Boolean
Range 0 Off No action
1 On Release resource, the resource
configured in the output will be
released independent of the step
output processing. Use with great
care.
Default Off
Config No
Load
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related OP[1..16].ACQSTATEOP[1..16].REQFL
Parameters
Remarks Accessible, if OP[1..16].TYPE > (greater than) or = N_IEC, otherwise the parameter is
undefined This parameter is not used for standard scenarios. It is provided for
advanced applications, diagnostic purposes, and recovery scenarios.

17.75 OP[1..16].REQFL

Specific to Step
Block(s)
Description Request Flag - Request resource input.
Data Type Boolean
Range 0 Off No action
1 On Request resource, the resource
configured in the output will be
acquired independent of the step
output processing. Use with great
care.

- 2041 -
Chapter 17 - Oxxxx Parameters

Default Off
Config No
Load
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related OP[1..16].ACQSTATEOP[1..16].RELFL
Parameters
Remarks Accessible, if OP[1..16].TYPE > (greater than) or = N_IEC, otherwise the parameter is
undefined This parameter is not used for standard scenarios. It is provided for
advanced applications, diagnostic purposes, and recovery scenarios.

17.76 OP[1..16].ROLE

Specific to Block(s) Step


Description Output Role
Data Type String
Range 16 Characters
Default Blank
Config Load
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

17.77 OP[1..16].SRCEXPR

Specific to Block(s) Step


Description Output Source Expression
Data Type String
Range Maximum Length: 255 characters
Default Null String
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

- 2042 -
Chapter 17 - Oxxxx Parameters

17.78 OP[1..16].STATE

Specific to Step
Block(s)
Description Sequential Control Module (SCM) Step Output State
Data Type Enumeration CSCOOUTPUTSTATE1
Range Edit (0) Inactive (1) ProcDelay (3) Processing (6) CompleteBypassed (7) Complete (8)
IEC_Init (9) IEC_Wait (12) Cancelled (14) IEC_Exit (15)
Default Edit (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

17.79 OP[1..16].TARGETCHANGE

Specific to Step
Block(s)
Description Step Output Target Value Change Allowed
Data Type Boolean
Range Off - Operator cannot change displayed Target Value On - Operator can change
displayed Target Value
Default Off
Config Load Yes
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related OP[1..16].TARGETDESCREF, OP[1..16].TARGETEUDESCREF, OP
Parameters [1..16].TARGETMAXREF, OP[1..16].TARGETMINREF, OP[1..16].TARGETVALREF
Remarks Specifies whether the Operator will be able to change the Target Value associated
with the Step Output shown on the SCM Table view.

- 2043 -
Chapter 17 - Oxxxx Parameters

17.80 OP[1..16].TARGETDESCREF

Specific to Step
Block(s)
Description Reference to the Target value descriptor
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference
Default Null string
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer Only
Residence SR
Related OP[1..16].TARGETEUDESCREF OP[1..16].TARGETMAXREF OP
Parameters [1..16].TARGETMINREF OP[1..16]TARGETVALREF
Remarks Identifies the parameter as the Target Value Reference Descriptor for Step Output.
The identified parameter is shown on the SCM Table view associated with the Step
Output. Example value is SCMNAME.DESC.

17.81 OP[1..16].TARGETEUDESCREF

Specific to Step
Block(s)
Description Reference to the Target value engineering units descriptor
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference
Default Null string
Config Yes
Load
Active Yes
Loadable
Access Lock Application Developer Only
Residence SR
Related OP[1..16].TARGETDESCREF OP[1..16].TARGETMAXREF OP[1..16].TARGETMINREF
Parameters OP[1..16]TARGETVALREF
Remarks Identifies the parameter as the Target Value Reference Engineering Units
Descriptor for Step Output. The identified parameter is shown on the SCM Table
view associated with the Step Output. Example value is SCMNAME.EUDESC.

- 2044 -
Chapter 17 - Oxxxx Parameters

17.82 OP[1..16].TARGETLABEL

Specific to Block(s) Step


Description Target Parameter Label
Data Type String
Range 0 to 2000 characters
Default
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters OP[1..16].TARGET
Remarks

17.83 OP[1..16].TARGETMAXREF

Specific to Step
Block(s)
Description Reference to the Target value maximum
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference
Default Null string
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer Only
Residence SR
Related OP[1..16].TARGETDESCREF OP[1..16].TARGETMINREF OP
Parameters [1..16].TARGETEUDESCREF OP[1..16]TARGETVALREF
Remarks Identifies the parameter as the Target Value Reference Maximum for Step Output.
The identified parameter is shown on the SCM Table view associated with the Step
Output. Example value is CM.NUMERIC.PVHILM.

17.84 OP[1..16].TARGETMINREF

Specific to Step
Block(s)
Description Reference to the Target value minimum
Data Type Parameter ID
Range Any Tag.[Block].Parameter reference
Default Null string
Config Load Yes

- 2045 -
Chapter 17 - Oxxxx Parameters

Active Yes
Loadable
Access Lock Application Developer Only
Residence SR
Related OP[1..16].TARGETDESCREF OP[1..16].TARGETMAXREF OP
Parameters [1..16].TARGETEUDESCREF OP[1..16]TARGETVALREF
Remarks Identifies the parameter as the Target Value Reference Maximum for Step Output.
The identified parameter is shown on the SCM Table view associated with the Step
Output. Example name is CMNAME.NUMERIC.PVLOLM.

17.85 OP[1..16].TARGETVALREF

Specific to Step
Block(s)
Description Step Output Target Value Reference
Data Type Parameter Id
Range Any Tag.[Block].Parameter reference
Default ""
Config Yes
Load
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related OP[1..16].TARGETCHANGE, OP[1..16].ENTRYVALREF, OP[1..16].ENTRYEUDESCREF
Parameters
Remarks Identifies a parameter as the Target Value associated with the Step Output. The
identified parameter is shown on the SCM Table view associated with the Step
Output. The Target Value can be used to show the operator the intended result for
the Output's Instruction.

17.86 OP[1..16].TYPE
It is not recommended to use step outputs of type S_IEC, N_IEC, or R_IEC with destination
parameters that are inputs to flip-flops or other bistable, monostable blocks, or logic
configurations. Examples are OPCMD[0..2] of DEVCTL and S and R of LOGIC:RS. Although these
configurations are technically supported and show a predictable behavior, the resulting behavior
may be non-intuitive and confusing to operators (example: using an N_IEC output on OPCMD[1]
will result in OP-behavior similar to what would be expected from an S_IEC output if directly
controlling a parameter such as OP). Therefore, this practice is not considered a good engineering
practice.

- 2046 -
Chapter 17 - Oxxxx Parameters

Specific to Step
Block(s)
Description Output Type
Data Type Enumeration CSCOOPTYPE
Range 0 Null Output writes the calculated value to the
destination. Then the output is complete.
No other action or side effect will occur.
Works with all supported Experion PKS
gateways and controllers which can be
accessed from the node where the SCM
or RCM is loaded. Works with all
supported scalar datatypes of the target
node. Does not work with the target
parameters listed for Set and NotStored.
1 Set Can only be selected if the target
parameter is one of CONTROLREQ,
MODEREQ, OPREQ, SPRATEREQ, SPREQ,
SPTVREQ.
2 NotStored Can only be selected if the target
parameter is one of CONTROLREQ,
MODEREQ.
3 Default For internal use only
4 N_IEC Action qualifier N according to IEC 61131-
3, Output sets the destination parameter
to TRUE for the duration of the step, can
only be selected for destination
parameters of data type BOOLEAN.
5 R_IEC Action qualifier R according to IEC 61131-
3, Output resets the destination
parameter to FALSE, can only be selected
for destination parameters of data type
BOOLEAN.
6 S_IEC Action qualifier S according to IEC 61131-
3, Output sets the destination parameter
to TRUE , can only be selected for
destination parameters of data type
BOOLEAN.
Default Null (0)
Config Yes
Load
Active No
Loadable

- 2047 -
Chapter 17 - Oxxxx Parameters

Access Application Developer


Lock
Residence CEE
Related For Set and NotStored: CONTROLREQ, MODEREQ, OPREQ, SCMOPT, SPRATEREQ,
Parameters SPREQ, SPTVREQ. For N_IEC, R_IEC, S_IEC: SCMOPT
Remarks Null output type is the default and can be used for almost all parameters in
Experion PKS controllers. If ControlModule.SCMOPT = Fixed, then Control Requests
(CONTROLREQ) to the RegCtl function block must use a set output type, output
requests to the DevCtl function block, and use a set of NotStored output type.
Output types of N_IEC, R_IEC, S_IEC are only supported, if the destination
parameter is in a Control Module with SCMOPT = COMMON The symbol shown in
charts is: - for Null, S for Set and S_IEC, N for NotStored and N_IEC, and R for R_
IEC.

17.87 OP[1..16].WARNING

Specific to Step
Block(s)
Description Step Output Warning
Data Type BigString
Range Maximum length of 20,000 characters
Default “”
Config Load Yes
Active No
Loadable
Access Lock AppDeveloper Only
Residence SR
Related OP[1..16].INSTRUCTION, OP[1..16].NOTE
Parameters
Remarks Contains raw HTML for configured Step Output Warning. User does not have to
be aware of or do anything with this parameter.

17.88 OP_AO_S

Specific to Block(s) UIO


Description Output Value(%)
Data Type FLOAT64
Range -6.9% to 106.9%
Default -6.9%
Config Load No
Active Loadable No

- 2048 -
Chapter 17 - Oxxxx Parameters

Access Lock Operator


Residence UIO
Related Parameters N/A
Remarks This is the output value of this point in percent.

Specific to Block(s) UIO, AO04, AO08


Description Output Value(%)
Data Type FLOAT64
Range -6.9% to 106.9%
Default -6.9%
Config Load No
Active Loadable

Access Lock Operator


Residence IOM Block
Related Parameters N/A
Remarks This is the output value of this point in percent.

17.89 OP_DO_S

Specific to Block(s) UIO


Description Status Output Value
Data Type BOOLEAN
Range
0 Off

1 On

Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence UIO
Related Parameters N/A
Remarks The current output value.

Specific to Block(s) UIO, DO32-24VDC , DO08-VAC, DO08-RELAY


Description Status Output Value
Data Type BOOLEAN
Range
0 Off

1 On

- 2049 -
Chapter 17 - Oxxxx Parameters

Default Off
Config Load No
Active Loadable

Access Lock ViewOnly


Residence IOM Block
Related Parameters N/A
Remarks The current output value.

17.90 OP2PVPOLYMODEL

Specific to Block(s) PROFCONOUT


Description OP2PV Poly Model
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence NOLOAD
Related Parameters MV.OPPVFILTERCOEF
Remarks OP to PV Polynomial Model

17.91 OPBIAS

Specific to AutoMan, OvrdSel, PID, PIDFF, PIDExtReset, RemCas, RatioBias, RatioCtl, RegCalc,
Block(s) EnhRegCalc, RegSummer, and Switch.
Description Total Output Bias (in Engineering Units) - OPBIAS is the sum of two components: a
user-specified fixed bias (OPBIAS.FIX) and a calculated floating bias
(OPBIAS.FLOAT).
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active No
Loadable

- 2050 -
Chapter 17 - Oxxxx Parameters

Access Lock Operator


Residence CEE
Related OPBIAS.FIX, OPBIAS.FLOAT, OPBIAS.RATE.
Parameters
Remarks The following occurs on a store to OPBIAS:
l OPBIAS and OPBIAS.FIX are both set to a new value.
l OPBIAS.FLOAT is set to zero.

17.92 OPBIAS[1..8]

Specific to Fanout
Block(s)
Description Total Output Bias for function blocks with Multiple Outputs - OPBIAS is the sum of
two components: a user-specified fixed bias (OPBIAS[1..8].FIX) and a calculated
floating bias (OPBIAS[1..8].FLOAT).
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related OPBIAS[1..8].FIX, OPBIAS[1..8].FLOAT, OPBIAS[1..8].RATE
Parameters
Remarks

17.93 OPBIAS.FIX

Specific to AutoMan, OvrdSel, PID, PIDFF, PIDExtReset, RemCas, RatioBias, RatioCtl, RegCalc,
Block(s) EnhRegCalc, RegSummer, and Switch.
Description Fixed Output Bias (in Engineering Units) - A user-specified bias that is applied to the
function blocks' Calculated Variable (CV).
Data Type 64-Bit Real Number
Range N/A
Default 0.0
Config Yes
Load
Active No
Loadable

- 2051 -
Chapter 17 - Oxxxx Parameters

Access Lock Operator


Residence CEE
Related OPBIASOPBIAS.FLOATOPBIAS.RATE RBOPTION BSLOLMBSHILM
Parameters
Remarks CV = OP + OPBIAS.FIX + OPBIAS.FLOAT The OPBIAS.FIX value will be limited to a
range between BSLOLM and BSHILM (-50.0 to 50.0, by default) when the
RBOPTION is set to FixedRatioBias. If you enter any values outside this range an
error message appears.

17.94 OPBIAS[1..8].FIX

Specific to Fanout
Block(s)
Description Fixed Output Bias (in Engineering Units) - A user specified bias which is applied to
the function blocks' Calculated Variable's Outputs (CV[1..8]).
Data Type 64-Bit Real Number
Range N/A
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related OPBIAS[1..8], OPBIAS[1..8].FLOAT, OPBIAS[1..8].RATE
Parameters
Remarks

17.95 OPBIAS.FLOAT

Specific to AutoMan,OvrdSel, PID, PIDFF, PIDExtReset, RemCas, RatioBias, RatioCtl, RegCalc,


Block(s) EnhRegCalc, RegSummer, and Switch.
Description Floating Output Bias (in Engineering Units) - Used in conjunction with
OPBIAS.RATE.
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config No
Load
Active No
Loadable

- 2052 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related OPBIAS, OPBIAS.FIX, OPBIAS.RATE.
Parameters
Remarks Floating bias is calculated as follows: OPBIAS.FLOAT = CV(init) - (CV(unbiased) +
OPBIAS.FIX) CV (init) = initialization value received from secondary CV(unbiased) =
unbiased calculated value OPBIAS.FIX = fixed bias (user specified)

17.96 OPBIAS[1..8].FLOAT

Specific to Fanout
Block(s)
Description Floating Output Bias (in Engineering Units) - Calculated bias for each of Fanout
Block's output which is applied to the function blocks' Calculated Variable's Output
(CV[1..8]). OPBIAS[1..8].FLOAT is used to ensure a bumpless transition, following
initialization or mode change.
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPBIAS[1..8], OPBIAS[1..8].FIX, OPBIAS[1..8].RATE
Parameters
Remarks OPBIAS.FLOAT(new value) = OPBIAS.FLOAT(current value) - (OPBIAS.RATE/
cycles/min) where cycles per minute is the number of function block executions per
minute.

17.97 OPBIAS.RATE

Specific to AutoMan, OvrdSel, PID, PIDFF, PIDExtReset, RemCas, RatioBias, RatioCtl, RegCalc,
Block(s) EnhRegCalc, RegSummer, and Switch.
Description Output Bias Ramp Rate (in Engineering Units per Minute) - Used in conjunction
with OPBIAS.FLOAT to eliminate output bumps when initialization path is done by
the user.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load Yes
Active No
Loadable

- 2053 -
Chapter 17 - Oxxxx Parameters

Access Lock Engineer


Residence CEE
Related OPBIAS, OPBIAS.FIX, OPBIAS.FLOAT.
Parameters
Remarks The Output Bias is the sum of two parts (OPBIAS.FIXED - a fixed output bias, and
OPBIAS.FLOAT - a calculated bias) and is generally used to ensure a bumpless
transfer when the block initializes or changes mode.

17.98 OPBIAS[1..8].RATE

Specific to Fanout
Block(s)
Description Output Bias Ramp Rate for function blocks with Multiple Outputs - There is a
separate rate for each output when the initialization path is broken by the user.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OPBIAS[1..8], OPBIAS[1..8].FIX, OPBIAS[1..8].FLOAT
Parameters
Remarks

17.99 OPCHAR

Specific to AOCHANNEL, HAOCHANNEL (PM I/O); AOCHANNEL (Series C I/O)


Block(s)
Description Output Characterization. Specifies whether the output characterization function is
to be used for this data point or not.
Data Type Boolean
Range Off: Output characterization is not to be used. On: Output characterization is to be
used.
Default Off
Config Yes
Load
Active No
Loadable

- 2054 -
Chapter 17 - Oxxxx Parameters

Access Application Developer


Lock
Residence IOM
Related
Parameters
Remarks If OPCHAR is On, you must configure the values for the input coordinates (OPIN1 to
4) and the output coordinates (OPOUT1 to 4). Refer to the Control Builder
Component Theory document for more information on output characterization.
OPCHAR allows the user to ensure that between any two points the OP value
isdetermined by plotting OP to a straight line which connects the two points. Each
point is described as OPIN/OPOUT (X/Y) coordinate and the plotting of OP can be
seen in the OPFINAL parameter.

17.100 OPCMD[0..2]
It is not recommended to use step outputs of type S_IEC, N_IEC, or R_IEC with destination
parameters that are inputs to flip-flops or other bistable, monostable blocks, or logic
configurations. Examples are OPCMD[0..2] of DEVCTL and S and R of LOGIC:RS. Although these
configurations are technically supported and show a predicatable behavior, the resulting behavior
may be non-intuitive and confusing to operators (example: using an N_IEC output on OPCMD[1]
will result in OP-behavior similar to what would be expected from an S_IEC output if directly
controlling a parameter such as OP). Therefore, this practice is not considered a good engineering
practice.

Specific to DevCtl
Block(s)
Description Output Command
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock Program
Residence CEE
Related GOPREQ, OPREQ, OPTYPE.
Parameters
Remarks If all the elements of OPCMD are Off, the OPREQ will be set to SAFEOP. The priority
of the OPCMD is determined by SAFEOP. If SAFEOP = S0, then priority is 0, 1, 2. If
SAFEOP = S1, then priority is 1, 0, 2. If SAFEOP = S2, then priority is 2, 0, 1.

- 2055 -
Chapter 17 - Oxxxx Parameters

17.101 OPCNAME

Specific to Block(s) OPCUASRVUOC


Description OPC Name
Data Type STRING
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEESRAL
Related Parameters None
Remarks

17.102 OPCTYPE

Specific to Block(s) OPCUASRVUOC


Description OPC Type
Data Type ENUM
Range NA
Default
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEESRAL
Related Parameters None
Remarks

17.103 OPCUASRVCONFIG

Specific to Block(s) OPCUASRVUOC


Description OPC UA Server Configuration

Data Type BOOLEAN


Range 0 to 4294967295
Default 0
Config Load Yes
Active Loadable No

- 2056 -
Chapter 17 - Oxxxx Parameters

Access Lock AppDevOnly


Residence CEESRAL
Related Parameters None
Remarks

17.104 OPDOMAP[0..3][1..3]

Specific to Block(s) DevCtl


Description Output (OP) to Digital Output Values (DO) Map of Settable State
Assignments.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters DO[1..3], GOP, GOPFINAL, NUMDOUTSNUMSTATES, OP, OPFINAL, PO
[1..3].
Remarks Illegal if NUMDOUTS = 0. OPDOMAP[2, x] is illegal, if NUMSTATES = 2.

17.105 OPENFEEDBKTIME

Specific to Block VALVEDAMPER


(s)
Description Open Feedback Time in seconds.
Data Type Float64
Range 0 - Max of Real Number
Default 0.0
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related TRKOPENFEEDBKTIME
Parameters
Remarks Time taken to receive OPEN feedback (LTO) after OPEN command
(CMDOpen) is issued

- 2057 -
Chapter 17 - Oxxxx Parameters

17.106 OPEM

Specific to Blocks HRBALG_REG, HRBALG_HLPIUAO, HRBALG_HLPIUAC


Description OP in EU
Data Type FLOAT 64
Range
Default NaN
Config. Load No
Access Lock Operator
Residence NO LOAD
Related Parameters
Remarks This parameter represents Algorithm OP on HRB.

Specific to Blocks HRBALG_REG, HRBALG_HLPIUDO, HRBALG_HLPIUDC


Description OP in EU
Data Type ENUM
Range
Default NaN
Config. Load No
Access Lock Operator
Residence NO LOAD
Related Parameters
Remarks This parameter represents Algorithm OP on HRB.

17.107 OPENIBV

Specific to Block(s) MAINIBV


Description Open command to IBV
Data Type Boolean
Range ON, OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CLOSEMAIN, CLOSEIBV, OPENMAIN
Remarks This out put will be connected to Drive control of IBV.

- 2058 -
Chapter 17 - Oxxxx Parameters

17.108 OPENLOOPRESP

Specific to PID-PL
Block(s)
Description Open-Loop Response Time - The calculated settling time (in minutes) when the
controller is in manual (MODE is MAN). The settling time is the amount of time
required to line out the controller after an OP step change.
Data Type Float64
Range
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CLOSEDLOOPRESP, PRFRATIO
Parameters
Remarks OPENLOOPRESP does not include process deadtime or the effective delay due to
inverse response dynamics. Add these to the OPENLOOPRESP to obtain a more
accurate estimate of the open-loop settling time. This parameter is applicable only
when CTLEQN is set to Profit Loop PKS, and is ignored in PID control equations.

17.109 OPENMAIN

Specific to Block(s) MAINIBV


Description Open command to MAIN
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CLOSEMAIN, CLOSEIBV, OPENIBV.
Remarks This out put will be connected to Drive control of MAIN valve.

- 2059 -
Chapter 17 - Oxxxx Parameters

17.110 OPENPULSEWIDTH

Specific to Block(s) SOLENOID, VALVEDAMPER


Description Open Output Pulsewidth
Data Type Double
Range 0 to 60 seconds
Default 1
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters POCLOSECONNECTEDPOOPENCONNECTED
Remarks Duration for which output should go high as signal for open comes

17.111 OPENSEQ

Specific to Block(s) MAINIBV


Description Open Sequence Command
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters
Remarks

17.112 OPENSEQALM.FL

Specific to Block(s) MAINIBV


Description Open SEQ Fail Alarm Flag
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No

- 2060 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters OPENSEQALM.PR, OPENSEQALM.SV
Remarks

17.113 OPENSEQALM.PR

Specific to Block(s) MAINIBV


Description Open SEQ Fail Alarm Priority
Data Type Enumeration
Range NONE JOURNAL LOW HIGH URGENT
Default Low
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters OPENSEQALM.FL, OPENSEQALM.SV
Remarks

17.114 OPENSEQALM.SV

Specific to Block(s) MAINIBV


Description Open Seq Fail Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters OPENSEQALM.FL, OPENSEQALM.PR,
Remarks

- 2061 -
Chapter 17 - Oxxxx Parameters

17.115 OPENWIRE [0..Number of status in assembly]

Specific to EtherNet/IP [EIP] IOMs: 1738-IB4DM12, 1732E-IB16M12DR


Block(s)
Description Open Wire detection flag — This parameter value changes to ON when the IO
hardware reports Open Wire condition.
Data Type Boolean
Range l Off
l On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related SHORTCIRCUIT
Parameters
Remarks 1732E-IB16M12DR Only — Each index of the parameter represents the combined
status of two channels. For example, if OPENWIRE[0] is ON, then channel 0 or
channel 1 or both are open.

17.116 OPERTAG

Specific to Most RegCtl Blocks: AUTOMAN, ENHREGCALC, FANOUT, OVRDSEL, PID, PID-PL,
Block(s) PIDER, PIDFF, POSPROP, RAMPSOAK, RATIOBIAS, RATIOCTL, REGCALC,
REGSUMMER, REMCAS, SWITCH DevCtl
Description Operator Tag
Data Type BOOLEAN
Range Off, On
Default Off
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related OPERTAGDESC
Parameters
Remarks Allows an operator to tag the block for “operator maintenance”or similar condition.
Control operations of the block are not affected in any way when OPERTAG is On.
Operator Tag is completely independent of REDTAG.

- 2062 -
Chapter 17 - Oxxxx Parameters

17.117 OPERTAGDESC

Specific to Most RegCtl Blocks: AUTOMAN, ENHREGCALC, FANOUT, OVRDSEL, PID, PID-PL,
Block(s) PIDER, PIDFF, POSPROP, RAMPSOAK, RATIOBIAS, RATIOCTL, REGCALC,
REGSUMMER, REMCAS, SWITCH DevCtl
Description Operator Tag
Data Type STRING
Range Length: 15 characters
Default “Operator Tag”
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related OPERTAG
Parameters
Remarks Used to comment why the block's Operator Tag is set.

17.118 OPEU

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDER, PIDFF, PID-PL,
Block(s) PosProp, PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RationCtl,
RegCalc, RegSummer, and Switch.
Description Output Value (in Engineering Units)
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related OP
Parameters
Remarks

Specific to HRBALG_REG block


Blocks
Description Output value in Engineering Units
Data Type FLOAT64
Range Not applicable
Default NaN
Config. No

- 2063 -
Chapter 17 - Oxxxx Parameters

Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks This parameter is applicable for the algorithms such as PIDSPC, PIDCM, and
PIDCMA which supports Supervisory Cascade connection. This parameter is used
for representing the OP value in Engineering Units.

17.119 OPEU

Specific to HRBALG_REG block


Blocks
Description Output value in Engineering Units
Data Type FLOAT64
Range Not applicable
Default NaN
Config. No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks This parameter is applicable for the algorithms such as PIDSPC, PIDCM, and
PIDCMA which supports Supervisory Cascade connection. This parameter is used
for representing the OP value in Engineering Units.

17.120 OPEU[1..8]

Specific to Fanout
Block(s)
Description Output Values (in Engineering Units) for Function Blocks with Multiple Outputs -
There is one value per output.
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active No
Loadable

- 2064 -
Chapter 17 - Oxxxx Parameters

Access Lock Operator


Residence CEE
Related OP[1..8]
Parameters
Remarks

17.121 OPEUMOVE

Specific to PID-PL
Block(s)
Description Change in OPEU Value - The amount of change in the OP (EU) from the previous
execution period.
Data Type Float64
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPEU
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

17.122 OPEUX

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description OPEU Value and Status
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable

- 2065 -
Chapter 17 - Oxxxx Parameters

Access ViewOnly
Lock
Residence CEE
Related OPEU
Parameters
Remarks OPEUX is a hidden connection in Control Builder. Refer to Control Builder
Components Theory, OUTPUT of block specific documentation for more information.
OPEUX is a two-part data structure that contains: OPEU (the output value in
engineering units) and a status component. OPEUX should be used when making a
cascade connection to a secondary control block. The OPEUX connection is
required in order for the initialization path to be established between the primary
and secondary blocks. This parameter will not indicate any value (it shows ****) on
the chart when the pin is exposed.

17.123 OPEUX[1..8]

Specific to Block(s) Fanout


Description OPEU Value and Status for function blocks with multiple outputs.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters OP[1..8], OPEU[1..8]
Remarks

17.124 OPEXHIFL

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Extended High Limit Flag. Indicates if OP is at its extended high limit.
Data Type Boolean
Range Off (0): OP is below its extended high limit. On (1): OP is at its extended high limit.
Default Off (0)
Config Load No
Active No
Loadable

- 2066 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related OPEXHILM
Parameters
Remarks

17.125 OPEXHIFL[1..8]

Specific to Fanout
Block(s)
Description Output (OP) Extended High Limit Flag. Indicate if OP[1..8] are at their extended
high limit.
Data Type Boolean
Range Off (0): Corresponding OP is below its extended high limit. On (1): Corresponding
OP is at its extended high limit.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPEXHILM
Parameters
Remarks

17.126 OPEXHILM

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) Extended High Limit (in percentage)
Data Type 64-Bit Real Number
Range Greater than OPLOLM
Default 106.9%
Config Load Yes
Active No
Loadable

- 2067 -
Chapter 17 - Oxxxx Parameters

Access Lock Engineer


Residence CEE
Related OPEXHIFL
Parameters
Remarks Only the Operator is permitted to specify an Output (OP) value that exceeds the
OPHILM value. Even the operator is prohibited from specifying values greater than
the OPIXHILM, however.

17.127 OPEXLOFL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) Extended Low Limit Flag. Indicates if OP is at its extended low limit.
Data Type Boolean
Range Off (0): OP is above its extended low limit. On (1): OP is at its extended low limit.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPEXLOLM
Parameters
Remarks

17.128 OPEXLOFL[1..8]

Specific to Fanout
Block(s)
Description Output (OP) Extended Low Limit Flag. Indicates if OP[1..8] are at their extended
low limit.
Data Type Boolean
Range Off (0): Corresponding OP is above its extended low limit. On (1): Corresponding
OP is at its extended low limit.
Default Off (0)
Config Load No
Active No
Loadable

- 2068 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related OPEXLOLM
Parameters
Remarks

17.129 OPEXLOLM

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) Extended Low Limit (in percentage)
Data Type 64-Bit Real Number
Range Less than OPHILM
Default -6.9%
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OPEXLOFL
Parameters
Remarks

17.130 OPFINAL

Specific to DevCtl
Block(s)
Description Field Output State
Data Type String
Range Length: 12 characters
Default STATETEXT[4]
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related DO[1..3], GOPFINAL, NUMDOUTS, NUMSTATES, NUMTRANS, OPDOMAP[0..3][1..3],
Parameters SEALOPT, STATETEXT[0..6], STATETIME[0..2].
Remarks OPFINAL is a String set equal to STATETEXT (GOPFINAL). Access is illegal if
NUMDOUTS = 0. STATETEXT[6] [‘State2’] is illegal if NUMSTATES = 2.

- 2069 -
Chapter 17 - Oxxxx Parameters

Specific to AO8, AO16, AO16HART


Block(s)
Description Output Final. Shows the final output value sent to the control element after direct
or reverse control action and output characterization have been applied.
Data Type 64-Bit Real Number
Range N/A
Default -6.9 percent of Full Scale
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks If OPTDIR parameter configuration is DIRECT, 0.0 percent OP represents 4mA and
100 percent OP represents 20mA. If OPTDIR parameter configuration is REVERSE,
0.0 percent OP represents 20mA and 100 percent OP represents 4mA.

Specific to PBAOCHANNEL, AOCHANNEL, HAOCHANNEL, Series C AOCHANNEL


Block(s)
Description Final Percent Output (Sent to Control Element)
Data Type FLOAT32
Range
Default -6.9% of Full
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is the output value after direct or reverse control action and output
characterization have all been applied. If output has been configured for direct
action (OPTDIR), 0.0% represents 4 mA to the control element and 100%
represents 20 mA. 18.110.1 If configured for reverse action, 0.0% represents 20
mA, and 100% represents 4 mA

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Field Output State
Data Type Self-Defining Enumeration
Range HTMOTOR, LTMOTOR: SAFE RUN STOP SOLENOID: SAFE OPEN CLOSE
VALVEDAMPER: SAFE OPEN CLOSE NOCOMMAND
Default HTMOTOR, LTMOTOR: STOP SOLENOID: CLOSE VALVEDAMPER: NOCOMMAND
Config Load No

- 2070 -
Chapter 17 - Oxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CMDRUN, CMDSTOP, CMDCLOSE, CMDOPEN, GOPFINAL, NUMTRANS SEALOPT
Parameters
Remarks OPFINAL is a String set equal to STATETEXT (GOPFINAL)

17.131 OPFINAL_AO_S

Specific to UIO
Block(s)

Description Final Output Value


Data Type FLOAT32
Range N/A
Default -6.9% of Full
Config Load No

Active No
Loadable

Access Lock ViewOnly

Residence UIO
Related N/A
Parameters

Remarks This parameter is the output value after direct or reverse control action is applied.
If output has been configured for direct action (DIRECTION_AO_C), 0.0% represents 4 mA
to the control element and 100% represents 20 mA.

If configured for reverse action, 0.0% represents 20 mA, and 100% represents 4 mA

Specific to UIO, AO04, AO08


Block(s)

Description Final Output Value


Data Type FLOAT32
Range N/A
Default -6.9% of Full
Config Load No

Active
Loadable

- 2071 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly

Residence IOM Block


Related N/A
Parameters

Remarks This parameter is the output value after direct or reverse control action is
applied.
If output has been configured for direct action (DIRECTION_AO_C), 0.0% represents 4 mA
to the control element and 100% represents 20 mA.
If configured for reverse action, 0.0% represents 20 mA, and 100% represents 4 mA

17.132 OPFINAL[0..numChans-1]

Specific to Block(s) AOM


Description Adjusted Output Value.
Data Type 64-Bit Real Number
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

17.133 OPFINAL[0..numChans-1]

Specific to EIP Analog Output Modules


Block(s)
Description Final Output Value— Represents the final output value sent to the IO module after
scaling based on OPFINALLORANGE and OPFINALHIRANGE has been applied on
OP.
Data Type INT32
Range

Default 0
Config Load
Active No
Loadable

- 2072 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence NoLoad
Related l OPFINALLORANGE
Parameters
l OPFINALHIRANGE
l OP
Remarks It is indexed by the channel number.

17.134 OPFINALHIRANGE [0..numChans-1]

Specific to EIP Analog Output Modules


Block(s)
Description High Range for OPFINAL— Specifies the high end value of the normal operating
range for the OPFINAL parameter.
Data Type INT32
Range OPFINALHIRANGE must be greater than OPFINALLORANGE

Default 0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks It is indexed by the channel number.

17.135 OPFINALLORANGE [0..numChans-1]

Specific to EIP Analog Output Modules


Block(s)
Description Low Range for OPFINAL— Specifies the low end value of the normal operating
range for the OPFINAL parameter.
Data Type INT32
Range OPFINALLORANGE must be less than OPFINALHIRANGE

Default 0
Config Load Yes
Active No
Loadable

- 2073 -
Chapter 17 - Oxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related None
Parameters
Remarks It is indexed by the channel number.

17.136 OPFL[0..numChans-1]

Specific to Block(s) EIP Digital Output modules


Description Final Output — Represents the Output Value being sent to the device.
Data Type BOOLEAN
Range l Off (0)
l On (1)
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters None
Remarks It is indexed by channel number.

17.137 OPHIACTIVE

Specific to PID-PL
Block(s)
Description OP (output) High Limit Active - Upper OP limit used by the Profit Loop PKS control
algorithm. This value may differ from the user-entered limit, OPHILM, if controller
windup exists.
Data Type Float64
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPHILM, OPLOACTIVE.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

- 2074 -
Chapter 17 - Oxxxx Parameters

17.138 OPHIALM.DB

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) High Alarm Deadband
Data Type 64-Bit Real Number
Range 0.0 to 100.0 if alarm deadband units (OPHILAM.DBU) are Percent. CVEULO to
CVEUHI if alarm deadband units (OPHIALM.DBU) are Engineering Units.
Default 0.0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related OP, OPHIALM.DBU, OPHIALM.FL, OPHIALM.PR, OPHIALM.SV, OPHIALM.TM,
Parameters OPHIALM.TP.
Remarks The following rule is applied to OPHIALM.DB to prevent OPHI and OPLO alarm that
are both active at the same time: OPHIALM.DB <= (OPHIALM.TP - OPLOALM.TP)/2
(or OPLOALM.TP <= OPHIALM.TP - (2*OPLOALM.DB)) For more information about
alarm configuration, refer to Control Builder Components Theory Guide.

17.139 OPHIALM.DBU

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) High Alarm Deadband Units - Indicates if OPHILAM.DB is in Percent or
Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU (1)
Default Percent (0)
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related OP, OPHIALM.DB, OPHIALM.FL, OPHIALM.PR, OPHIALM.SV, OPHIALM.TM,
Parameters OPHIALM.TP.
Remarks For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 2075 -
Chapter 17 - Oxxxx Parameters

17.140 OPHIALM.FL

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description OP High Alarm Flag
Data Type Boolean
Range Off (0) (not in OP High alarm) On (1) (in Op High alarm)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OP, OPHIALM.DB, OPHIALM.DBU, OPHIALM.PR, OPHIALM.SV, OPHIALM.TM,
Parameters OPHIALM.TP.
Remarks

17.141 OPHIALM.PR

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) High Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OP, OPHIALM.DB, OPHIALM.DBU, OPHIALM.FL, OPHIALM.SV, OPHIALM.TM,
Parameters OPHIALM.TP.
Remarks

- 2076 -
Chapter 17 - Oxxxx Parameters

17.142 OPHIALM.SV

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) High Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OP, OPHIALM.DB, OPHIALM.DBU, OPHIALM.FL, OPHIALM.PR, OPHIALM.TM,
Parameters OPHIALM.TP.
Remarks

17.143 OPHIALM.TM

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) High Alarm Filter Time (in seconds) - The purpose of this variable is to
prevent input spikes from causing OP High alarms. An alarm will only be generated
if the OP consistently exceeds the high trip point for more than the configured
alarm filter time.
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related OP, OPHIALM.DB, OPHIALM.DBU, OPHIALM.FL, OPHIALM.PR, OPHIALM.SV,
Parameters OPHIALM.TP.
Remarks If OPHIALM.TM = 0, alarm will be generated as soon as OP exceeds the high trip
point. For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 2077 -
Chapter 17 - Oxxxx Parameters

17.144 OPHIALM.TMO

Specific to AUTOMAN, OVRDSEL, PID, PID-PL, PIDER, PIDFF, POSPROP, RAMPSOAK,


Block(s) REMCAS, RATIOBIAS, REGCALC, REGSUMMER, SWITCH.
Description Output (OP) High Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for Output (OP)
High Alarm.

17.145 OPHIALM.TP

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) High Alarm Trip Point (in Percent)
Data Type 64-Bit Real Number
Range NaN, or OPLOLM to OPEXHILM
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OP, OPHIALM.DB, OPHIALM.DBU, OPHIALM.FL, OPHIALM.PR, OPHIALM.SV,
Parameters OPHIALM.TP.
Remarks If OPHIALM.TP = NaN, OP high alarms are inhibited. The following rule is applied to
OPHIALM.DB to prevent OPHI and OPLO alarm that are both active at the same
time: OPLOALM.TP <= OPHIALM.TP - (2 * OPLOALM.DB) (or OPHIALM.DB <=
(OPHIALM.TP - OPLOALM.TP)/2 )

- 2078 -
Chapter 17 - Oxxxx Parameters

17.146 OPHIFL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) High Limit Flag - Indicates if OP has reached the high limit, as
specified by OPHILM.
Data Type Boolean
Range Off (0): Output has not reached the high limit. On (1): Output has reached the high
limit.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPHILM
Parameters
Remarks

17.147 OPHIFL[1..8]

Specific to Fanout
Block(s)
Description Output (OP) High Limit Flag - Indicates if OP[1..8] have reached the high limit,
as specified by OPHILM.
Data Type Boolean
Range Off (0): Output has not reached the high limit. On (1): Output has reached the
high limit.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related OPHILM
Parameters
Remarks

- 2079 -
Chapter 17 - Oxxxx Parameters

17.148 OPHIGH.FL

Specific to Block(s) PROFCONOUT


Description OPHIGH FL
Data Type BOOL
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters OPLOW.FL
Remarks OPHIGH FL

17.149 OPHILM

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) High Limit (in percentage)
Data Type 64-Bit Real Number
Range NaN, or OPLOLM to OPEXHILM
Default 105.0%
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OPHIFL
Parameters
Remarks Entering NaN disables limit checking. Only the operator is permitted to specify an
OP value that exceeds the OPHILM value. Programs (SCM, and so on) can specify
output values up to the OPHILM limit. If values larger than this are requested, then
they are clamped at the OPHILM value.

- 2080 -
Chapter 17 - Oxxxx Parameters

17.150 OPHILMOPT

Specific to PID-PL
Block(s)
Description OP High Limit for Optimization - Defines an upper limit for optimization.
Data Type Float64
Range
Default
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CTLEQN, CTRLMODE,CTRLMODE OPTDIR, OPHILM, OPHIOPTOFFSET, OPLOLM,
Parameters OPHILMOPT, OPTMODE
Remarks Profit Loop PKS can be configured to optimize the process over a limited operating
range. As a guard against process excursions, the range used for optimization,
OPLOLMOPT to OPHILMOPT, may be more restrictive than the normal control
range, OPLOLM to OPHILM. OPHILMOPT is calculated as: OPHILMOPT = OPHILM
- OPHIOPTOFFSET If a conflict exists between the OP optimization limits and the SP
optimization limits, the SP limits are enforced; the OP limits are ignored. This
parameter is applicable only when OPTMODE is other than NONE and CTRLMODE
is RANGE. This parameter is applicable only when CTLEQN is set to Profit Loop PKS,
and is ignored in PID control equations.

17.151 OPHIOPTOFFSET

Specific to PID-PL
Block(s)
Description OP High Limit Offset for Optimization - Offset applied to OPHILM to restrict the
range over which the Profit Loop PKS algorithm optimizes.
Data Type Float64
Range ≥0
Default 0
Config Yes
Load
Active No
Loadable

- 2081 -
Chapter 17 - Oxxxx Parameters

Access Engineer
Lock
Residence CEE
Related CTLEQN, CTRLMODE,CTRLMODE OPTDIR, OPHILMOPT, OPLOLM, OPHILMOPT,
Parameters OPTMODE
Remarks Profit Loop PKS can be configured to optimize the process over a limited operating
range. To guard against process excursions, the range used for optimization,
OPLOLMOPT to OPHILMOPT, may be more restrictive than the normal control
range, OPLOLM to OPHILM. OPHILMOPTis calculated as: OPHILMOPT = OPHILM -
OPHIOPTOFFSET If a conflict exists between the OP optimization limits and the SP
optimization limits, the SP limits are enforced while the OP limits are ignored. This
parameter is applicable only when OPTMODE is other than NONE and CTRLMODE
is RANGE. This parameter is applicable only when CTLEQN is set to Profit Loop PKS,
and is ignored in PID control equations.

17.152 OPIN

Specific to Block UCNOUT, HIWAYOUT


(s)
Description Output Value in Percent Input - Shows the value brought from the primary in
percent.
Data Type Float64
Range -6.9 to 106.9 percent
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related OPOUT, RELEASEOPT, MODEOUT
Parameters
Remarks

17.153 OPIN0

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Input Coordinate Number 0. Defines the number 0 Input coordinate in percent for
the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range N/A
Default Fixed at -6.9 percent
Config Load Yes
Active No
Loadable

- 2082 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks This paramter can only be set when PTEXECST is INACTIVE.

17.154 OPIN1

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Input Coordinate Number 1. Specifies the number 1 Input coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range Greater than previous coordinate; Less than next coordinate.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related
Parameters
Remarks This paramter can only be set when PTEXECST is INACTIVE.

17.155 OPIN2

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Input Coordinate Number 2. Specifies the number 2 Input coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range Greater than previous coordinate; Less than next coordinate.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related
Parameters
Remarks This paramter can only be set when PTEXECST is INACTIVE.

- 2083 -
Chapter 17 - Oxxxx Parameters

17.156 OPIN3

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Input Coordinate Number 3. Specifies the number 3 Input coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range Greater than previous coordinate; Less than next coordinate.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related PTEXECST
Parameters
Remarks This paramter can only be set when PTEXECST is INACTIVE.

17.157 OPIN4

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Input Coordinate Number 1. Specifies the number 1 Input coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range Greater than previous coordinate; Less than next coordinate.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related PTEXECST
Parameters
Remarks This paramter can only be set when PTEXECST is INACTIVE.

- 2084 -
Chapter 17 - Oxxxx Parameters

17.158 OPIN5

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Input Coordinate Number 5. Defines the number 5 Input coordinate in percent for
the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range N/A
Default Fixed at 106.9 percent
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related OPCHAR
Parameters
Remarks

17.159 OPINCONNHNDL[1..16][1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

17.160 OPINCONNNAV[1..16][1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO

- 2085 -
Chapter 17 - Oxxxx Parameters

Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

17.161 OPINCONNPRM[1..16][1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable NO
Access Lock
Residence
Related Parameters
Remarks

17.162 OPINCONNSTRVAL[1..16][1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2086 -
Chapter 17 - Oxxxx Parameters

17.163 OPINCONNVAL[1..16][1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

17.164 OPINITVAL

Specific to DOCHANNEL (PM I/O) DOCHANNEL (Series C I/O)


Block(s)
Description OP Initialize Value. Defines the pulsed output value from the IOP in percent.
Data Type 64-Bit Real Number
Range 0.0 to 100.0 percent
Default 0.0 percent
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related OP, DOTYPE
Parameters
Remarks The data is available only when DOPTYPE is configured as PWM. Pulse on-time is
calculated as follows. For DIRECT action: Pulse On-Time = (OP percent x PERIOD) /
100 For REVERSE action: Pulse On-Time = (100 percent - OP percent x PERIOD) /
100

- 2087 -
Chapter 17 - Oxxxx Parameters

17.165 OPINITVAL[0..numChans-1]

Specific to Block(s) EIP Digital Output modules


Description Echo Back value Initialization Value - The value to which a primary should
initialize.
Data Type BOOLEAN
Range l Off (0)
l On (1)
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related None
Parameters
Remarks It is indexed by channel number.

17.166 OPLOACTIVE

Specific to PID-PL
Block(s)
Description Active OP Low Limit - Lower OP limit used by the Profit Loop PKS control algorithm.
This value may differ from the user-entered limit, OPLOLM, if controller windup
exists.
Data Type Float64
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CTLEQN, OPHIACTIVE, OPLOLM.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

- 2088 -
Chapter 17 - Oxxxx Parameters

17.167 OPLOALM.DB

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Low Alarm Deadband
Data Type 64-Bit Real Number
Range 0.0 to 100.0 if alarm deadband units (OPLOALM.DBU) are Percent. CVEULO to
CVEUHI if alarm deadband units (OPLOALM.DBU) are EUs.
Default 0.0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related OP, OPLOALM.DBU, OPLOALM.FL, OPLOALM.PR, OPLOALM.SVOPLOALM.TM,
Parameters OPLOALM.TP.
Remarks The following restriction is applied to OPLOALM.DB to prevent OPHI and OPLO
alarm that are both active at the same time: OPLOALM.DB <= (OPHIALM.TP -
OPLOALM.TP)/2 (or OPHIALM.TP >= OPLOALM.TP + (2* OPHIALM.DB)) For more
information about alarm configuration, refer to Control Builder Components Theory
Guide.

17.168 OPLOALM.DBU

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Low Alarm Deadband Units - Indicates if OPLOALM.DB is in Percent or
Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU (1)
Default Percent (0)
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related OP, OPLOALM.DB, OPLOALM.FL, OPLOALM.PR, OPLOALM.SV, OPLOALM.TM,
Parameters OPLOALM.TP.
Remarks For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 2089 -
Chapter 17 - Oxxxx Parameters

17.169 OPLOALM.FL

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Low Alarm Flag
Data Type Boolean
Range Off (0): Not in OP Low alarm. On (1): In OP Low alarm.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OP, OPLOALM.DB, OPLOALM.DBU, OPLOALM.PR, OPLOALM.SV, OPLOALM.TM,
Parameters OPLOALM.TP.
Remarks

17.170 OPLOALM.PR

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Low Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Engineer
Active No
Loadable
Access Lock Yes
Residence CEE
Related OP, OPLOALM.DB, OPLOALM.FL, OPLOALM.SV, OPLOALM.TM, OPLOALM.TP.
Parameters
Remarks

- 2090 -
Chapter 17 - Oxxxx Parameters

17.171 OPLOALM.SV

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, Regsummer,
and Switch.
Description Output (OP) Low Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OP, OPLOALM.DB, OPLOALM.DBU, OPLOALM.FL, OPLOALM.PROPLOALM.TM,
Parameters OPLOALM.TP.
Remarks

17.172 OPLOALM.TM

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Low Alarm Filter Time (in seconds) - The purpose of this variable is to
prevent input spikes from causing OP Low alarms. An alarm will only be generated
if the OP is consistently below the low trip point for more than the configured alarm
filter time.
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related OP, OPLOALM.DB, OPLOALM.DBU, OPLOALM.FL, OPLOALM.PR, OPLOALM.SV,
Parameters OPLOALM.TP.
Remarks If OPLOALM.TM = 0, an alarm will be generated as soon as OP falls below the low
trip point. For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 2091 -
Chapter 17 - Oxxxx Parameters

17.173 OPLOALM.TMO

Specific to AUTOMAN, OVRDSEL, PID, PID-PL, PIDER, PIDFF, POSPROP, RAMPSOAK,


Block(s) REMCAS, RATIOBIAS, REGCALC, REGSUMMER, SWITCH.
Description Output (OP) Low Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure individual off-delay time for Output (OP)
High Alarm.

17.174 OPLOALM.TP

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Low Alarm Trip Point (in percentage)
Data Type 64-Bit Real Number
Range NaN, or OPEXLOLM to OPEXHILM
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OP, OPLOALM.DB, OPLOALM.DBU, OPLOALM.FL, OPLOALM.PR, OPLOALM.SV,
Parameters OPLOALM.TM.
Remarks If OPLOALM.TP = NaN, OP low alarms are inhibited. The following restriction is
applied to OPLOALM.TP to prevent OPHI and OPLO alarm that are both active at
the same time: OPHIALM.TP >= OPLOALM.TP + (2 * OPHIALM.DB) (or
OPLOALM.DB <= ( OPHIALM.TP - OPLOALM.TP)/2)

- 2092 -
Chapter 17 - Oxxxx Parameters

17.175 OPLOFL

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Low Limit Flag - Indicates if OP has reached its low limit, as specified by
OPLOLM.
Data Type Boolean
Range Off (0): Output has not reached the low limit. On (1): Output has reached the low
limit.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPLOLM
Parameters
Remarks

17.176 OPLOFL[1..8]

Specific to Block Fanout


(s)
Description Output (OP) Low Limit Flag - Indicates if OP[1..8] have reached its low limit, as
specified by OPLOLM.
Data Type Boolean
Range Off (0): Output has not reached the low limit. On (1): Output has reached the
low limit.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related OPLOLM
Parameters
Remarks

- 2093 -
Chapter 17 - Oxxxx Parameters

17.177 OPLOLM

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) Low Limit (in percentage)
Data Type 64-Bit Real Number
Range NaN, or OPEXLOLM to OPHILM
Default -5.0%
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OPLOFL
Parameters
Remarks Entering NaN disables limit checking.

17.178 OPLOLMOPT

Specific to PID-PL
Block(s)
Description Lower OP Limit for Optimization
Data Type Float64
Range
Default
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CTLEQN, CTRLMODE CTRLMODE, OPTDIR, OPHILM, OPHILMOPTOPLOLM,
Parameters OPLOOPTOFFSET, OPTMODE
Remarks Profit Loop PKS can be configured to optimize the process over a limited operating
range. As a guard against process excursions, the range used for optimization,
OPLOLMOPT to OPHILMOPT, may be more restrictive than the normal control
range, OPLOLM to OPHILM. OPLOLMOPT is calculated as: OPLOLMOPT =
OPLOLM + OPLOOPTOFFSET If a conflict exists between the OP optimization limits
and the SP optimization limits, the SP limits are enforced while the OP limits are
ignored. This parameter is applicable only when OPTMODE is other than NONE and
CTRLMODE is RANGE. This parameter is applicable only when CTLEQN is set to
Profit Loop PKS, and is ignored in PID control equations.

- 2094 -
Chapter 17 - Oxxxx Parameters

17.179 OPLOOPTOFFSET

Specific to PID-PL
Block(s)
Description OP Low Limit Offset for Optimization - Offset applied to OPLOLM to restrict the
range over which the Profit Loop PKS algorithm optimizes.
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related CTLEQN, CTRLMODE CTRLMODE, OPTDIR, OPHILM,
Parameters OPHILMOPTOPHIOPTOFFSET, OPLOLM, OPLOLMOPT, OPTMODE
Remarks Profit Loop PKS can be configured to optimize the process over a limited operating
range. As a guard against process excursions, the range used for optimization,
OPLOLMOPT to OPHILMOPT, may be more restrictive than the normal control
range, OPLOLM to OPHILM. OPLOLMOPT is calculated as: OPLOLMOPT =
OPLOLM + OPLOOPTOFFSET If a conflict exists between the OP optimization limits
and the SP optimization limits, the SP limits are enforced while the OP limits are
ignored. This parameter is applicable only when OPTMODE is other than NONE and
CTRLMODE is RANGE. This parameter is applicable only when CTLEQN is set to
Profit Loop PKS, and is ignored in PID control equations.

17.180 OPLOW.FL

Specific to Block(s) PROFCONOUT


Description OPLOW FL
Data Type BOOL
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters OPHIGH.FL
Remarks OPLOW FL

- 2095 -
Chapter 17 - Oxxxx Parameters

17.181 OPMINCHG

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) Minimum Change Limit (in Percent)
Data Type 64-Bit Real Number
Range NaN, or a real number greater than or less than zero.
Default 0.0%
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OP
Parameters
Remarks Defines the minimum amount that the output must change before the function
blocks actually change the OP. If this value is NaN, then there is no minimum limit
set. Entering NaN disables limit checking.

17.182 OPNUMSRCCONN[1..16]

Specific to Step Block


Block(s)
Description Number of Source Connections for Output expression. Represents number of
source references in the expression of Output i, where i is the parameter index
from 1..16.
Data Type Integer32
Range 0 to 200
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence ACE, C200, SIM_C200
Related OPPCODESIZE[1..16]
Parameters
Remarks

- 2096 -
Chapter 17 - Oxxxx Parameters

17.183 OPOUT0

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Output Coordinate Number 0. Defines the number 0 Output coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range N/A
Default Fixed at -6.9 percent
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter can only be set when PTEXECST is INACTIVE. See the Control
Builder Component Theory document for more information.

17.184 OPOUT1

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Output Coordinate Number 1. Specifies the number 1 output coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range Greater than previous coordinate; Less than next coordinate
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence IOM
Related
Parameters
Remarks This parameter can only be set when PTEXECST is INACTIVE. See the Control
Builder Component Theory document for more information.

- 2097 -
Chapter 17 - Oxxxx Parameters

17.185 OPOUT2

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Output Coordinate Number 2. Specifies the number 2 Output coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range Greater than previous coordinate; Less than next coordinate
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence IOM
Related
Parameters
Remarks This parameter can only be set when PTEXECST is INACTIVE. See the Control
Builder Component Theory document for more information.

17.186 OPOUT3

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Output Coordinate Number 3. Specifies the number 3 Output coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range Greater than previous coordinate; Less than next coordinate.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence IOM
Related
Parameters
Remarks This parameter can only be set when PTEXECST is INACTIVE. See the Control
Builder Component Theory document for more information.

- 2098 -
Chapter 17 - Oxxxx Parameters

17.187 OPOUT4

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Output Coordinate Number 4. Specifies the number 4 Output coordinate in percent
for the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range Greater than previous coordinate; Less than next coordinate.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence IOM
Related
Parameters
Remarks This parameter can only be set when PTEXECST is INACTIVE. See the Control
Builder Component Theory document for more information.

17.188 OPOUT5

Specific to AOCHANNEL, HAOCHANNEL (PM I/O) AOCHANNEL (Series C I/O)


Block(s)
Description Input Coordinate Number 5. Defines the number 5 Input coordinate in percent for
the output when the OPCHAR parameter is On.
Data Type 32-Bit Real Number
Range N/A
Default Fixed at 106.9 percent
Config Load Yes
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

- 2099 -
Chapter 17 - Oxxxx Parameters

17.189 OPOUT

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Output Value sent to UCN - Indicates the output value that is being stored to the
UCN Process Manager in percent.
Data Type Floata64
Range -6.9 to 106.9 percent
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related OPIN, RELEASEOPT, REMCASTYPE
Parameters
Remarks

17.190 OPPCODESIZE[1..16]

Specific to Step Block


Block(s)
Description Number of Pcode Bytes for Output expression. Represents number of bytes
required for the Psuedo code for the expression of Output i, where i is the
parameter index from 1..16.
Data Type Integer32
Range 0 to 200
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence ACE, C200, SIM_C200
Related OPNUMSRCCONN[1..16]
Parameters
Remarks

- 2100 -
Chapter 17 - Oxxxx Parameters

17.191 OPREQ

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description The requested OP (Output) value. The SCM CONTROLREQ wants to change the
regulatory control block's output (OP).
Data Type 64-Bit Real Number
Range OPEXLOLM to OPEXHILM
Default 0
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related CONTROLREQ, HOLDOPT, LASTOPMNAME, LASTOPREQ, LASTOPTYPE,
Parameters RESTARTOPT, SCMOPT, STOPOPT.
Remarks OPREQ is illegal if ControlModule. SCMOPT ≠ Fixed. While MODEATTR is Operator, a
pending OPREQ can be terminated by the operator setting it to NaN.

Specific to DevCtl
Block(s)
Description The Output State Requested
Data Type String
Range Length: 12 characters
Default STATETEXT[0]
Config No
Load
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related GOP, GOPREQ, HOLDOPT, LASTOPMNAME, LASTOPREQ, MODEATTR,
Parameters NUMSTATES, OP, OPTYPE, RESTARTOPT, SAFEOP, STARTOPT, STATETEXT[0..6],
STOPOPT.
Remarks OPREQ is a String set equal to STATETEXT(GOPREQ). If OPTYPE = Set, and
MODEATTR is Operator, the Engineer may change OPREQ. STATETEXT[6] is illegal
if NUMSTATES = 2 If OPTYPE = Set, any output requests from external blocks
change the OPREQ value. Note that if the MODEATTR is Operator, and the
Engineer tries to change the OPREQ value, an error message appears.

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description The Output State Requested
Data Type Self-Defining Enumeration
Range HTMOTOR, LTMOTOR: BAD SAFE RUN STOP SOLENOID: BAD SAFE OPEN CLOSE
VALVEDAMPER: BAD SAFE OPEN CLOSE NOCOMMAND
Default BAD

- 2101 -
Chapter 17 - Oxxxx Parameters

Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related GOP, GOPREQ, HOLDOPT, LASTOPMNAME, LASTOPREQ, MODEATTR,
Parameters NUMSTATES, OP, OPTYPE, RESTARTOPT, SAFEOP, STARTOPT, STATETEXT[0..6],
STOPOPT.
Remarks OPREQ is a String set equal to STATETEXT(GOPREQ). If OPTYPE = Set, and
MODEATTR is Operator, the Engineer may change OPREQ.

17.192 OPROCLM

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) Rate of Change Limit (in Percent per minute)
Data Type 64-Bit Real Number
Range NaN, or Greater-than or equal-to 0.1
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related OPROCNEGFL, OPROCPOSFL.
Parameters
Remarks Entering NaN disables limit checking.

17.193 OPROCNEGFL

Specific to All RegCtl Blocks except Fanout: AutoMan, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Output (OP) Negative Rate of Change Flag
Data Type Boolean
Range Off (0): OP negative rate of change is above the limit. On (1): OP negative rate of
change is less-than or equal-to the limit.
Default Off (0)
Config Load No
Active No
Loadable

- 2102 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related OPROCLM
Parameters
Remarks

17.194 OPROCNEGFL[1..8]

Specific to Fanout
Block(s)
Description Output (OP) Negative Rate of Change Flag
Data Type Boolean
Range Off (0): OP negative rate of change is above the limit. On (1): OP negative rate of
change is below or equal to the the limit.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPROCLM
Parameters
Remarks This flag is set when the Output rate of change exceeds OPROCLM in the
negative direction

17.195 OPROCPOSFL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Output (OP) Positive Rate of Change Flag
Data Type Boolean
Range Off (0): OP positive rate of change is below the limit. On (1): OP positive rate of
change is above or equal to the limit.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OPROCLM
Parameters
Remarks

- 2103 -
Chapter 17 - Oxxxx Parameters

17.196 OPROCPOSFL[1..8]

Specific to Block Fanout


(s)
Description Output (OP) Positive Rate of Change Flag
Data Type Boolean
Range Off (0): OP positive rate of change is < the limit. On (1): OP positive rate of
change is >= the limit.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related OPROCLM
Parameters
Remarks This flag is set when the Output rate of change exceeds OPROCLM in the
positive direction.

17.197 OPSECDATA

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active No
Loadable
Access Lock
Residence
Related
Parameters
Remarks

- 2104 -
Chapter 17 - Oxxxx Parameters

17.198 OPSECDATA[1..8]

Specific to Block(s) Fanout


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

17.199 OPSECDATA.ARWSTS

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description
Data Type Integer
Range N/A
Default 0
Config Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

17.200 OPSECDATA.EUHI

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description
Data Type Real
Range N/A
Default NaN

- 2105 -
Chapter 17 - Oxxxx Parameters

Config Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

17.201 OPSECDATA.EULO

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description
Data Type Real
Range N/A
Default NaN
Config Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

17.202 OPSECDATA.INITREQ

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load
Active No
Loadable

- 2106 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence
Related
Parameters
Remarks

17.203 OPSECDATA.INITVAL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description
Data Type Real
Range N/A
Default NaN
Config Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

17.204 OPSECDATA.ONESHOT

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description
Data Type Integer
Range N/A
Default 0
Config Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

- 2107 -
Chapter 17 - Oxxxx Parameters

17.205 OPSECDATA.ORFBVA

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

17.206 OPSECDATA.OROFFS

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks

17.207 OPSOURCE

Specific to Block(s) AOC, PWM Channel


Description Output Source Connector
Data Type
Range

- 2108 -
Chapter 17 - Oxxxx Parameters

Default
Config Load
Active Loadable No
Access Lock Application Developer
Residence
Related Parameters
Remarks

17.208 OPSRC[1..16][1..6]

Specific to Block(s) Step


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

17.209 OPSTOREHNDL[1..16]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2109 -
Chapter 17 - Oxxxx Parameters

17.210 OPSTORENAV[1..16]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

17.211 OPSTOREPRM[1..16]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable NO
Access Lock
Residence
Related Parameters
Remarks

17.212 OPSTORESTRVAL[1..16]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO

- 2110 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence
Related Parameters
Remarks

17.213 OPSTOREVAL[1..16]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

17.214 OPTACCELTOL

Specific to Block(s) ProfitCtl


Description Opt Accel Tol
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

- 2111 -
Chapter 17 - Oxxxx Parameters

17.215 OPTDIR

Specific to PWMCHANNEL (PM I/O, IO Channel)


Block(s)
Description Output Direction. Direct or Reverse mode settings for the PWM Channel define the
output action to be applied to an associated digital output. The input connection
(OP) coming into PWM Channel Block Function Block is always scaled from 0-100%.
The OPTDIR in direct mode will cause the block to pass the unchanged OP value
directly to the control element as a percentage of on/off time. The initialization
value returning from the control element will also not be changed. When reverse
mode is selected, the OP to the control element is rescaled before final output as
follows: OPFINAL = 100 - OP. The initialization value is also converted so that
INITVAL is consistent with OP. The PWM Channel gauges on/off time for the
assigned digital output according to the PWM Period (PWMPERIOD), the input
percentage (OP), and the output direction (OPTDIR). When the direct mode is
specified, the digital output is set ON for the input percentage portion of time
determined by the PWM period. The remaining period time the digital output is set
OFF. The digital output is cycled in this manner. When the reverse mode is
specified, the digital output is set OFF for the input percentage portion of time
determined by the PWM period. The remaining period time the digital output is set
ON. The digital output is cycled in this manner. The PWM Channel initialization
value (INITVAL) is also converted in reverse mode so that is consistent with the OP
input.
Data Type Enumeration
Range DIRECT(0): OP is the percent On time. REVERSE(1): OP is the percent Off time.
Default DIRECT(0)
Config Yes
Load
Active No
Loadable
Access Engineer/Application Developer
Lock
Residence CEE
Related OP, OPFINAL, PWMPERIOD
Parameters
Remarks

Specific to AOCHANNEL , HAOCHANNEL (PM I/O) AOCHANNEL, (Series C I/O)


Block(s)
Description Output Direction. Direct or Reverse mode settings define the output action to be
applied to OP that determines the OPFINAL value used to control the actual field
device. The output (OP) coming into the AO Channel Function Block is always scaled
from 0-100%. The OPTDIR in direct mode will cause the block to pass the
unchanged OP value directly to the control element. The initialization value
returning from the control element will also not be changed. When reverse mode is
selected, the OP to the control element is rescaled before final output as follows:
OPFINAL = 100 - OP. The initialization value is also converted so that INITVAL is
consistent with OP.
Data Type Enumeration
Range 0 DIRECT Example: For OPFINAL,
0% = 4mA and 100% =
20mA.
1 REVERSE Example: For OPFINAL,

- 2112 -
Chapter 17 - Oxxxx Parameters

0% = 20mA and 100% =


4mA.
Default DIRECT (0)
Config Yes
Load
Active No
Loadable
Access Engineer/Application Developer
Lock
Residence CEE
Related OP, OPFINAL
Parameters
Remarks

Specific to Block(s) DOCHANNEL, Series C DOCHANNEL


Description Output Direction
Data Type Enumeration
Range 0 DIRECT OP is the % On time
1 REVERSE OP is the % Off time
Default DIRECT
Config Load Yes
Active Loadable No
Access Lock Engineer/Application Developer
Residence IOM
Related Parameters
Remarks This parameter defines the direct/reverse action of the PWM digital output.

17.216 INPTDIR_AO_C

Specific to Block(s) UIO


Description Output Direction
Data Type ENUM
Range
0 DIRECT For final OP: 0% = 4 mA; 100% = 20 mA

1 REVERSE For final OP: 0% = 20 mA; 100% = 4 mA

Default Direct
Config Load Yes
Active Loadable No

- 2113 -
Chapter 17 - Oxxxx Parameters

Access Lock Engineer / Application Developer


Residence UIO
Related Parameters N/A

Remarks This parameter defines the output action of the OPFINAL value of the data point.

Specific to Block(s) UIO, AO04, AO08


Description Output Direction
Data Type ENUM
Range
0 DIRECT For final OP: 0% = 4 mA; 100% = 20 mA

1 REVERSE For final OP: 0% = 20 mA; 100% = 0 mA

Default Direct
Config Load Yes
Active Loadable

Access Lock Engineer / Application Developer


Residence IOM Block
Related Parameters N/A

Remarks This parameter defines the output action of the OPFINAL value of the data point.

17.217 OPTFIELDS

Specific to EIM
Block(s)
Description Fields
Data Type BITSTRING
Range
Default
Config
Load
Active No
Loadable

- 2114 -
Chapter 17 - Oxxxx Parameters

Access AppDevOnly
Lock
Residence EIM
Related
Parameters
Remarks The attribute OptFlds shall be the client-specified optional fields to be included in
the report issued by this BRCB. This attribute defines a subset of the optional
header fields of the report that shall be included in the report: – sequence-number
(if TRUE SqNum shall be included in the report); – report-time-stamp (if TRUE
TimeOfEntry shall be included in the report); – reason-for-inclusion (if TRUE
ReasonCode shall be included in the report); – data-set-name (if TRUE DatSet shall
be included in the report); – data-reference (if TRUE DataRef or
DataAttributeReference shall be included in the report); – buffer-overflow (if TRUE
BufOvfl shall be included in the report); – entryID (if TRUE EntryID shall be included
in the report); – conf-revision (if TRUE ConfRev shall be included in the report).

17.218 OPTFLD_SET

Specific to Block(s) EIM


Description optFlds Setting
Data Type ENUM
Range NA
Default Dynamic
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

- 2115 -
Chapter 17 - Oxxxx Parameters

17.219 OPTMODE

Specific to PID-PL
Block(s)
Description Optimization Objective - PV operating objective for the optimizer in the Profit Loop
PKS algorithm.
Data Type Enumeration
Range NONE No optimization.
MINIMIZE Minimize PV - drive toward low limit.
MAXIMIZE Maximize PV - drive toward high limit.
OPTTARGET Optimize toward user-specified target
value (SP).
DUALRANGE Strive to keep optimal solution between
optimization limits, SPLOLMOPT to
SPHILMOPT.
Default OPTTARGET
Config Yes
Load
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related CTLEQN, OPTSPEED.
Parameters
Remarks The rate of movement toward the optimal target is dictated by the optimization
speed, OPTSPEED. This parameter is applicable only when CTRLMODE is RANGE.
This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

17.220 OPTOAOCONN

Specific to Regulatory HRB


Blocks
Description OP Connected to AO
Data Type BOOLEAN
Range TRUE – OP connected to AOCHANNEL FALSE – OP not connected to AOCHANNEL
Default FALSE
Config. Yes
Load

- 2116 -
Chapter 17 - Oxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related
Parameters
Remarks This parameter is applicable for RAMPSOAK algorithm only. This parameter is set to
TRUE if OP is connected to AOCHANNEL during translation of eb files to Experion
PKS strategies. Setting this parameter manually is not recommended.

17.221 OPTOL

Specific to ENHREGCALC, RATIOCTL, RegSummer, AutoMan, FanOut, OvrdSel, PID, PID-PL,


Block(s) PIDER, PIDFF, RAMPSOAK, RATIOBIAS, REGCALC, REMCAS, SWITCH
Description Output (OP) Tolerance - Define tolerance value for output in percent.
Data Type Float64
Range 0 to OPEXHILM
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks Since several blocks might share the FANOUT output, output tolerance does not
make sense for the FANOUT block as each connection might prefer a different
tolerance.

17.222 OTRPI

Specific to All ArmorPoint modules, ArmorBlock modules, PowerFlex Drive, E3, and E3 plus
Block(s) Devices
Description Originator -> Target RPI (ms) — Represents the rate at which the controller sends
data to the I/O module..
Data Type UINT16
Range 0-2000 ms

Default 0
Config Load Yes
Active No
Loadable

- 2117 -
Chapter 17 - Oxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related
Parameters
Remarks RPI should be a multiple of the base cycle of the controller, if it is not then the value
would be rounded down to the nearest base cycle and while loading a warning will
be displayed.

17.223 OPTSPEED

Specific to PID-PL
Block(s)
Description Optimization Speed - Unitless parameter controlling how fast the optimizer drives
the process toward the optimal target.
Data Type Float64
Range 0.1 - 10.0
Default 1
Config Yes
Load
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related CTRLMODEOPTMODE
Parameters
Remarks Profit Loop PKS uses the formula:

Where:
CLOSEDLOOPRESP = Closed loop response time
OPTSPEED = Optimization speed
OPTRESP = Settling time associated with changes
induced through optimization
An optimization speed of 6.0 makes the optimizer as aggressive as the controller.
Decreasing the optimization speed increases the time to the optimal target allowing
for less aggressive OP movement. This parameter is applicable only when CTLEQN
is set to Profit Loop PKS, and is ignored in PID control equations.

- 2118 -
Chapter 17 - Oxxxx Parameters

17.224 OPTSPEEDFACTOR

Specific to Block(s) ProfitCtl


Description Opt. speed factor
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

17.225 OPTYPE

Specific to DevCtl, All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,
VALVEDAMPER
Description Sequential Control Module (SCM) Control Output Request Type Option
Data Type Enumeration OPTYPE
Range Null (0) Set (1) NotStored (2) Default (3)
Default Null (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RegCtl only: ASSOCIATEDTRENDASTEPID, DevCtl only: HOLDOPT,
Parameters CONTROLREQ, LASTOPTYPE, OP[1..16].TYPE, LASTOPTYPE, OPREQ,
SCHEDCYCLE[0..120] SCMASTEP[1..15], SCMOPT, RESTARTOPT, STARTOPT,
SCMSTATE. Drive Control only: HOLDOPT, STOPOPT.
LASTOPTYPE, OPREQ, RESTARTOPT, STARTOPT,
STOPOPT.
Remarks

- 2119 -
Chapter 17 - Oxxxx Parameters

17.226 OPTYPEENUMMASK

Specific to Block(s) Step


Description Step Output Type Enumeration Mask
Data Type String
Range
Default
Config Load
Active Loadable No
Access Lock Appliction Developer Only
Residence SR
Related Parameters
Remarks

17.227 OPX

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, and Switch.
Description Output (OP) Value in Percent and Status.
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related OPEU
Parameters
Remarks OPX is a two-part data structure that contains: OP (the output value in percent) and
a status component. OPX can be used when making a connection to an AOC block.
The OPX connection is required in order for the initialization path to be established
between the Regulatory Control (RegCtl) block and the AOC block. OPEUXcan also
be used in the same capacity as the OPX parameter. This parameter will not
indicate any value (it shows * * * *) on the chart when the pin is exposed.

- 2120 -
Chapter 17 - Oxxxx Parameters

17.228 OPX[1..8]

Specific to Block(s) Fanout


Description Output (OP) Value and Status.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters OPEU
Remarks

17.229 ORBYPASSFL[1..4]

Specific to Block OvrdSel


(s)
Description Override Bypass Flags - Indicates which Override Selector inputs (if any)
should be bypassed.
Data Type Boolean
Range Off (0): Input is not bypassed. On (1): Input is bypassed.
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

17.230 ORBYPPERM

Specific to Block(s) Ovrdsel


Description Bypass Enable
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes

- 2121 -
Chapter 17 - Oxxxx Parameters

Active Loadable No
Access Lock Engineer/Applications Developer
Residence CEE
Related Parameters
Remarks

17.231 ORDER

Specific to Block(s) DevCtl


Description Execution Order within containing Control Module
Data Type Integer
Range 0 to 65535
Default A multiple of 10, established by Control Builder when the block is created.
Config Load Yes
Active Loadable No
Access Lock Point Build
Residence CEE
Related Parameters
Remarks

17.232 ORDERINCEE

Specific to CM, SCM, IOM, RCM, UCM


Block(s)
Description Order of execution of a container block relative to other container blocks within the
same cycle of the CEE.
Data Type 16-Bit Integer
Range 0 to 32,767
Default 10
Config Yes
Load
Active No
Loadable

- 2122 -
Chapter 17 - Oxxxx Parameters

Access Application Developer


Lock
Residence CEE
Related ORDERINCM, PENABLE[1..10], PHASE.
Parameters
Remarks Determines the relative execution order of container blocks when they execute
within the same cycle. Block with lower value execute first. If user assigns the same
value to different blocks, the CEE assigns a distinct and repeatable execution order
(based on the independent object code), but does not change the value of
ORDERINCEE. In this case, the user cannot readily determine the order of
execution of any two container blocks. Note that ORDERINCEE can only be changed
through block load.

17.233 ORDERINCM

Specific to All basic function blocks


Block(s)
Description Execution order of a component block relative to other component blocks within a
Control Module (CM) function block.
Data Type 32-Bit Integer
Range 1 to 32,767 A linearly increasing multiple of 10 starting at 10, the actual value
assigned by Control Builder according to the order of insertion into a CM function
block during configuration.
Default 10
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence SR
Related ORDERINCEE, PENABLE[1..10], PHASE.
Parameters
Remarks The parameter value determines the relative execution order of component blocks
within a Control Module (CM) function block. In a given CM, a block with a lower
value for ORDERINCM executes before any block with a higher value. If the same
value is assigned to multiple blocks, the Control Builder assigns a distinct and
repeatable execution order (based on the dependent object code), but does not
change the value of ORDERINCM. If the order of execution is critical, assign the
required values. A new parameter value can be configured by double-clicking the
parameter value on the function block faceplate or through the function block
configuration form. You can choose to display or conceal the ORDERINCM value on
the FB faceplate through Control Builder System Preferences dialog box.
ORDERINCM does not apply to CM, IOM, SCM, or SCM component blocks. It is
applicable only for blocks that execute inside the CM. For Fieldbus devices, the
ORDERINCM parameter sets or indicates the processing order of the Fieldbus
devices on the H1 Link. For more information, refer to the FFLink Configuration
Parameters Reference section in the Series C Fieldbus Interface Module User's Guide.

- 2123 -
Chapter 17 - Oxxxx Parameters

Specific to Block(s) CM
Description Execution Order within containing Control Module.
Data Type INTEGER
Range 0 to 35535
Default Multiple of 10, established by Control Builder when block is created.
Config Load Yes
Active Loadable No
Access Lock AppDeveloper
Residence CEE
Related Parameters
Remarks

Specific to Block(s) Up / Down Counter Block


Description Execution order in CM
Data Type Integer 32
Range 1 to 2,147,483,647
Default 10
Config Load No
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

17.234 ORDERINLINK

Specific to CONTROLMODULE
Block(s)
Description Execution Order in Link - Determines the order of block execution and publication
for the fieldbus blocks contatined in the CM in combination with the Execution
Order in CM.
Data Type 16-Bit Integer
Range 0 to 32767 ( in multiple of 10)
Default 10
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence SR
Related ORDERINCM
Parameters
Remarks

- 2124 -
Chapter 17 - Oxxxx Parameters

17.235 ORED

Specific to Block(s) NooN


Description Ored output value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

17.236 OREDOUT

Specific to Block(s) FIRSTOUT


Description OR of all Inputs
Data Type Boolean
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters IN[*]
Remarks

17.237 ORFBSTSSRC

Specific to Block(s) RegCalc


Description Override feedback status (ORFBSTS) source selector.
Data Type Enumeration
Range X1 to C8STS (0 - 27)
Default X1 (0)
Config Load Yes
Active Loadable No

- 2125 -
Chapter 17 - Oxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters
Remarks

17.238 ORFBVALSRC

Specific to Block(s) RegCalc


Description Override feedback value source selector
Data Type Enumeration REGCALCSELECTOR
Range x1 to C8STS (0 - 27)
Default X1 (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

17.239 ORIAPPCONNID[1..48]

Specific to Block FTEB


(s)
Description Originators Application Connection ID - Identifies initiator's application
connection ID.
Data Type 16-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related
Parameters
Remarks

- 2126 -
Chapter 17 - Oxxxx Parameters

17.240 ORICONNSTATE[1..48]

Specific to Block(s) FTEB


Description Originators Connection State - Identifies initiator's connection state.
Data Type Enumeration
Range 1 = Closed
2 = Closing
4 = Opening
8 = Open
Default Closed (1)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

17.241 ORIGINALGAIN

Specific to Block(s) ProfitCtl


Description Original Gain
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

17.242 ORIPATH[1..48]

Specific to Block(s) FTEB


Description Originators Path - Identifies initiator's connection path.
Data Type String
Range 32 Characters Maximum
Default 0

- 2127 -
Chapter 17 - Oxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

17.243 ORITCLASS[1..48]

Specific to Block(s) FTEB


Description Originators Transport Class - Identifies the initiator's transport class.
Data Type 8-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

17.244 ORMUXED[1..48]

Specific to Block FTEB


(s)
Description Originators Multiplexed - Identifies number of initiators using multiplexed
connections.
Data Type 8-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related
Parameters
Remarks

- 2128 -
Chapter 17 - Oxxxx Parameters

17.245 OROFFSET

Specific to OvrdSel
Block(s)
Description Override Offset
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related OROPT
Parameters
Remarks This flag applies only to upstream PIDs. It indicates if the PID should apply a
calculated offset to the override feedback value.

17.246 OROPT

Specific to OvrdSel
Block(s)
Description Override Option - Indicates how the nonselected inputs to the Override Selector
block should track the selected input.
Data Type Boolean
Range Off (0): Nonselected inputs do not use override feedback data. The block acts as a
simple high/low selector. On (1): Nonselected inputs should use override feedback
data.
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer/Applications Developer
Residence CEE
Related
Parameters
Remarks

- 2129 -
Chapter 17 - Oxxxx Parameters

17.247 ORPHANRESPCNT

Specific to Block(s) PCDI_MASTER


Description Orphaned Responses Count
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock VeiwOnly
Residence CEE
Related Parameters
Remarks

17.248 OSVER

Specific to CAB types


Block(s)
Description Operating System Version. Contains the version of the operating system that was
executing when the user's CAB program was built. It is set by the CAB Build
environment when a CAB type is created or edited.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type String
Range 32 characters
Default Blank
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence System Repository
Related CABSOFTVER, DOTNETVER[0..1]
Parameters
Remarks

- 2130 -
Chapter 17 - Oxxxx Parameters

17.249 OTCONNPRIORITY

Specific to Block(s) All EIP IOM/Devices/Drives/CNet IOs and EIP Generic adapter
Description OT Connection Priority
Data Type ENUM
Range 0 - Low Priority
1 - High Priority
2 - Scheduled
3 - Urgent
Default
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters TOCONNPRIORITY, CONNTMOMULT
Remarks This parameter represent Connection Priority as defined in CIP.

17.250 OTCONNTYPE

Specific to Block(s) All EIP IOM/Devices/Drives and EIP Generic adapter and supported CNet IOs
Description OT Connection Type
Data Type ENUM
Range 0 - NULL
1 - MULTICAST
2 - POINT2POINT
Default POINT2POINT
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters TOCONNTYPE, OTCONNPRIORITY, TOCONNPRIORITY, CONNTMOMULT
Remarks The parameter represent Connection type as defined in CIP.

- 2131 -
Chapter 17 - Oxxxx Parameters

17.251 OTDENBL

Specific to LLAI
Block(s)
Description Open Thermocouple Detection Enable. Defines whether an open-sensor
condition is to be detected for all eight channels.
Data Type Boolean
Range Off (0): Do not detect an open thermocouple
condition.
On (1): Detect an open thermocouple condition.

Default On (1)
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence IOM
Related PIUOTDCF
Parameters
Remarks

17.252 OTRPI

Specific to All ArmorPoint modules, ArmorBlock modules, PowerFlex Drive, E3, and E3 plus
Block(s) Devices
Description Originator -> Target RPI (ms) — Represents the rate at which the controller sends
data to the I/O module..
Data Type UINT16
Range 0-2000 ms

Default 0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks RPI should be a multiple of the base cycle of the controller, if it is not then the value
would be rounded down to the nearest base cycle and while loading a warning will
be displayed.

- 2132 -
Chapter 17 - Oxxxx Parameters

17.253 OUT

Specific to And, Checkbad, Delay, EQ, FTrig, GE, GT, LE, LT, Maxpulse, Minpulse, Mux, Nand,
Block(s) NE, Nor, Not, Offdelay, Ondelay, Or, Pulse, Qor, RTrig, Sel, Trig, Watchdog, Xor
Description Current output value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to Block(s) Limit, Muxreal, Max, Min, SelReal


Description Current output value
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

Specific to Block(s) ROL, ROR, SHL, SHR


Description Current output value
Data Type 16-Bit Integer
Range 16-Bit Integer
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2133 -
Chapter 17 - Oxxxx Parameters

Specific to Block(s) ABS, ADD, DIV, EXP, LN, LOG, MUL, NEG, POW, ROUND, SQRT, SUB,
TRUNC
Description Current output value
Data Type Real
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

Specific to Block(s) None


Description Current rolling average output value.
Data Type FLOAT64
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks None

Specific to Block(s) PROFITCTLIN, PROFCON


Description Out Connector
Data Type STRUCT
Range
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence
Related Parameters
Remarks This is an Internal parameter

- 2134 -
Chapter 17 - Oxxxx Parameters

17.254 OUT[0..12]

Specific to Genlin
Block(s)
Description Output Coordinates 0 to 12 - These Parameters define the output value at the
respective coordinate for the General Linearization function block.
Data Type 64-Bit Real Number
Range Any Real Number, not NaN.
Default N/A
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related IN[0..12], NUMSEGS.
Parameters
Remarks

17.255 OUT[1..8]

Specific to Block(s) CheckBool Logic Block


Description Output Value
Data Type Boolean
Range (0) OFF) (1) ON
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters OUTSTS[1..8]
Remarks Provides the current value of the connected output

17.256 OUT.Boolean

Specific to Block(s) TypeConvert, Push.


Description Boolean Output Value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)

- 2135 -
Chapter 17 - Oxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

17.257 OUT.ENUM

Specific to Block(s) TypeConvert, Push.


Description Enumerated Output Value
Data Type Enumeration
Range N/A
Default ENUM0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

17.258 OUT.FLOAT32

Specific to Block(s) TypeConvert, Push.


Description 32-Bit Floating Point Output Value
Data Type Real
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2136 -
Chapter 17 - Oxxxx Parameters

17.259 OUTFLOAT64

Specific to Block Up / Down Counter Block


(s)
Description Counter Value, Float 64
Data Type Float 64
Range Floating point equivalent of - (2,147,483,647 -1 ) to 2,147,483,647
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related This parameter is a representation of the internal counter value converted to
Parameters floating point format.
Remarks This parameter represents the internal counter value that is converted to a
floating point value.

17.260 OUT.INT8

Specific to Block(s) TypeConvert, Push.


Description 8-Bit Integer Output Value
Data Type 8-Bit Integer
Range -128 to 127
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

17.261 OUT.INT16

Specific to Block(s) TypeConvert, Push.


Description 16-Bit Integer Output Value
Data Type 16-Bit Integer
Range -32768 to 32767
Default 0
Config Load No

- 2137 -
Chapter 17 - Oxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

17.262 OUTINT32

Specific to Up / Down Counter Block


Block(s)
Description Counter Value, Integer 32
Data Type Integer 32
Range -(2,147,483,647 -1) to 2,147,483,647
Default 0
Config Load No
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks This parameter provides the direct value of the internal counter. It is restored from
checkpoint to help indirectly and directly preserve a snapshot of output state.

17.263 OUT.SDENUM

Specific to Block(s) TypeConvert, Push.


Description Self-defining Enumeration Output
Data Type Self-Defining Enumeration
Range 12 character string corresponding to ordinal value.
Default SDENUM0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2138 -
Chapter 17 - Oxxxx Parameters

17.264 OUT.UINT 8

Specific to Block(s) TypeConvert, Push.


Description 8-Bit Unsigned Integer Output Value
Data Type Integer
Range 0 to 255
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

17.265 OUT.UINT16

Specific to Block(s) TypeConvert, Push.


Description 16-Bit Unsigned Integer Output Value
Data Type Integer
Range 0 to 65535
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

17.266 OUT.UINT32

Specific to Block(s) TypeConvert, Push.


Description 32-Bit Unsigned Integer Output Value
Data Type Integer
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No

- 2139 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

17.267 OUT1

Specific to Block(s) CONTACTMON


Description Tracks IN[1] when both inputs of COC are not ON
Data Type Boolean
Range OFF (0) ON (1)
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters IN[1,2]
Remarks OUT1 = (IN[1] XOR IN[2]) AND IN [1]

17.268 OUT2

Specific to Block(s) CONTACTMON


Description Tracks IN[2] when both inputs of COC are not ON
Data Type Boolean
Range OFF (0) ON (1)
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters IN[1,2]
Remarks OUT2 = (IN[1] XOR IN[2]) AND IN [2]

- 2140 -
Chapter 17 - Oxxxx Parameters

17.269 OUTCAP

Specific to Block(s) GRPCAPARBK


Description Capability of Group of equipment
Data Type IEEEFloat64
Range Positive Float Value
Default NaN
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters OFFCAP[1..10]ONCAP[1..10]
Remarks The Group Capability output.

17.270 OUTDIR

Specific to Blocks HRBALG_HLPIUAO, HRBALG_HLPIUAC, HRBALG_HLPIUDO, HRBALG_


HLPIUDC
Description Output Direction
Data Type ENUM
Range DIRECT REVERSE
Default DIRECT
Config. Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks This parameter indicates the HLPIU digital point’s direction.

17.271 OUTFLOAT64

Specific to Block Up / Down Counter Block


(s)
Description Counter Value, Float 64
Data Type Float 64
Range Floating point equivalent of - (2,147,483,647 -1 ) to 2,147,483,647
Default 0.0
Config Load No

- 2141 -
Chapter 17 - Oxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related This parameter is a representation of the internal counter value converted to
Parameters floating point format.
Remarks This parameter represents the internal counter value that is converted to a
floating point value.

17.272 OUTHORN1

Specific to Block ANNPANEL


(s)
Description Audible horn output for the hooter 1
Data Type Boolean
Range ON/OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related FLSHSTAT
Parameters
Remarks Hooter 1 output. This will be ON when any one of the FLSHSTAT array is in
fast flash state.

17.273 OUTHORN2

Specific to Block ANNPANEL


(s)
Description Audible horn output for the hooter 2
Data Type Boolean
Range ON/OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related FLSHSTAT
Parameters
Remarks Hooter 2 output. This will be ON when any one of the FLSHSTAT array is in
slow flash state.

- 2142 -
Chapter 17 - Oxxxx Parameters

17.274 OUTIND

Specific to AUTOMAN, EHNREGCALC, FANOUT, OVRDSEL, PID, PID-PL, PIDER, PIDFF,


Block(s) RAMPSOAK, RATIOBIAS, RATIOCTL, REGCALC, REGSUMMER, REMCAS, SWITCH
Description Output Indication - Specifies how the OP parameter is accessed and whether
display indications will be shown on the block's faceplate display.
Data Type Enumeration
Range 0 Direct No value reversal and no display
indication
1 Reverse 1 Value reversal and no dislplay indication

2 DirectDisplnd No value reversal and show display


indications
3 ReverseDisplnd No value reversal and show reverse
display indications
Default Direct
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related OP OPHIALM.TP OPHIALM.TM
Parameters CTLACTN OPLOALM.TP OPHIALM.TMO
OPTDIR OPHIALM.PR OPLOALM.TM
OPEU OPLOALM.PR OPLOALM.TMO
OPHILM OPHIALM.FL OPHIALM.DB
OPLOLM OPLOALM.FL OPLOALM.DB
OPEXHILM OPEXHIFL OPHIALM.DBU
OPEXLOLM OPEXLOFLOPROCPOSFL OPLOALM.DBU
OPROCNEGFLHOLDVAL STARTVAL OPHIALM.SV
OPLOALM.SV SAFEOP
STOPVAL
Remarks This parameter has no affect on the block's control operation. The block's CTLACTN
parameter still supports the output direction of a PID function block and the
AOCHANNEL block's OPTDIR parameter applies the conversion of OP to OPFINAL.
The user can tailor the DIRECT/REVERSE selections of the OUTIND, CTLACTN, and
OPTDIR parameters to fit the process and operator needs. 1The PIDER and
RAMPSOAK blocks do not support the Reverse option.

17.275 OUTINT32

Specific to Up / Down Counter Block


Block(s)
Description Counter Value, Integer 32
Data Type Integer 32
Range -(2,147,483,647 -1) to 2,147,483,647

- 2143 -
Chapter 17 - Oxxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks This parameter provides the direct value of the internal counter. It is restored from
checkpoint to help indirectly and directly preserve a snapshot of output state.

17.276 OUTPIN

Specific to Block(s) ProfitCtl


Description Out Connector
Data Type OUTCONN
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence
Related Parameters
Remarks

17.277 OUTPUTTYPE

Specific to Blocks HRBALG_HLPIUDO, HRBALG_HLPIUDC


Description Output Type
Data Type ENUM
Range LATCH PULSE MOMENT
Default LATCH
Config. Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This parameter represents the type of DO point.

- 2144 -
Chapter 17 - Oxxxx Parameters

17.278 OUTSENSE

Specific to Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Output Safe State - Selects safe state of the associated Output. When target is
reached, the Output is set to this state.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Affects Channels 6-7 only.

17.279 OUTSENSE[6..7]

Specific to Pulse Input IOM


Block(s)
Description Output Safe State - Selects safe state of the associated Output. When target is
reached, the Output is set to this state.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Affects Channels 6-7 only.

- 2145 -
Chapter 17 - Oxxxx Parameters

17.280 OUTTYPE

Specific to All Regulatory Control Blocks


Block(s)
Description Output Type - Defines whether the connected output is a digial or analog type.
Data Type Enumeration
Range (0) Digital (1) Analog
Default Analog
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Most regualtory control blocks are connected to analog outputs except POSPROP
blocks, which have digital output connections

17.281 OUTSTS[1..8]

Specific to Block(s) CheckBool Logic Block


Description Output Status
Data Type Enumeration
Range 0-6
l (0) kBadValSts
l (1) kUncertainValSts
l (2) kNormalValSts
l (3) kManualValSts
l (4) kInitAckValSts
l (5) kInitRegValStst
l (6) kInitBadValSts
Default kNormalValSts
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters OUT[1..8]
Remarks Provides the current status of the connected output

- 2146 -
Chapter 17 - Oxxxx Parameters

17.282 OVERALLRESPONSETIME

Specific to Block(s) ProfitCtl


Description Overall Response Time
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

17.283 OVERCAPACITY[1..24]

Specific to Block QIPACTERM


Description Scale Over Capacity
Data Type Boolean
Range Off(0) OK
On(1) Over Capacity
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 2 of the Status 1 byte in the input assembly for the
designated position [1-24].

17.284 OVERCAPACITY[1..200]

Specific to QIPACCHAN
Block
Description Scale Over Capacity
Data Type Boolean
Range Off(0) OK
On(1) Over Capacity

- 2147 -
Chapter 17 - Oxxxx Parameters

Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 2 of the Status 1 byte in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

17.285 OVRDSEL

Specific to HRBALG_REG block


Blocks
Description OVRDSEL FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the OVRDSEL block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

17.286 OVRDSEL2

Specific to HRBALG_REG block


Blocks
Description OVRDSEL FB Reference 2
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly

- 2148 -
Chapter 17 - Oxxxx Parameters

Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the OVRDSEL block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

17.287 OVERRANGE

Specific to AIC
Block(s)
Description Over Range Alarm Indicator - Indicates the input value is above the valid hardware
input range of the channel. Overrange and Underrange parameters are not
supported for the Series A Analog Input Module — TC-FIAH81(1794-IE8). When
selected, Parameter ID error Err2088 will appear.
Data Type Boolean
Range Input is not in an over-range state (0) Input is in an over-range state (1)
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related UNDERRANGE
Parameters
Remarks

17.288 OVERRANGE[0..numChans-1]

Specific to AIM
Block(s)
Description Over Range Alarm Indicator - Indicates the input value is above the valid
hardware input range of the channel.
Data Type Boolean
Range Input is not in an over-range state (0) Input is in an over-range state (1)
Default N/A
Config Load No
Active No
Loadable

- 2149 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related UNDERRANGE[0..numChans-1
Parameters
Remarks

17.289 OVERRANGE [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1732E-IF4M12R, 1732E-IR4IM12R, 1732E-IT4IM12R,


Block(s) 1738-IE2CM12, 1738-IE4CM12, 1738-IR2M12, 1738-IT2IM12
Description Over Range detection flag
Data Type Boolean
Range l Off
l On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related UNDERRANGE
Parameters
Remarks The value of the parameter changes to ON when the IO hardware reports an over
range condition.

17.290 OVERRUNSCUR

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Overruns in Current Hour. Shows the number of I/O link overruns that have
occurred in the current hour.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable

- 2150 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related
Parameters
Remarks

17.291 OVERRUNSPREV

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Overruns in Previous Hour. Shows the number of I/O link overruns that have
occurred in the previous hour.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

17.292 OVERTEMP

Specific to Block(s) TCMI


Description Over temperature
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 2151 -
Chapter 17 - Oxxxx Parameters

17.293 OVERTEMPTHLD

Specific to C300 FBs, Series C FIM, PGM


Block(s)
Description Over Temperature Threshold
Data Type 32-Bit Integer
Range 0 to 100 °C
Default 80
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300, Series C FIM, PGM
Related C300TEMP [1...3]
Parameters
Remarks Configurable threshold value, above which function block posts a soft failure from
any of its thermometers. The default value 0 disables the alarm.

17.294 OVERTOLRNCE[1..200]

Specific to QIPACCHAN
Block
Description Over Tolerance
Data Type Boolean
Range Off(0) OK
On(1) Over Tolerance
Default Off
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MATERIALPATH[1..200], COMMAND, COMMANDSTATS[1..200], MXFERSTATUS
Parameters [1..200], MXFERSTATQ[1..200], OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200],
POWERFAIL[1..200], TARGETERROR[1..200], AVGSPILL[1..200], AVGFLOWRATE
[1..200]
Remarks This is the value of bit 0 of the MXFERSTATQ word in
the Command Status Object. This value provides
material transfer results and is valid after the material
transfer for the designated channel [1..200] in the
QiMPACT cluster completes.

- 2152 -
Chapter 17 - Oxxxx Parameters

17.295 OVERUNDERVOLTAGE

Specific to Block(s) EIM Platform Block


Description Power Over/Under Voltage Warning
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks True if the 24V DC input power is outside the acceptable input voltage
range.

Specific to UOC, C300


Block(s)
Description Power Over/Under Voltage Warning
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Soft failure condition. Under or over voltage condition detected. Replace power
supply and/or UOC hardware.

17.296 OVRRUNCURHR[1..40]

Specific to IOLINK, C300 IOLINK


Block(s)
Description Process Data Cycle Overruns Current Hour.
Data Type 16-Bit Integer
Range 0 to 32767
Default 0
Config Load No
Active No
Loadable

- 2153 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related OVRRUNPREVHR[1..40]
Parameters
Remarks Each element gives a count of cycle overruns that have occurred during the
current hour for each IOP. The time is not synchronized with wall clock time.

17.297 OVRRUNPREVHR[1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Process Data Cycle Overruns in Previous Hour.
Data Type 16-Bit Integer
Range 0 to 32767
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related OVRRUNPREVHR[1..40]
Parameters
Remarks Each element gives a count of cycle overruns that have occurred during the
previous hour for each IOP. The time is not synchronized with wall clock time.

17.298 OVRSIGNA

Specific to Block(s) IOLINK, Secondary IOLINK


Description P-Data Overrun Signature
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock Operator
Residence IOLINK
Related Parameters
Remarks

- 2154 -
Chapter 17 - Oxxxx Parameters

17.299 OWDENBL

Specific to Series CSeries C AICHANNEL and Series C DICHANNEL


Block(s)
Description Open Wire Detection Enable
Data Type Boolean
Range 0 OFF Do not detect an open wire
condition.
1 ON Detect an open wire
sensor condition.
Default OFF
Config Yes
Load
Active No
Loadable
Access Engineer/Application Developer
Lock
Residence IOM
Related
Parameters
Remarks This parameter enables the open wire diagnostic that detects and annunciates a
broken field wire or faulty sensor. In addition, a seemingly valid PV from a channel
diagnosed as having a broken-wire will not be made available (thus preventing
incorrect control action). When enabled, an open wire condition will generate Soft
Failure 179 “Open Wire Detected”. For DI channels, this parameter is only
configurable for:
l DI-24V modules with DIMODE = Normal
l DI-SOE modules with DIMODE = Normal
For AI channels, this parameter is only configurable for:
l AI-HART modules with SENSRTYP = 1_5_V connected to 4-20mA current
sources.
l AI-LLMUX /AI-LLAI modules with SENSRTYP = THERMCPL or 0_100_MV
For AI channels, if open wire detection is enabled (OWDENBL = ON) and the IOM
detects the broken-wire condition, then PVCALC will be NaN, in which case, PVAUTO
will be NaN. For LLMUX channels, no SoftFail event is reported when open wire
condition is detected. If OWDENBL is enabled (OWDENBL = ON) and the T/C wire
gets disconnected, then PV value will be NaN and BADPV is set to ON. When
OWDENBL is disabled, the PV value will be floating with BADPVFL set to OFF. Note:
DI-24V (CC-PDIL51) and AIH (CC-PAIH51) modules do not support open wire
detection. Therefore, if you load a DI channel to DI-24V (CC-PDIL51) module when
the OWDENBL is “ON,” the configuration mismatch warning message appears and
the loading of the DI channel succeeds. If you load the AI Channel to one modem
AIH (CC-PAIH51) module when the OWDENBL is “ON,” the configuration mismatch
warning message appears and the loading of the AI channel block succeeds.

Specific to UIO - Series C DOCHANNEL


Block(s)
Description Open Wire Detection Enable
Data Type Boolean
Range 0 OFF Do not detect an open wire
condition.

- 2155 -
Chapter 17 - Oxxxx Parameters

1 ON Detect an open wire


sensor condition.
Default OFF
Config Yes
Load
Active No
Loadable
Access Lock Engineer/Application Developer
Residence IOM
Related
Parameters
Remarks This parameter enables the open wire diagnostic that detects and annunciates a
broken field wire or faulty sensor. In addition, a seemingly valid PV from a channel
diagnosed as having a broken-wire will not be made available (thus preventing
incorrect control action). When enabled, an open wire condition will generate Soft
Failure 179 “Open Wire Detected”. For DO channels, this parameter is configurable
only for UIO modules.

17.300 OWDENBL [0..NUMCHANNELS - 1]

Specific to EtherNet/IP [EIP] IOM: 1738-IB4DM12, 1732E-IB16M12DR


Block(s)
Description Open Wire Detection Enable — This parameter configures the open-wire
diagnostics for the module hardware for each channel.
Data Type Boolean
Range l Off
l On
Default On
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related OPENWIRE
Parameters
Remarks

- 2156 -
Chapter 17 - Oxxxx Parameters

17.301 OWDENBL_AI_C

Specific to UIO
Block(s)

Description Open Wire Detect


Data Type BOOLEAN
Range
0 Off Do not detect an open wire condition.

1 On Detect an open wire sensor condition.

Default Off
Config Yes
Load

Active No
Loadable

Access AppDevOnly
Lock

Residence CEE
Related
Parameters

Remarks This parameter enables the open wire diagnostic that detects and annunciates a broken
field wire or faulty sensor. In addition, a seemingly valid PV from a channel diagnosed as
having a broken-wire will not be made available (thus preventing incorrect control action).
When enabled, an open wire condition will generate Soft Failure “Open Wire Detected”.

17.302 OWDENBL_DI_C

Specific to UIO
Block(s)

Description Open Wire Detect


Data Type BOOLEAN
Range
0 Off Do not detect an open wire condition.

1 On Detect an open wire sensor condition.

Default Off
Config Yes
Load

Active No
Loadable

- 2157 -
Chapter 17 - Oxxxx Parameters

Access AppDevOnly
Lock

Residence CEE
Related
Parameters

Remarks This parameter enables the open wire diagnostic that detects and annunciates a broken
field wire or faulty sensor. In addition, a seemingly valid PV from a channel diagnosed as
having a broken-wire will not be made available (thus preventing incorrect control action).
When enabled, an open wire condition will generate Soft Failure “Open Wire Detected”.

17.303 OWDENBL_DO_C

Specific to UIO
Block(s)

Description Open Wire Detect


Data Type BOOLEAN
Range
0 Off Do not detect an open wire condition.

1 On Detect an open wire sensor condition.

Default Off
Config Yes
Load

Active No
Loadable

Access AppDevOnly
Lock

Residence CEE
Related
Parameters

Remarks This parameter enables the open wire diagnostic that detects and annunciates a broken
field wire or faulty sensor. In addition, a seemingly valid PV from a channel diagnosed as
having a broken-wire will not be made available (thus preventing incorrect control action).
When enabled, an open wire condition will generate Soft Failure “Open Wire Detected”.

17.304 OWNCMNDSTS[1..5]

Specific to Block(s) UCM


Description Status of Last Owner Command
Data Type INT32
Range 0 to 231-1
Default Value 0
Config Load No

- 2158 -
Chapter 17 - Oxxxx Parameters

Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters
Remarks This parameter displays the status of the last owner command.

17.305 OWNCMPPHASESTS[1..5]

Specific to UCM
Block(s)
Description Composite phase state
Data Type Enumeration
Range 0 Loading
1 Loaded
2 Inactive
3 Validated
4 Running
5 Complete
6 Checking
7 Idle
8 Interrupting
9 Interrupted
10 Restarting
11 Restarted
12 Holding
13 Held
14 Stopping
15 Stopped
16 Aborting
17 Aborted
18 CommErr
20 Starting
21 Started
Default Inactive
Value
Config Load No
Active No
Loadable

- 2159 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks This parameter displays the composite state of children. That is, the most serious
state of the active phases and steps are displayed.

17.306 OWNCOMMAND[1..5]

Specific to Block UCM


(s)
Description Command
Data Type Enumeration
Range 0 None
1 Inactive
2 Start
3 Reset
4 Interrupt

5 Restart
6 Hold
7 Stop
8 Abort
9 Resume
10 Active
Default Value None
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related ABORTLOCK, CONTCUTOUT, CONTROLLOCK, MODE MODEATTR,
Parameters SSTEPLOCK, STATE
Remarks This parameter displays the command sent to the RCM or CR that presently
owns this UCM.

- 2160 -
Chapter 17 - Oxxxx Parameters

17.307 OWNERID[1..MAXOWNERS]

Specific to SCM, RCM, UCM, CM


Block(s)
Description Name of requesting block
Data Type BLOCKID
Range
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related MAXOWNERSOWNERIDN[1..MAXOWNERS]QUEUEID[1..n]
Parameters
Remarks All user interfaces will show the name of the object represented by this handle. The
array will be filled starting with 1. A fragmentation of the array will not occur.
Example: If QUEUEID[2]=NULL , than all QUEUEID[x>(greater than)2]=NULL.

ATTENTION This parameter cannot be processed in the expressions.


You must use the OWNERIDN parameter in the expressions.

17.308 OWNERIDN[1..5]

Specific to SCM, RCM or CR, and UCM


Block(s)
Description This parameter displays the present owner identification of requestor.
Data Type INT32
Range 0 to 231-1
Default 0
Value
Config No
Load
Active No
Loadable

- 2161 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related MAXOWNERSOWNERID[1..MAXOWNERS]QUEUEIDN[1..n]NUM
Parameters
Remarks This parameter can be used for comparisons in expressions only if compared with
other parameters returning an id(for example, NUM). Comparisons with absolute
values does not work reliably as internal ids are subject to change with some
engineering operations.

17.309 OWNERIDN[1..MAXOWNERS]

Specific to Block SCM, RCM, UCM, CM


(s)
Description Shows current owner, Identification of requester
Data Type 32-Bit Integer
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related MAXOWNERSOWNERID[1..MAXOWNERS]OWNERID
Parameters [1..MAXOWNERS]QUEUEIDN[1..n]
Remarks Diagnostic parameter only, shall not be used in control strategies.

17.310 OWNERLOOKUP

Specific to ACT, MR, RCM, and SCM


Block(s)
Description Displays the ClusterID, EEC, and IOC of the owner block.
Data Type String
Range 20 characters
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related OWNERID[1..MAXOWNERS]
Parameters
Remarks It is a parameter which is used in custom graphic to display the Cluster ID, EEC,
and IOC of the owner block in the following format: ClusterID, EEC, IOC.

- 2162 -
Chapter 17 - Oxxxx Parameters

17.311 OWNERS

Specific to Block(s) SCM, RCM, UCM, CM


Description Owners for internal communication only
Data Type STRUCT
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

17.312 OWNINGENIM

Specific to EHPM, TCMI


Block(s)
Description Owning ENIM is the FTE device index value that represents the device index of the
ENIM that owns the current EHPM.
Data Type INT32
Range 1–511
Default -
Config Yes
Load
Active Yes
Loadable
Access Lock AppDevOnly
Residence SR
Related ENIMIPADDRESS
Parameters
Remarks Owning ENIM device index is a user-entered value to calculate the IP address of
ENIM, so that the automatic import service can identify the owner ENIM and
establish communication with it. The Owning ENIM contains point database of the
current EHPM.

- 2163 -
Chapter 17 - Oxxxx Parameters

17.313 OWNMODE[1..5]

Specific to Block(s) UCM


Description Mode
Data Type Enumeration
Range 0 None
1 Auto
2 SemiAuto
3 Singlestep
4 Manual
5 Normal
6 Safestep
Default Value None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter displays the mode of the RCM or CR that presently owns this
UCM.

17.314 OWNMODEATTR[1..5]

Specific to UCM
Block(s)
Description Mode Attribute
Data Type Enumeration
Range 0 NONE
1 OPERATOR

2 PROGRAM
3 NORMAL
Default Value OPERATOR
Config Load No
Active No
Loadable

- 2164 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks This parameter displays the mode attribute of the RCM or CR that
presently possess the UCM.

17.315 OWNSTATE[1..5]

Specific to Block(s) UCM


Description State
Data Type Enumeration
Range 0 Loading
1 Loaded
2 Inactive
3 Validated
4 Running
5 Complete
6 Checking
7 Idle
8 Interrupting
9 Interrupted
10 Restarting
11 Restarted
12 Holding
13 Held
14 Stopping
15 Stopped
16 Aborting
17 Aborted
18 CommErr
20 Starting
21 Started
Default Value Inactive
Config Load No
Active Loadable No

- 2165 -
Chapter 17 - Oxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks This parameter displays the state of the RCM or CR that presently acquired
the UCM.

- 2166 -
CHAPTER

18 PXXXX PARAMETERS

18.1 P 2178
18.2 P[1..6] 2179
18.3 P[1..10] 2179
18.4 P0 2179
18.5 P1 2180
18.6 P1CLAMPOPT 2181
18.7 P1EU 2182

18.8 P1FILTINIT 2182


18.9 P1FILTTIME 2182
18.10 P1STS 2183
18.11 P2 2183
18.12 P2PEfficiency 2184
18.13 P2PSCANPERIOD 2184
18.14 P2STS 2184
18.15 PARAMETERREFERENCENAME.DESC 2185
18.16 PARAMETERREFENCENAME.PREF 2185
18.17 PARAMETERREFENCENAME.TYPE 2186
18.18 PARAMINIT 2186
18.19 PARAMNAME[0..500] 2187
18.20 PARENTASSET 2187
18.21 PARTNERINCOMPATIBLEA/PARTNERINCOMPATIBLEB 2188
18.22 PARTMISMATCH 2189
18.23 PARTNOTVIS 2190
18.24 PATH 2190
18.25 PATHBRKSTS 2191
18.26 PAUSEFL 2192
18.27 PCENGINEVER 2193
18.28 PCMCOMMAND 2193
18.29 PCMSTATE 2193
18.30 PCMNUMPRI 2194
18.31 PCMNUMSEC 2195
18.32 PCODESIZE[1..8] 2195

- 2167 -
Chapter 18 - Pxxxx Parameters

18.33 PCONN[1..10] 2195


18.34 PCOVERRUN 2196
18.35 PDELAYDIRCHG 2196
18.36 PDESC[1..10] 2197
18.37 PDFIFORATEA 2197
18.38 PDFIFORATEM 2198
18.39 PDTEIMIP 2198
18.40 PDTCONNSTS 2199
18.41 PDTEIMCONNSTS 2199
18.42 PDTEIMAVGRXPKTS 2199
18.43 PDTEIMMAXRXPKTS 2200
18.44 PDTTGTIPADDR 2200
18.45 PEAKFTEABLOCKRATE 2201
18.46 PEAKFTEBBLOCKRATE 2201

18.47 PEAKFTEARXRATE 2202


18.48 PEAKFTEBRXRATE 2202
18.49 PEAKFTEATXRATE 2203
18.50 PEAKFTEBTXRATE 2203
18.51 PEERAGETIME 2204
18.52 PEERALGOPT 2204
18.53 PEERALIASENB 2206
18.54 PEERALIASNUM 2207
18.55 PEERENV[ ] 2207
18.56 PEERGETAVG [1..30] 2208
18.57 PEERINPUTENB 2208
18.58 PEERINPUTNUM 2209
18.59 PEERRATEAVG 2209
18.60 PEERRATEMAX 2209
18.61 PEERREADOPT 2210
18.62 PEERSTRAVG [1..30] 2211
18.63 PEERSTRRESP [ ] 2211
18.64 PEERSUBSCPER [ ] 2212
18.65 PENABLE[1..10] 2212
18.66 PERFRATIOBACKOFFTOL 2212
18.67 PERIOD 2213
18.68 PERIODENUMMASK 2215
18.69 PERIODSEC 2215
18.70 PERSONALITYDAY 2216
18.71 PERSONALITYMONTH 2216

- 2168 -
Chapter 18 - Pxxxx Parameters

18.72 PERSONALITYNAME 2217


18.73 PERSONALITYREV 2217
18.74 PERSONALITYVER 2218
18.75 PERSONALITYYEAR 2218
18.76 PERSWAPENB 2218
18.77 PERSWAPTHRES 2219
18.78 PFANTICTIME 2219
18.79 PFREQ 2220
18.80 PFREQAVG 2221
18.81 PFREQMAX 2221
18.82 PHASE 2221
18.83 PHASEHOUR 2222
18.84 PHASEMIN 2223
18.85 PHASENAME[0..500] 2223

18.86 PHWYPRTLC 2224


18.87 PHWYPRTLCIP 2224
18.88 PHWYPRTLCIPISRED 2225
18.89 PHWYPRTRMIP1 2225
18.90 PHWYPRTRMIP2 2226
18.91 PHYCHNERRA1 [1...15] through PHYCHNERRA8 [1...15] 2226
18.92 PHYCHNERRB1 [1...15] through PHYCHNERRB8 [1...15] 2227
18.93 PHYCHNMNA1 [1...15] through PHYCHNMNA8 [1...15] 2227
18.94 PHYCHNMNB1 [1...15] through PHYCHNMNB8 [1...15] 2228
18.95 PHYCHNPLA1 [1...15] through PHYCHNPLA8 [1...15] 2228
18.96 PHYCHNPLB1 [1...15] through PHYCHNPLB8 [1...15] 2229
18.97 PHYCHNMNASC1 [1...20] through PHYCHNMNASC4 [1...20] 2229
18.98 PHYCHNMNBSC1 [1...20] through PHYCHNMNBSC4 [1...20] 2230
18.99 PHYCHNPLASC1 [1...20] through PHYCHNPLASC4 [1...20] 2230
18.100 PHYCHNPLBSC1 [1...20] through PHYCHNPLBSC4 [1...20] 2231
18.101 PHYCHNSILA1 [1...15] through PHYCHNSILA8 [1...15] 2231
18.102 PHYCHNSILB1 [1...15] through PHYCHNSILB8 [1...15] 2232
18.103 PHYCOMMERR1 [1...15] through PHYCOMMERR8 [1...15] 2233
18.104 PHYLHFSTA [1..8] 2234
18.105 PHYRCVCHN1 [1...15] through PHYRCVCHN8 [1...15] 2235
18.106 PHYSDSA1 [1...15] through PHYSDSA8 [1...15] 2235
18.107 PHYSIOPSTS1 [1...15] through PHYSIOPSTS8 [1...15] 2236
18.108 PHYSMODTYPE1 [1...15] through PHYSMODTYPE8 [1...15] 2237
18.109 PI[0..2] 2237
18.110 PID 2238

- 2169 -
Chapter 18 - Pxxxx Parameters

18.111 PIDSTATUS 2238


18.112 PIUCARDOP(1..32) 2238
18.113 PIUOTDCF 2239
18.114 PIUSMOTH 2239
18.115 PL 2240
18.116 PL[0..5] 2241
18.117 PLSTS 2241
18.118 PLVERSION 2242
18.119 PNETCONFIGCHNG 2243
18.120 PNETCONFIGPATH 2244
18.121 PNTALGOTYPE[ ] 2244
18.122 PNTFORM 2244
18.123 PNTTYPE 2245
18.124 PO 2246

18.125 PO[1..3] 2247


18.126 POCLOSE 2247
18.127 POCLOSECONNECTED 2248
18.128 POCONNECTED[1..3] 2248
18.129 PODIR 2249
18.130 POLOWER 2249
18.131 POLLTIME 2250
18.132 POOPEN 2250
18.133 POOPENCONNECTED 2250
18.134 POPERIOD 2251
18.135 PORAISE 2251
18.136 PORT 2252
18.137 PORUN 2252
18.138 PORUNCONNECTED 2253
18.139 POSTOP 2253
18.140 POSTOPCONNECTED 2254
18.141 POSTTRANSEXECSTS 2254
18.142 POWERCONNOPT 2255
18.143 POWERFAIL[1..200] 2256
18.144 PP[1..10] 2256
18.145 PPREDUNLINKFAIL 2257
18.146 PRBIAS 2257
18.147 PREDPVHIALM.FL 2258
18.148 PREDPVHIALM.PR 2258
18.149 PREDPVHIALM.SV 2259

- 2170 -
Chapter 18 - Pxxxx Parameters

18.150 PREDPVHIALM.TP 2259


18.151 PREDPVHIALM.TM 2260
18.152 PREDPVHIALM.TMO 2260
18.153 PREDPVLOALM.FL 2261
18.154 PREDPVLOALM.PR 2261
18.155 PREDPVLOALM.SV 2262
18.156 PREDPVLOALM.TM 2262
18.157 PREDPVLOALM.TMO 2263
18.158 PREDPVLOALM.TP 2263
18.159 PREFERREDCONN 2264
18.160 PREFSP 2264
18.161 PREFSPCLEAR 2265
18.162 PREFSPSET 2265
18.163 PRENGUNIT 2266

18.164 PRESSURE 2266


18.165 PRESSUREENGUNIT 2267
18.166 PRESSUREIO 2268
18.167 PREVALARM 2268
18.168 PREVISION 2268
18.169 PREVLOADSTAT 2269
18.170 PREVTRANSEXECSTS 2269
18.171 PRFRATIO 2270
18.172 PRIBLOCKNAME[1...40] 2270
18.173 PRICANTTALKTOSECONUCN 2271
18.174 PRICHNERRA [1...40] 2271
18.175 PRICHNERRB [1...40] 2272
18.176 PRICHNMNA [1...40] 2272
18.177 PRICHNMNB [1...40] 2273
18.178 PRICHNPLA [1...40] 2273
18.179 PRICHNPLB [1...40] 2274
18.180 PRICHNSILA [1...40] 2274
18.181 PRICHNSILB [1...40] 2275
18.182 PRICOMMERR [1...40] 2276
18.183 PRIIFCARD 2277
18.184 PRIIFCHNERRA 2277
18.185 PRIIFCHNERRB 2278
18.186 PRIIFCHNMNA 2278
18.187 PRIIFCHNMNB 2279
18.188 PRIIFCHNPLA 2279

- 2171 -
Chapter 18 - Pxxxx Parameters

18.189 PRIIFCHNPLB 2280


18.190 PRIIFCHNSILA 2280
18.191 PRIIFCHNSILB 2281
18.192 PRIIFCOMMERR 2282
18.193 PRIIFFILE 2283
18.194 PRIIFRCVCHN 2283
18.195 PRIIFSTS 2284
18.196 PRIM.[1..8].INITIALIZABLE 2284
18.197 PRIMARYACE 2285
18.198 PRIMARYSIG 2285
18.199 PRIMCONNSTS 2286
18.200 PRIMDATA.[1..8].ARWSTS 2286
18.201 PRIMDATA.[1..8]. EUHI 2287
18.202 PRIMDATA.[1..8]. EULO 2287

18.203 PRIMDATA.[1..8].HISELECT 2288


18.204 PRIMDATA.[1..8].INITSTS 2288
18.205 PRIMDATA.[1..8].INITVAL 2289
18.206 PRIMDATA.[1..8].LOCALMAN 2289
18.207 PRIMDATA.[1..8].ORFBSTS 2290
18.208 PRIMDATA.[1..8].ORFBVAL 2290
18.209 PRIMDATA.[1..8].OROFFSET 2291
18.210 PRIMDATA.[1..8].PROPOVRD 2291
18.211 PRIMERRCNT 2292
18.212 PRIMERRCODE 2292
18.213 PRIMERRFL 2293
18.214 PRIMERRINFO 2293
18.215 PRIMIP 2294
18.216 PRIMIPMON 2294
18.217 PRIMLASTCONNTIME 2294
18.218 PRIMLASTDISCONNTIME 2295
18.219 PRIMLASTERRTIME 2295
18.220 PRIMLOOPDATA 2296
18.221 PRIMNUMCONN 2296
18.222 PRIMNUMCONNATMPT 2297
18.223 PRIMNUMDISCONN 2297
18.224 PRIMOVERLAP[1..24] 2297
18.225 PRIMOVERLAP[1..200] 2298
18.226 PRIMTCP 2298
18.227 PRIMTCPMON 2299

- 2172 -
Chapter 18 - Pxxxx Parameters

18.228 PRIORITYIOM 2299


18.229 PRIRCVCHN [1..40] 2300
18.230 PRISECKEYSWMISMATCH 2301
18.231 PROCDEADTIME 2301
18.232 PROCDEADTIMEACT 2302
18.233 PROCDEADTIMEBIAS 2302
18.234 PROCEDURALLEVEL 2303
18.235 PROCESS_ID 2304
18.236 PROCESSED 2304
18.237 PROCGAIN 2305
18.238 PROCGAINACT 2305
18.239 PROCGAINEU 2306
18.240 PROCGAINMULT 2306
18.241 PROCGAINPCT 2307

18.242 PROCGAINUNITS 2308


18.243 PRODCODE 2308
18.244 PRODCODEA 2309
18.245 PRODTYPE 2309
18.246 PRODTYPEA 2310
18.247 PROFILEDESC[1..NUMPROFILES] 2310
18.248 PROFILEID 2311
18.249 PROFINETENABLE 2311
18.250 PROFRESET 2312
18.251 PROGCMD 2312
18.252 PROGCMDRECOG 2313
18.253 PROGID[0..40] 2313
18.254 PROGLCKTOIDLE 2314
18.255 PROGLCKTORUN 2314
18.256 PROGLOCKED 2314
18.257 PROGPACKET[0..2] 2315
18.258 PROGSTSDESC 2315
18.259 PROTOSTSTYPE 2316
18.260 PRPVHIGH.FL 2316
18.261 PrPVHigh.OffDelayTimeSec 2317
18.262 PrPVHigh.OnDelayTimeSec 2317
18.263 PrPVHigh.Priority 2317
18.264 PrPVHigh.Severity 2318
18.265 PrPVHigh.TripPoint 2318
18.266 PRPVLOW.FL 2319

- 2173 -
Chapter 18 - Pxxxx Parameters

18.267 PrPVLow.OffDelayTimeSec 2319


18.268 PrPVLow.OnDelayTimeSec 2320
18.269 PrPVLow.Priority 2320
18.270 PrPVLow.Severity 2320
18.271 PrPVLow.TripPoint 2321
18.272 PRSLOPE 2321
18.273 PSTS 2322
18.274 PSTS[1..6] 2322
18.275 PSTS[1..10] 2323
18.276 PSUB[1..10] 2323
18.277 PTEXECST 2324
18.278 PTEXECST[1..NUMCHAN] 2324
18.279 PTNRFLTIP 2325
18.280 PTPDELAY 2325

18.281 PTPDELAYMAX 2326


18.282 PTPENABLE 2326
18.283 PTPMASTERIP 2327
18.284 PTPNUMNODELAYRESP 2327
18.285 PTPNUMNOFOLLOWUP 2327
18.286 PTPNUMNOSYNC 2328
18.287 PTPOFFSET 2328
18.288 PTPOFFSETMAX 2329
18.289 PTPROCESSOROVERRUN 2329
18.290 PTPSKEWTHLD 2329
18.291 PTPSTAT 2330
18.292 PUBLICNAME 2331
18.293 PUBMETHOD 2332
18.294 PULSECMD 2332
18.295 PULSECMDTEXT[0..2] 2333
18.296 PULSEINTYPE 2333
18.297 PULSEMODE 2334
18.298 PULSEMODE[0..5] 2335
18.299 PULSETIME 2336
18.300 PULSEWIDTH 2336
18.301 PULSEWIDTH[1..3] 2337
18.302 PURGEDBCMD 2337
18.303 PURGEBUF 2338
18.304 PUSHSP 2339
18.305 PV 2339

- 2174 -
Chapter 18 - Pxxxx Parameters

18.306 PV[0..numChans-1] 2346


18.307 PV[0..7] 2346
18.308 PV[0..63] 2347
18.309 PV[0..120] 2347
18.310 PV[1..64] 2348
18.311 PV[1..200] 2348
18.312 PV[1..NUMCHAN] 2349
18.313 PV_AI_S 2349
18.314 PVASYNCOPT 2350
18.315 PVAUTO 2351
18.316 PVAUTOFL 2352
18.317 PVAUTOSTS 2353
18.318 PVBIAS 2353
18.319 PVCALC 2354

18.320 PVCHAR 2354


18.321 PVCHGDLY 2366
18.322 PVCLAMP 2367
18.323 PVCONN 2368
18.324 PVEM 2368
18.325 PVENGUNIT 2369
18.326 PVEQN 2369
18.327 PVERSION 2370
18.328 PVEUHI 2370
18.329 PVEUHI[0..120] 2372
18.330 PVEUHI_AI_C 2372
18.331 PVEULO 2373
18.332 PVEULO[0..120] 2374
18.333 PVEULO_AI_C 2375
18.334 PVEXEUHI 2375
18.335 PVEXEUHI_AI_C 2376
18.336 PVEXEULO 2377
18.337 PVEXEULO_AI_C 2378
18.338 PVEXHIFL 2379
18.339 PVEXHILM 2380
18.340 PVEXLOFL 2380
18.341 PVEXLOLM 2381
18.342 PVFL 2381
18.343 PVFL[0..numChans-1] 2382
18.344 PVFL[0..2] 2382

- 2175 -
Chapter 18 - Pxxxx Parameters

18.345 PVFL[0..511] 2383


18.346 PVFL[1..512] 2384
18.347 PVFL[1..1000] 2384
18.348 PVFL[1..1968] 2385
18.349 PVFL_DI_S 2385
18.350 PVFORMAT 2386
18.351 PVHHALM.DB 2387
18.352 PVHHALM.DBU 2387
18.353 PVHHALM.FL 2388
18.354 PVHHALM.PR 2388
18.355 PVHHALM.SV 2389
18.356 PVHHALM.TM 2389
18.357 PVHHALM.TMO 2390
18.358 PVHHALM.TP 2390

18.359 PVHIALM.DB 2391


18.360 PVHIALM.DBU 2391
18.361 PVHIALM.FL 2392
18.362 PVHIALM.PR 2392
18.363 PVHIALM.SV 2393
18.364 PVHIALM.TM 2393
18.365 PVHIALM.TMO 2394
18.366 PVHIALM.TP 2394
18.367 PVHILM 2395
18.368 PVHISIGCHG.CT 2395
18.369 PVHISIGCHG.TP 2396
18.370 PVHISIGNAL [0..NUMCHANNELS-1] 2396
18.371 PVLLALM.DB 2398
18.372 PVLLALM.DBU 2399
18.373 PVLLALM.FL 2399
18.374 PVLLALM.PR 2400
18.375 PVLLALM.SV 2400
18.376 PVLLALM.TM 2401
18.377 PVLLALM.TMO 2401
18.378 PVLLALM.TP 2402
18.379 PVLOALM.DB 2402
18.380 PVLOALM.DBU 2403
18.381 PVLOALM.FL 2403
18.382 PVLOALM.PR 2404
18.383 PVLOALM.SV 2404

- 2176 -
Chapter 18 - Pxxxx Parameters

18.384 PVLOALM.TM 2405


18.385 PVLOALM.TMO 2405
18.386 PVLOALM.TP 2406
18.387 PVLOLM 2406
18.388 PVLOSIGCHG.CT 2407
18.389 PVLOSIGCHG.TP 2407
18.390 PVLOSIGNAL [0..NUMCHANNELS-1] 2408
18.391 PVMANOPT 2409
18.392 PVNORMAL 2410
18.393 PVP 2411
18.394 PVRATE 2412
18.395 PVRAW 2412
18.396 PVRAW_AI_S 2414
18.397 PVRAW[0..numChans-1] 2414

18.398 PVRAW[0..120] 2415


18.399 PVRAW[0..numChans-1] 2415
18.400 PVRAWHI 2416
18.401 PVRAWHI[0..numChans-1] 2416
18.402 PVRAWHI[0..120] 2417
18.403 PVRAWLO 2417
18.404 PVRAWLO[0..numChans-1] 2418
18.405 PVRAWLO[0..120] 2418
18.406 PVRAWREF 2419
18.407 PVROCBYPASSFL 2419
18.408 PVROCNEGFL 2420
18.409 PVROCNEGLM 2420
18.410 PVROCPOSFL 2420
18.411 PVROCPOSLM 2421
18.412 PVSCALEFACTOR [0..NUMCHANNELS-1] 2421
18.413 PVSOURCE 2422
18.414 PVSRC 2424
18.415 PVSRCOPT 2424
18.416 PVSTS 2427
18.417 PVSTS[1..NUMCHAN] 2430
18.418 PVSTS[0..63] 2430
18.419 PVSTS[0..120] 2431
18.420 PVSTS[0..1968] 2431
18.421 PVSTS[0..numChans-1] 2432
18.422 PVSTS[0..numChans-1] 2432

- 2177 -
Chapter 18 - Pxxxx Parameters

18.423 PVSTS[1..64] 2433


18.424 PVSTSFL.ALL 2433
18.425 PVSTSFL.BAD 2434
18.426 PVSTSFL.MAN 2434
18.427 PVSTSFL.NORM 2435
18.428 PVSTSFL.UNCERTN 2436
18.429 PVSTS_AI_S 2437
18.430 PVSTSSRC 2438
18.431 PVTEMP 2438
18.432 PVTRAKOPT 2439
18.433 PVTRAKOPTAI 2440
18.434 PVVAL 2440
18.435 PVVAL[0..numChans-1] 2441
18.436 PVVALSTS 2441

18.437 PVVALSTS[0..63] 2443


18.438 PVVALSTS[1..64] 2443
18.439 PVVALSTS[0..511] 2444
18.440 PWMPERIOD 2444
18.441 PWMPERIOD[0..numChans-1] 2445
18.442 PWRGOOD1 2445
18.443 PWRGOOD2 2446
18.444 PWRSUPPLYSF 2446
18.445 PX[1..10] 2446

18.1 P

Specific to Block(s) FLOWCOMP


Description Pressure Input - Indicates the value of the gage pressure.
Data Type 64-Bit Real Number
Range
Default 1.0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence C200, C300, ACE
Related Parameters
Remarks

- 2178 -
Chapter 18 - Pxxxx Parameters

18.2 P[1..6]

Specific to Block(s) AUXCALC, SIGNALSEL


Description Process Input Values 1 through 6.
Data Type 64-Bit Real Number
Range
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters P1STS
Remarks

18.3 P[1..10]

Specific to Block(s) AUXSUMMER, ENHAUXCALC


Description Process Input Values 1 through 10.
Data Type 64-Bit Real Number
Range
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PSTS[1..10]
Remarks

18.4 P0

Specific to FLOWCOMP
Block(s)
Description Zero Reference for Pressure - Define value to compensate for ambient
atmospheric pressure.
Data Type 64-Bit Real Number
Range NaN is not allowed
Default 0.0
Config Load Yes
Active No

- 2179 -
Chapter 18 - Pxxxx Parameters

Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks P0 must be in the same engineering units as the P input. P0 is typically 14.696, if
P is in psia, or 101.325 if P is in kPascals.

18.5 P1

Specific to Block DataAcq, Deadtime, Totalizer, Genln, LeadLag.


(s)
Description Process Input Value #1 - The current value of the process input to a Data
Acquisition function block.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to Block Pulse Input Totalizer


(s)
Description PV Equation Type - Defines the equation (EqA, EqB, ...) to be used with a given
function block.
Data Type Enumeration PVEQN
Range 0 - EqA 1 - EqB 2 - EqC 3 - EqD 4 - EqE 5 - EqF
Default EqA
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

- 2180 -
Chapter 18 - Pxxxx Parameters

Specific to Block(s) ROC


Description Input
Data Type Float64
Range
Default NaN
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks Connects the input who's Rate of change of value needs to be controlled.

18.6 P1CLAMPOPT

Specific to DataAcq
Block(s)
Description Process Input Value #1 (P1) Clamping Option - Defines whether P1 clamping is
used for this function block. If P1CLAMPOPT = Clamp, and the Process Variable (PV)
is beyond its limits ( PVEXLOLMor PVEXHILM), then PUSHSPPVis set equal to the
limit that was violated; PVSTS is set to Uncertain.
Data Type Enumeration ENABLE
Range Disable (0): Do not clamp the Process Variable (PV)
value.
Enable (1): Clamp the Process Variable (PV) to its
high or low limit.
Default Disable (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

- 2181 -
Chapter 18 - Pxxxx Parameters

18.7 P1EU

Specific to Block(s) DataAcq


Description P1EU value
Data Type Real
Range N/A
Default NaN
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

18.8 P1FILTINIT

Specific to Block DataAcq


(s)
Description Process Input Value #1 (P1) Filter Initialization Request Flag - Used to reset
the filtered P1 value.
Data Type Boolean
Range Off (0): Initialization is not requested. On (1): Initialization is requested.
Default Off (0)
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks If the flag is set, the function block will set the filtered P1 value to the current
P1 value.

18.9 P1FILTTIME

Specific to Block(s) DataAcq


Description Process Input Value #1 (P1) Filter Time (in minutes)
Data Type 64-Bit Real Number
Range 0.0 to 1440.0 minutes
Default 0.0

- 2182 -
Chapter 18 - Pxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks The default reading, 0.0, means that no filtering will be done.

18.10 P1STS

Specific to Block(s) DataAcq, Deadtime, Totalizer, Genlin, Leadlag, Pulse Input Totalizer
Description Status of the Process Input #1 - Indicates the current status of P1.
Data Type Enumeration PVVALSTS
Range Bad (0): The P1 value is bad (that is, NaN).
Uncertn (1): The status of the value is uncertain.
Normal (2): The P1 value is good.
Manual (3): The P1 value was manually stored.
Default Bad (0) Pulse Input Totalizer only: Normal (2)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters P1
Remarks

18.11 P2

Specific to Block(s) Deadtime


Description Process Input Value #2
Data Type Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters P2STS
Remarks

- 2183 -
Chapter 18 - Pxxxx Parameters

18.12 P2PEfficiency

Specific to Block(s) TCMI


Description Peer-to-Peer Efficiency
Data Type FLOAT64
Range N/A
Default 0.0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.13 P2PSCANPERIOD

Specific to Block(s) TCMI


Description Peer-to-Peer Scan Period
Data Type FLOAT64
Range N/A
Default 0.0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.14 P2STS

Specific to Block(s) Deadtime


Description Status of Process Input #2
Data Type Enumeration PVVALSTS
Range Bad: (0) (ORD.0)The value is bad and has been replaced with NaN.
Uncertn: (1) (ORD.1)The status of the value is uncertain.
Normal: (2) (ORD.2)The value is good.
Manual: (3) (ORD.3)The value was manually stored.
Default Normal (2)

- 2184 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters P2
Remarks

18.15 PARAMETERREFERENCENAME.DESC

Specific to Block MAP


(s)
Description Parameter reference description
Data Type String
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks It is the descriptive text for the parameter reference. It is configured in PDE of
the Map block.

18.16 PARAMETERREFENCENAME.PREF

Specific to MAP
Block(s)
Description Parameter reference
Data Type INOUTCONN
Default None
Config Load Yes
Active No
Loadable

- 2185 -
Chapter 18 - Pxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related PARAMETERREFENCENAME.TYPE
Parameters
Remarks A parameter reference name is a parameter which is referred to indirectly during
execution. The parameter must have a matching data type.
l Example: If the type is Float, then the reference must be a float type
parameter such as CM.NUMERIC.PV.
l The parameter reference can also be a projected parameter that has
matching TYPE.

18.17 PARAMETERREFENCENAME.TYPE

Specific to MAP
Block(s)
Description Parameter reference type
Data Type String
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related PARAMETERREFERENCENAME.DESC
Parameters
Remarks A parameter reference type is a data type associated with a parameter reference. It
defines the type used when referring to the reference. The type must be:
l BOOLEAN
l ENUM
l FLOAT64
l INT32
l STRING (up to 255 in length)
It is configured in PDE of the Map block.

18.18 PARAMINIT

Specific to RCM, SCM


Block(s)
Description Parameter initialization option
Data Type BOOLEAN
Default OFF
Config Yes
Load

- 2186 -
Chapter 18 - Pxxxx Parameters

Active No
Loadable
Access APPDEVONLY
Lock
Residence OUTPUT
Related NUMACT
Parameters
Remarks PARAMINIT option if ON, initializes the Formula and Report parameters of the
procedure’s Datablock to their default loaded values when the procedure (RCM or
SCM) is commanded to Start. If OFF, the current values are retained in the
Datablock and do not get initialized when the procedure starts. This applies only to
those Formula and Report parameters that are Enabled in the Datablock. In case
Activities are configured for RCM or SCM, the default values of the Procedure
Datablock are loaded to the Activity Datablock when the activity is commanded to
Start. RECTARGET and HISTVALUE parameter arrays are not affected by this option

This feature is not applicable to a Master Recipe or a Control Recipe.

18.19 PARAMNAME[0..500]

Specific to Block(s) RCM


Description Parameter Name
Data Type String
Range 80 Characters
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

18.20 PARENTASSET

Specific to Block All FBs


(s)
Description Parent Asset.
Data Type String
Range Length: 132 Characters
Default Null
Config Load Yes
Active Loadable Yes

- 2187 -
Chapter 18 - Pxxxx Parameters

Access Lock Application Developer


Residence Server/SR
Related
Parameters
Remarks Specifies the Asset Group to be used for asset management and area
grouping for alarms and events.

Specific to Block(s) UOC


Description Parent Asset
Data Type STRING
Range NA
Default
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SRSCANAL
Related Parameters
Remarks

18.21 PARTNERINCOMPATIBLEA/PARTNERINCOMPATIBLEB

Specific to All Series C I/O Modules


Block(s)
Description IOM Partner Not Compatible
Data Type BOOLEAN
Range 0 OFF IOM Partner is redundantly
compatible.
1 ON IOM Partner is not redundantly
compatible.
Default OFF
Config Load No
Access Lock ViewOnly

- 2188 -
Chapter 18 - Pxxxx Parameters

Active No
Loadable
Residence IOLINK
Related Not applicable
Parameters
Remarks This parameter will be asserted on the secondary IOM when the following
conditions are true.
l The primary IOM firmware version is newer than the secondary.
l The primary IOM database is structurally different from the secondaries.
l Redundancy Status is set to SyncFailed.
l Auto Synchronization State is set to Enabled.
l Both partners are present on the I/O Link.
To clear this condition, upgrade the secondary IOM firmware to match the
primaryversion.

18.22 PARTMISMATCH

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Partner Interface mismatch on the I/O Link.
Data Type Boolean
Range Off (0): Correct Partner Interface.
On (1): Partner Interface Mismatch.
Default Off (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence IOLINK
Related
Parameters
Remarks When On (1), it shows the synchronized Primary IOLINK has detected the presence
of an incorrect partner interface module across the I/O Link. Specifically, in the
case of an IOLIM, the primary IOLINK in the chassis m slot n is connected via IOL
with another IOLIM that does not reside in the secondary chassis x slot n. A system
diagnostic alarm is generated for this condition. In the case of C300, the Device
Index of the partner where the C300 IOLINK EE resides in not what is expected.

- 2189 -
Chapter 18 - Pxxxx Parameters

18.23 PARTNOTVIS

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Partner Interface not visible on the I/O Link.
Data Type Boolean
Range Off (0): Parter Interface is Visible.
On (1): Partner Interface is Not Visible.
Default Off (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence IOLINK
Related
Parameters
Remarks When On (1), it shows that the Primary IOLINK is unable to view its redundant
partner across the I/O Link. This only applies if a Redundancy Module (RM) is
resident in the same chassis as the I/O Link Module (IOLIM). A system diagnostic
alarm is generated for this condition. . If the Primary still has visibility to one or
more I/O Processors (IOPs), this diagnostic indicates a problem with the backup
module's I/O Link cables or with the backup IOLIM itself. Do not initiate a
switchover because loss of view is likely. The recommended action is to first check
the cables coming to and then at the backup module, and replace the backup
module next, if the cables are okay. Starting with Experion software R200.0.6 (SP2),
this error causes synchronization to be dropped, to prevent an accidental
switchover and subsequent loss of view.

18.24 PATH

Specific to
Block All Exchange Library Request Array function blocks.
Path to the target device when the target device is on either a ControlNet or Fault
Tolerant Ethernet (FTE) network. Path to the DHRIO module when the target device
Description is on DH+. The path is specified as a comma-separated string of path segments.
Data Type String
Range Maximum of 40 characters
Default Null String
Config
Load Yes
Active
Loadable Yes

- 2190 -
Chapter 18 - Pxxxx Parameters

Access
Lock Application Developer
Residence CEE
Related
Parameters

Enter a PATH to indicate the relative path from the originator device, such as a
C300 or C200 Controller, to the target device. If the originator device is a C200
Controller, its communications network could be either ControlNet or Fault Tolerant
Ethernet (FTE). In either case, you must specify the path as a comma separated list
of path segments. Each path segment is specified as an X, Y pair; where X can
either be 1 to indicate that it is an ICP Backplane segment, or 2 to indicate that it is a
ControlNet/FTE segment. When X is 1, Y denotes a slot number and is in the 0 to 16
range. When X is 2, Y denotes a ControlNet MAC ID and is in the 1 to 99 range or IP
address of node (C300) on FTE, depending on the target network in use. The first
path segment must be an ICP Backplane segment. The path segment types, MAC
IDs or IP address and slot numbers must be specified in decimal values. If the
originator device is a C300 Controller on a FTE network, you must specify the path
as a comma separated list of path segments. Each path segment is specified as an
X, Y pair. It must start with 2 to indicate that it is a FTE segment followed by the IP
address of the target device. When the target device is a C300 Controller, path
segment must be only a single X, Y pair with X as 2 and Y as the IP address of the
target C300. When the target device is a C200 Controller, path segment must be
specified as 2, IP address of Fault Tolerant Ethernet Bridge module (FTEB) followed
by the X, Y pair. When X is 1 (indicating that this is an ICP Backplane segment), Y
denotes a slot number of the target and is in the 1 to 16 range. In a special case of
exchange communication between a C200 Controller on ControlNet and C300
Controller on FTE, the path will have multiple hops. For example, hops could be
C200-CNI-CNI-FTEB-C300. Then the path should be 1, slot number of the CNI, 2 to
indicate that it is a ControlNet segment, MAC ID of the CNI, 1, slot number of the
Remarks FTEB, 2 to indicate that it is a FTE segment, IP address of the C300.

18.25 PATHBRKSTS

Specific to HRBALG_REG, HRBALG_DI, HRBALG_AI HRBALG_PIUAI, HRBALG_HLPIUAO,


Blocks HRBALG_HLPIUDI, HRBALG_HLPIUDO HRBALG_HLPIUCO, HRBALG_HLPIUAC,
HRBALG_HLPIUDC
Description Path Break Status
Data Type ENUM
Range 0 – INOUTERR 1 – OK 2 – INERR 3 – OUTERR
Default INOUTERR
Config. No
Load
Access Lock View Only
Residence CEE
Related
Parameters
Remarks For Regulatory points INOUTERR - Both Input and Output Failure OK - Everything
OK INERR - Input path error OUTERR - Output path error For Input points OK -
Everything OK INERR - Input path error For Output points OK - Everything OK
OUTERR - Output path error

The following table summarizes the various scenarios in which path break condition can occur and

- 2191 -
Chapter 18 - Pxxxx Parameters

the corresponding path break status:

Scenario Path break status


CEE idle INERR
BOX HRB inactive INERR
BOX HRB active OK
Algo HRB inactive INERR
Algo HRB active OK
Input module inactive INERR
IO Module removal / firmware download /IO link failure INERR
Input channel inactive INERR
Input wire break INERR

18.26 PAUSEFL

Specific to Block(s) SCM, RCM


Description Pause Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

Specific to Up / Down Counter Block


Block(s)
Description Pause Flag
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related RESETFL, LOADFL
Parameters
Remarks This parameter is sensed as a level input, which does not self-clear on a block
execution. If the parameter is set to “TRUE”, count up or count down activity is
inhibited.

- 2192 -
Chapter 18 - Pxxxx Parameters

18.27 PCENGINEVER

Specific to Block(s) ProfitCtl


Description Profit Controller version
Data Type FLOAT64
Range NA
Default 430.1
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

18.28 PCMCOMMAND

Specific to CPM
Block(s)
Description Command parameter for changing PCMSTATE
Data Type Enumeration PCMCOMMAND
Range None (0) Shutdown (1)
Default None (0)
Config No
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PCMSTATE
Parameters
Remarks Shutdown can be commanded when the CEESTATE is IDLE, which takes the CPM
to the PIREADY (RDY) state. No other value of PCMSTATE can be commanded. Note
that in the future the name of this parameter will be changed to CPMCOMMAND.

18.29 PCMSTATE

Specific to CPM
Block(s)
Description Current state of CPM block.
Data Type Enumeration of PCMSTATE
Range OFFNET (0) TESTING (1) BOOTING (2) ALIVE (3) LOADING (4) OK (5) FAILED (6)

- 2193 -
Chapter 18 - Pxxxx Parameters

PIREADY (7) BACKUP (8) NOTLOADED (9) NOCEE (10) CEEIDLE (11) CEERUN (12)
CEEMIX (13)
Default OK (5)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PCMCOMMAND
Parameters
Remarks Note that in the future the name of this parameter will be changed to CPMSTATE.

Specific to C300 FBs


Block(s)
Description C300 Module State.
Data Type Enumeration
Range OFFNET (0) TESTING (1) BOOTING (2) ALIVE (3) LOADING (4) OK (5) FAILED (6)
PIREADY (7) BACKUP (8) NOTLOADED (9) NOCEE (10) CEEIDLE (11) CEERUN (12)
CEEMIX (13)
Default NOTLOADED (9)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300
Related PCMCOMMAND
Parameters
Remarks

18.30 PCMNUMPRI

Specific to Block(s) UOC


Description Primary PCM number
Data Type UINT16
Range 0 to 65535
Default 0
Config Load No

Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

- 2194 -
Chapter 18 - Pxxxx Parameters

18.31 PCMNUMSEC

Specific to Block(s) UOC


Description Secondary PCM number
Data Type UINT16
Range 0 to 65535
Default 0
Config Load No

Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

18.32 PCODESIZE[1..8]

Specific to Block(s) AUXCALC, ENHAUXCALC, ENHREGCALC, REGCALC


Description Pcode Size - Defines the size of the pcode for each expression.
Data Type 32-Bit Integer
Range 0 to 100
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameter
Remarks This parameter must be set by Control Builder.

18.33 PCONN[1..10]

Description Process Input Connection - Holds the connector of each input (P[1..10])
parameter
Data Type 64-Bit Real Number
Range
Default
Config Load No
Active Loadable No

- 2195 -
Chapter 18 - Pxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related P[1..10]
Parameter
Remarks

18.34 PCOVERRUN

Specific to ProfitCtl
Block(s)
Description PC Over Run Count
Data Type INT16
Range NA
Default 0
Config Load No
Active No
Loadable
Access Lock VIEWONLY
Residence NOLOAD
Related MAXPCOVERRUN
Parameters
Remarks If PCOVERUN > MAXPCOVERRUN, block goes into OFF state. This situation can
occur when for consecutive execution periods, block does not finish its execution

18.35 PDELAYDIRCHG

Specific to Pulse Length Control, Pulse Count Control


Block(s)
Description Delay (in seconds) before Pulse Output begins to react.
Data Type 64-Bit Real Number
Range Greater-than or equal-to 0.0 and a multiple of the containing Control Module
Default 0.0
Config Yes
Load
Active No
Loadable

- 2196 -
Chapter 18 - Pxxxx Parameters

Access Engineer
Lock
Residence CEE
Related
Parameter
Remarks Pulse Delay after Direction Change - specifies (in seconds) the delay time for
starting a pulse (on PORAISE, POLOWER, and PO outputs) after a change in
direction (PODIR output).

18.36 PDESC[1..10]

Specific to Block AUXSUMMER, ENHAUXCALC, SIGNALSEL


(s)
Description Process Input Description - Specifies description associated with each input (P
[1..10] parameter.
Data Type String
Range
Default
Config Load Yes
Active Loadable Yes
Access Lock Application Developer Only
Residence SR
Related P[1..10]
Parameters
Remarks

18.37 PDFIFORATEA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Average Process Data FIFO Access Rate. Shows the average number of parameters
accessed through process data FIFO per second.
Data Type 32-Bit Real Number
Range N/A
Default 0
Config Load No
Active No
Loadable

- 2197 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related
Parameters
Remarks

18.38 PDFIFORATEM

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Maximum Process Data FIFO Access Rate. Shows the maximum number of
parameters accessed through process data FIFO per second.
Data Type 32-Bit Real Number
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

18.39 PDTEIMIP

Specific to Block(s) C300 CEE


Description EIM IP Address
Data Type STRING
Range 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks In the PDT connection from C300 to EIM, this is the IP address of the target
EIM.

- 2198 -
Chapter 18 - Pxxxx Parameters

18.40 PDTCONNSTS

Specific to Block(s) EIM EIP Protocol Block


Description PDT Connection Status
Data Type ENUM
Range None Connected Timedout Closed
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters -
Remarks PDT connection status between the C300 and EIM.

18.41 PDTEIMCONNSTS

Specific to Block C300 CEE


(s)
Description PDT Connection Status
Data Type ENUM
Range None Connected Timedout Closed
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks In the PDT connection from C300 to EIM, this is the connection status of the
PDT connection.

18.42 PDTEIMAVGRXPKTS

Specific to Block(s) C300 CEE


Description Average Rx Packet Rate
Data Type FLOAT64
Range -
Default 0
Config Load No

- 2199 -
Chapter 18 - Pxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters -
Remarks Average Receive PDT Packet Rate from EIM to C300 in Packets/Second.

18.43 PDTEIMMAXRXPKTS

Specific to Block(s) C300 CEE


Description Maximum Rx Packet Rate
Data Type FLOAT64
Range -
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters -
Remarks Maximum Receive PDT Packet Rate from EIM to C300 in Packets/Second.

18.44 PDTTGTIPADDR

Specific to Block EIM EIP Protocol Block


(s)
Description PDT Target IP Address
Data Type String
Range -
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related -
Parameters
Remarks Target IP address for the PDT Connection in EIM – in this case it is the IP
address of the C300

- 2200 -
Chapter 18 - Pxxxx Parameters

18.45 PEAKFTEABLOCKRATE

Specific to Block(s) TCMI


Description FTE A Block Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of packets per second blocked (by CF9 firewall) on FTE B
interface.

18.46 PEAKFTEBBLOCKRATE

Specific to Block(s) TCMI


Description FTE B Block Rate Max (pkts/sec)
Data Type UINT32
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of packets per second blocked (by CF9 firewall) on FTE B
interface.

- 2201 -
Chapter 18 - Pxxxx Parameters

18.47 PEAKFTEARXRATE

Specific to TCMI
Block(s)
Description Local Area Network (LAN) A Receive Rate Maximum- Identifies maximum
communication receive rate in kilobits per second (kbps) for port A (Green Tree Port)
on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

18.48 PEAKFTEBRXRATE

Specific to TCMI
Block(s)
Description Local Area Network (LAN) B Receive Rate Maximum- Identifies maximum
communication receive rate in kilobits per second (kbps) for port B (Green Tree Port)
on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

- 2202 -
Chapter 18 - Pxxxx Parameters

18.49 PEAKFTEATXRATE

Specific to TCMI
Block(s)
Description Local Area Network (LAN) A Transmit Rate Maximum- Identifies maximum
communication transmission rate in kilobits per second (kbps) for port A (Green Tree
Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

18.50 PEAKFTEBTXRATE

Specific to TCMI
Block(s)
Description Local Area Network (LAN) B Transmit Rate Maximum- Identifies maximum
communication transmission rate in kilobits per second (kbps) for port B (Green Tree
Port) on the FTE interface.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence FTEB, C300, FIM4, PGM, EHPM
Related LANBFAILED
Parameters
Remarks

- 2203 -
Chapter 18 - Pxxxx Parameters

18.51 PEERAGETIME

Specific to SCM, RCM


Block(s)
Description Peer Age Time- Specifies the peer age time in seconds
Data Type Float64
Range 0.0075-160.0 (Min: PERIOD *1.5 ... Max: PERIOD *8)
Default 3.0
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PENABLE[1..10]PERIODSUBSCPERIOD
Parameters
Remarks Parameter has no effect, if PEERALGOPT is set to None. Range check: If the value
is lower than 1.5 * PERIOD, a Value Clamped warning appears and the value will be
set to 1.5 * PERIOD. If the value is greater than 8 * PERIOD, a Value Clamped
warning appears and the value will be set to 8 * PERIOD. Be aware, that
PEERAGETIME value must be greater then SUBSCPERIOD value.

18.52 PEERALGOPT

Specific to SCM, RCM


Block(s)
Description Peer Algorithm Option which determines how peer data is accessed by a SCM or
RCM.
Data Type Enumeration of CscoPeerAlgOpt.enm.xml
Range None (0) No RTable will be allocated; cyclic get requests of all
get connectors of the SCM will be permanently
enabled.
Auto (1) The SCM itself computes the necessary size of the
RTable. Algorithm to estimate the optimal size: S =
total number of steps and phases per SCM/RCM T
= total number of transitions per SCM/RCM H =
total number of handlers per SCM/RCM SN = max.
number of next handles in a step or phase, 0 if no
steps and no phases SF = number of steps and
phases with FORCEREADREQ=ON TF = number of
transitions with FORCEREADREQ=ON XN = max.
number of next handles in a sync object, XN=1 if
there are no sync objects TM = max. number of
transitions per handler SM = max. number of steps
and phases per handler KR = tuning constant for
RTable calculation, KR represents the length of a
mini-sequence of steps which can be passed,
normally during PEERAGETIME. LT = TM/XN,
rounded up to integer LS = SM/XN, rounded up to

- 2204 -
Chapter 18 - Pxxxx Parameters

integer RS1 = S + T RS2 = { MAX(0,(SN-1)) + MIN


(LS,KR) + MIN(LT,KR) } * XN+ H + SF + TF RS = MIN
(RS1,RS2) The RTable is allocated for RS parts.
Note: Only the first 100 handlers will be processed
by the AUTO algorithm. If more handlers are
detected, a download warning will be shown, “More
Than 100 Handlers Detected.”
Max (2) The RTable is allocated for Max Value= (total
number of Steps + total number of Phases + total
number of Transitions).
50_Percent (3) The RTable is allocated for Max value / 2 parts.
33_Percent (4) The RTable is allocated for Max value / 3 parts.
25_Percent (5) The RTable is allocated for Max value / 4 parts.
20_Percent (6) The RTable is allocated for Max value / 5 parts.
10_Percent (7) The RTable is allocated for Max value / 10 parts.
Default None (0)
Config Yes
Load
Active No
Loadable
Access AppDevOnly
Lock
Residence CEE
Related PEERAGETIME, DYNPEERALLOC
Parameters
Remarks Is located on the Main page of the SCM or RCM configuration form. PEERALGOPT =
NONE uses the smallest amount of memory and causes the highest
communication load. PEERALGOPT = MAX uses the highest amount of memory and
causes lower communication load. It may also cause slower execution of some
SCMs / RCMs depending on application logic. PEERALGOPT = AUTO is the
recommended value to reduce communication load while balancing memory. The
other values are provided as workarounds in case AUTO computes an unsuitable
memory allocation. If any other value is used, extensive testing of the SCM or RCM
is required since it is possible that SCM or RCM gets stuck with 2795-
CodeDataNotEnabledError. This is not a system problem, but caused by the fact,
that the configuration did not allocate sufficient memory for the communication
needs of the particular SCM or RCM. In this case the value shall be increased. If a
value of AUTO causes a 2795-CodeDataNotEnabledError, report to TAC or other
Honeywell support channel. In this case a value of MAX shall be used instead. If a
value other than NONE is selected, Chart Monitoring in Control Builder and Station
will return errors for some data of SCMs and RCMs as long as they are inactive. This
is not a system problem but part of the feature, that peer communication load
caused inactive SCMs and RCMs is zero.

Specific to MR
Block(s)
Description Peer Algorithm Option which determines how peer data is accessed by a MR.
Data Type Enumeration of CscoPeerAlgOpt.enm.xml
Range None (0) No RTable will be allocated; cyclic get requests of all get connectors of
the SCM will be permanently enabled.
Auto (1) The SCM itself computes the necessary size of the RTable. Algorithm

- 2205 -
Chapter 18 - Pxxxx Parameters

to estimate the optimal size: S = total number of steps and phases per
SCM/RCM T = total number of transitions per SCM/RCM H = total
number of handlers per SCM/RCM SN = max. number of next
handles in a step or phase, 0 if no steps and no phases SF = number
of steps and phases with FORCEREADREQ=ON TF = number of
transitions with FORCEREADREQ=ON XN = max. number of next
handles in a sync object, XN=1 if there are no sync objects TM = max.
number of transitions per handler SM = max. number of steps and
phases per handler KR = tuning constant for RTable calculation, KR
represents the length of a mini-sequence of steps which can be
passed, normally during PEERAGETIME. LT = TM/XN, rounded up to
integer LS = SM/XN, rounded up to integer RS1 = S + T RS2 = { MAX(0,
(SN-1)) + MIN(LS,KR) + MIN(LT,KR) } * XN+ H + SF + TF RS = MIN
(RS1,RS2) The RTable is allocated for RS parts. Note: Only the first 100
handlers will be processed by the AUTO algorithm. If more handlers
are detected, a download warning will be shown, “More Than 100
Handlers Detected.”
Max (2) The RTable is allocated for Max Value= (total number of Steps + total
number of Phases + total number of Transitions).
50_Percent The RTable is allocated for Max value / 2 parts.
(3)
33_Percent The RTable is allocated for Max value / 3 parts.
(4)
25_Percent The RTable is allocated for Max value / 4 parts.
(5)
20_Percent The RTable is allocated for Max value / 5 parts.
(6)
10_Percent The RTable is allocated for Max value / 10 parts.
(7)
Default Auto (1)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related PEERAGETIME, DYNPEERALLOC
Parameters
Remarks

18.53 PEERALIASENB

Specific to Block(s) SCM


Description Number of Enabled Peers in Alias Table
Data Type 32-Bit Integer
Range
Default 0

- 2206 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

18.54 PEERALIASNUM

Specific to Block(s) SCM


Description Number of Peer Connections in Alias Table
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

18.55 PEERENV[ ]

Specific to CEEC300, CEE, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description Peer Environment
Data Type BlockId
Range N/A
Default N/A
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300(CEEC300), C200(CEE), ACE(CEEACE), SIMC200(CEESIMC200) , UOC
(CEEUOC), CN100(CEECN100)
Related NUMPEERENV[ ], PEERSTRRESP [ ], PEERSUBSCPER [ ], STRRESP[ ],
Parameters SUBSCPERIOD.
Remarks Specifies the peer environment that is to have specific peer subscription period
(PEERSUBSCPER[ ]) and peer store response time (PEERSTRRESP[ ]) values
configured for it.

- 2207 -
Chapter 18 - Pxxxx Parameters

18.56 PEERGETAVG [1..30]

Specific to CEEC300, CEE, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description Average Peer Get Requests
Data Type Float64
Range N/A
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), ACE(CEEACE), SIM_C200(CEESIMC200), UOC
(CEEUOC), CN100(CEECN100)
Related NUMPEERENV[ ], PEERENV[ ]STATSRESET.
Parameters
Remarks Provides the running average of get responses per second to this CEE received
from the peer environment, identified by corresponding PEERENV [index]. If there
is no connection between the two peer environments, 0 will be returned. The
characteristic time constant of the average is 1 minute. Wait 2-3 minutes to be sure
averaging has fully settled. Averaging can be restarted by triggering the
STATSRESET parameter.

18.57 PEERINPUTENB

Specific to Block(s) SCM


Description Number of Enable Peers in SCM
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2208 -
Chapter 18 - Pxxxx Parameters

18.58 PEERINPUTNUM

Specific to Block(s) SCM


Description Number of Peer Connections in SCM
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

18.59 PEERRATEAVG

Specific to Block IOLIM, Secondary IOLIM, C300 IOLINK , FIM, CPM


(s)
Description Peer Rate Average. Shows the average peer-to-peer update rate in
parameters per second.
Data Type 32-Bit Real Number
Range N/A
Default 0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

18.60 PEERRATEMAX

Specific to Block IOLIM, Secondary IOLIM, C300 IOLINK, FIM, CPM


(s)
Description Peer Rate Maximum. Shows the maximum peer-to-peer update rate in
parameters per second.
Data Type 32-Bit Real Number
Range N/A
Default 0.0

- 2209 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related
Parameters
Remarks

18.61 PEERREADOPT

Specific to Control Module


Block(s)
Description Peer Read Option
Data Type Enumeration
Range PUBSUB PREFETCH
Default PUBSUB
Config Yes
Load
Active No
Loadable
Access Application Developer Only
Lock
Residence CEE
Related
Parameters
Remarks Enumeration configuration parameter added to specify PEERREADOPT. For ACE,
this parameter can take the value of either PUBSUB or PREFETCH. Any change in
value of this parameter requires a reload of the CM. Note that store of PERIOD
returns a value clamped warning when it cannot support configured value of
PEEREADOPT. The Peer read option is validated with the execution period during
the load of the CM. If the CM is configured with PEERREADOPT of PREFETCH, it
must have the PERIOD greater than the configured prefetch anticipation time or
PFANTICTIME. Otherwise, it is clamped to PUBSUB. For ACE Control modules
configured for Block Process Special (BPS), there is no validation between the
execution period and the Peer Read Option of Prefetch during load. Note: For a CM
configured with PEERREADOPT = PREFETCH, all peer data is fetched using
PREFETCH. It is not possible to use the same CM for fetching peer data using
prefetch and Pubsub simultaneously.

- 2210 -
Chapter 18 - Pxxxx Parameters

18.62 PEERSTRAVG [1..30]

Specific to CEEC300, CEE, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description Average Peer Store Requests
Data Type Float64
Range N/A
Default 0.0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300), C200(CEE), ACE(CEEACE), SIM_C200(CEESIMC200), UOC
(CEEUOC), CN100(CEECN100)
Related NUMPEERENV[ ], PEERENV[ ], STATSRESET.
Parameters
Remarks Provides the running average of acyclic stores added per second from this CEE sent
to the peer environment, identified by corresponding PEERENV[index]. If there is
no connection between the two peer environments, 0 will be returned. The
characteristic time constant of the average is 1 minute. Wait 2-3 minutes to be sure
averaging has fully settled. Averaging can be restarted by triggering the
STATSRESET parameter.

18.63 PEERSTRRESP [ ]

Specific to CEEC300, CEE, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description Peer Store Response Time - Specifies the specific store response expiration time to
be used for the corresponding peer environment number (PEERENV[ ]) in seconds.

Data Type Float64


Range Greater than 0
Default 15.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300(CEEC300), C200(CEE), ACE(CEEACE), SIM_C200(CEESIMC200), UOC
(CEEUOC), CN100(CEECN100)
Related NUMPEERENV[ ], PEERENV[ ], STRRESP[]
Parameters
Remarks If a store response is not received within the configured expiration time, the store is
marked failed.

- 2211 -
Chapter 18 - Pxxxx Parameters

18.64 PEERSUBSCPER [ ]

Specific to CEEC300, CEE, CEEACE, CEESIMC200, CEEUOC, CEECN100


Block(s)
Description Peer Subscription Period
Data Type Enumeration
Range Varies for given CEE
Default Varies for given CEE
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C300(CEEC300), C200(CEE), ACE(CEEACE), SIM_C200(CEESIMC200), UOC
(CEEUOC), CN100(CEECN100)
Related NUMPEERENV[ ], PEERENV[ ], SUBSCPERIOD
Parameters
Remarks Specifies the specific update period to be used for the corresponding peer
environment number (PEERENV[ ]) in seconds.

18.65 PENABLE[1..10]

Specific to Block(s) ENHAUXCALC


Description Enable/Disable Switch
Data Type Boolean
Range (0) False (Disabled) (1) True (Enabled)
Default True
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

18.66 PERFRATIOBACKOFFTOL

Specific to Block(s) ProfitCtl


Description Perf Ratio Backoff Tol
Data Type FLOAT64
Range NA
Default 0

- 2212 -
Chapter 18 - Pxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

18.67 PERIOD

Specific to CM, IOM, SCM, RCM, UCM, PIOMB


Block(s)
Description Execution Period - Specify an execution/processing period (or scan rate) of a block
in milliseconds (ms). The Execution Period is the amount of time between two
consecutive executions of the block. For example, if the Execution Period of a block
is 500 ms, then the block will run twice per second. The valid values and function
of the Default value for PERIOD are different for the 50 and 5 ms CEE
personalities as described in the Remarks section.
Data Type Enumeration of PERIOD
Range IOM only: 5 TO 2000 ms:
DEFAULT(0) 100ms(5)
5ms(1), 200ms(6)
10ms(2) 500ms(7)
20ms(3) 1000ms(8)
50ms(4) 2000ms(9)

CEE 5 ms TO 24 hr:
Configurable
DEFAULT(0) NONE(14)
Range:
5ms(1), 30sec(15)
10ms(2) 1min(16)
20ms(3) 2min(17)
40ms() 5min(18)
50ms(4) 10min(19)
100ms(5) 20min(20)
200ms( 6) 30min(21)
500ms(7) 1hr(22)
1000ms(8) 2hr(23)
2000ms(9) 4hr(24)
5sec(10) 8hr(25)
10sec(11) 12hr(26)
20sec(12) 24hr(27)
25ms(13)

- 2213 -
Chapter 18 - Pxxxx Parameters

Valid Range, 50 to 2000 ms:


50 ms CEE
DEFAULT(0)* 500ms(7)
50ms(4) 1000ms(8)
100ms(5) 2000ms(9)
200ms(6)

Valid Range, 5 to 200 ms:


5 ms CEE
DEFAULT(0)* 50ms(4)
5ms(1) 100ms(5)
10ms(2) 200ms(6)
20ms(3)

Valid Range, 500ms to 24hr


500ms
CEEACE
DEFAULT(0)*
500ms (7) 5min (18)
1sec (8) 10min (19)
2sec (9) 20min (20)
5sec (10) 30min (21)
10sec (11) 1hr (22)
20sec (12) 2hr (23)
NONE (14) 4hr (24)
30sec (15) 8hr (25)
1min (16) 12hr (26)
2min (17) 24hr (27)
* DEFAULT(0) is converted to an actual value upon load: Converted to 1000 ms for
the 50 ms CEE Converted to 200 ms for the 5 ms CEE Converted to 2 sec for the
500 ms CEEACE
Default Default
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PEERSTRAVG [1..30], PEERSTRAVG [1..30], PHASE, for SCM and RCM only:
Parameters PEERSTRAVG [1..30]
Remarks Determines execution period for a container block and its component blocks. Units
are in milliseconds. Can be changed while the container block is Inactive without
requiring reload. If you change the value of PERIOD online, a check is made to
determine whether the new PERIOD matches the currrent PEERAGETIME value
or not. If it does not match, the store of the new PERIOD value generates an
Invalid Period For Peer Age Time error.

- 2214 -
Chapter 18 - Pxxxx Parameters

Specific to DOCHANNEL, Series C DOCHANNEL


Block(s)
Description Pulse Width Modulated (PWM) Period. Specifies the status output period length in
seconds for a digital output point with DOTYPE configuration of PWM.
Data Type 32-Bit Real Number
Range 1.0 to 120.0 seconds
Default 10.0 seconds
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence IOM
Related
Parameters
Remarks

18.68 PERIODENUMMASK

Specific to Block(s) SCM


Description Execution Period Enumeration Mask
Data Type String
Range
Default null
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

18.69 PERIODSEC

Specific to CM, SCM, RCM, MR, CR


Block(s)
Description Execution period of a Control Module expressed in seconds.
Data Type FLOAT64
Range 0 to 86400
Default Follows default PERIOD parameter values of the CEE.
Config Load No
Active No

- 2215 -
Chapter 18 - Pxxxx Parameters

Loadable
Access Lock View Only
Residence CEE
Related PERIOD SCALEPERIOD
Parameters
Remarks If the value of this parameter is uninitialized or NaN, returns the SCALEPERIOD
parameter value when read.

18.70 PERSONALITYDAY

Specific to Block(s) TCMI


Description Current Day of Personality Image
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.71 PERSONALITYMONTH

Specific to Block(s) TCMI


Description Current Month of Personality Image
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 2216 -
Chapter 18 - Pxxxx Parameters

18.72 PERSONALITYNAME

Specific to Block(s) TCMI


Description Personality Name
Data Type STRING
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.73 PERSONALITYREV

Specific to Block(s) TCMI


Description Personality Revision
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 2217 -
Chapter 18 - Pxxxx Parameters

18.74 PERSONALITYVER

Specific to Block(s) TCMI


Description Personality Version
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.75 PERSONALITYYEAR

Specific to Block(s) TCMI


Description Current Year of Personality Image
Data Type UINT16
Range N/A
Default 0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.76 PERSWAPENB

Specific to C200IOLINK, C300 IOLINK


Block(s)
Description I/O Link Periodic Cable Swap. Lets users initiate a periodic cable swap.
Data Type Boolean
Range Off (0): Swapping of I/O Link cables A & B is
disabled.
On (1): Swapping of I/O Link cables A & B is
enabled.

- 2218 -
Chapter 18 - Pxxxx Parameters

Default Off (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30], PERSWAPTHRES.
Parameters
Remarks When more than PERSWAPTHRES parameter errors are detected within a one-
minute period, the PERSWAPENB parameter is automatically set to Off (disabled).
Note that this is the same as the IOLPERSW parameter in a TPS system.

18.77 PERSWAPTHRES

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Periodic Cable Swap Error Threshold (err/min). Defines the acceptable rate of I/O
link communication errors in errors per minute before the status of the cable
transitions to ERROR.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 10
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30], PEERSTRAVG [1..30].
Parameters
Remarks Note that this is the same as the IOLCHERT parameter in a TPS system.

18.78 PFANTICTIME

Specific to ACE
Block(s)
Description Prefetch Anticipation Time(sec)
Data Type FLOAT64
Range 1 to 10 (Granularity 0.5)
Default 1
Config Yes
Load
Active No
Loadable

- 2219 -
Chapter 18 - Pxxxx Parameters

Access Application Developer Only


Lock
Residence CEE
Related
Parameters
Remarks Configurable Prefetch Anticipation Time (PAT) in Seconds per
ACE. This value indicates the time before the execution of the
CM when prefetch will be triggered. The PFANTICTIME value
can be configured in the granularity of 0.5.For example, the
possible values can be 1, 1.5, 2, 2.5, 3, 3.5, 4...10. PFANTICTIME
will be clamped/rounded as follows:
l Out of range, which is less than minimum (1) and greater
than maximum (10), will be rejected.
l For values within range:

Entered Value Rounded/Clamped


value
>=X+0 and <=X+0.25 X
>X+0.25 and <=X+0.75 X+0.5
>X+0.75 and <=X+1 X+1
Where X is an integer between 1 and 10 (both inclusive) For example:
l If the entered value is 1.20 (>=1 and <=1.25), it will be clamped to 1.
l If the entered value is 1.3 or 1.7 (>1.25 and <=1.75), it will be clamped to 1.5.
l If the entered value is 1.8 (>1.75 and <=2), it will be rounded to 2.
Note: If a larger PAT value is configured for a node that responds with the data
faster, then the value used in block execution will not be fresh and can lead to
incorrect results.

18.79 PFREQ

Specific to Block(s) OPC Gateway


Description Total Prefetch Requests
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence

Related Parameter
Remarks Total number of prefetch requests processed by OPC Gateway.

- 2220 -
Chapter 18 - Pxxxx Parameters

18.80 PFREQAVG

Specific to Block(s) OPC Gateway


Description Average Prefetch Requests Rate
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence

Related Parameter
Remarks Average prefetch requests processed per second by OPC Gateway.

18.81 PFREQMAX

Specific to Block(s) OPC Gateway


Description Maximum Prefetch Requests Rate
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence

Related Parameter

Remarks Maximum number of prefetch requests processed per second by OPC


Gateway.

18.82 PHASE

Specific to CM, IOM, SCM


Block(s)
Description Determines the set of cycles in which a container block executes.
Data Type 16-Bit Integer
Range 0 to (CM/SCM Period in ms/CEE Base Execution Period in ms) - 1
Default 0
Config Yes
Load

- 2221 -
Chapter 18 - Pxxxx Parameters

Active No
Loadable
Access Lock Engineer
Residence CEE
Related PEERSTRAVG [1..30], PEERSTRAVG [1..30], PEERSTRAVG [1..30], PENABLE
Parameters [1..10]PERIOD
Remarks The combination of PHASE and PERIOD uniquely determine the set of cycles in
which a container block executes. As the maximum PHASE parameter value is
supported for ACE is 119, the formula is applicable when CM/SCM Execution Period
is 1 minute.

18.83 PHASEHOUR

Specific to Control Module in ACE


Block(s)
Description Phase hours are not tied to controller wall clock time. The 0 value for phase hour
may occur at any wall clock time. The controller cycles through phase hours from 0
to 23 during a 24 hour period. The PHASEHOUR value approximates the behavior
of the PHASE value. For periods of execution less than 1 hour, this parameter has
no effect. A one hour PERIOD can only have a PHASEHOUR of zero indicating that
it executes in every PHASEHOUR. A two hour PERIOD can be assigned
PHASEHOUR values of 0 or 1 indicating which set of alternating phase hours (0, 2,
4, ... or 1, 3, 5, ...) the block executes. Similarly, a 4 hour block can be assigned
PHASEHOUR values from 0 to 3, an 8 hour block can have values 0 to 7, and a 24
hour block can values 0 to 23.
Data Type INT16
Range 0 to 23
Default -1
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related PERIOD, PHASE, PHASEMIN
Parameters
Remarks Configuring a value of -1 causes the controller to select a value between 0 and 23
during load. The value selected by the controller will be one that is less used in
currently loaded control modules.

- 2222 -
Chapter 18 - Pxxxx Parameters

18.84 PHASEMIN

Specific to Control Module in ACE


Block(s)
Description Phase minutes are not tied to controller wall clock time. The zero value for phase
minute may occur at any wall clock time. The controller cycles through phase
minutes from 0 to 59 during a 60 minute period. The PHASEMINUTE value
approximates the behavior of the PHASE value. For periods of execution less than 1
minute, this parameter has no effect. A one minute PERIOD can only have a
PHASEMINUTE of zero indicating that it executes in every PHASEMINUTE. A two
minute PERIOD can be assigned PHASEMINUTE values of 0 or 1 indicating which
set of alternating phase minutes (0, 2, 4, ... or 1, 3, 5, ...) the block executes. Similarly,
a 5 minute block can be assigned PHASEMINUTE values from 0 to 4 and a 10
minute block can have values 0 to 9. In addition, a 20 minute block can values 0 to
19 and a 30 minute block can have PHASEMINUTE values from 0 to 29. Blocks with
period values of one hour or greater can be assigned PHASEMINUTE values from 0
to 59 indicating that the block can be assigned to execute on any PHASEMINUTE of
the PHASEHOUR.
Data Type INT16
Range 0 to 59
Default -1
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related PERIOD, PHASE, PHASEHOUR
Parameters
Remarks Configuring a value of -1 causes the controller to select a value between 0 and 59
during load. The value selected by the controller is one that is less used in currently
loaded control modules.

18.85 PHASENAME[0..500]

Specific to Block(s) RCM


Description Phase Name of Formula Parameter
Data Type String
Range 80 Characters
Default
Config Load Yes
Active Loadable No

- 2223 -
Chapter 18 - Pxxxx Parameters

Access Lock Application Developer Only


Residence SR
Related Parameters
Remarks

18.86 PHWYPRTLC

Specific to Experion Hiway Bridge (EHB) platform block, ELCN_NODE (EHB)


Blocks
Description Local partner
Data Type Block ID
Range Tag name of the one other EHB connected to same Server cluster, the same LCN,
and formerly the same Hiway.
Default Blank
Config. No
Load
Active
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter specifies the tag name of the EHB, if any, which is connected to the
same LCN under the same Server cluster and which had been connected to the
same physical Hiway through a partner HG. There can be no more than one other
EHB which replaces an HG on the same LCN and the same physical Hiway.

18.87 PHWYPRTLCIP

Specific to Experion Hiway Bridge (EHB) platform block, ELCN_NODE (EHB)


Blocks
Description Local Partner Address
Data Type IP Address String
Range
Default Blank
Config. No
Load
Active
Loadable

- 2224 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence SR
Related
Parameters
Remarks This parameter specifies the IP address of the EHB indicated by the PHWYPRTLC
parameter. The value of PHWYPRTLCIP parameter is automatically populated so
that it is always consistent with PHWYPRTLC.

18.88 PHWYPRTLCIPISRED

Specific to Blocks ELCN_NODE


Description Local Partner is Redundant
Data Type BOOLEAN
Range off(0) - Local Partner is not redundant
On (0) - Local Partner is not redundant
Default Off(0)
Config. Load Yes
Active Loadable No

Access Lock AppDevOnly


Residence SR
Related Parameters PHWYPRTLC, PHWYPRTLCIP

Remarks

18.89 PHWYPRTRMIP1

Specific to Experion Hiway Bridge (EHB) platform block, ELCN_NODE (EHB)


Blocks
Description Remote Partner 1 Address
Data Type IP Address String
Range
Default Blank
Config. No
Load
Active
Loadable

- 2225 -
Chapter 18 - Pxxxx Parameters

Access ViewOnly
Lock
Residence SR
Related
Parameters
Remarks This parameter specifies the IP address of an EHB which replaces an HG that had
been connected to the same TDC2000 physical Hiway but to a different LCN. When
DFNPHWYEM is set to OFF, the PHWYPRTRMIP1 parameter is unconfigured in the
form. Instead, when the EHB platform block is loaded, it is populated automatically
based on the partner EHB indicated by HWYNUM.

18.90 PHWYPRTRMIP2

Specific to Experion Hiway Bridge (EHB) platform block, ELCN_NODE (EHB)


Blocks
Description Remote Partner 2 Address
Data Type IP Address String
Range
Default Blank
Config. No
Load
Active
Loadable
Access ViewOnly
Lock
Residence SR
Related
Parameters
Remarks This parameter specifies the IP address of an EHB which replaces an HG that had
been connected to the same TDC2000 physical Hiway but to a different LCN. When
DFNPHWYEM is set to OFF, the PHWYPRTRMIP2 parameter is unconfigured in the
form. Instead, when the EHB platform block is loaded, it is populated automatically
based on the partner EHB indicated by HWYNUM.

18.91 PHYCHNERRA1 [1...15] through PHYCHNERRA8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Errors Channel A.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable

- 2226 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related PEERSTRAVG [1..30],
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Channel A Error count.
The index of each array [1 to 15] corresponds to the physical slot in the PMIO
Chassis Number.

18.92 PHYCHNERRB1 [1...15] through PHYCHNERRB8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Errors Channel B.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30], PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Channel B Error count.
The index of each array [1 to 15] corresponds to the physical slot in the PMIO
Chassis Number.

18.93 PHYCHNMNA1 [1...15] through PHYCHNMNA8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel A- Edges. Minus edge transitions missed on Channel A.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable

- 2227 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Channel A missed
minus edge transitions count. The index of each array [1 to 15] corresponds to the
physical slot in the PMIO Chassis Number.

18.94 PHYCHNMNB1 [1...15] through PHYCHNMNB8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel B- Edges. Minus edge transitions missed on Channel B.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30], PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Channel B missed
minus edge transitions count. The index of each array [1 to 15] corresponds to the
physical slot in the PMIO Chassis Number.

18.95 PHYCHNPLA1 [1...15] through PHYCHNPLA8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel A+ Edges. Plus edge transitions missed on Channel A.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable

- 2228 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Channel A missed plus
edge transitions count. The index of each array [1 to 15] corresponds to the
physical slot in the PMIO Chassis Number.

18.96 PHYCHNPLB1 [1...15] through PHYCHNPLB8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel B+ Edges. Plus edge transitions missed on Channel B.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Channel B missed plus
edge transitions count. The index of each array [1 to 15] corresponds to the
physical slot in the PMIO Chassis Number.

18.97 PHYCHNMNASC1 [1...20] through PHYCHNMNASC4 [1...20]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel A- Edges. Minus edge transitions missed on Channel A.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable

- 2229 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays of up to 20 entries each containing the associated
Series C IOM's Channel A missed minus edge transitions count.

18.98 PHYCHNMNBSC1 [1...20] through PHYCHNMNBSC4 [1...20]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel B- Edges. Minus edge transitions missed on Channel B.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays of up to 20 entries each containing the associated
Series C IOM's Channel B missed minus edge transitions count.

18.99 PHYCHNPLASC1 [1...20] through PHYCHNPLASC4 [1...20]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel A+ Edges. Plus edge transitions missed on Channel A.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays of up to 20 entries each containing the associated
Series C IOM's Channel A missed plus edge transitions count.

- 2230 -
Chapter 18 - Pxxxx Parameters

18.100 PHYCHNPLBSC1 [1...20] through PHYCHNPLBSC4 [1...20]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel B+ Edges. Plus edge transitions missed on Channel B.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays of up to 20 entries each containing the associated
Series C IOM's Channel B missed plus edge transitions count.

18.101 PHYCHNSILA1 [1...15] through PHYCHNSILA8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Silences Channel A.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Channel A Silences
count. The index of each array [1 to 15] corresponds to the physical slot in the PMIO
Chassis Number.

- 2231 -
Chapter 18 - Pxxxx Parameters

18.102 PHYCHNSILB1 [1...15] through PHYCHNSILB8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Silences Channel B.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30]PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Channel B Silences
count. The index of each array [1 to 15] corresponds to the physical slot in the
PMIO Chassis Number.

- 2232 -
Chapter 18 - Pxxxx Parameters

18.103 PHYCOMMERR1 [1...15] through PHYCOMMERR8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Last Error
Data Type Enumeration
Range None 0
InvAlert 1
InvDest 2
InvChCnt 3
InvSourc 4
InvCmd 5
CheckSum 6
No_Resp 7
ChTimOut 8
MsgOvRun 9
GapError 10
LpbckErr 11
NTH_O 12
TknRecov 13
RplBufOv 14
TknTmOut 15
IolDrver 16
--- 17
Default None 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related N/A
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Last Error Code. The
index of each array [1 to 15] corresponds to the physical slot in the PMIO Chassis
Number.

- 2233 -
Chapter 18 - Pxxxx Parameters

18.104 PHYLHFSTA [1..8]

Specific to Block IOLINK


(s)
Description Last Hard Fail Status.
Data Type Enumeration
Range Unknown (0): Unknown Status.
PowerDown (1): This IOP Powered Down.
InvPrgExec (2): Invalid Program Execution.
EpromErr (3): EPROM Checksum Error.
RamCntErr (4): RAM Contents Error.
RamAdrErr (5): RAM Addressing Error.
DpaError (6): Device Physical Address Error.
DsaError (7): Device Soft Address Error.
RxBufOvFl (8): I/O Link Receive Buffer Overflow.
IolJabber (9): I/O Link Jabber Circuit Failure.
BadPgJmp (11): Illegal Value Case Control.
AdConvInmcp (12): A-D Conversion Incomplete.
AdOutOvfl (13): A-D Output Value Overflow.
AdOutUndef (14): A-D Output is Undefined.
AdCalibErr (15): A-D Calibration is Incorrect.
BadLcLtc (16): Bad DC LTC.
Dmt_Tmot (17): Dead Man Timer Timeout.
MltOutFail (18): Multiple Output Failures.
BadDaRange (20): Bad D-A Range.
MstrTmot (21): Master 68K Timeout.
Um51WDog (22): Um51 Watchdog Timer Timed Out
CntrCrtFail (23): IOP Counter Circuit Failure
SOECntFail (24): SOE Counter Failure
OpCntrlHwFail (25): Output Control HW Failure
BadIopType (26): Wrong Processor Type
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence PCM
Related
Parameters
Remarks Refer to the Control Hardware Troubleshooting and Maintenance Guide for
more information.

- 2234 -
Chapter 18 - Pxxxx Parameters

18.105 PHYRCVCHN1 [1...15] through PHYRCVCHN8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Active Receive Channel.
Data Type Enumeration
Range 0 CHANNEL_A: Channel A is active.
1 CHANNEL_B: Channel B is active.
2 UNKNOWN: No active channel.
3 --- IOP is not configured.
Default UNKNOWN
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's Active Receive Channel.
The index of each array [1 to 15] corresponds to the physical slot in the PMIO
Chassis Number. If the PERSWAPENB parameter is On, the active receive channel
toggles between A and B once a minute.

18.106 PHYSDSA1 [1...15] through PHYSDSA8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOP Number
Data Type 16-Bit Unsigned Integer
Range 0 to 40
Default 0
Config Yes
Load
Active No
Loadable

- 2235 -
Chapter 18 - Pxxxx Parameters

Access Lock Application Developer


Residence IOLINK
Related PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's logical address on the
I/O Link. The index of each array [1 to 15] corresponds to the physical slot in the
PMIO Chassis Number. If IOMNUM=0 and the IOP block is assigned to an I/O Link
block, Control Builder automatically defaults the IOMNUM to the next available
value on the I/O Link.

18.107 PHYSIOPSTS1 [1...15] through PHYSIOPSTS8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOP Status
Data Type Enumeration
Range POWER_ON (0): Transient state when power is turned on.

IDLE (1): In the Idle state.


OK (2): Running.
NO_RESP (3): No response.
IDLE_SF (4): In the Idle state and has a Soft Failure.
SOFT_FAIL (5): In the Running state and has a Soft
Failure.
COMM_ERR (6): Communication Error.
CONFIG_MIS (7): Configuration Mismatch.
NO_CONFIG (8): This IOP is Not Configured.
--- (9): This IOP does not exist.
Default POWER_ON
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30], SECCHNERRA [1...40]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's status. The index of
each array [1 to 15] corresponds to the physical slot in the PMIO Chassis Number.

- 2236 -
Chapter 18 - Pxxxx Parameters

18.108 PHYSMODTYPE1 [1...15] through PHYSMODTYPE8 [1...15]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Actual Module Type.
Data Type Enumeration
Range Refer to IOPTYPE parameter of the IOP Block.
Default Null
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PEERSTRAVG [1..30]
Parameters
Remarks These parameters are arrays (corresponding to PMIO chassis numbered 1 through
8) with up to 15 entries each indicating the associated IOP's type. The index of each
array [1 to 15] corresponds to the physical slot in the PMIO Chassis Number.

18.109 PI[0..2]

Specific to Block DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


(s)
Description Permissive Interlocks
Data Type Boolean
Range Off (0) On (1)
Default On (1)
Config Load No
Active Loadable No
Access Lock Other Function Block (see Remarks)
Residence CEE
Related PEERSTRAVG [1..30], GOP, PEERSTRAVG [1..30], PEERSTRAVG [1..30],
Parameters PEERSTRAVG [1..30].
Remarks Engineer can change only when the function block is InActive or Box is idle.
DEVCTL Only:
l Illegal if NUMDOUTS = 0.
l PI[2] is illegal if NUMSTATES = 2.
l Permissives are ignored if BYPASS is set On.

- 2237 -
Chapter 18 - Pxxxx Parameters

18.110 PID

Specific to HRBALG_REG block


Blocks
Description PID FB Reference
Data Type BLOCKID
Range Not applicable
Default Null
Config. Load Yes
Active
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter contains a reference to the PID block in the emulation CM which
holds the HRBALG_REG instance.

18.111 PIDSTATUS

Specific to Block(s) ProfitCtl


Description PID status
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks This parameter represents status of downstream PID block.

18.112 PIUCARDOP(1..32)
This parameter indicates the Card Option for each DI, DO, CTR type slot in an HLPIU box.

Data Type Enumeration Range See the Range list.


Default None. Read from the Box. Configuration Load Yes
Access Lock Application Developer Only Residence PIU Box
Related Parameters Checkpoint Yes

Range:

- 2238 -
Chapter 18 - Pxxxx Parameters

For HLPIU:
l NOTIFYS (0)
l CHNGDECT (1)
l SOE (2)
l PULSEOUT (3)
l LATCHOUT (4)
l COUNTER16 (5)
l COUNTER32 (6)
l NONE (7)

For LXPIU:
l NONE

18.113 PIUOTDCF

Specific to AICHANNEL, HAICHANNEL (PM I/O)


Block(s)
Description Open Thermocouple Detection Enable. Specifies whether or not this point is to
detect an open thermocouple condition.
Data Type Boolean
Range Off: Disabled. Do not detect an open thermocouple condition. On: Enabled. Detect
an open thermocouple condition.
Default On
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence IOM
Related PEERSTRAVG [1..30]
Parameters
Remarks This parameter is only exposed if ASSOCIOPTYP is STI-MV, LLMUX, or RHMUX. It
is only configurable when:
1. ASSOCIOPTYP is STI-MV, LLMUX, or RHMUX, and
2. SENSRTYP is THERMCPL, 0_100_MV, or STT.

18.114 PIUSMOTH

Specific to HRBALG_PIUAI
Block(s)
Description Smoothing Coeff
Data Type ENUM
Range None (1.0000) Code01 Code02 Code03 Code04 Code05 Code06 Code07 Code08
Code09 Code10 Code11 Code12 Code13 Code14

- 2239 -
Chapter 18 - Pxxxx Parameters

Default None(1.0000)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related –
Parameters
Remarks This parameter represents the enumerations defined in the HRB Algo box.

18.115 PL

Specific to Block Pulse Input IOC


(s)
Description Pulse Length Value - Engineering Units value corresponding to the measured
pulse length.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PLSTS
Parameters
Remarks PL = C3 * (pulse / period length in microseconds)

Specific to Series C PICHANNEL


Block(s)
Description Pulse/Period Length Value
Data Type FLOAT64
Range N/A
Default NaN
Config No
Load
Active No
Loadable

- 2240 -
Chapter 18 - Pxxxx Parameters

Access Lock View Only


Residence IOM
Related C3 FREQPERIOD PLSTS
Parameters
Remarks PL represents the pulse length in engineering units that corresponds to the
measured pulse or period based on the following equation. PL = C3 * (pulse/period
length in microseconds). Note that if the pulses stop accumulating, the last non-
zero value will be reported.

18.116 PL[0..5]

Specific to Pulse Input IOM


Block(s)
Description Pulse Length Value - Engineering Units value corresponding to the measured
pulse length. If pulses stop accumulating the last non-zero value will be reported.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks For Pulse Input IOM (Channels 0-5 only), PL in EU = C3 * Timer Latch Value in
microseconds.

18.117 PLSTS

Specific to Block Pulse Input IOC


(s)
Description Pulse Length Value Status
Data Type Enumeration
Range Bad (0): Bad Status is set during loss of cummunication, IOC or IOM
function block is inactive.
Uncertn
(1):
Normal Associated data is valid.
(2):
Manual
(3):
Default Off

- 2241 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PL
Parameters
Remarks

Specific to Block(s) Series C PICHANNEL


Description PL Value Status
Data Type ENUM
Range BAD(0) UNCERTAIN(1) NORMAL(2) MANUAL(3)
Default BAD
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters PL
Remarks PLSTS represents the status of the pulse/period length value (PL).

18.118 PLVERSION

Specific to C300, PGM and FIM4 FBs.


Block(s)
Description Programmable Logic Version
Data Type String
Range Length: 5 characters
Default Null
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM
Related
Parameters
Remarks Factory programmed logic device version differs from the boot/application image
version, (which is updated with firmware load) in that the hardware has to be
returned to the factory for this version to be updated.

- 2242 -
Chapter 18 - Pxxxx Parameters

Specific to Block(s) EIM, TCMI


Description Programmable Logic Revision
Data Type String
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

Specific to Block(s) UOC


Description Programmable Logic Revision
Data Type String
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (hardware statistics, see C300 definition)

18.119 PNETCONFIGCHNG

Specific to Block(s) UOC


Description PROFINET Configuration Change
Data Type UINT8
Range

Default

Config Load Yes


Active Loadable

Access Lock Program


Residence ERDB
Related Parameters PROFINETENABLE
Remarks

- 2243 -
Chapter 18 - Pxxxx Parameters

18.120 PNETCONFIGPATH

Specific to Block(s) UOC


Description Set PROFINET Device Name
Data Type String
Range 114 characters
Default

Config Load Yes


Active Loadable

Access Lock Engineer


Residence UOC
Related Parameters PROFINETENABLE
Remarks

18.121 PNTALGOTYPE[ ]

Specific to CB and EC
Blocks
Description Point algorithm type
Data Type ENUM
Range Algorithm type enumerations for CB and EC
Default DAS
Config. Load No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter displays the regulatory algorithm type that is loaded in the slot
represented by the index.

18.122 PNTFORM

Specific to Block PMIO Channel Blocks; Series C I/O Channel Blocks


(s)
Description Point Form. Defines the form of the data point that is used.
Data Type Enumeration
Range Full (0): Point is fully displayed and alarmed.
Component (1): Point is partially displayed and not
alarmed.

- 2244 -
Chapter 18 - Pxxxx Parameters

Default Component (1)


Config Load Yes
Active Loadable No
Access Lock DICHANNEL block only: Application Developer All other blocks: ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is configurable only for DICHANNEL blocks assigned to a
DISOE block.

18.123 PNTTYPE

Specific to Block(s) All PM I/O Channels


Description
Data Type Enumeration
Range 0 NULL Point is not configured.
1 AI Analog Input.
2 AO Analog Output.
3 DI Digital Input.
4 DO Digital Output.
Default Based on channel type
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence IOM
Related Parameters
Remarks This parameter is always loaded first.

Specific to Block(s) All Series C I/O Channels


Description
Data Type Enumeration
Range 0 NULL Point is not configured.
1 AI Analog Input.
2 AO Analog Output.
3 DI Digital Input.
4 DO Digital Output.
Default Based on channel type.
Config Load Yes
Active Loadable No

- 2245 -
Chapter 18 - Pxxxx Parameters

Access Lock Application Developer, but hidden from user


Residence IOM
Related Parameters N/A
Remarks This parameter is always loaded first.

Specific to Universal IO module


Block(s)
Description
Data Type Enumeration
Range 0 NULL Point is not
configured.

1 AI Analog
Input
2 AO Analog
Output
4 DI Digital
Input
5 DO Digital
Output
Default DI
Config Yes
Load
Access Application Developer
Lock
Active No
Loadable
Residence IOM
Related
Parameters
Remarks When this parameter is modified, the associated IO channel
template is modified to match the selected channel type. This
operation can only be performed on channels that are not
contained within a Control Module. When assigned to a UIO
module, this parameter is always loaded only after the
INITPNTTYPE parameter.

18.124 PO

Specific to Pulse Length Control, Pulse Count Control


Block(s)
Description Pulse Output for both Raise and Lower pulses.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)

- 2246 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PODIR, POLOWER, PORAISE.
Parameter
Remarks This is an output parameter which produces pulses on either a +PULSETIME or
-PULSETIME value.

18.125 PO[1..3]

Specific to Block(s) DevCtl


Description Pulsed Output Values
Data Type Structure
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related DO[1..3], GOPFINAL, NUMDOUTS, OPDOMAP[0..3][1..3], OPFINAL,
Parameters PULSEWIDTH.
Remarks Only valid if NUMDOUTS allows the respective output.

18.126 POCLOSE

Specific to Block(s) VALVEDAMPER


Description Pulsed Output for Close
Data Type Structure
Range
Default
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CMDOPEN, CMDCLOSE, CLOSEPULSEWIDTH, OPENPULSEWIDTH
Remarks

- 2247 -
Chapter 18 - Pxxxx Parameters

18.127 POCLOSECONNECTED

Specific to VALVEDAMPER
Block(s)
Description Pulse Connection Flag - Whenever POCLOSE is connected to a DOC.ONPULSE or
DOC.OFFPULSE, the parameter POCLOSECONNECTED must be set to “ON”. This
allows the Device Control function block to know which outputs are configured for
pulsing.
Data Type Boolean
Range ON-OFF
Default OFF
Config YES
Load
Active No
Loadable
Access Lock App Dev
Residence CEE
Related POCLOSEPOOPENCLOSEPULSEWIDTH, OPENPULSEWIDTH
Parameters
Remarks

18.128 POCONNECTED[1..3]

Specific to DevCtl
Block(s)
Description Pulse Connection Flag - Whenever the respective PO(1..3) is connected to a DOC.
ONPULSE or DOC. OFFPULSE, the parameter POCONNECTED(1..3) must be set to
“On”. This allows the Device Control function block to know which outputs are
configured for pulsing. POCONNECTED[ ] may not be configured on the form until
at least one PO[ ] parameter is exposed on the block.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related PO[1..3]PULSEWIDTH.
Parameters
Remarks

- 2248 -
Chapter 18 - Pxxxx Parameters

18.129 PODIR

Specific to Block(s) Pulse Length Control, Pulse Count Control


Description Indicates direction for Pulse Output: Off-Lower, On-Raise.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameter P0, POLOWERPORAISE
Remarks

18.130 POLOWER

Specific to Block(s) Pulse Length Control, Pulse Count Control


Description Pulse Output for Lower pulses.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameter P0, PODIRPODIR
Remarks This is an output parameter which produces pulses on a -PULSETIME value.

- 2249 -
Chapter 18 - Pxxxx Parameters

18.131 POLLTIME

Specific to Block(s) TCMI


Description Poll Time
Data Type FLOAT64
Range NA
Default 0.0
Config Load No
Active Loadable NA
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.132 POOPEN

Specific to Block(s) VALVEDAMPER


Description Pulsed Output for Open
Data Type Structure
Range N/A
Default N/A
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CMDOPEN, CMDCLOSE, CLOSEPULSEWIDTH, OPENPULSEWIDTH
Remarks

18.133 POOPENCONNECTED

Specific to VALVEDAMPER
Block(s)
Description Pulse Connection Flag - Whenever POOPEN is connected to a DOC.ONPULSE or
DOC.OFFPULSE, the parameter POOPENCONNECTED must be set to “ON”. This
allows the Device Control function block to know which outputs are configured for
pulsing.
Data Type Boolean
Range ON-OFF
Default OFF

- 2250 -
Chapter 18 - Pxxxx Parameters

Config YES
Load
Active No
Loadable
Access Lock AppDev only
Residence CEE
Related POCLOSEPOOPENCLOSEPULSEWIDTH, OPENPULSEWIDTH
Parameters
Remarks

18.134 POPERIOD

Specific to Pulse Count Control


Block(s)
Description Period used for the pulses generated (in seconds).
Data Type 64-Bit Real Number
Range Greater-than 0.0. Only values that are multiples of two times the FB's execution
period are valid, other values are clamped to the greatest multiple of two times the
function block's execution period less than the entered value.
Default 4.0
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related
Parameter
Remarks

18.135 PORAISE

Specific to Block(s) Pulse Length Control, Pulse Count Control


Description Pulse Output for Raise pulses.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No

- 2251 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameter P0, PODIRPOLOWER.
Remarks This is an output parameter which produces pulses on a +PULSETIME
value.

18.136 PORT

Specific to Block(s) OPCUASRVUOC


Description Port
Data Type UINT32
Range 0 to 4294967295
Default 4840
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters None
Remarks

18.137 PORUN

Specific to HTMOTOR, LTMOTOR


Block(s)
Description Pulsed Output for Run
Data Type Structure
Range
Default
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CMDRUN, CMDSTOP, PORUNCONNECTED, POSTOPCONNECTED,
Parameters RUNPULSEWIDTH, STOPPULSEWIDTH.
Remarks 19.96.1

- 2252 -
Chapter 18 - Pxxxx Parameters

18.138 PORUNCONNECTED

Specific to HTMOTOR, LTMOTOR


Block(s)
Description Pulse Connection Flag - Whenever PORUN is connected to a DOC.ONPULSE or
DOC.OFFPULSE, the parameter PORUNCONNECTED must be set to “ON”. This
allows the Device Control function block to know which outputs are configured for
pulsing.
Data Type Boolean
Range ON-OFF
Default OFF
Config YES
Load
Active No
Loadable
Access Lock APPDEVONLY
Residence CEE
Related PORUN, POSTOP, POSTOPCONNECTED
Parameters
Remarks

18.139 POSTOP

Specific to HTMOTOR, LTMOTOR


Block(s)
Description Pulsed Output for Stop
Data Type Structure
Range
Default
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related CMDRUN, CMDSTOP, PORUNCONNECTED, POSTOPCONNECTED,
Parameters RUNPULSEWIDTH, STOPPULSEWIDTH.
Remarks

- 2253 -
Chapter 18 - Pxxxx Parameters

18.140 POSTOPCONNECTED

Specific to HTMOTOR, LTMOTOR


Block(s)
Description Pulse Connection Flag - Whenever POSTOP is connected to a DOC.ONPULSE or
DOC.OFFPULSE, the parameter POOSTOPCONNECTED must be set to “ON”. This
allows the Device Control function block to know which outputs are configured for
pulsing.
Data Type Boolean
Range ON-OFF
Default OFF
Config YES
Load
Active No
Loadable
Access Lock App Dev Only
Residence CEE
Related PORUN, POSTOP, POSTOPCONNECTED
Parameters
Remarks

18.141 POSTTRANSEXECSTS

Specific to Block(s) Step


Description Execution Status of Post (succeeding) Transitions.
Data Type Enumeration
Range
Default Ok
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2254 -
Chapter 18 - Pxxxx Parameters

18.142 POWERCONNOPT

Specific to RETENTIONTRIG
Block(s)
Description Power Conn. Option
Data Type Enum
Range Single, Dual2PerModule, Dual1PerModule
Default Single
Config Yes
Load
Active No
Loadable
Access AppDevOnly
Lock
Residence CEE
Related DEVICEIDX, PWRGOOD1, PWRGOOD2
Parameters
Remarks Establishes how a CN100, UOC responds to the loss of external power, as indicated by
signals PWRGOOD1 and PWRGOOD2. Must be configured in a manner consistent
with the physical power connectivity. Meaning of the available options is as follows.
Single
A single Power Source connects to the controller module’s power supply for either a
non-redundant controller or a pair of redundant controllers, irrespective of the number
of power supplies associated with each controller module.
Dual2PerModule

This applies only to non-redundant controller modules with 2 power supplies.


RETENTIONTRIG block load is rejected if the UOC rack does not have redundant
power supplies. Two power sources are used, each connected to one of the controller
module’s two supplies. Each of the two power sources is sensed with its own External
Power Good signal.

Dual1PerModule
This applies only to redundant controllers. The Device Index value of each redundant
partner plays an important role in this configuration. RETENTIONTRIG block load is
rejected if the UOC is configured as non-redundant. Two power sources are used,
where each power source is connected to an individual controller in the redundant
controller pair. Each of the two power sources is sensed with its own External Power
Good signal. The physical association between power source and redundant controller
module is as follows:
l PWRGOOD1 represents the power source attached to the controller module A
with the odd device index.
l PWRGOOD2 represents the power source attached to the controller module B
with the even device index.

For the virtual UOC, POWERCONNOPT is always set to either Single or


Dual2PerModule because the virtual UOC does not support the application
redundancy required for the Dual1PerModule configuration.

- 2255 -
Chapter 18 - Pxxxx Parameters

18.143 POWERFAIL[1..200]

Specific to QIPACCHAN
Block
Description Power Failure
Data Type Boolean
Range Off(0) OK
On(1) Power Failure During Feed
Default Off
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MATERIALPATH[1..200], COMMAND, COMMANDSTATS[1..200], MXFERSTATUS
Parameters [1..200], MXFERSTATQ[1..200], OVERTOLRNCE[1..200], UNDERTOLRNCE[1..200],
DELIVEREDWGT[1..200], TARGETERROR[1..200], AVGSPILL[1..200], AVGFLOWRATE
[1..200], MXFERSTATQ[1..200]
Remarks This is the value of bit 2 of the MXFERSTATQ word in
the Command Status Object. This value provides
material transfer results and is valid after the
material transfer for the designated channel
[1..200] in the QiMPACT cluster completes.

18.144 PP[1..10]

Specific to Block(s) ENHAUXCALC


Description Scale Input - Each P-input has a corresponding scaled input.
Data Type Float64
Range
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE/C200
Related Parameter PP[1..10]ENABLE[1..10], PSUB[1..10].
Remarks

- 2256 -
Chapter 18 - Pxxxx Parameters

18.145 PPREDUNLINKFAIL

Specific to Block(s) TCMI


Description PP Redundancy Link Fail
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.146 PRBIAS

Specific to LEVELCOMP
Block(s)
Description Drum pressure bias
Data Type Float64
Range
Default 0
Config Load YES
Active No
Loadable
Access Lock Engineer when CM is Inactive
Residence CEE
Related PRESSUREPRSLOPE
Parameters
Remarks This parameter participates in ranging required for the Pressure using the formula
of a straight line y = mx +c where m is the slope and c is bias constant.

- 2257 -
Chapter 18 - Pxxxx Parameters

18.147 PREDPVHIALM.FL

Specific to PID-PL
Block(s)
Description Predicted PV High Alarm Flag - This alarm detects high excursions in the predicted
steady state PV, STEADYSTATEPV. Because the alarm is associated with the steady
state operation, it is an early indication of potential control problems or prolonged
process upsets.
Data Type Boolean
Range Off (0): Not in Predicted PV High alarm
On (1): In Predicted PV High alarm
Default Off
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PREDPVHIALM.PR, PREDPVHIALM.SV, PREDPVHIALM.TP.
Parameters
Remarks This parameter is applicable only when
CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

18.148 PREDPVHIALM.PR

Specific to PID-PL
Block(s)
Description Predicted PV High Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PREDPVHIALM.FL, PREDPVHIALM.SV, PREDPVHIALM.TP.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

- 2258 -
Chapter 18 - Pxxxx Parameters

18.149 PREDPVHIALM.SV

Specific to PID-PL
Block(s)
Description Predicted PV High Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PREDPVHIALM.FL, PREDPVHIALM.PR, PREDPVHIALM.TP.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

18.150 PREDPVHIALM.TP

Specific to PID-PL
Block(s)
Description Predicted PV High Alarm Trip Point (in Engineering Units) - Defines the upper limit
for the predicted steady state PV.
Data Type Float64
Range PREDPVLOALM.TP - PVHIALM.TP, NaN
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PREDPVHIALM.FL, PREDPVHIALM.PR, PREDPVHIALM.SV.
Parameters
Remarks NaN disables this alarm. This parameter is applicable only when CTLEQN is set to
Profit Loop PKS, and is ignored in PID control equations.

- 2259 -
Chapter 18 - Pxxxx Parameters

18.151 PREDPVHIALM.TM

Specific to PID-PL
Block(s)
Description Predicted PV High Alarm filter time in seconds.
Data Type UNIT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure on-delay time for Predicted PV High
Alarm. For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

18.152 PREDPVHIALM.TMO

Specific to Block(s) PID-PL


Description Predicted PV High Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure off-delay time for Predicted PV
High Alarm.

- 2260 -
Chapter 18 - Pxxxx Parameters

18.153 PREDPVLOALM.FL

Specific to PID-PL
Block(s)
Description Predicted PV Low Alarm Flag - This alarm detects low excursions in the predicted
steady state PV, STEADYSTATEPV. Because the alarm is associated with the steady
state operation, it is an early indication of potential control problems or prolonged
process upsets.
Data Type Boolean
Range Off (0): Not in Predicted PV Low alarm
On (1): In Predicted PV Low alarm
Default Off
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PREDPVLOALM.PR, PREDPVLOALM.SV, PREDPVLOALM.TP
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

18.154 PREDPVLOALM.PR

Specific to PID-PL
Block(s)
Description Predicted PV Low Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PREDPVLOALM.FL, PREDPVLOALM.SV, PREDPVLOALM.TP
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

- 2261 -
Chapter 18 - Pxxxx Parameters

18.155 PREDPVLOALM.SV

Specific to PID-PL
Block(s)
Description Predicted PV High Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PREDPVLOALM.FL, PREDPVLOALM.PR, PREDPVLOALM.TP.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

18.156 PREDPVLOALM.TM

Specific to PID-PL
Block(s)
Description Predicted PV Low Alarm filter time in seconds.
Data Type UNIT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure on-delay time for Predicted PV Low
Alarm. For more information about alarm configuration, refer to Control Builder
Components Theory Guide.

- 2262 -
Chapter 18 - Pxxxx Parameters

18.157 PREDPVLOALM.TMO

Specific to Block(s) PID-PL


Description Predicted PV Low Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks This parameter is introduced to configure off-delay time for Predicted PV Low
Alarm.

18.158 PREDPVLOALM.TP

Specific to PID-PL
Block(s)
Description Predicted PV Low Alarm Trip Point (in Engineering Units) - Defines the lower limit
for the predicted steady state PV.
Data Type Float64
Range PVLOALM.TP -PREDPVHIALM.SV, NaN
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PREDPVLOALM.FL, PREDPVLOALM.PR, PREDPVLOALM.SV.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

- 2263 -
Chapter 18 - Pxxxx Parameters

18.159 PREFERREDCONN

Specific to Block PCDI_MASTER


(s)
Description Preferred Connection to use
Data Type Enumeration
Range 0 Primary
1 Secondary
Default Primary (0)
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related
Parameters
Remarks The preferred connection to use when the connection to use parameter is
set to Auto.

18.160 PREFSP

Specific to Block(s) ENHREGCALC, PID, PID-PL, PIDER, PIDFF, POSPROP, RATIOCTL


Description Preferred Setpoint - Provides value of the Preferred SP
Data Type FLOAT64
Range SPLOLM to SPHILM, NaN
Default NaN
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters HCMD00PREFSPCLEARPREFSPSET
Remarks A value of NaN indicates that PREFSP has not been set.

Specific to Block(s) TIMER


Description Preferred Setpoint - Provides value of the Preferred SP.
Data Type 32-Bit Integer
Range -1, 0 to Maximum upper limit based on TIMEBASE (see SP)
Default -1
Config Load No
Active Loadable No

- 2264 -
Chapter 18 - Pxxxx Parameters

Access Lock Operator


Residence CEE
Related Parameters HCMD00PREFSPCLEARPREFSPSET
Remarks A value of -1 indicates that PREFSP has not been set.

18.161 PREFSPCLEAR

Specific to ENHREGCALC, PID, PID-PL, PIDER, PIDFF, POSPROP, RATIOCTL


Block(s)
Description Preferred Setpoint Clear Trigger
Data Type BOOLEAN
Range Off, On
Default Off
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related HCMD00PREFSP
Parameters
Remarks Always returns a value of Off. Store of Off has no effect. Store of On causes the
PREFSP to be set to default value of NaN/-1 for RegCtl/Timer block, respectively.

18.162 PREFSPSET

Specific to ENHREGCALC, PID, PID-PL, PIDER, PIDFF, POSPROP, RATIOCTL


Block(s)
Description Preferred Setpoint Set Trigger
Data Type BOOLEAN
Range Off, On
Default Off
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related HCMD00PREFSP
Parameters
Remarks Always returns a value of Off. Store of Off has no effect. Store of On causes the
current SP to be copied into PREFSP.

- 2265 -
Chapter 18 - Pxxxx Parameters

18.163 PRENGUNIT

Specific to Block LEVELCOMP


(s)
Description Pressure Engineering Unit Selection
Data Type Enumeration
Range Kpa, Kg/Cm2, Bar, psi, ata
Default Kg/Cm2
Config Load YES
Active Loadable No
Access Lock App Dev
Residence CEE
Related PRESSURE
Parameters
Remarks This is a key input as engineering unit conversion on PRESSURE is applied
based on this parameter.

18.164 PRESSURE

Specific to Block(s) LEVELCOMP


Description Drum pressure
Data Type Float64
Range 0-200Kg/cm2
Default NaN
Config Load YES
Active Loadable No
Access Lock Program
Residence CEE
Related Parameters PRSLOPEPRBIAS
Remarks Drum pressure field input is fed here either through AI channel or DACA.

Specific to Steam Property Block


Block(s)
Description Pressure (P) Value
Data Type IEEE_FLOAT64
STEAM_WATER = STEAM, STEAM_WATER = STEAM, STEAM_WATER
STEAMTYPE = Saturated STEAMTYPE = Superheated = WATER

- 2266 -
Chapter 18 - Pxxxx Parameters

Range SI 0.005 to 25 Mpa 0 to 100 Mpa 0 to 100 Mpa


Metric 0.051 to 255 Kg/cm2 0.051 to 1019.71 Kg/cm2 0.051 to
1019.71
Kg/cm2
English 0.725 to 3625 lb/in2 (Psi) 0.725 to 14503.77 lb/in2 0.725 to
(Psi) 14503.77 lb/in2
(Psi)
Default IEEENaN
Config Load No
Access Lock Engineer
Active No
Loadable
Residence CEE
Related
Parameters
Remarks

18.165 PRESSUREENGUNIT

Specific to Block(s) Steam Property Block


Description Pressure (P) Engineering Unit
Data Type ENUM
Range MPa SI Unit
kg/cm2 Metric Unit
lb/in2 Eng Unit
Default MPa
Config Load Yes
Access Lock Application Developer Only
Active Loadable No
Residence SR
Related Parameters
Remarks

- 2267 -
Chapter 18 - Pxxxx Parameters

18.166 PRESSUREIO

Specific to Block(s) Steam Property Block


Description Pressure (P) IO Configuration
Data Type ENUM
Range Input Parameter configured as Input
Output Parameter configured as Output
Not Configured Parameter configured as None
Default Not Configured
Config Load Yes
Access Lock Application Developer Only
Active Loadable No
Residence CEE
Related Parameters
Remarks

18.167 PREVALARM

Specific to Block(s) ProfitCtl


Description Previous alarms
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

18.168 PREVISION

Specific to RM
Block(s)
Description Platform Revision. Identifies the minor revision of the RM.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default N/A

- 2268 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

18.169 PREVLOADSTAT

Specific to CM, SCM, RCM


Block(s)
Description Previous container block load state.
Data Type Enumeration of LOADSTATE
Range LOADFAILED (0) UNLOADED (1) LOADINGPROG (2) LOADINGCMPTYPES (3)
CMLOADINGTBR (4) LOADINGCONFG (5) LOADINGCONN (6) READY (7)
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related LOADSTATE
Parameters
Remarks This parameter captures the previous value of LOADSTATE during the container
block load process. This information is useful in debugging in the event that a load
failure is encountered by the container block.

18.170 PREVTRANSEXECSTS

Specific to Block(s) Step


Description Execution Status of Previous Transistions
Data Type Enumeration
Range
Default Ok
Config Load No
Active Loadable No

- 2269 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

18.171 PRFRATIO
This parameter is for non-integrating processes (D[1]<>0). For integrating systems, use
CLOSEDLOOPRESP to alter the speed of response.

Specific to PID-PL
Block(s)
Description Performance Ratio - Ratio of desired closed loop control response to open loop
response. Tells the function block how hard to push to a setpoint or range limit.
Data Type Float64
Range 0.1 - 10.0
Default 1
Config Yes
Load
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related CLOSEDLOOPRESP, OPENLOOPRESP.
Parameters
Remarks Increasing the ratio slows the loop response time. PRFRATIO has no meaning for
integrating processes and is set to 1. Use CLOSEDLOOPRESP to specify integrator
performance. This parameter is applicable only when CTLEQN is set to Profit Loop
PKS, and is ignored in PID control equations.

18.172 PRIBLOCKNAME[1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOP Block Name. Indicates the corresponding Primary IOP/IOM Tag. The index of
this array corresponds to the IOP/IOM Number.
Data Type BlockId
Range N/A
Default 0
Config Load No
Active No
Loadable

- 2270 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence IOLINK, C300 IOLINK
Related SECBLOCKNAME [1...40]
Parameters
Remarks

18.173 PRICANTTALKTOSECONUCN

Specific to Block(s) TCMI


Description Primary cannot talk to Secondary on UCN
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.174 PRICHNERRA [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Input/Output Processor (IOP) Errors on Channel A. Shows the number of
I/O link channel A errors encountered by the primary IOP/IOM, where the index of
this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNERRA
Parameters
Remarks Note that this is the same as the IOMCHAER parameter in a TPS system.

- 2271 -
Chapter 18 - Pxxxx Parameters

18.175 PRICHNERRB [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Input/Output Processor (IOP) Errors on Channel B. Shows the number of
I/O link channel B errors encountered by the primary IOP/IOM, where the index of
this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNERRB
Parameters
Remarks Note that this is the same as the IOMCHBER parameter in a TPS system.

18.176 PRICHNMNA [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel A- Edges. Shows the number of I/O link channel A missed minus edge
transitions encountered by the primary IOM, where the index of this array
corresponds to the number of the IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNMNA
Parameters
Remarks

- 2272 -
Chapter 18 - Pxxxx Parameters

18.177 PRICHNMNB [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel B- Edges. Shows the number of I/O link channel B missed minus edge
transitions encountered by the primary IOM, where the index of this array
corresponds to the number of the IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNMNB
Parameters
Remarks

18.178 PRICHNPLA [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel A+ Edges. Shows the number of I/O link channel A missed plus edge
transitions encountered by the primary IOM, where the index of this array
corresponds to the number of the IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNPLA
Parameters
Remarks

- 2273 -
Chapter 18 - Pxxxx Parameters

18.179 PRICHNPLB [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Channel B+ Edges. Shows the number of I/O link channel B missed plus edge
transitions encountered by the primary IOM, where the index of this array
corresponds to the number of the IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNPLB
Parameters
Remarks

18.180 PRICHNSILA [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Input/Output Processor (IOP) Silences on Channel A. Shows the number
of I/O link channel A silences encountered by the primary IOP/IOM, where the
index of this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNSILA
Parameters
Remarks Note that this is the same as the IOMCHASL parameter in a TPS system.

- 2274 -
Chapter 18 - Pxxxx Parameters

18.181 PRICHNSILB [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Input/Output Processor (IOP) Silences on Channel B. Shows the number
of I/O link channel B silences encountered by the primary IOP/IOM, where the
index of this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNSILB
Parameters
Remarks Note that this is the same as the IOMCHBSL parameter in a TPS system.

- 2275 -
Chapter 18 - Pxxxx Parameters

18.182 PRICOMMERR [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Input/Output Processor (IOP) Last Communication Error. Shows the last
I/O link communication error experienced by the primary IOP/IOM, where the
index of the array corresponds to the number of the IOP/IOM.
Data Type Enumeration
Range None (0): No communication error.
InvAlert (1): Invalid Alert - message bit problem.
InvDest (2): Invalid Destination.
InvChCnt (3): Invalid Character Count.
InvSourc (4): Invalid Source.
InvCmd (5): Invalid Command.
CheckSum (6): Data record Checksum Error.
No_Resp (7): No Response.
ChTimOut (8): Channel Time Out.
MsgOvRun (9): Message Overrun.
GapError (10): Message gap is too long.
LpbckErr (11): Loop Back Error.
NTH_O (12): Next Token Holder equals zero.
TknRecov (13): Token Recovery in progress.
RplBufOv (14): Reply Buffer Overflow.
TknTmOut (15): Token Pass Time Out.
IolDrver (16): IOL Driver Error.
---(17): IOP is not configured.
Default None (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks Note that this is the same as the IOMCOMER parameter in a TPS system.

- 2276 -
Chapter 18 - Pxxxx Parameters

18.183 PRIIFCARD

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Interface File Card Number. Shows the current primary I/O link interface's
card number that is a component of its physical address.
Data Type 16-Bit Unsigned Integer
Range 1 to 16
Default 16
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PRIIFFILE
Parameters
Remarks The card number will be 16 only, although for C300 the parameter is not
meaningful. It is supported only for compatibility and its value will be 2 or 3.

18.184 PRIIFCHNERRA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Errors on Channel A. Shows the number of I/O link channel
A errors encountered locally by the primary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNERRA
Parameters
Remarks Note that this is the same as the PMMCHAER parameter in a TPS system.

- 2277 -
Chapter 18 - Pxxxx Parameters

18.185 PRIIFCHNERRB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Errors on Channel B. Shows the number of I/O Link
Channel B errors encountered locally by the primary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNERRB
Parameters
Remarks Note that this is the same as the PMMCHBER parameter in a TPS system.

18.186 PRIIFCHNMNA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Channel A- Edges. Shows the number of I/O link channel A
missed minus edge transitions encountered locally by the primary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNMNA
Parameters
Remarks

- 2278 -
Chapter 18 - Pxxxx Parameters

18.187 PRIIFCHNMNB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link interface Channel B- Edges. Shows the number of I/O link channel B
missed minus edge transitions encountered locally by the primary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNMNB
Parameters
Remarks

18.188 PRIIFCHNPLA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primanry Link Interface Channel A+ Edges. Shows the number of I/O link channel
A missed plus edge transitions encountered locally by the primary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNPLA
Parameters
Remarks

- 2279 -
Chapter 18 - Pxxxx Parameters

18.189 PRIIFCHNPLB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Channel B+ Edges. Shows the number of I/O link channel B
missed plus edge transitions encountered locally by the primary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNPLB
Parameters
Remarks

18.190 PRIIFCHNSILA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Silences on Channel A. Shows the number of I/O link
silences on channel A encountered locally by the primary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNSILA
Parameters
Remarks Note that this is the same as the PMMCHASL parameter in a TPS system.

- 2280 -
Chapter 18 - Pxxxx Parameters

18.191 PRIIFCHNSILB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Silences on Channel B. Shows the number of I/O link
silences on channel B encountered locally by the primary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNSILB
Parameters
Remarks Note that this is the same as the PMMCHBSL parameter in a TPS system.

- 2281 -
Chapter 18 - Pxxxx Parameters

18.192 PRIIFCOMMERR

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Last Communication Error. Shows the last I/O link
communications error experienced by the primary link interface.
Data Type Enumeration
Range None (0) No communication error.
InvAlert (1) Invalid Alert - message bit problem.
InvDest (2) Invalid Destination.
InvChCnt (3) Invalid Character Count.
InvSourc (4) Invalid Source.
InvCmd (5) Invalid Command.
CheckSum (6) Data record Checksum Error.
No_Resp (7) No Response.
ChTimOut (8) Channel Time Out.
MsgOvRun (9) Message Overrun.
GapError (10) Message gap is too long.
LpbckErr (11) Loop Back Error.
NTH_O (12) Next Token Holder equals zero.
TknRecov (13) Token Recovery in progress.
RplBufOv (14) Reply Buffer Overflow.
TknTmOut (15) Token Pass Time Out.
IolDrver (16) IOL Driver Error.
Default None (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks Note that this is the same as the PMMCOMER parameter in a TPS system.

- 2282 -
Chapter 18 - Pxxxx Parameters

18.193 PRIIFFILE

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Interface File Number. Shows the current primary I/O link interface's file
number that is a component of its physical address.
Data Type 16-Bit Unsigned Integer
Range 1 to 8
Default 1
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PRIIFCARD
Parameters
Remarks The file number will be 1 or 2 only. For the C300 this parameter is not meaningful.
It is supported for compatibility and its value will be 6 for both partners.

18.194 PRIIFRCVCHN

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Active Receive Channel. Shows the channel that is actively
listening to transmitted messages.
Data Type Enumeration
Range UNKNOWN: No active channel.
CHANNEL_A: Channel A is active.
CHANNEL_B: Channel B is active.
Default UNKNOWN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PERIODENUMMASKPERIODSECPERSWAPENB
Parameters
Remarks If the PERSWAPENB parameter is On, the active receive channel toggles between A
and B once a minute. (Note that this is the same as the PMMRECHN parameter in a
TPS system.)

- 2283 -
Chapter 18 - Pxxxx Parameters

18.195 PRIIFSTS

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary Link Interface Processor Status. Shows the status of the link processor
for the primary link interface.
Data Type Enumeration
Range UnAvailable (0) Module is unavailable for
communication.
Idle (1) Module is idle with no soft failures.
Ok (2) * Module is running with no soft failures.
NoResponse (3) No response from module.
IdleSF (4) Module is idle with soft fail error(s)
present.
SoftFail (5) * Module is running with soft fail error(s)
present.
CommError (6) Communication error to IOM.
ConfgMis (7) Configuration mismatch detected.
NotConfig (8) IOM not configured.
NonExist (9) Module does not exist at this address.
Default UnAvailable (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks *Only the values of Ok (2) or SoftFail (5) are displayed. Note that this is the same as
the PMMIOLST parameter in a TPS system.

18.196 PRIM.[1..8].INITIALIZABLE

Specific to Block All Regulatory Control Blocks


(s)
Description Primary Initializable - Determines if a regulatory control point is connected to
initializable primaries.
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active Loadable No

- 2284 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks

18.197 PRIMARYACE

Specific to ACE
Block(s)
Description Primary ACE name
Data Type String
Range 255
Default NA
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related
Parameters
Remarks This parameter is updated only for the secondary(backup) ACE. During cutover
when secondary blocks are created, this parameter gets updated in secondary
(backup) ACE for identifying its primary.

18.198 PRIMARYSIG

Specific to Block(s) Most Function Blocks


Description Primary Signature
Data Type String
Range Length: 24 characters
Default Null
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters NUMSIGS
Remarks Lets you specify the meaning associated with entering the primary
signature.

- 2285 -
Chapter 18 - Pxxxx Parameters

Specific to Block(s) UOC


Description Primary Signature Meaning
Data Type STRING
Range NA
Default
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Parameters
Remarks

18.199 PRIMCONNSTS

Specific to Block(s) PCDI_MASTER


Description Priamary Connection Status
Data Type Enumeration
Range 0 Invalid
1 Initial
2 Connecting
3 Connected
4 Failed
Default Initial (1)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.200 PRIMDATA.[1..8].ARWSTS

Specific to Block All Regulatory Control Blocks


(s)
Description Primary Data Anti-Reset Windup Status - Determines the windup status for
the primary
Data Type Enumeration ARWSTS
Range (0) Normal (1) HI (2) Lo (3) HiLo

- 2286 -
Chapter 18 - Pxxxx Parameters

Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

18.201 PRIMDATA.[1..8]. EUHI

Specific to All Regulatory Control Blocks


Block(s)
Description Primary Data Engineering Unit High - Determines the Engineering Unit High
(EUHI) value propagated to the primaries.
Data Type Float64
Range
Default
Config Load
Active No
Loadable
Access Lock Control
Residence CEE
Related
Parameters
Remarks

18.202 PRIMDATA.[1..8]. EULO

Specific to All Regulatory Control Blocks


Block(s)
Description Primary Data Engineering Unit Low - Determines the Engineering Unit Low
(EULO) value propagated to the primaries.
Data Type Float64
Range
Default
Config Load
Active No
Loadable

- 2287 -
Chapter 18 - Pxxxx Parameters

Access Lock Control


Residence CEE
Related
Parameters
Remarks

18.203 PRIMDATA.[1..8].HISELECT

Specific to All Regulatory Control Blocks


Block(s)
Description Primary Data High Selector - Determines if the override selector in an override
strategy is configured as a high or low selector for type of override propagation.
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

18.204 PRIMDATA.[1..8].INITSTS

Specific to Block All Regulatory Control Blocks


(s)
Description Primary Data Initialization Status - Determines the initialization status
propagated to the primaries.
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 2288 -
Chapter 18 - Pxxxx Parameters

18.205 PRIMDATA.[1..8].INITVAL

Specific to Block All Regulatory Control Blocks


(s)
Description Primary Data Initialization Value - Determines the initialization value
propagated to the primaries.
Data Type Float64
Range
Default
Config Load
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

18.206 PRIMDATA.[1..8].LOCALMAN

Specific to Block All Regulatory Control Blocks


(s)
Description Primary Data Local Manual - Determines the local manual status propagated
to the primaries.
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 2289 -
Chapter 18 - Pxxxx Parameters

18.207 PRIMDATA.[1..8].ORFBSTS

Specific to Block All Regulatory Control Blocks


(s)
Description Primary Data Override Feedback Status - Indicates the override feedback
status for the primary.
Data Type Enumeration
Range (0) Notconnected (1) Selected (2) Notselected
Default Notconnected
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

18.208 PRIMDATA.[1..8].ORFBVAL

Specific to Block All Regulatory Control Blocks


(s)
Description Primary Data Override Feedback Value - Specifies the override feedback value
for the primary.
Data Type Float64
Range
Default
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

- 2290 -
Chapter 18 - Pxxxx Parameters

18.209 PRIMDATA.[1..8].OROFFSET

Specific to All Regulatory Control Blocks


Block(s)
Description Primary Data Override Offset - Determines if an offset value is to be added to PID
blocks connected upstream.
Data Type Boolean
Range (0) Off (1) On
Default On
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

18.210 PRIMDATA.[1..8].PROPOVRD

Specific to Block All Regulatory Control Blocks


(s)
Description Primary Data Propagation Override - Determines if override status is to be
propagated to the primary.
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

- 2291 -
Chapter 18 - Pxxxx Parameters

18.211 PRIMERRCNT

Specific to Block(s) PCDI_MASTER


Description Primary connection Error Count
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.212 PRIMERRCODE

Specific to Block(s) PCDI_MASTER


Description Primary connection's last Error Code
Data Type Enumeration
Range 0 OK
256 Conn Forced
257 Socket Warn
258 Conn Fail
259 Count Exceeded
260 Send Blocking
512 Not Init
513 Socket Err
514 Timeout
515 No Conn
516 Send Fail

517 Msg Size


518 Invalid Buffer
519 Invalid Param
520 Devs Failed
Default Not Init
Config Load No
Active Loadable No

- 2292 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks The primary connections last error status.

18.213 PRIMERRFL

Specific to Block(s) PCDI_MASTER


Description Primary Error Flag
Data Type Boolean
Range True/False
Default True
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.214 PRIMERRINFO

Specific to Block(s) PCDI_MASTER


Description Primary additional Error Information
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2293 -
Chapter 18 - Pxxxx Parameters

18.215 PRIMIP

Specific to PCDI_MASTER
Block(s)
Description Primary IP Address
Data Type String
Range 16
Default 0.0.0.0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks You cannot enter an invalid value such as zero or a duplicate value as the
secondary IP address with identical ports. An error message appears, if you try to
enter an invalid value. The default value is an invalid value.

18.216 PRIMIPMON

Specific to Block(s) PCDI_MASTER


Description Primary IP Address Monitor
Data Type String
Range 16
Default 0.0.0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.217 PRIMLASTCONNTIME

Specific to Block(s) PCDI_MASTER


Description Primary Last Connect Time
Data Type Time
Range
Default 0

- 2294 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.218 PRIMLASTDISCONNTIME

Specific to Block(s) PCDI_MASTER


Description Primary Last Disconnect Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.219 PRIMLASTERRTIME

Specific to Block(s) PCDI_MASTER


Description Primary Last Error Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2295 -
Chapter 18 - Pxxxx Parameters

18.220 PRIMLOOPDATA

Specific to PCDI_MASTER
Block(s)
Description Primary Loop Data
Data Type String
Range 40 Characters
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter is only active through the Monitoring tab of Control Builder for a
single device, this is the actual data value that is changing during diagnostic testing
for a primary connection. During monitoring, this value will be the result of the
diagnostic testing that occurs and will change. For example, on a diagnostic coil
with the invert LOOPMODE selected, this value will toggle between 1 and 0.

18.221 PRIMNUMCONN

Specific to Block(s) PCDI_MASTER


Description Primary Number of Successful Connects
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2296 -
Chapter 18 - Pxxxx Parameters

18.222 PRIMNUMCONNATMPT

Specific to Block(s) PCDI_MASTER


Description Primary Number of Connection Attempts
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.223 PRIMNUMDISCONN

Specific to Block(s) PCDI_MASTER


Description Primary Number of Disconnects
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.224 PRIMOVERLAP[1..24]

Specific to Block QIPACTERM


Description Primary Overlapped Feed in Progress
Data Type Boolean
Range Off(0) Off
On(1) In Progress
Default 0
Config Load No
Active Loadable No

- 2297 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This is the value of bit 14 of the Status 2 word in the input assembly for the
designated position [1-24].

18.225 PRIMOVERLAP[1..200]

Specific to QIPACCHAN
Bloc:
Description Primary Overlapped Feed in Progress
Data Type Boolean
Range Off(0) Off
On(1) In Progress
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 14 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

18.226 PRIMTCP

Specific to PCDI_MASTER
Block(s)
Description Primary TCP Port
Data Type 16-Bit Unsigned Integer
Range
Default 502
Config Yes
Load
Active No
Loadable

- 2298 -
Chapter 18 - Pxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related
Parameters
Remarks You cannot set the value for this parameter to zero. An error message appears and
the value will not be stored, if you try to enter a value of zero. An error message will
also appear, if an invalid value is in the database when the configuration form is
closed.

18.227 PRIMTCPMON

Specific to Block(s) PCDI_MASTER


Description Priamry TCP Port Monitor
Data Type 16-Bit Unsigned Integer
Range
Default 502
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.228 PRIORITYIOM

Specific to Series C I/O Modules


Block(s)
Description Priority IOM
Data Type Boolean
Range 0 Off Not configured to be a
Priority IOM
1 On Configured to be a Priority
IOM
Default Off (0)
Config CEE
Load
Active No
Loadable

- 2299 -
Chapter 18 - Pxxxx Parameters

Access Application Developer


Lock
Residence IOM
Related
Parameters
Remarks When this parameter is set, the IO module's process data collection from the
IOLINK will be better synchronized with the control cycle providing lower latency.
Note: IO Modules with this parameter set will use up a large amount of additional
Link Units. Excessive use of this option will result in overruns. Therefore, it is
recommended to use only for strategies with strict latency requirements. If a
change in the status of an IO Module is desired, it must be changed in the Project
Tree and then reloaded. This does not require IO Module deletion from the
Monitoring Tree first.

18.229 PRIRCVCHN [1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Primary IOP Active Receive Channel. Shows the channel that is actively listening to
the transmitted messages, where the index of this array corresponds to the
number of the Input/Output Processor (IOP).
Data Type Enumeration
Range UNKNOWN: No active channel.
CHANNEL_A: Channel A is active.
CHANNEL_B: Channel B is active.
--- IOP is not configured.
Default UNKNOWN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related IOPCOMMAND
Parameters
Remarks If the PERSWAPENB parameter is On, the active receive channel toggles between A
and B once a minute. Note that this is the same as the IOMRECHN parameter in a
TPS system.

- 2300 -
Chapter 18 - Pxxxx Parameters

18.230 PRISECKEYSWMISMATCH

Specific to Block(s) TCMI


Description Prim and Secondary Keyswitch Position mismatch
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.231 PROCDEADTIME

Specific to PID-PL
Block(s)
Description Process Deadtime, in Minutes - Process deadtime (transportation lag) as defined in
the Laplace transfer function model.
Data Type Float64
Range 0 - 3000 * Ts
Default 0
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related D[1..5]N
Parameters [1..5]
NUMCOEFDEN
NUMCOEFNUMPROCDEADTIMEACTPROCDEADTIMEBIASPROCGAIN
RESETMODEL UPDATEMODEL
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. After the function block has been loaded, this parameter must be updated
(see UPDATEMODEL ) before any change in its value is implemented. The effective
model deadtime of an active function block can be altered without updating using a
separate deadtime bias, PROCDEADTIMEBIAS, or directly through
PROCDEADTIMEACT. This parameter is applicable only when CTLEQN is set to
Profit Loop PKS, and is ignored in PID control equations.

- 2301 -
Chapter 18 - Pxxxx Parameters

18.232 PROCDEADTIMEACT

Specific to PID-PL
Block(s)
Description Active Process Deadtime, in Minutes - Active value of the process deadtime
(transportation lag) used in the Profit Loop PKS control algorithm.
Data Type Float64
Range 0 to 1.2*PROCDEADTIME
Default
Config No
Load
Active No
Loadable
Access Other Function Block
Lock
Residence CEE
Related PROCDEADTIMEPROCDEADTIME, PROCDEADTIMEBIAS
Parameters
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. After the function block has been loaded, PROCDEADTIME must be
updated (see UPDATEMODEL ) before any change in its value is implemented. The
effective model deadtime of an active function block can be altered without
updating using a separate deadtime bias, PROCDEADTIMEBIAS, or directly through
PROCDEADTIMEACT. PROCDEADTIMEACT is overwritten when the Laplace
transfer function model is updated or when a deadtime bias value is entered. In this
situation, PROCDEADTIMEACT = PROCDEADTIME + PROCDEADTIMEBIAS
PROCDEADTIMEACT is intended for use with external gain scheduling programs.
This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

18.233 PROCDEADTIMEBIAS

Specific to PID-PL
Block(s)
Description Process Deadtime Bias, in Minutes - Bias applied to the process deadtime to alter
the effective delay used in the Profit Loop PKS control algorithm.
Data Type Float64
Range (-PROCDEADTIME) to (0.2 * PROCDEADTIME)
Default 0
Config No
Load
Active No
Loadable

- 2302 -
Chapter 18 - Pxxxx Parameters

Access Operator
Lock
Residence CEE
Related PROCDEADTIME, PROCDEADTIMEACT.
Parameters
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. After the function block has been loaded, PROCDEADTIME must be
updated (see UPDATEMODEL.) before any change in its value is implemented. The
effective model deadtime on an active function block can be altered using a
separate deadtime bias, PROCDEADTIMEBIAS, or directly through
PROCDEADTIMEACT. PROCDEADTIMEBIAS is overwritten when the Laplace
transfer function model is updated or when the deadtime is directly entered in
PROCDEADTIMEACT. In this situation, PROCDEADTIMEBIAS = PROCDEADTIMEACT
- PROCDEADTIME This parameter is applicable only when CTLEQN is set to Profit
Loop PKS, and is ignored in PID control equations.

18.234 PROCEDURALLEVEL

Specific to Block(s) SCM


Description Procedural Level
Data Type Enumeration
Range 0 None
1 Phase
2 Unitop
3 UnitProcedure
4 Procedure
5 Batch
Default Unitop
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks
NOTE User should only set the
PROCEDUREICON parameter as template
defining if they’ve already set the
PROCEDURALLEVEL as template defining.

- 2303 -
Chapter 18 - Pxxxx Parameters

18.235 PROCESS_ID

Specific to Block(s) C300 FBs, SIMEHPM, UOC, CN100


Description WIN32 Process Identifier
Data Type UINT32
Range 0 and larger, 0 to 4294967295
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SIMC300, SIMEHPM
Related Parameters
Remarks Indicates the process ID of the simulator executable.

18.236 PROCESSED

Specific to Handler, Step, Transition, Phase


Block(s)
Description Component has been processed flag.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RSTPROCESSED
Parameters
Remarks An SCM component's Processed flag is set if it has been included in the SCM's
execution thread. All components' processed flags reset only when the SCM STATE
transitions to Checking (either by a Reset command or Check Handler's Invoke
Transition).

- 2304 -
Chapter 18 - Pxxxx Parameters

18.237 PROCGAIN

Specific to PID-PL
Block(s)
Description Process Gain -
Data Type Float64
Range 1
Default 1
Config Load
Active No
Loadable
Access Lock Engineer
Residence
Related D[1..5], N[1..5], NUMCOEFNUM, NUMCOEFDEN, PROCDEADTIME,
Parameters UPDATEMODEL, RESETMODEL, MODELUPDATED
Remarks Confirmation/Information if CTLACTN changes. Update when button pushed.

18.238 PROCGAINACT

Specific to PID-PL
Block(s)
Description Active Process Gain, in Engineering Units - Active value of the process gain used in
the Profit Loop PKS control algorithm.
Data Type Float64
Range <>0
Default
Config No
Load
Active No
Loadable
Access Other Function Block
Lock
Residence CEE
Related PROCGAINEU, PROCGAINMULT.
Parameters
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. After the function block has been loaded, PROCGAINEU must be updated
(see UPDATEMODEL) before any change in its value is implemented. The effective
model gain of an active function block can be altered without updating using a
separate gain multiplier, PROCGAINMULT, or directly through PROCGAINACT.
PROCGAINACT is overwritten when the Laplace transfer function model is updated
or when a gain multiplier is entered. In this situation, PROCGAINACT =
PROCGAINEU * PROCGAINMULT PROCGAINACT is intended for use with external
gain scheduling programs. This parameter is applicable only when CTLEQN is set to
Profit Loop PKS, and is ignored in PID control equations.

- 2305 -
Chapter 18 - Pxxxx Parameters

18.239 PROCGAINEU

Specific to PID-PL
Block(s)
Description Process Gain, in Engineering Units - Process gain associated with the Laplace
transfer function model of the process.
Data Type Float64
Range <> 0
Default 1
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related CTLACTN, D[1..5], N[1..5], NUMCOEFNUM, NUMCOEFDEN, PROCDEADTIME,
Parameters PROCDEADTIMEACT, PROCGAINMULT, PROCGAINPCT, PROCGAINUNITS,
RESETMODEL, UPDATEMODEL.
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. After the function block has been loaded, this parameter must be updated
(See UPDATEMODEL.) before any change in its value is implemented. The effective
model gain of an active function block can be altered without updating using a
separate gain multiplier, PROCGAINMULT, or directly through PROCGAINACT.
PROCGAINEU and PROCGAINPCT are two views of the same Laplace transfer
function model gain with the latter being scaled. If the sign of the process gain
changes, CTLACTN is automatically altered to reflect the new control action. This
parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is ignored
in PID control equations.

18.240 PROCGAINMULT

Specific to PID-PL
Block(s)
Description Process Gain Multiplier - Multiplier applied to the process gain to alter the effective
gain used in the Profit Loop PKS control algorithm.
Data Type Float64
Range 0.01 - 100
Default 1
Config No
Load
Active No
Loadable

- 2306 -
Chapter 18 - Pxxxx Parameters

Access Operator
Lock
Residence CEE
Related PROCGAINMULT, PROCGAINEU.
Parameters
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. After the function block has been loaded, PROCGAINEU must be updated
(see UPDATEMODEL.) before any change in its value is implemented. The effective
model gain of an active function block can be altered without updating using a
separate gain multiplier, PROCGAINMULT, or directly through PROCGAINACT.
PROCGAINMULT is overwritten when the Laplace transfer function model is
updated or when a gain multiplier is entered. In this situation, PROCGAINMULT =
PROCGAINACT / PROCGAINEU This parameter is applicable only when CTLEQN is
set to Profit Loop PKS, and is ignored in PID control equations.

18.241 PROCGAINPCT

Specific to PID-PL
Block(s)
Description Process Gain, in %PV/%OP - Process gain associated with the Laplace transfer
function model of the process.
Data Type Float64
Range <>0
Default 1
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related CTLACTN, D[1..5], N[1..5], NUMCOEFNUM, NUMCOEFDEN, PROCDEADTIME,
Parameters PROCDEADTIMEACT, PROCGAINMULT, PROCGAINEU, PROCGAINUNITS,
RESETMODEL, UPDATEMODEL.
Remarks The Profit Loop PKS control algorithm requires a dynamic model of the process for
prediction, control, and optimization. This model is entered as a Laplace transfer
function. After the function block has been loaded, this parameter must be updated
(see UPDATEMODEL.) before any change in its value is implemented. The effective
model gain of an active function block can be altered without updating using a
separate gain multiplier, PROCGAINMULT, or directly through PROCGAINACT.
PROCGAINEU and PROCGAINPCT are two views of the same Laplace transfer
function model gain with the latter being scaled. If the sign of the process gain
changes, CTLACTN is automatically altered to reflect the new control action. This
parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is ignored
in PID control equations.

- 2307 -
Chapter 18 - Pxxxx Parameters

18.242 PROCGAINUNITS

Specific to PID-PL
Block(s)
Description Process Gain Units - Flag indicating whether to display process gain in
engineering units or in percent.
Data Type Enumeration PLPROCGAINUNITS
Range PVEU/OPEU: Display gain in engineering units
%PV/%OP: Display gain in percent
Default %PV/%OP
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PROCGAINEU, PROCGAINPCT.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

18.243 PRODCODE

Specific to RM
Block(s)
Description Product Code. Identification of RM within product type (per ASA specification).
Data Type 16-Bit Unsigned Integer
Range 0 to 65535
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 2308 -
Chapter 18 - Pxxxx Parameters

18.244 PRODCODEA

Specific to Block RM
(s)
Description Module Product Code. For each module in the host chassis, factory assigned
product code
Data Type 16-Bit Unsigned Integer [20]
Range 0 to 65535
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

18.245 PRODTYPE

Specific to All IOM Function Blocks


Block(s)
Description IO Module Product Type - The numeric representation of a high level classification
of module type; see default values.
Data Type 32-Bit Integer
Range N/A
Default 10 for Analog Input/Output Modules, including Thermocouple and RTD. 7 for
Digital Input/Output Modules 12 for Serial Interface Module 109 for Pulse Input
Module
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related IOMTYPE
Parameters
Remarks Although loaded, this parameter is not exposed on any configuration form.

Specific to RM
Block(s)
Description Product Type. Identification of general RM type (per ASA specification).
Data Type 16-Bit Unsigned Integer
Range 0 to 65535
Default 0

- 2309 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

18.246 PRODTYPEA

Specific to RM
Block(s)
Description Module Product Type. For each module in the host chassis, factory assigned
product type.
Data Type 16-Bit Unsigned Integer [20]
Range 0 to 65535
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

18.247 PROFILEDESC[1..NUMPROFILES]

Specific to Block(s) RampSoak


Description Profile Descriptor
Data Type String
Range 15 Characters
Default Profile<#> where <#> is the number of profile.
Config Load
Active Loadable No

- 2310 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters
Remarks

18.248 PROFILEID

Specific to Block(s) RampSoak


Description Profile ID
Data Type Integer
Range N/A
Default 1
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

18.249 PROFINETENABLE

Specific to Block(s) UOC


Description Enable PROFINET updates in UOC
Data Type Boolean
Range On/Off
Default Off
Config Load Yes
Active Loadable Yes
Access Lock AppDevOnly
Residence CEE
Related Parameters DCPSCAN
DCPREAD
DCPSETIPADDR
DCPSETSIGNAL
DCPSETFACTORYRESET
PNETCONFIGCHNG
PNETCONFIGCHNG
Remarks

- 2311 -
Chapter 18 - Pxxxx Parameters

18.250 PROFRESET

Specific to RAMPSOAK
Block(s)
Description Profile Reset flag: Allows another function block or user program to reset the
profile.
Data Type Boolean
Range 0 OFF
1 ON
Default OFF (0)
Config No
Load
Active No
Loadable
Access Lock Otherfb
Residence
Related
Parameters
Remarks When the PROFRESET parameter changes from OFF to ON, the profile is reset and
the mode changes to MANUAL. The Profile is reset only when PROFRESET goes
from OFF to ON. The parameter must be reset to OFF before issuing another reset
command.

18.251 PROGCMD

Specific to RM
Block(s)
Description Program Command Recognition
Data Type Enumeration
Range Disabled (0) Enabled (1)
Default Disabled (0)
Config Load No
Active No
Loadable
Access Lock Operator Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 2312 -
Chapter 18 - Pxxxx Parameters

18.252 PROGCMDRECOG

Specific to RM
Block(s)
Description Program Command Recognition. Configurable option regarding Redundancy
Module recognition of user program commands
Data Type Enumeration
Range Disabled (0) Enabled (1)
Default Disabled (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

18.253 PROGID[0..40]

Specific to OPC
Block(s)
Description Program Identification - Specifies the Microsoft COM object Program ID for the
intended OPC sever. For example, use hci .tpnserver for the TPN server of a TPS
APP node or hwhsc.opcserver for Experion PKS OPC server.
Data Type String
Range N/A
Default N/A
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence SR
Related HOSTIPPRI
Parameter
Remarks You can specify this parameter as either version specific or general. For example,
hci.tpnserver.3 would be version specific and hci.tpnserver would be general. The
general type makes the version upgrade of OPC server component more automatic,
since it requires fewer user actions.

- 2313 -
Chapter 18 - Pxxxx Parameters

18.254 PROGLCKTOIDLE

Specific to Block(s) CEE, CEEC300, CEEACE, CEESIMC200, CEEUOC, CEECN100


Description Program Access may command CEE from Run to Idle
Data Type Boolean
Range N/A
Default True
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameter PROGLCKTORUN, USERLCKTORUN, USERLCKTOIDLE.
Remarks

18.255 PROGLCKTORUN

Specific to Block(s) CEE, CEEC300, CEEACE, CEESIMC200, CEEUOC, CEECN100


Description Program Access may command CEE from Idle to Run
Data Type Boolean
Range N/A
Default True
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameter PROGLCKTOIDLE, USERLCKTOIDLE, USERLCKTORUN.
Remarks

18.256 PROGLOCKED

Specific to Block(s) SCM


Description Mode Attribute Program is Locked
Data Type Boolean
Range
Default False
Config Load No
Active Loadable No

- 2314 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameter
Remarks

18.257 PROGPACKET[0..2]

Specific to Block(s) SCM, CM, RCM


Description Internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

18.258 PROGSTSDESC

Specific to CAB types


Block(s)
Description Program Status Descriptor. String valued parameter that can be used within a CAB
program to publish the last error detected by the program.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type String
Range 64 characters
Default Blank
Config Load No
Active No
Loadable

- 2315 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related CABSTATE, EXCPTNTYPE, EXECSTATE of parent CM
Parameters
Remarks PROGSTSDESC is never automatically written by CAB run-time services except for
a small set of conditions upon which it is automatically cleared. These conditions
are as follows:
l CAB instance load.
l Parent CM transitions to Active.
l CABSTATE transitions to Normal.
PROGSTSDESC only conveys information if the CAB program is written to detect
and report error information. Otherwise, it always shows blank.

18.259 PROTOSTSTYPE

Specific to Block(s) EIM


Description Protocol status type
Data Type ENUM
Range NA
Default IEC-Quality
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

18.260 PRPVHIGH.FL

Specific to Block(s) PROFITCTLIN


Description PRPVHIGH FL
Data Type BOOL
Range OFF, ON
Default OFF
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

- 2316 -
Chapter 18 - Pxxxx Parameters

18.261 PrPVHigh.OffDelayTimeSec

Specific to PROFITCTLIN
Block(s)
Description PredPVHigh:Off-Delay Time(sec)
Data Type UINT32
Range 0 to 65535
Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVHigh.TripPoint, PrPVHigh.Priority, PrPVHigh.Severity,
Parameters PrPVHigh.OnDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.262 PrPVHigh.OnDelayTimeSec

Specific to PROFITCTLIN
Block(s)
Description PredPVHigh:On-Delay Time(sec)
Data Type UINT32
Range 0 to 65535
Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVHigh.TripPoint, PrPVHigh.Priority, PrPVHigh.Severity,
Parameters PrPVHigh.OffDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.263 PrPVHigh.Priority

Specific to PROFITCTLIN
Block(s)
Description PredPVHigh:Priority
Data Type ENUM
Range None (0) Journal (1) Low (2) High (3) Urgent (4)

- 2317 -
Chapter 18 - Pxxxx Parameters

Default None
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVHigh.TripPoint, PrPVHigh.Severity,
Parameters PrPVHigh.OnDelayTimeSec, PrPVHigh.OffDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.264 PrPVHigh.Severity

Specific to PROFITCTLIN
Block(s)
Description PredPVHigh:Severity
Data Type INT16
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVHigh.TripPoint, PrPVHigh.Priority,
Parameters PrPVHigh.OnDelayTimeSec, PrPVHigh.OffDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.265 PrPVHigh.TripPoint

Specific to PROFITCTLIN
Block(s)
Description PredPVHigh:Trip Point
Data Type FLOAT64
Range ±1.7E+308
Default NaN
Config Load Yes
Active No
Loadable

- 2318 -
Chapter 18 - Pxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related NUMBEROFCVS , PrPVHigh.Priority, PrPVHigh.Severity,
Parameters PrPVHigh.OnDelayTimeSec, PrPVHigh.OffDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.266 PRPVLOW.FL

Specific to Block(s) PROFITCTLIN


Description PRPVLOW FL
Data Type BOOL
Range OFF, ON
Default OFF
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters NUMBEROFCVS
Remarks Arrayed parameters of size NUMBEROFCVS

18.267 PrPVLow.OffDelayTimeSec

Specific to PROFITCTLIN
Block(s)
Description PredPVLow:Off-Delay Time(sec)
Data Type UINT32
Range 0 to 65535
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVLow.TripPoint, PrPVLow.Priority, PrPVLow.Severity,
Parameters PrPVLow.OnDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

- 2319 -
Chapter 18 - Pxxxx Parameters

18.268 PrPVLow.OnDelayTimeSec

Specific to PROFITCTLIN
Block(s)
Description PredPVLow:On-Delay Time(sec)
Data Type UINT32
Range 0 to 65535
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVLow.TripPoint, PrPVLow.Priority, PrPVLow.Severity,
Parameters PrPVLow.OffDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.269 PrPVLow.Priority

Specific to PROFITCTLIN
Block(s)
Description PredPVLow:Priority
Data Type ENUM
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVLow.TripPoint, PrPVLow.Severity,
Parameters PrPVLow.OnDelayTimeSec, PrPVLow.OffDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.270 PrPVLow.Severity

Specific to PROFITCTLIN
Block(s)
Description PredPVLow:Severity
Data Type INT16
Range 0 to 15

- 2320 -
Chapter 18 - Pxxxx Parameters

Default 0
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVLow.TripPoint, PrPVLow.Priority,
Parameters PrPVLow.OnDelayTimeSec, PrPVLow.OffDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.271 PrPVLow.TripPoint

Specific to PROFITCTLIN
Block(s)
Description PredPVLow:Trip Point
Data Type FLOAT64
Range ±1.7E+308
Default NaN
Config Load Yes
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related NUMBEROFCVS , PrPVLow.Priority, PrPVLow.Severity,
Parameters PrPVLow.OnDelayTimeSec, PrPVLow.OffDelayTimeSec
Remarks Arrayed parameter of size NUMBEROFCVS

18.272 PRSLOPE

Specific to LEVELCOMP
Block(s)
Description Drum pressure slope
Data Type Float64
Range
Default 1
Config Load YES
Active No
Loadable

- 2321 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence CEE
Related PRESSUREPRBIAS
Parameters
Remarks This parameter participates in ranging required for the Pressure using the formula
of a straight line y = mx +c where m is the slope and c is bias constant.

18.273 PSTS

Specific to Block FLOWCOMP


(s)
Description Pressure Input Value Status - Indicates the current status of pressure input
P.
Data Type Enumeration PVVALSTS
Range Bad (0): The value is bad and has been replaced
with NaN.
Uncertn (1): The status of the value is uncertain.
Normal (2): The value is good.
Manual (3): The value was manually stored.
Default Normal
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C200, C300, ACE
Related P
Parameters
Remarks

18.274 PSTS[1..6]

Specific to Auxcalc, SignalSel


Block(s)
Description Status of PV Input Values 1 through 6 - The current value status of up to six PV
inputs to an Auxiliary function block.
Data Type Enumeration PVVALSTS
Range Bad (0): The value is bad and has been replaced
with NaN.
Uncertn (1): The status of the value is uncertain.
Normal (2): The value is good.
Manual (3): The value was manually stored.
Default Bad (0)

- 2322 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related P[1..6]
Parameters
Remarks

18.275 PSTS[1..10]

Specific to AUXSUMMER
Block(s)
Description Process Input Status - The current value status associated with given input (P
[1..10]) parameter to the block.
Data Type Enumeration PVVALSTS
Range Bad (0): The value is bad and has been replaced
with NaN.
Uncertn (1): The status of the value is uncertain.
Normal (2): The value is good.
Manual (3): The value was manually stored.
Default Bad (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related P[1..10]
Parameters
Remarks

18.276 PSUB[1..10]

Specific to AUXSUMMER, ENHAUXCALC


Block(s)
Description Process Input Substitute - Defines the substitute value to be used in place of the
given disabled input (P[1..10] parameter.
Data Type Float64
Range
Default NaN
Config Load No

- 2323 -
Chapter 18 - Pxxxx Parameters

Active No
Loadable
Access Lock Engineer
Residence CEE
Related P[1..10]
Parameters
Remarks

18.277 PTEXECST

Specific to Block PM I/O Channels; Series C I/O Channels


(s)
Description Point Execution State. Defines the execution state of the associated point as
Inactive or Active.
Data Type Enumeration
Range Inactive (0): Point is not scanned or processed.
Active (1): Point is scanned and processed.
Default Inactive (0)
Config Load No
Active Loadable No
Access Lock Supervisor
Residence IOM
Related
Parameters
Remarks When PTEXECST is Inactive, the point processing does not occur for the
channel.

18.278 PTEXECST[1..NUMCHAN]

Specific to Block HLAI, HLAI_100, STI_MV, AO8, AO16, DI, DI24, DISOE, DO16, DO32
(s)
Description Point Execution State. Defines the execution state of the associated point as
Inactive or Active.
Data Type Enumeration
Range Inactive (0): Point is not scanned or processed.
Active (1): Point is scanned and processed.
Default Inactive (0) For DO and DI IOPs, the unconfigured channel default value is
ACTIVE (1).
Config Load No
Active Loadable No

- 2324 -
Chapter 18 - Pxxxx Parameters

Access Lock Supervisor


Residence IOP
Related
Parameters
Remarks When PTEXECST is Inactive, the point processing does not occur for the
channel.

18.279 PTNRFLTIP

Specific to Block ACE


Description Partner floating IP Address
Data Type STRING
Range 15
Default 0.0.0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters

This parameter displays the floating IP of the backup ACE when the cut-over
Remarks is initiated.

18.280 PTPDELAY

Specific to Block(s) EIM, UOC, CN100


Description PTP Delay (msec)
Data Type FLOAT64
Range ±1.7E+308

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Network travel time between PTP server and device, in milliseconds.

- 2325 -
Chapter 18 - Pxxxx Parameters

18.281 PTPDELAYMAX

Specific to Block EIM, UOC, CN100


(s)
Description PTP Maximum Delay (msec)
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of network travel time between PTP server and device, in
milliseconds.

18.282 PTPENABLE

Specific to EHPM,EIM, TCMI, UOC, CN100


Block(s)
Description Enable Precision Time Protocol
Data Type BOOLEAN
Range ON (1)
Default ON (1)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence SR, CEE
Related
Parameters
Remarks When enabled (ON), the PTP client should attempt to synchronize its local clock
with a PTP GrandMaster. For EHPM, this value is set as ON by default. It can be
configured only from the Monitoring view.

- 2326 -
Chapter 18 - Pxxxx Parameters

18.283 PTPMASTERIP

Specific to Block(s) C300, PGM2, FIM4, FIM8, EHPM , EIM, TCMI, UOC, CN100
Description PTP Master IP Address
Data Type STRING
Range -
Default 0.0.0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, EHPM , ‘NOLOAD
Related Parameters
Remarks This parameter displays the IP address of the PTP GrandMaster clock.

18.284 PTPNUMNODELAYRESP

Specific to C300, PGM2, FIM4, and FIM8, EHPM


Block(s)
Description PTP Delay Reqs without Resp
Data Type UINT32
Range -
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, and EHPM
Related
Parameters
Remarks This parameter displays the count of instances the PTP client sends a PTP Delay_
Req message without receiving a PTP Delay_Resp message.

18.285 PTPNUMNOFOLLOWUP

Specific to C300, PGM2, FIM4, and FIM8, EHPM


Block(s)
Description PTP Syncs without Follow Up
Data Type UINT32
Range -
Default 0

- 2327 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, and EHPM
Related
Parameters
Remarks This parameter displays the count of instances the PTP client receives a PTP Sync
message without receiving a PTP Follow_Up message.

18.286 PTPNUMNOSYNC

Specific to C300, PGM2, FIM4, and FIM8, and EHPM


Block(s)
Description PTP Follow Ups without Sync
Data Type UINT32
Range -
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, and EHPM
Related
Parameters
Remarks This parameter displays the count of instances the PTP client receives a PTP
Follow_Up message without receiving a PTP Sync message.

18.287 PTPOFFSET

Specific to Block(s) EIM, TCMI, UOC, CN100, C300


Description PTP Offset (msec)
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Clock offset between PTP server and device, in milliseconds.

- 2328 -
Chapter 18 - Pxxxx Parameters

18.288 PTPOFFSETMAX

Specific to Block(s) EIM, TCMI, UOC, CN100, C300


Description PTP Maximum Offset (msec)
Data Type FLOAT64
Range ±1.7E+308
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks High water mark of clock offset between PTP server and device, in
milliseconds.

18.289 PTPROCESSOROVERRUN

Specific to Block(s) TCMI


Description Point Processor Overrun
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

18.290 PTPSKEWTHLD

Specific to C300, PGM2, FIM4, FIM8, EHPM


Block(s)
Description PTP Skew Limit (msec)
Data Type UINT32
Range -
Default 0
Config No

- 2329 -
Chapter 18 - Pxxxx Parameters

Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE, EHPM
Related
Parameters
Remarks This parameter displays (in milliseconds) the maximum skew between the local
clock and PTP GrandMaster clock, under which gradual correction of the local clock
will be allowed. When the system clock skew exceeds this value, the system clock will
be adjusted with a discontinuous jump.

18.291 PTPSTAT

Specific to C300, PGM2, FIM4, FIM8, EHPM , EIM


Block(s)
Description PTP Status
Data Type ENUM
Range (0) Failed (1) OK (3) NotActive (4) Listening
Default (3) NotActive
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, EHPM , NOLOAD
Related
Parameters
Remarks This parameter displays the current status of the PTP time synchronization:
l Failed - Module is unable to synchronize with a PTP GrandMaster.
l OK - Module has identified and PTP GrandMaster clock and is
synchronizing the module's system clock.
l NotActive - Module is not using PTP time (status when PTPENABLE is
OFF).
l Listening - Module is listening for PTP GrandMaster clock.

Specific to Block(s) UOC


Description PTP Status
Data Type ENUM
Exposure None
Range N/A
Default -
Config Load No
Active Loadable

- 2330 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks PTP time synchronization status.

Specific to Block(s) TCMI


Description PTP Status
Data Type STRING

Exposure None
Range N/A
Default --
Config Load No
Active Loadable NA
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks PTP time synchronization status.

18.292 PUBLICNAME

Specific to SCM, RCM, and MR


Block(s)
Description A name used to identify a group of recipe.
Data Type String
Range The tag name can be up to 40 characters.
Default Tag name of SCM/RCM/MR
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related
Parameters
Remarks If this parameter value is enabled, when you change the name, the value is set as
the name. If this parameter value is disabled, the Public Name is not affected.

- 2331 -
Chapter 18 - Pxxxx Parameters

18.293 PUBMETHOD

Specific to LINK, FFLINK


Block(s)
Description Publication Method - Select the peer-to-peer publication and subscription rate
between a FIM/FIM4 and a C200/C300.
Data Type Enumeration
Range 0 Immediate Sends publications immediately through CDA with
subscription rate of 200 milliseconds. Provides lowest
latency and highest processor use on C200/C300 peer
targets. This is the default behavior for Experion releases
prior to R310.

1 Periodic, Sends publications every 250 milliseconds with a


250 msec subscription rate of 250 milliseconds. Recommended for
fast macrocycles.
2 Periodic, Sends publications every 500 milliseconds with a
500 msec subscription rate of 500 milliseconds.
3 Periodic, 1 Sends publications every 1 second with a subscription
sec rate of 1 second. Provides highest latency and lowest
processor use on C200/C300 peer targets.
Default Immediate
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence PCM
Related
Parameters
Remarks Allows links with slow macrocycles to intelligently pack peer-to-peer
communications to C300s for an increased number of parameters per second.

18.294 PULSECMD

Specific to Block(s) PosProp, PidPosProp


Description Pulse Command - Indicates the current pulse command.
Data Type Enumeration PULSECMD
Range Idle (0): Output is not being affected by PULSECMD.
Lower (1): Output is being lowered.
Raise (2): Output is being raised.
Default N/A
Config Load No
Active Loadable No

- 2332 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

18.295 PULSECMDTEXT[0..2]

Specific to PosProp
Block(s)
Description Pulse Command Descriptor Text - Defines text for the three states of the Pulse
Command; PULSECMDTEXT[0] corresponds to the Boolean state of Idle for the
Pulse Command, PULSECMDTEXT[1] corresponds to the Raise command, and
PULSECMDTEXT[2] corresponds to the Low command.
Data Type String
Range Length: 255 characters
Default PULSECMDTEXT[0] Idle
PULSECMDTEXT[1] Raise
PULSECMDTEXT[2] Low
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PUBMETHODPULSECMD
Parameters
Remarks

18.296 PULSEINTYPE

Specific to Series C PICHANNEL


Block(s)
Description Pulse Input Channel Type
Data Type ENUM
Range Pulse Input(0) Pulse Input with Fast Cutoff(1)
Default Pulse Input(0)
Config Load Yes
Active No
Loadable

- 2333 -
Chapter 18 - Pxxxx Parameters

Access Lock AppDevOnly


Residence IOM
Related N/A
Parameters
Remarks Pulse Input is valid for channel 1 through channel 8. Pulse Input with Fast Cutoff
is valid only for channel 7 and channel 8.

18.297 PULSEMODE

Specific to Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Pulse Length Measurement Mode - Selects the portion of pulse whose time is
measured.
Data Type Enumeration
Range PulseHigh (0) PulseLow (1) Period (2)
Default PulseHigh (0)
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence CEE
Related
Parameters
Remarks Period mode means the Timer and Timer Latch measures the period of the input.
That is, the time elapsed between two consecutive Off-to-On transitions is recorded.
PulseHigh means the Timer and Timer Latch measure the “high”pulse width of
the input, that is, the time elapsed between an initial Off-to-On transition and a
later On-to-Off transition is recorded. Pulse Low means the Time Measure Mode is
Pulse Low. The Timer and Timer Latch measure the “low” pulse width of t he input,
that is, the time elapsed between an initial On-to-Off transition and a later Off-to-
On transition is recorded.

Specific to Series C PICHANNEL


Block(s)
Description Pulse Measurement Mode
Data Type ENUM
Range Period(0) PulseHigh(1) PulseLow(2)
Default PulseHigh
Config Load Yes
Active No
Loadable

- 2334 -
Chapter 18 - Pxxxx Parameters

Access Lock AppDevOnly


Residence IOM
Related N/A
Parameters
Remarks PULSEMODE represents whether the period or a specified pulse length of the
signal (applied to the screw terminals) will be measured.
l PULSEHIGH - Provides the elapsed time between an Off-to-On transition and
the next On-to-Off transition.
l PULSELOW - Provides the elapsed time between an On-to-Off transition and
the next Off-to-On transition.
l PERIOD - Provides the elapsed time between two consecutive Off-to-On
transitions.
All measurements have the resolution of 1 microsecond. The recorded value only
pertains to the last occurrence or event.

18.298 PULSEMODE[0..5]

Specific to Pulse Input IOM


Block(s)
Description Pulse Length Measurement Mode - Selects the portion of pulse whose time is
measured.
Data Type Enumeration
Range PulseHigh (0): Provides the elapsed time between an Off-to-On
transition and the next On-to-Off transition.
PulseLow (1): Provides the elapsed time between an On-to-Off
transition and the next Off-to-On transition.
Period (2): Provides the elapsed time between two consecutive Of-
to-On transitions.
Default PulseHigh (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Affects channels 0 to 5 only.

- 2335 -
Chapter 18 - Pxxxx Parameters

18.299 PULSETIME

Specific to Pulse Length Control, Pulse Count Control, PosProp, PidPosProp.


Block(s)
Description Pulse Time requested (in seconds)
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter is a structure, the main value of which is the Pulse Time requested,
in seconds. This parameter usually gets its input from the PosProp function block

18.300 PULSEWIDTH

Specific to Block(s) NooN


Description Pulsewidth in seconds
Data Type 32-Bit Integer
Range 0 to 8000 seconds
Default 5 seconds
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

Specific to Block(s) Pulse, Maxpulse, Minpulse


Description Pulsewidth in Seconds
Data Type Integer
Range 0 to 8000 seconds
Default 2 seconds
Config Load Yes
Active Loadable No

- 2336 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters
Remarks

18.301 PULSEWIDTH[1..3]

Specific to DevCtl
Block(s)
Description Output Pulsewidth
Data Type 64-Bit Real Number
Range 0.000 to 60.000 seconds
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DO[1..3]NUMDOUTS.
Parameters
Remarks Access is illegal if the index is greater-than NUMDOUTS. Resolution may be entered
in .001 seconds (1 mSec), but is dependent upon the connected DO function block
execution rate.

18.302 PURGEDBCMD

Specific to Block(s) IOLIM, Secondary IOLIM, C300 IOLINK


Description Purge IOLIM/C300 IOLINK Database
Data Type Boolean
Range Off (0): The command is not active. Of (1): The command is active.
Default Off (0)
Config Load No
Active Loadable No
Access Lock Engineer

- 2337 -
Chapter 18 - Pxxxx Parameters

Residence IOLIM, C300 IOLINK


Related Parameters ENCMDS
Remarks Pressing this button will purge the IOLIM's configuration and return
it to the NODB state.Note: This command should only be used when
there is a database mismatch between the ERDB and the IOLIM. A
mismatch exists when an IOP appears in the IOLINK block's “IOP
Status Summary” table but does not appear in the Control Builder
monitoring tree. A mismatch can be caused by:
l Reinitializing the ERDB without first deleting the loaded IOP
blocks from the IOLIM.
l Performing a Force Delete operation from Control Builder on
an IOP or channel block during a loss of communication
between the Server and the IOLIM.
The ‘Purge IOLIM Database’ button is located on the Main tab of
the IOLIM configuration form and is enabled only when Enable
IOLIM Commands (ENCMDS) is set to ON.

WARNING Performing an IOLIM Database Purge will result in a loss of control. All
outputs will transition to their configured safe state.Users should inactivate and delete all
loaded IOP and channel blocks prior to purging the IOLIM database.

18.303 PURGEBUF

Specific to Block(s) EIM


Description Initiate Purge Buffer
Data Type BOOL
Range NA
Default 0
Config Load
Active Loadable No
Access Lock Engineer
Residence NOLOAD
Related Parameters
Remarks

- 2338 -
Chapter 18 - Pxxxx Parameters

18.304 PUSHSP

Specific to Block PID, PID-PL, PIDER, PIDFF, ENHREGCALC, RATIOCTL


(s)
Description Push Set Point (SP) - Enables pushing SP from another block
Data Type Boolean
Range 0 OFF SP will be pulled by secondary
1 ON Secondary block allows SP to be
pushed to it
Default OFF
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks

18.305 PV

Specific to DataAcq
Block(s)
Description Process Variable - Contains the current value of the PV, after it has been selected
from one of the following sources: a field device, another function block, an
operator, or a program.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related PVSOURCE, PVSRCOPT.
Parameters
Remarks A PV change by an operator requires that PVSRCOPT = All, and PVSOURCE = Man. A
PV change by a program requires that PVSRCOPT = All, and PVSOURCE = Sub.

Specific to Block(s) Flag, Push.


Description Actual State - Indicates the current state of the function block.
Data Type Enumeration
Range STATETEXT[0]: PVFL = OFF STATETEXT[1]: PVFL = ON
Default STATETEXT[0]

- 2339 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active Loadable No
Access Lock Defined by ACCLOCK
Residence CEE
Related Parameters PVFL, STATETEXT[0..1].
Remarks

Specific to Numeric
Block(s)
Description Actual State - Indicates the current state of the Numeric function block.
Data Type Real number
Range PVLOLM to PVHILM
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Defined by ACCLOCK
Residence CEE
Related PVLOLM, PVHILM.
Parameters
Remarks For out of range values stored by people (Operator, Engineer, and so on), an error
is returned. For out of range values stored by other function blocks or programs,
the value is clamped to the limit that is exceeded and then stored to PV.

Specific to Block(s) Timer


Description Elapsed Time - Indicates the current elapsed time value of the Timer
function block.
Data Type Integer
Range 0 to 2,147,483,647 (2^31 -1)
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related RV, SO, SP, TIMEBASE
Parameters
Remarks Units are set by TIMEBASE.

Specific to DevCtl
Block(s)
Description Current Active State
Data Type String
Range Length: 12 characters
Default STATETEXT[0]

- 2340 -
Chapter 18 - Pxxxx Parameters

Config No
Load
Active No
Loadable
Access Lock ViewOnly, Operator, Other Function Block (see Remarks)
Residence CEE
Related BADPVALM.FL, BADPVALM.PR, BADPVALM.SV, GPV, GPVAUTO, NUMDINPUTS,
Parameters CMDDISALM.FL, CMDDISALM.PR, NUMSTATES, PVAUTO,
CMDDISALM.SV, CMDDISALM.TM[0..2], PVSOURCE, PVSRCOPT,
CMDFALALM.FL, CMDFALALM.PR, STATETEXT[0..6],
CMDFALALM.SV, CMDFALALM.TM[0..2], UNCMDALM.FL. UNCMDALM.PR,
DIPVMAP[0..15], UNCMDALM.SV.
Remarks Access is illegal if NUMDINPUTS = 0. PV is a String set equal to STATETEXT(GPV).

Access lock is ViewOnly if PVSOURCE = AUTO or TRACK or PVSRCOPT is ONLYAUTO.


Access lock is Operator if PVSOURCE = MAN.
Access lock is Other Function Block if PVSOURCE = SUB.
STATETEXT[6] ['State2'] is illegal if NUMSTATES = 2.

Specific to Block(s) PID, PIDFF, PosProp


Description Process Variable (in Engineering Units)
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PVSTS, PVVALSTS.
Remarks

Specific to Block Totalizer, Pulse Input Totalizer, Deadtime, LeadLag, Genlin, Auxcalc,
(s) RampSoak, SignalSel
Description Function Block Output - The calculated output of an Auxiliary function block.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 2341 -
Chapter 18 - Pxxxx Parameters

Specific to Block(s) Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC
Description Frequency/Rate Value - Engineering Units value corresponding to the rate
of pulses.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PVSTS
Parameters
Remarks PV = C1 / C2 * TIMEBASE * pulses / (frequency integration period)

Specific to AICHANNEL, HAICHANNEL (PM I/O) ; AICHANNEL (Series C I/O)


Block(s)
Description Process Variable (PV). Shows the current value of the converted input signal in
Engineering Units.
Data Type 64-Bit Real Number
Range The Analog Input Channel's PVEXEULO to PVEXEUHI.
Default NaN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks The PV exists in the IOM as a 32-bit floating point value. It is converted to a 64-bit
floating point value for convenience when wiring to other block parameters in
Control Builder (CB).

Specific to Series C PICHANNEL


Block(s)
Description Process Value
Data Type FLOAT64
Range N/A
Default NaN
Config Load No
Active No
Loadable

- 2342 -
Chapter 18 - Pxxxx Parameters

Access Lock Operator


Residence IOM
Related C1C2FREQPERIODPVSTS
Parameters
Remarks PV indicates the frequency value in engineering units corresponding to the rate of
pulses according to the equation: PV = (C1/C2) * TIMEBASE * pulses/frequency
integration period.

Specific to DICHANNEL (PM I/O) DICHANNEL (Series C I/O)


Block(s)
Description Process Variable. Shows the current state of this data point. It is derived from the
open or closed state of field contacts and from the Input Direction parameter
(INPTDIR) configuration.
Data Type Boolean
Range Off On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks Operators can only change PV when the PVSOURCE configuration is MAN.

Specific to Block(s) RATIOCTL


Description Process Variable. Shows actual ratio between X1 and X2 inputs.
Data Type
Range
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PVSTS
Remarks

Specific to Block(s) FLOWCOMP


Description Process Variable. Compensated flow
Data Type
Range
Default NaN
Config Load No
Active Loadable No

- 2343 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence C200, C300, ACE
Related Parameters
Remarks

Specific to CONTACTMON
Block(s)
Description Actual State
Data Type Self-Defining Enumeration
Range STATETEXT[0] STATETEXT[1]
Default STATETEXT[0]
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PVFL STATETEXT[0..1]
Parameters
Remarks PV will be equal to STATETEXT[0] when PVFL = OFF. PV will take the value of
STATETEXT[1] when PVFL = ON

Specific to DIGACQ
Block(s)
Description Actual State
Data Type Self-Defining Enumeration
Range STATETEXT[0]: PVFL = OFF STATETEXT[1]: PVFL = ON
Default OFF
Config NO
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related PVFL STATETEXT[0..1]
Parameters
Remarks A PV change by an operator requires that PVSRCOPT = All, and PVSOURCE = Man. A
PV change by a program requires that PVSRCOPT = All, and PVSOURCE = Sub.
Normally PV will be based on IN when PVSOURCE = Autot; PVSOURCEOPT
=ONLYAUTO.

Specific to Block(s) LEVELCOMP


Description Drum level in Engineer unit
Data Type Float64
Range This is a computed value from PVEULO and PVEUHI.
Default NaN
Config Load NO

- 2344 -
Chapter 18 - Pxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PVEUHIPVEULO
Remarks This is drum level in terms of PVENGUNIT.

Specific to HTMOTOR, LTMOTOR. SOLENOID, VALVEDAMPER


Block(s)
Description Current Actual State
Data Type Self-Defining Enumeration
Range HTMOTOR, LTMOTOR: BAD RUN STOP SOLENOID, VALVEDAMPER: INBET BAD
OPEN CLOSE
Default BAD
Config NO
Load
Active No
Loadable
Access Lock ViewOnly, Operator, Otherfb(see Remarks)
Residence CEE
Related BADPVALM.FL, BADPVALM.PR, BADPVALM.SV, GPV, GPVAUTO, PVAUTO,
Parameters CMDDISALM.FL, CMDDISALM.PR, PVSOURCE, PVSRCOPT,
CMDDISALM.SV, CMDDISALM.TM[0..2], STATETEXT[0..6],
CMDFALALM.FL, CMDFALALM.PR, UNCMDALM.FL,
CMDFALALM.SV, CMDFALALM.TM[0..2], UNCMDALM.PR,
UNCMDALM.SV.
Remarks PV is a String set equal to STATETEXT(GPV).

Access lock is Operator if PVSOURCE = MAN.


Access lock is ViewOnly if PVSOURCE = AUTO or TRACK or PVSRCOPT is ONLYAUTO.
Access lock is Other Function Block if PVSOURCE = SUB.

Specific to Block(s) ROC


Description PV in Eng unit
Data Type Float64
Range
Default NaN
Config Load NO
Active Loadable No
Access Lock Read only
Residence CEE
Related Parameters
Remarks PVP is calculated based PV applied on to the range PVEUHI and PVEULO.

- 2345 -
Chapter 18 - Pxxxx Parameters

18.306 PV[0..numChans-1]

Specific to EIP Analog Input Modules


Block(s)
Description Process value — Provides a numeric value for the device, obtained after performing
scaling on the PVRAW parameter, based on PVRAWLO, PVRAWHI, and
PVSCALEFACTOR parameters.
Data Type Float64
Range

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NoLoad
Related l PVRAWLO
Parameters
l PVRAWHI
l PVSCALEFACTOR
Remarks

18.307 PV[0..7]

Specific to Block(s) Pulse Input IOM


Description Frequency/Rate Value - Engineering Units value corresponding to the rate
of pulses.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PVSTS, PVVALSTS.
Parameters
Remarks

Specific to Block(s) Chassis HART AI IOM, HART AO IOM


Description Process Variable - Shows the PV value for the 8 IOM channels
Data Type Float64
Range
Default

- 2346 -
Chapter 18 - Pxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.308 PV[0..63]

Specific to REQNUMARRAY, RSPNUMARRAY


Block(s)
Description Array of Real values to be read from or written to the third-party device. Stores are
accepted to this parameter only if COMMAND indicates this is a “write” block.
Data Type 64-Bit Real Number
Range
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks

18.309 PV[0..120]

Specific to Block(s) PCDINUMARRCH


Description Process Value
Data Type Float64
Range
Default NaN
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks

- 2347 -
Chapter 18 - Pxxxx Parameters

18.310 PV[1..64]

Specific to SINUMARRCH
Block(s)
Description Process Value, from device - Provides Numeric value form the device.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Determined by ACCLOCK
Residence CEE
Related ERRFL, NNUMERIC
Parameters
Remarks PV[i] provides access to the array of data, one element at a time, by all other
function blocks of the CEE. Initial values can be configured, but these will be
overwritten once good data is imaged from the Serial Interface Module. When
ERRFL is On, an error will be returned on attempted Gets and Stores to this
parameter, to indicate that there is a problem with the array data.

18.311 PV[1..200]

Specific to NUMERICARRAY
Block(s)
Description Numeric Data - Provides access to the Numeric values, one element at a time, for
all other function blocks of the CEE. Initial values can be configured.
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Determined by ACCLOCK
Residence CEE
Related NNUMERIC
Parameters
Remarks

- 2348 -
Chapter 18 - Pxxxx Parameters

18.312 PV[1..NUMCHAN]

Specific to Block(s) HLAI, HLAI_100, STI_MV, DI, DI24, DISOE


Description Process Variable
Data Type 64-bitReal Number
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.313 PV_AI_S

Specific to UIO
Block(s)

Description Process Value


Data Type FLOAT64
Range The AI Channel’s PVEXEULO_AI_C to
PVEXEUHI_AI_C
Default NaN
Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence UIO
Related N/A
Parameters

Remarks This is the converted input signal in engineering units. The PV exists in the UIO as a 32-bit
floating-point value, however it is converted into a 64-bit floating-point value for
convenience when wiring to other XPKS parameters in CB.

Specific to UIO, UAI, AI16-100MS


Block(s)

Description Process Value


Data Type FLOAT64
Range The AI Channel’s PVEXEULO_AI_C to
PVEXEUHI_AI_C

- 2349 -
Chapter 18 - Pxxxx Parameters

Default NaN
Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence IOM Block


Related N/A
Parameters

Remarks This is the converted input signal in engineering units. The PV exists in the UIO and UAI as
a 32-bit floating-point value, however it is converted into a 64-bit floating-point value for
convenience when wiring to other XPKS parameters in CB.

18.314 PVASYNCOPT

Specific to PID-PL
Block(s)
Description Enable Asynchronous PV Measurement - Tells the function block when not to
expect a new PV measurement (that is, when not to expect a change) so that the
function block does not react to obsolete information.
Data Type Enumeration PLPVASYNCOPT
Range CONTINUOUS (0): PV measurement is updated at least
once every execution.
ONPVCHANGE(1): PV measurement is updated when PV
parameter changes.
EXTERNALSYNC(2): PV measurement is updated when an
external flag, connected to
NEWSAMPLE, is set.
Default CONTINUOUS
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related NEWSAMPLE
Parameters
Remarks Many analyzers, such as gas chromatographs, operate at a period longer than the
control execution period. PVASYNCOPT may be set to freeze the current model bias
between analyzer measurement updates. When PVASYNCOPT is EXTERNALSYNC,
the NEWSAMPLE flag must be set to indicate that a new PV value is available. This
block does not alter the value of the NEWSAMPLE parameter; an external block,
such as FTRIG, should be employed for this purpose. This parameter is applicable
only when CTLEQN is set to Profit Loop PKS, and is ignored in PID control
equations.

- 2350 -
Chapter 18 - Pxxxx Parameters

18.315 PVAUTO

Specific to Block(s) DataAcq


Description Filtered and clamped value of the Process Input 1 (P1)
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

Specific to DevCtl
Block(s)
Description State of Actual Inputs
Data Type String
Range Length: 12 characters
Default STATETEXT[0]
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PVAUTO, GPV, GPVAUTO, NUMDINPUTS, NUMSTATES, PV, PVSOURCE, STATETEXT
Parameters [0..6]
Remarks Access is illegal if NUMDINPUTS = 0. PVAUTO is a String set equal to STATETEXT
(GPVAUTO). STATETEXT[6] ['State2'] is illegal if NUMSTATES = 2.

Specific to DIGACQ
Block(s)
Description Field PV
Data Type Boolean
Range
Default OFF
Config Load YES
Active No
Loadable

- 2351 -
Chapter 18 - Pxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related PVFLPVFL
Parameters
Remarks This will be typically connected to a DI Channel. When PVSOURCE is AUTO, this
value will be written on to PVFL

Specific to Block HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


(s)
Description State of Actual Inputs
Data Type Self-Defining Enumeration
Range HTMOTOR, LTMOTOR: BAD RUN STOP SOLENOID, VALVEDAMPER: INBET
BAD OPEN CLOSE
Default BAD
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PVAUTO, GPV, GPVAUTO, PV, PVSOURCE STATETEXT[0..6]
Parameters
Remarks

18.316 PVAUTOFL

Specific to Block(s) DIGACQ


Description Field PV Value
Data Type Boolean
Range OFF, ON
Default OFF(0)
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This is a output parameter and always equal the field PV value

- 2352 -
Chapter 18 - Pxxxx Parameters

18.317 PVAUTOSTS

Specific to DataAcq
Block(s)
Description Status of the filtered and clamped value of the Process Input 1 ( PVAUTO)
Data Type Enumeration PVVALSTS
Range Bad (0): The PVAUTO value was bad, it was replaced with NaN. Uncertn (1): The
status of the PVAUTO value is uncertain. Normal (2): The value is good. Manual (3):
The value was manually stored.
Default Bad (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

18.318 PVBIAS

Specific to PID-PL
Block(s)
Description Bias - The bias added to model predictions.
Data Type Float64
Range
Default 0
Config
Load
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks PVBIAS is the feedback synchronizing internal model predictions with observed
response. Absolute size of the bias is not as important as its volatility. If it
perpetually swings, check for model inaccuracies. The bias should line out at steady
state.

- 2353 -
Chapter 18 - Pxxxx Parameters

18.319 PVCALC

Specific to Block AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


(s)
Description Calculated Process Variable (PV). Shows the value of the PV after the PV
algorithm has calculated it.
Data Type 32-Bit Real Number
Range
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

18.320 PVCHAR

- 2354 -
Chapter 18 - Pxxxx Parameters

Specific to Series C UIO-2 AICHANNEL


Block(s)

Description PV Characterization Option

Data Type ENUM

Exposure OUTPUT

- 2355 -
Chapter 18 - Pxxxx Parameters

Range UIO-2 Module interface to SCA TC/RTD

SENSRTYP X = Allowable Sensor Type

0-5V 1-5V TC RTD -7 to 0 to 500


22mV or or 0 to
-20 to 2000
125mV Ohms

0-Jtherm X

1-Ktherm X

2-Etherm X

3-Ttherm X

4-Btherm X

5-Stherm X

6-Rtherm X

12-Linear X X X X

13-Sqrroot X X

14-NTherm X

26-DeviceRange X

27-SystemRange X

28- X
SystemRangeAndSQRT

29-CTherm X

30-LTherm X

31-PT100 X
(alpha=0.00385)

32-PT200 X
(alpha=0.00385)

33-Ni120 X
(alpha=0.00672)

34-PT50 X
(alpha=0.00391)

35-PT100 X
(alpha=0.00391)

36-Cu50 X
(alpha=0.00426)

37-Cu100 X
(alpha=0.00426)

38-Cu50 X
(alpha=0.00428)

39-Cu100 X
(alpha=0.00428)

Default 12 LINEAR

- 2356 -
Chapter 18 - Pxxxx Parameters

Config Yes
Load

Application Developer

Residence IOM

Related PVEXEULO and PVEXEUHI


Parameters

Remarks This parameter defines the characterization to be used for characterizing the input PV
value. Characterization is based on the field sensor type. Note: ·    DeviceRange provides
the same function as PVCHAR set to Linear but uses the EU range values from the device.
·    SystemRange provides the same function as PVCHAR set to Linear. ·   
SystemRangeAndSQRT provide the same function as PVCHAR set to Sqrroot.

Internal No
Only

- 2357 -
Chapter 18 - Pxxxx Parameters

Specific to Series C AICHANNEL


Block(s)

Description PV Characterization Option

Data Type ENUM

Exposure OUTPUT

Range AI-HART & AI-LLMUX Modules

SENSRTYP X = Allowable Sensor Type

IOM 0.4 to 0-5V 1-5V 0-100


TC RTD
Type 2V mV

0-Jtherm AI-
X
LLMUX

1-Ktherm AI-
X
LLMUX

2-Etherm AI-
X
LLMUX

3-Ttherm AI-
X
LLMUX

4-Btherm AI-
X
LLMUX

5-Stherm AI-
X
LLMUX

6-Rtherm AI-
X
LLMUX

7-RPtherm AI-
X
LLMUX

8-DinRtd AI-
X
LLMUX

9-JisRtd AI-
X
LLMUX

10-NicklRtd AI-
X
LLMUX

11-CopprRtd AI-
X
LLMUX

12-Linear AI- X X X X
HART
AI-
LLMUX

13-Sqrroot AI- X X X
HART

26-DeviceRange AI- X
HART

27-SystemRange AI- X
HART

28-SystemRange AI- X
AndSQRT HART

- 2358 -
Chapter 18 - Pxxxx Parameters

Default 12 LINEAR

Config Yes
Load

Application Developer

Residence IOM

Related PVEXEULO and PVEXEUHI


Parameters

Remarks This parameter defines the characterization to be used for characterizing the input PV
value. Characterization is based on the field sensor type. Note: ·    DeviceRange provides
the same function as PVCHAR set to Linear but uses the EU range values from the
device. ·    SystemRange provides the same function as PVCHAR set to Linear. ·   
SystemRangeAndSQRT provide the same function as PVCHAR set to Sqrroot.

Internal No
Only

Specific to DataAcq
Block(s)
Description PV Characterization Option: Defines the characterization to be used for
characterizing the PI value.
Data Type Enumeration PVCHAR
Range None (0): Do nothing (typically used for RTD and thermocouple
inputs).
Linear (1): 0 to 100 input to P1 is converted to Eus using
configured PVEULO and PVEUH.
SquareRoot (2): Square root of 0 to 100 input to P1 is taken, then this
value is EUs using configured PVEULOand PVEUHI.
Default None (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks A floating point parameter P1EU is used to represent the converted EU value of P1.

Specific to FLOWCOMP
Block(s)
Description PV Characterization Option - Select whether COMPTERM is to be calculated as a
square-root value or not.
Data Type Enumeration PVCHAR
Range None (0)
Square Root (1)
Default Square Root

- 2359 -
Chapter 18 - Pxxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock Application Developer
Residence C200, C300, ACE
Related
Parameters
Remarks
Table 18.1 PV Characterization Range for PM IOM Types HLAI, HLAIHART, LLAI, LLMUX, and
RHMUX
Specific to AICHANNEL, HAICHANNEL (PM I/O)
Block(s)
Description Process Variable (PV) Characterization Option. Defines the display characterization
option to be used for characterizing the input PV value.
Data Type Enumeration
Range See Table 1: For IOM (also known as IOP) types HLAI, HLAIHART, LLAI, LLMUX,
and RHMUX. See Table 2 and Table 3: For IOM (also known as IOP) type STI.
Default 12-Linear for LLAI, HLAI, HLAIHART, and STIMV 0 - Jtherm for LLMUX and
RHMUX
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOM
Related PVEXEULO, PVEXEUHI
Parameters
Remarks

All Thermocouple and RTD types are not supported for IOM type HLAI.

- 2360 -
Chapter 18 - Pxxxx Parameters

Table 18.2 PV Characterization Range for PM IOM Type STI - ST3000 Pressure Transmitters and
MagneW 3000 Flowmeters
Range IOP X = Allowable Sensor Type (SENSTYPE) Valid Normal Valid Extended
TYPE Range (PVEULO- Range (PVEULO-
(See PVEUHI) In PVEUHI) In
Note Degrees C Degrees C (When
1) (When TCRNGOPT =
TCRNGOPT = Extended for
Normal for SENSTYPE =
SENSTYPE = THERMCPL
THERMCPL
0.4 to 2V 0 to 1 0 to THERMCPL SLIDEWIRE RTD
5V to 100
5V MV

0-Jtherm HLAI X X X -200 to 1200 N/A

LLAI X -100 to 750 -200 to 1200

MUX X -100 to 750 -200 to 1200

1- HLAI X X X -100 to 1370 N/A


Ktherm
LLAI X 0 to 1100 -100 to 1370

MUX X 0 to 1100 -100 to 1370

2- HLAI X X X -100 to 1370 N/A


Ntherm
LLAI X 0 to 1100 -100 to 1370
MUX X 0 to 1100 -100 to 1370
3- HLAI X X X -200 to 1000 N/A
Etherm
LLAI X -150 to 500 -200 to 1000

MUX X -150 to 500 -200 to 1000

4- HLAI X X X -230 to 400 N/A


Ttherm
LLAI X -200 to 300 -230 to 400

MUX X -200 to 300 -230 to 400

5- HLAI X X X 100 to 1820 N/A


Btherm
LLAI X 600 to 1650 100 to 1820

MUX X 600 to 1650 100 to 1820

6- HLAI X X X 0 to 1700 N/A


Stherm

- 2361 -
Chapter 18 - Pxxxx Parameters

Range IOP X = Allowable Sensor Type (SENSTYPE) Valid Normal Valid Extended
TYPE Range (PVEULO- Range (PVEULO-
(See PVEUHI) In PVEUHI) In
Note Degrees C Degrees C (When
1) (When TCRNGOPT =
TCRNGOPT = Extended for
Normal for SENSTYPE =
SENSTYPE = THERMCPL
THERMCPL
0.4 to 2V 0 to 1 0 to THERMCPL SLIDEWIRE RTD
5V to 100
5V MV

LLAI X 550 to 1500 0 to 1700

MUX X 550 to 1500 0 to 1700

7- HLAI X X X 0 to 1700 N/A


Rtherm
LLAI X 550 to 1500 0 to 1700

MUX X 550 to 1500 0 to 1700

8- HLAI X X X 0 to 1770 N/A


RPtherm
LLAI X 550 to 1500 0 to 1770

MUX X 550 to 1500 0 to 1770

9-DinRtd HLAI X X X -180 to 800 N/A

LLAI X -180 to 800 N/A

MUX X -180 to 800 N/A

10-JisRtd HLAI X X X -180 to 650 N/A

LLAI X -180 to 650 N/A

MUX X -180 to 650 N/A

11- HLAI X X X -45 to 315 N/A


NicklRtd
LLAI X -45 to 315 N/A

MUX X -45 to 315 N/A

12- HLAI X X X -20 to 250 N/A


CopprRtd
LLAI X -20 to 250 N/A

- 2362 -
Chapter 18 - Pxxxx Parameters

Range IOP X = Allowable Sensor Type (SENSTYPE) Valid Normal Valid Extended
TYPE Range (PVEULO- Range (PVEULO-
(See PVEUHI) In PVEUHI) In
Note Degrees C Degrees C (When
1) (When TCRNGOPT =
TCRNGOPT = Extended for
Normal for SENSTYPE =
SENSTYPE = THERMCPL
THERMCPL
0.4 to 2V 0 to 1 0 to THERMCPL SLIDEWIRE RTD
5V to 100
5V MV

MUX X -20 to 250 N/A

13- HLAI X X X X N/A N/A


Linear Only
LLAI X X X N/A N/A

MUX X N/A N/A

14- HLAI X X X N/A N/A


Sqrroot
LLAI X X N/A N/A

Notes:
1. MUX = LLMUX and RHMUX
2. HLAI = HLAI AND HLAIHART
3. N/A = Not Applicable

Table 18.3 PV Characterization Range for PM IOM Type STI - STT3000 Temperature Transmitters
(SENSRTYP = STT)
Range X = Allowable Sensor Type (SENSRTYP)
SPT_DP SPT_GP SPT_AP SFM

12-Linear X X X X
13-Ssqrroot X

Range Normal Range (PVEULO to PVEUHI) In Maximum Range (PVEXEULO to PVEXEUHI)


Degrees C (Except Where Noted) In Degrees C (Except Where Noted)
Linear
-50 to 220 mV -1000 to 1000 mV
Thermocouples
0-Jtherm -180 to 1200 -200 to 1200
1-Ktherm -170 to 1250 -200 to 1370
2-Etherm -100 to 1000 -200 to 1000
3-Ttherm -120 to 400 -250 to 400
4-Btherm 400 to 1820 200 to 1820

- 2363 -
Chapter 18 - Pxxxx Parameters

Range Normal Range (PVEULO to PVEUHI) In Maximum Range (PVEXEULO to PVEXEUHI)


Degrees C (Except Where Noted) In Degrees C (Except Where Noted)
5-Stherm 0 to 1760 -50 to 1760
6-Rtherm 0 to 1760 -50 to 1760
14- -100 to 1300 -200 to 1300
Ntherm
20- 0 to 2300 0 to 2300
W5W26TC

21- 0 to 2300 0 to 2300


W3W25TC

22- 600 to 1300 600 to 1300


NiNiMoTC
RTDs
8-Pt100 -200 to 450 -200 to 850
DinRtd
9-Pt100 -200 to 450 -200 to 640
JisRtd
15-Pt200 -200 to 450 -200 to 850
RTD
16-Pt500 -200 to 450 -200 to 850
RTD
17-Cu10 -20 to 250 -20 to 250
RTD
18-Cu25 -20 to 250 -20 to 250
RTD
19-RH 420 to 1800 700 to 1800
Rad
23-RTD 0 to 4000 ohms 0 to 4000 ohms
Ohms

Specific to Series C I/O AICHANNEL


Block(s)
Description PV Characterization Option
Data Type Enumeration
Range See Table 8 for Series C IOM types AI-HART, AI-LLAI, and AI-LLMUX
Default Linear (12)
Config Load Yes
Active No
Loadable

- 2364 -
Chapter 18 - Pxxxx Parameters

Access Lock Application Developer


Residence IOM
Related PVEXEULO, PVEXEUHI
Parameters
Remarks This parameter defines the characterization to be used for characterizing the input
PV value. Characterization is based on the field sensor type.

NOTE The following table lists the PV Characterization Range for Series
C IOM Types AI-HART, AI_LLAI, and AI-LLMUX for emulated HG boxes.

Table 18.4 Table 4. PV Characterization Range for Series C IOM Types AI-HART , AI_LLAI, and AI-
LLMUX
Range IOM X = Allowable Sensor Type Valid Normal Valid Extended
TYPE (SENSTYPE) Range Range
(See (PVEULO- (PVEULO-
Notes) PVEUHI) In PVEUHI) In
Degrees C Degrees C
(When (When
TCRNGOPT = TCRNGOPT =
Normal for Extended for
SENSTYPE = SENSTYPE =
THERMCPL THERMCPL
0.4 to 2V 0 to 5V 1 0 to THERMCPL RTD
to 100
5V MV

0-Jtherm LLMUX X -100 to 750 - -200 to 1200 -


LLAI 100 to 750 200 to 1200
1-Ktherm LLMUX X 0 to 1100 0 to -100 to 1370 -
LLAI 1100 100 to 1370
2-Etherm LLMUX X -150 to 500 - -200 to 1000 -
LLAI 150 to 500 200 to 1000
3-Ttherm LLMUX X -200 to 300 - -230 to 400 -
LLAI 200 to 300 230 to 400
4-Btherm LLMUX X 600 to 1650 100 to 1820
LLAI 600 to 1650 100 to 1820
5-Stherm LLMUX X 550 to 1500 0 to 1700 0 to
LLAI 550 to 1500 1700
6-Rtherm LLMUX X 550 to 1500 0 to 1700 0 to
LLAI 550 to 1500 1700
7-RPtherm LLMUX X 550 to 1500 0 to 1770 0 to
LLAI 550 to 1500 1770
8-DinRtd LLMUX X -180 to 800 -
LLAI 200 to 850
9-JisRtd LLMUX X -180 to 650 -
LLAI 200 to 650
10-NicklRtd LLMUX X -45 to 315 -45
LLAI to 315
11-CopprRtd LLMUX X -20 to 250 -20

- 2365 -
Chapter 18 - Pxxxx Parameters

Range IOM X = Allowable Sensor Type Valid Normal Valid Extended


TYPE (SENSTYPE) Range Range
(See (PVEULO- (PVEULO-
Notes) PVEUHI) In PVEUHI) In
Degrees C Degrees C
(When (When
TCRNGOPT = TCRNGOPT =
Normal for Extended for
SENSTYPE = SENSTYPE =
THERMCPL THERMCPL
0.4 to 2V 0 to 5V 1 0 to THERMCPL RTD
to 100
5V MV

LLAI to 250
CU50Rtd LLAI X -50 to +150

12-Linear HART X X
LLMUX X X

13-Sqrroot HART X X X
LLMUX X

26-DeviceRange HART X
27-SystemRange X
28- X
SystemRangeAndSQRT

Notes:
l LLMUX = AI-LLMUX
l LLAI = AI_LLAI
l HART = AI-HART

18.321 PVCHGDLY

Specific to Series C DI CHANNEL


Block(s)
Description Process Variable (PV) Change Delay Time. Specifies the time in seconds that a point
with a previously detected PV change event is guaranteed to remain at the new
value even if the PV returns to its original value.
Data Type 8-Bit Unsigned Integer
Range 0 to 60 seconds
Default 0 seconds
Config Load Yes
Active No
Loadable

- 2366 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence IOM
Related
Parameters
Remarks This parameter is only exposed when the ASSOCIOPTYP is DISOE IOM and the
EVTOPT configuration is not NONE. If the point remains at its new PV value when
the delay timer expires, the point is held at the new value.

Specific to UIO-DI channel


Block(s)
Description Process Variable (PV) Change Delay Time.
Data Type UINT8
Range 0 to 60 seconds
Default 0 seconds
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence IOM
Related
Parameters
Remarks This parameter specifies the time in seconds that a point with a previously detected
PV change event is guaranteed to remain at the new value even if the PV returns to
its original value. If the point remains at its new value when the delay timer expires,
the point is held at the new value.

18.322 PVCLAMP

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable Clamping Option. Specifies whether or not PV clamping action is to
be used with this data point.
Data Type Enumeration
Range 0 NOCLAMP No clamping of the PV
value.
1 CLAMP Clamp PV value at the
extended range limit.
Default NOCLAMP (0)
Config Load Yes
Active No
Loadable

- 2367 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer/Application Developer


Residence IOM
Related
Parameters
Remarks If PVCLAMP is set to CLAMP and PV extended range limit is exceeded, PV status
(PVSTS) is marked Uncertain and the PV is set equal to the extended limit that was
violated.

18.323 PVCONN

Specific to Block(s) PID, PIDFF, PosProp, RampSoak


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

18.324 PVEM

Specific to Block(s) HRBALG_HLPIUAI, HRBALG_HLPIUAC, HRBALG_HLPIUDI, HRBALG_


HLPIUDC
Description PV val in EUs
Data Type FLOAT64
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related –
Parameters
Remarks It is analog.

- 2368 -
Chapter 18 - Pxxxx Parameters

18.325 PVENGUNIT

Specific to Block(s) LEVELCOMP


Description Process Variable (PV) Engineering unit selector
Data Type Enumeration
Range Meter, mm,cm, inch
Default mm
Config Load YES
Active Loadable No
Access Lock App Dev
Residence CEE
Related Parameters PV
Remarks Engineering unit conversion on PV is applied based on this parameter.

18.326 PVEQN

Specific to Totalizer, Pulse Input Totalizer, FLOWCOMP


Block(s)
Description Process Variable (PV) Equation Type - Defines
the equation (EqA, EqB, ...) to be used with a
given function block.
Data Type Enumeration PVEQN
Range Equation: Bad Input Warm Restart
Handling: Handling:

EqA (0) Stop Continue


accumulation after input
while input is bad turns valid
EqB (1) Use last good Continue
value if input is after input
bad turns valid
EqC (2) Stop if the input is Continue
bad and set PV to after input
NaN turns valid
EqD (3) Stop Stop after a
accumulation warm restart
while input is bad
EqE (4) Use last good Stop after a
value if input is warm restart
bad
EqF (5) Stop if the input is Stop after a
bad and set PV to warm restart
NaN
Default EqA (0)
Config Load Yes
Active No

- 2369 -
Chapter 18 - Pxxxx Parameters

Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

18.327 PVERSION

Specific to Block(s) SR
Description Platform Version. Identifies the major revision of the RM.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.328 PVEUHI

Specific to DataAcq, PID, PIDFF, PosProp, RampSoak.


Block(s)
Description Process Variable (PV) High Range (in Engineering Units) - This value
corresponds to 100% of full scale.
Data Type Real
Range Greater-than PVEULO and less-than or equal to PVEXHILM.
Default 100.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

- 2370 -
Chapter 18 - Pxxxx Parameters

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable Engineering Units High. Specifies the high range PV value in
Engineering Units.
Data Type 32-Bit Real Number
Range PVEULO to PVEXEUHI, NaN
Default 100.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence IOM
Related
Parameters
Remarks Note that PVEUHI cannot be written with Not a Number (NaN). NaN is the
default power up value only.

Specific to Block(s) ROC


Description Engineering Unit High
Data Type Float64
Range
Default 100
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters PVEULO
Remarks This parameter should be more than PVEULO.

Specific to Block(s) LEVELCOMP


Description Process Value High Range
Data Type Float64
Range
Default 300
Config Load YES
Active Loadable No
Access Lock Engineer when CM is Inactive
Residence CEE
Related Parameters PVPVENGUNITPVEULO
Remarks This parameter value should be more than PVEULO.

- 2371 -
Chapter 18 - Pxxxx Parameters

18.329 PVEUHI[0..120]

Specific to Block(s) PCDINUMARRCH


Description Process Value High Range
Data Type Float64
Range PVEUHI must be greater than PVEULO
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks Set the PVEUHI limit for the device index.

18.330 PVEUHI_AI_C

Specific to UIO
Block(s)

Description Process Value


Data Type BOOLEAN
Range
0

Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence UIO
Related N/A
Parameters

Remarks This parameter indicates the current state of this data point. It is derived from the
open or closed state of field contacts and from the configured input direction
[INPTDIR].

Specific to UIO, UAI, AI16-100MS


Block(s)

Description PV High Range


Data Type FLOAT32
Range PVEULO_AI_C to PVEXEUHI_AI_C, NaN
Default 100.0

- 2372 -
Chapter 18 - Pxxxx Parameters

Config Load Yes


Active Loadable

Access Lock Application Developer Only


Residence IOM Block
Related This value is in Engineering Units. Note that PVEUHI_AI_C cannot be written with
Parameters NaN. NaN is the default power up value only.
Remarks This parameter indicates the current state of this data point. It is derived from the
open or closed state of field contacts and from the configured input direction
[INPTDIR].

18.331 PVEULO

Specific to Block DataAcq, PID, PIDFF, PosProp, RampSoak


(s)
Description Process Variable (PV) Low Range (in Engineering Units) - This value
corresponds to 0% of full scale.
Data Type Real
Range Less-than PVEUHI and Greater-than or equal to PVEXLOLM.
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable Engineering Units Low. Specifies the low range PV value in
Engineering Units.
Data Type 32-Bit Real Number
Range PVEXEULO to PVEUHI, NaN
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence IOM
Related
Parameters
Remarks Note that PVEULO cannot be written with Not a Number (NaN). NaN is the
default power up value only.

- 2373 -
Chapter 18 - Pxxxx Parameters

Specific to Block(s) ROC


Description Engineering Unit Low
Data Type Float64
Range
Default 0
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters PVEUHI
Remarks This parameter should be less than PVEUHI.

Specific to Block(s) LEVELCOMP


Description Process Value Low range
Data Type Float64
Range
Default -300
Config Load YES
Active Loadable No
Access Lock Engineer when CM is Inactive
Residence CEE
Related Parameters PVPVENGUNITPVEUHI
Remarks This parameter value should be less than PVEUHI

18.332 PVEULO[0..120]

Specific to Block(s) PCDINUMARRCH


Description Process Value Low Range
Data Type Float64
Range PVEULO must be less than PVEUHI
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks Set the PVEULO limit for the device index.

- 2374 -
Chapter 18 - Pxxxx Parameters

18.333 PVEULO_AI_C

Specific to Block(s) UIO


Description PV Low Range
Data Type FLOAT32
Range PVEXEULO_AI_C to PVEUHI_AI_C
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence UIO
Related Parameters N/A
Remarks This value is in Engineering Units.

Specific to Block(s) UIO, UAI, AI16-100MS


Description PV Low Range
Data Type FLOAT32
Range PVEXEULO_AI_C to PVEUHI_AI_C
Default 0.0
Config Load Yes
Active Loadable

Access Lock Application Developer Only


Residence IOM Block
Related Parameters N/A
Remarks This value is in Engineering Units

18.334 PVEXEUHI

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable Extended High Range. Specifies the extended high range PV value
in Engineering Units.
Data Type 32-Bit Real Number
Range Greater than or equal to PVEUHI
Default 102.9 (See PVEXEULO parameter)
Config Yes
Load
Active No
Loadable

- 2375 -
Chapter 18 - Pxxxx Parameters

Access Lock LLAI IOM with Thermocouple and RTD sensor types: ViewOnly All others: Engineer
Residence IOM
Related PVEXEULO
Parameters
Remarks For PM I/O, this parameter is only exposed when the ASSOCIOPTYP is HLAI or STI-
MV. It cannot be written with Not a Number (NaN). NaN is the default power up
value only. Both PVEXEUHI and PVEXEULO are used to clamp or detect a bad PV
value.

18.335 PVEXEUHI_AI_C

Specific to Block(s) UIO


Description PV Extended High Range
Data Type FLOAT32
Range >= PVEUHI, NaN
Default 102.9 (Refer to parameter PVEXEULO_AI_C)
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence UIO
Related Parameters PVEXEULO
Remarks Refer to parameter PVEXEULO_AI_C.

Specific to Block(s) UIO, AI16-100MS


Description PV Extended High Range
Data Type FLOAT32
Range >= PVEUHI, NaN
Default 102.9 (Refer to parameter PVEXEULO_AI_C)
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence IOM Block
Related Parameters PVEXEULO
Remarks Refer to parameter PVEXEULO_AI_C.

- 2376 -
Chapter 18 - Pxxxx Parameters

18.336 PVEXEULO

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable Extended Low Range. Specifies the extended low PV range in
Engineering Units.
Data Type 32-Bit Real Number
Range Less than or equal to PVEULO
Default See Table 9: For SENSRTYP equals THERMCPL and PVTEMP equals Degrees C.
Valid for IOPTYPE = RHMUX, LLMUX, or LLAI. See Table 10: For SENSRTYP equals
RTD and PVTEMP equals Degrees C. Valid for IOPTYPE = RHMUX, LLMUX, or LLAI.
READ/WRITE defaults when SENSRTYP = 0-100 mV OR (SENSRTYP = 0-5 V or 1-5V )
and (IOPTYPE = LLAI) and (PVCHAR = Linear or Sqrroot) OR SENSRTYP = STT
(IOPTYPE = STIMV by default) OR IOPTYPE = HLAI, HLAIHART s for PVEXEULO and
PVEXEUHI are -2.9 and 102.9. Limit error checking and range overlap error
checking for PVEXEULO and PVEXEUHI are performed by the IOM. The unit of
measure is engineering units
Config Yes
Load
Active No
Loadable
Access Lock When SENSRTYP = THERMCPL or RTD, access lock is ViewOnly All others: Engineer

Residence IOM
Related PVEXEUHI, PVTEMP, TCRNGOPT, SENSRTYP.
Parameters
Remarks For PM I/O, this parameter is only exposed when the ASSOCIOPTYP is HLAI or STI-
MV. It cannot be written with Not a Number (NaN). NaN is the default power up
value only. Both PVEXEUHI and PVEXEULO are used to clamp or detect a bad PV
value. These parameters cannot be set to NaN.
Table 18.5 Extended Range Parameter Defaults when SENSRTYP equals THERMCPL and PVTEMP
equals degrees C
PVCHAR TCRNGOPT = NORMAL TCRNGOPT = EXTENDED
PVEXEULO PVEXEUHI PVEXEULO PVEXEUHI
Btherm 600 1650 100 1820
Etherm -150 500 -200 1000
Jtherm -100 750 -200 1200
Ktherm 0 1100 -100 1370
Rtherm 550 1500 0 1700
RPtherm 550 1500 0 1770
Stherm 550 1500 0 1700
Ttherm -200 300 -230 400

- 2377 -
Chapter 18 - Pxxxx Parameters

Table 18.6 Extended Range Parameter Defaults when SENSRTYP equals RTD and PVTEMP equals
degrees C
PVCHAR PVEXEULO PVEXEUHI

DinRTD -200 850


JisRTD -200 650
NicklRTD -45 315
CopprRTD -20 250
Note:
l The parameter TCRNGOPT is not exposed
l In the Monitoring view, the above values are displayed. In the Project view, NaN
is displayed for these values.

18.337 PVEXEULO_AI_C

Specific to UIO
Block(s)

Description PV Extended Low Range


Data Type FLOAT32
Range
1 to 5 Volts or 4mA to 20mA

0 to 5 Volts or 0mA to 20mA

Default -2.9 - The unit of measure is engineering units.


Limit error checking and range overlap error checking for PVEXEULO_AI_C and
PVEXEUHI_AI_C are performed by the system.
Config Load Yes
Active No
Loadable

Access Lock Application Developer Only


Residence UIO
Related HENABLE_AI_C
Parameters

Remarks PVEXEUHI_AI_C and PVEXEULO_AI_C are used to clamp or detect a bad PV value.

Specific to UIO, AI16-100MS


Block(s)

Description PV Extended Low Range


Data Type FLOAT32
Range <= PVEULO_AI_C
Default -2.9 - The unit of measure is engineering units.
Limit error checking and range overlap error checking for PVEXEULO_AI_C and
PVEXEUHI_AI_C are performed by the system.

- 2378 -
Chapter 18 - Pxxxx Parameters

Config Load Yes


Active No
Loadable

Access Lock Application Developer Only


Residence IOM Block
Related PVEXEUHI_AI_C
Parameters

Remarks PVEXEUHI_AI_C and PVEXEULO_AI_C are used to clamp or detect a bad PV value

18.338 PVEXHIFL

Specific to Block(s) DataAcq


Description Process Variable (PV) High Limit Flag - Indicates if PV has exceeded its high
limit.
Data Type Boolean
Range Off (0): PVs high limit is not exceeded. On (1): PVs high limit is exceeded.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable (PV) Extended High Range Flag. Shows if the PV has exceeded
the extended high range trip point.
Data Type Boolean
Range Off: Extended high range limit not exceeded On: Extended high range limit
exceeded
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks

- 2379 -
Chapter 18 - Pxxxx Parameters

18.339 PVEXHILM

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Limit (in Engineering Units) - Used to detect and clamp
a bad Process Variable (PV) value.
Data Type 64-Bit Real Number
Range Greater-than or equal to PVEUHI.
Default 102.9
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

18.340 PVEXLOFL

Specific to Block(s) DataAcq


Description Process Variable (PV) Low Limit Flag - Indicates if PV has exceeded its low
limit.
Data Type Boolean
Range Off (0): PV low limit not exceeded. On (1): PV low limit exceeded.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable (PV) Extended Low Range Flag. Shows if the PV has exceeded
the extended low range trip point.
Data Type Boolean
Range Off: Extended low range limit not exceeded. On: Extended low range limit
exceeded.
Default Off
Config Load No

- 2380 -
Chapter 18 - Pxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks

18.341 PVEXLOLM

Specific to Block DataAcq


(s)
Description Process Variable (PV) Low Limit (in Engineering Units) - Used to detect and
clamp a bad PV value.
Data Type 64-Bit Real Number
Range Less than or equal to PVEULO
Default -2.9
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks

18.342 PVFL

Specific to Block(s) Flag, Push


Description Actual State Flag - Indicates the current state of the Flag function block as a
Boolean.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Defined by ACCLOCK
Residence CEE
Related PV, STATE0, STATE1, STATETEXT[0..1].
Parameters
Remarks

- 2381 -
Chapter 18 - Pxxxx Parameters

Specific to Block(s) DIC


Description Process Value Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.343 PVFL[0..numChans-1]

Specific to Block(s) EIP Digital Input modules


Description Process Value from device— Provides a Boolean value from the device.
Data Type BOOLEAN
Range l Off (0)
l On (1)
Default off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters None
Remarks It is indexed by channel number.

18.344 PVFL[0..2]

Specific to Block(s) DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Process Variable (PV) State Flags - PVFL(x) is On when PV = StateX.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No

- 2382 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters GPV, PV. DEVCTL Only: DIMODEDIPVMAP[0..15]NUMDINPUTS,
NUMSTATES
Remarks DEVCTL Only:
l Access is illegal if NUMDINPUTS = 0.
l PVFL[2] is illegal if NUMSTATES =2.

Specific to Block(s) DIGACQ


Description Actual State Flag
Data Type Boolean
Range OFF (0) ON (1)
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PV, STATE0, STATE1, STATETEXT[0..1].
Remarks The PVFL changes based on selected PVSRCOPT and PVSOURCE.

Specific to Block(s) CONTACTMON


Description Actual State Flag
Data Type Boolean
Range OFF (0) ON (1)
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PV, STATE0, STATE1, STATETEXT[0..1].
Remarks

18.345 PVFL[0..511]

Specific to REQFLAGARRAY, RSPFLAGARRAY


Block(s)
Description Array of Boolean values to be read from or written to the third-party device. Stores
are accepted to this parameter only if the COMMAND indicates that this is a “write”
block.
Data Type Boolean
Range Off (0) On (1)

- 2383 -
Chapter 18 - Pxxxx Parameters

Default Off (0)


Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks

18.346 PVFL[1..512]

Specific to SIFLAGARRCH
Block(s)
Description Process Value, from device - Provides Boolean value from the device.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Yes
Load
Active No
Loadable
Access Lock Determined by ACCLOCK
Residence CEE
Related ERRFL, NEXTPHASE, NFLAG.
Parameters
Remarks PVFL[i] provides access to the array of data, one element at a time, by all other
function blocks of the CEE. Initial values can be configured, but these will be
overwritten once good data is imaged from the Serial Interface Module. When
ERRFL is On, an error will be returned on attempted Gets and Stores to this
parameter, to indicate that there is a problem with the array data.

18.347 PVFL[1..1000]

Specific to FLAGARRAY
Block(s)
Description Flag Data - Provides access to the Boolean values, one element at a time, for all
other function blocks of the CEE. Initial values can be configured.
Data Type Boolean
Range Off(0) On(1)
Default Off(0)
Config Load Yes

- 2384 -
Chapter 18 - Pxxxx Parameters

Active No
Loadable
Access Lock Determined by ACCLOCK
Residence CEE
Related NEXTPHASE, NFLAG.
Parameters
Remarks

18.348 PVFL[1..1968]

Specific to Block(s) PCDIFLAGARRCH


Description Process Value, from device
Data Type Boolean
Range Off(0) On(1)
Default Off(0)
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters NFLAG.
Remarks

18.349 PVFL_DI_S

Specific to UIO
Block(s)

Description Process Value


Data Type BOOLEAN
Range
0 Off

1 On

Default Off
Config Load No
Active Loadable No

- 2385 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence UIO
Related N/A
Parameters

Remarks This parameter indicates the current state of this data point. It is derived from the
open or closed state of field contacts and from the configured input direction
[INPTDIR].

Specific to UIO, DI32-24VDC, DI16-VAC, DI16-DRYCT, DI16-VACDC


Block(s)

Description Process Value


Data Type BOOLEAN
Range
0 Off

1 On

Default Off
Config Load No
Active Loadable

Access Lock ViewOnly


Residence IOM Block
Related
Parameters

Remarks This parameter indicates the current state of this data point. It is derived from the
open or closed state of field contacts and from the configured input direction
[INPTDIR].

18.350 PVFORMAT

Specific to DataAcq, Numeric, PID, PIDFF, PosProp, Auxcalc, Genlin, Totalizer, LeadLag,
Block(s) Deadtime, Pulse Input Totalizer, NUMERICARRAY, AUXSUMMER, FLOWCOMP,
SignalSel
Description Process Variable (PV) Display Format - Defines the decimal format that is to be used
to display the PV value. It contains up to eight characters, including the minus sign
and decimal point.
Data Type Enumeration PVFORMAT
Range D0 (-XXXXXX.) D1 (-XXXXX.X) D2 (-XXXX.XX) D3 (XXX.XXX)
Default D1 (-XXXXX.X)
Config Load Yes
Active No
Loadable

- 2386 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence C200, C300, ACE
Related PV, SP.
Parameters
Remarks

18.351 PVHHALM.DB

Specific to DataAcq
Block(s)
Description Process Variable (PV) High High Alarm Deadband
Data Type 64-Bit Real Number
Range 0.0 to 100.0 if alarm deadband units (PVHHALM.DBU) are Percent. PVEULO to
PVEUHI if alarm deadband units (PVHHALM.DBU) are Engineering Units.
Default 0.0
Config No
Load
Active No
Loadable
Access EngineerAppDev
Lock
Residence CEE
Related PV, PVHHALM.DBU, PVHHALM.FL, PVHHALM.PR, PVHHALM.SV, PVHHALM.TM,
Parameters PVHHALM.TP.
Remarks The following rule is applied to PVHHALM.DB to prevent overlap between PV alarm
trip point values to avoid multiple alarms: PVHHALM.DB <= (PVHHALM.TP -
PVHIALM.TP + PVHIALM.DB) The following rule is applied to PVHHALM.DB to
prevent PVHH and PVLL alarm that are both active at the same time: PVHHALM.DB
<= (PVHHALM.TP - PVLLALM.TP)/2 (or PVLLALM.TP <= PVHHALM.TP -
(2*PVLLALM.DB)) For more information about alarm configuration, refer to Control
Builder Components Theory Guide.

18.352 PVHHALM.DBU

Specific to DataAcq
Block(s)
Description PV High High Alarm Deadband Units - Indicates if PVHIALM.DB is in Percent or
Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU (1)
Default Percent (0)
Config Load No
Active No
Loadable

- 2387 -
Chapter 18 - Pxxxx Parameters

Access Lock EngineerAppDev


Residence CEE
Related PV, PVHHALM.DB, PVHHALM.FL, PVHHALM.PR, PVHHALM.SV, PVHHALM.TM,
Parameters PVHHALM.TP.
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,. Alarm processing

18.353 PVHHALM.FL

Specific to DataAcq
Block(s)
Description Process Variable (PV) High High Alarm Flag
Data Type Boolean
Range Off (0): PV High High alarm is not active; PV is less than PVHHALM.TP On (1): PV
High High alarm is active; PV is greater than or equal to PVHHALM.TP
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.354 PVHHALM.PR

Specific to DataAcq
Block(s)
Description Process Variable (PV) High High Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable

- 2388 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.355 PVHHALM.SV

Specific to DataAcq
Block(s)
Description Process Variable (PV) High High Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder
Components Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.356 PVHHALM.TM

Specific to DataAcq
Block(s)
Description Process Variable (PV) High High Alarm Filter Time (Seconds) - The purpose of this
parameter is to prevent input spikes from causing PV High High alarms. An alarm
will only be generated if PV consistently exceeds the High High alarm trip point for
more than the configured alarm filter time.
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0
Config No
Load
Active No
Loadable

- 2389 -
Chapter 18 - Pxxxx Parameters

Access Lock EngineerAppDev


Residence CEE
Related PV, PVHHALM.DB, PVHHALM.DBU, PVHHALM.FL, PVHHALM.PR, PVHHALM.SV,
Parameters PVHHALM.TP.
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.357 PVHHALM.TMO

Specific to Block(s) DataAcq block


Description Process Variable (PV) High High Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related Parameters
Remarks To configure off-delay time for Process Variable (PV) High High Alarm.

18.358 PVHHALM.TP

Specific to DataAcq
Block(s)
Description Process Variable (PV) High High Alarm Trip Point - Defines the trip point for a PV
High High alarm.
Data Type 64-Bit Real Number
Range NaN or PVHIALM.TP to PVEUHI.
Default NaN
Config Yes
Load
Active No
Loadable

- 2390 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks The following rule is applied to PVHHALM.TP to prevent PVHH and PVLL alarm that
are both active at the same time. PVLOALM.TP <= PVHHALM.TP – (2 PVLLALM.DB)
(or PVHHALM.DB <= (PVHHALM.TP - PVLLALM.TP)/2 ) For more information on
DataAcq alarming, refer to the Control Builder Components Theory, DATAACQ (Data
Acquisition) Block,.Alarm processing.

18.359 PVHIALM.DB

Specific to DataAcq
Block(s)
Description Process Variable (PV) High Alarm Deadband
Data Type 64-Bit Real Number
Range 0.0 to 100.0: If alarm deadband units (PVHIALM.DBU) are Percent. PVEULO to
PVEUHI, If alarm deadband units (PVHIALM.DBU) are Engineering Units.
Default 0.0
Config No
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related PV, PVHIALM.DBU, PVHIALM.FL, PVHIALM.PR, PVHIALM.SV, PVHIALM.TM,
Parameters PVHIALM.TP.
Remarks The following rule is applied to PVHIALM.DB to prevent PVHI and PVLO alarm that
are both active at the same time: PVHIALM.DB <= (PVHIALM.TP - PVLOALM.TP)/2
(or PVLOALM.TP <= PVHIALM.TP - (2*PVLOALM.DB)) For more information about
alarm configuration, refer to Control Builder Components Theory Guide.

18.360 PVHIALM.DBU

Specific to DataAcq
Block(s)
Description Process Variable (PV) High Alarm Deadband Units - Indicates if PVHIALM.DB is in
Percent or Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU (1)
Default Percent (0)
Config No
Load
Active No

- 2391 -
Chapter 18 - Pxxxx Parameters

Loadable
Access Lock EngineerAppDev
Residence CEE
Related PV, PVHIALM.DB, PVHIALM.FL, PVHIALM.PR, PVHIALM.SV, PVHIALM.TM,
Parameters PVHIALM.TP.
Remarks You can configure the individual deadband units for the Process Variable (PV) High
Alarm. Hence, the individual deadband unit is assigned to the PVHIALM when the
block is loaded to the CEE. However, this is applicable only for the DATAACQ block.
For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.361 PVHIALM.FL

Specific to DataAcq
Block(s)
Description Process Variable (PV) High Alarm Flag - Indicates if a PV High alarm has been
issued.
Data Type Boolean
Range Off (0): PV High alarm is not active; PV is less than PVHIALM.TP. On (1): PV High
alarm present; PV is greater than or equal to PVHIALM.TP for the configured alarm
time.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.362 PVHIALM.PR

Specific to DataAcq
Block(s)
Description Process Variable (PV) High Alarm Priority - Priority of a PV High alarm
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable

- 2392 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.363 PVHIALM.SV

Specific to DataAcq
Block(s)
Description Process Variable (PV) High Alarm Severity - Severity of a PV High alarm
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.364 PVHIALM.TM

Specific to DataAcq
Block(s)
Description Process Variable (PV) High Alarm Filter Time (seconds)
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0
Config Load No
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related PV, PVHIALM.DB, PVHIALM.DBU, PVHIALM.FL, PVHIALM.PR, PVHIALM.SV,
Parameters PVHIALM.TP.
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2393 -
Chapter 18 - Pxxxx Parameters

18.365 PVHIALM.TMO

Specific to Block(s) DataAcq block


Description Process Variable (PV) High Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related Parameters
Remarks To configure off-delay time for Process Variable (PV) High Alarm.

18.366 PVHIALM.TP

Specific to DataAcq
Block(s)
Description Process Variable (PV) High Alarm Trip Point - Defines the trip point for a PV High
alarm.
Data Type 64-Bit Real Number
Range NaN or PVLOALM.TP to PVHHALM.TP
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks The following rule is applied to PVHIALM.TP to prevent PVHI and PVLO alarm that
are both active at the same time: PVLOALM.TP <= PVHIALM.TP - (2 * PVLOALM.DB)
(or PVHIALM.DB <= (PVHIALM.TP - PVLOALM.TP)/2 ) For more information on
DataAcq alarming, refer to the Control Builder Components Theory, DATAACQ (Data
Acquisition) Block,.Alarm processing.

- 2394 -
Chapter 18 - Pxxxx Parameters

18.367 PVHILM

Specific to Numeric
Block(s)
Description Process Variable (PV) High Limit
Data Type 64-Bit Real Number
Range Greater than PVLOLM
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PVLOLM, PV.
Parameters
Remarks When NaN, the limit is not checked on stores to PV. When there is some value,
stores to PV must be less than PVHILM.

18.368 PVHISIGCHG.CT

Specific to DataAcq
Block(s)
Description Process Variable ( PV) High Significant-Change Count - The number of times the
PV low alarm has been re-annunciated (because PVHIALM.TP has been exceeded).

Data Type 32-Bit Integer


Range Greater-than or equal-to 0.
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PVHISIGCHG.TP
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2395 -
Chapter 18 - Pxxxx Parameters

18.369 PVHISIGCHG.TP

Specific to DataAcq
Block(s)
Description Process Variable (PV) High Significant-Change Trip Point - If PV is between the
High and High-High alarm limits, the High alarm will be re-annunciated (if PV
increases by this amount).
Data Type 64-Bit Real Number
Range NaN, or greater-than 0.0.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PVHISIGCHG.CT
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.370 PVHISIGNAL [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1738-IR2M12, 1738-IT2IM12, 1732E-IR4IM12R, 1732E-


Block(s) IT4IM12R
Description Defines the range of a selected sensor type.
Data Type Enumeration
Range See:
l Table 1
l Table 2
Default
Config No
Load
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related SENSORTYPE, PVLOSIGNAL, TEMPUNITS
Parameters
Remarks The PVHISIGNAL parameter is not applicable (Readonly) for Armor Point
Thermocouple and RTD modules. But for the Armor Block Thermocouple and RTD
these parameters need to be entered by the user, as specified in the range table.
Temperature: PVHISIGNAL = Actual sensor high temperature x 10 Millivolt:
PVHISIGNAL = Actual sensor high limit(mV) x 100

- 2396 -
Chapter 18 - Pxxxx Parameters

Table 18.7 PV HISIGNAL Range for 1732E-IR4IM12R


RTD Sensor Type Value
Ohms 5000
100 Ohms Pt 385 l 8500° C
l 15620 F

200 Ohms Pt 385 l 6300° C


l 11660 F

100 Ohms Pt 3916 l 6300° C


l 11660 F

200 Ohms Pt 3916 l 6300° C


l 11660 F

10 Ohms Cu 427 l 2600° C


l 5000 F

120 Ohm Ni 672 l 2600° C


l 5000 F

100 Ohm Ni 618 l 1800° C


l 3560 F

120 Ohm Ni 618 l 1400° C


l 2840 F

Table 18.8 PV HISIGNAL Range for 1732E-IT4IM12R


Thermocouple Sensor Type Value
mV 7812
Type B l 18200° C
l 32720 F

Type C l 23200° C
l 32720 F

Type E l 10000° C
l 18320 F

Type J l 12000° C
l 21920 F

Type K l 13720° C
l 25016 F

- 2397 -
Chapter 18 - Pxxxx Parameters

Type N l 13000° C
l 23720 F

Type R l 17680° C
l 32144 F

Type S l 17680° C
l 32144 F

Type T l 4000° C
l 7520 F

18.371 PVLLALM.DB

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Low Alarm Deadband
Data Type 64-Bit Real Number
Range 0.0 to 100.0: If alarm deadband units ( PVLLALM.DBU) are Percent PVEULO to
PVEUHI If alarm deadband units ( PVLLALM.DBU) are Engineering Units.
Default 0.0
Config Yes
Load
Active No
Loadable
Access EngineerAppDev
Lock
Residence CEE
Related PV, PVLLALM.DBU, PVLLALM.FL, PVLLALM.PR, PVLLALM.SV, PVLLALM.TM,
Parameters PVLLALM.TP.
Remarks The following rule is applied to PVLLALM.DB to prevent overlap between PV alarm
trip point values to avoid multiple alarms. PVLLALM.DB <= PVLOALM.TP -
PVLLALM.TP + PVLOALM.DB The following rule is applied to PVLLALM.DB to
prevent PVHH and PVLL alarm that are both active at the same time: PVLLALM.DB
<= (PVHHALM.TP - PVLLALM.TP)/2 (or PVHHALM.TP >= PVLLALM.TP +
(2*PVHHALM.DB)) For more information on DataAcq alarming, refer to the Control
Builder Components Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2398 -
Chapter 18 - Pxxxx Parameters

18.372 PVLLALM.DBU

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Low Alarm Deadband Units - Indicates if PVLLALM.DB is
in Percent or Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU (1)
Default Percent (0)
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related PV, PVLLALM.DB, PVLLALM.FL, PVLLALM.PR, PVLLALM.SV, PVLLALM.TM,
Parameters PVLLALM.TP.
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.373 PVLLALM.FL

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Low Alarm Flag - Indicates if a PV Low Low alarm has
been issued.
Data Type Boolean
Range Off (0): PV Low Low Alarm is not active; PV is less than PVLLALM.TP. On (1): PV Low
Low Alarm present; PV is greater than or equal to PVLLALM.TP.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2399 -
Chapter 18 - Pxxxx Parameters

18.374 PVLLALM.PR

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Low Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.375 PVLLALM.SV

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Low Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2400 -
Chapter 18 - Pxxxx Parameters

18.376 PVLLALM.TM

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Low Alarm Filter Time (Seconds)
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related PV, PVLLALM.DB, PVLLALM.DBU, PVLLALM.FL, PVLLALM.PR, PVLLALM.SV,
Parameters PVLLALM.TP.
Remarks The purpose of this parameter is to prevent input spikes from causing PV Low Low
alarms. An alarm will only be generated if PV is consistently below the Low Low
alarm trip point for more than the configured alarm filter time. If PVLLALM.TM = 0,
an alarm will be generated as soon as PV exceeds the trip point. For more
information about alarm configuration, refer to Control Builder Components Theory
Guide.

18.377 PVLLALM.TMO

Specific to Block(s) DataAcq block


Description Process Variable (PV) Low Low Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related Parameters
Remarks To configure off-delay time for Process Variable (PV) Low Low Alarm.

- 2401 -
Chapter 18 - Pxxxx Parameters

18.378 PVLLALM.TP

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Low Alarm Trip Point - Defines the trip point for a PV Low
Low alarm.
Data Type 64-Bit Real Number
Range NaN, PVEULO to PVLOALM.TP
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks The following rule is applied to PVLLALM.TP to prevent PVHH and PVLL alarm that
are both active at the same time. PVHHALM.TP >= PVLLALM.TP + (2 PVHHALM.DB)
(or PVLLALM.DB <= (PVHHALM.TP - PVLLALM.TP)/2 ) For more information on
DataAcq alarming, refer to the Control Builder Components Theory, DATAACQ (Data
Acquisition) Block,.Alarm processing.

18.379 PVLOALM.DB

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Alarm Deadband
Data Type 64-Bit Real Number
Range 0.0 to 100.0: If alarm deadband units ( PVLOALM.DBU) are Percent. PVEULO to
PVEUHI: If alarm deadband units ( PVLOALM.DBU) are Engineering Units.
Default 0.0
Config Yes
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related PV, PVLOALM.DBU, PVLOALM.FL, PVLOALM.PR, PVLOALM.SV, PVLOALM.TM,
Parameters PVLOALM.TP.
Remarks The following restriction is applied to PVLOALM.DB to prevent that PVHI and PVLO
alarm are both active at the same time: PVLOALM.DB <= (PVHIALM.TP -
PVLOALM.TP)/2 (or PVHIALM.TP >= PVLOALM.TP + (2* PVHIALM.DB)) For more
information on DataAcq alarming, refer to the Control Builder Components Theory,
DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2402 -
Chapter 18 - Pxxxx Parameters

18.380 PVLOALM.DBU

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Alarm Deadband Units - Indicates if PVLOALM.DB is in
Percent or Engineering Units.
Data Type Enumeration ALMDBU
Range Percent (0) EU (1)
Default Percent (0)
Config Load No
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related PV, PVLOALM.DB, PVLOALM.FL, PVLOALM.PR, PVLOALM.SV, PVLOALM.TM,
Parameters PVLOALM.TP.
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.381 PVLOALM.FL

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Alarm Flag - Indicates if a PV Low alarm has been
issued.
Data Type Boolean
Range Off (0): PV Low alarm is not active; PV > PVLALM.TP. On (1): PV Low alarm present;
PV <= PVLALM.TP for the configured alarm time.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The flag is set only when PV is below the trip point for the configured alarm time.

- 2403 -
Chapter 18 - Pxxxx Parameters

18.382 PVLOALM.PR

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Alarm Priority - Priority of a PV Low alarm
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

18.383 PVLOALM.SV

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2404 -
Chapter 18 - Pxxxx Parameters

18.384 PVLOALM.TM

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Alarm Filter Time (Seconds)
Data Type 32-Bit Unsigned Integer
Range 0 to 9999 seconds
Default 0.0
Config No
Load
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related PV, PVLOALM.DB, PVLOALM.DBU, PVLOALM.FL, PVLOALM.PR, PVLOALM.SV,
Parameters PVLOALM.TP.
Remarks The purpose of this parameter is to prevent input spikes from causing PV Low
alarms. An alarm will only be generated if PV consistently exceeds the Low alarm
trip point for more than the configured alarm filter time. If PVLOALM.TM = 0, an
alarm will be generated as soon as PV falls below the trip point. For more
information about alarm configuration, refer to Control Builder Components Theory
Guide.

18.385 PVLOALM.TMO

Specific to Block(s) DataAcq


Description Process Variable (PV) Low Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related Parameters
Remarks To configure off-delay time for Process Variable (PV) Low Alarm.

- 2405 -
Chapter 18 - Pxxxx Parameters

18.386 PVLOALM.TP

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Alarm Trip Point - Defines the trip point for a PV Low
alarm.
Data Type 64-Bit Real Number
Range NaN, or PVLLALM.TP to PVHIALM.TP
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks The following restriction is applied to PVLOALM.TP to prevent that PVHI and PVLO
alarm are both active at the same time: PVHIALM.TP >= PVLOALM.TP + (2 *
PVHIALM.DB) (or PVLOALM.DB <= (PVHIALM.TP- PVLOALM.TP)/2) For more
information on DataAcq alarming, refer to the Control Builder Components Theory,
DATAACQ (Data Acquisition) Block,.Alarm processing.

18.387 PVLOLM

Specific to Numeric
Block(s)
Description Process Variable (PV) Low Limit
Data Type 64-Bit Real Number
Range Real number less than PVHILM
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PV, PVLOALM.DB, PVLOALM.TP.
Parameters
Remarks When NaN, the limit is not checked on stores to PV. When there is some value,
stores to PV must be greater than PVLOLM.

- 2406 -
Chapter 18 - Pxxxx Parameters

18.388 PVLOSIGCHG.CT

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Significant-Change Count - The number of times the PV
low alarm has been re-annunciated (because PVLOALM.TP has been exceeded).
Data Type 32-Bit Integer
Range Greater-than or equal-to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

18.389 PVLOSIGCHG.TP

Specific to DataAcq
Block(s)
Description Process Variable (PV) Low Significant-Change Trip Point - If PV is between its low
and low-low alarm limits, the low alarm will be re-annunciated if PV decrease by this
amount.
Data Type 64-Bit Real Number
Range NaN, or greater-than 0.0.
Default NaN
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PVLOSIGCHG.CT
Parameters
Remarks Re-alarming is disabled if PVLOSIGCHG.TP = NaN.

- 2407 -
Chapter 18 - Pxxxx Parameters

18.390 PVLOSIGNAL [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1738-IR2M12, 1738-IT2IM12, 1732E-IR4IM12R, 1732E-


Block(s) IT4IM12R
Description Defines the range of a selected sensor type.
Data Type Enumeration
Range See:
l Table 1
l Table 2
Default
Config No
Load
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related SENSORTYPE, PVHISIGNAL, TEMPUNITS
Parameters
Remarks The PVLOSIGNAL parameter is not applicable (Readonly) for Armor Point
Thermocouple and RTD modules. But for the Armor Block Thermocouple and RTD
these parameters need to be entered by the user, as specified in the range table.
Temperature: PVLOSIGNAL = Actual sensor low temperature x 10 Millivolt:
PVLOSIGNAL = Actual sensor low limit(mV) x 100
Table 18.9 PV LOSIGNAL Range for 1732E-IR4IM12R
RTD Sensor Type Value
Ohms 0
100 Ohms Pt 385 l —2000° C
l —3280 F

200 Ohms Pt 385 l —2000° C


l —3280 F

100 Ohms Pt 3916 l —2000° C


l —3280 F

200 Ohms Pt 3916 l —2000° C


l —3280 F

10 Ohms Cu 427 l —1000° C


l —1480 F

120 Ohm Ni 672 l —800° C


l —1120 F

100 Ohm Ni 618 l —600° C


l —760 F

120 Ohm Ni 618 l —900° C


l —1300 F

- 2408 -
Chapter 18 - Pxxxx Parameters

Table 18.10 PV LOSIGNAL Range for 1732E-IT4IM12R


Thermocouple Sensor Type Value
mV -7812
Type B l 400° C
l 1040 F

Type C l 0° C
l 320 F

Type E l –2700° C
l —4540 F

Type J l —2100° C
l —3460 F

Type K l —2700° C
l —4540 F

Type N l —2700° C
l —4540 F

Type R l —500° C
l —580 F

Type S l —500° C
l —580 F

Type T l —2700° C
l —4540 F

18.391 PVMANOPT

Specific to PID, PIDFF


Block(s)
Description Process Variable (PV) Manual Option - Indicates what to do when PVSTS = Manual.
Data Type Enumeration BADCTLOPT
Range NoShed (0): Do nothing (that is, behave the same as if PVSTS = Normal)
ShedHold (1): Set MODE to Manual, and MODEATTR to Operator; disable External
Mode Switching, and hold OP at the last good value.
ShedLow (2): Set MODE to Manual, and MODEATTR to Operator, disable External
Mode Switching, and set OP to its extended low limit (OPEXLOLM).
ShedHigh (3): Set MODE to Manual, and MODEATTR to Operator, disable External
Mode Switching, and set OP to its extended high limit (OPEXHILM).
ShedSafe (4): Set MODE to Manual and MODEATTR to Operator, disable External
Mode Switching, and set OP to the configured safe value (SAFEOP).
If SAFEOP is NaN, OP is held at the last good value.
Default ShedHold (1)
Config Yes
Load

- 2409 -
Chapter 18 - Pxxxx Parameters

Active No
Loadable
Access Lock Engineer
Residence CEE
Related ESWENB, MODE, MODEATTR, OP, PVSTS.
Parameters
Remarks

Specific to PosProp
Block(s)
Description Process Variable (PV) Manual Option - Indicates what to do when PVSTS =
Manual.
Data Type Enumeration
Range NO_SHED - Idle SHEDHIGH - Raise SHEDLOW - Lower SHEDSAFE - Depends
on Safe State SHEDHOLD - Idle
Default ShedHold (1)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related ESWENB, MODEMODEATTR, OP, PVSTS.
Parameters
Remarks

18.392 PVNORMAL

Specific to DICHANNEL
Block(s)
Description Process Variable (PV) Normal Option. Defines the normal state of the PV using the
appropriate State Text (STATETEXT) parameter descriptor. The PV normal state text
descriptor describes the normal (desired) state, such as Run, Stop, Open, Closed.
Data Type Enumeration
Range 0 STATETEXT Defaulted to Off for PV
STATE 0.
1 STATETEXT Defaulted to On for PV
STATE 1.
None No off normal checking.
Default STATETEXT(0)
Config Yes
Load
Active No
Loadable

- 2410 -
Chapter 18 - Pxxxx Parameters

Access Lock Engineer


Residence IOM
Related ALMOPT
Parameters
Remarks This parameter is only exposed when ALMOPT is OFFNORML.

18.393 PVP

Specific to Block(s) PID, PIDFF, PosProp, DataAcq


Description Process Variable (PV) Value (in Percent)
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PV, PVEUHI, PVEULO.
Remarks

Specific to Block(s) ROC


Description PV in percent
Data Type Float64
Range
Default NaN
Config Load NO
Active Loadable No
Access Lock Read only
Residence CEE
Related Parameters
Remarks PVP is calculated based PV applied on to the range PVEUHI and PVEULO.

Specific to Block(s) LEVELCOMP


Description Drum level in percent
Data Type Float64
Range
Default NaN
Config Load NO
Active Loadable No

- 2411 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters PVEUHI, PVEULO
Remarks This value will have PV value in percent span of PVEUHI and PEEULO.

18.394 PVRATE

Specific to Block(s) SignalSel


Description Rate for Bumpless Transfer
Data Type Float64
Range N/A
Default NaN
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related Parameters PV
Remarks The rate of change per minute to provide bumpless transfer of PV value.

18.395 PVRAW

Specific to PBAICHANNEL, PBAOCHANNEL, AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL


Block(s) (Series C I/O)
Description Process Variable (PV) Raw Value. Shows the raw input value of the PV before or
after initial processing has been applied, depending on the type of I/O Module that
is involved. See the Remarks below for more information.
Data Type 32-Bit Real Number
Range N/A
Default NaN
Config No
Load
Active No
Loadable

- 2412 -
Chapter 18 - Pxxxx Parameters

Access ViewOnly
Lock
Residence IOP
Related
Parameters
Remarks For analog IOMs, this parameter indicates the raw input value of the PV from the
Field Termination Assembly (FTA) before PV characterization is applied. The field
sensor type determines the units of value as follows: 0 - 5V, 0.4 - 2V, 1 - 5V Sensor:
Percent (%) Thermocouple Sensor: Microvolts RTD Sensor: Milliohms Slidewire
Sensor: Ratio 0 - 100mV Sensor: Millivolts For smart transmitter interface IOMs, this
parameter Indicates the raw input value of the PV in percent of span based on the
transmitter PV after PV characterization (PVCHAR) and DAMPING have been
applied. The span of the PV is determined by using LRV as a 0%-point and URV as a
100%-point. For HAICHANNEL: See HENABLE for description of PVRAW. The
PVRAW parameter is not supported in SimC300. Therefore, in Series C and PMIO AI
channels, the values of PVRAW take the default values. The default values are:
l For HART IO and 1756 IO, the default value is 0.
l For RAIL I/O, the default value is 2000.

Specific to Block(s) DICHANNEL (PM I/O) DICHANNEL (Series C I/O)


Description Raw Process Variable (PV). Shows the current raw state of the field
contacts.
Data Type Boolean
Range 0 Off Open contacts
1 On Closed contacts
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks

Specific to Analog Input, Analog Composite, Regulator blocks belonging to EHG


Block(s)
Description PVRAW
Data Type Real
Range -6.86% to 106.86%
Default “N/A”
Config Load No
Active No
Loadable

- 2413 -
Chapter 18 - Pxxxx Parameters

Access Lock View Only


Residence DH
Related PV PVAUTO
Parameters
Remarks This parameter provides the current value of the PV after A/D conversion, digital
filtering, and PV square rooting.

18.396 PVRAW_AI_S

Specific to UIO, UAI, AI16-100MS


Block(s)

Description PV RAW
Data Type FLOAT32
Range N/A
Default NaN
Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence IOM Block


Related N/A
Parameters

Remarks This parameter indicates the raw input value of the PV from the Field Termination
Assembly (FTA) before PV characterization is performed. The field sensor determines the
units of value.

18.397 PVRAW[0..numChans-1]

Specific to EIP Analog Input Modules


Block(s)
Description PV Raw Value — Represents the raw input value of the PV from Analog Input device
before any kind of initial processing has been applied.
Data Type Float 32
Range

Default 0
Config Load No
Active No
Loadable

- 2414 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence NoLoad
Related None
Parameters
Remarks It is indexed by channel number.

18.398 PVRAW[0..120]

Specific to Block(s) PCDINUMARRCH


Description Process Value Raw, from device
Data Type Float64
Range
Default NaN
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks

18.399 PVRAW[0..numChans-1]

Specific to Block(s) AIM


Description Process Variable from Analog Input device, indexed by channel number.
Data Type 64-Bit Real Number
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2415 -
Chapter 18 - Pxxxx Parameters

18.400 PVRAWHI

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable (PV) Raw High Range. Specifies the high end of the normal
operating range for the raw PV (PVRAW) input value.
Data Type 32-Bit Real Number
Range For SENSRTYP 0_100_MV: PVRAWLO to 100.0.
For SENSRTYP SLIDWIRE: PVRAWLO to 1.0.
Default 1.0 when SENSRTYP is SLIDWIRE 100.0 when SENSRTYP is 0_100_MV
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence IOM
Related
Parameters
Remarks This parameter is only exposed when SENSRTYP is 0_100_MV or SLIDWIRE. For a
slidewire input, the Engineering Units are ratio. For a 0 to 100 millivolt input, the
Engineering Units are millivolts. PVEUHI cannot be written with NaN (Not a
Number). NaN is the default power up value only.

18.401 PVRAWHI[0..numChans-1]

Specific to EIP Analog Input Modules


Block(s)
Description PV Raw High Range — Specifies the high end value of the normal operating
range for the raw PV input value (PVRAW).
Data Type INT32
Range PVRAWHI must be greater than PVRAWLO

Default 0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks It is indexed by the channel number.

- 2416 -
Chapter 18 - Pxxxx Parameters

18.402 PVRAWHI[0..120]

Specific to Block(s) PCDINUMARRCH


Description Process Value Raw High Range
Data Type Float64
Range PVRAWHI must be greater than PVRAWLO
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks Set the PVRAWHI limit for the device index

18.403 PVRAWLO

Specific to AICHANNEL, HAICHANNEL (PM I/O) AICHANNEL (Series C I/O)


Block(s)
Description Process Variable (PV) Raw Low Range. Specifies the low end of the normal
operating range for the raw PV (PVRAW) input value.
Data Type 32-Bit Real Number
Range 0.0 to PVRAWHI For SENSRTYP 0_100_MV: PVRAWLO to 100.0. For SENSRTYP
SLIDEWIRE: PVRAWLO to 1.0.
Default 0.0, regardless of SENSRTYP
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence IOP
Related
Parameters
Remarks This parameter is only exposed when SENSRTYP is 0_100_MV or SLIDWIRE. For a
slidewire input, the Engineering Units are ratio. For a 0 to 100 millivolt input, the
Engineering Units are millivolts. PVRAWLO cannot be written with NaN (Not a
Number). NaN is the default power up value only.

- 2417 -
Chapter 18 - Pxxxx Parameters

18.404 PVRAWLO[0..numChans-1]

Specific to EIP Analog Input Modules


Block(s)
Description PV Raw Low Range — Specifies the low end value of the normal operating range
for the raw PV parameter value (PVRAW).
Data Type INT32
Range PVRAWLO must be less than PVRAWHI

Default 0
Config Load Yes
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks It is indexed by the channel number.

18.405 PVRAWLO[0..120]

Specific to Block(s) PCDINUMARRCH


Description Process Value Raw Low Range
Data Type Float64
Range PVRAWLO must be less than PVRAWHI
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks Set the PVRAWLO limit for the device index.

- 2418 -
Chapter 18 - Pxxxx Parameters

18.406 PVRAWREF

Specific to PID, PID-PL, PIDER, PIDFF, POSPROP


Block(s)
Description PVRAWREF displays the name (BLOCKID) of the AICHANNEL block from where the
RegCtl block (PID block) is fetching its PV value.
Data Type BLOCKID
Range Any Tag.[Block] block reference
Default “”
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related PV
Parameters
Remarks When configuring this parameter, you must ensure that you define the PVRAWREF
parameter in the format <TAG.BLOCKNAME>. Do not include block parameters such
as PV, P1 or PVRAW while defining the PVRAWREF parameter. After defining the
channel block name into PID block when you download the parent CM, you can
view the channel block’s PVRAW value (before processing) besides the PV value
when you click the PV field in the PID faceplate. This configuration enables an
operator to compare changes on instrument output with PV value and ensure that
PVEU range is within the field instrument range (4-20 mA).

18.407 PVROCBYPASSFL

Specific to Block(s) ROC


Description Bypass Trip Limits
Data Type Boolean
Range
Default OFF
Config Load NO
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related
Parameters
Remarks When this parameter is ON the ROC limiting will cease and P1 will be written
on to PV.

- 2419 -
Chapter 18 - Pxxxx Parameters

18.408 PVROCNEGFL

Specific to Block ROC


(s)
Description Output (PV) Negative Rate of Change Flag
Data Type Boolean
Range
Default OFF
Config Load NO
Active Loadable No
Access Lock Read only
Residence CEE
Related
Parameters
Remarks This flag indicates that rate of change limit is applied to the PV in the negative
direction.

18.409 PVROCNEGLM

Specific to Block(s) ROC


Description Negative Output (PV) Rate of Change Limit (in Percent per minute)
Data Type Float64
Range
Default 0
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks This limit is imposed on output PV in the negative direction

18.410 PVROCPOSFL

Specific to Block ROC


(s)
Description Output (PV) Positive Rate of Change Flag
Data Type Boolean
Range
Default OFF

- 2420 -
Chapter 18 - Pxxxx Parameters

Config Load NO
Active Loadable No
Access Lock Read only
Residence CEE
Related
Parameters
Remarks This flag indicates that rate of change limit is applied to the PV in the positive
direction.

18.411 PVROCPOSLM

Specific to Block(s) ROC


Description Positive Output (PV) Rate of Change Limit (in Percent per minute)
Data Type Float64
Range
Default 0
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks This limit imposed on output PV in the positive direction.

18.412 PVSCALEFACTOR [0..NUMCHANNELS-1]

Specific to Block(s) EtherNet/IP [EIP] IOMs: 1738-IT2IM12,1732E-IT4IM12R


Description PV Scale factor
Data Type FLOAT 32
Range
Default 0.1
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters PV, PVRAW
Remarks PV = PVSCALEFACTOR x PVRAW

- 2421 -
Chapter 18 - Pxxxx Parameters

18.413 PVSOURCE

Specific to DATAACQ, DIGACQ, DEVCTL All Drive Control Blocks: HTMOTOR, LTMOTOR,
Block(s) SOLENOID, VALVEDAMPER
Description Process Variable ( PV) Source - Identifies the source of the PV input.
Data Type Enumeration PVSOURCE
Range Sub (0): PV value is provided by a user program.
Man (1): PV value is provided by the operator.
Auto (2): PV value is fetched from another function block.
Default Auto (2)
Config Yes
Load
Active No
Loadable
Access Lock DATAACQ, DIGACQ: Operator DEVCTL, All Drive Control: ViewOnly, Operator (see
Remarks)
Residence CEE
Related DEVCTL: GPV, GPVAUTO, NUMDINPUTS, NUMDOUTS, DIGACQ: PV, PVSRCOPT All
Parameters PV, PVAUTO, PVSRCOPT Drive Control: GPV,
GPVAUTO, PV, PVAUTO,
PVSRCOPT.
Remarks All: ViewOnly and defaulted to Auto if PVSRCOPT = OnlyAuto. DEVCTL and Drive
Control: If PVSOURCE is not Man and the function block is InActive, PV is defaulted
to Null. Drive Control:If PVSOURCE is Man, then the acess is OPERATOR.
DEVCTL:Access illegal if NUMDINPUTS = 0. DEVCTL PVSOURCE may not be set =
Track if NUMDOUTS = 0.

Specific to DICHANNEL (PM I/O) DICHANNEL (Series C I/O)


Block(s)
Description Process Variable (PV) Source. Defines the source of the PV input to this data
point.
Data Type Enumeration
Range 0 Sub Sequence program provides
PV.
1 Man Operator or program
provides PV.
2 Auto Field wiring or memory fetch
supplies PV.
Default Auto (2)
Config Load Yes
Active No
Loadable

- 2422 -
Chapter 18 - Pxxxx Parameters

Access Lock Operator


Residence IOM
Related
Parameters
Remarks PVSOURCE change by an operator requires PVSRCOPT = All. This parameter is
only exposed if PNTFORM = FULL

Specific to Block(s) Series C AICHANNEL


Description PV Source
Data Type Enumeration
Range 0 Sub PV is supplied by a program.
1 Man PV is supplied by the operator.
2 Auto PV is supplied by field wiring.
Default Auto (2)
Config Load Yes
Active Loadable No
Access Lock Operator
Residence IOM
Related Parameters PVSRCOPT
Remarks

Specific to Series C DICHANNEL


Block(s)
Description PV Source
Data Type Enumeration
Range 0 Sub Sequence program provides PV.

1 Man Operator or program provides


PV.
2 Auto Field wiring or memory fetch
supplies PV.
Default Auto (2)
Config Load Yes
Active Loadable No
Access Lock Operator
Residence IOM
Related PVSRCOPT
Parameters
Remarks "SUB" option is not supported for UIO - DI Channel when DITYPE is configured
as "ACCUM."

- 2423 -
Chapter 18 - Pxxxx Parameters

Specific to Block(s) HRBALG_PIUAI


Description PV Source
Data Type ENUM
Range 0123
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters -
Remarks

18.414 PVSRC

Specific to Auxcalc
Block(s)
Description Process Variable (PV) source: Any of P[1..6], PVSTS, C[1..8] or CSTS[1..8]
Data Type Enumeration CALCOUTSELECTOR
Range P1 (0) P2 (1) P3 (2) P4 (3) P5 (4) P6 (5) C1 (6) C2 (7) C3 (8) C4 (9) C5 (10) C6 (11) C7
(12) C8 (13) P1STS (14) P2STS (15) P3STS (16) P4STS (17) P5STS (18) P6STS (19)
C1STS (20) C2STS (21) C3STS (22) C4STS (23) C5STS (24) C6STS (25) C7STS (26)
C8STS (27)
Default P1 (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PVSTSSRC
Parameters
Remarks

18.415 PVSRCOPT

Specific to DEVCTL, All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,


Block(s) VALVEDAMPER
Description Process Variable (PV) Source Option - Identifies the PV source selection options
available to this function block.
Data Type Enumeration PVSRCOPT
Range OnlyAuto (0): PV may only be fetched from another function
block, via an active input connection; PV source

- 2424 -
Chapter 18 - Pxxxx Parameters

selection is not available.


All (1): PV may be fetched from another function block, or
provided by an operator or a user program, it
depends on the PVSOURCE.
Default All (1)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related GPVPV, PVSOURCE. DevCtl Only:
Parameters NUMDINPUTS
Remarks If set to OnlyAuto, and the function block is Inactive, PV is set to Null. DEVCTL:
Access is illegal if NUMDINPUTS = 0.

Specific to DATAACQ
Block(s)
Description Process Variable (PV) Source Option - Identifies the PV source selection options
available to this function block.
Data Type Enumeration PVSRCOPT
Range OnlyAuto (0): PV may only be fetched from another function
block, via an active input connection; PV source
selection is not available.
All (1): PV may be fetched from another function block, or
provided by an operator or a user program, it
depends on the PVSOURCE.
Default OnlyAuto (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related GPV, PV, PVSOURCE. DevCtl Only:
Parameters NUMDINPUTS
Remarks If set to OnlyAuto, and the function block is Inactive, PV is set to Null.

Specific to DICHANNEL (PM I/O)


Block(s)
Description Process Variable (PV) Source Option. Defines the source of the PV to be used for
this data point.
Data Type Enumeration
Range ONLYAUTO (0): PV source selection is not available and field
wiring or memory fetch supplies the PV.
ALL (1): PV is provided by operator, a sequence
program, or by field wiring.
Default ONLYAUTO (0)
Config Load Yes

- 2425 -
Chapter 18 - Pxxxx Parameters

Active No
Loadable
Access Lock Engineer
Residence IOM
Related
Parameters
Remarks This parameter is only exposed when the PNTFORM is Full. An operator can
change the PVSRCOPT, if the DITYPE configuration is LATCHED.

Specific to Series C AICHANNEL, DICHANNEL


Block(s)
Description PV Source Option
Data Type Enumeration
Range 0 OnlyAuto PV source selection is not available and field wiring supplies PV.
When set to OnlyAuto, users may not change PVSOURCE.
1 All PV can be provided by an operator or by a sequence program or
by field wiring. When set to All, users may change PVSOURCE.
Default OnlyAuto
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence IOM
Related PVSOURCE
Parameters
Remarks

Specific to DIGACQ
Block(s)
Description PV Source Option
Data Type Enumeration
Range 0 OnlyAuto PV may only be fetched from another function block, via an
active input connection; PV source selection is not available.

1 All PV may be fetched from another function block, or provided


by an operator or a user program, it depends on the
PVSOURCE.
Default OnlyAuto
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PV, PVSOURCE
Parameters
Remarks Gives an option to the engineer to enable selection of PVSOURCE.

- 2426 -
Chapter 18 - Pxxxx Parameters

18.416 PVSTS

Specific to PID, PIDER, PIDFF, PosProp, DataAcq, RatioCtl, RampSoak, AuxCalc, FlowComp,
Block(s) SignalSel
Description Process Variable (PV) Status - Contains the status of the PV value.
Data Type Enumeration
Range Bad (0): The PV value was bad and replaced with NaN.

Uncertain (1): The status of the PV value is uncertain,


stored by a program.
Normal (2): The PV value is good.
Manual (3): The PV value was manually entered.
Default Bad (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, PVVALSTS.
Parameters
Remarks

Specific to Block DEVCTL


(s)
Description Process Variable (PV) Status. Shows the current status of the PV value.
Data Type Enumeration
Range 0 BAD The input value is bad and replaced
with NaN.
1 UNCERTAIN The status of the input is uncertain.
2 NORMAL The input value is good.
3 MANUAL The input value is manually set.
4 INITACK Initialization Acknowledged
5 INITREQ Initialization Requested
6 INITBAD Initialization Bad
Default BAD (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PV
Parameters
Remarks

- 2427 -
Chapter 18 - Pxxxx Parameters

Specific to Block(s) Deadtime, Genlin, Leadlag, Totalizer


Description Bad Process Variable (PV) Status Flag - Indicates if the PV status is Bad.
Data Type Boolean
Range Off (0): PVSTS is not Bad. On (1): PVSTS is Bad.
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PV, PVSTSFL.BAD, PVSTSFL.MAN, PVSTSFL.NORM, PVSTSFL.UNCERTN.
Remarks

Specific to Block(s) Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC, Pulse Input Totalizer
Description Process Variable (PV) Status.
Data Type Enumeration
Range Bad (0) Uncertn (1) Normal (2) Manual (3)
Default Bad
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PV
Remarks

Specific to Block(s) Series C PICHANNEL


Description Process Value Status
Data Type ENUM
Range BAD(0) UNCERTAIN(1) NORMAL(2) MANUAL(3)
Default BAD
Config Load No
Active Loadable No
Access Lock View Only
Residence IOM
Related Parameters PV
Remarks PVSTS indicates the status of the Process Value (PV).

Specific to Block(s) DIC


Description PV Status
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No

- 2428 -
Chapter 18 - Pxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

Specific to AICHANNEL, HAICHANNEL (PM I/O), AICHANNEL (Series C I/O) HLAI, HLAIHART,
Block(s) LLAI, LLUMX, RHMUX, and STI
Description Process Variable (PV) Status. Shows the current status of the PV value.
Data Type Enumeration
Range 0 BAD The input value is bad and
replaced with NaN.
1 UNCERTAIN The status of the input is
uncertain.
2 NORMAL The input value is good.
3 MANUAL The input value is manually
set.
Default BAD (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related For HAICHANNELs and AICHANNELs (Series C I/O): HPVMISM
Parameters
Remarks

Specific to Block DIGACQ, LEVELCOMP


(s)
Description Process Variable (PV) or Level Status - Contains the status of the PV value.
Data Type Enumeration
Range Bad (0): The PV value was bad and replaced with NaN.
Uncertain (1): The status of the PV value is uncertain, stored
by a program.
Normal (2): The PV value is good.
Manual (3): The PV value was manually entered.
Default DIGACQ: Bad (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PV
Parameters
Remarks

- 2429 -
Chapter 18 - Pxxxx Parameters

18.417 PVSTS[1..NUMCHAN]

Specific to Block(s) Series C I/O Channel Blocks


Description Process value status
Data Type Enumeration
Range
Default BAD
Config Load No
Active Loadable No
Access Lock View Only
Residence IOM
Related Parameters
Remarks

18.418 PVSTS[0..63]

Specific to Block(s) REQNUMARRAY, RSPNUMARRAY


Description Array of Status Values. These values are obtained from the Status of the last
request.
Data Type Enumeration
Range 0 BAD
1 UNCERTN
2 NORMAL
3 MANUAL
4 INITACK
5 1.10.1 INITREQ
6 1.10.2 INITBAD
Default BAD (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

- 2430 -
Chapter 18 - Pxxxx Parameters

18.419 PVSTS[0..120]

Specific to Block(s) PCDINUMARRCH


Description PV Status
Data Type Enumeration
Range 0 BAD
1 UNCERTN
2 NORMAL
3 MANUAL
4 INITACK
5 1.11.1 INITREQ

6 1.11.2 INITBAD
Default BAD
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.420 PVSTS[0..1968]

Specific to Block(s) PCDIFLAGARRCH


Description PV Status
Data Type Enumeration
Range 0 BAD
1 UNCERTN
2 NORMAL
3 MANUAL
4 INITACK
5 1.12.1 INITREQ

6 1.12.2 INITBAD
Default BAD
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2431 -
Chapter 18 - Pxxxx Parameters

18.421 PVSTS[0..numChans-1]

Specific to Block(s) DIM, DOM (not exposed on the DOM)


Description DIM: PV Status DOM: Echoback Status
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

Specific to Block(s) AICHANNEL (PM I/O)


Description Process Variable (PV) Status. Shows the current status of the PV value.
Data Type Enumeration
Range BAD (0): The input value is bad and replaced with
NaN.
UNCERTAIN (1): The status of the input is uncertain.
NORMAL (2): The input value is good.
MANUAL (3): The input value is manually set.
Default BAD (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOP
Related ERRFL, PV[1..64].
Parameters
Remarks

18.422 PVSTS[0..numChans-1]

Specific to Block(s) EIP Analog Input Modules


Description Process Value Status - Indicates the status of the corresponding numeric
value.
Data Type Enum
Range l 0 : BAD
l 1 : NORMAL
Default NORMAL

- 2432 -
Chapter 18 - Pxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related PV[0..numChans-1]
Parameters
Remarks

18.423 PVSTS[1..64]

Specific to Block(s) SINUMARRCH


Description Process Value Status - Indicates the status of the corresponding Numeric
value.
Data Type Enumeration
Range Bad (0) Uncertain (1) Normal (2) Manual (3)
Default Normal (2)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related ERRFL, PV[1..64].
Parameters
Remarks

18.424 PVSTSFL.ALL

Specific to Block(s) Auxiliary Function Blocks


Description PV Status Flag
Data Type Structure
Range N/A
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related Parameters PVSTS, PVSTSFL.BAD, PVSTSFL.MAN, PVSTSFL.NORM,
PVSTSFL.UNCERTN.
Remarks

- 2433 -
Chapter 18 - Pxxxx Parameters

18.425 PVSTSFL.BAD

Specific to PID, PIDFF, PosProp, DataAcq, Deadtime, Leadlag, Auxcalc, Genlin, Totalizer,
Block(s) Pulse Input Totalizer, FlowComp, SignalSel
Description Bad Process Variable (PV) Status Flag - Indicates if the PV status is Bad.
Data Type Boolean
Range Off (0): PVSTS is not Bad. On (1): PVSTS is Bad.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, PVSTS, PVSTSFL.MAN, PVSTSFL.NORM. PVSTSFL.UNCERTN, PVVALSTS.
Parameters
Remarks

Specific to Block(s) DIGACQ


Description Bad PV Flag
Data Type Boolean
Range OFF, ON
Default OFF(0)
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter is ON when the PV status is Bad

18.426 PVSTSFL.MAN

Specific to PID, PIDFF, PosProp, RampSoak, DataAcq, Leadlag, Auxcalc, Genlin, Totalizer,
Block(s) Pulse Input Totalizer, FlowComp, SignalSel.
Description Manual Process Variable (PV) Status Flag - Indicates that the PVSTS is Manual.
Data Type Boolean
Range Off (0): PVSTS is not Manual. On (1): PVSTS is Manual.
Default Off (0)
Config Load No
Active No
Loadable

- 2434 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related PV, PVSTS, PVSTSFL.BAD, PVSTSFL.NORM., PVSTSFL.UNCERTN, PVVALSTS.
Parameters
Remarks

Specific to Block(s) DIGACQ


Description PV Source Manual
Data Type Boolean
Range OFF, ON
Default OFF(0)
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter is ON when the PV source is Man

18.427 PVSTSFL.NORM

Specific to PID, PIDFF, PosProp, RampSoak, DataAcq, Leadlag, Deadtime, Auxcalc, Genlin,
Block(s) Totalizer, Pulse Input Totalizer, FlowComp, SignalSel
Description Normal Process Variable (PV) Status Flag - Indicates that the PVSTS is Normal.
Data Type Boolean
Range Off (0): PVSTS is not Normal. On (1): PVSTS is Normal.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, PVSTS, PVSTSFL.BAD, PVSTSFL.MAN., PVSTSFL.UNCERTN, PVVALSTS.
Parameters
Remarks

Specific to Block(s) DIGACQ


Description PV Source Normal
Data Type Boolean
Range OFF, ON
Default OFF(0)
Config Load NO
Active Loadable No

- 2435 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks This parameter is ON when the PV status is AUTO

18.428 PVSTSFL.UNCERTN

Specific to PID, PIDFF, PosProp, RampSoak, DataAcq, Leadlag, Deadtime, Auxcalc, Genlin,
Block(s) Totalizer, Pulse Input Totalizer, FlowComp, SignalSel
Description Uncertain Process Variable (PV) Status Flag - Indicates whether the Process
Variable (PV) status is Uncertain.
Data Type Boolean
Range Off (0): PVSTS is not Uncertain. On (1): PVSTS is Uncertain.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, PVSTS, PVSTSFL.BAD, PVSTSFL.MAN., PVSTSFL.NORM, PVVALSTS.
Parameters
Remarks

Specific to Block(s) DIGACQ


Description PV Source uncertain
Data Type Boolean
Range OFF, ON
Default OFF(0)
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter is UNCERTN when the PV status is SUB

- 2436 -
Chapter 18 - Pxxxx Parameters

18.429 PVSTS_AI_S

Specific to Block(s) UIO


Description Process Variable Status
Data Type ENUM
Range
0 Bad The input value is bad and replaced with
NaN.

1 Uncertain The status of the input is uncertain.

2 Normal The input value is good.

3 Manual The input value is manually set.

Default Bad
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence UIO
Related Parameters

Specific to Block(s) UIO, UAI, AI16-100MS


Description Process Variable Status
Data Type ENUM
Range
0 Bad The input value is bad and replaced with
NaN.

1 Uncertain The status of the input is uncertain.

2 Normal The input value is good.

3 Manual The input value is manually set.

Default Bad
Config Load No
Active Loadable

Access Lock ViewOnly


Residence IOM Block
Related Parameters

Remarks N/A

- 2437 -
Chapter 18 - Pxxxx Parameters

18.430 PVSTSSRC

Specific to Auxcalc
Block(s)
Description PVSTS source: Any of C[1..8], CSTS[1..8], P[1..6], or PVSTS.
Data Type Enumeration CALCOUTSELECTOR
Range P1 (0) P2 (1) P3 (2) P4 (3) P5 (4) P6 (5) C1 (6) C2 (7) C3 (8) C4 (9) C5 (10) C6 (11) C7
(12) C8 (13) P1STS (14) P2STS (15) P3STS (16) P4STS (17) P5STS (18) P6STS (19)
C1STS (20) C2STS (21) C3STS (22) C4STS (23) C5STS (24) C6STS (25) C7STS (26)
C8STS (27)
Default P1STS (14)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PVSRC
Parameters
Remarks

18.431 PVTEMP

- 2438 -
Chapter 18 - Pxxxx Parameters

Specific to AICHANNEL, HAICHANNEL, Series C AICHANNEL


Block(s)

Description PV Temperature Scale

Data Type ENUM

Exposure OUTPUT

Range 0 Degrees_C Celsius

1 Degrees_F Fahrenheit

2 Degrees_R Rankin

3 Degrees_K Kelvin

Default Degrees_C

Config Yes
Load

Engineer / Application Developer

Residence IOM

Related N/A
Parameters

Remarks This parameter defines the temperature scale to be used in characterizing the PV input.
PVTEMP configuration applies only if SENSRTYP = Thermcpl or RTD.

Internal No
Only

18.432 PVTRAKOPT

Specific to PID, PIDFF, PIDER, PID-PL


Block(s)
Description Process Variable (PV) Tracking Option - Indicates whether the Set Point ( SP) is to
track PV in MAN MODE or when INITMAN is ON in CAS MODE.
Data Type Enumeration TRACKING
Range NoTrack (0): SP is never set equal to PV.
Track (1): Manual mode or initialization causes SP
to track PV.
Default NoTrack (0)
Config Load Yes
Active No
Loadable

- 2439 -
Chapter 18 - Pxxxx Parameters

Access Lock Operator


Residence CEE
Related
Parameters
Remarks SP is set equal to PV if PVTRAKOPT = Track and the function block is:
l in manual mode.
l being initialized from a secondary.
l undergoing a 1-shot initialization.

18.433 PVTRAKOPTAI

Specific to PID, PIDFF, PIDER, PID-PL


Block(s)
Description Process Variable Tracking Option Auto/Intialization - Provides a PV Tracking option
for the specific case when the block is in Auto mode and the block is undergoing
initialization (INITMAN is On).
Data Type Enumeration
Range NoTrack (0): SP is not set equal to PV in Auto/Init.
Track (1): SP is set equal to PV in Auto/Init.
Default NoTrack (0)
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related PVTRAKOPT
Parameters
Remarks The PVTRAKOPT PV Tracking option parameter does not include the Auto/Init case,
but does cover several other situations.

18.434 PVVAL

Specific to Block(s) DIC


Description Process Value.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No

- 2440 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

18.435 PVVAL[0..numChans-1]

Specific to Block(s)s DIM, DOM (not exposed on the DOM)


Description DIM: Process Value. DOM: Echoback Value.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

18.436 PVVALSTS

Specific to PID, PIDFF, PosProp, ENHAUXCALC


Block(s)
Description Process Variable (PV) Value and Status - Structure containing the current PV value
plus the status (PVSTS).
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, PVSTS.
Parameters
Remarks Use this parameter to pass the status of the PV along with the PV value in all input
connections. The status of the PV is monitored automatically by the PID block, and if
PVSTS is MANUAL, you may choose to configure the SHED response of the PID
block.

- 2441 -
Chapter 18 - Pxxxx Parameters

Specific to AIC, DIC, DataAcq, Auxcalc, Genlin, Totalizer, Deadtime, Leadlag, Pulse Input
Block(s) Totalizer, SignalSel
Description Process Variable (PV) Value and Status - Structure containing the current PV Value
and Status (PVSTS).
Data Type Structure
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, PVSTS.
Parameters
Remarks For AIC: Use this parameter to pass the status of PV along with the PV value in all
input connections. The status of the PV is monitored automatically by the PID block
and if PVSTS is MANUAL you may choose to configure the SHED response of the
PID block.

Specific to Block LEVELCOMP


(s)
Description Level Value and Status
Data Type Structure
Range
Default
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PVP, PVSTS.
Parameters
Remarks Use this parameter to pass the status of the PV along with the PV value in all
input connections.

Specific to DIGACQ
Block(s)
Description PV Value and Status
Data Type Structure
Range
Default
Config Load NO
Active No
Loadable

- 2442 -
Chapter 18 - Pxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related PV, PVSTS.
Parameters
Remarks This parameter is used to pass the status of PV along with the PV value. The status
of the PV can be monitored by down stream block.

18.437 PVVALSTS[0..63]

Specific to Block REQNUMARRAY, RSPNUMARRAY


(s)
Description Array of (Real Value, Status) pairs. These values are obtained from the Status
of the last request.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PV, PVSTS.
Parameters
Remarks

18.438 PVVALSTS[1..64]

Specific to SINUMARRCH
Block(s)
Description PV Value and Status - Provides Numeric value from the device, along with a
Status field.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ERRFL, PVFL[1..512].
Parameters
Remarks This structure is automatically used when the block fetching PVFL[i] is capable of
interpreting the ValueStatus structure.

- 2443 -
Chapter 18 - Pxxxx Parameters

18.439 PVVALSTS[0..511]

Specific to SIFLAGARRCH
Block(s)
Description PV Value and Status - Provides Boolean value from the device, along with a
Status field.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ERRFL, PVFL[1..512].
Parameters
Remarks This structure is automatically used when the block fetching PVFL[i] is capable of
interpreting the ValueStatus structure.

Specific to RSPFLAGARRAY
Block(s)
Description An array of (Boolean Value, Status) pairs. These values are obtained from the value
of the corresponding PVFL and the Status of the last response.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

18.440 PWMPERIOD

Specific to Block(s) PWM Channel


Description PWM Period in Seconds
Data Type 64-Bit Real Number
Range N/A
Default 10
Config Load Yes

- 2444 -
Chapter 18 - Pxxxx Parameters

Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks PWMPERIOD is configured on the PWM Channel block.

18.441 PWMPERIOD[0..numChans-1]

Specific to Block(s) DOM


Description PWM Period in Seconds
Data Type 64-Bit Real Number
Range N/A
Default 10
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks PWMPERIOD is not configured on the DOM.

18.442 PWRGOOD1

Specific to Block RETENTIONTRIG


(s)
Description Power Good 1
Data Type BOOLEAN
Exposure In /Out

Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock View Only (Pull type connection)
Residence CEE
Related POWERCONNOPT, INVPWRGOOD1
Parameters
Remarks Status of Power Source 1. If INVPWRGOOD1 = OFF, PWRGOOD1 = ON indicates
power is good.

- 2445 -
Chapter 18 - Pxxxx Parameters

18.443 PWRGOOD2

Specific to Block RETENTIONTRIG


(s)
Description Power Good 2
Data Type BOOLEAN
Exposure In / Out
Range OFF, ON
Default OFF
Config Load NO
Active Loadable No
Access Lock View Only (Pull type connection)
Residence CEE
Related POWERCONNOPT, INVPWRGOOD2
Parameters
Remarks Status of Power Source 2. If INVPWRGOOD2 = OFF, PWRGOOD2 = ON indicates
power is good.

18.444 PWRSUPPLYSF

Specific to Block(s) ELCN_BRG, ELCN_NODE

Description Power Supply Alarm

Data Type Boolean

Range ON, OFF

Default OFF

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG, ELCN_NODE

Related Parameters SOFTFAIL

Remarks UEA power voltage not in normal operating range

18.445 PX[1..10]

Specific to Block(s) ENHREGCALC


Description PX Input - Shows the scaled input value for corresponding X input.
Data Type Float64
Range

- 2446 -
Chapter 18 - Pxxxx Parameters

Default NaN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2447 -
CHAPTER

19 QXXXX PARAMETERS

19.1 Q 2448
19.2 QDFL 2449
19.3 QUFL 2449
19.4 QIMPACTMAC 2450
19.5 QUALITYPARAM 2450
19.6 QUALITYVAL[0…80] 2451
19.7 QUALITYVALBIT[0…80][0…32] 2451

19.8 QUALPROGA 2451


19.9 QUALSTATE 2452
19.10 QUEUEDREQCNT[0..15] 2452
19.11 QUEUEFULLFL 2453
19.12 QUEUEID[1..n] 2453
19.13 QUEUEIDN[1..n] 2454
19.14 QUEUELOOKUP 2454
19.15 QUEUESIZE 2454
19.16 QSTS 2455

19.1 Q

Specific to Block(s) SR, RS


Description The Q output value.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 2448 -
Chapter 19 - Qxxxx Parameters

Specific to Block(s) FLOWCOMP


Description Steam Quality Factor Input - Shows value of the steam quality factor
Data Type Real
Range NaN or Greater that or equal to 0.0
Default 0
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence C200, C300, ACE
Related Parameters
Remarks

19.2 QDFL

Specific to Block(s) Up / Down Counter Block


Description Count Down Reached Flag
Data Type Boolean
Range FALSE, TRUE
Default FALSE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters CARRYUPFL, CARRYDNFL, QUFL, CNTEQN
Remarks This parameter reflects a comparison of the IN value with the current
count.

19.3 QUFL

Specific to Block(s) Up / Down Counter Block


Description Count Up Reached Flag
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Load No
Active Loadable No

- 2449 -
Chapter 19 - Qxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related CARRYUPFL, CARRYDNFL, QDFL, CNTEQN
Parameters
Remarks This parameter reflects a comparison of the IN value with the current count
value.

19.4 QIMPACTMAC

Specific to Block(s) QIPACCHAN


Description QiMPACT CNET MAC Address
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

19.5 QUALITYPARAM

Specific to Block(s) EIM


Description Quality Parameter
Data Type UINT32
Range 4294967295
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence NOLOAD
Related Parameters
Remarks

- 2450 -
Chapter 19 - Qxxxx Parameters

19.6 QUALITYVAL[0…80]

Specific to Block(s) EIM


Description Quality Value
Data Type UINT32
Range 4294967295
Default 65
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters QUALITYVALBIT, NUMQUALITY
Remarks Accessed as an array. Mapped to custom Quality parameters

19.7 QUALITYVALBIT[0…80][0…32]

Specific to Block EIM


(s)
Description Quality Bit Value
Data Type BOOLEAN
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related QUALITYVAL
Parameters
Remarks Accessed as a 2D array. Each bits of a Quality can be individually accessed
using this parameters.

19.8 QUALPROGA

Specific to RM
Block(s)
Description Qualification progress indication for each module in the host chassis
Data Type 8-Bit Unsigned Integer [20]
Range 0 to 255
Default 0

- 2451 -
Chapter 19 - Qxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence
Related
Parameters
Remarks

19.9 QUALSTATE

Specific to Block(s) UOC


Description Qualification State
Data Type STRING
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock APPDEVONLY
Residence SR
Related Parameters
Remarks

19.10 QUEUEDREQCNT[0..15]

Specific to Block(s) PCDI_MASTER


Description Queued Requests
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2452 -
Chapter 19 - Qxxxx Parameters

19.11 QUEUEFULLFL

Specific to SCM, RCM, UCM, CM


Block(s)
Description Waiting Queue is full
Data Type BOOLEAN
Range Off Queue is
not full
On Queue is
full
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This flag indicates, whether additional requests can be put into the
queue If QUEUESIZE=0 , then QUEUEFULLFL=AVAILFL

19.12 QUEUEID[1..n]

Specific to SCM, RCM, UCM. CM


Block(s)
Description Name of requesting block
Data Type BLOCKID
Range N = QUEUESIZE
Default NULL
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related QUEUESIZE
Parameters
Remarks All user interfaces will show the name of the object represented by this handle. The
array will be filled starting with 1. A fragmentation of the array will not occur.
Example: If QUEUEID[2]=NULL , than all QUEUEID[x> (greater than)2]=NULL.

- 2453 -
Chapter 19 - Qxxxx Parameters

19.13 QUEUEIDN[1..n]

Specific to Block(s) SCM, RCM, UCM. CM


Description Shows current queue,Identification of requester
Data Type 32-Bit Integer
Range n = QUEUESIZE
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters QUEUESIZE
Remarks Diagnostic parameter only, shall not be used in control strategies.

19.14 QUEUELOOKUP

Specific to ACT, MR, SCM, and RCM


Block(s)
Description Displays the ClusterID, EEC, and IOC of the requesting block.
Data Type String
Range 20 characters
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related QUEUEID[1..n]
Parameters
Remarks It is a parameter which is used in custom graphic to display the Cluster ID, EEC,
and IOC of the requesting block in the following format: ClusterID, EEC, IOC.

19.15 QUEUESIZE

Specific to SCM, RCM, UCM, CM


Block(s)
Description Queue Size - Maximum number or waiting requesters
Data Type INT32
Range 0 to 10
Default 0

- 2454 -
Chapter 19 - Qxxxx Parameters

Config Load PCM


Active No
Loadable
Access Lock AppDevOnly
Residence PCM
Related
Parameters
Remarks A value of 0 disables the queue. Deadlock recognition will only work with
requesters fitting into the queue.

19.16 QSTS

Specific to FLOWCOMP
Block(s)
Description Steam Quality Factor Input - Shows value
of the steam quality factor
Data Type Enumeration PVVALSTS
Range Bad (0): The PV value was bad and replaced
with NaN.
Uncertain (1): The status of the PV value is
uncertain, stored by a program.
Normal (2): The PV value is good.
Manual (3): The PV value was manually entered.
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, C300, ACE
Related
Parameters
Remarks

- 2455 -
CHAPTER

20 RXXXX PARAMETERS

20.1 RACK_NUMBER 2465


20.2 R 2466
20.3 RACK_TYPE 2467
20.4 RACYCIMRAVAIL 2468
20.5 RACYCIMRAVAILDISP 2468
20.6 RACYCIMRAVAILPEER 2469
20.7 RACYCIMRMAX 2469

20.8 RACYCIMRUSED 2470


20.9 RACYCIMRUSEDDISP 2470
20.10 RACYCIMRUSEDPEER 2471
20.11 RACYCLGREQAVAIL 2471
20.12 RACYCLRQAVAILDISP 2472
20.13 RACYCLRQAVAILPEER 2472
20.14 RACYCLGREQMAX 2473
20.15 RACYCLGREQUSED 2473
20.16 RACYCLRQUSED 2474
20.17 RACYCLRQUSEDDISP 2474
20.18 RACYCLRQUSEDPEER 2475
20.19 RACYCSMREQAVAIL 2475
20.20 RACYCSRQAVAILDISP 2476
20.21 RACYCSRQAVAILPEER 2476
20.22 RACYCSMREQMAX 2477
20.23 RACYCSMREQUSED 2477
20.24 RACYCSMRQUSED 2478
20.25 RACYCSRQUSEDDISP 2478
20.26 RACYCSRQUSEDPEER 2479
20.27 RAISEDEADTM 2479
20.28 RAISEDESC 2479
20.29 RAISELMFL 2480
20.30 RAISERATE 2480
20.31 RAISETIME 2481
20.32 RAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK] 2481

- 2456 -
Chapter 20 - Rxxxx Parameters

20.33 RAMPSOAK 2482


20.34 RAMSCRUBERRS 2482
20.35 RAMSWEEPERR 2484
20.36 RANGE[0..numChans-1] 2485
20.37 RATE 2486
20.38 RATEALARM[1..24] 2486
20.39 RATEALARM[1..200] 2487
20.40 RATE[1..24] 2487
20.41 RATE[1..200] 2488
20.42 RATIOBIAS 2488
20.43 RATIOCTL 2489
20.44 RATIOEM 2489
20.45 RBOPTION 2489
20.46 RBROCLM 2490

20.47 RCCONFREV 2491


20.48 RCDATASET 2491
20.49 RCDESC 2492
20.50 RCINSTNUM 2492
20.51 RCMAXINSTNUM 2492
20.52 RCMCOMPLETED 2493
20.53 RCNAME 2493
20.54 RCNAMEREF 2494
20.55 RCRPTID 2494
20.56 RCRPTTYPE 2494
20.57 RCVCNTA 2495
20.58 RCVCNTB 2495
20.59 RCVERRA 2496
20.60 RCVERRB 2496
20.61 RCVNONRDRFRAMECOUNT 2497
20.62 RCVRDRREQUESTCOUNT 2497
20.63 RCVRDRRESPONSECOUNT 2498
20.64 RCYCIMRAVAIL 2498
20.65 RCYCIMRAVAILDISP 2499
20.66 RCYCIMRAVAILPEER 2499
20.67 RCYCIMRMAX 2500
20.68 RCYCIMRUSED 2500
20.69 RCYCIMRUSEDDISP 2501
20.70 RCYCIMRUSEDPEER 2501
20.71 RCYCLGREQAVAIL 2502

- 2457 -
Chapter 20 - Rxxxx Parameters

20.72 RCYCLGREQMAX 2502


20.73 RCYCLGRQUSED 2502
20.74 RCYCLGREQUSEDCONN 2503
20.75 RCYCLRQAVAILDISP 2503
20.76 RCYCLRQAVAILPEER 2504
20.77 RCYCLRQUSED 2504
20.78 RCYCLRQUSEDDISP 2505
20.79 RCYCLRQUSEDPEER 2505
20.80 RCYCSMIOREQUSEDCONN 2506
20.81 RCYCSMREQAVAIL 2506
20.82 RCYCSMREQMAX 2506
20.83 RCYCSMRQUSED 2507
20.84 RCYCSMREQUSEDCONN 2507
20.85 RCYCSRQAVAILDISP 2508

20.86 RCYCSRQAVAILPEER 2508


20.87 RCYCSRQUSEDDISP 2509
20.88 RCYCSRQUSEDPEER 2509
20.89 RDEGRADALM 2510
20.90 RDERRALM.PR 2510
20.91 RDERRALM.SV 2511
20.92 RDISPAVGLPS [1...RDISPCONNMAX] 2511
20.93 RDISPAVGLPSCONN [1...RDISPCONNMAX] 2512
20.94 RDISPAVGPPS [1...RDISPCONNMAX] 2512
20.95 RDISPAVGPPSCONN [1...RDISPCONNMAX] 2513
20.96 RDISPCONN 2513
20.97 RDISPCONNMAX 2514
20.98 RDISPDEGIMRCONN [1...RDISPCONNMAX] 2514
20.99 RDISPDEGRADIMR [1...RPEERCONNMAX] 2515
20.100 RDISPMAXLPS [1...RDISPCONNMAX] 2515
20.101 RDISPMAXLPSCONN [1...RDISPCONNMAX] 2516
20.102 RDISPMAXPPS [1...RDISPCONNMAX] 2516
20.103 RDISPMAXPPSCONN [1...RDISPCONNMAX] 2517
20.104 RDISPHOST [1...RPEERCONNMAX] 2517
20.105 RDNAUTOSYNC 2517
20.106 RDNCAPABILITY 2518
20.107 RDNCHASSISID 2519
20.108 RDNCMPT 2520
20.109 RDNCNTCYCMAX 2522
20.110 RDNCNTCYCMAX[0…40] 2522

- 2458 -
Chapter 20 - Rxxxx Parameters

20.111 RDNCNTCYCTP 2523


20.112 RDNCOMMFAILFTE 2524
20.113 RDNCOMMFAILRDN 2524
20.114 RDNCTLABILITY 2524
20.115 RDNDELAYAVG 2525
20.116 RDNDELAYMAX 2526
20.117 RDNDEVICEIDX 2527
20.118 RDNHISTREASON [1...15] 2528
20.119 RDNHISTSTATE [1...15] 2568
20.120 RDNHISTTIME[1...15] 2578
20.121 RDNHISTREASON 2579
20.122 RDNHISTSTATE 2579
20.123 RDNINHIBITSYNC 2579
20.124 RDNISTIMEMAX 2585

20.125 RDNLINKACTIVE 2586


20.126 RDNLINKFAILED 2586
20.127 RDNLOS 2588
20.128 RDNMACADDR 2595
20.129 RDNNONTRKMAX 2596
20.130 RDNOPMFRZTIME 2597
20.131 RDNOPMSTATUS 2599
20.132 RDNPKTRCVAVG 2604
20.133 RDNPKTRCVMAX 2605
20.134 RDNPKTXMITAVG 2605
20.135 RDNPKTXMITMAX 2606
20.136 RDNROLESTATE 2606
20.137 RDNRCVAVG 2608
20.138 RDNRCVMAX 2608
20.139 RDNRXRATE 2609
20.140 RDNRXRATEMAX 2609
20.141 RDNSOTIMEMAX 2609
20.142 RDNSYNCPROG 2610
20.143 RDNSYNCSTATE 2611
20.144 RDNTXRATE 2613
20.145 RDNTXRATEMAX 2613
20.146 RDNXFERAVG 2613
20.147 RDNXFERMAX 2614
20.148 RDNXMITAVG 2615
20.149 RDNXMITMAX 2615

- 2459 -
Chapter 20 - Rxxxx Parameters

20.150 RDRRETRYCOUNT 2616


20.151 RDYFL 2616
20.152 READERROPT 2617
20.153 READERRORS 2617
20.154 READERRORSMAX 2617
20.155 READINESS 2618
20.156 READINESSA 2618
20.157 READPPS 2618
20.158 READPPSMAX 2619
20.159 READSPECFLAG 2619
20.160 READSTATUS 2619
20.161 READSTATUS 2620
20.162 REASONSET 2620
20.163 RECPDESC[1..50] 2621

20.164 RECLIMITOPT 2622


20.165 RECMATCODE[1..50] 2622
20.166 RECOVMSGIDX 2623
20.167 RECSCALE[1..50] 2623
20.168 RDNHISTTIME 2624
20.169 RECTARGET[1..50] 2624
20.170 RECTARGETMAX[1..50] 2625
20.171 RECTARGETMIN[1..50] 2625
20.172 RECTOEQMENB 2625
20.173 RECTOEQMMAP 2626
20.174 RECVCLOSEREQ 2626
20.175 RECVCLOSERSP 2627
20.176 RECVNAKS 2627
20.177 RECVOPENREQ 2628
20.178 RECVOPENRSP 2628
20.179 REDDATAA 2629
20.180 REDDATAB 2630
20.181 REDSWITCHPERIOD 2631
20.182 REDTAG 2631
20.183 REDUNDANCY_WARNING 2633
20.184 REDUNDANT 2633
20.185 REDUNSTATE 2634
20.186 REDUNSTATEA 2634
20.187 REEXECOPT 2635
20.188 REEXECOPTOG 2636

- 2460 -
Chapter 20 - Rxxxx Parameters

20.189 REEXECOPTOH 2637


20.190 REEXECOPTOS 2639
20.191 REEXECPOLICY 2640
20.192 REFCOUNT 2640
20.193 REFRESHMS 2641
20.194 REJFACTOR 2641
20.195 REF 2642
20.196 REFTYPE 2642
20.197 REGCALC 2643
20.198 REGCTLOFFMODE 2643
20.199 REGCTLOFFMODEATTR 2644
20.200 REGCTLONMODE 2644
20.201 REGCTLONMODEATTR 2644
20.202 RegCtlStrategy 2645

20.203 REGCTLTARGETPARAM 2645


20.204 REGHASENAME 2646
20.205 REGREGISTERED 2646
20.206 REGTARGETBLK 2646
20.207 REGTARGETOPTMASK 2647
20.208 RELAYPRESENT 2647
20.209 RELOADINIDLY 2648
20.210 RELEASEOPT 2648
20.211 REMCAS 2649
20.212 REMCASTYPE 2649
20.213 REMOTESWITCH 2650
20.214 REMSOAKTIME 2650
20.215 REQ.ACQSTATE[1..100] 2651
20.216 REQ.CMDREQ.OUT[1..100] 2651
20.217 REQ.CMDREQSTS[1..100] 2652
20.218 REQ.EQUIPNAME[1..100] 2652
20.219 REQ.OUTDEST[1..100] 2652
20.220 REQ.OWNERSSRC[1..100] 2653
20.221 REQ.OWNERSSTS[1..100] 2653
20.222 REQ.OWNFL[1..100] 2654
20.223 REQ.REQFL[1..100] 2654
20.224 REQ.RELFL[1..100] 2654
20.225 REQEXECID[1..15] 2655
20.226 REQORDER 2655
20.227 REQRSPRCVD 2656

- 2461 -
Chapter 20 - Rxxxx Parameters

20.228 REQRTRY 2656


20.229 REQRTRYCNT[0..15] 2656
20.230 REQSTATE 2657
20.231 REQUSTEDSCANTIME 2658
20.232 RESADDR[1..15] 2658
20.233 RESAVEPERIOD 2659
20.234 RESADDRFUTUR[1..15] 2659
20.235 RESADDRFUTRN[1..15] 2660
20.236 RESADDRN[1..15] 2660
20.237 RESET 2661
20.238 RESETDEVDROPOFF 2663
20.239 RESETEIMNAME 2663
20.240 RESETERRORSCMD 2663
20.241 RESETFIRSTUP 2664

20.242 RESETFL 2664


20.243 RESETFL[0..7] 2667
20.244 RESETHCOMERR 2667
20.245 RESETMODE[0..numChans-1] 2668
20.246 RESETMODEL 2668
20.247 RESETSTAT 2669
20.248 RESETTIMER 2670
20.249 RESETVAL 2670
20.250 RESPTIMEAVG 2671
20.251 RESPTIMEMAX 2671
20.252 RESPTIMEMIN 2671
20.253 RESTART 2672
20.254 RESTARTFL 2673
20.255 RESTARTOPT 2674
20.256 RETAINISTS 2674
20.257 RETENDATAATTND 2675
20.258 RETENSAVEENABLED 2676
20.259 RETENSAVETIME 2676
20.260 RETENTIONSAVEFREEZE 2677
20.261 RETENVETOREASON 2677
20.262 RETRANSMISSIONSZ 2680
20.263 RETRYOPT 2680
20.264 RETRYSCURR 2681
20.265 RETRYSTOTAL 2681
20.266 RFB 2682

- 2462 -
Chapter 20 - Rxxxx Parameters

20.267 RG 2682
20.268 RHPWEIGHTS 2682
20.269 RJRAW 2683
20.270 RJTEMP 2683
20.271 RLSRESABNORM 2684
20.272 RLSRESNORM 2684
20.273 RMW 2685
20.274 ROCLM 2685
20.275 ROCLMOPT 2686
20.276 ROCNEGALM.FL 2686
20.277 ROCNEGALM.PR 2687
20.278 ROCNEGALM.SV 2687
20.279 ROCNEGALM.TM 2688
20.280 ROCNEGALM.TMO 2688

20.281 ROCNEGALM.TP 2689


20.282 ROCPOSALM.FL 2689
20.283 ROCPOSALM.PR 2690
20.284 ROCPOSALM.SV 2690
20.285 ROCPOSALM.TM 2691
20.286 ROCPOSALM.TMO 2691
20.287 ROCPOSALM.TP 2692
20.288 ROCSAFELM 2692
20.289 ROLE 2692
20.290 ROLLAVGBAD 2693
20.291 ROLLAVGOK 2693
20.292 ROLLAVGRST 2694
20.293 ROLLAVGSZ 2694
20.294 ROLLBFBASE 2695
20.295 ROLLBUF 2695
20.296 ROLLFRBASE 2696
20.297 ROLLFREQ 2697
20.298 ROLLMULTIPLE 2697
20.299 ROMAPPIMGCHKSMFAIL 2698
20.300 ROMBOOTIMGCHKSMFAIL 2698
20.301 RP 2699
20.302 RPEERAVGLPS [1...RPEERCONNMAX] 2699
20.303 RPEERAVGLPSCONN [1...RPEERCONNMAX] 2700
20.304 RPEERAVGPPS [1...RPEERCONNMAX] 2700
20.305 RPEERAVGPPSCONN [1...RPEERCONNMAX] 2701

- 2463 -
Chapter 20 - Rxxxx Parameters

20.306 RPEERCONN 2701


20.307 RPEERCONNMAX 2702
20.308 RPEERDEGIMRCONN [1...RPEERCONNMAX] 2702
20.309 RPEERDEGRADIMR[1..RPEERCONNMAX] 2703
20.310 RPEERMAXLPS [1..RPEERCONNMAX] 2703
20.311 RPEERMAXLPSCONN [1...RPEERCONNMAX] 2704
20.312 RPEERMAXPPS [1...RPEERCONNMAX] 2704
20.313 RPEERMAXPPSCONN [1...RPEERCONNMAX] 2705
20.314 RPEERNAME[1...RPEERCONNMAX] 2705
20.315 RPEERNAMELOOKUP 2706
20.316 RPEERSUBPER[1...RPEERCONNMAX] 2706
20.317 RPHYCONNID 2707
20.318 RPTCONNECTIONSTATE 2707
20.319 RPTENABLEFAILURE 2707

20.320 RQ 2708
20.321 RRRCEESTATE 2708
20.322 RSPPIN 2709
20.323 RSTERRCNT 2709
20.324 RSTPROCESSED 2710
20.325 RSTRTINIDLY 2710
20.326 RSTSTATS 2711
20.327 RT 2712
20.328 RTABLE.DIAG[1..5000] 2712
20.329 RTABLE.PART[1..5000] 2713
20.330 RTABLE.PARTN[1..5000] 2713
20.331 RTABLE.PEER[1..5000] 2714
20.332 RTABLE.STATE[1..5000] 2714
20.333 RTABLE.STATE[1..5000] 2715
20.334 RTABLENROWS 2715
20.335 RTABLEUROWS 2715
20.336 RTABLEIDX 2716
20.337 RTBACKCALOUT 2716
20.338 RTCONN 2717
20.339 RTDTYPE 2717
20.340 RTHIFL 2718
20.341 RTHILM 2719
20.342 RTLOFL 2719
20.343 RTLOLM 2719
20.344 RTOTACYCIMR 2720

- 2464 -
Chapter 20 - Rxxxx Parameters

20.345 RTOTACYCLGREQ 2720


20.346 RTOTACYCSMREQ 2721
20.347 RTOTCYCIMR 2721
20.348 RTOTCYCLGREQ 2722
20.349 RTOTCYCSMREQ 2722
20.350 RTPPRESENT 2722
20.351 RUNBKACTALM.FL 2723
20.352 RUNBKACTALM.PR 2723
20.353 RUNBKACTALM.SV 2724
20.354 RUNBKACTFL 2724
20.355 RUNPULSEWIDTH 2724
20.356 RUNTIME 2725
20.357 RV 2725
20.358 RX 2726

20.1 RACK_NUMBER

Specific to Block(s) Controller Rack, IO RACK


Description Rack Number
Data Type ENUM
Range
0 0 Controller Rack Only (Default for Controller Rack)

1 1 First Index

2 2 Second Index

3 3 Third Index

4 4 Fourth Index

5 5 Fifth Index

6 6 Sixth Index

7 7 Seventh Index

8 8 Eighth Index

9 9 Ninth Index

10 10 Tenth Index

11 11 Eleventh Index

12 12 Twelfth Index

13 13 Blank (Default for IO RACK)

Default 0 for Controller Rack and 13 for IO RACK


Config Load Yes

- 2465 -
Chapter 20 - Rxxxx Parameters

Active Loadable No
Access Lock APPDEVONLY
Residence CEE
Related Parameters IORACK_SCANRATE, TOPOLOGY
Remarks Unique number used by CPM to identify the IO RACK.

Specific to Block(s) Controller Rack, IO RACK


Description Rack Number
Data Type ENUM
Range
0 Controller Rack Only (Default for Controller Rack)

1 Rack Number 1

2 Rack Number 2

3 Rack Number 3

4 Rack Number 4

5 Rack Number 5

6 Rack Number 6

7 Rack Number 7

8 Rack Number 8

9 Rack Number 9

10 Rack Number 10

11 Rack Number 11

12 Rack Number 12

13 Blank (Default for IO RACK)

Default 0 for Controller Rack and 13 for IO RACK


Config Load Yes
Active Loadable -
Access Lock APPDEVONLY
Residence Controller Rack, IO RACK
Related Parameters IORACK_SCANRATE, TOPOLOGY
Remarks Unique number used by CPM to identify the IO RACK

20.2 R
It is not recommended to use step outputs of type S_IEC, N_IEC, or R_IEC with destination
parameters that are inputs to flip-flops or other bistable, monostable blocks, or logic
configurations. Examples are OPCMD[0..2] of DEVCTL and S and R of LOGIC:RS. Although these
configurations are technically supported and show a predicatable behavior, the resulting behavior
may be non-intuitive and confusing to operators (example: using an N_IEC output on OPCMD[1]
will result in OP-behavior similar to what would be expected from an S_IEC output if directly
controlling a parameter such as OP). Therefore, this practice is not considered a good engineering

- 2466 -
Chapter 20 - Rxxxx Parameters

practice.

Specific to Block(s) SR, RS


Description The R input value.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

20.3 RACK_TYPE

Specific to Block(s) Controller Rack, IO RACK


Description Rack Type
Data Type ENUM
Range
15 4 SLOTS Rack contained four IOM slots

11 8 SLOTS Rack contains eight IOM slots

9 12 SLOTS Rack contains twelve IOM slots

Default 4 SLOTS
Config Load Yes
Active Loadable No
Access Lock APPDEVONLY
Residence CEE
Related Parameters

Remarks IO rack model designated by the number of available IO module slots.

Specific to Block(s) Controller Rack, IO RACK


Description Rack Type
Data Type ENUM
Range
15 4 SLOTS Four slot rack

11 8 SLOTS Eight slot rack

9 12 SLOTS Twelve slot rack

Default 4 SLOTS
Config Load Yes

- 2467 -
Chapter 20 - Rxxxx Parameters

Active Loadable -
Access Lock APPDEVONLY
Residence Controller Rack, IO RACK
Related Parameters

Remarks IO rack model designated by the number of available IO module slots.

20.4 RACYCIMRAVAIL

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Acyclic IMR Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Inter-process Message Structure (IMR) is used to pass information between
the control object adapter and the control kernel object manager for
communications across the network

20.5 RACYCIMRAVAILDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic IMR Available Display - The number of available display acyclic
IMRs.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable

- 2468 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

20.6 RACYCIMRAVAILPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic IMRs Available Peer - The current number of available peer
acyclic IMRs.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

20.7 RACYCIMRMAX

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Maximum Acyclic IMRs
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable

- 2469 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

20.8 RACYCIMRUSED

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Acyclic Lists in Use
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

20.9 RACYCIMRUSEDDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic IMR Used Display - The current number of display acyclic IMRs
used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable

- 2470 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

20.10 RACYCIMRUSEDPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic IMR Used Peer - The current number of peer acyclic IMRs used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

20.11 RACYCLGREQAVAIL

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Acyclic Large Requests Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No

- 2471 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Responder Acyclic Large Requests Available

20.12 RACYCLRQAVAILDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic Large Requests Available Display - The current number of
available display acyclic large requests.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.13 RACYCLRQAVAILPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic Large Requests Available Peer - The current number of
available peer acyclic large requests.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 2472 -
Chapter 20 - Rxxxx Parameters

20.14 RACYCLGREQMAX

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Maximum Acyclic Large Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Responder Maximum Acyclic Large Requests

20.15 RACYCLGREQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300


(s)
Description Responder Acyclic Large Requests Used - The current number of acyclic large
requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM
Related
Parameters
Remarks

- 2473 -
Chapter 20 - Rxxxx Parameters

20.16 RACYCLRQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Responder Acyclic Large Requests in Use
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Responder Acyclic Large Requests in Use.

20.17 RACYCLRQUSEDDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic Large Requests Used Display - The current number of display
acyclic large requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 2474 -
Chapter 20 - Rxxxx Parameters

20.18 RACYCLRQUSEDPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic Large Requests Used Peer - The current number of peer
acyclic large requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.19 RACYCSMREQAVAIL

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Acyclic Small Requests Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

- 2475 -
Chapter 20 - Rxxxx Parameters

20.20 RACYCSRQAVAILDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic Small Requests Available Display - The current number of
available display acyclic small requests.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.21 RACYCSRQAVAILPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic Small Requests Available Peer - The current number of
available peer acyclic small requests.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 2476 -
Chapter 20 - Rxxxx Parameters

20.22 RACYCSMREQMAX

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Description Maximum Acyclic Small Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC),
CN100(CEECN100)
Related
Parameters
Remarks

20.23 RACYCSMREQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Acyclic Small Requests in Use
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

- 2477 -
Chapter 20 - Rxxxx Parameters

20.24 RACYCSMRQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC


(s)
Description Responder Acyclic Small Requests Used - The current number of acyclic small
requests in use.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC)
Related
Parameters
Remarks

20.25 RACYCSRQUSEDDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder C Acyclic Small Requests Used Display - The current number of
display acyclic small requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 2478 -
Chapter 20 - Rxxxx Parameters

20.26 RACYCSRQUSEDPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Acyclic Small Requests Used Peer - The current number of peer
acyclic small requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.27 RAISEDEADTM

Specific to Block(s) PosProp, PidPosProp


Description Raise Dead Time (in seconds).
Data Type Real
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

20.28 RAISEDESC

Specific to Block(s) PosProp, PidPosProp


Description Raise Output Descriptor.
Data Type String
Range
Default “Raise”
Config Load Yes

- 2479 -
Chapter 20 - Rxxxx Parameters

Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters
Remarks

20.29 RAISELMFL

Specific to PosProp, PidPosProp


Block(s)
Description Raise Pulse Limit Flag - Used to inhibit Raise pulses by the PosProp function block
and is pulled from another function block.
Data Type Boolean
Range Off (0): Allow raise pulse output. On (1): Inhibit raise pulse output.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related
Parameters
Remarks

20.30 RAISERATE

Specific to Block(s) PosProp, PidPosProp


Description Raise Output Pulse Rate - The raise stroke rate (in percent per second).
Data Type Real
Range 0.0 to 100.0
Default 100%/sec.
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

- 2480 -
Chapter 20 - Rxxxx Parameters

20.31 RAISETIME

Specific to Block(s) PosProp, PidPosProp


Description Raise Output Pulse Time (in seconds).
Data Type Real
Range MINPULSER, Lesser of MAXPULSER and CYCLETIME.
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters MINPULSER
Remarks If RAISETIME < MINPULSER, no raise pulse is issued.

20.32 RAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK]

Specific to RampSoak
Block(s)
Description Ramp Rate (in EUs per minute) - The target ramp rates, specified by the user.
There is one ramp rate per Ramp/Soak pair in a profile.
Data Type Real
Range N/A
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related NUMPROFILES, NUMRAMPSOAK[1..NUMPROFILES], SOAKTIME
Parameters [1..NUMPROFILES][1..NUMRAMPSOAK], SOAKVAL[1..NUMPROFILES]
[1..NUMRAMPSOAK], STARTOPT, STARTSEG[1..NUMPROFILES].
Remarks Negative values are accepted to allow ramping down.

- 2481 -
Chapter 20 - Rxxxx Parameters

20.33 RAMPSOAK

Specific to HRBALG_REG block


Blocks
Description RAMPSOAK FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the RAMPSOAK block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

20.34 RAMSCRUBERRS

Specific to C200, C300, FIM4, PGM, EHPM


Block(s)
Description Corrected RAM Sweep - Indicates status of detected RAM errors.
Data Type Boolean
Range Off (0) No RAM
errors
detected.
On (1) RAM
errors
detected
and
corrected.

Default Off (0)


Config No
Load
Active No
Loadable

- 2482 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence C200(CPM), C300, FIM4, PGM, EHPM
Related RAMSWEEPERR
Parameters
Remarks Errors detected within DRAM are corrected through a scrub operation.
Detected error count should remain low. However, if it gets above a
certain threshold, this parameter is set to On. When RAMSCRUBERRS
goes On, the module function block issues a diagnostic alarm.

Specific to Block(s) EIM


Description Corrected Internal RAM Sweep Error
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks True if a correctable memory error has been detected within the last 24
hours.

Specific to UOC
Block(s)
Description Corrected Internal RAM Sweep Error
Data Type BOOLEAN
Exposer OUTPUT
Range NA
Default Off
Config Load No
Active
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks Soft failure condition. Main RAM correctable error detected. Normal operation is
possible. Condition will return to normal if no further correctable errors are
detected within 24 hours.

- 2483 -
Chapter 20 - Rxxxx Parameters

20.35 RAMSWEEPERR

Specific to C200, C300, PGM, FIM4, EHPM


Block(s)
Description Uncorrectable RAM Sweep - Indicates status of detected RAM errors.
Data Type Boolean
Range Off (0) No RAM
errors
detected.
On (1) RAM errors
detected but
unable to
correct.
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200(CPM), C300, FIM4, PGM, EHPM
Related RAMSCRUBERRS
Parameters
Remarks When On, indicates the presence of one or more single bit memory
faults which could not be corrected by the DRAM scrub process.
When RAMSWEEPERR goes On, the module function block issues a
diagnostic alarm.

Specific to Block(s) EIM


Description Uncorrectable Internal RAM Sweep Error
Data Type BOOLEAN
Range NA
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks True if an uncorrectable memory error has been detected.

Specific to Block(s) UOC


Description Uncorrectable Internal RAM Sweep Error
Data Type BOOLEAN
Exposure OUTPUT
Range NA
Default Off

- 2484 -
Chapter 20 - Rxxxx Parameters

Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks Soft failure condition. Main RAM uncorrectable error detected.

20.36 RANGE[0..numChans-1]

Specific to l 1738-IE2CM12
Block(s)
l 1738-1E4CM12
l 1738-OE2CM12
l 1738-OE4CM12
l 1732E-IF4M12R
l 1732E-OF4M12R
Description Range — This parameter is part of configuration assembly for this module and it
indicates the operating range of the module.
Data Type ENUM
Range l For 1738-OE2CM12 and 1738-OE4CM12
l 0 : 4-20 mA
l 2 : 0-20 mA

l For 1738-IE2CM12 and 1738-IE4CM12


l 3 : 4-20 mA
l 8 : 0-20 Ma

l For 1732E-OF4M12R
l 1 : 0V to 10V
l 3 : -10V to 10
l 4 : 0V to 5V
l 5 : 0V to 5V
l 2 : 0mA to 20mA
l 0 : 4mA to 20mA

l For 1732E-IF4M12R
l 2 : 0V to 10V
l 0 : -10V to 10V
l 1 : 0V to 5V
l 6 : -5V to 5V
l 8 : 0mA to 20mA
l 3 : 4mA to 20mA
Default The default value for 1732E-OF4M12R is 0V to 10V and for all the other blocks, the
default value is 4-20 mA.

- 2485 -
Chapter 20 - Rxxxx Parameters

Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related
Parameters
Remarks

20.37 RATE

Specific to Pulse Input Totalizer


Block(s)
Description PI Input Flow Rate in Engineering Units/TIMEBASE. This value is used in Analog
Operation algorithm, when P1 input goes Bad.
Data Type Real
Range NAN, or greater-than or equal-to zero.
Default 0.0
Config No
Load
Active No
Loadable
Access Lock View Only
Residence CEE
Related
Parameters
Remarks RATEi = C1/C2 * (P1(i) - P1(i-1)) / TS where: P1i = The P1 input of this block from the
current pass in Counts. P1(i-1) = The P1 input of this block from the last processing
pass in Counts. C1 = Dimensionless scale factor C2 = Unit normalizer in Counts per
Engineering Units TS = Sample Time in TIMEBASE units, hence:
l TS = CM Execution Period in sec if TIMEBASE is seconds
l TS = CM Execution Period in sec / (60sec/min) if TIMEBASE is minutes
l TS = CM Execution Period in sec / (3600sec/hr) if TIMEBASE is hours

20.38 RATEALARM[1..24]

Specific to Block QIPACTERM


Description Fast Feed Rate Alarm
Data Type Boolean
Range Off(0) OK
On(1) Alarm
Default 0

- 2486 -
Chapter 20 - Rxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 11 of the Status 2 word in the input assembly for the
designated position [1-24].

20.39 RATEALARM[1..200]

Specific to QIPACCHAN
Block
Description Fast Feed Rate Alarm
Data Type Boolean
Range Off(0) OK
On(1) Alarm
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 11 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

20.40 RATE[1..24]

Specific to Block QIPACTERM


Description Rate of Change of Weight
Data Type Float64
Range N/A
Default NAN
Config Load No
Active Loadable No

- 2487 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks This is the value in the input assembly for the designated position [1-24].

20.41 RATE[1..200]

Specific to Block QIPACCHAN


Description Rate of Change of Weight
Data Type Float64
Range N/A
Default NAN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value in the input assembly for the designated channel [1-200] in
the QiMPACT cluster.

20.42 RATIOBIAS

Specific to HRBALG_REG block


Blocks
Description RATIOBIAS FB reference
Data Type BLOCKID
Range Not applicable

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the RATIOBIAS block in the emulation CM if
the algorithm type is PIDRATIO.

- 2488 -
Chapter 20 - Rxxxx Parameters

20.43 RATIOCTL

Specific to HRBALG_REG block


Blocks
Description RATIOCTL FB reference
Data Type BLOCKID
Range Not applicable

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the RATIOCTL block in the emulation CM if
the algorithm type is AUTORATIO/AUTOBIAS.

20.44 RATIOEM

Specific to Blocks Regulatory HRB


Description Ratio
Data Type FLOAT 64
Range
Default NaN
Config. Load No
Access Lock Operator
Residence NO LOAD
Related
Parameters
Remarks This parameter represents ratio of the algorithm supporting ratio on the
algorithm HRB

20.45 RBOPTION

Specific to RATIOBIAS
Block
Description Ratio Bias Option - Select desired ratio/bias operation.
Data Type Enumeration
Range FixedRatioBias During initialization, it is back calculated as
follows, INITVAL (X1) = (OP - OPBIAS.FIX) / RT
INITVAL (RT) = (OP - OPBIAS.FIX) / X1 In Auto
mode, the RT and BIAS values are set by the

- 2489 -
Chapter 20 - Rxxxx Parameters

operator or a user program. In Cascade mode,


the RT value is fetched from the upstream
function block only. The BIAS is set by the
operator or a user program.
AutoRatio During initialization, the RT value is not
fetched or settable. It is back calculated as
follows: RT = (OP - OPBIAS.FIX) / X1. If X1 is
zero in Auto mode, RT = INITVAL(RT). Clamp RT
within RT limits. The BIAS can be set by the
operator or a user program. INITVAL (X1) = (OP
- OPBIAS.FIX) / RT INITVAL (RT) = (OP -
OPBIAS.FIX) / X1
AutoBias During initialization, BIAS is not fetched or
settable. It is back calculated as follows: BIAS =
OP - (RT*X1) Clamp BIAS within BIAS limits.
INITVAL (X1)= (OP - OPBIAS.FIX) / RT INITVAL
(RT) = (OP - OPBIAS.FIX) / X1 In Auto mode,
the RT value is set by the operator or a user
program only. In Cascade mode, the RT value
is fetched from the upstream function block
only.
Default FixedRatioBias
Config Yes
Load
Active No
Loadable
Access Operator
Lock
Residence CEE
Related BSLOLMBSHILMOPBIAS.FIX
Parameters
Remarks In normal Auto mode operation, the RT and BIAS values are set by the operator or a
user program regardless of the RBOPTION selection. In normal Cascade mode
operation, the RT value is fetched from the upstream function block and the BIAS
value is set by the operator or a user program regardless of the RBOPTION
selection. When the RBOPTION is set to FixedRatioBias, the OPBIAS.FIX value is
limited to a range between BSLOLM and BSHILM (-50.0 to 50.0, by default). If you
enter any values outside this range an error message appears.

20.46 RBROCLM

Specific to GRPCAPRBK
Block(s)
Description Runback Rate of Change Limit.
Data Type IEEEFloat64
Range NA
Default NaN
Config Load YES
Active No
Loadable

- 2490 -
Chapter 20 - Rxxxx Parameters

Access Lock Engineer


Residence CEE
Related
Parameters
Remarks The Rate of Change Limit value for RUNBACK state. This value will is assigned to
OUTCAP in Runback active state.

20.47 RCCONFREV

Specific to Block(s)
Description Config Revision
Data Type UINT32
Range 4294967295
Default 0
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence EIM
Related
Parameters
Remarks Configuration Revision number of the Report. This is read from the CID/ICD
file.

20.48 RCDATASET

Specific to Block(s)
Description Data Set
Data Type STRING
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence EIM
Related Parameters
Remarks Dataset name of the MMS report. This read from CID/ICD file.

- 2491 -
Chapter 20 - Rxxxx Parameters

20.49 RCDESC

Specific to Block(s)
Description Description
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ERDBONLY
Related Parameters
Remarks

20.50 RCINSTNUM

Specific to Block(s)
Description Instance Number
Data Type UINT32
Range 4294967295
Default 0
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

20.51 RCMAXINSTNUM

Specific to Block(s)
Description Max Instance Number
Data Type UINT32
Range 4294967295
Default 1
Config Load No
Active Loadable No

- 2492 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence CEESR
Related Parameters
Remarks

20.52 RCMCOMPLETED

Specific to Block(s) RCM


Description Confirm Receiving RCM Completion Event
Data Type 64-Bit Unsigned Integer
Range
Default
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence
Related Parameters
Remarks

20.53 RCNAME

Specific to Block(s)
Description Name
Data Type STRING
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence EIM
Related Parameters
Remarks

- 2493 -
Chapter 20 - Rxxxx Parameters

20.54 RCNAMEREF

Specific to Block(s)
Description Report Name Ref
Data Type STRING
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence EIM
Related Parameters
Remarks

20.55 RCRPTID

Specific to Block(s)
Description Report ID
Data Type STRING
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence EIM
Related Parameters
Remarks Object Reference of the Report. This is read from the CID file.

20.56 RCRPTTYPE

Specific to Block(s)
Description Type
Data Type ENUM
Range NA
Default NOT DEFINED
Config Load
Active Loadable No

- 2494 -
Chapter 20 - Rxxxx Parameters

Access Lock AppDevOnly


Residence EIM
Related Parameters
Remarks This will describe if the Report is Buffered or Un-Buffered

20.57 RCVCNTA

Specific to Block(s) ELCN_BRG

Description Total A Packets Received

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics

Remarks

20.58 RCVCNTB

Specific to Block(s) ELCN_BRG

Description Total B Receive Errors

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics

Remarks

- 2495 -
Chapter 20 - Rxxxx Parameters

20.59 RCVERRA

Specific to Block(s) ELCN_BRG

Description Total A Receive Errors

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics

Remarks

20.60 RCVERRB

Specific to Block(s) ELCN_BRG

Description Total B Receive Errors

Data Type 32-Bit Integer

Range

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_BRG

Related Parameters ELCN Bridge Statistics

Remarks

- 2496 -
Chapter 20 - Rxxxx Parameters

20.61 RCVNONRDRFRAMECOUNT

Specific to Block EHPM


(s)
Description Count of non-RDR frames (per second) that include responses but not RWR
requests.
Data Type UINT32
Exposure NONE
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence EHPM
Related N/A
Parameters
Remarks

20.62 RCVRDRREQUESTCOUNT

Specific to EHPM
Block(s)
Description Number of RDR request counts. Receive RDR per second (raw counts with rate
conversion which represent EHPM data/message transfer counts).
Data Type UINT32
Exposure NONE
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence EHPM
Related N/A
Parameters
Remarks Raw counts with rate conversion which represent EHPM data/message transfer
counts.

- 2497 -
Chapter 20 - Rxxxx Parameters

20.63 RCVRDRRESPONSECOUNT

Specific to EHPM
Block(s)
Description Number of responses in RDR per second. Send RDR/second (raw counts with rate
conversion which represent EHPM data/message transfer counts).
Data Type UINT32
Exposure NONE
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence EHPM
Related N/A
Parameters
Remarks Raw counts with rate conversion which represent EHPM data/message transfer
counts.

20.64 RCYCIMRAVAIL

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Cyclic IMR Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Inter-process Message Structure (IMR) is used to pass information between
the control object adapter and the control kernel object manager for
communications across the network.

- 2498 -
Chapter 20 - Rxxxx Parameters

20.65 RCYCIMRAVAILDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic IMR Available Display - The number of available display cyclic
IMRs.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

20.66 RCYCIMRAVAILPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic IMRs Available Peer - The current number of available peer cyclic
IMRs.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

- 2499 -
Chapter 20 - Rxxxx Parameters

20.67 RCYCIMRMAX

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Maximum Cyclic IMRs.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Inter-process Message Structure (IMR) is used to pass information between
the control object adapter and the control kernel object manager for
communications across the network.

20.68 RCYCIMRUSED

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Cyclic IMR Used.
Data Type 32-Bit Integer
Exposure Output
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

- 2500 -
Chapter 20 - Rxxxx Parameters

20.69 RCYCIMRUSEDDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic IMR Used Display - The current number of display cyclic IMRs
used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

20.70 RCYCIMRUSEDPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cylic IMR Used Peer - The current number of peer cyclic IMRs used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks The Interprocess Message Structure (IMR) is used to pass information between the
control object adapter and the control kernel object manager for communications
across the network.

- 2501 -
Chapter 20 - Rxxxx Parameters

20.71 RCYCLGREQAVAIL

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Cyclic Large Requests Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.72 RCYCLGREQMAX

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Responder Cyclic Large Requests Maximum
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.73 RCYCLGRQUSED

Specific to Block(s) CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC


Description Cyclic Large Requests in Use
Data Type 32-Bit Integer
Range Greater than or equal to 0

- 2502 -
Chapter 20 - Rxxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC)
Related Parameters
Remarks

20.74 RCYCLGREQUSEDCONN

Specific to Block(s) CEE, IOLINK


Description Cyclic Large Requests Per connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), CN100(IOLINK)
Related Parameters
Remarks

20.75 RCYCLRQAVAILDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic Large Requests Available Display - The current number of
available display cyclic large requests.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 2503 -
Chapter 20 - Rxxxx Parameters

20.76 RCYCLRQAVAILPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic Large Requests Available Peer - The current number of
available peer cyclic large requests.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.77 RCYCLRQUSED

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Responder Cyclic Large Requests Used
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

- 2504 -
Chapter 20 - Rxxxx Parameters

20.78 RCYCLRQUSEDDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic Large Requests Used Display - The current number of display
cyclic large requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.79 RCYCLRQUSEDPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic Large Requests Used Peer - The current number of peer
cyclic large requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 2505 -
Chapter 20 - Rxxxx Parameters

20.80 RCYCSMIOREQUSEDCONN

Specific to Block(s) CEE, IOLINK, CEECN100


Description Cyclic Small IO Requests Per connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), CN100(IOLINK)
Related Parameters
Remarks

20.81 RCYCSMREQAVAIL

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Cyclic Small Requests Available
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.82 RCYCSMREQMAX

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Maximum Cyclic Small Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No

- 2506 -
Chapter 20 - Rxxxx Parameters

Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.83 RCYCSMRQUSED

Specific to CEEFB,CEEACEFB,CEESIMC200FB,FIM,FIMS,OPC,ICG,IOLIM,IOLIMS,
Block(s) CEEC300,GEEFB, CEEUOC, CEECN100
Description Cyclic Small Requests in Use
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence
Related
Parameters
Remarks Responder Cyclic Small Requests Used - The current number of cyclic small
requests used

20.84 RCYCSMREQUSEDCONN

Specific to Block(s) CEE, IOLINK, CEECN100


Description Cyclic Small Requests Per connection
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300), CN100(IOLINK)
Related Parameters
Remarks

- 2507 -
Chapter 20 - Rxxxx Parameters

20.85 RCYCSRQAVAILDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic Small Requests Available Display - The current number of
available display cyclic small requests.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.86 RCYCSRQAVAILPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic Small Requests Available Peer - The current number of
available peer cyclic small requests.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 2508 -
Chapter 20 - Rxxxx Parameters

20.87 RCYCSRQUSEDDISP

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic Small Requests Used Display - The current number of display
cyclic small requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.88 RCYCSRQUSEDPEER

Specific to CEE, IOLIM, FIM


Block(s)
Description Responder Cyclic Small Requests Used Peer - The current number of peer
cyclic small requests used.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

- 2509 -
Chapter 20 - Rxxxx Parameters

20.89 RDEGRADALM

Specific to Block CEEC300, CEE, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Comm Degraded to Req/Resp
Data Type Boolean
Range
Default False
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.90 RDERRALM.PR

Specific to CAB types


Block(s)
Description Read Error Alarm.Priority. Sets the priority of the alarm notification if a read error
alarm is reported. Engineer can change this value at run time.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Enumeration ALPRIOR
Range NONE, JOURNAL, LOW, HIGH, URGENT
Default JOURNAL
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related READSTATUS, READERROPT
Parameters
Remarks

- 2510 -
Chapter 20 - Rxxxx Parameters

20.91 RDERRALM.SV

Specific to CAB types


Block(s)
Description Read Error Alarm.Severity. Sets the severity of the alarm notification if a read
error alarm is reported. Engineer can change this value at run time.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type 16-Bit Integer
Range 0-15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related READSTATUS, READERROPT
Parameters
Remarks

20.92 RDISPAVGLPS [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Average Display IMRs/Sec
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RDISPMAXLPS
Parameters
Remarks Report By Exception Display Average IMRs Per Second - The average number of
display peer messages per second sent on the wire.

- 2511 -
Chapter 20 - Rxxxx Parameters

20.93 RDISPAVGLPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Display Average IMRs Per Connection - The average number
of display peer messages per connection sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, CEEUOC, CN100
(CEECN100)
Related
Parameters
Remarks Report By Exception Display Average IMRs Per Connection - The average number
of display peer messages per connection sent on the wire.

20.94 RDISPAVGPPS [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Display Average Parameters Per Second - The average
number of display parameters per second sent on the wire.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RDISPMAXPPS
Parameters
Remarks Report By Exception Display Average Parameters Per Second - The average
number of display parameters per second sent on the wire.

- 2512 -
Chapter 20 - Rxxxx Parameters

20.95 RDISPAVGPPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Display Average Parameters Per Connection - The average
number of display parameters per connection sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.96 RDISPCONN

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Responder Display Connections - The number of current display connections.

Data Type 32-Bit Integer


Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Responder Display Connections - The number of current display connections.

- 2513 -
Chapter 20 - Rxxxx Parameters

20.97 RDISPCONNMAX

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Responder Display Connections Maximum - The maximum number of display
connections supported in this version of firmware.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Responder Display Connections Maximum - The maximum number of display
connections supported in this version of firmware.

20.98 RDISPDEGIMRCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Number of Display IMRs Degraded to Request-Response - Indicates the count of
display IMRs (Interprocess Message Structure) that have degraded to Request-
Response on each connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Number of Display IMRs Degraded to Request-Response - Indicates the count of
display IMRs (Inter-process Message Structure) that have degraded to Request-
Response on each connection.

- 2514 -
Chapter 20 - Rxxxx Parameters

20.99 RDISPDEGRADIMR [1...RPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Request-Response Display Degradation IMRs - The number of display IMRs that
have degraded to Request -Response on each connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.100 RDISPMAXLPS [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Display Maximum IMRs Per Second - The maximum number
of display peer messages per second sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RDISPAVGLPS
Parameters
Remarks Report By Exception Display Maximum IMRs Per Second - The maximum number
of display peer messages per second sent on the wire.

- 2515 -
Chapter 20 - Rxxxx Parameters

20.101 RDISPMAXLPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Display Maximum IMRs Per Connection - The maximum
number of display peer messages per connection sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RDISPAVGLPSCONN
Parameters
Remarks

20.102 RDISPMAXPPS [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Display Maximum Parameters Per Second - The maximum
number of display parameters per second sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

- 2516 -
Chapter 20 - Rxxxx Parameters

20.103 RDISPMAXPPSCONN [1...RDISPCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Display Maximum Parameters Per Connection - The
maximum number of display parameters per connection sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RDISPAVGPPSCONN
Parameters
Remarks Report By Exception Display Maximum Parameters Per Connection - The
maximum number of display parameters per connection sent on the wire.

20.104 RDISPHOST [1...RPEERCONNMAX]

Specific to Block(s) CEE, IOLIM, FIM


Description Originator's Display Host - Shows the name of the originator's host.
Data Type EntityID
Range 16 characters
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related Parameters
Remarks

20.105 RDNAUTOSYNC

Specific to Platform Blocks C300, UOC, FIM4, and TCMI AI-HART, AI-LLAI, AI-LLMUX, AO-
Block(s) HART, DI-HV, DI-24, DO-24B, PGM
Description Auto Synchronization State
Data Type Enumeration
Range 0 DISABLED Auto synchronization

- 2517 -
Chapter 20 - Rxxxx Parameters

disabled either due to


Disable Synchronization
command or due to
persistent synchronization
fault.
1 ENABLED Auto synchronization
enabled by the Enable
Synchronization
command.
2 --- N/A because module
configured as non-
redundant.
Default DISABLED
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence Controller, NOLOAD
Related ALTSYNCCMD, DSBLSYNCCMD, ENBLSYNCCMD
Parameters
Remarks Indicates whether auto synchronization is enabled or disabled in the controller.
Auto synchronization is enabled upon receipt of the Enable Synchronization
command (ENBLSYNCCMD). When enabled, a Primary Module automatically
attempts to synchronize the Secondary, upon receipt of any Auto-Synchronization
trigger (in addition to the Enable Synchronization command). Auto synchronization
is disabled either upon receipt of the Disable Synchronization command
(DSBLSYNCCMD) or detection of a persistent synchronization fault condition (For
example, end-to-end checksum failure, synchronization hardware failure, and so
on). When disabled, the user must explicitly issue the Enable Synchronization
command to reset any persistent fault condition and re-attempt initial-sync.

20.106 RDNCAPABILITY

Specific to Platform Blocks for C200, C300, FTEB, FIM, FIM4, IOLIM, LIOM, PGM
Block(s)
Description Redundancy Capable Hardware Indicator - Indicates whether the module
hardware and/or firmware is capable of supporting redundancy.
Data Type Boolean
Range Off (0 On (1)
Default On
Config Load No
Active No
Loadable

- 2518 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence Controller
Related RDNCHASSISID
Parameters
Remarks

Specific to Block(s) UOC


Description Hardware Redundancy Capability
Data Type BOOLEAN
Exposure OUTPUT
Range NA
Default Off
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.107 RDNCHASSISID

Specific to IOLIM, FIM, CPM, FTEB


Block(s)
Description Redundancy Physical Chassis ID - Identifies a specific physical chassis in a
redundant chassis pair without regard to chassis redundancy state.
Data Type Enumeration RDNCHASSISID
Range ChassisUndef (0) ChassisA (1) ChassisB (2)
Default ChassisUndef (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, FIM, CEE
Related
Parameters
Remarks This is a user-configurable attribute of the Redundancy Module (RM) which the RM
distributes to all chassis resident redundancy compliant modules.

- 2519 -
Chapter 20 - Rxxxx Parameters

20.108 RDNCMPT

Specific to Platform Blocks for C200, C300, FTEB, FIM, FIM4, IOLIM, LIOM, PGM, EIM, TCMI
Block(s)
Description Redundancy Partner Compatibility - Indicates whether redundant partner modules
are compatible (from a controller redundancy perspective) and if not compatible,
provides a reason why.
Data Type Enumeration
Range NoPartner (0) Not Applicable - Initial/default state when no partner is
responding to the partner compatibility query.
QueryInProg (1) Not Applicable - Transient state indicating that the redundancy
partners are negotiating their compatibility.
Compatible (2) Compatible - Compatible indication for those platforms not
sensitive to difference in firmware versions. This includes FIM,
FIM4, FTEB, and IOLIM.
DirectCmpt (3) Compatible - Compatible indication for those platforms
sensitive to difference in firmware versions (that is,
C200/C300) when firmware versions are identical.
IndirectCmpt (4) Compatible - Compatible indication for those platforms
sensitive to difference in firmware versions (that is,
C200/C300) when firmware versions differ. This implies that
the Controller Migration Wizard must be invoked to coordinate
OPM initial synchronization and switchover to the different
firmware version.
MessageSize (5) Incompatible - The size of the partner's compatibility message
is unexpected. 1
Honeywellid (6) Incompatible - The partner's Honeywell ID does not match. 1
ProductType (7) Incompatible - The partner's Product Type does not match 1
ProductCode (8) Incompatible - The partner's Product Code does not match.1
MajRevision (9) Incompatible - The partner's Major revision is not supported. 1
MinRevision (10) Incompatible - The partner's Minor revision is not supported. 1
Platform (11) Incompatible - Mismatched compatibility types (that is,
different platform firmware). 1
OPMNotlmpl (12) Incompatible - Incompatible indication for those platforms
sensitive to difference in firmware versions when firmware
versions differ and the platform does not support OPM (there
are no known examples of this platform type).
OPMSequence Incompatible - Attempting to migrate across more than one
(13) major release For example, migration between R101 and R300
is not allowed.

NodeNumber (14) Incompatible - Device Indexes of potential redundant partner


modules are not properly configured as consecutive odd/even
pair.
- - - (15) Not Applicable - Module is configured as non-redundant.
ModuleType (16) Incompatible - Mismatched compatibility types (that is,
different platform firmware).
MessageFmt (17) Incompatible - Mismatched compatibility types (that is,
different platform firmware).

- 2520 -
Chapter 20 - Rxxxx Parameters

MessageFmt (18) Incompatible - The partner compatibility message format is


undefined or not supported.
PartnBootFmw Incompatible - The partner module is executing from boot
(19) firmware (for example, partner is in the Alive, Ready, or Fail
State). To be compatible, both partners must be executing from
application firmware.
Default NoPartner (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C200, FIM, IOLIM, C300, FTEB, FIM4, LIOM and FIM4, PGM
Related
Parameters
Remarks 1These reasons only apply to the C200/FIM/IOLIM/FTEB module types.

Specific to Platform Blocks for ACE


Block(s)
Description Cutover Compatibility
Data Type Enumeration
Range
Default NoPartner (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks This parameter indicates whether redundant partner modules are compatible
(from a controller redundancy perspective) and if not compatible, provides a reason
why.

Specific to Block(s) UOC


Description Redundancy Compatibility
Data Type ENUM
Exposure OUTPUT
Range NA
Default -
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

- 2521 -
Chapter 20 - Rxxxx Parameters

20.109 RDNCNTCYCMAX

Specific to CEE-C300 block


Block(s)
Description Redundancy transfer Count per Cycle Maximum - Maximum number of
redundancy data and address bytes transferred from primary to secondary every
cycle.
Data Type Floating Point
Range >0
Index 0 to 40
Range
Default Not Applicable
Config No
Load
Active No
Loadable
Access View Only
Lock
Residence CEE
Related RDNCNTCYCTP RDNXFERMAX RDNXFERAVG STATSRESET
Parameters
Remarks While a redundant C300 controller pair is running and synchronized, data and
address information must be passed from primary to secondary. This keeps the
database of the secondary synchronized with that of the primary so that it is ready
to take over if and when the primary fails. RDNCNTCYCMAX is an array parameter
which displays the maximum number of bytes that have been sent from primary
C300 to secondary C300 for each cycle. Index values 0 through 39 correspond to
the maximum count for cycles 0 through 39 respectively. Index 40 displays the
maximum across the maxima for each cycle. The time span of maximum detection
corresponds to reset of the CEE statistics parameters. To acquire new maxima
starting from the present moment, write On to the parameter CEE.STATSRESET,
RDNXFERAVG and RDNXFERMAX represent the total redundancy transferred
bytes/second average and maximum.

20.110 RDNCNTCYCMAX[0…40]

Specific to CEEC300, CEE, CEEUOC


Block(s)
Description Redundancy transfer Count per Cycle Maximum - Maximum number of redundancy
data and address bytes transferred from primary to secondary every cycle.
Exposure Output

Data Type Floating Point


Range >= 0
Default Not Applicable
Config Load No

- 2522 -
Chapter 20 - Rxxxx Parameters

Active No
Loadable
Access View Only
Lock
Residence CEE
Related RDNCNTCYCTP
Parameters
RDNXFERMAX
RDNXFERAVG
STATSRESET
Remarks While a redundant C300 or UOC controller pair is running and synchronized, data and
address information must be passed from primary to secondary. This keeps the
database of the secondary synchronized with that of the primary so that it is ready to
take over if and when the primary fails.
RDNCNTCYCMAX is an array parameter which displays the maximum number of
bytes that have been sent from primary C300 or UOC to secondary C300 or UOC for
each cycle.
Index values 0 through 39 correspond to the maximum count for cycles 0 through 39
respectively.
Internal No
Only

20.111 RDNCNTCYCTP

Specific to CEEFB, CEEC300, CEEUOC, CEECN100


Block(s)
Description Redundancy transfer Count per Cycle Trip Point
Data Type Integer
Range >= 0
Default 112500
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related RDNXFERMAX RDNXFERAVG RDNCNTCYCMAX
Parameters
Remarks CEE monitors the count of redundancy bytes transferred each cycle from primary
to secondary within a C300/UOC redundant controller pair. If, during any 2-second
interval, the maximum bytes transferred by any of the cycles reach the value of
parameter RDNCNTCYCTP, a high-priority alarm is reported by the CEE block. The
alarm clears once the maximum across a subsequent 2-second interval falls below
90% of the configured trip point value.

- 2523 -
Chapter 20 - Rxxxx Parameters

20.112 RDNCOMMFAILFTE

Specific to IEC61850IM
Block(s)
Description No Partner Communication On FTE Network.
Data Type Boolean
Data Size 1
Range True/False
Class Dynamic
Access Read Only
Related RDNCOMMFAILRDN
Parameters
Remarks The IEC61850 Interface Module establishes redundancy communication on both
the FTE and IEC61850 networks. This parameter reflects the redundancy
communication status on the FTE network.

20.113 RDNCOMMFAILRDN

Specific to IEC61850IM
Block(s)
Description No Partner Communication On IEC61850 Network
Data Type Boolean
Data Size 1
Range True/False
Class Dynamic
Access Read Only
Related RDNCOMMFAILFTE
Parameters
Remarks The IEC61850 Interface Module establishes redundancy communication on both
the FTE and IEC61850 networks. This parameter reflects the redundancy
communication status on the IEC61850 network.

20.114 RDNCTLABILITY

Specific to Platform Blocks for C200, C300, FTEB, FIM, FIM4, IOLIM, LIOM, PGM, TCMI
Block(s)
Description Redundancy Partner Contollability - Describes the module's ability to control
relative to its redundant partner.
Data Type Enumeration
Range --- (0) Not Applicable - Initial/default state when not
communicating with a partner module
Evaluating (1) Transient state while determining controllability.

- 2524 -
Chapter 20 - Rxxxx Parameters

Better (2) This module is better able to control. For example,


when this module has view to FTE but partner
does not.
Equal (3) Both modules of a redundant pair are equally
able to control.
Worse (4) This module is worse able to control. For example,
when this module does not have view to FTE but
partner does.
Default ---
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Controller
Related
Parameters
Remarks

Specific to Block(s) UOC


Description Redundancy Controllability
Data Type ENUM
Exposure OUTPUT
Range NA
Default -
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.115 RDNDELAYAVG

Specific to Platform Blocks for C200, C300, FTEB, FIM, FIM4, IOLIM, LIOM, PGM
Block(s)
Description Redundancy Delay Average - The average redundancy delay of the CPU, in percent.
The redundancy delay takes processing capacity away from all currently active
tasks, causing a delay until redundancy resources are freed. Triggering the
STATRESET parameter restarts averaging.
Data Type 64-Bit Real Number
Range 0.0 to 100.0
Default 0.0
Config No
Load

- 2525 -
Chapter 20 - Rxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence Controller
Related RDNDELAYMAX, STATSRESET.
Parameters
Remarks The average is computed by a one minute, first order lag filter.

Specific to Block(s) UOC


Description Redundancy Delay (%)
Data Type FLOAT64
Exposure OUTPUT
Range ±1.7E+308
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.116 RDNDELAYMAX

Specific to Platform Blocks for C200, C300, FTEB, FIM, FIM4, IOLIM, LIOM, PGM
Block(s)
Description Redundancy Delay Maximum in percent - Historical maximum redundancy delay
CPU value observed since last store to STATRESET.
Data Type 64-Bit Real Number
Range 0.0 to 100.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, FIM, IOLIM, C300, FTEB, FIM4, PGM
Related RDNDELAYAVG, STATRESET.
Parameters
Remarks

- 2526 -
Chapter 20 - Rxxxx Parameters

Specific to Block(s) UOC


Description Max Redundancy Delay (%)
Data Type FLOAT64
Exposure OUTPUT
Range ±1.7E+308
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.117 RDNDEVICEIDX

Specific to Platform Blocks for C300 and FIM4, PGM, TCMI


Block(s)
Description Device Index - Serves as a unique identifier that does not follow the redundancy
role. This parameter shows the Device Index specified on the hardware's rotary dial
on the Platform Block's Redundancy tab.
Data Type 32-Bit Integer
Range 1 to 255
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Controller
Related DEVICEIDX
Parameters
Remarks

Specific to Block(s) UOC


Description Device Index
Data Type INT32
Exposure OUTPUT
Range ±1.7E+308
Default 0
Config Load No
Active Loadable

- 2527 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.118 RDNHISTREASON [1...15]

Specific C300, EIM, FIM4, FIM8,PGM and UOC FBs


to Block
(s)
Descriptio Redundancy History Reason - Provide rational for the occurrence of a redundancy
n history state. Includes rational for loss-of-sync (LOS), redundancy role change
(ROLE), commencing initial sync (IS), and partner compatibility (CMPT).
Data Type Enumeration
Range --- (0) N/A because History State
does not require rational.
PreviouslyPrimary (1) Initial redundancy role of
Primary was chosen
because previously retained
primary role.
PreviouslySynchronizedSecondary (2) Initial redundancy role of
Secondary was chosen
because previously retained
synchronized secondary
role.
PreviouslyStandbySecondary (3) Initial redundancy role of
Secondary was chosen
because previously retained
standby secondary role.
PreviouslyUnsynchronizedSecondary (4) Initial redundancy role of
Secondary was chosen
because previously retained
not-synchronized
secondary role.
PreviouslyNonRedundant (5) Initial redundancy role of
Non-Redundant was
chosen because previously
retained non-redundant
role.
PrimaryIpOccupied (6) Initial redundancy role of
Secondary was chosen
because primary IP address
occupied.
SecondaryIpOccupied (7) Initial redundancy role of
Primary was chosen
because secondary IP
address occupied.
HardwareLimitation (8) Initial redundancy role was
chosen because of
hardware restriction.
OddDeviceIndex (9) Initial redundancy role of
Primary was chosen

- 2528 -
Chapter 20 - Rxxxx Parameters

because module is
configured with odd device
index.
EvenDeviceIndex Initial redundancy role of
(1 Secondary was chosen
0) because module is
configured with even device
index.
PartnerIsPrimary Initial redundancy role of
(1 Secondary was chosen
1) because partner already in
primary role.
PartnerIsSecondary Initial redundancy role of
(1 Primary was chosen
2) because partner already in
secondary role.
PartnerIsNonRedundant Initial redundancy role of
(1 Secondary was chosen
3) because partner already in
non-redundant role.
PartnerIsNoDb Initial redundancy role of
(1 Primary was chosen
4) because partner has no
loaded strategy. Note that as
a consequence, the partner
in NODB State is rebooted
into the secondary role.
PartnerRunningInBootFirmware Initial redundancy role of
(1 Primary was chosen
5) because partner running in
boot firmware. Note that if
the partner was in the
primary role, it transitions
into the secondary role.
LaterWallClockTime Initial redundancy role of
(1 Primary was chosen
6) because simultaneous
conflict resolved by more
recent wall-clock time.
Compatible Partner module is present
(1 and compatible. Compatible
7) indication for those
platforms not sensitive to
difference in firmware
versions. This includes FIM,
FIM4, FIM8, FTEB, IOLIM,
and PGM2.
DirectCompatible Partner module is present,
(1 compatible, and has
8) identical firmware version.
Compatible indication for
those platforms sensitive to
difference in firmware
versions which includes
C200, C200E, C300, and
UOC when firmware
versions are identical.
MigrateCompatible Partner module is present,

- 2529 -
Chapter 20 - Rxxxx Parameters

(1 compatible, but only


9) supports On Process
Migration due to different
firmware versions.
Compatible indication for
those platforms sensitive to
difference in firmware
versions which includes
C200, C200E, C300, and
UOC when firmware
versions differ. This implies
that the Controller
Migration Wizard must be
invoked to coordinate OPM
initial synchronization and
switchover to the different
firmware version.
HardwareType Incompatible - Different
(2 Hardware Types. Check for
0) a Factory Information
mismatch between the
redundant pair.
FirmwareType Incompatible - Different
(2 Firmware Types.
1)
DeviceIndex Incompatible - Incorrect
(2 Device Index. Redundant
2) pair requires consecutive
Device index pair.
OpmNotImplemented Incompatible - On Process
(2 Migration not implemented.
3)
OpmSequence Incompatible - On Process
(2 Migration not supported
4) across specified releases.
Attempting to migrate
across more than one major
release. For example,
migration between R101
and R300 is not allowed.This
may be allowed in later
releases. This reason is also
used to prevent
synchronization from a
primary controller with
newer firmware to a
secondary controller with
older firmware because the
secondary controller would
not be able to interpret any
new synchronization data
from primary controller with
newer firmware.
InitiateSwitchoverCommand User issued switchover
(2 command.
5)
InitiateSwapCommand User issued swap command.
(2
6)

- 2530 -
Chapter 20 - Rxxxx Parameters

PrimaryLonelyOnFte The original synchronized


(2 primary module became
7) lonely on FTE resulting in
automatic switchover. In
addition, the
unsynchronized controller
performs initial-sync with
immediate switchover with
this reason when the
primary controller suffers
from dual FTE cable
disconnect and the
secondary controller has
visibility to the FTE network.
Migration Automatic redundancy role
(2 change due to on-process
8) migration.
AlternateSync Automatic redundancy role
(2 change due to Alternate
9) Sync command (that is, one
time initial sync across FTE
instead of private path).
DiagnosticFailure Switchover triggered due to
(3 diagnostic failure.
0)
FatalError Switchover triggered due to
(3 fatal error.
1)
FteDeafMute Switchover triggered due to
(3 FTE becoming deaf & mute
2) even though link integrity
signal is still being sensed.
Link1IolLoopbackError Link 1 IOL Loopback Error.
(3 The IOL processor has
3) detected that it cannot see
what it has transmitted onto
the wire. This is a switchover
trigger because it may
represent a fault in the IOL
communication electronics.
Bad IOL wiring and/or
rogue IOL device
communications also could
cause Loopback Error.
PartnerRequest Partner Requested
(3 operation. The redundant
4) partner has either
requested initial-sync to be
inhibited/aborted or for role
change. Refer to the
partner's redundancy
history parameter for the
actual reason.
PartnerBetterPrimary Force role change because
(3 partner is better primary
5) candidate.
DisableSyncCommand User issued disable sync
(3 command.

- 2531 -
Chapter 20 - Rxxxx Parameters

6)

- 2532 -
Chapter 20 - Rxxxx Parameters

PartnerAbsent Partner module absent.


(3 Initial-sync is not applicable
7) without a redundant
partner.
PartnerNotCompatible Partner module not
(3 compatible. Initial-sync is
8) not applicable with an
incompatible redundant
partner.
PartnerPrivatePathDisconnected Redundancy private path
(3 cable disconnected.
9)
RedundancyCommOutOfSequenceError Redundancy
(4 communication out-of-
0) sequence error.
Redundancy
communication buffers
have been lost resulting in
the receipt of an
unexpected sequence
number. This could be a
fault in the redundancy
communication private path
or in the redundancy
communication electronics.
DataFormatError Redundancy
(4 communication format
1) error. Receipt of a
redundancy communication
buffer that has an unknown
fomat ID indicates corrupted
data. This could be a fault in
the redundancy
communication private path
or in the redundancy
communication electronics.
DataChecksumError [C200/C200E/C300/UOC].
(4 Database synchronization
2) checksum error. A
background diagnostic
continuously checks that
the primary and secondary
syncd memory remains
aligned. Failure of this
diagnostic indicates data
corruption due to marginal
secondary memory, fault in
the redundancy
communication private
path, or fault in the
redundancy communication
electronics. Loss-of-sync
due to database sync
checksum error disables
Auto-Sync. Use the Enable
Synchronization command
to return to trigger initial-
sync. [IOLIM] The
secondary received corrupt

- 2533 -
Chapter 20 - Rxxxx Parameters

sync data. The primary


redundancy subsystem
applies a checksum on the
sync-data communication
buffer and the secondary
validates the checksum
against the received sync-
data communication buffer.
[C200/C200E/IOLIM] It is
possible that a module is not
properly seated in the
chassis backplane which
may result intermittent
communication issues that
may be detected as a
checksum error. Perform
visual inspection on the
chassis and attempt to
push-in any modules that
slightly stick out.
SyncHardwareError Synchronization hardware
(4 error. Loss-of-sync due to
3) sync hardware error
disables Auto-Sync. Use the
Enable Synchronization
command to return to
trigger initial-sync.
CleanPointTimeout Encountered a timeout
(4 condition while performing
4) clean-point processing. The
primary is not able to send
redundancy data to the
secondary partner in a
timely fashion.
[C200/FIM/FTEB/IOLIM/LI
OM] This is an early
indication of loss of
communications between
the RMs.
PrimaryUnknownError Unknown cause on primary
(4 module.
5)
SecondaryUnknownError Unknown cause on
(4 secondary module.
6)
AlternateSyncCommand User commanded Alternate
(4 Synchronization.
7)
EnableSyncCommand User commanded Enable
(4 Synchronization.
8)
MigrationCommand Controller on-process
(4 migration.
9)
PartnerReady Compatible partner
(5 completed startup
0) initialization.

- 2534 -
Chapter 20 - Rxxxx Parameters

PartnerPrivatePathConnected Redundancy private path


(5 cable reconnected.
1)
PartnerPrivatePathCommunicationError Redundancy private path
(5 communication error.
2) Invalid redundancy data
was received or the periodic
partner status message was
not received over the
redundancy private path.
DataMessageSizeError Redundancy unexpected
(5 message size error.
3)
AutoSyncState Auto Sync state is disabled.
(5 Initial sync is inhibited while
4) the Auto Sync State is set to
disabled. This is a persistent
inhibit sync reason that is
canceled via the Enable
Sync command.
NoFbStart Missing FB_START
(5 indication.
5)
SyncDataReceiveError Error occurred on
(5 secondary receive of
6) parameterized sync data.
OutOfSyncBuffers Sync data and tag buffers
(5 not allocated.
7)
OutOfIMRs Unable to acquire IMR for
(5 receipt of sync data.
8)
LiveListMismatch Mismatch between primary
(5 & secondary live list.
9)
LinkStatus Link status.
(6
0)
RtpAttendance RTP attendance.
(6
1)
FteCableStatus Indicates that either both
(6 FTE Ethernet cables have
2) been disconnected (i.e. FTE
lonely) or at least one FTE
Ethernet cable has been
reconnected. The primary
triggers switchovers due to
dual-FTE-cable disconnect.
The synchronized
secondary aborts sync due
to dual-FTE-cable
disconnect and the
secondary inhibits sync due
to dual-FTE-cable
disconnect. This secondary

- 2535 -
Chapter 20 - Rxxxx Parameters

persistent inhibit sync


reason can only be canceled
by restoring FTE
communications.
Link1NvsCommands Link 1 Flash operations.
(6 Synchronization is aborted
3) and/or initial-sync is
inhibited during the
database initialization that
occurs upon I/O Link FB
commanded NVS
compaction.
OpmRequired Controller OPM required but
(6 not yet enabled. Initial-sync
4) is not allowed when the
application firmware
versions for the primary and
secondary controllers are
different (for those
platforms sensitive to
difference in firmware
versions that is,
C200/C200E/C300/UOC).
The Controller Migration
Wizard must be used to
perform On-Process
Migration.
OpmWaitRestore Controller OPM waiting for
(6 Secondary Checkpoint
5) Restore
OpmWaitSyncCommand Controller OPM waiting for
(6 sync/switch command from
6) the Controller Migration
Wizard.
OpmAbortCommand Control Migration Wizard
(6 commanded migration
7) abort.
OpmRestoreTimeout Controller OPM Secondary
(6 Checkpoint Restore timed
8) out; this occurs if the flow of
checkpoint data is stalled for
longer than 2 minutes. This
represents abnormal OPM
session termination.
OpmTimeout The redundancy subsystem
(6 aborts controller OPM if
9) control is frozen (during the
one-time OPM initial-sync
transfer of Dynamic Data)
longer than the maximum
specified time (that is, 10
seconds for C200 and 20
seconds for C300). This
represents abnormal OPM
session termination.
OpmInitialSyncTimeout Controller OPM commence
(7 initial sync timed out. Initial
0) sync failed to commence

- 2536 -
Chapter 20 - Rxxxx Parameters

within two minutes following


the receipt of the Migration
Wizard command to
commence initial-sync as
part of an OPM session. This
represents abnormal OPM
session termination.
OpmIoConnectionsTimeout Controller OPM I/O
(7 connection timeout. Loss-
1) of-sync occurred while
waiting for the Secondary
controller to form at least
the same number of I/O
Connections as the primary
controller (as part of initial-
sync during an OPM
session). The Secondary
Platform FB's
LASTOPMNAME parameter
is blank in this case. This
represents abnormal OPM
session termination. This
only applies to the C200
because it forms
connections directly with
the Series A I/O. [PLC/UOC]
Controller detected removal
under power. This may
indicate that the controller
is not fully inserted into the
rack.In the case of the C300,
connections are formed
between the FTEB and
Series A I/O.
OpmIoDataFailure Controller OPM I/O Data
(7 failure. Loss-of-sync
2) occurred while transferring
I/O Connection Data (as
part of initial-sync during an
OPM session). Although any
loss-of-sync triggers this
behavior, the most probable
loss-of-sync cause is the
inability of the secondary
controller to interpret the
I/O Connection Data format.
The Secondary Platform
FB's LASTOPMNAME
parameter is blank in this
case. This represents
abnormal OPM session
termination. This applies
equally to the C200 and
C300 because they both
transfer Series A I/O
Connection data during
OPM initial-sync.
OpmPeerReferencesMismatch Controller OPM peer
(7 reference mismatch. Loss-
3)

- 2537 -
Chapter 20 - Rxxxx Parameters

of-sync occurred while


transferring Peer Cross-
Reference ID data (as part
of initial-sync during an
OPM session). Although any
loss-of-sync triggers this
behavior, the most probable
loss-of-sync cause is the
presence of a ghost peer
connection reference. A
ghost peer connection
reference exists if the
primary controller has
knowledge of a peer
connection ID that was not
instantiated in the
Secondary controller during
OPM Secondary Checkpoint
Restore. The Secondary
Platform FB's
LASTOPMNAME parameter
is blank in this case. This
represents abnormal OPM
session termination.
OpmPeerReferencesFailure Controller OPM peer
(7 reference data fail. The one-
4) time OPM initial-sync
transfer of Dynamic Data
that occurs with control
frozen contains two
components of Peer
Dynamic Data and Block
Dynamic Data with the latter
typically being the larger of
the two. Loss-of-sync
occurred while transferring
Peer Dynamic Data.
Although any loss-of-sync
triggers this behavior, the
most probable loss-of-sync
cause is the inability of the
secondary controller to
interpret the Peer Dynamic
Data format. The Secondary
Platform FB's
LASTOPMNAME parameter
is blank in this case. This
represents abnormal OPM
session termination.
OpmBlockDataTimeout Controller OPM block data
(7 transfer timeout. The
5) redundancy subsystem
aborts controller OPM if
control is frozen (during the
one-time OPM initial-sync
transfer of Dynamic Data)
longer than the maximum
specified time (that is, 10
seconds for C200 and 20
seconds for C300). This
represents abnormal OPM

- 2538 -
Chapter 20 - Rxxxx Parameters

session termination.

- 2539 -
Chapter 20 - Rxxxx Parameters

OpmBlockDataFailure Controller OPM block data


(7 fail. The one-time OPM
6) initial-sync transfer of
Dynamic Data that occurs
with control frozen contains
two components of Peer
Dynamic Data and Block
Dynamic Data with the latter
typically being the larger of
the two. Loss-of-sync
occurred while transferring
Block Dynamic Data. This
represents abnormal OPM
session termination.
Although any loss-of-sync
triggers this behavior, the
most probable loss-of-sync
cause is either the inability
of the secondary controller
to interpret the Block
Dynamic Data format or the
secondary controller has no
destination block to receive
the Dynamic Data. The
latter is possible in the
presence of a ghost block; a
ghost block exists if the
primary controller has
knowledge of a block that
was not instantiated in the
Secondary controller during
OPM Secondary Checkpoint
Restore. The Secondary
Platform FB's
LASTOPMNAME parameter
indicates the name of the
last block to be (on-process)
migrated; the
LASTOPMNAME is used to
isolate the name of the first
CEE subordinate block that
has detected a dynamic
state data error. In the
special case of a ghost block,
the LASTOPMNAME is
either blank (because the
ghost block name no longer
exists in the ERDB) or
indicates the name of a
block that is not loaded to
the controller (that is, only
exists on the Control Builder
project tree).
OpmFormatError Receive of Controller OPM
(7 data failed.
7)
StartupInProgress Platform startup in
(7 progress. Initial sync is not
8) allowed until after the
controller has completed
system startup. This is a

- 2540 -
Chapter 20 - Rxxxx Parameters

transient inhibit sync


reason that is usually not
seen.
PlatformFunctionBlockLoadState Platform FB load state.
(7 Initial-sync is not allowed
9) until after the Platform FB
has been loaded to the
controller.
RedundancyConfigurationState Platform configured as non-
(8 redundant. Initial-sync is
0) not allowed when explicitly
configured as non-
redundant. This persistent
inhibit sync reason can only
be canceled by
reconfiguring the non-
redundant
platformC300/FIM4 FB as
redundant.
Link1PartnerTimeout Link 1 partner startup
(8 timeout. When an I/O Link
1) Fb is configured for PMIO or
Series C I/O, initial-sync
requires explicit
communication with the
partner I/O Link interface
across the I/O Link network.
This reason indicates that a
timeout occurred while
waiting for the partner
interface to commence
communication on the I/O
Link network. Make sure
that the primary and
secondary are connected to
the same I/O Link Network.
Link2PartnerTimeout Link 2 partner startup
(8 timeout. When an I/O Link
2) Fb is configured for PMIO or
Series C I/O, initial-sync
requires explicit
communication with the
partner I/O Link interface
across the I/O Link network.
This reason indicates that a
timeout occurred while
waiting for the partner
interface to commence
communication on the I/O
Link network. Make sure
that the primary and
secondary are connected to
the same I/O Link Network.
Link1PartnerNotVisible Link 1 Partner Not Visible.
(8 Once the I/O Link
3) (configured for PMIO or
Series C I/O) has completed
initial-sync, the primary
controller monitors the
presence of the partner

- 2541 -
Chapter 20 - Rxxxx Parameters

interface across the IOL


communication network.
Loss-of-view of the partner
I/O Link interface results in
loss-of-sync with this
reason.
Link2PartnerNotVisible Link 2 Partner Not Visible.
(8 Once the I/O Link
4) (configured for PMIO or
Series C I/O) has completed
initial-sync, the primary
controller monitors the
presence of the partner
interface across the IOL
communication network.
Loss-of-view of the partner
I/O Link interface results in
loss-of-sync with this
reason.
Link1PartnerMismatch Link 1 Partner Mismatch.
(8 When an I/O Link Fb is
5) configured for PMIO or
Series C I/O, initial-sync
requires explicit
communication with the
partner I/O Link interface
across the I/O Link network.
This reason indicates that
the primary established
communication with the
wrong partner interface
across the IOL. More
specifically, the partner
interface is the wrong link
number (for example,
primary Link 1 connected to
secondary Link 2) and/or
the partner interface on the
IOL communication network
belongs to a controller other
than the secondary
controller in this redundant
pair. Make sure that the
primary and secondary are
connected to the same I/O
Link Network.
Link2PartnerMismatch Link 2 Partner Mismatch.
(8 When an I/O Link Fb is
6) configured for PMIO or
Series C I/O, initial-sync
requires explicit
communication with the
partner I/O Link interface
across the I/O Link network.
This reason indicates that
the primary established
communication with the
wrong partner interface
across the IOL. More
specifically, the partner

- 2542 -
Chapter 20 - Rxxxx Parameters

interface is the wrong link


number (for example,
primary Link 2 connected to
secondary Link 1) and/or
the partner interface on the
IOL communication network
belongs to a controller other
than the secondary
controller in this redundant
pair. Make sure that the
primary and secondary are
connected to the same I/O
Link Network.
StateUnexpected Unexpected State in State
(8 Machine. Loss-of-sync
7) occurred due to internal
redundancy state machine
unexpected transition.
InitialSyncDelay Anti thrash delay in between
(8 initial sync attempts. There
8) is a guaranteed 30 second
delay in between initial-sync
attempts. More specifically,
for 30 seconds after a
compatible partner is
identified, initial-sync is
inhibited with this transient
reason.
InitialSyncFail Multiple consecutive initial
(8 sync failures After 3 failed
9) attempts to perform initial-
sync, the Auto Sync State is
automatically set to disabled
and the inhibit sync reason
is set to this persistent
value. Refer to the
redundancy history for the
reasons why initial-sync
failed, and issue the Enable
Sync command to attempt
initial-sync again after
correcting the abort-sync
reason.
DroppingSync Drop-synchronization in
(9 progress. Initial-sync cannot
0) commence until the
previous abort sync
operation has been
completed. This is a
transient inhibit sync
reason that is usually not
seen.
CclBinaryLoad Synchronization cannot be
(9 maintained during CCL
1) Binary load.
CeeLoadOrDelete Synchronization cannot be
(9 maintained during the
2) database initialization that
occurs upon CEE FB load or
delete.

- 2543 -
Chapter 20 - Rxxxx Parameters

UnsupportedHardwareVersion Unsupported controller HW


(9 version. Initial-sync is
3) inhibited for controller
hardware version that does
not support controller
redundancy.
BothRunningInBootFirmware Both running in boot
(9 firmware. Initial-sync is only
4) possible when both partners
of a redundant pair are
running in application
firmware.
ThisRunningInBootFirmware This module running in boot
(9 firmware. Initial-sync is only
5) possible when both partners
of a redundant pair are
running in application
firmware.
RedundancyCommOutOfBuffersError Redundancy
(9 communication out-of-TX-
6) buffers error. The
redundancy subsystem
cannot send any more
redundancy messages
because the TX buffers
have been exhausted. This
is a drop-sync trigger.
RedundancyCommTransmitError Redundancy
(9 communication transmit
7) error.
RedundancyCommReceiveError Redundancy
(9 communication receive
8) error.
RedundancyCommDeviceReset Redundancy
(9 communication device
9) reset.
(100) Redundancy
RedundancyCommBadBufferIn communication bad buffer
dex index.
BecomePrimaryCommand (101) Become Primary command.
LowerSerialNumber (102) When performing initial-
role-determination or dual
role correction upon re-
establishing partner
communication, the
redundancy subsystem’s
role decision was chosen
due to lower serial number.
This reason indicates that
the physical ID of the
redundant pair is not well
formed resulting in serial
number tie breaker.
HigherSerialNumber (103) When performing initial-
role-determination or dual
role correction upon re-
establishing partner

- 2544 -
Chapter 20 - Rxxxx Parameters

communication, the
redundancy subsystem’s
role decision was chosen
due to higher serial
number. This reason
indicates that the physical
ID of the redundant pair is
not well formed resulting in
serial number tie breaker.
BetterControlAbility (104) Indicates that the controller
is a better candidate to be
the primary controller.
Switchover immediately
occurs following initial-sync
when the secondary
controller has better control
ability. Initial-sync is
inhibited when the primary
controller has better control
ability.
WorseControlAbility (105) Indicates that the controller
is a worse candidate to be
the primary controller.
Switchover immediately
occurs following initial-sync
when only the primary
controller has worse control
ability. Initial-sync is
inhibited when only the
secondary controller has
worse control ability.
PartnerFaultDetected (106) Partner Fault Detected. The
partner module was
rebooted and/or powered
off.
Link1LoadState (107) Link 1 load has not
completed /occurred. Initial-
sync is not allowed to
commence until after all link
function blocks have been
loaded. This persistent
inhibit sync reason is
negated upon load of the
link function block to the
controller.
Link2LoadState (108) Link 2 load has not
completed /occurred. Initial-
sync is not allowed to
commence until after all link
function blocks have been
loaded. This persistent
inhibit sync reason is
negated upon load of the
link function block to the
controller.
Link3LoadState (109) Link 3 load has not
completed /occurred. Initial-
sync is not allowed to
commence until after all link
function blocks have been

- 2545 -
Chapter 20 - Rxxxx Parameters

loaded. This persistent


inhibit sync reason is
negated upon load of the
link function block to the
controller.
Link4LoadState (110) SYNC: Link 4 load has not
completed/occured. Initial-
sync is not allowed to
commence until after all link
function blocks have been
loaded. This persistent
inhibit sync reason is
negated upon load of the
link function block to the
controller.
Link5LoadState (111) Link 5 load has not
completed /occurred. Initial-
sync is not allowed to
commence until after all link
function blocks have been
loaded. This persistent
inhibit sync reason is
negated upon load of the
link function block to the
controller.
Link6LoadState (112) Link 6 load has not
completed /occurred. Initial-
sync is not allowed to
commence until after all link
function blocks have been
loaded. This persistent
inhibit sync reason is
negated upon load of the
link function block to the
controller.
Link7LoadState (113) Link 7 load has not
completed /occurred. Initial-
sync is not allowed to
commence until after all link
function blocks have been
loaded. This persistent
inhibit sync reason is
negated upon load of the
link function block to the
controller.
Link8LoadState (114) Link 8 load has not
completed /occurred. Initial-
sync is not allowed to
commence until after all link
function blocks have been
loaded. This persistent
inhibit sync reason is
negated upon load of the
link function block to the
controller.
UnexpectedPdTagSetOnLink (115) Unexpected set PD_TAG on
link.
UnexpectedPdTagClearOnLink (116) Unexpected clear PD_TAG
on link.

- 2546 -
Chapter 20 - Rxxxx Parameters

(117) Unexpected set node


UnexpectedNodeAddrSetOnLin address on link.
k
(118) Unexpected clear node
UnexpectedNodeAddrClearOnLi address on link.
nk
DupeNodeAddrDetectedOnLink (119) Duplicate node address
detected on link.
(120) Unknown SM event
UnknownSmEventIndicationOn indication on link.
Link
(121) Secondary cannot commit
OnProcessMigrationDSDThrottl DSD fast enough
ing
(122) Communication buffer
RedundancyCommBufferOverfl overflow
ow
RedundancyDataOverrun (123) Secondary received more
synchronization data than it
can accumulate. This is an
indication that the
secondary cannot keep up
with the rate of redundancy
data being generated by the
primary controller.
RedundancyResourceLocked (124) Resource Locked
OpenIoConnectionsTimeout (125) I/O connections open
timeout
RedundancyModuleRemoval (126) RM connection timed-out as
if removed
OpenSyncDataConnectionError (127) Sync connection open error

(128) Track connection open error


OpenTrackDataConnectionErro
r
InitialSyncTimeout (129) Initial-sync timed out
EnableStandbyCommand (130) User commanded Enable
Standby.
BadAddressOnLink1 (131) Incorrect address on link 1.
This is typically caused by
bad wiring, bad hardware, or
both. 1 - Check that there is
no "noise on the wire" as
this causes the FIM to
change addresses per FF
spec. 2 - Check that the
primary and secondary FIMs
are connected to the same
RTP. 3 - Check that the RTP
is good and that it has a
good fuse. 4 - Check for
proper termination on the
H1 link. 5 - Check that there
are no shorts in the wiring.
6 - Check that the wiring is

- 2547 -
Chapter 20 - Rxxxx Parameters

properly shielded. 7 - Check


that there are no failed
devices.
BadAddressOnLink2 (132) Incorrect address on link 2.
This is typically caused by
bad wiring, bad hardware, or
both. 1 - Check that there is
no "noise on the wire" as
this causes the FIM to
change addresses per FF
spec. 2 - Check that the
primary and secondary FIMs
are connected to the same
RTP. 3 - Check that the RTP
is good and that it has a
good fuse. 4 - Check for
proper termination on the
H1 link. 5 - Check that there
are no shorts in the wiring.
6 - Check that the wiring is
properly shielded. 7 - Check
that there are no failed
devices.
BadAddressOnLink3 (133) Incorrect address on link 3.
This is typically caused by
bad wiring, bad hardware, or
both. 1 - Check that there is
no "noise on the wire" as
this causes the FIM to
change addresses per FF
spec. 2 - Check that the
primary and secondary FIMs
are connected to the same
RTP. 3 - Check that the RTP
is good and that it has a
good fuse. 4 - Check for
proper termination on the
H1 link. 5 - Check that there
are no shorts in the wiring.
6 - Check that the wiring is
properly shielded. 7 - Check
that there are no failed
devices.
BadAddressOnLink4 (134) Incorrect address on link 4.
This is typically caused by
bad wiring, bad hardware, or
both. 1 - Check that there is
no "noise on the wire" as
this causes the FIM to
change addresses per FF
spec. 2 - Check that the
primary and secondary FIMs
are connected to the same
RTP. 3 - Check that the RTP
is good and that it has a
good fuse. 4 - Check for
proper termination on the
H1 link. 5 - Check that there
are no shorts in the wiring.
6 - Check that the wiring is
properly shielded. 7 - Check

- 2548 -
Chapter 20 - Rxxxx Parameters

that there are no failed


devices.
BadAddressOnLink5 (135) Incorrect address on link 5.
This is typically caused by
bad wiring, bad hardware, or
both. 1 - Check that there is
no "noise on the wire" as
this causes the FIM to
change addresses per FF
spec. 2 - Check that the
primary and secondary FIMs
are connected to the same
RTP. 3 - Check that the RTP
is good and that it has a
good fuse. 4 - Check for
proper termination on the
H1 link. 5 - Check that there
are no shorts in the wiring.
6 - Check that the wiring is
properly shielded. 7 - Check
that there are no failed
devices.
BadAddressOnLink6 (136) Incorrect address on link 6.
This is typically caused by
bad wiring, bad hardware, or
both. 1 - Check that there is
no "noise on the wire" as
this causes the FIM to
change addresses per FF
spec. 2 - Check that the
primary and secondary FIMs
are connected to the same
RTP. 3 - Check that the RTP
is good and that it has a
good fuse. 4 - Check for
proper termination on the
H1 link. 5 - Check that there
are no shorts in the wiring.
6 - Check that the wiring is
properly shielded. 7 - Check
that there are no failed
devices.
BadAddressOnLink7 (137) Incorrect address on link 7.
This is typically caused by
bad wiring, bad hardware, or
both. 1 - Check that there is
no "noise on the wire" as
this causes the FIM to
change addresses per FF
spec. 2 - Check that the
primary and secondary FIMs
are connected to the same
RTP. 3 - Check that the RTP
is good and that it has a
good fuse. 4 - Check for
proper termination on the
H1 link. 5 - Check that there
are no shorts in the wiring.
6 - Check that the wiring is
properly shielded. 7 - Check
that there are no failed

- 2549 -
Chapter 20 - Rxxxx Parameters

devices.

- 2550 -
Chapter 20 - Rxxxx Parameters

BadAddressOnLink8 (138) Incorrect address on link 8.


This is typically caused by
bad wiring, bad hardware, or
both. 1 - Check that there is
no "noise on the wire" as
this causes the FIM to
change addresses per FF
spec. 2 - Check that the
primary and secondary FIMs
are connected to the same
RTP. 3 - Check that the RTP
is good and that it has a
good fuse. 4 - Check for
proper termination on the
H1 link. 5 - Check that there
are no shorts in the wiring.
6 - Check that the wiring is
properly shielded. 7 - Check
that there are no failed
devices.
FTEB_IoManager (139) FTEB IO Manager.
Link1PartnerNotLoaded (140) Link 1 Partner Not Loaded.
Link2PartnerNotLoaded (141) Link 2 Partner Not Loaded.
Link1IoLinkLonely (142) Link 1 IOLINK Lonely. The
primary C300/IOLIM
triggers switchover when
the IOLINK Type for this I/O
Link has a value other than
NONE, there was at least
one configured IOM
previously communicating
on the I/O Link, and there is
no response from any
configured IOM nor the
partner's IOL interface. This
switchover trigger is a dual
fault that cannot be
detected until after some
control has been back-
initialized with failsafe data.
Although this dual fault
affects control, switchover
provides automatic recovery
that doesn't require the
operator to diagnose how to
deal with a primary that has
complete loss of IOM view.
Link2IoLinkLonely (143) Link 2 IOLINK Lonely. The
primary C300 triggers
switchover when the
IOLINK Type for this I/O
Link has a value other than
NONE, there was at least
one configured IOM
previously communicating
on the I/O Link, and there is
no response from any
configured IOM nor the
partner's IOL interface. This

- 2551 -
Chapter 20 - Rxxxx Parameters

switchover trigger is a dual


fault that cannot be
detected until after some
control has been back-
initialized with failsafe data.
Although this dual fault
affects control, switchover
provides automatic recovery
that doesn't require the
operator to diagnose how to
deal with a primary that has
complete loss of IOM view.
Link2IolLoopbackError (144) Link 2 IOL Loopback Error.
The IOL processor has
detected that it cannot see
what it has transmitted onto
the wire. This is a switchover
trigger because it may
represent a fault in the IOL
communication electronics.
Bad IOL wiring and/or
rogue IOL device
communications also could
cause Loopback Error.
Link2NvsCommands (145) Link 2 Flash operations.
Synchronization is aborted
and/or initial-sync is
inhibited during the
database initialization that
occurs upon I/O Link FB
commanded NVS
compaction.
CommDriverTxFault (146) Redundancy
communication driver TX
fault. There are too many
outstanding requests
prohibiting any further
transmissions.

- 2552 -
Chapter 20 - Rxxxx Parameters

Link1IntCircuitFail (147) Link 1 IOL Interrupt Circuit


Failed. Upon receipt of an
Interrupt Circuitry Fault
error from the IOL
processor, attempt
redundancy role change.
This occurs if the IOL
signals, CLRGHO and/or
GAPINT, are rendered
inoperable (SA0 or SA1).
Link2IntCircuitFail (148) Link 2 IOL Interrupt Circuit
Failed. Upon receipt of an
Interrupt Circuitry Fault
error from the IOL
processor, attempt
redundancy role change.
This occurs if the IOL
signals, CLRGHO and/or
GAPINT, are rendered
inoperable (SA0 or SA1).
SimultaneousStartup (149) Simultaneous Startup
detected. Target role is
primary or non-redundant
but primary IP has been
requested (that is, ARPed
during dual powerup);
override as secondary to
avoid dual primary role.
Note that this intentionally
may result in dual
secondary that is
considered as being better
than dual primary.
ClnPointOverrun (150) Secondary received more
cleanpoints than it can
process. This is an
indication that the
secondary cannot keep up
with the rate of redundancy
data being generated by the
primary controller.
(PrimaryRole) 151 Primary redundancy role.

(SecondaryRole) 152 Secondary redundancy role.

(NonRedundantRole) 153 Non-Redundant redundancy role.

FieldDevNetworkAddr 154 Incompatible - Incorrect Sensor Network Address.

IpAddress 155 Incompatible - Incorrect IP Address.

NotLoaded 156 Configuration Not Loaded

ConfigurationMismatch 157 Configuration Mismatch

MessageType 158 Unexpected message type.

- 2553 -
Chapter 20 - Rxxxx Parameters

- 2554 -
Chapter 20 - Rxxxx Parameters

PartnerConnection 159 Connection not established with partner.

FieldDevNetworkID 160 Incompatible - Incorrect Sensor Network ID.

PriPartnIpAddress 161 Incompatible - Incorrect Pri Partner IP Address


configuration.
SecPartnIpAddress 162 Incompatible - Incorrect Sec Partner IP Address
configuration.
FieldDevFreqHopMode 163 Incompatible - Incorrect Sensor Frequency
Hopping Mode.
FieldDevFreqHopID 164 Incompatible - Incorrect Sensor Frequency
Hopping ID.
FieldDevNetworkNotCnfg 165 Incompatible - Sensor Network not configured.

InvalidSystemStatusMemory 166 System Status Memory in RAM or NVS is invalid or


resulted in access error.
NonRetentionStartup 167 Non-Retention Startup.

PhysicalIdA 168 Physical ID A.

PhysicalIdB 169 Physical ID B.

PrimaryAndSecondaryIpOccupied 170 Both Primary & Secondary IP addresses occupied.

Link1FieldNetworkFailure 171 PROFIBUS Network communication failure on link


1.
Link2FieldNetworkFailure 172 PROFIBUS Network communication failure on link
2.
FdnPrimaryIpOccupied 173 Initial redundancy role of Secondary was chosen
because the primary IP address is occupied on
the Field Device Network (FDN).
PcnPrimaryIpOccupied 174 Initial redundancy role of Secondary was chosen
because the primary IP address is occupied on
the Process Control Network (PCN).
FdnSecondaryIpOccupied 175 Initial redundancy role of Primary was chosen
because the secondary IP address is occupied on
the Field Device Network (FDN).
PcnSecondaryIpOccupied 176 Initial redundancy role of Primary was chosen
because the secondary IP address is occupied on
the Process Control Network (PCN).
FdnBothRedunIpOccupied 177 Primary and Secondary FDN IP Addresses are
occupied.
PcnBothRedunIpOccupied 178 Primary and Secondary PCN IP Addresses are
occupied.
FdnPcnBothRedunIpOccupied 179 Primary and Secondary, FDN and PCN IP
Addresses are occupied.
FdnConfiguration 180 Incorrect FDN Ethernet Interface configuration.
Redundant partners must have identical subnet
masks, and redundant partners must have

- 2555 -
Chapter 20 - Rxxxx Parameters

unique IP addresses that are visible to one


another for the given subnet mask.
PcnConfiguration 181 Incorrect PCN Ethernet Interface configuration.
Redundant partners must have identical subnet
masks, and redundant partners must have
unique IP addresses that are visible to one
another for the given subnet mask.
FdnEthernetStatus 182 Indicates that the FDN Ethernet cable was either
disconnected or reconnected. The synchronized
primary triggers switchovers due to FDN Ethernet
cable disconnect. The synchronized secondary
aborts sync and the secondary in general inhibits
sync due to FDN Ethernet cable disconnects. This
secondary persistent inhibit sync reason can only
be canceled by restoring FDN Ethernet
communications.
PcnEthernetStatus 183 Indicates that the PCN Ethernet cable was either
disconnected or reconnected. The synchronized
primary triggers switchovers due to PCN Ethernet
cable disconnect. The synchronized secondary
aborts sync and the secondary in general inhibits
sync due to PCN Ethernet cable disconnects. This
secondary persistent inhibit sync reason can only
be canceled by restoring PCN Ethernet
communications.
PartIDConflict 184 Indicates that both controllers have the same
physical ID.
NtpConfigNeeded 185 Indicates that secondary has not yet configured
its NTP daemon from primary. Initial sync is
blocked until NTP configuration completes.
UCNnumber 186 The controller was loaded resulting in a different
UCN address and redundancy state than the
current redundancy state requiring a role
change.
SecureCommConfigMismatch 187 The primary and secondary have different secure
communication security levels which inhibits
initial-synchronization.
SecureCommPolicyMismatch 188 The primary and secondary have different secure
communication active policies which inhibits
initial-synchronization.
DownlinkNetworkCableSts 189 Indicates that the Downlink Ethernet cable was
either disconnected or reconnected. The
synchronized primary triggers switchovers due to
Downlink Ethernet cable disconnect. The
synchronized secondary aborts sync due to
Downlink Ethernet cable disconnect and the
secondary inhibits sync due to Downlink Ethernet
cable disconnects. This secondary persistent
inhibit sync reason can only be canceled by
restoring Downlink Ethernet communications.
FdnPartNotVis 190 Partner not visible across FDN interface.

PcnPartNotVis 191 Partner not visible across PCN interface.

- 2556 -
Chapter 20 - Rxxxx Parameters

UpgStartTask 192 C200-to-C300 Upgrade: Start Task

- 2557 -
Chapter 20 - Rxxxx Parameters

UpgConnOpened 193 C200-to-C300 Upgrade: Connection Opened

- 2558 -
Chapter 20 - Rxxxx Parameters

UpgResetEnable 194 C200-to-C300 Upgrade: Reset Enable

- 2559 -
Chapter 20 - Rxxxx Parameters

UpgSessionComplete 195 C200-to-C300 Upgrade: Session Complete

- 2560 -
Chapter 20 - Rxxxx Parameters

UpgConnFailed 196 C200-to-C300 Upgrade: Connection to the


Targets Failed
UpgResetFailed 197 C200-to-C300 Upgrade: Reset Targets Failed
FteNetworkDisconnected 201 A redundancy communication error over the FTE
network implies there is break in the
communication path.
DownlinkNetworkDisconnected 202 A redundancy communication error over the
Downlink Ethernet network implies there is break
in the communication path.
FTENetworkCommunicationError 203 Invalid redundancy data was received or the
periodic partner status message was not received
over the FTE network.
DownlinkNetworkCommunicationError 204 Invalid redundancy data was received or the
periodic partner status message was not received
over the Downlink Ethernet network.
SyncDataUnexpectedState 205 The primary controller is unable to participate in
initial-sync because a block refused to commence
initial-sync.
ProfibusDriverWatchdogTimeout 206 The PROFIBUS Driver has abnormally terminated
operation due to watchdog timeout. When
detected on a synchronized primary, this results
in redundancy switchover. One possible cause
may be that the controller has a high CPU load.
ProfibusDriverStoppingTimeout 207 The PROFIBUS Driver has abnormally terminated
operation due to stop command timeout. When
detected on a synchronized primary, this results
in redundancy switchover.
ProfibusDriverResettingTimeout 208 The PROFIBUS Driver has abnormally terminated
operation due to reset command timeout. When
detected on a synchronized primary, this results
in redundancy switchover.
ProfibusDriverChannelInitFail 209 The PROFIBUS Driver has abnormally terminated
operation due to channel initialization failure.
When detected on a synchronized primary, this
results in redundancy switchover.
ProfibusDriverConfLoadFail 210 The secondary has lost view to the primary
because PROFIBUS Driver has failed to load link
configuration. When detected, the synchronized
or synchronizing secondary aborts sync.
ProfibusDriverLostViewToPrimary 211 The secondary controller monitors the presence
of the partner across the PROFIBUS network and
aborts synchronization when it the primary does
not respond to the secondary’s scan request.
ProfibusDriverChannelReadFail 212 The PROFIBUS Driver has abnormally terminated
operation due to I/O read failure. When detected
on a synchronized primary, this results in
redundancy switchover.
FTENetworkConnectionReset 213 The partner intentionally reset the redundancy
communication connection over the FTE network.
When detected, the synchronized or
synchronizing controller aborts sync.
DownlinkNetworkConnectionReset 214 The partner intentionally reset the redundancy
communication connection over the Downlink

- 2561 -
Chapter 20 - Rxxxx Parameters

Ethernet network. When detected, the


synchronized or synchronizing controller aborts
sync.
PrimaryLonelyOnDownlinkNetwork 215 When an unsynchronized primary controller
suffers from Downlink Ethernet network cable
disconnect and the secondary controller has
visibility to the Downlink Ethernet network, the
controller performs initial-sync with immediate
switchover with this reason.
PrimaryDupIpOnDownlinkNetwork 216 When an unsynchronized primary controller
suffers from Duplicate IP Address on the
Downlink Ethernet network and the secondary
controller has visibility to the Downlink Ethernet
network, the controller performs initial-sync with
immediate switchover with this reason.
DownlinkNetworkDuplicateIp 217 The primary and secondary controllers change
their controllability parameter to worse with this
reason when they detect a duplicate IP Address
on the Downlink Ethernet network.
DownlinkNetworkConfiguration 218 The secondary controller inhibits synchronization
until it has configured its IP Address and Mask for
the Downlink Ethernet network communication
and confirmed that no duplicate IP address exists
on the Downlink Ethernet network.
DownlinkNetworkCommunication 219 When the primary has visibility to the Downlink
Ethernet network, it inhibits synchronization (with
this reason) until it establishes communication
with the secondary over the Downlink Ethernet
network. This ensures that the secondary has the
same view as the primary on the Downlink
Ethernet network.
FTENetworkCommunication 220 When the primary has visibility to the FTE
network, it inhibits synchronization (with this
reason) until it establishes communication with
the secondary over the FTE network. This
ensures that the secondary has the same view as
the primary on the FTE network.
DeviceConnectionStatus 221 The Primary Interface Module triggers switchover
(with this reason) when the primary transitions
from communicating with at least one Device to
unable to communicate with all Devices (and
there are Devices configured). The Secondary
Interface Module drops synchronization (with this
reason) when the secondary is unable to open a
connection with a Device (when the primary
interface module has successfully established a
connection with the same Device).
RedundancyCommOutOfRxBuffersErr 222 Redundancy communication out-of-RX-buffers
error. The redundancy subsystem cannot receive
any more redundancy messages because the RX
buffers have been exhausted. This is a drop-sync
trigger because received messages are discarded
until RX buffers are freed resulting in suspect
redundancy communication.
RedundancyCommQueueFull 223 Redundancy communication queue is full error.
The redundancy subsystem has received more

- 2562 -
Chapter 20 - Rxxxx Parameters

communication events than it can process


resulting in queue overflow. This is a drop-sync
trigger because received messages are discarded
until queue entries are freed resulting in suspect
redundancy communication.
LiveListReadFailedLink1 224 Live List reads fail on Link 1. The primary
controller triggers switchover (with this reason)
when the primary can no longer read and verify
its copy of the Fieldbus Live List. The secondary
controller aborts synchronization (with this
reason) when the secondary can no longer read
and verify its copy of the Fieldbus Live List. This is
typically caused by bad wiring, bad hardware, or
both. 1 - Check that there is no "noise on the wire"
as this prevents normal communications on the
H1 link. 2 - Check for proper termination on the
H1 link. 3 - Check that there are no shorts in the
wiring. 4 - Check that the wiring is properly
shielded. 5 - Check that there are no failed
devices.
LiveListReadFailedLink2 225 Live List reads fail on Link 2. The primary
controller triggers switchover (with this reason)
when the primary can no longer read and verify
its copy of the Fieldbus Live List. The secondary
controller aborts synchronization (with this
reason) when the secondary can no longer read
and verify its copy of the Fieldbus Live List. This is
typically caused by bad wiring, bad hardware, or
both. 1 - Check that there is no "noise on the wire"
as this prevents normal communications on the
H1 link. 2 - Check for proper termination on the
H1 link. 3 - Check that there are no shorts in the
wiring. 4 - Check that the wiring is properly
shielded. 5 - Check that there are no failed
devices.
LiveListReadFailedLink3 226 Live List reads fail on Link 3. The primary
controller triggers switchover (with this reason)
when the primary can no longer read and verify
its copy of the Fieldbus Live List. The secondary
controller aborts synchronization (with this
reason) when the secondary can no longer read
and verify its copy of the Fieldbus Live List. This is
typically caused by bad wiring, bad hardware, or
both. 1 - Check that there is no "noise on the wire"
as this prevents normal communications on the
H1 link. 2 - Check for proper termination on the
H1 link. 3 - Check that there are no shorts in the
wiring. 4 - Check that the wiring is properly
shielded. 5 - Check that there are no failed
devices.
LiveListReadFailedLink4 227 Live List reads fail on Link 4. The primary
controller triggers switchover (with this reason)
when the primary can no longer read and verify
its copy of the Fieldbus Live List. The secondary
controller aborts synchronization (with this
reason) when the secondary can no longer read
and verify its copy of the Fieldbus Live List. This is
typically caused by bad wiring, bad hardware, or
both. 1 - Check that there is no "noise on the wire"

- 2563 -
Chapter 20 - Rxxxx Parameters

as this prevents normal communications on the


H1 link. 2 - Check for proper termination on the
H1 link. 3 - Check that there are no shorts in the
wiring. 4 - Check that the wiring is properly
shielded. 5 - Check that there are no failed
devices.
LiveListReadFailedLink5 228 Live List reads fail on Link 5. The primary
controller triggers switchover (with this reason)
when the primary can no longer read and verify
its copy of the Fieldbus Live List. The secondary
controller aborts synchronization (with this
reason) when the secondary can no longer read
and verify its copy of the Fieldbus Live List. This is
typically caused by bad wiring, bad hardware, or
both. 1 - Check that there is no "noise on the wire"
as this prevents normal communications on the
H1 link. 2 - Check for proper termination on the
H1 link. 3 - Check that there are no shorts in the
wiring. 4 - Check that the wiring is properly
shielded. 5 - Check that there are no failed
devices.
LiveListReadFailedLink6 229 Live List reads fail on Link 6. The primary
controller triggers switchover (with this reason)
when the primary can no longer read and verify
its copy of the Fieldbus Live List. The secondary
controller aborts synchronization (with this
reason) when the secondary can no longer read
and verify its copy of the Fieldbus Live List. This is
typically caused by bad wiring, bad hardware, or
both. 1 - Check that there is no "noise on the wire"
as this prevents normal communications on the
H1 link. 2 - Check for proper termination on the
H1 link. 3 - Check that there are no shorts in the
wiring. 4 - Check that the wiring is properly
shielded. 5 - Check that there are no failed
devices. LiveListReadFailedLink7
230 Live List reads fail on Link 7. The primary
controller triggers switchover (with this reason)
when the primary can no longer read and verify
its copy of the Fieldbus Live List. The secondary
controller aborts synchronization (with this
reason) when the secondary can no longer read
and verify its copy of the Fieldbus Live List. This is
typically caused by bad wiring, bad hardware, or
both. 1 - Check that there is no "noise on the wire"
as this prevents normal communications on the
H1 link. 2 - Check for proper termination on the
H1 link. 3 - Check that there are no shorts in the
wiring. 4 - Check that the wiring is properly
shielded. 5 - Check that there are no failed
devices.
LiveListReadFailedLink8 231 Live List reads fail on Link 8. The primary
controller triggers switchover (with this reason)
when the primary can no longer read and verify
its copy of the Fieldbus Live List. The secondary
controller aborts synchronization (with this
reason) when the secondary can no longer read
and verify its copy of the Fieldbus Live List. This is
typically caused by bad wiring, bad hardware, or

- 2564 -
Chapter 20 - Rxxxx Parameters

both. 1 - Check that there is no "noise on the wire"


as this prevents normal communications on the
H1 link. 2 - Check for proper termination on the
H1 link. 3 - Check that there are no shorts in the
wiring. 4 - Check that the wiring is properly
shielded. 5 - Check that there are no failed
devices.
ConfigurationAlignment 232 Indicates the controller blocks initial-sync to
perform configuration alignment where the
secondary controller is updated to match the
primary controller’s configuration.
RS232SignalFailure 233 RS232 Signal Failure

RS485SignalFailure 234 RS485 Signal Failure


Ethernet0LinkStatus 235 Ethernet device #0 cable connection status.

Ethernet1LinkStatus 236 Ethernet device #1 cable connection status.

Ethernet2LinkStatus 237 Ethernet device #2 cable connection status.

Ethernet2RingStatus 238 Ethernet device #2 ring switch status.


FirmwareAlignment 239 Indicates the controller blocks initial-sync to
perform firmware alignment where the secondary
controller is updated to match the primary
controller’s firmware version.
OnProcessMigration 240 Firmware Load - On-Process Migration.

OffProcessMigration 241 Firmware Load - Off-Process Migration.

SDCardValidation 242 Check the redundant pair have compatible SD


Cards.
IotaRackSlot1 243 When performing initial-role-determination or
dual role correction upon re-establishing partner
communication, the redundancy subsystem’s role
decision was chosen due to lower slot number.
This reason indicates that the physical ID of the
redundant pair is well formed resulting in slot
number tie breaker.
IotaRackSlot2 244 When performing initial-role-determination or
dual role correction upon re-establishing partner
communication, the redundancy subsystem’s role
decision was chosen due to lower slot number.
This reason indicates that the physical ID of the
redundant pair is well formed resulting in slot
number tie breaker.
DualRoleOnLoad 245 Configuration load resulted in dual-role.

RestartCmd 246 The restart command to the primary controller is


an off-process operation that results in drop-sync
with this reason before performing the
commanded operation.
ResetFactoryDefaultCmd 247 The reset-to-factory-defaults command to the

- 2565 -
Chapter 20 - Rxxxx Parameters

primary controller is an off-process operation that


results in drop-sync with this reason before
performing the commanded operation.
EthernetConfiguration 248 On startup the default Ethernet configuration is
not valid for redundant controller operation when
the controller is at factory default configuration.
Load the controller with a valid configuration to
recover.
SecondaryRuntimeException 249 The secondary controller encountered a common
language runtime exception.
SecondaryReceiveSequence 250 The secondary controller’s common language
runtime application received an erroneous
sequence number.
PreviouslyInitialSyncdSecondary 251 Initial redundancy role of Primary was chosen
because previously retained initial-syncd
secondary role.
DownlinkIoConnectionTimeout 252 I/O communication exception resulted
switchover.
NoDownlinkIoConnections 253 I/O connection count is zero.

PrimaryRuntimeException 254 The primary controller encountered a common


language runtime exception.
RetainedEventsInitialization 255 Retained events initialization.

FlashReadWriteError 256 Internal flash read/write error


MRamReadWriteError 257 Internal MRAM read/write error.
OnlineDiagSoftFailure 258 Online diagnostics detected a soft failure.

OnlineDiagHardFailure 259 Online diagnostics detected a hard failure.


ModeSwitchInStopPosition 260 Inhibit sync when controller is in the stopped
state.
ConfigurationLoad 261 Synchronization is not supported during
configuration load to the controller. The controller
drops and inhibits sync on configuration load with
this transient reason.
PreInitialSyncFail 262 Multiple consecutive pre-initial-sync failures.
After 3 failed attempts to perform pre-initial-sync,
the Auto Sync State is automatically set to
disabled and the inhibit sync reason is set to this
persistent value. Refer to the redundancy history
for the reasons why pre-initial-sync failed, and
issue the Enable Sync command to attempt
initial-sync again after correcting the abort-sync
reason.
ModeSwitchMismatch 263 Synchronization is not supported when the
controllers have mismatched Mode Switch
settings.
SecureBootMismatch 264 Synchronization is not supported when the
controllers have mismatched Secure Boot status.
InvalidBootFirmware 265 The controller has two firmware versions boot
(recovery) and application (product). Steady-state

- 2566 -
Chapter 20 - Rxxxx Parameters

synchronization is not supported while a


controller’s boot firmware is invalid.
ReportConnectionStatus 266 Report Connection Status.
IPSecEnrollmentInfoMismatch 267 Primary does not have IPSec enrollment
information, but secondary does.
IPSecProfileStatusMismatch 268 One or more IPSec profile statuses do not match.
IPSecStatusMismatch 269 IPSec statuses on the primary and secondary do
not match.
IPSecSynchronizationFailure 270 Failure attempting to send IPSec related
synchronization data to the secondary controller.

Default NA
Config Load No
Active loadable No
Access Lock Viewonly
Residence Controller
Related RDNDELAYAVG, STATSRESET
Parameters
Remarks Historical maximum redundancy delay CPU value observed since last store to
STATSRESET.

Specific to ACE
Block(s)
Description Redundancy History Reason
Data Type ENUMERATION
Range
Default
Config Load No
Active No
loadable
Access Lock Viewonly
Residence ACE
Related RDNHISTSTATE [1...15], RDNHISTTIME[1...15], RDNINHIBITSYNC
Parameters
Remarks This parameter provides rational for the occurrence of a redundancy history state.
It also includes rational for the following:
l LOS: Loss-of-synchronization
l IS: Commencing initial synchronization
l IR: Initial Redundancy Role Determination
l CMPT : Partner Compatibility
l ROLE : Redundancy Role Change
l SYNC : Loss-of-Sync and Commencing Initial Sync
Historical maximum redundancy delay CPU value observed since last store to
STATSRESET.

- 2567 -
Chapter 20 - Rxxxx Parameters

20.119 RDNHISTSTATE [1...15]

- 2568 -
Chapter 20 - Rxxxx Parameters

Specific to C300 and FIM4 FBs, PGM, EIM, TCMI


Block(s)
Description Redundancy History State - Indicates the last 16 milestones within redundancy
related activities. Refer to the corresponding RDNHISTREASON entry for additional
information (when applicable).
Data Type Enumeration

- 2569 -
Chapter 20 - Rxxxx Parameters

Range --- (0) N/A history state null entry.

- 2570 -
Chapter 20 - Rxxxx Parameters

Startup (1) Module released from reset.

- 2571 -
Chapter 20 - Rxxxx Parameters

NonRedun (2) Module configured as non-redundant.

- 2572 -
Chapter 20 - Rxxxx Parameters

Primary (3) Module transitioned into the Primary


redundancy role. Refer to the associated
RDNHISTREASON for the reason why.
Secondary (4) Module transitioned into the Secondary
redundancy role. Refer to the associated
RDNHISTREASON for the reason why.
NoPartner (5) Partner absent synchronization state.
This module is not communicating with
a redundant partner This could be due
to a fault in the redundancy private
path, a fault in the redundancy
communication electronics, or simply
because the partner is powered off.
Incompatible (6) Incompatible synchronization state. This
module is communicating with a partner
across the redundancy private path, but
that partner is incompatible. Refer to the
associated RDNHISTREASON for the
reason why.
PartnerVisble (7) Partner visible synchronization state.
This module is communicating with a
compatible redundancy partner.
SyncInProgress (8) Synchronization in progress
synchronization state. This module is
performing initial transfer of
redundancy data from the primary to
the secondary. Redundancy role change
is not possible in this state.c Initial
synchronization takes on the order of 90
seconds for the C200, 180 seconds for
the C300, and less than a minut for
other redundant controller types.
Synchronized (9) Synchronized synchronization state.
This redundant pair has completed
initial synchronization and is performing
continuous synchronization
maintenance. Redundancy role change
is allowed in this state.
Standby (10) Standby synchronization state. The
purpose of the Standby mode of
operation is to improve the software
upgrade scenario by providing the user
with a convenient means to fallback to a
previous software and database, if
problems are encountered during
upgrade. While in the Standby State, the
secondary controller has a database
that was previously synchronized with
the primary controller but the secondary
is no longer receiving synchronization-
data updates from the primary
controller. Moreover, a Standby
Secondary controller is able to
switchover into the primary role with this
stale database. There is no time limit to
the time duration of the Standby mode
of operation, and as a consequence of

- 2573 -
Chapter 20 - Rxxxx Parameters

the secondary not being synchronized,


switchover to the secondary may cause
a bump in outputs. To ensure operator
intervention, the C300 CEE execution
state is forced to Idle on switchover out
of the Standby State.
AutoSyncDsbled (11) Auto synchronization disabled. Refer to
the associated RDNHISTREASON for the
reason why.
AutoSyncEnbled (12) Auto synchronization enabled. This
transition only occurs on the receipt of
the Enable Sycnhronization command.
AlternateSyncCommand (13) Module received the Alternate
Synchronization Command. When the
primary redundancy electronics are
faulted, this is used to perform one-time
initial-sync over FTE (instead of the
redundancy private path) followed by
immediate switchover.
BecomePrimaryCommand (14) Module received the Become Primary
command. This commands an
unsynchronized secondary module to
transition into the primary role in the
absence of a partner module. More
specifically, this command is only
applicable if the unsynchronized
secondary has no view to a partner
module across the redundancy cable
and the primary IP address is not
occupied.
DisableSyncCommand (15) Module received the Disable Sync
Command. This is used to drop
synchronization for a module in the
syncing/syncd/standby state and
prevent future initial-sync attempts by
disabiling Auto-Sync.
EnableSyncCommand (16) Module received the Enable Sync
Command. This transitions the Auto-
Sync state to Enabled, resets the initial-
sync failure count (to allow maximum of
3 trys), and triggers initial-sync.
EnableStandbyCommand (17) Module received the Enable Standby
Command. This commands a redundant
controller pair in the Synchronization
Maintenance State to switchover into
the Standby State. While in the Standby
State, the secondary controller has a
database that was previously
synchronized with the primary controller
but the secondary is no longer receiving
synchronization-data updates from the
primary controller. This command is
useful for testing the expected behavior
of a configured control strategy if the
redundant controller pair ever had to
invoke the Go-Back option during a
controller On-Process Migration. More

- 2574 -
Chapter 20 - Rxxxx Parameters

specifically, after entering the Standby


State, issue the switchover command,
and the controller with the stale
database switches into the primary role
with the CEE execution state set to Idle.
The Disable Synchronization command
exits the Standby State.
SyncAbort (18) Encountered loss-of-sync condition.
Refer to the associated
RDNHISTREASON for the reason why.
RoleChange (19) Redundancy Role Change occurred.
Refer to the associated
RDNHISTREASON for the reason why.
InitialSyncFail (20) Once the Auto Sync State is enabled,
loss of synchronization is automatically
followed by an automatic attempt to re-
synchronize the redundant controller
pair. However, after a maximum of 3
initial-sync failures, the Auto Sync State
is disabled with an inhibit sync reason of
Initial Sync Fail. Once initial-sync is
inhibited due to “Initial Sync fail”, the
Enable Synchronization command must
be used to retry initial-sync (after the
problem preventing initial-sync has
been resolved).
AbortSync (21) Encountered loss-of-sync condition.
Refer to the associated
RDNHISTREASON for the reason why.
AllowSync (22) Indicates negation of an inhibit sync
reason. Refer to the associated
RDNHISTREASON for the specific inhibit
sync reason.
InhibitSync (23) Indicates assertion of an inhibit sync
reason. Refer to the associated
RDNHISTREASON for the specific inhibit
sync reason.
ControllabilityBetter (24) This module is better able to control.
Refer to the associated
RDNHISTREASON for the reason why.
For example, when this module has view
to FTE but partner does not.
ControllabilityEqual (25) Both modules of a redundant pair are
equally able to control.
ControllabilityWorse (26) This module is worse able to control.
Refer to the associated
RDNHISTREASON for the reason why.
For example, when this module does not
have view to FTE but partner does.
OpmSessionEnabled (27) The Controller Migration Wizard has
commenced a controller On-Process
Migration session.
OpmBlocksCreated (28) As part of an OPM session, the Migration
Wizard completed Secondary
Checkpoint Restore to instantiate the

- 2575 -
Chapter 20 - Rxxxx Parameters

control strategy on the secondary


controller.
OpmInitialSync (29) Controller Migration Wizard commanded
the controller to commence initial-sync
as part of an OPM session.
OpmOpenIoConnections (30) The primary controller has commenced
transfer of I/O connection related data
as part of initial-sync during an OPM
session.
OpmMatchPeerReferences (31) The primary controller has commenced
transfer of CDA Peer Cross-Reference
ID data as part of initial-sync during an
OPM session.
OpmTransferData (32) The primary controller has commenced
transfer of Block Dynamic Data as part
of initial-sync during an OPM session.
From this point forward, control is frozen
on the primary controller for up to 10/20
seconds on the C200/C300 platform
(depending on the size of the control
strategy). Control is resumed either
following the switchover (upon
completing OPM initial-sync) or on
abnormal termination of the OPM
session.
OpmSessionSuccess (33) Upon the successful completion of OPM
initial-sync, switchover follows shortly
after (for example, <100 ms). This
represents successful completion of the
controller OPM session.
OpmSessionFailure (34) OPM session terminated due to failure.
Refer to the associated
RDNHISTREASON for the reason why.
RedundancyCommunicationError (35) Redundancy Communication Error.
Refer to the associated
RDNHISTREASON for the reason why.
BecomePrimaryDecision (36) When redundancy communication is
established after both modules are
committed to the same redundancy role,
the redundancy subsystem trys to
correct dual-role situations. This module
has won primaryship in a dual primary
situation. Refer to the associated
RDNHISTREASON for the reason why.
BecomeSecondaryDecision (37) When redundancy communication is
established after both modules are
committed to the same redundancy role,
the redundancy subsystem trys to
correct dual-role situations. This module
has won secondaryship in a dual
secondary situation. Refer to the
associated RDNHISTREASON for the
reason why.
SwitchoverTrigger (38) Redundancy role change has been
requested. Refer to the associated
RDNHISTREASON for the reason why.

- 2576 -
Chapter 20 - Rxxxx Parameters

OpmPartialColdInit (39) In the event that one or more blocks


have not yet implemented OPM support,
the default behavior is to cold initialize
that block. This indicates that one or
more blocks have been cold initialized.
This represents successful completion
of the controller OPM session.
ConfiguredRedundant 40 The controller is configured as
redundant as it received the
MODISREDUN parameter set to true.
ConfiguredNonRedundant 41 The controller is configured as non-
redundant as it received the
MODISREDUN parameter set to false.
PhysicalIdA 42 [WDM] Physical ID changed to A. On the
primary, the user issued the command
to toggle physical ID. On the secondary,
either the secondary’s physical ID was
the same as that of primary (i.e.
automatic correction) or the user issued
the command to toggle physical ID.
PhysicalIdB 43 [WDM] Physical ID changed to B. On the
primary, the user issued the command
to toggle physical ID. On the secondary,
either the secondary’s physical ID was
the same as that of primary (i.e.
automatic correction) or the user issued
the command to toggle physical ID.
UCNAddrChg 44 Redundancy Role Change occurred for a
UCN resident controller. Refer to the
associated RDNHISTREASON for the
reason why.
UpgStartTask 45 C200-to-C300 Upgrade: Start Task
UpgConnOpened 46 C200-to-C300 Upgrade: Connection
Opened
UpgResetEnable 47 C200-to-C300 Upgrade: Reset Enable
UpgSessionComplete 48 200-to-C300 Upgrade: Session Complete
UpgConnFailed 49 C200-to-C300 Upgrade: Conn to the
Targets Failed
UpgResetFailed 50 C200-to-C300 Upgrade: Reset Targets
Failed
UpgBecomePriCmd 51 C200-to-C300 Upgrade: Become Primary
command
CutoverStart 52
InitialSyncd 53 Post Initial Sync is in progress.
UserCommand 54 User triggered command.
ProgramCommand 55 Program triggered command.
Default - - - (0)
Config No
Load
Active No
Loadable

- 2577 -
Chapter 20 - Rxxxx Parameters

Access ViewOnly
Lock
Residence Controller
Related RDNINHIBITSYNC, RDNHISTREASON [1...15], RDNHISTTIME[1...15]
Parameters
Remarks

Specific to ACE
Block(s)
Description Redundancy History State
Data Type ENUMERATION
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Controller
Related RDNHISTREASON [1...15], RDNHISTTIME[1...15], RDNINHIBITSYNC
Parameters
Remarks This parameter indicates the last 16 milestones within redundancy related
activities. Refer to the corresponding RDNHISTREASON entry for additional
information (when applicable).

20.120 RDNHISTTIME[1...15]

Specific to Block(s) C300 and FIM4 FBs, PGM , ACE, EIM, TCMI
Description Time - Indicates wall clock time of redundancy history state change.
Data Type TIME
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4, PGM, ACE
Related Parameters RDNINHIBITSYNC, RDNHISTREASON [1...15], RDNHISTSTATE [1...15]
Remarks

- 2578 -
Chapter 20 - Rxxxx Parameters

20.121 RDNHISTREASON

Specific to Block(s) UOC, TCMI


Description Reason
Data Type ENUM
Range N/A
Default -
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.122 RDNHISTSTATE

Specific to Block(s) UOC


Description Event
Data Type ENUM
Range N/A
Default -
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.123 RDNINHIBITSYNC

Specific to Platform Blocks for C200, C300, FTEB, FIM, FIM4, IOLIM, LIOM, PGM, EIM, TCMI
Block(s)
Description Redundancy Inhibit Synchronization - Indicates the current reason why initial sync
is inhibited. In the case of the C300/FIM4, this parameter is non-null when the
redundant controller pair are not synchronizing/synchronized/standby. For the
other controller types (C200, FIM, FTEB, IOLIM, and LIOM), this parameter is only
non-null when any one of the modules has explicit reason to inhibit sync.
Data Type Enumeration
Range --- (0) N/A because controller is
synchronizing or is synchronized.

- 2579 -
Chapter 20 - Rxxxx Parameters

PartnerRequest (34) ROLE/SYNC: Partner Requested


operation. The redundant partner
has either requested initial-sync to
be inhibited/aborted or for role
change. Refer to the partner's
redundancy history parameter for
the actual reason.
PartnerAbsent (37) SYNC: Partner module absent.
Initial-sync is not applicable
without a redundant partner.
PartnerNotCompatible (38) SYNC: Partner module not
compatible. Initial-sync is not
applicable with an incompatible
redundant partner.
AutoSyncState (54) SYNC: Auto Sync state is disabled.
Initial sync is inhibited while the
Auto Sync State is set to disabled.
This is a persistent inhibit sync
reason that is canceled via the
Enable Sync command.
FteCableStatus (62) SYNC: FTE cable status. Indicates
that either both FTE cables have
been disconnected (that is, FTE
lonely) or at least one FTE cable
has been reconnected. The
primary triggers switchover due to
dual-FTE-cable disconnect. The
secondary inhibits sync due to
dual-FTE-cable disconnect. This
persistent inhibit sync reason can
only be canceled by restoring FTE
communications with the
secondary.
Link1NvsCommands (63) SYNC: Link 1 Flash operations.
Synchronization is aborted and/or
initial-sync is inhibited during the
database initialization that occurs
upon I/O Link FB commanded
NVS compaction.
OpmRequired (64) SYNC: Controller OPM required
but not yet enabled. Initial-sync is
not allowed when the application
firmware versions for the primary
and secondary controllers are
different (for those platforms
sensitive to difference in firmware
versions that is, C200/C300). The
Controller Migration Wizard must
be used to perform On-Process
Migration.
StartupInProgress (78) SYNC: Platform startup in
progress. Initial sync is not allowed
until after the C300/FIM4 has
completed system startup. This is a
transient inhibit sync reason that
is usually not seen.
PlatformFunctionBlockLoadState (79) SYNC: Platform FB load state.

- 2580 -
Chapter 20 - Rxxxx Parameters

Initial-sync is not allowed until


after the Platform FB has been
loaded to the controller.
RedundancyConfigurationState (80) SYNC: Platform configured as
non-redundant. Initial-sync is not
allowed when explicitly configured
as non-redundant. This persistent
inhibit sync reason can only be
canceled by reconfiguring the
non-redundant C300/FIM4 FB as
redundant.
InitialSyncDelay (88) SYNC: Anti thrash delay in
between initial sync attempts.
There is a guaranteed 30 second
delay in between initial-sync
attempts. More specifically, for 30
seconds after a compatible partner
is identified, initial-sync is inhibited
with this transient reason.
InitialSyncFail (89) SYNC: Multiple consequtive initial
sync failures after 3 failed
attempts to perform initial-sync,
the Auto Sync State is
automatically set to disabled and
the inhibit sync reason is set to
this persistent value. Refer to the
redundancy history for the
reasons why initial-sync failed,
and issue the Enable Sync
command to attempt initial-sync
again after correcting the abort-
sync reason.
DroppingSync (90) SYNC: Drop-synchronization in
progress. Initial-sync cannot
commence until the previous
abort sync operation has been
completed. This is a transient
inhibit sync reason that is usually
not seen.
CeeLoadOrDelete (92) SYNC: Synchronization cannot be
maintained during the database
initialization that occurs upon CEE
FB load or delete. This is a
transient inhibit sync reason that
is usually not seen.
UnsupportedHardwareVersion (93) SYNC: Unsupported controller HW
version. Initial-sync is inhibited for
controller hardware version that
does not support controller
redundancy.
Link1LoadState (107) SYNC: Link 1 load has not
completed/occured. Initial-sync is
not allowed to commence until
after all link function blocks have
been loaded. This persistent
inhibit sync reason is negated
upon load of the link function

- 2581 -
Chapter 20 - Rxxxx Parameters

block to the controller.

- 2582 -
Chapter 20 - Rxxxx Parameters

Link2LoadState (108) SYNC: Link 2 load has not


completed/occured. Initial-sync is
not allowed to commence until
after all link function blocks have
been loaded. This persistent
inhibit sync reason is negated
upon load of the link function
block to the controller.
Link3LoadState (109) SYNC: Link 3 load has not
completed/occured. Initial-sync is
not allowed to commence until
after all link function blocks have
been loaded. This persistent
inhibit sync reason is negated
upon load of the link function
block to the controller.
Link4LoadState (110) SYNC: Link 4 load has not
completed/occured. Initial-sync is
not allowed to commence until
after all link function blocks have
been loaded. This persistent
inhibit sync reason is negated
upon load of the link function
block to the controller.
Link5LoadState (111) SYNC: Link 5 load has not
completed/occured. Initial-sync is
not allowed to commence until
after all link function blocks have
been loaded. This persistent
inhibit sync reason is negated
upon load of the link function
block to the controller.
Link6LoadState (112) SYNC: Link 6 load has not
completed/occured. Initial-sync is
not allowed to commence until
after all link function blocks have
been loaded. This persistent
inhibit sync reason is negated
upon load of the link function
block to the controller.
Link7LoadState (113) SYNC: Link 7 load has not
completed/occured. Initial-sync is
not allowed to commence until
after all link function blocks have
been loaded. This persistent
inhibit sync reason is negated
upon load of the link function
block to the controller.
Link8LoadState (114) SYNC: Link 8 load has not
completed/occured. Initial-sync is
not allowed to commence until
after all link function blocks have
been loaded. This persistent
inhibit sync reason is negated
upon load of the link function
block to the controller.
Link2NvsCommands (145) SYNC: Link 2 Flash operations.

- 2583 -
Chapter 20 - Rxxxx Parameters

Synchronization is aborted and/or


initial-sync is inhibited during the
database initialization that occurs
upon I/O Link FB commanded
NVS compaction.
Default ---
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence Controller
Related ALTSYNCCMD, DSBLSYNCCMD, ENBLSYNCCMD
Parameters
Remarks

Specific to ACE
Block(s)
Description Redundancy Inhibit Synchronization - Indicates the current reason why initial sync
is inhibited. In the case of the C300/FIM4, this parameter is non-null when the
redundant controller pair are not synchronizing/synchronized/standby. For the
other controller types (C200, FIM, FTEB, IOLIM, and LIOM), this parameter is only
non-null when any one of the modules has explicit reason to inhibit sync.
Data Type Enumeration
Range ---
Default ---
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related ALTSYNCCMD, DSBLSYNCCMD, ENBLSYNCCMD
Parameters
Remarks

Specific to Block(s) UOC


Description Inhibit Sync Reason
Data Type ENUM
Exposure OUTPUT
Range N/A
Default -
Config Load No
Active Loadable

- 2584 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.124 RDNISTIMEMAX

Specific to Platform Blocks for C200, C300, FTEB, FIM, FIM4, IOLIM, LIOM, PGM, ACE, EIM,
Block(s) TCMI
Description Max Initial Sync Time - Indicates the maximum initial synchronization time in
seconds. This is a high-water mark for all the previous successfully completed
initial-sync attempts.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Controller
Related STATRESET
Parameters
Remarks This parameter is reset upon issuing the platform block's Stats Reset command.

Specific to Block(s) UOC


Description Max Initial Sync Time (sec)
Data Type UINT32
Exposure OUTPUT
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

- 2585 -
Chapter 20 - Rxxxx Parameters

20.125 RDNLINKACTIVE

Specific to
Block Platform Blocks for ACE
Description Cutover Link Active
Data Type BOOLEAN
OFF - The module is configured as redundant and its redundancy private path is
broken (for example, cable disconnect) or the module is configured as non-
redundant. ON - The redundancy private path is connected to the partner module
Range to start the cut-over.
Default OFF
Config
Load No
Active
Loadable No
Access Lock ViewOnly
Residence Controller
Related
Parameters GWHOSTNAMEPRI, MODHASBKUP

This parameter indicates the status of the redundancy path between ACERM’s. This
parameter is set as "ON "when the redundancy path is established between the
primary and secondary ACERM’s. The redundancy path is established when the
Remarks cut-over is enabled and is disabled after the cut-over.

20.126 RDNLINKFAILED

Specific to Platform Blocks for C300, FIM4, and PGM, EIM, TCMI
Block(s)
Description Redundancy Link Failed - Indicates the status of the redundancy private path
between redundant partners.
Data Type Boolean
Range Off 0 Either {1} the redundancy
private path is connected
to a powered partner
module or {2} this module
is configured as non-
redundant.
On 1 This module is configured
as redundant, and either
its redundancy private path
is broken (for example,
cable disconnect) or the
partner module is not able
to respond.
Default Off (0)
Config No
Load
Active No

- 2586 -
Chapter 20 - Rxxxx Parameters

Loadable
Access ViewOnly
Lock
Residence Controller
Related
Parameters
Remarks For C300, FIM4, and PGM: The RDNLINKFAILED parameter is set ON when the
redundancy private path is disconnected and/or partner is not running. Once the
redundancy private path cable is reconnected to a running partner, the
RDNLINKFAILED parameter is set OFF. Note that this parameter reflects the
physical status of the cable (that is, connected versus disconnected) and in no way
indicates if the redundancy private path cable is connected to a compatible partner.
The “Redundancy Link Inactive” and “Redundancy Link Active” notifications are
generated when the RDNLINKFAILED parameter is set ON and OFF, respectively.

Specific to Block(s) UOC


Description Redundancy Link Failed
Data Type BOOLEAN
Exposure OUTPUT
Range N/A
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

- 2587 -
Chapter 20 - Rxxxx Parameters

20.127 RDNLOS

- 2588 -
Chapter 20 - Rxxxx Parameters

Specific to IOLIM, FIM, CPM, FTEB


Block(s)
Description Redundancy Loss of Synchronization
Data Type Enumeration

- 2589 -
Chapter 20 - Rxxxx Parameters

Range None (0) No loss-of-sync condition asserted.

- 2590 -
Chapter 20 - Rxxxx Parameters

ClnPointBuff (1) Encountered a communication buffer overflow condition while


performing clean-point processing. Logged as LOS_CLNPT_
BUFF_OVERFLOW within the RM event log.
ClnPointFifo (2) Encountered a tracker FIFO overflow condition while performing
clean-point processing. Logged as LOS_CLNPT_FIFO_
OVERFLOW within the RM event log.
ClnPointTmo (3) Encountered a timeout condition while performing clean-point
processing. Logged as LOS_CLNPT_IDLE_TIMEOUT within the
RM event log.
ClnPointRx (4) Encountered a track-data connection receipt error while
performing clean-point processing. Logged as LOS_CLNPT_RX_
FAILURE within the RM event log.
ClnPointTx (5) Encountered a track-data connection transmission error while
performing clean-point processing. Logged as LOS_CLNPT_TX_
FAILURE within the RM event log.
ConfigLdBusy Temporary loss-of-sync occurrence due to either {1} Primary
(6) CPM FB create and/or delete or {2} first time CCL load. Logged as
LOS_CPM_CONFIG_LOAD within the RM event log.
ConfigLdDone Not a loss-of-sync condition; this event used to trigger initial sync
(7) upon completion of the action that incurred the ConfigLdBusy
RDNLOS State. Logged as SYN_CPM_CONFIG_LOAD within the
RM event log.
CrossLoadErr Logged as LOS_CROSSLOAD_ERROR within the RM event log.
(8)
ResrcLocked (9) Logged as LOS_EDIT_RESOURCE_LOCKED within the RM event
log.
ExecSyncTmo Logged as LOS_EXEC_SYNC_TIMEOUT within the RM event log.
(10)
IoPurgeBusy Logged as LOS_IOMGR_PURGE within the RM event log.
(11)
MemIsrBuff (12) Encountered a communication buffer overflow condition while
servicing a memory-board interrupt. Logged as LOS_ISR_BUFF_
OVERFLOW within the RM event log.
MemIsrFifo (13) Encountered a tracker FIFO overflow condition while servicing a
memory-board interrupt. Logged as LOS_ISR_FIFO_OVERFLOW
within the RM event log.
MemIsrRx (14) Encountered a track-data connection receipt error while
servicing a memory-board interrupt. Logged as LOS_ISR_RX_
FAILURE within the RM event log.
MemIsrTx (15) Encountered a track-data connection transmission error while
servicing a memory-board interrupt. Logged as LOS_ISR_TX_
FAILURE within the RM event log.
KeepAlvBuff (16) Encountered a communication buffer overflow condition while
performing a Keep Alive transmission. Logged as LOS_KPALV_
BUFF_OVERFLOW within the RM event log.
KeepAlvFifo (17) Encountered a tracker FIFO overflow condition while performing
a Keep Alive transmission. Logged as LOS_KPALV_FIFO_
OVERFLOW within the RM event log.
KeepAlvRx (18) Encountered a track-data connection receipt error while
performing a Keep Alive transmission. Logged as LOS_KPALV_
RX_FAILURE within the RM event log.

- 2591 -
Chapter 20 - Rxxxx Parameters

KeepAlvTx (19) Encountered a track-data connection transmission error while


performing a Keep Alive transmission. Logged as LOS_KPALV_
TX_FAILURE within the RM event log.
PartnAbsent Logged as LOS_PARTNER_ABSENT within the RM event log.
(20)
PartnNotCmpt Logged as LOS_PARTNER_INCOMPATIBLE within the RM event
(21) log.
PartnStartup Logged as LOS_PARTNER_STARTUP within the RM event log.
(22)
BlkMoveBuff Encountered a communication buffer overflow condition while
(23) packaging Redundancy Data for transfer to the secondary.
Logged as LOS_MOVE_BUFF_OVERFLOW within the RM event
log.
BlkMoveFifo (24) Encountered a tracker FIFO overflow condition while packaging
Redundancy Data for transfer to the secondary. Logged as LOS_
MOVE_FIFO_OVERFLOW within the RM event log.
BlkMoveRx (25) Encountered a track-data connection receipt error while
packaging Redundancy Data for transfer to the secondary.
Logged as LOS_MOVE_RX_FAILURE within the RM event log.
BlkMoveTx (26) Encountered a track-data connection transmission error while
packaging Redundancy Data for transfer to the secondary.
Logged as LOS_MOVE_TX_FAILURE within the RM event log.
RmConnTmo Logged as LOS_RM_CONNECTION_TIMEOUT within the RM
(27) event log.
SyncIdleTmo Logged as LOS_SD_IDLE_TIMEOUT within the RM event log.
(28)
ClnPointSeq Logged as LOS_SEC_CLNPT_SEQ_ERROR within the RM event
(29) log.
SyncSeqError Logged as LOS_SEC_SD_SEQ_ERROR within the RM event log.
(30)
AccFormat (31) Logged as LOS_SEC_TD_ACC_FORMAT within the RM event log.
AccOverrun (32) Logged as LOS_SEC_TD_ACC_OVERRUN within the RM event
log.
CommitFormat Logged as LOS_SEC_TD_COMMIT_FORMAT within the RM event
(33) log.
TrkSeqError (34) Logged as LOS_SEC_TD_SEQ_ERROR within the RM event log.

UnpackFormat Logged as LOS_SEC_TD_UNPACK_FORMAT within the RM event


(35) log.
SwitchovrTst Logged as LOS_SWITCHOVER_TEST within the RM event log.
(36)
SyncCksumErr Logged as LOS_SYNC_CHECKSUM_FAIL within the RM event
(37) log.
PriSyncHwErr Logged as LOS_SYNC_HW_FAILURE_PRI within the RM event
(38) log.
SecSyncHwErr Logged as LOS_SYNC_HW_FAILURE_SEC within the RM event
(39) log.
TrkBuffTmo (40) Logged as LOS_TD_BUFFER_TIMEOUT within the RM event log.
TrkPndRxFail Logged as LOS_TD_PNDING_RX_FAILURE within the RM event

- 2592 -
Chapter 20 - Rxxxx Parameters

(41) log.

- 2593 -
Chapter 20 - Rxxxx Parameters

TrkPndTxFail Logged as LOS_TD_PNDING_TX_FAILURE within the RM event


(42) log.
IoPurgeDone Not a loss-of-sync condition; this event used to trigger initial sync
(43) upon completion of the action that incurred the IoPurgeBusy
RDNLOS State. Logged as SYN_IOMGR_PURGE_COMPLETE
within the RM event log.
PartnStarted Not a loss-of-sync condition; this event used to trigger initial sync
(44) upon completion of the action that incurred the PartnStartup
RDNLOS State. Logged as SYN_PARTNER_STARTUP within the
RM event log.
PseudoDbWr Logged as DBG_PSEUDO_DATABASE_WRITES within the RM
(45) event log.
SyncConnOpen Logged as LOS_SD_CONN_OPEN_FAILURE within the RM event
(46) log.
SyncConnRx Logged as LOS_SD_CONN_RX_FAILURE within the RM event log.
(47)
SyncConnTx Logged as LOS_SD_CONN_TX_FAILURE within the RM event log.
(48)
TrkConnOpen Logged as LOS_TD_CONN_OPEN_FAILURE within the RM event
(49) log.
TrkConnRx (50) Logged as LOS_TD_CONN_RX_FAILURE within the RM event log.

SecCommitTmo Logged as LOS_CLNPT_COMMIT_TIMEOUT within the RM event


(51) log.
ResrcClrBusy Logged as LOS_EDIT_RSRC_CLR_INPROG within the RM event
(52) log.
ResrcClrDone Not a loss-of-sync condition; this event used to trigger initial sync
(53) upon completion of the action that incurred the ResrcClrBusy
RDNLOS State. Logged as SYN_EDIT_RSRC_CLR_DONE within
the RM event log.
SecUnknown Logged as LOS_UNKNOWN_SECONDARY within the RM event
(54) log.
CombufAlloc Logged as LOS_COMBUF_ALLOC within the RM event log.
(55)
QueueSyncData Logged as LOS_QUEUE_SYNC_DATA within the RM event log.
(56)
InitSyncTmo Logged as LOS_INITIAL_SYNC_TIMEOUT within the RM event
(57) log.
PriAppAbort (58) Logged as LOS_PRIMARY_APP_ABORT within the RM event log.
SecAppAbort Logged as LOS_SECONDARY_APP_ABORT within the RM event
(59) log.
PriAppError (60) Logged as LOS_PRIMARY_APP_ERROR within the RM event log.
SecAppError Logged as LOS_SECONDARY_APP_ERROR within the RM event
(61) log.
PriAppBusy (62) Logged as LOS_PRIMARY_APP_BUSY within the RM event log.
PriAppDone (63) Not a loss-of-sync condition; this event used to trigger initial sync
upon completion of the action that incurred the PriAppBusy
RDNLOS State. Logged as SYN_PRIMARY_APP_DONE within the
RM event log.

- 2594 -
Chapter 20 - Rxxxx Parameters

SecAppBusy (64) Logged as LOS_SECONDARY_APP_BUSY within the RM event


log.
SecAppDone Not a loss-of-sync condition; this event used to trigger initial sync
(65) upon completion of the action that incurred the SecAppBusy
RDNLOS State. Logged as SYN_SECONDARY_APP_DONE within
the RM event log.
PriUnknown Logged as LOS_UNKNOWN_PRIMARY within the RM event log.
(66)
IndSyncDis (67) Logged as LOS_INDIRSYNC_DISABLED within the RM event log.
IndSyncEnb (68) Logged as LOS_INDIRSYNC_ENABLED within the RM event log.

IndSyncWait Logged as LOS_INDIRSYNC_CMD_WAIT within the RM event log.


(69)
IndSyncXfer Not a loss-of-sync condition; this event used to trigger initial sync
(70) upon completion of the action that incurred the IndSyncWait
RDNLOS State. Logged as SYN_INDIRSYNC_TRANSFER within
the RM event log.
SecSnapTmo Logged as LOS_SEC_SNAPSHOT_TIMEOUT within the RM event
(71) log.
IndSyncAbort Logged as LOS_INDIRSYNC_ABORTED within the RM event log.
(72)
IndSyncFail (73) Logged as LOS_INDIRSYNC_FAILED within the RM event log.
IndSyncTmo Logged as LOS_INDIRSYNC_TIMEOUT within the RM event log.
(74)
Default None (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, FIM, C200
Related
Parameters
Remarks

20.128 RDNMACADDR

Specific to Block(s) UOC


Description Redundancy MAC Address
Data Type STRING
Exposure OUTPUT
Range NA
Default
Config Load No
Active Loadable

- 2595 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

Specific to Block(s) TCMI


Description Redundancy MAC Address
Data Type STRING
Exposure OUTPUT
Range NA
Default 00-40-84-14-91-51
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.129 RDNNONTRKMAX

Specific to CEE-C300 block


Block(s)
Description Maximum number of (non-tracked) redundancy parameter sync data bytes
transferred from primary to secondary every cycle
Data Type Floating Point
Range >= 0
Default 0
Config No
Load
Active No
Loadable

- 2596 -
Chapter 20 - Rxxxx Parameters

Access View Only


Lock
Residence CEE
Related RDNCNTCYCMAX RDNCNTCYCTP RDNXFERMAX RDNXFERAVG STATSRESET
Parameters
Remarks While a redundant C300 controller pair is running and synchronized, redundancy
information must be passed from primary to secondary. This keeps the database of
the secondary synchronized with that of the primary so that it is ready to take over if
and when the primary fails. There are two forms of redundancy information: {1}
tracked address and data bytes and {2} non-tracked parameter sync data bytes.
RDNNONTRKMAX is an array parameter which displays the maximum number of
non-tracked parameter sync data bytes that have been sent from primary C300 to
secondary C300 for each cycle. RDNCNTCYCMAX is an array parameter which
displays the maximum number of tracked address and data bytes that have been
sent from primary C300 to secondary C300 for each cycle. Index values 0 through
39 correspond to the maximum count for cycles 0 through 39 respectively. Index 40
displays the maximum across the maxima for each cycle. The time span of
maximum detection corresponds to reset of the CEE statistics parameters. To
acquire new maxima starting from the present moment, write On to the parameter
CEE.STATSRESET. RDNXFERAVG and RDNXFERMAX represent the total
redundancy transferred bytes/second average and maximum.

20.130 RDNOPMFRZTIME

Specific to Platform Blocks for C200, C300, LIOM, PGM


Block(s)
Description OPM Freeze Ctrl Time (msec) - indicates the duration that control was frozen
during controller On-Process Migration transfer of dynamic data. Controller OPM
aborts due to session timeout after a maximum of 10 seconds for the C200 and
LIOM or 20 seconds for the C300.
Data Type UNIT32
Range >= 0
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence Controller
Related STATSRESET
Parameters
Remarks

Specific to Platform Blocks for ACE


Block(s)
Description OPM Freeze Ctrl Time (msec)
Data Type UNIT32
Range >= 0

- 2597 -
Chapter 20 - Rxxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related STATSRESET
Parameters
Remarks This parameter indicates the duration that control was frozen during controller
On-Process Migration transfer of dynamic data.

- 2598 -
Chapter 20 - Rxxxx Parameters

20.131 RDNOPMSTATUS

- 2599 -
Chapter 20 - Rxxxx Parameters

Specific to Primary Platform Blocks for C200, C300, LIOM, PGM


Block(s)
Description OPM Status - This parameter is used by the Controller Migration Wizard to detect
controller OPM session abnormal termination.
Data Type Enumeration

- 2600 -
Chapter 20 - Rxxxx Parameters

Range --- (0) Controller OPM Disabled.

- 2601 -
Chapter 20 - Rxxxx Parameters

Enabled (1) STEP: Controller Migration Wizard starts a


controller On-Process Migration session.
BlocksCreated (2) STEP: Secondary OPM checkpoint restore to
instantiate the control strategy on the secondary
controller is complete.
InitialSync (3) STEP: Controller Migration Wizard commands the
controller to commence OPM initial-sync.
OpenIoConns (4) STEP: Begin OPM transfer of I/O connection
related data.
MatchPeerRefs (5) STEP: Begin OPM transfer of peer cross-
reference ID data.
TransferData (6) STEP: Begin OPM transfer of dynamic data. From
this point forward, control is frozen on the
primary controller for up to 10 seconds for the
C200 or 20 seconds for the C300 (depending on
the size of the control strategy). Control is
resumed following either the switchover (upon
completing OPM initial-sync) or on abnormal
termination of the OPM session.
SessionComplete (7) STEP: This indicates successful completion of the
controller OPM session.
PartialColdInit (8) WARN: Successful completion of the controller
OPM session but one or more blocks have been
cold initialized. The default behavior when one or
more blocks have not yet implemented OPM
support is to cold initialize the block(s).
CommandedAbort (9) FAIL: Controller Migration Wizard commands the
controller to abort the current OPM session. This
represents unsuccessful OPM session
termination.
CreateBlockTimeout (10) FAIL: Timeout of OPM secondary checkpoint
restore operation. Secondary checkpoint restore
timeout occurs if checkpoint data is stalled for
longer than 2 minutes. This represents abnormal
OPM session termination.
InitialSyncTimeout (11) FAIL: Initial sync does not commence within 2
minutes following the receipt of the Controller
Migration Wizard command to commence initial-
sync. This represents abnormal OPM session
termination.
IoConnsTimeout (12) FAIL: Indicates a loss-of-sync occurrence while
waiting for the secondary controller to form at
least the same number of I/O connections as the
primary controller (as part of initial-sync during
an OPM session). The secondary controller
block's LASTOPMNAME parameter is blank. This
represents abnormal OPM session termination.
This only applies to C200 controllers because it
forms connections directly with the Series A I/O.
As with the C300, connections are formed
between the FTEB and Series A I/O.
IoDataFailure (13) FAIL: Indicates a loss-of-sync occurrence while
transferring I/O connection data (as part of
initial-sync during an OPM session). Although

- 2602 -
Chapter 20 - Rxxxx Parameters

any loss-of-sync triggers this behavior, the most


probable loss-of-sync cause is the inability of the
secondary controller to interpret the I/O
connection data format. The secondary controller
block's LASTOPMNAME parameter is blank in this
case. This represents abnormal OPM session
termination. Note that this applies to both C200
and C300 controllers because they both transfer
Series A I/O Connection data during OPM initial-
sync.
PeerRefsMismatch (14) FAIL: Indicates a loss-of-sync occurrence while
transferring peer cross-reference ID data (as part
of initial-sync during an OPM session). Although
any loss-of-sync triggers this behavior, the most
probable loss-of-sync cause is the presence of a
ghost peer connection reference. A ghost peer
connection reference exists if the primary
controller has knowledge of a peer connection ID
that was not instantiated in the secondary
controller during OPM secondary checkpoint
restore. The secondary controller block's
LASTOPMNAME parameter is blank. This
represents abnormal OPM session termination.
PeerRefsFailure (15) FAIL: Indicates a loss-of-sync occurrence while
transferring peer dynamic data. Although any
loss-of-sync triggers this behavior, the most
probable loss-of-sync cause is the inability of the
secondary controller to interpret the peer
dynamic data format. The secondary controller
block's LASTOPMNAME parameter is blank in this
case. This represents abnormal OPM session
termination.
BlockDataFailure (16) FAIL: Indicates a loss-of-sync occurrence while
transferring Block Dynamic Data. This notification
represents abnormal OPM session termination.
Although any loss-of-sync triggers this behavior,
the most probable loss-of-sync cause is either the
inability of the secondary controller to interpret
the Block Dynamic Data format or the secondary
controller has no destination block to receive the
Dynamic Data. The latter is possible in the
presence of a ghost block; a ghost block exists if
the primary controller has knowledge of a block
that was not instantiated in the Secondary
controller during OPM Secondary Checkpoint
Restore. The Secondary Platform FB's
LASTOPMNAME parameter indicates the name of
the last block to be (on-process) migrated; the
LASTOPMNAME is used to isolate the name of
the first CEE subordinate block that has detected
a dynamic state data error. In the special case of
a ghost block, the LASTOPMNAME is either blank
(because the ghost block name no longer exists
in the ERDB) or indicates the name of a block that
is not loaded to the controller (that is, only exists
on the Control Builder project tree).
SessionTimeout (17) FAIL: The redundancy subsystem aborts
controller OPM if control is frozen (during the
one-time OPM initial-sync transfer of Dynamic

- 2603 -
Chapter 20 - Rxxxx Parameters

Data) longer than the maximum specified time


(that is, 10 seconds for C200 and 20 seconds for
C300).
Default ---
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence C200, C300, PGM
Related
Parameters
Remarks The primary controller updates RDNOPMSTATUS with an enumeration
representing the OPMSTEP/OPMWARN/OPMFAIL notifications generated during
an on-process migration session.

Specific to ACE
Block(s)
Description OPM Status - This parameter is used by the Cutover Migration Wizard to detect
controller OPM session abnormal termination.
Data Type ENUMERATION
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks The primary controller updates RDNOPMSTATUS with an enumeration
representing the OPMSTEP/OPMWARN/OPMFAIL notifications generated during
an on-process migration session.

20.132 RDNPKTRCVAVG

Specific to
Block ACE
Description Average receive in packets/seconds
Data Type FLOAT64
Range
Default 0
Config
Load No

- 2604 -
Chapter 20 - Rxxxx Parameters

Active
Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters None

This parameter displays redundancy packet receive rate average. The average of
the redundancy throughput received by the ACE in packets/seconds. When the
Remarks STATRESET parameter is set as "ON," the average of the redundancy restarts.

20.133 RDNPKTRCVMAX

Specific to
Block ACE
Description Maximum receive in packets/seconds
Data Type FLOAT64
Range
Default 0
Config
Load No
Active
Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters None

This parameter displays redundancy packet receive rate maximum. The maximum
of the redundancy throughput received by the ACE in packets/seconds. When the
Remarks STATRESET parameter is set as "ON," the maximum of the redundancy restarts.

20.134 RDNPKTXMITAVG

Specific to
Block ACE
Description Average transmit in packets/seconds
Data Type FLOAT64
Range
Default 0
Config
Load No
Active
Loadable No

- 2605 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters

This parameter displays redundancy packet transfer rate average. The average of
the redundancy throughput generated by the ACE in packets/seconds. When the
Remarks STATRESET parameter is set as "ON," the average of the redundancy restarts.

20.135 RDNPKTXMITMAX

Specific to
Block ACE
Description Maximum transmit in packets/seconds
Data Type FLOAT64
Range
Default 0
Config
Load No
Active
Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters

This parameter displays redundancy packet transfer rate maximum. The maximum
of the redundancy throughput generated by the ACE in packets/seconds. When the
Remarks STATRESET parameter is set as "ON," the maximum of the redundancy restarts.

20.136 RDNROLESTATE

Specific to C200, C300, FIM4, IOLIM, EHG, LIOM, FTEB, FIM, EHPM , and PGM
Block(s)
Description Redundancy Role - Indicates whether the module is operating as a Primary,
Secondary, or logically Non-Redundant.
Data Type Enumeration
Range Undefined (0) Initial redundancy role not yet
determined.
NonRedun (1) Module configured as non-redundant.
Primary (2) Primary redundancy role.
Secondary (3) Secondary redundancy role.
Default Undefined
Config Load No

- 2606 -
Chapter 20 - Rxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence C300, C200, C300, FIM4, IOLIM, EHG, LIOM, FTEB, FIM, PGM, EHPM , and ACE
Related RDNSYNCSTATE
Parameters
Remarks When module is configured as redundant, primary always reports itself as Primary
and secondary always reports itself as Secondary irrespective of whether or not the
redundant module pair is synchronized.

Specific to Block(s) UOC


Description Redundancy Role
Data Type ENUM
Exposure OUTPUT
Range N/A
Default Undefined
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

Specific to Block(s) TCMI


Description Redundancy Role
Data Type STRING

Exposure OUTPUT
Range N/A
Default Undefined
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks (redundancy parameters, see C300 definition)

- 2607 -
Chapter 20 - Rxxxx Parameters

20.137 RDNRCVAVG

Specific to
Block ACE
Description Average receive in bytes/seconds
Data Type FLOAT64
Range
Default 0
Config
Load No
Active
Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters

This parameter displays redundancy bytes receive rate average. The average of the
redundancy throughput received by the ACE in bytes/seconds. When the
Remarks STATRESET parameter is set as "ON," the average of the redundancy restarts.

20.138 RDNRCVMAX

Specific to
Block ACE
Description Maximum receive in bytes/seconds
Data Type FLOAT64
Range
Default 0
Config
Load No
Active
Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters

This parameter displays redundancy bytes receive rate maximum. The maximum of
the redundancy throughput received by the ACE in bytes/seconds. When the
Remarks STATRESET parameter is set as "ON," the maximum of the redundancy restarts.

- 2608 -
Chapter 20 - Rxxxx Parameters

20.139 RDNRXRATE

Specific to Block(s) ELCN_BRG, ELCN_NODE, TCMI, C300

Description Number of messages received over the redundancy private path per second.

Data Type 32-Bit Integer

Range Total redundancy traffic transfer rate that this device is receiving from its partner.

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related Parameters

Remarks Redundancy tab

20.140 RDNRXRATEMAX

Specific to Block(s) ELCN_BRG, ELCN_NODE, TCMI, C300

Description Highest redundancy traffic transfer rate that this device has received from its
partner.

Data Type 32-Bit Integer

Range Total redundancy traffic transfer rate that this device is receiving from its partner.

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related
Parameters

Remarks Redundancy tab

20.141 RDNSOTIMEMAX

Specific to C300, C200, FIM4, IOLIM, LIOM, FTEB and FIM FBs, and PGM, TCMI
Block(s)
Description Maximum Switchover Time - Indicates the high-water mark with regard to
redundancy switchover time, in milli-seconds.
Data Type 32-Bit Integer
Range Greater than or equal to 0

- 2609 -
Chapter 20 - Rxxxx Parameters

Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, C200, FIM4, IOLIM, LIOM, FTEB, FIM, PGM, and ACE
Related STATSRESET
Parameters
Remarks This parameter is reset by storing to the STATSRESET parameter.

Specific to Block(s) UOC


Description Max Switchover Time (msec)
Data Type UINT32
Exposure OUTPUT
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.142 RDNSYNCPROG

Specific to C300, C200, FIM, IOLIM, FTEB, FIM4 and LIOM FBs Primary EHG, PGM, and
Block(s) TCMI
Description Initial Sync Progress - Indicates the initial synchronization progress in terms of
percent complete.
Data Type 32-Bit Integer
Range 0 to 100
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Controller
Related
Parameters
Remarks Parameter is set to 0 when initial sync is not in progress and it is set to 100
when initial-sync is complete.

- 2610 -
Chapter 20 - Rxxxx Parameters

Specific to Block(s) UOC


Description Initial Sync Progress (%)
Data Type UINT32
Exposure OUTPUT
Range 0 to 4294967295
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.143 RDNSYNCSTATE

Specific to C200, FIM, IOLIM, FTEB, FIM4, EHG, LIOM and C300 FBs, PGM, and ACE
Block(s)
Description Redundant Synchronization State. Shows the current synchronization state of the
module.
Data Type Enumeration
Range NOTINSYNC (0) Not synchronized, Partner absent. Only used with
C200/FIM/IOLIM/FTEB modules.
PARTNERVISBL (1) Not synchronized. Partner is visible.
SYNCINPROG (2) Synchronization is in progress.
SYNCMAINT (3) Synchronized.
STANDBY (4) Standby
- - - (5) N/A because module configured as non-redundant.
NOPARTNER (6) Not synchronized. Partner absent.
INCOMPATIBLE (7) Not synchronized. Communicating with incompatible
partner.
Default NOPARTNER (6)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, FIM, IOLIM, C300, FTEB, FIM4, EHG, LIOM, PGM, and ACE
Related
Parameters
Remarks This parameter indicates level of module synchronization with redundancy partner
module.

- 2611 -
Chapter 20 - Rxxxx Parameters

Specific to Block(s) UOC


Description Synchronization State
Data Type ENUM
Exposure OUTPUT
Range N/A
Default -
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

Specific to Block(s) TCMI


Description Synchronization State
Data Type STRING

Exposure OUTPUT
Range N/A
Default -
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks (redundancy parameters, see C300 definition)

- 2612 -
Chapter 20 - Rxxxx Parameters

20.144 RDNTXRATE

Specific to Block(s)

Description

Data Type

Range

Default

Config Load

Active Loadable

Access Lock

Residence

Related Parameters

Remarks

20.145 RDNTXRATEMAX

Specific to Block C300, FIM4, FIM8, PGM, CN100, UOC, EIM, ELCN, WDM
(s)

Description Maximum number of messages transmitted over the redundancy private path per
second.

Data Type 32-Bit Integer

Range Total redundancy traffic transfer rate that this device is receiving from its partner.

Default 0

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related
Parameters

Remarks Redundancy tab

20.146 RDNXFERAVG

Specific to C300, FIM4, FIM8, PGM, CN100, UOC, EIM, ELCN, WDM, ELCNB, ELCNNODE,
Block(s) EHPM, and ACE
Description Redundancy Transfer Rate Average
Data Type 64-Bit Real Number
Range Greater-than or equal-to 0.00

- 2613 -
Chapter 20 - Rxxxx Parameters

Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, FIM, IOLIM, C300, FTEB, FIM4, PGM, and ACE
Related RDNXFERMAX, STATSRESET
Parameters
Remarks The average of module generated redundancy private path throughput in
bytes/sec. Triggering the STATRESET parameter restarts averaging.

Specific to Block(s) UOC


Description Redundancy Traffic (bytes/sec)
Data Type FLOAT64
Exposure OUTPUT
Range ±1.7E+308
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.147 RDNXFERMAX

Specific to C300, FIM4, FIM8, PGM, CN100, UOC, EIM, ELCN, WDM, ELCNB, ELCNNODE,
Block(s) EHPM, and ACE
Description Redundancy Transfer Maximum (bytes/sec)
Data Type 64-Bit Real Number
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C200, FIM, IOLIM, C300, FTEB, FIM4, PGM, and ACE
Related RDNXFERAVG, STATSRESET.
Parameters
Remarks The historical maximum of module generated redundancy private path
throughput since the last store to STATRESET.

- 2614 -
Chapter 20 - Rxxxx Parameters

Specific to Block(s) UOC


Description Max Redun. Traffic (bytes/sec)
Data Type FLOAT64
Exposure OUTPUT
Range ±1.7E+308
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.148 RDNXMITAVG

Specific to
Block ACE
Description Average transmit in bytes/seconds
Data Type FLOAT64
Range
Default 0
Config
Load No
Active
Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters

This parameter displays redundancy bytes transfer rate average. The average of
the redundancy throughput generated by the ACE in bytes/seconds. When the
Remarks STATRESET parameter is set as "ON," the average of the redundancy restarts.

20.149 RDNXMITMAX

Specific to
Block ACE
Description Maximum transmit in bytes/seconds
Data Type FLOAT64
Range

- 2615 -
Chapter 20 - Rxxxx Parameters

Default 0
Config
Load No
Active
Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters

This parameter displays redundancy bytes transfer rate maximum. The maximum
of the redundancy throughput generated by the ACE in bytes/seconds. When the
Remarks STATRESET parameter is set as "ON," the maximum of the redundancy restarts.

20.150 RDRRETRYCOUNT

Specific to EHPM
Block(s)
Description The number of messages retried due to no response by the EHPM per second.
Number of requests sent that do not receive a response and is retrieved.
Data Type UINT32
Exposure NONE
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence EHPM
Related N/A
Parameters
Remarks The retry count is normally zero unless event overload occurs.

20.151 RDYFL

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Ready Flag
Data Type Boolean
Range True/False
Default False
Config Load No
Active Loadable No

- 2616 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

20.152 READERROPT

Specific to CAB types


Block(s)
Description Read Error Option. CEs assign the instance default of parameter READERROPT at
the time of creating a CAB type. READERROPT controls whether or not the block
reports an event in response to parameter read errors. If READERROPT = Event,
then an event is reported whenever READSTATUS <> OK.
Modification The Attribute Instance Default may be modified at type creation time.
of Definition

Data Type Enumeration CABERROPT


Range NoEvent, Event
Default Assigned by CE on the type definition. See Note.
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related READSTATUS,WRITESTATUS,WRITEERROPT
Parameters
Remarks Note: When a CAB type is first created, the value of NoEvent is assigned as
instance default of READERROPT. CEs can then change the instance default to
Event if desired. The value of READERROPT cannot be changed on CAB instances.

20.153 READERRORS
Delete this text and replace it with your own content.

20.154 READERRORSMAX
Delete this text and replace it with your own content.

- 2617 -
Chapter 20 - Rxxxx Parameters

20.155 READINESS

Specific to RM
Block(s)
Description Ability of the RM to assume control of the assigned function. That is, to become a
Primary.
Data Type Enumeration
Range Undefined (0) NoPartner (1) Disqualified (2) Syncing (3) Synchronized (4) Standby
(5)
Default Undefined (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

20.156 READINESSA

Specific to RM
Block(s)
Description For each module in host chassis, readiness state of module.
Data Type Enumeration [20]
Range Undefined (0) NoPartner (1) Disqualified (2) Syncing (3) Synchronized (4) Standby
(5)
Default Undefined (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

20.157 READPPS
Delete this text and replace it with your own content.

- 2618 -
Chapter 20 - Rxxxx Parameters

20.158 READPPSMAX
Delete this text and replace it with your own content.

20.159 READSPECFLAG

Specific to Block(s) ProfitCtl


Description Read Spec Flag
Data Type ENUM
Range NA
Default READ
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

20.160 READSTATUS

Specific to CAB types


Block(s)
Description Read Status. READSTATUS indicates whether an error has occurred in read
processing associated with the parameter references of a CAB program. Normally,
READSTATUS shows OK. When an error occurs, its value provides information
about the nature of the error. READSTATUS automatically reverts to OK after the
error goes away.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type Enumeration CABACCSTATUS
Range OK = 0, Bad = 10, RightsViol = 11, AccLevelViol = 12, IllegalValue = 13, RangeLimExc
= 14, IndexLimExc = 15, ConfigMis = 16, CommFail = 17
Default OK
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related READERROPT, WRITESTATUS, WRITEERROPT
Parameters
Remarks

- 2619 -
Chapter 20 - Rxxxx Parameters

20.161 READSTATUS

Specific to UDT Block


Block(s)
Description Tag Read Status — Provides status of the read request of a particular UDT.
Data Type ENUM
Range l 0 : ReadSuccessful
l 1 : StaleData
l 2 : ReadFailed
l 3 : InvalidConnection
l 4 : NoDataChange
l 5 : DataTooLarge
Default ReadFailed
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related l TAGRDGENSTATUS
Parameters
l TAGRDEXTSTATUS
Remarks If a ReadFailed shows up as the status, it indicates that the read from the PLC has
failed. The value of TAGRDGENSTATUS and TAGRDEXTSTATUS would indicate the
reason of failure. This parameter does not indicate the validity of the configuration
of UDT in the C300, that is, it does not indicate whether the configuration of the
UDT in C300 is an exact match of the UDT configuration in the ControlLogix
structure.

20.162 REASONSET

Specific to Most Function Blocks


Block(s)
Description Reason Set
Data Type 16-Bit Integer
Range 0 to 100
Default 0 = Not Required
Config Load Yes
Active No
Loadable

- 2620 -
Chapter 20 - Rxxxx Parameters

Access Lock Application Developer Only


Residence SR
Related
Parameters
Remarks You configure the reason sets through the System configuration for Operator
Security/Electonric Signatures in Station. Refer to the Server and Client
Configuration Guide for more information.

Specific to Block(s) UOC


Description Reason Set Number
Data Type INT16
Range ±32767
Default 0
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Parameters
Remarks

20.163 RECPDESC[1..50]

Specific to Block(s) SCM


Description Recipe Parameter Descriptor
Data Type String
Range Length: 23 characters
Default Null String
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters NUMRECPARMS
Remarks RECDESC[i] defines the descriptor for the ith recipe parameter.

- 2621 -
Chapter 20 - Rxxxx Parameters

20.164 RECLIMITOPT

Specific to SCM
Block(s)
Description Recipe Limit Option - Recipe target exceed limits option
Data Type Enumeration
Range 0 REJECTANDERROR
1 CLAMPANDWARN
Default REJECTANDERROR
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related RECTARGET[1..50]
Parameters
Remarks If 0 , value outside the range will be rejected If 1 , value outside the range will be
clamped and the originator of the write receives a warning

20.165 RECMATCODE[1..50]

Specific to Block(s) SCM


Description Recipe Parameter Material Code
Data Type 32-Bit Integer
Range -2147483648 to 2147483647
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer/Application Developer
Residence CEE
Related Parameters NUMRECPARMS
Remarks RECMATCODE[i] defines material code for the Ith recipe parameter.

- 2622 -
Chapter 20 - Rxxxx Parameters

20.166 RECOVMSGIDX

Specific to RM
Block(s)
Description Redundancy Module Recovery Message Index. Full recovery code, which
references a matching test string.
Data Type 16-Bit Unsigned Integer
Range 0 to 65535
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

20.167 RECSCALE[1..50]

Specific to SCM
Block(s)
Description Recipe Parameter Scale Allowed Option
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related NUMRECPARMS
Parameters
Remarks RECSCALE[i] defines the scale allowed option for the ith recipe parameter. When
On, the ith recipe parameter is indicated as scaled. The SCM does not do the
scaling.

- 2623 -
Chapter 20 - Rxxxx Parameters

20.168 RDNHISTTIME

Specific to Block(s) UOC


Description Time
Data Type TIME
Exposure NONE

Range
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

20.169 RECTARGET[1..50]

Specific to SCM
Block(s)
Description Recipe Parameter Target Value
Data Type Double precision according IEEE 754
Range N/A
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related NUMRECPARMS, HISTTYPE[1..50], DATABLOCK
Parameters
Remarks RECTARGET allows the specification of formula values for SCMs. This is the legacy
mechanism which will not be developed any further. It is not recommended to use
RECTARGET and DATABLOCK at the same time for formula parameters, since this
may lead to confusion For more information on DATA block, refer to the Sequential
Control Module User Guide.

- 2624 -
Chapter 20 - Rxxxx Parameters

20.170 RECTARGETMAX[1..50]

Specific to Block(s) SCM


Description Recipe Parameter Target Value Maximum
Data Type 64-Bit Real Number
Range N/A
Default N/A
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters NUMRECPARMS
Remarks

20.171 RECTARGETMIN[1..50]

Specific to Block(s) SCM


Description Recipe Parameter Target Value Minimum
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters NUMRECPARMS
Remarks

20.172 RECTOEQMENB

Specific to Block PHASE


(s)
Description Recipe to Equipment Enable
Data Type Boolean
Range 0 OFF RCM defines recipe to equipment state
projection.
1 ON PHASE block defines recipe to equipment state
projection.
Default OFF

- 2625 -
Chapter 20 - Rxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks If EQUIPNAME is Null, this parameter has no effect.

20.173 RECTOEQMMAP

Specific to Block(s) RCM


Description Recipe State Propagation to Equipment State
Data Type Enumeration
Range 0 None
1 Default

2 Start
3 Reset
4 Interrupt
5 Restart
6 Hold
7 Stop
8 Abort
9 Resume
Default Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters
Remarks

20.174 RECVCLOSEREQ

Specific to Block(s) FTEB


Description Receive Close Request - Identifies the close requests received.
Data Type 32-Bit Integer
Range
Default 0

- 2626 -
Chapter 20 - Rxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

20.175 RECVCLOSERSP

Specific to Block(s) FTEB


Description Receive Close Response - Identifies the close responses received.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

20.176 RECVNAKS

Specific to Block(s) FTEB


Description Received Negative Acknowledgements (NAKS) - Identifies the NAKS
received.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

- 2627 -
Chapter 20 - Rxxxx Parameters

20.177 RECVOPENREQ

Specific to Block(s) FTEB


Description Receive Open Request - Identifies open requests received.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

20.178 RECVOPENRSP

Specific to Block(s) FTEB


Description Receive Open Response - Identifies open responses received.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

- 2628 -
Chapter 20 - Rxxxx Parameters

20.179 REDDATAA

Specific to Block All PM I/O Modules and Series C I/O Modules


(s)
Description Redundancy Data Channel A - Defines the synchronization state of a physical
I/O Module device.
Data Type Enumeration
Range 0 ---
2 DumpFailed Dump failed
3 FreezeNotAccepted Freeze not accepted
4 SyncFailed Synch failed
16 IolTimeOut IOI Time out
128 Syncd Synch'd
129 DumpComplete Dump complete
130 FreezePermitted Freeze permitted
131 FreezeAccepted Freeze accepted
132 FoInProgess Failover in progress
133 FoComplete Failover complete
134 SwapInProgress Swap in progress
135 SwapComplete Swap complete
160 Frozen Frozen
161 DumpSeqBegin Dump sequence begin
162..180 DumpSeq_02..20 Dump sequence 2-20
255 DumpSeqMax Dump sequence max
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

- 2629 -
Chapter 20 - Rxxxx Parameters

20.180 REDDATAB

Specific to Block All PM I/O Modules and Series C I/O Modules


(s)
Description Redundancy Data Channel B - Defines the synchronization state of a physical
I/O Module device.
Data Type Enumeration
Range 0 ---
2 DumpFailed Dump failed
3 FreezeNotAccepted Freeze not accepted
4 SyncFailed Synch failed
16 IolTimeOut IOI Time out
128 Syncd Synch'd
129 DumpComplete Dump complete
130 FreezePermitted Freeze permitted
131 FreezeAccepted Freeze accepted
132 FoInProgess Failover in progress
133 FoComplete Failover complete
134 SwapInProgress Swap in progress
135 SwapComplete Swap complete
160 Frozen Frozen
161 DumpSeqBegin Dump sequence begin
162..180 DumpSeq_02..20 Dump sequence 2-20
255 DumpSeqMax Dump sequence max
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks This parameter does not apply to nonredundant IOM configurations.

- 2630 -
Chapter 20 - Rxxxx Parameters

20.181 REDSWITCHPERIOD

Specific to PCDI_MASTER
Block(s)
Description Redundant Connection Switch Period - Specify time in seconds before a
redundancy switchover occurs after a connection failure.
Data Type 32-Bit Unsigned Integer
Range 0 to 1800
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks A value of zero disables redundancy switchover.

20.182 REDTAG

Specific to DevCtl, All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,
VALVEDAMPER
Description Red Tag - Allows the user to set the FB as being “out-of-service“; this indicates that
the FB or the associated control strategy needs repair, or is being repaired.
Data Type Boolean
Range Off (0): Block operates normally On (1): Operator cannot make changes to the block
Default Off
Config No
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related DevCtl only: NUMDOUTS DevCtl and Drive Control only:
Parameters MODEATTR
Remarks DevCtl: Illegal if NUMDOUTS = 0. Illegal if present state is Momentary. DevCtl and
Drive Control: Illegal if MODEATTR is not Operator. Illegal if ESWENB is ENABLED.

- 2631 -
Chapter 20 - Rxxxx Parameters

Specific to DevCtl, All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. Series C I/O AOCHANNEL, DOCHANNEL
Description Red Tag - Allows the user to set the FB as being “out-of-service”; this indicates that
the FB or the associated control strategy needs repair, or is being repaired.
Data Type Boolean
Range Off (0): Block operates normally On (1): Operator cannot make changes to the block
Default Off
Config No
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related Devctl only MODEATTRNUMDOUTSSeries C I/O AOCHANNEL, DOCHANNEL
Parameters MODEMODEATTR
Remarks In DevCtl: Illegal if NUMDOUTS = 0. Illegal if MODEATTR is not Operator. Illegal if
present state is Momentary. Illegal if ESWENB is ENABLED. In Series C I/O
AOCHANNEL, DOCHANNEL This parameter allows the user to set the channel as
being out of service indicating that this channel or its associated control loops need
(s) repair(s) or are (is) being repaired. Once a channel is put in the red tag condition,
its output is frozen at the last value, blocking manual or program changes, and its
MODE and MODEATTR cannot be changed. This parameter can only be written
when MODE is Man and MODEATTR is Operator.

Specific to Series C I/O AOCHANNEL, DOCHANNEL


Block(s)
Description Red Tag
Data Type Boolean
Range 0 Off Channel is in service and
its output is not frozen.
1 On Channel is out of service
and its output is frozen.
Default Off
Config No
Load
Active No
Loadable
Access Lock Engineer
Residence IOM
Related MODE, MODEATTR
Parameters
Remarks This parameter allows the user to set the channel as being out of service indicating
that this channel or its associated control loops need(s) repair(s) or are(is) being
repaired. Once a channel is put in the red tag condition, its output is frozen at the
last value, blocking manual or program changes, and its MODE and MODEATTR
cannot be changed. This parameter can only be written when MODE is Man and
MODEATTR is Operator. Illegal if ESWENB is ENABLED.

- 2632 -
Chapter 20 - Rxxxx Parameters

20.183 REDUNDANCY_WARNING

Specific to C300
Block(s)
Description Redundancy Warning Text. Entity is used to display the warning text mentioned in
default value on the form next to MODISREDUN parameter.
Data Type String
Range Length: 31 Characters
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related MODISREDUN
Parameters
Remarks Note: Checking/unchecking MODISREDUN will create/delete a secondary C300
automatically.

20.184 REDUNDANT

Specific to Block(s) Server


Description Redundancy - Indicates whether the server is redundant.
Data Type Boolean
Range (0) Non-redundant
(1) Redundant
Default (0) Non-redundant
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence SCAN
Related Parameters
Remarks

- 2633 -
Chapter 20 - Rxxxx Parameters

20.185 REDUNSTATE

Specific to RM
Block(s)
Description Redundancy State of the RM and the Chassis.
Data Type Enumeration
Range Undefined (0) Primary (1) Secondary (2)
Default Undefined (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence Not Loaded
Related
Parameters
Remarks Requests to read or store to any RM parameter must come from the Supervisory
platform (through Control Builder or Server).

20.186 REDUNSTATEA

Specific to RM
Block(s)
Description For each module in host chassis, redundancy state of module
Data Type Enumeration [20]
Range Undefined (0) Primary (1) Secondary (2)
Default Undefined (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

- 2634 -
Chapter 20 - Rxxxx Parameters

20.187 REEXECOPT

Specific to SCM, RCM


Block(s)
Description Re-execution Option - Provides a Phase specific Re-execution selection. A value of
FollowContainer means that the Phase will follow its container's REEXECOPT.
Data Type Enumeration
Range ReExecute (0); Continue (1)
Default ReExecute
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related REEXECPOLICY, REEXECOPTOG REEXECOPTOH, REEXECOPTOS
Parameters
Remarks On re-execution of a Step, the behavior is either:
l ReExecute - Step is executed “from the top” all Outputs will be executed.
l Continue - Step is continued “from where it left off”; only incomplete Outputs
are executed.

Specific to Step
Block(s)
Description Re-execution Option - Provides a Step specific Re-execution selection. A value of
FollowContainer means that the Step will follow its container's (SCM or RCM that
contains the Step) REEXECOPT.
Data Type Enumeration
Range ReExecute (0); Continue (1); FollowContainer (2)
Default FollowContainer
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related REEXECPOLICY, REEXECOPTOG REEXECOPTOH, REEXECOPTOS Also, see table
Parameters above specific to SCM/RCM REEXECOPT.
Remarks On re-execution of a Step, the behavior is either:
l ReExecute - Step is executed “from the top”; all Outputs will be executed
l Continue - Step is continued “from where it left off”; only incomplete Outputs
are executed.

- 2635 -
Chapter 20 - Rxxxx Parameters

Specific to PHASE
Block(s)
Description Re-execution Option - Provides a Phase specific Re-execution selection. A value of
FollowContainer means that the Phase will follow its container's REEXECOPT.
Data Type Enumeration
Range 0 ReExecute Phase is executed “from the
top”, it will follow its normal
procedure
1 Continue Phase is able to takeover
running equipment.
2 FollowContainer Phase follows its container's
REEXECOPT.
Default FollowContainer
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related REEXECPOLICY, REEXECOPTOG REEXECOPTOH, REEXECOPTOS Also, see table
Parameters above specific to SCM/RCM REEXECOPT.

20.188 REEXECOPTOG

Specific to Step
Block(s)
Description Goto Re-execution Option Override - Provides a one-shot/one time override of the
Step REEXECOPT for the manual Goto Step SCM/RCM execution scenario that is
supported in SingleStep mode.
Data Type Enumeration
Range ReExecute (0); Continue (1)
Default ReExecute
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related REEXECPOLICY, REEXECOPTOH REEXECOPTOS, REEXECOPT
Parameters
Remarks Read of REEXECOPTOG shows what will happen in the next Goto Step scenario,
based on the Step's current REEXECOPT. This parameter is utilized in the
SCM/RCM Table view Goto dialog, so direct user interaction with REEXECOPTOG is
normally not required.

- 2636 -
Chapter 20 - Rxxxx Parameters

Specific to PHASE
Block(s)
Description Goto Re-execution Option Override - Provides a one-shot/one time override of the
Phase REEXECOPT for the manual Goto Phase RCM execution scenario that is
supported in Single Step mode.
Data Type Enumeration
Range 0 ReExecute Phase is executed “from
the top”, it will follow its
normal procedure
1 Continue Phase is able to takeover
running equipment.
Default ReExecute
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related REEXECPOLICY, REEXECOPTOH, REEXECOPTOS REEXECOPT
Parameters
Remarks Read of REEXECOPTOG shows what will happen in the next Goto Phase scenario,
based on the Phase's current REEXECOPT. This parameter is used in the RCM
Table View Goto dialog, so direct user interaction with REEXECOPTOG is normally
not required.

20.189 REEXECOPTOH

Specific to Step
Block(s)
Description Handler Return Re-execution Option Override - Provides a one-shot/one time
override of the Step REEXECOPT for the return from Handler to Main Handler
SCM/RCM execution scenario.
Data Type Enumeration
Range ReExecute (0); Continue (1)
Default ReExecute
Config No
Load
Active No
Loadable

- 2637 -
Chapter 20 - Rxxxx Parameters

Access Lock Operator


Residence CEE
Related REEXECPOLICY, REEXECOPT, REEXECOPTOG, REEXECOPTOS
Parameters
Remarks Read of REEXECOPTOH shows what will happen in the next return from Handler to
Main handler scenario, based on the Step's current REEXECOPT. This parameter
can be set as required, normally by the SCM/RCM itself, prior to the return to the
Step in the Main handler. Returns to the Main handler and a State of Running are
from the States of either Held (no Restart handler), Restarting (Restart handler
finishing), or Interrupting (Interrupt handle finishing).

Specific to PHASE
Block(s)
Description Handler Return Re-execution Option Override - Provides a one-shot/one time
override of the Phase REEXECOPT for the return from Handler to Main Handler
RCM execution scenario.
Data Type Enumeration
Range 0 ReExecute Phase is executed “from
the top”, it will follow its
normal procedure
1 Continue Phase is able to takeover
running equipment.
Default ReExecute
Config No
Load
Active No
Loadable
Access Operator
Lock
Residence CEE
Related REEXECPOLICY, REEXECOPT, REEXECOPTOG, REEXECOPTOS
Parameters
Remarks Only available in Experion R311 or later. Read of REEXECOPTOH shows what will
happen in the next return from Handler to Main handler scenario, based on the
Phase's current REEXECOPT. This parameter can be set as required, normally by
the RCM itself, prior to the return to the Phase in the Main handler. Returns to the
Main handler and a State of Running are from the States of either Held (no Restart
handler), Restarting (Restart handler finishing), or Interrupting (Interrupt handle
finishing).

- 2638 -
Chapter 20 - Rxxxx Parameters

20.190 REEXECOPTOS

Specific to Step
Block(s)
Description Standard Sequence Re-execution Option Override - Provides a one-shot/one time
override of the Step REEXECOPT for the standard sequence flow SCM/RCM
execution scenario.
Data Type Enumeration
Range ReExecute (0); Continue (1)
Default ReExecute
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related REEXECPOLICY, REEXECOPT, REEXECOPTOG, REEXECOPTOH
Parameters
Remarks Read of REEXECOPTOS shows what will happen in the next standard sequence
flow scenario, based on the Step's current REEXECOPT. This parameter can be set
as required, normally by the SCM/RCM itself, prior to the re-execution of a Step.
Looping back to a Step within a Handler is the most common example of a
“standard sequence flow” execution scenario.

Specific to PHASE
Block(s)
Description Standard Sequence Re-execution Option Override - Provides a one-shot/one time
override of the Phase REEXECOPT for the standard sequence flow RCM execution
scenario.
Data Type Enumeration
Range 0 ReExecute Phase is executed “from
the top”, it will follow its
normal procedure
1 Continue Phase is able to takeover
running equipment.
Default ReExecute (0)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related REEXECPOLICY, REEXECOPT, REEXECOPTOG, REEXECOPTOH
Parameters
Remarks Read of REEXECOPTOS shows what will happen in the next standard sequence
flow scenario, based on the Phase's current REEXECOPT. This parameter can be
set as required, normally by the RCM itself, prior to the re-execution of a Phase.
Looping back to a Phase within a Handler is the most common example of a
“standard sequence flow” execution scenario.

- 2639 -
Chapter 20 - Rxxxx Parameters

20.191 REEXECPOLICY

Specific to SCM, RCM


Block(s)
Description Step Re-execution Policy - Provides selection of scheme to be used for the re-
execution of Steps.
Data Type Enumeration
Range AlwaysReExecute (0); Flexible (1)
Default AlwaysReExecute
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence CEE
Related RETAINISTS, REEXECOPT, REEXECOPTOG, REEXECOPTOH, REEXECOPTOS
Parameters
Remarks A value of AlwaysReExecute means that Step re-executions will always re-execute
all Outputs. One exception case is the return from Handler to a Step in the Main
handler scenario when RETAINISTS is On, which will cause confirmable
Instructions to not be re-executed. A value of Flexible enables the use of the
configured and one-shot re-execution options (see REEXECOPT, REEXECOPTOG,
REEXECOPTOH, REEXECOPTOS), which allow a Step to be re-executed or
continued.

20.192 REFCOUNT

Specific to Block(s) FTEB and C300 FBs


Description Reference Count
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300
Related Parameters
Remarks Internal Parameter used by FTEB module for debugging

- 2640 -
Chapter 20 - Rxxxx Parameters

20.193 REFRESHMS

Specific to RM
Block(s)
Description Refresh Interval in milliseconds.
Data Type 32-Bit Unsigned Integer
Range 0 to 4294967295
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly Requests to read or store to any RM parameter must come from the
Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

20.194 REJFACTOR

Specific to EXECTIMER
Block(s)
Description interrupt REJect FACTOR
Data Type FLOAT64
Range
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related DTIME, DTIMEMAX, DTIMEMIN, MAXMINRATIO
Parameters
Remarks When REJFACTOR is non-NaN, new values of DTIME are rejected from the
statistical computations unless the following criterion is met. DTIME <= REJFACTOR
* DTIMEMIN If the application engineer chooses to use REJFACTOR, the value of
MAXMINRATIO can be used to judge an appropriate value.

- 2641 -
Chapter 20 - Rxxxx Parameters

20.195 REF

Specific to AIREF, AOREF, DIREF, and DOREF


Block(s)
Description Reference
Data Type INOUTCONN
Range Not Applicable
Default Not Applicable
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence ERDBONLY
Related CHANTYPEREFTYPE
Parameters
Remarks This parameter is used for specifying the actual reference. Based on the REFTYPE
configuration, the reference can be a channel or a parameter.

NOTE
l The REF parameter value for an input-type Reference block must
be an output-type parameter when the REFTYPE is set as
"PARAMETER."
l The REF parameter value for an output-type Reference block must
be an input-type parameter when the REFTYPE is set as
"PARAMETER."

For more information about configuring the REF parameter, see Control Builder
Components Theory.

20.196 REFTYPE

Specific to AIREF, AOREF, DIREF, and DOREF blocks


Block(s)
Description Reference Type
Data Type Enumeration
Range NONE
SERIES_C_IO
PMIO
PARAMETER
Default SERIES_C_IO
Config No
Load
Active No
Loadable

- 2642 -
Chapter 20 - Rxxxx Parameters

Access Lock AppDevOnly


Residence SR
Related CHANTYPEREF
Parameters
Remarks This parameter is used for configuring the type of interface. If the REFTYPE is
configured as "SERIES_C_IO" or "PM I/O," then the type of interface is between the
CM and IOMs. If the REFTYPE is configured as "PARAMETER," then type of interface
is between two different blocks in Control Builder. By default, this parameter is set
to "SERIES_C_IO." For more information about the REFTYPE parameter, see Control
Builder Components Theory.

20.197 REGCALC

Specific to HRBALG_REG block


Blocks
Description REGCALC FB Reference
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the REGCALC block in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

20.198 REGCTLOFFMODE

Specific to Block(s) PROFCONOUT


Description RegCtl MODE value when Controller is OFF/SHED
Data Type ENUM
Range NA
Default AUTO
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters REGCTLOFFMODEATTR
Remarks RegCtl MODE value when Controller is OFF/SHED

- 2643 -
Chapter 20 - Rxxxx Parameters

20.199 REGCTLOFFMODEATTR

Specific to Block(s) PROFCONOUT


Description RegCtl MODEATTR value when Controller is OFF/SHED
Data Type ENUM
Range NA
Default OPERATOR
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters REGCTLOFFMODE
Remarks RegCtl MODEATTR value when Controller is OFF/SHED

20.200 REGCTLONMODE

Specific to Block(s) PROFCONOUT


Description RegCtl MODE value when Controller is ON
Data Type ENUM
Range NA
Default AUTO
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters REGCTLONMODEATTR
Remarks RegCtl MODE value when Controller is ON

20.201 REGCTLONMODEATTR

Specific to Block(s) PROFCONOUT


Description RegCtl MODEATTR value when Controller is ON
Data Type ENUM
Range NA
Default PROGRAM
Config Load No
Active Loadable No

- 2644 -
Chapter 20 - Rxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related Parameters REGCTLONMODE
Remarks RegCtl MODEATTR value when Controller is ON

20.202 RegCtlStrategy

Specific to Block(s) PROFCONOUT


Description RegCtl Strategy Parameter
Data Type ENUM
Range NA
Default SP_Ctrl-PAuto_Shed-OAuto
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters REGCTLTARGETPARAM
Remarks Defines mode, modeattr and target parameter of regctl while working with
PC

20.203 REGCTLTARGETPARAM

Specific to Block(s) PROFCONOUT


Description RegCtl Target Parameter to Send MV Value to
Data Type ENUM
Range NA
Default SP
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters REGCTLSTRATEGY
Remarks RegCtl Target Parameter to Send MV Value to

- 2645 -
Chapter 20 - Rxxxx Parameters

20.204 REGHASENAME

Specific to CB and EC
Blocks
Description Regulatory HASE Name
Data Type BLOCKID
Range
Default
Config. No
Load
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter displays the algorithm HRB name along with the HASE name
configured for the slot represented by the index. The format is
HASENAME.ALGOHRBNAME.

20.205 REGREGISTERED

Specific to CB and EC
Blocks
Description Regulatory point registered
Data Type BOOLEAN
Range TRUE or FALSE
Default FALSE
Config. Load No
Access Lock ViewOnly
Residence NOLOAD
Related
Parameters
Remarks This parameter is selected if the regulatory algorithm HRB configured in the slot
is registered with the Box HRB.

20.206 REGTARGETBLK

Specific to Block(s) PROFCONOUT


Description RegCtl block
Data Type ENUM
Range NA
Default PID

- 2646 -
Chapter 20 - Rxxxx Parameters

Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters REGCTLTARGETPARAM
Remarks Regctl target block to connect this MV to

20.207 REGTARGETOPTMASK

Specific to Block(s) PROFCONOUT


Description RegCtl Target block Enumeration Mask
Data Type STRING
Range NA
Default 0x69
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters REGTARGETBLK
Remarks RegCtl Target block Enumeration Mask

20.208 RELAYPRESENT

Specific to Block(s) Series C DO Modules


Description Relay Board Present
Data Type Boolean
Range 0 OFF Relay board absent.
1 ON Relay board present.
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks When asserted, indicates the DO IOM is connected to Relay Board.

- 2647 -
Chapter 20 - Rxxxx Parameters

20.209 RELOADINIDLY

Specific to Control Module in CEE. Not supported in FIM or LIOM.


Block(s)
Description Reload Initialization Delay - Specifies an execution count during which the CM
holds off read requests directed to component blocks following reload.
Data Type INT32
Range 0 to 100 CM executions
Default 2
Config Yes
Load
Active No
Loadable
Access Application Developer Only
Lock
Residence CEE
Related CURRELINIDLYINITPENDING RSTRTINIDLY
Parameters
Remarks RELOADINIDLY specifies a delay interval, in units of CM execution counts, during
which a CM prevents blocks and supervisory applications from reading its data.
While the delay counts down, the CM executes its component blocks to bring their
data state into alignment with the process. RELOADINIDLY comes into play
following the load of a CM which is already resident in the CEE, also known as a
“reload”. Whenever a CM with nonzero RELOADINIDLY is reloaded, it hides its data
until it has executed RELOADINIDLY times. If the reloaded CM is not activated
immediately after reload, then it hides its data until it is activated. RELOADINIDLY
needs to be large enough for all component blocks to have executed at least once
using fresh data. For most CMs, a value RELOADINIDLY of 1 is sufficient.
Depending on block ordering and on how delays are used within the configuration,
some CMs may require more than one execution to insure that all component
blocks have executed with fresh input values. Also, in cases where the CM depends
on external data which may be slow to become fresh after reload, the CM may
require more than one execution for initialization following reload.

20.210 RELEASEOPT

Specific to Phase
Block(s)
Description Release Resource after Execution
Data Type Boolean
Range OFF (0) no resource release will be initiated by this phase block ON (1) Resource
specified by EQUIPNAME will be released immediately after phase is finished.
Default ON (1)
Config Load Yes
Active No
Loadable

- 2648 -
Chapter 20 - Rxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related EQUIPNAME or EQUIPNAMEREF , TERMSTATEOPT, RLSRESABNORM,
Parameters RLSRESNORM
Remarks will be ignored (assumed to be OFF) if EQUIPNAME and EQUIPNAMEREF is NULL if
ACQUIREOPT=ON and RELEASEOPT=OFF the resource will be kept by the recipe
and needs to be released by another phase in the same recipe.

20.211 REMCAS

Specific to HRBALG_REG block


Blocks
Description REMCAS FB Reference
Data Type BLOCKID
Range Not applicable
Default Null
Config. Load Yes
Active
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter contains a reference to the REMCAS block in the emulation CM
which holds the HRBALG_REG instance.

20.212 REMCASTYPE

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Remote Cascade Type - Defines the type of remote cascade intended between the
regulatory control block in the ACE supervisory controller and Universal Control
Network (UCN) Process Manager control point.
Data Type Enumeration
Range (0) None (1) Spc (2) Ddc (3) Rsp (4) DdcRsp
Default (0) None
Config Load Yes
Active No
Loadable

- 2649 -
Chapter 20 - Rxxxx Parameters

Access Lock Application Developer


Residence ACE
Related
Parameters
Remarks

20.213 REMOTESWITCH

Specific to Block(s) All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER

Description Switch in Remote Position


Data Type Boolean
Range OFF ON
Default ON
Config Load NO
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters LOCALSWITCH
Remarks All commands other than ‘local’ allowed only when RemoteSwitch is ON

20.214 REMSOAKTIME

Specific to Block(s) RampSoak


Description Remaining Soak Time for the current SOAK segment.
Data Type Real
Range 0.0 - 7200.0
Default 0.0
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters SOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK]
Remarks

- 2650 -
Chapter 20 - Rxxxx Parameters

20.215 REQ.ACQSTATE[1..100]

Specific to Block(s) SCM, RCM


Description Acquisition State
Data Type Enumeration
Range 0 NONE
1 ACQUIRING
2 ACQUIRED
3 RELEASING
4 ERROR
5 WARNING
Default NONE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.216 REQ.CMDREQ.OUT[1..100]

Specific to Block(s) SCM, RCM


Description Resource Command Structure
Data Type STRUCT
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2651 -
Chapter 20 - Rxxxx Parameters

20.217 REQ.CMDREQSTS[1..100]

Specific to Block(s) SCM, RCM


Description Request Command Store Status
Data Type 32-Bit Integer
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.218 REQ.EQUIPNAME[1..100]

Specific to Block(s) SCM, RCM


Description Name of Resource to be Acquired
Data Type BlockID
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.219 REQ.OUTDEST[1..100]

Specific to Block(s) SCM, RCM


Description Output Destination Connection
Data Type OUTCONN
Range
Default
Config Load No
Active Loadable No

- 2652 -
Chapter 20 - Rxxxx Parameters

Access Lock Application Developer Only


Residence
Related Parameters
Remarks

20.220 REQ.OWNERSSRC[1..100]

Specific to Block(s) SCM, RCM


Description Input Source Connection
Data Type INCONN
Range
Default
Config Load No
Active Loadable No
Access Lock Application Developer Only
Residence
Related Parameters
Remarks

20.221 REQ.OWNERSSTS[1..100]

Specific to Block(s) SCM, RCM


Description Resource Owners Get Status
Data Type 32-Bit Integer
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2653 -
Chapter 20 - Rxxxx Parameters

20.222 REQ.OWNFL[1..100]

Specific to Block(s) SCM, RCM


Description Ownership Flag
Data Type Boolean
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.223 REQ.REQFL[1..100]

Specific to Block(s) SCM, RCM


Description Request Resource Input
Data Type Boolean
Range
Default
Config Load No
Active Loadable No
Access Lock Operator
Residence
Related Parameters
Remarks

20.224 REQ.RELFL[1..100]

Specific to Block(s) SCM, RCM


Description Release Resource Input
Data Type Boolean
Range
Default
Config Load No
Active Loadable No

- 2654 -
Chapter 20 - Rxxxx Parameters

Access Lock Operator


Residence
Related Parameters
Remarks

20.225 REQEXECID[1..15]

Specific to Block(s) SCM, RCM, UCM, CM


Description Execution ID of Requesting Block
Data Type 64-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks ArraySize = Owner-ArraySize + Queue-ArraySize

20.226 REQORDER

Specific to Block(s) SCM, RCM, UCM, CM


Description Resource request order
Data Type 32-Bit Integer
Range
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks Reserved for future use. Do not use in control strategies.

- 2655 -
Chapter 20 - Rxxxx Parameters

20.227 REQRSPRCVD

Specific to Block(s) PCDI_MASTER


Description Request Responses Received
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

20.228 REQRTRY

Specific to PCDI_MASTER
Block(s)
Description Request Retries - Specifies the maximum number of retry counts the peer device
will attempt after a failed read or write.
Data Type 32-Bit Unsigned Integer
Range 0 to 10
Default 1
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related
Parameters
Remarks This parameter value is used for all serial devices, unless overridden by a serial
device. An alarm is generated, if a request attempt exceeds the request retry count.
A value of zero automatically reports a timeout with no retries.

20.229 REQRTRYCNT[0..15]

Specific to Block(s) PCDI_MASTER


Description Request Retries Count
Data Type 32-Bit Unsigned Integer
Range

- 2656 -
Chapter 20 - Rxxxx Parameters

Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

20.230 REQSTATE

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Current Request State
Data Type Enumeration
Range 0 Idle
1 Req Alloc
2 Adding
3 Add Fail
4 Ready
5 Sending
6 Sent
7 Freeing
8 Complete
9 Failed
10 Cancel
Default Idle
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2657 -
Chapter 20 - Rxxxx Parameters

20.231 REQUSTEDSCANTIME

Specific to Block(s) TCMI


Description Requested Scan Time
Data Type FLOAT64
Range N/A
Default 0.0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

20.232 RESADDR[1..15]

Specific to SCM, RCM


Block(s)
Description Restart Address Name
Data Type BlockId
Range N/A
Default Null String
Config No
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related RESADDRFUTUR[1..15], RESADDRN[1..15], UPDRESOPT.
Parameters
Remarks RESADDR[i] contains the name (for example, SCMName.StepName) of the Step in
thread i that will become the active step on return to the Main or Interrupt handlers
from an exception. It can only be set to a valid step name in the Main or Interrupt
handler that was preempted. RESADDR[1..15] is a BlockId parameter and not
supported in expressions. Its Integer-32 Partner Parameter RESADDRN[1..15] can
be used in Transition Condition expressions and Step Output expressions.

- 2658 -
Chapter 20 - Rxxxx Parameters

20.233 RESAVEPERIOD

Specific to RETENTIONTRIG
Block(s)
Description Re-Save Period
Data Type FLOAT64
Range NaN, >= 5
Default 10.0
Config Load Yes
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related TIMETORESAVE
Parameters
Remarks Count down time before repeating save of retention data after loss of external power.
If RESAVEPERIOD is NaN, the save is never repeated. If RESAVEPERIOD is not NaN,
RESAVEPERIOD defines the period of time, in minutes, for repeating the save
operation.

20.234 RESADDRFUTUR[1..15]

Specific to SCM, RCM


Block(s)
Description Restart Address Future Name
Data Type BlockId
Range N/A
Default Null String
Config No
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related RESADDRFUTUR[1..15], RESADDRN[1..15], UPDRESOPT.
Parameters
Remarks RESADDRFUTUR[i] contains the name (for example, CMName.StepName) of the
step in thread i that RESADDR [i] will be set to if the currently active Main or
Interrupt hander is preempted. It can only be set to a valid step name in the
currently active Main or Interrupt handler. If a step's UPDRESOPT is On, the step
will update RESADDRFUTUR to its own name, for its thread. RESADDRFUTUR[1..15]
is a BlockId parameter and not supported in expressions. Its Integer-32 Partner
Parameter RESADDRFUTRN[1..15] can be used in Transition Condition expressions
and Step Output expressions.

- 2659 -
Chapter 20 - Rxxxx Parameters

20.235 RESADDRFUTRN[1..15]

Specific to SCM, RCM


Block(s)
Description Restart Address Future Number
Data Type 32-Bit Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related RESADDRN[1..10], UPDRESOPT.
Parameters
Remarks RESADDRFUTUR[i] contains the name (for example, SCMName.StepName) of the
step in thread i that RESADDR [i] will be set to if the currently active Main or
Interrupt hander is preempted. It can only be set to a valid step name in the
currently active Main or Interrupt handler. If a step's UPDRESOPT is On, the step
will update RESADDRFUTUR to its own name, for its thread. RESADDRFUTRN[1..15]
may be used in Transition Condition expressions and Step Output expressions,
whereas RESADDRFUTUR[1..15] (a BlockId parameter) is not supported in
expressions.

20.236 RESADDRN[1..15]

Specific to SCM, RCM


Block(s)
Description Restart Address Number
Data Type 32-Bit Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable

- 2660 -
Chapter 20 - Rxxxx Parameters

Access Lock Engineer


Residence CEE
Related RESADDRFUTUR[1..10], RESADDRN[1..10], UPDRESOPT.
Parameters
Remarks RESADDR[i] contains the name (for example, SCMName.StepName) of the Step in
thread i that will become the active step on return to the Main or Interrupt handlers
from an exception. It can only be set to a valid step name in the Main or Interrupt
handler that was preempted. RESADDRN[1..15] may be used in Transition
Condition expressions and Step Output expressions, whereas RESADDR[1..15] (a
BlockId parameter) is not supported in expressions.

20.237 RESET

CAUTION
When reinitialized, the function block loses all knowledge of past process behavior.
Reinitialize only if process biases no longer reflect deviation from the true property (for
instance, after fixing a failed analyzer).

Specific to PID-PL
Block(s)
Description Reinitialize Function Block - Reinitializes function block database. Selecting this
switch is equivalent to inactivating and reactivating the control module.
Data Type Boolean
Range Off(0): Do not reinitialize function block.
On(1): Reinitialize function block to current
operation conditions.
Default Off
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks Important! Do not confuse this parameter with RESETMODEL. This parameter is
applicable only when CTLEQN is set to Profit Loop PKS, and is ignored in PID
control equations.

Specific to Block(s) ANNPANEL


Description OFF to ON transition resets the alarm if the alarm is returned to normal
Data Type Boolean
Range ON/OFF
Default OFF

- 2661 -
Chapter 20 - Rxxxx Parameters

Config Load NO
Active Loadable No
Access Lock Operator
Residence CEE
Related FLSHSTAT
Parameters
Remarks When this ON, it resets the FLSHSTAT to LAMPOFF when FLSHSTAT is slow
flash.

Specific to Block FIRSTOUT


(s)
Description First Up Flag Reset
Data Type Boolean
Range OFF, ON
Default OFF
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related
Parameters
Remarks This resets the INPUTACTED[*](OFF), FIRSTUPACTED(OFF) INPUTACTED
(NONE) parameters.

Specific to EXECTIMER
Block(s)
Description Trigger parameter for resetting the statistical computations within an EXECTIMER
instance.
Data Type BOOLEAN
Range
Default Off
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related DTIMEAVG, DTIMEAVGCOMP, DTIMEMAX, DTIMEMIN, DTIMESTD, DTIMESTDPRC,
Parameters MAXMINRATIO
Remarks When read, RESET always returns a value of Off. When written to On, the
EXECTIMER instance restarts all statistical computations from the present moment.
Setting RESET at one instance of EXECTIMER has no effect on other instances of
EXECTIMER. Parameter RESET is unrelated to the STATSRESET parameter of the
CEE function block or any of the device function blocks.

- 2662 -
Chapter 20 - Rxxxx Parameters

20.238 RESETDEVDROPOFF

Specific to Block(s) FIM, FIM4


Description Resets device drop off counters for all devices across all links.
Data Type Boolean
Range N/A
Default False
Config Load No
Active Loadable No
Access Lock Engineer
Residence Controller
Related Parameters DEVDROPOFFCOUNT on Fieldbus Devices
Remarks Clears all device drop off counters on a per FIM/FIM4 basis.

20.239 RESETEIMNAME

Specific to Block(s) C300


Description Reset EIM Associations
Data Type BOOLEAN

Range On, Off

Default Off

Config Load
Active Loadable
Access Lock AppDevOnly

Residence ERDB

Related Parameters EIPSUPPPORTED


Remarks

20.240 RESETERRORSCMD

Specific to All PM I/O Modules


Block(s)
Description Reset I/O Link Errors. Resets the I/O Processor's error counts.
Data Type Boolean
Range 0 On Reset Errors command has
been initiated.
1 Off No command.
Default Off (1)
Config Load No
Active No

- 2663 -
Chapter 20 - Rxxxx Parameters

Loadable
Access Lock Engineer
Residence IOLIM
Related
Parameters
Remarks Used to reset the IOM's error counts. Unlike the Link FB's COMMAND parameter
that affects the entire I/O Link, the scope of this command is limited to the
redundant IOM pair (or single IOM, if non-redundant).

20.241 RESETFIRSTUP

Specific to HTMOTOR
Block(s)
Description Reset Firstup
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active No
Loadable
Access Lock ENGINEER
Residence CEE
Related AUTOSTOP OPCMD[0..2] UCPSTOPACTED UCPSTOP
Parameters AUTOSTOPACTED ERRCODE SIACTED SEQSTO
LOCALSTOPLOCALSTOPACTEDOI SEQSTOPACTED
[0..2]OIACTEDOP
Remarks Resets all the Acted flags.

20.242 RESETFL

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Reset Totalizer Command Flag - When this flag changes from Off to On, the
Totalizer function block resets the PV to equal the value of the RESETVAL variable.
Data Type Boolean
Range Off (0): Do not reset the accumulator. On (1): Reset the accumulator.
Default Off (0)
Config Load No
Active No
Loadable

- 2664 -
Chapter 20 - Rxxxx Parameters

Access Lock Other Function Block


Residence CEE
Related RESETVAL, STALECOUNT, STARTFL, STOPFL.
Parameters
Remarks The Totalizer block must be reset using the reset pin prior to counting. When read,
the flag will always return to OFF.

Specific to Timer
Block(s)
Description Reset Command Flag - Provides ability to issue Reset command to the Timer
function block using Boolean parameter.
Data Type Boolean
Range Off (0): Do not reset the accumulator. On (1): Reset the accumulator.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related COMMAND, RESTARTFL, STALECOUNT, STARTFL, STOPFL.
Parameters
Remarks An Off-to-On transition of RESETFL causes the timer to be reset. When read, the
flag will always return to OFF.

Specific to Pulse Input IOC, Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Reset Counter Flag - storing On to this parameter will cause the pulse count to
reset to 0; reading this parameter always returns a value of Off.
Data Type Boolean
Range Off (0): Do not reset the accumulator. On (1): Reset the accumulator.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related SO
Parameters
Remarks

Specific to Series C PICHANNEL, UIO - Series C DICHANNEL


Block(s)
Description Reset Counter Flag
Data Type BOOLEAN
Range OFF(0) ON(1)
Default OFF

- 2665 -
Chapter 20 - Rxxxx Parameters

Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOM
Related AVAVRAW
Parameters
Remarks RESETFL indicates whether the pulse count of the associated channel in the pulse
input device is to be reset (storing ON resets the accumulated value in the device).
The default value is OFF. RESETFL is edge-triggered; reading it always returns a
value of OFF.

Specific to DEVCTL All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,


Block(s) VALVEDAMPER
Description Maintenance Statistics Reset Flag - When set from Off to On, resets all
Maintenance Statistics to their default or 0 values.
Data Type Boolean
Range Off (0): Do not reset the accumulator. On (1): Reset the accumulator.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Operator, Other Function Block (see remarks)
Residence CEE
Related DEVCTL: MAINTOPT, MAXTIME[0..2], MAXTRANS All Drive Control: NUMSIOVRD,
Parameters [0..2], NUMSIOVRD, NUMTRANS, REDTAG, NUMTRANS, REDTAG,
STATETIME[0..2]..
Remarks DEVCTL: Illegal if MAINTOPT is not set On. Operator may reset only when REDTAG
is set on. When read, the flag will always return to OFF.

Specific to Up / Down Counter Block


Block(s)
Description Reset Flag
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Load No
Active No
Loadable
Access Lock Other Function Block

- 2666 -
Chapter 20 - Rxxxx Parameters

Residence CEE
Related LOADFL, PAUSEFL
Parameters
Remarks This parameter is sensed as a level input, which is self-clear on a block execution. If
the parameter is set to “TRUE”, it resets the internal counter value to zero.
The reset operation has precedence over a load operation. If the reset and load
operation inputs are sensed as “TRUE” during the block execution time, the
internal counter value will be set to zero.

20.243 RESETFL[0..7]

Specific to Pulse Input IOM


Block(s)
Description Reset Counter Flag - Storing On to this parameter will cause the pulse count
associated with the Pulse Input Channel to reset to 0. RESETFL is edge-triggered,
so reading this parameter always returns a value of Off.
Data Type Boolean
Range Off (0): Normal value On (1): Storing On will reset accumulated value in device.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SO[6..7]
Parameters
Remarks

20.244 RESETHCOMERR

Specific to HAICHANNEL and HAOCHANNEL (PM I/O)


Block
Description Reset Errors and Failures - Clears and resets HART communication diagnostic
parameters to their default values. See Remarks.
Data Type Boolean Push button
Range
Default 0
Config Load No
Active No
Loadable

- 2667 -
Chapter 20 - Rxxxx Parameters

Access Lock Engineer


Residence
Related HCOMERFLHNCOMERRHCOMSTSHCOMFAILHCMDFAILHCMDRESP
Parameters
Remarks When RESETHCOMERR is pressed:
l HCOMERFL is cleared.
l HNCOMERR is set to zero.
l HCOMSTS is set to its default value.
l HCOMFAIL is set to its default value.
l HCMDFAIL is set to its default value.
l HCMDRESP is set to its default value.
l Any pending notifications relating to HNCOMERR, HCOMSTS and HCMDFAIL
are returned to normal.

20.245 RESETMODE[0..numChans-1]

Specific to Block(s) l 1738-OB2EPM12


l 1738-OB8EM12
Description Reset Mode
Data Type Boolean
Range l 0 : OFF
l 1: ON
Default OFF
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

20.246 RESETMODEL

Specific to PID-PL
Block(s)
Description Reset Model - Reset the model buffer to active model in the function block.
Data Type Boolean
Range
Default
Config Yes
Load

- 2668 -
Chapter 20 - Rxxxx Parameters

Active No
Loadable
Access Engineer
Lock
Residence CEE
Related UPDATEMODEL
Parameters
Remarks To prevent undesired bumps in the controller due to partial model updating, the
user-entered model is stored in a buffer until complete model is entered.
UPDATEMODEL indicates that the model stored in buffer should be transferred to
the active controller; whereas, RESETMODEL resets the buffer with model stored in
active controller. Important! Do not confuse this parameter with RESET. Setting this
parameter, regardless of its value, forces a reset of the model buffer. Ordinarily, this
flag is set on to initiate the reset and is switched off, by the function block, during
the reset. This parameter is applicable only when CTLEQN is set to Profit Loop PKS,
and is ignored in PID control equations.

20.247 RESETSTAT

Specific to Block Series C AICHANNEL


(s)

Description Reset Statistics

Data Type BOOLEAN Push button

Exposure INANDOUT

Range N/A

Default 0

Config Load No

View Only

Residence IOM

Related SCACOMSTS, SCALASTCOMCODE, SCAREQCODE, SCARESPCODE,


Parameters SCACOMCOUNT

Remarks When RESETSTAT is pressed by the user, all the SCA related parameters are set to
default values.

This parameter is only applicable when the channel has the following attributes:
·        The module type is UIO-2 and
·        The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

- 2669 -
Chapter 20 - Rxxxx Parameters

20.248 RESETTIMER

Specific to RampSoak
Block(s)
Description Reset Segment Timer On Profile - used to control the timers on restarting a profile.
Data Type Boolean
Range Off (0) On (1)
Default On (1)
Config No
Load
Active No
Loadable
Access Lock Engineer
Residence
Related
Parameters
Remarks When the profile starts If RESETTIMER = Off, all timers resume with their previous
values If RESETTIMER = On, the event timer NETTIMEPASTTHISSEG and
REMSOAKTIME are reset TIMEPASTTHISSEG does not reset as this parameter is
used to compute the values of statistics parameters.

20.249 RESETVAL

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Accumulator Reset Value - Value that the Totalizer function block uses to reset the
accumulator. When RESET is applied, the Process Variable (PV) is set to RESETVAL.
Data Type 64-Bit Real Number
Range N/A
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related RESETFL
Parameters
Remarks

- 2670 -
Chapter 20 - Rxxxx Parameters

20.250 RESPTIMEAVG

Specific to Block(s) 850M


Description Average response time(ms)
Data Type FLOAT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

20.251 RESPTIMEMAX

Specific to Block(s) 850M


Description Slowest response time(ms)
Data Type FLOAT32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

20.252 RESPTIMEMIN

Specific to Block(s) 850M


Description Fastest response time(ms)
Data Type FLOAT32
Range
Default 0
Config Load No
Active Loadable No

- 2671 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks

20.253 RESTART

Specific to SCM, RCM


Block(s)
Description Restart - Indicates type of last restart.
Data Type Enumeration (Blockrestart)
Range None (0) There has been no restart transition since the last execution of the
SCM/RCM.
CMLOAD (1) The SCM/RCM has been loaded since its last execution. This value
also applies the very first time an SCM/RCM is executed.
CMACTIVE The SCM/RCM has been stopped and reset since it's last execution.
(3)
CEECOLD The CEE containing the SCM/RCM has gone through a cold restart
(4) since the last execution of the SCM/RCM.
CEEWARM The CEE containing the SCM/RCM has gone through a warm restart
(5) since the last execution of the SCM/RCM.
CEESWITCH The controller hosting the CEE which contains the SCM/RCM has
(6) gone through a redundancy switchover since the last execution of
the SCM/RCM.
Default None (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to STARTSIGNAL
Block(s)
Description This is an enumeration type summary parameter. It stores the type of restart that
has occurred since last execution
Data Type Enumeration (Blockrestart)
Range NONE (0) The normal value for the RESTART parameter is NONE.
Following a transition, it shows a value other than NONE
until the end of the first block execution.
CMLOAD (1) This parameter holds True for the first execution cycle
following a load of the parent CM.
CMACTIVE (3) This parameter holds True for the first execution cycle

- 2672 -
Chapter 20 - Rxxxx Parameters

following inactivation and then activation of the parent CM.


CEECOLD (4) This parameter holds True for the first execution cycle
following cold start of the CEE.
CEEWARM (5) This parameter holds True for the first execution cycle
following warm start of the CEE.
CEESWITCH (6) This parameter holds True for the first execution cycle
following redundant switchover of the CEE on a C200
Controller and C300 Controller.
Default NONE
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

20.254 RESTARTFL

Specific to Block Timer


(s)
Description Restart Command Flag - Provides ability to issue Restart command to the
Timer function block.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related COMMAND, RESETFL, STALECOUNT, STARTFL, STOPFL.
Parameters
Remarks An Off-to-On transition of RESTARTFL causes the timer to restart.

- 2673 -
Chapter 20 - Rxxxx Parameters

20.255 RESTARTOPT

Specific to DevCtl All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,
VALVEDAMPER
Description Sequential Control Module (SCM) Restart Option - Indicates activity for device when
ControlModule.SCMSTATE returns to Restarting or Running.
Data Type Enumeration RESTARTOPT
Range None (0) LastReq (1)
Default None (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related HOLDOPT, LASTOPMNAME, LASTOPREQ, All Drive Control: HOLDOPT,
Parameters LASTOPTYPE, LASTSTEP, OPREQ, OPTYPE, LASTOPMNAME, LASTOPREQ,
SAFEOP, SCHEDCYCLE[0..120] SCMASTEP[1..15] LASTOPTYPE, LASTSTAT.
SCMOPT, SCMSTATE, STARTOPT, STOPOPT.
Remarks Illegal if ControlModule.SCMOPT ≠ Fixed.

20.256 RETAINISTS

Specific to SCM
Block(s)
Description Retain Instruction Status - Provides a mechanism to control what happens to the
Instruction completion status of the Step in the Main handler that is returned to
from an Interrupt, Restart, or Hold handler.
Data Type Boolean
Range Off - Instruction Status of the Step in Main returned to is not retained, which
means that any confirmable Instructions of the Step will have to be confirmed
again, even if already confirmed prior to leaving the Main handler On - Instruction
Status of the Step in Main returned to is retained, which means that any
confirmable Instructions of the Step that have already been confirmed will not need
to be confirmed again
Default Off
Config No
Load
Active No
Loadable

- 2674 -
Chapter 20 - Rxxxx Parameters

Access Engineer
Lock
Residence CEE
Related For STEP block: INSTRUCTCOMP, OP[1..16].INSTRUCTCOMP.
Parameters
Remarks The Instruction completion status of the Step overall (INSTRUCTCOMP) and the
Step Outputs (OP[].INSTRUCTCOMP) is the specific information that is retained or
not. RETAINISTS can only be used when the SCM/RCM REEXECPOLICY is set to
AlwaysReExecute. Store errors will result on attempts to store to RETAINISTS when
the SCM/RCM REEXECPOLICY is set to Flexible. RETAINISTS can be set to On by
the Interrupt, Restart, or Hold handler as required before returning to the Main
handler. The value of RETAINISTS that is set in a Hold handler will be used on the
next return to Main. If a user configured Restart handler is defined and selected, it
can choose to write a new value to RETAINISTS or not before the return to Main is
actually executed. The value of RETAINISTS at the time of the return to Main will
drive the SCM behavior. After the return to Main handler is completed, RETAINISTS
is always be set to Off. RETAINISTS must be set to On again for the next return to
Main if retaining the Instruction Status is desired again.

20.257 RETENDATAATTND

Specific to Block(s) UOC


Description Retention Data Attendance
Data Type Enumeration
Range Absent, Present
Default Absent
Config Load No
Active Loadable No
Access Lock View Only
Residence UOC
Related Parameters RETENTIONSAVEFREEZE
Remarks True indicates that retention data is present.

Specific to UOC
Block(s)
Description Retention Data Attendance
Data Type Enumeration
Exposure Output
Range Absent, Present
Default Absent
Config Load No

- 2675 -
Chapter 20 - Rxxxx Parameters

Access Lock View Only


Residence CEE
Related RETENTIONSAVETIME
Parameters
Remarks RETENDATAATTND indicates when retention data is absent or present. When
present, RETENSAVETIME indicates the time it was saved.

20.258 RETENSAVEENABLED

Specific to Block CN100, C300, UOC


Description Enable periodic database retention save and diagnostics
Data Type Boolean
Range True, False
Default True
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence PCM
Related Parameters RETENDATAATTND, RETENSAVETIME, RETENVETOREASON
Remarks Enables power fail restart with saved database.

20.259 RETENSAVETIME

Specific to Block(s) CN100, C300, UOC


Description Retention Data Save Time
Data Type TIME
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence UOC
Related Parameters RETENTIONSAVEFREEZE
Remarks

- 2676 -
Chapter 20 - Rxxxx Parameters

20.260 RETENTIONSAVEFREEZE

Specific to Block(s) UOC


Description Control Freeze for Retention Data save (soft failure)
Data Type BOOLEAN
Range OFF, ON
Default OFF
Config Load No
Active Loadable No
Access Lock View Only
Residence UOC
Related Parameters RETENSAVETIME
RETENDATAATTND
RETENVETOREASON
Remarks

Specific to UOC
Block(s)
Description Control Freeze for Retention Data save
Data Type BOOLEAN
Exposure Output
Range OFF, ON
Default OFF
Config Load No
Access View Only
Lock
Residence CEE
Related None
Parameters
Remarks Upon commencing the save of retention data, this parameter is ON and a “Control
Freeze for Retention Data Save” soft failure is reported by the non-redundant or
primary UOC to indicate that control processing has been temporarily suspended.
Once retention data save is complete, this parameter is OFF and the soft failure
returns to normal.

20.261 RETENVETOREASON

Specific to Block(s) UOC


Description Reason Retention Restart was not performed
Data Type Enumeration
Range None
DeviceIndexChanged

- 2677 -
Chapter 20 - Rxxxx Parameters

UnsupportedHardware
RetentionMediaError
RetentionDataAbsent
RetentionDataCorrupt
RetentionDataExpired
RedundancyRoleSecondary
TimeSyncNotConfigured
TimeSyncTimeout
BaseIpAddrChanged
Default None
Config Load No
Active Loadable No
Access Lock View Only
Residence UOC
Related Parameters RETENTIONSAVEFREEZE
Remarks

Specific to UOC
Block(s)
Description Retention Veto Reason
Data Type Enumeration
Exposure Output
Range None

DeviceIndexChanged
UnsupportedHardware
RetentionMediaError

RetentionDataAbsent
RetentionDataCorrupt
RetentionDataExpired
RedundancyRoleSecondary
TimeSyncNotConfigured
TimeSyncTimeout
Default None
Config Load No

- 2678 -
Chapter 20 - Rxxxx Parameters

Access View Only


Lock
Residence CEE
Related None
Parameters
Remarks Initialized once on startup to indicate the reason why the controller has vetoed
retention startup.
None
Retention restart was not vetoed.
DeviceIndexChanged
Retention restart was vetoed due to a change in the controller’s device index setting.
BaseIpAddrChanged
Retention restart was vetoed due to a change in Base IP Address (and/or Base IP
Mask). A change in base IP Address implies the controller was redeployed in a
different Experion PKS cluster without changing its Device Index.
UnsupportedHardware
The controller hardware is defective or was not properly initialized when it was
manufactured.
RetentionMediaError
Retention restart was vetoed due to invalid retention memory detected by the
controller. Possible causes for invalid retention memory are as follows:
l SD card missing.
l SD card not inserted fully or not inserted properly.
l SD card format not recognized.
l SD card locked for read-only access.

RetentionDataAbsent
Retention data was not saved.

RetentionDataCorrupt
Retention data exists but did not pass controller validation.
RetentionDataExpired
The retention data was saved more than 48 hours ago.
RedundancyRoleSecondary
The retention data is discarded when the controller is in the secondary redundancy
role.
TimeSyncNotConfigured
Time-sync is not configured on the controller. Without time-sync configured, the
controller cannot determine the age of the retention data and to be safe, the retention
data is discarded.
TimeSyncTimeout
Time-sync is configured on the controller, but the controller timed-out waiting for the
time-sync server response. Without time-sync configured, the controller cannot
determine the age of the retention data and to be safe, the retention data is
discarded.

- 2679 -
Chapter 20 - Rxxxx Parameters

Starting in R511.4, the RetentionDataExpired, TimeSyncNotConfigured, and


TimeSyncTimeout retention restart veto reasons are no longer applicable as the
retention data no longer expires due to time-of-life.

20.262 RETRANSMISSIONSZ

Specific to Block(s) OPCUASRVUOC


Description Maximum Retransmission Queue
Sizes
Data Type UINT32
Range 0 to 4294967295
Default 20
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEEAL
Related Parameters None
Remarks

20.263 RETRYOPT

Specific to SCM, RCM


Block(s)
Description Retry Option
Data Type Enumeration
Range 0 Default If available: Follow CEE, otherwise: Endless retries (this is the
behavior of former releases). Failed output can be cancelled in
SingleStep mode.
1 Retry0 No retries. Step will complete immediately after all outputs have
been processed one time, regardless of their success.
2 Retry1 One retry. Step will complete after 1 failed retry or after success,
whatever comes first. Failed output can be cancelled in SingleStep
mode when retry is not yet done.
3 Retry3 Three retries. Step will complete after 3 failed retries or after
success, whatever comes first. Failed output can be cancelled in
SingleStep mode when retries are not yet done.
4 Retry10 Ten retries. Step will complete after 10 failed retries or after success,
whatever comes first. Failed output can be cancelled in SingleStep
mode when retries are not yet done.
Default Default (0)
Config Yes
Load

- 2680 -
Chapter 20 - Rxxxx Parameters

Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related STORESTS
Parameters

20.264 RETRYSCURR

Specific to Block(s) QIPACCHAN


Description Retrys Last Transaction
Data Type 32-Bit Unsigned Integer
Range n/a
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters None
Remarks

20.265 RETRYSTOTAL

Specific to Block(s) QIPACCHAN


Description Retrys Total
Data Type 32-Bit Unsigned Integer
Range n/a
Default 0
Config Load No
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters None
Remarks

- 2681 -
Chapter 20 - Rxxxx Parameters

20.266 RFB

Specific to Block(s) PIDER


Description Reset Feedback (RFB) - Indicates RFB input value.
Data Type Float64
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PV, S1, K1, SP, TRFB.
Remarks

20.267 RG

Specific to FLOWCOMP
Block(s)
Description Reference Specific Gravity - Reference specific gravity or molecular weight used by
the block. The value must be in the same engineering units as G (specific gravity).
Data Type Real
Range NaN is not allowed
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related G
Parameters
Remarks

20.268 RHPWEIGHTS

Specific to Block(s) ProfitCtl


Description RHP weights
Data Type FLOAT64
Range NA
Default 0
Config Load Yes

- 2682 -
Chapter 20 - Rxxxx Parameters

Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

20.269 RJRAW

Specific to Block(s) LLAI


Description Reference Junction's Raw Count, in microvolts
Data Type 32-Bit Real Number
Range
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks

20.270 RJTEMP

Specific to LLAI
Block(s)
Description Reference Junction Temperature, in Celsius. Displays the current temperature of
the reference junction sensor, and is updated only if the thermocouple input is
configured.
Data Type 32-Bit Real Number
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks

- 2683 -
Chapter 20 - Rxxxx Parameters

20.271 RLSRESABNORM

Specific to SCM, RCM


Block(s)
Description Release Resources in Abnormal termination
Data Type Boolean
Range 0 OFF All resources that were not explicitly
released by the phases or steps are
left acquired to the RCM or SCM
1 ON Resources acquired by the RCM or
SCM are released automatically
before the RCM has reached the
ABORTED or terminal STOPPED
state
Default ON
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related RLSRESNORM
Parameters
Remarks RCM or SCM will reach the terminal state, even if there are errors releasing the
resources. If the terminal state has been reached, although not all resources have
been released; the ExecSts of RCM or SCM will be Warning, if no other higher
ExecSts condition exists.

20.272 RLSRESNORM

Specific to SCM, RCM


Block(s)
Description Release Resources in Normal termination
Data Type Boolean
Range 0 OFF All resources that were not
explicitly released by the phases
or steps are left acquired to the
RCM or SCM
1 ON Resources acquired by the RCM
or SCM are released
automatically before the RCM
has reached the COMPLETE
state.
Default ON
Config Yes
Load
Active No

- 2684 -
Chapter 20 - Rxxxx Parameters

Loadable
Access Lock Engineer
Residence CEE
Related RLSRESABNORM
Parameters
Remarks RCM or SCM will reach the terminal state, even if there are errors releasing the
resources. If the terminal state has been reached, although not all resources have
been released; the ExecSts of RCM or SCM will be Warning, if no other higher
ExecSts condition exists.

20.273 RMW

Specific to FLOWCOMP
Block(s)
Description Reference Molecular weight. The RMW value must be in the same engineering
units as MW (Molecular Weight).
Data Type Real
Range NaN is not allowed
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related MW
Parameters
Remarks

20.274 ROCLM

Specific to Block(s) GRPCAPRBK


Description Current Rate of Change Limit.
Data Type Float64
Range
Default NaN
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks The Rate of Change Limit Output.

- 2685 -
Chapter 20 - Rxxxx Parameters

20.275 ROCLMOPT

Specific to Block(s) GRPCAPRBK


Description ROCLimit FailSafe Option
Data Type Enumeration
Range SAFEVAL, LASTVAL
Default SAFEVAL
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks User sets the safe value option using this parameter.

20.276 ROCNEGALM.FL

Specific to DataAcq
Block(s)
Description Negative Rate-of-Change Alarm Flag - Indicates if a negative rate-of-change alarm
has been issued.
Data Type Boolean
Range Off (0): Negative rate-of-change alarm does not exist. On (1): Negative rate-of-
change alarm present.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2686 -
Chapter 20 - Rxxxx Parameters

20.277 ROCNEGALM.PR

Specific to DataAcq
Block(s)
Description Negative Rate-of-Change Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

20.278 ROCNEGALM.SV

Specific to DataAcq
Block(s)
Description Negative Rate-of-Change Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2687 -
Chapter 20 - Rxxxx Parameters

20.279 ROCNEGALM.TM

Specific to DataAcq block


Block(s)
Description Rate Of Change Negative Alarm time in seconds.
Data Type UNIT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks To configure the on-delay time for the Rate Of Change Negative alarm. For more
information about alarm configuration, refer to Control Builder Components Theory
Guide.

20.280 ROCNEGALM.TMO

Specific to Block(s) DataAcq block


Description Rate Of Change Negative Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related Parameters
Remarks To configure the off-delay time for the Rate Of Change Negative alarm.

- 2688 -
Chapter 20 - Rxxxx Parameters

20.281 ROCNEGALM.TP

Specific to DataAcq
Block(s)
Description Negative Rate-of-Change Alarm Trip Point (in Engineering Units per minute) -
Maximum change in the Process Variable (PV), in the negative direction, before a
negative rate-of-change alarm is issued.
Data Type 64-Bit Real Number
Range NaN, or greater-than or equal-to 0.0.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PV, ROCNEGALM.FL, ROCNEGALM.PR, ROCNEGALM.SV.
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

20.282 ROCPOSALM.FL

Specific to DataAcq
Block(s)
Description Positive Rate-of-Change Alarm Flag - Indicates if a positive rate-of-change alarm
has been issued.
Data Type Boolean
Range Off (0): Positive rate-of-change alarm does not exist. vOn (1): Positive rate-of-
change alarm present.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, ROCPOSALM.PR, ROCPOSALM.SV, ROCPOSALM.TP.
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2689 -
Chapter 20 - Rxxxx Parameters

20.283 ROCPOSALM.PR

Specific to DataAcq
Block(s)
Description Positive Rate-of-Change Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PV, ROCPOSALM.FL, ROCPOSALM.SV, ROCPOSALM.TP.
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

20.284 ROCPOSALM.SV

Specific to DataAcq
Block(s)
Description Positive Rate-of-Change Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PV, ROCPOSALM.FL, ROCPOSALM.PR, ROCPOSALM.TP.
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

- 2690 -
Chapter 20 - Rxxxx Parameters

20.285 ROCPOSALM.TM

Specific to DataAcq block


Block(s)
Description Rate Of Change Positive Alarm time in seconds.
Data Type UNIT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active No
Loadable
Access Lock EngineerAppDev
Residence CEE
Related
Parameters
Remarks To configure the on-delay time for the Rate Of Change Positive alarm. For more
information about alarm configuration, refer to Control Builder Components Theory
Guide.

20.286 ROCPOSALM.TMO

Specific to Block(s) DataAcq block


Description Rate Of Change Positive Alarm Off Delay Time
Data Type UINT32
Range 0 to 9999 seconds
Default 0
Config Load Yes
Active Loadable No
Access Lock EngineerAppDev
Residence CEE
Related Parameters
Remarks To configure the off-delay time for the Rate Of Change Positive alarm.

- 2691 -
Chapter 20 - Rxxxx Parameters

20.287 ROCPOSALM.TP

Specific to DataAcq
Block(s)
Description Positive Rate-of-Change Alarm Trip Point (in Engineering Units per minute) -
Maximum change in the Process Variable (PV), in the positive direction, before a
positive rate-of-change alarm is issued.
Data Type 64-Bit Real Number
Range NaN, or greater-than or equal-to 0.0.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PV, ROCPOSALM.FL, ROCPOSALM.PR, ROCPOSALM.SV.
Parameters
Remarks For more information on DataAcq alarming, refer to the Control Builder Components
Theory, DATAACQ (Data Acquisition) Block,.Alarm processing.

20.288 ROCSAFELM

Specific to Block(s) GRPCAPRBK


Description ROC Limit Safe Value
Data Type IEEEFloat64
Range
Default NaN
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks This can be configured only when ROCLMOPT=SAFEVAL

20.289 ROLE

Specific to Block(s) Step


Description Role
Data Type String
Range 16 Characters

- 2692 -
Chapter 20 - Rxxxx Parameters

Default Blank
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

20.290 ROLLAVGBAD

Specific to RollAvg
Block(s)
Description Number of bad samples that are excluded from calculating the rolling average.
Data Type INTEGER
Range 0 to 3800 - 3800 is the maximum number of samples that can be collected based on
the Control Module's execution period and sample collection frequency.
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related None
Parameters
Remarks During execution of the block, this parameter value is incremented by “1” if the
input (IN) is bad (“NaN” or “Infinity”). Also, if the rolling average sample buffer
contains only NaN values, this parameter value is equal to the ROLLAVGSZ
parameter value and the OUT remains at NaN. A disconnected input, NaN, or
infinity is considered as bad value and is excluded from rolling average calculation.
A warm or cold restart of the controller results in initialization of ROLLAVGBAD
value (start at 0).

20.291 ROLLAVGOK

Specific to RollAvg
Block(s)
Description Number of good samples that are included in calculating the rolling average.
Data Type INTEGER
Range 0 to 3800 - 3800 is the maximum number of samples that can be collected based on
the Control Module's execution period and sample collection frequency.
Default 0
Config No

- 2693 -
Chapter 20 - Rxxxx Parameters

Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related None
Parameters
Remarks During execution of the block, this parameter remains at “1” if the input (IN) is only
one good IN value followed by all NaN values. The OUT remains at the good IN
value. Also, if the rolling average sample buffer contains only NaN values, this
parameter value remains at “0” and the OUT remains at NaN. A warm or cold
restart of the controller results in initialization of ROLLAVGOK value (start at 0).

20.292 ROLLAVGRST

Specific to RollAvg
Block(s)
Description Used to reset the number of samples in the buffer to “0” and restart the next rolling
average sample collection without inactivating the CM.
Data Type Boolean
Range On - Remains “ON” until the next rolling average CM execution. Off -“OFF” if the
rolling average values are reset.
Default Off
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related None
Parameters
Remarks The initial value (default value) is stored internally in the following scenarios:
l Control Module's EXCESTATE transitions from INACTIVE to ACTIVE.
l ROLLAVGRST parameter is ON.
The values that are stored are ROLLAVGOK and ROLLAVGBAD are set to 0 and
ROLLAVGRST set to OFF.

20.293 ROLLAVGSZ

Specific to RollAvg
Block(s)
Description Displays the maximum number of FLOAT64 values that can be collected in the
Average Rolling function block.
Data Type Integer
Range 0 to 3800

- 2694 -
Chapter 20 - Rxxxx Parameters

Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ROLLBUF ROLLBUF ROLLFREQ ROLLFRBASE PERIOD
Parameters
Remarks The value of this parameter remains at “0” when a CM containing the Rolling
Average function block is activated without correcting the Rolling Average block load
errors. The value of this parameter remains unchanged when the CM Period is
change to a value that is illegal for Rolling Average execution.

20.294 ROLLBFBASE

Specific to RollAvg
Block(s)
Description Defines the unit of time for the collection buffer (ROLLBUF).
Data Type Enumeration ROLLBFBASE
Range Seconds (0) Minutes (1) Hours (2)
Default Minutes (1)
Config Yes
Load
Active No
Loadable
Access Lock AppDeveloper
Residence CEE
Related ROLLBUF ROLLFREQ ROLLFRBASE PERIOD
Parameters
Remarks This parameter along with ROLLBUF parameter specifies the duration of the
sample collection. For example, if the ROLLBFBASE is “Seconds” and ROLLBUF is
“20” then the size of the collection buffer if 20 seconds. This means that the
samples are collected upto 20 seconds and after 20 seconds, the new samples
overwrite the old samples in the buffer.

20.295 ROLLBUF

Specific to RollAvg
Block(s)
Description Defines how long the samples must be collected.
Data Type INTEGER
Range 1 to 3800

- 2695 -
Chapter 20 - Rxxxx Parameters

Default 1
Config Yes
Load
Active No
Loadable
Access Lock AppDeveloper
Residence CEE
Related ROLLFREQ ROLLFRBASE ROLLBFBASE PERIOD
Parameters
Remarks This parameter along with ROLLBFBASE parameter specifies the duration of the
sample collection. For example, if the ROLLBUF is “20” and ROLLBFBASE is
“Seconds” then the size of the collection buffer if 20 seconds. This means that the
samples are collected upto 20 seconds and after 20 seconds, the new samples
overwrite the old samples in the buffer.

20.296 ROLLFRBASE

Specific to RollAvg
Block(s)
Description Defines the unit of time that is associated with the frequency of sample collection
(ROLLFREQ).
Data Type Enumeration ROLLFRBASE
Range Seconds (0) Minute (1) Hours (2)
Default Seconds (0)
Config Yes
Load
Active No
Loadable
Access Lock AppDeveloper
Residence CEE
Related ROLLBUF ROLLFREQ ROLLBFBASE PERIOD
Parameters
Remarks This parameter along with the ROLLFREQ parameter defines how frequently the
samples must be collected. For example, if the ROLLFRBASE is “Seconds” and
ROLLFREQ is “2” then the frequency of sample collection is 2 seconds. This means
that the samples are collected every 2 seconds.

- 2696 -
Chapter 20 - Rxxxx Parameters

20.297 ROLLFREQ

Specific to RollAvg
Block(s)
Description Defines how frequently the samples must be collected. This must be a multiple of
the associated CM Period. For example, if the CM Period is 5 secs, ROLLFREQ value
can be a multiple of 5 (5, 10, 15, 20, and so on).
Data Type INTEGER
Range 1 to 3800
Default 1
Config Yes
Load
Active No
Loadable
Access Lock AppDeveloper
Residence CEE
Related ROLLBUF ROLLFRBASE ROLLBFBASE PERIOD
Parameters
Remarks This parameter along with the ROLLFRBASE parameter defines how frequently the
samples must be collected. For example, if ROLLFREQ is “2” and ROLLFRBASE is
“Seconds”then the frequency of sample collection is 2 seconds. This means that
the samples are collected every 2 seconds.

20.298 ROLLMULTIPLE

Specific to RollAvg
Block(s)
Description Displays the number of times the CM executes between rolling average sample
collections.
Data Type INTEGER
Range 0 to --
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ROLLBUF ROLLFREQ ROLLFRBASE ROLLBFBASE PERIOD
Parameters
Remarks The value of this parameter remains at “0” when a CM containing the Rolling
Average function block is activated without correcting the Rolling Average block load
errors. Also, the value of this parameter remains at “0” when the CM Period is
changed to a value that is illegal for Rolling Average execution.

- 2697 -
Chapter 20 - Rxxxx Parameters

20.299 ROMAPPIMGCHKSMFAIL

Specific to C300, FIM4, PGM, EHPM


Block(s)
Description ROM Application Image Checksum Failure
Data Type Boolean
Range On, Off
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related ROLLAVGSZ
Parameters
Remarks The Application image has a checksum value appended to the end. If this checksum
value is not the same as the value calculated at runtime then this flag is set to
indicate the softfail condition and a diagnostic alarm is issued.

20.300 ROMBOOTIMGCHKSMFAIL

Specific to C300, FIM4, PGM, EHPM


Block(s)
Description ROM Boot Image Checksum Failure
Data Type Boolean
Range On, Off
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related ROLLAVGSZ
Parameters
Remarks The Boot image has a checksum value appended to the end. If this checksum value
is not the same as the value calculated at runtime then this flag is set to indicate
the softfail condition and a diagnostic alarm is issued.

- 2698 -
Chapter 20 - Rxxxx Parameters

20.301 RP

Specific to FLOWCOMP
Block(s)
Description Reference Pressure - Defines the reference pressure used by the block. The RP
value must be in the same engineering units as P (pressure).
Data Type Real
Range NaN is not allowed
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence ACE/C200
Related ROLLAVGSZ
Parameters
Remarks

20.302 RPEERAVGLPS [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Peer Average IMRs Per Second - The average number of
peer messages per second sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RPEERMAXLPS
Parameters
Remarks Report By Exception Peer Average IMRs Per Second - The average number of
peer messages per second sent on the wire.

- 2699 -
Chapter 20 - Rxxxx Parameters

20.303 RPEERAVGLPSCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Peer Average IMRs Per Connection - The average number of
peer messages per connection sent on the wire.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RPEERMAXLPSCONN
Parameters
Remarks Report By Exception Peer Average IMRs Per Connection - The average number of
peer messages per connection sent on the wire.

20.304 RPEERAVGPPS [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Peer Average Parameters Per Second - The average number
of parameters per second sent on the wire.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RPEERMAXPPS
Parameters
Remarks Report By Exception Peer Average Parameters Per Second - The average number
of parameters per second sent on the wire.

- 2700 -
Chapter 20 - Rxxxx Parameters

20.305 RPEERAVGPPSCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Peer Average Parameters Per Connection - The average
number of parameters per Connection sent on the wire.
Data Type Float64
Range Greater than or equal to 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CEECN100
Related RPEERMAXPPSCONN
Parameters
Remarks Report By Exception Peer Average Parameters Per Connection - The average
number of parameters per Connection sent on the wire.

20.306 RPEERCONN

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Responder Peer Connections - The number of peer connections currently
open.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Responder Peer Connections - The number of peer connections currently
open.

- 2701 -
Chapter 20 - Rxxxx Parameters

20.307 RPEERCONNMAX

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Responder Peer Connections Maximum - The maximum number of peer
connections supported in this version of firmware.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Responder Peer Connections Maximum - The maximum number of peer
connections supported in this version of firmware.

20.308 RPEERDEGIMRCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Number of Peer IMRs Degraded to Request-Response - Indicates the count of peer
IMRs that have degraded to Request-Response on each connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks Number of Peer IMRs Degraded to Request-Response - Indicates the count of peer
IMRs that have degraded to Request-Response on each connection.

- 2702 -
Chapter 20 - Rxxxx Parameters

20.309 RPEERDEGRADIMR[1..RPEERCONNMAX]

Specific to CEE, IOLIM, FIM


Block(s)
Description Request-Response Peer Degradation IMRs - The number of peer IMRs that have
degraded to Request -Response on each connection.
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE, IOLIM, FIM
Related
Parameters
Remarks

20.310 RPEERMAXLPS [1..RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Peer Maximum IMRs Per Second - The maximum number of
peer messages per second sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RPEERAVGLPS
Parameters
Remarks Report By Exception Peer Maximum IMRs Per Second - The maximum number of
peer messages per second sent on the wire.

- 2703 -
Chapter 20 - Rxxxx Parameters

20.311 RPEERMAXLPSCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Peer Maximum IMRs Per Connection - The maximum number
of peer messages per connection sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RPEERAVGLPSCONN
Parameters
Remarks Report By Exception Peer Maximum IMRs Per Connection - The maximum number
of peer messages per connection sent on the wire.

20.312 RPEERMAXPPS [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Peer Maximum Parameters Per Second - The maximum
number of parameters per second sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RPEERAVGPPS
Parameters
Remarks Report By Exception Peer Maximum Parameters Per Second - The maximum
number of parameters per second sent on the wire.

- 2704 -
Chapter 20 - Rxxxx Parameters

20.313 RPEERMAXPPSCONN [1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Report By Exception Peer Maximum Parameters Per Connection - The maximum
number of parameters per connection sent on the wire.
Data Type Float64
Range Greater than or equal to 0
Default 0.0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related RPEERAVGPPSCONN
Parameters
Remarks Report By Exception Peer Maximum Parameters Per Connection - The maximum
number of parameters per connection sent on the wire.

20.314 RPEERNAME[1...RPEERCONNMAX]

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Originator's Peer Name - The name of the CPM, ACE, FIM, or IOLIM peer
originator block.
Data Type EntityID
Range 16 Characters
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The name of the CPM, ACE, FIM, or IOLIM peer originator block.

- 2705 -
Chapter 20 - Rxxxx Parameters

20.315 RPEERNAMELOOKUP

Specific to CEE
Block(s)
Description Displays the ClusterID, EEC, and IOC of the originator name.
Data Type String
Range 20 characters
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related RPEERNAME[1...RPEERCONNMAX]
Parameters
Remarks It is a parameter which is used in custom graphic to display the Cluster ID, EEC, and
IOC of the originator name in the following format: ClusterID, EEC, IOC.

20.316 RPEERSUBPER[1...RPEERCONNMAX]

Specific to CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


Block(s)
Description Originator Peer Subscription Period - The subscription period in milliseconds for
the originator peer block.
Data Type 32-Bit Integer
Range 10 to 10000
Default 100
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks The subscription period in milliseconds for the originator peer block.

- 2706 -
Chapter 20 - Rxxxx Parameters

20.317 RPHYCONNID

Specific to Block CEEC300,GEEFB, CEEUOC


(s)
Description Physical Connection ID
Data Type 16-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, ACE, SIM_C200, UOC
(CEEUOC).
Related
Parameters
Remarks

20.318 RPTCONNECTIONSTATE

Specific to Block(s)
Description Primary Report Status
Data Type ENUM
Range NA
Default Not Defined
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

20.319 RPTENABLEFAILURE

Specific to Block(s)
Description Report Enable Failure
Data Type BOOL
Range NA
Default
Config Load No
Active Loadable No

- 2707 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks

20.320 RQ

Specific to FLOWCOMP
Block(s)
Description Reference Steam Quality Factor - Defines the reference steam quality factor used
by the block. The RQ value must be in the same engineering units as Q (steam
quality).
Data Type Real
Range NaN is not allowed
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related ROLLAVGSZ
Parameters
Remarks

20.321 RRRCEESTATE

Specific to Block(s) CEEC300, CEE, CPM


Description CEE STATE
Data Type ENUM
Range INPUT
Default IDLE (0) LASTCOLD (1) LASTWARM (2) LASTTIMEOUT (3)
Config Load IDLE
Active Loadable Yes
Access Lock Engineer
Residence C300(CEEC300), C200(CEE, CPM)
Related Parameters WARMTIMEOUT
Remarks Specifies the CEESTATE after RAM Retention Restart.

- 2708 -
Chapter 20 - Rxxxx Parameters

Specific to Block(s) CEEUOC


Description CEE STATE
Data Type ENUM
Range INPUT
Default IDLE (0) LASTCOLD (1) LASTWARM (2) LASTTIMEOUT (3)
Config Load IDLE
Active Loadable Yes
Access Lock Engineer
Residence UOC(CEEUOC)
Related Parameters WARMTIMEOUT
Remarks Specifies the CEESTATE after RAM Retention Restart.

20.322 RSPPIN

Specific to Block UCNOUT, HIWAYOUT


(s)
Description Remote Setpoint value in Percent Input - Indicates the value brought from the
primary in percent.
Data Type Float64
Range -6.9 to 106.9 percent
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related MODEOUT
Parameters
Remarks

20.323 RSTERRCNT

Specific to Block(s) PCDI_MASTER


Description Reset Error Count - Resets statistics on tab to zero.
Data Type Boolean
Range True/False
Default False
Config Load No
Active Loadable No

- 2709 -
Chapter 20 - Rxxxx Parameters

Access Lock Operator


Residence CEE
Related Parameters
Remarks Click the button to intitate reset of values in Monitoring mode.

20.324 RSTPROCESSED

Specific to SCM, RCM


Block(s)
Description Reset Processed Command
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related PROCEDURALLEVELPROCESSED
Parameters
Remarks Resets the PROCESSED flag on all blocks in this SCM/RCM. This will also cause
blue objects to become grey. Useful in loop configurations.

20.325 RSTRTINIDLY

Specific to CEEFB, CEEACEFB, CEESIMC200FB, CEEC300, CEEUOC, CEECN100


Block(s)
Description Restart Initialization Delay
Data Type INT32
Range 0 to 100 seconds
Default 10
Config Yes
Load
Active No
Loadable

- 2710 -
Chapter 20 - Rxxxx Parameters

Access Engineer
Lock
Residence CEE
Related RELOADINIDLY CURRELINIDLYINITPENDING
Parameters
Remarks RSTRTINIDLY specifies a delay interval, in seconds, during which CMs prevent
blocks and supervisory applications from reading component block data. While the
delay counts down, CMs execute their component blocks to bring data state into
alignment with the process. RSTRTINIDLY comes into play following two types of
CEE restart transitions.
l RAM Retention Start Up of a C300 or C200E.
l Idle to Run transition following checkpoint restore of an ACE, a C300 or a
C200E.
If the CEE is left idle following RAM Retention Restart or Checkpoint Restore, then
CMs hold off read clients until the CEE transitions to run. CEE.RSTRTINIDLY is
similar to CM.RELOADINIDLY except that it applies to the CEE as a whole rather
than to an individual CM. Also, it has units of seconds rather than units of CM
execution counts. If RELOADINIDLY is nonzero for a particular CM, then the total
delay imposed at restart is the sum of CM.RELOADINIDLY and the scaled value of
CEE.RSTRTINIDLY. This is shown by the following formula which applies
immediately after restart. CM.CURRELINIDLY = CM.RELOADINIDLY + (
CEE.RSTRTINIDLY / CM.PERIOD ) RSTRTINIDLY needs to be large enough for
groups of interconnected CMs to initialize completely before any of them allow their
data to be read. A value of 10 seconds is generally more than sufficient. However,
unusual CEE configurations might require a larger value. For example, a CEE with a
strategy of more than 5 interconnected CMs each with a period of 2 seconds, where
the CMs were not ordered by data dependency, would require a RSTRTINIDLY
greater than 10 seconds.

20.326 RSTSTATS

Specific to Block(s) PCDI_MASTER


Description Reset Statistics - Resets statistics on tab to zero.
Data Type Boolean
Range True/False
Default False
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks Click button to intitate reset of statistic values in Monitoring mode.

- 2711 -
Chapter 20 - Rxxxx Parameters

20.327 RT

Specific to Block RatioBias


(s)
Description Ratio Input Value (in Engineering Units) - The value by which ROLLAVGSZ is
multiplied.
Data Type Real
Range RTLOLM to RTHILM
Default 1
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related ROLLAVGSZROLLAVGSZ
Parameters
Remarks RT is an initializable input.

Specific to FLOWCOMP
Block(s)
Description Reference Temperature - Defines the reference temperature used by the block.
The RT value must be in the same engineering units as T (temperature).
Data Type Real
Range NaN is not allowed
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks

20.328 RTABLE.DIAG[1..5000]

Specific to SCM, RCM


Block(s)
Description Diagnostic Bits of RTable Part
Data Type Integer32
Range Bit 0: The object has been selected by the user to permanently
enable get requests.
Bit 1: The object is an InvokeTransition
Bit 2: The object is a Step with configured exception condition(s).

- 2712 -
Chapter 20 - Rxxxx Parameters

Bit 3: The object is needed for the current context of execution of


the SCM.
Bit 4: The object is needed to satisfy external requests (other
function blocks, CB Monitoring, Displays and so on).
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Diagnostic parameter only , Not for use by operator or normal project engineering

20.329 RTABLE.PART[1..5000]

Specific to Block(s) SCM, RCM


Description R-Table: Step/Transition
Data Type BlockID
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.330 RTABLE.PARTN[1..5000]

Specific to Block(s) SCM, RCM


Description R-Table: Step/Transition Number
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No

- 2713 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence
Related Parameters
Remarks

20.331 RTABLE.PEER[1..5000]

Specific to Block(s) SCM, RCM


Description R-Table: Number of Peer Connections
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.332 RTABLE.STATE[1..5000]

Specific to Block(s) SCM, RCM


Description R-Table: Age of Part in seconds
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2714 -
Chapter 20 - Rxxxx Parameters

20.333 RTABLE.STATE[1..5000]

Specific to Block(s) SCM, RCM


Description R-Table: Age of Part in seconds
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.334 RTABLENROWS

Specific to Block(s) SCM, RCM


Description Number of R-Table Rows
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.335 RTABLEUROWS

Specific to Block(s) SCM, RCM


Description Number of R-Table Used Rows
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No

- 2715 -
Chapter 20 - Rxxxx Parameters

Access Lock Engineer


Residence
Related Parameters
Remarks

20.336 RTABLEIDX

Specific to Block(s) STEP, TRANSITION


Description Index of Step/Transition in RTable
Data Type Integer32
Range 0: Step/Transition not registered in
RTable
>= 1 The index of Step/Transition in
RTable.
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Diagnostic parameter only , Not for use by operator or normal project
Parameters engineering
Remarks Diagnostic parameter only , Not for use by operator or normal project
engineering

20.337 RTBACKCALOUT

Specific to RatioBias
Block(s)
Description RT Secondary Data - Contains limits, initialization data, windup status, and so on for
the RT primary.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active No
Loadable

- 2716 -
Chapter 20 - Rxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks RatioBias function block maintains separate BACKCALC records for each of its
primaries, that is, RTBACKCALOUT for RT primary and X1BACKCALOUT for X1
primary.

20.338 RTCONN

Specific to Block(s) RatioBias


Description RT Connector
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock Application Developer
Residence
Related Parameters
Remarks

20.339 RTDTYPE

Specific to UAI
Block(s)

Description RTD Type


Data Type ENUM
Range
0 PT100(-184_816_C)

1 PT100(-300_1500_F)

2 PT100(-184_649_C)

3 PT100(-300_1200_F)

4 PT100(-184_316_C)

5 PT100(-300_600_F)

6 PT500(-184_649_C)

7 PT500(-300_1200_F)

8 PT1000(-40_260_C)

9 PT1000(-40_500_F)

10 JIS100(-n200_500_C)

- 2717 -
Chapter 20 - Rxxxx Parameters

11 JIS100(-328_932_F)

12 JIS100(-200_260_C)

13 JIS100(-328_500_F)

14 Cu10(-20_250_C)

15 Cu10(-4_482_F)

16 YSI405(10_37.8_C)

17 YSI405(50_100_F)

18 0_200_Ohms

19 0_500_Ohms

20 0_1000_Ohms

21 0_2000_Ohms

22 0_4000_Ohms

Default 0 PT100(-184_816_C)
Config Yes
Load

Active No
Loadable

Access Application Developer


Lock

Residence IOM Block


Related SENSRTYP_AI_C
Parameters

Remarks This parameter defines the type of RTD device connected. This parameter is exposed
when SENSRTYP_AI_C is set to RTD.
The user is always provided with the list of valid values for the particular AI sensor type.
The user is NEVER shown or given the opportunity to select an invalid value.

20.340 RTHIFL

Specific to Block(s) RatioBias


Description RT High Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2718 -
Chapter 20 - Rxxxx Parameters

20.341 RTHILM

Specific to Block(s) RatioBias


Description Ratio High Limit (in Engineering Units)
Data Type Real
Range RTLOLM to 100.0
Default 100.0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters ROLLAVGSZ
Remarks

20.342 RTLOFL

Specific to Block(s) RatioBias


Description RT Low Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

20.343 RTLOLM

Specific to Block(s) RatioBias


Description Ratio Low Limit (in Engineering Units)
Data Type Real
Range 0.001 to RTHILM
Default 0.001
Config Load Yes
Active Loadable No

- 2719 -
Chapter 20 - Rxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters ROLLAVGSZ
Remarks

20.344 RTOTACYCIMR

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Total Acyclic IMRs Used
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.345 RTOTACYCLGREQ

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Total Acyclic Large Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

- 2720 -
Chapter 20 - Rxxxx Parameters

20.346 RTOTACYCSMREQ

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Total Acyclic Small Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.347 RTOTCYCIMR

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Total Cyclic IMRs Used
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

- 2721 -
Chapter 20 - Rxxxx Parameters

20.348 RTOTCYCLGREQ

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Total Cyclic Large Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.349 RTOTCYCSMREQ

Specific to Block CEE, CEEC300, IOLIM, FIM, IOLINKC300, CEEUOC, CEECN100


(s)
Description Total Cyclic Small Requests
Data Type 32-Bit Integer
Range Greater than or equal to 0
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300(CEEC300, IOLINKC300), C200(CEE), IOLIM, FIM, UOC(CEEUOC), CN100
(CEECN100)
Related
Parameters
Remarks

20.350 RTPPRESENT

Specific to Block(s) AIM


Description RTP Present.
Data Type Boolean
Range Off (0) On (1)

- 2722 -
Chapter 20 - Rxxxx Parameters

Default Off (0)


Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks RTPPRESENT is only configurable on the Thermocouple module.

20.351 RUNBKACTALM.FL

Specific to Block(s) GRPCAPRBK


Description Runback active alarm Flag
Data Type Boolean
Range OFF ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters RUNBKACTALM.PR, RUNBKACTALM.SV
Remarks

20.352 RUNBKACTALM.PR

Specific to Block(s) GRPCAPRBK


Description Runback active alarm Priority
Data Type Enumeration
Range NONE JOURNAL LOW HIGH URGENT
Default LOW
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters RUNBKACTALM.FL, RUNBKACTALM.SV
Remarks Priority for alarm

- 2723 -
Chapter 20 - Rxxxx Parameters

20.353 RUNBKACTALM.SV

Specific to Block(s) GRPCAPRBK


Description Runback active alarm Severity
Data Type 16-Bit Integer
Range 0-15
Default 0
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters RUNBKACTALM.FL, RUNBKACTALM.PR
Remarks Severity for alarm.

20.354 RUNBKACTFL

Specific to Block(s) GRPCAPRBK


Description Runback active due to Group.
Data Type Boolean
Range OFF ON
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

20.355 RUNPULSEWIDTH

Specific to Block(s) HTMOTOR, LTMOTOR


Description Run Output Pulsewidth
Data Type Float64
Range 0 to 60 seconds
Default 1
Config Load YES
Active Loadable No

- 2724 -
Chapter 20 - Rxxxx Parameters

Access Lock ENGINEER


Residence CEE
Related Parameters STOPPULSEWIDTH
Remarks

20.356 RUNTIME

Specific to Block(s) HTMOTOR, LTMOTOR


Description Amount of RUN hours
Data Type Float64
Range 0 - Max of Real Number
Default 0.0
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters TRKSTATETIME
Remarks Used to indicate the amount of time the motor is in RUN state.

20.357 RV

Specific to Timer
Block(s)
Description Remaining Time - Indicates the current remaining time until the Timer function
block will time out.
Data Type Integer
Range 0 to 2,147,483,647 (2^31-1)
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, SO, SP, TIMEBASE.
Parameters
Remarks RV is equal to the difference between the Set Point and Process Variable (SP -
PV). Units are set by TIMEBASE.

- 2725 -
Chapter 20 - Rxxxx Parameters

20.358 RX

Specific to FLOWCOMP
Block(s)
Description Reference Steam Compressibility - Defines the reference steam compressibility
used by the block. The RX value must be in the same engineering units as Q (steam
compressibility).
Data Type Real
Range NaN is not allowed
Default 1.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence C200, C300, ACE
Related
Parameters
Remarks

- 2726 -
CHAPTER

21 SXXXX PARAMETERS

21.1 S 2738
21.2 S1 2739
21.3 SAFEOP 2740
21.4 SAFEOPALM.FL 2741
21.5 SAFEOPALM.PR 2741
21.6 SAFEOPALM.SV 2742
21.7 SAFEOPCMD 2742

21.8 SAFEOPTRIGFL 2742


21.9 SAFEOUTPUT 2743
21.10 SAFEOUTPUT[6..7] 2744
21.11 SAFEREDTAG 2744
21.12 SAFESTATE[0..numChans-1] 2745
21.13 SAFINTER.FL 2745
21.14 SAMPLERATE 2746
21.15 SAMPLESKEW 2746
21.16 SAVEDELAY1 2747
21.17 SAVEDELAY2 2747
21.18 SCAADVCODE1 2748
21.19 SCAADVCODE2 2749
21.20 SCACOMCOUNT 2750
21.21 SCACOMSTS 2751
21.22 SCADEVID 2751
21.23 SCADEVMFG 2752
21.24 SCADEVREV 2753
21.25 SCADEVTYPE 2753
21.26 SCADEVTYPENAME 2754
21.27 SCAHWREV 2754
21.28 SCALASTCOMCODE 2755
21.29 SCAREQCODE 2756
21.30 SCARESPCODE 2757
21.31 SCASWREV 2757
21.32 SC.BYPPERM 2758

- 2727 -
Chapter 21 - Sxxxx Parameters

21.33 SC.BYPREQ 2758


21.34 SC.CONFIGCODE 2758
21.35 SC.CONFIGDESC 2759
21.36 SC.CONFIGSTS 2759
21.37 SC.DESC 2760
21.38 SC.EXECCODE 2760
21.39 SC.EXECDESC 2761
21.40 SC.EXECSTS 2761
21.41 SC.EXPR 2761
21.42 SC.EXPRPCODE 2762
21.43 SC.FL 2762
21.44 SC.INVOKFL 2763
21.45 SC.OPT 2763
21.46 SCALARTAGREADS 2763

21.47 SCALEMOTION[1..24] 2764


21.48 SCALEMOTION[1..200] 2764
21.49 SCALEPERIOD 2765
21.50 SCALESELECTD[1..4] 2766
21.51 SCANAREA 2766
21.52 SCANASSOCDSP 2767
21.53 SCANCTRLLVL 2768
21.54 SCANEUHI 2768
21.55 SCANEULO 2769
21.56 SCANFREQ 2770
21.57 SCANGRPDTL 2770
21.58 SCANOVERRUN 2771
21.59 SCANPNTDTL 2771
21.60 SCANRATE 2772
21.61 SCANRATE(UOC) 2775
21.62 SCANRATE [1...40] 2776
21.63 SCHDOPTIMIZE 2776
21.64 SCHEDCYCLE[0..120] 2777
21.65 SCINCONNHNDL[1..6] 2777
21.66 SCINCONNNAV[1..6] 2778
21.67 SCINCONNPRM[1..6] 2778
21.68 SCINCONNSTRVAL[1..6] 2778
21.69 SCINCONNVAL[1..6] 2779
21.70 SCMASTEP[1..15] 2779
21.71 SCMID 2780

- 2728 -
Chapter 21 - Sxxxx Parameters

21.72 SCMMODE 2780


21.73 SCMMONITOR 2780
21.74 SCMMONSRC 2781
21.75 SCMNAME 2781
21.76 SCMOPT 2782
21.77 SCMSTATE 2783
21.78 SCNUMSRCCONN 2783
21.79 SCRIPTOR 2784
21.80 SCSRC[1..6] 2784
21.81 SDENUMTEXT 2784
21.82 SEALOPT 2785
21.83 SECCANTTALKTOPRIONUCN 2785
21.84 SECBLOCKNAME [1...40] 2786
21.85 SECCHNERRA [1...40] 2786

21.86 SECCHNERRB [1...40] 2787


21.87 SECCHNMNA [1...40] 2787
21.88 SECCHNMNB [1...40] 2788
21.89 SECCHNPLA [1...40] 2788
21.90 SECCHNPLB [1...40] 2789
21.91 SECCHNSILA [1...40] 2789
21.92 SECCHNSILB [1...40] 2790
21.93 SECCOMMERR [1..40] 2791
21.94 SECCONNSTS 2792
21.95 SECDATAIN 2792
21.96 SECDATAIN.ARWSTS 2793
21.97 SECDATAIN.CASREQ 2794
21.98 SECDATAIN.CASSHED 2795
21.99 SECDATAIN.EUHI 2795
21.100 SECDATAIN.EULO 2796
21.101 SECDATAIN.EUSPAN100 2797
21.102 SECDATAIN.HISELECT 2798
21.103 SECDATAIN.INITREQ 2798
21.104 SECDATAIN.INITSTS 2799
21.105 SECDATAIN.INITVAL 2800
21.106 SECDATAIN.LOCALMAN 2801
21.107 SECDATAIN.ONESHOT 2802
21.108 SECDATAIN.ORFBSTS 2802
21.109 SECDATAIN.ORFBVAL 2803
21.110 SECDATAIN.OROFFSET 2804

- 2729 -
Chapter 21 - Sxxxx Parameters

21.111 SECDATAIN.PROPOVRD 2804


21.112 SECDATAIN.SECTYPE 2805
21.113 SECERRCNT 2806
21.114 SECERRCODE 2806
21.115 SECERRFL 2807
21.116 SECERRINFO 2807
21.117 SECIFCHNERRA 2808
21.118 SECIFCHNERRB 2808
21.119 SECIFCHNMNA 2809
21.120 SECIFCHNMNB 2809
21.121 SECIFCHNPLA 2810
21.122 SECIFCHNPLB 2810
21.123 SECIFCHNSILA 2811
21.124 SECIFCHNSILB 2811

21.125 SECIFCOMMERR 2812


21.126 SECIFRCVCHN 2813
21.127 SECINITOPT[1..8] 2813
21.128 SECINITOPT1 2814
21.129 SECIP 2814
21.130 SECIPMON 2815
21.131 SECLASTCONNTIME 2815
21.132 SECLASTDISCONNTIME 2815
21.133 SECLASTERRTIME 2816
21.134 SECLOOPDATA 2816
21.135 SECMODNAME 2817
21.136 SECNAMESTRG 2817
21.137 SECNAMESTRING 2818
21.138 SECNOTSYNED 2819
21.139 SECNUMCONN 2819
21.140 SECNUMCONNATMPT 2819
21.141 SECNUMDISCONN 2820
21.142 SECOND 2820
21.143 SECONDARYSIG 2821
21.144 SECOVERLAP[1..24] 2821
21.145 SECOVERLAP[1..200] 2822
21.146 SECRCVCHN [1..40] 2822
21.147 SECRPTCONNECTIONSTATE 2823
21.148 SECSIGSECLVL 2823
21.149 SECTCP 2824

- 2730 -
Chapter 21 - Sxxxx Parameters

21.150 SECTCPMON 2824


21.151 SECTMPNAME 2825
21.152 SECVAR 2825
21.153 SELDESC 2826
21.154 SELECTCABLEACMD 2826
21.155 SELECTCABLEBCMD 2827
21.156 SELHANDLER[1..8] 2828
21.157 SELHANDLERN[1..8] 2828
21.158 SELIN 2829
21.159 SELINT32FL 2829
21.160 SELMETHOD 2830
21.161 SELXDESC 2830
21.162 SELXFL[1..4] 2831
21.163 SELXFL[1..6] 2831

21.164 SELXFL[1..8] 2832


21.165 SELXINP 2832
21.166 SENDCLOSEREQ 2833
21.167 SENDCLOSERESP 2833
21.168 SENDFL[0..15] 2834
21.169 SENDOPENREQ 2834
21.170 SENDOPENRSP 2834
21.171 SENSORTYPE[0..numChans-1] 2835
21.172 SENSORTYPE [0..NUMCHANNELS-1] 2835
21.173 SENSRTYP 2836
21.174 SENSRTYP_AI_C 2840
21.175 SEQCLOSE 2842
21.176 SEQNOCMD 2843
21.177 SEQOPEN 2843
21.178 SEQSTART 2844
21.179 SEQSTATUS 2844
21.180 SEQSTOP 2844
21.181 SEQSTOPACTED 2845
21.182 SERIALNO 2845
21.183 SERIALNUM 2846
21.184 SERVERIP 2847
21.185 SHAREDMEM 2847
21.186 SHEDHOLD 2848
21.187 SHEDMODE[0..7] 2848
21.188 SHEDHOLD 2849

- 2731 -
Chapter 21 - Sxxxx Parameters

21.189 SHORT 2849


21.190 SHORT_DI_C 2850
21.191 SHORT[0..numChans-1] 2850
21.192 SHORTCIRCUIT[0..Number of status in assembly] 2851
21.193 Show UCM On Unit Timeline 2851
21.194 SHUTDOWNCMD 2851
21.195 SI 2852
21.196 SIACTED 2852
21.197 SIALM.FL 2853
21.198 SIALM.OPT 2853
21.199 SIALM.PR 2854
21.200 SIALM.SV 2855
21.201 SIFL 2855
21.202 SIMC200MACID 2856

21.203 SIMC200EMACID 2857


21.204 SIMCOMMAND 2857
21.205 SIMVALUE[1..1968] 2858
21.206 SIMDEVICEIDX 2858
21.207 SIMENABLE 2859
21.208 SIMIPADDRESS 2859
21.209 SIMMODE 2860
21.210 SIMSTATE 2862
21.211 SIMTARGET 2863
21.212 SIMULATEDIO 2863
21.213 SIMVALUE 2864
21.214 SIMVALUE[1..16] 2865
21.215 SIMVALUE[1..120] 2865
21.216 SIMVALUEREAL 2866
21.217 SIOPT 2866
21.218 SIPTYPE[0..7] 2867
21.219 SIPTYPE[0..numChans-1] 2867
21.220 SLOT0[0..7] 2868
21.221 SLOT1[0..7] 2868
21.222 SLOT2[0..7] 2869
21.223 SLOT3[0..7] 2869
21.224 SLOT 2870
21.225 SLOTNUM 2871
21.226 SLOTNUMBER 2872
21.227 SLOTNUM[0-3] 2873

- 2732 -
Chapter 21 - Sxxxx Parameters

21.228 SLOTSFBT 2873


21.229 SLOT0BOARDSTATUS 2874
21.230 SLOT0SELFTEST 2875
21.231 SLOT0STATUS 2875
21.232 SLOT0TS 2876
21.233 SLOT0TYPE 2876
21.234 SLOT2BOARDSTATUS 2877
21.235 SLOT2SELFTEST 2877
21.236 SLOT2STATUS 2878
21.237 SLOT2TYPE 2878
21.238 SLOT3BOARDSTATUS 2879
21.239 SLOT3SELFTEST 2879
21.240 SLOT3STATUS 2880
21.241 SLOT3TYPE 2880

21.242 SLOT4BOARDSTATUS 2881


21.243 SLOT4SELFTEST 2881
21.244 SLOT4STATUS 2882
21.245 SLOT4TYPE 2882
21.246 SLOT5BOARDSTATUS 2883
21.247 SLOT5SELFTEST 2883
21.248 SLOT5STATUS 2884
21.249 SLOT5TYPE 2884
21.250 SLOTTYPE 2885
21.251 SLOTNUM 2885
21.252 SLOWSTEPTIMR[1..24] 2886
21.253 SLOWSTEPTIMR[1..200] 2886
21.254 SLWFLSHSPD 2886
21.255 SNTPADDRESS 2887
21.256 SNTP1ADDR 2887
21.257 SNTP2ADDR 2888
21.258 SNTPSKEWTHLD 2888
21.259 SNTPSTAT 2889
21.260 SO 2889
21.261 SO[1..NUMCHAN] 2891
21.262 SO[6..7] 2892
21.263 SOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK] 2892
21.264 SOAKVAL[1..NUMPROFILES][1..NUMRAMPSOAK] 2893
21.265 SOCMDOFF 2893
21.266 SOCMDON 2894

- 2733 -
Chapter 21 - Sxxxx Parameters

21.267 SOESDENUM 2895


21.268 SOESTDESC 2895
21.269 SOFTFAIL 2896
21.270 SOFTFAIL1A 2897
21.271 SOFTFAIL2A 2897
21.272 SOFTFAIL1B 2898
21.273 SOFTFAIL2B 2898
21.274 SOFTWAREREV[0..7] 2899
21.275 SOINITVAL 2899
21.276 SOINITVAL[1..NUMCHAN] 2900
21.277 SOREADFAIL 2900
21.278 SOSOURCE 2901
21.279 SOSTS 2901
21.280 SLWSRCID 2901

21.281 SP 2902
21.282 SP1FASTFEED[1..4] 2904
21.283 SP2FASTFEED[1..4] 2904
21.284 SP1FEEDING[1..4] 2905
21.285 SP2FEEDING[1..4] 2905
21.286 SP1TOLERANCE[1..4] 2906
21.287 SPCODESIZE 2906
21.288 SPCONN 2907
21.289 SPECIALTYPE 2907
21.290 SPECIFICVOLUME 2908
21.291 SPECIFICVOLUMEENGUNIT 2908
21.292 SPECIFICVOLUMEIO 2909
21.293 SPEM 2909
21.294 SPEUHI 2909
21.295 SPEULO 2910
21.296 SPFORMAT 2911
21.297 SPHI 2911
21.298 SPHIACTIVE 2912
21.299 SPHIFL 2912
21.300 SPHILM 2913
21.301 SPHILMOPT 2913
21.302 SPHIOPTOFFSET 2914
21.303 SPHIRAMPRATE 2915
21.304 SPLO 2915
21.305 SPLOACTIVE 2916

- 2734 -
Chapter 21 - Sxxxx Parameters

21.306 SPLOFL 2916


21.307 SPLOLM 2917
21.308 SPLOLMOPT 2917
21.309 SPLOOPTOFFSET 2918
21.310 SPLORAMPRATE 2918
21.311 SPOUT 2919
21.312 SPP 2919
21.313 SPPIN 2920
21.314 SPRATEREQ 2920
21.315 SPREQ 2921
21.316 SPTOL 2921
21.317 SPTV 2922
21.318 SPTVARWOPT 2922
21.319 SPTVDEVFL 2923

21.320 SPTVDEVMAX 2924


21.321 SPTVNORMRATE 2924
21.322 SPTVOPT 2925
21.323 SPTVP 2925
21.324 SPTVRATE 2926
21.325 SPTVREQ 2926
21.326 SPTVSTATE 2927
21.327 SPTVTIME 2927
21.328 SRC 2928
21.329 SRCDATA[0] 2928
21.330 SRVACEHASBKP 2929
21.331 SRVHASBKP 2929
21.332 SSERROR 2930
21.333 SSOBJECTIVEVALUE 2930
21.334 SSRECTOEQM 2930
21.335 SSSINGULARVALUE 2931
21.336 SSTEPLOCK 2931
21.337 STALECOUNT 2932
21.338 STARTFL 2932
21.339 STARTINDEX 2933
21.340 STARTOFFSET 2935
21.341 STARTOP[1..NUMPROFILES] 2935
21.342 STARTOPSEL 2936
21.343 STARTOPT 2936
21.344 STARTPHASE 2937

- 2735 -
Chapter 21 - Sxxxx Parameters

21.345 STARTRATE 2938


21.346 STARTSEG[1..NUMPROFILES] 2938
21.347 STARTTIME 2939
21.348 STARTVAL 2939
21.349 STATE 2940
21.350 STATE0 2943
21.351 STATE1 2944
21.352 STATETEXT[*] 2944
21.353 STATETEXT[0..1] 2945
21.354 STATETEXT[0..3] 2945
21.355 STATETEXT[0..6] 2946
21.356 STATETIME[0..2] 2946
21.357 STATRESET 2947
21.358 STATSRESET 2948

21.359 STATRESETA 2949


21.360 STATRESETB 2950
21.361 STATUS_1[1..24] 2950
21.362 STATUS_2[1..24] 2951
21.363 STATUS 2951
21.364 STATUSRAW[1..4] 2952
21.365 STDBYMAN 2952
21.366 STDBYSTS 2953
21.367 STDBYSTSA 2953
21.368 STDBYSTSB 2954
21.369 STDTIME 2954
21.370 STEADYSTATEOP 2955
21.371 STEADYSTATEOPEU 2955
21.372 STEADYSTATEPV 2956
21.373 STEAM_WATER 2956
21.374 STEAMQUALITY 2957
21.375 STEAMQUALITYIO 2957
21.376 STEAMTYPE 2958
21.377 STEP 2958
21.378 STEPALM.FL 2958
21.379 STEPALM.PR 2959
21.380 STEPALM.SV 2959
21.381 STEPPERSTATUS 2960
21.382 STEPTOPHASE 2960
21.383 STICTIONL 2961

- 2736 -
Chapter 21 - Sxxxx Parameters

21.384 STICTIONR 2961


21.385 STIDBDISCRE 2961
21.386 STI_EU 2962
21.387 STIPVNUMBER 2964
21.388 STISCRATCHPAD 2964
21.389 STISTATUS 2965
21.390 STISWVER 2965
21.391 STITAG 2965
21.392 STMCHOVRRUNSA 2966
21.393 STMCHOVRRUNSB 2966
21.394 STMCHMAXOVRRUNTIMEA 2967
21.395 STMCHMAXOVRRUNTIMEB 2967
21.396 STMCHLASTOVERRUNTIMEA 2968
21.397 STMCHLASTOVERRUNTIMEB 2968

21.398 STNDPIPELEN 2968


21.399 STOPALM.FL 2969
21.400 STOPALM.PR 2969
21.401 STOPALM.SV 2970
21.402 STOPFL 2970
21.403 STOPOPT 2971
21.404 STOPPULSEWIDTH 2972
21.405 STOPRATE 2973
21.406 STOPSTATEOPT 2973
21.407 STOPTIME 2974
21.408 STOPVAL 2974
21.409 STOREENB 2975
21.410 STORESTS 2975
21.411 STORONCHGENB 2976
21.412 STR[0..7] 2976
21.413 STR[1..8] 2977
21.414 STR[1..16] 2977
21.415 STR[1..120] 2978
21.416 STRLEN 2978
21.417 STRRESP[ ] 2979
21.418 STTEXT 2980
21.419 STTEXTA 2980
21.420 STTEXTB 2981
21.421 STUBIOM 2981
21.422 SUBMODTYPE 2982

- 2737 -
Chapter 21 - Sxxxx Parameters

21.423 SUBSCRIBEFAIL 2982


21.424 SUBSCPERIOD 2983
21.425 SUBSLOTNUM 2984
21.426 SUBVAL 2985
21.427 SUBVALTYPE 2986
21.428 SUM_MAXD 2986
21.429 SUM_N_A 2986
21.430 SUM_N_B 2987
21.431 SUM_N_F 2987
21.432 SUM_N_S 2988
21.433 SUM_N_SJL 2988
21.434 SUM_N_SS 2988
21.435 SUPVFIFORATEA 2989
21.436 SUPVFIFORATEM 2989

21.437 SURPLUSSCNTIME 2990


21.438 SWAPCTRLCMD 2990
21.439 SWAPPOSCMD 2990
21.440 SWAPPRIMARYCMD 2991
21.441 SWAPSBYCMD 2991
21.442 SWITCH 2992
21.443 SWITCHCMD 2992
21.444 SWTCHACT 2993
21.445 SYNCHSTS [1...40] 2994
21.446 SYNCPINSTONUMINPUTS 2994
21.447 SYNCSECCMD 2995
21.448 SYNCTIME 2995
21.449 SYNCTIMEBEG 2996
21.450 SYNCTIMEEND 2996
21.451 System Template 2997

21.1 S
It is not recommended to use step outputs of type S_IEC, N_IEC, or R_IEC with destination
parameters that are inputs to flip-flops or other bistable, monostable blocks, or logic
configurations. Examples are OPCMD[0..2] of DEVCTL and S and R of LOGIC:RS. Although these
configurations are technically supported and show a predicatable behavior, the resulting behavior
may be non-intuitive and confusing to operators (example: using an N_IEC output on OPCMD[1]
will result in OP-behavior similar to what would be expected from an S_IEC output if directly
controlling a parameter such as OP). Therefore, this practice is not considered a good engineering
practice.

- 2738 -
Chapter 21 - Sxxxx Parameters

Specific to Block(s) RS, SR


Description S input value
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

21.2 S1

Specific to Block(s) PIDER


Description Switch 1 - Specifies state of the tracking control switch.
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related Parameters RETRYSCURRRETRYOPT, RETRYSTOTAL, TRFB.
Remarks

Specific to AICHANNEL (PM I/O)


Block(s)
Description Status. Shows the current status of the Smart Transmitter associated with this
Smart Transmitter Interface (STI) point.
Data Type String
Range N/A, Blank
Default Null
Config Load No
Active No
Loadable

- 2739 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence IOP
Related
Parameters
Remarks This parameter is only exposed, if ASSOCIOPTYP is STI-MV. However, it does not
appear on the block form in Control Builder. Transmitter status includes the
following:
l Transmitter scratch pads 1, 2, 3 and 4,
l Detailed transmitter status
l List of parameters whose values are not the same in both the STI database
and the Smart Transmitter's database. (Parameters are mismatched.)

21.3 SAFEOP

Specific to RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Safe Output (OP) Value (in Percent)
Data Type 64-Bit Real Number
Range NaN, or OPEXLOLM to OPEXHILM
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related
Parameters
Remarks NaN causes the last good value of OP to be used.

Specific to DEVCTL, SOLENOID, VALVEDAMPER


Block(s)
Description Safe Output State
Data Type Enumeration GENSTATE
Range DEVCTL, VALVEDAMPER: S0(4): State0, State1, State2 S1(5): State1, State0, State2
S2(6): State2, State0, State1 SOLENOID: S0(4): State0, State1, State2 S1(5): State1,
State0, State2
Default S0(4)
Config Load Yes
Active No
Loadable

- 2740 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related GOP, GPV, GOPREQ, HOLDOPT, OI[0..2], OP, DEVCTL: DIMODEDIPVMAP
Parameters OPCMD[0..2], OPREQ, RESTARTOPT, [0..15]NUMDOUTS, NUMSTATES
SEALOPT, SI, STARTOPT, STOPOPT.
Remarks DEVCTL:
l Illegal if NUMDOUTS = 0.
l SAFEOP may not be assigned to a Momentary State.
l S2 is illegal if NUMSTATES = 2.

21.4 SAFEOPALM.FL

Specific to Block(s) GRPCAPRBK


Description Safe output alarm Flag
Data Type Boolean
Range ON OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters SAFEOPALM.PR SAFEOPALM.SV
Remarks Indicates current Alarm state

21.5 SAFEOPALM.PR

Specific to Block(s) GRPCAPRBK


Description Safe output alarm Priority
Data Type Enumeration
Range NONE JOURNAL LOW HIGH URGENT
Default LOW
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters SAFEOPALM.FL SAFEOPALM.SV
Remarks Priority for alarm

- 2741 -
Chapter 21 - Sxxxx Parameters

21.6 SAFEOPALM.SV

Specific to Block(s) GRPCAPRBK


Description Safe output alarm Severity
Data Type 16-Bit Integer
Range 0-15
Default 0
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters SAFEOPALM.FL SAFEOPALM.PR
Remarks Severity for alarm.

21.7 SAFEOPCMD

Specific to Block(s) PosProp, PidPosProp


Description Safe Output (OP) Command.
Data Type Enumeration PULSECMD
Range Idle (0) Raise (1) Lower (2)
Default Idle (0)
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters PUBMETHODPULSECMD
Remarks

21.8 SAFEOPTRIGFL

Specific to Block GRPCAPRBK


(s)
Description Safe Output triggered flag.
Data Type Boolean
Range ON OFF
Default OFF
Config Load NO
Active Loadable No

- 2742 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This flag indicates that the safe output of the block is triggered due to any of
the following.
1. Load set point input status is bad
2. Equipment ON/ OFF status is bad for all the equipments.

21.9 SAFEOUTPUT

Specific to Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Output Safe State - Selects safe state of the associated Output. When target is
reached the output is set to this state.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Affects Channels 6-7 only.

Specific to Series C PICHANNEL


Block(s)
Description Output Safe State.
Data Type BOOLEAN
Range OFF (0) ON (1)
Default OFF (0)
Config Load Yes
Active No
Loadable

- 2743 -
Chapter 21 - Sxxxx Parameters

Access Lock AppDevOnly


Residence IOM
Related SO
Parameters
Remarks SAFEOUTPUT determines the fast cutoff channel output state when the counter
value meets or exceeds the target value.
l OFF indicates the safe state of the output screw is to be de-energized.
l ON indicates the safe state of the output screw is to be energized.
SAFEOUTPUT is also applied during controller failure, loss of communications, or
inactivation of the IO module function block.

21.10 SAFEOUTPUT[6..7]

Specific to Pulse Input IOM


Block(s)
Description Output Safe State - Selects safe state of the associated Output. When target is
reached the output is set to this state.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Affects Channels 6-7 only.

21.11 SAFEREDTAG

Specific to Block DEVCTL All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,
(s) VALVEDAMPER
Description Safe State Before RedTag - Requires that Output (OP) be Safe before RedTag
may be set.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No

- 2744 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related GOP, OP, REDTAG, SAFEOP.
Parameters
Remarks DEVCTL: Illegal if NUMDOUTS= 0.

21.12 SAFESTATE[0..numChans-1]

Specific to DOM
Block(s)
Description Safe State - Specifies a safe output state to be assumed in the event of a controller
failure or loss of communication between the controller and IOM.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related FAILSTATE[0..numChans-1]
Parameters
Remarks FAILSTATE must be enabled in order to configure and use the SAFESTATE. If the
IOM device itself fails, the output value is not deterministic.

21.13 SAFINTER.FL

Specific to Block(s) PROFCONOUT


Description SAFINTER FL
Data Type BOOL
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence CEE
Related Parameters
Remarks SAFINTER FL

- 2745 -
Chapter 21 - Sxxxx Parameters

21.14 SAMPLERATE

Specific to AIM, AOM (Note that although a part of the configuration assembly, SAMPLERATE
Block(s) is not used for output modules.)
Description Sample Rate (msec) - Defines the input module sampling period.
Data Type 32-Bit Integer
Range s
Default 25 msec, with the following exceptions: 50 msec for Thermocouple and RTD AIM
250 msec for Non-Isolated (high-density) AIM
Config Load No
Active No
Loadable
Access Lock AIM: Application Developer AOM: ViewOnly
Residence CEE
Related SIPTYPE[0..numChans-1]
Parameters
Remarks The parameter is not loaded, but appears on the AIM configuration form for
informational purposes.

21.15 SAMPLESKEW

Specific to Block(s) FIM, FIM4


Description Sample Skew
Data Type Enumeration
Range 0 SKEW
1 NOSKEW
Default SKEW (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters
Remarks

- 2746 -
Chapter 21 - Sxxxx Parameters

21.16 SAVEDELAY1

Specific to RETENTIONTRIG
Block(s)
Description Retention Save Delay(m)
Data Type FLOAT64
Range >= 0.0
Default 10.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PWRGOOD1
Parameters
Remarks Delay in minutes before triggering save of retention data the first time after external
power is lost as indicated by a change in the value of parameter PWRGOOD1.

21.17 SAVEDELAY2

Specific to RETENTIONTRIG
Block(s)
Description Retention Save Delay(m)
Data Type FLOAT64
Exposure In / Out
Range >= 0.0
Default 10.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related PWRGOOD2
Parameters
Remarks Delay in minutes before triggering save of retention data the first time after external
power is lost as indicated by a change in the value of parameter PWRGOOD2.

- 2747 -
Chapter 21 - Sxxxx Parameters

21.18 SCAADVCODE1

Specific to Series C AICHANNEL


Block(s)

Description Advanced Code 1

Data Type UINT8

Exposure OUTPUT

Range N/A

Default N/A

Config NO
Load

Access View Only


Lock

Residence IOM

Related N/A
Parameters

Remarks This parameter holds the advanced internal code when the IOM reports an SCA device
fault soft failure. This code will be used by Honeywell Personnel for additional diagnosis.
This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal No
Only

- 2748 -
Chapter 21 - Sxxxx Parameters

21.19 SCAADVCODE2

Specific to Series C AICHANNEL


Block(s)

Description Advanced Code 2

Data Type UINT8

Exposure OUTPUT

Range N/A

Default N/A

Config NO
Load

Access View Only


Lock

Residence IOM

Related N/A
Parameters

Remarks This parameter holds the advanced internal code when the IOM reports an SCA device
fault soft failure. This code will be used by Honeywell Personnel for additional diagnosis.
This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal No
Only

- 2749 -
Chapter 21 - Sxxxx Parameters

21.20 SCACOMCOUNT

Specific to Series C AICHANNEL


Block(s)

Description Communication Count

Data Type UINT16

Exposure OUTPUT

Range N/A

Default 0

Config NO
Load

Access View Only


Lock

Residence IOM

Related RESETSTAT
Parameters

Remarks This parameter provides a count that represents a statistic about the communication path
between the IO module and the SCA device. It is not unusual to have this count be non-
zero.
RESETSTAT button resets this parameter to its default value.
This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal No
Only

- 2750 -
Chapter 21 - Sxxxx Parameters

21.21 SCACOMSTS

Specific to Block(s) Series C AICHANNEL

Description SCA device Communication Status

Data Type ENUM

Exposure OUTPUT

Range 0 OK IO Module communication with the SCA device is good.

1 No The SCA device was found to be non-responsive (possibly due


Response faulty wiring between the IO module and the SCA device or SCA
device is missing or there is an unusual amount of noise in the
path between the IO module and the SCA device).

2 IOM As viewed by the IO Module: The communication between the


Detected IO module and the SCA device is experiencing some errors that
Errors may be due to faulty wiring or presence of noise in the
communications path.

3 Device As viewed by the SCA device: The communication between the


Detected IO module and the SCA device is experiencing some errors that
Errors may be due to faulty wiring or presence of noise in the
communications path.

4 Device As viewed by both the IO Module and the SCA device: The
and IOM communication between the IO module and the SCA device is
Detected experiencing some errors that may be due to faulty wiring or
Errors presence or noise in the communications path.

Default OK

Config Load NO

Access Lock View Only

Residence IOM

Related Parameters SCALASTCOMCODE, RESETSTAT

Remarks RESETSTAT button resets this parameter to its default value.


This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

21.22 SCADEVID

- 2751 -
Chapter 21 - Sxxxx Parameters

Specific to Block(s) Series C AICHANNEL

Description Serial Number

Data Type UINT32

Exposure OUTPUT

Range N/A

Default N/A

Config Load No

View Only.

Residence IOM

Related Parameters N/A

Remarks SCA Device Id number.


This parameter is only applicable when the channel has the following attributes:
·        The module type is UIO-2 and
·        The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

21.23 SCADEVMFG

Specific to Block(s) Series C AICHANNEL

Description Manufacturer

Data Type ENUM

Exposure OUTPUT

Range N/A

Default N/A

Config Load NO

Access Lock View Only

Residence IOM

Related Parameters N/A

Remarks SCA Device Manufacturer name. This will always show Honeywell.
This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

- 2752 -
Chapter 21 - Sxxxx Parameters

21.24 SCADEVREV

Specific to Block Series C AICHANNEL


(s)

Description Device Revision

Data Type UINT8

Exposure OUTPUT

Range N/A

Default N/A

Config Load NO

Access Lock View Only

Residence IOM

Related NA
Parameters

Remarks SCA Device Revision. This parameter is only applicable when the channel has the
following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

21.25 SCADEVTYPE

Specific to Block(s) Series C AICHANNEL

Description Type

Data Type UINT16

Exposure OUTPUT

Range N/A

Default N/A

Config Load NO

Access Lock View Only

Residence IOM

Related Parameters N/A

Remarks SCA Device type.


This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

- 2753 -
Chapter 21 - Sxxxx Parameters

21.26 SCADEVTYPENAME

Specific to Block(s) Series C AICHANNEL

Description Type Name

Data Type ENUM

Exposure OUTPUT

Range N/A

Default Any Device

Config Load NO

Access Lock View Only

Residence IOM

Related Parameters N/A

Remarks This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

21.27 SCAHWREV

Specific to Block(s) Series C AICHANNEL

Description Hardware Revision

Data Type UINT8

Exposure OUTPUT

Range N/A

Default N/A

Config Load NO

Access Lock View Only

Residence IOM

Related Parameters N/A

Remarks SCA device hardware revision.


This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

- 2754 -
Chapter 21 - Sxxxx Parameters

21.28 SCALASTCOMCODE

Specific to Series C AICHANNEL


Block(s)

Description Last Communication Code

Data Type UINT8

Exposure OUTPUT

Range N/A

Default 0

Config NO
Load

Access View Only


Lock

Residence IOM

Related SCACOMSTS, RESETSTAT


Parameters

Remarks This parameter holds the last internal communication code from the IO module to the SCA
Device prior to a communication disruption when indicated by the SCACOMSTS
parameter.
RESETSTAT button resets this parameter to its default value.
This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal No
Only

- 2755 -
Chapter 21 - Sxxxx Parameters

21.29 SCAREQCODE

Specific to Series C AICHANNEL


Block(s)

Description Request Code

Data Type UINT8

Exposure OUTPUT

Range N/A

Default 0

Config Load NO

Access Lock View Only

Residence IOM

Related SCARESPCODE, RESETSTAT


Parameters

Remarks This parameter holds the current internal communication code from the IO module to the
SCA Device prior to a communication disruption.
RESETSTAT button resets this parameter to its default value.
This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal No
Only

- 2756 -
Chapter 21 - Sxxxx Parameters

21.30 SCARESPCODE

Specific to Series C AICHANNEL


Block(s)

Description Response Code

Data Type UINT8

Exposure OUTPUT

Range N/A

Default 0

Config Load NO

Access Lock View Only

Residence IOM

Related SCAREQCODE, RESETSTAT


Parameters

Remarks This parameter holds the current internal communication code from the SCA device to
the IO module prior to a communication disruption.
RESETSTAT button resets this parameter to its default value.
This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal No
Only

21.31 SCASWREV

Specific to Block(s) Series C AICHANNEL

Description Software Revision

Data Type UINT8

Exposure OUTPUT

Range N/A

Default N/A

Config Load NO

Access Lock View Only

Residence IOM

Related Parameters N/A

Remarks SCA Device software revision.


This parameter is only applicable when the channel has the following attributes:
l The module type is UIO-2 and
l The sensor type is NOT 1_5_V or 0_5_V

Internal Only No

- 2757 -
Chapter 21 - Sxxxx Parameters

21.32 SC.BYPPERM

Specific to Block(s) Step


Description Step Stop Condition Bypass Permit
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters SC.BYPREQ, SC.FL.
Remarks When On, SC.FL is set according to SC.BYPREQ.

21.33 SC.BYPREQ

Specific to Block(s) Step


Description Step Stop Condition Bypass Request
Data Type Enumeration CSCOBYPREQ
Range ToOff (0) ToOn (1) None (2)
Default None (2)
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters SC.BYPPERM, SC.FL.
Remarks See SC.BYPPERM for additional information.

21.34 SC.CONFIGCODE

Specific to Step
Block(s)
Description Step Stop Condition Configuration Code
Data Type Enumeration CSCOCONFIGCODECOND
Range None (0) Ok (1) UnknownError (2) ImplicitConv (3) LossOfPrecsn (4) UnexpctEnd (5)
UnexpctComma (6) ColonWoQMark (7) FctNotMltArg (8) ClosParenExp (9)
OperandExp (10) MissingArg (11) OperatorExp (12) ColonExp (13) TypeMismatch
(14) TypeNotSupp (15) SyntaxError (16) ExprTooCmplx (17) NotEPcodeMe (18)
NotEDataStak (19) UnsuppFeatur (20) ExprTooLong (21) DivideByZero (22)
UnknownToken (23) UnexpTokenOS (24) UnknownFunc (25) UnexpOCExpr2 (26)
UnexpOCExpr3 (27) ZeroArgument (28) UnexpToken (29) InvalResult (30)

- 2758 -
Chapter 21 - Sxxxx Parameters

InvalTokenTb (31) IntegerExp (32) DoubleExp (33) MissedImpl (34) UnicodeConv


(35) ConstExprRem (36) DuplExprRem (37) ExtUse38 (38) ExtUse39 (39) ExtUse40
(40) ExtUse41 (41) ExtUse42 (42) ExtUse43 (43) ExtUse44 (44) ExtUse45 (45)
ExtUse46 (46) ExtUse47 (47) ExtUse48 (48) ExtUse49 (49) ExtUse50 (50)
UnSupConType (51) UnExpClsParn (52) CantAssRVal (53) UnExpArrOpen (54)
ArrClsExpect (55) ArrOpnExpect (56) ArrIndxError (57) StringExpect (58)
InvalidRefer (59) TooManyConnS (60) CantConvInpt (61)
Default None (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related
Parameters
Remarks See SC.CONFIGSTS for additional information.

21.35 SC.CONFIGDESC

Specific to Block(s) Step


Description Step Stop Condition Configuration Description
Data Type String
Range Maximum of 39 characters.
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See SC.CONFIGSTS for additional information.

21.36 SC.CONFIGSTS

Specific to Step
Block(s)
Description Step Stop Condition Configuration Status
Data Type Enumeration CSCOCONFIGSTS
Range Ok (0) Information (1) Warning (2) SevereWarn (3) Error (4) SevereError (5)
Default Ok (0)
Config Load No

- 2759 -
Chapter 21 - Sxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SC.CONFIGCODE, SC.CONFIGDESC.
Parameters
Remarks Stop input condition configuration status parameters SC.CONFIGSTS,
SC.CONFIGCODE, and SC.CONFIGDESC are set on SCM STATE transition from
Inactive to Validated.

21.37 SC.DESC

Specific to Block(s) Step/Transition


Description Step Stop Condition Description
Data Type String
Range String Length: 23 characters
Default Null String
Config Load Yes
Active Loadable Yes
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

21.38 SC.EXECCODE

Specific to Step
Block(s)
Description Step Stop Condition Execution Code
Data Type Enumeration CSCOEXECCODE
Range None (0) ConfigError (1) ExprEvalFail (2) StoreFailed (3) CommError (4)
StoreWarning (5) InternalErr (6) CtrlReqErr (7) DataTypeErr (8) StorePending (9)
Default None (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks See SC.EXECSTS for additional information.

- 2760 -
Chapter 21 - Sxxxx Parameters

21.39 SC.EXECDESC

Specific to Block(s) Step


Description Step Stop Condition Execution Code Descriptor
Data Type String
Range Maximum of 39 characters.
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks See SC.EXECSTS for additional information.

21.40 SC.EXECSTS

Specific to Step
Block(s)
Description Step Stop Condition Execution Status
Data Type Enumeration CSCOEXECSTS
Range Ok (0) Bypass (1) Info (2) Warning (3) Fail (4) Error (5) OkPaused (6) BypassPaused
(7) InfoPaused (8) WarnPaused (9) FailPaused (10) ErrorPaused (11)
Default Ok (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SC.EXECCODE, SC.EXECDESC.
Parameters
Remarks Step Stop Condition execution status parameters SC.EXECSTS, SC.EXECCODE,
and SC.EXECDESC are updated when the step is in the Sequential Control
Module's (SCM) current scope of execution.

21.41 SC.EXPR

Specific to Block(s) Step


Description Step Stop Condition Expression
Data Type String
Range String Length: 255 characters

- 2761 -
Chapter 21 - Sxxxx Parameters

Default Null String


Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related Parameters
Remarks

21.42 SC.EXPRPCODE

Specific to Block(s) Step


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

21.43 SC.FL

Specific to Block(s) Step


Description Step Stop Condition Status Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2762 -
Chapter 21 - Sxxxx Parameters

21.44 SC.INVOKFL

Specific to Block Step


(s)
Description Step Stop Condition Invoke Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related SC.FL
Parameters
Remarks Provides the status of the step's stop condition at the time the stop handler
was invoked.

21.45 SC.OPT

Specific to Block(s) Step


Description Step Stop Condition Option
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence CEE
Related Parameters
Remarks SC.OPT must be set to On, to enable the Step Stop Condition.

21.46 SCALARTAGREADS

Specific to Block PB_EIP, CEEC300, CEEUOC


(s)
Description Scalar Tag Reads
Data Type UINT16
Range 0-2325
Default 0

- 2763 -
Chapter 21 - Sxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related -
Parameters
Remarks Number of Scalar Tag Reads configured through this EIM, initiated from one
or more C300’s.

21.47 SCALEMOTION[1..24]

Specific to Block QIPACTERM


Description Scale Motion
Data Type Boolean
Range Off(0) No Motion
On(1) Motion
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 4 of the Status 1 byte in the input assembly for the
designated position [1-24].

21.48 SCALEMOTION[1..200]

Specific to QIPACCHAN
Block
Description Scale Motion
Data Type Boolean
Range Off(0) No Motion
On(1) Motion
Default Off
Config Load No
Active No
Loadable

- 2764 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This is the value of bit 4 of the Status 1 byte in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

21.49 SCALEPERIOD

Specific to Control Module in ACE


Block(s)
Description The SCALEPERIOD value is used by time dependent blocks contained in a CM with
a PERIOD of None (block process special). In such a case, the block uses the
SCALEPERIOD value instead of the CM period for time dependent calculations. The
SCALEPERIOD value is in units of seconds. For example, the default value would
indicate that the intended period of execution of the block process special CM would
be 1 hour (60 seconds).
Data Type 64-Bit Real Number
Range Greater than 0.0 up to 86400.0 (24 hours)
Default 60
Config Yes
Load
Active No
Loadable
Access Operator
Lock
Residence BPS, PERIOD
Related
Parameters
Remarks A PERIOD of None indicates the CM is executed as a block process special only
when commanded by strategy execution or direct operator intervention. Specifying
a value for SCALEPERIOD does not enforce that the block actually executes at the
specified period. Strategies must be designed to provide the correct period of
execution matching the SCALEPERIOD value. This parameter can be updated just
prior to initiating a block process special execution to more accurately indicate the
period of execution for the block process special. Variations in actual period of
execution may make it difficult or impossible to properly use time dependent blocks
in the CM.

- 2765 -
Chapter 21 - Sxxxx Parameters

21.50 SCALESELECTD[1..4]

Specific to JAGXCHAN
Block(s)
Description Scale selected (weight on local display)
Data Type Boolean
Range Off(0) Scale Not Selected
On(1) Scale Selected
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 5 of the status word in the floating point input assembly for
the designated scale slot [1..4].

21.51 SCANAREA

Specific to CM, CEE, CEEC300, CPM (100 and 200), SCM, IOM, RM, C300, CEEUOC, CEECN100
Block(s)
Description Scan Area
Data Type String
Range Length: 2 characters
Default Null
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence Server/SR
Related Name of the Server Area
Parameters
Remarks

Specific to Block(s) UOC


Description SCAN Area
Data Type STRING
Range N/A
Default 0

- 2766 -
Chapter 21 - Sxxxx Parameters

Config Load Yes


Active Loadable
Access Lock AppDevOnly
Residence SRSCAN
Related Parameters
Remarks

21.52 SCANASSOCDSP

Specific to CM, CEE, CEEC300, CPM (100 and 200), SCM, IOM, RM, C300, CEEUOC, UOC
Block(s)
Description SCAN Associated Display
Data Type String
Range Length: 255 characters
Default Null
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence Server
Related
Parameters
Remarks

Specific to Block(s) UOC


Description SCAN Associated Display
Data Type STRING
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Parameters
Remarks

- 2767 -
Chapter 21 - Sxxxx Parameters

21.53 SCANCTRLLVL

Specific to CM, CEE, CEEC300, CPM (100 and 200), SCM, IOM, RM, C300, CEEUOC, UOC,
Block(s) CEECN100, CN100
Description Server Security Level.
Data Type Integer
Range 0 to 255
Default 200
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence Server
Related
Parameters
Remarks

Specific to Block(s) UOC


Description SCAN Control Level
Data Type INT16
Exposure FACEPLATONLY
Range ±32767
Default 200
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Parameters
Remarks

21.54 SCANEUHI

Specific to CM, CEE, CEEC300, CPM (100 and 200), SCM, IOM, RM, C300, CEEUOC, UOC,
Block(s) CN100
Description Server Engineering Units High.
Data Type String
Range Length: 255 characters.
Default Null String
Config Load
Active Yes
Loadable

- 2768 -
Chapter 21 - Sxxxx Parameters

Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence Server
Related
Parameters
Remarks

Specific to Block(s) UOC


Description SCAN EUHI Parameter
Data Type STRING
Exposure FACEPLATONLY
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Parameters
Remarks

21.55 SCANEULO

Specific to CM, CEE, CEEC300, CPM (100 and 200), SCM, IOM, RM, C300, CEEUOC, UOC,
Block(s) CEECN100
Description Server Engineering Units Low.
Data Type String
Range Length: 255 characters.
Default Null
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence Server
Related
Parameters
Remarks

Specific to Block(s) UOC


Description SCAN EULO Parameter
Data Type STRING
Range N/A

- 2769 -
Chapter 21 - Sxxxx Parameters

Default
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Parameters
Remarks

21.56 SCANFREQ

Specific to Block(s) HRBALG_PIUAI


Description Scan Frequency
Data Type ENUM
Range Offscan Scan60 Scan15 Scan5 Scan1 Scan25 Scan05 Reserve
Default Offscan
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters –
Remarks This parameter represents the enumerations defined in the HRB Algo box.

21.57 SCANGRPDTL

Specific to CM, CEE, CEEC300, CPM (100 and 200), SCM, IOM, RM, C300, CEEUOC, UOC,
Block(s) CN100, CEECN100
Description SCAN Group Detail Page
Data Type String
Range Length: 255 characters.
Default Null String
Config Load Yes
Active Yes
Loadable
Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence Server
Related
Parameters
Remarks

- 2770 -
Chapter 21 - Sxxxx Parameters

Specific to Block(s) UOC


Description SCAN Group Detail Page
Data Type STRING
Range N/A
Default sysDtlUOCa_fp
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Parameters
Remarks

21.58 SCANOVERRUN

Specific to Block(s) TCMI


Description Scan Overrun
Data Type FLOAT64
Range N/A
Default 0.0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

21.59 SCANPNTDTL

Specific to CM, CEE, CEEC300, CPM (100 and 200), SCM, IOM, RM, C300, CEEUOC, UOC,
Block(s) CN100, CEECN100
Description SCAN Point Detail Page
Data Type String
Range Length: 255 characters
Default Null
Config Load Yes
Active Yes
Loadable

- 2771 -
Chapter 21 - Sxxxx Parameters

Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence Server
Related
Parameters
Remarks

Specific to UOC
Block(s)
Description SCAN Point Detail Page
Data Type STRING
Range N/A
Default sysDtlUOCa
Config Load Yes
Active
Loadable
Access Lock Application Developer RM only: Requests to read or store to any RM parameter
must come from the Supervisory platform (through Control Builder or Server).
Residence SCAN
Related
Parameters
Remarks

21.60 SCANRATE

Specific to All PM I/O Modules


Block(s)
Description Scan Rate. Lets users configure how often periodic process data is collected from
the I/O Modules and published to the controller.
Data Type Enumeration
Range 100 100MS Process data scanned
once every 100
milliseconds. (See note in
Remarks.)
200 200MS Process data scanned
once every 200
milliseconds.
250 250MS Process data scanned
once every 250
milliseconds.
500 500MS Process data scanned
once every 500
milliseconds.
1000 1S Process data scanned
once every second.
2000 2S Process data scanned
once every 2 seconds.

- 2772 -
Chapter 21 - Sxxxx Parameters

Default 250MS
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence IOLINK
Related
Parameters
Remarks 100 ms selection is invalid and cannot be chosen for AO8, AO16, and AO16HART
IOMs. To ensure fresh I/O data in the associated Control Module (CM), configure
the IOM scan rate to be twice the execution period of the CM. For example, if the
CM execution period is set to 1S, set the IOM scan rate to 500ms.

Specific to Series C I/O AI-HART, AI-LLAI, AI-LLMUX, DI-24, DI-HV, DI-SOE, UIO
Block(s)
Description Scan Rate. Lets users configure how often periodic process data is collected from
the I/O Modules) and published to the controller.
Data Type Enumeration
Range 1 Priority_IOM Process data scanned at the same rate
as internal CEE SCANRATE. See
Remarks.
200 200MS Process data scanned once every 200
milliseconds.
250 250MS Process data scanned once every 250
milliseconds.
500 500MS Process data scanned once every 500
milliseconds.
1000 1S Process data scanned once every
second.
2000 2S Process data scanned once every 2
seconds.
Default 1S
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOLINK
Related
Parameters
Remarks This parameter determines how often the periodic process data is collected from
the IOMs and published to the CPM.

NOTE Priority_IOM scan is not supported for the AI-LLMUX and the AI-
LLAI modules.

- 2773 -
Chapter 21 - Sxxxx Parameters

Specific to Series C I/O AO-HART and DO-24B


Block(s)
Description Scan Rate. Lets users configure how often periodic process data is collected from
the I/O Modules) and published to the controller.
Data Type Enumeration
Range 1 Priority_IOM Process data scanned at the same
rate as internal CEE SCANRATE
1000 1S Process data scanned once every
second.
Default 1S
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence IOLINK
Related
Parameters
Remarks

Specific to UIO
Block(s)

Description IOM Scan Rate


Data Type ENUM
Range
25 25_ms

50 50_ms

100 100_ms

200 200_ms

500 500_ms

1000 1S

2000 2S

Default 50_ms
Config Load Yes
Active No
Loadable

Access Lock AppDevOnly


Residence CEE
Related N/A
Parameters

Remarks The scan rate parameter determines how often periodic process data is collected from
the IOMs and published to the CPM.

- 2774 -
Chapter 21 - Sxxxx Parameters

Specific to UIO, UAI, DI32-24VDC, DO32-24VDC, DI16-VAC, DO08-VAC, DI16-DRYCT, DO08-RELAY,


Block(s) AO04, AI16-100MS, AO08, DI16-VACDC
Description IOM Scan Rate
Data Type ENUM
Range
25 25_ms

50 50_ms

100 100_ms

200 200_ms

500 500_ms

1000 1S

2000 2S

Default 50_ms
Config Yes
Load

Active
Loadable

Access AppDevOnly
Lock

Residence IOM Block


Related N/A
Parameters

Remarks The scan rate parameter determines how often periodic process data is collected from
the IOMs and published to the CPM. Note that some scan rates may not be supported for
some module types and will be masked out in the configuration forms. For example UAI
only supports scan rates equal to 500ms or greater and default scan rate is 500ms.

21.61 SCANRATE(UOC)

Specific to UIO
Block(s)

Description IOM Scan Rate


Data Type ENUM
Range
25 25_ms

50 50_ms

100 100_ms

200 200_ms

500 500_ms

1000 1S

2000 2S

- 2775 -
Chapter 21 - Sxxxx Parameters

Default 50_ms
Config Load Yes
Active No
Loadable

Access Lock AppDevOnly


Residence CEE
Related N/A
Parameters

Remarks The scan rate parameter determines how often periodic process data is collected from
the IOMs and published to the CPM.

21.62 SCANRATE [1...40]

Specific to C200 IOLINK, C300 IOLINK, CN100 IOLINK


Block(s)
Description I/O Link Scanning Rate
Data Type Enumeration
Range Varies for given IOM - See Related Parameter for details.
Default Varies for given IOM - See Related Parameter for details.
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM, C300 IOLINK
Related SCANRATE
Parameters
Remarks The scan rate parameter determines how often periodic process data is collected
from the IOPs/IOMs and published to the controllers. The index of this array
corresponds to the the IOP/IOM number.

21.63 SCHDOPTIMIZE

Specific to Block(s) FIM, FIM4


Description Link Schedule Optimization
Data Type Enumeration
Range 0 OPT
1 OPT_NOFORCE
2 NO_OPT
Default OPT (0)
Config Load Yes
Active Loadable No

- 2776 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence SR
Related Parameters
Remarks

21.64 SCHEDCYCLE[0..120]

Specific to Block(s) SCM


Description Scheduled Cycle
Data Type Boolean
Range ON/OFF
Default OFF
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters
Remarks

21.65 SCINCONNHNDL[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

- 2777 -
Chapter 21 - Sxxxx Parameters

21.66 SCINCONNNAV[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

21.67 SCINCONNPRM[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable NO
Access Lock
Residence
Related Parameters
Remarks

21.68 SCINCONNSTRVAL[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO

- 2778 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence
Related Parameters
Remarks

21.69 SCINCONNVAL[1..6]

Specific to Block(s) Step


Description This is an Internal Parameter for system use only.
Data Type
Range
Default
Config Load NO
Active Loadable NO
Access Lock ViewOnly
Residence
Related Parameters
Remarks

21.70 SCMASTEP[1..15]

Specific to Block(s) CM
Description Monitored Sequential Control Module (SCM) Active Step
Data Type Integer
Range 0 to 32,767
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters SCMOPT, SCMMODE, SCMSTATE.
Remarks Invalid if SCMOPT ≠ Fixed.

- 2779 -
Chapter 21 - Sxxxx Parameters

21.71 SCMID

Specific to CM
Block(s)
Description Sequential Control Module Identifier
Data Type Entity Id (Independent Block Code)
Range N/A
Default Null String
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SCMOPT
Parameters
Remarks Identifies the SCM controlling the Control Module contained devices. Applicable
only when SCMOPT is equal to Fixed.

21.72 SCMMODE

Specific to Block(s) CM
Description Monitored Sequential Control Module (SCM) Mode
Data Type Enumeration of SCMMODE
Range None (0) Auto (1) SemiAuto (2) SnglStep (3) Manual (4) Normal (5)
Default Manual (4)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters SCMOPT, SCHEDCYCLE[0..120], SCMASTEP[1..15], SCMSTATE.
Remarks SCMMODE is invalid if SCMOPT is not Fixed.

21.73 SCMMONITOR

Specific to Block(s) SCM


Description This is an internal parameter for system use only.
Data Type
Range
Default

- 2780 -
Chapter 21 - Sxxxx Parameters

Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

21.74 SCMMONSRC

Specific to CM
Block(s)
Description This is an internal parameter for system use only.
Data Type
Range
Default
Config
Load
Active No
Loadable
Access Lock
Residence
Related
Parameters
Remarks Depending on the order in which blocks are loaded, the following status may be
returned for this parameter: “Referenced FB Not Found”. This indicates that a
function block was referenced which has not yet been loaded to the controller.
When this happens, no action is required except to load the referenced block before
putting the strategy on control.

21.75 SCMNAME

Specific to CM
Block(s)
Description Name of associated Sequential Control Module (SCM).
Data Type String
Range String Length: 16 characters
Default Null String
Config Yes
Load
Active No
Loadable

- 2781 -
Chapter 21 - Sxxxx Parameters

Access Lock Application Developer


Residence SR
Related SCHEDCYCLE[0..120] SCMASTEP[1..15] SCMID, SCMMODE, SCMSTATE,
Parameters
Remarks The block designated by SCMNAME is the SCM associated with the CM. Parameters
SCMASTEP[1..15], SCMID, SCMMODE and SCMSTATE reflect the status of this
SCM. SCM Name is configurable on CM configuration form. It identifies the related
SCM and it cannot be changed on-line. This entry is only required and possible if
SCMOPT selection is Fixed.

21.76 SCMOPT

Specific to CM
Block(s)
Description Sequential Control Module (SCM) Option
Data Type Enumeration SCMOPT
Range 0 None No special device support
enabled
1 Fixed Enable support for step
output types Set and
NotStored
2 Dynamic Not implemented, do not
use
3 Common Enable support for step
output types N_IEC , R_IEC
and S_IEC. Also enables
common device
functionality for this
Control Module.
Default None (0)
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence CEE
Related SCMID MODEATTRREF
Parameters
Remarks Used for selection of additional device functionality if blocks in the Control Module
are controlled by steps of SCMs or RCMs A value of Fixed is only supported for a
limited set of standard library blocks residing in CEE based controllers (C200, C300,
ACE) and their simulations. For a list of blocks see parameter OPTYPE A value of
Common is only supported for blocks residing in CEE based controllers (C200, C300,
ACE) and their simulations, if these blocks have at least one writeable parameter of
data type BOOLEAN. Common is not supported on Experion PKS Releases 301.1
and earlier.

- 2782 -
Chapter 21 - Sxxxx Parameters

21.77 SCMSTATE

Specific to CM
Block(s)
Description Monitored Sequential Control Module (SCM) State
Data Type Enumeration SCMSTATE
Range Loading (0) Loaded (1) Inactive (2) Validated (3) Running (4) Complete (5) Checking
(6) Idle (7) Interrupting (8) Interrupted (9) Restarting (10) Restarted (11) Holding
(12) Held (13) Stopping (14) Stopped (15) Aborting (16) Aborted (17) CommErr (18)
Default Null (2)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SCMOPT, SCMMODE, SCHEDCYCLE[0..120],
Parameters
Remarks Invalid if SCMOPT ≠ Fixed.

21.78 SCNUMSRCCONN

Specific to Step Block


Block(s)
Description Number of Source Connections for Stop Condition expression. Represents number
of source references in the Step-specific Stop Condition expression.
Data Type Integer32
Range 0 to 6
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence ACE, C200, SIM_C200
Related SPCODESIZE
Parameters
Remarks

- 2783 -
Chapter 21 - Sxxxx Parameters

21.79 SCRIPTOR

Specific to Block CM, CEE, CEEC300, CPM (100 and 200), SCM, IOM, RM, C300, CEEUOC, UOC,
(s) CN100, CEECN100
Description SERVER SCRIPTOR
Data Type Blob
Range
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence Server
Related
Parameters
Remarks SERVER SCRIPTOR

21.80 SCSRC[1..6]

Specific to Block(s) Step


Description This is an internal parameter for system use only.
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

21.81 SDENUMTEXT

Specific to Block(s) Type Convert, Push.


Description Enumeration Text
Data Type String
Range Maximum 12 characters
Default SDENUM0 to SDENUM63
Config Load Yes
Active Loadable No

- 2784 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence SR
Related Parameters
Remarks

21.82 SEALOPT

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Seal-in Option.
Data Type Enumeration ENABLE
Range Disable (0) Enable (1)
Default Disable (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related GOP, GOPFINAL, OP, OPFINAL, SAFEOP, DEVCTL Only: MOMSTATE, NUMDOUTS,
Parameters, NUMDINPUTS.
Remarks Function block must be InActive to change SEALOPT. Illegal if Command Disagree
is not configured [All CMDDISALM.TM[x] = 0]. DEVCTL Only:
l Illegal if MOMSTATE is not NONE.
l Illegal if NUMDOUTS = 0 or NUMDINPUTS = 0.

21.83 SECCANTTALKTOPRIONUCN

Specific to Block(s) TCMI


Description Secondary cannot talk to Primary on UCN
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

- 2785 -
Chapter 21 - Sxxxx Parameters

21.84 SECBLOCKNAME [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description IOP Block Name. Indicates the corresponding Secondary IOP/IOM Tag. The index
of this array corresponds to the number of the IOP/IOM.
Data Type BlockId
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PRIBLOCKNAME[1...40]
Parameters
Remarks

21.85 SECCHNERRA [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Errors on Channel A. Shows the number
of I/O link channel A errors encountered by the Secondary IOP/IOM, where the
index of this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNERRA
Parameters
Remarks Note that this is the same as the IOMCHAER parameter in a TPS system.

- 2786 -
Chapter 21 - Sxxxx Parameters

21.86 SECCHNERRB [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Errors on Channel B. Shows the number
of I/O link channel B errors encountered by the Secondary IOP/IOM, where the
index of this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNERRB
Parameters
Remarks Note that this is the same as the IOMCHBER parameter in a TPS system.

21.87 SECCHNMNA [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Channel A- Edges. Shows the number of
I/O link channel A missed minus edge transitions encountered by the Secondary
IOP/IOM, where the index of this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNMNA
Parameters
Remarks

- 2787 -
Chapter 21 - Sxxxx Parameters

21.88 SECCHNMNB [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Channel B- Edges. Shows the number of
I/O link channel B missed minus edge transitions encountered by the Secondary
IOP/IOM, where the index of this array corresponds to the number of the IOP/IOM.

Data Type 16-Bit Unsigned Integer


Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNMNB
Parameters
Remarks

21.89 SECCHNPLA [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Channel A+ Edges. Shows the number of
I/O link channel A missed plus edge transitions encountered by the Secondary
IOP/IOM, where the index of this array corresponds to the number of the IOP/IOM.

Data Type 16-Bit Unsigned Integer


Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNPLA
Parameters
Remarks

- 2788 -
Chapter 21 - Sxxxx Parameters

21.90 SECCHNPLB [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Channel B+ Edges. Shows the number of
I/O link channel B missed plus edge transitions encountered by the Secondary
IOP/IOM, where the index of this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNPLB
Parameters
Remarks

21.91 SECCHNSILA [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Silences on Channel A. Shows the
number of I/O link channel A silences encountered by the Secondary IOP/IOM,
where the index of this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks Note that this is the same as the IOMCHASL parameter in a TPS system.

- 2789 -
Chapter 21 - Sxxxx Parameters

21.92 SECCHNSILB [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Silences on Channel B. Shows the
number of I/O link channel B silences encountered by the Secondary IOP/IOM,
where the index of this array corresponds to the number of the IOP/IOM.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks Note that this is the same as the IOMCHBSL parameter in a TPS system.

- 2790 -
Chapter 21 - Sxxxx Parameters

21.93 SECCOMMERR [1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Input/Output Processor (IOP) Last Communication Error. Shows the
last I/O link communication error experienced by the Secondary IOP/IOM, where
the index of the array corresponds to the number of the IOP/IOM.
Data Type Enumeration
Range None (0): No communication error.
InvAlert (1): Invalid Alert - message bit problem.
InvDest (2): Invalid Destination.
InvChCnt (3): Invalid Character Count.
InvSourc (4): Invalid Source.
InvCmd (5): Invalid Command.
CheckSum (6): Data record Checksum Error.
No_Resp (7): No Response.
ChTimOut (8): Channel Time Out.
MsgOvRun (9): Message Overrun.
GapError (10): Message gap is too long.
LpbckErr (11): Loop Back Error.
NTH_O (12): Next Token Holder equals zero.
TknRecov (13): Token Recovery in progress.
RplBufOv (14): Reply Buffer Overflow.
TknTmOut (15): Token Pass Time Out.
IolDrver (16): IOL Driver Error.
--- (17): IOP is not configured.
Default None (0)
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks Note that this is the same as the IOMCOMER parameter in a TPS system.

- 2791 -
Chapter 21 - Sxxxx Parameters

21.94 SECCONNSTS

Specific to Block(s) PCDI_MASTER


Description Secondary Connection Status
Data Type Enumeration
Range 0 Invalid
1 Initial
2 Connecting
3 Connected
4 Failed
Default Initial (1)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

21.95 SECDATAIN

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Seconday Data Input - Brings SECDATA (Secondary Data) parameter from the
Universal Control Network (UCN) Process Manager control point.
Data Type ExtRefStruct
Range N/A
Default N/A
Config No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

- 2792 -
Chapter 21 - Sxxxx Parameters

Specific to REEOUT
Block(s)
Description Seconday Data Input - Fetches SECDATA (Secondary Data) parameter from the
secondary Experion cluster.
Data Type Structure
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

21.96 SECDATAIN.ARWSTS

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Secondary Data Input Anti-Reset Windup Status - Brings the anti-reset windup
status from the Universal Control Network (UCN) Process Manager secondary.
Data Type Enumeration
Range (0) Normal (1) Hi (2) Lo (3) HiLo
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Anti-Reset Windup Status - Fetches the anti-reset windup
status from the secondary Experion cluster
Data Type Enumeration
Range (0) Normal (1) Hi (2) Lo (3) HiLo
Default
Config Load No
Active No
Loadable

- 2793 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence ACE
Related
Parameters
Remarks

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Anti-Reset Windup Status - Reads the anti-reset windup
status that is propagated to a Regulatory Control block from its secondary.
Data Type Enumeration
Range (0) Normal (1) Hi (2) Lo (3) HiLo
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

21.97 SECDATAIN.CASREQ

Specific to Block UCNOUT, HIWAYOUT


(s)
Description Secondary Data Input Cascade Request - Show if the secondary is requesting
a cascade.
Data Type Boolean
Range Off - Cascade is not requested ON - Cascade is requested
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

- 2794 -
Chapter 21 - Sxxxx Parameters

21.98 SECDATAIN.CASSHED

Specific to Block(s) UCNOUT, HIWAYOUT


Description Secondary Data Input Cascade Shed - Shows if the secondary
Data Type Boolean
Range Off - Has not shed On - Has shed
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related Parameters SECDATAIN
Remarks

21.99 SECDATAIN.EUHI

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Engineering Units High - Shows the Engineering Units High
value that is propagated to a Regulatory Control block from its secondary.
Data Type Float64
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Engineering Units High - Shows the Engineering Units High
value that is fetched from the secondary Experion cluster.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable

- 2795 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence ACE
Related SECDATAIN
Parameters
Remarks

21.100 SECDATAIN.EULO

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Secondary Data Input Engineering Units Low - Shows the Engineering Units Low
Limit that corresponds to 0 percent of the scale that is brought from the Universal
Control Network (UCN) Process Manager secondary.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Engineering Units Low - Shows the Engineering Units Low
Limit that corresponds to 0 percent of the scale that is fetched from the secondary
Experion cluster
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

- 2796 -
Chapter 21 - Sxxxx Parameters

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Engineering Units Low - Shows the Engineering Units Low
value that is propagated to a Regulatory Control block from its secondary.
Data Type Float64
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

21.101 SECDATAIN.EUSPAN100

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Secondary Data Input Engineering Units Span - Shows the normalized
Engineering Units span that is equal to (EUHI - EULO) divided by 100, and is
brought from the Universal Control Network (UCN) Process Manager secondary.
Data Type Float64
Range N/A
Default N/A
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

- 2797 -
Chapter 21 - Sxxxx Parameters

21.102 SECDATAIN.HISELECT

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input High Select- Shows the override feedback type (high or low
selector) that is propagated to a Regulatory Control block from its secondary .
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input High Select- Shows the override feedback type (high or low
selector) that is fetched from the secondary Experion cluster .
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

21.103 SECDATAIN.INITREQ

Specific to Block UCNOUT, HIWAYOUT


(s)
Description Secondary Data Input Initialization Request - Shows if the secondary is
requesting initialization.
Data Type Boolean
Range Off - Initialization is not requested On - Initialization is requested
Default N/A

- 2798 -
Chapter 21 - Sxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

21.104 SECDATAIN.INITSTS

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Initialization Status - Reads the initialization status that is
propagated to a Regulatory Control block from its secondary..
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Initialization Status - Reads the initialization status that is
fetched from the secondary Experion cluster
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

- 2799 -
Chapter 21 - Sxxxx Parameters

21.105 SECDATAIN.INITVAL

Specific to Block UCNOUT, HIWAYOUT


(s)
Description Secondary Data Input Initialization Value - Shows the value that is provided
from the secondary.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Initialization Value - Shows the value that is fetched from
the secondary Experion cluster.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Engineering Units Low - Reads initializatrion value that is
propagated to a Regulatory Control block from its secondary.
Data Type Float64
Range
Default
Config Load No
Active No
Loadable

- 2800 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks

21.106 SECDATAIN.LOCALMAN

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Local Manual - Reads the local manual status that is
propagated to a Regulatory Control block from its secondary.
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Local Manual - Reads the local manual status that is
fetched from the secondary Experion cluster
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

- 2801 -
Chapter 21 - Sxxxx Parameters

21.107 SECDATAIN.ONESHOT

Specific to REEOUT
Block(s)
Description Secondary Data Input One Shot - Indicates the one-shot initialization value that is
fetched from the secondary Experion cluster
Data Type 32-Bit Integer
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

21.108 SECDATAIN.ORFBSTS

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Override Feedback Status- Reads the override feedback
status that is propagated to a regulatory control point from its secondary.
Data Type Enumeration
Range (0) Notconnected (1) Selected (2) Notselected
Default Notconnected
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PRIMDATA.[1..8].OROFFSET
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Override Feedback Status- Reads the override feedback
status that is fetched from the secondary Experion cluster
Data Type Enumeration
Range (0) Notconnected (1) Selected (2) Notselected
Default Notconnected

- 2802 -
Chapter 21 - Sxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

21.109 SECDATAIN.ORFBVAL

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Override Feedback Value- Reads the override feedback value
that is propagated to a regulatory control point from its secondary.
Data Type Float64
Range
Default NaN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Override Feedback Value- Reads the override feedback value
that is fetched from the secondary Experion cluster.
Data Type Float64
Range
Default NaN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

- 2803 -
Chapter 21 - Sxxxx Parameters

21.110 SECDATAIN.OROFFSET

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Input Override Offset- Shows the override offset value that is
propagated to a regulatory control point from its secondary.
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Input Override Offset- Shows the override offset value that is
fetched from the secondary Experion cluster
Data Type Boolean
Range (0) False (1) True
Default False
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

21.111 SECDATAIN.PROPOVRD

Specific to All Regulatory Control Blocks


Block(s)
Description Secondary Data Propagation Override - Reads propagation override value that is
propagated to a Regulatory Control block from its secondary.
Data Type Boolean
Range (0) False (1) True
Default

- 2804 -
Chapter 21 - Sxxxx Parameters

Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to REEOUT
Block(s)
Description Secondary Data Propagation Override - Reads propagation override value that is
fetched from the secondary Experion cluster
Data Type Boolean
Range (0) False (1) True
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related
Parameters
Remarks

21.112 SECDATAIN.SECTYPE

Specific to UCNOUT, HIWAYOUT


Block(s)
Description Secondary Data Input Secondary Type - Shows the secondary type that is
configured in the Universal Control Network (UCN) Process Manager control point.
Data Type Enumeration
Range (0) None (1) Spc (2) Ddc
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related SECDATAIN
Parameters
Remarks

- 2805 -
Chapter 21 - Sxxxx Parameters

21.113 SECERRCNT

Specific to Block(s) PCDI_MASTER


Description Secondary connection Error Count
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

21.114 SECERRCODE

Specific to Block(s) PCDI_MASTER


Description Secondary connection's last Error Code
Data Type Enumeration
Range 0 OK
256 Conn Forced
257 Socket Warn
258 Conn Fail
259 Count Exceeded
260 Send Blocking
512 Not Init
513 Socket Err
514 Timeout
515 No Conn
516 Send Fail
517 Msg Size
518 Invalid Buffer
519 Invalid Param
520 Devs Failed
Default Not Init
Config Load No
Active Loadable No

- 2806 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters
Remarks

21.115 SECERRFL

Specific to Block(s) PCDI_MASTER


Description Secondary Error Flag
Data Type Boolean
Range True/False
Default True
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

21.116 SECERRINFO

Specific to Block(s) PCDI_MASTER


Description Secondary additional Error Information
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2807 -
Chapter 21 - Sxxxx Parameters

21.117 SECIFCHNERRA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Errors on Channel A. Shows the number of I/O link
channel A errors encountered by the secondary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNERRA
Parameters
Remarks

21.118 SECIFCHNERRB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Errors on Channel B. Shows the number of I/O link
channel B errors encountered by the secondary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNERRB
Parameters
Remarks

- 2808 -
Chapter 21 - Sxxxx Parameters

21.119 SECIFCHNMNA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Channel A- Edges. Shows the number of I/O link channel
A missed minus edge transitions encountered by the secondary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNMNA
Parameters
Remarks

21.120 SECIFCHNMNB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Channel B- Edges. Shows the number of I/O link channel
B missed minus edge transitions encountered by the secondary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNMNB
Parameters
Remarks

- 2809 -
Chapter 21 - Sxxxx Parameters

21.121 SECIFCHNPLA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Channel A+ Edges. Shows the number of I/O link
channel A missed plus edge transitions encountered by the secondary link
interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNPLA
Parameters
Remarks

21.122 SECIFCHNPLB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Channel B+ Edges. Shows the number of I/O link
channel B missed plus edge transitions encountered by the secondary link
interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related TOTCHNPLB
Parameters
Remarks

- 2810 -
Chapter 21 - Sxxxx Parameters

21.123 SECIFCHNSILA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Silences on Channel A. Shows the number of I/O link
channel A silences encountered by the secondary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

21.124 SECIFCHNSILB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Silences on Channel B. Shows the number of I/O link
channel B silences encountered by the secondary link interface.
Data Type 16-Bit Unsigned Integer
Range N/A
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

- 2811 -
Chapter 21 - Sxxxx Parameters

21.125 SECIFCOMMERR

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Last Communication Error. Shows the last I/O link
communications error experienced by the secondary link interface.
Data Type Enumeration
Range None (0): No communication error.
InvAlert (1): Invalid Alert - message bit problem.
InvDest (2): Invalid Destination.
InvChCnt (3): Invalid Character Count.
InvSourc (4): Invalid Source.
InvCmd (5): Invalid Command.
CheckSum (6): Data record Checksum Error.
No_Resp (7): No Response.
ChTimOut (8): Channel Time Out.
MsgOvRun (9): Message Overrun.
GapError (10): Message gap is too long.
LpbckErr (11): Loop Back Error.
NTH_O (12): Next Token Holder equals zero.
TknRecov (13): Token Recovery in progress.
RplBufOv (14): Reply Buffer Overflow.
TknTmOut (15): Token Pass Time Out.
IolDrver (16): IOL Driver Error.
Default None (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks

- 2812 -
Chapter 21 - Sxxxx Parameters

21.126 SECIFRCVCHN

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary Link Interface Active Receive Channel. Shows the channel that is
actively listening to transmitted messages.
Data Type Enumeration
Range UNKNOWN: No active channel.
CHANNEL_A: Channel A is active.
CHANNEL_B: Channel B is active.
Default UNKNOWN
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related PERIODENUMMASKPERIODSECPERSWAPENB
Parameters
Remarks If the PERSWAPENB parameter is On, the active receive channel toggles between
A and B once a minute.

21.127 SECINITOPT[1..8]

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDER, PIDFF, PID-PL, PosProp,
Block(s) RampSoak, RemCas, RatioBias, RatioCtl, RegCalc, RegSummer, and Switch.
Description Secondary Initialization Option - Indicates if a Regulatory Control function block
should accept or ignore initialization requests, and override feedback data from the
secondary. There is one option parameter for each secondary. (The number of
secondaries depends on the function block type.)
Data Type Enumeration ENBSTATE
Range Disable (0): Ignore initialization and override data
from secondary
Enable (1): Accept initialization and override data
from secondary.
Default Enable (1)
Config Yes
Load
Active No
Loadable

- 2813 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related BACKCALCIN, BACKCALCIN[1..3], BACKCALCIN[1..8]BADOCOPT
Parameters
Remarks If this parameter is set to “Disable” and if the block experiences an IO
communication error with the corresponding secondary, the mode shed behavior
of the block is not affected irrespective of the value set in the BADOCOPT
parameter. Note: This is not applicable to the PIDER block.

21.128 SECINITOPT1

Specific to Block(s) RampSoak


Description
Data Type
Range
Default Checked (X)
Config Load
Active Loadable No
Access Lock
Residence
Related Parameters
Remarks

21.129 SECIP

Specific to Block(s) PCDI_MASTER


Description Secondary IP Address
Data Type String
Range 16
Default 0.0.0.0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks This parameter is only available when redundant peer device types are
configured.

- 2814 -
Chapter 21 - Sxxxx Parameters

21.130 SECIPMON

Specific to Block(s) PCDI_MASTER


Description Secondary IP Address Monitor
Data Type String
Range 16
Default 0.0.0.0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

21.131 SECLASTCONNTIME

Specific to Block(s) PCDI_MASTER


Description Secondary Last Connect Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

21.132 SECLASTDISCONNTIME

Specific to Block(s) PCDI_MASTER


Description Secondary Last Disconnect Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No

- 2815 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters PRIMLASTDISCONNTIME
Remarks

21.133 SECLASTERRTIME

Specific to Block(s) PCDI_MASTER


Description Secondary Last Error Time
Data Type Time
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PRIMLASTERRTIME
Remarks

21.134 SECLOOPDATA

Specific to PCDI_MASTER
Block(s)
Description Secondary Loop Data
Data Type String
Range 40 Characters
Default
Config Yes
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PRIMLOOPDATA
Parameters
Remarks The value for this parameter is only visible during Monitoring mode. For a single
device, this is the actual data value that is changing during diagnostic testing for a
secondary connection. During monitoring, this value will be the result of the
diagnostic testing that occurs and will change. For example, on a diagnostic coil
with the invert LOOPMODE selected, this value will toggle between 1 and 0.

- 2816 -
Chapter 21 - Sxxxx Parameters

21.135 SECMODNAME

Specific to Block(s) EIM, TCMI


Description The name of the secondary module.
Data Type BlockId
Range N/A
Default
Config Load
Active Loadable No
Access Lock APPDEVONLY
Residence SR
Related Parameters MODISREDUN
Remarks Secondary EIM tag name.

Specific to Block(s) C200, C300, BCM, FIM, IOLIM, FTEB, FIM4, EHG, RM and LIOM, UOC,
CN100
Description The name of secondary Module
Data Type BLOCKID
Range N/A
Default N/A
Config Load Yes
Access Lock Application Developer
Residence SR
Related Parameters NAME
Remarks (redundancy parameters, see C300 definition)

21.136 SECNAMESTRG

Specific to Block C300, C200, FIM, IOLIM, FIM4, EHG, LIOM, RM, FTEB, PGM, EHPM, EIM PB_
(s) 61850
Description Secondary Name String - Specifies name of secondary module, if configured
for redundancy.
Data Type String
Range Length: 16 characters
Default Null
Config Load Yes
Active Loadable No

- 2817 -
Chapter 21 - Sxxxx Parameters

Access Lock Application Developer


Residence SR
Related
Parameters
Remarks

Specific to Block(s) C300, BCM, C200, FIM, IOLIM, FIM4, EHG, LIOM, RM and FTEB FBs
Description Secondary Name String – Specifies name of Secondary Module
Data Type STRING
Exposure FACEPLATE
Range Length : 16 Characters
Default NULL
Config Load Yes
Access Lock Application Developer

Specific to Block(s) UOC


Description Secondary Module Name String
Data Type STRING
Exposure FACEPLATONLY
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

21.137 SECNAMESTRING

Specific to Block(s) CPM, RM


Description The name of the secondary module
Data Type String
Range N/A
Default None
Config Load 0
Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters
Remarks

- 2818 -
Chapter 21 - Sxxxx Parameters

21.138 SECNOTSYNED

Specific to Block(s) TCMI


Description Secondary not synched
Data Type BOOLEAN
Range N/A
Default

Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

21.139 SECNUMCONN

Specific to Block(s) PCDI_MASTER


Description Secondary Number of Successful Connects
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters PRIMNUMCONN
Remarks

21.140 SECNUMCONNATMPT

Specific to Block(s) PCDI_MASTER


Description Secondary Number of Connection Attempts
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No

- 2819 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters PRIMNUMCONNATMPT
Remarks

21.141 SECNUMDISCONN

Specific to Block(s) PCDI_MASTER


Description Secondary Number of Disconnects
Data Type 32-Bit Unsigned Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

21.142 SECOND

Specific to Block(s) ACE, CPM, SIMC200, CEEC300, CEEUOC, CEECN100


Description Defines the second component of the Controller's local time.
Data Type 32-Bit Integer
Range 0 to 59
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE, C200, SIMC200, C300(CEEC300) , UOC(CEEUOC), CN100(CEECN100)
Related Parameters DAYLIGHTTIME, TIMEZONE.
Remarks Name of the secondary module if configured for redundancy

- 2820 -
Chapter 21 - Sxxxx Parameters

21.143 SECONDARYSIG

Specific to Block(s) Most Function Blocks


Description Secondary Signature
Data Type String
Range Length: 24 characters
Default Null
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence SR
Related NUMSIGS
Parameters
Remarks Lets you specify the meaning associated with entering the secondary
signature.

Specific to Block(s) UOC


Description Secondary Signature Meaning
Data Type STRING
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Lets you specify the meaning associated with entering the secondary
Parameters signature.
Remarks

21.144 SECOVERLAP[1..24]

Specific to Block QIPACTERM


Description Secondary Overlapped Feed in Progress
Data Type Boolean
Range Off(0) Off
On(1) In Progress
Default 0
Config Load No
Active Loadable No

- 2821 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related
Parameters
Remarks This is the value of bit 15 of the Status 2 word in the input assembly for the
designated position [1-24].

21.145 SECOVERLAP[1..200]

Specific to QIPACCHAN
Block
Description Secondary Overlapped Feed in Progress
Data Type Boolean
Range Off(0) Off
On(1) In Progress
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 15 of the Status 2 word in the input assembly for the
designated channel [1-200] in the QiMPACT cluster.

21.146 SECRCVCHN [1..40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Secondary IOM Active Receive Channel. Shows the channel that is actively
listening to the transmitted messages, where the index of this array corresponds to
the number of the IOP/IOM.
Data Type Enumeration
Range UNKNOWN No active channel.
CHANNEL_A Channel A is active.
CHANNEL_B Channel B is active.
--- IOM is not configured or is not
configured as a redundant pair.
Default UNKNOWN
Config Load No
Active No

- 2822 -
Chapter 21 - Sxxxx Parameters

Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks If the PERSWAPENB parameter is On, the active receive channel toggles between
channel A and B once a minute. Note that this is the same as the IOMRECHN
parameter in a TPS system.

21.147 SECRPTCONNECTIONSTATE

Specific to Block(s) EIM


Description Secondary Report Status
Data Type ENUM
Range NA
Default Not Defined
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

21.148 SECSIGSECLVL

Specific to Block(s) Most Function Blocks


Description Secondary Signer Security Level
Data Type Enumeration
Range VIEWONLY (0) ACKONLY (1) OPER (2) SUPR (3) ENGR (4) MNGR (5)
Default VIEWONLY
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related
Parameters
Remarks Lets you select the minimum security level of the second signature when
required.

- 2823 -
Chapter 21 - Sxxxx Parameters

Specific to Block(s) UOC


Description Sec Signer Security Level
Data Type ENUM
Range N/A
Default SUPV
Config Load Yes
Active Loadable
Access Lock AppDevOnly
Residence SCAN
Related Parameters
Remarks

21.149 SECTCP

Specific to PCDI_MASTER
Block(s)
Description Secondary TCP Port
Data Type 16-Bit Unsigned Integer
Range 16
Default 502
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks This parameter is only available when redundant peer device types are configured.
An error message appears, if an invalid number, such as zero, is entered. A zero
value cannot be stored to the database.

21.150 SECTCPMON

Specific to Block(s) PCDI_MASTER


Description Secondary TCP Port Monitor
Data Type 16-Bit Unsigned integer
Range
Default 502
Config Load No
Active Loadable No

- 2824 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters PRIMTCPMON
Remarks

21.151 SECTMPNAME

Specific to Block(s) Primary C200, FIM, IOLIM, EHG, FIM4, LIOM, RM, FTEB, C300, RM, PGM,
EHPM, UOC
Description The name of the secondary template
Data Type String
Exposure FACEPLATONLY
Range N/A
Default Null
Config Load Yes
Access Lock Application Developer
Residence SR
Related
Parameters
Remarks

21.152 SECVAR

Specific to AICHANNEL, HAICHANNEL (PM I/O)


Block(s)
Description Secondary Variable. Shows the value of secondary variable for the given Smart
Transmitter.
Data Type 32-Bit Real Number
Range
Default NaN
Config Load No
Active No
Loadable

- 2825 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence IOP
Related
Parameters
Remarks This parameter is only exposed, if ASSOCIOPTYP is STI-MV. The secondary
variable for a given Smart Transmitter is as follows:
l For Pressure Transmitter: Temperature of the transmitter
l For Temperature Transmitter: Cold junction temperature
l For Magnetic Flowmeter Transmitter: Totalized value

21.153 SELDESC

Specific to SignalSel
Block(s)
Description Selected Input Descriptor
Data Type Self-Defining Enumeration: PDESC
Range N/A
Default “”
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related PDESC[1..10]
Parameters
Remarks This parameter contains the description of the currently selected input , which is
shown in SELIN parameter

21.154 SELECTCABLEACMD

Specific to All PM I/O Modules


Block(s)
Description Select I/O Link Cable A. Used to select the A cable (channel A) to communicate
between the IOM and the IOLIM.
Data Type Boolean
Range 0 On Select I/O Link Cable A
command has been
initiated.
1 Off No command.
Default Off (1)
Config No
Load

- 2826 -
Chapter 21 - Sxxxx Parameters

Active No
Loadable
Access Lock Operator
Residence IOLIM
Related
Parameters
Remarks Used to select the A cable (channel A) to communicate between the IOM and the
IOLIM. Unlike the Link FB's COMMAND parameter that affects the entire I/O Link,
the scope of this command is limited to the redundant IOM pair (or single IOM if
non-redundant). If Periodic Cable Swap is enabled, the effect of selecting a
particular channel does not persist longer than one minute.

21.155 SELECTCABLEBCMD

Specific to All PM I/O Modules


Block(s)
Description Select I/O Link Cable B. Used to select the B cable (channel B) to communicate
between the IOM and the IOLIM.
Data Type Boolean
Range 0 On Select I/O Link Cable B
command has been
initiated.
1 Off No command.
Default Off (1)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOLIM
Related
Parameters
Remarks Used to select the B cable (channel B) to communicate between the IOM and the
IOLIM. Unlike the Link FB's COMMAND parameter that affects the entire I/O Link,
the scope of this command is limited to the redundant IOM pair (or single IOM if
non-redundant). If Periodic Cable Swap is enabled, the effect of selecting a
particular channel does not persist longer than one minute.

- 2827 -
Chapter 21 - Sxxxx Parameters

21.156 SELHANDLER[1..8]

Specific to SCM, RCM


Block(s)
Description Selected Handler Handle
Data Type BlockId
Range
Default Null String
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related TYPE SELHANDLERN[1..8]
Parameters
Remarks A handler of is assigned by setting SELHANDLER[i] to that handler's name (for
example, SCMName.HandlerName). For example, to change the selected Hold
Handler (TYPE 6) to another named LONGHOLD, the assignment SELHANDLER[6]
= SCMName.LONGHOLD would be made. The recommended method of
deselecting a handler of TYPE i is to set SELHANDLERN[i] = 0. Note, that
expressions within the CEE cannot operate on parameters of type BlockId,
therefore expressions in step outputs must use the parameter SELHANDLER
instead. The selected handler of a given TYPE can only be changed if it is not
currently executing. The Main handler selection cannot be changed once the SCM
transitions to Running. The Interrupt handler selection cannot be changed if the
currently selected Interrupt handler is being preempted. The Null and Edit handler
selections cannot be changed by the user or program.

21.157 SELHANDLERN[1..8]

Specific to SCM, RCM


Block(s)
Description Specifies the component number of the selected handler of the SCM for each
handler type. SELHANDLERN is an internal numeric form for the Handler name
that the controller can recognize. Numeric identifiers are assigned to handlers at
the time the SCM's handlers are built.
Data Type 32-Bit Integer
Range
Default N/A
Config No
Load
Active No
Loadable

- 2828 -
Chapter 21 - Sxxxx Parameters

Access Engineer
Lock
Residence CEE
Related SELHANDLER[1..8], NUM
Parameters
Remarks The index [1..8] identifies the handler type as: 1-Edit 2-Main 3-Check 4-Interrupt 5-
Restart 6-Hold 7-Stop 8-Abort. SELHANDLERN[1] for the Edit handler cannot be
changed. SELHANDLERN[i] cannot be changed when handler type i is active, for
example, the selected Hold handler cannot be changed (via SELHANDLERN[6])
when the SCM STATE is Holding. An SCM can be used to change the selected
handler, using an Output expression. Example: SCMName.SELHANDLERN[7] :=
SCMName.StopHandlerName.NUM Changes the selected Stop handler to the
handler StopHandlerName To disable a specific handler type, set the
SELHANDLERN to 0. Example: To disable all Hold Handlers use the expression:
SELHANDLERN[6] = 0. After setting SELHANDLERN[6] = 0, the read value of
SELHANDLERN[6] will equal -16. The value when a handler type is not selected
reads: SELHANDLERN[2] = -12 SELHANDLERN[3] = -13 SELHANDLERN[4] = -14
SELHANDLERN[5] = -15 SELHANDLERN[6] = -16 SELHANDLERN[7] = -17
SELHANDLERN[8] = -18

21.158 SELIN

Specific to Block(s) SignalSel


Description Selected Input
Data Type Enumeration: PINP
Range 0: None 1: SelectP1 2: SelectP2 3: SelectP3 4: SelectP4 5: SelectP5 6:
SelectP6
Default None
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related Parameters BOOLMUX, P, PV
Remarks This parameter denotes which P input is taken as the PV value.

21.159 SELINT32FL

Specific to Up / Down Counter Block


Block(s)
Description Input Selection Specifier - This parameter is used to select the input data type.
Data Type Boolean
Range FALSE,TRUE
Default FALSE
Config Yes
Load

- 2829 -
Chapter 21 - Sxxxx Parameters

Active No
Loadable
Access Lock Application Developer
Residence CEE
Related ININT32, INFLOAT64
Parameters
Remarks When this parameter is set to “TRUE”, the ININT32 parameter is used as input for
the CTUD block. When this parameter is set to “FALSE”, the INFLOAT64 parameter
is used as input for the CTUD block. By default, this parameter value is “FALSE”.

21.160 SELMETHOD

Specific to SignalSel
Block(s)
Description Selection Method
Data Type Enumeration: SELMETHOD
Range 0: MIN 1: MAX 2: AVG 3: MED 4: MUX
Default MIN
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related P, PV
Parameters
Remarks This parameter defines the functionality of the block. This parameter can be
changed only when the block is inactive or CEE state is IDLE. This parameter can
be changed by other agents, such as SCM block or CAB block, when the function
block is inactive or CEE is IDLE.

21.161 SELXDESC

Specific to Switch, OvrdSel, RemCas


Block(s)
Description Selected Input Descriptor - 15-character descriptor for the currently-selected
input to the OvrdSel and Switch function blocks.
Data Type String
Range Length: 15 characters
Default Null String
Config Load No
Active No
Loadable

- 2830 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related XDESC[1..8]
Parameters
Remarks

21.162 SELXFL[1..4]

Specific to OvrdSel
Block(s)
Description Input Selection Flags - Identifies the currently-selected input to the OvrdSel
function block. There is one flag per input.
Data Type Boolean
Range Off (0): Input is not selected. On (1): Input is selected
Default SELXFL[1] = On (1) All others =Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SELXINP
Parameters
Remarks

21.163 SELXFL[1..6]

Specific to Block(s) SignalSel


Description Boolean Selection flags for Individual inputs
Data Type Boolean
Range Each array element takes values OFF, ON
OFF (0) The associated input is not selected
ON (1) The associated input has been selected

Default ON
Config Load Yes
Active Loadable No
Access Lock Operator
Residence C300 (CEEC300), C200 (CEE), ACE (CEEACE).
Related Parameters BOOLMUX, BOOLMUX
Remarks This parameter represents the selection flags for Boolean MUX selection.

- 2831 -
Chapter 21 - Sxxxx Parameters

21.164 SELXFL[1..8]

Specific to Switch, OvrdSel


Block(s)
Description Input Selection Flags - Identifies the currently-selected input to the Switch
function block. There is one flag per input.
Data Type Boolean
Range Off (0): Input is not selected. On (1): Input is selected
Default SELXFL[1] = On (1) All others =Off (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related SELXINP
Parameters
Remarks

21.165 SELXINP

Specific to Block(s) Switch


Description Selection ID - Identifies the currently-selected input to the function block.
Data Type Integer
Range 1 to 8
Default 1
Config Load No
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters SELXDESC, SELXFL[1..8].
Remarks

Specific to Block(s) OvrdSel, RemCas


Description Selection ID - Identifies the currently-selected input to the function block.
Data Type Integer
Range 1 to 4
Default 1
Config Load No
Active Loadable No

- 2832 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related Parameters SELXDESC, SELXFL[1..8]..
Remarks

21.166 SENDCLOSEREQ

Specific to Block(s) FTEB


Description Send Close Request - Identifies the close requests sent.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

21.167 SENDCLOSERESP

Specific to Block(s) FTEB


Description Send Close Response - Identifies the close responses sent.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

- 2833 -
Chapter 21 - Sxxxx Parameters

21.168 SENDFL[0..15]

Specific to Block(s) Message


Description Send Flag to trigger sending message.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks

21.169 SENDOPENREQ

Specific to Block(s) FTEB


Description Send Open Request - Identifies open requests sent.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB
Related Parameters
Remarks

21.170 SENDOPENRSP

Specific to Block(s) FTEB


Description Send Open Response - Identifies open responses sent.
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No

- 2834 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence FTEB
Related Parameters
Remarks

21.171 SENSORTYPE[0..numChans-1]

Specific to AIM
Block(s)
Description Sensor Type
Data Type Enumeration of SENSOR_RTD for RTD AIM Enumeration of SENSOR_TC for
Thermocouple AIM
Range SENSOR_RTD Ohms (0) 100_Pt_385 (1) 200_Pt_385 (2) 500_Pt_385 (3) 1000_Pt_385
(4) 100_Pt_3916 (5) 200_Pt_3916 (6) 500_Pt_3916 (7) 1000_Pt_3916 (8) 10_Cop_427
(9) 120_Ni_672 (10) 100_Ni_618 (11) 120_Ni_618 (12) 200_Ni_618 (13) 500_Ni_618
(14) SENSOR_TC MV (0) B (1) C (2) E (3) J (4) K (5) N (6) R (7) S (8) T (9)
Default SENSOR_RTD: Ohms (0) SENSOR_TC: MV (0)
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related OHMOFFSET[0..numChans-1]
Parameters
Remarks Configurable only on RTD and Thermocouple AIMs.

21.172 SENSORTYPE [0..NUMCHANNELS-1]

Specific to EtherNet/IP [EIP] IOMs: 1738-IR2M12, 1738-IT2IM12, 1732E-IR4IM12R, 1732E-


Block(s) IT4IM12R
Description Sensor Type — Specifies the sensor type for each channel. This parameter allows
you to select one of nine sensor types for the RTD and one of the ten sensor types
for the thermocouples.
Data Type Enumeration
Range 1738-IR2M12, 1732E-IR4IM12R:
l Ohms
l 100 Ohms Pt 385
l 200 Ohms Pt 385
l 100 Ohms Pt 3916
l 200 Ohms Pt 3916
l 10 Ohms Cu 427
l 120 Ohm Ni 672

- 2835 -
Chapter 21 - Sxxxx Parameters

l mv
l Type B
l Type C
l Type E
l Type J
l Type K
l Type N
l Type R
l Type S
l Type T
Default
Config Load No
Active No
Loadable
Access Lock AppDevOnly
Residence SR
Related PVLOSIGNAL,PVHISIGNAL, TEMPUNITS
Parameters
Remarks

21.173 SENSRTYP

- 2836 -
Chapter 21 - Sxxxx Parameters

Specific to Series C AICHANNEL


Block(s)

Description Sensor Type

Data Type ENUM

Exposure OUTPUT

Range 0 1_5_V 1 to 5 volts

1 0_5_V 0 to 5 volts

2 0_100_MV 0 to 100 millivolts

3 THERMCPL Thermocouple

4 RTD Resistance
Temperature Device
5 P4_2_V 0.4 to 2 volts

6 Not Used Was Slidewire in PM


I/O, Not used and
reserved in Series C
I/O
8 SPT_DP ST3000 – differential
pressure
9 SPT_GP ST3000 – gauge
pressure
10 SPT_AP ST3000 – absolute
pressure
11 STT ST3000 –
temperature
12 SFM ST3000 – MagneW
3000 – magnetic flow
and most
multivariable
transmitters
21 LVDT

22 RVDT

23 Resolver

24 -7_22_mV -7.0 mV to 22mV


input used on SCA
TC/RTD module
25 -20_125_mV -20.0 mV to 125mV
input used on SCA
TC/RTD module
26 0_500_Ohms 0 to 500 Ohms input
used on SCA TC/RTD
module
27 0_2000_Ohms 0 to 2000 Ohms input
used on SCA TC/RTD
module
Default 0 1_5_V Channels on an AI-
LLMUX, AI-HART,
UIO and UIO2
8 SPT_DP Channels on an STI
module

- 2837 -
Chapter 21 - Sxxxx Parameters

Config Yes
Load

Application Developer

Residence IOM

Related HENABLE
Parameters

Remarks For channels on AI-HART and AI-LLMUX modules, this parameter defines the type of field
sensor connected to the I/O Terminal Assembly (IOTA). For channels on an STI module,
this parameter defines the Smart Transmitter Type. When HENABLE is set to TRUE on AI
channels, SENSRTYP is forced to 1_5_V. The user is always provided with the list of valid
values for the particular AI channel type. The user is NEVER shown or given the
opportunity to select an invalid value for any particular AI channel type. Valid values for
each AI module type are listed below.

AI-HART Valid values are 1_5_V, 0_5_V, P4_2_V

AI-LLMUX UIO Valid values are 1_5_V, 0_5_V, 0_100_MV,


THERMCPL, RTD Valid values are 1_5_V, 0_
5_V

UIO-2 Valid values are 1_5_V, 0_5_V, THERMCPL,


RTD, -7_22mV, -20_125mV, 0_500_Ohms,
0_2000_Ohms

Internal No
Only

- 2838 -
Chapter 21 - Sxxxx Parameters

Specific to AICHANNEL, HAICHANNEL


Block(s)

Description Sensor Type

Data Type ENUM

Exposure OUTPUT

Range 0 1_5_V 1 to 5 volts

1 0_5_V 0 to 5 volts

2 0_100_MV 0 to 100 millivolts

3 THERMCPL Thermocouple

4 RTD Resistance
Temperature Device
5 P4_2_V 0.4 to 2 volts

8 SPT_DP ST3000 – differential


pressure
9 SPT_GP ST3000 – gauge
pressure
10 SPT_AP ST3000 – absolute
pressure
11 STT ST3000 – temperature

12 SFM ST3000 – MagneW


3000 – magnetic flow
and most
multivariable
transmitters
Default 0

Config Yes
Load

Application Developer

Residence IOM

Related HENABLE
Parameters

Remarks For HLAI, HLAIHART, LLAI, LLMUX, and RHMUX, this parameter defines the type of field
sensor connected to the Field Terminal Assembly (FTA). For STI, this parameter defines
the Smart Transmitter Type. Restrictions: When HENABLE is set to TRUE (HAI channel
blocks only), SENSRTYP is forced to 1_5_V.

HLAI Valid values are 1_5_V, 0_5_V, P4_2_V

HLAIHART Valid values are 1_5_V, 0_5_V, P4_2_V

LLAI Valid values are 1_5_V, 0_5_V, 0_100_MV,


THERMCPL, RTD

- 2839 -
Chapter 21 - Sxxxx Parameters

LLMUX Valid values are 0_100_MV, THERMCPL,


RTD

RHMUX Valid values are 0_100_MV, THERMCPL

STI Valid values are SPT_DP, SPT_GP, SPT_AP,


STT, SFM

Internal No
Only

21.174 SENSRTYP_AI_C

Specific to UIO
Block(s)

Description Sensor Type


Data Type ENUM
Range
0 1_5_V 1 to 5 Volts

1 0_5_V 0 to 5 Volts

Default -2.9 - The unit of measure is engineering units.


Limit error checking and range overlap error checking for PVEXEULO_AI_C and
PVEXEUHI_AI_C are performed by the system.
Config Yes
Load

Active No
Loadable

Access Application Developer


Lock

Residence UIO
Related HENABLE
Parameters

Remarks This parameter defines the type of field sensor connected to the IOM screws.
The user is always provided with the list of valid values for the particular AI channel type.
The user is NEVER shown or given the opportunity to select an invalid value for any
particular AI channel type.

Specific to UIO
Block(s)

Description Sensor Type


Data Type ENUM
Range
0 1_5_V 1 to 5 Volts or 4mA to 20mA

1 0_5_V 0 to 5 Volts or 0mA to 20mA

- 2840 -
Chapter 21 - Sxxxx Parameters

Default
0 1_5_V Channels on an UIO

Config Yes
Load

Active No
Loadable

Access Application Developer


Lock

Residence IOM Block


Related HENABLE_AI_C
Parameters

Remarks This parameter defines the type of field sensor connected to the IOM screws. The user is
always provided with the list of valid values for the particular AI channel type. The user is
NEVER shown or given the opportunity to select an invalid value for any particular AI
channel type

Specific to UAI
Block(s)

Description Sensor Type


Data Type ENUM
Range
0 THERMOCOUPLE

1 RTD

2 LINEAR

3 SPECIAL

Default
2 LINEAR

Config Yes
Load

Active No
Loadable

Access Application Developer


Lock

Residence IOM Block


Related THERMOCOUPLETYPE
Parameters
RTDTYPE
LINEARTYPE
SPECIALTYPE
Remarks This parameter defines the type of field sensor connected to the UAI screws. The user is
always provided with the list of valid values for the particular AI channel type. The user is
NEVER shown or given the opportunity to select an invalid value for any particular AI
channel type.

- 2841 -
Chapter 21 - Sxxxx Parameters

Specific to AI16-100MS
Block(s)

Description Sensor Type


Data Type ENUM
Range
0 4_20_mA 1 to 5 Volts or 4mA to 20mA

1 0_10_mA 0 to 5 Volts or 0mA to 20mA

2 0_1_V 0 to 1 Volts

3 0_2_V 0 to 2 Volts

4 0_5_V 0 to 5 Volts

5 0_10_V 0 to 10 Volts

6 -1_1_V -1 to 1 Volts

7 -2_2_V -2 to 2 Volts

8 -5_5_V -5 to 5 Volts

9 -10_10_V -10 to 10 Volts

Default
0 4_20_mA

Config Yes
Load

Active
Loadable

Access Application Developer


Lock

Residence IOM Block


Related HENABLE_AI_C
Parameters

Remarks This parameter defines the type of field sensor connected to the IOM screws. The user is
always provided with the list of valid values for the particular AI channel type. The user is
NEVER shown or given the opportunity to select an invalid value for any particular AI
channel type.

21.175 SEQCLOSE

Specific to Block(s) SOLENOID, VALVEDAMPER


Description Sequential Close
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No

- 2842 -
Chapter 21 - Sxxxx Parameters

Access Lock Program


Residence CEE
Related Parameters GOPOPOPFINALOPREQ REMOTESWITCH
Remarks Command to close the valve through SCM.

21.176 SEQNOCMD

Specific to VALVEDAMPER
Block(s)
Description Sequence No Command
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active No
Loadable
Access Lock Program
Residence CEE
Related SEQCLOSE SEQOPEN
Parameters
Remarks The “Sequence No Command”through SCM can be used to disable the Sequential
Open/Sequential Close command, if any.

21.177 SEQOPEN

Specific to Block(s) VALVEDAMPER


Description Sequential Open
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Program
Residence CEE
Related Parameters GOPOPOPFINALOPREQ REMOTESWITCH
Remarks Command to open the valve through SCM.

- 2843 -
Chapter 21 - Sxxxx Parameters

21.178 SEQSTART

Specific to Block(s) HTMOTOR, LTMOTOR


Description Sequence Start
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No
Access Lock Program
Residence CEE
Related Parameters GOPOPOPFINALOPREQ REMOTESWITCH
Remarks Command to start the motor through SCM.

21.179 SEQSTATUS

Specific to Block(s) MAINIBV


Description Sequence Status
Data Type Enumeration
Range IDLE, CLOSESEQ, OPENSEQ
Default IDLE
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

21.180 SEQSTOP

Specific to Block(s) HTMOTOR, LTMOTOR


Description Sequence Stop
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active Loadable No

- 2844 -
Chapter 21 - Sxxxx Parameters

Access Lock Program


Residence CEE
Related Parameters GOPOPOPFINALOPREQ REMOTESWITCH
Remarks Command to stop the motor through SCM.

21.181 SEQSTOPACTED

Specific to HTMOTOR
Block(s)
Description Sequence Stop Acted
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SEQSTOP RESETFIRSTUP
Parameters
Remarks Indicates that the corresponding command has been issued that has changed
the output state to STOP.

21.182 SERIALNO

Specific to Block AICHANNEL


(s)
Description Serial Number. Shows the value of the serial number/PROM number for the
Smart Transmitter.
Data Type String
Range
Default NULL
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is only exposed, if ASSOCIOPTYP is STI-MV.

- 2845 -
Chapter 21 - Sxxxx Parameters

21.183 SERIALNUM

Specific to RM, PGM, FIM4, EHPM , TCMI


Block(s)
Description Redundancy Module Serial Number
Data Type 32-Bit Unsigned Integer
Range 0 to 4294967295
Default Null
Config Load No
Active No
Loadable
Access Lock ViewOnly RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence Not Loaded, C300, PGM, FIM4, RM, EHPM
Related
Parameters
Remarks

Specific to C300 and FIM4 FBs


Block(s)
Description Serial Number. Unique module serial number. Used within initial redundancy role
determination as final tie breaker during simultaneous module power up.
Data Type INT
Range 0...4294967295
Default Null
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4
Related
Parameters
Remarks

Specific to Block(s) EIM


Description Serial Number.
Data Type UINT32
Range 0...4294967295
Default
Config Load No
Active Loadable No

- 2846 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related Parameters
Remarks

Specific to Block(s) UOC


Description Serial Number
Data Type UINT32
Exposure NONE
Range 0 to 4294967295
Default
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (hardware statistics, see C300 definition)

21.184 SERVERIP

Specific to Block(s) FTEB and C300 FBs


Description Server's Primary IP
Data Type String
Range Length : 16 Characters
Default Null
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence FTEB, C300
Related Parameters
Remarks

21.185 SHAREDMEM

Specific to Block(s) ProfitCtl


Description Shared Memory(KB)
Data Type FLOAT64
Range NA
Default False

- 2847 -
Chapter 21 - Sxxxx Parameters

Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

21.186 SHEDHOLD

Specific to EIM
Block(s)
Description Shed Hold
Data Type BOOLEAN
Range NA
Default OFF
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related COMMOK
Parameters
Remarks If shed hold is true then dataset parameter will hold last value in case of any
communication failure else dataset parameter will set to datatype default value.

21.187 SHEDMODE[0..7]

Specific to Chassis HART AO IOM


Block(s)
Description Shed Mode - Shed to Safe Value enabler If enabled, the output will assume the
Safe Value (FAULTVALUE) in the event of controller failure or a loss of
communication between the controller and the IOM. If disabled, the output will hold
the last value processed.
Data Type Boolean
Range Hold Last Output Value (0), Use Safe Value (1)
Default Use Safe Value (1)
Config Yes
Load
Active No
Loadable

- 2848 -
Chapter 21 - Sxxxx Parameters

Access Lock Application Developer Only


Residence CEE
Related FAULTVALUE
Parameters
Remarks SHEDMODE must be set to “Use Safe Value” in order to configure FAULTVALUE.
Note that if the IOM device fails, the output value is not deterministic.

21.188 SHEDHOLD

Specific to EIM
Block(s)
Description Shed Hold
Data Type BOOLEAN
Range NA
Default OFF
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related COMMOK
Parameters
Remarks If shed hold is true then dataset parameter will hold last value in case of any
communication failure else dataset parameter will set to datatype default value.

21.189 SHORT

Specific to Block(s) DOC


Description Indicates that a short circuit or overload condition exists.
Data Type Boolean
Range Short condition does not exist (0) Short condition exists (1)
Default Short condition does not exist (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2849 -
Chapter 21 - Sxxxx Parameters

21.190 SHORT_DI_C

Specific to UIO
Block(s)

Description Short Circuit Detect


Data Type BOOLEAN
Range
OUTPUT

0 OFF Disable Short Circuit Detection

1 ON Enable Short Circuit Detection.

Default Off
Config Load Yes
Active No
Loadable

Access Lock AppDevOnly


Residence CEE, IOM Block
Related
Parameters

Remarks This parameter allows the user to enable/disable short circuit detection.
When enabled, the condition is annunciated as an alarm in the System Alarm
Summary.
When a Short Circuit is detected, the PVSTS is set to BAD and Soft Failure “Short
Circuit Detected” will be generated.

21.191 SHORT[0..numChans-1]

Specific to Block(s) DOM


Description Indicates that a short circuit or overload condition exists.
Data Type Boolean
Range Short condition does not exist (0) Short condition exists (1)
Default Short condition does not exist (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks

- 2850 -
Chapter 21 - Sxxxx Parameters

21.192 SHORTCIRCUIT[0..Number of status in assembly]

Specific to EtherNet/IP [EIP] IOMs: 1738-IB4DM12, 1732E-IB16M12DR


Block(s)
Description Short Circuit detection flag — This parameter value changes to ON when the IO
hardware reports Short Circuit condition.
Data Type Boolean
Range l Off
l On
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence NOLOAD
Related OPENWIRE
Parameters
Remarks 1732E-IB16M12DR Only: Each index of the parameter represents the combined
status of two channels. For example, if SHORTCIRCUIT[0] is = ON, then channel 0
or channel 1 or both are short circuits.

21.193 Show UCM On Unit Timeline

Specific to Block(s) UCM


Description Show UCM On Unit Timeline
Data Type Boolean
Range Off/On
Default On
Config Load Yes
Active Loadable Yes
Access Lock APPDEVONLY
Residence Server
Related Parameters
Remarks Indicates that this UCM should appear or not appear on the Unit Timeline

21.194 SHUTDOWNCMD

Specific to Block(s) IOLIM, Secondary IOLIM


Description Shutdown IOLIM
Data Type Boolean
Range Off (0): The command is not active. Of (1): The command is active.

- 2851 -
Chapter 21 - Sxxxx Parameters

Default Off (0)


Config Load No
Active Loadable No
Access Lock Engineer
Residence IOLIM
Related Parameters ENCMDS
Remarks Pressing this button will shutdown the IOLIM. The 'Shutdown
IOLIM'button is located on the Main tab of the IOLIM configuration
form and is enabled only when Enable IOLIM Commands (ENCMDS)
is set to ON.

WARNING Performing an IOLIM shutdown will result in a loss of control. All outputs will
transition to their configured safe state.

21.195 SI

Specific to DEVCTL, HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Safety Override Interlock
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Engineer, Other Function Block, (see Remarks)
Residence CEE
Related GOP, OI[0..2], OP, SAFEOP, SIALM.FL, DEVCTL Only: NUMDOUTS,
Parameters SIALM.OPT, SIALM.PR, SIALM.SV.
Remarks Engineer can change only when function block is inactive or CEE is idle. DEVCTL:
Illegal if NUMDOUTS = 0

21.196 SIACTED

Specific to HTMOTOR
Block(s)
Description Safety Interlock (SI) Acted
Data Type Boolean
Range ON-OFF
Default OFF
Config Load NO

- 2852 -
Chapter 21 - Sxxxx Parameters

Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related ERRCODE RESETFIRSTUP
Parameters
Remarks Indicates that the safety interlock has been corresponding issued that has
changed the output state to STOP.

21.197 SIALM.FL

Specific to DevCtl All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, Regsummer,
and Switch. All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,
VALVEDAMPER
Description Safety Override Alarm
Data Type Boolean
Range Off (0): Is not in Safety Interlock alarm. On (1): Is in Safety Interlock alarm condition.

Default Off (0)


Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SIFL, SIALM.OPT, SIALM.PR, SIALM.SV. DevCtl Only: HENABLE, HEU,
Parameters Drive Control Only: HIALM, INALM, SI, HEXCOMERRSFL, HFASSYNO, HFLAGS,
SIALM.OPT, SIALM.PR, SIALM.SV. HHWREV, HIALM, INALM, NUMDOUTS,
SI.
Remarks DevCtl Only: Illegal if NUMDOUTS = 0.

21.198 SIALM.OPT

Specific to Block(s) DevCtl


Description Safety Interlock Alarm Option
Data Type Enumeration OVRDALOP
Range No Yes
Default N/A
Config Load Yes
Active Loadable No

- 2853 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters SIFL, SIALM.FL, SIALM.PR, SIALM.SV.
Remarks Illegal if NUMDOUTS = 0. To change, function block must be InActive.

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Safety Interlock Alarm Option - Indicates if Safety Interlock alarming is enabled.
Data Type Enumeration ENBSTATE
Range Checked (X): Enable Safety Interlock alarming
Unchecked ( ): Disable Safety Interlock alarming
Default Checked (X)
Config Load Yes
Active No
Loadable
Access Lock Engineer/Application Developer
Residence CEE
Related SIFL, SIALM.FL, SIALM.PR, SIALM.SV.
Parameters
Remarks

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Safety Interlock Alarm Option
Data Type Enumeration
Range DISABLE ENABLE
Default ENABLE
Config Load Yes
Active Loadable No
Access Lock Engineer when CM is inactive
Residence CEE
Related Parameters SIALM.FL, SIALM.PR, SIALM.SV.
Remarks

21.199 SIALM.PR

Specific to DevCtl All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,
VALVEDAMPER
Description Safety Interlock Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)

- 2854 -
Chapter 21 - Sxxxx Parameters

Default None
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SIFL, SIALM.FL, SIALM.OPT, SIALM.PR. DevCtl Only: NUMDOUTS SI, Drive
Parameters Control Only: SIALM.FL, SIALM.OPT,
SIALM.SV.
Remarks DevCtl Only: Illegal if NUMDOUTS = 0.

21.200 SIALM.SV

Specific to DevCtl All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch. All Drive Control Blocks: HTMOTOR, LTMOTOR, SOLENOID,
VALVEDAMPER
Description Safety Interlock Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SIFL, SIALM.FL, SIALM.OPT, SIALM.PR. DevCtl Only: NUMDOUTS SI, Drive
Parameters Control Only: SIALM.FL, SIALM.OPT,
SIALM.SV.
Remarks DevCtl Only: Illegal if NUMDOUTS = 0.

21.201 SIFL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Safety Interlock Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No

- 2855 -
Chapter 21 - Sxxxx Parameters

Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related SIOPT, SIALM.FL, SIALM.OPT, SIALM.PR, SIALM.SV.
Parameters
Remarks

Specific to Block(s) ProfitCtl


Description Safety Interlock Flag
Data Type BOOLEAN
Range NA
Default OFF
Config Load No
Active Loadable No
Access Lock OtherFb
Residence CEE
Related Parameters
Remarks

21.202 SIMC200MACID

Specific to SIM_C200
Block(s)
Description Simulation C200 Media Access Control (MAC) ID - Specifies the MAC address
assigned to the PCIC card installed in the SIM_C200 node for ControlNet
connections.
Data Type 32-Bit Integer
Range 1 to 99
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related CMLOADFL, CNETCONNECT
Parameters
Remarks

- 2856 -
Chapter 21 - Sxxxx Parameters

21.203 SIMC200EMACID

Specific to SIM-C200E
Block(s)
Description Simulation C200E Media Access Control (MAC) ID - Specifies the MAC address
assigned to the PCIC card installed in the SIM-C200E node for ControlNet
connections.
Data Type 32-Bit Integer
Range 1 to 99
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence SR
Related CMLOADFL, CNETCONNECT
Parameters
Remarks

21.204 SIMCOMMAND

Specific to CEEC300, CEEACE, CEESIMC200, CN100


Block(s)
Description Simulation State
Data Type Enumeration : SIMCOMMAND
Range NONE (0)
SIMRUN (1)
SIMFREEZE (2)
SIMDISABLE (3)
Default NONE
Config No
Load
Active No
Loadable

- 2857 -
Chapter 21 - Sxxxx Parameters

Access ViewOnly
Lock
Residence C300, ACE, SIM_C200
Related SIMENABLE, SIMSTATE
Parameters
Remarks Lets user with Engineer access level, initiate SIMDISABLE command. Only UniSim
can issue commands other than SIMDISABLE. SIMFREEZE: Freezes CEESIMC200
operation and stops simulation. The following is a summary of system operation in
this state. SIMRUN: Tells CEESIMC200 to start running the simulation or stepping
through different execution cycles. The following is a summary of system operation
in this state. SIMDISABLE: Disables the simulation because UniSim has exited or
the engineer has issued a SIMDISABLE command. This will always change
SIMSTATE to SIMRUN. NONE: No command has been issued or the issued
command has been processed.

21.205 SIMVALUE[1..1968]

Specific to PCDIFLAGARRCH
Block(s)
Description Simulation Value
Data Type Boolean
Range OFF/ON
Default OFF
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related SIMMODE
Parameters
Remarks When SIMMODE = SimValSub, the PV is substituted with SIMVALUE. SIMVALUE
can be fetched from another block using a parameter connection or it can be set by
an operator or other applications. Reading SIMVALUE always returns the value of
PV. Writing SIMVALUE returns an error, if SIMMODE does not equal SimValSub.

21.206 SIMDEVICEIDX

Specific to Block C300 and FIM4 FB, PGM


(s)
Description Simulation Node's Device Index. User configured FTE Device Index of the
SIMC300 node.
Data Type 32-Bit Integer
Range 0-255
Default 0

- 2858 -
Chapter 21 - Sxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Application Developer Only
Residence SR
Related SIMIPADDRESS, SIMENABLE
Parameters
Remarks

21.207 SIMENABLE

Specific to Block C300 and FIM4 FBs CEEACE, CEESIMC200, OPC, ICG, GEE,
(s) PGM, CN100
Description Simulation Enable
Data Type Boolean
Range Off (0) - Disabled On (1) - Enabled
Default Off
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence C300, ACE, SIM_C200, OPC, ICG, GEEFB, PGM
Related SIMDEVICEIDX, SIMIPADDRESS
Parameters
Remarks

21.208 SIMIPADDRESS

Specific to Block(s) C300 & FIM4, PGM


Description Simulation Node IP Address
Data Type String
Range Length : 15 Characters
Default 0.0.0.0
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters SIMDEVICEIDX, SIMENABLE
Remarks

- 2859 -
Chapter 21 - Sxxxx Parameters

21.209 SIMMODE

Specific to DICHANNEL, AICHANNEL


Block(s)
Description Simulation Mode
Data Type Enumeration
Range 0 None No simulation. Input value is obtained from the wire.
1 DirectSub Operator / ShadowPlant writes to PV.
2 SimValSub Operator / ShadowPlant writes to SIMVALUE. Or
SIMVALUE is fetched from a parameter connection.
Default 0 None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence IOP
Related SIMVALUE
Parameters
Remarks SIMMODE is always 0 (None) in a non-simulation environment.

Specific to UIO – Series C DICHANNEL


Block(s)
Description Simulation Mode
Data Type Enumeration
Range 0 None No simulation. Input value is obtained from the wire.
1 DirectSub Operator / ShadowPlant writes to PV, if DITYPE is "Status" or
"Latched." Operator / ShadowPlant writes frequency to
SIMVALUEREAL, if DITYPE is "Accum."
2 SimValSub When DITYPE is "Status" or "Latched," Operator / ShadowPlant
writes to SIMVALUE. Or SIMVALUE is fetched from a parameter
connection. When DITYPE is "Accum," Operator / ShadowPlant
writes to SIMVALUEREAL Or SIMVALUEREAL is fetched from a
parameter connection. SIMVALUEREAL contains frequency for
pulse counting.
Default 0 None
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence IOP
Related SIMVALUESIMVALUEREAL
Parameters
Remarks SIMMODE is always 0 (None) in a non-simulation environment.

- 2860 -
Chapter 21 - Sxxxx Parameters

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Simulation Mode
Data Type Enumeration
Range 0 None No simulation. Input value is obtained
from the wire.
1 DirectSub Operator or other applications can write
to PV.
2 SimValSub PV is substituted with SIMVALUE.
SIMVALUE can be fetched from a
parameter connection or set by an
operator or the other applications.
3 Initdisable Initialization is disabled.
Default 0 None
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SIMVALUE
Parameters
Remarks SIMMODE is always 0 (None) in a non-simulation environment. In both DirectSub
and SimValueSub modes, the ERRFL and ERRCODE parameters can be written by
an operator or the other applications.

Specific to Block(s) EIM


Description Simulation Mode
Data Type ENUM
Range NA
Default NONE
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters
Remarks

- 2861 -
Chapter 21 - Sxxxx Parameters

21.210 SIMSTATE

Specific to Block(s) CEEC300, CEEACE, CEESIMC200, SIMIOLINK, SIMEHPM, CN100


Description Simulation State
Data Type Enumeration
Range SIMFREEZE (0) SIMRUN (1) NONE (2)
Default NONE
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, ACE, SIM_C200, SIMIOLINK, SIMEHPM
Related Parameters CEESTATE, SIMENABLE, SIMC200EMACIDSIMCOMMAND
Remarks If UniSim is not controlling the CEE, the SIMSTATE always equals NONE

Specific to All IOM blocks


Block(s)
Description Simulation State
Data Type ENUMERATION
Range 0 SIMFREEZE IOM is assigned to I/O link of
a frozen simulation
environment.
1 SIMRUN IOM is assigned to I/O link of
an executing simulation
environment.
2 NONE IOM is not assigned to I/O
link of simulation
environment.
Default NONE
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLIM
Related
Parameters
Remarks The Simulation State of the I/O Link is accessible on each IOM for display
purposes. If IOMs are assigned to the physical IOLIM (non-simulation), the
SIMSTATE always equals NONE.

- 2862 -
Chapter 21 - Sxxxx Parameters

21.211 SIMTARGET

Specific to Block C200, C300 FBs, SIMEHPM, UOC, CN100


(s)
Description Load to simulation Environment.
Data Type BOOLEAN
Exposure OUTPUT, NONE
Range OFF (0) ON (1) N/A
Default OFF (0)
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related SIMENABLEMODISREDUN
Parameters
Remarks Determines if the controller should be a physical EHPM or a simulated EHPM
loaded to a SCE node.

21.212 SIMULATEDIO

Specific to Block(s) EHPM


Description Enabled simulated IO.
Data Type Boolean
Exposure NONE
Range ON
Default OFF (FALSE)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters N/A
Remarks Indicates that the EHPM Controller executes simulated IO personality.

- 2863 -
Chapter 21 - Sxxxx Parameters

21.213 SIMVALUE

Specific to DICHANNEL
Block(s)
Description Simulation Value
Data Type Boolean
Range Off On
Default Off
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOP
Related SIMMODE
Parameters
Remarks When SIMMODE = SimValSub, the PV is substituted with SIMVALUE. SIMVALUE
can be fetched from another block using a parameter connection or it can be set by
an operator or the ShadowPlant application. Reading SIMVALUE always returns
the value of PV. Writing SIMVALUE returns an error if SIMMODE does not equal
SimValSub.

Specific to AICHANNEL
Block(s)
Description Simulation Value
Data Type Float64
Range
Default NaN
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOM
Related SIMMODE
Parameters
Remarks When SIMMODE = SimValSub, the PV is substituted with SIMVALUE. SIMVALUE
can be fetched from another block using a parameter connection or it can be set by
an operator or the ShadowPlant application. Reading SIMVALUE always returns
the value of PV. Writing SIMVALUE returns an error if SIMMODE does not equal
SimValSub.

- 2864 -
Chapter 21 - Sxxxx Parameters

21.214 SIMVALUE[1..16]

Specific to PCDITEXTARRCH
Block(s)
Description Simulation Value
Data Type String
Range
Default 0
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related SIMMODE
Parameters
Remarks When SIMMODE = SimValSub, the PV is substituted with SIMVALUE. SIMVALUE
can be fetched from another block using a parameter connection or it can be set by
an operator or other applications. Reading SIMVALUE always returns the value of
PV. Writing SIMVALUE returns an error, if SIMMODE does not equal SimValSub.

21.215 SIMVALUE[1..120]

Specific to PCDINUMARRCH
Block(s)
Description Simulation Value
Data Type Float64
Range
Default 0
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related SIMMODE
Parameters
Remarks When SIMMODE = SimValSub, the PV is substituted with SIMVALUE. SIMVALUE
can be fetched from another block using a parameter connection or it can be set by
an operator or other applications. Reading SIMVALUE always returns the value of
PV. Writing SIMVALUE returns an error, if SIMMODE does not equal SimValSub.

- 2865 -
Chapter 21 - Sxxxx Parameters

21.216 SIMVALUEREAL

Specific to UIO - Series C DICHANNEL


Block(s)
Description Simulation Value
Data Type Float64
Range
Default NaN
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOM
Related SIMMODE
Parameters
Remarks When SIMMODE is equal to SimValSub, SIMVALUEREAL contains frequency for
pulse counting. SIMVALUEREAL can be fetched from another block using a
parameter connection or it can be set by an operator or the ShadowPlant
application. Reading SIMVALUEREAL always returns the frequency value for pulse
counting. Writing SIMVALUEREAL returns an error if SIMMODE does not equal to
SimValSub.

21.217 SIOPT

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Safety Interlock Option - Indicates what to do when Safety Interlock Flag (SIFL) is
On.
Data Type Enumeration BADCTLOPT
Range No_Shed (0): Does nothing. There is no change in the
behavior of the RegCtl block.
ShedHold (1): MODE is shed to Manual, MODEATTR
goes to Operator, external mode
switching is disabled, and OP is held at
the current value.
ShedLow (2): MODE is shed to Manual, MODEATTR
goes to Operator, external mode
switching is disalbed, and OP goes to
OPEXLOLM.
ShedHigh (3): MODE is shed to Manual, MODEATTR
goes to Operator, external mode
switching is disabled, and OP goes to
OPEXHILM.
ShedSafe (4): MODE is shed to Manual, MODEATTR
goes to Operator, external mode
switching is disabled, and OP goes to
SAFEOP.

- 2866 -
Chapter 21 - Sxxxx Parameters

Default ShedHold (1)


Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related ESWENB, MODE, MODEATTR, OP, SIFL, BADOCOPT
Parameters
Remarks The mode shed option configured in the SIOPT comes into effect whenever there is
an IO communication loss and a safety interlock condition occurs within the time
delay specified in the BADOCOPT parameter. However, if the BADCTLOPT is
configured as No_Shed, the mode shed occurs after the specified time delay.

21.218 SIPTYPE[0..7]

Specific to Chassis HART AO IOM


Block(s)
Description Output Range Mode
Data Type Enumeration of SIPTYPE
Range 4-20mA (0) -10/+10 V (1)
Default SIPTYPE_HART: 4mA_to_20mA (0)
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Note that when the HART Channel parameter is selected for a channel (HART
Channel parameter box is checked), the SIPTYPE becomes SIPTYPE_HART. This is
because HART is available only in CURRENT mode. The SIPTYPE can be changed to
VOLTAGE mode only when the respective HART Channel parameter box is not
checked.

21.219 SIPTYPE[0..numChans-1]

Specific to AIM, AOM


Block(s)
Description Channel Type / Range Mode
Data Type Enumeration: SIPTYPE Enumeration: RANGEMODE (8-channel AOM only)
Range SIPTYPE: 10V_Input (65) RTD_SIP (66) Thermocouple (67) 10V_Output (88) 4-
20mA_Cur (89) RANGEMODE: Voltage_Mode (0) Current Mode (1)

- 2867 -
Chapter 21 - Sxxxx Parameters

Default Specified appropriately on a per module basis.


Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks SIPTYPE is only configurable on an 8-channel AOM, which operates in both
current and voltage modes.

21.220 SLOT0[0..7]

Specific to Chassis HART AO IOM


Block(s)
Description This parameter is for configuring slot 0 variables to be fetched from a HART device.
The device variables in each HART device are given an index code. This parameter
must be configured by the user.
Data Type 16-Bit Integer
Range 0-255
Default 0 = no configuration
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Note that the SLOT parameter for SLOT0 should be set to a value other than zero.
A value of 0 indicates that the SLOT is not configured and it may give unpredictable
results.

21.221 SLOT1[0..7]

Specific to Chassis HART AO IOM


Block(s)
Description This parameter is for configuring the 2nd slot variable to be fetched from a HART
device. The device variables in each HART device are given an index code. This
parameter must be configured by the user.
Data Type 16-Bit Integer
Range 0-255
Default 0 = no configuration

- 2868 -
Chapter 21 - Sxxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Note that the SLOT parameter SLOT0 should be set to a value other than zero. A
value of 0 indicates that the SLOT is not configured and it may give unpredictable
results.

21.222 SLOT2[0..7]

Specific to Chassis HART AO IOM


Block(s)
Description This parameter is for configuring the 3rd slot variable to be fetched from a HART
device. The device variables in each HART device are given an index code. This
parameter must be configured by the user.
Data Type 16-Bit Integer
Range 0-255
Default 0 = no configuration
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Note that the SLOT parameter for SLOT0 and SLOT1 should be set to a value other
than zero. A value of 0 indicates that the SLOT is not configured and it may give
unpredictable results.

21.223 SLOT3[0..7]

Specific to Chassis HART AO IOM


Block(s)
Description This parameter is for configuring the 4th slot variable to be fetched from a HART
device. The device variables in each HART device are given an index code. This
parameter must be configured by the user.
Data Type 16-Bit Integer
Range 0 to 255
Default 0 = no configuration
Config Load Yes

- 2869 -
Chapter 21 - Sxxxx Parameters

Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Note that the SLOT parameter for SLOT0, SLOT1 and SLOT2 should be set to a
value other than zero. A value of 0 indicates that the SLOT is not configured and it
may give unpredictable results.

21.224 SLOT

Specific to Block(s) All EtherNet/IP ArmorPoint I/O modules


Description IOM Slot Number in the chassis
Data Type UINT8
Range
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks Represents the Slot number of this IOM/Adapter in the chassis.

Specific to Block(s) ControlLogixModule


Description Slot Number - This parameter represents the slot number of the PLC in the
chassis.
Data Type UINT 8
Range
Default
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks

- 2870 -
Chapter 21 - Sxxxx Parameters

21.225 SLOTNUM

Specific to Blocks HRBBOX_CB block and HRBBOX_EC block


Description Slot Number
Data Type UINT8
Range 1–8
Default 1
Config. Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related HMW
Parameters
Remarks This parameter is used to view the memory layout of that particular slot in
HMW.

Specific to HRBALG_REG block , HRBALG_DI block, HRBALG_AI block, HRBALG_PIUAI,


Blocks HRBALG_HLPIUAO, HRBALG_HLPIUDI, HRBALG_HLPIUDO, HRBALG_HLPIUCO,
HRBALG_HLPIUAC, HRBALG_HLPIUDC
Description Slot Number
Data Type UINT8
Range 1-8 for CB 1-16 for Regular HLPIU, LLPIU, and LEPIU 1-32 for Extended HLPIU,
LLPIU, and LEPIU
Default 1
Config. No
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter represents the slot number to which this algorithm belongs.

Specific to Blocks PB_EIP, CEEC300, CEEUOC


Description CLX Slot Number
Data Type UINT8
Range -
Default 0
Config. Load No
Active Loadable No

- 2871 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence NoLoad
Related Parameters -
Remarks Slot number of the Control Logix module mounted on a 1756 chassis.

21.226 SLOTNUMBER

Specific to Block CPM, RM, IOLIM, FTEB


(s)
Description Slot Number - Represents number of the slot in the chassis where the
module is installed.
Data Type 32-Bit Integer
Range 0 to 16
Default
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence SR
Related ABORTALM.PR
Parameters
Remarks Chassis slot numbering is zero based, starting from the left most slot.

Specific to Block(s) EIM EIP Protocol Block


Description CLX Slot Number
Data Type 8-Bit Integer
Range
Default 0
Config Load Yes
Active Loadable No
Access Lock Application Developer
Residence No Load
Related Parameters -
Remarks Slot number of the Control Logix module mounted on a 1756 chassis.

- 2872 -
Chapter 21 - Sxxxx Parameters

21.227 SLOTNUM[0-3]

Specific to Block(s) CEEFB


Description ControlLogix Slot Number — Indicates the slot number of the PLC in the
chassis.
Data Type INT16
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related ENETIPADDR
Parameters
Remarks The IP Address and Slot together form the unique communication path to
the PLC.

21.228 SLOTSFBT

Specific to All PM I/O Channels


Block(s)
Description Channel Soft Failures. Shows bit that represents one of the soft failure codes listed
in the Remarks row below.
Data Type Bit String
Range N/A
Default 0
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence IOP
Related
Parameters
Remarks The following Soft Failure Codes are presented for the associated I/O Processor
(IOP) block. 0: Null Soft Failure - Not Used. 7: EEPROM checksum error or IOP not
calibrated. 8: EEPROM counter error - too many writes or unformatted EEPROM. 21:
Input point failed diagnostic. 23: Failure in input circuitry detected by AO or DO. 29:
Bad input or bad FTA plug-in module. 31: FTA type mismatch with slot configuration.
35: Illegal internal zero configuration attempted on this channel. 36: *** Spare
failure indicator *** 37: *** Spare failure indicator *** 38: Calibration of this slot has
aborted. 42-80: A/D slot conversion on AIM slot underflowed minimum allowed
count.

- 2873 -
Chapter 21 - Sxxxx Parameters

Specific to Block(s) All Series C I/O Modules


Description Channel Soft Failures
Data Type Bit String
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks Each bit represents one of the Soft Failures listed in the Series C IO User's
Guide.

21.229 SLOT0BOARDSTATUS

Specific to Block(s) ELCN_NODE

Description Slot 0 board has failed

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related Parameters ELCN_NODE- ELCN Node Statustab

Remarks

- 2874 -
Chapter 21 - Sxxxx Parameters

21.230 SLOT0SELFTEST

Specific to Block(s) ELCN_NODE

Description Slot 0 board has passed self-test.

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related Parameters ELCN_NODE- ELCN Node Statustab

Remarks

21.231 SLOT0STATUS

Specific to ELCN_NODE
Block(s)

Description Slot 0 registers

Data Type String

Range Length: 40 Characters maximum

Default NULL

Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks This data reflects the slot register contents for each of the emulated slots. During
operations, the register contents change at a very high rate, but the data is updated only
at the designated refresh rate. Slot Register data is of a diagnostic nature and is normally
of use only to Honeywell Field Service personnel.

- 2875 -
Chapter 21 - Sxxxx Parameters

21.232 SLOT0TS

Specific to PMIO:HAICHANNEL Series C I/O: HAOCHANNEL, HAICHANNEL


Block
Description Slot 0 Data Time Stamp
Data Type TIME
Range 00:00:00 to 23:59:59
Default 00:00:00
Config Load No
Active No
Loadable
Access Lock View Only
Residence IOM
Related Command 9 parameters
Parameters
Remarks Time stamp of HART device/dynamic variable read. Time stamp is monotonic and
rollovers or resets every 24 hours.

21.233 SLOT0TYPE

Specific to Block(s) ELCN_NODE (ENIM)

Description The type of board that is installed in slot 0.

Data Type String

Range Length: 10 Characters maximum

Default “NONE”

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_NODE

Related Parameters ELCN_NODE- ELCN Node Statustab

Remarks

- 2876 -
Chapter 21 - Sxxxx Parameters

21.234 SLOT2BOARDSTATUS

Specific to Block(s) ELCN_NODE

Description Slot 2 board has failed. Slots 2-4 are the boards that are being emulated by the
device.

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks

21.235 SLOT2SELFTEST

Specific to Block ELCN_NODE


(s)

Description Slot 2 board has passed self test. Slots 2-4 are the boards that are being emulated
by the device.

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks

- 2877 -
Chapter 21 - Sxxxx Parameters

21.236 SLOT2STATUS

Specific to ELCN_NODE
Block(s)

Description Slot 2 registers. Slots 2-4 are the boards that are being emulated by the device.

Data Type String

Range Length: 40 Characters maximum

Default NULL

Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks This data reflects the slot register contents for each of the emulated slots. During
operations, the register contents change at a very high rate, but the data is updated only
at the designated refresh rate. Slot Register data is of a diagnostic nature and is normally
of use only to Honeywell Field Service personnel.

21.237 SLOT2TYPE

Specific to ELCN_NODE (ENIM)


Block(s)

Description The type of board that is installed in slot 2. Slots 2-4 are the boards that are being
emulated by the device.

Data Type String

Range Length: 10 Characters maximum

Default “NONE”

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_NODE

Related ELCN_NODEELCN Node Statustab


Parameters

Remarks

- 2878 -
Chapter 21 - Sxxxx Parameters

21.238 SLOT3BOARDSTATUS

Specific to Block(s) ELCN_NODE

Description Slot 3 board has failed. Slots 2-4 are the boards that are being emulated by the
device.

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks

21.239 SLOT3SELFTEST

Specific to Block ELCN_NODE


(s)

Description Slot 3 board has passed self test. Slots 2-4 are the boards that are being emulated
by the device.

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks

- 2879 -
Chapter 21 - Sxxxx Parameters

21.240 SLOT3STATUS

Specific to ELCN_NODE
Block(s)

Description Slot 3 registers. Slots 2-4 are the boards that are being emulated by the device.

Data Type String

Range Length: 40 Characters maximum

Default NULL

Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks This data reflects the slot register contents for each of the emulated slots. During
operations, the register contents change at a very high rate, but the data is updated only
at the designated refresh rate. Slot Register data is of a diagnostic nature and is normally
of use only to Honeywell Field Service personnel.

21.241 SLOT3TYPE

Specific to ELCN_NODE (ENIM)


Block(s)

Description The type of board that is installed in slot 3. Slots 2-4 are the boards that are being
emulated by the device.

Data Type String

Range Length: 10 Characters maximum

Default “NONE”

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_NODE

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks

- 2880 -
Chapter 21 - Sxxxx Parameters

21.242 SLOT4BOARDSTATUS

Specific to Block(s) ELCN_NODE

Description Slot 4 board has failed. Slots 2-4 are the boards that are being emulated by the
device.

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks

21.243 SLOT4SELFTEST

Specific to Block ELCN_NODE


(s)

Description Slot 4 board has passed self test. Slots 2-4 are the boards that are being emulated
by the device.

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks

- 2881 -
Chapter 21 - Sxxxx Parameters

21.244 SLOT4STATUS

Specific to ELCN_NODE
Block(s)

Description Slot 4 registers. Slots 2-4 are the boards that are being emulated by the device.

Data Type String

Range Length: 40 Characters maximum

Default NULL

Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks This data reflects the slot register contents for each of the emulated slots. During
operations, the register contents change at a very high rate, but the data is updated only
at the designated refresh rate. Slot Register data is of a diagnostic nature and is normally
of use only to Honeywell Field Service personnel.

21.245 SLOT4TYPE

Specific to ELCN_NODE (ENIM)


Block(s)

Description The type of board that is installed in slot 4. Slots 2-4 are the boards that are being
emulated by the device.

Data Type String

Range Length: 10 Characters maximum

Default “NONE”

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_NODE

Related ELCN_NODE- ELCN Node Statustab


Parameters

Remarks

- 2882 -
Chapter 21 - Sxxxx Parameters

21.246 SLOT5BOARDSTATUS

Specific to Block(s) ELCN_NODE

Description Slot 4 board has failed

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related Parameters ELCN_NODE- ELCN Node Statustab

Remarks

21.247 SLOT5SELFTEST

Specific to Block(s) ELCN_NODE

Description Slot 4 board has passed self test

Data Type Boolean

Range True or False

Default F

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence Residency is the platform to which the tagged block is configured and loaded.

Related Parameters ELCN_NODE ELCN Node Status page

Remarks

- 2883 -
Chapter 21 - Sxxxx Parameters

21.248 SLOT5STATUS

Specific to ELCN_NODE
Block(s)

Description Slot 4 registers

Data Type String

Range Length: 40 Characters maximum

Default NULL

Config No
Load

Active No
Loadable

Access ViewOnly
Lock

Residence Residency is the platform to which the tagged block is configured and loaded.

Related ELCN_NODE ELCN Node Status page


Parameters

Remarks This data reflects the slot register contents for each of the emulated slots. During
operations, the register contents change at a very high rate, but the data is updated only
at the designated refresh rate. Slot Register data is of a diagnostic nature and is normally
of use only to Honeywell Field Service personnel.

21.249 SLOT5TYPE

Specific to Block(s) ELCN_NODE(ENIM)

Description The type of board that is installed in slot 4

Data Type String

Range Length: 10 Characters maximum

Default “NONE”

Config Load No

Active Loadable No

Access Lock ViewOnly

Residence ELCN_NODE

Related Parameters ELCN_NODE ELCN Node Status page

Remarks

- 2884 -
Chapter 21 - Sxxxx Parameters

21.250 SLOTTYPE

Specific to HRBALG_REG block, HRBALG_AI block, HRBALG_DI blockHRBALG_PIUAI,


Blocks HRBALG_HLPIUAO, HRBALG_HLPIUDI, HRBALG_HLPIUDO, HRBALG_HLPIUCO,
HRBALG_HLPIUAC, HRBALG_HLPIUDC
Description Slot Type
Data Type Enumeration
Range 0 - None 1 - AI 2 - AO 3 - DI 4 - DO 5 - DC 6 - REGCTL 7 - COUNTER 8 - TIMER 9 -
FLAG 10 - NUMERIC 11 - PROCMODULE 12- LOGIC 13 - CTLCOUNTER 14 -
BATCHASSIGN 15 - AC
Default 0 None
Config. No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This parameter represents the algorithm block type for which the slot is configured.

21.251 SLOTNUM

Specific to Block All I/O Module Function Blocks.


(s)
Description Slot Number
Data Type UNIT16
Range 1-32767
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related SUBSLOTNUM
Parameters
Remarks Slot number of submodule. This is same as configured in tool. Cannot be
changed from form.

- 2885 -
Chapter 21 - Sxxxx Parameters

21.252 SLOWSTEPTIMR[1..24]

Specific to Block QIPACTERM


Description Time Until Slow Step Timer Expires in Seconds
Data Type 32-Bit Integer
Range 0-65535
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This is the value in the input assembly for the designated position [1-24].

21.253 SLOWSTEPTIMR[1..200]

Specific to Block QIPACCHAN


Description Time Until Slow Step Timer Expires in Seconds
Data Type Float64
Range N/A
Default NAN
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value in the input assembly for the designated channel [1-200] in
the QiMPACT cluster.

21.254 SLWFLSHSPD

Specific to Block(s) ANNPANEL


Description Speed of the slow flash in blinks per min
Data Type Enumeration
Range 30_BlinksPerMin, 37_BlinksPerMin
Default 30_BlinksPerMin
Config Load YES
Active Loadable No

- 2886 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related Parameters FSTFLSHSPD
Remarks Determines the slow flashing speed of the Alarm window in blinks per
minute.

21.255 SNTPADDRESS

Specific to Block(s) Primary C300 and FIM4 FBs


Description SNTP Address - Indicates the IP address of SNTP server (it may not be an
FTE device)
Data Type String
Range Length: 15 Characters
Default 0.0.0.0
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence C300, FIM4
Related
Parameters
Remarks

21.256 SNTP1ADDR

Specific to Block(s) C300 FBs


Description SNTP Server 1 IP Address
Data Type String
Range Length: 15 Characters
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300
Related Parameters C300MINTEMP [1...3], SNTPSTAT
Remarks

- 2887 -
Chapter 21 - Sxxxx Parameters

21.257 SNTP2ADDR

Specific to Block(s) C300 FBs


Description SNTP Server 2 IP Address
Data Type String
Range Length: 15 Characters
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300
Related Parameters C300MINTEMP [1...3], SNTPSTAT
Remarks

21.258 SNTPSKEWTHLD

Specific to C300, FIM4 FBs, PGM, EHPM


Block(s)
Description SNTP Skew Limit (msec) - Sets the maximum skew tolerated between the module
clock and SNTP time under which gradual correction of the module clock is allowed.

Data Type 32-bit unsigned integer


Range
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related MAXSNTPSKEW, NUMSNTPSKEWEX
Parameters
Remarks When the difference between the module clock and SNTP time exceeds the value
of SNTPSKEWTLHD, the module clock will be adjusted with a one time,
discontinuous jump. SNTPSKEWTLHD limit is 5 Minutes.

- 2888 -
Chapter 21 - Sxxxx Parameters

21.259 SNTPSTAT

Specific to C300, FIM4, PGM, EHPM


Block(s)
Description SNTP Status
Data Type Enumeration
Range ------- (0) - Default on project side NotActive (1) - Currently SNTP is not the time
source NoServer (2) - No SNTP server available SNTP1 (3) - SNTP Server 1 is active
SNTP2 (4) - SNTP Server 2 is active
Default -------
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related C300MINTEMP [1...3]
Parameters
Remarks

21.260 SO

Specific to Timer, Transition


Block(s)
Description Timer Status Output - Indicates when the timer has expired.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PV, RV, SP.
Parameters
Remarks SO is set to On when the timer expires, (that is, PV = SP). SO is returned to Off
when the timer is reset.

Specific to Block(s) DOC


Description Status Output
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No

- 2889 -
Chapter 21 - Sxxxx Parameters

Active Loadable No
Access Lock Operator
Residence IOP
Related Parameters DOMSO[0..numChans-1]
Remarks

Specific to Block Pulse Input w/ Fast Cutoff IOC


(s)
Description Output State - Indicates current state of the Output associated with the Pulse
Input channel.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to Series C PICHANNEL


Block(s)
Description Status Output State
Data Type BOOLEAN
Range OFF (0) ON (1)
Default OFF
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related BADSOSAFEOUTPUTSOSO
Parameters
Remarks SO indicates the current state of the fast cutoff output screw value associated
with the pulse input channel.
l OFF indicates the current state of the output screw is de-energized.
l ON indicates the current state of the output screw is energized.

Specific to DOCHANNEL (PM I/O) DOCHANNEL (Series C I/O)


Block(s)
Description Status Output. Specifies the state of the status output from a digital output point as
On or Off.
Data Type Boolean
Range 0 0ff Field contact is to be de-

- 2890 -
Chapter 21 - Sxxxx Parameters

energized.
1 On Field contact is to be
energized.
Default Off
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOM
Related SOINITVAL
Parameters
Remarks This parameter is the output from a digital output point.
l When the channel is configured as STATUS and the SO pin is connected to a
Function Block, the value indicates the fetched value from the upstream
Function Block. The SO value can only be changed by changing the value in
the upstream Function Block.
l When the channel is configured as STATUS and either the ONPULSE or
OFFPULSE pins are connected to a Function Block, storing to SO will be
rejected. The value shows OFF for ONPULSE configuration, and ON for
OFFPULSE configuration.
l When the channel is configured as STATUS and SO, ONPULSE, and
OFFPULSE are not connected to a Function Block, the user can store a value
to this parameter and control the Status Output. The value indicates the
current Status Output status.
l When the channel is configured as PWM, the user cannot write to SO. The
value indicates OFF.
l When the channel's REDTAG parameter is On the Status Output is frozen at
its last value.

21.261 SO[1..NUMCHAN]

Specific to Block(s) DO16, DO32


Description Status Output
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Operator
Residence IOP
Related Parameters DOMSO[0..numChans-1]
Remarks

- 2891 -
Chapter 21 - Sxxxx Parameters

21.262 SO[6..7]

Specific to Pulse Input IOM


Block(s)
Description Output State - Indicates current state of the Output associated with the Pulse Input
Channel.
Data Type Boolean
Range Off (0): Current state of the output screw is de-energized. On (1): Current state of
the output screw is energized.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SO
Parameters
Remarks This parameter can be set from the Control Builder configuration form. Writing this
parameter overrides any SO set from the associated PI channel with fast cutoff
block.

21.263 SOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK]

Specific to RampSoak
Block(s)
Description Soak Time (in Minutes) - The target soak times, specified by the user. There is one
soak time per Ramp/Soak pair.
Data Type Real
Range 0.0 to 7200.0
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related NUMRAMPSOAK[1..NUMPROFILES], RAMPRATE[1..NUMPROFILES]
Parameters [1..NUMRAMPSOAK], SOAKVAL[1..NUMPROFILES][1..NUMRAMPSOAK], STARTOP
[1..NUMPROFILES], STARTSEG[1..NUMPROFILES].
Remarks

- 2892 -
Chapter 21 - Sxxxx Parameters

21.264 SOAKVAL[1..NUMPROFILES][1..NUMRAMPSOAK]

Specific to RampSoak
Block(s)
Description Soak Value (in Engineering Units) - The target soak values, specified by the user.
There is one soak value per Ramp/Soak pair.
Data Type Real
Range N/A
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Supervisor
Residence CEE
Related NUMRAMPSOAK[1..NUMPROFILES], RAMPRATE[1..NUMPROFILES]
Parameters [1..NUMRAMPSOAK], SOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK], STARTOP
[1..NUMPROFILES], STARTSEG[1..NUMPROFILES].
Remarks

21.265 SOCMDOFF

Specific to Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Command Status Output Off - storing On to this parameter will cause the Output
associated with the Pulse Input channel to be set Off; reading this parameter
always returns a value of Off.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related SO
Parameters
Remarks

Specific to Series C PICHANNEL


Block(s)
Description SO Command OFF
Data Type BOOLEAN
Range OFF (0) ON (1)

- 2893 -
Chapter 21 - Sxxxx Parameters

Default OFF (0)


Config Load No
Active No
Loadable
Access Lock Operator
Residence IOM
Related SO
Parameters
Remarks SOCMDOFF provides a command status to indicate whether the output channel in
the associated pulse input device is to be commanded OFF. Storing ON sets the SO
state to OFF.

21.266 SOCMDON

Specific to Pulse Input w/ Fast Cutoff IOC


Block(s)
Description Command Status Output On - storing On to this parameter will cause the Output
associated with the Pulse Input channel to be set On; reading this parameter
always returns a value of On.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related SO
Parameters
Remarks

Specific to Series C PICHANNEL


Block(s)
Description SO Command ON
Data Type BOOLEAN
Range OFF (0) ON (1)
Default OFF (0)
Config Load No
Active No
Loadable

- 2894 -
Chapter 21 - Sxxxx Parameters

Access Lock Operator


Residence IOM
Related SO
Parameters
Remarks SOCMDON provides a command status to indicate whether the output channel in
the associated pulse input device is to be commanded ON. Storing ON sets the SO
state to ON.

21.267 SOESDENUM

Specific to Block(s) EIM


Description SOE Enum value
Data Type SDENUM
Range
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

21.268 SOESTDESC

Specific to Block(s) EIM


Description State Description
Data Type STRING
Range NA
Default
Config Load
Active Loadable No
Access Lock AppDevOnly
Residence SR
Related Parameters
Remarks

- 2895 -
Chapter 21 - Sxxxx Parameters

21.269 SOFTFAIL

Specific to C300, FIM4, PGM, , EHPM, TCMI


Block(s)
Description Soft Failures present - Indicates the Soft Fail state at the C300 Controller or FIM4
level. (See Soft Failures tab for details)
Data Type Boolean
Range On - One or more Soft Failures occurred or exists. Off - No Soft Failure.
Default Off
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence C300, FIM4, PGM, EHPM
Related WDTHWFAIL, WDTSWFAIL, ROMBOOTIMGCHKSMFAIL, ROMAPPIMGCHKSMFAIL,
Parameters IOL2SOFTFAIL, IOL1SOFTFAIL, IOL1SOFTFAIL, BCDSWSTS,
BATTERYNOTOKSFTAB, BACKUPRAMSCRUBERRS, BACKUPRAMSWEEPERR,
BATTERYNOTOK, RAMSCRUBERRS, RAMSWEEPERR
Remarks SOFTFAIL derives it's state from the parameters listed in Related Parameters.

Specific to Block(s) EIM


Description Soft Failures
Data Type BOOLEAN or ENUM
Range NA
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks True if one or more soft failure diagnostics are detected.

Specific to Block UOC


(s)
Description Soft Failures Present (See Soft Failures Tab for details)
Data Type BOOLEAN
Exposure
Range N/A
Default OFF
Config Load No
Active Loadable

- 2896 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence NOLOAD
Related
Parameters
Remarks Indicates one or more soft failure conditions is active. See the soft failures tab
for details.

21.270 SOFTFAIL1A

Specific to Block All IOM Blocks


(s)
Description Primary IOM Block Soft Failure
Data Type Bit String
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks Each bit represents one of the Soft Failures listed in the PM I/O and Series C
I/O soft failure codes.

21.271 SOFTFAIL2A

Specific to Block All IOM Blocks


(s)
Description Primary IOM Block Soft Failure
Data Type Bit String
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks Each bit represents one of the Soft Failures listed in the PM I/O and Series C
I/O soft failure codes.

- 2897 -
Chapter 21 - Sxxxx Parameters

21.272 SOFTFAIL1B

Specific to Block All IOM Blocks


(s)
Description Secondary IOM Block Soft Failure
Data Type Bit String
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks Each bit represents one of the Soft Failures listed in the PM I/O and Series C
I/O soft failure codes.

21.273 SOFTFAIL2B

Specific to Block All IOM Blocks


(s)
Description Secondary IOM Block Soft Failure
Data Type Bit String
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks Each bit represents one of the Soft Failures listed in the PM I/O and Series C
I/O soft failure codes.

- 2898 -
Chapter 21 - Sxxxx Parameters

21.274 SOFTWAREREV[0..7]

Specific to Chassis HART AI IOM, HART AO IOM


Block(s)
Description Software Revision Number- Indicates the software revision number of the HART
device connected to the channel.
Data Type 8-Bit Unsigned Integer
Range 0 to 255
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

21.275 SOINITVAL

Specific to DOCHANNEL (PM I/O) DOCHANNEL (Series C I/O)


Block(s)
Description SO Initialize Value. This is the field output value of the DOCHANNEL.
Data Type Boolean
Range Off Field contact is to be de-energized.
On Field contact is to be energized.
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related SO
Parameters
Remarks This parameter is the field output value of this channel. The data reflects the actual
IOM output for both STATUS and PWM configurations.

- 2899 -
Chapter 21 - Sxxxx Parameters

21.276 SOINITVAL[1..NUMCHAN]

Specific to Block(s) DO16, DO32


Description Status Echoback Value
Data Type Boolean
Range Off: Field contact is to be de-energized. On: Field contact is to be energized.
Default Off
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOP
Related SO
Parameters
Remarks The data reflects the actual IOP output for both STATUS and PWM
configurations.

21.277 SOREADFAIL

Specific to DOC, DO16, DO32; DOCHANNEL (Series C I/O)


Block(s)
Description SO Initialize Value Invalid
Data Type Boolean
Range 0 Off The SO data for the channel was
successfully read.
1 On Error occurred upon reading the SO
data from the IOM.
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is only valid
for Status types.

- 2900 -
Chapter 21 - Sxxxx Parameters

21.278 SOSOURCE

Specific to Block(s) DOC


Description Timer Status Output (SO) Source Connector
Data Type
Range
Default
Config Load
Active Loadable No
Access Lock Application Developer
Residence
Related Parameters
Remarks

21.279 SOSTS

Specific to Block(s) Pulse Input w/ Fast Cutoff IOC


Description Status of Output (SO)
Data Type Boolean
Range Good (0) Bad (1)
Default Good (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters SO
Remarks

21.280 SLWSRCID

Specific to Block AICHANNEL, HAICHANNEL (PM I/O)


(s)
Description Slidewire Voltage Source Identifier: Defines the slot number of the voltage
source for the slidewire.
Data Type Integer
Range 1 to 16
Default 1
Config Load No
Active Loadable No

- 2901 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence IOP
Related
Parameters
Remarks The SENSRTYP must equal Slidewire. This parameter is currently not
supported.

21.281 SP

Specific to Block(s) PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Description Setpoint Value (in Engineering Units)
Data Type 64-Bit Real Number
Range SPLOLM to SPHILM
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters
Remarks SP is an initializable input for all function blocks

Specific to Block(s) RATIOCTL


Description Setpoint Value - Defines target ratio between X1 and X2 inputs.
Data Type Float64
Range SPLOLM to SPHILM
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters SPHILM SPLOLM
Remarks

- 2902 -
Chapter 21 - Sxxxx Parameters

Specific to Block Timer


(s)
Description Preset Time Value - Sets the amount of time that the Timer function block is to
run.
Data Type Integer
Range Determined by TIMEBASE parameter selection.
If TIMEBASE is set to ... SP Range is...

Seconds 0 to 4,294,947
Minutes 0 to 71,581
Cycles 0 to 2,147,483,647 (2^31-1)
Default 0
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related PV RV SO TIMEBASE
Parameters
Remarks SP limit is determined by TIMEBASE units selection, but not to exceed
equivalent of 49.71 days.

Specific to HRBALG_HLPIUCO
Block(s)
Description Set Point
Data Type FLOAT64
Range
Default 0.0
Config Yes
Load
Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter maps to the PRESET (SP) parameter of a COUNTER16 point. The
value displayed is the scaled value based on the scaling factor (AVCONV)
configuration This value is not displayed for a 32-bit counter as this parameter is
not applicable for a 32-bit counter.

- 2903 -
Chapter 21 - Sxxxx Parameters

21.282 SP1FASTFEED[1..4]

Specific to JAGXCHAN
Block(s)
Description Setpoint 1 Fast Feeding
Data Type Boolean
Range Off(0) Not Fast Feeding
On(1) Fast Feeding
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 2 of the status word in the floating point input assembly for
the designated scale slot [1..4].

21.283 SP2FASTFEED[1..4]

Specific to JAGXCHAN
Block(s)
Description Setpoint 2 Fast Feeding
Data Type Boolean
Range Off(0) Not Fast Feeding
On(1) Fast Feeding
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 3 of the status word in the floating point input assembly for
the designated scale slot [1..4].

- 2904 -
Chapter 21 - Sxxxx Parameters

21.284 SP1FEEDING[1..4]

Specific to JAGXCHAN
Block(s)
Description Setpoint 1 Feeding
Data Type Boolean
Range Off(0) Not Feeding
On(1) Feeding
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 0 of the status word in the floating point input assembly for
the designated scale slot [1..4].

21.285 SP2FEEDING[1..4]

Specific to JAGXCHAN
Block(s)
Description Setpoint 2 Feeding
Data Type Boolean
Range Off(0) Not Feeding
On(1) Feeding
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 1 of the status word in the floating point input assembly for
the designated scale slot [1..4].

- 2905 -
Chapter 21 - Sxxxx Parameters

21.286 SP1TOLERANCE[1..4]

Specific to JAGXCHAN
Block(s)
Description Setpoint 1 In Tolerance
Data Type Boolean
Range Off(0) Not in Tolerance
On(1) In Tolerance
Default Off
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks This is the value of bit 4 of the status word in the floating point input assembly for
the designated scale slot [1..4].

21.287 SPCODESIZE

Specific to Step Block


Block(s)
Description Number of Pcode Bytes for Stop Condition expression. Represents number of bytes
required for the Psuedo code of the Step-specific Stop Condition expression.
Data Type Integer32
Range 0 to 200
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence ACE, C200, SIM_C200
Related SCNUMSRCCONN
Parameters
Remarks

- 2906 -
Chapter 21 - Sxxxx Parameters

21.288 SPCONN

Specific to PID, PIDFF, PosProp


Block(s)
Description This is an internal parameter for system use only.
Data Type Depending on the order in which blocks are loaded, the following status may be
returned for this parameter: “Referenced FB Not Found”. This indicates that a
function block was referenced which has not yet been loaded to the controller.
When this happens, no action is required except to load the referenced block before
putting the strategy on control.
Range
Default
Config
Load
Active No
Loadable
Access Lock
Residence
Related
Parameters
Remarks

21.289 SPECIALTYPE

Specific to UAI
Block(s)

Description Special Type


Data Type ENUM
Range
0 Carbon(0_1250_mV)

1 Oxygen(-30_510_mV)

Default 0 Carbon(0_1250_mV)
Config Yes
Load

Active No
Loadable

- 2907 -
Chapter 21 - Sxxxx Parameters

Access Application Developer


Lock

Residence IOM Block


Related SENSRTYP_AI_C
Parameters

Remarks This parameter defines the type of Linear Signal connected. This parameter is exposed
when SENSRTYP_AI_C is set to SPECIAL.
The user is always provided with the list of valid values for the particular AI sensor type.
The user is NEVER shown or given the opportunity to select an invalid value.

21.290 SPECIFICVOLUME

Specific to Block(s) Steam Property Block


Description Specific Volume (V) value
Data Type ENUM
Range m3/kg SI Unit
m3/kg Metric Unit
ft3/lb Eng Unit
Default m3/kg
Config Load No
Access Lock Engineer
Active Loadable No
Residence CEE
Related Parameters
Remarks

21.291 SPECIFICVOLUMEENGUNIT

Specific to Block(s) Steam Property Block


Description Specific Volume (V) Engineering Unit
Data Type IEEE_FLOAT64
Range Any Real Number
Default IEEENaN
Config Load No
Access Lock Engineer or CONTCONTROL
Active Loadable No
Residence NO LOAD
Related Parameters
Remarks

- 2908 -
Chapter 21 - Sxxxx Parameters

21.292 SPECIFICVOLUMEIO

Specific to Block(s) Steam Property Block


Description Specific Volume (V) IO Configuration
Data Type ENUM
Range Input Parameter configured as Input
Output Parameter configured as Output
Not Configured Parameter configured as None
Default Not Configured
Config Load Yes
Access Lock Application Developer Only
Active Loadable No
Residence CEE
Related Parameters
Remarks

21.293 SPEM

Specific to Block(s) HRBALG_PIUAI


Description PV Target val in EUs
Data Type FLOAT64
Range N/A
Default NaN
Config Load No
Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters -
Remarks -

21.294 SPEUHI

Specific to PID, PIDER, PIDFF, PID-PL, PosProp


Block(s)
Description Set Point (SP) High Range (in Engineering Units) - This value corresponds to
100% of full-scale value.
Data Type 64-Bit Real Number
Range Same as PVEUHI
Default Same as PVEUHI

- 2909 -
Chapter 21 - Sxxxx Parameters

Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PVEUHIPVEULO, SPEULO
Parameters
Remarks SPEUHI tracks PVEUHI

Specific to ENGREGCALC
Block(s)
Description Set Point (SP) High Range (in Engineering Units) - Specifies set point high
range value in Engineering Units.
Data Type 64-Bit Real Number
Range Greater than SPEULO
Default 100.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SP SPEULO
Parameters
Remarks

21.295 SPEULO

Specific to Block PID, PIDER, PIDFF, PID-PL, PosProp


(s)
Description Set Point (SP) Low Range (in Engineering Units) - This value corresponds to
0% of full-scale value.
Data Type 64-Bit Real Number
Range Same as PVEULO
Default Same as PVEULO
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related PVEUHIPVEULO, SPEUHI
Parameters
Remarks SPEULO tracks PVEULO.

- 2910 -
Chapter 21 - Sxxxx Parameters

Specific to ENGREGCALC
Block(s)
Description Set Point (SP)(Low Range (in Engineering Units) - Specifies set point low range
value in Engineering Units.
Data Type 64-Bit Real Number
Range SPLOLM to SPHILM
Default 0.0
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SP SPEUHI
Parameters
Remarks

21.296 SPFORMAT

Specific to Block(s) PID, PIDFF, PosProp


Description Set Point Display Format
Data Type Enumeration PVFORMAT
Range D0 (0) D1 (1) D2 (2) D3 (3)
Default D1 (1)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence
Related Parameters PVFORMAT
Remarks

21.297 SPHI

Specific to PID-PL
Block(s)
Description Setpoint High - Upper range limit when controlling PV within a range.
Data Type Float64
Range SPLO - SPHILM
Default 0
Config Load Yes
Active No

- 2911 -
Chapter 21 - Sxxxx Parameters

Loadable
Access Lock Operator
Residence CEE
Related CTRLMODE SPLO
Parameters
Remarks This parameter is applicable only when CTRLMODE is RANGE. This parameter is
applicable only when CTLEQN is set to Profit Loop PKS, and is ignored in PID
control equations.

21.298 SPHIACTIVE

Specific to PID-PL
Block(s)
Description Active SP High Limit - Upper SP limit used by the Profit Loop PKS control algorithm.
This value may differ from the user-entered limit, SPHI, while ramping the SPHI
limit.
Data Type Float64
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SPHI
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

21.299 SPHIFL

Specific to PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Block(s)
Description Set Point (SP) High Limit Flag - Indicates if SP has exceeded its upper limit, as
specified by the Set Point High Limit (SPHILM).
Data Type Boolean
Range Off (0): SP high limit is not exceeded. On (1): SP high limit is exceeded.
Default Off (0)
Config Load No
Active No
Loadable

- 2912 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related SPHILM
Parameters
Remarks

21.300 SPHILM

Specific to Block PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


(s)
Description Set Point (SP) High Limit (in Engineering Units) - Defines the upper limit for
the SP value.
Data Type 64-Bit Real Number
Range NaN, or SPLOLM to PVEUHI
Default 100.00
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related SPHIFL
Parameters
Remarks Entering NaN disables SP limit checking, by forcing SPHILM to its extreme
value (PVEUHI).

21.301 SPHILMOPT

Specific to PID-PL
Block(s)
Description SP High Limit for Optimization
Data Type Float64
Range
Default
Config No
Load
Active No
Loadable

- 2913 -
Chapter 21 - Sxxxx Parameters

Access ViewOnly
Lock
Residence CEE
Related CTRLMODEOPTMODE SPHIOPTOFFSET SPLOLMOPT
Parameters
Remarks Profit Loop PKS can be configured to optimize the process over a limited operating
range. As a guard against process excursions, the range used for optimization,
SPLOLMOPT to SPHILMOPT, may be more restrictive than the normal control
range, SPLO to SPHI. SPHILMOPT is calculated as: SPHILMOPT = SPHI -
SPHIOPTOFFSET If a conflict exists between the OP optimization limits and the SP
optimization limits, the SP limits are enforced while the OP limits are ignored. This
parameter is applicable only when OPTMODE is other than NONE and CTRLMODE
is RANGE. This parameter is applicable only when CTLEQN is set to Profit Loop PKS,
and is ignored in PID control equations.

21.302 SPHIOPTOFFSET

Specific to PID-PL
Block(s)
Description SP High Limit Offset for Optimization
Data Type Float64
Range 0 to (SPEUHI - SPEULO)
Default 0
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related SPHI SPHILMOPT
Parameters
Remarks Profit Loop PKS can be configured to optimize the process over a limited operating
range. As a guard against process excursions, the range used for optimization,
SPLOLMOPT to SPHILMOPT, may be more restrictive than the normal control
range, SPLO to SPHI. SPHILMOPT is calculated as: SPHILMOPT = SPHI -
SPHIOPTOFFSET If a conflict exists between the OP optimization limits and the SP
optimization limits, the SP limits are enforced while the OP limits are ignored. This
parameter is applicable only when OPTMODE is other than NONE and CTRLMODE
is RANGE. This parameter is applicable only when CTLEQN is set to Profit Loop PKS,
and is ignored in PID control equations.

- 2914 -
Chapter 21 - Sxxxx Parameters

21.303 SPHIRAMPRATE

Specific to PID-PL
Block(s)
Description SPHI Ramp Rate, in Engineering Units/Minute - Ramp rate applied to external
(operator or program) changes in the upper control limit, SPHI.
Data Type Float64
Range >0, NaN
Default NaN
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related CTRLMODE SPHI SPHIACTIVE SPLORAMPRATE
Parameters
Remarks When the active high limit, SPHIACTIVE, is above the operator-set value, SPHI, the
active limit ramps toward SPHI at this specified rate. A one-shot jump in the active
limit toward the new SPHI limit is allowed if the jump is deemed to not adversely
impact control. Ramping proceeds from this point. This jump is automatic and
cannot be disabled by the end user. Setting the ramp rate to NaN disables ramping.
SPHI ramping is valid only when the CTRLMODE is set to RANGE control. This
parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is ignored
in PID control equations.

21.304 SPLO

Specific to PID-PL
Block(s)
Description Setpoint Low - Lower range limit when controlling PV within a range.
Data Type Float64
Range SPLOLM - SPHI
Default 0
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related CTRLMODE SPHI
Parameters
Remarks This parameter is applicable only when CTRLMODE is RANGE. This parameter is
applicable only when CTLEQN is set to Profit Loop PKS, and is ignored in PID
control equations.

- 2915 -
Chapter 21 - Sxxxx Parameters

21.305 SPLOACTIVE

Specific to PID-PL
Block(s)
Description Active SP Low Limit - Lower SP limit used by the Profit Loop PKS control algorithm.
This value may differ from the user-entered limit, SPLO, while ramping the SPLO
limit.
Data Type Float64
Range
Default
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SPHIACTIVE, SPLO.
Parameters
Remarks This parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is
ignored in PID control equations.

21.306 SPLOFL

Specific to PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Block(s)
Description Set Point (SP) Low Limit Flag - Indicates if SP has exceeded its lower limit, as
specified by the Set Point Low Limit (SPLOLM).
Data Type Boolean
Range Off (0): SP low limit not exceeded. On (1): SP low limit exceeded.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related SPLOLM
Parameters
Remarks

- 2916 -
Chapter 21 - Sxxxx Parameters

21.307 SPLOLM

Specific to Block PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


(s)
Description Set Point (SP) Low Limit (in Engineering Units) - Defines the lower limit for
the SP value.
Data Type 64-Bit Real Number
Range NaN, or PVEULO to SPHILM
Default 0.00
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related SPLOFL
Parameters
Remarks Entering NaN disables SP limit checking, by forcing SPLOLM to its extreme
value (PVEULO).

21.308 SPLOLMOPT

Specific to PID-PL
Block(s)
Description SP Low Limit for Optimization
Data Type Float64
Range
Default
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related CTRLMODEOPTMODE SPHILMOPT SPLOOPTOFFSET
Parameters
Remarks Profit Loop PKS can be configured to optimize the process over a limited operating
range. As a guard against process excursions, the range used for optimization,
SPLOLMOPT to SPHILMOPT, may be more restrictive than the normal control
range, SPLO to SPHI. SPLOLMOPT is calculated as: SPLOLMOPT = SPLO +
SPLOOPTOFFSET If a conflict exists between the OP optimization limits and the SP
optimization limits, the SP limits are enforced while the OP limits are ignored. This
parameter is applicable only when OPTMODE is other than NONE and CTRLMODE
is RANGE. This parameter is applicable only when CTLEQN is set to Profit Loop PKS,
and is ignored in PID control equations.

- 2917 -
Chapter 21 - Sxxxx Parameters

21.309 SPLOOPTOFFSET

Specific to PID-PL
Block(s)
Description SP Low Limit Offset for Optimization
Data Type Float64
Range 0 to (SPEUHI - SPEULO)
Default 0
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related SPLO SPLOLMOPT
Parameters
Remarks Profit Loop PKS can be configured to optimize the process over a limited operating
range. As a guard against process excursions, the range used for optimization,
SPLOLMOPT to SPHILMOPT, may be more restrictive than the normal control
range, SPLO to SPHI. SPLOLMOPT is calculated as: SPLOLMOPT = SPLO +
SPLOOPTOFFSET If a conflict exists between the OP optimization limits and the SP
optimization limits, the SP limits are enforced while the OP limits are ignored. This
parameter is applicable only when OPTMODE is other than NONE and CTRLMODE
is RANGE. This parameter is applicable only when CTLEQN is set to Profit Loop PKS,
and is ignored in PID control equations.

21.310 SPLORAMPRATE

Specific to PID-PL
Block(s)
Description SPLO Ramp Rate, in Engineering Units/Minute - Ramp rate applied to external
(operator or program) changes in the lower control limit, SPLO.
Data Type Float64
Range >0, NaN
Default NaN
Config Yes
Load
Active No
Loadable

- 2918 -
Chapter 21 - Sxxxx Parameters

Access Engineer
Lock
Residence CEE
Related CTRLMODE SPHIRAMPRATE SPLO SPLOACTIVE
Parameters
Remarks When the active low limit, SPLOACTIVE, is below the operator-set value, SPLO, the
active limit ramps toward SPLO at this specified rate. A one-shot jump in the active
limit toward the new SPLO limit is allowed if the jump is deemed to not adversely
impact control. Ramping proceeds from this point. This jump is automatic and
cannot be disabled by the end user. Setting the ramp rate to NaN disables ramping.
SPLO ramping is valid only when the CTRLMODE is set to RANGE control. This
parameter is applicable only when CTLEQN is set to Profit Loop PKS, and is ignored
in PID control equations.

21.311 SPOUT

Specific to UCNOUT, HIWAYOUT, REEOUT


Block(s)
Description Setpont Output - Indicates the setpoint value that is being stored to the Universal
Control Network (UCN) Process Manager control point SP parameter.
Data Type Float64
Range N/A
Default N/A
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ACE
Related RELEASEOPT MODEOUT, SPPIN
Parameters
Remarks

21.312 SPP

Specific to Block(s) PID, PIDFF, PosProp


Description Setpoint Value (in Percent)
Data Type 64-Bit Real Number
Range N/A
Default NaN
Config Load No
Active Loadable No

- 2919 -
Chapter 21 - Sxxxx Parameters

Access Lock Operator


Residence CEE
Related Parameters SP
Remarks

21.313 SPPIN

Specific to Block UCNOUT, HIWAYOUT, REEOUT


(s)
Description Setpoint in Percent Input - Shows the Setpoint value brought from the
primary in percent.
Data Type Float64
Range -6.9 to 106.9 percent
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence ACE
Related RELEASEOPT MODEOUTSPOUT
Parameters
Remarks

21.314 SPRATEREQ

Specific to PID, PIDFF, PosProp


Block(s)
Description Requested Set Point (SP) ramp rate (from Sequential Control Module (SCM)
Control Request)
Data Type 64-Bit Real Number
Range NaN, positive or negative Real number, or 0.0
Default 0.0
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related CONTROLREQLASTRATEREQ RESTARTOPT SCMOPT SPTVREQ
Parameters
Remarks A pending SPRATEREQ can be canceled by setting it to NaN. Operator change
requires MODEATTR = Operator. A SPRATEREQ should immediately be followed by
a SPTVREQ.

- 2920 -
Chapter 21 - Sxxxx Parameters

21.315 SPREQ

Specific to PID, PIDFF, PosProp


Block(s)
Description The requested SP(Set Point) value. The SCM CONTROLREQ wants a step-change
in the regulatory control block's SP.
Data Type 64-Bit Real Number
Range SPLOLM to SPHILM
Default 0
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related CONTROLREQ, LASTSPREQ, RESTARTOPT, SCMOPT.
Parameters
Remarks A pending SPREQ can be canceled by setting it to NaN. Operator change requires
MODEATTR = Operator.

21.316 SPTOL

Specific to Block(s) ENHREGCALC, RATIOCTL, PID, PID-PL, PIDER, PIDFF, POSPROP


Description Set Point (SP) Tolerance - Define tolerance value for SP input.
Data Type Float64
Range
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence C200
Related Parameters
Remarks

- 2921 -
Chapter 21 - Sxxxx Parameters

21.317 SPTV

Specific to PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Block(s)
Description Set Point (SP) Target Value (in Engineering Units) - Contains the target SP value
when SP ramping is being used.
Data Type 64-Bit Real Number
Range NaN or SPLOLM to SPHILM
Default N/A
Config No
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related SPTVP
Parameters
Remarks To invoke SP ramping, the user must store a target SP value (SPTV). Note: In order
to store the SPTV, target value processing must be enabled byt not running (that is,
SPTVOPT = Enable, and = Off or Preset). When SPTV is stored, and the function
block is active, the following will occur: The system calculates a ramp time
(SPTVTIME), based on the normal ramp rate. SPTVSTATE goes to Preset.

21.318 SPTVARWOPT

Specific to PID, PIDER, PID-PL, ENHREGCALC, POSPROP, RATIOCTL


Block(s)
Description Set Point (SP) Target Value Anti-Rest Windup (ARW) Option - Indicates if SP
ramping should pause on an ARW condition that continued ramping will not
correct.
Data Type Enumeration
Range 0 Disable Target value processing
should not pause on ARW.
1 Enable Target value processing
should pause on ARW.
Default Enable (1)
Config Load Yes
Active No
Loadable

- 2922 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related ARWNET[1..8] SPTVOPT SPTVSTATE
Parameters
Remarks This parameter is only available when SPTVOPT = Enable. If SPTVARWOPT = Enable
and SPTVSTATE = RUN, the SP will remain constant while one of the following
conditions exist:
l ARWNET = HI and SPTV is greater than SP
l ARWNET = LO and SPTV is less than SP
l ARWNET = HILO
You cannot change SPTVARWOPT setting when SPTVSTATE = RUN.

21.319 SPTVDEVFL

Specific to PID, PIDFF, PosProp


Block(s)
Description Set Point (SP) Target Value Deviation Flag - This flag is set to “On (1)” when the
difference between the Process Variable (PV) and the ramping SP is greater than
SPTVDEVMAX. While SPTVDEVMAX is exceeded, the ramping is temporarily
stopped. Ramping resumes once the difference between SP and PV is less than
SPTVDEVMAX.
Data Type Boolean
Range Off (0): Deviation is within limits. On (1): Deviation exceeds maximum; Set Point (SP)
ramping has temporarily stopped.
Default Off (0)
Config No
Load
Active No
Loadable
Access ViewOnly
Lock
Residence CEE
Related SPTVDEVMAX
Parameters
Remarks If the function block has a SP and PV input, the user can specify a maximum ramp
deviation (SPTVDEVMAX). If the maximum deviation is exceeded, SP ramping will
stop until PV catches up with the SP. SPTVDEVMAX is the maximum deviation
allowed during set point ramping, in engineering units/min. Guaranteed Maximum
Ramp processing works as follows: SPTVDEVMAX may be NaN or greter than zero.
NaN means “do not check ramp deviation”. If SPTVDEVMAX is not NaN, set point
ramping stops when the absolute value of the deviation (|PV - SP|) exceeds
SPTVDEVMAX. The deviation flag (SPTVDEVFL) is set, and SPTVSTATE remains in
Run. Ramping resumes as soon as the absolute value of the deviation returns
within the limit. When ramping resumes, the deviation flag (SPTVDEVFL) is reset.
Note: If the user has specified a ramp time, and ramping is interrupted by
Guaranteed Max Ramp processing, then the actual ramp time will be greater than
the user-specified time.

- 2923 -
Chapter 21 - Sxxxx Parameters

21.320 SPTVDEVMAX

Specific to PID, PIDFF, PosProp


Block(s)
Description Set Point (SP) Target Value Maximum Deviation - The maximum deviation allowed
during set point ramping, in engineering units.
Data Type 64-Bit Real Number
Range NaN, or greater than 0.0.
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SPTVDEVFL
Parameters
Remarks

21.321 SPTVNORMRATE

Specific to PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Block(s)
Description Set Point (SP) Target Value Normal Ramp Rate - The rate that the set point will
ramp, in engineering units/min.
Data Type 64-Bit Real Number
Range NaN, or greater than 0.0.
Default NaN
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related SPTVTIME
Parameters
Remarks This parameter allows the user to start SP ramping without having to specify a
ramp time. SPTVNORMRATE may be NaN or greater than zero. NaN means
“change immediately” (that is, ramp time = 0). If the function block has a SP and PV
input, specify a maximum deviation allowed between PV and SP during ramping
(SPTVDEVMAX).

- 2924 -
Chapter 21 - Sxxxx Parameters

21.322 SPTVOPT

Specific to PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Block(s)
Description Set Point (SP) Target Value Option - Indicates if SP target value processing is
requested.
Data Type Enumeration ENBSTATE
Range Disable (0): Target value processing is not requested.

Enable (1): Target value processing is requested.


Default Disable (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related SPTV, SPTVDEVMAX, SPTVNORMRATE, SPTVSTATE.
Parameters
Remarks To invoke SP ramping, the user must store a target SP value (SPTV). Note: In order
to store to SPTV, target value processing must be enabled but not running (that is,
SPTVOPT = Enable, and SPTVSTATE = Off or Preset). When SPTV is stored, and the
function block is active, the following will occur: The system calculates a ramp time
(SPTVTIME) based on the normal ramp rate. SPTVSTATE goes to Preset.

21.323 SPTVP

Specific to Block(s) PID, PIDFF, PosProp


Description Set Point (SP) Target Value (in Percent)
Data Type 64-Bit Real Number
Range NaN
Default N/A
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters SPTV
Remarks

- 2925 -
Chapter 21 - Sxxxx Parameters

21.324 SPTVRATE

Specific to Block(s) PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Description Set Point (SP) Target Value Ramp Rate (calculated)
Data Type 64-Bit Real Number
Range NaN
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters SPTVTIME
Remarks

21.325 SPTVREQ

Specific to PID, PIDFF, PosProp


Block(s)
Description Requested Set Point (SP) target value. The SCM sets a target value in regulatory
control block's SP in preparation for an SP ramp request.
Data Type 64-Bit Real Number
Range NaN, or SPLOLM to SPHILM
Default 0
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related SPRATEREQ
Parameters
Remarks A pending SPTVREQ can be canceled by setting it to NaN. Operator change
requires MODEATTR = Operator.

- 2926 -
Chapter 21 - Sxxxx Parameters

21.326 SPTVSTATE

Specific to PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Block(s)
Description Set Point (SP) Target Value Processor State - State of the ramping function. A
state of RUN(2) is required to start ramping.
Data Type Enumeration TVPROC
Range Off (0): No target value processing.
Preset (1): Set-up the SP target value and ramp
time.
Run (2): Perform the SP ramping function.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks Value will change to Preset (1), if the containing CM is inactivated or the CEE
transitions to Idle.

21.327 SPTVTIME

Specific to Block(s) PID, PIDER, PIDFF, PID-PL, PosProp, ENHREGCALC


Description Set Point (SP) Target Value Ramp Time in minutes
Data Type 64-Bit Real Number
Range Greater than or equal to 0.0.
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters SPTVRATE
Remarks

- 2927 -
Chapter 21 - Sxxxx Parameters

21.328 SRC

Specific to Auxcalc, Enhauxcalc, RegCalc


Block(s)
Description This is an internal parameter for system use only.
Data Type Depending on the order in which blocks are loaded, the following status may be
returned for this parameter: “Referenced FB Not Found”. This indicates that a
function block was referenced which has not yet been loaded to the controller.
When this happens, no action is required except to load the referenced block
before putting the strategy on control.
Range
Default
Config
Load
Active No
Loadable
Access Lock
Residence
Related
Parameters
Remarks

21.329 SRCDATA[0]

Specific to CAB types


Block(s)
Description Source Data. Parameter that holds a copy of the CAB source code. In Library and
Project view it reflects the latest CAB type code saved in ERDB. In Monitor view it
reflects the source code that is loaded and running in CEE. This can be cut and
pasted back into MSVS if you wish to recover code that was saved over.
Modification Definition of this parameter cannot be modified.
of Definition
Data Type BIGSTRING
Range Unlimited size string
Default None
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence ERDB Only
Related None
Parameters
Remarks

- 2928 -
Chapter 21 - Sxxxx Parameters

21.330 SRVACEHASBKP

Specific to
Block OPC Gateway
Description Server is ACE that has backup
Data Type BOOLEAN
Range OFF ON
Default OFF
Config
Load Yes
Active
Loadable Yes
Access Lock AppDevOnly
Residence CEE
Related
Parameters HOSTIPPRI, HOSTNAMEPRI

If this parameter is set to "TRUE," it indicates that the target server is an ACE that
has backup and is enabled for cut-over. In addition, the HOSTNAMEPRI is not
available for configuration and the floating IP of the server must be provided as
Remarks HOSTPRI value.

21.331 SRVHASBKP

Specific to
Block Inter Cluster Gateway
Description Server has backup
Data Type BOOLEAN
Range OFF ON
Default OFF
Config
Load Yes
Active
Loadable Yes
Access Lock AppDevOnly
Residence CEE
Related
Parameters HOSTIPPRI, HOSTNAMEPRI

If this parameter is set to "TRUE," it indicates that the target server has Backup and
is enabled for cut-over. In addition, the HOSTNAMEPRI is not available for
Remarks configuration and the floating IP of the server must be provided in HOSTPRI.

- 2929 -
Chapter 21 - Sxxxx Parameters

21.332 SSERROR

Specific to Block(s) ProfitCtl


Description SS Error
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

21.333 SSOBJECTIVEVALUE

Specific to Block(s) ProfitCtl


Description SS obj func value
Data Type FLOAT64
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters
Remarks

21.334 SSRECTOEQM

Specific to RCM
Block(s)
Description Recipe to Equipment Propagation during SingleStep execution
Data Type Enumeration
Range 0 None No
propagation

6 Hold Propagate
Hold
7 Stop Propagate

- 2930 -
Chapter 21 - Sxxxx Parameters

Stop
8 Abort Propagate
Abort
Default Stop (7)
Config Yes
Load
Active No
Loadable
Access Application Developer
Lock
Residence CEE
Related SSRECTOEQM, RECTOEQMENB
Parameters
Remarks Only available in Experion R311 or later. The behavior of RCMs
in R310 and before is equivalent to value of NONE. Migrated
RCMs will have their value set to NONE. They need to be
manually reconfigured to get the default value of Stop. When
the equipment reaches terminal Stop or Abort, it will be given a
RESET command, which normally cause it to reach the IDLE
state.

21.335 SSSINGULARVALUE

Specific to Block(s) ProfitCtl


Description Largest singular value
Data Type FLOAT64
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

21.336 SSTEPLOCK

Specific to SCM, RCM


Block(s)
Description Single Step Mode Access Lock
Data Type Enumeration CSCOACCLOCK
Range Engineer (0) Operator (1) OtherFB (2) ViewOnly (3) Supervisor(4)
Default Engineer (0)

- 2931 -
Chapter 21 - Sxxxx Parameters

Config Load Yes


Active No
Loadable
Access Lock Engineer
Residence CEE
Related MODE
Parameters
Remarks The value of SSTEPLOCK restricts who can change the Sequential Control
Module (SCM) MODE to SingleStep.

21.337 STALECOUNT

Specific to CONTROLMODULE
Block(s)
Description Stale Count - Defines the maximum number of consecutive stale input values that
may be received before the input status is set to BAD.
Data Type
Range 0 to 60
Default 2
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence SR
Related
Parameters
Remarks If the STALECOUNT limit is set to zero, then no detection of stale data is required.

21.338 STARTFL

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Start Totalizer Command Flag - When this flag changes from Off to On, the
Totalizer function block starts the accumulator.
Data Type Boolean
Range Off (0): Do not start the accumulator On (1): Start the accumulator
Default Off (0): Do not start the accumulator
Config Load No
Active No
Loadable

- 2932 -
Chapter 21 - Sxxxx Parameters

Access Lock Other Function Block


Residence CEE
Related RESETFL, STOPFL.
Parameters
Remarks

Specific to Block Timer


(s)
Description Start Command Flag - Provides the ability to issue the Start command to Timer
function block.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No
Access Lock Other Function Block
Residence CEE
Related COMMAND, RESETFL, RESTARTFL, STOPFL.
Parameters
Remarks An Off-to-On transition of STARTFL starts the timer.

21.339 STARTINDEX

Specific to SIFLAGARRCH, SINUMARRCH, SITEXTARRCH


Block(s)
Description Starting Element Index - Identifies the start of the contiguous array in the device.
Data Type 32-Bit Integer
Range 0 to 99,999
Default 0
Config Load Yes
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related
Parameters
Remarks Refer to the Allen-Bradley Interface Appendix the MODBUS Interface Appendix in
the Serial Interface Module Implementation Guide for additional configuration data.

- 2933 -
Chapter 21 - Sxxxx Parameters

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Starting Element Index - Identifies the start of the contiguous array in the device.
Data Type 32-Bit Unsigned Integer
Range 1 to 965535
Default 1
Config Load Yes
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Starting index of flags to read or write depending on the Read/Write Option:
l 000001-065535: read from1 to 1968 contiguous flags or write single flag.
l100001-165535: read from 1 to 1968 contiguous flags. This is read only
addresses. Read/Write Option setting is ignored.
Starting index of numerics to read or write depending on the Read/Write Option:
l 200001-265535: read or write from 1 to 60 contiguous Word Swapped IEEE
floating point numbers.
l 300001-365535: read from 1 to 120 or 1 to 60 contiguous Signed Integer
numbers. This is read only addresses. Read/Write Option setting is ignored.
l 400001-465535: read from 1 to 120, 1 to 60, or write a single Signed Integer
numbers.
l 700001-765535: read or write from 1 to 60 contiguous IEEE floating point
numbers.
l 800002-865535: read or write from 1 to 60 contiguous IEEE floating point in
Address-1.
l900001-965535: read from 1 to 120 or write a single Unsigned Integer
numbers. 1 to 60, if CONVTOLONG is selected.
Starting index of strings to read or write depending on the Read/Write Option:
l 500001-565535: read/write up to 120 Unicode characters or 240 ASCII
characters. (NSTRING = 120/STRLEN, if CONVTOASCII is not checked, or
NSTRING = 240/STRLEN, if CONVTOASCII is checked.)
l 600000: write diagnostic loopback message. (NSTRING = 120/STRLEN, if
CONVTOASCII is not checked, or NSTRING = 240/STRLEN, if CONVTOASCII is
checked.)
l 600001-665535: read/write vendor information, 1 to 80 characters.
l 699999: write vendor information, 1 to 80 characters.

- 2934 -
Chapter 21 - Sxxxx Parameters

21.340 STARTOFFSET

Specific to Step
Block(s)
Description Start Offset in seconds
Data Type 32-Bit Integer
Range
Default 0
Config Yes
Load
Active No
Loadable
Access Application Developer Only
Lock
Residence SR
Related
Parameters
Remarks Minitrend frozen values use two parameters defined for the step to allow visibility
for phenomena occurring before the step started and after the step completed.
Both times are in seconds with a default of 0. STARTOFFSET defines how much
history is shown before the step started. The start is calculated as: Start time = Step
start - STARTOFFSET When the step is repeated as part of an execution loop in
SCM/RCM, the step start time is larger that the recorded step end time when the
step is reactivated. In this case, the minitrend display resumes the realtime method
for the current values for the duration of the repeated step execution.

21.341 STARTOP[1..NUMPROFILES]

Specific to Block(s) RampSoak


Description Starting Output ( OP) Value for a RampSoak profile.
Data Type Real
Range N/A
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters STARTSEG[1..NUMPROFILES]
Remarks

- 2935 -
Chapter 21 - Sxxxx Parameters

21.342 STARTOPSEL

Specific to HRBALG_REG block


Blocks
Description STARTOPSEL Reference
Data Type BLOCKID
Range

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the STARTOPSEL CAB in the emulation CM
which holds the HRBALG_REG instance.
Checkpoint Yes

21.343 STARTOPT

Specific to DevCtl, All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp,
Block(s) PulseCount, PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer,
and Switch.
Description Starting State Option - A configurable parameter that specifies the action the
control device takes, when SCMSTATE is Checking, Idle, or Complete. For making
STARTOPT Settings to function for IDLE state, it is required to put SCM in to
RUNNING state. Once SCM changes to RUNNING state and then any appropriate
state transitions if it appears in the IDLE state, STARTOPT works in IDLE state.
Data Type Enumeration REGEXCOPT
Range None (0): No changes
Man (1): Set MODEREQ = Manual
Auto (2): Set MODEREQ = Auto
Cas (3): Set MODEREQ = Cas
FixedOP (4): Set OPREQ = STARTVAL
HoldPV (5): Set SPREQ = PV
FixedSP (6): Set SPREQ = STARTVAL, and
SPRATEREQ = NaN
RampedSP (7): Set SPTVREQ = STARTVAL, and
SPRATEREQ = STARTRATE
Default None (0)
Config Yes
Load
Active No
Loadable

- 2936 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related STARTRATE STARTTIME OUTIND
Parameters
Remarks Defines values for SPREQ, SPRATEREQ, OPREQ, and MODEREQ when
MONSCOSTATE = Ready, Checking, or End. Illegal if SCMOPT ≠ Fixed. Note: If the
Man and Cas modes are not supported, then corresponding error should be
displayed while configuring or loading. Also, the value box should be disabled.

Specific to HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Block(s)
Description Starting State Option - A configurable parameter that specifies the action the
control device takes, when SCMSTATE is Checking, Idle, or Complete. For making
STARTOPT Settings to function for IDLE state, it is required to put SCM in to
RUNNING state. Once SCM changes to RUNNING state and then any appropriate
state transitions if it appears in the IDLE state, STARTOPT works in IDLE state.
Data Type Enumeration
Range NONE, SAFEOP
Default NONE
Config YES
Load
Active No
Loadable
Access Lock ENGINEER
Residence CE
Related STOPOPT
Parameters
Remarks

21.344 STARTPHASE

Specific to ProfitCtl
Block(s)
Description Algo Start Processing Phase
Data Type INT32
Range NA
Default 0
Config No
Load
Active No
Loadable

- 2937 -
Chapter 21 - Sxxxx Parameters

Access Lock VIEWONLY


Residence NOLOAD
Related ENDPHASE
Parameters
Remarks This parameter represents the CEE phase in which profit controller execution starts
and in most cases it should match with PHASE parameter of control module. Since
the execution of this block happens in background processing, this block may not
start execution in the same phase where it was scheduled to start

21.345 STARTRATE

Specific to Most RegCtl Blocks with SP support: AutoMan, Fanout, OvrdSel, PID, PIDFF, PIDER,
Block(s) PID-PL, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Starting State Set Point (SP) Ramp Rate - The value used for setting when
STARTOPT is Ramped SP.
Data Type 64-Bit Real Number
Range NaN, 0.0, or positive or negative Real numbers
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related STARTOPT
Parameters
Remarks Defines value for SPRATEREQ, when STARTOPT = RampedSP.

21.346 STARTSEG[1..NUMPROFILES]

Specific to Block(s) RampSoak


Description Starting Segment ID
Data Type Integer
Range Greater than zero
Default 1
Config Load Yes
Active Loadable No
Access Lock Operator
Residence CEE
Related Parameters STARTOP[1..NUMPROFILES]
Remarks

- 2938 -
Chapter 21 - Sxxxx Parameters

21.347 STARTTIME

Specific to Block Step,Phase


(s)
Description Start Time
Data Type TimeOfDay
Range
Default
Config Load No
Access Lock ViewOnly
Residence CEE
Related ENDTIME
Parameters
Remarks Time when step/phase has been activated and becomes part of
ACTIVELOC.STEP[1..15]

Specific to Block(s) ProfitCtl


Description Exec Start Time
Data Type INT32
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock VIEWONLY
Residence NOLOAD
Related Parameters ENDTIME
Remarks

21.348 STARTVAL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Starting State Value - The value used for setting OPREQ when STARTOPT is
FixedOP; or for setting SPREQ or SPTVREQ when STARTOPT is FixedSP or
RampedSP.
Data Type 64-Bit Real Number
Range OPEXLOLM to OPEXHILM when STARTOPT = FixedOP. SPLOLM to SPHILM when
STARTOPT = FixedSP or RampedSP. (NaN, 0.0, positive or negative real numbers)
Default NaN
Config Yes
Load
Active No
Loadable

- 2939 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related STARTOPT
Parameters
Remarks Defines a value for OP when STARTOPT = FixedOP; or a value for SP when
STARTOPT = FixedSP; Or a value for SP when STARTOPT = RampedSP. Note: If the
Man and Cas modes are not supported, then corresponding error should be
displayed while configuring or loading. Also, the value box should be disabled.

21.349 STATE

Specific to Block(s) Totalizer, Pulse Input Totalizer


Description Totalizer State - Indicates the current state of the Totalizer function block.
Data Type Enumeration STATE
Range Stopped (0) Running (1) - (accumulating)
Default Stopped (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters RESETFL, STALECOUNT, STARTFL, STOPFL.
Remarks

Specific to Block(s) Timer


Description Timer State - Indicates current state of Timer function block.
Data Type Enumeration TIMERSTATE
Range Stopped (0) Running (1)
Default Stopped (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters COMMAND
Remarks

Specific to SCM, RCM


Block(s)
Description Indicates current state of the SCM/RCM function block.
Data Type Enumeration CSCOSTATE
Range Loading (0) Loaded (1) Inactive (2) Validated (3) Running (4) Complete (5) Checking
(6) Idle (7) Interrupting (8) Interrupted (9) Restarting (10) Restarted (11) Holding
(12) Held (13) Stopping (14) Stopped (15) Aborting (16) Aborted (17) CommErr (18)
Default Inactive (2)

- 2940 -
Chapter 21 - Sxxxx Parameters

Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks Refer to the SCM STATE transition diagram in SCM STATE and COMMAND
interraction in the Sequential Control Module User Guide for additional information.

Specific to Handler, Step, Transition


Block(s)
Description Sequential Control Module (SCM) Component State
Data Type Enumeration CSCOPARTSTATE
Range Edit (0) Inactive (1) Disabled (2) Enabled (3) Active (4) ActiveComplt (5)
ProcOutputs (6) ProcMessages (7) ProcMinWait (8)
Default Edit (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks

Specific to Phase
Block(s)
Description State of phase block
Data Type Enumeration CSCOPARTSTATE
Range Edit (0) Inactive (1) Active (4) ActiveComplt (5) ProcMinWait (8) ProcAcquire (9)
ProcFormula (10) ProcExec (11) ProcState (12) ProcReport (13) ProcReset (14)
ProcRelease (15) ProcModeTrk (16)
Default Edit (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks For more information refer to the Sequential Control Module User Guide,State Model
of Phase Block

- 2941 -
Chapter 21 - Sxxxx Parameters

Specific to Block(s) C200 IOLINK, C300 IOLINK


Description I/O Link State. Shows the current state of the associated I/O link.
Data Type Enumeration
Range NOTLOADED (0): IOLINK block has not been
loaded.
ONLINE (1): IOLINK is online.
Default NOTLOADED (0)
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks The IOLINK does not have an “INACTIVE”
state.

Specific to AICHANNEL, HAICHANNEL (PM I/O)


Block(s)
Description Current State of the Smart Transmitter Interface (STI) point.
Data Type Enumeration
Range None (0): Off net.

Loading Loading of the database is occurring between the STI point and the
(2): transmitter.
Loadcomp Loading of the database between the STI point and the transmitter
(3): has completed successfully.
Loadfail Loading of the database between the STI point and the transmitter
(4): has failed.
Calib (5): The STI point is calibrating certain parameters at the transmitter.
Calcomp Calibration has completed successfully.
(6):
Calfail (7): Calibration has failed.
OK (8): Normal State - The STI and the transmitter are okay. Transmitter is
updating the Process Variable (PV) value at the STI point. State
remains OK when the point is made inactive.
DBChange A database mismatch exists between the STI point and the
(9): transmitter. Transmitter is not updating the PV value at the STI point.
State remains Dbchange when point is made inactive.
Default None (0)
Config Load No
Active No
Loadable

- 2942 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks This parameter is only exposed, if ASSOCIOPTYP is STI-MV.

Specific to Block(s) EIM


Description State of block
Data Type ENUM
Range NA
Default Inactive
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

Specific to Block(s) EIM EIP Protocol Block


Description State
Data Type ENUM
Range NOTLOADED ONLINE IDLE NOTSYNCED OFFLINE RESERVED
Default NOTLOADED
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NoLoad
Related Parameters -
Remarks EIM EIP Protocol Block State.

21.350 STATE0

Specific to CONTACTMON, DIGACQ, FLAG, PUSH


Block(s)
Description State 0 Indicator
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable

- 2943 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related PV, PVFL, STATE.
Parameters
Remarks Value is On, when Flag function block is in State 0 (Process Variable (PV) shows
STATETEXT[0] and PVFL is Off).

21.351 STATE1

Specific to CONTACTMON, DIGACQ, FLAG, PUSH


Block(s)
Description State 1 Indicator
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related PV, PVFL, STATE0.
Parameters
Remarks Value is On, when Flag function block is in State 1 (Process Variable (PV) shows
STATETEXT[1] and PVFL is On).

21.352 STATETEXT[*]

Specific to Block DIGACQ


(s)
Description Text for Each State
Data Type String
Range 12 characters
Default STATETEXT [0] OFF STATETEXT [1] ON
Config Load YES
Active Loadable No
Access Lock Engineer
Residence CEE
Related NORMALPV
Parameters
Remarks STATETEXT[*] value is applied to PV based on PVFL. PV = STATETEXT[1]
whenPVFL= ON.

- 2944 -
Chapter 21 - Sxxxx Parameters

21.353 STATETEXT[0..1]

Specific to FLAG, PUSH


Block(s)
Description State Descriptor Text - Defines text for the two states of the Flag FB; STATETEXT[0]
corresponds to the Boolean state of Off for the Flag, while STATETEXT[1]
corresponds to On.
Data Type String
Range Length: 12 characters
Default “Off”, “On”
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related NORMAL, PV.
Parameters
Remarks

Specific to Block(s) CONTACTMON


Description Text for Each State
Data Type String
Range Length: 12 characters
Default “Healthy” / Unhealthy
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters NORMAL, PV.
Remarks This Statext will give more clarity to the user when used in Display.

21.354 STATETEXT[0..3]

Specific to Block(s) DICHANNEL


Description Text for Process Variable (PV) Normal State.
Data Type String
Range 12 Characters
Default 0 STATETEXT [0] OFF
1 STATETEXT [1] ON
2 STATETEXT [2] RESERVED
3 STATETEXT [3] NONE

- 2945 -
Chapter 21 - Sxxxx Parameters

Config Load Yes


Active Loadable No
Access Lock Engineer
Residence SR
Related Parameters
Remarks This parameter is only exposed if ALMOPT is OFFNORML.

21.355 STATETEXT[0..6]

Specific to Block DevCtl


(s)
Description Text for Defined States
Data Type String
Range Length: 12 characters
Default Null String
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related LASTOPMNAME, LASTOPREQ, NUMDINPUTS, NUMDOUTS, PV, PVAUTO, OP,
Parameters OPFINAL, OPREQ.
Remarks Access is illegal if NUMDINPUTS = 0, and NUMDOUTS = 0.

21.356 STATETIME[0..2]

Specific to DevCtl
Block(s)
Description Accumulated State Time - The amount of time (in hours) that the device has spent
in any of the settable states.
Data Type DeltaTime
Range 0 to 4000 days
Default 0
Config No
Load
Active No
Loadable

- 2946 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related GPV, MAINTOPT. NUMSTATES, PV, RESETFL.
Parameters
Remarks Defaulted to 0 if MAINTOPT is not set On. Reset to 0 whenever RESETFL is set from
Off to On. STATETIME[2] is illegal if NUMSTATES = 2. The parameter will not be
maintained during C300 migration. The value will be reset to zero and cannot
modify manually.

21.357 STATRESET

Specific to CEEACE, ACE, CEE, CEESIMC200, SIMC200, C300, CEEC300, UOC, CEEUOC
Block(s)
Description Reset Statistics Command Parameter
Data Type Boolean
Range Off (0): Statistical parameters accumulate.
On (1): All statistical parameters are reset.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock Operator
Residence ACE(CEEACE, ACE), C200(CEE, CPM), SIMC200(CEESIMC200, SIMC200), C300
(C300, CEEC300), UOC(CEEUOC)
Related
Parameters
Remarks Writing ‘On’ to this parameter will reset the statistical parameters on the
performance tab.

Specific to Block(s) EIM EIP Protocol Block


Description Reset Statistics
Data Type BOOLEAN
Range 0–1
Default 0
Config Load No
Active Loadable No
Access Lock Operator
Residence PCM
Related Parameters -
Remarks Command to reset PDT statistics in the EIM.

- 2947 -
Chapter 21 - Sxxxx Parameters

Specific to Block(s) UOC


Description Reset All Statistics
Data Type BOOLEAN
Exposure INPUT
Range N/A
Default OFF
Config Load Yes
Active Loadable
Access Lock Operator
Residence NOLOAD
Related Parameters
Remarks Reset all UOC platform block statistics.

21.358 STATSRESET

Specific to C300, C200, FIM4, EHG, LIOM, TCMI CN100, ACE, SIM_C200, CEE, CEEACE,
Block(s) CEESIMC200, CEEC300, GEE, EE, PGM, EHPM, EIM PB_61850
Description Reset Statistics command parameter
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence ACE(CEEACE, ACE), C200(CEE, CPM), SIM_C200(SIM_C200, CEESIMC200), C300
(C300, CEEC300), LIOM, EHG, PGM, EHPM
Related CPUCYCLEAVG[0..39], CPUCYCLEMAX[0..39], NUMNTFRQUMAX,
Parameters CPUFREEAVG, CPUFREEAVGA, NUMACCRQUAVG,
CPUFREEAVGB, CPUFREEMIN, NUMACCRQUMAX, RDNCMPT,
NUMPARRSPAVG, NUMPARRSPMAX, RDNDELAYAVG, RDNDELAYMAX,
NUMNTFRQUAVG, RDNXFERAVG, RDNXFERMAX.
Remarks Store to this parameter causes initialization of all statistics parameters maintained
within the CPM and CEE (listed above). Any attempts to read this parameter will
return Off(0).

Specific to Block(s) EIM


Description Reset All Statistics
Data Type Boolean
Range NA
Default Off
Config Load

- 2948 -
Chapter 21 - Sxxxx Parameters

Active Loadable No
Access Lock Operator
Residence NOLOAD
Related Parameters
Remarks

Specific to Block CEEACE, ACE, CEE, CEESIMC200, SIMC200, C300, CEEC300, CEEUOC,
(s) CEECN100
Description Reset Statistics Command Parameter
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load No
Access Lock Operator
Residence ACE(CEEACE, ACE), C200(CEE, CPM), SIMC200 (CEESIMC200, SIMC200), C300
(C300, CEEC300), UOC(CEEUOC), CN100(CEECN100)
Related -
Parameters
Remarks Writing ‘On’ to this parameter will reset the statistical parameters on the
performance tab.

21.359 STATRESETA

Specific to All Series C I/O Modules


Block(s)
Description Reset Statistics
Data Type Boolean
Range 0 Off No action
1 On Reset all statistical
parameters on both
IOM partners
Default OFF
Config Load No
Active No
Loadable
Access Lock Operator
Residence IOM
Related CPUFREEAVGA, CPUFREEMINA. CPUFREEAVGB,
Parameters CPUFREEMINB
Remarks Writing ‘On’ to this parameter will reset all statistical
parameters (CPUFREEAVGA, CPUFREEMINA,
CPUFREEAVGB, CPUFREEMINB, ) on both IOM partners.

- 2949 -
Chapter 21 - Sxxxx Parameters

21.360 STATRESETB

Specific to All Series C I/O Modules


Block(s)
Description Reset Statistics
Data Type Boolean
Range 0 Off No action
1 On Reset all statistical
parameters on both IOM
partners
Default OFF
Config Load No
Active No
Loadable
Access Lock Operator
Residence IOM
Related CPUFREEAVGA, CPUFREEMINA. CPUFREEAVGB, CPUFREEMINB.
Parameters
Remarks Writing ‘On’ to this parameter will reset all statistical parameters (CPUFREEAVGA,
CPUFREEMINA, CPUFREEAVGB, CPUFREEMINB, ) on both IOM partners

21.361 STATUS_1[1..24]

Specific to QIPACTERM
Block
Description Status 1 bYTE
Data Type 32-Bit Integer
Range 0-255
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The QiMPACT Status 1 byte bit-packed structure in integer format. This is the value
in the input assembly for the designated position [1-24].

- 2950 -
Chapter 21 - Sxxxx Parameters

21.362 STATUS_2[1..24]

Specific to QIPACTERM
Block
Description Status 2 Word
Data Type 32-Bit Integer
Range 0-65535
Default 0
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related
Parameters
Remarks The QiMPACT Status 2 word bit-packed structure in integer format. This is the
value in the input assembly for the designated position [1-24].

21.363 STATUS

Specific to Block(s) PCDI_MASTER


Description Experion PKS Status
Data Type Enumeration
Range 0 UNKNOWN
1 NONE
2 DISABLED
3 FAILED
4 MARGINAL
5 OK
Default UNKNOWN
Config Load Yes
Active Loadable No
Access Lock ViewOnly
Residence SR
Related Parameters
Remarks

Specific to Block(s) SCM, RCM


Description Status
Data Type String
Range

- 2951 -
Chapter 21 - Sxxxx Parameters

Default
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence SR
Related Parameters
Remarks

21.364 STATUSRAW[1..4]

Specific to Block(s) JAGXTERM


Description Status Word
Data Type 16-Bit Unsigned Integer
Range 0-65535
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks The status word presented as an integer.

21.365 STDBYMAN

Specific to PMIO: AOCHANNEL, DOCHANNEL, HAOCHANNEL Series C IO: AOCHANNEL,


Block(s) DOCHANNEL
Description Standby Manual Flag: Indicates whether the associated hardware output is
connected to a standby manual device. It is not an indication of whether or not the
output is isolated from the process.
Data Type Boolean
Range Off (0): Output is not connected to standby-
manual device.
On (1): Output is connected to standby-manual
device.
Default Off (0)
Config Load No
Active No
Loadable

- 2952 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks

21.366 STDBYSTS

Specific to AO, AO16, AO16HART, DO16


Block(s)
Description Standby Status. Shows whether the associated hardware is connected to a
standby manual device or not.
Data Type Boolean
Range Off (0): No Standby Manual device is present.
On (1): Standby Manual device is present.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOP
Related
Parameters
Remarks This parameter does not show whether or not the output is isolated from the
process.

21.367 STDBYSTSA

Specific to PM I/O Output Modules, Series C I/O Output Modules, and Universal IO Modules
Block(s)
Description Standby Status Flag Channel A. Returns blind record of STDBYMAN status.
Data Type Boolean
Range 0 Off No Standby Manual
present.
1 On Standby Manual is
activated.
Default Off (0)
Config Load No
Active No
Loadable

- 2953 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks This parameter indicates whether the associated hardware is connected to a
standby manual device. It is not an indication of whether or not the output is
isolated from the process.

21.368 STDBYSTSB

Specific to PM I/O Output Modules, Series C I/O Output Modules, and Universal IO Modules
Block(s)
Description Standby Status Flag Channel B. Returns blind record of STDBYMAN status.
Data Type Boolean
Range 0 Off No Standby Manual
present.
1 On Standby Manual is
activated.
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter indicates whether the associated hardware is connected to a
standby manual device. It is not an indication of whether or not the output is
isolated from the process.

21.369 STDTIME

Specific to RM
Block(s)
Description Standard or Daylight Savings Time
Data Type Enumeration
Range Standard (0) Daylight (1)
Default Standard (0)
Config Load No
Active No
Loadable

- 2954 -
Chapter 21 - Sxxxx Parameters

Access Lock Operator RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

21.370 STEADYSTATEOP

Specific to PID-PL
Block(s)
Description Predicted Steady State OP, in Percent - Defines the predicted OP value at which the
process will line out.
Data Type Float64
Range
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related STEADYSTATEOPEU, STEADYSTATEPV.
Parameters
Remarks This parameter may vary slightly with every execution, as Profit Loop PKS refines its
steady-state estimate. Steady state conditions are not calculated when the
controller is in manual. This parameter is applicable only when CTLEQN is set to
Profit Loop PKS, and is ignored in PID control equations.

21.371 STEADYSTATEOPEU

Specific to PID-PL
Block(s)
Description Predicted Steady State OP, in Engineering Units - Defines the predicted OP value at
which the process will line out.
Data Type Float64
Range
Default
Config No
Load
Active No
Loadable

- 2955 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence CEE
Related STEADYSTATEOP, STEADYSTATEPV.
Parameters
Remarks This parameter may vary slightly with every execution, as Profit Loop PKS refines its
steady-state estimate. Steady state conditions are not calculated when the
controller is in manual. This parameter is applicable only when CTLEQN is set to
Profit Loop PKS, and is ignored in PID control equations.

21.372 STEADYSTATEPV

Specific to PID-PL
Block(s)
Description Predicted Steady State PV, in Engineering Units - Defines the predicted PV value at
which the process will line out.
Data Type Float64
Range
Default
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related STEADYSTATEOP, STEADYSTATEOPEU.
Parameters
Remarks This parameter may vary slightly with every execution, as Profit Loop PKS refines
its steady-state estimate. Steady state conditions are not calculated when the
controller is in manual. This parameter is applicable only when CTLEQN is set to
Profit Loop PKS, and is ignored in PID control equations.

21.373 STEAM_WATER

Specific to Block(s) Steam Property Block


Description Steam/Water
Data Type ENUM
Range STEAM
WATER
Default STEAM
Config Load Yes
Access Lock Application Developer Only

- 2956 -
Chapter 21 - Sxxxx Parameters

Active Loadable No
Residence CEE
Related Parameters
Remarks

21.374 STEAMQUALITY

Specific to Block(s) Steam Property Block


Description Steam Quality (X) Value
Data Type IEEE_FLOAT64
Range SI 0 to 100%
Metric 0 to 100%
English 0 to 100%
Default IEEENaN
Config Load No
Access Lock Engineer or CONTCONTROL
Active Loadable No
Residence CEE
Related Parameters
Remarks

21.375 STEAMQUALITYIO

Specific to Block(s) Steam Property Block


Description Steam Quality (X) IO Configuration
Data Type ENUM
Range Input Parameter configured as Input
Output Parameter configured as Output
Not Configured Parameter configured as None
Default Not Configured
Config Load Yes
Access Lock Application Developer Only
Active Loadable No
Residence CEE
Related Parameters
Remarks

- 2957 -
Chapter 21 - Sxxxx Parameters

21.376 STEAMTYPE

Specific to Steam Property Block


Block(s)
Description Steam Type
Data Type ENUM
Range SATURATED
SUPERHEATED
Default SATURATED
Config Load Yes
Access Lock Application Developer Only
Active No
Loadable
Residence CEE
Related
Parameters
Remarks This parameter is not available for configuration if the STEAM_WATER
parameter is configured as "Water."

21.377 STEP

Specific to Block(s) CEEC300, CEEACEFB,CEESIM200


Description Number of cycles to execute
Data Type 32-Bit integer
Range N/A
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence C300(CEEC300), C200(CEE), ACE(C200), SIMC200(CEE), UOC(CEEUOC)
Related Parameters
Remarks

21.378 STEPALM.FL

Specific to SCM, RCM


Block(s)
Description Sequential Control Module (SCM) Step Timeout Alarm Flag
Data Type Boolean
Range Off (0) On (1)

- 2958 -
Chapter 21 - Sxxxx Parameters

Default Off (0)


Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related MAXTIME, STEPALM.PR, STEPALM.SV.
Parameters
Remarks When On, this indicates that the SCM Step Timeout Alarm condition (the Active
SCM Step has remained active for longer than the configured maximum step time,
MAXTIME) exists.

21.379 STEPALM.PR

Specific to SCM, RCM


Block(s)
Description Sequential Control Module (SCM) Step Timeout Alarm Priority - Specifies the
alarm priority for the SCM Step Timeout alarm.
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related STEPALM.FL, STEPALM.SV.
Parameters
Remarks

21.380 STEPALM.SV

Specific to SCM, RCM


Block(s)
Description Sequential Control Module (SCM) Step Timeout Alarm Severity - Specifies the
alarm severity for the SCM Step Timeout alarm.
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active No
Loadable

- 2959 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related STEPALM.FL, STEPALM.PR.
Parameters
Remarks

21.381 STEPPERSTATUS

Specific to Block(s) ProfitCtl


Description Stepper Status
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters
Remarks

21.382 STEPTOPHASE

Specific to Block CEEC300, CEEACEFB, CEESIM200


(s)

Description Phase range in step


Data Type INT32
Range 0 to 39
Default -1
Config Load No
Access Lock AppDevOnly
Residence C300(CEEC300), C200(CEE), ACE(C200), SIMC200(CEE), UOC(CEEUOC)
Related CEESTATE
Parameters

Remarks Engineer Point Build (Lock is a combination of Engineer and Application Developer
Only access levels)

- 2960 -
Chapter 21 - Sxxxx Parameters

21.383 STICTIONL

Specific to Block(s) PosProp, PidPosProp


Description Stiction Lower Compensation of actuator (in seconds).
Data Type Real
Range 0.0 to 60.0
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Related Parameters
Remarks

21.384 STICTIONR

Specific to Block(s) PosProp, PidPosProp


Description Stiction Raise Compensation of actuator (in seconds).
Data Type Real
Range 0.0 to 60.0
Default 0.0
Config Load Yes
Active Loadable No
Access Lock Supervisor
Residence CEE
Remarks

21.385 STIDBDISCRE

Specific to AICHANNEL
Block(s)
Description Smart Transmitter Interface (STI) Database Discrepancy. Shows the list of
parameters whose values are not the same in both the STI database and the Smart
Transmitter's database. (Parameters are mismatched.)
Data Type String
Range 26 Characters
Default Null
Config Load No
Active No
Loadable

- 2961 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence IOM
Related
Parameters
Remarks This parameter is only exposed if ASSOCIOPTYP is STI-MV.

21.386 STI_EU

Specific to Block(s) AICHANNEL


Description Smart Transmitter Interface Engineering
Units. Specifies the Engineering Units of
measurement to be used for the display
of transmitter range parameters LRL,
LRV, URL, and URV.
Data Type Enumeration
Range: (0) InH2O: Pressure Transmitter-Inches of Water (1) MMHG: Pressure Transmitter-
SENSRTYP Millimeters of Mercury (2) PSI: Pressure Transmitter-Pounds per Square Inch (3)
= SPT_ KPA: Pressure Flow Transmitter-Kilopascals (4) MPA: Pressure Transmitter-
AP,SPT_DP, Millipascals (5) MBar: Pressure Transmitter-Millibars (6) Bar: Pressure Transmitter-
orSPT_GP Bars (7) G_SQCM: Pressure Transmitter-Grams per Square Centimeter) (8) KG_
SQCM: Pressure Flow Transmitter-Kilograms per Square Centimeter (9) MMH2O:
Pressure Transmitter-Millimeters of Water (10) INHG: Pressure Transmitter-Inches
of Mercury
Default: (0) InH2O: Pressure Transmitter-Inches of Water
SENSRTYP
= SPT_
AP,SPT_DP
orSPT_GP
Range: (18) CM_HR: Magnetic Flow Transmitter (volume)-Cubic Meters per Hour (19) Gal_
SENSRTYP HR: (Magnetic Flow Transmitter (volume)-Gallons per Hour) (20) LIT_HR: Magnetic
= SFM Flow Transmitter (volume)-Liters per Hour (21) CC_HR: Magnetic Flow Transmitter
(volume)-Cubic Centimeters per Hour (22) CM_Min: Magnetic Flow Transmitter
(volume)-Cubic Meters per Hour (23) Gal_Min: Magnetic Flow Transmitter
(volume)-Gallons per Minute (24) Lit_Min: Magnetic Flow Transmitter (volume)-
Liters per Minute (25) CC_Min: Magnetic Flow Transmitter (volume)-Cubic
Centimeters per Minute (26) CM_Day: Magnetic Flow Transmitter (volume)-Cubic
Meters per Day) (27) Gal_Day: Magnetic Flow Transmitter (volume)-Gallons per
Day) (28) KGal_Day: Magnetic Flow Transmitter (volume)-Thousands of Gallons per
Day (29) BRL_Day: Magnetic Flow Transmitter (volume)-Barrels per Day) (30) CM_
Sec: Magnetic Flow Transmitter (volume)-Centimeters per Second) (31) KG_HR:
Magnetic Flow Transmitter (mass)-Kilograms per Hour (32) LBS_HRn: Magnetic
Flow Transmitter (mass)-Pounds per Hour) (33) Ft_Sec: Magnetic Flow Transmitter
(velocity)-Feet per Second (34) M_Sec: Magnetic Flow Transmitter (velocity)-Meters
per Second (35) KG_Min: Magnetic Flow Transmitter (mass)-Kilograms per Minute)
(36) KG_Sec: Magnetic Flow Transmitter (mass)-Kilograms per Second) (37) LBS_
Min: Magnetic Flow Transmitter (mass)-Pounds per Minute) (38) LBS_Sec:
Magnetic Flow Transmitter (mass)-Pounds per Second) (39) PRCNT: Percent (40)
BLANK: Blank - Multivariable Transmitter with SFM SENSRTYP (41) LBS: Pounds
(42) KG: Kilograms (43) TONS: Tons (44) GRAMS: Grams (45) OZ: Ounces (46) GAL:
Gallons (47) BRL: Barrels (48) CUB_M: Cubic Meters (49) LITERS: Liters (50)
MLITRES: Milliliters (51) FL_OZ: Fluid ounce (52) FEET: Feet (53) METERS: Meters
(54) MM: Millimeters (55) INCHES: Inches (56) KG_CUM: Kilograms per Cubic Meter
(57) G_CUM: Grams per Cubic Meter (58) LBS_CUFT: Pounds per Cubic Foot (59)
LBS_CUIN: Pounds per Cubic Inch

- 2962 -
Chapter 21 - Sxxxx Parameters

Default: (40) BLANK (Blank): Multivariable transmitter with SFM SENSRTYP


SENSRTYP
= SFM
Range: (15) MV: Temperature Transmitter-Millivolts (16) V: Temperature Transmitter-Volts
SENSRTYP
= STT
and
PVCHAR =
Linear
Default: (15) MV: Temperature Transmitter-Millivolts
SENSRTYP
= STT
and
PVCHAR =
Linear
Range: (17)-Ohms (Temperature transmitter-RTD Ohms)
SENSRTYP
= STT
and
PVCHAR =
RTDOHMS
Default: (17)-Ohms (Temperature transmitter-RTD Ohms)
SENSRTYP
= STT
and
PVCHAR =
RTDOHMS
Range: (11) Deg_C: (Temperature Transmitter-Degrees Centigrade) (12) Deg_F:
SENSRTYP (Temperature Transmitter-Degrees Fahrenheit) (13) Deg_K: (Temperature
= STT Transmitter-Degrees Kelvin) (14) Deg_R: (Temperature Transmitter-Degrees)
and
PVCHAR =
all other
valid values
Default: 11-Deg_C (Temperature transmitter-Degrees Centigrade)
SENSRTYP
= STT and
PVCHAR =
all other
valid values
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence IOM
Related
Parameters
Remarks This parameter specifies the units of measurement for parameters LRL, LRV, URL,
and URV. These units are for display only. When BLANK is selected the limit values
URL, LRL, URV and LRV are displayed in the base engineering units specified in the
transmitter user manual. Loading an invalid STI_EU type causes an error. This
parameter is only exposed if [ASSOCIOPTYP] = STI-MV.

- 2963 -
Chapter 21 - Sxxxx Parameters

21.387 STIPVNUMBER

Specific to AICHANNEL
Block(s)
Description Smart Transmitter Interface (STI) Process Variable (PV) Number. Shows which of
the up to 4 PVs from a single transmitter is associated with this STI.
Data Type String
Range 7 Characters
Default Null
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is only exposed if ASSOCIOPTYP is STI-MV.

21.388 STISCRATCHPAD

Specific to AICHANNEL
Block(s)
Description Smart Transmitter Interface (STI) Scratch Pad. Shows the current contents of
scratch Pads 1, 2, 3, and 4 of the transmitter associated with this STI point.
Data Type String
Range 35 Characters
Default Null
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is only exposed if ASSOCIOPTYP is STI-MV.

- 2964 -
Chapter 21 - Sxxxx Parameters

21.389 STISTATUS

Specific to AICHANNEL
Block(s)
Description Smart Transmitter Interface (STI) Status. Show the current detailed status of the
Smart Transmitter associated with this STI point.
Data Type String
Range 67 Characters
Default Null
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOM
Related
Parameters
Remarks This parameter is only exposed if ASSOCIOPTYP is STI-MV.

21.390 STISWVER

Specific to Block(s) AICHANNEL


Description Software Revision Level of the Smart Transmitter.
Data Type String
Range
Default NULL
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOM
Related Parameters
Remarks STISWVER is exposed only if ASSOCIOPTYP is STI-MV.

21.391 STITAG

Specific to AICHANNEL
Block(s)
Description Smart Transmitter Interface Tag Name. Defines the name of the Smart Transmitter
to be used in the system and on displays, reports, and logs.
Data Type String
Range 8 Characters

- 2965 -
Chapter 21 - Sxxxx Parameters

Default All Spaces


Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence IOP
Related
Parameters
Remarks This parameter is only exposed if the ASSOCIOPTYP is STI-MV For multivariable
transmitters, the identical STITAG must be entered for each active slot related to
that transmitter. The I/O Processor (IOP) uses the number of identical STITAG
names to calculate the number of Process Variables (PVs) associated with a given
transmitter. This parameter is an ASCII string and has no support for
internationalization.

21.392 STMCHOVRRUNSA

Specific to Block(s) Series C DI-SOE IOM Blocks


Description This parameter is used to count the missed SOE processing interrupt.
Data Type UINT 16
Range 0 to 65535
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence IOM
Related Parameters
Remarks

21.393 STMCHOVRRUNSB

Specific to Block(s) Series C DI-SOE IOM Blocks


Description This parameter is used to count the missed SOE processing interrupt.
Data Type UINT 16
Range 0 to 65535
Default 0
Config Load No
Active Loadable No

- 2966 -
Chapter 21 - Sxxxx Parameters

Access Lock View Only


Residence IOM
Related Parameters
Remarks

21.394 STMCHMAXOVRRUNTIMEA

Specific to Block(s) Series C DI-SOE IOM Blocks


Description This parameter is used to track the high water mark of all overruns.
Data Type UNIT 16
Range 0 to 65535
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence IOM
Related Parameters
Remarks

21.395 STMCHMAXOVRRUNTIMEB

Specific to Block(s) Series C DI-SOE IOM Blocks


Description This parameter is used to track the high water mark of all overruns.
Data Type UNIT 16
Range 0 to 65535
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence IOM
Related Parameters
Remarks

- 2967 -
Chapter 21 - Sxxxx Parameters

21.396 STMCHLASTOVERRUNTIMEA

Specific to Block Series C DI-SOE IOM Blocks


(s)
Description This parameter is used to capture the time spent by the state machine during
the last overrun.
Data Type UNIT 16
Range 0 to 65535
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence IOM
Related
Parameters
Remarks

21.397 STMCHLASTOVERRUNTIMEB

Specific to Block Series C DI-SOE IOM Blocks


(s)
Description This parameter is used to capture the time spent by the state machine during
the last overrun.
Data Type UNIT 16
Range 0 to 65535
Default 0
Config Load No
Active Loadable No
Access Lock View Only
Residence IOM
Related
Parameters
Remarks

21.398 STNDPIPELEN

Specific to Block(s) LEVELCOMP


Description Length of stand pipe
Data Type Float64
Range Computed from PVEUHI and PVEULO.

- 2968 -
Chapter 21 - Sxxxx Parameters

Default 600
Config Load NO
Active Loadable No
Access Lock View only
Residence CEE
Related Parameters PVEULOPVEUHI
Remarks The stand pipe length is computed from PVEULO and PVEUHI.

21.399 STOPALM.FL

Specific to SCM, RCM


Block(s)
Description Sequential Control Module (SCM) Stop Alarm Flag
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence CEE
Related STATE, STOPALM.PR, STOPALM.SV
Parameters
Remarks When On, it indicates that the Stop Alarm condition (SCM STATE has transitioned
to Stopping or Stopped) exists.

21.400 STOPALM.PR

Specific to Block(s) SCM, RCM


Description Sequential Control Module (SCM ) Stop Alarm Priority
Data Type Enumeration ALPRIOR
Range None (0) Journal (1) Low (2) High (3) Urgent (4)
Default None
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters STOPALM.FL, STOPALM.SV
Remarks See STOPALM.FL for additional information.

- 2969 -
Chapter 21 - Sxxxx Parameters

21.401 STOPALM.SV

Specific to Block(s) SCM, RCM


Description Sequential Control Module (SCM) Stop Alarm Severity
Data Type 16-Bit Integer
Range 0 to 15
Default 0
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters STOPALM.FL, STOPALM.PR.
Remarks See STOPALM.FL for additional information.

21.402 STOPFL

Specific to Totalizer, Pulse Input Totalizer


Block(s)
Description Stop Totalizer Command Flag - When this flag changes form Off to On, the
Totalizer function block stops the accumulator.
Data Type Boolean
Range Off (0): Do not stop the accumulator On (1): Stop the accumulator
Default Off (0): Do not stop the accumulator
Config Load No
Active No
Loadable
Access Lock Other Function Block
Residence CEE
Related RESETFL, STALECOUNT, STARTFL.
Parameters
Remarks

Specific to Block Timer


(s)
Description Stop Command Flag - Provides ability to issue Stop command to Timer
function block.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load No
Active Loadable No

- 2970 -
Chapter 21 - Sxxxx Parameters

Access Lock Other Function Block


Residence CEE
Related COMMAND, RESETFL, RESTARTFL, STALECOUNT, STARTFL.
Parameters
Remarks An Off-to-On transition of STOPFL stops the timer.

21.403 STOPOPT

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Fail State Option - A configurable parameter that specifies the action the control
device takes, when SCMSTATE is Stopping or Stopped, or Aborting or Aborted. This
option should be disabled, when sequencing actions are required as part of the
SCM. In this case, the SCM should execute its Stop Handler. The SCM can also
disable this option.
Data Type Enumeration REGEXCOPT
Range None (0): No changes
Man (1): = Manual
Auto (2): Set MODEREQ = Auto
Cas (3): Set MODEREQ = Cas
FixedOP (4): STOPVAL
HoldPV (5): Set SPREQ = PUSHSP
FixedSP (6): = NaN
RampedSP (7): Set SPTVREQ = STOPVAL, and
SPRATEREQ = STOPRATE)
Default None (0)
Config Yes
Load
Active No
Loadable
Access Lock Engineer
Residence CEE
Related STOPVAL, STOPRATE.
Parameters
Remarks Defines values for the following: SPREQ, SPRATEREQ, OPREQ and MODEREQ
when ControlModule.SCMSTATE = Stopping or Stopped. Note: If the Man and Cas
modes are not supported, then corresponding error should be displayed while
configuring or loading. Also, the value box should be disabled.

Specific to DevCtl
Block(s)
Description Fail State Option
Data Type Enumeration DDOPTIONS
Range None (0) SafeOp (1)

- 2971 -
Chapter 21 - Sxxxx Parameters

Default None (0)


Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related HOLDOPT, OPREQ, OPTYPE, RESTARTOPT, SAFEOP, SCHEDCYCLE[0..120]
Parameters SCMASTEP[1..10], SCMOPT, SCMSTATE, STARTOPT.
Remarks Illegal if ControlModule.SCMOPT ≠ Fixed.

Specific to Block(s) HTMOTOR, LTMOTOR, SOLENOID, VALVEDAMPER


Description Fail State Option
Data Type Enumeration DDOPTIONS
Range None (0) SafeOp (1)
Default None (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters STARTOPT
Remarks

21.404 STOPPULSEWIDTH

Specific to Block(s) HTMOTOR, LTMOTOR


Description Stop Output Pulsewidth
Data Type Float64
Range 0 to 60 seconds
Default 1
Config Load YES
Active Loadable No
Access Lock ENGINEER
Residence CEE
Related Parameters RUNPULSEWIDTH
Remarks

- 2972 -
Chapter 21 - Sxxxx Parameters

21.405 STOPRATE

Specific to Most RegCtl Blocks with SP support: AutoMan, Fanout, OvrdSel, PID, PIDFF, PIDER,
Block(s) PID-PL, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description is RampedSP.
Data Type 64-Bit Real Number
Range NaN, 0.0, positive or negative Real numbers
Default NaN
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related STOPOPT
Parameters
Remarks Defines values for SPRATEREQ when STOPOPT = RampedSP.

21.406 STOPSTATEOPT

Specific to SCM, RCM


Block(s)
Description Stopped State Option
Data Type Enumeration
Range 0 Not Terminal - can return to running state after the
SCM has reached the Stopped state. Commands
allowed are Hold and Reset. For the RCM also, Hold
and Abort are the commands that are allowed.
However, the SCM accepts Reset command, which is
not intended. Therefore, when SCM is Stopped, first
allow the SCM to Abort and then to Reset. STOP
state is not the Final stage. You can go to running
state from the following Sequence: STOPPED-Hold-
HELD-Restart-RUNNING
1 Terminal - cannot return to running state after the
SCM/RCM has reached the Stopped state; the only
command allowed from a Stopped state is Reset.
STOP state is the final stage. You CANNOT go to
running state from the following Sequence:
STOPPED-Hold-HELD-Restart-RUNNING. You can
only follow this sequence -- STOPPED-Reset-IDLE-
Start-RUNNING
Default For SCM: Not Terminal For RCM: Terminal
Config Yes
Load
Active No
Loadable
Access Engineer

- 2973 -
Chapter 21 - Sxxxx Parameters

Lock
Residence CEE
Related
Parameters
Remarks A setting of Terminal is required to implement a state model according the sample
state model specified in S88 / IEC 61512-1 A setting of Terminal will provide a state
model with 1 non-terminal abnormal exception ( Hold ) and 2 terminal abnormal
exceptions ( Stop and Abort ). This is often required in batch automation. A setting of
NotTerminal will provide a state model with 2 non-terminal abnormal exceptions (
Hold , Stop ) and 1 terminal abnormal exception ( Abort ). This is often required in
process startup, shutdown and transition management.

21.407 STOPTIME

Specific to Block(s) HTMOTOR, LTMOTOR


Description Amount of STOP hrs
Data Type Float64
Range 0 - Max of Real Number
Default 0
Config Load NO
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters TRKSTATETIME
Remarks Used to indicate the amount of time the motor is in STOP state.

21.408 STOPVAL

Specific to All RegCtl Blocks: AutoMan, Fanout, OvrdSel, PID, PIDFF, PosProp, PulseCount,
Block(s) PulseLength, RampSoak, RemCas, RatioBias, RegCalc, RegSummer, and Switch.
Description Stop State Value - The value used for setting OPREQ, when STOPOPT is FixedOP;
or for setting SPREQ or SPTVREQ, when STOPOPT is FixedSP or RampedSP
Data Type 64-Bit Real Number
Range OPEXLOLM to OPEXHILM when STOPOPT = FixedOP SPLOLM to SPHILM when
STOPOPT = FixedSP or RampedSP. (NaN, 0.0, positive or negative Real numbers)
Default NaN
Config Yes
Load
Active No
Loadable

- 2974 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related STOPOPT
Parameters
Remarks Defines a value for: Output (OP) when STOPOPT = FixedOP; Or SP when STOPOPT
= FixedSP; Or SPTV when STOPOPT = RampedSP. Note: If the Man and Cas modes
are not supported, then corresponding error should be displayed while configuring
or loading. Also, the value box should be disabled.

21.409 STOREENB

Specific to Block(s) Push


Description Output store enable.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active Loadable No
Access Lock Engineer
Residence CEE
Related Parameters STORONCHGENB
Remarks This value must be set to ON for continuous storing to destination.

21.410 STORESTS

Specific to Block(s) Push


Description Store Status.
Data Type Enumeration TCStoreSts
Range STOREOK STOREFAIL STOREPENDING DATATYPERR
Default STOREOK
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters
Remarks This parameter describes the status of store request.

- 2975 -
Chapter 21 - Sxxxx Parameters

21.411 STORONCHGENB

Specific to Push
Block(s)
Description Store on change Enable.
Data Type Boolean
Range Off (0) On (1)
Default Off (0)
Config Load Yes
Active No
Loadable
Access Lock Engineer
Residence CEE
Related STOREENB
Parameters
Remarks Setting this flag ensures that input value will be stored to destination only when it
changes. The STOREENB flag has to be set though for store to take place.

21.412 STR[0..7]

Specific to REQTEXTARRCH, RSPTEXTARRAY


Block(s)
Description Array of strings to be read from or written to the third-party device. Stores are
accepted to this parameter only if the COMMAND indicates that this is a “write”
block.
Data Type String
Range Length: 8, 16, or 64 characters, as specified by STRLEN.
Default N/A
Config Yes
Load
Active No
Loadable
Access Lock Operator
Residence CEE
Related ERRFL, NSTRING, STRLEN.
Parameters
Remarks STR[i] provides access to the array of data, one element at a time, by all other
function blocks of the CEE. Initial values can be configured, but these will be
overwritten once good data is imaged from the Serial Interface Module. When
ERRFL is On, an error will be returned on attempted Gets and Stores to this
parameter, to indicate that there is a problem with the array data.

- 2976 -
Chapter 21 - Sxxxx Parameters

21.413 STR[1..8]

Specific to SITEXTARRCH
Block(s)
Description Process Value - Provides String value from the device.
Data Type String
Range Length: 8, 16, or 64 characters, as specified by STRLEN.
Default Null String
Config Yes
Load
Active No
Loadable
Access Lock Determined by ACCLOCK
Residence CEE
Related ERRFL, NSTRING, STRLEN.
Parameters
Remarks STR[i] provides access to the array of data, one element at a time, by all other
function blocks of the CEE. Initial values can be configured, but these will be
overwritten once good data is imaged from the Serial Interface Module. When
ERRFL is On, an error will be returned on attempted Gets and Stores to this
parameter, to indicate that there is a problem with the array data.

21.414 STR[1..16]

Specific to PCDITEXTARRCH
Block(s)
Description String Process Value from device
Data Type String
Range Maximum size is 250, if CONVTOASCII parameter is True and single string is being
used or 125 , if CONVTOASCII parameter is False.
Default Null String
Config Load Yes
Active No
Loadable
Access Lock Operator
Residence CEE
Related
Parameters
Remarks

- 2977 -
Chapter 21 - Sxxxx Parameters

21.415 STR[1..120]

Specific to TEXTARRAY
Block(s)
Description String Data - Provides access to the String values, one element at a time, for all
other function blocks of the CEE. Initial values can be configured.
Data Type String
Range Length: 8, 16, 32, or 64 characters, as specified by STRLEN.
Default Null String
Config Load Yes
Active No
Loadable
Access Lock Determined by ACCLOCK
Residence CEE
Related NSTRING, STRLEN.
Parameters
Remarks

21.416 STRLEN

Specific to TEXTARRAY, SITEXTARRCH


Block(s)
Description String Length of String Values - Specifies the number of characters per string
value.
Data Type 32-Bit Integer
Range Length: 8, 16, 32, or 64 characters.
Default 8
Config Yes
Load
Active No
Loadable
Access Lock Application Developer
Residence CEE
Related TEXTARRAY: NSTRING, STR[1..120] SITEXTARRCH: NSTRING, STR[1..8].
Parameters
Remarks The Text Array block supports a maximum size of 960 two-byte characters. This
number is chosen based on the amount of data that can fit in one ControlNet
message. This is important when full array access is supported. The following table
shows the maximum data combinations of NSTRING and STRLEN that are possible.
Illegal combinations of NSTRING and STRLEN (those requiring more than 960 two-
byte characters of data) will be rejected.
NSTRING STRLEN STR[ ] Range

15 64 1..15
30 32 1..30

- 2978 -
Chapter 21 - Sxxxx Parameters

60 16 1..60
120 8 1..120
SITEXTARRCH only: With the interface to the serial device haivng a maximum size
of 64-bytes, the table below shows how the 64-bytes are interpreted, based on the
NSTRING and STRLEN configured, and the resulting STR[ ] range. Illegal
combinations of NSTRING and STRLEN (those requiring more than 64-bytes of
data) will be rejected.
NSTRING STRLEN STR[ ] Range

1 64 1..1
2 32 1..2
4 16 1..4
8 8 1..8

Specific to PCDITEXTARRCH
Block(s)
Description Character Length of String Values
Data Type 16-Bit Unsigned Integer
Range 1 to 240
Default 8
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related
Parameters
Remarks Number of characters per string. The number of characters per string (STRLEN)
times the number of strings (NSTRING) may not exceed 120 Unicode characters or
240 ASCII characters. Error message is generated if invalid number of characters is
entered.

21.417 STRRESP[ ]

Specific to CEE, CEEC300, CEEACE, CEESIMC200


Block(s)
Description Store Response - Specifies the default store response expiration time to be
used for all peer environments in seconds.
Data Type Float64
Range N/A
Default 15.0
Config Load Yes
Active Loadable No

- 2979 -
Chapter 21 - Sxxxx Parameters

Access Lock Engineer


Residence CEE
Related NUMPEERENV[ ] PEERENV[ ], PEERSTRRESP[ ].
Parameters
Remarks If a store response is not received within the configured expiration time, the
store is marked failed.

21.418 STTEXT

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Soft Failure Text. Used to provide the string text found in the event packet attribute
when the IOP is non-redundant for consistency with redundant IOP. The string is
also appended with the DSA value of the IOP.
Data Type Enumeration
Range IOP_00 through IOP_40
Default IOP_00
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related STTEXTA, STTEXTB
Parameters
Remarks

21.419 STTEXTA

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Soft Failure Text Partner A. Used to provide the string text found in the event packet
value attribute to further indicate that IOP partner A generated the alarm/event
when the IOP is configured to be redundant. The string is also appended with the
DSA value of the IOP.
Data Type Enumeration
Range
Default PartnerA_00 through PartnerA_40
Config No
Load
Active No
Loadable

- 2980 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence SR
Related STTEXT, STTEXTB
Parameters
Remarks

21.420 STTEXTB

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Soft Failure Text Partner B. Used to provide the string found in the event packet
value attribute to further indicate that IOP partner B generated the alarm/event
when the IOP is configured to be redundant. The string is also appended with the
DSA value of the IOP.
Data Type Enumeration
Range
Default PartnerB_00 through PartnerB_40
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence SR
Related STTEXT, STTEXTA,
Parameters
Remarks

21.421 STUBIOM

Specific to Block(s) PCDI_MASTER


Description Stub I/O Module
Data Type 32-Bit Integer
Range
Default 0
Config Load No
Active Loadable No
Access Lock Engineer
Residence Device
Related Parameters
Remarks For simulation use

- 2981 -
Chapter 21 - Sxxxx Parameters

21.422 SUBMODTYPE

Specific to Block(s) All I/O Module Function Blocks.


Description Submodule Type
Data Type ENUM
Range 0 - NOT CONFIGURED
1 – AI
2 - AO
3 - DI
4 - DO
5 - Input
6 - Output
7 - Input and Ouput
8- NO IO
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence CEE
Related Parameters SLOTNUM, SUBSLOTNUM
Remarks

21.423 SUBSCRIBEFAIL

Specific to Block(s) EIM


Description Additional Error Info
Data Type STRING
Range NA
Default
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks

- 2982 -
Chapter 21 - Sxxxx Parameters

21.424 SUBSCPERIOD

Specific to CEEACE, CEE, CEESIMC200, CEEC300, CEECN100


Block(s)
Description Peer Update Rate for Peer-to-Peer communications between two or more CEE's
(Control Execution Environments) in milliseconds (ms) from the following Range.
Data Type Enumeration
Range DEFAULT(0)
10 ms (1)
20 ms (2)
50 ms (3)
100 ms (4)
200 ms (5)
500 ms (6)
1 sec. (7)
 2 sec. (8)
 5 sec. (9)
 10 sec. (10)
Default DEFAULT (0) DEFAULT is converted to an actual value upon load: Converted to 500
ms for the 50 ms CEE Converted to 100 ms for the 5 ms CEE Converted to 1000 ms
for CEEACE Converted to 2000 ms for CEESCE
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related
Parameters
Remarks The Peer Update Rate (SUBSCPERIOD parameter is the rate at which this CEE
subscribes to data from other CEEs through peer-to-peer communications. In the
event of a peer-to-peer communications problem such as a broken cable, the
connection will timeout, returning an error. The valid values and function of the
DEFAULT value for SUBSCPERIOD are different for the 50 and 5 ms CEE
personalities as described below. 50 ms CEE: Valid Range: DEFAULT, 100, 200, 500,
1000 ms is converted to 500 ms upon load to a 50 ms CEE. Connection timeout time
is approximately 5.2 seconds. 5 ms CEE: Valid Range: DEFAULT, 10, 20, 50, 100, 200,
500, 1000 ms is converted to 100 ms upon load to a 5 ms CEE. Connection timeout
time is approximately 5.2 seconds.

- 2983 -
Chapter 21 - Sxxxx Parameters

Specific to CEEUOC
Block(s)
Description Peer Update Rate for Peer-to-Peer communications between two or more CEE's
(Control Execution Environments) in milliseconds (ms) from the following Range.
Data Type Enumeration
Range DEFAULT(0)
100 ms (4)
200 ms (5)
500 ms (6)
1 sec. (7)
 2 sec. (8)
 5 sec. (9)
 10 sec. (10)
Default DEFAULT (0) DEFAULT is converted to an actual value upon load: Converted to 500
ms for the 50 ms CEE Converted to 1000 ms for the 500 ms CEE
Config Yes
Load
Active No
Loadable
Access Engineer
Lock
Residence CEE
Related
Parameters
Remarks The Peer Update Rate (SUBSCPERIOD parameter is the rate at which this CEE
subscribes to data from other CEEs through peer-to-peer communications. In the
event of a peer-to-peer communications problem such as a broken cable, the
connection will timeout, returning an error. The valid values and function of the
DEFAULT value for SUBSCPERIOD are different for the 50 and 500 ms CEE
personalities as described below. 50 ms CEE: Valid Range: DEFAULT, 100, 200, 500,
1000 ms is converted to 500 ms upon load to a 50 ms CEE. 500 ms CEE: Valid
Range: DEFAULT, 1000 ms, 2000ms, 5000ms, 10000ms is converted to 1000 ms
upon load to a 500 ms CEE.

21.425 SUBSLOTNUM

Specific to HRBALG_PIUAI, HRBALG_HLPIUAO, HRBALG_HLPIUDI, HRBALG_HLPIUDO,


Blocks HRBALG_HLPIUCO, HRBALG_HLPIUAC, HRBALG_HLPIUDC
Description Sub Slot Number
Data Type INT8
Range AI/DO/AC: 1–8 AO: 1-4 DI/DO: 1-16
Default 1
Config. No
Load

- 2984 -
Chapter 21 - Sxxxx Parameters

Active No
Loadable
Access Lock AppDevOnly
Residence CEE
Related
Parameters
Remarks This parameter represents the subslot number in a particular slot.

Specific to Blocks All I/O Module Function Blocks


Description Sub Slot Number
Data Type UINT16
Range 1-32767
Default

Config. Load No
Active Loadable No
Access Lock ViewOnly
Residence SR
Related SLOTNUM
Parameters

Remarks Slot number of submodule. This is same as configured in tool. Cannot be changed
from form.

21.426 SUBVAL

Specific to PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Block(s)
Description Value to Substitute when error occurs
Data Type Boolean
Range True/False
Default False
Config Yes
Load
Active No
Loadable
Access Lock Application Developer Only
Residence CEE
Related SUBVALTYPE
Parameters
Remarks For PCDI Flag Array Channel block, this is a check box. When checked, the
substitution value will be True, otherwise, False. For the PCDI Numeric Array
Channel block or PCDI Text Array Channel block, this is an edit box. When an error
occurs, the value in the edit box will be set if the SUBVALTYPE parameter is set to
SUBVAL Param.

- 2985 -
Chapter 21 - Sxxxx Parameters

21.427 SUBVALTYPE

Specific to Block(s) PCDIFLAGARRCH, PCDINUMARRCH, PCDITEXTARRCH


Description Type of Value to Substitute when error occurs
Data Type Enumeration
Range 0 Last known good
1 SUBVAL Param
2 NaN
Default Last known good
Config Load Yes
Active Loadable No
Access Lock Application Developer Only
Residence CEE
Related Parameters SUBVAL
Remarks The NaN is only available for PCDINUMARRCH blocks.

21.428 SUM_MAXD

Specific to Block(s) ProfitCtl


Description SUM_MAXD
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

21.429 SUM_N_A

Specific to Block(s) ProfitCtl


Description SUM_N_A
Data Type UINT32
Range NA
Default 0
Config Load Yes

- 2986 -
Chapter 21 - Sxxxx Parameters

Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

21.430 SUM_N_B

Specific to Block(s) ProfitCtl


Description SUM_N_B
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

21.431 SUM_N_F

Specific to Block(s) ProfitCtl


Description SUM_N_F
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

- 2987 -
Chapter 21 - Sxxxx Parameters

21.432 SUM_N_S

Specific to Block(s) ProfitCtl


Description SUM_N_S
Data Type UINT32
Range NA
Default 0
Config Load No
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

21.433 SUM_N_SJL

Specific to Block(s) ProfitCtl


Description SUM_N_SJL
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters
Remarks

21.434 SUM_N_SS

Specific to Block(s) ProfitCtl


Description SUM_N_SS
Data Type UINT32
Range NA
Default 0
Config Load Yes
Active Loadable No

- 2988 -
Chapter 21 - Sxxxx Parameters

Access Lock AppDevOnly


Residence CEE
Related Parameters
Remarks

21.435 SUPVFIFORATEA

Specific to Block(s) C200 IOLINK, C300 IOLINK


Description Supervisor FIFO rate average - Currently not used.
Data Type Float32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related Parameters
Remarks

21.436 SUPVFIFORATEM

Specific to Block(s) C200 IOLINK, C300 IOLINK


Description Supervisor FIFO rate maximum - Currently not used.
Data Type Float32
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence IOLINK
Related Parameters
Remarks

- 2989 -
Chapter 21 - Sxxxx Parameters

21.437 SURPLUSSCNTIME

Specific to Block(s) TCMI


Description Surplus Scan Time
Data Type FLOAT64
Range N/A
Default 0.0
Config Load No
Active Loadable N/A
Access Lock ViewOnly
Residence NOLOAD
Related Parameters

Remarks

21.438 SWAPCTRLCMD

Specific to RM
Block(s)
Description Swap Control Command
Data Type Boolean
Range True (0) False (1)
Default N/A
Config Load No
Active No
Loadable
Access Lock Operator RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

21.439 SWAPPOSCMD

Specific to RM
Block(s)
Description Swap Position Command
Data Type Enumeration
Range Chassis_A (0) Chassis_B (1)

- 2990 -
Chapter 21 - Sxxxx Parameters

Default N/A
Config Load No
Active No
Loadable
Access Lock Operator RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

21.440 SWAPPRIMARYCMD

Specific to All redundant PM IOMs. (HLAI, HLAIHART, STI-MV, AO8, AO16, AO16HART, DI24V,
Block(s) DISOE and DO32)
Description Swap Primary I/O Processor.
Data Type Boolean
Range 0 On Swap Primary IOP
command has been
initiated.
1 Off No command.
Default Off (1)
Config No
Load
Active No
Loadable
Access Lock Operator
Residence IOLINK
Related
Parameters
Remarks Used to command the secondary IOM to become the primary IOM. This operation is
only allowed if {1} the IOM partners are synchronized and {2} if the Primary is
connected to a FTA, the Secondary must also be connected to a FTA.

21.441 SWAPSBYCMD

Specific to RM
Block(s)
Description Swap to Standby Command
Data Type Boolean
Range True (0) False (1)
Default N/A
Config Load No

- 2991 -
Chapter 21 - Sxxxx Parameters

Active No
Loadable
Access Lock Operator RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

21.442 SWITCH

Specific to HRBALG_REG block


Blocks
Description SWITCH FB reference
Data Type BLOCKID
Range Not applicable

Default NULL
Config. Load Yes
Access Lock AppDevOnly
Residence CEE
Related None
Parameters
Remarks This parameter holds a reference to the SWITCH block in the emulation CM if
the algorithm type is EC SWITCH.

21.443 SWITCHCMD

Specific to C300 and FIM4 FBs, PGM, TCMI


Block(s)
Description Initiate Switchover Command
Data Type Boolean
Range Off (0) On (1)
Default Off
Config Load No
Active No
Loadable

- 2992 -
Chapter 21 - Sxxxx Parameters

Access Lock Operator


Residence C300, FIM4, PGM
Related
Parameters
Remarks Used to command switchover to a synchronized pair of redundancy modules. This
parameter has edge trigger semantics and always returns OFF when read.

Specific to Block(s) UOC


Description Initiate Switchover
Data Type BOOLEAN
Exposure INPUT
Range N/A
Default
Config Load Yes
Active Loadable
Access Lock Operator
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

21.444 SWTCHACT

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Switch Active
Data Type Boolean
Range 0 Off Inactive
1 On Active
Default On
Config No
Load
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks When this parameter is OFF, the backup request line from the IOM's partner is NOT
asserted. When this parameter is ON, the backup request line from the IOM's
partner is asserted. This parameter does not appear on the Control Builder forms.

- 2993 -
Chapter 21 - Sxxxx Parameters

21.445 SYNCHSTS [1...40]

Specific to C200 IOLINK, C300 IOLINK


Block(s)
Description Synchronization Status. Shows the status of the IOM database synchronization,
where the index of the array corresponds to the number of the IOM.
Data Type Enumeration
Range OK (0): Redundant IOM pair is synchronized.
WARNING (1): Database inconsistency detected, but the
secondary IOM appears capable of providing
backup.
FAIL (2): IOM synchronization unsuccessful (after
retries).
NONREDUN (3): IOM not configured for redundancy.
--- (4): IOM is not configured.
Disable (5): Synchronization disabled.
Default FAIL (2)
Config Load No
Active No
Loadable
Access Lock ViewOnly
Residence IOLINK
Related
Parameters
Remarks Applies to the primary IOM only. Note that this is the same as the SYNCHSTS
parameter in a TPS system.

21.446 SYNCPINSTONUMINPUTS

Specific to Block(s) GE, GT, LE, LT, EQ, NE


Description Synchronization of input pins with number of inputs
Data Type Boolean
Range OFF, ON
Default OFF
Config Load Yes
Active Loadable No
Access Lock AppDevOnly
Residence CEE
Related Parameters -
Remarks

- 2994 -
Chapter 21 - Sxxxx Parameters

21.447 SYNCSECCMD

Specific to RM
Block(s)
Description Synchronize Secondary Command
Data Type Boolean
Range True (0) False (1)
Default True (0)
Config Load No
Active No
Loadable
Access Lock Operator RM only: Requests to read or store to any RM parameter must come from
the Supervisory platform (through Control Builder or Server).
Residence Not Loaded
Related
Parameters
Remarks

21.448 SYNCTIME

Specific to ProfitCtl
Block(s)
Description Synchronization Time
Data Type INT32
Range NA
Default 0
Config Load No
Active No
Loadable
Access Lock VIEWONLY
Residence NOLOAD
Related EXECTIME, TOTALTIME
Parameters
Remarks Once the PC block finishes execution, it needs to transfer its modified data to
redundant partner whether it is initial sync or sync maintenance. This parameter
represents time it took to transfer data. The time is in milliseconds

- 2995 -
Chapter 21 - Sxxxx Parameters

21.449 SYNCTIMEBEG

Specific to Block C300, C200, FIM, IOLIM, FTEB, FIM4 and LIOM FBs, PGM, TCMI
(s)
Description Last Synchronization Time. System-time that module completed initial
synchronization.
Data Type TIME
Range
Default 0
Config Load No
Active Loadable No
Access Lock ViewOnly
Residence C300, C200, FIM, IOLIM, FTEB, FIM4, LIOM, PGM
Related SYNCTIMEEND
Parameters
Remarks

Specific to Block(s) UOC, CN100


Description Last Synchronization Time
Data Type TIME
Exposure OUTPUT
Range
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

21.450 SYNCTIMEEND

Specific to Block(s) C300, C200, FIM, IOLIM, FTEB, FIM4 and LIOM FBs, PGM, TCMI
Description Last Sync Lost Time. System-time that module last lost synchronization.
Data Type TIME
Range
Default 0
Config Load No
Active Loadable No

- 2996 -
Chapter 21 - Sxxxx Parameters

Access Lock ViewOnly


Residence C300, C200, FIM, IOLIM, FTEB, FIM4, LIOM, PGM
Related Parameters SYNCTIMEBEG
Remarks

Specific to Block(s) UOC


Description Last Loss of Sync Time
Data Type TIME
Exposure OUTPUT
Range
Default 0
Config Load No
Active Loadable
Access Lock ViewOnly
Residence NOLOAD
Related Parameters
Remarks (redundancy parameters, see C300 definition)

21.451 System Template

Specific to Block(s) Server, Asset, Alarm Group


Description System Template name - Indicates the System Template that is source for
this block.
Data Type String
Range Limit: 5 characters
Default Null
Config Load
Active Loadable No
Access Lock
Residence
Related
Parameters
Remarks

- 2997 -
CHAPTER

22 TXXXX PARAMETERS

22.1 T 3006
22.2 T0 3007
22.3 T1 3007
22.4 T1HILM 3008
22.5 T1LOLM 3008
22.6 T2 3008
22.7 T2HILM 3009

22.8 T2LOLM 3009


22.9 TAGEXECSTATUS 3010
22.10 Tag Name 3010
22.11 TAGPARENT 3011
22.12 TAGTYPE 3011
22.13 TAGRDEXTSTATUS 3012
22.14 TAGRDGENSTATUS 3013
22.15 TARGETERROR[1..200] 3014
22.16 TARGETNAME 3015
22.17 TARGETPLATFORM 3015
22.18 TARGETSTEP[1..15] 3016
22.19 TARGETSTEPN[1..15] 3016
22.20 TASKHLTHMON 3017
22.21 TASKSTACKHILM 3017
22.22 TASKSTACKSIZE [0...N] 3018
22.23 TASKSTACKUSED [0...N] 3018
22.24 TAU 3019
22.25 TBADREADS 3019
22.26 TBREF[0..2] 3020
22.27 TCDISPAVGPPS 3020
22.28 TCDISPMAXPPS 3021
22.29 TCMICURRENTSTATE 3021
22.30 TCMIANDTCMKEYSWPOSMISMATCH 3022
22.31 TCMIAUTHSERVERIP 3022
22.32 TCMIAUTHSTS 3023

- 2998 -
Chapter 22 - Txxxx Parameters

22.33 TCMICOMMAND 3023


22.34 TCMIDOWNLINKIP 3024
22.35 TCMIDOWNLINKRXERROR 3024
22.36 TCMIDOWNLINKRXRATE 3025
22.37 TCMIDOWNLINKTXERROR 3025
22.38 TCMIDOWNLINKTXRATE 3026
22.39 TCMIDRIFTVALUE 3026
22.40 TCMIIPADDRLEFT 3027
22.41 TCMIIPADDRRIGHT 3027
22.42 TCMIMULTIIPADDRSTR 3028
22.43 TCMINODETYPE 3028
22.44 TCMINUM 3029
22.45 TCMIPRIMARYKEYSWITCH 3029
22.46 TCMIPRIVATEPATHIP 3030

22.47 TCMIPRIVATEPATHRXERROR 3030


22.48 TCMIPRIVATEPATHTXERROR 3031
22.49 TCMIPRIVATEPATHRXRATE 3031
22.50 TCMIPRIVATEPATHTXRATE 3032
22.51 TCMINODEDATE 3032
22.52 TCMINODETIME 3033
22.53 TCMISECKEYSWITCH 3033
22.54 TCMISTATE 3034
22.55 TCMISYNCHERNODE 3034
22.56 TCMITIMESYNCFAIL 3035
22.57 TCMKEYSWITCH 3035
22.58 TCMVERSION 3036
22.59 TCMPROGRAM 3036
22.60 TCPACTIVEOPENS 3036
22.61 TCPATTEMPTFAILS 3037
22.62 TCPCONNNUM 3038
22.63 TCPCONNTABLE 3038
22.64 TCPCURRESTAB 3038
22.65 TCPEERAVGPPS 3039
22.66 TCPEERMAXPPS 3039
22.67 TCPESTABRESETS 3040
22.68 TCPINCSUMERRS 3040
22.69 TCPINERRS 3041
22.70 TCPINSEGS 3041
22.71 TCPMAXCONN 3042

- 2999 -
Chapter 22 - Txxxx Parameters

22.72 TCPOUTRESETS 3042


22.73 TCPOUTSEGS 3042
22.74 TCPPASSIVEOPENS 3043
22.75 TCPRETRANSSEGS 3044
22.76 TCPRTOALGO 3044
22.77 TCPRTOMAX 3044
22.78 TCPRTOMIN 3045
22.79 TCRNGOPT 3045
22.80 TEMPAVG 3046
22.81 TEMPCRIT 3046
22.82 TEMPCRITLM 3047
22.83 TEMPCURA 3047
22.84 TEMPCURB 3048
22.85 TEMPERATURE 3048

22.86 TEMPERATUREENGUNIT 3049


22.87 TEMPERATUREIO 3049
22.88 TEMPHILM 3050
22.89 TEMPLOLM 3051
22.90 TEMPMAX 3052
22.91 TEMPMAXA 3052
22.92 TEMPMAXB 3053
22.93 TEMPMIN 3053
22.94 TEMPMINA 3054
22.95 TEMPMINB 3054
22.96 TEMPMODE 3055
22.97 TEMPUNITS [0..NUMCHANNELS-1] 3055
22.98 TERMSTATEOPT 3056
22.99 TESTDATASAVE 3056
22.100 TESTOPT 3057
22.101 TESTPAR_Boolean [6] 3057
22.102 TESTPAR_CONTEXT 3058
22.103 TESTPAR_FLOAT64 [6] 3058
22.104 TESTPAR_UINT32 [6] 3059
22.105 TEXTCOLOR 3059
22.106 TEXTCOMMENT 3060
22.107 TEXTSIZE 3060
22.108 TF 3061
22.109 TGTAPPCONNID[1..24] 3061
22.110 TGTCONNSTATE [1..20] 3062

- 3000 -
Chapter 22 - Txxxx Parameters

22.111 TGTCONNSTATE[1..24] 3062


22.112 TGTIP 3063
22.113 TGTRECVMSGRATE [1..20] 3063
22.114 TGTRESENTMSGCNT [1..20] 3063
22.115 TGTRNDTRIPAVG [1..20] 3064
22.116 TGTRNDTRIPMAX [1..20] 3064
22.117 TGTRNGDEF 3065
22.118 TGTRNGDEFOPT 3065
22.119 TGTSENTMSGRATE [1..20] 3065
22.120 TGTTCLASS[1..24] 3066
22.121 THERMERR 3066
22.122 THERMOCOUPLETYPE 3067
22.123 THREAD[1..10] 3069
22.124 THRESHOLD 3069

22.125 TIME 3070


22.126 TIME[1..8] 3070
22.127 TIMEBASE 3071
22.128 TIMEBASE[0..7] 3072
22.129 TIMEIN 3073
22.130 TIMEOUT 3073
22.131 TIMELASTSKEW 3074
22.132 TIMELASTSYNC 3074
22.133 TIMEPASTTHISSEG 3075
22.134 TIMER1 3076
22.135 TIMER2 3076
22.136 TIMER3 3077
22.137 TIMER4 3077
22.138 TIMER5 3078
22.139 TIMER6 3078
22.140 TIMESOURCE 3079
22.141 TIMESYNCSTAT 3080
22.142 TIMETOFINISH[1..24] 3080
22.143 TIMETOFINISH[1..200] 3081
22.144 TIMETORESAVE 3081
22.145 TIMETOSAVE1 3082
22.146 TIMETOSAVE2 3083
22.147 TIMOUT[0..15] 3083
22.148 TIMOUTCNT[0..15] 3084
22.149 TIMEZONE 3084

- 3001 -
Chapter 22 - Txxxx Parameters

22.150 TINUMINMSGAVGPS 308