High Performance,
4th Generation
Guided Wave Radar
Level Transmitter
2014/68/EU
Read this Manual Before Installing WARNING! Explosion hazard. Do not connect or dis-
This manual provides information on the Eclipse® trans- connect designs rated Explosion proof or Non-incendive
mitter. It is important that all instructions are read care- unless power has been switched off and/or the area is
fully and followed in sequence. The QuickStart known to be non-hazardous.
Installation instructions are a brief guide to the sequence
of steps for experienced technicians to follow when Low Voltage Directive
installing the equipment. Detailed instructions are For use in Installations Category II, Pollution Degree 2.
included in the Complete Installation section of this manual. If equipment is used in a manner not specified by the
manufacturer, protection provided by equipment may be
Conventions Used in this Manual impaired.
Certain conventions are used in this manual to convey
specific types of information. General technical material, Notice of Copyright and Limitations
support data, and safety information are presented in Magnetrol® & Magnetrol® logotype and Eclipse®
narrative form. The following styles are used for notes, are registered trademarks of Magnetrol® International,
cautions, and warnings. Incorporated.
Copyright © 2018 Magnetrol® International, Incorporated.
NOTES
All rights reserved.
Notes contain information that augments or clarifies an
operating step. Notes do not normally contain actions. MAGNETROL reserves the right to make changes to the
They follow the procedural steps to which they refer. product described in this manual at any time without
notice. MAGNETROL makes no warranty with respect
Cautions to the accuracy of the information in this manual.
Cautions alert the technician to special conditions that
could injure personnel, damage equipment, or reduce Warranty
a component’s mechanical integrity. Cautions are also All MAGNETROL electronic level and flow controls are
used to alert the technician to unsafe practices or the warranted free of defects in materials or workmanship for
need for special protective equipment or specific eighteen months from the date of original factory ship-
materials. In this manual, a caution box indicates a ment. If returned within the warranty period; and, upon
potentially hazardous situation which, if not avoided, factory inspection of the control, the cause of the claim is
may result in minor or moderate injury. determined to be covered under the warranty; then,
WARNINGS MAGNETROL will repair or replace the control at no cost
Warnings identify potentially dangerous situations or to the purchaser (or owner) other than transportation.
serious hazards. In this manual, a warning indicates an MAGNETROL shall not be liable for misapplication,
imminently hazardous situation which, if not avoided, labor claims, direct or consequential damage or expense
could result in serious injury or death. arising from the installation or use of equipment. There
are no other warranties expressed or implied, except spe-
Safety Messages cial written warranties covering some MAGNETROL
The ECLIPSE system is designed for use in Category II, products.
Pollution Degree 2 installations. Follow all standard
industry procedures for servicing electrical and computer Quality Assurance
equipment when working with or around high voltage. The quality assurance system in place at MAGNETROL
Always shut off the power supply before touching any guarantees the highest level of quality throughout the
components. Although high voltage is not present in this company. MAGNETROL is committed to providing
system, it may be present in other systems. full customer satisfaction both in quality products and
quality service.
Electrical components are sensitive to electrostatic discharge.
To prevent equipment damage, observe safety procedures The MAGNETROL quality assurance system is registered
when working with electrostatic sensitive components. to ISO 9001 affirming its commitment to known interna-
tional quality standards providing the strongest assurance
This device complies with Part 15 of the FCC rules. of product/service quality available.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received,
including interference that may cause undesired operation.
1.2.1 Probe
1. Carefully place the probe into the vessel. Align the probe
process connection with the threaded or flanged mounting
on the vessel.
2. Tighten the hex nut of the probe process connection or
flange bolts.
NOTES: Leave the plastic protective cap in place on the probe until you
are ready to install the transmitter. Do not use sealing com-
pound or TFE tape on probe connection to transmitter as this
connection is sealed with a Viton® o-ring.
If using a segmented probe or removable rod, ensure that all
pieces are assembled and connected before installation.
√ ƒ 1.2.2 Transmitter
3. Remove the protective plastic cap from the top of the probe
and store for future use. Make sure the top probe connector
¬ ≈ (male connection) is clean and dry. Clean with isopropyl
alcohol and cotton swabs if necessary.
4. Carefully place the transmitter onto the probe. Align the
¡
universal connection at the base of the transmitter housing
with the top of the probe. Only hand-tighten the connec-
¿ tion at this point in time.
5. Rotate the transmitter so that it is in the most convenient
position for wiring, configuring and viewing.
6. Using a 11⁄2" (38 mm) wrench, tighten the universal connec-
tion on the transmitter 1⁄4 to 1⁄2 turn beyond hand-tight. As
this is a critical connection, a torque wrench is highly
recommended to obtain 45 ft-lbs (60 Nm).
DO NOT LEAVE HAND-TIGHT.
NOTE: The ECLIPSE Model 706 transmitter can be supplied with a
universal connector containing lock screws for applications
with significant vibration. Contact the factory for additional
information.
Black (-) Red (+) NOTE: Ensure that the electrical wiring to the ECLIPSE Model 706
transmitter is complete and in compliance with all local regula-
tions and codes.
(+)
(-) 1. Remove the cover of the upper wiring compartment of the
Model 706 transmitter.
2. Attach a conduit fitting and mount the conduit plug in the
spare opening. Pull the power supply wire through the con-
duit fitting.
3. If present, connect cable shield to an earth ground at the
power supply.
4. Connect an earth ground to the nearest green ground screw.
(Not shown in illustration.)
5. Connect the positive supply wire to the (+) terminal and the
negative supply wire to the (-) terminal. For Explosion
Proof Installations, see Wiring, Section 2.5.3.
6. Replace and tighten the cover.
Dielectric
The graphic LCD display can be programmed to change
of Medium every 2 seconds to show pertinent Measured Values on the
Home Screen. For example: Level, %Output, and Loop
4 mA Level
(0%-point) current can all be displayed on a rotating screen.
Level Offset
The LCD can also be programmed to always show just one
of the Measured Variables at all times. For example: Level
NOTE: A small transition zone (0–12") can be the only value displayed on the screen.
(0-300 mm) may exist at the top
and bottom of certain probes. 2. Remove the lower electronic compartment cover.
➪
UP moves up through the menu or increases a displayed
value.
➪
DOWN moves down through the menu or decreases a
displayed value.
➪
BACK exits a branch of the menu or exits without
accepting entered value.
➪ ENTER enters a branch of the menu or accepts a
displayed entry.
Probe Length Enter the exact Probe Length as printed on the probe nameplate. Probe Length is shown
as the last three digits of the Probe Model number. Range is 12 inches to 100 feet (30 cm
to 30 meters) probe dependent. Refer to Section 1.4.1.1.
Level Offset Enter the desired level reading when the liquid is at the end of the probe. Range is -25 feet
to 75 feet (-762 cm to 22 meters). Refer to Section 3.4 for further information. (With default
Level Offset = 0, all measurements are referenced from the bottom of the probe.)
Dielectric Range Enter the Dielectric Range for the material to be measured.
Below 1.7 (Light Hydrocarbons like Propane and Butane)
1.7 to 3.0 (Most typical hydrocarbons)
3.0 to 10 (Varying dielectric, for example: mixing tanks)
Above 10 (Water-based media)
4 mA Set Point Enter the level value (0%-point) for the 4 mA point. Lower Range Value (LRV).
(LRV) Refer to Section 1.4.1.1.
20 mA Set Point Enter the level value (100%-point) for the 20 mA point. Upper Range Value (URV).
HART Only
➪
UP moves up to the next highest digit (0,1,2,3,....,9 or
the decimal point).
If held down the digits scroll until the push button is
released.
➪
DOWN moves up to the next lowest digit (0,1,2,3,....,9
or the decimal point). If held down the digits scroll until
the push button is released.
➪
BACK moves the cursor to the left and deletes a digit.
If the cursor is already at the leftmost position, then the
screen is exited without changing the previously saved
value.
➪ ENTER Moves the cursor to the right. If the cursor is
located at a blank character position, the new value is
saved.
Scrolling further DOWN in the QuickStart menu results in
the remaining parameters appearing one by one, with the
present highlighted value shown at the bottom of the
screen.
➪
BACK returns to the previous menu without changing
the original value, which is immediately redisplayed.
➪ ENTER accepts the displayed value and returns to the
previous menu.
Negative values can be entered by highlighting the “+” sign
shown prior to the number, then pressing UP to change it
to show “-”.
2.1 Unpacking
Model Number
Serial Number
NOTE: Models 7yD, 7yJ, 7yL, 7yM, 7yN, 7yP and 7yS High
Temperature/High Pressure probes (containing a glass ceramic
alloy process seal) should be handled with extra care. Only
handle these probes by the flanges or NPT connections.
NOTE: If using a removable rod, ensure that all pieces are assembled
and connected before installation.
1. Ensure that the nozzle does not restrict performance by
ensuring the following:
• Nozzle is > 2" (50mm) diameter.
• Ratio of Diameter: Length (A:B) is 1:1 or greater; any ratio
<1:1 (e.g., a 2"¥ 6" nozzle = 1:3) may require a Blocking
Distance and/or DIELECTRIC RANGE adjustment.
2. No pipe reducers (restrictions) are used.
3. Probe is kept away from conductive objects to ensure proper
performance.
• See Probe Clearance Table below. A lower gain (increase in
DIELECTRIC RANGE setting) may be necessary to ignore
certain objects
• This table is only a recommendation. These distances can
be improved by optimizing the transmitter configuration
with PACTware™.
Distance
Acceptable Objects
to Probe
Continuous, smooth, parallel conductive sur-
<6" (15 cm) face, for example a metal tank wall; important
that probe does not touch wall
<1" (25 mm) diameter pipe and beams,
>6" (15 cm)
ladder rungs
<3" (75 mm) diameter pipe and beams,
>12" (30 cm)
concrete walls
NOTES:
1) If the transmitter is to be installed at a later time, do not
remove the protective cap from the probe.
2) Do not use sealing compound or TFE tape on probe con-
nection to transmitter as this connection is sealed by a
Viton® O-ring.
➀
3. Align the universal connection at the base of the transmitter
housing with the top of the probe. Only hand-tighten the
➄ connection at this time.
➂ 4. Rotate the transmitter to face the most convenient direction
for wiring, configuration, and viewing.
5. When the transmitter is facing the desired direction, use a
11⁄2" wrench to tighten the universal connection on the
transmitter to 45 ft-lbs (60 Nm). A torque wrench is highly
recommended. This is a critical connection. DO NOT
LEAVE HAND-TIGHT.
2.6 Configuration
Up
No action as the cursor is already at the first
item in the MAIN MENU
Down Moves the cursor to DIAGNOSTICS
Back
Moves back to HOME SCREEN, the level
above MAIN MENU
Enter Presents the selected item, DEVICE SETUP
NOTES: 1. Items and parameters that are shown in lower level menus
will depend on the Measurement Type chosen. Those para-
meter not applicable to the present Measurement Type will
be hidden.
2. Holding down the Enter key when the cursor is highlighted
over a parameter or menu will provide additional information
about that item.
DEVICE SETUP
Choosing DEVICE SETUP from the MAIN MENU will
result in an LCD presentation as shown at left.
The small down arrow shown at the right hand side of the
screen is the indication that more items are available below
and can be accessed by pressing the DOWN key.
Section 2.6.5 shows the entire tree menu for the Model 706
DEVICE SETUP Menu.
DIAGNOSTICS
Refer to Section 3.3.4
MEASURED VALUES
Allows the user to scroll through all of the available
measured values for the measurement type chosen.
Main Menu
Main Menu
Level Units: Probe Coating: (7yF only) Volume Units: Vessel Dimensions:
Inches None (Bare) Cubic Feet (not used with Custom Table)
Feet PFA Coated Cubic Inches Radius
Millimeters Gallons Ellipse Depth
Centimeters Probe Mount: Milliliters Conical Height
Meters NPT Liters Width
BSP Length
Probe Model: Flange Vessel Type:
7YD Coax HTHP NPT/Flushing Rectangular Custom Table Setup:
7YF Sngl Rod Std BSP/Flushing Horizontal/Flat Custom Table Type:
7YG Sngl Rod Std Flange/Flushing Horizontal/Ellipse Linear
7YJ Sngl Rod HTHP Hygienic Horizontal/Spherical Spline
7YL Sngl Rod HP Spherical
Level Input Source:
7YM Sngl Rod HP Probe Length: Vertical/Flat
Vertical/Ellipse Keypad
7YN Sngl Rod HTHP 12 inches to 100 feet
Vertical/Spherical Sensor
7YP Coax HP (30 cm to 30 m)
7YS Coax Steam Vertical/Conical
CUSTOM TABLE VALUES:
7YT Coax Std Level Offset: Custom Table
Up to 30 Pairs of
7Y1 Sngl Flex Std -25 feet to +75 feet
Level/Volume Data
7Y2 Sngl Flex Bulk (-7.6 m to 22.9 m)
7Y3 Sngl Flex HP
7Y5 Twin Flex Bulk Dielectric Range:
7Y6 Sngl Flx HTHP Cage Below 1.7
7Y7 Twin Flex Clad 1.7 to 3.0
3.0 to 10
Above 10
Volume Setup:
Main Menu
Level Units: Probe Mount: Flow Units: V-notch Weir Maximum Flow
Inches NPT Cubic Ft/Second V-notch Weir Angle: (calculated, read only)
Feet BSP Cubic Ft/Minute 22.5°
Millimeters Flange Cubic Ft/Hour 30° Low Flow Cutoff:
Centimeters NPT/Flushing Gallons/Minute 45° 0 to 9999999 cubic
Meters BSP/Flushing Gallons/Hour 60° ft/min
Flange/Flushing Mil Gallons/Day 90°
Probe Model: Hygienic Liters/Second 120° TOTALIZER SETUP:
7YD Coax HTHP Liters/Minute Units:
7YF Sngl Rod Std Probe Coating: Liters/Hour Rect Weir with Ends Cubic Feet
7YG Sngl Rod Std None (Bare) Cubic Meters/Hour 0 to 215.0 feet Gallons
7YJ Sngl Rod HTHP PFA Coated (0 to 65 m) Mil Gallons
7YL Sngl Rod HP Flow Element: Liters
7YM Sngl Rod HP Probe Length: Palmer-Bowlus Flume Rect Weir w/o Ends Mil Liters
7YN Sngl Rod HTHP 12 inches to 100 feet Flume Channel Width: 0 to 215.0 feet Cubic Meters
7YP Coax HP (30 cm to 30 m) 4 inches (0 to 65 m)
7YS Coax Steam 6 inches NON-RESET
7YT Coax Std Level Offset: 8 inches Cipolletti Weir TOTALIZER:
7Y1 Sngl Flex Std -25 feet to +75 feet 10 inches 0 to 215.0 feet Multiplier:
7Y2 Sngl Flex Bulk (-7.6 m to 22.9 m) 12 inches (0 to 65 m) 1
7Y3 Sngl Flex HP 15 inches 10
7Y5 Twin Flex Bulk Dielectric Range: 18 inches Generic Equation 100
7Y6 Sngl Flx HTHP Cage Below 1.7 21 inches K 1,000
7Y7 Twin Flex Clad 1.7 to 3.0 24 inches L 10,000
3.0 to 10 27 inches C 100,000
Above 10 30 inches n
Value (read only)
Flow Setup: Parshall Flume Custom Table RunTime (read only)
Flume Channel Width: Custom Table Type:
1 inch Linear RESETTABLE
2 inches Spline TOTALIZER:
3 inches Mode:
6 inches CUSTOM TABLE Disabled
9 inches VALUES: Enabled
12 inches Up to 30 Pairs of
18 inches Head/Flow Data Multiplier:
24 inches 1
36 inches Reference Distance: 10
48 inches 11.8 inches to 100 feet 100
60 inches (30 cm to 30 m) 1,000
72 inches 10,000
96 inches Maximum Head 100,000
120 inches The Maximum Head
144 inches value can be revised Value (read only)
depending on the value RunTime (read only)
of the Reference
Distance, or for end user Reset
preference.
Main Menu
4 mA Set Pt (LRV):
-25 to +175 feet ([Upr] Level, Ifc Level)
(-7.6 m to 53 m)
2.0 inches to 100 feet (Upr Thickness)
(5 cm to 30 m)
0 to 9999999 gals (Volume)
0 to 9999999 cubic ft/min (Flow)
20 mA Set Pt (URV):
-25 to +175 feet ([Upr] Level, Ifc Level)
(-7.6 m to 53 m)
2.0 inches to 100 feet (Upr Thickness)
(5 cm to 30 m)
0 to 9999999 cf (Volume)
0 to 9999999 cfs (Flow)
Failure Alarm:
22 mA
3.6 mA
Hold
Damping:
0 to 10 seconds
Level: % Output:
Hide Hide
View View
Main Menu
Main Menu
NAP Value
Factory Reset
FACTORY CALIB
(Factory password required)
Window
Fiducial Ticks
Conversion Factor
Scale Offset
2.7.1 Connections
Control
Room
Display A HART communicator can be operated from a remote
Power location by connecting it to a remote junction or by con-
Supply
necting it directly to the terminal block in the wiring com-
partment of the ECLIPSE transmitter.
Current
Meter HART uses the Bell 202 frequency shift keying technique
of high-frequency digital signals. It operates on the 4–20
mA loop and requires 250 Ω load resistance. A typical con-
nection between a communicator and the ECLIPSE trans-
mitter is shown at left.
6 Local Display
Config 1 Enter Password
2 Language
3 Status Symbol 1 Safety Zone Alarm
4 Long Tag 2 Safety Zone Height
5 PV Bar Graph 3 Reset SZ Alarm
6 Display Setup Diagram
7 Measured Values
1 Reject Curve State
2 Reject Curve Mode
3 Saved Media Location
4 New Rejection Curve
1 Poll Address
2 Analog Output Mode
3 Fixed Loop Current
4 Adjust Analog Output
5 4mA Trim Value
6 20mA Trim Value
7 Fdbk 4mA Trim Value
8 Fdbk 20mA Trim Value
1 Window
2 Fiducial Ticks
3 Conversion Factor
4 Scale Offset
5 7YK Scale Offset
1 NE 107 Mapping
2 Reset NE 107 Mapping
1 Present Temperature
2 Max Temperature
3 Min Temperature
4 Reset Min/Max Temps
1 Analog OutputTest
Dry
Echo Lost
Out of
In this example, “Calibration Required” is mapped to both
High
Temperature
Probe Specification the Out of Specification and Maintenance Required status
signals, and the diagnostic indicator named “High
Calibration
Required
Temperature” is mapped to none of the signals.
Maintenance
Required Indicators that are mapped to the Failure category will nor-
mally result in a current loop alarm output. The alarm state
for HART transmitters is configurable as high (22 mA),
Diagnostic Indicators NE-107
Status Signals Low (3.6 mA), or Hold (last value).
Users will not have the ability to unassign certain indicators
from the Failure signal category as the Model 706 user
interfaces will prohibit or reject such re-assignment entries).
This is to ensure that current loop alarms are asserted in situ-
ations where the device is not able to provide measurements
due to critical failures. (For example, if the alarm selection
has not been set to Hold, or a fixed current mode is in
effect.)
A default mapping of all diagnostic indicators will be applied
initially, and can be re-applied through use of a reset function.
Software Error
Unrecoverable error occurred in stored
1 Failure
program.
2 RAM Error Failure RAM (read/write) memory failing.
3 ADC Error Failure Analog-to-digital converter failure. Contact MAGNETROL Technical Support.
Analog Output
Actual loop current deviates from com-
Error
Perform Adjust Analog Output mainte-
6 Failure manded value. Analog output is inaccu-
nance procedure.
rate.
7 Spare Indicator 1 OK Reserved for future use.
Default
Parameters
Saved parameters are set to default val-
8 Perform complete Device Configuration.
ues.
Attach a probe.
Torque HF nut.
No Probe
Clean gold pin on transmitter and socket
9 Failure No Probe Connected. on probe.
Ensure Model 705 style probe is not
being used.
Contact MAGNETROL Technical Support.
Torque HF nut.
Clean gold pin on transmitter and socket
on probe.
No Fiducial
Check settings:
10 Failure Reference signal too weak to detect. Fiducial Gain
HF Cable Length
Window
Increase Fid Gain.
Contact MAGNETROLTechnical Support.
Check settings:
Dielectric Range
No Echoes
Sensitivity
11 Failure No signal detected anywhere on probe. EoP Thresh Value
Increase Sensitivity.
Lower EoP Thresh.
View Echo Curve.
Check settings:
Upper Dielectric,
Check settings:
EoP Above
Probe Length
ProbeEnd
End of Probe appears above Probe
14 Failure Decrease Sensitivity
Length
Increase Blocking Distance
View Echo Curve.
Check settings:
Lvl Below
Probe Model,
Level signal appears beyond Probe
ProbeEnd
Probe Length,
15 Failure Length.
Level Threshold = Fixed
(Possible water bottom situation)
Increase Sensitivity
View Echo Curve.
Check settings:
EoP Below
Probe Length
ProbeEnd
End of Probe appears beyond Probe
16 Failure Dielectric Range
Length.
Sensitivity
View Echo Curve.
Config Conflict
Measurement type and primary variable Confirm proper configuration.
18 Failure
selection parameters are inconsistent. Check Measurement Type.
Check settings:
Initializing
Function Distance measurement is inaccurate Standard start-up message. Wait for up
22
Check while internal filters are settling. to 10 seconds.
Analog Output
Loop current not following PV. May be If unexpected, check Loop Current
Fixed
Function
23 caused by existing alarm condition, ongoing Mode. Ensure device is not in Loop
Check
Loop Test or Trim Loop operations. Test.
Config Changed
Function A parameter has been modified from the If desired, reset Config Changed indica-
24
Check User Interface. tor in ADVANCED CONFIG menu.
Default
Priority Indicator Name Explanation Remedy
Category
25 Spare Indicator 4 OK Reserved for future use.
Ramp Interval
Check accuracy of Level reading.
Error
Internal signal timing out of limits causing
27 Out of Spec Replace transmitter electronics.
inaccurate distance measurement.
Contact MAGNETROL Technical Support.
Echo Reject
Echo Rejection inoperative. May report
Invalid
31 Out of Spec erroneous Level readings. Upr Echo Save a fresh Echo Rejection Curve.
may be lost near top of probe.
Inferred Level
Distance measurement calculated indi- Verify Level reading. If incorrect, com-
32 Out of Spec rectly from probe elongation. Level pare Dielectric Range against EoP
reading is only approximate. Dielectric reading.
Totalizer Data
Lost
Non-volatile Totalizer Data storage fail- Contact MAGNETROL Technical
34 Out of Spec
ing. Support.
No Probe Target
Check settings:
35 Out of Spec Not actively compensating Probe Model
Sensitivity
Low Supply
Voltage
Loop current may be incorrect at high- Verify loop resistance.
36 Out of Spec
er values. Analog output is inaccurate. Replace loop power supply.
Dry Probe
No liquid is contacting probe. Level at If unexpected, verify proper probe
37 OK
unknown distance beyond probe. length for application.
38 Spare Indicator 6 OK Reserved for future use.
Check settings:
Low Echo Strength
Maintenance Dielectric Range
39 Risk of Echo Lost due to weak signal.
Required Sensitivity
View Echo Curve.
Check settings:
Low Ifc Echo Str
Maintenance Risk of Interface Echo Lost due to Dielectric Range
40
Required weak signal. Sensitivity
View Echo Curve.
Sequence Record
A Sequence Record number has been If desired, report Sequence Record
42 OK
stored in Event Log. number to factory.
The ECLIPSE Model 706 offers the ability to do Trending and Echo Curve analysis via the local graphical LCD or by using PACTware and the Model 706 DTM.
The Model 706 DTM is a power troubleshooting tool that can aid in the resolution of some of the Diagnostic Indicators shown above.
➪
explanation pairs) exceeds the available space, a appears
in the rightmost column of the last line indicating more text
below. In this situation, the DN key scrolls text up one line
at a time. Similarly, while text exists above the upper line of
➪
the text field, a appears in the rightmost column of the
top (text) line. In this situation, the UP key scrolls the text
down one line at a time. Otherwise the DN and UP keys
are inoperative. In all cases the ENT or DEL key reverts to
the previous screen.
When the transmitter is operating normally and the high-
light cursor is positioned on Present Status, the bottom
LCD line displays “OK” because no diagnostic indicators
are active.
EVENT HISTORY – This menu displays the parameters
related to diagnostic event logging.
ADVANCED DIAGNOSTICS – This menu displays para-
meters related to some of the advanced diagnostics available
within the Model 706.
INTERNAL VALUES – Displays read-only internal
parameters.
ELEC TEMPERATURES – Displays temperature
information as measured in the potted module in
degrees F or C.
TRANSMITTER TESTS – Allows the user to
manually set the output current to a constant value.
This is a method for the user to verify operation of the
other equipment in the loop.
ECHO CURVES – This menu allows the user to display
the live Echo Curve and Echo Rejection on the LCD.
52 57-606 ECLIPSE Model 706 Guided Wave Radar Transmitter
ECHO HISTORY SETUP – The Model 706 contains the
unique and powerful feature that allows waveforms to be
automatically captured based on Diagnostic Events, Time or
both. This menu contains those parameters that configure
that feature.
Eleven (11) waveforms can be saved directly into the trans-
mitter.
• Nine (9) Troubleshooting Curves
• One (1) Echo Rejection Curve
• One (1) Reference Curve
TREND DATA – A 15-minute trend of the PV can be
displayed on the LCD.
Nozzles
Due to the impedance mismatch that takes place at the end
Coaxial Probe of a nozzle, they can create false echoes that can cause diag-
nostic indicators and/or errors in measurement.
As mentioned above, by virtue of the pure physics of the
technology, all single rod GWR probes are influenced by
the application and installation. Mismatches in impedance
Large Impedance along the length of the probe, whether they be expected
Mismatch
(liquid level) or unexpected (metal in close proximity), will
result in reflections.
To better illustrate this, a comparison between a coaxial
probe and single rod probe mounted in the same application
is shown at left.
NOTE: Use caution when rejecting large positive going signals as the
negative going level signal can be lost when passing through
them.
PROBE CLEARANCE TABLE
Distance Acceptable Objects
to Probe
Continuous, smooth, parallel conductive surface, for example a metal tank wall;
<6" (15 cm)
important that probe does not touch wall
>6" (15 cm) <1" (25mm) diameter pipe and beams, ladder rungs
>12" (30 cm) <3" (75mm) diameter pipe and beams, concrete walls
20 mA = 30 in
Located in the DEVICE SETUP/ADVANCED CONFIG
Menu, this feature is patterned after the “Tank-Bottom
Example 3 Following” algorithms of the early Non-Contact radar
transmitters. When the return signal from the level is lost,
this feature allows the Model 706 transmitter to infer level
measurement based on the apparent location of the end-of-
probe (EoP) signal.
Due to the fact that the propagation of the GWR signal is
affected by the dielectric constant of the medium in which
it is traveling, signals along the probe are delayed in propor-
tion to the dielectric constant. By monitoring the location
of the (delayed) EoP signal and knowing the dielectric con-
stant of the medium, the level signal can be back-calculated,
or inferred.
The End-of-Probe Analysis feature is located in the
Advanced Config menu and requires an Advanced Password
to activate. Several additional parameters will need to be
configured for optimum performance.
A selection of Gallons (factory default Volume Unit), Milliliters, Liters, Cubic Feet, or Cubic
Volume Units
Inches, is provided.
Vessel Dims See the vessel drawings on the following page for relevant measuring areas.
Radius Used for all Vessel Types with the exception of Rectangular.
hoRIzonTal/sphERICal
sphERICal
hoRIzonTal/EllIpTICal
VERTICal/EllIpTICal VERTICal/sphERICal
RECTangulaR
VERTICal/FlaT VERTICal/ConICal
hoRIzonTal/FlaT
Vessel Type Select Custom Table if none of the nine Vessel Types can be used.
The Custom Table points can be a Linear (straight line between adjacent points) or
Cust Table Type Spline (can be a curved line between points) relationship. See below drawing for
more information.
A maximum of 30 points can be used in building the Custom Table. Each pair of
values will have a level (height) in the units chosen in the Level Units screen, and
the associated volume for that level point. The values must be monotonic, i.e.
Cust Table Vals
each pair of values must be greater than the previous level/volume pair. The last
pair of values should have the highest level value and volume value associated
with the level in the vessel.
P9
P8
P2
Transition P7
point P6
P5
P4
P3
P1 P2
LINEAR SPLINE
Model
706
Blocking Distance
10" (250 mm) min.
Reference
Distance
Water Surface
Throat Section
Head
Flow
Model
706
10" (250 mm)
minimum
Distance
Blocking
Reference
Distance
Water Surface Crest
Head
Weir Plate
Channel Floor
Select one of the following primary Flow Elements that are stored in the firmware:
Parshall flume sizes of 1", 2", 3", 6", 9", 12", 18", 24", 36", 48", 60", 72", 96",
120" and 144". Palmer-Bwls (Palmer-Bowlus) flume sizes of 4", 6", 8", 10", 12",
15", 18", 21", 24", 27" and 30". V-notch weir sizes of 22.5O, 30O, 45O, 60O, 90O and
Flow Element 120O. Rect with Ends (Rectangular Weir with End Contractions), Rect w/o Ends
(Rectangular Weir without End Contractions), and Cipoletti weir. Custom Table (see
page 65 can be selected if none of the stored Flow Elements can be used. The
table can be built with a maximum of 30 points. The Model 706 also has the capa-
bility of using a Generic Equation (see page 26) for flow calculation.
The Weir Crest Length screen only appears when the chosen Flow Element is
Weir Crest Length Cipoletti or one of the Rectangular weirs. Input this length in the user-selected
level units.
Flume Channel Width Allows for entry of the width of the palmer bowlus flume.
Only appears when flow element is V-Notch weir. It allows for the entry of angle of
V-Notch Weir Angle
the V-Notch weir.
The Reference Distance is measured from the sensor reference point to the point
Reference Dist of zero flow in the weir or flume. This must be measured very accurately in the
user-selected level units.
Maximum Head is the highest liquid level (Head) value in the flume or weir before
the flow equation is no longer valid. The Maximum Head is expressed in the user-
Maximum Head selected Level Units. The Model 706 will default to the largest Maximum Head value
that is allowed for any given flume or weir. The Maximum Head value can be revised
depending on the value of the Reference Distance, or for end user preference.
Maximum Flow is a read-only value that represents the flow value corresponding
Maximum Flow
to the Maximum Head value for the flume or weir.
The Low Flow Cutoff (in user-selected level units) will force the calculated flow
Low Flow Cutoff value to zero whenever the Head is below this point. This parameter will have a
default and minimum value of zero.
Generic Equation Example (using equation for an 8' rectangular weir w/ end contractions)
Q = Cubic Ft/Second flow rate L = 8' (weir crest length in feet) H = Head value
K = 3.33 for Cubic Ft/Second units C = 0.2 (constant) n = 1.5 as an exponent
Transition P10
point
P9
P7
P8
P6 P5
P5
P4 Average flow rate
P3
P4
P2
P1 P3
SPLINE OR LINEAR
P2
SPLINE Concentrate points along curve P1
Up to 75 °C T6 TCD= PT+10K=85 °C
3.6.1 Functional/Physical
System Design
Measurement Principle Guided Wave Radar based on Time Domain Reflectometry (TDR)
Input
Measured Variable Level, as determined by GWR time of flight
Span 6 inches to 100 feet (15 cm to 30 m); Model 7yS Probe 20 feet (610 cm) max.
Output
Type 4 to 20 mA with HART: 3.8 mA to 20.5 mA useable (per NAMUR NE43)
FOUNDATION fieldbus™: H1 (ITK Ver. 6.2.0)
PROFIBUS PA
Modbus
Resolution Analog: .003 mA
Digital Display: 1 mm
Loop Resistance 591 ohms @ 24 VDC and 22 mA
Diagnostic Alarm Selectable: 3.6 mA, 22 mA (meets requirements of NAMUR NE 43), or HOLD last output
Diagnostic Indication Meets requirements of NAMUR NE107
Damping Adjustable 0 –10 seconds
User Interface
Keypad 4-button menu-driven data entry
Display Graphic liquid crystal display
Digital Communication/Systems HART Version 7—with Field Communicator, AMS, or FDT
DTM (PACTware™), EDDL
FOUNDATION fieldbus, PROFIBUS PA or Modbus
Menu Languages Transmitter LCD: English, French, German, Spanish, Russian
HART DD: English, French, German, Spanish, Russian, Chinese, Portuguese
FOUNDATION fieldbus, PROFIBUS PA and Modbus Host System: English
Power (at transmitter terminals) HART: General Purpose (Weatherproof)/Intrinsically Safe/Explosion-proof:
16 to 36 VDC
11 VDC minimum under certain conditions
FOUNDATION fieldbus and PROFIBUS PA: 9 to 17.5 VDC
FISCO ia / FNICO ic, Explosion Proof, General Purpose and Weatherproof
Modbus: 8 to 30 VDC
Explosion Proof, General Purpose, and Weatherproof
Housing
Material IP67/die-cast aluminum A413 (<0.4% copper); optional stainless steel
Net/Gross Weight Aluminum: 4.5 lbs. (2.0 kg)
Stainless Steel: 10.0 lbs. (4.50 kg)
Overall Dimensions H 8.34" (212 mm) x W 4.03" (102 mm) x D 7.56" (192 mm)
Cable Entry ⁄2" NPT or M20
1
SIL 2 Hardware (Safety Integrity Level) Safe Failure Fraction = 93% (HART only)
Functional Safety to SIL 2 as 1oo1 in accordance with IEC 61508
“O”-Ring Max. Process Min. Process Max. Process Not Recommended For
Code Recommended for Applications
Material Temperature Temperature Pressure Applications
Launch
end view
Vacuum ➄
GWR Dielectric Temperature
end view Max. Overfill Viscosity
Range ➁➂ Range ➃
Description Application Installation
Probe➀ Pressure Safe cP (mPa.s)
Coaxial GWR Probes— Liquids
Standard Level/Interface Tank/Chamber ε 1.4 –100 -40 to +400 °F 1000 psi
7yT r Yes Yes 500/2000
Temperature (-40 to +200 °C) (70 bar)
High -320 to +400 °F
ε 1.4 –100 (-196 6250 psi
7yP Pressure Level/Interface Tank/Chamber r Full Yes 500/2000
to +200 °C) (431 bar)
High Temp./ Level/Interface Tank/Chamber ε 1.4 –100 -320 to +850 °F 6250 psi
7yD r Full Yes 500/2000
High Press. (-196 to +450 °C) (431 bar)
7yS Steam Saturated Tank/Chamber εr 10 –100 -40 to +750 °F ≈ 3000 psi Full No ∆ 500
Probe Steam (-40 to +400 °C) (207 bar)
Dual-element Probes
Coaxial / Cage HP Coaxial/Cage HTHP Coaxial/Cage Steam Flexible Twin Rod
(7yL, 7yP) ➀ (7yD, 7yJ) ➀ (7yS) ➀
Model
(7yG, 7yT) (7y5, 7y7)
316/316L SS (Hastelloy 316/316L SS, 316/316L SS,
316/316L SS, 316/316L SS
C and Monel opt.) Glass Ceramic Alloy, Glass Ceramic Alloy,
Materials Peek™, Inconel FEP Coating
TFE spacers, Inconel Inconel
Aegis PF 128 O-ring Viton® O-rings
Viton® O-rings TFE spacers TFE or Peek™ spacers
.875" (10 mm) +575 °F
Small Coaxial: .3125" (8 mm) diameter rod, .875" (10 mm) diameter tube
1.25" (32 mm) +750 °F
Two .25" (6 mm) dia.
Diameter Enlarged Coaxial: .6" (15 mm) dia. rod, 1.75" (44 mm) dia. tube N/A cables; .875" (22 mm)
CL to CL
Process 3
⁄4" NPT, 1" BSP 3
⁄4" NPT, 1" BSP 3
⁄4" NPT, 1" BSP 2" NPT
Connection ASME or DIN flanges ASME or DIN flanges ASME or DIN flanges ASME or DIN flanges
Transition zone 6" (150 mm) @ εr = 1.4 6" (150 mm) @ εr = 1.4
1" (25 mm)@ εr = 80 12" (305 mm)
(Bottom) 1" (25 mm) @ εr = 80.0 1" (25 mm) @ εr = 80.0
NOTE: Transition Zone is dielectric dependent; εr = dielectric permittivity. The transmitter still operates but
level reading may become nonlinear in Transition Zone.
Model 7yF 7yM, 7yN ➀ 7y1 Flexible 7y3, 7y6 Flexible ➀ 7y2 Flexible
6000 6000
Maximum Pressure (PSI)
5000 5000
4500 4500
4000 4000
3500 3500
3000 3000
0 100 200 300 400 500 0 200 400 600 800 1000
Temperature (°F) Temperature (°F)
316/316L SST 316/316L SST
Hastelloy C276 Hastelloy C276
Monel 400 Monel 400
High Pressure Probes Low Pressure High Pressure Probes Low Pressure
NOTES: Temp. SST Hastelloy Monel All Materials Temp. SST Hastelloy Monel All Materials
• 7yS steam probes are rated to 3000 psi (207 bar) up to +750 °F (+400 °C) -40 6000 6250 5000 750 +600 3760 5040 3940 —
• 7y3, 7y6 flexible probes: Pressure is limited by the chamber +70 6000 6250 5000 1000 +650 3680 4905 3940 —
• 7y2, 7y5 bulk solids probes: 50 psi (3.45 bar) to +150 °F (+65 °C) +100 6000 6250 5000 1000 +700 3620 4730 3920 —
• High pressure probes with threaded fittings are rated as follows: +200 5160 6250 4380 650 +750 3560 4430 3880 —
• 7yD, 7yN, 7yP and 7y3 probes with threaded fittings have 3600 psi (248 bar)
+300 4660 6070 4080 400 +800 3520 4230 3820 —
• rating. 7yM probes with threaded fittings have 2016 psi (139 bar) rating.
+400 4280 5820 3940 270 +850 3480 4060 3145 —
+500 3980 5540 3940 —
3.6.5 Physical Specifications – Transmitter
inches (mm)
3.38 4.18
(86) (106)
3.77
3.38 4.18 8.34
(96)
(86) (106) (212)
5.09
9.30 (129)
(236) 3.77
(96)
4.03
45° (102)
2 cable
entries
2 cable Eclipse® Housing
entries
Integral Electronics (45° View)
2.75
Eclipse® Housing (70) 45° 33 or 144
(838 or 3650)
(45° View)
3.00 3.75
2.00 (76) (95)
(51)
3.50 2 Holes
(89) .38 (10) Dia. 4.75
(120)
4.46
(113) Optional
3.0 (76 mm) Flushing Port Optional
typical 1/4" NPT 7.76 Flushing Port
(197) 1/4" NPT
10.45
Mounting 3.0 (76 mm) (265)
Flange typical
3.0 (76 mm)
typical
Probe
Mounting
Insertion
Flange
Length
Probe
Insertion Mounting
Length Flange Probe
Insertion
Length
3.77 A
(96)
C
9.30
(236) B E
2 cable 45°
F
entries
D
Coaxial GWR Probe,
End View Coaxial Probe Slots
Model 7yS
with flanged connection
3.77
9.30
3.77 (96)
(236)
(96)
9.30
9.30 (236)
(236) 45°
2 cable
entries
2 cable 45°
2 cable 45° entries
entries
10.45
4.70 6.39
(265)
(119) (162)
Mounting
Flange
Mounting
Flange
Mounting
Flange
Probe
Insertion Probe
Length Insertion Probe
Length Insertion
Length
4.53
(115)
10.45 10.45
Mounting (265) (265)
Flange
Mounting
Flange Mounting
Flange
Probe
Insertion
Length
⌀ 2.0 (51)
⌀ 2.0 (51) ⌀ 2.0 (51)
⌀ 0.5 (0.19) 3.88
(99) Probe Probe
Insertion Insertion
Length Length
0.75 (19)
Model 7y3 6.0 Model 7y6 6.0
with flanged (152) with flanged (152)
Model 7y1 connection connection
with flanged connection
3.38 4.18
3.38 4.18 (86) (106)
(86) (106)
3.77
3.77 (96)
(96)
9.30
9.30 (236)
(236)
6
(152)
Ø2
2 cable 45°
(51)
2 cable 45° entries
entries
5.46
4.70 (139)
(119)
Mounting Mounting
Flange Flange
2 cable 45°
entries
2 cable 45°
2 cable 45° entries
entries
4.53
(115) 10.45
8.38 (265)
Mounting (213)
Flange
Mounting
Flange Mounting
Probe Flange
Insertion
Length
⌀ .38 ⌀ .38 ⌀ .50
Probe Probe
Insertion Insertion
(9.6) (9.6) Length (13)
Length
Probe
Insertion Probe
Length Insertion
0.875 (22.2) Length
R Loop
591
Ω
Typical HART
4-20 mA
Digital Solar Mode Operating Area
0 11 V 16.25 V 24 V 36 V
Vsupply
HART
3.7.1 Transmitter
1 2 3 | BASIC MODEL NUMBER
706 ECLIPSE 4th Generation Guided Wave Radar (GWR) Level Transmitter
4 | POWER
5 24 VDC, Two-Wire
5 | SIGNAL OUTPUT
1 4 –20 mA with HART
2 FOUNDATION fieldbus™ Communication
3 PROFIBUS PA Communication
4 Modbus Communication (8th Digit = 0 or 3 only)
6 | SAFETY OPTIONS
0 None (FOUNDATION fieldbus, PROFIBUS PA or Modbus) (5th digit = 2, 3 or 4)
2 SIL 2/3 Certified - HART only (5th digit = 1)
7 | ACCESSORIES/MOUNTING
0 No Digital Display or Keypad - Integral
1 No Digital Display or Keypad - 3-foot (1 meter) remote
2 No Digital Display or Keypad - 12-foot (3.6 meter) remote
A Digital Display and Keypad - Integral
B Digital Display and Keypad - 3-foot (1 meter) remote
C Digital Display and Keypad - 12-foot (3.6 meter) remote
8 | CLASSIFICATION
0 General Purpose, Weatherproof (IP 67)
1 Intrinsically Safe (FM & CSA CL 1 Div 1, Grps A, B, C, D)
3 Explosion-proof (FM & CSA CL 1 Div 1, Grps B, C, D)
A Intrinsically Safe (ATEX/IEC Ex ia IIC T4)
B Flame-proof (ATEX/IEC Ex d ia IIC T6)
Non-sparking (ATEX Ex n IIC T6) /
C
Non-incendive (FM & CSA, CL 1 Div 2)
D Dust Ex (ATEX II)
9 | HOUSING
1 Die-cast Aluminum, Dual-compartment, 45-degree
2 Investment Cast, Stainless Steel, Dual-compartment, 45-degree
10 | CONDUIT CONNECTION
1
0 ⁄2" NPT
1 M20
1
2 ⁄2" NPT with sunshade
3 M20 with sunshade
7 0 6 5
1 2 3 4 5 6 7 8 9 10
3 | CONFIGURATION/STYLE (RIGID)
D Enlarged Coaxial, High Temp/High Pressure: Overfill w/Glass Seal (+850 °F/+450 °C) — Only available with 10th digit N or D
P Enlarged Coaxial, High Pressure: Overfill w/Glass Seal (+400 °F/+200 °C) — Only available with 10th digit N or D
T Enlarged Coaxial, Overfill Standard O-Ring Seal (+400 °F/+200 °C) — NOT available with 10th digit N or D
7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
7 | FLANGE OPTIONS — Offset flanges are only available with small coaxial probes
0 None
9 | SPACER MATERIAL
1 TFE (+400 °F/+200 °C) — Only available with 3rd digit P or T — εr ≥ 1.4
2 PEEK HT — Only available with 3rd digit D (+650 °F/+345 °C) — εr ≥ 1.4
3 Ceramic (High Temp. >+800 °F/+425 °C) — Only available with 3rd digit D — εr ≥ 2.0
4 Celazole (+800 °F/+425 °C) — Only available with 3rd digit D — εr ≥ 1.4
5 None - with metal shorting rod — εr ≥ 1.4 — Future
13 14 15 | INSERTION LENGTH
inches (012 – 396)
X X X cm (030 – 999)
7 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
7 | FLANGE OPTIONS — Offset flanges are only available with small coaxial probes
0 None
1 Offset (For use with AURORA) — 4" Only available with 3rd digit P, S or T
2 Offset with 1⁄2" NPT Vent (For use with AURORA) — 4" Only available with 3rd digit P, S or T
3 Offset with 3⁄4" NPT Vent (For use with AURORA) — 4" Only available with 3rd digit P, S or T
9 | SPACER MATERIAL
1 TFE (+400 °F/+200 °C) — Only available with 3rd digit P or T — εr ≥ 1.4
2 PEEK HT — Only available with 3rd digit D (+650 °F/+345 °C) — εr ≥ 1.4 or S (+575 °F/+300 °C)
3 Ceramic (Temp. >+650 °F/+345 °C) — Only available with 3rd digit D — εr ≥ 2.0 or 3rd digit S
5 None - with metal shorting rod — εr ≥ 1.4 — Future
12 | SPECIAL OPTIONS
0 Single Length Probe (Non-Segmented)
13 14 15 | INSERTION LENGTH
inches (012 – 240)
XXX cm (030 – 610)
unit of measure determined by
2nd digit of model number
7 2 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2 | MEASUREMENT SYSTEM
A English
C Metric
3 | CONFIGURATION/STYLE (RIGID)
G Overfill Caged Rigid Probe for use in chambers +400 °F (+200 °C) — Only available with 2", 3" and 4" flanges
Overfill Caged High Temp/High Pressure Probe with Glass Seal for use in chambers +850 °F (+450 °C)
J
Only available with 2", 3" and 4" flanges
Overfill Caged High Pressure Probe with Glass Seal for use in chambers +400 °F (+200 °C)
L
Only available with 2", 3" and 4" flanges
7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
7 | FLANGE OPTIONS
0 None
1 Offset (For use with AURORA)–4” Only available with 3rd digit G and J and 4th digit 6
2 Offset with 1⁄2" NPT Vent (For use with AURORA)–4” Only available with 3rd digit G and J and 4th digit 6
3 Offset with 3⁄4" NPT Vent (For use with AURORA)–4” Only available with 3rd digit G and J and 4th digit 6
9 | SPACER MATERIAL
2 PEEK HT (+650 °F/+345 °C)
3 Ceramic (High Temp.>+800 °F/+425 °C) — Only available with 3rd digit J
4 Celazole® (+800 °F/+425 °C) — Only available with 3rd digit J
13 14 15 | INSERTION LENGTH
inches (012 – 288)
XXX cm (030 – 732)
unit of measure determined by
2nd digit of model number
7 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2 | MEASUREMENT SYSTEM
A English
C Metric
3 | CONFIGURATION/STYLE (RIGID)
F Single Rod, Standard (+400 °F/200 °C) for in-tank applications NOT available with 10th digit N or D
M Single Rod, High Pressure Probe with glass seal (+400 °F/+200 °C), for in-tank applications Only available with 10th digit N or D
N Single Rod, High Temp/High Pressure with glass seal (+850 °F/+450 °C), for in-tank applications Only available with 10th digit N or D
ASME Flanges
33 11⁄2" 150# ASME RF ➀ ➂ 4N 2" 2500# ASME RTJ 5N 3" 2500# ASME RTJ
34 11⁄2" 300# ASME RF ➀ ➂ 53 3" 150# ASME RF 63 4" 150# ASME RF
35 11⁄2" 600# ASME RF ➀ ➂ 54 3" 300# ASME RF 64 4" 300# ASME RF
43 2" 150# ASME RF ➀ 55 3" 600# ASME RF 65 4" 600# ASME RF ➃
44 2" 300# ASME RF ➀ 56 3" 900# ASME RF 66 4" 900# ASME RF ➃
45 2" 600# ASME RF ➀ 57 3" 1500# ASME RF 67 4" 1500# ASME RF ➃
47 2" 900/1500# ASME RF 58 3" 2500# ASME RF 68 4" 2500# ASME RF ➃
48 2" 2500# ASME RF 5K 3" 600# ASME RTJ 6K 4" 600# ASME RTJ ➃
4K 2" 600# ASME RTJ 5L 3" 900# ASME RTJ 6L 4" 900# ASME RTJ ➃
4M 2" 900/1500# ASME RTJ 5M 3" 1500# ASME RTJ 6M 4" 1500# ASME RTJ ➃
6N 4" 2500# ASME RTJ ➃
EN Flanges
CB DN 40, PN 16/25/40 EN 1092-1 TYPE A ED DN 80, PN 63 EN 1092-1 TYPE B2
CC DN 40, PN 63/100 EN 1092-1 TYPE B2 EE DN 80, PN 100 EN 1092-1 TYPE B2
CF DN 40, PN 160 EN 1092-1 TYPE B2 EF DN 80, PN 160 EN 1092-1 TYPE B2 ➃
CG DN 40, PN 250 EN 1092-1 TYPE B2 EG DN 80, PN 250 EN 1092-1 TYPE B2 ➃
DA DN 50, PN 16 EN 1092-1 TYPE A ➀ EH DN 80, PN 320 EN 1092-1 TYPE B2 ➃
DB DN 50, PN 25/40 EN 1092-1 TYPE A ➀ E J DN 80, PN 400 EN 1092-1 TYPE B2 ➃
DD DN 50, PN 63 EN 1092-1 TYPE B2 ➀ FA DN 100, PN 16 EN 1092-1 TYPE A
DE DN 50, PN 100 EN 1092-1 TYPE B2 ➀ FB DN 100, PN 25/40 EN 1092-1 TYPE A
DF DN 50, PN 160 EN 1092-1 TYPE B2 ➃ FD DN 100, PN 63 EN 1092-1 TYPE B2
DG DN 50, PN 250 EN 1092-1 TYPE B2 ➃ FE DN 100, PN 100 EN 1092-1 TYPE B2
DH DN 50, PN 320 EN 1092-1 TYPE B2 ➃ FF DN 100, PN 160 EN 1092-1 TYPE B2 ➃
DJ DN 50, PN 400 EN 1092-1 TYPE B2 ➃ FG DN 100, PN 250 EN 1092-1 TYPE B2 ➃
EA DN 80, PN 16 EN 1092-1 TYPE A ➀ FH DN 100, PN 320 EN 1092-1 TYPE B2 ➃
EB DN 80, PN 25/40 EN 1092-1 TYPE A FJ DN 100, PN 400 EN 1092-1 TYPE B2 ➃
➀ Confirm mounting conditions/nozzle diameter to ensure sufficient clearance.
➁ Not available with 3rd Digit N or 8th Digit P
➂ Not available with 3rd Digit M or N
➃ Available only with 3rd Digit M or N
7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
7 | FLANGE OPTIONS
0 None
9 | SPACER MATERIAL
0 None – NOT available with 3rd Digit N
2 PEEK HT (+650 °F/+345 °C) — Only available with 3rd digit N
3 Ceramic (High Temp.>+800 °F/+425 °C) — Only available with 3rd digit N
4 Celazole® (+800 °F/+425 °C) — Only available with 3rd digit N
12 | SPECIAL OPTIONS
Non-Removable Rod
0
Only available with PFA Coated Probes(8th digit F or P)
Removable Rod
1
NOT available with PFA Coated Probes(8th Digit F or P)
13 14 15 | INSERTION LENGTH
inches (012 – 288)
XXX cm (030 – 732)
unit of measure determined by
2nd digit of model number
7 0 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2 | MEASUREMENT SYSTEM
A English
C Metric
ASME Flanges
43 2" 150# ASME RF ➀ 53 3" 150# ASME RF 63 4" 150# ASME RF
44 2" 300# ASME RF ➀ 54 3" 300# ASME RF 64 4" 300# ASME RF
45 2" 600# ASME RF ➀ 55 3" 600# ASME RF 65 4" 600# ASME RF
47 2" 900/1500# ASME RF 56 3" 900# ASME RF 66 4" 900# ASME RF ➁
48 2" 2500# ASME RF 57 3" 1500# ASME RF 67 4" 1500# ASME RF ➁
4K 2" 600# ASME RTJ 58 3" 2500# ASME RF 68 4" 2500# ASME RF ➁
4M 2" 900/1500# ASME RTJ 5K 3" 600# ASME RTJ 6K 4" 600# ASME RTJ ➁
4N 2" 2500# ASME RTJ 5L 3" 900# ASME RTJ 6L 4" 900# ASME RTJ ➁
5M 3" 1500# ASME RTJ 6M 4" 1500# ASME RTJ ➁
5N 3" 2500# ASME RTJ 6N 4" 2500# ASME RTJ ➁
EN Flanges
DA DN 50, PN 16 EN 1092-1 TYPE A ➀ EF DN 80, PN 160 EN 1092-1 TYPE B2 ➁
DB DN 50, PN 25/40 EN 1092-1 TYPE A ➀ EG DN 80, PN 250 EN 1092-1 TYPE B2 ➁
DD DN 50, PN 63 EN 1092-1 TYPE B2 ➀ EH DN 80, PN 320 EN 1092-1 TYPE B2 ➁
DE DN 50, PN 100 EN 1092-1 TYPE B2 ➀ E J DN 80, PN 400 EN 1092-1 TYPE B2 ➁
DF DN 50, PN 160 EN 1092-1 TYPE B2 ➁ FA DN 100, PN 16 EN 1092-1 TYPE A
DG DN 50, PN 250 EN 1092-1 TYPE B2 ➁ FB DN 100, PN 25/40 EN 1092-1 TYPE A
DH DN 50, PN 320 EN 1092-1 TYPE B2 ➁ FD DN 100, PN 63 EN 1092-1 TYPE B2
DJ DN 50, PN 400 EN 1092-1 TYPE B2 ➁ FE DN 100, PN 100 EN 1092-1 TYPE B2
EA DN 80, PN 16 EN 1092-1 TYPE A ➀ FF DN 100, PN 160 EN 1092-1 TYPE B2 ➁
EB DN 80, PN 25/40 EN 1092-1 TYPE A FG DN 100, PN 250 EN 1092-1 TYPE B2 ➁
ED DN 80, PN 63 EN 1092-1 TYPE B2 FH DN 100, PN 320 EN 1092-1 TYPE B2 ➁
EE DN 80, PN 100 EN 1092-1 TYPE B2 FJ DN 100, PN 400 EN 1092-1 TYPE B2 ➁
➀ Confirm mounting conditions/nozzle diameter to ensure sufficient clearance.
➁ Only available with 3rd Digit 3 or 6
7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
6 | CONSTRUCTION CODES
0 Industrial
7 | FLANGE OPTIONS
0 None
9 | SPACER/WEIGHT MATERIAL
0 No Spacer — Not available with 3rd digit 3
1 PTFE Spacer — Available only with 3rd digit 3
4 Celazole® Spacer — Available only with 3rd digit 6
5 Metal Weight — Available only with 3rd digit 3
12 | SPECIAL OPTIONS
Non-removable Probe Cable
0
Only available with 3rd digit 2 or 8th digit F
Removable Single-piece Probe Cable
1
Only available with 3rd digit 1, 3 and 6
13 14 15 | INSERTION LENGTH
feet (003 – 100)
XXX
meters (001 – 030)
unit of measure determined by
2nd digit of model number
7 0 0 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2 | MEASUREMENT SYSTEM
A English
C Metric
ASME Flanges
53 3" 150 lbs. ASME RF
54 3" 300 lbs. ASME RF
55 3" 600 lbs. ASME RF
63 4" 150 lbs. ASME RF
64 4" 300 lbs. ASME RF
65 4" 600 lbs. ASME RF
EN Flanges
EA DN 80, PN 16 EN 1092-1 TYPE A
EB DN 80, PN 25/40 EN 1092-1 TYPE A
ED DN 80, PN 63 EN 1092-1 TYPE B2
EE DN 80, PN 100 EN 1092-1 TYPE B2
FA DN 100, PN 16 EN 1092-1 TYPE A
FB DN 100, PN 25/40 EN 1092-1 TYPE A
FD DN 100, PN 63 EN 1092-1 TYPE B2
FE DN 100, PN 100 EN 1092-1 TYPE B2
➀ Confirm mounting conditions/nozzle diameter to ensure sufficient clearance.
7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
6 | CONSTRUCTION CODES
0 Industrial
7 | FLANGE OPTIONS
0 None
9 | SPACER MATERIAL
0 None
12 | SPECIAL OPTIONS
0 None
13 14 15 | INSERTION LENGTH
feet (003 – 100)
XXX meters (001 – 030)
unit of measure determined by
2nd digit of model number
7 0 0 0 3 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Coaxial Models
7yD, 7yP and 7yT
24 – 72" 48 – 144" 72 – 216" 96 – 288" 120 – 360" 144 – 396"
(Enlarged versions only)
(60 – 182 cm) (120 – 365 cm) (180 – 548 cm) (240 – 731 cm) (305 – 914 cm) (365 – 999 cm)
(3", DN 80 Process
Connections and larger)
NOTE: Segments will be evenly divided over the length of the probe.
5
7
TB1
J1
- +
3 6
CURRENT LOOP
R
1
4
R
Electronics:
Digit: 1 2 3 4 5 6 7 8 9 10
Part Number: 7 0 6 5 Serial Number: 7 7 7 7 0 6 7 7 7 7 7
X = product with a non-standard customer requirement See nameplate, always provide complete part number and
serial number when ordering spares.
Replacement Part
(4) O-ring Z12-2201-237
(5) O-ring Z12-2201-237
Bottom Spacer for Single Rod GWR Probe (8) Bottom Spacer + Pin Kit
Digit 3 Digit 8 Replacement Part
A or R 089-9114-008
F or M B or S 089-9114-009
➇
C or T 089-9114-010
A or R 089-9114-005
N B or S 089-9114-006
7yF, 7yM or 7yN single rod
C or T 089-9114-007
7 089-9121-001
➈ ➈
5 004-8778-002
11
(11) Cable Clamp
11
Digit 3 Replacement Part
010-1731-001
2 or 5
(ordering quantity: 2)
7y2 single cable 7y5 twin cable
Select the Diagnostics tab and then the Echo Curve tab.
Then click on New Rejection Curve
Maintenance Policy
With proper ECLIPSE Guided Wave Radar (GWR) probe selection, there is virtually no maintenance required for a
Model 706 system. As explained in Section 3.3.5, application-related issues, such as coating or bridging on the probe can
occur. Therefore, although internal diagnostics can be utilized to proactively display overall system degradation, a peri-
odic visual inspection of he probe is recommended. Refer to Section 3.8 for replacement parts.
24/7 Technical Support assistance is available at 1-630-723-6730 or fieldservice@magnetrol.com.
ECLIPSE Guided Wave Radar transmitters may be protected by one or more of the following U.S. Patent Nos. US 6,062,095:
US 6,247,362; US 6,588,272; US 6,626,038; US 6,640,629; US 6,642,807; US 6,690,320; US 6,750,808; US 6,801,157;
US 6,867,729; US 6,879,282; 6,906,662. May depend on model. Other patents pending.