AF-300 G11 Specifications


GE Industrial Systems

Product Specifications

AF-300 G11
TM

1
TM

AF-300 G11 Specifications

Category Item Description


Nominal Motor 230 VAC, 3 Phase 1/4 Hp to 125 Hp
460 VAC, 3 Phase 1/2 Hp to 450 Hp
Braking Torque (Standard) 1/4 Hp to 1 Hp 150%
2 Hp to 10 Hp 100%
15 Hp to 30 Hp 20%
40 Hp and Higher 10% - 15%
Braking Torque (Optional) 1 Hp to 30 Hp 150%
40Hp and Higher 100%
Enclosure, Standard 1/4 Hp to 30 Hp NEMA 1 Standard, NEMA 4 Optional to 10 Hp, NEMA 12 Optional all ratings
40 Hp and Up NEMA 1 Standard, IP00 Optional 40Hp and above
Cooling Method Convection 1 Hp and below
Fan Cooled Above 1 Hp
Standards UL/cUL No input fuses required
CE EN61800-3 for EMC EN61800-2 for Low Voltage
Input Item Description
Up to 30 Hp, 230 VAC 200V - 230V (+10%, -15%), 50 or 60 Hz (+/- 5%)
Up to 30 Hp, 460 VAC 380V - 480V (+10%, -15%), 50 or 60 Hz (+/- 5%)
40 Hp & Above, 230 200V - 220V (+10%, -15%), 50 Hz (+/- 5%) / 220V - 230V (+10%, -15%), 60 Hz
VAC (+/- 5%)
40 Hp & Above, 460 380V - 440V (+10%, -15%), 50 Hz (+/- 5%) / 380V - 480V (+10%, -15%), 60 Hz
VAC (+/- 5%)
Unbalance Voltage Unbalance within 3%
Power Dip For input voltage greater than Vmin, the drive will operate at rated output
continuously.
For input voltage less than Vmin, the drive will operate at 85% of rated output
for 15 Msec.
Vmin (230V Series) = 165V, Vmin (460V Series) = 310V. Smooth recovery
method is selectable
Condition Item Description
Altitude 1000 meters or less. Derate at 1% for each 100 meters from 1000 to 3000
meters (Above 3000 meters, consult factory)
Temperature Ambient -10 to 50°C (units less than and equal to 30Hp must have ventilation covers
removed for 40°C and above)
Storage -20 to 65°C
Vibration IEC61200-2
Humidity 5 - 95% Relative Humidity (Non-condensing)
Output Item Description
230V, 3 Phase 3 Phase, 200V, 50Hz or 3 Phase, 200V, 220V, 230V, 60Hz
460V, 3 Phase 3 Phase, 380V, 400V, 415V, 440V, 50Hz or 3 Phase, 380V, 400V, 440V, 460V,
60Hz
Frequency 50 / 60 Hz
Overload 150% of rated current for 1 min
180% of rated current for 0.5 sec => 30Hp
200% of rated current for 0.5 sec =< 30Hp
Max Freq. 50 - 400 Hz
Base Freq. 25 - 400 Hz
Starting Freq. 0.1 - 60 Hz
Carrier Freq. 0.75 - 15 kHz up to 100 Hp. 0.75 - 10 kHz 125 Hp and above.
Minimum carrier frequency changes dependent on maximum output frequency
Accuracy (Stability) Analog +/- 0.2% of maximum frequency (speed) at 25 +/- 10°C
Digital +/- 0.01% of maximum frequency (speed) between -10 and 50°C
Setting Resolution Analog 1/3000 of maximum frequency (speed)
Digital 0.01 Hz for frequency up to 99.9 Hz (0.1 Hz for frequency > 100 Hz)

2
TM

AF-300 G11 Specifications


Control Item Description
Control Method Sinusoidal PWM V/Hz
Dynamic Torque Vector Control (Sensorless)
Flux-vector Control with Pulse Tachometer
Operation Methods Keypad, Digital Input, Bus Communication
Frequency Setting Keypad (UP or DOWN)
Potentiometer 1-5KW (1/2 W) Optional
Analog 0 - 5 VDC
0 to +/– 10 VDC Bi-polar (Reversible operation by signal polarity)
0 - 10 VDC (10 - 0 VDC selectable)
4 - 20 MA (20 - 4 MA selectable)
Digital Up/Down Control (Increases with UP, decreases with DOWN)
Multi-step (4 different frequencies via SS1 and SS2)
Multi-step (8 different frequencies via SS1, SS2, and SS4)
Multi-step (16 different frequencies via SS1, SS2, SS4, and SS8)
Programmed pattern operation - 8 stages
Serial RS485 with Modbus RTU - Standard
Networks Optional network cards
Acceleration Setting Four Modes 0.01 - 3600 seconds (Independent Acc/Dec, four times, three modes - Linear, S-
Curve, Non-linear)
Automatic When the motor acc.(dec.) torque reaches a preset value, the acc. (dec.) time is
automatically extended for tripless operation.
Frequency Limiter High and low values are presettable
Bias Frequency -400.0 to +400.0 Hz
Frequency Gain Adjustable from 0 - 200 %
Jump Frequency Jump frequency setting (3 points), jump hysteresis width (1 setting)
Catch Spinning Motor Smoothly pick up a rotating motor without stopping (speed search method) -
No DB required
Auto-Restart Autorestart is available after a momentary power failure (speed search
method)
Continuous operation mode is selectable
Switching Operation Control terminals are provided for smooth switching operation from line power
to drive
Slip Compensation Related to load torque and magnified for negative slips frequencies
Torque Limiting Automatic overcurrent adjustments
2 torque limiting functions can be preset
Torque Control Output torque or load factor can be controlled by analog input signal with PG
option
PID Control Process controller - standard
Automatic Deceleration Automatic extension of deceleration time when braking torque limit is reached
for tripless operation without a DB resistor
2nd Motor Settings Settings for a second motor: base freq., rated voltage, rated current, no load
current, impedances
Fan Stop Operation Automatically manage cooling fan operation to extend life - up to 30Hp
operation is preset, above 30Hp signal is preset
Motor Autotune Offline Tuning Selectable with motor rotating and without motor rotating
Online Tuning Dynamically compensates regulator for changes in motor temperature
Energy Saving Reduces losses at light loads
Keypad Item Description
Backlit LCD Display
Smart Keypad to copy parameters from one drive to another
Extension cable adapter for RJ45 connector

3
TM

AF-300 G11 Specifications

Indication Item Description


Operation Mode LED Output frequency
Output current, Output voltage
Motor synchronous speed (RPM)
Line speed (M/min)
Load shaft speed (RPM)
Output torque (%)
Frequency setting
PID (Set 1 value, Set 2 value, Feedback value)
Power consumption
Motor load factor
LCD Heatsink temperature
Drive internal temperature
I/O Test - indicates signal existence or absence of digital I/O and signal value
of analog I/O
RMS current - 1 cycle
%DB - 1 cycle
Other DC Link power charge display
Program Mode Feature Function Code and Function Name, Data or Data Code
Languages English, French, German, Italian, Japanese, Spanish
Trip Mode OC1 Overcurrent during acceleration
OC2 Overcurrent during deceleration
OC3 Overcurrent running at constant speed
FUS Fuse blown
OU1 Overvoltage during acceleration
OU2 Overvoltage during deceleration
OU3 Overvoltage running at constant speed
LV Low voltage
OH1 Overheating of heatsink
OH2 External thermal relay tripped
OH3 Overtemperature of inside air
dBH Overheating of DB circuit
OL1, OL2 Motor overload
OUV Drive unit overload
EF Ground fault
LIM Input Phase Loss
FUS DC Fuse open (40 Hp and above)
Er1 Memory error
Er2 KEYPAD communication error
Er3 CPU error
Er4 Option card error, detected by the control card
Er5 Option card error, detected by the option card
Er6 Operations procedure error.
Er7 Output wiring error - impedance unbalance
Er8 RS485 communications error
Diagnostics History Trip history - passed four events (Trip and Warning)

4
TM

AF-300 G11 Specifications


Protection Item Description
Overload Detection of electronic thermal overload relay
Overvoltage Detection of DC link circuit overvoltage (230V series - 400V, 460V series -
800V)
Incoming Surge Drive protection from surge voltage input (Max. 1.2 x 50 usec 7KV peak)
Undervoltage Detection of DC link circuit undervoltage (230V series - 200V, 460V series -
400V)
Overheating Drive overheating protection by temperature detection
Short Circuit Short circuit protection for drive output circuit
Ground Fault Ground fault protection for drive output circuit - 3 phase circuit detection
method
Zero phase current detection method - 40 Hp and above
Motor Overload Electronic thermal overload relay can be selected for general purpose motor or
dedicated drive motor
Calculation of thermal time constant can be preset
2nd motor electronic thermal overload relay
DB Resistor Overheating Internal electronic thermal overload relay - up to 10 Hp
Overheating detection thermal overload relay installed in braking resistor unit -
15 Hp and above (option)
Motor Overheating Overheating detection PTC thermistor can be connected to terminals 13-C1-11
Phase Loss Drive protection for line side phase loss
Drive protection for motor side phase loss during tuning
Detection of output impedance unbalance during tuning
Signal Loss Detection of loss of C1 current signal
Auto-reset Auto reset times and reset interval can be preset
Terminal Functions Item Description
Main Circuit
Power Input L1/R, L2/S, L3/T Connect a three phase power source
Drive Output U, V, W Connect to a three phase induction motor
DC Reactor P1, P(+) Connect the DC reactor for power factor correcting or harmonic current
reduction Shipped in same carton with drive
Braking Unit P(+), N(-) Connect the braking unit - optional for 15 Hp and above
Ext. Braking Resistor Unit P(+). DB Connect the external braking resistor - 230V/460V series up to 10 Hp
Ground G Ground terminal for drive chassis (housing)
Aux. Control Power R0, T0 Connect the same AC power source used for Power Input as backup for control
circuit power supply - 2 Hp and above
Analog Inputs Item Description
Potentiometer Power 13 +10V DC power supply, maximum allowable output current 10ma
Voltage Input 12 0-10V / 0-100%, 22K ohm input impedance
0-5V / 0-100% can be selected by signal gain setting
Inverse mode operation by polarity
Reversible operation can be selected by function code
Frequency command, torque control, Tach feedback, or PID control
Common 11 Common for analog signal
Current Input C1 4-20ma / 0-100 % (input impedance 250 ohm)
Inverse mode operation
Frequency command, PID feedback
Analog Input 1 V2 0 - +/- 10V / 0 - +/- 100% (input impedance 22K ohm)

5
TM

AF-300 G11 Specifications

Digital Inputs Item Description


Forward Operation FWD ON - Motor runs in the forward direction, OFF - Motor decelerates and stops
Reverse Operation REV ON - Motor runs in the reverse direction, OFF - Motor decelerates and stops
Digital Input 1 X1 Functions selected via function codes - Sink type terminal specification
default with source type hardware selectable
Digital Input 2 X2 ON state - maximum input voltage 2V, maximum source current 5ma
Digital Input 3 X3 OFF state - maximum voltage 27V, maximum leakage current 0.5ma
Digital Input 4 X4 Selectable from the following
Digital Input 5 X5
Digital Input 6 X6
Digital Input 7 X7
Digital Input 8 X8
Digital Input 9 X9
3 Wire Stop HLD ON - the drive latches the FWD or REV signal, OFF - the drive releases the
latch
Coast Stop BX ON - motor will coast to a stop, no alarm signal will be issued
Trip Command THR OFF - OH2 trip is issued and latched, motor will coast to a stop
Alarm Reset RST ON - Momentary on for > 0.1 sec will reset faults
Multistep Frequency SS1 / SS2 4 different frequencies can be selected by ON/OFF pattern on terminals SS1
and SS2
SS4 8 different frequencies can be selected by ON/OFF pattern on terminals SS1,
SS2, and SS4
SS8 16 different frequencies can be selected by ON/OFF pattern on terminals SS1,
SS2, SS4, and SS8
ACC/DEC Time Select RT1 Second ACC/DEC time can be selected by terminal RT1
RT2 4 different ACC/DEC times can be selected by ON/OFF pattern on terminals
RT1 and RT2
JOG JOG ON - JOG frequency is activated
2nd Frequency Select HZ2/HZ1 ON - drive will stop and the 2nd frequency command becomes effective
2nd Motor Select M2/M1 ON - drive will stop and Motor 1 values are changed to Motor 2 values
DC Brake Command DCBRK ON - DC injection braking is active during deceleration
2nd Torque Limiter TL2/TL1 ON - Torque Limiter 2 is active
Line/drive Switching SW50 / SW60 ON - Motor is changed from drive operation to line operation (Main circuit
signal output via Y1-Y5)
UP Command UP ON - drive output frequency increases (change rate determined by ACC time)
DOWN Command DOWN ON - drive output frequency decreases (change rate determined by DEC time)
Write Enable WE-KP ON - data can be changed by KEYPAD operation
PID Control Cancel HZ/PID ON - PID control is canceled
Inverse Mode Changeover IVS ON - Operation mode is toggled from Normal to Inverse or Inverse to Normal
Interlock Signal (52-2) IL Connection for auxiliary contact 52-2
TRQ Control Cancel HZ/TRQ ON - Torque control is canceled
Link Enable (RS485) LE ON - Bus link or RS485 link is active
Universal Digital Input U-DI ON - Enables input from RS485 or LAN option
Sync/Tach Enable PG/HZ ON - Synchronize operation or Tach feedback operation is active
Zero Speed Command ZERO ON - Enables stall torque function
Timed Alarm Command STP OFF -The drive decelerates and stops
Pre-exciting Command EXITE ON - The motor eneters into a pre-exciting state during flux vector control
RS485 I/O Terminal DXA, DXB, SD Connections for RS485 serial port communications Modbus RTU standard
protocol
PLC Terminal PLC Connection for PLC power supply that avoids drive current loops on Sink type
inputs when PLC power supply is off.
Common CM Common for digital inputs

6
TM

AF-300 G11 Specifications


Analog Outputs Item Description
Analog Monitor FMA / 11 Output DC voltage is proportional to selected function's value. Functions are
selected by FC31
Slip frequency (0 - max frequency)
Output frequency (0 - max frequency)
Output current (0 - 200 %)
Output voltage (0 - 200 %)
Output torque (0 - 200 %)
Load factor (0 - 200 %)
Input power (0 - 200 %)
PID feedback value (0 - 100 %)
Tach feedback value (0 - max speed)
Universal Analog Output Analog output pass through for process control
Pulse Rate Monitor FMP / CM Pulse rate is proportional to selected function's value. maximum output
current: 2ma
The average value of the pulse train is proportional to the selected function's
value, output functions same as for FMA
Transistor Outputs Item Description
Power Supply P24 DC power supply - +24V, 100ma
Transistor Output 1 Y1 ON state maximum output voltage 2V, sink current 50ma
Transistor Output 2 Y2 OFF state maximum allowable voltage 27V, leakage current 0.1ma
Transistor Output 3 Y3 Select from the following
Transistor Output 4 Y4
Drive Running RUN ON - output frequency is larger than starting frequency
Frequency Equivalence FAR ON - difference between output frequency and setting frequency is smaller
than FAR hysteresis width
Frequency Level Detection FDT ON - output frequency is larger than preset detection level
Undervoltage Detection LV ON - drive undervoltage stops and operation command is ON
Torque Polarity B/D ON - drive is in braking mode
Torque Limiting TL2/TL1 ON - drive is in torque limiting mode
Auto-restarting IPF ON - drive auto restarting mode active or restart waiting mode is active
KEYPAD Operation Mode TP ON - drive is in KEYPAD operation mode
Drive Stopping STOP ON - drive is in stopping mode or DC braking mode
Overload Early Warning OL ON - electronic thermal calculated value is larger than preset protection level
(Selectable) ON - output current is larger than preset detection level
Line/drive Changeover SW88 Outputs signal 88 for line/drive changeover
SW52-2 Outputs signal 52-2 for line/drive changeover
SW52-1 Outputs signal 52-1 for line/drive changeover
Motor 2 / Motor 1 SWM2 Outputs motor changeover control switch for switching between motor 1 and
motor 2
Auxiliary Terminal AX ON - drive is running
Times UP TU Outputs a 100ms ON pulse for time up for pattern operation
Cycle Complete TO Outputs a 100ms ON pulse for cycle complete for pattern operation
Stage 1 Indicator STG-1, STG-2, STG-3 Pattern operation stage indicator (binary encoded)
Alarm 1 Indicator AL-1, AL-2, AL-4 Trip alarm number (binary encoded)
Fan Control FAN Outputs the drive fan control signal for 40 Hp and larger drives
Auto-resetting 1-TRY ON - auto resetting mode or reset waiting mode active
Universal Digital Output U-DO ON - Enables output from RS485 or LAN option
Overheating Early Warning OH ON - heatsink temperature is larger than preset detection level
Synchronization Complete SY Synchronization signal for synchronize operation option
Loss of C1 Current Input C1-OFF ON - When C1 current input is smaller than 2mA
Signal
Common CM Common terminal for transistor output signals

7
TM

AF-300 G11 Specifications

Relay Output Item Description


Alarm Relay Output 30A, 30B, 30C Activates when a protective function is activated, programmable with the
default state function code settable
Programmable Relay Output Y5A, Y5C Selectable the same as Y1-Y4
Options Item Description
LAN GENIUS
LAN Profibus DP
LAN N2 - Metasys
LAN Interbus-S
LAN Modbus Plus
LAN DeviceNet
Tachometer
KEYPAD Extension Cable Adaptor for RJ45 cable, up to 100'

Input/Output Specifications
Three-phase 230V series
Type designation
6KG1123_ _ _X1A1 (NEMA Type1)
6KG1123_ _ _ X2A1 (NEMA Type12)
6KG1123_ _ _ X4A1 (NEMA Type4) F25 F50 001 002 003 005 007 010 015 020 025 030 040 050 060 075 100 125
6KG1123_ _ _ X8A1 (Open, Type 12 Heatsink)
6KG1123_ _ _ X9A1 (Open)

Nominal 230V system pplied motor HP 1/4 1/2 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125
Output Rated Capacity *1) kVA 0.59 1.1 1.9 3.1 4.3 6.7 9.9 13 18 23 29 34 45 57 71 85 112 137
ratings Rated Voltage *2) V 3-phase, 200V /50Hz , 200V ,220V ,230V /60Hz
Rated Current *3) A 1.5 3.0 5.0 8.0 11 17 25 33 46 59 74 87 115 145 180 215 283 346
Overload Capability 150% of rated current for 1min , 200% of rated current for 0.5s 150% of rated current for 1min ,
180% of rated current for 0.5s
Rated Frequency Hz 50, 60Hz
Input Phases, Voltage, Frequency 3-phase, 200 to 230V , 50/60Hz 3-phase, 200 to 220V /50Hz , 200 to 230V /60Hz
ratings * 220 to 230V /50Hz *4),
Voltage / frequency variations -Voltage : +10 to -15% ( Voltage unbalance *5) : 2% or less ) -Frequency :+5 to -5%
Momentary voltage dip When the input voltage is 165V or more, the inverter can be operated continuously.
capability *6) When the input voltage drops below 165V from rated voltage, the inverter can be operated for 15ms . (within 85% load of nominal applied motors)
The smooth recovery method is selectable.

1) Drive output capacity [kVA] at 230V


2) Output voltage is proportional to the power supply and can’t exceed the power supply voltage.
3) Current derating may be required in case of low impedence load such as high frequency motor.
4) 220 to 230 V/50 Hz: Order individually
5) Reference to the IEC 61800-3 (5.2.3)
6) Input power: 85%

Three-phase 460V series


Type designation
6KG1143_ _ _X1A1 (NEMA Type1)
6KG1143_ _ _ X2A1 (NEMA Type12)
6KG1143_ _ _ X4A1 (NEMA Type 4) F50 001 002 003 005 007 010 015 020 025 030 040 050 060 075 100 125 150 200 250 300 350 400 450
6KG1143_ _ _ X8A1 (Open, Type 12 Heatsink)
6KG1143_ _ _ X9A1 (Open)

Norminal 460V system applied mot HP 1/2 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450
Output Rated Capacity *1) kVA 1.1 1.9 2.9 4.3 7.1 10 14 19 23 31 35 47 59 72 89 119 140 167 201 242 300 330 414
ratings
Rated Voltage *2) V 3-phase, 380V , 400V , 415V /50Hz , 380V , 400V , 440V , 460V /60Hz
Rated Current *3) A 1.5 2.5 3.7 5.5 9.0 13 18 24 30 39 45 60 75 91 112 150 176 210 253 304 377 415 520
Overload Capability 150% of rated current for 1min , 150% of rated current for 1min ,
200% of rated current for 0.5s 180% of rated current for 0.5s
Rated Frequency Hz 50, 60Hz
Input Phases, Voltage, Frequency 3-phase, 380 to 480V , 50/60Hz 3-phase, 380 to 440V /50Hz , 380 to 480V /60Hz
ratings * 380V/50Hz and 380 to 415V/60Hz *4)
Voltage / frequency variations -Voltage : +10 to -15% ( Voltage unbalance *5) : 2% or less ) -Frequency :+5 to -5%
Momentary voltage dip When the input voltage is 310V or more, the inverter can be operated continuously.
capability *6) When the input voltage drops below 310V from rated voltage, the inverter can be operated for 15ms . (less than 85% load of nominal applied motors)
The smooth recovery method is selectable.

1) Drive output capacity [kVA] at 460V


2) Output voltage is proportional to the power supply and can’t exceed the power supply voltage.
3) Current derating may be required in case of low impedence load such as high frequency motor.
4) Change the tap of auxiliary transformer
380/50 Hz: Change over CN UX connector from U1 part to U2 part (reference to the instruction manual)

Input Voltage CN UX connector


400 to 440V/50 Hz, 440 to 480V/60 Hz U4 (factory setting)
380V/50 Hz (398V or smaller)
380 to 415V/60 Hz (430V or smaller) U2

5) Reference to the IEC 61800-3 (5.2.3)


6) Input power: 85%

8
TM

AF-300 G11 Specifications

Dimensions .25 - 30 Hp
4.34(110) 0.28(7)
Fig. 1 D Fig. 2
0.28(7) 3.78(96) D1
0.24(6) 5.91(150) 0.28(7) 5.71(145)

0.28(7)
2-ø”0.24(ø”6)
0.28(7) 5.35(136) 2.42 (61.5)

0.28(7)
2-ø”0.24(ø”6) 0.24(6)
Control circuit terminals
M3

9.69(246)
10.25(260)
Main circuit terminals
Control circuit terminals
(M3, 5)
(M3)

NP

9.69(246)
10.25(260)
Auxiliary control
power supply terminals
(M3, 5)

NP
0.24(6) D2 Main circuit terminals
0.28(7)

D3 (M4)
0.61(15.5) 3.43(87)
1.56(39.5) 0.61(15.5) 0.31(8) 0.28(6)
3.74(95)

0.28(7)
3-ø”0.87(ø”22) 4.29(109)
Wire inlet 1.22(31)
knock out
hole 1.73(44) 1.22(31) 0.31(8)
1.06(27)
D4

3-ø”0.87(ø”22)
Wire inlet
Type D D1 D2 D3 D4 Knock out
hole
5.12 1.44 3.15 3.70 2.81

3.92(99.5)
1/4, 1/2 HP (130) (36.5) (80) (94) (71.5)

1 HP 5.71 2.03 3.74 4.29 3.41


(145) (51.5) (95) (109) (86.5)

2 to 5 Hp

Fig. 3 8.66(220) 0.47(12) Fig. 4 0.47(12)


9.84(250)
7.68(195) 7.68(195)
0.47(12) 7.72(196) 0.47(12) 8.90(226) 4.17(106)
4.09(104)
0.44(11)

2-ø”0.39(ø”10)

0.44(11)
0.39(10)
2-ø”0.39(ø”10) 0.39(10)

Control circuit terminals


(M3)
Control circuit terminals
9.37(238)
10.25(260)

Auxiliary control (M3)


power supply terminals
14.88(378)
15.76(400)

Auxiliary control
(M3, 5) power supply terminals
NP

(M3, 5)
Main circuit terminals
(M5) Main circuit terminals
5.49(139.5)
(M5)
NP

0.39(10) 5.67(144)
0.44(11)

6.26(159)
1.81(46)
0.31(8) 5.06(128.5)
0.39(10)
2.28(58) 2.07(52.5)
2.17(55) 5.12(130)
0.44(11)

ø”1.06(ø”27) 2-ø”1.34(ø”34) 2.54(64.5) 2.42(61.5)


Wire inlet Wire inlet 6.26(159)
knock out hole knock out hole 0.31(8)
ø”1.34(ø”34)
Wire inlet
knock out hole
2-ø”1.65(ø”42)
5.51(140)

Wire inlet
knock out hole
5.75(146)

7 to 10 Hp 15 to 30 Hp

9
TM

AF-300 G11 Specifications

Dimensions NEMA 1
Surface Mount

230V SERIES NEMA 1


DIMENSIONS inches (mm) Mtg. Wt.
HP W1 W2 W3 W4 H1 H2 H3 H6 H7 H9 H10 D D2 D3 D4 Bolts Lb (kg)
40 HP 9.4 12.8 – 13.5 20.9 19.7 20.2 0.4 7.1 3 29.7 10 0.2 5.7 4.1 M8 70
(240) (326) (342) (530) (500) (512) (9) (180) (75) (755) (255) (4) (145) (105) (32)
50 HP 10.8 14.2 14.9 23.4 22.2 22.7 7.9 33.1 10.6 86
(275) (361) (377) (595) (565) (577) (200) (840) (270) (39)
60 HP 28.3 27.2 27.6 38 106
(720) (690) (702) (965) (48)
75 HP 110
(50)
100 HP 16.9 20.01 21 27 27.4 0.5 11.1 3.3 41.3 11.2 3.6 M12 172
(430) (510) (533) (685) (695) (13) (283) (83) (1050) (285) (91) (78)
125 HP 22.8 26 11.4 26.9 33.5 32.1 32.5 15.1 50.4 14.2 8.7 6.5 282
(580) (660) (290) (683) (850) (815) (825) (383) (1280) (360) (220) (166) (128)
460V SERIES NEMA 1
DIMENSIONS inches (mm) Mtg. Wt.
HP W1 W2 W3 W4 H1 H2 H3 H6 H7 H9 H10 D D2 D3 D4 Bolts Lb (kg)
40 HP 9.4 12.8 – 13.5 20.9 19.7 20.2 0.4 7.1 3 29.7 10 0.2 5.7 4.1 M8 70
(240) (326) (342) (530) (500) (512) (9) (180) (75) (755) (255) (4) (145) (105) (32)
50 HP 10.8 14.2 14.9 10.6 82
(275) (361) (377) (270) (37)
60 HP 25.8 24.6 25.1 34.6 95
(655) (625) (637) (880) (43)
75 HP 97
(44)
100 HP 28.3 27.2 27.6 7.9 38 115
(720) (690) (702) (200) (965) (52)
125 HP 16.9 20.0 21 28 26.6 27 0.5 8.2 3.3 12.4 6.9 4.7 M12 174
150 HP (430) (510) (533) (710) (675) (685) (13) (208) (83) (315) (175) (121) (79)
200 HP 38 37 37 13 53.1 14.2 9 7 245
250 HP (970) (935) (945) (333) (1350) (360) (220) (166) (111)
300 HP 22.8 26 11.4 26.9 15.1 55.1 337
350 HP (580) (660) (290) (683) (383) (1400) (153)
400 HP
450 HP

10
TM

AF-300 G11 Specifications

Dimensions Open Type

Surface Mount Through Panel Mount

[230V SERIES]
HP DIMENSION Inch (mm) Mtg. Weight
230V W W1 W2 W3 H H1 H2 H3 H4 H5 H6 D D1 D2 C Bolts Lb (kg)
40 HP 13.4 9.4 12.8 21.7 20.9 19.7 20.2 0.5 1 0.4 10 5.7 0.2 0.4 M8 64
(340) (240) (326) (550) (530) (500) (512) (12) (25) (9) (255) (145) (4) (10) (29)
50 HP 14.8 10.8 14.2 24.2 23.4 22.2 22.7 10.6 79
(375) (275) (361) (615) (595) (565) (577) (270) (36)
60 HP 29.1 28.3 27.2 27.6 97
(740) (720) (690) (702) (44)
75 HP 101
(46)
100 HP 20.9 16.9 20.1 29.5 27 27.4 0.6 1.3 0.5 11.2 0.6 M12 154
(530) (430) (510) (750) (685) (695) (16) (33) (13) (285) (15) (70)
125 HP 26.8 22.8 26 34.6 33.5 32.1 32.5 14.2 8.7 253
(680) (580) (660) (880) (850) (815) (825) (360) (220) (115)
[460V SERIES]
HP DIMENSION Inch (mm) Mtg. Weight
460V W W1 W2 W3 H H1 H2 H3 H4 H5 H6 D D1 D2 C Bolts Lb (kg)
40 HP 13.4 9.4 12.8 21.7 20.9 19.7 20.2 0.5 1 0.4 10 5.7 0.2 0.4 M8 64
(340) (240) (326) (550) (530) (500) (512) (12) (25) (9) (255) (145) (4) (10) (29)
50 HP 14.8 10.8 14.2 10.6 75
(375) (275) (361) (270) (34)
60 HP 26.6 25.8 24.6 25.1 86
(675) (655) (625) (637) (39)
75 HP 88
(40)
100 HP 29.1 28.3 27.2 27.6 106
(740) (720) (690) (702) (48)
125 HP 20.9 16.9 20.1 28 26.6 27 0.6 1.3 0.5 12.4 6.9 0.6 M12 154
150 HP (530) (430) (510) (710) (675) (682) (16) (33) (13) (315) (175) (15) (70)
200 HP 39.4 38.2 36.8 37.2 14.2 8.7 220
250 HP (1000) (970) (935) (945) (360) (220) (100)
300 HP 26.8 22.8 26 11.4 308
350 HP (680) (580) (660) (290) (140)
400 HP
450 HP

11
TM

AF-300 G11 Specifications


Plug-in Terminal Strip Assignments

30A Y5A CMY Y3 Y1 C1 FMA FMP PLC X1 X2 X3 X4 X5 X6 X7 X8 X9


30C 30B Y5C Y4 Y2 11 12 13 V2 CM CM FWD REV P24 P24 DX DX SD

Terminal
Classification Symbol Terminal Name Function

Analog input 13 Potentiometer power supply Used for +10V DC power supply for frequency setting POT
(resistance of 1 to 5k Ohm)

12 Voltage input ① Frequency is set according to the analog input voltage


supplied from an external circuit.
- 0 to +10V DC / 0 to 100%
- Reversible operation using positive and negative signals:
0 to +/- 10V DC / 0 to 100%
- Reverse operation: +10 to 0V DC / 0 to 100%
② The feedback signal for PID control is input.
③ The analog input value from the external circuit is used
for torque control
* Input resistance: 22 k Ohm

V2 Voltage input ¨ Frequency is set according to the analog input voltage


supplied from an external circuit.
- 0 to +10V DC/0 to 100%
- Reverse operation: +10 to 0V DC/0 to 100%
* Use only one terminal - V2 or C1 alternatively.
* Input resistance: 22 k Ohm

C1 Current input ① Frequency is set according to the analog input current supplied
from an external circuit.
- 4 to 20mA DC / 0 to 100%
- Reverse operation: 20 to 4mA DC / 0 to 100%
② The feedback signal for PID control is input.
③ PTC thermistor input

* Use only one terminal - V2 or C1 alternatively


* Input resistance: 250 Ohm

11 Analog input common Common terminal for analog input signals

12
TM

AF-300 G11 Specifications

Digital input FWD Forward operation / Used for forward operation (when FWD-CM is on) or
Stop command deceleration and stop (when FWD-CM is off)
REV Reverse operation / Used for reverse operation (when REV-CM is on) or
Stop command deceleration and stop (when REV-CM is off)
X1 Digital input 1 The coast-to-stop command, external alarm, alarm reset, multi-
step frequency selection, and other functions (from an external
circuit) can be assigned to terminals X1 to X9. For details, see
"Setting the Terminal Functions E01 to E09" in Section 5.2
Function Explanation in the Instruction Manual.
<Specifications of digital input circuit>

Item min. typ. max.


Operating voltage ON 0V - 2V
X2 Digital input 2 OFF 22V 24V 27V
X3 Digital input 3 Operating current ON 3.2mA 4.5mA
X4 Digital input 4 Allowable leakage current OFF 0.5mA
X5 Digital input 5
X6 Digital input 6
X7 Digital input 7
X8 Digital input 8
X9 Digital input 9

P24 Control Unit power Supply +24VDC power supply for control input. Maximum output current = 100mA
PLC PLC signal power Used to connect power supply for PLC output signals; rated
voltage = 24 VDC (22 to 27) at sink logic operation.
CM Digital input common Common terminal for digital input signals and P24
Analog output FMA Analog monitor Outputs monitor signal using analog DC voltage 0 to +10V DC.
The signal indicates one of the following:
(11: common - Output frequency (before slip compensation)
terminal) - Load factor
- Output frequency (after slip compensation)
- Power consumption
- Output current
- PID feedback value
- Output voltage
- PG feedback value
- Output torque
- DC link circuit voltage
* Connectable impedance: min. 5kW

Pulse output FMP Frequency monitor Outputs a monitor signal using the pulse waveform.
(CM: Common (pulse waveform output) This signal has the same function as the FMA signal.
terminal)

13
TM

AF-300 G11 Specifications

Transistor Y1 Transistor output 1 A running signal, frequency equivalence signal, overload early
warning output signal, and other signals from the drive are output
(as transistor output) to arbitrary ports. For details, see "Setting the
Terminal Functions E20 to E23" in Section 5.2 Function Explanation In
the Instruction Manual.
* <Specifications of transistor output circuit>

Item min. typ. max.


Operating voltage ON – 1V 2V
Y2 Transistor output 2
OFF – 24V 27V
Y3 Transistor output 3
Y4 Transistor output 4
Maximum load current ON – – 50 mA
Leakage current OFF – – 0.1 mA

CME Transistor output common Common terminal for transistor output signals. This terminal is
isolated from terminals (CM) and [11].
Relay output 30A,30B,30C Alarm outputs for any fault. If the drive is stopped by an alarm (protective function), the alarm
signal is output from the relay contact output terminal (1SPDT).
Contact rating: 250 VAC, 0.3A,cosØ = 0.3, 48 VDC, 0.5A for CE Marking
An excitation mode (excitation at alarm occurrence or at normal
operation) can be selected.

Y5A,Y5C Multi-purpose signal These signals can be output similar to the Y1 to Y4 signals above.
relay outputs The contact rating for any fault is the same as that of the alarm
output above.

Communic- DX+,DX– RTU communication Input / output signal terminals for RTU communication input / output
ation Up to 31 inverters can be connected using the daisy chain method.

SD Communication cable Terminal for connecting the cable shield. The terminal is electrically
shield connection terminal floating.-