GENERAL NOTES AND SPECIFICATIONS

1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION
OF THE PHILIPPINE ELECTRICAL CODE, THE RULES AND REGULATIONS OF THE AUTHORITIES THAT HAVE
JURISDICTION OVER THE PROJECT, AND WITH THE POLICIES OF THE LOCAL UTILITY COMLPNIES FOR ELECTRICAL
AND FOR COMMUNICATION.
2. THERE SHALL BE ONLY ONE SERVICE DROP FOR THE WHOLE BUILDING. POWER SERVICE TO THE BUILDING SHALL
BE 230V, 3Ø , 4W, & 60 HZ. DISTRIBUTION SYSTEM WITHIN THE BUILDING SHALL BE 230V, 3Ø, 4W, 60HZ AND 230V, 1Ø,
3W, 60HZ AS SHOWN IN THE PLANS.
3. WIRING METHOD SHALL BE DONE IN THE FOLLOWING MANNER:
A. INTERMEDIATE METALLIC CONDUIT (IMC) PIPE AS SPECIFIED IN THE PLANS, IF ANY.
B. POLYVINYL CHLORIDE (PVC) PIPE FOR POWER SERVICE ENTRANCE AND TELEPHONE SERVICE ENTRANCE
AND BRANCH CIRCUIT RUN.
C. FLEXIBLE METAL CONDUIT FOR CONNECTION BETWEEN JUNCTION BOX INSIDE TO LIGHTING OUTLET OF
FIXTURES AT DROP CEILING.
D. ELECTRICAL METALLIC TUBING FOR EXPOSED LAYOUT AND THOSE SPECIFIED IN THE PLAN.
4. ALL ELECTRICAL MATERIALS/EQUIPMENTS TO BE USED SHALL BE NEW AND OF THE APPROVED TYPE FOR BOTH
LOCATION AND PURPOSE.
5. GENERAL USE RECEPTACLE SHALL BE RATED 15A, 250V, GROUNDING TYPE WITH LPRALLEL SLOTS. SPECIAL
PURPOSE OUTLETS SHALL BE OF THE TYPE AND RATING APPROPRIATE FOR THE EQUIPMENT TO BE SERVED.
6. SWITCHES FOR LIGHTS SHALL BE RATED 10A, 250V, AC RATED ONLY.
7. ALL OUTDOOR INSTALLATIONS SHALL BE OF THE WEATHERPROOF TYPE.
8. UNLESS OTHERWISE SPECIFIED IN THE PLANS, THE MINIMUM SIZE OF WIRE AND CONDUIT TO BE USED SHALL BE
2.0MM THHN AND 15MMØ IMC/EMT(20Ø PVC), RESPECTIVELY. ALL WIRES SHALL BE INSULATED FOR 600V EXCEPT
AS SPECIFIED IN THE PLAN. A SERVICE POST DETAIL
9. WHERE SLPRE CIRCUITS ARE INDICATED IN THE SCHEDULE OF LPNELBOARD, THE CONTRACTOR SHALL PROVIDE E1 SCALE NTS

AN EMPTY CONDUIT STUBBED-OUT INSIDE THE CEILING AND CAPPED.


10. OUTLET BOXES SHALL BE 1.35MM THICK AND AS FOLLOWS:
A. CEILING LIGHT OUTLET 100MM X 100MM X 55MM DEEP OCTAGONAL BOX FOR 1 OR 2
RACEWAY ENTRIES;
100MM X 100MM X 55MM DEEP SQUARE BOX FOR 3 OR
MORE RACEWAY ENTRIES.
B. LIGHT SWITCHES 50MM X 100MM X 55MM DEEP UTILITY BOX FOR 1, 2, OR 3 B RISER DIAGRAM
SWITCHES IN ON STRAP. E1 SCALE NTS

C. WALL MOUNTED CONVENIENCE,


TELEPHONE, ACU OUTLETS, ETC. 50MM X 100MM X 55MM DEEP UTILITY BOX
D. CONVENIENCE OUTLET
SCHEDULE OF LOADS MAIN FEEDER 2
(FLOOR-MOUNTED) POP-UP 100MM X 100MM X 55MM DEEP SQUARE BOX WITH SPECIAL LEGENDS AND SYMBOLS CIRCUIT
TYPE RAISED COVER CKT. LOAD DISCRIPTION
TOTAL
VOLTS
AMPERES
PROTECTION SERVICE WIRE GROUND WIRE
CONDUIT
WATTS (THHN, CU.WIRE) (TW, CU.WIRE)
E. OTHERS AS REQUIRED BY EQUIPMENTS SERVED. PHASE AT

11. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: 1 LIGHTING OUTLET 2700 230 11.739130 1Ø 20A,2P
20A,2P
2-3.5mm² 1-2.0mm² 20mm Ø PVC
2 LIGHTING OUTLET 3100 230 13.478261 1Ø 2-3.5mm² 1-2.0mm² 20mm Ø PVC
A. LPNEL BOARDS, CABINETS & DISCONNECTING SWITCHES - 1400MM ABOVE FLOOR FINISH ON 3 LIGHTING OUTLET 1000 230 4.347826 1Ø 20A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
4 CONVENIENCE OUTLET 3240 230 14.086957 1Ø 20A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
CENTER OR AS REQUIRED BY FIELD CONDITION 5 CONVENIENCE OUTLET 4860 230 21.130435 1Ø 30A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
B. LIGHT CONTROL SWITCHES - 1400MM ABOVE FLOOR FINISH ON CENTER 6
7
CONVENIENCE OUTLET
ACU1 4.0HP/FCU1
1440
2982
230
230
6.260870
12.965217


20A,2P
30A,2P
2-3.5mm²
2-3.5mm²
1-2.0mm²
1-2.0mm²
20mm Ø PVC
20mm Ø PVC
C. CONVENIENCE/ TELEPHONE OUTLETS - 300MM ABOVE FLOOR FINISH ON CENTER 8 ACU2 1.5HP 1118 230 4.860870 1Ø 30A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
9 ACU3 1.5HP 1118 230 4.860870 1Ø 30A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
D. DESK TOP CONVENIENCE OUTLET - 300MM ABOVE WORKING COUNTER @ CENTER 10 ACU4 1.5HP 1118 230 4.860870 1Ø 30A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
E. OTHERS AS REQUIRED BY EQUIPMENT SERVED 11
12
REFRIGERATOR
REFRIGERATOR
800
800
230
230
3.478261
3.478261


20A,2P
20A,2P
2-3.5mm²
2-3.5mm²
1-2.0mm²
1-2.0mm²
20mm Ø PVC
20mm Ø PVC
12. SIZE AND NUMBER OF WIRES AND CONDUITS FOR ALL AUXILLIARY SYSTEM SHALL BE VERIFIED FROM THE 13 WASHING MACHINE/DRYER 800 230 3.478261 1Ø 20A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
14 MICROWAVE OVEN 1300 230 5.652174 1Ø 20A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
SUPPLIER PRIOR TO THE SUBMISSION OF BIDS. REF
15 MICROWAVE OVEN 1300 230 5.652174 1Ø 20A,2P 2-3.5mm² 1-2.0mm² 20mm Ø PVC
13. THE ENTIRE ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER DIRECT SUPERVISION OF A COMPETENT WM/D 16 SPARE 0 230 0.000000 1Ø - - - 20mm Ø PVC
26376 114.678261
REGISTERED ELECTRICAL ENGINEER. OVEN

14.PROVIDE AN ADEQUATE AND EFFECTIVE GROUNDING SYSTEM. IN THE ABSENCE OF GI WATER PIPE IN SERVICE, A CATV
LOAD COMPUTATION:
GROUND ROD MUST BE USED AS REQUIRED. FCU1
IT = 114.678 (PF 1.0) (DF 1.0)
15. SINGLE PHASE (1) LOAD SHALL BE SO CONNECTED TO EFFECT A BALANCE THREE PHASE (3ø) LOADING. Sa IT = 114.678 AMP
MOUNTING HEIGHTS SHALL BE SUBJECT TO PRIOR APPROVAL BY THE ARCHITECT. S2 (a,b)
USE = 125A, 2P, 250V 60HZ BOLT-ON CIRCUIT BREAKER AS MAIN PROTECTION
S3 (a,b,c)

S (EXF1)
USE = 2-50mm² THHN CU. WIRE AS MAIN FEEDER
USE = 1-50mm² THHN AS GROUND WIRE ON 60 mmØ DIA RSC

C SCHEDULE OF LOADS
E1 SCALE NTS

PROPOSED ONE STOREY RESIDENCE


MRS. CARMEN G. FAMULARCANO
E1
N
N
13
PNL

WM/D gg
3 hh
Sgg PNL
Shh
8 9 10 PNL
ACU2 PNL ACU3 PNL ACU4 PNL

11
PNL p p u u y S2 (z,aa)
k k
ee ee
Sy z
14 Sn Ss Sx S2 (ee,ff)
PNL REF S (EXF2)
n s x
OVEN ff
EXF2
aa
l q v
6
12 15 PNL
5 PNL PNL dd
PNL m S (EXF1)
w
REF
OVEN r bb bb ee ee
EXF1
j o o t t
j

S3 (j,k,l) S3 (o,p,q) S3 (t,u,v)


Sm Sr Sw S3 (bb,cc,dd)
2
PNL

f f cc

f a a h h
f
4 S2 (h,i)
PNL S2 (f,g)

g c
b i
aa

7
PNL

ACU1
f f a a h h
FCU1 S3 (a,b,c)
S2 (d,e) 1
f PNL
f

e d d d d e

PROVINCIAL ROAD

A POWER LAYOUT B LIGHTING LAYOUT


E2 SCALE 1:100 MTS E2 SCALE 1:100 MTS

PROPOSED ONE STOREY RESIDENCE


MRS. CARMEN G. FAMULARCANO
E2