Deep Sea Electronics Plc

500 Series CONTROL MODULES

MODEL 500 AUTOMATIC TRANSFER SWITCH MODULE


DESCRIPTION
SPECIFICATION
The 500 is an automatic transfer switch control module.
It is designed to monitor the incoming AC mains supply (3
phases) for under voltage. Should this fall out of limits the
module will issue a start command to the generating set
controller. Once the set is available the ATS module will
control the transfer devices and switch the load from the
mains to the generating set. Should the mains supply
return to within limits the module will command a return to
the mains supply and stop requesting the generator.

A clear mimic diagram with ‘International’ symbols and


LED indications provide ‘at a glance’ information as to
supply availability and load switching status.

In the even of a Mains failure the module operation would


normally be as follows:-
‘Mains available’ LED extinguishes and the module de-
energises the ‘Run Generator’ Relay, causing the ‘Run’
contacts to close. A generator start module receives this signal DC SUPPLY :
and initiates the engine start. The module DC is powered from the plant battery or from
a low voltage supply between 8 to 35V Continuous. It is
Once the generator is running and the ‘Engine Running’ signal able to operate at 0V for 50ms during cranking, providing
is present the ‘Generator available’ LED will illuminate. The supply was at least 10V before dropout and supply
module will then await the ‘Load transfer’ signal from the recovers to 5V. This is achieved without the need for
generator controller, once this is present the Module will then internal batteries.
energise the ‘Close mains’ relay which causes the ‘Close MAX. OPERATING CURRENT :
mains’ contacts to open, thus opening the mains contactor. 85mA @ 12V, 92mA @ 24V.
The ‘Mains on load’ LED will extinguish. After a short time 1 LOW VOLTAGE AUXILIARY RELAY CONTACT :
5Amp DC rated - NC connected internally to -Ve.
delay (Transfer Delay 0.7) to allow the mains contactor to open,
2 MAINS RATED RELAY CONTACTS :
the ‘Close generator’ relay is energised causing the ‘Close
8Amp RMS rated 1 of each -
generator’ contacts to close, thus causing the generator
NO (Voltage Free)
contactor to close. The ‘Generator on load’ LED will illuminate.
NC (Voltage Free)
Should the mains supply return to with-in limits the ‘Mains DIMENSIONS :
Available’ LED will illuminate and the module will energise the 72 x 72 x 76 DIN STANDARD.
‘Run Generator’ Relay causing the ‘Run’ contacts to open, on OPERATING TEMPERATURE RANGE :
removal of the ‘Load transfer’ signal the ‘Generator Close’ -30 to +70oC
relay will de-energise and the ‘Generator Close’ contacts will INDICATIONS :
open. The ‘Generator On load’ LED will extinguish. Following Mains Available LED (Green)
the ‘transfer delay’ the module will de-energise the ‘Mains Mains on Load LED (Amber)
close’ relay and the ‘Close mains’ contacts will close. The Generator Available LED (Green)
‘Mains On Load’ LED will illuminate. When the ‘Engine Running’ Generator On load LED (Amber)
signal is removed the module will then extinguish the ‘Generator OPERATING VOLTAGE :
Available’ LED. The module will then await the next mains failure 100-300V NOMINAL RMS Input Range.
Mains Trip 75V-275V AC RMS (Adjusted via a
event.
potentiometer accessible from the rear of the module.)
The 500 ATS module is intended to be used with the DSE 52x
TRANSFER DELAY :
range of Remote start controllers. The ‘RUN’ contacts connect
0.8Sec (+/- 0.1sec) (Fixed)
to the ‘Remote Start’ input and ‘ENGINE RUNNING’ and ‘LOAD The module is mounted in a robust plastic case, connection to the
TRANSFER’ are fed from Relay outputs on the 52x configured module is via plug and socket connectors.
accordingly. Sequence timers (Start Delay, Warm-up, Stop Though intended for connection to the DSE range of engine
Delay and Cooling) are configured in the 52x module. controllers. The flexibility of the module allows it to be
connected directly to a range of commercially available and
11/24/00 500sales_leaflet.doc Issue 3 MR custom built generator control systems.
CASE DIMENSIONS

1 2 34 5
72.0mm
65.5mm
6 7 8 910111213

76.0mm
72.0mm

Panel Cut-out: 68mmx68mm


8.5mm

TYPICAL CONNECTIONS
Mechanical Interlock

LOAD

Generator Output Mains Input


L1 L1

L2 L2

L3 L3

N N
Electrical Interlock FUSES
FUSE
G M

6 7 8 9 10
Close Gen. Relay (N/O) Close Mains Relay (N/C) 11
FUSE 12
2 500 Automatic Transfer Switch Control Module 13
+V
3 To -Ve
-V 1 4 5

Refer to Operator Manual for input


Start/Run
and output function details and Generator Relay
suggested connection schemes
(Normally Closed)

Engine Running Input Load Generator Input


Optional: Else
Connect 'Load Generator'
to a suitable 'Gen
Available' Signal only.

+V +V
(Suggested 52x Output (Suggested 52x Output ('Remote Start' )
'Delayed Alarms Active') 'Load Transfer') IF USING 52x REMOTE START CONTROLLER

Deep Sea Electronics Plc


Mountside Park, Queen Margarets Road,
Scarborough, YO11 2RH. ENGLAND
Tel:- +44 (0)1723 377566 Fax:- +44 (0)1723 354453 E-Mail:- sales@deepseaplc.com

You might also like