Protection Settings For 11Kv GTG Incomers (Ref620)
Protection Settings For 11Kv GTG Incomers (Ref620)
Protection Settings For 11Kv GTG Incomers (Ref620)
1 8S-ZAN-4010A A01 2500/5 11/√3 40000 11 2099.52 ABB REF 620 50P Three-phase non-directional overcurrent protection - Instantaneous stage PHIPTOC
0.11/√3
2 8S-ZAN-4010B A02 5P20 0.11/√3 Start Value 1.0…..40.00 xIn 0.01 - 1.00 -
GTG INCOMERS
3 7P-ZAN-4010C B01 30VA 0.11/3 kV Start Value Multiplier 0.8…..10.0 - 0.1 - 1 - Disabled
1 = on
Operation - - - 1 = on 5=off
5 = off
1 = 1 out of 3
Disabled
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 -
3 = 3 out of 3
Reset delay time - ms 1 0….60000 20 -
1 = on
Operation - - - 1 = on 1 = on
5 = off
1 = 1 out of 3
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3
Minimum Operate time - ms 1 20…60000 20 20
1 8S-ZAN-4010A A01 2500/5 40000 11 2099.52 ABB REF 620 51P-2 Three phase non-directional overcurrent protection - High Stage PHHPTOC
11/√3
1 = on
2 8S-ZAN-4010B A02 5P20 0.11/√3 Operation - - - 1 = on 1 = on
5 = off
GTG INCOMERS 0.11/√3
1 = 1 out of 3
0.11/3 kV
3 7P-ZAN-4010C B01 30VA Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3
4 7P-ZAN-4010D B02 50/5 Minimum Operate time - ms 1 20…60000 20 20
10P10
1VA Reset delay time - ms 1 0…60000 20 20
1= RMS
Measurement mode 2= DFT - - - 2 = DFT 2 = DFT
3 = Peak-to-Peak
1= Measured Io
Io signal selection 1= Measured Io 1= Measured Io
2 = Calculated Io
1 = on
Operation - - - 1 = on 1 = on
5 = off
1= RMS
Measurement mode 2= DFT 2 = DFT 2 = DFT
3 = Peak-to-Peak
1= Measured Io
Io signal selection 1= Measured Io 1= Measured Io
2 = Calculated Io
Department
Author Status
PROTECTION SETTINGS FOR 11kV GTG INCOMERS (REF620)
Lang. Rev. Date
1 8S-ZAN-4010A A01 2500/5 11/√3 40000 11 2099.52 ABB REF 620 51N-2 Non-directional earth fault protection - High Stage EFHPTOC
0.11/√3
2 8S-ZAN-4010B A02 5P20 Start Value 0.10…..40.00 xIn 0.01 - 0.10 -
0.11/√3
GTG INCOMERS
3 7P-ZAN-4010C B01 30VA 0.11/3 kV Start Value Multiplier 0.8…..10.0 0.1 - 1.0 -
1 = on
Operation - - - 1 = on 5=off
5 = off
1 = 1 out of 3
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3
1= RMS
Measurement mode 2= DFT 2 = DFT 2 = DFT
3 = Peak-to-Peak
1= Measured Io
Io signal selection 1= Measured Io 1= Measured Io
2 = Calculated Io
1 = on
Operation 1 = on 1 = on
5 = off
Current Value 0.05…….1.00 xIn 0.05 0.30 0.10
Current Value Res 0.05…….1.00 xIn 0.05 0.30 0.05 Earth Fault pickup setting is 5%
1 8S-ZAN-4010A A01 2500/5 40000 11 2099.52 ABB REF 620 25 Synchronism and energizing check SECRSYN Group Setting
-1 = Off
1 = Both dead
11/√3 2 = Live L, Dead B
0.11/√3 3 = Dead L, Live B
2 8S-ZAN-4010B A02 5P20 Live dead mode - 1 = Both Dead 2= Live L, Dead B
0.11/√3 4 = Dead Bus, L Any
GTG INCOMERS
0.11/3 kV 5 = Dead L, Bus Any
6 = One Live, Dead
7 = Not Both Live
3 7P-ZAN-4010C B01 30VA Difference voltage 0.01……0.50 xUn 0.01 - 0.05 0.1
4 7P-ZAN-4010D B02 50/5 Difference frequency 0.001…..0.100 xFn 0.001 - 0.001 0.001
10P10
1VA Difference angle 5……90 deg 1 - 5 5.0
1 = on
Operation 1 = on 1 = on
5 = off
1 = Off
Synchro check mode 2 = Synchronous 2 = Synchronous 2 = Synchronous
3 = Asynchronous
Close pulse ms 10 200…..60000 200 200.0 Applicable for command control mode
Maximum syn time - ms 10 100…..6000000 2000 2000.0 Applicable for command control mode
Phase start value 0.50...40.00 xIn 0.01 2.5 0.93 Same as 51P-1 Pickup
Ground start value 0.05...8.00 xIn 1.01 0.2 0.05 Same as 51N-1 Pickup
1=Light+current
ARCSARC1 settings stage needs to be
Operation mode 2=Light only 1=Light+current 1=Light+current
configured with Cable Compartment arc sensor
3=BI controlled
1 = on
Operation 1 = on 1 = on
5 = off
Phase start value 0.50...40.00 xIn 0.01 2.5 0.00 Not applicable
Ground start value 0.05...8.00 xIn 1.01 0.2 0.00 Not applicable
1=Light+current ARCSARC2 settings stage needs to be
Operation mode 2=Light only 1=Light+current 2=Light only configured with Breaker Compartment arc
3=BI controlled sensor
1 = on
Operation 1 = on 1 = on
5 = off
Department
Author Status
PROTECTION SETTINGS FOR 11kV GTG INCOMERS (REF620)
Lang. Rev. Date
Phase start value 0.50...40.00 xIn 0.01 2.5 0.00 Not applicable
Ground start value 0.05...8.00 xIn 1.01 0.2 0.00 Not applicable
1=Light+current ARCSARC3 settings stage needs to be
Operation mode 2=Light only 1=Light+current 2=Light only configured with Busbar Compartment arc
3=BI controlled sensor
1 = on
Operation 1 = on 1 = on
5 = off
Department
Author
PROTECTION SETTINGS FOR 11kV ESSENTIAL GENERATOR INCOMERS (REF620)
Status Lang. Rev. Date
1 ER2-ZAN-4051A ESS GEN INCOMER A16 200/5 11/√3 3375 11 177.15 ABB REF 620 50P Three-phase non-directional overcurrent protection - Instantaneous stage PHIPTOC
0.11/√3
2 ER2-ZAN-4051B B13 5P30 0.11/√3 Start Value 1.0…..40.00 xIn 0.01 - 1.00 -
1 = on
Operation - - - 1 = on 5=off
5 = off
1 = 1 out of 3
Disabled
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 -
3 = 3 out of 3
Reset delay time - ms 1 0….60000 20 -
1 = on
Operation - - - 1 = on 1 = on
5 = off
1 = 1 out of 3
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3
Minimum Operate time - ms 1 20…60000 20 20
1 ER2-ZAN-4051A ESS GEN INCOMER A16 200/5 3375 11 177.15 ABB REF 620 51P-2 Three phase non-directional overcurrent protection - High Stage PHHPTOC
11/√3
1 = on
2 ER2-ZAN-4051B B13 5P30 0.11/√3 Operation - - - 1 = on 1 = on
5 = off
0.11/√3
1 = 1 out of 3
0.11/3 kV
15VA Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3
50/1 Minimum Operate time - ms 1 20…60000 20 20.00
10P10
1VA Reset delay time - ms 1 0…60000 20 20.00
1= RMS
Measurement mode 2= DFT - - - 2 = DFT 2 = DFT
3 = Peak-to-Peak
1= Measured Io
Io signal selection 1= Measured Io 1= Measured Io
2 = Calculated Io
1 = on
Operation - - - 1 = on 1 = on
5 = off
1= RMS
Measurement mode 2= DFT 2 = DFT 2 = DFT
3 = Peak-to-Peak
1= Measured Io
Io signal selection 1= Measured Io 1= Measured Io
2 = Calculated Io
Department
Author
PROTECTION SETTINGS FOR 11kV ESSENTIAL GENERATOR INCOMERS (REF620)
Status Lang. Rev. Date
1 ER2-ZAN-4051A ESS GEN INCOMER A16 200/5 3375 11 177.15 ABB REF 620 51N-2 Non-directional earth fault protection - High Stage EFHPTOC
11/√3
2 ER2-ZAN-4051B B13 5P30 Start Value 0.10…..40.00 xIn 0.01 - 0.10
0.11/√3
0.11/√3
15VA Start Value Multiplier 0.8…..10.0 0.1 - 1.0
0.11/3 kV
50/1 Time Multiplier - 0.01 0.05….15.00 1.00
10P10
1VA Operate delay time - ms 10 40…..200000 40
1 = on
Operation - - - 1 = on 5=off
5 = off
1 = 1 out of 3
Number of start phases 2 = 2 out of 3 - - - 1 = 1 out of 3 1 = 1 out of 3
3 = 3 out of 3
1= RMS
Measurement mode 2= DFT 2 = DFT 2 = DFT
3 = Peak-to-Peak
1= Measured Io
Io signal selection 1= Measured Io 1= Measured Io
2 = Calculated Io
1 = on
Operation 1 = on 1 = on
5 = off
Current Value 0.05…….1.00 xIn 0.05 0.30 0.10
Current Value Res 0.05…….1.00 xIn 0.05 0.30 0.05 Earth Fault pickup setting is 5%
-1 = Off
1 = Both dead
2 = Live L, Dead B
3 = Dead L, Live B
Live dead mode - 1 = Both Dead 2= Live L, Dead B
4 = Dead Bus, L Any
5 = Dead L, Bus Any
6 = One Live, Dead
7 = Not Both Live
1 = on
Operation 1 = on 1 = on
5 = off
1 = Off
Synchro check mode 2 = Synchronous 2 = Synchronous 2 = Synchronous
3 = Asynchronous
Close pulse ms 10 200…..60000 200 200.0 Applicable for command control mode
Maximum syn time - ms 10 100…..6000000 2000 2000.0 Applicable for command control mode
Phase start value 0.50...40.00 xIn 0.01 2.5 0.95 Same as 51P-1 Pickup
Ground start value 0.05...8.00 xIn 1.01 0.2 0.05 Same as 51N-1 Pickup
1=Light+current
ARCSARC1 settings stage needs to be
Operation mode 2=Light only 1=Light+current 1=Light+current
configured with Cable Compartment arc sensor
3=BI controlled
1 = on
Operation 1 = on 1 = on
5 = off
Phase start value 0.50...40.00 xIn 0.01 2.5 0.00 Not applicable
Ground start value 0.05...8.00 xIn 1.01 0.2 0.00 Not applicable
1=Light+current ARCSARC2 settings stage needs to be
Operation mode 2=Light only 1=Light+current 2=Light only configured with Breaker Compartment arc
3=BI controlled sensor
1 = on
Operation 1 = on 1 = on
5 = off
Department
Author
PROTECTION SETTINGS FOR 11kV ESSENTIAL GENERATOR INCOMERS (REF620)
Status Lang. Rev. Date
Phase start value 0.50...40.00 xIn 0.01 2.5 0.00 Not applicable
Ground start value 0.05...8.00 xIn 1.01 0.2 0.00 Not applicable
1=Light+current ARCSARC3 settings stage needs to be
Operation mode 2=Light only 1=Light+current 2=Light only configured with Busbar Compartment arc
3=BI controlled sensor
50L Arc protection ARCSARC3 Non Group Setting
1 = on
Operation 1 = on 1 = on
5 = off
Department
Author
UNDER VOLTAGE & OVER VOLTAGE PROTECTION SETTINGS FOR 11kV GTG & ESSENTIAL INCOMERS (REF620)
Status Lang. Rev. Date
1 8S-ZAN-4010A A01 ABB REF 620 27-1 Three-phase undervoltage protection PHPTUV Group settings
2 8S-ZAN-4010B GTG INCOMERS & A02 Start value 0.05…..1.20 xUn 0.01 - 0.90 0.90
11/√3//0.11/√3//0.11/√3//0.11/3 kV
3 7P-ZAN-4010C ESS GEN INCOMERS B01 Time multiplier - 0.01 0.05……15.00 1.00 -
1 8S-ZAN-4010A A01 ABB REF 620 27-3 Three-phase undervoltage protection PHPTUV Group settings
2 8S-ZAN-4010B GTG INCOMERS & A02 Start value 0.05…..1.20 xUn 0.01 - 0.90 -
11/√3//0.11/√3//0.11/√3//0.11/3 kV
3 7P-ZAN-4010C ESS GEN INCOMERS B01 Time multiplier - 0.01 0.05……15.00 1.00 -
1 8S-ZAN-4010A A01 ABB REF 620 59-2 Three-phase Overvoltage protection PHPTOV Group settings
GTG INCOMERS & 11/√3//0.11/√3//0.11/√3//0.11/3 kV
2 8S-ZAN-4010B A02 Start value 0.05...1.60 xUn 0.01 1.10 1.15
ESS GEN INCOMERS
3 7P-ZAN-4010C B01 Time multiplier - 0.01 0.05...15.00 1.00 -
5 = ANSI Def. Time
15 = IEC Def. Time
STAGE-2: FOR TRIP
17 = Inv. Curve A
4 7P-ZAN-4010D B02 Operating curve type - IEC Def. Time IEC Def. Time
18 = Inv. Curve B 19
= Inv. Curve C
20 = Programmable
1 EGR-ZAN-4090 ESS GEN INCOMER B1F1 4000/5 2250 0.45 2886.84 Schneider SEPAM S81 51-1 Phase overcurrent
1 EGR-ZAN-4090 ESS GEN INCOMER B1F1 4000/5 2250 0.45 2886.84 Schneider SEPAM S81 50-2 Phase overcurrent
27-1 Undervoltage
27-2 Undervoltage
Phase-to-phase
Voltage mode Phase-to-phase voltage / Phase-to-neutral voltage - 27-2 Stage For Trip
voltage
25 Synchro-check
Anticipation of circuit
0.1 to 500 s 10ms 70.00
breaker closing time