isoHV425 D00082 D XXEN
isoHV425 D00082 D XXEN
isoHV425 D00082 D XXEN
isoHV425_D00082_04_D_XXEN/02.2022
ISOMETER® isoHV425xx Insulation monitoring device for
unearthed AC, AC/DC and DC systems (IT system)
with coupling device AGH422 up to 3(N)AC, AC 1000 V, DC 1000 V
Product description
The ISOMETER® monitors the insulation resistance of unearthed AC, AC/DC and DC systems
(IT systems) with nominal system voltages of 3(N)AC, AC/DC 0…1000 V or DC 0…1000 V.
The maximum permissible system leakage capacitance Ce is 150 μF. DC components existing
in AC systems do not influence the operating characteristics, when a minimum load current
of DC 100 mA flows. A separate supply voltage allows de-energised systems to be moni-
tored too.
In order to meet the requirements of applicable standards, customised parameter settings
must be made on the equipment in order to adapt it to local equipment and operating
conditions. Please heed the limits of the area of application indicated in the technical
specifications. Any use other than that described in this manual is regarded as improper.
ISOMETER® isoHV425xx
Application
with coupling device AGH422
• AC main circuits up to 1000 V
Device features • DC main circuits up to 1000 V
• Monitoring the insulation resistance for • Systems including switched-mode power supplies
unearthed AC/DC systems
Variants
• Measurement of the system voltage
(true r.m.s.) with undervoltage and • isoHV425-D4-4 with a serial interface
overvoltage detection • isoHV425-D4M-4 with an analogue output
• Measurement of DC system voltages to Function
earth (L1+/PE and L2-/PE)
The ISOMETER® measures the insulation resistance RF and the system leakage capacitance
• Automatic adaptation to the system Ce between the system to be monitored (L1/+, L2/-) and earth (PE). The RMS value of the
leakage capacitance up to 150 μF nominal system voltage Un between L1/+ and L2/-, as well as the residual voltages UL1e
• Selectable start-up delay, response delay (between L1/+ and earth) and UL2e (between L2/- and earth) are also measured.
and delay on release From a minimum nominal system voltage, the ISOMETER® determines the faulty conductor
• Two separately adjustable response value L1/+ or L2/-, i.e. the distribution of the insulation resistance between the conductors L1/+
ranges of 10…500 kΩ (Alarm 1, Alarm 2) and L2/-, and indicates this by means of a positive or negative sign preceding the insulation
• Alarm signalling via LEDs (AL1, AL2), resistance measurement. The value range of the faulty conductor is ±100 %:
a display and alarm relays (K1, K2)
Display Meaning
• Automatic device self test with connection
monitoring -100 % One-sided fault at conductor L2/-
0% Symmetrical fault
• Selectable N/C or N/O relay operation
+100 % One-sided fault at conductor L1/+
• Measured value indication via a multi-
functional LC display The partial resistances can be calculated from the total insulation resistance RF and the
• Fault memory can be activated faulty conductor (R %) using the following formula:
• Password protection to prevent unau- Fault at conductor L1/+ ->RL1F = (200 % * RF)/(100 % + R %)
thorised parameter changes Fault at conductor L2/- -> RL2F = (200 % * RF)/(100 % – R %)
isoHV425-D4-4 It is possible to assign the detected fault or the faulty conductor to an alarm relay via the
• RS-485 (galvanically separated) including menu. If the values RF or Un violate the response values activated in the “AL” menu, this will
the following protocols: be indicated by the LEDs and relays K1 and K2 according to the signalling assignment set
– BMS interface (Bender measuring device in the “out” menu. In addition, the operation of the relay (n.c./n.o.) can be set and the fault
interface) for data exchange with other memory “M” can be activated.
Bender components If the values RF or Un do not violate their release value (response value plus hysteresis) for
– Modbus RTU the period toff without interruption, the alarm relays will switch back to their initial position
and the alarm LEDs AL1/AL2 go out. If the fault memory is activated, the alarm relays
– IsoData (for continuous data output) remain in the alarm condition and the LEDs light until the reset button “R” is pressed or
isoHV425-D4M-4 the supply voltage Us is interrupted.
• 0(4)…20 mA, 0…400 µA, 0…10 V The device function can be tested using the test button “T”. Parameters are assigned to
analogue output (galvanically separated) the device via the LCD and the control buttons on the front panel; this function can be pass-
word-protected. Parameterisation of the isoHV425-D4-4 is also possible via the BMS bus, for
Certifications example by using a BMS Ethernet gateway (COM460IP) or Modbus RTU.
2 isoHV425_D00082_04_D_XXEN/02.2022
ISOMETER® isoHV425xx with AGH422
isoHV425_D00082_04_D_XXEN/02.2022 3
ISOMETER® isoHV425xx with AGH422
Ordering information
93 90 45 70,5
31,1
47,5
74,5
Operating elements
1 2 3 1 - O
peration LED “ON” flashes in case of interruption of the
connecting wires E/KE or L1(+)/L2(-) or system error.
2 - A
larm LED “AL1” lights when the values fall below the set response
value of alarm 1 and flashes in case of interruption of the connecting
wires E/KE or L1(+)/L2(-), in case of system errors as well as in
AL1 AL2
case of overvoltage (can be activated).
3 - A
larm LED “AL2” lights when the values fall below the set response
value of alarm 2 and flashes in case of interruption of the connecting
wires E/KE or L1(+)/L2(-), in case of system errors as well as in
case of undervoltage (can be activated).
4 4 - LC display
5 - Test button “T”: Call up self test
Arrow-up button: Change parameters, move upwards in the menu
6 - R
eset button “R”: Delete stored alarms
Arrow-down button: Change parameters, move down in the menu
7 - Menu button “MENU”: Call up the menu system
Enter button: Confirm parameter changes
5 6 7
4 isoHV425_D00082_04_D_XXEN/02.2022
ISOMETER® isoHV425xx with AGH422
A2
KE
A1
E
E
GND
AK2
AK1
AK1
AK2
on
o
L1/+
L2/-
8 - A, B RS-485 communication
T/R
B
A
A2
KE
A1
E
E
GND
AK2
AK1
AK1
AK2
k
GND, AK2 the AGH422 to the corres
ponding terminals of the
ON AL1 AL2
ISOMETER®.
5 - T/R Connection for the external
combined test/reset button
T R MENU
on
o
L1/+
L2/-
M+
T/R
K1 K2
isoHV425_D00082_04_D_XXEN/02.2022 5
ISOMETER® isoHV425xx with AGH422
6 isoHV425_D00082_04_D_XXEN/02.2022
ISOMETER® isoHV425xx with AGH422
isoHV425_D00082_04_D_XXEN/02.2022 7
Bender GmbH & Co. KG
Londorfer Straße 65 • 35305 Grünberg • Germany
Tel.: +49 6401 807-0 • info@bender.de • www.bender.de
BENDER Group
isoHV425_D00082_04_D_XXEN / 02.2022 / © Bender GmbH & Co. KG, Germany – Subject to change! The specified standards take into account the edition valid until 02.2022 unless otherwise indicated.