EC3-D13 Digital Scroll Driver and ECD-002 Keypad / Display Unit

Operating Instructions
GB
Wiring
Description
EC3-D13 receives an input signal from
an existing system controller (0…10V,
1 … 6V or 4…20mA) and activates
Copeland Scroll DigitalTM solenoid
valves for capacity control of the Digital
Scroll.
An input allows to monitor the
discharge temperature or the
compressors DLT signal and to send an
Alarm signal if the specified
temperature is exceeded.

! Safety instructions:
• Read installation instructions thoroughly. Failure to comply can result in
device failure, system damage or personal injury.
• The product is intended for use by persons having the appropriate
knowledge and skills.
• Disconnect all voltages from system before installation.
• Do not operate system before all cable connections are completed.
• Do not exceed the specified voltage and current limits
• Comply with local electrical regulations when wiring.

Technical data
Power supply 24VAC ±10%; 50/60Hz; 1A
Power consumption 5VA max.
Plug-in connector Removable screw terminals
wire size 0.14 … 1.5 mm2
Grounding 6.3 mm spade earth connector
Protection class IP20
Connection to ECD-002 ECC-Nxx or CAT5 cable with RJ45 connectors
Digital Input I: 0/24VAC/DC for stop/start function
Analog Inputs O: 4...20 mA, 0...10V, 1 ... 6V
N: Copeland NTC temperature sensor (86K at
25°C) or Discharge Line Thermostat (DLT)
Digital Outputs (2): H: Alarm F: 24V/230V Triac output to PWM J class II cat. transformer for 24VAC
L: Compressor relay for compressor contactor Digital Scroll valve L Compressor relay, dry contact. Relay
SPDT; Imax = 8A res (2A), VAC max = 250V H: Alarm relay, dry contact. Relay coil is energized during normal
Activated: During normal operation (no alarm condition) is not energised at Alarm or power operation.
Deactivated: During alarm condition or power supply is OFF off ! Not for direct compressor
If the alarm relay is not utilized, the user must ensure appropriate safety pre- ! The use of the relay is essential to connection. Use contactor.
!
cautions are in place to protect the system against damage caused by a protect the system in case of power N: Discharge Temp. Sensor or
power failure. failure, if communication interface or Discharge Line Thermostat (DLT)
Digital Scroll valve output SPST contact, Solid State Relay (SSR) the ECD-002 are not utilized! O: One of 4...20 mA, 0...10V, 1...6V
Imax = 1A res (1A), VAC max = 250V Digital Scroll capacity demand
signal from system controller
Ambient temperature range 0 … 50°C
ECD-002 display/keypad unit (LEDs and button functions)
Mounting Next parameter/
Parameters setting/saving value (higher)
The EC3-D13 is designed to be mounted onto a standard DIN rail.

Electrical installation
• Refer to the electrical wiring diagram for electrical connections. ON: demand
• Do not apply voltage to the controller before completion of wiring. OFF: no demand
• Ground the metal housing with a 6.3mm spade connector.
• Important: Keep controller and sensor wiring well separated from mains wiring.
Minimum recommended distance 30mm.
Warning: Use a class II category transformer for 24VAC power supply. Do not ON: alarm Next parameter/
OFF: no alarm Prg & Sel (5 sec) value (lower)
ground the 24VAC lines. We recommend to use individual transformers for EC3
Manual reset for
controller(s) and for 3rd party controllers to avoid possible interference or Selecting/confirming
blinking alarm codes
grounding problems in the power supply. Connecting any EC3 inputs to mains
voltage will permanently damage the EC3.

Digital input status is dependant to operation of compressor/thermostat


Commander Operating condition Digital input (I)
Start / Stop Compressor starts Closed / 24V (Start)
Compressor stops Open / 0V (Stop)

Document Nr.: EC3-D13_65164_EN_R00 091027.doc Replacement for R 1/2 PCN 865888 27.10.2009
EC3-D13 Digital Scroll Driver and ECD-002 Keypad / Display Unit GB
Operating Instructions

Setup and Parameter Modification Using the Keypad Parameter list (must be checked and modified if necessary)
All parameters can be accessed via the 4-button keypad. The configuration
/ DISPLAY PARAMETERS Min Max Unit Def. Custom
parameters are protected by a numerical password. The default password is “12”.
/1 Value to show 0 1 - 0
Select the parameter configuration: 0 = Compressor capacity in %
• Press the PRG button for more than 5 seconds, a flashing “0” is displayed 1 = Discharge temperature / DLT input state
• Press or until “12” is displayed (password) /5 Temperature Unit 0 = °C, 1 = °F 0 1 - 0
• Press SEL to confirm password, the first modifiable parameter code is displayed (/1) Note: This affects only data display. All configuration parameters
To modify parameters see Parameter modification below. must be entered in °C / °K !
Parameter Modification: Procedure A ALARM PARAMETERS
A5 Discharge sensor type 0 1 - 0
• Press or to show the code of the parameter that has to be changed; 0 = NTC, 1 = DLT
• Press SEL to display the selected parameter value; A6 Maximum discharge temperature 100 140 °C 130
• Press or to increase or decrease the value; A7 Discharge temperature alarm delay 0 199 sec 30
• Press SEL to temporarily confirm the new value and display its code; F COMPRESSOR PARAMETERS
• Repeat the procedure from the beginning "press or to show..." F2 Minimum capacity 10 100 % 10
To exit and save the new settings: F3 Maximum capacity 10 100 % 100
• Press PRG to confirm the new values and exit the parameters modification F6 PWM Scroll Valve cycle time 10 20 sec 20
procedure. Match cycle rate to system controller. Reducing F6 will increase number of
Reset all parameters to factory setting: solenoid pulses over lifetime and will reduce life expectancy.
• Make shure that digital input is 0V (open). r SENSOR PARAMETERS
• Press and together for more than 5 seconds. r1 Analog input type 0 2 - 0
• A flashing “0” is displayed. 0 = 0…10V, 1 = 1…6V, 2 = 4…20mA
• Press or until the password is displayed (Factory setting = “12”). ru Analog input filtering 0 1 - 1
• If password was changed, select the new password. 0 = off, 1 = on
• Press SEL to confirm password, “0” is displayed. H OTHER PARAMETERS
• Press SEL to reset all parameters to factory setting H5 Password 0 199 - 12
• Press PRG to activate the function and leave the special function mode.
Alarm Codes •

E3 Discharge Temperature sensor failure


No sensor connected or sensor cable is broken or short circuited Mounting of ECD-002
dA High discharge temperature ECD-002 can be installed at any time also during operation.
• ECD-002 can be mounted in panels with 71x29
Er Data error display - out of range: Data send to the display is out of range.
mm cutout
• Push controller into panel cut-out.(1)
• Make sure that mounting lugs are flush with
Messages
outside of controller housing
--- No data to display
• Insert Allen key into front panel holes and turn
At node start up and when no data is send to the display.
clockwise. Mounting lugs will turn and gradually
In Configuration data initialization
move towards panel (2)
Configuration data are initialized with the factory default values.
• Turn Allen key until mounting lug barely touches
panel. Then move other mounting lug to the same
Note: When multiple alarms occur, the highest priority alarm is displayed until being
position (3)
cleared, then the next highest alarm is displayed until all alarms are cleared. Only then
• Tighten both sides very carefully until keypad is
will parameters be shown again.
secured. Do not over tighten as mounting lugs will
break easily.

Dimensions

EC3-D13 ECD-002

Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111 - D-71332 Waiblingen - Germany - Phone .49-(0)7151-509-0 - Fax .49-(0)7151-509-200
www.emersonclimate.eu

Document Nr.: EC3-D13_65164_EN_R00 091027.doc Replacement for R 2/2 PCN 865888 27.10.2009