PID Temp. Controller
PID Temp. Controller
PID Temp. Controller
WWW.AUBERINS.COM
Instruction Manual
SYL-2342, SYL-2352 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL
Version 4.6
Caution 2. Available Configurations
This controller is intended to control equipment under normal operating Table 1. Controller models conditions. If failure or malfunction of the controller may lead to abnormal Model Control output Ramp/soak option operating conditions that may result in personal injury or damage to the SYL-2342 Relay contact output No equipment or other property, devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of or protect against failure or SYL-2352 SSR control output No malfunction of the controller must be incorporated into and maintained as SYL-2342P Relay contact output Yes part of the control system. SYL-2352P SSR control output Yes Installing the rubber gasket supplied will protect the controller front panel from dust and water splash (IP54 rating). Additional protection is needed All the models listed in table 1 are 1/16 DIN size with dual-alarm outputs. for higher IP rating. This controller carries a 90-day warranty. This warranty is limited to the 3. Terminal Wiring controller only. Model SYL-2352, SYL-2352P Model SYL-2342, SYL-2342P
AL1 AL2
1. Specification
Thermocouple(TC): K, E, S, N, J, T, B, WRe5/26 RTD(Resistance temperature detector): Pt100, Cu50 Input type DC Voltage: 0~5V, 1~5V, 0~1V, -100~100mV, -20~20mV, -5~5V, 0.2~1V. DC current : 0~10mA, 1~20mA, 4~20mA. (use external shunt resistor for higher current) Input range Please see section 4.7 for detail. 0.2% Full scale: RTD, linear voltage, linear current and thermocouple input with ice point compensation or Cu50 copper compensation. Accuracy 0.2% Full scale or 2 C: thermocouple input with internal automatic compensation. Note: for thermocouple B, the measurement accuracy of 0.2% can only be guaranteed when input range is between Response time Display resolution Control mode 600~1800 C. 0.5s (when FILt=0) 1 C, 1 F; or 0.1 C Fuzzy logic enhanced PID control On-off control Manual control Output mode Alarm output Alarm function Manual function Power supply Relay contact (NO): 250VAC/7A, 120V/10A, 24VDC/10A SSR voltage output: 12VDC/30mA Relay contact. 250VAC/1A, 120VAC/3A, 24V/3A Process high alarm, process low alarm, deviation high alarm, and deviation low alarm Automatic/Manual bumpless transfer 85~260VAC/50~60Hz
V + mA + RTD
R R W
AL1
AL2
1 2 3 4 5 +
13 14
6 7 8 9 10
AC 85~260V V Out + mA + RTD
R R W
1 2 3 4 5 +
13 14
6 7 8 9 10
+ SSR AC 85~260V
TC
TC
Power consumption 5 Watt Ambient temperature 0~50C, 32~122F Dimension Mounting cutout 48 x 48 x100 mm (WxHxD) 45 x 45 mm
2011.12
3.1 Sensor connection Please refer to table 3 for the input sensor type (Sn) setting codes. The initial setting for input is for a K type thermocouple. Set Sn to the right sensor code if another sensor type is used. 3.1.1 Thermocouple The thermocouple should be connected to terminals 4 and 5. Make sure that the polarity is correct. There are two commonly used color codes for the K type thermocouple. US color code uses yellow (positive) and red (negative). Imported DIN color code uses red (positive) and green/blue (negative). The temperature reading will decrease as temperature increases if the connection is reversed. When using ungrounded thermocouple that is in touch with a large conductive subject, the electromagnetic field picked up by the sensor tip might be too large for the controller to handle, the temperature display will change erratically. In that case, connecting the shield of thermocouple to terminal 5 (circuit ground of the controller) might solve the problem. Another option is to connect the conductive subject to terminal 5. 3.1.2 RTD sensor For a three-wire RTD with standard DIN color code, the two red wires should be connected to the terminals 3 and 4. The white wire should be connected to terminal 5. For a two-wire RTD, the wires should be connected to terminals 4 and 5. Jump a wire between terminals 3 and 4. Set controller input type, Sn to 21. 3.1.3 Linear input (V, mV, mA or resistance) V and mA current signal inputs should be connected between terminals 2 and 5. Terminal 2 is positive. mV signal inputs should be connected between terminals 4 and 5. Terminal 4 is positive. For resistance inputs, short terminals 3 and 4, then connect resistance inputs between terminals 4 and 5. 3.2 Power to the controller The power cables should be connected to terminals 9 and 10. Polarity does not matter. It can be powered by 85- 2 6 0 V A C power source. N e i t h e r a transformer nor jumper is needed to wire it up. For the sake of consistency with the wiring example described later, we suggest you connect the hot wire to terminal 9 and neutral to 10.
P1/8
AUBER INSTRUMENTS
3.3 Control output connection The SSR control output of the controller SYL-2352 provides a 12V DC signal that can control up to 5 SSRs in parallel. The relay output of the controller SYL-2342 can be used to turn on a contactor or a solenoid valve. It can drive a small heater directly if the heater draws less than 10 Ampere when connected to 120V AC power source. For applications needing two control outputs, such as one for heating and another for cooling, relays AL1 or AL2 can be used for the second output with on/off control mode. Please see Figure 11 for details. 3.3.1 Connecting the load through SSR (for SYL-2352) Connect terminal 7 to the positive input and terminal 8 to the negative input of the SSR. See Figure 8 and 9 for details. 3.3.2 Connecting the load through a contactor (for SYL-2342) Assuming the controller is powered by 120V AC and the contactor has a 120V AC coil, jump a wire between terminals 8 and 9. Connect terminal 7 to one lead of the coil and terminal 10 to the other lead of the coil. Please see Figure 7 for example. 3.3.3. Connecting the heater (or cooler) directly from the internal relay Assuming the controller and the load (heater or cooler) are powered by the same voltage. Jump a wire from terminal 9 to 8. Connect terminal 7 to the one lead of the load and terminal 10 to the other lead of the load. Please see Figure 6 and 11 for details. 3.4 For first time users without prior experience with PID controllers, the following notes may prevent you from making common mistakes. 3.4.1 Power to the heater does not flow through terminal 9 and 10 of the controller. The controller consumes less than 2 watts of power. It only provides a control signal to the relay. Therefore, wires in the 18 to 26 gauge range should be used for providing power to terminals 9 and 10. Thicker wires may be more difficult to install. 3.4.2 The control relay outputs (for SYL-2342), -AL1 and AL2, are dry single pole switches. They do not provide power by themselves. Please see Figure 6, 7 and 11 for how they are wired when providing a 120V output (or when output voltage is the same as the power source for the controller). If the load of the relay requires a different voltage than that for the controller, another power source will be needed. See Figure 10 for examples. 3.4.3 SSR output power does not come from the input of the SSR. The output of the SSR is a single pole switch between terminals 1 and 2 of the SSR. The input of the SSR is for control, or triggering the SSR. (Please note we are talking about the SSR itself, not the SSR control output of the controller). When switching a North American 240V AC power, the heater will be live even when the SSR is off. Users should install a double pole mechanical switch to the power input. 3.4.4. For all controller models listed in this manual, the power is controlled by regulating the duration of on time for a fixed period of time. It is not controlled by regulating amplitude of the voltage or current. This is often referred as time proportional control. e.g. If the cycle rate is set for 100 seconds, a 60% output means controller will switch on the power for 60 seconds and off for 40 seconds (60/100=60%). Almost all high power control systems use time proportional control because amplitude proportional control is too expensive and inefficient.
WWW.AUBERINS.COM
PV display: Indicates the sensor read out, or process value (PV). SV display: Indicates the set value (SV) or output value (%). AL1 indicator: It lights up when AL1 relay is on. AL2 indicator: It lights up when AL2 relay is on. A-M indicator: The light indicates that the controller is in manual mode. For the controllers with the Ramp/Soak option, this light indicates that the program is running. Output indicator: It is synchronized with control output (terminal 7 and 8), and the power to the load. When it is on, the heater (or cooler) is powered. SET key: When it is pressed momentarily, the controller will switch the lower (SV) display between set value and percentage of output. When pressed and held for two seconds will put the controller into parameter setting mode. Automatic/Manual function key (A/M) /Data shift key Decrement key : Decreases numeric value of the setting value. Increment key : Increases numeric value of the setting value. 4.1 Display Status
Power on Display mode 2
SET
Display mode 1
8 0 0 .0 8 0 0 .5
PV SV
8 0 0.0 A 60
PV
A/M
8 0 0.0 M 60
PV
SET 2S
A/M
SET
Display mode 3
A L M1 1005
ALM1 (high limit alarm)=1005
SET
Next parameter
Figure 3. Display modes Display mode 1: When the power is turned on, the upper display window shows the measured value (PV) and the lower window shows the four-digit set value (SV). Display mode 2: Press the SET key to change the display status into mode 2. The upper display window shows the measured value (PV) and the lower windows shows the output value. This picture shows the output percentage is 60% when in Automatic (PID) control mode. If parameter A-M=1 (see table 2), pressing the A/M key will switch the controller between PID and Manual control mode with the output unchanged. -This bumpless transfer allows the controller to be switched between manual and automatic mode without the output suddenly 'bumping' to a different value. Display mode 3: Press the SET key for 2 seconds to enter the display mode 3. This mode allows users to change the system parameters.
3 4 5 6
8888 8888
7 8 9 10 Figure 2. Front panel
1 2
2011.12
P2/8
AUBER INSTRUMENTS
4.2.2 Display change 4.4 Parameter Setting Press the SET key to change the display mode. The display can be changed Table 2. System parameters between display modes 1 and 2. Code Description 4.2.3 Manual/Automatic mode switch Bumpless switching between PID mode and Manual mode can be performed ALM1 Process high alarm by pressing the A/M key. The A-M LED will light up when the controller is in ALM2 Process low alarm Manual mode. In Manual mode, the output amplitude can be increased or Hy-1 Deviation high alarm decreased by pressing and (display mode 2). Please note that manual control is initially disabled (A/M=2). To activate Hy-2 Deviation low alarm the manual control, set A/M=0 or 1. Hy Hysteresis Band 4.2.4 Parameter Setup Mode When the display mode is 1 or 2, press SET and hold for roughly 2 seconds At Auto tuning until the parameter setup menu is displayed (display mode 3). Please refer to 4.3 for how to set the parameters. 4.3 Setup flow chart While in the parameter setup mode, use and to modify a digit and use A/M to select the digit that needs to be modified. Press the A/M and SET key a t t h e s a m e t i m e to exit the parameter setup mode. The instrument will automatically exit if no key is pressed for 10 seconds. Figure 4 is the setup flow chart. Please note the changed parameter will be automatically registered without pressing the SET key. If the controller is locked ( see 4.17 ) , only limited parameters (or no parameters) can be changed. PV SV
SET 2S
WWW.AUBERINS.COM
Setting Range -1999~+9999 C or F -1999~+9999 C or F 0~9999 C or F 0~9999 C or F 0~200.0 C or F or 0~2000 for linear input 0~3. Set to 1 or 2 to start auto tuning 0~9999 1~9999 % 0~2000 2~125 0~37 0~3 -1999~+9999 C or F -1999~+9999 C or F -1999~+4000 -1999~+9999 C or F 0~2 0~110 % 0~110 % 0-31 0~15 0~20 0~19200 0~20 0. Manual 1. Automatic 2. Manual suppressing 0~9999 nonE ~ A-M
Initial Setting 100 50 9999 9999 0.3 3 1000 500 120 2 for SSR 20 for relay 0 (K type TC) 0 -100 2500 0.0 0 0 100 17 10 1 9600 0 2
Remarks
See 4.4.1
Integral time
P d t Sn dP P-SL P-SH Pb OP-A OUTL OUTH AL-P COOL Addr bAud FILt A-M
Proportional Constant Derivative Time Cycle time Input type Decimal point position Display low limit Display high limit Input offset Output mode Output low limit Output high limit Alarm output definition System function selection Communication address Communication baud rate PV input filter Automatic/Manual status Configuration privilege Field parameter definition
See 4.5.1
- 100
SET ALM1 Process high alarm ALM2 Process low alarm Hy-1 Deviation high alarm Hy-2 Deviation low alarm Hy Hysteresis band At
P-SL
P-SL Display low limit P-SH Display high limit Pb Input offset OP-A Output mode OutL Output low limit OutH Output high limit AL-P Alarm output definition Cool System function selection Addr Communication address Baud Communication baud FILT PV input filter A-M Running status Lock Configuration privilege
See 4.10 See 4.11 See 4.12 See 4.13 For heating and F display, see 4.14 Ignore this setting Ignore this setting See 4.15 Manual control is disabled. Set to 1 to activate. See 4.16 All parameters are unlocked. See 4.17 To be defined by user. See 4.17
ALM1
100
SET
2500
SET
P-SH Pb
ALM2
50
SET
0.0
SET
9999
SET
HY-1
Op-A
0
SET
9999
SET
HY-2 HY AT I
outL
SET
0.3
SET
OUtH
100
SET
AL-P
Control mode I
17
SET
LocK EP1-EP8
808 nonE
SET
1000
SET
10
SET
500
SET
SET
4.4.1 Alarm parameters This controller offers four types of alarm, ALM1, ALM2, Hy-1, Hy-2. ALM1: High limit absolute alarm. If the process value is greater than the value specified as ALM1+Hy (Hy is the Hysteresis Band), then the alarm will turn on. It will turn off when the process value is less than ALM1-Hy. ALM2: Low limit absolute alarm. If the process value is less than the value specified as ALM2-Hy, then the alarm will turn on, and the alarm will turn off if the process value is greater than ALM2+Hy. Hy-1: Deviation high alarm. If the temperature is above SV+Hy-1 +Hy, the alarm will turn on, and the alarm will turn off if the process value is less than SV+Hy-1 -Hy (we will discuss the role of Hy in the next section) Hy-2: Deviation low alarm. If the temperature is below SV-Hy-2 -Hy, the alarm will turn on, and the alarm will turn off if the temperature is greater than SV-Hy-2 +Hy.
120
SET
d t
SET
filt
2
SET
Cycle time Sn
SET
SN DP
A-M
2
SET
Input type dP
SET
Locw
808
SET
SET
2011.12
P3/8
AUBER INSTRUMENTS
The things you should know about alarm 1) Absolute alarm and deviation alarm High (or low) limit absolute alarm is set by the specific temperatures that the alarm will be on. Deviation high (or low) alarm is set by how many degrees above (or below) the control target temperature (SV) that the alarm will be on. e.g. Assuming ALM1=1000 F, Hy-1=5 F, SV=700 F. When the probe temperature (PV) is above 705, the deviation alarm will be on. When the temperature is above 1000 F, the process high alarm will be on. Later, when SV changes to 600 F, the deviation alarm will be changed to 605 but process high alarm will remain the same. Here the Hysteresis Band (Hy) setting is ignored. Please see 4.5.2 for details. 2) Alarm Suppression feature Sometimes, user may not want the low alarm to be turned on when starting the controller at a temperature below the low alarm setting. The Alarm Suppression feature will suppress the alarm from turning on when the controller is powered up (or SV changes). The alarms can only be activated after the PV has reached SV. This feature is controlled by the B constant of the COOL parameter (see 4.14). The default setting is alarm suppression on. If you use the AL1 or AL2 relay for a control application that needs it to be active as soon as the controller is powered up, you need to turn off the alarm suppression by setting B=0. 3) Assignment of the relays for the alarms AL1 and AL2 are the name of the two relays used for alarm output. AL1 is the alarm relay 1 and AL2 is alarm relay 2. Please do not confuse the relays with alarm parameter ALM1 (process high alarm) and ALM2 (process low alarm). Either the AL1 or the AL2 can be used for any of the four alarms. AL-P (alarm output definition) is a parameter that allows you to select the relay(s) to be activated when the alarm set condition is met. You can set all four alarms to activate the one relay (AL1 or AL2), but you cant activate both relays for with just one alarm. 4) Display of the alarm When AL1 or AL2 relay is activated, the LED on the upper left will light up. If you have multiple alarms assigned to a single relay, you might want to know which alarm activated the relay. This can be done by setting the E constant in the AL-P parameter (see 4.13). When E=0, the bottom display of the controller will alternately display the SV and the activated alarm parameter. 5) Activate the AL1 and AL2 by time instead of temperature For the controllers with the ramp and soak function (SYL-2342P and SYL2352P), AL1 and AL2 can be activated when the process reaches a specific time. This is discussed in the section 3.7 of Supplementary Instruction Manual for ramp/soak option. 4.4.2 Hysteresis Band Hy The Hysteresis Band parameter Hy is also referred as Dead Band, or Differential. It permits protection of the on/off control from high switching frequency caused by process input fluctuation. Hysteresis Band parameter is used for on/off control, 4-alarm control as well as the on/off control at auto tuning. For example: 1) When controller is set for on/off heating control mode, the output will turn off when temperature goes above SV+Hy and on again when it drops to below SV-Hy. 2) If the high alarm is set at 800 F and hysteresis is set for 2 F, the high alarm will be on at 802 F (ALM1+Hy) and off at 798 F (ALM1-Hy). Please note that the cycle time can also affect the action. If the temperature passes the Hy set point right after the start of a cycle, the controller will not respond to the Hy set point until the next cycle. If cycle time is set to 20 seconds, the action can be delay as long as 20 seconds. Users can reduce the cycle time to avoid the delay. 4.4.3 Control mode At At=0 On/off control. It works like a mechanical thermostat. It is suitable for devices that do not like to be switched at high frequency, such as motor and valves. See 4.5.2 for details. At=1 Gets the controller ready to start the Auto tuning process by pressing the A/M key. At=2 Start auto tuning. The function is the same as starting auto tuning from front panel. At=3 This configuration is automatically set after auto tuning is done. Auto
WWW.AUBERINS.COM
tuning from the front panel is inhibited to prevent accidental re-starting of the auto tuning process. To start auto tuning again, set At=1 or At=2. 4.5 Control action explanations 4.5.1 PID Please note that because this controller uses fuzzy logic enhanced PID control software, the definition of the control constants (P, I and d) are different than that of the traditional proportional, integral, and derivative parameters. In most cases the fuzzy logic enhanced PID control is very adaptive and may work well without changing the initial PID parameters. If not, users may need to use auto-tune function to let the controller determine the parameters automatically. If the auto tuning results are not satisfactory, you can manually fine-tune the PID constants for improved performance. Or you can try to modify the initial PID values and perform auto tune again. Sometimes the controller will get the better parameters. The auto-tune can be started in two ways. 1) Set At=2. It will start automatically after 10 seconds. 2) Set At=1. Then you can start the auto-tune any time during the normal operation by pressing the A/M key. During auto tuning, the instrument executes on-off control. After 2-3 times on-off action, the microprocessor in the instrument will analyze the period, amplitude, waveform of the oscillation generated by the on-off control, and calculate the optimal control parameter value. The instrument begins to perform accurate artificial intelligence control after auto tuning is finished. If you want to exit from auto tuning mode, press and hold the (A/M) key for about 2 seconds until the blinking of "At" symbol is stopped in the lower display window. Generally, you will only need perform auto tuning once. After the auto tuning is finished. The instrument will set parameter At to 3, which will prevent the (A/M) key from triggering auto-tune. This will prevent an accidental repeat of the auto-tuning process. (1) Proportional constant P Please note the P constant is not defined as Proportional Band as in the traditional model. Its unit is not in degrees. A larger constant results in larger and quicker action, which is the opposite of the traditional proportional band value. It also functions in the entire control range rather than a limited band. If you are controlling a very fast response system (>1 F/second) that fuzzy logic is not quick enough to adjust, set P=1 will change the controller to the traditional PID system with a moderate gain for the P. (2) Integral time I Integral action is used to eliminate offset. Larger values lead to slower action. Increase the integral time when temperature fluctuates regularly (system oscillating). Decrease it if the controller is taking too long to eliminate the temperature offset. When I =0, the system becomes a PD controller. (3) Derivative time D Derivative action can be used to minimize the temperature over-shoot by responding to its rate of change. The larger the number, the faster the action.
When heating, At=0 If PV(SV-Hy), relay on If PV(SV+Hy), relay off (SV=100, Hy=3)
Relay On
2011.12
P4/8
AUBER INSTRUMENTS
4.5.3. Manual mode
Manual mode allows the user to control the output as a percentage of the total heater power. It is like a dial on a stove. The output is independent of the temperature sensor reading. One application example is controlling the strength of boiling during beer brewing. You can use the manual mode to control the boiling so that it will not boil over to make a mess. The manual mode can be switched from PID mode but not from On/off mode. This controller offers a bumpless switch from the PID to manual mode. If the controller outputs 75% of power at PID mode, the controller will stay at 75% when it is switched to the manual mode, until it is adjusted manually. See Figure 3 for how to switch the display mode. The Manual control is initially disabled (A/M=2). To activate the manual control, set A/M=0 or 1. 4.6 Cycle time t It is the time period (in seconds) that the controller uses to calculate its output. e.g. When t=2, if the controller decides output should be 10%, the heater will be on 0.2 second and off 1.8 seconds for every 2 seconds. Smaller t values result in more precision control. For SSR output, t is set at the minimum (2 seconds). For relay or contactor output, it should be set longer to prevent contacts from wearing out too soon. Normally it is set to 20~ 4 0 seconds. 4.7 Input selection code for Sn Table 3. Code for Sn and its range.
WWW.AUBERINS.COM
2) For linear input devices (voltage, current or resistance input, Sn=26-37) Table 4. dP parameter setting dP Value 0 1 2 3
Display format
0000
000.0
00.00
0.000
Sn code 0 1 2 3 4 5 6 7 20 21 26 27 28 29 30 31 32
Input device K (thermocouple) S(thermocouple) WRe (5/26) (thermocouple) T (thermocouple) E (thermocouple) J (thermocouple) B (thermocouple) N (thermocouple) Cu50 (RTD) Pt100 (RTD) 0~80 0~400 0~20mV 0~100 mV 0~60 mV 0~1V 0.2~1V 4-20mA (w/ 50 Resistor) 1~5V 4~20mA (w/ 250 Resistor) 0~5V -20~+20mV -100~+100mV -5V~+5V
Display range (C) Display range (F) -50~+1300 -50~+1700 0~2300 -200~350 0~800 0~1000 0~1800 0~1300 -50~+150 -200~+600 -58~2372 -58~3092 32~4172 -328~662 32~1472 32~1832 32~3272 32~2372 -58~302 -328~1112
33 34 35 36 37
4.8 Decimal point setting dP 1) In case of thermocouple or RTD input, dP is used to define temperature display resolution. dP=0, temperature display resolution is 1 C (F). dP=1, temperature display resolution is 0.1 C . The 0.1 degree resolution is only available for Celsius display. The temperature will be displayed at the resolution of 0.1 C for input below 1000 C and 1 C for input over 1000 C.
4.9 Limiting the control range, P-SH and P-SL 1) For temperature sensor input, the P-SH and P-SL values define the set value range. P-SL is the low limit, and P-SH is the high limit. e.g. Sometimes, you may want to limit the temperature setting range so that the operator cant set a very high temperature by accident. If you set the PSL=100 and P-SH =130, operator will only be able to set the temperature between 100 and 130. 2) For linear input devices, P-SH and P-SL are used to define the display span. e.g. If the input is 0-5V. P-SL is the value to be displayed at 0V and PSH is the value at 5V. 4.10 Input offset Pb Pb is used to set an input offset to compensate the error produced by the sensor or input signal itself. For example, if the controller displays 5 C when probe is in ice/water mixture, setting Pb=-5, will make the controller display 0 C. 4.11 Output definition OP-A This parameter is not used for this model. It should not be changed. 4.12 Output range limits OUTL and OUTH OUTL and OUTH allow you set the output range low and high limit. OUTL is a useful feature for a system that needs to have a minimum amount of power as long as the controller is powered. e.g. If OUTL=20, the controller will maintain a minimum of 20% power output even when input sensor failed. OUTH can be used when you have an overpowered heater to control a small subject. e.g. If you set the OUTH=50, the 5000 watt heater will be used as 2500W heater (50%) even when the PID wants to send 100% output. 4.13 Alarm output definition AL-P Parameter AL-P may be configured in the range of 0 to 31. It is used to define which alarms (ALM1, ALM2, Hy-1 and Hy-2) is output to AL1 or AL2. Its function is determined by the following formula: AL-P=AX1+BX2+CX4+DX8+EX16 If A=0, then AL2 is activated when Process high alarm occurs; If A=1, then AL1 is activated when Process high alarm occurs; If B=0, then AL2 is activated when Process low alarm occurs; If B=1, then AL1 is activated when Process low alarm occurs; If C=0, then AL2 is activated when Deviation high alarm occurs; If C=1, then AL1 is activated when Deviation high alarm occurs; If D=0, then AL2 is activated when Deviation low alarm occurs; If D=1, then AL1 is activated when Deviation low alarm occurs; If E=0, then alarm types, such as ALM1 and ALM2 will be displayed alternatively in the lower display window when the alarms are on. This makes it easier to determine which alarms are on. If E=1, the alarm will not be displayed in the lower display window (except for orAL). Generally this setting is used when the alarm output is used for control purposes. For example , in order to activate AL1 when a Process high alarm occurs, trigger AL2 by a Process low alarm, Deviation high alarm, or Deviation low alarm, and not show the alarm type in the lower display window, set A=1, B=0, C=0, D=0, and E=1. Parameter AL-P should be configured to: AL-P=1X1+0X2+0X4+0X8+1X16=17 (this is the factory default setting) Note: Unlike controllers that can be set to only one alarm type (either absolute or deviation but not both at same time), this controller allows both alarm types to function simultaneously. If you only want one alarm type to function, set the other alarm type parameters to maximum or minimum (ALM1, Hy-1 and Hy-2 to 9999, ALM2 to 1999) to stop its function. 4.14 COOL for Celsius, Fahrenheit, Heating, and Cooling Selection Parameter COOL is used to set the display unit, heating or cooling, and alarm suppression. Its value is determined by the following formula: COOL=AX1+BX2+CX8 A=0, reverse action control mode for heating control.
2011.12
P5/8
AUBER INSTRUMENTS
A=1, direct action control mode for cooling control. B=0, without alarm suppressing when turned on or when set point changes. B=1, alarm suppressing at power up or set point changes. C=0, display unit in C. C=1, display unit in F. The factory setting is A=0, B=1, C=1 (heating, with alarm suppression, display in Fahrenheit). Therefore, COOL=0X1+1X2+1X8=10 To change from Fahrenheit to Celsius display, set COOL=2 4.15 Input digital filter FILt If measurement input fluctuates due to noise, then a digital filter can be used to smooth the input. FILt may be configured in the range of 0 to 20. Stronger filtering increases the stability of the readout display, but causes more delay in the response to change in temperature. FILt=0 disables the filter. 4.16 Manual and Automatic Mode Selection A-M Parameter A-M is for selecting automatic or manual control mode. A-M=0, manual control mode A-M=1, automatic control mode (either PID or On/off control) A-M=2, automatic control mode, in this state manual operation is prohibited This parameter functions differently for controllers with the ramp/soak function (see supplemental manual for details). 4.17 Lock up the settings, field parameter EP and parameter LocK To prevent the operator from changing the settings by accident, you can lock the parameter settings after initial setup. You can select which parameter can be viewed or changed by assigning one of the field parameters to it. Up to 8 parameters can be assigned into field parameter EP1-EP8. The field parameter can be set to any parameter listed in Table 2, except parameter EP itself. When LocK is set to 0, 1, 2, and so on, only parameters or setting values of program defined in an EP can be displayed. This function can speed up parameter modification and prevent critical parameters (like input, output parameters) from being modified. If the number of field parameters is less than 8, then define the first unused parameter as none. For example, if only ALM1 and ALM2 need to be modified by field operators, the parameter EP can be set as following: LocK=0, EP1=ALM1, EP2=ALM2, EP3=nonE. In this case, the controller will ignore the field parameters from EP4 to EP8. If field parameters are not needed after the instrument is initially adjusted, simply set EP1 to nonE. Lock code 0, 1 and 2 will give the operator limited privileges to change some of the parameters that can be viewed. Table 5 shows the privileges associated with each lock code. Table 5. LocK parameter
WWW.AUBERINS.COM
5. Wiring examples
5.1 Controlling the load directly with internal relay
1 2 13 14 6 7 Fuse L N 120VAC
Heater
3 SYL-2342 8 + 4 9 TC - 5 10
Figure 6. SYL-2342 or SYL-2342P control the heater directly by the internal relay of the controller. The heater must consume less current than the internal relays maximum rating (7A at 240VAC and 10A at 120VAC).
120VAC
L
2 3 SYL-2342
7 8 9 10
Contactor Fuse
13
14
Heater
TC
+ 4 - 5
L N 120VAC
Figure 7. SYL-2342 or SYL-2342P with thermocouple input and external relay output. This is a typical wiring for oven and kiln. Using the external contactor allows users to control higher power loads than the internal relay can handle. It is also easy to service. If the contacts of the relay wear out, it is more economical to replace them than to repair the controller. In this example, we assume the coil voltage of the contactor is the same as the voltage of the controller power supply. The voltage of power supply for alarm is 120V AC. Note: You dont have to wire or set the alarm to control the temperature. It is just to show how the alarm can be wired. 5.3 Controlling the load via SSR
120VAC buzzer
1 2
13 14
6 7 + SSR -4
1 3 2
Heater
3 SYL-2352 8 4 9 5 10
Fuse
L N 120V AC
Figure 8. SYL-2352 or SYL-2352P with RTD input. This is a typical wiring for controlling the temperature of a tank of liquid with high precision. The RTD sensor can offer accuracy within a fraction of a degree . The SSR allows the heater to be switched at higher frequency for better stability. It also has longer life time than the electromechanical relay. A proper heat sink is needed when the SSR switches >8A of current. For wiring a 240V heater, please see 5.4.
Note: to limit the control temperature range instead of completely locking it, please refer to section 4.9.
2011.12
P6/8
AUBER INSTRUMENTS
5.4 Controlling the load via SSR, 240VAC example
1 2
R R
WWW.AUBERINS.COM
5.7 Maintaining a temperature difference using two thermocouples
13 14
6 7 + SSR 4 1 3 2
13 14
6 7 L N 120VAC
RTD
3 SYL-2352 8 4 9 5 10
3 SYL-2342 8 + 4 9 - 5 10
Figure 9. This is the essentially the same wiring example as 5.3, except the heater and controller are powered by 240V AC. An alarm is not installed in this example. 5.5 Controlling a 24V valve
Solenoid valve 1 2 13 14 6 7 L Fuse N 120VAC
Figure 12. SYL-2342 with two thermocouple inputs. Connect two thermocouples in series with opposite polarity (negative connected to negative). Leave the two positive connected respectively to the input terminals on the controller. The one for lower temperature is connected to negative input of the TC input. The one for higher temperature is connected to the positive input. Set up the controller (assume K type TC is used) 1) Sn=35. Set the input type to -20mv~20mv. It eliminates the interference of internal cold junction compensation circuit. 2) P-SL= -501 and P-SH=501. This converts the mili-volt units to degree Celsius. (P-SL= -902 and P-SH=902 for Fahrenheit). To control a 20C difference, set SV=20. Note, P-SL and P-SH are calculated assuming the temperature/ voltage relation of the TC is linear for the application range. We used 20C temperature difference at 0C for this calculation. Please contact us if you have any question.
S
24VAC
3 SYL-2342 8 + 4 9
TC
- 5
10
Figure 10. SYL-2342 or SYL-2342P with thermocouple input. This is a typical wiring set up for a 24V gas, hot water valve, or a contactor with 24V coil voltage. 5.6 Cooling and heating with the same controller
Bulb
1 2 3
13
14
SYL-2342
TC
+ 4 - 5
Figure 11. A refrigerator connected to SYL-2342 directly This is an example for beer fermentation. The refrigerator is driven by the internal relay of the controller directly. Please note that the internal relay output (terminals 7 and 8) is not powered by itself. A power supply must be used to drive the external relay. The refrigerator must consume less current than the internal relays maximum rating (7A at 240V AC and 10A at 120V AC). The bulb (less than 100-300 W) is for heating. The example is setup to have the heater to turn on when temperature drops to below 60 F and turns off at 64 F. The refrigerator will turn on when temperature is above 69 F and turn off at 65 F. Set up for the controller 1) Hy = 2.0. Set both hysteresis band for heater and cooler to 2 degree. 2) COOL=9. Set the controller to cooling mode, no alarm suppression, Fahrenheit temperature unit display. 3) AT=0. Set the controller main output to on/off control mode for refrigerator compressor control 4) ALM2= 6 2 . Set the low limit alarm to 6 2 F. Heater will be on at 6 0 F (ALM2-Hy) and off at 64 F (ALM2+Hy) 5) SV=67. Refrigerator will be on at 69 F (SV+Hy) and off at 65 F (SV-Hy).
2011.12
P7/8
AUBER INSTRUMENTS
WWW.AUBERINS.COM
Auber Instruments 730 Culworth, Alpharetta, GA 30022 www.auberins.com e-mail: info@auberins.com Tel: 770-569-8420
2011.12
P8/8