Cat® DE165 GC

Diesel Generator Sets

Standby: 50 Hz & 60 Hz Engine Model Cat® C7.1 Inline 4-stroke Diesel


Bore x Stroke 105.0 mm x 135.0 mm (4.1 in x 5.3 in)
Displacement 7.0 L (427.8 in³)
Compression Ratio 16.0:1
Turbocharged Air To Air
Aspiration
Charge Cooled
Fuel Injection System Inline
Governor Mechanical
Image shown might not reflect actual configuration.

Standby
Model 50 Hz kVA (ekW) 60 Hz kVA (ekW) Emission Strategy
DE165 GC 163.9 (131.1) 185.5 (150.0) Low BSFC

PACKAGE PERFORMANCE
Performance Standby
50 Hz 60 Hz
Genset power rating 163.9 kVA 187.5 kVA
Genset power rating with fan @ 0.8 power factor 131.1 kW 150.0 kW
Emissions Low BSFC
Performance number P4200A P4202A
Fuel Consumption
Fuel tank capacity, litres (US gal) 325 (85.9)
100% load with fan, L/hr (gal/hr) 35.1 (9.3) 41.1 (10.9)
75% load with fan, L/hr (gal/hr) 27.2 (7.2) 31.9 (8.4)
50% load with fan, L/hr (gal/hr) 18.3 (4.8) 21.8 (5.8)
Cooling System1
Radiator air flow, m³/min (cfm) 259.0 (9147) 318 (11230)
Total coolant capacity, L (gal) 21.0 (5.5)
Inlet Air
Max. combustion air intake restriction, kPa (in H2O) 5.0 (20.1)
Combustion air inlet flow rate, m³/min (cfm) 10.7 (377) 15.0 (529)
Exhaust System
Exhaust stack gas temperature, °C (°F) 484 (903) 407 (765)
Exhaust gas flow rate, m³/min (cfm) 25.5 (902) 32.2 (1137)
Exhaust system backpressure (maximum allowable), kPa (in. water) 6.0 (1.8)
Heat Rejection
Heat rejection to jacket water, kW (Btu/min) 75.7 (4305) 80.1 (4555)
Heat rejection to alternator, kW (Btu/min) 10.2 (580) 11.1 (631)
Heat rejection to atmosphere from engine, kW (Btu/min) 12.2 (694) 12.3 (699)
Heat rejection to exhaust (total) kW (Btu/min) 105.6 (6005) 120.6 (6858)

LEHE2690-00 1/2
DE165 GC Diesel Generator Sets
Electric Power

Alternator2 50 Hz 60 Hz
Voltages 380 415 400 480 440 220 380 240
Motor starting capability @ 30%
378 453 419 504 425 425 316 377
Voltage Dip, skVA
Current, amps 247.4 228 236 225.5 244.9 489.7 255.1 437.4
Temperature Rise, °C 163/27 163/27 163/27 130/40 163/27 163/27 163/27 163/27
Frame Size A2625L4
Excitation S.E

WEIGHTS & DIMENSIONS

A B
Note: General configuration not to be used for installation. See general dimension drawings for detail.

Dim “A” Dim “B” Dim “C” Dry Weight


mm (in) mm (in) mm (in) kg (lb)

3325 (130.9) 1134 (44.6) 1666 (65.6) 1834 (4043.3)


#
Weight includes standard generator, Enclosure and Integral Tank base

APPLICABLE CODES AND STANDARDS: DEFINITIONS AND CONDITIONS


AS1359, NFPA37, NFPA70, NFPA99, NFPA110, IEC 60034-1, 1
For ambient and altitude capabilities consult your Cat dealer.
ISO 3046, ISO 8528, 2006/95/EC, 2006/42/EC, 2004/108/EC. Air flow restriction (system) is added to existing restriction
Note: Codes may not be available in all model configurations. from factory.
Please consult your local Cat Dealer representative for 2
.Generator temperature rise is based on a 27°C ambient per
availability. NEMA MG1-32.
STANDBY: Output available with varying load for the duration
of the interruption of the normal source power. Average power
output is 70% of the standby power rating. Typical operation
is 200 hours per year, with maximum expected usage of
500 hours per year.
RATINGS: Ratings are based on SAE J1349 standard
conditions. These ratings also apply at ISO 3046
standard conditions.

www.cat.com/electricpower
©2020 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”
the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity
LEHE2690-00 (11/20) used herein, are trademarks of Caterpillar and may not be used without permission.