Rcug-Ahyz1 TC1
Rcug-Ahyz1 TC1
Rcug-Ahyz1 TC1
– SCREW TYPE –
HITACHI
Nominal Capacity Range
R22: 116kW to 1,146kW Technical Catalog I
99,760kcal/h to 985,560kcal/h Design Information
33RT to 326 RT
R407C: 110kW to 1,089kW
94,600kcal/h to 936,540kcal/h Model: R22 R407C
31RT to 310 RT
RCU40AHYZ1 RCUG40AHYZ1
RCU50AHYZ1 RCUG50AHYZ1
RCU60AHYZ1 RCUG60AHYZ1
RCU75AHYZ1 RCUG75AHYZ1
RCU100AHYZ1 RCUG100AHYZ1
RCU120AHYZ1 RCUG120AHYZ1
RCU150AHYZ1 RCUG150AHYZ1
RCU180AHYZ1 RCUG180AHYZ1
RCU200AHYZ1 RCUG200AHYZ1
RCU240AHYZ1 RCUG240AHYZ1
RCU270AHYZ1 RCUG270AHYZ1
RCU300AHYZ1 RCUG300AHYZ1
RCU330AHYZ1 RCUG330AHYZ1
RCU350AHYZ1 RCUG350AHYZ1
RCU360AHYZ1 RCUG360AHYZ1
RCU380AHYZ1 RCUG380AHYZ1
RCU400AHYZ1 RCUG400AHYZ1
New Series! This series of HITACHI air-cooled water chillers up to 400HP has been developed for various
requirements of air-conditioning systems and industrial chilled water systems, where these equipment are operated under high
ambient temperatures of 43 ℃,Therefore, the units can be utilized under a wide temperature range.
These water chillers are equipped with newly model-changed semi-hermetic HITACHI A-type screw compressors,
featuring high reliability, low noise and low vibration, and highly efficient air-cooled condenser, resulting in compact design.
The unit is composed of compressors, air-cooled condensers, shell-tube type water coolers, and other auxiliary and control
devices, compactly packaged in a weather-proof cabinet which is constructed of galvanized steel plates processed with
specially baked resin paint.
FEATURE
In this new century when people pay more attention to the change of the environment,
HITACHI semi-hermetic screw type compressors ,which use the R407C refrigerant directly,
and reduce the refrigerant leak greatly, have been sold 140,000 in the world !
Slide Valve
Suction Inlet
Bearing
●Highly Efficiency Operation
The appropriate combination of the air side heat exchangers with high performance SLIT fins, highly efficient
screw compressors and water side heat exchangers has achieved this high efficiency of operation.
Heat-Exchanger(AHYZ1)
1.Improve the air heat exchanger configuration. 2.Adopt high heat exchange efficiency inner thread tube 3.Improve air velocity
distribution to enhance efficiency .
1
FEATURE
Capacity Control
Load-up signal
Start
Inlet water
Inlet water 2sec. temperature
temperature 60sec.
Outlet water
≈
Outlet water temperature
temperature
≈
Neutral zone
6 standard
(Set temperature:5℃)
4 Stop temperature
Stop standard
Lapsed time
Load-down signal The inlet water temperature
A given load status is is detected at a stop, and it
maintained. is restarted by a raise in
2sec.
60sec. inlet water temperature
2
GENERAL DATA
Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal
Safety Devices ─ Overcurrent Relay for Fan Motor,High Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection
Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for Control Circuit and Pressure Relief Valve
Shipping Weight*3 kg 2,000 2,040 2,080 2,100 3,610 3,680 3,720 5,500 5,535
Depth mm 2,600 2,600 2,600 2,600 4,700 4,700 4,700 6,800 6,800
Shipping
Width mm 2,190 2,190 2,190 2,190 2,190 2,190 2,190 2,190 2,190
Dimension
Height mm 2,510 2,510 2,510 2,510 2,510 2,510 2,510 2,510 2,510
NOTE:
1. The nominal cooling capacities are based on GB/T 4. Water Flow
18430.1-2007(*1) 1) RCU(G)240,300,360,400AHYZ1
Chilled Water Inlet/Outlet Temperature:12/7℃ It is necessary to control the common water flow volume to
Condenser Air Inlet Temperature:35℃(DB) each cooler.
2. Applicable Power Supply 2) RCU(G)270,330,350,380AHYZ1
Main Power Source Control Power Source Because the chilled water flow rate is different between No.1
(AC3φ) (AC1φ) and No.2 units. It is necessary to control the water flow
380V,50HZ 220V,50HZ volume of each unit with adjusting valves (Filed-Supplied).
415V,50HZ 240V,50HZ 5. It is required to connect electrical control wires between No.1
3. The units greater than 240AHYZ1 including 240AHYZ1 and No.2 units for the unit greater than 240AHYZ1including
consist of two modules and are separately shipped. (*3). 240AHYZ1.
The common chilled water piping (Filed-Supplied) 6. ( ) marked with *2 is available by selection switch.
between each water cooler shall be directly connected
at site.
Working Range
Item Standard
Chilled Water Outlet Temperature 5~15℃
Condenser Air Inlet Temperature(DB) 5~43℃
3
GENERAL DATA
General Data(R22 and R407C)
R22 RCU240AHYZ1 RCU270AHYZ1 RCU300AHYZ1 RCU330AHYZ1 RCU350AHYZ1 RCU360AHYZ1 RCU380AHYZ1 RCU400AHYZ1
Model
R407C RCUG240AHYZ1 RCUG270AHYZ1 RCUG300AHYZ1 RCUG330AHYZ1 RCUG350AHYZ1 RCUG360AHYZ1 RCUG380AHYZ1 RCUG400AHYZ1
Net Weight kg 2×3,280 3,320+3,280 2×3,320 4,865+3,320 4,900+3,320 2×4,865 4,900+4,865 2×4,900
Standard — R22
R407C — R407C
Refrigerant
Flow Control — Thermal Expansion Valve
Number of Circuit — 4 5 6
Compressor Model ─ 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z 60ASCC-Z
Quantity ─ 4 5 6
Heat- Fan Power Input kW 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
Exchanger Motor
Quantity ─ 2×8 8+8 2×8 12+8 12+8 2×12 12+12 2×12
Air Discharge m3/min 3,720 3,720 3,720 4,650 4,650 5,580 5,580 5,580
Evaporator ─ Shell and Tube Type
Overcurrent Relay for Compressor , Internal Thermostat for Compressor, Reverse Phase Protection Device for Compressor,Thermal Overcurrent Relay for Fan Motor,High
Safety Devices ─ Pressure Switch, Low Pressure Control, Suction Gas Temperature Control,Freeze Protection Thermistor control,Oil Heater, Discharge Gas Thermistor, Fusible Plug, Fuse for
Control Circuit and Pressure Relief Valve
Main Power
mm 2×233×140
Connection Hole (square orifice)
Circuit mm 6×φ48;2×φ64;2×φ52;4×φ75
Shipping Weight*3 kg 2×3,680 3,720+3,680 2×3,720 5,500+3,720 5,535+3,720 2×5,500 5,535+5,500 2×5,535
NOTE:
1. The nominal cooling capacities are based on GB/T 4. Water Flow
18430.1-2007(*1) 1) RCU(G)240,300,360,400AHYZ1
Chilled Water Inlet/Outlet Temperature:12/7℃ It is necessary to control the common water flow volume to
Condenser Air Inlet Temperature:35℃(DB) each cooler.
2. Applicable Power Supply 2) RCU(G)270,330,350,380AHYZ1
Main Power Source Control Power Source Because the chilled water flow rate is different between No.1
(AC3φ) (AC1φ) and No.2 units. It is necessary to control the water flow
380V,50HZ 220V,50HZ volume of each unit with adjusting valves (Filed-Supplied).
415V,50HZ 240V,50HZ 5. It is required to connect electrical control wires between No.1
3. The units greater than 240AHYZ1 including 240AHYZ1 and No.2 units for the unit greater than 240AHYZ1including
consist of two modules and are separately shipped. (*3). 240AHYZ1.
The common chilled water piping (Filed-Supplied) 6. ( ) marked with *2 is available by selection switch.
between each water cooler shall be directly connected
at site.
Working Range
Item Standard
Chilled Water Outlet Temperature 5~15℃
Condenser Air Inlet Temperature(DB) 5~43℃
4
DIMENSION DATA
Unit Dimensions
Rigging holes(4-φ50)
Mounting Holes(4-φ26)
Earth Connection Terminal Screw Type Compressor
NOTES:
Fan 1.Surpport the water pipes with stay not to give the weight of water pipes directly to the unit.
Wiring Hole
for Power Supply 2.Water connection flanges( 90mm inner diameter )are supplied by factory with the unit.
Air Discharge
Air Side Heat-Exchanger
Rigging Holes(4-φ50)
1.Surpport the water pipes with stay not to give the weight of water pipes directly to the unit .
2.Water connection flanges( 142mm inner diameter)are supplied by factory with the unit.
5
DIMENSION DATA
Unit Dimensions
RCU(G)180AHYZ1and RCU(G)200AHYZ1
Air Discharge
Air Side Heat-Exchanger
Rigging Holes
(4-φ50)
Mounting Holes
Earth Connection Terminal Screw Type Compressor (8-φ26)
Fan
NOTES:
Wiring Hole 1.Surpport the water pipes with stay not to give the
for Power Supply
give the weight of water pipes directly to the unit.
2.Water connection flanges( 142mm inner diameter )
are supplied by factory with the unit.
Air Discharge
Air Side Heat-Exchanger
Minimum) Air Side Heat-Exchanger
Rigging Holes(8-φ50)
Screw Type Compressor Screw Type Compressor Screw Type Compressor Screw Type Compressor Mounting Holes(12-φ26)
Earth Connection Terminal Earth Connection Terminal
6
DIMENSION DATA
Unit Dimensions
Rigging Holes
(8-φ50)
P
Mounting Holes
Earth Connection Terminal Screw Type Compressor Earth Connection Terminal Screw Type Compressor Screw Type Compressor (14-φ26)
(Minimum)
Air Discharge
Air Side Heat-Exchanger Air Side Heat-Exchanger
起吊孔(8-φ50)
安装孔(16-φ26)
Earth Connection Terminal Screw Type Compressor Earth Connection Terminal Screw Type Compressor
No.1 Water Outlet No.1 Water Inlet No.2 Water Outlet No.2 Water Inlet NOTES:
1.This chiller consists of unit No.1 and No.2 and should be
separately shipped.
Fan 2.Support the water pipes with stay not to give
the weight of water pipes directly to the unit.
3.Provide a field-supplied common water piping
Wiring Hole for at the water coolers to connect unit No.1 and No.2.
Power Supply Furthermore,for RCU360,400AHYZ1:as the No.1 unit and No.2 unit
have a same water flow rate, it just needs to control the common water volume
to the chiller; for RCU380AHYZ1:because the chilled water flow rate
between No.1and No.2 unit is different, It is necessary to
Wiring Hole for control the water volume of each unit with adjusting valves.
Power Supply 4.It needs to field-connect the control wiring between the
No.1 unit and No. 2 unit.
7
PREPARATION
Operation Space
h1≤h2
h1≤h2
Refer to C,D
Refer to C,D
E F
30mmm
Refer to C,D
15mm
G
8
PREPARATION
Center of Gravity
Center of Center of
Gravity Operation Gravity Operation
Model Model
Weight(kg) Weight(kg)
X Y X Y
RCU(G)40AHYZ1 1050 970 1870 RCU(G)270AHYZ1-2 2240 870 3420
RCU(G)50AHYZ1 1050 970 1900 RCU(G)300AHYZ1-1 2050 870 3460
RCU(G)60AHYZ1 1050 970 1940 RCU(G)300AHYZ1-2 2240 870 3460
RCU(G)75AHYZ1 1050 970 1960 RCU(G)330AHYZ1-1 3240 857 5075
RCU(G)100AHYZ1 2050 870 3350 RCU(G)330AHYZ1-2 2240 870 3460
RCU(G)120AHYZ1 2050 870 3420 RCU(G)350AHYZ1-1 3240 857 5110
RCU(G)150AHYZ1 2050 870 3460 RCU(G)350AHYZ1-2 2240 870 3460
RCU(G)180AHYZ1 3240 857 5075 RCU(G)360AHYZ1-1 3240 857 5075
RCU(G)200AHYZ1 3240 857 5110 RCU(G)360AHYZ1-2 3440 857 5075
RCU(G)240AHYZ1-1 2050 870 3420 RCU(G)380AHYZ1-1 3240 857 5110
RCU(G)240AHYZ1-2 2240 870 3420 RCU(G)380AHYZ1-2 3440 857 5075
RCU(G)400AHYZ1-1 3240 857 5110
RCU(G)270AHYZ1-1 2050 870 3460
RCU(G)400AHYZ1-2 3440 857 5110
Weight Balance
Weight Destribution (kg)
Model
1 2 3 4
RCU(G)40AHYZ1 380 360 615 515
RCU(G)50AHYZ1 385 365 625 525
RCU(G)60AHYZ1 395 375 635 535
RCU(G)75AHYZ1 400 380 640 540
9
SELECTION DATA
1、RCU(G)40AHYZ1
2、RCU(G)50AHYZ1
3、RCU(G)60AHYZ1
RCU(G)75AHYZ1
Water Cooler Pressure Drop(kPa)
4、RCU(G)100AHYZ1
5、RCU(G)120AHYZ1
RCU(G)150AHYZ1
RCU(G)240AHYZ1-1
RCU(G)240AHYZ1-2
RCU(G)270AHYZ1-1
RCU(G)270AHYZ1-2
RCU(G)300AHYZ1-1
RCU(G)300AHYZ1-2
RCU(G)330AHYZ1-2
RCU(G)350AHYZ1-2
6、RCU(G)180AHYZ1
RCU(G)200AHYZ1
RCU(G)330AHYZ1-1
RCU(G)350AHYZ1-1
RCU(G)360AHYZ1-1
RCU(G)360AHYZ1-2
RCU(G)380AHYZ1-1
RCU(G)380AHYZ1-2
RCU(G)400AHYZ1-1
RCU(G)400AHYZ1-2
3
Chilled Water Flow Rate of Each Water Cooler(m /h)
(Total Flow Rate /Number of Cooler)
NOTE: The flow rate of each model is not different; please refer to the chilled water flow rate on the pages 11 to 16.
10
SELECTION DATA
Cooling Capacities(R22)
Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq
11
SELECTION DATA
Cooling Capacities(R22)
Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq
RCU240AHYZ1 RCU270AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 744.2 64.0 64.0 66.2 66.2 165.2 769.1 68.3 64.0 75.6 66.2 170.6
6 769.6 66.2 66.2 70.9 70.9 166.8 795.4 70.6 66.2 81.0 70.9 172.1
7 794.8 68.3 68.3 75.7 75.7 168.2 821.4 72.9 68.3 86.5 75.7 173.6
25
8 819.7 70.5 70.5 80.7 80.7 169.7 847.3 75.2 70.5 92.2 80.7 175.1
9 844.4 72.6 72.6 85.8 85.8 171.3 872.8 77.5 72.6 98.1 85.8 176.7
10 868.7 74.7 74.7 90.9 90.9 172.8 898.0 79.7 74.7 104.0 90.9 178.4
5 706.7 60.8 60.8 59.5 59.5 186.0 730.3 64.8 60.8 68.0 59.5 191.8
6 731.0 62.9 62.9 63.8 63.8 187.5 755.5 67.1 62.9 72.9 63.8 193.6
7 755.5 65.0 65.0 68.2 68.2 189.1 780.7 69.3 65.0 77.9 68.2 195.1
30
8 779.6 67.0 67.0 72.8 72.8 190.8 805.8 71.5 67.0 83.2 72.8 196.9
9 803.4 69.1 69.1 77.4 77.4 192.4 830.3 73.7 69.1 88.5 77.4 198.5
10 826.9 71.1 71.1 82.2 82.2 193.9 854.6 75.9 71.1 93.9 82.2 200.2
5 668.9 57.5 57.5 53.1 53.1 206.5 691.3 61.4 57.5 60.7 53.1 213.0
6 692.4 59.5 59.5 57.0 57.0 208.3 715.6 63.5 59.5 65.2 57.0 214.8
7 716.0 61.6 61.6 61.1 61.1 210.0 740.0 65.7 61.6 69.8 61.1 216.6
35
8 739.4 63.6 63.6 65.3 65.3 211.7 764.1 67.8 63.6 74.6 65.3 218.4
9 762.4 65.6 65.6 69.5 69.5 213.5 788.0 70.0 65.6 79.5 69.5 220.2
10 785.2 67.5 67.5 73.9 73.9 215.2 811.4 72.0 67.5 84.4 73.9 221.9
5 631.2 54.3 54.3 47.1 47.1 227.2 652.4 57.9 54.3 53.9 47.1 234.4
6 653.9 56.2 56.2 50.7 50.7 229.0 675.8 60.0 56.2 57.9 50.7 236.2
7 676.7 58.2 58.2 54.4 54.4 230.9 699.4 62.1 58.2 62.2 54.4 238.1
40
8 699.3 60.1 60.1 58.2 58.2 232.7 722.6 64.1 60.1 66.5 58.2 239.9
9 721.4 62.0 62.0 62.1 62.1 234.6 745.7 66.2 62.0 71.0 62.1 241.9
10 743.3 63.9 63.9 66.0 66.0 236.5 768.3 68.2 63.9 75.4 66.0 243.8
RCU300AHYZ1 RCU330AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 794.0 68.3 68.3 75.6 75.6 176.0 955.2 96.0 68.3 83.6 75.6 211.9
6 821.2 70.6 70.6 81.0 81.0 177.5 987.8 99.3 70.6 89.2 81.0 213.8
7 848.0 72.9 72.9 86.5 86.5 179.0 1020.1 102.5 72.9 94.9 86.5 215.6
25
8 874.8 75.2 75.2 92.2 92.2 180.5 1052.2 105.7 75.2 100.7 92.2 217.5
9 901.2 77.5 77.5 98.1 98.1 182.1 1083.9 108.9 77.5 106.6 98.1 219.5
10 927.2 79.7 79.7 104.0 104.0 184.0 1115.2 112.0 79.7 112.6 104.0 221.6
5 754.0 64.8 64.8 68.0 68.0 197.7 907.0 91.1 64.8 75.7 68.0 238.3
6 780.0 67.1 67.1 72.9 72.9 199.6 938.2 94.3 67.1 80.8 72.9 240.4
7 806.0 69.3 69.3 77.9 77.9 201.1 969.6 97.4 69.3 86.1 77.9 242.4
30
8 832.0 71.5 71.5 83.2 83.2 203.0 1000.7 100.5 71.5 91.4 83.2 244.6
9 857.2 73.7 73.7 88.5 88.5 204.5 1031.2 103.6 73.7 96.9 88.5 246.5
10 882.4 75.9 75.9 93.9 93.9 206.4 1061.4 106.6 75.9 102.4 93.9 248.7
5 713.6 61.4 61.4 60.7 60.7 219.4 858.5 86.3 61.4 68.1 60.7 264.6
6 738.8 63.5 63.5 65.2 65.2 221.3 888.7 89.3 63.5 72.8 65.2 266.8
7 764.0 65.7 65.7 69.8 69.8 223.2 919.0 92.3 65.7 77.6 69.8 269.1
35
8 788.8 67.8 67.8 74.6 74.6 225.1 949.0 95.4 67.8 82.6 74.6 271.4
9 813.6 70.0 70.0 79.5 79.5 227.0 978.6 98.3 70.0 87.6 79.5 273.6
10 837.6 72.0 72.0 84.4 84.4 228.5 1007.7 101.3 72.0 92.7 84.4 275.7
5 673.6 57.9 57.9 53.9 53.9 241.5 810.2 81.4 57.9 60.9 53.9 291.2
6 697.6 60.0 60.0 57.9 57.9 243.4 839.3 84.3 60.0 65.2 57.9 293.4
7 722.0 62.1 62.1 62.2 62.2 245.3 868.5 87.3 62.1 69.7 62.2 295.8
40
8 746.0 64.1 64.1 66.5 66.5 247.2 897.5 90.2 64.1 74.2 66.5 298.1
9 770.0 66.2 66.2 71.0 71.0 249.1 926.1 93.0 66.2 78.8 71.0 300.5
10 793.2 68.2 68.2 75.4 75.4 251.0 954.1 95.9 68.2 83.4 75.4 302.9
12
SELECTION DATA
Cooling Capacities(R22)
Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq
RCU350AHYZ1 RCU360AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 992.5 102.4 68.3 94.7 75.6 220.0 1116.3 96.0 96.0 83.6 83.6 247.9
6 1026.5 105.9 70.6 101.1 81.0 221.9 1154.4 99.3 99.3 89.2 89.2 250.2
7 1060.0 109.4 72.9 107.5 86.5 223.8 1192.1 102.5 102.5 94.9 94.9 252.2
25
8 1093.5 112.8 75.2 114.1 92.2 225.7 1229.6 105.7 105.7 100.7 100.7 254.6
9 1126.5 116.2 77.5 120.8 98.1 227.6 1266.7 108.9 108.9 106.6 106.6 256.9
10 1159.0 119.6 79.7 127.6 104.0 230.0 1303.1 112.0 112.0 112.6 112.6 259.2
5 942.5 97.2 64.8 85.8 68.0 247.1 1060.0 91.1 91.1 75.7 75.7 279.0
6 975.0 100.6 67.1 91.5 72.9 249.5 1096.5 94.3 94.3 80.8 80.8 281.3
7 1007.5 104.0 69.3 97.5 77.9 251.4 1133.2 97.4 97.4 86.1 86.1 283.6
30
8 1040.0 107.3 71.5 103.6 83.2 253.8 1169.4 100.5 100.5 91.4 91.4 286.2
9 1071.5 110.6 73.7 109.8 88.5 255.7 1205.2 103.6 103.6 96.9 96.9 288.6
10 1103.0 113.8 75.9 116.0 93.9 258.1 1240.3 106.6 106.6 102.4 102.4 290.9
5 892.0 92.0 61.4 77.1 60.7 274.2 1003.4 86.3 86.3 68.1 68.1 309.8
6 923.5 95.3 63.5 82.5 65.2 276.6 1038.5 89.3 89.3 72.8 72.8 312.4
7 955.0 98.5 65.7 88.0 69.8 279.0 1074.0 92.3 92.3 77.6 77.6 315.0
35
8 986.0 101.7 67.8 93.5 74.6 281.4 1109.1 95.4 95.4 82.6 82.6 317.6
9 1017.0 104.9 70.0 99.3 79.5 283.8 1143.6 98.3 98.3 87.6 87.6 320.2
10 1047.0 108.0 72.0 105.0 84.4 285.7 1177.8 101.3 101.3 92.7 92.7 322.8
5 842.0 86.9 57.9 69.0 53.9 301.9 946.7 81.4 81.4 60.9 60.9 340.9
6 872.0 90.0 60.0 73.9 57.9 304.2 980.9 84.3 84.3 65.2 65.2 343.5
7 902.5 93.1 62.1 78.9 62.2 306.6 1015.1 87.3 87.3 69.7 69.7 346.4
40
8 932.5 96.2 64.1 84.0 66.5 309.0 1048.9 90.2 90.2 74.2 74.2 349.0
9 962.5 99.3 66.2 89.3 71.0 311.4 1082.1 93.0 93.0 78.8 78.8 351.9
10 991.5 102.3 68.2 94.5 75.4 313.8 1115.0 95.9 95.9 83.4 83.4 354.8
RCU380AHYZ1 RCU400AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 1153.7 102.4 96.0 94.7 83.6 255.9 1191.0 102.4 102.4 94.7 94.7 264.0
6 1193.1 105.9 99.3 101.1 89.2 258.2 1231.8 105.9 105.9 101.1 101.1 266.2
7 1232.1 109.4 102.5 107.5 94.9 260.4 1272.0 109.4 109.4 107.5 107.5 268.5
25
8 1270.9 112.8 105.7 114.1 100.7 262.7 1312.2 112.8 112.8 114.1 114.1 270.8
9 1309.2 116.2 108.9 120.8 106.6 265.0 1351.8 116.2 116.2 120.8 120.8 273.1
10 1347.0 119.6 112.0 127.6 112.6 267.6 1390.8 119.6 119.6 127.6 127.6 276.0
5 1095.5 97.2 91.1 85.8 75.7 287.7 1131.0 97.2 97.2 85.8 85.8 296.5
6 1133.2 100.6 94.3 91.5 80.8 290.3 1170.0 100.6 100.6 91.5 91.5 299.4
7 1171.1 104.0 97.4 97.5 86.1 292.6 1209.0 104.0 104.0 97.5 97.5 301.7
30
8 1208.7 107.3 100.5 103.6 91.4 295.4 1248.0 107.3 107.3 103.6 103.6 304.5
9 1245.5 110.6 103.6 109.8 96.9 297.7 1285.8 110.6 110.6 109.8 109.8 306.8
10 1282.0 113.8 106.6 116.0 102.4 300.3 1323.6 113.8 113.8 116.0 116.0 309.7
5 1036.9 92.0 86.3 77.1 68.1 319.4 1070.4 92.0 92.0 77.1 77.1 329.1
6 1073.4 95.3 89.3 82.5 72.8 322.2 1108.2 95.3 95.3 82.5 82.5 331.9
7 1110.0 98.5 92.3 88.0 77.6 324.9 1146.0 98.5 98.5 88.0 88.0 334.8
35
8 1146.2 101.7 95.4 93.5 82.6 327.6 1183.2 101.7 101.7 93.5 93.5 337.7
9 1182.0 104.9 98.3 99.3 87.6 330.4 1220.4 104.9 104.9 99.3 99.3 340.5
10 1217.1 108.0 101.3 105.0 92.7 332.8 1256.4 108.0 108.0 105.0 105.0 342.8
5 978.6 86.9 81.4 69.0 60.9 351.5 1010.4 86.9 86.9 69.0 69.0 362.2
6 1013.7 90.0 84.3 73.9 65.2 354.3 1046.4 90.0 90.0 73.9 73.9 365.1
7 1049.0 93.1 87.3 78.9 69.7 357.2 1083.0 93.1 93.1 78.9 78.9 367.9
40
8 1084.0 96.2 90.2 84.0 74.2 359.9 1119.0 96.2 96.2 84.0 84.0 370.8
9 1118.6 99.3 93.0 89.3 78.8 362.8 1155.0 99.3 99.3 89.3 89.3 373.7
10 1152.4 102.3 95.9 94.5 83.4 365.7 1189.8 102.3 102.3 94.5 94.5 376.5
13
SELECTION DATA
14
SELECTION DATA
RCUG300AHYZ1 RCUG330AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 754.3 64.9 64.9 68.0 68.0 188.3 907.2 91.2 64.9 75.7 68.0 226.8
6 780.1 67.1 67.1 72.9 72.9 189.9 938.2 94.3 67.1 80.8 72.9 228.8
7 805.6 69.3 69.3 77.9 77.9 191.5 968.9 97.4 69.3 85.9 77.9 230.7
25
8 831.1 71.5 71.5 83.0 83.0 193.2 999.4 100.4 71.5 91.2 83.0 232.8
9 856.1 73.6 73.6 88.2 88.2 194.8 1029.6 103.4 73.6 96.6 88.2 234.8
10 880.8 75.7 75.7 93.6 93.6 196.8 1059.2 106.4 75.7 102.0 93.6 237.1
5 716.3 61.6 61.6 61.2 61.2 211.5 861.5 86.6 61.6 68.6 61.2 255.0
6 741.0 63.7 63.7 65.6 65.6 213.6 891.2 89.5 63.7 73.2 65.6 257.3
7 765.7 65.8 65.8 70.1 70.1 215.2 921.0 92.5 65.8 78.0 70.1 259.3
30
8 790.4 68.0 68.0 74.9 74.9 217.2 950.5 95.5 68.0 82.8 74.9 261.7
9 814.3 70.0 70.0 79.6 79.6 218.9 979.5 98.4 70.0 87.7 79.6 263.8
10 838.3 72.1 72.1 84.5 84.5 220.9 1008.1 101.3 72.1 92.7 84.5 266.1
5 677.9 58.3 58.3 54.6 54.6 234.7 815.4 81.9 58.3 61.7 54.6 283.1
6 701.9 60.3 60.3 58.7 58.7 236.8 844.1 84.8 60.3 65.9 58.7 285.5
7 725.8 62.4 62.4 62.8 62.8 238.8 872.9 87.7 62.4 70.3 62.8 287.9
35
8 749.4 64.4 64.4 67.1 67.1 240.9 901.4 90.6 64.4 74.8 67.1 290.4
9 772.9 66.5 66.5 71.5 71.5 242.9 929.5 93.4 66.5 79.3 71.5 292.8
10 795.7 68.4 68.4 75.9 75.9 244.5 957.2 96.2 68.4 84.0 75.9 295.0
5 639.9 55.0 55.0 48.5 48.5 258.4 769.5 77.3 55.0 55.2 48.5 311.6
6 662.7 57.0 57.0 52.1 52.1 260.4 797.2 80.1 57.0 59.1 52.1 314.0
7 685.9 59.0 59.0 55.9 55.9 262.5 825.0 82.9 59.0 63.1 55.9 316.5
40
8 708.7 60.9 60.9 59.8 59.8 264.5 852.5 85.7 60.9 67.2 59.8 319.0
9 731.5 62.9 62.9 63.9 63.9 266.5 879.6 88.4 62.9 71.3 63.9 321.5
10 753.5 64.8 64.8 67.9 67.9 268.6 906.2 91.1 64.8 75.6 67.9 324.1
15
SELECTION DATA
Cooling Capacities (R407C)
Conversion Multiplier:1kW=860kcal/h
=3412Btu/h
-50Hz- 1kPa=0.102mAq
RCUG350AHYZ1 RCUG360AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 942.9 97.3 64.9 85.8 68.0 235.4 1060.2 91.2 91.2 75.7 75.7 265.2
6 975.2 100.6 67.1 91.6 72.9 237.4 1096.3 94.3 94.3 80.8 80.8 267.7
7 1007.0 103.9 69.3 97.4 77.9 239.4 1132.2 97.4 97.4 85.9 85.9 269.9
25
8 1038.8 107.2 71.5 103.4 83.0 241.5 1167.7 100.4 100.4 91.2 91.2 272.4
9 1070.2 110.4 73.6 109.5 88.2 243.5 1203.0 103.4 103.4 96.6 96.6 274.9
10 1101.1 113.6 75.7 115.6 93.6 246.1 1237.6 106.4 106.4 102.0 102.0 277.4
5 895.4 92.4 61.6 77.7 61.2 264.4 1006.7 86.6 86.6 68.6 68.6 298.5
6 926.3 95.6 63.7 82.9 65.6 266.9 1041.3 89.5 89.5 73.2 73.2 301.0
7 957.1 98.8 65.8 88.3 70.1 269.0 1076.3 92.5 92.5 78.0 78.0 303.5
30
8 988.0 101.9 68.0 93.9 74.9 271.5 1110.6 95.5 95.5 82.8 82.8 306.3
9 1017.9 105.0 70.0 99.4 79.6 273.6 1144.6 98.4 98.4 87.7 87.7 308.8
10 1047.9 108.1 72.1 105.1 84.5 276.1 1177.9 101.3 101.3 92.7 92.7 311.2
5 847.4 87.4 58.3 69.9 54.6 293.4 952.9 81.9 81.9 61.7 61.7 331.5
6 877.3 90.5 60.3 74.7 58.7 296.0 986.3 84.8 84.8 65.9 65.9 334.3
7 907.3 93.6 62.4 79.7 62.8 298.5 1020.0 87.7 87.7 70.3 70.3 337.1
35
8 936.7 96.7 64.4 84.7 67.1 301.1 1053.4 90.6 90.6 74.8 74.8 339.8
9 966.2 99.7 66.5 89.9 71.5 303.6 1086.1 93.4 93.4 79.3 79.3 342.6
10 994.7 102.6 68.4 95.1 75.9 305.7 1118.6 96.2 96.2 84.0 84.0 345.4
5 799.9 82.5 55.0 62.6 48.5 323.0 899.1 77.3 77.3 55.2 55.2 364.7
6 828.4 85.5 57.0 66.9 52.1 325.5 931.6 80.1 80.1 59.1 59.1 367.5
7 857.4 88.5 59.0 71.5 55.9 328.1 964.1 82.9 82.9 63.1 63.1 370.6
40
8 885.9 91.4 60.9 76.1 59.8 330.6 996.2 85.7 85.7 67.2 67.2 373.4
9 914.4 94.3 62.9 80.9 63.9 333.2 1027.7 88.4 88.4 71.3 71.3 376.5
10 941.9 97.2 64.8 85.7 67.9 335.7 1058.9 91.1 91.1 75.6 75.6 379.6
RCUG380AHYZ1 RCUG400AHYZ1
ABT CLOT
CCAP CFR1 CFR2 CPD1 CPD2 IPT CCAP CFR1 CFR2 CPD1 CPD2 IPT
5 1095.8 97.3 91.2 85.8 75.7 273.8 1131.5 97.3 97.3 85.8 85.8 282.4
6 1133.3 100.6 94.3 91.6 80.8 276.3 1170.2 100.6 100.6 91.6 91.6 284.9
7 1170.3 103.9 97.4 97.4 85.9 278.6 1208.4 103.9 103.9 97.4 97.4 287.3
25
8 1207.2 107.2 100.4 103.4 91.2 281.1 1246.6 107.2 107.2 103.4 103.4 289.8
9 1243.6 110.4 103.4 109.5 96.6 283.5 1284.2 110.4 110.4 109.5 109.5 292.2
10 1279.4 113.6 106.4 115.6 102.0 286.3 1321.3 113.6 113.6 115.6 115.6 295.3
5 1040.6 92.4 86.6 77.7 68.6 307.9 1074.5 92.4 92.4 77.7 77.7 317.3
6 1076.4 95.6 89.5 82.9 73.2 310.7 1111.5 95.6 95.6 82.9 82.9 320.3
7 1112.4 98.8 92.5 88.3 78.0 313.1 1148.6 98.8 98.8 88.3 88.3 322.8
30
8 1148.1 101.9 95.5 93.9 82.8 316.1 1185.6 101.9 101.9 93.9 93.9 325.8
9 1183.0 105.0 98.4 99.4 87.7 318.5 1221.5 105.0 105.0 99.4 99.4 328.3
10 1217.7 108.1 101.3 105.1 92.7 321.3 1257.4 108.1 108.1 105.1 105.1 331.3
5 984.9 87.4 81.9 69.9 61.7 341.8 1016.9 87.4 87.4 69.9 69.9 352.1
6 1019.5 90.5 84.8 74.7 65.9 344.7 1052.8 90.5 90.5 74.7 74.7 355.2
7 1054.4 93.6 87.7 79.7 70.3 347.6 1088.7 93.6 93.6 79.7 79.7 358.2
35
8 1088.7 96.7 90.6 84.7 74.8 350.6 1124.0 96.7 96.7 84.7 84.7 361.3
9 1122.8 99.7 93.4 89.9 79.3 353.5 1159.4 99.7 99.7 89.9 89.9 364.3
10 1156.1 102.6 96.2 95.1 84.0 356.1 1193.6 102.6 102.6 95.1 95.1 366.8
5 929.5 82.5 77.3 62.6 55.2 376.2 959.9 82.5 82.5 62.6 62.6 387.6
6 962.8 85.5 80.1 66.9 59.1 379.1 994.1 85.5 85.5 66.9 66.9 390.6
7 996.5 88.5 82.9 71.5 63.1 382.2 1028.9 88.5 88.5 71.5 71.5 393.7
40
8 1029.6 91.4 85.7 76.1 67.2 385.1 1063.1 91.4 91.4 76.1 76.1 396.7
9 1062.5 94.3 88.4 80.9 71.3 388.2 1097.3 94.3 94.3 80.9 80.9 399.8
10 1094.6 97.2 91.1 85.7 75.6 391.3 1130.3 97.2 97.2 85.7 85.7 402.9
16
SELECTION DATA
Electric Data (Voltage:380V)
Application Compressor(Three Phases) Motor for Condenser
Unit Main Power Maximum Unit
Model Voltage(V) Fan
STC(A) RNC(A) IPT (kW) Current(A)
Voltage Hz Max. Min. RNC(A) IPT (kW)
RCU40AHYZ1 114 58 34.6 4×2.7 4×1.1 96
RCU50AHYZ1 148 75 42.3 4×2.7 4×1.1 129
RCU60AHYZ1 178 95 52.5 4×2.7 4×1.1 162
RCU75AHYZ1 178 100 55.8 4×2.7 4×1.1 173
RCU100AHYZ1 148 2×75 2×42.3 8×2.7 8×1.1 258
RCU120AHYZ1 178 2×95 2×52.5 8×2.7 8×1.1 324
RCU150AHYZ1 178 2×100 2×55.8 8×2.7 8×1.1 346
RCU180AHYZ1 178 3×95 3×52.5 12×2.7 12×1.1 486
RCU200AHYZ1 178 3×100 3×55.8 12×2.7 12×1.1 519
RCU240AHYZ1 178 4×95 4×52.5 16×2.7 16×1.1 648
RCU270AHYZ1 178 2×100+2×95 2×55.8+2×52.5 16×2.7 16×1.1 670
RCU300AHYZ1 178 4×100 4×55.8 16×2.7 16×1.1 692
RCU330AHYZ1 178 3×95+2×100 3×52.5+2×55.8 20×2.7 20×1.1 832
RCU350AHYZ1 178 5×100 5×55.8 20×2.7 20×1.1 865
RCU360AHYZ1 178 6×95 6×52.5 24×2.7 24×1.1 972
RCU380AHYZ1 178 3×100+3×95 3×55.8+3×52.5 24×2.7 24×1.1 1005
RCU400AHYZ1 178 6×100 6×55.8 24×2.7 24×1.1 1038
380 50 418 342
RCUG40AHYZ1 114 64 36.6 4×2.7 4×1.1 114
RCUG50AHYZ1 148 81 45.3 4×2.7 4×1.1 138
RCUG60AHYZ1 178 102 56.2 4×2.7 4×1.1 171
RCUG75AHYZ1 178 107 59.7 4×2.7 4×1.1 181
RCUG100AHYZ1 148 2×81 2×45.3 8×2.7 8×1.1 276
RCUG120AHYZ1 178 2×102 2×56.2 8×2.7 8×1.1 342
RCUG150AHYZ1 178 2×107 2×59.7 8×2.7 8×1.1 362
RCUG180AHYZ1 178 3×102 3×56.2 12×2.7 12×1.1 513
RCUG200AHYZ1 178 3×107 3×59.7 12×2.7 12×1.1 543
RCUG240AHYZ1 178 4×102 4×56.2 16×2.7 16×1.1 684
RCUG270AHYZ1 178 2×107+2×102 2×59.7+2×56.2 16×2.7 16×1.1 704
RCUG300AHYZ1 178 4×107 4×59.7 16×2.7 16×1.1 724
RCUG330AHYZ1 178 3×102+2×107 3×56.2+2×59.7 20×2.7 20×1.1 875
RCUG350AHYZ1 178 5×107 5×59.7 20×2.7 20×1.1 905
RCUG360AHYZ1 178 6×102 6×56.2 24×2.7 24×1.1 1026
RCUG380AHYZ1 178 3×107+3×102 3×59.7+3×56.2 24×2.7 24×1.1 1056
RCUG400AHYZ1 178 6×107 6×59.7 24×2.7 24×1.1 1086
1. These data are based on the same conditions as those for the cooling capacity; please refer to the notes for the Unit
General Data.
2. The starting current is indicated for each compressor.
3. The “Maximum Unit Current” is the total running current of the unit under the following conditions, which consume the
maximum current within the unit working range.
Supplied Voltage: Rated Voltage×0.9
Condenser Air Inlet Temperature: 43 ℃
Chilled Water Outlet Temperature: 15℃
Capacity Control: 100%
Therefore, the size of wiring and fuses must be determined according to applicable national and local codes.
4. In addition to the conditions mentioned in the item 3, the compressor currents can be estimated as shown below.
One-Compressor
Maximum
Instantaneous STC
Current
5. The unit power input can be estimated from that of the compressor in the Cooling Capacity Table and that of the condenser fan
motor above.
17
SELECTION DATA
One-Compressor
Maximum
Instantaneous STC
Current
5. The unit power input can be estimated from that of the compressor in the Cooling Capacity Table and that of the condenser fan
motor above.
18
SOUND DATA
Sound Data
Unit Power Frequency :50Hz
Model Frequency Band(Hz)
45~90 90~180 180~355 355~710 710~1400 1400~2800 2800~5600 5600~11200 Overall
RCU40AHYZ1
49.6 54.4 62.4 65.2 66.5 60.9 44.3 38.9 69.0
RCUG40AHYZ1
RCU50AHYZ1
49.9 54.8 63.0 65.8 67.0 61.2 44.7 39.1 69.5
RCUG50AHYZ1
RCU60AHYZ1
51.1 55.2 63.4 66.4 67.2 61.5 44.9 39.3 69.8
RCUG60AHYZ1
RCU75AHYZ1
51.5 55.8 63.8 66.7 67.4 61.8 45.3 39.8 70.1
RCUG75AHYZ1
RCU100AHYZ1
52.4 56.5 64.7 66.3 67.4 66.5 46.2 41.5 71.4
RCUG100AHYZ1
RCU120AHYZ1
52.8 57.2 65.4 66.5 67.8 66.9 46.7 42.2 71.8
RCUG120AHYZ1
RCU150AHYZ1
52.8 57.3 65.5 66.8 68.1 66.9 46.8 42.3 72.0
RCUG150AHYZ1
RCU180AHYZ1
53.1 57.5 66.4 67.3 68.7 67.2 47.2 42.6 72.5
RCUG180AHYZ1
RCU200AHYZ1
53.1 57.7 66.7 67.6 68.8 67.5 47.2 42.6 72.7
RCUG200AHYZ1
RCU240AHYZ1
53.3 57.9 66.8 68.1 69.3 67.8 47.3 43.1 73.1
RCUG240AHYZ1
RCU270AHYZ1
53.3 57.9 66.8 68.3 69.4 67.9 47.3 43.1 73.2
RCUG270AHYZ1
RCU300AHYZ1
53.3 57.9 66.8 68.4 69.5 67.9 47.3 43.1 73.3
RCUG300AHYZ1
RCU330AHYZ1
53.5 58.1 67.3 68.8 70.1 68.2 47.6 43.4 73.7
RCUG330AHYZ1
RCU350AHYZ1
53.5 58.1 67.3 69.1 70.3 68.4 47.6 43.4 73.9
RCUG350AHYZ1
RCU360AHYZ1
54.7 58.6 67.9 69.5 70.9 69.2 49.4 44.5 74.6
RCUG360AHYZ1
RCU380AHYZ1
54.7 58.6 67.9 69.7 71.1 69.4 49.4 44.5 74.8
RCUG380AHYZ1
RCU400AHYZ1
55.2 58.5 68.1 69.9 71.4 69.7 49.6 44.9 75.0
RCUG400AHYZ1
19
WOKING RANGE
Working Range
Power Supply:
Working Voltage :90%-100% Rating Voltage
Unbalanced Voltage :Within ±3% Deviation from Each Voltage at Compressor Terminals
Start Voltage:Higher than 85% of the Rated Voltage
Maximum Water Flow Rate and Minimum Water Flow Rate (m3/h)
Max.Flow Rate Min.Flow Rate Max.Flow Rate Min.Flow Rate
Model Model
(No.1) (No.1) (No.1/No.2) (No.1/No.2)
RCU40AHYZ1, RCUG40AHYZ1 41.0 12.8 RCU200AHYZ1, RCUG200AHYZ1 159.4 57.1
RCU50AHYZ1, RCUG50AHYZ1 50.5 15.7 RCU240AHYZ1, RCUG240AHYZ1 98.3/98.3 35.2/35.2
RCU60AHYZ1, RCUG60AHYZ1 63.3 19.7 RCU270AHYZ1, RCUG270AHYZ1 135/98.3 42/35.2
RCU75AHYZ1, RCUG75AHYZ1 67.5 21.0 RCU300AHYZ1, RCUG300AHYZ1 135/135 42/42
RCU100AHYZ1, RCUG100AHYZ1 76.4 28.6 RCU330AHYZ1, RCUG330AHYZ1 152.2/135 53.4/42
RCU120AHYZ1, RCUG120AHYZ1 98.3 35.2 RCU350AHYZ1, RCUG350AHYZ1 159.4/135 57.1/42
RCU150AHYZ1, RCUG150AHYZ1 135.0 42.0 RCU360AHYZ1, RCUG360AHYZ1 152.2/152.2 53.4/53.4
RCU380AHYZ1, RCUG380AHYZ1 159.4/152.2 57.1/53.4
RCU180AHYZ1, RCUG180AHYZ1 152.2 53.4
RCU400AHYZ1, RCUG400AHYZ1 159.4/159.4 57.1/57.1
3
Internal Water Volume in Water Cooler (m )
Model Volume(No.1) Model Volume(No.1/No.2)
RCU40AHYZ1, RCUG40AHYZ1 0.08 RCU200AHYZ1, RCUG200AHYZ1 0.21
RCU50AHYZ1, RCUG50AHYZ1 0.07 RCU240AHYZ1, RCUG240AHYZ1 0.14/0.14
RCU60AHYZ1, RCUG60AHYZ1 0.07 RCU270AHYZ1, RCUG270AHYZ1 0.14/0.14
RCU75AHYZ1, RCUG75AHYZ1 0.07 RCU300AHYZ1, RCUG300AHYZ1 0.14/0.14
RCU100AHYZ1, RCUG100AHYZ1 0.14 RCU330AHYZ1, RCUG330AHYZ1 0.21/0.14
RCU120AHYZ1, RCUG120AHYZ1 0.14 RCU350AHYZ1, RCUG350AHYZ1 0.21/0.14
RCU150AHYZ1, RCUG150AHYZ1 0.14 RCU360AHYZ1, RCUG360AHYZ1 0.21/0.21
RCU380AHYZ1, RCUG380AHYZ1 0.21/0.21
RCU180AHYZ1, RCUG180AHYZ1 0.21
RCU400AHYZ1, RCUG400AHYZ1 0.21/0.21
Volume
0.42 0.51 0.64 0.68 1.02 1.28 1.37 1.92 2.05
(m3)
RCU240AHYZ1 RCU270AHYZ1 RCU300AHYZ1 RCU330AHYZ1 RCU350AHYZ1 RCU360AHYZ1 RCU380AHYZ1 RCU400AHYZ1
Model
RCUG240AHYZ1 RCUG270AHYZ1 RCUG300AHYZ1 RCUG330AHYZ1 RCUG350AHYZ1 RCUG360AHYZ1 RCUG380AHYZ1 RCUG400AHYZ1
Volume
2.57 2.65 2.74 3.29 3.42 3.85 3.98 4.11
(m3)
Note: Minimum internal system water volume in the above table is setting according to the standard neutral zone temperature.
In case of changing the setting, minimum internal system water volume shall be increased as follows.
2℃(Standard) 100%
1.5℃ 130%
1℃ 200%
Temperature Range
The temperature range is given in the following table.
Item Standard
Chilled Water Outlet Temperature 5~15℃
Condenser Air Inlet Temperature(DB) 5~43℃
20
COMPONENT DATA
Maximum Operation Pressure MPa 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
Number of Condenser/unit(s) — 4 4 4 4 8 8 8 12
Type — Direct-Drive Propeller Fan
21
COMPONENT DATA
Water Cooler
Refrigerant Outer Diameter 420 420 420 420 420 420 420 500
Side
Length 101 101 101 101 101 101 101 101
Thickness 10 10 10 10 10 10 10 12
Material Copper
Tube Outer Diameter 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7
Quantity 220 272 310 310 272 310 310 437
Number of Pass 4 4 4 4 2 2 2 2
Maximum Refrigerant R22 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
Pemissable Side R407C 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
Pressure Water Side 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05
Insulation Polyethylene(25mm)
Insulation Polyethylene(25mm)
Note: the data above is indicated for each water cooler, as these units greater than 240AHYZ1 including
240AHYZ1 consist of two water coolers for two modules, in the case the data for the two water coolers are different,
it is showed as no.1water cooler data + no.2 water cooler data.
22
CONTROL SYSTEM
Refrigerant System
In addition to the basic air-cooled water chiller components (compressor, condenser, thermal expansion
valves and water cooler), the following components are equipped in each refrigerant cycle:
Stop Valve for Compressor Discharge Line and Liquid Line:
These stop valves are equipped at the liquid line, and facilitate easy compressor service without appreciable
leakage of refrigerant.
Capacity Control
All models are equipped with an unloading system for each compressor, in order to adjust the cooling
capacity and provide precise temperature control for the chilled water, coupled with electric thermostat.
Control Panel
ON switch, OFF switch, Power Supply Lamp, Operation Lamp, Alarm Lamp, Operation/Alarm Indicator for
each refrigerant cycle and check switch are mounted in the Control Panel. The Control Panel is located at a
position where easy access is available. Operation/Alarm indicator can display individual alarm codes such
as High-Cut, Low-Cut etc. This function is very useful for detecting what alarm has occurred. Check
switches are for checking chilled water temperature and alarm occurrence data. Chilled water temperature
setting switches, ON/OFF Differential Setting Switches, Remote-Local Switch and so on are located at the
rear side of Control Panel, in order not to access during operation.
23
CONTROL SYSTEM
Refrigerant Charge
R22
Model RCU40A RCU50A RCU60AHYZ RCU75AH RCU100A RCU120AHY RCU150A RCU180AHY
HYZ1 HYZ1 1 YZ1 HYZ1 Z1 HYZ1 Z1
Charge(kg) 38 44 48 50 2×42 2×43 2×47 3×43
Model RCU200 RCU240 RCU270AHY RCU300A RCU330A RCU350AHY RCU360A RCU380AHY RCU400
AHYZ1 AHYZ1 Z1 HYZ1 HYZ1 Z1 HYZ1 Z1 AHYZ1
Charge(kg) 3×48 4×43 2×47+ 2×43 4×47 3×43+2x47 3×48+2×47 6×43 3×48+3×43 6×48
R407C
Model RCUG40 RCUG50 RCUG60A RCUG75A RCUG100 RCUG120A RCUG150A RCUG180A
AHYZ1 AHYZ1 HYZ1 HYZ1 AHYZ1 HYZ1 HYZ1 HYZ1
Charge(kg) 38 48 2×35 2×38 2×40 3×44
Model RCUG200 RCUG240 RCUG270 RCUG300 RCUG330 RCUG350A RCUG360A RCUG380A RCUG400
AHYZ1 AHYZ1 AHYZ1 AHYZ1 AHYZ1 HYZ1 HYZ1 HYZ1 AHYZ1
Charge(kg) 3×46 4×38 2×40+ 4×40 3×44+2×40 3×46+2×40 6×44 3×46+3×44 6×46
2×38
Note: for the details of the blank places, please contact HITACHI or Hitachi’s distributors.
The safety and protective devices are equipped in the unit to ensure dependable and long life operation.
Their functions should be carefully noted, and field adjustment is not recommended, if the setting is
maintained at the point listed in the table.
Compressor Protection
1、The high pressure switch and the low pressure control protect against excessive discharge pressure and
exceedingly low suction pressure. The switch and control cut out compressor operation when the
discharge pressure exceeds the setting or when the suction pressure decrease below the setting.
2、Overcurrent relays equipped in the magnetic switch box cut out each compressor operation when the
current to the compressor exceeds the setting.
3、The internal thermostat embedded in the compressor motor winding cuts out each operations, when the
temperature of the motor winding exceeds the setting.
4、An oil heater in the compressor prevents from oil foaming during cold starting. Energize this heater to
warm the oil, while the compressor is stopped.
The thermal overcurrent relays for the condenser fan motors cut out fan operation and compressor operation,
when the current to the fan motor exceeds the setting.
Refrigerant Cycle
1、The fusible plug is equipped on the liquid line. When refrigerant temperature exceeds the melting point,
and the plug melts and purges the refrigerant gas, in order to avoid explosion of the condenser.
2、The freeze protection control, for which the sensor is located in the water outlet near the water cooler, cuts
out the compressor operation, when the water outlet temperature decreases below the setting.
24
CONTROL SYSTEM
Note: The data marked with *1 is indicated for each compressor, as in a module the same compressors are used,
for these chillers greater than 240AHYZ1 including 240AHYZ1 which consist of two modules, when the data for the
compressor in the two modules are different, it is showed as data for one of the compressor in the no.1 module /
data for one of the compressor in the no.2 module.
25
CONTROL SYSTEM
Note: The data marked with *1 is indicated for each compressor, as in a module the same compressors are used,
for these chillers greater than 240AHYZ1 including 240AHYZ1 which consist of two modules, when the data for the
compressor in the two modules are different, it is showed as data for one of the compressor in the no.1 module /
data for one of the compressor in the no.2 module.
26
INSTALLATION DATA
Drain Ditch
6-Vibration Proof Rubber Mat [Tubing Side]
Foundation Bolt
(4-M20×300)
☆Foundation Bolt
☆Nut
3
☆Washer
☆Bushing
[Compressor Side]
☆:Supplied by Factory
Steel Plate(1mm): Field Supply
Foundation Bolt
(6-M20×300)
☆Foundation Bolt
☆Nut
☆Washer
☆Bushing
☆:Supplied by Factory
Steel Plate(1mm) : Field Supply
27
INSTALLATION DATA
14-Vibration
Drain Ditch Proof Rubber Mat [Tubing Side]
Foundation Bolt
☆Foundation Bolt
☆Nut
☆Washer
☆Bushing
☆Vibration Proof Rubber Mat
Steel Plate(1mm)
☆:Supplied by Factory
☆Foundation Bolt
☆Nut
☆Washer
☆Bushing
☆:Supplied by Factory
Steel Plate(1mm) : Field Supply
28
INSTALLATION DATA
Recommended Concrete Curbs
RCU(G)330AHYZ1 and RCU(G)350AHYZ1
14-Vibration Proof 10-Vibration Proof
Drain Ditch
Rubber Mat [Tubing Side] Rubber Mat [Tubing Side]
☆Foundation Bolt
☆Nut
☆Washer
☆Bushing
☆Vibration Proof Rubber Mat
Steel Plate(1mm)
☆:Supplied by Factory
Steel Plate(1mm): Field Supply
☆Foundation Bolt
☆Nut
☆Washer
☆Bushing
☆:Supplied by Factory
Steel Plate(1mm) : Field Supply
29
CONTROL SYSTEM
Electrical Wiring Diagram
MODELS: RCU(G)40、50、60、75AHYZ1
30
CONTROL SYSTEM
1,2,4
31
CONTROL SYSTEM
32
CONTROL SYSTEM
1,2,4
33
CONTROL SYSTEM
34
CONTROL SYSTEM
35
SPECIFICATIONS
Standard Specifications
Unit − The unit shall be an air-cooled screw type Compressor − The compressor shall be a
water chiller with R22 or R407C refrigerant, and semi-hermetic compressor from the same
shall be factory-completed with screw-type manufacturer. The compressor shall be
compressors, refrigeration cycle(s), air-cooled serviceable type. The compressor protection
condensers, shell-and-tube water coolers, system shall include an overcurrent relay, a
condenser fan motors, a star-delta starter, protective pressure switch, a timer relays and an internal
and safety devices, thermal expansion valves and thermostat embedded in the motor winding.
compressor discharge stop valves, and shall be
factory-assembled, piped, internal wired and Water-Cooler-the water cooler shall be the dry
charged with R22 or R407C refrigerant. The unit expansion type with a horizontal welded steel
shall be completely weather-proofed for outdoor construction shell, containing inside tubes. The
installation. The unit shall comply with Chinese refrigerant side of the water cooler shall be cleaned,
Industrial Standards and other Chinese Industrial dehydrated and tested for leakage at the maximum
Standardization statutes, including safety codes. permissible working pressure of _ MPa.The water
side of the water cooler shall be cleaned and
Capacity − The cooling capacity of the unit shall performed water pressure test at_ MPa.
be kW or greater under the following
conditions: Air-Side Heat Exchanger Fan and Fan Motor −
m3/h chilled water flow rate, The fan shall be the propeller type directly driven by
℃chilled water inlet temperature, a kW motor. The motor shall be thermally
℃chilled water outlet temperature, protected from overloaded conditions with a thermal
m2.℃/W fouling factor for the water-side overcurrent relay and shall be permanently
heat exchanger or greater. lubricated, The winding and bearing of the
The water-side heat exchanger pressure decrease condenser fan motor shall be weather-proof
shall not exceed kPa. construction.
The compressor power input shall not exceed
kW under the prescribed conditions. Condenser-The condenser shall be the multi-pass,
cross-finned tube type, equipped with aluminum slit
Power Supply − The unit shall operate on V, fins, mechanically bonded to seamless, oxygen-free
___Hz, three-phase current, and shall be capable to copper tubes. The condenser shall be cleaned,
operate within maximum V and minimum dehydrated and tested for leakage at the maximum
V. permissible working pressure of MPa.
Dimensions and Weight − The height of the unit Accessories-Standard accessories shall include
shall be mm, the width shall be mm, and vibration-proof mats, foundation bolts
the depth shall be mm. The weight of the
unit shall not exceed kg.
36
Hitachi Appliances , Inc.
Distributed By:
Air Conditioning Division
URL: http://www.hitachiacs.co.jp
Specifications in this catalogue are subject to change without notice in order that HITACHI may bring the latest innovations to
their customers.
36