En INT-AO
En INT-AO
En INT-AO
INT-AO
8 channels - Analog Output 4-20mA
Description :
The control signals are connected to the DCS or the PLC either by
a SUBD 25 pins male connector or by an HE10-16 pins male
connector.
Product options :
Option SUBD : INT-AO-SUBD, Communication with the PLC or the
DCS via a SUBD connector
Option HE10 : INT-AO-HE10, Communication with the PLC or the
DCS via an HE10 connector
Option ST : INT-AO-SUBD (or HE10)-ST, Screw terminals for the
process signals connection
Option CCT : INT-AO-SUBD-CCT, Cage clamp terminals for the
process signals connection (only with option SUBD)
Option VSH : Conformal coating (Tropicalization)
For HE10 : The lower terminal row is unused
Technical specifications :
Dimensions : Signal wiring conductor section :
Length : 77mm INT-AO-HE10 : Outputs
Width : 55 mm ST: 26 to 16AWG (0.14 to 1.5mm²)
Height : 55mm INT-AO-SUBD : Outputs
Weight : ST: 26 to 14AWG (0.14 to 1.5mm²)
90g (HE10) and 110 g (SUBD) CCT: 24 to 12AWG (0.2 to 2.5mm²)
Temperature range : Withstanding voltage rating :
Operating: -10°C to 60°C 250Vac between non connected
Storage: -20°C to 60°C signal
Humidity : Input specification :
Up to 90% (no condensation) Max current per channel 1A
Mounting : Connection to ground :
Asymmetric or symmetric DIN rail 1 x M3 screw
Connection to the DCS or PLC :
OPTION SUBD :
1 x SUBD 25 pin male connector with UNC 4-40 female lock.
OPTION HE10 :
1 x HE10-10 pin male connectors with locks for female connector, central
polarization and strain relief.