Comparing Effects of TCR and TSC On MHO Distance Protection Setting in 400 KV Algerian Transmission Line
Comparing Effects of TCR and TSC On MHO Distance Protection Setting in 400 KV Algerian Transmission Line
Comparing Effects of TCR and TSC On MHO Distance Protection Setting in 400 KV Algerian Transmission Line
net/publication/235917734
Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400
kV Algerian Transmission Line
CITATIONS READS
2 570
2 authors, including:
Mohamed Zellagui
Université Batna 2
129 PUBLICATIONS 826 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Impact des D-FACTS sur les Performances des Systèmes de Protection dans les Réseaux Électriques MT View project
All content following this page was uploaded by Mohamed Zellagui on 03 June 2014.
Abstract
This paper presents a study on the performances of distance relays setting in
400 kV in Eastern Algerian transmission networks at Sonelgaz Group
(Algerian company of Electrical and Gas) compensated by shunt Flexible AC
Transmission System (FACTS). The facts are used for controlling
transmission voltage, power flow, reactive power, and damping of power
system oscillations in high power transfer levels. The effects of SVC devices
i.e. Thyristor Controlled Reactor (TCR) and the Thyristor Switched
Capacitors (TSC) insertion, on the total impedance of a transmission line
protected by MHO distance relay are investigated. The modified setting zones
protections for three forward zones (Z1, Z2 and Z3) have been calculated in
order to improve the performances of distance relay protection and prevent
circuit breaker nuisance tripping.
Keywords
Transmission Lin; Impedance; MHO Distance Relay; Setting Zones;
Substance; Shunt FACTS; SVC Devices; TSR; TSC.
Introduction
In recent years, power demand has increased substantially while the expansion of
power generation and transmission has been severely limited due to limited resources and
1
http://lejpt.academicdirect.org
Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400 kV Algerian Transmission…
Mohamed ZELLAGUI, Abdelaziz CHAGHI
environmental restrictions. As a consequence, some transmission lines are heavily loaded and
the system stability becomes a power transfer-limiting factor. Flexible AC transmission
systems (FACTS) controllers have been mainly used for solving various power system steady
state control problems [1]. The literature shows an increasing interest in this subject for the
last two decades, where FACTS devices are introduced in power systems to increase the
transmitting capacity of transmission lines and provide the optimum utilization of the system
capability. This is done by pushing the power systems to their limits [2-3]. It is well
documented in the literature that the introduction of FACTS devices in a power system has a
great influence on its dynamics. As power system dynamics changes, many sub-systems are
affected, including the protective systems. Therefore, it is essential to study the effects of
shunt FACTS devices on the protective systems, especially the distance protection, which is
the main protective device at HV and EHV levels.
The application of SVC was initially for load compensation of fast changing loads
such as steel mills and arc furnaces. Here the objectives are: increase power transfer in long
lines [4], improve stability with fast acting voltage regulation [5], damping low frequency
oscillations due to swing (rotor) modes [6] and damping sub-synchronous frequency
oscillations due to torsion modes and over-voltages dynamic control [7]. Unlike the power
system parameters, the controlling parameters of SVC devices, as well as their installation
points could affect the measured impedance [8-13]. This variation has a direct effect on the
protective zones settings for distance relays protected this line compensated. In the presence
of shunt FACTS devices, the conventional distance characteristic such as MHO and
quadrilateral are greatly subjected to mal-operation in the form of over-reaching or under-
reaching the fault point. Therefore, the conventional characteristics might not be utilized
satisfactorily in the presence of shunt FACTS devices [11,13].
In this paper, the three protection zones setting (Z1, Z2 and Z3) for a MHO distance
relay based analytic method on a 400 kV single transmission line installed at eastern Algerian
electrical network is considered.
The aim of this research was the investigation concerns TCR and TSC shunt FACTS
devices, for different values of firing angle (α) for injected reactive power ± 60 MVar shunt
compensation on midline transmission high voltage.
2
Leonardo Electronic Journal of Practices and Technologies Issue 21, July-December 2012
ISSN 1583-1078 p. 1-14
First Zone: It is normal practice to adjust the first zone relays (Z1) at A to protect only
up to 80% of the protective line AB. This is a high speed unit and is used for the primary
protection of the protected line. Its operation is instantaneous. This unit is not set to protect
the entire line to avoid undesired tripping due to over reach. Over reach may occur due to
transients during the fault condition.
Second Zone: Is set to cover about 20% of the second line (BC). The main object of
the second zone unit is to provide protection to the end zone of the first section which is
beyond the reach of the first unit. The setting of the second unit is so adjusted that it operates
the relay even for arcing faults at the end of the line. To achieve this, the unit must take care
beyond the end of the line. In other words its setting must take care of under reach caused by
arc resistance. Under reach is also caused by intermediate current sources, errors in CT, and
VT and measurement performed by the relay. To take into account the under reaching
tendency caused by these factors, the normal practice is to set the second zone reach up to
3
Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400 kV Algerian Transmission…
Mohamed ZELLAGUI, Abdelaziz CHAGHI
20% of the shortest adjoining line section. The protective zone of the second unit is known as
the second zone of protection. The second zone unit operates after a certain time delay. Its
operating time is 0.3 sec.
Third Zone: Is provided for back-up protection of the adjoining line. Its reach should
extend beyond the end of the adjoining line under the maximum under reach, which may be
caused by arcs, intermediate current sources and errors in CT, VT and measuring unit. The
protective zone of the third stage is known as the third zone of protection. The setting of the
third zone covers the first line i.e. the protected line plus the longest second line plus 20% of
the third line. The time delay for the third unit is usually 1 to 1.5 sec.
The setting zones for protected transmission line without shunt FACTS devices are
expressed by [16-17]:
4
Leonardo Electronic Journal of Practices and Technologies Issue 21, July-December 2012
ISSN 1583-1078 p. 1-14
The presence of SVC devices has a direct influence on the total impedance of the
protected line (ZAB). Connected at midline point of the line, the SVC is considered as a
reactor (XSVC) and lead to the new setting zones which can be expressed by [16-17]:
5
Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400 kV Algerian Transmission…
Mohamed ZELLAGUI, Abdelaziz CHAGHI
The overall action of the thyristor controller on the linear reactor of the TCR and
capacitor of the TSC is to enable the reactor to act as a controllable susceptance, in the
inductive mode, which is a function of the angle α [19]. The figure 4(a) and 4(b) represent the
substance for TCR and TSC respectively.
a) b)
Figure 4. Injected susceptance of SVC devices
The current ITCR directly related to the firing angle of thyristors (α), which was varied
between 90° and 180° [1-3,19]. The value of the substance BTCR will be represented by the
equation [3,19]:
Case Study
The figure below represents the power system studied in this paper and is the 400 kV,
50 Hz eastern Algerian electrical transmission networks at SONELGAZ group. The MHO
6
Leonardo Electronic Journal of Practices and Technologies Issue 21, July-December 2012
ISSN 1583-1078 p. 1-14
distance relay is located in the busbar A at Ramdane Djamel substation (Skikda) to protect
transmission line between busbar A and busbar B at Oued El Athmanai substation (Mila), the
busbar C at Ain M’lila substation (Oum El Bouaghi).
The shunt FACTS study type SVC is installed in the midpoint of the line protected by
a MHO distance relay as represented in figure 5. The parameters of the transmission line and
installed SVC device are summarized in the appendix.
The characteristic curves of the SVC compensator (TCR and TSC) used in this
network are indicated by figure 6(a) and figure 6(b) respectively.
7
Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400 kV Algerian Transmission…
Mohamed ZELLAGUI, Abdelaziz CHAGHI
a) BTCR = f (α)
b) BTSC = f (α)
Figure 6. Characteristic curves of the installed SVC
Figures 7 and 8 represented the impact of the variation angle α in the presence of TCR
and TSC on the total reactance XAB and resistance RAB respectively measured by MHO
distance relay.
8
Leonardo Electronic Journal of Practices and Technologies Issue 21, July-December 2012
ISSN 1583-1078 p. 1-14
As can be seen the presence of TCR and TSC has a direct influence on the parameters
of the protected line XAB and RAB. The total impedance measured by the distance relay
without SVC devices is equal 4,8407 + j 46,8048 (Ω), the settings zones are summered in
table 1.
9
Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400 kV Algerian Transmission…
Mohamed ZELLAGUI, Abdelaziz CHAGHI
Figure 9. Impact of the firing angle α on the reactance setting zones in the presence of TCR
Figure 10. Impact of the firing angle α on the resistance setting zones in the presence of TCR
10
Leonardo Electronic Journal of Practices and Technologies Issue 21, July-December 2012
ISSN 1583-1078 p. 1-14
From figures 9 and 10, the setting of the three zones of protection is dependent on the
angle α of the TCR.
Figure 11. Impact of the firing angle α on the reactance setting zones in the presence of TSC
Figure 12. Impact of the firing angle α on the resistance setting zones in the presence of TSC
11
Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400 kV Algerian Transmission…
Mohamed ZELLAGUI, Abdelaziz CHAGHI
As can be seen from figures 11 and 12 the setting of the three protection zones is
dependent on the firing angle α of the TSC.
Conclusions
The results show the direct effects of SVC devices i.e. thyristors controlled reactor
(TCR) and the thyristors switched capacitors (TSC) insertion, on the total impedance of a
transmission line protected by MHO distance relay. The impact is investigated for different
values of the thyristors firing angle.
As demonstrated these angles injected variable substance (BTCR or BTCS) in the
protected line which results in direct impact on the total impedance of the protected line. In
fact this effect varies the settings zones by increasing performance of the total system
protection and avoiding unwanted tripping of circuit breaker in the presence of SVC
compensator.
Appendix
12
Leonardo Electronic Journal of Practices and Technologies Issue 21, July-December 2012
ISSN 1583-1078 p. 1-14
References
1. Sen K. K., Sen M. L., Introduction to FACTS Controllers: Theory, Modelling and
Applications, New Jersey, USA, John Wiley & Sons Inc., 2009.
2. Zhang X. P., Rehtanz C., Pal B., Flexible AC Transmission Systems: Modelling and
Control, Heidelberg, Germany, Springer Publishers, 2006.
3. Noroozian M., Modelling of SVC in Power System Studies, Vasteras, Sweden, Published
by ABB Power Systems, Reactive Power Compensation Division, 2006.
4. Padiyar K. R., Varma R. K., Concepts of Static Var System Control for Enhancing
Power Transfer in Long Transmission Lines, Electric Machines and Power Systems,
1990, 18(4), p. 337-358.
6. Padiyar K. R., Varma R. K., Static Var System Auxiliary Controllers for Improvement of
Dynamic Stability, International Journal of Electrical Power and Energy Systems, 1990,
12(4), p.287-298.
7. Padiyar K. R., Varma R. K., Static Var System Auxiliary Controllers for Damping
Torsional Oscillations, International Journal of Electrical Power and Energy Systems, ,
1990, 12(4), p. 271-286.
9. Sidhu T. S., Varma R. K., Gangadharan P. K., Albasri F. A., Ortiz G. R., Performance
of Distance Relays on Shunt-FACTS Compensated Transmission Lines, IEEE
Transactions on Power Delivery, 2005, 20(3), p. 1837-1845.
10. Albasri F. A., Sidhu T. S., Varma R. K., Performance Comparison of Distance
Protection Schemes for Shunt-FACTS Compensated Transmission Lines, IEEE
Transactions on Power Delivery, 2007, 22(4), p. 2116-2125.
11. Kazemi A., Jamali S., Shateri H., Measured Impedance by Distance Relay for Inter
13
Comparing Effects of TCR and TSC on MHO Distance Protection Setting in 400 kV Algerian Transmission…
Mohamed ZELLAGUI, Abdelaziz CHAGHI
12. Jamali S., Kazemi A., Shateri H., Comparing Effects of SVC and STATCOM on
Distance Relay Tripping Characteristic, IEEE International Symposium on Industrial
Electronics (ISIE’2008), Cambridge, UK, 30 June - 2 July 2008, p. 1568-1573.
13. Kazemi A., Jamali S., Shateri H., Measured Impedance by Distance Relay in Presence
of SVC on Transmission Line, 2nd Annual Conference on IEEE Industrial Electronics,
Paris, France, 6-10 November 2006, p. 2214-2219.
14. Zigler G., Numerical Distance Protection: Principles and Applications, Third Edition,
Germany, Publics Corporate Publishing, 2008.
15. Blackburn J. L., Domin T. J., Protective Relaying: Principles and Applications, Third
Edition, USA, Published by CRC Press and Taylor & Francis Group, 2006.
16. Manamani N., Principles and Settings of Distance Relay, Sonelgaz, Algeria, Training at
GRTE Sétif, June 2009.
17. Zellagui M., Chaghi A., MHO Distance Relay of Transmission Line High Voltage using
Series Compensation in Algerian Networks, Journal of ACTA Electrotehnica, 2011,
52(3), p. 126-133.
18. Gérin-Lajoie L., A MHO Distance Relay Device in EMTP Works, Electric Power
Systems Research, 2009, 79(3), p. 484-491.
19. Acha E., Fuerte-Esquivel C. R., Pérez A. H., Angeles-Camacho C., FACTS Modelling
and Simulation in Power Networks, England, John Wiley & Sons, 2004.
14