ARCHITECTURAL

SPECIFICATIONS

PROPOSED THREE STOREY


RESIDENCE WITH ROOF DECK

PROJECT OWNER:
CLENT ANDREY O. GALAMITON

PROJECT LOCATION:
LOT 18B BLK 8 AGUILA ST., GATCHALIAN SUBD., BRGY. MANUYO DOS,
LAS PINAS

AR. SAMUEL PAULUS TOLENTINO


PRC NO.: 0043067
PTR NO.: 8012552
DATE ISSUED: 07/14/2022
PLACE ISUED: VALENZUELA
SPECIFICATIONS
Page 1 of 20
_________________________________________________________________________________________

1.00 GENERAL REQUIREMENTS

1.01 RELATED SECTIONS


All applicable provisions of the different divisions of the Specifications for each work trade shall
apply for all items cited in this Summary.

1.02 INFERRED ITEMS AND WORK


Materials and workmanship deemed necessary to complete the works but NOT specifically
mentioned in the Specifications, Working Drawings, or in the other Contract Documents, shall be
supplied and installed by the Contractor without extra cost to the Owner. Such materials shall be
of APPROVED quality, and installed or applied in a workmanlike manner at prescribed or
appropriate locations.

1.03 SPECIFICS
Materials specifically mentioned in this Summary shall be installed following efficient and sound
engineering and construction practice, and especially as per manufacturer's application for
installation specifications which shall govern all works alluded to in these Specifications.

1.04 ON-SITE ITEMS


Materials and finishes for on-site improvements and facilities as listed below are part of the scope
of work and shall be supplied and installed by the Contractor without extra cost to the Owner.
A. Installation of engineered and drainage fills for building and landscaped areas.
B. Construction of:
1. Concrete driveways, walks, ramps, steps, posts, and miscellaneous slabs;
2. Concrete splash slabs, steel or hard plastic gratings;
3. Below grade structures such as septic vaults, cisterns, handholes, and manholes

1.05 OFF-SITE ITEMS


Off-site improvements shall generally be under the responsibility of the Owner and not included in
the Contract, with the exception of the following which shall be part of the Contractor's Work:
A. Concreting of entry slabs. This work shall neatly make connections to the existing roads or
curbs, if any, and shall incorporate necessary utility ways under such as required. Access
road drainage system and other existing utility lines must be kept in working condition.
B. Installation of concrete drainage pipes to neatly receive connections from the storm drainage
system of the site to access road and/or to existing drainage system.
C. Permanent connections to the local utility lines for electrical, water, drainage, sewer and
telephone lines including equipment, facilities, materials, fees, and/or work which utility
companies or authorities may require of the applicant Owner, such as electrical transformers,
electric poles, service laterals and drops, etc; by their respective Specialty Contractors.
SPECIFICATIONS
Page 2 of 20
_________________________________________________________________________________________

1.06 OWNER SUPPLIED ITEMS


Owner supplied items shall include all furniture and fixture not reflected in the construction
drawings.

2.00 SITEWORK

2.01 EXCAVATION SUPPORT SYSTEM


A. SHORING AND BRACING SYSTEMS
Types of shoring and bracing systems include, but are not limited to the following:
1. Steel H-section (soldier) piles
2. Timber lagging
3. Steel sheet piles

2.02 EARTHWORK
A. FILL MATERIALS
1. General Fill for structures and under spread footings, pavers, or concrete slabs on
grade shall conform to the general requirement for soil materials above and shall be
classified as GW, GM, GP, SW, SM by the ASTM 2487 and conform to the following.
a. Liquid Limit – shall not exceed 25% when tested in accordance with ASTM 423.
b. Plasticity Index – shall not exceed 12 % when tested in accordance with ASTM
424.
c. Under Buildings, no more than 25% by weight shall be finer than No. 200 sieve
when tested in accordance with ASTM D 1140.
2. Granular Fill shall conform to the general requirements for soil material above and shall
be clean, crushed stone or gravel conforming to ASTM C 33, size 67 and with a sand
equivalent of not less than 50% when tested in accordance with ASTM D 2419.
3. Backfill material behind walls shall consist of free-draining granular fills, sized in
particular to provide a filter media around subsoil drainage system.
4. Drainage Fill: Fill material shall clean, well graded, free draining sand conforming to
ASTM C 33 for Fine Aggregate.
5. Borrow: If additional material is required for fill in excess of that obtained by
excavation at the site, obtain same from sources acceptable to the Civil/Structural
Engineer’s specifications. All arrangement for obtaining borrow from off site shall be
the responsibility of the Contractor and all cost thereof shall re borne by the Contractor.
Acceptable borrow will consist of suitable material for fills as herein before specified.
Representative of each type of borrow materials considered suitable shall be delivered
to the Testing Laboratory and tested prior to placement. Any borrow material not
meeting the standard herein specified, or considered unsuitable by the Owner’s
Engineer will be rejected at the site.

B. RIPRAP: Rock Boulders, natural, hard rock, high density, from 400 mm to 800 mm in
diameter.

C. Batterboards: Second class, pest free lumber assembled and rendered secure for proper
delineation of building lines and grades.
SPECIFICATIONS
Page 3 of 20
_________________________________________________________________________________________

2.03TERMITE & BUKBOK PROOFING


Product and application by Owner-accredited termite and pest control contractor.
A. TERMITE PROOFING: Use only LENTREK TC Termicide Concentrate. Dilution rating: 1
part LENTREK TC to 50 parts water. There shall be no disturbance of treated soil between
application of poison and pouring concrete.

2.04 UNIT PAVERS


A. CONCRETE PAVERS: Precast concrete stepping stones, made from normal-weight
aggregate, in shapes and sizes indicated.

2.05CONCRETE CURBS, GUTTER, AND PAVED WALKS


A. CEMENT: shall be as per ASTM Standard Specifications for Portland Cement (ASTM C-
150: latest revision) for Type 1 Portland Cement.

B. CONCRETE AGGREGATES
1. Aggregates shall be well-graded, clean, hard particles or gravel or crushed rock
conforming to the STANDARD SPECIFICATION FOR CONCRETE AGGREGATES
(ASTM Designation C-33: latest revision).
2. SAND: shall be coarse sand free from injurious materials such as shells or earth or
organic materials. Sand from salt water is not allowed.

C. WATER: shall be clean and free from injurious amounts of oils, acids, alkali, organic
materials or other deleterious substances.

D. FORMS: shall be either wood or steel.

E. CONTROLLED STRENGTH OF CONCRETE: Concrete shall develop a minimum of 28-


day cylinder strength of 21 Mpa (3,000 PSI).

2.06SITE DRAINAGE
A. DRAINAGE PIPE:
1. Plain concrete drain pipe and fittings 250 mm (10") and below in diameter: T & G
conforming to ASTM C-14-59.
2. Reinforced concrete pipes fittings 300 mm (12”) and bigger: Centrifugally cast or
vibrated T & G conforming to ASTM C-76-59 T.

B. JOINING MATERIAL: One part cement to two parts sand.

C. BUILDING STORM DRAIN CONNECTION TO MAIN: Concrete wye branch and clean out,
T & G or use junction boxes.

D. AREA DRAIN CATCH BASIN: Load-bearing 4.8 Mpa (700 PSI) concrete hollow blocks
(CHB) or reinforced concrete with cover as show on the drawings.
SPECIFICATIONS
Page 4 of 20
_________________________________________________________________________________________

E. CATCH BASINS OF JUNCTION BOXES: Load-bearing 4.8 Mpa (700 PSI) concrete hollow
blocks (CHB) or reinforced concrete as indicated in the drawings, with solid reinforced
concrete cover.

3.00 CONCRETE

3.01 CONCRETE FORM WORKS


A. FORMS:
1. TYPE OF FORMS: Use phenolic boards for exposed and unexposed concrete works, for
all cast in place and pre-cast works.
2. SCAFFOLDS: Use of metal scaffolding is advised.

3.02 CONCRETE STEEL REINFORCEMENT


A. STEEL BARS: Use locally manufactured deformed billet-steel bars conforming to Philippine
standard, Intermediate Grade of 275.8 Mpa (Fy = 40,000 psi) for bars 12 mm diameter or
smaller, and High Strength Structural Grade of 415 Mpa (Fy = 60,000 psi) for bars 16mm
diameter and larger. Use standard-sized deformed steel conforming to ASTM A615 / PNS
49 standards, for concrete and masonry reinforcements. Upgrade to next bigger size if
specified standard sizes are unavailable.

B. TIE WIRES: Use Ga.16 Galvanized Iron (G.I.) tie wires at joints or laps of placed
reinforcements.

3.03 CAST IN PLACE CONCRETE


A. GENERAL:
Concrete shall be composed of Portland cement, fine and coarse aggregates, water and
admixture as specified, all thoroughly mixed and brought to the proper consistency, uniformity
and temperature for final placement. Strength requirements shall be:
1. 21 Mpa (3000 psi) for columns, girders, beams, footings, retaining walls, footing tie
beams, cistern and suspended slabs.
2. 17.2 Mpa (2500 psi) for slabs on grade, partitions, walks, & other non-structural members;
3. 10.5 MPa (1500 psi) for lean concrete, or as required by the Engineer.

B. CEMENT:
Cement shall be Portland cement, conforming to the Standard Specifications for Portland
Cement (ASTM Designation C-150 latest revision) for type 1 Portland Cement. Use only one
brand of cement throughout.

C. FINE AGGREGATES:
Fine aggregates shall consist of natural sand, manufactured sand, or a combination thereof. If
the fine aggregate shall be a combination of separately processed sizes, or if hatching shall
result in a combination of natural and manufactured sand, the different components shall be
batched separately.
Fine aggregates shall consist of hard, tough, durable, uncoated particles. The specified
percentages of fines in the sand may be obtained either by the processing of natural sand or
by the production of a suitably graded manufactured sand. The shape of the particles shall be
generally rounded or cubical and reasonably free from flat or elongated pieces. The use of
SPECIFICATIONS
Page 5 of 20
_________________________________________________________________________________________

beach sand shall be prohibited. The fine aggregate shall conform to the following specific
requirements:

Sieve Designation
Standard (MM) U.S. Standard, Cumulated Percentage by
Square Mesh Weight Passing

9.5 3/8 100


4.75 No. 4 95-100
2.36 No. 8 -
1.18 No. 16 45-80
0.60 No. 30 -
0.30 No. 50 10-30
- No. 100 2-10

In addition to the grading limits shown above, the fine aggregates, as delivered to the mixer
shall have a fineness modulus of not less than 2.3 nor more than 3.0 and during normal
operations, the grading of the fine aggregate shall be controlled so that the fineness modulus
of at least nine (9) of ten (10) test samples of the fine aggregate as delivered to the mixer shall
not vary more than 0.20 from the average fineness modulus of all samples tested during the
preceding 30-day period. The fineness modulus can be determined by dividing by 100 the
sum of the cumulated percentages retained on U.S. Standard Sieves Nos. 4, 8, 16, 30, 50 and
100. At the option of the Contractor, fine aggregates may be separated into two or more sizes
or classification, but the resulting combined sand shall be of uniformed grading within the limits
specified above. It can be generally assumed that a fine blending sand maybe required to
meet the above grading.

D. COARSE AGGREGATES:
Coarse agreement shall consist of gravel, crushed gravel or rock, or a combination thereof.
The coarse aggregate as delivered to the batching plant shall have a uniform and stable
moisture content. The approval of deposits shall not be construed as constituting the approval
of all the materials taken from the deposits and the Contractor shall be held responsible for
the specified quality of all such materials used in the work. Coarse aggregate shall consist of
hard, tough, durable, clean and uncoated particles. All foreign materials and dust shall be
removed by adequate processing. The particle shape of one of the smallest size of crushed
coarse aggregate shall be generally rounded or cubical, and the coarse aggregate shall be
reasonably free from flat and elongated particles. A thin, flat and elongated particle can be
defined as a particle having a maximum dimension greater than five times the minimum
dimension. The coarse aggregate shall be well graded from fine to coarse. It shall be
separated into size groups.
The grading of the aggregate within the separated size groups as delivered to the mixer shall
be as follows:
Sieve Sizes
Standard U.S. Std. Sq. Percent by Weight Passing Individual
(MM) Mesh Sizes 1-1/2" 3/4"size
50.00 2" - 100
37.50 1-1/2" - 90-100
25.00 1" 100 20-55
19.00 3/4" 90-100 0-15
SPECIFICATIONS
Page 6 of 20
_________________________________________________________________________________________

9.50 3/8" 20-55 0-5


4.75 No.4 0-10 -

- Use 19mm (3/4) coarse aggregate for slab on grade, columns, beams, suspended
slabs, tie beams.
- Use 38mm (1 1/2") coarse aggregate for footings

E. WATER:
Water shall be clean and free from injurious amounts of oils, acids, alkalis, salts and organic
materials, or other substances that may be deleterious to concrete or steel.

F. ADMIXTURES: shall be subject to prior approval by the Engineer. The admixtures shall be
capable of maintaining essentially the same composition and performance throughout the
work.
1. Plasticizing admixtures shall be free from chlorides and shall conform to ASTM C494. The
admixtures shall be used in concrete mixtures in accordance with the manufacturer's
instructions.
2. Air-entraining admixtures, accelerators, water reducing retarders shall comply with
Section 03400.
3. Integral Waterproofing Compound - SIKA or approved equal. For canopy slab. Use one
kilo pack per forty kilo bag of Portland cement.
4. Calcium chloride is not allowed. Secure approval of the Engineer prior to using of any
other additive.

G. EPOXY BONDING COMPOUND:


1. ASTM C881, 2-component materials suitable for use on dry or damp surfaces. Material
type, grade and class to suit project requirements. For bonding new to old concrete, repair
of cracks, bonding grout.

NOTE: PLACEMENT DRAWINGS: Shop drawings of each reinforcing steel detail and
placement drawings shall be submitted for approval in accordance with the requirements of the
General Conditions. Any material fabricated before final approval of the shop drawings will be
done at Contractor's risk, but no material shall be placed until shop drawings have final
approval. Shop drawings shall be in accordance with the "Manual of Standard Practice for
Detailing Reinforced Concrete Structures" (ACI 315).

3.04 ARCHITECTURAL PRE-CAST CONCRETE


A. MOLD MATERIALS: Metal, plastic, or wood that is non-reactive with concrete and will produce
required finish surface.

B. REINFORCING MATERIALS:
1. Reinforcing bars: ASTM A 615M, Grade 400, deformed.
2. Steel-Welded Wire Fabric: ASTM A 185, plain, cold drawn.

C. CONCRETE MATERIALS:
1. Portland Cement: ASTM C 150, Type 1. Use only one brand, type, and color of cement
from the same mill throughout Project.
SPECIFICATIONS
Page 7 of 20
_________________________________________________________________________________________

2. Normal-Weight Aggregates: ASTM C 33, with coarse aggregates meeting Class 5S and
MNL-117 requirements.
a) Face-Mix Coarse Aggregates: Selected, hard, and durable; free of materials that reacts
with cement or causes staining. Uniformly graded.
b) Face- Mix Fine Aggregates: Selected, natural or manufactured sand of the same
material as coarse aggregate, unless otherwise acceptable to the Architect.
3. Coloring Agent: C 979, synthetic, mineral oxide pigments or colored water-reducing
admixtures, color stable, non-fading, resistant to lime and other alkalis.
4. Water: Potable; free from deleterious material that may affect color stability, setting, or
strength of concrete.
5. Air-Entraining Admixture: ASTM C 260, certified by manufacturer to be compatible with
other required admixtures.
6. Water-Reducing Admixture: ASTM C 494, Type A.
7. Retarding Admixture: ASTM C 494, Type B.

D. CONNECTION MATERIALS:
1. Steel Shapes and Plates: ASTM A 36M.
2. Malleable Iron Castings: ASTM A 47M
3. Carbon Steel Plates: ASTM A 283M.
4. Carbon-Steel Bolts and Studs: ASTM F 568, Property Class 4.6; carbon-steel, hex-head
bolts and studs; carbon-steel nuts; and flat, unhardened steel washers.
5. Welded Headed Studs: AWS D1.1, Type B headed studs, cold-finished carbon-steel bars.
6. Deformed-Steel Wire Bar Anchors: ASTM A 496.
7. Welding Electrodes: Comply with AWS standards.
8. Accessories: Provide clips, hangers, plastic shims, and other accessories required to
install architectural pre-cast concrete units.

E. BEARING PADS: Elastomeric pads; AASHTO M 251, plain, vulcanized, 100 percent
polychloroprene (neoprene) elastomer, molded to size or cut from a molded sheet, 50 to 70
shore A durometer, minimum tensile strength 15.5 Mpa (2250 psi) per ASTM D 412.

F. GROUT MATERIALS: Cement Grout; Portland cement, ASTM C 150, Type 1, and clean,
natural sand, ASTM C 404. Mix at ratio of 1 part cement to 2-1/2 parts sand, by volume, with
minimum water required for placement and hydration.

G. CONCRETE MIXES:
1. Normal-Weight Concrete Face and Back-Up Mixes: Proportion mixes by either laboratory
trial batch or field test data methods according to ACI 211.1, using materials to be used on
the Project, to provide normal weight concrete with the following properties:
a) Compressive Strength (28-day): 20.7 Mpa (3000 psi).
b) Maximum Water-Cement Ratio at Point of Placement: 0.40.
2. Lightweight Concrete Back-Up Mixes: Proportion mixes by either laboratory trial batch or
field test data methods according to ACI 211.2, using materials to be used on the Project,
to provide lightweight concrete with the following properties:
a) Compressive Strength (28-day): 34.5 Mpa (5000 psi).
b) Unit Weight: Calculated equilibrium unit weight of 1842 kg/cum (115 lb/cuft), plus or
minus 48 kg/cum (3lb/cuft), according to ASTM C 567.
SPECIFICATIONS
Page 8 of 20
_________________________________________________________________________________________

4.00 MASONRY

4.01 04100: MORTAR


A. PORTLAND CEMENT: Use only one brand of cement throughout. Portland cement shall
conform to the Standard Specifications for Portland Cement (ASTM Designation C-150 latest
revision) for type 1 Portland Cement.

B. SAND: ASTM C 35 – 67, clean, washed river sand, strong, free from organic and other
deleterious materials. Sand from salt water or lahar is not allowed.

C. WATER: Fit for drinking, free from injurious amount of oil, acids, alkali, organic materials
and other deleterious substances.

D. CONCRETE MORTAR COMPRESSIVE STRENGTH: ( f'c ) = 13.8 Mpa (2000 psi).

E. ADHESIVE MORTAR: Use ABC ADHESIVE MORTAR for laying vitrified ceramic tiled with
ABC DISPERSION COMPOUND as an additive to ABC ADHESIVE MORTAR.

F. GROUT: Use ABC GROUT pre-mixed dry wall filler for floor and wall tile joints either
glazed or semi-glazed tiles. Masonry concrete grout compressive strength ( fc’ ) = 13.8
Mpa (2000 psi). For kitchen, toilet works and tile works.

G. PLASTER BOND: Plaster Bond: N & H PLASTER BOND or approved equal. Apply on all
wall areas prior to plastering.

H. MORTAR TOPPING & PLASTER REINFORCING FIBER: GRACE MICROFIBER, as


manufactured by W.R. Grace Philippines. For plaster works thicker than 25mm (1”) and for
mortar topping over membrane waterproofing for roof decks and balconies.

4.02 UNIT MASONRY


A. CONCRETE HOLLOW BLOCKS (CHB):
1. 150 mm x 200 mm x 400 mm (6" x 8" x 16") and 100 mm x 200 mm x 400 mm (4” x 8”
x 16”) Non-Load Bearing Concrete Hollow Block Units of standard manufacture,
machine vibrated with even texture and well defined edges, steam-cured, conforming
to PNS16 Type 1, Class A, with a minimum compressive strength of 3.50 Mpa (500
psi) for building exterior and interior walls and septic tank.
Note: For CHB interior walls, use 4” CHB from floor to bottom of slab or bottom of
beam, with 10mm dia. reinforcing bars at 600mm o.c. bothways. Anchor to floor by
embedding vertical bars 75mm deep into the floor slab. Anchor to slab or beam by
providing 10mm dia. dowels. Provide stiffener columns and beams as required in the
general notes. PLAIN CEMENT PLASTER-PAINTED FINISH.
SPECIFICATIONS
Page 9 of 20
_________________________________________________________________________________________

B. REINFORCING BARS: Masonry reinforcing steel yield strength (fy) =228 Mpa (33,000 psi),
Grade 33 bars, conforming to ASTM Specifications A615 / PNS 49 of sizes shown in Plans.
Use standard sizes; upgrade to next bigger size if specified standard sizes are unavailable.

C. TIE WIRES: Gauge 16 Galvanized Iron (G.I.) tie wires.

5.00 METALS

5.01 STRUCTURAL STEEL


Owner / Architect – approved manufacturer / sub – contractor. Conform all materials and
workmanship to the requirements of the American Institute of Steel Construction
"Specifications for Design, Fabrication and Erection of Structural Steel for Buildings" as
amended to date or as may be specifically modified by the drawings or by these Specifications.
A. PLATES, SHEETS AND CONNECTORS: Conform to ASTM Designation A36 with
specified yield point of 248 Mpa (36,000 psi). From mild steel sheets or plates with
standard thickness, size, shape and design as indicated in the plans. For miscellaneous
stiffener, bearing anchorage and connector plates or straps. Upgrade to next higher /
bigger size and thickness if specified sizes & thicknesses are unavailable.

B. HIGH STRENGTH BOLTS, NUTS AND WASHERS: Conform bolts to the Specification for
High Strength Bolts ASTM A 325, Type 1 . See structural connection details for location of
bearing-type and friction-type bolts.

C. ANCHOR BOLTS: A36.

D. WELDING ELECTRODES: Conform all welding electrodes to AWS D1.1:2000 Structural


Welding Code – Steel, E-60XX for structural welding.

E. GROUT: Conform all non-shrink grout to ASTM C827. Grout shall be non-metallic, non-
shrink, flowable cementitious grout. Apply using manufacturer’s standards strictly.

F. STRUCTURAL STEEL PRIMER PAINT: Epoxy zinc chromate primer except as otherwise
recommended by the manufacturer of the coating for all structural steel surfaces.

5.02 MISCELLANEOUS METALS


A. STANDARD SOLID SECTION: Conform to ASTM 611 with specified yield point of 228 Mpa
(33,000 psi). Mild steel flat bars, square bars, overhead anchorage of roll-up doors, grill
work, miscellaneous fabricated mounting brackets, straps, dowels, frames and connectors.
Upgrade to next higher / bigger size and thickness if specified sizes & thickness are
unavailable.

B. BRACING RODS: Use standard structural grade steel rods with turnbuckles whenever
required, for roof framing.
SPECIFICATIONS
Page 10 of 20
_________________________________________________________________________________________

C. PAINTING: Use only approved brand of epoxy zinc chromate paint and linseed oil for all
architectural steel components only. For field painting, use only approved brand of enamel
paint.

D. STAINLESS STEEL: Pipes, tubes, square bars, and other sections shall be provided with
appropriate guarantee.
1. Roof Gutter: Whenever necessary, 1.2 mm (gauge 18) thick, Stainless Steel Sheets,
Type 304 bent to design shape.
2. Main and Side Entrance Ramp and Step Railing: SS Pipes, Gauge 40, of sizes as
indicated in Plans and details.
3. RC Precast Anchors: 10mm Stainless Steel Plain Bars

E. GALVANIZED IRON:
1. Minor Ramp and Step Railing, Exterior and Interior Ledge Railing shall be Gauge 40,
of sizes as indicated in Plans and details, finish with Epoxy Enamel Paint.
Note: Upgrade to next bigger size if specified standard sizes are unavailable.
2. Yard Hose Bibbs: G.I. Pipes, Ga. 40, painted with Epoxy Enamel Paint.
a. Hangers: Gauge 10 G.I. wire hanger.

F. FASTENINGS: Commercial types, except where special types are shown or required.
Fastenings for all exterior work shall be non-ferrous, unless otherwise shown. Fastening for
stainless steel and aluminum and other interior work, where exposed shall match the
fastened metal.
0: STEEL DECK
6.00 WOOD AND PLASTICS

6.01 FINISH CARPENTRY


All wood sources shall be certified as lawful by the Contractor. Each separate lumber piece or
assembly is required to bear an official mark of the millworks supplier. Submit detail plans
and specifications for Owner’s approval.

7.00 THERMAL AND MOISTURE PROTECTION

7.01 WATERPROOFING AND DAMPPROOFING


Apply with surface preparation, methods application and density as per manufacturer’s
specifications and with guarantee.

A. INTEGRAL WATERPROOFING. Cementitious powder, pre-mix admixture or water base


surface coat conforming to the standard specifications set by the Bureau of Product
Standard of the Department of Trade and Industry.

B. MEMBRANE WATERPROOFING: Osmo-seal powder, Liquid Elastomeric or Epoxy


Solventless waterproofing compound for extra flexibility and resiliency to give lasting
waterproof effect. Mixture shall be notched trowel, squeegee, roller, paint brush or airless
spray and shall remain tight under condition of expansion, contraction and vibration loads.
SPECIFICATIONS
Page 11 of 20
_________________________________________________________________________________________

C. Dampproofing: vapor barrier, one layer at six mils (0.006) thick. For slabs on fill at the
building interior. Provide 300 mm overlapping.

7.02 DRAINAGE SHEET AND FILTER


When necessary, use Drainage Sheets and Geotextile Filter to cover all underground exterior
walls and slabs. Use stop pins on sheeting overlaps and on top edge of sheeting; installation by
Owner approved installer with guarantee.

7.03 BUILDING AND ROOFING INSULATION


A. METAL ROOFING INSULATION: For all metal roofing, installed directly under C-purlins.

7.04 PREFORMED ROOFING


A. METAL SHEET ROOFING & ACCESSORIES: As manufactured by DN STEEL
MARKETING, INC. or approved equivalent.
1. Metal Sheet Roofing: Pre-formed, pre-painted long-span G.I. roofing sheets, in color
approved by the Owner. For roofing as indicated in the plans.
Base metal type: Cold rolled steel tempered to 275 Mpa (40,000 psi).
Thickness: 0.60 mm
Effective Coverage: 1030 mm
Anti-rust Coating: 55% Alum, 43.4% zinc & 1.6% silicon
Coating Standards: AZ 125 (125 gm/m2); ASTM A-792
Top Coat: 20 Microns Regular Polyester
Back Coat: 8 Microns Epoxy Primer
2. Ridge rolls, flashings, cappings, trims, mouldings and awnings: 0.60 mm thick base
metal thickness, (215 g/m² zinc coating) pre-painted zinc coated from plain sheets, pre-
formed with matching shape and fitting provisions.
3. Fasteners and Fixation: Use rivets and straps whenever possible, TEKSCREWS or
appropriate connectors as recommended by the manufacturer and approved by the
Architect. Paint same color as roof, all fixation and fastening devices. Apply fastener
in a neat, consistent, even and standard manner. Apply strip or butyl rubber-based
caulking compound along all end lap joints and passing over pre-drilled fixation holes,
for fixation of metal sheet to built up purlins and when lapped over another metal sheet
and for fixation of flashing and fascias to metal or concrete support.
4. Strainer: Use Brass Dome Strainers for gutters.

7.05 JOINT SEALANTS


A. Silicon Sealant: Use as a general purpose, neutral cure sealant. Contractor must
guarantee watertightness of all joints even during strong winds. Use also as sealant for
acoustic-treated walls in between classrooms.

B. Use Co-Polymer Clear Sealant for roofs, awnings, roof flashings, skylights, gutters and
downspouts.

C. Use Solvent-Based Synthetic Rubber Contact Type Adhesive for bonding wood, plastic
laminate, concrete, steel aluminum and hardwood, rubber and glass.
SPECIFICATIONS
Page 12 of 20
_________________________________________________________________________________________

D. Use Acrylic Latex Gap Sealant for use between windows or door frames and walls, along
skirting boards, around cornices, between countertops and splashboard. In corner or
between the wall and ceiling or where shrinkage or movement causes rigid fillers to crack.

E. Use Acid Cure Silicon for use on non-porous surfaces such as glass, ceramics and
porcelain.

8.00 DOORS AND WINDOWS

8.01 METAL DOORS AND WINDOWS


A. WINDOWS: Provide and install all windows with complete locksets, hinges and
accessories.
1. GLAZED ALUMINUM WINDOWS: Use extruded aluminum 6063-T5 alloy for aluminum
window frame sections. Use steel-strengthened aluminum.

8.02 WOOD and PVC DOORS


A. WOOD DOORS:
1. Guijo or Yakal, single length, sound, warp-free, S4S and fine-sanded lumber, sun-
dried, for door jambs, when required in the drawings.
2. Solid Wood Panel Door, double-leaf swing, 44 mm (1-3/4”) thick with 6mm (1/4”) thick
glass panels as indicated in drawings. For main entrance door.
3. Hollow Core Flush Swing Door, single-leaf, 44 mm (1-3/4”) thick, with 6 mm (1/4”) thick
Tanguile Ribbon-Grained Plywood both faces on K.D. Tanguile frames. For bedroom
and rear entrance doors.
4. PVC Swing Door, single-leaf, 44 mm (1-3/4”) thick. For T&B doors.

8.03 FINISH HARDWARE


A. ALUMINUM DOOR HARDWARE: All aluminum entrances, complete with all components
and hardware. Use HAFELE or approved equal.

B. DOOR LOCKS AND LOCKSETS: HAFELE, or approved equal. Note: Provide 4 pcs Master
Keys for all cylindrical locksets and deadbolt locking device.
1. Cylindrical Locksets:
a) For entrance doors and bedrooms: Satin chromium finish. Turn-button locking in
inside knob; requires use of key at all times until button is manually restored to
unlock position.
b) For all toilet doors: Satin chromium finish. Push button locking in inside knob. Can
be opened from outside by screwdriver or similar tool or by turning inside knob.
2. Deadbolts: Satin chromium finish, heavy duty deadbolt thrown or retracted by key from
outside or by inside turn unit. Bolt automatically deadlocks when fully thrown.

C. HINGES:
SPECIFICATIONS
Page 13 of 20
_________________________________________________________________________________________

1. 88.5 mm x 88.5 mm, (3-1/2” x 3-1/2”) plain bearing, stainless steel, loose pin or fixed
pin, button tip, four (4) pieces per door panel

D. SLIDING DOOR HARDWARE:


1. Use manufacturer’s standard

E. DOOR STOP / DOOR HOLDER: Chrome finish, floor / wall mounting. Attached securely
to floor / wall to prevent door knob from hitting the wall.

F. CABINET ACCESSORIES: (Owner-supplied and installed)

8.05 GLAZING
As manufactured by REPUBLIC GLASS CORPORATION or approved equal.
A. RAGC CLEAR FLOAT GLASS: 6 mm (1/4 inch) thick. For all aluminum doors and
windows; must be able to withstand a Design Wind Velocity of 250 km/h.

B. DECORATIVE MIRRORS: 6 mm (1/4”) thick plate glass mirror, distortion-free with felt
paper on 6 mm (1/4”) thick Weatherproof Marine Plywood backing installed on satin-finish
anodized aluminum frame. For toilets. (Owner-supplied and installed)
d
C. BULK COMPOUND FOR GLASS INSTALLATIONS:
1. Mastics – Elastic compounds and non-skinning compound.
2. Putties- Wood sash putty, metal sash putty.
3. Sealants – one component, two components.

D. PREFORMED SEALANTS:
1. Synthetic Polymer – base sealants – resilient or non-resilient type.
2. Pre-formed gaskets – compression type, structural type.

E. CAULKING: Silicon Building Sealant or approved equal. For all joint gaps between
aluminum frames and concrete.

9.00 FINISHES

9.01 PLASTER
A. PLAIN CEMENT PLASTER FINISH: Consisting of the scratch and finish coats, both
consisting of one (1) part Portland cement and two (2) parts of clean, washed sand,
measured by volume. For all interior and exterior wall surfaces where plastering is
essential to complete the work.

B. SMOOTH RUBBED FINISH: For all exposed undersides of suspended floor RC slabs and
beams.

C. TOOLED JOINT FINISH: Surface preparation shall be plain cement plaster finish with
tooled mortar joints. Joints shall be concave, clean, plumb and true to line. All joints shall
be spaced as directed by the Architect.
SPECIFICATIONS
Page 14 of 20
_________________________________________________________________________________________

9.02 FIBER CEMENT BOARD


A. FIBER CEMENT BOARD: 4.5 mm thick for ceiling boards of toilets and of uppermost
floors covering roof structure; and 12 mm thick for wall boards: 1200 mm x 2400 mm,
HARDIFLEX as manufactured by JAMES HARDIE BUILDING BOARDS and distributed by
JARDINE-DAVIES INC., or approved equal Install as per manufacturer’s instructions.
Fixings shall be rust proof screws or nails.

B. Light Metal Frames for Wall Assemblies:


1. For walls, as indicated, use 35mm x 92 mm x 0.80mm thick Metal studs at 0.60 M on
center and 35mm x 92mm x 0.80mm thick tracks and noggings, knurling stiffeners,
side assemblies, bullnoses, cornerbeads, utility holes and others to complete. Finish
with 6 mm thick FCBs each side. Submit mock-up on site, with boards, before
installation.

C. Metal Ceiling Assembly: Use 19mm x 50mm x 0.4 mm thick G.I. furring channel and 0.6
mm thick J-type-wall angle with 12mm x 38mm x 1.0 mm thick G.I. carrying channel, 6
mm diameter hanger rod, suspension clips, rod joiners, steel angles, furring clips, fastening
devices and others to complete. Submit mock-up on site, with ceiling boards, before
installation.

9.03 GYPSUM BOARDS


A. Gypsum Board: 10 mm thick x 1200 mm x 2400 mm gypsum board, standard type,
tapered edge BORAL PLASTERBOARD as distributed by RIVIERA HOME
IMPROVEMENTS, INC or approved equal. Seal all joints by using appropriate gypsum
joining plaster and cotton tape as per manufacturer’s instructions. Use for interior wall
boards of academic offices and cubicles. Provide 2” fiberglass insulation and acoustic
sealants at floor slab connection for all partitions of cubicles.

9.04 TILES
A. VITRIFIED CERAMIC TILES: Use one brand from same batch throughout for each
type/size:
1. 600mm x 600mm Floor Tiles - Use MARIWASA, EUROTILES (Philippines) or
approved equal, in colors approved by the Owner, for living, dining, kitchen and
bedroom floors and as shown in the drawings.
2. 300mm x 300mm Floor Tiles – Use MARIWASA, EUROTILES (Philippines) or
approved equal, in colors approved by the Owner, for toilet floors and as shown in the
drawings.
3. 300mm x 300mm Wall Tiles - Use MARIWAS, EUROTILES (Philippines) or approved
equal, in colors approved by the Owner, for toilet walls, for all troughs and as shown in
drawings.
Finish shall be clean, plumb and true to line. Use ABC Grout from all ALLGEMEINE-BAU-
CHEMIE (ABC) PHIL., INC. only.

B. ADHESIVE, GROUT AND SEALANT: Use ABC Adhesive, ABC Grout (color coordinated
as required) and ABC Sealant from all ALLGEMEINE-BAU-CHEMIE (ABC) PHIL., INC., or
approved equal.
SPECIFICATIONS
Page 15 of 20
_________________________________________________________________________________________

C. TILE TRIM: Use plastic tile trim to cover all exposed tile joints; color-coordinated as
required.

9.05 STRAIGHT TO FINISH SLAB


Use Plain Cement Plaster Finish with vitrified ceramic tile inlays, design as per drawings, cast
straight-to-finish. For floor finish of lobbies and corridors, with vitrified tiles décor as per
drawings.

9.06 PAINTING :
Use BOYSEN PAINTS only (one brand all throughout). All exposed finish hardware, lighting
fixtures and accessories, plumbing fixtures and accessories, glass surfaces and the like shall
be adequately protected against stains from paint and other painting materials prior to painting
works. All other surfaces which would be endangered by stains or paint marks should be taped
and covered with craft paper or equal.
A. EXTERIOR:
1. PERMACOAT SEMI-GLOSS LATEX, for all concrete/masonry surfaces; concrete
parapets and fascias; spandrel walls; underside of concrete ledges, exposed sides of
retaining walls, concrete railing of ramps, stepped platform at atrium and all other
minor surfaces unless otherwise specified.
Surface Preparation: BOYSEN Masonry Neutralizer #44
1st Coat: BOYSEN Permacoat Concrete Sealer #705 White or
BOYSEN Permacoat Latex #701 White.
Putty minor cracks and surface imperfections with
BOYSEN Patching Compound
2nd and 3rd Coats: BOYSEN Permacoat Semi-Gloss Latex #715
Tint to get the required color with BOYSEN Latex Colors.

B. INTERIOR:
1. PERMACOAT SEMI-GLOSS LATEX, for all interior concrete & masonry walls;
exposed beams, girders and ceiling surfaces; FCB wall and column surfaces; for walls
above toilet tiles; for gypsum board surfaces and all other miscellaneous concrete
areas unless otherwise specified.
Surface Preparation: BOYSEN Masonry Neutralizer #44
1st Coat: BOYSEN Permacoat Concrete Sealer #705 White or
BOYSEN Permacoat Latex #701 White.
Putty minor cracks and surface imperfections with
BOYSEN Patching Compound
2nd and 3rd Coats: BOYSEN Permacoat Semi-Gloss Latex #715
Tint to get the required color with BOYSEN Latex Colors.
2. BOYSEN CLEAR DEAD FLAT LACQUER #1253
For all exposed interior wood surfaces, where applicable.
Surface Preparation: BOYSEN Wood Paste Filler #60 or
BOYSEN Lacquer Wood Tite #61
SPECIFICATIONS
Page 16 of 20
_________________________________________________________________________________________

1st Coat: BOYSEN Lacquer Sanding Sealer #1254


BOYSEN Oil Wood Stain Series #2700
2nd and 3rd Coats: BOYSEN Clear Dead Flat Lacquer #1253
Solvent / Cleaner: BOYSEN Lacquer Thinner
3. BOYSEN Flatwall Enamel #800 - For minor unexposed wood surfaces, where
applicable.
1st Coat: BOYSEN #300 White Interior Primer & Sealer of
BOYSEN Flatwall Enamel #800
BOYSEN #311 White Glazing Putty
2nd & 3rd Coats: BOYSEN Flatwall Enamel #800
Thinner: BOYSEN Paint Thinner

C. METAL SURFACES:
1. BOYSEN EPOXY ENAMEL
For ferrous surfaces such as all structural steel surfaces, steel railings, grilles, steel
louvers, roof framing components and other exposed steel surfaces unless otherwise
specified.
Surface Preparation: BOYSEN Masonry Neutralizer #44
1st Coat: BOYSEN Epoxy Red Lead Primer #2270 or
BOYSEN Zinc Chromate Primer #2260
2nd and 3rd Coats: BOYSEN Epoxy Enamel. Tint to get the required color.
Thinner: BOYSEN Epoxy Reducer

10.00 SPECIALTIES

10.01 TOILET ACCESSORIES:


A. Toilet Paper Holder: One (1) beside every water closet.
B. Soap Holder: One (1) set for each shower area

11.00 EQUIPMENT (NOT USED)

12.00 FURNISHINGS (NOT USED)

13.00 SPECIAL CONSTRUCTION (NOT USED)

14.00 CONVEYING SYSTEMS (NOT USED)

15.00 MECHANICAL / SANITARY

15.01 PLUMBING SYSTEMS:


A. PIPES AND FITTINGS:
1. COLD AND HOT WATER LINES: Polypropelene pipes and fittings, PN20 conforming
to DIN standards. Fittings shall be fusion weld type joints conforming to DIN standards
for polypropelene pipes and fittings.
2. SEWER AND WASTE PIPES:
SPECIFICATIONS
Page 17 of 20
_________________________________________________________________________________________

a) Main Lines and Stacks: Polyvinyl chloride (PVC) pipe, series 1000II, CROWN PIPE
or EMERALD brand or approved equal. Fittings shall be PVC with solvent cement
joint to ASTM D 1784.
c) Vent Pipes: POLYVINYL CHLORIDE PIPES AND FITTINGS Equivalent to Series
1000, Class 35, by EMERALD or approved equal.
3. STORM DRAINAGE SYSTEMS:
a) Downspouts: POLYVINYL CHLORIDE PIPES AND FITTINGS Equivalent to Series
1000, Class 35, by EMERALD or approved equal. Use gauge 40 black iron pipes for
3-meter lower portion of downspout connected to catch basins; epoxy-enamel
painted.
b) Storm Drainage: CONCRETE PIPES with sizes as required, conforming to Class
IV.1, reinforced for 300 mm Φ and larger.
4. AIR-CON DRAIN: POLYVINYL CHLORIDE PIPES AND FITTINGS, Equivalent to Series
1000, Class 35, by EMERALD with Elastomeric Closed Cell Insulation.

B. VALVES:
1. Valves: ASTM B-61 & 62, ASTM A 197, KITZ or approved equal. For gate valves and
check valves, cast brass, sizes as required in the drawings.
2. Gate valves and check valves for hydropneumatic pumps piping shall be tested at 150 psi
for a period of 2 hours. As required for rehabilitation of existing pump.
3. Rubber Seated Check valves for hydropneumatic pumps, use CLAYTON WAFER swing
check valve Model 501 or approved equivalent. As required for rehab of existing pump.
Size 2" diameter
Fits Flanges
Pressure Class 150 ANSI
Pressure Ratings 275 psi
Temperature Range Resilient vitron rubber seat 446 degrees F
Fluid Water
Standard Materials Valve Body -- Cast Iron ASTM A-48
Valve Trim -- Stainless Steel ASTM 304

C. TRAPS AND CLEANOUTS:


1. Cleanout plugs for PVC pipes shall be EMERALD or approved equal or cast brass ferrule
with countersunk tap screw cover.
2. Underground traps except P-traps on floor drains shall be provided with removable
cleanouts.

D. DRAINS: JPI or approved equal.


1. Roof Gutter - M-319-16, ASA or equal
2. Floor/Shower - M-210, ASA or equal
3. Cleanout - M-240, ASA or equal

E. FAUCETS: See Section 15450 Plumbing Fixtures.

F. HOSE BIBBS:
1. Hose Bibbs: Brass, made of male inlet threads, hexagon shoulder and three quarter inch
(20mm) hose connections.
SPECIFICATIONS
Page 18 of 20
_________________________________________________________________________________________

G. PIPE SLEEVES:
1. Wrought iron or steel pipe schedule 40 for sleeves in walls and partitions.
2. Steel pipe schedule 40 for sleeves in concrete beams or concrete fireproofing.
3. Galvanized steel pipe schedule 40 for sleeves through floors.
4. Steel pipe sleeves in footings shall be not less than four inches larger in diameter than the
pipe to be installed.
2
H. CATCH BASINS/JUNCTION BOXES: 140 kg/cm RC with C.I. grating cover M-452 E. In-
site and pre-cast reinforced slabs, with concrete hollow block walls, details as shown in the
drawings. For drain terminals discharge, and generally at all intersecting points of pipes.

I. OVERFLOW DRAIN: 50 mm dia. G.I. pipe with polished brass METMA hub adaptor M-685.

J. JOINTING:
Flanged Joint Gasket – GARLOCK or equal
Screwed Joints – U.S. Federal Specifications GG-P-251
PVC Pipes and Fittings – PVC cement or as per Manufacturer’s recommendations.
Dissimilar Pipes – Adopter fittings shall be used.
Concrete Drain Pipe – Cement mortar

NOTES:
1. The Plumbing Contractor shall supply and install water service entrance meter and
connection, all pumps and all tanks and their respective accessories, including steel
supports and anchors, and shall wire all pumps up to their respective breakers; and
pumps up to tank level controllers & float switches; test and commission.
2. The Electrical Contractor shall supply, install and wire all pump breakers to MDP.

15.03 15450: PLUMBING FIXTURES:

Note: Verify roughing in dimensions and installation procedures from manufacturer before
proceeding with final set of pipe inlets and mounting hardware.
PLUMBING FIXTURES:
A. WATER CLOSET: HCG, low consumption 6 lpf round front water closet, innoglaze finish,
with seat and cover, for all toilets. White color.

B. OVER-THE-COUNTER LAVATORY: HCG, Countertop Lavatory, innoglaze finish, white


color. Use Lever Faucet, chrome, with angle valve, steel braided flexible hose, strainer, P-
trap, and all other fittings to complete. For all applicable toilets.

C. WALL-HUNG LAVATORY: HCG, Wall-Hung Lavatory, innoglaze finish, white color. Use
Lever Faucet, chrome, with angle valve, steel braided flexible hose, strainer, P-trap, and all
other fittings to complete. For applicable toilets.

D. KITCHEN SINK: Stainless Steel, single drain bowl, with overall size of 560mm x 635mm
(22” x 25”). Provide DELTA or CASCADE Chrome finish single lever kitchen faucet with P-
trap, angle valves, strainers and all other fittings to complete.
SPECIFICATIONS
Page 19 of 20
_________________________________________________________________________________________

E. FLOOR DRAINS: METMA, M-200-D MAB, 100mm x 100mm (4” x 4”). For all floor drains.

16.00 ELECTRICAL

16.01 BASIC ELECTRICAL MATERIALS AND METHODS:


A. WIRES AND CABLES: PHELPS DODGE or approved equal. No conductor shall be less
than 3.5 mm2 in size unless otherwise specified.
B. CONDUITS: As indicated in the Electrical (E) Plans.
1. Non-metallic conduit (PVC): CS40 smooth wall non-metallic conduit conforming to
Philippine National Standards No. 14 for PVC Pipes. Conduit shall be in standard
length of 3.05 meters including coupling; EMERALD, NELTEX, MOLDEX, ATLANTA or
approved equal.
C. OUTLET BOXES AND FITTINGS:
1. Convenience Outlets: NATIONAL, CREAM COLOR, 220V, with amperage as required.
For general building interior use.
2. Weatherproofed Outlets: NATIONAL, double device plate with cover receptacle, heavy
duty. For outlets inside pump room and other exterior-located outlets, as indicated in
the plans.
3. Boxes: FUMACO metal utility boxes Ga. 16, sizes and shapes as required.
D. SWITCHES:
1. Switches: NATIONAL, JIMBO or MEIKOSHIA, cream color, with amperage as
required. Suited to location and intended purpose.

16.02 ELECTRICAL DISTRIBUTION SYSTEM


A. LIGHTING FIXTURES AND ACCESSORIES: Samples of lighting fixtures, complete with
lamps and accessories, shall be submitted for approval by the Owner prior to fabrication
and purchase.

1. DROP LIGHTS: All drop lights and chandeliers shall be for the approval of the Owner.
2. FLUORESCENT LAMPS: All pinlights, cove lights, and other fluorescent lamps shall
be OSRAM or approved equal.

Note: Luminaires of other brands as approved by the Architect are acceptable. Lamps and
electronic ballasts of G.E. or PHILIPS, approved by the Architect, are acceptable.
Submit sample for approval prior to purchase.

END