Architectural Specifications
Architectural Specifications
Architectural Specifications
SPECIFICATIONS
PROJECT OWNER:
CLENT ANDREY O. GALAMITON
PROJECT LOCATION:
LOT 18B BLK 8 AGUILA ST., GATCHALIAN SUBD., BRGY. MANUYO DOS,
LAS PINAS
1.03 SPECIFICS
Materials specifically mentioned in this Summary shall be installed following efficient and sound
engineering and construction practice, and especially as per manufacturer's application for
installation specifications which shall govern all works alluded to in these Specifications.
2.00 SITEWORK
2.02 EARTHWORK
A. FILL MATERIALS
1. General Fill for structures and under spread footings, pavers, or concrete slabs on
grade shall conform to the general requirement for soil materials above and shall be
classified as GW, GM, GP, SW, SM by the ASTM 2487 and conform to the following.
a. Liquid Limit – shall not exceed 25% when tested in accordance with ASTM 423.
b. Plasticity Index – shall not exceed 12 % when tested in accordance with ASTM
424.
c. Under Buildings, no more than 25% by weight shall be finer than No. 200 sieve
when tested in accordance with ASTM D 1140.
2. Granular Fill shall conform to the general requirements for soil material above and shall
be clean, crushed stone or gravel conforming to ASTM C 33, size 67 and with a sand
equivalent of not less than 50% when tested in accordance with ASTM D 2419.
3. Backfill material behind walls shall consist of free-draining granular fills, sized in
particular to provide a filter media around subsoil drainage system.
4. Drainage Fill: Fill material shall clean, well graded, free draining sand conforming to
ASTM C 33 for Fine Aggregate.
5. Borrow: If additional material is required for fill in excess of that obtained by
excavation at the site, obtain same from sources acceptable to the Civil/Structural
Engineer’s specifications. All arrangement for obtaining borrow from off site shall be
the responsibility of the Contractor and all cost thereof shall re borne by the Contractor.
Acceptable borrow will consist of suitable material for fills as herein before specified.
Representative of each type of borrow materials considered suitable shall be delivered
to the Testing Laboratory and tested prior to placement. Any borrow material not
meeting the standard herein specified, or considered unsuitable by the Owner’s
Engineer will be rejected at the site.
B. RIPRAP: Rock Boulders, natural, hard rock, high density, from 400 mm to 800 mm in
diameter.
C. Batterboards: Second class, pest free lumber assembled and rendered secure for proper
delineation of building lines and grades.
SPECIFICATIONS
Page 3 of 20
_________________________________________________________________________________________
B. CONCRETE AGGREGATES
1. Aggregates shall be well-graded, clean, hard particles or gravel or crushed rock
conforming to the STANDARD SPECIFICATION FOR CONCRETE AGGREGATES
(ASTM Designation C-33: latest revision).
2. SAND: shall be coarse sand free from injurious materials such as shells or earth or
organic materials. Sand from salt water is not allowed.
C. WATER: shall be clean and free from injurious amounts of oils, acids, alkali, organic
materials or other deleterious substances.
2.06SITE DRAINAGE
A. DRAINAGE PIPE:
1. Plain concrete drain pipe and fittings 250 mm (10") and below in diameter: T & G
conforming to ASTM C-14-59.
2. Reinforced concrete pipes fittings 300 mm (12”) and bigger: Centrifugally cast or
vibrated T & G conforming to ASTM C-76-59 T.
C. BUILDING STORM DRAIN CONNECTION TO MAIN: Concrete wye branch and clean out,
T & G or use junction boxes.
D. AREA DRAIN CATCH BASIN: Load-bearing 4.8 Mpa (700 PSI) concrete hollow blocks
(CHB) or reinforced concrete with cover as show on the drawings.
SPECIFICATIONS
Page 4 of 20
_________________________________________________________________________________________
E. CATCH BASINS OF JUNCTION BOXES: Load-bearing 4.8 Mpa (700 PSI) concrete hollow
blocks (CHB) or reinforced concrete as indicated in the drawings, with solid reinforced
concrete cover.
3.00 CONCRETE
B. TIE WIRES: Use Ga.16 Galvanized Iron (G.I.) tie wires at joints or laps of placed
reinforcements.
B. CEMENT:
Cement shall be Portland cement, conforming to the Standard Specifications for Portland
Cement (ASTM Designation C-150 latest revision) for type 1 Portland Cement. Use only one
brand of cement throughout.
C. FINE AGGREGATES:
Fine aggregates shall consist of natural sand, manufactured sand, or a combination thereof. If
the fine aggregate shall be a combination of separately processed sizes, or if hatching shall
result in a combination of natural and manufactured sand, the different components shall be
batched separately.
Fine aggregates shall consist of hard, tough, durable, uncoated particles. The specified
percentages of fines in the sand may be obtained either by the processing of natural sand or
by the production of a suitably graded manufactured sand. The shape of the particles shall be
generally rounded or cubical and reasonably free from flat or elongated pieces. The use of
SPECIFICATIONS
Page 5 of 20
_________________________________________________________________________________________
beach sand shall be prohibited. The fine aggregate shall conform to the following specific
requirements:
Sieve Designation
Standard (MM) U.S. Standard, Cumulated Percentage by
Square Mesh Weight Passing
In addition to the grading limits shown above, the fine aggregates, as delivered to the mixer
shall have a fineness modulus of not less than 2.3 nor more than 3.0 and during normal
operations, the grading of the fine aggregate shall be controlled so that the fineness modulus
of at least nine (9) of ten (10) test samples of the fine aggregate as delivered to the mixer shall
not vary more than 0.20 from the average fineness modulus of all samples tested during the
preceding 30-day period. The fineness modulus can be determined by dividing by 100 the
sum of the cumulated percentages retained on U.S. Standard Sieves Nos. 4, 8, 16, 30, 50 and
100. At the option of the Contractor, fine aggregates may be separated into two or more sizes
or classification, but the resulting combined sand shall be of uniformed grading within the limits
specified above. It can be generally assumed that a fine blending sand maybe required to
meet the above grading.
D. COARSE AGGREGATES:
Coarse agreement shall consist of gravel, crushed gravel or rock, or a combination thereof.
The coarse aggregate as delivered to the batching plant shall have a uniform and stable
moisture content. The approval of deposits shall not be construed as constituting the approval
of all the materials taken from the deposits and the Contractor shall be held responsible for
the specified quality of all such materials used in the work. Coarse aggregate shall consist of
hard, tough, durable, clean and uncoated particles. All foreign materials and dust shall be
removed by adequate processing. The particle shape of one of the smallest size of crushed
coarse aggregate shall be generally rounded or cubical, and the coarse aggregate shall be
reasonably free from flat and elongated particles. A thin, flat and elongated particle can be
defined as a particle having a maximum dimension greater than five times the minimum
dimension. The coarse aggregate shall be well graded from fine to coarse. It shall be
separated into size groups.
The grading of the aggregate within the separated size groups as delivered to the mixer shall
be as follows:
Sieve Sizes
Standard U.S. Std. Sq. Percent by Weight Passing Individual
(MM) Mesh Sizes 1-1/2" 3/4"size
50.00 2" - 100
37.50 1-1/2" - 90-100
25.00 1" 100 20-55
19.00 3/4" 90-100 0-15
SPECIFICATIONS
Page 6 of 20
_________________________________________________________________________________________
- Use 19mm (3/4) coarse aggregate for slab on grade, columns, beams, suspended
slabs, tie beams.
- Use 38mm (1 1/2") coarse aggregate for footings
E. WATER:
Water shall be clean and free from injurious amounts of oils, acids, alkalis, salts and organic
materials, or other substances that may be deleterious to concrete or steel.
F. ADMIXTURES: shall be subject to prior approval by the Engineer. The admixtures shall be
capable of maintaining essentially the same composition and performance throughout the
work.
1. Plasticizing admixtures shall be free from chlorides and shall conform to ASTM C494. The
admixtures shall be used in concrete mixtures in accordance with the manufacturer's
instructions.
2. Air-entraining admixtures, accelerators, water reducing retarders shall comply with
Section 03400.
3. Integral Waterproofing Compound - SIKA or approved equal. For canopy slab. Use one
kilo pack per forty kilo bag of Portland cement.
4. Calcium chloride is not allowed. Secure approval of the Engineer prior to using of any
other additive.
NOTE: PLACEMENT DRAWINGS: Shop drawings of each reinforcing steel detail and
placement drawings shall be submitted for approval in accordance with the requirements of the
General Conditions. Any material fabricated before final approval of the shop drawings will be
done at Contractor's risk, but no material shall be placed until shop drawings have final
approval. Shop drawings shall be in accordance with the "Manual of Standard Practice for
Detailing Reinforced Concrete Structures" (ACI 315).
B. REINFORCING MATERIALS:
1. Reinforcing bars: ASTM A 615M, Grade 400, deformed.
2. Steel-Welded Wire Fabric: ASTM A 185, plain, cold drawn.
C. CONCRETE MATERIALS:
1. Portland Cement: ASTM C 150, Type 1. Use only one brand, type, and color of cement
from the same mill throughout Project.
SPECIFICATIONS
Page 7 of 20
_________________________________________________________________________________________
2. Normal-Weight Aggregates: ASTM C 33, with coarse aggregates meeting Class 5S and
MNL-117 requirements.
a) Face-Mix Coarse Aggregates: Selected, hard, and durable; free of materials that reacts
with cement or causes staining. Uniformly graded.
b) Face- Mix Fine Aggregates: Selected, natural or manufactured sand of the same
material as coarse aggregate, unless otherwise acceptable to the Architect.
3. Coloring Agent: C 979, synthetic, mineral oxide pigments or colored water-reducing
admixtures, color stable, non-fading, resistant to lime and other alkalis.
4. Water: Potable; free from deleterious material that may affect color stability, setting, or
strength of concrete.
5. Air-Entraining Admixture: ASTM C 260, certified by manufacturer to be compatible with
other required admixtures.
6. Water-Reducing Admixture: ASTM C 494, Type A.
7. Retarding Admixture: ASTM C 494, Type B.
D. CONNECTION MATERIALS:
1. Steel Shapes and Plates: ASTM A 36M.
2. Malleable Iron Castings: ASTM A 47M
3. Carbon Steel Plates: ASTM A 283M.
4. Carbon-Steel Bolts and Studs: ASTM F 568, Property Class 4.6; carbon-steel, hex-head
bolts and studs; carbon-steel nuts; and flat, unhardened steel washers.
5. Welded Headed Studs: AWS D1.1, Type B headed studs, cold-finished carbon-steel bars.
6. Deformed-Steel Wire Bar Anchors: ASTM A 496.
7. Welding Electrodes: Comply with AWS standards.
8. Accessories: Provide clips, hangers, plastic shims, and other accessories required to
install architectural pre-cast concrete units.
E. BEARING PADS: Elastomeric pads; AASHTO M 251, plain, vulcanized, 100 percent
polychloroprene (neoprene) elastomer, molded to size or cut from a molded sheet, 50 to 70
shore A durometer, minimum tensile strength 15.5 Mpa (2250 psi) per ASTM D 412.
F. GROUT MATERIALS: Cement Grout; Portland cement, ASTM C 150, Type 1, and clean,
natural sand, ASTM C 404. Mix at ratio of 1 part cement to 2-1/2 parts sand, by volume, with
minimum water required for placement and hydration.
G. CONCRETE MIXES:
1. Normal-Weight Concrete Face and Back-Up Mixes: Proportion mixes by either laboratory
trial batch or field test data methods according to ACI 211.1, using materials to be used on
the Project, to provide normal weight concrete with the following properties:
a) Compressive Strength (28-day): 20.7 Mpa (3000 psi).
b) Maximum Water-Cement Ratio at Point of Placement: 0.40.
2. Lightweight Concrete Back-Up Mixes: Proportion mixes by either laboratory trial batch or
field test data methods according to ACI 211.2, using materials to be used on the Project,
to provide lightweight concrete with the following properties:
a) Compressive Strength (28-day): 34.5 Mpa (5000 psi).
b) Unit Weight: Calculated equilibrium unit weight of 1842 kg/cum (115 lb/cuft), plus or
minus 48 kg/cum (3lb/cuft), according to ASTM C 567.
SPECIFICATIONS
Page 8 of 20
_________________________________________________________________________________________
4.00 MASONRY
B. SAND: ASTM C 35 – 67, clean, washed river sand, strong, free from organic and other
deleterious materials. Sand from salt water or lahar is not allowed.
C. WATER: Fit for drinking, free from injurious amount of oil, acids, alkali, organic materials
and other deleterious substances.
E. ADHESIVE MORTAR: Use ABC ADHESIVE MORTAR for laying vitrified ceramic tiled with
ABC DISPERSION COMPOUND as an additive to ABC ADHESIVE MORTAR.
F. GROUT: Use ABC GROUT pre-mixed dry wall filler for floor and wall tile joints either
glazed or semi-glazed tiles. Masonry concrete grout compressive strength ( fc’ ) = 13.8
Mpa (2000 psi). For kitchen, toilet works and tile works.
G. PLASTER BOND: Plaster Bond: N & H PLASTER BOND or approved equal. Apply on all
wall areas prior to plastering.
B. REINFORCING BARS: Masonry reinforcing steel yield strength (fy) =228 Mpa (33,000 psi),
Grade 33 bars, conforming to ASTM Specifications A615 / PNS 49 of sizes shown in Plans.
Use standard sizes; upgrade to next bigger size if specified standard sizes are unavailable.
5.00 METALS
B. HIGH STRENGTH BOLTS, NUTS AND WASHERS: Conform bolts to the Specification for
High Strength Bolts ASTM A 325, Type 1 . See structural connection details for location of
bearing-type and friction-type bolts.
E. GROUT: Conform all non-shrink grout to ASTM C827. Grout shall be non-metallic, non-
shrink, flowable cementitious grout. Apply using manufacturer’s standards strictly.
F. STRUCTURAL STEEL PRIMER PAINT: Epoxy zinc chromate primer except as otherwise
recommended by the manufacturer of the coating for all structural steel surfaces.
B. BRACING RODS: Use standard structural grade steel rods with turnbuckles whenever
required, for roof framing.
SPECIFICATIONS
Page 10 of 20
_________________________________________________________________________________________
C. PAINTING: Use only approved brand of epoxy zinc chromate paint and linseed oil for all
architectural steel components only. For field painting, use only approved brand of enamel
paint.
D. STAINLESS STEEL: Pipes, tubes, square bars, and other sections shall be provided with
appropriate guarantee.
1. Roof Gutter: Whenever necessary, 1.2 mm (gauge 18) thick, Stainless Steel Sheets,
Type 304 bent to design shape.
2. Main and Side Entrance Ramp and Step Railing: SS Pipes, Gauge 40, of sizes as
indicated in Plans and details.
3. RC Precast Anchors: 10mm Stainless Steel Plain Bars
E. GALVANIZED IRON:
1. Minor Ramp and Step Railing, Exterior and Interior Ledge Railing shall be Gauge 40,
of sizes as indicated in Plans and details, finish with Epoxy Enamel Paint.
Note: Upgrade to next bigger size if specified standard sizes are unavailable.
2. Yard Hose Bibbs: G.I. Pipes, Ga. 40, painted with Epoxy Enamel Paint.
a. Hangers: Gauge 10 G.I. wire hanger.
F. FASTENINGS: Commercial types, except where special types are shown or required.
Fastenings for all exterior work shall be non-ferrous, unless otherwise shown. Fastening for
stainless steel and aluminum and other interior work, where exposed shall match the
fastened metal.
0: STEEL DECK
6.00 WOOD AND PLASTICS
C. Dampproofing: vapor barrier, one layer at six mils (0.006) thick. For slabs on fill at the
building interior. Provide 300 mm overlapping.
B. Use Co-Polymer Clear Sealant for roofs, awnings, roof flashings, skylights, gutters and
downspouts.
C. Use Solvent-Based Synthetic Rubber Contact Type Adhesive for bonding wood, plastic
laminate, concrete, steel aluminum and hardwood, rubber and glass.
SPECIFICATIONS
Page 12 of 20
_________________________________________________________________________________________
D. Use Acrylic Latex Gap Sealant for use between windows or door frames and walls, along
skirting boards, around cornices, between countertops and splashboard. In corner or
between the wall and ceiling or where shrinkage or movement causes rigid fillers to crack.
E. Use Acid Cure Silicon for use on non-porous surfaces such as glass, ceramics and
porcelain.
B. DOOR LOCKS AND LOCKSETS: HAFELE, or approved equal. Note: Provide 4 pcs Master
Keys for all cylindrical locksets and deadbolt locking device.
1. Cylindrical Locksets:
a) For entrance doors and bedrooms: Satin chromium finish. Turn-button locking in
inside knob; requires use of key at all times until button is manually restored to
unlock position.
b) For all toilet doors: Satin chromium finish. Push button locking in inside knob. Can
be opened from outside by screwdriver or similar tool or by turning inside knob.
2. Deadbolts: Satin chromium finish, heavy duty deadbolt thrown or retracted by key from
outside or by inside turn unit. Bolt automatically deadlocks when fully thrown.
C. HINGES:
SPECIFICATIONS
Page 13 of 20
_________________________________________________________________________________________
1. 88.5 mm x 88.5 mm, (3-1/2” x 3-1/2”) plain bearing, stainless steel, loose pin or fixed
pin, button tip, four (4) pieces per door panel
E. DOOR STOP / DOOR HOLDER: Chrome finish, floor / wall mounting. Attached securely
to floor / wall to prevent door knob from hitting the wall.
8.05 GLAZING
As manufactured by REPUBLIC GLASS CORPORATION or approved equal.
A. RAGC CLEAR FLOAT GLASS: 6 mm (1/4 inch) thick. For all aluminum doors and
windows; must be able to withstand a Design Wind Velocity of 250 km/h.
B. DECORATIVE MIRRORS: 6 mm (1/4”) thick plate glass mirror, distortion-free with felt
paper on 6 mm (1/4”) thick Weatherproof Marine Plywood backing installed on satin-finish
anodized aluminum frame. For toilets. (Owner-supplied and installed)
d
C. BULK COMPOUND FOR GLASS INSTALLATIONS:
1. Mastics – Elastic compounds and non-skinning compound.
2. Putties- Wood sash putty, metal sash putty.
3. Sealants – one component, two components.
D. PREFORMED SEALANTS:
1. Synthetic Polymer – base sealants – resilient or non-resilient type.
2. Pre-formed gaskets – compression type, structural type.
E. CAULKING: Silicon Building Sealant or approved equal. For all joint gaps between
aluminum frames and concrete.
9.00 FINISHES
9.01 PLASTER
A. PLAIN CEMENT PLASTER FINISH: Consisting of the scratch and finish coats, both
consisting of one (1) part Portland cement and two (2) parts of clean, washed sand,
measured by volume. For all interior and exterior wall surfaces where plastering is
essential to complete the work.
B. SMOOTH RUBBED FINISH: For all exposed undersides of suspended floor RC slabs and
beams.
C. TOOLED JOINT FINISH: Surface preparation shall be plain cement plaster finish with
tooled mortar joints. Joints shall be concave, clean, plumb and true to line. All joints shall
be spaced as directed by the Architect.
SPECIFICATIONS
Page 14 of 20
_________________________________________________________________________________________
C. Metal Ceiling Assembly: Use 19mm x 50mm x 0.4 mm thick G.I. furring channel and 0.6
mm thick J-type-wall angle with 12mm x 38mm x 1.0 mm thick G.I. carrying channel, 6
mm diameter hanger rod, suspension clips, rod joiners, steel angles, furring clips, fastening
devices and others to complete. Submit mock-up on site, with ceiling boards, before
installation.
9.04 TILES
A. VITRIFIED CERAMIC TILES: Use one brand from same batch throughout for each
type/size:
1. 600mm x 600mm Floor Tiles - Use MARIWASA, EUROTILES (Philippines) or
approved equal, in colors approved by the Owner, for living, dining, kitchen and
bedroom floors and as shown in the drawings.
2. 300mm x 300mm Floor Tiles – Use MARIWASA, EUROTILES (Philippines) or
approved equal, in colors approved by the Owner, for toilet floors and as shown in the
drawings.
3. 300mm x 300mm Wall Tiles - Use MARIWAS, EUROTILES (Philippines) or approved
equal, in colors approved by the Owner, for toilet walls, for all troughs and as shown in
drawings.
Finish shall be clean, plumb and true to line. Use ABC Grout from all ALLGEMEINE-BAU-
CHEMIE (ABC) PHIL., INC. only.
B. ADHESIVE, GROUT AND SEALANT: Use ABC Adhesive, ABC Grout (color coordinated
as required) and ABC Sealant from all ALLGEMEINE-BAU-CHEMIE (ABC) PHIL., INC., or
approved equal.
SPECIFICATIONS
Page 15 of 20
_________________________________________________________________________________________
C. TILE TRIM: Use plastic tile trim to cover all exposed tile joints; color-coordinated as
required.
9.06 PAINTING :
Use BOYSEN PAINTS only (one brand all throughout). All exposed finish hardware, lighting
fixtures and accessories, plumbing fixtures and accessories, glass surfaces and the like shall
be adequately protected against stains from paint and other painting materials prior to painting
works. All other surfaces which would be endangered by stains or paint marks should be taped
and covered with craft paper or equal.
A. EXTERIOR:
1. PERMACOAT SEMI-GLOSS LATEX, for all concrete/masonry surfaces; concrete
parapets and fascias; spandrel walls; underside of concrete ledges, exposed sides of
retaining walls, concrete railing of ramps, stepped platform at atrium and all other
minor surfaces unless otherwise specified.
Surface Preparation: BOYSEN Masonry Neutralizer #44
1st Coat: BOYSEN Permacoat Concrete Sealer #705 White or
BOYSEN Permacoat Latex #701 White.
Putty minor cracks and surface imperfections with
BOYSEN Patching Compound
2nd and 3rd Coats: BOYSEN Permacoat Semi-Gloss Latex #715
Tint to get the required color with BOYSEN Latex Colors.
B. INTERIOR:
1. PERMACOAT SEMI-GLOSS LATEX, for all interior concrete & masonry walls;
exposed beams, girders and ceiling surfaces; FCB wall and column surfaces; for walls
above toilet tiles; for gypsum board surfaces and all other miscellaneous concrete
areas unless otherwise specified.
Surface Preparation: BOYSEN Masonry Neutralizer #44
1st Coat: BOYSEN Permacoat Concrete Sealer #705 White or
BOYSEN Permacoat Latex #701 White.
Putty minor cracks and surface imperfections with
BOYSEN Patching Compound
2nd and 3rd Coats: BOYSEN Permacoat Semi-Gloss Latex #715
Tint to get the required color with BOYSEN Latex Colors.
2. BOYSEN CLEAR DEAD FLAT LACQUER #1253
For all exposed interior wood surfaces, where applicable.
Surface Preparation: BOYSEN Wood Paste Filler #60 or
BOYSEN Lacquer Wood Tite #61
SPECIFICATIONS
Page 16 of 20
_________________________________________________________________________________________
C. METAL SURFACES:
1. BOYSEN EPOXY ENAMEL
For ferrous surfaces such as all structural steel surfaces, steel railings, grilles, steel
louvers, roof framing components and other exposed steel surfaces unless otherwise
specified.
Surface Preparation: BOYSEN Masonry Neutralizer #44
1st Coat: BOYSEN Epoxy Red Lead Primer #2270 or
BOYSEN Zinc Chromate Primer #2260
2nd and 3rd Coats: BOYSEN Epoxy Enamel. Tint to get the required color.
Thinner: BOYSEN Epoxy Reducer
10.00 SPECIALTIES
a) Main Lines and Stacks: Polyvinyl chloride (PVC) pipe, series 1000II, CROWN PIPE
or EMERALD brand or approved equal. Fittings shall be PVC with solvent cement
joint to ASTM D 1784.
c) Vent Pipes: POLYVINYL CHLORIDE PIPES AND FITTINGS Equivalent to Series
1000, Class 35, by EMERALD or approved equal.
3. STORM DRAINAGE SYSTEMS:
a) Downspouts: POLYVINYL CHLORIDE PIPES AND FITTINGS Equivalent to Series
1000, Class 35, by EMERALD or approved equal. Use gauge 40 black iron pipes for
3-meter lower portion of downspout connected to catch basins; epoxy-enamel
painted.
b) Storm Drainage: CONCRETE PIPES with sizes as required, conforming to Class
IV.1, reinforced for 300 mm Φ and larger.
4. AIR-CON DRAIN: POLYVINYL CHLORIDE PIPES AND FITTINGS, Equivalent to Series
1000, Class 35, by EMERALD with Elastomeric Closed Cell Insulation.
B. VALVES:
1. Valves: ASTM B-61 & 62, ASTM A 197, KITZ or approved equal. For gate valves and
check valves, cast brass, sizes as required in the drawings.
2. Gate valves and check valves for hydropneumatic pumps piping shall be tested at 150 psi
for a period of 2 hours. As required for rehabilitation of existing pump.
3. Rubber Seated Check valves for hydropneumatic pumps, use CLAYTON WAFER swing
check valve Model 501 or approved equivalent. As required for rehab of existing pump.
Size 2" diameter
Fits Flanges
Pressure Class 150 ANSI
Pressure Ratings 275 psi
Temperature Range Resilient vitron rubber seat 446 degrees F
Fluid Water
Standard Materials Valve Body -- Cast Iron ASTM A-48
Valve Trim -- Stainless Steel ASTM 304
F. HOSE BIBBS:
1. Hose Bibbs: Brass, made of male inlet threads, hexagon shoulder and three quarter inch
(20mm) hose connections.
SPECIFICATIONS
Page 18 of 20
_________________________________________________________________________________________
G. PIPE SLEEVES:
1. Wrought iron or steel pipe schedule 40 for sleeves in walls and partitions.
2. Steel pipe schedule 40 for sleeves in concrete beams or concrete fireproofing.
3. Galvanized steel pipe schedule 40 for sleeves through floors.
4. Steel pipe sleeves in footings shall be not less than four inches larger in diameter than the
pipe to be installed.
2
H. CATCH BASINS/JUNCTION BOXES: 140 kg/cm RC with C.I. grating cover M-452 E. In-
site and pre-cast reinforced slabs, with concrete hollow block walls, details as shown in the
drawings. For drain terminals discharge, and generally at all intersecting points of pipes.
I. OVERFLOW DRAIN: 50 mm dia. G.I. pipe with polished brass METMA hub adaptor M-685.
J. JOINTING:
Flanged Joint Gasket – GARLOCK or equal
Screwed Joints – U.S. Federal Specifications GG-P-251
PVC Pipes and Fittings – PVC cement or as per Manufacturer’s recommendations.
Dissimilar Pipes – Adopter fittings shall be used.
Concrete Drain Pipe – Cement mortar
NOTES:
1. The Plumbing Contractor shall supply and install water service entrance meter and
connection, all pumps and all tanks and their respective accessories, including steel
supports and anchors, and shall wire all pumps up to their respective breakers; and
pumps up to tank level controllers & float switches; test and commission.
2. The Electrical Contractor shall supply, install and wire all pump breakers to MDP.
Note: Verify roughing in dimensions and installation procedures from manufacturer before
proceeding with final set of pipe inlets and mounting hardware.
PLUMBING FIXTURES:
A. WATER CLOSET: HCG, low consumption 6 lpf round front water closet, innoglaze finish,
with seat and cover, for all toilets. White color.
C. WALL-HUNG LAVATORY: HCG, Wall-Hung Lavatory, innoglaze finish, white color. Use
Lever Faucet, chrome, with angle valve, steel braided flexible hose, strainer, P-trap, and all
other fittings to complete. For applicable toilets.
D. KITCHEN SINK: Stainless Steel, single drain bowl, with overall size of 560mm x 635mm
(22” x 25”). Provide DELTA or CASCADE Chrome finish single lever kitchen faucet with P-
trap, angle valves, strainers and all other fittings to complete.
SPECIFICATIONS
Page 19 of 20
_________________________________________________________________________________________
E. FLOOR DRAINS: METMA, M-200-D MAB, 100mm x 100mm (4” x 4”). For all floor drains.
16.00 ELECTRICAL
1. DROP LIGHTS: All drop lights and chandeliers shall be for the approval of the Owner.
2. FLUORESCENT LAMPS: All pinlights, cove lights, and other fluorescent lamps shall
be OSRAM or approved equal.
Note: Luminaires of other brands as approved by the Architect are acceptable. Lamps and
electronic ballasts of G.E. or PHILIPS, approved by the Architect, are acceptable.
Submit sample for approval prior to purchase.
END