Internal Wiring Systems and Lamp Circuits: After The Main
Internal Wiring Systems and Lamp Circuits: After The Main
Internal Wiring Systems and Lamp Circuits: After The Main
-Th
7
Internal Wiring Systems and
Lamp Circuits
(a) Looping out from switch and ceiling Rose. Fig. 7.1
shows a simple looping in method which is commonly employed. It
will be seen that one terminal of the ceiling roses and switches is
connected to the wires coming from the main switch and other
terminals of both are connected to each other. The system is similar
even if the light point is to be provided with a batten or bracket
holder intend of pendant holder. In that case one terminal of the
holders is commonly connected to the neutral and other terminal of
each is connected to the live wire or phase through a switch as shown
in Fig. 7.2.
FIEX/5L5
FOR
CIF)LIA'(9
PENDANT
LAMP/ROSE
NEUTRAL \
TOt/EXT
HALF OR CEILING
/ OFF WIRE ROSE AND
FL/SE ON SWITCH
PHASE
PHASE OR
WIRE
FuSE ,
L2) HALF OR
W/R
PHASE 1T0 NEXT
BA TTEN I
I 1/CL DER
K
1III
SWITCHES AND
TFJ
WIREW/TCN
P1/ASEO
L15
I
A'EIITR.4L_1
I
FL X/8L. E -
CiI.CTOR
L / MP
;.•E'TnAL
:7.
70 ,vCX 7.
--
PHASE OR
LIVE WIRE
,V..f Li TR40
TO ;'Lx r
CEO IN G
ROSE
FUSE ON
PHA SE
O TER..'y..'
-; O•'s CDIINEOTOP OR P&4 '17
TEIL,'cV5 P(YSE
.c Wi rcg
\Vn-ing with two terminals and one connector ceiling rose
Fig. 74
(d)
Looping out with Junction box. In this system pair of
conductor from the s.vitches and ceiliig roses will terminate in
box krxon asjunctioo box. The junction box is
kept in the centro
of all light PomtE fcr the economy in
wire icagth. This system is
only economical in small houses having few lighting
p oints because
the looping is only done in the joint box as shown in Fig. 7.5.
4. Wiring of a Building. Fig. 7.6 shows the wiring of a hou'
.vith srige phase A.C.
or two wire D.C. supply. From the main
INTERNAL WIRING SYSTEMS AND LAMP CIRCUITS 185
)ToNExr
Pt?/NT
CEILING
J ROcE
-F EX/&E
9R PENDANT
A LAMP
OR
Wh'5
BOX WI 7W
THREE
TERMINALS
Swirai
i
Ir -
Fig. 7.5 Looping out with Junct on Box
THIRD FLOOR
SUB-BOARD
AND
5113-CIRCUITS i
_
7T L
r - --
SECOND FLOOR
5I8-8a4RO
AND
H
FR5TF1OQR C— 't '! 1
5/88OARO I
AND
Sa-CIRCLII IS ____ T TEl1
GROUND FLOOR
S5-8OARO L RCU1T5
SUB-C/RCL/i 15
FOR G'QUNO
FLOOR
MAINS
4JN D/STRJ&/T/0I?
FL'5 BOARD
MAIN SW/7.CN&+qEUTRAL LJA/(
Fig. 7.6
186
WIRING, ESTThIAT]NG AND COSTING
switch the leads known as rrins are taer
to main distribution
board. From the main distributu beard wras ae taken to various
distribution boards whicn are known 3s sib-L..ards The
connec-
tions between the main distribution hoard and sub-boards are
known as circuits. Various su5 -circu its as shown are drawn from
the sub-boards for connection to various ei:L-i: load p c int
The
uiringofthe points is dofle by an y of the me:h..d explained in article
3. For the purpose of reliability and safety, the fusing current
capacity of the fuse wire inserted at the mar sv : itch should be 1.5
times the numerical sum of the afl loads. Sirnflar principle is to be
adopted while inserting fuse in circuits and sub-circuits. The wire
size of the mains circuits and sub-circuits shauld be in accordance
with the electric toads on them. For econo:ny, the bigger size of the
wire is used for sub-circuits in the beginning and later on small size
of wire matching the load is used.
Fig. 7.7 showthe wiring of
a building with three-phase four-
wire A.C. source without any main board.
co
AiO 5c'd-cu'y
SECONO FL .;o.
CIRC,! 7
fIRST
L..JAND 5418-CIRCJ,71;
RJIJk
INTERNAL WIRING SYSTEMS AND TAMP CIRCUITS 187
5EOONO FLOOR
CENTRAL
TO SECC SUE -8CARO
FL O(,' VIES T
I F/Psi. FLOOR
,.ORTII 5V3-BCAR
ro FIRST FLOOR
CE/I TP2 L 4/ID
WEST- SUB 80,4R)
RI5/N—.
MAINS
6RUU1/O FL cUR
AZPR7,W
S tJI-8OA".) J8-8CARO
5L'81,4ISCAR0
CROt VU FOCR
TO NO
MAIN 5iTC F/CUR W TS T
TRIPPLE r St9-BG.4R0
POLE WITH
NEUTRAL
L/N ___
1WRCE PHASE
FOUR WIRE
SUFVLY
The rising mains are usually provided in the centre of the 1od for
the purpose of economy. At each floor rising mains are connectcd
to sub-main boards as shown in Fig. 7.8. Various circuits are taken
from the nb-main board to sub-board. Sub-circuits are taken from
the sub-boards. The sub circuits are used for wiring the portion of
the load in accordance with the method explained in articles 3 and
.4.
6
Ring System. In this systems a pair of conductors are run
through all the rooms. The ceiling roses, plugs and appliances are
fitted after decision on the layout of furniture is taken. The ring
circuits is brought back to the main board. With this system, wiring
is required to be done with suitable fuse in each plug and ceihr.g
roses if the both ends of the conductors are ending on the same main
sub-hoard. There may be saving of Copper because the current can
be fed from both sides, but the method is not used because of higher
cost of the special plugs and ceiling roses. -.
Sometimes the main boards are connected to two diflèren
switches of suitable capacity. The both ends of the ring circits
terminate ma separate switch. One of the switches is always he;t
in off-position. This reduces the cost of the special type of plug a.d
ceilin g, roses and also increases the reliability.
7. Lamp Circuits. The lamp circuits used for house ring
are quite simple and they are generally controlled from one
_Iclias roorr(lighting, bathroom lighting, lavatory lighting etc ;but.
in staircase wiring it is necessary to control the lamp circuit fron
two points, .e. at the top and bottom of the staircase. Similarly in
halls or corridors or bedrooms, it may be necessary to contro jh'
lamp from more than two points. But still there are other circuits
which are not frequently used for particular house wiring, but still
they ha'e utility in other spheres of life. In general the lamp circuits
can be d:vided into the following heads
(1) Simple Circuits.
(2 Series Parallel Circuits.
(3) Master Switch Circuits.
(4) Pilot Circuits.
(5) Miscellaneous Circuits.
8. Simple Circuits. In addition to the lamp circuits
explained in article 3,.the following are commonly used
(a) Bed-rooii Lighting. In bed-rooms a light is required at the
dressirg table which may be a single switch circuit, and another
light provided near, the bed must be controlled by two 2-way
swtchs. One of the two-way switches used should be a tumbler
INTERNAL WIRING SYSTEMS AND LAMP CIRCUITS 189
C
£cp Tc
3('C ';Pc
Spv
7) pe v C/.
Circuit for bed-room lighting
Fg79
b) Staircase wirngorlamp circuit controlled by tuo i
For the lamps to he controlled by two switches, it is necessars. to, ue
two-way switches. Fig. 7.10 (a) shows that the lamp is dark. Tc
WjrtS used between the switches are called as strap wires.
In Fig. 7.10 (b) the lamp is switched on with the switch No. 1,
while Fig. 7.10 (c) represents that the lighted lamp is switched off
with switch No. 2 and in Fig. 7.10(d) the lamp is again lighted with
switch No. 1. Thus when the lamp is lighted either off the strap
wires carries current.
SL'. pf
(a)
Lamp made off with switch No. 2
Fig. 7.10.
V,flNC EST1MATG AND COSTThG
2 -
..,'
(b)
Lamp made on with
No. 1
—7—_'/
No
2w
Aci
(c)
S howing lamp dark
L.
2w07 —"ck?
is used; but for wiring between terminal box and either of the 2-way
switches 3-core cable is used.
frffTc
Way
L
L mp circuit controlled by single-way switch
(ci)
Fig. 7.12.
circuit being controlled by a single-way switch. For conversion the
single-way switch is removed and is replaced by a two-way switch.
Now if the connections to the two 2-way switches are made in a
similar manner as in the previous cases, then it is necessary to have
a joint at the point shown in Fig. 7.12 (b). A revised method of
connecting two switches is as shown in which case no jointing of
wires is required. -
-14
192 WflUNG, ESTP.ATiNG ANL) COSTThC.
2y
Switch
2 Wy
Switch
5W14v,
^tD6
r.
There is an a1ternatvc i'conv ia which case one
of the two-way switch*" , De har 4 terminals, two of
which are shorted toget in Fig. 13.
E)
Corridor lighting
Fig. 7.14
9. Series Parallel Circuits. Series parallel circuits are
to either provide dim lights or full bright lights. Such lights are
required in hospitals, bedrooms, hotels, railway carriages etc. The
dim lights are usually obtained by con nec tin gthc parallel lamps of
the circuit in Feries. The following are the methods of obt.ziwng
such lights
(j" With "Two-way ON and OFF' Switch.
IV
.\ >-...S,,_---
Nf \_-
First assume that the
single-way switch of circuit
•
011 shown in Fig. 7.16 is in the 'ON'
• position. When the two-way
switch is on terminal 1, the lamp
No. L 1 is shoit-circujted and
lamp No. L2 is full bright.
Alternatively when the two-way
2 Wcy
Off Svi 3t./ switch is on terminal 3 the lamp
No.L2 is short circuited while the
S.79/e K'cy -.'ich
lamp No. L 1 is full bright. When
Circuit for one of the lamp bright the two-way switch is on the
or two in series 'OFF position both the lamp are
Fig. 7.16 made in series for dim lighting.
The purpose of single-way swit&
is to control both the lamps.
(iii) Circuit for only one particular la7r.p bright or two lamps in
series. Foj-such circuit one single-way switch and one ordinary 2-way
switch is used. Assume the siagle.va y swjtcho in the on position
and the 2-way switch is on the position No. 1, then the lamp No. L1
is fully bright and lamp No. L2 is out of circuit. When the 2-way
switch is on position No. 2 ; at that instant both the lamps are made
in series to give dim light.
moved down making contact with terminals 3 and ' 4 the lamps are
connected in parallel across 220 V mains.
.
7_f3
400V -
720 /
(a) Circuit for lamps in senes
(b) Circuit for 'amps in parallel
Fig. 7.18
Such a circuit can also be obtained with the help of either two
ordinary 2-way switches and a single-way switch orby a single 2-way
switches and single-way switch or by a single 2-way ON and OFF
switch and a single-way switch.
Fig. 7.19 (a) represents the circuit in which the position of 2-way
switches is so shown that the lamps become in series while Fig. 7.19
(b) represents the position of 2-way switches for the lamps to be
connected in parallel across the main.
2 W.y8 011
--------------------- p175
Fig. 7.20
The terr.tive .ircuit for achievement of above-mentioned
aims is as shv.' u h g. 7.20 in which one of the switches is
single- wa arid he other is 2-way with off-position. When the 2-way
switch is conneced to terminal 3 and the single-way switch is off,
the two lamps are connected in series across the mains. When the
2-way switch is connected to terminal 1 and the single-way switch
is switched on, then both the lamps are connected in parallel across
the mains.
10. Master Switch Circuit. The master switch is just an
ordinary standard s"itch either single-way or two-way, btt it has
attained its name due to its function. Following are the main objects
of the master with
(1) toput o f the lamps irrespective of the position of the
individual switches and to prevent anybody switchingon the lamps,
such a control i z also --a] led as "Master off';
(2) to switch on t h e lamps and to prevent anybody switching
thorn off with i rdividli.a1 switches ; such a control is also called as
Master on";
(3) to control eithrr switching on or off of the circuit,
i.e. its
(unction is as in (1) or in (2), so it is called as variable master control.
INTERNAL W[JUNG SYSTEMS AND LAMP CIRCUITS 197
(a) "Master on" Switch Circuits. (1) Fig. 7.21 represents the
two-way control of the 3 lamps in the corridor, but when a single-way
switch is connected across terminals 1 and 2 of the two-way and is
switched on, then the independent control of the 3 lamps by the
two-way switches goes away. Whatever be the positions of the
two-way switches, the lamps will remain lighted.
re
Master on circuit - with two 2-way switches and one single-way switch
Fig. 7.21
A/e,,70t, s/f/0
- Of
SbI'itCh
Master control on circuit with two way Switches
and one intermediate switch.
Fig. 7.23
(b)"Master off'
Circuit. Fig. 7.24 Shows
three lamps being
controlled by three single-way switches in
dependently. Across the
main supply is connected a double-pole switch and when this switch
Hasler Off
I I I Swi
is made off, then the complete circuit is isolated from the mains and
the lamps cannot be lighted until and unless the main switch is
made on.
In Fig. 7.25 the lamp is being controlled by 3 switches, if the
first 2-way switch used is of the special type, i.e. two-way on and off
switch. The special two-way switch acts as a master off switch, i.e.
when it is put on the off-position the lamps cannot be lighted.
Znkr,nedoie5p -,:,C, i 2y
S q/kb Q S'ci 'PP1Y
Cs
Twiiob
5Tth
t
Variable master control circuit for corridor lights
(a)
ii. Pilot Circuits. The pilot circuits are used only to indicate
whether at the remote point, the load is on or off. The simplest pilot
indicator is a lamp which is automaticany switched on when the
remote load is switched on. Fig. 7.28 represents circuits for 2
lamp-loads at different remote places. Fig. 7.28 also shows the two
pilot lamps in the circuit.
1o.iips-,/Q\4_LLonoi1
I jCirrwfI.l
ç P tLompç I
.4
piv 4omp
''CvOrc"ItNo.?
yfl\ V\
—L
toLo
- ^3^
110
lip Cer,/rc) 0^,^
Marvei switch, inter
mediate type
Fig. 7.30 -
(3) Whole or Pa
terminals, Switch
T h1 5 type of switch has four
ter minals 3for such a switch the live wire comes to terminal 1, while
and 4 are Con nected to the lamps
.
Whole of the circuit comes into the circuit in In one posi tion, the
only thpar circuit remains in the circuit, th e second Position ,
the whole of and in the third position
the circuit is made of
P;:.
o. j.
Position No. 2
Fig. 7.31 position No. 3
(4) Parallel or Series Switch
Positions. In one positiorl, the lampsSuch
are a switch again has three
co nnected in p arallel in
Ist Positjo
2nd Pos i tio n
Parallel or Series Stch 3rd Position
Fig. 7.32
INTERNAL WIRING SYSTEMS AND
LM1P CIRCUITS 203
the second position the lamps are connected in series while in the
third position, all the lamps are switched off.
(.S) Reversing Switch.
The reversing switch is generally used
to reverse the direction of current in the load.
It is a six-terminal
switch. The terminal 1 a;d 4 also 2 and 3
are short circuited. The
terminals 5 and 6 are con nected to two links which move in unison
and can either be connected to terminals 3, 4 or to terminals 1 and
2 as shown in Fig. 7.33.
To load
S
Position No. 1
Fig. 7.34(a)
204
wmrNG, ESTI
MATiNG AND COSTThJG
In Fig. 7.34 (a) the m oveable
c ontacts of both the switches are
up. In each of the switches the termjnalsL
ter and 3 are connected and
theminals
lamp L2land U are shorted In this case the lamp L2
is off. lights while
M. Cfnfrv/
Position N. 2
Fig. 7.34(b)
In Fig. 7.34 (b) the
thus terminal L zm r, d L' Marvel switch S 1 is in the central position
up and the and 2 are shorted, while the switch MS 2 is
T the circuit oiL slinks make contacts with te rminals 1 and 3.
completed
and Lamp L2 is off.
Posit No. 3
Fig. 7.34 (c)
In Fig. 734 (c) switch M.s1
is in the down P o sition and so the
moveable links make contact with t
2 is up. It is clear fron Fig. 7.34 erminals 2 and 3, while switch
(c) that the circuit of either lamp
is not completed , thus both of them remain off.
205
INTERNAL WIRING SYSTEM S AND LkMP CIRCUITS
M5 Cenfrol !i Dow"
Position No. 4 Fig. 7.34(d)
For the circuit shovn in Fig. 7.34 (c) the moveable contacts of
the two Marvel switches are down. Thus lamp L, lights.
Down H. 5 Dow'?
1-01 W111,
I,
MS
Cow
Position No. 7
M.S ....... Central
MS2 ...... Down
No. Lamp lights
Pig. 7.34 (g)
In this circuit [Fig. 7.34 (g)] MS 1 is in the central-position while
MS2 is in the down position and the circuit. of neither lamp is
completed, thus the lamps remain in the off-pojtjon
In Fig. 7.31 (h)M.S 2 5 down position andM5 1 isin up position
A4.5
.iton No. 8
ig. 7.34 (/)
1TERNAL WIR?NG SYSTEMS AND LAMP CIRCUITS 207
and again lamp L 2 is lighted vheres when the switches are on the
position as shown in Fig. 731 (;), lamp I is lighted.
H. 5
Oo
Position No. 9
Lamp L 1 lights; M.S 1 --Up ; M.S2--Down
Fig. 7.34(i)
Circuits of either one lamp or both of them light in
parallel. With the revised connçctions in between the two Marvel
switches, a circuit for either lamp L 1 or lamps L 1 and L 2 in parallel
can be lighted. When the switch po5itions ofM.S, and M.S 2 are in
the Down and "Up directions respectively, no lamp will light as
shoo in Fig- 7.35 (h). The position of the two Marvel switches are
similarl y to the other positions as shown in Fig. 7.34.
Circuit for one lamp or two lamp or three lamps without off posinon
Fig. 7.36
For other positions of these switches, it will be observed that
either lamp L 1 alone lights, or L 1 and "2 light in parallel and there
is no off position.
Lamp controls at 3 places with the help of Marvel
Switches. Fig. 7.37 represents a two-lamp circuit similar to that of
shown in Fig. 734 in which case the two Marvel switches M.S and
INTERNAL VIR1NC. SYSTEMS AND LAMP CIRCUITS 209
M..)? up M51 Up
C:rcjit for controlling the li.rnps at three places
Fig. 7.37
5w,fh
Three lamps being controlled at three places
Fig. 7.38
210 WIRING, ESTIMATING AND COSTING
J
1ferm&'/e Stch
$
2y
Switch 24ty $wiftf
Afternale 4°csitai.
Y I,,ter,ik Si,q*jè
-Q
Controlling a lamp from more than one point
Fig. 7.41
/
7
h't- /7cC c' 5w'(c/ er,yerJ
Hoins
Lcir *',r.
2Wy 5w•c,
. L
\
5w.
(es.'? Wp
Fig. 7.45 (b
INTERNAL WIRING SYSTEMS AND LAMP C1RCUTS 213
6 p—..
Themo/$t'op,.,
Srr;os
II
Circuit of a fluor
escent tube with thermal starter
Fig. 7.47
INTERNAL WIRINMSY STFMISAND LAMP CIRCUITS 215
4' C
itch
V/(' rst—,
71ff?Lq7
(Jer7s'rAcrcss
Star Coll tacts -Gkw
T E/4muc.', Hrne/j, Sec/ed
In Gloss Casdy
/n/et-fer',.
Eaye..f.L0* Cv'c/..
Internal view of starter
Fig. 7.50
c1
Li
-
U,.
-
U
219
LO
I
00
wD 9E
OO1 O IH5F4
-i
j
Ii
r-.
----.--
C E
•__
0
H
ir$
0
H
CD
XQ-
cc
-4
w
<0
04
U
o
-- -I
UI -,
Q -
4
220
WIRING, ESTIMATlNG .INI) COSTING
TYPICAL QUESTIONS
1. Explain the looping in system of wiring.
2. Explain the looping in system of wiring with junction box.
3. What are the different types of house wiring?
4. State the precautions to be observed in various types of wiring.
5. What are the various types of lamp circuits?
6. Explain with diagram the application of series parallel circuit.
7. Explain with diagram the working principle of fluorescent tube
8. What doyou understand by Master switch circuits? Explain wit}
diagram the Master-on Circuit.
9. How many types of marvel switches are there? Write short note
on any two of them.
Transmission and Distribution
of Electrical Energy and House
Service Connections
.J . 5r(p IP TR4NcFopfl(j
"/220kv
220kv TgA,IcM1ccW,
9 L ..................
1;Qj
,e(.;(c-5
Ar
(v) All metallic portion viz supports and bolts are to be con
nected with the earth.
Table 8.1
Copper efficiencies
Systems
Maximum voltage Maximum voltage
between one conductor between two outgoing
and earth conductors
(z) D. C. System
(i) two-wire systeni 1 1
(ii) tNo-wiro systeml
vth mid-point 0.25 1
earthed
(iii)three-wire system 1 0.3125 1.25
(b) Single phase A.C.
System
(i) two-wire system
cs2 0 c0s 2 0
(ii) two-wire with 0.5 2
mid-point c0s2 0 C0s 2 0
earthed
(iii)three-wi ' e system 0.625 25
c0s 2 0 0
C0s 2
C)i C
C)
C)
W.
C.)
C
C.)
> Cu,
tz o I-.
CL
C) t,
C
to to 10
C C
C.)
C _z, •
C >
C) C
1.-
C.
C
C
-
.- ,, •::
C..
C
LLr,-' E
I- Cl)
C
C
—a C
C) -
I-'-'-
.a C
—
-
C
0•
C
Cr— C)
C) 0 2
Cl)
.0>>
C - C)
,.c
C. C cC
5-. C)
.-'
z
th
228 WIRING, ESTIMATING AND COSTING
Table 8.3
L.
I.
. te
N - - cc - cc c) - cc N- O N C) C,
ON L) .-C) N- I) ' coco C'
C') C') C' C' c'fcs -
L
PIZ
cc
t- .- I) C '- ) - cQ c - C' N- c N- C L -
C'
-4-C) C) N L,C') C')
C4 C"I - - - -,
C C) "
C) '•'
C C ''
C) ' C') '' (C' C'- a) C) -
C)-- -
I -
Table 8.5
Properties of Soli&Aluminiu.m Conductor Used for
Making A..C.S.R.
(The particularsare based on data from I.S. 398)
,. E °-ttS
N
C,
&
j
0
-
-
-. .c z,ir- N "t 0 cU,OOZO't tNN'tN
N N ?".-. 4 t L. N t
r_t,LcN.tC_NPtNNOXTZC
I coo0
z
C1 N CI - -
_CO_COCOCrC.C000t_N
E
0
z
it t
C OC C C 57CC C'tOOCCC ..CN = 7:
7: 0 7: St 55 = 0 CO C N hO Ct U, N 0 CO N C CI Ct
N CI CI N N N N CD CD CO CD 7:'? '7 Ct
—
CI SI N 7:7:7: 7:
0 CC C,CC55000000000000 CD0
z N CD tO CD CDt, CD CD
7: CD CD 7: 7:
I-
COCCOL000Ct ZQL0000t00005"° QISOj
N
C
234
WIRING, ESTIMATING AND COSTING
Table .7
Showing Properties of the Conductor,
Mechenj Copper L1u,.jnjum Steel AJunijo,, S:ecl
properies
13
Specific weight
kgiczn.'
•9x1042.7x10 786xI01 345x 3.7 x l0'
Young's Modulus
kgJmm 13,000 5.600
Ultimate Tensile 20,700 1 7,5000 8,300
Strength 40 18
kgimrn.2 40to320 120 120
Specific resistance p
at 2OC in
Conductivity 1 at 20'C
56 :4 8 56
Resistance tempera.
ore 00038 0-()4 000496 - -
Table 8.8
Comparison of Aluminium and Copper Conductors
- Pci rticulars
Alum *"umCoppe,
A. For equaj. resistance
U) Area ratio
16
(ii) Diameter ratio round conductor i2
(iii) Weight ratio
041
B. For equal current and temp. rise
(1) Area ratio
. 1-39 i
(ii) Diameter ratio for round conduc
tor 1-18 1
(iii) Weight ratio
0 42 1
C. For Equal Diameter
(1) Resistance ratio
(ii) Current carrying capacity 1-61 1
0.78 1
(6) They must be easily accessible for paint and erection of line
conductors.
(7) They must have longer life.
(8) They must be of pleasing shape.
The poles are grouted in the earth with cement concrete in the
ratio oil :2 :4 and one-sixth of the pole is embedded in the earth.
values vary to a Ia rge extent dcpenng upon degree
TRANSMISSION AND DISTRIBUTION OF ELECTRICAL 235
The main disadvantages of such poles are that they are elastic
and tend to rot, hence their life is short.
8. Arrangements of Conductors
A Transmission Lines. The following are the methods of
arrangement of conductors over the line supports:
(i) Single-phase circuits.
The single-phase transmission lines
can either be double-circuit.Fig. 8.3 represents the
most common method of single-phase single-circuit transmission.
Fig. 8.4 represents a double-circuit single-circuit transmission line
with conductors arranged in a horizontal disposition, while Fig. 8.5
represents double . oircujt-wjth vertical disposition of conductors.
.4 8 d F
A
A
T a
1 8
MRTH V/h
ARTJ4 WJRF
FOR CA
ture,Ifits
the insulating material is manufactured at lower tempera.
m ecanica1 properjes
improve, but the material remains
porous and when it is put in service it may deteriorate If the
material is manufactured at higher temperature, the Porosity of t
decreases but the material becomes brittle. So, a
co mpromje is
always made between the mechanical strength and the porooity
of
the material and a suitai-p temperature of the kiln is designed A
m
echanically sound porcelain irultor has a dielectric strength
of
about 60,000 V per cm. of its thickness, and its compressive and
tensile strengths are 70,000 kg/cm, 2
and 500 kg./cm.2.
(b) Class Insulators.
Many times glass is used as an insulating
material. The glass is made tough by annealing and these
have the follow i ng advantages . i nsulators
(i) They have very high dielectric strength of the order of about
140KV per cm. of thickness of the material
(ii)
When properly annealed they have high resistivity.
(iii) They have low coefficient of thermal expansion
(iv)
Due to higher dielectric strength, the glass insulators have
simpler d2sigii
and even one-piece designs can he used.
(u) They have higher comprssj .
insulators. ,.e strength than porcelain
95 M M
t 1
T_.r
28 5mrn-f-
¶
B
(h) One-piece Pin insulator (c) Gal vani zed Steel p;n.
Da
:anzm.
CONDUCTOR
Eel
Such type of insulators are used only for straight run of the
lines.
TRANSMISSION AND DISTRIBUTION OF ELECTRICAL 245
Ii
c.
z
ci)
- -w-1
IC LI.t
SPENS!C.N hLAO.S
&.so r S'
LWE CONDUCTOR
srR.v-
INSULATOR
GUY WIRE
O(.-(NO POLE
[E1111 M11
St isu]at,cr
- Fig. 8.16
15. Shackle Insulators or Spool Insulators. The shackle
isutor or the spool insulator is mostly used for low voltage
249
'SS1ON AND DISTRIBUTION OF ELECTRICAL
POLE
j,-6AL VAN/SED
fT THM5L
iHPE,4 D -D
END W.'T/
NEEL
STAY 80W 15117117. £21A.
AND 37. 5 Cli? LONG
/ CCKRETE
(i) Mild stel stay plate 6.5 mm. thick, 22.5 cmx22.5 cm having
16 mm dia. or 30 cm x 30 cm having mm dia. pole in its centre.
PVLE__J i \\)lEL
I ROAD
IPRIVATE
IOF M425Hy
PROJECTED ANGLE
5RACKE T AND BRACE
STAY ROD
.-GAL VA N/SEQ
-STAY 80L7
62
shown in Figs. 8.7 and 8.8.
7/I/ELY
CH'ARGED CLOUD
TOWER
ZEAKA6 4- 7Z?
E4R7y
22. Service Lines. As already said that the service lines are
tapped from the distribu t ors with water proof cable olsuitable size
and the oher rends of the water proof cable terminate in meter.
ITho erv line laid in 3ch a way is known as Overhead Service
Line.
Meters of suitable size are placed at about 165 cm. above the
floor level. The low tension meter can be single phase three-phase
three wire, three-phase four-wire of varying capacity depending
upon the requirement. In case of very high loads at high voltage,
TRANSMISSION AND DISTRIBUTION OF ELECTRICAL 255
IL1! ___lID
30 M G.LVNISEO
/RC;V T
50 MM.
FL AT
50/77,77.26 25177177.
ClaDs fo r fxin 7 House
Service House Service ine Bracket
Bracket Fig. 5.23
Fig. 8.24
23. Comparison between overhead system and under-
ground system. Following are the adL'antages and disadoitages
of oterhead system oucr underground system.
Advantages:
(i) Repair. It is easy to repair the overhead line as compared
to underground cable.
(ii) Fault Iocation.The fa'fltin overhead lines can be detected
easily and quickly as compare(' to underground cable.
(iii) Initial cost. Overhead s ,,-stem has a lower cost t.;z' the
underground system.
(iu) Charng Current. Due to more spacing of the conduc-
tors, the charging current is less in overhead s ystem than the
underground cable.
IQ
256
WIRING, ESTLMATING AND COSTFNc
(v) Jointing.
Jointing it underground cable is difficult and
precise as compared to overhead conductors
Disadvantages.
(i) Maintenance Cost.
system is more than the undergroThe maintenance cost of overhead
in overhead lines.
und system as there are more faults
(ii) Safety.
Underground cables are buried in the ground and
therefore more safer to the public.
(iii) Appearance.
Overhead system produces a shabby
appearance, whereas underground cables are not visible.
(iv) Effect of lightning and thunderst
orm. Lightning and
thunderstorm produces effect on overhead system whereas these do
not produce any effect or underground cables.
(v) Effect of Surge. The surges are absorbed by the metallic
sheath of underground cable and as such produce no demaging
effect.
(vi) Accidents. There can be accidents by overhead lines,
whereas chances are remote in underground system.
Voltage drop.
The inductance in an overhead line is more
because of larger spacing of conductors, therefore more voltage drop
is there in an overhead line.
(i i) Interference to telephone
lines. The overhead lines will
interfere with the nearby telec
ommunication lines, where under-
ground cables do not have any effect on them.
24.
Tariffs. Consuiners can be classified as 'Good and "poor'.
consumers are those who take regular supplies during 24 Hours or
when the general demand is low. Poor consumers are those who
require supplies only at times of general maximum demand (M.D.)
Hence consumers must be charged according to their type of load,
as well as to the number of units they consume. The following tariffs
are available.
1. Maximum-demand tariffs. (2 part or 3 part M.D. tariffs)
(a) a FIXED charge based on the maximum power required.
(b) a MAXIMUM-DEMAND charge based on the M.D. made
in each month or year.
(c) A Unit charge based on the number of units used
2. Block Tariffs:
(a) First block depending on the consumers' requirernens
(.J Second h1)c- dependjr on the demand and
TRANSMISSION AND DISTRIBUTION OF ELECTRICAL 257
TYPICAL QUESTIONS
1. What are the advantages of aluminium as a coflductor?
2. How many types of insulators are there? Of what material these
are made? -
3. Explain where the following are used
(i) Pin-type Insulator
(ii) Suspension type insulator
(iii) Stay insulator
4. What are the advantages of pin-type insulators and why shackle
insulators are not used for high voltage?
5. How the size of conductor is expressed?
6. Explain why lightning arrestor is used on overhead lines.
7. How many types of lightning arrestor are there?
8. Why stay or guy is used ?
9. Explain the various parts of stay guy set?
10. What are the most common types of stays?
11. What should be the vertical clearance of the conductor above the
building and horizontal clearance from the building?
12. Why flying, foot stays and stubs are used?
13. How service connections to the conjmerz are given from the
distributor?
14. Why poles of overhead lines are earthed?
15. What are the advantages and disadvantages of overhead system
over urderground system?
TRANSMISSION AND DISTRIBUTION OF ELECTRICAL 259
I. Introduction. Un
for tr ansmission and dergrou1id cables are being mostly utilised
dis t ribution of electrical energy. In
posh c olonies, the consumers desire service certain
gr ound cables because of the reason that such Connection
ac
by under-
onnection does not
spoil the beauty of their construction In addition, for certain loads
i:iz.
air-field thickly populated areas etc. it is necessary to use
ur. 3orground cable for distribution transmission and service con-
ni s. Aluminium c onductor underpound cables are being
in In used
dia. Thus the underground cable can be specified by
number
of cores, voltage they can withstand or type of insulation
2. Cable Insul
ation. The cables are usually classified
according to the type of insulation used. The type of insulation
be used must have the following properties to
(1)
It should have high specific resistance.
(2) It should be tough and flexible.
(3) It should not be hygroscopic
(4) It
should be capable of standing high temperatures without
much deterioration
(5) It should be non—inflammable
(6) It should not be attacked by acids or alkalies.
(7) It should not be capable of
Voltages. with standing high ru p
turing
261
UNDERGROUND CABLES AND INSTALLATIONS
262
WIRING, ESTIMATLNG AND COSTING
264
WIPING, ESTIMATING AND COSTING
C ''
-
- C
C:
.' H "
C - I
C)
C .- • .-' -•I-
-
CL C)
' 2 -J
'—C
E
CC)
0 C• -
CC. C
a z •E
C) - - •
— C
CC-
• OC ' Cr
C)C)
.5 •
o
C) C
- -
•F4 -e
ba p..
8D
C-Jo . --J-'0 C
, C_I r ,, = C -
- -- ••_• C
C) 0
-E -
x El 0 0
—
•JC)C C)_I
E E-
C: C
x
- C
C C- 0 C cc
CC o'j k. • 'CCL C ,— CC) CC
00
C)'
2 2 -'2
C C,
E C
m -
° o 1
—
b
Q
C)
>
0
C
0 I-
0
>
C C)
C) C) V
C, -C)
C C
0
C: _C) -
bc
C) Cl
C C
41 — C,
C ft
a C-, C)
C
I-
0 SC
0<,, 0S UC O
0 I-
C-,
> > .
>
7: ft
Ii C
ft C, C 'r CC
C C)
C,
C
C C 0
C >
• 5C) 0 0 0
C
as
tC$ •'
.c. C
-C
c0. •-E --i
CC . 0 g
•0"
0 l.. 0 1..,
••I. .5
'—.
O 0 4)
8 0 .o 5C
- CC
'tC C' t C
t.2
H
-
• . 4,o2 o-' -o
E.
4
a,., 00Ca, 0 -a,
o I._._ C.0
cd
8.00... 0__ C) 0 05
Va C0 4)00 C
I.0
• i-c 'E
:
o.0..-.oZo8 oa_.2
;o 0
c5 'C.
C
2
N
N ci
C
C
N
-.- 2 S S 04
ci 0 0
C, >0
C C.
C Cl C
0 C. C'
C) * >
C -S
1.0 Q 0
0 I. 0 0
1-
.0 E
C
I.
C'— 0 .0 C
O Cl CC 1:
V
o.o E C
V
— O CI.
E-0< 0
C
N
266 WIRING, ESTIMATING AND COSTING
3. Polythene insulated
cables, sheathed 1596 & -do-
with PVC,
-do-
Polythen insuleted, 3035-1964
taped, Braided
2. 2593-1964
3. 69l—j96
(Contd.)
IJNDERGRO!JND CABLES AND INSTALLATIONS 27
PER SkEATN
APE
ARMOURING
27
'
CONDUCTOR
I /._SEM/CONDU
PAPER
METALL/SE,
V PA PER SCREE/
PA PER
INSULATION
LEAO SHEATH
-. COPRCSON
/ PROTECTION
SPVIN
-, JUTS WAR-l1NG
B ECDING
DOUBLE STEEL
TAPE ARMQUR,NG
Fg 9.2 H-Type Cable.
(h) S. L. p cables (Fig. 9.3). in this type of cables each core
is first i:isulated with an impregnated paper and then each of them,
is sepa'-tely lead sheathed. Now the three cores are just equivalent
to th i c separate caHes, each having its own lead sheath. The three
cables are laid up with fillers, armoured and served overall with
imPregnated hessian tape as usual. The surrounding of all the three
cores are provided with lead sheaths.
The advantages of S.L. type cables over
H-type cables are:
(i) Owing to no overall lead sheath, bending of cable becomes
possible.
UNDERGROUND CABLES AND IITJILL.AT1ONS 271
PAP-'R 514EA
IMPEC,NAT LEAD SIJEATU
LJ.VfA, T4p1 O F A41 CORE
5EPARATa
JUTE FILL fM
COMuk
IIE,iS/4N 7l
5£ OOi.ij
57frL WIRE.
ARMOQ
C OMPO/
HESSL4N TA!
OVER ROLL
c-.j' Type
T511
Pig .4.
-19
272 WIRING, ESTIMATING AND COSTING
S.L. type cables can be u.ed upto 66 K V
(c) H.S.L. Cable (Fig. .
4). Such a caes is a combination of
H-type and S.L. type cables in which each conductor is insulated,
sheathed with metallized paper and is then lead sheathed. The
three cores are than laid up and provided with filler, braided,
armoured and finally served.
In addition to the above types of cables there are oil-filled cables.
Advantages of screened types of cables over Belted type
cables
(i) Possibility of core to core faults is reduced to some extent
in the metal sheathed core cable on account of having a greater core
to core thickness for a given overall diameter than a plain cable.
(ii) Electric stresses are uniformly radial in all sections of the
dielectric to be used in the metal sheathed core cable.
(iii) Possibility of formation of voids within the electric field is
not there as there is no warming or packing in the electric field and
dielectric subjected to electric stress is only paper which is quite
home g n us.
(iv) The current carrying capacity of the cables in increased
because the metal sheaths help in dissipation of heat.
Extra High Tension Cables.
To overcome the drawbacks of belted cables and super tension
cables, the manufacturing of extra High Tension Cables in done.
Such cables meet the demand for 132 KV and above. In these cables,
voids have been eliminated by increasing the pressure of the com-
pound and that is why these cables are also known as Pressure
Cables. These are of two types
(a) Oil Filled cables (b) gas pressure or compression cables.
(a) Oil Filled Cables. A single core oil filled cable is shown in
the Fig. In this cable, a channel is formed at thecentre of the core
by stranding the conductor wire around a hollow cylindrical steel
spiral. The channel is filled with thin oil by means of oil reservoirs
and feeding tanks, placed about every 600 metres along its length
and maintained at a pressure, not below atmospheric one at any
point along the cable. The oil used is the light mineral oil of low
viscosity as used for initial impregnation. The system is designed
in such a way that when the oil gets expanded due to increase in
UNDERGROUND CABLES AND INSTALLATIONS 273
LEAD SHEATH
PAPER
-CONDUCTOR
INSULATION
3ROQVED
SHEATH 20km ....,
- T II
PAPER
INSULATION
DUCTS
"SERVING
Single core sheath channel Three core Filler space channel
oil filled cable oil Filled cable
Fig. 9.6 Fig. 9.7
In 3 core oil filled cables, the oil ducts are accommodated in the
hollow filler spaces. The fillers are made of perforated metal ribbon
tubing and are at earth potential. At the time of jointing the cable,
great care is to be taken.
274
WIRING, ESTIMATING AND COSTING
Single core oil filled cables can be used upto 1,32000 volts and
three core oil filled cables can be used upto 66000 volts
Advantages of oil filled cables
(i) Due to reduction in the thickness of dielectric to be used,
the cable can be ma
nufactured smaller in size and in reduced weight.
(ii) There is no oxidation, formation of voids and no ionisation.
(iii) There is possibility of increased
service. temp erature range in
(iv) It has perfect imp regnation than others
(v) Due to reduction in thickness of dielectric to be used, the
cable has smaller thermal resisance
(vi) There is possbiitv uf imp
regnation even after sheathing
(vii) The cable can bear more stresses.
cviii) Fault can be located easily due to leakage o
f oil, ifañywhere
Disadvantages of oil Filled Cables
(1) The cable is more costly than that of others.
(ii) Maintenance of the cables is difficult.
(iii) Laying of cable is complicated
(b) Gas Pressure Cables
These are of two types:
(i) External Pressure cable
(ii) Gas Filled cables
(i) External Pressure Cables.
When the oil filled type cables
are developed for the highest voltages they are known as external
pressure cables. In such a cable the pressure is applied exterijv
and raised to such an tent that no ion i
sation can take place. Due
to increased pressure in the cable, the radial compression tend to
close any voids. The power factor of such a cable is also improver.
The external pressure cables are similar in Construction to that
of ordinary solid type except it is triangular instead of 75% circular.
in section. The triangular secton reduces the weight and gives low
thermal resistance. The lead sheath acts as a pressure membrane.
The cable is armoured with a thin metal tape so that the formation
of any abnormal ties over its surface is avoided. The cable is laid in
a steel pipe of some larger section. The pipe is filled with nitrogen
at a atmospheric pressure from 12 to 15 which continuallycom-
pressed the cable radially from outside and an y
voids etc. if any, are
closed. To avoid corrosion effect on the pipes, they are coated wiLl-i
a special p aint and it is further p
rotected with an i m p regnated felt.
UNDERGROUND CABLES AND INSTALLATIONS 275
(1) The moisture of the soil should not enter the core of the
cable.
IT
,
,
Method for laying the cable
Fig. 9.9
(3) It should be able to withstand the heat
of current p roduced due to flow
(4)
It Should not be capable of being damaged while handling
or laying
usually in the ground; so due to this reason armoured cables are
used.
(5) It should be sufciently flexible.
(6) It Should not be bulky.
(7) It should not be costly.
271
UNDERGROUN D CABLES AND INSTALLATIONS
ka
I- 0
"•
' Ii NO
C
-
• c Q..
CC
'-A
UNDERGROUND CABLES AND INSTALLATIONS 279
some means, the stress maybe distributed that its value in the outer
layers of the dielectric is increased without increasing the stress
near the conductor, insulation of less thickness will be required for
any given working voltage and an import economy is effected.
Thus the process of achieving uniformity in dielectric
stress is known as grading of cables.
There are two methods of grading
(i) Capacitance grading.
(ii) Intersheath grading.
(iii) Capacitance grading. By applying this method to the cable
grading, the uniformity in dielectric stress is achieved by using
various layers of different dielectrics in such a way that the per-
mittivity, K, of any layer is inversely proportional to its radius or
distance from the centre i.e.
or Kx = constant
Thus we obseive that if such a condition is achieved, the value
of dielectric stress of any point is constant and is independent of
distance from the centre, and the grading will be ideal one. But it
is not possible to use infinite number of dielectrics for a single cable
and in practice two or three dielectrics are used in such a way that
the permittivity of the dielectric near the core has got highest value
and then it decreases and finally it has got minimum value in the
outer most layer.
The advantage of this t y pe of grading is that if the overall
diameter is same for a non-graded and graded cable, then the per
missible safe potential of the cable is increased i.e. for the same
permissible safe potential, the size of the graded cable wilibe smaller
than that of the non-graded cable.
(ii) Inters heath grading. A homogeneous dielectric is used in
this method of cable grading. The dielectric is divided into various
layers, placing suitably the metallic intersheaths. These metallic
intersheaths are held at certain potential, which are in between
the tore potential and the earth potential. There is thus a definite
potential difference between the inner and outer layer-of earth
sheath, so that each sheath can be treated like a homogeneous single
core cable.
The modern trend is to avoid grading as far possible and ernplo
oil 61led or gas pressure cables because with the capacitance
280
WIRING,
ESTIMAG AND COST!Nc
grading, there are only few high iirade insulating materials of'
reasonable cost and with inter sheath grading, there is possibility
of damaging to the intersheath the time of
transp ortation and'
installation The heat looses are also there due to charging currents.
ll .Measu.rement of I
nsulation Resistance of Cables
1. Gal vanometer method. To
apply this method to measure the
insulation resistance of the cables, a very sensitive
high resistance i.e. galvanometer of
of 1000 ohm or more is connected in series with
the resistance to be measured and to a battery supply. The deflection
on the galv
under me anometer dial reads the insulation resistance of the cable
asurement. This method of measuring the insulation
resistance of the cable is not precise. This method is only sufficient
to indicate whether the insulation is faulty or otherwise
2. B) Insulation Testing megger.
The adequate and accurate
method of testing the insulation resistance of the cables is with the
help of megger. It carries two terminals marked E
minal L is connected to the core of the cable and and L. The ter-
terminal
connected to earth terminal. Now the handle ofthe meggeris rotatedis
'E'
at uniform speed, then there will be deflection of the pointer on the
calibrated dial of the megger. This is the direct reading of insulation
rejstance of the cable between core and earth.
l2. Cable Jointing. The cable jointing is the work of a highly
skilled man, snce the successful working of the cable depends
the quality of the joint made. All joints in the cables mustupon
mechan be
ically and electrically perfect as imperfect joints are the
source of weakness and danger. The cable jointing can be divided
into following heads
(a) Preparation of the ends of the cable.
required for cable jointing and their equipmenWhen all the materials
t is ready, the seal of
the cable shcu!d be broken. Remove the lead sheath only two-thirds
of its thickness for a length of about iS cm. (about 4 cm.
than the half length of the sleeve of the joint) by means ofgreater
a back
knife and hammer. Care should be taken to make a slanting cut in
the lead sheath so that the core insulation may not be damaged.
After this operation, bare the C
onductor for a length of about
0.625 cm. more than the half length of the sleeve and the bare
stranded conductor should he cleaned with niaptha. The remaining
length of the cable from which 2/3rd t
protected f hickness of lead is removed is
i.e. 3 cm
stranded end of the co pprox.) with the help of a tape. Then
nductor is secured with the help of two turnsthe
UNDERGROUND CABLES AND INSTALLATIONS 281
of binding wire, also near the end of the of cut the cable is secured
with afew turns of tinned copper binding wire. Now remove the first
binding wire made solder it either with the help of a soldering iron
or by pouring molten solder from one ladle to another. For such
soldering, powdered resin may be used as flux.
(b) Making sleeve for the joint. For making the sleeve for the
joint, the conductors are made to butt each other in the sleeve and
are soldered. The sleeve usually is made from a sheet of copper,
which is cleaned thoroughly and is bent to form a split tube. Two
holes of about 1.25 cm. diameter are drilled from each end of the
tube. Then a layer of pure tallow is applied on the inside and outside
of the tube. Now a layer of solder is applied on the inside and outside
of the sleeve, first by rolling in it powdered resin and then dipping
it in molten solder. The excess of the solder on the sleeve is usually
removed by means of pulling a piece of rag through the sleeve when
hot.
(c) Jointing. Before the actual process ofjointing starts, a lead
pipe about 20 cm. long is taken to cover the jointing copper sleeve
and a hole of 0.5 cm. dia. is made which is called the filling hole.
Then beat up the lead so that a lip is formed at the top of the hole.
Drill two holes more, one at each end so as to act as air vents. Clean
the ends of the lead pipe and scrap outer edges slightly. If it is not
done, the joint will not take solder. Now thoroughly clean the lead
sheath on each end of the cable and pass this lead pipe on one end
of the cable.
Now insert the prepared ends of the copper or aluminium
conductors of the cable into the copper sleeve. It is necessary that
this sleeve should be a close fit over the conductors, and conductors
should be placed so as to butt each other. Pour molten solder over
the split copper sleeve from a small ladle and keep another ladle
below the joint to catch the drops of the solder. The excess of the
molten solder should be wiped off. Care must be taken that the joint
is in a horizontal position. It should be remembered that the jointing
should not take more than half a minute otherwise the insulation of
the cable will be spoiled.
(d) Insulating the joint. The method of insulating rubber
insulated cables and paper insulated cables is different.. For insu-
lated rubber cable, India rubber tape is used with the help of rubber
solution which is available either in collapsible tubes Or in tins.
Before the rubber tape is provided over the joint, it is necessary to
checkup the rubber insulation on the cable ; if it is damaged during
the soldering operation, it mustbe cutaway. Also bare the insulation
for about 3 cm. on each side of the joint. Clean the insulation by
282
WNG, ESTIMATING AND CCSTING
scraping so that no dust or threads etc, are left out. The rubc:
insulation on the cable now should be tapered by means of curved
scissors for about 1.5 cm. on each side.
• Now just beyond the point cf taper, start providing tape on the
bare conductors and copper sleeve. Care should be taken not to use
rubber solution for the fi rst layer, i.e. rubber solution should not come
in contact with copper conductor. After first layer the second layer
is provided, so that this layer overlaps the previous one for half of
its width ; over the first layer, apply a small quantity of rubber
solution and the serving of this tape now should be continued (only
after the conductor is covered with rubber tape) upto the tapered
portion of the rubber insulation. The serving of the tape should be
continued until the insulation provided is of so much thickness that
it comes up to the level of the rubber insulation with continued use
of rubber solution on both sides of the tape. The last two layers
should be contihued beyond the start of tapered rubber insulation
for about 1.25 cm. For insulating the joint, care should be taken that
the work must be clean and the rubber solution should be sparingly
used. The cable insulation should be kept tapered only for the
minimum period and in no case dirt or dust should come in contact
with it.
taking care not to overheat it, otherwise the solder at the ends will
be melted and the Joint will be weakened. The warming of it is
necessary, otherwise the poured compound
will solidify and thus
prevent the complete compounding of the joint.
Pour the mcten cornpoun in t
o the lip hole of the sleeve until
it comes out of the vent holes of the sleeve. Allow the sleeve to cool
down and then pour more compound to allow for shrinkage. Seal
the filling by means of soldering a lead cover over it, while the air
vents should be soldered with drops of solder.
14. Jointing a Multicore Cable. For multi-core cables also
the tapered lead sleeve joints are the best, since approximates to
the actual construction of the cable. But such a method is quite
expensive and takes more time, so such joint are not justified for
low voltage and medium voltage cables. For such cables, the con-
ductor joints so made (without lead sleeve) can well be insulated
and protected in a cast box which is filled with an insulating
compound. The method of making a straight joint for 3,500 V.3-core
paper cable is as explained below
the internal diame.er of the inner gland. For proper adhesion each
turn is warmed up with blow lamp.
(9) At the points, where both the cables are to be gripped, clean
the armouring of each cable and bind with lead strip 1.5 mm. thick
until the overall diameter is slightly more than the internal diam-
eter of the armourclamp.
(10) The three cores joined together should be separated with
the help of porcelain spreader which must be quite dry. For this
purpose before use, it is immersed in a hot compound.
(11) Place the bottom half of the box under the joint so made
and provide the armour clamp as shown and bolt it to the cable. The
inside of the clamp must be well cleaned in order to ensure better
electrical contact.
(12) With the stud, connect the lead bonding strip to the box.
(13) Warm thebottom haifofthe box with filling compound and
while the compound is hot, place the upper half of the box over it
and provide a bolt.
(14) Remove t1e manhole and heat up the box from outside and
fill it up with the compound.
(15) Remove t1e filling plugs of the glands and provide seaing
compound over thi glands.
(16) Allow the joint to cool down, and after the contraction of
the insulating compound, provide more quantity of it.
(1) After theoritraction is complete, fill the groove shown with
the sealing compnd and replace the manhole. Before replacing
the manhole, sealing compound houid be provided there.
(18) All the enings should be sealed with the sealing com-
pound.
Typical Questions
1.
propertiesWhat is tie use of under ground cables ? Explain about the
which the insulation of underground cable possess?
2. What type of insulating material are mostly used for under
ground cables? Explain about them.
3. Explain about the general Construction of underground cable.
How are the cables classified according to Voltage?
4. What are the types of 3 phases cables?
Explain about them with their diagrams.
5. What points are taken into consideration at the time of laying
under ground cables ?
6.
What methods are adopted for laying of cables under ground ?
E\plan about them.
7.
tvp cahesWhat
?
are the advantages of screened types of cables over belted
between the electrical element Of '!he apparatus and its metal case
be fl, and resistance of the body of person, who happens to touch
the apparatus be R,
lithe person who touches the apparatus
standing on the earth, then the current from the supply main will
have an alternative path through the insulation resistanceR of the
electrical apparatus resistance R6 of the body to earth, and finally
through the earth resistance R to the neutral of the supply. The
electrical circuit for the above is shown in Fig. 10.2. The current
in the second shunt path depends upon the insulation resistanceR1b
R, R and the applied voltage V. However, mostly it is dependent
upon R, since it varies from infinity when the insulation is quite
sound and zero ohms when there is a dead short circuit between the
element and the metal case respectively. No current will pass
through alternative circuit, if the insulator resistance is infinity.
Rb
R i soc ..(10.l)
16 oc+R6+R0 ...(l0.2)
V
(10.3)
IVRI'Pi
L
c
2 ra
Re Re,
(a) (b)
Illustrating an earthed Electric circuit when the apparatus
apparatus. is earthed.
Fig. 10.3
Now let the metal case be earthed as shown in Fig. 10.3 (a). Fig.
10.3 (b) represents the electrical circuit when any person standing
on the earth touches -the apparatus.
290
WUflG, ESTIMAT[NG AND COSTING
R =R.+--_--
l/R, + I/R b -
R, x
P, --:-
...(10.4)
V
/ &
..:(10.5)
The current for which value has been arrived at in Eqn. (10.5)
will be divided in two parts at junction A. If
the value of the current
through the body and earth be I and
'd which adjust themselves in
the inverse ratio of their resistance, then.
/b
Ac
R 1 +R R 1.
..(I0.6)
and
R,1±R ...(I0.7)
Fig. 10.4
Thus it will provide an alternative low resistance path to the-
neutral. The salient features of the bonding must be:
(i) the earth wire acting as a bonding connection must be of
sufficient cross-section to carry the fault current under
worst conditions
(ii) the bonding must be continuous from the appliance to be
protected to the neutral of the source;
(iii) the resistance of the bonding must be very low
(iv) the bonding wire must be strong enough so that it cannot
be broken easily at any point;
(v) the connection of the bonding wire must be perfect at both
ends;
(vi) all bonding connection should be protected against corro-
sion.
292
WIRING, ESTIMATING AND COSTING
and source and thus will get a severe shock since it is still not
disconnected from the live mains.
Hence for safety reasons, a fuse should never be used in the
neutral.
Fig. 10.5 -
7ed Out
'Y.'"_
Soldered SO/Id
W
Wre Mesh
6' (,
I9m Did ()
Cm.
.12mm flak
.-.-
of
earthja
wire is carried over from one machine to the other, it should
be well protected from mechanical injury, by carrying the earth
a recessed portion.
Plate Eart?iing. The earth connection can again be provided
with the help of a copper plate or a G.I. plate. When G.I. plate is
used it should not be of less than 60 cm. x 60 cm. x 6.35 mm while
for copper plate these dimensions may be 60 cm. x 60 cm. x 3.18
mm. However, the use of the copper plate in these days, is limited.
Cast I,o., (-"er
-
Hi
OrCi aja..e
::at
H (b
(1
Fig. 10.8 Plate earthing
The plate is kept with its face vertical at a depth of 3 in. (10 ft.)
and is so arranged that it is embedded in an alternate layer of coke
and salt for a minimum thickness of about 15 cm. in case earthing
is done by copper plate and in coke layers of 15 cm. if it is done with
G. I. plate. The earth wire is securely bolted to the earthplate with
the help of bolt nut and washer, the details of which are shown in
Fig. 10.8(b). It should be remembered that the nuts and bolts must
be of copper for copper plate and should be of galvanized iron for
galvanized plate. The other details of plate earthing are same as
that ofG.l. pipe earthing.
298
WIRING, ESTIMATING AND COSTEr-
10. Definitions.
(1) Earth Electrode. The conductor
e mbedded in the grow—
for the purpose of rnak ng connection with the general mass of ear
is known as earth electrode and the wire which connects overhe
earth wire (or any other equipment to be earthed) with ear
electrode is known as earthing lead.
Where available underground water pipes or lead sheathed a—
steel armoured cables should not be used as earth electrodes. The
are prohibited by ISI, vide IS 732-1963 (Revised)
"Sprinkler pipes or conveying gas, water or flammable liqui
conduit, metallic enclosures of cables, conductors and Iightnii-
protection system, shall not be used as a means of earthing =
installation, or even as a link in earthing system."
The reason is, the water pipes are not usually in direct conta
with earth, particularly if no-conducting joining have been us
between section of water main. The same is the case with lead shea
or steel armouring of cables.
There are 3 types of artificial electrodes, following ti
specifications of ISS.
(1) Driven Electrodes i.e. pipe or rode electrodes,
(it) Strip electr dc
(iii) Plate electrodes.
(ii) Driven Electrodes The electrode is made of metal rod
pipe having a clean surface line, not cjvered by any poor
conducting material such a paint or enamel. Rod electrodes ofste
or iron shall have a minimum dia. of 16 mm and those of copper
at least 12.5mm dia. Pipe electrodes shall not be less than 38m
internal dia-meter if made of iron or steel, (galvanised,) The lengt
of this electrodes shall be not less than 2.5m. The electrodes sha-
normally be driven to a depth of at least 1.25 metres. But if rock
encountered they may be burned in a horizontal trench and sha
be not less than 2.5m. in length.
(iii) Strip Electrodes. These consist of copper strips, n
smaller than 25mm x 1.6mm in cross section of bare COPPE
conductor not less than 3mm 2 in section. They are burned i
horizontal trenches, not less than 2.5m deep. The length shall b
such as to give required earth resistance.
(iv) Plate Electrodes. A plate of copper or galvanised iron c
(0.6 x 0.6 x 0.006 m for iron OR 0.6 x 0.6 x 0.003 m. copper) is burrie
with its face vertical iri an alternate layer of coke and salt for
minimum thickness of about 15cm. The earthing lead is enclosed i
a G.I. pipe of 12.7 mm dia and is bolted to the earth plate with th
help of bolt, nut and washer.
ELECTRIC EARTHING AND SHOCK 299
NEUTRAL
-
py
OP
MA IN S TCH
RESISTOR
KEY I
I:; INSULATED
LEAD
J
EAR 7- H F
WIRE
L
Ll LAETO BE
301
ELECTRIC EARTHING AND SHOCK
material for earth electrode and earth lead should be same and the
electrode should always be placed in vertc :l position. The size of the
plate earth electrode for various loads and insulation should be in
accordance with the details given in Table 10.1.
Table 10.1
Type of loads and Size of the earth lead I Size of the earth
installation electrode
-J
Copper I G.1. Wire
SWG Area inSWG Area in
sq. mm sq. mm Copper i G.I.
Consumers S 12.97 8 12.97 o0cm.x 6Ocm.x
residential 60cm x 60cm. x
premises 3.18 mm 6.35 mn
Pole earthing of-do . -do. S 12.97 -do . -do-
transmission or
distribution lines
Industrial loads -do- -do- 8 12.97 -do- .do-
upto 10 HP
Industrial loads -do- -do- 6 - 18.68 -do- -do-
between 10 HP to
15 HP
Industrial loads 6 18.68 2 38.60 -do- 9cm.x
between 15 HP to I 90cm. x
30 HP 6.35 mm
Industrial loads 4 27.27 not used 90cm.x Not used
betWeen 30 HP tol cm. x
50 HP 16.35 mm
Industrial loads (i) 2 38.60 not used -do- Not used
between 50 HP to (iL)copp 12.7mm
100 HP er strip 2.54mm
Industrial loads copper 25.4mm rot 1 used -do- L
above 100 HP strip 2.54mm
PowerHouses and copper 25.4mm not used -do- -
sub-stations strip 2.54mm --d
Condit Electric re
ion of szstanceo/ bo y 500V 10,000 V
body the body
ohms Current I Current Current
A zFect A I A Effect
Totally 1,000 0.1 Cin 0.5 A B 10 Severe
wet and probable burns;
1 itht I death may
survive
Neither 5,000 0.02 1Xv 5urnsl 0.1 2 Severe
wet not o ijury; death; burns;
dry pail slight
burns vive
Dry 100,000 0.003 Vligh coo: Light 0.1 ue
sh; oaF shock, no de'ayth;
I lburns sli ht
14. Cure of Shocks. Innost of the cases the electric shock due
to accidents is momentarvand the contact with the live wire is
imperfect, in such cases breh stops momentarily. But ifdue to the
shock the victim becomesnscious, stops breathing and his heart
still beats, the most urgetand immediate cure for this victim is
that should be given irnm-ate artificial respiration in the manner
detailed on next pages be, and it should be continued until the
victim starts breathing nos'nally. It should be borne in mind that if
the artificial respiration ispped just after the victim recovers, he
is liable to become unconus again. In some cases the artificial
respiration is to be contimi for 6 to S hours.
If due to shock the hearistops beating it means that fibrillation
of the heart has occuredas1 death is certain.
15. Artificial Respiution. At the time of accident due to
electric shock, proceed asfdlows
(i) When anyone getsa shock, the first and foremost duty of
the observer is toreak the contact of the live mains and
body eTher by swithing off the main supply, or the body
should be rclledavay with a dry wooden stick. If stick
—21
304 WIRING, ESTIMATING AND COSTING
Now relax the pressure slowly and come to the oriinal kneeling
position for about twe seconds as represented in Fig. 10.9. Repeat
the process for about 12 to 15 times in a minute. It expands and
contracts the patient's lungs so as to initiate breathing. The process
should be continued with great patience and in so case violence
should be used.
ELECTRIC EARTHING AND SHOCK 305
Method 2. When the patient has got burns etc. on his chest or
anywhere on front side, then the patient must definitely not be laid
as in Fig. 10. 11, instead lay him as shown in Fig. 10.12 with a pillow
or rolled coat under his shoulders. The clothes of the patient must
be loosened before starting the process of artificial respiration.
Artifici al respiration
Fig. 10.11
(a) Hold the patient just below the elbows and draw his hands
over his head until they are horizontal, keep them in that position
for about two seconds. Now bring the patient's hands on to his siIes
kneeling over the patient's hands so as to compress them down as
represented in Fig. 10.12. After 2 seconds repeat the process again.
Artificial respiration
Fig. 10.12
306
WIRING. ESTIMATING AND COSTING
(h) If the operator has got burns cnly, the burns should be
dressed properly ; oil should never be used on the burns. After the
patient's burns have been dressed properly, he may look cheerful
and quite all right. It is important to note that one who has received
electric shock is liable to get an attack of h yp
orstatjc pneumonia.
So it is necessary to keep him warm for at least one day.
16. Precautions against Shock. It is always necessary to
observe the following precautions against shock, since prevention
is better than cure
(1) Try to avoid work on live mains which should be switched
off before working.
(2) If it is not possible to switch off the mains, be sure before
working that your hands r feet are not wet and i
rubber shoes. nsulated with
(3) In order to rescue a person who has got an electric shock if
there is no other insulator available for rescuing, useyour feet rather
than hands, wearing the rebber shoes or P.V.C. shoes.
(4) When working on high voltages, be sure that the floor is not
conductor. Concrete floors are dan g erously conductive.
(5) When working on high voltage, try to keep your left hand
in the pocket i.e. avoid your left hand to get in contact with an
y live
conductor orme tall ic causing of an apparatus or metal pole or cross
arms.
(6) Do not work in such a place where your head is liable to
touch the live mains before making the circuit dead.
TYPICAL QUESTIONS
1. Why earthing is done?
2. Why fuse is not used in the neutral?
3. What are the various points which are to be earthed in accordance
with Indian Electricity Rule !
4. Write short notes on the following:
(i) Earth lead (ii) Electrode
(iii) Earth Continuity conductor (iv)
Sub-main earthing conductor
5. What are the various points to
be remembered while earthing?
6. What are the values of earth resistance?
7. What are factors on which earth resistance depend?
8. What are the various methods of earthing ? Explain one of the
method with sketch.
9. Recommend type of earthing for residential accommodation.
10. What should be the size of conductor and plate ejectr
recommended for earthing at various places?
11. What do you understand by the phenomena of"Electi-jc Shock"?
12. How a person who has suffered an electric shock is to be cured.
13. Suggest various precautions required to be taken to avoid electric
shock to a worker.
14. Write down the specifications for:
(a) Plate electrode (b) Pipe electrode
(c) Earth lead (d) Barth conductor
11
Power Stations and Substations
1. Thermal Power Stations. 2. Hydro Electric Power Stations. 3. Diesel Power Ste.
tioüs. 4. Nuclear Power Stations. 5, The Gas Turbine Power Plant.
Substations 1. Introduction. 2. Ciassication of Substations. 3. Transformer. 4.
Advantages and Disadvantages of Out-door Substations as Compared to Indoor
Substations. 5.Design of substation. 6. Main connection Schemes. 7. Graphical
symbols for various types ofApparatus and Circuit elements on Substation. S. Main
Connection diagrams showing the arrangements of various typical connections and
of the simple substation scheme. 9. Insulators. 10. Substation Auxiliaries Supply.
11. Complete Bus BarArrangementa on High and Low Voltage side for a 5L.8titions
12.RingMain system 13. CrruitBreaker 14. Circuit Breaker Contacts. 15. }luhi -igs.
16. Oil Circuit Breaker 17. Description of Oil Circuit Breaker 18. Ccr.necti fla-
.1
JE
LAT
EHE
FLUE O AS ES
E .AE jj_l_
TANSFCME
AN VA .E
SUEP L-
hE4IEC 5E -
Con d en s
PJSTEA
P UNP
CO EN-1
, P'I'ts e^SE
1,
IAZU' AT
RIVER OR CANAL
into the hoppers by gravity and finally the requisite quantity of coal
either goes on falling directly on the grate, or where the coal
spreaders are provided, coal is spread in the grate up to the rear
end. When use of spreaders is made, most of the coal burns in air
and remaining falls at the rear end of the grate. Any unburnt coal
particles in the middle of the grate are collected in a pipe and are
again refired by cinder-refiring fan. The grate in such types of
boilers, where use of spreaders is made, moves from rear end to front
end, and without spreaders, the movement of the grate is from front
to rear end. Combustion is controlled by controlling the grate speed,
quantity of coal entering the grate, the damper openings. The ash
is collected after complete combustion of fuel at the back of the boiler
and is removed to the ash storage by means of scrap conveyors. -
(ii) Air and Flue Gas Circuit. Air is drawn from the atmosphere
by a forced draught fan through the air preheater, in which it is
heated by the heat of flue-gases passing to chimney, and then
admitted to the furnaces. The flue-gases after passing around boiler
tubes and superheater tubes are drawn by the induced draught fan
through economiser and air pre-heater and finally exhausted to the
atmosphere through chimney.
the heat must be extracted before the water is again pumped to the
condenser. A low pressure in the condenser is maintained with the
circulation of cooling water to the condenser.
Factors Influencing the Choice of Site For Thermal Plants. The
following factors should be considered while selecting a site for
steam power station for economical and efficient generation
(i) Nearness to the load centre. The power station should be as
near as possible to the centre of the load to reduce the transmission
cost and losses. This factor is most important when d.c. supply
system is adopted. Howver, in case of ac. supply system where
transformation of energy from lower voltage to higher voltage and
vk'e-versa is possible, power station can be erected at places other
than that of centre of load provided other conditions are favourable.
(ii) Supply of water. The power station should be near
6
source of water. Since large quantity of cooling water (500 tonnes
the
of cooling water for every tonne of coal burnt) is required far the
condenser.
(iii) Supply of Fuels. The power station should be near to the
coal mines if possible to reduce the transportation cost of fuel.
(iv) Transportation Facilities. The facilities like railway station
must be available for transportation of heavy equipment anct fuels.
(v) Cost of land. Land should be available at a reasonable price.
(vi) Type of land. Soil of land should be very stiff to bear the
weight of th6 large building and heavy machinery.
(vii) Available area. Sufficient area must be available to keep
the land in reserve for future expansions.
(viii) Distance from populated area. The site for the power station
should be away from the populated area so that there may be no
effect of pulverised fuel, residues and fumes on the population.
All the factors given above make us to select the site for the
thermal power station away from the towns. New-a-days more
importance is given to the facilities for generation than those of
distribution and a site for steam power station neaqr by river side,
where ample water is available, no pollution of atmosphere occurs
and fuel can be transported easily, is an ideal choice.
Constitutents of Steam Power Station and Layout. The
important parts and auxiliaries of steam power stations are dis-
cussed below
(i) Steam Generating Equipments.
(a) Boilers. Steam boilers used in steam plants are of two types
namely fire tube and water tube. In fire tube boilers, the tubes
containing hot gases of combustion inside are Surrounded with
POWER STATIONS AND SUBSTATIONS311
while in water tube boiler, the water is inside the tubes and hot
gases outside the tubes. Fire tube boilers use is limited to low cost,
small size and low pressure (to about 10 kg/cm 2 ) plants. For central
steam plants of large capacity, water tube boilers are usually used.
The water tube boilers have following advantages over fire tube
boilers.
1. It has high evaporative capacity due to having a large
heating surface
2. Owing to rapid and uniform circulation of water in tubes,
it has better heat transfer to the mass of water and better efficiencY.
3. It has high working pressure due to small size of drum.
4. Owing to large ratio of heating surface to water volume, it
has quick raising of steam.
5. It has got safety in operation.
6. It occupies less space.
7. Overall control is better.
S Easy removal of scale from inside the tubes.
Fire tube boilers for low pressure are cheaper and capable of
nieting large fluctuation in steam demands due to greater cater
crge n tho anm.
The design of boiler depends upon weight, height, portability,
safet y , bulk, character of operating labour life, efficiency and cost.
The boilers may be straight or bent tube of diameter ranging from
25 mm to 100 mm; longitudinal or cross drum, horizontal, vertical
or inclined tube, forced or natural circulation, single or multi-drum,
sectional or box header, cross or parallel baffles, marine or sta-
tionary. Header boilers, using straight tubes are superseded by
curved-tube drum type. Natural circulation (by density difference)
of water is used with pressure upto 175 kgicm 2 . Pumps giving
controlled circulation, are often preferred on design delivering more
than 3,40,000 kgm of steam per hour at pressures above 100 kg'cm2.
(b) Boiler Furnaces-. The construction of boiler furnace varies
fromplain refractory walls to completely water cooled walls,
depending upon characteristics of fuel used and ash produced, firing
methods, nature of load demand, combustion space required, excess
air used, operating temperature, initial and operating cost. Water
walls are built of tubes of diameter from 25 mm to 100 mm variously
spaced, with or without fins or studs, and bare cr,witla different
thickness of moldable refractory on the inner face. Heat transfer
rates run from 50,000 to 150,000 B. Th. U. per holr cubic ft. of
surface. To meet these requirements of heat transmission, circu-
lation on the water side should be adequate, obtained by convection
or by pumps. Air cooled walls are no more preferred. Surrounding
312 VLUNG, ESTIMATING AND COSTING
the furnace, and the rest of the boiler, is the insulated casing which
may be finished in plastic or with a sheet-metal sheath. The boiler
is supported on its own structural steel with provision for expansion.
There are two methods offiring coal in boiler furnaces i.e. hand
firing and mechanical firing. Hand firing of coal is limited to small
or transient services (less than 4,500 kg of ream p€r 1cur where
the inefficiency of poor combustion control is acceptable. Stokers
give mechanical feeding of coal. Mechanical stoker receive fuel by
gravity, carry it to the furnace for combustion and after combustion,
discharge the ash at the appropriate point. The advantages of stoker
or mechanical firing over hand firing are given below:
(i) There is uniform feeding of fuel into the furnace.
(ii) There is better regulation and efficient combustion due to
easy control of firing.
(iii) Lobour cost is less.
(i) There is a possibility of use of poor grades of coal due to
better control.
(v) Combustion capacity is more.
Mechanical stokers are of two types namely over feeo stokers
and under feed stokers. In the over feed stokers, the fresh fuel is
added to the top of the burning fuel bed while in the under feed
stokers the fre's' h fuel is introduced from below the burning fuel.
Underfeed tokers are suitable for cooking type coals and run with
fuel bed thicknesses upto 60 cm. Travelling orhain grate stokers
are used for burning middle-western bituminous coals with fuel beds
less than 15 cm in thickness and grate travel rates of 30 to 60 cm
per minute. Spreader stokers, with dumping or travelling grates,
are suitable for a wide variety of coals using thin fires (5 to 7 cm).
Solid fuels can be used in a powdered form and burn like oil and
gases. The coal is first dried usually by the flue gases and then
ground to a fine powder in pulverised mill. The pulverised fuel has
the following advantages.
(i) It enables the boilers to operate for longer period at maxi-
mum capacity
(ii) Steam can be raised rapidly.
(iii) There is possibility of high rates of combustion.
(iv) Quantity of air required for combustion is less.
(v) Efficiency can be increased if fuel and air are adjusted
accurately.
313
t ND SUBSTATIONS
P OWER STAT1OS
low grade.
(vi) Fuel used may be of
(vii) Ash removing troubles are not more.
However the pulverised fuels have the following disadvantages:
Initial and running costs of pulverisation plant are high.
(i)
Higher thermal losses in the flue gases are caused by higher
(ii)
combustion temperatures
(iii) There is a risk of explosion.
These consist of groups of
(c) Superheater and Re-heaters.
tubes made of special steel (carbon steel for steam temperature up
to 950°F, carbon -molybdenum steel for steam temperature of 1050°F
and stainless steel for steam temperature of 1200°F) with an outside
diameter from 25 mm to 64 mm. Tube bundle location and
arrangement, with counter current, an'or parallel flow is dictated
type of firing, required steam temperature, and steam-
I b
tomperature characteristic. Tbe superheater tubes are heated
the heat of ccibustiufl gases duag their passage from the furnace
to he chimney.
ldiant superheater5 ad
Superheat ers are of two types . (i superheater is located ia he
ronv000fl superleat r. diant L. po the
furnace between the f,rnace water-walls, absorbs heat from
ves droopir
radiation and
bu.ing fuel through
characteristics—the temperatra of superheat falls with the
increase in steam output. Convection superheater is located well
back in the boiler tube bank, receives its heat entirely from Cue
racteriStjc5_t
gases through convection and gives rising
temperature of super-heat increase with the increase in steam out
Desir ed
ut. Convection superheater3 are more commonly used.
p
control of characteristic is obtained by
(i) proportioning and locating surfaces in series.
using internal dampers on boiler gas side.
(ii)
(iii) temp. rating by vater or
supplementary burners. Heat transfer rates of 10 to 12
(iv)
B.T.U. per hour per square ft per degree temperature difference are
representative.
The steam is superheated to the highest economical, tempera-
ture not only to increase the efficiency but also to have following
advantages:
Owing to its high internal energy, there is reduction in
(0
requirement of steam quantity fr a given output of energy which
reduces the turbine size.
WIRING. EATING AND COG.
(ii)
Superheated steam being dry, turbine blades remain dry
so the mechanical re sistance to the
flow
which increases ta efficeiicy -. ofstam over them is small
(iii)
There
to dryness is no or rosion and pitting at the turbine blades due
of steam.
(d) EconQmisers and Air
number of closely, pre-heaters 1 con sists of a large
spaced
diameter (about SO mm) co parallel tubes with thin walls and small
nnected by, headers or drums.
rate sometimes finned to increase the heat transfer The tubes
omiser and air p su rface Econ-
would p re-heater are used to recover a part of heat that
therwise be lost. These raise boiler efficiency lowering the
stack temperature and saving the fuel but involve extra cost of
in stallation and maintenance and additional
requ irement of floor
space. Either one or both may be used or they may
entirely, be omitted
Eco
nomisers recover heat from the flue gases by adding it
to the feed water on its way to the boiler, thus raising the temper-
ature of water usually without
ev
he sufficiently, pure which may notaporation
fo
The
feed water Should
Corrosion scales and cause internal
Air p
re-heaters recover the heat from the
it to the air suppijed for flue g ases by adding
co mbustion This raises the temperature
of the furnace gases, improves co
mbustion rites and efficiency ,
lowers the stack temperature thus theoyerLIl efficiency of the boiler and
is increasedr p reheaters are ofto types namely
re
generative types. The recuperative type uses a recup bank erative and
of straight
light gauge steel tubes 25 mm to 75 mm. in
the flue gases inside the tubes and di ameter usually with
air
types transfers the heat by using slowly outside The regenerative
of c o rrugated metal which moves r evoMng drum (1 or 2 m)
and cold air streams atr nately through the hot gas
condenser pressure. If this jet is now passed over a single blade rinMm
and its kinetic energy is absorbed by this ring, it will be found tha-
the speed of this blade ring is too high for practical purpose. One o
the chief objects in steam turbines development has been to devis
of ove r coming this high speed of turbine wheels. No reduction gea
is required for the reaction type turbine because the speed beinj
relatively low.
The steam turbines used are of two types namely axial flow am
radial flow type according to the type of flow of steam. In axial flo'
type turbines, the steam flows over the blades in a direction paralle
to the axis of the wheel. In radial flow turbines, the blades are—
arranged radially so that the steam enters at the blade tip nearest—
the axis of the wheel and flows towards the circumference
be: The steam turbines ha ving horizontal shaft are used. These ma
H WATE,R P.M :I
I OFFICE I
I4 CH
yQD
&
lTRAS-
VCRWER
0 tJ
a
0
454 C-,
FAT At,O 10
rX
LII P
= 5,850k. cais
=
= 2O,cX)OXO.4X87607008X lO4kWh.
(j) -uch power stnticcl s have constant speed and hence con-
stant frequency as very acute governing is possible with water
turbines.
(v) No standby losses are there.
(vi) Such plants have got longer life.
(vii) It is very neat and clean plant as there is no smoke or ash.
(viii) Highly skilled engineers are required only at the time of
construction but later a few experienced persons will be sufficient.
(ix) In addition to generation of electric power such plants also
serve other purposes such as irrigation and flood control.
Disadvantages. (i) Large area is required for its installation.
(ii) It has very high construction cost.
(iii) Very longer period is required for its erection i.e. from 5 to
7 years.
([v) Transmission lines cost more.
(v) The power supply may be effected due to long dr y seasons.
Factors to be considered for the location of hydro-
electric power stations.
The following factors should be taken into consideration for the
location of hydroelectric power stations.
' such power stations should be built where there is ade-
(juate water available at good head or huge quantity of water is
flowing across a given point as generation ofeleetric power depends
upon the potential energy of water fall or kinetic energy c.fflowing
stream.
vii) Convenient accommodation for the erection of a-dam or
reservoir must be available because storage of water in a suitable
reservoir at a height or building of dam across the river is essential
in order to have continuous and perennial supply during the dry
season.
(iii) The reservoir must have a large catch mentarea to maintain
the level of water in the reservoir required in the dry season.
(iv) The land should be of reasonable cost and rock y to with-
stand the weight of large building and heavy machinery.
(v) Adequate transportation facilities -must be availahle
nearby.
(vi) There should be possibility of stream diversion at the time
of construction
E1ernenL f a Hydroelectric Plant. An hydro-electnc plant
consists ofa diversion dam, a conduit to carry the water to the water
-22
320
WIRING, ESTIMATING AND COSTING
wheel, the powerhouse 4nd its equipment, and a tail race. The size,
location, and type of each of these essential elements depend upon
the topography and geological conditions and the amount of water
to be used. The height to which the dam is to be built is usually
limited by the extent of flowage damage. Pondage may have great
value, particularly for peak load power plants. The spillway section
ofthe dam must belong enough to pass safely the maximum amount
of water to be expected. Likewise the abutments and other short
structures must be built to withstand successfully the greatest
freshet conceivable on the river.
(v) Values and Gates. In low head plants gates are needed at
the entrance to the turbine casing to close the flow of water for
inspection and repairs Individual hoist-operated gates are provided
in cases where frequent shutdowns are required and where the time
available for inspection is limited. Other plants use stop gates or
stop logs placed in sections by means of travelling crane. While using
medium or longer length penstocks or a common penstock for more
than one unit, it is necessary to install valves at or near the entrance
to the turbine casing. These are usually of the butterfly or pivot type
for low and medium heads.
(vi) Rocks. These are built up from long, flat bars set vertically
or nearly and spaced in accordance .vith the minimum width of water
passage through the turbine. The clear space between the bars
varies from 25 mm or 40 mm to 150 or 200 mm on very large
installations. These are used to prevent the ingress of floating and
other material to the turbine. In some cases where large diameter
turbines are used, the racks are omitted, but provision is made for
skimmer walls or booms to prevent ice and other material from
entering the unit.
- -'7
iKg
- I
IE
ir[Lr_
T - % I
L
'.t.
Fig. 11.3. The Hvdrn . Electrjc Schemes
(cji) Tail Race, The wtr after having done its usual'work
in
the turbine is discharged to the tail race which may lead it to the
same stream cr to another one
(viii) Dra ft Tubes
An air tight pipe of suitable diameter con
nectod to the runner outlet and conducting water down from the
wheel and discharging it under the suace of the water in t h e t at
322 WrnrNG, ESTEMATING AND COSTING
and have higher speed but for large machines generally vertical
construction is preferred.
Kaplan Turbine. In this type of turbine the drawback of con-
siderahle loss at low loads due to rotary motion of water in Francis
turbine is overcome and uniform ernciency ataliloads is maintained.
It is also a reaction type turbine and has gate and governing
mechanism similar to that of a Francis turbine. The difference
between Kaplan turbine and Francis turbine is that in the former
runner, the water strikes the turbine blades axiall y wherea3 the
latter receives water radially. This type of turbine is suitable for low
head and large flow plants. Kaplan turbine gives high speed than
ordinary Francis turbines. The characteristic features of Kaplan
turbine is that the gate opening and blade angle are adjusted
simultaneously by the governing mechanism. Its efficiency is about
90 per cent at all loads.
Propeller Turbine. In these turbines, the blades are casted
integrally with the hub. It is an axial flow turbine and has got no
provision for changing the runner blade angles while the turbine is
in motion. Its efTciency is about 92 per cent at full load and drops
to 65 per cent at half full load.
Classification of Hydro-electric Plants.
On thebasisof operating head, Hydro-electric power plants may
be classified as (i) low head (ii) medium head, and (iii) high he:il
plants. Though there is no definite line of demarcation for low,
medium and high heads but the head below 60 metres is con sid
as low he, the head above 60 metres and below 300-metres is
considered ai medium head and the head above 300 metres is
considered as high head.
F 0F, ES 4Y
04 H
S..'.
POWER HOU
GROSS HEAD
STREAM DEE
TAIL
CACE
TUR B I NE 1 1 -7,
other uses in the power station. Fans are used for ventilation of the
turbine and switchgear room or for cooling transformers. Oil pumps
iandie transformer oil through the cleaning and cooling system.
Cranes are used to lift heavy parts or replace them in position during
repairs. Water pumps are used for unwatering of turbine pits durir
repairs or inspection. Storage batteries are used to supply low
voltage d.c. power for switchgear control. These batteries are con-
stantly charged through a battery charging equipment using a
rectifier or motor generator set. Carbon-di-oxide cylinders and other
fire extinguishing equipment are used in case the fire breaks out.
The supply for the above auxiliaries is usually obtained from the
station transformer, which is installed solely for this purpose.
qESERVOIP(DAN
( DGE'\
I TANK
PE5SUP
HAPThEL VALVE HOUSE
PENS OCK
POWER HOUSE
2,592x 10 9 x 9.81
=
1 , 000 x 3,600
r=A <F x
=6x103x1x 0 6 555> 1(
\Vh€e k is theyield factor to allow
forr unoff and loss byoperic
:nd is eq9a1 to 0.65
Weight of water available per annum,
585 x 10'
W -18,57lkg
8760 x3.600
Head of water,H =4Ometres
Solution.
=225Xl0'XO.5=2.5xl06m
= 112.5x IO kgrn
=73.6x lO'kWh
Total energy available
8,760
32
WIRING, ESTIMATING AND COMING
LU
LOADING
BAY
0
LU Ili 417F , ' I,
LJ L
V) GLn
STORES
L_J /
.' .. z•.
COMPRESSORS
WATER COOLING ___
Pump =
HOT WELL WATER FUEL
OIL PUMP TO
COOLING STORAGE SERVICE
TOWERS TANKS O.H. TANKS
Fig. 11.7. The Layout of Diesel Plant
of large capacity say above 75 kW, tho compressed air is required
to be sent into the engine for starting purpose. Ba
can also be used for starting purposes. ttery driven motors
STEAM 'ISOLATOR
AToMIc I t
Ho T
STEP-UP
TRANSFORMER
IN ALTERNATOR
EXHAUST STEAM
PUMPL-NDR
WATER
PUMP FEED
METAL
COLD
cCCQLG \TowER
RIVER OR CANAL
Fig. 11.8. System of Atomatic Power Station.
The above metals become unstable and transformed to metals
of lower atomic weights like silicon, nickel etc. by Fission Process.
The splitting of 1 kg of Uranium (U) atoms yields 25 x 10' kWh
in heat form, which when conveyed to gas turbine or steam turbine
through molten metal and heat exchanger results in about 6.5 X
lO
AIR
OUTLET
jUEL 4
OIL __-1 COUPLING
C3JP.-NG Lj
TO R
CCMPRESSOP TURBINE
.3
L F
C co' •E
>
I,
•2
C
C
a CL
F0
I—
'I,
1
IUU •U fl V 0
L .. D U
.0 00
•—C
C
F
--
E . 2 cc
.'•:
C3
r.'
Et:
-
- U
C - Cs
-,
-..s
I-
C
F
C
C
c-i
] Q COG • Z OW V
I-
I. -A
L
1fl!1
—
C
0.
>CGG -
— - - - c
CZ . ts
I- -0 S- >-•L. 0
r. .
C 0
c-d
0I.
L
.0
C
0.
C . • C
I
—23
336
WIRING, ESTLMAT1NG8JW COSTING
—'a
'
L
'a
;
a C
:, C
JIH f4i1T1f1T!P:
j.
C'a
.rl
- C I-
cz
i.- E
C C
o
0' C
c3 0
C
E 'a C
E c
73 be
-_ —
a "
C > cz
-
C a-
'a C
- 'a C 'a - > E
a =
'a
'a
CC'a
POWER STATIONS AND SUBSTATIONS 337
/ND/CAT! pJ, )
ME Ti
& pR 'IAN/SM
CC MPA
MEN T
BUSBA PS
COMPARTMENT
'OMPAPTMENT
OR CURRENT T/R
NO CABLE SEALING
OXE$
H-pole and 4-pole structures with suitable platforms are used for
transformers of capacity upto 200 KVA. These substations are
cheapest, simple and smallest in size. All the equipment is of outdoor
type and mounted on the supporting structure of H.T. distribution
lines. Gang operating (G.O.) switch is used for switching "ON" and
'OFF of H.T. transmission line. H.T. fuse unit is installed for
protection of H.T. side. To control L.T. side iron clad low tension
switch with fuses of suitable capacity is installed. Lightning
arrestors are installed over the H.T. line to protectthe transformers
from the surges. The substations is earthed at two or more places.
The maintenance cost of substation is low and by using a large
number of such substations in a town, it is possible to lay the dis-
tributions at a lower cost. But owning to increase in number of
transformers, total KVA is increased, no-load losses increases and
the cost per KVA thus increased.
(b) Foundation Mounted Substation. These types of substa-
tions are used for primary and secondary transmission. Since
equipments required for such substations are veryheavy, therefore,
site selected for these substations must have a good access for heavy
tran2port. Owing to exposed bus-bars and other associated equip-
ment the clearances and the spacings are not only to be governed
by the operating voltage but also from the consideration of the
encroachment from outside.
The switchgear consists of circuit breakers of suitable type on
bo:h the-sides but now a days, the circuit breaker is dispersed on
the incoming side of the modem transformers from economy paint
of view. The isolating switches thus solve purpose.
3. Transformer. It is an essential part of a voltage conversion
substation. The transformer consists of two coils which are insulated
with each other and are placed on steel core. The steel core is made
of laminations. The steel cores with windings are placed in a con-
tainer. Insulating material viz, transformer oil is placed in the
container which provides insulation between the windings on the
core and the container. This oil also radiates out the heat of the
windings. For radiating the heat, tubes are provided along with two•
side of the container. The oil after heating expands and circulates
in the tubes and the container. When the hot oil is in the tubes, th
heat is radiated to the surroundings. The terminals of the windings
are brought out into porcelain-oil filled or condenser type bushings.
Transformer can be classified in various categories as below,
depending upon the type of core or type of cooling employed:
(a) In accordance with the type of core. Transformer can
POWER STATIONS AND SUBST T IONS 341
CORE
/1/6/I VOLTAGE
INSULATION
LOW VOL LOW VOLTAGE
FNS(/(A T/O,V
h?6H
VOL TAGE
Wit/DING
81611 VOLTS
WINDING
SHELL TYPt
CORE
INSt/LA NON
are provided to increase the dissipation area. Only this type ofcooling
is adopted for outdoor transformer.
(ii) Oil-filled Water-cooled. In this type of transformer, coils
through which cold water is circulated, are placed inside the con-
tainer in which oil is placed. The heat from oil is conveyed through
the water circulating in the coil.
(iii) Air Blast type. This type of cooling is adopted in high
voltage transformer of 33 KV or above. The transformer core and
windings are placed in a container which is open at two opposite
sides. The air is blown through it with the help of blower for cooling
purposes.
4. Advantages and Disadvantages of Outdoor Substa-
tions as compared to Indoor Substations. The outdoor sub-
station has the following advantages:
(i) The constructional work needed is much smaller than the
indoor substation.
(ii) Less quantity of building material is needed.
(iii) Installation cost of switchgear is low.
(w) Adequate space betwe, r two adjoining equipment can be
-t
(i) Bus-bars
Position
(b) Switching Apparatus
open closed
U
(iv) Three phase synchronous generator
$
(vii) Three phase steel core transformer with
star-delta connected windings ind
brought out neutral
i
69
4110*
(x) Three-phase three winding potential
transformer having two star connected
windings, each with therieutral brought
out and earth, and one winding con-
nected as an open delta.
347
1 c •. iie arA-igcmeflts
of various typical connections and of the simplest substation
schemes.
(i) Connection with isolator and fuse -
\
348 WIRING, ESTrM\T!NG AND COSTING
C . 10 2)0 c1-------1'
kw
-- .-
I -
For Transformer
of Lower Ratings
RELAY
'•
OUTGOING
FEEDERS
ft®E
CC REL A
n
TIME LAG RELAY
for stepping down the voltage for further distribution at main step
down transformer substations. Usually naturally cooled, oil
immersed, known as ON type, two windings three phase trans-
formers are used 'ip to the rating of 10 MVA The transformers of
rating higher than 10 MVA are usually air blast cooled. For very
high rating, the forced oil, water cooling and air blast cooling are
used. The transformers used are provided with on load tap changer
for regulating the voltage.
The transformers are generally installed upon lengths of rails
fixed on concrete slabs having foundation 1 to I metres deep.
14
352 WIRING, ESTIMATING AND COSTING
can also be said that the fuse protects the system from transformer.
The relays are also used to protect the power system equipment
from damage against fault at any point en route.
(Xiii) Switch Boards. The switch board consists of meters, relay
and control equipment as illustrated in Fig. 11.15(a). The essential
meters are placed at the bottom. The control equipment is generally
half-way between top and bottom, so as to facilitate the operation
A control desk may also be provided as shown in Fig. 11.15 cbs.
CONTROL
OESA
Fig. 11.15
'the materials generally used tot switchboard panels are slate
and asbestos ebon y , although all steel switch boards can also b€
used only where voltage is not more than 11 KV.
(xiv) Control Room. All equipments such as switchboard, carrier
current equipment, batteries etc. are housed in the control room,
which generally also has a basementhatch way (2 m 1.5 m approx.)
left in the floor for facilitating the installation. Below the switch
board, a slot of about 10 cm. may be provided for control cables etc.
'Fig. 11.16 represents layout of the control room, which is about 10
cmx 7 m.The basement maybe used as a battery room, or for storage
etc.
10. Substation Auxiliaries Supply. In small unattended
substations only a small amount of power for electric lighting during
regular periods of inspection, maintenance and repair is reqdired.
In regional substations, the electric power is required for the
auxiliaries--the lighting circuits, air blast fans of power trans-
forme:s, battery charging sets, oil servicing facilities, compressor
units in case of air blast circuit breakers, ventilating fans of the
substation buildings, water supply and heating system equipmer.L
etc.
10,77
----
L:.IIriiiL I
CARRIER CURRi,v7
EQUIPMENT El
FUTURE
,-FUTURE
::::::
CONTRO4
SwIrCH ' ,Qa.SOT
STA/L TO
8ASEI4EI.T CABLES i
/NCO/IiNG LINES
C B.
CIRCUIT SPEAKER
(SCS,) flO OR
ItO *Y
&IS BAR
C li
i Y)
STEP DOP/tv
TRANS
.1
Sc2 ' c3kif.
SVS BAR
J —/
CM.
1
[J(1
C,
(1$ COUPLE,'
r.'EAKEp
70 02 761 , c 8U&4,
LrJ
Cli.
STEP t'O.'/N
TRANSORME.'
'C2 C3.
--: • i_cd,
I I i 1 •••'—--'' 4 4 I
C
Fig. 11.18. Double bus arrangement of primary substation.
12. Ring Main System. In this s y stem two or more power
houe.s are connected in a fashion as so'.-i in Fi g .11.19. The gen-
erateu supply at 400 V is taken to step-up substations.
. 2<
I.- , Lu
..
II
E5L/.R
/ 7 -
->-: ffl'1' f_
&,ifT ST47I0WARY
& CONTACT .
CONTACT
FIXED -=---'"TE) G
CONTACTS.. CONUCT
III
FL A 5/i -\ ¼ PLJNC TLjR.
1.
CONDUC T
TOP CAP
FILLER PLUG
OI L LEVEL
tN 3, CA TUR
FL EXIBLE
CONNEC TION
riq
SPLIT
(LA KP5
4
•1 BüH/C16
FLANGE
J: \
ATE
LEVER
- X- V--
(a)
Fig. 11.22. Single break oil circuit breaker for
indoo r purposes.
POWER STATIONS AND SUBSTATiONS
3€ 1
OPPtA1i
OIL I.
CO7*I M
PUtL ROD I
rUNSOLATOR IH
TANK LINING
U I
-= ---
Fig. 11.22. (b) Single break outdoor type circuit breaker
VE CRA/
yE ARM
hR CUSHON
OIL LEVEL
Fig. 1123 (a). Double break oil circuit breaker for indoor purposes.
362
ESTIM'rmra A.ND COSTING
(b)
Fig. 11.23. Double break outdoor type circuit breaker.
2. It forms an explosive mixture with air.
3. Due to composition etc., the oil has to be kept clear and
requires maintenance
1 7 .Description of Oil Circuit
Breaker. In this type ofcircujt
breaker, a system of levers, toggles and rollers is utilised to close
the circuit breaker by raising the moving contacts against the action
of strong spring which open the contacts when the circuit breaker
is tripped mechanically or by action of relays and current trans-
formers.
POWER STATIONS AND SUBSTATIONS
ME TER
Two SWITCHES
FOR AMMETER
NO VOLTMETER
CALt
BOX
aliT-
6OING
Fig. 11.21. Side view of H.T. ii KV, 3-phase 3-wire oil circuit breaker.
Fig. 11.24 represents the general outlook of H.T. 11 KV oil
circuiL breaker. In Fig. 11.25 general outlook of H.T. 11 KV, HRC
fuse switch is represented.
feeder panel having
in Fig. 11.26, the general outlook of an L.T.
draw-out type incoming O.C.B. and many outgoing switches panel
has been shown.
364
WIRING ESTIMATING AND COSTING
CIO
-a
zo
Lu -
-J C
I.-.
-. b
LJL.
L
= . >
'-a
1 •-• .0
0 •fl 7)
q 7)
0 S' nb
- JOfft
0
C Lj
—<=------
'
A
cr.
—& —4,--1
2
zc 0- 0 >
-'
Ni -'--o-->4-
- -4
-4
366
WIRING, ESTIMATING AND COSTING
54 1 5 50t
NO.1234
NI.256 769
O(JTGQWG FEEDERS OUTGOING rEEDEPS
N .IC
1- •-O- >--'.---,- 2
9N 9 L %
--------- -- -
—---------------------------
- -
H
cc
L • - --- --- . :
Lo
0
L_-- -
N ;
0
cl
IL
TPPIh& .IP.E
I HYIZONT4.?U,4Tl
r4 FORMATION
1
T _
JUMPERS w-
r
:t 34kgJT
p41L 10-97,71
H
-
763,'
Ji -
JUMPERS
TR A N SFORMER
s q
H
=1i;5 , r "-^_
Fig. 11-31 -
25
:368
WIRING ESTIMATING AND COSTING
OUT GO ii
CABLE i CABLE FO
L.T. Line 3
No. I 2
55 Grin
Jumpers
I
Fig 11.32
POWER STATIONS AND SIJBSTATIO' 36
arm
27
W7 1 1 Iu1vI
-IMMIM112M. am.
I
H171
I,
IOperorg rod -
25mm Goh,pipe
j'
'ondl -rn Ioc.k'P9
orranqemehr
Steel pole
Fig. 1133
370
WIRING, ESTIMATING AND COSTING
VIEWAT
STEAK
A RN
BARE
JUMPERS
WrTH
BEADS
NNEL
/NSUL4 75
JUMPERS
2134
'I
ANGLE -V
L
\f.
IRON
SP4ING I
--
LL
Fig. 11.34
371
POWER STATIONS ANDJBSTAT1ONS
.iPICAL QUESTIONS
I. What are differet types of power stations? Write the advantages
and disadvantages of each type of power stat;Ofl.
circuits, a modern coal fed power plant can be
2. In how many rr.zin
divided? Explain abouteach circuit and give the schematic arrangement
of the same.
3. What are the fxtors which influence the choice of site for thermal
plants and give the layout diagram?
constituents of steam power station.
4. Explain about the
5. Ex p lain about the Hydro-electric Power station and what are the
factors u ..,. onsidereA for the location of hydro-electric power station?
(d) Cycles : 50
(e) Type of excitation : Hand excited
(J) Requirement of parallel operation : To be provided with
damper windings
(g) Coupling: Flexible coupling or Rigid coupling
The diesel engine and alternator as specified above are to be
mounted on a common base pla:e. The base plate supplied is to be
fabticated out of sheet steel and angle iron for the engine and
alternator. SuLEable foundation bolts for keeping the base plate in
posj'ion on the fu:ndation are to be pro L'ided. Furthersu itable engiae
alternator and coupling bolts to tight them on,fhe base plate should
-R- F' prooH-'L
(iii) Alterrator control paneL
(a) Totally et.:iosed sheet cubical type with door at the back
(b) Rus bars : Copper or aluminium of sufficient rating for the
above set
(c) Circuit breaker : Air circuit breaker complete with overload
and short circuit release
(d) Working voltage : 500 V
(e) Voltmeter: 0-500 V (moving iron.)
(I) Ammeter: 0-300 A (moving iron.)
(g) Other meter : kWh meter, KW meter, frequency meter,
power factor meter, moving coil ammeter for
exciter.
(e) Arrangement for synchronising and excitation : Set of
synchronising sockets and plug to be provided for parallel
operation of sets. Shunt field regulator with hand wheel
for varying the excitation also is to be provided.
S. Switches and 0. C. B. Specifications for various switches
and O.C.B. are given below:
375
GENERALSFIONS
4. L.T. G.J.2.
Indoor type with time limit Switch. L.T.
400 amps enclosed oil circuit breaker fitted with
(a) S. P. neutral link.
ib) 5 amps overload trips calibrated 1001200%.
(c) Time limit fuse totally enclosed.
(d) C.T. of rating 400/5 amps.
(e) Mechanical on and off handle with indicator.
. paper insulated
(I). Cable box suitable for 3core, 150 sq. mm
lead covered underground cable.
(g) 3 Nos. 500-Amp copper or aluminium bus-bars placed in a
metal clad enclosures.
5. H.T. 11KV Switch with H.R.C. Fuses. 11 KV A.C. metal
clad extensible automatic manually operated indoor oil fuse switch
unit of the tripping all phase type and breaking capacity 300 M.V.A.
with the following attachment
(a) Withdrawal fuse carrier complete with 3 Nos, 11KV suit
g capacity) oil tight striker-ablP.rtedHRC(ighupn
pin cartridges fuses.
(bi 3-300 Amps bus bars copper or aluminium, placed in a
metal clad chamber filled with compound.
(c) Mechanical off and on handle with indicator and padlocking
arrangement.
(d) Suitable oil level indicator.
. H.T. underground
(e) Two cable boxes for 3 core 25 sq. mm
PILCADSTA cable.
6. Ring Main T. off Switch. It should have the following
specifications.
H. T. 11 KV extensible type ring main T. off switch indoor type
comprises of one transformer control panel and 2 Nos. isolator panel
each fitted with:
(A) Transformer Control Panel. Consists of Automatic
manually operated oil fuse switch unit 300 Amps capacity having
following parts
(a) Withdra:al fuse carrier complete with 3 Nos H.R.C. oil
tight striker pin cartridges fuses.
(b) Three, 500 Amp bus bars, copper aluminium placed in a
metal clad chamber filled with compound.
376
WIRING E STIMATING AND COST!NG
(c) Mechanical on and off handle with
in dicator and padlocking
arrangement.
(d) Suitable oil level indicator.
(e) Two cable boxes each suitable for 25 mm
2 PILCADST
HT underground cable.
(B) Isolator pannel 2 Nog . for each unit.
of the following: It should comprise
(a) Metal clad non automatic type load breaking, fault making
oil immersed isolator assisted with spring.
(b) Three 500 Amp bus bars of copper or aluminium placed in
a metal clad chamber filled with compound
(c) Mechanical o p erati ng h andle
devices to bring it in the
positions—On Off, Earth and Test.
(d) One no. cable box suitable for 25 mm2
underground cable.
P1L CADSTA, H.T.
7. H.T. Feeder Panel. It can be specified as under:
(a) Type : Indoor.
(b) System :..l I KV, 50 cycles, 3-phase ;
3-vrire.
(c) Incoming panel with following accessories attachment
(i) Vertical dropdown drawout free handle mechanism oil
circuit breaker capacity 40 amps.
(ii) 3 Nos. of 5 amps. overload trips calibrated 100/200%.
(iii) 3 Nos. of time limit fuses.
(iv) 3 Nos. of cur-rent transformer ratio 40/5 amps accuracy.
(v) Voltmeter: 0-15 KY.
(vi) Ammeter: 0-40 amps.
(vii) Rotary selector switch.
(viii) 3-phase draw-out type oil immersed potential transformer
ratio 1 1,000V/110v with H.V. and L.V. fuses.
(ix) Cable Box indoor type suitable for 3-core PILCADSTA 50
sq. mm U/G cable.
(x) Metal clad air insulated 3 Nos. bus bars suitable for working
voltage 11 KY, capacity 50 amps.
(d) 3 Nos. outgoing panne] each with following accessories
attachment.
(1) Vertical dropdown drawout free handle mechanism oil
circuit breaker, capacity 40 amp.
GENERAL SPECIFICATIONS 377
379
GENERAL SPECIFICATIONS
Table 12.1
Size of galvanised
Working I In.sulatr size in m'v'- mild steel spindle in
Voltage
Maxim urn Dia. of Top
Height dia. Dia. ofgroou€ shankcordon
Ithread
Side Top
500 V 63.50 57.15 9.52 15.885 15,885
1100 V 82.55 69.85 15.885 15.885 35.885 15.885
3,300 V 8255 8552 15.885 15885 28.575 19.05
6,600 V 131.70 1).85 19.05 19.05 22.575 19.05
1.000 V 168.5 146.06 19.05 19.05 22.515 19.05
Table 12.2
Working Size of shackle insulator7
Pressure Size ofgaluani3ed steel
Urapsand bolts in mm.
Height
Maxiazurn Dia.of
dia. !groove for
Section of
s:rQp
fño
bolt
I
conductor
500 V 5239 6350 635
1,100 V 25.40 x 1.60 9.52
78.21 14-29 31.75 x 3.18
3,300 V 106.36 I 25.40 12.70
6,600 V 41.36 x 4.80 19.05
139.70 127.00 I 12.70
11,000 V 152.40 J 127.00 I 16.00
38.10 x 4.80
38.10 x 4.80
19.05
19.05
14. Disc type Insulators. Disc type insulators are made of
porcelain, vitreous white or brown in colour and each disc of size
152.40 mm dia. should be in a position to withstand 11,000 volts.
The no. of disc used depends upon the working voltage. These car
be specified as tinder
Working voltage: 11 KV or 33 KIV
Dia. of disc 152.40 mm
No. of discs : 1 or 3
Other fittings : Equipped with tension clamps.
15. Stay Assembly. It can be Specified as under:
(a) Stay bow.
Dia. of rod :15 mm
(j )
(ii) Length :37.5 cm.
(b) Stay plate.
(i) Cross-section : 22.5 cm x 22.5 cm or 30 cm x 30 cm
(ii) Thickness of the plate :6.5 mm
(c) Stay or Anchor rcxl
(i) Dia. of rod: 16 mm or 19 mm
(ii) Length :60 cm.
One end of the stay rod should be threaded and have a suitable
bolt and the other end should be joined with the stay plate by means
of forged head as shown in Fig. 8.18.
Table 12.3
Method of Method ofspec.
Stranding no. and were dia. ecifving by fyig 5y trd
size I narre
Alumnum I - Steel
No. a. Tho
Rim inch I No. MM. L,.cl.
Squirrel
0 2.11 0. C S3 1 2.11 0.083 6/1 x .083
6/1 x .102 Weasel.
6 2.59 0.102 I 2.59 0.102
6 3.00 0.118 1 3.00 0.118 6/1 x .118 Fer,ot
6 3.35 0.132 1 3.35 0.132 6/1 x .132 Rabbit
6 3.66 0.144 1 3.66 0.144 6/1 x .144 Mink
6 3.99 0.157 1 3.99 0.157 6/1 x .157 Beaver
Other
6 4.19 0.166 1 4.19 0.166 6/1 x .166
26 2.54 0.100 1 2.54 0.100 26/7 x .100 Coyote
30 3.00 0.118 7 3.00 0.118 3017 x .118 Panther
TYPICAL QUESTIONS
1. What do you understand by the term specifications'?
2. What are the various £quipments used in a substation ? Specify
any of the equipment.
3. Draw out the specifications of a 0.4111 KV transformer 300 KVA
capacity.
4. Draw out the specifications of a diesel generating set.
5. It is required to procure a L.T. feeder panel, capacity 400 Amp.
for four outgoing feeders each ofcapcity 200 Amps. Chalk out the
specifications for the same.
6. Chalk out the specifications for L.T. and H.T. underground cable.
7. How would you specify (a) stay assembly and (b) A.C.S.R.
8. Write down the specifications of a main switch to control consumer
two-wire mains for his connected light and fan load of 1kW at
230 V.
9. Write down briefspecifications ofa switch for controlling 100 watts
230 volts lamp in cleat wiring.
10. How would you specify (a) Energy Meter (5) Fuse wire (c) Cond.nt
(d) Metal shades.
11. Write down brief specifications of the following material
(a) Earth plate required for earthing LI. lines.
(b) 5 Amp plug used in concealed conduit.
(c) 500 Amp 3-phase A.C. kWh meter 400 volts for use in a fac-
tory.
(d) V.I.R. wire used in domestic purposes.
12. Wrte down brief specifications for
(a) Insulator for 11KV.
(b) Stay rod.
13. Write down brief specifications for
(i) Tansfbrmer.
(ii) Generator.
(iii) Energy meter for domestic use.
(iv) Switch.
14. Writedown brief specifications for:
(a) Earthing material for grounding a small workshop.
(b) Stay Insulator for L.T. lines.
(c) Insulator for 11 KV line.
(d) Lighting arrestors for 11 KV line.
(e) Circuit breaker for L.T. line.