Datasheet

Power cable DK05 Basic


Power cable, XLPE insulated, flexible copper conductor, halogen free 300/500 V

based upon VDE0276-604. Used in low voltage installations, for indoor use in visible and hidden installation, and in the open, shielded from direct sunlight. Suitable for laying in the ground.
May be bricked in and embedded directly. Not suitable for embedment in vibrated concrete. The installation must be carried out properly and by qualified persons and using suitable materials.

Characteristics Properties Unit

Conductor material Copper


Conductor category Class 1 = solid
Core insulation material Polyolefin
Core identification according to HD 308 S2 Yes
Protective conductor Yes
Max. conductor temperature 90 °C
Screen No
Armouring/reinforcement None
Material outer sheath Polyolefin
Colour outer sheath Grey
Reaction-to-fire according to EN 13501-6: Class Eca
Halogen free (acc. EN 60754-1/2) Yes
Flame retardant In accordance with IEC/EN 60332-1-2
Datasheet

Characteristics Properties Unit

Low smoke (acc. EN 61034-2) Yes


Permitted cable outer temperature during assembling/handling 5 => 70 °C
Permitted cable outer temperature after assembling without vibration -20 => 70 °C
Nominal voltage U0 300 V
Nominal voltage U 500 V
Shape of conductor Round
Suitable as installation cable Yes
Certified for shipboard application No
Suitable as medium-voltage cable No
Suitable as high-voltage cable No
Certified as airport lighting cable No
Minimum bending radius 12 x Außen-Ø
max. short circuit temperature 250 °C

Conductor Outer
Bruttogewicht pro Conductor Metal Nominal cross Number of Individual Net
resistance at 20 Core colour diameter Paletteinheit Weight Packing
Paletteinheit Diameter number section conductor cores length weight
°C approx.

Copper
465.24 kg 2.5 mm 7.41 Green/yellow 2.5 mm² 1 5 mm 12,000 m 36.87 100 m 4 kg Ring
24
Copper
788.11 kg 1.5 mm 12.1 1.5 mm² 3 7 mm 9,600 m 79.72 100 m 8 kg Ring
43
Copper
630.3 kg 2.5 mm 7.41 2.5 mm² 3 8 mm 5,400 m 112.5 100 m 11 kg Ring
72
Copper
375.426 kg 2.5 mm 7.41 2.5 mm² 3 7 mm 3,000 m 112.5 500 m 56 kg Drum
72
Copper Cut Ring,
1.5 mm 12.1 1.5 mm² 5 9 mm 168.53 169 kg
120 length Drum
Copper
932.86 kg 1.5 mm 12.1 1.5 mm² 5 10 mm 5,400 m 168.53 100 m 17 kg Ring
120

Waskönig + Walter Kabel-Werk GmbH u. Co. KG DK05 Basic


Ostermoorstraße 77, 26683 Saterland
Phone: +49 4498 88-0 | Fax: +49 4498 88-900 Status:: 21.02.2023
https://www.waskoenig.de Subject to technical alterations
Datasheet

Conductor Outer
Bruttogewicht pro Conductor Metal Nominal cross Number of Individual Net
resistance at 20 Core colour diameter Paletteinheit Weight Packing
Paletteinheit Diameter number section conductor cores length weight
°C approx.

Copper
543.516 kg 1.5 mm 12.1 1.5 mm² 5 9 mm 3,000 m 168.53 500 m 84 kg Drum
120
Copper Cut Ring,
1.5 mm 12.1 1.5 mm² 7 9 mm 146.99 147 kg
101 length Drum
Copper
816.55 kg 1.5 mm 12.1 1.5 mm² 7 8 mm 5,400 m 146.99 100 m 15 kg Ring
101

Waskönig + Walter Kabel-Werk GmbH u. Co. KG DK05 Basic


Ostermoorstraße 77, 26683 Saterland
Phone: +49 4498 88-0 | Fax: +49 4498 88-900 Status:: 21.02.2023