Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Actuador Caldera SQN31.401 A 2760

Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

7 808

ISO 9001

Version with integrated potentiometer Basic version

Actuators SQN3...
SQN4...
supplementary Data Sheet 7921 «Potentiometers ASZ...»

Electromotoric actuators for air dampers or for fuel / air ratio control with oil or
gas burners of small to medium capacity.

· Versions for integrating a potentiometer


· Running times from 4.5 to 120 seconds
· All versions feature:
– Auxiliary switches and integrated relays (optional)
– Geartrains which can be disengaged
– Internal and external position indication
– Easily adjustable end and auxiliary switches

The SQN3... / SQN4... and this Data Sheet are intended for use by OEMs which
integrate the actuators in their products!

Use

SQN30... Counterclockwise Up to 3 Nm
SQN31... Clockwise Up to 3 Nm
SQN41... Clockwise Up to 6 Nm

The actuators are used primarily for controlling the amount of combustion air:
- Load-dependent in connection with P-PI or PID controllers,
such as the RWF40...
- Directly with the help of the different types of burner controls,
such as the LOA..., LMO..., LMG... or LFL...

CC1N7808en
Siemens Building Technologies
30.07.2002 HVAC Products
Warning notes

To avoid injury to persons, damage to property or the environment, the following


warning notes should be observed!

Do not interfere with or modify the actuators!

· Before performing any wiring changes in the connection area of the actuators,
completely isolate the equipment from the mains supply (all-polar disconnection)
· Ensure protection against electric shock hazard by providing adequate protection
for the connection terminals and by securing the housing cover
· Check wiring and all safety functions prior to commissioning and each time a fuse
has been changed
· Fall or shock can adversely affect the safety functions. Such actuators may not be
put into operation, even if they do not exhibit any damage

Mounting notes

· Ensure that the relevant national safety regulations are complied with

Installation notes

· Installation work must be carried out by qualified staff

Commissioning notes

· Commissioning and maintenance work must be carried out by qualified staff

Service notes

· If a potentiometer is subsequently fitted, the user must change the type reference
of the actuator as described in section «Mechanical design» using a permanent
felt-tip pen
· Check wiring and all safety functions each time an actuator has been replaced

Norms and standards

CE conformity according to the directives of the European Union


- Electromagnetic compatibility EMC (immunity) 89 / 336 EEC
- Low-voltage directive 73 / 23 EEC

Disposal notes

The actuator contains electrical and electronic components and may not be disposed of
together with household garbage.
Local and currently valid legislation must be observed.

2/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Mechanical design

Housing - Made of impact-proof and heat-resistant plastic


- Accommodating:
– The reversible synchronous motor with the geartrain, which can be disengaged
– The camshaft of the control section
– The relays (depending on the type of actuator)
– The switches which, via a printed circuit board, are connected to the terminals

Drive motor Scales beside the cams facilitate adjustment of the switching points.
An additional scale at the end of the camshaft serves for internal position indication.

A potentiometer, which can subsequently be integrated, delivers an electrical signal


which gives the position of the drive shaft (with the types of actuators prepared for fit-
ting a potentiometer).

A disk with a groove is attached to the head of the camshaft or to the potentiometer,
thus making visible the position of the actuator’s drive shaft from outside (refer to pho-
tos on the front page).
The actuator has 2 openings for cable entry glands Pg9 and Pg11.

Type of motor - Reversible and locking-proof synchronous motor

Coupling - Drive shaft can be manually disengaged from geartrain and motor
- Automatic reengagement

Adjustment of - By means of adjustable cams


switching points - Scales beside the cams indicate the angle of the switching point

Position indication - Internally:


Scale at the beginning of the camshaft on the geartrain side

Electrical connections - Screw terminals

Geartrain - Maintenance-free

Drive shaft - Made of black-finished steel.


- Ready fitted to the front of the geartrain
- Different versions available

Mounting and fixing - Front of geartrain is used as the mounting surface


- Actuator is secured via through-holes

ASZ...7... - Coiled rotary type potentiometers


- Resistance track and wiper are accommodated in a dust-proof casing

ASZ...8... - Conductive plastic potentiometers

3/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Fitting the Certain types of actuators are supplied ready prepared for fitting a potentiometer.
potentiometer These actuators differ from the basic version only in that the housing is higher and
that they are prepared for accepting a potentiometer. Accessories are not required.

The required potentiometer is to be ordered as a separate item (refer to «Accesso-


ries»).

In that case, the third digit after the dot in the actuator’s type reference will change from
«1» to «2».

Example:
SQN31.111A2700 ® basic version
SQN31.112A2700 ® version for fitting a potentiometer

Conversion by the user Users have the choice of converting a basic version to a version for fitting a potenti-
ometer. For that purpose, a conversion kit AGA32 is available (refer to «Accessories»
and «Example» under «Ordering»).

Conversion of the type reference must be made with a permanent felt-tip pen (impor-
tant for service work).

Type code

Do not use this type code for ordering. It only serves as a general guide for creating
type references.

SQN3 1 . 1 2 1 A 27 3 0

Version
0 Standard

Drive shaft no. 1)

Voltage / frequency
17 AC 110 V / 50...60 Hz
27 AC 230 V / 50...60 Hz
35 AC 230 V / 50 Hz; max. 50 % on time

Series

Height of housing
1 110 mm
2 125 mm, for fitting potentiometer

Internal diagram2)
2 Diagram no.

Running time, 90°, 50 Hz


1 4.5 s
2 12 s
3 15 s
4 30 s
9 120 s
3)
Direction of rotation
7808s01e/0702

0 Counterclockwise
1 Clockwise

Actuator generation
SQN3 Standard geartrain
SQN4 Heavy-duty geartrain

¹) Refer to «Dimensions» ²) Refer to «Connection diagrams» ³) When facing the drive shaft

4/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Type summary

Actuators SQN30... / basic versions – not suited for fitting a potentiometer (other types on request)

Diagram Drive Direction of Running Operating Holding Relay 9) AS 10) AC 220 V -15 % AC 100 V -15 %
7)
shaft ¹) rotation time torque torque AC 240 V +10 % AC 110 V +10 %
at 50 Hz ²) (max.) 50...60 Hz 50...60 Hz
no. no. for 90° Nm Nm Pcs. Pcs. Type reference 5) Type reference 5)
11) 2
1 0 4.5 1 0.8 1 SQN30.111A2700 SQN30.111A1700
11)
1 0 4.5 1.5 0.8 1 2 SQN30.111A3500 3)
2 6) 0 11)
4.5 1 0.8 2 1 4) SQN30.121A2700 SQN30.121A1700
6) 11)
2 0 4.5 1.5 0.8 2 1 4) SQN30.121A3500 3)
11)
3 0 4.5 1 0.8 2 1 4) SQN30.131A2700 SQN30.131A1700
11)
5 0 4.5 1 0.8 2 1 4) SQN30.151A2700 SQN30.151A1700
11)
5 0 12 1.8 1.8 2 1 4
) SQN30.251A2700 SQN30.251A1700
11) 3
0 0 30 3 3 --- SQN30.401A2700
11) 3
0 3 30 3 3 --- SQN30.401A2730
11)
3 0 30 3 3 2 1 4) SQN30.431A2700
11)
5 0 30 3 3 2 1 4) SQN30.451A2700

Actuators SQN31... / basic versions – not suited for fitting a potentiometer (other types on request)

Diagram Drive Direction of Running Operating Holding Relay 9) AS 10) AC 220 V -15 % AC 100 V -15 %
shaft ¹) rotation 7) time torque torque AC 240 V +10 % AC 110 V +10 %
at 50 Hz ²) (max.) 50...60 Hz 50...60 Hz
no. no. for 90° Nm Nm Pcs. Pcs. Type reference 5) Type reference 5)
0 0 Clockwise 4.5 1 0.8 --- 3 SQN31.101A2700 SQN31.101A1700
1 0 Clockwise 4.5 1 0.8 1 2 SQN31.111A2700
1 6 Clockwise 4.5 1 0.8 1 2 SQN31.111A2760
2 6) 0 Clockwise 4.5 1 0.8 2 1 4) SQN31.121A2700
2 6) 3 Clockwise 4.5 1 0.8 2 1 4) SQN31.121A2730
2 6) 6 Clockwise 4.5 1 0.8 2 1 4) SQN31.121A2760
5 0 Clockwise 4.5 1 0.8 2 1 4) SQN31.151A2700 SQN31.151A1700
5 3 Clockwise 4.5 1 0.8 2 1 SQN31.151A2730
2 6) 0 Clockwise 12 1.8 1.8 2 1 4) SQN31.221A2700
2 6) 3 Clockwise 12 1.8 1.8 2 1 4) SQN31.221A2730
5 0 Clockwise 12 1.8 1.8 2 1 4) SQN31.251A2700 SQN31.251A1700
5 3 Clockwise 12 1.8 1.8 2 1 SQN31.251A2730
5 0 Clockwise 15 1.8 1.8 2 1 4) SQN31.351A2700
0 0 Clockwise 30 3 3 --- 3 SQN31.401A2700 SQN31.401A1700
0 3 Clockwise 30 3 3 --- 3 SQN31.401A2730
0 6 Clockwise 30 3 3 --- 3 SQN31.401A2760
1 0 Clockwise 30 3 3 1 2 SQN31.411A2700
1 3 Clockwise 30 3 3 1 2 SQN31.411A2730
6 0 Clockwise 23 2.5 2.5 2 --- 4) SQN31.762A2700
4 0 Clockwise 120 6 6 1 2 SQN31.941A2700
0 3 Clockwise 12 1.8 1.8 --- 3 SQN31.201A2730

Actuators SQN30... with high cover for fitting a potentiometer

Diagram Drive Direction of Running Operating Holding Relay 9) AS 10) AC 220 V -15 % AC 100 V -15 %
shaft ¹) rotation 7) time torque torque AC 240 V +10 % AC 110 V +10 %
at 50 Hz ²) (max.) 50...60 Hz 50...60 Hz
no. no. for 90° Nm Nm Pcs. Pcs. Type reference Type reference 5)
11) 3
0 0 30 3 3 --- SQN30.402A2700 SQN30.402A1700
11)
0 3 30 3 3 --- 3 SQN30.402A2730
11) 3
0 6 30 3 3 --- SQN30.402A2760

5/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Actuators SQN31... with high cover for fitting a potentiometer

Diagram Drive Direction of Running Operating Holding Relay 9) AS 10) AC 220 V -15 % AC 100 V -15 %
shaft ¹) rotation 7) time torque torque AC 240 V +10 % AC 110 V +10 %
at 50 Hz ²) (max.) 50...60 Hz 50...60 Hz
no. no. for 90° Nm Nm Pcs. Pcs. Type reference Type reference 5)
0 0 Clockwise 30 3 3 --- 3 SQN31.402A2700 SQN31.402A1700
0 0 Clockwise 4.5 1 0.8 --- 3 SQN31.102A2700 SQN31.102A1700
0 0 Clockwise 12 1.8 1.8 --- 3 SQN31.202A2700 SQN31.202A1700
5 0 Clockwise 12 1.8 1.8 2 1 4) SQN31.252A2700 SQN31.252A1700

Actuators SQN4...

Diagram Drive Direction of Running Operating Holding Relay AS 10) AC 220 V -15 % AC 100 V -15 %
shaft ¹) rotation 7) time torque torque 9) AC 240 V +10 % AC 110 V +10 %
at 50 Hz ²) (max.) Pcs. 50...60 Hz 50...60 Hz
no. no. for 90° Nm Nm Pcs. Type reference 5) Type reference 5)
0 0 Clockwise 120 6 6 --- 3 SQN41.902A1700
4 0 Clockwise 120 6 6 1 2 SQN41.941A2700

Legend to ¹) Refer to «Dimensions»


«Type summary» ²) At 60 Hz, running times are about 20 % shorter
³) On time at
- AC 220 V -15 % / +10 % and 50 Hz – max. 50 %
- AC 240 V -15 % / +10 % and 50 Hz – max. 35 %
4)
Additional switches for special applications (refer to «Connection diagrams»)
5)
For actuators suited for fitting a potentiometer (refer to «Mechanical design»)
6)
Actuators with diagram no. 2 may not be used in connection with the LOA26...
7)
When facing the drive shaft and when control voltage is fed to end switch I
8)
Types in normal print and other types on request
9)
Built-in relays
10)
Free auxiliary switches (in addition to the 2 end switches)
11)
Counterclockwise

6/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Ordering

When ordering, please give type reference of actuator and accessories according to
«Type summary».

Example SQN30.402A2730 - Actuator with counterclockwise rotation


- Drive shaft no. 3
- Running time 30 seconds
- Internal diagram no. 0
- AC 220 V
- For fitting a potentiometer
ASZ8.703 Coiled potentiometer 220 W / 90° ) , triple pole

Example of SQN30.401A2730 - Actuator, not suited for fitting a potentiometer


conversion by the user AGA32 - Conversion kit
ASZ8.703 - Potentiometer

Potentiometers must be ordered as separate items.

Accessories

Adapter In addition to the actuator, the following items are to be ordered separately:

Conversion kit AGA32


- For converting a basic version to a version for fitting a potentiometer (refer to Data
Sheet 7921)

Service kit AGA33


- For replacing old potentiometers ASZ...5... / ASZ...6... by new potentiometers
ASZ...7... and ASZ...8... (refer to Data Sheet 7921)

7/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Technical data
General actuator data

Actuator Mains voltage AC 220 V –15 %...AC 240 V +10 %


AC 100 V –15 %...AC 110 V +10 %
Mains frequency 50...60 Hz ±6 %
Type of motor synchronous motor
Power consumption 6.5 VA
Angular position max. 160°
Mounting position optional
Degree of protection IP 40 to DIN 40050, provided adequate cable
entries and screws are used
Cable entry suited for 1 x Pg9 and 1 x Pg11, no locknut
required
Cable connections screw terminals for wires having a cross-
sectional area of 0.5 to 2.5 mm²
Ferrules matching the dia. of the stranded wire
Direction of rotation refer to «Type summary»
Torques and holding torques refer to «Type summary»
Running times 4.5...120 s for 90°
Coupling drive shaft / geartrain by means of a pin
Weight (on average) approx. 800 g

End and Number of end switches 2


auxiliary switches Number of auxiliary switches 1...3
Actuation via camshaft
Switching voltage AC 24...250 V
Terminal rating at cos j = 0.9: under load ON, with no load OFF
- starting current 14 A
- operating current 2 A
Under load ON...OFF
- starting current 7 A
- operating current 1 A
Adjustment of cams in increments of 1°

Norms and standards Environmental conditions


Transport DIN EN 60 721-3-2
Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -50...+60 °C
Humidity < 95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions class 3K5
Mechanical conditions class 3M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

Function

The synchronous motor drives the actuator’s drive shaft via the geartrain. The attached camshaft
actuates the end and auxiliary switches. The switching position of each end and auxiliary switch
can be adjusted within its working range via the associated cam. Some of the actuator versions
are equipped with electronic modules that perform auxiliary functions in connection with the end
and auxiliary switches or with external devices, such as controllers (refer to «Connection dia-
grams»).

8/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Connection diagrams
No. ­ ® LOA... / LMO... 2-stage operation
Prepurge at low-fire position «KL» (see «S5»)
LOA... / LMO...
1) Program sequence with no oil preheater
1 2 10 8 3 7 6 4 5 11 12
2) LOA... / LMO...
QRB
OW
SB A B C D
R
W
W
OH Z OH
t4

R AL M BV1 OW
tw t1
S2)
LR
M
4) 4)
LR

BV1

SB BV2
BV2
TSA
HS FS
N 1 2 6 7 5 4 3
I 0 b1 b2 B I 100 %
M IV BV2

7808d01/1201
3) IV S4)
N L III
IV III min.
LK
a b a b II 0%

a3 a1 A
1) Not suited for use in connection with LOA26...
a2
II I V
2) Broken lines: With oil preheater
M 3) Cams III and IV are rigidly connected
a b a b a b
2 LK 4) Voltage at terminal no. 6 of SQN3...
SQN3x.x2xAxxxx 7808a09/0502
LKP

entspr. 6°
NL I I
3) Vb
S4) Va Vb
IV
KL III S5) III
BV2
ZU
t1 TSA 7808d02/0202 t
t4

No. ­ ® LMG21... / LMG25... / LGB21... 2-stage operation


Prepurge at low-fire position «KL»
LMG21.../25... LMG21... / LMG25... / LGB21...
12 2 10 8 3 6 11 9 7 4 5 1 SB A B C D
R
FE W
EK2 tw t1 t4
LP
AL M Z M
BV1 4) 4)
GP LR

BV1
R/W LR
BV2
TSA

BV2 FS
SB N 1 2 6 7 5 4 3
I 100 %
HS b2 B IV BV2
7808a13/0502

b1 M IV
7808d10/1201

III min.
0 I 3) LK
III IV II 0%
a b a b
N L
A
a3 a2
3) Cams III and IV are rigidly connected
II I
4) Voltage at terminal no. 6 of SQN3...
V
MS
a b a b a b LKP
entspr. 6°

2 LK
NL I I
SQN3x.x2xAxxxx 3)
Vb
IV S4) Va Vb

KL III S5) III

ZU
t1 TSA 7808d09/0202 t
t4

For notes on «S1...S5», refer to «Notes on connection diagrams»

9/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Connection diagrams
No. ° ® LMG22... / LGB22... / LGB32... Modulating or 2-stage operation «S1»
Prepurge at nominal load position «NL»
LMG22... / LGB22... / LGB32... LMG22... / LGB22... / LGB32...
SB A B C D
12 2 10 8 3 6 11 9 5 7 4 1
R/W
GP
FE tw t1
GP EK2 LP Z
M
AL
S1)
LP
R/W M BV1
LR
BV1

LR

* FS
BV2 *
SB
N 1 8 2 7 5 6 3 4 9 2) 9
HS
R3 I 100 %

7808d14/1201
R1

0 I M

7808a15/0502
b1 b2 III min.
B LK
N L
II 0%
A a1 a2 RV

LKP
M LK
I II III V 1) NL I I
5
RV
SQN3x.x5xAxxxx
KL III III

* Note:
ZU II
With 2-stage modulating burners (with gas control damper «RV»), «BV2» t
t1 t4 7808d13/1201
is not used and the broken connecting line between terminals (*) does TSA
not apply.

1) For arrangement with modulating operation, refer to «S1» Program sequence diagrams show modulating operation.
2) Actuator with connection diagram no. 5 and last digit of type Dotted line: 2-stage operation
reference = 6 (8th character after the dot), uses other terminal
markings

No. ± ® LMG22... / LGB22... / LGB32... Modulating or 2-stage operation «S1»


Prepurge at nominal load position «NL»
LMG22... / LGB22... / LGB32... LMG22... / LGB22... / LGB32...
SB A B C D
12 2 10 8 3 6 11 9 5 7 4 1
R/W
GP
FE tw t1
GP EK2
LP M
AL
S1)
LP
R/W M BV1
LR
BV1

LR

2)
FS
Z
SB
N 1 8 2 7 5 6 3 4 9 9
HS
I 100 %
7808d12/1201

R1 R3
0 I M
7808a14/0502

b1 b2 III min.
B LK
N L
II 0%
A a1 a2 RV

LKP
2)

2)
M LK
I II III V I I
entspr. 5°

1) NL
6
RV
SQN3x.x6xAxxxx
V
KL III III

1) Arrangement for modulating and 2-stage operation is identical.


ZU II
No «BV2», refer to «S1» t
t1 t4 7808d11/1201
2) Cams of switches III and V are rigidly connected. This is re- TSA
quired to ensure that the flame will be established only when Program sequence diagrams show modulating operation.
damper ignition position «KL» is reached, that is, that ignition Dotted line: 2-stage operation
takes place at low-fire «KL»
If the contacts of switch V welded in position 4 ® 9, supervision of the ignition load position would be negated and it would not be de-
tected in operation. This means that the circuit is not safety-related but only used for supervision purposes. The user must ensure that in
the event of failure (should the burner ignite at nominal load «NL»), no damage will occur.

For notes on «S1...S5», refer to «notes on connection diagrams»

10/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Connection diagrams
N0. 0 ® LFL... / LGK16... / LAL... / LOK16... 2-stage or modulating operation
Prepurge at nominal load position «NL»

LFL... / LGK16... / LAL... / LOK16... LFL... / LGK16... / LAL... / LOK16...


A B C D
1 2 9 11 20 10 8 18 19
R
M1
M2

Z
S1)
LR
BV1
BV1
LR

RV
FS
t1
I 100 %
S1) M IV

7808d05/1201
BV2 III min.
SB
LK II 0 %

HS
N 3 1 2 4 10 8 9 13 11 12 7 5 6
I 0

LKP
N L
NL I I I

KL III III

I II III IV V
M ZU II
~ t1 TSA 7808d06/1101 t
t4
0

SQN3x.x0xAxxxx 7808a11/0502

Program sequence diagrams show modulating operation

No. ¬ ® LFL... / LGK16... / LAL... / LOK16... 2-stage operation


Prepurge at nominal load position «NL»

LFL... / LGK16... / LAL... / LOK16...


LFL... / LGK16... / LAL... / LOK16...
A B C D
1 2 19 9 20 11 10 8 18 R
M1
M2
Z
BV1

S2)
LR
LR
BV1 BV2
FS
t1
I 100 %
M
IV 7808d07/1201
SB III min.
LK
HS BV2 II 0 %

I 0 N 7 3 1 6 5 2 4 10 8 9 13 11 12

N L

LKP
NL I I

IV IV IV IV
I II III IV
M KL III III
~
1 ZU II
t1 7808d08/0202 t
7808a12/0502 TSA
SQN3x.x1xAxxxx
t4

For notes on«S1...S5», refer to «Notes on connection diagrams»

11/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Connection diagram
No. ® ® TMG740 / TMO720 2-stage operation

Prepurge at nominal load position «NL»

· TMG... and TMO... are devices of other manufac-


TMG740
ture. They are neither made nor supplied by
TMO720 21 2)
Siemens. Combination with the type of Siemens
8 13 14 9 15 4 6 12
actuator proposed here must be checked with the
supplier of the TMG... or TMO... while taking into
M consideration safety aspects and the current ver-
NL S2)
sion of the burner control.
BV2
The user assumes full responsibility for this ap-
L2 plication.
N 7 1 6 5 2 3 4 8
LKP
NL I I
B V

1)
V V V

entspr. 5°
b a IV IV IV IV
KL
III
a1 A a2 III III III
ZU
7808d03/0202
II II t

I II III 1) IV V
M
7808a10/1201

b a b a
3

SQN3x.x3xAxxxx
1) Cams of switches III and IV are rigidly connected
2) TMO720 terminal no. 6
TMG740 terminal no. 21

No. ¯ ® Special application

N 7 3 1 6 5 2 4 10 8 9 13 11 12

I II III IV
M
~
4
SQN4x.x4xAxxxx 7808d04/1101

For notes on «S1...S5», refer to «Notes on connection diagrams»

12/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Legend No. ­ Number corresponds to the designation number or letter of the internal circuit of the SQN3...
(second character after the dot in the type code)
AL Remote indication of fault (alarm)
BV1 Fuel valve stage 1
BV2 Fuel valve stage 2
EK2 External remote reset button
FE Ionization probe
FS Flame signal amplifier
GL Gas / air ratio controller
GP Gas pressure switch
HS Main switch
KL Low-fire
L Live conductor
LK Air damper
LKP Air damper position
LP Air pressure switch
LR Load controller (also refer to «S1»)
M Burner or fan motor
M Actuator’s synchronous motor
M1 Without postpurge
M2 With postpurge
N Neutral conductor
NL Nominal load
OH Oil preheater
OW Oil preheater’s readiness contact
QRB... Photoresistive flame detector
R Temperature or pressure controller
Relay
RV Control damper
SA Actuator
Fuse
SB Safety limiter
ST... Stage
t... / T... Program times (refer to the Data Sheet of the relevant burner control)
TSA Safety time
R Resistance
Z Ignition transformer
ZU Damper fully closed
s Direction of rotation OPEN
t Direction of rotation CLOSE
Program sequence diagrams
A Burner ON
A–B Startup of burner
B–C Burner operation / load control operation (modulating or 2-stage)
C Burner OFF
C–D Overrun time
D End of program, burner control ready for a new start

13/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
Notes on «Connection diagrams»
S1) Controller for: · 2-stage operation Thermostat or similar, with changeover
contact (2-wire control).
Feuerungsautomat

7804a12/1101 In place of «BV2», a control damper can


be used that is rigidly connected to the air
damper (shown in dotted lines).
LR SA RV

BV1 BV2

· Modulating operation 3-position controller for OPEN / CLOSE


positioning pulses with neutral position (2-
Feuerungsautomat wire control).
7804a13/1101
«BV2» is not used. Gas / air ratio control is
used instead.
LR SA RV
LK This can be accomplished with
· a control damper «RV» which is rigidly
GL connected to the air damper, or
BV1 · a gas / air ratio controller «GL» type
SKP70... (refer to Data Sheet 7651)
which – if combined with safety shutoff
LR load controller for temperature or – is used in place of the «BV1»
pressure control from the Siemens (shown in dotted lines)
range: RWF40...
Digital PID universal controller for
· temperature or pressure control
· 2-stage or modulating operation, and
with special functions for heat generation plant
(refer to Data Sheet 7865)

S2) Thermostat or similar with N.O. contact (single-wire control)

S4) If, during the program sequence, a damper switch position is approached from both
sides, actuation does not take place in the same damper position due to the switching
differential. To ensure that actuation occurs in the same position, the program se-
quence makes certain the required damper position will first be passed for a short mo-
ment.

S5) The prepurge rate of the heat generation system (boiler, stack, etc.) prior to flame es-
tablishment must be in compliance with country-specific regulations. As a general rule,
the prepurge rate with oil burners should be 3 times the volume of the heat generation
system, and with gas burners, 5 times that volume. These are guide values. The effec-
tive prepurge volume required depends primarily on the construction of the heat gen-
eration system and is entirely the responsibility of the system manufacturer. If prepurg-
ing is selected for the low-fire position, the prepurge time must be appropriately ex-
tended (against prepurging for the nominal load) to ensure the required air volume will
be attained.
· For supplementary connections to the burner controls, refer to the relevant Data Sheets
· In the connection diagrams, the position of the end and auxiliary switches I...V in the actuator for the working
range are shown between 0° and the adjusted angular position of the cams, that is, in the start position

14/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002
· Dimensions

Dimensions in mm
36 24
14h10
20 24 32 17 28,5 M5 x ... (3x) 8h9
10

7808m01/0202

24
3

16
5,5 0
45°

16
7

96
-0
83

,0
10

72
Pg9 Pg11
16,5 22 14
25 110 (125)2 > 85 44 32
76

12,5 5 -0,05

14h10
10h9
2

6,5 5 +0,05

14h10
10h9
3 3)

14h10 -0,03
8 -0,09
25 10h9

Section through drive shaft ¹) Drive shaft no. ¹)

1) Drive shafts are shown in the fully closed position (voltage present at end switch
II).
Drive shaft no. is identical to the last but one digit of the type reference.
Example: SQN31.401A2760 = drive shaft no. 6
2) Height of actuator housing for fitting a potentiometer (SQN30...2A...)
3) Center slot: 6.3 mm deep
Hole dia. 5.1 mm: 16.5 mm deep (including depth of center slot)

ã2002 Siemens Building Technologies AG


Subject to change! 15/15

Siemens Building Technologies CC1N7808en


HVAC Products 30.07.2002

You might also like