Electromotoric Actuators For Air Dampers and Control Valves of Oil or Gas Burners of Small To Medium Capacity
Electromotoric Actuators For Air Dampers and Control Valves of Oil or Gas Burners of Small To Medium Capacity
Electromotoric Actuators For Air Dampers and Control Valves of Oil or Gas Burners of Small To Medium Capacity
27.04.2007
Bui l di ng Technol ogi es
HVAC Products
7
802
Actuators SQN72
Electromotoric actuators for air dampers and control valves of oil or gas
burners of small to medium capacity.
The SQN72... and this Data Sheet are intended for use by OEMs which integrate
the actuators in their products!
Use / features
The SQN7... actuators are designed for driving gas or air dampers of oil or gas burners
of small to medium capacity, for load-dependent control of the fuel and the combustion
air volume:
- In connection with P-PI or PID controllers, such as the RWF40...
- Directly via the different types of burner controls, such as LOA..., LMO..., LME..., or
LFL...
- In connection with 1- or 2-wire control or 3-position controllers
Features: - Impact-proof and heat-resistant plastic housings
- Plug terminals for the electrical connections
- Maintenance-free gear train (can be disengaged)
- Internal position indication
- Easy-to-adjust end and auxiliary switches for setting the switching points
- Integrated electronic circuits
- Degree of protection IP54
Holding torque: 0.7...1.3 Nm
Running time: 4...30 s
Direction of rotation: counterclockwise
2/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes should be observed!
Do not interfere with or modify the actuators!
All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
Before making wiring changes in the connection area of the actuator, completely
isolate the equipment from the mains supply (all-polar disconnection)
Ensure protection against electric shock hazard by providing adequate protection
for the connection terminals and by securing the housing cover
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
Fall or shock can adversely affect the safety functions. Such actuators must not be
put into operation, even if they do not exhibit any damage
Mounting notes
Ensure that the relevant national safety regulations are complied with
Standards and certificates
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Low-voltage directive
89 / 336 / EEC
73 / 23 / EEC
ISO 9001: 2000
Cert. 00739
ISO 14001: 2004
Cert. 38233
Disposal notes
The actuators contain electrical and electronic components and must not be disposed
of together with domestic waste.
Local and currently valid legislation must be observed.
3/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Mechanical design
- Made of impact-proof and heat-resistant plastic
- The housing accommodates:
The reversible synchronous motor with gear train, which can be disengaged
The camshaft of the control section
The relays, depending on the type of actuator
The switches, connected to the terminals via the printed circuit board
Color: Gear train housing dark-grey, cover light-grey
- Reversible and locking-proof synchronous motor
- Drive shaft can be manually disengaged from the
gear train and motor (by pressing pin K)
- Automatic reengagement
Pressing pin "K"
7
8
0
5
p
0
1
e
/0
2
0
7
- Via adjustable cams
- Scales beside the cams indicate the angle of the switching point
- Assignment of cams to the end and auxiliary switches is color-coded (refer to
Connection diagrams)
- Some of the cams feature fine adjustment; they can be adjusted with a standard
screwdriver
- The other cams can be adjusted manually or with the enclosed hook-spanner or
similar tool
- Internally: Scale at the beginning of the camshaft on the gear train side
- Refer to Technical data
- Maintenance-free
- Made of black-finished steel
- Ready fitted to the front of the gear train
- As different actuator versions available
- Front of the gear train is used as the mounting surface
- Actuator is secured via through-holes
Versions for fitting potentiometer
Certain types of actuators are supplied ready prepared for fitting a potentiometer.
They are prepared for housing the potentiometer. Accessories are not required.
The required type of potentiometer is to be ordered as a separate item (refer to Order-
ing).
Housing
Drive motor
Coupling
Adjustment of
switching points
Position indication
Electrical connections
Gear train
Drive shaft
Mounting and fixing
Fitting a
potentiometer
4/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Type summary (other types on request)
Types for mains voltage /
mains frequency
Diagram
No.
Drive shaft )
No.
Running time 2)
for 90
s
Nominal torque 4)
(max.)
Nm
Holding torque
Nm
AS 5)
Pcs.
Relay
Pcs.
Pot.
7)
Length of
housing )
mm
AC 230 V
3)
+10 % -15 %
50...60 Hz
Actuators SQN70 / counterclockwise rotation
6)
A 0 4 1.5 0.7 2 2 x 117 SQN72.2A4A20
A 0 30 2.5 1.3 2 2 x 117 SQN72.6A4A20
B 0 4 1.5 0.7 2 3 --- 117 SQN72.2B4A20
C 0 30 2,5 1,3 2 ---
x
117 SQN72.6C4A20
1)
Refer to Dimensions
2)
Valid for 50 Hz; at 60 Hz, running times are about 20 % shorter
3)
AC 230 V +10 % / -15 % possible, but in the case of undervoltage, torque is reduced by about 20 %
4)
Under nominal conditions; under extreme conditions (e.g. +60 C, AC 230 V 15 %) approx. 25 %
5)
Auxiliary switches (in addition to the 2 end switches)
6)
When facing the drive shaft and when control voltage is supplied to end switch I
7)
Suited for direct fitting of potentiometer (refer to Fitting a potentiometer)
Ordering
Actuator refer to Type reference
Potentiometer ASZ refer to Data Sheet N7921
refer to Mounting Instructions M7921 (4 319 9604 0)
Legend
5/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Technical data
Mains voltage AC 230 V 15 % +10 %
Mains frequency 50...60 Hz 6 %
Drive motor synchronous motor
Power consumption 6 VA
Angular adjustment max. 160, scale range 0...130
Mounting position optional
Degree of protection IP54 to DIN 40050, when using the cable
entry gland provided plus plastic washers
for the fixing screws M as shown under
Dimensions
Safety class II to VDE 0631
Cable entry Rubber grommet for single cable with a
max. jacket dia. of 11 mm.
The hole in the grommet must be ade-
quately matched to the dia. of the jacket.
To ensure that the grommet will be tight,
the cable must be correctly laid in this area
(no bends); the grommet is provided
Cable strain relief Cable strain relief with 2 fixing screws is
provided
Cable connections 2 plug-in spaces with connection terminals
type CUM, made by Stelvio for the following
types of connectors:
- CUF 5-4 (plug-in space X1)
- CUF 5-5 (plug-in space X2)
recommended cross-sectional area of
stranded wire: min. 0.5 mm , max. 1.5 mm
Ferrules adapted to cross-sectional area of <cf
complexscriptssize="9">stranded wire
Direction of rotation refer to Type summary
Nominal and holding torque refer to Type summary
Running times refer to Type summary
Weight (average) approx. 500 g
On time 60 %, max. 3 min. continuous operation
Backlash between drive motor and drive
shaft
- As supplied
- After 250,000 cycles
1.2 0.3
1.5 0.3
Actuator
6/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Technical data (contd)
Number of end switches 2
Number of auxiliary switches refer to Type summary
Actuation via camshaft, color-coded cams (refer to
Connection diagrams)
switches with fine adjustment: II and III
Breaking voltage AC 24...250 V
Adjustment of cams
- Without fine adjustment
- With fine adjustment
1
infinitely
Max. perm. amperage at cos =0.9
(values in parentheses: short-time peaks for max. 0.5 s)
Diagram A
Terminals 1, 2, 3, 8
Terminal 4, 5
Terminal 6, 7
0.5 A
2 A (14 A)
1 A (7 A)
Diagram B
Terminals 1, 3, 8
Terminal 4, 5
Terminal 6, 7
0.5 A
3 A (14 A)
1 A (7 A)
Diagram C
Terminals 1, 2, 3, 4, 5
Terminal 6, 7, 8
0.5 A
1 A (7 A)
Storage DIN EN 60 721-3-1
Climatic conditions class 1K3
Mechanical conditions class 1M2
Temperature range -20...+60 C
Humidity <95 % r.h.
Transport DIN EN 60 721-3-2
Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -50...+60 C
Humidity <95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions class 3K5
Mechanical conditions class 3M2
Temperature range -20...+60 C
Humidity <95 % r.h.
Condensation, formation of ice and ingress of water are not permitted!
Function
A synchronous motor drives a driveshaft with attached camshaft via a gear train.
The camshaft actuates the end and the auxiliary switches. Using the associated cam,
the switching position of each end and auxiliary switch can be adjusted within the work-
ing range. Some of the actuator versions are equipped with electronic modules, which
perform auxiliary functions in connection with the end and auxiliary switches and exter-
nal devices, such as controllers (refer to Connection diagrams).
End and auxiliary
switches
Environmental
conditions
7/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Connection diagrams (examples)
All following connection diagrams show the start position as supplied:
- End switch position II Closed
- Dead
No. A LME22...
2-stage or modulating operation prepurging at nominal load position NL
LK
7805a02/0407
N
I
HS
L
R
GP
12
EK2
3 8
Z
LR
ION
BV1
4 1
0
1 2
10 9 5 7
BV2
6
LP
M
2
LME22...
AL
11
SB
*)
Si
SQN72.xA4xxx
M
6 7 4 2 8 5 1 3 N
X1
A
A
b1
a1 b2
X2
N
a2
B
~
*)
X1
X2
I
II
III
IV
Thermostat or similar unit with
changeover contact
(2-wire control), or 3-position con-
troller for on / off positioning
pulses and neutral position
Plug-in space, 4-pole
Plug-in space, 5-pole
Red
Blue
Orange
Black
A B D
LK
M
I
IV
III
II
7
8
0
5
d
0
3
/
0
2
0
7
GP/SB
R/W
M
LP
BV2
BV1
LR
FS
9
tw t1
C
LKP
NL
KL
Zu
II
I
III IV
I
IV
III
t
SA
2 1
1
2
Sequence diagram shows 2-stage
operation
8/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Connection diagrams (examples)
No. B LOA24... / LOA25... / LOA26... / LOA28... / LOA36... / LMO24... / LMO44...
2-stage operation prepurging at low fire position KL
HS
N
I
L
LOA24... / LOA25... / LOA26... / LOA28... / LOA36...
LMO24... / LMO44...
AL
OH
Z
LR
BV1
3 6 4 5 11 12
QRB..
OW
3)
1)
GP
R
BV2
2 10 8 1
M
0
SB
Si
*)
LK
6 7 2 3 5 1 4 8 N
N
a1
C
a2
M
b1
A B
B
b2
X1
c1
X2
7805a05/0407
SQN72.xB4xxx
~
QRC
1
br
bl sw
1)
2)
*)
X1
X2
I
II
III
IV
Without oil preheater
With oil preheater:
If OW contact opens during
operation, a new start will be
made
Thermostat or similar unit with n.o.
contact (1-wire control)
Plug-in space, 4-pole
Plug-in space, 5-pole
Red
Blue
Orange
Black
SB
GP
R/W
OH
OW
M
LR
BV1
BV2
FS
M
I
IV
III
II
LK
A C
tw t1
t4
B D
7
8
0
5
d
0
1
/
0
2
0
7
LKP
NL
KL
I
III
IV
I
IV
III
t
Zu
II
4)
4) 4)
SA
4)
Required position is approached
from only one side to eliminate
switching differential (compensa-
tion of backlash)
9/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Connection diagrams (examples)
No. C LFL... / LGK16... / LAL... / LOK16...
2-stage or modulating operation prepurging at nominal load position NL
I
HS
L N
LFL... / LGK16... / LAL... / LOK16...
0
1 20 10 18
BV2
BV1
19 8 2 9 11
**)
SB
Si
LR *)
LK
7805a06/0407
SQN72.xC4xxx
X1
C
M
X2
N 6 4 7 8 2 5 1 3
N
~
*)
**)
X1
X2
I
II
III
IV
Thermostat or similar unit with
changeover contact or 3-position
controller for on / off positioning
pulses and neutral position
In the case of modulating opera-
tion, fuel valve BV2 is replaced
by a gas control valve RV
Plug-in space, 4-pole
Plug-in space, 5-pole
Red
Blue
Orange
Black
R
M1
M2
Z
BV1
RV**
FS
I
IV
III
II
A
7
8
0
5
d
0
2
/
0
2
0
7
C
t1
B D
LKP
NL
KL
Zu
II
I
III
I
III
t
LK
M
RV
**
**
SA
LR *)
Program sequence diagram
shows modulating operation
10/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Legend
No. A Number of internal diagram (second position after the dot in the type reference)
I / II End switches
III / IV / V Auxiliary switches
AL Remote indication of lockout (alarm)
BV1 Fuel valve stage 1
BV2 Fuel valve stage 2
BV3 Fuel valve stage 3
EK2 External remote reset button
ION Ionization probe
FS Flame signal
GP Gas pressure switch
HS Main switch
KL Low-fire
L Live conductor
LK Air damper
LKP Air damper position
LP Air pressure switch
LR Load controller
M Burner or fan motor
M
Actuators synchronous motor
M1 Without postpurge
M2 With postpurge
N Neutral conductor
NL Nominal load
OH Oil preheater
OW Oil preheaters release contact
QRB... Photoresistive flame detector
R Temperature or pressure controller
Relay
RV Control valve
SA Actuator
Si External primary fuse (as specified in the Data Sheet of the relevant burner control)
SB Safety limiter
ST... Stage
t... / T... Program times (refer to the Data Sheet of the relevant burner control)
TSA Safety time
R
Resistance
Z Ignition transformer
CLOSED Damper fully closed
Direction of rotation OPEN
Direction of rotation CLOSE
Program sequence - diagrams
A Burner ON
A B Startup of burner
B C Burner operation / load control operation (modulating or 2-stage)
C Burner OFF
C D Overrun time
D End of program, burner control ready for new start
Control signals delivered by burner control
Required input signals
Permissible input signals
11/11
Building Technologies CC1N7802en
HVAC Products 27.04.2007
Dimensions
Dimensions in mm
7
8
0
5
m
0
1
e
/
0
2
0
7
0
26
24 24
M
M
T
M
24
35.9
71,8
7
1
.
5
1
6
1
6
5,3
1
1
12
>=105
17
25
7
0
0
.0
5
4
5
8h9
117
9
8
,
3
Grommet
Drive shaft versions
Side view
Drife shaft versions
Cross-section
Drife shaft no.
(refer to "Type summary"
8h9
1
0
All drive shafts shown in end switch position II Closed as supplied.
M Through-hole 5.3 mm dia.
T Knockout hole 5.3 mm dia.
2007 Siemens Building Technologies HVAC Products GmbH
Subject to change!