Product Data Sheet: DEHNshield

DSH TT 2P 255 FM (941 115)


■ Application-optimised and prewired spark-gap-based type 1 and type 2 combined lightning current and surge arrester
■ Compact design due to space-saving spark gap technology with a width of only 1 module / pole
■ Allows compact lightning equipotential bonding including protection of terminal equipment

Figure without obligation

Basic circuit diagram DSH TT 2P 255 FM Dimension drawing DSH TT 2P 255 FM


Application-optimised and prewired combined lightning current and surge arrester for single-phase TT and TN-S systems (1+1 configuration); with
floating remote signalling contact.

Type DSH TT 2P 255 FM  


Part No. 941 115  
SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II   
Energy coordination with terminal equipment (≤ 10 m) type 1 + type 2 + type 3   
Nominal voltage (a.c.) (UN) 230 V (50 / 60 Hz)   
Max. continuous operating voltage (a.c.) (UC) 255 V (50 / 60 Hz)   
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal) 25 kA  
Specific energy [L+N-PE] (W/R) 156.25 kJ/ohms  
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp) 12.5 / 25 kA  
Specific energy [L-N]/[N-PE] (W/R) 39.06 / 156.25 kJ/ohms  
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In) 12.5 / 25 kA  
Voltage protection level [L-N]/[N-PE] (UP) ≤ 1.5 / ≤ 1.5 kV  
Follow current extinguishing capability [L-N]/[N-PE] (Ifi) 25 kArms / 100 Arms   
Follow current limitation / Selectivity no tripping of a 32 A gG fuse up to 25 kArms (prosp.)   
Response time (tA) ≤ 100 ns  
Max. mains-side overcurrent protection 160 A gG  
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic 440 V / 120 min. – withstand   
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic 1200 V / 200 ms – withstand   
Operating temperature range (TU) -40 °C ... +80 °C   
Operating state / fault indication green / red   
Number of ports 1   
2
Cross-sectional area (L, N, PE, 9) (min.) 1.5 mm solid / flexible   
2 2
Cross-sectional area (L, N, PE, 9) (max.) 35 mm stranded / 25 mm flexible   
For mounting on 35 mm DIN rails acc. to EN 60715   
Enclosure material thermoplastic, red, UL 94 V-0   
Place of installation indoor installation   
Degree of protection IP 20   
Capacity 2 module(s), DIN 43880  
Approvals KEMA, VDE   
Type of remote signalling contact changeover contact   
Switching capacity (a.c.) 250 V / 0.5 A   
Switching capacity (d.c.) 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A   
2
Cross-sectional area for remote signalling terminals max. 1.5 mm solid / flexible   
Extended technical data: ---------------------------------   
Voltage protection level [L-PE] (UP) 2.0 kV  
Weight 285 g  
Customs tariff number (Comb. Nomenclature EU) 85363090  
GTIN 4013364289208  
PU 1 pc(s)  

We reserve the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.