3RP25741NW30 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Data sheet 3RP2574-1NW30

Timing relay, electronic with star-delta (wye-delta) function 1 NO


delayed 1 NO instantaneous 1 time range, 1...20 s 12-240 V AC/DC
at 50/60 Hz AC screw terminal

product brand name SIRIUS


product designation timing relay
design of the product Star-delta (wye-delta) function
product type designation 3RP25

General technical data


● product component relay output Yes
● product component semi-conductor output No
product extension required remote control No
product extension optional remote control No

— insulation voltage for overvoltage category 300 V
III according to IEC 60664 with degree of
pollution 3 rated value
Test voltage for isolation test 2.5 kV
degree of pollution 3
surge voltage resistance rated value 4 000 V
● protection class IP IP20
● shock resistance acc. to IEC 60068-2-27 11g / 15 ms
● vibration resistance acc. to IEC 60068-2-6 10 ... 55 Hz / 0.35 mm

3RP2574-1NW30 Subject to change without notice


Page 1/8 09/29/2020 © Copyright Siemens
● mechanical service life (switching cycles) 10 000 000
typical
● Electrical endurance (switching cycles) at AC- 100 000
15 at 230 V typical
adjustable time 1 ... 20 s
Relative setting accuracy relating to full-scale value 5 %
thermal current 5 A
● recovery time 250 ms
reference code acc. to DIN EN 81346-2 K
relative repeat accuracy 1 %

Control circuit/ Control


Type of voltage of the control supply voltage AC/DC
Control supply voltage 1 at AC
● at 50 Hz 12 ... 240 V
● at 60 Hz 12 ... 240 V
control supply voltage frequency 1 50 ... 60 Hz
Control supply voltage 1
● at DC 12 ... 240 V
operating range factor control supply voltage rated
value at DC
● initial value 0.8
● full-scale value 1.1
operating range factor control supply voltage rated
value at AC at 50 Hz
● initial value 0.8
● full-scale value 1.1
operating range factor control supply voltage rated
value at AC at 60 Hz
● initial value 0.8
● full-scale value 1.1
Inrush current peak
● at 24 V 0.5 A
● at 240 V 5 A
Duration of inrush current peak
● at 24 V 0.4 ms
● at 240 V 0.5 ms

Switching Function
switching function
● ON-delay No
● ON-delay/instantaneous contact No
● passing make contact No
● passing make contact/instantaneous contact No

3RP2574-1NW30 Subject to change without notice


Page 2/8 09/29/2020 © Copyright Siemens
● OFF delay No
Switching function
● flashing symmetrically starting with No
interval/instantaneous
● flashing symmetrically starting with interval No
● flashing symmetrically starting with No
pulse/instantaneous
● flashing symmetrically starting with pulse No
● flashing asymmetrically starting with interval No
● flashing asymmetrically starting with pulse No
Switching function
● star-delta circuit with delay time No
● star-delta circuit Yes
● Switching function with control signal additive No
ON delay
● switching function with control signal passing No
break contact
● Switching function with control signal passing No
break contact/instantaneous
● Switching function with control signal OFF No
delay
● Switching function with control signal OFF No
delay/instantaneous
● Switching function with control signal pulse No
delayed
● Switching function with control signal pulse No
delayed/instantaneous
● switching function with control signal pulse- No
shaping
● Switching function with control signal pulse- No
shaping/instantaneous
● Switching function with control signal additive No
ON delay/instantaneous
● Switching function with control signal ON- No
delay/OFF-delay/instantaneous
● Switching function with control signal passing No
make contact
● Switching function with control signal passing No
make contact/instantaneous contact
Switching function of interval relay with control signal
● retrotriggerable with deactivated control No
signal/instantaneous contact
● retrotriggerable with activated control signal No

3RP2574-1NW30 Subject to change without notice


Page 3/8 09/29/2020 © Copyright Siemens
● retrotriggerable with activated control No
signal/instantaneous contact
● retriggerable with deactivated control signal No

Short-circuit protection
● design of the fuse link for short-circuit fuse gL/gG: 4 A
protection of the auxiliary switch required

Auxiliary circuit
Material of switching contacts AgSnO2
● number of NC contacts delayed switching 0
● number of NO contacts delayed switching 1
● number of CO contacts delayed switching 0
operating current of auxiliary contacts at AC-15
● at 24 V 3 A
● at 250 V 3 A
operating current of auxiliary contacts at DC-13
● at 24 V 1 A
● at 125 V 0.2 A
● at 250 V 0.1 A
operating frequency with 3RT2 contactor maximum 5 000 1/h
contact reliability of auxiliary contacts one incorrect switching operation of 100 million switching
operations (17 V, 5 mA)
contact rating of auxiliary contacts according to UL R300 / B300
influence of the surrounding temperature 1% in the whole temperature range to the set runtime
Power supply influence 1% in the whole voltage range to the set runtime
Switching capacity current with inductive load 0.01 ... 3 A

Inputs/ Outputs
● product function at the relay outputs switchover No
delayed/without delay
● Product function non-volatile No

Electromagnetic compatibility
EMI immunity
● acc. to IEC 61812-1 EN 61000-6-2
● conducted interference due to burst acc. to IEC 2 kV network connection / 1 kV control connection
61000-4-4
● Conducted interference due to conductor-earth 2 kV
surge acc. to IEC 61000-4-5
● Conducted interference due to conductor- 1 kV
conductor surge acc. to IEC 61000-4-5
field-bound parasitic coupling acc. to IEC 61000-4-3 10 V/m
electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge

Safety related data

3RP2574-1NW30 Subject to change without notice


Page 4/8 09/29/2020 © Copyright Siemens
protection against electrical shock finger-safe
Type of insulation Basic insulation
category acc. to EN 954-1 none

Connections/ Terminals
● product function removable terminal for Yes
auxiliary and control circuit
● type of electrical connection for auxiliary and screw-type terminals
control current circuit
● type of connectable conductor cross-sections 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
solid
● Type of connectable conductor cross-sections 1x (0.5 ... 4 mm²), 2x (0.5 ... 1.5 mm²)
finely stranded with core end processing
● Type of connectable conductor cross-sections 1x (20 ... 12), 2x (20 ... 14)
at AWG conductors solid
● type of connectable conductor cross-sections at 1x (20 ... 12), 2x (20 ... 14)
AWG conductors stranded
● connectable conductor cross-section solid 0.5 ... 4 mm²
● connectable conductor cross-section finely 0.5 ... 4 mm²
stranded with core end processing
AWG number as coded connectable conductor cross
section
● solid 20 ... 12
● stranded 20 ... 14
tightening torque 0.6 ... 0.8 N·m
design of the thread of the connection screw M3

Installation/ mounting/ dimensions


● mounting position any
● mounting type screw and snap-on mounting onto 35 mm standard mounting rail
height 100 mm
width 22.5 mm
depth 90 mm
required spacing
● with side-by-side mounting
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm

3RP2574-1NW30 Subject to change without notice


Page 5/8 09/29/2020 © Copyright Siemens
— at the side 0 mm
— downwards 0 mm
● for live parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm

Ambient conditions
● installation altitude at height above sea level 2 000 m
maximum
● ambient temperature during operation -25 ... +60 °C
● ambient temperature during storage -40 ... +85 °C
● ambient temperature during transport -40 ... +85 °C
relative humidity
● during operation 10 ... 95 %

Certificates/ approvals
General Product Approval EMC Declaration of
Conformity

Declaration of Test Certific- Marine / Shipping


Conformity ates
Miscellaneous Type Test Certific-
ates/Test Report

Marine / Shipping other


Confirmation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RP2574-1NW30

3RP2574-1NW30 Subject to change without notice


Page 6/8 09/29/2020 © Copyright Siemens
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RP2574-1NW30
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RP2574-1NW30
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RP2574-1NW30&lang=en
Characteristic: Derating
https://support.industry.siemens.com/cs/ww/en/ps/3RP2574-1NW30/manual

91.6

22.5 86.5

S IRIU S
3 RP2 5 7 4 - 1 NW3 0

A2 A2
1 2 ...2 4 0 V 1 2 ...2 4 0 V
AC/ DC AC/ DC

A1 A1
50

3 RP2 5 7 4 - 1 NW3 0
100

1 8 NO 2 8 NO
17C

3 RP2 5 7 4 - 1 NW3 0

3RP2574-1NW30 Subject to change without notice


Page 7/8 09/29/2020 © Copyright Siemens
17 C
A1

A1
-K

18 NO

28 NO
A2

A2

last modified: 09/23/2020

3RP2574-1NW30 Subject to change without notice


Page 8/8 09/29/2020 © Copyright Siemens