Industrial Controls Monitoring and Control Devices SIRIUS 3UG4 / 3RR2 Monitoring Relay
Industrial Controls Monitoring and Control Devices SIRIUS 3UG4 / 3RR2 Monitoring Relay
Industrial Controls Monitoring and Control Devices SIRIUS 3UG4 / 3RR2 Monitoring Relay
Safety information 2
System overview 3
Industrial Controls
3RR2 current monitoring
relays 4
Monitoring and control devices
SIRIUS 3UG4 / 3RR2 monitoring 3UG4501 filling level
monitoring relay 5
relay
3UG4.1 line monitoring
Equipment Manual
relay 6
3UG4621/3UG4622 current
monitoring relays 7
3UG4625 residual current
monitoring relay with 8
3UL23 transformer
3UG458. insulation
monitoring relay. 9
3UG463. voltage
monitoring relay 10
3UG4641 cos phi and active
current monitoring relay 11
3UG4651 speed monitoring
relay 12
Accessories 13
References A
Parameters B
Dimension Drawings C
07/2022
NEB927043002000/RS-AE/006
Menu-based operation D
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring only to property damage have no safety alert symbol. These notices shown below are graded according to
the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance
are required to ensure that the products operate safely and without any problems. The permissible ambient
conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may
be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.
1 Introduction ........................................................................................................................................... 9
1.1 Siemens Industry Online Support ......................................................................................... 9
1.2 DataMatrix code ................................................................................................................ 11
1.3 Siemens Industry Online Support app................................................................................. 12
1.4 Support Request ................................................................................................................ 12
2 Safety information............................................................................................................................... 13
2.1 Standards .......................................................................................................................... 13
2.2 Requirements for switching high-efficiency motors ............................................................. 14
2.3 Voltages ............................................................................................................................ 14
2.4 Notes on the protection of device connections ................................................................... 14
2.5 Product-specific safety information..................................................................................... 15
2.5.1 Current information about operational safety ..................................................................... 15
2.6 Recycling and disposal ....................................................................................................... 16
2.7 Security information .......................................................................................................... 16
2.8 Approvals, test certificates, characteristics .......................................................................... 16
3 System overview.................................................................................................................................. 17
3.1 Product description ............................................................................................................ 17
3.2 Application planning.......................................................................................................... 18
3.3 Connection methods.......................................................................................................... 18
3.3.1 Screw-type connection....................................................................................................... 18
3.3.2 Spring-loaded connection .................................................................................................. 21
3.3.3 Device replacement by means of removable terminals ........................................................ 26
3.4 Mounting / removal ........................................................................................................... 27
3.4.1 Mounting 3RR2 current monitoring relay ............................................................................ 27
3.4.2 Mounting the 3UG4 monitoring relay ................................................................................. 32
3.4.3 Installing the 3UG458. monitoring relay. ............................................................................ 33
3.5 Overview of the functions .................................................................................................. 35
3.5.1 3RR2 current monitoring relays .......................................................................................... 35
3.5.2 3UG45 / 3UG46 monitoring relays ...................................................................................... 36
3.6 Menu-based operation....................................................................................................... 37
4 3RR2 current monitoring relays ........................................................................................................... 43
4.1 Product description ............................................................................................................ 43
4.2 Application areas ............................................................................................................... 44
4.3 Performance features of current monitoring relays ............................................................. 46
Product support
You can find information and comprehensive know-how covering all aspects of your product
here:
• FAQs
Answers to frequently asked questions
• Manuals/operating instructions
Read online or download, available as PDF or individually configurable.
• Certificates
Clearly sorted according to approving authority, type and country.
• Characteristics
For support in planning and configuring your system.
• Product announcements
The latest information and news concerning our products.
• Downloads
Here you will find updates, service packs, HSPs and much more for your product.
• Application examples
Function blocks, background and system descriptions, performance statements,
demonstration systems, and application examples, clearly explained and represented.
• Technical data
Technical product data for support in planning and implementing your project
Link: Product support (https://support.industry.siemens.com/cs/ww/en/ps)
mySupport
The following functions are available in your personal work area "mySupport":
• Support Request
Search for request number, product or subject
• My filters
With filters, you limit the content of the online support to different focal points.
• My favorites
With favorites you bookmark articles and products that you need frequently.
• My notifications
Your personal mailbox for exchanging information and managing your contacts. You can
compile your own individual newsletter in the "Notifications" section.
• My products
With product lists you can virtually map your control cabinet, your system or your entire
automation project.
• My documentation
Configure your individual documentation from different manuals.
• CAx data
Easy access to CAx data, e.g. 3D models, 2D dimension drawings, EPLAN macros, device
circuit diagrams
• My IBase registrations
Register your Siemens products, systems and software.
Further documentation
To install and connect the monitoring relays, you require the operating instructions of the
monitoring relays used.
The Appendix "References (Page 263)" has a list of the operating instructions.
DataMatrix code
A DataMatrix code is lasered onto all 3UG4/3RR2 monitoring relay devices underneath the label.
The DataMatrix codes are standardized in ISO/IEC 16022. The DataMatrix codes on Siemens
devices use ECC200 coding for powerful error correction.
The following device information is encoded in the DataMatrix codes as a bit stream:
• Article number
• Serial number
• Where applicable, MAC address
This information is stored in the following format in the DataMatrix code:
Note
The information content is displayed without spaces.
This machine-readable information simplifies and accelerates handling of the respective devices.
As well as fast access to the serial numbers of the respective devices for unique identification, the
DataMatrix codes simplify communication with Siemens Technical Support.
Android iOS
Applicable standards
The monitoring relays comply with the following standards:
Device standards • IEC / EN 60947‑1 "Low-voltage switchgear and controlgear: General rules"
• IEC / EN 60947‑4‑1 "Contactors and motor-starters: Electromechanical con‐
tactors and motor-starters"
• IEC / EN 60947‑5‑1 "Control circuit devices and switching elements: Electro‐
mechanical control circuit devices";
VDE 0660 "Low-voltage switchgear"
• IEC / EN 61557‑8 "Equipment for testing, measuring or monitoring of protec‐
tive measures - Electrical safety in low voltage distribution systems up to
1000 V AC and 1500 V DC, Part 8: Insulation monitoring devices for IT sys‐
tems".
• DIN EN 50042 "Terminal marking"
• DIN EN 61869-2 "Instrument transformers - Part 2: Additional requirements
for current transformers"
EMC standard1) • IEC / EN 61000‑6‑2 "Generic standards - Immunity for industrial environments"
• IEC / EN 61000‑6‑4 "Generic standards - Emission standard for industrial en‐
vironments"
Resistance to ex‐ • IEC 60721‑3‑3 "Classification of environmental conditions"
treme climates The monitoring relays are climate-proof according to IEC 60721‑3.
Touch protection • IEC / EN 60529 "Degrees of protection provided by enclosures"
Monitoring relays are safe to touch in accordance with IEC / EN 60529.
1)
This is a device of Class A. When used in domestic areas, the device can cause radio interference. Users
may have to take suitable measures.
Reference
SIRIUS components have been approved by a whole range of bodies for various sectors
(shipbuilding, etc.). An up-to-date list of approvals appears in Chapter 10 of the Catalog IC 10 -
SIRIUS "Industrial Controls" (https://support.industry.siemens.com/cs/de/de/view/109747945/
en), and more information, as well as an option to download certificates, can be obtained on the
Internet (https://support.industry.siemens.com/cs/ww/en/ps/16364/cert).
2.3 Voltages
The specifications for 3-phase line supply according to IEC 60947‑4‑1 are valid for the following
line system configurations:
-- not specified
Hazardous Voltage
WARNING
Hazardous Voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
Radio interference
Note
The devices have been built as Class A devices.
Use of these devices in domestic areas can result in radio interference!
Product description
The tried and tested SIRIUS monitoring relays for electrical and mechanical quantities enable
constant monitoring of all important characteristic quantities that provide information about
the reliability performance of the plant. Sudden disturbances and gradual changes, which may
reveal a maintenance requirement, for example, are both indicated. By means of relay outputs,
the monitoring relays enable direct shutdown of the affected sections of the plant as well as
issuing an alarm (e.g. by switching on a warning lamp). To respond flexibly to short-term
disturbances such as voltage dips or load variation, the monitoring relays have settable delay
times. This avoids unnecessary alarming and shutdowns while enhancing plant availability.
The individual 3UG4 monitoring relays offer the following functions in various combinations:
• Undershoot and/or overshoot of liquid levels
• Phase sequence
• Phase failure, neutral failure
• Phase asymmetry
• Undershoot and/or overshoot of voltage thresholds
• Undershoot and/or overshoot of current thresholds
• Undershoot and/or overshoot of power factor thresholds
• Monitoring of the active current or apparent current
• Monitoring of the fault current
• Monitoring the insulation resistance
• Undershoot and/or overshoot of speed thresholds
The 3RT2 contactors for mounting on 3RR2 current monitoring relays offer:
• Phase sequence
• Phase failure
• Undershoot and/or overshoot of current thresholds
• Monitoring of the active current or apparent current
• Monitoring of the fault current
Installation altitude
The monitoring relays are approved for installation altitudes up to 2,000 m. The reduced air
density at altitudes higher than 2,000 meters affects the electrical characteristics of the
monitoring relays. The reduction factors which have to be taken into account when using
monitoring relays at altitudes higher than 2,000 m can be obtained on request on the Internet
(https://support.industry.siemens.com/My/ww/en/requests).
Screw-type connection
Use the following tool to establish the connection: All SIRIUS monitoring relays feature size PZ 2
screws for Pozidriv screwdrivers.
The devices have screw terminals with captive screws and washers. The screw terminals also
allow for the connection of 2 conductors with different cross-sections.
Table 3-1 Removable terminal block with screw-type connections - monitoring relays
Removable terminal
Tool Pozidriv size PZ 2, Ø 5 to 6 mm
Table 3-2 Removable terminal block with screw-type connection technology- insulation monitoring relay 3UG458.-1AW31 /
3UG4583-1CW31 / voltage reducer module 3UG4983-1AA01
Removable terminal
Tool Pozidriv size PZ 1, diam. 4.5 mm
Table 3-3 Permanently connected terminal block with screw-type connection - Main conductor terminals of the 3RR2 current
monitoring relays
Spring-loaded connection
All SIRIUS monitoring relays have spring-loaded connections. They make wiring quick and
maintenance-free, while also meeting high demands in terms of vibration and shock resistance.
If the cross-section of a connectable wire is greater than 6 mm², the forces required for operation
of the tension spring are so high that the spring-loaded connection can no longer be used in a
problem-free manner. For this reason, size S2 current monitoring relays are only offered with
screw-type or spring-loaded terminals in the control circuit. The terminals of the main current
paths are always screw-type terminals.
D
① Solid
② Finely stranded
③ Stranded
④ Finely stranded with end sleeve
a Spring-loaded terminal
b Busbar
Figure 3-1 Spring-loaded terminal
The conductors can be clamped directly or you can pre-treat them to add a form of splice
protection. This could involve attaching end sleeves or pin cable lugs to the ends of the
conductors; the tidiest solution is to use conductors whose ends have been sealed by means of
ultrasound.
The devices are equipped with a two-wire terminal, i.e. two independent connections for each
current path (exception: in the case of 3RR2, terminals of the main current paths have one
clamping point). Just one conductor is connected to each clamping point. The spring-loaded
terminal presses the conductor against the busbar, which curves around inside the terminal. The
high contact pressure per unit area achieved in this way is gas-tight. The spring-loaded terminal
presses flat against the conductor, but does not damage it. The spring force of the spring-loaded
terminal has been dimensioned such that the clamping force adjusts to the conductor diameter
automatically. This ensures that any conductor deformation caused by settling, creepage, or
yielding is compensated for. The clamping point cannot become loose of its own accord. This
connection is vibration- and shock-proof. Vibrations or shocks will not damage the conductor,
nor will they cause contact separation. These terminals are particularly well suited for use with
machines and systems which are subject to stresses such as these, e.g. vibrators, rail vehicles,
and elevators.
The contact pressure between the conductor and the busbar is set to an optimum level, so this
clamp connection is appropriate for high-voltage applications, as well as for transferring
voltages and currents in the mV or mA range within instrumentation and electronic
components.
A standardized screwdriver (3 mm slot; 3RA2908-1A) is offered in the Catalog IC10 "Industrial
Controls" (https://support.industry.siemens.com/cs/de/de/view/109747945/en) as an
actuation tool for opening the spring-loaded terminals.
DANGER
Hazardous Voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
~10°
~10°
② Press the screwdriver down, then push it into the operating slot as far as it will go.
The screwdriver blade keeps the spring-loaded terminal open automatically.
③ Insert the conductor into the oval connection slot.
④ Remove the screwdriver. The terminal closes and the conductor is now securely clamped.
Note
Damage to spring-loaded terminal on the 3RR2 current monitoring relay!
If you insert the screwdriver into the central opening (main circuit S00 and S0 only) on the
spring-loaded terminal, this could damage the terminal.
Do not insert the screwdriver into the central opening on the spring-loaded terminal.
ar
$
%
ar
① Insert the screwdriver into the topmost (A) or bottommost (B) operating slot on the right-hand
side.
② Press the screwdriver up (A) or down (B), then push it into the operating slot as far as it will go.
The screwdriver blade keeps the spring-loaded terminal open automatically.
Connecting the spring-loaded terminal (solid and stranded/finely stranded with end
sleeve)
Connection cross-sections of the removable terminal blocks with a spring-loaded connection (3RR
and 3UG)
Table 3-4 Removable terminal block with spring-loaded connections - monitoring relays
Removable terminal
Tool Ø 3.0 x 0.5 (3RA2908-1A)
Removable terminal
Finely stranded without end 2 x (0.25 to 1.5) mm²
sleeve
Table 3-5 Removable terminal block with spring-loaded connection technology - insulation monitoring
relay 3UG458.-2AW31 / 3UG4583-2CW31 / voltage reducer module 3UG4983-2AA01
Removable terminal
Tool Ø 3.0 x 0.5 (3RA2908-1A)
Table 3-6 Permanently connected terminal block with spring-loaded connection - main conductor terminals of 3RR2 current
monitoring relays
DANGER
Hazardous Voltage
Will cause death or serious injury.
Turn off and lock out power before working on this equipment.
The removable terminals of 3UG4 monitoring relays facilitate device replacement when
necessary. The mechanical coding on the terminals prevents mix-ups.
Note
The terminals can only be dismantled in the following order due to their arrangement on the
monitoring relay:
1. Lower, front terminal (A)
2. Lower, rear terminal (B)
3. Upper, front terminal (C)
4. Upper, rear terminal (D)
'
%
&
$
Note
The procedure is similar on devices with fewer connection terminals.
Mounting options
3RR2 current monitoring relays are matched to 3RT2 contactors and 3RF34 (size S0) solid-state
contactors in terms of their electrical and mechanical features. As a result, direct mounting can
be achieved easily.
Alternatively, the devices can also be installed individually in the case of stand-alone assembly
or if a 3RU2 / 3RB3 overload relay is being used at the same time. The accessories required for
separate mounting are described in Chapter "Terminal support for stand-alone assembly
(Page 228)."
Minimum clearance
The following minimum clearances from grounded and live parts must be complied with when
installing the 3RR2 monitoring relay:
• At the side: 6 mm
• Forward (on front): 6 mm
Mounting position
It can be mounted in any position.
Mounting of 3RR2 current monitoring relay, screw-type connection system (size S0)
① Push the current monitoring relay into the contactor from below. Attach the two hooks on the
current monitoring relay to the two openings on the rear of the contactor. This pushes the main
current contacts into the corresponding terminals on the contactor.
② Tighten the screws on the contactor with a Pozidriv size 2 (S00) or Pozidriv size 3 (S0) screwdriver
(tightening torque 0.8 ... 1.2 Nm).
Check that the cable is clamped tight.
Note
The connection cross-sections of the removable and permanently connected terminal blocks
with screw-type connections are described in the Chapter "Screw-type connection (Page 18)".
Mounting of 3RR2 current monitoring relay, spring-loaded connection technology (size S0)
① Insert the contacts (a) into the central opening of the spring-loaded terminals on the contactor
(see below, a), with the contacts flush to the right. Make sure that the guide tabs (zoom view) are
inserted into the designated slots on the contactor.
The current monitoring relay will sit correctly flush with the contactor on the left- and right-hand
sides.
The figures below show the openings of the main conductor terminals on the contactor (S00 and
S0) into which the contacts on the current monitoring relay have to be inserted.
Main conductor terminal on the contactor (a) Main conductor terminal on the contactor (a)
(S00): (S0):
Note
Adapter for direct mounting on 3RF34 solid-state contactor
For direct mounting on a 3RF34 solid-state contactor, an additional 3RF3900-0QA88 adapter is
required, which is attached to the solid-state contactor. Information is provided in the "SIRIUS
solid state contactors / solid state reversing contactors" (http://
support.automation.siemens.com/WW/view/en/44362244) operating instructions.
Disassembly
To disassemble the S00/S0/S2 assemblies from the DIN rail, press the contactor down and pull
it toward you.
Removing the 3RR2 current monitoring relay, screw-type connection system (size S0)
Removing the 3RR2 current monitoring relay, spring-loaded connection technology (size
S00)
① Position the screwdriver on the current monitoring relay as shown in the figure. Carefully dislodge
the current monitoring relay from the contactor.
② Pull the current monitoring relay toward you and away from the contactor.
Separately mounted
Note
The accessories required for separate mounting are described in the Chapter "Terminal support
for stand-alone assembly (Page 228)".
Mounting position
It can be mounted in any position.
Screw mounting
The illustration below shows how to screw-mount the 3UG4 monitoring relay.
53
① Slide the push-in lugs into the openings on the monitoring relay at the top and bottom, and use
the screwdriver to secure the device by screwing suitable screws through the holes in the push-in
lugs.
Mounting the monitoring relay (mounting on and removing from standard rail)
① Position the device on the top edge of the DIN rail and press it down until it snaps onto the bottom
edge of the DIN rail.
To remove the device, press it down, pushing against the mounting springs, and swivel the device
to remove it.
Installing the 3UG458. insulation monitoring relay (mounting onto standard rail)
①/ Position the device on the top edge of the DIN rail and press down until it snaps onto the bottom
② edge of the DIN rail.
Removing the 3UG458. insulation monitoring relay. (Removing from standard rail)
①/ To remove, apply the screwdriver to the device and push it up with a twisting motion against the
② tension of the fixing spring.
③ Swing the device upwards to remove it.
FOLF
① Position the device on the top edge of the DIN rail and press it down until it snaps onto the bottom
② edge of the DIN rail.
① For disassembly, press the device down and remove the device with a swiveling motion to the
② front.
③
Table 3-7 Functions of the 3RR21 / 3RR22 current monitoring relays for analog and digital setting
✓: Function available
2p: Monitoring is 2-phase
3p: Monitoring is 3-phase
— : Function not available
Table 3-8 Functions of the 3UG45/3UG46 monitoring relays for analog and digital setting
✓: Function available
1p: Monitoring is 1-phase
3p: Monitoring is 3-phase
True root mean square measurement (tRMS) / use with frequency converters:
The monitoring relays work with an electronic measuring method which calculates the actual
(effective) value of a measured value (tRMS), regardless of whether the measured variable's
waveform is purely sinusoidal or distorted.
The measured signal must only meet the following requirements:
• Periodic waveform (sinusoidal) within the specified frequency range
• Continuous zero crossings
As long as the line on the primary or the secondary side in the environment of a frequency
converter fulfills these requirements, the monitoring relays can also be operated upstream or
downstream of frequency converters. The required line quality can be ensured by using line
filters/sine-wave filters where applicable. Of course, the suitability of the relevant monitoring
relay for the monitored line frequencies must also be considered.
Operator controls
The digitally adjustable monitoring relays have three keys for navigating on the menu levels:
• SET key for navigating to the menu levels and for switching between the menu levels
• 2 arrow keys for setting parameters
Navigation through the menu system of the monitoring relays is explained below in a schematic
diagram.
Depending on the device version and as long as no faults have occurred, one or more different
measuring values ① can be displayed with the help of the arrow keys. In the event of a fault, the
display indicates the type of fault ③ by means of flashing symbols. By repeatedly pressing the
SET key briefly, it is possible to set the desired type of monitoring (overshoot, undershoot, or
range monitoring) and parameterize the lower and/or upper threshold ② in accordance with
the device-specific setting ranges. After pressing the SET key for at least 2.5 s, in a further step,
the basic device parameters ④, such as the switching behavior of the output relays, the reset
response in the event of a fault, and/or the tripping delay times can be set.
Menu-based operation
581
9$/8(
2.
Threshold1
0HDV9DOXH
0HDV9DOXH
Threshold2
(5525
(UURU
(UURU
(UURU ...
6(7
Parameter1 Parameter2 Parameter3 ...
! V V
3 2
The RUN menu shows the up-to-date current measured value ①. You can use the arrow keys
to change between the individual measuring values on devices with multiple outputs. In this
case, the display automatically switches between the name of the measured value and the
actual measured value.
② represents the selected type of monitoring (overshoot, undershoot, or range monitoring). An
arrow symbol indicates whether the measuring value is within, above or below the set
thresholds.
Next to this, one or two symbols ③ represent the type (changeover contact or semiconductor
output) and the switching status of the outputs.
Entry Display at the RUN menu level Display at the SET menu level
1. Current measuring value (MeasValue1 / Parameter1
MeasValue2 / ...) or error symbol (Error1 /
Error2 / Error3 / ...), switching contact sym‐
bols and monitoring methods for diagnostics
2. Threshold1 Parameter2
3. Threshold2 Parameter3
4. Threshold3 ...
5. ...
Note
The setting options a device actually offers depends on the type and can be looked up in the
relevant chapters on operation in this manual.
You can find full details of menu-based operation for the individual devices in Appendix D
"Menu-based operation" (Page 291).
Note
Aborting the menu switchover
The switchover process will be interrupted if the SET key is released while or is
displayed. The menu will revert to the menu command you were working with when the switch
was initiated.
Note
Reset in the event of an error
To reset the device, it is necessary to press both arrow keys simultaneously for more than 2.5 s
after removal of the cause of error and with Hand‑RESET active. While the keys are pressed,
appears on the display.
The possible settings for resetting the devices via the "Reset response" parameter can be found
in the "Operation" chapters of the relevant monitoring relays.
Note
3UG4625 residual current monitoring relays automatically return to showing the actual
measured value 30 seconds after the last limit value change.
Note
Quitting the SET menu level will trigger an internal reset in 3UG4621/3UG4622/3UG4625 and
3UG4641 device variants and restart the startup delay.
Overview
SIRIUS 3RR2 current monitoring relays are suitable for current monitoring of motors or other
loads. They are capable of two-phase or three-phase monitoring of the rms value of AC currents,
checking that the values do not overshoot or undershoot set thresholds.
SIRIUS 3RR2 current monitoring relays are available in the following variants:
• Basic version (3RR21): with analog setting using rotary buttons, two-phase monitoring and
CO contact.
• Basic version (3RR22): digital setting via a display, 3-phase monitoring, CO contact, and
semiconductor output; also monitors phase sequence, phase failure, ground fault and
blocking current
• Version for IO-Link (3RR24): same as standard version, but additionally with IO-Link interface
for direct interfacing to a PLC for remote parameterization, remote diagnostics, cyclic transfer
of measured values, support of the parameter server functionality of IO-Link (with master as
from specification V1.1), with integrated runtime and switching cycle counter
You can find further information in the Manual "3UG48/3RR24 Monitoring Relays for IO-Link".
Whereas apparent current monitoring is primarily used in the rated torque range or for overload,
active current monitoring can be used to observe and evaluate the degree of loading across a
motor's entire torque range.
Apparent current monitoring and active current monitoring are described in more detail in the
Chapter "Parameters (Page 265)".
System integration
3RR2 current monitoring relays are available in three sizes, S00, S0 and S2. 3RR2 current
monitoring relays are matched to 3RT2 contactors and 3RF34 (size S0) solid-state contactors in
terms of their electrical and mechanical features. They can be integrated in the feeder by means
of direct mounting. This eliminates the need for the main circuit to be wired separately and no
additional transformers are required.
For a stand-alone assembly or if an overload relay is being used at the same time, terminal
supports for stand-alone assembly are available for separate DIN rail mounting.
3RR2 current monitoring relays were conceived for monitoring 3-phase systems.
Depending on the device version used, monitoring of 1- or 2-phase AC systems is possible with
the following wiring variants:
/ / / / / / 1 /
55
55 55 55 55
0
a
1 1 1 2
① Complete device functionality possible
② Device functionality only possible with limitations:
• Residual current monitoring not possible (→ switch off)
• Phase sequence monitoring not possible (→ switch off)
• Active current monitoring not possible (→ switch off)
Note
The monitoring functions of the 2 phases (3RR21) or the 3 phases (3RR22) are ORed to the
output relay(s), i.e. a fault in one monitored phase (e.g. current violation L1) already affects the
output relay(s).
Accessories
The accessories have been tailored to the current monitoring relays; they can be mounted easily
and without the need for tools. The accessories are described in the Chapter "Accessories for
3RR2 current monitoring relays (Page 227)".
• Monitoring for no-load operation and load shedding (as might be the case, for example, in
the event of a torn V belt)
• Underload monitoring in the lower performance range (if a pump was running in no-load
operation, for example)
• Monitoring for overload (as might affect pumps with a soiled filter system, for example)
• Monitoring the performance of electrical loads such as heaters
• Monitoring for incorrect phase sequences on mobile equipment such as compressors or
cranes
• Monitoring for high-impedance faults to ground (caused by damaged insulation or moisture,
for example)
Function Application
• Undercurrent • Emergency lighting
• Overcurrent • Heating systems (electroplating plants, plastic injec‐
• Apparent current tion machines, paintshops)
• Active current (3RR22 only) • Lamps (tunnels, OR lighting, traffic lights, signal sys‐
tems, UV lamps, infrared radiators, laser lamps)
• Phase failure / wire break
• Fan
• Phase sequence (3RR22 only)
• Pumps
• Internal ground fault detection (fault cur‐
rent) (3RR22 only) • Sawing system
Table 4-2 Performance features of 3RR2 current monitoring relays with analog setting
Table 4-3 Performance features of 3RR2 current monitoring relays with digital setting
You can find further technical information on 3RR24 in the Manual "3UG48/3RR24 monitoring
relays for IO-Link (http://support.automation.siemens.com/WW/view/en/54375430)" on the
internet.
4.3.2 Properties
Monitoring re‐ Current 3RT20 1 S00 contactors 3RT20 2 S0 contactors 3RT20 3 S2 contactors
lay type range 3/4/5.5/7.5 kW 5.5/7.5/11/15/18.5 kW 18.5/22/30/37 kW
3RR2141 1.6 to 16 A ✓ X X
3RR2241 1.6 to 16 A ✓ X X
3RR2142 4.0 to 40 A X ✓ X
3RR2242 4.0 to 40 A X ✓ X
3RR2143 8.0 to 80 A X X ✓
3RR2243 8.0 to 80 A X X ✓
You can find more information on the connection terminals and the permissible conductor cross-
sections in Chapter "Connection methods (Page 18)".
You can find information on connecting in Chapter "Circuit diagrams (Page 54)".
B1 Supply voltage ∼ / + Observe the relevant standards and regulations for the configuration of control panels and the
B2 Supply voltage ∼ / - parts and components contained therein, e.g. when dimensioning the cables.
Select a current-limiting power supply, for example, to protect these circuits.
When selecting the source and the connecting cable, observe the load characteristics of the
current monitoring relay. The same applies to the selection of suitable protection devices.
You can find all the technical data of the product in the Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/16205/td).
Further recommendations, e.g. the use of miniature circuit breakers or equipment circuit
breakers in control circuits, can be found under the following link:
Practical tip for control panels: Selecting and dimensioning suitable power supplies quickly and
reliably. (https://new.siemens.com/global/en/markets/panel-building/tipps/design-and-
engineering-in-the-control-circuit.html)
32 Output relay K1 You can find technical data of the product in the Siemens Industry Online Support (https://
changeover con‐ support.industry.siemens.com/cs/ww/en/ps/16205/td).
tact NC contact
31 Output relay K1
changeover con‐
tact root
34 Output relay K1
changeover con‐
tact NO contact
2/T1 Main circuit termi‐ For information on the protection of the main circuit of the 3RT2. contactors used, refer to the
4/T2 nals Equipment Manual - SIRIUS Contactors / Contactor Combinations 3RT (https://
support.industry.siemens.com/cs/ww/en/view/60306557) and the technical data sheet
6/T3 (https://support.industry.siemens.com/cs/ww/en/ps/16132/td).
14 / 22 Feed-through con‐ For information on the protection of the auxiliary contacts of the 3RT2. contactors used, refer
tactor auxiliary to the Equipment Manual - SIRIUS Contactors / Contactor Combinations 3RT (https://
switch (S00) support.industry.siemens.com/cs/ww/en/view/60306557) and the technical data sheet
(https://support.industry.siemens.com/cs/ww/en/ps/16132/td).
A2 Feed-through con‐ For information on the protection of 3RT2. contactor coils, refer to the Equipment Manual -
tactor coil terminal SIRIUS Contactors / Contactor Combinations 3RT (https://support.industry.siemens.com/cs/ww/
(S00) en/view/60306557) and the technical data sheet (https://
support.industry.siemens.com/cs/ww/en/ps/16132/td).
4.4.2 Function
General functionality
Depending on the setting, the current monitoring relays monitor an AC load current that flows
through terminals 1/L1 - 2/T1 and 3/L2 - 4/T2 of the device for overshoot (I▲) or undershoot (I▼)
or in range monitoring (I▲ and I▼ ≠ OFF).
Depending on their design, the current monitoring relays are powered with a 24 V AC/DC or
24 to 240 V AC/DC supply voltage through terminals B1/B2.
With two-phase apparent current monitoring, one changeover output, and analog adjustment,
the 3RR214.‑.A.30 (basic‑version) current monitoring relays provide a high level of monitoring
reliability particularly in the rated and overload ranges.
The switching states of the output relay are given below in the section entitled "Function
diagrams."
,>$@
/
/
/
1 2 W>V@
If a cable break (zero current in branch circuit 1/L1 - 2/T1 or 3/L2 - 4/T2) is detected (time ①), all
running delay times are aborted, the red FAULT LED flashes rapidly and the CO contact
immediately changes its switching state.
When a defined current flow returns to both branch circuits (1/L1 - 2/T1, 3/L2 - 4/T2) (time ②),
the CO contact responds according to the defined settings.
If Memory = I, the tripping state is saved.
If the unmonitored phase 5/L3 - 6/T3 fails, this can be detected if a motor is connected by an
increase in current in both phases 1/L1 - 2/T1 and 3/L2 - 4/T2.
Function diagrams
Memory = O: 2 I Memory = I: 2 I
I▲ %%
%%
1.
2
I▼ = Off !, a, !, 2 2.
I
I
, ,
+ \VW + \VW
a,
a,
)$8/7 )$8/7
/(' /('
OFF F LASH O F F F LASH O F F F LASH ON OFF F LASH OFF
OFF F LASH OFF F LASH ON ON F LASH OFF
slow slow slow fast
slow slow slow
onD el onD el I D el
onD el
onD el I D el
+ \VW
+ \VW
, ,
a, a,
)$8/7 )$8/7
/(' /(' OFF O F F F LASH ON ON OFF
OFF F LASH ON F LASH O F F F LASH ON OFF F LASH OFF F LASH F LASH
slow slow slow fast slow slow slow
onD el
onD el onD el I D el onD el I D el
I▲ %% %% 1.
2 I
I▼ !, , a, !, , 2 2. I
, + \VW , + \VW
+ \VW + \VW
, ,
a, a,
)$8/7 )$8/7
/(' /('
OFF F LASH ON F LASH OFF F LASH ON OFF F LASH ON OFF F LASH OFF OFF F LASH OFF F LASH ON ON ON F LASH OFF
slow slow slow slow fast slow slow slow
onD el
onD el onD el I D el I D el onD el I D el
4.4.3 Operation
Parameters
The following parameters can be set on the relevant rotary button using a screwdriver:
Table 4-7 Parameter information, 3RR21 current monitoring relays with analog setting
Hysteresis
The hysteresis is set to a fixed value of 6.25% of the set threshold.
Changes to settings of threshold for current overshoot (I▲) and threshold for current undershoot
(I▼)
Note
Deactivating monitoring
If both threshold values are deactivated (OFF), the following will no longer be monitored:
• Current overshoot
• Current undershoot
The following parameters continue to be monitored:
• Phase failure
Required tools
The same screwdriver can be used to set the parameters as for mounting the current monitoring
relays.
4.4.4 Diagnostics
Status display
On the current monitoring relay with analog setting, two status LEDs indicate the operating
state:
• FAULT (red)
• READY (green)
Display Meaning
FAULT off Measured value is within range limits
FAULT steady on Device has tripped
FAULT flashes at 1 Hz Delay time is running
FAULT flashes at 4 Hz Cable break/phase failure detected
READY off Voltage is not applied at B1 - B2
READY on Voltage is applied at B1 - B2
You can find more information about the LED display response in the Chapter "Function
(Page 50)."
You can find more information on the connection terminals and the permissible conductor cross-
sections in Chapter "Connection methods (Page 18)".
You can find information on connecting in Chapter "Circuit diagrams (Page 63)".
B1 Supply voltage ∼ / + Observe the relevant standards and regulations for the configuration of control panels and the
B2 Supply voltage ∼ / - parts and components contained therein, e.g. when dimensioning the cables.
Select a current-limiting power supply, for example, to protect these circuits.
When selecting the source and the connecting cable, observe the load characteristics of the
current monitoring relay. The same applies to the selection of suitable protection devices.
You can find all the technical data of the product in the Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/16205/td).
Further recommendations, e.g. the use of miniature circuit breakers or equipment circuit
breakers in control circuits, can be found under the following link:
Practical tip for control panels: Selecting and dimensioning suitable power supplies quickly and
reliably. (https://new.siemens.com/global/en/markets/panel-building/tipps/design-and-
engineering-in-the-control-circuit.html)
Q Semiconductor You can find technical data of the product in the Siemens Industry Online Support (https://
output, e.g. for pre- support.industry.siemens.com/cs/ww/en/ps/16205/td).
warning threshold
32 Output relay K1 CO You can find technical data of the product in the Siemens Industry Online Support (https://
contact NC con‐ support.industry.siemens.com/cs/ww/en/ps/16205/td).
tact, e.g. for alarm
threshold
31 Output relay K1 CO
contact root, e.g.
for alarm threshold
34 Output relay K1 CO
contact NO con‐
tact, e.g. for alarm
threshold
2/T1 Main circuit termi‐ For information on the protection of the main circuit of the 3RT2. contactors used, refer to the
4/T2 nals Equipment Manual - SIRIUS Contactors / Contactor Combinations 3RT (https://
support.industry.siemens.com/cs/ww/en/view/60306557) and the technical data sheet
6/T3 (https://support.industry.siemens.com/cs/ww/en/ps/16132/td).
14 / 22 Feed-through con‐ For information on the protection of the auxiliary contacts of the 3RT2. contactors used, refer
tactor auxiliary to the Equipment Manual - SIRIUS Contactors / Contactor Combinations 3RT (https://
switch (S00) support.industry.siemens.com/cs/ww/en/view/60306557) and the technical data sheet
(https://support.industry.siemens.com/cs/ww/en/ps/16132/td).
A2 Feed-through con‐ For information on the protection of 3RT2. contactor coils, refer to the Equipment Manual -
tactor coil terminal SIRIUS Contactors / Contactor Combinations 3RT (https://support.industry.siemens.com/cs/ww/
(S00) en/view/60306557) and the technical data sheet (https://
support.industry.siemens.com/cs/ww/en/ps/16132/td).
4.5.2 Function
General functionality
Depending on its setting, the plant is monitored for overshoot (I▲ CO contact, I!
▲ semiconductor output) or undershoot (I▼ CO contact, I!▼ semiconductor output) or for
a range (I▲ , I!▲ and I▼ , I!▼ ≠ OFF).
Depending on their design, the current monitoring relays are powered with a 24 V AC/DC or
24 to 240 V AC/DC supply voltage through terminals B1/B2.
If the power supply is switched on, the CO contact and the semiconductor output responds after
expiry of the set ON-delay time (onDel) on the set circuit principle (closed-circuit principle NC or
open-circuit principle NO).
The 3RR224.‑.F.30 current monitoring relays with digital setting (standard variations) monitor
the AC load current (apparent current Is or active current Ip) that flows through the 1/L1 - 2/T1,
3/L2 - 4/T2 and 5/L3 - 6/T3 device terminals. The monitoring relay has two separate outputs,
which respond to separately settable thresholds.
The devices support further diagnostic options such as residual current monitoring and phase
sequence monitoring, and are also be used to monitor motors even below the rated torque. The
monitoring relays have an additional separate semiconductor output, an actual-value display,
and support digital adjustment.
The 3RR22 current monitoring relays have a display and are parameterized with three keys.
You will find the adjustment ranges and factory settings of the available parameters in Chapter
"Operation (Page 60)".
You can find a description of the individual parameters in Chapter "Parameters (Page 265)".
You will find the switching states of the output relay below in the Section "Function diagrams"
and in the Chapter "Diagnostics (Page 62)."
Reset response
If the device is set to automatic reset, the CO contact and the semiconductor output will respond
once a previously occurring error has been dealt with and the reclosing delay time has elapsed.
A previously occurring error is, therefore, not saved.
If manual RESET is selected, the CO contact remains in the current switching state even if a
previously occurring error has been dealt with.
This saved fault condition can be reset by pressing both arrow keys at the same time for longer
than 2.5 s or by disconnecting and reconnecting the auxiliary voltage.
Note
Semiconductor output
The semiconductor output always responds in automatic reset.
,>$@
/
/
/
1 2 W>V@
If a cable break is detected in a branch circuit (time ①), all delay times which are running (onDel,
RsDel, Del) are aborted and both the CO contact and the semiconductor output change their
switching state immediately (≤ 200 ms).
When a defined current flow returns to all branch circuits (1/L1 - 2/T1, 3/L2 - 4/T2 und 5/L3 - 6/T3)
(time ②), the CO contact and the semiconductor output respond again according to the
defined settings.
If manual RESET (Mem = yes) is selected, the tripping state is saved.
Function diagrams
n x I▲
Q[,Ⴃ Q[,Ⴃ
,Ⴃ,Ⴃ ,Ⴃ,Ⴃ
+ \VW + \VW
a, a,
4RQ 4RQ
4RII 4RII
onD el onD el D el R sD el R sD el
onD el onD el D el R sD el R sD el
a, a,
4RQ
4RQ
4RII
4RII
onD el onD el D el R sD el
onD el onD el D el R sD el
, , , ,
+ \VW + \VW
a, a,
4RQ 4RQ
4RII 4RII
onD el onD el D el R sD el D el R sD el
onD el onD el D el R sD el D el R sD el
a,
a,
4RQ 4RQ
4RII 4RII
4.5.3 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3RR22 current monitoring
relay with digital setting:
Table 4-8 Parmeter information, 3RR22 current monitoring relays with digital setting
Note
The "current overshoot" or "current undershoot" monitoring mode is defined with the setting
OFF for the upper and lower threshold.
Note
Deactivating monitoring
If the upper and lower threshold values are deactivated (OFF), monitoring will cease for:
• Current overshoot
• Current undershoot
• Blocking current
The following parameters continue to be monitored:
• Fault current (if activated)
• Incorrect phase sequence (if activated)
• Phase failure
The up-to-date measured value is displayed permanently.
4.5.4 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and faults are indicated on the display as a diagnostics message with
flashing symbols:
You will find more information about the switching behavior of the output relays in Chapter
"Function (Page 57)".
Application areas
The 3UG4501 filling level monitoring relays are used, for example, in the following
applications:
Table 5-1 Application areas of the 3UG4501 filling level monitoring relay
Function Application
• One-point filling level • Open-loop control of a bilge pump, e.g. on ships or construction sites
monitoring and two- • Filling level monitoring of lubricants
point filling level mon‐
• Filling level monitoring of dosing containers
itoring
• Filling level monitoring of oil sumps
• Overflow protection
• Filling level monitoring of rainwater catchment basins
• Dry-run protection
• Water supply
• Leakage monitoring
• Waste water treatment plant
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 71)".
5.3 Functions
General functionality
The 3UG4501 filling level monitoring relays and the connectable 2‑pole or 3‑pole 3UG3207-..
probes are used to monitor the filling levels of electrically conductive liquids.
Monitoring
The working principle of the 3UG4501 filling level monitoring relay is based on measurement of
the electrical resistance of the liquid between the probes (minimum and maximum level) or the
reference potential (conductive measurement principle). The output relay changes its switching
state if the measured value is below the sensitivity set on the front. The probes (e.g. 3UG3207‑..)
are powered with alternating current (AC measured current) to exclude electrolysis phenomena
in the liquid.
Note
The filling level monitoring relays do not have active monitoring of probe defects or probe
conductor defects. Therefore when selecting the probes and routing the cable, make sure that
this source of error is precluded. For example, use stable bow probes if wire electrodes are in
danger of being broken.
Depending on their design, the 3UG4501 filling level monitoring relays are powered with a
24 V AC/DC or 24 to 240 V AC/DC rated control supply voltage through terminals A1+ / A2-. When
the rated control supply voltage is applied, the green LED next to the coil symbol on the device
cover lights up.
Note
On the 3UG4501‑.AA30 devices with 24 V AC / DC versions, as a common reference for the AC
probe voltage at terminals Min and Max, terminal M must not be connected to terminals A1 / A2
of the device or grounded!
On the 3UG4501‑.AW30 24 to 240 V AC / DC versions, terminals M, Min, and Max are electrically
isolated from terminals A1 and A2 of the rated control supply voltage!
Note
The specified voltages represent the absolute thresholds.
Tripping delay
Tripping can be delayed by 0.5 to 10 s to avoid tripping the switching function too early when
the level has not quite been reached (e.g. wave motion or foaming of the liquid).
The switching states of the output relay are given below in the section entitled "Function
diagrams."
These necessary accessories are described in Chapter "Probes for the 3UG4501 monitoring relay
(Page 233)."
Note
At the terminals, other resistance sensors in the range 2 to 200 kΩ (e.g. photoresistor,
temperature sensors, resistor-based position encoders, etc.) can also be connected. The
monitoring relays are therefore also suitable as resistance triggers.
Two-point monitoring
If the liquid level reaches the maximum probe while the minimum probe and reference probe are
immersed, the output relay changes its switching state. The output relay reverts to its original
switching state as soon as the minimum probe is no longer in contact with the liquid.
One-point monitoring
For closed loop control of only one level, the terminals for Min and Max are bridged on the
filling level monitoring relay. The output relay changes its switching state as soon as the liquid
level has been reached. The output relay reverts to its original switching state as soon as the
probe is no longer in contact with the liquid.
Reset response
For reliable resetting, the rated control supply voltage must be interrupted at least for the set
delay time of +0.5 s.
When the rated control supply voltage is interrupted, the output relay returns to the quiescent
state when the power failure backup time has expired (contact 11‑12 is closed, contact 11‑14
is open). If the rated control supply voltage is switched on again after > 0.5 s + Delay ( t ) (device
reset), the output relay switches depending on the set relay switching behavior.
Drainage control (OV 1)), two-point closed-loop Inflow control (UN 2)), two-point closed-loop con‐
control trol
Reset Reset
A1/A2 A1/A2
Min Min
t t t t t t t t
11/14 11/14
11/12 11/12
1)
OV = overshoot
2)
UN = undershoot
Drainage control (OV 1)), one-point closed-loop Inflow control (UN 2)), one-point closed-loop con‐
control trol
Reset Reset
A1/A2 A1/A2
> 0,5 s + t > 0,5 s + t
t t t t t t t t
11/14 11/14
11/12 11/12
1)
OV = overshoot
2)
UN = undershoot
5.4 Operation
Parameters
The following parameters can be set on the relevant rotary button using a screwdriver:
Required tools
The same screwdriver can be used to set the parameters as for mounting the filling level
monitoring relays.
5.5 Diagnostics
The switching behavior of the output relay is shown in Chapter "Functions (Page 66)."
3UG4501
$ದ
Wiring examples
Drainage control
AC/+U AC/+U
11 11
K1 K1
12 14 A1 (+) Max Min M 12 14
A1 (+) Max Min M
3UG45 01 3UG45 01
K1 K1
29 29
5VHQV 'HOD\ 5VHQV 'HOD\
A2 (–) A2 (–)
AC/0V AC/0V
Inflow control
AC/+U AC/+U
11 11
K1 K1
A1 (+) Max Min M 12 14 A1 (+) Max Min M 12 14
3UG45 01 3UG45 01
K1 K1
81 81
5VHQV 'HOD\ 5VHQV 'HOD\
A2 (–) A2 (–)
AC/0V AC/0V
Application areas
The various line monitoring relays are used, for example, in non-stationary systems such as
refrigeration containers, construction site compressors, and cranes. The devices are used in the
following application areas:
Function Application
Phase sequence • Direction of rotation of the drive
• Refrigeration trucks
• Refrigerators
• Saws
• Pumps
• Rollers
• Transport of persons (elevators, moving staircases and walkways)
Phase failure • A fuse has tripped
• Control supply voltage failure
• Cable break
• Crane systems
• Electrical welding
• Emergency generating sets (banks, hospitals, alarm systems, power
plants)
• Transport of persons (elevators, moving staircases and walkways)
Phase asymmetry • Motor protection (overheating of the motor through asymmetric volt‐
age)
• Detection of asymmetric systems
Undervoltage • Increased current on a motor with corresponding overheating
• Unintended device reset
• Mains failure – particularly with battery supply
• Heating systems
• Cranes
• Elevators
• Protection on unstable systems (switchover to emergency current, mon‐
itoring of the generator)
Overvoltage • System protection against destruction caused by supply overvoltages
• Energy supply to the line
• Lamps (UV lamps, laser lamps, OP lighting, tunnels, traffic lights)
⑤ Status display: LED contact symbol (green)
Terminal labels
L1, L2, L3 Rated control supply voltage
12 Output relay K1 CO contact NC contact
L1 L2 L3 11
11 Output relay K1 CO contact root
12 14
14 Output relay K1 CO contact NO contact
22 Output relay K2 CO contact NC contact (on the 3UG4511‑.B only)
3UG4511-.....
21 Output relay K2 CO contact root (on the 3UG4511‑.B only)
24 Output relay K2 CO contact NC contact (on the 3UG4511‑.B only)
12 11 14
22 21 24
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 77)".
6.2.2 Function
General functionality
The 3UG4511 line monitoring relays monitor the phase sequence in a three-phase system.
The devices are self-powered (measuring voltage = rated control supply voltage) and work on
the closed-circuit principle. Depending on the version, the line monitoring relays are powered
with a rated control supply voltage of 160 V to 260 V (3UG4511‑..N20), 320 to 500 V
(3UG4511‑..P20) and 420 to 690 V (3UG4511‑..Q20) through terminals L1 / L2 / L3.
All 3UG4511 line monitoring relays feature at least one output relay (output relay K1 CO
contact). The 3UG4511-.B line monitoring relays have an additional relay (output relay K2 CO
contact). Output relay K2 switches synchronously with output relay K1.
No settings are required for operation.
Note
The specified voltages represent the absolute thresholds.
Monitoring
If the correct phase sequences are applied to terminals L1‑L2‑L3, the output relay picks up after
the response time and the "contact symbol" LED lights up green. If the phase sequence is
incorrect, the output relay remains in its quiescent position. After the power system has been
disconnected, the output relays drop out after the response time has expired.
Note
After failure of one phase, motors generate a reverse voltage at the terminal of the failed phase
due to the regenerative power recovery. This can be up to 90 % of the line voltage in magnitude.
Because the 3UG4511 line monitoring relays are not protected against reverse voltage, such a
phase failure is not reliabily detected.
If this type of monitoring is required, the 3UG4512 line monitoring relay should be used, for
example!
You will find the switching states of the output relays below in section "Function diagrams" and
in Chapter "Diagnostics (Page 77)."
Reset response
The device features an autoreset that resets the output relay to its original state after an error
message and rectification of the fault that has occurred.
L1-L2-L3 L3-L2-L1
11/14 11/14
ON 11/12
OFF 11/12
21/24 21/24
21/22 21/22
6.2.3 Diagnostics
Status display
The following information about the operating state is displayed on the 3UG4511 line
monitoring relay:
Operating status LED contact symbol (green) State of the output relay
12/ 11/ 14
22/ 21/ 24
Correct phase sequence On
You will find more information about the switching behavior of the output relays in Chapter
"Function (Page 75)."
/ / /
8*
/ / /
8*
Note
It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection
depends on the cross-section used.
Note
The 3UG4511 line monitoring relays are only suitable for line frequencies of 50 / 60 Hz!
22 21 24
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 82)".
6.3.2 Function
General functionality
The 3UG4512 line monitoring relays monitor the phase sequence and the phase failure of one
of the three phases in a three-phase system. The asymmetry threshold is 10 %.
The devices are self-powered (measuring voltage = rated control supply voltage) and work on
the closed-circuit principle. The 3UG4512 line monitoring relays monitor all phases of three-
phase AC networks from 160 to 690 V through terminals L1 / L2 / L3 and also draw power from
all three phases simultaneously.
All 3UG4512 line monitoring relays feature at least one output relay (output relay K1 CO
contact). The 3UG4512-.B line monitoring relays have an additional relay (output relay K2 CO
contact). Output relay K2 switches synchronously with output relay K1.
No settings are required for operation.
Note
The specified voltages represent the absolute thresholds.
Monitoring
Thanks to a special measuring method, a phase failure is detected with certainty despite wide-
range voltage from 160 to 690 V AC and reverse power of up to 90 % from the load in the case
of regenerative power recovery.
If the line voltage is switched on, the LED "coil symbol" will light up green. If the correct phase
sequence is applied to terminals L1‑L2‑L3, the output relays pick up. If the phase sequence is
incorrect, the "phase failure / phase sequence" LED flashes red and the output relays remain in
their quiescent position. On a phase failure, the "phase failure / phase sequence" LED lights up
red continuously and the output relays drop out to protect the application from any damage that
may result.
You will find the switching states of the output relays below in section "Function diagrams" and
in Chapter "Diagnostics (Page 81)."
Reset response
The device features an autoreset function. The autoreset function resets the output relay to its
original state after an error message and rectification of the fault that has occurred.
Note
The red "phase failure / phase sequence" LED is a fault diagnostics display and does not indicate
the current state of the relay!
11/14
11/12
11/14
11/12
21/24
21/22
21/24
LED 1
21/22
OFF FLASH OFF
LED 1
2
OFF ON OFF
2
① Red ① Red
② Phase failure ② Phase sequence
6.3.3 Diagnostics
Status display
The following information about the operating state is displayed on the 3UG4512 line
monitoring relay:
You will find more information about the switching behavior of the output relays in Chapter
"Function (Page 79)".
/ / /
8*
/ / /
8*
Note
It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection
depends on the cross-section used.
Note
The 3UG4512 line monitoring relays are only suitable for line frequencies of 50 / 60 Hz!
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 88)".
6.4.2 Function
General functionality
The 3UG4513 line monitoring relays monitor for phase sequence, phase failure of one of the
three phases, and undershoot of at least one line-to-line voltage of the set nominal line voltage
by 20 % in a three-phase system.
The devices are self-powered (measuring voltage = rated control supply voltage) and work on
the closed-circuit principle. The 3UG4513 line monitoring relays monitor all phases of three-
phase AC networks from 160 to 690 V through terminals L1 / L2 / L3 and also draw power from
all three phases simultaneously.
The 3UG4513 line monitoring relay features two rotary buttons for setting the trip delay (Delay)
and the nominal line voltage (Un 3AC).
The hysteresis is 5 % of the set value of the nominal line voltage.
The 3UG4513 line monitoring relays feature 2 output relays (output relay K1 and output relay
K2). The relays work synchronously.
Note
The specified voltages represent the absolute thresholds.
Monitoring
If the line voltage is switched on, the LED "coil symbol" will light up green. If the correct phase
sequence is applied to terminals L1‑L2‑L3 and if the monitored line-to-line voltage is in the
permissible range of the set nominal line voltage (Un 3AC), the output relays pick up.
If the phase sequence is incorrect, the "phase failure / phase sequence" LED flashes red and the
output relays remain in their quiescent position.
If the monitored line-to-line voltage falls symmetrically (all three phase voltages at the same
time) or asymmetrically (only one phase voltage) to more than 20 % below the value for the
nominal line voltage set on the front of the device, after the time set on the front has elapsed
(Delay), the output relays will drop out and the "phase failure / phase sequence" LED will light up
red continuously. On a phase failure, the "phase failure / phase sequence" LED lights up red
continuously and the output relays drop out to protect the application from any damage that
may result. The set delay time has no effect on the phase failure monitoring.
Thanks to a special measuring method, a phase failure is detected with certainty despite wide-
range voltage from 160 to 690 V AC and reverse power of up to 80 % from the load in the case
of regenerative power recovery.
You will find the switching states of the output relays below in section "Function diagrams" and
in Chapter "Diagnostics (Page 87)."
Reset response
The device features an autoreset that resets the output relays to their original state after an error
message and rectification of the fault that has occurred.
Note
The red LED is a fault diagnostics display and does not indicate the current state of the relay!
4
L1-L2-L3 L2-L3 L1-L2-L3 L3-L2-L1
5%
-20 %
3~ n 11/14
11/12
11/14
11/12
21/24
21/22
21/24
LED 1
21/22
OFF FLASH OFF
LED 1 2
OFF ON OFF ON OFF
2 3
① LED phase failure / phase sequence: Red ① LED phase failure / phase sequence: Red
② Phase failure ② Phase sequence
③ Tripping delay time
④ Hysteresis
6.4.3 Operation
Parameters
The following parameters can be set on the relevant rotary button using a screwdriver:
Required tools
The same screwdriver can be used to set the parameters as for mounting the line monitoring
relays.
6.4.4 Diagnostics
Status display
The following information about the operating state is displayed on the 3UG4513 line
monitoring relays:
You will find more information about the switching behavior of the output relays in Chapter
"Function (Page 84)."
/ / /
8*
Note
It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection
depends on the cross-section used.
Note
The 3UG4513 line monitoring relays are only suitable for line frequencies of 50 / 60 Hz!
onDel -> Power on delay
Del -> Umin/Asym delay
⑥ Legend for menu
Mem ? -> Memory?
? -> Phase sequence?
NC -> Circuit principle
⑦ Display for parameterization, actual-value indication, and diagnostics
Terminal labels
L1, L2, L3 Rated control supply voltage
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
3UG4614-..... 14 Output relay K1 CO contact NO contact
22 Output relay K2 CO contact NC contact
12 11 14
21 Output relay K2 CO contact root
24 Output relay K2 CO contact NO contact
22 21 24
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 94)".
6.5.2 Functions
General functionality
The 3UG4614 line monitoring relays monitor a three-phase system for phase
asymmetry, undervoltage, phase failure, and phase sequence.
The devices feature a wide-range voltage input and are self-powered (measuring voltage
= rated control supply voltage). The 3UG4614 line monitoring relays monitor all phases of three-
phase AC networks from 160 to 690 V through terminals L1 / L2 / L3 and also draw power from
all three phases simultaneously.
The 3UG4614 line monitoring relays feature 2 output relays (output relay K1 and output relay
K2). The relays work synchronously.
You will find the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 92)."
You will find a description of the individual parameters in Chapter "Parameters (Page 265)."
Note
The specified voltages represent the absolute thresholds.
Monitoring
The output relays respond in accordance with the set relay switching behavior (closed-circuit
principle NC or open-circuit principle NO) if the following conditions are met:
• The correct phase sequence is present at terminals L1‑L2‑L3
• The monitored voltage (Ux-y) is larger than the set value
• The voltage asymmetry (Asy) is smaller than the set value
If a fault occurs (phase failure, incorrect phase sequence, or phase asymmetry), the output
relays switch in accordance with the relay switching behavior.
Note
The line-to-line voltages are measured as a reference for voltage asymmetry and phase failure
(20%).
In the case of incorrect direction of rotation, the 3UG4614 line monitoring relays immediately
shut down. Thanks to a special measuring method, a phase failure is reliably detected despite a
wide voltage range of 160 to 690 V AC and feedback of up to 80% by the load, even in case of
regenerative feedback.
If one of the phases fails, the output relays are switched off immediately to protect the
application from consequential damage. Set delay times have no effect on the phase failure
monitoring.
Note
The 3UG4614 line monitoring relays are only suitable for line frequencies of 50 / 60 Hz.
Startup delay
After applying the supply voltage or resetting the monitoring relays, the set ON-delay begins
(onDel). During this time, undershooting or overshooting of the set threshold values will not
cause the CO contact to respond but instead will result in a restart of the ON-delay.
Tripping delay
If the measured value overshoots or undershoots the set threshold after expiry of the ON-delay
time (onDel), the set tripping delay time (Del) and the relay symbol will flash. After expiry of this
time, the output relays change the switching state. On the display, the current measuring value
and the symbol for undershoot or overshoot flash.
You will find the switching states of the output relays below in section "Function diagrams" and
in Chapter "Diagnostics (Page 93)".
L3-L2-L1 L3-L2-L1
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
L
L1-L2-L3 L2-L3 L1-L2-L3 L1-L2-L3 L2-L3 L1-L2-L3
L1-L2-L3-N L1-L2-L3 L1-L2-L3-N L1-L2-L3-N L1-L2-L3 L1-L2-L3-N
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
Ux-y >
U Hyst U Hyst
Ux-y Ux-y
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
Asym
> ! Asy ! Asy
Hyst, 2% Hyst, 2%
0% 0%
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
6.5.3 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3UG4614 line monitoring
relays:
Table 6-3 Parmeter information, 3UG4614 line monitoring relays with digital setting
6.5.4 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and line faults are indicated as a diagnostics message with flashing
symbols:
You will find more information about the switching behavior of the output relays in Chapter
"Functions (Page 89)".
6.5.4.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 265)").
The following settings can be selected:
• Automatic reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt with.
• Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the error
has not been removed, a new error message appears immediately. Alternatively, the devices
can be reset by switching the rated control supply voltage on and off.
/ / /
8*
Note
It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection
depends on the cross-section used.
SIRIUS
④ Device article number
3 160-690V
⑤ Label
⑥ Legend for menu
⑦ Display for parameterization, actual-value indication, and diagnostics
U Del -> Umin delay
U Del -> Umax delay
Mem ? -> Memory? Terminal labels
? -> Phase sequence?
NC -> Circuit principle L1, L2, L3 Rated control supply voltage
N Neutral conductor (only on 3UG4616)
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
3UG4616-..... 14 Output relay K1 CO contact NO contact
22 Output relay K2 CO contact NC contact
21 Output relay K2 CO contact root
12 11 14
24 Output relay K2 CO contact NO contact
22 21 24
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 102)".
6.6.2 Functions
General functionality
The 3UG4615 line monitoring relays monitor a three-phase system for phase
failure, undervoltage, overvoltage, and phase sequence.
Note
The 3UG4616 line monitoring relays have the same functions as the 3UG4615 monitoring relays
and also monitor the neutral conductor for failure.
The devices feature a wide-range voltage input and are self-powered (measuring voltage
= rated control supply voltage). Depending on the version, the line monitoring relays are
powered with a line-to-line voltage of 160 to 690 V (3UG4615) or with a line-to-neutral voltage
of 90 to 400 V (3UG4616) through terminals L1 / L2 / L3.
The 3UG4615 / 3UG4616 line monitoring relays feature 2 output relays (output relay K1 and
output relay K2).
The 3UG4615 / 3UG4616 line monitoring relays have a display and are parameterized with three
keys.
You will find the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 99)."
You will find a description of the individual parameters in Chapter "Parameters (Page 265)."
Note
The specified voltages represent the absolute thresholds.
Monitoring
The 3UG4615 / 3UG4616 line monitoring relays have two output relays. With output relay K1,
a three-phase system is monitored for undervoltage. With output relay K2, a three-phase system
is monitored for overvoltage.
The output relays respond in accordance with the set relay switching behavior (closed-circuit
principle NC or open-circuit principle NO).
If a fault occurs (phase failure, incorrect phase sequence, voltage undershoot or voltage
overshoot), the output relays switch in accordance with the relay switching behavior. In the case
of voltage undershoot or voltage overshoot, the output relays do not respond until expiry of the
set tripping delay time (U▼Del and U▲Del).
In the case of incorrect direction of rotation, the devices immediately shut down.
The display indicates the following voltages in the case of the line monitoring relays:
• 3UG4615: Line-to-line voltage between L1 and L2, L1 and L3, L2 and L3
• 3UG4616: Line-to-neutral voltage between L1 and N, L2 and N, L3 and N
Thanks to a special measuring method, a phase failure is detected with certainty despite wide-
range voltage from 160 to 690 V AC and reverse power of up to 80 % from the load in the case
of regenerative power recovery.
On failure of one of the phases (or neutral conductor failure for the 3UG4616 line monitoring
relays), the output relays drop out immediately to protect the application from any damage that
may result. Set delay times have no effect on the phase failure monitoring.
Note
The 3UG4615 and 3UG4616 line monitoring relays are only suitable for line frequencies of 50 /
60 Hz!
You will find the switching states of the output relays below in section "Function diagrams" and
in Chapter "Diagnostics (Page 100)."
L3-L2-L1 L3-L2-L1
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
L
LN L1-L2-L3 L2-L3 L1-L2-L3 L1-L2-L3 L2-L3 L1-L2-L3
L1-L2-L3-N L1-L2-L3 L1-L2-L3-N L1-L2-L3-N L1-L2-L3 L1-L2-L3-N
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
U Del U Del
Ux-y
> !U !U
Hyst Hyst
Ux-y Ux-y
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
U Del U Del
6.6.3 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3UG4615 and 3UG4616 line
monitoring relays:
Table 6-4 Parmeter information, 3UG4615 and 3UG4616 line monitoring relays with digital setting
6.6.4 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and line faults are indicated as a diagnostics message with flashing
symbols:
Note
On phase failure or phase sequence error, both CO contacts respond.
Note
If the monitoring relays are used downstream of a frequency converter, it is necessary to obtain
a waveform without additional zero crossings of the voltage. This can be achieved with the help
of a sine-wave filter.
You will find more information about the switching behavior of the output relays in Chapter
"Functions (Page 97)".
6.6.4.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 265)").
/ / /
8*
1 / / /
8*
Note
It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection
depends on the cross-section used.
SIRIUS
④ Device article number
3 160-690V
⑤ Label
⑥ Legend for menu
⑦ Display for parameterization, actual-value indication, and diagnostics
Del -> Umin/Umax/
Asym delay
Mem ? -> Memory?
Terminal labels
L1, L2, L3 Rated control supply voltage
N Neutral conductor (on 3UG4618 only)
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
3UG4618-....
22 Output relay K2 CO contact NC contact
21 Output relay K2 CO contact root
12 11 14
24 Output relay K2 CO contact NO contact
22 21 24
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 111)".
6.7.2 Functions
General functionality
The 3UG4617 line monitoring relays monitor a three-phase system for phase sequence, phase
failure, phase asymmetry, undervoltage, and overvoltage.
Note
The 3UG4618 line monitoring relays have the same functions as the 3UG4617 monitoring relays
and also monitor the neutral conductor for failure.
The devices feature a wide-range voltage input and are self-powered (measuring voltage
= rated control supply voltage) and work on the closed-circuit principle. Depending on the
version, the line monitoring relays are powered with a line-to-line voltage of 160 to 690 V
(3UG4617) and with a line-to-neutral voltage of 90 to 400 V (3UG4618) through terminals
L1 / L2 / L3.
The 3UG4617 / 3UG4618 line monitoring relays have a display and are parameterized with three
keys.
You will find the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 108)."
You will find a description of the individual parameters in Chapter "Parameters (Page 265)."
Note
The specified voltages represent the absolute thresholds.
Monitoring
Output relay K1 is for warning or shutdown on faults in the power system (voltage, asymmetry).
Output relay K2 responds differently depending on the phase sequence.
Phase sequence
If the correct phase sequence is applied to terminals L1‑L2‑L3, output relay K2 (relay contact
21-22-24) picks up. This is represented by a relay symbol on the display. If the phase sequence
is incorrect, output relay K2 will not pick up. An error is not indicated on the display; only the relay
symbol remains in the disconnected state.
Undervoltage or overvoltage
If the monitored voltages (Ux-y) are larger than the set lower voltage value (U▼) and smaller
than the set upper voltage value (U▲), i.e. they are within the voltage limits and the line voltage
asymmetry (Asy) is less than the set value, the output relay K1 (relay contact 11‑12‑14) picks up
approx. 50 ms after the response of output relay K2 (relay contact 21‑22‑24).
The display indicates the following voltages in the case of the line monitoring relays:
• 3UG4617: Line-to-line voltage between L1 and L2, L1 and L3, L2 and L3
• 3UG4618: Line-to-neutral voltage between L1 and N, L2 and N, L3 and N
Phase failure
In the case of a phase failure (or neutral conductor failure for the 3UG4618 line monitoring
relays), output relay K1 (relay contact 11‑12‑14) drops out without delay to protect the
application from any damage that may result. Set delay times have no effect on phase failure
monitoring.
In the case of voltage undershoot, voltage overshoot, or asymmetry overshoot faults, output
relay K1 drops out after the set tripping delay time (Del).
Thanks to a special measuring method, a phase failure is detected with certainty despite wide-
range voltage from 160 to 690 V AC and reverse power of up to 80 % from the load in the case
of regenerative power recovery.
Incorrect direction of rotation
With the CO contact 21‑22‑24 of the output relay K2, for example, an incorrectly fed phase
sequence for a load connected downstream can be automatically corrected using an external
reversing combination. The Chapter "Circuit diagrams (Page 111)" provides an example of wiring
for automatic phase correction.
Note
The 3UG4617 and 3UG4618 line monitoring relays only evaluate the phase sequence while all
3 phases are present. For safety reasons, the phase sequence is not reevaluated after 2-phase
operation or a phase failure after which the third phase has appeared. In this case, the output
relay for the phase rotation remains in its last switching state. The phase sequence is not
reevaluated until after the device has been reset or all 3 phases have been simultaneously
switched off and on again.
Note
The 3UG4617 and 3UG4618 line monitoring relays are only suitable for line frequencies of 50 /
60 Hz!
You will find the switching states of the output relays below in the Section "Function diagrams"
and in the Chapter "Diagnostics (Page 109)."
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
50 ms 50 ms
Ux-y >
U Hyst U Hyst
Ux-y Ux-y
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
50 ms Del 50 ms Del
Ux-y
> !U !U
Hyst Hyst
Ux-y Ux-y
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
50 ms Del 50 ms Del
Asym
> ! Asy ! Asy
Hyst, 2% Hyst, 2%
0% 0%
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
50 ms Del 50 ms Del
6.7.3 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
3 2
Parameter information
The table below shows the settable parameter information of the 3UG4617 and 3UG4618 line
monitoring relays:
Table 6-5 Parmeter information, 3UG4617 and 3UG4618 line monitoring relays with digital setting
6.7.4 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and line faults are indicated as a diagnostics message with flashing
symbols:
Note
CO contact 1 switches on all types of error.
CO contact 2 is for operating a reversing combination.
You will find more information about the switching behavior of the output relays in Chapter
"Functions (Page 105)".
6.7.4.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 265)").
The following settings can be selected:
• Automatic reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt with.
• Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the error
has not been removed, a new error message appears immediately. Alternatively, the devices
can be reset by switching the rated control supply voltage on and off.
/ / /
8*
1 / / /
8*
Note
It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection
depends on the cross-section used.
L1L2L3
3UG4617 H1
12
K1 ⊗
11
14 K4 K3
22
K2 21
24
3UG4618
N K3 K4
M
N 3~
Application areas
The current monitoring relays are used, for example, in the following applications:
Function Application
• Undercurrent monitoring and overcurrent mon‐ • Threshold switch for analog signals from 4 to 20
itoring mA
• Monitoring the functionality of electrical loads • Emergency lighting (failure of a lamp → drop in
• Wire-break monitoring current strength in the system)
• Heating systems (electroplating plants, plastic
injection machines, paintshops)
• Lamps (tunnels, OP lighting, traffic lights, sig‐
nal systems, UV lamps, infrared radiators, laser
lamps)
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 121)".
7.3 Functions
General functionality
Depending on the set threshold, the 3UG4621 / 3UG4622 current monitoring relays monitor a
single-phase AC load current (RMS value) or DC load current flowing over terminals IN and M of
the device for overshoot (I▲) or undershoot (I▼) or in range monitoring (I▲ and I▼). The
devices differ by their measuring ranges and versions with different rated control supply
voltages. The true root mean square value (tRMS) of the current is measured. Depending on
their design, the current monitoring relays are powered with a rated control supply voltage of
24 V AC/DC or 24 to 240 V AC/DC supply voltage through terminals A1/A2.
The 3UG4621 / 3UG4622 current monitoring relays have a display and are parameterized with
three keys.
You will find the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 119)."
You will find a description of the individual parameters in Chapter "Parameters (Page 265)."
Monitoring
If the rated control supply voltage is switched on and no load current is as yet flowing, the display
indicates 0.0 mA (on the 3UG4621) or 0.00 A (on the 3UG4622) and shows a symbol for current
overshoot monitoring, current undershoot monitoring, or range monitoring.
ON-delay time
If the load current overshoots the lower measuring range limit 3 mA (3UG4621) or 50 mA
(3UG4622), the set ON-delay time begins (onDel). During this time, undershooting or
overshooting of the set threshold values will not result in a relay response of the CO contact.
Tripping delay
If a threshold is reached, the output relay K1 responds after expiry of the tripping delay time
(I ▼ D el) depending on the set relay switching behavior. An output change-over contact is
▼
Note
For AC currents I > 10 A, commercially available current transformers, e.g. 4NC, can be used as
accessories. You will find more information in Catalog LV10 (https://
support.industry.siemens.com/cs/de/de/view/109482234/en).
measured. In this case, the monitoring relay will hold the contactor until a fault occurs or the
current flow is interrupted by a further button or switch. If an ON-delay time is necessary, initial
switching of the output relay on application of the supply voltage or on starting the ON-delay
time must be suppressed by means of external logic.
Note
The name of the parameter values is based on the assumption that the ON-delay time onDel = 0
is set. The output relay K1 then responds either immediately when the supply voltage US is
applied or after measurement of a current flow on the set NC or NO working principle.
You will find the switching states of the output relay below in the section entitled "Function
diagrams" and in Chapter "Diagnostics (Page 120)."
Function diagrams (from application of the rated control supply voltage US = on)
A1-A2 A1-A2
I>
-!, -!,
I > = off
I I
Hyst Hyst
J=0 J=0
11/14 11/14
11/12 11/12
Hyst Hyst
I I
J=0 J=0
11/14 11/14
11/12 11/12
Function diagrams (on reaching the lower measuring range limit of the measuring current
I > 3 mA / 50 mA)
I>
J> I J> I
I > = off
I I
Hyst Hyst Hyst Hyst
J=0 J=0
11/14 11/14
11/12 11/12
Hyst Hyst
I I
J=0 J=0
11/14 11/14
11/12 11/12
7.4 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3UG4621 and 3UG4622
current monitoring relays:
Table 7-2 Parmeter information, 3UG4621 and 3UG4622 current monitoring relays with digital setting
Note
"Overshoot" monitoring mode is activated when the undershoot threshold is set to OFF.
"Undershoot" monitoring mode is activated when the overshoot threshold is set to OFF.
Note
Deactivating monitoring
If the upper and lower threshold values are deactivated (OFF), monitoring will cease for:
• Current overshoot
• Current undershoot
The up-to-date measured value is displayed permanently.
7.5 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and faults are indicated on the display as a diagnostics message with
flashing symbols:
You will find more information about the switching behavior of the output relay in Chapter
"Functions (Page 114)."
7.5.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 265)").
The following settings can be selected:
• Automatic reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt with.
• Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the error
has not been removed, a new error message appears immediately. Alternatively, the devices
can be reset by switching the rated control supply voltage on and off.
,1 $ $
,!
0
Note
On the 24 V AC / DC version of the 3UG4621/22‑.AA30, terminals A2 and M (GND) are electrically
connected in the device! The load current must flow through terminal M (GND).
On the 24 to 240 V AC/DC versions of the 3UG4621/22‑.AW30, terminals A2 and M (GND) are
electrically separated!
< >
12 14 < > 12 14
A2 M A2 M
Mload
Load
3UG462.-.AW30 single-phase operation
Note
If this arrangement is not complied with, the monitoring relay may be destroyed and the short-
circuit current may damage the plant!
< >
12 14
A2 M
Mload
• three-phase
o.k. o.k.
24 V AC/DC L1 L2 L3 24 V AC/DC L1 L2 L3
A1 IN A1 IN
A2 M
A2 M
load
load
• single-phase
o.k. o.k.
24 V AC/DC 24 V AC/DC
Load
Load
A1 IN 11 A1 IN
12 14
optional A2 M A2 M
Note
Configuration
In the case of 3UG462.-.AA30, A2 and M (GND) are internally electrically connected!
If the load to be monitored and the current monitoring relay are powered from the same system,
terminal A2 is not required!
The load current must always flow away through M (GND), otherwise the current monitoring
relay may be destroyed!
Application areas
Residual current monitoring relays are used in industry to:
• Protect systems from damage caused by fault currents
• Prevent production losses caused by unplanned downtime
• Perform maintenance to meet all demands
3UG4625 residual current monitoring relays are used in conjunction with 3UL23 residual
current transformers to monitor systems where environmental conditions increase the chance
of higher fault currents. The devices are used for applications including in the following areas:
Note
3UG4625 residual current monitoring relays monitor devices and systems for their correct
function.
They are not suitable for personal protection or protection from fires.
SIRIUS
④ Device article number
⑤ Label
⑥ Legend for menu
⑦ Display for parameterization, actual-value indication, and diagnostics
Terminal labels
A1+ Rated control supply voltage ∼ / +
A2- Rated control supply voltage ∼ / -
C1 Connection for 3UL23 residual current transformer
C2
12 Output relay K1 CO contact NC contact (alarm output)
3UG4625-.....
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
12 11 14
22 Output relay K2 CO contact NC contact (warning output)
21 Output relay K2 CO contact root
22 21 24
24 Output relay K2 CO contact NO contact
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 137)".
8.3 Functions
General functionality
3UG4625 residual current monitoring relays are supplied with a rated control supply voltage of
24 to 240 V AC/DC (rms value), 50/60 Hz via terminals A1+ and A2-.
3UG4625 residual current monitoring relays are equipped with a display and are parameterized
with three keys.
You will find the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 134)".
You will find a description of the individual parameters in Chapter "Parameters (Page 265)".
The main conductors and, if present, the neutral conductor to which the load is connected, are
routed through the opening of the ring core of a 3UL23 residual current transformer. There is a
secondary winding around this ring core to which the 3UG4625 residual current monitoring
relay is connected.
In fault-free operation of a system, the sum of inflowing and outflowing currents equals zero. No
current is then induced in the secondary winding of the residual current transformer.
When an insulation error occurs, for example, the sum of the inflowing currents is greater than
the sum of the outflowing currents.
The residual current induces a secondary current in the secondary winding of the transformer.
This current is evaluated in the monitoring relay and used to display the current residual current
and to switch the output relays when the set warning threshold or the tripping threshold is
overshot.
To ensure a maximum plant availability 3UG4625 residual current monitoring relays focus on
the following features:
• High degree of measuring accuracy
3UG4625 residual current monitoring relays in combination with 3UL23 residual current
transformers operate with a measuring accuracy of -7.5 %/+7.5 %. This enables set limit
values to be monitored very precisely. False tripping caused by measuring errors is
minimized.
• Adjustable delay times
The ON-delay time of 3UG4625 residual current monitoring relays can be configured freely,
enabling fading out of fault currents due to high input currents that are measured during
motor start-up only. Short-term fault currents or emitted interference can be easily faded out
using the adjustable tripping delay time. For more information please see the Chapter
"Measuring accuracy (Page 126)".
• Wide-range supply voltage
3UG4625 residual current monitoring relays can be operated at an input voltage of between
24 and 240 V AC/DC. This not only ensures that devices can be used worldwide, but that
temporary supply voltage dips do not cause a failure of the monitoring function, that is, plant
stoppage.
The switching response of the relay outputs can be set to open-circuit principle (NO) if you
intend to continue plant operation even if the monitoring function fails. This means only
actively determined fault currents are reported via the relay outputs.
• Permanent self-monitoring
The permanent self-monitoring feature of 3UG4625 ensures reliable system monitoring.
The connected 3UL23 residual current transformer is also permanently monitored for open-
circuit or short-circuit. As a result, cyclic manual tests to ensure its function are obsolete.
Regardless of this, it is possible at any time to test the output relays for switching capability.
Pressing the Set button for longer than 2.5 s will call up parameter assignment mode. This
will cause the output relays to switch to the fault state as a safety precaution. Proceed as
described above to quit parameter assignment mode. The output relay will once again switch
back to its normal operating state.
Measuring accuracy
The combination of 3UG4625 residual current monitoring relay and 3UL23 residual current
transformer is designed so that a warning or alarm is triggered at the latest upon exceeding the
set limit values. To safeguard this function, slightly higher fault currents than those actually
measured are displayed and compared with the set limit values.
The measuring accuracy is -7.5 %/+7.5 % of the value displayed. This takes into account the
measuring accuracy of monitoring relay and residual current transformer.
0LQLPXPDGMXVWDEOHSDUDPHWHUV,ႣIRUDOOWUDQVIRUPHUVL]HVDW+]
0LQLPXPDGMXVWDEOHOLPLW,Ⴃ>P$@
5DWHGFXUUHQW>$@
If monitoring is required within limit values that are lower than those recommended, we
recommend the use of delay times, particularly if false tripping occurs exclusively during motor
start-up.
If delay times do not lead to the desired result, the use of shield sleeves may considerably lower
the minimum possible monitoring limit.
For more information see Chapters "Installation specifications (Page 237)" and "Potential for
optimization (Page 240)".
The monitored current waveforms also have a strong influence on the measuring accuracy. In
the case of loads with generalized phase control, deviations from the measuring accuracy can
occur when monitoring for high residual current limits. The cause of this is the extreme
difference between the monitored rms values and the peak values of the residual current. The
more extreme the generalized phase control, the shorter the time during which current flows,
and the lower the resulting rms value. To achieve and monitor a high rms value in such a case,
an extremely high peak value of the residual current is necessary. In the case of high currents,
current transformers tend towards saturation in which a further increase in current on the
primary side does not result in an equivalent increase on the secondary side. In the case of
extreme peak values of the residual current, the measuring accuracy suffers as a result of this
principle. Due to the great difference between the peak value and the rms value, monitoring for
lower limits is useful.
Monitoring
Initialization
When the monitoring relay is connected to the supply voltage, the initialization phase starts and
internal functional tests are performed. During the initialization phase that lasts approximately
1.6 s, the connection to the 3UL23 residual-current transformer is one of the things that is
checked. During this time, no measurement or monitoring of the fault current takes place. - - A
is shown on the display. The relay switching behavior during the initialization phase can be
determined with the help of the "Init" parameter. In the factory setting ("Init" parameter = ERR),
the output relays switch to the fault state until completion of the initialization phase because
there is no valid measuring result of the fault current.
If the parameter is set to "OK", it is assumed that there is no internal fault and the fault current
will be within the set limits. For this reason, the output relays are switched to the work position
when the supply voltage is present.
This parameter setting is useful if the residual current monitoring relays are not permanently
connected to the supply voltage and instead are to be started immediately when the monitored
application is started, and output relays in the alarm position result in immediate shutdown of
the application again, e.g. when connecting a contactor with interruption of the self-locking by
the output relay contacts.
After completion of the initialization phase, a permanent self-test takes place without
interrupting the monitoring function.
Normal operation
If the measured fault current exceeds the set warning threshold (I!), the associated CO contact
21-22-24 changes the switching state without delay. On the display, the arrows for "threshold
overshot" and "measured value within the set limits" ( ) flash alternately as an indication.
On the display, the currently displayed measuring value and the symbol for overshoot flash.
Note
Currents with line frequencies of between 16 and 400 Hz can be monitored by 3UG4625
residual current monitoring relays in conjunction with 3UL23 residual current transformers!
Startup delay
The set ON-delay time is triggered if the fault current overshoots the lower measuring range limit
of 20 mA (onDel). During this time, exceeding the set limit values will not trigger a relay response
of the CO contacts.
To start a drive, the output relay switches to the correct state during the ON-delay time (onDel),
depending on the selected open-circuit principle or closed-circuit principle, even if the measured
value remains above the set value.
Tripping delay
If the measured value exceeds the set threshold (I▲) after expiry of the ON-delay time (onDel),
the set tripping delay time (I▲Del) starts and the relay symbol flashes. After expiry of this time,
the output relay K1 changes the switching state. Exceeding the set warning threshold will cause
output relay K2 to switch immediately without taking into account the tripping delay time. On
the display, the actual measured value and the symbol for overshoot flash.
You will find the switching states of the output relays below in section "Function diagrams" and
in Chapter "Diagnostics (Page 135)".
Tripping conditions
The combination of 3UG4625 residual current monitoring relay and 3UL23 residual current
transformer responds according to the following tripping conditions:
These necessary accessories are described in Chapter "3UL23 residual current transformers for
3UG4625 monitoring relays (Page 235)."
Note
Do not ground the neutral conductor downstream of the residual current transformer as
otherwise fault current monitoring functions can no longer be ensured.
Note
Difference between Hyst and Hysteresis
In the following diagrams, the term "Hyst" refers to the "Hysteresis" parameter. The "Hysteresis"
parameter refers to the monitored limit values (I▲) and can be set in the SET menu.
However, "Hyst = 5 %" refers to the warning thresholds (I!) and is permanently set to 5 %.
Mem = no
I >I
Init = ERR I >I !
I
Hyst
I! Hyst = 5 %
I = 0.02A
I=0
11/14
11/12
21/24
21/22
Init I Del onDel
onDel
Mem = no
I >I
Init = ERR I >I !
I
Hyst
I!
Hyst = 5 %
I = 0.02A
I=0
11/14
11/12
21/24
21/22
Init I Del onDel
onDel
I!
Hyst = 5 %
I = 0.02A
I=0
11/14
11/12
21/24
21/22
Init I Del onDel
onDel
onDel
I!
Hyst = 5 %
I = 0.02A
I=0
11/14
11/12
21/24
21/22
Init
onDel
I Del onDel onDel
Mem = no
I >I
Init = OK I >I !
I
Hyst
I! Hyst = 5 %
I = 0.02A
I=0
11/14
11/12
21/24
21/22
Init I Del onDel
onDel
Mem = no
I >I
Init = OK I >I !
I
Hyst
I!
Hyst = 5 %
I = 0.02A
I=0
11/14
11/12
21/24
21/22
Init I Del onDel
onDel
I!
Hyst = 5 %
I = 0.02A
I=0
11/14
11/12
21/24
21/22
Init I Del onDel
onDel
onDel
I!
Hyst = 5 %
I = 0.02A
I=0
11/14
11/12
21/24
21/22
Init
onDel
I Del onDel onDel
Note
The system is immediately switched off in the event of an open-circuit or short-circuit in the
transformer connection cables.
8.4 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The following table lists the adjustable parameter information for the 3UG4625 residual current
monitoring relay:
Table 8-2 Parameter information, 3UG4625 residual current monitoring relays with digital setting
Note
Various parameters are deactivated by setting OFF.
8.5 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and faults are indicated on the display as a diagnostics message with the
following symbols:
You will find more information about the switching behavior of the output relay in Chapter
"Functions (Page 126)."
8.5.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 265)").
Note
The warning threshold is always reset by autoreset.
$ & &
$
Note
3UG4625 residual current monitoring relays are suitable for operation with 3UL23 residual
current transformers for external ground-fault monitoring. The output signal of the
3UL23 residual current transformer is connected to terminals C1 and C2 of the monitoring relay.
To avoid interference injection, which could result in incorrect measurements, these connecting
lines must be routed as parallel as possible and twisted, or shielded cables must be used.
F1
3UL23
/ / / 1
S1
S2
3UG4625
$ & &
load
$
Ungrounded, insulated systems (IT networks) are always used when high requirements are
placed on the reliability of the power supply, e.g. emergency lighting. IT systems are supplied via
an isolation transformer or voltage sources such as batteries or a generator. An insulation fault
that occurs between an external conductor and ground represents a grounding of this
conductor. This does not result in the closing of a circuit and operation can continue without
hazard (single fault security). Before a second insulation fault occurs, the first fault must be
corrected (e.g. in accordance with DIN VDE 0100‑410). Insulation monitoring relays are used to
implement this requirement. The insulation monitoring relays measure the resistance of the
external conductor and the neutral conductor against ground, and immediately report a fault if
the set insulation resistance is undershot. This procedure enables controlled shutdown, or
correction of the fault without interrupting the power supply.
The insulation monitoring relays monitor the following fault types, depending on the version:
• Open circuit
• Incorrect settings
• Ungrounded, strictly AC systems for insulation faults
• Ungrounded, strictly DC systems for insulation faults
• Ungrounded, mixed DC systems and AC systems for insulation faults (e.g. AC systems with
rectifiers or switched-mode power supplies)
Note
The use of two 3UG458 devices in a galvanically connected area (monitored area) is not
permissible.
3UG458. 3UG458.
① Monitored area
Application areas
The 3UG458. insulation monitoring relays are used in the following applications, for example:
Function Application
• Insulation monitor for • Emergency power supplies
ungrounded systems • Safety lighting
• Industrial production plants with high availability requirements (chemi‐
cal industry, automobile manufacture, printing)
• Shipbuilding and railways
• Mobile power generators (aircraft)
• Renewable energies (wind energy and photovoltaic plants)
• Mining industry
Note
The 3UG4582 and 3UG4583 insulation monitors are only suitable for use in systems with
frequency converters (primary or secondary side) if operation with generated frequencies <
15Hz and > 400Hz is ruled out.
The 3UG4581 version is not suitable for operation with a frequency converter.
✓: Function available
1p: Monitoring is 1-phase
2p: Monitoring is 2-phase
2p + N: Monitoring is 2-phase + N conductor
3p: Monitoring is 3-phase
3p + N: Monitoring is 3-phase + N conductor
— : Function not available
1)
Configurable
General data
✓: Function available
— : Function not available
1)
With 3UG4983‑.A voltage reducer module
2)
Configurable
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 158)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 154)".
1
① Terminal block:
Screw-type connections are possible.
Y1 Y2 Y3
② Test/RESET button1)
③ Status display: LED for device status (green)
2 ④ Status display: LED for monitoring status F (red)
R=R.1+R.2
R.1-VALUE kΩ
⑤ Status display: LED output contact status (yellow)
9
3
⑥ Label
8
R.2-VALUE kΩ
4
⑦ Device article number
5
⑧ Rotary knob for adjusting the insulation resistance (R.2 for the units position of
R)
7
⑨ Rotary knob for adjusting the insulation resistance (R.1 for the tens position of
6 R)Setting value "0" is colored yellow.2)
Terminal labels
1 A1+ Rated control supply voltage ∼ / +
L
A2- Rated control supply voltage ∼ / -
Y1 Control inputs; isolation control
14 12 A2-
Y2 Y1-Y3: Remote test
Y3 Y2-Y3: Remote reset/autoreset
L Measuring signal input, connection to phase or N conductor
Measured signal input, grounding connection
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
1)
A test is only possible if there is no fault. A reset is only possible if the measured value is greater
than the set threshold including the hysteresis.
2)
Information on setting accuracy
• at setting value "0", a setting accuracy of >15 % applies for R
• at setting value ">1", a setting accuracy of 6 % applies for R
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 158)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 154)".
1
① Terminal block:
Supports spring-loaded connection technology.
Y1 Y2 Y3
② Test/RESET button1)
③ Status display: LED for device status (green)
2 ④ Status display: LED for monitoring status F (red)
R=R.1+R.2
R.1-VALUE kΩ
⑤ Status display: LED output contact status (yellow)
9
3
⑥ Label
8
R.2-VALUE kΩ
4
⑦ Device article number
5
⑧ Rotary knob for adjusting the insulation resistance (R.2 for the units position of
R)
7
⑨ Rotary knob for adjusting the insulation resistance (R.1 for the tens position of
6 R)Setting value "0" is colored yellow.2)
Terminal labels
1 A1+ Rated control supply voltage ∼ / +
L
A2- Rated control supply voltage ∼ / -
Y1 Control inputs; isolation control
14 12 A2-
Y2 Y1-Y3: Remote test
Y3 Y2-Y3: Remote reset/autoreset
L Measuring signal input, connection to phase or N conductor
Measured signal input, grounding connection
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
1)
A test is only possible if there is no fault. A reset is only possible if the measured value is greater
than the set threshold including the hysteresis.
2)
Information on setting accuracy
• at setting value "0", a setting accuracy of >15 % applies for R
• at setting value ">1", a setting accuracy of 6 % applies for R
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 158)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 154)".
9.3.2 Functions
General functionality
The 3UG4581 insulation monitoring relays are supplied with a rated control and supply voltage
of 24 V to 240 V AC/DC, and they monitor the insulation resistance in ungrounded AC systems
in accordance with IEC 61557‑8.
The devices can monitor control circuits (1-phase) and main circuits (3-phase). For this purpose,
the insulation resistance between the system cables (terminal L) and system ground (terminal
) is measured. Systems with rated system voltages Un = 0 to 400 V AC (50 to 60 Hz) can be
connected directly to the measuring inputs, and their insulation resistance can be monitored.
The 3UG4581 insulation monitoring relays have two rotary buttons for adjusting the insulation
resistance R and a test/RESET button for performing an internal test on the device, or for
resetting the device.
If the measured value drops below the set threshold, the output relays are set to fault status.
For systems with voltages over 400 V AC, the 3UG4583 insulation monitoring relays with
3UG4983 voltage reducer module can be used for system voltages to 690 V AC.
You will find the adjustment ranges and factory settings of the available parameters in Chapter
"Operator control (Page 152)".
You will find a description of the individual parameters in the Chapter "Parameters (Page 265)".
Monitoring
The system to be monitored is connected to terminal L (connection to phase or N conductor).
The ground potential is connected to terminal .
The devices work according to the closed-circuit principle NC.
After applying the rated control and supply voltage, the insulation monitoring relay goes
through an internal test that checks the proper functioning of the operational device. The test
encompasses an internal test of the device at hardware and firmware level, as well as system
diagnostics with calculation of the first measured value of the insulation resistance. If there are
no internal device faults or external faults on completion of this test, output relay K1 picks up.
This test can take several seconds depending on individual system properties.
If the measured value undershoots the set threshold, output relay K1 drops out. If the measured
value overshoots the threshold including hysteresis, output relay K1 picks up (if autoreset is
active). All operating statuses of the insulation monitoring relay are displayed via three LEDs.
Note
If the continuously present rated system voltage is greater than 240 V, a minimum gap of 10 mm
must be maintained to the next device.
You will find the switching states of the output relay below in the section "Functions (Page 148)"
and in Chapter "Diagnostics (Page 153)".
WV
/('
/(' )
/('
① Test (Y1-Y3)
② Reset (Y2-Y3)
③ Measured value
④ Hysteresis
⑤ Threshold
⑥ Green
⑦ Red
⑧ Yellow
tS = Time for internal device test after applying the supply voltage
WV
/('
/(' )
/('
① Test (Y1-Y3)
② Reset (Y2-Y3)
③ Measured value
④ Hysteresis
⑤ Threshold
⑥ Green
⑦ Red
⑧ Yellow
tS = Time for internal device test after applying the supply voltage
Parameters
The following parameters can be set on the two ten-level rotary buttons (absolute scale) with the
help of a screwdriver:
Tools required
The same screwdriver can be used to set the parameters as for wiring the insulation monitoring
relays.
9.3.4 Diagnostics
Status display
The following information indicates the operating state on the 3UG4581 insulation monitoring
relays:
1)
The device has tripped following an insulation fault. The fault has been stored and the insulation
resistance has reverted to a value above the set threshold including hysteresis.
2)
Dependent on the fault.
The switching behavior of the output relay is shown in Chapter "Functions (Page 148)".
$
N˖
$
$ $
< < < < < <
/ /
$ $
/ /
1 1
3( 3(
3-wire AC system
$ $
< < < < < <
/ /
$ $
/ /
/ /
/ /
3( 3(
4-wire AC system
$ $
< < < < < <
/ /
$ $
/ /
/ /
/ /
1 1
3( 3(
Application examples
The figure below shows monitoring for ground fault/insulation fault in the case of an
ungrounded 2‑wire IT AC system. The voltage source is the secondary side of an isolating
transformer that galvanically isolates the system and the downstream circuit.
/
1
3(
$
< < <
8*
$:
/
$
① Loads
Figure 9-2 Monitoring for ground fault/insulation fault in the case of an ungrounded 2-wire IT AC system
Note
The maximum cable length of the control cables is 50 m or 100 pF/m.
The figure below shows monitoring for ground fault/insulation fault in the case of an
ungrounded 4‑wire IT AC system. The voltage source is the secondary side of an isolating
transformer that galvanically isolates the system and the downstream circuit.
/
/
/
1
3(
$
< < <
8*
$:
/
$
0
a
Figure 9-3 Monitoring for ground fault/insulation fault in the case of an ungrounded 4-wire IT AC system
Note
The maximum cable length of the control cables is 50 m or 100 pF/m.
9.3.6 Characteristics
9
8
, $
9
8
, $
)
FRV˳
Figure 9-6 Reduction factor F in the case of inductive AC load
>$@
① Operating cycles
② 250 V, resistive load
③ Switching current
Figure 9-7 Contact service life
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 190)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 181)".
1
① Terminal block:
Screw-type connections are possible.
Y1 Y2 Y3
② Test/RESET button
③ Status display: LED for device status (green)
2 ④ Status display: LED for monitoring status F (red)
⑤
TEST/
R=R.1+R.2
RESET
Status display: LED output contact status (yellow)
R.1-VALUE kΩ
9
3
⑥ Label
8
R.2-VALUE kΩ
4
⑦ Device article number
5
⑧ Rotary knob for adjusting the insulation resistance (R.2 for the units position of
R)
7
⑨ Rotary knob for adjusting the insulation resistance (R.1 for the tens position of
6 R)Setting value "0" is colored yellow.1)
Terminal labels
1 A1+ Rated control supply voltage ∼ / +
L+ L-
A2- Rated control supply voltage ∼ / -
Y1 Control inputs; isolation control
14 12 A2-
Y2 Y1-Y3: Remote test
Y3 Y2-Y3: Remote reset/autoreset
L+ Measuring signal input, connection to phase or L+
L- Measuring signal input, connection to phase, N conductor or L-
KE Measuring signal input, control ground connection for open-circuit monitoring
Measured signal input, grounding connection
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
1)
Information on setting accuracy
• at setting value "0", a setting accuracy of >15 % applies for R
• at setting value ">1", a setting accuracy of 8 % applies for R
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 190)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 181)".
1
① Terminal block:
Supports spring-loaded connection technology.
Y1 Y2 Y3
② Test/RESET button
③ Status display: LED for device status (green)
2 ④ Status display: LED for monitoring status F (red)
R=R.1+R.2
R.1-VALUE kΩ
⑤ Status display: LED output contact status (yellow)
9
3
⑥ Label
8
R.2-VALUE kΩ
4
⑦ Device article number
5
⑧ Rotary knob for adjusting the insulation resistance (R.2 for the units position of
R)
7
⑨ Rotary knob for adjusting the insulation resistance (R.1 for the tens position of
6 R)Setting value "0" is colored yellow.1)
Terminal labels
1 A1+ Rated control supply voltage ∼ / +
L+ L-
A2- Rated control supply voltage ∼ / -
Y1 Control inputs; isolation control
14 12 A2-
Y2 Y1-Y3: Remote test
Y3 Y2-Y3: Remote reset/autoreset
L+ Measuring signal input, connection to phase or L+
L- Measuring signal input, connection to phase, N conductor or L-
KE Measuring signal input, control ground connection for open-circuit monitoring
Measured signal input, grounding connection
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
1)
Information on setting accuracy
• at setting value "0", a setting accuracy of >15 % applies for R
• at setting value ">1", a setting accuracy of 8 % applies for R
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 190)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 181)".
1)
Information on setting accuracy
• at setting value "0", a setting accuracy of >15 % applies for R
• at setting value ">1", a setting accuracy of 6 % applies for R
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 190)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 181)".
1
① Terminal block:
Screw-type connections are possible.
② Test/RESET button
③ Rotary knob for adjusting the insulation resistance (R2.1 for
the tens position of R2)
2
Rx=Rx.1+Rx.2
TEST/
RESET Setting value "0" is colored yellow.1)
④
R1.1-VALUE kΩ R2.1-VALUE kΩ
11 3 Status display: LED for device status (green)
4 ⑤ Status display: LED for monitoring status F (red)
R1.2-VALUE kΩ R2.2-VALUE kΩ
5
⑥ Status display: LED output contact status (yellow)
10 6
⑦ Rotary knob for adjusting the insulation resistance (R2.2 for
7 the units position of R2)
9
ON 8 ⑧ Label
4 3 2 1
⑨ Device order number
⑩ Rotary knob for adjusting the insulation resistance (R1.2 for
12 14 L+ VS V1+ V1-
1 the units position of R1)
⑪ Rotary knob for adjusting the insulation resistance (R1.1 for
22 24 L- KE A2- the tens position of R1)
Setting value "0" is colored yellow.1)
Terminal labels
A1+ Rated control supply voltage ∼ / +
A2- Rated control supply voltage ∼ / -
Y1 Control inputs; isolation control
Y2 Y1-Y3: Remote test
Y3 Y2-Y3: Remote reset/autoreset
VS Connection terminals for the voltage reducer module
V1+
V1-
L+ Measuring signal input, connection to phase or L+
L- Measuring signal input, connection to phase, N conductor or
L-
KE Measuring signal input, control ground connection for open-
circuit monitoring
Measured signal input, grounding connection
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
22 Output relay K2 CO contact NC contact
21 Output relay K2 CO contact root
24 Output relay K2 CO contact NO contact
1)
Information on setting accuracy
• at setting value "0", a setting accuracy of >15 % applies for R
• at setting value ">1", a setting accuracy of 6 % applies for R
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 190)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 181)".
1
① Terminal block:
Supports spring-loaded connection technology.
② Test/RESET button
③ Rotary knob for adjusting the insulation resistance (R2.1 for
the tens position of R2)
2
Rx=Rx.1+Rx.2
TEST/
RESET Setting value "0" is colored yellow.1)
11
R1.1-VALUE kΩ R2.1-VALUE kΩ
3 ④ Status display: LED for device status (green)
4 ⑤ Status display: LED for monitoring status F (red)
5
⑥
F
Status display: LED output contact status (yellow)
R1.2-VALUE kΩ R2.2-VALUE kΩ
10 6
⑦ Rotary knob for adjusting the insulation resistance (R2.2 for
7 the units position of R2)
9
ON 8 ⑧ Label
4 3 2 1
⑨ Device order number
⑩ Rotary knob for adjusting the insulation resistance (R1.2 for
12 14 L+ VS V1+ V1-
1 the units position of R1)
⑪ Rotary knob for adjusting the insulation resistance (R1.1 for
22 24 L- KE A2- the tens position of R1)
Setting value "0" is colored yellow.1)
Terminal labels
A1+ Rated control supply voltage ∼ / +
A2- Rated control supply voltage ∼ / -
Y1 Control inputs; isolation control
Y2 Y1-Y3: Remote test
Y3 Y2-Y3: Remote reset/autoreset
VS Connection terminals for the voltage reducer module
V1+
V1-
L+ Measuring signal input, connection to phase or L+
L- Measuring signal input, connection to phase, N conductor or
L-
KE Measuring signal input, control ground connection for open-
circuit monitoring
Measured signal input, grounding connection
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
22 Output relay K2 CO contact NC contact
21 Output relay K2 CO contact root
24 Output relay K2 CO contact NO contact
1)
Information on setting accuracy
• at setting value "0", a setting accuracy of >15 % applies for R
• at setting value ">1", a setting accuracy of 6 % applies for R
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Technical data (Page 190)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 181)".
9.4.2 Functions
General functionality
The 3UG4582/3UG4583 insulation monitoring relays are supplied with a rated control and
supply voltage of 24 V to 240 V AC/DC, and they monitor the insulation resistance in accordance
with IEC 61557‑8 in ungrounded IT-AC systems, IT‑AC systems with galvanically connected DC
circuits, or IT‑DC systems.
The devices can monitor control circuits (1-phase) and main circuits (3-phase). For this purpose,
the insulation resistance between power supply cords (terminal: L+ and L-) and the ground of the
system (terminal and KE) is measured. Systems with rated system voltages Un = 0 to
250 V AC (15 to 400 Hz) / Un = 0 to 300 V DC (3UG4582) or Un = 0 to 400 V AC (15 to 400 Hz) /
Un = 0 to 600 V DC (3UG4583) can be connected direct to the measuring inputs, and their
insulation resistance can be monitored.
The insulation monitoring relays have two rotary buttons (3UG4582)/four rotary buttons
(3UG4583) for adjusting the insulation resistance R and a Test/RESET button, to perform an
internal test on the device or to reset the device.
If the measured value drops below the set threshold, the output relays are set to fault status.
For systems with voltages over 400 V AC and 600 V DC, the 3UG4583 insulation monitoring
relays with 3UG4983 voltage reducer module can be used for extending the voltage range.
You will find the adjustment ranges and factory settings of the available parameters in Chapter
"Operator control (Page 177)".
You will find a description of the individual parameters in the Chapter "Parameters (Page 265)".
Measuring method
The 3UG4582/3UG4583 insulation monitoring relays use a new predictive measuring method
for high-speed measurements and fast pick-up times. The devices can be configured to the
relevant application conditions and are therefore versatile in use.
A pulsing measuring signal is fed into the system to be monitored and the insulation resistance
is calculated from this.
The received signal is different in form to the injected measuring signal. This change depends on
the insulation resistance and the system discharge capacity. The change to the insulation
resistance is predicted from this deviating form. If the predicted insulation resistance
corresponds to the insulation resistance calculated in the next measuring cycle and is lower than
the set threshold, output relay K1 responds depending on the device configuration.
This adaptive measuring principle is suitable for detecting symmetrical insulation faults.
Monitoring
The system to be monitored is connected to the measuring signal inputs L+, L-. The terminals can
be connected to any conductor (phase, +/- potential, or N conductor). The measuring signal
inputs must be connected to different conductors.
The ground potential is connected to the terminals and KE.
KE stands for control ground and is used for monitoring the fault-free ground connection of the
insulation monitoring relay.
The 3UG4582 insulation monitoring relays work according to the closed-circuit principle NC. The
3UG4583 insulation monitoring relays work in accordance with the set relay switching behavior
(closed-circuit principle NC or open-circuit principle NO).
After applying the rated control supply voltage, the insulation monitoring relay goes through an
internal test that checks the proper functioning of the operational device. The test encompasses
an internal test of the device at hardware and firmware level (on the 3UG4583, a settings check
is also carried out) , as well as system diagnostics with calculation of the system discharge
capacity of the first measured value of the insulation resistance. If there are no internal device
faults or external faults on completion of this test, the output relays change their switching state
(if closed-circuit principle is set). The time for this test can be 10 s - 15 s with purely AC systems.
The circuit is opened instantaneously after detection of a fault. In AC systems with DC
components, as is the case when rectifiers are used, up to 15 s can be needed.
Note
If the 3UG4583 insulation monitoring relay is used for monitoring the winding insulation of a
motor, the function test first results in a fault message if the closed-circuit principle is selected,
since the device is not applied to the supply voltage until a measurement is possible on the
switched-off motor. Either this fault must be hidden by downstream logic, or the open-circuit
principle must be set. The output relays would only pick up if an insulation fault or internal device
faults are detected. However, the fault "Missing supply voltage" can then no longer be detected.
If the measured value undershoots the set threshold in the case of the 3UG4582 insulation
monitoring relays, output relay K1 drops out. If the measured value overshoots the threshold
including hysteresis, output relay K1 picks up.
The principle of operation of the 3UG4583 insulation monitoring relays can be configured via
DIP switch 4:
In the functional principle 1 x 2 changeover contacts, both output relays K1 and K2 respond to
threshold R1 (warning). The settings of threshold R2 have no influence on the principle of
operation. If the measured value undershoots the set threshold, the output relays switch to the
fault status. If the measured value overshoots the set threshold including hysteresis, the output
relays revert to the original state.
In the functional principle 2 x 1 changeover contacts, output relay K1 responds to threshold R1
(shutdown) and output relay K2 responds to threshold R2 (warning). If the measured value
undershoots the set threshold R2 (warning), output relay K2 switches. If the measured value
undershoots the set threshold R1 (shutdown), output relay K1 switches. If the measured value
overshoots the set threshold R1 (shutdown) including hysteresis, output relay K1 reverts to the
original state. If the measured value overshoots the set threshold R2 (warning) including
hysteresis, output relay K2 reverts to the original state.
All operating states of the 3UG4582/3UG4583 insulation monitoring relays are displayed via
three LEDs.
supply voltage off and on again, provided the fault is not stored in retentive (non-volatile)
memory.
on)
< < < 1) Autoreset (factory setting) — 1)
1)
If there is no external connection between terminals Y2 and Y3 while retentive fault storage is set,
internal device monitoring detects a parameterization error.
You will find the adjustment ranges and factory settings of the available parameters and the
definitions of the DIP switch positions in Chapter "Operator control (Page 177)".
WV
/('
/(' )
/('
① Test (Y1-Y3)
② Reset (Y2-Y3)
③ Measured value
④ Hysteresis
⑤ Threshold
⑥ Green
⑦ Red
⑧ Yellow
tS = Time for internal device test after applying the supply voltage
WV
/('
/(' )
/('
① Test (Y1-Y3)
② Reset (Y2-Y3)
③ Measured value
④ Hysteresis
⑤ Threshold
⑥ Green
⑦ Red
⑧ Yellow
tS = Time for internal device test after applying the supply voltage
Relay switching behavior = NC(closed-circuit With fault storage, manual RESET, 1 x 2 changeover contacts, shut‐
principle) down
$$
WV
WV
/('
/(' )
/('
① Test (Y1-Y3)
② Reset (Y2-Y3)
③ Measured value
④ Hysteresis
⑤ Threshold
⑥ Green
⑦ Red
⑧ Yellow
tS = Time for internal device test after applying the supply voltage
Relay switching behavior = NO (open-circuit With fault storage, manual RESET, 1 x 2 changeover contacts, shut‐
principle) down
$$
WV
WV
/('
/(' )
/('
① Test (Y1-Y3)
② Reset (Y2-Y3)
③ Measured value
④ Hysteresis
⑤ Threshold
⑥ Green
⑦ Red
⑧ Yellow
tS = Time for internal device test after applying the supply voltage
Relay switching behavior = NC(closed-circuit With fault storage, manual RESET, 2 x 1 changeover contacts, warning
principle) and shutdown
$$
WV WV
/('
/(' )
/('
① Test (Y1-Y3)
② Reset (Y2-Y3)
③ Measured value
④ Hysteresis
⑤ Warning
⑥ Shutdown
⑦ Green
⑧ Red
⑨ Yellow
tS = Time for internal device test after applying the supply voltage
Relay switching behavior = NO (open-circuit With fault storage, manual RESET, 2 x 1 changeover contacts, warning
principle) and shutdown
$$
WV WV
/('
/(' )
/('
① Test (Y1-Y3)
② Reset (Y2-Y3)
③ Measured value
④ Hysteresis
⑤ Warning
⑥ Shutdown
⑦ Green
⑧ Red
⑨ Yellow
tS = Time for internal device test after applying the supply voltage
Parameters
The following parameters can be set on the two (3UG4582) or four (3UG4583) ten-level rotary
buttons (absolute scale) with the help of a screwdriver:
The position digits refer to the front view of the respective 3UG4582 / 3UG4583 devices in
1)
DIP switch
The DIP switches are located behind the label on the front of the 3UG4583 insulation monitoring
relays. Four settings can be parameterized with the DIP switch.
The tables below contain the setting options on the device and the explanations for the relevant
switch positions. When the device is delivered, the switch is in the position OFF.
Position 4 3 2 1
Functional principle Open-circuit detection Non-volatile (retentive) Functional principle of
fault storage output relays K1 and K2
ON ↑ 2 x 1 changeover con‐ Activated Activated Closed-circuit principle
tacts NC
OFF 1 x 2 changeover contacts Deactivated Deactivated Open-circuit principle NO
Chapter "Wiring examples (Page 182)" shows the examples for the different monitoring modes.
The parameters are defined in the Chapter "Parameters (Page 265)".
Tools required
The same screwdriver can be used to set the parameters as for wiring the insulation monitoring
relays.
9.4.4 Diagnostics
Status display
The following information indicates the operating state on the 3UG4582/3UG4583 insulation
monitoring relays:
1)
Only on the 3UG4583-1CW30.
2)
Possible setting error: The threshold for shutdown is set to a higher value than the warning threshold,
and non-volatile (retentive) fault storage is set simultaneously with autoreset.
3)
The device has tripped following an insulation fault. The fault has been stored and the insulation
resistance has reverted to a value above the set threshold including hysteresis.
4)
Dependent on the fault.
The switching behavior of the output relay is shown in Chapter "Functions (Page 167)".
$
N˖
$
$
N˖
$
9 9 96
/ / / /
$ $
/ 3:0 /
1 '& /
3( 3(
/ / 3:0 / / /
$ $
'& /
/ 3:0 / /
/ 0
/ '& / /
3( 3(
4-wire AC system
4-wire AC system
$ .( $ .(
< < < < < <
/ / / /
$ $
/ /
/ /
/ /
1 1
3( 3(
Application examples
The figure below shows monitoring for ground fault/insulation fault in the different load circuits.
/
/
/
1
3(
$ .( $ .(
< < < < < <
8* 8*
$: $:
/ / / /
$ $
0
a
① The voltage source is the secondary side of an isolating transformer that galvanically isolates the system and the
downstream circuit.
② The insulation resistance of this motor feeder is always monitored when the motor is switched off. If the motor
contactor drops out, the two NC contacts connect the measuring circuit with the motor cables.
③ The 3UG4582-.AW3. insulation monitoring relay permanently monitors the insulation resistance of the remaining
system with all connected loads.
④ Loads
Figure 9-9 Monitoring for ground fault/insulation fault with different load circuits
Note
The maximum cable length of the control cables is 50 m or 100 pF/m.
/ 3:0 /
1 '& /
3( 3(
/ 3:0 / /
/ 0
/ '& / /
3( 3(
4-wire AC system
4-wire AC system
$ < < < $ < < <
/ /
/ /
/ /
1 1
3( 3(
Application examples
The figure below shows monitoring for ground fault/insulation fault in the case of an
ungrounded 4‑wire AC system.
/
/
/
1
3(
8*
&:
/ 9 9 9
/ .( $
0
a
① Loads
Figure 9-10 Monitoring for ground fault/insulation fault in the case of an ungrounded 4-wire AC system
Note
The maximum cable length of the control cables is 50 m or 100 pF/m.
/
/
/
1
3(
8* 8*
&: &:
/ 96 9 9 / 9 9 9
/ .( $ / . $
0
a
① The voltage source is the secondary side of an isolating transformer that galvanically isolates the system and the
downstream circuit.
② The insulation resistance of this motor feeder is always monitored when the motor is switched off. If the motor
contactor drops out, the two NC contacts connect the measuring circuit with the motor cables.
③ The 3UG4583-.CW3. insulation monitoring relay permanently monitors the insulation resistance of the remaining
system with all connected loads.
④ Loads
Figure 9-11 Monitoring for ground fault/insulation fault with different load circuits
Note
The maximum cable length of the control cables is 50 m or 100 pF/m.
9.4.6 Characteristics
9
8
, $
9
8
, $
)
FRV˳
Figure 9-14 Reduction factor F in the case of inductive AC load
>$@
① Operating cycles
② 250 V, resistive load
③ Switching current
Figure 9-15 Contact service life
9
8
, $
9
8
, $
)
FRV˳
Figure 9-18 Reduction factor F in the case of inductive AC load
>$@
① Operating cycles
② 250 V, resistive load
③ Switching current
Figure 9-19 Contact service life
Application areas
The voltage monitoring relays are used, for example, in the following applications:
Function Application
• Undervoltage • Increased current on a motor with corresponding overheating
• Overvoltage • Unintended device reset
• Power system collapse on overloaded supply voltages
• Fork-lift trucks
• Heating systems
• Cranes
• Elevators
• Protection from undervoltage (especially with battery power; result: e.g.
exhaustive discharge)
• System protection against destruction caused by supply overvoltages
• Energy supply to the line
• Machine switch-on when a defined voltage is reached
• Threshold switch for analog signals from 0.1 to 10 V
Del -> Umin/Umax delay
Mem ? -> Memory?
⑥ Legend for menu
NC -> Circuit principle
⑦ Display for parameterization, actual-value indication, and diagnostics
Terminal labels
A1+ Rated control supply voltage ∼ / +
A2- Rated control supply voltage ∼ / -
M (GND) Measuring signal input -
3UG4632-1AW30
IN Measuring signal input +
12 Output relay K1 CO contact NC contact
A2- 11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
12 11 14
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 201)".
10.2.2 Functions
General functionality
Depending on the setting, the 3UG4631 / 3UG4632 voltage monitoring relays are powered with
a rated control supply voltage of 24 V AC/DC or 24 to 240 AC/DC and monitor an AC voltage or
DC voltage at terminals IN and M of the device for overshoot (U▲) or undershoot (U▼) or
in range monitoring (U▲ and U▼).
The 3UG4631 / 32 voltage monitoring relays have a display and are parameterized with three
keys.
You will find the adjustment ranges and factory settings of the available parameters in Chapter
"Operation (Page 198)".
You can find a description of the individual parameters in Chapter "Parameters (Page 265)".
Monitoring
The output relay K1 responds in accordance with the set relay switching behavior (closed-circuit
principle NC or open-circuit principle NO). The set tripping delay time starts if the monitored
voltage overshoots or undershoots the corresponding set threshold value. After expiry of the
tripping delay time, the output relay K1 changes the switching state. On the display, the
currently displayed measuring value and the symbol for undershoot or overshoot flash.
An output change-over contact is available as a signaling contact.
If the rated control supply voltage is switched on and no monitoring voltage is yet present, the
display indicates 0.0 V and shows a symbol for voltage overshoot monitoring, voltage
undershoot monitoring, or range monitoring.
You will find the switching states of the output relay below in the section entitled "Function
diagrams" and in Chapter "Diagnostics (Page 199)."
U>
> ! U ! U
U = off
U U
Hyst Hyst
U=0 U=0
11/14 11/14
11/12 11/12
U Del U Del
A1-A2 A1-A2
U> = off
> U U
U
Hyst Hyst
U U
U=0 U=0
11/14 11/14
11/12 11/12
U Del U Del
U >
! U U ! U U
U U Hyst
Hyst
Hyst
U Hyst U
U=0 U=0
11/14 11/14
11/12 11/12
U Del U Del
U Del U Del
onDel -> Power on delay
Del -> Umin/Umax delay
⑥ Legend for menu
Mem ? -> Memory?
NC -> Circuit principle
⑦ Display for parameterization, actual-value indication, and diagnostics
Terminal labels
A1+ Rated control supply voltage ∼ / +
A2- Rated control supply voltage ∼ / -
12 Output relay K1 CO contact NC contact
3UG4633-1AL30
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
A2-
12 11 14
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 201)".
10.3.2 Functions
General functionality
Depending on the setting, the 3UG4633 voltage monitoring relays are self-powered
(measuring voltage = rated control supply voltage) and monitor an AC voltage or DC voltage at
terminals A1 and A2 of the device for overshoot (U▲) or undershoot (U▼) or in range
monitoring (U▲ and U▼).
The voltage monitoring relays are powered with a rated control supply voltage of 17 to 275 V AC/
DC through terminals A1/A2.
The 3UG4633 voltage monitoring relays have a display and are parameterized with three keys.
You will find the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 198)."
You will find a description of the individual parameters in Chapter "Parameters (Page 265)."
Monitoring
Output relay K1 responds in accordance with the set relay switching behavior (closed-circuit
principle NC or open-circuit principle NO).
An output change-over contact is available as a signaling contact.
If the voltage is switched on, the display will show the current measured value and a symbol for
monitoring for voltage overshoot, voltage undershoot, or range monitoring.
Startup delay
To be able to start a drive, the output relay switches to the correct state during the ON-delay time
(onDel) depending on the selected open-circuit principle or closed-circuit principle, even if the
measured value is still under the set value.
Tripping delay
If the measured value overshoots or undershoots the set threshold after expiry of the ON-delay
time (onDel), the set tripping delay time (Del) and the relay symbol will flash. After expiry of this
time, the output relays change the switching state. On the display, the current measuring value
and the symbol for undershoot or overshoot flash.
You will find the switching states of the output relay below in the section entitled "Function
diagrams" and in Chapter "Diagnostics (Page 199)."
A1 - A2 =U A1 - A2 =U
U>
> ! U ! U
U = off
U Hyst U Hyst
U=0 U=0
11/14 11/14
11/12 11/12
onDel
onDel
U Del U Del
A1 - A2 =U A1 - A2 =U
U> = off
U >
U U
Hyst Hyst
U U
U=0 U=0
11/14 11/14
11/12 11/12
onDel onDel
U Del U Del
U> A1 - A2 =U A1 - A2 =U
U >
! U U ! U U
U Hyst U Hyst
Hyst Hyst
U U
U=0
11/14 11/14
11/12 11/12
onDel onDel
U Del U Del
U Del U Del
U Del = U Del U Del = U Del
10.4 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3UG463. voltage monitoring
relays:
Table 10-2 Parmeter information, 3UG463. voltage monitoring relays with digital setting
Note
The monitoring mode "Overshoot" or "Undershoot" is defined with the setting OFF at the
threshold for undershoot or overshoot.
Note
Deactivating monitoring
If the upper and lower threshold values are deactivated (OFF), monitoring will cease for:
• Voltage overshoot
• Voltage undershoot
The up-to-date measured value is displayed permanently.
10.5 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and faults are indicated on the display as a diagnostics message with
flashing symbols:
You will find more information about the switching behavior of the output relay in Chapter
"Functions (Page 192)" (3UG4631 / 3UG4632) and "Functions (Page 195)" (3UG4633).
10.5.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 265)").
The following settings can be selected:
• Automatic reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt with.
• Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the error
has not been removed, a new error message appears immediately. Alternatively, the devices
can be reset by switching the rated control supply voltage on and off.
8!
0
$ $
8!
Note
On the 24 V AC/DC versions of the 3UG4631‑.AA30 and 3UG4632‑.AA30, terminals A2 and M
(GND) are electrically connected in the device!
On the 24 to 240 V AC/DC versions of the 3UG4631‑.AW30 and 3UG4632‑.AW30, terminals A2
and M (GND) are electrically separated!
3UG4631‑.AA30 / 3UG4632‑.AA30
AC/DC U Last
A1(+) IN(+) 11
<U>
12 14
A2(–) M(–)
3UG4631‑.AW30 / 3UG4632‑.AW30
AC/DC U Last
A1(+) IN(+) 11
<U> 12 14
A2(–) M(–)
3UG4633
$ $
8!
Application areas
The cos phi and active current monitoring relays are used, for example, in the following
application areas:
Table 11-1 Application areas of the cos phi and active current monitoring relays
Function Application
• No-load monitoring and load shedding • Fans (in the case of a broken fan belt, for exam‐
• Underload monitoring in the low-end perform‐ ple)
ance range • Pumps (in the case of an idling pump, for ex‐
• Monitoring for overload ample)
• Simple cos phi monitoring in power systems for • Filter system (a contaminated filter system, for
controlling compensation systems example)
• Cable break between the control cabinet and • Reactive power compensation
the motor • Sawing system
• Conveyor belt
• Surface grinding machine
• Breaking mill
• Milling machine
• Car wash
• Lifting platform
• Screw conveyor
• Crane
• Turning machine
• Infrared heating system
-> cos = PF
Ires -> Active current
⑥ Legend for menu
onDel -> Current on delay
Mem ? -> Memory?
NC -> Circuit principle
⑦ Display for parameterization, actual-value indication, and diagnostics
Terminal labels
Lx Power supply (measuring signal) ∼ / +
Ly/N Power supply (measuring signal) ∼ / +
IN Measuring signal input (current)
3UG4641-.....
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
12 11 14 14 Output relay K1 CO contact NO contact
22 Output relay K2 CO contact NC contact
22 21 24 21 Output relay K2 CO contact root
24 Output relay K2 CO contact NO contact
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 213)".
11.3 Functions
General functionality
The 3UG4641 cos phi and active current monitoring relays are self-powered (measuring
voltage = rated control supply voltage) and monitor the cos phi value (PF: power factor) and the
resulting active current Ires (I resistive), depending on the setting, for overshoot (φ▲ / Ires▲),
undershoot (φ▼ / Ires▼) or in range monitoring (φ▲ and φ▼ / Ires▲ and Ires▼). The load to be
monitored is connected upstream of the terminal IN. The load current flows through
terminals IN and Ly / N. The devices are powered with a voltage of 90 to 690 V through the
terminals Lx and Ly / N .
The 3UG4641 cos phi and active current monitoring relays have a display and are parameterized
with three keys.
You will find the adjustment ranges and factory settings of the available parameters in Chapter
"Operation (Page 211)".
You can find a description of the individual parameters in Chapter "Parameters (Page 265)".
Note
The specified voltages represent the absolute thresholds.
Monitoring
If the motor is switched on and the current value overshoots the measuring range limit 0.2 A, the
set ON-delay time begins (onDel). During this time, undershooting or overshooting of the set
threshold values will not result in a relay response of the CO contact.
If monitoring for active current undershoot is switched off (Ires▼ = off), and if the load current
undershoots the lower measuring range threshold (0.2 A), the change-over contacts remain
unchanged. If a threshold is set for monitoring for active current undershoot, undershoot of the
measuring range threshold (0.2 A) will result in a relay response of the change-over contacts.
Note
In the case of active currents Ires > 10 A, commercially available current transformers, e.g. 4NC,
can be used as accessories. You will find more information in Catalog LV10 (https://
support.industry.siemens.com/cs/de/de/view/109482234/en).
Startup delay
To be able to start a drive, the output relay switches to the correct state during the ON-delay time
(onDel) depending on the selected open-circuit principle or closed-circuit principle, even if the
measured value is still under the set value.
Tripping delay
If the measured value overshoots or undershoots the set threshold after expiry of the ON-delay
time (onDel), the set tripping delay time (Del) and the relay symbol will flash. After expiry of this
time, the output relays change the switching state. On the display, the current measuring value
and the symbol for undershoot or overshoot flash.
You will find the switching states of the output relays below in section "Function diagrams" and
in Chapter "Diagnostics (Page 212)."
21/24 21/24
21/22 21/22
Ir > = off
Lx-Ly/N Lx-Ly/N
21/24 21/24
21/22 21/22
Ir > = off
Ir >
J< I U J < IU
,U Hyst
,U Hyst
J=0 J=0
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
Ir>
Ir >
J> IU J< IU J >IU J <IU
,U Hyst
,U Hyst
Hyst Hyst
,U ,U
J=0 J=0
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
φ > = off
φ >
PF < ϕ PF < ϕ
Hyst, 0.10 ϕ Hyst, 0.10
ϕ
PF = 0 cos ϕ = 0 PF = 0 cos ϕ = 0
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
φ>
φ >
PF > ϕ PF < ϕ PF > ϕ PF < ϕ
ϕ ϕ
Hyst, 0.10 Hyst, 0.10
PF = 0 cos ϕ = 0 PF = 0 cos ϕ = 0
11/14 11/14
11/12 11/12
21/24 21/24
21/22 21/22
11.4 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3UG4641 cos phi and active
current monitoring relays:
Table 11-2 Parameter information, 3UG4641 cos phi and active current monitoring relay with digital setting
Note
The monitoring mode "Overshoot" or "Undershoot" is defined with the setting OFF at the
threshold for undershoot or overshoot.
11.5 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and faults are indicated on the display as a diagnostics message with
flashing symbols:
You will find more information about the switching behavior of the output relay in Chapter
"Functions (Page 206)."
11.5.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 265)").
The following settings can be selected:
• Automatic reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt with.
• Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the error
has not been removed, a new error message appears immediately. Alternatively, the devices
can be reset by switching the rated control supply voltage on and off.
/[ /\1 ,1
FRVSKL!
M
1~
Lx IN
3UG4641 12
11 ϕ |/ Ir |
14
22
| |
21 ϕ / Ir
24
Ly/N
N or L
Figure 11-1 Cos phi and active current monitoring for single-phase motors
22 | | 22
ϕ / Ir | |
21 21 ϕ / Ir
24 24
Ly/N Ly/N
Cos phi and active current monitoring for three- Cos phi and active current monitoring for three-
phase motors phase motors (with neutral conductor)
Cos phi and active current monitoring for three-phase motors with transformers for currents
n = 1, 2, 3 3~,I > 10 A n = 1,2,3 3~,I > 10 A
Ln Ln
Ln M Ln M
Ln 3~ Ln 3~
N
Lx IN Lx IN
3UG4641 12 12
3UG4641
11 ϕ |/ Ir | 11 ϕ |/ Ir |
14 14
22 | | 22
ϕ / Ir | |
21 21 ϕ / Ir
24 24
Ly/N Ly/N
Cos phi and active current monitoring for three- Cos phi and active current monitoring for three-
phase motors with transformers for currents phase motors with transformer for currents (with
neutral conductor)
Application areas
The speed monitoring relays are used, for example, in the following applications:
Function Application
• Monitoring for overload/underload • Conveyor belt (monitoring transported goods
for completeness, for example)
• Milling machine
• Turning machine
• Slippage or tear of a drive belt
The speed monitoring relays can also be used for all functions where a continuous pulse signal
is to be monitored (e.g. belt travel monitoring, completeness check, pass monitoring, or cycle
time monitoring).
SIRIUS
④ Device article number
⑤ Label
⑥ Legend for menu
⑦ Display for parameterization, actual-value indication, and diagnostics
rpm -> Revolutions/min
Scale -> Pulses/revolution
Terminal labels
onDel -> Power on delay
Mem ? -> Memory?
NC -> Circuit principle A1+ Rated control supply voltage ∼ / +
A2- Rated control supply voltage ∼ / -
24V Supply voltage for pulse input IN1 (24 V / max. 50 mA)
IN1 Pulse input for pnp‑switching three-wire sensor (for 0 V DC/ +24 V pulses)
0V Supply voltage for pulse input IN1 (0 V / max. 50 mA)
3UG4651-.....
EN Enable
RES Reset
8V2 IN2 A2-
IN2 Pulse input for two-wire NAMUR sensor or mechanical contact
8V2 Supply voltage for pulse input IN2
12 11 14
12 Output relay K1 CO contact NC contact
11 Output relay K1 CO contact root
14 Output relay K1 CO contact NO contact
You can find additional information on the connection terminals and the permissible conductor
cross-sections in the Chapter "Connection methods (Page 18)".
You can find information on connecting in the Chapter "Circuit diagrams (Page 224)".
12.3 Functions
General functionality
Depending on the setting, the speed monitoring relays monitor a speed in revolutions per
minute (rpm) for overshoot (rpm▲), undershoot (rpm▼) or in range monitoring (rpm▲ and
rpm▼). Depending on their design, the devices are powered with a rated control supply voltage
of 24 V AC/DC or 24 to 240 V AC/DC supply voltage through terminals A1/A2.
The 3UG4651 speed monitoring relays have a display and are parameterized with three keys.
You will find the adjustment ranges and factory settings of the available parameters in Chapter
"Operation (Page 222)".
You can find a description of the individual parameters in Chapter "Parameters (Page 265)".
Speed monitoring functions according to the principle of period duration measurement.
In the speed monitoring relay, the time interval between two consecutive rising edges of the
pulse encoder is measured and compared with the minimum and/or maximum permissible
period duration calculated from the set threshold values for the speed. Period duration
measurement detects a speed deviation after only two pulses.
By using up to ten pulse encoders distributed simultaneously across the range, the period
duration, and thus the response time, can be reduced. By taking account of the number of
sensors in the speed monitoring relay, the speed continues to be displayed in revolutions per
minute.
The number of pulses supplied by the pulse encoder can be defined with the help of entering a
scaling value (Scale). This allows the revolutions per minute to be read direct on the display.
The speed monitoring relays have two different pulse inputs. Only one of these may be used! A
pnp‑switching three-wire sensor for 0 V / +24 V DC pulses can be connected at terminal IN1. It
is supplied from the output relay via terminals 0V and 24V / with up to 50 mA. Use of a
mechanical pulse contact with an external DC supply of 4.5 to 30 V is also permissible at terminal
IN1.
Note
To detect the edges reliably, the pulses and pauses between pulses of the pulse encoders used
must be applied for at least 5 ms. A pause is detected at voltage level < 1 V. A pulse requires a
minimum value of 4.5 V.
Alternatively, a two-wire NAMUR sensor supplied from terminal 8V2, or a mechanical contact,
can be connected at terminal IN2.
Monitoring
Startup delay
To be able to start a drive, the output relay switches to the correct state during the ON-delay time
(onDel) depending on the selected open-circuit principle or closed-circuit principle, even if the
measured value is still under the set value.
The ON-delay time is started either by switching on the rated control supply voltage or, if the
rated control supply voltage is present, by actuating the relevant contact (e.g. auxiliary contact
of a contactor).
Tripping delay
If the measured value overshoots or undershoots the set threshold after expiry of the ON-delay
time (onDel), the set tripping delay time (Del) and the relay symbol will flash. After expiry of this
time, the output relays change the switching state. On the display, the current measuring value
and the symbol for undershoot or overshoot flash.
Operating mode with/without enable contact
In the operating mode without enable contact (terminal EN = Enable not connected), the output
relay responds when the rated control supply voltage is switched in accordance with the set
closed-circuit principle NC or open-circuit principle NO (relay control is inverted to the closed-
circuit principle NC), and the ON-delay time (onDel) is started, provided the lower threshold is
not at OFF. If the speed reaches the lower threshold value plus the set hysteresis during this time,
the ON-delay time is stopped and normal monitoring begins. If this value has not yet been
reached after expiry of the ON-delay time, the output relay switches to the fault state depending
on the selected relay switching behavior.
For the functioning of the operating mode with enable contact (terminal EN = Enable is
connected to terminal 24V with an isolated NC contact), a rated control supply voltage must be
present at terminals A1 and A2 on the monitoring relay. Only when this NC contact is actuated
will the ON-delay time (onDel) and the drive (with a second contact, for example) be started.
You will find the switching states of the output relay below in the section entitled "Function
diagrams" and in Chapter "Diagnostics (Page 223)."
Display Memory = no
Relay switching behavior = NC (closed-circuit principle)
Without Enable input With Enable input
rpm > A1-A2 A1-A2
rpm > = off
! EN
> RPM
rpm
Hyst Hyst !
RPM=0 > RPM
rpm
Hyst Hyst
RPM=0
11/14
11/12
11/14
Del Del
11/12
Del Del
rpm >
A1-A2 A1-A2
rpm >
! !
EN
> RPM < RPM
rpm ! !
Hyst
> RPM < RPM
Hyst
rpm Hyst
rpm
RPM=0 Hyst
rpm
11/14 RPM=0
11/12
11/14
OnDel Del Del 11/12
Note
The relay control for the open-circuit principle NO is inverted to the represented function
diagrams in the closed-circuit principle NC after application of the rated control supply
voltage US.
12.4 Operation
Parameters
Parameterization of the devices is possible locally using the display and the three keys.
Parameter information
The table below shows the settable parameter information of the 3UG4651 speed monitoring
relays:
Table 12-2 Parmeter information, 3UG4651 speed monitoring relays with digital setting
Note
The monitoring mode "Overshoot" or "Undershoot" is defined with the setting OFF at the
threshold for undershoot or overshoot.
12.5 Diagnostics
Display information
The display is divided into three different areas.
3 2
Note
Indications in the event of a fault
The symbols on the display flash to indicate an error.
The following statuses and faults are indicated on the display as a diagnostics message with
flashing symbols:
You will find more information about the switching behavior of the output relay in Chapter
"Functions (Page 218)."
12.5.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 265)").
The following settings can be selected:
• Automatic reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt with.
• Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the error
has not been removed, a new error message appears immediately. Alternatively, the devices
can be reset by switching the rated control supply voltage on and off.
12 14
AC/DC NAMUR
– +
3UG4651‑.AA30 24 V AC/DC
3UG4651‑.AW30 24 to 240 V AC/DC
Note
On the 24 V AC/DC versions of the 3UG4651‑.AA30, terminals A1 / A2 and 0V / 24V are
electrically connected in the device!
On the 24 to 240 V AC / DC versions of the 3UG4651‑.AW30, terminals A1 / A2 and 0V / 24V are
electrically separated!
AC/0V
AC/0V
Description
A sealable cover for use with all sizes (3RR2940) is available for the 3RR2 current monitoring
relays with digital and analog setting.
The sealable cover is used to protect the rotary buttons and the slide switch on the current
monitoring relay with analog setting or the buttons on the current monitoring relay with digital
setting against unauthorized or unintentional tampering.
Siemens also offers a sealable membrane (3TK2820-0AA00) for securing the current monitoring
relays with analog setting. The sealable membrane is fixed to the front of the device and secures
the rotary buttons and sliding switches against unintentional tampering.
Mounting
The diagram below shows an example mounting scenario based on mounting the sealable cover
on the 3RR21 current monitoring relay with analog setting, size S0. The mounting sequence for
the sealable cover for size S00 is exactly the same as that for size S0.
Description
For a stand-alone assembly or if an overload relay is being used at the same time, adapters for
stand-alone installation are available for separate DIN rail mounting or screw mounting.
The accessories are exactly the same as the accessories for the 3RU21 thermal overload relay and
the 3RB3 solid-state overload relay.
Mounting
The terminal supports can be snapped onto 35 mm DIN rails according to DIN EN 50022. They
can also be screw-mounted.
The figure below shows how the terminal support for stand-alone assembly is mounted and
disassembled, based on the example of an analog setting current monitoring relay.
① Guide the current monitoring relay into the terminal support from below.
② Tighten the screws on the terminal support with a
Pozidriv size 2 (S00) or Pozidriv size 3 (S0)
screwdriver (tightening torque 0.8 to 1.2 Nm).
Check that the cable is clamped tight.
Figure 13-2 Mounting the terminal support (screw-type connection technology in the main circuit)
D
① Insert the contacts (a) into the central opening of the main terminals on the terminal support,
with the contacts flush to the right. Make sure that the guide tabs are inserted into the designated
slots on the terminal support.
Figure 13-3 Mounting the terminal support (spring-loaded connection technology in the main circuit)
Disassembly
① Release the current monitoring relay by pushing down the clip on the underside of the terminal
support.
② Position the screwdriver on the terminal support as shown in the figure. Carefully dislodge the
current monitoring relay from the contactor.
③ Pull the current monitoring relay toward you and away from the terminal support.
Figure 13-5 Removing the terminal support (spring-loaded connection technology in the main circuit)
Description
There is a uniform sealable cover for the monitoring relays with an overall width of 22.5 mm.
The sealable cover can be used to secure the actuators (rotary buttons, sliding switches, and
keys) of the monitoring relays against unauthorized or unintentional manipulation.
Siemens also offers a sealable membrane (3TK2820-0AA00) for securing the monitoring relays
with analog setting. The sealable membrane is affixed to the front of the device and secures
rotary buttons and sliding switches against unintentional manipulation.
Note
The sealable membrane does not protect keys against unauthorized or unintentional
manipulation.
Mounting
The figure below shows how to attach the 3RP1902 sealable cover to the monitoring relay.
53
Description
The 3RP1903 push-in lugs are available for the monitoring relays.
With the help of the push-in lugs, the monitoring relays can be secured with screws on a level
surface (e.g. a wall). Two push-in lugs are required per device.
Mounting
The figure below shows how to attach the 3RP1903 push-in lugs to the monitoring relay.
53
① Insert the push-in lugs at the top and bottom on the monitoring relay and tighten the push-in lugs
with a screwdriver.
Figure 13-7 Attaching the push-in lugs on the monitoring relay
Note
Probes for level monitoring
Probes for level monitoring are available from various suppliers.
We recommend probes from Jacob GmbH (https://www.jacob-gmbh.de/en/).
There you can also obtain the previous 3UG3 wire electrodes and bow electrodes.
Description
The 3UL22 summation current transformers acquire residual current in machines and plants.
Together with the 3UG4624 residual current monitoring relay or the motor management and
control unit SIMOCODE 3UF, residual current monitoring and ground-fault monitoring are
possible. The 3UL22 summation current transformer is available in three sizes with a bushing
opening of ∅ 40 mm, ∅ 65 mm and ∅ 120 mm.
a1
a2 a3
b5
b1
b2
b4
b3
a4
a5
A2 Z3
c1
c2
c3
Z1 Z2
a6
Type a1 a2 a3 a4 a5 a6 b1 b2 b3 b4 b5 c1 c2 c3
3UL2201 100 75 10 15 for 80 85 72,5 42,5 7,5 40 65 50 40
M4
3UL2202 125 95 10 15 for 100 110 97,5 55 7,5 65 70 60 45
M4
3UL2203 200 165 20 20 for 170 200 100 100 10 120 85 70 55
M4
Description
3UL23 residual current transformers detect fault currents in machines and systems. Together
with the residual current monitoring relay or the 3UF7510 SIMOCODE motor management and
control device ground-fault module, residual current monitoring and ground-fault monitoring
are possible. The 3UL23 residual current transformer is available in six sizes with bushing
opening diameters of ∅ 35 mm, ∅ 55 mm, ∅ 80 mm, ∅ 110 mm, ∅ 140 mm, and ∅ 210 mm.
Note
3UG4.25 residual current monitoring relays are only suitable for use with 3UL23 residual current
transformers.
① Suitable FI type
② Circuit
③ Load current
④ Fault current
Figure 13-9 Possible fault current forms and suitable residual current devices
Note
Please ensure strict adherence to the installation specifications for live cables.
WARNING
Open-circuit voltage may result in death, serious injury or material damage
The current transformer output is a constant current power supply. In accordance with U = R * I,
the output voltage increases with an increasing resistance. If the connecting terminals of the
current transformer are open, the output voltage may become high enough for you to put your
life at risk or permanently damage the current transformer.
Avoid operating the unit when open. Operating a network for monitoring safely and without
faults requires that the monitoring relay and the 3UL23 residual current transformer have been
installed completely. It is absolutely necessary to short-circuit previously installed
3UL23 residual current transformers when the units are not connected to a monitoring relay.
Order number Bushing opening Max. conductor cross- AWG [kcmil] Rated current per
Diameter [mm] section phase [A]
3P copper cable + N
[mm2]
3UL2302-1A 35 25 4 85
3UL2303-1A 55 50 1/0 150
3UL2304-1A 80 150 300 225
3UL2305-1A 110 240 500 400
3UL2306-1A 140 2 x 185 2 x 350/400 500
3UL2307-1A 210 2 x 240 2 x 500 630
conductors must not be routed through the transformer or need to be routed through the
transformer in both directions.
/ /
3( / / 3( / /
1 1
1
/ /
/
Route power cables around the residual current transformer in a straight line and ensure the area
corresponds at minimum to the internal transformer diameter.
The internal transformer diameter must be at minimum twice the size of the power cable bundle
diameter.
E
1 1
/ / / /
/ /
D
∅a≥2x∅b
Transformer connection
Transformer connecting cables must be twisted and not routed in parallel to live cables to protect
from emitted interference. Keep the length of the connecting cables to a minimum. The
resistance at the transformer connecting cable must not exceed 5 Ω to ensure correct fault
current monitoring. This is ensured by the following limits given here as examples.
Note
We recommend using twisted cables.
Note
Use shielded, twisted, and grounded cables for transformer connecting cables with a length of
more than 10 m.
Potential for optimization in the event of extremely high currents, false tripping due to high
starting currents or in environments with high EMC interference
1. Extend the ON-delay time to fade out fault currents measured during motor startup.
2. Extend the tripping delay time to prevent false tripping due to EMC interference.
3. Select a residual current transformer with a larger internal diameter. The reduced magnetic
field strength that passes through the transformer due to the extended distance between
power cables and transformer reduces the measuring accuracy but also the susceptibility to
interference.
b) A solid shield sleeve, e.g. turned from a normal, low-carbon tool steel must be precisely in
contact with the internal ring of the residual current transformer. The wall thickness of the
sleeve must be 1 mm at minimum, the length of the sleeve (L) must correspond to the
internal diameter of the transformer used.
/
,*
; ;
1
,*
,
: ,* :
, ,
,
; ;
,*
Mixing up conductors
In a network with several loads there is the risk that active conductors of loads that are to be
separately monitored for fault currents can get mixed up. This fault leads to false tripping as the
inflowing and outflowing currents are not always exactly the same strength, even if the loads are
identical.
/
,*
1
,*
,*
: ,* :
,*
,*
,*
/
/
/
,*
,*
,*,*
,*
:
,*
1
,* ,*
1 / / /
6
6
13.2.5.6 Installing
①/ Insert the fixing lugs into the designated openings in the unit until they reach the stop.
②
③ Place the device against the wall surface prepared for establishing a screw connection.
④ Insert the head screws through the
corresponding elongated holes in the fixing lugs.
⑤ Screw the device onto the level surface so that it is secure.
70
5
ෘ3
75.5
6.2
50
64
92
5
ෘ5
98
38
6.2
50
64
124.5
0
ෘ8
130
60
6.2
50
64
163
10
ෘ1
169
84.5
6.2
50
64
201
4 0
ෘ1
207.5
110
6.2
50
64
300
1 0
ෘ2
286
6.2
161
62
46
Description
A sealable cover compatible is available for the 3UG458. insulation monitoring relays.
The sealable cover can be used to secure the actuators (rotary buttons and sliding switches) of
the monitoring relays against unauthorized or unintentional manipulation.
Siemens also offers a sealable membrane (3TK2820-0AA00) with a width of 22.5 mm for
securing the monitoring relays. The sealable membrane is affixed to the front of the device and
secures rotary buttons and sliding switches against unintentional operation.
Mounting
The figure below shows how to attach the 3UG4983‑0C sealable cover to the
3UG4583 insulation monitoring relay.
13.3.2 3UG4983 voltage reducer module for the 3UG4583-1CW30 monitoring relay
Description
The 3UG4983‑1A passive voltage reducer module is used for extending the measuring range of
the 3UG4583 insulation monitoring relays. The voltage reducer module enables monitoring of
the insulation resistance in systems with rated line voltages of up to 690 V AC (15 to 400 Hz) and
1000 V DC in accordance with IEC 61557‑8. The device does not require any rated control supply
voltage for operation, and it is connected between the 3UG4583 insulation monitoring relay
and the system to be monitored.
Note
If the continuously present voltage is greater than 600 V, a minimum gap of 10 mm must be
maintained between the neighboring devices.
9 9(
8*$
④ Label
96 96 Terminal labels
PDLQVFRQQHFWLRQ
9/ / /
VL+ Measuring signal input, connection to the system
9 9
9/ / / VL- Measuring signal input, connection to the system
9 9
VS Connection to 3UG4583 terminal VS
8* 8*
VE Connection to 3UG4583 terminal
V Measuring signal input, ground connection
L+ Connection to 3UG4583 terminal L+
/ 9 / 9
L- Connection to 3UG4583 terminal L-
V1+ Connection to 3UG4583 terminal V1+
96 9( 9 V1- Connection to 3UG4583 terminal V1-
①/ Position the device on the top edge of the DIN rail and press it down until it snaps onto the bottom
② edge of the DIN rail.
Figure 13-20 Installing the 3UG4983 voltage reducer module (mounting onto standard rail)
①/ To remove, apply the screwdriver to the device and push it up with a twisting motion against the
② tension of the fixing spring.
③ Swing the device upwards to remove it.
Figure 13-21 Removing the 3UG4983 voltage reducer module (mounting onto DIN rail)
. / / 96 9(
N˖
Wiring examples for the 3UG4583 insulation monitoring relay with connected 3UG4983 upstream
module
Measuring inputs L+ and L- can be connected to any conductor. Measuring inputs L+ and L- must
always be connected to different conductors.
The rated system voltage is Un ≤ 690 V AC (15 to 400 Hz) or Un ≤ 1000 V DC.
/ 3:0 /
1 '& /
3( 3(
/ 3:0 / /
/ 0
/ '& / /
3( 3(
4-wire AC system
4-wire AC system
9/ 9/ $ < < <
/
/
/
1
3(
Application example
The figure below shows how to connect the 3UG4983 upstream module to the 3UG4583
insulation monitoring relay.
/
/
/
1
3(
8*$ 8*&:
Note
The maximum cable length between the 3UG4583 insulation monitoring relay and the
3UG4983 upstream module is 0.4 m.
Note
The maximum cable length of the measuring circuit connections is 50 m or 100 pF/m.
Description
The 3UG4983‑1AA01 passive voltage reducer module is used for extending the measuring
range of the 3UG4583 insulation monitoring relays. The voltage reducer module enables
monitoring of the insulation resistance in systems with rated line voltages of up to 690 V
AC (15 to 400 Hz) and 1000 V DC in accordance with IEC 61557‑8. The device does not require
any rated control supply voltage for operation, and it is connected between the 3UG4583
insulation monitoring relay and the system to be monitored.
Note
If the continuously present voltage is greater than 600 V, a minimum gap of 10 mm must be
maintained between the neighboring devices.
VS VE V
Description
The 3UG4983‑2AA01 passive voltage reducer module is used for extending the measuring
range of the 3UG4583 insulation monitoring relays. The voltage reducer module enables
monitoring of the insulation resistance in systems with rated line voltages of up to 690 V
AC (15 to 400 Hz) and 1000 V DC in accordance with IEC 61557‑8. The device does not require
any rated control supply voltage for operation, and it is connected between the 3UG4583
insulation monitoring relay and the system to be monitored.
Note
If the continuously present voltage is greater than 600 V, a minimum gap of 10 mm must be
maintained between the neighboring devices.
1
① Terminal block:
Supports spring-loaded connection technology.
② Circuit diagram
③ Device article number
④ Label
Terminal labels
MAINS CONNECTION
L+ V1+ L- V1-
V1+ Connection to 3UG4583 terminal V1+
1
V1- Connection to 3UG4583 terminal V1-
VS VE V
FOLF
① Position the device on the top edge of the DIN rail and press it down until it snaps onto the bottom
② edge of the DIN rail.
① For disassembly, press the device down and remove the device with a swiveling motion to the
② front.
③
. / / 96 9(
N˖
/ 3:0 /
1 '& /
3( 3(
/ 3:0 / /
/ 0
/ '& / /
3( 3(
4-wire AC system
4-wire AC system
9/ 9/ $ < < <
/
/
/
1
3(
Application example
The figure below shows the connection of the 3UG4983-.AA01 voltage reducer module to
the 3UG4583-.CW31 insulation monitoring relay
/
/
/
1
3(
8*$$ 8*&:
Figure 13-25 Connection example: Voltage reducer module - insulation monitoring relay
Note
The maximum cable length between the 3UG4583-.CW31 insulation monitoring relay and
the 3UG4983-.AA01 voltage reducer module is 0.4 m.
Note
The maximum cable length of the measuring circuit connections is 50 m or 100 pF/m.
Operating instructions
Manuals
Title Reference
Functional safety - Use of SIRIUS 3UG4 and 3RR2 monitoring relays with Internet (http://
integrated sensors support.automation.siemens
.com/WW/view/en/
39863898)
Note
Deviation from the definition according to IEC/NEMA
The definition given above for voltage asymmetry deviates from the definition according to IEC/
NEMA. It usually results in a greater value for voltage asymmetry than that arrived at from the
definition according to IEC/NEMA, so that a higher level of measuring accuracy is achieved.
ON-delay time
The setting of the "ON-delay time" parameter prevents limit violations such as undershoots
(typical of inductive loads) while the system engages from generating a switching response.
The ON-delay time starts in the following cases, depending on the parameter settings:
• At restart
If a measurable signal is again detected after the lower measuring range limit has been
undershot.
• At Power‑ON
Re-connection of the supply voltage (Power‑ON) of the device after switching off the current
flow (zero current).
• At manual reset
A fault is acknowledged by a manual reset. Following this, the device behaves in the same
way as when the supply voltage is switched on again.
Note
After exiting the menu level SET, the ON-delay time starts again.
The measured value can be parameterized as "Threshold for overshoot" or as "Warning threshold
for overshoot" (only on devices for IO-Link).
The setting for the "Warning threshold for overshoot" parameter defines the switching threshold
of the relevant output relay prior to tripping due to a measured value overshoot.
If the set "Threshold for overshoot" parameter is overshot, the output relay will change its
switching state after expiry of the set delay time and an IO-Link message may be sent. If the
measured value has reached the relevant set hysteresis value, the output relay ("Reset response"
parameter set to autoreset) will immediately revert to its original state and a new IO-Link
message may be sent.
Further response depends on the set reset response (see "Reset response" parameter).
You can find information on the switching behavior of the output relays in the "Functionality"
chapters of the relevant monitoring relays.
Possible indications on the display:
• Current overshoot: I▲ (threshold), I!▲ (warning threshold)
• Voltage overshoot: U▲ (threshold), possibly U!▲ (warning threshold)
• Speed overshoot: rpm▲ (threshold), possibly rpm!▲ (warning threshold)
• Power factor overshoot: φ▲ (threshold), possibly φ!▲ (warning threshold)
• Active current overshoot: Ir▲ (threshold), possibly Ir!▲ (warning threshold)
• Fault current overshoot: I▲(threshold), possibly I! (warning threshold)
Reset response
The setting of the "Reset response" parameter controls how the device behaves after tripping in
the event of an error, and the subsequent reversion of the measured values to the normal range
once the cause of the error has been dealt with.
The outputs are reset dependent on the setting of the "Reset response" parameter.
The following settings can be selected:
• Automatic reset
If the device is set to automatic reset, the switching contact will respond once the normal
range plus the hysteresis threshold have been reached. The device is reset automatically as
soon as a previously occurring error has been dealt with. The overshoot or undershoot which
triggered the response is not saved.
• Manual RESET
If manual RESET is selected, the switching contact remains in the current switching state
even if the measured value returns to a permissible value.
Hysteresis
Hysteresis is the continuation of an effect within the hysteresis range after its cause has been
removed; its purpose is to prevent repeated response in the threshold value range.
&RUUHFWUDQJH
1RUPDOUDQJH
+\VWHUHVLVWKUHVKROG
IRUWKH
7KUHVKROG WKUHVKROGIRU
IRU RYHUVKRRW
+\VW
RYHUVKRRW
+\VWHUHVLVWKUHVKROG
7KUHVKROG +\VW IRUWKH
IRU WKUHVKROGIRU
XQGHUVKRRW XQGHUVKRRW
0HDVXUHG
YDOXH
If, after the upper threshold value has been overshot to such an extent that switching was
necessary, the measured value returns to the normal range, and switching over to the correct
range will not take place until a measured value which undershoots the hysteresis threshold has
been reached. The same applies if the lower threshold value is undershot.
The hysteresis is only active if the "Reset response" parameter is set to autoreset.
Initialization
When the monitoring relay is connected to the supply voltage, the initialization phase starts and
internal functional tests are performed. During the initialization phase that lasts approximately
1.6 s, the connection to the 3UL23 residual-current transformer is one of the things that is
checked. During this time, no measurement or monitoring of the fault current takes place. - - A
is shown on the display. The relay switching behavior during the initialization phase can be
determined with the help of the "Init" parameter. In the factory setting ("Init" parameter = ERR),
the output relays switch to the fault state until completion of the initialization phase because
there is no valid measuring result of the fault current.
If the parameter is set to "OK", it is assumed that there is no internal fault and the fault current
will be within the set limits. For this reason, the output relays are switched to the work position
when the supply voltage is present.
After completion of the initialization phase, a permanent self-test takes place without
interrupting the monitoring function.
The restart delay time allows the motor to cool down if the device has tripped due to
overtemperature.
Possible indications on the display: RsDel
FRV˳ ,>$@
FRV˳
,V ,S ,V[FRV˳
0>@
The diagram shows that it only makes sense to use the power factor cos φ to monitor the rated
current up to approx. 70%. At a higher rated current the change in the power factor is too slight
to produce measured values of any significance. In contrast, the monitoring quality of the
apparent current Is increases along with the torque, in other words as the rated current rises. It
is for this reason that monitoring of the apparent current is primarily used if a load needs to be
protected against overload. Integrated monitoring from no-load operation up to overload is only
possible by monitoring the active current Ip, the product of power factor and apparent current.
Note
Determining the thresholds in practice
You can determine the thresholds by operating the motor at the load limits, for example. You can
then read the thresholds as the up-to-date measured values off the display of the monitoring
relay.
Sensor sensitivity
The sensor sensitivity is the sensitivity R sens, with which the filling level monitoring relay must
respond.
The working principle of the filling level monitoring relays is based on resistance measurement
of conductive liquids (conductive measurement method). This method can be used with all
liquids and substances that have a resistivity < 200 kΩ.
Product kΩ Product kΩ
Buttermilk 1 Natural water 5
Fruit juice 1 Waste water treatment 5
Product kΩ Product kΩ
Vegetable juice 1 Starch solution 5
Milk 1 Oil 10
Soup 2,2 Condensation 18
Beer 2,2 Soap foam 18
Coffee 2,2 Jellies 45
Ink 2,2 Gelatin 45
Salt water 2,2 Sugar solution 90
Wine 2,2 Whisky 220
Distilled water 450
Scaling factor
The "scaling factor" parameter allows the user to set the number of pulses per revolution
provided by the pulse encoder. This allows the revolutions per minute to be read direct on the
display.
Possible indications on the display: Scale
Stabilization delay
An output is only switched to the "correct position" after switching on the supply voltage if all
monitored measured values are stable for the duration of the stabilization delay. The monitoring
functions are active within the stabilization delay. A threshold overshoot or undershoot in this
time does not result in a fault, but instead in restarting of the stabilization delay.
The stabilization delay starts in the following cases:
• At Power‑ON
Reapplication of the supply voltage (Power‑ON) of the device after
disconnection of the current flow (zero current).
• At manual reset
A fault is acknowledged by a manual reset. After this, the device responds in the same way
as
when the supply voltage is connected.
The stabilization of line voltage is useful, for example, in the case of generator operation.
Note
Whenever the menu level is exited SET, the stabilization time starts again.
3RR2143-1A.30 (S2)
Figure C-9 3RR2143-1A.30 with contactor
Figure C-10 3RR2143-1A.30 with terminal support for stand-alone assembly
3RR2143-3A.30 (S2)
Figure C-11 3RR2143-3A.30 with contactor
Figure C-12 3RR2143-3A.30 with terminal support for stand-alone assembly
3RR2243-1F.30 (S2)
Figure C-13 3RR2243-1F.30 with contactor
Figure C-14 3RR2243-1F.30 with terminal support for stand-alone assembly
3RR2243-3F.30 (S2)
Figure C-15 3RR2243-3F.30 with contactor
Figure C-16 3RR2243-3F.30 with terminal support for stand-alone assembly
6,5,86
Figure C-17 3UG4. monitoring relays with 2 connecting terminals with screw-type connections
6,5,86
Figure C-18 3UG4. monitoring relays with 2 connecting terminals with spring-loaded connections
6,5,86
Figure C-19 3UG4. monitoring relays with 3 connecting terminals with screw-type connections
6,5,86
Figure C-20 3UG4. monitoring relays with 3 connecting terminals with spring-loaded connections
6,5,86
Figure C-21 3UG4. monitoring relays with 4 connecting terminals with screw-type connections
6,5,86
Figure C-22 3UG4. monitoring relays with 4 connecting terminals with spring-loaded connections
A1+ 11
Y1 Y2 Y3
R=R.1+R.2
R.1-VALUE kΩ
R.2-VALUE kΩ
14 12 A2-
A1+ 11
Y1 Y2 Y3
R=R.1+R.2
R.1-VALUE kΩ
R.2-VALUE kΩ
14 12 A2-
A1+ 11 KE
Y1 Y2 Y3
TEST/
RESET
R=R.1+R.2
R.1-VALUE kΩ
R.2-VALUE kΩ
L+ L-
14 12 A2-
A1+ 11 KE
Y1 Y2 Y3
R=R.1+R.2
R.1-VALUE kΩ
R.2-VALUE kΩ
L+ L-
14 12 A2-
A1+ 11 21 Y1 Y2 Y3
TEST/
Rx=Rx.1+Rx.2 RESET
R1.1-VALUE kΩ R2.1-VALUE kΩ
R1.2-VALUE kΩ R2.2-VALUE kΩ
ON
4 3 2 1
12 14 L+ VS V1+ V1-
22 24 L- KE A2-
A1+ 11 21 Y1 Y2 Y3
TEST/
RESET
Rx=Rx.1+Rx.2
R1.1-VALUE kΩ R2.1-VALUE kΩ
F
R1.2-VALUE kΩ R2.2-VALUE kΩ
ON
4 3 2 1
12 14 L+ VS V1+ V1-
22 24 L- KE A2-
VL+ VL-
MAINS CONNECTION
L+ V1+ L- V1-
VS VE V
Run
1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
1) 2)
>500ms
Value
1) 1) 1)
1) 1) 1) 1)
1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
Set >2s
Error + >2s
+ >500ms
>500ms
yes
no
Memory ?
1) 2) 1) 2)
1) 2) 1) 2)
1) 2)
1) B1 11 On
Del
Q 12 14
Off
I! , I! Ir , Ir
2) Value"
According to the setting in the"menu
Not exceeded
Fallen below
Display Threshold
Exceeded
Not above- Fallen below
Fallen below
Run
1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
1) 2)
>500ms
Value
1) 1) 1)
1) 1) 1) 1)
1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
Set >2s
Error + >2s
+ >500ms
>500ms
yes
no
Memory ?
1) 2) 1) 2)
1) 2) 1) 2)
1) 2)
1) B1 11 On
Del
Q 12 14
Off
I! , I! Ir , Ir
Not exceeded
Fallen below
Display Threshold
Exceeded
Not above- Fallen below
Fallen below
Run
1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
1) 2)
>500ms
Value
1) 1) 1)
1) 1) 1) 1)
1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
Set >2s
Error + >2s
+ >500ms
>500ms
yes
no
Memory ?
1) 2) 1) 2)
1) 2) 1) 2)
1) 2)
1) B1 11 On
Del
Q 12 14
Off
I! , I! Ir , Ir
Not exceeded
Fallen below
Display Threshold
Exceeded
Not above- Fallen below
Fallen below
Run
1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
1) 2)
>500m s
V a lu e
1) 1) 1)
1) 1) 1)
>500m s
>2s >2s
>2s >2s
Set E rro r +
>500m s >500m s
+
ye s
no
M e m o ry ?
1) 1)
1) On
D el
O ff
11 21
12 14 22 24
Run
!PV
Value
!PV
!V !V
!V
Set Error !V
!PV
!PV
QR \HV
0HPRU\"
1) 2Q
'HO
2II
2) 8SSHUOLPLWYDOXH
RYHUVKRW
QRWRYHUVKRW
/RZHUOLPLWYDOXH
QRWXQGHUVKRW
XQGHUVKRW
Run
1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
1) 2)
>500ms
Value
1) 1) 1)
1) 1) 1)
>500ms
>2s >2s
>2s
Set Error + >2s
>500ms
+ >500ms
no yes
Memory ?
1) 1)
On
1) Del
Off
11 21
12 14 22 24
2) Upper limit value
... overshot
... not overshot
Lower limit value
... not undershot
... undershot
Run
1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
1) 2)
>500ms
Value
1) 1) 1)
1) 1) 1)
1) 1) 1)
>500ms
>2s >2s
>2s
Set Error + >2s
>500ms +
>500ms no yes
Memory ?
1) 1)
On
1) Del
Off
11 21
1214 22 24
2) Upper limit value
... overshot
... not overshot
Lower limit value
... not undershot
... undershot
Run
1) 2) 1) 2) 1) 2) 1) 2) 1) 2)
1) 2)
>500ms
Value
1) 1) 1)
1) 1) 1)
1) 1) 1)
>500ms
>2s >2s
>2s
Set Error + >2s
>500ms +
>500ms no yes
Memory ?
1) 1)
1) On
Del
Off
11 21
12 14 22 24
Run Example
1) 2)
>500ms
Value
1) 1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
Set >2s
Error + >2s
>500ms +
yes
>500ms no
Memory?
1) 1)
2) 2)
1) 11
On
Del
12 14 Off
2) 2)
exceeded
not overshot
Display Limit
exceeded
not overshot/undershot
Fallen below
Run Example
1) 2)
>500ms
Value
1) 1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
Set >2s
Error + >2s
>500ms +
>500ms
yes
no
Memory?
1) 1)
2) 2)
1) 11 On
Del
2) 2) 12 14 Off
Display Limit
exceeded
not overshot/undershot
Fallen below
Run
1) 2)
>500ms
Value
3)
1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
Set >2s
Error
+ >2s
>500ms
+ >500ms
yes
no
Memory ?
3) 3) 1)
3)
1) 11 On
Del
12 14 Off
21 On
Off
22 24
2)
Display
upper limit value and
warning threshold not overshot
Display
Display
Upper limit overshot
1) 11 On
Run Del/OnDel
12 14 Off
1) 2) 21 On
OnDel
>500ms
22 24 Off
Value
2) Limit value and warning threshold
...overshot
1) 1) 1)
... not overshot
1) 1) 1) 1)
>500ms
>2s
+ >500ms
>500ms yes
no
Memory ?
1) 2)
1) 2)
1) 2)
Run
1) 2)
>500ms
Value
1) 1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
Set >2s
Error + >2s
>500ms
>500ms +
no yes
Memory ?
1) 1)
2) 2)
2) 2)
1) 11
On
Del
12 14 Off
exceeded
not overshot
Display Limit
exceeded
not overshot/undershot
Fallen below
Run
1) 2)
>500ms
Value
1) 1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
Set >2s
Error + >2s
>500ms
+
yes
>500ms no Memory?
1) 1)
2) 2)
2) 2) 1) 11
On
Del
12 14 Off
exceeded
not overshot
Display Limit
exceeded
not overshot/undershot
Fallen below
Run
1) 2)
>500ms
Value
1) 1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
>2s
Set Error + >2s
>500ms
>500ms
+
no yes
Memory ?
1) 1)
2) 2)
1) 11
On
Del
12 14 Off
2) 2)
2) Depending on the setting in menu " Value"
Display Upper limit value
exceeded
not overshot
Display Limit
exceeded
not overshot/undershot
Fallen below
Run
1) 2) 1) 2) 1) 2)
1) 2)
>500ms
Value
1) 1) 1) 1)
1) 1) 1) 1)
1) 1) 1) 1)
1) 1) 1) 1)
>500ms
>2s >2s
>2s
Set Error + >2s
>500ms >500ms
yes +
no Memory ?
1) 2)
1) 2) 1) 2)
1) 11 21
On
Del
12 14 22 24 Off
not overshot
Fallen below
Display Limit
overshot (21-22-24)
not overshot/undershot
undershot (11-12-14)
Run
1) 2)
1) 2)
> 500ms
Value
1) 1) 1) 1)
1) 1) 1) 1)
> 500ms
>2s >2s
Error + >2s
Set >2s
>2s
yes + >500ms
Memory?
no
> 500ms > 500ms
1)
2)
1)
2)
1) 11 On
Del
12 14 Off
Display Limit
exceeded
not overshot/undershot
Fallen below
C
4
Cable break
4-wire AC system
3RR21 current monitoring relays, 51
3UG4581-.AW3., 155
3RR22 current monitoring relays, 58
3UG4582-.AW3., 182
Certifications, 16
3UG4583-.CW3., 184
Characteristics, 16
3UG4583-.CW31 and 3UG4983-.AA01, 261
Load limit curves 3UG4581, 156
3UG4583-1CW30 and 3UG4983-1A, 255
Load limit curves 3UG4582, 186
Load limit curves 3UG4583, 188
Closed-circuit principle, 272
A Cos phi monitoring
Accessories - 3RR2 current monitoring relays 3UG4641 cos phi and active current monitoring
Sealable cover, 227 relay, 205
Terminal support for stand-alone assembly, 228, Current monitoring principle, 271
230
M
Manual RESET, 268
P
Manuals, 264 Parameters for
Memory function, 149, 169 3RR21 current monitoring relay, analog, 53
Menu navigation, 38, 40 3UG4501 filling level monitoring relay, 70
Menu-based operation, 37 3UG4513 line monitoring relay, 86
Minimum clearance 3UG4581 insulation monitoring relay, 152
3RR2 current monitoring relays, 27 3UG4582/3UG4583 insulation monitoring
relays, 177
3UG4614 line monitoring relay, 92
R T
Reference, 263 Terminal support for stand-alone assembly
Relay switching behavior, 272 3RR2 current monitoring relays, 228, 230
Removable terminals, 26 Test certificates, 16
Reset response, 268 Threshold for overshoot, 267
Residual current monitoring, 270 Threshold for undershoot, 267
Residual current transformer Tripping delay time, 265
3UG4625 residual current monitoring relay, 130, tRMS, 37
235 True root mean square measurement, 37
Resistance to extreme climates, 18 Two-point monitoring
Restart delay time, 269 3UG4501 filling level monitoring relay, 68
rms value, 37
U
S Undercurrent
Scaling factor, 273 3UG4621/3UG4622 current monitoring
Scope of validity relays, 113
Manual, 9 3UG4641 cos phi and active current monitoring
Screw mounting relay, 205
3UG4 monitoring relay, 32 Undervoltage
Screw-type connection, 20 3UG4.1 line monitoring relay, 73, 74
Screw-type connection system 3UG4631/3UG4632/3UG4633 voltage monitoring
Connection cross-sections, 19 relay, 191
Screw-type connections, 18
Sealable cover, 231, 232, 251, 252
3RR2 current monitoring relays, 227 V
Sensor sensitivity, 272
Voltage asymmetry, 265
Setting, 37
Voltage reducer module, 252, 257, 258
W
Warning threshold for overshoot, 267
Warning threshold for undershoot, 267
Wire-break monitoring
3UG4621/3UG4622 current monitoring
relays, 113