Powerware APR48 Rectifier Module

Product Datasheet

AC Input
Nominal AC Input: 240 V
Rated Operating Ranges: 185 to 275 V rms – full output up to 50°C [122°F]
150 to 185V rms – full output up to 30°C [86°F]
Extended Operating Range: 90 to 300 V rms
Reduced output power below 150V (see derating curves)
Frequency Range: 45 to 66 Hz
Maximum Input Current: 12A rms (150V AC, 20°C)
Efficiency: 90% typical (50 to 100% load, 230V AC)
Power Factor: >0.99 (50 to 100% load)
Total Harmonic Distortion (THD): <5% (50 to 100% load, rated AC voltage)
Swell Tolerance: Rectifier shuts down above 320V, returns to normal operation
when input is within operating range.
Input Over-current Protection: Fuses (phase and neutral) HRC
AC Fuse Ratings: 15A / 250V

100
100
% of Maximum output

% of Maximum output

Vac > 185V


current at 48V

current at 48V

TA ≤ 30oC
Vac > 150V TA ≤ 50oC
50 50

0 0
-20 0 10 20 30 40 50 60 70 80 120 160 200 240 280
Ambient Temperature (°C) AC Supply Voltage (Vrms )

Temperature derating of output current AC input voltage derating of output current

Issue C, October 2004 Page 1 of 3


Email: dc.info@powerware.com, www.powerware.com
© Eaton Corporation. All Rights Reserved. In the interests of continual product improvement all specifications are subject to change without notice. Performance ratings are valid with all other
variables at Nominal. Specifications guaranteed over operating range. Powerware, Intergy, CellSure, SiteSure, DCTools and PowerManager are trade marks of Eaton Corporation. All other
marks are the property of their respective owners.
Powerware APR48 Rectifier Module

DC Output
Nominal Voltage: 48 V
Adjustable Voltage Range: 43 to 57.5V
Rated Output Power: 1500 W
Rated Output Current: 31 A @ 48V
Preset Accuracy ±0.1 V
Regulation: ±0.1 V
Constant voltage mode, AVC enabled from SM40.
Default (Fail-safe) voltages
Loss of System Communication: Output voltage resets to system preset voltage
Preset voltage: 54.5 ±0.1 V (manufacturer preset)
Hold-up Time: 7 ms
At rated output power over the rated AC voltage range
Start-up time: Soft start
Protection
Current Limit: Factory set to 31A
Over Temperature Turndown: Automatic current turndown. See temperature derating graphs.
Crowbar diode and fuse in negative output
Polarity Reversal: <3 ms delay
Over Voltage Shutdown:
Noise under nominal conditions
Ripple (<100Hz) <10 mV rms (unweighted)
Audio Frequency (300 Hz – 3.4 kHz): <2 mV (psophometric)
Wide band (5Hz – 1MHz): <10 mV rms (unweighted)
Peak to peak (0 – 20 kHz): <200 mV p-p (unweighted)
Discrete frequency (3.4kHz – 150kHz): <5 mV rms (1kHz wide selective frequency)

Environmental Requirements
Ambient Temperature
Rated Operating Range: -10°C to +50°C [14°F to 122°F]
Extended Operating Range: -40°C to +70°C [-40°F to 158°F]
Output derates above 50°C (or 30°C at low AC voltage) and
below -10°C [14°F] . Refer to derating graphs.
Humidity
Nominal: 50% RH
Range: < 95% RH (non condensing)
Altitude: < 2000m [6500’]

Mechanical
Dimensions H, W, D: 3U (133mm, 5.25”), 13E (66mm, 2.6”), 257mm (10.1”) overall
Weight: 1.9kg [4.2lb]
Connector: H16 Eurocard male
Cooling: Temperature controlled, high reliability fan
Front panel LEDs:
Power on: Green
Non-urgent alarm: Amber
Urgent alarm: Red

Issue C, October 2004


Page 2 of 3
Powerware APR48 Rectifier Module

Compliances
Safety: AS/NZS 60950, UL 60950, IEC 60950
EMC – immunity
Electrostatic discharge: EN 61000-4-2
Radiated radio frequency: EN 61000-4-3
Electrical fast transients: EN 61000-4-4
Surge: EN 61000-4-5
Conducted radio frequency: EN 61000-4-6
Dips, interruptions & variations: EN 61000-4-11
EMC – emissions
Conducted emissions (AC): EN 55022 / CISPR 22 (Class B)
Conducted emissions (DC): EN 300 386 (Class A)
Radiated emissions: EN 55022 / CISPR 22 (Class B)
Harmonics: EN 61000-3-2
Fluctuations and flicker: EN 61000-3-3

Certifications
Europe CE-mark
USA UL and FCC (pending)
Canada IC
China MII
Australia C-tick
New Zealand C-tick, Telepermit

Issue C, October 2004