Module Eaton APR48 2G
Module Eaton APR48 2G
Module Eaton APR48 2G
Product Datasheet
AC Input
Nominal AC Input: 240 V
Rated Operating Ranges: 185 to 275 V rms – full output up to 50°C [122°F]
150 to 185V rms – full output up to 30°C [86°F]
Extended Operating Range: 90 to 300 V rms
Reduced output power below 150V (see derating curves)
Frequency Range: 45 to 66 Hz
Maximum Input Current: 12A rms (150V AC, 20°C)
Efficiency: 90% typical (50 to 100% load, 230V AC)
Power Factor: >0.99 (50 to 100% load)
Total Harmonic Distortion (THD): <5% (50 to 100% load, rated AC voltage)
Swell Tolerance: Rectifier shuts down above 320V, returns to normal operation
when input is within operating range.
Input Over-current Protection: Fuses (phase and neutral) HRC
AC Fuse Ratings: 15A / 250V
100
100
% of Maximum output
% of Maximum output
current at 48V
TA ≤ 30oC
Vac > 150V TA ≤ 50oC
50 50
0 0
-20 0 10 20 30 40 50 60 70 80 120 160 200 240 280
Ambient Temperature (°C) AC Supply Voltage (Vrms )
DC Output
Nominal Voltage: 48 V
Adjustable Voltage Range: 43 to 57.5V
Rated Output Power: 1500 W
Rated Output Current: 31 A @ 48V
Preset Accuracy ±0.1 V
Regulation: ±0.1 V
Constant voltage mode, AVC enabled from SM40.
Default (Fail-safe) voltages
Loss of System Communication: Output voltage resets to system preset voltage
Preset voltage: 54.5 ±0.1 V (manufacturer preset)
Hold-up Time: 7 ms
At rated output power over the rated AC voltage range
Start-up time: Soft start
Protection
Current Limit: Factory set to 31A
Over Temperature Turndown: Automatic current turndown. See temperature derating graphs.
Crowbar diode and fuse in negative output
Polarity Reversal: <3 ms delay
Over Voltage Shutdown:
Noise under nominal conditions
Ripple (<100Hz) <10 mV rms (unweighted)
Audio Frequency (300 Hz – 3.4 kHz): <2 mV (psophometric)
Wide band (5Hz – 1MHz): <10 mV rms (unweighted)
Peak to peak (0 – 20 kHz): <200 mV p-p (unweighted)
Discrete frequency (3.4kHz – 150kHz): <5 mV rms (1kHz wide selective frequency)
Environmental Requirements
Ambient Temperature
Rated Operating Range: -10°C to +50°C [14°F to 122°F]
Extended Operating Range: -40°C to +70°C [-40°F to 158°F]
Output derates above 50°C (or 30°C at low AC voltage) and
below -10°C [14°F] . Refer to derating graphs.
Humidity
Nominal: 50% RH
Range: < 95% RH (non condensing)
Altitude: < 2000m [6500’]
Mechanical
Dimensions H, W, D: 3U (133mm, 5.25”), 13E (66mm, 2.6”), 257mm (10.1”) overall
Weight: 1.9kg [4.2lb]
Connector: H16 Eurocard male
Cooling: Temperature controlled, high reliability fan
Front panel LEDs:
Power on: Green
Non-urgent alarm: Amber
Urgent alarm: Red
Compliances
Safety: AS/NZS 60950, UL 60950, IEC 60950
EMC – immunity
Electrostatic discharge: EN 61000-4-2
Radiated radio frequency: EN 61000-4-3
Electrical fast transients: EN 61000-4-4
Surge: EN 61000-4-5
Conducted radio frequency: EN 61000-4-6
Dips, interruptions & variations: EN 61000-4-11
EMC – emissions
Conducted emissions (AC): EN 55022 / CISPR 22 (Class B)
Conducted emissions (DC): EN 300 386 (Class A)
Radiated emissions: EN 55022 / CISPR 22 (Class B)
Harmonics: EN 61000-3-2
Fluctuations and flicker: EN 61000-3-3
Certifications
Europe CE-mark
USA UL and FCC (pending)
Canada IC
China MII
Australia C-tick
New Zealand C-tick, Telepermit