RT7-48V/6kW: Specification

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

RT7-48V/6kW

Specification

The RT7-48V/6kW is a 3 phase, active power factor Illustrated is a single rectifier module.
corrected, switched mode rectifier (SMR) module
designed to provide up to 6kW of output power
(100A nominal) into a 48V nominal system. This
rectifier is primarily used in conjunction with a
battery to provide an uninterruptible DC power
system for telecommunications applications. Up
to 20 rectifiers can fit in a rack and up to 225
rectifiers can be configured as a system using one
control and supervisory unit (CSU). The system
can be monitored and controlled remotely using
WinCSU software (see CSU specification for more
details).

Operating characteristics of the RT7-48V/6KW at 25°C ambient, 400VAC, 50Hz unless otherwise
stated:

Input
Voltage Three phase, three wire and Earth
400 +32/-20% VAC (320VAC - 530VAC)
Phase to phase delta connection;
Tolerable phase imbalance 10%
(Measured L-L as defined by IEEE/IEC)
Voltage withstand 575VAC line-line indefinitely
Current 13A RMS max line current at 320VAC;
10A RMS line current at 400 VAC;
Sinusoidal waveform;
Frequency 45 - 66Hz;
Phase Rotation Insensitive to Phase Rotation
Harmonic Distortion Current THD < 5% typically at full output power when operated with mains
voltage THD < 2%; (±1% phase imbalance)
Inrush Current < 16A peak at nominal mains voltage;
Soft Start Output current ramp-up time 7 seconds to 100A;
Protection HRC fuses at input of SMR; power circuit is turned off if the AC voltage
exceeds ~535VAC or falls to less than ~315VAC; unit re-activates when AC
voltage is within approximately 340 – 510 VAC; input inrush limiting circuit
prevents high surge currents when connecting to a live AC bus;
Voltage Withstand Test 1500VAC input to chassis for 1 minute;
(2200VDC 100% testing on production units);
Efficiency Typically >91% at > 40% output power;
Power Factor > 0.98 for >50% output power;
> 0.99 for 100% output power;
Efficiency vs Load at 54V Power Factor vs Load at 54V
0.94 1.00
0.92
0.96
0.90

0.88 0.92

0.86 0.88
0.84
0.84
0.82
Efficiency (Po/Pin) Pow er Factor
0.80 0.80
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Load Current (A) Load Current (A)

www.rectifiertechnologies.com Page 1 of 7
950-1485-07 RT7 48V-6kW
RT7-48V/6kW
Specification

Output
Voltage Float: 43.0 – 58.0V
Equalise: 50.0 – 59.5V
Current Limit Range: 10 - 130A
Power Limit Current limit is automatically reduced in inverse proportion to output
voltage above 46VDC to limit output power to 6 kW (min);
Max. current:
• 125A at 48.0V
• 110A at 54.0V
• 101A at 59.5V
Voltage Withstand Test 1000VAC output to chassis for 1 minute;
(1500VDC 100% testing on production units);
Conversion Frequency >20kHz;
Static Regulation Line: better than ± 0.05%;
Load: terminal voltage drops by 0.42V ± 0.03V from zero to 100A load (for
passive current sharing) for stand-alone units, or regulates to better than
±0.05% for CSU controlled units;
Dynamic Regulation ± 2% for 10A to 90A to 10A step load change;
± 1% of final value within 4ms of step change;
± 1% for a 25% step change in AC input voltage;
Noise < 2mV RMS Psophometrically weighted;
< 10mV RMS (10kHz - 100MHz);
< 100mV peak to peak (10kHz - 100MHz);
Load Sharing Better than ± 5% of full scale with active current sharing from CSU;
Protection Fuse at output of SMR;
Soft start circuit prevents surges when connection is made to a live DC bus;
Overvoltage - only faulty unit shuts down;
Overcurrent - can sustain short circuit at output terminals indefinitely.
Output current starts folding back when output voltage drops below 30V
to less than 50A at zero terminal voltage;
Over-temperature - gradual reduction of power limit if heatsink
temperature exceeds pre-set limit;

70

Pow er Limit
Region
60

50
Output Voltage (V)

40

30

20

10

0
0 20 40 60 80 100 120 140
Output Current (A)

*130A current limit automatically reduces by 1A/°C for heatsink temperatures above 60°C.

www.rectifiertechnologies.com Page 2 of 7
950-1485-07 RT7 48V-6kW
RT7-48V/6kW
Specification

Remote Controls
Equalise Mode Equalise mode is initiated by a signal from the CSU. In case of loss of
communication with the controller the SMR will default to the Float mode.
Rectifier Inhibit Rectifiers can be inhibited by a signal from a remote WinCSU terminal,
transmitted via the CSU;
External Digital Voltage The CSU uses the optically isolated communications lines to digitally
Control (EDVC) control rectifier Float and Equalise voltages over a limited voltage range in
order to adjust battery voltage for temperature and voltage drop in DC bus,
limit the maximum battery recharging current and to achieve active
current sharing;

SMR Parameters Programmed by CSU


In the SMR menu • Current Limit
on the CSU • High Voltage Shut-Down (HVSD)
• High Voltage Alarm
• Low Voltage Alarm
• Latched Fault Reset
In the Battery menu • Float Voltage
on the CSU • Equalise Voltage
Test Function Test function causes all rectifier LEDs to flash.
(when activated on CSU)

Alarms and Monitoring


SMR Status Monitoring CSU and WinCSU monitor status of the SMR:
• Output current of SMR;
• Temperature of heatsink of SMR;
• SMR alarms;
Current Monitored on CSU and WinCSU with 1A resolution; Analogue measurement
accuracy ± 1% at full load; Optional bar-graph display on rectifier;
Voltage System voltage normally displayed on CSU alphanumeric display. Accuracy
± 0.5%
SMR address The SMR address is automatically set by resistors in the magazine

Front Panel LED condition table

Green Yellow Red Condition


Off Off Off No AC power No AC Power available to SMR
Blink Off Off Primary power bad Indicates the input AC is too low or too high, or
the primary circuit is faulty
ON Off Off Normal Status is normal
ON Flash Off Alarm See Alarm table
ON ON Off Equalise SMR is in equalise mode
Off Flash ON Shutdown SMR is shut down by remote control, or due to
environmental conditions, or there is an internal
control circuit fault
Off Off ON Microcontroller fault

www.rectifiertechnologies.com Page 3 of 7
950-1485-07 RT7 48V-6kW
RT7-48V/6kW
Specification

SMR Alarm Monitoring: The table shows alarm conditions that are monitored by the SMR and are
displayed on both CSU and WinCSU. The mnemonics listed here appear on WinCSU, but full alarm
description appears on CSU;

Vh Output voltage too high


Vl Output voltage too low
Il Unit is in current limit
Po Unit is in power limit
Th Heatsink temperature high and thermal limit is active
Lo Low output current (less than 1A)
Ma Operating parameters out of range (or EEPROM fault)
No Response SMR communication fault. Generated within CSU
Sd * Unit is shut down by remote command - user shutdown
Mr * Internal voltage reference faulty
Vs * High voltage shut down (output), latched alarm. User setting or fault
Unit Off * Unit is shut down due to AC out of range (normal operation) or SMR primary circuit fault.
NC * SMR incorrectly inserted into the magazine
Ff * Fan failure
Tl ** Low temperature (below -25C)
Oh * Overheat (heatsink temp. > 95C)
Ts * Temperature sensor fault
Rs * Resonance on primary converter
Dc * DC-DC converter feedback fault, latched alarm
Notes: * indicates unit shut-down,
** shut-down below -28C

Compliances
Safety Designed to IEC60950; AS/NZS 60950; (with European group difference);
UL60950
EMC Emissions and ETSI EN300 386 V1.3.1(2001-09)
Immunity
Environmental ETSI EN 300 019

EMC Test Levels


Emissions:
Harmonics IEC 61000-3-2 Class A
Flicker IEC 61000-3-3
Conducted RF AC Terminals: CISPR 22; Class B
DC Terminals: CISPR 22 Class A
Radiated RF CISPR 22; EN55022*; AS/NZS 3548*: Class B

Immunity:
Electrostatic Discharge IEC 61000-4-2
(ESD) (Level 4: Air 15kV, Contact 8kV) Criterion A
Radiated RF IEC 61000-4-3
(Level 4: 10V/m, 1kHz 80% AM) Criterion A
ENV50204 - GSM Radiation (Mobile Phone)
(Level 4: 10V/m, 100% AM, 50% duty) Criterion A

www.rectifiertechnologies.com Page 4 of 7
950-1485-07 RT7 48V-6kW
RT7-48V/6kW
Specification

Electrical Fast Transient IEC 61000-4-4


(EFT) (Level 4: 4kV on AC lines) Criterion A
(Level 3: 2kV on load and 1kV on comms lines) Criterion A
Surge Protection ANSI C62.41-1991 category B3 - AC lines
(Combination Wave 6kV/3kA; Ring Wave 6kV/500A)
IEC 61000-4-5 (Impulse)
(Level X: 6kV/3kA Common Mode [CM] on AC lines) Criterion B
(Level X: 6kV/3kA Differential Mode [DM] on AC lines) Criterion B
(Level 3: 2kV CM, 1kV DM on DC lines) Criterion A
IEC 61000-4-12 (Ring Wave)
(Level X: 6kV/500A, 100kHz CM & DM on AC lines) Criterion A
(Level 3: 2kV CM, 1kV DM on DC lines) Criterion A
Conducted RF IEC 61000-4-6
(Level 3: 10V on AC, load and comms lines) Criterion A
Voltage Dip, Interruptions IEC 61000-4-11
(Level: 100% dip for 10ms) Criterion B
(Level: 30% dip for 500ms) Criterion B
(Level: 60% dip for 1000ms) Criterion B
(Level: 100% dropout for 5s) Criterion B

Environmental
Environmental Class (EN Operational: Class 3.3 (Stationary Use at Non-Temperature-Controlled Locations)
300 019) Transport: Class 2.3 (Public Transportation)
Storage: Class 1.2 (Weather Protected Non-Temperature-Controlled Locations)
Cooling Forced convection cooling using 80mm fans with variable speed
temperature control and finger guards. Fans stop if AC power fails or
rectifier inhibited remotely;
Temperature Operating range: -25°C to +70°C
Full power range: -25°C to +50°C
Derated operation: 50% power at +70°C
Storage: -25°C to +60°C
Transport: -40°C to +70°C

The rectifier senses its internal heat-sink temperature and, if necessary,


adjusts power limit in order to protect itself against over-heating;
Humidity Class 3.3: 0 to 100% RH condensing including dripping water and icing
conditions
Altitude Operational to 4000m.(Consult factory above 4km)

Derate maximum ambient temperature by 5°C per 1000m above sea level.
Vibration Operational: 1.5mm displacement 2-9Hz, 5m/s2 acceleration 9-200Hz,
Continuous, in any direction.
Transport(packaged): 3.5mm displacement 2-9Hz, 10m/s2 acceleration 9-
200Hz, 15m/s2 acceleration 200-500Hz, One hour, in any direction.
Shocks Operational: 40m/s2 half sine, 11ms duration, Any direction
Transport(packaged): 180m/s2 half sine, 6ms duration, Any direction
Drop Test Transport: 0.8m drop when packaged

www.rectifiertechnologies.com Page 5 of 7
950-1485-07 RT7 48V-6kW
RT7-48V/6kW
Specification

Mechanical
Dimensions Width: 441mm (17.35”)
Height: 86mm (2U) ( 3.40”)
Depth: 458mm (18.03”)
Mass < 19kg (42 lb)
Acoustic Noise < 55dB ( A Weighted)
Magazine size The RT7-48V/6KW magazine is installed in a standard 600mm (23.6”) deep
19-inch rack and takes up 2U of height. No additional clearance needs to
be left at the top and bottom of the rack.

Connections

Input, Output, and Communications:


Connectors are mounted on the back of the rectifier module; with matching connectors located at the
back of the magazine; mating of connectors occurs when unit is plugged into the magazine; the rectifier is
mechanically secured to ensure reliable mating.

www.rectifiertechnologies.com Page 6 of 7
950-1485-07 RT7 48V-6kW
RT7-48V/6kW
Specification

RT7-48V/6kW Dimensions

www.rectifiertechnologies.com Page 7 of 7
950-1485-07 RT7 48V-6kW