Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Water Wash CHECKLIST

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

EGYPTIAN ELECTRICITY HOLDING COMPANY ‫اﻟﺸﺮﻛـﺔ اﻟﻘﺎﺑﻀـﺔ ﻟﻜﮭﺮﺑﺎء ﻣﺼـﺮ‬

MIDDLE DELTA ELECTRICITY PRODUCTION COMPANY ‫ﺷﺮﻛﺔ وﺳـﻂ اﻟﺪﻟﺘـﺎ ﻹﻧﺘـــﺎج اﻟﻜﮭﺮﺑﺎء‬
NUBARIA POWER STATION COMBINED CYCLE ‫ﻣﺤﻄﺔ ﺗﻮﻟﯿﺪ ﻛﮭﺮﺑﺎء اﻟﻨﻮﺑﺎرﯾﺔ اﻟﻤﺮﻛﺒﺔ‬
Module III ‫اﻟﻤﻮدﯾﻮل اﻟﺜﺎﻟﺚ‬

Date: ……………………………………….. Shift Charge Engineer: ……………………….…………..

Operating hours:………………………. Operation Engineer:………………..………..…….……


EGYPTIAN ELECTRICITY HOLDING COMPANY ‫اﻟﺸﺮﻛـﺔ اﻟﻘﺎﺑﻀـﺔ ﻟﻜﮭﺮﺑﺎء ﻣﺼـﺮ‬
MIDDLE DELTA ELECTRICITY PRODUCTION COMPANY ‫ﺷﺮﻛﺔ وﺳـﻂ اﻟﺪﻟﺘـﺎ ﻹﻧﺘـــﺎج اﻟﻜﮭﺮﺑﺎء‬
NUBARIA POWER STATION COMBINED CYCLE ‫ﻣﺤﻄﺔ ﺗﻮﻟﯿﺪ ﻛﮭﺮﺑﺎء اﻟﻨﻮﺑﺎرﯾﺔ اﻟﻤﺮﻛﺒﺔ‬
Module III ‫اﻟﻤﻮدﯾﻮل اﻟﺜﺎﻟﺚ‬

A - Field Preparation:

ITEM POSITION
ITEM LOCATION
DURING DURING NORMAL
WASH DRYING OPERATION

The HEATER to raise water temperature to 82ºC, hot water Water wash Switch
1. Switch ON Switch ON
is more effective than cold water skid OFF

Water wash Check Check Check


2. Check Water tank and Detergent tank levels skid levels levels levels
Water wash
3. Check all valves positions in the WW skid. skid
Checked Checked Checked

The stage 2 aft wheelspace temperature must be stabilized at 150 ºF 150 ºF 150 ºF
4. HMI
150 ºF (65.5ºC) or lower. (65.5ºC) (65.5ºC) (65.5ºC)
Prior to initiating the off-line water wash, the bell mouth, struts,
and IGV’s should first be hand cleaned to prevent these deposits IGV Hand Hand Hand
5.
from being washed into the compressor during the cleaning. These bell mouth Cleaned Cleaned Cleaned
deposits can be removed by washing with a garden hose.
If necessary, close flame detector valves or blank-off, based on both Turbine Close Close
6. the type of flame detector and gas turbine model. Water may foul If If Open
the flame scanners and make start-up difficult. Compartment necessary necessary
SWITCH Rack-IN Rack-IN Rack-IN
7. Excitation 6.3 K: Rack-IN and press ON. GEAR press ON press ON press ON
SWITCH
8. LCI 6.3 K: Rack-IN and ready. GEAR
Rack-IN Rack-IN Rack-IN

SWITCH
9. A.A Compressor 6.3 K : Rack-out GEAR
Rack-out Rack-out Rack-IN

10. Open all manual isolation valves of the gas fuel line. Gas fuel line Open Open Open

Switch Switch
11. Spark plug power supply in Mark Vie PEECC OFF OFF
Switch ON

Ready to Ready to Ready to


12. Unit at Turning Gear and Ready to Start. HMI
Start Start Start
EGYPTIAN ELECTRICITY HOLDING COMPANY ‫اﻟﺸﺮﻛـﺔ اﻟﻘﺎﺑﻀـﺔ ﻟﻜﮭﺮﺑﺎء ﻣﺼـﺮ‬
MIDDLE DELTA ELECTRICITY PRODUCTION COMPANY ‫ﺷﺮﻛﺔ وﺳـﻂ اﻟﺪﻟﺘـﺎ ﻹﻧﺘـــﺎج اﻟﻜﮭﺮﺑﺎء‬
NUBARIA POWER STATION COMBINED CYCLE ‫ﻣﺤﻄﺔ ﺗﻮﻟﯿﺪ ﻛﮭﺮﺑﺎء اﻟﻨﻮﺑﺎرﯾﺔ اﻟﻤﺮﻛﺒﺔ‬
Module III ‫اﻟﻤﻮدﯾﻮل اﻟﺜﺎﻟﺚ‬

B- Manually isolate systems, open drains of Manual Isolation Valves as follows:


ITEM POSITION
ITEM LOCATION DURING DURING NORMAL
WASH DRYING OPERATION
Under the
1. Off line water wash line isolation valve inlet plenum
Open Open Close

Under the
2. ON line water wash line isolation valve inlet plenum
Close Close Open

Under the
3. the Inlet Plenum water wash drain valve inlet plenum
Open Open Close

Near turbine
4. the manual Isolation valve of IBH compartment Close Close Open
door
False Start Drain valves must be diverted from the sludge
Diverted Diverted Diverted
1 tank to a water wash effluent tank
120° to 0º 120° to 0º 0° to 120º
5. 3-way valve from 120° to 0º near IBH Near turbine
compartment Diverted Diverted Diverted
2 3-way valve near exhaust diffuser door door to water to water to sludge
Diverted Diverted Diverted
3 Manual bypass valve near exhaust diffuser door. to water to water to sludge
Under
6. Open the Exhaust Plenum water wash drain valve Diverter Open Open Close
Damper

1 the manual drain valve #1 of IBH Open Open Close


Turbine
7.
Compartment
2 the manual drain valve #2 of IBH Open Open Close

Water wash drain valve for the FSD of Combustion Chamber Turbine
8. Open Open Close
water wash drain header. Compartment
Water wash drain valve for the FSD of man-way cover in the Turbine
9. Open Open Close
Combustion Chamber. Compartment
Turbine
10. Close the manual isolation valve for APU. Compartment
Close Close Open
EGYPTIAN ELECTRICITY HOLDING COMPANY ‫اﻟﺸﺮﻛـﺔ اﻟﻘﺎﺑﻀـﺔ ﻟﻜﮭﺮﺑﺎء ﻣﺼـﺮ‬
MIDDLE DELTA ELECTRICITY PRODUCTION COMPANY ‫ﺷﺮﻛﺔ وﺳـﻂ اﻟﺪﻟﺘـﺎ ﻹﻧﺘـــﺎج اﻟﻜﮭﺮﺑﺎء‬
NUBARIA POWER STATION COMBINED CYCLE ‫ﻣﺤﻄﺔ ﺗﻮﻟﯿﺪ ﻛﮭﺮﺑﺎء اﻟﻨﻮﺑﺎرﯾﺔ اﻟﻤﺮﻛﺒﺔ‬
Module III ‫اﻟﻤﻮدﯾﻮل اﻟﺜﺎﻟﺚ‬

ITEM POSITION
ITEM LOCATION DURING DURING NORMAL
WASH DRYING OPERATION
1 manual isolation valve for Cooling Line for 9 stage left side Close Close Open

2 manual isolation valve for Cooling Line for 13 stage left side Close Close Open
Turbine
11.
Compartment
3 manual isolation valve for Cooling Line for 9 stage right side Close Close Open

4 manual isolation valve for Cooling Line for 13 stage right side Close Close Open

1 manual drain valve # 1 for Cooling Line for 9 stage left side Open Open Close

2 manual drain valve # 2 for Cooling Line for 9 stage left side Open Open Close

3 manual drain valve # 1 for Cooling Line for 13 stage left side Open Open Close

4 manual drain valve # 2 for Cooling Line for 13 stage left side Open Open Close
Turbine
12.
Compartment
5 manual drain valve # 1 for Cooling Line for 9 stage right side Open Open Close

6 manual drain valve # 2 for Cooling Line for 9 stage right side Open Open Close

7 manual drain valve # 1 for Cooling Line for 13 stage right side Open Open Close

8 manual drain valve # 2 for Cooling Line for 13 stage right side Open Open Close
Turbine
13. Manual isolation valve for AA and Gas purge. Compartment
Close Close Open

1 Manual drain valve # 1 for AA and Gas purge. Turbine


Open Open Close
14.
Compartment
2 Manual drain valve # 2 for AA and Gas purge. Open Open Close

1 Gas Fuel manifold low point drains PM1 Close Open Close
Turbine
15. 2 Gas Fuel manifold low point drains PM2 Compartment
Close Open Close

3 Gas Fuel manifold low point drains PM3 Close Open Close
EGYPTIAN ELECTRICITY HOLDING COMPANY ‫اﻟﺸﺮﻛـﺔ اﻟﻘﺎﺑﻀـﺔ ﻟﻜﮭﺮﺑﺎء ﻣﺼـﺮ‬
MIDDLE DELTA ELECTRICITY PRODUCTION COMPANY ‫ﺷﺮﻛﺔ وﺳـﻂ اﻟﺪﻟﺘـﺎ ﻹﻧﺘـــﺎج اﻟﻜﮭﺮﺑﺎء‬
NUBARIA POWER STATION COMBINED CYCLE ‫ﻣﺤﻄﺔ ﺗﻮﻟﯿﺪ ﻛﮭﺮﺑﺎء اﻟﻨﻮﺑﺎرﯾﺔ اﻟﻤﺮﻛﺒﺔ‬
Module III ‫اﻟﻤﻮدﯾﻮل اﻟﺜﺎﻟﺚ‬

C- Manually isolate systems, open drains of Transmitters Lines as follows:


ITEM POSITION
ITEM LOCATION
DURING DURING NORMAL
WASH DRYING OPERATION
1. Close THREE VALVES for compressor discharge pressure transducer Turbine Close Close Open
supply lines 96CD-1,-1B,-1C Compartment
2. Close THREE VALVES for Liquid Fuel Purge pressure transmitters Turbine Close Close Open
supply lines 96PL-1A,-1B,-1C Compartment
3. Close THREE VALVES for Water Injection Purge Differential pressure Turbine Close Close Open
transmitters supply lines 96WP-2A,-2B,-2C Compartment
4. Close THREE VALVES for Gas Fuel Nozzle Pressure Ratio pressure Turbine Close Close Open
transmitter supply lines 96GN-1,-2,-3 Compartment
5. Close THREE VALVES for Atomizing Air Purge pressure transducer Turbine Close Close Open
supply lines 96AA-1A,-1B,-1C Compartment
6. Turbine Close Close
Close the VALVE for Online Compressor Wash Manifold supply line 96WW-3 Open
Compartment
7. Close THREE VALVES for Gas Fuel Nozzle Pressure Ratio pressure Above Turbine Close Close Open
transmitter supply lines 96GN-2A,-2B,-2C Compartment
8. Close THREE VALVES for Gas Fuel Nozzle Pressure Ratio pressure Above Turbine Close Close Open
transmitter supply lines 96GN-3A,-3B,-3C Compartment
9. Close THREE VALVES for Gas Fuel Nozzle Pressure Ratio pressure Above Turbine Close Close Open
transmitter supply lines 96GN-4A,-4B,-4C Compartment
10. Close THREE VALVES for Cavity Pressure Transmitter S2N supply lines Above Turbine Close Close Open
96S2N-1,-2,-3 Compartment
11. Close THREE VALVES for Cavity Pressure Transmitter S3N supply lines Above Turbine Close Close Open
96S3N-1,-2,-3 Compartment
12. Close TWO VALVES for EXHAUST DUCT PRESSURE Transmitter Above Turbine Close Close Open
96EP-2,-3 Compartment
Divert VALVES to the vent for Diverted Diverted Diverted
1 to normal
96CS-1 COMPRESSOR INLET TOTAL PRESSURE Transmitter to vent to vent operation

2 96AP-1,-2,-3 PAROMETRIC PRESSURE Transmitter Close Close Open

13. 3 96BD-1 BELLMOUTH STATIC PRESSURE Transmitter


Above Turbine Diverted Diverted Diverted
to normal
Compartment to vent to vent operation
Diverted Diverted Diverted
4 96EP-1 EXHAUST PRESSURE Transmitter to vent to vent
to normal
operation
Diverted Diverted Diverted
5 96EP-2,-3 EXHAUST PRESSURE Transmitter to vent to vent
to normal
operation

You might also like