EDM-M*
DIGITAL AMPLIFIER
FOR OPEN LOOP
PROPORTIONAL VALVES
SERIES 40
OPERATING PRINCIPLE
TECHNICAL CHARACTERISTICS
Power supply (Ub) V DC 9 ÷ 32 ripple included
Required power W min 20 - max 70 (see point 5.2)
Max input current A 5.5
Max output current A 5.5 (see point 5.2)
89 252/222 ED 1/10
EDM-M* SERIES 40
1 - IDENTIFICATION CODE
E D M - M / 40 -
Digital amplifier
Pin 12 function:
for rail mounting DIN EN 50022
A = external enable on PIN 12
B = 24 V aux on PIN 12
(internal enable) (standard)
For open loop
Reference signal:
Versions: E0 = voltage ± 10V (standard)
1 = for single solenoid proportional valve E1 = current 4 ÷ 20 mA
2 = for double solenoid proportional valve
3 = two channels for an independent
control of two single solenoid valves Series N.
(from 40 to 49 sizes and mounting dimensions
remain unchanged)
Max current (I Max):
(first channel for EDM - M3 version)
Only for EDM-M3 version: omit for other versions
0 = 780 mA 3 = 1600 mA 6 = 1530 mA
Switching frequency (PWM) of the second channel:
1 = 860 mA 4 = 1880 mA
2 = 1200 mA 5 = 2600 mA 1 = 100 Hz 3 = 300 Hz
2 = 200 Hz 4 = 400 Hz
NOTE: other setting available upon request. Please contact our technical dept.
2 - FEATURES
Card with analogue reference signal: version A and version B Monitoring functions
The versions differ for pin 12 function. ▪ The output stage is monitored for cable breakdown, is short
EDM-M*/40*-A is configured for external enable: the amplifier is circuit proof and disables the power stage in case of an error
powered but not operational, and will supply current to the valve ▪ Failure monitoring for current analogue inputs
only if an enabling signal received from the outside (PLC) is
Other characteristics
present. The enable signal is expected on pin 12.
▪ Scaling of analogue inputs
This version offers faster response times as it eliminates
▪ Card configuration via software
initialization times at power up. The external enable can be
deactivate by parameter. ▪ Diagnostic
Controller functions
Power amplifier with current controlled by analogue input signal for
three different applications:
M1: control of 1 single solenoid proportional valve
(e.g. throttle, pressure, directional.)
M2: control of 1 dual solenoid proportional valve
(e.g. directional)
M3: control of 2 single solenoid proportional valves, via 2
independent channels.
▪ The current to solenoid is closed loop controlled, so is
independent from supply and solenoid resistance.
▪ Parameters programmable via software: ramps, PWM frequency,
dither.
89 252/222 ED 2/10
EDM-M* SERIES 40
3 - FUNCTIONAL SPECIFICATIONS
89 252/222 ED 3/10
EDM-M* SERIES 40
4 - EDM-M, DUPLOMATIC VALVES AND DEFAULT SETTINGS
EDM-M card is pre-set at factory. The following table shows the default settings of EDM-M standard versions and the current Duplomatic
valves to be coupled with. Different settings are available upon request.
Curve adaption parameters (point 8.3) permit to scale the current up to 120% of the nominal CURRENT value set.
Cards are tuned by the manufacturer to optimize the performance in accordance with the reference coil selected. Working conditions far from
nominal settings could require advanced tuning. Apply for them at our technical dept.
NOTE about EDM-M3: Combinations shown here below are just few examples of possible matches. All combinations provided in the ordering
code are possible.
CARDS FOR 24V SOLENOIDS
200 860 1125 200 DSE3, DSE3B, PRE*, PRE3, PDE3, DZCE*,
EDM-M31122 ▪ ▪
200 860 1125 200 PZE3
89 252/222 ED 4/10
EDM-M* SERIES 40
As a general rule, the valve and the electronic card connection L2 Solenoid 1 not
wires must be kept as far as possible from interference sources open coil short circuit enabled
L3 Solenoid 2 NOTE 1
(e.g. power wires, electric motors, inverters and electrical switches).
Complete protection of the connection wires can be requested in fault
L4 Ready - -
environments with critical electromagnetic interferences. NOTE 2
89 252/222 ED 5/10
EDM-M* SERIES 40
7 - DEVICE SETUP
Please note that the USB port is not galvanically isolated. We strongly recommend the use of a galvanic isolator.
The EDM-M* card can only be configured via software, from a PC with USB port, with a standard micro USB cable.
The EDM40-SmartManager configuration software can be downloaded from the Duplomatic MS website. The software is compatible with
Microsoft OS Windows only.
Detailed information about parameters operation, settings and commissioning are in the Start-up manual 89252 ETM. The technical literature
is downloadable from our website upon request for access credentials.
8 - MAIN FEATURES
8.1 - Diagnostics
Activates / deactivates the error detection. DISABLE is useful in
troubleshooting tasks.
parameter DIAGNOSTICS (ENABLE | DISABLE | AUTO)
default for EDM-M*/40*- A: ENABLE
default for EDM-M*/40*- B: AUTO
8.4 - PWM
Pwm frequencies for current output.
RAMP_UP_A RAMP1_UP
RAMP_UP RAMP_DOWN_A RAMP1_DOWN
RAMP_DOWN RAMP_UP_B RAMP2_UP
RAMP_DOWN_B RAMP2_DOWN
range: 0 … 20000 ms
default: 0
89 252/222 ED 6/10
EDM-M* SERIES 40
9 - BLOCK DIAGRAMS
The function of PIN 12 varies depending on the card version. The reference signal can be either ENABLE input (A version) or an auxiliary
voltage output (B version).
9.1 - EDM-M1
at par. 9.4
9.2 - EDM-M2
at par. 9.4
89 252/222 ED 7/10
EDM-M* SERIES 40
9.3 - EDM - M3
at par. 9.4
10 - WIRING
Pin 8 (and 11 for EDM-M3 version) must be connected to pin 15 (0V), when the potentiometer is used as reference signal. This is
recommended also when the generator has a pure differential output (not connected to ground).
89 252/222 ED 8/10
EDM-M* SERIES 40
1 Status LED
3 Protection flap
89 252/222 ED 9/10
EDM-M*SERIES 40