Technical Information
Cerabar PMP23
Process pressure measurement

Pressure transducer with hygienic, flush-mounted


metal sensors

Application
The Cerabar is a pressure transducer for the measurement of absolute and gauge
pressure in gases, vapors, liquids and dust for applications with hygienic
requirements. The Cerabar can be used internationally thanks to a wide range of
approvals and process connections.

Your benefits
• High reproducibility and long-term stability
• Reference accuracy: up to 0.3%
• Customized measuring ranges
– Turn down up to 5:1
– Sensor for measuring ranges up to 40 bar (600 psi)
• Housing and process isolating diaphragm made of 316L
• IP69 protection
• Fully-welded process connections
• Suitable for CIP/SIP cleaning
Cerabar PMP23

Table of contents

Document information . . . . . . . . . . . . . . . . . . . . . . . 4 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18


Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Ambient temperature range . . . . . . . . . . . . . . . . . . . . . 18
Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Storage temperature range . . . . . . . . . . . . . . . . . . . . . . 18
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . 6 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Turn down calculation . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . 18
Function and system design . . . . . . . . . . . . . . . . . . . 8
Measuring principle - process pressure measurement . . . . . 8 Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Process temperature range for devices with metallic
Device features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 process isolating diaphragm . . . . . . . . . . . . . . . . . . . . . 19
Product design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Pressure specifications . . . . . . . . . . . . . . . . . . . . . . . . . 19
System integration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mechanical construction . . . . . . . . . . . . . . . . . . . . 20
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Process connections with flush-mounted, metal process
isolating diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Materials in contact with process . . . . . . . . . . . . . . . . . . 27
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Materials not in contact with process . . . . . . . . . . . . . . . 28
Signal range 4 to 20 mA . . . . . . . . . . . . . . . . . . . . . . . . 11
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Load (for 4 to 20 mA devices ) . . . . . . . . . . . . . . . . . . . . 11
Load resistance (for 0 to 10 V devices) . . . . . . . . . . . . . . 11
Signal on alarm 4 to 20 mA . . . . . . . . . . . . . . . . . . . . . . 11 Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Dead time, time constant . . . . . . . . . . . . . . . . . . . . . . . 11 Plug-on display PHX20 (optional) . . . . . . . . . . . . . . . . . . 29
Dynamic behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Certificates and approvals . . . . . . . . . . . . . . . . . . . 30
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . 13 RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 RCM-Tick marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Current consumption and alarm signal . . . . . . . . . . . . . . 13 EAC conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Power supply fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Safety Instructions (XA) . . . . . . . . . . . . . . . . . . . . . . . . 30
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Suitability for hygienic processes . . . . . . . . . . . . . . . . . . 30
Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Pressure Equipment Directive 2014/68/EU (PED) . . . . . . . 31
Influence of power supply . . . . . . . . . . . . . . . . . . . . . . . 14 Manufacturer declarations . . . . . . . . . . . . . . . . . . . . . . 31
Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . 14 Other standards and guidelines . . . . . . . . . . . . . . . . . . . 32
CRN approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Calibration unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Performance characteristics of metallic process
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
isolating diaphragm . . . . . . . . . . . . . . . . . . . . . . . . 15
Inspection certificates . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Reference operating conditions . . . . . . . . . . . . . . . . . . . 15
Additional approval . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Measuring uncertainty for small absolute pressure
measuring ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Influence of the installation position . . . . . . . . . . . . . . . . 15 Ordering information . . . . . . . . . . . . . . . . . . . . . . . 33
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Reference accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Thermal change of the zero output and the output span . . . 15 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Weld-in adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Switch-on time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Process adapter M24 . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Plug-on display PHX20 . . . . . . . . . . . . . . . . . . . . . . . . . 34
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 M12 plug connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . 15
Influence of the installation position . . . . . . . . . . . . . . . . 16 Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Field of Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . 36
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . 36
Brief Operating Instructions . . . . . . . . . . . . . . . . . . . . . 36

2 Endress+Hauser
Cerabar PMP23

Safety Instructions (XA) . . . . . . . . . . . . . . . . . . . . . . . . 36

Endress+Hauser 3
Cerabar PMP23

Document information
Document function The document contains all the technical data on the device and provides an overview of the
accessories and other products that can be ordered for the device.

Symbols used Safety symbols

Symbol Meaning

DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.

WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.

CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.

NOTE!
NOTICE This symbol contains information on procedures and other facts which do not result in
personal injury.

Electrical symbols

Symbol Meaning Symbol Meaning

Protective ground connection Ground connection


A terminal which must be connected A grounded terminal which, as far as
to ground prior to establishing any the operator is concerned, is
other connections. grounded via a grounding system.

Symbols for certain types of information

Symbol Meaning

Permitted
Procedures, processes or actions that are permitted.

Forbidden
Procedures, processes or actions that are forbidden.

Tip
Indicates additional information.

Reference to documentation

A Reference to page

Reference to graphic

Visual inspection

Symbols in graphics

Symbol Meaning

1, 2, 3 ... Item numbers

1. , 2. , 3. … Series of steps

A, B, C, ... Views

4 Endress+Hauser
Cerabar PMP23

Documentation The document types listed are available:


In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download

Brief Operating Instructions (KA): getting the 1st measured value quickly
The Brief Operating Instructions contain all the essential information from incoming acceptance to
initial commissioning.

Operating Instructions (BA): your comprehensive reference


These Operating Instructions contain all the information that is required in various phases of the life
cycle of the device: from product identification, incoming acceptance and storage, to mounting,
connection, operation and commissioning through to troubleshooting, maintenance and disposal.

Safety Instructions (XA)


Safety Instructions (XA) are supplied with the device depending on the approval. These instructions
are an integral part of the Operating Instructions.

Device Directive Documentation Option 1)

PMP23 ATEX II 1/2G Ex ia IIC T4 Ga/Gb XA01271P BA

PMP23 FM IS Cl. I, Div.1 Gr. A-D T4 XA01321P FA

PMP23 CSA C/US IS Cl. I Div. 1 Gr. A-D XA01322P CB

PMP23 EAC Ex ia IIC T4 Ga/Gb XA01540P GA

PMP23 IEC Ex ia IIC T4 Ga/Gb XA01271P IA

PMP23 NEPSI Ex ia IIC T4 XA01363P NA

PMP23 TIIS Ex ia IIC T4 In preparation TA

1) Product Configurator, order code for "Approval"

The nameplate provides information on the Safety Instructions (XA) that are relevant for the
device.

Endress+Hauser 5
Cerabar PMP23

Terms and abbreviations

p
0
LRL LRV URV URL MWP OPL
A0029505

Item Term/ Explanation


abbreviation

1 OPL The OPL (over pressure limit = sensor overload limit) for the measuring device
depends on the lowest-rated element, with regard to pressure, of the selected
components, i.e. the process connection has to be taken into consideration in
addition to the measuring cell. Also observe pressure-temperature dependency. For
the relevant standards and additional notes, see the "Pressure specifications" section
→  19 .
The OPL may only be applied for a limited period of time.

2 MWP The MWP (maximum working pressure) for the sensors depends on the lowest-
rated element, with regard to pressure, of the selected components, i.e. the process
connection has to be taken into consideration in addition to the measuring cell.
Also observe pressure-temperature dependency. For the relevant standards and
additional notes, see the "Pressure specifications" section →  19 .
The MWP may be applied at the device for an unlimited period.
The MWP can also be found on the nameplate.

3 Maximum sensor Span between LRL and URL


measuring range This sensor measuring range is equivalent to the maximum calibratable/adjustable
span.

4 Calibrated/ Span between LRV and URV


adjusted span Factory setting: 0 to URL
Other calibrated spans can be ordered as customized spans.

p - Pressure

- LRL Lower range limit

- URL Upper range limit

- LRV Lower range value

- URV Upper range value

- TD (turn down) Turn down


The turn down is preset at the factory and cannot be changed.
Example - see the following section.

6 Endress+Hauser
Cerabar PMP23

Turn down calculation


1=2 3
LRL LRV URV URL

A0029545

1 Calibrated/adjusted span
2 Zero point-based span
3 URL sensor

Example

• Sensor:10 bar (150 psi) • Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)


• Upper range value (URL) = 10 bar (150 psi) • Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
Turn down (TD):

URL
TD =
|URV - LRV|

10 bar (150 psi)


TD = = 2
|5 bar (75 psi) - 0 bar (0 psi)|

In this example, the TD is 2:1.


This span is based on the zero point.

Endress+Hauser 7
Cerabar PMP23

Function and system design


Measuring principle - Devices with metallic process isolating diaphragm
process pressure
The process pressure deflects the metal process isolating diaphragm of the sensor and a fill fluid
measurement
transfers the pressure to a Wheatstone bridge (semiconductor technology). The pressure-dependent
change in the bridge output voltage is measured and evaluated.
Advantages:
• Can be used for high process pressures
• Fully welded sensor
• Slim, flush-mounted process connections available

1
2
3
4

p
A0016448

1 Silicon measuring element, substrate


2 Wheatstone bridge
3 Channel with fill fluid
4 Metal process isolating diaphragm

Measuring system A complete measuring system comprises:

1 2 3

A0021926

1 PLC (programmable logic control)


2 e.g. RN221N / RMA42 (if required)
3 Pressure transducer

Device features  

PMP23

Field of application • Gauge pressure and absolute pressure


• Hygiene applications

Process connections • Thread ISO 228


• Clamp/Tri-Clamp
• DIN 11851
• Thread M24 x 1.5
• Universal adapter
• SMS
• Varivent

Measuring ranges From –400 to +400 mbar (–6 to +6 psi) to –1 to +40 bar (–15 to +600 psi)

OPL (depends on the measuring range) Max. 0 to +160 bar (0 to +2 400 psi)

Process temperature range –10 to +100 °C (+14 to +212 °F)


(+135 °C (+275 °F) for one hour maximum)

8 Endress+Hauser
Cerabar PMP23

PMP23

Ambient temperature range • –40 to +85 °C (–40 to +185 °F)


• Devices for hazardous areas: –40 to +70 °C (–40 to +158 °F)

Reference accuracy 0.3 %, TD 5:1

Supply voltage 10 to 30 V DC

Output 4 to 20 mA

Material • Housing made from 316L (1.4404)


• Process connections made from 316L (1.4435)
• Process isolating diaphragm made from 316L (1.4435)

Options • Ex approvals
• Min. alarm current setting
• 3.1 Material certificates
• EHEDG/3A approvals
• Certificate of calibration
• Weld-in adapter
• IP69

Product design  

Overview Position Description

A B C-1 C-2 A Valve plug

B Cable

C- 1 M12 plug
Housing cap made of plastic

C- 2 M12 plug
A0027231 A0027232 A0021987 A0027289 For Ex ec and IP69: metal housing cap
Metal housing cap can also be ordered as an option.

D D Housing
E Process connection (sample illustration)

A0027227

System integration The device can be given a tag name (max. 8 alphanumeric characters).

1)
Description Option

Measuring point (TAG), see additional specifications Z1

1) Product Configurator, order code for "Identification"

Endress+Hauser 9
Cerabar PMP23

Input
Measured variable Measured process variable
PMP23: gauge pressure or absolute pressure

Calculated process variable


Pressure

Measuring range Metal process isolating diaphragm

Sensor Device Maximum Lowest MWP OPL Factory settings 2) Option 3)


Sensor measuring range calibratable
span 1)
lower (LRL) upper (URL)

[bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)]

Devices for gauge pressure measurement


4)
400 mbar (6 psi) PMP23 –0.4 (–6) +0.4 (+6) 0.4 (6) 1 (15) 1.6 (24) 0 to 400 mbar (0 to 6 psi) 1F
4)
1 bar (15 psi) PMP23 –1 (–15) +1 (+15) 0.4 (6) 2.7 (40.5) 4 (60) 0 to 1 bar (0 to 15 psi) 1H
4)
2 bar (30 psi) PMP23 –1 (–15) +2 (+30) 0.4 (6) 6.7 (100.5) 10 (150) 0 to 2 bar (0 to 30 psi) 1K
4)
4 bar (60 psi) PMP23 –1 (–15) +4 (+60) 0.8 (12) 10.7 (160.5) 16 (240) 0 to 4 bar (0 to 60 psi) 1M
4)
6 bar (90 psi) PMP23 –1 (–15) +6 (+90) 2.4 (36) 16 (240) 24 (360) 0 to 6 bar (0 to 90 psi) 1N
4)
10 bar (150 psi) PMP23 –1 (–15) +10 (+150) 2 (30) 25 (375) 40 (600) 0 to 10 bar (0 to 150 psi) 1P
4)
16 bar (240 psi) PMP23 –1 (–15) +16 (+240) 5 (75) 25 (375) 64 (960) 0 to 16 bar (0 to 240 psi) 1Q
4)
25 bar (375 psi) PMP23 –1 (–15) +25 (+375) 5 (75) 25 (375) 100 (1500) 0 to 25 bar (0 to 375 psi) 1R

40 bar (600 psi) 4) PMP23 –1 (–15) +40 (+600) 8 (120) 100 (1500) 160 (2400) 0 to 40 bar (0 to 600 psi) 1S

Devices for absolute pressure measurement

400 mbar (6 psi) 4) PMP23 0 (0) 0.4 (+6) 0.4 (6) 1 (15) 1.6 (24) 0 to 400 mbar (0 to 6 psi) 2F
4)
1 bar (15 psi) PMP23 0 (0) 1 (+15) 0.4 (6) 2.7 (40.5) 4 (60) 0 to 1 bar (0 to 15 psi) 2H
4)
2 bar (30 psi) PMP23 0 (0) 2 (+30) 0.4 (6) 6.7 (100.5) 10 (150) 0 to 2 bar (0 to 30 psi) 2K
4)
4 bar (60 psi) PMP23 0 (0) 4 (+60) 0.8 (12) 10.7 (160.5) 16 (240) 0 to 4 bar (0 to 60 psi) 2M
4)
10 bar (150 psi) PMP23 0 (0) 10 (+150) 2 (30) 25 (375) 40 (600) 0 to 10 bar (0 to 150 psi) 2P
4)
40 bar (600 psi) PMP23 0 (0) +40 (+600) 8 (120) 100 (1500) 160 (2400) 0 to 40 bar (0 to 600 psi) 2S

1) Highest turn down that can be set at the factory: 5:1. The turn down is preset and cannot be changed.
2) Other measuring ranges (e.g. –1 to +5 bar (–15 to 75 psi)) can be ordered with customer-specific settings (see the Product Configurator, order
code for "Calibration; Unit" option "J"). It is possible to invert the output signal (LRV = 20 mA; URV = 4 mA). Prerequisite: URV < LRV
3) Product Configurator, order code for "Sensor range"
4) Vacuum resistance: 0.01 bar (0.145 psi) abs

Maximum turn down which can be ordered for absolute pressure and gauge pressure sensors

Device Range 400 mbar (6 psi) 1 bar (15 psi) 2 bar (30 psi)
6 bar (90 psi) 4 bar (60 psi)
16 bar (240 psi) 10 bar (150 psi)
25 to 40 bar (375 to 600 psi)

PMP23 0.3% TD 1:1 TD 1:1 to TD 2.5:1 TD 1:1 to TD 5:1

10 Endress+Hauser
Cerabar PMP23

Output
Output signal Description Option 1)

4 to 20 mA (2-wire) 1

1) Product Configurator, order code for "Output"

Signal range 4 to 20 mA 3.8 mA to 20.5 mA

Load (for 4 to 20 mA In order to guarantee sufficient terminal voltage in two-wire devices, a maximum load resistance RL
devices ) (including line resistance) must not be exceeded, depending on the supply voltage UB of the supply
unit.

R L max
[W ]
1068

614 2 R L max £ U B - 6.5V


22mA

10 20 30 UB
[V]
1

A0029452

1 Power supply 10 to 30 V DC
2 RLmax maximum load resistance
UB Supply voltage

Load resistance (for 0 to 10 V The load resistance must be ≥ 5 [kΩ].


devices)

Signal on alarm 4 to 20 mA The response of the output to error is regulated in accordance with NAMUR NE43.
Factory setting MAX alarm: >21 mA

alarm current

Device Description Option

PMP23 Adjusted min. alarm current IA 1)

1) Product Configurator order code for "Service"

Dead time, time constant Presentation of the dead time and the time constant:

I
100 %
90 %

63 %

t1 t2 t
t3

A0019786

Endress+Hauser 11
Cerabar PMP23

Dynamic behavior Analog electronics

Dead time (t1) [ms] Time constant (T63), t2 [ms] Time constant (T90), t3 [ms]

6 ms 10 ms 15 ms

12 Endress+Hauser
Cerabar PMP23

Power supply
LWARNING
Limitation of electrical safety due to incorrect connection!
‣ In accordance with IEC/EN61010 a separate circuit breaker must be provided for the device .
‣ When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings.
‣ All explosion protection data are given in separate documentation which is available upon
request. The Ex documentation is supplied as standard with all devices approved for use in
explosion hazardous areas.
‣ Protective circuits against reverse polarity, HF influences and overvoltage peaks are integrated.
‣ The device must be operated with a 500 mA fine-wire fuse (slow-blow).

Terminal assignment 4 to 20 mA output


Device M12 plug Valve plug Cable

PMP23 0.5A 0.5A 1 0.5A


L+ 1 L+ L+
2 1
3 2
3 4 L–
L– 3
2
A0023487 L–
(a)
A0022823 A0023783

1 brown = L+
2 blue = L-
3 green/yellow = ground connection
(a) reference air hose

Supply voltage Electronic version Device Supply voltage

4 to 20 mA output PMP23 10 to 30 V DC

Current consumption and Number of wires Device Normal operation Alarm signal 1)
alarm signal
2 PMP23 ≤ 26 mA > 21 mA

1) For MAX alarm (factory setting)

Power supply fault • Behavior in the event of overvoltage (>30 V):


The device works continuously up to 34 V DC without damage. If the supply voltage is exceeded,
the specified characteristics are no longer guaranteed.
• Behavior in the event of undervoltage:
If the supply voltage falls below the minimum value, the device switches off in a defined manner
(status same as for no power supply).

Electrical connection Degree of protection

Device Connection Climate class Option 1)

PMP23 Cable5 m (16 ft) IP66/68 2) NEMA type 4X/6P enclosure A


2)
PMP23 Cable10 m (33 ft) IP66/68 NEMA type 4X/6P enclosure B
2)
PMP23 Cable25 m (82 ft) IP66/68 NEMA type 4X/6P enclosure C

PMP23 M12 plug IP65/67 NEMA type 4X enclosure M


3)
PMP23 M12 plug made of metal IP66/69 NEMA type 4X enclosure N

Endress+Hauser 13
Cerabar PMP23

Device Connection Climate class Option 1)

PMP23 Valve plug ISO4400 M16 IP65 NEMA type 4X enclosure U

PMP23 Valve plug ISO4400 NPT ½ IP65 NEMA type 4X enclosure V

1) Product Configurator, order code for "Electrical connection"


2) IP 68 (1.83m H2O for 24 h)
3) Designation of the IP protection class according to DIN EN 60529. Previous designation "IP69K" according
to DIN 40050 Part 9 is no longer valid (standard withdrawn on November 1, 2012). The tests required by
both standards are identical.

Cable specification For valve plug: < 1.5 mm2 (16 AWG) and Ø3.5 to 6.5 mm (0.14 to 0.26 in)

Residual ripple The device operates within the reference accuracy up to ±5 % of the residual ripple of the supply
voltage, within the permitted voltage range.

Influence of power supply ≤0.005 % of the URL/1 V

Overvoltage protection The device does not contain any special elements to protect against overvoltage ("wire to ground").
Nevertheless the requirements of the applicable EMC standard EN 61000-4-5 (testing voltage 1kV
EMC wire/ground) are met.

14 Endress+Hauser
Cerabar PMP23

Performance characteristics of metallic process isolating


diaphragm
Reference operating • As per IEC 60770
conditions • Ambient temperature TA = constant, in the range of:+21 to +33 °C (+70 to +91 °F)
• Humidity φ = constant, in the range of 5 to 80 % rH
• Ambient pressure pA = constant, in the range of:860 to 1 060 mbar (12.47 to 15.37 psi)
• Position of measuring cell = constant, in range: horizontal ±1° (see also "Influence of the
installation position" section →  16)
• Zero based span
• Process isolating diaphragm material: AISI 316L (1.4435)
• Filling oil: NSF-H1 synthetic oil in accordance with FDA 21 CFR 178.3570
• Supply voltage: 24 V DC ±3 V DC
• Load: 320 Ω (at 4 to 20 mA output)

Measuring uncertainty for The smallest extended uncertainty of measurement that can delivered by our standards is:
small absolute pressure • in range 1 to 30 mbar (0.0145 to 0.435 psi): 0.4 % of reading
measuring ranges • in range < 1 mbar (0.0145 psi): 1 % of reading.

Influence of the installation →  16


position

Resolution Current output: min. 1.6 μA

Reference accuracy The reference accuracy contains the non-linearity [DIN EN 61298-2 3.11] including the pressure
hysteresis [DIN EN 61298-23.13] and non-repeatability [DIN EN 61298-2 3.11] in accordance with
the limit point method as per [DIN EN 60770].

Device % of the calibrated span to the maximum turn down

Reference accuracy Non-linearity Non-repeatability

PMP23 ±0.3 ±0.1 ±0.1

Overview of the turn down ranges →  10

Thermal change of the zero Measuring cell –10 to +85 °C (+14 to +185 °F) +85 to +100 °C (+185 to +212 °F)
output and the output span
% of the calibrated span for TD 1:1

<1 bar (15 psi) <1 <1.2

≥ 1 bar (15 psi) <0.8 <1

Long-term stability 1 year 5 years 8 years

% of URL

±0.2 ±0.4 ±0.45

Switch-on time ≤2 s

Installation
Installation conditions • No moisture may enter the housing when installing or operating the device, or when establishing
the electrical connection.
• Point the cable and connector downwards where possible to prevent moisture from entering (e.g.
rain or condensation water).

Endress+Hauser 15
Cerabar PMP23

Influence of the installation Any orientation is possible. However, the orientation may cause a zero point shift i.e. the measured
position value does not show zero when the vessel is empty or partially full.

A B C

A0024708

Type Process isolating diaphragm Process isolating diaphragm Process isolating diaphragm
axis is horizontal (A) pointing upwards (B) pointing downwards (C)

PMP23 Calibration position, no effect Up to +4 mbar (+0.058 psi) Up to –4 mbar (–0.058 psi)

Mounting location Pressure measurement

Pressure measurement in gases


Mount the device with shutoff device above the tapping point so that any condensate can flow into
the process.

A0021904

1 Device
2 Shutoff device

Pressure measurement in vapors


For pressure measurement in vapors, use a siphon. The siphon reduces the temperature to almost
ambient temperature. Mount the device with a shutoff device at the same height as the tapping
point.
Advantage:
only minor/negligible heat effects on the device.
Note the max. permitted ambient temperature of the transmitter!

3
A0024395

1 Device
2 Shutoff device
3 Siphon

16 Endress+Hauser
Cerabar PMP23

Pressure measurement in liquids


Mount the device with a shutoff device at the same height as the tapping point.

2 1
A0024399

1 Device
2 Shutoff device

Level measurement

• Always install the device below the lowest measuring point.


• Do not install the device at the following positions:
– In the filling curtain
– In the tank outlet
– In the suction area of a pump
– Or at a point in the tank which could be affected by pressure pulses from the agitator.

A0024405

Endress+Hauser 17
Cerabar PMP23

Environment
Ambient temperature range Device Ambient temperature range 1)

PMP23 –40 to +85 °C (–40 to +185 °F)

PMP23 Devices for hazardous areas: –40 to +70 °C (–40 to +158 °F)

1) Exception: the following cable is designed for an operating temperature range of


–25 to +70 °C (–13 to +158 °F): Product Configurator order code for "Accessory enclosed", option "RZ".

Storage temperature range –40 to +85 °C (–40 to +185 °F)

Climate class Device Climate class Note

PMP23 Class 4K4H Air temperature: –20 to +55 °C (–4 to +131 °F),
relative humidity: 4 to 100 %
satisfied according to DIN EN 60721-3-4 (condensation is possible)

Degree of protection Device Connection Climate class Option 1)

PMP23 Cable5 m (16 ft) IP66/68 2) NEMA type 4X/6P enclosure A

PMP23 Cable10 m (33 ft) IP66/68 2) NEMA type 4X/6P enclosure B

PMP23 Cable25 m (82 ft) IP66/68 2) NEMA type 4X/6P enclosure C

PMP23 M12 plug IP65/67 NEMA type 4X enclosure M


3)
PMP23 M12 plug made of metal IP66/69 NEMA type 4X enclosure N

PMP23 Valve plug ISO4400 M16 IP65 NEMA type 4X enclosure U

PMP23 Valve plug ISO4400 NPT ½ IP65 NEMA type 4X enclosure V

1) Product Configurator, order code for "Electrical connection"


2) IP 68 (1.83m H2O for 24 h)
3) Designation of the IP protection class according to DIN EN 60529. Previous designation "IP69K" according
to DIN 40050 Part 9 is no longer valid (standard withdrawn on November 1, 2012). The tests required by
both standards are identical.

Vibration resistance Test standard Vibration resistance

IEC 60068-2-64:2008 Guaranteed for 5 to 2000Hz: 0.05g2/Hz

Electromagnetic • Interference emission as per EN 61326-1 equipment B


compatibility • Interference immunity as per EN 61326-1 (industrial environment)
• NAMUR recommendation EMC (NE21)
• Maximum deviation: 1.5% for TD 1:1
For more details, refer to the Declaration of Conformity.

18 Endress+Hauser
Cerabar PMP23

Process
Process temperature range Device Process temperature range
for devices with metallic
process isolating diaphragm PMP23 –10 to +100 °C (+14 to +212 °F)

PMP23 At +135°C (+275 °F) for a maximum of one hour (device in operation but not within
Sterilization in place (SIP) measuring specification)

Applications with changes in temperature


Frequent extreme changes in temperatures can temporarily cause measuring errors. Internal
temperature compensation is faster the smaller the change in temperature and the longer the time
interval.
For further information please contact your local Endress+Hauser Sales Center.

Pressure specifications LWARNING


The maximum pressure for the measuring device depends on the lowest-rated element with
regard to pressure.
‣ For pressure specifications, see the "Measuring range" section and the "Mechanical construction"
section.
‣ The Pressure Equipment Directive (2014/68/EU) uses the abbreviation "PS". The abbreviation "PS"
corresponds to the MWP (maximum working pressure) of the measuring device.
‣ MWP (maximum working pressure): The MWP (maximum working pressure) is specified on the
nameplate. This value is based on a reference temperature of +20 °C (+68 °F) and may be applied
to the device for an unlimited period of time. Observe the temperature dependency of the MWP.
‣ OPL (over pressure limit): The test pressure corresponds to the over pressure limit of the sensor
and may only be applied temporarily to ensure that the measurement is within the specifications
and no permanent damage develops. In the case of sensor range and process connections where
the over pressure limit (OPL) of the process connection is smaller than the nominal value of the
sensor, the device is set at the factory, at the very maximum, to the OPL value of the process
connection. If you want to use the entire sensor range, select a process connection with a higher
OPL value.

Endress+Hauser 19
Cerabar PMP23

Mechanical construction
Design, dimensions Device height
The device height is calculated from
• the height of the electrical connection
• the height of the housing and
• the height of the individual process connection.
The individual heights of the components are listed in the following sections. To calculate the device
height simply add up the individual heights of the components. Where applicable also take into
consideration the installation distance (space that is used to install the device). You can use the
following table for this purpose:

Section Page Height Example

Electrical connection →  20 (A)


D
Housing height →  21 (B)

Process connection height →  22 (C) A


Installation distance - (D)

A0027268

Electrical connection  

A B C 35 (1.38) D
25 (1.0)

25 (1.0)

28 (1.1)
45 (1.77)
M12x1 M12x1

r ³ 102 (4.02)
52 (2.05)

A0024426 A0024427

A0024428

A0024429

Engineering unit mm (in)

1)
Position Description Material Weight kg (lbs) Device Option

A M12 plug IP65/67 Housing cap made of plastic 0.012 (0.03) PMP23 M
(Additional dimensions →  35) Plug connector with cable
can be ordered as an accessory →  35

B M12 plug IP66/67 Housing cap made of metal 0.030 (0.07) PMP23 In the case of Ex ec type of protection,
the housing cap is made of metal.
Can be ordered separately via option "N".

C M16 valve plug Plastic PPSU 0.060 (0.14) PMP23 U

C NPT ½ valve plug Plastic PPSU 0.060 (0.14) PMP23 V

D Cable5 m (16 ft) PUR (UL94V0) 0.280 (0.62) PMP23 A

D Cable10 m (33 ft) PUR (UL94V0) 0.570 (1.26) PMP23 B

D Cable25 m (82 ft) PUR (UL94V0) 1.400 (3.09) PMP23 C

1) Product Configurator, order code for "Electrical connection"

20 Endress+Hauser
Cerabar PMP23

Housing

64 (2.52)
A0025115

Engineering unit mm (in)

Device Material Weight kg (lbs)

PMP23 Stainless steel 316L 0.100 (0.22)

Endress+Hauser 21
Cerabar PMP23

Process connections with  


flush-mounted, metal
process isolating diaphragm Thread ISO 228 G

A B

36 36

7 (0.28)
48 (1.89)

48 (1.89)
7 (0.28)

29.5 (1.16)
26.8 (1.06)

ø25.4 (1)
22.3 (0.88)

10.9 (0.43)
ø29 (1.14)
8.8 (0.35)

ø30 (1.18) G 1" A


G 1" A ø39 (1.54)
A0021972 A0021973

Engineering unit mm (in). Diameter of process isolating diaphragm: 17.2 mm (0.68 in)

Item Description Seal Material Weight Approval Option 1)

kg (lbs)

A Thread ISO 228 G 1" A Metal joint 316L 0.270 (0.60) CRN WQJ
2)
B Thread ISO 228 G 1" A Seal established via O-ring. 316L 0.270 (0.60) EHEDG, 3A , CRN WSJ
VMQ O-ring is enclosed with QJ and QK accessories.

1) Product Configurator, order code for "Process connection"


2) EHEDG and 3A only in conjunction with weld-in adapter →  34

22 Endress+Hauser
Cerabar PMP23

Thread M24 x 1.5

7 (0.28)
ø24 (0.94)

32

41 (1.61)
4 (0.16)

13.8 (0.54)
M24x1.5

17 (0.67)
2 ø31.5 (1.24)

A0021969

Engineering unit mm (in). Diameter of process isolating diaphragm: 17.2 mm (0.68 in)

Description Seal Material Weight Approval Option 1)

kg (lbs)

M24 x 1.5 EPDM O-ring (2), pre-mounted 316L 0.150 (0.33) EHEDG, 3A, CRN X2J

M24 x 1.5 FKM O-ring (2), pre-mounted 316L 0.150 (0.33) EHEDG, 3A, CRN X3J

1) Product Configurator, order code for "Process connection"

Endress+Hauser 23
Cerabar PMP23

Hygienic connections

A ø35 (1.38) B ø48 (1.89)

28 (1.1)

28 (1.1)
10 (0.39)

10 (0.39)
3 (0.12)

3 (0.12)
ø27 (1.06) ø39 (1.54)
ø43.4 (1.71) ø55.4 (2.18)
A0021956
A0021957

C ø61 (2.4) D

4 (0.16)
28 (1.1)
ø4 (0.16)
28 (1.1)
11 (0.43)
3 (0.12)

ø51 (2.01) ø55 (2.17)


ø67.4 (2.65) A0021974

A0021958

Engineering unit mm (in). Diameter of process isolating diaphragm: 17.2 mm (0.68 in)

Item Description Approval Nominal pressure Material 1) Weight Approval Option 2)

PN kg (lbs)

A DIN 11851 DN 25 3A, EHEDG, CRN 40 316L 0.360 (0.79) - 1GJ

B DIN 11851 DN 40 3A, EHEDG, CRN 40 316L 0.520 (1.15) - 1JJ

C DIN 11851 DN 50 3A, EHEDG 25 316L 0.760 (1.68) CRN 1DJ

D SMS 1 ½" 3A, EHEDG, CRN 25 316L 0.440 (0.97) - 4QJ

1) Roughness of wetted surfaces Ra ≤0.76 μm (29.9 μin).


2) Product Configurator, order code for "Process connection"

24 Endress+Hauser
Cerabar PMP23

Hygienic connections

A B

28 (1.1)

28 (1.1)
ø50.5 (1.99) ø64 (2.52)
A0021976 A0021979

C ø57 (2.24) D ø75 (2.95)

28 (1.1)

28 (1.1)
12.3 (0.48)

19 (0.75)

12.3 (0.48)
ø84 (3.31)
19 (0.75)

ø66 (2.6)

A0021981 A0021980

Engineering unit mm (in). Diameter of process isolating diaphragm: 17.2 mm (0.68 in)

Item Description Approval Nominal pressure Material 1) Weight Option 2)

PN kg (lbs)

A Tri-Clamp ISO 2852 DN 25 – DN 38 (1 ½"), DIN32676 DN25-38 3A, EHEDG, CRN 40 316L 0.160 (0.35) 3CJ

B Tri-Clamp ISO 2852 DN 40 – DN 51 (2"), DIN32676 DN50, 3A, EHEDG, CRN 40 316L 0.230 (0.51) 3EJ
EHEDG, 3A

C Varivent F pipe DN25-32 3A, EHEDG, CRN 40 316L 0.350 (0.77) 41J

D Varivent N pipe DN40-162 3A, EHEDG, CRN 40 316L 0.630 (1.39) 42J

1) Roughness of wetted surfaces Ra ≤0.76 μm (29.9 μin).


2) Product Configurator, order code for "Process connection"

Endress+Hauser 25
Cerabar PMP23

Hygienic connections

ø43.8 (1.72)
ø34 (1.34)

7 (0.28)
18.8 (0.74)

57 (2.24)
45 (1.77)
ø43.5 (1.71)

A0021986

Engineering unit mm (in). Diameter of process isolating diaphragm: 17.2 mm (0.68 in)

Item Description Seal Approval Nominal pressure Material 1) Weight Option 2)

PN kg (lbs)

A Universal adapter 44 mm EPDM form seal, pre-mounted. 3A, EHEDG, CRN 10 316L 0.730 (1.61) 52J

1) Roughness of wetted surfaces Ra ≤0.76 μm (29.9 μin).


2) Product Configurator, order code for "Process connection"

26 Endress+Hauser
Cerabar PMP23

Materials in contact with NOTICE


process ‣ Device components in contact with the process are listed in the "Mechanical construction" and
"Ordering information" sections.

TSE Certificate of Suitability


The following applies to all device components in contact with the process:
• They do not contain any materials derived from animals.
• No additives or operating materials derived from animals are used in production or processing.

Process connections
• Endress+Hauser supplies a threaded connection made of stainless steel in accordance with AISI
316L (DIN/ EN material number 1.4404 or 1.4435). With regard to their stability-temperature
property, the materials 1.4404 and 1.4435 are grouped together under 13E0 in EN 1092-1: 2001
Tab. 18. The chemical composition of the two materials can be identical.
• "Clamp connections" and "Hygienic process connections": AISI 316L (DIN/EN material number
1.4435)

Process isolating diaphragm

Description Material

Metal process isolating diaphragm AISI 316L (DIN/EN material number 1.4435)

Seals
See the specific process connection.

Endress+Hauser 27
Cerabar PMP23

Materials not in contact with Housing


process

1 2
3
3 6
5
A0027299

4
A0025117

7 8 9
A0025116

Item number Component part Material

1 Valve plug • Seal: NBR


• Plug: PA
• Screw: V2A

2 Cable • Pressure screw: PVDF


• Seal: TPE-V
• Cable: PUR (UL 94 V0)

3 Design element PBT/PC

4 Connection PPSU

5 M12 plug Plastic: PPSU

6 M12 plug Metal 316L (1.4404)


Metal housing cap can be ordered as an option.
For Ex ec: metal housing cap

7 Pressure compensation element

8 Housing 316L (1.4404)

9 Nameplates Lasered directly onto the housing

Filling oil

Device Filling oil

PMP23 NSF-H1 synthetic oil in accordance with FDA 21 CFR 178.3570

Cleaning Device Description Option 1)

PMP23 Cleaned from oil+grease HA

1) Product Configurator, order code for "Service"

28 Endress+Hauser
Cerabar PMP23

Operability
Plug-on display PHX20 No display or other operation facility is required to operate the device. However, devices with a valve
(optional) plug can be fitted with the optional local display PHX20.

Description Option 1)

Plug-on display PHX20, IP65 RU

1) Product Configurator, order code for "Accessories"

A 1-line liquid crystal display (LCD) is used. The local display shows measured values, fault messages
and information messages. The device display can be turned in 90° steps. Depending on the
orientation of the device, it is therefore easy to read the measured values.

Technical data

Display: 4-digit, red LED display

Digit height: 7.62 mm; programmable decimal point setting

Display range: -1999 to 9999

Accuracy: 0.2% of the span ±1 digit

Electrical connection: To transmitter with 4 to 20 mA output and elbow plug DIN 43 650,
reverse polarity protection

Display power supply: Not required, powered automatically from the power loop

Voltage drop: ≤ 5 V (corresponds to load: max. 250 Ω)

Rate of conversion: 3 measurements per second

Damping: 0.3 to 20 s (configurable)

Data backup: Non-volatile EEPROM

Error message: • HI: overrange


• LO: below range

Programming: Via 2 keys, menu-guided, display range scaling, decimal point, damping,
error message

Degree of protection: IP 65

Influence of temperature on the 0.1% / 10 K


display:

Electromagnetic compatibility Interference emission as per EN 50081, interference immunity as per EN


(EMC): 50082

Permitted current load: Max. 60 mA

Ambient temperature: 0 to +60 °C (+32 to +140 °F)

Housing material: Pa6 GF30 plastic, blue


Front screen made from red PMMA

Order number: 52022914

Endress+Hauser 29
Cerabar PMP23

Certificates and approvals


CE mark The device meets the legal requirements of the relevant EC directives. Endress+Hauser confirms that
the device has been successfully tested by applying the CE mark.

RoHS The measuring system complies with the substance restrictions of the Restriction on Hazardous
Substances Directive 2011/65/EU (RoHS 2).

RCM-Tick marking The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.

A0029561

EAC conformity The PMP21 and PMP23 devices meet the legal requirements of the applicable EAC directives. These
are listed in the corresponding EAC Declaration of Conformity along with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark.

Approval CSA C/US General Purpose

Safety Instructions (XA) Safety Instructions (XA) are supplied with the device depending on the approval. These instructions
are an integral part of the Operating Instructions.

Device Directive Documentation Option 1)

PMP23 ATEX II 1/2G Ex ia IIC T4 Ga/Gb XA01271P BA

PMP23 FM IS Cl. I, Div.1 Gr. A-D T4 XA01321P FA

PMP23 CSA C/US IS Cl. I Div. 1 Gr. A-D XA01322P CB

PMP23 EAC Ex ia IIC T4 Ga/Gb XA01540P GA

PMP23 IEC Ex ia IIC T4 Ga/Gb XA01271P IA

PMP23 NEPSI Ex ia IIC T4 XA01363P NA

PMP23 TIIS Ex ia IIC T4 In preparation TA

1) Product Configurator, order code for "Approval"

The nameplate provides information on the Safety Instructions (XA) that are relevant for the
device.

Suitability for hygienic All materials in contact with foodstuffs comply with framework regulation (EC) 1935/2004. The
processes device is available with hygienic process connections (overview: see order code).

30 Endress+Hauser
Cerabar PMP23

LCAUTION
Contamination in the process!
Risk of contamination if incorrect seals and parts are used!
‣ To avoid the risk of contamination, when installing the device comply with the design principles
of EHEDG, Guideline 37 "Hygienic Design and Application of Sensors" and Guideline 16 "Hygienic
Pipe Couplings".
‣ Suitable assemblies and seals must be used to ensure hygienic design in accordance with 3-A SSI
and EHEDG specifications.
‣ The leak-proof connections can be cleaned with the cleaning methods typical of this industry
(CIP and SIP). Attention must be paid to the pressure and temperature specifications of the
sensor and process connections for CIP and SIP processes (clean in place/sterilize in place).

The seamless connections can be cleaned of all residue using any of the typical cleaning
methods within this industry.

74 -

TYPE EL
CLASS I
OCTOBER 2014

A0025304

Pressure Equipment Pressure equipment with allowable pressure ≤ 200 bar (2 900 psi)
Directive 2014/68/EU (PED)
Pressure equipment (with a maximum allowable pressure PS ≤ 200 bar (2 900 psi)) can be classified
as pressure accessories in accordance with Pressure Equipment Directive 2014/68/EU. If the
maximum allowable pressure is ≤ 200 bar (2 900 psi) and the pressurized volume of the pressure
equipment is ≤ 0.1 l, the pressure equipment is subject to the Pressure Equipment Directive (cf.
Pressure Equipment Directive 2014/68/EU, Article 4, point 3). The Pressure Equipment Directive
only requires that the pressure equipment shall be designed and manufactured in accordance with
the "sound engineering practice of a Member State".

Reasons:
• Pressure Equipment Directive (PED) 2014/68/EU Article 4, point 3
• Pressure equipment directive 2014/68/EU, Commission's Working Group "Pressure", Guideline
A-05 + A-06

Note:
A partial examination shall be performed for pressure instruments that are part of safety equipment
for the protection of a pipe or vessel from exceeding allowable limits (safety accessory in accordance
with Pressure Equipment Directive 2014/68/EU, Article 2, point 4).

Manufacturer declarations Depending on the desired configuration, the following documents can be ordered additionally with
the device:
• FDA conformity
• TSE-free: materials free from animal origin
• Regulation (EC) No. 2023/2006 (GMP)
• Regulation (EC) No. 1935/2004 on materials and articles intended to come into contact with food

Downloading the Declaration of Conformity


http://www.endress.com/en/download

Endress+Hauser 31
Cerabar PMP23

1
3

A0031778

1. Select "Approvals & Certificates"


2. Select "Manufact. Declaration"
3. Enter the required product code
4. Click "Search"
The available downloads are displayed.

Other standards and The applicable European guidelines and standards can be found in the relevant EU Declarations of
guidelines Conformity. The following were also applied:

DIN EN 60770 (IEC 60770):


Transmitters for use in industrial process control systems Part 1: Methods for performance
evaluation
Methods for evaluating the performance of transmitters for control and regulation in industrial
process control systems.

DIN 16086:
Electrical pressure measuring instruments, pressure sensors, pressure transmitters, pressure
measuring instruments, concepts, specifications on data sheets
Procedure for writing specifications in data sheets for electrical pressure measuring instruments,
pressure sensors and pressure transmitters.

EN 61326-X:
EMC product family standard for electrical equipment for measurement, control and laboratory use.

EN 60529:
Degrees of protection provided by enclosures (IP code)

NAMUR - User association of automation technology in process industries.


NE21 - Electromagnetic Compatibility (EMC) of Industrial Process and Laboratory Control
Equipment.
NE43 - Standardization of the Signal Level for the Failure Information of Digital Transmitters.
NE44 - Standardization of Status Indicators on PCT Instruments with the Help of Light Emitting
Diodes
NE53 - Software of Field Devices and Signal-processing Devices with Digital Electronics

CRN approval A CRN approval is available for some device versions. A CRN-approved process connection with a
CSA approval must be ordered for a CRN-approved device. The CRN-approved devices are assigned
the registration number 0F18141.5C.
Ordering information: Product Configurator, order code for "Process connection" (the CRN process
connections are indicated appropriately in the "Mechanical construction" section.)

32 Endress+Hauser
Cerabar PMP23

Calibration unit Description Option 1)

Sensor range; % A

Sensor range; mbar/bar B

Sensor range; kPa/MPa C

Sensor range; psi F

Customer-specific; see additional spec. J

1) Product Configurator, order code for "Calibration; unit"

Calibration Description Option 1)

3-point certificate of calibration F3

1) Product Configurator order code for "Calibration"

Inspection certificates Device Description Option 1)

PMP23 3.1 Material documentation, wetted metal parts, EN10204-3.1 inspection certificate JA

PMP23 Surface finish measurement ISO4287/Ra, wetted metal parts, inspection certificate KB

1) Product Configurator, order code for "Test, Certificate"

Additional approval Device Description Option 1)

PMP23 EHEDG, certificate copy L1

PMP23 3A, certificate copy L2

PMP23 Declaration of Conformity EC1935/2004, wetted parts L3

1) Product Configurator, order code for "Additional approval"

Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field ->
Open product page -> The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop

Scope of delivery • Measuring device


• Optional accessories
• Brief Operating Instructions
• Certificates

Endress+Hauser 33
Cerabar PMP23

Accessories
Weld-in adapter Various weld-in adapters are available for installation in vessels or pipes.

Device Description Option 1) Order number

PMP23 Weld-in adapter M24, d=65, 316L PM 71041381

PMP23 Weld-in adapter M24, d=65, 316L 3.1 EN10204-3.1 PN 71041383


material, inspection certificate

PMP23 Weld-in adapter G1, 316L, conical metal joint QE 52005087

PMP23 Weld-in adapter G1, 316L, 3.1, conical metal joint, QF 52010171
EN10204-3.1 material, inspection certificate

PMP23 Weld-in tool adapter G1, brass QG 52005272

PMP23 Weld-in adapter G1, 316L, silicone O-ring seal QJ 52001051

PMP23 Weld-in adapter G1, 316L, 3.1, silicone O-ring seal, QK 52011896
EN10204-3.1 material, inspection certificate

PMP23 Weld-in adapter Uni D65, 316L QL 214880-0002

PMP23 Weld-in adapter Uni D65, 316L 3.1 EN10204-3.1 QM 52010174


material, inspection certificate

PMP23 Weld-in tool adapter Uni D65/D85, brass QN 71114210

PMP23 Weld-in adapter Uni D85, 316L QP 52006262

PMP23 Weld-in adapter Uni D85, 316L 3.1 EN10204-3.1 QR 52010173


material, inspection certificate

1) Product Configurator, order code for "Enclosed accessories"

If installed horizontally and weld-in adapters with a leakage hole are used, ensure that the leakage
hole is pointing down. This allows leaks to be detected as quickly as possible.

Process adapter M24 The following process adapters can be ordered for the process connections with order option X2J and
X3J:

Device Description Order number Order number with inspection certificate 3.1 EN10204

PMP23 Varivent F DN32 PN40 52023996 52024003

PMP23 Varivent N DN50 PN40 52023997 52024004

PMP23 DIN11851 DN40 52023999 52024006

PMP23 DIN11851 DN50 52023998 52024005

PMP23 SMS 1½" 52026997 52026999

PMP23 Clamp 1½" 52023994 52024001

PMP23 Clamp 2" 52023995 52024002

Plug-on display PHX20 →  29

34 Endress+Hauser
Cerabar PMP23

M12 plug connectors Connector Degree of protection Material Option 1) Order


number

M12 IP67 • Union nut: Cu Sn/Ni R1 52006263


(self-terminated connection • Body: PBT
at M12 plug) • Seal: NBR

(0.8)
ø20 53 (2.09)
A0024475

M12 90 degrees IP67 • Union nut: GD Zn/Ni RZ 52010285


with 5m (16 ft) cable • Body: PUR
• Cable: PVC
(1.1)
28

³40 (1.57)
A0024476

M12 90 degrees IP67 • Union nut: GD Zn/Ni RM 71114212


(self-terminated connection • Body: PBT
at M12 plug) • Seal: NBR

28
(1.1)
(1.38)
35

20 (0.79)
A0024478

M12 90 degrees IP69 2) • Union nut: 316L RW 52024216


with 5m (16 ft) cable (1.4435)
(terminated at one end) • Body and cable:
PVC and PUR
(1.1)
28

³40 (1.57)
A0024477

1) Product Configurator, order code for "Enclosed accessories"


2) Designation of the IP protection class according to DIN EN 60529. Previous designation "IP69K" according
to DIN 40050 Part 9 is no longer valid (standard withdrawn on November 1, 2012). The tests required by
both standards are identical.

Endress+Hauser 35
Cerabar PMP23

Documentation
Field of Activities Pressure measurement, powerful instruments for process pressure, differential pressure, level and
flow:
FA00004P/00/EN

Technical Information • TI00241F/00/EN: EMC test procedures


• TI00426F/00/EN: Weld-in adapters, process adapters and flanges (overview)

Operating Instructions BA01271P/00/EN

Brief Operating Instructions KA01164P/00/EN

Safety Instructions (XA) Safety Instructions (XA) are supplied with the device depending on the approval. These instructions
are an integral part of the Operating Instructions.

Device Directive Documentation Option 1)

PMP23 ATEX II 1/2G Ex ia IIC T4 Ga/Gb XA01271P BA

PMP23 FM IS Cl. I, Div.1 Gr. A-D T4 XA01321P FA

PMP23 CSA C/US IS Cl. I Div. 1 Gr. A-D XA01322P CB

PMP23 EAC Ex ia IIC T4 Ga/Gb XA01540P GA

PMP23 IEC Ex ia IIC T4 Ga/Gb XA01271P IA

PMP23 NEPSI Ex ia IIC T4 XA01363P NA

PMP23 TIIS Ex ia IIC T4 In preparation TA

1) Product Configurator, order code for "Approval"

The nameplate provides information on the Safety Instructions (XA) that are relevant for the
device.