Liquicap M FMI51, FMI52: Technical Information
Liquicap M FMI51, FMI52: Technical Information
Liquicap M FMI51, FMI52: Technical Information
Application The Liquicap M compact transmitter is used for the continuous level measurement of liquids. Thanks to its robust and tried-and-tested construction (self-sealing cone), the probe can be used both in vacuums and in overpressure up to 100 bar. The sealing and insulation materials used allow operating temperatures of 80 C to +200 C in the medium container. The measurement is independent of the dielectric constant (DK) as of a liquid conductivity of 100 S/cm. In this way, various liquids can be measured without the need for recalibration. Used in conjunction with Fieldgate (remote measured value interrogation using Internet technology), Liquicap M provides an ideal solution for inventorying materials and optimizing logistics (inventory control). Your benefits No calibration necessary for media with a conductivity of 100 S/cm and higher. The probes are calibrated to the ordered probe length on leaving the factory (0 % to 100 %). This makes easy and fast commissioning possible. Menu-guided local configuration via plain text display (optional) Universal application thanks to wide range of certificates and approvals Use also in safety systems requiring functional safety to SIL2 in accordance with IEC 61508 Material in contact with the process made of corrosion-resistant material and FDA-listed materials for wetted parts Two-stage overvoltage protection against discharge from the container (gas discharger + protective diodes) Electronics can be switched for media forming buildup Short measured value reaction time No need for recalibration after replacing electronics Automatic monitoring of electronics Monitors damage to insulation and rod breaking or rope tearing Suitable for interface measurement
TI401F/00/en
Table of contents
Function and system design. . . . . . . . . . . . . . . . . . . . . 3
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 System integration via Fieldgate . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Performance characteristics. . . . . . . . . . . . . . . . . . . . 25
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Influence of ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . Startup settling time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measured value reaction time . . . . . . . . . . . . . . . . . . . . . . . . . Integration time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accuracy of factory calibration. . . . . . . . . . . . . . . . . . . . . . . . . . Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 25 25 25 25 26 26 26
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Electronic inserts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating concept with FEI50H display (optional) . . . . . . . . . . . Display (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 27 27 28 29
Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 30
Liquicap M FMI51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Liquicap M FMI52 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 14
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Technical data (probe) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Protective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shortening kit for FMI52 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Commubox FXA191, FXA195 HART . . . . . . . . . . . . . . . . . . . . . Surge arrester HAW569 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weld-in adapter for universal adapter . . . . . . . . . . . . . . . . . . . . . Weld-in adapter for G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weld-in adapter for G 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 37 37 37 38 38 38 38
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Measuring range with electronic insert FEI50H (4 to 20 mA HART) FEI57C (PFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Measuring condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Supplementary Documentation . . . . . . . . . . . . . . . . . 39
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Patents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 39 39 40
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 HART residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 HART noise (FEI50H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Endress+Hauser
Note! A ground tube is used as a counterelectrode for containers made of nonconductive materials.
1 2 3
CE
CA
CA
L00-FMI5xxxx-15-05-xx-xx-001
R: Conductivity of liquid C: Capacitance of liquid CA: Initial capacitance (probe not covered ) CE: Final capacitance (probe covered): change in capacitance C: Change in capacitance
Function The selected electronic insert of the probe (e.g. FEI50H 4 to 20 mA HART) converts the measured change in capacitance of the liquid to a signal in proportion to the level (e.g. 4 to 20 mA) and thus makes it possible to display the level. Phase-selective measurement The electronic evaluation of the container capacitance works along the principle of phase-selective measurement. In this process, the amount of alternating current and the phase shift between the voltage and current is measured. With these two characteristic quantities, the capacitive idle current can be calculated by the medium capacitor and the real current by the medium resistance. Conductive buildup stuck to the probe rod/rope acts like additional medium resistance and causes an error in measurement. As the size of the medium resistance can be determined with phase-selective measurement, an algorithm is used to compensate the buildup on the probe. Thus, Liquicap M has buildup compensation.
Endress+Hauser
Interface measurement The calibration values for empty and full calibration can be calculated with the ToF Tool configuration and service software from Endress+Hauser.
3.) 2.)
1.)
L00-FMI5xxxx-15-05-xx-xx-000
1.) Water, for example (the medium must be conductive 100 S/cm) 2.) Emulsion 3.) Oil, for example (nonconductive medium < 1 S/cm)
A certain and definite measured value is ensured even if the emulsion layer is of varying thickness. It is always the average value of the emulsion film measured. Measuring system
Note! The make-up of the measuring system depends on the electronic insert selected. PFM output (FEI57C) The complete measuring system consists of: The capacitive Liquicap M FMI51 or FMI52 level probe The FEI57C electronic insert A transmitter power supply unit e.g. FMC671, FMC672, FMC661, FMX570 (order stop 2006)
Note! The twin-core feeder is also used for PFM signal transmission. In combination with a power supply unit the FEC57C will only run in a 1-channel-mode and without an automatic alignment correction.
EX
EX
FMC671Z
L00-FMI5xxxx-14-00-06-xx-001
Level measurement
Endress+Hauser
4 to 20 mA output with HART protocol (FEI50H) The complete measuring system consists of: The capacitive Liquicap M FMI51 or FMI52 level probe The FEI50H electronic insert A transmitter power supply unit (e.g. RN221N, RNS221, RMA421, RMA422)
Note! DC voltage must be supplied to the electronic insert. The twin-core feeder is also used for HART protocol signal transmission.
Commubox FXA191/195
EX
EX
Transmitter power supply unit e.g. RMA422 or RN221N (with integrated communication resistor)
#%&
Measured Value
64.50
+
352 mbar 0 C
HELP
SAVE
Page Up
Bksp
Delete
Page On
ABC
DEF
1
Copy GHI
2
Paste JKL
3
Hot Key MNO
4
PQRS
5
Insert TUV
6
+ Hot Key W XY Z
FXA191/195 or DXR375
7
,()
8
_<>
9
+*/
375
FIELD COMMUNICATOR
L00-FMI5xxxx-14-00-06-en-001
Local operation Standard - via keys and switches on the electronic insert Optional - via display and operating module Remote operation With HART handheld terminal DXR375 With a personal computer, Commubox FXA191, FXA195 and the operating programs ToF Tool FieldTool Package or FieldCare.
Note! ToF Tool and FieldCare are graphic operating programs for measuring devices from Endress+Hauser. They are used to support commissioning, data backup, signal analysis and documentation of the measuring point.
Endress+Hauser
Vendor managed inventory The remote interrogation of tank or silo levels via Fieldgate enables suppliers of raw materials to gather information about the current inventories of their regular customers at any time and, for example, take this into account in their own production planning. The Fieldgate monitors the configured level limits and automatically triggers the next order as required. Here, the range of possibilities ranges from simple requisitioning by e-mail through to fully automatic order processing by incorporating XML data into the planning systems on both sides. Remote maintenance of measuring systems Not only does Fieldgate transmit the current measured values, it also alerts the standby personnel responsible by e-mail or SMS as required.- Service technicians can diagnose and configure the connected HART devices remotely in the event of an alarm or also for routine checks. All that is required for this is the appropriate HART operating software (e.g. ToF Tool - FieldTool Package, FieldCare, ...) for the connected device. Fieldgate forwards the information transparently. In this way, all options of the operating software in question are available remotely. By using remote diagnosis and remote configuration some onsite service operations can be avoided and all others can at least be planned and prepared better.
Remote interrogation Remote configuration/diagnostics via HART client: - ToF Tool - FieldTool Package - FieldCare ...
e.g. RNS221
e.g. 2 x RN221N-B
ENDRESS+HAUSER RN 221N
ENDRESS+HAUSER RN 221N
Channel 1
Channel 2
Channel 1
Channel 2
L00-FMI5xxxx-14-00-06-en-002
Endress+Hauser
L00-FMI5xxxx-11-06-xx-xx-001
L00-FMI5xxxx-11-06-xx-xx-002
Endress+Hauser
For information on ordering, please refer also to the "Ordering information" => "Probe design" on Page 30 ff.
EX
Zone 1
EX
Zone 0
L4 6 m
L1
L00-FMI5xxxx-14-00-06-xx-002*
Note! The maximum connection length between the probe and the separate housing is 6 m (L4). The desired length must be quoted when ordering a Liquicap M with a separate housing. The overall length L = L1 + L4 may not exceed 10 m. If the connecting cable is to be shortened or guided through a wall, it has to be separated from the process connection. See "Documentation" => "Operating Instructions". Extension heights Housing side: wall mounting
~61 mm
B
Sensor side
r 100 mm
H1
~41 mm
~41 mm
H1
r 100 mm
L00-FMI5xxxx-06-05-xx-xx-049
Note! The cable has a bending radius of r 100 mm which may not be undershot! B (mm) H1 (mm) H2 (mm) Polyester housing F16 76 172 191 Stainless steel housing F15 Aluminum housing F17 64 65 166 177 205 206
Endress+Hauser
H3
Rod probes, rope probes G, G, G1, NPT, NPT, NPT1 Clamp 1, 1 bar 25 16 D (mm) 38 38 H3 (mm) 103 122
bar 100 16 16
D (mm) 50 50 50
Note! Connecting cable: 10.5 mm Outer jacket: silicone, mechanical resistance Wall holder unit
86 +1.1 0.8 mm
28 mm 6.2 mm
3 mm
70 +1.2 0.8 mm
L00-FMI5xxxx-06-05-xx-xx-065
Note that the wall holder unit first has to be screwed to the separate housing before you can use it as a drilling template. The distance between the holes is reduced by screwing it to the separate housing.
Endress+Hauser
DIN EN 60068-2-38/IEC 68-2-38: test Z/AD DIN EN 60068-2-64/IEC 68-2-64: 20 to 2000 Hz, 1 (m/s2)2/Hz Housing: When cleaning, make sure that the cleaning agent used does not attack or corrode the housing surface or seals. Probe: Depending on the application, buildup (contamination and soiling) can form on the probe rod. A high degree of material buildup can affect the measurement result. If the medium tends to create a high degree of buildup, regular cleaning is recommended. When cleaning, it is important to make sure that the insulation of the probe rod is not damaged. If cleaning agents are used make sure the material is resistant to them!
Interference emission to EN 61326, Electrical Equipment Class B Interference immunity to EN 61326, Annex A (Industrial) and NAMUR Recommendation NE 21 (EMC) If only the analog signal is to be used, a usual commercial instrument cable is sufficient. If the superimposed communication signal (HART 4 to 20 mA) is used, a shielded cable must be used. A usual commercial cable can be used for PFM.
Shock resistance
Ta C
Ta
80 60
+80/ +70
TP
40
+200/ +38
20
40
60
80
100
120 140
TP C
Note! Restriction on Ta 40 C for F16 polyester housing. Only relevant for FMI51! If additional option B is selected (free from paint-wetting impairment substances), the minimum ambient temperature Ta is 40 C.
10
Endress+Hauser
Ta
*
Ta
C
120 100
TP
80 60 40
20 0 80 60 40 20 20 40 60
L00-FMI5xxxx-05-05-xx-xx-011
20
40
60
80
100
120 140
TP C
!
Pressure and temperature derating
Note! The maximum connection length between the probe and the separate housing is 6 m (L4). The desired length must be quoted when ordering a Liquicap M with a separate housing. If the connecting cable is to be shortened or guided through a wall, it has to be separated from the process connection. See "Documentation" => "Operating Instructions". For process connections "; " and 1" Rod insulation: PTFE Rope insulation: FEP, PFA Note! See also "Process connections" on Page 16 ff.
Pp bar 40 +50/ +25 +200/ +2 0 20 40 60 80 100 120 140 160 180 +200/ 1
20 0 80 60 40 20
TP C
L00-FMI5xxxx-05-05-xx-xx-008
Note! In the case of flange process connections, the maximum pressure is limited by the nominal pressure of the flange.
Endress+Hauser
11
For process connections 1" Rod insulation: PTFE, PFA Rope insulation: FEP, PFA
TP C
L00-FMI5xxxx-05-05-xx-xx-010
TP C
L00-FMI5xxxx-05-05-xx-xx-012
Probe 10 mm (including insulation) 1 to 25 bar (observe dependencies: process temperature and process connection from Page 10 and Page 16 ff.) Probe 16 mm / 22 mm (including insulation) 1 to 100 bar (observe dependencies: process temperature and process connection from Page 10 and Page 16 ff.)
12
Endress+Hauser
State of aggregation
Conductivity [S/cm]
The measuring accuracy is independent of the conductivity and DK value (dielectric constant) 0 %...100 % factory calibration
10
10 10
e.g. Water-based liquids, aqueous solutions of salts, acids and alkalis, aqueous dispersions and emulsions, wastewater, electrolytes, beverages
The measuring accuracy depends on the DC value and the conductivity of the medium. Measurement not recommendable, select therefore different measurement principle. 0% factory calibration
10 1 10
1
10 10
e.g. Hydrocarbons with a water content under 0.1%, petrols, oils, solvents
L00-FMI5xxxx-05-06-xx-en-000
Typical DK values Air Vacuum General liquefied gases Gasoline Cyclohexane Diesel fuel General oils Methyl ether Butanol Ammonia Latex Ethanol Caustic soda Acetone Glycerine Water
Endress+Hauser
13
Overview
14
Polyester housing F16 Aluminium housing F17 Stainless steel housing F15 Aluminium housing T13
with a separate connection compartment and gas-tight process seal with a gas-tight process seal
Display
Display holder
Electronics
Mechanical construction
Thread (G, NPT; G, NPT; G1, NPT1) Hygiene connections Hose gland (DN50 PN40)
Thread (G, NPT; G1, NPT1; G1, NPT1) Flanges (EN, ANSI, JIS)
Endress+Hauser
L00-FMI5xxxx-03-05-xx-en-001
Rod/rope probe
Rod/rope probe
Housing
Note! High cover for housing with display. Polyester housing F16
85 max. 76
approx. 116
approx. 97
L00-FMI5xxxx-06-05-xx-en-001
76
max. 64
approx. 134
approx. 95
L00-FMI5xxxx-06-05-xx-en-003
max. 65 80 max. 60
approx. 134
approx. 105
L00-FMI5xxxx-06-05-xx-en-002
max. 65 80 max. 60
approx. 147
approx. 118
L00-FMI5xxxx-06-05-xx-en-000
Aluminum housing T13 With separate connection compartment and gas-tight process seal
max. 65
max. 97
approx. 147
approx. 135
L00-FMI5xxxx-06-05-xx-en-004
Endress+Hauser
15
H2 H1
H2 H1
H2 H1
L00-FMI5xxxx-06-05-xx-xx-044
L00-FMI5xxxx-06-05-xx-xx-046
H2 H1
L00-FMI5xxxx-06-05-xx-xx-045
L00-FMI5xxxx-06-05-xx-xx-048
H2 H1
L00-FMI5xxxx-06-05-xx-xx-047
Order code FMI51, FMI52 H1 (for electronic inserts without display) H2 (for electronic inserts with display)
144 163
142 181
152 181
194 223
202 214
Process connections
Thread G
AF
Thread NPT
AF
Tri-Clamp
H2 H1
H2 H1
H1
L00-FMI5xxxx-06-05-xx-en-007
L00-FMI5xxxx-06-05-xx-en-008
L00-FMI5xxxx-06-05-xx-xx-040
H1
L00-FMI5xxxx-06-05-xx-xx-041
(DIN ISO228/I) Rod probes 10, rope probes For pressures up to Version / order code 25 bar G / GCJ G / GDJ G1 / GEJ H1 = 38 H2 = 19 AF = 41 With elastomer flat seal
(ANSI B 1.20.1)
(DIN11851)
(ISO2852)
Dimensions
H1 = 57
Surface roughness Additional information Rod probes 16, rope probes For pressures up to Version / order code
0.8 m
0.8 m EHEDG*
25 bar
100 bar
40 bar
Dimensions
H1 = 41 H2 = 25 AF = 55
0.8 m
0.8 m
0.8 m
* EHEDG: Certificate only applies for probes without an inactive length and with a fully insulated probe rod.
16
Endress+Hauser
Thread G Rod probes 22, rope probes For pressures up to Version / order code Dimensions 50 bar G1 / GGJ H1 = 85 H2 = 25 AF = 55 With elastomer flat seal
Thread NPT
Tri-Clamp
0.8 m
0.8 m
Flanges
Hygiene connection
Hygiene connection
Hygiene connection
H2 H1
H2 H1
H1
AF
AF
L00-FMI5xxxx-06-05-xx-xx-042
L00-FMI5xxxx-06-05-xx-en-009
L00-FMI5xxxx-06-05-xx-en-010
H1
L00-FMI5xxxx-06-05-xx-xx-043
(EN1092-1) (ANSI B 16.5) (JIS B2220) Rod probes 10, rope probes For pressures up to Version / order code Max. 25 bar (depends on flange) EN ANSI JIS / B** / A** / K**
With flush-mounted seal With flush-mounted seal Adapter 44 mm with flush-mounted seal
25 bar G / GQJ
25 bar G1 / GWJ
Dimensions
H1 = 57
H1 = 31 H2 = 26 AF = 41
H1 = 30 H2 = 27 AF = 41
Additional information
Welding neck Welding neck see "Accessories"Page 37 see "Accessories"Page 37 EHEDG* EHEDG*
Rod probes 16, rope probes For pressures up to Max. 100 bar (depends on flange) 16 bar (tightening torque 10 Nm) Universal adapter / UPJ
EN ANSI JIS
Dimensions Additional information Rod probes 22, rope probes For pressures up to Version / order code
* EHEDG: Certificate only applies for probes without an inactive length and with a fully insulated probe rod. ** Wildcard for nominal diameter and permitted process pressure Note! Only use clad flanges for aggressive liquids!
Endress+Hauser
17
Note! The active probe rod is always fully insulated (dimension L1). Total length of probe from sealing surface: L = L1 + L3 Thickness of insulation for probe rod 10 mm = 1 mm; 16 mm = 2 mm; 22 mm = 2 mm For conductive liquids (>100 S/cm), the probe is calibrated at the factory to the probe length ordered (0 % to 100 %). For nonconductive liquids (<1 S/cm), 0% calibration is performed at the factory. Only the 100% calibration has to be carried out on site. The isolation is at the probe point approx. 10 mm welded. This range is not part of the active measuring range.
Rod probe
NPT
L1/L3
L1/L3
L3
L3
L1
L1
L1
L1
L00-FMI5xxxx-06-05-xx-xx-061.eps
Total length (L) Active rod length (L1) Inactive rod length (L3) Probe rod diameter Diameter of ground tube with or without inactive length Lateral loading capacity (Nm) at 20 C For use in agitating tanks For conductive liquids > 100 S/cm For nonconductive liquids < 100 S/cm For aggressive liquids For high-viscosity liquids For use in plastic tanks For use in mounting nozzles In the event of condensate on tank ceiling
100 to 6000 100 to 4000 100 to 2000 10 / 16 22 / 43 < 40 /< 300 -/X X X X X
L1
L00-FMI5xxxx-06-05-xx-xx-051
L3
up to 1 m: 0...5 mm
1 m up to 3 m: 0...10 mm
3 m up to 6 m: 0...20 mm
18
Endress+Hauser
Note! The active probe length is always fully insulated (dimension L1). Total length of probe from sealing surface: L = L1 + L3 All rope probes are prepared for tensioning in containers (tensioning weight with anchor hole) For conductive liquids (>100 S/cm), the probe is calibrated at the factory to the probe length ordered (0 % to 100 %). For nonconductive liquids (<1 S/cm), 0% calibration is performed at the factory. Only the 100% calibration has to be carried out on site. Not suitable for agitator tanks, high-viscosity liquids and plastic tanks. Thickness of rope insulation 0.75 mm In the range of the anchor weight the measurement is not linear.
Rope probe
NPT
L1/L3
L1/L3
L3
L1
L1
120
120
L1
L00-FMI5xxxx-06-05-xx-xx-061.eps
L3 120
L00-FMI5xxxx-06-05-xx-xx-036
Total length (L) Active rope length (L1) Inactive length (L3) Probe rope diameter Anchor weight diameter Anchor hole diameter Tensile loading capacity (N) of probe rope at 20 C For conductive liquids > 100 S/cm For nonconductive liquids < 100 S/cm For aggressive liquids For use in mounting nozzles In the event of condensate on tank ceiling
X X X X = recommended
X X X X
X X X X X
up to 1 m: 0...10 mm
Endress+Hauser
19
Capacitance values of probe Basic capacitance: approx. 18 pF Additional capacitance Mount the probe with a minimum distance of 50 mm from a conductive container wall: Probe rod: approx. 1.3 pF/100 mm in air Probe rope: approx. 1.0 pF/100 mm in air Fully insulated probe rod in water: Approx. 38 pF/100 mm (16 mm rod) Approx. 45 pF/100 mm (10 mm rod) Approx. 50 pF/100 mm (22 mm rod) Insulated probe rope in water: approx. 19 pF/100 mm Rod probe with ground tube: Insulated probe rod: in air approx. 6.4 pF/100 mm Insulated probe rod: in water approx. 38 pF/100 mm (16 mm rod) Insulated probe rod: in water approx. 45 pF/100 mm (10 mm rod) Probe lengths for continuous measurement in conductive liquids With FEI57C, FEI50H Rod probe (range 0 to 2000 pF for 4000 mm) Rope probe < 6 m (range 0 to 2000 pF) Rope probe > 6 m (range 0 to 4000 pF)
Weight
With F15, F16, F17 or F13 housing approx. 4.0 kg + Flange weight + Probe rod 0.5 kg/m (with 10 mm probe rod) or + Probe rod 1.1 kg/m (with 16 mm probe rod) or + Probe rope 0.04 kg/m (with rope probes) With T13 housing approx. 4.5 kg + Flange weight + Probe rod 0.5 kg/m (with 10 mm probe rod) or + Probe rod 1.1 kg/m (with 16 mm probe rod) or + Probe rope 0.04 kg/m (with rope probes)
Material
Housing Aluminum housing F17, F13, T13: GD-Al Si 10 Mg, DIN 1725, with plastic coating (blue/gray) Polyester housing F16: PBT-FR fiberglass reinforced polyester (blue/gray) Stainless steel housing F15: corrosion-resistant steel 316L (14435), uninsulated Housing cover and seals Housing cover and seals: Aluminum housing F17, F13, T13: EN-AC-AlSi10Mg, plastic-coated cover seal: EPDM Polyester housing F16: cover made of PBT-FR or with cover with sight glass made of PA12 cover seal: EPDM Stainless steel housing F15: AISI 316L cover seal: silicone Process connection seal Sealing ring for process connection G, G, G1, G1 : Elastomer fiber, asbestos-free, resistant to oils, solvents, steam, weak acids and alkalis; To 300 C and to 100 bar Probe material Probe rod, ground tube, process connection, inactive length, tensioning weight for rope probe: 1.4435 (316L) Probe rope: 1.4401 (AISI 316) Probe insulation: PFA or PTFE (in conformity with FDA) Rope insulation: PFA or FEP (in conformity with FDA)
20
Endress+Hauser
Input
Measured variable Continuous measurement of change in capacitance between probe rod and container wall or ground tube, depending on the level of a liquid. Measuring frequency: 500 kHz Span: C = 25 to 4000 pF recommended (2 to 4000 pF possible) Final capacitance: CE = max. 4000 pF Adjustable initial capacitance: CA = 0 to 2000 pF (< 6 m probe length) CA = 0 to 4000 pF (< 6 m probe length) Input signal Probe covered => high capacitance Probe not covered => low capacitance Measuring range L1 possible from the tip of the probe to the process connection. Particularly suited for small containers.
L3
Measuring condition
Note! When installing in a nozzle, use inactive length (L3). The 0 %, 100 % calibration can be inverted.
L1
100 %
0%
L00-FMI5xxxx-15-05-xx-xx-002
Endress+Hauser
21
Output
Output signal FEI50H (4 to 20mA/HART Version 5.0) 3.8 to 20.5 mA with HART protocol FEI57C (PFM) The transmitter superimposes current pulses (PFM signal 60 to 2800 Hz) with a pulse width of approx. 100 s and a current strength of approx. 8 mA on the supply current (approx. 8 mA). Signal on alarm FEI50H Fault diagnosis can be called up as follows: Via the local display: Red LED Via the local display showing: Error symbol Plain text display Via the current output: 22 mA Via the digital interface (HART status error message) FEI57C Fault diagnosis can be called up as follows: Via the local display: Red LED Via the local display at the switching unit: silometer (FMX570, FMC671/672), Prolevel (FMC661/662) Linearization FEI50H The Liquicap M linearization function enables conversion of the measured value into any desired length or volume units. Linearization tables for volume calculation of horizontal cylindrical tanks and spherical tanks are pre-programmed. Any other tables with up to 32 value pairs can be input manually or semi-automatically. FEI57C With FEI57C, linearization takes place in the switching units.
22
Endress+Hauser
Power supply
Electrical connection Connection compartment Five housings are available: Standard Plastic housing F16 Stainless steel housing F15 Aluminum housing F17 Aluminum housing F13 Aluminum housing T13 (with separate connection compartment) X X X X X EEx ia X X X X X EEx d X Gas-tight process seal X X
Terminal assignment
2-wire, 4 to 20 mA with HART The twin-core connecting cable is connected to the screw terminals (conductor cross-section 0.5 to 2.5 mm) in the connection compartment at the electronic insert. If the superimposed communication signal (HART) is used, a shielded cable must be used and the shielding connected at the sensor and power supply. Protective circuits against reverse polarity, HFinfluences and overvoltage peaks are integrated (see TI241F "EMC test procedures").
1 2
+
PML
L00-FMI5xxxx-04-00-00-en-002
2-wire, PFM The twin-core, shielded connecting cable with a cable resistance of max. 50 per core is connected to the screw terminals (conductor cross-section 0.5 to 2.5 mm) in the connection compartment. The shielding must be connected at the sensor and power supply. Protective circuits against reverse polarity, HFinfluences and overvoltage peaks are integrated (see TI241F "EMC test procedures").
1 2
+
PML
L00-FMI5xxxx-04-00-00-en-003
Endress+Hauser
23
Connector
For the versions with a connector (M12 or 7/8"), the housing does not have to be opened to connect the signal line. PIN assignment for M12 connector (PROFIBUS PA standard, HART)
PIN 1
1 2 3 + 4 nc
2 3 4
L00-FMxxxxxx-04-00-00-yy-016
2 3 4
L00-FMxxxxxx-04-00-00-yy-017
+ 4
Supply voltage
All of the following voltages are terminal voltages directly at the device: FEI50H: 12.0 to 36 VDC (in the non-hazardous area) 12.0 to 30 VDC (in hazardous areas EEx ia) 14.4 to 30 VDC (in hazardous areas EEx d) FEI57C: 14.8 VDC from related supply unit e.g. FMC661 (* order stop 2006)
!
Cable entry
Note! Both electronic inserts have integrated reverse polarity protection. Cable gland: M20x1.5 (for EEx d only cable entry) Two cable glands are included in scope of delivery. Cable entry: G or NPT FEI50H Min. 40 mW, max. 800 mW FEI57C Max. 250 mW
Power consumption
24
Endress+Hauser
Current consumption
16 mA
PFM
8 mA
0 mA
t
L00-FMI5xxxx-05-05-xx-xx-005
Frequency: 60 to 2800 Hz
47 to 125 Hz: Uss = 200 mV (with 500 ) 500 Hz to 10 kHz: Ueff < 2.2 mV (with 500 )
Performance characteristics
Reference operating conditions Temperature = +20 C 5 C Pressure = 1013 mbar abs. 20 mbar Humidity = 65 % 20% Medium = water from mains (conductivity 180 S/cm Rod probe PFA: Probe length 1 m
Linearity: 0.5 % Reproducibility: 0.1 % Electronic insert < 0.06 % / 10 K related to the full scale value Separate housing Change in capacitance of connecting cable 0.015 pF/m per K
FEI50H 14 s (stable measured value after switch-on procedure) FEI57C 1.5 s (stable measured value after switch-on procedure)
FEI50H t1 0.3 s t1 0.5 s for operating mode SIL FEI57C t1 = 0.3 s Note! Observe integration time of switching unit
100 % 63 %
t1
L00-FMI5xxxx-05-05-xx-xx-009
Endress+Hauser
25
Integration time
FEI50H =1 s (factory setting) 0 to 60 s can be set. The integration time affects the speed at which the display and the current output react to changes in the level. Probe length < 2 m 5 mm 5 mm Probe length > 2 m Approx. 2 % Approx. 2 %
Accuracy of factory calibration Empty calibration (0 %) Full calibration (100 %) Medium conductivity 100 S/cm Minimum distance to container wall = 250 mm
Note! In an installed state, recalibration is only necessary if: The 0 % or the 100 % value have to be adjusted specifically for the customer. The liquid is not conductive. The distance from probe to tank wall is < 250 mm.
L3
100 %
L1
0%
L00-FMI5xxxx-15-05-xx-xx-002
Resolution
FEI50H Analog in % (4 to 20 mA) FMI51, FMI52: 0.03 % of set span (11 bit/2048 steps), 8 A The resolution of the electronics can be directly converted to units of length of the probe FMI51 or FMI52. e.g. active probe rod 1000 mm Resolution = 1000 mm/2048 = 0.48 mm FEI57C Zero frequency f0 60 Hz: Sensitivity of the electronic insert = 0.685 Hz/pF Entry in switching unit FMC671 under V3H5 and V3H6 or V7H5 and V7H6
26
Endress+Hauser
Human interface
Electronic inserts FEI50H Green LED ( operational status) Red LED ( fault message) Key (-) Key (+) Mode switch 1 : Operation 2 : Empty calibration 3 : Full calibration 4 : Measuring modes 5 : Measuring range 6 : Self-test 7 : Reset (factory settings) 8 : Upload sensor EEPROM 4 to 20 mA current pick-off, e.g. for full/empty calibration with multimeter. (No need to disconnect circuit!) Display connection
1 7 3 5
FEI50H
4...20mA
Display
L00-FMI5xxxx-07-05-xx-xx-000
FEI57C Green LED ( operational status) Red LED ( fault message) DIP switch, buildup (YES/NO) DIP switch, probe length (> 6 m/< 6 m)
FEI57C
PFM
Yes Build up No
>6m
Probe 6 m length
L00-FMI5xxxx-07-05-xx-xx-002
The measured value is displayed and Liquicap M is configured onsite by means of a graphic display. The menu guidance with integrated help texts ensures quick and safe commissioning. For accessing the display, the cover of the electronics compartment can also be opened in hazardous areas (EEx ia). FieldCare and ToF Tool are graphic operating programs for Endress+Hauser measuring devices which support remote configuration with documentation of the measuring point and also more in-depth analytical functions. Liquid crystal display (LCD display) Graphic display with operating keys
Display (optional)
360
Messwert
Mes Messwert
64.50
es
sw
64.50
. 64
+
50
er
L00-FMI5xxxx-07-05-xx-en-002
Endress+Hauser
27
Local operation
The display can be used to configure via 3 keys directly at the device. All device functions can be set via menu operation. The menu consists of function groups and functions. Application parameters can be read or set in the functions.
Label
Measure Value
Measure Value
64.50
+
64.50
Softkeys
+
Value Bargraph
Unit Position
main menu
Picklist
CX001
language
English Deutsch Franais
D0011
L00-FMIxxxxx-07-00-00-en-002
Operation with handheld terminal Field Communicator DXR375 The handheld terminal DXR375 can be used to set all device functions via menu operation.
8.7 m
Delete
HELP
SAVE
H
HELP
Page Up
SAVE
FMI51: LIC0001 GROUP SELECTION 1 2 3 4 5 BASIC SETUP SAFETY SETTINGS LINEARISATION EXTENDED CALIB. OUTPUT
Bksp
Delete
Delete
Page On
Bksp
DEF
#%&
ABC
1
Copy GHI
2
Paste JKL
3
Hot Key MNO
H
SAVE HOME
4
PQRS
5
Insert TUV
6
+ Hot Key W XY Z
FMI51: LIC0001 BASIC SETUP 1 2 3 4 5 MEASURED VALUE TANK SHAPE MEDIUM PROPERTY PROCESS COND. EMPTY CALIBR.
7
,()
8
_<>
9
+*/
Page Up Page On
Bksp
375
FIELD COMMUNICATOR
SAVE HOME
L00-FMI5xxxx-07-00-00-xx-007
!
28
Note! Further information on the HART handheld terminal is provided in the associated Operating Instructions which can be found in the carrying case for DXR375.
Endress+Hauser
Remote operation
HART can be used for Liquicap M remote operation. Settings can be made on site. Operation with ToF Tool ToF Tool is a graphic operating program for measuring devices from Endress+Hauser. It is used to support commissioning, data backup, signal analysis and documentation of the devices. The following operating systems are supported: WinNT4.0, Win2000 and WinXP. The ToF Tool supports the following functions: Configuration of transmitters in online operation Linearization table (creating, editing, importing and exporting) Loading and saving device data (upload/download) Documentation of the measuring point
L00-FMIxxxxx-20-00-00-en-003
Connection options: HART with Commubox FXA191, FXA195 Operation with FieldCare FieldCare is an FDT-based system asset management tool from Endress+Hauser. It can configure every intelligent field device in your system and helps you in managing these devices. The use of status information means that you also have a simple but effective tool for monitoring devices. Supports all Endress+Hauser devices Supports all third-party devices which support the FDT standard, e.g. drives, I/O systems, sensors etc. Ensures the full functionality of all devices with DTMs Offers general profile operation for third-party fieldbus devices without vendor DTM
Endress+Hauser
29
!
Liquicap M FMI51
Ordering information
Note! In this list, versions which are mutually exclusive are not marked.
10 Approval:
Non-hazardous area Non-hazardous area, WHG (German Water Resources Act) ATEX II 1/2 GD EEx ia IIC T6 ATEX II 1/2 GD EEx ia IIC T6, WHG ATEX II 1/2 GD EEx ia IIB T6 ATEX II 1/2 GD EEx ia IIB T6, WHG ATEX II 1/2 GD EEx ia IIC T6, XA, observe safety instructions (electrostatic charge)! J ATEX II 1/2 GD EEx ia IIC T6, WHG XA, observe safety instructions (electrostatic charge)! K ATEX II 1/2 G EEx ia IIC T6, WHG XA, observe safety instructions (electrostatic charge)! L ATEX II 1/2 G EEx d (ia) IIC T6, WHG XA, observe safety instructions (electrostatic charge)! M ATEX II 3 GD EEx nA II T6, WHG N CSA General Purpose, CSA C US P CSA/FM IS Cl. I, II, III Div. 1+2 Gr. A-G R CSA/FM XP Cl. I, II, III Div. 1+2 Gr. A-G S TIIS Ex ia IIC T3 T TIIS Ex d IIC T3 Y Special version, to be specified 1 NEPSI Ex ia IIC T6 2 NEPSI Ex d(ia) IIC T6 A B C D E F H
20
30
Endress+Hauser
30
50
Process Connection:
Threaded connection GCJ G , GDJ G , GEJ G 1, GGJ G 1, RCJ NPT , RDJ NPT , REJ NPT 1, RGJ NPT 1, 316L, 25 bar 316L, 25 bar 316L, 25 bar 316L, 100 bar 316L, 25 bar 316L, 25 bar 316L, 25 bar 316L, 100 bar Thread ISO228 Thread ISO228 Thread ISO228 Thread ISO228 Thread ANSI Thread ANSI Thread ANSI Thread ANSI
Hygiene connection GQJ G , 316L, 25 bar, EHEDG Accessories installation, welding neck GWJ G 1, 316L, 25 bar, EHEDG Accessories installation, welding neck MRJ DN50 PN40, 316L UPJ Universal adapter 44 mm 316L, 16 bar Tri-Clamp connection TCJ DN25 (1"), TJJ DN38 (1"), TDJ DN40-51 (2"), TNJ DN38 (1"), Tri-Clamp removable EN flanges B0J DN25 PN25/40 A, B1J DN32 PN25/40 A, B2J DN40 PN25/40 A, B3J DN50 PN25/40 A, CRJ DN50 PN25/40 B1, DRJ DN50 PN40 C, ERJ DN50 PN40 D, BSJ DN80 PN10/16 A, CGJ DN80 PN10/16 B1, DGJ DN80 PN16 C, EGJ DN80 PN16 D, BTJ DN100 PN10/16 A, CHJ DN100 PN10/16 B1, PTFE clad DN25 PN25/40, DN32 PN25/40, DN40 PN25/40, DN50 PN25/40, DN80 PN10/16, DN100 PN10/16,
EHEDG EHEDG
316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L
Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 C) Flange EN1092-1 (DIN2512 F) Flange EN1092-1 (DIN2512 N) Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 C) Flange EN1092-1 (DIN2512 F) Flange EN1092-1 (DIN2512 N) Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 C)
PTFE >316L PTFE >316L PTFE >316L PTFE >316L PTFE >316L PTFE >316L
Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527)
Endress+Hauser
31
50
Process Connection:
ANSI flanges ACJ 1" 150 lbs RF, ANJ 1" 300 lbs RF, AEJ 1" 150 lbs RF, AQJ 1" 300 lbs RF, AFJ 2" 150 lbs RF, ARJ 2" 300 lbs RF, AGJ 3" 150 lbs RF, ASJ 3" 300 lbs RF, AHJ 4" 150 lbs RF, ATJ 4" 300 lbs RF, AJJ 6" 150 lbs RF, AUJ 6" 300 lbs RF, PTFE clad 1" 150 lbs, 1" 300 lbs, 1" 150 lbs, 1" 300 lbs, 2" 150 lbs, 2" 300 lbs, 3" 150 lbs, 4" 150 lbs, 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5
PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L
Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5
JIS flanges KCJ 10K 25 RF, KEJ 10K 40 RF, KFJ 10K 50 RF, KGJ 10K 80 RF, KHJ 10K 100 RF, KRJ 20K 50 RF, PTFE clad 10K 25 RF, 10K 40 RF, 10K 50 RF, 10K 80 RF, 10K 100 RF,
Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220
PTFE >316L PTFE >316L PTFE >316L PTFE >316L PTFE >316L
Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220
60
Electronics; Output:
A B C V W Y FEI50H; 4 to 20 mA HART + display FEI50H; 4 to 20 mA HART FEI57C; 2-wire PFM Prepared for FEI5x + display, cover high, transparent Prepared for FEI5x, cover flat Special version, to be specified
70
Housing:
1 2 3 4 5 9 F15 316L F16 polyester F17 aluminum F13 aluminum + gas-tight process seal T13 aluminum + gas-tight process seal + separate connection compartment Special version, to be specified IP66, NEMA4X IP66, NEMA4X IP66, NEMA4X IP66, NEMA4X IP66, NEMA4X
80
Cable Entry:
A B C D E F Y Gland M20 (EEx d > thread M20) Thread G Thread NPT Thread NPT Plug M12 Plug 7/8" Special version, to be specified
32
Endress+Hauser
90
Type of Probe:
L4: 300 to 6000 mm/12 to 240 inch 1 Compact 2 2000 mm L4 cable > separate housing 3 ....mm L4 cable > separate housing 4 80 inch L4 cable > separate housing 5 ....inch L4 cable > separate housing 9 Special version, to be specified
100
Additional Option:
A B C D E F S Y Basic version Cleaned for silicone- free service* Metal probe rod surface refining** EN10204-3.1 (316L wetted parts), EN10204-3.1 (316L wetted parts), NACE MR0175 SIL declaration of conformity GL marine certificate Special version, to be specified
FMI51 Product designation * With this option, the complete device is cleaned for applications free from paint-wetting impairment substances ** With this option, the surface of the probe rod (316L) is passivated and acts as additional corrosion protection
Endress+Hauser
33
Liquicap M FMI52
10
Approval:
Non-hazardous area Non-hazardous area, WHG ATEX II 1/2 GD EEx ia IIB T6 ATEX II 1/2 GD EEx ia IIB T6, WHG ATEX II 1/2 GD EEx ia IIC T6, XA, observe safety instructions (electrostatic charge)! J ATEX II 1/2 GD EEx ia IIC T6, WHG XA, observe safety instructions (electrostatic charge)! K ATEX II 1/2 G EEx ia IIC T6, WHG XA, observe safety instructions (electrostatic charge)! L ATEX II 1/2 G EEx d (ia) IIC T6, WHG XA, observe safety instructions (electrostatic charge)! M ATEX II 3 GD EEx nA II T6, WHG N CSA General Purpose, CSA C US P CSA/FM IS Cl. I, II, III Div. 1+2 Gr. A-G R CSA/FM XP Cl. I, II, III Div. 1+2 Gr. A-G S TIIS Ex ia IIC T3 T TIIS Ex d IIC T3 Y Special version, to be specified 1 NEPSI Ex ia IIC T6 2 NEPSI Ex d(ia) IIC T6 A B E F H
20
30
50
Process Connection:
Threaded connection GDJ G , GEJ G 1, GGJ G 1, RDJ NPT , REJ NPT 1, RGJ NPT 1, 316L, 25 bar 316L, 25 bar 316L, 100 bar 316L, 25 bar 316L, 25 bar 316L, 100 bar Thread ISO228 Thread ISO228 Thread ISO228 Thread ANSI Thread ANSI Thread ANSI
Hygiene connection GWJ G 1 316L, 25 bar, EHEDG Accessories installation, welding neck MRJ DN50 PN40, 316L UPJ Universal adapter 44 mm 316L, 16 bar, EHEDG Tri-Clamp connection TCJ DN25 (1"), TJJ DN38 (1"), TDJ DN40-51 (2"), EN flanges B0J DN25 PN25/40 A, B1J DN32 PN25/40 A,
EHEDG EHEDG
316L 316L
34
Endress+Hauser
50
Process Connection:
B2J B3J CRJ DRJ ERJ BSJ CGJ DGJ EGJ BTJ CHJ DN40 PN25/40 A, DN50 PN25/40 A, DN50 PN25/40 B1, DN50 PN40 C, DN50 PN40 D, DN80 PN10/16 A, DN80 PN10/16 B1, DN80 PN16 C, DN80 PN16 D, DN100 PN10/16 A, DN100 PN10/16 B1, PTFE clad DN25 PN25/40, DN32 PN25/40, DN40 PN25/40, DN50 PN25/40, DN80 PN10/16, DN100 PN10/16, 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L 316L Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 C) Flange EN1092-1 (DIN2512 F) Flange EN1092-1 (DIN2512 N) Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 C) Flange EN1092-1 (DIN2512 F) Flange EN1092-1 (DIN2512 N) Flange EN1092-1 (DIN2527 B) Flange EN1092-1 (DIN2527 C)
PTFE >316L PTFE >316L PTFE >316L PTFE >316L PTFE >316L PTFE >316L
Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527) Flange EN1092-1 (DIN2527)
ANSI flanges ACJ 1" 150 lbs RF, ANJ 1" 300 lbs RF, AEJ 1" 150 lbs RF, AQJ 1" 300 lbs RF, AFJ 2" 150 lbs RF, ARJ 2" 300 lbs RF, AGJ 3" 150 lbs RF, ASJ 3" 300 lbs RF, AHJ 4" 150 lbs RF, ATJ 4" 300 lbs RF, AJJ 6" 150 lbs RF, AUJ 6" 300 lbs RF, PTFE clad 1" 150 lbs, 1" 300 lbs, 1" 150 lbs, 1" 300 lbs, 2" 150 lbs, 2" 300 lbs, 3" 150 lbs, 4" 150 lbs,
316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L 316/316L
Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5
PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L PTFE >316/316L
Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5 Flange ANSI B16.5
JIS flanges KCJ 10K 25 RF, KEJ 10K 40 RF, KFJ 10K 50 RF, KGJ 10K 80 RF, KHJ 10K 100 RF, KRJ 20K 50 RF,
Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220
PTFE clad 10K 25 RF, PTFE >316L 10K 40 RF, PTFE >316L 10K 50 RF, PTFE >316L 10K 80 RF, PTFE >316L 10K 100 RF, PTFE >316L Special version, to be specified
Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220 Flange JIS B2220
60
Electronics; Output:
A B C V W Y FEI50H; 4 to 20 mA HART + display FEI50H; 4 to 20 mA HART FEI57C; 2-wire PFM Prepared for FEI5x + display, Prepared for FEI5x, Special version, to be specified
Endress+Hauser
35
70
Housing:
1 2 3 4 5 9 F15 316L F16 polyester F17 aluminum F13 aluminum + gas-tight process seal T13 aluminum + gas-tight process seal + separate connection compartment Special version, to be specified IP66, NEMA4X IP66, NEMA4X IP66, NEMA4X IP66, NEMA4X IP66, NEMA4X
80
Cable Entry:
A B C D E F Y Gland M20 (EEx d > thread M20) Thread G Thread NPT Thread NPT Plug M12 Plug 7/8" Special version, to be specified
90
Type of Probe:
L4: 100 to 6000 mm/12 to 240 inch 1 Compact 2 2000 mm L4 cable > separate housing 3 ....mm L4 cable > separate housing 4 80 inch L4 cable > separate housing 5 ....inch L4 cable > separate housing 9 Special version, to be specified
100
Additional Option:
A Basic version D EN10204-3.1 (316L wetted parts), E EN10204-3.1 (316L wetted parts), NACE MR0175 F SIL declaration of conformity S GL marine certificate Y Special version, to be specified Inspection certificate Inspection certificate
FMI52
Product designation
36
Endress+Hauser
Accessories
Protective cover For F13 and F17 housing (only possible with flat cover!) Order number: TSP17090 Order number: 942901-0001 For intrinsically safe HART communication with ToF Tool/FieldCare via an RS232C interface or USB.
Shortening kit for FMI52 Commubox FXA191, FXA195 HART Surge arrester HAW569
Note! Both these versions can be screwed directly into the housing (M20x1.5). Surge arrester for limiting overvoltage in signal lines and components. The HAW562Z module can be used in hazardous areas.
S-Ableiter/Arrester
ENDRESS+HAUSER HAW569
HAW569-A1
Uc 34.8 V In 10 kA IL 500 mA
protected
L00-FMI5xxxx-03-05-xx-xx-009
Endress+Hauser
37
Order number: 52006262 Order number: 52010173 with 3.1 certificate Diameter D: 85 mm Height H: 12 mm Order number: 214880-0002 Order number: 52010174 with 3.1 certificate Diameter D: 65 mm Height H: 8 mm For flush-mounted Liquicap M installation with process connection UPJ Material: corrosion-resistant steel 1.4435 (AISI 316L) Replacement seal: Silicone O-ring (Set of 5 sealsFDA-listed) Order number: 52023572
52
30
D
L00-FMI5xxxx-06-05-xx-en-012
Order number: 52018765 with 3.1 certificate For flush-mounted Liquicap M installation with process connection GQJ (seal included in scope of delivery) Material: corrosion-resistant steel 1.4435 (AISI 316L) Weight: 0.13 kg Certificate: EHEDG Replacement seal: Silicone O-ring (5-piece set - FDA listed) Order number: 52021717
G ISO 228
50 0.4
L00-FTL5xxxx-06-05-xx-xx-026
Order number: 52001051 Order number: 52011896 with 3.1 certificate For flush-mounted Liquicap M installation with process connection GWJ (seal included in scope of delivery) Material: corrosion-resistant steel 1.4435 (AISI 316L) Weight: 0.19 kg Certificate: EHEDG Replacement seal: Silicone O-ring (5-piece set - FDA listed) Order number: 52014472
32
G1 ISO 228
60 0.4
L00-FTL5xxxx-06-05-xx-xx-020
Spare parts
Electronic insert FEI50H electronic insert 52028260 FEI57C electronic insert 52028261 Cover for housing without display Cover for aluminum housing F13: gray with sealing ring 52002698 Cover for stainless steel housing F15: with sealing ring 52027000 Cover for stainless steel housing F15: with clasp and sealing ring 52028268
38
41
Endress+Hauser
Cover for polyester housing F16, flat: gray with sealing ring 52025606 Cover for aluminum housing F17, flat: with sealing ring 52002699 Cover for aluminum housing T13, flat: gray with sealing ring/electronics compartment 52006903 Cover for aluminum housing T13, flat: gray with sealing ring/connection compartment 52007103 Cover for housing with display Cover for stainless steel housing F15: with sight glass, clasp and sealing ring 52028267 Cover for stainless steel housing F15: high, with sight glass and sealing ring 52028269 Cover for stainless steel housing F15: high, with sight glass, clasp and sealing ring 71005440 Cover for aluminum housing F13/F17: high, with sight glass and sealing ring 52028270 Cover for aluminum housing T13: high, with sight glass/electronics compartment for EEx d 52028271 Cover for polyester housing F16: high, with transparent housing and sealing ring 52025605 Display with holder Display with holder for electronic insert FEI50H 52028266 Seal set for stainless steel housing Seal set for stainless steel housing F15: with 5 sealing rings 52028179 Terminal module Terminal module 2-pin EEx d, RFI filter for T13 housing 71020804
!
Technical Information Operating Instructions
Supplementary Documentation
Note! This documentation is available on the product pages at www.endress.com Fieldgate FXA320, FXA520 TI369F/00/en Liquicap M FMI51, FMI52 (PFM) BA297F/00/en Liquicap M FMI51, FMI52 (HART) BA298F/00/en
Certificates
ATEX safety instructions Liquicap M FMI51, FMI52 ATEX II 1/2 G (EEx ia IIC/IIB T3 to T6), II 1/2 D IP65 T 85 C XA327F/00/a3 Liquicap M FMI51, FMI52 ATEX II 1/2 G (EEx d (ia) IIC/IIB T3 to T6) XA328F/00/a3
Endress+Hauser
39
Overfill protection DIBt (WHG) Liquicap M FMI51, FMI52 ZE265F/00/de Functional safety (SIL2) Liquicap M FMI51, FMI52 SD198F/00/en Control Drawings Liquicap M FMI51, FMI52 FM ZD220F/00/en Liquicap M FMI51, FMI52 CSA ZD221F/00/en Patents This product is protected by at least one of the patents listed below. Further patents are under development. DE 203 00 901 U1 DE 103 22 279, WO 2004 102 133, US 2005 003 9528 DE 203 13 695, WO 2005 025 015
Instruments International
Endress+Hauser Instruments International AG Kaegenstrasse 2 4153 Reinach Switzerland Tel. +41 61 715 81 00 Fax +41 61 715 25 00 www.endress.com info@ii.endress.com